Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-07-03 12:26:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30233.86 | 652.71 | 652.71 |
Net Site Energy | 30233.86 | 652.71 | 652.71 |
Total Source Energy | 91991.23 | 1985.98 | 1985.98 |
Net Source Energy | 91991.23 | 1985.98 | 1985.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1804.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1788.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2460.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 351.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2920.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 407.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 458.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5338.98 |
Humidification | 2349.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.98 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28429.06 | 1804.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8493.12 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1804.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1788.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2460.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 351.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2920.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 407.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 458.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5338.98 |
Humidification | General | 2349.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.98 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1804.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1788.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2460.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 351.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2920.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 407.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 458.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5338.98 |
Humidification | Unassigned | 2349.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.98 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.80 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 613.75 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.80 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 613.75 | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28429.057 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28429.057 | 100.00 |
Total On-Site and Utility Electric Sources | 28429.057 | 100.00 |
Total Electricity End Uses | 28429.057 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8493.12 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8493.12 | 100.00 |
Total Water End Uses | 8493.12 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 47.67 |
Time Setpoint Not Met During Occupied Cooling | 1764.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5899.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:39 | 23-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 26-JUN-15:09 |
Heating | 0.00 | 1529692.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 400299.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 330577.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44973.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46039.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 24597.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33572.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2104512.47 | 1529692.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1529692.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 400299.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 330577.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 44973.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 46039.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 24597.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 33572.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1956.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5662.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7792.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1111.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1290.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1452.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7440.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1426.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 90034.82 | 1956.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 122.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 160.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1943.74 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 122.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 160.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1943.74 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 6.12 | 0.345954 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.65 | 0.286012 | 0.243000 | 1.62 | 0.762699 | 0.500000 | 0.001332 | 0.000116 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 62.54 | 0.304144 | 0.259000 | 16.20 | 0.811050 | 0.500000 | 0.001253 | 0.003471 | 16.20 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.24 | 0.304670 | 0.259000 | 1.62 | 0.812452 | 0.500000 | 0.001251 | 0.000820 | 3.44 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.16 | 0.205659 | 0.175000 | 0.203218 | 0.548423 | 0.500000 | 0.001853 | 0.000123 | 0.514266 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.57 | 0.098121 | 0.083000 | 0.130187 | 0.300000 | 0.500000 | 0.003883 | 0.000087 | 0.365307 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.69 | 0.141163 | 0.120000 | 0.203021 | 0.376435 | 0.500000 | 0.002699 | 0.000144 | 0.604621 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.97 | 0.077953 | 0.066000 | 0.130306 | 0.300000 | 0.500000 | 0.004888 | 0.000066 | 0.277249 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.88 | 0.219507 | 0.187000 | 2.03 | 0.585353 | 0.500000 | 0.001736 | 0.001967 | 8.27 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.77 | 0.300000 | 0.500000 | 0.004151 | 0.001322 | 5.55 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.64 | 0.143538 | 0.122000 | 2.03 | 0.382768 | 0.500000 | 0.002654 | 0.001991 | 8.37 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.29 | 0.084151 | 0.072000 | 1.32 | 0.300000 | 0.500000 | 0.004528 | 0.001262 | 5.30 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.25 | 0.191769 | 0.163000 | 0.202993 | 0.511383 | 0.500000 | 0.001987 | 0.000255 | 1.07 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.68 | 0.091517 | 0.078000 | 0.131174 | 0.300000 | 0.500000 | 0.004163 | 0.000170 | 0.713300 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.81 | 0.131973 | 0.112000 | 0.202681 | 0.351928 | 0.500000 | 0.002887 | 0.000257 | 1.08 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.94 | 0.079460 | 0.068000 | 0.131708 | 0.300000 | 0.500000 | 0.004795 | 0.000166 | 0.695642 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13207.55 | 0.000116 | 266.25 | |
CORE_MID VAV BOX REHEAT COIL | 396809.74 | 0.003471 | 10011.66 | |
CORE_TOP VAV BOX REHEAT COIL | 93783.07 | 0.000820 | 2474.85 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14005.05 | 0.000123 | 369.47 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9946.01 | 0.000087 | 262.36 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16459.81 | 0.000144 | 434.16 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7553.99 | 0.000066 | 199.33 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 224883.32 | 0.001967 | 5929.99 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 151109.03 | 0.001322 | 3984.50 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 227605.04 | 0.001991 | 6001.70 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 144309.77 | 0.001262 | 3805.33 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29113.35 | 0.000255 | 767.57 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19397.98 | 0.000170 | 511.41 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 29412.84 | 0.000257 | 775.46 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18918.22 | 0.000166 | 498.77 | |
VAV_BOT WITH REHEAT HEATING COIL | 63846.42 | 0.000559 | 1031.66 | |
VAV_MID WITH REHEAT HEATING COIL | 523687.40 | 0.004581 | 8571.96 | |
VAV_TOP WITH REHEAT HEATING COIL | 53073.43 | 0.000464 | 876.55 | |
CAV_BAS HEATING COIL | 261617.33 | 0.000875 | 2620.43 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.599671 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.76 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.587272 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 30.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.52 | 2.28 | 13.05 | 2.84 | 11.16 | 11.16 | 0.300000 | 0.254455 | 11.16 |
VAV_MID WITH REHEAT | 62.56 | 22.89 | 125.11 | 41.26 | 104.36 | 104.36 | 0.300000 | 0.395324 | 104.36 |
VAV_TOP WITH REHEAT | 6.46 | 2.29 | 12.92 | 7.00 | 11.66 | 11.66 | 0.300000 | 0.600536 | 11.66 |
CAV_BAS | 0.000000 | 0.000000 | 6.12 | 1.20 | 6.12 | 6.12 | 1.00 | 0.196040 | 6.12 |
AIRLOOP DATACENTER BASEMENT | 30.17 | 30.17 | 30.17 | 30.17 | 30.17 | 30.17 | 1.00 | 0.999989 | 30.17 |
AIRLOOP DATACENTER BOT | 0.599671 | 0.599671 | 0.599671 | 0.599671 | 0.599671 | 0.599671 | 1.00 | 1.00 | 0.599671 |
AIRLOOP DATACENTER MID | 5.76 | 5.76 | 5.76 | 5.76 | 5.76 | 5.76 | 1.00 | 1.00 | 5.76 |
AIRLOOP DATACENTER TOP | 0.587272 | 0.587272 | 0.587272 | 0.587272 | 0.587272 | 0.587272 | 1.00 | 1.00 | 0.587272 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.16 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 104.36 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.66 | |
CAV_BAS_OA_CONTROLLER | 6.12 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 30.17 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.599671 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.76 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.587272 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.84 | 6.67 | 10.64 | 0.006999 | 0.006999 | 168707.14 | 0.004825 | 11.16 |
VAV_MID WITH REHEAT COOLING COIL | 26.02 | 6.67 | 10.64 | 0.006986 | 0.006986 | 1596970.15 | 0.045673 | 104.36 |
VAV_TOP WITH REHEAT COOLING COIL | 25.73 | 6.67 | 10.64 | 0.006996 | 0.006996 | 175013.71 | 0.005005 | 11.66 |
CAV_BAS COOLING COIL | 26.03 | 6.67 | 10.61 | 0.007097 | 0.007097 | 93882.88 | 0.002685 | 6.12 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.16 |
VAV_MID WITH REHEAT FAN | 104.36 |
VAV_TOP WITH REHEAT FAN | 11.66 |
CAV_BAS FAN | 6.12 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004825 | 0.000099 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000559 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.045673 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004581 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005005 | 0.000095 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000464 | |
CAV_BAS_COOLC_CONTROLLER | 0.002685 | 0.000177 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 30.17 | 547101.36 | 286714.26 | 0.013398 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.599671 | 10569.69 | 5595.76 | 0.000259 |
AIRLOOP DATACENTER MID COOLING COIL | 5.76 | 101528.95 | 53741.64 | 0.002486 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.587272 | 10357.81 | 5482.06 | 0.000254 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 30.17 | 30.17 | 30.17 | 30.17 | 547101.36 | 547101.36 | 19243.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.599671 | 0.599671 | 0.599671 | 0.599671 | 10569.69 | 10569.69 | 888.99 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.76 | 5.76 | 5.76 | 5.76 | 101528.95 | 101528.95 | 8889.90 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.587272 | 0.587272 | 0.587272 | 0.587272 | 10357.81 | 10357.81 | 888.99 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 30.17 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.599671 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.76 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.587272 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 30.17 | 547101.36 | 0.013398 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.599671 | 10569.69 | 0.000259 |
AIRLOOP DATACENTER MID HEATING COIL | 5.76 | 101528.95 | 0.002486 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.587272 | 10357.81 | 0.000254 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 19243.92 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 888.99 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8889.90 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 888.99 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000201 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.058189 | 9406.35 | |
HEATSYS1 PUMP | 0.018696 | 5574.81 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.058189 | 6.98 |
HEATSYS1 | 0.018696 | 2.24 |
COOLSYS1_SUPPLY | 0.058189 | 6.98 |
SINGLE WATER PLANT LOOP | 0.016397 | 1.97 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.058189 | 0.058189 | 244246.56 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2137122.03 | 2137122.03 | 0.018696 |
CENTRAL BOILER | 675433.45 | 659607.45 | 0.016397 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.029094 | 3256.17 |
COOLSYS1 CHILLER2 PUMP | 0.029094 | 3256.17 |
PLANT CIRC PUMP | 0.016397 | 4140.76 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.058189 | 0.029513 | 1031929.40 | 1031928.54 | 0.053039 |
COOLSYS1 CHILLER2 | 0.058189 | 0.029513 | 1031929.40 | 1031928.54 | 0.053039 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.016397 | 162814.29 | 82425.10 | 81407.15 | 7004.20 | 49455.06 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.106078 | 12.73 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.106078 | 26002.60 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 49.06 | 1236769.54 | 9.81 | 154596.19 |
TOWERWATERSYS COOLTOWER 2 | 49.06 | 1236769.54 | 9.81 | 154596.19 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.053512 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9150E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9173E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6176E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6195E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7668E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7683E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6225E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6233E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9678E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1271E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6627E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8041E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8055E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9201E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6441E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6991E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1699 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5683E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1928 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7298E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1168 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7096E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7407E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6489E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9681E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1265E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6627E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8024E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8056E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9201E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6446E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7007E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9147E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9170E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6173E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6192E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7666E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7681E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6224E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6232E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6847E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9937E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3569E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6956E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1630E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2961E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4838E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5217E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2004E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0611E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6770E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7327E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0938E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5379E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9359E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8463E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5847E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6949E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2265E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3061E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1201E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1499E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4839E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5223E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7666E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7687E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3455E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3472E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0736E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0749E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6225E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6233E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8146E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9409E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3843E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4835E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1045E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1734E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6447E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7008E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4630E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3583E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4141E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7820E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0836E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1996E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7407E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6484E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8137E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9372E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3838E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4812E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1045E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1735E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6441E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6992E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7665E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7686E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3454E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3471E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0736E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0748E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6224E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6232E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6710E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7806E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3351E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4144E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1869E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2171E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4840E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5224E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3503E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1211E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8645E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8079E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2170E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5874E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9359E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8463E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7742E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0962E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4697E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8249E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2301E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3652E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4837E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5217E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1641 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1151 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1797 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1288 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1285 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9161E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8052E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8715E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.4114E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4212E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.8258E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0172E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2447E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7599E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9539E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9044E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5358E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.6906E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.3483E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9041E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9878E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1763E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8053E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8710E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.5811E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5041E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0381E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.1213E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3828E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8255E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9539E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9044E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1641 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1153 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1798 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1291 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1287 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9330E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8177E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8779E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.4161E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4278E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.8311E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0234E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2558E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7679E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9663E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9108E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5361E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.6948E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.3491E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9074E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9941E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1804E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8177E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8774E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.5860E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5109E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0437E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.1278E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3942E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8336E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9663E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9108E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 68805.56632 | 68805.56632 | 6.12198 | 6.12198 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 74742.89432 | 74742.89432 | 6.65022 | 6.65022 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 703035.47388 | 703035.47388 | 62.53768 | 62.53768 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 264429.91880 | 264429.91880 | 13.76409 | 13.76409 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 69554.86839 | 69554.86839 | 6.24297 | 6.24297 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 65655.77565 | 65655.77565 | 3.44150 | 3.44150 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12938.10554 | 12938.10554 | 1.16125 | 1.16125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 9803.37641 | 9803.37641 | 0.51427 | 0.51427 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17476.00507 | 17476.00507 | 1.56852 | 1.56852 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.82267 | 5.46148E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 6961.21752 | 6961.21752 | 0.36531 | 0.36531 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18849.84394 | 18849.84394 | 1.69184 | 1.69184 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.16000 | 5.47412E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 11519.45849 | 11519.45849 | 0.60462 | 0.60462 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21997.50704 | 21997.50704 | 1.97434 | 1.97434 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5289.22404 | 5289.22404 | 0.27725 | 0.27725 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 121219.23971 | 121219.23971 | 10.87985 | 10.87985 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 157350.06107 | 157350.06107 | 8.26604 | 8.26604 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 186830.66355 | 186830.66355 | 16.76849 | 16.76849 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 105727.28174 | 105727.28174 | 5.55469 | 5.55469 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 185380.96802 | 185380.96802 | 16.63850 | 16.63850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 159252.83208 | 159252.83208 | 8.36625 | 8.36625 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 203773.63867 | 203773.63867 | 18.28916 | 18.28916 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 100973.58777 | 100973.58777 | 5.30440 | 5.30440 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13875.37557 | 13875.37557 | 1.24536 | 1.24536 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 20367.34600 | 20367.34600 | 1.07051 | 1.07051 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18737.31847 | 18737.31847 | 1.68171 | 1.68171 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13570.35934 | 13570.35934 | 0.71330 | 0.71330 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20162.70447 | 20162.70447 | 1.80966 | 1.80966 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 20576.73098 | 20576.73098 | 1.08153 | 1.08153 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 21580.45391 | 21580.45391 | 1.93689 | 1.93689 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13234.90869 | 13234.90869 | 0.69564 | 0.69564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8470.79537 | 8470.79537 | 0.59967 | 0.59967 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81342.60152 | 81342.60152 | 5.75850 | 5.75850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8295.63238 | 8295.63238 | 0.58727 | 0.58727 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370551.95267 | 426134.74557 | 26.23203 | 30.16684 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 20.43200 | 5.45503E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | -17.90000 | 9.55238E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 140058.29 | 11.15824 | 11.15824 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 61897.22 | 2.83927 | 2.83927 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1290927.52 | 104.35862 | 104.35862 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 611158.49 | 41.25548 | 41.25548 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 147775.46 | 11.66038 | 11.66038 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 61186.23 | 7.00248 | 7.00248 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 03:40:00 |
7 | CAV_BAS | Cooling | Sensible | 70454.92 | 6.12198 | 6.12198 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 68251.22 | 1.20016 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422552.69 | 30.16716 | 30.16716 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 19243.92 | 0.33839 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8385.68 | 0.59967 | 0.59967 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80534.44 | 5.75850 | 5.75850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8889.90 | 0.15632 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8216.19 | 0.58727 | 0.58727 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 6.12198 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.34595 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.65022 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28601 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61600 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76270 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33211E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15545E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61600 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13207.55260 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15545E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 266.25389 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 62.53768 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30414 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.19726 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81105 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25270E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.47146E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.19726 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 396809.74356 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.47146E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10011.66360 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.24297 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30467 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61693 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81245 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25053E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.20455E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.44150 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 93783.07223 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.20455E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2474.85033 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16125 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20566 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17500 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20322 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54842 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85258E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22522E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51427 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14005.05092 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22522E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 369.47144 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56852 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.81212E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.30000E-002 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13019 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.88295E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.70120E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36531 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9946.00857 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.70120E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 262.35943 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.69184 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14116 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20302 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37644 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69900E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43998E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60462 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16459.81447 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43998E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 434.16045 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97434 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.79528E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 6.60000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13031 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.88757E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.60856E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27725 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7553.98765 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.60856E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 199.32813 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.87985 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21951 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18700 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03453 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58535 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73571E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96738E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.26604 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 224883.32229 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96738E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5929.98546 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.76849 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.15113E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32197E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.55469 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 151109.02861 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32197E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3984.49501 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.63850 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14354 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12200 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02990 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38277 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65435E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99119E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.36625 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 227605.03674 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99119E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6001.70116 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.28916 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.41510E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.20000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31682 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.52758E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26248E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.30440 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 144309.76902 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26248E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3805.32587 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24536 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19177 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16300 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20299 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51138 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98677E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.54696E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.07051 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29113.34742 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.54696E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 767.56805 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.68171 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.15168E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.80000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13117 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.16317E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69702E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71330 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19397.98016 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69702E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 511.41424 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80966 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13197 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20268 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35193 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88695E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.57316E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08153 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29412.84170 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.57316E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 775.45963 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.93689 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.94599E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 6.80000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13171 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.79487E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65505E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69564 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18918.22457 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65505E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 498.77114 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.59967 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.75850 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58727 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 30.16684 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.52308 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28274 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.04616 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.83927 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.15824 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.15824 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.25445 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 62.55683 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.88645 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 125.11367 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 41.25548 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 104.35862 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 104.35862 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39532 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.45829 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28549 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.91659 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.00248 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.66038 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.66038 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.60054 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.12198 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.12198 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.12198 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.19604 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 30.16684 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.16684 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 30.16684 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.16684 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 30.16716 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 30.16716 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.59967 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.59967 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.59967 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.59967 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.59967 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.59967 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.75850 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.75850 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.75850 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.75850 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.75850 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.75850 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58727 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58727 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58727 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58727 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58727 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.58727 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.15824 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 104.35862 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.66038 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.12198 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 30.16716 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.59967 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.75850 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.58727 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.15824 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.83672 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63949 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.99933E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.99933E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 168707.14228 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.82500E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.15824 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 63846.41852 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.58556E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1031.66350 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.15824 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.82500E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.86923E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.58556E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 104.35862 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.02117 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63944 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.98624E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.98624E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1596970.15268 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.56731E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 104.35862 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 523687.40168 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.58145E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8571.95667 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 104.35862 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.56731E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.04260E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.58145E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.66038 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.72598 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.63947 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.99608E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.99608E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 175013.70941 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.00537E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.66038 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53073.42968 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64310E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 876.54521 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.66038 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.00537E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.51359E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.64310E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.12198 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.02576 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.61432 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09724E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09724E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 93882.88007 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.68504E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.12198 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 261617.33069 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2620.42996 |
350 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.12198 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.68504E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.77350E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 30.16716 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 30.16716 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 547101.36128 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 286714.26247 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.33985E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 30.16716 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 30.16716 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 30.16716 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 30.16716 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 547101.36128 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 547101.36128 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 19243.92393 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 30.16716 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 30.16716 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 547101.36128 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.33985E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 19243.92393 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.00568E-004 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.59967 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59967 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10569.68930 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5595.75788 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.58851E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.59967 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.59967 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.59967 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.59967 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10569.68930 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10569.68930 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.59967 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59967 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10569.68930 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.58851E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.75850 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.75850 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 101528.95289 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 53741.64002 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48644E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.75850 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.75850 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.75850 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.75850 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 101528.95289 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 101528.95289 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8889.89563 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.75850 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.75850 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 101528.95289 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48644E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8889.89563 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58727 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58727 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10357.80927 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5482.05975 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53662E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58727 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58727 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58727 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58727 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10357.80927 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10357.80927 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58727 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58727 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10357.80927 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53662E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.81886E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9406.34958 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.81886E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.98263 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.81886E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.81886E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 244246.56476 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.86965E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.24358 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.86965E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5574.80937 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2137122.03038 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2137122.03000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.86965E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.81886E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.98263 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.90943E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3256.16652 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.90943E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3256.16652 |
456 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.81886E-002 |
457 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.95131E-002 |
458 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1031929.40329 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1031928.53500 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.30391E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.81886E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.95131E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1031929.40329 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1031928.53500 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.30391E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.63974E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.96769 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.63974E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 4140.75650 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.63974E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 162814.29305 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 82425.09554 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 81407.14653 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 49455.05732 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 675433.44695 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 659607.45000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.63974E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10608 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.72939 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10608 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 26002.59864 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 49.05793 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1236769.53685 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.81159 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 154596.19211 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 49.05793 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1236769.53685 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.81159 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 154596.19211 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.35125E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.35125E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 12525.54 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 376015.04 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 88901.88 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13275.38 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9427.62 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15601.77 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7160.72 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 213148.34 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 143222.93 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 215727.66 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 136779.30 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 27593.28 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 18385.10 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 27877.11 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17930.44 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 47319.69 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 398790.09 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 41166.63 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94850.22 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 213528.30 | 143636.68 | 69891.62 | 0.67 | 29956.94 | 303.84 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2009720.72 | 1347741.62 | 661979.10 | 0.67 | 280331.67 | 2843.28 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 222274.17 | 149803.85 | 72470.32 | 0.67 | 31294.89 | 317.41 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 118179.70 | 79182.90 | 38996.80 | 0.67 | 16535.66 | 167.71 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6952099663E-003 | 1.3106812784E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1244076908 | 0.1985025850 | Pass | Pass | 0.1964361858 | 0.4158162147 | Pass | Fail |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.8643149166E-002 | 9.7614999859E-002 | Pass | Pass | 0.1469792878 | 0.3535014221 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.9865647913E-002 | 4.2088042604E-002 | Pass | Pass | 0.4098745213 | 0.4881009826 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.2028615394E-002 | 0.1235774205 | Pass | Pass | 0.1810896909 | 0.3820704091 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1595398850 | 0.2759852842 | Pass | Pass | 0.1861747917 | 0.3982743219 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3771297327 | 0.7045287404 | Pass | Pass | 0.1976780829 | 0.4287555629 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1364600094 | 0.2437711536 | Pass | Pass | 0.1892760751 | 0.4064488065 | Pass | Fail |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.1535405666E-002 | 4.5714187677E-002 | Pass | Pass | 0.1470553405 | 0.3526767074 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1246826716 | 0.1669228533 | Pass | Pass | 0.1504386963 | 0.3613653021 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3878495549 | 0.6750426092 | Pass | Pass | 0.1581865238 | 0.3888454602 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1053084665 | 0.1481068339 | Pass | Pass | 0.1457475927 | 0.3463752978 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2298724936 | 0.2885356875 | Pass | Pass | 37.5265665156 | 156.6802426474 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1797259572 | 0.2057335240 | Pass | Pass | 54.6527608155 | 541.7663681765 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2832608051 | 0.3530371500 | Pass | Pass | 0.6619443191 | 2.8775367576 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1337651916 | 0.1345663488 | Pass | Pass | 4.1785168372 | 39.0327848431 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.4580155187E-002 | 3.6731499293E-002 | Pass | Pass | 0.7249602595 | 2.7783175376 | Fail | Fail |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7426751304E-002 | 6.5087878054E-002 | Pass | Pass | 0.2110055943 | 0.6185361169 | Pass | Fail |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1030696546 | 8.3633211997E-002 | Pass | Pass | 0.4970831972 | 0.8982145750 | Pass | Fail |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.3855875064E-006 | 7.3801079157E-006 | Pass | Pass | 6.8965447516E-003 | 1.0199136393E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8082476231E-006 | 9.0103619374E-006 | Pass | Pass | 0.1769727281 | 0.4218824370 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.3029236593E-002 | 4.3929031655E-002 | Pass | Pass | 0.1504162727 | 0.9443909330 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.4463620959E-005 | 3.4764055876E-005 | Pass | Pass | 9.4899570846E-005 | 1.0995356040E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7862.02 | 92.05 | 0.00 | 28227.12 | 13119.30 | 49300.48 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.47 | 0.0000 | Y | 10.67 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.42 | 0.0000 | Y | 6.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.13 | 0.0000 | Y | 10.53 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.11 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.43 | 0.0000 | Y | 106.51 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.39 | 0.0000 | Y | 68.54 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.11 | 0.0000 | Y | 105.26 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.09 | 0.0000 | Y | 67.78 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.43 | 0.0000 | Y | 10.65 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.39 | 0.0000 | Y | 6.85 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.11 | 0.0000 | Y | 10.53 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.09 | 0.0000 | Y | 6.78 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 775.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.26 | 42.26 | 105.29 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.67 | 62.97 | 11.70 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.67 | 46.88 | 234.03 | |
Exterior Lighting Total | 40855.88 | 351.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2028307.21 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2137122.03 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1031928.54 | 5.17 | 1028434.08 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1031928.54 | 5.17 | 1028434.08 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 678528.57 | |||||
CENTRAL BOILER | Boiler:HotWater | 659607.45 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1236769.54 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1236769.54 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 168707.14 | 213528.30 | 143636.68 | 69891.62 | 0.67 | - | 29956.94 | 303.84 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1596970.15 | 2009720.72 | 1347741.62 | 661979.10 | 0.67 | - | 280331.67 | 2843.28 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 175013.71 | 222274.17 | 149803.85 | 72470.32 | 0.67 | - | 31294.89 | 317.41 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 93882.88 | 118179.70 | 79182.90 | 38996.80 | 0.67 | - | 16535.66 | 167.71 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 547101.36 | 286714.26 | 260387.10 | 0.52 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10569.69 | 5595.76 | 4973.93 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 101528.95 | 53741.64 | 47787.31 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10357.81 | 5482.06 | 4875.75 | 0.53 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13207.55 | 12525.54 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 396809.74 | 376015.04 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 93783.07 | 88901.88 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14005.05 | 13275.38 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9946.01 | 9427.62 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16459.81 | 15601.77 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7553.99 | 7160.72 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 224883.32 | 213148.34 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 151109.03 | 143222.93 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 227605.04 | 215727.66 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 144309.77 | 136779.30 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29113.35 | 27593.28 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19397.98 | 18385.10 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29412.84 | 27877.11 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 18918.22 | 17930.44 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 63846.42 | 47319.69 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 523687.40 | 398790.09 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 53073.43 | 41166.63 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94850.22 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 547101.36 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10569.69 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 101528.95 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10357.81 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 19243.92 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8889.90 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.16 | 23984.24 | 2149.46 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 104.36 | 224315.15 | 2149.46 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.66 | 25063.57 | 2149.46 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.12 | 13314.63 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 30.17 | 49544.49 | 1642.33 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 671.70 | 1120.11 | 1.00 | 1.53 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.76 | 6450.15 | 1120.11 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.59 | 657.81 | 1120.11 | 1.00 | 1.54 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.058189 | 9406.35 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.018696 | 5574.81 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029094 | 3256.17 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029094 | 3256.17 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.016397 | 4140.76 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.106078 | 26002.60 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 68805.57 | 68805.57 | 24.76 | 6.122 | 6.122 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00751 | 22.95 | 0.00546 | 1.200 | 0.00 |
CORE_BOTTOM | 74742.89 | 74742.89 | 29.94 | 6.650 | 6.650 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 22.95 | 0.00546 | 1.078 | 0.00 |
CORE_MID | 703035.47 | 703035.47 | 281.65 | 62.538 | 62.538 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00744 | 22.95 | 0.00546 | 10.778 | 0.00 |
CORE_TOP | 69554.87 | 69554.87 | 27.87 | 6.243 | 6.243 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00744 | 33.90 | 0.00548 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12938.11 | 12938.11 | 41.28 | 1.161 | 1.161 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00728 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17476.01 | 17476.01 | 86.53 | 1.569 | 1.569 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 24.00 | 24.00 | 0.00713 | 24.82 | 0.00546 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18849.84 | 18849.84 | 60.14 | 1.692 | 1.692 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00719 | 33.16 | 0.00547 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21997.51 | 21997.51 | 108.91 | 1.974 | 1.974 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00711 | 32.03 | 0.00547 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 121219.24 | 121219.24 | 386.77 | 10.880 | 10.880 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00728 | 33.90 | 0.00548 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 186830.66 | 186830.66 | 925.02 | 16.768 | 16.768 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00712 | 25.76 | 0.00546 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 185380.97 | 185380.97 | 591.48 | 16.638 | 16.638 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00718 | 33.41 | 0.00547 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 203773.64 | 203773.64 | 1008.90 | 18.289 | 18.289 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00711 | 31.83 | 0.00547 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13875.38 | 13875.38 | 44.27 | 1.245 | 1.245 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00724 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18737.32 | 18737.32 | 92.77 | 1.682 | 1.682 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00711 | 26.18 | 0.00546 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20162.70 | 20162.70 | 64.33 | 1.810 | 1.810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00716 | 33.53 | 0.00547 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 21580.45 | 21580.45 | 106.85 | 1.937 | 1.937 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00710 | 31.83 | 0.00547 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8470.80 | 8470.80 | 233.98 | 0.600 | 0.600 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81342.60 | 81342.60 | 2246.86 | 5.759 | 5.759 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8295.63 | 8295.63 | 229.14 | 0.587 | 0.587 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370551.95 | 426134.75 | 543.76 | 26.232 | 30.167 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 20.43 | 0.00546 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 23.79 | 0.00096 | -17.90 | 0.00096 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 17.60 | 21.25 | 0.00096 | -17.90 | 0.00096 | 1.078 | 0.00 |
CORE_MID | 264429.92 | 264429.92 | 105.94 | 13.764 | 13.764 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 10.778 | 0.00 |
CORE_TOP | 65655.78 | 65655.78 | 26.30 | 3.441 | 3.441 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 9803.38 | 9803.38 | 31.28 | 0.514 | 0.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 6961.22 | 6961.22 | 34.47 | 0.365 | 0.365 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11519.46 | 11519.46 | 36.75 | 0.605 | 0.605 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5289.22 | 5289.22 | 26.19 | 0.277 | 0.277 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 157350.06 | 157350.06 | 502.05 | 8.266 | 8.266 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 105727.28 | 105727.28 | 523.47 | 5.555 | 5.555 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 159252.83 | 159252.83 | 508.11 | 8.366 | 8.366 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 100973.59 | 100973.59 | 499.93 | 5.304 | 5.304 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20367.35 | 20367.35 | 64.99 | 1.071 | 1.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13570.36 | 13570.36 | 67.19 | 0.713 | 0.713 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20576.73 | 20576.73 | 65.65 | 1.082 | 1.082 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13234.91 | 13234.91 | 65.53 | 0.696 | 0.696 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -17.90 | 0.00096 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 18.00 | 25.42 | 0.00531 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 22.80 | 0.00188 | -17.90 | 0.00096 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.60 | 0.00161 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 18.00 | 27.00 | 0.00700 | -17.90 | 0.00096 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.16 | 11.16 | 2.84 | 2.84 | 11.1582 | 2.8393 | 11.1582 | 0.2545 | 0.3000 |
VAV_MID WITH REHEAT | 104.36 | 104.36 | 41.26 | 41.26 | 104.3586 | 41.2555 | 104.3586 | 0.3953 | 0.3000 |
VAV_TOP WITH REHEAT | 11.66 | 11.66 | 7.00 | 7.00 | 11.6604 | 7.0025 | 11.6604 | 0.6005 | 0.3000 |
CAV_BAS | 6.12 | 6.12 | 1.20 | 1.20 | 6.1220 | 1.2002 | 6.1220 | 0.1960 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 30.17 | 30.17 | 0.34 | 0.34 | 30.1672 | 30.1668 | 30.1672 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.60 | 0.60 | 0.02 | 0.02 | 0.5997 | 0.5997 | 0.5997 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.76 | 5.76 | 0.16 | 0.16 | 5.7585 | 5.7585 | 5.7585 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.59 | 0.59 | 0.02 | 0.02 | 0.5873 | 0.5873 | 0.5873 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13207.553 | 13207.553 | 1.616003 | 0.00011555 | 266.254 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 13207.55 | 13207.55 | 1.616003 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 13256.25 | 13256.25 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 396809.744 | 396809.744 | 16.197260 | 0.00347146 | 10011.664 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 396809.74 | 396809.74 | 16.197260 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 264429.92 | 0.00 | 398040.69 | 398040.69 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 93783.072 | 93783.072 | 3.441500 | 0.00082046 | 2474.850 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 93783.07 | 93783.07 | 3.441500 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 65655.78 | 0.00 | 94101.87 | 94101.87 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14005.051 | 14005.051 | 0.514266 | 0.00012252 | 369.471 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14005.05 | 14005.05 | 0.514266 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00785210 | 41.2146 | 9803.38 | 0.00 | 14051.87 | 14051.87 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9946.009 | 9946.009 | 0.365307 | 0.00008701 | 262.359 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9946.01 | 9946.01 | 0.365307 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787539 | 41.3352 | 6961.22 | 0.00 | 9979.05 | 9979.05 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16459.814 | 16459.814 | 0.604621 | 0.00014400 | 434.160 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16459.81 | 16459.81 | 0.604621 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789493 | 41.4363 | 11519.46 | 0.00 | 16514.33 | 16514.33 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7553.988 | 7553.988 | 0.277249 | 0.00006609 | 199.328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7553.99 | 7553.99 | 0.277249 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776382 | 40.7575 | 5289.22 | 0.00 | 7579.56 | 7579.56 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 224883.322 | 224883.322 | 8.266040 | 0.00196738 | 5929.985 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 224883.32 | 224883.32 | 8.266040 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784618 | 41.1844 | 157350.06 | 0.00 | 225615.51 | 225615.51 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 151109.029 | 151109.029 | 5.554695 | 0.00132197 | 3984.495 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 151109.03 | 151109.03 | 5.554695 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784791 | 41.1934 | 105727.28 | 0.00 | 151600.12 | 151600.12 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 227605.037 | 227605.037 | 8.366245 | 0.00199119 | 6001.701 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 227605.04 | 227605.04 | 8.366245 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784816 | 41.1946 | 159252.83 | 0.00 | 228345.69 | 228345.69 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 144309.769 | 144309.769 | 5.304403 | 0.00126248 | 3805.326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 144309.77 | 144309.77 | 5.304403 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00784019 | 41.1534 | 100973.59 | 0.00 | 144779.60 | 144779.60 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 29113.347 | 29113.347 | 1.070506 | 0.00025470 | 767.568 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29113.35 | 29113.35 | 1.070506 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00785380 | 41.2241 | 20367.35 | 0.00 | 29207.22 | 29207.22 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 19397.980 | 19397.980 | 0.713300 | 0.00016970 | 511.414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19397.98 | 19397.98 | 0.713300 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00785371 | 41.2237 | 13570.36 | 0.00 | 19460.46 | 19460.46 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 29412.842 | 29412.842 | 1.081532 | 0.00025732 | 775.460 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29412.84 | 29412.84 | 1.081532 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00785526 | 41.2317 | 20576.73 | 0.00 | 29507.65 | 29507.65 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 18918.225 | 18918.225 | 0.695642 | 0.00016550 | 498.771 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18918.22 | 18918.22 | 0.695642 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00785013 | 41.2052 | 13234.91 | 0.00 | 18979.19 | 18979.19 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 168707.142 | -999.000 | 11.158238 | 0.00482500 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 168707.14 | 168707.14 | 11.158238 | 25.84 | 13.63 | 0.00699933 | 10.64 | 7.86 | 0.00699933 | 33.90 | 0.00547527 | 15.07 | 18.1973 | 24.00 | 0.00734673 | 32.1630 | 121867.63 | 0.00 | 142181.12 | 142181.12 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 63846.419 | 63846.419 | 3.347471 | 0.00055856 | 1031.664 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 63846.42 | 63846.42 | 3.347471 | -6.62 | -7.04 | 0.00240660 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 60.6577 | 20.88 | 0.00565692 | 30.0221 | 25950.07 | 0.00 | 57215.36 | 57215.36 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1596970.153 | -999.000 | 104.358616 | 0.04567314 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1596970.15 | 1596970.14 | 104.358616 | 26.02 | 13.69 | 0.00698624 | 10.64 | 7.84 | 0.00698624 | 33.90 | 0.00547527 | 15.07 | 19.4579 | 24.00 | 0.00737410 | 32.2814 | 1107593.44 | 0.00 | 1346117.68 | 1346117.68 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 523687.402 | 523687.402 | 31.307585 | 0.00458145 | 8571.957 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 523687.40 | 523687.40 | 31.307585 | -4.23 | -4.23 | 0.00337819 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 64.8597 | 18.06 | 0.00777133 | 48.9819 | 253474.16 | 0.00 | 482367.49 | 482367.49 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 175013.709 | -999.000 | 11.660379 | 0.00500537 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 175013.71 | 175013.71 | 11.660379 | 25.73 | 13.59 | 0.00699608 | 10.64 | 7.85 | 0.00699608 | 33.90 | 0.00547527 | 15.07 | 17.4137 | 24.00 | 0.00731743 | 32.0361 | 129684.69 | 0.00 | 147317.08 | 147317.08 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 53073.430 | 53073.430 | 3.498114 | 0.00046431 | 876.545 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 03:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 53073.43 | 53073.43 | 3.498114 | -2.65 | -2.65 | 0.00380462 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 58.0456 | 16.11 | 0.00778145 | 55.4856 | 23343.84 | 0.00 | 49802.69 | 49802.69 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 93882.880 | -999.000 | 6.121984 | 0.00268504 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 93882.88 | 93882.88 | 6.121984 | 26.03 | 13.78 | 0.00709724 | 10.61 | 7.95 | 0.00709724 | 33.16 | 0.00547412 | 14.83 | 19.6040 | 24.00 | 0.00755846 | 33.0792 | 60426.98 | 0.00 | 80027.64 | 80027.64 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.743149 | 0.00087484 | 2620.430 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.743149 | -3.51 | -7.65 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 32.0627 | 23.89 | 0.00095524 | 4.2536 | 0.00 | 0.00 | 100031.84 | 100031.84 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 547101.361 | 286714.262 | 30.167161 | 0.01339848 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 464998.30 | 463754.36 | -999.0 | 28.78 | 14.64 | 0.00702469 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | -999.0000 | 27.00 | 0.00704228 | 25.8136 | 370167.70 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10569.689 | 5595.758 | 0.599671 | 0.00025885 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8936.04 | 8893.43 | -999.0 | 28.20 | 14.47 | 0.00704301 | 12.80 | 8.76 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | -999.0000 | 27.00 | 0.00708519 | 25.9672 | 8470.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 101528.953 | 53741.640 | 5.758505 | 0.00248644 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 85841.40 | 85416.50 | -999.0 | 28.20 | 14.47 | 0.00704465 | 12.80 | 8.76 | 0.00700000 | 28.50 | 0.00546700 | 13.26 | -999.0000 | 27.00 | 0.00708867 | 25.9799 | 81342.60 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10357.809 | 5482.060 | 0.587272 | 0.00025366 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8757.99 | 8715.56 | -999.0 | 28.21 | 14.47 | 0.00704371 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708683 | 25.9732 | 8293.36 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 547101.361 | 547101.361 | 30.167161 | 0.01339848 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 547101.36 | 547101.36 | 30.167161 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.1217 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10569.689 | 10569.689 | 0.599671 | 0.00025885 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10569.69 | 10569.69 | 0.599671 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6068 | 25.99 | 0.00531243 | 20.7159 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 101528.953 | 101528.953 | 5.758505 | 0.00248644 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 101528.95 | 101528.95 | 5.758505 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7147 | 23.96 | 0.00187879 | 8.3144 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10357.809 | 10357.809 | 0.587272 | 0.00025366 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10357.81 | 10357.81 | 0.587272 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6619 | 22.63 | 0.00161277 | 7.7378 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 19243.92 | 19243.92 | 30.167161 | -0.20 | -0.20 | 0.00693219 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.1217 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.599671 | -0.47 | -0.47 | 0.00519884 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6068 | 25.99 | 0.00531243 | 20.7159 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8889.90 | 8889.90 | 5.758505 | -0.49 | -4.35 | 0.00185372 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7147 | 23.96 | 0.00187879 | 8.3144 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.587272 | -0.48 | -4.75 | 0.00159527 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6619 | 22.63 | 0.00161277 | 7.7378 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13207.553 | 13207.553 | 1.616003 | 0.00011555 | 266.254 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.6058 | 0.618006 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | Sensible | 13207.55 | 13207.55 | 1.0000 | 1.57954185 | 1.616003 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.11553364 | 60.00 | 32.22 | 27.78 | 0.000 | 13207.55 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 13256.25 | 13256.25 | 1.57954185 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 396809.744 | 396809.744 | 16.197260 | 0.00347146 | 10011.664 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 18.2012 | 18.567482 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 396809.74 | 396809.74 | 1.0000 | 15.83181075 | 16.197260 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 3.47111061 | 60.00 | 32.22 | 27.78 | 0.000 | 396809.74 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 264429.92 | 0.00 | 398040.69 | 398040.69 | 15.83181075 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.46 | 20.42 | 0.00800000 | 58201.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 93783.072 | 93783.072 | 3.441500 | 0.00082046 | 2474.850 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 4.3017 | 4.388288 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 93783.07 | 93783.07 | 1.0000 | 3.36385123 | 3.441500 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.82037153 | 60.00 | 32.22 | 27.78 | 0.000 | 93783.07 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 65655.78 | 0.00 | 94101.87 | 94101.87 | 3.36385123 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14005.051 | 14005.051 | 0.514266 | 0.00012252 | 369.471 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.6424 | 0.655323 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14005.05 | 14005.05 | 1.0000 | 0.50266327 | 0.514266 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.12250980 | 60.00 | 32.22 | 27.78 | 0.000 | 14005.05 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785210 | 21.00 | 0.00785210 | 41.2146 | 9803.38 | 0.00 | 14051.87 | 14051.87 | 0.50266327 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9946.009 | 9946.009 | 0.365307 | 0.00008701 | 262.359 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.4562 | 0.465393 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9946.01 | 9946.01 | 1.0000 | 0.35706468 | 0.365307 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08700315 | 60.00 | 32.22 | 27.78 | 0.000 | 9946.01 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787539 | 21.00 | 0.00787539 | 41.3352 | 6961.22 | 0.00 | 9979.05 | 9979.05 | 0.35706468 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16459.814 | 16459.814 | 0.604621 | 0.00014400 | 434.160 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.7550 | 0.770186 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16459.81 | 16459.81 | 1.0000 | 0.59097924 | 0.604621 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.14398295 | 60.00 | 32.22 | 27.78 | 0.000 | 16459.81 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789493 | 21.00 | 0.00789493 | 41.4363 | 11519.46 | 0.00 | 16514.33 | 16514.33 | 0.59097924 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7553.988 | 7553.988 | 0.277249 | 0.00006609 | 199.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.3465 | 0.353465 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7553.99 | 7553.99 | 1.0000 | 0.27099344 | 0.277249 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.06607884 | 60.00 | 32.22 | 27.78 | 0.000 | 7553.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00776382 | 21.00 | 0.00776382 | 40.7575 | 5289.22 | 0.00 | 7579.56 | 7579.56 | 0.27099344 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61029.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 224883.322 | 224883.322 | 8.266040 | 0.00196738 | 5929.985 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 10.3151 | 10.522718 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 224883.32 | 224883.32 | 1.0000 | 8.07953801 | 8.266040 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.96717671 | 60.00 | 32.22 | 27.78 | 0.000 | 224883.32 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784618 | 21.00 | 0.00784618 | 41.1844 | 157350.06 | 0.00 | 225615.51 | 225615.51 | 8.07953801 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 151109.029 | 151109.029 | 5.554695 | 0.00132197 | 3984.495 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 6.9312 | 7.070679 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 151109.03 | 151109.03 | 1.0000 | 5.42936760 | 5.554695 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.32183285 | 60.00 | 32.22 | 27.78 | 0.000 | 151109.03 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784791 | 21.00 | 0.00784791 | 41.1934 | 105727.28 | 0.00 | 151600.12 | 151600.12 | 5.42936760 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 227605.037 | 227605.037 | 8.366245 | 0.00199119 | 6001.701 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 10.4400 | 10.650072 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 227605.04 | 227605.04 | 1.0000 | 8.17748283 | 8.366245 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.99098503 | 60.00 | 32.22 | 27.78 | 0.000 | 227605.04 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784816 | 21.00 | 0.00784816 | 41.1946 | 159252.83 | 0.00 | 228345.69 | 228345.69 | 8.17748283 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 144309.769 | 144309.769 | 5.304403 | 0.00126248 | 3805.326 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 6.6193 | 6.752528 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 144309.77 | 144309.77 | 1.0000 | 5.18472320 | 5.304403 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.26235603 | 60.00 | 32.22 | 27.78 | 0.000 | 144309.77 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00784019 | 21.00 | 0.00784019 | 41.1534 | 100973.59 | 0.00 | 144779.60 | 144779.60 | 5.18472320 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29113.347 | 29113.347 | 1.070506 | 0.00025470 | 767.568 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 1.3354 | 1.362269 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29113.35 | 29113.35 | 1.0000 | 1.04635293 | 1.070506 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.25467028 | 60.00 | 32.22 | 27.78 | 0.000 | 29113.35 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785380 | 21.00 | 0.00785380 | 41.2241 | 20367.35 | 0.00 | 29207.22 | 29207.22 | 1.04635293 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19397.980 | 19397.980 | 0.713300 | 0.00016970 | 511.414 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.8898 | 0.907668 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19397.98 | 19397.98 | 1.0000 | 0.69720591 | 0.713300 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.16968468 | 60.00 | 32.22 | 27.78 | 0.000 | 19397.98 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785371 | 21.00 | 0.00785371 | 41.2237 | 13570.36 | 0.00 | 19460.46 | 19460.46 | 0.69720591 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29412.842 | 29412.842 | 1.081532 | 0.00025732 | 775.460 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 1.3491 | 1.376283 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29412.84 | 29412.84 | 1.0000 | 1.05713050 | 1.081532 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.25729012 | 60.00 | 32.22 | 27.78 | 0.000 | 29412.84 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785526 | 21.00 | 0.00785526 | 41.2317 | 20576.73 | 0.00 | 29507.65 | 29507.65 | 1.05713050 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18918.225 | 18918.225 | 0.695642 | 0.00016550 | 498.771 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 0.8678 | 0.885220 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18918.22 | 18918.22 | 1.0000 | 0.67994653 | 0.695642 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.16548800 | 60.00 | 32.22 | 27.78 | 0.000 | 18918.22 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00785013 | 21.00 | 0.00785013 | 41.2052 | 13234.91 | 0.00 | 18979.19 | 18979.19 | 0.67994653 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 168707.142 | -999.000 | 11.158238 | 0.00482500 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8514 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.158238 | 10.90648137 | 4197.9300 | 999.8980 | 58.18261971 | 15.00 | 6.67 | 8.33 | 2034573.88 | 8.2920 | 8.292014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 168707.14 | 168707.14 | 1.0000 | 10.90648137 | 11.158238 | 25.84 | 13.63 | 0.00699933 | 43802.8 | 10.64 | 7.86 | 0.00699933 | 28334.3 | 4.82451071 | 6.67 | 15.00 | 8.33 | 23984.237 | 144722.91 | 33.90 | 0.00547527 | 15.07 | 2.03050000 | 18.1973 | 24.00 | 0.00734673 | 24.00 | 0.00734673 | 32.1630 | 121867.63 | 0.00 | 142181.12 | 142181.12 | 10.90648137 | 25.84 | 15.74 | 0.00699933 | 43802.8 | 13.03 | 10.65 | 0.00699933 | 30766.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 63846.419 | 63846.419 | 3.347471 | 0.00055856 | 1031.664 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.158238 | 10.90648137 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 2.9286 | 2.987495 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 63846.42 | 63846.42 | 1.0000 | 3.27194441 | 3.347471 | -6.62 | -7.04 | 0.00240660 | -661.8 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.55849934 | 60.00 | 32.22 | 27.78 | 0.000 | 63846.42 | -17.90 | 0.00095524 | -17.90 | 2.03050000 | 60.6577 | 10.77 | 0.00464431 | 20.88 | 0.00565692 | 30.0221 | 25950.07 | 0.00 | 57215.36 | 57215.36 | 3.27194441 | 2.80 | -0.55 | 0.00240660 | 8844.9 | 20.13 | 8.79 | 0.00240660 | 26331.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1596970.153 | -999.000 | 104.358616 | 0.04567314 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8271 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 104.358616 | 102.00403690 | 4197.9300 | 999.8980 | 58.18261971 | 15.00 | 6.67 | 8.33 | 2034573.88 | 78.4916 | 78.491627 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1596970.15 | 1596970.14 | 1.0000 | 102.00403690 | 104.358616 | 26.02 | 13.69 | 0.00698624 | 43957.2 | 10.64 | 7.84 | 0.00698624 | 28301.3 | 45.66848508 | 6.67 | 15.00 | 8.33 | 224315.148 | 1372655.00 | 33.90 | 0.00547527 | 15.07 | 20.30600000 | 19.4579 | 24.00 | 0.00737410 | 24.00 | 0.00737410 | 32.2814 | 1107593.44 | 0.00 | 1346117.68 | 1346117.68 | 102.00403690 | 26.02 | 15.79 | 0.00698624 | 43957.2 | 13.06 | 10.65 | 0.00698624 | 30760.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 523687.402 | 523687.402 | 31.307585 | 0.00458145 | 8571.957 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 104.358616 | 102.00403690 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 24.0209 | 24.504328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 523687.40 | 523687.40 | 1.0000 | 30.60121107 | 31.307585 | -4.23 | -4.23 | 0.00337819 | 4171.1 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 4.58097849 | 60.00 | 32.22 | 27.78 | 0.000 | 523687.40 | -17.90 | 0.00095524 | -17.90 | 20.30600000 | 64.8597 | 21.00 | 0.00785031 | 18.06 | 0.00777133 | 48.9819 | 253474.16 | 0.00 | 482367.49 | 482367.49 | 30.60121107 | 2.80 | 1.07 | 0.00337819 | 11279.8 | 18.39 | 9.09 | 0.00337819 | 27042.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 175013.709 | -999.000 | 11.660379 | 0.00500537 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8454 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.660379 | 11.39729272 | 4197.9300 | 999.8980 | 58.18261971 | 15.00 | 6.67 | 8.33 | 2034573.88 | 8.6020 | 8.601983 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 175013.71 | 175013.71 | 1.0000 | 11.39729272 | 11.660379 | 25.73 | 13.59 | 0.00699608 | 43681.8 | 10.64 | 7.85 | 0.00699608 | 28326.1 | 5.00485934 | 6.67 | 15.00 | 8.33 | 25063.571 | 149950.14 | 33.90 | 0.00547527 | 15.07 | 2.03050000 | 17.4137 | 24.00 | 0.00731743 | 24.00 | 0.00731743 | 32.0361 | 129684.69 | 0.00 | 147317.08 | 147317.08 | 11.39729272 | 25.73 | 15.70 | 0.00699608 | 43681.8 | 13.03 | 10.65 | 0.00699608 | 30756.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53073.430 | 53073.430 | 3.498114 | 0.00046431 | 876.545 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.660379 | 11.39729272 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 2.4344 | 2.483407 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 03:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 53073.43 | 53073.43 | 1.0000 | 3.41918782 | 3.498114 | -2.65 | -2.65 | 0.00380462 | 6836.4 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.46426215 | 60.00 | 32.22 | 27.78 | 0.000 | 53073.43 | -17.90 | 0.00095524 | -17.90 | 2.03050000 | 58.0456 | 18.46 | 0.00774684 | 16.11 | 0.00778145 | 55.4856 | 23343.84 | 0.00 | 49802.69 | 49802.69 | 3.41918782 | 2.80 | 1.67 | 0.00380462 | 12348.5 | 17.19 | 9.03 | 0.00380462 | 26914.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 93882.880 | -999.000 | 6.121984 | 0.00268504 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0334 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:VariableVolume | 6.121984 | 5.98385722 | 4197.9300 | 999.8980 | 58.18261971 | 15.00 | 6.67 | 8.33 | 2034573.88 | 4.6144 | 4.614376 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 93882.88 | 93882.88 | 1.0000 | 5.98385722 | 6.121984 | 26.03 | 13.78 | 0.00709724 | 44244.9 | 10.61 | 7.95 | 0.00709724 | 28555.5 | 2.68476458 | 6.67 | 15.00 | 8.33 | 13314.631 | 80568.25 | 33.16 | 0.00547412 | 14.83 | 1.20015641 | 19.6040 | 24.00 | 0.00755846 | 24.00 | 0.00755846 | 33.0792 | 60426.98 | 0.00 | 80027.64 | 80027.64 | 5.98385722 | 26.03 | 15.89 | 0.00709724 | 44244.9 | 12.89 | 10.70 | 0.00709724 | 30870.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.743149 | 0.00087484 | 2620.430 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:VariableVolume | 6.121984 | 5.98385722 | 4197.9300 | 999.8980 | 18.69456858 | 54.44 | 82.22 | 27.78 | 2180132.46 | 4.5869 | 4.679190 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.743149 | -3.51 | -7.65 | 0.00095524 | -1143.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -17.90 | 0.00095524 | -17.90 | 1.20015641 | 32.0627 | 0.00 | 0.00095524 | 23.89 | 0.00095524 | 4.2536 | 0.00 | 0.00 | 100031.84 | 100031.84 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40228.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 547101.361 | 286714.262 | 30.167161 | 0.01339848 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8985 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 464998.30 | 463754.36 | 0.8499 | -999.0 | -999.0 | 28.78 | 14.64 | 0.00702469 | 46867.7 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 464998.30 | 33.90 | 0.00547527 | 15.07 | 0.33839277 | -999.0000 | 27.00 | 0.00704228 | 27.00 | 0.00704228 | 25.8136 | 370167.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10569.689 | 5595.758 | 0.599671 | 0.00025885 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9326 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8936.04 | 8893.43 | 0.8454 | -999.0 | -999.0 | 28.20 | 14.47 | 0.00704301 | 46323.1 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8936.04 | 28.50 | 0.00546700 | 13.26 | 0.01563234 | -999.0000 | 27.00 | 0.00708519 | 27.00 | 0.00708519 | 25.9672 | 8470.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 101528.953 | 53741.640 | 5.758505 | 0.00248644 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9357 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 85841.40 | 85416.50 | 0.8455 | -999.0 | -999.0 | 28.20 | 14.47 | 0.00704465 | 46328.9 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85841.40 | 28.50 | 0.00546700 | 13.26 | 0.15632344 | -999.0000 | 27.00 | 0.00708867 | 27.00 | 0.00708867 | 25.9799 | 81342.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10357.809 | 5482.060 | 0.587272 | 0.00025366 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9339 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8757.99 | 8715.56 | 0.8455 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704371 | 46335.8 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8757.99 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708683 | 27.00 | 0.00708683 | 25.9732 | 8293.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 547101.361 | 547101.361 | 30.167161 | 0.01339848 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 547101.36 | 547101.36 | 1.0000 | 29.48651739 | 30.167161 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 547101.36 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.1217 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10569.689 | 10569.689 | 0.599671 | 0.00025885 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10569.69 | 10569.69 | 1.0000 | 0.58614119 | 0.599671 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10569.69 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6068 | 0.00 | 0.00531243 | 25.99 | 0.00531243 | 20.7159 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 101528.953 | 101528.953 | 5.758505 | 0.00248644 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 101528.95 | 101528.95 | 1.0000 | 5.62857920 | 5.758505 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101528.95 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7147 | 0.00 | 0.00187879 | 23.96 | 0.00187879 | 8.3144 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10357.809 | 10357.809 | 0.587272 | 0.00025366 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10357.81 | 10357.81 | 1.0000 | 0.57402200 | 0.587272 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10357.81 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6619 | 0.00 | 0.00161277 | 22.63 | 0.00161277 | 7.7378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 30.167161 | 29.48651739 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 19243.92 | 19243.92 | 1.0000 | 29.48651739 | 30.167161 | -0.20 | -0.20 | 0.00693219 | 17132.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19243.92 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.1217 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.599671 | 0.58614119 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.58614119 | 0.599671 | -0.47 | -0.47 | 0.00519884 | 12528.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6068 | 0.00 | 0.00531243 | 25.99 | 0.00531243 | 20.7159 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.758505 | 5.62857920 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8889.90 | 8889.90 | 1.0000 | 5.62857920 | 5.758505 | -0.49 | -4.35 | 0.00185372 | 4146.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8889.90 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7147 | 0.00 | 0.00187879 | 23.96 | 0.00187879 | 8.3144 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.587272 | 0.57402200 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.57402200 | 0.587272 | -0.48 | -4.75 | 0.00159527 | 3509.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6619 | 0.00 | 0.00161277 | 22.63 | 0.00161277 | 7.7378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.16 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 104.36 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.66 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.12 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 30.17 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2694.33 | 1859.67 | 949.17 |
CORE_BOTTOM | 1937.00 | 1299.33 | 135.67 |
CORE_MID | 1117.17 | 3182.83 | 193.00 |
CORE_TOP | 1682.33 | 3808.17 | 789.33 |
PERIMETER_BOT_ZN_3 | 1848.67 | 3585.83 | 444.50 |
PERIMETER_BOT_ZN_2 | 2394.50 | 2950.50 | 545.17 |
PERIMETER_BOT_ZN_1 | 2930.17 | 2445.50 | 611.00 |
PERIMETER_BOT_ZN_4 | 2840.83 | 1940.67 | 437.17 |
PERIMETER_MID_ZN_3 | 2505.17 | 4026.67 | 1438.17 |
PERIMETER_MID_ZN_2 | 2394.83 | 2921.00 | 1065.83 |
PERIMETER_MID_ZN_1 | 3009.17 | 2778.83 | 962.17 |
PERIMETER_MID_ZN_4 | 2710.67 | 3297.83 | 1035.33 |
PERIMETER_TOP_ZN_3 | 3242.00 | 4162.00 | 2199.17 |
PERIMETER_TOP_ZN_2 | 3229.50 | 3546.00 | 1667.50 |
PERIMETER_TOP_ZN_1 | 3277.67 | 3043.33 | 1355.00 |
PERIMETER_TOP_ZN_4 | 3206.67 | 3544.83 | 1641.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 505.50 | 505.50 |
DATACENTER_MID_ZN_6 | 5740.50 | 78.17 | 71.83 |
DATACENTER_TOP_ZN_6 | 5133.67 | 307.50 | 137.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5868.00 | 5868.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5939.17 | 5899.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 2300.33 | 0.00 | 1399.50 |
CORE_BOTTOM | 0.00 | 28.50 | 0.00 | 13.67 |
CORE_MID | 0.00 | 0.33 | 0.00 | 0.17 |
CORE_TOP | 7.50 | 1.50 | 1.00 | 1.50 |
PERIMETER_BOT_ZN_3 | 0.50 | 51.50 | 0.00 | 43.00 |
PERIMETER_BOT_ZN_2 | 0.67 | 78.67 | 0.00 | 70.50 |
PERIMETER_BOT_ZN_1 | 1.17 | 228.83 | 0.00 | 221.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 166.67 | 0.00 | 90.83 |
PERIMETER_MID_ZN_3 | 23.00 | 10.83 | 4.33 | 9.00 |
PERIMETER_MID_ZN_2 | 33.33 | 58.67 | 0.33 | 55.00 |
PERIMETER_MID_ZN_1 | 9.33 | 309.83 | 0.17 | 306.17 |
PERIMETER_MID_ZN_4 | 9.67 | 61.67 | 0.17 | 40.50 |
PERIMETER_TOP_ZN_3 | 157.00 | 24.33 | 47.17 | 19.00 |
PERIMETER_TOP_ZN_2 | 93.00 | 59.33 | 9.67 | 52.17 |
PERIMETER_TOP_ZN_1 | 69.67 | 159.17 | 7.83 | 152.00 |
PERIMETER_TOP_ZN_4 | 51.67 | 64.00 | 7.00 | 41.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 22.83 | 0.00 | 21.83 |
DATACENTER_MID_ZN_6 | 0.00 | 21.33 | 0.00 | 20.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 17.33 | 0.00 | 16.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 3.50 | 0.00 | 3.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 185.00 | 2688.17 | 47.67 | 1764.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.060 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.027 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.721 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.697 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.945 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.591 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.707 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.010 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.739 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.382 | 0.050 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.554 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.283 | 0.047 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.778 | 0.056 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.497 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.650 | 0.057 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.347 | 0.058 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 31.203 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42098120.55 | 0.00 | 42098120.55 | 0.00 | 42098120.55 | 37848132.68 | 5130.13 | 634.56 | 2995.32 | 0.00 |
CORE_BOTTOM | 44413624.48 | 0.00 | 44413624.48 | 0.00 | 44413624.48 | 33990283.35 | 4319.11 | 57.65 | 4383.24 | 567.70 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 5268.34 | 555.05 | 2936.61 | 249.47 |
CORE_TOP | 28880437.44 | 0.00 | 28880437.44 | 0.00 | 28880437.44 | 33990283.35 | 5595.72 | 742.68 | 2421.60 | 376.30 |
PERIMETER_BOT_ZN_3 | 5140317.13 | 0.00 | 5140317.13 | 203001.59 | 5343318.72 | 4267819.30 | 5316.60 | 87.93 | 3355.46 | 567.70 |
PERIMETER_BOT_ZN_2 | 5414393.23 | 0.00 | 5414393.23 | 135334.30 | 5549727.54 | 2750345.05 | 4958.54 | 87.27 | 3714.19 | 567.70 |
PERIMETER_BOT_ZN_1 | 8988718.10 | 0.00 | 8988718.10 | 203001.59 | 9191719.69 | 4267912.63 | 4525.37 | 71.79 | 4162.84 | 567.70 |
PERIMETER_BOT_ZN_4 | 6910115.69 | 0.00 | 6910115.69 | 135334.30 | 7045449.99 | 2750345.05 | 4148.28 | 81.84 | 4529.88 | 567.70 |
PERIMETER_MID_ZN_3 | 38619877.06 | 0.00 | 38619877.06 | 476094.69 | 39095971.76 | 42678193.03 | 5300.38 | 507.06 | 2952.57 | 249.47 |
PERIMETER_MID_ZN_2 | 46539794.85 | 0.00 | 46539794.85 | 317396.25 | 46857191.10 | 27503450.52 | 4965.62 | 576.09 | 3218.29 | 920.58 |
PERIMETER_MID_ZN_1 | 79694768.94 | 0.00 | 79694768.94 | 476094.69 | 80170863.63 | 42679126.28 | 4332.67 | 574.80 | 3852.53 | 249.47 |
PERIMETER_MID_ZN_4 | 42973696.16 | 0.00 | 42973696.16 | 317396.25 | 43291092.41 | 27503450.52 | 4821.95 | 316.76 | 3621.29 | 249.47 |
PERIMETER_TOP_ZN_3 | 4050009.75 | 0.00 | 4050009.75 | 591121.17 | 4641130.93 | 4267819.30 | 4796.42 | 633.29 | 3330.28 | 376.30 |
PERIMETER_TOP_ZN_2 | 4953225.41 | 0.00 | 4953225.41 | 394080.51 | 5347305.92 | 2750345.05 | 4548.41 | 537.35 | 3674.24 | 376.30 |
PERIMETER_TOP_ZN_1 | 8450233.23 | 0.00 | 8450233.23 | 591121.17 | 9041354.40 | 4267912.63 | 4215.92 | 743.79 | 3800.29 | 376.30 |
PERIMETER_TOP_ZN_4 | 4513464.08 | 0.00 | 4513464.08 | 394080.51 | 4907544.59 | 2750345.05 | 4520.54 | 340.62 | 3898.84 | 376.30 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.50E+09 | 0.00 | 0.50E+09 | 0.00 | 0.50E+09 | 10671554.30 | 108.81 | 520.17 | 8131.03 | 2798.30 |
Total Facility | 0.58E+10 | 0.00 | 0.58E+10 | 18516893.95 | 0.58E+10 | 0.50E+10 | 7562.03 | 4363.29 | 8661.86 | 3471.12 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9677 | 0.0000 | 1.9677 | 0.0000 | 1.9677 | 1.2002 | 2313.13 | 634.56 | 2995.32 |
CORE_BOTTOM | 1.9262 | 0.0000 | 1.9262 | 0.0000 | 1.9262 | 1.0778 | 1970.41 | 56.72 | 3915.87 |
CORE_MID | 13.5361 | 0.0000 | 13.5361 | 0.0000 | 13.5361 | 10.7782 | 2590.73 | 554.19 | 2798.08 |
CORE_TOP | 1.3096 | 0.0000 | 1.3096 | 0.0000 | 1.3096 | 1.0778 | 2896.36 | 742.63 | 2304.01 |
PERIMETER_BOT_ZN_3 | 0.2229 | 0.0000 | 0.2229 | 0.0046 | 0.2275 | 0.1353 | 2952.01 | 86.22 | 2904.77 |
PERIMETER_BOT_ZN_2 | 0.2419 | 0.0000 | 0.2419 | 0.0031 | 0.2450 | 0.0872 | 2593.58 | 85.98 | 3263.44 |
PERIMETER_BOT_ZN_1 | 0.4028 | 0.0000 | 0.4028 | 0.0046 | 0.4074 | 0.1353 | 2161.29 | 70.21 | 3711.50 |
PERIMETER_BOT_ZN_4 | 0.3054 | 0.0000 | 0.3054 | 0.0031 | 0.3085 | 0.0872 | 1791.23 | 81.16 | 4070.61 |
PERIMETER_MID_ZN_3 | 1.7466 | 0.0000 | 1.7466 | 0.0108 | 1.7574 | 1.3533 | 2625.92 | 505.76 | 2811.32 |
PERIMETER_MID_ZN_2 | 2.1017 | 0.0000 | 2.1017 | 0.0077 | 2.1094 | 0.8721 | 1925.94 | 572.49 | 2535.56 |
PERIMETER_MID_ZN_1 | 3.6659 | 0.0000 | 3.6659 | 0.0108 | 3.6767 | 1.3533 | 1656.95 | 573.76 | 3712.29 |
PERIMETER_MID_ZN_4 | 1.9523 | 0.0000 | 1.9523 | 0.0072 | 1.9595 | 0.8721 | 2146.42 | 316.06 | 3480.52 |
PERIMETER_TOP_ZN_3 | 0.1839 | 0.0000 | 0.1839 | 0.0133 | 0.1972 | 0.1353 | 2099.96 | 632.85 | 3210.19 |
PERIMETER_TOP_ZN_2 | 0.2278 | 0.0000 | 0.2278 | 0.0089 | 0.2367 | 0.0872 | 1853.81 | 537.16 | 3552.03 |
PERIMETER_TOP_ZN_1 | 0.3895 | 0.0000 | 0.3895 | 0.0133 | 0.4028 | 0.1353 | 1518.38 | 743.54 | 3681.09 |
PERIMETER_TOP_ZN_4 | 0.2050 | 0.0000 | 0.2050 | 0.0089 | 0.2139 | 0.0872 | 1823.64 | 340.50 | 3778.86 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 16.1524 | 0.0000 | 16.1524 | 0.0000 | 16.1524 | 0.3384 | 90.11 | 520.17 | 5332.73 |
Total Facility | 254.7262 | 0.0000 | 254.7262 | 0.4233 | 255.1496 | 158.4706 | 4745.03 | 4358.43 | 5861.84 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 67705400.50 | 0.00 | 67705400.50 | 48026705.38 | 3652.43 | 364.31 | 4743.26 | 567.70 |
VAV_MID WITH REHEAT | 0.49E+09 | 0.00 | 0.49E+09 | 0.48E+09 | 4758.96 | 111.23 | 3889.82 | 249.47 |
VAV_TOP WITH REHEAT | 48578780.06 | 0.00 | 48578780.06 | 48026705.38 | 5000.46 | 204.90 | 3554.65 | 376.13 |
CAV_BAS | 40219892.41 | 0.00 | 40219892.41 | 37848132.68 | 5787.53 | 19.17 | 2953.30 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 628.97 | 0.00 | 8131.03 | 2798.30 |
AIRLOOP DATACENTER BOT | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2333965.77 | 0.00 | 2333965.77 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9610 | 0.0000 | 2.9610 | 1.5229 | 1299.75 | 362.93 | 4280.31 |
VAV_MID WITH REHEAT | 22.0097 | 0.0000 | 22.0097 | 15.2292 | 2080.29 | 110.30 | 3752.41 |
VAV_TOP WITH REHEAT | 2.2124 | 0.0000 | 2.2124 | 1.5229 | 2300.82 | 204.90 | 3437.28 |
CAV_BAS | 1.8799 | 0.0000 | 1.8799 | 1.2002 | 2970.53 | 19.17 | 2953.30 |
AIRLOOP DATACENTER BASEMENT | 15.4318 | 0.0000 | 15.4318 | 0.3384 | 610.27 | 0.00 | 5332.73 |
AIRLOOP DATACENTER BOT | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1091 | 0.0000 | 0.1091 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1084.67 | 3183.01 | 0.00 | 0.00 | 0.00 | 1288.33 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 895.14 | 2776.90 | 0.00 | 0.00 | 0.00 | 1475.12 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 396.95 | 2660.47 | 0.00 | 0.00 | 0.00 | 2242.10 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 625.54 | 3004.25 | 0.00 | 13.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 520.17 | 8131.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 1.9778 | 5.1074 | 0.0000 | 0.0000 | 0.0000 | 1.6236 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 19.2734 | 35.7091 | 0.0000 | 0.0000 | 0.0000 | 15.7858 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 1.9210 | 3.8870 | 0.0000 | 0.0000 | 0.0000 | 1.5629 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1476 | 3.4769 | 0.0000 | 0.8006 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3234 | 17.1686 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1494 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1185 |
Fields with Defaults | 3880 |
Autosized Fields | 335 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
Electricity:Building | 17137.03 | 216479.19 | 14-MAY-17:20 | 1025582.59 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17137.03 | 216479.19 | 14-MAY-17:20 | 1025582.59 | 01-DEC-16:30 |
InteriorLights:Electricity | 2460.64 | 9223.03 | 14-MAY-17:20 | 247210.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2460.64 | 9223.03 | 14-MAY-17:20 | 247210.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 2460.64 | 9223.03 | 14-MAY-17:20 | 247210.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2460.64 | 9223.03 | 14-MAY-17:20 | 247210.90 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.03 | 603.11 | 26-MAR-17:10 | 3823.11 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.67 | 43.94 | 01-JAN-08:50 | 1662.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.67 | 43.94 | 01-JAN-08:50 | 1662.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.30 | 388.67 | 26-MAR-17:10 | 2463.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.86 | 28.32 | 01-JAN-07:40 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.86 | 28.32 | 01-JAN-07:40 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.90 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.53 | 43.94 | 01-JAN-07:50 | 1662.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.53 | 43.94 | 01-JAN-07:50 | 1662.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.22 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.78 | 28.32 | 01-JAN-08:50 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.78 | 28.32 | 01-JAN-08:50 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 470.16 | 6031.15 | 26-MAR-17:10 | 38231.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.51 | 439.44 | 01-JAN-08:50 | 16625.62 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.51 | 439.44 | 01-JAN-08:50 | 16625.62 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.89 | 3886.70 | 26-MAR-17:10 | 24637.60 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.54 | 283.19 | 01-JAN-07:40 | 10714.18 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.54 | 283.19 | 01-JAN-07:40 | 10714.18 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 468.92 | 6031.24 | 12-MAR-17:10 | 38231.83 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.26 | 439.45 | 01-JAN-07:50 | 16625.99 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.26 | 439.45 | 01-JAN-07:50 | 16625.99 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 302.13 | 3886.68 | 12-MAR-17:10 | 24637.51 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.78 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.78 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.02 | 603.11 | 26-MAR-17:10 | 3823.11 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.65 | 43.94 | 01-JAN-08:50 | 1662.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.65 | 43.94 | 01-JAN-08:50 | 1662.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.29 | 388.67 | 26-MAR-17:10 | 2463.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.85 | 28.32 | 01-JAN-07:40 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.85 | 28.32 | 01-JAN-07:40 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.89 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.53 | 43.94 | 01-JAN-07:50 | 1662.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.53 | 43.94 | 01-JAN-07:50 | 1662.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.21 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.78 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.78 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2048.10 | 4232.75 | 05-JAN-04:40 | 388823.00 | 26-JUN-15:10 |
HeatRejection:Electricity | 458.64 | 58.80 | 05-JAN-07:20 | 74036.60 | 15-JUN-12:30 |
General:HeatRejection:Electricity | 458.64 | 58.80 | 05-JAN-07:20 | 74036.60 | 15-JUN-12:30 |
Electricity:HVAC | 6381.32 | 63712.16 | 21-MAY-02:30 | 546447.36 | 02-AUG-16:00 |
ExteriorEquipment:Electricity | 2566.27 | 20217.42 | 01-JAN-00:10 | 233391.87 | 21-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
ElectricityPurchased:Plant | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
Cogeneration:ElectricityPurchased | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
ElectricityNet:Plant | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
Cogeneration:ElectricityNet | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
General:Cogeneration:ElectricityNet | 28429.06 | 305714.20 | 29-MAY-04:40 | 2104512.47 | 02-AUG-15:40 |
Fans:Electricity | 2920.73 | 57324.14 | 01-JAN-00:10 | 343887.06 | 12-SEP-15:10 |
General:Fans:Electricity | 2920.73 | 57324.14 | 01-JAN-00:10 | 343887.06 | 12-SEP-15:10 |
ExteriorLights:Electricity | 351.01 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 351.01 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1788.03 | 2152.02 | 05-JAN-07:10 | 436854.43 | 16-AUG-15:10 |
General:Cooling:Electricity | 1788.03 | 2152.02 | 05-JAN-07:10 | 436854.43 | 16-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2349.40 | 0.00 | 13-APR-17:00 | 100000.00 | 01-JAN-09:50 |
General:Humidifier:Electricity | 2349.40 | 0.00 | 13-APR-17:00 | 100000.00 | 01-JAN-09:50 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 450.41 | 0.00 | 01-JAN-00:10 | 55492.22 | 14-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 450.41 | 0.00 | 01-JAN-00:10 | 55492.22 | 14-FEB-12:50 |
Pumps:Electricity | 407.54 | 4140.76 | 01-JAN-00:10 | 46046.50 | 12-JUL-13:40 |
General:Pumps:Electricity | 407.54 | 4140.76 | 01-JAN-00:10 | 46046.50 | 12-JUL-13:40 |
WIRED_LTG_ELECTRICITY | 69.14 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1804.80 | 0.00 | 01-JAN-00:10 | 1529692.54 | 23-DEC-07:10 |
NaturalGas:Plant | 1804.80 | 0.00 | 01-JAN-00:10 | 1529692.54 | 23-DEC-07:10 |
Heating:NaturalGas | 1804.80 | 0.00 | 01-JAN-00:10 | 1529692.54 | 23-DEC-07:10 |
Boiler:Heating:NaturalGas | 1804.80 | 0.00 | 01-JAN-00:10 | 1529692.54 | 23-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10418.78 | 6289.72 | 05-JAN-07:10 | 2365276.92 | 16-AUG-15:10 |
PlantLoopCoolingDemand:HVAC | 10418.78 | 6289.72 | 05-JAN-07:10 | 2365276.92 | 16-AUG-15:10 |
CoolingCoils:PlantLoopCoolingDemand | 10418.78 | 6289.72 | 05-JAN-07:10 | 2365276.92 | 16-AUG-15:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8493.12 | 0.00 | 20-MAY-24:00 | 0.00 | 26-JUN-15:10 |
Water:HVAC | 873.98 | 0.00 | 13-APR-17:00 | 0.00 | 15-JAN-15:30 |
Humidifier:Water | 873.98 | 0.00 | 13-APR-17:00 | 0.00 | 15-JAN-15:30 |
General:Humidifier:Water | 873.98 | 0.00 | 13-APR-17:00 | 0.00 | 15-JAN-15:30 |
MainsWater:Facility | 8493.12 | 0.00 | 20-MAY-24:00 | 0.00 | 26-JUN-15:10 |
MainsWater:HVAC | 873.98 | 0.00 | 13-APR-17:00 | 0.00 | 15-JAN-15:30 |
Humidifier:MainsWater | 873.98 | 0.00 | 13-APR-17:00 | 0.00 | 15-JAN-15:30 |
General:Humidifier:MainsWater | 873.98 | 0.00 | 13-APR-17:00 | 0.00 | 15-JAN-15:30 |
Water:Plant | 7619.14 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7619.14 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 5338.98 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
General:HeatRejection:Water | 5338.98 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
HeatRejection:MainsWater | 5338.98 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
General:HeatRejection:MainsWater | 5338.98 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 49437.73 | 99533.10 | 06-JAN-03:40 | 8919492.31 | 16-AUG-15:10 |
EnergyTransfer:Building | 18752.41 | 88334.71 | 08-JAN-11:40 | 1640951.76 | 31-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 542.23 | 0.00 | 01-JAN-00:10 | 99924.41 | 02-JAN-07:10 |
Heating:EnergyTransfer | 391.73 | 0.00 | 01-JAN-16:30 | 640814.67 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 391.73 | 0.00 | 01-JAN-16:30 | 640814.67 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 18360.68 | 87262.91 | 08-JAN-05:50 | 1640951.76 | 31-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 542.23 | 0.00 | 01-JAN-00:10 | 99924.41 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 18360.68 | 87262.91 | 08-JAN-05:50 | 1640951.76 | 31-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 542.23 | 0.00 | 01-JAN-00:10 | 99924.41 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 630.26 | 0.00 | 01-JAN-00:10 | 69081.10 | 19-JUL-10:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 630.26 | 0.00 | 01-JAN-00:10 | 69081.10 | 19-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 630.26 | 0.00 | 01-JAN-00:10 | 69081.10 | 19-JUL-10:10 |
EnergyTransfer:Zone:CORE_MID | 4122.83 | 0.00 | 01-JAN-00:10 | 442917.22 | 19-JUL-10:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.28 | 0.00 | 01-JAN-00:10 | 142756.66 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.28 | 0.00 | 01-JAN-00:10 | 142756.66 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4122.55 | 0.00 | 01-JAN-00:10 | 442917.22 | 19-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4122.55 | 0.00 | 01-JAN-00:10 | 442917.22 | 19-JUL-10:10 |
EnergyTransfer:Zone:CORE_TOP | 366.51 | 0.00 | 01-JAN-00:10 | 66376.00 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 10.50 | 0.00 | 01-JAN-00:10 | 66376.00 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 10.50 | 0.00 | 01-JAN-00:10 | 66376.00 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 356.01 | 0.00 | 01-JAN-00:10 | 58277.14 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 356.01 | 0.00 | 01-JAN-00:10 | 58277.14 | 26-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.88 | 0.00 | 01-JAN-00:10 | 13163.36 | 18-JUL-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.53 | 0.00 | 01-JAN-00:10 | 5719.92 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.53 | 0.00 | 01-JAN-00:10 | 5719.92 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.35 | 0.00 | 01-JAN-00:10 | 13163.36 | 18-JUL-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.35 | 0.00 | 01-JAN-00:10 | 13163.36 | 18-JUL-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.34 | 0.00 | 01-JAN-00:10 | 17337.92 | 07-AUG-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.50 | 0.00 | 01-JAN-00:10 | 5325.78 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.50 | 0.00 | 01-JAN-00:10 | 5325.78 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 73.84 | 0.00 | 01-JAN-00:10 | 17337.92 | 07-AUG-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 73.84 | 0.00 | 01-JAN-00:10 | 17337.92 | 07-AUG-07:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 136.08 | 0.00 | 01-JAN-00:10 | 21609.38 | 07-NOV-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.89 | 0.00 | 01-JAN-00:10 | 9334.90 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.89 | 0.00 | 01-JAN-00:10 | 9334.90 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.19 | 0.00 | 01-JAN-00:10 | 21609.38 | 07-NOV-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.19 | 0.00 | 01-JAN-00:10 | 21609.38 | 07-NOV-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 100.87 | 0.00 | 01-JAN-00:10 | 20881.96 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1824.71 | 05-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1824.71 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 100.86 | 0.00 | 01-JAN-00:10 | 20881.96 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 100.86 | 0.00 | 01-JAN-00:10 | 20881.96 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 556.79 | 0.00 | 01-JAN-00:10 | 114113.14 | 22-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 76.10 | 0.00 | 01-JAN-00:10 | 114113.14 | 22-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 76.10 | 0.00 | 01-JAN-00:10 | 114113.14 | 22-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 480.70 | 0.00 | 01-JAN-00:10 | 111184.82 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 480.70 | 0.00 | 01-JAN-00:10 | 111184.82 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 652.92 | 0.00 | 01-JAN-00:10 | 171929.94 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.26 | 0.00 | 01-JAN-00:10 | 97470.89 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.26 | 0.00 | 01-JAN-00:10 | 97470.89 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 614.66 | 0.00 | 01-JAN-00:10 | 171929.94 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 614.66 | 0.00 | 01-JAN-00:10 | 171929.94 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1267.08 | 0.00 | 01-JAN-00:10 | 238958.60 | 05-NOV-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 37.25 | 0.00 | 01-JAN-00:10 | 128559.26 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 37.25 | 0.00 | 01-JAN-00:10 | 128559.26 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1229.83 | 0.00 | 01-JAN-00:10 | 238958.60 | 05-NOV-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1229.83 | 0.00 | 01-JAN-00:10 | 238958.60 | 05-NOV-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 654.08 | 0.00 | 01-JAN-00:10 | 188851.66 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.83 | 0.00 | 01-JAN-00:10 | 86398.40 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.83 | 0.00 | 01-JAN-00:10 | 86398.40 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 626.24 | 0.00 | 01-JAN-00:10 | 188851.66 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 626.24 | 0.00 | 01-JAN-00:10 | 188851.66 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.03 | 0.00 | 01-JAN-00:10 | 14451.46 | 22-DEC-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 25.11 | 0.00 | 01-JAN-00:10 | 14451.46 | 22-DEC-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 25.11 | 0.00 | 01-JAN-00:10 | 14451.46 | 22-DEC-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.91 | 0.00 | 01-JAN-00:10 | 13019.36 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.91 | 0.00 | 01-JAN-00:10 | 13019.36 | 26-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.95 | 0.00 | 01-JAN-00:10 | 17374.11 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 12.96 | 0.00 | 01-JAN-00:10 | 14656.72 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 12.96 | 0.00 | 01-JAN-00:10 | 14656.72 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.99 | 0.00 | 01-JAN-00:10 | 17374.11 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.99 | 0.00 | 01-JAN-00:10 | 17374.11 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 128.22 | 0.00 | 01-JAN-00:10 | 23753.02 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 14.47 | 0.00 | 01-JAN-00:10 | 18704.28 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 14.47 | 0.00 | 01-JAN-00:10 | 18704.28 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.75 | 0.00 | 01-JAN-00:10 | 23753.02 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.75 | 0.00 | 01-JAN-00:10 | 23753.02 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 69.44 | 0.00 | 01-JAN-00:10 | 19713.28 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 9.69 | 0.00 | 01-JAN-00:10 | 13025.30 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 9.69 | 0.00 | 01-JAN-00:10 | 13025.30 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.75 | 0.00 | 01-JAN-00:10 | 19713.28 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.75 | 0.00 | 01-JAN-00:10 | 19713.28 | 16-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 64.29 | 0.00 | 01-JAN-00:10 | 12516.01 | 10-JUL-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.13 | 0.00 | 01-JAN-00:10 | 4380.45 | 24-DEC-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.13 | 0.00 | 01-JAN-00:10 | 4380.45 | 24-DEC-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.16 | 0.00 | 01-JAN-00:10 | 12516.01 | 10-JUL-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.16 | 0.00 | 01-JAN-00:10 | 12516.01 | 10-JUL-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 428.68 | 0.00 | 01-JAN-00:10 | 83048.64 | 17-JUL-10:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 96.69 | 0.00 | 01-JAN-00:10 | 67043.73 | 01-JAN-13:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 96.69 | 0.00 | 01-JAN-00:10 | 67043.73 | 01-JAN-13:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 331.99 | 0.00 | 01-JAN-00:10 | 83048.64 | 17-JUL-10:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 331.99 | 0.00 | 01-JAN-00:10 | 83048.64 | 17-JUL-10:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 97.97 | 0.00 | 01-JAN-00:10 | 25090.95 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.37 | 0.00 | 01-JAN-00:10 | 25090.95 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.37 | 0.00 | 01-JAN-00:10 | 25090.95 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.60 | 0.00 | 01-JAN-00:10 | 23291.63 | 26-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.60 | 0.00 | 01-JAN-00:10 | 23291.63 | 26-JUN-15:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.56 | 540.34 | 06-JAN-06:20 | 8673.62 | 05-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.56 | 540.34 | 06-JAN-06:20 | 8673.62 | 05-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.56 | 540.34 | 06-JAN-06:20 | 8673.62 | 05-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1220.77 | 10.19 | 16-JAN-23:40 | 82423.46 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.44 | 0.00 | 01-JAN-12:50 | 3540.53 | 06-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.44 | 0.00 | 01-JAN-12:50 | 3540.53 | 06-JAN-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1220.33 | 0.00 | 01-JAN-00:10 | 82423.46 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1220.33 | 0.00 | 01-JAN-00:10 | 82423.46 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 111.68 | 1.91 | 05-JAN-12:20 | 8406.12 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.74 | 0.00 | 01-JAN-16:30 | 709.01 | 01-JAN-18:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.74 | 0.00 | 01-JAN-16:30 | 709.01 | 01-JAN-18:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.94 | 0.00 | 01-JAN-00:10 | 8406.12 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.94 | 0.00 | 01-JAN-00:10 | 8406.12 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.96 | 86537.03 | 08-JAN-08:30 | 369236.96 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.96 | 86537.03 | 08-JAN-08:30 | 369236.96 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.96 | 86537.03 | 08-JAN-08:30 | 369236.96 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1837.52 | 0.00 | 01-JAN-00:10 | 1269418.05 | 23-DEC-07:20 |
PlantLoopHeatingDemand:Plant | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:10 |
EnergyTransfer:HVAC | 10754.64 | 8595.96 | 05-JAN-03:50 | 2155724.55 | 16-AUG-15:10 |
HeatingCoils:EnergyTransfer | 1392.37 | 0.00 | 01-JAN-00:10 | 1259281.09 | 23-DEC-07:20 |
PlantLoopHeatingDemand:HVAC | 1392.37 | 0.00 | 01-JAN-00:10 | 1259281.09 | 23-DEC-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 1392.37 | 0.00 | 01-JAN-00:10 | 1259281.09 | 23-DEC-07:20 |
CoolingCoils:EnergyTransfer | 9362.27 | 4137.70 | 05-JAN-07:10 | 2155724.55 | 16-AUG-15:10 |
EnergyTransfer:Plant | 19930.67 | 0.00 | 01-JAN-00:10 | 5358907.52 | 26-JUN-15:10 |
LoopToLoop:EnergyTransfer | 5790.31 | 0.00 | 01-JAN-00:10 | 1693925.13 | 26-JUN-15:10 |
WaterSystems:EnergyTransfer | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 445.14 | 0.00 | 01-JAN-00:10 | 54678.49 | 13-FEB-12:10 |
Boilers:EnergyTransfer | 1385.19 | 0.00 | 01-JAN-00:10 | 1270617.16 | 23-DEC-07:10 |
Chillers:EnergyTransfer | 5789.25 | 0.00 | 01-JAN-00:10 | 1694593.07 | 26-JUN-15:10 |
HeatRejection:EnergyTransfer | 6520.77 | 0.00 | 01-JAN-00:10 | 1935475.15 | 26-JUN-15:10 |
General:HeatRejection:EnergyTransfer | 6520.77 | 0.00 | 01-JAN-00:10 | 1935475.15 | 26-JUN-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -542.200 | 0.000 | 0.000 | 87.286 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -135.213 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -630.260 | 0.000 | 0.000 | 83.333 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 108.476 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.281 | -4122.533 | 0.000 | 0.000 | 840.333 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1102.574 |
CORE_TOP | 0.000 | 0.000 | 10.499 | -356.011 | 0.000 | 0.000 | 86.924 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -179.860 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.525 | -71.355 | 0.000 | 0.000 | 10.748 | 10.666 | 36.365 | 34.516 | 0.000 | 0.054 | 54.925 | 0.000 | -73.452 | 0.000 | -2.993 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.503 | -73.840 | 0.000 | 0.000 | 6.871 | 6.861 | 23.435 | 80.760 | 0.000 | 0.035 | 3.749 | 0.000 | -46.373 | 0.000 | -2.002 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.885 | -135.191 | 0.000 | 0.000 | 10.594 | 10.533 | 36.366 | 168.161 | 0.000 | 0.053 | 0.001 | 0.000 | -69.061 | 0.000 | -3.041 | -19.299 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.010 | -100.859 | 0.000 | 0.000 | 6.778 | 6.784 | 23.435 | 72.950 | 0.000 | 0.035 | 45.034 | 0.000 | -51.981 | 0.000 | -2.186 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 76.095 | -480.694 | 0.000 | 0.000 | 112.313 | 106.509 | 363.654 | 358.457 | 0.000 | 1.269 | 198.954 | 0.000 | -672.780 | 0.000 | -63.777 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 38.255 | -614.657 | 0.000 | 0.000 | 51.382 | 68.536 | 234.352 | 806.522 | 0.000 | 0.797 | 0.025 | 0.000 | -440.575 | 0.000 | -44.342 | -100.269 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 37.250 | -1229.818 | 0.000 | 0.000 | 106.718 | 105.262 | 363.660 | 1675.043 | 0.000 | 1.220 | 0.025 | 0.000 | -674.225 | 0.000 | -68.846 | -316.264 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 27.832 | -626.237 | 0.000 | 0.000 | 70.637 | 67.783 | 234.351 | 740.625 | 0.000 | 0.802 | 0.002 | 0.000 | -463.906 | 0.000 | -45.474 | -6.413 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 25.111 | -44.914 | 0.000 | 0.000 | 11.412 | 10.650 | 36.365 | 36.350 | 0.000 | 0.151 | 0.000 | 0.000 | -63.378 | 0.000 | -7.495 | -4.253 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 12.961 | -59.991 | 0.000 | 0.000 | 7.093 | 6.853 | 23.435 | 81.165 | 0.000 | 0.097 | 0.002 | 0.000 | -41.584 | 0.000 | -5.218 | -24.814 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 14.469 | -113.747 | 0.000 | 0.000 | 10.842 | 10.526 | 36.366 | 168.118 | 0.000 | 0.146 | 0.002 | 0.000 | -63.844 | 0.000 | -8.114 | -54.763 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 9.688 | -59.753 | 0.000 | 0.000 | 7.169 | 6.778 | 23.435 | 74.293 | 0.000 | 0.096 | 0.000 | 0.000 | -44.085 | 0.000 | -5.381 | -12.240 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.564 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.892 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.435 | -1220.332 | 0.000 | 0.000 | 9.498 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -364.670 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.742 | -110.935 | 0.000 | 0.000 | 0.951 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -48.265 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7172.969 | 0.000 | 0.000 | 20.562 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -390.062 |
GROUNDFLOOR_PLENUM | 3.132 | -61.159 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.097 | 64.344 | 0.000 | 0.000 | 0.000 | -6.414 | 0.000 |
MIDFLOOR_PLENUM | 96.688 | -331.991 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.866 | 343.820 | 0.000 | 0.000 | 0.000 | -110.383 | -0.004 |
TOPFLOOR_PLENUM | 36.373 | -61.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.156 | 36.685 | 0.000 | 0.000 | 0.000 | -11.616 | -0.002 |
Total Facility | 136.193 | -454.749 | 255.542 | -17905.860 | 0.000 | 0.000 | 1542.395 | 2460.638 | 14676.396 | 4296.959 | 0.000 | 6.874 | 856.050 | 0.000 | -2705.243 | 0.000 | -387.282 | -2777.862 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-JUL-06:11 | 0.00 | 0.00 | 0.00 | -118173.05 | 0.00 | 0.00 | 1273.02 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 98527.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 11-SEP-04:13 | 0.00 | 0.00 | 0.00 | -92834.25 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 86359.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:13 | 0.00 | 0.00 | 0.00 | -816578.69 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 751828.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:13 | 0.00 | 0.00 | 0.00 | -84673.96 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 78198.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-18:22 | 0.00 | 0.00 | 0.00 | -18050.26 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 5592.29 | 0.00 | 0.00 | 11857.56 | 0.00 | -0.00 | 0.00 | -2.71 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-07:41 | 0.00 | 0.00 | 0.00 | -25362.03 | 0.00 | 0.00 | 18.17 | 28.32 | 464.11 | 19232.66 | 0.00 | 0.00 | 5653.63 | 0.00 | -0.00 | 0.00 | -34.86 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:11 | 0.00 | 0.00 | 0.00 | -28997.13 | 0.00 | 0.00 | 25.04 | 43.94 | 720.19 | 29930.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -37.92 | -1684.70 |
PERIMETER_BOT_ZN_4 | 11-JUN-15:51 | 0.00 | 0.00 | 0.00 | -33747.22 | 0.00 | 0.00 | 12.83 | 28.32 | 464.11 | 22631.55 | 0.00 | 0.00 | 10618.04 | 0.00 | -0.00 | 0.00 | -7.62 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-14:53 | 0.00 | 0.00 | 0.00 | -160078.91 | 0.00 | 0.00 | 383.68 | 439.44 | 7201.84 | 78041.47 | 0.00 | 3305.78 | 70706.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:51 | 0.00 | 0.00 | 0.00 | -287659.46 | 0.00 | 0.00 | 158.63 | 283.19 | 4641.14 | 200872.37 | 0.00 | 0.00 | 82144.59 | 0.00 | -0.00 | 0.00 | -440.46 | 0.00 |
PERIMETER_MID_ZN_1 | 26-FEB-12:41 | 0.00 | 0.00 | 0.00 | -296283.88 | 0.00 | 0.00 | 226.18 | 439.45 | 7201.95 | 359757.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4472.50 | -66868.34 |
PERIMETER_MID_ZN_4 | 25-JUN-16:11 | 0.00 | 0.00 | 0.00 | -314052.24 | 0.00 | 0.00 | 128.97 | 283.19 | 4641.11 | 213118.86 | 0.00 | 321.02 | 95559.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:51 | 0.00 | 0.00 | 0.00 | -18560.00 | 0.00 | 0.00 | 36.00 | 43.94 | 720.18 | 7670.16 | 0.00 | 340.64 | 9749.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -28716.16 | 0.00 | 0.00 | 16.16 | 28.32 | 464.11 | 19373.64 | 0.00 | 0.00 | 8893.37 | 0.00 | -0.00 | 0.00 | -59.43 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:11 | 0.00 | 0.00 | 0.00 | -32011.03 | 0.00 | 0.00 | 23.09 | 43.94 | 720.19 | 29660.76 | 0.00 | 0.00 | 1680.15 | 0.00 | -0.00 | 0.00 | -117.11 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-16:11 | 0.00 | 0.00 | 0.00 | -34090.12 | 0.00 | 0.00 | 11.27 | 28.32 | 464.11 | 21208.53 | 0.00 | 30.61 | 12347.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 05-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8673.67 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 861.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 13-AUG-18:44 | 0.00 | 0.00 | 0.00 | -82632.92 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 4512.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:41 | 0.00 | 0.00 | 0.00 | -8423.12 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 611.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 21-AUG-15:30 | 0.00 | 0.00 | 0.00 | -369524.31 | 0.00 | 0.00 | 2182.07 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16447.47 |
GROUNDFLOOR_PLENUM | 17-JUL-05:15 | 0.00 | -15126.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15152.89 | 0.00 | -0.00 | 0.00 | -26.28 | 0.00 |
MIDFLOOR_PLENUM | 20-DEC-04:01 | 0.00 | -139624.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159119.14 | 0.00 | -0.00 | 0.00 | -19494.97 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-15:00 | 0.00 | -26880.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.89 | 26717.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | -83198.18 | 0.00 | -1759130.69 | 0.00 | 0.00 | 16089.38 | 10593.62 | 616289.16 | 0.00 | 0.00 | 0.00 | 1264523.44 | 0.00 | -63797.03 | 0.00 | -1369.68 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-DEC-06:03 | 0.00 | 0.00 | 373354.14 | 0.00 | 0.00 | 0.00 | 11635.51 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -466836.86 |
CORE_TOP | 06-FEB-04:01 | 0.00 | 0.00 | 73847.21 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -80322.20 |
PERIMETER_BOT_ZN_3 | 23-DEC-05:01 | 0.00 | 0.00 | 12034.54 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8265.49 | 0.00 | -578.74 | -3816.96 |
PERIMETER_BOT_ZN_2 | 21-DEC-05:01 | 0.00 | 0.00 | 11419.88 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6130.66 | 0.00 | -264.60 | -5548.56 |
PERIMETER_BOT_ZN_1 | 21-DEC-05:01 | 0.00 | 0.00 | 16869.50 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9054.49 | 0.00 | -391.65 | -8236.41 |
PERIMETER_BOT_ZN_4 | 05-JAN-06:01 | 0.00 | 0.00 | 7227.20 | 0.00 | 0.00 | 0.00 | 94.15 | 43.48 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5014.32 | 0.00 | -26.52 | -2942.80 |
PERIMETER_MID_ZN_3 | 24-DEC-03:02 | 0.00 | 0.00 | 135326.86 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74131.84 | 0.00 | -14360.50 | -53100.94 |
PERIMETER_MID_ZN_2 | 24-DEC-03:02 | 0.00 | 0.00 | 180595.82 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50988.08 | 0.00 | -9744.21 | -123901.85 |
PERIMETER_MID_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 193895.34 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55091.85 | 0.00 | -6431.14 | -140502.80 |
PERIMETER_MID_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 171544.05 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37072.97 | 0.00 | -4342.03 | -135368.50 |
PERIMETER_TOP_ZN_3 | 24-DEC-03:02 | 0.00 | 0.00 | 16242.74 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7104.45 | 0.00 | -1724.45 | -8040.49 |
PERIMETER_TOP_ZN_2 | 24-DEC-06:22 | 0.00 | 0.00 | 21220.22 | 0.00 | 0.00 | 0.00 | 59.16 | 59.52 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4598.73 | 0.00 | -970.40 | -16233.89 |
PERIMETER_TOP_ZN_1 | 24-DEC-06:22 | 0.00 | 0.00 | 22951.93 | 0.00 | 0.00 | 0.00 | 91.01 | 92.36 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6993.44 | 0.00 | -1450.43 | -15411.63 |
PERIMETER_TOP_ZN_4 | 24-DEC-03:02 | 0.00 | 0.00 | 22102.18 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5004.41 | 0.00 | -1204.19 | -16297.40 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 09-JAN-03:15 | 0.00 | 0.00 | 4287.01 | 0.00 | 0.00 | 0.00 | 0.00 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23948.98 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:05 | 0.00 | 0.00 | 711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2677.79 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-NOV-14:21 | 14115.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -36.13 | -14079.23 |
MIDFLOOR_PLENUM | 26-MAR-15:51 | 161640.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3802.64 | -157838.14 |
TOPFLOOR_PLENUM | 22-DEC-05:11 | 29379.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -820.01 | -28559.30 |
Total Facility | 26-DEC-06:03 | -418655.89 | 495754.78 | 1024780.28 | -495754.78 | 0.00 | 0.00 | 20566.99 | 10593.62 | 616289.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103863.92 | 0.00 | -8756.78 | -1140953.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 13.0462 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.1582 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 125.1137 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 104.3586 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.9166 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6604 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.1220 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.1220 | 0.1960 | 1.0000 | Not calculated | 1.2002 | 0.1960 | ||
AIRLOOP DATACENTER BASEMENT | 30.1668 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 30.1672 | 0.0112 | 1.0000 | Not calculated | 0.3384 | 0.0112 | ||
AIRLOOP DATACENTER BOT | 0.5997 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5997 | 0.0261 | 1.0000 | Not calculated | 0.0156 | 0.0261 | ||
AIRLOOP DATACENTER MID | 5.7585 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.7585 | 0.0271 | 1.0000 | Not calculated | 0.1563 | 0.0271 | ||
AIRLOOP DATACENTER TOP | 0.5873 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5873 | 0.0266 | 1.0000 | Not calculated | 0.0156 | 0.0266 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.5231 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2827 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 62.5568 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8864 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.4583 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2855 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 30.1668 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 30.1668 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0112 | ||
AIRLOOP DATACENTER BOT | 0.5997 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5997 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0261 | ||
AIRLOOP DATACENTER MID | 5.7585 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.7585 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0271 | ||
AIRLOOP DATACENTER TOP | 0.5873 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5873 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0266 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 6.1220 | 6.1220 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6502 | 6.6502 | 1.6160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 62.5377 | 62.5377 | 16.1973 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2430 | 6.2430 | 1.6169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1612 | 1.1612 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5685 | 1.5685 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6918 | 1.6918 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9743 | 1.9743 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8798 | 10.8798 | 2.0345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.7685 | 16.7685 | 1.3079 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.6385 | 16.6385 | 2.0299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.2892 | 18.2892 | 1.3168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2454 | 1.2454 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6817 | 1.6817 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8097 | 1.8097 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9369 | 1.9369 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5997 | 0.5997 | 0.5997 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7585 | 5.7585 | 5.7585 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5873 | 0.5873 | 0.5873 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 30.1668 | 30.1668 | 30.1668 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 13.0462 | 11.1582 | 13.0462 | 2.2827 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 125.1137 | 104.3586 | 125.1137 | 22.8864 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.9166 | 11.6604 | 12.9166 | 2.2855 | 0.0000 | 1.0000 |
CAV_BAS | 6.1220 | 6.1220 | 6.1220 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 30.1668 | 30.1672 | 30.1668 | 30.1668 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5997 | 0.5997 | 0.5997 | 0.5997 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.7585 | 5.7585 | 5.7585 | 5.7585 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5873 | 0.5873 | 0.5873 | 0.5873 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3251 | 3.3251 | 1.6160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 31.2688 | 31.2688 | 16.1973 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1215 | 3.1215 | 1.6169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5806 | 0.5806 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7843 | 0.7843 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8459 | 0.8459 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9872 | 0.9872 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4399 | 5.4399 | 2.0345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3842 | 8.3842 | 1.3079 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3192 | 8.3192 | 2.0299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1446 | 9.1446 | 1.3168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6227 | 0.6227 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8409 | 0.8409 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9048 | 0.9048 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9684 | 0.9684 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5997 | 0.5997 | 0.5997 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7585 | 5.7585 | 5.7585 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5873 | 0.5873 | 0.5873 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 30.1668 | 30.1668 | 30.1668 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.5231 | 2.2827 | 2.2827 | 2.2827 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 62.5568 | 22.8864 | 22.8864 | 22.8864 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.4583 | 2.2855 | 2.2855 | 2.2855 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 30.1668 | 30.1668 | 30.1668 | 30.1668 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5997 | 0.5997 | 0.5997 | 0.5997 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.7585 | 5.7585 | 5.7585 | 5.7585 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5873 | 0.5873 | 0.5873 | 0.5873 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 47.67 |
Number of hours cooling loads not met | 1764.33 |
Number of hours not met | 1789.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1804.80 | 1529692.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1788.03 | 436854.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2460.64 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 351.01 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2920.73 | 343887.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 407.54 | 46046.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 458.64 | 74036.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2349.40 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 450.41 | 55492.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28429.06 |
Natural Gas | 0.00 | 1804.80 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30233.86 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.12 |
Space Heating | 0.00 |
Space Cooling | 38.60 |
Fans (All) | 63.06 |
Service Water Heating | 9.72 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 613.75 |
Subtotal | 613.75 |
Natural Gas [MJ/m2] | |
Space Heating | 38.96 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 38.96 |
Subtotal | 38.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.14 |
Space Heating | 5.97 |
Space Cooling | 5.91 |
Fans (All) | 9.66 |
Service Water Heating | 1.49 |
Receptacle Equipment | 48.54 |
Miscellaneous | 20.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 610. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7233.83 | 717.67 | 414.67 | 393.83 | 0.00 |
CORE_BOTTOM | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8705.67 | 54.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8697.00 | 63.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8548.83 | 211.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8697.67 | 62.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8695.50 | 64.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8704.67 | 55.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8693.83 | 66.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8382.50 | 377.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8677.50 | 82.50 | 0.00 | 0.00 | 0.00 |
Min | 7233.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 717.67 | 414.67 | 393.83 | 0.00 |
Average | 8639.28 | 85.57 | 18.03 | 17.12 | 0.00 |
Sum | 198703.50 | 1968.00 | 414.67 | 393.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 314824.67 | 23309.17 | 10424.83 | 20057.33 | 0.00 |
CORE_BOTTOM | 330778.00 | 35.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2262.50 | 5.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2264.33 | 3.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2265.50 | 2.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 100546.83 | 2848.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 23309.17 | 10424.83 | 20057.33 | 0.00 |
Average | 77870.30 | 1139.30 | 453.25 | 872.06 | 0.00 |
Sum | 1791016.83 | 26204.00 | 10424.83 | 20057.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7321.50 | 660.33 | 310.50 | 467.67 | 0.00 |
CORE_BOTTOM | 8626.17 | 133.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8680.33 | 79.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8685.33 | 74.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8667.17 | 92.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8670.50 | 89.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8670.50 | 89.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8526.50 | 233.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8698.67 | 61.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8670.00 | 90.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8720.17 | 39.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8703.83 | 56.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8712.33 | 47.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8682.33 | 77.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8466.33 | 293.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8644.00 | 116.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8689.83 | 70.17 | 0.00 | 0.00 | 0.00 |
Min | 7321.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 660.33 | 310.50 | 467.67 | 0.00 |
Average | 8620.09 | 106.08 | 13.50 | 20.33 | 0.00 |
Sum | 198262.00 | 2439.83 | 310.50 | 467.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 315785.33 | 24093.33 | 7018.67 | 21718.67 | 0.00 |
CORE_BOTTOM | 330601.00 | 212.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330724.00 | 89.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330708.00 | 105.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101591.67 | 1803.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330724.00 | 24093.33 | 7018.67 | 21718.67 | 0.00 |
Average | 77941.87 | 1143.59 | 305.16 | 944.29 | 0.00 |
Sum | 1792663.00 | 26302.67 | 7018.67 | 21718.67 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:33
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459585E+11 | 107057.11 | 02-JAN-07:05 | -2.3 | -3.5 | 0.568899E+10 | 7623.27 | 02-JAN-10:09 | -1.8 | -2.4 |
February | 0.396954E+11 | 96938.20 | 27-FEB-07:03 | 3.33 | -0.8 | 0.515229E+10 | 7499.27 | 08-FEB-14:09 | 3.33 | -0.8 |
March | 0.492816E+11 | 99904.33 | 13-MAR-06:11 | 7.33 | 1.79 | 0.615040E+10 | 7499.34 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.469013E+11 | 96548.29 | 10-APR-06:03 | 3.17 | -3.0 | 0.546633E+10 | 7499.54 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.490039E+11 | 102928.33 | 30-MAY-06:11 | 9.67 | 8.85 | 0.600492E+10 | 10129.78 | 17-MAY-13:00 | 9.67 | 8.85 |
June | 0.332710E+11 | 113796.24 | 15-JUN-06:11 | 16.10 | 9.72 | 0.740734E+10 | 12032.25 | 14-JUN-13:00 | 16.10 | 9.72 |
July | 0.263628E+11 | 118314.20 | 03-JUL-06:11 | 11.00 | 7.64 | 0.755032E+10 | 12651.53 | 27-JUL-13:00 | 26.00 | 16.77 |
August | 0.471687E+11 | 111267.76 | 17-AUG-06:11 | 12.67 | 5.40 | 0.713910E+10 | 11603.30 | 21-AUG-13:00 | 29.00 | 14.55 |
September | 0.491283E+11 | 111099.15 | 11-SEP-20:41 | 17.57 | 10.34 | 0.601321E+10 | 11807.69 | 11-SEP-13:00 | 17.57 | 10.34 |
October | 0.547303E+11 | 108313.18 | 10-OCT-06:11 | 8.67 | 4.44 | 0.570189E+10 | 7632.11 | 10-OCT-09:00 | 21.00 | 8.17 |
November | 0.519826E+11 | 100679.80 | 13-NOV-07:03 | 0.17 | 0.17 | 0.563651E+10 | 7499.15 | 08-NOV-14:20 | 0.17 | 0.17 |
December | 0.487431E+11 | 101921.79 | 04-DEC-07:11 | 6.67 | 0.99 | 0.548992E+10 | 7499.21 | 15-DEC-14:50 | 9.50 | 3.13 |
Annual Sum or Average | 0.542228E+12 | 0.734012E+11 | ||||||||
Minimum of Months | 0.263628E+11 | 96548.29 | -2.3 | -3.5 | 0.515229E+10 | 7499.15 | -1.8 | -2.4 | ||
Maximum of Months | 0.547303E+11 | 118314.20 | 17.57 | 10.34 | 0.755032E+10 | 12651.53 | 29.00 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388808E+11 | 88434.24 | 02-JAN-04:01 | -2.8 | -3.4 | 0.507178E+10 | 6734.81 | 10-JAN-10:20 | 2.33 | 2.33 |
February | 0.353128E+11 | 82559.36 | 21-FEB-04:01 | -1.0 | -1.0 | 0.459953E+10 | 6734.77 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.482646E+11 | 84492.17 | 13-MAR-04:12 | 6.67 | 1.13 | 0.549731E+10 | 6734.82 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.465292E+11 | 85201.30 | 10-APR-04:12 | 2.67 | -3.2 | 0.488674E+10 | 6735.06 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.493355E+11 | 85664.19 | 30-MAY-04:12 | 8.67 | 7.88 | 0.528824E+10 | 6734.84 | 26-MAY-13:09 | 8.67 | 7.88 |
June | 0.673973E+11 | 92589.11 | 08-JUN-04:13 | 13.07 | 8.19 | 0.528287E+10 | 7318.65 | 22-JUN-09:20 | 24.93 | 15.42 |
July | 0.770404E+11 | 91786.45 | 24-JUL-04:23 | 18.00 | 14.77 | 0.494121E+10 | 7760.00 | 19-JUL-09:00 | 18.00 | 14.77 |
August | 0.749935E+11 | 88203.11 | 21-AUG-04:23 | 19.50 | 12.04 | 0.551295E+10 | 7006.58 | 21-AUG-13:00 | 29.00 | 14.55 |
September | 0.551450E+11 | 92835.98 | 11-SEP-04:13 | 16.97 | 8.44 | 0.488936E+10 | 6970.50 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.480309E+11 | 88320.40 | 02-OCT-04:12 | 3.67 | 3.67 | 0.508023E+10 | 6734.94 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.458763E+11 | 84570.57 | 13-NOV-04:02 | 1.00 | 0.92 | 0.502799E+10 | 6734.80 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.434543E+11 | 86478.83 | 18-DEC-05:12 | 2.00 | -2.3 | 0.489755E+10 | 6734.79 | 20-DEC-10:20 | -18.0 | -18.4 |
Annual Sum or Average | 0.630261E+12 | 0.609758E+11 | ||||||||
Minimum of Months | 0.353128E+11 | 82559.36 | -2.8 | -3.4 | 0.459953E+10 | 6734.77 | -18.0 | -18.4 | ||
Maximum of Months | 0.770404E+11 | 92835.98 | 19.50 | 14.77 | 0.551295E+10 | 7760.00 | 29.40 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259515E+11 | 68643.93 | 27-JAN-06:02 | -1.2 | -1.2 | 0.498607E+10 | 6734.78 | 10-JAN-10:20 | -1.2 | -1.2 |
February | 0.230826E+11 | 67793.26 | 28-FEB-06:03 | -3.0 | -3.4 | 0.446643E+10 | 6734.73 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.313517E+11 | 70376.54 | 13-MAR-05:03 | 6.17 | 0.88 | 0.542645E+10 | 6734.78 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.280254E+11 | 72931.37 | 21-APR-05:02 | 5.83 | 3.87 | 0.484134E+10 | 6734.99 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.385983E+11 | 73577.48 | 23-MAY-05:02 | 8.33 | 7.03 | 0.528035E+10 | 6734.79 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.464613E+11 | 76225.81 | 20-JUN-04:12 | 14.80 | 11.84 | 0.526762E+10 | 6915.63 | 22-JUN-09:20 | 24.93 | 15.42 |
July | 0.455992E+11 | 81669.50 | 24-JUL-04:13 | 18.00 | 14.77 | 0.489547E+10 | 7097.56 | 19-JUL-09:00 | 18.00 | 14.77 |
August | 0.477029E+11 | 78168.88 | 28-AUG-04:12 | 14.33 | 14.13 | 0.549675E+10 | 6734.80 | 15-AUG-13:39 | 14.33 | 14.13 |
September | 0.412108E+11 | 77485.44 | 05-SEP-04:12 | 14.40 | 9.51 | 0.487736E+10 | 6735.34 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.328583E+11 | 73036.26 | 10-OCT-04:12 | 9.00 | 5.09 | 0.504581E+10 | 6734.76 | 03-OCT-09:20 | 9.00 | 5.09 |
November | 0.276048E+11 | 71923.32 | 10-NOV-06:02 | 5.67 | 4.71 | 0.496918E+10 | 6734.78 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.238079E+11 | 55676.37 | 05-DEC-06:03 | -3.0 | -4.3 | 0.472237E+10 | 6734.72 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.412255E+12 | 0.602752E+11 | ||||||||
Minimum of Months | 0.230826E+11 | 55676.37 | -3.0 | -4.3 | 0.446643E+10 | 6734.72 | -9.0 | -9.0 | ||
Maximum of Months | 0.477029E+11 | 81669.50 | 18.00 | 14.77 | 0.549675E+10 | 7097.56 | 24.93 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169217E+11 | 31430.31 | 20-JAN-16:20 | 16.00 | 6.84 | 0.444209E+10 | 6734.60 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.154549E+11 | 26030.09 | 24-FEB-17:00 | 6.00 | 1.47 | 0.405539E+10 | 6734.60 | 28-FEB-14:20 | 4.67 | 2.76 |
March | 0.241855E+11 | 55287.21 | 15-MAR-05:03 | 10.83 | 3.07 | 0.511236E+10 | 6734.77 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.231288E+11 | 67732.92 | 21-APR-05:02 | 5.83 | 3.87 | 0.457487E+10 | 6734.99 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.345783E+11 | 69299.68 | 18-MAY-05:03 | 11.67 | 7.89 | 0.521535E+10 | 6734.77 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.489557E+11 | 75966.80 | 19-JUN-04:12 | 16.97 | 11.72 | 0.527180E+10 | 7114.24 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.478186E+11 | 84699.43 | 24-JUL-04:13 | 18.00 | 14.77 | 0.489938E+10 | 7095.82 | 19-JUL-09:00 | 18.00 | 14.77 |
August | 0.491810E+11 | 76428.54 | 28-AUG-04:12 | 14.33 | 14.13 | 0.549611E+10 | 6734.78 | 31-AUG-09:09 | 25.33 | 13.65 |
September | 0.386428E+11 | 77395.43 | 05-SEP-04:12 | 14.40 | 9.51 | 0.485615E+10 | 6786.45 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.238937E+11 | 47688.47 | 11-OCT-05:03 | 10.17 | 3.29 | 0.475366E+10 | 6734.72 | 03-OCT-13:20 | 10.17 | 3.29 |
November | 0.183971E+11 | 33549.64 | 07-NOV-15:50 | 21.17 | 7.21 | 0.452038E+10 | 6734.59 | 17-NOV-14:20 | 13.33 | 5.89 |
December | 0.148560E+11 | 22856.53 | 15-DEC-16:00 | 6.00 | 2.22 | 0.418731E+10 | 6734.54 | 15-DEC-14:20 | 6.00 | 2.22 |
Annual Sum or Average | 0.356014E+12 | 0.573849E+11 | ||||||||
Minimum of Months | 0.148560E+11 | 22856.53 | 5.83 | 1.47 | 0.405539E+10 | 6734.54 | 4.67 | 2.22 | ||
Maximum of Months | 0.491810E+11 | 84699.43 | 21.17 | 14.77 | 0.549611E+10 | 7114.24 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224372E+10 | 3751.41 | 23-JAN-13:40 | 19.33 | 5.70 | 0.577400E+09 | 845.61 | 27-JAN-14:20 | 9.33 | 5.12 |
February | 0.205547E+10 | 4494.23 | 27-FEB-15:30 | 13.50 | 4.54 | 0.518428E+09 | 845.62 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.369788E+10 | 6956.93 | 14-MAR-13:40 | 23.33 | 7.70 | 0.663966E+09 | 845.63 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.422393E+10 | 7716.34 | 20-APR-13:30 | 21.50 | 8.83 | 0.599554E+09 | 845.67 | 13-APR-13:50 | 21.50 | 8.83 |
May | 0.651453E+10 | 9406.73 | 17-MAY-13:30 | 29.00 | 11.78 | 0.661644E+09 | 845.64 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.118034E+11 | 16127.21 | 11-JUN-17:51 | 27.20 | 12.42 | 0.664908E+09 | 957.18 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.129881E+11 | 18050.24 | 02-JUL-18:22 | 27.00 | 12.28 | 0.622403E+09 | 985.60 | 19-JUL-09:00 | 25.00 | 15.80 |
August | 0.115819E+11 | 15227.41 | 20-AUG-15:41 | 28.00 | 14.08 | 0.692496E+09 | 910.77 | 21-AUG-13:00 | 29.00 | 14.55 |
September | 0.739641E+10 | 16047.60 | 10-SEP-14:51 | 31.60 | 12.46 | 0.612000E+09 | 880.10 | 12-SEP-13:50 | 29.40 | 13.74 |
October | 0.379513E+10 | 7655.73 | 10-OCT-14:30 | 25.00 | 8.59 | 0.610504E+09 | 845.65 | 03-OCT-13:09 | 25.00 | 8.59 |
November | 0.287061E+10 | 5774.61 | 09-NOV-13:20 | 20.00 | 8.84 | 0.591523E+09 | 845.61 | 13-NOV-10:20 | 4.67 | 2.45 |
December | 0.218388E+10 | 5048.94 | 04-DEC-12:00 | 20.00 | 6.71 | 0.556216E+09 | 845.62 | 12-DEC-14:09 | 8.00 | 2.07 |
Annual Sum or Average | 0.713550E+11 | 0.737104E+10 | ||||||||
Minimum of Months | 0.205547E+10 | 3751.41 | 13.50 | 4.54 | 0.518428E+09 | 845.61 | 2.67 | 1.45 | ||
Maximum of Months | 0.129881E+11 | 18050.24 | 31.60 | 14.08 | 0.692496E+09 | 985.60 | 37.70 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248331E+10 | 10476.12 | 01-JAN-09:23 | 5.50 | 1.13 | 0.389948E+09 | 544.96 | 10-JAN-10:09 | 2.17 | 2.17 |
February | 0.279093E+10 | 11747.40 | 27-FEB-09:00 | 9.00 | 2.63 | 0.350306E+09 | 544.96 | 23-FEB-10:09 | 9.00 | 2.63 |
March | 0.475591E+10 | 23892.35 | 12-MAR-09:11 | 14.33 | 5.23 | 0.430904E+09 | 546.62 | 13-MAR-09:30 | 15.50 | 5.22 |
April | 0.482176E+10 | 18550.43 | 09-APR-08:62 | 10.17 | 4.69 | 0.386582E+09 | 546.17 | 19-APR-09:09 | 18.17 | 8.45 |
May | 0.691984E+10 | 16605.34 | 28-MAY-08:32 | 11.33 | 8.57 | 0.427493E+09 | 545.99 | 16-MAY-09:09 | 11.33 | 8.57 |
June | 0.115801E+11 | 24865.24 | 11-JUN-07:51 | 17.20 | 10.73 | 0.428630E+09 | 637.13 | 22-JUN-09:20 | 24.93 | 15.42 |
July | 0.118409E+11 | 25361.06 | 23-JUL-07:41 | 24.67 | 14.74 | 0.399950E+09 | 653.53 | 27-JUL-08:50 | 26.50 | 15.79 |
August | 0.113434E+11 | 23986.56 | 06-AUG-08:31 | 24.00 | 15.32 | 0.447014E+09 | 626.94 | 16-AUG-09:30 | 31.00 | 13.20 |
September | 0.810764E+10 | 24909.56 | 04-SEP-08:51 | 24.40 | 13.41 | 0.395234E+09 | 551.61 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.430337E+10 | 22987.40 | 09-OCT-09:51 | 15.00 | 8.94 | 0.394241E+09 | 544.98 | 03-OCT-13:09 | 15.00 | 8.94 |
November | 0.288072E+10 | 11612.38 | 05-NOV-09:42 | 17.00 | 5.92 | 0.388102E+09 | 544.95 | 03-NOV-09:20 | 17.00 | 5.92 |
December | 0.201254E+10 | 7527.29 | 18-DEC-09:10 | 0.50 | -2.0 | 0.367322E+09 | 544.95 | 22-DEC-10:20 | -17.3 | -17.7 |
Annual Sum or Average | 0.738405E+11 | 0.480573E+10 | ||||||||
Minimum of Months | 0.201254E+10 | 7527.29 | 0.50 | -2.0 | 0.350306E+09 | 544.95 | -17.3 | -17.7 | ||
Maximum of Months | 0.118409E+11 | 25361.06 | 24.67 | 15.32 | 0.447014E+09 | 653.53 | 31.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104937E+11 | 25652.50 | 22-JAN-12:41 | 6.83 | 3.54 | 0.620516E+09 | 963.52 | 20-JAN-14:09 | 6.83 | 3.54 |
February | 0.956810E+10 | 25991.92 | 26-FEB-12:52 | 18.00 | 4.84 | 0.554774E+09 | 912.62 | 17-FEB-14:09 | 18.00 | 4.84 |
March | 0.101435E+11 | 26185.34 | 12-MAR-12:31 | 18.67 | 6.04 | 0.668725E+09 | 930.28 | 13-MAR-13:20 | 22.33 | 6.86 |
April | 0.716513E+10 | 23479.45 | 09-APR-11:23 | 16.00 | 5.67 | 0.594321E+09 | 849.26 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.815348E+10 | 14528.22 | 07-MAY-14:52 | 23.00 | 9.38 | 0.659871E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.128608E+11 | 23272.57 | 11-JUN-15:11 | 28.83 | 13.00 | 0.664414E+09 | 948.78 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.144633E+11 | 25050.23 | 23-JUL-12:22 | 33.00 | 16.02 | 0.619863E+09 | 930.34 | 19-JUL-09:00 | 33.00 | 16.02 |
August | 0.160917E+11 | 24222.04 | 20-AUG-13:42 | 27.83 | 14.68 | 0.696405E+09 | 953.14 | 31-AUG-10:00 | 29.00 | 12.53 |
September | 0.139727E+11 | 27519.00 | 10-SEP-12:11 | 30.90 | 12.81 | 0.617556E+09 | 1011.46 | 12-SEP-13:50 | 29.40 | 13.74 |
October | 0.117078E+11 | 28990.92 | 09-OCT-13:11 | 22.00 | 8.98 | 0.616600E+09 | 983.46 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.112277E+11 | 26772.34 | 05-NOV-12:21 | 20.50 | 6.10 | 0.620472E+09 | 972.24 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.934415E+10 | 26687.54 | 17-DEC-12:51 | 18.00 | 5.78 | 0.592134E+09 | 933.84 | 14-DEC-14:09 | 18.00 | 5.78 |
Annual Sum or Average | 0.135192E+12 | 0.752565E+10 | ||||||||
Minimum of Months | 0.716513E+10 | 14528.22 | 6.83 | 3.54 | 0.554774E+09 | 845.68 | 6.83 | 3.54 | ||
Maximum of Months | 0.160917E+11 | 28990.92 | 33.00 | 16.02 | 0.696405E+09 | 1011.46 | 37.70 | 16.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365609E+10 | 14468.20 | 22-JAN-15:22 | 8.50 | 4.34 | 0.396687E+09 | 544.95 | 10-JAN-10:20 | 8.50 | 4.34 |
February | 0.424515E+10 | 22726.03 | 26-FEB-16:12 | 17.33 | 4.97 | 0.362469E+09 | 544.96 | 08-FEB-14:09 | 17.33 | 4.97 |
March | 0.754015E+10 | 29972.03 | 12-MAR-15:51 | 18.00 | 5.76 | 0.443518E+09 | 544.96 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.811805E+10 | 26546.51 | 08-APR-17:42 | 14.33 | 4.60 | 0.395132E+09 | 544.99 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.814327E+10 | 27610.55 | 07-MAY-15:31 | 22.33 | 8.84 | 0.428523E+09 | 544.98 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.134481E+11 | 33747.25 | 11-JUN-15:51 | 28.90 | 12.69 | 0.429011E+09 | 600.49 | 26-JUN-14:00 | 39.40 | 15.63 |
July | 0.138368E+11 | 33691.34 | 02-JUL-16:22 | 28.00 | 12.40 | 0.399702E+09 | 611.73 | 12-JUL-15:50 | 32.17 | 13.94 |
August | 0.154114E+11 | 30799.50 | 13-AUG-16:21 | 22.50 | 10.02 | 0.447607E+09 | 596.90 | 15-AUG-15:00 | 30.00 | 14.16 |
September | 0.908507E+10 | 32890.76 | 10-SEP-16:11 | 31.63 | 12.58 | 0.396371E+09 | 580.76 | 12-SEP-15:00 | 31.10 | 14.26 |
October | 0.674872E+10 | 31789.32 | 09-OCT-14:31 | 22.00 | 8.98 | 0.406396E+09 | 544.99 | 03-OCT-13:09 | 22.00 | 8.98 |
November | 0.564543E+10 | 27959.25 | 05-NOV-15:01 | 20.67 | 6.59 | 0.404394E+09 | 544.95 | 16-NOV-14:09 | 16.00 | 6.65 |
December | 0.498076E+10 | 25993.63 | 17-DEC-14:51 | 17.50 | 5.64 | 0.389332E+09 | 544.95 | 21-DEC-14:30 | -16.0 | -16.7 |
Annual Sum or Average | 0.100859E+12 | 0.489914E+10 | ||||||||
Minimum of Months | 0.365609E+10 | 14468.20 | 8.50 | 4.34 | 0.362469E+09 | 544.95 | -16.0 | -16.7 | ||
Maximum of Months | 0.154114E+11 | 33747.25 | 31.63 | 12.69 | 0.447607E+09 | 611.73 | 39.40 | 15.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121194E+10 | 2210.11 | 20-JAN-15:10 | 19.67 | 6.93 | 0.505040E+09 | 823.32 | 20-JAN-14:00 | 19.67 | 6.93 |
February | 0.105479E+10 | 2224.22 | 27-FEB-15:40 | 13.33 | 4.47 | 0.452550E+09 | 823.78 | 27-FEB-14:00 | 13.33 | 4.47 |
March | 0.209625E+10 | 5289.95 | 14-MAR-14:30 | 23.00 | 7.59 | 0.597329E+09 | 845.62 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.234549E+10 | 5876.55 | 20-APR-13:30 | 21.50 | 8.83 | 0.553860E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.504289E+10 | 8593.08 | 17-MAY-13:30 | 29.00 | 11.78 | 0.651870E+09 | 845.63 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.917128E+10 | 15773.10 | 25-JUN-17:32 | 31.97 | 14.00 | 0.662484E+09 | 911.68 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.892648E+10 | 16007.80 | 16-JUL-14:53 | 36.00 | 14.77 | 0.616314E+09 | 917.42 | 19-JUL-09:00 | 25.00 | 15.80 |
August | 0.793288E+10 | 13070.41 | 20-AUG-15:31 | 28.00 | 14.04 | 0.689695E+09 | 846.58 | 18-AUG-13:20 | 28.00 | 14.04 |
September | 0.555514E+10 | 14625.38 | 10-SEP-15:01 | 31.70 | 12.51 | 0.605352E+09 | 845.70 | 05-SEP-09:09 | 31.70 | 12.51 |
October | 0.232124E+10 | 5675.14 | 11-OCT-14:00 | 27.00 | 9.73 | 0.565935E+09 | 845.62 | 11-OCT-13:20 | 27.00 | 9.73 |
November | 0.150864E+10 | 3863.95 | 09-NOV-13:30 | 20.00 | 8.78 | 0.515504E+09 | 845.62 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.902634E+09 | 2138.07 | 04-DEC-14:40 | 19.33 | 6.32 | 0.472103E+09 | 802.53 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.480697E+11 | 0.688804E+10 | ||||||||
Minimum of Months | 0.902634E+09 | 2138.07 | 13.33 | 4.47 | 0.452550E+09 | 802.53 | 11.67 | 3.37 | ||
Maximum of Months | 0.917128E+10 | 16007.80 | 36.00 | 14.77 | 0.689695E+09 | 917.42 | 37.70 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139812E+10 | 7457.71 | 20-JAN-09:40 | 12.67 | 4.18 | 0.270266E+09 | 548.50 | 10-JAN-11:09 | 12.67 | 4.18 |
February | 0.181753E+10 | 16038.11 | 26-FEB-10:41 | 13.83 | 3.52 | 0.247113E+09 | 548.50 | 17-FEB-11:09 | 13.83 | 3.52 |
March | 0.374536E+10 | 22523.63 | 26-MAR-09:52 | 13.10 | 4.95 | 0.305944E+09 | 548.51 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.385576E+10 | 17129.87 | 09-APR-09:02 | 11.33 | 5.12 | 0.276885E+09 | 548.52 | 13-APR-10:09 | 15.17 | 8.09 |
May | 0.631940E+10 | 18259.63 | 28-MAY-08:52 | 12.00 | 8.64 | 0.314068E+09 | 548.54 | 31-MAY-10:09 | 25.17 | 13.22 |
June | 0.107410E+11 | 27338.22 | 11-JUN-08:41 | 19.53 | 10.79 | 0.315496E+09 | 599.37 | 22-JUN-08:39 | 24.93 | 15.42 |
July | 0.100183E+11 | 27424.20 | 09-JUL-09:01 | 24.67 | 12.86 | 0.294768E+09 | 598.98 | 27-JUL-08:50 | 26.50 | 15.79 |
August | 0.102972E+11 | 28758.40 | 06-AUG-08:51 | 25.00 | 15.42 | 0.328638E+09 | 548.56 | 30-AUG-10:09 | 25.17 | 12.29 |
September | 0.728642E+10 | 26615.02 | 04-SEP-09:41 | 25.82 | 13.37 | 0.290838E+09 | 548.54 | 18-SEP-10:09 | 25.18 | 11.04 |
October | 0.334002E+10 | 18728.10 | 01-OCT-09:12 | 13.33 | 7.78 | 0.280522E+09 | 548.51 | 10-OCT-14:09 | 25.00 | 8.67 |
November | 0.176062E+10 | 9045.27 | 07-NOV-09:00 | 14.00 | 4.09 | 0.269762E+09 | 548.50 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.886296E+09 | 4543.94 | 14-DEC-09:30 | 9.00 | 1.12 | 0.249198E+09 | 548.49 | 15-DEC-15:09 | 8.50 | 2.91 |
Annual Sum or Average | 0.614660E+11 | 0.344350E+10 | ||||||||
Minimum of Months | 0.886296E+09 | 4543.94 | 9.00 | 1.12 | 0.247113E+09 | 548.49 | 0.33 | -0.4 | ||
Maximum of Months | 0.107410E+11 | 28758.40 | 25.82 | 15.42 | 0.328638E+09 | 599.37 | 26.50 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108191E+11 | 28074.96 | 01-JAN-13:11 | 4.67 | 1.33 | 0.619523E+09 | 1047.88 | 20-JAN-14:09 | 20.83 | 6.93 |
February | 0.969926E+10 | 29626.16 | 26-FEB-12:41 | 17.83 | 4.77 | 0.554959E+09 | 980.04 | 17-FEB-14:09 | 17.83 | 4.77 |
March | 0.957135E+10 | 26499.30 | 26-MAR-12:31 | 10.00 | 5.27 | 0.653609E+09 | 969.47 | 15-MAR-13:39 | 10.00 | 5.27 |
April | 0.596386E+10 | 22754.93 | 09-APR-12:23 | 15.50 | 4.87 | 0.575889E+09 | 847.70 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.730195E+10 | 13500.05 | 07-MAY-15:21 | 22.50 | 8.97 | 0.654005E+09 | 845.68 | 02-MAY-13:30 | 22.50 | 8.97 |
June | 0.107011E+11 | 23975.83 | 25-JUN-14:11 | 33.07 | 13.24 | 0.662400E+09 | 911.68 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.109571E+11 | 24272.20 | 30-JUL-11:32 | 24.67 | 19.23 | 0.616225E+09 | 871.09 | 19-JUL-09:00 | 24.67 | 19.23 |
August | 0.134824E+11 | 25696.48 | 27-AUG-12:51 | 26.00 | 15.18 | 0.692707E+09 | 934.00 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.133873E+11 | 27771.61 | 04-SEP-11:41 | 28.12 | 13.34 | 0.616666E+09 | 1050.13 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.115640E+11 | 26844.44 | 09-OCT-13:21 | 22.00 | 8.88 | 0.610574E+09 | 1028.64 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.110235E+11 | 27334.62 | 05-NOV-13:01 | 21.00 | 6.54 | 0.614069E+09 | 1045.45 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.851180E+10 | 29514.31 | 17-DEC-13:21 | 18.00 | 5.77 | 0.577297E+09 | 985.48 | 14-DEC-14:09 | 18.00 | 5.77 |
Annual Sum or Average | 0.122983E+12 | 0.744792E+10 | ||||||||
Minimum of Months | 0.596386E+10 | 13500.05 | 4.67 | 1.33 | 0.554959E+09 | 845.68 | 10.00 | 4.77 | ||
Maximum of Months | 0.134824E+11 | 29626.16 | 33.07 | 19.23 | 0.692707E+09 | 1050.13 | 37.70 | 19.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215262E+10 | 10112.92 | 20-JAN-15:40 | 18.67 | 7.30 | 0.356825E+09 | 544.94 | 09-JAN-14:00 | 18.67 | 7.30 |
February | 0.225659E+10 | 25444.02 | 26-FEB-16:01 | 17.67 | 5.08 | 0.322401E+09 | 544.95 | 28-FEB-14:00 | 4.00 | 3.02 |
March | 0.397555E+10 | 26685.78 | 26-MAR-17:11 | 12.33 | 5.42 | 0.406131E+09 | 544.97 | 10-MAR-14:30 | 12.33 | 5.42 |
April | 0.380894E+10 | 24737.38 | 08-APR-17:03 | 15.67 | 5.07 | 0.369470E+09 | 544.98 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.612917E+10 | 25880.20 | 07-MAY-16:02 | 21.67 | 8.93 | 0.422936E+09 | 544.97 | 10-MAY-13:39 | 24.67 | 8.89 |
June | 0.104411E+11 | 31405.65 | 25-JUN-16:11 | 32.70 | 13.79 | 0.427458E+09 | 557.88 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.911840E+10 | 31077.32 | 02-JUL-17:01 | 28.00 | 12.40 | 0.397563E+09 | 558.20 | 19-JUL-09:00 | 25.00 | 15.80 |
August | 0.957306E+10 | 31009.17 | 13-AUG-17:31 | 22.67 | 10.36 | 0.445679E+09 | 551.55 | 02-AUG-15:00 | 22.67 | 10.36 |
September | 0.699475E+10 | 31019.63 | 10-SEP-16:21 | 31.35 | 12.48 | 0.393047E+09 | 576.35 | 12-SEP-15:00 | 31.10 | 14.26 |
October | 0.410802E+10 | 26631.06 | 09-OCT-16:01 | 21.83 | 8.61 | 0.377868E+09 | 544.96 | 06-OCT-13:20 | 21.83 | 8.61 |
November | 0.251783E+10 | 19931.05 | 05-NOV-15:01 | 20.67 | 6.59 | 0.360018E+09 | 544.99 | 07-NOV-14:30 | 22.00 | 7.34 |
December | 0.154839E+10 | 20091.06 | 17-DEC-15:21 | 16.75 | 5.34 | 0.333676E+09 | 544.97 | 01-DEC-14:00 | 16.75 | 5.34 |
Annual Sum or Average | 0.626244E+11 | 0.461307E+10 | ||||||||
Minimum of Months | 0.154839E+10 | 10112.92 | 12.33 | 5.07 | 0.322401E+09 | 544.94 | 4.00 | 3.02 | ||
Maximum of Months | 0.104411E+11 | 31405.65 | 32.70 | 13.79 | 0.445679E+09 | 576.35 | 37.70 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.648291E+09 | 2165.34 | 20-JAN-16:00 | 18.00 | 7.49 | 0.482013E+09 | 809.89 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.611939E+09 | 2077.30 | 27-FEB-15:10 | 13.83 | 4.68 | 0.435793E+09 | 775.33 | 27-FEB-14:00 | 13.83 | 4.68 |
March | 0.158632E+10 | 5389.96 | 14-MAR-14:30 | 23.00 | 7.59 | 0.571690E+09 | 845.61 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.190854E+10 | 6319.58 | 20-APR-13:30 | 21.50 | 8.83 | 0.529332E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.465319E+10 | 9034.55 | 17-MAY-13:30 | 29.00 | 11.78 | 0.637189E+09 | 845.63 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.954266E+10 | 18272.25 | 25-JUN-16:51 | 32.70 | 14.00 | 0.662469E+09 | 922.81 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.927881E+10 | 18560.26 | 16-JUL-14:51 | 36.00 | 14.77 | 0.616148E+09 | 896.56 | 19-JUL-09:00 | 25.00 | 15.80 |
August | 0.817129E+10 | 17527.96 | 20-AUG-15:31 | 28.00 | 14.04 | 0.688280E+09 | 845.64 | 28-AUG-13:00 | 26.00 | 16.77 |
September | 0.537028E+10 | 14974.81 | 10-SEP-15:51 | 32.20 | 12.77 | 0.598059E+09 | 846.81 | 12-SEP-13:00 | 29.40 | 13.78 |
October | 0.178190E+10 | 5870.62 | 11-OCT-14:30 | 26.50 | 9.60 | 0.537063E+09 | 845.62 | 11-OCT-13:20 | 26.50 | 9.60 |
November | 0.883561E+09 | 3240.47 | 09-NOV-13:40 | 20.00 | 8.72 | 0.493504E+09 | 845.61 | 08-NOV-14:20 | 20.00 | 8.72 |
December | 0.477304E+09 | 1973.90 | 01-DEC-15:00 | 21.00 | 7.36 | 0.456019E+09 | 759.04 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.449141E+11 | 0.670756E+10 | ||||||||
Minimum of Months | 0.477304E+09 | 1973.90 | 13.83 | 4.68 | 0.435793E+09 | 759.04 | 13.83 | 4.68 | ||
Maximum of Months | 0.954266E+10 | 18560.26 | 36.00 | 14.77 | 0.688280E+09 | 922.81 | 37.70 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104654E+10 | 5745.86 | 20-JAN-09:50 | 13.33 | 4.49 | 0.348690E+09 | 544.96 | 10-JAN-10:20 | 13.33 | 4.49 |
February | 0.137182E+10 | 7215.19 | 27-FEB-09:20 | 9.33 | 2.70 | 0.326457E+09 | 544.96 | 23-FEB-10:09 | 9.33 | 2.70 |
March | 0.326728E+10 | 21317.93 | 12-MAR-09:01 | 14.17 | 5.14 | 0.408687E+09 | 544.97 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.351491E+10 | 13951.08 | 21-APR-08:50 | 11.83 | 5.97 | 0.368819E+09 | 544.98 | 13-APR-13:50 | 11.83 | 5.97 |
May | 0.611439E+10 | 15287.87 | 28-MAY-09:12 | 12.67 | 8.79 | 0.422673E+09 | 545.69 | 16-MAY-09:30 | 12.67 | 8.79 |
June | 0.112544E+11 | 24400.14 | 11-JUN-08:52 | 20.00 | 10.75 | 0.427486E+09 | 613.90 | 22-JUN-09:20 | 24.93 | 15.42 |
July | 0.104970E+11 | 27395.49 | 16-JUL-08:11 | 31.00 | 14.43 | 0.397967E+09 | 591.56 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.107194E+11 | 28708.75 | 06-AUG-09:01 | 25.33 | 15.45 | 0.445312E+09 | 546.39 | 31-AUG-09:50 | 26.67 | 13.56 |
September | 0.728520E+10 | 24163.24 | 04-SEP-09:12 | 24.97 | 13.41 | 0.392761E+09 | 546.10 | 08-SEP-09:39 | 25.53 | 11.95 |
October | 0.284502E+10 | 23403.14 | 09-OCT-09:51 | 15.00 | 8.94 | 0.371982E+09 | 544.97 | 03-OCT-13:09 | 15.00 | 8.94 |
November | 0.138513E+10 | 7212.57 | 07-NOV-09:10 | 14.00 | 4.09 | 0.350555E+09 | 544.95 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.689919E+09 | 2604.91 | 14-DEC-09:50 | 9.67 | 1.34 | 0.322233E+09 | 544.95 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.599911E+11 | 0.458362E+10 | ||||||||
Minimum of Months | 0.689919E+09 | 2604.91 | 9.33 | 1.34 | 0.322233E+09 | 544.95 | 0.67 | -0.7 | ||
Maximum of Months | 0.112544E+11 | 28708.75 | 31.00 | 15.45 | 0.445312E+09 | 613.90 | 31.00 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.880530E+10 | 27231.92 | 15-JAN-14:32 | 6.00 | 0.75 | 0.592501E+09 | 997.12 | 20-JAN-14:09 | 20.83 | 6.93 |
February | 0.830310E+10 | 30901.59 | 26-FEB-12:41 | 17.83 | 4.77 | 0.535904E+09 | 921.45 | 17-FEB-14:09 | 17.83 | 4.77 |
March | 0.853022E+10 | 30385.91 | 12-MAR-13:01 | 18.67 | 5.91 | 0.634156E+09 | 938.08 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.529102E+10 | 17299.18 | 21-APR-13:05 | 15.83 | 6.37 | 0.558017E+09 | 848.16 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.683729E+10 | 13838.41 | 16-MAY-13:20 | 27.33 | 12.20 | 0.642075E+09 | 845.67 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.111188E+11 | 27035.99 | 25-JUN-14:11 | 33.07 | 13.24 | 0.661934E+09 | 926.99 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.113435E+11 | 26784.92 | 16-JUL-14:51 | 36.00 | 14.77 | 0.615851E+09 | 875.35 | 12-JUL-13:00 | 36.00 | 14.77 |
August | 0.137575E+11 | 28264.41 | 20-AUG-13:31 | 27.67 | 14.76 | 0.690928E+09 | 915.36 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.131360E+11 | 27936.09 | 04-SEP-12:31 | 29.03 | 13.49 | 0.611663E+09 | 1016.27 | 28-SEP-13:39 | 30.50 | 11.31 |
October | 0.105194E+11 | 32004.25 | 09-OCT-13:11 | 22.00 | 8.98 | 0.587310E+09 | 985.55 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.921645E+10 | 28986.67 | 05-NOV-13:21 | 21.00 | 6.47 | 0.590702E+09 | 994.15 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.688974E+10 | 27829.44 | 03-DEC-13:21 | 17.60 | 6.45 | 0.556239E+09 | 920.82 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.113748E+12 | 0.727728E+10 | ||||||||
Minimum of Months | 0.529102E+10 | 13838.41 | 6.00 | 0.75 | 0.535904E+09 | 845.67 | 12.83 | 4.44 | ||
Maximum of Months | 0.137575E+11 | 32004.25 | 36.00 | 14.77 | 0.690928E+09 | 1016.27 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160846E+10 | 9949.25 | 20-JAN-15:40 | 18.67 | 7.30 | 0.341962E+09 | 544.94 | 24-JAN-14:20 | 17.67 | 6.59 |
February | 0.182290E+10 | 21796.38 | 26-FEB-16:01 | 17.67 | 5.08 | 0.311925E+09 | 544.95 | 28-FEB-14:20 | 4.67 | 2.76 |
March | 0.354874E+10 | 28697.03 | 12-MAR-16:21 | 18.00 | 5.68 | 0.391011E+09 | 544.94 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.349805E+10 | 26111.74 | 08-APR-17:03 | 15.67 | 5.07 | 0.355924E+09 | 544.98 | 13-APR-13:50 | 15.50 | 9.79 |
May | 0.585585E+10 | 21931.69 | 07-MAY-15:42 | 22.17 | 8.70 | 0.416066E+09 | 544.96 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.107168E+11 | 34090.68 | 25-JUN-16:11 | 32.70 | 13.79 | 0.427564E+09 | 590.72 | 26-JUN-14:00 | 39.40 | 15.63 |
July | 0.936436E+10 | 30079.32 | 02-JUL-16:31 | 28.00 | 12.40 | 0.397389E+09 | 551.76 | 12-JUL-15:09 | 32.83 | 14.11 |
August | 0.972952E+10 | 33124.78 | 20-AUG-15:31 | 28.00 | 14.04 | 0.445280E+09 | 555.24 | 02-AUG-15:00 | 28.00 | 14.04 |
September | 0.687069E+10 | 29985.64 | 10-SEP-16:31 | 31.07 | 12.39 | 0.389918E+09 | 571.68 | 12-SEP-15:00 | 31.10 | 14.26 |
October | 0.362853E+10 | 29505.65 | 09-OCT-14:31 | 22.00 | 8.98 | 0.362539E+09 | 544.96 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.197222E+10 | 16531.16 | 05-NOV-15:22 | 20.00 | 6.21 | 0.345996E+09 | 544.94 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.113775E+10 | 7998.74 | 01-DEC-15:30 | 19.50 | 7.14 | 0.321987E+09 | 544.94 | 18-DEC-14:00 | 5.00 | 0.54 |
Annual Sum or Average | 0.597538E+11 | 0.450756E+10 | ||||||||
Minimum of Months | 0.113775E+10 | 7998.74 | 15.67 | 5.07 | 0.311925E+09 | 544.94 | 4.67 | 0.54 | ||
Maximum of Months | 0.107168E+11 | 34090.68 | 32.70 | 14.04 | 0.445280E+09 | 590.72 | 39.40 | 15.63 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148482E+10 | 7856.28 | 05-JAN-06:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.118548E+10 | 4867.81 | 27-FEB-15:50 | 13.17 | 4.40 | 0.00 | 0.00 | 01-FEB-00:10 | 13.17 | 4.40 |
March | 0.297336E+10 | 6879.24 | 13-MAR-16:00 | 23.00 | 6.97 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 6.97 |
April | 0.323302E+10 | 5719.40 | 21-APR-13:50 | 15.17 | 5.71 | 0.00 | 0.00 | 01-APR-00:10 | 15.17 | 5.71 |
May | 0.504207E+10 | 6593.84 | 30-MAY-05:15 | 8.33 | 7.37 | 0.00 | 0.00 | 01-MAY-00:10 | 8.33 | 7.37 |
June | 0.102441E+11 | 12055.98 | 26-JUN-14:58 | 39.40 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 39.40 | 15.63 |
July | 0.114498E+11 | 15126.27 | 17-JUL-05:15 | 20.00 | 10.12 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 10.12 |
August | 0.105035E+11 | 13367.92 | 07-AUG-05:10 | 16.17 | 11.34 | 0.00 | 0.00 | 01-AUG-00:10 | 16.17 | 11.34 |
September | 0.740316E+10 | 13997.38 | 05-SEP-05:08 | 14.30 | 8.64 | 0.00 | 0.00 | 01-SEP-00:10 | 14.30 | 8.64 |
October | 0.372111E+10 | 9783.82 | 10-OCT-05:10 | 8.83 | 5.14 | 0.00 | 0.00 | 01-OCT-00:10 | 8.83 | 5.14 |
November | 0.247078E+10 | 5815.08 | 06-NOV-15:50 | 20.83 | 6.39 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 6.39 |
December | 0.144803E+10 | 6593.30 | 21-DEC-05:01 | -18.2 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -18.2 | -18.4 |
Annual Sum or Average | 0.611593E+11 | 0.00 | ||||||||
Minimum of Months | 0.118548E+10 | 4867.81 | -18.2 | -18.4 | 0.00 | 0.00 | -18.2 | -18.4 | ||
Maximum of Months | 0.114498E+11 | 15126.27 | 39.40 | 15.63 | 0.00 | 0.00 | 39.40 | 15.63 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347627E+09 | 10547.30 | 14-JAN-05:01 | -16.5 | -16.5 | 0.00 | 0.00 | 01-JAN-00:10 | -16.5 | -16.5 |
February | 0.265625E+09 | 11335.93 | 06-FEB-04:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-FEB-00:10 | -10.0 | -10.0 |
March | 0.107365E+10 | 8187.36 | 20-MAR-03:01 | -1.5 | -1.5 | 0.00 | 0.00 | 01-MAR-00:10 | -1.5 | -1.5 |
April | 0.907316E+09 | 9922.30 | 03-APR-04:01 | -8.0 | -8.0 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.0 |
May | 0.303594E+10 | 5074.88 | 18-MAY-14:20 | 23.67 | 11.39 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 11.39 |
June | 0.679253E+10 | 9660.63 | 26-JUN-14:20 | 38.27 | 15.36 | 0.00 | 0.00 | 01-JUN-00:10 | 38.27 | 15.36 |
July | 0.679799E+10 | 9644.21 | 17-JUL-05:15 | 20.00 | 10.12 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 10.12 |
August | 0.673341E+10 | 7848.06 | 21-AUG-05:15 | 19.83 | 12.23 | 0.00 | 0.00 | 01-AUG-00:10 | 19.83 | 12.23 |
September | 0.483333E+10 | 7779.83 | 12-SEP-14:43 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.161426E+10 | 10232.00 | 30-OCT-04:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-OCT-00:10 | -10.0 | -10.0 |
November | 0.560461E+09 | 10937.22 | 29-NOV-05:11 | -10.0 | -10.0 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.0 |
December | 0.237023E+09 | 13962.56 | 20-DEC-04:01 | -19.0 | -19.2 | 0.00 | 0.00 | 01-DEC-00:10 | -19.0 | -19.2 |
Annual Sum or Average | 0.331992E+11 | 0.00 | ||||||||
Minimum of Months | 0.237023E+09 | 5074.88 | -19.0 | -19.2 | 0.00 | 0.00 | -19.0 | -19.2 | ||
Maximum of Months | 0.679799E+10 | 13962.56 | 38.27 | 15.36 | 0.00 | 0.00 | 38.27 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276748E+09 | 5006.30 | 20-JAN-15:05 | 19.67 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 19.67 | 6.93 |
February | 0.430900E+09 | 5009.07 | 18-FEB-14:50 | 19.17 | 7.95 | 0.00 | 0.00 | 01-FEB-00:10 | 19.17 | 7.95 |
March | 0.220689E+10 | 12133.08 | 14-MAR-14:15 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.265732E+10 | 12835.23 | 21-APR-13:50 | 15.17 | 5.71 | 0.00 | 0.00 | 01-APR-00:10 | 15.17 | 5.71 |
May | 0.606154E+10 | 16607.00 | 31-MAY-14:20 | 28.00 | 14.79 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.79 |
June | 0.136885E+11 | 26881.41 | 26-JUN-15:00 | 39.40 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 39.40 | 15.63 |
July | 0.125192E+11 | 20031.70 | 18-JUL-14:20 | 31.00 | 15.32 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 15.32 |
August | 0.126357E+11 | 21400.77 | 16-AUG-15:10 | 36.17 | 16.19 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 16.19 |
September | 0.786058E+10 | 20284.90 | 12-SEP-13:02 | 29.40 | 13.57 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.57 |
October | 0.244523E+10 | 11424.75 | 11-OCT-14:40 | 26.33 | 9.55 | 0.00 | 0.00 | 01-OCT-00:10 | 26.33 | 9.55 |
November | 0.684038E+09 | 7435.45 | 09-NOV-13:05 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.133331E+09 | 2473.67 | 02-DEC-14:20 | 21.33 | 7.39 | 0.00 | 0.00 | 01-DEC-00:10 | 21.33 | 7.39 |
Annual Sum or Average | 0.615999E+11 | 0.00 | ||||||||
Minimum of Months | 0.133331E+09 | 2473.67 | 15.17 | 5.71 | 0.00 | 0.00 | 15.17 | 5.71 | ||
Maximum of Months | 0.136885E+11 | 26881.41 | 39.40 | 16.19 | 0.00 | 0.00 | 39.40 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351341E+10 | 2515.57 | 23-JAN-16:40 | 15.67 | 5.76 | 95230891.00 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.781415E+10 | 4498.49 | 21-FEB-17:00 | 8.00 | 2.80 | 86396812.97 | 126.83 | 23-FEB-10:00 | 6.00 | 3.52 |
March | 0.141707E+11 | 7146.28 | 31-MAR-24:00 | 6.10 | 2.00 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.10 | 2.00 |
April | 0.186989E+11 | 8402.75 | 08-APR-18:00 | 14.00 | 4.47 | 91605671.75 | 126.83 | 28-APR-09:09 | 10.17 | 7.81 |
May | 0.438514E+10 | 3479.09 | 31-MAY-24:00 | 16.00 | 10.67 | 99237733.65 | 126.85 | 22-MAY-13:39 | 16.00 | 10.67 |
June | 0.958602E+10 | 5458.59 | 30-JUN-24:00 | 22.50 | 11.08 | 98962934.62 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.150421E+11 | 7263.99 | 31-JUL-24:00 | 18.90 | 16.75 | 91884746.68 | 126.85 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.199233E+11 | 8673.62 | 05-AUG-18:40 | 19.33 | 15.14 | 0.103738E+09 | 138.94 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.451289E+10 | 3366.82 | 30-SEP-24:00 | 10.40 | 8.79 | 91608319.92 | 126.85 | 01-SEP-13:09 | 10.40 | 8.79 |
October | 0.926559E+10 | 5039.32 | 09-OCT-16:45 | 21.17 | 8.73 | 95231563.08 | 126.84 | 03-OCT-13:00 | 21.17 | 8.73 |
November | 0.137227E+11 | 6533.36 | 05-NOV-16:13 | 17.67 | 5.18 | 94301072.54 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.189294E+11 | 8244.40 | 03-DEC-15:55 | 16.00 | 6.27 | 91880777.40 | 126.82 | 07-DEC-14:09 | 1.00 | -4.2 |
Annual Sum or Average | 0.139564E+12 | 0.114332E+10 | ||||||||
Minimum of Months | 0.351341E+10 | 2515.57 | 6.10 | 2.00 | 86396812.97 | 126.82 | 1.00 | -4.2 | ||
Maximum of Months | 0.199233E+11 | 8673.62 | 22.50 | 16.75 | 0.103738E+09 | 138.94 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189311E+10 | 2335.83 | 23-JAN-16:40 | 15.67 | 5.76 | 95227076.25 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.603839E+10 | 4226.16 | 23-FEB-17:00 | 5.00 | 2.11 | 86396811.03 | 126.83 | 23-FEB-10:00 | 5.00 | 2.11 |
March | 0.122976E+11 | 6683.09 | 31-MAR-23:30 | 6.75 | 2.17 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.75 | 2.17 |
April | 0.167464E+11 | 7963.23 | 08-APR-18:00 | 14.00 | 4.47 | 91605735.59 | 126.83 | 28-APR-13:39 | 17.00 | 11.96 |
May | 0.372273E+10 | 3280.30 | 31-MAY-24:00 | 16.00 | 10.67 | 99237237.32 | 126.85 | 22-MAY-09:00 | 16.00 | 10.67 |
June | 0.892192E+10 | 5222.11 | 30-JUN-24:00 | 22.50 | 11.08 | 98962778.51 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.140535E+11 | 6861.00 | 31-JUL-24:00 | 18.90 | 16.75 | 91885186.96 | 126.85 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.188535E+11 | 8263.29 | 13-AUG-18:44 | 21.33 | 9.71 | 0.103645E+09 | 137.64 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.390056E+10 | 3025.04 | 30-SEP-23:50 | 10.50 | 8.84 | 91608028.98 | 126.85 | 01-SEP-13:09 | 10.50 | 8.84 |
October | 0.786691E+10 | 4527.60 | 09-OCT-17:00 | 21.00 | 8.75 | 95231491.92 | 126.84 | 03-OCT-13:00 | 21.00 | 8.75 |
November | 0.117367E+11 | 6039.57 | 07-NOV-16:20 | 19.00 | 6.82 | 94301070.44 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.160019E+11 | 7532.47 | 14-DEC-16:00 | 13.00 | 4.65 | 91880814.21 | 126.82 | 07-DEC-14:09 | 13.00 | 4.65 |
Annual Sum or Average | 0.122033E+12 | 0.114322E+10 | ||||||||
Minimum of Months | 0.189311E+10 | 2335.83 | 5.00 | 2.11 | 86396811.03 | 126.82 | 5.00 | 2.11 | ||
Maximum of Months | 0.188535E+11 | 8263.29 | 22.50 | 16.75 | 0.103645E+09 | 137.64 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853934E+09 | 2305.49 | 20-JAN-16:40 | 14.00 | 6.06 | 93738817.24 | 126.83 | 10-JAN-14:00 | 14.00 | 6.06 |
February | 0.445701E+10 | 4178.96 | 17-FEB-17:00 | 13.00 | 6.46 | 86396927.62 | 126.83 | 23-FEB-14:00 | 9.00 | 4.54 |
March | 0.109138E+11 | 6500.47 | 31-MAR-23:20 | 6.97 | 2.22 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.97 | 2.22 |
April | 0.153735E+11 | 8018.13 | 08-APR-18:00 | 14.00 | 4.47 | 91605818.00 | 126.83 | 28-APR-13:39 | 17.00 | 11.96 |
May | 0.327718E+10 | 3219.97 | 31-MAY-23:50 | 16.12 | 10.64 | 99222743.30 | 126.84 | 30-MAY-09:00 | 16.12 | 10.64 |
June | 0.892339E+10 | 5218.70 | 30-JUN-24:00 | 22.50 | 11.08 | 98962956.56 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.140676E+11 | 6770.73 | 31-JUL-24:00 | 18.90 | 16.75 | 91885270.18 | 126.85 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.188247E+11 | 8423.12 | 13-AUG-18:41 | 21.33 | 9.71 | 0.103549E+09 | 136.69 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.363694E+10 | 3138.17 | 10-SEP-17:31 | 29.77 | 11.98 | 91608199.44 | 126.85 | 01-SEP-13:09 | 29.77 | 11.98 |
October | 0.658766E+10 | 4521.42 | 09-OCT-16:48 | 21.17 | 8.73 | 95231465.52 | 126.83 | 03-OCT-13:00 | 21.17 | 8.73 |
November | 0.100412E+11 | 6051.94 | 07-NOV-16:20 | 19.00 | 6.82 | 94301101.07 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.139784E+11 | 7460.57 | 14-DEC-16:00 | 13.00 | 4.65 | 91880825.70 | 126.82 | 07-DEC-14:09 | 13.00 | 4.65 |
Annual Sum or Average | 0.110935E+12 | 0.114162E+10 | ||||||||
Minimum of Months | 0.853934E+09 | 2305.49 | 6.97 | 2.22 | 86396927.62 | 126.82 | 5.00 | 2.22 | ||
Maximum of Months | 0.188247E+11 | 8423.12 | 29.77 | 16.75 | 0.103549E+09 | 136.69 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237653E+12 | 91828.25 | 02-JAN-15:00 | 0.00 | -1.4 | 0.206153E+10 | 2745.52 | 09-JAN-10:09 | 12.33 | 3.90 |
February | 0.434532E+12 | 183349.52 | 27-FEB-17:00 | 13.00 | 4.60 | 0.187030E+10 | 2745.77 | 02-FEB-10:09 | 13.00 | 4.60 |
March | 0.727745E+12 | 358864.08 | 31-MAR-24:00 | 6.10 | 2.00 | 0.223484E+10 | 2745.89 | 30-MAR-09:09 | 6.10 | 2.00 |
April | 0.941626E+12 | 367013.33 | 10-APR-16:00 | 11.00 | 2.07 | 0.198319E+10 | 2751.21 | 28-APR-13:00 | 18.00 | 12.50 |
May | 0.240018E+12 | 175842.08 | 31-MAY-24:00 | 16.00 | 10.67 | 0.214819E+10 | 2746.81 | 17-MAY-13:00 | 16.00 | 10.67 |
June | 0.471569E+12 | 268839.65 | 30-JUN-24:00 | 22.50 | 11.08 | 0.214290E+10 | 2749.19 | 02-JUN-09:00 | 22.50 | 11.08 |
July | 0.734024E+12 | 359829.91 | 31-JUL-24:00 | 18.90 | 16.75 | 0.198993E+10 | 2750.79 | 21-JUL-09:00 | 18.90 | 16.75 |
August | 0.978977E+12 | 369236.96 | 14-AUG-16:00 | 33.00 | 12.83 | 0.223880E+10 | 2903.80 | 04-AUG-09:00 | 33.00 | 12.83 |
September | 0.236798E+12 | 176396.74 | 30-SEP-24:00 | 10.40 | 8.79 | 0.198333E+10 | 2747.64 | 11-SEP-13:00 | 10.40 | 8.79 |
October | 0.486927E+12 | 266210.20 | 31-OCT-24:00 | -5.8 | -5.8 | 0.206153E+10 | 2745.70 | 26-OCT-09:09 | -5.8 | -5.8 |
November | 0.707767E+12 | 276600.71 | 07-NOV-17:00 | 15.00 | 5.62 | 0.204142E+10 | 2745.76 | 09-NOV-10:09 | 18.33 | 8.73 |
December | 0.975328E+12 | 368062.91 | 04-DEC-17:00 | 12.00 | 4.76 | 0.198896E+10 | 2745.53 | 06-DEC-10:50 | -2.0 | -3.7 |
Annual Sum or Average | 0.717296E+13 | 0.247449E+11 | ||||||||
Minimum of Months | 0.236798E+12 | 91828.25 | -5.8 | -5.8 | 0.187030E+10 | 2745.52 | -5.8 | -5.8 | ||
Maximum of Months | 0.978977E+12 | 369236.96 | 33.00 | 16.75 | 0.223880E+10 | 2903.80 | 33.00 | 16.75 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 3693275.86 | 30777.30 | 06-FEB-06:02 | -10.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 24365999.59 | 37335.38 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 28059275.46 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 24365999.59 | 37335.38 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199907E+10 | 70347.54 | 17-JAN-04:11 | -1.7 |
February | 0.202889E+10 | 73847.38 | 06-FEB-04:01 | -10.0 |
March | 0.917918E+09 | 71883.06 | 20-MAR-03:01 | -1.5 |
April | 0.119235E+10 | 69557.49 | 03-APR-03:01 | -8.0 |
May | 38785591.05 | 60367.73 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.655706E+09 | 67361.08 | 30-OCT-04:01 | -10.0 |
November | 0.937674E+09 | 65146.71 | 27-NOV-05:01 | -7.0 |
December | 0.272843E+10 | 73120.08 | 26-DEC-04:01 | 0.50 |
Annual Sum or Average | 0.104988E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.272843E+10 | 73847.38 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102620E+09 | 11637.64 | 06-JAN-05:01 | -7.8 |
February | 73664596.11 | 11207.89 | 08-FEB-06:01 | -5.8 |
March | 957287.11 | 10837.51 | 20-MAR-05:01 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 8123209.22 | 10986.52 | 31-OCT-05:02 | -8.2 |
November | 27600233.14 | 11104.42 | 30-NOV-06:01 | -12.0 |
December | 0.312139E+09 | 12034.51 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.525104E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.312139E+09 | 12034.51 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78102691.86 | 10528.76 | 06-JAN-05:01 | -7.8 |
February | 88257097.14 | 10408.23 | 06-FEB-05:01 | -10.0 |
March | 3472064.89 | 9637.21 | 20-MAR-05:01 | 0.00 |
April | 3208880.26 | 6322.76 | 03-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 21480638.01 | 9943.62 | 31-OCT-05:02 | -8.2 |
November | 44378636.49 | 9713.83 | 30-NOV-06:01 | -12.0 |
December | 0.264405E+09 | 11419.83 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.503305E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.264405E+09 | 11419.83 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123205E+09 | 15782.71 | 06-JAN-05:01 | -7.8 |
February | 0.212558E+09 | 16574.92 | 06-FEB-05:01 | -10.0 |
March | 26069939.90 | 15097.54 | 20-MAR-04:01 | 0.83 |
April | 42811779.63 | 13928.30 | 03-APR-04:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 80924124.55 | 14941.27 | 31-OCT-05:02 | -8.2 |
November | 76148827.52 | 15116.08 | 30-NOV-05:01 | -12.8 |
December | 0.323519E+09 | 16869.45 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.885236E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.323519E+09 | 16869.45 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7052379.46 | 7227.30 | 05-JAN-06:01 | -17.0 |
February | 1047342.73 | 4870.41 | 06-FEB-06:02 | -10.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 1737698.18 | 6295.22 | 21-DEC-06:01 | -19.0 |
Annual Sum or Average | 9837420.37 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 7052379.46 | 7227.30 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122367E+10 | 12091.46 | 05-JAN-04:01 | -16.2 |
February | 0.156237E+10 | 12804.94 | 06-FEB-04:01 | -10.0 |
March | 0.568380E+09 | 12302.16 | 20-MAR-03:01 | -1.5 |
April | 0.305641E+09 | 11967.48 | 17-APR-03:01 | -8.0 |
May | 4543022.49 | 9152.88 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 2829512.12 | 5317.63 | 22-SEP-05:03 | -1.7 |
October | 0.461191E+09 | 11631.59 | 30-OCT-04:01 | -10.0 |
November | 0.833765E+09 | 12056.48 | 30-NOV-04:02 | -13.8 |
December | 0.264717E+10 | 13532.78 | 24-DEC-03:02 | -20.8 |
Annual Sum or Average | 0.760956E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.8 | |
Maximum of Months | 0.264717E+10 | 13532.78 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533163E+09 | 15497.55 | 06-JAN-05:01 | -7.8 |
February | 0.749851E+09 | 17032.88 | 06-FEB-04:01 | -10.0 |
March | 0.290454E+09 | 16346.06 | 20-MAR-03:01 | -1.5 |
April | 0.172462E+09 | 15229.16 | 17-APR-04:01 | -8.0 |
May | 2333514.97 | 6721.63 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 1292627.18 | 2929.54 | 22-SEP-05:03 | -1.7 |
October | 0.306758E+09 | 15233.82 | 30-OCT-04:01 | -10.0 |
November | 0.447204E+09 | 15658.40 | 29-NOV-05:11 | -10.0 |
December | 0.132201E+10 | 18059.61 | 24-DEC-03:02 | -20.8 |
Annual Sum or Average | 0.382553E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.8 | |
Maximum of Months | 0.132201E+10 | 18059.61 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390511E+09 | 17675.68 | 06-JAN-05:01 | -7.8 |
February | 0.796731E+09 | 19388.99 | 06-FEB-04:01 | -10.0 |
March | 0.345073E+09 | 18592.48 | 20-MAR-03:01 | -1.5 |
April | 0.269690E+09 | 17583.03 | 17-APR-04:01 | -8.0 |
May | 4903795.20 | 9551.06 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 1227008.89 | 2952.71 | 22-SEP-05:03 | -1.7 |
October | 0.384208E+09 | 17571.36 | 31-OCT-04:01 | -8.0 |
November | 0.387299E+09 | 17861.07 | 29-NOV-05:11 | -10.0 |
December | 0.114539E+10 | 19238.71 | 22-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.372503E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.8 | |
Maximum of Months | 0.114539E+10 | 19388.99 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400204E+09 | 15459.84 | 06-JAN-05:01 | -7.8 |
February | 0.545536E+09 | 17153.47 | 06-FEB-04:01 | -10.0 |
March | 0.173424E+09 | 15156.96 | 20-MAR-04:01 | 0.83 |
April | 0.132577E+09 | 15192.54 | 17-APR-04:01 | -8.0 |
May | 1074035.74 | 3674.92 | 01-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 1466916.64 | 3005.38 | 22-SEP-05:03 | -1.7 |
October | 0.224049E+09 | 15181.18 | 31-OCT-04:01 | -8.0 |
November | 0.293461E+09 | 15491.77 | 29-NOV-05:11 | -10.0 |
December | 0.101144E+10 | 17131.56 | 23-DEC-04:11 | -21.1 |
Annual Sum or Average | 0.278323E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.1 | |
Maximum of Months | 0.101144E+10 | 17153.47 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445752E+10 | 15377.58 | 16-JAN-07:42 | -9.2 |
February | 0.456396E+10 | 15930.89 | 12-FEB-07:12 | -19.0 |
March | 0.258488E+10 | 15968.76 | 19-MAR-06:22 | -14.4 |
April | 0.159230E+10 | 15301.15 | 03-APR-02:53 | -8.0 |
May | 0.129185E+09 | 14145.93 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 53442107.39 | 12644.16 | 22-SEP-04:02 | -0.3 |
October | 0.190673E+10 | 15338.30 | 30-OCT-03:11 | -9.3 |
November | 0.306261E+10 | 15125.79 | 30-NOV-04:11 | -13.7 |
December | 0.676059E+10 | 16243.00 | 24-DEC-03:02 | -20.8 |
Annual Sum or Average | 0.251112E+11 | |||
Minimum of Months | 0.00 | 0.00 | -20.8 | |
Maximum of Months | 0.676059E+10 | 16243.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206379E+10 | 19879.86 | 17-JAN-04:11 | -1.7 |
February | 0.227229E+10 | 20670.85 | 12-FEB-07:12 | -19.0 |
March | 0.134302E+10 | 20713.17 | 19-MAR-06:22 | -14.4 |
April | 0.872399E+09 | 19807.89 | 24-APR-03:01 | -2.0 |
May | 57942631.74 | 18705.58 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 25945251.39 | 11575.43 | 22-SEP-04:02 | -0.3 |
October | 0.116730E+10 | 20232.30 | 30-OCT-03:11 | -9.3 |
November | 0.155662E+10 | 19996.51 | 30-NOV-04:11 | -13.7 |
December | 0.360226E+10 | 21220.29 | 24-DEC-06:22 | -19.0 |
Annual Sum or Average | 0.129616E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 0.360226E+10 | 21220.29 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180485E+10 | 20949.76 | 05-JAN-04:01 | -16.2 |
February | 0.261796E+10 | 22665.62 | 06-FEB-03:52 | -10.0 |
March | 0.188408E+10 | 22795.91 | 19-MAR-06:22 | -14.4 |
April | 0.138319E+10 | 21564.07 | 24-APR-03:01 | -2.0 |
May | 0.133396E+09 | 20304.03 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 41742550.63 | 15737.95 | 22-SEP-04:02 | -0.3 |
October | 0.153741E+10 | 21965.73 | 30-OCT-03:11 | -9.3 |
November | 0.155952E+10 | 21555.56 | 30-NOV-04:11 | -13.7 |
December | 0.350711E+10 | 22952.06 | 24-DEC-06:22 | -19.0 |
Annual Sum or Average | 0.144693E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 0.350711E+10 | 22952.06 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161153E+10 | 20891.66 | 17-JAN-04:11 | -1.7 |
February | 0.172199E+10 | 21371.69 | 06-FEB-05:11 | -10.0 |
March | 0.975560E+09 | 21003.00 | 20-MAR-03:01 | -1.5 |
April | 0.610162E+09 | 20489.51 | 17-APR-03:01 | -8.0 |
May | 51578215.81 | 18762.14 | 01-MAY-04:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 23634407.79 | 9697.40 | 22-SEP-04:02 | -0.3 |
October | 0.830111E+09 | 21182.62 | 30-OCT-03:11 | -9.3 |
November | 0.113966E+10 | 20858.53 | 30-NOV-04:11 | -13.7 |
December | 0.272412E+10 | 22102.30 | 24-DEC-03:02 | -20.8 |
Annual Sum or Average | 0.968834E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.8 | |
Maximum of Months | 0.272412E+10 | 22102.30 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332077E+09 | 9590.82 | 15-JAN-15:21 | 6.50 |
February | 0.581612E+09 | 10524.70 | 26-FEB-15:32 | 17.67 |
March | 0.271966E+09 | 13071.15 | 26-MAR-16:01 | 11.33 |
April | 93989105.82 | 10570.01 | 24-APR-04:01 | -2.0 |
May | 85823327.69 | 10026.12 | 01-MAY-04:11 | 6.00 |
June | 0.120778E+09 | 13347.82 | 11-JUN-15:51 | 28.90 |
July | 0.204405E+09 | 10582.84 | 23-JUL-09:41 | 28.33 |
August | 0.124296E+09 | 12375.77 | 20-AUG-15:01 | 28.00 |
September | 0.121882E+09 | 12410.32 | 10-SEP-14:51 | 31.60 |
October | 0.197452E+09 | 12442.96 | 08-OCT-14:31 | 20.00 |
November | 0.376765E+09 | 14115.80 | 05-NOV-14:21 | 21.00 |
December | 0.621193E+09 | 13463.52 | 17-DEC-14:11 | 17.83 |
Annual Sum or Average | 0.313224E+10 | |||
Minimum of Months | 85823327.69 | 9590.82 | -2.0 | |
Maximum of Months | 0.621193E+09 | 14115.80 | 31.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168924E+10 | 12173.70 | 01-JAN-13:12 | 4.67 |
February | 0.179698E+10 | 13567.78 | 26-FEB-16:01 | 17.67 |
March | 0.103655E+10 | 16164.14 | 26-MAR-15:51 | 11.00 |
April | 0.741655E+09 | 7075.28 | 08-APR-17:42 | 14.33 |
May | 0.120633E+09 | 8146.63 | 07-MAY-15:21 | 22.50 |
June | 85633452.10 | 14267.72 | 11-JUN-16:01 | 28.72 |
July | 0.102198E+09 | 12864.26 | 02-JUL-16:21 | 28.00 |
August | 69592290.65 | 13570.89 | 20-AUG-15:31 | 28.00 |
September | 0.103234E+09 | 13972.45 | 10-SEP-15:01 | 31.70 |
October | 0.474741E+09 | 12700.92 | 15-OCT-15:21 | 15.00 |
November | 0.125024E+10 | 13879.26 | 05-NOV-15:01 | 20.67 |
December | 0.219789E+10 | 13616.18 | 17-DEC-15:21 | 16.75 |
Annual Sum or Average | 0.966858E+10 | |||
Minimum of Months | 69592290.65 | 7075.28 | 4.67 | |
Maximum of Months | 0.219789E+10 | 16164.14 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612211E+10 | 23288.69 | 05-JAN-06:01 | -17.0 |
February | 0.576605E+10 | 28418.65 | 13-FEB-05:22 | -11.0 |
March | 0.401582E+10 | 21101.07 | 20-MAR-05:13 | 0.00 |
April | 0.281249E+10 | 25156.75 | 17-APR-04:22 | -8.0 |
May | 0.755017E+09 | 14247.07 | 05-MAY-05:02 | 6.00 |
June | 0.134037E+09 | 13589.40 | 09-JUN-05:03 | 6.97 |
July | 0.115397E+09 | 11370.21 | 03-JUL-04:12 | 11.00 |
August | 0.137051E+09 | 12268.31 | 14-AUG-05:02 | 15.33 |
September | 0.516187E+09 | 13936.05 | 27-SEP-05:02 | 9.22 |
October | 0.330823E+10 | 22840.12 | 30-OCT-05:01 | -10.0 |
November | 0.444229E+10 | 23415.72 | 30-NOV-06:01 | -12.0 |
December | 0.824835E+10 | 29379.30 | 22-DEC-05:11 | -21.0 |
Annual Sum or Average | 0.363730E+11 | |||
Minimum of Months | 0.115397E+09 | 11370.21 | -21.0 | |
Maximum of Months | 0.824835E+10 | 29379.30 | 15.33 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43522375.33 | 428.70 | 09-JAN-03:15 | 6.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 43522375.33 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 43522375.33 | 428.70 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645324E+09 | 711.60 | 16-JAN-18:05 | -2.8 |
February | 65393375.17 | 665.35 | 06-FEB-02:50 | -11.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 2285856.58 | 674.90 | 30-APR-24:00 | 5.40 |
May | 20684600.77 | 675.36 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 2961884.26 | 243.14 | 22-SEP-05:15 | -1.7 |
October | 4899913.28 | 478.68 | 29-OCT-21:50 | -7.0 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.741549E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.0 | |
Maximum of Months | 0.645324E+09 | 711.60 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.998803E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.848029E+09 | 1549.95 | 06-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.942918E+09 | 1216.44 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.811854E+09 | 931.94 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.852337E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.838071E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.788831E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.897024E+09 | 862.44 | 28-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.822046E+09 | 871.56 | 21-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.907369E+09 | 1402.08 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.978080E+09 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.980178E+09 | 1662.56 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106655E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.788831E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.998803E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.635838E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.543590E+09 | 999.29 | 06-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.606420E+09 | 748.32 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.524298E+09 | 589.99 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.552757E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.543878E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.511769E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.580639E+09 | 562.22 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.530132E+09 | 569.06 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.581040E+09 | 887.81 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.625749E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.625253E+09 | 1071.42 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.686136E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.511769E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.635838E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.954239E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.829221E+09 | 1547.40 | 06-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.937706E+09 | 1201.85 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.813727E+09 | 930.60 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.856080E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.843131E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.793427E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.900285E+09 | 856.42 | 28-AUG-15:00 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.820887E+09 | 855.94 | 21-SEP-15:00 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.896110E+09 | 1388.13 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.944327E+09 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.944176E+09 | 1662.60 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105333E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.793427E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.954239E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.621073E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.535619E+09 | 994.96 | 06-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.602872E+09 | 795.39 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.521603E+09 | 702.64 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.548570E+09 | 509.78 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.539958E+09 | 540.43 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.508187E+09 | 509.78 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.575497E+09 | 553.51 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.527941E+09 | 575.57 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.578853E+09 | 905.57 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.610469E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.613141E+09 | 1071.42 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.678378E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.508187E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.621073E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.996474E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.846215E+09 | 1548.80 | 06-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.941668E+09 | 1211.65 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.811405E+09 | 926.77 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.852095E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.837942E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.788346E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.896394E+09 | 853.22 | 28-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.821298E+09 | 862.89 | 21-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.905560E+09 | 1399.33 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.975851E+09 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.977698E+09 | 1662.56 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106509E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.788346E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.996474E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.634545E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.542673E+09 | 997.43 | 06-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.605807E+09 | 740.72 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.523974E+09 | 586.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.552431E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.543578E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.511481E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.580270E+09 | 556.84 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.529776E+09 | 564.08 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.580354E+09 | 883.33 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.624523E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.624191E+09 | 1071.42 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.685360E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.511481E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.634545E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.953759E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.828653E+09 | 1546.25 | 06-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.936577E+09 | 1196.97 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.813311E+09 | 925.37 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.855735E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.842779E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.793028E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.899762E+09 | 846.91 | 28-AUG-15:00 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.820329E+09 | 846.52 | 21-SEP-15:00 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.894870E+09 | 1385.36 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.943482E+09 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.943925E+09 | 1662.60 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105262E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.793028E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.953759E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620231E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.534946E+09 | 993.04 | 06-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.602471E+09 | 788.22 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.521310E+09 | 693.01 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.548403E+09 | 509.78 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.539826E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.508079E+09 | 509.78 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.575315E+09 | 547.52 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.527654E+09 | 570.92 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.578224E+09 | 901.29 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.609376E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.612468E+09 | 1071.42 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.677830E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.508079E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.620231E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.996433E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.846171E+09 | 1548.56 | 06-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.941641E+09 | 1210.72 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.811364E+09 | 926.56 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.852080E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.837937E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.788339E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.896384E+09 | 852.85 | 28-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.821280E+09 | 862.54 | 21-SEP-15:00 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.905441E+09 | 1398.78 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.975765E+09 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.977600E+09 | 1662.56 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106504E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.788339E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.996433E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.634528E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.542653E+09 | 997.28 | 06-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.605791E+09 | 740.08 | 21-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.523964E+09 | 586.36 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.552421E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.543554E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.511469E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.580262E+09 | 556.63 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.529766E+09 | 563.88 | 21-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.580334E+09 | 882.96 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.624498E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.624170E+09 | 1071.42 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.685341E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.511469E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.634528E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.953745E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.828631E+09 | 1546.00 | 06-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.936532E+09 | 1196.01 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.813263E+09 | 925.15 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.855720E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.842762E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.793014E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.899746E+09 | 846.53 | 28-AUG-15:00 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.820313E+09 | 846.14 | 21-SEP-15:00 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.894763E+09 | 1384.79 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.943458E+09 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.943912E+09 | 1662.60 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105259E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.793014E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.953745E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620199E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.534917E+09 | 992.88 | 06-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.602460E+09 | 787.64 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.521284E+09 | 692.24 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.548396E+09 | 509.78 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.539806E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.508069E+09 | 509.78 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.575314E+09 | 547.32 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.527647E+09 | 570.75 | 22-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.578201E+09 | 900.94 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.609357E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.612455E+09 | 1071.42 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.677811E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.508069E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.620199E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.998803E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223521E+09 |
February | 0.136985E+10 | 0.848029E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346822E+09 |
March | 0.163685E+10 | 0.942918E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | 0.382325E+09 |
April | 0.145243E+10 | 0.811854E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415612E+09 |
May | 0.157338E+10 | 0.852337E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 791577.24 | 0.207337E+09 |
June | 0.156900E+10 | 0.838071E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16115586.85 | 88334934.92 |
July | 0.145680E+10 | 0.788831E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19815437.66 | 89417503.28 |
August | 0.163685E+10 | 0.897024E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10927106.76 | 84529044.20 |
September | 0.145243E+10 | 0.822046E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5769919.06 | 0.132015E+09 |
October | 0.150991E+10 | 0.907369E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112561.38 | 0.290612E+09 |
November | 0.149516E+10 | 0.978080E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253217E+09 |
December | 0.145680E+10 | 0.980178E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479616E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106655E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53532190.96 | 0.299336E+10 |
Minimum of Months | 0.136985E+10 | 0.788831E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84529044.20 |
Maximum of Months | 0.163685E+10 | 0.998803E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19815437.66 | 0.479616E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.635838E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151857E+09 |
February | 0.882782E+09 | 0.543590E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233657E+09 |
March | 0.105485E+10 | 0.606420E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 | 0.255044E+09 |
April | 0.936002E+09 | 0.524298E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274798E+09 |
May | 0.101394E+10 | 0.552757E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527530.35 | 0.139125E+09 |
June | 0.101113E+10 | 0.543878E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10690301.23 | 58967347.47 |
July | 0.938820E+09 | 0.511769E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13189949.73 | 59735970.61 |
August | 0.105485E+10 | 0.580639E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7205055.90 | 55803743.21 |
September | 0.936002E+09 | 0.530132E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3731774.73 | 90091859.97 |
October | 0.973041E+09 | 0.581040E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75037.77 | 0.195686E+09 |
November | 0.963541E+09 | 0.625749E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168832E+09 |
December | 0.938820E+09 | 0.625253E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318348E+09 |
Annual Sum or Average | 0.116768E+11 | 0.686136E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35419651.01 | 0.200195E+10 |
Minimum of Months | 0.882782E+09 | 0.511769E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55803743.21 |
Maximum of Months | 0.105485E+10 | 0.635838E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13189949.73 | 0.318348E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.954239E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233013E+09 |
February | 0.136988E+10 | 0.829221E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356566E+09 |
March | 0.163688E+10 | 0.937706E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385423E+09 |
April | 0.145246E+10 | 0.813727E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409042E+09 |
May | 0.157341E+10 | 0.856080E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 791177.71 | 0.206618E+09 |
June | 0.156904E+10 | 0.843131E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16092367.59 | 87592694.62 |
July | 0.145684E+10 | 0.793427E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19879056.26 | 88370089.15 |
August | 0.163688E+10 | 0.900285E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10665687.75 | 87152092.69 |
September | 0.145246E+10 | 0.820887E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5214276.44 | 0.137848E+09 |
October | 0.150994E+10 | 0.896110E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56115.48 | 0.297717E+09 |
November | 0.149520E+10 | 0.944327E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260512E+09 |
December | 0.145684E+10 | 0.944176E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490833E+09 |
Annual Sum or Average | 0.181198E+11 | 0.105333E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52698681.24 | 0.304069E+10 |
Minimum of Months | 0.136988E+10 | 0.793427E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87152092.69 |
Maximum of Months | 0.163688E+10 | 0.954239E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19879056.26 | 0.490833E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.621073E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158575E+09 |
February | 0.882782E+09 | 0.535619E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248989E+09 |
March | 0.105485E+10 | 0.602872E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 0.278323E+09 |
April | 0.936002E+09 | 0.521603E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305416E+09 |
May | 0.101394E+10 | 0.548570E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527262.35 | 0.149121E+09 |
June | 0.101113E+10 | 0.539958E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10407840.28 | 67359537.01 |
July | 0.938820E+09 | 0.508187E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12912028.26 | 67386920.56 |
August | 0.105485E+10 | 0.575497E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7105410.42 | 68242999.63 |
September | 0.936002E+09 | 0.527941E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3549803.15 | 97913020.29 |
October | 0.973041E+09 | 0.578853E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75038.76 | 0.209410E+09 |
November | 0.963541E+09 | 0.610469E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184088E+09 |
December | 0.938820E+09 | 0.613141E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350691E+09 |
Annual Sum or Average | 0.116768E+11 | 0.678378E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34577384.59 | 0.218552E+10 |
Minimum of Months | 0.882782E+09 | 0.508187E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67359537.01 |
Maximum of Months | 0.105485E+10 | 0.621073E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12912028.26 | 0.350691E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.996474E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470899E+09 |
February | 0.136985E+10 | 0.846215E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738714E+09 |
March | 0.163685E+10 | 0.941668E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806630E+09 |
April | 0.145243E+10 | 0.811405E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873130E+09 |
May | 0.157338E+10 | 0.852095E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1765595.88 | 0.461341E+09 |
June | 0.156900E+10 | 0.837942E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37457846.44 | 0.198572E+09 |
July | 0.145680E+10 | 0.788346E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47572387.70 | 0.197796E+09 |
August | 0.163685E+10 | 0.896394E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25664009.30 | 0.194446E+09 |
September | 0.145243E+10 | 0.821298E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14190822.19 | 0.287102E+09 |
October | 0.150991E+10 | 0.905560E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243069.62 | 0.619777E+09 |
November | 0.149516E+10 | 0.975851E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534525E+09 |
December | 0.145680E+10 | 0.977698E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 | 0.994769E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106509E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126894E+09 | 0.637770E+10 |
Minimum of Months | 0.136985E+10 | 0.788346E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194446E+09 |
Maximum of Months | 0.163685E+10 | 0.996474E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47572387.70 | 0.994769E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.634545E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329824E+09 |
February | 0.649041E+09 | 0.542673E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514113E+09 |
March | 0.773965E+09 | 0.605807E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560974E+09 |
April | 0.688021E+09 | 0.523974E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603189E+09 |
May | 0.744847E+09 | 0.552431E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101631.82 | 0.317978E+09 |
June | 0.742030E+09 | 0.543578E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24048550.78 | 0.137246E+09 |
July | 0.690839E+09 | 0.511481E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30118461.44 | 0.139497E+09 |
August | 0.773965E+09 | 0.580270E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090191.46 | 0.137690E+09 |
September | 0.688021E+09 | 0.529776E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8169666.08 | 0.204513E+09 |
October | 0.715730E+09 | 0.580354E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141460.10 | 0.434468E+09 |
November | 0.708685E+09 | 0.624523E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370372E+09 |
December | 0.690839E+09 | 0.624191E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684376E+09 |
Annual Sum or Average | 0.858171E+10 | 0.685360E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79669961.69 | 0.443424E+10 |
Minimum of Months | 0.649041E+09 | 0.511481E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137246E+09 |
Maximum of Months | 0.773965E+09 | 0.634545E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30118461.44 | 0.684376E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.953759E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536346E+09 |
February | 0.136988E+10 | 0.828653E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812250E+09 |
March | 0.163688E+10 | 0.936577E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865370E+09 |
April | 0.145246E+10 | 0.813311E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904437E+09 |
May | 0.157341E+10 | 0.855735E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1764258.69 | 0.471701E+09 |
June | 0.156904E+10 | 0.842779E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37113204.80 | 0.199496E+09 |
July | 0.145684E+10 | 0.793028E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46770655.42 | 0.201107E+09 |
August | 0.163688E+10 | 0.899762E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24557560.70 | 0.208315E+09 |
September | 0.145246E+10 | 0.820329E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11740389.50 | 0.315458E+09 |
October | 0.150994E+10 | 0.894870E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55357.57 | 0.678236E+09 |
November | 0.149520E+10 | 0.943482E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592529E+09 |
December | 0.145684E+10 | 0.943925E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109937E+10 |
Annual Sum or Average | 0.181198E+11 | 0.105262E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122001E+09 | 0.688461E+10 |
Minimum of Months | 0.136988E+10 | 0.793028E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199496E+09 |
Maximum of Months | 0.163688E+10 | 0.953759E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46770655.42 | 0.109937E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.620231E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336154E+09 |
February | 0.882782E+09 | 0.534946E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523471E+09 |
March | 0.105485E+10 | 0.602471E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572779E+09 |
April | 0.936002E+09 | 0.521310E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614369E+09 |
May | 0.101394E+10 | 0.548403E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1175841.76 | 0.327900E+09 |
June | 0.101113E+10 | 0.539826E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24064330.05 | 0.147098E+09 |
July | 0.938820E+09 | 0.508079E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30106295.26 | 0.146129E+09 |
August | 0.105485E+10 | 0.575315E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16496724.36 | 0.148835E+09 |
September | 0.936002E+09 | 0.527654E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8178154.30 | 0.212515E+09 |
October | 0.973041E+09 | 0.578224E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162034.43 | 0.440049E+09 |
November | 0.963541E+09 | 0.609376E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378491E+09 |
December | 0.938820E+09 | 0.612468E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699567E+09 |
Annual Sum or Average | 0.116768E+11 | 0.677830E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80183380.16 | 0.454736E+10 |
Minimum of Months | 0.882782E+09 | 0.508079E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146129E+09 |
Maximum of Months | 0.105485E+10 | 0.620231E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30106295.26 | 0.699567E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.996433E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537987E+09 |
February | 0.136985E+10 | 0.846171E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870907E+09 |
March | 0.163685E+10 | 0.941641E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948284E+09 |
April | 0.145243E+10 | 0.811364E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100390E+10 |
May | 0.157338E+10 | 0.852080E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2079831.08 | 0.549973E+09 |
June | 0.156900E+10 | 0.837937E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44925136.19 | 0.246420E+09 |
July | 0.145680E+10 | 0.788339E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56421410.53 | 0.245864E+09 |
August | 0.163685E+10 | 0.896384E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30556646.21 | 0.239579E+09 |
September | 0.145243E+10 | 0.821280E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16404829.96 | 0.344434E+09 |
October | 0.150991E+10 | 0.905441E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276439.72 | 0.714415E+09 |
November | 0.149516E+10 | 0.975765E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 720.06 | 0.617095E+09 |
December | 0.145680E+10 | 0.977600E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3603.06 | 0.117609E+10 |
Annual Sum or Average | 0.181194E+11 | 0.106504E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150669E+09 | 0.749495E+10 |
Minimum of Months | 0.136985E+10 | 0.788339E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239579E+09 |
Maximum of Months | 0.163685E+10 | 0.996433E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56421410.53 | 0.117609E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.634528E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373991E+09 |
February | 0.882782E+09 | 0.542653E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605979E+09 |
March | 0.105485E+10 | 0.605791E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662324E+09 |
April | 0.936002E+09 | 0.523964E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697157E+09 |
May | 0.101394E+10 | 0.552421E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1386227.35 | 0.381055E+09 |
June | 0.101113E+10 | 0.543554E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29454102.09 | 0.170262E+09 |
July | 0.938820E+09 | 0.511469E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36577156.07 | 0.173243E+09 |
August | 0.105485E+10 | 0.580262E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19881595.93 | 0.169675E+09 |
September | 0.936002E+09 | 0.529766E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9988222.12 | 0.247348E+09 |
October | 0.973041E+09 | 0.580334E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184272.75 | 0.506156E+09 |
November | 0.963541E+09 | 0.624498E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427379E+09 |
December | 0.938820E+09 | 0.624170E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803495E+09 |
Annual Sum or Average | 0.116768E+11 | 0.685341E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97471576.30 | 0.521807E+10 |
Minimum of Months | 0.882782E+09 | 0.511469E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169675E+09 |
Maximum of Months | 0.105485E+10 | 0.634528E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36577156.07 | 0.803495E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.953745E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614600E+09 |
February | 0.136988E+10 | 0.828631E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957845E+09 |
March | 0.163688E+10 | 0.936532E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102380E+10 |
April | 0.145246E+10 | 0.813263E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104366E+10 |
May | 0.157341E+10 | 0.855720E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2079315.05 | 0.564492E+09 |
June | 0.156904E+10 | 0.842762E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44611698.59 | 0.247433E+09 |
July | 0.145684E+10 | 0.793014E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55715936.57 | 0.249552E+09 |
August | 0.163688E+10 | 0.899746E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29628054.42 | 0.256714E+09 |
September | 0.145246E+10 | 0.820313E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14111011.66 | 0.381949E+09 |
October | 0.150994E+10 | 0.894763E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98297.68 | 0.792742E+09 |
November | 0.149520E+10 | 0.943458E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693585E+09 |
December | 0.145684E+10 | 0.943912E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128715E+10 |
Annual Sum or Average | 0.181198E+11 | 0.105259E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146244E+09 | 0.811353E+10 |
Minimum of Months | 0.136988E+10 | 0.793014E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247433E+09 |
Maximum of Months | 0.163688E+10 | 0.953745E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55715936.57 | 0.128715E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.620199E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385582E+09 |
February | 0.882782E+09 | 0.534917E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619456E+09 |
March | 0.105485E+10 | 0.602460E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678490E+09 |
April | 0.936002E+09 | 0.521284E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714450E+09 |
May | 0.101394E+10 | 0.548396E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1386002.99 | 0.395095E+09 |
June | 0.101113E+10 | 0.539806E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29040686.26 | 0.182022E+09 |
July | 0.938820E+09 | 0.508069E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36219829.46 | 0.180726E+09 |
August | 0.105485E+10 | 0.575314E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19879916.82 | 0.183189E+09 |
September | 0.936002E+09 | 0.527647E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9753301.00 | 0.257267E+09 |
October | 0.973041E+09 | 0.578201E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184291.64 | 0.515822E+09 |
November | 0.963541E+09 | 0.609357E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443317E+09 |
December | 0.938820E+09 | 0.612455E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825850E+09 |
Annual Sum or Average | 0.116768E+11 | 0.677811E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96464028.18 | 0.538126E+10 |
Minimum of Months | 0.882782E+09 | 0.508069E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180726E+09 |
Maximum of Months | 0.105485E+10 | 0.620199E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36219829.46 | 0.825850E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485871E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750015E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821642E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880620E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1152041.53 | 0.433883E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29537063.31 | 0.184557E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37500941.59 | 0.189363E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18940054.64 | 0.184570E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9961037.00 | 0.281669E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84828.34 | 0.624721E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544595E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103262E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97175966.41 | 0.641412E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184557E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37500941.59 | 0.103262E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833562E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129312E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141810E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151399E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2074952.15 | 0.763979E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55077367.92 | 0.320832E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74503768.96 | 0.317916E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35423438.91 | 0.321384E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19340839.71 | 0.491548E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162272.40 | 0.108779E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937450E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173865E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186583E+09 | 0.110383E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317916E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74503768.96 | 0.173865E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838999E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134457E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148164E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157542E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1407659.61 | 0.850025E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48509595.20 | 0.366990E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61608314.27 | 0.367393E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30563508.15 | 0.368628E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14297148.21 | 0.539182E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42340.46 | 0.113289E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965260E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178476E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156429E+09 | 0.116158E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366990E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61608314.27 | 0.178476E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 432.59 | 13-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1549.95 | 06-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 540.06 | 05-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1216.44 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1126.17 | 19-MAR-06:52 |
April | 2010.79 | 03-APR-09:09 | 931.94 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 798.90 | 16-APR-15:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 17-MAY-14:50 | 444.28 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.39 | 25-JUN-17:44 | 263.53 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.97 | 16-JUL-12:00 | 254.80 | 03-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 862.44 | 28-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 | 02-AUG-15:30 | 296.61 | 27-AUG-17:40 |
September | 2010.79 | 01-SEP-09:09 | 871.56 | 21-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.79 | 10-SEP-14:54 | 277.88 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 1402.08 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 11-OCT-14:00 | 674.30 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 651.78 | 01-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 929.45 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.80 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 170.97 | 1126.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 297.63 | 08-JAN-09:00 |
February | 1295.83 | 01-FEB-10:09 | 999.29 | 06-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 354.06 | 05-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 748.32 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 738.77 | 19-MAR-06:52 |
April | 1295.83 | 03-APR-09:09 | 589.99 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 531.88 | 16-APR-15:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 | 17-MAY-14:50 | 293.60 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.22 | 25-JUN-17:44 | 174.47 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.98 | 16-JUL-12:00 | 188.57 | 02-JUL-09:00 |
August | 1295.83 | 01-AUG-09:09 | 562.22 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 | 02-AUG-15:30 | 193.62 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 569.06 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.25 | 10-SEP-14:53 | 184.13 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 887.81 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 11-OCT-14:00 | 446.67 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 425.99 | 01-NOV-03:52 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 610.06 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.47 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 113.98 | 738.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 436.70 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1547.40 | 06-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 549.42 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 1201.85 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1082.78 | 19-MAR-06:52 |
April | 2010.83 | 03-APR-09:09 | 930.60 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 753.43 | 16-APR-15:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 17-MAY-14:50 | 437.08 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.83 | 25-JUN-17:44 | 261.34 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.97 | 16-JUL-12:00 | 250.86 | 03-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 856.42 | 28-AUG-15:00 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 | 02-AUG-15:30 | 321.21 | 27-AUG-17:40 |
September | 2010.83 | 01-SEP-09:09 | 855.94 | 21-SEP-15:00 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 10-SEP-14:54 | 274.67 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 1388.13 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 11-OCT-14:00 | 662.41 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 625.29 | 01-NOV-04:02 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 932.95 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.86 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 170.97 | 1082.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 305.30 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 994.96 | 06-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 383.67 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 795.39 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 789.03 | 19-MAR-06:52 |
April | 1295.83 | 03-APR-09:09 | 702.64 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 581.03 | 16-APR-15:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 | 17-MAY-14:50 | 315.87 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 540.43 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 25-JUN-18:00 | 203.46 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.98 | 16-JUL-12:00 | 184.44 | 03-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 553.51 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 | 02-AUG-15:30 | 251.77 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 575.57 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.84 | 10-SEP-14:56 | 192.16 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 905.57 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 11-OCT-14:00 | 475.83 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 462.99 | 01-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 658.47 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.44 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 113.98 | 789.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 910.57 | 31-JAN-02:00 |
February | 2010.79 | 01-FEB-10:09 | 1548.80 | 06-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1125.32 | 23-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 1211.65 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2367.09 | 19-MAR-06:52 |
April | 2010.79 | 03-APR-09:09 | 926.77 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1678.19 | 15-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 17-MAY-14:50 | 953.40 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.96 | 25-JUN-17:34 | 571.91 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.25 | 16-JUL-12:00 | 552.93 | 03-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 853.22 | 28-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.77 | 02-AUG-15:30 | 705.08 | 27-AUG-18:00 |
September | 2010.79 | 01-SEP-09:09 | 862.89 | 21-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.96 | 10-SEP-14:41 | 613.45 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 1399.33 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 11-OCT-14:00 | 1383.21 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1457.43 | 01-NOV-04:09 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 02-DEC-15:00 | 2037.15 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.93 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 396.25 | 2367.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 614.68 | 13-JAN-05:00 |
February | 1239.33 | 01-FEB-08:09 | 997.43 | 06-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 777.41 | 23-FEB-24:00 |
March | 1239.33 | 01-MAR-08:09 | 740.72 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1577.16 | 19-MAR-06:52 |
April | 1239.33 | 03-APR-07:10 | 586.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1119.04 | 16-APR-15:00 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 17-MAY-14:50 | 639.86 | 03-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.67 | 25-JUN-17:33 | 386.90 | 08-JUN-23:00 |
July | 1239.33 | 03-JUL-07:10 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.17 | 16-JUL-12:00 | 446.65 | 02-JUL-09:00 |
August | 1239.33 | 01-AUG-07:10 | 556.84 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.18 | 02-AUG-15:30 | 501.24 | 27-AUG-18:00 |
September | 1239.33 | 01-SEP-07:10 | 564.08 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.99 | 10-SEP-15:03 | 411.33 | 22-SEP-02:00 |
October | 1239.33 | 02-OCT-07:10 | 883.33 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 11-OCT-14:10 | 939.52 | 29-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 980.40 | 01-NOV-04:04 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1348.95 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.90 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 264.17 | 1577.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 976.93 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1546.25 | 06-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1263.79 | 19-FEB-17:00 |
March | 2010.83 | 01-MAR-10:09 | 1196.97 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2368.19 | 19-MAR-06:52 |
April | 2010.83 | 03-APR-09:09 | 925.37 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1678.18 | 15-APR-04:52 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 17-MAY-14:50 | 970.57 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.31 | 25-JUN-18:00 | 571.38 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.25 | 16-JUL-12:00 | 556.86 | 03-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 846.91 | 28-AUG-15:00 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.76 | 02-AUG-15:30 | 816.71 | 27-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 846.52 | 21-SEP-15:00 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.44 | 10-SEP-14:44 | 620.66 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 1385.36 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 11-OCT-14:00 | 1451.81 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1457.46 | 01-NOV-04:09 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2093.03 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.86 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 396.25 | 2368.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 629.96 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 993.04 | 06-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 804.68 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 788.22 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1579.53 | 19-MAR-06:52 |
April | 1295.83 | 03-APR-09:09 | 693.01 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1118.77 | 15-APR-04:52 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 17-MAY-14:50 | 668.39 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.21 | 25-JUN-18:00 | 425.37 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.17 | 16-JUL-12:00 | 404.11 | 03-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 547.52 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.18 | 02-AUG-15:30 | 568.65 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 570.92 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.96 | 10-SEP-14:50 | 410.68 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 901.29 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | 11-OCT-14:00 | 945.57 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 979.36 | 01-NOV-04:04 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1381.22 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.11 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 264.17 | 1579.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1111.27 | 13-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 1548.56 | 06-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1330.21 | 05-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1210.72 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2916.52 | 19-MAR-06:52 |
April | 2010.79 | 03-APR-09:09 | 926.56 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2053.90 | 15-APR-04:52 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 | 17-MAY-14:50 | 1079.51 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.93 | 25-JUN-18:00 | 699.54 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.13 | 16-JUL-12:00 | 678.41 | 03-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 852.85 | 28-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.79 | 02-AUG-15:30 | 894.92 | 27-AUG-18:00 |
September | 2010.79 | 01-SEP-09:09 | 862.54 | 21-SEP-15:00 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.18 | 10-SEP-14:34 | 715.38 | 21-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1398.78 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 | 11-OCT-14:00 | 1511.34 | 29-OCT-19:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 05-NOV-12:52 | 1787.00 | 01-NOV-04:10 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | 02-DEC-15:00 | 2457.66 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.41 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 486.13 | 2916.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 740.87 | 13-JAN-05:06 |
February | 1295.83 | 01-FEB-10:09 | 997.28 | 06-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 907.73 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 740.08 | 21-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1945.10 | 19-MAR-07:04 |
April | 1295.83 | 03-APR-09:09 | 586.36 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1369.40 | 15-APR-04:52 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 | 17-MAY-14:50 | 728.53 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.48 | 25-JUN-17:33 | 473.00 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.09 | 16-JUL-12:00 | 519.46 | 02-JUL-08:30 |
August | 1295.83 | 01-AUG-09:09 | 556.63 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.86 | 02-AUG-15:30 | 630.07 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 563.88 | 21-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.10 | 10-SEP-14:34 | 481.63 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 882.96 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 11-OCT-14:00 | 1019.29 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1212.10 | 01-NOV-04:05 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1638.45 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.00 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 324.09 | 1945.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1119.52 | 13-JAN-05:04 |
February | 2010.83 | 01-FEB-10:09 | 1546.00 | 06-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1484.67 | 19-FEB-17:00 |
March | 2010.83 | 01-MAR-10:09 | 1196.01 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2917.51 | 19-MAR-06:52 |
April | 2010.83 | 03-APR-09:09 | 925.15 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2056.13 | 15-APR-04:52 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 | 17-MAY-14:50 | 1107.18 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.95 | 25-JUN-17:33 | 698.85 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.13 | 16-JUL-12:00 | 683.84 | 03-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 846.53 | 28-AUG-15:00 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.78 | 02-AUG-15:30 | 1020.59 | 27-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 846.14 | 21-SEP-15:00 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.79 | 10-SEP-14:54 | 729.08 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1384.79 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 11-OCT-14:00 | 1587.80 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1818.14 | 01-NOV-04:06 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2470.72 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.84 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 486.13 | 2917.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 740.86 | 13-JAN-05:07 |
February | 1295.83 | 01-FEB-10:09 | 992.88 | 06-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 947.28 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 787.64 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1949.07 | 19-MAR-06:52 |
April | 1295.83 | 03-APR-09:09 | 692.24 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1372.51 | 15-APR-04:52 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 | 17-MAY-14:50 | 773.19 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.96 | 25-JUN-18:00 | 522.25 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.09 | 16-JUL-12:00 | 495.13 | 03-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 547.32 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.85 | 02-AUG-15:30 | 708.55 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 570.75 | 22-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.20 | 10-SEP-15:00 | 483.11 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 900.94 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 11-OCT-14:00 | 1050.75 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1212.09 | 01-NOV-04:09 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1644.76 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.11 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 324.09 | 1949.07 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 965.36 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1184.57 | 05-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2478.01 | 19-MAR-06:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1662.55 | 16-APR-15:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 17-MAY-14:40 | 964.30 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.74 | 25-JUN-18:00 | 532.13 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.90 | 16-JUL-12:00 | 532.34 | 03-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 | 02-AUG-15:20 | 616.21 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.90 | 10-SEP-14:41 | 604.20 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 11-OCT-14:00 | 1445.66 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1430.88 | 01-NOV-03:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2009.97 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.13 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.90 | 2478.01 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1691.17 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1998.52 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4298.26 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2881.48 | 15-APR-04:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 17-MAY-14:40 | 1681.09 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.67 | 25-JUN-18:00 | 924.69 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.84 | 16-JUL-12:00 | 895.15 | 03-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.14 | 06-AUG-12:00 | 1053.87 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.49 | 10-SEP-15:00 | 1077.98 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 11-OCT-14:00 | 2486.83 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2420.88 | 01-NOV-03:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3493.25 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 895.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.84 | 4298.26 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1631.86 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2092.00 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4269.22 | 19-MAR-06:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2951.95 | 15-APR-04:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 | 17-MAY-13:00 | 1681.02 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.08 | 25-JUN-18:00 | 1023.11 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.00 | 16-JUL-12:00 | 992.90 | 03-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.53 | 02-AUG-15:37 | 1356.05 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.33 | 10-SEP-15:00 | 1101.88 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 | 11-OCT-14:00 | 2433.95 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2375.98 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3709.36 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.00 | 4269.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 107057.11 | 02-JAN-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96938.20 | 27-FEB-07:03 | 14361.80 | 19658.71 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99904.33 | 13-MAR-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96548.29 | 10-APR-06:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102928.33 | 30-MAY-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113796.24 | 15-JUN-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 118314.20 | 03-JUL-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111267.76 | 17-AUG-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 111099.15 | 11-SEP-20:41 | 17952.25 | 32763.91 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 108313.18 | 10-OCT-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 100679.80 | 13-NOV-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 101921.79 | 04-DEC-07:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 96548.29 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 118314.20 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88434.24 | 02-JAN-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82559.36 | 21-FEB-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84492.17 | 13-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85201.30 | 10-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85664.19 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92589.11 | 08-JUN-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 91786.45 | 24-JUL-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88203.11 | 21-AUG-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92835.98 | 11-SEP-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88320.40 | 02-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84570.57 | 13-NOV-04:02 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86478.83 | 18-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82559.36 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92835.98 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 68643.93 | 27-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67793.26 | 28-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70376.54 | 13-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72931.37 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73577.48 | 23-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76225.81 | 20-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81669.50 | 24-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78168.88 | 28-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77485.44 | 05-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73036.26 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71923.32 | 10-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55676.37 | 05-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 55676.37 | 0.00 | 2149.44 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81669.50 | 8061.19 | 3224.16 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 31430.31 | 20-JAN-16:20 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26030.09 | 24-FEB-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55287.21 | 15-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67732.92 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69299.68 | 18-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75966.80 | 19-JUN-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84699.43 | 24-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76428.54 | 28-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77395.43 | 05-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47688.47 | 11-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33549.64 | 07-NOV-15:50 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22856.53 | 15-DEC-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22856.53 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84699.43 | 15316.26 | 13241.18 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3751.41 | 23-JAN-13:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
February | 4494.23 | 27-FEB-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 |
March | 6956.93 | 14-MAR-13:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
April | 7716.34 | 20-APR-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
May | 9406.73 | 17-MAY-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 |
June | 16127.21 | 11-JUN-17:51 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 18050.24 | 02-JUL-18:22 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 |
August | 15227.41 | 20-AUG-15:41 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
September | 16047.60 | 10-SEP-14:51 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 | 0.00 |
October | 7655.73 | 10-OCT-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 0.00 |
November | 5774.61 | 09-NOV-13:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
December | 5048.94 | 04-DEC-12:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3751.41 | 0.00 | 351.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18050.24 | 2010.79 | 791.05 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 | 67.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10476.12 | 01-JAN-09:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.54 |
February | 11747.40 | 27-FEB-09:00 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 |
March | 23892.35 | 12-MAR-09:11 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.58 |
April | 18550.43 | 09-APR-08:62 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.10 |
May | 16605.34 | 28-MAY-08:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 |
June | 24865.24 | 11-JUN-07:51 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.29 |
July | 25361.06 | 23-JUL-07:41 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.86 |
August | 23986.56 | 06-AUG-08:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 |
September | 24909.56 | 04-SEP-08:51 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
October | 22987.40 | 09-OCT-09:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
November | 11612.38 | 05-NOV-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.45 |
December | 7527.29 | 18-DEC-09:10 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7527.29 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | |
Maximum of Months | 25361.06 | 2478.65 | 1019.56 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25652.50 | 22-JAN-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.16 |
February | 25991.92 | 26-FEB-12:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.00 |
March | 26185.34 | 12-MAR-12:31 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.97 |
April | 23479.45 | 09-APR-11:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.18 |
May | 14528.22 | 07-MAY-14:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.38 |
June | 23272.57 | 11-JUN-15:11 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
July | 25050.23 | 23-JUL-12:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 | 0.00 |
August | 24222.04 | 20-AUG-13:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 0.00 |
September | 27519.00 | 10-SEP-12:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 0.00 |
October | 28990.92 | 09-OCT-13:11 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.92 |
November | 26772.34 | 05-NOV-12:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 |
December | 26687.54 | 17-DEC-12:51 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14528.22 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28990.92 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 | 394.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14468.20 | 22-JAN-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.78 |
February | 22726.03 | 26-FEB-16:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.54 |
March | 29972.03 | 12-MAR-15:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.30 |
April | 26546.51 | 08-APR-17:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 |
May | 27610.55 | 07-MAY-15:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.48 |
June | 33747.25 | 11-JUN-15:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 |
July | 33691.34 | 02-JUL-16:22 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
August | 30799.50 | 13-AUG-16:21 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 |
September | 32890.76 | 10-SEP-16:11 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
October | 31789.32 | 09-OCT-14:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 |
November | 27959.25 | 05-NOV-15:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 |
December | 25993.63 | 17-DEC-14:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14468.20 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33747.25 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 155.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2210.11 | 20-JAN-15:10 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 |
February | 2224.22 | 27-FEB-15:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.55 |
March | 5289.95 | 14-MAR-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.12 |
April | 5876.55 | 20-APR-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
May | 8593.08 | 17-MAY-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 0.00 |
June | 15773.10 | 25-JUN-17:32 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 223.33 | 0.00 |
July | 16007.80 | 16-JUL-14:53 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 330.58 | 0.00 |
August | 13070.41 | 20-AUG-15:31 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 0.00 |
September | 14625.38 | 10-SEP-15:01 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 129.48 | 0.00 |
October | 5675.14 | 11-OCT-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 0.00 |
November | 3863.95 | 09-NOV-13:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 |
December | 2138.07 | 04-DEC-14:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2138.07 | 0.00 | 351.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16007.80 | 3846.22 | 1582.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 330.58 | 154.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7457.71 | 20-JAN-09:40 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.90 |
February | 16038.11 | 26-FEB-10:41 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.47 |
March | 22523.63 | 26-MAR-09:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.42 |
April | 17129.87 | 09-APR-09:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.31 |
May | 18259.63 | 28-MAY-08:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.51 |
June | 27338.22 | 11-JUN-08:41 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.42 |
July | 27424.20 | 09-JUL-09:01 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 |
August | 28758.40 | 06-AUG-08:51 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.05 |
September | 26615.02 | 04-SEP-09:41 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 |
October | 18728.10 | 01-OCT-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.02 |
November | 9045.27 | 07-NOV-09:00 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 |
December | 4543.94 | 14-DEC-09:30 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4543.94 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | |
Maximum of Months | 28758.40 | 1239.33 | 509.78 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28074.96 | 01-JAN-13:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.61 |
February | 29626.16 | 26-FEB-12:41 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.25 |
March | 26499.30 | 26-MAR-12:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.75 |
April | 22754.93 | 09-APR-12:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 949.38 |
May | 13500.05 | 07-MAY-15:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.14 |
June | 23975.83 | 25-JUN-14:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 | 0.00 |
July | 24272.20 | 30-JUL-11:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.56 |
August | 25696.48 | 27-AUG-12:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.20 |
September | 27771.61 | 04-SEP-11:41 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.12 |
October | 26844.44 | 09-OCT-13:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.15 |
November | 27334.62 | 05-NOV-13:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 |
December | 29514.31 | 17-DEC-13:21 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13500.05 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29626.16 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 | 949.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10112.92 | 20-JAN-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
February | 25444.02 | 26-FEB-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.54 |
March | 26685.78 | 26-MAR-17:11 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 |
April | 24737.38 | 08-APR-17:03 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.26 |
May | 25880.20 | 07-MAY-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.75 |
June | 31405.65 | 25-JUN-16:11 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 | 0.00 |
July | 31077.32 | 02-JUL-17:01 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.13 |
August | 31009.17 | 13-AUG-17:31 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.28 |
September | 31019.63 | 10-SEP-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 0.00 |
October | 26631.06 | 09-OCT-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.14 |
November | 19931.05 | 05-NOV-15:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.61 |
December | 20091.06 | 17-DEC-15:21 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10112.92 | 0.00 | 169.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31405.65 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 | 265.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2165.34 | 20-JAN-16:00 | 1923.11 | 1097.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 |
February | 2077.30 | 27-FEB-15:10 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.50 |
March | 5389.96 | 14-MAR-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 |
April | 6319.58 | 20-APR-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 |
May | 9034.55 | 17-MAY-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 0.00 |
June | 18272.25 | 25-JUN-16:51 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 183.28 | 0.00 |
July | 18560.26 | 16-JUL-14:51 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 340.64 | 0.00 |
August | 17527.96 | 20-AUG-15:31 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 0.00 |
September | 14974.81 | 10-SEP-15:51 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 78.42 | 0.00 |
October | 5870.62 | 11-OCT-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 0.00 |
November | 3240.47 | 09-NOV-13:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
December | 1973.90 | 01-DEC-15:00 | 2010.79 | 840.51 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1973.90 | 809.73 | 351.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18560.26 | 3846.22 | 1582.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 340.64 | 187.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5745.86 | 20-JAN-09:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.74 |
February | 7215.19 | 27-FEB-09:20 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.96 |
March | 21317.93 | 12-MAR-09:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.80 |
April | 13951.08 | 21-APR-08:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 |
May | 15287.87 | 28-MAY-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.84 |
June | 24400.14 | 11-JUN-08:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.19 |
July | 27395.49 | 16-JUL-08:11 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 0.00 |
August | 28708.75 | 06-AUG-09:01 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 |
September | 24163.24 | 04-SEP-09:12 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.94 |
October | 23403.14 | 09-OCT-09:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 |
November | 7212.57 | 07-NOV-09:10 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.64 |
December | 2604.91 | 14-DEC-09:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2604.91 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28708.75 | 1239.33 | 509.78 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 380.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27231.92 | 15-JAN-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.51 |
February | 30901.59 | 26-FEB-12:41 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.58 |
March | 30385.91 | 12-MAR-13:01 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.48 |
April | 17299.18 | 21-APR-13:05 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.41 |
May | 13838.41 | 16-MAY-13:20 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 | 0.00 |
June | 27035.99 | 25-JUN-14:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | 0.00 |
July | 26784.92 | 16-JUL-14:51 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 345.40 | 0.00 |
August | 28264.41 | 20-AUG-13:31 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.26 |
September | 27936.09 | 04-SEP-12:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 0.00 |
October | 32004.25 | 09-OCT-13:11 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 |
November | 28986.67 | 05-NOV-13:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.13 |
December | 27829.44 | 03-DEC-13:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13838.41 | 607.31 | 263.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32004.25 | 4021.67 | 1582.13 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 345.40 | 878.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9949.25 | 20-JAN-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
February | 21796.38 | 26-FEB-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.47 |
March | 28697.03 | 12-MAR-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.87 |
April | 26111.74 | 08-APR-17:03 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.43 |
May | 21931.69 | 07-MAY-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.67 |
June | 34090.68 | 25-JUN-16:11 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 0.00 |
July | 30079.32 | 02-JUL-16:31 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 |
August | 33124.78 | 20-AUG-15:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 |
September | 29985.64 | 10-SEP-16:31 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 0.00 |
October | 29505.65 | 09-OCT-14:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 |
November | 16531.16 | 05-NOV-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 |
December | 7998.74 | 01-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7998.74 | 391.37 | 169.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34090.68 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 323.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7856.28 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.11 |
February | 4867.81 | 27-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.89 |
March | 6879.24 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
April | 5719.40 | 21-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 |
May | 6593.84 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.02 |
June | 12055.98 | 26-JUN-14:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 0.00 |
July | 15126.27 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 |
August | 13367.92 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 |
September | 13997.38 | 05-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.62 |
October | 9783.82 | 10-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.60 |
November | 5815.08 | 06-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 |
December | 6593.30 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4867.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15126.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.00 | 878.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10547.30 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.58 |
February | 11335.93 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.84 |
March | 8187.36 | 20-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.82 |
April | 9922.30 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 962.22 |
May | 5074.88 | 18-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 |
June | 9660.63 | 26-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.68 | 0.00 |
July | 9644.21 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.05 |
August | 7848.06 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 |
September | 7779.83 | 12-SEP-14:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 | 0.00 |
October | 10232.00 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871.25 |
November | 10937.22 | 29-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.51 |
December | 13962.56 | 20-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5074.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13962.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.68 | 1949.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5006.30 | 20-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.16 |
February | 5009.07 | 18-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.43 |
March | 12133.08 | 14-MAR-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 |
April | 12835.23 | 21-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.99 |
May | 16607.00 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 0.00 |
June | 26881.41 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.89 | 0.00 |
July | 20031.70 | 18-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.70 | 0.00 |
August | 21400.77 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 0.00 |
September | 20284.90 | 12-SEP-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
October | 11424.75 | 11-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 0.00 |
November | 7435.45 | 09-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 |
December | 2473.67 | 02-DEC-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2473.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26881.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.89 | 143.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2515.57 | 23-JAN-16:40 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4498.49 | 21-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7146.28 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8402.75 | 08-APR-18:00 | 11.69 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3479.09 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5458.59 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7263.99 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8673.62 | 05-AUG-18:40 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3366.82 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5039.32 | 09-OCT-16:45 | 70.15 | 105.55 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6533.36 | 05-NOV-16:13 | 81.84 | 123.14 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8244.40 | 03-DEC-15:55 | 70.15 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2515.57 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8673.62 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2335.83 | 23-JAN-16:40 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4226.16 | 23-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6683.09 | 31-MAR-23:30 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7963.23 | 08-APR-18:00 | 11.69 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3280.30 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5222.11 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6861.00 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8263.29 | 13-AUG-18:44 | 0.00 | 123.14 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3025.04 | 30-SEP-23:50 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4527.60 | 09-OCT-17:00 | 11.69 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6039.57 | 07-NOV-16:20 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7532.47 | 14-DEC-16:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2335.83 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8263.29 | 222.14 | 316.63 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2305.49 | 20-JAN-16:40 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4178.96 | 17-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6500.47 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8018.13 | 08-APR-18:00 | 11.69 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3219.97 | 31-MAY-23:50 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5218.70 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6770.73 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8423.12 | 13-AUG-18:41 | 0.00 | 123.14 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3138.17 | 10-SEP-17:31 | 0.00 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4521.42 | 09-OCT-16:48 | 70.15 | 105.55 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6051.94 | 07-NOV-16:20 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7460.57 | 14-DEC-16:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2305.49 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8423.12 | 222.14 | 316.63 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91828.25 | 02-JAN-15:00 | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183349.52 | 27-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358864.08 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367013.33 | 10-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175842.08 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268839.65 | 30-JUN-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359829.91 | 31-JUL-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369236.96 | 14-AUG-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176396.74 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266210.20 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276600.71 | 07-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368062.91 | 04-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91828.25 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369236.96 | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.170918E+13 | 1341069.44 | 20-JAN-15:30 | 0.301591E+12 | 1221500.78 | 05-JAN-07:10 |
February | 0.191574E+13 | 1387962.00 | 17-FEB-16:49 | 0.313739E+12 | 1199494.76 | 06-FEB-07:10 |
March | 0.253169E+13 | 1758870.49 | 14-MAR-15:09 | 0.196723E+12 | 689025.72 | 20-MAR-06:19 |
April | 0.271482E+13 | 1846710.56 | 07-APR-15:20 | 0.126070E+12 | 842791.05 | 03-APR-06:10 |
May | 0.182412E+13 | 1531439.33 | 16-MAY-15:09 | 0.111378E+11 | 309222.37 | 02-MAY-06:10 |
June | 0.238383E+13 | 1778254.16 | 05-JUN-15:09 | 2509637.21 | 2968.30 | 09-JUN-06:10 |
July | 0.283011E+13 | 1935787.77 | 18-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.328205E+13 | 2104512.47 | 02-AUG-15:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.189795E+13 | 1618655.22 | 12-SEP-15:00 | 0.788871E+10 | 368397.16 | 22-SEP-06:10 |
October | 0.215766E+13 | 1633693.35 | 11-OCT-15:09 | 0.149678E+12 | 945599.85 | 30-OCT-06:10 |
November | 0.240297E+13 | 1687295.60 | 07-NOV-15:00 | 0.237461E+12 | 981143.96 | 30-NOV-07:10 |
December | 0.277892E+13 | 1723916.82 | 01-DEC-15:09 | 0.460510E+12 | 1529692.54 | 23-DEC-07:10 |
Annual Sum or Average | 0.284291E+14 | 0.180480E+13 | ||||
Minimum of Months | 0.170918E+13 | 1341069.44 | 0.00 | 0.00 | ||
Maximum of Months | 0.328205E+13 | 2104512.47 | 0.460510E+12 | 1529692.54 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.208856E+12 | 0.403751E+11 | 0.766053E+12 | 0.213316E+12 | 0.204549E+12 | 0.226746E+11 | 0.00 | 0.289071E+11 | 0.288331E+10 | 0.180164E+12 | 0.00 | 0.414063E+11 | 0.00 |
February | 0.187607E+12 | 0.324286E+11 | 0.978954E+12 | 0.195308E+12 | 0.186908E+12 | 0.214093E+11 | 0.00 | 0.380583E+11 | 0.269940E+10 | 0.234295E+12 | 0.00 | 0.380771E+11 | 0.00 |
March | 0.220978E+12 | 0.302578E+11 | 0.141687E+13 | 0.226028E+12 | 0.224023E+12 | 0.241481E+11 | 0.00 | 0.703075E+11 | 0.103750E+11 | 0.264579E+12 | 0.00 | 0.441228E+11 | 0.00 |
April | 0.196070E+12 | 0.240974E+11 | 0.165903E+13 | 0.211475E+12 | 0.213471E+12 | 0.231326E+11 | 0.00 | 0.865188E+11 | 0.154635E+11 | 0.247059E+12 | 0.00 | 0.385059E+11 | 0.00 |
May | 0.210869E+12 | 0.213551E+11 | 0.774844E+12 | 0.219671E+12 | 0.253115E+12 | 0.318849E+11 | 0.00 | 0.755644E+11 | 0.333470E+11 | 0.164567E+12 | 0.00 | 0.389038E+11 | 0.00 |
June | 0.209575E+12 | 0.192545E+11 | 0.106252E+13 | 0.217906E+12 | 0.311881E+12 | 0.536881E+11 | 0.00 | 0.286397E+12 | 0.858698E+11 | 0.100420E+12 | 0.00 | 0.363239E+11 | 0.00 |
July | 0.196000E+12 | 0.203382E+11 | 0.139340E+13 | 0.213239E+12 | 0.308817E+12 | 0.578769E+11 | 0.00 | 0.386509E+12 | 0.106866E+12 | 0.114026E+12 | 0.00 | 0.330385E+11 | 0.00 |
August | 0.219357E+12 | 0.231234E+11 | 0.173200E+13 | 0.226028E+12 | 0.312800E+12 | 0.585666E+11 | 0.00 | 0.454331E+12 | 0.106871E+12 | 0.113381E+12 | 0.00 | 0.355962E+11 | 0.00 |
September | 0.196419E+12 | 0.268551E+11 | 0.740713E+12 | 0.211474E+12 | 0.266183E+12 | 0.423897E+11 | 0.00 | 0.153920E+12 | 0.637682E+11 | 0.163304E+12 | 0.00 | 0.329256E+11 | 0.00 |
October | 0.205905E+12 | 0.335603E+11 | 0.108340E+13 | 0.213315E+12 | 0.227264E+12 | 0.268075E+11 | 0.00 | 0.725362E+11 | 0.151678E+11 | 0.244114E+12 | 0.00 | 0.355859E+11 | 0.00 |
November | 0.206310E+12 | 0.375710E+11 | 0.135889E+13 | 0.205269E+12 | 0.206961E+12 | 0.233095E+11 | 0.00 | 0.641640E+11 | 0.783098E+10 | 0.255649E+12 | 0.00 | 0.370115E+11 | 0.00 |
December | 0.202693E+12 | 0.417968E+11 | 0.170972E+13 | 0.213241E+12 | 0.204762E+12 | 0.216475E+11 | 0.00 | 0.708131E+11 | 0.749497E+10 | 0.267840E+12 | 0.00 | 0.389120E+11 | 0.00 |
Annual Sum or Average | 0.246064E+13 | 0.351013E+12 | 0.146764E+14 | 0.256627E+13 | 0.292073E+13 | 0.407535E+12 | 0.00 | 0.178803E+13 | 0.458637E+12 | 0.234940E+13 | 0.00 | 0.450409E+12 | 0.00 |
Minimum of Months | 0.187607E+12 | 0.192545E+11 | 0.740713E+12 | 0.195308E+12 | 0.186908E+12 | 0.214093E+11 | 0.00 | 0.289071E+11 | 0.269940E+10 | 0.100420E+12 | 0.00 | 0.329256E+11 | 0.00 |
Maximum of Months | 0.220978E+12 | 0.417968E+11 | 0.173200E+13 | 0.226028E+12 | 0.312800E+12 | 0.585666E+11 | 0.00 | 0.454331E+12 | 0.106871E+12 | 0.267840E+12 | 0.00 | 0.441228E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.301591E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.313739E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.196723E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.126070E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.111378E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2509637.21 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.788871E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149678E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.237461E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.460510E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180480E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.460510E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-16:49 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233389.01 | 31-JAN-08:20 | 159047.00 | 20-JAN-16:49 | 21351.72 | 20-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 242626.37 | 06-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233389.23 | 08-FEB-08:20 | 167032.54 | 23-FEB-16:40 | 20777.70 | 06-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 228867.07 | 21-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233387.58 | 21-MAR-07:19 | 213574.88 | 10-MAR-16:19 | 38869.99 | 13-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 219197.08 | 03-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233382.47 | 03-APR-07:19 | 219211.77 | 07-APR-14:50 | 21246.85 | 19-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 212815.01 | 01-MAY-07:10 | 27558.46 | 01-MAY-18:49 | 423497.50 | 01-MAY-07:10 | 233379.09 | 01-MAY-07:19 | 246175.16 | 18-MAY-14:30 | 40993.91 | 31-MAY-14:30 | 0.00 | 01-MAY-00:10 |
June | 212845.67 | 16-JUN-07:10 | 27558.46 | 01-JUN-19:19 | 541788.89 | 01-JUN-07:10 | 233379.11 | 16-JUN-07:19 | 343887.06 | 05-JUN-14:00 | 46039.58 | 05-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 212815.01 | 03-JUL-07:10 | 27558.46 | 01-JUL-19:30 | 660080.29 | 03-JUL-07:10 | 233379.09 | 03-JUL-07:19 | 343887.06 | 12-JUL-13:50 | 46046.50 | 12-JUL-13:39 | 0.00 | 01-JUL-00:10 |
August | 214819.06 | 28-AUG-15:00 | 40855.88 | 10-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233379.33 | 21-AUG-07:19 | 330577.75 | 02-AUG-15:39 | 45977.27 | 10-AUG-10:00 | 0.00 | 01-AUG-00:10 |
September | 215016.35 | 21-SEP-15:00 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233379.79 | 22-SEP-07:19 | 343887.06 | 12-SEP-15:09 | 46043.31 | 12-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 236439.16 | 30-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233391.59 | 30-OCT-07:19 | 207163.27 | 20-OCT-15:50 | 40500.75 | 11-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 06-NOV-16:49 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233389.53 | 01-NOV-07:19 | 181974.95 | 08-NOV-15:00 | 39055.91 | 07-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-16:30 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233391.87 | 21-DEC-08:20 | 155331.93 | 04-DEC-15:39 | 20997.01 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 212815.01 | 27558.46 | 423497.50 | 233379.09 | 155331.93 | 20777.70 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233391.87 | 343887.06 | 46046.50 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 139590.39 | 20-JAN-14:00 | 44465.61 | 20-JAN-15:30 | 100000.00 | 01-JAN-09:50 | 0.00 | 55291.57 | 24-JAN-12:50 | 0.00 |
February | 87386.66 | 17-FEB-15:39 | 44017.49 | 18-FEB-14:30 | 100000.00 | 01-FEB-04:10 | 0.00 | 55492.22 | 14-FEB-12:50 | 0.00 |
March | 249112.11 | 14-MAR-13:00 | 45842.92 | 14-MAR-12:30 | 100000.00 | 01-MAR-06:10 | 0.00 | 55350.01 | 02-MAR-12:30 | 0.00 |
April | 240580.24 | 19-APR-13:30 | 44722.86 | 19-APR-13:30 | 100000.00 | 01-APR-16:10 | 0.00 | 53034.06 | 03-APR-11:00 | 0.00 |
May | 221925.12 | 16-MAY-12:09 | 49725.83 | 31-MAY-16:30 | 100000.00 | 01-MAY-21:10 | 0.00 | 51247.85 | 01-MAY-11:00 | 0.00 |
June | 373058.21 | 26-JUN-15:09 | 74036.60 | 15-JUN-12:30 | 100000.00 | 04-JUN-09:30 | 0.00 | 47547.73 | 01-JUN-11:20 | 0.00 |
July | 379439.67 | 12-JUL-13:39 | 74036.60 | 19-JUL-10:39 | 100000.00 | 01-JUL-04:19 | 0.00 | 45265.80 | 03-JUL-11:20 | 0.00 |
August | 436854.43 | 16-AUG-15:09 | 74036.60 | 03-AUG-10:30 | 100000.00 | 01-AUG-04:19 | 0.00 | 44035.88 | 31-AUG-11:39 | 0.00 |
September | 275376.83 | 12-SEP-14:50 | 58906.42 | 01-SEP-11:00 | 100000.00 | 02-SEP-17:49 | 0.00 | 45440.36 | 29-SEP-11:00 | 0.00 |
October | 260616.29 | 11-OCT-14:09 | 46473.48 | 10-OCT-10:39 | 100000.00 | 01-OCT-06:19 | 0.00 | 47823.52 | 31-OCT-11:00 | 0.00 |
November | 225272.40 | 07-NOV-13:00 | 44657.00 | 07-NOV-14:09 | 100000.00 | 01-NOV-03:09 | 0.00 | 51472.03 | 30-NOV-12:50 | 0.00 |
December | 204414.36 | 01-DEC-14:00 | 44230.49 | 01-DEC-14:00 | 100000.00 | 01-DEC-06:10 | 0.00 | 53161.72 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 87386.66 | 44017.49 | 100000.00 | 0.00 | 44035.88 | 0.00 | ||||
Maximum of Months | 436854.43 | 74036.60 | 100000.00 | 0.00 | 55492.22 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1341069.44 | 20-JAN-15:30 | 214038.21 | 423497.50 | 0.00 | 233116.22 | 135434.16 | 21351.72 | 0.00 | 137575.37 | 44465.61 |
February | 1387962.00 | 17-FEB-16:49 | 218831.91 | 541788.89 | 0.00 | 233267.27 | 160230.71 | 20517.39 | 0.00 | 68461.52 | 2746.09 |
March | 1758870.49 | 14-MAR-15:09 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 210603.07 | 37195.63 | 0.00 | 219752.80 | 44440.45 |
April | 1846710.56 | 07-APR-15:20 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 218268.59 | 20772.40 | 0.00 | 198247.04 | 44361.95 |
May | 1531439.33 | 16-MAY-15:09 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 232253.91 | 37521.60 | 0.00 | 210709.64 | 44562.27 |
June | 1778254.16 | 05-JUN-15:09 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 343887.06 | 46039.58 | 0.00 | 301673.31 | 44858.44 |
July | 1935787.77 | 18-JUL-10:09 | 212815.01 | 660080.29 | 0.00 | 233115.89 | 330577.75 | 44971.13 | 0.00 | 353161.14 | 44935.32 |
August | 2104512.47 | 02-AUG-15:39 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 330577.75 | 44973.99 | 0.00 | 400299.32 | 46039.28 |
September | 1618655.22 | 12-SEP-15:00 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 343887.06 | 46040.68 | 0.00 | 269185.57 | 44975.14 |
October | 1633693.35 | 11-OCT-15:09 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 179702.53 | 38426.76 | 0.00 | 248011.90 | 44952.55 |
November | 1687295.60 | 07-NOV-15:00 | 218910.42 | 660080.29 | 0.00 | 233116.92 | 144093.18 | 38090.74 | 0.00 | 221167.83 | 44031.73 |
December | 1723916.82 | 01-DEC-15:09 | 214114.58 | 778371.69 | 0.00 | 233116.41 | 116256.28 | 20845.22 | 0.00 | 187517.60 | 44189.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1341069.44 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 116256.28 | 20517.39 | 0.00 | 68461.52 | 2746.09 | |
Maximum of Months | 2104512.47 | 218910.42 | 778371.69 | 0.00 | 233267.27 | 343887.06 | 46040.68 | 0.00 | 400299.32 | 46039.28 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1221500.78 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1199494.76 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 689025.72 | 20-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 842791.05 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 309222.37 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2968.30 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 368397.16 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 945599.85 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 981143.96 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1529692.54 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1529692.54 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 27.24 | 38.33 | 27.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 56.83 | 26.29 | 23.83 | 26.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 26.13 | 28.33 | 26.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 26.29 | 25.50 | 26.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 84.83 | 26.73 | 46.67 | 26.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 413.17 | 27.94 | 295.50 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 637.50 | 28.54 | 418.17 | 28.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 382.83 | 27.68 | 260.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 261.17 | 27.70 | 152.17 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 119.33 | 27.24 | 49.67 | 27.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 26.90 | 34.33 | 26.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 | 26.50 | 26.67 | 26.46 |
Annual Sum or Average | 0.00 | 0.00 | 2300.33 | 27.73 | 1399.50 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 26.13 | 23.83 | 26.14 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 637.50 | 28.54 | 418.17 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.74 | 0.00 | 25.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.94 | 0.00 | 25.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.87 | 0.00 | 25.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.38 | 2.00 | 25.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 25.26 | 11.67 | 25.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.83 | 0.00 | 25.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.88 | 0.00 | 25.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.06 | 0.00 | 26.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Annual Sum or Average | 0.00 | 0.00 | 28.50 | 25.42 | 13.67 | 25.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.06 | 11.67 | 26.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.07 | 0.17 | 24.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.17 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 2.00 | 18.74 | 0.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
March | 0.83 | 19.28 | 0.17 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
April | 1.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.73 | 1.17 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.61 | 0.33 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 19.02 | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Annual Sum or Average | 7.50 | 18.89 | 1.00 | 19.05 | 1.50 | 19.90 | 1.50 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.28 | 0.50 | 19.46 | 1.17 | 24.73 | 1.17 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.49 | 7.00 | 26.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 26.11 | 27.33 | 26.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.14 | 5.83 | 26.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.34 | 2.83 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 0.50 | 19.27 | 0.00 | 19.27 | 51.50 | 26.18 | 43.00 | 26.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.27 | 0.00 | 19.27 | 32.50 | 27.34 | 27.33 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.61 | 1.00 | 27.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.78 | 1.00 | 27.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.45 | 1.83 | 28.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.24 | 1.17 | 28.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 2.33 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.20 | 13.50 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.42 | 22.33 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.14 | 12.67 | 27.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.97 | 8.50 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.10 | 4.33 | 28.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.77 | 1.33 | 27.77 |
December | 0.67 | 19.06 | 0.00 | 19.06 | 0.50 | 22.63 | 0.50 | 24.05 |
Annual Sum or Average | 0.67 | 19.06 | 0.00 | 19.06 | 78.67 | 27.42 | 70.50 | 27.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.63 | 0.50 | 24.05 |
Maximum of Months | 0.67 | 19.06 | 0.00 | 19.06 | 27.33 | 28.45 | 22.33 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.35 | 0.00 | 19.35 | 23.33 | 25.92 | 23.33 | 25.94 |
February | 0.33 | 19.20 | 0.00 | 19.20 | 18.67 | 25.60 | 18.67 | 25.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.13 | 12.33 | 26.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.85 | 0.83 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.39 | 2.17 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.89 | 10.50 | 26.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 26.72 | 20.50 | 26.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 26.01 | 23.33 | 25.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 26.59 | 21.00 | 26.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 26.16 | 29.00 | 26.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 25.94 | 32.50 | 25.94 |
December | 0.67 | 19.02 | 0.00 | 19.02 | 27.00 | 25.50 | 27.00 | 25.58 |
Annual Sum or Average | 1.17 | 19.12 | 0.00 | 19.12 | 228.83 | 26.11 | 221.17 | 26.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.50 | 0.83 | 25.58 |
Maximum of Months | 0.67 | 19.35 | 0.00 | 19.35 | 32.50 | 27.85 | 32.50 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.72 | 1.67 | 27.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.06 | 3.00 | 28.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.55 | 3.33 | 28.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.84 | 1.67 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.89 | 6.17 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.48 | 13.83 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.59 | 21.50 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.46 | 16.83 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.71 | 10.33 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.47 | 4.67 | 28.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.08 | 4.50 | 28.08 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.06 | 3.33 | 28.06 |
Annual Sum or Average | 0.00 | 0.00 | 166.67 | 27.66 | 90.83 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.46 | 1.67 | 27.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 28.55 | 21.50 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.93 | 0.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 4.33 | 18.63 | 0.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 1.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 1.50 | 19.27 | 0.33 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.81 | 2.50 | 26.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.70 | 6.50 | 26.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
November | 2.17 | 18.77 | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
December | 10.83 | 17.97 | 3.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 23.00 | 18.43 | 4.33 | 18.58 | 10.83 | 20.89 | 9.00 | 21.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.83 | 19.27 | 3.00 | 19.47 | 7.33 | 26.81 | 6.50 | 26.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 6.33 | 18.82 | 0.00 | 18.82 | 0.50 | 19.47 | 0.50 | 20.03 |
March | 1.17 | 19.28 | 0.00 | 19.28 | 2.00 | 24.89 | 2.00 | 26.15 |
April | 1.33 | 19.11 | 0.00 | 19.11 | 1.00 | 23.00 | 1.00 | 24.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.77 | 3.17 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.00 | 10.83 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 28.15 | 16.67 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.27 | 8.50 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.99 | 8.33 | 28.00 |
October | 5.33 | 19.46 | 0.00 | 19.46 | 3.50 | 22.86 | 3.50 | 24.33 |
November | 1.67 | 18.45 | 0.00 | 18.45 | 0.50 | 20.54 | 0.50 | 21.85 |
December | 14.33 | 18.22 | 0.33 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
Annual Sum or Average | 33.33 | 18.69 | 0.33 | 18.65 | 58.67 | 24.64 | 55.00 | 25.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 0.00 | 18.14 |
Maximum of Months | 14.33 | 19.46 | 0.33 | 19.46 | 18.67 | 28.27 | 16.67 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.65 | 0.00 | 18.65 | 47.83 | 25.68 | 47.83 | 25.73 |
February | 2.00 | 18.12 | 0.00 | 18.12 | 45.50 | 25.17 | 45.50 | 25.32 |
March | 0.33 | 18.68 | 0.00 | 18.68 | 24.50 | 25.52 | 24.33 | 25.56 |
April | 1.00 | 18.92 | 0.00 | 18.92 | 1.00 | 23.22 | 1.00 | 24.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.41 | 1.67 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.19 | 7.83 | 27.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.79 | 10.50 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.61 | 12.33 | 26.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 26.87 | 19.83 | 26.86 |
October | 0.67 | 18.75 | 0.00 | 18.75 | 49.50 | 25.74 | 49.00 | 25.78 |
November | 1.33 | 18.70 | 0.00 | 18.70 | 51.50 | 25.69 | 51.50 | 25.78 |
December | 3.33 | 17.83 | 0.17 | 17.69 | 34.83 | 24.96 | 34.83 | 25.30 |
Annual Sum or Average | 9.33 | 18.29 | 0.17 | 18.23 | 309.83 | 25.74 | 306.17 | 25.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 23.22 | 1.00 | 24.65 |
Maximum of Months | 3.33 | 18.92 | 0.17 | 18.92 | 51.50 | 27.79 | 51.50 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.95 | 0.00 | 18.95 | 0.33 | 20.83 | 0.33 | 22.04 |
February | 2.17 | 18.25 | 0.00 | 18.25 | 1.00 | 21.27 | 1.00 | 22.84 |
March | 0.33 | 18.84 | 0.00 | 18.84 | 2.50 | 27.29 | 1.83 | 27.70 |
April | 0.83 | 18.98 | 0.00 | 18.98 | 0.83 | 23.47 | 0.67 | 24.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.87 | 4.17 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.48 | 7.00 | 28.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.17 | 9.33 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.22 | 5.17 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.14 | 6.67 | 28.17 |
October | 0.67 | 18.80 | 0.00 | 18.80 | 3.67 | 27.04 | 3.00 | 27.73 |
November | 1.17 | 18.63 | 0.00 | 18.63 | 0.67 | 22.10 | 0.67 | 23.73 |
December | 3.33 | 17.75 | 0.17 | 17.61 | 0.67 | 19.20 | 0.67 | 20.34 |
Annual Sum or Average | 9.67 | 18.33 | 0.17 | 18.27 | 61.67 | 26.85 | 40.50 | 27.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 19.20 | 0.33 | 20.34 |
Maximum of Months | 3.33 | 18.98 | 0.17 | 18.98 | 15.33 | 28.48 | 9.33 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 17.06 | 6.83 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
February | 30.17 | 16.65 | 10.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
March | 16.50 | 16.44 | 4.33 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
April | 12.50 | 17.43 | 3.17 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
May | 0.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.97 | 6.83 | 26.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.12 | 8.33 | 27.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.43 | 2.00 | 27.43 |
September | 0.17 | 19.35 | 0.00 | 19.35 | 2.00 | 26.75 | 1.83 | 27.04 |
October | 8.67 | 17.45 | 1.83 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
November | 12.17 | 18.33 | 2.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
December | 50.00 | 16.72 | 18.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
Annual Sum or Average | 157.00 | 16.97 | 47.17 | 17.20 | 24.33 | 18.26 | 19.00 | 18.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 | 0.00 | 16.36 |
Maximum of Months | 50.00 | 19.35 | 18.33 | 19.35 | 10.67 | 27.43 | 8.33 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 16.31 | 1.00 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
February | 20.00 | 15.84 | 3.50 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
March | 13.50 | 15.89 | 3.00 | 15.65 | 1.33 | 16.56 | 1.33 | 17.35 |
April | 7.50 | 16.01 | 0.17 | 15.99 | 0.83 | 17.15 | 0.83 | 18.09 |
May | 0.33 | 18.95 | 0.00 | 18.95 | 2.67 | 26.65 | 2.67 | 27.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.04 | 10.83 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 28.19 | 16.83 | 28.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.26 | 8.83 | 28.30 |
September | 0.17 | 19.37 | 0.00 | 19.37 | 9.33 | 27.78 | 8.50 | 27.87 |
October | 5.17 | 16.22 | 0.00 | 16.22 | 2.33 | 19.83 | 2.33 | 21.72 |
November | 6.67 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
December | 26.33 | 15.53 | 2.00 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
Annual Sum or Average | 93.00 | 15.98 | 9.67 | 15.85 | 59.33 | 20.33 | 52.17 | 22.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 | 0.00 | 15.45 |
Maximum of Months | 26.33 | 19.37 | 3.50 | 19.37 | 19.83 | 28.26 | 16.83 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 17.79 | 0.00 | 17.79 | 18.67 | 23.89 | 18.67 | 24.71 |
February | 16.17 | 16.28 | 3.83 | 16.07 | 12.67 | 19.79 | 12.67 | 21.43 |
March | 12.33 | 16.04 | 2.67 | 15.83 | 11.67 | 20.28 | 11.50 | 21.99 |
April | 7.33 | 16.16 | 0.00 | 16.16 | 0.17 | 16.41 | 0.17 | 16.65 |
May | 0.33 | 18.99 | 0.00 | 18.99 | 1.33 | 25.74 | 1.33 | 26.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.15 | 9.17 | 27.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.79 | 11.00 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.33 | 9.50 | 27.32 |
September | 0.17 | 19.42 | 0.00 | 19.42 | 19.00 | 27.06 | 17.33 | 27.07 |
October | 4.33 | 16.32 | 0.00 | 16.32 | 27.50 | 24.82 | 27.00 | 25.42 |
November | 5.00 | 17.85 | 0.00 | 17.85 | 23.00 | 24.56 | 23.00 | 25.21 |
December | 18.17 | 16.21 | 1.33 | 16.14 | 10.67 | 19.65 | 10.67 | 21.32 |
Annual Sum or Average | 69.67 | 16.47 | 7.83 | 16.33 | 159.17 | 23.13 | 152.00 | 24.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 16.41 | 0.17 | 16.65 |
Maximum of Months | 18.17 | 19.42 | 3.83 | 19.42 | 27.50 | 27.79 | 27.00 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 17.44 | 0.67 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 13.17 | 16.39 | 2.67 | 16.15 | 0.33 | 16.39 | 0.33 | 16.62 |
March | 6.83 | 16.52 | 1.83 | 16.11 | 2.00 | 18.44 | 1.50 | 19.70 |
April | 2.67 | 17.26 | 0.00 | 17.26 | 0.50 | 18.98 | 0.33 | 19.88 |
May | 0.17 | 18.98 | 0.00 | 18.98 | 5.33 | 27.62 | 4.33 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.11 | 9.00 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.26 | 9.83 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.20 | 5.83 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.18 | 7.00 | 28.18 |
October | 2.50 | 16.98 | 0.00 | 16.98 | 3.33 | 23.58 | 2.83 | 25.23 |
November | 5.00 | 17.92 | 0.00 | 17.92 | 0.67 | 19.10 | 0.67 | 20.03 |
December | 15.17 | 15.91 | 1.83 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
Annual Sum or Average | 51.67 | 16.62 | 7.00 | 16.40 | 64.00 | 22.55 | 41.67 | 23.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 0.00 | 15.77 |
Maximum of Months | 15.17 | 18.98 | 2.67 | 18.98 | 16.67 | 28.26 | 9.83 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 28.03 | 21.83 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.83 | 28.03 | 21.83 | 28.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 28.03 | 21.83 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.01 | 20.33 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.33 | 28.01 | 20.33 | 28.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.01 | 20.33 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.98 | 16.50 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.33 | 27.98 | 16.50 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.98 | 16.50 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.99 | 3.50 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 27.99 | 3.50 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.99 | 3.50 | 27.99 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.00 | 24.51 | 109.83 | 25.37 | 13.67 | 25.55 |
February | 193.50 | 24.00 | 75.50 | 24.65 | 0.00 | 24.65 |
March | 190.67 | 24.00 | 95.67 | 24.65 | 0.00 | 24.65 |
April | 63.33 | 24.00 | 127.83 | 25.37 | 0.00 | 25.37 |
May | 70.67 | 24.69 | 212.83 | 25.40 | 15.00 | 25.50 |
June | 257.33 | 28.22 | 463.83 | 27.33 | 257.33 | 27.56 |
July | 362.50 | 28.88 | 487.83 | 28.33 | 362.50 | 28.49 |
August | 191.00 | 27.90 | 450.50 | 26.76 | 191.00 | 27.02 |
September | 109.33 | 27.61 | 280.50 | 26.88 | 92.17 | 27.15 |
October | 77.83 | 24.82 | 152.67 | 25.87 | 16.50 | 26.00 |
November | 43.50 | 24.09 | 133.83 | 25.88 | 1.00 | 25.90 |
December | 169.00 | 24.00 | 103.50 | 24.94 | 0.00 | 24.94 |
Annual Sum or Average | 1859.67 | 26.25 | 2694.33 | 26.49 | 949.17 | 26.82 |
Minimum of Months | 43.50 | 24.00 | 75.50 | 24.65 | 0.00 | 24.65 |
Maximum of Months | 362.50 | 28.88 | 487.83 | 28.33 | 362.50 | 28.49 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 185.17 | 24.01 | 38.83 | 24.32 | 0.00 | 24.32 |
February | 224.00 | 24.00 | 32.83 | 24.22 | 0.00 | 24.22 |
March | 180.33 | 24.01 | 34.83 | 24.23 | 0.00 | 24.23 |
April | 67.17 | 24.00 | 95.67 | 24.97 | 0.00 | 24.97 |
May | 54.50 | 24.00 | 157.33 | 24.62 | 0.00 | 24.62 |
June | 39.83 | 24.45 | 362.33 | 24.43 | 39.83 | 24.43 |
July | 71.33 | 24.64 | 419.50 | 24.60 | 71.33 | 24.61 |
August | 24.50 | 24.27 | 389.33 | 24.40 | 24.50 | 24.39 |
September | 34.33 | 24.00 | 186.83 | 24.74 | 0.00 | 24.74 |
October | 107.00 | 24.01 | 103.67 | 24.75 | 0.00 | 24.75 |
November | 84.00 | 24.00 | 83.50 | 24.80 | 0.00 | 24.80 |
December | 227.17 | 24.05 | 32.33 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 1299.33 | 24.07 | 1937.00 | 24.50 | 135.67 | 24.50 |
Minimum of Months | 24.50 | 24.00 | 32.33 | 24.22 | 0.00 | 24.22 |
Maximum of Months | 227.17 | 24.64 | 419.50 | 24.97 | 71.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.67 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
February | 383.67 | 23.40 | 2.00 | 23.39 | 2.00 | 23.38 |
March | 461.00 | 23.70 | 6.17 | 23.70 | 0.00 | 23.70 |
April | 320.17 | 23.80 | 20.33 | 23.86 | 0.00 | 23.86 |
May | 156.00 | 23.97 | 91.33 | 24.26 | 0.00 | 24.26 |
June | 55.67 | 24.18 | 252.33 | 24.31 | 40.67 | 24.30 |
July | 106.67 | 24.22 | 297.17 | 24.31 | 90.50 | 24.30 |
August | 43.33 | 24.07 | 293.50 | 24.33 | 33.00 | 24.31 |
September | 98.00 | 23.96 | 110.67 | 24.38 | 0.00 | 24.38 |
October | 284.00 | 23.84 | 14.67 | 23.90 | 0.00 | 23.90 |
November | 371.17 | 23.71 | 2.17 | 23.72 | 0.00 | 23.72 |
December | 490.50 | 23.28 | 26.83 | 23.15 | 26.83 | 23.03 |
Annual Sum or Average | 3182.83 | 23.65 | 1117.17 | 23.83 | 193.00 | 23.83 |
Minimum of Months | 43.33 | 23.28 | 0.00 | 23.15 | 0.00 | 23.03 |
Maximum of Months | 490.50 | 24.22 | 297.17 | 24.38 | 90.50 | 24.38 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 21.89 | 126.83 | 21.49 | 126.83 | 21.22 |
February | 442.50 | 22.08 | 105.50 | 21.72 | 105.50 | 21.47 |
March | 495.33 | 22.70 | 52.00 | 22.41 | 52.00 | 22.17 |
April | 395.50 | 22.62 | 66.33 | 22.30 | 61.33 | 22.04 |
May | 226.00 | 23.63 | 52.33 | 23.76 | 0.00 | 23.76 |
June | 57.33 | 24.18 | 277.00 | 24.34 | 38.83 | 24.33 |
July | 98.00 | 24.25 | 323.00 | 24.36 | 89.00 | 24.35 |
August | 51.83 | 24.03 | 298.00 | 24.30 | 34.00 | 24.28 |
September | 148.33 | 23.69 | 99.50 | 24.10 | 0.00 | 24.10 |
October | 440.50 | 23.00 | 40.50 | 22.82 | 40.50 | 22.66 |
November | 462.00 | 22.36 | 57.33 | 22.19 | 57.33 | 22.06 |
December | 497.00 | 21.67 | 184.00 | 21.25 | 184.00 | 21.02 |
Annual Sum or Average | 3808.17 | 22.55 | 1682.33 | 22.63 | 789.33 | 22.43 |
Minimum of Months | 51.83 | 21.67 | 40.50 | 21.25 | 0.00 | 21.02 |
Maximum of Months | 497.00 | 24.25 | 323.00 | 24.36 | 184.00 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.00 | 22.46 | 63.67 | 22.28 | 63.67 | 22.13 |
February | 450.00 | 22.38 | 67.67 | 22.16 | 67.67 | 21.99 |
March | 480.50 | 23.11 | 13.00 | 23.03 | 13.00 | 22.96 |
April | 349.17 | 23.35 | 6.50 | 23.36 | 0.00 | 23.36 |
May | 148.83 | 23.79 | 126.33 | 24.20 | 0.00 | 24.20 |
June | 43.50 | 25.13 | 412.67 | 24.54 | 43.50 | 24.59 |
July | 91.17 | 25.31 | 452.83 | 24.76 | 91.17 | 24.84 |
August | 35.50 | 25.20 | 402.33 | 24.48 | 34.33 | 24.53 |
September | 114.83 | 23.86 | 155.83 | 24.41 | 3.17 | 24.45 |
October | 406.50 | 23.23 | 33.67 | 23.26 | 13.83 | 23.19 |
November | 467.83 | 22.97 | 17.17 | 22.90 | 17.17 | 22.83 |
December | 497.00 | 22.48 | 97.00 | 22.19 | 97.00 | 21.98 |
Annual Sum or Average | 3585.83 | 23.01 | 1848.67 | 23.35 | 444.50 | 23.29 |
Minimum of Months | 35.50 | 22.38 | 6.50 | 22.16 | 0.00 | 21.98 |
Maximum of Months | 501.00 | 25.31 | 452.83 | 24.76 | 97.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 419.00 | 22.71 | 55.50 | 22.67 | 36.33 | 22.54 |
February | 336.00 | 22.35 | 97.83 | 22.30 | 64.33 | 22.10 |
March | 362.83 | 22.95 | 85.33 | 23.11 | 24.33 | 23.04 |
April | 273.17 | 23.07 | 78.83 | 23.31 | 9.17 | 23.31 |
May | 103.83 | 24.01 | 218.50 | 24.45 | 7.00 | 24.50 |
June | 66.33 | 25.94 | 447.17 | 24.69 | 66.33 | 24.83 |
July | 120.67 | 25.85 | 468.33 | 24.91 | 120.67 | 25.07 |
August | 57.50 | 25.72 | 436.50 | 24.58 | 54.17 | 24.71 |
September | 85.67 | 24.63 | 259.50 | 24.71 | 24.00 | 24.86 |
October | 313.33 | 23.13 | 99.17 | 23.47 | 29.00 | 23.46 |
November | 366.50 | 22.85 | 53.50 | 22.94 | 21.50 | 22.87 |
December | 445.67 | 22.45 | 94.33 | 22.21 | 88.33 | 21.99 |
Annual Sum or Average | 2950.50 | 23.12 | 2394.50 | 23.61 | 545.17 | 23.61 |
Minimum of Months | 57.50 | 22.35 | 53.50 | 22.21 | 7.00 | 21.99 |
Maximum of Months | 445.67 | 25.94 | 468.33 | 24.91 | 120.67 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.83 | 23.00 | 190.17 | 23.45 | 52.67 | 23.45 |
February | 259.83 | 22.51 | 199.83 | 22.89 | 76.00 | 22.70 |
March | 307.33 | 22.82 | 139.50 | 23.16 | 33.17 | 23.09 |
April | 275.67 | 22.84 | 93.50 | 23.02 | 20.17 | 22.92 |
May | 147.00 | 23.60 | 161.50 | 24.15 | 0.83 | 24.16 |
June | 55.67 | 25.47 | 397.50 | 24.61 | 51.50 | 24.71 |
July | 100.50 | 25.51 | 441.00 | 24.79 | 100.50 | 24.90 |
August | 54.50 | 25.78 | 438.50 | 24.63 | 52.00 | 24.74 |
September | 98.33 | 24.90 | 295.33 | 24.79 | 38.17 | 24.99 |
October | 266.83 | 23.30 | 196.00 | 23.78 | 56.17 | 23.85 |
November | 262.00 | 23.31 | 197.83 | 23.85 | 51.50 | 23.92 |
December | 319.00 | 22.76 | 179.50 | 23.02 | 78.33 | 22.88 |
Annual Sum or Average | 2445.50 | 23.28 | 2930.17 | 23.85 | 611.00 | 23.87 |
Minimum of Months | 54.50 | 22.51 | 93.50 | 22.89 | 0.83 | 22.70 |
Maximum of Months | 319.00 | 25.78 | 441.00 | 24.79 | 100.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.00 | 23.21 | 77.67 | 23.36 | 17.67 | 23.30 |
February | 273.83 | 23.30 | 81.83 | 23.58 | 13.00 | 23.59 |
March | 189.83 | 23.89 | 115.83 | 24.28 | 11.83 | 24.38 |
April | 69.50 | 24.18 | 201.50 | 24.61 | 5.33 | 24.66 |
May | 62.33 | 24.91 | 275.67 | 24.80 | 19.50 | 24.92 |
June | 78.50 | 25.89 | 462.17 | 24.80 | 78.50 | 24.94 |
July | 124.50 | 25.90 | 487.67 | 24.97 | 124.50 | 25.13 |
August | 89.67 | 26.11 | 497.50 | 24.83 | 89.67 | 25.00 |
September | 69.00 | 25.41 | 298.00 | 24.95 | 34.00 | 25.13 |
October | 174.67 | 23.86 | 134.50 | 24.39 | 16.50 | 24.54 |
November | 176.17 | 23.90 | 125.83 | 24.41 | 10.33 | 24.50 |
December | 277.67 | 23.58 | 82.67 | 23.82 | 16.33 | 23.79 |
Annual Sum or Average | 1940.67 | 24.05 | 2840.83 | 24.45 | 437.17 | 24.57 |
Minimum of Months | 62.33 | 23.21 | 77.67 | 23.36 | 5.33 | 23.30 |
Maximum of Months | 355.00 | 26.11 | 497.50 | 24.97 | 124.50 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.04 | 232.00 | 20.77 | 232.00 | 20.63 |
February | 454.00 | 21.00 | 242.67 | 20.76 | 242.67 | 20.64 |
March | 511.50 | 21.87 | 132.17 | 21.51 | 132.17 | 21.28 |
April | 449.50 | 22.16 | 85.67 | 21.86 | 82.17 | 21.63 |
May | 245.83 | 23.38 | 83.83 | 23.66 | 1.50 | 23.65 |
June | 46.00 | 24.56 | 349.67 | 24.44 | 39.67 | 24.46 |
July | 93.00 | 24.51 | 382.50 | 24.51 | 90.17 | 24.51 |
August | 60.33 | 23.94 | 303.33 | 24.30 | 27.00 | 24.29 |
September | 195.67 | 23.42 | 103.50 | 23.86 | 1.00 | 23.85 |
October | 484.83 | 22.32 | 77.17 | 22.07 | 77.17 | 21.88 |
November | 487.00 | 21.45 | 182.67 | 21.23 | 182.67 | 21.11 |
December | 497.00 | 20.68 | 330.00 | 20.47 | 330.00 | 20.39 |
Annual Sum or Average | 4026.67 | 21.85 | 2505.17 | 22.03 | 1438.17 | 21.80 |
Minimum of Months | 46.00 | 20.68 | 77.17 | 20.47 | 1.00 | 20.39 |
Maximum of Months | 511.50 | 24.56 | 382.50 | 24.51 | 330.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 402.17 | 21.80 | 132.83 | 21.50 | 130.67 | 21.30 |
February | 330.33 | 21.61 | 155.00 | 21.31 | 138.83 | 21.05 |
March | 335.33 | 22.13 | 119.83 | 22.02 | 81.33 | 21.76 |
April | 286.83 | 22.19 | 108.17 | 22.15 | 62.50 | 21.91 |
May | 129.00 | 23.64 | 166.33 | 24.28 | 6.83 | 24.34 |
June | 63.00 | 26.07 | 349.50 | 24.82 | 62.67 | 24.98 |
July | 116.50 | 25.71 | 373.83 | 24.98 | 116.33 | 25.12 |
August | 64.67 | 25.50 | 342.50 | 24.71 | 53.50 | 24.84 |
September | 110.33 | 24.27 | 189.50 | 24.66 | 23.50 | 24.83 |
October | 307.17 | 22.47 | 125.00 | 22.62 | 72.83 | 22.43 |
November | 367.17 | 22.02 | 110.33 | 21.85 | 95.50 | 21.65 |
December | 408.50 | 21.30 | 222.00 | 20.92 | 221.33 | 20.74 |
Annual Sum or Average | 2921.00 | 22.39 | 2394.83 | 22.79 | 1065.83 | 22.62 |
Minimum of Months | 63.00 | 21.30 | 108.17 | 20.92 | 6.83 | 20.74 |
Maximum of Months | 408.50 | 26.07 | 373.83 | 24.98 | 221.33 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.50 | 22.81 | 220.00 | 23.23 | 100.17 | 23.20 |
February | 281.17 | 22.21 | 236.00 | 22.56 | 121.50 | 22.35 |
March | 328.50 | 22.25 | 187.17 | 22.49 | 84.83 | 22.28 |
April | 325.83 | 22.11 | 128.83 | 22.12 | 65.67 | 21.87 |
May | 193.50 | 23.31 | 140.00 | 23.85 | 3.17 | 23.84 |
June | 74.50 | 24.88 | 350.67 | 24.52 | 53.67 | 24.61 |
July | 112.83 | 24.94 | 391.17 | 24.64 | 100.83 | 24.71 |
August | 70.17 | 25.20 | 394.50 | 24.58 | 50.83 | 24.70 |
September | 122.83 | 24.53 | 275.83 | 24.68 | 37.50 | 24.89 |
October | 299.67 | 22.98 | 235.00 | 23.39 | 102.00 | 23.35 |
November | 300.00 | 22.97 | 218.33 | 23.51 | 90.50 | 23.54 |
December | 348.33 | 22.17 | 231.67 | 22.34 | 151.50 | 22.16 |
Annual Sum or Average | 2778.83 | 22.87 | 3009.17 | 23.43 | 962.17 | 23.36 |
Minimum of Months | 70.17 | 22.11 | 128.83 | 22.12 | 3.17 | 21.87 |
Maximum of Months | 348.33 | 25.20 | 394.50 | 24.68 | 151.50 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 430.00 | 21.78 | 152.50 | 21.59 | 128.50 | 21.38 |
February | 376.17 | 21.65 | 173.00 | 21.48 | 142.00 | 21.24 |
March | 408.00 | 22.31 | 126.50 | 22.23 | 76.83 | 21.99 |
April | 333.67 | 22.37 | 108.17 | 22.30 | 58.67 | 22.07 |
May | 167.17 | 23.72 | 188.50 | 24.21 | 13.83 | 24.32 |
June | 64.50 | 25.45 | 408.00 | 24.66 | 58.00 | 24.77 |
July | 109.50 | 25.22 | 431.17 | 24.73 | 109.50 | 24.82 |
August | 54.33 | 25.33 | 421.00 | 24.60 | 46.00 | 24.69 |
September | 131.00 | 24.19 | 218.17 | 24.55 | 26.33 | 24.72 |
October | 367.33 | 22.67 | 138.33 | 22.75 | 72.83 | 22.60 |
November | 400.00 | 22.10 | 121.33 | 22.07 | 85.00 | 21.90 |
December | 456.17 | 21.40 | 224.00 | 21.09 | 217.83 | 20.90 |
Annual Sum or Average | 3297.83 | 22.41 | 2710.67 | 22.86 | 1035.33 | 22.70 |
Minimum of Months | 54.33 | 21.40 | 108.17 | 21.09 | 13.83 | 20.90 |
Maximum of Months | 456.17 | 25.45 | 431.17 | 24.73 | 217.83 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 358.83 | 20.12 | 358.83 | 20.03 |
February | 454.00 | 20.49 | 336.00 | 20.32 | 336.00 | 20.26 |
March | 514.00 | 21.39 | 232.17 | 20.99 | 232.17 | 20.78 |
April | 450.83 | 21.42 | 176.67 | 20.92 | 173.33 | 20.63 |
May | 280.17 | 22.93 | 91.67 | 23.16 | 14.67 | 23.07 |
June | 63.50 | 24.60 | 349.17 | 24.44 | 41.50 | 24.50 |
July | 108.83 | 24.60 | 381.00 | 24.53 | 96.00 | 24.56 |
August | 89.67 | 23.89 | 308.00 | 24.24 | 34.00 | 24.27 |
September | 218.17 | 23.10 | 109.50 | 23.50 | 13.67 | 23.43 |
October | 494.83 | 21.69 | 167.83 | 21.31 | 167.83 | 21.09 |
November | 489.00 | 20.79 | 306.00 | 20.53 | 306.00 | 20.41 |
December | 497.00 | 20.15 | 425.17 | 20.04 | 425.17 | 20.00 |
Annual Sum or Average | 4162.00 | 21.36 | 3242.00 | 21.49 | 2199.17 | 21.24 |
Minimum of Months | 63.50 | 20.15 | 91.67 | 20.04 | 13.67 | 20.00 |
Maximum of Months | 514.00 | 24.60 | 425.17 | 24.53 | 425.17 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.33 | 21.14 | 248.50 | 20.73 | 248.50 | 20.53 |
February | 417.67 | 21.37 | 208.50 | 20.92 | 205.33 | 20.68 |
March | 397.17 | 21.75 | 186.17 | 21.48 | 155.50 | 21.19 |
April | 340.33 | 21.52 | 181.83 | 21.25 | 133.17 | 20.89 |
May | 160.83 | 23.19 | 196.83 | 23.87 | 11.33 | 23.85 |
June | 67.50 | 25.96 | 426.17 | 24.68 | 64.33 | 24.84 |
July | 132.33 | 25.54 | 447.17 | 24.83 | 129.50 | 24.97 |
August | 74.17 | 25.25 | 418.33 | 24.56 | 55.33 | 24.69 |
September | 136.50 | 23.99 | 238.00 | 24.37 | 31.83 | 24.50 |
October | 371.50 | 22.01 | 169.00 | 21.93 | 125.33 | 21.66 |
November | 458.67 | 21.50 | 195.83 | 21.14 | 194.17 | 20.94 |
December | 497.00 | 20.83 | 313.17 | 20.46 | 313.17 | 20.30 |
Annual Sum or Average | 3546.00 | 21.91 | 3229.50 | 22.24 | 1667.50 | 21.99 |
Minimum of Months | 67.50 | 20.83 | 169.00 | 20.46 | 11.33 | 20.30 |
Maximum of Months | 497.00 | 25.96 | 447.17 | 24.83 | 313.17 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 337.00 | 21.78 | 265.33 | 21.98 | 162.67 | 21.73 |
February | 295.67 | 21.52 | 253.00 | 21.77 | 149.83 | 21.47 |
March | 353.00 | 21.80 | 234.67 | 21.85 | 148.50 | 21.59 |
April | 344.67 | 21.30 | 188.67 | 21.12 | 131.50 | 20.76 |
May | 224.83 | 22.85 | 145.33 | 23.39 | 14.00 | 23.31 |
June | 91.17 | 24.63 | 346.00 | 24.48 | 50.83 | 24.59 |
July | 133.00 | 24.82 | 390.83 | 24.61 | 106.00 | 24.70 |
August | 89.83 | 24.74 | 383.17 | 24.50 | 51.00 | 24.62 |
September | 155.00 | 24.10 | 265.33 | 24.43 | 44.50 | 24.60 |
October | 323.50 | 22.32 | 261.67 | 22.62 | 139.50 | 22.45 |
November | 316.33 | 22.15 | 260.50 | 22.45 | 144.83 | 22.25 |
December | 379.33 | 21.50 | 283.17 | 21.48 | 211.83 | 21.22 |
Annual Sum or Average | 3043.33 | 22.27 | 3277.67 | 22.75 | 1355.00 | 22.54 |
Minimum of Months | 89.83 | 21.30 | 145.33 | 21.12 | 14.00 | 20.76 |
Maximum of Months | 379.33 | 24.82 | 390.83 | 24.61 | 211.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.33 | 21.08 | 256.83 | 20.79 | 243.50 | 20.60 |
February | 393.33 | 21.17 | 240.00 | 20.96 | 215.67 | 20.77 |
March | 422.17 | 21.82 | 195.33 | 21.62 | 151.67 | 21.36 |
April | 352.17 | 21.58 | 165.17 | 21.37 | 116.17 | 21.04 |
May | 205.83 | 23.30 | 181.17 | 23.83 | 23.33 | 23.89 |
June | 75.33 | 25.25 | 403.83 | 24.64 | 61.17 | 24.75 |
July | 123.33 | 25.14 | 425.67 | 24.72 | 114.17 | 24.81 |
August | 74.50 | 24.97 | 407.00 | 24.56 | 52.67 | 24.66 |
September | 159.83 | 23.80 | 215.17 | 24.27 | 32.83 | 24.40 |
October | 394.17 | 22.08 | 191.00 | 22.04 | 133.00 | 21.83 |
November | 422.67 | 21.51 | 215.50 | 21.30 | 190.67 | 21.10 |
December | 468.17 | 20.86 | 310.00 | 20.56 | 306.33 | 20.41 |
Annual Sum or Average | 3544.83 | 21.92 | 3206.67 | 22.29 | 1641.17 | 22.05 |
Minimum of Months | 74.50 | 20.86 | 165.17 | 20.56 | 23.33 | 20.41 |
Maximum of Months | 468.17 | 25.25 | 425.67 | 24.72 | 306.33 | 24.81 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 27.00 | 502.00 | 27.00 | 2.50 | 27.00 |
February | 10.33 | 27.00 | 454.00 | 27.00 | 10.33 | 27.00 |
March | 18.50 | 27.00 | 514.00 | 27.00 | 18.50 | 27.00 |
April | 23.83 | 27.00 | 485.00 | 27.00 | 23.83 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 45.50 | 27.00 | 496.00 | 27.00 | 45.50 | 27.00 |
July | 138.83 | 27.00 | 497.00 | 27.00 | 138.83 | 27.00 |
August | 199.50 | 27.14 | 514.00 | 27.08 | 199.50 | 27.09 |
September | 8.67 | 27.00 | 485.00 | 27.00 | 8.67 | 27.00 |
October | 17.33 | 27.00 | 502.00 | 27.00 | 17.33 | 27.00 |
November | 25.17 | 27.00 | 489.00 | 27.00 | 25.17 | 27.00 |
December | 15.33 | 27.00 | 497.00 | 27.00 | 15.33 | 27.00 |
Annual Sum or Average | 505.50 | 27.06 | 5943.00 | 27.01 | 505.50 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 199.50 | 27.14 | 514.00 | 27.08 | 199.50 | 27.09 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 449.50 | 27.00 | 0.00 | 27.00 |
February | 1.83 | 27.00 | 407.33 | 27.00 | 1.83 | 27.00 |
March | 2.33 | 27.00 | 499.50 | 27.00 | 2.33 | 27.00 |
April | 5.33 | 27.00 | 481.00 | 27.00 | 5.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 7.67 | 27.00 | 496.00 | 27.00 | 7.67 | 27.00 |
July | 1.83 | 27.00 | 497.00 | 27.00 | 1.83 | 27.00 |
August | 43.00 | 27.50 | 514.00 | 27.08 | 43.00 | 27.11 |
September | 4.00 | 27.00 | 485.00 | 27.00 | 4.00 | 27.00 |
October | 5.00 | 27.00 | 498.17 | 27.00 | 5.00 | 27.00 |
November | 0.83 | 27.00 | 485.00 | 27.00 | 0.83 | 27.00 |
December | 6.33 | 27.00 | 420.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 78.17 | 27.28 | 5740.50 | 27.01 | 71.83 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 407.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 43.00 | 27.50 | 514.00 | 27.08 | 43.00 | 27.11 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.00 | 25.05 | 329.17 | 26.58 | 2.17 | 26.56 |
February | 25.33 | 27.00 | 298.83 | 27.00 | 1.00 | 27.00 |
March | 21.83 | 27.00 | 447.17 | 27.00 | 2.83 | 27.00 |
April | 10.83 | 27.00 | 426.50 | 27.00 | 6.00 | 27.00 |
May | 0.83 | 26.71 | 501.83 | 27.00 | 0.50 | 27.00 |
June | 26.33 | 27.00 | 496.00 | 27.00 | 26.33 | 27.00 |
July | 26.67 | 27.00 | 497.00 | 27.00 | 26.67 | 27.00 |
August | 60.17 | 27.32 | 514.00 | 27.07 | 60.17 | 27.09 |
September | 6.17 | 27.00 | 485.00 | 27.00 | 6.17 | 27.00 |
October | 5.00 | 27.00 | 435.83 | 27.00 | 4.50 | 27.00 |
November | 1.17 | 27.00 | 415.83 | 27.00 | 0.83 | 27.00 |
December | 37.17 | 27.00 | 286.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 307.50 | 26.52 | 5133.67 | 26.97 | 137.17 | 26.98 |
Minimum of Months | 0.83 | 25.05 | 286.50 | 26.58 | 0.00 | 26.56 |
Maximum of Months | 86.00 | 27.32 | 514.00 | 27.07 | 60.17 | 27.09 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.33 | 27.00 | 502.00 | 27.00 | 469.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 467.83 | 27.00 | 508.00 | 27.00 | 467.83 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
September | 482.83 | 27.00 | 485.00 | 27.00 | 482.83 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5868.00 | 27.00 | 5943.00 | 27.00 | 5868.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00006 | 18.41265 | 0.74732 | 16.90435 |
February | 454.00000 | 27.00002 | 17.20385 | 0.77044 | 17.65646 |
March | 514.00000 | 27.00005 | 17.51208 | 0.82738 | 19.52772 |
April | 485.00000 | 27.00006 | 19.51318 | 0.88169 | 21.48082 |
May | 508.00000 | 27.00040 | 21.96691 | 0.15936 | 5.61674 |
June | 496.00000 | 27.00058 | 23.78985 | 0.27486 | 6.65902 |
July | 497.00000 | 27.00041 | 24.08959 | 0.33058 | 7.34622 |
August | 514.00000 | 27.05557 | 23.85740 | 0.36882 | 8.02307 |
September | 485.00000 | 27.00029 | 21.89808 | 0.18804 | 5.87741 |
October | 502.00000 | 27.00011 | 19.00034 | 0.82078 | 19.31744 |
November | 489.00000 | 27.00005 | 19.78123 | 0.84542 | 20.18093 |
December | 497.00000 | 26.99999 | 14.63406 | 0.80889 | 18.93606 |
Annual Sum or Average | 5943.00000 | 27.00497 | 20.16118 | 0.58348 | 13.91825 |
Minimum of Months | 454.00000 | 26.99999 | 14.63406 | 0.15936 | 5.61674 |
Maximum of Months | 514.00000 | 27.05557 | 24.08959 | 0.88169 | 21.48082 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99950 | 18.42445 | 0.65145 | 14.13486 |
February | 454.00000 | 27.00002 | 17.18975 | 0.65240 | 14.21634 |
March | 514.00000 | 27.00004 | 17.49945 | 0.70617 | 15.68468 |
April | 485.00000 | 27.00006 | 19.50035 | 0.74509 | 16.87837 |
May | 508.00000 | 27.00036 | 21.99761 | 0.08819 | 5.30644 |
June | 496.00000 | 27.00057 | 23.81055 | 0.18745 | 5.84691 |
July | 497.00000 | 27.00044 | 24.10711 | 0.20756 | 5.98493 |
August | 514.00000 | 27.04818 | 23.86657 | 0.24023 | 6.42484 |
September | 485.00000 | 27.00027 | 21.92340 | 0.11459 | 5.45266 |
October | 502.00000 | 27.00010 | 18.98752 | 0.72626 | 16.29393 |
November | 489.00000 | 27.00005 | 19.76782 | 0.71138 | 15.82071 |
December | 497.00000 | 27.00000 | 14.62211 | 0.62964 | 13.59908 |
Annual Sum or Average | 5943.00000 | 27.00428 | 20.16445 | 0.46995 | 11.27202 |
Minimum of Months | 454.00000 | 26.99950 | 14.62211 | 0.08819 | 5.30644 |
Maximum of Months | 514.00000 | 27.04818 | 24.10711 | 0.74509 | 16.87837 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.63543 | 18.89015 | 0.49384 | 11.61000 |
February | 454.00000 | 27.00017 | 17.20146 | 0.57700 | 12.42651 |
March | 514.00000 | 27.00004 | 17.51644 | 0.64791 | 14.22208 |
April | 485.00000 | 27.00006 | 19.51041 | 0.68655 | 15.38263 |
May | 508.00000 | 26.99763 | 22.02037 | 0.05956 | 5.41743 |
June | 496.00000 | 27.00058 | 23.80988 | 0.19989 | 6.04072 |
July | 497.00000 | 27.00045 | 24.10639 | 0.21872 | 6.17106 |
August | 514.00000 | 27.03916 | 23.87489 | 0.24471 | 6.55582 |
September | 485.00000 | 27.00028 | 21.93200 | 0.10071 | 5.55439 |
October | 502.00000 | 27.00010 | 19.01618 | 0.66654 | 14.72444 |
November | 489.00000 | 27.00005 | 19.78437 | 0.63194 | 13.70456 |
December | 497.00000 | 27.00000 | 14.62791 | 0.54328 | 11.61346 |
Annual Sum or Average | 5943.00000 | 26.97253 | 20.21449 | 0.42104 | 10.26157 |
Minimum of Months | 454.00000 | 26.63543 | 14.62791 | 0.05956 | 5.41743 |
Maximum of Months | 514.00000 | 27.03916 | 24.10639 | 0.68655 | 15.38263 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00051 | 29.02067 | 1.03580 | 27.66812 |
February | 454.00000 | 27.00055 | 26.17374 | 1.16429 | 33.54518 |
March | 514.00000 | 27.00041 | 20.42613 | 1.27001 | 38.75622 |
April | 485.00000 | 27.00114 | 21.72508 | 1.42081 | 46.63635 |
May | 508.00000 | 27.00044 | 27.51759 | 0.45226 | 9.32834 |
June | 496.00000 | 27.00391 | 30.84844 | 0.74179 | 16.64386 |
July | 497.00000 | 27.00538 | 31.64705 | 0.96243 | 24.62481 |
August | 514.00000 | 27.01979 | 29.39156 | 1.13477 | 32.16426 |
September | 485.00000 | 27.00157 | 26.89155 | 0.52076 | 10.76913 |
October | 502.00000 | 27.00048 | 24.22591 | 1.19756 | 35.15281 |
November | 489.00000 | 27.00059 | 23.73248 | 1.32734 | 41.69933 |
December | 497.00000 | 27.00007 | 17.60901 | 1.39366 | 45.18127 |
Annual Sum or Average | 5943.00000 | 27.00296 | 25.77204 | 1.05085 | 30.14288 |
Minimum of Months | 454.00000 | 27.00007 | 17.60901 | 0.45226 | 9.32834 |
Maximum of Months | 514.00000 | 27.01979 | 31.64705 | 1.42081 | 46.63635 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.65680 | 19.83549 | 0.37127 | 9.39069 |
February | 454.00000 | 24.56836 | 16.71244 | 0.31924 | 7.63163 |
March | 514.00000 | 24.49087 | 16.45897 | 0.30968 | 7.37607 |
April | 485.00000 | 24.58915 | 20.53439 | 0.36306 | 8.26374 |
May | 508.00000 | 24.71788 | 25.94961 | -0.4057 | 10.35292 |
June | 496.00000 | 26.64481 | 57.38065 | 0.44953 | 20.81782 |
July | 497.00000 | 27.84276 | 73.39785 | 0.99067 | 36.67945 |
August | 514.00000 | 26.00088 | 44.91760 | 0.15953 | 13.14527 |
September | 485.00000 | 25.51579 | 29.93209 | -0.1006 | 12.08227 |
October | 502.00000 | 24.78310 | 18.28055 | 0.40557 | 9.46155 |
November | 489.00000 | 24.72724 | 19.18017 | 0.39563 | 9.08118 |
December | 497.00000 | 24.66792 | 13.00277 | 0.32781 | 7.84152 |
Annual Sum or Average | 5943.00000 | 25.27149 | 29.73396 | 0.29766 | 12.70350 |
Minimum of Months | 454.00000 | 24.49087 | 13.00277 | -0.4057 | 7.37607 |
Maximum of Months | 514.00000 | 27.84276 | 73.39785 | 0.99067 | 36.67945 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.25847 | 19.67474 | 0.27604 | 6.85077 |
February | 454.00000 | 24.23924 | 18.29999 | 0.26112 | 6.64870 |
March | 514.00000 | 24.24516 | 17.50347 | 0.27769 | 6.75874 |
April | 485.00000 | 24.38542 | 21.31529 | 0.34027 | 7.78012 |
May | 508.00000 | 24.30301 | 25.62961 | -0.5091 | 10.92273 |
June | 496.00000 | 24.31775 | 35.10645 | -0.3762 | 8.48172 |
July | 497.00000 | 24.50681 | 36.96651 | -0.2776 | 7.48678 |
August | 514.00000 | 24.31092 | 36.05362 | -0.3650 | 8.34360 |
September | 485.00000 | 24.37637 | 25.85033 | -0.4545 | 10.11084 |
October | 502.00000 | 24.38710 | 19.60787 | 0.32995 | 7.64056 |
November | 489.00000 | 24.35178 | 20.50824 | 0.32463 | 7.46245 |
December | 497.00000 | 24.31329 | 14.45286 | 0.26313 | 6.69237 |
Annual Sum or Average | 5943.00000 | 24.33302 | 24.30563 | 0.00485 | 7.93955 |
Minimum of Months | 454.00000 | 24.23924 | 14.45286 | -0.5091 | 6.64870 |
Maximum of Months | 514.00000 | 24.50681 | 36.96651 | 0.34027 | 10.92273 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63628 | 21.33370 | 0.09737 | 5.81425 |
February | 454.00000 | 23.53325 | 19.86065 | 0.06011 | 5.89120 |
March | 514.00000 | 23.78042 | 19.06945 | 0.13024 | 5.73775 |
April | 485.00000 | 23.95246 | 23.23746 | 0.19767 | 6.11055 |
May | 508.00000 | 24.19611 | 26.35127 | -0.5806 | 12.39067 |
June | 496.00000 | 24.20400 | 35.63369 | -0.4788 | 10.10689 |
July | 497.00000 | 24.24669 | 37.93536 | -0.4490 | 9.54410 |
August | 514.00000 | 24.23184 | 36.20729 | -0.4655 | 9.87336 |
September | 485.00000 | 24.21894 | 26.46950 | -0.5518 | 11.79352 |
October | 502.00000 | 24.05039 | 21.47586 | 0.22213 | 6.30711 |
November | 489.00000 | 23.82858 | 22.50172 | 0.15993 | 5.84881 |
December | 497.00000 | 23.29637 | 16.26908 | -0.0253 | 6.23050 |
Annual Sum or Average | 5943.00000 | 23.93440 | 25.58152 | -0.1424 | 7.98833 |
Minimum of Months | 454.00000 | 23.29637 | 16.26908 | -0.5806 | 5.73775 |
Maximum of Months | 514.00000 | 24.24669 | 37.93536 | 0.22213 | 12.39067 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92784 | 23.35293 | -0.3381 | 10.73945 |
February | 454.00000 | 22.12956 | 21.45557 | -0.3009 | 9.85193 |
March | 514.00000 | 22.76104 | 20.41019 | -0.1330 | 8.19955 |
April | 485.00000 | 22.89952 | 24.57014 | -0.0672 | 7.94325 |
May | 508.00000 | 23.93956 | 26.91689 | -0.6796 | 15.59205 |
June | 496.00000 | 24.22287 | 35.43321 | -0.4588 | 9.78903 |
July | 497.00000 | 24.28347 | 37.84826 | -0.4250 | 9.22998 |
August | 514.00000 | 24.22878 | 36.25325 | -0.4564 | 9.73781 |
September | 485.00000 | 24.10218 | 26.56709 | -0.5989 | 13.42146 |
October | 502.00000 | 23.13257 | 22.50792 | -0.0244 | 6.72860 |
November | 489.00000 | 22.45397 | 24.67581 | -0.1946 | 7.53516 |
December | 497.00000 | 21.66714 | 17.87026 | -0.4412 | 12.39328 |
Annual Sum or Average | 5943.00000 | 23.15481 | 26.53488 | -0.3438 | 10.10113 |
Minimum of Months | 454.00000 | 21.66714 | 17.87026 | -0.6796 | 6.72860 |
Maximum of Months | 514.00000 | 24.28347 | 37.84826 | -0.0244 | 15.59205 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.46724 | 21.63895 | -0.1909 | 7.28656 |
February | 454.00000 | 22.39719 | 19.94761 | -0.2162 | 7.77690 |
March | 514.00000 | 23.18460 | 18.33739 | -0.0193 | 6.27585 |
April | 485.00000 | 23.55755 | 21.62422 | 0.10687 | 6.08147 |
May | 508.00000 | 24.14905 | 25.19807 | -0.5736 | 12.84040 |
June | 496.00000 | 24.40338 | 34.17897 | -0.3047 | 7.87562 |
July | 497.00000 | 24.59482 | 36.19476 | -0.2089 | 7.33727 |
August | 514.00000 | 24.33275 | 35.34182 | -0.3441 | 8.33632 |
September | 485.00000 | 24.24916 | 25.39188 | -0.5119 | 12.01354 |
October | 502.00000 | 23.44694 | 20.58038 | 0.06230 | 6.30604 |
November | 489.00000 | 23.01952 | 22.37089 | -0.0442 | 6.10680 |
December | 497.00000 | 22.47822 | 15.95113 | -0.2266 | 8.14114 |
Annual Sum or Average | 5943.00000 | 23.53206 | 24.77764 | -0.2064 | 8.03452 |
Minimum of Months | 454.00000 | 22.39719 | 15.95113 | -0.5736 | 6.08147 |
Maximum of Months | 514.00000 | 24.59482 | 36.19476 | 0.10687 | 12.84040 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.98799 | 20.62709 | -0.0465 | 7.23111 |
February | 454.00000 | 22.86482 | 18.92729 | -0.0704 | 8.29519 |
March | 514.00000 | 23.32748 | 17.64536 | 0.06864 | 7.61160 |
April | 485.00000 | 23.52424 | 21.28378 | 0.15178 | 7.29058 |
May | 508.00000 | 24.27167 | 24.60875 | -0.4452 | 10.87301 |
June | 496.00000 | 24.45311 | 33.82388 | -0.1692 | 7.35392 |
July | 497.00000 | 24.63137 | 36.00721 | -0.0905 | 7.72124 |
August | 514.00000 | 24.37807 | 34.91138 | -0.2134 | 7.91943 |
September | 485.00000 | 24.38433 | 24.86160 | -0.3577 | 10.22822 |
October | 502.00000 | 23.61340 | 19.86341 | 0.14507 | 8.12214 |
November | 489.00000 | 23.22902 | 21.65550 | 0.03004 | 7.06788 |
December | 497.00000 | 22.66505 | 15.56664 | -0.1674 | 8.36980 |
Annual Sum or Average | 5943.00000 | 23.70098 | 24.19881 | -0.0977 | 8.17388 |
Minimum of Months | 454.00000 | 22.66505 | 15.56664 | -0.4452 | 7.06788 |
Maximum of Months | 514.00000 | 24.63137 | 36.00721 | 0.15178 | 10.87301 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53756 | 19.18980 | 0.17200 | 9.90986 |
February | 454.00000 | 23.30068 | 17.63999 | 0.10444 | 10.60078 |
March | 514.00000 | 23.41253 | 17.32475 | 0.12156 | 8.97184 |
April | 485.00000 | 23.40131 | 21.42124 | 0.11366 | 7.46085 |
May | 508.00000 | 24.12448 | 25.04461 | -0.5470 | 12.99857 |
June | 496.00000 | 24.39312 | 34.14201 | -0.2875 | 7.98499 |
July | 497.00000 | 24.56302 | 36.17870 | -0.1905 | 7.54732 |
August | 514.00000 | 24.41713 | 34.94355 | -0.2294 | 7.76920 |
September | 485.00000 | 24.44065 | 24.68700 | -0.3116 | 10.21322 |
October | 502.00000 | 23.78461 | 19.29927 | 0.24960 | 10.54122 |
November | 489.00000 | 23.81813 | 20.13269 | 0.25896 | 10.52168 |
December | 497.00000 | 23.35628 | 14.13987 | 0.07821 | 10.15802 |
Annual Sum or Average | 5943.00000 | 23.88343 | 23.73697 | -0.0407 | 9.55149 |
Minimum of Months | 454.00000 | 23.30068 | 14.13987 | -0.5470 | 7.46085 |
Maximum of Months | 514.00000 | 24.56302 | 36.17870 | 0.25896 | 12.99857 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.54443 | 19.49668 | 0.10553 | 7.05166 |
February | 454.00000 | 23.72402 | 17.57862 | 0.15805 | 7.57915 |
March | 514.00000 | 24.15013 | 16.18906 | 0.30686 | 8.18906 |
April | 485.00000 | 24.36245 | 19.81225 | 0.40778 | 9.21692 |
May | 508.00000 | 24.44282 | 24.35963 | -0.3551 | 9.49405 |
June | 496.00000 | 24.57723 | 33.58807 | -0.0894 | 7.57992 |
July | 497.00000 | 24.72387 | 35.75424 | -0.0226 | 7.42151 |
August | 514.00000 | 24.57935 | 34.45200 | -0.0555 | 7.26616 |
September | 485.00000 | 24.52392 | 24.66510 | -0.2874 | 9.44871 |
October | 502.00000 | 24.20719 | 18.85984 | 0.32915 | 8.88922 |
November | 489.00000 | 24.24937 | 19.67704 | 0.31999 | 8.36140 |
December | 497.00000 | 23.98230 | 13.53718 | 0.19697 | 7.57374 |
Annual Sum or Average | 5943.00000 | 24.25896 | 23.21908 | 0.08345 | 8.17164 |
Minimum of Months | 454.00000 | 23.54443 | 13.53718 | -0.3551 | 7.05166 |
Maximum of Months | 514.00000 | 24.72387 | 35.75424 | 0.40778 | 9.49405 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.03749 | 23.12751 | -0.5615 | 13.74201 |
February | 454.00000 | 21.00366 | 20.94880 | -0.5863 | 14.50088 |
March | 514.00000 | 21.88204 | 20.13349 | -0.3506 | 10.36688 |
April | 485.00000 | 22.29201 | 23.90296 | -0.2127 | 8.72063 |
May | 508.00000 | 23.81436 | 26.15647 | -0.7119 | 17.25091 |
June | 496.00000 | 24.31121 | 34.25445 | -0.3881 | 8.94538 |
July | 497.00000 | 24.41272 | 36.65995 | -0.3418 | 8.44093 |
August | 514.00000 | 24.22318 | 35.44294 | -0.4450 | 9.83763 |
September | 485.00000 | 23.94765 | 26.07554 | -0.6493 | 15.84124 |
October | 502.00000 | 22.37883 | 23.02891 | -0.2065 | 8.09632 |
November | 489.00000 | 21.46208 | 24.53830 | -0.4393 | 10.57861 |
December | 497.00000 | 20.67828 | 16.82297 | -0.7035 | 17.75131 |
Annual Sum or Average | 5943.00000 | 22.63439 | 25.97090 | -0.4656 | 11.98632 |
Minimum of Months | 454.00000 | 20.67828 | 16.82297 | -0.7119 | 8.09632 |
Maximum of Months | 514.00000 | 24.41272 | 36.65995 | -0.2065 | 17.75131 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.94114 | 21.34953 | -0.3295 | 10.25986 |
February | 385.00000 | 22.00884 | 19.17578 | -0.3149 | 12.25822 |
March | 433.00000 | 22.61913 | 18.24402 | -0.1285 | 10.23050 |
April | 410.00000 | 22.77178 | 22.38729 | -0.0484 | 9.27807 |
May | 430.00000 | 24.17466 | 24.99838 | -0.5064 | 13.09739 |
June | 418.00000 | 24.50074 | 33.42530 | -0.1961 | 8.03975 |
July | 422.00000 | 24.68165 | 35.71441 | -0.1388 | 8.46974 |
August | 433.00000 | 24.45406 | 34.51010 | -0.2376 | 8.61615 |
September | 410.00000 | 24.33988 | 24.88169 | -0.4159 | 12.08991 |
October | 427.00000 | 23.06515 | 21.00844 | -0.0120 | 9.53064 |
November | 417.00000 | 22.31802 | 22.62524 | -0.2188 | 9.11028 |
December | 422.00000 | 21.39814 | 15.67297 | -0.5178 | 14.55434 |
Annual Sum or Average | 5034.00000 | 23.19791 | 24.53985 | -0.2551 | 10.44876 |
Minimum of Months | 385.00000 | 21.39814 | 15.67297 | -0.5178 | 8.03975 |
Maximum of Months | 433.00000 | 24.68165 | 35.71441 | -0.0120 | 14.55434 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.37380 | 19.20292 | 0.13178 | 11.55368 |
February | 454.00000 | 23.06526 | 17.52743 | 0.03967 | 13.03223 |
March | 514.00000 | 22.99082 | 17.91241 | 0.01356 | 10.87062 |
April | 485.00000 | 22.77309 | 22.49796 | -0.0441 | 8.94284 |
May | 508.00000 | 23.93584 | 25.57798 | -0.6231 | 15.60276 |
June | 496.00000 | 24.31637 | 34.14601 | -0.3560 | 8.96736 |
July | 497.00000 | 24.44583 | 36.45458 | -0.2891 | 8.47238 |
August | 514.00000 | 24.36070 | 34.80353 | -0.2911 | 8.54013 |
September | 485.00000 | 24.35098 | 24.83147 | -0.3518 | 11.51669 |
October | 502.00000 | 23.54613 | 20.31454 | 0.19394 | 11.97044 |
November | 489.00000 | 23.54383 | 20.51973 | 0.18907 | 11.94847 |
December | 497.00000 | 22.85061 | 14.04278 | -0.0640 | 12.48266 |
Annual Sum or Average | 5943.00000 | 23.63434 | 24.04633 | -0.1227 | 11.14878 |
Minimum of Months | 454.00000 | 22.77309 | 14.04278 | -0.6231 | 8.47238 |
Maximum of Months | 514.00000 | 24.44583 | 36.45458 | 0.19394 | 15.60276 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.11876 | 21.27409 | -0.2681 | 10.01296 |
February | 454.00000 | 22.10565 | 19.22160 | -0.2767 | 11.41661 |
March | 514.00000 | 22.70975 | 18.68787 | -0.0972 | 9.65352 |
April | 485.00000 | 22.90101 | 22.59760 | -0.0161 | 8.56792 |
May | 508.00000 | 24.10245 | 25.36665 | -0.5262 | 13.61495 |
June | 496.00000 | 24.44099 | 33.83326 | -0.2195 | 8.33948 |
July | 497.00000 | 24.53594 | 36.24442 | -0.2037 | 7.91932 |
August | 514.00000 | 24.41430 | 34.82334 | -0.2540 | 8.29669 |
September | 485.00000 | 24.26408 | 25.23808 | -0.4359 | 12.38722 |
October | 502.00000 | 23.09384 | 21.44014 | 0.01854 | 8.96370 |
November | 489.00000 | 22.50088 | 22.60295 | -0.1546 | 8.65182 |
December | 497.00000 | 21.64146 | 15.66593 | -0.4387 | 13.23889 |
Annual Sum or Average | 5943.00000 | 23.24573 | 24.80129 | -0.2392 | 10.07879 |
Minimum of Months | 454.00000 | 21.64146 | 15.66593 | -0.5262 | 7.91932 |
Maximum of Months | 514.00000 | 24.53594 | 36.24442 | 0.01854 | 13.61495 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33161 | 23.63709 | -0.7856 | 21.11676 |
February | 454.00000 | 20.48824 | 21.32868 | -0.7613 | 19.78742 |
March | 514.00000 | 21.39029 | 20.51545 | -0.5048 | 14.16545 |
April | 485.00000 | 21.59794 | 24.75203 | -0.4003 | 13.74644 |
May | 508.00000 | 23.49098 | 26.71759 | -0.8289 | 22.22737 |
June | 496.00000 | 24.28986 | 34.23378 | -0.3836 | 9.14037 |
July | 497.00000 | 24.39378 | 36.76753 | -0.3368 | 8.75541 |
August | 514.00000 | 24.16716 | 35.69419 | -0.4542 | 10.39424 |
September | 485.00000 | 23.74952 | 26.28059 | -0.7198 | 19.10053 |
October | 502.00000 | 21.72333 | 23.18371 | -0.3965 | 11.68778 |
November | 489.00000 | 20.78707 | 25.06446 | -0.6480 | 16.44212 |
December | 497.00000 | 20.15130 | 16.98797 | -0.8891 | 24.42376 |
Annual Sum or Average | 5943.00000 | 22.22922 | 26.30916 | -0.5911 | 15.87771 |
Minimum of Months | 454.00000 | 20.15130 | 16.98797 | -0.8891 | 8.75541 |
Maximum of Months | 514.00000 | 24.39378 | 36.76753 | -0.3368 | 24.42376 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.19952 | 22.51151 | -0.5452 | 15.58955 |
February | 454.00000 | 21.59238 | 19.94250 | -0.4541 | 15.14243 |
March | 514.00000 | 22.31900 | 18.84297 | -0.2275 | 12.07558 |
April | 485.00000 | 22.29085 | 23.13183 | -0.1779 | 12.94536 |
May | 508.00000 | 23.94972 | 25.26154 | -0.5762 | 15.21473 |
June | 496.00000 | 24.40891 | 33.56821 | -0.1907 | 7.82738 |
July | 497.00000 | 24.56527 | 36.16762 | -0.1412 | 8.31852 |
August | 514.00000 | 24.35018 | 34.69694 | -0.2329 | 8.46731 |
September | 485.00000 | 24.18003 | 25.03154 | -0.4499 | 13.00549 |
October | 502.00000 | 22.65104 | 21.20433 | -0.1395 | 11.18700 |
November | 489.00000 | 21.66618 | 23.55188 | -0.4093 | 12.39545 |
December | 497.00000 | 20.83119 | 16.49538 | -0.6951 | 19.67801 |
Annual Sum or Average | 5943.00000 | 22.84576 | 25.08011 | -0.3524 | 12.62810 |
Minimum of Months | 454.00000 | 20.83119 | 16.49538 | -0.6951 | 7.82738 |
Maximum of Months | 514.00000 | 24.56527 | 36.16762 | -0.1395 | 19.67801 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.61569 | 19.82469 | -0.1015 | 13.10797 |
February | 454.00000 | 22.50719 | 18.04579 | -0.1417 | 14.47716 |
March | 514.00000 | 22.55525 | 18.31580 | -0.1278 | 12.67730 |
April | 485.00000 | 22.11682 | 23.37446 | -0.2220 | 13.43846 |
May | 508.00000 | 23.65350 | 26.07950 | -0.7282 | 19.92506 |
June | 496.00000 | 24.27657 | 34.16801 | -0.3568 | 9.39446 |
July | 497.00000 | 24.41266 | 36.60137 | -0.2883 | 8.95076 |
August | 514.00000 | 24.30354 | 35.04653 | -0.3004 | 9.06532 |
September | 485.00000 | 24.20102 | 24.92473 | -0.4078 | 13.58523 |
October | 502.00000 | 23.01936 | 20.29106 | 0.03146 | 13.19708 |
November | 489.00000 | 22.94071 | 20.97575 | -0.0031 | 12.52517 |
December | 497.00000 | 22.17122 | 14.49230 | -0.2764 | 15.30195 |
Annual Sum or Average | 5943.00000 | 23.23809 | 24.40361 | -0.2447 | 12.95978 |
Minimum of Months | 454.00000 | 22.11682 | 14.49230 | -0.7282 | 8.95076 |
Maximum of Months | 514.00000 | 24.41266 | 36.60137 | 0.03146 | 19.92506 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37003 | 21.90785 | -0.4886 | 15.10205 |
February | 454.00000 | 21.58048 | 19.70460 | -0.4408 | 14.81152 |
March | 514.00000 | 22.24541 | 19.14346 | -0.2364 | 12.07293 |
April | 485.00000 | 22.26281 | 23.39932 | -0.1832 | 12.27693 |
May | 508.00000 | 23.85854 | 25.78659 | -0.6171 | 17.17559 |
June | 496.00000 | 24.41616 | 33.83125 | -0.2163 | 8.68021 |
July | 497.00000 | 24.50755 | 36.36261 | -0.2022 | 8.28232 |
August | 514.00000 | 24.37234 | 35.02634 | -0.2596 | 8.68492 |
September | 485.00000 | 24.11037 | 25.37632 | -0.4916 | 14.67047 |
October | 502.00000 | 22.55461 | 21.56021 | -0.1391 | 11.00897 |
November | 489.00000 | 21.87212 | 23.11830 | -0.3414 | 11.69388 |
December | 497.00000 | 21.05756 | 15.99493 | -0.6206 | 18.15725 |
Annual Sum or Average | 5943.00000 | 22.86254 | 25.15106 | -0.3524 | 12.69738 |
Minimum of Months | 454.00000 | 21.05756 | 15.99493 | -0.6206 | 8.28232 |
Maximum of Months | 514.00000 | 24.50755 | 36.36261 | -0.1391 | 18.15725 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.136295E+11 | 129874.53 | 20-JAN-15:00 | 195.45 | 0.110351E+12 | 0.00 | 0.123980E+12 | 2.18 | 8.68 | 23-JAN-11:00 | 0.00 | 0.00 |
February | 0.107450E+11 | 73729.92 | 17-FEB-15:10 | 192.99 | 0.906780E+11 | 0.00 | 0.101423E+12 | 2.40 | 8.68 | 17-FEB-11:10 | 0.00 | 0.00 |
March | 0.183282E+11 | 157636.33 | 14-MAR-14:05 | 216.51 | 0.147135E+12 | 0.00 | 0.165464E+12 | 2.41 | 8.68 | 03-MAR-14:20 | 0.00 | 0.00 |
April | 0.151731E+11 | 129172.12 | 19-APR-13:30 | 210.36 | 0.124911E+12 | 0.00 | 0.140084E+12 | 2.43 | 8.68 | 07-APR-11:30 | 0.00 | 0.00 |
May | 0.413829E+11 | 156910.07 | 18-MAY-12:20 | 322.24 | 0.329117E+12 | 0.00 | 0.370500E+12 | 3.56 | 8.68 | 23-MAY-14:50 | 0.00 | 0.00 |
June | 0.106038E+12 | 165445.51 | 22-JUN-09:10 | 537.12 | 0.830406E+12 | 0.00 | 0.936444E+12 | 6.03 | 8.71 | 24-JUN-05:03 | 0.00 | 0.00 |
July | 0.112619E+12 | 166554.68 | 20-JUL-11:50 | 614.66 | 0.875401E+12 | 0.00 | 0.988019E+12 | 6.68 | 8.73 | 17-JUL-04:12 | 0.00 | 0.00 |
August | 0.104664E+12 | 164429.28 | 05-AUG-10:00 | 616.35 | 0.821589E+12 | 0.00 | 0.926252E+12 | 6.72 | 8.72 | 01-AUG-05:03 | 0.00 | 0.00 |
September | 0.782621E+11 | 161729.22 | 05-SEP-12:25 | 426.35 | 0.617967E+12 | 0.00 | 0.696229E+12 | 4.82 | 8.72 | 13-SEP-04:12 | 0.00 | 0.00 |
October | 0.316170E+11 | 162252.32 | 17-OCT-15:40 | 252.95 | 0.254169E+12 | 0.00 | 0.285786E+12 | 2.81 | 8.70 | 08-OCT-12:04 | 0.00 | 0.00 |
November | 0.170807E+11 | 158977.24 | 07-NOV-15:10 | 211.31 | 0.139537E+12 | 0.00 | 0.156617E+12 | 2.44 | 8.71 | 05-NOV-14:24 | 0.00 | 0.00 |
December | 0.968558E+10 | 102266.22 | 01-DEC-15:00 | 176.78 | 0.810159E+11 | 0.00 | 0.907015E+11 | 1.98 | 8.68 | 14-DEC-12:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.559225E+12 | 3973.06 | 0.442228E+13 | 0.00 | 0.498150E+13 | 3.71 | 0.00 | 0.00 | ||||
Minimum of Months | 0.968558E+10 | 73729.92 | 176.78 | 0.810159E+11 | 0.00 | 0.907015E+11 | 1.98 | 8.68 | 0.00 | 0.00 | ||
Maximum of Months | 0.112619E+12 | 166554.68 | 616.35 | 0.875401E+12 | 0.00 | 0.988019E+12 | 6.72 | 8.73 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.864165E+09 | 79868.28 | 14-MAR-14:15 | 4.00 | 0.710307E+10 | 0.00 | 0.796724E+10 | 0.04 | 8.61 | 14-MAR-12:20 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.645469E+10 | 92336.71 | 16-MAY-12:05 | 26.58 | 0.529336E+11 | 0.00 | 0.593883E+11 | 0.29 | 8.67 | 17-MAY-11:50 | 0.00 | 0.00 |
June | 0.470262E+11 | 135017.82 | 22-JUN-08:33 | 164.60 | 0.370814E+12 | 0.00 | 0.417840E+12 | 1.81 | 8.67 | 07-JUN-17:30 | 0.00 | 0.00 |
July | 0.435476E+11 | 145699.14 | 19-JUL-10:03 | 154.96 | 0.344037E+12 | 0.00 | 0.387585E+12 | 1.66 | 8.67 | 08-JUL-10:50 | 0.00 | 0.00 |
August | 0.458317E+11 | 123793.31 | 07-AUG-08:63 | 161.72 | 0.362387E+12 | 0.00 | 0.408218E+12 | 1.73 | 8.67 | 26-AUG-10:40 | 0.00 | 0.00 |
September | 0.255820E+11 | 111650.37 | 12-SEP-14:43 | 96.67 | 0.205503E+12 | 0.00 | 0.231085E+12 | 1.08 | 8.67 | 07-SEP-16:40 | 0.00 | 0.00 |
October | 0.266099E+10 | 91346.83 | 11-OCT-12:05 | 11.17 | 0.215445E+11 | 0.00 | 0.242054E+11 | 0.12 | 8.61 | 10-OCT-11:30 | 0.00 | 0.00 |
November | 0.326442E+09 | 75031.83 | 07-NOV-16:00 | 1.33 | 0.265279E+10 | 0.00 | 0.297923E+10 | 0.02 | 8.30 | 07-NOV-14:30 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.172294E+12 | 621.03 | 0.136697E+13 | 0.00 | 0.153927E+13 | 0.57 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.470262E+11 | 145699.14 | 164.60 | 0.370814E+12 | 0.00 | 0.417840E+12 | 1.81 | 8.67 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.285089E+10 | 744.00 | 43776.24 | 20-JAN-11:05 | 60570.79 | 23-JAN-16:10 | 18.80 | 18.35 | 17.46 |
February | 0.268024E+10 | 672.00 | 43776.24 | 18-FEB-12:00 | 95443.71 | 28-FEB-07:15 | 19.27 | 18.34 | 17.46 |
March | 0.103141E+11 | 744.00 | 43776.24 | 11-MAR-13:40 | 419890.20 | 14-MAR-13:05 | 20.08 | 18.49 | 17.47 |
April | 0.154089E+11 | 720.00 | 43776.24 | 06-APR-12:50 | 483373.35 | 19-APR-13:30 | 20.92 | 18.58 | 17.47 |
May | 0.329278E+11 | 744.00 | 43776.24 | 04-MAY-08:20 | 256367.16 | 17-MAY-14:05 | 20.12 | 19.33 | 17.47 |
June | 0.820482E+11 | 720.00 | 43776.24 | 01-JUN-08:00 | 516235.68 | 18-JUN-10:50 | 27.75 | 24.23 | 17.47 |
July | 0.996481E+11 | 744.00 | 43776.24 | 01-JUL-00:05 | 788196.73 | 30-JUL-12:40 | 31.46 | 25.36 | 17.47 |
August | 0.102042E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 833160.75 | 05-AUG-14:15 | 33.52 | 25.17 | 17.47 |
September | 0.627337E+11 | 720.00 | 43776.24 | 01-SEP-00:05 | 277407.90 | 10-SEP-16:51 | 22.85 | 21.50 | 17.46 |
October | 0.150110E+11 | 744.00 | 43776.24 | 01-OCT-14:52 | 398661.55 | 11-OCT-14:05 | 19.80 | 18.65 | 17.47 |
November | 0.778230E+10 | 720.00 | 43776.24 | 05-NOV-09:52 | 342071.94 | 07-NOV-15:00 | 19.97 | 18.44 | 17.47 |
December | 0.747601E+10 | 744.00 | 43776.24 | 01-DEC-10:40 | 479270.26 | 01-DEC-14:05 | 20.35 | 18.42 | 17.46 |
Annual Sum or Average | 0.440923E+12 | 8760.00 | 22.94 | 20.42 | 17.47 | ||||
Minimum of Months | 0.268024E+10 | 672.00 | 43776.24 | 60570.79 | 18.80 | 18.34 | 17.46 | ||
Maximum of Months | 0.102042E+12 | 744.00 | 43776.24 | 833160.75 | 33.52 | 25.36 | 17.47 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 32429464.40 | 47.75 | 689.37 | 20-JAN-15:30 | 1033376.77 | 20-JAN-15:00 | 21.17 | 20.94 | 6.81 |
February | 19158658.83 | 60.28 | 242.08 | 17-FEB-15:05 | 683429.02 | 17-FEB-15:40 | 21.14 | 20.94 | 7.84 |
March | 54825557.33 | 83.75 | 1199.73 | 14-MAR-14:05 | 1175664.84 | 14-MAR-14:05 | 21.20 | 20.90 | 9.09 |
April | 54583159.76 | 77.31 | 992.52 | 20-APR-13:05 | 1025905.53 | 19-APR-13:30 | 21.24 | 20.98 | 9.00 |
May | 0.358706E+09 | 198.63 | 3502.08 | 31-MAY-17:00 | 1141492.99 | 04-MAY-13:20 | 21.78 | 21.09 | 18.00 |
June | 0.271883E+10 | 438.59 | 15130.18 | 01-JUN-11:20 | 1185126.33 | 22-JUN-09:10 | 23.01 | 21.17 | 35.51 |
July | 0.501856E+10 | 464.61 | 15130.18 | 18-JUL-16:10 | 1184551.80 | 27-JUL-08:40 | 23.00 | 21.14 | 37.70 |
August | 0.320706E+10 | 429.03 | 15130.18 | 02-AUG-17:00 | 1160450.57 | 31-AUG-08:20 | 22.88 | 21.10 | 36.12 |
September | 0.808503E+09 | 343.50 | 15130.18 | 01-SEP-12:00 | 1177740.13 | 15-SEP-12:50 | 22.53 | 21.15 | 28.61 |
October | 0.131893E+09 | 146.68 | 1348.62 | 10-OCT-10:30 | 1199096.60 | 13-OCT-15:00 | 21.53 | 21.01 | 13.61 |
November | 48134966.22 | 88.71 | 895.21 | 07-NOV-14:10 | 1128879.00 | 06-NOV-14:30 | 21.23 | 20.94 | 9.19 |
December | 18957473.13 | 42.78 | 454.25 | 01-DEC-15:00 | 867842.75 | 01-DEC-15:00 | 21.13 | 20.97 | 6.27 |
Annual Sum or Average | 0.124716E+11 | 2421.62 | 21.82 | 21.03 | 18.20 | ||||
Minimum of Months | 18957473.13 | 42.78 | 242.08 | 683429.02 | 21.13 | 20.90 | 6.27 | ||
Maximum of Months | 0.501856E+10 | 464.61 | 15130.18 | 1199096.60 | 23.01 | 21.17 | 37.70 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.17 | 21.17 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.14 | 21.14 | 0.00 |
March | 6099211.94 | 2.50 | 1033.34 | 14-MAR-12:30 | 992729.39 | 14-MAR-14:15 | 21.20 | 21.19 | 0.18 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.24 | 21.24 | 0.00 |
May | 60497748.35 | 23.25 | 2974.79 | 31-MAY-16:30 | 1059832.82 | 31-MAY-15:20 | 21.78 | 21.64 | 1.65 |
June | 0.110272E+10 | 151.10 | 15130.18 | 15-JUN-12:30 | 1078528.90 | 08-JUN-14:40 | 23.01 | 22.15 | 11.08 |
July | 0.219888E+10 | 142.71 | 15130.18 | 18-JUL-16:10 | 1135281.57 | 19-JUL-10:03 | 23.00 | 22.23 | 10.12 |
August | 0.162238E+10 | 151.58 | 15130.18 | 03-AUG-10:30 | 1078766.46 | 02-AUG-12:40 | 22.88 | 22.04 | 10.73 |
September | 0.225967E+09 | 85.08 | 3634.81 | 01-SEP-11:30 | 1077907.10 | 05-SEP-14:40 | 22.53 | 22.02 | 6.24 |
October | 24861158.42 | 8.42 | 1348.62 | 10-OCT-10:40 | 1071764.33 | 11-OCT-15:00 | 21.53 | 21.48 | 0.60 |
November | 545853.26 | 0.50 | 336.08 | 07-NOV-15:30 | 930531.39 | 07-NOV-15:30 | 21.23 | 21.23 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.13 | 21.13 | 0.00 |
Annual Sum or Average | 0.524196E+10 | 565.14 | 21.82 | 21.56 | 3.40 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 21.13 | 0.00 | ||
Maximum of Months | 0.219888E+10 | 151.58 | 15130.18 | 1135281.57 | 23.01 | 22.23 | 11.08 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.232296E+12 | 0.00 | 400.15 | 1164055.04 | 30-JAN-06:01 | 0.00 | 33.78 | 58.94 | 0.52 | 0.00 | 0.04 | 0.54 | 30-JAN-06:01 |
February | 0.242581E+12 | 0.00 | 368.34 | 1372415.58 | 06-FEB-06:02 | 0.00 | 33.89 | 59.26 | 0.56 | 0.00 | 0.05 | 0.64 | 06-FEB-06:02 |
March | 0.145524E+12 | 0.00 | 320.79 | 1163114.78 | 21-MAR-04:01 | 0.00 | 30.08 | 51.35 | 0.28 | 0.00 | 0.03 | 0.54 | 21-MAR-04:01 |
April | 0.912542E+11 | 0.00 | 251.69 | 1120154.76 | 24-APR-04:01 | 0.00 | 28.74 | 46.64 | 0.18 | 0.00 | 0.02 | 0.52 | 24-APR-04:01 |
May | 0.738560E+10 | 0.00 | 55.84 | 714977.67 | 01-MAY-05:03 | 0.00 | 25.61 | 29.74 | 0.01 | 0.00 | 0.00 | 0.33 | 01-MAY-05:03 |
June | 1607930.38 | 0.00 | 0.33 | 1901.80 | 09-JUN-06:10 | 0.00 | 23.01 | 23.03 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 23.00 | 23.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 23.00 | 23.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.566491E+10 | 0.00 | 22.08 | 432111.15 | 21-SEP-13:05 | 0.00 | 23.84 | 25.47 | 0.01 | 0.00 | 0.00 | 0.20 | 21-SEP-13:05 |
October | 0.114844E+12 | 0.00 | 222.85 | 1159818.89 | 23-OCT-05:01 | 0.00 | 28.31 | 43.36 | 0.24 | 0.00 | 0.02 | 0.54 | 23-OCT-05:01 |
November | 0.180931E+12 | 0.00 | 315.61 | 1233335.31 | 27-NOV-05:01 | 0.00 | 31.17 | 52.65 | 0.39 | 0.00 | 0.03 | 0.58 | 27-NOV-05:01 |
December | 0.364712E+12 | 0.00 | 444.17 | 1424038.28 | 26-DEC-06:03 | 0.00 | 36.25 | 62.42 | 0.95 | 0.00 | 0.06 | 0.67 | 26-DEC-06:03 |
Annual Sum or Average | 0.138519E+13 | 0.00 | 2401.85 | 0.00 | 28.36 | 41.48 | 0.26 | 0.00 | 0.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 23.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.364712E+12 | 0.00 | 444.17 | 1424038.28 | 0.00 | 36.25 | 62.42 | 0.95 | 0.00 | 0.06 | 0.67 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.80 | 18.80 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.27 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.08 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.92 | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.12 | 20.12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 27.75 | 27.75 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 31.46 | 31.46 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 33.52 | 33.52 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 22.85 | 22.85 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.80 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.97 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.35 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 22.94 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 18.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 | 33.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.139367E+11 | 0.00 | 151.78 | 0.139367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67869.72 | 19-JAN-15:00 | 67869.72 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.127235E+11 | 0.00 | 139.10 | 0.127235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65716.94 | 17-FEB-15:00 | 65716.94 | 17-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.154410E+11 | 0.00 | 164.76 | 0.154410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98274.51 | 13-MAR-16:00 | 98274.51 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.117473E+11 | 0.00 | 132.05 | 0.117473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79952.20 | 19-APR-13:30 | 79952.20 | 19-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.342962E+11 | 0.00 | 262.65 | 0.342962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109630.48 | 17-MAY-13:30 | 109630.48 | 17-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.121447E+12 | 0.00 | 513.87 | 0.121148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184073.72 | 26-JUN-14:53 | 184073.72 | 26-JUN-14:53 | 0.00 | 0.00 | 0.00 |
July | 0.137324E+12 | 0.00 | 586.60 | 0.132943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 175291.26 | 18-JUL-11:43 | 175291.26 | 18-JUL-11:43 | 0.00 | 0.00 | 0.00 |
August | 0.123083E+12 | 0.00 | 595.89 | 0.122002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 165735.86 | 16-AUG-09:23 | 165735.86 | 16-AUG-09:23 | 0.00 | 0.00 | 0.00 |
September | 0.770234E+11 | 0.00 | 390.53 | 0.770234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137227.55 | 11-SEP-14:30 | 137227.55 | 11-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.199038E+11 | 0.00 | 177.92 | 0.199038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120332.71 | 10-OCT-15:20 | 120332.71 | 10-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.154334E+11 | 0.00 | 160.09 | 0.154334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82992.56 | 06-NOV-14:00 | 82992.56 | 06-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.159174E+11 | 0.00 | 147.91 | 0.159174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70093.13 | 13-DEC-15:00 | 70093.13 | 13-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598277E+12 | 0.00 | 3423.14 | 0.592516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.117473E+11 | 0.00 | 132.05 | 0.117473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65716.94 | 65716.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137324E+12 | 0.00 | 595.89 | 0.132943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184073.72 | 184073.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.838787E+11 | 0.00 | 121.60 | 0.838787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 642462.95 | 20-JAN-15:05 | 642462.95 | 20-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.719761E+11 | 0.00 | 142.25 | 0.719761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 519264.21 | 27-FEB-15:05 | 519264.21 | 27-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.118505E+12 | 0.00 | 160.75 | 0.118505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 801014.26 | 13-MAR-15:50 | 801014.26 | 13-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.965082E+11 | 0.00 | 159.05 | 0.965082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 604267.40 | 20-APR-13:00 | 604267.40 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.292364E+12 | 0.00 | 272.79 | 0.292364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 993008.15 | 16-MAY-14:05 | 993008.15 | 16-MAY-14:05 | 0.00 | 0.00 | 0.00 |
June | 0.931107E+12 | 0.00 | 460.10 | 0.929768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1553896.27 | 26-JUN-14:13 | 1553896.27 | 26-JUN-14:13 | 0.00 | 0.00 | 0.00 |
July | 0.935541E+12 | 0.00 | 468.09 | 0.918672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1270307.30 | 17-JUL-10:30 | 1270307.30 | 17-JUL-10:30 | 0.00 | 0.00 | 0.00 |
August | 0.902272E+12 | 0.00 | 453.81 | 0.899382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1313125.32 | 16-AUG-15:10 | 1313125.32 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.630126E+12 | 0.00 | 381.14 | 0.630126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1161776.72 | 12-SEP-16:00 | 1161776.72 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.223757E+12 | 0.00 | 211.08 | 0.223757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 987231.47 | 11-OCT-14:05 | 987231.47 | 11-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.110504E+12 | 0.00 | 142.95 | 0.110504E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 768168.70 | 07-NOV-15:05 | 768168.70 | 07-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.566342E+11 | 0.00 | 103.35 | 0.566342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 541247.86 | 01-DEC-15:05 | 541247.86 | 01-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.445317E+13 | 0.00 | 3076.97 | 0.443207E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.566342E+11 | 0.00 | 103.35 | 0.566342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 519264.21 | 519264.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.935541E+12 | 0.00 | 468.09 | 0.929768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1553896.27 | 1553896.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.396128E+10 | 0.00 | 64.50 | 0.396128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48963.03 | 24-JAN-15:00 | 48963.03 | 24-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.391430E+10 | 0.00 | 79.41 | 0.391430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45860.85 | 17-FEB-15:30 | 45860.85 | 17-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.900666E+10 | 0.00 | 104.01 | 0.900666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83476.84 | 13-MAR-15:40 | 83476.84 | 13-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.746058E+10 | 0.00 | 95.23 | 0.746058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65701.87 | 20-APR-13:00 | 65701.87 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.296599E+11 | 0.00 | 249.28 | 0.296599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118211.73 | 31-MAY-15:20 | 118211.73 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.104572E+12 | 0.00 | 453.66 | 0.104486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198718.28 | 26-JUN-14:53 | 198718.28 | 26-JUN-14:53 | 0.00 | 0.00 | 0.00 |
July | 0.103156E+12 | 0.00 | 467.48 | 0.101484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 161573.84 | 12-JUL-15:05 | 161573.84 | 12-JUL-15:05 | 0.00 | 0.00 | 0.00 |
August | 0.998789E+11 | 0.00 | 448.09 | 0.996158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159716.07 | 16-AUG-15:10 | 159716.07 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.652625E+11 | 0.00 | 367.86 | 0.652625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133822.40 | 12-SEP-16:00 | 133822.40 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.139819E+11 | 0.00 | 141.71 | 0.139819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109708.93 | 11-OCT-15:00 | 109708.93 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.655891E+10 | 0.00 | 88.84 | 0.655891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63164.00 | 07-NOV-15:00 | 63164.00 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.339121E+10 | 0.00 | 62.82 | 0.339121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40836.19 | 01-DEC-14:00 | 40836.19 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450805E+12 | 0.00 | 2622.90 | 0.448783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.339121E+10 | 0.00 | 62.82 | 0.339121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40836.19 | 40836.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.104572E+12 | 0.00 | 467.48 | 0.104486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198718.28 | 198718.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.270567E+10 | 0.00 | 51.67 | 0.270567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35726.33 | 23-JAN-13:10 | 35726.33 | 23-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.228756E+09 | 0.00 | 9.67 | 0.228756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16297.72 | 18-FEB-13:00 | 16297.72 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.531894E+10 | 0.00 | 78.90 | 0.531894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58589.98 | 13-MAR-14:00 | 58589.98 | 13-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.674288E+10 | 0.00 | 108.25 | 0.674288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39817.93 | 20-APR-13:00 | 39817.93 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.202845E+11 | 0.00 | 224.01 | 0.202742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64685.63 | 18-MAY-13:10 | 64685.63 | 18-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.328398E+11 | 0.00 | 172.12 | 0.320597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93912.30 | 28-JUN-14:00 | 93912.30 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.290913E+11 | 0.00 | 115.82 | 0.234935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103083.66 | 28-JUL-13:00 | 99389.91 | 12-JUL-11:55 | 0.00 | 0.00 | 0.00 |
August | 0.482149E+11 | 0.00 | 244.37 | 0.463505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91644.33 | 22-AUG-12:43 | 91644.33 | 22-AUG-12:43 | 0.00 | 0.00 | 0.00 |
September | 0.397638E+11 | 0.00 | 242.54 | 0.396640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94696.02 | 12-SEP-16:10 | 94696.02 | 12-SEP-16:10 | 0.00 | 0.00 | 0.00 |
October | 0.983681E+10 | 0.00 | 96.18 | 0.983681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84460.85 | 10-OCT-14:00 | 84460.85 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.460979E+10 | 0.00 | 61.68 | 0.460979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58448.22 | 06-NOV-13:05 | 58448.22 | 06-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 0.234985E+10 | 0.00 | 34.39 | 0.234985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48746.40 | 04-DEC-12:00 | 48746.40 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201987E+12 | 0.00 | 1439.59 | 0.193635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.228756E+09 | 0.00 | 9.67 | 0.228756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16297.72 | 16297.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.482149E+11 | 0.00 | 244.37 | 0.463505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103083.66 | 99389.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.102744E+11 | 0.552321E+10 | 744.00 | 0.874128E+10 | 0.153309E+10 | 0.00 | 0.02 | 20-JAN-13:20 | 0.01 | 28-JAN-10:55 | 5661.82 | 19-JAN-11:20 | 4929.82 | 23-JAN-17:15 | 803.21 | 19-JAN-11:20 | 2723.28 | 20-JAN-14:00 | 0.00 |
February | 0.138837E+11 | 0.634727E+10 | 672.00 | 0.119627E+11 | 0.192099E+10 | 0.00 | 0.08 | 18-FEB-14:00 | 0.02 | 19-FEB-14:23 | 25222.53 | 18-FEB-14:00 | 25222.53 | 18-FEB-14:00 | 1256.75 | 20-FEB-10:20 | 9059.05 | 18-FEB-14:00 | 0.00 |
March | 0.323836E+11 | 0.129358E+11 | 744.00 | 0.309264E+11 | 0.145717E+10 | 0.00 | 0.65 | 14-MAR-13:00 | 0.01 | 17-MAR-15:00 | 239683.53 | 14-MAR-13:00 | 239683.53 | 14-MAR-13:00 | 1823.80 | 20-MAR-11:50 | 83812.94 | 14-MAR-13:00 | 0.00 |
April | 0.680681E+11 | 0.229658E+11 | 718.50 | 0.641576E+11 | 0.391043E+10 | 0.00 | 0.70 | 19-APR-13:00 | 0.01 | 28-APR-17:10 | 271669.57 | 19-APR-14:00 | 271669.57 | 19-APR-14:00 | 79262.28 | 28-APR-14:00 | 87425.46 | 19-APR-13:10 | 0.00 |
May | 0.271148E+11 | 0.114146E+11 | 676.22 | 0.257626E+11 | 0.135216E+10 | 0.00 | 0.38 | 17-MAY-11:00 | 0.00 | 15-MAY-17:10 | 155371.21 | 31-MAY-16:00 | 145804.22 | 16-MAY-16:00 | 13553.20 | 31-MAY-16:50 | 52467.98 | 17-MAY-14:00 | 0.00 |
June | 0.285274E+12 | 0.970120E+11 | 617.49 | 0.256761E+12 | 0.285124E+11 | 0.00 | 0.69 | 18-JUN-10:50 | 0.00 | 06-JUN-05:40 | 346031.06 | 18-JUN-10:42 | 238769.40 | 26-JUN-14:53 | 123358.95 | 18-JUN-10:42 | 107859.90 | 26-JUN-15:00 | 0.00 |
July | 0.564969E+12 | 0.176842E+12 | 724.50 | 0.470585E+12 | 0.943843E+11 | 0.00 | 1.00 | 30-JUL-12:32 | 0.00 | 12-JUL-01:00 | 534951.81 | 30-JUL-12:22 | 330526.50 | 10-JUL-09:30 | 258249.14 | 31-JUL-23:05 | 147775.09 | 30-JUL-12:40 | 0.00 |
August | 0.799039E+12 | 0.237312E+12 | 738.31 | 0.640424E+12 | 0.158614E+12 | 0.00 | 1.00 | 04-AUG-09:30 | 0.01 | 12-AUG-20:55 | 538210.09 | 05-AUG-14:40 | 429641.89 | 05-AUG-10:25 | 333151.21 | 04-AUG-02:00 | 175108.16 | 16-AUG-16:00 | 0.00 |
September | 0.871397E+11 | 0.317151E+11 | 680.38 | 0.821830E+11 | 0.495667E+10 | 0.00 | 0.39 | 18-SEP-12:40 | 0.00 | 02-SEP-04:12 | 157758.99 | 11-SEP-16:00 | 147250.24 | 18-SEP-12:40 | 18851.38 | 01-SEP-12:00 | 57514.11 | 09-SEP-13:00 | 0.00 |
October | 0.277411E+11 | 0.113782E+11 | 744.00 | 0.260217E+11 | 0.171940E+10 | 0.00 | 0.63 | 11-OCT-14:00 | 0.01 | 03-OCT-13:00 | 239058.22 | 11-OCT-14:00 | 239058.22 | 11-OCT-14:00 | 1454.03 | 31-OCT-23:10 | 87003.85 | 11-OCT-14:00 | 0.00 |
November | 0.272408E+11 | 0.109019E+11 | 720.00 | 0.249832E+11 | 0.225752E+10 | 0.00 | 0.51 | 06-NOV-14:00 | 0.02 | 09-NOV-24:00 | 181950.27 | 07-NOV-15:00 | 181950.27 | 07-NOV-15:00 | 2522.41 | 09-NOV-09:50 | 61964.01 | 06-NOV-14:00 | 0.00 |
December | 0.344378E+11 | 0.135511E+11 | 744.00 | 0.340012E+11 | 0.436586E+09 | 0.00 | 0.71 | 01-DEC-14:00 | 0.03 | 23-DEC-08:23 | 270673.05 | 01-DEC-14:00 | 270673.05 | 01-DEC-14:00 | 1370.28 | 30-DEC-17:10 | 88393.06 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.197757E+13 | 0.637899E+12 | 8523.38 | 0.167651E+13 | 0.301055E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.102744E+11 | 0.552321E+10 | 617.49 | 0.874128E+10 | 0.436586E+09 | 0.00 | 0.02 | 0.00 | 5661.82 | 4929.82 | 803.21 | 2723.28 | 0.00 | ||||||
Maximum of Months | 0.799039E+12 | 0.237312E+12 | 744.00 | 0.640424E+12 | 0.158614E+12 | 0.00 | 1.00 | 0.03 | 538210.09 | 429641.89 | 333151.21 | 175108.16 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.484166E+10 | 0.122943E+10 | 744.00 | 0.483265E+10 | 9017731.20 | 0.00 | 0.38 | 22-JAN-16:33 | 0.09 | 05-JAN-07:03 | 3076.95 | 22-JAN-16:35 | 3076.95 | 22-JAN-16:35 | 110.16 | 10-JAN-16:20 | 753.20 | 22-JAN-16:33 | 0.00 |
February | 0.898462E+10 | 0.215962E+10 | 672.00 | 0.898056E+10 | 4057431.98 | 0.00 | 0.58 | 26-FEB-16:52 | 0.32 | 06-FEB-07:03 | 5010.61 | 20-FEB-16:55 | 5010.61 | 20-FEB-16:55 | 89.02 | 28-FEB-16:50 | 1166.07 | 26-FEB-16:52 | 0.00 |
March | 0.155513E+11 | 0.358385E+10 | 744.00 | 0.155398E+11 | 11521316.62 | 0.00 | 0.85 | 31-MAR-24:00 | 0.56 | 20-MAR-06:05 | 7817.98 | 31-MAR-24:00 | 7817.98 | 31-MAR-24:00 | 155.68 | 17-MAR-15:10 | 1886.95 | 13-MAR-17:00 | 0.00 |
April | 0.201195E+11 | 0.442839E+10 | 720.00 | 0.200902E+11 | 29329039.95 | 0.00 | 1.00 | 08-APR-18:00 | 0.30 | 30-APR-24:00 | 9066.46 | 08-APR-18:00 | 9066.46 | 08-APR-18:00 | 236.41 | 28-APR-15:20 | 2144.89 | 19-APR-14:00 | 0.00 |
May | 0.602367E+10 | 0.152782E+10 | 744.00 | 0.596528E+10 | 58392185.96 | 0.00 | 0.48 | 31-MAY-24:00 | 0.20 | 03-MAY-06:05 | 4171.47 | 31-MAY-24:00 | 4150.96 | 31-MAY-24:00 | 222.32 | 22-MAY-14:05 | 956.40 | 31-MAY-24:00 | 0.00 |
June | 0.114135E+11 | 0.320272E+10 | 720.00 | 0.112951E+11 | 0.118362E+09 | 0.00 | 0.72 | 30-JUN-23:20 | 0.45 | 10-JUN-06:19 | 6130.28 | 30-JUN-24:00 | 6130.28 | 30-JUN-24:00 | 386.45 | 20-JUN-17:00 | 2182.51 | 26-JUN-15:05 | 0.00 |
July | 0.169684E+11 | 0.471137E+10 | 744.00 | 0.168135E+11 | 0.154969E+09 | 0.00 | 0.94 | 01-JUL-18:40 | 0.65 | 05-JUL-21:00 | 7935.69 | 31-JUL-24:00 | 7935.69 | 31-JUL-24:00 | 553.34 | 31-JUL-16:00 | 2803.69 | 16-JUL-13:00 | 0.00 |
August | 0.218027E+11 | 0.580702E+10 | 744.00 | 0.216721E+11 | 0.130617E+09 | 0.00 | 1.00 | 06-AUG-11:43 | 0.32 | 31-AUG-24:00 | 9391.09 | 05-AUG-18:12 | 9345.32 | 05-AUG-18:40 | 557.86 | 29-AUG-15:00 | 3274.52 | 16-AUG-16:00 | 0.00 |
September | 0.618402E+10 | 0.169221E+10 | 720.00 | 0.613856E+10 | 45459569.74 | 0.00 | 0.48 | 10-SEP-17:21 | 0.18 | 22-SEP-06:05 | 4038.52 | 30-SEP-24:00 | 4038.52 | 30-SEP-24:00 | 235.57 | 01-SEP-14:40 | 1318.17 | 10-SEP-17:21 | 0.00 |
October | 0.107297E+11 | 0.256409E+10 | 744.00 | 0.107093E+11 | 20320657.11 | 0.00 | 0.66 | 09-OCT-16:42 | 0.36 | 31-OCT-06:03 | 5711.01 | 09-OCT-16:45 | 5711.01 | 09-OCT-16:45 | 141.85 | 03-OCT-11:00 | 1491.28 | 11-OCT-14:00 | 0.00 |
November | 0.150483E+11 | 0.341068E+10 | 720.00 | 0.150336E+11 | 14718852.68 | 0.00 | 0.80 | 07-NOV-16:00 | 0.57 | 01-NOV-06:10 | 7205.06 | 05-NOV-16:13 | 7205.06 | 05-NOV-16:13 | 136.62 | 10-NOV-11:00 | 1793.09 | 07-NOV-16:00 | 0.00 |
December | 0.202053E+11 | 0.456442E+10 | 744.00 | 0.202053E+11 | -0.0 | 0.00 | 0.98 | 03-DEC-15:52 | 0.75 | 23-DEC-07:03 | 8916.10 | 03-DEC-15:55 | 8916.10 | 03-DEC-15:55 | 0.00 | 08-DEC-13:20 | 2199.62 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.157873E+12 | 0.388816E+11 | 8760.00 | 0.157276E+12 | 0.596765E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.484166E+10 | 0.122943E+10 | 672.00 | 0.483265E+10 | -0.0 | 0.00 | 0.38 | 0.09 | 3076.95 | 3076.95 | 0.00 | 753.20 | 0.00 | ||||||
Maximum of Months | 0.218027E+11 | 0.580702E+10 | 744.00 | 0.216721E+11 | 0.154969E+09 | 0.00 | 1.00 | 0.75 | 9391.09 | 9345.32 | 557.86 | 3274.52 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.310609E+11 | 0.812300E+10 | 742.08 | 0.309741E+11 | 86757205.40 | 0.00 | 0.36 | 23-JAN-16:40 | 0.00 | 03-JAN-03:45 | 28056.85 | 23-JAN-16:40 | 28056.85 | 23-JAN-16:40 | 1111.67 | 10-JAN-16:20 | 6868.52 | 23-JAN-16:40 | 0.00 |
February | 0.714440E+11 | 0.174350E+11 | 672.00 | 0.714031E+11 | 40882332.28 | 0.00 | 0.55 | 26-FEB-16:52 | 0.18 | 06-FEB-07:03 | 46570.19 | 17-FEB-17:00 | 46336.09 | 17-FEB-17:00 | 891.01 | 28-FEB-16:50 | 10649.78 | 26-FEB-16:52 | 0.00 |
March | 0.136068E+12 | 0.317049E+11 | 744.00 | 0.135953E+12 | 0.115101E+09 | 0.00 | 0.83 | 31-MAR-23:30 | 0.43 | 20-MAR-06:05 | 73281.04 | 31-MAR-23:30 | 73281.04 | 31-MAR-23:30 | 1552.41 | 17-MAR-15:10 | 17977.39 | 13-MAR-17:00 | 0.00 |
April | 0.180979E+12 | 0.401888E+11 | 720.00 | 0.180685E+12 | 0.293628E+09 | 0.00 | 0.99 | 08-APR-18:00 | 0.16 | 30-APR-24:00 | 86082.48 | 08-APR-18:00 | 86082.48 | 08-APR-18:00 | 2343.24 | 28-APR-15:20 | 20283.45 | 19-APR-14:00 | 0.00 |
May | 0.528887E+11 | 0.135298E+11 | 744.00 | 0.523142E+11 | 0.574518E+09 | 0.00 | 0.47 | 31-MAY-23:40 | 0.11 | 01-MAY-06:10 | 39544.65 | 31-MAY-23:20 | 39255.02 | 31-MAY-24:00 | 2211.74 | 22-MAY-14:05 | 9065.92 | 31-MAY-23:40 | 0.00 |
June | 0.106794E+12 | 0.300861E+11 | 720.00 | 0.105619E+12 | 0.117494E+10 | 0.00 | 0.72 | 30-JUN-23:20 | 0.42 | 10-JUN-06:20 | 58671.30 | 30-JUN-24:00 | 58671.30 | 30-JUN-24:00 | 3777.69 | 20-JUN-17:00 | 20446.52 | 26-JUN-18:00 | 0.00 |
July | 0.159074E+12 | 0.443258E+11 | 744.00 | 0.157535E+12 | 0.153947E+10 | 0.00 | 0.93 | 01-JUL-18:40 | 0.63 | 29-JUL-06:10 | 75060.12 | 31-JUL-24:00 | 75060.12 | 31-JUL-24:00 | 5449.26 | 31-JUL-16:00 | 26146.07 | 16-JUL-13:00 | 0.00 |
August | 0.206611E+12 | 0.551742E+11 | 744.00 | 0.205310E+12 | 0.130076E+10 | 0.00 | 1.00 | 10-AUG-14:40 | 0.28 | 31-AUG-24:00 | 89390.09 | 13-AUG-18:44 | 89390.09 | 13-AUG-18:44 | 5487.83 | 29-AUG-15:00 | 31451.48 | 16-AUG-16:00 | 0.00 |
September | 0.550164E+11 | 0.151974E+11 | 720.00 | 0.545708E+11 | 0.445648E+09 | 0.00 | 0.48 | 10-SEP-17:21 | 0.12 | 22-SEP-06:05 | 36700.55 | 30-SEP-23:50 | 36700.55 | 30-SEP-23:50 | 2308.73 | 01-SEP-14:40 | 12507.30 | 10-SEP-17:21 | 0.00 |
October | 0.925938E+11 | 0.223564E+11 | 744.00 | 0.923923E+11 | 0.201468E+09 | 0.00 | 0.62 | 09-OCT-17:00 | 0.24 | 30-OCT-06:03 | 51726.15 | 09-OCT-17:00 | 51726.15 | 09-OCT-17:00 | 1415.41 | 03-OCT-11:00 | 14059.76 | 11-OCT-14:00 | 0.00 |
November | 0.129933E+12 | 0.298047E+11 | 720.00 | 0.129785E+12 | 0.147787E+09 | 0.00 | 0.78 | 07-NOV-16:00 | 0.47 | 29-NOV-07:03 | 65605.21 | 07-NOV-16:20 | 65605.21 | 07-NOV-16:20 | 1350.07 | 10-NOV-11:00 | 16939.61 | 07-NOV-16:00 | 0.00 |
December | 0.172065E+12 | 0.394665E+11 | 744.00 | 0.172065E+12 | -0.0 | 0.00 | 0.93 | 03-DEC-15:52 | 0.63 | 25-DEC-07:40 | 80159.54 | 03-DEC-16:00 | 80159.54 | 03-DEC-16:00 | 0.00 | 03-DEC-07:30 | 20483.14 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.139453E+13 | 0.347393E+12 | 8758.08 | 0.138861E+13 | 0.592095E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.310609E+11 | 0.812300E+10 | 672.00 | 0.309741E+11 | -0.0 | 0.00 | 0.36 | 0.00 | 28056.85 | 28056.85 | 0.00 | 6868.52 | 0.00 | ||||||
Maximum of Months | 0.206611E+12 | 0.551742E+11 | 744.00 | 0.205310E+12 | 0.153947E+10 | 0.00 | 1.00 | 0.63 | 89390.09 | 89390.09 | 5487.83 | 31451.48 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.150387E+10 | 0.401923E+09 | 478.83 | 0.149614E+10 | 7726344.92 | 0.00 | 0.34 | 20-JAN-16:30 | 0.00 | 01-JAN-00:05 | 2764.75 | 20-JAN-16:30 | 2764.75 | 20-JAN-16:30 | 111.54 | 10-JAN-16:20 | 670.59 | 20-JAN-16:30 | 0.00 |
February | 0.552863E+10 | 0.137135E+10 | 661.76 | 0.552462E+10 | 4004108.66 | 0.00 | 0.54 | 17-FEB-17:00 | 0.00 | 05-FEB-02:45 | 4639.96 | 17-FEB-17:00 | 4619.79 | 17-FEB-17:00 | 88.43 | 28-FEB-16:50 | 1055.46 | 17-FEB-17:00 | 0.00 |
March | 0.122571E+11 | 0.289060E+10 | 744.00 | 0.122458E+11 | 11329070.48 | 0.00 | 0.80 | 12-MAR-17:22 | 0.24 | 20-MAR-03:02 | 7158.28 | 31-MAR-23:20 | 7158.28 | 31-MAR-23:20 | 155.22 | 17-MAR-15:10 | 1818.93 | 13-MAR-17:00 | 0.00 |
April | 0.167559E+11 | 0.376271E+10 | 719.50 | 0.167266E+11 | 29269070.88 | 0.00 | 0.98 | 08-APR-18:00 | 0.00 | 30-APR-23:40 | 8675.94 | 08-APR-18:00 | 8675.94 | 08-APR-18:00 | 234.72 | 28-APR-15:20 | 2056.12 | 19-APR-14:00 | 0.00 |
May | 0.485684E+10 | 0.125467E+10 | 736.27 | 0.479960E+10 | 57237830.99 | 0.00 | 0.46 | 31-MAY-23:20 | 0.00 | 01-MAY-00:10 | 3918.05 | 31-MAY-23:20 | 3878.01 | 31-MAY-23:50 | 221.21 | 22-MAY-14:00 | 925.66 | 31-MAY-16:00 | 0.00 |
June | 0.107141E+11 | 0.303189E+10 | 720.00 | 0.105965E+11 | 0.117611E+09 | 0.00 | 0.71 | 30-JUN-23:20 | 0.38 | 10-JUN-06:20 | 5876.50 | 30-JUN-24:00 | 5876.50 | 30-JUN-24:00 | 380.77 | 20-JUN-17:00 | 2116.78 | 26-JUN-15:20 | 0.00 |
July | 0.159557E+11 | 0.446342E+10 | 744.00 | 0.158018E+11 | 0.153941E+09 | 0.00 | 0.94 | 01-JUL-18:40 | 0.60 | 29-JUL-06:10 | 7428.54 | 31-JUL-24:00 | 7428.54 | 31-JUL-24:00 | 547.42 | 31-JUL-16:00 | 2715.34 | 16-JUL-15:02 | 0.00 |
August | 0.206667E+11 | 0.554273E+10 | 744.00 | 0.205367E+11 | 0.130022E+09 | 0.00 | 1.00 | 10-AUG-15:00 | 0.28 | 31-AUG-24:00 | 9103.21 | 13-AUG-18:41 | 9103.21 | 13-AUG-18:41 | 550.07 | 29-AUG-15:00 | 3208.42 | 16-AUG-16:00 | 0.00 |
September | 0.526819E+10 | 0.147122E+10 | 720.00 | 0.522366E+10 | 44529460.23 | 0.00 | 0.50 | 10-SEP-17:21 | 0.01 | 22-SEP-06:05 | 3795.97 | 10-SEP-17:33 | 3795.97 | 10-SEP-17:33 | 233.10 | 01-SEP-14:40 | 1348.01 | 10-SEP-17:21 | 0.00 |
October | 0.800922E+10 | 0.195935E+10 | 743.86 | 0.798939E+10 | 19833505.59 | 0.00 | 0.62 | 09-OCT-16:42 | 0.00 | 29-OCT-21:25 | 5179.23 | 09-OCT-16:48 | 5179.23 | 09-OCT-16:45 | 144.50 | 03-OCT-11:00 | 1427.30 | 11-OCT-14:00 | 0.00 |
November | 0.113308E+11 | 0.263946E+10 | 720.00 | 0.113162E+11 | 14581071.13 | 0.00 | 0.77 | 07-NOV-16:00 | 0.34 | 30-NOV-04:23 | 6585.69 | 07-NOV-16:20 | 6585.69 | 07-NOV-16:20 | 133.36 | 10-NOV-11:00 | 1704.75 | 07-NOV-16:00 | 0.00 |
December | 0.152173E+11 | 0.354548E+10 | 744.00 | 0.152173E+11 | 0.00 | 0.00 | 0.89 | 01-DEC-15:50 | 0.46 | 25-DEC-07:20 | 7964.65 | 01-DEC-16:00 | 7964.65 | 01-DEC-16:00 | 0.00 | 01-DEC-21:00 | 2020.80 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.128064E+12 | 0.323348E+11 | 8476.22 | 0.127474E+12 | 0.590084E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.150387E+10 | 0.401923E+09 | 478.83 | 0.149614E+10 | 0.00 | 0.00 | 0.34 | 0.00 | 2764.75 | 2764.75 | 0.00 | 670.59 | 0.00 | ||||||
Maximum of Months | 0.206667E+11 | 0.554273E+10 | 744.00 | 0.205367E+11 | 0.153941E+09 | 0.00 | 1.00 | 0.60 | 9103.21 | 9103.21 | 550.07 | 3208.42 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.26 | 736.41 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 23.94 | 737.90 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 91.81 | 568.49 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 144.98 | 500.60 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 350.69 | 277.88 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 573.75 | 154.21 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 544.09 | 150.09 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 415.07 | 167.36 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 305.93 | 259.33 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 98.92 | 549.84 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.33 | 671.48 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.07 | 833.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 218.90 | 465.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.07 | 150.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 573.75 | 833.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.26 | 736.41 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 23.94 | 737.90 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 91.81 | 568.49 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 144.98 | 500.60 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 350.69 | 277.88 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 573.75 | 154.21 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 544.09 | 150.09 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 415.07 | 167.36 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 305.93 | 259.33 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 98.92 | 549.84 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.33 | 671.48 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.07 | 833.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 218.90 | 465.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.07 | 150.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 573.75 | 833.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.26 | 736.41 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 23.94 | 737.90 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 91.81 | 568.49 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 144.98 | 500.60 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 350.69 | 277.88 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 573.75 | 154.21 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 544.09 | 150.09 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 415.07 | 167.36 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 305.93 | 259.33 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 98.92 | 549.84 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.33 | 671.48 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.07 | 833.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 218.90 | 465.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.07 | 150.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 573.75 | 833.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.26 | 736.41 | 0.00 | 0.00 | 0.00 |
February | 171.63 | 0.00 | 171.63 | 23.94 | 737.90 | 0.00 | 0.00 | 0.00 |
March | 233.53 | 0.00 | 233.53 | 91.81 | 568.49 | 0.00 | 0.00 | 0.00 |
April | 293.28 | 1.63 | 291.65 | 144.98 | 500.60 | 0.00 | 0.00 | 0.00 |
May | 400.64 | 13.24 | 387.39 | 350.69 | 277.88 | 0.00 | 0.00 | 0.00 |
June | 439.33 | 48.71 | 390.62 | 573.75 | 154.21 | 0.00 | 0.00 | 0.00 |
July | 415.48 | 26.89 | 388.59 | 544.09 | 150.09 | 0.00 | 0.00 | 0.00 |
August | 330.69 | 7.82 | 322.87 | 415.07 | 167.36 | 0.00 | 0.00 | 0.00 |
September | 277.78 | 0.07 | 277.72 | 305.93 | 259.33 | 0.00 | 0.00 | 0.00 |
October | 198.96 | 0.00 | 198.96 | 98.92 | 549.84 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.33 | 671.48 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.07 | 833.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.21 | 8.22 | 256.99 | 218.90 | 465.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.07 | 150.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.33 | 48.71 | 390.62 | 573.75 | 833.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.55 | 0.00 | 136.55 | 18.26 | 736.38 | 0.00 | 0.00 | 0.00 |
February | 171.62 | 0.00 | 171.62 | 23.94 | 737.87 | 0.00 | 0.00 | 0.00 |
March | 233.52 | 0.00 | 233.52 | 91.80 | 568.47 | 0.00 | 0.00 | 0.00 |
April | 293.27 | 1.63 | 291.64 | 144.97 | 500.58 | 0.00 | 0.00 | 0.00 |
May | 400.62 | 13.24 | 387.38 | 350.67 | 277.86 | 0.00 | 0.00 | 0.00 |
June | 439.31 | 48.70 | 390.60 | 573.73 | 154.20 | 0.00 | 0.00 | 0.00 |
July | 415.47 | 26.89 | 388.57 | 544.07 | 150.08 | 0.00 | 0.00 | 0.00 |
August | 330.68 | 7.82 | 322.86 | 415.06 | 167.35 | 0.00 | 0.00 | 0.00 |
September | 277.77 | 0.07 | 277.71 | 305.92 | 259.32 | 0.00 | 0.00 | 0.00 |
October | 198.95 | 0.00 | 198.95 | 98.92 | 549.82 | 0.00 | 0.00 | 0.00 |
November | 151.03 | 0.00 | 151.03 | 32.33 | 671.46 | 0.00 | 0.00 | 0.00 |
December | 127.76 | 0.00 | 127.76 | 14.07 | 833.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.20 | 8.22 | 256.98 | 218.90 | 465.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.76 | 0.00 | 127.76 | 14.07 | 150.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.31 | 48.70 | 390.60 | 573.73 | 833.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.09 | 291.15 | 183.94 | 406.01 | 758.61 | 0.00 | 0.00 | 0.00 |
February | 631.10 | 398.41 | 232.69 | 581.55 | 772.89 | 0.00 | 0.00 | 0.00 |
March | 761.72 | 444.31 | 317.42 | 758.89 | 593.82 | 0.00 | 0.00 | 0.00 |
April | 781.19 | 380.53 | 400.66 | 760.94 | 525.69 | 0.00 | 0.00 | 0.00 |
May | 913.20 | 381.45 | 531.75 | 1023.78 | 308.67 | 0.00 | 0.00 | 0.00 |
June | 1114.19 | 584.92 | 529.27 | 1486.34 | 171.14 | 0.00 | 0.00 | 0.00 |
July | 1012.89 | 482.31 | 530.58 | 1358.61 | 165.35 | 0.00 | 0.00 | 0.00 |
August | 1021.64 | 562.68 | 458.96 | 1367.07 | 181.82 | 0.00 | 0.00 | 0.00 |
September | 850.05 | 461.77 | 388.28 | 1075.74 | 275.07 | 0.00 | 0.00 | 0.00 |
October | 615.61 | 337.32 | 278.29 | 636.84 | 588.08 | 0.00 | 0.00 | 0.00 |
November | 479.17 | 270.55 | 208.63 | 435.43 | 701.76 | 0.00 | 0.00 | 0.00 |
December | 414.84 | 238.97 | 175.86 | 337.10 | 857.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.37 | 402.66 | 353.70 | 853.63 | 490.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.84 | 238.97 | 175.86 | 337.10 | 165.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1114.19 | 584.92 | 531.75 | 1486.34 | 857.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.09 | 291.15 | 183.94 | 406.01 | 758.61 | 0.00 | 0.00 | 0.00 |
February | 631.10 | 398.41 | 232.69 | 581.55 | 772.89 | 0.00 | 0.00 | 0.00 |
March | 761.72 | 444.31 | 317.42 | 758.89 | 593.82 | 0.00 | 0.00 | 0.00 |
April | 781.19 | 380.53 | 400.66 | 760.94 | 525.69 | 0.00 | 0.00 | 0.00 |
May | 913.20 | 381.45 | 531.75 | 1023.78 | 308.67 | 0.00 | 0.00 | 0.00 |
June | 1114.19 | 584.92 | 529.27 | 1486.34 | 171.14 | 0.00 | 0.00 | 0.00 |
July | 1012.89 | 482.31 | 530.58 | 1358.61 | 165.35 | 0.00 | 0.00 | 0.00 |
August | 1021.64 | 562.68 | 458.96 | 1367.07 | 181.82 | 0.00 | 0.00 | 0.00 |
September | 850.05 | 461.77 | 388.28 | 1075.74 | 275.07 | 0.00 | 0.00 | 0.00 |
October | 615.61 | 337.32 | 278.29 | 636.84 | 588.08 | 0.00 | 0.00 | 0.00 |
November | 479.17 | 270.55 | 208.63 | 435.43 | 701.76 | 0.00 | 0.00 | 0.00 |
December | 414.84 | 238.97 | 175.86 | 337.10 | 857.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.37 | 402.66 | 353.70 | 853.63 | 490.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.84 | 238.97 | 175.86 | 337.10 | 165.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1114.19 | 584.92 | 531.75 | 1486.34 | 857.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.08 | 291.14 | 183.94 | 406.01 | 758.60 | 0.00 | 0.00 | 0.00 |
February | 631.09 | 398.40 | 232.69 | 581.54 | 772.87 | 0.00 | 0.00 | 0.00 |
March | 761.71 | 444.30 | 317.41 | 758.87 | 593.81 | 0.00 | 0.00 | 0.00 |
April | 781.17 | 380.52 | 400.65 | 760.93 | 525.68 | 0.00 | 0.00 | 0.00 |
May | 913.18 | 381.44 | 531.74 | 1023.76 | 308.66 | 0.00 | 0.00 | 0.00 |
June | 1114.17 | 584.91 | 529.26 | 1486.32 | 171.13 | 0.00 | 0.00 | 0.00 |
July | 1012.87 | 482.30 | 530.57 | 1358.58 | 165.35 | 0.00 | 0.00 | 0.00 |
August | 1021.62 | 562.67 | 458.95 | 1367.04 | 181.82 | 0.00 | 0.00 | 0.00 |
September | 850.04 | 461.77 | 388.27 | 1075.72 | 275.06 | 0.00 | 0.00 | 0.00 |
October | 615.60 | 337.31 | 278.29 | 636.83 | 588.07 | 0.00 | 0.00 | 0.00 |
November | 479.16 | 270.54 | 208.62 | 435.42 | 701.74 | 0.00 | 0.00 | 0.00 |
December | 414.83 | 238.97 | 175.86 | 337.09 | 857.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.35 | 402.66 | 353.69 | 853.61 | 490.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.83 | 238.97 | 175.86 | 337.09 | 165.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1114.17 | 584.91 | 531.74 | 1486.32 | 857.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1482.57 | 640.73 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1412.05 | 664.73 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1052.03 | 537.26 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 616.50 | 492.68 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 619.35 | 300.23 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 721.55 | 168.65 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 749.86 | 159.63 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 966.02 | 176.33 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1168.52 | 264.00 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1242.66 | 529.05 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1457.97 | 613.07 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.32 | 1332.36 | 724.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1066.48 | 437.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.32 | 616.50 | 159.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1482.57 | 724.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1482.57 | 640.73 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1412.05 | 664.73 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1052.03 | 537.26 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 616.50 | 492.68 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 619.35 | 300.23 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 721.55 | 168.65 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 749.86 | 159.63 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 966.02 | 176.33 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1168.52 | 264.00 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1242.66 | 529.05 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1457.96 | 613.07 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.31 | 1332.36 | 724.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1066.48 | 437.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.31 | 616.50 | 159.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1482.57 | 724.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1482.57 | 640.73 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1412.05 | 664.73 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1052.03 | 537.26 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 616.50 | 492.68 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 619.35 | 300.23 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 721.55 | 168.65 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 749.86 | 159.63 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 966.02 | 176.33 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1168.52 | 264.00 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1242.66 | 529.05 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1457.97 | 613.07 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.32 | 1332.36 | 724.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1066.48 | 437.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.32 | 616.50 | 159.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1482.57 | 724.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.68 | 1076.53 | 232.15 | 1482.57 | 640.73 | 0.00 | 0.00 | 0.00 |
February | 1255.27 | 1000.78 | 254.49 | 1412.05 | 664.73 | 0.00 | 0.00 | 0.00 |
March | 925.48 | 608.91 | 316.57 | 1052.03 | 537.26 | 0.00 | 0.00 | 0.00 |
April | 599.41 | 241.03 | 358.39 | 616.50 | 492.68 | 0.00 | 0.00 | 0.00 |
May | 549.29 | 100.68 | 448.61 | 619.35 | 300.23 | 0.00 | 0.00 | 0.00 |
June | 506.43 | 92.56 | 413.87 | 721.55 | 168.65 | 0.00 | 0.00 | 0.00 |
July | 527.18 | 94.40 | 432.78 | 749.86 | 159.63 | 0.00 | 0.00 | 0.00 |
August | 671.21 | 280.59 | 390.62 | 966.02 | 176.33 | 0.00 | 0.00 | 0.00 |
September | 863.58 | 481.87 | 381.71 | 1168.52 | 264.00 | 0.00 | 0.00 | 0.00 |
October | 1032.59 | 732.64 | 299.94 | 1242.66 | 529.05 | 0.00 | 0.00 | 0.00 |
November | 1258.06 | 1002.86 | 255.20 | 1457.96 | 613.07 | 0.00 | 0.00 | 0.00 |
December | 1203.04 | 973.72 | 229.31 | 1332.36 | 724.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.63 | 554.69 | 334.93 | 1066.48 | 437.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.43 | 92.56 | 229.31 | 616.50 | 159.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.68 | 1076.53 | 448.61 | 1482.57 | 724.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1308.63 | 1076.49 | 232.14 | 1482.51 | 640.70 | 0.00 | 0.00 | 0.00 |
February | 1255.22 | 1000.74 | 254.48 | 1412.00 | 664.71 | 0.00 | 0.00 | 0.00 |
March | 925.44 | 608.89 | 316.55 | 1051.99 | 537.24 | 0.00 | 0.00 | 0.00 |
April | 599.39 | 241.02 | 358.37 | 616.47 | 492.66 | 0.00 | 0.00 | 0.00 |
May | 549.27 | 100.68 | 448.59 | 619.33 | 300.21 | 0.00 | 0.00 | 0.00 |
June | 506.41 | 92.56 | 413.85 | 721.52 | 168.65 | 0.00 | 0.00 | 0.00 |
July | 527.16 | 94.40 | 432.76 | 749.83 | 159.62 | 0.00 | 0.00 | 0.00 |
August | 671.18 | 280.58 | 390.60 | 965.98 | 176.32 | 0.00 | 0.00 | 0.00 |
September | 863.54 | 481.85 | 381.69 | 1168.48 | 263.99 | 0.00 | 0.00 | 0.00 |
October | 1032.55 | 732.61 | 299.93 | 1242.61 | 529.03 | 0.00 | 0.00 | 0.00 |
November | 1258.01 | 1002.82 | 255.19 | 1457.91 | 613.05 | 0.00 | 0.00 | 0.00 |
December | 1202.99 | 973.68 | 229.31 | 1332.31 | 724.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.59 | 554.67 | 334.92 | 1066.43 | 437.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 506.41 | 92.56 | 229.31 | 616.47 | 159.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1308.63 | 1076.49 | 448.59 | 1482.51 | 724.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.39 | 320.24 | 185.15 | 462.03 | 812.82 | 0.00 | 0.00 | 0.00 |
February | 609.43 | 377.66 | 231.76 | 554.72 | 839.59 | 0.00 | 0.00 | 0.00 |
March | 713.60 | 393.71 | 319.89 | 689.13 | 669.46 | 0.00 | 0.00 | 0.00 |
April | 671.88 | 284.46 | 387.42 | 612.49 | 612.19 | 0.00 | 0.00 | 0.00 |
May | 821.22 | 289.51 | 531.71 | 910.33 | 350.38 | 0.00 | 0.00 | 0.00 |
June | 1004.40 | 483.25 | 521.14 | 1344.57 | 211.27 | 0.00 | 0.00 | 0.00 |
July | 818.35 | 299.74 | 518.60 | 1089.76 | 200.20 | 0.00 | 0.00 | 0.00 |
August | 854.12 | 421.95 | 432.17 | 1121.65 | 226.73 | 0.00 | 0.00 | 0.00 |
September | 757.35 | 363.20 | 394.15 | 956.86 | 313.12 | 0.00 | 0.00 | 0.00 |
October | 637.13 | 364.17 | 272.96 | 670.74 | 645.38 | 0.00 | 0.00 | 0.00 |
November | 522.80 | 317.40 | 205.40 | 487.17 | 778.48 | 0.00 | 0.00 | 0.00 |
December | 422.28 | 249.45 | 172.83 | 342.84 | 952.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.04 | 346.65 | 348.40 | 771.08 | 549.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 422.28 | 249.45 | 172.83 | 342.84 | 200.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1004.40 | 483.25 | 531.71 | 1344.57 | 952.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.39 | 320.24 | 185.15 | 462.03 | 812.82 | 0.00 | 0.00 | 0.00 |
February | 609.43 | 377.66 | 231.76 | 554.72 | 839.59 | 0.00 | 0.00 | 0.00 |
March | 713.60 | 393.71 | 319.89 | 689.13 | 669.46 | 0.00 | 0.00 | 0.00 |
April | 671.88 | 284.46 | 387.42 | 612.49 | 612.19 | 0.00 | 0.00 | 0.00 |
May | 821.22 | 289.51 | 531.71 | 910.33 | 350.38 | 0.00 | 0.00 | 0.00 |
June | 1004.40 | 483.25 | 521.14 | 1344.57 | 211.27 | 0.00 | 0.00 | 0.00 |
July | 818.35 | 299.74 | 518.60 | 1089.76 | 200.20 | 0.00 | 0.00 | 0.00 |
August | 854.12 | 421.95 | 432.17 | 1121.65 | 226.73 | 0.00 | 0.00 | 0.00 |
September | 757.35 | 363.20 | 394.15 | 956.86 | 313.12 | 0.00 | 0.00 | 0.00 |
October | 637.13 | 364.17 | 272.96 | 670.74 | 645.38 | 0.00 | 0.00 | 0.00 |
November | 522.80 | 317.40 | 205.40 | 487.17 | 778.48 | 0.00 | 0.00 | 0.00 |
December | 422.28 | 249.45 | 172.83 | 342.84 | 952.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.04 | 346.65 | 348.40 | 771.08 | 549.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 422.28 | 249.45 | 172.83 | 342.84 | 200.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1004.40 | 483.25 | 531.71 | 1344.57 | 952.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.38 | 320.23 | 185.14 | 462.02 | 812.81 | 0.00 | 0.00 | 0.00 |
February | 609.41 | 377.66 | 231.76 | 554.71 | 839.58 | 0.00 | 0.00 | 0.00 |
March | 713.58 | 393.70 | 319.88 | 689.12 | 669.45 | 0.00 | 0.00 | 0.00 |
April | 671.87 | 284.46 | 387.41 | 612.48 | 612.18 | 0.00 | 0.00 | 0.00 |
May | 821.20 | 289.50 | 531.70 | 910.31 | 350.37 | 0.00 | 0.00 | 0.00 |
June | 1004.38 | 483.25 | 521.13 | 1344.54 | 211.27 | 0.00 | 0.00 | 0.00 |
July | 818.33 | 299.74 | 518.59 | 1089.75 | 200.20 | 0.00 | 0.00 | 0.00 |
August | 854.10 | 421.94 | 432.16 | 1121.63 | 226.72 | 0.00 | 0.00 | 0.00 |
September | 757.34 | 363.19 | 394.14 | 956.84 | 313.12 | 0.00 | 0.00 | 0.00 |
October | 637.12 | 364.16 | 272.96 | 670.72 | 645.36 | 0.00 | 0.00 | 0.00 |
November | 522.79 | 317.40 | 205.39 | 487.16 | 778.46 | 0.00 | 0.00 | 0.00 |
December | 422.27 | 249.45 | 172.82 | 342.83 | 952.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 695.03 | 346.64 | 348.39 | 771.07 | 549.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 422.27 | 249.45 | 172.82 | 342.83 | 200.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1004.38 | 483.25 | 531.70 | 1344.54 | 952.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 682.75 | 0.00 | 682.75 | 122.86 | 3361.35 | 0.00 | 0.00 | 0.00 |
February | 858.13 | 0.00 | 858.13 | 159.97 | 3383.18 | 0.00 | 0.00 | 0.00 |
March | 1167.63 | 0.00 | 1167.63 | 518.79 | 2589.11 | 0.00 | 0.00 | 0.00 |
April | 1466.38 | 8.13 | 1458.24 | 782.20 | 2251.06 | 0.00 | 0.00 | 0.00 |
May | 2003.16 | 66.22 | 1936.94 | 1778.19 | 1332.00 | 0.00 | 0.00 | 0.00 |
June | 2196.60 | 243.53 | 1953.07 | 2901.71 | 731.93 | 0.00 | 0.00 | 0.00 |
July | 2077.39 | 134.47 | 1942.92 | 2776.49 | 692.87 | 0.00 | 0.00 | 0.00 |
August | 1653.44 | 39.11 | 1614.33 | 2113.73 | 790.94 | 0.00 | 0.00 | 0.00 |
September | 1388.89 | 0.33 | 1388.57 | 1563.65 | 1221.74 | 0.00 | 0.00 | 0.00 |
October | 994.78 | 0.00 | 994.78 | 539.92 | 2543.80 | 0.00 | 0.00 | 0.00 |
November | 755.17 | 0.00 | 755.17 | 208.22 | 3034.81 | 0.00 | 0.00 | 0.00 |
December | 638.79 | 0.00 | 638.79 | 108.99 | 3746.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1326.01 | 41.08 | 1284.94 | 1136.66 | 2133.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 638.79 | 0.00 | 638.79 | 108.99 | 692.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2196.60 | 243.53 | 1953.07 | 2901.71 | 3746.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1425.25 | 873.44 | 551.81 | 1236.38 | 2145.73 | 0.00 | 0.00 | 0.00 |
February | 1893.28 | 1195.22 | 698.06 | 1745.51 | 2201.44 | 0.00 | 0.00 | 0.00 |
March | 2285.14 | 1332.90 | 952.24 | 2271.80 | 1687.75 | 0.00 | 0.00 | 0.00 |
April | 2343.54 | 1141.58 | 1201.96 | 2277.80 | 1482.20 | 0.00 | 0.00 | 0.00 |
May | 2739.56 | 1144.32 | 1595.23 | 3050.37 | 908.13 | 0.00 | 0.00 | 0.00 |
June | 3342.54 | 1754.75 | 1587.80 | 4441.61 | 498.54 | 0.00 | 0.00 | 0.00 |
July | 3038.64 | 1446.92 | 1591.71 | 4070.61 | 473.82 | 0.00 | 0.00 | 0.00 |
August | 3064.88 | 1688.03 | 1376.85 | 4081.89 | 541.64 | 0.00 | 0.00 | 0.00 |
September | 2550.14 | 1385.31 | 1164.83 | 3212.91 | 799.67 | 0.00 | 0.00 | 0.00 |
October | 1846.81 | 1011.94 | 834.86 | 1904.20 | 1686.34 | 0.00 | 0.00 | 0.00 |
November | 1437.50 | 811.63 | 625.87 | 1318.05 | 1989.07 | 0.00 | 0.00 | 0.00 |
December | 1244.49 | 716.92 | 527.58 | 1032.76 | 2401.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.07 | 1207.98 | 1061.09 | 2557.46 | 1397.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1244.49 | 716.92 | 527.58 | 1032.76 | 473.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3342.54 | 1754.75 | 1595.23 | 4441.61 | 2401.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6543.34 | 5382.60 | 1160.74 | 7362.93 | 3182.85 | 0.00 | 0.00 | 0.00 |
February | 6276.27 | 5003.84 | 1272.43 | 6998.58 | 3275.59 | 0.00 | 0.00 | 0.00 |
March | 4627.35 | 3044.54 | 1582.82 | 5229.61 | 2605.81 | 0.00 | 0.00 | 0.00 |
April | 2997.02 | 1205.11 | 1791.90 | 3080.57 | 2349.45 | 0.00 | 0.00 | 0.00 |
May | 2746.44 | 503.40 | 2243.03 | 3087.68 | 1474.71 | 0.00 | 0.00 | 0.00 |
June | 2532.12 | 462.80 | 2069.32 | 3621.27 | 806.68 | 0.00 | 0.00 | 0.00 |
July | 2635.88 | 472.01 | 2163.87 | 3777.14 | 750.56 | 0.00 | 0.00 | 0.00 |
August | 3356.01 | 1402.94 | 1953.07 | 4830.18 | 854.44 | 0.00 | 0.00 | 0.00 |
September | 4317.84 | 2409.33 | 1908.51 | 5815.76 | 1293.35 | 0.00 | 0.00 | 0.00 |
October | 5162.87 | 3663.18 | 1499.70 | 6173.92 | 2602.63 | 0.00 | 0.00 | 0.00 |
November | 6290.24 | 5014.23 | 1276.01 | 7242.70 | 3014.05 | 0.00 | 0.00 | 0.00 |
December | 6015.11 | 4868.55 | 1146.56 | 6633.30 | 3520.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4448.08 | 2773.44 | 1674.64 | 5311.53 | 2137.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2532.12 | 462.80 | 1146.56 | 3080.57 | 750.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6543.34 | 5382.60 | 2243.03 | 7362.93 | 3520.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1516.15 | 960.71 | 555.43 | 1416.96 | 2235.10 | 0.00 | 0.00 | 0.00 |
February | 1828.26 | 1132.98 | 695.28 | 1698.68 | 2273.03 | 0.00 | 0.00 | 0.00 |
March | 2140.77 | 1181.11 | 959.66 | 2110.62 | 1767.96 | 0.00 | 0.00 | 0.00 |
April | 2015.63 | 853.39 | 1162.25 | 1889.78 | 1563.52 | 0.00 | 0.00 | 0.00 |
May | 2463.62 | 868.52 | 1595.10 | 2746.24 | 990.18 | 0.00 | 0.00 | 0.00 |
June | 3013.16 | 1449.75 | 1563.41 | 4055.89 | 583.38 | 0.00 | 0.00 | 0.00 |
July | 2455.01 | 899.23 | 1555.79 | 3309.39 | 535.57 | 0.00 | 0.00 | 0.00 |
August | 2562.34 | 1265.83 | 1296.51 | 3407.97 | 600.47 | 0.00 | 0.00 | 0.00 |
September | 2272.02 | 1089.59 | 1182.44 | 2886.04 | 879.86 | 0.00 | 0.00 | 0.00 |
October | 1911.37 | 1092.49 | 818.88 | 2040.02 | 1754.64 | 0.00 | 0.00 | 0.00 |
November | 1568.38 | 952.20 | 616.18 | 1507.80 | 2057.63 | 0.00 | 0.00 | 0.00 |
December | 1266.83 | 748.35 | 518.48 | 1080.29 | 2462.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2085.11 | 1039.93 | 1045.18 | 2348.51 | 1471.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1266.83 | 748.35 | 518.48 | 1080.29 | 535.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3013.16 | 1449.75 | 1595.10 | 4055.89 | 2462.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 682.75 | 0.00 | 682.75 | 152.92 | 3111.98 | 0.00 | 0.00 | 0.00 |
February | 858.13 | 0.00 | 858.13 | 185.84 | 3188.80 | 0.00 | 0.00 | 0.00 |
March | 1167.63 | 0.00 | 1167.63 | 549.97 | 2431.29 | 0.00 | 0.00 | 0.00 |
April | 1466.38 | 8.13 | 1458.24 | 818.70 | 2067.53 | 0.00 | 0.00 | 0.00 |
May | 2003.16 | 66.22 | 1936.94 | 1804.26 | 1279.62 | 0.00 | 0.00 | 0.00 |
June | 2196.60 | 243.53 | 1953.07 | 2883.23 | 728.75 | 0.00 | 0.00 | 0.00 |
July | 2077.39 | 134.47 | 1942.92 | 2757.59 | 692.44 | 0.00 | 0.00 | 0.00 |
August | 1653.44 | 39.11 | 1614.33 | 2101.34 | 782.31 | 0.00 | 0.00 | 0.00 |
September | 1388.89 | 0.33 | 1388.57 | 1567.98 | 1182.52 | 0.00 | 0.00 | 0.00 |
October | 994.78 | 0.00 | 994.78 | 573.76 | 2373.24 | 0.00 | 0.00 | 0.00 |
November | 755.17 | 0.00 | 755.17 | 243.60 | 2815.50 | 0.00 | 0.00 | 0.00 |
December | 638.79 | 0.00 | 638.79 | 128.18 | 3536.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1326.01 | 41.08 | 1284.94 | 1152.65 | 2009.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 638.79 | 0.00 | 638.79 | 128.18 | 692.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2196.60 | 243.53 | 1953.07 | 2883.23 | 3536.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1425.25 | 873.44 | 551.81 | 1279.04 | 1978.66 | 0.00 | 0.00 | 0.00 |
February | 1893.28 | 1195.22 | 698.06 | 1772.41 | 2075.89 | 0.00 | 0.00 | 0.00 |
March | 2285.14 | 1332.90 | 952.24 | 2295.00 | 1592.42 | 0.00 | 0.00 | 0.00 |
April | 2343.54 | 1141.58 | 1201.96 | 2301.84 | 1367.28 | 0.00 | 0.00 | 0.00 |
May | 2739.56 | 1144.32 | 1595.23 | 3064.29 | 877.78 | 0.00 | 0.00 | 0.00 |
June | 3342.54 | 1754.75 | 1587.80 | 4432.12 | 496.70 | 0.00 | 0.00 | 0.00 |
July | 3038.64 | 1446.92 | 1591.71 | 4061.21 | 473.10 | 0.00 | 0.00 | 0.00 |
August | 3064.88 | 1688.03 | 1376.85 | 4075.74 | 536.47 | 0.00 | 0.00 | 0.00 |
September | 2550.14 | 1385.31 | 1164.83 | 3215.88 | 779.06 | 0.00 | 0.00 | 0.00 |
October | 1846.81 | 1011.94 | 834.86 | 1923.66 | 1585.61 | 0.00 | 0.00 | 0.00 |
November | 1437.50 | 811.63 | 625.87 | 1354.23 | 1846.17 | 0.00 | 0.00 | 0.00 |
December | 1244.49 | 716.92 | 527.58 | 1064.46 | 2262.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.07 | 1207.98 | 1061.09 | 2573.74 | 1318.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1244.49 | 716.92 | 527.58 | 1064.46 | 473.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3342.54 | 1754.75 | 1595.23 | 4432.12 | 2262.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6543.34 | 5382.60 | 1160.74 | 7432.67 | 2963.46 | 0.00 | 0.00 | 0.00 |
February | 6276.27 | 5003.84 | 1272.43 | 7039.14 | 3095.99 | 0.00 | 0.00 | 0.00 |
March | 4627.35 | 3044.54 | 1582.82 | 5255.65 | 2459.98 | 0.00 | 0.00 | 0.00 |
April | 2997.02 | 1205.11 | 1791.90 | 3107.94 | 2167.98 | 0.00 | 0.00 | 0.00 |
May | 2746.44 | 503.40 | 2243.03 | 3101.22 | 1417.88 | 0.00 | 0.00 | 0.00 |
June | 2532.12 | 462.80 | 2069.32 | 3601.57 | 801.74 | 0.00 | 0.00 | 0.00 |
July | 2635.88 | 472.01 | 2163.87 | 3757.09 | 748.66 | 0.00 | 0.00 | 0.00 |
August | 3356.01 | 1402.94 | 1953.07 | 4812.90 | 845.85 | 0.00 | 0.00 | 0.00 |
September | 4317.84 | 2409.33 | 1908.51 | 5809.93 | 1259.75 | 0.00 | 0.00 | 0.00 |
October | 5162.87 | 3663.18 | 1499.70 | 6198.23 | 2453.96 | 0.00 | 0.00 | 0.00 |
November | 6290.24 | 5014.23 | 1276.01 | 7288.53 | 2831.59 | 0.00 | 0.00 | 0.00 |
December | 6015.11 | 4868.55 | 1146.56 | 6683.47 | 3317.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4448.08 | 2773.44 | 1674.64 | 5331.00 | 2024.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2532.12 | 462.80 | 1146.56 | 3101.22 | 748.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6543.34 | 5382.60 | 2243.03 | 7432.67 | 3317.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1516.15 | 960.71 | 555.43 | 1444.39 | 2085.07 | 0.00 | 0.00 | 0.00 |
February | 1828.26 | 1132.98 | 695.28 | 1715.01 | 2157.11 | 0.00 | 0.00 | 0.00 |
March | 2140.77 | 1181.11 | 959.66 | 2124.58 | 1674.19 | 0.00 | 0.00 | 0.00 |
April | 2015.63 | 853.39 | 1162.25 | 1905.98 | 1454.59 | 0.00 | 0.00 | 0.00 |
May | 2463.62 | 868.52 | 1595.10 | 2751.15 | 957.08 | 0.00 | 0.00 | 0.00 |
June | 3013.16 | 1449.75 | 1563.41 | 4040.30 | 579.12 | 0.00 | 0.00 | 0.00 |
July | 2455.01 | 899.23 | 1555.79 | 3295.03 | 532.80 | 0.00 | 0.00 | 0.00 |
August | 2562.34 | 1265.83 | 1296.51 | 3395.90 | 594.14 | 0.00 | 0.00 | 0.00 |
September | 2272.02 | 1089.59 | 1182.44 | 2883.16 | 857.05 | 0.00 | 0.00 | 0.00 |
October | 1911.37 | 1092.49 | 818.88 | 2054.65 | 1659.89 | 0.00 | 0.00 | 0.00 |
November | 1568.38 | 952.20 | 616.18 | 1529.82 | 1936.28 | 0.00 | 0.00 | 0.00 |
December | 1266.83 | 748.35 | 518.48 | 1097.81 | 2336.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2085.11 | 1039.93 | 1045.18 | 2355.80 | 1397.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1266.83 | 748.35 | 518.48 | 1097.81 | 532.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3013.16 | 1449.75 | 1595.10 | 4040.30 | 2336.71 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 48914854.67 | 0.197240E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 57908135.59 | 0.178512E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.245891E+09 | 0.152265E+10 |
April | 0.760179E+09 | 4217145.19 | 0.755962E+09 | 0.375782E+09 | 0.129754E+10 |
May | 0.107307E+10 | 35471222.39 | 0.103759E+10 | 0.939277E+09 | 0.744261E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101249E+10 | 0.148716E+10 | 0.399711E+09 |
July | 0.111283E+10 | 72035381.25 | 0.104079E+10 | 0.145728E+10 | 0.401991E+09 |
August | 0.885727E+09 | 20953327.99 | 0.864774E+09 | 0.111174E+10 | 0.448248E+09 |
September | 0.720011E+09 | 169117.77 | 0.719842E+09 | 0.792981E+09 | 0.672179E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.264946E+09 | 0.147268E+10 |
November | 0.391483E+09 | 0.00 | 0.391483E+09 | 83797912.19 | 0.174048E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678957.82 | 0.223320E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.690335E+10 | 0.146905E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678957.82 | 0.399711E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.148716E+10 | 0.223320E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 48914753.07 | 0.197240E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 57908033.39 | 0.178512E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.245891E+09 | 0.152265E+10 |
April | 0.760178E+09 | 4217140.13 | 0.755961E+09 | 0.375781E+09 | 0.129754E+10 |
May | 0.107306E+10 | 35471179.83 | 0.103759E+10 | 0.939276E+09 | 0.744261E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101248E+10 | 0.148716E+10 | 0.399711E+09 |
July | 0.111283E+10 | 72035294.82 | 0.104079E+10 | 0.145728E+10 | 0.401991E+09 |
August | 0.885727E+09 | 20953302.84 | 0.864773E+09 | 0.111174E+10 | 0.448248E+09 |
September | 0.720010E+09 | 169117.57 | 0.719841E+09 | 0.792980E+09 | 0.672179E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.264945E+09 | 0.147268E+10 |
November | 0.391482E+09 | 0.00 | 0.391482E+09 | 83797793.31 | 0.174048E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678898.34 | 0.223320E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.690335E+10 | 0.146905E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678898.34 | 0.399711E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.148716E+10 | 0.223320E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 48914854.67 | 0.197240E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 57908135.59 | 0.178512E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.245891E+09 | 0.152265E+10 |
April | 0.760179E+09 | 4217145.19 | 0.755962E+09 | 0.375782E+09 | 0.129754E+10 |
May | 0.107307E+10 | 35471222.39 | 0.103759E+10 | 0.939277E+09 | 0.744261E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101249E+10 | 0.148716E+10 | 0.399711E+09 |
July | 0.111283E+10 | 72035381.25 | 0.104079E+10 | 0.145728E+10 | 0.401991E+09 |
August | 0.885727E+09 | 20953327.99 | 0.864774E+09 | 0.111174E+10 | 0.448248E+09 |
September | 0.720011E+09 | 169117.77 | 0.719842E+09 | 0.792981E+09 | 0.672179E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.264946E+09 | 0.147268E+10 |
November | 0.391483E+09 | 0.00 | 0.391483E+09 | 83797912.19 | 0.174048E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678957.82 | 0.223320E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.690335E+10 | 0.146905E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678957.82 | 0.399711E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.148716E+10 | 0.223320E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365737E+09 | 0.00 | 0.365737E+09 | 48914753.07 | 0.197240E+10 |
February | 0.415202E+09 | 0.00 | 0.415202E+09 | 57908033.39 | 0.178512E+10 |
March | 0.625484E+09 | 0.00 | 0.625484E+09 | 0.245891E+09 | 0.152265E+10 |
April | 0.760178E+09 | 4217140.13 | 0.755961E+09 | 0.375781E+09 | 0.129754E+10 |
May | 0.107306E+10 | 35471179.83 | 0.103759E+10 | 0.939276E+09 | 0.744261E+09 |
June | 0.113873E+10 | 0.126247E+09 | 0.101248E+10 | 0.148716E+10 | 0.399711E+09 |
July | 0.111283E+10 | 72035294.82 | 0.104079E+10 | 0.145728E+10 | 0.401991E+09 |
August | 0.885727E+09 | 20953302.84 | 0.864773E+09 | 0.111174E+10 | 0.448248E+09 |
September | 0.720010E+09 | 169117.57 | 0.719841E+09 | 0.792980E+09 | 0.672179E+09 |
October | 0.532891E+09 | 0.00 | 0.532891E+09 | 0.264945E+09 | 0.147268E+10 |
November | 0.391482E+09 | 0.00 | 0.391482E+09 | 83797793.31 | 0.174048E+10 |
December | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678898.34 | 0.223320E+10 |
Annual Sum or Average | 0.836353E+10 | 0.259093E+09 | 0.810444E+10 | 0.690335E+10 | 0.146905E+11 |
Minimum of Months | 0.342193E+09 | 0.00 | 0.342193E+09 | 37678898.34 | 0.399711E+09 |
Maximum of Months | 0.113873E+10 | 0.126247E+09 | 0.104079E+10 | 0.148716E+10 | 0.223320E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365723E+09 | 0.00 | 0.365723E+09 | 48912883.19 | 0.197232E+10 |
February | 0.415185E+09 | 0.00 | 0.415185E+09 | 57905801.64 | 0.178505E+10 |
March | 0.625459E+09 | 0.00 | 0.625459E+09 | 0.245881E+09 | 0.152259E+10 |
April | 0.760148E+09 | 4216975.22 | 0.755931E+09 | 0.375766E+09 | 0.129749E+10 |
May | 0.107302E+10 | 35469792.75 | 0.103755E+10 | 0.939239E+09 | 0.744231E+09 |
June | 0.113869E+10 | 0.126242E+09 | 0.101244E+10 | 0.148710E+10 | 0.399695E+09 |
July | 0.111278E+10 | 72032477.91 | 0.104075E+10 | 0.145723E+10 | 0.401975E+09 |
August | 0.885692E+09 | 20952483.47 | 0.864739E+09 | 0.111169E+10 | 0.448230E+09 |
September | 0.719982E+09 | 169110.95 | 0.719813E+09 | 0.792949E+09 | 0.672152E+09 |
October | 0.532870E+09 | 0.00 | 0.532870E+09 | 0.264935E+09 | 0.147262E+10 |
November | 0.391467E+09 | 0.00 | 0.391467E+09 | 83794534.76 | 0.174041E+10 |
December | 0.342179E+09 | 0.00 | 0.342179E+09 | 37677439.19 | 0.223311E+10 |
Annual Sum or Average | 0.836320E+10 | 0.259083E+09 | 0.810411E+10 | 0.690308E+10 | 0.146899E+11 |
Minimum of Months | 0.342179E+09 | 0.00 | 0.342179E+09 | 37677439.19 | 0.399695E+09 |
Maximum of Months | 0.113869E+10 | 0.126242E+09 | 0.104075E+10 | 0.148710E+10 | 0.223311E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127247E+10 | 0.779811E+09 | 0.492664E+09 | 0.108747E+10 | 0.203186E+10 |
February | 0.152676E+10 | 0.963838E+09 | 0.562922E+09 | 0.140690E+10 | 0.186977E+10 |
March | 0.204020E+10 | 0.119003E+10 | 0.850167E+09 | 0.203260E+10 | 0.159049E+10 |
April | 0.202484E+10 | 0.986334E+09 | 0.103850E+10 | 0.197236E+10 | 0.136259E+10 |
May | 0.244590E+10 | 0.102166E+10 | 0.142424E+10 | 0.274209E+10 | 0.826741E+09 |
June | 0.288799E+10 | 0.151612E+10 | 0.137187E+10 | 0.385261E+10 | 0.443586E+09 |
July | 0.271292E+10 | 0.129183E+10 | 0.142110E+10 | 0.363889E+10 | 0.442881E+09 |
August | 0.273635E+10 | 0.150709E+10 | 0.122927E+10 | 0.366156E+10 | 0.486993E+09 |
September | 0.220334E+10 | 0.119692E+10 | 0.100642E+10 | 0.278831E+10 | 0.712978E+09 |
October | 0.164885E+10 | 0.903473E+09 | 0.745374E+09 | 0.170572E+10 | 0.157511E+10 |
November | 0.124202E+10 | 0.701254E+09 | 0.540761E+09 | 0.112864E+10 | 0.181895E+10 |
December | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.902884E+09 | 0.229578E+10 |
Annual Sum or Average | 0.238527E+11 | 0.126984E+11 | 0.111543E+11 | 0.269200E+11 | 0.154577E+11 |
Minimum of Months | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.902884E+09 | 0.442881E+09 |
Maximum of Months | 0.288799E+10 | 0.151612E+10 | 0.142424E+10 | 0.385261E+10 | 0.229578E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127247E+10 | 0.779811E+09 | 0.492664E+09 | 0.108747E+10 | 0.203186E+10 |
February | 0.152676E+10 | 0.963838E+09 | 0.562922E+09 | 0.140690E+10 | 0.186977E+10 |
March | 0.204020E+10 | 0.119003E+10 | 0.850167E+09 | 0.203260E+10 | 0.159049E+10 |
April | 0.202484E+10 | 0.986334E+09 | 0.103850E+10 | 0.197236E+10 | 0.136259E+10 |
May | 0.244590E+10 | 0.102166E+10 | 0.142424E+10 | 0.274209E+10 | 0.826741E+09 |
June | 0.288799E+10 | 0.151612E+10 | 0.137187E+10 | 0.385261E+10 | 0.443586E+09 |
July | 0.271292E+10 | 0.129183E+10 | 0.142110E+10 | 0.363889E+10 | 0.442881E+09 |
August | 0.273635E+10 | 0.150709E+10 | 0.122927E+10 | 0.366156E+10 | 0.486993E+09 |
September | 0.220334E+10 | 0.119692E+10 | 0.100642E+10 | 0.278831E+10 | 0.712978E+09 |
October | 0.164885E+10 | 0.903473E+09 | 0.745374E+09 | 0.170572E+10 | 0.157511E+10 |
November | 0.124202E+10 | 0.701254E+09 | 0.540761E+09 | 0.112864E+10 | 0.181895E+10 |
December | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.902884E+09 | 0.229578E+10 |
Annual Sum or Average | 0.238527E+11 | 0.126984E+11 | 0.111543E+11 | 0.269200E+11 | 0.154577E+11 |
Minimum of Months | 0.111110E+10 | 0.640070E+09 | 0.471025E+09 | 0.902884E+09 | 0.442881E+09 |
Maximum of Months | 0.288799E+10 | 0.151612E+10 | 0.142424E+10 | 0.385261E+10 | 0.229578E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127245E+10 | 0.779797E+09 | 0.492655E+09 | 0.108745E+10 | 0.203182E+10 |
February | 0.152673E+10 | 0.963820E+09 | 0.562912E+09 | 0.140687E+10 | 0.186973E+10 |
March | 0.204016E+10 | 0.119001E+10 | 0.850152E+09 | 0.203256E+10 | 0.159046E+10 |
April | 0.202480E+10 | 0.986315E+09 | 0.103848E+10 | 0.197232E+10 | 0.136256E+10 |
May | 0.244586E+10 | 0.102164E+10 | 0.142421E+10 | 0.274204E+10 | 0.826726E+09 |
June | 0.288793E+10 | 0.151609E+10 | 0.137184E+10 | 0.385254E+10 | 0.443577E+09 |
July | 0.271287E+10 | 0.129180E+10 | 0.142107E+10 | 0.363882E+10 | 0.442873E+09 |
August | 0.273630E+10 | 0.150706E+10 | 0.122925E+10 | 0.366149E+10 | 0.486984E+09 |
September | 0.220330E+10 | 0.119690E+10 | 0.100641E+10 | 0.278826E+10 | 0.712965E+09 |
October | 0.164882E+10 | 0.903456E+09 | 0.745361E+09 | 0.170569E+10 | 0.157509E+10 |
November | 0.124199E+10 | 0.701242E+09 | 0.540751E+09 | 0.112862E+10 | 0.181892E+10 |
December | 0.111108E+10 | 0.640058E+09 | 0.471017E+09 | 0.902867E+09 | 0.229574E+10 |
Annual Sum or Average | 0.238523E+11 | 0.126982E+11 | 0.111541E+11 | 0.269195E+11 | 0.154574E+11 |
Minimum of Months | 0.111108E+10 | 0.640058E+09 | 0.471017E+09 | 0.902867E+09 | 0.442873E+09 |
Maximum of Months | 0.288793E+10 | 0.151609E+10 | 0.142421E+10 | 0.385254E+10 | 0.229574E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350518E+10 | 0.288339E+10 | 0.621791E+09 | 0.397092E+10 | 0.171613E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615661E+09 | 0.341604E+10 | 0.160812E+10 |
March | 0.247881E+10 | 0.163092E+10 | 0.847893E+09 | 0.281776E+10 | 0.143899E+10 |
April | 0.155367E+10 | 0.624738E+09 | 0.928935E+09 | 0.159796E+10 | 0.127703E+10 |
May | 0.147123E+10 | 0.269666E+09 | 0.120156E+10 | 0.165888E+10 | 0.804128E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187026E+10 | 0.437152E+09 |
July | 0.141201E+10 | 0.252851E+09 | 0.115915E+10 | 0.200842E+10 | 0.427543E+09 |
August | 0.179777E+10 | 0.751536E+09 | 0.104623E+10 | 0.258740E+10 | 0.472278E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989383E+09 | 0.302881E+10 | 0.684278E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.332834E+10 | 0.141702E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661490E+09 | 0.377905E+10 | 0.158908E+10 |
December | 0.322221E+10 | 0.260802E+10 | 0.614198E+09 | 0.356859E+10 | 0.194051E+10 |
Annual Sum or Average | 0.280553E+11 | 0.174929E+11 | 0.105624E+11 | 0.336324E+11 | 0.138123E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614198E+09 | 0.159796E+10 | 0.427543E+09 |
Maximum of Months | 0.350518E+10 | 0.288339E+10 | 0.120156E+10 | 0.397092E+10 | 0.194051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350517E+10 | 0.288338E+10 | 0.621791E+09 | 0.397092E+10 | 0.171613E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615660E+09 | 0.341603E+10 | 0.160812E+10 |
March | 0.247881E+10 | 0.163091E+10 | 0.847893E+09 | 0.281776E+10 | 0.143899E+10 |
April | 0.155367E+10 | 0.624737E+09 | 0.928934E+09 | 0.159796E+10 | 0.127703E+10 |
May | 0.147123E+10 | 0.269665E+09 | 0.120156E+10 | 0.165888E+10 | 0.804128E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187025E+10 | 0.437152E+09 |
July | 0.141200E+10 | 0.252851E+09 | 0.115915E+10 | 0.200842E+10 | 0.427543E+09 |
August | 0.179777E+10 | 0.751535E+09 | 0.104623E+10 | 0.258739E+10 | 0.472278E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989382E+09 | 0.302881E+10 | 0.684278E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.332833E+10 | 0.141702E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661489E+09 | 0.377905E+10 | 0.158908E+10 |
December | 0.322221E+10 | 0.260801E+10 | 0.614197E+09 | 0.356859E+10 | 0.194051E+10 |
Annual Sum or Average | 0.280552E+11 | 0.174928E+11 | 0.105624E+11 | 0.336324E+11 | 0.138123E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614197E+09 | 0.159796E+10 | 0.427543E+09 |
Maximum of Months | 0.350517E+10 | 0.288338E+10 | 0.120156E+10 | 0.397092E+10 | 0.194051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350518E+10 | 0.288339E+10 | 0.621791E+09 | 0.397092E+10 | 0.171613E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615661E+09 | 0.341604E+10 | 0.160812E+10 |
March | 0.247881E+10 | 0.163092E+10 | 0.847893E+09 | 0.281776E+10 | 0.143899E+10 |
April | 0.155367E+10 | 0.624738E+09 | 0.928935E+09 | 0.159796E+10 | 0.127703E+10 |
May | 0.147123E+10 | 0.269666E+09 | 0.120156E+10 | 0.165888E+10 | 0.804128E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187026E+10 | 0.437152E+09 |
July | 0.141201E+10 | 0.252851E+09 | 0.115915E+10 | 0.200842E+10 | 0.427543E+09 |
August | 0.179777E+10 | 0.751536E+09 | 0.104623E+10 | 0.258740E+10 | 0.472278E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989383E+09 | 0.302881E+10 | 0.684278E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.332834E+10 | 0.141702E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661490E+09 | 0.377905E+10 | 0.158908E+10 |
December | 0.322221E+10 | 0.260802E+10 | 0.614198E+09 | 0.356859E+10 | 0.194051E+10 |
Annual Sum or Average | 0.280553E+11 | 0.174929E+11 | 0.105624E+11 | 0.336324E+11 | 0.138123E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614198E+09 | 0.159796E+10 | 0.427543E+09 |
Maximum of Months | 0.350518E+10 | 0.288339E+10 | 0.120156E+10 | 0.397092E+10 | 0.194051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350517E+10 | 0.288338E+10 | 0.621791E+09 | 0.397092E+10 | 0.171613E+10 |
February | 0.303675E+10 | 0.242109E+10 | 0.615660E+09 | 0.341603E+10 | 0.160812E+10 |
March | 0.247881E+10 | 0.163091E+10 | 0.847893E+09 | 0.281776E+10 | 0.143899E+10 |
April | 0.155367E+10 | 0.624737E+09 | 0.928934E+09 | 0.159796E+10 | 0.127703E+10 |
May | 0.147123E+10 | 0.269665E+09 | 0.120156E+10 | 0.165888E+10 | 0.804128E+09 |
June | 0.131267E+10 | 0.239919E+09 | 0.107275E+10 | 0.187025E+10 | 0.437152E+09 |
July | 0.141200E+10 | 0.252851E+09 | 0.115915E+10 | 0.200842E+10 | 0.427543E+09 |
August | 0.179777E+10 | 0.751535E+09 | 0.104623E+10 | 0.258739E+10 | 0.472278E+09 |
September | 0.223839E+10 | 0.124901E+10 | 0.989382E+09 | 0.302881E+10 | 0.684278E+09 |
October | 0.276568E+10 | 0.196231E+10 | 0.803367E+09 | 0.332833E+10 | 0.141702E+10 |
November | 0.326090E+10 | 0.259941E+10 | 0.661489E+09 | 0.377905E+10 | 0.158908E+10 |
December | 0.322221E+10 | 0.260801E+10 | 0.614197E+09 | 0.356859E+10 | 0.194051E+10 |
Annual Sum or Average | 0.280552E+11 | 0.174928E+11 | 0.105624E+11 | 0.336324E+11 | 0.138123E+11 |
Minimum of Months | 0.131267E+10 | 0.239919E+09 | 0.614197E+09 | 0.159796E+10 | 0.427543E+09 |
Maximum of Months | 0.350517E+10 | 0.288338E+10 | 0.120156E+10 | 0.397092E+10 | 0.194051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.350504E+10 | 0.288327E+10 | 0.621766E+09 | 0.397076E+10 | 0.171606E+10 |
February | 0.303663E+10 | 0.242099E+10 | 0.615636E+09 | 0.341590E+10 | 0.160806E+10 |
March | 0.247871E+10 | 0.163085E+10 | 0.847859E+09 | 0.281765E+10 | 0.143894E+10 |
April | 0.155361E+10 | 0.624713E+09 | 0.928897E+09 | 0.159789E+10 | 0.127698E+10 |
May | 0.147117E+10 | 0.269655E+09 | 0.120151E+10 | 0.165881E+10 | 0.804095E+09 |
June | 0.131262E+10 | 0.239909E+09 | 0.107271E+10 | 0.187018E+10 | 0.437134E+09 |
July | 0.141195E+10 | 0.252841E+09 | 0.115911E+10 | 0.200834E+10 | 0.427526E+09 |
August | 0.179770E+10 | 0.751506E+09 | 0.104619E+10 | 0.258729E+10 | 0.472259E+09 |
September | 0.223830E+10 | 0.124896E+10 | 0.989343E+09 | 0.302869E+10 | 0.684251E+09 |
October | 0.276557E+10 | 0.196223E+10 | 0.803335E+09 | 0.332820E+10 | 0.141696E+10 |
November | 0.326077E+10 | 0.259931E+10 | 0.661463E+09 | 0.377890E+10 | 0.158901E+10 |
December | 0.322208E+10 | 0.260791E+10 | 0.614173E+09 | 0.356845E+10 | 0.194044E+10 |
Annual Sum or Average | 0.280541E+11 | 0.174921E+11 | 0.105620E+11 | 0.336311E+11 | 0.138117E+11 |
Minimum of Months | 0.131262E+10 | 0.239909E+09 | 0.614173E+09 | 0.159789E+10 | 0.427526E+09 |
Maximum of Months | 0.350504E+10 | 0.288327E+10 | 0.120151E+10 | 0.397076E+10 | 0.194044E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135363E+10 | 0.857733E+09 | 0.495896E+09 | 0.123749E+10 | 0.217707E+10 |
February | 0.147432E+10 | 0.913643E+09 | 0.560678E+09 | 0.134197E+10 | 0.203115E+10 |
March | 0.191130E+10 | 0.105451E+10 | 0.856793E+09 | 0.184577E+10 | 0.179308E+10 |
April | 0.174153E+10 | 0.737332E+09 | 0.100419E+10 | 0.158758E+10 | 0.158680E+10 |
May | 0.219954E+10 | 0.775421E+09 | 0.142412E+10 | 0.243822E+10 | 0.938455E+09 |
June | 0.260340E+10 | 0.125259E+10 | 0.135080E+10 | 0.348512E+10 | 0.547617E+09 |
July | 0.219186E+10 | 0.802837E+09 | 0.138902E+10 | 0.291883E+10 | 0.536215E+09 |
August | 0.228768E+10 | 0.113014E+10 | 0.115753E+10 | 0.300422E+10 | 0.607269E+09 |
September | 0.196305E+10 | 0.941413E+09 | 0.102164E+10 | 0.248019E+10 | 0.811619E+09 |
October | 0.170649E+10 | 0.975388E+09 | 0.731105E+09 | 0.179650E+10 | 0.172857E+10 |
November | 0.135510E+10 | 0.822712E+09 | 0.532385E+09 | 0.126274E+10 | 0.201782E+10 |
December | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918261E+09 | 0.255132E+10 |
Annual Sum or Average | 0.219189E+11 | 0.109319E+11 | 0.109871E+11 | 0.243169E+11 | 0.173270E+11 |
Minimum of Months | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918261E+09 | 0.536215E+09 |
Maximum of Months | 0.260340E+10 | 0.125259E+10 | 0.142412E+10 | 0.348512E+10 | 0.255132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135363E+10 | 0.857733E+09 | 0.495896E+09 | 0.123749E+10 | 0.217707E+10 |
February | 0.147432E+10 | 0.913643E+09 | 0.560678E+09 | 0.134197E+10 | 0.203115E+10 |
March | 0.191130E+10 | 0.105451E+10 | 0.856793E+09 | 0.184577E+10 | 0.179308E+10 |
April | 0.174153E+10 | 0.737332E+09 | 0.100419E+10 | 0.158758E+10 | 0.158680E+10 |
May | 0.219954E+10 | 0.775421E+09 | 0.142412E+10 | 0.243822E+10 | 0.938455E+09 |
June | 0.260340E+10 | 0.125259E+10 | 0.135080E+10 | 0.348512E+10 | 0.547617E+09 |
July | 0.219186E+10 | 0.802837E+09 | 0.138902E+10 | 0.291883E+10 | 0.536215E+09 |
August | 0.228768E+10 | 0.113014E+10 | 0.115753E+10 | 0.300422E+10 | 0.607269E+09 |
September | 0.196305E+10 | 0.941413E+09 | 0.102164E+10 | 0.248019E+10 | 0.811619E+09 |
October | 0.170649E+10 | 0.975388E+09 | 0.731105E+09 | 0.179650E+10 | 0.172857E+10 |
November | 0.135510E+10 | 0.822712E+09 | 0.532385E+09 | 0.126274E+10 | 0.201782E+10 |
December | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918261E+09 | 0.255132E+10 |
Annual Sum or Average | 0.219189E+11 | 0.109319E+11 | 0.109871E+11 | 0.243169E+11 | 0.173270E+11 |
Minimum of Months | 0.113103E+10 | 0.668132E+09 | 0.462902E+09 | 0.918261E+09 | 0.536215E+09 |
Maximum of Months | 0.260340E+10 | 0.125259E+10 | 0.142412E+10 | 0.348512E+10 | 0.255132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135360E+10 | 0.857717E+09 | 0.495887E+09 | 0.123747E+10 | 0.217703E+10 |
February | 0.147429E+10 | 0.913626E+09 | 0.560668E+09 | 0.134195E+10 | 0.203111E+10 |
March | 0.191126E+10 | 0.105449E+10 | 0.856777E+09 | 0.184573E+10 | 0.179305E+10 |
April | 0.174149E+10 | 0.737319E+09 | 0.100418E+10 | 0.158755E+10 | 0.158677E+10 |
May | 0.219950E+10 | 0.775407E+09 | 0.142410E+10 | 0.243818E+10 | 0.938438E+09 |
June | 0.260335E+10 | 0.125257E+10 | 0.135078E+10 | 0.348505E+10 | 0.547607E+09 |
July | 0.219182E+10 | 0.802822E+09 | 0.138899E+10 | 0.291877E+10 | 0.536205E+09 |
August | 0.228763E+10 | 0.113012E+10 | 0.115751E+10 | 0.300417E+10 | 0.607258E+09 |
September | 0.196301E+10 | 0.941396E+09 | 0.102162E+10 | 0.248014E+10 | 0.811604E+09 |
October | 0.170646E+10 | 0.975370E+09 | 0.731092E+09 | 0.179647E+10 | 0.172854E+10 |
November | 0.135507E+10 | 0.822697E+09 | 0.532376E+09 | 0.126272E+10 | 0.201778E+10 |
December | 0.113101E+10 | 0.668119E+09 | 0.462893E+09 | 0.918244E+09 | 0.255127E+10 |
Annual Sum or Average | 0.219185E+11 | 0.109317E+11 | 0.109869E+11 | 0.243165E+11 | 0.173267E+11 |
Minimum of Months | 0.113101E+10 | 0.668119E+09 | 0.462893E+09 | 0.918244E+09 | 0.536205E+09 |
Maximum of Months | 0.260335E+10 | 0.125257E+10 | 0.142410E+10 | 0.348505E+10 | 0.255127E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.329072E+09 | 0.900304E+10 |
February | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.387007E+09 | 0.818459E+10 |
March | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.138953E+10 | 0.693468E+10 |
April | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.202747E+10 | 0.583475E+10 |
May | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.476269E+10 | 0.356764E+10 |
June | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.752123E+10 | 0.189717E+10 |
July | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.743655E+10 | 0.185579E+10 |
August | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.566141E+10 | 0.211846E+10 |
September | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.405299E+10 | 0.316675E+10 |
October | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.144612E+10 | 0.681332E+10 |
November | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.539713E+09 | 0.786622E+10 |
December | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.291916E+09 | 0.100357E+11 |
Annual Sum or Average | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.358457E+11 | 0.672780E+11 |
Minimum of Months | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.291916E+09 | 0.185579E+10 |
Maximum of Months | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.752123E+10 | 0.100357E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.331151E+10 | 0.574711E+10 |
February | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.422275E+10 | 0.532572E+10 |
March | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.608480E+10 | 0.452048E+10 |
April | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.590406E+10 | 0.384187E+10 |
May | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.817011E+10 | 0.243234E+10 |
June | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.115127E+11 | 0.129222E+10 |
July | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.109027E+11 | 0.126909E+10 |
August | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.109329E+11 | 0.145074E+10 |
September | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.832787E+10 | 0.207274E+10 |
October | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.510020E+10 | 0.451670E+10 |
November | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.341638E+10 | 0.515568E+10 |
December | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.276613E+10 | 0.643284E+10 |
Annual Sum or Average | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.806522E+11 | 0.440575E+11 |
Minimum of Months | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.276613E+10 | 0.126909E+10 |
Maximum of Months | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.115127E+11 | 0.643284E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.197209E+11 | 0.852495E+10 |
February | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.169310E+11 | 0.792430E+10 |
March | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.140070E+11 | 0.697941E+10 |
April | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.798483E+10 | 0.608977E+10 |
May | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.827005E+10 | 0.394986E+10 |
June | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.938633E+10 | 0.209093E+10 |
July | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.101167E+11 | 0.201031E+10 |
August | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.129371E+11 | 0.228853E+10 |
September | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.150745E+11 | 0.335238E+10 |
October | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.165362E+11 | 0.697088E+10 |
November | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.187731E+11 | 0.781242E+10 |
December | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.177666E+11 | 0.942872E+10 |
Annual Sum or Average | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.167504E+12 | 0.674225E+11 |
Minimum of Months | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.798483E+10 | 0.201031E+10 |
Maximum of Months | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.197209E+11 | 0.942872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.379518E+10 | 0.598648E+10 |
February | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.410945E+10 | 0.549891E+10 |
March | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.565310E+10 | 0.473531E+10 |
April | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.489832E+10 | 0.405265E+10 |
May | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.735553E+10 | 0.265211E+10 |
June | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.105129E+11 | 0.151212E+10 |
July | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.886388E+10 | 0.143448E+10 |
August | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.912791E+10 | 0.160829E+10 |
September | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.748062E+10 | 0.228059E+10 |
October | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.546400E+10 | 0.469962E+10 |
November | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.390823E+10 | 0.533338E+10 |
December | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.289344E+10 | 0.659666E+10 |
Annual Sum or Average | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.740625E+11 | 0.463906E+11 |
Minimum of Months | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.289344E+10 | 0.143448E+10 |
Maximum of Months | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.105129E+11 | 0.659666E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.409569E+09 | 0.833512E+10 |
February | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.449575E+09 | 0.771435E+10 |
March | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.147305E+10 | 0.651198E+10 |
April | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.212206E+10 | 0.535904E+10 |
May | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.483253E+10 | 0.342732E+10 |
June | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.747333E+10 | 0.188892E+10 |
July | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.738592E+10 | 0.185462E+10 |
August | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.562822E+10 | 0.209535E+10 |
September | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.406421E+10 | 0.306510E+10 |
October | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.153676E+10 | 0.635650E+10 |
November | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.631406E+09 | 0.729778E+10 |
December | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.343326E+09 | 0.947191E+10 |
Annual Sum or Average | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.363500E+11 | 0.633780E+11 |
Minimum of Months | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.343326E+09 | 0.185462E+10 |
Maximum of Months | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.747333E+10 | 0.947191E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.342579E+10 | 0.529964E+10 |
February | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.428780E+10 | 0.502198E+10 |
March | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.614693E+10 | 0.426513E+10 |
April | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.596637E+10 | 0.354399E+10 |
May | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.820738E+10 | 0.235106E+10 |
June | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.114880E+11 | 0.128744E+10 |
July | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.108775E+11 | 0.126716E+10 |
August | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.109165E+11 | 0.143688E+10 |
September | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.833555E+10 | 0.201933E+10 |
October | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.515233E+10 | 0.424690E+10 |
November | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.351015E+10 | 0.478528E+10 |
December | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.285105E+10 | 0.605894E+10 |
Annual Sum or Average | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.811654E+11 | 0.415837E+11 |
Minimum of Months | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.285105E+10 | 0.126716E+10 |
Maximum of Months | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.114880E+11 | 0.605894E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.199077E+11 | 0.793732E+10 |
February | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.170291E+11 | 0.748982E+10 |
March | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.140767E+11 | 0.658882E+10 |
April | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.805579E+10 | 0.561940E+10 |
May | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.830631E+10 | 0.379766E+10 |
June | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.933528E+10 | 0.207811E+10 |
July | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.100630E+11 | 0.200522E+10 |
August | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.128909E+11 | 0.226552E+10 |
September | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.150593E+11 | 0.326528E+10 |
October | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.166013E+11 | 0.657267E+10 |
November | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.188919E+11 | 0.733949E+10 |
December | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.179010E+11 | 0.888463E+10 |
Annual Sum or Average | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.168118E+12 | 0.638439E+11 |
Minimum of Months | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.805579E+10 | 0.200522E+10 |
Maximum of Months | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.199077E+11 | 0.888463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.386866E+10 | 0.558464E+10 |
February | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.414896E+10 | 0.521847E+10 |
March | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.569048E+10 | 0.448415E+10 |
April | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.494030E+10 | 0.377031E+10 |
May | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.736867E+10 | 0.256343E+10 |
June | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.104725E+11 | 0.150108E+10 |
July | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.882541E+10 | 0.142706E+10 |
August | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.909557E+10 | 0.159134E+10 |
September | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.747316E+10 | 0.222147E+10 |
October | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.550318E+10 | 0.444585E+10 |
November | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.396530E+10 | 0.501885E+10 |
December | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.294039E+10 | 0.625864E+10 |
Annual Sum or Average | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.742925E+11 | 0.440853E+11 |
Minimum of Months | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.294039E+10 | 0.142706E+10 |
Maximum of Months | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.104725E+11 | 0.625864E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.31 | 3682.02 | 682.75 | 0.00 | 682.75 | 0.00 | 0.00 |
February | 119.68 | 3689.45 | 858.13 | 0.00 | 858.13 | 0.00 | 0.00 |
March | 459.02 | 2842.44 | 1167.64 | 0.00 | 1167.64 | 0.00 | 0.00 |
April | 724.88 | 2502.96 | 1466.38 | 8.13 | 1458.25 | 0.00 | 0.00 |
May | 1753.41 | 1389.37 | 2003.17 | 66.22 | 1936.95 | 0.00 | 0.00 |
June | 2868.72 | 771.04 | 2196.61 | 243.53 | 1953.08 | 0.00 | 0.00 |
July | 2720.42 | 750.43 | 2077.40 | 134.47 | 1942.92 | 0.00 | 0.00 |
August | 2075.36 | 836.78 | 1653.45 | 39.12 | 1614.33 | 0.00 | 0.00 |
September | 1529.66 | 1296.63 | 1388.90 | 0.33 | 1388.57 | 0.00 | 0.00 |
October | 494.59 | 2749.16 | 994.79 | 0.00 | 994.79 | 0.00 | 0.00 |
November | 161.65 | 3357.39 | 755.17 | 0.00 | 755.17 | 0.00 | 0.00 |
December | 70.34 | 4168.87 | 638.80 | 0.00 | 638.80 | 0.00 | 0.00 |
Annual Sum or Average | 1094.51 | 2329.14 | 1326.02 | 41.08 | 1284.94 | 0.00 | 0.00 |
Minimum of Months | 70.34 | 750.43 | 638.80 | 0.00 | 638.80 | 0.00 | 0.00 |
Maximum of Months | 2868.72 | 4168.87 | 2196.61 | 243.53 | 1953.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1218.04 | 2275.82 | 1425.25 | 873.44 | 551.82 | 0.00 | 0.00 |
February | 1744.65 | 2318.65 | 1893.29 | 1195.23 | 698.06 | 0.00 | 0.00 |
March | 2276.65 | 1781.45 | 2285.15 | 1332.91 | 952.24 | 0.00 | 0.00 |
April | 2282.80 | 1577.06 | 2343.55 | 1141.58 | 1201.96 | 0.00 | 0.00 |
May | 3071.32 | 926.00 | 2739.57 | 1144.33 | 1595.24 | 0.00 | 0.00 |
June | 4459.01 | 513.41 | 3342.56 | 1754.75 | 1587.80 | 0.00 | 0.00 |
July | 4075.79 | 496.06 | 3038.65 | 1446.93 | 1591.72 | 0.00 | 0.00 |
August | 4101.18 | 545.46 | 3064.89 | 1688.03 | 1376.86 | 0.00 | 0.00 |
September | 3227.19 | 825.20 | 2550.15 | 1385.31 | 1164.84 | 0.00 | 0.00 |
October | 1910.52 | 1764.23 | 1846.82 | 1011.95 | 834.87 | 0.00 | 0.00 |
November | 1306.28 | 2105.25 | 1437.51 | 811.63 | 625.88 | 0.00 | 0.00 |
December | 1011.29 | 2571.42 | 1244.50 | 716.92 | 527.58 | 0.00 | 0.00 |
Annual Sum or Average | 2560.87 | 1470.48 | 2269.08 | 1207.98 | 1061.10 | 0.00 | 0.00 |
Minimum of Months | 1011.29 | 496.06 | 1244.50 | 716.92 | 527.58 | 0.00 | 0.00 |
Maximum of Months | 4459.01 | 2571.42 | 3342.56 | 1754.75 | 1595.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7412.80 | 3203.62 | 6543.36 | 5382.62 | 1160.74 | 0.00 | 0.00 |
February | 7060.20 | 3323.64 | 6276.30 | 5003.86 | 1272.44 | 0.00 | 0.00 |
March | 5260.11 | 2686.27 | 4627.37 | 3044.55 | 1582.82 | 0.00 | 0.00 |
April | 3082.45 | 2463.39 | 2997.03 | 1205.12 | 1791.91 | 0.00 | 0.00 |
May | 3096.75 | 1501.12 | 2746.45 | 503.40 | 2243.04 | 0.00 | 0.00 |
June | 3607.72 | 843.26 | 2532.13 | 462.80 | 2069.33 | 0.00 | 0.00 |
July | 3749.26 | 798.13 | 2635.89 | 472.01 | 2163.88 | 0.00 | 0.00 |
August | 4830.07 | 881.64 | 3356.02 | 1402.94 | 1953.08 | 0.00 | 0.00 |
September | 5842.57 | 1319.97 | 4317.85 | 2409.34 | 1908.52 | 0.00 | 0.00 |
October | 6213.24 | 2645.25 | 5162.89 | 3663.19 | 1499.70 | 0.00 | 0.00 |
November | 7289.77 | 3065.33 | 6290.26 | 5014.25 | 1276.01 | 0.00 | 0.00 |
December | 6661.74 | 3622.50 | 6015.13 | 4868.57 | 1146.57 | 0.00 | 0.00 |
Annual Sum or Average | 5332.34 | 2189.90 | 4448.10 | 2773.45 | 1674.65 | 0.00 | 0.00 |
Minimum of Months | 3082.45 | 798.13 | 2532.13 | 462.80 | 1146.57 | 0.00 | 0.00 |
Maximum of Months | 7412.80 | 3622.50 | 6543.36 | 5382.62 | 2243.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1386.07 | 2438.46 | 1516.15 | 960.72 | 555.44 | 0.00 | 0.00 |
February | 1664.14 | 2518.77 | 1828.26 | 1132.98 | 695.28 | 0.00 | 0.00 |
March | 2067.38 | 2008.37 | 2140.78 | 1181.12 | 959.66 | 0.00 | 0.00 |
April | 1837.47 | 1836.56 | 2015.64 | 853.39 | 1162.25 | 0.00 | 0.00 |
May | 2730.97 | 1051.13 | 2463.63 | 868.52 | 1595.11 | 0.00 | 0.00 |
June | 4033.68 | 633.81 | 3013.17 | 1449.75 | 1563.42 | 0.00 | 0.00 |
July | 3269.28 | 600.60 | 2455.02 | 899.23 | 1555.79 | 0.00 | 0.00 |
August | 3364.92 | 680.18 | 2562.35 | 1265.84 | 1296.51 | 0.00 | 0.00 |
September | 2870.57 | 939.37 | 2272.03 | 1089.59 | 1182.44 | 0.00 | 0.00 |
October | 2012.19 | 1936.11 | 1911.38 | 1092.50 | 818.88 | 0.00 | 0.00 |
November | 1461.50 | 2335.42 | 1568.39 | 952.21 | 616.18 | 0.00 | 0.00 |
December | 1028.51 | 2857.64 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Annual Sum or Average | 2313.24 | 1648.29 | 2085.12 | 1039.93 | 1045.19 | 0.00 | 0.00 |
Minimum of Months | 1028.51 | 600.60 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Maximum of Months | 4033.68 | 2857.64 | 3013.17 | 1449.75 | 1595.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.86 | 3361.35 | 682.75 | 0.00 | 682.75 | 0.00 | 0.00 |
February | 159.97 | 3383.18 | 858.13 | 0.00 | 858.13 | 0.00 | 0.00 |
March | 518.79 | 2589.11 | 1167.63 | 0.00 | 1167.63 | 0.00 | 0.00 |
April | 782.20 | 2251.06 | 1466.38 | 8.13 | 1458.24 | 0.00 | 0.00 |
May | 1778.19 | 1332.00 | 2003.16 | 66.22 | 1936.94 | 0.00 | 0.00 |
June | 2901.71 | 731.93 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
July | 2776.49 | 692.87 | 2077.39 | 134.47 | 1942.92 | 0.00 | 0.00 |
August | 2113.73 | 790.94 | 1653.44 | 39.11 | 1614.33 | 0.00 | 0.00 |
September | 1563.65 | 1221.74 | 1388.89 | 0.33 | 1388.57 | 0.00 | 0.00 |
October | 539.92 | 2543.80 | 994.78 | 0.00 | 994.78 | 0.00 | 0.00 |
November | 208.22 | 3034.81 | 755.17 | 0.00 | 755.17 | 0.00 | 0.00 |
December | 108.99 | 3746.88 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Annual Sum or Average | 1136.66 | 2133.37 | 1326.01 | 41.08 | 1284.94 | 0.00 | 0.00 |
Minimum of Months | 108.99 | 692.87 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Maximum of Months | 2901.71 | 3746.88 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1236.38 | 2145.73 | 1425.25 | 873.44 | 551.81 | 0.00 | 0.00 |
February | 1745.51 | 2201.44 | 1893.28 | 1195.22 | 698.06 | 0.00 | 0.00 |
March | 2271.80 | 1687.75 | 2285.14 | 1332.90 | 952.24 | 0.00 | 0.00 |
April | 2277.80 | 1482.20 | 2343.54 | 1141.58 | 1201.96 | 0.00 | 0.00 |
May | 3050.37 | 908.13 | 2739.56 | 1144.32 | 1595.23 | 0.00 | 0.00 |
June | 4441.61 | 498.54 | 3342.54 | 1754.75 | 1587.80 | 0.00 | 0.00 |
July | 4070.61 | 473.82 | 3038.64 | 1446.92 | 1591.71 | 0.00 | 0.00 |
August | 4081.89 | 541.64 | 3064.88 | 1688.03 | 1376.85 | 0.00 | 0.00 |
September | 3212.91 | 799.67 | 2550.14 | 1385.31 | 1164.83 | 0.00 | 0.00 |
October | 1904.20 | 1686.34 | 1846.81 | 1011.94 | 834.86 | 0.00 | 0.00 |
November | 1318.05 | 1989.07 | 1437.50 | 811.63 | 625.87 | 0.00 | 0.00 |
December | 1032.76 | 2401.75 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Annual Sum or Average | 2557.46 | 1397.06 | 2269.07 | 1207.98 | 1061.09 | 0.00 | 0.00 |
Minimum of Months | 1032.76 | 473.82 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Maximum of Months | 4441.61 | 2401.75 | 3342.54 | 1754.75 | 1595.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7362.93 | 3182.85 | 6543.34 | 5382.60 | 1160.74 | 0.00 | 0.00 |
February | 6998.58 | 3275.59 | 6276.27 | 5003.84 | 1272.43 | 0.00 | 0.00 |
March | 5229.61 | 2605.81 | 4627.35 | 3044.54 | 1582.82 | 0.00 | 0.00 |
April | 3080.57 | 2349.45 | 2997.02 | 1205.11 | 1791.90 | 0.00 | 0.00 |
May | 3087.68 | 1474.71 | 2746.44 | 503.40 | 2243.03 | 0.00 | 0.00 |
June | 3621.27 | 806.68 | 2532.12 | 462.80 | 2069.32 | 0.00 | 0.00 |
July | 3777.14 | 750.56 | 2635.88 | 472.01 | 2163.87 | 0.00 | 0.00 |
August | 4830.18 | 854.44 | 3356.01 | 1402.94 | 1953.07 | 0.00 | 0.00 |
September | 5815.76 | 1293.35 | 4317.84 | 2409.33 | 1908.51 | 0.00 | 0.00 |
October | 6173.92 | 2602.63 | 5162.87 | 3663.18 | 1499.70 | 0.00 | 0.00 |
November | 7242.70 | 3014.05 | 6290.24 | 5014.23 | 1276.01 | 0.00 | 0.00 |
December | 6633.30 | 3520.28 | 6015.11 | 4868.55 | 1146.56 | 0.00 | 0.00 |
Annual Sum or Average | 5311.53 | 2137.95 | 4448.08 | 2773.44 | 1674.64 | 0.00 | 0.00 |
Minimum of Months | 3080.57 | 750.56 | 2532.12 | 462.80 | 1146.56 | 0.00 | 0.00 |
Maximum of Months | 7362.93 | 3520.28 | 6543.34 | 5382.60 | 2243.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1416.96 | 2235.10 | 1516.15 | 960.71 | 555.43 | 0.00 | 0.00 |
February | 1698.68 | 2273.03 | 1828.26 | 1132.98 | 695.28 | 0.00 | 0.00 |
March | 2110.62 | 1767.96 | 2140.77 | 1181.11 | 959.66 | 0.00 | 0.00 |
April | 1889.78 | 1563.52 | 2015.63 | 853.39 | 1162.25 | 0.00 | 0.00 |
May | 2746.24 | 990.18 | 2463.62 | 868.52 | 1595.10 | 0.00 | 0.00 |
June | 4055.89 | 583.38 | 3013.16 | 1449.75 | 1563.41 | 0.00 | 0.00 |
July | 3309.39 | 535.57 | 2455.01 | 899.23 | 1555.79 | 0.00 | 0.00 |
August | 3407.97 | 600.47 | 2562.34 | 1265.83 | 1296.51 | 0.00 | 0.00 |
September | 2886.04 | 879.86 | 2272.02 | 1089.59 | 1182.44 | 0.00 | 0.00 |
October | 2040.02 | 1754.64 | 1911.37 | 1092.49 | 818.88 | 0.00 | 0.00 |
November | 1507.80 | 2057.63 | 1568.38 | 952.20 | 616.18 | 0.00 | 0.00 |
December | 1080.29 | 2462.91 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Annual Sum or Average | 2348.51 | 1471.04 | 2085.11 | 1039.93 | 1045.18 | 0.00 | 0.00 |
Minimum of Months | 1080.29 | 535.57 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Maximum of Months | 4055.89 | 2462.91 | 3013.16 | 1449.75 | 1595.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.92 | 3111.98 | 682.75 | 0.00 | 682.75 | 0.00 | 0.00 |
February | 185.84 | 3188.80 | 858.13 | 0.00 | 858.13 | 0.00 | 0.00 |
March | 549.97 | 2431.29 | 1167.63 | 0.00 | 1167.63 | 0.00 | 0.00 |
April | 818.70 | 2067.53 | 1466.38 | 8.13 | 1458.24 | 0.00 | 0.00 |
May | 1804.26 | 1279.62 | 2003.16 | 66.22 | 1936.94 | 0.00 | 0.00 |
June | 2883.23 | 728.75 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
July | 2757.59 | 692.44 | 2077.39 | 134.47 | 1942.92 | 0.00 | 0.00 |
August | 2101.34 | 782.31 | 1653.44 | 39.11 | 1614.33 | 0.00 | 0.00 |
September | 1567.98 | 1182.52 | 1388.89 | 0.33 | 1388.57 | 0.00 | 0.00 |
October | 573.76 | 2373.24 | 994.78 | 0.00 | 994.78 | 0.00 | 0.00 |
November | 243.60 | 2815.50 | 755.17 | 0.00 | 755.17 | 0.00 | 0.00 |
December | 128.18 | 3536.41 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Annual Sum or Average | 1152.65 | 2009.70 | 1326.01 | 41.08 | 1284.94 | 0.00 | 0.00 |
Minimum of Months | 128.18 | 692.44 | 638.79 | 0.00 | 638.79 | 0.00 | 0.00 |
Maximum of Months | 2883.23 | 3536.41 | 2196.60 | 243.53 | 1953.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1279.04 | 1978.66 | 1425.25 | 873.44 | 551.81 | 0.00 | 0.00 |
February | 1772.41 | 2075.89 | 1893.28 | 1195.22 | 698.06 | 0.00 | 0.00 |
March | 2295.00 | 1592.42 | 2285.14 | 1332.90 | 952.24 | 0.00 | 0.00 |
April | 2301.84 | 1367.28 | 2343.54 | 1141.58 | 1201.96 | 0.00 | 0.00 |
May | 3064.29 | 877.78 | 2739.56 | 1144.32 | 1595.23 | 0.00 | 0.00 |
June | 4432.12 | 496.70 | 3342.54 | 1754.75 | 1587.80 | 0.00 | 0.00 |
July | 4061.21 | 473.10 | 3038.64 | 1446.92 | 1591.71 | 0.00 | 0.00 |
August | 4075.74 | 536.47 | 3064.88 | 1688.03 | 1376.85 | 0.00 | 0.00 |
September | 3215.88 | 779.06 | 2550.14 | 1385.31 | 1164.83 | 0.00 | 0.00 |
October | 1923.66 | 1585.61 | 1846.81 | 1011.94 | 834.86 | 0.00 | 0.00 |
November | 1354.23 | 1846.17 | 1437.50 | 811.63 | 625.87 | 0.00 | 0.00 |
December | 1064.46 | 2262.15 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Annual Sum or Average | 2573.74 | 1318.61 | 2269.07 | 1207.98 | 1061.09 | 0.00 | 0.00 |
Minimum of Months | 1064.46 | 473.10 | 1244.49 | 716.92 | 527.58 | 0.00 | 0.00 |
Maximum of Months | 4432.12 | 2262.15 | 3342.54 | 1754.75 | 1595.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7432.67 | 2963.46 | 6543.34 | 5382.60 | 1160.74 | 0.00 | 0.00 |
February | 7039.14 | 3095.99 | 6276.27 | 5003.84 | 1272.43 | 0.00 | 0.00 |
March | 5255.65 | 2459.98 | 4627.35 | 3044.54 | 1582.82 | 0.00 | 0.00 |
April | 3107.94 | 2167.98 | 2997.02 | 1205.11 | 1791.90 | 0.00 | 0.00 |
May | 3101.22 | 1417.88 | 2746.44 | 503.40 | 2243.03 | 0.00 | 0.00 |
June | 3601.57 | 801.74 | 2532.12 | 462.80 | 2069.32 | 0.00 | 0.00 |
July | 3757.09 | 748.66 | 2635.88 | 472.01 | 2163.87 | 0.00 | 0.00 |
August | 4812.90 | 845.85 | 3356.01 | 1402.94 | 1953.07 | 0.00 | 0.00 |
September | 5809.93 | 1259.75 | 4317.84 | 2409.33 | 1908.51 | 0.00 | 0.00 |
October | 6198.23 | 2453.96 | 5162.87 | 3663.18 | 1499.70 | 0.00 | 0.00 |
November | 7288.53 | 2831.59 | 6290.24 | 5014.23 | 1276.01 | 0.00 | 0.00 |
December | 6683.47 | 3317.14 | 6015.11 | 4868.55 | 1146.56 | 0.00 | 0.00 |
Annual Sum or Average | 5331.00 | 2024.48 | 4448.08 | 2773.44 | 1674.64 | 0.00 | 0.00 |
Minimum of Months | 3101.22 | 748.66 | 2532.12 | 462.80 | 1146.56 | 0.00 | 0.00 |
Maximum of Months | 7432.67 | 3317.14 | 6543.34 | 5382.60 | 2243.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1444.39 | 2085.07 | 1516.15 | 960.71 | 555.43 | 0.00 | 0.00 |
February | 1715.01 | 2157.11 | 1828.26 | 1132.98 | 695.28 | 0.00 | 0.00 |
March | 2124.58 | 1674.19 | 2140.77 | 1181.11 | 959.66 | 0.00 | 0.00 |
April | 1905.98 | 1454.59 | 2015.63 | 853.39 | 1162.25 | 0.00 | 0.00 |
May | 2751.15 | 957.08 | 2463.62 | 868.52 | 1595.10 | 0.00 | 0.00 |
June | 4040.30 | 579.12 | 3013.16 | 1449.75 | 1563.41 | 0.00 | 0.00 |
July | 3295.03 | 532.80 | 2455.01 | 899.23 | 1555.79 | 0.00 | 0.00 |
August | 3395.90 | 594.14 | 2562.34 | 1265.83 | 1296.51 | 0.00 | 0.00 |
September | 2883.16 | 857.05 | 2272.02 | 1089.59 | 1182.44 | 0.00 | 0.00 |
October | 2054.65 | 1659.89 | 1911.37 | 1092.49 | 818.88 | 0.00 | 0.00 |
November | 1529.82 | 1936.28 | 1568.38 | 952.20 | 616.18 | 0.00 | 0.00 |
December | 1097.81 | 2336.71 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Annual Sum or Average | 2355.80 | 1397.94 | 2085.11 | 1039.93 | 1045.18 | 0.00 | 0.00 |
Minimum of Months | 1097.81 | 532.80 | 1266.83 | 748.35 | 518.48 | 0.00 | 0.00 |
Maximum of Months | 4040.30 | 2336.71 | 3013.16 | 1449.75 | 1595.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244572E+09 | 0.986192E+10 | 0.182867E+10 | 0.00 | 0.182867E+10 | 0.00 | 0.00 |
February | 0.289538E+09 | 0.892552E+10 | 0.207599E+10 | 0.00 | 0.207599E+10 | 0.00 | 0.00 |
March | 0.122945E+10 | 0.761319E+10 | 0.312739E+10 | 0.00 | 0.312739E+10 | 0.00 | 0.00 |
April | 0.187889E+10 | 0.648766E+10 | 0.380086E+10 | 21085545.88 | 0.377978E+10 | 0.00 | 0.00 |
May | 0.469634E+10 | 0.372128E+10 | 0.536528E+10 | 0.177355E+09 | 0.518793E+10 | 0.00 | 0.00 |
June | 0.743572E+10 | 0.199854E+10 | 0.569361E+10 | 0.631229E+09 | 0.506239E+10 | 0.00 | 0.00 |
July | 0.728636E+10 | 0.200994E+10 | 0.556410E+10 | 0.360174E+09 | 0.520392E+10 | 0.00 | 0.00 |
August | 0.555864E+10 | 0.224122E+10 | 0.442860E+10 | 0.104766E+09 | 0.432383E+10 | 0.00 | 0.00 |
September | 0.396487E+10 | 0.336087E+10 | 0.360002E+10 | 845581.62 | 0.359918E+10 | 0.00 | 0.00 |
October | 0.132472E+10 | 0.736336E+10 | 0.266443E+10 | 0.00 | 0.266443E+10 | 0.00 | 0.00 |
November | 0.418986E+09 | 0.870235E+10 | 0.195740E+10 | 0.00 | 0.195740E+10 | 0.00 | 0.00 |
December | 0.188393E+09 | 0.111659E+11 | 0.171095E+10 | 0.00 | 0.171095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.345165E+11 | 0.734518E+11 | 0.418173E+11 | 0.129545E+10 | 0.405219E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188393E+09 | 0.199854E+10 | 0.171095E+10 | 0.00 | 0.171095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.743572E+10 | 0.111659E+11 | 0.569361E+10 | 0.631229E+09 | 0.520392E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326239E+10 | 0.609555E+10 | 0.381740E+10 | 0.233942E+10 | 0.147798E+10 | 0.00 | 0.00 |
February | 0.422067E+10 | 0.560927E+10 | 0.458025E+10 | 0.289150E+10 | 0.168876E+10 | 0.00 | 0.00 |
March | 0.609777E+10 | 0.477145E+10 | 0.612055E+10 | 0.357006E+10 | 0.255049E+10 | 0.00 | 0.00 |
April | 0.591703E+10 | 0.408773E+10 | 0.607447E+10 | 0.295898E+10 | 0.311549E+10 | 0.00 | 0.00 |
May | 0.822622E+10 | 0.248021E+10 | 0.733766E+10 | 0.306497E+10 | 0.427269E+10 | 0.00 | 0.00 |
June | 0.115577E+11 | 0.133075E+10 | 0.866390E+10 | 0.454832E+10 | 0.411558E+10 | 0.00 | 0.00 |
July | 0.109166E+11 | 0.132864E+10 | 0.813872E+10 | 0.387546E+10 | 0.426326E+10 | 0.00 | 0.00 |
August | 0.109846E+11 | 0.146097E+10 | 0.820901E+10 | 0.452123E+10 | 0.368778E+10 | 0.00 | 0.00 |
September | 0.836489E+10 | 0.213892E+10 | 0.660998E+10 | 0.359073E+10 | 0.301925E+10 | 0.00 | 0.00 |
October | 0.511713E+10 | 0.472531E+10 | 0.494651E+10 | 0.271040E+10 | 0.223611E+10 | 0.00 | 0.00 |
November | 0.338589E+10 | 0.545682E+10 | 0.372602E+10 | 0.210375E+10 | 0.162227E+10 | 0.00 | 0.00 |
December | 0.270864E+10 | 0.688730E+10 | 0.333327E+10 | 0.192020E+10 | 0.141307E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.807596E+11 | 0.463729E+11 | 0.715578E+11 | 0.380950E+11 | 0.334627E+11 | 0.00 | 0.00 |
Minimum of Months | 0.270864E+10 | 0.132864E+10 | 0.333327E+10 | 0.192020E+10 | 0.141307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115577E+11 | 0.688730E+10 | 0.866390E+10 | 0.454832E+10 | 0.427269E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198544E+11 | 0.858057E+10 | 0.175257E+11 | 0.144168E+11 | 0.310893E+10 | 0.00 | 0.00 |
February | 0.170800E+11 | 0.804056E+10 | 0.151836E+11 | 0.121053E+11 | 0.307828E+10 | 0.00 | 0.00 |
March | 0.140887E+11 | 0.719491E+10 | 0.123939E+11 | 0.815451E+10 | 0.423943E+10 | 0.00 | 0.00 |
April | 0.798972E+10 | 0.638510E+10 | 0.776830E+10 | 0.312366E+10 | 0.464463E+10 | 0.00 | 0.00 |
May | 0.829432E+10 | 0.402061E+10 | 0.735608E+10 | 0.134832E+10 | 0.600776E+10 | 0.00 | 0.00 |
June | 0.935120E+10 | 0.218574E+10 | 0.656328E+10 | 0.119958E+10 | 0.536370E+10 | 0.00 | 0.00 |
July | 0.100420E+11 | 0.213770E+10 | 0.705997E+10 | 0.126424E+10 | 0.579573E+10 | 0.00 | 0.00 |
August | 0.129369E+11 | 0.236137E+10 | 0.898878E+10 | 0.375765E+10 | 0.523113E+10 | 0.00 | 0.00 |
September | 0.151439E+11 | 0.342136E+10 | 0.111919E+11 | 0.624500E+10 | 0.494687E+10 | 0.00 | 0.00 |
October | 0.166416E+11 | 0.708503E+10 | 0.138283E+11 | 0.981148E+10 | 0.401680E+10 | 0.00 | 0.00 |
November | 0.188951E+11 | 0.794533E+10 | 0.163044E+11 | 0.129969E+11 | 0.330742E+10 | 0.00 | 0.00 |
December | 0.178428E+11 | 0.970249E+10 | 0.161109E+11 | 0.130400E+11 | 0.307096E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.168161E+12 | 0.690608E+11 | 0.140275E+12 | 0.874635E+11 | 0.528117E+11 | 0.00 | 0.00 |
Minimum of Months | 0.798972E+10 | 0.213770E+10 | 0.656328E+10 | 0.119958E+10 | 0.307096E+10 | 0.00 | 0.00 |
Maximum of Months | 0.198544E+11 | 0.970249E+10 | 0.175257E+11 | 0.144168E+11 | 0.600776E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.371246E+10 | 0.653116E+10 | 0.406086E+10 | 0.257318E+10 | 0.148768E+10 | 0.00 | 0.00 |
February | 0.402589E+10 | 0.609340E+10 | 0.442294E+10 | 0.274091E+10 | 0.168202E+10 | 0.00 | 0.00 |
March | 0.553727E+10 | 0.537922E+10 | 0.573386E+10 | 0.316350E+10 | 0.257036E+10 | 0.00 | 0.00 |
April | 0.476272E+10 | 0.476036E+10 | 0.522455E+10 | 0.221198E+10 | 0.301256E+10 | 0.00 | 0.00 |
May | 0.731463E+10 | 0.281535E+10 | 0.659859E+10 | 0.232625E+10 | 0.427234E+10 | 0.00 | 0.00 |
June | 0.104553E+11 | 0.164284E+10 | 0.781014E+10 | 0.375776E+10 | 0.405238E+10 | 0.00 | 0.00 |
July | 0.875643E+10 | 0.160864E+10 | 0.657553E+10 | 0.240850E+10 | 0.416703E+10 | 0.00 | 0.00 |
August | 0.901261E+10 | 0.182180E+10 | 0.686299E+10 | 0.339041E+10 | 0.347257E+10 | 0.00 | 0.00 |
September | 0.744051E+10 | 0.243484E+10 | 0.588911E+10 | 0.282422E+10 | 0.306489E+10 | 0.00 | 0.00 |
October | 0.538946E+10 | 0.518569E+10 | 0.511945E+10 | 0.292615E+10 | 0.219330E+10 | 0.00 | 0.00 |
November | 0.378821E+10 | 0.605341E+10 | 0.406527E+10 | 0.246812E+10 | 0.159715E+10 | 0.00 | 0.00 |
December | 0.275477E+10 | 0.765390E+10 | 0.339308E+10 | 0.200438E+10 | 0.138870E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.729502E+11 | 0.519806E+11 | 0.657564E+11 | 0.327954E+11 | 0.329610E+11 | 0.00 | 0.00 |
Minimum of Months | 0.275477E+10 | 0.160864E+10 | 0.339308E+10 | 0.200438E+10 | 0.138870E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104553E+11 | 0.765390E+10 | 0.781014E+10 | 0.375776E+10 | 0.427234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.329072E+09 | 0.900304E+10 | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.00 | 0.00 |
February | 0.387007E+09 | 0.818459E+10 | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.00 | 0.00 |
March | 0.138953E+10 | 0.693468E+10 | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.00 | 0.00 |
April | 0.202747E+10 | 0.583475E+10 | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.00 | 0.00 |
May | 0.476269E+10 | 0.356764E+10 | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.00 | 0.00 |
June | 0.752123E+10 | 0.189717E+10 | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.00 | 0.00 |
July | 0.743655E+10 | 0.185579E+10 | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.00 | 0.00 |
August | 0.566141E+10 | 0.211846E+10 | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.00 | 0.00 |
September | 0.405299E+10 | 0.316675E+10 | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.00 | 0.00 |
October | 0.144612E+10 | 0.681332E+10 | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.00 | 0.00 |
November | 0.539713E+09 | 0.786622E+10 | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.00 | 0.00 |
December | 0.291916E+09 | 0.100357E+11 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.358457E+11 | 0.672780E+11 | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.291916E+09 | 0.185579E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Maximum of Months | 0.752123E+10 | 0.100357E+11 | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.331151E+10 | 0.574711E+10 | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.00 | 0.00 |
February | 0.422275E+10 | 0.532572E+10 | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.00 | 0.00 |
March | 0.608480E+10 | 0.452048E+10 | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.00 | 0.00 |
April | 0.590406E+10 | 0.384187E+10 | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.00 | 0.00 |
May | 0.817011E+10 | 0.243234E+10 | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.00 | 0.00 |
June | 0.115127E+11 | 0.129222E+10 | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.00 | 0.00 |
July | 0.109027E+11 | 0.126909E+10 | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.00 | 0.00 |
August | 0.109329E+11 | 0.145074E+10 | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.00 | 0.00 |
September | 0.832787E+10 | 0.207274E+10 | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.00 | 0.00 |
October | 0.510020E+10 | 0.451670E+10 | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.00 | 0.00 |
November | 0.341638E+10 | 0.515568E+10 | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.00 | 0.00 |
December | 0.276613E+10 | 0.643284E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.806522E+11 | 0.440575E+11 | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.276613E+10 | 0.126909E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115127E+11 | 0.643284E+10 | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197209E+11 | 0.852495E+10 | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.00 | 0.00 |
February | 0.169310E+11 | 0.792430E+10 | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.00 | 0.00 |
March | 0.140070E+11 | 0.697941E+10 | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.00 | 0.00 |
April | 0.798483E+10 | 0.608977E+10 | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.00 | 0.00 |
May | 0.827005E+10 | 0.394986E+10 | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.00 | 0.00 |
June | 0.938633E+10 | 0.209093E+10 | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.00 | 0.00 |
July | 0.101167E+11 | 0.201031E+10 | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.00 | 0.00 |
August | 0.129371E+11 | 0.228853E+10 | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.00 | 0.00 |
September | 0.150745E+11 | 0.335238E+10 | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.00 | 0.00 |
October | 0.165362E+11 | 0.697088E+10 | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.00 | 0.00 |
November | 0.187731E+11 | 0.781242E+10 | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.00 | 0.00 |
December | 0.177666E+11 | 0.942872E+10 | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.167504E+12 | 0.674225E+11 | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.798483E+10 | 0.201031E+10 | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.197209E+11 | 0.942872E+10 | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.379518E+10 | 0.598648E+10 | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.00 | 0.00 |
February | 0.410945E+10 | 0.549891E+10 | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.00 | 0.00 |
March | 0.565310E+10 | 0.473531E+10 | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.00 | 0.00 |
April | 0.489832E+10 | 0.405265E+10 | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.00 | 0.00 |
May | 0.735553E+10 | 0.265211E+10 | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.00 | 0.00 |
June | 0.105129E+11 | 0.151212E+10 | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.00 | 0.00 |
July | 0.886388E+10 | 0.143448E+10 | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.00 | 0.00 |
August | 0.912791E+10 | 0.160829E+10 | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.00 | 0.00 |
September | 0.748062E+10 | 0.228059E+10 | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.00 | 0.00 |
October | 0.546400E+10 | 0.469962E+10 | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.00 | 0.00 |
November | 0.390823E+10 | 0.533338E+10 | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.00 | 0.00 |
December | 0.289344E+10 | 0.659666E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.740625E+11 | 0.463906E+11 | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.289344E+10 | 0.143448E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105129E+11 | 0.659666E+10 | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.409569E+09 | 0.833512E+10 | 0.182866E+10 | 0.00 | 0.182866E+10 | 0.00 | 0.00 |
February | 0.449575E+09 | 0.771435E+10 | 0.207598E+10 | 0.00 | 0.207598E+10 | 0.00 | 0.00 |
March | 0.147305E+10 | 0.651198E+10 | 0.312738E+10 | 0.00 | 0.312738E+10 | 0.00 | 0.00 |
April | 0.212206E+10 | 0.535904E+10 | 0.380085E+10 | 21085471.00 | 0.377976E+10 | 0.00 | 0.00 |
May | 0.483253E+10 | 0.342732E+10 | 0.536526E+10 | 0.177354E+09 | 0.518791E+10 | 0.00 | 0.00 |
June | 0.747333E+10 | 0.188892E+10 | 0.569359E+10 | 0.631227E+09 | 0.506237E+10 | 0.00 | 0.00 |
July | 0.738592E+10 | 0.185462E+10 | 0.556408E+10 | 0.360173E+09 | 0.520390E+10 | 0.00 | 0.00 |
August | 0.562822E+10 | 0.209535E+10 | 0.442858E+10 | 0.104765E+09 | 0.432382E+10 | 0.00 | 0.00 |
September | 0.406421E+10 | 0.306510E+10 | 0.360001E+10 | 845578.62 | 0.359916E+10 | 0.00 | 0.00 |
October | 0.153676E+10 | 0.635650E+10 | 0.266442E+10 | 0.00 | 0.266442E+10 | 0.00 | 0.00 |
November | 0.631406E+09 | 0.729778E+10 | 0.195739E+10 | 0.00 | 0.195739E+10 | 0.00 | 0.00 |
December | 0.343326E+09 | 0.947191E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.363500E+11 | 0.633780E+11 | 0.418172E+11 | 0.129545E+10 | 0.405217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.343326E+09 | 0.185462E+10 | 0.171094E+10 | 0.00 | 0.171094E+10 | 0.00 | 0.00 |
Maximum of Months | 0.747333E+10 | 0.947191E+10 | 0.569359E+10 | 0.631227E+09 | 0.520390E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.342579E+10 | 0.529964E+10 | 0.381738E+10 | 0.233941E+10 | 0.147798E+10 | 0.00 | 0.00 |
February | 0.428780E+10 | 0.502198E+10 | 0.458023E+10 | 0.289148E+10 | 0.168875E+10 | 0.00 | 0.00 |
March | 0.614693E+10 | 0.426513E+10 | 0.612052E+10 | 0.357005E+10 | 0.255048E+10 | 0.00 | 0.00 |
April | 0.596637E+10 | 0.354399E+10 | 0.607445E+10 | 0.295897E+10 | 0.311548E+10 | 0.00 | 0.00 |
May | 0.820738E+10 | 0.235106E+10 | 0.733763E+10 | 0.306496E+10 | 0.427267E+10 | 0.00 | 0.00 |
June | 0.114880E+11 | 0.128744E+10 | 0.866387E+10 | 0.454830E+10 | 0.411557E+10 | 0.00 | 0.00 |
July | 0.108775E+11 | 0.126716E+10 | 0.813868E+10 | 0.387544E+10 | 0.426324E+10 | 0.00 | 0.00 |
August | 0.109165E+11 | 0.143688E+10 | 0.820898E+10 | 0.452121E+10 | 0.368777E+10 | 0.00 | 0.00 |
September | 0.833555E+10 | 0.201933E+10 | 0.660996E+10 | 0.359071E+10 | 0.301924E+10 | 0.00 | 0.00 |
October | 0.515233E+10 | 0.424690E+10 | 0.494649E+10 | 0.271039E+10 | 0.223610E+10 | 0.00 | 0.00 |
November | 0.351015E+10 | 0.478528E+10 | 0.372601E+10 | 0.210374E+10 | 0.162227E+10 | 0.00 | 0.00 |
December | 0.285105E+10 | 0.605894E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.811654E+11 | 0.415837E+11 | 0.715575E+11 | 0.380949E+11 | 0.334626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.285105E+10 | 0.126716E+10 | 0.333325E+10 | 0.192019E+10 | 0.141306E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114880E+11 | 0.605894E+10 | 0.866387E+10 | 0.454830E+10 | 0.427267E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199077E+11 | 0.793732E+10 | 0.175257E+11 | 0.144168E+11 | 0.310892E+10 | 0.00 | 0.00 |
February | 0.170291E+11 | 0.748982E+10 | 0.151836E+11 | 0.121053E+11 | 0.307827E+10 | 0.00 | 0.00 |
March | 0.140767E+11 | 0.658882E+10 | 0.123939E+11 | 0.815448E+10 | 0.423942E+10 | 0.00 | 0.00 |
April | 0.805579E+10 | 0.561940E+10 | 0.776827E+10 | 0.312365E+10 | 0.464462E+10 | 0.00 | 0.00 |
May | 0.830631E+10 | 0.379766E+10 | 0.735605E+10 | 0.134831E+10 | 0.600774E+10 | 0.00 | 0.00 |
June | 0.933528E+10 | 0.207811E+10 | 0.656326E+10 | 0.119958E+10 | 0.536368E+10 | 0.00 | 0.00 |
July | 0.100630E+11 | 0.200522E+10 | 0.705994E+10 | 0.126424E+10 | 0.579570E+10 | 0.00 | 0.00 |
August | 0.128909E+11 | 0.226552E+10 | 0.898874E+10 | 0.375763E+10 | 0.523111E+10 | 0.00 | 0.00 |
September | 0.150593E+11 | 0.326528E+10 | 0.111918E+11 | 0.624498E+10 | 0.494685E+10 | 0.00 | 0.00 |
October | 0.166013E+11 | 0.657267E+10 | 0.138282E+11 | 0.981145E+10 | 0.401679E+10 | 0.00 | 0.00 |
November | 0.188919E+11 | 0.733949E+10 | 0.163043E+11 | 0.129969E+11 | 0.330741E+10 | 0.00 | 0.00 |
December | 0.179010E+11 | 0.888463E+10 | 0.161109E+11 | 0.130399E+11 | 0.307095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.168118E+12 | 0.638439E+11 | 0.140275E+12 | 0.874632E+11 | 0.528115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.805579E+10 | 0.200522E+10 | 0.656326E+10 | 0.119958E+10 | 0.307095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.199077E+11 | 0.888463E+10 | 0.175257E+11 | 0.144168E+11 | 0.600774E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.386866E+10 | 0.558464E+10 | 0.406084E+10 | 0.257317E+10 | 0.148767E+10 | 0.00 | 0.00 |
February | 0.414896E+10 | 0.521847E+10 | 0.442292E+10 | 0.274090E+10 | 0.168202E+10 | 0.00 | 0.00 |
March | 0.569048E+10 | 0.448415E+10 | 0.573384E+10 | 0.316349E+10 | 0.257035E+10 | 0.00 | 0.00 |
April | 0.494030E+10 | 0.377031E+10 | 0.522452E+10 | 0.221197E+10 | 0.301255E+10 | 0.00 | 0.00 |
May | 0.736867E+10 | 0.256343E+10 | 0.659856E+10 | 0.232624E+10 | 0.427232E+10 | 0.00 | 0.00 |
June | 0.104725E+11 | 0.150108E+10 | 0.781011E+10 | 0.375775E+10 | 0.405236E+10 | 0.00 | 0.00 |
July | 0.882541E+10 | 0.142706E+10 | 0.657550E+10 | 0.240849E+10 | 0.416702E+10 | 0.00 | 0.00 |
August | 0.909557E+10 | 0.159134E+10 | 0.686296E+10 | 0.339040E+10 | 0.347256E+10 | 0.00 | 0.00 |
September | 0.747316E+10 | 0.222147E+10 | 0.588909E+10 | 0.282421E+10 | 0.306488E+10 | 0.00 | 0.00 |
October | 0.550318E+10 | 0.444585E+10 | 0.511943E+10 | 0.292613E+10 | 0.219329E+10 | 0.00 | 0.00 |
November | 0.396530E+10 | 0.501885E+10 | 0.406525E+10 | 0.246811E+10 | 0.159714E+10 | 0.00 | 0.00 |
December | 0.294039E+10 | 0.625864E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.742925E+11 | 0.440853E+11 | 0.657561E+11 | 0.327952E+11 | 0.329609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294039E+10 | 0.142706E+10 | 0.339306E+10 | 0.200437E+10 | 0.138869E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104725E+11 | 0.625864E+10 | 0.781011E+10 | 0.375775E+10 | 0.427232E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.414065E+11 | -0.409636E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442896658.7 | 60.05 | 0.00 | 0.00 |
February | 0.380771E+11 | -0.376755E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401580319.3 | 60.05 | 0.00 | 0.00 |
March | 0.441230E+11 | -0.436775E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445542940.0 | 60.05 | 0.00 | 0.00 |
April | 0.385059E+11 | -0.380765E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429429376.9 | 60.05 | 0.00 | 0.00 |
May | 0.389034E+11 | -0.384611E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442311968.8 | 60.05 | 0.00 | 0.00 |
June | 0.363241E+11 | -0.359163E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -407762723.5 | 60.05 | 0.00 | 0.00 |
July | 0.330386E+11 | -0.326323E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -406249895.5 | 60.05 | 0.00 | 0.00 |
August | 0.355960E+11 | -0.351690E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -426939765.9 | 60.05 | 0.00 | 0.00 |
September | 0.329257E+11 | -0.325077E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -418011858.0 | 60.05 | 0.00 | 0.00 |
October | 0.355856E+11 | -0.351455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440047833.5 | 60.05 | 0.00 | 0.00 |
November | 0.370118E+11 | -0.365849E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -426939529.9 | 60.05 | 0.00 | 0.00 |
December | 0.389118E+11 | -0.384693E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442459705.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.450409E+12 | -0.445279E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.513017E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.329257E+11 | -0.436775E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -445542940.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.441230E+11 | -0.325077E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -401580319.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10579.33 | 39.79 | 274.33 | 267.83 | 5649.13 | 35.45 | 240.67 | 259.83 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14143.61 | 39.57 | 241.00 | 264.50 | 2329.15 | 25.66 | 134.00 | 244.00 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-06:00 | 2819.79 | 20.91 | 99.83 | 327.83 | 1599.18 | 21.97 | 169.33 | 293.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2173.24 | 20.61 | 114.67 | 341.67 | 1250.58 | 22.00 | 204.67 | 303.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1954.72 | 20.68 | 184.33 | 395.17 | 1069.48 | 22.08 | 306.50 | 358.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1601.36 | 20.16 | 102.67 | 394.33 | 953.05 | 21.62 | 260.17 | 353.67 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 1786.69 | 20.31 | 158.50 | 397.83 | 1004.26 | 21.73 | 293.50 | 359.50 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1910.74 | 20.07 | 113.83 | 371.83 | 1154.38 | 21.48 | 232.00 | 337.83 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3058.92 | 21.84 | 150.00 | 333.83 | 1415.75 | 21.95 | 218.50 | 305.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13774.22 | 37.07 | 241.50 | 299.33 | 1956.38 | 22.56 | 175.67 | 277.33 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12102.80 | 39.90 | 256.00 | 265.67 | 3589.39 | 30.19 | 183.67 | 242.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9916.11 | 40.21 | 250.67 | 258.50 | 7966.35 | 40.75 | 251.00 | 248.17 |
Annual Sum or Average | 3902.00 | 0.50 | 5432.28 | 26.81 | 2187.33 | 3918.33 | 2217.50 | 24.85 | 2669.67 | 3583.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1601.36 | 20.07 | 99.83 | 258.50 | 953.05 | 21.48 | 134.00 | 242.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14143.61 | 40.21 | 274.33 | 397.83 | 7966.35 | 40.75 | 306.50 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2639.58 | 24.99 | 116.17 | 242.33 | 1497.01 | 24.65 | 126.50 | 211.50 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3974.32 | 25.33 | 90.17 | 253.67 | 2351.51 | 25.19 | 91.00 | 209.00 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3811.52 | 24.69 | 99.50 | 322.00 | 2115.51 | 24.82 | 124.67 | 283.67 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4226.70 | 25.34 | 105.83 | 343.67 | 1836.08 | 24.48 | 158.33 | 305.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3346.77 | 24.25 | 130.67 | 402.50 | 1808.78 | 24.72 | 265.33 | 369.50 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 3997.92 | 24.73 | 126.83 | 407.17 | 2270.52 | 25.22 | 195.17 | 378.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3579.04 | 24.10 | 126.83 | 408.83 | 1920.67 | 24.47 | 247.83 | 376.33 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:40 | 4909.29 | 25.30 | 136.17 | 375.50 | 1954.29 | 24.08 | 179.33 | 342.17 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 4031.21 | 25.55 | 132.33 | 334.50 | 1591.84 | 24.26 | 178.83 | 310.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3703.23 | 25.16 | 89.17 | 291.33 | 2066.10 | 25.21 | 136.33 | 254.67 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:39 | 2555.42 | 24.17 | 98.67 | 245.17 | 1338.87 | 23.86 | 112.17 | 206.17 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-07:40 | 2664.96 | 25.60 | 109.17 | 236.33 | 1550.19 | 25.28 | 115.00 | 199.67 |
Annual Sum or Average | 3902.00 | 0.50 | 3682.19 | 24.89 | 1361.50 | 3863.00 | 1873.08 | 24.67 | 1930.50 | 3447.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2555.42 | 24.10 | 89.17 | 236.33 | 1338.87 | 23.86 | 91.00 | 199.67 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4909.29 | 25.60 | 136.17 | 408.83 | 2351.51 | 25.28 | 265.33 | 378.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-08:50 | 595.47 | 16.25 | 0.00 | 224.33 | 393.82 | 18.18 | 11.67 | 167.67 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 713.80 | 17.69 | 0.00 | 243.67 | 488.79 | 19.55 | 22.50 | 182.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 918.74 | 18.90 | 0.33 | 317.33 | 592.96 | 20.47 | 71.00 | 264.33 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1213.87 | 20.07 | 27.83 | 346.33 | 717.50 | 21.43 | 162.67 | 303.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1423.02 | 20.80 | 122.17 | 409.33 | 810.28 | 22.18 | 309.50 | 381.17 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1602.22 | 23.20 | 187.67 | 418.17 | 891.42 | 24.57 | 330.17 | 404.50 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1507.30 | 21.71 | 150.17 | 420.50 | 822.86 | 22.09 | 310.33 | 391.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1188.66 | 19.92 | 56.33 | 380.67 | 732.37 | 21.30 | 198.50 | 347.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 1002.45 | 19.37 | 5.83 | 332.17 | 630.13 | 20.85 | 129.83 | 291.67 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 862.02 | 18.69 | 0.00 | 283.83 | 575.96 | 20.42 | 45.50 | 221.67 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:50 | 670.09 | 17.22 | 0.00 | 232.33 | 451.43 | 19.12 | 22.67 | 174.50 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:30 | 613.94 | 16.88 | 0.00 | 220.50 | 402.67 | 18.83 | 9.00 | 158.17 |
Annual Sum or Average | 3902.00 | 0.50 | 1092.82 | 19.59 | 550.33 | 3829.17 | 657.22 | 21.05 | 1623.33 | 3288.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 595.47 | 16.25 | 0.00 | 220.50 | 393.82 | 18.18 | 9.00 | 158.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 1602.22 | 23.20 | 187.67 | 420.50 | 891.42 | 24.57 | 330.17 | 404.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:50 | 2984.48 | 26.02 | 126.83 | 253.83 | 1770.90 | 25.65 | 133.50 | 224.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3172.19 | 25.66 | 93.00 | 257.67 | 1734.92 | 25.39 | 95.67 | 218.17 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:19 | 3608.81 | 25.18 | 118.33 | 330.50 | 2034.70 | 25.33 | 141.67 | 297.17 |
April | 296.67 | 0.49 | 0.48 | 03-APR-09:39 | 3431.61 | 23.90 | 96.00 | 349.33 | 1528.21 | 23.39 | 153.83 | 314.50 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2940.01 | 21.32 | 78.33 | 400.17 | 1535.44 | 21.42 | 232.50 | 369.50 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:49 | 3496.73 | 18.83 | 12.67 | 405.17 | 1951.98 | 21.15 | 168.83 | 380.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 3001.71 | 21.01 | 72.83 | 408.00 | 1610.09 | 21.23 | 213.83 | 380.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:10 | 3872.10 | 21.95 | 85.67 | 381.17 | 1723.36 | 21.18 | 141.00 | 358.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 3390.09 | 24.80 | 134.33 | 337.17 | 1823.84 | 24.99 | 184.00 | 312.50 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:00 | 4392.26 | 27.03 | 109.17 | 296.50 | 1699.80 | 25.21 | 133.33 | 262.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 3033.33 | 26.56 | 116.00 | 255.17 | 1718.15 | 26.23 | 130.00 | 218.00 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-08:30 | 2499.97 | 26.36 | 113.50 | 245.17 | 1423.68 | 25.93 | 125.00 | 218.00 |
Annual Sum or Average | 3902.00 | 0.50 | 3323.52 | 23.55 | 1156.67 | 3919.83 | 1716.35 | 23.53 | 1853.17 | 3554.50 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2499.97 | 18.83 | 12.67 | 245.17 | 1423.68 | 21.15 | 95.67 | 218.00 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4392.26 | 27.03 | 134.33 | 408.00 | 2034.70 | 26.23 | 232.50 | 380.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.49 | 0.48 | 01-JAN-07:49 | 10685.00 | 39.40 | 274.17 | 267.83 | 5820.47 | 33.44 | 205.33 | 261.50 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14277.76 | 39.10 | 241.00 | 264.83 | 2507.54 | 21.18 | 69.33 | 246.33 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-06:00 | 2974.27 | 14.41 | 10.33 | 330.00 | 1728.54 | 17.52 | 10.00 | 296.83 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2216.62 | 14.45 | 0.00 | 341.83 | 1340.08 | 17.94 | 6.50 | 307.17 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1982.31 | 14.59 | 0.00 | 395.50 | 1139.40 | 18.05 | 0.00 | 363.83 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1633.90 | 14.36 | 0.00 | 394.67 | 1018.56 | 17.91 | 0.00 | 358.67 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 1815.30 | 14.32 | 0.00 | 398.33 | 1071.00 | 17.79 | 0.00 | 363.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1957.77 | 14.05 | 0.00 | 372.00 | 1239.49 | 17.58 | 4.50 | 342.17 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3122.01 | 15.92 | 29.50 | 334.33 | 1523.05 | 17.64 | 3.00 | 308.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13902.78 | 36.28 | 240.33 | 300.67 | 2120.24 | 17.73 | 6.83 | 280.17 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12219.63 | 39.50 | 256.00 | 265.83 | 3793.12 | 27.15 | 131.83 | 246.67 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10027.02 | 39.81 | 250.67 | 258.50 | 8141.75 | 40.34 | 247.17 | 249.67 |
Annual Sum or Average | 3902.00 | 0.50 | 5506.83 | 22.61 | 1302.00 | 3924.33 | 2333.48 | 21.17 | 684.50 | 3624.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1633.90 | 14.05 | 0.00 | 258.50 | 1018.56 | 17.52 | 0.00 | 246.33 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14277.76 | 39.81 | 274.17 | 398.33 | 8141.75 | 40.34 | 247.17 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2685.90 | 22.69 | 99.83 | 244.33 | 1554.80 | 22.93 | 82.67 | 215.83 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 4038.64 | 22.76 | 84.33 | 254.33 | 2428.35 | 23.21 | 64.17 | 215.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3892.10 | 21.69 | 83.50 | 322.50 | 2204.36 | 22.48 | 61.67 | 288.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4288.56 | 22.48 | 96.17 | 343.83 | 1924.28 | 21.93 | 52.50 | 311.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:40 | 3391.03 | 21.05 | 111.67 | 403.00 | 1889.40 | 22.26 | 83.83 | 372.50 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 4035.22 | 20.66 | 109.00 | 407.33 | 2366.78 | 22.74 | 91.67 | 381.00 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-04:00 | 3630.30 | 20.90 | 116.33 | 409.17 | 2008.16 | 21.94 | 84.67 | 380.33 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:40 | 4967.40 | 22.32 | 131.00 | 375.67 | 2050.25 | 21.48 | 70.83 | 346.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 4074.79 | 21.87 | 108.33 | 334.50 | 1676.92 | 21.75 | 61.50 | 314.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3767.37 | 22.31 | 79.83 | 292.33 | 2150.51 | 23.08 | 56.17 | 260.67 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:39 | 2571.46 | 20.75 | 70.50 | 246.00 | 1403.86 | 21.89 | 66.00 | 209.33 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-07:40 | 2708.57 | 23.38 | 93.17 | 237.17 | 1605.38 | 23.65 | 85.33 | 204.00 |
Annual Sum or Average | 3902.00 | 0.50 | 3732.74 | 21.79 | 1183.67 | 3870.17 | 1955.04 | 22.37 | 861.00 | 3500.17 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2571.46 | 20.66 | 70.50 | 237.17 | 1403.86 | 21.48 | 52.50 | 204.00 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4967.40 | 23.38 | 131.00 | 409.17 | 2428.35 | 23.65 | 91.67 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-08:50 | 605.89 | 10.47 | 0.00 | 225.50 | 419.79 | 14.30 | 0.00 | 179.00 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 729.56 | 12.04 | 0.00 | 243.83 | 522.05 | 15.89 | 0.00 | 190.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 938.16 | 13.54 | 0.00 | 317.67 | 632.94 | 17.13 | 0.00 | 271.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1236.42 | 14.68 | 0.00 | 346.67 | 764.94 | 18.15 | 4.83 | 307.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1489.72 | 15.07 | 2.33 | 410.00 | 862.95 | 18.58 | 9.17 | 384.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1635.23 | 18.38 | 64.83 | 418.50 | 951.74 | 21.60 | 74.67 | 407.17 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:19 | 1536.54 | 16.36 | 29.33 | 420.83 | 885.87 | 19.74 | 39.50 | 396.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1239.66 | 14.52 | 0.00 | 383.00 | 782.14 | 18.08 | 12.83 | 352.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 1023.06 | 14.04 | 0.00 | 332.67 | 672.18 | 17.58 | 0.00 | 298.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:49 | 879.28 | 13.32 | 0.00 | 285.17 | 614.60 | 17.02 | 0.00 | 231.33 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 682.05 | 11.52 | 0.00 | 232.83 | 481.30 | 15.35 | 0.00 | 181.67 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:20 | 622.87 | 11.09 | 0.00 | 221.33 | 428.69 | 14.94 | 0.00 | 170.17 |
Annual Sum or Average | 3902.00 | 0.50 | 1121.18 | 14.15 | 96.50 | 3838.00 | 701.96 | 17.72 | 141.00 | 3370.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 605.89 | 10.47 | 0.00 | 221.33 | 419.79 | 14.30 | 0.00 | 170.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 1635.23 | 18.38 | 64.83 | 420.83 | 951.74 | 21.60 | 74.67 | 407.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:39 | 3033.29 | 23.85 | 109.00 | 254.17 | 1829.71 | 24.04 | 95.83 | 227.83 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3239.31 | 23.03 | 81.50 | 258.83 | 1813.74 | 23.35 | 62.50 | 224.33 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:19 | 3678.14 | 22.44 | 99.83 | 330.50 | 2114.56 | 23.14 | 74.17 | 300.83 |
April | 296.67 | 0.49 | 0.48 | 03-APR-09:39 | 3489.66 | 20.84 | 85.17 | 349.67 | 1605.43 | 20.66 | 38.33 | 318.00 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-06:19 | 3653.94 | 18.84 | 82.17 | 401.17 | 1611.57 | 18.17 | 0.00 | 372.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:49 | 3533.70 | 14.20 | 1.83 | 405.50 | 2040.72 | 17.76 | 0.00 | 383.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 3034.76 | 17.12 | 56.83 | 408.00 | 1685.48 | 17.94 | 0.17 | 383.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:10 | 3927.49 | 18.44 | 79.17 | 381.17 | 1803.89 | 17.92 | 7.83 | 361.67 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 3447.31 | 21.70 | 109.83 | 336.83 | 1899.40 | 22.69 | 80.17 | 314.50 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:00 | 4403.67 | 23.44 | 93.83 | 296.67 | 1784.34 | 23.02 | 54.50 | 268.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 3084.97 | 24.31 | 98.50 | 255.67 | 1784.70 | 24.54 | 86.00 | 221.00 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-08:20 | 2544.89 | 24.22 | 96.50 | 245.17 | 1480.43 | 24.36 | 86.00 | 223.00 |
Annual Sum or Average | 3902.00 | 0.50 | 3442.36 | 20.43 | 994.17 | 3923.33 | 1792.15 | 20.94 | 585.50 | 3599.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2544.89 | 14.20 | 1.83 | 245.17 | 1480.43 | 17.76 | 0.00 | 221.00 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4403.67 | 24.31 | 109.83 | 408.00 | 2114.56 | 24.54 | 95.83 | 383.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.49 | 0.48 | 01-JAN-07:49 | 10686.07 | 39.39 | 274.17 | 267.83 | 5822.39 | 33.43 | 205.33 | 261.50 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14279.23 | 39.09 | 241.00 | 264.83 | 2509.42 | 21.16 | 69.33 | 246.33 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-06:00 | 2976.87 | 14.38 | 10.33 | 330.00 | 1730.45 | 17.51 | 9.67 | 297.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2219.65 | 14.43 | 0.00 | 341.83 | 1341.97 | 17.93 | 6.33 | 307.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:00 | 1985.27 | 14.56 | 0.00 | 395.50 | 1141.19 | 18.03 | 0.00 | 363.83 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1635.82 | 14.33 | 0.00 | 394.67 | 1019.87 | 17.90 | 0.00 | 358.67 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 1817.83 | 14.29 | 0.00 | 398.33 | 1072.58 | 17.78 | 0.00 | 363.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1960.10 | 14.02 | 0.00 | 372.00 | 1241.02 | 17.56 | 4.50 | 342.17 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3124.95 | 15.89 | 29.50 | 334.33 | 1525.02 | 17.62 | 2.83 | 308.67 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13905.13 | 36.27 | 240.33 | 300.67 | 2122.44 | 17.71 | 6.83 | 280.50 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12220.73 | 39.49 | 256.00 | 265.83 | 3795.33 | 27.14 | 131.83 | 246.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 10027.92 | 39.80 | 250.67 | 258.50 | 8143.87 | 40.34 | 247.17 | 249.83 |
Annual Sum or Average | 3902.00 | 0.50 | 5509.02 | 22.58 | 1302.00 | 3924.33 | 2335.29 | 21.16 | 683.83 | 3626.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1635.82 | 14.02 | 0.00 | 258.50 | 1019.87 | 17.51 | 0.00 | 246.33 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14279.23 | 39.80 | 274.17 | 398.33 | 8143.87 | 40.34 | 247.17 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-07:40 | 2686.48 | 22.67 | 99.83 | 244.33 | 1555.61 | 22.91 | 82.50 | 215.83 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 4039.16 | 22.73 | 84.33 | 254.33 | 2429.31 | 23.20 | 64.17 | 215.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3893.04 | 21.66 | 83.50 | 322.50 | 2205.64 | 22.47 | 61.67 | 288.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4290.43 | 22.45 | 96.17 | 344.00 | 1926.03 | 21.92 | 52.50 | 311.50 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:40 | 3393.45 | 21.02 | 111.67 | 403.00 | 1891.34 | 22.25 | 83.83 | 372.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 4037.00 | 20.63 | 109.00 | 407.33 | 2368.51 | 22.73 | 91.67 | 381.00 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-04:00 | 3632.51 | 20.87 | 116.33 | 409.17 | 2010.02 | 21.93 | 84.67 | 380.33 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:40 | 4969.13 | 22.29 | 131.00 | 375.83 | 2151.09 | 21.65 | 73.83 | 346.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 4076.27 | 21.84 | 108.33 | 334.50 | 2330.39 | 23.42 | 86.83 | 314.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3768.21 | 22.28 | 79.83 | 292.50 | 2151.88 | 23.06 | 56.17 | 260.83 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:39 | 2572.09 | 20.72 | 70.50 | 246.17 | 1404.83 | 21.87 | 65.50 | 209.83 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-07:40 | 2709.14 | 23.35 | 93.17 | 237.17 | 1606.27 | 23.63 | 85.17 | 204.17 |
Annual Sum or Average | 3902.00 | 0.50 | 3734.17 | 21.76 | 1183.67 | 3870.83 | 2025.68 | 22.53 | 888.50 | 3501.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2572.09 | 20.63 | 70.50 | 237.17 | 1404.83 | 21.65 | 52.50 | 204.17 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4969.13 | 23.35 | 131.00 | 409.17 | 2429.31 | 23.63 | 91.67 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-08:50 | 606.19 | 10.44 | 0.00 | 225.50 | 420.21 | 14.28 | 0.00 | 179.17 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 729.85 | 12.01 | 0.00 | 244.00 | 522.52 | 15.87 | 0.00 | 190.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 938.81 | 13.50 | 0.00 | 317.67 | 633.62 | 17.11 | 0.00 | 271.83 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1237.62 | 14.65 | 0.00 | 346.67 | 765.93 | 18.14 | 4.50 | 307.83 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1491.35 | 15.04 | 2.33 | 410.00 | 864.18 | 18.57 | 8.67 | 384.83 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1636.46 | 18.35 | 64.83 | 418.50 | 952.84 | 21.58 | 73.83 | 407.33 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:19 | 1538.06 | 16.33 | 29.33 | 420.83 | 887.06 | 19.72 | 39.00 | 396.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1240.60 | 14.49 | 0.00 | 383.00 | 783.04 | 18.06 | 12.83 | 352.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 1023.86 | 14.01 | 0.00 | 332.83 | 672.96 | 17.57 | 0.00 | 298.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:49 | 879.67 | 13.29 | 0.00 | 285.50 | 615.19 | 17.00 | 0.00 | 232.00 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 682.30 | 11.48 | 0.00 | 232.83 | 481.75 | 15.33 | 0.00 | 181.83 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:20 | 623.15 | 11.06 | 0.00 | 221.33 | 429.13 | 14.92 | 0.00 | 170.17 |
Annual Sum or Average | 3902.00 | 0.50 | 1122.06 | 14.12 | 96.50 | 3838.67 | 702.79 | 17.71 | 138.83 | 3372.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 606.19 | 10.44 | 0.00 | 221.33 | 420.21 | 14.28 | 0.00 | 170.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 1636.46 | 18.35 | 64.83 | 420.83 | 952.84 | 21.58 | 73.83 | 407.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:39 | 3033.94 | 23.82 | 109.00 | 254.17 | 1830.53 | 24.03 | 95.67 | 228.17 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3239.90 | 23.00 | 81.50 | 258.83 | 1814.69 | 23.33 | 62.33 | 224.67 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:19 | 3679.33 | 22.41 | 99.83 | 330.50 | 2115.92 | 23.13 | 74.17 | 301.33 |
April | 296.67 | 0.49 | 0.48 | 03-APR-09:39 | 3491.63 | 20.81 | 85.17 | 349.67 | 1607.10 | 20.65 | 38.33 | 318.00 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-06:19 | 3656.58 | 18.81 | 82.17 | 401.17 | 1613.54 | 18.15 | 0.00 | 372.67 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:49 | 3535.53 | 14.16 | 1.83 | 405.50 | 2042.40 | 17.74 | 0.00 | 383.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:00 | 3037.12 | 17.09 | 56.83 | 408.17 | 1687.31 | 17.93 | 0.00 | 383.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:10 | 3929.02 | 18.41 | 79.17 | 381.17 | 1805.37 | 17.91 | 7.83 | 361.67 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 3448.94 | 21.67 | 109.83 | 337.00 | 1900.97 | 22.68 | 80.17 | 314.67 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:00 | 4404.62 | 23.41 | 93.83 | 296.83 | 1785.56 | 23.00 | 54.50 | 269.00 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 3085.56 | 24.28 | 98.50 | 255.67 | 1785.62 | 24.53 | 85.67 | 221.17 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-08:20 | 2545.45 | 24.20 | 96.50 | 245.17 | 1481.28 | 24.34 | 86.00 | 223.17 |
Annual Sum or Average | 3902.00 | 0.50 | 3443.87 | 20.40 | 994.17 | 3923.83 | 1793.58 | 20.92 | 584.67 | 3601.17 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2545.45 | 14.16 | 1.83 | 245.17 | 1481.28 | 17.74 | 0.00 | 221.17 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4404.62 | 24.28 | 109.83 | 408.17 | 2115.92 | 24.53 | 95.67 | 383.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113371E+11 | 52713.22 | 05-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107777E+11 | 35463.39 | 11-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612358E+10 | 34989.24 | 04-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317281E+10 | 32235.72 | 17-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.257294E+09 | 15904.49 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327441E+09 | 19540.51 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479424E+10 | 38179.98 | 30-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712863E+10 | 42120.40 | 29-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164673E+11 | 61270.01 | 22-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164673E+11 | 61270.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208975E+09 | 14759.89 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197176E+09 | 14782.26 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7312236.26 | 13995.61 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1083492.72 | 631.97 | 03-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44969970.97 | 14766.02 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77159423.30 | 14781.33 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.525629E+09 | 14790.23 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525629E+09 | 14790.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132611E+09 | 13972.90 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181713E+09 | 13994.17 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15862961.91 | 13636.37 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11269424.84 | 8877.57 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58567890.93 | 13974.83 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89537299.10 | 13990.56 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414602E+09 | 14018.15 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.904164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414602E+09 | 14018.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227454E+09 | 19324.02 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370968E+09 | 19341.35 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67232301.95 | 18881.96 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76824001.54 | 19422.34 | 24-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166729E+09 | 19330.06 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146816E+09 | 19544.50 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504931E+09 | 19385.77 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504931E+09 | 19544.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20417194.53 | 12070.49 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5322511.94 | 6259.60 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9976965.71 | 8088.78 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35716672.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20417194.53 | 12070.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144256E+12 | 480983.56 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141041E+12 | 394144.36 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927313E+11 | 315111.76 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591573E+11 | 307090.95 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.517282E+10 | 247765.53 | 02-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.425519E+10 | 344222.08 | 21-SEP-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.706898E+11 | 355394.40 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116231E+12 | 397066.45 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206488E+12 | 552134.78 | 21-DEC-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840023E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206488E+12 | 552134.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182937E+09 | 400146.67 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.918997E+09 | 515007.12 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.918997E+09 | 515007.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196341E+11 | 132190.72 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233420E+11 | 143289.74 | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.989269E+10 | 142011.96 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.498417E+10 | 142805.77 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161931E+09 | 117134.34 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103643E+09 | 74884.67 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.740042E+10 | 131663.23 | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138745E+11 | 143221.08 | 15-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375121E+11 | 148123.04 | 23-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.375121E+11 | 148123.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.815975E+10 | 179385.80 | 18-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105446E+11 | 179333.97 | 21-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.462525E+10 | 179278.36 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257878E+10 | 179143.24 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49577873.49 | 85996.33 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36775713.66 | 41282.12 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452232E+10 | 179294.28 | 30-OCT-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677575E+10 | 179298.24 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182652E+11 | 180651.53 | 21-DEC-11:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182652E+11 | 180651.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.614823E+10 | 200965.23 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114473E+11 | 201117.52 | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.626253E+10 | 201977.33 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422168E+10 | 201143.10 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197016E+09 | 122218.12 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78778069.49 | 45151.18 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602870E+10 | 201387.07 | 25-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.589060E+10 | 201044.49 | 01-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161612E+11 | 201029.59 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161612E+11 | 201977.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.655486E+10 | 181337.52 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.832067E+10 | 181270.21 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343612E+10 | 181077.00 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210054E+10 | 181086.56 | 24-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44205252.29 | 47091.77 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61579674.59 | 42334.82 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360729E+10 | 181151.95 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490612E+10 | 181134.99 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145922E+11 | 181206.78 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145922E+11 | 181337.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176244E+11 | 53592.09 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171969E+11 | 41506.45 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117951E+11 | 35806.59 | 29-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.751321E+10 | 37042.21 | 17-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.890725E+09 | 18566.19 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1688181.92 | 1977.70 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.592715E+09 | 21268.39 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.917686E+10 | 43801.07 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143739E+11 | 46795.78 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237589E+11 | 56602.17 | 23-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237589E+11 | 56602.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.370371E+10 | 76237.32 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374431E+10 | 75837.38 | 06-FEB-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170794E+10 | 76082.92 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183090E+10 | 76069.26 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114705E+09 | 75418.49 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135721E+10 | 75653.32 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192275E+10 | 76277.02 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579101E+10 | 75652.01 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579101E+10 | 76277.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.589763E+10 | 15851.18 | 05-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588396E+10 | 15202.01 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344440E+10 | 15240.63 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216241E+10 | 15167.42 | 03-APR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185148E+09 | 15154.64 | 01-MAY-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87688199.80 | 15144.50 | 23-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257150E+10 | 15236.63 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422969E+10 | 15239.87 | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.870641E+10 | 17289.70 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.870641E+10 | 17289.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269719E+10 | 20390.29 | 19-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284587E+10 | 20376.87 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172897E+10 | 20350.76 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116264E+10 | 20355.10 | 26-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77514492.14 | 20359.88 | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37462614.30 | 14137.84 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155002E+10 | 20432.00 | 28-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207347E+10 | 20359.69 | 24-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462803E+10 | 20365.21 | 23-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.462803E+10 | 20432.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243050E+10 | 22108.96 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326831E+10 | 22039.43 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243446E+10 | 22118.18 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183529E+10 | 22102.33 | 03-APR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194473E+09 | 21949.36 | 01-MAY-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64297670.56 | 19235.49 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203986E+10 | 22112.27 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210967E+10 | 22039.61 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455771E+10 | 22042.38 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.455771E+10 | 22118.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220040E+10 | 21603.54 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225328E+10 | 21600.12 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132022E+10 | 21606.26 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.844439E+09 | 21603.99 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78873803.74 | 21598.06 | 01-MAY-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37842891.03 | 11853.14 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114186E+10 | 21591.91 | 25-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160107E+10 | 21609.73 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362539E+10 | 21638.29 | 23-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362539E+10 | 21638.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225952E+10 | 26258.08 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226668E+10 | 20739.70 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.711079E+09 | 18544.51 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82975546.06 | 17120.36 | 03-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6172551.78 | 6969.77 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67.89 | 0.40 | 10-JUN-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3204535.28 | 10681.69 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200744E+09 | 15564.72 | 31-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.472747E+09 | 22570.51 | 30-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366821E+10 | 31614.42 | 20-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.967134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366821E+10 | 31614.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.139367E+11 | 0.139367E+11 | 67869.72 | 19-JAN-15:00 | 67869.72 | 0.00 |
February | 0.00 | 0.00 | 0.127235E+11 | 0.127235E+11 | 65716.94 | 17-FEB-15:00 | 65716.94 | 0.00 |
March | 0.00 | 0.00 | 0.154410E+11 | 0.154410E+11 | 98274.51 | 13-MAR-16:00 | 98274.51 | 0.00 |
April | 0.00 | 0.00 | 0.117473E+11 | 0.117473E+11 | 79952.20 | 19-APR-13:30 | 79952.20 | 0.01 |
May | 0.00 | 0.00 | 0.342962E+11 | 0.342962E+11 | 109630.48 | 17-MAY-13:30 | 109630.48 | 0.06 |
June | 0.00 | 0.00 | 0.121447E+12 | 0.121148E+12 | 184073.72 | 26-JUN-14:53 | 184073.72 | 0.33 |
July | 0.00 | 0.00 | 0.137324E+12 | 0.132943E+12 | 175291.26 | 18-JUL-11:43 | 175291.26 | 0.40 |
August | 0.00 | 0.00 | 0.123083E+12 | 0.122002E+12 | 165735.86 | 16-AUG-09:23 | 165735.86 | 0.47 |
September | 0.00 | 0.00 | 0.770234E+11 | 0.770234E+11 | 137227.55 | 11-SEP-14:30 | 137227.55 | 0.09 |
October | 0.00 | 0.00 | 0.199038E+11 | 0.199038E+11 | 120332.71 | 10-OCT-15:20 | 120332.71 | 0.00 |
November | 0.00 | 0.00 | 0.154334E+11 | 0.154334E+11 | 82992.56 | 06-NOV-14:00 | 82992.56 | 0.00 |
December | 0.00 | 0.00 | 0.159174E+11 | 0.159174E+11 | 70093.13 | 13-DEC-15:00 | 70093.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.598277E+12 | 0.592516E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.117473E+11 | 0.117473E+11 | 65716.94 | 65716.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137324E+12 | 0.132943E+12 | 184073.72 | 184073.72 | 0.47 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.838787E+11 | 0.838787E+11 | 642462.95 | 20-JAN-15:05 | 642462.95 | 0.00 |
February | 0.00 | 0.00 | 0.719761E+11 | 0.719761E+11 | 519264.21 | 27-FEB-15:05 | 519264.21 | 0.00 |
March | 0.00 | 0.00 | 0.118505E+12 | 0.118505E+12 | 801014.26 | 13-MAR-15:50 | 801014.26 | 0.01 |
April | 0.00 | 0.00 | 0.965082E+11 | 0.965082E+11 | 604267.40 | 20-APR-13:00 | 604267.40 | 0.01 |
May | 0.00 | 0.00 | 0.292364E+12 | 0.292364E+12 | 993008.15 | 16-MAY-14:05 | 993008.15 | 0.06 |
June | 0.00 | 0.00 | 0.931107E+12 | 0.929768E+12 | 1553896.27 | 26-JUN-14:13 | 1553896.27 | 0.30 |
July | 0.00 | 0.00 | 0.935541E+12 | 0.918672E+12 | 1270307.30 | 17-JUL-10:30 | 1270307.30 | 0.31 |
August | 0.00 | 0.00 | 0.902272E+12 | 0.899382E+12 | 1313125.32 | 16-AUG-15:10 | 1313125.32 | 0.33 |
September | 0.00 | 0.00 | 0.630126E+12 | 0.630126E+12 | 1161776.72 | 12-SEP-16:00 | 1161776.72 | 0.08 |
October | 0.00 | 0.00 | 0.223757E+12 | 0.223757E+12 | 987231.47 | 11-OCT-14:05 | 987231.47 | 0.01 |
November | 0.00 | 0.00 | 0.110504E+12 | 0.110504E+12 | 768168.70 | 07-NOV-15:05 | 768168.70 | 0.00 |
December | 0.00 | 0.00 | 0.566342E+11 | 0.566342E+11 | 541247.86 | 01-DEC-15:05 | 541247.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.445317E+13 | 0.443207E+13 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.566342E+11 | 0.566342E+11 | 519264.21 | 519264.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.935541E+12 | 0.929768E+12 | 1553896.27 | 1553896.27 | 0.33 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.396128E+10 | 0.396128E+10 | 48963.03 | 24-JAN-15:00 | 48963.03 | 0.00 |
February | 0.00 | 0.00 | 0.391430E+10 | 0.391430E+10 | 45860.85 | 17-FEB-15:30 | 45860.85 | 0.00 |
March | 0.00 | 0.00 | 0.900666E+10 | 0.900666E+10 | 83476.84 | 13-MAR-15:40 | 83476.84 | 0.00 |
April | 0.00 | 0.00 | 0.746058E+10 | 0.746058E+10 | 65701.87 | 20-APR-13:00 | 65701.87 | 0.00 |
May | 0.00 | 0.00 | 0.296599E+11 | 0.296599E+11 | 118211.73 | 31-MAY-15:20 | 118211.73 | 0.06 |
June | 0.00 | 0.00 | 0.104572E+12 | 0.104486E+12 | 198718.28 | 26-JUN-14:53 | 198718.28 | 0.30 |
July | 0.00 | 0.00 | 0.103156E+12 | 0.101484E+12 | 161573.84 | 12-JUL-15:05 | 161573.84 | 0.32 |
August | 0.00 | 0.00 | 0.998789E+11 | 0.996158E+11 | 159716.07 | 16-AUG-15:10 | 159716.07 | 0.32 |
September | 0.00 | 0.00 | 0.652625E+11 | 0.652625E+11 | 133822.40 | 12-SEP-16:00 | 133822.40 | 0.07 |
October | 0.00 | 0.00 | 0.139819E+11 | 0.139819E+11 | 109708.93 | 11-OCT-15:00 | 109708.93 | 0.00 |
November | 0.00 | 0.00 | 0.655891E+10 | 0.655891E+10 | 63164.00 | 07-NOV-15:00 | 63164.00 | 0.00 |
December | 0.00 | 0.00 | 0.339121E+10 | 0.339121E+10 | 40836.19 | 01-DEC-14:00 | 40836.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.450805E+12 | 0.448783E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.339121E+10 | 0.339121E+10 | 40836.19 | 40836.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104572E+12 | 0.104486E+12 | 198718.28 | 198718.28 | 0.32 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.270567E+10 | 0.270567E+10 | 35726.33 | 23-JAN-13:10 | 35726.33 | 0.00 |
February | 0.00 | 0.00 | 0.228756E+09 | 0.228756E+09 | 16297.72 | 18-FEB-13:00 | 16297.72 | 0.00 |
March | 0.00 | 0.00 | 0.531894E+10 | 0.531894E+10 | 58589.98 | 13-MAR-14:00 | 58589.98 | 0.00 |
April | 0.00 | 0.00 | 0.674288E+10 | 0.674288E+10 | 39817.93 | 20-APR-13:00 | 39817.93 | 0.00 |
May | 0.00 | 0.00 | 0.202845E+11 | 0.202742E+11 | 64685.63 | 18-MAY-13:10 | 64685.63 | 0.06 |
June | 0.00 | 0.00 | 0.328398E+11 | 0.320597E+11 | 93912.30 | 28-JUN-14:00 | 93912.30 | 0.16 |
July | 0.00 | 0.00 | 0.290913E+11 | 0.234935E+11 | 103083.66 | 28-JUL-13:00 | 61915.77 | 0.09 |
August | 0.00 | 0.00 | 0.482149E+11 | 0.463505E+11 | 91644.33 | 22-AUG-12:43 | 91644.33 | 0.20 |
September | 0.00 | 0.00 | 0.397638E+11 | 0.396640E+11 | 94696.02 | 12-SEP-16:10 | 94696.02 | 0.05 |
October | 0.00 | 0.00 | 0.983681E+10 | 0.983681E+10 | 84460.85 | 10-OCT-14:00 | 84460.85 | 0.00 |
November | 0.00 | 0.00 | 0.460979E+10 | 0.460979E+10 | 58448.22 | 06-NOV-13:05 | 58448.22 | 0.00 |
December | 0.00 | 0.00 | 0.234985E+10 | 0.234985E+10 | 48746.40 | 04-DEC-12:00 | 48746.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201987E+12 | 0.193635E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.228756E+09 | 0.228756E+09 | 16297.72 | 16297.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.482149E+11 | 0.463505E+11 | 103083.66 | 94696.02 | 0.20 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102744E+11 | 0.874128E+10 | 5661.82 | 19-JAN-11:20 | 4858.61 | 0.00 |
February | 0.00 | 0.00 | 0.138837E+11 | 0.119627E+11 | 25222.53 | 18-FEB-14:00 | 25222.53 | 0.00 |
March | 0.00 | 0.00 | 0.323836E+11 | 0.309264E+11 | 239683.53 | 14-MAR-13:00 | 239683.53 | 0.00 |
April | 0.00 | 0.00 | 0.680681E+11 | 0.641576E+11 | 271669.57 | 19-APR-14:00 | 271669.57 | 0.00 |
May | 0.00 | 0.00 | 0.271148E+11 | 0.257626E+11 | 155371.21 | 31-MAY-16:00 | 142306.74 | 0.00 |
June | 0.00 | 0.00 | 0.285274E+12 | 0.256761E+12 | 346031.06 | 18-JUN-10:42 | 222672.11 | 0.00 |
July | 0.00 | 0.00 | 0.564969E+12 | 0.470585E+12 | 534951.81 | 30-JUL-12:22 | 308516.84 | 0.00 |
August | 0.00 | 0.00 | 0.799039E+12 | 0.640424E+12 | 538210.09 | 05-AUG-14:40 | 244848.83 | 0.00 |
September | 0.00 | 0.00 | 0.871397E+11 | 0.821830E+11 | 157758.99 | 11-SEP-16:00 | 144919.60 | 0.00 |
October | 0.00 | 0.00 | 0.277411E+11 | 0.260217E+11 | 239058.22 | 11-OCT-14:00 | 239058.22 | 0.00 |
November | 0.00 | 0.00 | 0.272408E+11 | 0.249832E+11 | 181950.27 | 07-NOV-15:00 | 181950.27 | 0.00 |
December | 0.00 | 0.00 | 0.344378E+11 | 0.340012E+11 | 270673.05 | 01-DEC-14:00 | 270673.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197757E+13 | 0.167651E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.102744E+11 | 0.874128E+10 | 5661.82 | 4858.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.799039E+12 | 0.640424E+12 | 538210.09 | 308516.84 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.484166E+10 | 0.483265E+10 | 3076.95 | 22-JAN-16:35 | 3076.95 | 0.00 |
February | 0.00 | 0.00 | 0.898462E+10 | 0.898056E+10 | 5010.61 | 20-FEB-16:55 | 5010.61 | 0.00 |
March | 0.00 | 0.00 | 0.155513E+11 | 0.155398E+11 | 7817.98 | 31-MAR-24:00 | 7817.98 | 0.00 |
April | 0.00 | 0.00 | 0.201195E+11 | 0.200902E+11 | 9066.46 | 08-APR-18:00 | 9066.46 | 0.00 |
May | 0.00 | 0.00 | 0.602367E+10 | 0.596528E+10 | 4171.47 | 31-MAY-24:00 | 4150.96 | 0.00 |
June | 0.00 | 0.00 | 0.114135E+11 | 0.112951E+11 | 6130.28 | 30-JUN-24:00 | 6130.28 | 0.00 |
July | 0.00 | 0.00 | 0.169684E+11 | 0.168135E+11 | 7935.69 | 31-JUL-24:00 | 7935.69 | 0.00 |
August | 0.00 | 0.00 | 0.218027E+11 | 0.216721E+11 | 9391.09 | 05-AUG-18:12 | 9335.50 | 0.00 |
September | 0.00 | 0.00 | 0.618402E+10 | 0.613856E+10 | 4038.52 | 30-SEP-24:00 | 4038.52 | 0.00 |
October | 0.00 | 0.00 | 0.107297E+11 | 0.107093E+11 | 5711.01 | 09-OCT-16:45 | 5711.01 | 0.00 |
November | 0.00 | 0.00 | 0.150483E+11 | 0.150336E+11 | 7205.06 | 05-NOV-16:13 | 7205.06 | 0.00 |
December | 0.00 | 0.00 | 0.202053E+11 | 0.202053E+11 | 8916.10 | 03-DEC-15:55 | 8916.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157873E+12 | 0.157276E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.484166E+10 | 0.483265E+10 | 3076.95 | 3076.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218027E+11 | 0.216721E+11 | 9391.09 | 9335.50 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.310609E+11 | 0.309741E+11 | 28056.85 | 23-JAN-16:40 | 28056.85 | 0.00 |
February | 0.00 | 0.00 | 0.714440E+11 | 0.714031E+11 | 46570.19 | 17-FEB-17:00 | 46336.09 | 0.00 |
March | 0.00 | 0.00 | 0.136068E+12 | 0.135953E+12 | 73281.04 | 31-MAR-23:30 | 73281.04 | 0.00 |
April | 0.00 | 0.00 | 0.180979E+12 | 0.180685E+12 | 86082.48 | 08-APR-18:00 | 86082.48 | 0.00 |
May | 0.00 | 0.00 | 0.528887E+11 | 0.523142E+11 | 39544.65 | 31-MAY-23:20 | 39077.44 | 0.00 |
June | 0.00 | 0.00 | 0.106794E+12 | 0.105619E+12 | 58671.30 | 30-JUN-24:00 | 58671.30 | 0.00 |
July | 0.00 | 0.00 | 0.159074E+12 | 0.157535E+12 | 75060.12 | 31-JUL-24:00 | 75060.12 | 0.00 |
August | 0.00 | 0.00 | 0.206611E+12 | 0.205310E+12 | 89390.09 | 13-AUG-18:44 | 89390.09 | 0.00 |
September | 0.00 | 0.00 | 0.550164E+11 | 0.545708E+11 | 36700.55 | 30-SEP-23:50 | 36700.55 | 0.00 |
October | 0.00 | 0.00 | 0.925938E+11 | 0.923923E+11 | 51726.15 | 09-OCT-17:00 | 51726.15 | 0.00 |
November | 0.00 | 0.00 | 0.129933E+12 | 0.129785E+12 | 65605.21 | 07-NOV-16:20 | 65605.21 | 0.00 |
December | 0.00 | 0.00 | 0.172065E+12 | 0.172065E+12 | 80159.54 | 03-DEC-16:00 | 80159.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139453E+13 | 0.138861E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.310609E+11 | 0.309741E+11 | 28056.85 | 28056.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206611E+12 | 0.205310E+12 | 89390.09 | 89390.09 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.150387E+10 | 0.149614E+10 | 2764.75 | 20-JAN-16:30 | 2764.75 | 0.00 |
February | 0.00 | 0.00 | 0.552863E+10 | 0.552462E+10 | 4639.96 | 17-FEB-17:00 | 4619.79 | 0.00 |
March | 0.00 | 0.00 | 0.122571E+11 | 0.122458E+11 | 7158.28 | 31-MAR-23:20 | 7158.28 | 0.00 |
April | 0.00 | 0.00 | 0.167559E+11 | 0.167266E+11 | 8675.94 | 08-APR-18:00 | 8675.94 | 0.00 |
May | 0.00 | 0.00 | 0.485684E+10 | 0.479960E+10 | 3918.05 | 31-MAY-23:20 | 3871.14 | 0.00 |
June | 0.00 | 0.00 | 0.107141E+11 | 0.105965E+11 | 5876.50 | 30-JUN-24:00 | 5876.50 | 0.00 |
July | 0.00 | 0.00 | 0.159557E+11 | 0.158018E+11 | 7428.54 | 31-JUL-24:00 | 7428.54 | 0.00 |
August | 0.00 | 0.00 | 0.206667E+11 | 0.205367E+11 | 9103.21 | 13-AUG-18:41 | 9103.21 | 0.00 |
September | 0.00 | 0.00 | 0.526819E+10 | 0.522366E+10 | 3795.97 | 10-SEP-17:33 | 3795.97 | 0.00 |
October | 0.00 | 0.00 | 0.800922E+10 | 0.798939E+10 | 5179.23 | 09-OCT-16:48 | 5179.23 | 0.00 |
November | 0.00 | 0.00 | 0.113308E+11 | 0.113162E+11 | 6585.69 | 07-NOV-16:20 | 6585.69 | 0.00 |
December | 0.00 | 0.00 | 0.152173E+11 | 0.152173E+11 | 7964.65 | 01-DEC-16:00 | 7964.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128064E+12 | 0.127474E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.150387E+10 | 0.149614E+10 | 2764.75 | 2764.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206667E+11 | 0.205367E+11 | 9103.21 | 9103.21 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 86729.23 | 1164055.04 | 30-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 100273.38 | 1372415.58 | 06-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 54332.52 | 1163114.78 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 35206.08 | 1120154.76 | 24-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2757.47 | 714977.67 | 01-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.62 | 1901.80 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 2185.54 | 432111.15 | 21-SEP-13:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42877.94 | 1159818.89 | 23-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 69803.58 | 1233335.31 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 136168.01 | 1424038.28 | 26-DEC-06:03 |
Annual Sum or Average | 0.00 | 43924.24 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 136168.01 | 1424038.28 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 41200.16 | 892503.81 | 20-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 37482.63 | 598547.99 | 17-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 57988.18 | 1265331.95 | 14-MAR-14:15 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 48190.90 | 889335.19 | 19-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 145751.64 | 1407681.18 | 16-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 469649.34 | 1830716.61 | 22-JUN-08:33 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 462950.32 | 1890798.06 | 19-JUL-10:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 448515.80 | 1726446.68 | 02-AUG-15:33 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 323869.84 | 1613875.49 | 12-SEP-14:43 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 104141.64 | 1396999.56 | 11-OCT-12:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 54857.01 | 1183580.02 | 07-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30247.88 | 759776.42 | 01-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186195.04 | 0.00 | ||||
Minimum of Months | 30247.88 | 598547.99 | 0.00 | 0.00 | ||
Maximum of Months | 469649.34 | 1890798.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 40473.44 | 891736.01 | 20-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 36663.25 | 606722.85 | 17-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 57391.25 | 1621209.10 | 14-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 47378.57 | 906914.11 | 20-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 144904.52 | 1370177.08 | 31-MAY-16:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 472957.30 | 2005897.53 | 22-JUN-09:15 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 465461.04 | 1961661.75 | 27-JUL-08:40 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 448200.68 | 2191560.17 | 24-AUG-12:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 325710.62 | 2118768.95 | 05-SEP-12:50 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 103291.36 | 1548646.14 | 11-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 54163.16 | 1275421.59 | 07-NOV-14:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 29576.25 | 760177.34 | 01-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186304.43 | 0.00 | ||||
Minimum of Months | 29576.25 | 606722.85 | 0.00 | 0.00 | ||
Maximum of Months | 472957.30 | 2191560.17 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28460.62 | 220680.10 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56862.63 | 225360.54 | 18-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 106325.14 | 910750.47 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 157222.27 | 878959.87 | 19-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 108855.23 | 993826.32 | 17-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 579334.37 | 1906809.17 | 26-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 809084.88 | 1961897.92 | 16-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 936838.81 | 2188382.80 | 16-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 276414.70 | 1230686.56 | 10-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 89482.99 | 1072058.47 | 11-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 99597.06 | 686531.66 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 122554.46 | 871341.89 | 01-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 282791.43 | 0.00 | ||||
Minimum of Months | 28460.62 | 220680.10 | 0.00 | 0.00 | ||
Maximum of Months | 936838.81 | 2188382.80 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15209.28 | 54426.07 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15488.43 | 54570.19 | 13-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16221.18 | 54357.77 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14606.00 | 52666.00 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14276.07 | 50262.74 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13773.59 | 47256.06 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 12102.71 | 44631.53 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13048.56 | 43387.75 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12460.28 | 44814.16 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13039.76 | 47512.76 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14031.17 | 50424.41 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14279.23 | 52859.98 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14036.40 | ||||
Minimum of Months | 0.00 | 0.00 | 12102.71 | 43387.75 | ||
Maximum of Months | 0.00 | 0.00 | 16221.18 | 54570.19 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 41862.30 | 1033376.77 | 20-JAN-15:00 | 4821.87 | 130402.40 | 13-JAN-06:40 |
February | 36428.87 | 683429.02 | 17-FEB-15:40 | 5414.15 | 142098.97 | 06-FEB-02:30 |
March | 62270.69 | 1985458.79 | 14-MAR-14:15 | 4739.23 | 127580.67 | 29-MAR-09:40 |
April | 49572.44 | 1025905.53 | 19-APR-13:30 | 3994.49 | 121490.17 | 17-APR-11:30 |
May | 177891.67 | 2119665.64 | 31-MAY-15:20 | 2584.94 | 116420.82 | 01-MAY-06:11 |
June | 606883.56 | 2157057.80 | 08-JUN-14:40 | 1446.55 | 95822.24 | 09-JUN-07:50 |
July | 598738.44 | 2768200.50 | 19-JUL-10:03 | 1923.27 | 100029.40 | 02-JUL-06:51 |
August | 582912.37 | 2157532.91 | 02-AUG-12:40 | 2523.03 | 83703.02 | 18-AUG-00:50 |
September | 420597.29 | 2155814.20 | 05-SEP-14:40 | 1241.42 | 113491.00 | 22-SEP-08:30 |
October | 121121.33 | 2143528.66 | 11-OCT-15:00 | 2542.95 | 121124.49 | 23-OCT-14:40 |
November | 58460.79 | 1861062.78 | 07-NOV-15:30 | 4518.38 | 134874.84 | 27-NOV-05:42 |
December | 27461.06 | 867842.75 | 01-DEC-15:00 | 4673.13 | 128619.15 | 07-DEC-12:00 |
Annual Sum or Average | 233055.96 | 3358.03 | ||||
Minimum of Months | 27461.06 | 683429.02 | 1241.42 | 83703.02 | ||
Maximum of Months | 606883.56 | 2768200.50 | 5414.15 | 142098.97 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.530789E+10 | 0.43 | 15272.22 | 02-JAN-09:40 | 1.63 |
February | 0.510629E+10 | 0.45 | 14681.44 | 27-FEB-15:50 | 1.60 |
March | 0.811955E+10 | 0.53 | 19756.17 | 13-MAR-09:20 | 1.92 |
April | 0.884514E+10 | 0.53 | 18707.65 | 07-APR-14:40 | 1.86 |
May | 0.989378E+10 | 0.58 | 17922.39 | 18-MAY-14:30 | 1.80 |
June | 0.194178E+11 | 0.92 | 23974.64 | 05-JUN-10:20 | 2.16 |
July | 0.216760E+11 | 1.01 | 23974.64 | 02-JUL-15:01 | 2.17 |
August | 0.201782E+11 | 1.00 | 23974.64 | 02-AUG-14:40 | 2.16 |
September | 0.127331E+11 | 0.69 | 23974.64 | 01-SEP-11:05 | 2.15 |
October | 0.771586E+10 | 0.51 | 23974.64 | 10-OCT-08:40 | 2.17 |
November | 0.677973E+10 | 0.49 | 17252.36 | 06-NOV-15:50 | 1.77 |
December | 0.602828E+10 | 0.45 | 17515.78 | 04-DEC-15:40 | 1.79 |
Annual Sum or Average | 0.131802E+12 | 0.63 | |||
Minimum of Months | 0.510629E+10 | 0.43 | 14681.44 | 1.60 | |
Maximum of Months | 0.216760E+11 | 1.01 | 23974.64 | 2.17 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358130E+11 | 0.40 | 92865.19 | 23-JAN-06:02 | 1.26 |
February | 0.335290E+11 | 0.42 | 98053.68 | 24-FEB-06:02 | 1.29 |
March | 0.484455E+11 | 0.46 | 125460.70 | 01-MAR-06:02 | 1.50 |
April | 0.448373E+11 | 0.42 | 121619.13 | 07-APR-15:20 | 1.48 |
May | 0.722266E+11 | 0.51 | 147732.72 | 18-MAY-14:05 | 1.66 |
June | 0.122713E+12 | 0.70 | 224225.42 | 01-JUN-12:05 | 2.15 |
July | 0.116073E+12 | 0.66 | 224225.42 | 17-JUL-05:02 | 2.17 |
August | 0.115847E+12 | 0.66 | 224225.42 | 02-AUG-15:37 | 2.16 |
September | 0.853454E+11 | 0.57 | 224225.42 | 12-SEP-14:43 | 2.16 |
October | 0.481560E+11 | 0.43 | 114872.52 | 20-OCT-15:50 | 1.43 |
November | 0.378566E+11 | 0.41 | 96805.05 | 15-NOV-06:02 | 1.28 |
December | 0.328068E+11 | 0.41 | 95804.78 | 05-DEC-06:03 | 1.28 |
Annual Sum or Average | 0.793648E+12 | 0.50 | |||
Minimum of Months | 0.328068E+11 | 0.40 | 92865.19 | 1.26 | |
Maximum of Months | 0.122713E+12 | 0.70 | 224225.42 | 2.17 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.361169E+10 | 0.48 | 6886.72 | 20-JAN-16:40 | 0.99 |
February | 0.335527E+10 | 0.47 | 5867.25 | 17-FEB-16:30 | 0.90 |
March | 0.450706E+10 | 0.50 | 11122.90 | 10-MAR-16:10 | 1.31 |
April | 0.430061E+10 | 0.46 | 12770.05 | 07-APR-15:30 | 1.43 |
May | 0.637207E+10 | 0.48 | 15793.21 | 31-MAY-15:20 | 1.61 |
June | 0.129212E+11 | 0.68 | 25053.55 | 05-JUN-13:30 | 2.16 |
July | 0.119412E+11 | 0.64 | 25053.55 | 12-JUL-13:30 | 2.16 |
August | 0.117492E+11 | 0.63 | 25053.55 | 02-AUG-15:33 | 2.16 |
September | 0.801644E+10 | 0.53 | 25053.55 | 05-SEP-15:05 | 2.16 |
October | 0.414657E+10 | 0.44 | 10880.75 | 06-OCT-16:00 | 1.29 |
November | 0.337731E+10 | 0.43 | 7975.26 | 07-NOV-16:20 | 1.08 |
December | 0.361883E+10 | 0.49 | 5702.45 | 07-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.779175E+11 | 0.52 | |||
Minimum of Months | 0.335527E+10 | 0.43 | 5702.45 | 0.89 | |
Maximum of Months | 0.129212E+11 | 0.68 | 25053.55 | 2.16 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.627916E+10 | 0.54 | 13309.31 | 02-JAN-07:05 | 2.17 |
February | 0.623886E+10 | 0.57 | 13309.31 | 01-FEB-07:03 | 2.20 |
March | 0.941394E+10 | 0.71 | 13309.31 | 01-MAR-07:03 | 2.20 |
April | 0.690409E+10 | 0.59 | 13309.31 | 01-APR-06:05 | 2.20 |
May | 0.110851E+11 | 0.78 | 13309.31 | 01-MAY-06:10 | 2.18 |
June | 0.824467E+10 | 0.53 | 13309.31 | 01-JUN-06:10 | 2.18 |
July | 0.559037E+10 | 0.34 | 13309.31 | 03-JUL-06:10 | 2.11 |
August | 0.114887E+11 | 0.71 | 13309.31 | 01-AUG-06:20 | 2.17 |
September | 0.115042E+11 | 0.76 | 13309.31 | 01-SEP-06:10 | 2.12 |
October | 0.137087E+11 | 0.90 | 13309.31 | 02-OCT-06:05 | 2.19 |
November | 0.103635E+11 | 0.76 | 13309.31 | 01-NOV-06:05 | 2.20 |
December | 0.877062E+10 | 0.66 | 13309.31 | 01-DEC-07:10 | 2.20 |
Annual Sum or Average | 0.109592E+12 | 0.66 | |||
Minimum of Months | 0.559037E+10 | 0.34 | 13309.31 | 2.11 | |
Maximum of Months | 0.137087E+11 | 0.90 | 13309.31 | 2.20 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132700E+12 | 1.65 | 49544.49 | 01-JAN-00:05 | 1.65 |
February | 0.119858E+12 | 1.65 | 49544.49 | 01-FEB-00:20 | 1.65 |
March | 0.132700E+12 | 1.66 | 49544.49 | 01-MAR-00:10 | 1.65 |
April | 0.128419E+12 | 1.66 | 49544.49 | 01-APR-00:10 | 1.66 |
May | 0.132700E+12 | 1.65 | 49544.49 | 01-MAY-00:10 | 1.65 |
June | 0.128419E+12 | 1.65 | 49544.49 | 01-JUN-00:10 | 1.65 |
July | 0.132700E+12 | 1.65 | 49544.49 | 01-JUL-00:05 | 1.66 |
August | 0.132700E+12 | 1.65 | 49544.49 | 01-AUG-00:05 | 1.64 |
September | 0.128419E+12 | 1.65 | 49544.49 | 01-SEP-00:05 | 1.65 |
October | 0.132700E+12 | 1.65 | 49544.49 | 01-OCT-00:10 | 1.65 |
November | 0.128419E+12 | 1.66 | 49544.49 | 01-NOV-00:10 | 1.66 |
December | 0.132700E+12 | 1.66 | 49544.49 | 01-DEC-00:10 | 1.66 |
Annual Sum or Average | 0.156244E+13 | 1.65 | |||
Minimum of Months | 0.119858E+12 | 1.65 | 49544.49 | 1.64 | |
Maximum of Months | 0.132700E+12 | 1.66 | 49544.49 | 1.66 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179907E+10 | 1.13 | 671.70 | 01-JAN-00:05 | 1.13 |
February | 0.162497E+10 | 1.13 | 671.70 | 01-FEB-00:10 | 1.13 |
March | 0.179907E+10 | 1.13 | 671.70 | 01-MAR-00:10 | 1.13 |
April | 0.174104E+10 | 1.13 | 671.70 | 01-APR-00:10 | 1.13 |
May | 0.179907E+10 | 1.13 | 671.70 | 01-MAY-00:10 | 1.13 |
June | 0.174104E+10 | 1.13 | 671.70 | 01-JUN-00:10 | 1.13 |
July | 0.179907E+10 | 1.13 | 671.70 | 01-JUL-00:05 | 1.13 |
August | 0.179907E+10 | 1.13 | 671.70 | 01-AUG-00:05 | 1.13 |
September | 0.174104E+10 | 1.13 | 671.70 | 01-SEP-00:10 | 1.13 |
October | 0.179907E+10 | 1.13 | 671.70 | 01-OCT-00:10 | 1.13 |
November | 0.174104E+10 | 1.13 | 671.70 | 01-NOV-00:10 | 1.13 |
December | 0.179907E+10 | 1.13 | 671.70 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.211826E+11 | 1.13 | |||
Minimum of Months | 0.162497E+10 | 1.13 | 671.70 | 1.13 | |
Maximum of Months | 0.179907E+10 | 1.13 | 671.70 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.172761E+11 | 1.13 | 6450.15 | 01-JAN-00:05 | 1.13 |
February | 0.156042E+11 | 1.13 | 6450.15 | 01-FEB-00:10 | 1.13 |
March | 0.172761E+11 | 1.13 | 6450.15 | 01-MAR-00:10 | 1.13 |
April | 0.167188E+11 | 1.13 | 6450.15 | 01-APR-00:10 | 1.13 |
May | 0.172761E+11 | 1.13 | 6450.15 | 01-MAY-00:10 | 1.13 |
June | 0.167188E+11 | 1.13 | 6450.15 | 01-JUN-00:10 | 1.13 |
July | 0.172761E+11 | 1.13 | 6450.15 | 01-JUL-00:05 | 1.13 |
August | 0.172761E+11 | 1.13 | 6450.15 | 01-AUG-00:05 | 1.13 |
September | 0.167188E+11 | 1.13 | 6450.15 | 01-SEP-00:05 | 1.13 |
October | 0.172761E+11 | 1.13 | 6450.15 | 01-OCT-00:20 | 1.13 |
November | 0.167188E+11 | 1.13 | 6450.15 | 01-NOV-00:10 | 1.13 |
December | 0.172761E+11 | 1.13 | 6450.15 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.203412E+12 | 1.13 | |||
Minimum of Months | 0.156042E+11 | 1.13 | 6450.15 | 1.13 | |
Maximum of Months | 0.172761E+11 | 1.13 | 6450.15 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176187E+10 | 1.13 | 657.81 | 01-JAN-00:05 | 1.13 |
February | 0.159137E+10 | 1.13 | 657.81 | 01-FEB-00:10 | 1.13 |
March | 0.176187E+10 | 1.13 | 657.81 | 01-MAR-00:10 | 1.13 |
April | 0.170504E+10 | 1.13 | 657.81 | 01-APR-00:10 | 1.13 |
May | 0.176187E+10 | 1.13 | 657.81 | 01-MAY-00:10 | 1.13 |
June | 0.170504E+10 | 1.13 | 657.81 | 01-JUN-00:10 | 1.13 |
July | 0.176187E+10 | 1.13 | 657.81 | 01-JUL-00:05 | 1.13 |
August | 0.176187E+10 | 1.13 | 657.81 | 01-AUG-00:05 | 1.13 |
September | 0.170504E+10 | 1.13 | 657.81 | 01-SEP-00:05 | 1.13 |
October | 0.176187E+10 | 1.13 | 657.81 | 01-OCT-00:10 | 1.13 |
November | 0.170504E+10 | 1.13 | 657.81 | 01-NOV-00:10 | 1.13 |
December | 0.176187E+10 | 1.13 | 657.81 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.207446E+11 | 1.13 | |||
Minimum of Months | 0.159137E+10 | 1.13 | 657.81 | 1.13 | |
Maximum of Months | 0.176187E+10 | 1.13 | 657.81 | 1.13 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 43495654.66 | 39537550.09 | 741.50 | 05-JAN-07:10 | 674.02 | 674.02 | 52.75 | 8.00 |
February | 32780407.94 | 29797390.82 | 1279.67 | 06-FEB-06:02 | 1163.22 | 1163.22 | 49.61 | 10.13 |
March | 13433938.62 | 12211450.21 | 480.07 | 20-MAR-05:01 | 436.38 | 436.38 | 46.79 | 6.62 |
April | 7913761.61 | 7193609.31 | 458.70 | 03-APR-05:01 | 416.96 | 416.96 | 46.28 | 6.48 |
May | 326596.50 | 296876.22 | 135.77 | 01-MAY-05:03 | 123.41 | 123.41 | 35.28 | 3.66 |
June | 40.24 | 36.58 | 0.05 | 09-JUN-06:10 | 0.04 | 0.04 | 23.01 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 23.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 23.00 | 0.00 |
September | 337105.75 | 306429.13 | 36.84 | 21-SEP-13:05 | 33.48 | 33.48 | 25.96 | 1.84 |
October | 15977621.44 | 14523657.89 | 480.46 | 30-OCT-05:01 | 436.74 | 436.74 | 46.45 | 6.62 |
November | 22985177.61 | 20893526.45 | 478.11 | 02-NOV-05:01 | 434.60 | 434.60 | 45.13 | 6.61 |
December | 0.131770E+09 | 0.119779E+09 | 1286.50 | 23-DEC-07:10 | 1169.42 | 1169.42 | 52.63 | 10.14 |
Annual Sum or Average | 0.269021E+09 | 0.244540E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 | |
Maximum of Months | 0.131770E+09 | 0.119779E+09 | 1286.50 | 1169.42 | 1169.42 | 52.75 | 10.14 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 56617586.95 | 51465386.54 | 956.07 | 20-JAN-15:30 | 869.07 | 869.07 | 6.71 | 22.41 |
February | 30375194.15 | 27611051.48 | 381.03 | 17-FEB-15:05 | 346.35 | 346.35 | 6.71 | 14.68 |
March | 96623023.25 | 87830328.13 | 5524.41 | 14-MAR-14:00 | 5021.69 | 5021.69 | 10.11 | 46.99 |
April | 43966925.72 | 39965935.48 | 850.88 | 19-APR-13:30 | 773.45 | 773.45 | 6.71 | 21.27 |
May | 0.300544E+09 | 0.273195E+09 | 6083.99 | 31-MAY-16:50 | 5530.35 | 5530.35 | 9.23 | 48.84 |
June | 0.185056E+10 | 0.168216E+10 | 9461.85 | 05-JUN-15:00 | 8600.82 | 8600.82 | 6.74 | 58.18 |
July | 0.170784E+10 | 0.155243E+10 | 9461.85 | 12-JUL-13:40 | 8600.82 | 8600.82 | 6.73 | 58.18 |
August | 0.193452E+10 | 0.175848E+10 | 9461.85 | 24-AUG-12:13 | 8600.82 | 8600.82 | 9.78 | 58.18 |
September | 0.966905E+09 | 0.878917E+09 | 9461.85 | 01-SEP-11:05 | 8600.82 | 8600.82 | 9.42 | 58.18 |
October | 0.198819E+09 | 0.180727E+09 | 3941.57 | 11-OCT-12:00 | 3582.88 | 3582.88 | 9.65 | 40.98 |
November | 72140200.70 | 65575442.44 | 2494.09 | 07-NOV-14:50 | 2267.13 | 2267.13 | 9.66 | 33.90 |
December | 28936384.81 | 26303173.79 | 608.82 | 01-DEC-15:00 | 553.42 | 553.42 | 6.71 | 18.27 |
Annual Sum or Average | 0.728785E+10 | 0.662465E+10 | ||||||
Minimum of Months | 28936384.81 | 26303173.79 | 381.03 | 346.35 | 346.35 | 6.71 | 14.68 | |
Maximum of Months | 0.193452E+10 | 0.175848E+10 | 9461.85 | 8600.82 | 8600.82 | 10.11 | 58.18 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.229111E+10 | 0.208262E+10 | 3256.17 | 02-JAN-08:07 | 2959.86 | 2959.86 | 6.71 | 29.09 |
February | 0.226228E+10 | 0.205641E+10 | 3256.17 | 01-FEB-05:01 | 2959.86 | 2959.86 | 6.73 | 29.09 |
March | 0.253796E+10 | 0.230701E+10 | 3256.17 | 01-MAR-06:02 | 2959.86 | 2959.86 | 6.76 | 29.09 |
April | 0.246584E+10 | 0.224145E+10 | 3256.17 | 03-APR-03:01 | 2959.86 | 2959.86 | 6.73 | 29.09 |
May | 0.377738E+10 | 0.343363E+10 | 3256.17 | 01-MAY-05:03 | 2959.86 | 2959.86 | 6.77 | 29.09 |
June | 0.629622E+10 | 0.572326E+10 | 3256.17 | 01-JUN-04:12 | 2959.86 | 2959.86 | 7.62 | 29.09 |
July | 0.720521E+10 | 0.654954E+10 | 3256.17 | 01-JUL-00:20 | 2959.86 | 2959.86 | 6.86 | 29.09 |
August | 0.722496E+10 | 0.656749E+10 | 3256.17 | 01-AUG-00:05 | 2959.86 | 2959.86 | 6.83 | 29.09 |
September | 0.499776E+10 | 0.454297E+10 | 3256.17 | 01-SEP-00:15 | 2959.86 | 2959.86 | 6.86 | 29.09 |
October | 0.296512E+10 | 0.269530E+10 | 3256.17 | 01-OCT-07:17 | 2959.86 | 2959.86 | 6.77 | 29.09 |
November | 0.247697E+10 | 0.225157E+10 | 3256.17 | 01-NOV-10:20 | 2959.86 | 2959.86 | 6.73 | 29.09 |
December | 0.207221E+10 | 0.188364E+10 | 3256.17 | 01-DEC-07:12 | 2959.86 | 2959.86 | 6.86 | 29.09 |
Annual Sum or Average | 0.465730E+11 | 0.423349E+11 | ||||||
Minimum of Months | 0.207221E+10 | 0.188364E+10 | 3256.17 | 2959.86 | 2959.86 | 6.71 | 29.09 | |
Maximum of Months | 0.722496E+10 | 0.656749E+10 | 3256.17 | 2959.86 | 2959.86 | 7.62 | 29.09 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
March | 50796197.64 | 46173743.65 | 3256.17 | 13-MAR-13:20 | 2959.86 | 2959.86 | 15.33 | 14.55 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
May | 0.370226E+09 | 0.336536E+09 | 3256.17 | 04-MAY-13:30 | 2959.86 | 2959.86 | 15.21 | 14.55 |
June | 0.204080E+10 | 0.185509E+10 | 3256.17 | 01-JUN-10:50 | 2959.86 | 2959.86 | 14.12 | 14.55 |
July | 0.195517E+10 | 0.177725E+10 | 3256.17 | 01-JUL-10:20 | 2959.86 | 2959.86 | 14.88 | 14.55 |
August | 0.200808E+10 | 0.182534E+10 | 3256.17 | 02-AUG-09:50 | 2959.86 | 2959.86 | 16.05 | 14.55 |
September | 0.123474E+10 | 0.112238E+10 | 3256.17 | 01-SEP-10:20 | 2959.86 | 2959.86 | 13.02 | 14.55 |
October | 0.146527E+09 | 0.133193E+09 | 3256.17 | 10-OCT-10:30 | 2959.86 | 2959.86 | 15.42 | 14.55 |
November | 15629599.27 | 14207305.74 | 3256.17 | 07-NOV-14:20 | 2959.86 | 2959.86 | 15.70 | 14.55 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
Annual Sum or Average | 0.782196E+10 | 0.711016E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.204080E+10 | 0.185509E+10 | 3256.17 | 2959.86 | 2959.86 | 16.05 | 14.55 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-JAN-00:05 | 3763.95 | 3763.95 | 18.67 | 17.47 |
February | 0.100173E+11 | 0.910574E+10 | 4140.76 | 01-FEB-00:10 | 3763.95 | 3763.95 | 19.22 | 17.47 |
March | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-MAR-00:10 | 3763.95 | 3763.95 | 19.73 | 17.47 |
April | 0.107328E+11 | 0.975615E+10 | 4140.76 | 01-APR-00:10 | 3763.95 | 3763.95 | 20.31 | 17.47 |
May | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-MAY-00:10 | 3763.95 | 3763.95 | 18.76 | 17.47 |
June | 0.107328E+11 | 0.975615E+10 | 4140.76 | 01-JUN-00:10 | 3763.95 | 3763.95 | 19.36 | 17.47 |
July | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-JUL-00:05 | 3763.95 | 3763.95 | 29.82 | 17.47 |
August | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-AUG-00:05 | 3763.95 | 3763.95 | 31.34 | 17.47 |
September | 0.107328E+11 | 0.975615E+10 | 4140.76 | 01-SEP-00:05 | 3763.95 | 3763.95 | 19.32 | 17.47 |
October | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-OCT-00:10 | 3763.95 | 3763.95 | 19.35 | 17.47 |
November | 0.107328E+11 | 0.975615E+10 | 4140.76 | 01-NOV-00:10 | 3763.95 | 3763.95 | 19.57 | 17.47 |
December | 0.110906E+11 | 0.100814E+11 | 4140.76 | 01-DEC-00:10 | 3763.95 | 3763.95 | 20.08 | 17.47 |
Annual Sum or Average | 0.130583E+12 | 0.118700E+12 | ||||||
Minimum of Months | 0.100173E+11 | 0.910574E+10 | 4140.76 | 3763.95 | 3763.95 | 18.67 | 17.47 | |
Maximum of Months | 0.110906E+11 | 0.100814E+11 | 4140.76 | 3763.95 | 3763.95 | 31.34 | 17.47 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.95 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 57.01 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.87 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.89 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.23 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.22 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.38 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.47 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.51 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.14 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 57.36 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.10 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.87 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.51 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.907984E+10 | 0.825357E+10 | 12943.21 | 20-JAN-15:00 | 11765.38 | 11765.38 | 25.78 | 52.81 |
February | 0.896460E+10 | 0.814882E+10 | 12927.24 | 17-FEB-15:40 | 11750.86 | 11750.86 | 24.20 | 52.81 |
March | 0.102458E+11 | 0.931340E+10 | 25882.51 | 14-MAR-14:15 | 23527.20 | 23527.20 | 25.60 | 105.63 |
April | 0.977277E+10 | 0.888345E+10 | 12942.84 | 19-APR-13:30 | 11765.04 | 11765.04 | 25.75 | 52.81 |
May | 0.162329E+11 | 0.147557E+11 | 25889.10 | 31-MAY-15:20 | 23533.19 | 23533.19 | 25.90 | 105.63 |
June | 0.326584E+11 | 0.296865E+11 | 25890.94 | 08-JUN-14:40 | 23534.86 | 23534.86 | 25.99 | 105.63 |
July | 0.358052E+11 | 0.325469E+11 | 25921.01 | 19-JUL-10:03 | 23562.20 | 23562.20 | 27.37 | 105.63 |
August | 0.361956E+11 | 0.329018E+11 | 25890.96 | 02-AUG-12:40 | 23534.89 | 23534.89 | 25.99 | 105.63 |
September | 0.243478E+11 | 0.221322E+11 | 25890.88 | 05-SEP-14:40 | 23534.81 | 23534.81 | 25.98 | 105.63 |
October | 0.122776E+11 | 0.111603E+11 | 25890.28 | 11-OCT-15:00 | 23534.26 | 23534.26 | 25.96 | 105.63 |
November | 0.987972E+10 | 0.898066E+10 | 25876.40 | 07-NOV-15:30 | 23521.65 | 23521.65 | 25.32 | 105.63 |
December | 0.821110E+10 | 0.746389E+10 | 12935.06 | 01-DEC-15:00 | 11757.97 | 11757.97 | 25.03 | 52.81 |
Annual Sum or Average | 0.213671E+12 | 0.194227E+12 | ||||||
Minimum of Months | 0.821110E+10 | 0.746389E+10 | 12927.24 | 11750.86 | 11750.86 | 24.20 | 52.81 | |
Maximum of Months | 0.361956E+11 | 0.329018E+11 | 25921.01 | 23562.20 | 23562.20 | 27.37 | 105.63 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 39.23 | 39.23 | 86729.23 | 1164055.04 | 30-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 38.79 | 38.79 | 100273.38 | 1372415.58 | 06-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 32.42 | 32.42 | 54332.52 | 1163114.78 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.59 | 26.59 | 35206.08 | 1120154.76 | 24-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24.37 | 24.37 | 2757.47 | 714977.67 | 01-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.02 | 23.02 | 0.62 | 1901.80 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 23.00 | 23.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.00 | 23.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.00 | 23.00 | 2185.54 | 432111.15 | 21-SEP-13:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.58 | 24.58 | 42877.94 | 1159818.89 | 23-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 43.99 | 43.99 | 69803.58 | 1233335.31 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 36.34 | 36.34 | 136168.01 | 1424038.28 | 26-DEC-06:03 |
Annual Sum or Average | 0.00 | 43924.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.00 | 23.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 43.99 | 43.99 | 136168.01 | 1424038.28 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 41200.16 | 892503.81 | 20-JAN-15:00 | 14.03 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 37482.63 | 598547.99 | 17-FEB-15:10 | 11.61 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 57988.18 | 1265331.95 | 14-MAR-14:15 | 11.89 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 48190.90 | 889335.19 | 19-APR-13:30 | 14.00 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 145751.64 | 1407681.18 | 16-MAY-12:05 | 12.48 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 469649.34 | 1830716.61 | 22-JUN-08:33 | 14.22 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 462950.32 | 1890798.06 | 19-JUL-10:03 | 14.46 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 448515.80 | 1726446.68 | 02-AUG-15:33 | 13.79 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 323869.84 | 1613875.49 | 12-SEP-14:43 | 13.32 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 104141.64 | 1396999.56 | 11-OCT-12:05 | 12.43 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 54857.01 | 1183580.02 | 07-NOV-16:00 | 11.56 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30247.88 | 759776.42 | 01-DEC-15:00 | 12.94 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186195.04 | 0.00 | ||||||
Minimum of Months | 30247.88 | 598547.99 | 11.56 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 469649.34 | 1890798.06 | 14.46 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 40473.44 | 891736.01 | 20-JAN-15:00 | 16.26 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 36663.25 | 606722.85 | 17-FEB-15:05 | 16.58 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 57391.25 | 1621209.10 | 14-MAR-14:00 | 14.94 | 10.23 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 47378.57 | 906914.11 | 20-APR-13:00 | 18.30 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 144904.52 | 1370177.08 | 31-MAY-16:50 | 13.40 | 9.40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 472957.30 | 2005897.53 | 22-JUN-09:15 | 15.34 | 11.81 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 465461.04 | 1961661.75 | 27-JUL-08:40 | 15.15 | 10.71 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 448200.68 | 2191560.17 | 24-AUG-12:20 | 15.70 | 11.19 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 325710.62 | 2118768.95 | 05-SEP-12:50 | 15.40 | 11.38 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 103291.36 | 1548646.14 | 11-OCT-12:00 | 15.73 | 9.75 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 54163.16 | 1275421.59 | 07-NOV-14:50 | 15.69 | 10.07 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 29576.25 | 760177.34 | 01-DEC-15:00 | 16.64 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186304.43 | 0.00 | ||||||
Minimum of Months | 29576.25 | 606722.85 | 13.40 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 472957.30 | 2191560.17 | 18.30 | 11.81 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28460.62 | 220680.10 | 20-JAN-14:00 | 21.97 | 21.25 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56862.63 | 225360.54 | 18-FEB-14:00 | 22.04 | 20.53 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 106325.14 | 910750.47 | 14-MAR-13:00 | 33.18 | 26.39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 157222.27 | 878959.87 | 19-APR-13:30 | 32.66 | 24.78 | 0.00 | 0.00 | 01-APR-00:10 |
May | 108855.23 | 993826.32 | 17-MAY-14:00 | 34.51 | 30.44 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 579334.37 | 1906809.17 | 26-JUN-15:00 | 48.95 | 41.94 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 809084.88 | 1961897.92 | 16-JUL-13:00 | 49.81 | 40.41 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 936838.81 | 2188382.80 | 16-AUG-16:00 | 53.33 | 41.37 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 276414.70 | 1230686.56 | 10-SEP-14:00 | 38.29 | 34.17 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 89482.99 | 1072058.47 | 11-OCT-14:00 | 35.76 | 29.29 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 99597.06 | 686531.66 | 07-NOV-15:00 | 29.56 | 23.96 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 122554.46 | 871341.89 | 01-DEC-14:00 | 32.54 | 24.75 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 282791.43 | 0.00 | ||||||
Minimum of Months | 28460.62 | 220680.10 | 21.97 | 20.53 | 0.00 | 0.00 | ||
Maximum of Months | 936838.81 | 2188382.80 | 53.33 | 41.94 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.03 | 58.03 | 15209.28 | 54426.07 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.46 | 57.46 | 15488.43 | 54570.19 | 13-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.46 | 57.46 | 16221.18 | 54357.77 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.53 | 57.53 | 14606.00 | 52666.00 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.13 | 58.13 | 14276.07 | 50262.74 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.79 | 57.79 | 13773.59 | 47256.06 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.92 | 57.92 | 12102.71 | 44631.53 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.99 | 57.99 | 13048.56 | 43387.75 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.99 | 57.99 | 12460.28 | 44814.16 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.91 | 57.91 | 13039.76 | 47512.76 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.79 | 57.79 | 14031.17 | 50424.41 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.65 | 57.65 | 14279.23 | 52859.98 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14036.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.46 | 57.46 | 12102.71 | 43387.75 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 16221.18 | 54570.19 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 41862.30 | 1033376.77 | 20-JAN-15:00 | 25.78 | 21.10 | 4821.87 | 130402.40 | 13-JAN-06:40 |
February | 36428.87 | 683429.02 | 17-FEB-15:40 | 24.20 | 21.10 | 5414.15 | 142098.97 | 06-FEB-02:30 |
March | 62270.69 | 1985458.79 | 14-MAR-14:15 | 25.60 | 21.10 | 4739.23 | 127580.67 | 29-MAR-09:40 |
April | 49572.44 | 1025905.53 | 19-APR-13:30 | 25.75 | 21.10 | 3994.49 | 121490.17 | 17-APR-11:30 |
May | 177891.67 | 2119665.64 | 31-MAY-15:20 | 25.90 | 21.10 | 2584.94 | 116420.82 | 01-MAY-06:11 |
June | 606883.56 | 2157057.80 | 08-JUN-14:40 | 25.99 | 21.10 | 1446.55 | 95822.24 | 09-JUN-07:50 |
July | 598738.44 | 2768200.50 | 19-JUL-10:03 | 27.37 | 22.23 | 1923.27 | 100029.40 | 02-JUL-06:51 |
August | 582912.37 | 2157532.91 | 02-AUG-12:40 | 25.99 | 21.10 | 2523.03 | 83703.02 | 18-AUG-00:50 |
September | 420597.29 | 2155814.20 | 05-SEP-14:40 | 25.98 | 21.10 | 1241.42 | 113491.00 | 22-SEP-08:30 |
October | 121121.33 | 2143528.66 | 11-OCT-15:00 | 25.96 | 21.10 | 2542.95 | 121124.49 | 23-OCT-14:40 |
November | 58460.79 | 1861062.78 | 07-NOV-15:30 | 25.32 | 21.10 | 4518.38 | 134874.84 | 27-NOV-05:42 |
December | 27461.06 | 867842.75 | 01-DEC-15:00 | 25.03 | 21.10 | 4673.13 | 128619.15 | 07-DEC-12:00 |
Annual Sum or Average | 233055.96 | 3358.03 | ||||||
Minimum of Months | 27461.06 | 683429.02 | 24.20 | 21.10 | 1241.42 | 83703.02 | ||
Maximum of Months | 606883.56 | 2768200.50 | 27.37 | 22.23 | 5414.15 | 142098.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.119266E+11 | 0.00 | 0.139367E+11 | 0.530789E+10 | 0.00 | 0.00 |
February | 0.115329E+11 | 0.00 | 0.127235E+11 | 0.510629E+10 | 0.00 | 0.00 |
March | 0.621399E+10 | 0.00 | 0.154410E+11 | 0.811955E+10 | 0.00 | 0.00 |
April | 0.326199E+10 | 0.00 | 0.117473E+11 | 0.884514E+10 | 0.00 | 0.00 |
May | 0.257294E+09 | 0.00 | 0.342962E+11 | 0.989378E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121447E+12 | 0.194178E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.137324E+12 | 0.216760E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.123083E+12 | 0.201782E+11 | 0.00 | 0.00 |
September | 0.327441E+09 | 0.00 | 0.770234E+11 | 0.127331E+11 | 0.00 | 0.00 |
October | 0.506451E+10 | 0.00 | 0.199038E+11 | 0.771586E+10 | 0.00 | 0.00 |
November | 0.744214E+10 | 0.00 | 0.154334E+11 | 0.677973E+10 | 0.00 | 0.00 |
December | 0.179224E+11 | 0.00 | 0.159174E+11 | 0.602828E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.639493E+11 | 0.00 | 0.598277E+12 | 0.131802E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.117473E+11 | 0.510629E+10 | 0.00 | 0.00 |
Maximum of Months | 0.179224E+11 | 0.00 | 0.137324E+12 | 0.216760E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.184753E+12 | 0.00 | 0.838787E+11 | 0.358130E+11 | 0.00 | 0.00 |
February | 0.194879E+12 | 0.00 | 0.719761E+11 | 0.335290E+11 | 0.00 | 0.00 |
March | 0.116948E+12 | 0.00 | 0.118505E+12 | 0.484455E+11 | 0.00 | 0.00 |
April | 0.730425E+11 | 0.00 | 0.965082E+11 | 0.448373E+11 | 0.00 | 0.00 |
May | 0.562555E+10 | 0.00 | 0.292364E+12 | 0.722266E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.931107E+12 | 0.122713E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.935541E+12 | 0.116073E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.902272E+12 | 0.115847E+12 | 0.00 | 0.00 |
September | 0.453596E+10 | 0.00 | 0.630126E+12 | 0.853454E+11 | 0.00 | 0.00 |
October | 0.922486E+11 | 0.00 | 0.223757E+12 | 0.481560E+11 | 0.00 | 0.00 |
November | 0.147678E+12 | 0.00 | 0.110504E+12 | 0.378566E+11 | 0.00 | 0.00 |
December | 0.293938E+12 | 0.00 | 0.566342E+11 | 0.328068E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.111365E+13 | 0.00 | 0.445317E+13 | 0.793648E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.566342E+11 | 0.328068E+11 | 0.00 | 0.00 |
Maximum of Months | 0.293938E+12 | 0.00 | 0.935541E+12 | 0.122713E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.345538E+11 | 0.00 | 0.396128E+10 | 0.361169E+10 | 0.00 | 0.00 |
February | 0.351926E+11 | 0.00 | 0.391430E+10 | 0.335527E+10 | 0.00 | 0.00 |
March | 0.224311E+11 | 0.00 | 0.900666E+10 | 0.450706E+10 | 0.00 | 0.00 |
April | 0.153489E+11 | 0.00 | 0.746058E+10 | 0.430061E+10 | 0.00 | 0.00 |
May | 0.154144E+10 | 0.00 | 0.296599E+11 | 0.637207E+10 | 0.00 | 0.00 |
June | 1688181.92 | 0.00 | 0.104572E+12 | 0.129212E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.103156E+12 | 0.119412E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.998789E+11 | 0.117492E+11 | 0.00 | 0.00 |
September | 0.820007E+09 | 0.00 | 0.652625E+11 | 0.801644E+10 | 0.00 | 0.00 |
October | 0.178373E+11 | 0.00 | 0.139819E+11 | 0.414657E+10 | 0.00 | 0.00 |
November | 0.263105E+11 | 0.00 | 0.655891E+10 | 0.337731E+10 | 0.00 | 0.00 |
December | 0.510675E+11 | 0.00 | 0.339121E+10 | 0.361883E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.205105E+12 | 0.00 | 0.450805E+12 | 0.779175E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.339121E+10 | 0.335527E+10 | 0.00 | 0.00 |
Maximum of Months | 0.510675E+11 | 0.00 | 0.104572E+12 | 0.129212E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.225952E+10 | 0.00 | 0.270567E+10 | 0.627916E+10 | 0.00 | 0.00 |
February | 0.226668E+10 | 0.00 | 0.228756E+09 | 0.623886E+10 | 0.00 | 0.00 |
March | 0.711079E+09 | 0.00 | 0.531894E+10 | 0.941394E+10 | 0.00 | 0.00 |
April | 82975546.06 | 0.00 | 0.674288E+10 | 0.690409E+10 | 0.00 | 0.00 |
May | 6172551.78 | 0.00 | 0.202845E+11 | 0.110851E+11 | 0.00 | 0.00 |
June | 67.89 | 0.00 | 0.328398E+11 | 0.824467E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.290913E+11 | 0.559037E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.482149E+11 | 0.114887E+11 | 0.00 | 0.00 |
September | 3204535.28 | 0.00 | 0.397638E+11 | 0.115042E+11 | 0.00 | 0.00 |
October | 0.200744E+09 | 0.00 | 0.983681E+10 | 0.137087E+11 | 0.00 | 0.00 |
November | 0.472747E+09 | 0.00 | 0.460979E+10 | 0.103635E+11 | 0.00 | 0.00 |
December | 0.366821E+10 | 0.00 | 0.234985E+10 | 0.877062E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.967134E+10 | 0.00 | 0.201987E+12 | 0.109592E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.228756E+09 | 0.559037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.366821E+10 | 0.00 | 0.482149E+11 | 0.137087E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.157976E+11 | 0.318387E+12 | 0.00 | 67.02 |
February | 0.00 | 0.00 | 0.202310E+11 | 0.360500E+12 | 0.00 | 87.16 |
March | 0.00 | 0.00 | 0.453194E+11 | 0.410214E+12 | 0.00 | 98.42 |
April | 0.00 | 0.00 | 0.910338E+11 | 0.398444E+12 | 0.00 | 91.91 |
May | 0.00 | 0.00 | 0.385293E+11 | 0.308681E+12 | 0.00 | 61.22 |
June | 0.00 | 0.00 | 0.382286E+12 | 0.325852E+12 | 0.00 | 37.36 |
July | 0.00 | 0.00 | 0.741812E+12 | 0.423568E+12 | 0.00 | 42.42 |
August | 0.00 | 0.00 | 0.103635E+13 | 0.483393E+12 | 0.00 | 42.18 |
September | 0.00 | 0.00 | 0.118855E+12 | 0.323438E+12 | 0.00 | 60.75 |
October | 0.00 | 0.00 | 0.391193E+11 | 0.388192E+12 | 0.00 | 90.81 |
November | 0.00 | 0.00 | 0.381427E+11 | 0.394970E+12 | 0.00 | 95.10 |
December | 0.00 | 0.00 | 0.479889E+11 | 0.414091E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.261547E+13 | 0.454973E+13 | 0.00 | 873.98 |
Minimum of Months | 0.00 | 0.00 | 0.157976E+11 | 0.308681E+12 | 0.00 | 37.36 |
Maximum of Months | 0.00 | 0.00 | 0.103635E+13 | 0.483393E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.607110E+10 | 0.302850E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111442E+11 | 0.378459E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191352E+11 | 0.538293E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245479E+11 | 0.616942E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.755149E+10 | 0.332689E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146162E+11 | 0.494376E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216798E+11 | 0.651044E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276097E+11 | 0.760609E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.787623E+10 | 0.343325E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132938E+11 | 0.436317E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.184590E+11 | 0.515172E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247697E+11 | 0.636350E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196754E+12 | 0.600642E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.607110E+10 | 0.302850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.276097E+11 | 0.760609E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.391839E+11 | 0.253991E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.888790E+11 | 0.330392E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167773E+12 | 0.489810E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.221168E+12 | 0.569076E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.664185E+11 | 0.308059E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136880E+12 | 0.468049E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203400E+12 | 0.616018E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.261785E+12 | 0.724503E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.702138E+11 | 0.319162E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.114950E+12 | 0.396325E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159738E+12 | 0.465235E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211531E+12 | 0.567426E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174192E+13 | 0.550805E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.391839E+11 | 0.253991E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.261785E+12 | 0.724503E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.190579E+10 | 0.216380E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.689998E+10 | 0.296272E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.151477E+11 | 0.465247E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.205186E+11 | 0.546775E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.611151E+10 | 0.301655E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137460E+11 | 0.473693E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204192E+11 | 0.622529E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262095E+11 | 0.730460E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.673941E+10 | 0.317626E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.996857E+10 | 0.372123E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.139703E+11 | 0.434450E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.187628E+11 | 0.530735E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160399E+12 | 0.530794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.190579E+10 | 0.216380E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262095E+11 | 0.730460E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.530789E+10 | 0.139367E+11 | 0.119266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510629E+10 | 0.127235E+11 | 0.115329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811955E+10 | 0.154410E+11 | 0.621399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.884514E+10 | 0.117473E+11 | 0.326199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989378E+10 | 0.342962E+11 | 0.257294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194178E+11 | 0.121447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216760E+11 | 0.137324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201782E+11 | 0.123083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127331E+11 | 0.770234E+11 | 0.327441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.771586E+10 | 0.199038E+11 | 0.506451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677973E+10 | 0.154334E+11 | 0.744214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.602828E+10 | 0.159174E+11 | 0.179224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131802E+12 | 0.598277E+12 | 0.639493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.510629E+10 | 0.117473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216760E+11 | 0.137324E+12 | 0.179224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.358130E+11 | 0.838787E+11 | 0.184753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335290E+11 | 0.719761E+11 | 0.194879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484455E+11 | 0.118505E+12 | 0.116948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448373E+11 | 0.965082E+11 | 0.730425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.722266E+11 | 0.292364E+12 | 0.562555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122713E+12 | 0.931107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116073E+12 | 0.935541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115847E+12 | 0.902272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853454E+11 | 0.630126E+12 | 0.453596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481560E+11 | 0.223757E+12 | 0.922486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378566E+11 | 0.110504E+12 | 0.147678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328068E+11 | 0.566342E+11 | 0.293938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793648E+12 | 0.445317E+13 | 0.111365E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328068E+11 | 0.566342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122713E+12 | 0.935541E+12 | 0.293938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.361169E+10 | 0.396128E+10 | 0.345538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335527E+10 | 0.391430E+10 | 0.351926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450706E+10 | 0.900666E+10 | 0.224311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430061E+10 | 0.746058E+10 | 0.153489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637207E+10 | 0.296599E+11 | 0.154144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129212E+11 | 0.104572E+12 | 1688181.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119412E+11 | 0.103156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117492E+11 | 0.998789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.801644E+10 | 0.652625E+11 | 0.820007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414657E+10 | 0.139819E+11 | 0.178373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337731E+10 | 0.655891E+10 | 0.263105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361883E+10 | 0.339121E+10 | 0.510675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.779175E+11 | 0.450805E+12 | 0.205105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.335527E+10 | 0.339121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129212E+11 | 0.104572E+12 | 0.510675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.627916E+10 | 0.270567E+10 | 0.225952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623886E+10 | 0.228756E+09 | 0.226668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.941394E+10 | 0.531894E+10 | 0.711079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690409E+10 | 0.674288E+10 | 82975546.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110851E+11 | 0.202845E+11 | 6172551.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.824467E+10 | 0.328398E+11 | 67.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.559037E+10 | 0.290913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114887E+11 | 0.482149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115042E+11 | 0.397638E+11 | 3204535.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137087E+11 | 0.983681E+10 | 0.200744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103635E+11 | 0.460979E+10 | 0.472747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877062E+10 | 0.234985E+10 | 0.366821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109592E+12 | 0.201987E+12 | 0.967134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.559037E+10 | 0.228756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137087E+11 | 0.482149E+11 | 0.366821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132700E+12 | 0.102744E+11 | 0.00 | 0.00 | 0.00 | 0.179357E+12 | 0.00 | 0.00 |
February | 0.119858E+12 | 0.138837E+11 | 0.00 | 0.00 | 0.00 | 0.233245E+12 | 0.00 | 0.00 |
March | 0.132700E+12 | 0.323836E+11 | 0.00 | 0.00 | 0.00 | 0.263393E+12 | 0.00 | 0.00 |
April | 0.128419E+12 | 0.680681E+11 | 0.00 | 0.00 | 0.00 | 0.245952E+12 | 0.00 | 0.00 |
May | 0.132700E+12 | 0.271148E+11 | 0.00 | 0.00 | 0.00 | 0.163829E+12 | 0.00 | 0.00 |
June | 0.128419E+12 | 0.285274E+12 | 0.00 | 0.00 | 0.00 | 0.999704E+11 | 0.00 | 0.00 |
July | 0.132700E+12 | 0.564969E+12 | 0.00 | 0.00 | 0.00 | 0.113515E+12 | 0.00 | 0.00 |
August | 0.132700E+12 | 0.799039E+12 | 0.00 | 0.00 | 0.00 | 0.112873E+12 | 0.00 | 0.00 |
September | 0.128419E+12 | 0.871397E+11 | 0.00 | 0.00 | 0.00 | 0.162572E+12 | 0.00 | 0.00 |
October | 0.132700E+12 | 0.277411E+11 | 0.00 | 0.00 | 0.00 | 0.243020E+12 | 0.00 | 0.00 |
November | 0.128419E+12 | 0.272408E+11 | 0.00 | 0.00 | 0.00 | 0.254503E+12 | 0.00 | 0.00 |
December | 0.132700E+12 | 0.344378E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.156244E+13 | 0.197757E+13 | 0.00 | 0.00 | 0.00 | 0.233887E+13 | 0.00 | 0.00 |
Minimum of Months | 0.119858E+12 | 0.102744E+11 | 0.00 | 0.00 | 0.00 | 0.999704E+11 | 0.00 | 0.00 |
Maximum of Months | 0.132700E+12 | 0.799039E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.179907E+10 | 0.484166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162497E+10 | 0.898462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179907E+10 | 0.155513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174104E+10 | 0.201195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179907E+10 | 0.602367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174104E+10 | 0.114135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179907E+10 | 0.169684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179907E+10 | 0.218027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174104E+10 | 0.618402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179907E+10 | 0.107297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174104E+10 | 0.150483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179907E+10 | 0.202053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211826E+11 | 0.157873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162497E+10 | 0.484166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179907E+10 | 0.218027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.172761E+11 | 0.310609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156042E+11 | 0.714440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172761E+11 | 0.136068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167188E+11 | 0.180979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172761E+11 | 0.528887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167188E+11 | 0.106794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172761E+11 | 0.159074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172761E+11 | 0.206611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167188E+11 | 0.550164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172761E+11 | 0.925938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167188E+11 | 0.129933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172761E+11 | 0.172065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203412E+12 | 0.139453E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156042E+11 | 0.310609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172761E+11 | 0.206611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176187E+10 | 0.150387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159137E+10 | 0.552863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176187E+10 | 0.122571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170504E+10 | 0.167559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176187E+10 | 0.485684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170504E+10 | 0.107141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176187E+10 | 0.159557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176187E+10 | 0.206667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170504E+10 | 0.526819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176187E+10 | 0.800922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170504E+10 | 0.113308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176187E+10 | 0.152173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207446E+11 | 0.128064E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159137E+10 | 0.150387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176187E+10 | 0.206667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.530789E+10 | 0.119266E+11 | 0.139367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510629E+10 | 0.115329E+11 | 0.127235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811955E+10 | 0.621399E+10 | 0.154410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.884514E+10 | 0.326199E+10 | 0.117473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989378E+10 | 0.257294E+09 | 0.342962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194178E+11 | 0.00 | 0.121447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216760E+11 | 0.00 | 0.137324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201782E+11 | 0.00 | 0.123083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127331E+11 | 0.327441E+09 | 0.770234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.771586E+10 | 0.506451E+10 | 0.199038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.677973E+10 | 0.744214E+10 | 0.154334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.602828E+10 | 0.179224E+11 | 0.159174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131802E+12 | 0.639493E+11 | 0.598277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.510629E+10 | 0.00 | 0.117473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.216760E+11 | 0.179224E+11 | 0.137324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.358130E+11 | 0.184753E+12 | 0.838787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335290E+11 | 0.194879E+12 | 0.719761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484455E+11 | 0.116948E+12 | 0.118505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448373E+11 | 0.730425E+11 | 0.965082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.722266E+11 | 0.562555E+10 | 0.292364E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122713E+12 | 0.00 | 0.931107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116073E+12 | 0.00 | 0.935541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115847E+12 | 0.00 | 0.902272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.853454E+11 | 0.453596E+10 | 0.630126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481560E+11 | 0.922486E+11 | 0.223757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378566E+11 | 0.147678E+12 | 0.110504E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328068E+11 | 0.293938E+12 | 0.566342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793648E+12 | 0.111365E+13 | 0.445317E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328068E+11 | 0.00 | 0.566342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122713E+12 | 0.293938E+12 | 0.935541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.361169E+10 | 0.345538E+11 | 0.396128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335527E+10 | 0.351926E+11 | 0.391430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450706E+10 | 0.224311E+11 | 0.900666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430061E+10 | 0.153489E+11 | 0.746058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637207E+10 | 0.154144E+10 | 0.296599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129212E+11 | 1688181.92 | 0.104572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119412E+11 | 0.00 | 0.103156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117492E+11 | 0.00 | 0.998789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.801644E+10 | 0.820007E+09 | 0.652625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414657E+10 | 0.178373E+11 | 0.139819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337731E+10 | 0.263105E+11 | 0.655891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361883E+10 | 0.510675E+11 | 0.339121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.779175E+11 | 0.205105E+12 | 0.450805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.335527E+10 | 0.00 | 0.339121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129212E+11 | 0.510675E+11 | 0.104572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.627916E+10 | 0.225952E+10 | 0.270567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623886E+10 | 0.226668E+10 | 0.228756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.941394E+10 | 0.711079E+09 | 0.531894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690409E+10 | 82975546.06 | 0.674288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110851E+11 | 6172551.78 | 0.202845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.824467E+10 | 67.89 | 0.328398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.559037E+10 | 0.00 | 0.290913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114887E+11 | 0.00 | 0.482149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115042E+11 | 3204535.28 | 0.397638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137087E+11 | 0.200744E+09 | 0.983681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103635E+11 | 0.472747E+09 | 0.460979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877062E+10 | 0.366821E+10 | 0.234985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109592E+12 | 0.967134E+10 | 0.201987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.559037E+10 | 0.00 | 0.228756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137087E+11 | 0.366821E+10 | 0.482149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132700E+12 | 0.00 | 0.157976E+11 | 0.00 | 0.552321E+10 | 0.00 | 0.00 | 0.00 | 0.180164E+12 | 0.00 | 0.00 | 0.00 |
February | 0.119858E+12 | 0.00 | 0.202310E+11 | 0.00 | 0.634727E+10 | 0.00 | 0.00 | 0.00 | 0.234295E+12 | 0.00 | 0.00 | 0.00 |
March | 0.132700E+12 | 0.00 | 0.453194E+11 | 0.00 | 0.129358E+11 | 0.00 | 0.00 | 0.00 | 0.264579E+12 | 0.00 | 0.00 | 0.00 |
April | 0.128419E+12 | 0.00 | 0.910338E+11 | 0.00 | 0.229658E+11 | 0.00 | 0.00 | 0.00 | 0.247059E+12 | 0.00 | 0.00 | 0.00 |
May | 0.132700E+12 | 0.00 | 0.385293E+11 | 0.00 | 0.114146E+11 | 0.00 | 0.00 | 0.00 | 0.164567E+12 | 0.00 | 0.00 | 0.00 |
June | 0.128419E+12 | 0.00 | 0.382286E+12 | 0.00 | 0.970120E+11 | 0.00 | 0.00 | 0.00 | 0.100420E+12 | 0.00 | 0.00 | 0.00 |
July | 0.132700E+12 | 0.00 | 0.741812E+12 | 0.00 | 0.176842E+12 | 0.00 | 0.00 | 0.00 | 0.114026E+12 | 0.00 | 0.00 | 0.00 |
August | 0.132700E+12 | 0.00 | 0.103635E+13 | 0.00 | 0.237312E+12 | 0.00 | 0.00 | 0.00 | 0.113381E+12 | 0.00 | 0.00 | 0.00 |
September | 0.128419E+12 | 0.00 | 0.118855E+12 | 0.00 | 0.317151E+11 | 0.00 | 0.00 | 0.00 | 0.163304E+12 | 0.00 | 0.00 | 0.00 |
October | 0.132700E+12 | 0.00 | 0.391193E+11 | 0.00 | 0.113782E+11 | 0.00 | 0.00 | 0.00 | 0.244114E+12 | 0.00 | 0.00 | 0.00 |
November | 0.128419E+12 | 0.00 | 0.381427E+11 | 0.00 | 0.109019E+11 | 0.00 | 0.00 | 0.00 | 0.255649E+12 | 0.00 | 0.00 | 0.00 |
December | 0.132700E+12 | 0.00 | 0.479889E+11 | 0.00 | 0.135511E+11 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156244E+13 | 0.00 | 0.261547E+13 | 0.00 | 0.637899E+12 | 0.00 | 0.00 | 0.00 | 0.234940E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119858E+12 | 0.00 | 0.157976E+11 | 0.00 | 0.552321E+10 | 0.00 | 0.00 | 0.00 | 0.100420E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132700E+12 | 0.00 | 0.103635E+13 | 0.00 | 0.237312E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.179907E+10 | 0.00 | 0.607110E+10 | 0.00 | 0.122943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162497E+10 | 0.00 | 0.111442E+11 | 0.00 | 0.215962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179907E+10 | 0.00 | 0.191352E+11 | 0.00 | 0.358385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174104E+10 | 0.00 | 0.245479E+11 | 0.00 | 0.442839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179907E+10 | 0.00 | 0.755149E+10 | 0.00 | 0.152782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174104E+10 | 0.00 | 0.146162E+11 | 0.00 | 0.320272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.179907E+10 | 0.00 | 0.216798E+11 | 0.00 | 0.471137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179907E+10 | 0.00 | 0.276097E+11 | 0.00 | 0.580702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174104E+10 | 0.00 | 0.787623E+10 | 0.00 | 0.169221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179907E+10 | 0.00 | 0.132938E+11 | 0.00 | 0.256409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174104E+10 | 0.00 | 0.184590E+11 | 0.00 | 0.341068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179907E+10 | 0.00 | 0.247697E+11 | 0.00 | 0.456442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211826E+11 | 0.00 | 0.196754E+12 | 0.00 | 0.388816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162497E+10 | 0.00 | 0.607110E+10 | 0.00 | 0.122943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179907E+10 | 0.00 | 0.276097E+11 | 0.00 | 0.580702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.172761E+11 | 0.00 | 0.391839E+11 | 0.00 | 0.812300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156042E+11 | 0.00 | 0.888790E+11 | 0.00 | 0.174350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172761E+11 | 0.00 | 0.167773E+12 | 0.00 | 0.317049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167188E+11 | 0.00 | 0.221168E+12 | 0.00 | 0.401888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172761E+11 | 0.00 | 0.664185E+11 | 0.00 | 0.135298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167188E+11 | 0.00 | 0.136880E+12 | 0.00 | 0.300861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172761E+11 | 0.00 | 0.203400E+12 | 0.00 | 0.443258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172761E+11 | 0.00 | 0.261785E+12 | 0.00 | 0.551742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167188E+11 | 0.00 | 0.702138E+11 | 0.00 | 0.151974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172761E+11 | 0.00 | 0.114950E+12 | 0.00 | 0.223564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167188E+11 | 0.00 | 0.159738E+12 | 0.00 | 0.298047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172761E+11 | 0.00 | 0.211531E+12 | 0.00 | 0.394665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203412E+12 | 0.00 | 0.174192E+13 | 0.00 | 0.347393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156042E+11 | 0.00 | 0.391839E+11 | 0.00 | 0.812300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172761E+11 | 0.00 | 0.261785E+12 | 0.00 | 0.551742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176187E+10 | 0.00 | 0.190579E+10 | 0.00 | 0.401923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159137E+10 | 0.00 | 0.689998E+10 | 0.00 | 0.137135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176187E+10 | 0.00 | 0.151477E+11 | 0.00 | 0.289060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170504E+10 | 0.00 | 0.205186E+11 | 0.00 | 0.376271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176187E+10 | 0.00 | 0.611151E+10 | 0.00 | 0.125467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170504E+10 | 0.00 | 0.137460E+11 | 0.00 | 0.303189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176187E+10 | 0.00 | 0.204192E+11 | 0.00 | 0.446342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176187E+10 | 0.00 | 0.262095E+11 | 0.00 | 0.554273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170504E+10 | 0.00 | 0.673941E+10 | 0.00 | 0.147122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176187E+10 | 0.00 | 0.996857E+10 | 0.00 | 0.195935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170504E+10 | 0.00 | 0.139703E+11 | 0.00 | 0.263946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176187E+10 | 0.00 | 0.187628E+11 | 0.00 | 0.354548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207446E+11 | 0.00 | 0.160399E+12 | 0.00 | 0.323348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159137E+10 | 0.00 | 0.190579E+10 | 0.00 | 0.401923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176187E+10 | 0.00 | 0.262095E+11 | 0.00 | 0.554273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.107305E+09 | 0.00 | 0.00 | 0.580177E+11 | 0.00 | 0.58 |
February | 0.00 | 0.00 | 0.00 | 92801320.35 | 0.00 | 0.00 | 0.529935E+11 | 0.00 | 0.57 |
March | 0.00 | 0.00 | 0.00 | 0.109776E+09 | 0.00 | 0.00 | 0.602053E+11 | 0.00 | 0.82 |
April | 0.00 | 0.00 | 0.00 | 97242508.34 | 0.00 | 0.00 | 0.524684E+11 | 0.00 | 0.79 |
May | 0.00 | 13196555.79 | 0.00 | 0.109739E+09 | 0.00 | 0.00 | 0.460795E+11 | 0.00 | 1.04 |
June | 0.00 | 0.246604E+09 | 0.00 | 0.104684E+09 | 0.00 | 0.00 | 0.153828E+11 | 0.00 | 0.53 |
July | 0.00 | 0.746014E+09 | 0.00 | 0.119370E+09 | 0.00 | 0.00 | 0.879202E+10 | 0.00 | 0.39 |
August | 0.00 | 0.650678E+09 | 0.00 | 0.138337E+09 | 0.00 | 0.00 | 0.192278E+11 | 0.00 | 0.68 |
September | 0.00 | 0.134462E+09 | 0.00 | 0.145049E+09 | 0.00 | 0.00 | 0.285893E+11 | 0.00 | 0.86 |
October | 0.00 | 0.00 | 0.00 | 0.128254E+09 | 0.00 | 0.00 | 0.647675E+11 | 0.00 | 0.97 |
November | 0.00 | 0.00 | 0.00 | 0.116330E+09 | 0.00 | 0.00 | 0.638832E+11 | 0.00 | 0.75 |
December | 0.00 | 0.00 | 0.00 | 0.119248E+09 | 0.00 | 0.00 | 0.642054E+11 | 0.00 | 0.63 |
Annual Sum or Average | 0.00 | 0.179095E+10 | 0.00 | 0.138814E+10 | 0.00 | 0.00 | 0.534612E+12 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 92801320.35 | 0.00 | 0.00 | 0.879202E+10 | 0.00 | 0.39 |
Maximum of Months | 0.00 | 0.746014E+09 | 0.00 | 0.145049E+09 | 0.00 | 0.00 | 0.647675E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259452E+10 | 0.00 | 0.00 | 85046742.56 | 0.00 | 0.00 | 0.461555E+11 | 0.00 | 0.44 |
February | 0.257050E+10 | 0.00 | 0.00 | 78758547.31 | 0.00 | 0.00 | 0.415721E+11 | 0.00 | 0.41 |
March | 0.243968E+10 | 0.00 | 0.00 | 0.104095E+09 | 0.00 | 0.00 | 0.544415E+11 | 0.00 | 0.71 |
April | 0.158553E+10 | 0.00 | 0.00 | 98689738.74 | 0.00 | 0.00 | 0.534169E+11 | 0.00 | 0.80 |
May | 0.230043E+10 | 6787282.00 | 0.00 | 96633487.12 | 582479.94 | 0.00 | 0.430315E+11 | 0.00 | 0.95 |
June | 0.375173E+10 | 0.711113E+09 | 0.00 | 99676131.53 | 42220183.83 | 0.00 | 0.190260E+11 | 0.00 | 0.91 |
July | 0.577289E+10 | 0.786144E+09 | 0.00 | 0.112445E+09 | 0.139414E+09 | 0.00 | 0.178247E+11 | 0.00 | 1.02 |
August | 0.748661E+10 | 0.720515E+09 | 0.00 | 0.115914E+09 | 0.248763E+09 | 0.00 | 0.236830E+11 | 0.00 | 1.05 |
September | 0.186810E+10 | 0.136750E+09 | 0.00 | 0.108192E+09 | 65261749.68 | 0.00 | 0.281269E+11 | 0.00 | 0.91 |
October | 0.301378E+10 | 0.00 | 0.00 | 0.101814E+09 | 0.00 | 0.00 | 0.510046E+11 | 0.00 | 0.73 |
November | 0.293850E+10 | 0.00 | 0.00 | 0.101241E+09 | 0.00 | 0.00 | 0.509438E+11 | 0.00 | 0.59 |
December | 0.257199E+10 | 0.00 | 0.00 | 0.101806E+09 | 0.00 | 0.00 | 0.536374E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.388943E+11 | 0.236131E+10 | 0.00 | 0.120431E+10 | 0.496242E+09 | 0.00 | 0.482864E+12 | 0.00 | 0.75 |
Minimum of Months | 0.158553E+10 | 0.00 | 0.00 | 78758547.31 | 0.00 | 0.00 | 0.178247E+11 | 0.00 | 0.41 |
Maximum of Months | 0.748661E+10 | 0.786144E+09 | 0.00 | 0.115914E+09 | 0.248763E+09 | 0.00 | 0.544415E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129256E+12 | 0.00 | 0.00 | 0.367627E+09 | 0.00 | 0.00 | 0.245473E+12 | 0.00 | 0.32 |
February | 0.155859E+12 | 0.00 | 0.00 | 0.280564E+09 | 0.00 | 12076662.12 | 0.182539E+12 | 0.00 | 0.31 |
March | 0.101810E+12 | 0.00 | 0.00 | 0.491728E+09 | 0.00 | 0.00 | 0.295952E+12 | 0.00 | 0.49 |
April | 0.584280E+11 | 0.00 | 0.00 | 0.459094E+09 | 0.00 | 0.00 | 0.284301E+12 | 0.00 | 0.50 |
May | 0.220770E+11 | 39453913.88 | 0.00 | 0.717857E+09 | 12609553.39 | 0.00 | 0.325208E+12 | 0.00 | 0.74 |
June | 0.147608E+11 | 0.735783E+10 | 0.00 | 0.657584E+09 | 0.586960E+09 | 0.00 | 0.132130E+12 | 0.00 | 0.63 |
July | 0.122774E+11 | 0.689187E+10 | 0.00 | 0.651745E+09 | 0.136729E+10 | 0.00 | 0.106781E+12 | 0.00 | 0.59 |
August | 0.143119E+11 | 0.695611E+10 | 0.00 | 0.788787E+09 | 0.938919E+09 | 0.00 | 0.162482E+12 | 0.00 | 0.65 |
September | 0.133791E+11 | 0.128549E+10 | 0.00 | 0.760594E+09 | 0.541140E+09 | 0.00 | 0.199816E+12 | 0.00 | 0.66 |
October | 0.607381E+11 | 0.00 | 0.00 | 0.581866E+09 | 0.00 | 0.00 | 0.290590E+12 | 0.00 | 0.45 |
November | 0.104408E+12 | 0.00 | 0.00 | 0.416586E+09 | 0.00 | 0.00 | 0.261719E+12 | 0.00 | 0.38 |
December | 0.190431E+12 | 0.00 | 0.00 | 0.266155E+09 | 0.00 | 0.451628E+09 | 0.207398E+12 | 0.00 | 0.33 |
Annual Sum or Average | 0.877736E+12 | 0.225308E+11 | 0.00 | 0.644019E+10 | 0.344692E+10 | 0.463705E+09 | 0.269439E+13 | 0.00 | 0.51 |
Minimum of Months | 0.122774E+11 | 0.00 | 0.00 | 0.266155E+09 | 0.00 | 0.00 | 0.106781E+12 | 0.00 | 0.31 |
Maximum of Months | 0.190431E+12 | 0.735783E+10 | 0.00 | 0.788787E+09 | 0.136729E+10 | 0.451628E+09 | 0.325208E+12 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241127E+11 | 0.00 | 0.00 | 7418815.22 | 0.00 | 0.170337E+10 | 0.515427E+10 | 0.00 | 0.30 |
February | 0.212673E+11 | 0.00 | 0.00 | 6651841.43 | 0.00 | 0.202640E+10 | 0.530486E+10 | 0.00 | 0.29 |
March | 0.180423E+11 | 0.00 | 0.00 | 24440790.45 | 0.00 | 0.435321E+09 | 0.157150E+11 | 0.00 | 0.45 |
April | 0.128118E+11 | 0.00 | 0.00 | 26598702.72 | 0.00 | 0.680284E+09 | 0.177602E+11 | 0.00 | 0.48 |
May | 0.508204E+10 | 489863.04 | 0.00 | 52915822.97 | 18584.27 | 0.103232E+09 | 0.259781E+11 | 0.00 | 0.70 |
June | 0.154735E+10 | 0.513652E+09 | 0.00 | 69103138.07 | 41570548.86 | 0.00 | 0.124133E+11 | 0.00 | 0.66 |
July | 0.127891E+10 | 0.452074E+09 | 0.00 | 70321126.60 | 92222669.08 | 0.00 | 0.101241E+11 | 0.00 | 0.61 |
August | 0.145828E+10 | 0.529331E+09 | 0.00 | 79116810.81 | 0.105206E+09 | 0.00 | 0.147156E+11 | 0.00 | 0.64 |
September | 0.269380E+10 | 91230275.57 | 0.00 | 64913290.89 | 43905243.22 | 0.00 | 0.156256E+11 | 0.00 | 0.63 |
October | 0.142496E+11 | 0.00 | 0.00 | 25855453.91 | 0.00 | 0.858788E+09 | 0.150153E+11 | 0.00 | 0.44 |
November | 0.209740E+11 | 0.00 | 0.00 | 12000776.70 | 0.00 | 0.103439E+10 | 0.782467E+10 | 0.00 | 0.34 |
December | 0.246145E+11 | 0.00 | 0.00 | 3798582.47 | 0.00 | 0.392097E+10 | 0.365750E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.148133E+12 | 0.158678E+10 | 0.00 | 0.443135E+09 | 0.282923E+09 | 0.107628E+11 | 0.149288E+12 | 0.00 | 0.49 |
Minimum of Months | 0.127891E+10 | 0.00 | 0.00 | 3798582.47 | 0.00 | 0.00 | 0.365750E+10 | 0.00 | 0.29 |
Maximum of Months | 0.246145E+11 | 0.529331E+09 | 0.00 | 79116810.81 | 0.105206E+09 | 0.392097E+10 | 0.259781E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.287795E+10 | 0.00 | 0.00 | 1123725.68 | 0.00 | 0.302089E+09 | 0.545434E+09 | 0.00 | 0.27 |
February | 0.270791E+10 | 0.00 | 0.00 | 1016621.67 | 0.00 | 0.248433E+09 | 0.545531E+09 | 0.00 | 0.26 |
March | 0.221037E+10 | 0.00 | 0.00 | 4315294.73 | 0.00 | 2161817.02 | 0.238045E+10 | 0.00 | 0.50 |
April | 0.137724E+10 | 0.00 | 0.00 | 6233732.72 | 0.00 | 0.00 | 0.357992E+10 | 0.00 | 0.65 |
May | 0.635465E+09 | 1852852.72 | 0.00 | 10850234.88 | 73248.97 | 0.00 | 0.470826E+10 | 0.00 | 1.01 |
June | 0.514543E+09 | 0.147491E+09 | 0.00 | 15596872.24 | 4703741.14 | 0.00 | 0.277242E+10 | 0.00 | 1.15 |
July | 0.811748E+09 | 0.168106E+09 | 0.00 | 17086535.28 | 12938663.33 | 0.00 | 0.239639E+10 | 0.00 | 1.23 |
August | 0.101126E+10 | 0.144425E+09 | 0.00 | 16342235.50 | 31282851.32 | 0.00 | 0.295488E+10 | 0.00 | 1.17 |
September | 0.534027E+09 | 30195577.52 | 0.00 | 12243241.82 | 8206902.69 | 0.00 | 0.265265E+10 | 0.00 | 0.89 |
October | 0.188960E+10 | 0.00 | 0.00 | 4708273.43 | 0.00 | 58724225.98 | 0.233599E+10 | 0.00 | 0.51 |
November | 0.244338E+10 | 0.00 | 0.00 | 2388484.49 | 0.00 | 0.128566E+09 | 0.124443E+10 | 0.00 | 0.36 |
December | 0.243421E+10 | 0.00 | 0.00 | 1368784.92 | 0.00 | 0.774647E+09 | 0.677086E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.194477E+11 | 0.492070E+09 | 0.00 | 93274037.35 | 57205407.45 | 0.151462E+10 | 0.267934E+11 | 0.00 | 0.69 |
Minimum of Months | 0.514543E+09 | 0.00 | 0.00 | 1016621.67 | 0.00 | 0.00 | 0.545434E+09 | 0.00 | 0.26 |
Maximum of Months | 0.287795E+10 | 0.168106E+09 | 0.00 | 17086535.28 | 31282851.32 | 0.774647E+09 | 0.470826E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147635E+10 | 0.00 | 0.00 | 4123804.81 | 0.00 | 0.183365E+09 | 0.157357E+10 | 0.00 | 0.38 |
February | 0.127104E+10 | 0.00 | 0.00 | 5564648.77 | 0.00 | 0.227545E+09 | 0.211073E+10 | 0.00 | 0.44 |
March | 0.119607E+10 | 0.00 | 0.00 | 10191584.71 | 0.00 | 10841869.07 | 0.430594E+10 | 0.00 | 0.93 |
April | 0.778093E+09 | 0.00 | 0.00 | 9478238.76 | 0.00 | 15045802.93 | 0.484733E+10 | 0.00 | 1.11 |
May | 0.291630E+09 | 1373226.40 | 0.00 | 13439861.76 | 46925.32 | 0.00 | 0.570944E+10 | 0.00 | 1.66 |
June | 0.301091E+09 | 0.108683E+09 | 0.00 | 18664091.04 | 3229931.60 | 0.00 | 0.348438E+10 | 0.00 | 1.94 |
July | 0.480491E+09 | 0.131639E+09 | 0.00 | 20609063.66 | 6464826.42 | 0.00 | 0.246175E+10 | 0.00 | 1.77 |
August | 0.622478E+09 | 0.109218E+09 | 0.00 | 19958814.06 | 20040660.61 | 0.00 | 0.389093E+10 | 0.00 | 1.93 |
September | 0.268779E+09 | 25487987.99 | 0.00 | 16308680.30 | 5257569.07 | 0.00 | 0.371324E+10 | 0.00 | 1.64 |
October | 0.980862E+09 | 0.00 | 0.00 | 9246134.12 | 0.00 | 0.110007E+09 | 0.353182E+10 | 0.00 | 0.87 |
November | 0.131406E+10 | 0.00 | 0.00 | 5096898.74 | 0.00 | 0.124035E+09 | 0.204104E+10 | 0.00 | 0.52 |
December | 0.138388E+10 | 0.00 | 0.00 | 3113190.72 | 0.00 | 0.510955E+09 | 0.109152E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.103648E+11 | 0.376401E+09 | 0.00 | 0.135795E+09 | 35039913.01 | 0.118180E+10 | 0.387617E+11 | 0.00 | 1.13 |
Minimum of Months | 0.268779E+09 | 0.00 | 0.00 | 3113190.72 | 0.00 | 0.00 | 0.109152E+10 | 0.00 | 0.33 |
Maximum of Months | 0.147635E+10 | 0.131639E+09 | 0.00 | 20609063.66 | 20040660.61 | 0.510955E+09 | 0.570944E+10 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156095E+10 | 0.00 | 0.00 | 27700379.46 | 0.00 | 0.300306E+09 | 0.871891E+10 | 0.00 | 0.90 |
February | 0.138499E+10 | 0.00 | 0.00 | 23183586.61 | 0.00 | 0.396369E+09 | 0.809320E+10 | 0.00 | 0.83 |
March | 0.170587E+10 | 0.00 | 0.00 | 22768030.14 | 0.00 | 35848655.35 | 0.880088E+10 | 0.00 | 1.29 |
April | 0.125145E+10 | 0.00 | 0.00 | 12381980.13 | 0.00 | 70165420.56 | 0.682149E+10 | 0.00 | 1.15 |
May | 0.729678E+09 | 2648855.52 | 0.00 | 13886451.89 | 73177.86 | 0.00 | 0.576133E+10 | 0.00 | 1.27 |
June | 0.540796E+09 | 0.159567E+09 | 0.00 | 16269864.15 | 5078840.98 | 0.00 | 0.253855E+10 | 0.00 | 1.18 |
July | 0.825230E+09 | 0.213103E+09 | 0.00 | 18032542.75 | 9802762.40 | 0.00 | 0.226367E+10 | 0.00 | 1.27 |
August | 0.966164E+09 | 0.210621E+09 | 0.00 | 24962343.02 | 30883039.18 | 0.00 | 0.373246E+10 | 0.00 | 1.47 |
September | 0.439057E+09 | 59080762.07 | 0.00 | 27135452.30 | 7299381.33 | 0.00 | 0.478235E+10 | 0.00 | 1.59 |
October | 0.116495E+10 | 0.00 | 0.00 | 33861181.96 | 0.00 | 0.234451E+09 | 0.966091E+10 | 0.00 | 1.54 |
November | 0.136848E+10 | 0.00 | 0.00 | 32297126.63 | 0.00 | 0.145707E+09 | 0.947230E+10 | 0.00 | 1.16 |
December | 0.155742E+10 | 0.00 | 0.00 | 24334444.81 | 0.00 | 0.606624E+09 | 0.735972E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.134950E+11 | 0.645020E+09 | 0.00 | 0.276813E+09 | 53137201.74 | 0.178947E+10 | 0.780058E+11 | 0.00 | 1.21 |
Minimum of Months | 0.439057E+09 | 0.00 | 0.00 | 12381980.13 | 0.00 | 0.00 | 0.226367E+10 | 0.00 | 0.82 |
Maximum of Months | 0.170587E+10 | 0.213103E+09 | 0.00 | 33861181.96 | 30883039.18 | 0.606624E+09 | 0.966091E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125318E+10 | 0.00 | 0.00 | 6369612.71 | 0.00 | 24105810.71 | 0.292533E+10 | 0.00 | 0.55 |
February | 0.989291E+09 | 0.00 | 0.00 | 8293421.03 | 0.00 | 1522911.07 | 0.369637E+10 | 0.00 | 0.60 |
March | 0.400752E+09 | 0.00 | 0.00 | 17305535.02 | 0.00 | 0.00 | 0.765299E+10 | 0.00 | 1.52 |
April | 0.148466E+09 | 0.00 | 0.00 | 16369381.64 | 0.00 | 0.00 | 0.889644E+10 | 0.00 | 1.88 |
May | 0.159238E+09 | 3018677.19 | 0.00 | 16234161.94 | 43102.65 | 0.00 | 0.626890E+10 | 0.00 | 1.94 |
June | 0.157842E+09 | 0.198972E+09 | 0.00 | 19556632.57 | 380403.51 | 0.00 | 0.303371E+10 | 0.00 | 1.84 |
July | 0.199843E+09 | 0.220684E+09 | 0.00 | 20068486.69 | 1006876.99 | 0.00 | 0.285562E+10 | 0.00 | 1.92 |
August | 0.151057E+09 | 0.252292E+09 | 0.00 | 27836383.24 | 2081912.99 | 0.00 | 0.465170E+10 | 0.00 | 2.26 |
September | 0.159244E+09 | 47317293.77 | 0.00 | 17636043.41 | 1184544.58 | 0.00 | 0.350418E+10 | 0.00 | 1.67 |
October | 0.595650E+09 | 0.00 | 0.00 | 16043668.63 | 0.00 | 0.00 | 0.593032E+10 | 0.00 | 1.40 |
November | 0.544243E+09 | 0.00 | 0.00 | 12572074.10 | 0.00 | 0.00 | 0.529247E+10 | 0.00 | 0.95 |
December | 0.844084E+09 | 0.00 | 0.00 | 10899395.29 | 0.00 | 6048246.44 | 0.460246E+10 | 0.00 | 0.71 |
Annual Sum or Average | 0.560288E+10 | 0.722284E+09 | 0.00 | 0.189185E+09 | 4696840.71 | 31676968.22 | 0.593105E+11 | 0.00 | 1.44 |
Minimum of Months | 0.148466E+09 | 0.00 | 0.00 | 6369612.71 | 0.00 | 0.00 | 0.285562E+10 | 0.00 | 0.55 |
Maximum of Months | 0.125318E+10 | 0.252292E+09 | 0.00 | 27836383.24 | 2081912.99 | 24105810.71 | 0.889644E+10 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211145E+11 | 0.00 | 0.00 | 186760.76 | 0.00 | 0.200007E+11 | 0.130949E+09 | 0.00 | 0.28 |
February | 0.184835E+11 | 0.00 | 0.00 | 208395.54 | 0.00 | 0.200809E+11 | 0.133747E+09 | 0.00 | 0.28 |
March | 0.238714E+11 | 0.00 | 0.00 | 12784327.79 | 0.00 | 0.100198E+11 | 0.610648E+10 | 0.00 | 0.39 |
April | 0.208242E+11 | 0.00 | 0.00 | 20618778.37 | 0.00 | 0.390291E+10 | 0.110186E+11 | 0.00 | 0.42 |
May | 0.987553E+10 | 11903589.63 | 0.00 | 74317845.03 | 1583880.97 | 92091945.57 | 0.304122E+11 | 0.00 | 0.78 |
June | 0.261024E+10 | 0.192393E+10 | 0.00 | 0.108531E+09 | 72819134.05 | 0.00 | 0.193929E+11 | 0.00 | 0.89 |
July | 0.207870E+10 | 0.196863E+10 | 0.00 | 0.105546E+09 | 0.163917E+09 | 0.00 | 0.151820E+11 | 0.00 | 0.81 |
August | 0.338635E+10 | 0.166684E+10 | 0.00 | 0.107303E+09 | 0.118380E+09 | 0.00 | 0.185284E+11 | 0.00 | 0.75 |
September | 0.677916E+10 | 0.347058E+09 | 0.00 | 80197047.17 | 67972401.70 | 0.139205E+09 | 0.155286E+11 | 0.00 | 0.65 |
October | 0.198703E+11 | 0.00 | 0.00 | 15395681.92 | 0.00 | 0.821331E+10 | 0.539107E+10 | 0.00 | 0.34 |
November | 0.225931E+11 | 0.00 | 0.00 | 4270480.41 | 0.00 | 0.134616E+11 | 0.176186E+10 | 0.00 | 0.30 |
December | 0.165997E+11 | 0.00 | 0.00 | 20978.34 | 0.00 | 0.332259E+11 | 36096066.69 | 0.00 | 0.31 |
Annual Sum or Average | 0.168087E+12 | 0.591837E+10 | 0.00 | 0.529380E+09 | 0.424673E+09 | 0.109136E+12 | 0.123623E+12 | 0.00 | 0.52 |
Minimum of Months | 0.207870E+10 | 0.00 | 0.00 | 20978.34 | 0.00 | 0.00 | 36096066.69 | 0.00 | 0.28 |
Maximum of Months | 0.238714E+11 | 0.196863E+10 | 0.00 | 0.108531E+09 | 0.163917E+09 | 0.332259E+11 | 0.304122E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118735E+11 | 0.00 | 0.00 | 18379709.18 | 0.00 | 0.778652E+10 | 0.746860E+10 | 0.00 | 0.29 |
February | 0.886907E+10 | 0.00 | 0.00 | 33589798.68 | 0.00 | 0.805099E+10 | 0.152566E+11 | 0.00 | 0.38 |
March | 0.958436E+10 | 0.00 | 0.00 | 79456178.71 | 0.00 | 0.395583E+10 | 0.346142E+11 | 0.00 | 0.80 |
April | 0.729597E+10 | 0.00 | 0.00 | 73350498.76 | 0.00 | 0.191853E+10 | 0.358979E+11 | 0.00 | 0.90 |
May | 0.327494E+10 | 10057743.73 | 0.00 | 0.121322E+09 | 1018231.70 | 34788363.74 | 0.492227E+11 | 0.00 | 1.50 |
June | 0.116027E+10 | 0.150313E+10 | 0.00 | 0.172463E+09 | 44412977.90 | 0.00 | 0.322808E+11 | 0.00 | 1.82 |
July | 0.836711E+09 | 0.180195E+10 | 0.00 | 0.172728E+09 | 48832563.57 | 0.00 | 0.205201E+11 | 0.00 | 1.47 |
August | 0.129879E+10 | 0.151075E+10 | 0.00 | 0.187608E+09 | 73824405.27 | 0.00 | 0.367328E+11 | 0.00 | 1.72 |
September | 0.255671E+10 | 0.342217E+09 | 0.00 | 0.142129E+09 | 43083654.81 | 33036911.12 | 0.309892E+11 | 0.00 | 1.44 |
October | 0.802115E+10 | 0.00 | 0.00 | 69729822.91 | 0.00 | 0.432144E+10 | 0.215718E+11 | 0.00 | 0.61 |
November | 0.110464E+11 | 0.00 | 0.00 | 27005879.90 | 0.00 | 0.598798E+10 | 0.106549E+11 | 0.00 | 0.38 |
December | 0.976926E+10 | 0.00 | 0.00 | 9040848.19 | 0.00 | 0.152326E+11 | 0.432888E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.755871E+11 | 0.516811E+10 | 0.00 | 0.110680E+10 | 0.211172E+09 | 0.473217E+11 | 0.299539E+12 | 0.00 | 0.97 |
Minimum of Months | 0.836711E+09 | 0.00 | 0.00 | 9040848.19 | 0.00 | 0.00 | 0.432888E+10 | 0.00 | 0.29 |
Maximum of Months | 0.118735E+11 | 0.180195E+10 | 0.00 | 0.187608E+09 | 73824405.27 | 0.152326E+11 | 0.492227E+11 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160033E+11 | 0.00 | 0.00 | 0.316435E+09 | 0.00 | 0.540848E+10 | 0.966828E+11 | 0.00 | 0.94 |
February | 0.124446E+11 | 0.00 | 0.00 | 0.266289E+09 | 0.00 | 0.837794E+10 | 0.913920E+11 | 0.00 | 0.93 |
March | 0.150607E+11 | 0.00 | 0.00 | 0.229752E+09 | 0.00 | 0.650488E+10 | 0.799820E+11 | 0.00 | 1.21 |
April | 0.152566E+11 | 0.00 | 0.00 | 99385123.36 | 0.00 | 0.333482E+10 | 0.491946E+11 | 0.00 | 0.94 |
May | 0.846589E+10 | 18962104.20 | 0.00 | 0.121959E+09 | 1580272.74 | 0.120252E+09 | 0.482791E+11 | 0.00 | 1.13 |
June | 0.301029E+10 | 0.216588E+10 | 0.00 | 0.124793E+09 | 72620863.40 | 0.00 | 0.190208E+11 | 0.00 | 0.97 |
July | 0.217778E+10 | 0.268164E+10 | 0.00 | 0.125327E+09 | 0.103553E+09 | 0.00 | 0.159544E+11 | 0.00 | 0.92 |
August | 0.263124E+10 | 0.289359E+10 | 0.00 | 0.201306E+09 | 0.112048E+09 | 0.00 | 0.294108E+11 | 0.00 | 1.16 |
September | 0.446242E+10 | 0.841834E+09 | 0.00 | 0.252616E+09 | 56312787.87 | 62640977.80 | 0.408403E+11 | 0.00 | 1.45 |
October | 0.101204E+11 | 0.00 | 0.00 | 0.349882E+09 | 0.00 | 0.717723E+10 | 0.735088E+11 | 0.00 | 1.22 |
November | 0.141068E+11 | 0.00 | 0.00 | 0.349680E+09 | 0.00 | 0.488787E+10 | 0.925988E+11 | 0.00 | 1.09 |
December | 0.164451E+11 | 0.00 | 0.00 | 0.246802E+09 | 0.00 | 0.129501E+11 | 0.802644E+11 | 0.00 | 0.89 |
Annual Sum or Average | 0.120185E+12 | 0.860190E+10 | 0.00 | 0.268423E+10 | 0.346115E+09 | 0.488243E+11 | 0.717129E+12 | 0.00 | 1.07 |
Minimum of Months | 0.217778E+10 | 0.00 | 0.00 | 99385123.36 | 0.00 | 0.00 | 0.159544E+11 | 0.00 | 0.89 |
Maximum of Months | 0.164451E+11 | 0.289359E+10 | 0.00 | 0.349882E+09 | 0.112048E+09 | 0.129501E+11 | 0.966828E+11 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158368E+11 | 0.00 | 0.00 | 26759655.19 | 0.00 | 0.614875E+10 | 0.118994E+11 | 0.00 | 0.39 |
February | 0.131381E+11 | 0.00 | 0.00 | 32874940.81 | 0.00 | 0.690581E+10 | 0.151001E+11 | 0.00 | 0.42 |
March | 0.126853E+11 | 0.00 | 0.00 | 77492700.36 | 0.00 | 0.362459E+10 | 0.284880E+11 | 0.00 | 0.86 |
April | 0.997752E+10 | 0.00 | 0.00 | 61700132.16 | 0.00 | 0.169722E+10 | 0.316735E+11 | 0.00 | 0.96 |
May | 0.425048E+10 | 19180851.25 | 0.00 | 0.113928E+09 | 977033.73 | 38016148.44 | 0.411498E+11 | 0.00 | 1.45 |
June | 0.119945E+10 | 0.286411E+10 | 0.00 | 0.125877E+09 | 5058338.21 | 0.00 | 0.176055E+11 | 0.00 | 1.37 |
July | 0.968688E+09 | 0.258963E+10 | 0.00 | 0.101165E+09 | 46726589.53 | 0.00 | 0.139767E+11 | 0.00 | 1.20 |
August | 0.121056E+10 | 0.263133E+10 | 0.00 | 0.147340E+09 | 15303353.81 | 0.00 | 0.200794E+11 | 0.00 | 1.28 |
September | 0.300148E+10 | 0.520082E+09 | 0.00 | 0.123630E+09 | 16282032.34 | 56191408.13 | 0.213201E+11 | 0.00 | 1.20 |
October | 0.919335E+10 | 0.00 | 0.00 | 84573637.74 | 0.00 | 0.444042E+10 | 0.234173E+11 | 0.00 | 0.74 |
November | 0.148239E+11 | 0.00 | 0.00 | 36769063.58 | 0.00 | 0.441980E+10 | 0.133929E+11 | 0.00 | 0.46 |
December | 0.146224E+11 | 0.00 | 0.00 | 17605357.99 | 0.00 | 0.129674E+11 | 0.735712E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.100908E+12 | 0.862434E+10 | 0.00 | 0.949716E+09 | 84347347.63 | 0.402982E+11 | 0.245460E+12 | 0.00 | 0.90 |
Minimum of Months | 0.968688E+09 | 0.00 | 0.00 | 17605357.99 | 0.00 | 0.00 | 0.735712E+10 | 0.00 | 0.38 |
Maximum of Months | 0.158368E+11 | 0.286411E+10 | 0.00 | 0.147340E+09 | 46726589.53 | 0.129674E+11 | 0.411498E+11 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126440E+10 | 0.00 | 0.00 | 6228.24 | 0.00 | 0.318164E+10 | 14047697.43 | 0.00 | 0.33 |
February | 0.124368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283525E+10 | 0.00 | 0.00 | 0.32 |
March | 0.182722E+10 | 0.00 | 0.00 | 1002743.84 | 0.00 | 0.170794E+10 | 0.517080E+09 | 0.00 | 0.40 |
April | 0.158336E+10 | 0.00 | 0.00 | 1772879.53 | 0.00 | 0.108885E+10 | 0.102247E+10 | 0.00 | 0.44 |
May | 0.109886E+10 | 131124.06 | 0.00 | 6677054.80 | 2333.11 | 67214877.42 | 0.272396E+10 | 0.00 | 0.76 |
June | 0.241555E+09 | 0.125177E+09 | 0.00 | 12813579.63 | 4341392.80 | 0.00 | 0.194201E+10 | 0.00 | 0.92 |
July | 0.231031E+09 | 0.119231E+09 | 0.00 | 12145913.11 | 9664546.06 | 0.00 | 0.148460E+10 | 0.00 | 0.83 |
August | 0.388452E+09 | 0.114739E+09 | 0.00 | 11825341.18 | 13261950.11 | 0.00 | 0.174575E+10 | 0.00 | 0.75 |
September | 0.699871E+09 | 22635363.15 | 0.00 | 7998120.22 | 5511969.03 | 43931263.22 | 0.139243E+10 | 0.00 | 0.64 |
October | 0.175825E+10 | 0.00 | 0.00 | 986085.76 | 0.00 | 0.146732E+10 | 0.429651E+09 | 0.00 | 0.40 |
November | 0.130201E+10 | 0.00 | 0.00 | 238896.11 | 0.00 | 0.253356E+10 | 0.124891E+09 | 0.00 | 0.34 |
December | 0.950910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474004E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.125896E+11 | 0.381913E+09 | 0.00 | 55466842.41 | 32782191.11 | 0.176657E+11 | 0.113969E+11 | 0.00 | 0.54 |
Minimum of Months | 0.231031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.182722E+10 | 0.125177E+09 | 0.00 | 12813579.63 | 13261950.11 | 0.474004E+10 | 0.272396E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110378E+10 | 0.00 | 0.00 | 914971.58 | 0.00 | 0.136564E+10 | 0.486679E+09 | 0.00 | 0.35 |
February | 0.930500E+09 | 0.00 | 0.00 | 1893116.09 | 0.00 | 0.113263E+10 | 0.109610E+10 | 0.00 | 0.41 |
March | 0.874036E+09 | 0.00 | 0.00 | 6314327.25 | 0.00 | 0.709030E+09 | 0.319040E+10 | 0.00 | 0.82 |
April | 0.680935E+09 | 0.00 | 0.00 | 6289257.24 | 0.00 | 0.508962E+09 | 0.359633E+10 | 0.00 | 0.96 |
May | 0.384555E+09 | 120124.44 | 0.00 | 11419376.21 | 1507.65 | 22803546.76 | 0.483047E+10 | 0.00 | 1.53 |
June | 87034230.61 | 99112893.26 | 0.00 | 19404210.88 | 2103651.81 | 0.00 | 0.336545E+10 | 0.00 | 1.94 |
July | 83546792.08 | 0.113371E+09 | 0.00 | 19736062.06 | 2389185.24 | 0.00 | 0.208136E+10 | 0.00 | 1.54 |
August | 0.119935E+09 | 0.104954E+09 | 0.00 | 20980232.79 | 8558441.39 | 0.00 | 0.374798E+10 | 0.00 | 1.79 |
September | 0.238855E+09 | 22259126.60 | 0.00 | 14592280.04 | 3503351.49 | 18320333.16 | 0.295922E+10 | 0.00 | 1.48 |
October | 0.729054E+09 | 0.00 | 0.00 | 5304428.88 | 0.00 | 0.859661E+09 | 0.223743E+10 | 0.00 | 0.73 |
November | 0.100176E+10 | 0.00 | 0.00 | 1651812.64 | 0.00 | 0.113649E+10 | 0.802757E+09 | 0.00 | 0.43 |
December | 0.954755E+09 | 0.00 | 0.00 | 269672.73 | 0.00 | 0.229591E+10 | 0.178161E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.718875E+10 | 0.339817E+09 | 0.00 | 0.108770E+09 | 16556137.58 | 0.804945E+10 | 0.285723E+11 | 0.00 | 1.03 |
Minimum of Months | 83546792.08 | 0.00 | 0.00 | 269672.73 | 0.00 | 0.00 | 0.178161E+09 | 0.00 | 0.35 |
Maximum of Months | 0.110378E+10 | 0.113371E+09 | 0.00 | 20980232.79 | 8558441.39 | 0.229591E+10 | 0.483047E+10 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122573E+10 | 0.00 | 0.00 | 21768809.28 | 0.00 | 0.122127E+10 | 0.879996E+10 | 0.00 | 1.02 |
February | 0.106647E+10 | 0.00 | 0.00 | 19587634.02 | 0.00 | 0.120477E+10 | 0.880635E+10 | 0.00 | 0.98 |
March | 0.120986E+10 | 0.00 | 0.00 | 19879440.84 | 0.00 | 0.101886E+10 | 0.839293E+10 | 0.00 | 1.26 |
April | 0.124969E+10 | 0.00 | 0.00 | 8703139.07 | 0.00 | 0.743174E+09 | 0.519165E+10 | 0.00 | 0.97 |
May | 0.881056E+09 | 209774.65 | 0.00 | 11377165.12 | 2329.53 | 69172886.67 | 0.471801E+10 | 0.00 | 1.12 |
June | 0.322584E+09 | 0.135475E+09 | 0.00 | 14978364.13 | 4370461.03 | 0.00 | 0.203165E+10 | 0.00 | 1.03 |
July | 0.247174E+09 | 0.156091E+09 | 0.00 | 15571541.67 | 5732591.08 | 0.00 | 0.166522E+10 | 0.00 | 0.97 |
August | 0.296894E+09 | 0.186509E+09 | 0.00 | 23614056.85 | 12938721.62 | 0.00 | 0.300593E+10 | 0.00 | 1.18 |
September | 0.423761E+09 | 52487990.22 | 0.00 | 27400357.19 | 4082511.75 | 35755956.98 | 0.422920E+10 | 0.00 | 1.50 |
October | 0.808075E+09 | 0.00 | 0.00 | 31163811.95 | 0.00 | 0.115903E+10 | 0.894314E+10 | 0.00 | 1.53 |
November | 0.987731E+09 | 0.00 | 0.00 | 26288626.75 | 0.00 | 0.110698E+10 | 0.872935E+10 | 0.00 | 1.15 |
December | 0.121904E+10 | 0.00 | 0.00 | 16623716.73 | 0.00 | 0.207575E+10 | 0.667757E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.993807E+10 | 0.530774E+09 | 0.00 | 0.236957E+09 | 27126615.02 | 0.863477E+10 | 0.711910E+11 | 0.00 | 1.14 |
Minimum of Months | 0.247174E+09 | 0.00 | 0.00 | 8703139.07 | 0.00 | 0.00 | 0.166522E+10 | 0.00 | 0.91 |
Maximum of Months | 0.124969E+10 | 0.186509E+09 | 0.00 | 31163811.95 | 12938721.62 | 0.207575E+10 | 0.894314E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110298E+10 | 0.00 | 0.00 | 1937306.09 | 0.00 | 0.120697E+10 | 0.110554E+10 | 0.00 | 0.44 |
February | 0.999295E+09 | 0.00 | 0.00 | 2536708.38 | 0.00 | 0.103431E+10 | 0.146738E+10 | 0.00 | 0.45 |
March | 0.108884E+10 | 0.00 | 0.00 | 6981131.13 | 0.00 | 0.633640E+09 | 0.293718E+10 | 0.00 | 0.90 |
April | 0.882511E+09 | 0.00 | 0.00 | 5588884.86 | 0.00 | 0.388899E+09 | 0.327370E+10 | 0.00 | 0.98 |
May | 0.453907E+09 | 186927.23 | 0.00 | 10927090.33 | 1513.80 | 35489400.48 | 0.409074E+10 | 0.00 | 1.46 |
June | 0.110865E+09 | 0.176990E+09 | 0.00 | 15856094.15 | 322372.53 | 0.00 | 0.186417E+10 | 0.00 | 1.43 |
July | 0.104182E+09 | 0.149986E+09 | 0.00 | 13290625.46 | 3138351.51 | 0.00 | 0.143498E+10 | 0.00 | 1.24 |
August | 0.113075E+09 | 0.172547E+09 | 0.00 | 17399433.94 | 2237531.52 | 0.00 | 0.201280E+10 | 0.00 | 1.29 |
September | 0.294010E+09 | 35203021.18 | 0.00 | 13563249.48 | 1161161.48 | 19887530.92 | 0.212496E+10 | 0.00 | 1.24 |
October | 0.866452E+09 | 0.00 | 0.00 | 7493829.69 | 0.00 | 0.689467E+09 | 0.255410E+10 | 0.00 | 0.89 |
November | 0.100888E+10 | 0.00 | 0.00 | 2907512.27 | 0.00 | 0.958978E+09 | 0.130814E+10 | 0.00 | 0.51 |
December | 0.101272E+10 | 0.00 | 0.00 | 1210129.54 | 0.00 | 0.193893E+10 | 0.633839E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.803772E+10 | 0.534912E+09 | 0.00 | 99691995.32 | 6860930.84 | 0.690657E+10 | 0.248075E+11 | 0.00 | 0.94 |
Minimum of Months | 0.104182E+09 | 0.00 | 0.00 | 1210129.54 | 0.00 | 0.00 | 0.633839E+09 | 0.00 | 0.42 |
Maximum of Months | 0.110298E+10 | 0.176990E+09 | 0.00 | 17399433.94 | 3138351.51 | 0.193893E+10 | 0.409074E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 4082845.76 | 0.00 | 0.00 | 0.565414E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 9004071.27 | 0.00 | 0.00 | 0.531809E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15920447.24 | 0.00 | 0.00 | 0.507570E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18659213.33 | 0.00 | 0.00 | 0.394205E+09 | 0.00 | 0.29 |
May | 0.00 | 208240.56 | 0.00 | 4363770.13 | 0.00 | 0.00 | 0.261460E+09 | 0.00 | 0.29 |
June | 0.00 | 29908325.31 | 0.00 | 5554296.17 | 0.00 | 0.00 | 43912002.47 | 0.00 | 0.30 |
July | 0.00 | 57016631.28 | 0.00 | 5749014.14 | 0.00 | 0.00 | 26514626.70 | 0.00 | 0.28 |
August | 0.00 | 31556413.50 | 0.00 | 12523737.95 | 0.00 | 0.00 | 50114082.89 | 0.00 | 0.30 |
September | 0.00 | 757143.14 | 0.00 | 4387388.12 | 0.00 | 0.00 | 0.163587E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 9633741.31 | 0.00 | 0.00 | 0.426279E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 14395736.01 | 0.00 | 0.00 | 0.497959E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 21176591.51 | 0.00 | 0.00 | 0.594393E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.119447E+09 | 0.00 | 0.125451E+09 | 0.00 | 0.00 | 0.406322E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4082845.76 | 0.00 | 0.00 | 26514626.70 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 57016631.28 | 0.00 | 21176591.51 | 0.00 | 0.00 | 0.594393E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 88513311.09 | 0.00 | 0.00 | 26820982.35 | 0.00 | 0.00 | 0.558215E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 73335618.51 | 0.00 | 0.00 | 0.533429E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.141688E+09 | 0.00 | 0.00 | 0.509267E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.171049E+09 | 0.00 | 0.00 | 0.395711E+10 | 0.00 | 0.29 |
May | 0.00 | 1924432.95 | 0.00 | 38143378.58 | 0.00 | 0.00 | 0.262645E+10 | 0.00 | 0.29 |
June | 0.00 | 0.295195E+09 | 0.00 | 52285078.26 | 0.00 | 0.00 | 0.443233E+09 | 0.00 | 0.30 |
July | 0.00 | 0.566122E+09 | 0.00 | 54632483.39 | 0.00 | 0.00 | 0.268235E+09 | 0.00 | 0.28 |
August | 0.00 | 0.314553E+09 | 0.00 | 0.119586E+09 | 0.00 | 0.00 | 0.504576E+09 | 0.00 | 0.30 |
September | 0.00 | 7362081.82 | 0.00 | 38798325.45 | 0.00 | 0.00 | 0.164592E+10 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 83722106.55 | 0.00 | 0.00 | 0.427561E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.126308E+09 | 0.00 | 0.00 | 0.499621E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.185333E+09 | 0.00 | 0.00 | 0.597001E+10 | 0.00 | 0.28 |
Annual Sum or Average | 88513311.09 | 0.118516E+10 | 0.00 | 0.111170E+10 | 0.00 | 0.00 | 0.406965E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 26820982.35 | 0.00 | 0.00 | 0.268235E+09 | 0.00 | 0.28 |
Maximum of Months | 88513311.09 | 0.566122E+09 | 0.00 | 0.185333E+09 | 0.00 | 0.00 | 0.597001E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187522E+09 | 0.00 | 0.00 | 1503784.10 | 0.00 | 0.00 | 0.377591E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6080291.20 | 0.00 | 0.00 | 0.534789E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13106649.39 | 0.00 | 0.00 | 0.510554E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16331106.09 | 0.00 | 0.00 | 0.396582E+09 | 0.00 | 0.29 |
May | 5877438.07 | 204109.60 | 0.00 | 3509996.26 | 0.00 | 0.00 | 0.257323E+09 | 0.00 | 0.29 |
June | 0.00 | 29593596.74 | 0.00 | 5241119.63 | 0.00 | 0.00 | 44311841.64 | 0.00 | 0.30 |
July | 0.00 | 56648425.97 | 0.00 | 5466618.30 | 0.00 | 0.00 | 26801918.23 | 0.00 | 0.28 |
August | 0.00 | 31531489.35 | 0.00 | 11920135.42 | 0.00 | 0.00 | 50235030.90 | 0.00 | 0.30 |
September | 2118675.48 | 728974.16 | 0.00 | 3695825.82 | 0.00 | 0.00 | 0.162734E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 7313345.14 | 0.00 | 0.00 | 0.429013E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11351308.39 | 0.00 | 0.00 | 0.501115E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16977867.62 | 0.00 | 0.00 | 0.598574E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.195519E+09 | 0.118707E+09 | 0.00 | 0.102498E+09 | 0.00 | 0.00 | 0.388962E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1503784.10 | 0.00 | 0.00 | 26801918.23 | 0.00 | 0.28 |
Maximum of Months | 0.187522E+09 | 56648425.97 | 0.00 | 16977867.62 | 0.00 | 0.00 | 0.598574E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.645531E+09 | 0.00 | 0.00 | 0.540783E+12 | 0.00 | 11.60 |
February | 0.00 | 0.00 | 0.00 | 0.122622E+10 | 0.00 | 0.00 | 0.774186E+12 | 0.00 | 18.02 |
March | 0.00 | 0.00 | 0.00 | 0.190906E+10 | 0.00 | 0.00 | 0.109165E+13 | 0.00 | 31.65 |
April | 0.00 | 0.00 | 0.00 | 0.214830E+10 | 0.00 | 0.00 | 0.124755E+13 | 0.00 | 40.25 |
May | 0.00 | 0.00 | 0.00 | 0.541010E+09 | 0.00 | 0.00 | 0.511126E+12 | 0.00 | 24.77 |
June | 0.00 | 0.270422E+10 | 0.00 | 0.112310E+10 | 0.00 | 0.00 | 0.418727E+12 | 0.00 | 37.90 |
July | 0.00 | 0.109174E+11 | 0.00 | 0.173460E+10 | 0.00 | 0.00 | 0.426633E+12 | 0.00 | 42.31 |
August | 0.00 | 0.902625E+10 | 0.00 | 0.240442E+10 | 0.00 | 0.00 | 0.435016E+12 | 0.00 | 45.24 |
September | 0.00 | 0.00 | 0.00 | 0.587759E+09 | 0.00 | 0.00 | 0.442246E+12 | 0.00 | 29.00 |
October | 0.00 | 0.00 | 0.00 | 0.128592E+10 | 0.00 | 0.00 | 0.835427E+12 | 0.00 | 26.67 |
November | 0.00 | 0.00 | 0.00 | 0.190152E+10 | 0.00 | 0.00 | 0.106342E+13 | 0.00 | 28.75 |
December | 0.00 | 0.00 | 0.00 | 0.289315E+10 | 0.00 | 0.00 | 0.133922E+13 | 0.00 | 32.06 |
Annual Sum or Average | 0.00 | 0.226479E+11 | 0.00 | 0.184006E+11 | 0.00 | 0.00 | 0.912598E+13 | 0.00 | 30.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.541010E+09 | 0.00 | 0.00 | 0.418727E+12 | 0.00 | 11.60 |
Maximum of Months | 0.00 | 0.109174E+11 | 0.00 | 0.289315E+10 | 0.00 | 0.00 | 0.133922E+13 | 0.00 | 45.24 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:33
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.433498E+12 | 0.696707E+10 | 0.00 | 0.237855E+13 | 0.279371E+12 |
February | 0.553097E+12 | 0.109943E+11 | 0.00 | 0.241274E+13 | 0.318796E+12 |
March | 0.688634E+12 | 0.119483E+11 | 0.00 | 0.293349E+13 | 0.504192E+12 |
April | 0.743741E+12 | 0.125840E+11 | 0.00 | 0.312165E+13 | 0.567519E+12 |
May | 0.856915E+12 | 0.640105E+10 | 0.00 | 0.234907E+13 | 0.652929E+12 |
June | 0.904323E+12 | 0.291976E+10 | 0.00 | 0.159297E+13 | 0.218819E+13 |
July | 0.853579E+12 | 0.235814E+10 | 0.00 | 0.142513E+13 | 0.266689E+13 |
August | 0.835576E+12 | 0.232508E+10 | 0.00 | 0.141548E+13 | 0.302310E+13 |
September | 0.626937E+12 | 0.412121E+10 | 0.00 | 0.182117E+13 | 0.135694E+13 |
October | 0.545233E+12 | 0.890044E+10 | 0.00 | 0.274968E+13 | 0.574353E+12 |
November | 0.461596E+12 | 0.793096E+10 | 0.00 | 0.292903E+13 | 0.471935E+12 |
December | 0.358887E+12 | 0.145984E+11 | 0.00 | 0.309787E+13 | 0.515085E+12 |
Annual Sum or Average | 0.786202E+13 | 0.920487E+11 | 0.00 | 0.282268E+14 | 0.131193E+14 |
Minimum of Months | 0.358887E+12 | 0.232508E+10 | 0.00 | 0.141548E+13 | 0.279371E+12 |
Maximum of Months | 0.904323E+12 | 0.145984E+11 | 0.00 | 0.312165E+13 | 0.302310E+13 |