Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:21:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26509.71 | 572.31 | 572.31 |
Net Site Energy | 26509.71 | 572.31 | 572.31 |
Total Source Energy | 81640.16 | 1762.51 | 1762.51 |
Net Source Energy | 81640.16 | 1762.51 | 1762.51 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 951.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2470.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2311.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 289.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1893.49 |
Humidification | 1043.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.36 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 438.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25397.81 | 1111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4562.02 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 951.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2470.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2311.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 289.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1893.49 |
Humidification | General | 1043.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.36 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 438.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 951.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2470.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2311.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 289.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1893.49 |
Humidification | Unassigned | 1043.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.36 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 438.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 115.03 | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 548.31 | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 115.03 | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 548.31 | 24.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 25397.807 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25397.807 | 100.00 |
Total On-Site and Utility Electric Sources | 25397.807 | 100.00 |
Total Electricity End Uses | 25397.807 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4562.02 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4562.02 | 100.00 |
Total Water End Uses | 4562.02 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 15.50 |
Time Setpoint Not Met During Occupied Cooling | 503.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:20 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1281357.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 404381.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 270536.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37784.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 72883.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34477.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2044516.27 | 1281357.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1281357.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 404381.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 270536.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 37784.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 72883.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 34477.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1205.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3013.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7824.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1128.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 915.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 929.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3306.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1388.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 80434.86 | 1205.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1736.49 | 26.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1736.49 | 26.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.11 | 0.414630 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.46 | 0.348208 | 0.296000 | 1.62 | 0.928554 | 0.500000 | 0.001094 | 0.000140 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 51.13 | 0.372000 | 0.316000 | 16.16 | 0.992000 | 0.500000 | 0.001024 | 0.003169 | 16.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.93 | 0.385856 | 0.328000 | 1.62 | 1.00 | 0.500000 | 0.000987 | 0.000623 | 2.15 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.832604 | 0.286836 | 0.244000 | 0.203155 | 0.764896 | 0.500000 | 0.001328 | 0.000069 | 0.237946 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.27 | 0.120730 | 0.103000 | 0.131303 | 0.321947 | 0.500000 | 0.003156 | 0.000050 | 0.173147 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.77 | 0.134909 | 0.115000 | 0.203581 | 0.359758 | 0.500000 | 0.002824 | 0.000090 | 0.309089 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.53 | 0.100337 | 0.085000 | 0.130380 | 0.300000 | 0.500000 | 0.003797 | 0.000032 | 0.130380 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.59 | 0.314773 | 0.268000 | 2.03 | 0.839394 | 0.500000 | 0.001210 | 0.001550 | 5.36 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.34 | 0.307694 | 0.500000 | 0.003302 | 0.001030 | 3.56 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.27 | 0.130724 | 0.111000 | 2.03 | 0.348597 | 0.500000 | 0.002915 | 0.001536 | 5.31 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.01 | 0.109830 | 0.093000 | 1.30 | 0.300000 | 0.500000 | 0.003469 | 0.000948 | 3.28 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.853916 | 0.279677 | 0.238000 | 0.203232 | 0.745805 | 0.500000 | 0.001362 | 0.000200 | 0.692859 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.32 | 0.116229 | 0.099000 | 0.131091 | 0.309944 | 0.500000 | 0.003278 | 0.000132 | 0.457280 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.92 | 0.124188 | 0.106000 | 0.203849 | 0.331167 | 0.500000 | 0.003068 | 0.000199 | 0.687735 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.47 | 0.104999 | 0.089000 | 0.130454 | 0.300000 | 0.500000 | 0.003629 | 0.000125 | 0.433721 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16047.69 | 0.000140 | 323.51 | |
CORE_MID VAV BOX REHEAT COIL | 362266.50 | 0.003169 | 8349.49 | |
CORE_TOP VAV BOX REHEAT COIL | 71160.21 | 0.000623 | 1879.60 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7892.99 | 0.000069 | 208.52 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5739.65 | 0.000050 | 151.58 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10238.83 | 0.000090 | 270.32 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3636.93 | 0.000032 | 89.59 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 177162.05 | 0.001550 | 4673.42 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 117682.54 | 0.001030 | 3104.28 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 175606.35 | 0.001536 | 4632.43 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 108313.60 | 0.000948 | 2857.39 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22897.36 | 0.000200 | 603.86 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15111.30 | 0.000132 | 398.51 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22728.36 | 0.000199 | 599.41 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14334.07 | 0.000125 | 378.03 | |
VAV_BOT WITH REHEAT HEATING COIL | 44204.58 | 0.000387 | 737.81 | |
VAV_MID WITH REHEAT HEATING COIL | 375848.69 | 0.003288 | 6313.17 | |
VAV_TOP WITH REHEAT HEATING COIL | 36741.74 | 0.000321 | 623.41 | |
CAV_BAS HEATING COIL | 249715.87 | 0.000875 | 2622.59 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.504237 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.84 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.491439 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.80 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.44 | 2.29 | 10.87 | 2.29 | 9.02 | 9.02 | 0.300000 | 0.253451 | 9.02 |
VAV_MID WITH REHEAT | 52.17 | 22.83 | 104.34 | 28.28 | 83.07 | 83.07 | 0.300000 | 0.340451 | 83.07 |
VAV_TOP WITH REHEAT | 5.25 | 2.29 | 10.50 | 4.42 | 9.31 | 9.31 | 0.300000 | 0.474383 | 9.31 |
CAV_BAS | 0.000000 | 0.000000 | 5.11 | 1.20 | 5.11 | 5.11 | 1.00 | 0.234957 | 5.11 |
AIRLOOP DATACENTER BASEMENT | 24.80 | 24.80 | 24.80 | 24.80 | 24.80 | 24.80 | 1.00 | 0.999996 | 24.80 |
AIRLOOP DATACENTER BOT | 0.504237 | 0.504237 | 0.504237 | 0.504237 | 0.504237 | 0.504237 | 1.00 | 1.00 | 0.504237 |
AIRLOOP DATACENTER MID | 4.84 | 4.84 | 4.84 | 4.84 | 4.84 | 4.84 | 1.00 | 1.00 | 4.84 |
AIRLOOP DATACENTER TOP | 0.491439 | 0.491439 | 0.491439 | 0.491439 | 0.491439 | 0.491439 | 1.00 | 1.00 | 0.491439 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.02 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 83.07 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.31 | |
CAV_BAS_OA_CONTROLLER | 5.11 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.80 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.504237 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.84 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.491439 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.22 | 6.67 | 11.02 | 0.008845 | 0.008500 | 164488.21 | 0.004704 | 9.02 |
VAV_MID WITH REHEAT COOLING COIL | 25.33 | 6.67 | 11.02 | 0.008869 | 0.008500 | 1533301.03 | 0.043852 | 83.07 |
VAV_TOP WITH REHEAT COOLING COIL | 25.18 | 6.67 | 11.02 | 0.008837 | 0.008500 | 169230.09 | 0.004840 | 9.31 |
CAV_BAS COOLING COIL | 25.29 | 6.67 | 11.01 | 0.008989 | 0.008500 | 95943.47 | 0.002744 | 5.11 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.02 |
VAV_MID WITH REHEAT FAN | 83.07 |
VAV_TOP WITH REHEAT FAN | 9.31 |
CAV_BAS FAN | 5.11 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004704 | 0.000101 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000387 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.043852 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003288 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004840 | 0.000098 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000321 | |
CAV_BAS_COOLC_CONTROLLER | 0.002744 | 0.000174 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.80 | 490344.31 | 351281.93 | 0.012009 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.504237 | 9744.96 | 7061.29 | 0.000239 |
AIRLOOP DATACENTER MID COOLING COIL | 4.84 | 93616.61 | 67819.88 | 0.002293 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.491439 | 9503.89 | 6884.14 | 0.000233 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.80 | 24.80 | 24.80 | 24.80 | 490344.31 | 490344.31 | 17840.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.504237 | 0.504237 | 0.504237 | 0.504237 | 9744.96 | 9744.96 | 824.14 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.84 | 4.84 | 4.84 | 4.84 | 93616.61 | 93616.61 | 8241.36 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.491439 | 0.491439 | 0.491439 | 0.491439 | 9503.89 | 9503.89 | 824.14 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.80 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.504237 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.84 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.491439 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.80 | 490344.31 | 0.012009 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.504237 | 9744.96 | 0.000239 |
AIRLOOP DATACENTER MID HEATING COIL | 4.84 | 93616.61 | 0.002293 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.491439 | 9503.89 | 0.000233 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17840.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 824.14 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8241.36 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 824.14 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000165 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.056140 | 9075.27 | |
HEATSYS1 PUMP | 0.014764 | 4402.24 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.056140 | 6.74 |
HEATSYS1 | 0.014764 | 1.77 |
COOLSYS1_SUPPLY | 0.056140 | 6.74 |
SINGLE WATER PLANT LOOP | 0.014773 | 1.77 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.056140 | 0.056140 | 235649.79 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1687613.43 | 1687613.43 | 0.014764 |
CENTRAL BOILER | 608503.17 | 596268.42 | 0.014773 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.028070 | 3141.56 |
COOLSYS1 CHILLER2 PUMP | 0.028070 | 3141.56 |
PLANT CIRC PUMP | 0.014773 | 3730.44 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.056140 | 0.028388 | 992588.32 | 992587.72 | 0.051017 |
COOLSYS1 CHILLER2 | 0.056140 | 0.028388 | 992588.32 | 992587.72 | 0.051017 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014773 | 146680.64 | 74254.09 | 73340.32 | 7004.20 | 44552.45 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.102034 | 12.24 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.102034 | 25011.29 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 38.86 | 1189621.49 | 7.77 | 148702.69 |
TOWERWATERSYS COOLTOWER 2 | 38.86 | 1189621.49 | 7.77 | 148702.69 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.051472 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.075 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7632 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8055 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6228 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.34463022E-15 | 0.36894385E-16 | -0.14288780E-09 | 0.12757077E-17 |
51 | 8 | 0.20913840E-07 | 0.14359092E-12 | 0.36762620E-03 | -0.23779757E-09 |
52 | 7 | -0.11937955E-01 | 0.75343451E-08 | -0.22648608E-01 | 0.13573889E-03 |
53 | 6 | 0.39710065 | 0.26364580E-05 | 0.46505929 | -0.46505182E-02 |
54 | 5 | -5.1100523 | 0.98937734E-04 | -4.3872286 | 0.62185548E-01 |
55 | 4 | 32.646709 | 0.81302423E-03 | 21.229086 | -0.41739428 |
56 | 3 | -110.46842 | 0.17791168E-02 | -55.206350 | 1.5042464 |
57 | 2 | 196.38009 | 0.10043743E-02 | 77.491871 | -2.8887901 |
58 | 1 | -170.88709 | 0.10757908E-03 | -55.143519 | 2.7407251 |
59 | 0 | 57.057407 | 0.61468164E-06 | 15.577169 | |
60 | 9 | -0.22955380E-15 | 0.37743381E-16 | -0.14509256E-09 | 0.32676096E-18 |
61 | 8 | 0.21224167E-07 | 0.13772622E-12 | 0.37092755E-03 | -0.24132609E-09 |
62 | 7 | -0.12036605E-01 | 0.72012381E-08 | -0.22790691E-01 | 0.13686058E-03 |
63 | 6 | 0.39978134 | 0.25163753E-05 | 0.46734577 | -0.46821170E-02 |
64 | 5 | -5.1362151 | 0.94318005E-04 | -4.4048053 | 0.62509952E-01 |
65 | 4 | 32.762449 | 0.77422319E-03 | 21.297824 | -0.41893096 |
66 | 3 | -110.71472 | 0.16925811E-02 | -55.342260 | 1.5078047 |
67 | 2 | 196.62425 | 0.95470525E-03 | 77.616458 | -2.8926672 |
68 | 1 | -170.97729 | 0.10217823E-03 | -55.179630 | 2.7423060 |
69 | 0 | 57.057407 | 0.58332056E-06 | 15.571109 | |
70 | 9 | 0.11276195E-14 | 0.47405760E-16 | -0.13382366E-09 | -0.64614724E-17 |
71 | 8 | 0.19634610E-07 | 0.16705312E-12 | 0.35383761E-03 | -0.22325229E-09 |
72 | 7 | -0.11525316E-01 | 0.88979655E-08 | -0.22054087E-01 | 0.13104703E-03 |
73 | 6 | 0.38588679 | 0.31323747E-05 | 0.45547913 | -0.45183345E-02 |
74 | 5 | -5.0005974 | 0.11815564E-03 | -4.3135163 | 0.60828376E-01 |
75 | 4 | 32.162433 | 0.97545471E-03 | 20.940665 | -0.41096462 |
76 | 3 | -109.43770 | 0.21433374E-02 | -54.636007 | 1.4893559 |
77 | 2 | 195.35810 | 0.12144036E-02 | 76.969321 | -2.8725616 |
78 | 1 | -170.50942 | 0.13051365E-03 | -54.992579 | 2.7341060 |
79 | 0 | 57.057407 | 0.74839837E-06 | 15.602923 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1581E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1604E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0740E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0760E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4338E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4353E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4917E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4924E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2102E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3666E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1190E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2595E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4714E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5818E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5122E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5645E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1656 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4328E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1907 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1105 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1057 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4306E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5025E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5661E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2131E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3810E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1221E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2747E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4737E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5906E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5127E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5660E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1578E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1602E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0737E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0758E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4336E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4352E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4916E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4923E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8123E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2136E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5904E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0559E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0969E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2306E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2602E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2962E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4527E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2086E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0695E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9501E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1274E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5728E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6880E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7537E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6597E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7745E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3865E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4705E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0538E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0850E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2603E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2968E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7919E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7941E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3600E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3618E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0538E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0551E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4917E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8407E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9685E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4004E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5030E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0861E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1585E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5127E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5660E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6691E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4699E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5878E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8765E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1795E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2296E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5025E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5656E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8394E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9661E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3990E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4998E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0842E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1529E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5122E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5645E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7918E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7939E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3599E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3617E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0537E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0549E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4916E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4923E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4935E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6096E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1706E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2553E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9426E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9730E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2604E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2969E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1654E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0876E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6984E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7932E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9224E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4878E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6880E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7537E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6324E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9942E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3565E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7699E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9846E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1141E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2601E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2961E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1623 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1238 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1806 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1426 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1183 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4902E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5140E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7277E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6832E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6077E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2581E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3012E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2604E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7796E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6552E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7590E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7396E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.8170E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5184E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0086E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0755E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1989E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5140E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7273E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3573E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.4395E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8368E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0827E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0308E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6676E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6552E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7590E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1623 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1240 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1806 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1428 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1185 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5053E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5258E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7338E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6874E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6146E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2629E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3078E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2712E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7876E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6670E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7650E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7399E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.8215E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5191E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0121E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0821E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2031E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5258E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7333E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3611E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.4460E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8411E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0889E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0413E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6752E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6670E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7650E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69959.15132 | 69959.15132 | 5.10799 | 5.10799 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 74812.31154 | 74812.31154 | 5.46238 | 5.46238 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 700486.03664 | 700486.03664 | 51.13022 | 51.13022 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 201903.72968 | 201903.72968 | 8.61196 | 10.77825 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67540.44936 | 67540.44936 | 4.92942 | 4.92942 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 49861.21837 | 49861.21837 | 2.14595 | 2.14595 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11296.19481 | 11296.19481 | 0.83260 | 0.83260 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5534.73902 | 5534.73902 | 0.23795 | 0.23795 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17295.60073 | 17295.60073 | 1.27479 | 1.27479 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4023.28003 | 4023.28003 | 0.17315 | 0.17315 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24017.99423 | 24017.99423 | 1.77027 | 1.77027 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.82080E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7174.02643 | 7174.02643 | 0.30909 | 0.30909 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20810.86180 | 20810.86180 | 1.53388 | 1.53388 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2346.11647 | 2346.11647 | 0.10041 | 0.10041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 102936.16332 | 102936.16332 | 7.58708 | 7.58708 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 124023.18076 | 124023.18076 | 5.35779 | 5.35779 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 180967.59270 | 180967.59270 | 13.33835 | 13.33835 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 82381.19796 | 82381.19796 | 3.55927 | 3.55927 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 247870.41363 | 247870.41363 | 18.26951 | 18.26951 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 122935.78115 | 122935.78115 | 5.31063 | 5.31063 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 190121.18272 | 190121.18272 | 14.01303 | 14.01303 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 75832.27457 | 75832.27457 | 3.27528 | 3.27528 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11585.34840 | 11585.34840 | 0.85392 | 0.85392 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 16025.02230 | 16025.02230 | 0.69286 | 0.69286 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17965.38946 | 17965.38946 | 1.32415 | 1.32415 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10575.64507 | 10575.64507 | 0.45728 | 0.45728 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26091.56820 | 26091.56820 | 1.92310 | 1.92310 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15906.87550 | 15906.87550 | 0.68774 | 0.68774 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19886.79722 | 19886.79722 | 1.46577 | 1.46577 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10032.25166 | 10032.25166 | 0.43372 | 0.43372 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8673.55330 | 8673.55330 | 0.50424 | 0.50424 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83289.58467 | 83289.58467 | 4.84207 | 4.84207 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8453.37172 | 8453.37172 | 0.49144 | 0.49144 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370951.57498 | 426594.31123 | 21.56501 | 24.79977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 03:00:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 133521.11 | 9.01668 | 9.01668 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 38493.86 | 1.89841 | 1.89841 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1230287.89 | 83.06976 | 83.06976 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 411113.23 | 28.28122 | 28.28122 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 137449.63 | 9.31221 | 9.31221 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 41145.79 | 4.41755 | 4.41755 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
7 | CAV_BAS | Cooling | Sensible | 67575.99 | 5.10799 | 5.10799 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63272.12 | 1.20016 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 420581.78 | 24.79985 | 24.79985 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17840.03 | 0.33839 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8513.43 | 0.50424 | 0.50424 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81741.66 | 4.84207 | 4.84207 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8241.36 | 0.15632 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8301.50 | 0.49144 | 0.49144 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.10799 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.41463 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.46238 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34821 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29600 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61687 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92855 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09417E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40392E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61687 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16047.68860 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40392E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 323.50881 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 51.13022 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37200 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.15715 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99200 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02419E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.16927E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.15715 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 362266.50167 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.16927E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8349.49311 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.92942 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38586 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61685 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.87416E-004 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.22541E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.14595 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 71160.20528 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.22541E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1879.60414 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83260 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28684 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24400 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20316 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76490 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32829E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.90513E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23795 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7892.99033 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.90513E-005 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 208.51544 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27479 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12073 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13130 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32195 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15580E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.02130E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17315 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5739.64945 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.02130E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 151.58200 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77027 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13491 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20358 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35976 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82412E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.95738E-005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30909 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10238.83379 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.95738E-005 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.31695 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53388 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10034 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13038 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79719E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18175E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13038 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3636.93013 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18175E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.59219 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.58708 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31477 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03334 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83939 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21040E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54989E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.35779 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 177162.04630 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54989E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4673.41915 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.33835 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30769 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30198E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02954E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.55927 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 117682.53507 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02954E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3104.28054 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.26951 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13072 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02792 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34860 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91454E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53628E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.31063 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 175606.35487 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53628E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4632.42735 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.01303 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10983 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30321 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46900E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.47575E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.27528 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108313.60072 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.47575E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2857.39191 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85392 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27968 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20323 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74581 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36229E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.00316E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69286 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22897.36286 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00316E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 603.86206 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32415 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11623 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13109 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30994 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27801E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32200E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45728 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15111.29587 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32200E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 398.51461 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92310 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12419 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20385 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33117 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06793E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98838E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68774 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22728.36305 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98838E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 599.40914 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46577 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10500 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.90000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13045 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.62859E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25401E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43372 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14334.06607 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25401E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 378.03353 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50424 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.84207 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49144 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.79977 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.43696 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28528 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.87392 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28528 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.01668 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.01668 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.25345 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.16909 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.82877 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.33819 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.28122 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 83.06976 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 83.06976 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34045 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.24818 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28547 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.49636 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.41755 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.31221 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.31221 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47438 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.10799 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.10799 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.10799 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.23496 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.79977 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.79977 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.79977 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.79977 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.79985 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.79985 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50424 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50424 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50424 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50424 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50424 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50424 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.84207 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.84207 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.84207 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.84207 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.84207 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.84207 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49144 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49144 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49144 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49144 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49144 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49144 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.01668 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 83.06976 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.31221 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.10799 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.79985 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50424 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.84207 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49144 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.01668 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.21512 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01741 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84463E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 164488.20690 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.70434E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.01668 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 44204.57716 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.86721E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 737.80578 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.01668 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.70434E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.01224E-004 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.86721E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 83.06976 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.33125 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01749 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.86932E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1533301.02796 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.38522E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 83.06976 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 375848.69363 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28809E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6313.16932 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 83.06976 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.38522E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.08590E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.28809E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.31221 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.17670 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01739 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.83697E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 169230.08975 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.83996E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.31221 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 36741.73542 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.21433E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 623.40659 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.31221 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.83996E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.83873E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.21433E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.10799 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.29019 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00638 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.98880E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 95943.46725 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.74397E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.10799 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 249715.86621 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.58834 |
350 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.10799 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.74397E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.73541E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.79985 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.79985 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 490344.30579 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 351281.92830 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20085E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.79985 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.79985 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.79985 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.79985 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 490344.30579 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 490344.30579 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17840.03233 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.79985 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.79985 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 490344.30579 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20085E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17840.03233 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.64754E-004 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50424 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50424 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9744.95532 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7061.29467 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38653E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50424 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50424 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50424 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50424 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9744.95532 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9744.95532 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50424 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50424 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9744.95532 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38653E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.84207 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.84207 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93616.61326 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67819.88010 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29266E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.84207 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.84207 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.84207 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.84207 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93616.61326 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93616.61326 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8241.35587 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.84207 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.84207 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93616.61326 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29266E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8241.35587 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49144 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49144 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9503.89035 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6884.13555 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32750E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49144 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49144 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49144 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49144 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9503.89035 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9503.89035 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49144 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49144 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9503.89035 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32750E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.61405E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9075.27339 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.61405E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.73686 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.61405E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.61405E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 235649.79494 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.47640E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.77168 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.47640E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4402.23957 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1687613.43028 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1687613.43000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47640E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.61405E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.73686 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.80702E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3141.55891 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.80702E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3141.55891 |
456 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.61405E-002 |
457 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.83879E-002 |
458 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 992588.31966 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 992587.72000 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.10171E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.61405E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.83879E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 992588.31966 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 992587.72000 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.10171E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.47726E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.77271 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.47726E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3730.43927 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.47726E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 146680.64435 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74254.09110 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73340.32218 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44552.45466 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 608503.16860 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 596268.42000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47726E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10203 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.24410 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10203 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 25011.28637 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 38.85715 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1189621.49004 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.77143 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 148702.68625 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 38.85715 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1189621.49004 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.77143 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 148702.68625 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.14725E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.14725E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15216.49 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 343248.76 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 67440.53 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7480.63 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5439.47 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9702.77 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3444.82 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 167860.77 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 111503.30 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 166387.07 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 102627.98 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21694.17 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14317.18 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21534.08 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13580.90 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 35004.55 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 301445.32 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 30060.73 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.70 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 207059.05 | 150996.28 | 56062.77 | 0.73 | 34746.73 | 352.42 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1918031.36 | 1395192.54 | 522838.82 | 0.73 | 319636.84 | 3241.93 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 213465.34 | 155796.90 | 57668.44 | 0.73 | 35905.74 | 364.18 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 119104.57 | 86271.32 | 32833.25 | 0.72 | 19778.00 | 200.60 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 8.3976537693E-004 | 1.4125647447E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.9581449569E-003 | 6.1368949569E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.2785648518E-003 | 7.1472769967E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.4672863029E-002 | 1.1939220306E-002 | Pass | Pass | 1.9622226632 | 17.2886949254 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.3215234839E-002 | 1.3693063226E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.4589915631E-002 | 1.4881791285E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.4511005192E-002 | 1.5545920411E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.3711987988E-002 | 1.4222945687E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.5993563034E-002 | 1.5291570361E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.7343056924E-002 | 1.6610623645E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.7944044082E-002 | 1.8077061942E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.6894838341E-002 | 1.6427400625E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2534727705 | 0.2313932387 | Pass | Pass | 19.3193891080 | 44.4252445421 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2621454944 | 0.2406043569 | Pass | Pass | 19.5861013153 | 45.0216681540 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2438203149 | 0.2249487567 | Pass | Pass | 19.0703755226 | 43.8388219753 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1242211188 | 0.1403617161 | Pass | Pass | 21.7408781635 | 52.5866087474 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5201578953E-003 | 2.4761906072E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.1165994303E-003 | 3.1475304117E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7547617023E-002 | 4.5596662720E-002 | Pass | Pass | 0.4108962438 | 0.4751546896 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.9466877508E-006 | 5.8622992137E-006 | Pass | Pass | 1.6463737000E-003 | 1.3176667925E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.9404672623E-003 | 3.6719513364E-003 | Pass | Pass | 1.3553158773E-003 | 9.8238945799E-004 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.6573705352E-003 | 3.9837661609E-003 | Pass | Pass | 1.5986496131E-003 | 1.3338851564E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0809980080E-006 | 2.8356243219E-006 | Pass | Pass | 2.8286877362E-005 | 1.0859343910E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5747.72 | 91.24 | 0.00 | 30554.96 | 6907.01 | 43300.94 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.22 | 0.0000 | Y | 10.96 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.95 | 0.0000 | Y | 6.99 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.70 | 0.0000 | Y | 10.75 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.89 | 0.0000 | Y | 6.98 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.15 | 0.0000 | Y | 109.32 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.91 | 0.0000 | Y | 69.83 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.67 | 0.0000 | Y | 107.44 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.85 | 0.0000 | Y | 69.68 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.15 | 0.0000 | Y | 10.93 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.91 | 0.0000 | Y | 6.98 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.67 | 0.0000 | Y | 10.74 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.84 | 0.0000 | Y | 6.97 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 777.66 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.59 | 42.59 | 106.11 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.55 | 63.07 | 11.71 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.55 | 47.80 | 238.62 | |
Exterior Lighting Total | 40855.88 | 356.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1956916.69 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1687613.43 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 992587.72 | 5.17 | 989226.48 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 992587.72 | 5.17 | 989226.48 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 611291.59 | |||||
CENTRAL BOILER | Boiler:HotWater | 596268.42 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1189621.49 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1189621.49 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 164488.21 | 207059.05 | 150996.28 | 56062.77 | 0.73 | - | 34746.73 | 352.42 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1533301.03 | 1918031.36 | 1395192.54 | 522838.82 | 0.73 | - | 319636.84 | 3241.93 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 169230.09 | 213465.34 | 155796.90 | 57668.44 | 0.73 | - | 35905.74 | 364.18 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 95943.47 | 119104.57 | 86271.32 | 32833.25 | 0.72 | - | 19778.00 | 200.60 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 490344.31 | 351281.93 | 139062.38 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9744.96 | 7061.29 | 2683.66 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93616.61 | 67819.88 | 25796.73 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9503.89 | 6884.14 | 2619.75 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16047.69 | 15216.49 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 362266.50 | 343248.76 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 71160.21 | 67440.53 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7892.99 | 7480.63 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5739.65 | 5439.47 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10238.83 | 9702.77 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3636.93 | 3444.82 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 177162.05 | 167860.77 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 117682.54 | 111503.30 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 175606.35 | 166387.07 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 108313.60 | 102627.98 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22897.36 | 21694.17 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15111.30 | 14317.18 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22728.36 | 21534.08 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14334.07 | 13580.90 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 44204.58 | 35004.55 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 375848.69 | 301445.32 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 36741.74 | 30060.73 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.70 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 490344.31 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9744.96 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93616.61 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9503.89 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17840.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8241.36 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.02 | 19484.57 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 83.07 | 179509.32 | 2160.95 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.31 | 20123.19 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.11 | 11109.30 | 2174.89 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.80 | 40901.08 | 1649.25 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 564.80 | 1120.11 | 1.00 | 1.60 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.84 | 5423.64 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 550.46 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.056140 | 9075.27 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014764 | 4402.24 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028070 | 3141.56 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028070 | 3141.56 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014773 | 3730.44 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.102034 | 25011.29 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69959.15 | 69959.15 | 25.17 | 5.108 | 5.108 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00900 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 74812.31 | 74812.31 | 29.97 | 5.462 | 5.462 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 700486.04 | 700486.04 | 280.63 | 51.130 | 51.130 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 67540.45 | 67540.45 | 27.06 | 4.929 | 4.929 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 21.70 | 0.00881 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11296.19 | 11296.19 | 36.04 | 0.833 | 0.833 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00884 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17295.60 | 17295.60 | 85.63 | 1.275 | 1.275 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00864 | 23.02 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24017.99 | 24017.99 | 76.63 | 1.770 | 1.770 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00866 | 28.97 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20810.86 | 20810.86 | 103.04 | 1.534 | 1.534 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 27.94 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 102936.16 | 102936.16 | 328.44 | 7.587 | 7.587 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 180967.59 | 180967.59 | 895.99 | 13.338 | 13.338 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 23.68 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 247870.41 | 247870.41 | 790.86 | 18.270 | 18.270 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00866 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 190121.18 | 190121.18 | 941.31 | 14.013 | 14.013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11585.35 | 11585.35 | 36.97 | 0.854 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17965.39 | 17965.39 | 88.95 | 1.324 | 1.324 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 23.68 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26091.57 | 26091.57 | 83.25 | 1.923 | 1.923 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 29.14 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19886.80 | 19886.80 | 98.46 | 1.466 | 1.466 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 27.77 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8673.55 | 8673.55 | 239.58 | 0.504 | 0.504 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 25.60 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83289.58 | 83289.58 | 2300.64 | 4.842 | 4.842 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 25.60 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8453.37 | 8453.37 | 233.50 | 0.491 | 0.491 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370951.57 | 426594.31 | 544.35 | 21.565 | 24.800 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.49 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 19.60 | 22.18 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 201903.73 | 201903.73 | 80.89 | 8.612 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 49861.22 | 49861.22 | 19.98 | 2.146 | 2.146 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5534.74 | 5534.74 | 17.66 | 0.238 | 0.238 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00730 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4023.28 | 4023.28 | 19.92 | 0.173 | 0.173 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7174.03 | 7174.03 | 22.89 | 0.309 | 0.309 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2346.12 | 2346.12 | 11.62 | 0.100 | 0.100 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00673 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 124023.18 | 124023.18 | 395.72 | 5.358 | 5.358 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 82381.20 | 82381.20 | 407.88 | 3.559 | 3.559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 122935.78 | 122935.78 | 392.24 | 5.311 | 5.311 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 75832.27 | 75832.27 | 375.45 | 3.275 | 3.275 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16025.02 | 16025.02 | 51.13 | 0.693 | 0.693 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10575.65 | 10575.65 | 52.36 | 0.457 | 0.457 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15906.88 | 15906.88 | 50.75 | 0.688 | 0.688 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10032.25 | 10032.25 | 49.67 | 0.434 | 0.434 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.72 | 0.00850 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.44 | 0.00574 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.79 | 0.00302 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 03:00:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.02 | 9.02 | 1.90 | 1.90 | 9.0167 | 2.2853 | 9.0167 | 0.2535 | 0.3000 |
VAV_MID WITH REHEAT | 83.07 | 83.07 | 28.28 | 28.28 | 83.0698 | 28.2812 | 83.0698 | 0.3405 | 0.3000 |
VAV_TOP WITH REHEAT | 9.31 | 9.31 | 4.42 | 4.42 | 9.3122 | 4.4175 | 9.3122 | 0.4744 | 0.3000 |
CAV_BAS | 5.11 | 5.11 | 1.20 | 1.20 | 5.1080 | 1.2002 | 5.1080 | 0.2350 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.80 | 24.80 | 0.34 | 0.34 | 24.7999 | 24.7998 | 24.7999 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.5042 | 0.5042 | 0.5042 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.84 | 4.84 | 0.16 | 0.16 | 4.8421 | 4.8421 | 4.8421 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4914 | 0.4914 | 0.4914 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16047.689 | 16047.689 | 1.616866 | 0.00014039 | 323.509 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 16047.69 | 16047.69 | 1.616866 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 16106.86 | 16106.86 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 362266.502 | 362266.502 | 16.157148 | 0.00316927 | 8349.493 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 362266.50 | 362266.50 | 16.157148 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 201903.73 | 0.00 | 363467.10 | 363467.10 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 71160.205 | 71160.205 | 2.145954 | 0.00062254 | 1879.604 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 71160.21 | 71160.21 | 2.145954 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 49861.22 | 0.00 | 71414.66 | 71414.66 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7892.990 | 7892.990 | 0.237946 | 0.00006905 | 208.515 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7892.99 | 7892.99 | 0.237946 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00730057 | 46.5782 | 5534.74 | 0.00 | 7921.45 | 7921.45 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5739.649 | 5739.649 | 0.173147 | 0.00005021 | 151.582 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5739.65 | 5739.65 | 0.173147 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00740339 | 47.2263 | 4023.28 | 0.00 | 5760.01 | 5760.01 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10238.834 | 10238.834 | 0.309089 | 0.00008957 | 270.317 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10238.83 | 10238.83 | 0.309089 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00754589 | 48.1239 | 7174.03 | 0.00 | 10274.52 | 10274.52 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3636.930 | 3636.930 | 0.130380 | 0.00003182 | 89.592 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3636.93 | 3636.93 | 0.130380 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00673349 | 42.9994 | 2346.12 | 0.00 | 3648.36 | 3648.36 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 177162.046 | 177162.046 | 5.357794 | 0.00154989 | 4673.419 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 177162.05 | 177162.05 | 5.357794 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00768322 | 48.9892 | 124023.18 | 0.00 | 177751.85 | 177751.85 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 117682.535 | 117682.535 | 3.559265 | 0.00102954 | 3104.281 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 117682.54 | 117682.54 | 3.559265 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00768869 | 49.0236 | 82381.20 | 0.00 | 118073.55 | 118073.55 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 175606.355 | 175606.355 | 5.310630 | 0.00153628 | 4632.427 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 175606.35 | 175606.35 | 5.310630 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767851 | 48.9595 | 122935.78 | 0.00 | 176191.32 | 176191.32 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 108313.601 | 108313.601 | 3.275281 | 0.00094757 | 2857.392 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 108313.60 | 108313.60 | 3.275281 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00763955 | 48.7144 | 75832.27 | 0.00 | 108675.28 | 108675.28 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22897.363 | 22897.363 | 0.692859 | 0.00020032 | 603.862 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22897.36 | 22897.36 | 0.692859 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772642 | 49.2613 | 16025.02 | 0.00 | 22972.47 | 22972.47 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15111.296 | 15111.296 | 0.457280 | 0.00013220 | 398.515 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15111.30 | 15111.30 | 0.457280 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772470 | 49.2505 | 10575.65 | 0.00 | 15160.80 | 15160.80 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22728.363 | 22728.363 | 0.687735 | 0.00019884 | 599.409 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22728.36 | 22728.36 | 0.687735 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772420 | 49.2473 | 15906.88 | 0.00 | 22802.95 | 22802.95 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14334.066 | 14334.066 | 0.433721 | 0.00012540 | 378.034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14334.07 | 14334.07 | 0.433721 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00770744 | 49.1419 | 10032.25 | 0.00 | 14381.14 | 14381.14 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 164488.207 | -999.000 | 9.016681 | 0.00470434 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 164488.21 | 154857.72 | 9.016681 | 25.22 | 16.96 | 0.00884463 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 22.5194 | 24.00 | 0.00885136 | 46.9452 | 122331.63 | 0.00 | 166483.14 | 150921.49 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 44204.577 | 44204.577 | 2.705004 | 0.00038672 | 737.806 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 44204.58 | 44204.58 | 2.705004 | -0.90 | -1.46 | 0.00319204 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 75.0646 | 21.44 | 0.00568004 | 35.3709 | 19078.16 | 0.00 | 42356.60 | 42356.60 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1533301.028 | -999.000 | 83.069756 | 0.04385221 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1533301.03 | 1438241.86 | 83.069756 | 25.33 | 17.02 | 0.00886932 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 24.4445 | 24.00 | 0.00888497 | 47.1210 | 1116738.31 | 0.00 | 1551685.12 | 1402037.27 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 375848.694 | 375848.694 | 24.920927 | 0.00328809 | 6313.169 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 375848.69 | 375848.69 | 24.920927 | 0.16 | -0.27 | 0.00359113 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 81.4817 | 19.62 | 0.00712242 | 49.5119 | 266628.98 | 0.00 | 364798.39 | 364798.39 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 169230.090 | -999.000 | 9.312209 | 0.00483996 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 169230.09 | 159504.49 | 9.312209 | 25.18 | 16.94 | 0.00883697 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 21.8047 | 24.00 | 0.00884128 | 46.8925 | 126321.85 | 0.00 | 171290.36 | 155437.95 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 36741.735 | 36741.735 | 2.793663 | 0.00032143 | 623.407 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36741.74 | 36741.74 | 2.793663 | 1.77 | 1.32 | 0.00403421 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 72.6824 | 17.60 | 0.00730333 | 57.5879 | 31345.56 | 0.00 | 36382.81 | 36382.81 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 95943.467 | -999.000 | 5.107985 | 0.00274397 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 95943.47 | 88205.02 | 5.107985 | 25.29 | 17.10 | 0.00898880 | 11.01 | 11.01 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 23.4957 | 24.00 | 0.00904929 | 47.9803 | 61539.98 | 0.00 | 97080.29 | 86040.77 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.082328 | -0.99 | -2.30 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 38.9367 | 24.54 | 0.00269032 | 13.9492 | 0.00 | 0.00 | 100078.78 | 100078.78 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 490344.306 | 351281.928 | 24.799853 | 0.01200850 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 456118.50 | 453051.59 | -999.0 | 28.44 | 17.81 | 0.00854616 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | -999.0000 | 27.00 | 0.00854235 | 37.9340 | 370610.90 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9744.955 | 7061.295 | 0.504237 | 0.00023865 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 9029.97 | 8907.80 | -999.0 | 27.91 | 17.67 | 0.00859066 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00858346 | 38.1116 | 8673.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93616.613 | 67819.880 | 4.842066 | 0.00229266 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 86753.50 | 85533.21 | -999.0 | 27.91 | 17.67 | 0.00859429 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00858692 | 38.1268 | 83289.58 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9503.890 | 6884.136 | 0.491439 | 0.00023275 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8807.57 | 8685.79 | -999.0 | 27.92 | 17.67 | 0.00859271 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858538 | 38.1201 | 8453.37 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 490344.306 | 490344.306 | 24.799853 | 0.01200850 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 490344.31 | 490344.31 | 24.799853 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.3645 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9744.955 | 9744.955 | 0.504237 | 0.00023865 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9744.96 | 9744.96 | 0.504237 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1002 | 26.97 | 0.00850000 | 37.8111 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93616.613 | 93616.613 | 4.842066 | 0.00229266 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 93616.61 | 93616.61 | 4.842066 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2284 | 24.63 | 0.00573895 | 29.4465 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9503.890 | 9503.890 | 0.491439 | 0.00023275 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9503.89 | 9503.89 | 0.491439 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1809 | 23.59 | 0.00301667 | 16.5532 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17840.03 | 17840.03 | 24.799853 | -0.06 | -0.06 | 0.00842073 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.3645 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.504237 | -0.13 | -0.13 | 0.00831989 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1002 | 26.97 | 0.00850000 | 37.8111 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8241.36 | 8241.36 | 4.842066 | -0.14 | -0.14 | 0.00564053 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2284 | 24.63 | 0.00573895 | 29.4465 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.491439 | -0.13 | -1.32 | 0.00300629 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1809 | 23.59 | 0.00301667 | 16.5532 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16047.689 | 16047.689 | 1.616866 | 0.00014039 | 323.509 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.9322 | 0.950910 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | Sensible | 16047.69 | 16047.69 | 1.0000 | 1.91920460 | 1.616866 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.14037786 | 60.00 | 32.22 | 27.78 | 0.000 | 16047.69 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 16106.86 | 16106.86 | 1.91920460 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 362266.502 | 362266.502 | 16.157148 | 0.00316927 | 8349.493 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 21.0427 | 21.466202 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 362266.50 | 362266.50 | 1.0000 | 19.17838631 | 16.157148 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 3.16894209 | 60.00 | 32.22 | 27.78 | 0.000 | 362266.50 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 201903.73 | 0.00 | 363467.10 | 363467.10 | 19.17838631 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.39 | 18.50 | 0.00800000 | 52011.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 71160.205 | 71160.205 | 2.145954 | 0.00062254 | 1879.604 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 4.1334 | 4.216618 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 71160.21 | 71160.21 | 1.0000 | 2.54722750 | 2.145954 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.62247701 | 60.00 | 32.22 | 27.78 | 0.000 | 71160.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 49861.22 | 0.00 | 71414.66 | 71414.66 | 2.54722750 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61096.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7892.990 | 7892.990 | 0.237946 | 0.00006905 | 208.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.4585 | 0.467701 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7892.99 | 7892.99 | 1.0000 | 0.28243949 | 0.237946 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06904428 | 60.00 | 32.22 | 27.78 | 0.000 | 7892.99 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00730057 | 21.00 | 0.00730057 | 46.5782 | 5534.74 | 0.00 | 7921.45 | 7921.45 | 0.28243949 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61106.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5739.649 | 5739.649 | 0.173147 | 0.00005021 | 151.582 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.3334 | 0.340105 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5739.65 | 5739.65 | 1.0000 | 0.20552352 | 0.173147 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05020784 | 60.00 | 32.22 | 27.78 | 0.000 | 5739.65 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00740339 | 21.00 | 0.00740339 | 47.2263 | 4023.28 | 0.00 | 5760.01 | 5760.01 | 0.20552352 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61085.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10238.834 | 10238.834 | 0.309089 | 0.00008957 | 270.317 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.5947 | 0.606705 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10238.83 | 10238.83 | 1.0000 | 0.36688537 | 0.309089 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08956465 | 60.00 | 32.22 | 27.78 | 0.000 | 10238.83 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00754589 | 21.00 | 0.00754589 | 48.1239 | 7174.03 | 0.00 | 10274.52 | 10274.52 | 0.36688537 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61064.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3636.930 | 3636.930 | 0.130380 | 0.00003182 | 89.592 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.2113 | 0.215507 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3636.93 | 3636.93 | 1.0000 | 0.15475931 | 0.130380 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.03181421 | 60.00 | 32.22 | 27.78 | 0.000 | 3636.93 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00673349 | 21.00 | 0.00673349 | 42.9994 | 2346.12 | 0.00 | 3648.36 | 3648.36 | 0.15475931 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.92 | 19.94 | 0.00800000 | 56634.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 177162.046 | 177162.046 | 5.357794 | 0.00154989 | 4673.419 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 10.2907 | 10.497786 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 177162.05 | 177162.05 | 1.0000 | 6.35965210 | 5.357794 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.54973276 | 60.00 | 32.22 | 27.78 | 0.000 | 177162.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00768322 | 21.00 | 0.00768322 | 48.9892 | 124023.18 | 0.00 | 177751.85 | 177751.85 | 6.35965210 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61009.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 117682.535 | 117682.535 | 3.559265 | 0.00102954 | 3104.281 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 6.8357 | 6.973311 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 117682.54 | 117682.54 | 1.0000 | 4.22481486 | 3.559265 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.02943313 | 60.00 | 32.22 | 27.78 | 0.000 | 117682.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00768869 | 21.00 | 0.00768869 | 49.0236 | 82381.20 | 0.00 | 118073.55 | 118073.55 | 4.22481486 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 175606.355 | 175606.355 | 5.310630 | 0.00153628 | 4632.427 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 10.2003 | 10.405603 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 175606.35 | 175606.35 | 1.0000 | 6.30366913 | 5.310630 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.53612428 | 60.00 | 32.22 | 27.78 | 0.000 | 175606.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00767851 | 21.00 | 0.00767851 | 48.9595 | 122935.78 | 0.00 | 176191.32 | 176191.32 | 6.30366913 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 108313.601 | 108313.601 | 3.275281 | 0.00094757 | 2857.392 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 6.2915 | 6.418152 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 108313.60 | 108313.60 | 1.0000 | 3.88772836 | 3.275281 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.94747797 | 60.00 | 32.22 | 27.78 | 0.000 | 108313.60 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00763955 | 21.00 | 0.00763955 | 48.7144 | 75832.27 | 0.00 | 108675.28 | 108675.28 | 3.88772836 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22897.363 | 22897.363 | 0.692859 | 0.00020032 | 603.862 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 1.3300 | 1.356790 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22897.36 | 22897.36 | 1.0000 | 0.82241774 | 0.692859 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.20029568 | 60.00 | 32.22 | 27.78 | 0.000 | 22897.36 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772642 | 21.00 | 0.00772642 | 49.2613 | 16025.02 | 0.00 | 22972.47 | 22972.47 | 0.82241774 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15111.296 | 15111.296 | 0.457280 | 0.00013220 | 398.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.8778 | 0.895424 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15111.30 | 15111.30 | 1.0000 | 0.54278771 | 0.457280 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.13218672 | 60.00 | 32.22 | 27.78 | 0.000 | 15111.30 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772470 | 21.00 | 0.00772470 | 49.2505 | 10575.65 | 0.00 | 15160.80 | 15160.80 | 0.54278771 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22728.363 | 22728.363 | 0.687735 | 0.00019884 | 599.409 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 1.3202 | 1.346775 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22728.36 | 22728.36 | 1.0000 | 0.81633566 | 0.687735 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.19881735 | 60.00 | 32.22 | 27.78 | 0.000 | 22728.36 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772420 | 21.00 | 0.00772420 | 49.2473 | 15906.88 | 0.00 | 22802.95 | 22802.95 | 0.81633566 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14334.066 | 14334.066 | 0.433721 | 0.00012540 | 378.034 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 0.8326 | 0.849369 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14334.07 | 14334.07 | 1.0000 | 0.51482247 | 0.433721 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12538787 | 60.00 | 32.22 | 27.78 | 0.000 | 14334.07 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00770744 | 21.00 | 0.00770744 | 49.1419 | 10032.25 | 0.00 | 14381.14 | 14381.14 | 0.51482247 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 164488.207 | -999.000 | 9.016681 | 0.00470434 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2817 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.016681 | 10.70271761 | 4197.9300 | 999.8980 | 56.13476045 | 15.00 | 6.67 | 8.33 | 1962962.79 | 8.3796 | 8.379589 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 164488.21 | 154857.72 | 1.0000 | 10.70271761 | 9.016681 | 25.22 | 16.96 | 0.00884463 | 47871.6 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 4.70386200 | 6.67 | 15.00 | 8.33 | 19484.568 | 145003.64 | 29.40 | 0.00882150 | 18.34 | 2.03050000 | 22.5194 | 24.00 | 0.00885136 | 24.00 | 0.00885136 | 46.9452 | 122331.63 | 0.00 | 166483.14 | 150921.49 | 10.70271761 | 25.22 | 17.11 | 0.00884463 | 47871.6 | 11.41 | 11.28 | 0.00826814 | 32316.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 44204.577 | 44204.577 | 2.705004 | 0.00038672 | 737.806 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.016681 | 10.70271761 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 2.5677 | 2.619354 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 44204.58 | 44204.58 | 1.0000 | 3.21081528 | 2.705004 | -0.90 | -1.46 | 0.00319204 | 7072.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.38668148 | 60.00 | 32.22 | 27.78 | 0.000 | 44204.58 | -4.20 | 0.00269032 | -4.20 | 2.03050000 | 75.0646 | 9.03 | 0.00470242 | 21.44 | 0.00568004 | 35.3709 | 19078.16 | 0.00 | 42356.60 | 42356.60 | 3.21081528 | 2.80 | 0.80 | 0.00319204 | 10813.3 | 15.85 | 7.69 | 0.00319204 | 24005.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1533301.028 | -999.000 | 83.069756 | 0.04385221 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3276 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.069756 | 98.60303486 | 4197.9300 | 999.8980 | 56.13476045 | 15.00 | 6.67 | 8.33 | 1962962.79 | 78.1116 | 78.111569 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1533301.03 | 1438241.86 | 1.0000 | 98.60303486 | 83.069756 | 25.33 | 17.02 | 0.00886932 | 48053.1 | 11.02 | 11.02 | 0.00850000 | 32502.9 | 43.84774192 | 6.67 | 15.00 | 8.33 | 179509.319 | 1353791.71 | 29.40 | 0.00882150 | 18.34 | 20.30600000 | 24.4445 | 24.00 | 0.00888497 | 24.00 | 0.00888497 | 47.1210 | 1116738.31 | 0.00 | 1551685.12 | 1402037.27 | 98.60303486 | 25.33 | 17.17 | 0.00886932 | 48053.1 | 11.41 | 11.28 | 0.00826758 | 32316.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 375848.694 | 375848.694 | 24.920927 | 0.00328809 | 6313.169 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.069756 | 98.60303486 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 21.8316 | 22.271018 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 375848.69 | 375848.69 | 1.0000 | 29.58091046 | 24.920927 | 0.16 | -0.27 | 0.00359113 | 9138.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 3.28775291 | 60.00 | 32.22 | 27.78 | 0.000 | 375848.69 | -4.20 | 0.00269032 | -4.20 | 20.30600000 | 81.4817 | 19.32 | 0.00755478 | 19.62 | 0.00712242 | 49.5119 | 266628.98 | 0.00 | 364798.39 | 364798.39 | 29.58091046 | 2.80 | 1.37 | 0.00359113 | 11813.5 | 14.99 | 7.75 | 0.00359113 | 24145.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 169230.090 | -999.000 | 9.312209 | 0.00483996 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2675 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.312209 | 11.05350625 | 4197.9300 | 999.8980 | 56.13476045 | 15.00 | 6.67 | 8.33 | 1962962.79 | 8.6212 | 8.621156 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 169230.09 | 159504.49 | 1.0000 | 11.05350625 | 9.312209 | 25.18 | 16.94 | 0.00883697 | 47812.9 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 4.83946542 | 6.67 | 15.00 | 8.33 | 20123.188 | 149106.90 | 29.40 | 0.00882150 | 18.34 | 2.03050000 | 21.8047 | 24.00 | 0.00884128 | 24.00 | 0.00884128 | 46.8925 | 126321.85 | 0.00 | 171290.36 | 155437.95 | 11.05350625 | 25.18 | 17.09 | 0.00883697 | 47812.9 | 11.41 | 11.28 | 0.00826834 | 32316.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 36741.735 | 36741.735 | 2.793663 | 0.00032143 | 623.407 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.312209 | 11.05350625 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 2.1342 | 2.177142 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 36741.74 | 36741.74 | 1.0000 | 3.31605187 | 2.793663 | 1.77 | 1.32 | 0.00403421 | 11884.8 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.32139994 | 60.00 | 32.22 | 27.78 | 0.000 | 36741.74 | -4.20 | 0.00269032 | -4.20 | 2.03050000 | 72.6824 | 17.67 | 0.00760981 | 17.60 | 0.00730333 | 57.5879 | 31345.56 | 0.00 | 36382.81 | 36382.81 | 3.31605187 | 2.80 | 1.99 | 0.00403421 | 12923.9 | 13.64 | 7.63 | 0.00403421 | 23895.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 95943.467 | -999.000 | 5.107985 | 0.00274397 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5497 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:VariableVolume | 5.107985 | 6.06313131 | 4197.9300 | 999.8980 | 56.13476045 | 15.00 | 6.67 | 8.33 | 1962962.79 | 4.8877 | 4.887686 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 95943.47 | 88205.02 | 1.0000 | 6.06313131 | 5.107985 | 25.29 | 17.10 | 0.00898880 | 48315.6 | 11.01 | 11.01 | 0.00850000 | 32491.6 | 2.74369110 | 6.67 | 15.00 | 8.33 | 11109.297 | 84834.17 | 28.88 | 0.00882066 | 18.17 | 1.20015641 | 23.4957 | 24.00 | 0.00904929 | 24.00 | 0.00904929 | 47.9803 | 61539.98 | 0.00 | 97080.29 | 86040.77 | 6.06313131 | 25.29 | 17.25 | 0.00898880 | 48315.6 | 11.40 | 11.28 | 0.00826688 | 32304.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:VariableVolume | 5.107985 | 6.06313131 | 4197.9300 | 999.8980 | 14.76247241 | 54.44 | 82.22 | 27.78 | 1721577.32 | 5.8086 | 5.925528 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.082328 | -0.99 | -2.30 | 0.00269032 | 5731.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.20 | 0.00269032 | -4.20 | 1.20015641 | 38.9367 | 0.00 | 0.00269032 | 24.54 | 0.00269032 | 13.9492 | 0.00 | 0.00 | 100078.78 | 100078.78 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 490344.306 | 351281.928 | 24.799853 | 0.01200850 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7269 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 456118.50 | 453051.59 | 0.9302 | -999.0 | -999.0 | 28.44 | 17.81 | 0.00854616 | 50406.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456118.50 | 29.40 | 0.00882150 | 18.34 | 0.33839277 | -999.0000 | 27.00 | 0.00854235 | 27.00 | 0.00854235 | 37.9340 | 370610.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9744.955 | 7061.295 | 0.504237 | 0.00023865 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8096 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 9029.97 | 8907.80 | 0.9266 | -999.0 | -999.0 | 27.91 | 17.67 | 0.00859066 | 49980.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9029.97 | 25.60 | 0.00881543 | 17.07 | 0.01563234 | -999.0000 | 27.00 | 0.00858346 | 27.00 | 0.00858346 | 38.1116 | 8673.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93616.613 | 67819.880 | 4.842066 | 0.00229266 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8164 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 86753.50 | 85533.21 | 0.9267 | -999.0 | -999.0 | 27.91 | 17.67 | 0.00859429 | 49987.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86753.50 | 25.60 | 0.00881543 | 17.07 | 0.15632344 | -999.0000 | 27.00 | 0.00858692 | 27.00 | 0.00858692 | 38.1268 | 83289.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9503.890 | 6884.136 | 0.491439 | 0.00023275 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8134 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8807.57 | 8685.79 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859271 | 49992.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8807.57 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858538 | 27.00 | 0.00858538 | 38.1201 | 8453.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 490344.306 | 490344.306 | 24.799853 | 0.01200850 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 490344.31 | 490344.31 | 1.0000 | 29.43719668 | 24.799853 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 490344.31 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.3645 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9744.955 | 9744.955 | 0.504237 | 0.00023865 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9744.96 | 9744.96 | 1.0000 | 0.59852504 | 0.504237 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9744.96 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1002 | 0.00 | 0.00850000 | 26.97 | 0.00850000 | 37.8111 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93616.613 | 93616.613 | 4.842066 | 0.00229266 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 93616.61 | 93616.61 | 1.0000 | 5.74748741 | 4.842066 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93616.61 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.2284 | 0.00 | 0.00573895 | 24.63 | 0.00573895 | 29.4465 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9503.890 | 9503.890 | 0.491439 | 0.00023275 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9503.89 | 9503.89 | 1.0000 | 0.58333321 | 0.491439 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9503.89 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1809 | 0.00 | 0.00301667 | 23.59 | 0.00301667 | 16.5532 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.799853 | 29.43719668 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17840.03 | 17840.03 | 1.0000 | 29.43719668 | 24.799853 | -0.06 | -0.06 | 0.00842073 | 21001.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17840.03 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.3645 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.504237 | 0.59852504 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.59852504 | 0.504237 | -0.13 | -0.13 | 0.00831989 | 20674.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1002 | 0.00 | 0.00850000 | 26.97 | 0.00850000 | 37.8111 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.842066 | 5.74748741 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8241.36 | 8241.36 | 1.0000 | 5.74748741 | 4.842066 | -0.14 | -0.14 | 0.00564053 | 13968.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8241.36 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.2284 | 0.00 | 0.00573895 | 24.63 | 0.00573895 | 29.4465 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.491439 | 0.58333321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.58333321 | 0.491439 | -0.13 | -1.32 | 0.00300629 | 7383.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1809 | 0.00 | 0.00301667 | 23.59 | 0.00301667 | 16.5532 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.02 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 83.07 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.31 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.11 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.80 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2970.00 | 214.17 | 47.17 |
CORE_BOTTOM | 2566.50 | 379.83 | 13.00 |
CORE_MID | 1378.33 | 2364.83 | 12.00 |
CORE_TOP | 1444.00 | 3503.00 | 371.83 |
PERIMETER_BOT_ZN_3 | 1477.50 | 2866.67 | 16.83 |
PERIMETER_BOT_ZN_2 | 1817.33 | 2869.67 | 85.67 |
PERIMETER_BOT_ZN_1 | 2220.17 | 2580.33 | 154.00 |
PERIMETER_BOT_ZN_4 | 3087.83 | 1230.50 | 218.33 |
PERIMETER_MID_ZN_3 | 1660.00 | 4045.67 | 790.00 |
PERIMETER_MID_ZN_2 | 1852.50 | 3097.50 | 706.67 |
PERIMETER_MID_ZN_1 | 2281.00 | 3180.83 | 518.33 |
PERIMETER_MID_ZN_4 | 2165.33 | 3374.67 | 567.50 |
PERIMETER_TOP_ZN_3 | 2311.33 | 4385.67 | 1530.00 |
PERIMETER_TOP_ZN_2 | 2718.50 | 3841.50 | 1393.67 |
PERIMETER_TOP_ZN_1 | 2635.67 | 3614.50 | 1094.50 |
PERIMETER_TOP_ZN_4 | 2581.50 | 3786.67 | 1169.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 710.67 | 710.67 |
DATACENTER_MID_ZN_6 | 5855.50 | 139.50 | 125.17 |
DATACENTER_TOP_ZN_6 | 5521.83 | 327.50 | 202.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5749.50 | 5749.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 782.17 | 0.00 | 381.67 |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 4.67 | 0.00 | 0.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 18.83 | 0.00 | 18.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 34.83 | 0.00 | 34.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 88.67 | 0.00 | 49.67 |
PERIMETER_MID_ZN_3 | 2.50 | 0.00 | 0.33 | 0.00 |
PERIMETER_MID_ZN_2 | 5.33 | 18.67 | 0.00 | 18.67 |
PERIMETER_MID_ZN_1 | 1.17 | 31.33 | 0.00 | 30.33 |
PERIMETER_MID_ZN_4 | 0.83 | 32.50 | 0.00 | 19.00 |
PERIMETER_TOP_ZN_3 | 53.00 | 0.00 | 15.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 29.00 | 19.50 | 2.33 | 19.00 |
PERIMETER_TOP_ZN_1 | 18.17 | 26.33 | 0.83 | 25.00 |
PERIMETER_TOP_ZN_4 | 12.17 | 31.00 | 0.33 | 17.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 58.50 | 936.50 | 15.50 | 503.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.241 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.026 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.746 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.705 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.917 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.252 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.436 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 1.940 | 0.019 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.715 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.036 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.282 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.189 | 0.044 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.716 | 0.053 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.138 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.291 | 0.053 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.203 | 0.055 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 28.890 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 48929021.12 | 0.00 | 48929021.12 | 0.00 | 48929021.12 | 37848132.68 | 4480.55 | 335.01 | 3944.44 | 0.00 |
CORE_BOTTOM | 43006295.06 | 0.00 | 43006295.06 | 0.00 | 43006295.06 | 33990283.35 | 3780.12 | 117.99 | 4861.89 | 393.52 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 4310.76 | 648.55 | 3800.69 | 145.32 |
CORE_TOP | 28649984.55 | 0.00 | 28649984.55 | 0.00 | 28649984.55 | 33990283.35 | 4492.26 | 1179.84 | 3087.90 | 205.52 |
PERIMETER_BOT_ZN_3 | 4831703.84 | 0.00 | 4831703.84 | 189059.25 | 5020763.09 | 4267819.30 | 5037.46 | 180.67 | 3541.87 | 393.52 |
PERIMETER_BOT_ZN_2 | 4196674.59 | 0.00 | 4196674.59 | 126039.41 | 4322714.00 | 2750345.05 | 4920.83 | 156.96 | 3682.21 | 393.52 |
PERIMETER_BOT_ZN_1 | 7431104.13 | 0.00 | 7431104.13 | 189059.25 | 7620163.38 | 4267912.63 | 4769.71 | 166.15 | 3824.14 | 393.52 |
PERIMETER_BOT_ZN_4 | 6513842.17 | 0.00 | 6513842.17 | 126039.41 | 6639881.58 | 2750345.05 | 3974.07 | 141.96 | 4643.97 | 393.52 |
PERIMETER_MID_ZN_3 | 36654343.19 | 0.00 | 36654343.19 | 443394.83 | 37097738.02 | 42678193.03 | 4826.46 | 591.40 | 3342.14 | 145.32 |
PERIMETER_MID_ZN_2 | 34883757.86 | 0.00 | 34883757.86 | 295596.35 | 35179354.22 | 27503450.52 | 4950.48 | 662.57 | 3146.95 | 680.46 |
PERIMETER_MID_ZN_1 | 65025867.81 | 0.00 | 65025867.81 | 443394.83 | 65469262.64 | 42679126.28 | 4399.29 | 690.05 | 3670.67 | 145.32 |
PERIMETER_MID_ZN_4 | 39278563.66 | 0.00 | 39278563.66 | 295596.35 | 39574160.02 | 27503450.52 | 4650.94 | 822.28 | 3286.78 | 145.32 |
PERIMETER_TOP_ZN_3 | 3667628.50 | 0.00 | 3667628.50 | 550519.38 | 4218147.88 | 4267819.30 | 4396.53 | 1082.47 | 3280.99 | 205.52 |
PERIMETER_TOP_ZN_2 | 3724204.53 | 0.00 | 3724204.53 | 367012.67 | 4091217.19 | 2750345.05 | 4294.41 | 999.89 | 3465.70 | 205.52 |
PERIMETER_TOP_ZN_1 | 6543392.75 | 0.00 | 6543392.75 | 550519.38 | 7093912.13 | 4267912.63 | 4189.65 | 794.26 | 3776.09 | 205.52 |
PERIMETER_TOP_ZN_4 | 3974686.33 | 0.00 | 3974686.33 | 367012.67 | 4341698.99 | 2750345.05 | 4417.96 | 1356.58 | 2985.45 | 205.52 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.45E+09 | 0.00 | 0.45E+09 | 0.00 | 0.45E+09 | 10671554.30 | 9.00 | 60.17 | 8690.83 | 2816.67 |
Total Facility | 0.54E+10 | 0.00 | 0.54E+10 | 17245085.19 | 0.55E+10 | 0.50E+10 | 6537.43 | 4380.11 | 8753.80 | 3352.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.2870 | 0.0000 | 2.2870 | 0.0000 | 2.2870 | 1.2002 | 1663.55 | 335.01 | 3944.44 |
CORE_BOTTOM | 1.9087 | 0.0000 | 1.9087 | 0.0000 | 1.9087 | 1.0778 | 1292.44 | 114.15 | 4536.41 |
CORE_MID | 13.8795 | 0.0000 | 13.8795 | 0.0000 | 13.8795 | 10.7782 | 1600.63 | 648.10 | 3694.28 |
CORE_TOP | 1.3130 | 0.0000 | 1.3130 | 0.0000 | 1.3130 | 1.0778 | 1746.81 | 1179.82 | 3016.37 |
PERIMETER_BOT_ZN_3 | 0.2143 | 0.0000 | 0.2143 | 0.0043 | 0.2186 | 0.1353 | 2539.95 | 176.52 | 3226.53 |
PERIMETER_BOT_ZN_2 | 0.1887 | 0.0000 | 0.1887 | 0.0029 | 0.1916 | 0.0872 | 2424.12 | 152.29 | 3366.59 |
PERIMETER_BOT_ZN_1 | 0.3358 | 0.0000 | 0.3358 | 0.0043 | 0.3401 | 0.1353 | 2273.00 | 161.42 | 3508.58 |
PERIMETER_BOT_ZN_4 | 0.2921 | 0.0000 | 0.2921 | 0.0029 | 0.2950 | 0.0872 | 1482.61 | 138.94 | 4321.45 |
PERIMETER_MID_ZN_3 | 1.6740 | 0.0000 | 1.6740 | 0.0101 | 1.6841 | 1.3533 | 2117.28 | 590.80 | 3234.92 |
PERIMETER_MID_ZN_2 | 1.5631 | 0.0000 | 1.5631 | 0.0071 | 1.5703 | 0.8721 | 1754.37 | 660.62 | 2619.02 |
PERIMETER_MID_ZN_1 | 2.9997 | 0.0000 | 2.9997 | 0.0101 | 3.0098 | 1.3533 | 1690.38 | 689.56 | 3563.06 |
PERIMETER_MID_ZN_4 | 1.7925 | 0.0000 | 1.7925 | 0.0067 | 1.7992 | 0.8721 | 1941.51 | 821.66 | 3179.83 |
PERIMETER_TOP_ZN_3 | 0.1680 | 0.0000 | 0.1680 | 0.0125 | 0.1805 | 0.1353 | 1653.35 | 1082.29 | 3207.37 |
PERIMETER_TOP_ZN_2 | 0.1717 | 0.0000 | 0.1717 | 0.0083 | 0.1801 | 0.0872 | 1556.62 | 999.71 | 3386.67 |
PERIMETER_TOP_ZN_1 | 0.3022 | 0.0000 | 0.3022 | 0.0125 | 0.3147 | 0.1353 | 1449.50 | 794.04 | 3699.47 |
PERIMETER_TOP_ZN_4 | 0.1814 | 0.0000 | 0.1814 | 0.0083 | 0.1897 | 0.0872 | 1675.79 | 1356.43 | 2910.78 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.8593 | 0.0000 | 14.8593 | 0.0000 | 14.8593 | 0.3384 | 8.67 | 60.17 | 5874.17 |
Total Facility | 242.4757 | 0.0000 | 242.4757 | 0.3961 | 242.8718 | 158.4706 | 3720.43 | 4372.75 | 5936.83 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 92961795.39 | 0.00 | 92961795.39 | 48026705.38 | 3497.28 | 7.95 | 5254.77 | 393.52 |
VAV_MID WITH REHEAT | 0.68E+09 | 0.00 | 0.68E+09 | 0.48E+09 | 3931.06 | 4.16 | 4824.78 | 145.32 |
VAV_TOP WITH REHEAT | 65600432.24 | 0.00 | 65600432.24 | 48026705.38 | 4034.03 | 7.52 | 4718.45 | 205.43 |
CAV_BAS | 68938404.43 | 0.00 | 68938404.43 | 37848132.68 | 4479.00 | 0.13 | 4280.87 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.64E+09 | 0.00 | 0.64E+09 | 10671554.30 | 9.00 | 0.00 | 8751.00 | 2816.67 |
AIRLOOP DATACENTER BOT | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442001.72 | 0.00 | 3442001.72 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.1418 | 0.0000 | 4.1418 | 1.5229 | 1054.17 | 5.31 | 4883.53 |
VAV_MID WITH REHEAT | 30.9274 | 0.0000 | 30.9274 | 15.2292 | 1225.82 | 4.12 | 4713.05 |
VAV_TOP WITH REHEAT | 3.0099 | 0.0000 | 3.0099 | 1.5229 | 1294.09 | 6.78 | 4642.13 |
CAV_BAS | 3.2222 | 0.0000 | 3.2222 | 1.2002 | 1662.00 | 0.13 | 4280.87 |
AIRLOOP DATACENTER BASEMENT | 20.9359 | 0.0000 | 20.9359 | 0.3384 | 8.67 | 0.00 | 5934.33 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 603.44 | 3935.92 | 0.00 | 0.00 | 0.00 | 781.09 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 346.13 | 3361.86 | 0.00 | 0.00 | 0.00 | 1248.53 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 30.21 | 3063.11 | 0.00 | 0.00 | 0.00 | 1925.17 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 328.40 | 3950.71 | 0.00 | 9.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 60.17 | 8690.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.8687 | 5.9334 | 0.0000 | 0.0000 | 0.0000 | 2.3932 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.5634 | 45.2857 | 0.0000 | 0.0000 | 0.0000 | 22.6828 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8327 | 4.7501 | 0.0000 | 0.0000 | 0.0000 | 2.1985 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6930 | 4.7050 | 0.0000 | 1.0411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4781 | 21.1770 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1185 |
Fields with Defaults | 3880 |
Autosized Fields | 335 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
Electricity:Building | 17146.87 | 216479.19 | 07-MAY-17:20 | 1025582.59 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17146.87 | 216479.19 | 07-MAY-17:20 | 1025582.59 | 01-DEC-16:20 |
InteriorLights:Electricity | 2470.48 | 9223.03 | 23-APR-17:20 | 247210.90 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2470.48 | 9223.03 | 23-APR-17:20 | 247210.90 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 2470.48 | 9223.03 | 23-APR-17:20 | 247210.90 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2470.48 | 9223.03 | 23-APR-17:20 | 247210.90 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.32 | 603.11 | 19-MAR-17:10 | 3823.11 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.96 | 43.94 | 08-JAN-10:20 | 1662.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.96 | 43.94 | 08-JAN-10:20 | 1662.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.43 | 388.67 | 09-APR-17:10 | 2463.76 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.99 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.99 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.12 | 603.12 | 19-MAR-17:10 | 3823.18 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.75 | 43.94 | 01-JAN-09:40 | 1662.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.75 | 43.94 | 01-JAN-09:40 | 1662.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.41 | 388.67 | 19-MAR-17:10 | 2463.75 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.98 | 28.32 | 01-JAN-10:30 | 1071.42 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.98 | 28.32 | 01-JAN-10:30 | 1071.42 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 472.97 | 6031.15 | 19-MAR-17:10 | 38231.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 109.32 | 439.44 | 08-JAN-10:10 | 16625.62 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 109.32 | 439.44 | 08-JAN-10:10 | 16625.62 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 304.18 | 3886.70 | 09-APR-17:10 | 24637.60 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 69.83 | 283.19 | 01-JAN-09:50 | 10714.18 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 69.83 | 283.19 | 01-JAN-09:50 | 10714.18 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 471.10 | 6031.24 | 19-MAR-17:10 | 38231.83 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 107.44 | 439.45 | 01-JAN-09:40 | 16625.99 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 107.44 | 439.45 | 01-JAN-09:40 | 16625.99 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 304.03 | 3886.68 | 19-MAR-17:10 | 24637.51 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 69.68 | 283.19 | 01-JAN-10:20 | 10714.18 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 69.68 | 283.19 | 01-JAN-10:20 | 10714.18 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.30 | 603.11 | 19-MAR-17:10 | 3823.11 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.93 | 43.94 | 08-JAN-10:10 | 1662.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.93 | 43.94 | 08-JAN-10:10 | 1662.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.42 | 388.67 | 09-APR-17:10 | 2463.76 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.98 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.98 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.11 | 603.12 | 19-MAR-17:10 | 3823.18 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.74 | 43.94 | 01-JAN-09:40 | 1662.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.74 | 43.94 | 01-JAN-09:40 | 1662.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.40 | 388.67 | 19-MAR-17:10 | 2463.75 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.97 | 28.32 | 01-JAN-10:20 | 1071.42 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.97 | 28.32 | 01-JAN-10:20 | 1071.42 | 02-JAN-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1348.29 | 3835.18 | 16-JAN-05:50 | 405558.11 | 29-AUG-12:30 |
HeatRejection:Electricity | 293.39 | 85.61 | 07-JAN-08:00 | 72883.01 | 27-APR-12:20 |
General:HeatRejection:Electricity | 293.39 | 85.61 | 07-JAN-08:00 | 72883.01 | 27-APR-12:20 |
Electricity:HVAC | 4034.61 | 52609.74 | 12-JAN-02:20 | 439625.18 | 29-AUG-15:20 |
ExteriorEquipment:Electricity | 2566.28 | 20217.42 | 01-JAN-00:10 | 233396.85 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
ElectricityPurchased:Plant | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
Cogeneration:ElectricityPurchased | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
ElectricityNet:Plant | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
Cogeneration:ElectricityNet | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
General:Cogeneration:ElectricityNet | 25397.81 | 294517.03 | 29-MAY-04:50 | 2044516.27 | 29-AUG-15:20 |
Fans:Electricity | 2311.71 | 47439.98 | 02-JAN-05:50 | 277574.26 | 11-SEP-14:40 |
General:Fans:Electricity | 2311.71 | 47439.98 | 02-JAN-05:50 | 277574.26 | 11-SEP-14:40 |
ExteriorLights:Electricity | 356.44 | 0.00 | 01-JAN-08:10 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.44 | 0.00 | 01-JAN-08:10 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 951.53 | 1498.10 | 03-JAN-08:00 | 421316.31 | 29-AUG-14:30 |
General:Cooling:Electricity | 951.53 | 1498.10 | 03-JAN-08:00 | 421316.31 | 29-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1043.98 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:10 |
General:Humidifier:Electricity | 1043.98 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 438.44 | 0.00 | 01-JAN-00:10 | 52005.65 | 10-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 438.44 | 0.00 | 01-JAN-00:10 | 52005.65 | 10-FEB-12:20 |
Pumps:Electricity | 289.18 | 3730.44 | 01-JAN-00:10 | 42585.91 | 20-JUL-12:20 |
General:Pumps:Electricity | 289.18 | 3730.44 | 01-JAN-00:10 | 42585.91 | 20-JUL-12:20 |
WIRED_LTG_ELECTRICITY | 69.42 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1111.90 | 0.00 | 01-JAN-00:10 | 1281357.61 | 02-JAN-06:10 |
NaturalGas:Plant | 1111.90 | 0.00 | 01-JAN-00:10 | 1281357.61 | 02-JAN-06:10 |
Heating:NaturalGas | 1111.90 | 0.00 | 01-JAN-00:10 | 1281357.61 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 1111.90 | 0.00 | 01-JAN-00:10 | 1281357.61 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5676.80 | 3686.43 | 03-JAN-08:00 | 2342686.28 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 5676.80 | 3686.43 | 03-JAN-08:00 | 2342686.28 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 5676.80 | 3686.43 | 03-JAN-08:00 | 2342686.28 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4562.02 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
Water:HVAC | 388.36 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:Water | 388.36 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:Water | 388.36 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
MainsWater:Facility | 4562.02 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
MainsWater:HVAC | 388.36 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:MainsWater | 388.36 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:MainsWater | 388.36 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Water:Plant | 4173.66 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 4173.66 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1893.49 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 1893.49 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 1893.49 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 1893.49 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 32352.12 | 96817.38 | 22-JAN-06:00 | 9079727.84 | 29-AUG-14:30 |
EnergyTransfer:Building | 17156.41 | 88495.62 | 22-JAN-13:20 | 1622210.89 | 10-AUG-15:10 |
EnergyTransfer:Zone:BASEMENT | 604.58 | 0.00 | 01-JAN-00:10 | 93444.35 | 13-NOV-07:10 |
Heating:EnergyTransfer | 201.75 | 0.00 | 11-JAN-22:10 | 860366.09 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 201.75 | 0.00 | 11-JAN-22:10 | 860366.09 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 16954.65 | 87342.36 | 17-JAN-04:30 | 1622210.89 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 604.58 | 0.00 | 01-JAN-00:10 | 93444.35 | 13-NOV-07:10 |
General:Cooling:EnergyTransfer | 16954.65 | 87342.36 | 17-JAN-04:30 | 1622210.89 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 604.58 | 0.00 | 01-JAN-00:10 | 93444.35 | 13-NOV-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 581.38 | 0.00 | 01-JAN-00:10 | 52007.30 | 10-OCT-07:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 581.38 | 0.00 | 01-JAN-00:10 | 52007.30 | 10-OCT-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 581.38 | 0.00 | 01-JAN-00:10 | 52007.30 | 10-OCT-07:40 |
EnergyTransfer:Zone:CORE_MID | 3925.78 | 0.00 | 01-JAN-00:10 | 409797.21 | 20-JUL-12:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.42 | 0.00 | 01-JAN-00:10 | 277920.64 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.42 | 0.00 | 01-JAN-00:10 | 277920.64 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3924.37 | 0.00 | 01-JAN-00:10 | 409797.21 | 20-JUL-12:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3924.37 | 0.00 | 01-JAN-00:10 | 409797.21 | 20-JUL-12:30 |
EnergyTransfer:Zone:CORE_TOP | 336.65 | 0.00 | 01-JAN-00:10 | 65807.71 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.32 | 0.00 | 01-JAN-00:10 | 65807.71 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.32 | 0.00 | 01-JAN-00:10 | 65807.71 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 331.34 | 0.00 | 01-JAN-00:10 | 45764.24 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 331.34 | 0.00 | 01-JAN-00:10 | 45764.24 | 10-AUG-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.99 | 0.00 | 01-JAN-00:10 | 9687.31 | 24-JUL-14:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.99 | 0.00 | 01-JAN-00:10 | 9687.31 | 24-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.99 | 0.00 | 01-JAN-00:10 | 9687.31 | 24-JUL-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 51.48 | 0.00 | 01-JAN-00:10 | 15268.83 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 404.38 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 404.38 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 51.48 | 0.00 | 01-JAN-00:10 | 15268.83 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 51.48 | 0.00 | 01-JAN-00:10 | 15268.83 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 94.51 | 0.00 | 01-JAN-00:10 | 23683.61 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 5013.26 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 5013.26 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 94.47 | 0.00 | 01-JAN-00:10 | 23683.61 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 94.47 | 0.00 | 01-JAN-00:10 | 23683.61 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.08 | 0.00 | 01-JAN-00:10 | 18987.16 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.08 | 0.00 | 01-JAN-00:10 | 18987.16 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.08 | 0.00 | 01-JAN-00:10 | 18987.16 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 416.41 | 0.00 | 01-JAN-00:10 | 99674.01 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.30 | 0.00 | 01-JAN-00:10 | 99674.01 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.30 | 0.00 | 01-JAN-00:10 | 99674.01 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 390.11 | 0.00 | 01-JAN-00:10 | 84255.15 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 390.11 | 0.00 | 01-JAN-00:10 | 84255.15 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 418.23 | 0.00 | 01-JAN-00:10 | 155458.27 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 16.52 | 0.00 | 01-JAN-00:10 | 83248.13 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 16.52 | 0.00 | 01-JAN-00:10 | 83248.13 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 401.71 | 0.00 | 01-JAN-00:10 | 155458.27 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 401.71 | 0.00 | 01-JAN-00:10 | 155458.27 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 829.49 | 0.00 | 01-JAN-00:10 | 251006.94 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 15.73 | 0.00 | 01-JAN-00:10 | 125204.50 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 15.73 | 0.00 | 01-JAN-00:10 | 125204.50 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 813.76 | 0.00 | 01-JAN-00:10 | 251006.94 | 04-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 813.76 | 0.00 | 01-JAN-00:10 | 251006.94 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 484.01 | 0.00 | 01-JAN-00:10 | 169102.05 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.30 | 0.00 | 01-JAN-00:10 | 65654.99 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.30 | 0.00 | 01-JAN-00:10 | 65654.99 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 475.70 | 0.00 | 01-JAN-00:10 | 169102.05 | 10-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 475.70 | 0.00 | 01-JAN-00:10 | 169102.05 | 10-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.95 | 0.00 | 01-JAN-00:10 | 11589.71 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.58 | 0.00 | 01-JAN-00:10 | 11589.71 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.58 | 0.00 | 01-JAN-00:10 | 11589.71 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.37 | 0.00 | 01-JAN-00:10 | 9337.52 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.37 | 0.00 | 01-JAN-00:10 | 9337.52 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.91 | 0.00 | 01-JAN-00:10 | 15448.44 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.49 | 0.00 | 01-JAN-00:10 | 12394.30 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.49 | 0.00 | 01-JAN-00:10 | 12394.30 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.42 | 0.00 | 01-JAN-00:10 | 15448.44 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.42 | 0.00 | 01-JAN-00:10 | 15448.44 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.98 | 0.00 | 01-JAN-00:10 | 25609.16 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.47 | 0.00 | 01-JAN-00:10 | 18479.29 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.47 | 0.00 | 01-JAN-00:10 | 18479.29 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.52 | 0.00 | 01-JAN-00:10 | 25609.16 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.52 | 0.00 | 01-JAN-00:10 | 25609.16 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.14 | 0.00 | 01-JAN-00:10 | 17513.29 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.59 | 0.00 | 01-JAN-00:10 | 11366.82 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.59 | 0.00 | 01-JAN-00:10 | 11366.82 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.55 | 0.00 | 01-JAN-00:10 | 17513.29 | 10-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.55 | 0.00 | 01-JAN-00:10 | 17513.29 | 10-AUG-16:40 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.86 | 0.00 | 01-JAN-00:10 | 8745.81 | 14-AUG-13:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.45 | 0.00 | 01-JAN-00:10 | 3699.42 | 19-FEB-12:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.45 | 0.00 | 01-JAN-00:10 | 3699.42 | 19-FEB-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 48.41 | 0.00 | 01-JAN-00:10 | 8745.81 | 14-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 48.41 | 0.00 | 01-JAN-00:10 | 8745.81 | 14-AUG-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 316.42 | 0.00 | 01-JAN-00:10 | 83374.83 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 64.15 | 0.00 | 01-JAN-00:10 | 83374.83 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 64.15 | 0.00 | 01-JAN-00:10 | 83374.83 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 252.28 | 0.00 | 01-JAN-00:10 | 66595.22 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 252.28 | 0.00 | 01-JAN-00:10 | 66595.22 | 10-AUG-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.04 | 0.00 | 01-JAN-00:10 | 20319.47 | 17-JAN-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.59 | 0.00 | 01-JAN-00:10 | 20319.47 | 17-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.59 | 0.00 | 01-JAN-00:10 | 20319.47 | 17-JAN-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.45 | 0.00 | 01-JAN-00:10 | 18474.35 | 10-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.45 | 0.00 | 01-JAN-00:10 | 18474.35 | 10-AUG-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.52 | 755.92 | 16-JAN-06:00 | 8689.36 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.52 | 755.92 | 16-JAN-06:00 | 8689.36 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.52 | 755.92 | 16-JAN-06:00 | 8689.36 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1201.24 | 5.32 | 07-JAN-22:20 | 81573.52 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.05 | 0.00 | 02-JAN-14:10 | 5480.18 | 01-JAN-19:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.05 | 0.00 | 02-JAN-14:10 | 5480.18 | 01-JAN-19:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1199.19 | 0.00 | 01-JAN-00:10 | 81573.52 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1199.19 | 0.00 | 01-JAN-00:10 | 81573.52 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.06 | 0.39 | 07-JAN-09:10 | 8356.47 | 06-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.75 | 0.00 | 02-JAN-16:40 | 608.87 | 08-JAN-17:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.75 | 0.00 | 02-JAN-16:40 | 608.87 | 08-JAN-17:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.31 | 0.00 | 01-JAN-00:10 | 8356.47 | 06-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.31 | 0.00 | 01-JAN-00:10 | 8356.47 | 06-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.68 | 86523.86 | 17-JAN-05:00 | 368286.52 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.68 | 86523.86 | 17-JAN-05:00 | 368286.52 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.68 | 86523.86 | 17-JAN-05:00 | 368286.52 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1261.17 | 0.00 | 01-JAN-00:10 | 1040787.00 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 5880.62 | 2490.45 | 01-JAN-07:30 | 2180703.68 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 828.07 | 0.00 | 01-JAN-00:10 | 1034592.08 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 828.07 | 0.00 | 01-JAN-00:10 | 1034592.08 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 828.07 | 0.00 | 01-JAN-00:10 | 1034592.08 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 5052.55 | 2188.33 | 03-JAN-08:00 | 2180703.68 | 29-AUG-14:30 |
EnergyTransfer:Plant | 9315.09 | 0.00 | 01-JAN-00:10 | 5296720.41 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 2567.16 | 0.00 | 01-JAN-00:10 | 1671997.13 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 820.57 | 0.00 | 01-JAN-00:10 | 1061145.29 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 2583.48 | 0.00 | 01-JAN-00:10 | 1669905.24 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 2910.77 | 0.00 | 01-JAN-00:10 | 1929238.95 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 2910.77 | 0.00 | 01-JAN-00:10 | 1929238.95 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -604.576 | 0.000 | 0.000 | 92.435 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -77.985 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -581.381 | 0.000 | 0.000 | 83.408 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 59.523 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 1.415 | -3924.355 | 0.000 | 0.000 | 843.314 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1304.868 |
CORE_TOP | 0.000 | 0.000 | 5.316 | -331.333 | 0.000 | 0.000 | 87.211 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -199.643 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -59.994 | 0.000 | 0.000 | 10.688 | 10.957 | 36.365 | 22.747 | 0.000 | 0.006 | 43.436 | 0.000 | -61.227 | 0.000 | -2.979 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.001 | -51.478 | 0.000 | 0.000 | 6.898 | 6.994 | 23.435 | 45.371 | 0.000 | 0.004 | 9.178 | 0.000 | -38.442 | 0.000 | -1.961 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.045 | -94.464 | 0.000 | 0.000 | 10.695 | 10.754 | 36.366 | 98.900 | 0.000 | 0.006 | 0.001 | 0.000 | -57.573 | 0.000 | -2.969 | -1.760 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -85.080 | 0.000 | 0.000 | 6.762 | 6.979 | 23.435 | 48.064 | 0.000 | 0.004 | 46.502 | 0.000 | -44.467 | 0.000 | -2.199 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 26.303 | -390.105 | 0.000 | 0.000 | 112.528 | 109.320 | 363.654 | 237.324 | 0.000 | 0.163 | 146.068 | 0.000 | -543.305 | 0.000 | -61.951 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 16.523 | -401.712 | 0.000 | 0.000 | 52.444 | 69.831 | 234.352 | 454.033 | 0.000 | 0.082 | 0.010 | 0.000 | -354.820 | 0.000 | -42.402 | -28.331 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 15.731 | -813.748 | 0.000 | 0.000 | 109.419 | 107.443 | 363.660 | 987.218 | 0.000 | 0.122 | 0.022 | 0.000 | -549.683 | 0.000 | -65.872 | -154.290 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.304 | -475.696 | 0.000 | 0.000 | 71.249 | 69.677 | 234.351 | 490.213 | 0.000 | 0.081 | 24.379 | 0.000 | -378.429 | 0.000 | -44.128 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 12.580 | -33.369 | 0.000 | 0.000 | 11.504 | 10.931 | 36.365 | 24.390 | 0.000 | 0.018 | 0.000 | 0.000 | -50.188 | 0.000 | -7.148 | -5.084 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.495 | -38.418 | 0.000 | 0.000 | 7.284 | 6.983 | 23.435 | 46.039 | 0.000 | 0.010 | 0.000 | 0.000 | -32.856 | 0.000 | -4.893 | -15.079 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.467 | -72.515 | 0.000 | 0.000 | 11.178 | 10.744 | 36.366 | 99.504 | 0.000 | 0.014 | 0.000 | 0.000 | -51.165 | 0.000 | -7.636 | -34.956 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.593 | -43.548 | 0.000 | 0.000 | 7.277 | 6.967 | 23.435 | 49.310 | 0.000 | 0.009 | 0.000 | 0.000 | -35.449 | 0.000 | -5.158 | -7.435 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.521 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.936 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.051 | -1199.184 | 0.000 | 0.000 | 9.503 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -387.439 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.746 | -109.314 | 0.000 | 0.000 | 0.952 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.891 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7166.682 | 0.000 | 0.000 | 20.565 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -396.351 |
GROUNDFLOOR_PLENUM | 1.446 | -48.410 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.010 | 53.283 | 0.000 | 0.000 | 0.000 | -6.329 | 0.000 |
MIDFLOOR_PLENUM | 64.150 | -252.275 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.199 | 295.017 | 0.000 | 0.000 | 0.000 | -107.092 | -0.006 |
TOPFLOOR_PLENUM | 26.592 | -38.446 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.011 | 23.064 | 0.000 | 0.000 | 0.000 | -11.221 | -0.002 |
Total Facility | 92.188 | -339.131 | 109.569 | -16615.475 | 0.000 | 0.000 | 1556.265 | 2470.476 | 14676.396 | 2603.112 | 0.000 | 0.741 | 700.484 | 0.000 | -2197.605 | 0.000 | -373.937 | -2683.062 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-SEP-06:11 | 0.00 | 0.00 | 0.00 | -108275.09 | 0.00 | 0.00 | 1492.95 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 88409.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 12-JUN-04:13 | 0.00 | 0.00 | 0.00 | -89812.27 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 83337.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-04:11 | 0.00 | 0.00 | 0.00 | -783309.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 718559.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 | -73205.49 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 66730.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-18:31 | 0.00 | 0.00 | 0.00 | -13931.17 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 5777.18 | 0.00 | 0.00 | 7583.55 | 0.00 | -0.00 | 0.00 | -32.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:31 | 0.00 | 0.00 | 0.00 | -24786.59 | 0.00 | 0.00 | 19.82 | 28.32 | 464.11 | 18968.83 | 0.00 | 0.00 | 5405.24 | 0.00 | -0.00 | 0.00 | -99.74 | 0.00 |
PERIMETER_BOT_ZN_1 | 08-OCT-13:01 | 0.00 | 0.00 | 0.00 | -33337.67 | 0.00 | 0.00 | 33.21 | 43.94 | 720.19 | 27509.35 | 0.00 | 0.00 | 5137.29 | 0.00 | -0.00 | 0.00 | -106.33 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-16:31 | 0.00 | 0.00 | 0.00 | -32409.84 | 0.00 | 0.00 | 13.87 | 28.32 | 464.11 | 21676.67 | 0.00 | 0.00 | 10280.98 | 0.00 | -0.00 | 0.00 | -54.11 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -84252.60 | 0.00 | 0.00 | 11143.86 | 7910.47 | 21605.52 | 63649.80 | 0.00 | 364.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20421.80 |
PERIMETER_MID_ZN_2 | 30-JUL-08:41 | 0.00 | 0.00 | 0.00 | -265566.51 | 0.00 | 0.00 | 186.36 | 283.19 | 4641.14 | 187029.32 | 0.00 | 0.00 | 74588.04 | 0.00 | -0.00 | 0.00 | -1161.54 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:41 | 0.00 | 0.00 | 0.00 | -346189.69 | 0.00 | 0.00 | 322.58 | 439.45 | 7201.95 | 223743.06 | 0.00 | 0.00 | 115212.01 | 0.00 | -0.00 | 0.00 | -729.36 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:11 | 0.00 | 0.00 | 0.00 | -292758.06 | 0.00 | 0.00 | 0.00 | 283.19 | 3603.49 | 203661.88 | 0.00 | 0.00 | 86415.89 | 0.00 | -0.00 | 0.00 | -1206.39 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -9337.32 | 0.00 | 0.00 | 1114.38 | 791.05 | 2160.55 | 6309.65 | 0.00 | 44.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1082.84 |
PERIMETER_TOP_ZN_2 | 06-AUG-10:01 | 0.00 | 0.00 | 0.00 | -24902.37 | 0.00 | 0.00 | 21.13 | 28.32 | 464.11 | 12532.70 | 0.00 | 0.00 | 12066.46 | 0.00 | -0.00 | 0.00 | -210.35 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-12:21 | 0.00 | 0.00 | 0.00 | -38300.81 | 0.00 | 0.00 | 28.71 | 43.94 | 720.19 | 28075.97 | 0.00 | 0.00 | 9665.70 | 0.00 | -0.00 | 0.00 | -233.72 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -30204.87 | 0.00 | 0.00 | 15.68 | 28.32 | 464.11 | 20832.50 | 0.00 | 0.00 | 9066.68 | 0.00 | -0.00 | 0.00 | -202.42 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:41 | 0.00 | 0.00 | 0.00 | -8697.08 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 885.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:35 | 0.00 | 0.00 | 0.00 | -81573.52 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 3453.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:30 | 0.00 | 0.00 | 0.00 | -8356.47 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 544.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | -368288.73 | 0.00 | 0.00 | 2183.01 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17683.99 |
GROUNDFLOOR_PLENUM | 14-AUG-05:15 | 0.00 | -10957.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10987.60 | 0.00 | -0.00 | 0.00 | -30.13 | 0.00 |
MIDFLOOR_PLENUM | 14-JAN-05:11 | 0.00 | -71686.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84485.78 | 0.00 | -0.00 | 0.00 | -12799.61 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:40 | 0.00 | -18475.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 | 18439.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-05:03 | 0.00 | -3853.27 | 0.00 | -1701343.98 | 0.00 | 0.00 | 15725.69 | 10593.62 | 616289.16 | 67981.12 | 0.00 | 0.00 | 1032213.46 | 0.00 | -35591.71 | 0.00 | -2014.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:11 | 0.00 | 0.00 | 324717.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -389466.99 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 70893.26 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -77368.24 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 09-JAN-06:01 | 0.00 | 0.00 | 2865.07 | 0.00 | 0.00 | 0.00 | 90.71 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3262.44 | 0.00 | -39.61 | -316.02 |
PERIMETER_BOT_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 10911.17 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3670.43 | 0.00 | -138.24 | -7915.55 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 108380.52 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21412.43 | 0.00 | -4624.64 | -90473.77 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 147436.88 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14110.88 | 0.00 | -3150.24 | -135415.24 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 211916.05 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21993.52 | 0.00 | -4762.55 | -193290.42 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 134600.95 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15834.95 | 0.00 | -3423.75 | -120581.70 |
PERIMETER_TOP_ZN_3 | 16-JAN-08:33 | 0.00 | 0.00 | 12639.26 | 0.00 | 0.00 | 0.00 | 88.24 | 68.62 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2619.47 | 0.00 | -682.34 | -10214.48 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 17388.60 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1250.11 | 0.00 | -372.78 | -16289.65 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 25756.96 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1928.52 | 0.00 | -558.10 | -24083.39 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 17458.48 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1341.50 | 0.00 | -380.69 | -16260.24 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-19:15 | 0.00 | 0.00 | 5480.40 | 0.00 | 0.00 | 0.00 | 0.00 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25142.37 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:30 | 0.00 | 0.00 | 608.88 | 0.00 | 0.00 | 0.00 | 5.58 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2580.66 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-04:01 | 11467.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -452.15 | -11015.03 |
MIDFLOOR_PLENUM | 30-JUL-16:01 | 129254.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -130590.58 |
TOPFLOOR_PLENUM | 17-JAN-05:23 | 23646.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -499.27 | -23146.98 |
Total Facility | 02-JAN-05:11 | -177627.79 | 177531.94 | 1077117.20 | -177531.94 | 0.00 | 0.00 | 0.00 | 10593.62 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90961.03 | 0.00 | -28475.81 | -1023071.41 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.8739 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.0167 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.3382 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 83.0698 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.4964 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3122 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1080 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1080 | 0.2350 | 1.0000 | Not calculated | 1.2002 | 0.2350 | ||
AIRLOOP DATACENTER BASEMENT | 24.7998 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.7999 | 0.0136 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.5042 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5042 | 0.0310 | 1.0000 | Not calculated | 0.0156 | 0.0310 | ||
AIRLOOP DATACENTER MID | 4.8421 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8421 | 0.0323 | 1.0000 | Not calculated | 0.1563 | 0.0323 | ||
AIRLOOP DATACENTER TOP | 0.4914 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4914 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4370 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2853 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.1691 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8288 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.2482 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2855 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.7998 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.7998 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.5042 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5042 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0310 | ||
AIRLOOP DATACENTER MID | 4.8421 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8421 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0323 | ||
AIRLOOP DATACENTER TOP | 0.4914 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4914 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.1080 | 5.1080 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4624 | 5.4624 | 1.6169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 51.1302 | 51.1302 | 16.1571 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9294 | 4.9294 | 1.6168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8326 | 0.8326 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2748 | 1.2748 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7703 | 1.7703 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5339 | 1.5339 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5871 | 7.5871 | 2.0333 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.3384 | 13.3384 | 1.3072 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.2695 | 18.2695 | 2.0279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0130 | 14.0130 | 1.3032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8539 | 0.8539 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3242 | 1.3242 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9231 | 1.9231 | 0.2038 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4658 | 1.4658 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5042 | 0.5042 | 0.5042 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8421 | 4.8421 | 4.8421 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4914 | 0.4914 | 0.4914 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.7998 | 24.7998 | 24.7998 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.8739 | 9.0167 | 10.8739 | 2.2853 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.3382 | 83.0698 | 104.3382 | 22.8288 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.4964 | 9.3122 | 10.4964 | 2.2855 | 0.0000 | 1.0000 |
CAV_BAS | 5.1080 | 5.1080 | 5.1080 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.7998 | 24.7999 | 24.7998 | 24.7998 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5042 | 0.5042 | 0.5042 | 0.5042 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8421 | 4.8421 | 4.8421 | 4.8421 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4914 | 0.4914 | 0.4914 | 0.4914 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7312 | 2.7312 | 1.6169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.5651 | 25.5651 | 16.1571 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4647 | 2.4647 | 1.6168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4163 | 0.4163 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6374 | 0.6374 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8851 | 0.8851 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7669 | 0.7669 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7935 | 3.7935 | 2.0333 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6692 | 6.6692 | 1.3072 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1348 | 9.1348 | 2.0279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0065 | 7.0065 | 1.3032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4270 | 0.4270 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6621 | 0.6621 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9616 | 0.9616 | 0.2038 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7329 | 0.7329 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5042 | 0.5042 | 0.5042 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8421 | 4.8421 | 4.8421 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4914 | 0.4914 | 0.4914 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.7998 | 24.7998 | 24.7998 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4370 | 2.2853 | 2.2853 | 2.2853 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.1691 | 22.8288 | 22.8288 | 22.8288 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.2482 | 2.2855 | 2.2855 | 2.2855 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.7998 | 24.7998 | 24.7998 | 24.7998 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5042 | 0.5042 | 0.5042 | 0.5042 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8421 | 4.8421 | 4.8421 | 4.8421 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4914 | 0.4914 | 0.4914 | 0.4914 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 15.50 |
Number of hours cooling loads not met | 503.50 |
Number of hours not met | 508.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1111.90 | 1281357.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 951.53 | 421316.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2470.48 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.44 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2311.71 | 277574.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 289.18 | 42585.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 293.39 | 72883.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1043.98 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 438.44 | 52005.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25397.81 |
Natural Gas | 0.00 | 1111.90 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 26509.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.33 |
Space Heating | 0.00 |
Space Cooling | 20.54 |
Fans (All) | 49.91 |
Service Water Heating | 9.47 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 548.31 |
Subtotal | 548.31 |
Natural Gas [MJ/m2] | |
Space Heating | 24.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 24.00 |
Subtotal | 24.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.32 |
Space Heating | 4.19 |
Space Cooling | 3.59 |
Fans (All) | 8.72 |
Service Water Heating | 1.65 |
Receptacle Equipment | 55.36 |
Miscellaneous | 17.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 767. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8292.83 | 467.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8721.50 | 38.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8721.50 | 38.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8448.00 | 312.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8732.17 | 27.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8697.50 | 62.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7885.17 | 874.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7850.17 | 909.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7830.33 | 929.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7355.33 | 1404.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
Min | 7355.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1404.67 | 0.00 | 0.00 | 0.00 |
Average | 8529.41 | 230.59 | 0.00 | 0.00 | 0.00 |
Sum | 196176.33 | 5303.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367136.00 | 1480.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330742.00 | 71.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1733.17 | 534.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1704.00 | 564.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1690.33 | 577.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 86139.83 | 17255.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367136.00 | 17255.17 | 0.00 | 0.00 | 0.00 |
Average | 79444.36 | 890.55 | 0.00 | 0.00 | 0.00 |
Sum | 1827220.33 | 20482.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8089.17 | 670.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8556.33 | 203.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8598.83 | 161.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8673.33 | 86.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8726.50 | 33.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8699.67 | 60.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8389.67 | 370.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8710.00 | 50.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8681.50 | 78.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8631.33 | 128.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8717.17 | 42.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8693.17 | 66.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8653.00 | 107.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8493.83 | 266.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8474.67 | 285.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8470.17 | 289.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7767.50 | 992.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8627.00 | 133.00 | 0.00 | 0.00 | 0.00 |
Min | 7767.50 | 3.83 | 0.00 | 0.00 | 0.00 |
Max | 8756.17 | 992.50 | 0.00 | 0.00 | 0.00 |
Average | 8581.93 | 178.07 | 0.00 | 0.00 | 0.00 |
Sum | 197384.33 | 4095.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 366490.17 | 2125.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330474.00 | 339.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330542.00 | 271.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330637.00 | 176.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2080.83 | 187.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2065.33 | 202.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2062.00 | 206.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 90989.17 | 12405.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366490.17 | 12405.83 | 0.00 | 0.00 | 0.00 |
Average | 79643.02 | 691.89 | 0.00 | 0.00 | 0.00 |
Sum | 1831789.50 | 15913.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418551E+11 | 99070.82 | 02-JAN-07:05 | 6.20 | 5.35 | 0.567818E+10 | 7499.22 | 11-JAN-14:09 | 14.40 | 10.49 |
February | 0.407121E+11 | 97020.67 | 28-FEB-07:11 | 10.60 | 9.82 | 0.515260E+10 | 7499.21 | 22-FEB-14:09 | 10.60 | 9.82 |
March | 0.518875E+11 | 96019.99 | 20-MAR-06:05 | 6.70 | 4.63 | 0.615349E+10 | 7499.28 | 31-MAR-13:09 | 8.98 | 7.53 |
April | 0.498482E+11 | 102046.60 | 03-APR-06:11 | 10.40 | 9.80 | 0.547080E+10 | 7499.30 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.514077E+11 | 104221.64 | 30-MAY-06:11 | 10.77 | 9.90 | 0.592495E+10 | 7499.32 | 05-MAY-09:09 | 10.77 | 9.90 |
June | 0.536825E+11 | 103391.10 | 05-JUN-06:11 | 11.30 | 9.68 | 0.590834E+10 | 7499.35 | 09-JUN-13:09 | 21.78 | 13.51 |
July | 0.540318E+11 | 103938.26 | 03-JUL-06:11 | 12.07 | 8.59 | 0.550097E+10 | 7566.75 | 31-JUL-09:30 | 22.75 | 17.29 |
August | 0.595172E+11 | 98693.28 | 07-AUG-06:11 | 13.60 | 12.49 | 0.616698E+10 | 7758.08 | 21-AUG-13:50 | 23.70 | 15.41 |
September | 0.515454E+11 | 108289.39 | 05-SEP-06:11 | 10.93 | 9.52 | 0.547850E+10 | 7522.70 | 11-SEP-15:20 | 23.30 | 15.94 |
October | 0.526268E+11 | 107636.21 | 10-OCT-06:11 | 12.03 | 10.85 | 0.569424E+10 | 7499.25 | 05-OCT-09:00 | 12.03 | 10.85 |
November | 0.499762E+11 | 105127.67 | 06-NOV-07:11 | 12.20 | 8.87 | 0.563526E+10 | 7499.22 | 02-NOV-09:20 | 12.20 | 8.87 |
December | 0.474900E+11 | 99735.73 | 26-DEC-07:03 | -1.6 | -1.6 | 0.548810E+10 | 7499.45 | 13-DEC-14:09 | -1.6 | -1.6 |
Annual Sum or Average | 0.604581E+12 | 0.682524E+11 | ||||||||
Minimum of Months | 0.407121E+11 | 96019.99 | -1.6 | -1.6 | 0.515260E+10 | 7499.21 | -1.6 | -1.6 | ||
Maximum of Months | 0.595172E+11 | 108289.39 | 13.60 | 12.49 | 0.616698E+10 | 7758.08 | 26.10 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334244E+11 | 81888.98 | 02-JAN-05:11 | 6.10 | 5.29 | 0.506114E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.355499E+11 | 81830.01 | 27-FEB-05:12 | 6.50 | 5.53 | 0.460115E+10 | 6734.80 | 08-FEB-10:20 | 6.50 | 5.53 |
March | 0.491668E+11 | 84394.40 | 13-MAR-04:11 | 6.30 | 5.39 | 0.550163E+10 | 6734.80 | 02-MAR-10:20 | 6.30 | 5.39 |
April | 0.526250E+11 | 85509.77 | 17-APR-04:12 | 6.10 | 5.14 | 0.488345E+10 | 6734.78 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.493511E+11 | 85886.66 | 01-MAY-04:12 | 12.20 | 10.35 | 0.528787E+10 | 6734.83 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.538781E+11 | 89813.94 | 12-JUN-04:13 | 14.80 | 13.61 | 0.527174E+10 | 6734.85 | 05-JUN-09:00 | 14.80 | 13.61 |
July | 0.595811E+11 | 87992.45 | 10-JUL-04:13 | 13.30 | 11.94 | 0.489752E+10 | 6734.77 | 18-JUL-09:20 | 17.43 | 12.11 |
August | 0.671640E+11 | 85104.43 | 22-AUG-04:12 | 12.00 | 10.91 | 0.549727E+10 | 6832.01 | 21-AUG-13:50 | 12.00 | 10.91 |
September | 0.473682E+11 | 89444.21 | 05-SEP-04:12 | 11.33 | 9.63 | 0.488638E+10 | 6734.82 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.469884E+11 | 89795.70 | 10-OCT-04:12 | 12.20 | 11.04 | 0.508019E+10 | 6734.77 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.438620E+11 | 87812.82 | 06-NOV-05:12 | 10.77 | 8.10 | 0.503081E+10 | 6734.76 | 02-NOV-09:20 | 10.77 | 8.10 |
December | 0.424227E+11 | 85213.59 | 04-DEC-05:12 | 3.70 | 1.47 | 0.490160E+10 | 6734.79 | 12-DEC-10:09 | 3.58 | 3.51 |
Annual Sum or Average | 0.581382E+12 | 0.609007E+11 | ||||||||
Minimum of Months | 0.334244E+11 | 81830.01 | 3.70 | 1.47 | 0.460115E+10 | 6734.76 | 3.58 | 2.79 | ||
Maximum of Months | 0.671640E+11 | 89813.94 | 14.80 | 13.61 | 0.550163E+10 | 6832.01 | 26.10 | 16.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208055E+11 | 23919.56 | 12-JAN-17:00 | 7.20 | 5.41 | 0.471405E+10 | 6734.59 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.223967E+11 | 67754.35 | 28-FEB-06:02 | 10.60 | 9.74 | 0.446716E+10 | 6734.77 | 08-FEB-10:20 | 10.60 | 9.74 |
March | 0.315615E+11 | 69520.65 | 03-MAR-06:02 | 6.60 | 6.18 | 0.545005E+10 | 6734.78 | 02-MAR-10:20 | 6.60 | 6.18 |
April | 0.325993E+11 | 74168.15 | 29-APR-05:02 | 8.40 | 8.40 | 0.485728E+10 | 6734.80 | 14-APR-09:20 | 8.40 | 8.40 |
May | 0.390245E+11 | 74452.72 | 01-MAY-04:12 | 12.20 | 10.35 | 0.527496E+10 | 6734.83 | 05-MAY-09:20 | 16.33 | 13.64 |
June | 0.411186E+11 | 76226.49 | 12-JUN-04:12 | 14.80 | 13.61 | 0.526377E+10 | 6734.82 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.417308E+11 | 76852.43 | 17-JUL-04:12 | 14.23 | 12.63 | 0.489252E+10 | 6734.82 | 14-JUL-09:20 | 14.23 | 12.63 |
August | 0.451830E+11 | 78340.42 | 28-AUG-04:11 | 15.40 | 14.02 | 0.549383E+10 | 6735.08 | 09-AUG-09:00 | 15.40 | 14.02 |
September | 0.374759E+11 | 74675.92 | 25-SEP-04:12 | 13.30 | 13.30 | 0.487507E+10 | 6734.81 | 14-SEP-09:09 | 13.30 | 13.30 |
October | 0.321627E+11 | 74001.68 | 06-OCT-05:02 | 11.10 | 10.49 | 0.504359E+10 | 6734.78 | 05-OCT-13:20 | 11.10 | 10.49 |
November | 0.256061E+11 | 69705.18 | 07-NOV-06:02 | 12.12 | 9.85 | 0.494130E+10 | 6734.75 | 02-NOV-09:20 | 12.12 | 9.85 |
December | 0.227722E+11 | 35889.06 | 07-DEC-06:02 | 4.27 | 2.78 | 0.470351E+10 | 6734.75 | 12-DEC-10:39 | 4.43 | 4.12 |
Annual Sum or Average | 0.392437E+12 | 0.599771E+11 | ||||||||
Minimum of Months | 0.208055E+11 | 23919.56 | 4.27 | 2.78 | 0.446716E+10 | 6734.59 | 4.43 | 4.12 | ||
Maximum of Months | 0.451830E+11 | 78340.42 | 15.40 | 14.02 | 0.549383E+10 | 6735.08 | 16.33 | 14.02 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150640E+11 | 16011.75 | 11-JAN-17:00 | 12.20 | 9.27 | 0.419091E+10 | 6482.97 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.163878E+11 | 27019.27 | 28-FEB-17:00 | 14.40 | 10.82 | 0.399943E+10 | 6734.55 | 28-FEB-14:20 | 14.40 | 10.82 |
March | 0.234678E+11 | 29864.23 | 15-MAR-16:00 | 11.10 | 7.72 | 0.513297E+10 | 6734.70 | 09-MAR-14:30 | 11.10 | 7.72 |
April | 0.270395E+11 | 68147.37 | 28-APR-05:03 | 11.10 | 9.92 | 0.472575E+10 | 6734.81 | 14-APR-09:20 | 11.10 | 9.92 |
May | 0.348787E+11 | 68071.81 | 05-MAY-05:03 | 12.98 | 10.75 | 0.522287E+10 | 6734.81 | 05-MAY-09:20 | 16.33 | 13.64 |
June | 0.392779E+11 | 73202.65 | 12-JUN-04:12 | 14.80 | 13.61 | 0.524443E+10 | 6734.82 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.412433E+11 | 71963.88 | 25-JUL-04:12 | 13.90 | 13.04 | 0.488243E+10 | 6734.81 | 11-JUL-09:20 | 13.90 | 13.04 |
August | 0.440780E+11 | 72360.26 | 11-AUG-04:12 | 12.73 | 11.87 | 0.548203E+10 | 6735.06 | 09-AUG-09:00 | 12.73 | 11.87 |
September | 0.324027E+11 | 68402.37 | 14-SEP-05:03 | 12.62 | 12.25 | 0.482424E+10 | 6734.79 | 14-SEP-09:20 | 17.57 | 15.54 |
October | 0.240163E+11 | 36504.72 | 04-OCT-15:40 | 21.30 | 11.43 | 0.483120E+10 | 6734.71 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.179276E+11 | 24028.13 | 02-NOV-16:00 | 13.30 | 10.88 | 0.445861E+10 | 6734.63 | 02-NOV-13:20 | 13.30 | 10.88 |
December | 0.155521E+11 | 16003.69 | 06-DEC-16:40 | 1.83 | 1.63 | 0.410282E+10 | 6540.01 | 06-DEC-14:00 | 1.83 | 1.63 |
Annual Sum or Average | 0.331336E+12 | 0.570977E+11 | ||||||||
Minimum of Months | 0.150640E+11 | 16003.69 | 1.83 | 1.63 | 0.399943E+10 | 6482.97 | 1.83 | 1.63 | ||
Maximum of Months | 0.440780E+11 | 73202.65 | 21.30 | 13.61 | 0.548203E+10 | 6735.06 | 17.57 | 15.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230301E+10 | 2361.79 | 12-JAN-06:02 | 6.70 | 6.36 | 0.566520E+09 | 845.61 | 11-JAN-14:20 | 6.70 | 6.36 |
February | 0.253117E+10 | 4659.47 | 27-FEB-15:30 | 19.70 | 12.30 | 0.538427E+09 | 845.62 | 27-FEB-10:20 | 19.70 | 12.30 |
March | 0.387843E+10 | 5152.91 | 20-MAR-13:40 | 12.03 | 7.87 | 0.674110E+09 | 845.63 | 09-MAR-14:09 | 12.03 | 7.87 |
April | 0.525674E+10 | 7448.05 | 27-APR-15:20 | 27.20 | 17.16 | 0.607467E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.605634E+10 | 7564.39 | 15-MAY-13:50 | 23.22 | 13.56 | 0.660076E+09 | 845.63 | 05-MAY-09:09 | 23.22 | 13.56 |
June | 0.734779E+10 | 11276.83 | 12-JUN-04:12 | 14.80 | 13.61 | 0.661043E+09 | 845.64 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.864739E+10 | 13930.80 | 23-JUL-18:31 | 24.97 | 15.79 | 0.614755E+09 | 845.89 | 20-JUL-13:00 | 24.97 | 15.79 |
August | 0.926285E+10 | 11059.87 | 14-AUG-05:03 | 15.37 | 13.48 | 0.689909E+09 | 873.67 | 21-AUG-13:50 | 23.70 | 15.41 |
September | 0.518543E+10 | 8438.61 | 11-SEP-15:25 | 23.30 | 15.99 | 0.609424E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.391926E+10 | 6103.68 | 10-OCT-05:03 | 12.20 | 11.22 | 0.626469E+09 | 845.63 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.300045E+10 | 4653.39 | 06-NOV-11:40 | 13.70 | 9.94 | 0.608797E+09 | 845.62 | 02-NOV-09:20 | 13.70 | 9.94 |
December | 0.260546E+10 | 2827.27 | 29-DEC-13:30 | 11.10 | 9.04 | 0.574722E+09 | 845.61 | 14-DEC-14:09 | 11.10 | 9.04 |
Annual Sum or Average | 0.599943E+11 | 0.743172E+10 | ||||||||
Minimum of Months | 0.230301E+10 | 2361.79 | 6.70 | 6.36 | 0.538427E+09 | 845.61 | 6.70 | 6.36 | ||
Maximum of Months | 0.926285E+10 | 13930.80 | 27.20 | 17.16 | 0.689909E+09 | 873.67 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147669E+10 | 2875.71 | 05-JAN-09:25 | 1.10 | 0.98 | 0.366136E+09 | 544.95 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.179174E+10 | 4907.61 | 08-FEB-09:45 | 1.93 | 0.91 | 0.349972E+09 | 544.96 | 08-FEB-10:20 | 2.77 | 1.67 |
March | 0.317120E+10 | 9407.21 | 14-MAR-08:55 | 7.80 | 5.89 | 0.434366E+09 | 544.96 | 02-MAR-10:09 | 7.80 | 5.89 |
April | 0.482082E+10 | 12502.73 | 27-APR-08:30 | 16.95 | 12.18 | 0.391567E+09 | 544.96 | 20-APR-09:00 | 16.95 | 12.18 |
May | 0.556990E+10 | 19910.37 | 14-MAY-08:32 | 15.93 | 11.13 | 0.425811E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.699524E+10 | 21475.11 | 25-JUN-08:32 | 16.33 | 11.87 | 0.426278E+09 | 545.14 | 19-JUN-09:09 | 16.33 | 11.87 |
July | 0.749962E+10 | 24785.51 | 23-JUL-08:31 | 18.53 | 13.73 | 0.396461E+09 | 546.43 | 31-JUL-09:50 | 23.12 | 17.56 |
August | 0.818461E+10 | 22548.21 | 13-AUG-08:42 | 20.67 | 15.77 | 0.444569E+09 | 549.95 | 21-AUG-13:50 | 23.70 | 15.41 |
September | 0.507691E+10 | 24016.70 | 10-SEP-08:31 | 15.53 | 13.26 | 0.393376E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.331585E+10 | 10348.54 | 04-OCT-08:50 | 15.32 | 10.37 | 0.403102E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.192636E+10 | 4415.06 | 15-NOV-09:10 | 6.78 | 5.27 | 0.387254E+09 | 544.95 | 15-NOV-10:20 | 7.40 | 5.77 |
December | 0.164887E+10 | 3847.66 | 05-DEC-10:00 | 6.70 | 5.10 | 0.359920E+09 | 544.95 | 12-DEC-10:09 | 3.58 | 3.51 |
Annual Sum or Average | 0.514778E+11 | 0.477881E+10 | ||||||||
Minimum of Months | 0.147669E+10 | 2875.71 | 1.10 | 0.91 | 0.349972E+09 | 544.95 | 2.77 | 1.67 | ||
Maximum of Months | 0.818461E+10 | 24785.51 | 20.67 | 15.77 | 0.444569E+09 | 549.95 | 23.70 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305049E+10 | 16607.66 | 20-JAN-13:05 | 6.70 | 4.72 | 0.569339E+09 | 845.64 | 11-JAN-14:09 | 6.70 | 4.72 |
February | 0.460753E+10 | 29406.20 | 12-FEB-11:53 | 5.60 | 0.67 | 0.544402E+09 | 846.84 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.743753E+10 | 20344.15 | 01-MAR-13:30 | 11.15 | 5.98 | 0.672616E+09 | 846.94 | 01-MAR-14:00 | 13.30 | 7.37 |
April | 0.882086E+10 | 23822.44 | 02-APR-14:02 | 19.18 | 11.40 | 0.606223E+09 | 846.62 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.872264E+10 | 30381.21 | 07-MAY-13:02 | 20.68 | 16.03 | 0.659112E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.933704E+10 | 21183.62 | 04-JUN-13:53 | 17.20 | 12.45 | 0.660901E+09 | 845.68 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.117040E+11 | 31021.73 | 23-JUL-13:52 | 27.80 | 16.97 | 0.615392E+09 | 846.64 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.137914E+11 | 30542.27 | 13-AUG-12:42 | 26.43 | 18.35 | 0.690513E+09 | 855.57 | 21-AUG-13:50 | 23.70 | 15.41 |
September | 0.104567E+11 | 32470.92 | 10-SEP-12:31 | 20.20 | 13.87 | 0.611034E+09 | 921.79 | 11-SEP-14:50 | 23.22 | 15.82 |
October | 0.809978E+10 | 33339.48 | 08-OCT-13:01 | 18.17 | 13.70 | 0.626028E+09 | 846.59 | 02-OCT-13:39 | 18.17 | 13.70 |
November | 0.430100E+10 | 21802.03 | 11-NOV-12:53 | 6.70 | 5.18 | 0.601793E+09 | 845.64 | 15-NOV-10:20 | 7.40 | 5.77 |
December | 0.413618E+10 | 28464.59 | 03-DEC-12:43 | 12.12 | 6.49 | 0.566916E+09 | 845.64 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.944651E+11 | 0.742427E+10 | ||||||||
Minimum of Months | 0.305049E+10 | 16607.66 | 5.60 | 0.67 | 0.544402E+09 | 845.64 | 6.70 | 4.72 | ||
Maximum of Months | 0.137914E+11 | 33339.48 | 27.80 | 18.35 | 0.690513E+09 | 921.79 | 28.30 | 18.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197699E+10 | 5663.89 | 05-JAN-15:30 | 6.40 | 4.89 | 0.393539E+09 | 544.95 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.314472E+10 | 13009.60 | 28-FEB-06:02 | 10.60 | 9.74 | 0.369301E+09 | 544.95 | 08-FEB-10:20 | 10.60 | 9.74 |
March | 0.616011E+10 | 15416.32 | 18-MAR-17:06 | 19.22 | 9.55 | 0.445112E+09 | 544.96 | 09-MAR-14:09 | 19.22 | 9.55 |
April | 0.893264E+10 | 26376.70 | 02-APR-15:22 | 20.60 | 11.92 | 0.396291E+09 | 544.96 | 27-APR-13:39 | 26.10 | 16.65 |
May | 0.786883E+10 | 30738.30 | 07-MAY-17:01 | 21.60 | 16.13 | 0.428336E+09 | 544.96 | 05-MAY-09:09 | 21.60 | 16.13 |
June | 0.954392E+10 | 27429.59 | 18-JUN-16:52 | 17.20 | 12.22 | 0.427570E+09 | 544.97 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.128026E+11 | 32410.13 | 23-JUL-16:31 | 27.07 | 15.77 | 0.398196E+09 | 544.97 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.138673E+11 | 28932.76 | 06-AUG-16:51 | 23.40 | 15.11 | 0.446536E+09 | 552.00 | 21-AUG-13:50 | 23.70 | 15.41 |
September | 0.720050E+10 | 30410.61 | 10-SEP-16:31 | 22.20 | 14.28 | 0.395941E+09 | 579.12 | 11-SEP-15:30 | 23.30 | 15.99 |
October | 0.537008E+10 | 22793.61 | 08-OCT-13:42 | 19.63 | 14.09 | 0.411109E+09 | 544.96 | 05-OCT-09:00 | 19.63 | 14.09 |
November | 0.413712E+10 | 14989.20 | 03-NOV-05:02 | 10.60 | 9.38 | 0.406697E+09 | 544.95 | 02-NOV-09:20 | 10.60 | 9.38 |
December | 0.407583E+10 | 15583.63 | 04-DEC-05:11 | 3.70 | 1.47 | 0.396225E+09 | 544.96 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.850806E+11 | 0.491485E+10 | ||||||||
Minimum of Months | 0.197699E+10 | 5663.89 | 3.70 | 1.47 | 0.369301E+09 | 544.95 | 7.10 | 5.11 | ||
Maximum of Months | 0.138673E+11 | 32410.13 | 27.07 | 16.13 | 0.446536E+09 | 579.12 | 26.10 | 16.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.786947E+09 | 1704.11 | 11-JAN-16:10 | 14.03 | 10.30 | 0.477348E+09 | 731.53 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.129029E+10 | 2174.24 | 28-FEB-15:00 | 13.90 | 10.81 | 0.457835E+09 | 845.60 | 28-FEB-14:50 | 13.90 | 10.81 |
March | 0.232465E+10 | 3020.62 | 10-MAR-14:30 | 16.40 | 11.76 | 0.602873E+09 | 845.60 | 10-MAR-14:20 | 16.40 | 11.76 |
April | 0.299634E+10 | 6066.39 | 27-APR-15:20 | 27.20 | 17.16 | 0.572809E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.460455E+10 | 6711.41 | 05-MAY-13:30 | 23.85 | 16.52 | 0.648262E+09 | 845.63 | 24-MAY-13:20 | 15.00 | 10.87 |
June | 0.551605E+10 | 7261.87 | 21-JUN-15:30 | 24.70 | 15.68 | 0.656316E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.618090E+10 | 8425.52 | 24-JUL-15:00 | 30.60 | 18.78 | 0.612007E+09 | 846.58 | 24-JUL-13:20 | 30.60 | 18.78 |
August | 0.625546E+10 | 7988.82 | 25-AUG-14:00 | 27.40 | 18.74 | 0.686120E+09 | 846.39 | 25-AUG-13:20 | 27.40 | 18.74 |
September | 0.391379E+10 | 6392.69 | 11-SEP-15:25 | 23.30 | 15.99 | 0.596569E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.254488E+10 | 3757.83 | 04-OCT-15:00 | 21.70 | 11.49 | 0.576121E+09 | 845.62 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.165190E+10 | 2159.53 | 04-NOV-05:03 | 12.80 | 11.49 | 0.514196E+09 | 817.88 | 02-NOV-13:00 | 12.80 | 11.49 |
December | 0.944945E+09 | 1617.01 | 29-DEC-16:10 | 10.40 | 8.63 | 0.466081E+09 | 706.34 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.390107E+11 | 0.686654E+10 | ||||||||
Minimum of Months | 0.786947E+09 | 1617.01 | 10.40 | 8.63 | 0.457835E+09 | 706.34 | 10.40 | 8.63 | ||
Maximum of Months | 0.625546E+10 | 8425.52 | 30.60 | 18.78 | 0.686120E+09 | 846.58 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433336E+09 | 1234.83 | 20-JAN-11:10 | 5.60 | 3.32 | 0.230249E+09 | 507.15 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.831160E+09 | 4339.39 | 27-FEB-11:05 | 14.37 | 10.03 | 0.230400E+09 | 548.49 | 08-FEB-11:09 | 14.37 | 10.03 |
March | 0.198074E+10 | 9490.76 | 14-MAR-10:05 | 10.28 | 7.92 | 0.301441E+09 | 548.50 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.362628E+10 | 13283.24 | 27-APR-10:05 | 19.27 | 13.13 | 0.282327E+09 | 548.50 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.483697E+10 | 23868.15 | 14-MAY-07:42 | 14.03 | 10.08 | 0.310187E+09 | 548.52 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.639220E+10 | 22909.34 | 25-JUN-08:52 | 16.70 | 12.03 | 0.313083E+09 | 548.51 | 07-JUN-10:09 | 16.70 | 12.03 |
July | 0.669825E+10 | 26560.55 | 30-JUL-08:41 | 20.22 | 15.61 | 0.292706E+09 | 548.51 | 07-JUL-12:09 | 20.22 | 15.61 |
August | 0.721439E+10 | 23971.41 | 13-AUG-09:22 | 21.80 | 16.25 | 0.327104E+09 | 552.48 | 09-AUG-10:09 | 21.80 | 16.25 |
September | 0.440432E+10 | 21784.99 | 10-SEP-08:42 | 15.82 | 13.36 | 0.286674E+09 | 548.50 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.229466E+10 | 10400.80 | 04-OCT-10:05 | 17.48 | 10.97 | 0.282811E+09 | 548.51 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.920139E+09 | 4878.95 | 04-NOV-10:05 | 16.38 | 13.96 | 0.252308E+09 | 548.49 | 15-NOV-11:09 | 7.88 | 5.98 |
December | 0.538531E+09 | 2821.23 | 05-DEC-11:05 | 8.58 | 5.53 | 0.228049E+09 | 546.04 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.401710E+11 | 0.333734E+10 | ||||||||
Minimum of Months | 0.433336E+09 | 1234.83 | 5.60 | 3.32 | 0.228049E+09 | 507.15 | 5.60 | 3.32 | ||
Maximum of Months | 0.721439E+10 | 26560.55 | 21.80 | 16.25 | 0.327104E+09 | 552.48 | 21.80 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205661E+10 | 16758.90 | 20-JAN-13:15 | 6.70 | 4.72 | 0.525391E+09 | 845.64 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.396335E+10 | 32118.37 | 12-FEB-12:22 | 5.85 | 0.79 | 0.512509E+09 | 846.31 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.649972E+10 | 21843.25 | 01-MAR-13:25 | 11.15 | 5.98 | 0.645068E+09 | 846.45 | 01-MAR-14:00 | 13.30 | 7.37 |
April | 0.724223E+10 | 22391.00 | 02-APR-13:43 | 18.90 | 11.23 | 0.591805E+09 | 847.17 | 25-APR-13:20 | 15.77 | 9.31 |
May | 0.799433E+10 | 32165.04 | 14-MAY-12:22 | 21.65 | 12.39 | 0.652021E+09 | 845.68 | 19-MAY-13:30 | 14.15 | 8.68 |
June | 0.816538E+10 | 31305.73 | 11-JUN-13:02 | 21.78 | 15.29 | 0.656696E+09 | 845.68 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.100185E+11 | 34619.12 | 30-JUL-12:41 | 26.10 | 17.66 | 0.613194E+09 | 847.32 | 31-JUL-13:20 | 27.57 | 18.47 |
August | 0.116869E+11 | 31833.92 | 13-AUG-12:42 | 26.43 | 18.35 | 0.688250E+09 | 847.60 | 09-AUG-13:20 | 26.43 | 18.35 |
September | 0.102696E+11 | 33320.92 | 10-SEP-12:42 | 20.40 | 13.99 | 0.606094E+09 | 942.56 | 11-SEP-14:00 | 23.30 | 15.83 |
October | 0.747151E+10 | 31841.22 | 08-OCT-13:12 | 18.53 | 13.81 | 0.606774E+09 | 863.42 | 04-OCT-13:20 | 18.53 | 13.81 |
November | 0.325673E+10 | 32146.31 | 11-NOV-14:02 | 7.80 | 5.52 | 0.560814E+09 | 845.66 | 02-NOV-13:39 | 7.80 | 5.52 |
December | 0.275073E+10 | 27290.38 | 03-DEC-13:32 | 12.20 | 6.14 | 0.519251E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.813756E+11 | 0.717787E+10 | ||||||||
Minimum of Months | 0.205661E+10 | 16758.90 | 5.85 | 0.79 | 0.512509E+09 | 845.64 | 6.78 | 4.76 | ||
Maximum of Months | 0.116869E+11 | 34619.12 | 26.43 | 18.35 | 0.688250E+09 | 942.56 | 27.57 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781327E+09 | 2270.37 | 05-JAN-15:40 | 6.30 | 4.80 | 0.320691E+09 | 541.90 | 05-JAN-14:00 | 6.30 | 4.80 |
February | 0.134172E+10 | 8463.46 | 27-FEB-15:30 | 19.70 | 12.30 | 0.314343E+09 | 544.94 | 06-FEB-14:30 | 19.70 | 12.30 |
March | 0.252192E+10 | 11118.87 | 14-MAR-16:00 | 17.20 | 10.94 | 0.406927E+09 | 544.95 | 09-MAR-14:30 | 17.20 | 10.94 |
April | 0.394024E+10 | 16104.51 | 01-APR-17:05 | 26.52 | 12.40 | 0.380287E+09 | 544.96 | 13-APR-13:20 | 16.87 | 9.00 |
May | 0.583034E+10 | 28424.58 | 07-MAY-17:01 | 21.60 | 16.13 | 0.421899E+09 | 544.96 | 24-MAY-13:20 | 15.00 | 10.87 |
June | 0.637875E+10 | 27594.89 | 18-JUN-17:11 | 17.03 | 12.24 | 0.424825E+09 | 544.97 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.846327E+10 | 29276.63 | 23-JUL-17:11 | 26.50 | 15.70 | 0.396664E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.804623E+10 | 25938.03 | 06-AUG-16:51 | 23.40 | 15.11 | 0.444554E+09 | 545.00 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.523710E+10 | 24850.86 | 10-SEP-16:42 | 22.20 | 14.22 | 0.390668E+09 | 585.90 | 11-SEP-15:30 | 23.30 | 15.99 |
October | 0.268406E+10 | 12266.31 | 04-OCT-16:00 | 21.10 | 11.40 | 0.384743E+09 | 544.95 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.136727E+10 | 6324.78 | 04-NOV-15:30 | 20.55 | 15.94 | 0.347850E+09 | 544.94 | 02-NOV-13:20 | 20.55 | 15.94 |
December | 0.978185E+09 | 3459.42 | 05-DEC-15:30 | 8.05 | 5.82 | 0.318453E+09 | 544.94 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.475704E+11 | 0.455190E+10 | ||||||||
Minimum of Months | 0.781327E+09 | 2270.37 | 6.30 | 4.80 | 0.314343E+09 | 541.90 | 6.30 | 4.80 | ||
Maximum of Months | 0.846327E+10 | 29276.63 | 26.52 | 16.13 | 0.444554E+09 | 585.90 | 24.70 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294665E+09 | 1555.76 | 11-JAN-16:20 | 13.67 | 10.10 | 0.465935E+09 | 684.35 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.681704E+09 | 1984.66 | 28-FEB-15:00 | 13.90 | 10.81 | 0.437084E+09 | 817.49 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.164808E+10 | 2485.22 | 10-MAR-14:40 | 16.30 | 11.68 | 0.558772E+09 | 845.60 | 10-MAR-14:20 | 16.30 | 11.68 |
April | 0.250059E+10 | 6632.66 | 27-APR-15:20 | 27.20 | 17.16 | 0.543944E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.417471E+10 | 7125.02 | 15-MAY-14:30 | 23.30 | 13.06 | 0.630558E+09 | 845.63 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.529522E+10 | 7862.29 | 21-JUN-15:30 | 24.70 | 15.68 | 0.648725E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.611745E+10 | 9337.52 | 24-JUL-15:00 | 30.60 | 18.78 | 0.608538E+09 | 845.63 | 20-JUL-13:09 | 30.60 | 18.78 |
August | 0.614117E+10 | 8520.46 | 09-AUG-14:40 | 28.17 | 18.42 | 0.680965E+09 | 845.67 | 09-AUG-09:00 | 28.17 | 18.42 |
September | 0.349295E+10 | 6206.50 | 12-SEP-14:40 | 24.40 | 16.65 | 0.576727E+09 | 845.63 | 14-SEP-09:20 | 17.57 | 15.54 |
October | 0.187884E+10 | 3537.12 | 04-OCT-15:20 | 21.50 | 11.47 | 0.534353E+09 | 845.61 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.857315E+09 | 1855.24 | 02-NOV-14:40 | 13.67 | 11.26 | 0.479650E+09 | 773.74 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.286665E+09 | 1476.00 | 29-DEC-16:10 | 10.40 | 8.63 | 0.449665E+09 | 663.94 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.333694E+11 | 0.661492E+10 | ||||||||
Minimum of Months | 0.286665E+09 | 1476.00 | 10.40 | 8.63 | 0.437084E+09 | 663.94 | 10.40 | 8.63 | ||
Maximum of Months | 0.614117E+10 | 9337.52 | 30.60 | 18.78 | 0.680965E+09 | 845.67 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281435E+09 | 1029.94 | 20-JAN-10:50 | 5.32 | 3.17 | 0.301755E+09 | 453.97 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.623717E+09 | 1555.13 | 27-FEB-15:40 | 19.60 | 12.34 | 0.295155E+09 | 544.93 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.164469E+10 | 6068.79 | 14-MAR-09:50 | 9.63 | 7.44 | 0.389043E+09 | 544.96 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.333103E+10 | 12271.57 | 27-APR-09:10 | 17.98 | 12.34 | 0.374488E+09 | 544.96 | 20-APR-09:00 | 17.98 | 12.34 |
May | 0.469342E+10 | 23801.52 | 14-MAY-10:12 | 19.47 | 12.42 | 0.415484E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.642183E+10 | 21615.52 | 25-JUN-09:12 | 17.07 | 12.34 | 0.423068E+09 | 544.97 | 09-JUN-13:09 | 17.07 | 12.34 |
July | 0.681900E+10 | 23677.64 | 30-JUL-08:52 | 20.60 | 15.79 | 0.394739E+09 | 545.86 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.739449E+10 | 24902.13 | 06-AUG-10:01 | 17.23 | 13.62 | 0.442500E+09 | 545.98 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.427072E+10 | 24060.84 | 10-SEP-09:02 | 16.28 | 13.48 | 0.381386E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.195462E+10 | 8426.86 | 04-OCT-09:20 | 16.13 | 10.66 | 0.365743E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.665532E+09 | 1596.96 | 04-NOV-10:10 | 16.38 | 13.96 | 0.315977E+09 | 538.60 | 02-NOV-13:00 | 16.38 | 13.96 |
December | 0.317660E+09 | 1101.42 | 05-DEC-10:40 | 7.77 | 5.32 | 0.293016E+09 | 474.82 | 05-DEC-10:50 | 8.03 | 5.37 |
Annual Sum or Average | 0.384182E+11 | 0.439236E+10 | ||||||||
Minimum of Months | 0.281435E+09 | 1029.94 | 5.32 | 3.17 | 0.293016E+09 | 453.97 | 5.60 | 3.25 | ||
Maximum of Months | 0.739449E+10 | 24902.13 | 20.60 | 15.79 | 0.442500E+09 | 545.98 | 23.30 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126098E+10 | 14891.81 | 20-JAN-13:25 | 6.70 | 4.72 | 0.501405E+09 | 845.63 | 11-JAN-14:39 | 6.70 | 4.72 |
February | 0.289544E+10 | 18535.84 | 27-FEB-14:20 | 18.87 | 11.68 | 0.486969E+09 | 845.64 | 08-FEB-10:20 | 18.87 | 11.68 |
March | 0.527316E+10 | 20677.40 | 01-MAR-13:40 | 11.33 | 6.09 | 0.612676E+09 | 846.23 | 01-MAR-14:50 | 13.03 | 7.20 |
April | 0.640291E+10 | 25267.72 | 02-APR-14:02 | 19.18 | 11.40 | 0.573249E+09 | 846.50 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.743211E+10 | 34532.53 | 14-MAY-13:32 | 22.60 | 12.25 | 0.638143E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.792154E+10 | 19762.41 | 11-JUN-15:13 | 22.43 | 15.08 | 0.649490E+09 | 845.67 | 09-JUN-13:09 | 22.43 | 15.08 |
July | 0.991476E+10 | 33424.43 | 30-JUL-13:32 | 26.50 | 17.71 | 0.609794E+09 | 846.52 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.116244E+11 | 36033.95 | 06-AUG-13:21 | 22.15 | 15.53 | 0.684123E+09 | 847.51 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.968034E+10 | 38298.05 | 10-SEP-12:21 | 20.00 | 13.75 | 0.593086E+09 | 907.79 | 11-SEP-14:50 | 23.22 | 15.82 |
October | 0.623772E+10 | 31519.92 | 08-OCT-13:12 | 18.53 | 13.81 | 0.578791E+09 | 846.12 | 04-OCT-13:00 | 18.53 | 13.81 |
November | 0.214570E+10 | 19320.28 | 11-NOV-13:12 | 7.07 | 5.29 | 0.522513E+09 | 845.64 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.172744E+10 | 14453.75 | 05-DEC-12:30 | 10.30 | 6.13 | 0.491746E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.725165E+11 | 0.694199E+10 | ||||||||
Minimum of Months | 0.126098E+10 | 14453.75 | 6.70 | 4.72 | 0.486969E+09 | 845.63 | 6.70 | 4.72 | ||
Maximum of Months | 0.116244E+11 | 38298.05 | 26.50 | 17.71 | 0.684123E+09 | 907.79 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436617E+09 | 1794.11 | 05-JAN-15:30 | 6.40 | 4.89 | 0.308736E+09 | 521.18 | 05-JAN-16:19 | 5.37 | 4.14 |
February | 0.911954E+09 | 7832.68 | 27-FEB-15:30 | 19.70 | 12.30 | 0.299141E+09 | 544.94 | 28-FEB-14:20 | 14.23 | 11.32 |
March | 0.203275E+10 | 10828.53 | 14-MAR-16:00 | 17.20 | 10.94 | 0.382276E+09 | 544.94 | 15-MAR-13:20 | 11.83 | 7.46 |
April | 0.354854E+10 | 18505.58 | 02-APR-15:22 | 20.60 | 11.92 | 0.365776E+09 | 544.96 | 27-APR-13:39 | 26.10 | 16.65 |
May | 0.550932E+10 | 29865.19 | 14-MAY-16:51 | 22.80 | 11.74 | 0.413709E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.622813E+10 | 28216.97 | 18-JUN-18:01 | 16.60 | 12.33 | 0.421404E+09 | 544.97 | 09-JUN-13:09 | 16.60 | 12.33 |
July | 0.837619E+10 | 27722.38 | 23-JUL-16:41 | 26.88 | 15.68 | 0.395517E+09 | 544.96 | 20-JUL-13:09 | 26.88 | 15.68 |
August | 0.798441E+10 | 30201.34 | 06-AUG-16:41 | 23.47 | 15.19 | 0.442796E+09 | 545.00 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.490915E+10 | 29096.56 | 10-SEP-16:21 | 22.20 | 14.33 | 0.382252E+09 | 562.68 | 11-SEP-15:30 | 23.30 | 15.99 |
October | 0.220872E+10 | 12211.92 | 04-OCT-16:00 | 21.10 | 11.40 | 0.362880E+09 | 544.95 | 19-OCT-13:20 | 13.50 | 10.13 |
November | 0.889182E+09 | 5762.47 | 04-NOV-15:30 | 20.55 | 15.94 | 0.323559E+09 | 544.93 | 08-NOV-14:00 | 9.40 | 8.82 |
December | 0.513985E+09 | 2469.43 | 05-DEC-15:30 | 8.05 | 5.82 | 0.301856E+09 | 544.92 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.435489E+11 | 0.439990E+10 | ||||||||
Minimum of Months | 0.436617E+09 | 1794.11 | 6.40 | 4.89 | 0.299141E+09 | 521.18 | 5.37 | 4.14 | ||
Maximum of Months | 0.837619E+10 | 30201.34 | 26.88 | 15.94 | 0.442796E+09 | 562.68 | 26.88 | 16.65 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436795E+09 | 2228.07 | 12-JAN-06:10 | 6.70 | 6.36 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 6.36 |
February | 0.110251E+10 | 4305.94 | 28-FEB-06:15 | 10.60 | 9.74 | 0.00 | 0.00 | 01-FEB-00:10 | 10.60 | 9.74 |
March | 0.303773E+10 | 4887.41 | 20-MAR-05:15 | 5.97 | 4.27 | 0.00 | 0.00 | 01-MAR-00:10 | 5.97 | 4.27 |
April | 0.453866E+10 | 6471.51 | 27-APR-14:40 | 26.83 | 17.14 | 0.00 | 0.00 | 01-APR-00:10 | 26.83 | 17.14 |
May | 0.484157E+10 | 7024.38 | 08-MAY-05:15 | 9.60 | 9.49 | 0.00 | 0.00 | 01-MAY-00:10 | 9.60 | 9.49 |
June | 0.628598E+10 | 10061.76 | 12-JUN-05:15 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.751801E+10 | 8438.91 | 31-JUL-14:10 | 28.30 | 18.91 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 18.91 |
August | 0.838199E+10 | 10957.68 | 14-AUG-05:15 | 15.33 | 13.50 | 0.00 | 0.00 | 01-AUG-00:10 | 15.33 | 13.50 |
September | 0.521757E+10 | 8940.36 | 05-SEP-05:15 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 10.77 | 9.27 |
October | 0.362047E+10 | 8414.68 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.16 |
November | 0.211266E+10 | 6703.56 | 06-NOV-06:15 | 11.47 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 11.47 | 8.44 |
December | 0.131594E+10 | 3630.88 | 04-DEC-06:08 | 3.22 | 1.95 | 0.00 | 0.00 | 01-DEC-00:10 | 3.22 | 1.95 |
Annual Sum or Average | 0.484099E+11 | 0.00 | ||||||||
Minimum of Months | 0.436795E+09 | 2228.07 | 3.22 | 1.95 | 0.00 | 0.00 | 3.22 | 1.95 | ||
Maximum of Months | 0.838199E+10 | 10957.68 | 28.30 | 18.91 | 0.00 | 0.00 | 28.30 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101352E+09 | 7168.64 | 14-JAN-05:11 | 2.20 | 1.37 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.37 |
February | 0.304998E+09 | 5813.95 | 18-FEB-05:01 | -1.2 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -2.4 |
March | 0.737667E+09 | 5389.17 | 06-MAR-06:02 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 6.18 |
April | 0.153526E+10 | 4290.57 | 27-APR-15:10 | 27.20 | 17.22 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 17.22 |
May | 0.288738E+10 | 4571.35 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.385906E+10 | 5162.88 | 28-JUN-15:30 | 26.10 | 15.92 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 15.92 |
July | 0.477803E+10 | 6225.20 | 31-JUL-14:20 | 28.30 | 18.91 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 18.91 |
August | 0.543812E+10 | 6659.52 | 10-AUG-15:00 | 30.20 | 18.90 | 0.00 | 0.00 | 01-AUG-00:10 | 30.20 | 18.90 |
September | 0.340344E+10 | 6072.74 | 11-SEP-15:35 | 23.30 | 16.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.04 |
October | 0.147191E+10 | 3745.80 | 04-OCT-15:40 | 21.30 | 11.43 | 0.00 | 0.00 | 01-OCT-00:10 | 21.30 | 11.43 |
November | 0.472427E+09 | 6584.49 | 13-NOV-06:01 | 1.70 | 1.50 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 1.50 |
December | 0.237939E+09 | 6754.66 | 26-DEC-05:01 | -0.6 | -0.6 | 0.00 | 0.00 | 01-DEC-00:10 | -0.6 | -0.6 |
Annual Sum or Average | 0.252276E+11 | 0.00 | ||||||||
Minimum of Months | 0.101352E+09 | 3745.80 | -1.2 | -2.4 | 0.00 | 0.00 | -1.2 | -2.4 | ||
Maximum of Months | 0.543812E+10 | 7168.64 | 30.20 | 18.91 | 0.00 | 0.00 | 30.20 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 75732614.91 | 2854.15 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.653198E+09 | 5649.95 | 14-MAR-15:00 | 16.10 | 10.31 | 0.00 | 0.00 | 01-MAR-00:10 | 16.10 | 10.31 |
April | 0.273604E+10 | 15301.62 | 27-APR-14:40 | 26.83 | 17.14 | 0.00 | 0.00 | 01-APR-00:10 | 26.83 | 17.14 |
May | 0.513722E+10 | 15930.39 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.684514E+10 | 16049.18 | 28-JUN-14:20 | 25.37 | 15.62 | 0.00 | 0.00 | 01-JUN-00:10 | 25.37 | 15.62 |
July | 0.891023E+10 | 17355.35 | 31-JUL-14:20 | 28.30 | 18.91 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 18.91 |
August | 0.862367E+10 | 18474.35 | 10-AUG-14:40 | 29.93 | 18.99 | 0.00 | 0.00 | 01-AUG-00:10 | 29.93 | 18.99 |
September | 0.434456E+10 | 14518.23 | 11-SEP-14:07 | 22.88 | 15.76 | 0.00 | 0.00 | 01-SEP-00:10 | 22.88 | 15.76 |
October | 0.106131E+10 | 8830.17 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 60016470.09 | 3125.58 | 04-NOV-14:10 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.384471E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.891023E+10 | 18474.35 | 29.93 | 18.99 | 0.00 | 0.00 | 29.93 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309244E+10 | 1947.92 | 05-JAN-16:10 | 5.73 | 4.38 | 95230010.77 | 126.82 | 19-JAN-14:09 | 5.40 | 2.91 |
February | 0.786249E+10 | 4033.73 | 07-FEB-16:50 | 7.30 | 3.84 | 86397220.64 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.142260E+11 | 7009.32 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.188705E+11 | 8154.66 | 26-APR-18:00 | 22.80 | 13.49 | 91605327.89 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.437997E+10 | 3446.05 | 31-MAY-24:00 | 13.00 | 10.11 | 99236075.69 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.928446E+10 | 5322.30 | 30-JUN-24:00 | 15.50 | 12.58 | 98960960.82 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.148138E+11 | 7270.17 | 31-JUL-24:00 | 17.40 | 14.08 | 91884493.15 | 126.84 | 11-JUL-09:09 | 17.40 | 14.08 |
August | 0.197736E+11 | 8697.08 | 06-AUG-18:41 | 22.13 | 15.01 | 0.103239E+09 | 126.83 | 02-AUG-09:00 | 22.13 | 15.01 |
September | 0.430041E+10 | 3332.13 | 30-SEP-24:00 | 14.30 | 12.32 | 91611881.20 | 126.84 | 13-SEP-13:00 | 14.30 | 12.32 |
October | 0.924846E+10 | 5051.92 | 31-OCT-24:00 | 9.10 | 7.85 | 95231783.80 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.136487E+11 | 5839.70 | 11-NOV-15:55 | 6.70 | 5.18 | 94301428.37 | 126.83 | 01-NOV-13:00 | 6.70 | 5.18 |
December | 0.190202E+11 | 7754.83 | 05-DEC-15:50 | 6.75 | 4.97 | 91880905.38 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.138521E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.309244E+10 | 1947.92 | 5.73 | 3.84 | 86397220.64 | 126.82 | 5.40 | 2.91 | ||
Maximum of Months | 0.197736E+11 | 8697.08 | 22.80 | 15.01 | 0.103239E+09 | 126.84 | 22.13 | 15.01 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.818758E+09 | 1538.25 | 05-JAN-16:20 | 5.37 | 4.14 | 95064891.44 | 126.82 | 09-JAN-10:09 | 2.57 | 1.11 |
February | 0.583989E+10 | 3705.58 | 07-FEB-17:00 | 7.20 | 3.36 | 86397173.31 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.124090E+11 | 6252.31 | 31-MAR-23:50 | 8.05 | 7.50 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.05 | 7.50 |
April | 0.173167E+11 | 7786.17 | 26-APR-18:00 | 22.80 | 13.49 | 91605377.00 | 126.83 | 28-APR-13:09 | 16.97 | 14.14 |
May | 0.367426E+10 | 3218.45 | 31-MAY-24:00 | 13.00 | 10.11 | 99235928.56 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.849034E+10 | 5001.88 | 30-JUN-24:00 | 15.50 | 12.58 | 98960733.63 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.139032E+11 | 6991.99 | 31-JUL-24:00 | 17.40 | 14.08 | 91884520.55 | 126.84 | 11-JUL-09:39 | 17.40 | 14.08 |
August | 0.186988E+11 | 8157.35 | 06-AUG-18:35 | 22.47 | 15.07 | 0.103240E+09 | 126.83 | 02-AUG-09:00 | 22.47 | 15.07 |
September | 0.363626E+10 | 2998.48 | 30-SEP-23:50 | 14.25 | 12.27 | 91611556.59 | 126.84 | 13-SEP-13:00 | 14.25 | 12.27 |
October | 0.781939E+10 | 4251.72 | 31-OCT-24:00 | 9.10 | 7.85 | 95231692.67 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.113896E+11 | 5328.70 | 10-NOV-16:10 | 8.53 | 6.27 | 94301330.22 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.159223E+11 | 7168.58 | 05-DEC-16:00 | 6.10 | 4.53 | 91880925.02 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.119919E+12 | 0.114265E+10 | ||||||||
Minimum of Months | 0.818758E+09 | 1538.25 | 5.37 | 3.36 | 86397173.31 | 126.82 | 2.57 | 1.11 | ||
Maximum of Months | 0.186988E+11 | 8157.35 | 22.80 | 15.07 | 0.103240E+09 | 126.84 | 22.47 | 15.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262574E+09 | 1398.62 | 05-JAN-16:20 | 5.37 | 4.14 | 93079403.06 | 127.95 | 10-JAN-10:30 | 6.95 | 3.86 |
February | 0.421815E+10 | 3580.71 | 08-FEB-17:00 | 6.70 | 3.26 | 86397292.98 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.110960E+11 | 5758.96 | 31-MAR-23:20 | 8.20 | 7.64 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.20 | 7.64 |
April | 0.165506E+11 | 7851.74 | 26-APR-18:00 | 22.80 | 13.49 | 91605401.05 | 126.83 | 28-APR-13:09 | 16.97 | 14.14 |
May | 0.318054E+10 | 3130.34 | 31-MAY-23:30 | 13.50 | 10.66 | 99235927.59 | 126.84 | 31-MAY-13:00 | 13.50 | 10.66 |
June | 0.826932E+10 | 4910.45 | 30-JUN-23:40 | 15.63 | 12.81 | 98960766.18 | 126.84 | 12-JUN-13:00 | 15.63 | 12.81 |
July | 0.137735E+11 | 6956.94 | 31-JUL-24:00 | 17.40 | 14.08 | 91884613.63 | 126.84 | 11-JUL-09:39 | 17.40 | 14.08 |
August | 0.185509E+11 | 8356.47 | 06-AUG-18:30 | 22.80 | 15.13 | 0.103240E+09 | 126.83 | 02-AUG-09:00 | 22.80 | 15.13 |
September | 0.313320E+10 | 2595.43 | 30-SEP-23:20 | 14.10 | 12.13 | 91611242.57 | 126.84 | 13-SEP-13:00 | 14.10 | 12.13 |
October | 0.664148E+10 | 4162.74 | 04-OCT-16:50 | 20.68 | 11.37 | 95231648.87 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.969801E+10 | 5215.44 | 04-NOV-16:02 | 19.82 | 15.68 | 94301342.21 | 126.83 | 01-NOV-13:00 | 19.82 | 15.68 |
December | 0.139400E+11 | 6971.48 | 05-DEC-16:00 | 6.10 | 4.53 | 91880939.65 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.109314E+12 | 0.114066E+10 | ||||||||
Minimum of Months | 0.262574E+09 | 1398.62 | 5.37 | 3.26 | 86397292.98 | 126.82 | 6.95 | 3.86 | ||
Maximum of Months | 0.185509E+11 | 8356.47 | 22.80 | 15.68 | 0.103240E+09 | 127.95 | 22.80 | 15.68 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236639E+12 | 91053.20 | 12-JAN-17:00 | 7.20 | 5.41 | 0.206144E+10 | 2745.29 | 09-JAN-14:00 | 7.20 | 5.41 |
February | 0.435158E+12 | 183297.66 | 27-FEB-17:00 | 18.90 | 12.17 | 0.187022E+10 | 2745.79 | 22-FEB-14:39 | 18.90 | 12.17 |
March | 0.729110E+12 | 358391.21 | 31-MAR-24:00 | 8.00 | 7.45 | 0.223480E+10 | 2747.22 | 10-MAR-14:00 | 8.00 | 7.45 |
April | 0.943176E+12 | 367369.74 | 27-APR-16:00 | 27.20 | 16.90 | 0.198320E+10 | 2750.82 | 28-APR-13:39 | 17.77 | 13.44 |
May | 0.240803E+12 | 176106.82 | 31-MAY-24:00 | 13.00 | 10.11 | 0.214809E+10 | 2746.25 | 05-MAY-13:00 | 13.00 | 10.11 |
June | 0.470149E+12 | 267641.67 | 30-JUN-24:00 | 15.50 | 12.58 | 0.214219E+10 | 2746.93 | 19-JUN-13:39 | 15.50 | 12.58 |
July | 0.732173E+12 | 360243.33 | 31-JUL-24:00 | 17.40 | 14.08 | 0.198995E+10 | 2750.45 | 11-JUL-13:09 | 17.40 | 14.08 |
August | 0.977459E+12 | 368286.52 | 14-AUG-16:00 | 27.50 | 16.95 | 0.223707E+10 | 2751.89 | 30-AUG-09:09 | 19.33 | 17.24 |
September | 0.234656E+12 | 175662.23 | 30-SEP-24:00 | 14.30 | 12.32 | 0.198297E+10 | 2746.42 | 14-SEP-13:00 | 14.30 | 12.32 |
October | 0.485787E+12 | 267221.64 | 31-OCT-24:00 | 9.10 | 7.85 | 0.206144E+10 | 2746.60 | 02-OCT-13:20 | 9.10 | 7.85 |
November | 0.706788E+12 | 275762.42 | 06-NOV-17:00 | 11.70 | 10.80 | 0.204134E+10 | 2747.84 | 17-NOV-14:30 | 10.30 | 8.83 |
December | 0.974784E+12 | 367135.29 | 04-DEC-17:00 | 6.70 | 4.39 | 0.198900E+10 | 2747.14 | 28-DEC-10:09 | 10.10 | 8.95 |
Annual Sum or Average | 0.716668E+13 | 0.247417E+11 | ||||||||
Minimum of Months | 0.234656E+12 | 91053.20 | 6.70 | 4.39 | 0.187022E+10 | 2745.29 | 7.20 | 5.41 | ||
Maximum of Months | 0.977459E+12 | 368286.52 | 27.50 | 16.95 | 0.223707E+10 | 2751.89 | 19.33 | 17.24 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141249E+09 | 32478.14 | 02-JAN-05:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 301710.29 | 2514.25 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 0.141551E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.141249E+09 | 32478.14 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237230E+10 | 70893.35 | 02-JAN-05:11 | 6.10 |
February | 0.913900E+09 | 67356.87 | 21-FEB-04:51 | 1.70 |
March | 0.166823E+09 | 61382.50 | 06-MAR-05:11 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 18943305.46 | 42834.02 | 30-OCT-05:03 | 7.20 |
November | 0.578207E+09 | 63617.27 | 13-NOV-05:01 | 1.20 |
December | 0.126581E+10 | 68935.49 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.531599E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.237230E+10 | 70893.35 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 735708.93 | 2865.07 | 09-JAN-06:01 | -1.5 |
February | 44034.49 | 513.74 | 18-FEB-06:01 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 779743.42 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 735708.93 | 2865.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35328936.23 | 10911.09 | 17-JAN-05:01 | 1.60 |
February | 4848860.87 | 7787.02 | 18-FEB-06:01 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 4718770.39 | 7652.66 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 44896567.49 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 35328936.23 | 10911.09 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124142E+10 | 10838.06 | 02-JAN-05:11 | 6.10 |
February | 0.458056E+09 | 10036.73 | 21-FEB-05:01 | 1.70 |
March | 53516804.95 | 9241.83 | 06-MAR-05:11 | 6.70 |
April | 2339376.16 | 4897.74 | 19-APR-05:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 6739550.26 | 8683.39 | 30-OCT-05:03 | 7.20 |
November | 0.174711E+09 | 9342.65 | 24-NOV-05:11 | 2.60 |
December | 0.693564E+09 | 10280.80 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.263034E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.124142E+10 | 10838.06 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765154E+09 | 14743.71 | 02-JAN-05:11 | 6.10 |
February | 0.261691E+09 | 13124.04 | 21-FEB-05:01 | 1.70 |
March | 26244604.76 | 11836.14 | 06-MAR-05:11 | 6.70 |
April | 1721938.51 | 2903.80 | 19-APR-05:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 3130788.36 | 4156.50 | 31-OCT-05:03 | 8.58 |
November | 0.120134E+09 | 12102.85 | 24-NOV-05:11 | 2.60 |
December | 0.474178E+09 | 13131.10 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.165225E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.765154E+09 | 14743.71 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.768376E+09 | 21191.64 | 02-JAN-05:11 | 6.10 |
February | 0.205853E+09 | 18072.01 | 21-FEB-05:01 | 1.70 |
March | 16741387.19 | 16606.95 | 06-MAR-06:02 | 6.70 |
April | 274826.83 | 1811.79 | 18-APR-05:03 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 315551.61 | 2103.68 | 28-OCT-05:03 | 8.22 |
November | 0.105752E+09 | 17339.83 | 24-NOV-05:11 | 2.60 |
December | 0.475779E+09 | 19115.54 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.157309E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.768376E+09 | 21191.64 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443677E+09 | 13460.12 | 02-JAN-05:11 | 6.10 |
February | 0.131070E+09 | 11677.97 | 21-FEB-05:01 | 1.70 |
March | 5265128.82 | 10309.18 | 06-MAR-06:02 | 6.70 |
April | 3170.03 | 21.13 | 19-APR-05:05 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 44425988.40 | 10670.21 | 13-NOV-06:01 | 1.70 |
December | 0.205928E+09 | 12417.70 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.830370E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.443677E+09 | 13460.12 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406247E+10 | 12639.24 | 16-JAN-08:33 | -0.8 |
February | 0.234485E+10 | 12608.49 | 20-FEB-05:43 | -0.6 |
March | 0.806999E+09 | 12215.82 | 06-MAR-05:11 | 6.70 |
April | 0.220335E+09 | 10522.66 | 18-APR-04:12 | 2.97 |
May | 11133502.89 | 10104.44 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 5304347.25 | 6431.40 | 27-SEP-05:03 | 7.38 |
October | 0.327166E+09 | 11191.70 | 30-OCT-04:11 | 7.20 |
November | 0.152360E+10 | 12457.77 | 13-NOV-04:01 | 1.60 |
December | 0.327768E+10 | 12614.67 | 26-DEC-03:43 | -0.9 |
Annual Sum or Average | 0.125795E+11 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.406247E+10 | 12639.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249681E+10 | 17388.48 | 02-JAN-05:11 | 6.10 |
February | 0.128657E+10 | 17041.77 | 13-FEB-04:11 | 0.77 |
March | 0.425873E+09 | 16955.27 | 06-MAR-05:11 | 6.70 |
April | 0.109017E+09 | 13442.66 | 01-APR-05:02 | 7.38 |
May | 7945624.37 | 13457.29 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 3434248.91 | 5303.33 | 27-SEP-05:03 | 7.38 |
October | 0.194789E+09 | 14819.15 | 30-OCT-04:11 | 7.20 |
November | 0.937688E+09 | 17104.05 | 13-NOV-04:01 | 1.60 |
December | 0.203257E+10 | 17026.31 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.749470E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.77 | |
Maximum of Months | 0.249681E+10 | 17388.48 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280327E+10 | 25756.80 | 02-JAN-05:11 | 6.10 |
February | 0.134193E+10 | 25058.59 | 21-FEB-04:51 | 1.70 |
March | 0.511113E+09 | 24870.86 | 06-MAR-05:11 | 6.70 |
April | 0.157612E+09 | 19972.76 | 01-APR-05:02 | 7.38 |
May | 12427638.19 | 20072.77 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 1602942.04 | 4091.56 | 27-SEP-05:03 | 7.38 |
October | 0.193806E+09 | 21520.69 | 16-OCT-04:12 | 7.20 |
November | 0.107114E+10 | 24921.39 | 24-NOV-05:11 | 2.60 |
December | 0.237416E+10 | 25235.51 | 18-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.846706E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.280327E+10 | 25756.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171537E+10 | 17458.34 | 02-JAN-05:11 | 6.10 |
February | 0.770106E+09 | 16978.39 | 21-FEB-04:51 | 1.70 |
March | 0.246434E+09 | 16006.43 | 06-MAR-05:11 | 6.70 |
April | 51111697.13 | 11422.89 | 01-APR-05:02 | 7.38 |
May | 3914574.61 | 10516.30 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 81310269.58 | 10816.46 | 23-OCT-05:02 | 10.60 |
November | 0.529240E+09 | 16128.85 | 24-NOV-05:11 | 2.60 |
December | 0.119551E+10 | 17097.70 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.459299E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.171537E+10 | 17458.34 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324628E+09 | 10480.22 | 02-JAN-05:11 | 6.10 |
February | 0.117950E+09 | 9285.52 | 06-FEB-05:11 | 4.23 |
March | 82300533.85 | 10211.78 | 06-MAR-05:11 | 6.70 |
April | 0.140205E+09 | 11343.89 | 10-APR-04:12 | 9.63 |
May | 93545833.58 | 10044.85 | 14-MAY-14:32 | 23.13 |
June | 83254746.70 | 7862.96 | 26-JUN-04:12 | 12.80 |
July | 0.136086E+09 | 11426.80 | 23-JUL-15:51 | 27.80 |
August | 0.117312E+09 | 10740.70 | 06-AUG-15:31 | 23.77 |
September | 64761931.71 | 10717.59 | 10-SEP-14:31 | 22.60 |
October | 0.107591E+09 | 10065.82 | 08-OCT-13:42 | 19.63 |
November | 91869293.83 | 11219.01 | 27-NOV-05:11 | 12.03 |
December | 86698279.09 | 11462.87 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.144620E+10 | |||
Minimum of Months | 64761931.71 | 7862.96 | -1.0 | |
Maximum of Months | 0.324628E+09 | 11462.87 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220670E+10 | 9163.81 | 02-JAN-06:10 | 6.10 |
February | 0.118316E+10 | 11629.78 | 12-FEB-11:43 | 5.60 |
March | 0.343383E+09 | 6165.86 | 29-MAR-05:02 | 4.40 |
April | 70307726.00 | 8035.36 | 02-APR-15:02 | 20.60 |
May | 77322100.43 | 12359.02 | 14-MAY-15:01 | 23.30 |
June | 57711623.25 | 6619.62 | 25-JUN-16:12 | 21.70 |
July | 73943878.79 | 12925.64 | 30-JUL-16:01 | 27.62 |
August | 54308237.59 | 11265.02 | 06-AUG-15:31 | 23.77 |
September | 50498304.03 | 11312.28 | 10-SEP-14:42 | 22.70 |
October | 0.161038E+09 | 8724.94 | 29-OCT-14:23 | 11.70 |
November | 0.754755E+09 | 9403.78 | 11-NOV-12:42 | 6.42 |
December | 0.138169E+10 | 10284.13 | 03-DEC-13:32 | 12.20 |
Annual Sum or Average | 0.641481E+10 | |||
Minimum of Months | 50498304.03 | 6165.86 | 4.40 | |
Maximum of Months | 0.220670E+10 | 12925.64 | 27.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643962E+10 | 23646.26 | 17-JAN-05:23 | 1.40 |
February | 0.403755E+10 | 20222.41 | 21-FEB-06:13 | 1.70 |
March | 0.240894E+10 | 12610.03 | 06-MAR-06:02 | 6.70 |
April | 0.118135E+10 | 11795.15 | 27-APR-05:03 | 9.37 |
May | 0.623751E+09 | 12715.62 | 04-MAY-05:02 | 10.78 |
June | 0.313184E+09 | 12944.40 | 02-JUN-05:03 | 10.18 |
July | 0.182191E+09 | 11745.40 | 18-JUL-05:03 | 12.80 |
August | 0.232286E+09 | 11847.22 | 21-AUG-05:03 | 11.20 |
September | 0.613621E+09 | 12366.29 | 08-SEP-05:02 | 10.18 |
October | 0.168044E+10 | 9824.95 | 05-OCT-05:03 | 8.30 |
November | 0.338969E+10 | 16628.98 | 13-NOV-06:13 | 1.70 |
December | 0.548872E+10 | 21895.92 | 26-DEC-05:12 | -0.6 |
Annual Sum or Average | 0.265914E+11 | |||
Minimum of Months | 0.182191E+09 | 9824.95 | -0.6 | |
Maximum of Months | 0.643962E+10 | 23646.26 | 12.80 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205091E+09 | 548.04 | 01-JAN-19:15 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.205091E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.205091E+09 | 548.04 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.732074E+09 | 608.87 | 08-JAN-17:30 | 2.75 |
February | 13755665.80 | 415.39 | 19-FEB-06:43 | -5.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.745829E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.732074E+09 | 608.87 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107059E+10 | 1662.56 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.875263E+09 | 1500.21 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.957407E+09 | 1306.38 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.811478E+09 | 927.82 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.854166E+09 | 852.96 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.835677E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785076E+09 | 917.45 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.886656E+09 | 908.20 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.837440E+09 | 1317.30 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.935264E+09 | 1640.38 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.103462E+10 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.107335E+10 | 1662.56 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.109570E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785076E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.107335E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.670623E+09 | 1071.42 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.557062E+09 | 978.00 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.614091E+09 | 802.58 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.523113E+09 | 570.29 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.552959E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.541511E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.508427E+09 | 545.08 | 12-JUL-08:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.573871E+09 | 567.93 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.535949E+09 | 812.37 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.594990E+09 | 1053.47 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.653254E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.668274E+09 | 1071.42 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.699412E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.508427E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.670623E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101677E+10 | 1662.60 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.847322E+09 | 1461.58 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.947774E+09 | 1290.29 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.812166E+09 | 924.57 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.857820E+09 | 854.69 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.839761E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.791287E+09 | 909.06 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.891944E+09 | 906.16 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.833442E+09 | 1305.23 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.914087E+09 | 1636.19 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.992688E+09 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.100932E+10 | 1662.60 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.107544E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.791287E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.101677E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.670014E+09 | 1071.42 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.552020E+09 | 940.18 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.613707E+09 | 856.72 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.522797E+09 | 718.61 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.550887E+09 | 566.83 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.538594E+09 | 556.42 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507891E+09 | 742.06 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.571974E+09 | 729.21 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.538941E+09 | 862.04 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.595275E+09 | 1057.46 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.649974E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.667421E+09 | 1071.42 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.697949E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507891E+09 | 556.42 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.670014E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106639E+10 | 1662.56 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.872514E+09 | 1498.31 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.955370E+09 | 1302.48 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.810755E+09 | 922.45 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.853746E+09 | 843.30 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.835046E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.784186E+09 | 911.38 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.885875E+09 | 901.66 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.835943E+09 | 1313.48 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.932711E+09 | 1640.12 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.103026E+10 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.106921E+10 | 1662.56 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.109320E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.784186E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.106921E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668928E+09 | 1071.42 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.555876E+09 | 975.61 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.613022E+09 | 796.55 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.522684E+09 | 566.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.552553E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.541160E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.508155E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.573443E+09 | 563.39 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.535449E+09 | 806.55 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.593880E+09 | 1053.08 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.651506E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.666438E+09 | 1071.42 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.698309E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.508155E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.668928E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101555E+10 | 1662.60 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.846317E+09 | 1459.28 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.946796E+09 | 1286.31 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.811608E+09 | 919.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.857211E+09 | 845.11 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.839358E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.790687E+09 | 902.62 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.891179E+09 | 899.52 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.832730E+09 | 1301.33 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.913071E+09 | 1635.93 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.991647E+09 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.100817E+10 | 1662.60 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.107443E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.790687E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.101555E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668204E+09 | 1071.42 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.551031E+09 | 936.80 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612560E+09 | 851.14 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.522241E+09 | 709.30 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.550481E+09 | 561.71 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.538196E+09 | 550.71 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507388E+09 | 732.72 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.571503E+09 | 719.64 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.538300E+09 | 856.59 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.594240E+09 | 1057.10 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.647998E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.665537E+09 | 1071.42 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.696768E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507388E+09 | 550.71 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.668204E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106618E+10 | 1662.56 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.872394E+09 | 1498.00 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.955230E+09 | 1301.75 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.810714E+09 | 922.24 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.853727E+09 | 842.92 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.835018E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.784167E+09 | 911.15 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.885817E+09 | 901.39 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.835908E+09 | 1312.77 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.932626E+09 | 1640.08 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.103005E+10 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.106891E+10 | 1662.56 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.109307E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.784167E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.106891E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668825E+09 | 1071.42 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.555832E+09 | 975.43 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.612974E+09 | 796.04 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.522708E+09 | 566.11 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.552539E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.541143E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.508150E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.573431E+09 | 563.18 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.535448E+09 | 806.05 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.593959E+09 | 1053.04 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.651400E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.666355E+09 | 1071.42 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.698276E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.508150E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.668825E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101545E+10 | 1662.60 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.846278E+09 | 1458.92 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.946743E+09 | 1285.56 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.811558E+09 | 918.82 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.857185E+09 | 844.73 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.839339E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.790670E+09 | 902.37 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.891155E+09 | 899.25 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.832697E+09 | 1300.60 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.913020E+09 | 1635.88 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.991583E+09 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.100806E+10 | 1662.60 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.107437E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.790670E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.101545E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668040E+09 | 1071.42 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.550979E+09 | 936.53 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612494E+09 | 850.69 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.522225E+09 | 708.59 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.550463E+09 | 561.51 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.538187E+09 | 550.49 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507318E+09 | 732.12 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.571491E+09 | 719.17 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.538274E+09 | 856.15 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.594182E+09 | 1057.07 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.647902E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.665300E+09 | 1071.42 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.696685E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507318E+09 | 550.49 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.668040E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.107059E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367566E+09 |
February | 0.136985E+10 | 0.875263E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327767E+09 |
March | 0.163685E+10 | 0.957407E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315011E+09 |
April | 0.145243E+10 | 0.811478E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 404540.49 | 0.297434E+09 |
May | 0.157338E+10 | 0.854166E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17302.75 | 0.227485E+09 |
June | 0.156900E+10 | 0.835677E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173865.07 | 0.188766E+09 |
July | 0.145680E+10 | 0.785076E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2044530.23 | 0.155760E+09 |
August | 0.163685E+10 | 0.886656E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3655159.61 | 0.125142E+09 |
September | 0.145243E+10 | 0.837440E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17241.75 | 0.106193E+09 |
October | 0.150991E+10 | 0.935264E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252763E+09 |
November | 0.149516E+10 | 0.103462E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293863E+09 |
December | 0.145680E+10 | 0.107335E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320781E+09 |
Annual Sum or Average | 0.181194E+11 | 0.109570E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6312639.89 | 0.297853E+10 |
Minimum of Months | 0.136985E+10 | 0.785076E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106193E+09 |
Maximum of Months | 0.163685E+10 | 0.107335E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3655159.61 | 0.367566E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.670623E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242376E+09 |
February | 0.882782E+09 | 0.557062E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217660E+09 |
March | 0.105485E+10 | 0.614091E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206786E+09 |
April | 0.936002E+09 | 0.523113E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 268858.67 | 0.195211E+09 |
May | 0.101394E+10 | 0.552959E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11534.73 | 0.152460E+09 |
June | 0.101113E+10 | 0.541511E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115907.67 | 0.126089E+09 |
July | 0.938820E+09 | 0.508427E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1084637.59 | 0.102534E+09 |
August | 0.105485E+10 | 0.573871E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2368406.75 | 81986600.46 |
September | 0.936002E+09 | 0.535949E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11493.80 | 71101229.47 |
October | 0.973041E+09 | 0.594990E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166715E+09 |
November | 0.963541E+09 | 0.653254E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190619E+09 |
December | 0.938820E+09 | 0.668274E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207022E+09 |
Annual Sum or Average | 0.116768E+11 | 0.699412E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3860839.20 | 0.196056E+10 |
Minimum of Months | 0.882782E+09 | 0.508427E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71101229.47 |
Maximum of Months | 0.105485E+10 | 0.670623E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2368406.75 | 0.242376E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.101677E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356352E+09 |
February | 0.136988E+10 | 0.847322E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330484E+09 |
March | 0.163688E+10 | 0.947774E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314410E+09 |
April | 0.145246E+10 | 0.812166E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297036.40 | 0.297790E+09 |
May | 0.157341E+10 | 0.857820E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17300.29 | 0.229470E+09 |
June | 0.156904E+10 | 0.839761E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173856.28 | 0.190344E+09 |
July | 0.145684E+10 | 0.791287E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1519704.34 | 0.158382E+09 |
August | 0.163688E+10 | 0.891944E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3523114.80 | 0.128768E+09 |
September | 0.145246E+10 | 0.833442E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17148.64 | 0.109683E+09 |
October | 0.150994E+10 | 0.914087E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255084E+09 |
November | 0.149520E+10 | 0.992688E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286370E+09 |
December | 0.145684E+10 | 0.100932E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311421E+09 |
Annual Sum or Average | 0.181198E+11 | 0.107544E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5548160.76 | 0.296856E+10 |
Minimum of Months | 0.136988E+10 | 0.791287E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109683E+09 |
Maximum of Months | 0.163688E+10 | 0.101677E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3523114.80 | 0.356352E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.670014E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258360E+09 |
February | 0.882782E+09 | 0.552020E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238532E+09 |
March | 0.105485E+10 | 0.613707E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231641E+09 |
April | 0.936002E+09 | 0.522797E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155809.75 | 0.222930E+09 |
May | 0.101394E+10 | 0.550887E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11534.36 | 0.164925E+09 |
June | 0.101113E+10 | 0.538594E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115867.25 | 0.139898E+09 |
July | 0.938820E+09 | 0.507891E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 967033.77 | 0.122038E+09 |
August | 0.105485E+10 | 0.571974E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2337646.54 | 0.100651E+09 |
September | 0.936002E+09 | 0.538941E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11492.26 | 78580641.57 |
October | 0.973041E+09 | 0.595275E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185606E+09 |
November | 0.963541E+09 | 0.649974E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216312E+09 |
December | 0.938820E+09 | 0.667421E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239679E+09 |
Annual Sum or Average | 0.116768E+11 | 0.697949E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3599383.94 | 0.219915E+10 |
Minimum of Months | 0.882782E+09 | 0.507891E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78580641.57 |
Maximum of Months | 0.105485E+10 | 0.670014E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2337646.54 | 0.258360E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.106639E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729839E+09 |
February | 0.136985E+10 | 0.872514E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662118E+09 |
March | 0.163685E+10 | 0.955370E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653196E+09 |
April | 0.145243E+10 | 0.810755E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1331495.76 | 0.629624E+09 |
May | 0.157338E+10 | 0.853746E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28809.71 | 0.502666E+09 |
June | 0.156900E+10 | 0.835046E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358102.02 | 0.417175E+09 |
July | 0.145680E+10 | 0.784186E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5756887.68 | 0.348774E+09 |
August | 0.163685E+10 | 0.885875E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8833281.62 | 0.283729E+09 |
September | 0.145243E+10 | 0.835943E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30209.17 | 0.230797E+09 |
October | 0.150991E+10 | 0.932711E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522531E+09 |
November | 0.149516E+10 | 0.103026E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585881E+09 |
December | 0.145680E+10 | 0.106921E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628732E+09 |
Annual Sum or Average | 0.181194E+11 | 0.109320E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16338785.96 | 0.619506E+10 |
Minimum of Months | 0.136985E+10 | 0.784186E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230797E+09 |
Maximum of Months | 0.163685E+10 | 0.106921E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8833281.62 | 0.729839E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.668928E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487977E+09 |
February | 0.649041E+09 | 0.555876E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454594E+09 |
March | 0.773965E+09 | 0.613022E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448323E+09 |
April | 0.688021E+09 | 0.522684E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630691.14 | 0.435890E+09 |
May | 0.744847E+09 | 0.552553E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18048.00 | 0.346406E+09 |
June | 0.742030E+09 | 0.541160E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229387.93 | 0.290040E+09 |
July | 0.690839E+09 | 0.508155E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2221460.02 | 0.241575E+09 |
August | 0.773965E+09 | 0.573443E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5123752.31 | 0.198587E+09 |
September | 0.688021E+09 | 0.535449E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19311.77 | 0.160517E+09 |
October | 0.715730E+09 | 0.593880E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359730E+09 |
November | 0.708685E+09 | 0.651506E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394529E+09 |
December | 0.690839E+09 | 0.666438E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422033E+09 |
Annual Sum or Average | 0.858171E+10 | 0.698309E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8242651.17 | 0.424020E+10 |
Minimum of Months | 0.649041E+09 | 0.508155E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160517E+09 |
Maximum of Months | 0.773965E+09 | 0.668928E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5123752.31 | 0.487977E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.101555E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765569E+09 |
February | 0.136988E+10 | 0.846317E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730131E+09 |
March | 0.163688E+10 | 0.946796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698459E+09 |
April | 0.145246E+10 | 0.811608E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639982.70 | 0.665758E+09 |
May | 0.157341E+10 | 0.857211E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28803.45 | 0.523501E+09 |
June | 0.156904E+10 | 0.839358E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358073.59 | 0.431850E+09 |
July | 0.145684E+10 | 0.790687E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257207.39 | 0.365746E+09 |
August | 0.163688E+10 | 0.891179E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7932436.71 | 0.302625E+09 |
September | 0.145246E+10 | 0.832730E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29803.02 | 0.251412E+09 |
October | 0.150994E+10 | 0.913071E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570849E+09 |
November | 0.149520E+10 | 0.991647E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617414E+09 |
December | 0.145684E+10 | 0.100817E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663920E+09 |
Annual Sum or Average | 0.181198E+11 | 0.107443E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12246306.85 | 0.658723E+10 |
Minimum of Months | 0.136988E+10 | 0.790687E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251412E+09 |
Maximum of Months | 0.163688E+10 | 0.101555E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7932436.71 | 0.765569E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.668204E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504668E+09 |
February | 0.882782E+09 | 0.551031E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468336E+09 |
March | 0.105485E+10 | 0.612560E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462972E+09 |
April | 0.936002E+09 | 0.522241E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 342273.45 | 0.450792E+09 |
May | 0.101394E+10 | 0.550481E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19179.96 | 0.361557E+09 |
June | 0.101113E+10 | 0.538196E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238627.33 | 0.299081E+09 |
July | 0.938820E+09 | 0.507388E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2160237.09 | 0.261751E+09 |
August | 0.105485E+10 | 0.571503E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5287807.30 | 0.213034E+09 |
September | 0.936002E+09 | 0.538300E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20133.94 | 0.170462E+09 |
October | 0.973041E+09 | 0.594240E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373886E+09 |
November | 0.963541E+09 | 0.647998E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408097E+09 |
December | 0.938820E+09 | 0.665537E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438134E+09 |
Annual Sum or Average | 0.116768E+11 | 0.696768E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8068259.07 | 0.441277E+10 |
Minimum of Months | 0.882782E+09 | 0.507388E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170462E+09 |
Maximum of Months | 0.105485E+10 | 0.668204E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5287807.30 | 0.504668E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.106618E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838415E+09 |
February | 0.136985E+10 | 0.872394E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749284E+09 |
March | 0.163685E+10 | 0.955230E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741243E+09 |
April | 0.145243E+10 | 0.810714E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1712956.94 | 0.729770E+09 |
May | 0.157338E+10 | 0.853727E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23381.88 | 0.598093E+09 |
June | 0.156900E+10 | 0.835018E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387706.96 | 0.506289E+09 |
July | 0.145680E+10 | 0.784167E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6173756.45 | 0.426576E+09 |
August | 0.163685E+10 | 0.885817E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10060238.17 | 0.345672E+09 |
September | 0.145243E+10 | 0.835908E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26052.82 | 0.271248E+09 |
October | 0.150991E+10 | 0.932626E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584257E+09 |
November | 0.149516E+10 | 0.103005E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652036E+09 |
December | 0.145680E+10 | 0.106891E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704623E+09 |
Annual Sum or Average | 0.181194E+11 | 0.109307E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18384093.22 | 0.714750E+10 |
Minimum of Months | 0.136985E+10 | 0.784167E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271248E+09 |
Maximum of Months | 0.163685E+10 | 0.106891E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10060238.17 | 0.838415E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.668825E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559760E+09 |
February | 0.882782E+09 | 0.555832E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510818E+09 |
March | 0.105485E+10 | 0.612974E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509586E+09 |
April | 0.936002E+09 | 0.522708E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 767032.24 | 0.507757E+09 |
May | 0.101394E+10 | 0.552539E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15586.32 | 0.413268E+09 |
June | 0.101113E+10 | 0.541143E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258460.13 | 0.352523E+09 |
July | 0.938820E+09 | 0.508150E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2607700.00 | 0.295514E+09 |
August | 0.105485E+10 | 0.573431E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6318482.63 | 0.241859E+09 |
September | 0.936002E+09 | 0.535448E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17366.22 | 0.189226E+09 |
October | 0.973041E+09 | 0.593959E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403672E+09 |
November | 0.963541E+09 | 0.651400E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437732E+09 |
December | 0.938820E+09 | 0.666355E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471746E+09 |
Annual Sum or Average | 0.116768E+11 | 0.698276E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9984627.54 | 0.489346E+10 |
Minimum of Months | 0.882782E+09 | 0.508150E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189226E+09 |
Maximum of Months | 0.105485E+10 | 0.668825E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6318482.63 | 0.559760E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.101545E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872369E+09 |
February | 0.136988E+10 | 0.846278E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825030E+09 |
March | 0.163688E+10 | 0.946743E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802246E+09 |
April | 0.145246E+10 | 0.811558E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 742220.69 | 0.780104E+09 |
May | 0.157341E+10 | 0.857185E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23375.62 | 0.625952E+09 |
June | 0.156904E+10 | 0.839339E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387679.03 | 0.524659E+09 |
July | 0.145684E+10 | 0.790670E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3793747.33 | 0.448078E+09 |
August | 0.163688E+10 | 0.891155E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9449574.55 | 0.369608E+09 |
September | 0.145246E+10 | 0.832697E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25776.05 | 0.299508E+09 |
October | 0.150994E+10 | 0.913020E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652587E+09 |
November | 0.149520E+10 | 0.991583E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690372E+09 |
December | 0.145684E+10 | 0.100806E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745298E+09 |
Annual Sum or Average | 0.181198E+11 | 0.107437E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14422373.26 | 0.763581E+10 |
Minimum of Months | 0.136988E+10 | 0.790670E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299508E+09 |
Maximum of Months | 0.163688E+10 | 0.101545E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9449574.55 | 0.872369E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.668040E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578708E+09 |
February | 0.882782E+09 | 0.550979E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535944E+09 |
March | 0.105485E+10 | 0.612494E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535720E+09 |
April | 0.936002E+09 | 0.522225E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 395786.19 | 0.531234E+09 |
May | 0.101394E+10 | 0.550463E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15550.55 | 0.434850E+09 |
June | 0.101113E+10 | 0.538187E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258424.11 | 0.364301E+09 |
July | 0.938820E+09 | 0.507318E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2497616.71 | 0.320922E+09 |
August | 0.105485E+10 | 0.571491E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6291091.97 | 0.260635E+09 |
September | 0.936002E+09 | 0.538274E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17365.79 | 0.204150E+09 |
October | 0.973041E+09 | 0.594182E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429091E+09 |
November | 0.963541E+09 | 0.647902E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463444E+09 |
December | 0.938820E+09 | 0.665300E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499494E+09 |
Annual Sum or Average | 0.116768E+11 | 0.696685E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9475835.33 | 0.515849E+10 |
Minimum of Months | 0.882782E+09 | 0.507318E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204150E+09 |
Maximum of Months | 0.105485E+10 | 0.668040E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6291091.97 | 0.578708E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790076E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702207E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667744E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603209.56 | 0.625427E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2376.15 | 0.478327E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136465.26 | 0.394533E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3395473.85 | 0.329309E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5867747.60 | 0.271584E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.17 | 0.225802E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537619E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623065E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683695E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10006621.61 | 0.632939E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225802E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5867747.60 | 0.790076E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127437E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116965E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114017E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1480238.04 | 0.107318E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3691.86 | 0.841481E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244933.62 | 0.691061E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7232666.74 | 0.576067E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10943681.29 | 0.478466E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1851.47 | 0.395764E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918326E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103566E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111499E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19907063.01 | 0.107092E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395764E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10943681.29 | 0.127437E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126890E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117255E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117877E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052770.85 | 0.115777E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944144E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70827.42 | 0.794058E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2373789.63 | 0.670636E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7740205.37 | 0.544761E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432292E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940433E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102468E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109185E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11237593.27 | 0.112208E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432292E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7740205.37 | 0.126890E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 601.99 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1500.21 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 564.11 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1306.38 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 528.78 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 927.82 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 | 01-APR-17:10 | 542.54 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 852.96 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 05-MAY-16:00 | 390.10 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 28-JUN-16:00 | 532.59 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 917.45 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 | 23-JUL-16:00 | 271.52 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 908.20 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 08-AUG-17:00 | 342.50 | 04-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1317.30 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 257.08 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1640.38 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 474.65 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 576.44 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 475.40 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.08 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 | 601.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 393.28 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 978.00 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 366.88 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 802.58 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 348.38 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 570.29 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | 01-APR-17:10 | 356.58 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 05-MAY-16:00 | 255.87 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 28-JUN-16:00 | 347.90 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 545.08 | 12-JUL-08:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 | 23-JUL-15:54 | 174.47 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 567.93 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 08-AUG-17:00 | 222.63 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 812.37 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 14-SEP-17:00 | 168.33 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1053.47 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 308.60 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 371.78 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 304.53 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.33 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 | 393.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 579.19 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1461.58 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 575.18 | 19-FEB-11:50 |
March | 2010.83 | 01-MAR-10:09 | 1290.29 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 535.55 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 924.57 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 01-APR-17:10 | 542.95 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 854.69 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 05-MAY-16:00 | 382.55 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 28-JUN-16:00 | 520.99 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 909.06 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 | 23-JUL-15:53 | 268.30 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 906.16 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 08-AUG-17:00 | 350.29 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1305.23 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 252.04 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1636.19 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 459.30 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 555.26 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 439.61 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.04 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 | 579.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 424.15 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 940.18 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 404.50 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 856.72 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 392.60 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 718.61 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 01-APR-16:00 | 406.12 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 566.83 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 05-MAY-16:00 | 272.90 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 556.42 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 28-JUN-16:00 | 387.18 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 742.06 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 23-JUL-15:57 | 210.63 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 729.21 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 08-AUG-17:00 | 277.65 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 862.04 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 14-SEP-17:00 | 183.43 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1057.46 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 341.66 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 422.87 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 355.02 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 556.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.43 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 424.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1232.62 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 1498.31 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1131.81 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1302.48 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1094.55 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 922.45 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.21 | 01-APR-17:02 | 1146.66 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 843.30 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 05-MAY-16:00 | 843.87 | 18-MAY-04:55 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | 28-JUN-16:00 | 1127.34 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 911.38 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.24 | 23-JUL-14:00 | 571.82 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 901.66 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.72 | 13-AUG-14:53 | 793.84 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 1313.48 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 | 14-SEP-17:00 | 551.06 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1640.12 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 986.07 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1166.00 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 925.46 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.06 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 160.21 | 1232.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 817.46 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 975.61 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 762.50 | 19-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 796.55 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 752.26 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 566.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | 01-APR-17:02 | 787.10 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 05-MAY-16:00 | 564.40 | 22-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 28-JUN-16:00 | 754.79 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.55 | 23-JUL-15:53 | 386.93 | 02-JUL-10:00 |
August | 1239.33 | 01-AUG-07:10 | 563.39 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 08-AUG-17:00 | 541.13 | 11-AUG-03:55 |
September | 1239.33 | 01-SEP-07:10 | 806.55 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 14-SEP-17:00 | 367.89 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1053.08 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 655.99 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 773.57 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 615.03 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.89 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | 817.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1242.05 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1459.28 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1330.52 | 19-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 1286.31 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1169.27 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 919.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.72 | 01-APR-16:00 | 1184.33 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 845.11 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 05-MAY-16:00 | 851.47 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | 28-JUN-16:00 | 1125.76 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 902.62 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.80 | 23-JUL-15:53 | 583.99 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 899.52 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 | 08-AUG-17:00 | 825.82 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 1301.33 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 | 14-SEP-17:00 | 557.80 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1635.93 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 989.58 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1171.03 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 952.42 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.80 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 69.80 | 1330.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 833.09 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 936.80 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 766.26 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 851.14 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 767.15 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 709.30 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | 01-APR-16:00 | 789.11 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 561.71 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 05-MAY-16:00 | 578.53 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 550.71 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 28-JUN-16:00 | 761.39 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 732.72 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 | 23-JUL-13:53 | 409.23 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 719.64 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 08-AUG-17:00 | 580.69 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 856.59 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 14-SEP-17:00 | 376.33 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1057.10 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 668.38 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 789.47 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 630.73 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 550.71 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.33 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 | 833.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1415.83 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 1498.00 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1309.32 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1301.75 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1269.94 | 29-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 922.24 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.50 | 01-APR-17:02 | 1349.54 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 842.92 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 1005.30 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 28-JUN-16:00 | 1311.02 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 911.15 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.88 | 23-JUL-13:52 | 665.52 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 901.39 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 | 08-AUG-17:00 | 962.23 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 1312.77 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 628.87 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1640.08 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1216.22 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1344.66 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1082.10 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.87 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 206.50 | 1415.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 937.88 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 975.43 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 872.27 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 796.04 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 866.43 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 566.11 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 | 01-APR-17:02 | 931.64 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 675.07 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 28-JUN-16:00 | 877.22 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.26 | 23-JUL-16:04 | 452.79 | 02-JUL-09:40 |
August | 1295.83 | 01-AUG-09:09 | 563.18 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 08-AUG-17:00 | 656.62 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 806.05 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 14-SEP-17:00 | 419.97 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1053.04 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 810.08 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 891.48 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 719.80 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.97 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 | 937.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1425.42 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1458.92 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1448.74 | 19-FEB-12:20 |
March | 2010.83 | 01-MAR-10:09 | 1285.56 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1355.93 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 918.82 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 | 01-APR-16:00 | 1402.03 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 844.73 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 1019.98 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 28-JUN-16:00 | 1308.13 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 902.37 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.90 | 23-JUL-16:04 | 681.65 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 899.25 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 | 08-AUG-17:00 | 1003.79 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 1300.60 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 639.60 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1635.88 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1216.71 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1346.85 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1095.52 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.60 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 85.90 | 1448.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 967.40 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 936.53 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 875.16 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 850.69 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 891.42 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 708.59 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | 01-APR-16:00 | 938.37 | 10-APR-21:10 |
May | 1295.83 | 01-MAY-09:09 | 561.51 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 695.46 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 550.49 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 28-JUN-16:00 | 889.67 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 732.12 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 23-JUL-14:05 | 483.04 | 22-JUL-22:55 |
August | 1295.83 | 01-AUG-09:09 | 719.17 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 08-AUG-17:00 | 707.03 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 856.15 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 14-SEP-17:00 | 437.42 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1057.07 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 813.64 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 919.94 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 743.58 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 550.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.42 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 967.40 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1299.70 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1208.60 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1128.35 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.25 | 01-APR-17:02 | 1144.78 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 05-MAY-16:00 | 843.81 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 28-JUN-15:00 | 1131.70 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.50 | 23-JUL-15:51 | 569.73 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.02 | 13-AUG-15:00 | 737.92 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 14-SEP-17:00 | 533.56 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1015.30 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1230.41 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1013.09 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.50 | 1299.70 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2185.88 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2026.22 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1931.57 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.21 | 01-APR-17:02 | 1987.05 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 05-MAY-16:00 | 1494.33 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 | 28-JUN-15:00 | 1968.75 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.07 | 23-JUL-15:51 | 989.74 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.65 | 13-AUG-15:10 | 1334.01 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 14-SEP-17:00 | 926.39 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1730.48 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2050.47 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1625.88 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.07 | 2185.88 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2233.63 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2014.74 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1987.92 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.00 | 01-APR-17:02 | 2143.52 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1534.33 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 28-JUN-17:00 | 2034.33 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 24-JUL-14:05 | 1030.00 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.94 | 08-AUG-17:00 | 1488.21 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 967.51 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1844.73 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2098.87 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1705.45 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.00 | 2233.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 99070.82 | 02-JAN-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97020.67 | 28-FEB-07:11 | 25133.15 | 34402.75 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96019.99 | 20-MAR-06:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 102046.60 | 03-APR-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 104221.64 | 30-MAY-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103391.10 | 05-JUN-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 103938.26 | 03-JUL-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98693.28 | 07-AUG-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 108289.39 | 05-SEP-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 107636.21 | 10-OCT-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 105127.67 | 06-NOV-07:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99735.73 | 26-DEC-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 96019.99 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108289.39 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81888.98 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81830.01 | 27-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84394.40 | 13-MAR-04:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85509.77 | 17-APR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85886.66 | 01-MAY-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89813.94 | 12-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87992.45 | 10-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85104.43 | 22-AUG-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89444.21 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89795.70 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87812.82 | 06-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85213.59 | 04-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81830.01 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89813.94 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23919.56 | 12-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67754.35 | 28-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69520.65 | 03-MAR-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74168.15 | 29-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74452.72 | 01-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76226.49 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76852.43 | 17-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78340.42 | 28-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74675.92 | 25-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74001.68 | 06-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 69705.18 | 07-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35889.06 | 07-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 23919.56 | 0.00 | 2686.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78340.42 | 15316.26 | 13241.18 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16011.75 | 11-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27019.27 | 28-FEB-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29864.23 | 15-MAR-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68147.37 | 28-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68071.81 | 05-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73202.65 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71963.88 | 25-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72360.26 | 11-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68402.37 | 14-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36504.72 | 04-OCT-15:40 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24028.13 | 02-NOV-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16003.69 | 06-DEC-16:40 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16003.69 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73202.65 | 15316.26 | 13241.18 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2361.79 | 12-JAN-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.05 |
February | 4659.47 | 27-FEB-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
March | 5152.91 | 20-MAR-13:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.71 |
April | 7448.05 | 27-APR-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
May | 7564.39 | 15-MAY-13:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
June | 11276.83 | 12-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.71 |
July | 13930.80 | 23-JUL-18:31 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 |
August | 11059.87 | 14-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
September | 8438.61 | 11-SEP-15:25 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
October | 6103.68 | 10-OCT-05:03 | 607.30 | 202.41 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 |
November | 4653.39 | 06-NOV-11:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 |
December | 2827.27 | 29-DEC-13:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2361.79 | 0.00 | 202.41 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13930.80 | 3846.22 | 1582.09 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 125.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2875.71 | 05-JAN-09:25 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 |
February | 4907.61 | 08-FEB-09:45 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 |
March | 9407.21 | 14-MAR-08:55 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 |
April | 12502.73 | 27-APR-08:30 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 |
May | 19910.37 | 14-MAY-08:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.74 |
June | 21475.11 | 25-JUN-08:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.16 |
July | 24785.51 | 23-JUL-08:31 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.74 |
August | 22548.21 | 13-AUG-08:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 |
September | 24016.70 | 10-SEP-08:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 |
October | 10348.54 | 04-OCT-08:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 |
November | 4415.06 | 15-NOV-09:10 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 |
December | 3847.66 | 05-DEC-10:00 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2875.71 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | |
Maximum of Months | 24785.51 | 2478.65 | 1019.56 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16607.66 | 20-JAN-13:05 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
February | 29406.20 | 12-FEB-11:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.34 |
March | 20344.15 | 01-MAR-13:30 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 |
April | 23822.44 | 02-APR-14:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.66 |
May | 30381.21 | 07-MAY-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.28 |
June | 21183.62 | 04-JUN-13:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.74 |
July | 31021.73 | 23-JUL-13:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
August | 30542.27 | 13-AUG-12:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 |
September | 32470.92 | 10-SEP-12:31 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.38 |
October | 33339.48 | 08-OCT-13:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.33 |
November | 21802.03 | 11-NOV-12:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.93 |
December | 28464.59 | 03-DEC-12:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16607.66 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33339.48 | 3846.30 | 1582.13 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 291.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5663.89 | 05-JAN-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 |
February | 13009.60 | 28-FEB-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
March | 15416.32 | 18-MAR-17:06 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.42 |
April | 26376.70 | 02-APR-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.95 |
May | 30738.30 | 07-MAY-17:01 | 0.00 | 254.87 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.53 |
June | 27429.59 | 18-JUN-16:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.87 |
July | 32410.13 | 23-JUL-16:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 |
August | 28932.76 | 06-AUG-16:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.65 |
September | 30410.61 | 10-SEP-16:31 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 |
October | 22793.61 | 08-OCT-13:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.19 |
November | 14989.20 | 03-NOV-05:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 |
December | 15583.63 | 04-DEC-05:11 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5663.89 | 0.00 | 141.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32410.13 | 1239.33 | 509.78 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1704.11 | 11-JAN-16:10 | 1923.11 | 1448.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 |
February | 2174.24 | 28-FEB-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3020.62 | 10-MAR-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.10 |
April | 6066.39 | 27-APR-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 |
May | 6711.41 | 05-MAY-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
June | 7261.87 | 21-JUN-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
July | 8425.52 | 24-JUL-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 0.00 |
August | 7988.82 | 25-AUG-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 0.00 |
September | 6392.69 | 11-SEP-15:25 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
October | 3757.83 | 04-OCT-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 |
November | 2159.53 | 04-NOV-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.49 |
December | 1617.01 | 29-DEC-16:10 | 1923.11 | 1550.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1617.01 | 809.73 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8425.52 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 99.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1234.83 | 20-JAN-11:10 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 |
February | 4339.39 | 27-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 |
March | 9490.76 | 14-MAR-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 |
April | 13283.24 | 27-APR-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 |
May | 23868.15 | 14-MAY-07:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.29 |
June | 22909.34 | 25-JUN-08:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.61 |
July | 26560.55 | 30-JUL-08:41 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 |
August | 23971.41 | 13-AUG-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.89 |
September | 21784.99 | 10-SEP-08:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.25 |
October | 10400.80 | 04-OCT-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
November | 4878.95 | 04-NOV-10:05 | 782.73 | 339.85 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 |
December | 2821.23 | 05-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1234.83 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | |
Maximum of Months | 26560.55 | 2478.65 | 1019.56 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16758.90 | 20-JAN-13:15 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 |
February | 32118.37 | 12-FEB-12:22 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.25 |
March | 21843.25 | 01-MAR-13:25 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 |
April | 22391.00 | 02-APR-13:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.03 |
May | 32165.04 | 14-MAY-12:22 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.58 |
June | 31305.73 | 11-JUN-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.01 |
July | 34619.12 | 30-JUL-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.94 |
August | 31833.92 | 13-AUG-12:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.91 |
September | 33320.92 | 10-SEP-12:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.85 |
October | 31841.22 | 08-OCT-13:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 |
November | 32146.31 | 11-NOV-14:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.70 |
December | 27290.38 | 03-DEC-13:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16758.90 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 | |
Maximum of Months | 34619.12 | 3846.30 | 1582.13 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2270.37 | 05-JAN-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 |
February | 8463.46 | 27-FEB-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
March | 11118.87 | 14-MAR-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 |
April | 16104.51 | 01-APR-17:05 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 |
May | 28424.58 | 07-MAY-17:01 | 0.00 | 254.87 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.52 |
June | 27594.89 | 18-JUN-17:11 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.75 |
July | 29276.63 | 23-JUL-17:11 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.64 |
August | 25938.03 | 06-AUG-16:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.72 |
September | 24850.86 | 10-SEP-16:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.12 |
October | 12266.31 | 04-OCT-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
November | 6324.78 | 04-NOV-15:30 | 130.46 | 84.96 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
December | 3459.42 | 05-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2270.37 | 0.00 | 84.96 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | |
Maximum of Months | 29276.63 | 1239.33 | 509.78 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1555.76 | 11-JAN-16:20 | 1923.11 | 1535.47 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 |
February | 1984.66 | 28-FEB-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2485.22 | 10-MAR-14:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 |
April | 6632.66 | 27-APR-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.80 | 0.00 |
May | 7125.02 | 15-MAY-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 |
June | 7862.29 | 21-JUN-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 0.00 |
July | 9337.52 | 24-JUL-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 | 0.00 |
August | 8520.46 | 09-AUG-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 | 0.00 |
September | 6206.50 | 12-SEP-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 0.00 |
October | 3537.12 | 04-OCT-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 |
November | 1855.24 | 02-NOV-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.38 |
December | 1476.00 | 29-DEC-16:10 | 1923.11 | 1550.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1476.00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9337.52 | 2010.79 | 1550.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 | 118.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1029.94 | 20-JAN-10:50 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
February | 1555.13 | 27-FEB-15:40 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
March | 6068.79 | 14-MAR-09:50 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.74 |
April | 12271.57 | 27-APR-09:10 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
May | 23801.52 | 14-MAY-10:12 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.87 |
June | 21615.52 | 25-JUN-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.75 |
July | 23677.64 | 30-JUL-08:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.86 |
August | 24902.13 | 06-AUG-10:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.35 |
September | 24060.84 | 10-SEP-09:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 |
October | 8426.86 | 04-OCT-09:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.90 |
November | 1596.96 | 04-NOV-10:10 | 782.73 | 339.85 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 |
December | 1101.42 | 05-DEC-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1029.94 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 | |
Maximum of Months | 24902.13 | 2591.66 | 1019.56 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14891.81 | 20-JAN-13:25 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 |
February | 18535.84 | 27-FEB-14:20 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.63 |
March | 20677.40 | 01-MAR-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 |
April | 25267.72 | 02-APR-14:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.93 |
May | 34532.53 | 14-MAY-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.70 |
June | 19762.41 | 11-JUN-15:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.46 |
July | 33424.43 | 30-JUL-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 |
August | 36033.95 | 06-AUG-13:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.93 |
September | 38298.05 | 10-SEP-12:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.72 |
October | 31519.92 | 08-OCT-13:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.23 |
November | 19320.28 | 11-NOV-13:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.37 |
December | 14453.75 | 05-DEC-12:30 | 1058.33 | 791.06 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14453.75 | 404.87 | 175.78 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | |
Maximum of Months | 38298.05 | 3846.30 | 1582.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1794.11 | 05-JAN-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 |
February | 7832.68 | 27-FEB-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 |
March | 10828.53 | 14-MAR-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 |
April | 18505.58 | 02-APR-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.27 |
May | 29865.19 | 14-MAY-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.24 |
June | 28216.97 | 18-JUN-18:01 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.77 |
July | 27722.38 | 23-JUL-16:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.35 |
August | 30201.34 | 06-AUG-16:41 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.42 |
September | 29096.56 | 10-SEP-16:21 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 |
October | 12211.92 | 04-OCT-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 |
November | 5762.47 | 04-NOV-15:30 | 130.46 | 84.96 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
December | 2469.43 | 05-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1794.11 | 0.00 | 84.96 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 30201.34 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2228.07 | 12-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.19 |
February | 4305.94 | 28-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 |
March | 4887.41 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.90 |
April | 6471.51 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 0.00 |
May | 7024.38 | 08-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 |
June | 10061.76 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.16 |
July | 8438.91 | 31-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
August | 10957.68 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 |
September | 8940.36 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.06 |
October | 8414.68 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.08 |
November | 6703.56 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.98 |
December | 3630.88 | 04-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2228.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10957.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 147.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7168.64 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1279.96 |
February | 5813.95 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.70 |
March | 5389.17 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.86 |
April | 4290.57 | 27-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 0.00 |
May | 4571.35 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 |
June | 5162.88 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 0.00 |
July | 6225.20 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 0.00 |
August | 6659.52 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 | 0.00 |
September | 6072.74 | 11-SEP-15:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
October | 3745.80 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 |
November | 6584.49 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.23 |
December | 6754.66 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3745.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7168.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 | 1279.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.74 |
February | 2854.15 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
March | 5649.95 | 14-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.48 |
April | 15301.62 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
May | 15930.39 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 |
June | 16049.18 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
July | 17355.35 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 0.00 |
August | 18474.35 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 | 0.00 |
September | 14518.23 | 11-SEP-14:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 |
October | 8830.17 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.30 |
November | 3125.58 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18474.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 947.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1947.92 | 05-JAN-16:10 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4033.73 | 07-FEB-16:50 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7009.32 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8154.66 | 26-APR-18:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3446.05 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5322.30 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7270.17 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8697.08 | 06-AUG-18:41 | 0.00 | 158.32 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3332.13 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5051.92 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5839.70 | 11-NOV-15:55 | 23.38 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7754.83 | 05-DEC-15:50 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1947.92 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8697.08 | 222.14 | 316.63 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1538.25 | 05-JAN-16:20 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3705.58 | 07-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6252.31 | 31-MAR-23:50 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7786.17 | 26-APR-18:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3218.45 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5001.88 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6991.99 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8157.35 | 06-AUG-18:35 | 0.00 | 140.73 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2998.48 | 30-SEP-23:50 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4251.72 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5328.70 | 10-NOV-16:10 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7168.58 | 05-DEC-16:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1538.25 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8157.35 | 222.14 | 316.63 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1398.62 | 05-JAN-16:20 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3580.71 | 08-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5758.96 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7851.74 | 26-APR-18:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3130.34 | 31-MAY-23:30 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4910.45 | 30-JUN-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6956.94 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8356.47 | 06-AUG-18:30 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2595.43 | 30-SEP-23:20 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4162.74 | 04-OCT-16:50 | 70.15 | 175.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5215.44 | 04-NOV-16:02 | 70.15 | 105.55 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6971.48 | 05-DEC-16:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1398.62 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8356.47 | 222.14 | 316.63 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91053.20 | 12-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183297.66 | 27-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358391.21 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367369.74 | 27-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176106.82 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267641.67 | 30-JUN-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360243.33 | 31-JUL-24:00 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368286.52 | 14-AUG-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175662.23 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267221.64 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275762.42 | 06-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367135.29 | 04-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91053.20 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368286.52 | 4808.68 | 4157.19 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.154926E+13 | 1131748.64 | 10-JAN-16:00 | 0.349230E+12 | 1281357.61 | 02-JAN-06:10 |
February | 0.176005E+13 | 1387221.62 | 27-FEB-15:09 | 0.195157E+12 | 619653.17 | 18-FEB-07:10 |
March | 0.237365E+13 | 1518879.04 | 14-MAR-15:00 | 0.864843E+11 | 482279.39 | 29-MAR-13:20 |
April | 0.259661E+13 | 1918772.92 | 27-APR-14:39 | 0.378604E+11 | 428483.55 | 03-APR-13:20 |
May | 0.159102E+13 | 1464786.37 | 15-MAY-15:09 | 0.993947E+10 | 264641.43 | 17-MAY-09:00 |
June | 0.192935E+13 | 1565803.12 | 09-JUN-15:20 | 0.440673E+09 | 252555.18 | 13-JUN-09:20 |
July | 0.239089E+13 | 1849062.89 | 31-JUL-15:09 | 0.104597E+09 | 165400.95 | 12-JUL-09:20 |
August | 0.292605E+13 | 2044516.27 | 29-AUG-15:20 | 87100423.82 | 93145.58 | 03-AUG-09:09 |
September | 0.152870E+13 | 1442199.34 | 11-SEP-15:20 | 0.169952E+10 | 314706.07 | 27-SEP-09:20 |
October | 0.188253E+13 | 1551864.96 | 04-OCT-15:09 | 0.211772E+11 | 233691.30 | 10-OCT-09:50 |
November | 0.219661E+13 | 1436241.79 | 16-NOV-16:30 | 0.138730E+12 | 501487.66 | 24-NOV-07:10 |
December | 0.267309E+13 | 1572696.72 | 05-DEC-16:19 | 0.270993E+12 | 769018.81 | 26-DEC-07:10 |
Annual Sum or Average | 0.253978E+14 | 0.111190E+13 | ||||
Minimum of Months | 0.152870E+13 | 1131748.64 | 87100423.82 | 93145.58 | ||
Maximum of Months | 0.292605E+13 | 2044516.27 | 0.349230E+12 | 1281357.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.211428E+12 | 0.441256E+11 | 0.766053E+12 | 0.213317E+12 | 0.158112E+12 | 0.142694E+11 | 0.00 | 0.896903E+10 | 0.751376E+09 | 0.931767E+11 | 0.00 | 0.390568E+11 | 0.00 |
February | 0.188487E+12 | 0.343652E+11 | 0.978954E+12 | 0.195309E+12 | 0.150242E+12 | 0.157333E+11 | 0.00 | 0.251291E+11 | 0.307203E+10 | 0.133028E+12 | 0.00 | 0.357280E+11 | 0.00 |
March | 0.221474E+12 | 0.307121E+11 | 0.141687E+13 | 0.226028E+12 | 0.181822E+12 | 0.197104E+11 | 0.00 | 0.485701E+11 | 0.581669E+10 | 0.181099E+12 | 0.00 | 0.415407E+11 | 0.00 |
April | 0.196038E+12 | 0.231133E+11 | 0.165903E+13 | 0.211475E+12 | 0.191307E+12 | 0.189748E+11 | 0.00 | 0.845783E+11 | 0.187805E+11 | 0.156631E+12 | 0.00 | 0.366859E+11 | 0.00 |
May | 0.210933E+12 | 0.194367E+11 | 0.774844E+12 | 0.219671E+12 | 0.209030E+12 | 0.234035E+11 | 0.00 | 0.408758E+11 | 0.188373E+11 | 0.362408E+11 | 0.00 | 0.377491E+11 | 0.00 |
June | 0.209451E+12 | 0.168813E+11 | 0.106252E+13 | 0.217906E+12 | 0.215470E+12 | 0.301380E+11 | 0.00 | 0.808156E+11 | 0.371963E+11 | 0.229298E+11 | 0.00 | 0.360473E+11 | 0.00 |
July | 0.195875E+12 | 0.181386E+11 | 0.139340E+13 | 0.213239E+12 | 0.231516E+12 | 0.392972E+11 | 0.00 | 0.177131E+12 | 0.668030E+11 | 0.221007E+11 | 0.00 | 0.333862E+11 | 0.00 |
August | 0.219001E+12 | 0.215466E+11 | 0.173200E+13 | 0.226028E+12 | 0.246567E+12 | 0.454918E+11 | 0.00 | 0.301988E+12 | 0.964241E+11 | 0.790180E+09 | 0.00 | 0.362148E+11 | 0.00 |
September | 0.196941E+12 | 0.266127E+11 | 0.740713E+12 | 0.211475E+12 | 0.206357E+12 | 0.284393E+11 | 0.00 | 0.555002E+11 | 0.276227E+11 | 0.172979E+10 | 0.00 | 0.333050E+11 | 0.00 |
October | 0.206805E+12 | 0.349330E+11 | 0.108340E+13 | 0.213315E+12 | 0.187493E+12 | 0.180116E+11 | 0.00 | 0.394465E+11 | 0.821424E+10 | 0.554976E+11 | 0.00 | 0.354161E+11 | 0.00 |
November | 0.208332E+12 | 0.406597E+11 | 0.135889E+13 | 0.205270E+12 | 0.166471E+12 | 0.169745E+11 | 0.00 | 0.388757E+11 | 0.542738E+10 | 0.119620E+12 | 0.00 | 0.360879E+11 | 0.00 |
December | 0.205710E+12 | 0.459151E+11 | 0.170972E+13 | 0.213242E+12 | 0.167317E+12 | 0.187328E+11 | 0.00 | 0.496491E+11 | 0.444864E+10 | 0.221132E+12 | 0.00 | 0.372214E+11 | 0.00 |
Annual Sum or Average | 0.247048E+13 | 0.356440E+12 | 0.146764E+14 | 0.256628E+13 | 0.231171E+13 | 0.289177E+12 | 0.00 | 0.951529E+12 | 0.293394E+12 | 0.104398E+13 | 0.00 | 0.438439E+12 | 0.00 |
Minimum of Months | 0.188487E+12 | 0.168813E+11 | 0.740713E+12 | 0.195309E+12 | 0.150242E+12 | 0.142694E+11 | 0.00 | 0.896903E+10 | 0.751376E+09 | 0.790180E+09 | 0.00 | 0.333050E+11 | 0.00 |
Maximum of Months | 0.221474E+12 | 0.459151E+11 | 0.173200E+13 | 0.226028E+12 | 0.246567E+12 | 0.454918E+11 | 0.00 | 0.301988E+12 | 0.964241E+11 | 0.221132E+12 | 0.00 | 0.415407E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.349230E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.195157E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.864843E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.378604E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.993947E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.440673E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.104597E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 87100423.82 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.169952E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.211772E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.138730E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.270993E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111190E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 87100423.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.349230E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-16:30 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233394.81 | 04-JAN-08:20 | 90649.18 | 02-JAN-06:10 | 21342.75 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 239816.34 | 02-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233392.41 | 02-FEB-08:20 | 137981.97 | 27-FEB-15:09 | 20390.85 | 06-FEB-10:20 | 0.00 | 01-FEB-00:10 |
March | 232449.70 | 22-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233389.48 | 22-MAR-07:19 | 154949.17 | 14-MAR-15:20 | 20242.41 | 25-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 219022.99 | 03-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233382.37 | 03-APR-07:19 | 239317.40 | 27-APR-14:39 | 38570.55 | 26-APR-14:39 | 0.00 | 01-APR-00:10 |
May | 214737.25 | 17-MAY-07:10 | 27558.46 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 233380.11 | 17-MAY-07:19 | 227850.01 | 15-MAY-14:30 | 39021.67 | 04-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 213311.67 | 29-JUN-07:10 | 27558.46 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 233379.35 | 29-JUN-07:19 | 214092.61 | 28-JUN-15:20 | 38814.25 | 27-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 218153.98 | 12-JUL-07:30 | 27558.46 | 01-JUL-20:10 | 660080.29 | 03-JUL-07:10 | 233381.91 | 12-JUL-07:40 | 262761.66 | 20-JUL-12:20 | 42585.91 | 20-JUL-12:20 | 0.00 | 01-JUL-00:10 |
August | 217315.09 | 28-AUG-07:30 | 40855.88 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233381.47 | 28-AUG-07:40 | 274484.96 | 10-AUG-14:39 | 38711.38 | 29-AUG-12:30 | 0.00 | 01-AUG-00:10 |
September | 232947.01 | 25-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233389.74 | 25-SEP-07:19 | 277574.26 | 11-SEP-14:39 | 39333.99 | 11-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 246230.77 | 31-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233396.79 | 31-OCT-07:19 | 212029.34 | 04-OCT-15:39 | 36342.37 | 04-OCT-13:20 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 06-NOV-16:49 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233396.80 | 03-NOV-07:19 | 109947.96 | 15-NOV-13:00 | 20723.10 | 24-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-16:19 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233396.85 | 28-DEC-08:20 | 105305.77 | 05-DEC-11:00 | 21585.69 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 213311.67 | 27558.46 | 423497.50 | 233379.35 | 90649.18 | 20242.41 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233396.85 | 277574.26 | 42585.91 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7455.60 | 20-JAN-15:39 | 1399.07 | 11-JAN-15:30 | 64331.37 | 09-JAN-11:00 | 0.00 | 51962.28 | 31-JAN-12:00 | 0.00 |
February | 96810.48 | 27-FEB-15:09 | 45048.17 | 27-FEB-15:30 | 100000.00 | 11-FEB-17:10 | 0.00 | 52005.65 | 10-FEB-12:20 | 0.00 |
March | 98301.20 | 18-MAR-15:00 | 44009.10 | 18-MAR-13:39 | 100000.00 | 01-MAR-06:10 | 0.00 | 51854.47 | 03-MAR-12:50 | 0.00 |
April | 318448.06 | 27-APR-14:00 | 72883.01 | 27-APR-12:20 | 100000.00 | 01-APR-17:10 | 0.00 | 50575.06 | 06-APR-11:39 | 0.00 |
May | 224116.92 | 04-MAY-14:09 | 72883.01 | 04-MAY-13:00 | 100000.00 | 14-MAY-12:50 | 0.00 | 48763.98 | 01-MAY-11:00 | 0.00 |
June | 240817.02 | 21-JUN-14:09 | 72883.01 | 20-JUN-13:39 | 100000.00 | 01-JUN-14:09 | 0.00 | 46818.54 | 02-JUN-11:20 | 0.00 |
July | 362705.34 | 31-JUL-15:00 | 72883.01 | 07-JUL-12:30 | 100000.00 | 18-JUL-14:30 | 0.00 | 45392.54 | 03-JUL-11:00 | 0.00 |
August | 421316.31 | 29-AUG-14:30 | 72883.01 | 07-AUG-10:30 | 100000.00 | 09-AUG-08:00 | 0.00 | 44766.81 | 31-AUG-11:30 | 0.00 |
September | 209803.50 | 11-SEP-15:30 | 72883.01 | 12-SEP-13:20 | 38380.78 | 08-SEP-14:00 | 0.00 | 45683.79 | 29-SEP-11:39 | 0.00 |
October | 178344.11 | 04-OCT-14:20 | 45687.54 | 04-OCT-14:30 | 100000.00 | 03-OCT-11:20 | 0.00 | 47250.75 | 31-OCT-11:00 | 0.00 |
November | 118666.89 | 04-NOV-14:09 | 45593.84 | 04-NOV-14:20 | 100000.00 | 13-NOV-22:10 | 0.00 | 49235.58 | 30-NOV-12:00 | 0.00 |
December | 25772.76 | 05-DEC-14:39 | 3591.92 | 14-DEC-11:00 | 100000.00 | 02-DEC-05:30 | 0.00 | 51100.98 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 7455.60 | 1399.07 | 38380.78 | 0.00 | 44766.81 | 0.00 | ||||
Maximum of Months | 421316.31 | 72883.01 | 100000.00 | 0.00 | 52005.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1131748.64 | 10-JAN-16:00 | 247210.90 | 423497.50 | 40855.88 | 233284.51 | 68771.48 | 19429.29 | 0.00 | 5788.86 | 654.26 |
February | 1387221.62 | 27-FEB-15:09 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 137981.97 | 20135.55 | 0.00 | 96810.48 | 44975.79 |
March | 1518879.04 | 14-MAR-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 150082.33 | 20089.05 | 0.00 | 92875.29 | 28819.29 |
April | 1918772.92 | 27-APR-14:39 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 239317.40 | 37410.82 | 0.00 | 316349.05 | 72883.01 |
May | 1464786.37 | 15-MAY-15:09 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 225172.64 | 35665.11 | 0.00 | 154073.03 | 44446.55 |
June | 1565803.12 | 09-JUN-15:20 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 193604.32 | 35573.96 | 0.00 | 180020.16 | 46289.94 |
July | 1849062.89 | 31-JUL-15:09 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 255414.90 | 37558.41 | 0.00 | 343762.36 | 72883.01 |
August | 2044516.27 | 29-AUG-15:20 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 270536.85 | 37784.73 | 0.00 | 404381.15 | 72883.01 |
September | 1442199.34 | 11-SEP-15:20 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 277574.26 | 28527.70 | 0.00 | 173792.59 | 58329.63 |
October | 1551864.96 | 04-OCT-15:09 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 181152.05 | 35707.12 | 0.00 | 168554.85 | 44052.71 |
November | 1436241.79 | 16-NOV-16:30 | 247210.90 | 660080.29 | 40855.88 | 233281.95 | 84854.80 | 19552.69 | 0.00 | 17118.97 | 1533.36 |
December | 1572696.72 | 05-DEC-16:19 | 247210.90 | 778371.69 | 40855.88 | 233279.28 | 89639.23 | 19533.97 | 0.00 | 23812.14 | 1883.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1131748.64 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 68771.48 | 19429.29 | 0.00 | 5788.86 | 654.26 | |
Maximum of Months | 2044516.27 | 247210.90 | 778371.69 | 40855.88 | 233284.51 | 277574.26 | 37784.73 | 0.00 | 404381.15 | 72883.01 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1281357.61 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 619653.17 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 482279.39 | 29-MAR-13:20 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 428483.55 | 03-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 264641.43 | 17-MAY-09:00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 252555.18 | 13-JUN-09:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 165400.95 | 12-JUL-09:20 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 93145.58 | 03-AUG-09:09 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 314706.07 | 27-SEP-09:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 233691.30 | 10-OCT-09:50 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 501487.66 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 769018.81 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 93145.58 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1281357.61 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 | 26.46 | 37.33 | 26.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 26.11 | 24.33 | 26.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 26.27 | 28.33 | 26.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 26.40 | 26.67 | 26.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 26.56 | 30.00 | 26.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 26.55 | 30.83 | 26.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 26.89 | 30.67 | 26.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 26.80 | 34.17 | 26.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 26.96 | 41.00 | 26.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 | 26.95 | 40.67 | 26.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 26.78 | 31.33 | 26.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 26.31 | 26.33 | 26.31 |
Annual Sum or Average | 0.00 | 0.00 | 782.17 | 26.64 | 381.67 | 26.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 26.11 | 24.33 | 26.11 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 26.96 | 41.00 | 26.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 25.60 | 0.00 | 25.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.02 | 0.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.67 | 19.26 | 0.17 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
December | 0.83 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
Annual Sum or Average | 4.67 | 19.00 | 0.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.27 | 0.67 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.83 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.83 | 2.33 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.78 | 4.33 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.01 | 5.00 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.12 | 4.00 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.01 | 2.00 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 18.83 | 27.92 | 18.83 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.12 | 5.00 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.69 | 2.17 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.81 | 2.33 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.78 | 3.83 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.62 | 4.33 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.79 | 6.33 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.04 | 4.17 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.26 | 4.33 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.83 | 3.00 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.88 | 1.33 | 27.88 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.67 | 1.17 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 34.83 | 27.72 | 34.17 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.26 | 0.50 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.04 | 6.33 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.46 | 1.17 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.50 | 1.83 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.63 | 6.33 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.42 | 4.50 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.73 | 4.67 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.66 | 11.83 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.49 | 9.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.59 | 4.50 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.59 | 2.83 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.50 | 1.00 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 88.67 | 27.67 | 49.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 28.42 | 11.83 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.00 | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Annual Sum or Average | 2.50 | 19.07 | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.30 | 0.33 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.86 | 2.50 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.86 | 4.17 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.10 | 5.50 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.20 | 4.50 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.03 | 1.83 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
Annual Sum or Average | 5.33 | 19.40 | 0.00 | 19.40 | 18.67 | 26.11 | 18.67 | 26.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.52 | 0.00 | 19.52 | 5.50 | 28.20 | 5.50 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.05 | 0.00 | 19.05 | 0.50 | 22.21 | 0.50 | 23.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.97 | 1.67 | 27.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.79 | 2.17 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.83 | 3.83 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.59 | 3.83 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.83 | 5.50 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.17 | 3.67 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.44 | 4.33 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.90 | 3.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.03 | 1.17 | 28.03 |
December | 0.33 | 19.33 | 0.00 | 19.33 | 0.67 | 24.90 | 0.67 | 26.01 |
Annual Sum or Average | 1.17 | 19.13 | 0.00 | 19.13 | 31.33 | 27.49 | 30.33 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.33 | 0.00 | 19.33 | 5.83 | 28.17 | 5.50 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.67 | 1.67 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.46 | 3.50 | 28.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.14 | 2.50 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.26 | 4.67 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.40 | 2.50 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.61 | 3.83 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 0.83 | 19.01 | 0.00 | 19.01 | 32.50 | 27.94 | 19.00 | 28.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.35 | 0.00 | 19.35 | 9.50 | 28.46 | 4.67 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.83 | 17.70 | 7.33 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
February | 12.00 | 18.06 | 3.83 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
March | 1.67 | 19.20 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
November | 4.50 | 19.06 | 0.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 12.67 | 18.48 | 3.33 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Annual Sum or Average | 53.00 | 18.14 | 15.50 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.83 | 19.29 | 7.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 16.56 | 1.67 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
February | 5.50 | 17.48 | 0.67 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
March | 0.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.76 | 2.50 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.74 | 4.33 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.07 | 5.50 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.05 | 5.17 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.93 | 1.50 | 27.93 |
October | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
November | 2.83 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 6.83 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
Annual Sum or Average | 29.00 | 17.28 | 2.33 | 17.11 | 19.50 | 21.26 | 19.00 | 23.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.83 | 19.34 | 1.67 | 19.34 | 5.83 | 28.07 | 5.50 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 17.34 | 0.83 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
February | 2.33 | 18.59 | 0.00 | 18.59 | 0.67 | 20.57 | 0.67 | 21.83 |
March | 0.50 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.89 | 1.50 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.84 | 3.83 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.62 | 3.83 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.89 | 5.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.26 | 3.50 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.29 | 4.00 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.72 | 1.83 | 27.72 |
November | 1.83 | 19.01 | 0.00 | 19.01 | 0.67 | 21.28 | 0.67 | 22.60 |
December | 4.33 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
Annual Sum or Average | 18.17 | 18.03 | 0.83 | 17.90 | 26.33 | 23.64 | 25.00 | 25.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | 0.00 | 17.15 |
Maximum of Months | 9.17 | 19.01 | 0.83 | 19.01 | 5.83 | 28.26 | 5.17 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 18.41 | 0.33 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
February | 2.33 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 0.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.69 | 1.17 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.48 | 3.33 | 28.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.17 | 2.50 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.34 | 4.67 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.50 | 2.67 | 28.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.79 | 3.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
December | 3.17 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Annual Sum or Average | 12.17 | 18.66 | 0.33 | 18.56 | 31.00 | 25.48 | 17.33 | 26.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 19.18 | 0.33 | 19.18 | 9.50 | 28.50 | 4.67 | 28.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.50 | 24.57 | 114.17 | 25.43 | 13.33 | 25.54 |
February | 43.83 | 24.00 | 132.83 | 25.26 | 0.00 | 25.26 |
March | 34.50 | 24.00 | 129.50 | 25.55 | 0.00 | 25.55 |
April | 3.50 | 24.00 | 184.00 | 25.62 | 0.00 | 25.62 |
May | 0.50 | 27.54 | 261.17 | 25.20 | 0.50 | 25.20 |
June | 0.00 | 0.00 | 294.50 | 25.02 | 0.00 | 25.02 |
July | 4.33 | 27.43 | 424.50 | 24.91 | 4.33 | 24.94 |
August | 2.33 | 27.54 | 475.17 | 24.70 | 2.33 | 24.71 |
September | 14.67 | 27.62 | 381.83 | 24.99 | 14.67 | 25.08 |
October | 10.83 | 27.75 | 215.33 | 25.77 | 10.83 | 25.86 |
November | 3.17 | 25.30 | 219.83 | 25.53 | 1.17 | 25.54 |
December | 20.00 | 24.00 | 137.17 | 25.96 | 0.00 | 25.96 |
Annual Sum or Average | 214.17 | 24.78 | 2970.00 | 25.20 | 47.17 | 25.24 |
Minimum of Months | 0.00 | 0.00 | 114.17 | 24.70 | 0.00 | 24.71 |
Maximum of Months | 76.50 | 27.75 | 475.17 | 25.96 | 14.67 | 25.96 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 187.33 | 23.97 | 25.33 | 24.13 | 13.00 | 24.21 |
February | 95.00 | 23.96 | 65.83 | 24.37 | 0.00 | 24.37 |
March | 32.33 | 24.01 | 104.50 | 25.03 | 0.00 | 25.03 |
April | 2.67 | 24.00 | 168.83 | 24.89 | 0.00 | 24.89 |
May | 1.67 | 23.95 | 215.83 | 24.64 | 0.00 | 24.64 |
June | 0.00 | 0.00 | 284.83 | 24.49 | 0.00 | 24.49 |
July | 0.00 | 0.00 | 415.83 | 24.37 | 0.00 | 24.37 |
August | 0.00 | 0.00 | 479.17 | 24.25 | 0.00 | 24.25 |
September | 0.00 | 0.00 | 352.50 | 24.49 | 0.00 | 24.49 |
October | 0.83 | 23.88 | 178.50 | 25.05 | 0.00 | 25.05 |
November | 9.00 | 23.98 | 180.50 | 24.96 | 0.00 | 24.96 |
December | 51.00 | 23.98 | 94.83 | 25.12 | 0.00 | 25.12 |
Annual Sum or Average | 379.83 | 23.97 | 2566.50 | 24.56 | 13.00 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 25.33 | 24.13 | 0.00 | 24.21 |
Maximum of Months | 187.33 | 24.01 | 479.17 | 25.12 | 13.00 | 25.12 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.67 | 22.79 | 12.00 | 22.71 | 12.00 | 22.64 |
February | 385.17 | 23.30 | 0.00 | 23.30 | 0.00 | 23.30 |
March | 297.33 | 23.71 | 3.83 | 23.72 | 0.00 | 23.72 |
April | 161.33 | 23.69 | 49.50 | 23.95 | 0.00 | 23.95 |
May | 66.33 | 23.75 | 126.33 | 24.26 | 0.00 | 24.26 |
June | 12.67 | 23.73 | 153.83 | 24.46 | 0.00 | 24.46 |
July | 0.67 | 23.60 | 300.00 | 24.37 | 0.00 | 24.37 |
August | 3.33 | 23.64 | 400.17 | 24.25 | 0.00 | 24.25 |
September | 8.67 | 23.59 | 260.50 | 24.40 | 0.00 | 24.40 |
October | 145.00 | 23.58 | 48.67 | 23.94 | 0.00 | 23.94 |
November | 330.00 | 23.53 | 23.50 | 23.60 | 0.00 | 23.60 |
December | 465.67 | 23.21 | 0.00 | 23.21 | 0.00 | 23.21 |
Annual Sum or Average | 2364.83 | 23.32 | 1378.33 | 23.71 | 12.00 | 23.70 |
Minimum of Months | 0.67 | 22.79 | 0.00 | 22.71 | 0.00 | 22.64 |
Maximum of Months | 488.67 | 23.75 | 400.17 | 24.46 | 12.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.26 | 142.17 | 20.86 | 142.17 | 20.61 |
February | 441.83 | 21.86 | 78.00 | 21.55 | 78.00 | 21.32 |
March | 465.17 | 22.81 | 14.33 | 22.74 | 14.33 | 22.67 |
April | 317.17 | 23.18 | 31.50 | 23.29 | 0.00 | 23.29 |
May | 189.67 | 23.41 | 80.50 | 23.67 | 0.00 | 23.67 |
June | 72.50 | 23.55 | 133.50 | 24.07 | 0.00 | 24.07 |
July | 27.50 | 23.62 | 287.67 | 24.23 | 0.00 | 24.23 |
August | 31.67 | 23.49 | 367.00 | 24.16 | 0.00 | 24.16 |
September | 124.83 | 23.33 | 168.50 | 23.84 | 0.00 | 23.84 |
October | 375.83 | 22.89 | 1.67 | 22.90 | 0.00 | 22.90 |
November | 457.83 | 22.16 | 36.17 | 22.02 | 34.33 | 21.90 |
December | 497.00 | 21.55 | 103.00 | 21.28 | 103.00 | 21.09 |
Annual Sum or Average | 3503.00 | 22.32 | 1444.00 | 22.55 | 371.83 | 22.36 |
Minimum of Months | 27.50 | 21.26 | 1.67 | 20.86 | 0.00 | 20.61 |
Maximum of Months | 502.00 | 23.62 | 367.00 | 24.23 | 142.17 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.31 | 12.67 | 22.28 | 12.67 | 22.24 |
February | 407.67 | 22.72 | 5.67 | 22.71 | 3.83 | 22.69 |
March | 392.00 | 23.38 | 0.00 | 23.38 | 0.00 | 23.38 |
April | 201.33 | 23.63 | 60.50 | 23.83 | 0.00 | 23.83 |
May | 122.17 | 23.58 | 128.83 | 24.05 | 0.00 | 24.05 |
June | 18.33 | 23.66 | 215.00 | 24.37 | 0.00 | 24.37 |
July | 0.00 | 0.00 | 381.67 | 24.36 | 0.00 | 24.36 |
August | 0.33 | 27.00 | 423.50 | 24.24 | 0.33 | 24.24 |
September | 80.83 | 23.46 | 210.83 | 24.11 | 0.00 | 24.11 |
October | 277.17 | 23.39 | 24.33 | 23.53 | 0.00 | 23.53 |
November | 377.17 | 23.15 | 14.50 | 23.20 | 0.00 | 23.20 |
December | 487.67 | 22.92 | 0.00 | 22.92 | 0.00 | 22.92 |
Annual Sum or Average | 2866.67 | 23.02 | 1477.50 | 23.47 | 16.83 | 23.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.28 | 0.00 | 22.24 |
Maximum of Months | 502.00 | 27.00 | 423.50 | 24.37 | 12.67 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 22.26 | 15.33 | 22.22 | 15.33 | 22.17 |
February | 393.50 | 22.69 | 11.67 | 22.70 | 6.00 | 22.67 |
March | 354.67 | 23.19 | 10.50 | 23.22 | 0.00 | 23.22 |
April | 171.67 | 23.44 | 125.33 | 23.86 | 0.50 | 23.87 |
May | 122.33 | 23.74 | 202.17 | 24.24 | 8.00 | 24.30 |
June | 45.50 | 24.66 | 295.00 | 24.49 | 14.00 | 24.59 |
July | 21.00 | 26.41 | 384.50 | 24.52 | 16.67 | 24.62 |
August | 28.67 | 25.62 | 419.00 | 24.36 | 17.17 | 24.46 |
September | 85.00 | 23.74 | 267.17 | 24.26 | 7.67 | 24.32 |
October | 262.50 | 23.27 | 68.33 | 23.56 | 0.33 | 23.56 |
November | 392.67 | 22.88 | 18.33 | 22.95 | 0.00 | 22.95 |
December | 490.83 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
Annual Sum or Average | 2869.67 | 22.94 | 1817.33 | 23.50 | 85.67 | 23.53 |
Minimum of Months | 21.00 | 22.26 | 0.00 | 22.22 | 0.00 | 22.17 |
Maximum of Months | 501.33 | 26.41 | 419.00 | 24.52 | 17.17 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.33 | 22.07 | 50.17 | 22.03 | 36.33 | 21.92 |
February | 331.00 | 22.61 | 81.00 | 22.92 | 15.33 | 22.87 |
March | 312.50 | 23.19 | 86.33 | 23.44 | 0.33 | 23.44 |
April | 170.83 | 23.57 | 157.17 | 24.00 | 5.67 | 24.06 |
May | 142.50 | 23.77 | 206.83 | 24.19 | 12.83 | 24.29 |
June | 57.33 | 24.40 | 279.00 | 24.45 | 13.67 | 24.55 |
July | 24.33 | 26.52 | 382.83 | 24.58 | 20.50 | 24.70 |
August | 25.50 | 25.95 | 434.67 | 24.42 | 17.50 | 24.52 |
September | 74.50 | 24.02 | 298.33 | 24.38 | 14.17 | 24.48 |
October | 212.83 | 23.36 | 142.83 | 23.87 | 9.33 | 23.95 |
November | 357.67 | 22.86 | 58.17 | 23.14 | 4.83 | 23.19 |
December | 417.00 | 22.45 | 42.83 | 22.63 | 3.50 | 22.63 |
Annual Sum or Average | 2580.33 | 22.93 | 2220.17 | 23.60 | 154.00 | 23.64 |
Minimum of Months | 24.33 | 22.07 | 42.83 | 22.03 | 0.33 | 21.92 |
Maximum of Months | 454.33 | 26.52 | 434.67 | 24.58 | 36.33 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 443.33 | 23.12 | 1.50 | 23.13 | 0.00 | 23.13 |
February | 246.33 | 23.68 | 76.50 | 23.96 | 2.00 | 23.97 |
March | 68.17 | 24.06 | 147.67 | 24.66 | 2.17 | 24.68 |
April | 25.17 | 26.78 | 309.00 | 25.01 | 23.33 | 25.14 |
May | 41.00 | 25.46 | 312.50 | 24.74 | 20.83 | 24.87 |
June | 19.83 | 27.04 | 441.17 | 24.65 | 19.83 | 24.74 |
July | 53.33 | 26.81 | 489.00 | 24.90 | 53.33 | 25.07 |
August | 62.50 | 26.27 | 514.00 | 24.73 | 62.50 | 24.88 |
September | 25.33 | 26.40 | 390.33 | 24.69 | 21.17 | 24.80 |
October | 29.83 | 24.77 | 197.33 | 24.95 | 9.00 | 25.03 |
November | 87.83 | 24.08 | 136.83 | 24.62 | 3.50 | 24.66 |
December | 127.83 | 24.00 | 72.00 | 24.49 | 0.67 | 24.50 |
Annual Sum or Average | 1230.50 | 24.09 | 3087.83 | 24.53 | 218.33 | 24.64 |
Minimum of Months | 19.83 | 23.12 | 1.50 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 443.33 | 27.04 | 514.00 | 25.01 | 62.50 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 287.33 | 20.41 | 287.33 | 20.33 |
February | 451.00 | 21.11 | 151.67 | 20.87 | 151.67 | 20.72 |
March | 509.17 | 22.12 | 29.17 | 22.04 | 29.17 | 21.96 |
April | 400.17 | 22.77 | 18.00 | 22.84 | 0.00 | 22.84 |
May | 254.00 | 23.17 | 63.50 | 23.38 | 0.00 | 23.38 |
June | 118.00 | 23.43 | 107.67 | 23.83 | 0.00 | 23.83 |
July | 60.33 | 23.52 | 267.50 | 24.11 | 0.00 | 24.11 |
August | 73.50 | 23.38 | 311.17 | 24.03 | 0.00 | 24.03 |
September | 227.83 | 23.11 | 101.50 | 23.43 | 0.00 | 23.43 |
October | 463.67 | 22.44 | 3.67 | 22.43 | 3.00 | 22.42 |
November | 489.00 | 21.51 | 92.67 | 21.33 | 92.67 | 21.20 |
December | 497.00 | 20.82 | 226.17 | 20.67 | 226.17 | 20.58 |
Annual Sum or Average | 4045.67 | 21.89 | 1660.00 | 22.01 | 790.00 | 21.80 |
Minimum of Months | 60.33 | 20.58 | 3.67 | 20.41 | 0.00 | 20.33 |
Maximum of Months | 509.17 | 23.52 | 311.17 | 24.11 | 287.33 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.59 | 248.33 | 20.38 | 248.33 | 20.29 |
February | 376.17 | 21.45 | 108.83 | 21.20 | 108.83 | 21.05 |
March | 389.83 | 22.38 | 18.33 | 22.31 | 16.00 | 22.24 |
April | 229.00 | 22.86 | 72.50 | 23.27 | 0.00 | 23.27 |
May | 172.67 | 23.31 | 127.67 | 23.88 | 7.67 | 23.96 |
June | 84.33 | 24.01 | 201.00 | 24.42 | 14.50 | 24.55 |
July | 54.17 | 24.87 | 289.67 | 24.61 | 20.33 | 24.75 |
August | 55.00 | 24.59 | 319.83 | 24.44 | 17.67 | 24.56 |
September | 159.17 | 23.35 | 168.67 | 23.95 | 7.33 | 24.02 |
October | 320.33 | 22.49 | 31.17 | 22.67 | 0.50 | 22.67 |
November | 407.83 | 21.62 | 75.17 | 21.44 | 74.17 | 21.30 |
December | 422.00 | 20.92 | 191.33 | 20.72 | 191.33 | 20.62 |
Annual Sum or Average | 3097.50 | 22.00 | 1852.50 | 22.39 | 706.67 | 22.20 |
Minimum of Months | 54.17 | 20.59 | 18.33 | 20.38 | 0.00 | 20.29 |
Maximum of Months | 427.00 | 24.87 | 319.83 | 24.61 | 248.33 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.83 | 21.17 | 181.33 | 20.96 | 172.67 | 20.80 |
February | 362.33 | 21.86 | 121.67 | 22.05 | 65.17 | 21.89 |
March | 351.83 | 22.42 | 91.00 | 22.73 | 9.83 | 22.69 |
April | 247.33 | 22.93 | 133.33 | 23.50 | 5.00 | 23.54 |
May | 200.67 | 23.37 | 181.17 | 23.89 | 12.50 | 23.99 |
June | 124.67 | 23.69 | 222.33 | 24.17 | 12.00 | 24.26 |
July | 79.50 | 24.29 | 331.50 | 24.43 | 18.17 | 24.55 |
August | 59.50 | 24.35 | 373.33 | 24.35 | 16.50 | 24.45 |
September | 130.00 | 23.57 | 268.17 | 24.16 | 14.33 | 24.26 |
October | 299.00 | 22.87 | 131.50 | 23.41 | 10.83 | 23.50 |
November | 416.50 | 22.03 | 75.33 | 22.16 | 39.50 | 22.10 |
December | 442.67 | 21.41 | 170.33 | 21.35 | 141.83 | 21.18 |
Annual Sum or Average | 3180.83 | 22.30 | 2281.00 | 22.89 | 518.33 | 22.78 |
Minimum of Months | 59.50 | 21.17 | 75.33 | 20.96 | 5.00 | 20.80 |
Maximum of Months | 466.83 | 24.35 | 373.33 | 24.43 | 172.67 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.96 | 202.50 | 20.73 | 202.50 | 20.60 |
February | 420.67 | 21.61 | 95.33 | 21.42 | 89.33 | 21.25 |
March | 423.00 | 22.52 | 35.67 | 22.58 | 10.00 | 22.54 |
April | 274.17 | 23.11 | 95.17 | 23.50 | 5.83 | 23.55 |
May | 170.17 | 23.64 | 183.67 | 24.09 | 17.00 | 24.23 |
June | 73.83 | 23.98 | 252.83 | 24.33 | 11.33 | 24.42 |
July | 38.50 | 25.65 | 391.00 | 24.63 | 23.17 | 24.75 |
August | 34.67 | 24.76 | 417.17 | 24.40 | 14.33 | 24.48 |
September | 123.00 | 23.77 | 250.00 | 24.22 | 17.50 | 24.35 |
October | 365.67 | 22.78 | 57.50 | 23.03 | 1.50 | 23.04 |
November | 457.83 | 21.89 | 48.33 | 21.84 | 38.83 | 21.75 |
December | 491.17 | 21.29 | 136.17 | 21.10 | 136.17 | 20.98 |
Annual Sum or Average | 3374.67 | 22.18 | 2165.33 | 22.72 | 567.50 | 22.59 |
Minimum of Months | 34.67 | 20.96 | 35.67 | 20.73 | 1.50 | 20.60 |
Maximum of Months | 502.00 | 25.65 | 417.17 | 24.63 | 202.50 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 389.83 | 19.95 | 389.83 | 19.90 |
February | 454.00 | 20.50 | 266.67 | 20.27 | 266.67 | 20.16 |
March | 511.50 | 21.34 | 150.50 | 21.10 | 150.50 | 20.95 |
April | 428.17 | 22.20 | 53.33 | 22.09 | 42.50 | 21.97 |
May | 301.50 | 22.67 | 57.33 | 22.89 | 2.83 | 22.87 |
June | 170.00 | 23.13 | 102.00 | 23.55 | 0.00 | 23.55 |
July | 114.67 | 23.33 | 255.83 | 23.95 | 0.00 | 23.95 |
August | 130.00 | 23.17 | 282.00 | 23.85 | 0.33 | 23.86 |
September | 293.83 | 22.62 | 76.50 | 22.93 | 0.00 | 22.93 |
October | 494.00 | 21.69 | 65.17 | 21.50 | 65.17 | 21.36 |
November | 489.00 | 20.70 | 228.50 | 20.45 | 228.50 | 20.32 |
December | 497.00 | 20.21 | 383.67 | 20.10 | 383.67 | 20.06 |
Annual Sum or Average | 4385.67 | 21.38 | 2311.33 | 21.38 | 1530.00 | 21.12 |
Minimum of Months | 114.67 | 20.08 | 53.33 | 19.95 | 0.00 | 19.90 |
Maximum of Months | 511.50 | 23.33 | 389.83 | 23.95 | 389.83 | 23.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 365.67 | 19.98 | 365.67 | 19.92 |
February | 454.00 | 20.86 | 229.67 | 20.57 | 229.67 | 20.42 |
March | 483.17 | 21.81 | 100.17 | 21.53 | 99.00 | 21.33 |
April | 292.50 | 22.40 | 99.67 | 22.64 | 25.67 | 22.52 |
May | 215.33 | 22.78 | 154.33 | 23.47 | 9.83 | 23.51 |
June | 110.00 | 23.61 | 244.67 | 24.19 | 14.83 | 24.31 |
July | 91.00 | 24.22 | 345.33 | 24.39 | 21.17 | 24.51 |
August | 90.17 | 24.07 | 378.50 | 24.27 | 20.00 | 24.38 |
September | 210.67 | 22.73 | 182.83 | 23.49 | 5.83 | 23.55 |
October | 409.17 | 21.86 | 61.33 | 21.77 | 45.67 | 21.63 |
November | 486.50 | 20.87 | 204.83 | 20.59 | 204.83 | 20.44 |
December | 497.00 | 20.29 | 351.50 | 20.14 | 351.50 | 20.08 |
Annual Sum or Average | 3841.50 | 21.48 | 2718.50 | 21.79 | 1393.67 | 21.52 |
Minimum of Months | 90.17 | 20.13 | 61.33 | 19.98 | 5.83 | 19.92 |
Maximum of Months | 502.00 | 24.22 | 378.50 | 24.39 | 365.67 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.33 | 20.59 | 290.00 | 20.30 | 286.33 | 20.16 |
February | 386.33 | 21.17 | 197.67 | 21.09 | 161.83 | 20.88 |
March | 388.17 | 21.72 | 143.83 | 21.75 | 87.83 | 21.53 |
April | 285.33 | 22.35 | 144.17 | 22.80 | 33.83 | 22.70 |
May | 238.33 | 22.80 | 168.67 | 23.46 | 15.50 | 23.54 |
June | 162.83 | 23.32 | 206.33 | 23.94 | 12.83 | 24.04 |
July | 118.00 | 23.80 | 312.00 | 24.27 | 17.83 | 24.38 |
August | 110.33 | 23.71 | 349.33 | 24.19 | 15.00 | 24.29 |
September | 196.33 | 22.99 | 230.00 | 23.77 | 11.67 | 23.85 |
October | 337.33 | 22.07 | 133.50 | 22.51 | 34.00 | 22.42 |
November | 444.83 | 21.21 | 179.67 | 21.11 | 150.00 | 20.90 |
December | 460.33 | 20.69 | 280.50 | 20.48 | 267.83 | 20.34 |
Annual Sum or Average | 3614.50 | 21.74 | 2635.67 | 22.15 | 1094.50 | 21.91 |
Minimum of Months | 110.33 | 20.59 | 133.50 | 20.30 | 11.67 | 20.16 |
Maximum of Months | 486.33 | 23.80 | 349.33 | 24.27 | 286.33 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 313.00 | 20.13 | 313.00 | 20.03 |
February | 434.00 | 21.00 | 202.83 | 20.73 | 199.67 | 20.58 |
March | 452.00 | 21.83 | 100.00 | 21.70 | 82.83 | 21.53 |
April | 319.50 | 22.54 | 99.33 | 22.88 | 19.83 | 22.86 |
May | 228.67 | 23.13 | 169.67 | 23.71 | 16.67 | 23.85 |
June | 121.00 | 23.54 | 232.00 | 24.11 | 12.00 | 24.21 |
July | 76.00 | 24.52 | 363.00 | 24.51 | 24.00 | 24.63 |
August | 70.17 | 24.03 | 381.83 | 24.31 | 19.67 | 24.38 |
September | 200.33 | 23.22 | 211.17 | 23.84 | 16.50 | 23.96 |
October | 413.33 | 22.12 | 65.83 | 22.20 | 28.83 | 22.11 |
November | 473.17 | 21.14 | 156.83 | 20.93 | 150.17 | 20.77 |
December | 496.50 | 20.65 | 286.00 | 20.44 | 286.00 | 20.35 |
Annual Sum or Average | 3786.67 | 21.69 | 2581.50 | 22.06 | 1169.17 | 21.83 |
Minimum of Months | 70.17 | 20.35 | 65.83 | 20.13 | 12.00 | 20.03 |
Maximum of Months | 502.00 | 24.52 | 381.83 | 24.51 | 313.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 1.50 | 27.00 | 454.00 | 27.00 | 1.50 | 27.00 |
March | 9.17 | 27.00 | 514.00 | 27.00 | 9.17 | 27.00 |
April | 94.83 | 27.00 | 485.00 | 27.00 | 94.83 | 27.00 |
May | 3.83 | 27.00 | 508.00 | 27.00 | 3.83 | 27.00 |
June | 38.00 | 27.00 | 496.00 | 27.00 | 38.00 | 27.00 |
July | 181.00 | 27.00 | 497.00 | 27.00 | 181.00 | 27.00 |
August | 330.33 | 27.00 | 514.00 | 27.00 | 330.33 | 27.00 |
September | 28.67 | 27.00 | 485.00 | 27.00 | 28.67 | 27.00 |
October | 10.33 | 27.00 | 502.00 | 27.00 | 10.33 | 27.00 |
November | 8.17 | 27.00 | 489.00 | 27.00 | 8.17 | 27.00 |
December | 4.83 | 27.00 | 497.00 | 27.00 | 4.83 | 27.00 |
Annual Sum or Average | 710.67 | 27.00 | 5943.00 | 27.00 | 710.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 330.33 | 27.00 | 514.00 | 27.00 | 330.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 25.36 | 438.50 | 26.95 | 0.00 | 26.95 |
February | 0.00 | 0.00 | 430.00 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 514.00 | 27.00 | 0.67 | 27.00 |
April | 8.17 | 27.00 | 485.00 | 27.00 | 8.17 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 7.33 | 27.00 | 496.00 | 27.00 | 7.33 | 27.00 |
July | 33.50 | 27.00 | 497.00 | 27.00 | 33.50 | 27.00 |
August | 62.17 | 27.00 | 514.00 | 27.00 | 62.17 | 27.00 |
September | 9.83 | 27.00 | 485.00 | 27.00 | 9.83 | 27.00 |
October | 3.50 | 27.00 | 502.00 | 27.00 | 3.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 139.50 | 26.83 | 5855.50 | 27.00 | 125.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 430.00 | 26.95 | 0.00 | 26.95 |
Maximum of Months | 62.17 | 27.00 | 514.00 | 27.00 | 62.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.67 | 24.56 | 311.67 | 26.21 | 13.67 | 26.10 |
February | 21.33 | 27.01 | 352.17 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 483.67 | 27.00 | 0.67 | 27.00 |
April | 10.83 | 27.00 | 485.00 | 27.00 | 10.83 | 27.00 |
May | 2.50 | 27.00 | 508.00 | 27.00 | 2.50 | 27.00 |
June | 15.17 | 27.00 | 496.00 | 27.00 | 15.17 | 27.00 |
July | 61.17 | 27.00 | 497.00 | 27.00 | 61.17 | 27.00 |
August | 81.33 | 27.00 | 514.00 | 27.00 | 81.33 | 27.00 |
September | 13.50 | 27.00 | 485.00 | 27.00 | 13.50 | 27.00 |
October | 3.33 | 27.00 | 502.00 | 27.00 | 3.33 | 27.00 |
November | 0.00 | 0.00 | 465.00 | 27.00 | 0.00 | 27.00 |
December | 5.00 | 27.00 | 422.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 327.50 | 26.16 | 5521.83 | 26.94 | 202.17 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 311.67 | 26.21 | 0.00 | 26.10 |
Maximum of Months | 112.67 | 27.01 | 514.00 | 27.00 | 81.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 308.50 | 27.00 | 502.00 | 27.00 | 308.50 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5749.50 | 27.00 | 5943.00 | 27.00 | 5749.50 | 27.00 |
Minimum of Months | 308.50 | 27.00 | 454.00 | 27.00 | 308.50 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 26.82456 | 0.78235 | 17.99153 |
February | 454.00000 | 27.00006 | 27.11667 | 0.84657 | 20.24082 |
March | 514.00000 | 27.00003 | 28.03201 | 0.91083 | 22.58678 |
April | 485.00000 | 27.00002 | 30.77601 | 0.98724 | 25.63789 |
May | 508.00000 | 27.00023 | 33.75893 | 0.25054 | 6.39290 |
June | 496.00000 | 27.00026 | 35.04277 | 0.32334 | 7.23919 |
July | 497.00000 | 27.00029 | 36.25542 | 0.40234 | 8.44935 |
August | 514.00000 | 27.00066 | 36.85465 | 0.44005 | 9.12406 |
September | 485.00000 | 27.00060 | 36.59854 | 0.28249 | 6.75198 |
October | 502.00000 | 27.00012 | 33.28876 | 0.93253 | 23.40825 |
November | 489.00000 | 27.00009 | 31.33036 | 0.92616 | 23.16782 |
December | 497.00000 | 27.00000 | 27.21633 | 0.91008 | 22.52940 |
Annual Sum or Average | 5943.00000 | 27.00020 | 31.95575 | 0.66434 | 16.07677 |
Minimum of Months | 454.00000 | 27.00000 | 26.82456 | 0.25054 | 6.39290 |
Maximum of Months | 514.00000 | 27.00066 | 36.85465 | 0.98724 | 25.63789 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94677 | 26.98546 | 0.63438 | 13.67783 |
February | 454.00000 | 27.00006 | 27.11624 | 0.71092 | 15.84390 |
March | 514.00000 | 27.00003 | 28.01099 | 0.78768 | 18.20049 |
April | 485.00000 | 27.00002 | 30.75475 | 0.86474 | 20.88977 |
May | 508.00000 | 27.00022 | 33.77480 | 0.17441 | 5.77027 |
June | 496.00000 | 27.00025 | 35.04069 | 0.22856 | 6.18375 |
July | 497.00000 | 27.00030 | 36.25521 | 0.28999 | 6.86417 |
August | 514.00000 | 27.00071 | 36.85580 | 0.31161 | 7.15375 |
September | 485.00000 | 27.00057 | 36.69479 | 0.20789 | 6.03113 |
October | 502.00000 | 27.00011 | 33.28278 | 0.83478 | 19.78284 |
November | 489.00000 | 27.00008 | 31.31523 | 0.77492 | 17.76414 |
December | 497.00000 | 27.00000 | 27.20482 | 0.71466 | 15.84020 |
Annual Sum or Average | 5943.00000 | 26.99570 | 31.97216 | 0.54278 | 12.79628 |
Minimum of Months | 454.00000 | 26.94677 | 26.98546 | 0.17441 | 5.77027 |
Maximum of Months | 514.00000 | 27.00071 | 36.85580 | 0.86474 | 20.88977 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.38126 | 27.51587 | 0.45294 | 11.31918 |
February | 454.00000 | 27.00036 | 27.12872 | 0.63328 | 13.78738 |
March | 514.00000 | 27.00003 | 28.02091 | 0.72361 | 16.25458 |
April | 485.00000 | 27.00002 | 30.76199 | 0.82401 | 19.54257 |
May | 508.00000 | 27.00023 | 33.79256 | 0.14284 | 5.72815 |
June | 496.00000 | 27.00025 | 35.04676 | 0.21707 | 6.17626 |
July | 497.00000 | 27.00031 | 36.25435 | 0.28635 | 6.91959 |
August | 514.00000 | 27.00061 | 36.85527 | 0.30363 | 7.15262 |
September | 485.00000 | 27.00055 | 36.76571 | 0.17152 | 5.88363 |
October | 502.00000 | 27.00011 | 33.30826 | 0.77582 | 17.85435 |
November | 489.00000 | 27.00009 | 31.33235 | 0.69255 | 15.28513 |
December | 497.00000 | 27.00000 | 27.20985 | 0.62655 | 13.40908 |
Annual Sum or Average | 5943.00000 | 26.94795 | 32.03104 | 0.48591 | 11.57979 |
Minimum of Months | 454.00000 | 26.38126 | 27.12872 | 0.14284 | 5.72815 |
Maximum of Months | 514.00000 | 27.00061 | 36.85527 | 0.82401 | 19.54257 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 30.01443 | 1.03063 | 27.43619 |
February | 454.00000 | 27.00016 | 30.49244 | 1.20676 | 35.59037 |
March | 514.00000 | 27.00026 | 28.85015 | 1.35034 | 42.89623 |
April | 485.00000 | 27.00165 | 29.80154 | 1.49958 | 50.87956 |
May | 508.00000 | 27.00011 | 32.17890 | 0.50329 | 10.35666 |
June | 496.00000 | 27.00059 | 32.83461 | 0.73599 | 16.43404 |
July | 497.00000 | 27.00539 | 35.87609 | 0.97517 | 25.12260 |
August | 514.00000 | 27.01133 | 36.82310 | 1.17706 | 34.15084 |
September | 485.00000 | 27.00007 | 36.86777 | 0.56947 | 11.86694 |
October | 502.00000 | 27.00020 | 31.22688 | 1.24673 | 37.56805 |
November | 489.00000 | 27.00049 | 31.23209 | 1.38134 | 44.52708 |
December | 497.00000 | 27.00041 | 28.52533 | 1.48039 | 49.83862 |
Annual Sum or Average | 5943.00000 | 27.00175 | 32.06970 | 1.09545 | 32.18347 |
Minimum of Months | 454.00000 | 26.99998 | 28.52533 | 0.50329 | 10.35666 |
Maximum of Months | 514.00000 | 27.01133 | 36.86777 | 1.49958 | 50.87956 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55699 | 28.77209 | 0.39906 | 9.03993 |
February | 454.00000 | 24.55972 | 28.61657 | 0.40508 | 8.87478 |
March | 514.00000 | 24.52739 | 28.24823 | 0.40808 | 8.90752 |
April | 485.00000 | 24.63720 | 31.69408 | 0.46153 | 10.08831 |
May | 508.00000 | 24.62012 | 36.32828 | -0.3560 | 8.78358 |
June | 496.00000 | 24.60549 | 38.22945 | -0.3356 | 8.39972 |
July | 497.00000 | 24.75694 | 43.15899 | -0.2493 | 7.69898 |
August | 514.00000 | 24.62974 | 47.00004 | -0.2529 | 7.46640 |
September | 485.00000 | 24.69698 | 44.04377 | -0.2657 | 7.96116 |
October | 502.00000 | 24.72017 | 34.90549 | 0.50615 | 11.15925 |
November | 489.00000 | 24.69737 | 33.16000 | 0.48426 | 10.65259 |
December | 497.00000 | 24.65142 | 27.79271 | 0.42730 | 9.39661 |
Annual Sum or Average | 5943.00000 | 24.63830 | 35.21173 | 0.13310 | 9.03134 |
Minimum of Months | 454.00000 | 24.52739 | 27.79271 | -0.3560 | 7.46640 |
Maximum of Months | 514.00000 | 24.75694 | 47.00004 | 0.50615 | 11.15925 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16164 | 31.60972 | 0.32084 | 7.60864 |
February | 454.00000 | 24.25181 | 30.32558 | 0.34949 | 7.78581 |
March | 514.00000 | 24.31386 | 29.87420 | 0.38297 | 8.32202 |
April | 485.00000 | 24.32683 | 32.72224 | 0.42233 | 8.99413 |
May | 508.00000 | 24.29873 | 37.79206 | -0.4279 | 9.28994 |
June | 496.00000 | 24.28323 | 39.87347 | -0.3969 | 8.68968 |
July | 497.00000 | 24.30784 | 44.64583 | -0.3431 | 7.80285 |
August | 514.00000 | 24.23302 | 48.49725 | -0.3300 | 7.52080 |
September | 485.00000 | 24.35778 | 45.43533 | -0.3505 | 8.17926 |
October | 502.00000 | 24.38665 | 36.59726 | 0.44763 | 9.52979 |
November | 489.00000 | 24.39554 | 35.29693 | 0.43265 | 9.25276 |
December | 497.00000 | 24.37830 | 30.23634 | 0.38634 | 8.42687 |
Annual Sum or Average | 5943.00000 | 24.30782 | 36.95933 | 0.07156 | 8.45208 |
Minimum of Months | 454.00000 | 24.16164 | 29.87420 | -0.4279 | 7.52080 |
Maximum of Months | 514.00000 | 24.39554 | 48.49725 | 0.44763 | 9.52979 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82428 | 34.51212 | -0.0350 | 5.96031 |
February | 454.00000 | 23.40916 | 32.94668 | 0.11712 | 5.97791 |
March | 514.00000 | 23.88903 | 32.32054 | 0.25077 | 6.51777 |
April | 485.00000 | 24.05913 | 34.73310 | 0.32056 | 7.38567 |
May | 508.00000 | 24.13631 | 38.74610 | -0.5136 | 10.81641 |
June | 496.00000 | 24.15686 | 40.70446 | -0.4789 | 10.02008 |
July | 497.00000 | 24.22616 | 45.81219 | -0.4191 | 8.99880 |
August | 514.00000 | 24.19039 | 49.43631 | -0.3977 | 8.58853 |
September | 485.00000 | 24.20605 | 46.45202 | -0.4332 | 9.27250 |
October | 502.00000 | 24.02010 | 38.90226 | 0.33451 | 7.56350 |
November | 489.00000 | 23.71104 | 38.18418 | 0.23134 | 6.52134 |
December | 497.00000 | 23.25665 | 33.49729 | 0.07601 | 5.61849 |
Annual Sum or Average | 5943.00000 | 23.84348 | 38.89802 | -0.0812 | 7.78482 |
Minimum of Months | 454.00000 | 22.82428 | 32.32054 | -0.5136 | 5.61849 |
Maximum of Months | 514.00000 | 24.22616 | 49.43631 | 0.33451 | 10.81641 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25841 | 35.24093 | -0.4364 | 12.15685 |
February | 454.00000 | 21.91650 | 35.62465 | -0.2580 | 9.24296 |
March | 514.00000 | 22.92102 | 34.48632 | -0.0020 | 6.25015 |
April | 485.00000 | 23.50244 | 36.32428 | 0.17546 | 6.44332 |
May | 508.00000 | 23.85323 | 39.71347 | -0.6199 | 13.84607 |
June | 496.00000 | 24.05344 | 41.04442 | -0.5160 | 10.88281 |
July | 497.00000 | 24.15708 | 46.02239 | -0.4379 | 9.33083 |
August | 514.00000 | 24.11671 | 49.73444 | -0.4232 | 9.06765 |
September | 485.00000 | 23.90192 | 47.71515 | -0.5510 | 11.95589 |
October | 502.00000 | 23.18056 | 41.42178 | 0.11474 | 6.26771 |
November | 489.00000 | 22.27154 | 41.99962 | -0.1311 | 7.18717 |
December | 497.00000 | 21.54541 | 36.69552 | -0.3540 | 9.29801 |
Annual Sum or Average | 5943.00000 | 23.06576 | 40.53306 | -0.2874 | 9.32982 |
Minimum of Months | 454.00000 | 21.25841 | 34.48632 | -0.6199 | 6.25015 |
Maximum of Months | 514.00000 | 24.15708 | 49.73444 | 0.17546 | 13.84607 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.31314 | 31.83938 | -0.1596 | 6.48176 |
February | 454.00000 | 22.85661 | 31.98663 | -0.0184 | 6.21962 |
March | 514.00000 | 23.54606 | 30.91878 | 0.15380 | 5.99845 |
April | 485.00000 | 23.94485 | 32.90619 | 0.29266 | 7.17102 |
May | 508.00000 | 24.04978 | 37.42351 | -0.5346 | 11.72484 |
June | 496.00000 | 24.20005 | 39.23313 | -0.4358 | 9.38384 |
July | 497.00000 | 24.28659 | 43.90836 | -0.3503 | 7.99434 |
August | 514.00000 | 24.19815 | 47.83873 | -0.3540 | 7.96514 |
September | 485.00000 | 24.07334 | 45.47262 | -0.4873 | 10.60655 |
October | 502.00000 | 23.74063 | 37.62366 | 0.24938 | 6.72541 |
November | 489.00000 | 23.36647 | 37.14683 | 0.13947 | 6.10987 |
December | 497.00000 | 22.93700 | 32.38201 | -0.0038 | 5.50660 |
Annual Sum or Average | 5943.00000 | 23.63151 | 37.42880 | -0.1272 | 7.66640 |
Minimum of Months | 454.00000 | 22.31314 | 30.91878 | -0.5346 | 5.50660 |
Maximum of Months | 514.00000 | 24.28659 | 47.83873 | 0.29266 | 11.72484 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26330 | 31.94700 | -0.1710 | 6.59252 |
February | 454.00000 | 22.89315 | 31.90170 | -0.0046 | 6.40513 |
March | 514.00000 | 23.46831 | 30.84801 | 0.15382 | 6.22119 |
April | 485.00000 | 23.92730 | 32.67170 | 0.32586 | 7.98142 |
May | 508.00000 | 24.12876 | 37.04209 | -0.4542 | 11.03067 |
June | 496.00000 | 24.26646 | 38.83638 | -0.3410 | 8.92324 |
July | 497.00000 | 24.33933 | 43.66310 | -0.2712 | 8.03521 |
August | 514.00000 | 24.21338 | 47.67243 | -0.2786 | 8.01253 |
September | 485.00000 | 24.14049 | 45.03668 | -0.4058 | 10.03381 |
October | 502.00000 | 23.71862 | 37.44143 | 0.26458 | 7.22933 |
November | 489.00000 | 23.12475 | 37.66391 | 0.08626 | 6.13822 |
December | 497.00000 | 22.55103 | 33.03984 | -0.0903 | 5.92356 |
Annual Sum or Average | 5943.00000 | 23.59141 | 37.35212 | -0.1002 | 7.71809 |
Minimum of Months | 454.00000 | 22.26330 | 30.84801 | -0.4542 | 5.92356 |
Maximum of Months | 514.00000 | 24.33933 | 47.67243 | 0.32586 | 11.03067 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.27764 | 31.71970 | -0.1608 | 7.54626 |
February | 454.00000 | 23.10879 | 31.12200 | 0.06901 | 7.69876 |
March | 514.00000 | 23.57544 | 30.29488 | 0.20892 | 7.17691 |
April | 485.00000 | 23.98980 | 32.36255 | 0.35566 | 8.72808 |
May | 508.00000 | 24.08259 | 37.03417 | -0.4688 | 11.57585 |
June | 496.00000 | 24.24214 | 38.92778 | -0.3808 | 9.32071 |
July | 497.00000 | 24.36592 | 43.51160 | -0.2628 | 7.87577 |
August | 514.00000 | 24.27242 | 47.34821 | -0.2429 | 7.62327 |
September | 485.00000 | 24.22006 | 44.61212 | -0.3289 | 9.40962 |
October | 502.00000 | 23.88151 | 36.74686 | 0.34073 | 8.88129 |
November | 489.00000 | 23.24678 | 37.06934 | 0.12918 | 7.20439 |
December | 497.00000 | 22.74649 | 32.32262 | -0.0279 | 6.89283 |
Annual Sum or Average | 5943.00000 | 23.67146 | 36.96431 | -0.0658 | 8.33123 |
Minimum of Months | 454.00000 | 22.27764 | 30.29488 | -0.4688 | 6.89283 |
Maximum of Months | 514.00000 | 24.36592 | 47.34821 | 0.35566 | 11.57585 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23348 | 30.01696 | 0.06030 | 5.83979 |
February | 454.00000 | 23.98678 | 29.23649 | 0.27374 | 7.42754 |
March | 514.00000 | 24.31649 | 28.43041 | 0.40564 | 8.88561 |
April | 485.00000 | 24.55597 | 30.94514 | 0.55148 | 12.34744 |
May | 508.00000 | 24.40900 | 36.13944 | -0.3007 | 8.77012 |
June | 496.00000 | 24.47801 | 38.14028 | -0.2018 | 7.41444 |
July | 497.00000 | 24.67620 | 42.51482 | -0.0229 | 7.26550 |
August | 514.00000 | 24.54560 | 46.43016 | -0.0288 | 6.94954 |
September | 485.00000 | 24.46247 | 43.82224 | -0.2359 | 7.89891 |
October | 502.00000 | 24.41078 | 35.23872 | 0.46423 | 10.16687 |
November | 489.00000 | 24.33863 | 34.00382 | 0.40689 | 9.05480 |
December | 497.00000 | 24.31193 | 28.63922 | 0.35668 | 7.98384 |
Annual Sum or Average | 5943.00000 | 24.31197 | 35.34243 | 0.14240 | 8.33009 |
Minimum of Months | 454.00000 | 23.23348 | 28.43041 | -0.3007 | 5.83979 |
Maximum of Months | 514.00000 | 24.67620 | 46.43016 | 0.55148 | 12.34744 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58209 | 34.21851 | -0.6180 | 14.66482 |
February | 454.00000 | 21.12991 | 34.66210 | -0.4514 | 11.28956 |
March | 514.00000 | 22.14055 | 34.45843 | -0.1859 | 6.91690 |
April | 485.00000 | 23.00133 | 35.79073 | 0.05038 | 6.27819 |
May | 508.00000 | 23.62128 | 38.82448 | -0.7000 | 16.65848 |
June | 496.00000 | 23.94477 | 40.22975 | -0.5543 | 12.01975 |
July | 497.00000 | 24.09565 | 44.79090 | -0.4565 | 9.84671 |
August | 514.00000 | 24.01491 | 48.84911 | -0.4611 | 10.03022 |
September | 485.00000 | 23.61327 | 47.26568 | -0.6627 | 15.34548 |
October | 502.00000 | 22.56312 | 41.42579 | -0.0342 | 6.08807 |
November | 489.00000 | 21.50934 | 40.87004 | -0.3148 | 8.44115 |
December | 497.00000 | 20.82193 | 35.50472 | -0.5394 | 11.83396 |
Annual Sum or Average | 5943.00000 | 22.59838 | 39.77480 | -0.4108 | 10.78059 |
Minimum of Months | 454.00000 | 20.58209 | 34.21851 | -0.7000 | 6.08807 |
Maximum of Months | 514.00000 | 24.09565 | 48.84911 | 0.05038 | 16.65848 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.58613 | 33.56279 | -0.6172 | 14.79019 |
February | 385.00000 | 21.50531 | 33.32291 | -0.3620 | 9.90633 |
March | 433.00000 | 22.53927 | 32.92829 | -0.0815 | 6.75759 |
April | 410.00000 | 23.48810 | 33.64845 | 0.19653 | 7.43212 |
May | 430.00000 | 23.87891 | 37.40530 | -0.5657 | 14.58525 |
June | 418.00000 | 24.20544 | 38.93695 | -0.3896 | 10.39073 |
July | 422.00000 | 24.36501 | 43.48502 | -0.2971 | 8.99622 |
August | 433.00000 | 24.25367 | 47.39790 | -0.2988 | 8.88399 |
September | 410.00000 | 23.89928 | 45.62710 | -0.5144 | 13.09821 |
October | 427.00000 | 22.91134 | 39.76703 | 0.06048 | 6.64985 |
November | 417.00000 | 21.66999 | 39.86792 | -0.2789 | 8.36539 |
December | 422.00000 | 20.92004 | 34.77275 | -0.5178 | 11.65178 |
Annual Sum or Average | 5034.00000 | 22.85968 | 38.42570 | -0.3056 | 10.12632 |
Minimum of Months | 385.00000 | 20.58613 | 32.92829 | -0.6172 | 6.64985 |
Maximum of Months | 433.00000 | 24.36501 | 47.39790 | 0.19653 | 14.79019 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.39753 | 32.80724 | -0.3968 | 11.41758 |
February | 454.00000 | 22.38991 | 32.15430 | -0.1108 | 9.07509 |
March | 514.00000 | 22.98509 | 32.10716 | 0.06873 | 7.53767 |
April | 485.00000 | 23.58041 | 33.69417 | 0.24720 | 8.33852 |
May | 508.00000 | 23.85591 | 37.74543 | -0.5527 | 14.29097 |
June | 496.00000 | 24.06322 | 39.55518 | -0.4594 | 11.21641 |
July | 497.00000 | 24.26261 | 44.04400 | -0.3238 | 9.10416 |
August | 514.00000 | 24.19557 | 47.83609 | -0.2961 | 8.76586 |
September | 485.00000 | 24.05177 | 45.30289 | -0.3864 | 11.14481 |
October | 502.00000 | 23.43834 | 38.48837 | 0.23811 | 8.69311 |
November | 489.00000 | 22.37811 | 38.81696 | -0.0861 | 8.17995 |
December | 497.00000 | 21.73755 | 33.64231 | -0.2927 | 9.78138 |
Annual Sum or Average | 5943.00000 | 23.20112 | 38.05796 | -0.1971 | 9.80218 |
Minimum of Months | 454.00000 | 21.39753 | 32.10716 | -0.5527 | 7.53767 |
Maximum of Months | 514.00000 | 24.26261 | 47.83609 | 0.24720 | 14.29097 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.95652 | 33.56854 | -0.5118 | 12.11308 |
February | 454.00000 | 21.79882 | 33.27424 | -0.2770 | 9.10333 |
March | 514.00000 | 22.81006 | 32.78018 | -0.0078 | 6.69134 |
April | 485.00000 | 23.59767 | 33.97790 | 0.23342 | 7.84744 |
May | 508.00000 | 23.98152 | 37.60623 | -0.4985 | 13.07729 |
June | 496.00000 | 24.16330 | 39.36985 | -0.3961 | 9.88892 |
July | 497.00000 | 24.41602 | 43.57107 | -0.2219 | 8.13240 |
August | 514.00000 | 24.28409 | 47.64681 | -0.2570 | 8.17400 |
September | 485.00000 | 24.07647 | 45.46141 | -0.4222 | 11.05133 |
October | 502.00000 | 23.18313 | 39.53773 | 0.13245 | 6.85733 |
November | 489.00000 | 22.03720 | 39.64839 | -0.1826 | 7.45239 |
December | 497.00000 | 21.31882 | 34.56290 | -0.4062 | 9.62259 |
Annual Sum or Average | 5943.00000 | 23.06194 | 38.45288 | -0.2347 | 9.16698 |
Minimum of Months | 454.00000 | 20.95652 | 32.78018 | -0.5118 | 6.69134 |
Maximum of Months | 514.00000 | 24.41602 | 47.64681 | 0.23342 | 13.07729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07512 | 35.24658 | -0.7901 | 21.02337 |
February | 454.00000 | 20.49813 | 35.74236 | -0.6488 | 17.00732 |
March | 514.00000 | 21.34989 | 35.57303 | -0.4009 | 10.20719 |
April | 485.00000 | 22.41203 | 36.92061 | -0.1013 | 7.27281 |
May | 508.00000 | 23.23687 | 39.82294 | -0.8348 | 22.36229 |
June | 496.00000 | 23.76712 | 40.72673 | -0.6152 | 14.23116 |
July | 497.00000 | 23.97265 | 45.08406 | -0.4946 | 11.11131 |
August | 514.00000 | 23.88168 | 49.27929 | -0.5057 | 11.51999 |
September | 485.00000 | 23.17559 | 48.59836 | -0.8170 | 21.31413 |
October | 502.00000 | 21.72754 | 43.20742 | -0.2514 | 7.98648 |
November | 489.00000 | 20.70069 | 42.67358 | -0.5491 | 13.68384 |
December | 497.00000 | 20.20848 | 36.85294 | -0.7425 | 18.64169 |
Annual Sum or Average | 5943.00000 | 22.09719 | 40.84171 | -0.5622 | 14.67509 |
Minimum of Months | 454.00000 | 20.07512 | 35.24658 | -0.8348 | 7.27281 |
Maximum of Months | 514.00000 | 23.97265 | 49.27929 | -0.1013 | 22.36229 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13176 | 35.14277 | -0.7679 | 20.26596 |
February | 454.00000 | 20.86337 | 35.15228 | -0.5498 | 14.52863 |
March | 514.00000 | 21.94488 | 34.42515 | -0.2443 | 8.98586 |
April | 485.00000 | 23.09315 | 34.86906 | 0.09930 | 7.65696 |
May | 508.00000 | 23.59981 | 38.53003 | -0.6509 | 17.95883 |
June | 496.00000 | 24.06368 | 39.42189 | -0.4214 | 11.27712 |
July | 497.00000 | 24.22130 | 44.10086 | -0.3214 | 9.48457 |
August | 514.00000 | 24.12296 | 48.14017 | -0.3213 | 9.44490 |
September | 485.00000 | 23.55289 | 47.05325 | -0.6242 | 17.01105 |
October | 502.00000 | 22.26536 | 41.57791 | -0.1078 | 7.72272 |
November | 489.00000 | 20.88918 | 42.21232 | -0.4992 | 12.88552 |
December | 497.00000 | 20.29459 | 36.69624 | -0.7127 | 17.79435 |
Annual Sum or Average | 5943.00000 | 22.43329 | 39.80621 | -0.4261 | 12.89902 |
Minimum of Months | 454.00000 | 20.13176 | 34.42515 | -0.7679 | 7.65696 |
Maximum of Months | 514.00000 | 24.22130 | 48.14017 | 0.09930 | 20.26596 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.69957 | 34.12252 | -0.6051 | 16.96321 |
February | 454.00000 | 21.63886 | 33.35898 | -0.3302 | 12.24147 |
March | 514.00000 | 22.32133 | 33.12271 | -0.1185 | 9.25405 |
April | 485.00000 | 23.12167 | 34.60752 | 0.12256 | 8.58755 |
May | 508.00000 | 23.52433 | 38.59845 | -0.6721 | 19.14184 |
June | 496.00000 | 23.88959 | 40.01394 | -0.5187 | 13.41079 |
July | 497.00000 | 24.14029 | 44.33527 | -0.3613 | 10.36832 |
August | 514.00000 | 24.07648 | 48.23424 | -0.3359 | 10.06653 |
September | 485.00000 | 23.72367 | 46.31821 | -0.5082 | 15.23528 |
October | 502.00000 | 22.79861 | 39.83645 | 0.06135 | 8.84834 |
November | 489.00000 | 21.51784 | 40.73330 | -0.3283 | 11.34337 |
December | 497.00000 | 20.95146 | 35.29779 | -0.5266 | 15.07847 |
Annual Sum or Average | 5943.00000 | 22.70924 | 39.08632 | -0.3439 | 12.54747 |
Minimum of Months | 454.00000 | 20.69957 | 33.12271 | -0.6721 | 8.58755 |
Maximum of Months | 514.00000 | 24.14029 | 48.23424 | 0.12256 | 19.14184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35414 | 34.72309 | -0.6935 | 18.09811 |
February | 454.00000 | 21.13674 | 34.38207 | -0.4669 | 13.15747 |
March | 514.00000 | 22.11604 | 33.79202 | -0.1938 | 8.48936 |
April | 485.00000 | 23.10995 | 34.94793 | 0.10740 | 8.04760 |
May | 508.00000 | 23.68315 | 38.39497 | -0.6058 | 17.20231 |
June | 496.00000 | 24.01928 | 39.77426 | -0.4463 | 11.57993 |
July | 497.00000 | 24.31941 | 43.79949 | -0.2519 | 8.97249 |
August | 514.00000 | 24.19215 | 47.97198 | -0.2893 | 9.10225 |
September | 485.00000 | 23.76821 | 46.43833 | -0.5361 | 14.75340 |
October | 502.00000 | 22.48468 | 41.01112 | -0.0493 | 7.36275 |
November | 489.00000 | 21.24009 | 41.34466 | -0.4013 | 10.75415 |
December | 497.00000 | 20.65344 | 35.93540 | -0.6048 | 14.63610 |
Annual Sum or Average | 5943.00000 | 22.60172 | 39.40864 | -0.3689 | 11.83410 |
Minimum of Months | 454.00000 | 20.35414 | 33.79202 | -0.6935 | 7.36275 |
Maximum of Months | 514.00000 | 24.31941 | 47.97198 | 0.10740 | 18.09811 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.138302E+09 | 2557.84 | 11-JAN-07:14 | 53.45 | 0.114994E+10 | 0.00 | 0.128824E+10 | 0.60 | 8.40 | 06-JAN-06:50 | 0.00 | 0.00 |
February | 0.258965E+10 | 81684.00 | 27-FEB-15:05 | 106.12 | 0.214915E+11 | 0.00 | 0.240811E+11 | 1.31 | 8.66 | 27-FEB-13:00 | 0.00 | 0.00 |
March | 0.814785E+10 | 70473.68 | 14-MAR-16:00 | 166.64 | 0.685549E+11 | 0.00 | 0.767028E+11 | 1.87 | 8.68 | 01-MAR-14:00 | 0.00 | 0.00 |
April | 0.132145E+11 | 156607.94 | 27-APR-17:10 | 152.90 | 0.106735E+12 | 0.00 | 0.119950E+12 | 1.76 | 8.68 | 19-APR-15:50 | 0.00 | 0.00 |
May | 0.215507E+11 | 159337.42 | 31-MAY-15:50 | 225.69 | 0.173634E+12 | 0.00 | 0.195185E+12 | 2.51 | 8.68 | 14-MAY-17:02 | 0.00 | 0.00 |
June | 0.393448E+11 | 158760.36 | 20-JUN-13:05 | 342.38 | 0.314498E+12 | 0.00 | 0.353843E+12 | 3.92 | 8.68 | 19-JUN-11:30 | 0.00 | 0.00 |
July | 0.660809E+11 | 161142.09 | 11-JUL-15:00 | 467.12 | 0.520582E+12 | 0.00 | 0.586663E+12 | 5.14 | 8.68 | 30-JUL-13:26 | 0.00 | 0.00 |
August | 0.786909E+11 | 161013.90 | 25-AUG-10:00 | 526.87 | 0.608349E+12 | 0.00 | 0.687040E+12 | 5.74 | 8.68 | 10-AUG-05:03 | 0.00 | 0.00 |
September | 0.337586E+11 | 160008.97 | 12-SEP-12:40 | 308.90 | 0.268305E+12 | 0.00 | 0.302064E+12 | 3.53 | 8.68 | 13-SEP-09:10 | 0.00 | 0.00 |
October | 0.121264E+11 | 148060.70 | 04-OCT-14:20 | 138.24 | 0.999698E+11 | 0.00 | 0.112096E+12 | 1.55 | 8.68 | 02-OCT-11:50 | 0.00 | 0.00 |
November | 0.208756E+10 | 55923.65 | 04-NOV-14:10 | 120.88 | 0.175218E+11 | 0.00 | 0.196094E+11 | 1.40 | 8.67 | 04-NOV-15:50 | 0.00 | 0.00 |
December | 0.876658E+09 | 7511.79 | 16-DEC-07:13 | 138.46 | 0.729685E+10 | 0.00 | 0.817350E+10 | 1.55 | 8.40 | 05-DEC-16:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278607E+12 | 2747.67 | 0.220809E+13 | 0.00 | 0.248669E+13 | 2.58 | 0.00 | 0.00 | ||||
Minimum of Months | 0.138302E+09 | 2557.84 | 53.45 | 0.114994E+10 | 0.00 | 0.128824E+10 | 0.60 | 8.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.786909E+11 | 161142.09 | 526.87 | 0.608349E+12 | 0.00 | 0.687040E+12 | 5.74 | 8.68 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.193802E+10 | 85555.39 | 27-APR-14:40 | 7.33 | 0.153949E+11 | 0.00 | 0.173329E+11 | 0.08 | 8.63 | 27-APR-11:50 | 0.00 | 0.00 |
May | 0.191547E+10 | 129764.95 | 04-MAY-14:05 | 7.92 | 0.154520E+11 | 0.00 | 0.173674E+11 | 0.09 | 8.64 | 15-MAY-12:20 | 0.00 | 0.00 |
June | 0.340949E+10 | 124577.12 | 21-JUN-14:05 | 14.00 | 0.274168E+11 | 0.00 | 0.308263E+11 | 0.16 | 8.67 | 21-JUN-14:00 | 0.00 | 0.00 |
July | 0.112324E+11 | 119876.84 | 31-JUL-16:00 | 42.00 | 0.869970E+11 | 0.00 | 0.982295E+11 | 0.44 | 8.96 | 19-JUL-13:30 | 0.00 | 0.00 |
August | 0.256592E+11 | 129666.85 | 29-AUG-14:30 | 87.58 | 0.194047E+12 | 0.00 | 0.219706E+12 | 0.90 | 8.53 | 23-AUG-17:30 | 0.00 | 0.00 |
September | 0.436203E+10 | 126655.58 | 11-SEP-15:25 | 17.67 | 0.347985E+11 | 0.00 | 0.391605E+11 | 0.20 | 8.50 | 11-SEP-16:20 | 0.00 | 0.00 |
October | 0.159546E+09 | 67509.62 | 04-OCT-15:10 | 0.83 | 0.129060E+10 | 0.00 | 0.145015E+10 | 0.01 | 8.62 | 04-OCT-14:30 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.486763E+11 | 177.33 | 0.375397E+12 | 0.00 | 0.424073E+12 | 0.16 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.256592E+11 | 129764.95 | 87.58 | 0.194047E+12 | 0.00 | 0.219706E+12 | 0.90 | 8.96 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.751376E+09 | 744.00 | 1399.07 | 11-JAN-15:30 | 32930.79 | 12-JAN-20:20 | 18.62 | 18.33 | 15.73 |
February | 0.305700E+10 | 672.00 | 43776.24 | 27-FEB-13:15 | 81995.08 | 27-FEB-15:05 | 19.24 | 18.34 | 15.73 |
March | 0.579249E+10 | 744.00 | 43776.24 | 18-MAR-13:05 | 253581.12 | 18-MAR-16:01 | 19.87 | 18.35 | 15.74 |
April | 0.181654E+11 | 720.00 | 43776.24 | 01-APR-10:30 | 663412.68 | 27-APR-16:00 | 21.45 | 18.79 | 15.74 |
May | 0.180775E+11 | 744.00 | 43776.24 | 02-MAY-15:40 | 147943.64 | 05-MAY-16:00 | 19.31 | 18.71 | 15.73 |
June | 0.358690E+11 | 720.00 | 43776.24 | 01-JUN-14:20 | 349762.70 | 28-JUN-17:00 | 20.55 | 19.17 | 15.73 |
July | 0.606972E+11 | 744.00 | 43776.24 | 01-JUL-12:30 | 561951.19 | 31-JUL-18:00 | 24.01 | 20.59 | 15.74 |
August | 0.849890E+11 | 744.00 | 43776.24 | 01-AUG-00:03 | 738720.34 | 25-AUG-15:00 | 28.94 | 22.23 | 15.74 |
September | 0.249028E+11 | 720.00 | 43776.24 | 01-SEP-14:20 | 149352.10 | 22-SEP-16:00 | 19.43 | 18.82 | 15.74 |
October | 0.813001E+10 | 744.00 | 43776.24 | 03-OCT-12:40 | 157073.89 | 04-OCT-15:00 | 19.37 | 18.37 | 15.74 |
November | 0.539957E+10 | 720.00 | 43776.24 | 04-NOV-10:50 | 316543.95 | 04-NOV-15:00 | 19.80 | 18.36 | 15.74 |
December | 0.444864E+10 | 744.00 | 3591.92 | 14-DEC-12:00 | 118351.00 | 05-DEC-16:00 | 20.21 | 18.33 | 15.74 |
Annual Sum or Average | 0.270280E+12 | 8760.00 | 20.92 | 19.04 | 15.73 | ||||
Minimum of Months | 0.751376E+09 | 672.00 | 1399.07 | 32930.79 | 18.62 | 18.33 | 15.73 | ||
Maximum of Months | 0.849890E+11 | 744.00 | 43776.24 | 738720.34 | 28.94 | 22.23 | 15.74 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 197097.44 | 06-JAN-05:07 | 20.99 | 20.99 | 0.25 |
February | 15021154.40 | 8.83 | 1271.93 | 27-FEB-15:30 | 727988.72 | 27-FEB-15:10 | 20.98 | 20.93 | 2.75 |
March | 24201502.40 | 59.93 | 785.01 | 14-MAR-16:00 | 654108.48 | 14-MAR-16:00 | 21.15 | 21.00 | 6.75 |
April | 0.418590E+09 | 80.48 | 14553.39 | 27-APR-11:40 | 1080964.43 | 27-APR-17:20 | 21.40 | 21.16 | 8.14 |
May | 0.684250E+09 | 138.35 | 14553.39 | 04-MAY-13:00 | 1126746.19 | 31-MAY-15:50 | 21.58 | 21.21 | 12.71 |
June | 0.114850E+10 | 238.20 | 14553.39 | 20-JUN-12:20 | 1145713.45 | 20-JUN-13:05 | 21.82 | 21.13 | 20.87 |
July | 0.446509E+10 | 334.22 | 14553.39 | 06-JUL-15:40 | 1093017.37 | 21-JUL-16:00 | 22.25 | 21.17 | 27.58 |
August | 0.750084E+10 | 367.41 | 14553.39 | 07-AUG-09:30 | 1095688.80 | 07-AUG-18:00 | 22.53 | 21.27 | 30.08 |
September | 0.204882E+10 | 204.07 | 14553.39 | 11-SEP-12:50 | 1153739.66 | 12-SEP-12:50 | 21.79 | 21.21 | 18.75 |
October | 84225408.59 | 85.34 | 1911.30 | 04-OCT-14:30 | 1103525.32 | 04-OCT-13:40 | 21.26 | 21.05 | 7.59 |
November | 27814462.83 | 12.33 | 1817.60 | 04-NOV-14:20 | 541067.29 | 04-NOV-14:10 | 21.03 | 20.99 | 2.26 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 197221.28 | 26-DEC-06:50 | 20.99 | 20.97 | 1.59 |
Annual Sum or Average | 0.164174E+11 | 1529.18 | 21.49 | 21.09 | 11.67 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 197097.44 | 20.98 | 20.93 | 0.25 | ||
Maximum of Months | 0.750084E+10 | 367.41 | 14553.39 | 1153739.66 | 22.53 | 21.27 | 30.08 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.99 | 20.99 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.98 | 20.98 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.15 | 21.15 | 0.00 |
April | 0.196526E+09 | 6.42 | 14553.39 | 27-APR-12:20 | 978234.25 | 26-APR-15:00 | 21.40 | 21.36 | 0.45 |
May | 75572349.95 | 4.25 | 14553.39 | 04-MAY-14:00 | 1004812.75 | 04-MAY-14:05 | 21.58 | 21.56 | 0.29 |
June | 0.178837E+09 | 12.25 | 14553.39 | 20-JUN-13:40 | 1008885.73 | 22-JUN-14:50 | 21.82 | 21.75 | 0.86 |
July | 0.164074E+10 | 35.42 | 14553.39 | 07-JUL-12:30 | 955469.64 | 18-JUL-14:05 | 22.25 | 22.07 | 2.41 |
August | 0.393426E+10 | 78.58 | 14553.39 | 07-AUG-10:30 | 989992.40 | 21-AUG-15:00 | 22.53 | 22.14 | 5.36 |
September | 0.671110E+09 | 13.58 | 14553.39 | 11-SEP-15:25 | 1053721.10 | 11-SEP-15:25 | 21.79 | 21.72 | 0.96 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.26 | 21.26 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.03 | 21.03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.99 | 20.99 | 0.00 |
Annual Sum or Average | 0.669704E+10 | 150.50 | 21.49 | 21.42 | 0.87 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 | 20.98 | 0.00 | ||
Maximum of Months | 0.393426E+10 | 78.58 | 14553.39 | 1053721.10 | 22.53 | 22.14 | 5.36 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.266835E+12 | 0.00 | 466.25 | 1286711.37 | 02-JAN-06:03 | 0.00 | 34.30 | 63.99 | 0.52 | 0.00 | 0.06 | 0.76 | 02-JAN-06:03 |
February | 0.146528E+12 | 0.00 | 342.66 | 979699.44 | 15-FEB-06:02 | 0.00 | 30.92 | 56.28 | 0.31 | 0.00 | 0.04 | 0.58 | 15-FEB-06:02 |
March | 0.592452E+11 | 0.00 | 296.44 | 926247.28 | 06-MAR-06:02 | 0.00 | 27.82 | 49.27 | 0.10 | 0.00 | 0.01 | 0.55 | 06-MAR-06:02 |
April | 0.254784E+11 | 0.00 | 174.90 | 350590.30 | 03-APR-13:20 | 0.00 | 27.21 | 40.29 | 0.04 | 0.00 | 0.01 | 0.21 | 03-APR-13:20 |
May | 0.652918E+10 | 0.00 | 68.84 | 285163.83 | 17-MAY-13:10 | 0.00 | 26.14 | 31.28 | 0.01 | 0.00 | 0.00 | 0.17 | 17-MAY-13:10 |
June | 0.304543E+09 | 0.00 | 10.60 | 192785.50 | 13-JUN-09:20 | 0.00 | 26.53 | 27.33 | 0.00 | 0.00 | 0.00 | 0.11 | 13-JUN-09:20 |
July | 72197734.44 | 0.00 | 0.33 | 114609.62 | 12-JUL-09:20 | 0.00 | 27.20 | 27.22 | 0.00 | 0.00 | 0.00 | 0.07 | 12-JUL-09:20 |
August | 60002624.20 | 0.00 | 0.17 | 133347.78 | 03-AUG-09:05 | 0.00 | 28.05 | 28.06 | 0.00 | 0.00 | 0.00 | 0.08 | 03-AUG-09:05 |
September | 0.112161E+10 | 0.00 | 25.38 | 248533.80 | 27-SEP-09:20 | 0.00 | 27.26 | 29.19 | 0.00 | 0.00 | 0.00 | 0.15 | 27-SEP-09:20 |
October | 0.139294E+11 | 0.00 | 168.77 | 409461.33 | 30-OCT-05:03 | 0.00 | 25.32 | 38.05 | 0.02 | 0.00 | 0.00 | 0.24 | 30-OCT-05:03 |
November | 0.988732E+11 | 0.00 | 315.40 | 1030791.32 | 24-NOV-05:11 | 0.00 | 28.31 | 51.55 | 0.18 | 0.00 | 0.02 | 0.61 | 24-NOV-05:11 |
December | 0.201591E+12 | 0.00 | 418.38 | 1130970.57 | 18-DEC-05:11 | 0.00 | 31.34 | 59.69 | 0.38 | 0.00 | 0.04 | 0.67 | 18-DEC-05:11 |
Annual Sum or Average | 0.820568E+12 | 0.00 | 2288.13 | 0.00 | 28.36 | 41.78 | 0.13 | 0.00 | 0.02 | ||||
Minimum of Months | 60002624.20 | 0.00 | 0.17 | 114609.62 | 0.00 | 25.32 | 27.22 | 0.00 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.266835E+12 | 0.00 | 466.25 | 1286711.37 | 0.00 | 34.30 | 63.99 | 0.52 | 0.00 | 0.06 | 0.76 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.62 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.24 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.87 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.45 | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.31 | 19.31 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.55 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 24.01 | 24.01 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 28.94 | 28.94 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 19.43 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.37 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.80 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.21 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 28.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.662817E+09 | 0.00 | 39.58 | 0.662817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18269.41 | 20-JAN-13:30 | 18269.41 | 20-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.484643E+10 | 0.00 | 76.82 | 0.484643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54544.12 | 27-FEB-15:00 | 54544.12 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.555053E+10 | 0.00 | 102.28 | 0.555053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50819.24 | 02-MAR-13:05 | 50819.24 | 02-MAR-13:05 | 0.00 | 0.00 | 0.00 |
April | 0.103958E+11 | 0.00 | 106.94 | 0.103958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120823.86 | 27-APR-14:40 | 120823.86 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.160577E+11 | 0.00 | 181.97 | 0.160521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97110.43 | 04-MAY-15:00 | 97110.43 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.314536E+11 | 0.00 | 295.58 | 0.314473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108733.24 | 28-JUN-15:20 | 108733.24 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.572943E+11 | 0.00 | 425.30 | 0.565424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142506.68 | 31-JUL-15:40 | 130390.44 | 31-JUL-15:10 | 0.00 | 0.00 | 0.00 |
August | 0.778205E+11 | 0.00 | 493.96 | 0.756300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147818.13 | 29-AUG-14:30 | 134791.38 | 29-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.249290E+11 | 0.00 | 250.77 | 0.245608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124308.12 | 11-SEP-15:25 | 124308.12 | 11-SEP-15:25 | 0.00 | 0.00 | 0.00 |
October | 0.465388E+10 | 0.00 | 77.50 | 0.465388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75816.72 | 04-OCT-15:00 | 75816.72 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.496308E+10 | 0.00 | 101.38 | 0.496308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41919.84 | 15-NOV-14:00 | 41919.84 | 15-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.583333E+10 | 0.00 | 128.36 | 0.583333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46213.73 | 05-DEC-14:30 | 46213.73 | 05-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244461E+12 | 0.00 | 2280.43 | 0.241138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.662817E+09 | 0.00 | 39.58 | 0.662817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18269.41 | 18269.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.778205E+11 | 0.00 | 493.96 | 0.756300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147818.13 | 134791.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 30746.79 | 0.00 | 10.25 | 30746.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 02-JAN-07:00 | 2.46 | 02-JAN-07:00 | 0.00 | 0.00 | 0.00 |
February | 0.142385E+11 | 0.00 | 36.87 | 0.142385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 537474.20 | 27-FEB-15:05 | 537474.20 | 27-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.598878E+11 | 0.00 | 100.56 | 0.598878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 520792.56 | 14-MAR-15:40 | 520792.56 | 14-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.966835E+11 | 0.00 | 128.30 | 0.966835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1021709.20 | 27-APR-14:40 | 1021709.20 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.146480E+12 | 0.00 | 191.23 | 0.146420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 915515.04 | 04-MAY-15:00 | 915515.04 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.258587E+12 | 0.00 | 292.52 | 0.258563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 973877.44 | 28-JUN-15:20 | 973877.44 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.453434E+12 | 0.00 | 381.67 | 0.449046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1237752.84 | 31-JUL-16:00 | 1118556.51 | 31-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.599350E+12 | 0.00 | 398.90 | 0.584434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1305463.20 | 29-AUG-14:30 | 1210309.55 | 29-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.235719E+12 | 0.00 | 261.88 | 0.231243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1102687.18 | 11-SEP-15:25 | 1041412.31 | 11-SEP-15:25 | 0.00 | 0.00 | 0.00 |
October | 0.881890E+11 | 0.00 | 121.35 | 0.881890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 723952.10 | 04-OCT-13:20 | 723952.10 | 04-OCT-13:20 | 0.00 | 0.00 | 0.00 |
November | 0.103491E+11 | 0.00 | 27.89 | 0.103491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 392871.01 | 04-NOV-14:05 | 392871.01 | 04-NOV-14:05 | 0.00 | 0.00 | 0.00 |
December | 28104.41 | 0.00 | 9.82 | 28104.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 26-DEC-06:02 | 2.99 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196292E+13 | 0.00 | 1961.24 | 0.193905E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 28104.41 | 0.00 | 9.82 | 28104.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 2.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.599350E+12 | 0.00 | 398.90 | 0.584434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1305463.20 | 1210309.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.390035E+09 | 0.00 | 10.42 | 0.390035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27486.27 | 27-FEB-15:00 | 27486.27 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.101644E+10 | 0.00 | 31.30 | 0.101644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33301.00 | 01-MAR-15:00 | 33301.00 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.764622E+10 | 0.00 | 80.78 | 0.764622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119309.40 | 27-APR-14:40 | 119309.40 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.141105E+11 | 0.00 | 169.23 | 0.141086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100532.12 | 04-MAY-15:00 | 100532.12 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.268694E+11 | 0.00 | 280.26 | 0.268676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116132.20 | 28-JUN-15:20 | 116132.20 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.481077E+11 | 0.00 | 367.41 | 0.477006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142173.58 | 31-JUL-16:00 | 131635.89 | 31-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.632128E+11 | 0.00 | 388.53 | 0.618101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146685.64 | 10-AUG-15:40 | 140257.68 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.215210E+11 | 0.00 | 237.42 | 0.212331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111213.88 | 11-SEP-15:25 | 111213.88 | 11-SEP-15:25 | 0.00 | 0.00 | 0.00 |
October | 0.309679E+10 | 0.00 | 60.65 | 0.309679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66071.09 | 04-OCT-15:00 | 66071.09 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.516383E+09 | 0.00 | 9.83 | 0.516383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29528.85 | 04-NOV-14:10 | 29528.85 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 26462.81 | 0.00 | 0.02 | 26462.81 | 0.00 | 0.00 | 0.00 | 0.00 | 441.05 | 26-DEC-05:01 | 441.05 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186487E+12 | 0.00 | 1635.85 | 0.184386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.632128E+11 | 0.00 | 388.53 | 0.618101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146685.64 | 140257.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 44228642.85 | 0.00 | 5.23 | 44228642.85 | 0.00 | 0.00 | 0.00 | 0.00 | 7411.38 | 11-JAN-07:14 | 7411.38 | 11-JAN-07:14 | 0.00 | 0.00 | 0.00 |
February | 0.969962E+09 | 0.00 | 31.10 | 0.883147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45234.39 | 24-FEB-07:12 | 34568.59 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.674618E+09 | 0.00 | 29.33 | 0.668730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34735.90 | 10-MAR-07:13 | 20151.57 | 09-MAR-07:13 | 0.00 | 0.00 | 0.00 |
April | 0.456647E+10 | 0.00 | 59.21 | 0.455548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58214.48 | 27-APR-15:00 | 58214.48 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.970129E+10 | 0.00 | 139.06 | 0.965838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57941.51 | 15-MAY-16:00 | 57941.51 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.206019E+11 | 0.00 | 253.10 | 0.200158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60255.75 | 12-JUN-06:35 | 54056.69 | 20-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.374619E+11 | 0.00 | 323.88 | 0.350854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96175.88 | 31-JUL-10:10 | 74507.27 | 24-JUL-11:00 | 0.00 | 0.00 | 0.00 |
August | 0.481420E+11 | 0.00 | 351.14 | 0.456342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79037.71 | 07-AUG-12:05 | 78128.18 | 21-AUG-15:05 | 0.00 | 0.00 | 0.00 |
September | 0.172572E+11 | 0.00 | 228.31 | 0.166330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76932.25 | 11-SEP-15:25 | 74437.60 | 11-SEP-15:25 | 0.00 | 0.00 | 0.00 |
October | 0.288060E+10 | 0.00 | 63.88 | 0.282953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41515.20 | 04-OCT-15:00 | 41515.20 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.560913E+09 | 0.00 | 12.02 | 0.540625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38483.62 | 04-NOV-06:14 | 24654.03 | 06-NOV-07:25 | 0.00 | 0.00 | 0.00 |
December | 9118321.70 | 0.00 | 0.28 | 7223948.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22536.97 | 16-DEC-07:13 | 13587.33 | 16-DEC-07:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142870E+12 | 0.00 | 1496.55 | 0.136556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9118321.70 | 0.00 | 0.28 | 7223948.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7411.38 | 7411.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.481420E+11 | 0.00 | 351.14 | 0.456342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96175.88 | 78128.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.451994E+10 | 0.370919E+10 | 740.92 | 0.451991E+10 | 24252.20 | 0.00 | 0.02 | 09-JAN-12:00 | 0.01 | 11-JAN-22:40 | 3119.97 | 09-JAN-12:00 | 3119.97 | 09-JAN-12:00 | 8.35 | 11-JAN-23:00 | 1747.42 | 09-JAN-12:00 | 0.00 |
February | 0.679760E+10 | 0.412479E+10 | 597.87 | 0.676016E+10 | 37442340.00 | 0.00 | 0.06 | 27-FEB-15:00 | 0.01 | 28-FEB-08:65 | 18252.01 | 27-FEB-15:00 | 18252.01 | 27-FEB-15:00 | 69.41 | 26-FEB-16:40 | 6092.76 | 27-FEB-15:00 | 0.00 |
March | 0.118246E+11 | 0.582800E+10 | 689.88 | 0.114416E+11 | 0.383008E+09 | 0.00 | 0.36 | 18-MAR-16:00 | 0.01 | 11-MAR-06:02 | 126263.66 | 18-MAR-16:00 | 126263.66 | 18-MAR-16:00 | 4681.13 | 09-MAR-12:00 | 37958.10 | 18-MAR-16:00 | 0.00 |
April | 0.766841E+11 | 0.238198E+11 | 629.46 | 0.723599E+11 | 0.432416E+10 | 0.00 | 1.00 | 01-APR-16:25 | 0.01 | 02-APR-22:40 | 408346.75 | 27-APR-16:00 | 408346.75 | 27-APR-16:00 | 61327.91 | 28-APR-13:00 | 129862.29 | 01-APR-16:25 | 0.00 |
May | 0.430446E+10 | 0.383360E+10 | 491.93 | 0.407864E+10 | 0.225816E+09 | 0.00 | 0.21 | 05-MAY-16:00 | 0.01 | 26-MAY-10:05 | 84113.33 | 05-MAY-16:00 | 72610.43 | 05-MAY-16:00 | 11502.89 | 05-MAY-16:00 | 24969.32 | 05-MAY-16:00 | 0.00 |
June | 0.331722E+11 | 0.122768E+11 | 375.93 | 0.316610E+11 | 0.151122E+10 | 0.00 | 0.52 | 28-JUN-17:00 | 0.00 | 19-JUN-00:40 | 214401.62 | 28-JUN-17:00 | 214401.62 | 28-JUN-17:00 | 16922.20 | 21-JUN-17:00 | 64863.59 | 28-JUN-17:00 | 0.00 |
July | 0.208486E+12 | 0.592265E+11 | 564.95 | 0.177262E+12 | 0.312237E+11 | 0.00 | 0.78 | 31-JUL-17:50 | 0.01 | 19-JUL-22:40 | 357081.26 | 27-JUL-16:00 | 318322.62 | 24-JUL-15:00 | 84851.24 | 27-JUL-18:50 | 104382.47 | 24-JUL-15:00 | 0.00 |
August | 0.534071E+12 | 0.143263E+12 | 684.58 | 0.426856E+12 | 0.107215E+12 | 0.00 | 1.00 | 24-AUG-12:05 | 0.01 | 31-AUG-23:25 | 473401.08 | 29-AUG-11:00 | 411051.13 | 29-AUG-12:05 | 158390.79 | 30-AUG-09:00 | 136475.63 | 10-AUG-17:00 | 0.00 |
September | 0.339362E+10 | 0.389142E+10 | 233.21 | 0.286077E+10 | 0.532846E+09 | 0.00 | 0.22 | 22-SEP-16:00 | 0.01 | 28-SEP-21:03 | 86201.97 | 22-SEP-16:00 | 73177.16 | 22-SEP-16:00 | 13024.81 | 22-SEP-16:00 | 25437.91 | 22-SEP-16:00 | 0.00 |
October | 0.380186E+10 | 0.372642E+10 | 501.66 | 0.372578E+10 | 76086205.53 | 0.00 | 0.21 | 04-OCT-15:00 | 0.01 | 25-OCT-08:25 | 71684.43 | 04-OCT-15:00 | 71684.43 | 04-OCT-15:00 | 2258.12 | 08-OCT-13:52 | 22369.58 | 04-OCT-15:00 | 0.00 |
November | 0.997547E+10 | 0.518603E+10 | 550.38 | 0.866579E+10 | 0.130968E+10 | 0.00 | 0.44 | 04-NOV-14:10 | 0.01 | 01-NOV-21:30 | 180788.58 | 04-NOV-14:10 | 135467.22 | 04-NOV-14:10 | 49531.40 | 04-NOV-13:00 | 47533.52 | 04-NOV-15:00 | 0.00 |
December | 0.130203E+11 | 0.626312E+10 | 721.90 | 0.121201E+11 | 0.900175E+09 | 0.00 | 0.03 | 13-DEC-24:00 | 0.01 | 29-DEC-00:10 | 6025.50 | 27-DEC-00:40 | 5621.12 | 04-DEC-05:11 | 608.41 | 10-DEC-21:30 | 2646.03 | 18-DEC-19:40 | 0.00 |
Annual Sum or Average | 0.910050E+12 | 0.275149E+12 | 6782.67 | 0.762311E+12 | 0.147739E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.339362E+10 | 0.370919E+10 | 233.21 | 0.286077E+10 | 24252.20 | 0.00 | 0.02 | 0.00 | 3119.97 | 3119.97 | 8.35 | 1747.42 | 0.00 | ||||||
Maximum of Months | 0.534071E+12 | 0.143263E+12 | 740.92 | 0.426856E+12 | 0.107215E+12 | 0.00 | 1.00 | 0.01 | 473401.08 | 411051.13 | 158390.79 | 136475.63 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.407884E+10 | 0.979488E+09 | 744.00 | 0.407851E+10 | 326849.25 | 0.00 | 0.27 | 08-JAN-16:15 | 0.12 | 07-JAN-08:00 | 2127.82 | 08-JAN-16:15 | 2127.82 | 08-JAN-16:15 | 16.34 | 02-JAN-07:05 | 509.92 | 08-JAN-16:15 | 0.00 |
February | 0.879396E+10 | 0.196192E+10 | 672.00 | 0.878354E+10 | 10423281.98 | 0.00 | 0.54 | 12-FEB-16:45 | 0.37 | 18-FEB-08:00 | 4449.77 | 12-FEB-16:45 | 4449.77 | 12-FEB-16:45 | 128.12 | 24-FEB-11:10 | 1007.82 | 12-FEB-16:45 | 0.00 |
March | 0.152870E+11 | 0.324094E+10 | 744.00 | 0.152789E+11 | 8065868.49 | 0.00 | 0.81 | 31-MAR-24:00 | 0.58 | 01-MAR-07:05 | 7574.12 | 31-MAR-24:00 | 7574.12 | 31-MAR-24:00 | 136.81 | 09-MAR-17:00 | 1518.65 | 31-MAR-24:00 | 0.00 |
April | 0.199884E+11 | 0.409177E+10 | 720.00 | 0.199748E+11 | 13662674.14 | 0.00 | 0.99 | 01-APR-17:32 | 0.30 | 30-APR-24:00 | 8685.55 | 23-APR-18:03 | 8685.55 | 23-APR-18:03 | 167.24 | 28-APR-13:00 | 2439.23 | 01-APR-17:02 | 0.00 |
May | 0.561126E+10 | 0.129190E+10 | 744.00 | 0.557495E+10 | 36311755.53 | 0.00 | 0.46 | 31-MAY-24:00 | 0.18 | 18-MAY-06:05 | 4018.83 | 31-MAY-24:00 | 4010.92 | 31-MAY-24:00 | 132.35 | 05-MAY-17:00 | 851.31 | 31-MAY-24:00 | 0.00 |
June | 0.105490E+11 | 0.231340E+10 | 720.00 | 0.104970E+11 | 52060233.64 | 0.00 | 0.64 | 30-JUN-24:00 | 0.42 | 07-JUN-06:10 | 5888.96 | 30-JUN-24:00 | 5887.11 | 30-JUN-24:00 | 194.08 | 12-JUN-15:00 | 1279.61 | 28-JUN-17:00 | 0.00 |
July | 0.162641E+11 | 0.356953E+10 | 744.00 | 0.161491E+11 | 0.115001E+09 | 0.00 | 0.85 | 30-JUL-18:31 | 0.61 | 01-JUL-07:00 | 7864.50 | 31-JUL-23:55 | 7835.07 | 31-JUL-24:00 | 246.14 | 11-JUL-10:00 | 2056.83 | 30-JUL-18:01 | 0.00 |
August | 0.212835E+11 | 0.475402E+10 | 744.00 | 0.211227E+11 | 0.160804E+09 | 0.00 | 1.00 | 06-AUG-18:01 | 0.29 | 31-AUG-24:00 | 9269.74 | 06-AUG-18:41 | 9269.74 | 06-AUG-18:41 | 277.51 | 30-AUG-08:00 | 2731.94 | 10-AUG-17:40 | 0.00 |
September | 0.559983E+10 | 0.127464E+10 | 720.00 | 0.550915E+10 | 90686769.88 | 0.00 | 0.44 | 30-SEP-24:00 | 0.19 | 28-SEP-06:05 | 3897.99 | 30-SEP-24:00 | 3896.94 | 30-SEP-24:00 | 173.33 | 14-SEP-11:00 | 828.45 | 30-SEP-24:00 | 0.00 |
October | 0.104255E+11 | 0.224767E+10 | 744.00 | 0.104028E+11 | 22721046.94 | 0.00 | 0.63 | 31-OCT-24:00 | 0.39 | 28-OCT-07:00 | 5616.72 | 31-OCT-24:00 | 5616.72 | 31-OCT-24:00 | 135.98 | 26-OCT-14:10 | 1168.67 | 31-OCT-24:00 | 0.00 |
November | 0.147019E+11 | 0.306932E+10 | 720.00 | 0.146783E+11 | 23593369.15 | 0.00 | 0.71 | 11-NOV-15:55 | 0.59 | 24-NOV-07:05 | 6404.48 | 11-NOV-15:55 | 6404.48 | 11-NOV-15:55 | 165.38 | 03-NOV-16:00 | 1425.25 | 04-NOV-15:50 | 0.00 |
December | 0.200314E+11 | 0.411159E+10 | 744.00 | 0.200290E+11 | 2451667.76 | 0.00 | 0.91 | 03-DEC-15:25 | 0.77 | 18-DEC-07:05 | 8191.42 | 10-DEC-15:35 | 8191.42 | 10-DEC-15:35 | 85.63 | 28-DEC-15:00 | 1688.56 | 03-DEC-15:35 | 0.00 |
Annual Sum or Average | 0.152615E+12 | 0.329062E+11 | 8760.00 | 0.152079E+12 | 0.536109E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.407884E+10 | 0.979488E+09 | 672.00 | 0.407851E+10 | 326849.25 | 0.00 | 0.27 | 0.12 | 2127.82 | 2127.82 | 16.34 | 509.92 | 0.00 | ||||||
Maximum of Months | 0.212835E+11 | 0.475402E+10 | 744.00 | 0.211227E+11 | 0.160804E+09 | 0.00 | 1.00 | 0.77 | 9269.74 | 9269.74 | 277.51 | 2731.94 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.153967E+11 | 0.400823E+10 | 688.95 | 0.153967E+11 | -0.0 | 0.00 | 0.22 | 20-JAN-16:20 | 0.00 | 01-JAN-00:05 | 16735.79 | 05-JAN-16:20 | 16735.79 | 05-JAN-16:20 | 0.00 | 26-JAN-07:40 | 3927.88 | 20-JAN-16:20 | 0.00 |
February | 0.671695E+11 | 0.152730E+11 | 672.00 | 0.670671E+11 | 0.102401E+09 | 0.00 | 0.48 | 08-FEB-16:50 | 0.24 | 21-FEB-07:10 | 40321.11 | 27-FEB-16:20 | 40122.04 | 27-FEB-16:20 | 1250.11 | 24-FEB-11:10 | 8917.34 | 27-FEB-16:20 | 0.00 |
March | 0.134099E+12 | 0.287271E+11 | 744.00 | 0.134018E+12 | 81224517.44 | 0.00 | 0.77 | 31-MAR-23:50 | 0.50 | 06-MAR-07:10 | 67946.72 | 31-MAR-23:50 | 67946.72 | 31-MAR-23:50 | 1359.47 | 09-MAR-17:00 | 13742.43 | 31-MAR-23:50 | 0.00 |
April | 0.183766E+12 | 0.378548E+11 | 720.00 | 0.183628E+12 | 0.138071E+09 | 0.00 | 0.97 | 01-APR-17:32 | 0.23 | 30-APR-24:00 | 82486.09 | 26-APR-18:00 | 82486.09 | 26-APR-18:00 | 1662.88 | 28-APR-13:00 | 22935.29 | 01-APR-17:02 | 0.00 |
May | 0.484483E+11 | 0.112581E+11 | 744.00 | 0.480915E+11 | 0.356750E+09 | 0.00 | 0.45 | 31-MAY-23:50 | 0.13 | 18-MAY-06:05 | 37707.65 | 31-MAY-23:40 | 37608.81 | 31-MAY-24:00 | 1301.62 | 05-MAY-16:10 | 8004.39 | 31-MAY-23:50 | 0.00 |
June | 0.969641E+11 | 0.213695E+11 | 720.00 | 0.964471E+11 | 0.516967E+09 | 0.00 | 0.63 | 30-JUN-24:00 | 0.38 | 14-JUN-06:25 | 55462.70 | 30-JUN-24:00 | 55442.60 | 30-JUN-24:00 | 1928.83 | 12-JUN-15:00 | 12223.54 | 28-JUN-17:00 | 0.00 |
July | 0.152924E+12 | 0.336661E+11 | 744.00 | 0.151785E+12 | 0.113925E+10 | 0.00 | 0.84 | 31-JUL-23:20 | 0.59 | 18-JUL-06:10 | 75632.06 | 31-JUL-23:55 | 75344.48 | 31-JUL-24:00 | 2447.00 | 11-JUL-10:00 | 19516.49 | 30-JUL-18:01 | 0.00 |
August | 0.201476E+12 | 0.451188E+11 | 744.00 | 0.199879E+12 | 0.159715E+10 | 0.00 | 1.00 | 10-AUG-17:50 | 0.25 | 31-AUG-24:00 | 86997.16 | 06-AUG-18:35 | 86997.16 | 06-AUG-18:40 | 2763.16 | 30-AUG-08:00 | 26210.98 | 10-AUG-17:50 | 0.00 |
September | 0.487566E+11 | 0.111942E+11 | 720.00 | 0.478683E+11 | 0.888258E+09 | 0.00 | 0.42 | 30-SEP-23:50 | 0.14 | 28-SEP-06:55 | 35424.38 | 30-SEP-23:50 | 35408.62 | 30-SEP-23:50 | 1712.98 | 14-SEP-13:20 | 7568.48 | 30-SEP-23:50 | 0.00 |
October | 0.893620E+11 | 0.194702E+11 | 744.00 | 0.891362E+11 | 0.225711E+09 | 0.00 | 0.56 | 31-OCT-24:00 | 0.32 | 28-OCT-07:00 | 47940.88 | 31-OCT-24:00 | 47940.88 | 31-OCT-24:00 | 1335.53 | 26-OCT-14:10 | 10813.00 | 04-OCT-16:50 | 0.00 |
November | 0.123847E+12 | 0.262290E+11 | 720.00 | 0.123611E+12 | 0.235398E+09 | 0.00 | 0.67 | 04-NOV-16:00 | 0.48 | 24-NOV-07:05 | 58347.95 | 04-NOV-16:00 | 57159.55 | 04-NOV-16:02 | 1644.88 | 03-NOV-16:00 | 13254.36 | 04-NOV-15:50 | 0.00 |
December | 0.168736E+12 | 0.352336E+11 | 744.00 | 0.168711E+12 | 24831517.33 | 0.00 | 0.83 | 05-DEC-15:50 | 0.63 | 26-DEC-07:03 | 73202.89 | 05-DEC-15:50 | 73202.89 | 05-DEC-15:50 | 846.54 | 28-DEC-15:00 | 14898.41 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.133094E+13 | 0.289403E+12 | 8704.95 | 0.132564E+13 | 0.530602E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.153967E+11 | 0.400823E+10 | 672.00 | 0.153967E+11 | -0.0 | 0.00 | 0.22 | 0.00 | 16735.79 | 16735.79 | 0.00 | 3927.88 | 0.00 | ||||||
Maximum of Months | 0.201476E+12 | 0.451188E+11 | 744.00 | 0.199879E+12 | 0.159715E+10 | 0.00 | 1.00 | 0.63 | 86997.16 | 86997.16 | 2763.16 | 26210.98 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.483413E+09 | 0.133817E+09 | 346.28 | 0.483413E+09 | 0.00 | 0.00 | 0.20 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 1542.07 | 05-JAN-16:20 | 1542.07 | 05-JAN-16:20 | 0.00 | 31-JAN-22:00 | 364.16 | 05-JAN-16:20 | 0.00 |
February | 0.510112E+10 | 0.117974E+10 | 671.36 | 0.509103E+10 | 10096918.39 | 0.00 | 0.47 | 27-FEB-16:20 | 0.00 | 19-FEB-06:15 | 3992.71 | 27-FEB-16:30 | 3971.46 | 27-FEB-16:20 | 123.63 | 24-FEB-11:20 | 884.92 | 27-FEB-16:20 | 0.00 |
March | 0.121187E+11 | 0.262621E+10 | 744.00 | 0.121106E+11 | 8053573.12 | 0.00 | 0.71 | 31-MAR-23:20 | 0.36 | 06-MAR-05:14 | 6309.42 | 31-MAR-23:20 | 6309.42 | 31-MAR-23:20 | 135.47 | 09-MAR-17:00 | 1340.47 | 18-MAR-17:02 | 0.00 |
April | 0.176315E+11 | 0.365939E+10 | 720.00 | 0.176177E+11 | 13754113.27 | 0.00 | 0.95 | 01-APR-17:32 | 0.19 | 30-APR-24:00 | 8322.28 | 26-APR-18:00 | 8322.28 | 26-APR-18:00 | 166.37 | 28-APR-13:00 | 2297.09 | 27-APR-16:00 | 0.00 |
May | 0.437263E+10 | 0.102599E+10 | 744.00 | 0.433714E+10 | 35497396.88 | 0.00 | 0.43 | 31-MAY-23:20 | 0.05 | 18-MAY-06:05 | 3696.53 | 31-MAY-23:20 | 3680.91 | 31-MAY-23:30 | 131.23 | 05-MAY-16:10 | 787.05 | 31-MAY-23:20 | 0.00 |
June | 0.949641E+10 | 0.210155E+10 | 720.00 | 0.944469E+10 | 51721553.40 | 0.00 | 0.61 | 30-JUN-23:40 | 0.32 | 14-JUN-06:40 | 5464.44 | 30-JUN-23:40 | 5460.94 | 30-JUN-23:40 | 192.90 | 12-JUN-15:00 | 1246.59 | 28-JUN-17:00 | 0.00 |
July | 0.151845E+11 | 0.335536E+10 | 744.00 | 0.150704E+11 | 0.114060E+09 | 0.00 | 0.85 | 30-JUL-18:31 | 0.56 | 18-JUL-06:10 | 7536.45 | 31-JUL-23:55 | 7507.50 | 31-JUL-24:00 | 244.78 | 11-JUL-10:00 | 2011.76 | 30-JUL-18:01 | 0.00 |
August | 0.200214E+11 | 0.450214E+10 | 744.00 | 0.198617E+11 | 0.159709E+09 | 0.00 | 1.00 | 10-AUG-17:50 | 0.23 | 31-AUG-24:00 | 8906.93 | 06-AUG-18:30 | 8906.93 | 06-AUG-18:30 | 275.48 | 30-AUG-08:00 | 2660.91 | 10-AUG-17:50 | 0.00 |
September | 0.439253E+10 | 0.101924E+10 | 720.00 | 0.430478E+10 | 87748187.89 | 0.00 | 0.38 | 10-SEP-17:22 | 0.07 | 27-SEP-06:40 | 3149.17 | 30-SEP-23:20 | 3145.92 | 30-SEP-23:20 | 174.32 | 14-SEP-13:20 | 757.86 | 10-SEP-17:22 | 0.00 |
October | 0.777963E+10 | 0.171635E+10 | 744.00 | 0.775745E+10 | 22180321.42 | 0.00 | 0.55 | 04-OCT-16:50 | 0.21 | 16-OCT-06:05 | 4593.85 | 04-OCT-16:50 | 4593.85 | 04-OCT-16:50 | 131.51 | 26-OCT-14:10 | 1088.79 | 04-OCT-16:50 | 0.00 |
November | 0.107139E+11 | 0.230381E+10 | 720.00 | 0.106906E+11 | 23308230.66 | 0.00 | 0.65 | 04-NOV-16:00 | 0.34 | 13-NOV-05:00 | 5749.04 | 04-NOV-16:00 | 5630.62 | 04-NOV-16:02 | 164.01 | 03-NOV-16:00 | 1310.12 | 04-NOV-15:50 | 0.00 |
December | 0.149130E+11 | 0.316414E+10 | 744.00 | 0.149105E+11 | 2455978.31 | 0.00 | 0.80 | 05-DEC-16:00 | 0.46 | 26-DEC-04:07 | 7128.11 | 05-DEC-16:00 | 7128.11 | 05-DEC-16:00 | 84.09 | 28-DEC-15:10 | 1458.66 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.122209E+12 | 0.267877E+11 | 8361.64 | 0.121680E+12 | 0.528586E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.483413E+09 | 0.133817E+09 | 346.28 | 0.483413E+09 | 0.00 | 0.00 | 0.20 | 0.00 | 1542.07 | 1542.07 | 0.00 | 364.16 | 0.00 | ||||||
Maximum of Months | 0.200214E+11 | 0.450214E+10 | 744.00 | 0.198617E+11 | 0.159709E+09 | 0.00 | 1.00 | 0.56 | 8906.93 | 8906.93 | 275.48 | 2660.91 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.79 | 627.07 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 15.61 | 553.92 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 64.75 | 450.41 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.21 | 352.43 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 278.66 | 270.22 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 327.67 | 207.62 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.02 | 185.40 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.43 | 181.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 163.95 | 276.87 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.06 | 394.83 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.08 | 522.10 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.16 | 646.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.26 | 388.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.16 | 181.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.02 | 646.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.79 | 627.07 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 15.61 | 553.92 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 64.75 | 450.41 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.21 | 352.43 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 278.66 | 270.22 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 327.67 | 207.62 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.02 | 185.40 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.43 | 181.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 163.95 | 276.87 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.06 | 394.83 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.08 | 522.10 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.16 | 646.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.26 | 388.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.16 | 181.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.02 | 646.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.79 | 627.07 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 15.61 | 553.92 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 64.75 | 450.41 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.21 | 352.43 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 278.66 | 270.22 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 327.67 | 207.62 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.02 | 185.40 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.43 | 181.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 163.95 | 276.87 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.06 | 394.83 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.08 | 522.10 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.16 | 646.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.26 | 388.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.16 | 181.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.02 | 646.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.79 | 627.07 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 15.61 | 553.92 | 0.00 | 0.00 | 0.00 |
March | 195.60 | 0.00 | 195.60 | 64.75 | 450.41 | 0.00 | 0.00 | 0.00 |
April | 276.80 | 0.98 | 275.81 | 162.21 | 352.43 | 0.00 | 0.00 | 0.00 |
May | 356.17 | 10.58 | 345.59 | 278.66 | 270.22 | 0.00 | 0.00 | 0.00 |
June | 374.50 | 24.73 | 349.77 | 327.67 | 207.62 | 0.00 | 0.00 | 0.00 |
July | 355.94 | 27.91 | 328.04 | 354.02 | 185.40 | 0.00 | 0.00 | 0.00 |
August | 288.14 | 7.79 | 280.35 | 290.43 | 181.88 | 0.00 | 0.00 | 0.00 |
September | 223.82 | 0.07 | 223.75 | 163.95 | 276.87 | 0.00 | 0.00 | 0.00 |
October | 153.35 | 0.00 | 153.35 | 56.06 | 394.83 | 0.00 | 0.00 | 0.00 |
November | 96.60 | 0.00 | 96.60 | 7.08 | 522.10 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.16 | 646.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 212.00 | 144.26 | 388.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.16 | 181.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.50 | 27.91 | 349.77 | 354.02 | 646.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.32 | 0.00 | 85.32 | 0.79 | 627.04 | 0.00 | 0.00 | 0.00 |
February | 132.76 | 0.00 | 132.76 | 15.61 | 553.90 | 0.00 | 0.00 | 0.00 |
March | 195.59 | 0.00 | 195.59 | 64.75 | 450.39 | 0.00 | 0.00 | 0.00 |
April | 276.79 | 0.98 | 275.80 | 162.20 | 352.42 | 0.00 | 0.00 | 0.00 |
May | 356.15 | 10.58 | 345.57 | 278.65 | 270.20 | 0.00 | 0.00 | 0.00 |
June | 374.49 | 24.73 | 349.76 | 327.66 | 207.61 | 0.00 | 0.00 | 0.00 |
July | 355.93 | 27.91 | 328.02 | 354.01 | 185.40 | 0.00 | 0.00 | 0.00 |
August | 288.13 | 7.79 | 280.34 | 290.41 | 181.87 | 0.00 | 0.00 | 0.00 |
September | 223.81 | 0.07 | 223.74 | 163.95 | 276.85 | 0.00 | 0.00 | 0.00 |
October | 153.34 | 0.00 | 153.34 | 56.06 | 394.81 | 0.00 | 0.00 | 0.00 |
November | 96.59 | 0.00 | 96.59 | 7.08 | 522.08 | 0.00 | 0.00 | 0.00 |
December | 72.50 | 0.00 | 72.50 | 0.16 | 646.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.04 | 6.05 | 211.99 | 144.26 | 388.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.50 | 0.00 | 72.50 | 0.16 | 181.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.49 | 27.91 | 349.76 | 354.01 | 646.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.33 | 38.62 | 113.71 | 45.34 | 653.72 | 0.00 | 0.00 | 0.00 |
February | 279.51 | 99.20 | 180.31 | 162.10 | 566.25 | 0.00 | 0.00 | 0.00 |
March | 417.33 | 151.08 | 266.25 | 327.94 | 464.71 | 0.00 | 0.00 | 0.00 |
April | 646.93 | 268.81 | 378.12 | 639.00 | 363.85 | 0.00 | 0.00 | 0.00 |
May | 688.39 | 239.34 | 449.06 | 721.60 | 299.77 | 0.00 | 0.00 | 0.00 |
June | 824.43 | 358.72 | 465.71 | 936.53 | 232.45 | 0.00 | 0.00 | 0.00 |
July | 767.74 | 344.60 | 423.13 | 912.30 | 201.55 | 0.00 | 0.00 | 0.00 |
August | 754.58 | 377.48 | 377.09 | 928.86 | 195.01 | 0.00 | 0.00 | 0.00 |
September | 557.90 | 257.31 | 300.59 | 604.82 | 293.32 | 0.00 | 0.00 | 0.00 |
October | 363.64 | 154.51 | 209.13 | 315.72 | 412.22 | 0.00 | 0.00 | 0.00 |
November | 178.24 | 50.32 | 127.92 | 81.96 | 539.73 | 0.00 | 0.00 | 0.00 |
December | 146.19 | 47.06 | 99.13 | 59.04 | 662.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.32 | 199.36 | 282.96 | 479.57 | 406.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.19 | 38.62 | 99.13 | 45.34 | 195.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 824.43 | 377.48 | 465.71 | 936.53 | 662.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.33 | 38.62 | 113.71 | 45.34 | 653.72 | 0.00 | 0.00 | 0.00 |
February | 279.51 | 99.20 | 180.31 | 162.10 | 566.25 | 0.00 | 0.00 | 0.00 |
March | 417.33 | 151.08 | 266.25 | 327.94 | 464.71 | 0.00 | 0.00 | 0.00 |
April | 646.93 | 268.81 | 378.12 | 639.00 | 363.85 | 0.00 | 0.00 | 0.00 |
May | 688.39 | 239.34 | 449.06 | 721.60 | 299.77 | 0.00 | 0.00 | 0.00 |
June | 824.43 | 358.72 | 465.71 | 936.53 | 232.45 | 0.00 | 0.00 | 0.00 |
July | 767.74 | 344.60 | 423.13 | 912.30 | 201.55 | 0.00 | 0.00 | 0.00 |
August | 754.58 | 377.48 | 377.09 | 928.86 | 195.01 | 0.00 | 0.00 | 0.00 |
September | 557.90 | 257.31 | 300.59 | 604.82 | 293.32 | 0.00 | 0.00 | 0.00 |
October | 363.64 | 154.51 | 209.13 | 315.72 | 412.22 | 0.00 | 0.00 | 0.00 |
November | 178.24 | 50.32 | 127.92 | 81.96 | 539.73 | 0.00 | 0.00 | 0.00 |
December | 146.19 | 47.06 | 99.13 | 59.04 | 662.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.32 | 199.36 | 282.96 | 479.57 | 406.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.19 | 38.62 | 99.13 | 45.34 | 195.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 824.43 | 377.48 | 465.71 | 936.53 | 662.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.33 | 38.62 | 113.71 | 45.34 | 653.71 | 0.00 | 0.00 | 0.00 |
February | 279.51 | 99.20 | 180.30 | 162.10 | 566.24 | 0.00 | 0.00 | 0.00 |
March | 417.32 | 151.07 | 266.25 | 327.94 | 464.70 | 0.00 | 0.00 | 0.00 |
April | 646.92 | 268.81 | 378.12 | 638.99 | 363.84 | 0.00 | 0.00 | 0.00 |
May | 688.38 | 239.33 | 449.05 | 721.59 | 299.77 | 0.00 | 0.00 | 0.00 |
June | 824.41 | 358.71 | 465.71 | 936.51 | 232.45 | 0.00 | 0.00 | 0.00 |
July | 767.72 | 344.60 | 423.12 | 912.28 | 201.54 | 0.00 | 0.00 | 0.00 |
August | 754.56 | 377.48 | 377.09 | 928.84 | 195.01 | 0.00 | 0.00 | 0.00 |
September | 557.89 | 257.30 | 300.59 | 604.81 | 293.31 | 0.00 | 0.00 | 0.00 |
October | 363.63 | 154.51 | 209.12 | 315.71 | 412.21 | 0.00 | 0.00 | 0.00 |
November | 178.23 | 50.32 | 127.92 | 81.95 | 539.72 | 0.00 | 0.00 | 0.00 |
December | 146.19 | 47.06 | 99.13 | 59.04 | 662.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.31 | 199.36 | 282.96 | 479.56 | 406.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.19 | 38.62 | 99.13 | 45.34 | 195.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 824.41 | 377.48 | 465.71 | 936.51 | 662.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 321.01 | 533.75 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 570.07 | 483.32 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 648.63 | 425.09 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 728.04 | 356.05 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 676.59 | 288.14 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 632.70 | 228.52 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 763.66 | 205.64 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 848.88 | 198.91 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 881.32 | 278.20 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 724.12 | 373.01 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 350.45 | 459.46 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.29 | 141.38 | 378.40 | 558.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 627.23 | 365.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 321.01 | 198.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 881.32 | 558.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 321.00 | 533.75 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 570.07 | 483.32 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 648.63 | 425.09 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 728.04 | 356.05 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 676.59 | 288.14 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 632.70 | 228.52 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 763.65 | 205.64 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 848.88 | 198.91 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 881.31 | 278.20 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 724.12 | 373.01 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 350.45 | 459.46 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.28 | 141.38 | 378.40 | 558.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 627.23 | 365.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 321.00 | 198.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 881.31 | 558.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 321.01 | 533.75 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 570.07 | 483.32 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 648.63 | 425.09 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 728.04 | 356.05 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 676.59 | 288.14 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 632.70 | 228.52 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 763.66 | 205.64 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 848.88 | 198.91 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 881.32 | 278.20 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 724.12 | 373.01 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 350.45 | 459.46 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.29 | 141.38 | 378.40 | 558.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 627.23 | 365.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 321.01 | 198.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 881.32 | 558.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.97 | 223.85 | 153.12 | 321.00 | 533.75 | 0.00 | 0.00 | 0.00 |
February | 579.72 | 358.86 | 220.87 | 570.07 | 483.32 | 0.00 | 0.00 | 0.00 |
March | 623.62 | 332.57 | 291.05 | 648.63 | 425.09 | 0.00 | 0.00 | 0.00 |
April | 658.42 | 285.88 | 372.54 | 728.04 | 356.05 | 0.00 | 0.00 | 0.00 |
May | 602.04 | 179.35 | 422.69 | 676.59 | 288.14 | 0.00 | 0.00 | 0.00 |
June | 550.81 | 147.89 | 402.92 | 632.70 | 228.52 | 0.00 | 0.00 | 0.00 |
July | 600.68 | 220.00 | 380.68 | 763.65 | 205.64 | 0.00 | 0.00 | 0.00 |
August | 645.36 | 300.94 | 344.42 | 848.88 | 198.91 | 0.00 | 0.00 | 0.00 |
September | 715.03 | 394.86 | 320.17 | 881.31 | 278.20 | 0.00 | 0.00 | 0.00 |
October | 647.69 | 399.90 | 247.79 | 724.12 | 373.01 | 0.00 | 0.00 | 0.00 |
November | 382.94 | 219.46 | 163.48 | 350.45 | 459.46 | 0.00 | 0.00 | 0.00 |
December | 400.66 | 259.28 | 141.38 | 378.40 | 558.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.08 | 276.39 | 288.69 | 627.23 | 365.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 147.89 | 141.38 | 321.00 | 198.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.03 | 399.90 | 422.69 | 881.31 | 558.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.96 | 223.84 | 153.12 | 320.99 | 533.73 | 0.00 | 0.00 | 0.00 |
February | 579.70 | 358.84 | 220.86 | 570.05 | 483.30 | 0.00 | 0.00 | 0.00 |
March | 623.59 | 332.55 | 291.04 | 648.61 | 425.07 | 0.00 | 0.00 | 0.00 |
April | 658.39 | 285.87 | 372.52 | 728.01 | 356.03 | 0.00 | 0.00 | 0.00 |
May | 602.02 | 179.35 | 422.67 | 676.56 | 288.12 | 0.00 | 0.00 | 0.00 |
June | 550.79 | 147.88 | 402.91 | 632.68 | 228.51 | 0.00 | 0.00 | 0.00 |
July | 600.66 | 219.99 | 380.66 | 763.62 | 205.63 | 0.00 | 0.00 | 0.00 |
August | 645.33 | 300.93 | 344.40 | 848.85 | 198.90 | 0.00 | 0.00 | 0.00 |
September | 715.00 | 394.85 | 320.15 | 881.28 | 278.19 | 0.00 | 0.00 | 0.00 |
October | 647.67 | 399.89 | 247.78 | 724.09 | 372.99 | 0.00 | 0.00 | 0.00 |
November | 382.92 | 219.45 | 163.48 | 350.44 | 459.44 | 0.00 | 0.00 | 0.00 |
December | 400.65 | 259.27 | 141.37 | 378.39 | 558.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 565.06 | 276.38 | 288.68 | 627.20 | 365.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.96 | 147.88 | 141.37 | 320.99 | 198.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 715.00 | 399.89 | 422.67 | 881.28 | 558.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.67 | 47.38 | 113.29 | 57.28 | 705.64 | 0.00 | 0.00 | 0.00 |
February | 288.07 | 108.27 | 179.81 | 176.90 | 636.72 | 0.00 | 0.00 | 0.00 |
March | 403.66 | 136.25 | 267.41 | 307.00 | 538.18 | 0.00 | 0.00 | 0.00 |
April | 614.13 | 234.80 | 379.32 | 581.48 | 441.71 | 0.00 | 0.00 | 0.00 |
May | 790.24 | 321.03 | 469.21 | 852.33 | 337.83 | 0.00 | 0.00 | 0.00 |
June | 759.99 | 295.08 | 464.91 | 835.87 | 274.52 | 0.00 | 0.00 | 0.00 |
July | 938.87 | 493.52 | 445.35 | 1138.03 | 257.09 | 0.00 | 0.00 | 0.00 |
August | 776.67 | 396.59 | 380.08 | 949.66 | 256.91 | 0.00 | 0.00 | 0.00 |
September | 632.48 | 303.48 | 329.00 | 714.06 | 334.61 | 0.00 | 0.00 | 0.00 |
October | 360.07 | 146.71 | 213.36 | 308.51 | 472.77 | 0.00 | 0.00 | 0.00 |
November | 179.31 | 50.57 | 128.74 | 80.58 | 618.82 | 0.00 | 0.00 | 0.00 |
December | 150.75 | 51.66 | 99.09 | 68.49 | 774.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.90 | 216.26 | 289.63 | 508.04 | 470.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.75 | 47.38 | 99.09 | 57.28 | 256.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 938.87 | 493.52 | 469.21 | 1138.03 | 774.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.67 | 47.38 | 113.29 | 57.28 | 705.64 | 0.00 | 0.00 | 0.00 |
February | 288.07 | 108.27 | 179.81 | 176.90 | 636.72 | 0.00 | 0.00 | 0.00 |
March | 403.66 | 136.25 | 267.41 | 307.00 | 538.18 | 0.00 | 0.00 | 0.00 |
April | 614.13 | 234.80 | 379.32 | 581.48 | 441.71 | 0.00 | 0.00 | 0.00 |
May | 790.24 | 321.03 | 469.21 | 852.33 | 337.83 | 0.00 | 0.00 | 0.00 |
June | 759.99 | 295.08 | 464.91 | 835.87 | 274.52 | 0.00 | 0.00 | 0.00 |
July | 938.87 | 493.52 | 445.35 | 1138.03 | 257.09 | 0.00 | 0.00 | 0.00 |
August | 776.67 | 396.59 | 380.08 | 949.66 | 256.91 | 0.00 | 0.00 | 0.00 |
September | 632.48 | 303.48 | 329.00 | 714.06 | 334.61 | 0.00 | 0.00 | 0.00 |
October | 360.07 | 146.71 | 213.36 | 308.51 | 472.77 | 0.00 | 0.00 | 0.00 |
November | 179.31 | 50.57 | 128.74 | 80.58 | 618.82 | 0.00 | 0.00 | 0.00 |
December | 150.75 | 51.66 | 99.09 | 68.49 | 774.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.90 | 216.26 | 289.63 | 508.04 | 470.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.75 | 47.38 | 99.09 | 57.28 | 256.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 938.87 | 493.52 | 469.21 | 1138.03 | 774.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.67 | 47.38 | 113.29 | 57.28 | 705.63 | 0.00 | 0.00 | 0.00 |
February | 288.07 | 108.26 | 179.80 | 176.90 | 636.71 | 0.00 | 0.00 | 0.00 |
March | 403.65 | 136.24 | 267.41 | 307.00 | 538.17 | 0.00 | 0.00 | 0.00 |
April | 614.12 | 234.80 | 379.32 | 581.47 | 441.71 | 0.00 | 0.00 | 0.00 |
May | 790.22 | 321.03 | 469.20 | 852.31 | 337.82 | 0.00 | 0.00 | 0.00 |
June | 759.98 | 295.07 | 464.90 | 835.86 | 274.51 | 0.00 | 0.00 | 0.00 |
July | 938.85 | 493.51 | 445.34 | 1138.01 | 257.09 | 0.00 | 0.00 | 0.00 |
August | 776.65 | 396.58 | 380.07 | 949.64 | 256.90 | 0.00 | 0.00 | 0.00 |
September | 632.47 | 303.47 | 329.00 | 714.05 | 334.61 | 0.00 | 0.00 | 0.00 |
October | 360.07 | 146.71 | 213.36 | 308.51 | 472.76 | 0.00 | 0.00 | 0.00 |
November | 179.31 | 50.57 | 128.74 | 80.57 | 618.81 | 0.00 | 0.00 | 0.00 |
December | 150.74 | 51.66 | 99.09 | 68.49 | 774.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.89 | 216.26 | 289.63 | 508.03 | 470.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 150.74 | 47.38 | 99.09 | 57.28 | 256.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 938.85 | 493.51 | 469.20 | 1138.01 | 774.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 426.60 | 0.00 | 426.60 | 12.05 | 2693.89 | 0.00 | 0.00 | 0.00 |
February | 663.80 | 0.00 | 663.80 | 117.37 | 2410.36 | 0.00 | 0.00 | 0.00 |
March | 978.00 | 0.00 | 978.00 | 382.88 | 2002.10 | 0.00 | 0.00 | 0.00 |
April | 1383.97 | 4.91 | 1379.06 | 870.35 | 1594.50 | 0.00 | 0.00 | 0.00 |
May | 1780.82 | 52.91 | 1727.91 | 1420.72 | 1282.98 | 0.00 | 0.00 | 0.00 |
June | 1872.49 | 123.65 | 1748.83 | 1661.51 | 984.92 | 0.00 | 0.00 | 0.00 |
July | 1779.69 | 139.54 | 1640.16 | 1798.04 | 881.00 | 0.00 | 0.00 | 0.00 |
August | 1440.68 | 38.95 | 1401.73 | 1482.35 | 862.69 | 0.00 | 0.00 | 0.00 |
September | 1119.07 | 0.33 | 1118.74 | 845.76 | 1295.52 | 0.00 | 0.00 | 0.00 |
October | 766.75 | 0.00 | 766.75 | 328.67 | 1757.67 | 0.00 | 0.00 | 0.00 |
November | 482.97 | 0.00 | 482.97 | 57.89 | 2223.28 | 0.00 | 0.00 | 0.00 |
December | 362.50 | 0.00 | 362.50 | 5.26 | 2725.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1090.21 | 30.25 | 1059.96 | 752.55 | 1722.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.50 | 0.00 | 362.50 | 5.26 | 862.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1872.49 | 139.54 | 1748.83 | 1798.04 | 2725.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.99 | 115.86 | 341.13 | 154.01 | 1713.23 | 0.00 | 0.00 | 0.00 |
February | 838.53 | 297.61 | 540.92 | 517.09 | 1539.22 | 0.00 | 0.00 | 0.00 |
March | 1251.98 | 453.23 | 798.75 | 995.39 | 1298.46 | 0.00 | 0.00 | 0.00 |
April | 1940.78 | 806.42 | 1134.36 | 1913.38 | 1041.43 | 0.00 | 0.00 | 0.00 |
May | 2065.16 | 718.01 | 1347.15 | 2152.83 | 872.57 | 0.00 | 0.00 | 0.00 |
June | 2473.26 | 1076.14 | 1397.13 | 2785.65 | 683.27 | 0.00 | 0.00 | 0.00 |
July | 2303.18 | 1033.80 | 1269.38 | 2715.87 | 597.97 | 0.00 | 0.00 | 0.00 |
August | 2263.71 | 1132.44 | 1131.27 | 2763.07 | 586.08 | 0.00 | 0.00 | 0.00 |
September | 1673.68 | 771.92 | 901.76 | 1806.52 | 848.05 | 0.00 | 0.00 | 0.00 |
October | 1090.90 | 463.53 | 627.37 | 958.13 | 1148.44 | 0.00 | 0.00 | 0.00 |
November | 534.70 | 150.95 | 383.75 | 263.81 | 1443.24 | 0.00 | 0.00 | 0.00 |
December | 438.57 | 141.19 | 297.38 | 194.31 | 1754.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1446.95 | 598.07 | 848.88 | 1439.73 | 1125.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.57 | 115.86 | 297.38 | 154.01 | 586.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2473.26 | 1132.44 | 1397.13 | 2785.65 | 1754.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1884.84 | 1119.22 | 765.61 | 1622.95 | 2495.80 | 0.00 | 0.00 | 0.00 |
February | 2898.59 | 1794.27 | 1104.32 | 2859.15 | 2306.82 | 0.00 | 0.00 | 0.00 |
March | 3118.04 | 1662.82 | 1455.23 | 3236.60 | 2033.37 | 0.00 | 0.00 | 0.00 |
April | 3292.06 | 1429.40 | 1862.67 | 3627.78 | 1710.34 | 0.00 | 0.00 | 0.00 |
May | 3010.17 | 896.76 | 2113.41 | 3359.07 | 1412.63 | 0.00 | 0.00 | 0.00 |
June | 2754.01 | 739.42 | 2014.59 | 3146.69 | 1110.09 | 0.00 | 0.00 | 0.00 |
July | 3003.37 | 1099.99 | 1903.38 | 3801.70 | 1001.53 | 0.00 | 0.00 | 0.00 |
August | 3226.74 | 1504.68 | 1722.06 | 4227.83 | 973.78 | 0.00 | 0.00 | 0.00 |
September | 3575.10 | 1974.29 | 1600.81 | 4385.67 | 1366.82 | 0.00 | 0.00 | 0.00 |
October | 3238.43 | 1999.49 | 1238.94 | 3604.36 | 1798.25 | 0.00 | 0.00 | 0.00 |
November | 1914.67 | 1097.27 | 817.40 | 1768.16 | 2153.54 | 0.00 | 0.00 | 0.00 |
December | 2003.29 | 1296.41 | 706.88 | 1912.25 | 2587.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2825.39 | 1381.95 | 1443.44 | 3130.45 | 1743.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1884.84 | 739.42 | 706.88 | 1622.95 | 973.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3575.10 | 1999.49 | 2113.41 | 4385.67 | 2587.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.01 | 142.14 | 339.87 | 192.61 | 1778.75 | 0.00 | 0.00 | 0.00 |
February | 864.20 | 324.79 | 539.41 | 574.64 | 1601.94 | 0.00 | 0.00 | 0.00 |
March | 1210.97 | 408.74 | 802.24 | 969.10 | 1367.50 | 0.00 | 0.00 | 0.00 |
April | 1842.36 | 704.41 | 1137.96 | 1800.70 | 1137.31 | 0.00 | 0.00 | 0.00 |
May | 2370.69 | 963.08 | 1407.61 | 2564.72 | 948.08 | 0.00 | 0.00 | 0.00 |
June | 2279.96 | 885.23 | 1394.72 | 2528.47 | 746.71 | 0.00 | 0.00 | 0.00 |
July | 2816.58 | 1480.54 | 1336.04 | 3437.52 | 693.09 | 0.00 | 0.00 | 0.00 |
August | 2329.98 | 1189.76 | 1140.23 | 2885.62 | 674.98 | 0.00 | 0.00 | 0.00 |
September | 1897.41 | 910.42 | 986.99 | 2154.47 | 929.01 | 0.00 | 0.00 | 0.00 |
October | 1080.20 | 440.13 | 640.07 | 961.89 | 1222.67 | 0.00 | 0.00 | 0.00 |
November | 537.94 | 151.72 | 386.21 | 275.14 | 1494.88 | 0.00 | 0.00 | 0.00 |
December | 452.24 | 154.97 | 297.27 | 231.23 | 1827.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1517.67 | 648.79 | 868.89 | 1554.46 | 1199.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.24 | 142.14 | 297.27 | 192.61 | 674.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2816.58 | 1480.54 | 1407.61 | 3437.52 | 1827.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 426.60 | 0.00 | 426.60 | 20.60 | 2479.79 | 0.00 | 0.00 | 0.00 |
February | 663.80 | 0.00 | 663.80 | 146.26 | 2197.45 | 0.00 | 0.00 | 0.00 |
March | 978.00 | 0.00 | 978.00 | 431.30 | 1825.23 | 0.00 | 0.00 | 0.00 |
April | 1383.97 | 4.91 | 1379.06 | 912.18 | 1489.26 | 0.00 | 0.00 | 0.00 |
May | 1780.82 | 52.91 | 1727.91 | 1446.25 | 1222.88 | 0.00 | 0.00 | 0.00 |
June | 1872.49 | 123.65 | 1748.83 | 1665.05 | 958.11 | 0.00 | 0.00 | 0.00 |
July | 1779.69 | 139.54 | 1640.16 | 1792.54 | 863.62 | 0.00 | 0.00 | 0.00 |
August | 1440.68 | 38.95 | 1401.73 | 1481.57 | 841.30 | 0.00 | 0.00 | 0.00 |
September | 1119.07 | 0.33 | 1118.74 | 869.16 | 1219.31 | 0.00 | 0.00 | 0.00 |
October | 766.75 | 0.00 | 766.75 | 375.94 | 1585.66 | 0.00 | 0.00 | 0.00 |
November | 482.97 | 0.00 | 482.97 | 80.27 | 1978.82 | 0.00 | 0.00 | 0.00 |
December | 362.50 | 0.00 | 362.50 | 12.85 | 2471.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1090.21 | 30.25 | 1059.96 | 773.39 | 1591.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.50 | 0.00 | 362.50 | 12.85 | 841.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1872.49 | 139.54 | 1748.83 | 1792.54 | 2479.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.99 | 115.86 | 341.13 | 169.99 | 1574.69 | 0.00 | 0.00 | 0.00 |
February | 838.53 | 297.61 | 540.92 | 554.35 | 1399.50 | 0.00 | 0.00 | 0.00 |
March | 1251.98 | 453.23 | 798.75 | 1035.27 | 1187.78 | 0.00 | 0.00 | 0.00 |
April | 1940.78 | 806.42 | 1134.36 | 1942.22 | 980.34 | 0.00 | 0.00 | 0.00 |
May | 2065.16 | 718.01 | 1347.15 | 2169.52 | 835.74 | 0.00 | 0.00 | 0.00 |
June | 2473.26 | 1076.14 | 1397.13 | 2787.50 | 667.04 | 0.00 | 0.00 | 0.00 |
July | 2303.18 | 1033.80 | 1269.38 | 2715.38 | 588.31 | 0.00 | 0.00 | 0.00 |
August | 2263.71 | 1132.44 | 1131.27 | 2764.33 | 573.79 | 0.00 | 0.00 | 0.00 |
September | 1673.68 | 771.92 | 901.76 | 1824.36 | 803.13 | 0.00 | 0.00 | 0.00 |
October | 1090.90 | 463.53 | 627.37 | 995.13 | 1042.85 | 0.00 | 0.00 | 0.00 |
November | 534.70 | 150.95 | 383.75 | 291.88 | 1282.22 | 0.00 | 0.00 | 0.00 |
December | 438.57 | 141.19 | 297.38 | 213.62 | 1587.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1446.95 | 598.07 | 848.88 | 1459.89 | 1041.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.57 | 115.86 | 297.38 | 169.99 | 573.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2473.26 | 1132.44 | 1397.13 | 2787.50 | 1587.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1884.84 | 1119.22 | 765.61 | 1667.41 | 2289.38 | 0.00 | 0.00 | 0.00 |
February | 2898.59 | 1794.27 | 1104.32 | 2920.29 | 2111.20 | 0.00 | 0.00 | 0.00 |
March | 3118.04 | 1662.82 | 1455.23 | 3275.96 | 1873.09 | 0.00 | 0.00 | 0.00 |
April | 3292.06 | 1429.40 | 1862.67 | 3653.74 | 1614.80 | 0.00 | 0.00 | 0.00 |
May | 3010.17 | 896.76 | 2113.41 | 3370.15 | 1351.59 | 0.00 | 0.00 | 0.00 |
June | 2754.01 | 739.42 | 2014.59 | 3141.21 | 1080.59 | 0.00 | 0.00 | 0.00 |
July | 3003.37 | 1099.99 | 1903.38 | 3789.73 | 983.74 | 0.00 | 0.00 | 0.00 |
August | 3226.74 | 1504.68 | 1722.06 | 4218.25 | 952.62 | 0.00 | 0.00 | 0.00 |
September | 3575.10 | 1974.29 | 1600.81 | 4398.01 | 1301.75 | 0.00 | 0.00 | 0.00 |
October | 3238.43 | 1999.49 | 1238.94 | 3642.78 | 1652.35 | 0.00 | 0.00 | 0.00 |
November | 1914.67 | 1097.27 | 817.40 | 1819.14 | 1935.36 | 0.00 | 0.00 | 0.00 |
December | 2003.29 | 1296.41 | 706.88 | 1956.03 | 2352.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2825.39 | 1381.95 | 1443.44 | 3155.24 | 1622.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1884.84 | 739.42 | 706.88 | 1667.41 | 952.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3575.10 | 1999.49 | 2113.41 | 4398.01 | 2352.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.01 | 142.14 | 339.87 | 204.13 | 1642.76 | 0.00 | 0.00 | 0.00 |
February | 864.20 | 324.79 | 539.41 | 597.20 | 1480.32 | 0.00 | 0.00 | 0.00 |
March | 1210.97 | 408.74 | 802.24 | 993.75 | 1267.95 | 0.00 | 0.00 | 0.00 |
April | 1842.36 | 704.41 | 1137.96 | 1817.93 | 1078.00 | 0.00 | 0.00 | 0.00 |
May | 2370.69 | 963.08 | 1407.61 | 2568.39 | 911.75 | 0.00 | 0.00 | 0.00 |
June | 2279.96 | 885.23 | 1394.72 | 2521.59 | 728.27 | 0.00 | 0.00 | 0.00 |
July | 2816.58 | 1480.54 | 1336.04 | 3425.53 | 680.98 | 0.00 | 0.00 | 0.00 |
August | 2329.98 | 1189.76 | 1140.23 | 2877.16 | 661.48 | 0.00 | 0.00 | 0.00 |
September | 1897.41 | 910.42 | 986.99 | 2160.16 | 888.40 | 0.00 | 0.00 | 0.00 |
October | 1080.20 | 440.13 | 640.07 | 985.34 | 1127.71 | 0.00 | 0.00 | 0.00 |
November | 537.94 | 151.72 | 386.21 | 293.55 | 1358.80 | 0.00 | 0.00 | 0.00 |
December | 452.24 | 154.97 | 297.27 | 242.29 | 1682.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1517.67 | 648.79 | 868.89 | 1563.60 | 1124.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.24 | 142.14 | 297.27 | 204.13 | 661.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2816.58 | 1480.54 | 1407.61 | 3425.53 | 1682.77 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2114124.55 | 0.167954E+10 |
February | 0.321175E+09 | 0.00 | 0.321175E+09 | 37761299.84 | 0.134004E+10 |
March | 0.523901E+09 | 0.00 | 0.523901E+09 | 0.173438E+09 | 0.120636E+10 |
April | 0.717457E+09 | 2545038.93 | 0.714912E+09 | 0.420443E+09 | 0.913507E+09 |
May | 0.953960E+09 | 28340757.90 | 0.925619E+09 | 0.746372E+09 | 0.723744E+09 |
June | 0.970708E+09 | 64101511.40 | 0.906607E+09 | 0.849326E+09 | 0.538157E+09 |
July | 0.953358E+09 | 74747816.12 | 0.878611E+09 | 0.948218E+09 | 0.496585E+09 |
August | 0.771750E+09 | 20862733.60 | 0.750888E+09 | 0.777879E+09 | 0.487150E+09 |
September | 0.580131E+09 | 171071.71 | 0.579959E+09 | 0.424965E+09 | 0.717637E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.150147E+09 | 0.105751E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18363197.03 | 0.135329E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 437064.00 | 0.173188E+10 |
Annual Sum or Average | 0.687626E+10 | 0.190769E+09 | 0.668549E+10 | 0.454946E+10 | 0.122454E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 437064.00 | 0.487150E+09 |
Maximum of Months | 0.970708E+09 | 74747816.12 | 0.925619E+09 | 0.948218E+09 | 0.173188E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2114105.85 | 0.167954E+10 |
February | 0.321174E+09 | 0.00 | 0.321174E+09 | 37761176.55 | 0.134004E+10 |
March | 0.523900E+09 | 0.00 | 0.523900E+09 | 0.173438E+09 | 0.120636E+10 |
April | 0.717457E+09 | 2545035.87 | 0.714911E+09 | 0.420442E+09 | 0.913507E+09 |
May | 0.953959E+09 | 28340723.90 | 0.925618E+09 | 0.746371E+09 | 0.723744E+09 |
June | 0.970707E+09 | 64101434.48 | 0.906606E+09 | 0.849325E+09 | 0.538157E+09 |
July | 0.953358E+09 | 74747726.43 | 0.878610E+09 | 0.948217E+09 | 0.496585E+09 |
August | 0.771750E+09 | 20862708.56 | 0.750887E+09 | 0.777878E+09 | 0.487150E+09 |
September | 0.580130E+09 | 171071.50 | 0.579959E+09 | 0.424965E+09 | 0.717637E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.150147E+09 | 0.105751E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18363130.89 | 0.135329E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 437059.26 | 0.173188E+10 |
Annual Sum or Average | 0.687625E+10 | 0.190769E+09 | 0.668549E+10 | 0.454946E+10 | 0.122454E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 437059.26 | 0.487150E+09 |
Maximum of Months | 0.970707E+09 | 74747726.43 | 0.925618E+09 | 0.948217E+09 | 0.173188E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2114124.55 | 0.167954E+10 |
February | 0.321175E+09 | 0.00 | 0.321175E+09 | 37761299.84 | 0.134004E+10 |
March | 0.523901E+09 | 0.00 | 0.523901E+09 | 0.173438E+09 | 0.120636E+10 |
April | 0.717457E+09 | 2545038.93 | 0.714912E+09 | 0.420443E+09 | 0.913507E+09 |
May | 0.953960E+09 | 28340757.90 | 0.925619E+09 | 0.746372E+09 | 0.723744E+09 |
June | 0.970708E+09 | 64101511.40 | 0.906607E+09 | 0.849326E+09 | 0.538157E+09 |
July | 0.953358E+09 | 74747816.12 | 0.878611E+09 | 0.948218E+09 | 0.496585E+09 |
August | 0.771750E+09 | 20862733.60 | 0.750888E+09 | 0.777879E+09 | 0.487150E+09 |
September | 0.580131E+09 | 171071.71 | 0.579959E+09 | 0.424965E+09 | 0.717637E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.150147E+09 | 0.105751E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18363197.03 | 0.135329E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 437064.00 | 0.173188E+10 |
Annual Sum or Average | 0.687626E+10 | 0.190769E+09 | 0.668549E+10 | 0.454946E+10 | 0.122454E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 437064.00 | 0.487150E+09 |
Maximum of Months | 0.970708E+09 | 74747816.12 | 0.925619E+09 | 0.948218E+09 | 0.173188E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228522E+09 | 0.00 | 0.228522E+09 | 2114105.85 | 0.167954E+10 |
February | 0.321174E+09 | 0.00 | 0.321174E+09 | 37761176.55 | 0.134004E+10 |
March | 0.523900E+09 | 0.00 | 0.523900E+09 | 0.173438E+09 | 0.120636E+10 |
April | 0.717457E+09 | 2545035.87 | 0.714911E+09 | 0.420442E+09 | 0.913507E+09 |
May | 0.953959E+09 | 28340723.90 | 0.925618E+09 | 0.746371E+09 | 0.723744E+09 |
June | 0.970707E+09 | 64101434.48 | 0.906606E+09 | 0.849325E+09 | 0.538157E+09 |
July | 0.953358E+09 | 74747726.43 | 0.878610E+09 | 0.948217E+09 | 0.496585E+09 |
August | 0.771750E+09 | 20862708.56 | 0.750887E+09 | 0.777878E+09 | 0.487150E+09 |
September | 0.580130E+09 | 171071.50 | 0.579959E+09 | 0.424965E+09 | 0.717637E+09 |
October | 0.410735E+09 | 0.00 | 0.410735E+09 | 0.150147E+09 | 0.105751E+10 |
November | 0.250377E+09 | 0.00 | 0.250377E+09 | 18363130.89 | 0.135329E+10 |
December | 0.194185E+09 | 0.00 | 0.194185E+09 | 437059.26 | 0.173188E+10 |
Annual Sum or Average | 0.687625E+10 | 0.190769E+09 | 0.668549E+10 | 0.454946E+10 | 0.122454E+11 |
Minimum of Months | 0.194185E+09 | 0.00 | 0.194185E+09 | 437059.26 | 0.487150E+09 |
Maximum of Months | 0.970707E+09 | 74747726.43 | 0.925618E+09 | 0.948217E+09 | 0.173188E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228513E+09 | 0.00 | 0.228513E+09 | 2114039.34 | 0.167947E+10 |
February | 0.321162E+09 | 0.00 | 0.321162E+09 | 37759777.90 | 0.133998E+10 |
March | 0.523879E+09 | 0.00 | 0.523879E+09 | 0.173431E+09 | 0.120632E+10 |
April | 0.717428E+09 | 2544936.35 | 0.714883E+09 | 0.420426E+09 | 0.913470E+09 |
May | 0.953921E+09 | 28339615.65 | 0.925582E+09 | 0.746342E+09 | 0.723715E+09 |
June | 0.970669E+09 | 64098927.82 | 0.906570E+09 | 0.849292E+09 | 0.538135E+09 |
July | 0.953320E+09 | 74744803.46 | 0.878575E+09 | 0.948180E+09 | 0.496565E+09 |
August | 0.771719E+09 | 20861892.74 | 0.750857E+09 | 0.777847E+09 | 0.487130E+09 |
September | 0.580107E+09 | 171064.81 | 0.579936E+09 | 0.424948E+09 | 0.717608E+09 |
October | 0.410719E+09 | 0.00 | 0.410719E+09 | 0.150141E+09 | 0.105746E+10 |
November | 0.250367E+09 | 0.00 | 0.250367E+09 | 18362456.92 | 0.135324E+10 |
December | 0.194177E+09 | 0.00 | 0.194177E+09 | 437046.39 | 0.173181E+10 |
Annual Sum or Average | 0.687598E+10 | 0.190761E+09 | 0.668522E+10 | 0.454928E+10 | 0.122449E+11 |
Minimum of Months | 0.194177E+09 | 0.00 | 0.194177E+09 | 437046.39 | 0.487130E+09 |
Maximum of Months | 0.970669E+09 | 74744803.46 | 0.925582E+09 | 0.948180E+09 | 0.173181E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408002E+09 | 0.103442E+09 | 0.304560E+09 | 0.121428E+09 | 0.175093E+10 |
February | 0.676194E+09 | 0.239995E+09 | 0.436198E+09 | 0.392158E+09 | 0.136987E+10 |
March | 0.111778E+10 | 0.404645E+09 | 0.713132E+09 | 0.878359E+09 | 0.124467E+10 |
April | 0.167685E+10 | 0.696756E+09 | 0.980094E+09 | 0.165629E+10 | 0.943088E+09 |
May | 0.184380E+10 | 0.641045E+09 | 0.120275E+10 | 0.193274E+10 | 0.802905E+09 |
June | 0.213692E+10 | 0.929790E+09 | 0.120713E+10 | 0.242748E+10 | 0.602518E+09 |
July | 0.205630E+10 | 0.922987E+09 | 0.113332E+10 | 0.244350E+10 | 0.539824E+09 |
August | 0.202106E+10 | 0.101105E+10 | 0.101001E+10 | 0.248785E+10 | 0.522324E+09 |
September | 0.144607E+10 | 0.666942E+09 | 0.779132E+09 | 0.156769E+10 | 0.760276E+09 |
October | 0.973968E+09 | 0.413845E+09 | 0.560123E+09 | 0.845618E+09 | 0.110408E+10 |
November | 0.461985E+09 | 0.130423E+09 | 0.331562E+09 | 0.212429E+09 | 0.139897E+10 |
December | 0.391563E+09 | 0.126056E+09 | 0.265507E+09 | 0.158127E+09 | 0.177476E+10 |
Annual Sum or Average | 0.152105E+11 | 0.628698E+10 | 0.892352E+10 | 0.151237E+11 | 0.128142E+11 |
Minimum of Months | 0.391563E+09 | 0.103442E+09 | 0.265507E+09 | 0.121428E+09 | 0.522324E+09 |
Maximum of Months | 0.213692E+10 | 0.101105E+10 | 0.120713E+10 | 0.248785E+10 | 0.177476E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408002E+09 | 0.103442E+09 | 0.304560E+09 | 0.121428E+09 | 0.175093E+10 |
February | 0.676194E+09 | 0.239995E+09 | 0.436198E+09 | 0.392158E+09 | 0.136987E+10 |
March | 0.111778E+10 | 0.404645E+09 | 0.713132E+09 | 0.878359E+09 | 0.124467E+10 |
April | 0.167685E+10 | 0.696756E+09 | 0.980094E+09 | 0.165629E+10 | 0.943088E+09 |
May | 0.184380E+10 | 0.641045E+09 | 0.120275E+10 | 0.193274E+10 | 0.802905E+09 |
June | 0.213692E+10 | 0.929790E+09 | 0.120713E+10 | 0.242748E+10 | 0.602518E+09 |
July | 0.205630E+10 | 0.922987E+09 | 0.113332E+10 | 0.244350E+10 | 0.539824E+09 |
August | 0.202106E+10 | 0.101105E+10 | 0.101001E+10 | 0.248785E+10 | 0.522324E+09 |
September | 0.144607E+10 | 0.666942E+09 | 0.779132E+09 | 0.156769E+10 | 0.760276E+09 |
October | 0.973968E+09 | 0.413845E+09 | 0.560123E+09 | 0.845618E+09 | 0.110408E+10 |
November | 0.461985E+09 | 0.130423E+09 | 0.331562E+09 | 0.212429E+09 | 0.139897E+10 |
December | 0.391563E+09 | 0.126056E+09 | 0.265507E+09 | 0.158127E+09 | 0.177476E+10 |
Annual Sum or Average | 0.152105E+11 | 0.628698E+10 | 0.892352E+10 | 0.151237E+11 | 0.128142E+11 |
Minimum of Months | 0.391563E+09 | 0.103442E+09 | 0.265507E+09 | 0.121428E+09 | 0.522324E+09 |
Maximum of Months | 0.213692E+10 | 0.101105E+10 | 0.120713E+10 | 0.248785E+10 | 0.177476E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407994E+09 | 0.103440E+09 | 0.304554E+09 | 0.121426E+09 | 0.175090E+10 |
February | 0.676181E+09 | 0.239991E+09 | 0.436190E+09 | 0.392151E+09 | 0.136985E+10 |
March | 0.111776E+10 | 0.404637E+09 | 0.713119E+09 | 0.878343E+09 | 0.124465E+10 |
April | 0.167682E+10 | 0.696743E+09 | 0.980077E+09 | 0.165626E+10 | 0.943070E+09 |
May | 0.184376E+10 | 0.641034E+09 | 0.120273E+10 | 0.193271E+10 | 0.802891E+09 |
June | 0.213688E+10 | 0.929773E+09 | 0.120711E+10 | 0.242744E+10 | 0.602507E+09 |
July | 0.205627E+10 | 0.922970E+09 | 0.113330E+10 | 0.244346E+10 | 0.539814E+09 |
August | 0.202102E+10 | 0.101103E+10 | 0.100999E+10 | 0.248781E+10 | 0.522315E+09 |
September | 0.144605E+10 | 0.666930E+09 | 0.779118E+09 | 0.156766E+10 | 0.760262E+09 |
October | 0.973950E+09 | 0.413837E+09 | 0.560113E+09 | 0.845602E+09 | 0.110406E+10 |
November | 0.461977E+09 | 0.130421E+09 | 0.331556E+09 | 0.212425E+09 | 0.139895E+10 |
December | 0.391556E+09 | 0.126053E+09 | 0.265502E+09 | 0.158124E+09 | 0.177472E+10 |
Annual Sum or Average | 0.152102E+11 | 0.628686E+10 | 0.892335E+10 | 0.151234E+11 | 0.128140E+11 |
Minimum of Months | 0.391556E+09 | 0.103440E+09 | 0.265502E+09 | 0.121426E+09 | 0.522315E+09 |
Maximum of Months | 0.213688E+10 | 0.101103E+10 | 0.120711E+10 | 0.248781E+10 | 0.177472E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.859780E+09 | 0.142960E+10 |
February | 0.140247E+10 | 0.868148E+09 | 0.534322E+09 | 0.137911E+10 | 0.116925E+10 |
March | 0.167029E+10 | 0.890750E+09 | 0.779544E+09 | 0.173730E+10 | 0.113855E+10 |
April | 0.170663E+10 | 0.741008E+09 | 0.965618E+09 | 0.188709E+10 | 0.922873E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181218E+10 | 0.771745E+09 |
June | 0.142770E+10 | 0.383319E+09 | 0.104438E+10 | 0.163997E+10 | 0.592331E+09 |
July | 0.160886E+10 | 0.589252E+09 | 0.101961E+10 | 0.204537E+10 | 0.550776E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227364E+10 | 0.532766E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829870E+09 | 0.228437E+10 | 0.721100E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663683E+09 | 0.193949E+10 | 0.999066E+09 |
November | 0.992577E+09 | 0.568830E+09 | 0.423747E+09 | 0.908367E+09 | 0.119093E+10 |
December | 0.107314E+10 | 0.694469E+09 | 0.378667E+09 | 0.101352E+10 | 0.149579E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871633E+10 | 0.910418E+10 | 0.197802E+11 | 0.115148E+11 |
Minimum of Months | 0.992577E+09 | 0.383319E+09 | 0.378667E+09 | 0.859780E+09 | 0.532766E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228437E+10 | 0.149579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.859779E+09 | 0.142960E+10 |
February | 0.140247E+10 | 0.868147E+09 | 0.534322E+09 | 0.137911E+10 | 0.116925E+10 |
March | 0.167029E+10 | 0.890748E+09 | 0.779544E+09 | 0.173730E+10 | 0.113855E+10 |
April | 0.170662E+10 | 0.741007E+09 | 0.965618E+09 | 0.188709E+10 | 0.922873E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181218E+10 | 0.771745E+09 |
June | 0.142770E+10 | 0.383318E+09 | 0.104438E+10 | 0.163997E+10 | 0.592331E+09 |
July | 0.160886E+10 | 0.589251E+09 | 0.101961E+10 | 0.204537E+10 | 0.550776E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227364E+10 | 0.532766E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829869E+09 | 0.228437E+10 | 0.721100E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663682E+09 | 0.193949E+10 | 0.999066E+09 |
November | 0.992575E+09 | 0.568829E+09 | 0.423746E+09 | 0.908365E+09 | 0.119093E+10 |
December | 0.107314E+10 | 0.694468E+09 | 0.378667E+09 | 0.101352E+10 | 0.149579E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871632E+10 | 0.910417E+10 | 0.197802E+11 | 0.115148E+11 |
Minimum of Months | 0.992575E+09 | 0.383318E+09 | 0.378667E+09 | 0.859779E+09 | 0.532766E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228437E+10 | 0.149579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.859780E+09 | 0.142960E+10 |
February | 0.140247E+10 | 0.868148E+09 | 0.534322E+09 | 0.137911E+10 | 0.116925E+10 |
March | 0.167029E+10 | 0.890750E+09 | 0.779544E+09 | 0.173730E+10 | 0.113855E+10 |
April | 0.170663E+10 | 0.741008E+09 | 0.965618E+09 | 0.188709E+10 | 0.922873E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181218E+10 | 0.771745E+09 |
June | 0.142770E+10 | 0.383319E+09 | 0.104438E+10 | 0.163997E+10 | 0.592331E+09 |
July | 0.160886E+10 | 0.589252E+09 | 0.101961E+10 | 0.204537E+10 | 0.550776E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227364E+10 | 0.532766E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829870E+09 | 0.228437E+10 | 0.721100E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663683E+09 | 0.193949E+10 | 0.999066E+09 |
November | 0.992577E+09 | 0.568830E+09 | 0.423747E+09 | 0.908367E+09 | 0.119093E+10 |
December | 0.107314E+10 | 0.694469E+09 | 0.378667E+09 | 0.101352E+10 | 0.149579E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871633E+10 | 0.910418E+10 | 0.197802E+11 | 0.115148E+11 |
Minimum of Months | 0.992577E+09 | 0.383319E+09 | 0.378667E+09 | 0.859780E+09 | 0.532766E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228437E+10 | 0.149579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100968E+10 | 0.599553E+09 | 0.410128E+09 | 0.859779E+09 | 0.142960E+10 |
February | 0.140247E+10 | 0.868147E+09 | 0.534322E+09 | 0.137911E+10 | 0.116925E+10 |
March | 0.167029E+10 | 0.890748E+09 | 0.779544E+09 | 0.173730E+10 | 0.113855E+10 |
April | 0.170662E+10 | 0.741007E+09 | 0.965618E+09 | 0.188709E+10 | 0.922873E+09 |
May | 0.161251E+10 | 0.480382E+09 | 0.113212E+10 | 0.181218E+10 | 0.771745E+09 |
June | 0.142770E+10 | 0.383318E+09 | 0.104438E+10 | 0.163997E+10 | 0.592331E+09 |
July | 0.160886E+10 | 0.589251E+09 | 0.101961E+10 | 0.204537E+10 | 0.550776E+09 |
August | 0.172852E+10 | 0.806038E+09 | 0.922483E+09 | 0.227364E+10 | 0.532766E+09 |
September | 0.185335E+10 | 0.102348E+10 | 0.829869E+09 | 0.228437E+10 | 0.721100E+09 |
October | 0.173478E+10 | 0.107110E+10 | 0.663682E+09 | 0.193949E+10 | 0.999066E+09 |
November | 0.992575E+09 | 0.568829E+09 | 0.423746E+09 | 0.908365E+09 | 0.119093E+10 |
December | 0.107314E+10 | 0.694468E+09 | 0.378667E+09 | 0.101352E+10 | 0.149579E+10 |
Annual Sum or Average | 0.178205E+11 | 0.871632E+10 | 0.910417E+10 | 0.197802E+11 | 0.115148E+11 |
Minimum of Months | 0.992575E+09 | 0.383318E+09 | 0.378667E+09 | 0.859779E+09 | 0.532766E+09 |
Maximum of Months | 0.185335E+10 | 0.107110E+10 | 0.113212E+10 | 0.228437E+10 | 0.149579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100964E+10 | 0.599529E+09 | 0.410112E+09 | 0.859746E+09 | 0.142955E+10 |
February | 0.140241E+10 | 0.868113E+09 | 0.534301E+09 | 0.137906E+10 | 0.116921E+10 |
March | 0.167023E+10 | 0.890714E+09 | 0.779513E+09 | 0.173723E+10 | 0.113850E+10 |
April | 0.170656E+10 | 0.740978E+09 | 0.965579E+09 | 0.188701E+10 | 0.922836E+09 |
May | 0.161244E+10 | 0.480363E+09 | 0.113208E+10 | 0.181211E+10 | 0.771714E+09 |
June | 0.142764E+10 | 0.383303E+09 | 0.104434E+10 | 0.163990E+10 | 0.592308E+09 |
July | 0.160880E+10 | 0.589228E+09 | 0.101957E+10 | 0.204529E+10 | 0.550754E+09 |
August | 0.172845E+10 | 0.806006E+09 | 0.922446E+09 | 0.227355E+10 | 0.532745E+09 |
September | 0.185328E+10 | 0.102344E+10 | 0.829837E+09 | 0.228428E+10 | 0.721071E+09 |
October | 0.173471E+10 | 0.107106E+10 | 0.663656E+09 | 0.193941E+10 | 0.999026E+09 |
November | 0.992537E+09 | 0.568807E+09 | 0.423730E+09 | 0.908330E+09 | 0.119088E+10 |
December | 0.107309E+10 | 0.694441E+09 | 0.378652E+09 | 0.101348E+10 | 0.149573E+10 |
Annual Sum or Average | 0.178198E+11 | 0.871598E+10 | 0.910381E+10 | 0.197794E+11 | 0.115143E+11 |
Minimum of Months | 0.992537E+09 | 0.383303E+09 | 0.378652E+09 | 0.859746E+09 | 0.532745E+09 |
Maximum of Months | 0.185328E+10 | 0.107106E+10 | 0.113208E+10 | 0.228428E+10 | 0.149573E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430342E+09 | 0.126900E+09 | 0.303442E+09 | 0.153428E+09 | 0.189000E+10 |
February | 0.696902E+09 | 0.261915E+09 | 0.434986E+09 | 0.427953E+09 | 0.154035E+10 |
March | 0.108117E+10 | 0.364923E+09 | 0.716244E+09 | 0.822273E+09 | 0.144146E+10 |
April | 0.159182E+10 | 0.608613E+09 | 0.983205E+09 | 0.150719E+10 | 0.114492E+10 |
May | 0.211658E+10 | 0.859850E+09 | 0.125673E+10 | 0.228288E+10 | 0.904834E+09 |
June | 0.196990E+10 | 0.764848E+09 | 0.120505E+10 | 0.216658E+10 | 0.711555E+09 |
July | 0.251466E+10 | 0.132184E+10 | 0.119283E+10 | 0.304811E+10 | 0.688591E+09 |
August | 0.208023E+10 | 0.106223E+10 | 0.101800E+10 | 0.254356E+10 | 0.688095E+09 |
September | 0.163938E+10 | 0.786612E+09 | 0.852771E+09 | 0.185086E+10 | 0.867313E+09 |
October | 0.964416E+09 | 0.392954E+09 | 0.571463E+09 | 0.826326E+09 | 0.126626E+10 |
November | 0.464781E+09 | 0.131087E+09 | 0.333693E+09 | 0.208854E+09 | 0.160398E+10 |
December | 0.403763E+09 | 0.138359E+09 | 0.265403E+09 | 0.183456E+09 | 0.207501E+10 |
Annual Sum or Average | 0.159539E+11 | 0.682012E+10 | 0.913382E+10 | 0.160215E+11 | 0.148224E+11 |
Minimum of Months | 0.403763E+09 | 0.126900E+09 | 0.265403E+09 | 0.153428E+09 | 0.688095E+09 |
Maximum of Months | 0.251466E+10 | 0.132184E+10 | 0.125673E+10 | 0.304811E+10 | 0.207501E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430342E+09 | 0.126900E+09 | 0.303442E+09 | 0.153428E+09 | 0.189000E+10 |
February | 0.696902E+09 | 0.261915E+09 | 0.434986E+09 | 0.427953E+09 | 0.154035E+10 |
March | 0.108117E+10 | 0.364923E+09 | 0.716244E+09 | 0.822273E+09 | 0.144146E+10 |
April | 0.159182E+10 | 0.608613E+09 | 0.983205E+09 | 0.150719E+10 | 0.114492E+10 |
May | 0.211658E+10 | 0.859850E+09 | 0.125673E+10 | 0.228288E+10 | 0.904834E+09 |
June | 0.196990E+10 | 0.764848E+09 | 0.120505E+10 | 0.216658E+10 | 0.711555E+09 |
July | 0.251466E+10 | 0.132184E+10 | 0.119283E+10 | 0.304811E+10 | 0.688591E+09 |
August | 0.208023E+10 | 0.106223E+10 | 0.101800E+10 | 0.254356E+10 | 0.688095E+09 |
September | 0.163938E+10 | 0.786612E+09 | 0.852771E+09 | 0.185086E+10 | 0.867313E+09 |
October | 0.964416E+09 | 0.392954E+09 | 0.571463E+09 | 0.826326E+09 | 0.126626E+10 |
November | 0.464781E+09 | 0.131087E+09 | 0.333693E+09 | 0.208854E+09 | 0.160398E+10 |
December | 0.403763E+09 | 0.138359E+09 | 0.265403E+09 | 0.183456E+09 | 0.207501E+10 |
Annual Sum or Average | 0.159539E+11 | 0.682012E+10 | 0.913382E+10 | 0.160215E+11 | 0.148224E+11 |
Minimum of Months | 0.403763E+09 | 0.126900E+09 | 0.265403E+09 | 0.153428E+09 | 0.688095E+09 |
Maximum of Months | 0.251466E+10 | 0.132184E+10 | 0.125673E+10 | 0.304811E+10 | 0.207501E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.430334E+09 | 0.126898E+09 | 0.303437E+09 | 0.153425E+09 | 0.188996E+10 |
February | 0.696889E+09 | 0.261911E+09 | 0.434979E+09 | 0.427946E+09 | 0.154032E+10 |
March | 0.108115E+10 | 0.364916E+09 | 0.716231E+09 | 0.822258E+09 | 0.144143E+10 |
April | 0.159179E+10 | 0.608602E+09 | 0.983187E+09 | 0.150717E+10 | 0.114490E+10 |
May | 0.211654E+10 | 0.859835E+09 | 0.125670E+10 | 0.228283E+10 | 0.904818E+09 |
June | 0.196987E+10 | 0.764834E+09 | 0.120503E+10 | 0.216654E+10 | 0.711542E+09 |
July | 0.251462E+10 | 0.132181E+10 | 0.119281E+10 | 0.304805E+10 | 0.688578E+09 |
August | 0.208019E+10 | 0.106221E+10 | 0.101799E+10 | 0.254351E+10 | 0.688082E+09 |
September | 0.163935E+10 | 0.786597E+09 | 0.852756E+09 | 0.185082E+10 | 0.867297E+09 |
October | 0.964399E+09 | 0.392946E+09 | 0.571452E+09 | 0.826311E+09 | 0.126623E+10 |
November | 0.464772E+09 | 0.131085E+09 | 0.333687E+09 | 0.208850E+09 | 0.160395E+10 |
December | 0.403755E+09 | 0.138357E+09 | 0.265399E+09 | 0.183452E+09 | 0.207498E+10 |
Annual Sum or Average | 0.159537E+11 | 0.682000E+10 | 0.913365E+10 | 0.160212E+11 | 0.148221E+11 |
Minimum of Months | 0.403755E+09 | 0.126898E+09 | 0.265399E+09 | 0.153425E+09 | 0.688082E+09 |
Maximum of Months | 0.251462E+10 | 0.132181E+10 | 0.125670E+10 | 0.304805E+10 | 0.207498E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114260E+10 | 0.00 | 0.114260E+10 | 32266911.94 | 0.721531E+10 |
February | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.283952E+09 | 0.583114E+10 |
March | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.102551E+10 | 0.536242E+10 |
April | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.225595E+10 | 0.413295E+10 |
May | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.380524E+10 | 0.343632E+10 |
June | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.430663E+10 | 0.255290E+10 |
July | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.481586E+10 | 0.235967E+10 |
August | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.397032E+10 | 0.231064E+10 |
September | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.219222E+10 | 0.335799E+10 |
October | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.880319E+09 | 0.470775E+10 |
November | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.150046E+09 | 0.576275E+10 |
December | 0.970912E+09 | 0.00 | 0.970912E+09 | 14081962.67 | 0.730067E+10 |
Annual Sum or Average | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.237324E+11 | 0.543305E+11 |
Minimum of Months | 0.970912E+09 | 0.00 | 0.970912E+09 | 14081962.67 | 0.231064E+10 |
Maximum of Months | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.481586E+10 | 0.730067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.412505E+09 | 0.458872E+10 |
February | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.125095E+10 | 0.372368E+10 |
March | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.266605E+10 | 0.347780E+10 |
April | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.495947E+10 | 0.269939E+10 |
May | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.576614E+10 | 0.233709E+10 |
June | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.722041E+10 | 0.177104E+10 |
July | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.727418E+10 | 0.160161E+10 |
August | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.740060E+10 | 0.156975E+10 |
September | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.468250E+10 | 0.219814E+10 |
October | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.256627E+10 | 0.307598E+10 |
November | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.683808E+09 | 0.374089E+10 |
December | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.520432E+09 | 0.469793E+10 |
Annual Sum or Average | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.454033E+11 | 0.354820E+11 |
Minimum of Months | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.412505E+09 | 0.156975E+10 |
Maximum of Months | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.740060E+10 | 0.469793E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.434692E+10 | 0.668476E+10 |
February | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.691686E+10 | 0.558066E+10 |
March | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.866890E+10 | 0.544619E+10 |
April | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.940321E+10 | 0.443320E+10 |
May | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.899692E+10 | 0.378358E+10 |
June | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.815623E+10 | 0.287736E+10 |
July | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.101825E+11 | 0.268249E+10 |
August | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.113238E+11 | 0.260816E+10 |
September | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.113677E+11 | 0.354279E+10 |
October | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.965393E+10 | 0.481643E+10 |
November | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.458306E+10 | 0.558198E+10 |
December | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.512177E+10 | 0.693073E+10 |
Annual Sum or Average | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.987218E+11 | 0.549683E+11 |
Minimum of Months | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.434692E+10 | 0.260816E+10 |
Maximum of Months | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.113677E+11 | 0.693073E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.515883E+09 | 0.476422E+10 |
February | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.139016E+10 | 0.387541E+10 |
March | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.259564E+10 | 0.366271E+10 |
April | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.466743E+10 | 0.294791E+10 |
May | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.686935E+10 | 0.253935E+10 |
June | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.655379E+10 | 0.193546E+10 |
July | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.920705E+10 | 0.185637E+10 |
August | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.772883E+10 | 0.180785E+10 |
September | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.558438E+10 | 0.240800E+10 |
October | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.257632E+10 | 0.327480E+10 |
November | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.713175E+09 | 0.387472E+10 |
December | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.619316E+09 | 0.489607E+10 |
Annual Sum or Average | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.490213E+11 | 0.378429E+11 |
Minimum of Months | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.515883E+09 | 0.180785E+10 |
Maximum of Months | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.920705E+10 | 0.489607E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114260E+10 | 0.00 | 0.114260E+10 | 55170184.89 | 0.664188E+10 |
February | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.353837E+09 | 0.531606E+10 |
March | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.115520E+10 | 0.488870E+10 |
April | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.236437E+10 | 0.386017E+10 |
May | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.387363E+10 | 0.327537E+10 |
June | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.431581E+10 | 0.248343E+10 |
July | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.480115E+10 | 0.231311E+10 |
August | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.396824E+10 | 0.225334E+10 |
September | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.225287E+10 | 0.316044E+10 |
October | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.100691E+10 | 0.424703E+10 |
November | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.208048E+09 | 0.512910E+10 |
December | 0.970912E+09 | 0.00 | 0.970912E+09 | 34418847.21 | 0.661908E+10 |
Annual Sum or Average | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.243896E+11 | 0.501877E+11 |
Minimum of Months | 0.970912E+09 | 0.00 | 0.970912E+09 | 34418847.21 | 0.225334E+10 |
Maximum of Months | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.480115E+10 | 0.664188E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.455295E+09 | 0.421766E+10 |
February | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.134109E+10 | 0.338568E+10 |
March | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.277286E+10 | 0.318136E+10 |
April | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.503424E+10 | 0.254105E+10 |
May | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.581084E+10 | 0.223845E+10 |
June | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.722519E+10 | 0.172897E+10 |
July | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.727287E+10 | 0.157572E+10 |
August | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.740398E+10 | 0.153684E+10 |
September | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.472874E+10 | 0.208171E+10 |
October | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.266534E+10 | 0.279317E+10 |
November | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.756558E+09 | 0.332353E+10 |
December | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.572161E+09 | 0.425200E+10 |
Annual Sum or Average | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.460392E+11 | 0.328561E+11 |
Minimum of Months | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.455295E+09 | 0.153684E+10 |
Maximum of Months | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.740398E+10 | 0.425200E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.446599E+10 | 0.613188E+10 |
February | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.706477E+10 | 0.510742E+10 |
March | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.877433E+10 | 0.501689E+10 |
April | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.947051E+10 | 0.418556E+10 |
May | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.902662E+10 | 0.362010E+10 |
June | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.814202E+10 | 0.280089E+10 |
July | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.101504E+11 | 0.263486E+10 |
August | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.112982E+11 | 0.255151E+10 |
September | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.113996E+11 | 0.337413E+10 |
October | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.975683E+10 | 0.442565E+10 |
November | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.471520E+10 | 0.501646E+10 |
December | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.523903E+10 | 0.630014E+10 |
Annual Sum or Average | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.995035E+11 | 0.511655E+11 |
Minimum of Months | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.446599E+10 | 0.255151E+10 |
Maximum of Months | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.113996E+11 | 0.630014E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.546738E+09 | 0.439998E+10 |
February | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.144474E+10 | 0.358120E+10 |
March | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.266166E+10 | 0.339607E+10 |
April | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.471208E+10 | 0.279419E+10 |
May | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.687918E+10 | 0.244203E+10 |
June | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.653596E+10 | 0.188766E+10 |
July | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.917493E+10 | 0.182393E+10 |
August | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.770618E+10 | 0.177172E+10 |
September | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.559913E+10 | 0.230274E+10 |
October | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.263914E+10 | 0.302046E+10 |
November | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.760892E+09 | 0.352200E+10 |
December | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.648963E+09 | 0.450714E+10 |
Annual Sum or Average | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.493096E+11 | 0.354491E+11 |
Minimum of Months | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.546738E+09 | 0.177172E+10 |
Maximum of Months | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.917493E+10 | 0.450714E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.95 | 3135.31 | 426.60 | 0.00 | 426.60 | 0.00 | 0.00 |
February | 78.04 | 2769.56 | 663.80 | 0.00 | 663.80 | 0.00 | 0.00 |
March | 323.77 | 2252.01 | 978.00 | 0.00 | 978.00 | 0.00 | 0.00 |
April | 811.03 | 1762.15 | 1383.97 | 4.91 | 1379.06 | 0.00 | 0.00 |
May | 1393.30 | 1351.07 | 1780.82 | 52.91 | 1727.92 | 0.00 | 0.00 |
June | 1638.35 | 1038.10 | 1872.49 | 123.65 | 1748.84 | 0.00 | 0.00 |
July | 1770.10 | 927.01 | 1779.70 | 139.54 | 1640.16 | 0.00 | 0.00 |
August | 1452.12 | 909.40 | 1440.68 | 38.95 | 1401.74 | 0.00 | 0.00 |
September | 819.76 | 1384.32 | 1119.07 | 0.33 | 1118.74 | 0.00 | 0.00 |
October | 280.29 | 1974.12 | 766.75 | 0.00 | 766.75 | 0.00 | 0.00 |
November | 35.42 | 2610.50 | 482.98 | 0.00 | 482.98 | 0.00 | 0.00 |
December | 0.82 | 3233.02 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Annual Sum or Average | 721.31 | 1941.48 | 1090.21 | 30.25 | 1059.97 | 0.00 | 0.00 |
Minimum of Months | 0.82 | 909.40 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Maximum of Months | 1770.10 | 3233.02 | 1872.49 | 139.54 | 1748.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.01 | 1961.16 | 456.99 | 115.86 | 341.13 | 0.00 | 0.00 |
February | 486.30 | 1698.74 | 838.53 | 297.61 | 540.92 | 0.00 | 0.00 |
March | 983.82 | 1394.11 | 1251.98 | 453.23 | 798.75 | 0.00 | 0.00 |
April | 1917.00 | 1091.53 | 1940.79 | 806.43 | 1134.36 | 0.00 | 0.00 |
May | 2164.80 | 899.31 | 2065.17 | 718.01 | 1347.16 | 0.00 | 0.00 |
June | 2809.57 | 697.35 | 2473.27 | 1076.14 | 1397.14 | 0.00 | 0.00 |
July | 2736.88 | 604.64 | 2303.19 | 1033.81 | 1269.39 | 0.00 | 0.00 |
August | 2786.56 | 585.04 | 2263.72 | 1132.44 | 1131.28 | 0.00 | 0.00 |
September | 1814.45 | 879.94 | 1673.69 | 771.92 | 901.77 | 0.00 | 0.00 |
October | 947.15 | 1236.64 | 1090.91 | 463.53 | 627.37 | 0.00 | 0.00 |
November | 245.87 | 1619.17 | 534.70 | 150.95 | 383.75 | 0.00 | 0.00 |
December | 177.11 | 1987.84 | 438.58 | 141.19 | 297.39 | 0.00 | 0.00 |
Annual Sum or Average | 1438.70 | 1219.00 | 1446.96 | 598.07 | 848.88 | 0.00 | 0.00 |
Minimum of Months | 136.01 | 585.04 | 438.58 | 115.86 | 297.39 | 0.00 | 0.00 |
Maximum of Months | 2809.57 | 1987.84 | 2473.27 | 1132.44 | 1397.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1605.01 | 2668.74 | 1884.84 | 1119.23 | 765.61 | 0.00 | 0.00 |
February | 2850.33 | 2416.59 | 2898.60 | 1794.27 | 1104.33 | 0.00 | 0.00 |
March | 3243.14 | 2125.41 | 3118.06 | 1662.82 | 1455.23 | 0.00 | 0.00 |
April | 3640.19 | 1780.22 | 3292.07 | 1429.40 | 1862.67 | 0.00 | 0.00 |
May | 3382.93 | 1440.67 | 3010.18 | 896.76 | 2113.42 | 0.00 | 0.00 |
June | 3163.49 | 1142.61 | 2754.02 | 739.42 | 2014.60 | 0.00 | 0.00 |
July | 3818.24 | 1028.17 | 3003.38 | 1100.00 | 1903.38 | 0.00 | 0.00 |
August | 4244.37 | 994.55 | 3226.75 | 1504.69 | 1722.06 | 0.00 | 0.00 |
September | 4406.54 | 1391.00 | 3575.11 | 1974.29 | 1600.82 | 0.00 | 0.00 |
October | 3620.59 | 1865.03 | 3238.44 | 1999.50 | 1238.94 | 0.00 | 0.00 |
November | 1752.24 | 2297.29 | 1914.68 | 1097.27 | 817.41 | 0.00 | 0.00 |
December | 1892.00 | 2792.31 | 2003.30 | 1296.41 | 706.89 | 0.00 | 0.00 |
Annual Sum or Average | 3136.10 | 1825.64 | 2825.40 | 1381.95 | 1443.45 | 0.00 | 0.00 |
Minimum of Months | 1605.01 | 994.55 | 1884.84 | 739.42 | 706.89 | 0.00 | 0.00 |
Maximum of Months | 4406.54 | 2792.31 | 3575.11 | 1999.50 | 2113.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.85 | 2116.92 | 482.01 | 142.14 | 339.87 | 0.00 | 0.00 |
February | 530.69 | 1910.15 | 864.21 | 324.79 | 539.41 | 0.00 | 0.00 |
March | 921.00 | 1614.53 | 1210.98 | 408.74 | 802.24 | 0.00 | 0.00 |
April | 1744.43 | 1325.13 | 1842.37 | 704.41 | 1137.96 | 0.00 | 0.00 |
May | 2556.97 | 1013.47 | 2370.70 | 963.09 | 1407.61 | 0.00 | 0.00 |
June | 2507.60 | 823.55 | 2279.97 | 885.24 | 1394.73 | 0.00 | 0.00 |
July | 3414.08 | 771.27 | 2816.59 | 1480.54 | 1336.04 | 0.00 | 0.00 |
August | 2848.95 | 770.71 | 2329.99 | 1189.76 | 1140.23 | 0.00 | 0.00 |
September | 2142.18 | 1003.83 | 1897.42 | 910.42 | 987.00 | 0.00 | 0.00 |
October | 925.54 | 1418.29 | 1080.21 | 440.13 | 640.08 | 0.00 | 0.00 |
November | 241.73 | 1856.44 | 537.94 | 151.72 | 386.22 | 0.00 | 0.00 |
December | 205.48 | 2324.15 | 452.24 | 154.97 | 297.27 | 0.00 | 0.00 |
Annual Sum or Average | 1524.10 | 1410.03 | 1517.68 | 648.79 | 868.89 | 0.00 | 0.00 |
Minimum of Months | 171.85 | 770.71 | 452.24 | 142.14 | 297.27 | 0.00 | 0.00 |
Maximum of Months | 3414.08 | 2324.15 | 2816.59 | 1480.54 | 1407.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.05 | 2693.89 | 426.60 | 0.00 | 426.60 | 0.00 | 0.00 |
February | 117.37 | 2410.36 | 663.80 | 0.00 | 663.80 | 0.00 | 0.00 |
March | 382.88 | 2002.10 | 978.00 | 0.00 | 978.00 | 0.00 | 0.00 |
April | 870.35 | 1594.50 | 1383.97 | 4.91 | 1379.06 | 0.00 | 0.00 |
May | 1420.72 | 1282.98 | 1780.82 | 52.91 | 1727.91 | 0.00 | 0.00 |
June | 1661.51 | 984.92 | 1872.49 | 123.65 | 1748.83 | 0.00 | 0.00 |
July | 1798.04 | 881.00 | 1779.69 | 139.54 | 1640.16 | 0.00 | 0.00 |
August | 1482.35 | 862.69 | 1440.68 | 38.95 | 1401.73 | 0.00 | 0.00 |
September | 845.76 | 1295.52 | 1119.07 | 0.33 | 1118.74 | 0.00 | 0.00 |
October | 328.67 | 1757.67 | 766.75 | 0.00 | 766.75 | 0.00 | 0.00 |
November | 57.89 | 2223.28 | 482.97 | 0.00 | 482.97 | 0.00 | 0.00 |
December | 5.26 | 2725.76 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Annual Sum or Average | 752.55 | 1722.81 | 1090.21 | 30.25 | 1059.96 | 0.00 | 0.00 |
Minimum of Months | 5.26 | 862.69 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Maximum of Months | 1798.04 | 2725.76 | 1872.49 | 139.54 | 1748.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 154.01 | 1713.23 | 456.99 | 115.86 | 341.13 | 0.00 | 0.00 |
February | 517.09 | 1539.22 | 838.53 | 297.61 | 540.92 | 0.00 | 0.00 |
March | 995.39 | 1298.46 | 1251.98 | 453.23 | 798.75 | 0.00 | 0.00 |
April | 1913.38 | 1041.43 | 1940.78 | 806.42 | 1134.36 | 0.00 | 0.00 |
May | 2152.83 | 872.57 | 2065.16 | 718.01 | 1347.15 | 0.00 | 0.00 |
June | 2785.65 | 683.27 | 2473.26 | 1076.14 | 1397.13 | 0.00 | 0.00 |
July | 2715.87 | 597.97 | 2303.18 | 1033.80 | 1269.38 | 0.00 | 0.00 |
August | 2763.07 | 586.08 | 2263.71 | 1132.44 | 1131.27 | 0.00 | 0.00 |
September | 1806.52 | 848.05 | 1673.68 | 771.92 | 901.76 | 0.00 | 0.00 |
October | 958.13 | 1148.44 | 1090.90 | 463.53 | 627.37 | 0.00 | 0.00 |
November | 263.81 | 1443.24 | 534.70 | 150.95 | 383.75 | 0.00 | 0.00 |
December | 194.31 | 1754.01 | 438.57 | 141.19 | 297.38 | 0.00 | 0.00 |
Annual Sum or Average | 1439.73 | 1125.13 | 1446.95 | 598.07 | 848.88 | 0.00 | 0.00 |
Minimum of Months | 154.01 | 586.08 | 438.57 | 115.86 | 297.38 | 0.00 | 0.00 |
Maximum of Months | 2785.65 | 1754.01 | 2473.26 | 1132.44 | 1397.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1622.95 | 2495.80 | 1884.84 | 1119.22 | 765.61 | 0.00 | 0.00 |
February | 2859.15 | 2306.82 | 2898.59 | 1794.27 | 1104.32 | 0.00 | 0.00 |
March | 3236.60 | 2033.37 | 3118.04 | 1662.82 | 1455.23 | 0.00 | 0.00 |
April | 3627.78 | 1710.34 | 3292.06 | 1429.40 | 1862.67 | 0.00 | 0.00 |
May | 3359.07 | 1412.63 | 3010.17 | 896.76 | 2113.41 | 0.00 | 0.00 |
June | 3146.69 | 1110.09 | 2754.01 | 739.42 | 2014.59 | 0.00 | 0.00 |
July | 3801.70 | 1001.53 | 3003.37 | 1099.99 | 1903.38 | 0.00 | 0.00 |
August | 4227.83 | 973.78 | 3226.74 | 1504.68 | 1722.06 | 0.00 | 0.00 |
September | 4385.67 | 1366.82 | 3575.10 | 1974.29 | 1600.81 | 0.00 | 0.00 |
October | 3604.36 | 1798.25 | 3238.43 | 1999.49 | 1238.94 | 0.00 | 0.00 |
November | 1768.16 | 2153.54 | 1914.67 | 1097.27 | 817.40 | 0.00 | 0.00 |
December | 1912.25 | 2587.64 | 2003.29 | 1296.41 | 706.88 | 0.00 | 0.00 |
Annual Sum or Average | 3130.45 | 1743.03 | 2825.39 | 1381.95 | 1443.44 | 0.00 | 0.00 |
Minimum of Months | 1622.95 | 973.78 | 1884.84 | 739.42 | 706.88 | 0.00 | 0.00 |
Maximum of Months | 4385.67 | 2587.64 | 3575.10 | 1999.49 | 2113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.61 | 1778.75 | 482.01 | 142.14 | 339.87 | 0.00 | 0.00 |
February | 574.64 | 1601.94 | 864.20 | 324.79 | 539.41 | 0.00 | 0.00 |
March | 969.10 | 1367.50 | 1210.97 | 408.74 | 802.24 | 0.00 | 0.00 |
April | 1800.70 | 1137.31 | 1842.36 | 704.41 | 1137.96 | 0.00 | 0.00 |
May | 2564.72 | 948.08 | 2370.69 | 963.08 | 1407.61 | 0.00 | 0.00 |
June | 2528.47 | 746.71 | 2279.96 | 885.23 | 1394.72 | 0.00 | 0.00 |
July | 3437.52 | 693.09 | 2816.58 | 1480.54 | 1336.04 | 0.00 | 0.00 |
August | 2885.62 | 674.98 | 2329.98 | 1189.76 | 1140.23 | 0.00 | 0.00 |
September | 2154.47 | 929.01 | 1897.41 | 910.42 | 986.99 | 0.00 | 0.00 |
October | 961.89 | 1222.67 | 1080.20 | 440.13 | 640.07 | 0.00 | 0.00 |
November | 275.14 | 1494.88 | 537.94 | 151.72 | 386.21 | 0.00 | 0.00 |
December | 231.23 | 1827.98 | 452.24 | 154.97 | 297.27 | 0.00 | 0.00 |
Annual Sum or Average | 1554.46 | 1199.99 | 1517.67 | 648.79 | 868.89 | 0.00 | 0.00 |
Minimum of Months | 192.61 | 674.98 | 452.24 | 142.14 | 297.27 | 0.00 | 0.00 |
Maximum of Months | 3437.52 | 1827.98 | 2816.58 | 1480.54 | 1407.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.60 | 2479.79 | 426.60 | 0.00 | 426.60 | 0.00 | 0.00 |
February | 146.26 | 2197.45 | 663.80 | 0.00 | 663.80 | 0.00 | 0.00 |
March | 431.30 | 1825.23 | 978.00 | 0.00 | 978.00 | 0.00 | 0.00 |
April | 912.18 | 1489.26 | 1383.97 | 4.91 | 1379.06 | 0.00 | 0.00 |
May | 1446.25 | 1222.88 | 1780.82 | 52.91 | 1727.91 | 0.00 | 0.00 |
June | 1665.05 | 958.11 | 1872.49 | 123.65 | 1748.83 | 0.00 | 0.00 |
July | 1792.54 | 863.62 | 1779.69 | 139.54 | 1640.16 | 0.00 | 0.00 |
August | 1481.57 | 841.30 | 1440.68 | 38.95 | 1401.73 | 0.00 | 0.00 |
September | 869.16 | 1219.31 | 1119.07 | 0.33 | 1118.74 | 0.00 | 0.00 |
October | 375.94 | 1585.66 | 766.75 | 0.00 | 766.75 | 0.00 | 0.00 |
November | 80.27 | 1978.82 | 482.97 | 0.00 | 482.97 | 0.00 | 0.00 |
December | 12.85 | 2471.28 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Annual Sum or Average | 773.39 | 1591.44 | 1090.21 | 30.25 | 1059.96 | 0.00 | 0.00 |
Minimum of Months | 12.85 | 841.30 | 362.50 | 0.00 | 362.50 | 0.00 | 0.00 |
Maximum of Months | 1792.54 | 2479.79 | 1872.49 | 139.54 | 1748.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.99 | 1574.69 | 456.99 | 115.86 | 341.13 | 0.00 | 0.00 |
February | 554.35 | 1399.50 | 838.53 | 297.61 | 540.92 | 0.00 | 0.00 |
March | 1035.27 | 1187.78 | 1251.98 | 453.23 | 798.75 | 0.00 | 0.00 |
April | 1942.22 | 980.34 | 1940.78 | 806.42 | 1134.36 | 0.00 | 0.00 |
May | 2169.52 | 835.74 | 2065.16 | 718.01 | 1347.15 | 0.00 | 0.00 |
June | 2787.50 | 667.04 | 2473.26 | 1076.14 | 1397.13 | 0.00 | 0.00 |
July | 2715.38 | 588.31 | 2303.18 | 1033.80 | 1269.38 | 0.00 | 0.00 |
August | 2764.33 | 573.79 | 2263.71 | 1132.44 | 1131.27 | 0.00 | 0.00 |
September | 1824.36 | 803.13 | 1673.68 | 771.92 | 901.76 | 0.00 | 0.00 |
October | 995.13 | 1042.85 | 1090.90 | 463.53 | 627.37 | 0.00 | 0.00 |
November | 291.88 | 1282.22 | 534.70 | 150.95 | 383.75 | 0.00 | 0.00 |
December | 213.62 | 1587.51 | 438.57 | 141.19 | 297.38 | 0.00 | 0.00 |
Annual Sum or Average | 1459.89 | 1041.86 | 1446.95 | 598.07 | 848.88 | 0.00 | 0.00 |
Minimum of Months | 169.99 | 573.79 | 438.57 | 115.86 | 297.38 | 0.00 | 0.00 |
Maximum of Months | 2787.50 | 1587.51 | 2473.26 | 1132.44 | 1397.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1667.41 | 2289.38 | 1884.84 | 1119.22 | 765.61 | 0.00 | 0.00 |
February | 2920.29 | 2111.20 | 2898.59 | 1794.27 | 1104.32 | 0.00 | 0.00 |
March | 3275.96 | 1873.09 | 3118.04 | 1662.82 | 1455.23 | 0.00 | 0.00 |
April | 3653.74 | 1614.80 | 3292.06 | 1429.40 | 1862.67 | 0.00 | 0.00 |
May | 3370.15 | 1351.59 | 3010.17 | 896.76 | 2113.41 | 0.00 | 0.00 |
June | 3141.21 | 1080.59 | 2754.01 | 739.42 | 2014.59 | 0.00 | 0.00 |
July | 3789.73 | 983.74 | 3003.37 | 1099.99 | 1903.38 | 0.00 | 0.00 |
August | 4218.25 | 952.62 | 3226.74 | 1504.68 | 1722.06 | 0.00 | 0.00 |
September | 4398.01 | 1301.75 | 3575.10 | 1974.29 | 1600.81 | 0.00 | 0.00 |
October | 3642.78 | 1652.35 | 3238.43 | 1999.49 | 1238.94 | 0.00 | 0.00 |
November | 1819.14 | 1935.36 | 1914.67 | 1097.27 | 817.40 | 0.00 | 0.00 |
December | 1956.03 | 2352.20 | 2003.29 | 1296.41 | 706.88 | 0.00 | 0.00 |
Annual Sum or Average | 3155.24 | 1622.45 | 2825.39 | 1381.95 | 1443.44 | 0.00 | 0.00 |
Minimum of Months | 1667.41 | 952.62 | 1884.84 | 739.42 | 706.88 | 0.00 | 0.00 |
Maximum of Months | 4398.01 | 2352.20 | 3575.10 | 1999.49 | 2113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 204.13 | 1642.76 | 482.01 | 142.14 | 339.87 | 0.00 | 0.00 |
February | 597.20 | 1480.32 | 864.20 | 324.79 | 539.41 | 0.00 | 0.00 |
March | 993.75 | 1267.95 | 1210.97 | 408.74 | 802.24 | 0.00 | 0.00 |
April | 1817.93 | 1078.00 | 1842.36 | 704.41 | 1137.96 | 0.00 | 0.00 |
May | 2568.39 | 911.75 | 2370.69 | 963.08 | 1407.61 | 0.00 | 0.00 |
June | 2521.59 | 728.27 | 2279.96 | 885.23 | 1394.72 | 0.00 | 0.00 |
July | 3425.53 | 680.98 | 2816.58 | 1480.54 | 1336.04 | 0.00 | 0.00 |
August | 2877.16 | 661.48 | 2329.98 | 1189.76 | 1140.23 | 0.00 | 0.00 |
September | 2160.16 | 888.40 | 1897.41 | 910.42 | 986.99 | 0.00 | 0.00 |
October | 985.34 | 1127.71 | 1080.20 | 440.13 | 640.07 | 0.00 | 0.00 |
November | 293.55 | 1358.80 | 537.94 | 151.72 | 386.21 | 0.00 | 0.00 |
December | 242.29 | 1682.77 | 452.24 | 154.97 | 297.27 | 0.00 | 0.00 |
Annual Sum or Average | 1563.60 | 1124.08 | 1517.67 | 648.79 | 868.89 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 661.48 | 452.24 | 142.14 | 297.27 | 0.00 | 0.00 |
Maximum of Months | 3425.53 | 1682.77 | 2816.58 | 1480.54 | 1407.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 10570500.16 | 0.839762E+10 | 0.114260E+10 | 0.00 | 0.114260E+10 | 0.00 | 0.00 |
February | 0.188805E+09 | 0.670013E+10 | 0.160586E+10 | 0.00 | 0.160586E+10 | 0.00 | 0.00 |
March | 0.867182E+09 | 0.603178E+10 | 0.261948E+10 | 0.00 | 0.261948E+10 | 0.00 | 0.00 |
April | 0.210220E+10 | 0.456750E+10 | 0.358726E+10 | 12725085.96 | 0.357453E+10 | 0.00 | 0.00 |
May | 0.373183E+10 | 0.361869E+10 | 0.476976E+10 | 0.141703E+09 | 0.462806E+10 | 0.00 | 0.00 |
June | 0.424660E+10 | 0.269076E+10 | 0.485350E+10 | 0.320505E+09 | 0.453300E+10 | 0.00 | 0.00 |
July | 0.474105E+10 | 0.248291E+10 | 0.476675E+10 | 0.373736E+09 | 0.439302E+10 | 0.00 | 0.00 |
August | 0.388936E+10 | 0.243573E+10 | 0.385872E+10 | 0.104313E+09 | 0.375441E+10 | 0.00 | 0.00 |
September | 0.212481E+10 | 0.358816E+10 | 0.290063E+10 | 855351.23 | 0.289977E+10 | 0.00 | 0.00 |
October | 0.750728E+09 | 0.528749E+10 | 0.205366E+10 | 0.00 | 0.205366E+10 | 0.00 | 0.00 |
November | 91815112.76 | 0.676642E+10 | 0.125188E+10 | 0.00 | 0.125188E+10 | 0.00 | 0.00 |
December | 2185292.91 | 0.865933E+10 | 0.970916E+09 | 0.00 | 0.970916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.227471E+11 | 0.612265E+11 | 0.343810E+11 | 0.953837E+09 | 0.334272E+11 | 0.00 | 0.00 |
Minimum of Months | 2185292.91 | 0.243573E+10 | 0.970916E+09 | 0.00 | 0.970916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474105E+10 | 0.865933E+10 | 0.485350E+10 | 0.373736E+09 | 0.462806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.364282E+09 | 0.525277E+10 | 0.122400E+10 | 0.310324E+09 | 0.913673E+09 | 0.00 | 0.00 |
February | 0.117647E+10 | 0.410960E+10 | 0.202857E+10 | 0.719982E+09 | 0.130859E+10 | 0.00 | 0.00 |
March | 0.263506E+10 | 0.373398E+10 | 0.335331E+10 | 0.121393E+10 | 0.213938E+10 | 0.00 | 0.00 |
April | 0.496885E+10 | 0.282925E+10 | 0.503052E+10 | 0.209025E+10 | 0.294027E+10 | 0.00 | 0.00 |
May | 0.579820E+10 | 0.240870E+10 | 0.553135E+10 | 0.192312E+10 | 0.360823E+10 | 0.00 | 0.00 |
June | 0.728240E+10 | 0.180754E+10 | 0.641073E+10 | 0.278935E+10 | 0.362137E+10 | 0.00 | 0.00 |
July | 0.733046E+10 | 0.161946E+10 | 0.616887E+10 | 0.276895E+10 | 0.339993E+10 | 0.00 | 0.00 |
August | 0.746351E+10 | 0.156696E+10 | 0.606314E+10 | 0.303313E+10 | 0.303001E+10 | 0.00 | 0.00 |
September | 0.470305E+10 | 0.228081E+10 | 0.433820E+10 | 0.200081E+10 | 0.233738E+10 | 0.00 | 0.00 |
October | 0.253684E+10 | 0.331222E+10 | 0.292188E+10 | 0.124153E+10 | 0.168036E+10 | 0.00 | 0.00 |
November | 0.637282E+09 | 0.419690E+10 | 0.138595E+10 | 0.391267E+09 | 0.994681E+09 | 0.00 | 0.00 |
December | 0.474378E+09 | 0.532423E+10 | 0.117468E+10 | 0.378165E+09 | 0.796517E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.453708E+11 | 0.384424E+11 | 0.456312E+11 | 0.188608E+11 | 0.267704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.364282E+09 | 0.156696E+10 | 0.117468E+10 | 0.310324E+09 | 0.796517E+09 | 0.00 | 0.00 |
Maximum of Months | 0.746351E+10 | 0.532423E+10 | 0.641073E+10 | 0.303313E+10 | 0.362137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.429886E+10 | 0.714796E+10 | 0.504836E+10 | 0.299774E+10 | 0.205062E+10 | 0.00 | 0.00 |
February | 0.689551E+10 | 0.584623E+10 | 0.701229E+10 | 0.434070E+10 | 0.267159E+10 | 0.00 | 0.00 |
March | 0.868643E+10 | 0.569271E+10 | 0.835140E+10 | 0.445371E+10 | 0.389769E+10 | 0.00 | 0.00 |
April | 0.943536E+10 | 0.461433E+10 | 0.853306E+10 | 0.370501E+10 | 0.482805E+10 | 0.00 | 0.00 |
May | 0.906084E+10 | 0.385869E+10 | 0.806247E+10 | 0.240189E+10 | 0.566058E+10 | 0.00 | 0.00 |
June | 0.819978E+10 | 0.296163E+10 | 0.713842E+10 | 0.191658E+10 | 0.522185E+10 | 0.00 | 0.00 |
July | 0.102268E+11 | 0.275386E+10 | 0.804425E+10 | 0.294623E+10 | 0.509802E+10 | 0.00 | 0.00 |
August | 0.113681E+11 | 0.266381E+10 | 0.864254E+10 | 0.403016E+10 | 0.461238E+10 | 0.00 | 0.00 |
September | 0.114217E+11 | 0.360547E+10 | 0.926669E+10 | 0.511737E+10 | 0.414932E+10 | 0.00 | 0.00 |
October | 0.969738E+10 | 0.499529E+10 | 0.867385E+10 | 0.535546E+10 | 0.331839E+10 | 0.00 | 0.00 |
November | 0.454179E+10 | 0.595459E+10 | 0.496284E+10 | 0.284413E+10 | 0.211872E+10 | 0.00 | 0.00 |
December | 0.506755E+10 | 0.747891E+10 | 0.536564E+10 | 0.347232E+10 | 0.189332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.989002E+11 | 0.575735E+11 | 0.891018E+11 | 0.435813E+11 | 0.455205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429886E+10 | 0.266381E+10 | 0.496284E+10 | 0.191658E+10 | 0.189332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114217E+11 | 0.747891E+10 | 0.926669E+10 | 0.535546E+10 | 0.566058E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460281E+09 | 0.566996E+10 | 0.129102E+10 | 0.380698E+09 | 0.910321E+09 | 0.00 | 0.00 |
February | 0.128385E+10 | 0.462103E+10 | 0.209069E+10 | 0.785741E+09 | 0.130495E+10 | 0.00 | 0.00 |
March | 0.246680E+10 | 0.432435E+10 | 0.324348E+10 | 0.109476E+10 | 0.214872E+10 | 0.00 | 0.00 |
April | 0.452155E+10 | 0.343474E+10 | 0.477542E+10 | 0.182583E+10 | 0.294960E+10 | 0.00 | 0.00 |
May | 0.684859E+10 | 0.271449E+10 | 0.634969E+10 | 0.257953E+10 | 0.377015E+10 | 0.00 | 0.00 |
June | 0.649971E+10 | 0.213465E+10 | 0.590967E+10 | 0.229453E+10 | 0.361514E+10 | 0.00 | 0.00 |
July | 0.914426E+10 | 0.206576E+10 | 0.754395E+10 | 0.396548E+10 | 0.357846E+10 | 0.00 | 0.00 |
August | 0.763063E+10 | 0.206427E+10 | 0.624065E+10 | 0.318666E+10 | 0.305399E+10 | 0.00 | 0.00 |
September | 0.555254E+10 | 0.260192E+10 | 0.491812E+10 | 0.235982E+10 | 0.255830E+10 | 0.00 | 0.00 |
October | 0.247896E+10 | 0.379874E+10 | 0.289323E+10 | 0.117885E+10 | 0.171438E+10 | 0.00 | 0.00 |
November | 0.626558E+09 | 0.481190E+10 | 0.139433E+10 | 0.393260E+09 | 0.100107E+10 | 0.00 | 0.00 |
December | 0.550364E+09 | 0.622500E+10 | 0.121128E+10 | 0.415075E+09 | 0.796205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.480641E+11 | 0.444668E+11 | 0.478615E+11 | 0.204602E+11 | 0.274013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.460281E+09 | 0.206427E+10 | 0.121128E+10 | 0.380698E+09 | 0.796205E+09 | 0.00 | 0.00 |
Maximum of Months | 0.914426E+10 | 0.622500E+10 | 0.754395E+10 | 0.396548E+10 | 0.377015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32266911.94 | 0.721531E+10 | 0.114260E+10 | 0.00 | 0.114260E+10 | 0.00 | 0.00 |
February | 0.283952E+09 | 0.583114E+10 | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.00 | 0.00 |
March | 0.102551E+10 | 0.536242E+10 | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.00 | 0.00 |
April | 0.225595E+10 | 0.413295E+10 | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.00 | 0.00 |
May | 0.380524E+10 | 0.343632E+10 | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.00 | 0.00 |
June | 0.430663E+10 | 0.255290E+10 | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.00 | 0.00 |
July | 0.481586E+10 | 0.235967E+10 | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.00 | 0.00 |
August | 0.397032E+10 | 0.231064E+10 | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.00 | 0.00 |
September | 0.219222E+10 | 0.335799E+10 | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.00 | 0.00 |
October | 0.880319E+09 | 0.470775E+10 | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.00 | 0.00 |
November | 0.150046E+09 | 0.576275E+10 | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.00 | 0.00 |
December | 14081962.67 | 0.730067E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237324E+11 | 0.543305E+11 | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.00 | 0.00 |
Minimum of Months | 14081962.67 | 0.231064E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Maximum of Months | 0.481586E+10 | 0.730067E+10 | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412505E+09 | 0.458872E+10 | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.00 | 0.00 |
February | 0.125095E+10 | 0.372368E+10 | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.00 | 0.00 |
March | 0.266605E+10 | 0.347780E+10 | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.00 | 0.00 |
April | 0.495947E+10 | 0.269939E+10 | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.00 | 0.00 |
May | 0.576614E+10 | 0.233709E+10 | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.00 | 0.00 |
June | 0.722041E+10 | 0.177104E+10 | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.00 | 0.00 |
July | 0.727418E+10 | 0.160161E+10 | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.00 | 0.00 |
August | 0.740060E+10 | 0.156975E+10 | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.00 | 0.00 |
September | 0.468250E+10 | 0.219814E+10 | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.00 | 0.00 |
October | 0.256627E+10 | 0.307598E+10 | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.00 | 0.00 |
November | 0.683808E+09 | 0.374089E+10 | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.00 | 0.00 |
December | 0.520432E+09 | 0.469793E+10 | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.454033E+11 | 0.354820E+11 | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.00 | 0.00 |
Minimum of Months | 0.412505E+09 | 0.156975E+10 | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.740060E+10 | 0.469793E+10 | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434692E+10 | 0.668476E+10 | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.00 | 0.00 |
February | 0.691686E+10 | 0.558066E+10 | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.00 | 0.00 |
March | 0.866890E+10 | 0.544619E+10 | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.00 | 0.00 |
April | 0.940321E+10 | 0.443320E+10 | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.00 | 0.00 |
May | 0.899692E+10 | 0.378358E+10 | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.00 | 0.00 |
June | 0.815623E+10 | 0.287736E+10 | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.00 | 0.00 |
July | 0.101825E+11 | 0.268249E+10 | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.00 | 0.00 |
August | 0.113238E+11 | 0.260816E+10 | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.00 | 0.00 |
September | 0.113677E+11 | 0.354279E+10 | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.00 | 0.00 |
October | 0.965393E+10 | 0.481643E+10 | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.00 | 0.00 |
November | 0.458306E+10 | 0.558198E+10 | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.00 | 0.00 |
December | 0.512177E+10 | 0.693073E+10 | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.987218E+11 | 0.549683E+11 | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.00 | 0.00 |
Minimum of Months | 0.434692E+10 | 0.260816E+10 | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113677E+11 | 0.693073E+10 | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515883E+09 | 0.476422E+10 | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.00 | 0.00 |
February | 0.139016E+10 | 0.387541E+10 | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.00 | 0.00 |
March | 0.259564E+10 | 0.366271E+10 | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.00 | 0.00 |
April | 0.466743E+10 | 0.294791E+10 | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.00 | 0.00 |
May | 0.686935E+10 | 0.253935E+10 | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.00 | 0.00 |
June | 0.655379E+10 | 0.193546E+10 | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.00 | 0.00 |
July | 0.920705E+10 | 0.185637E+10 | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.00 | 0.00 |
August | 0.772883E+10 | 0.180785E+10 | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.00 | 0.00 |
September | 0.558438E+10 | 0.240800E+10 | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.00 | 0.00 |
October | 0.257632E+10 | 0.327480E+10 | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.00 | 0.00 |
November | 0.713175E+09 | 0.387472E+10 | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.00 | 0.00 |
December | 0.619316E+09 | 0.489607E+10 | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.490213E+11 | 0.378429E+11 | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.515883E+09 | 0.180785E+10 | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.00 | 0.00 |
Maximum of Months | 0.920705E+10 | 0.489607E+10 | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 55170184.89 | 0.664188E+10 | 0.114260E+10 | 0.00 | 0.114260E+10 | 0.00 | 0.00 |
February | 0.353837E+09 | 0.531606E+10 | 0.160585E+10 | 0.00 | 0.160585E+10 | 0.00 | 0.00 |
March | 0.115520E+10 | 0.488870E+10 | 0.261947E+10 | 0.00 | 0.261947E+10 | 0.00 | 0.00 |
April | 0.236437E+10 | 0.386017E+10 | 0.358724E+10 | 12725040.77 | 0.357452E+10 | 0.00 | 0.00 |
May | 0.387363E+10 | 0.327537E+10 | 0.476974E+10 | 0.141702E+09 | 0.462804E+10 | 0.00 | 0.00 |
June | 0.431581E+10 | 0.248343E+10 | 0.485348E+10 | 0.320504E+09 | 0.453298E+10 | 0.00 | 0.00 |
July | 0.480115E+10 | 0.231311E+10 | 0.476673E+10 | 0.373735E+09 | 0.439300E+10 | 0.00 | 0.00 |
August | 0.396824E+10 | 0.225334E+10 | 0.385871E+10 | 0.104312E+09 | 0.375439E+10 | 0.00 | 0.00 |
September | 0.225287E+10 | 0.316044E+10 | 0.290062E+10 | 855348.19 | 0.289976E+10 | 0.00 | 0.00 |
October | 0.100691E+10 | 0.424703E+10 | 0.205365E+10 | 0.00 | 0.205365E+10 | 0.00 | 0.00 |
November | 0.208048E+09 | 0.512910E+10 | 0.125187E+10 | 0.00 | 0.125187E+10 | 0.00 | 0.00 |
December | 34418847.21 | 0.661908E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243896E+11 | 0.501877E+11 | 0.343809E+11 | 0.953833E+09 | 0.334270E+11 | 0.00 | 0.00 |
Minimum of Months | 34418847.21 | 0.225334E+10 | 0.970912E+09 | 0.00 | 0.970912E+09 | 0.00 | 0.00 |
Maximum of Months | 0.480115E+10 | 0.664188E+10 | 0.485348E+10 | 0.373735E+09 | 0.462804E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.455295E+09 | 0.421766E+10 | 0.122399E+10 | 0.310323E+09 | 0.913670E+09 | 0.00 | 0.00 |
February | 0.134109E+10 | 0.338568E+10 | 0.202856E+10 | 0.719979E+09 | 0.130858E+10 | 0.00 | 0.00 |
March | 0.277286E+10 | 0.318136E+10 | 0.335330E+10 | 0.121392E+10 | 0.213937E+10 | 0.00 | 0.00 |
April | 0.503424E+10 | 0.254105E+10 | 0.503050E+10 | 0.209025E+10 | 0.294025E+10 | 0.00 | 0.00 |
May | 0.581084E+10 | 0.223845E+10 | 0.553133E+10 | 0.192312E+10 | 0.360821E+10 | 0.00 | 0.00 |
June | 0.722519E+10 | 0.172897E+10 | 0.641070E+10 | 0.278934E+10 | 0.362136E+10 | 0.00 | 0.00 |
July | 0.727287E+10 | 0.157572E+10 | 0.616885E+10 | 0.276893E+10 | 0.339991E+10 | 0.00 | 0.00 |
August | 0.740398E+10 | 0.153684E+10 | 0.606311E+10 | 0.303312E+10 | 0.303000E+10 | 0.00 | 0.00 |
September | 0.472874E+10 | 0.208171E+10 | 0.433818E+10 | 0.200081E+10 | 0.233737E+10 | 0.00 | 0.00 |
October | 0.266534E+10 | 0.279317E+10 | 0.292187E+10 | 0.124152E+10 | 0.168035E+10 | 0.00 | 0.00 |
November | 0.756558E+09 | 0.332353E+10 | 0.138594E+10 | 0.391265E+09 | 0.994677E+09 | 0.00 | 0.00 |
December | 0.572161E+09 | 0.425200E+10 | 0.117468E+10 | 0.378163E+09 | 0.796514E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.460392E+11 | 0.328561E+11 | 0.456310E+11 | 0.188607E+11 | 0.267703E+11 | 0.00 | 0.00 |
Minimum of Months | 0.455295E+09 | 0.153684E+10 | 0.117468E+10 | 0.310323E+09 | 0.796514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.740398E+10 | 0.425200E+10 | 0.641070E+10 | 0.303312E+10 | 0.362136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.446599E+10 | 0.613188E+10 | 0.504835E+10 | 0.299773E+10 | 0.205062E+10 | 0.00 | 0.00 |
February | 0.706477E+10 | 0.510742E+10 | 0.701227E+10 | 0.434069E+10 | 0.267158E+10 | 0.00 | 0.00 |
March | 0.877433E+10 | 0.501689E+10 | 0.835137E+10 | 0.445369E+10 | 0.389768E+10 | 0.00 | 0.00 |
April | 0.947051E+10 | 0.418556E+10 | 0.853303E+10 | 0.370499E+10 | 0.482803E+10 | 0.00 | 0.00 |
May | 0.902662E+10 | 0.362010E+10 | 0.806244E+10 | 0.240188E+10 | 0.566056E+10 | 0.00 | 0.00 |
June | 0.814202E+10 | 0.280089E+10 | 0.713840E+10 | 0.191657E+10 | 0.522183E+10 | 0.00 | 0.00 |
July | 0.101504E+11 | 0.263486E+10 | 0.804422E+10 | 0.294622E+10 | 0.509800E+10 | 0.00 | 0.00 |
August | 0.112982E+11 | 0.255151E+10 | 0.864250E+10 | 0.403014E+10 | 0.461236E+10 | 0.00 | 0.00 |
September | 0.113996E+11 | 0.337413E+10 | 0.926665E+10 | 0.511735E+10 | 0.414930E+10 | 0.00 | 0.00 |
October | 0.975683E+10 | 0.442565E+10 | 0.867382E+10 | 0.535544E+10 | 0.331838E+10 | 0.00 | 0.00 |
November | 0.471520E+10 | 0.501646E+10 | 0.496282E+10 | 0.284412E+10 | 0.211871E+10 | 0.00 | 0.00 |
December | 0.523903E+10 | 0.630014E+10 | 0.536562E+10 | 0.347230E+10 | 0.189331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.995035E+11 | 0.511655E+11 | 0.891015E+11 | 0.435811E+11 | 0.455203E+11 | 0.00 | 0.00 |
Minimum of Months | 0.446599E+10 | 0.255151E+10 | 0.496282E+10 | 0.191657E+10 | 0.189331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113996E+11 | 0.630014E+10 | 0.926665E+10 | 0.535544E+10 | 0.566056E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.546738E+09 | 0.439998E+10 | 0.129101E+10 | 0.380696E+09 | 0.910317E+09 | 0.00 | 0.00 |
February | 0.144474E+10 | 0.358120E+10 | 0.209068E+10 | 0.785738E+09 | 0.130495E+10 | 0.00 | 0.00 |
March | 0.266166E+10 | 0.339607E+10 | 0.324347E+10 | 0.109476E+10 | 0.214871E+10 | 0.00 | 0.00 |
April | 0.471208E+10 | 0.279419E+10 | 0.477540E+10 | 0.182582E+10 | 0.294958E+10 | 0.00 | 0.00 |
May | 0.687918E+10 | 0.244203E+10 | 0.634966E+10 | 0.257952E+10 | 0.377014E+10 | 0.00 | 0.00 |
June | 0.653596E+10 | 0.188766E+10 | 0.590965E+10 | 0.229452E+10 | 0.361513E+10 | 0.00 | 0.00 |
July | 0.917493E+10 | 0.182393E+10 | 0.754391E+10 | 0.396547E+10 | 0.357845E+10 | 0.00 | 0.00 |
August | 0.770618E+10 | 0.177172E+10 | 0.624062E+10 | 0.318664E+10 | 0.305398E+10 | 0.00 | 0.00 |
September | 0.559913E+10 | 0.230274E+10 | 0.491810E+10 | 0.235981E+10 | 0.255829E+10 | 0.00 | 0.00 |
October | 0.263914E+10 | 0.302046E+10 | 0.289322E+10 | 0.117885E+10 | 0.171437E+10 | 0.00 | 0.00 |
November | 0.760892E+09 | 0.352200E+10 | 0.139433E+10 | 0.393258E+09 | 0.100107E+10 | 0.00 | 0.00 |
December | 0.648963E+09 | 0.450714E+10 | 0.121128E+10 | 0.415073E+09 | 0.796202E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.493096E+11 | 0.354491E+11 | 0.478613E+11 | 0.204602E+11 | 0.274012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.546738E+09 | 0.177172E+10 | 0.121128E+10 | 0.380696E+09 | 0.796202E+09 | 0.00 | 0.00 |
Maximum of Months | 0.917493E+10 | 0.450714E+10 | 0.754391E+10 | 0.396547E+10 | 0.377014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390572E+11 | -0.386122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444988680.5 | 60.05 | 0.00 | 0.00 |
February | 0.357278E+11 | -0.353262E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401598665.0 | 60.05 | 0.00 | 0.00 |
March | 0.415409E+11 | -0.410963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444580974.8 | 60.05 | 0.00 | 0.00 |
April | 0.366859E+11 | -0.362576E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428329567.5 | 60.05 | 0.00 | 0.00 |
May | 0.377491E+11 | -0.373060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443097607.1 | 60.05 | 0.00 | 0.00 |
June | 0.360474E+11 | -0.356186E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428741640.9 | 60.05 | 0.00 | 0.00 |
July | 0.333860E+11 | -0.329455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440537883.2 | 60.05 | 0.00 | 0.00 |
August | 0.362146E+11 | -0.357723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442296893.5 | 60.05 | 0.00 | 0.00 |
September | 0.333052E+11 | -0.328780E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427243879.2 | 60.05 | 0.00 | 0.00 |
October | 0.354159E+11 | -0.349745E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441336177.6 | 60.05 | 0.00 | 0.00 |
November | 0.360882E+11 | -0.356606E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427648144.9 | 60.05 | 0.00 | 0.00 |
December | 0.372213E+11 | -0.367784E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442829617.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.438439E+12 | -0.433226E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.521323E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.333052E+11 | -0.410963E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -444988680.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.415409E+11 | -0.328780E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -401598665.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:39 | 2756.62 | 32.57 | 224.33 | 219.67 | 2173.73 | 33.68 | 226.67 | 187.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4688.14 | 33.54 | 245.83 | 244.00 | 2034.17 | 29.26 | 224.33 | 218.83 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7763.86 | 33.51 | 209.67 | 313.00 | 1660.48 | 22.71 | 204.00 | 267.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:00 | 2218.16 | 20.35 | 170.67 | 345.33 | 1212.63 | 21.77 | 250.00 | 308.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2038.95 | 20.20 | 160.83 | 386.00 | 1100.56 | 21.58 | 278.17 | 344.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:00 | 1789.61 | 19.74 | 112.33 | 396.33 | 1017.01 | 21.15 | 265.83 | 346.17 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1590.99 | 18.58 | 117.17 | 395.50 | 923.34 | 19.97 | 191.67 | 340.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1879.74 | 19.63 | 117.00 | 374.50 | 1111.35 | 21.04 | 209.17 | 328.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3010.85 | 22.37 | 143.67 | 320.17 | 1461.86 | 22.54 | 226.00 | 288.17 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7206.81 | 34.96 | 224.33 | 285.00 | 1937.98 | 23.90 | 187.17 | 256.17 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-08:09 | 3072.27 | 32.12 | 226.83 | 225.17 | 2440.53 | 33.30 | 230.50 | 193.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3700.35 | 35.79 | 149.50 | 207.33 | 3110.51 | 37.05 | 149.67 | 167.00 |
Annual Sum or Average | 3714.00 | 0.51 | 3130.76 | 25.12 | 2102.17 | 3712.00 | 1512.29 | 24.35 | 2643.17 | 3246.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1590.99 | 18.58 | 112.33 | 207.33 | 923.34 | 19.97 | 149.67 | 167.00 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7763.86 | 35.79 | 245.83 | 396.33 | 3110.51 | 37.05 | 278.17 | 346.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:50 | 933.44 | 21.20 | 70.33 | 200.50 | 572.67 | 22.53 | 94.00 | 132.00 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:30 | 1524.18 | 23.19 | 98.50 | 228.67 | 793.55 | 23.33 | 136.00 | 181.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2743.39 | 25.62 | 117.17 | 304.17 | 1198.53 | 24.50 | 158.50 | 255.83 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:19 | 2863.42 | 24.33 | 148.33 | 347.83 | 1592.66 | 24.70 | 229.17 | 308.50 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2943.71 | 23.64 | 160.67 | 391.50 | 1283.58 | 23.41 | 248.00 | 351.83 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3095.30 | 23.54 | 107.33 | 404.17 | 1694.29 | 23.99 | 208.33 | 359.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2908.98 | 23.76 | 170.33 | 410.83 | 1315.22 | 23.34 | 221.17 | 373.33 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3385.51 | 24.42 | 127.50 | 379.50 | 1472.71 | 23.72 | 177.50 | 340.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2778.60 | 24.19 | 99.33 | 323.83 | 1541.04 | 24.53 | 163.67 | 286.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2516.40 | 25.23 | 108.83 | 272.00 | 1100.58 | 24.04 | 139.33 | 227.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1158.69 | 22.44 | 87.83 | 208.33 | 601.01 | 22.59 | 93.33 | 146.83 |
December | 160.33 | 0.52 | 0.48 | 01-DEC-09:39 | 1093.97 | 23.41 | 64.83 | 185.83 | 586.52 | 23.34 | 71.50 | 107.67 |
Annual Sum or Average | 3714.00 | 0.51 | 2510.69 | 23.80 | 1361.00 | 3657.17 | 1228.01 | 23.71 | 1940.50 | 3070.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 933.44 | 21.20 | 64.83 | 185.83 | 572.67 | 22.53 | 71.50 | 107.67 | |
Maximum of Months | 471.00 | 0.52 | 0.48 | 3385.51 | 25.62 | 170.33 | 410.83 | 1694.29 | 24.70 | 248.00 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 02-JAN-10:50 | 506.54 | 16.03 | 0.00 | 179.67 | 275.32 | 17.36 | 0.00 | 53.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 644.35 | 17.21 | 0.00 | 215.50 | 363.52 | 18.62 | 1.50 | 131.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:09 | 870.97 | 18.63 | 0.00 | 298.67 | 514.77 | 20.08 | 68.17 | 217.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 1020.91 | 19.31 | 0.50 | 349.00 | 590.14 | 20.65 | 162.00 | 302.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1253.28 | 21.40 | 93.50 | 399.67 | 717.49 | 22.13 | 273.67 | 365.33 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1332.20 | 22.47 | 125.83 | 413.83 | 756.05 | 22.46 | 261.67 | 380.50 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1124.24 | 21.62 | 126.83 | 423.50 | 645.66 | 21.55 | 230.67 | 378.00 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 976.04 | 19.35 | 15.33 | 388.83 | 608.15 | 20.70 | 131.33 | 345.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 948.85 | 19.41 | 0.00 | 314.17 | 574.27 | 20.84 | 101.33 | 256.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 707.02 | 17.69 | 0.00 | 260.67 | 426.98 | 19.21 | 13.17 | 170.67 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-09:00 | 545.83 | 16.34 | 0.00 | 193.17 | 296.72 | 17.63 | 0.17 | 69.17 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:00 | 475.05 | 16.03 | 0.00 | 155.33 | 276.36 | 17.62 | 0.00 | 40.83 |
Annual Sum or Average | 3714.00 | 0.51 | 937.39 | 19.33 | 362.00 | 3592.00 | 544.60 | 20.32 | 1243.67 | 2711.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 475.05 | 16.03 | 0.00 | 155.33 | 275.32 | 17.36 | 0.00 | 40.83 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 1332.20 | 22.47 | 126.83 | 423.50 | 756.05 | 22.46 | 273.67 | 380.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:30 | 1062.71 | 22.55 | 87.33 | 201.83 | 564.79 | 22.66 | 94.67 | 138.50 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1509.03 | 23.16 | 95.00 | 232.17 | 773.63 | 23.23 | 126.17 | 184.33 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2398.88 | 24.40 | 112.33 | 306.67 | 1279.64 | 24.59 | 152.17 | 253.50 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:30 | 2867.28 | 23.20 | 133.67 | 345.83 | 1250.08 | 22.64 | 208.17 | 308.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 2973.53 | 20.76 | 88.17 | 392.67 | 1589.77 | 20.96 | 222.83 | 357.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 3033.87 | 20.34 | 51.83 | 403.50 | 1367.81 | 20.72 | 188.83 | 363.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:00 | 3326.90 | 19.59 | 75.50 | 405.00 | 1457.75 | 19.65 | 156.50 | 363.83 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-06:19 | 3174.65 | 22.00 | 92.83 | 383.83 | 1823.04 | 22.69 | 160.50 | 345.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3510.48 | 25.44 | 124.67 | 316.50 | 1949.38 | 25.50 | 180.33 | 273.83 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2420.89 | 25.91 | 116.33 | 274.50 | 1075.29 | 24.69 | 153.17 | 228.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:39 | 1128.96 | 22.03 | 79.17 | 210.17 | 588.37 | 22.11 | 91.33 | 142.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:00 | 1115.30 | 22.55 | 55.67 | 185.83 | 590.02 | 22.54 | 66.00 | 103.50 |
Annual Sum or Average | 3714.00 | 0.51 | 2576.83 | 22.35 | 1112.50 | 3658.50 | 1282.23 | 22.38 | 1800.67 | 3063.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1062.71 | 19.59 | 51.83 | 185.83 | 564.79 | 19.65 | 66.00 | 103.50 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3510.48 | 25.91 | 133.67 | 405.00 | 1949.38 | 25.50 | 222.83 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:39 | 2760.85 | 31.99 | 220.33 | 219.67 | 2235.21 | 33.12 | 221.33 | 190.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4711.16 | 32.96 | 238.83 | 244.50 | 2126.80 | 27.47 | 156.50 | 223.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7803.57 | 32.30 | 208.50 | 313.00 | 1771.56 | 17.99 | 8.50 | 272.00 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:00 | 2248.24 | 13.83 | 0.00 | 345.67 | 1295.51 | 17.29 | 0.67 | 312.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2063.76 | 13.83 | 0.00 | 386.33 | 1173.44 | 17.24 | 0.00 | 349.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:49 | 1820.97 | 13.70 | 0.00 | 396.50 | 1086.63 | 17.11 | 0.00 | 351.50 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:19 | 1623.42 | 12.32 | 0.00 | 396.33 | 988.91 | 15.77 | 0.00 | 348.00 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1922.77 | 13.42 | 0.00 | 374.67 | 1193.48 | 16.94 | 1.33 | 333.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3057.54 | 16.44 | 27.00 | 320.33 | 1567.48 | 18.15 | 11.17 | 291.83 |
October | 245.33 | 0.50 | 0.48 | 01-OCT-07:49 | 7248.74 | 34.05 | 220.33 | 285.00 | 2048.55 | 19.37 | 26.17 | 258.67 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-07:00 | 3084.69 | 31.49 | 221.67 | 225.50 | 2503.98 | 32.76 | 226.17 | 197.00 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3717.24 | 34.96 | 149.17 | 207.67 | 3198.07 | 36.43 | 149.67 | 171.00 |
Annual Sum or Average | 3714.00 | 0.51 | 3160.84 | 20.93 | 1285.83 | 3715.17 | 1594.20 | 20.86 | 801.50 | 3298.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1623.42 | 12.32 | 0.00 | 207.67 | 988.91 | 15.77 | 0.00 | 171.00 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7803.57 | 34.96 | 238.83 | 396.50 | 3198.07 | 36.43 | 226.17 | 351.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:50 | 949.57 | 18.35 | 61.33 | 202.17 | 596.49 | 20.65 | 71.33 | 137.83 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:30 | 1550.38 | 20.50 | 81.17 | 230.17 | 829.80 | 21.28 | 61.67 | 188.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 2791.73 | 23.13 | 91.50 | 304.67 | 1257.06 | 22.33 | 51.50 | 260.50 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:19 | 2913.28 | 21.51 | 118.33 | 348.83 | 1657.09 | 22.52 | 91.67 | 313.50 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2986.18 | 20.40 | 132.67 | 392.83 | 1348.11 | 20.93 | 79.50 | 356.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-04:00 | 3145.62 | 20.40 | 98.83 | 405.33 | 1772.28 | 21.56 | 73.67 | 364.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2950.12 | 20.05 | 148.50 | 411.00 | 1380.03 | 20.90 | 99.33 | 379.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3440.35 | 21.54 | 116.33 | 380.50 | 1545.34 | 21.19 | 66.50 | 345.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2832.24 | 21.34 | 84.33 | 324.17 | 1604.96 | 22.31 | 61.50 | 290.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2556.25 | 22.88 | 93.33 | 273.17 | 1152.05 | 22.00 | 58.00 | 232.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1177.86 | 19.78 | 78.83 | 210.17 | 627.75 | 20.54 | 62.83 | 154.33 |
December | 160.33 | 0.52 | 0.48 | 01-DEC-09:39 | 1112.43 | 21.01 | 56.33 | 186.67 | 613.49 | 21.60 | 52.67 | 114.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2551.51 | 20.86 | 1161.50 | 3669.67 | 1284.74 | 21.46 | 830.17 | 3135.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 949.57 | 18.35 | 56.33 | 186.67 | 596.49 | 20.54 | 51.50 | 114.17 | |
Maximum of Months | 471.00 | 0.52 | 0.48 | 3440.35 | 23.13 | 148.50 | 411.00 | 1772.28 | 22.52 | 99.33 | 379.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 02-JAN-10:39 | 511.49 | 9.50 | 0.00 | 180.00 | 292.01 | 12.98 | 0.00 | 67.50 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:09 | 652.10 | 11.06 | 0.00 | 216.33 | 386.04 | 14.56 | 0.00 | 142.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:09 | 884.58 | 12.96 | 0.00 | 298.83 | 547.55 | 16.43 | 0.00 | 228.83 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 1037.32 | 13.66 | 0.00 | 349.00 | 628.06 | 17.06 | 0.00 | 309.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1289.72 | 16.17 | 39.00 | 399.67 | 767.94 | 19.32 | 44.67 | 371.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1357.26 | 17.80 | 60.17 | 414.17 | 830.52 | 20.87 | 62.00 | 388.33 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1151.12 | 16.75 | 78.00 | 424.00 | 717.63 | 19.88 | 80.00 | 389.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 1017.74 | 13.88 | 0.00 | 391.83 | 648.60 | 17.44 | 0.50 | 354.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 964.69 | 14.15 | 0.00 | 314.83 | 611.52 | 17.60 | 0.00 | 264.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 717.51 | 12.07 | 0.00 | 261.67 | 454.17 | 15.60 | 0.00 | 186.50 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:30 | 551.46 | 9.86 | 0.00 | 193.33 | 314.81 | 13.29 | 0.00 | 83.00 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:00 | 479.56 | 9.78 | 0.00 | 156.00 | 293.19 | 13.49 | 0.00 | 51.00 |
Annual Sum or Average | 3714.00 | 0.51 | 957.63 | 13.81 | 177.17 | 3599.67 | 586.48 | 17.17 | 187.17 | 2836.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 479.56 | 9.50 | 0.00 | 156.00 | 292.01 | 12.98 | 0.00 | 51.00 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 1357.26 | 17.80 | 78.00 | 424.00 | 830.52 | 20.87 | 80.00 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:20 | 1080.07 | 19.99 | 79.17 | 203.67 | 589.73 | 20.70 | 64.17 | 145.17 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1524.12 | 19.33 | 66.50 | 232.17 | 810.96 | 21.15 | 59.67 | 190.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2436.52 | 21.61 | 78.17 | 307.50 | 1335.36 | 22.54 | 59.83 | 258.00 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:19 | 2915.14 | 20.19 | 105.33 | 346.50 | 1311.99 | 20.01 | 51.00 | 313.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 3009.64 | 16.83 | 52.17 | 392.83 | 1660.94 | 17.67 | 0.00 | 360.83 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:00 | 3080.87 | 16.45 | 42.83 | 404.00 | 1439.81 | 17.45 | 0.00 | 367.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:49 | 3375.83 | 15.57 | 58.83 | 406.33 | 1533.28 | 16.25 | 3.67 | 367.50 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-06:10 | 3208.24 | 18.52 | 75.83 | 384.00 | 1900.01 | 19.93 | 50.17 | 350.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3546.00 | 22.41 | 100.50 | 316.67 | 2024.72 | 23.30 | 76.83 | 279.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2431.61 | 22.21 | 89.83 | 275.00 | 1127.09 | 22.70 | 64.50 | 232.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1148.08 | 19.30 | 70.50 | 211.50 | 615.39 | 20.00 | 52.17 | 149.50 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:50 | 1133.58 | 19.89 | 48.67 | 186.50 | 616.83 | 20.65 | 45.33 | 110.83 |
Annual Sum or Average | 3714.00 | 0.51 | 2610.44 | 18.94 | 868.33 | 3666.67 | 1341.57 | 19.76 | 527.33 | 3124.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1080.07 | 15.57 | 42.83 | 186.50 | 589.73 | 16.25 | 0.00 | 110.83 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3546.00 | 22.41 | 105.33 | 406.33 | 2024.72 | 23.30 | 76.83 | 367.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:39 | 2762.01 | 31.99 | 220.33 | 219.67 | 2236.67 | 33.12 | 221.33 | 190.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4712.94 | 32.95 | 238.83 | 244.50 | 2128.86 | 27.46 | 156.50 | 223.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7806.60 | 32.29 | 208.50 | 313.33 | 1774.13 | 17.97 | 8.50 | 272.17 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:00 | 2251.62 | 13.80 | 0.00 | 345.67 | 1297.60 | 17.28 | 0.67 | 312.50 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2067.02 | 13.80 | 0.00 | 386.83 | 1175.35 | 17.23 | 0.00 | 349.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:49 | 1823.49 | 13.67 | 0.00 | 396.67 | 1088.20 | 17.10 | 0.00 | 351.83 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:19 | 1625.64 | 12.29 | 0.00 | 396.33 | 990.27 | 15.75 | 0.00 | 348.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1925.22 | 13.39 | 0.00 | 374.83 | 1195.06 | 16.93 | 1.33 | 333.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3060.64 | 16.42 | 27.00 | 320.33 | 1569.76 | 18.13 | 11.00 | 291.83 |
October | 245.33 | 0.50 | 0.48 | 01-OCT-07:49 | 7250.69 | 34.04 | 220.33 | 285.00 | 2050.89 | 19.36 | 26.17 | 258.83 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-07:00 | 3085.97 | 31.49 | 221.50 | 225.50 | 2505.63 | 32.76 | 226.17 | 197.33 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3717.99 | 34.95 | 149.17 | 207.83 | 3199.53 | 36.42 | 149.67 | 171.17 |
Annual Sum or Average | 3714.00 | 0.51 | 3163.23 | 20.90 | 1285.67 | 3716.50 | 1596.04 | 20.84 | 801.33 | 3300.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1625.64 | 12.29 | 0.00 | 207.83 | 990.27 | 15.75 | 0.00 | 171.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7806.60 | 34.95 | 238.83 | 396.67 | 3199.53 | 36.42 | 226.17 | 351.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:50 | 950.55 | 18.33 | 61.33 | 202.33 | 597.30 | 20.64 | 71.33 | 138.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:30 | 1551.59 | 20.47 | 81.00 | 230.33 | 830.85 | 21.26 | 61.50 | 188.17 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 2793.39 | 23.10 | 91.50 | 304.67 | 1258.52 | 22.32 | 51.33 | 260.83 |
April | 379.50 | 0.50 | 0.48 | 01-APR-06:19 | 2890.27 | 20.41 | 105.17 | 348.50 | 1658.69 | 22.50 | 91.67 | 313.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2988.57 | 20.37 | 132.50 | 393.17 | 1349.81 | 20.92 | 79.50 | 356.83 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-04:00 | 3147.66 | 20.37 | 98.83 | 405.33 | 1773.97 | 21.55 | 73.67 | 364.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2951.80 | 20.03 | 148.50 | 411.00 | 1381.35 | 20.89 | 99.33 | 379.33 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3441.77 | 21.51 | 116.33 | 380.50 | 1546.74 | 21.17 | 66.50 | 345.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2829.19 | 21.11 | 82.67 | 324.00 | 1606.36 | 22.30 | 61.33 | 290.17 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2517.97 | 21.42 | 83.00 | 273.33 | 1153.20 | 21.99 | 57.67 | 232.17 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1178.93 | 19.76 | 78.83 | 210.17 | 628.62 | 20.53 | 62.67 | 154.83 |
December | 160.33 | 0.52 | 0.48 | 01-DEC-09:39 | 1113.15 | 20.99 | 56.33 | 186.67 | 614.26 | 21.59 | 52.50 | 114.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2547.57 | 20.62 | 1136.00 | 3670.00 | 1286.08 | 21.45 | 829.00 | 3138.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 950.55 | 18.33 | 56.33 | 186.67 | 597.30 | 20.53 | 51.33 | 114.17 | |
Maximum of Months | 471.00 | 0.52 | 0.48 | 3441.77 | 23.10 | 148.50 | 411.00 | 1773.97 | 22.50 | 99.33 | 379.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 02-JAN-10:39 | 512.19 | 9.47 | 0.00 | 180.33 | 292.50 | 12.97 | 0.00 | 68.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:09 | 652.89 | 11.03 | 0.00 | 216.33 | 386.64 | 14.54 | 0.00 | 142.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:09 | 885.47 | 12.92 | 0.00 | 298.83 | 548.30 | 16.42 | 0.00 | 229.17 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 1038.47 | 13.63 | 0.00 | 349.00 | 628.96 | 17.05 | 0.00 | 310.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1291.25 | 16.14 | 39.00 | 400.00 | 769.05 | 19.30 | 44.50 | 371.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1358.51 | 17.77 | 60.17 | 414.17 | 831.56 | 20.86 | 62.00 | 388.33 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1152.22 | 16.73 | 78.00 | 424.00 | 718.51 | 19.86 | 79.83 | 389.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 1018.58 | 13.85 | 0.00 | 391.83 | 649.37 | 17.42 | 0.50 | 354.00 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 965.55 | 14.12 | 0.00 | 314.83 | 612.31 | 17.59 | 0.00 | 265.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 718.14 | 12.04 | 0.00 | 262.00 | 454.76 | 15.59 | 0.00 | 186.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:30 | 552.22 | 9.84 | 0.00 | 193.33 | 315.34 | 13.28 | 0.00 | 83.33 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:00 | 480.01 | 9.75 | 0.00 | 156.17 | 293.61 | 13.47 | 0.00 | 51.33 |
Annual Sum or Average | 3714.00 | 0.51 | 958.61 | 13.78 | 177.17 | 3600.83 | 587.27 | 17.16 | 186.83 | 2839.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 480.01 | 9.47 | 0.00 | 156.17 | 292.50 | 12.97 | 0.00 | 51.33 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 1358.51 | 17.77 | 78.00 | 424.00 | 831.56 | 20.86 | 79.83 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:20 | 1081.04 | 19.97 | 79.17 | 203.83 | 590.53 | 20.69 | 63.83 | 145.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1525.32 | 19.31 | 66.50 | 232.33 | 812.01 | 21.14 | 59.33 | 190.33 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2438.13 | 21.58 | 78.17 | 307.67 | 1336.84 | 22.53 | 59.67 | 258.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:19 | 2917.08 | 20.16 | 105.33 | 346.50 | 1313.60 | 19.99 | 51.00 | 313.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 3012.06 | 16.80 | 52.17 | 392.83 | 1662.78 | 17.65 | 0.00 | 361.17 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:00 | 3082.91 | 16.42 | 42.83 | 404.00 | 1441.48 | 17.44 | 0.00 | 367.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:40 | 3377.59 | 15.54 | 58.83 | 406.33 | 1534.72 | 16.23 | 3.67 | 367.67 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-06:10 | 3209.68 | 18.49 | 75.83 | 384.00 | 1901.43 | 19.92 | 50.17 | 350.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3547.73 | 22.38 | 100.50 | 316.67 | 2026.45 | 23.29 | 76.83 | 280.00 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2432.72 | 22.19 | 89.83 | 275.00 | 1128.29 | 22.69 | 64.50 | 232.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1149.15 | 19.27 | 70.50 | 211.50 | 616.26 | 19.99 | 52.00 | 150.00 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:50 | 1134.27 | 19.87 | 48.67 | 186.67 | 617.59 | 20.63 | 45.17 | 111.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2612.06 | 18.91 | 868.33 | 3667.33 | 1342.97 | 19.75 | 526.17 | 3127.67 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1081.04 | 15.54 | 42.83 | 186.67 | 590.53 | 16.23 | 0.00 | 111.00 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3547.73 | 22.38 | 105.33 | 406.33 | 2026.45 | 23.29 | 76.83 | 367.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103357E+11 | 28225.93 | 06-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608426E+10 | 23820.76 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155890E+10 | 21092.70 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.433108E+09 | 14778.24 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205463E+09 | 8650.22 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2373.51 | 0.85 | 12-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1879.58 | 1.93 | 27-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1101.32 | 0.85 | 05-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16896838.74 | 3013.57 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236335E+09 | 6648.84 | 13-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259644E+10 | 18681.03 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.553117E+10 | 25120.54 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1101.32 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103357E+11 | 28225.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21094641.39 | 1808.89 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 443845.34 | 184.85 | 18-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21538486.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21094641.39 | 1808.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 32346246.55 | 4069.88 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5606500.52 | 1727.94 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113718.96 | 101.15 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38066466.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32346246.55 | 4069.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161586E+09 | 15934.19 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39190869.33 | 15953.62 | 21-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2753382.91 | 963.76 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26266208.69 | 15975.81 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161586E+09 | 15975.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152241E+12 | 292365.51 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.941387E+11 | 249384.61 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433724E+11 | 317081.41 | 29-MAR-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205646E+11 | 287089.62 | 18-APR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.538729E+10 | 251527.87 | 17-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.261183E+09 | 171157.19 | 13-JUN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69717979.03 | 109826.31 | 12-JUL-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 58466055.14 | 126548.93 | 03-AUG-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.894890E+09 | 208505.27 | 27-SEP-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902572E+10 | 179073.62 | 18-OCT-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659131E+11 | 203718.23 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122686E+12 | 266808.03 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 58466055.14 | 109826.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152241E+12 | 317081.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.370785E+10 | 431536.37 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54448169.06 | 127135.77 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370785E+10 | 431536.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240713E+11 | 112990.41 | 02-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105698E+11 | 112323.92 | 22-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221347E+10 | 121794.62 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.327613E+09 | 68958.17 | 19-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.514407E+09 | 111357.16 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569897E+10 | 112298.32 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167590E+11 | 112306.75 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240713E+11 | 121794.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137966E+11 | 153280.80 | 02-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540524E+10 | 153233.10 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997289E+09 | 152930.51 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150248E+09 | 41215.04 | 19-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315496E+09 | 52560.59 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335874E+10 | 153035.13 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.976595E+10 | 153185.15 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137966E+11 | 153280.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148832E+11 | 220886.59 | 02-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508085E+10 | 220037.56 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.882059E+09 | 220053.88 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177818E+09 | 37038.71 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183305E+09 | 33534.31 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326366E+10 | 220169.24 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108421E+11 | 220745.93 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148832E+11 | 220886.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.979694E+10 | 148138.47 | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342043E+10 | 147799.66 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.431136E+09 | 143489.95 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27220877.89 | 9426.34 | 19-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55308249.41 | 5536.59 | 31-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177211E+10 | 147779.12 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579761E+10 | 148115.70 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.979694E+10 | 148138.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171688E+11 | 33383.46 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114209E+11 | 29892.42 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.636860E+10 | 23917.52 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.290419E+10 | 19046.65 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.851915E+09 | 12060.82 | 18-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43596261.86 | 3967.26 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153767E+09 | 6917.69 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183487E+10 | 12401.30 | 16-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.861773E+10 | 24343.97 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148368E+11 | 30786.01 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171688E+11 | 33383.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542142E+10 | 72917.00 | 23-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228252E+10 | 72660.56 | 21-FEB-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391510E+09 | 73192.37 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162330E+09 | 54821.54 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147030E+10 | 73225.39 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348310E+10 | 73187.11 | 18-DEC-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542142E+10 | 73225.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579583E+10 | 12653.35 | 30-JAN-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354016E+10 | 12652.18 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145765E+10 | 12651.06 | 06-MAR-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458454E+09 | 12574.50 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47515445.96 | 12504.45 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 369926.18 | 222.78 | 14-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30410215.83 | 8253.78 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.713750E+09 | 12624.52 | 21-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262008E+10 | 12677.10 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497450E+10 | 12652.33 | 26-DEC-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579583E+10 | 12677.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357249E+10 | 17614.40 | 18-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195211E+10 | 17624.38 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.716516E+09 | 17621.23 | 06-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198248E+09 | 17574.65 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28131138.86 | 17572.23 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 956491.99 | 359.84 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15430586.96 | 6801.65 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.379136E+09 | 17590.67 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158157E+10 | 17617.70 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304069E+10 | 17629.63 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357249E+10 | 17629.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.408318E+10 | 26063.14 | 18-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208457E+10 | 26078.14 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.912085E+09 | 26073.53 | 06-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.335023E+09 | 26005.03 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48312532.17 | 26001.37 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 325501.08 | 174.60 | 14-JUN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23406920.06 | 5421.46 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.415426E+09 | 26003.92 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184709E+10 | 26068.77 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352175E+10 | 26085.93 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.408318E+10 | 26085.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261791E+10 | 17886.20 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129289E+10 | 17865.67 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471866E+09 | 17863.21 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127215E+09 | 14579.92 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12915375.67 | 13441.12 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3325737.32 | 382.00 | 28-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213010E+09 | 13820.81 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100742E+10 | 17885.28 | 24-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198995E+10 | 17868.97 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.773650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261791E+10 | 17886.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161601E+10 | 13342.93 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.572126E+09 | 11322.62 | 18-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10994398.98 | 7978.08 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 255.55 | 0.85 | 27-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 125523.05 | 416.99 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1292.43 | 0.86 | 07-JUN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1384.97 | 0.90 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 591.71 | 0.34 | 18-AUG-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 552.23 | 0.80 | 22-SEP-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 571.52 | 0.82 | 06-OCT-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17.83 | 0.21 | 08-NOV-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105634E+09 | 10655.14 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17.83 | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161601E+10 | 13342.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.662817E+09 | 0.662817E+09 | 18269.41 | 20-JAN-13:30 | 18269.41 | 0.02 |
February | 0.00 | 0.00 | 0.484643E+10 | 0.484643E+10 | 54544.12 | 27-FEB-15:00 | 54544.12 | 0.02 |
March | 0.00 | 0.00 | 0.555053E+10 | 0.555053E+10 | 50819.24 | 02-MAR-13:05 | 50819.24 | 0.03 |
April | 0.00 | 0.00 | 0.103958E+11 | 0.103958E+11 | 120823.86 | 27-APR-14:40 | 120823.86 | 0.05 |
May | 0.00 | 0.00 | 0.160577E+11 | 0.160521E+11 | 97110.43 | 04-MAY-15:00 | 97110.43 | 0.16 |
June | 0.00 | 0.00 | 0.314536E+11 | 0.314473E+11 | 108733.24 | 28-JUN-15:20 | 108733.24 | 0.34 |
July | 0.00 | 0.00 | 0.572943E+11 | 0.565424E+11 | 142506.68 | 31-JUL-15:40 | 124821.17 | 0.54 |
August | 0.00 | 0.00 | 0.778205E+11 | 0.756300E+11 | 147818.13 | 29-AUG-14:30 | 130154.39 | 0.66 |
September | 0.00 | 0.00 | 0.249290E+11 | 0.245608E+11 | 124308.12 | 11-SEP-15:25 | 124308.12 | 0.34 |
October | 0.00 | 0.00 | 0.465388E+10 | 0.465388E+10 | 75816.72 | 04-OCT-15:00 | 75816.72 | 0.06 |
November | 0.00 | 0.00 | 0.496308E+10 | 0.496308E+10 | 41919.84 | 15-NOV-14:00 | 41919.84 | 0.03 |
December | 0.00 | 0.00 | 0.583333E+10 | 0.583333E+10 | 46213.73 | 05-DEC-14:30 | 46213.73 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.244461E+12 | 0.241138E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.662817E+09 | 0.662817E+09 | 18269.41 | 18269.41 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.778205E+11 | 0.756300E+11 | 147818.13 | 130154.39 | 0.66 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 30746.79 | 30746.79 | 2.46 | 02-JAN-07:00 | 2.46 | 0.00 |
February | 0.00 | 0.00 | 0.142385E+11 | 0.142385E+11 | 537474.20 | 27-FEB-15:05 | 537474.20 | 0.02 |
March | 0.00 | 0.00 | 0.598878E+11 | 0.598878E+11 | 520792.56 | 14-MAR-15:40 | 520792.56 | 0.03 |
April | 0.00 | 0.00 | 0.966835E+11 | 0.966835E+11 | 1021709.20 | 27-APR-14:40 | 1021709.20 | 0.06 |
May | 0.00 | 0.00 | 0.146480E+12 | 0.146420E+12 | 915515.04 | 04-MAY-15:00 | 915515.04 | 0.17 |
June | 0.00 | 0.00 | 0.258587E+12 | 0.258563E+12 | 973877.44 | 28-JUN-15:20 | 973877.44 | 0.33 |
July | 0.00 | 0.00 | 0.453434E+12 | 0.449046E+12 | 1237752.84 | 31-JUL-16:00 | 1058815.49 | 0.48 |
August | 0.00 | 0.00 | 0.599350E+12 | 0.584434E+12 | 1305463.20 | 29-AUG-14:30 | 1141245.44 | 0.53 |
September | 0.00 | 0.00 | 0.235719E+12 | 0.231243E+12 | 1102687.18 | 11-SEP-15:25 | 1041412.31 | 0.36 |
October | 0.00 | 0.00 | 0.881890E+11 | 0.881890E+11 | 723952.10 | 04-OCT-13:20 | 723952.10 | 0.11 |
November | 0.00 | 0.00 | 0.103491E+11 | 0.103491E+11 | 392871.01 | 04-NOV-14:05 | 392871.01 | 0.02 |
December | 0.00 | 0.00 | 28104.41 | 28104.41 | 2.99 | 26-DEC-06:02 | 2.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196292E+13 | 0.193905E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 28104.41 | 28104.41 | 2.46 | 2.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.599350E+12 | 0.584434E+12 | 1305463.20 | 1141245.44 | 0.53 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.390035E+09 | 0.390035E+09 | 27486.27 | 27-FEB-15:00 | 27486.27 | 0.01 |
March | 0.00 | 0.00 | 0.101644E+10 | 0.101644E+10 | 33301.00 | 01-MAR-15:00 | 33301.00 | 0.01 |
April | 0.00 | 0.00 | 0.764622E+10 | 0.764622E+10 | 119309.40 | 27-APR-14:40 | 119309.40 | 0.05 |
May | 0.00 | 0.00 | 0.141105E+11 | 0.141086E+11 | 100532.12 | 04-MAY-15:00 | 100532.12 | 0.15 |
June | 0.00 | 0.00 | 0.268694E+11 | 0.268676E+11 | 116132.20 | 28-JUN-15:20 | 116132.20 | 0.32 |
July | 0.00 | 0.00 | 0.481077E+11 | 0.477006E+11 | 142173.58 | 31-JUL-16:00 | 123454.55 | 0.47 |
August | 0.00 | 0.00 | 0.632128E+11 | 0.618101E+11 | 146685.64 | 10-AUG-15:40 | 134604.51 | 0.52 |
September | 0.00 | 0.00 | 0.215210E+11 | 0.212331E+11 | 111213.88 | 11-SEP-15:25 | 111213.88 | 0.33 |
October | 0.00 | 0.00 | 0.309679E+10 | 0.309679E+10 | 66071.09 | 04-OCT-15:00 | 66071.09 | 0.04 |
November | 0.00 | 0.00 | 0.516383E+09 | 0.516383E+09 | 29528.85 | 04-NOV-14:10 | 29528.85 | 0.01 |
December | 0.00 | 0.00 | 26462.81 | 26462.81 | 441.05 | 26-DEC-05:01 | 441.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186487E+12 | 0.184386E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.632128E+11 | 0.618101E+11 | 146685.64 | 134604.51 | 0.52 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 44228642.85 | 44228642.85 | 7411.38 | 11-JAN-07:14 | 7411.38 | 0.00 |
February | 0.00 | 0.00 | 0.969962E+09 | 0.883147E+09 | 45234.39 | 24-FEB-07:12 | 30748.47 | 0.02 |
March | 0.00 | 0.00 | 0.674618E+09 | 0.668730E+09 | 34735.90 | 10-MAR-07:13 | 19119.57 | 0.01 |
April | 0.00 | 0.00 | 0.456647E+10 | 0.455548E+10 | 58214.48 | 27-APR-15:00 | 58214.48 | 0.04 |
May | 0.00 | 0.00 | 0.970129E+10 | 0.965838E+10 | 57941.51 | 15-MAY-16:00 | 57941.51 | 0.15 |
June | 0.00 | 0.00 | 0.206019E+11 | 0.200158E+11 | 60255.75 | 12-JUN-06:35 | 33779.70 | 0.29 |
July | 0.00 | 0.00 | 0.374619E+11 | 0.350854E+11 | 96175.88 | 31-JUL-10:10 | 70946.81 | 0.41 |
August | 0.00 | 0.00 | 0.481420E+11 | 0.456342E+11 | 79037.71 | 07-AUG-12:05 | 71764.62 | 0.47 |
September | 0.00 | 0.00 | 0.172572E+11 | 0.166330E+11 | 76932.25 | 11-SEP-15:25 | 74437.60 | 0.31 |
October | 0.00 | 0.00 | 0.288060E+10 | 0.282953E+10 | 41515.20 | 04-OCT-15:00 | 41515.20 | 0.04 |
November | 0.00 | 0.00 | 0.560913E+09 | 0.540625E+09 | 38483.62 | 04-NOV-06:14 | 24399.94 | 0.01 |
December | 0.00 | 0.00 | 9118321.70 | 7223948.90 | 22536.97 | 16-DEC-07:13 | 13587.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142870E+12 | 0.136556E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 9118321.70 | 7223948.90 | 7411.38 | 7411.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.481420E+11 | 0.456342E+11 | 96175.88 | 74437.60 | 0.47 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.451994E+10 | 0.451991E+10 | 3119.97 | 09-JAN-12:00 | 3119.97 | 0.00 |
February | 0.00 | 0.00 | 0.679760E+10 | 0.676016E+10 | 18252.01 | 27-FEB-15:00 | 18252.01 | 0.00 |
March | 0.00 | 0.00 | 0.118246E+11 | 0.114416E+11 | 126263.66 | 18-MAR-16:00 | 126263.66 | 0.00 |
April | 0.00 | 0.00 | 0.766841E+11 | 0.723599E+11 | 408346.75 | 27-APR-16:00 | 408346.75 | 0.00 |
May | 0.00 | 0.00 | 0.430446E+10 | 0.407864E+10 | 84113.33 | 05-MAY-16:00 | 72610.43 | 0.00 |
June | 0.00 | 0.00 | 0.331722E+11 | 0.316610E+11 | 214401.62 | 28-JUN-17:00 | 214401.62 | 0.00 |
July | 0.00 | 0.00 | 0.208486E+12 | 0.177262E+12 | 357081.26 | 27-JUL-16:00 | 289700.75 | 0.00 |
August | 0.00 | 0.00 | 0.534071E+12 | 0.426856E+12 | 473401.08 | 29-AUG-11:00 | 388848.37 | 0.00 |
September | 0.00 | 0.00 | 0.339362E+10 | 0.286077E+10 | 86201.97 | 22-SEP-16:00 | 73177.16 | 0.00 |
October | 0.00 | 0.00 | 0.380186E+10 | 0.372578E+10 | 71684.43 | 04-OCT-15:00 | 71684.43 | 0.00 |
November | 0.00 | 0.00 | 0.997547E+10 | 0.866579E+10 | 180788.58 | 04-NOV-14:10 | 135467.22 | 0.00 |
December | 0.00 | 0.00 | 0.130203E+11 | 0.121201E+11 | 6025.50 | 27-DEC-00:40 | 5490.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.910050E+12 | 0.762311E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.339362E+10 | 0.286077E+10 | 3119.97 | 3119.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.534071E+12 | 0.426856E+12 | 473401.08 | 408346.75 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.407884E+10 | 0.407851E+10 | 2127.82 | 08-JAN-16:15 | 2127.82 | 0.00 |
February | 0.00 | 0.00 | 0.879396E+10 | 0.878354E+10 | 4449.77 | 12-FEB-16:45 | 4449.77 | 0.00 |
March | 0.00 | 0.00 | 0.152870E+11 | 0.152789E+11 | 7574.12 | 31-MAR-24:00 | 7574.12 | 0.00 |
April | 0.00 | 0.00 | 0.199884E+11 | 0.199748E+11 | 8685.55 | 23-APR-18:03 | 8685.55 | 0.00 |
May | 0.00 | 0.00 | 0.561126E+10 | 0.557495E+10 | 4018.83 | 31-MAY-24:00 | 4010.92 | 0.00 |
June | 0.00 | 0.00 | 0.105490E+11 | 0.104970E+11 | 5888.96 | 30-JUN-24:00 | 5887.11 | 0.00 |
July | 0.00 | 0.00 | 0.162641E+11 | 0.161491E+11 | 7864.50 | 31-JUL-23:55 | 7834.92 | 0.00 |
August | 0.00 | 0.00 | 0.212835E+11 | 0.211227E+11 | 9269.74 | 06-AUG-18:41 | 9269.74 | 0.00 |
September | 0.00 | 0.00 | 0.559983E+10 | 0.550915E+10 | 3897.99 | 30-SEP-24:00 | 3896.94 | 0.00 |
October | 0.00 | 0.00 | 0.104255E+11 | 0.104028E+11 | 5616.72 | 31-OCT-24:00 | 5616.72 | 0.00 |
November | 0.00 | 0.00 | 0.147019E+11 | 0.146783E+11 | 6404.48 | 11-NOV-15:55 | 6404.48 | 0.00 |
December | 0.00 | 0.00 | 0.200314E+11 | 0.200290E+11 | 8191.42 | 10-DEC-15:35 | 8191.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152615E+12 | 0.152079E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.407884E+10 | 0.407851E+10 | 2127.82 | 2127.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212835E+11 | 0.211227E+11 | 9269.74 | 9269.74 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153967E+11 | 0.153967E+11 | 16735.79 | 05-JAN-16:20 | 16735.79 | 0.00 |
February | 0.00 | 0.00 | 0.671695E+11 | 0.670671E+11 | 40321.11 | 27-FEB-16:20 | 40122.04 | 0.00 |
March | 0.00 | 0.00 | 0.134099E+12 | 0.134018E+12 | 67946.72 | 31-MAR-23:50 | 67946.72 | 0.00 |
April | 0.00 | 0.00 | 0.183766E+12 | 0.183628E+12 | 82486.09 | 26-APR-18:00 | 82486.09 | 0.00 |
May | 0.00 | 0.00 | 0.484483E+11 | 0.480915E+11 | 37707.65 | 31-MAY-23:40 | 37589.47 | 0.00 |
June | 0.00 | 0.00 | 0.969641E+11 | 0.964471E+11 | 55462.70 | 30-JUN-24:00 | 55442.60 | 0.00 |
July | 0.00 | 0.00 | 0.152924E+12 | 0.151785E+12 | 75632.06 | 31-JUL-23:55 | 75342.90 | 0.00 |
August | 0.00 | 0.00 | 0.201476E+12 | 0.199879E+12 | 86997.16 | 06-AUG-18:35 | 86997.16 | 0.00 |
September | 0.00 | 0.00 | 0.487566E+11 | 0.478683E+11 | 35424.38 | 30-SEP-23:50 | 35408.62 | 0.00 |
October | 0.00 | 0.00 | 0.893620E+11 | 0.891362E+11 | 47940.88 | 31-OCT-24:00 | 47940.88 | 0.00 |
November | 0.00 | 0.00 | 0.123847E+12 | 0.123611E+12 | 58347.95 | 04-NOV-16:00 | 57152.12 | 0.00 |
December | 0.00 | 0.00 | 0.168736E+12 | 0.168711E+12 | 73202.89 | 05-DEC-15:50 | 73202.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133094E+13 | 0.132564E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.153967E+11 | 0.153967E+11 | 16735.79 | 16735.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201476E+12 | 0.199879E+12 | 86997.16 | 86997.16 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.483413E+09 | 0.483413E+09 | 1542.07 | 05-JAN-16:20 | 1542.07 | 0.00 |
February | 0.00 | 0.00 | 0.510112E+10 | 0.509103E+10 | 3992.71 | 27-FEB-16:30 | 3966.34 | 0.00 |
March | 0.00 | 0.00 | 0.121187E+11 | 0.121106E+11 | 6309.42 | 31-MAR-23:20 | 6309.42 | 0.00 |
April | 0.00 | 0.00 | 0.176315E+11 | 0.176177E+11 | 8322.28 | 26-APR-18:00 | 8322.28 | 0.00 |
May | 0.00 | 0.00 | 0.437263E+10 | 0.433714E+10 | 3696.53 | 31-MAY-23:20 | 3679.97 | 0.00 |
June | 0.00 | 0.00 | 0.949641E+10 | 0.944469E+10 | 5464.44 | 30-JUN-23:40 | 5460.94 | 0.00 |
July | 0.00 | 0.00 | 0.151845E+11 | 0.150704E+11 | 7536.45 | 31-JUL-23:55 | 7507.35 | 0.00 |
August | 0.00 | 0.00 | 0.200214E+11 | 0.198617E+11 | 8906.93 | 06-AUG-18:30 | 8906.93 | 0.00 |
September | 0.00 | 0.00 | 0.439253E+10 | 0.430478E+10 | 3149.17 | 30-SEP-23:20 | 3145.92 | 0.00 |
October | 0.00 | 0.00 | 0.777963E+10 | 0.775745E+10 | 4593.85 | 04-OCT-16:50 | 4593.85 | 0.00 |
November | 0.00 | 0.00 | 0.107139E+11 | 0.106906E+11 | 5749.04 | 04-NOV-16:00 | 5630.19 | 0.00 |
December | 0.00 | 0.00 | 0.149130E+11 | 0.149105E+11 | 7128.11 | 05-DEC-16:00 | 7128.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122209E+12 | 0.121680E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.483413E+09 | 0.483413E+09 | 1542.07 | 1542.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200214E+11 | 0.198617E+11 | 8906.93 | 8906.93 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 99624.66 | 1286711.37 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 60568.80 | 979699.44 | 15-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22119.62 | 926247.28 | 06-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9829.62 | 350590.30 | 03-APR-13:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2437.72 | 285163.83 | 17-MAY-13:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 117.49 | 192785.50 | 13-JUN-09:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.96 | 114609.62 | 12-JUL-09:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.40 | 133347.78 | 03-AUG-09:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 432.72 | 248533.80 | 27-SEP-09:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 5200.66 | 409461.33 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 38145.54 | 1030791.32 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 75265.56 | 1130970.57 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 26020.04 | ||||
Minimum of Months | 0.00 | 0.00 | 22.40 | 114609.62 | ||
Maximum of Months | 0.00 | 0.00 | 99624.66 | 1286711.37 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 429.34 | 21288.50 | 11-JAN-07:14 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 8883.72 | 640170.33 | 27-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 25595.48 | 572939.84 | 14-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 47378.14 | 1317024.53 | 27-APR-14:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 71774.02 | 1756309.84 | 04-MAY-14:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 133223.29 | 1713836.18 | 21-JUN-14:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 229669.18 | 1601653.38 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 302953.51 | 1669905.24 | 29-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 118206.11 | 1702435.79 | 11-SEP-15:25 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 37889.17 | 1081058.33 | 04-OCT-15:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6759.95 | 475047.10 | 04-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2724.33 | 62655.96 | 16-DEC-07:13 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 82788.64 | 0.00 | ||||
Minimum of Months | 429.34 | 21288.50 | 0.00 | 0.00 | ||
Maximum of Months | 302953.51 | 1756309.84 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 224.34 | 23145.10 | 11-JAN-07:12 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 8440.15 | 649662.78 | 27-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24977.50 | 571271.13 | 14-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46849.55 | 1314942.98 | 27-APR-14:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 71531.67 | 1853833.21 | 04-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 133170.27 | 1741435.94 | 20-JUN-13:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 229087.33 | 1990006.80 | 20-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 303122.91 | 1910278.93 | 09-AUG-10:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 120221.60 | 1953818.87 | 11-SEP-15:20 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 37370.15 | 1109391.77 | 04-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6283.87 | 480273.28 | 04-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2193.02 | 84602.60 | 16-DEC-07:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 82618.62 | 0.00 | ||||
Minimum of Months | 224.34 | 23145.10 | 0.00 | 0.00 | ||
Maximum of Months | 303122.91 | 1990006.80 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15825.42 | 32930.79 | 12-JAN-20:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49299.01 | 197913.38 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 84185.34 | 460338.37 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 171172.63 | 1396849.38 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53511.99 | 566858.58 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 121528.06 | 937169.74 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 313229.84 | 1404740.43 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 587074.39 | 1688014.39 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 59981.53 | 568776.16 | 22-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 56878.89 | 396727.08 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80398.43 | 579995.73 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102640.60 | 118351.00 | 05-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 142428.86 | 0.00 | ||||
Minimum of Months | 15825.42 | 32930.79 | 0.00 | 0.00 | ||
Maximum of Months | 587074.39 | 1688014.39 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14332.43 | 51088.77 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14518.51 | 51150.72 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15258.69 | 50975.57 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13905.14 | 49837.65 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13845.35 | 48284.37 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13658.88 | 46383.74 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12219.48 | 44763.74 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13273.49 | 44110.86 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12602.97 | 45073.86 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12975.99 | 46819.57 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13675.01 | 48660.72 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13648.71 | 50167.44 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 13654.68 | ||||
Minimum of Months | 0.00 | 0.00 | 12219.48 | 44110.86 | ||
Maximum of Months | 0.00 | 0.00 | 15258.69 | 51150.72 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19.57 | 13542.58 | 27-JAN-11:30 | 2388.66 | 114057.98 | 09-JAN-06:40 |
February | 7311.12 | 727988.72 | 27-FEB-15:10 | 3222.69 | 106975.32 | 14-FEB-14:10 |
March | 25692.02 | 654108.48 | 14-MAR-16:00 | 2875.54 | 115501.15 | 25-MAR-10:20 |
April | 55242.99 | 2012446.78 | 27-APR-13:20 | 1188.21 | 90281.21 | 24-APR-07:00 |
May | 82627.64 | 2082646.06 | 04-MAY-14:05 | 1159.86 | 87095.10 | 18-MAY-08:00 |
June | 158560.32 | 2031796.66 | 22-JUN-14:50 | 1218.22 | 71141.49 | 06-JUN-13:30 |
July | 290154.33 | 3036299.07 | 31-JUL-16:00 | 1365.26 | 61001.71 | 05-JUL-20:10 |
August | 416735.04 | 3408623.84 | 29-AUG-14:30 | 1648.51 | 54102.30 | 12-AUG-05:30 |
September | 142968.70 | 2509185.84 | 11-SEP-15:25 | 995.14 | 60229.61 | 19-SEP-19:20 |
October | 42030.93 | 1310132.64 | 04-OCT-13:20 | 660.71 | 76899.06 | 13-OCT-09:40 |
November | 5318.92 | 541067.29 | 04-NOV-14:10 | 3975.65 | 103289.52 | 16-NOV-08:50 |
December | 272.53 | 37356.96 | 06-DEC-15:10 | 5206.09 | 105900.39 | 21-DEC-15:10 |
Annual Sum or Average | 103153.24 | 2153.41 | ||||
Minimum of Months | 19.57 | 13542.58 | 660.71 | 54102.30 | ||
Maximum of Months | 416735.04 | 3408623.84 | 5206.09 | 115501.15 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.298771E+10 | 0.29 | 9209.68 | 02-JAN-06:03 | 1.12 |
February | 0.380679E+10 | 0.34 | 13304.14 | 27-FEB-15:00 | 1.41 |
March | 0.640259E+10 | 0.42 | 13014.32 | 14-MAR-14:50 | 1.39 |
April | 0.853373E+10 | 0.50 | 19200.93 | 27-APR-14:40 | 1.77 |
May | 0.773967E+10 | 0.46 | 16371.73 | 15-MAY-14:30 | 1.61 |
June | 0.959131E+10 | 0.54 | 19476.77 | 12-JUN-04:12 | 1.78 |
July | 0.117247E+11 | 0.61 | 19476.77 | 31-JUL-14:10 | 1.78 |
August | 0.135093E+11 | 0.69 | 19476.77 | 07-AUG-10:40 | 1.78 |
September | 0.787689E+10 | 0.46 | 19476.77 | 11-SEP-14:03 | 1.78 |
October | 0.634296E+10 | 0.40 | 15561.95 | 04-OCT-15:20 | 1.56 |
November | 0.464842E+10 | 0.35 | 10268.08 | 03-NOV-05:02 | 1.20 |
December | 0.441681E+10 | 0.34 | 10267.68 | 04-DEC-05:11 | 1.20 |
Annual Sum or Average | 0.875808E+11 | 0.45 | |||
Minimum of Months | 0.298771E+10 | 0.29 | 9209.68 | 1.12 | |
Maximum of Months | 0.135093E+11 | 0.69 | 19476.77 | 1.78 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212418E+11 | 0.28 | 54043.04 | 02-JAN-05:52 | 0.86 |
February | 0.229624E+11 | 0.29 | 69051.03 | 28-FEB-06:02 | 0.99 |
March | 0.342378E+11 | 0.33 | 80134.19 | 02-MAR-15:05 | 1.08 |
April | 0.431877E+11 | 0.36 | 146923.63 | 27-APR-14:40 | 1.57 |
May | 0.566557E+11 | 0.41 | 142674.15 | 15-MAY-14:05 | 1.55 |
June | 0.653667E+11 | 0.45 | 134351.74 | 28-JUN-14:05 | 1.48 |
July | 0.759957E+11 | 0.47 | 179437.52 | 20-JUL-12:20 | 1.78 |
August | 0.861516E+11 | 0.51 | 179437.52 | 09-AUG-10:00 | 1.78 |
September | 0.591615E+11 | 0.41 | 179437.52 | 11-SEP-14:03 | 1.78 |
October | 0.378919E+11 | 0.33 | 129617.48 | 04-OCT-15:40 | 1.46 |
November | 0.236868E+11 | 0.28 | 70727.21 | 10-NOV-06:03 | 1.01 |
December | 0.222098E+11 | 0.28 | 47744.22 | 07-DEC-06:02 | 0.80 |
Annual Sum or Average | 0.548749E+12 | 0.37 | |||
Minimum of Months | 0.212418E+11 | 0.28 | 47744.22 | 0.80 | |
Maximum of Months | 0.861516E+11 | 0.51 | 179437.52 | 1.78 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.260802E+10 | 0.34 | 4752.46 | 02-JAN-05:11 | 0.75 |
February | 0.227017E+10 | 0.32 | 4752.46 | 06-FEB-05:11 | 0.75 |
March | 0.269275E+10 | 0.31 | 5413.37 | 14-MAR-15:40 | 0.81 |
April | 0.347707E+10 | 0.32 | 15531.43 | 27-APR-14:40 | 1.51 |
May | 0.475903E+10 | 0.36 | 14992.15 | 15-MAY-14:50 | 1.49 |
June | 0.587594E+10 | 0.41 | 14788.38 | 28-JUN-15:20 | 1.47 |
July | 0.716347E+10 | 0.43 | 17905.11 | 31-JUL-14:30 | 1.65 |
August | 0.796032E+10 | 0.46 | 19339.35 | 10-AUG-14:40 | 1.73 |
September | 0.486559E+10 | 0.36 | 20115.14 | 11-SEP-14:07 | 1.78 |
October | 0.284448E+10 | 0.30 | 11054.53 | 04-OCT-15:30 | 1.23 |
November | 0.213329E+10 | 0.29 | 4752.46 | 13-NOV-05:01 | 0.75 |
December | 0.232991E+10 | 0.30 | 4752.46 | 01-DEC-06:02 | 0.75 |
Annual Sum or Average | 0.489800E+11 | 0.35 | |||
Minimum of Months | 0.213329E+10 | 0.29 | 4752.46 | 0.75 | |
Maximum of Months | 0.796032E+10 | 0.46 | 20115.14 | 1.78 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.421154E+10 | 0.39 | 11104.85 | 02-JAN-07:05 | 1.80 |
February | 0.643575E+10 | 0.53 | 11104.85 | 01-FEB-07:10 | 1.80 |
March | 0.114253E+11 | 0.75 | 11104.85 | 01-MAR-07:05 | 1.81 |
April | 0.131443E+11 | 0.84 | 11104.85 | 01-APR-06:05 | 1.81 |
May | 0.128127E+11 | 0.81 | 11104.85 | 01-MAY-06:10 | 1.79 |
June | 0.116715E+11 | 0.78 | 11104.85 | 01-JUN-06:05 | 1.80 |
July | 0.956931E+10 | 0.65 | 11104.85 | 01-JUL-06:10 | 1.79 |
August | 0.118823E+11 | 0.78 | 11104.85 | 01-AUG-06:10 | 1.79 |
September | 0.114890E+11 | 0.76 | 11104.85 | 01-SEP-06:10 | 1.79 |
October | 0.133507E+11 | 0.83 | 11104.85 | 02-OCT-06:05 | 1.80 |
November | 0.130382E+11 | 0.83 | 11104.85 | 01-NOV-06:10 | 1.80 |
December | 0.112970E+11 | 0.73 | 11104.85 | 01-DEC-07:05 | 1.81 |
Annual Sum or Average | 0.130328E+12 | 0.72 | |||
Minimum of Months | 0.421154E+10 | 0.39 | 11104.85 | 1.79 | |
Maximum of Months | 0.133507E+11 | 0.84 | 11104.85 | 1.81 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109549E+12 | 1.37 | 40901.08 | 01-JAN-00:05 | 1.37 |
February | 0.989479E+11 | 1.37 | 40901.08 | 01-FEB-00:20 | 1.37 |
March | 0.109549E+12 | 1.37 | 40901.08 | 01-MAR-00:10 | 1.37 |
April | 0.106016E+12 | 1.37 | 40901.08 | 01-APR-00:10 | 1.37 |
May | 0.109549E+12 | 1.37 | 40901.08 | 01-MAY-00:10 | 1.37 |
June | 0.106016E+12 | 1.36 | 40901.08 | 01-JUN-00:10 | 1.37 |
July | 0.109549E+12 | 1.36 | 40901.08 | 01-JUL-00:30 | 1.36 |
August | 0.109549E+12 | 1.36 | 40901.08 | 01-AUG-00:03 | 1.36 |
September | 0.106016E+12 | 1.36 | 40901.08 | 01-SEP-00:05 | 1.36 |
October | 0.109549E+12 | 1.37 | 40901.08 | 01-OCT-00:10 | 1.36 |
November | 0.106016E+12 | 1.37 | 40901.08 | 01-NOV-00:10 | 1.37 |
December | 0.109549E+12 | 1.37 | 40901.08 | 01-DEC-00:20 | 1.37 |
Annual Sum or Average | 0.128986E+13 | 1.37 | |||
Minimum of Months | 0.989479E+11 | 1.36 | 40901.08 | 1.36 | |
Maximum of Months | 0.109549E+12 | 1.37 | 40901.08 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151276E+10 | 0.93 | 564.80 | 01-JAN-00:05 | 0.93 |
February | 0.136636E+10 | 0.93 | 564.80 | 01-FEB-00:10 | 0.93 |
March | 0.151276E+10 | 0.93 | 564.80 | 01-MAR-00:10 | 0.93 |
April | 0.146396E+10 | 0.93 | 564.80 | 01-APR-00:10 | 0.93 |
May | 0.151276E+10 | 0.93 | 564.80 | 01-MAY-00:10 | 0.93 |
June | 0.146396E+10 | 0.93 | 564.80 | 01-JUN-00:10 | 0.93 |
July | 0.151276E+10 | 0.93 | 564.80 | 01-JUL-00:10 | 0.93 |
August | 0.151276E+10 | 0.93 | 564.80 | 01-AUG-00:03 | 0.93 |
September | 0.146396E+10 | 0.93 | 564.80 | 01-SEP-00:05 | 0.93 |
October | 0.151276E+10 | 0.93 | 564.80 | 01-OCT-00:10 | 0.93 |
November | 0.146396E+10 | 0.93 | 564.80 | 01-NOV-00:10 | 0.93 |
December | 0.151276E+10 | 0.93 | 564.80 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.178115E+11 | 0.93 | |||
Minimum of Months | 0.136636E+10 | 0.93 | 564.80 | 0.93 | |
Maximum of Months | 0.151276E+10 | 0.93 | 564.80 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145267E+11 | 0.93 | 5423.64 | 01-JAN-00:05 | 0.92 |
February | 0.131209E+11 | 0.93 | 5423.64 | 01-FEB-00:10 | 0.93 |
March | 0.145267E+11 | 0.93 | 5423.64 | 01-MAR-00:10 | 0.93 |
April | 0.140581E+11 | 0.93 | 5423.64 | 01-APR-00:10 | 0.93 |
May | 0.145267E+11 | 0.93 | 5423.64 | 01-MAY-00:10 | 0.93 |
June | 0.140581E+11 | 0.93 | 5423.64 | 01-JUN-00:10 | 0.93 |
July | 0.145267E+11 | 0.93 | 5423.64 | 01-JUL-00:10 | 0.93 |
August | 0.145267E+11 | 0.93 | 5423.64 | 01-AUG-00:03 | 0.93 |
September | 0.140581E+11 | 0.93 | 5423.64 | 01-SEP-00:05 | 0.93 |
October | 0.145267E+11 | 0.93 | 5423.64 | 01-OCT-00:10 | 0.93 |
November | 0.140581E+11 | 0.93 | 5423.64 | 01-NOV-00:10 | 0.93 |
December | 0.145267E+11 | 0.93 | 5423.64 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.171040E+12 | 0.93 | |||
Minimum of Months | 0.131209E+11 | 0.93 | 5423.64 | 0.92 | |
Maximum of Months | 0.145267E+11 | 0.93 | 5423.64 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147436E+10 | 0.93 | 550.46 | 01-JAN-00:05 | 0.93 |
February | 0.133168E+10 | 0.93 | 550.46 | 01-FEB-00:10 | 0.93 |
March | 0.147436E+10 | 0.93 | 550.46 | 01-MAR-00:10 | 0.93 |
April | 0.142680E+10 | 0.93 | 550.46 | 01-APR-00:10 | 0.93 |
May | 0.147436E+10 | 0.93 | 550.46 | 01-MAY-00:10 | 0.93 |
June | 0.142680E+10 | 0.93 | 550.46 | 01-JUN-00:10 | 0.93 |
July | 0.147436E+10 | 0.93 | 550.46 | 01-JUL-00:10 | 0.93 |
August | 0.147436E+10 | 0.93 | 550.46 | 01-AUG-00:03 | 0.93 |
September | 0.142680E+10 | 0.93 | 550.46 | 01-SEP-00:05 | 0.93 |
October | 0.147436E+10 | 0.93 | 550.46 | 01-OCT-00:10 | 0.93 |
November | 0.142680E+10 | 0.93 | 550.46 | 01-NOV-00:10 | 0.93 |
December | 0.147436E+10 | 0.93 | 550.46 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173594E+11 | 0.93 | |||
Minimum of Months | 0.133168E+10 | 0.93 | 550.46 | 0.93 | |
Maximum of Months | 0.147436E+10 | 0.93 | 550.46 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.117326E+10 | 0.106649E+10 | 3462.08 | 02-JAN-06:03 | 3147.03 | 3147.03 | 46.66 | 8.71 |
February | 0.654464E+09 | 0.594908E+09 | 3023.25 | 21-FEB-06:01 | 2748.13 | 2748.13 | 44.14 | 5.53 |
March | 0.252928E+09 | 0.229911E+09 | 3002.70 | 06-MAR-06:02 | 2729.45 | 2729.45 | 41.31 | 5.45 |
April | 0.107968E+09 | 98142959.30 | 1418.70 | 18-APR-11:30 | 1289.60 | 1289.60 | 34.29 | 1.74 |
May | 26775644.20 | 24339060.58 | 1177.34 | 17-MAY-13:10 | 1070.21 | 1070.21 | 32.99 | 1.39 |
June | 1246513.30 | 1133080.59 | 758.11 | 13-JUN-09:20 | 689.13 | 689.13 | 27.68 | 0.85 |
July | 291507.57 | 264980.38 | 461.91 | 12-JUL-09:20 | 419.88 | 419.88 | 27.10 | 0.50 |
August | 244741.66 | 222470.17 | 539.47 | 03-AUG-09:05 | 490.37 | 490.37 | 27.79 | 0.59 |
September | 4605805.16 | 4186676.89 | 975.42 | 27-SEP-09:20 | 886.66 | 886.66 | 29.05 | 1.12 |
October | 57187843.77 | 51983749.99 | 1539.57 | 30-OCT-05:03 | 1399.47 | 1399.47 | 31.09 | 1.92 |
November | 0.424827E+09 | 0.386168E+09 | 3005.30 | 24-NOV-06:03 | 2731.82 | 2731.82 | 42.07 | 5.46 |
December | 0.877916E+09 | 0.798026E+09 | 3145.35 | 26-DEC-06:02 | 2859.12 | 2859.12 | 45.59 | 6.13 |
Annual Sum or Average | 0.358171E+10 | 0.325578E+10 | ||||||
Minimum of Months | 244741.66 | 222470.17 | 461.91 | 419.88 | 419.88 | 27.10 | 0.50 | |
Maximum of Months | 0.117326E+10 | 0.106649E+10 | 3462.08 | 3147.03 | 3147.03 | 46.66 | 8.71 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 78260.58 | 71138.87 | 3.14 | 11-JAN-07:14 | 2.85 | 2.85 | 6.70 | 0.74 |
February | 11660886.01 | 10599745.38 | 809.31 | 27-FEB-15:05 | 735.66 | 735.66 | 6.71 | 20.39 |
March | 22826269.66 | 20749079.12 | 741.44 | 14-MAR-15:40 | 673.97 | 673.97 | 6.71 | 19.60 |
April | 0.109444E+09 | 99484272.08 | 3604.96 | 26-APR-14:40 | 3276.91 | 3276.91 | 6.72 | 38.68 |
May | 0.162800E+09 | 0.147985E+09 | 4780.64 | 04-MAY-14:05 | 4345.60 | 4345.60 | 8.02 | 43.39 |
June | 0.367396E+09 | 0.333963E+09 | 4367.95 | 22-JUN-14:30 | 3970.47 | 3970.47 | 9.03 | 41.83 |
July | 0.612138E+09 | 0.556434E+09 | 7647.90 | 20-JUL-12:20 | 6951.94 | 6951.94 | 11.14 | 52.34 |
August | 0.892678E+09 | 0.811445E+09 | 9093.74 | 09-AUG-10:00 | 8266.21 | 8266.21 | 11.96 | 56.03 |
September | 0.338510E+09 | 0.307706E+09 | 9128.82 | 11-SEP-14:03 | 8298.10 | 8298.10 | 10.53 | 56.13 |
October | 60901450.27 | 55359418.30 | 1403.84 | 04-OCT-13:20 | 1276.09 | 1276.09 | 8.72 | 26.00 |
November | 4730673.17 | 4300181.91 | 240.68 | 04-NOV-14:05 | 218.78 | 218.78 | 6.70 | 11.53 |
December | 601329.73 | 546608.72 | 12.88 | 16-DEC-07:13 | 11.71 | 11.71 | 6.70 | 2.15 |
Annual Sum or Average | 0.258377E+10 | 0.234864E+10 | ||||||
Minimum of Months | 78260.58 | 71138.87 | 3.14 | 2.85 | 2.85 | 6.70 | 0.74 | |
Maximum of Months | 0.892678E+09 | 0.811445E+09 | 9128.82 | 8298.10 | 8298.10 | 11.96 | 56.13 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.604499E+09 | 0.549489E+09 | 3141.56 | 02-JAN-08:20 | 2855.68 | 2855.68 | 6.72 | 28.07 |
February | 0.120020E+10 | 0.109098E+10 | 3141.56 | 01-FEB-07:12 | 2855.68 | 2855.68 | 6.82 | 28.07 |
March | 0.188465E+10 | 0.171315E+10 | 3141.56 | 01-MAR-06:00 | 2855.68 | 2855.68 | 6.76 | 28.07 |
April | 0.172928E+10 | 0.157191E+10 | 3141.56 | 01-APR-05:02 | 2855.68 | 2855.68 | 7.21 | 28.07 |
May | 0.255243E+10 | 0.232016E+10 | 3141.56 | 01-MAY-04:12 | 2855.68 | 2855.68 | 6.74 | 28.07 |
June | 0.387222E+10 | 0.351984E+10 | 3141.56 | 01-JUN-04:12 | 2855.68 | 2855.68 | 6.91 | 28.07 |
July | 0.528293E+10 | 0.480219E+10 | 3141.56 | 01-JUL-04:12 | 2855.68 | 2855.68 | 7.34 | 28.07 |
August | 0.595875E+10 | 0.541650E+10 | 3141.56 | 01-AUG-00:25 | 2855.68 | 2855.68 | 6.79 | 28.07 |
September | 0.349358E+10 | 0.317566E+10 | 3141.56 | 01-SEP-00:05 | 2855.68 | 2855.68 | 6.75 | 28.07 |
October | 0.156340E+10 | 0.142113E+10 | 3141.56 | 01-OCT-12:15 | 2855.68 | 2855.68 | 6.83 | 28.07 |
November | 0.136712E+10 | 0.124271E+10 | 3141.56 | 01-NOV-06:12 | 2855.68 | 2855.68 | 6.93 | 28.07 |
December | 0.156597E+10 | 0.142347E+10 | 3141.56 | 01-DEC-09:40 | 2855.68 | 2855.68 | 6.73 | 28.07 |
Annual Sum or Average | 0.310750E+11 | 0.282472E+11 | ||||||
Minimum of Months | 0.604499E+09 | 0.549489E+09 | 3141.56 | 2855.68 | 2855.68 | 6.72 | 28.07 | |
Maximum of Months | 0.595875E+10 | 0.541650E+10 | 3141.56 | 2855.68 | 2855.68 | 7.34 | 28.07 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.88 | 0.00 |
April | 86707025.90 | 78816686.54 | 3141.56 | 26-APR-13:20 | 2855.68 | 2855.68 | 14.96 | 14.03 |
May | 0.114039E+09 | 0.103661E+09 | 3141.56 | 04-MAY-13:50 | 2855.68 | 2855.68 | 14.68 | 14.03 |
June | 0.180011E+09 | 0.163630E+09 | 3141.56 | 09-JUN-14:30 | 2855.68 | 2855.68 | 15.15 | 14.03 |
July | 0.517415E+09 | 0.470330E+09 | 3141.56 | 06-JUL-15:50 | 2855.68 | 2855.68 | 17.29 | 14.03 |
August | 0.104331E+10 | 0.948370E+09 | 3141.56 | 07-AUG-10:00 | 2855.68 | 2855.68 | 15.35 | 14.03 |
September | 0.222422E+09 | 0.202182E+09 | 3141.56 | 08-SEP-14:40 | 2855.68 | 2855.68 | 13.81 | 14.03 |
October | 9424676.73 | 8567031.15 | 3141.56 | 04-OCT-13:20 | 2855.68 | 2855.68 | 15.86 | 14.03 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.81 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
Annual Sum or Average | 0.217333E+10 | 0.197556E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.104331E+10 | 0.948370E+09 | 3141.56 | 2855.68 | 2855.68 | 17.29 | 14.03 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-JAN-00:05 | 3390.97 | 3390.97 | 18.48 | 15.74 |
February | 0.902468E+10 | 0.820343E+10 | 3730.44 | 01-FEB-00:10 | 3390.97 | 3390.97 | 19.11 | 15.74 |
March | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-MAR-00:10 | 3390.97 | 3390.97 | 19.80 | 15.74 |
April | 0.966930E+10 | 0.878939E+10 | 3730.44 | 01-APR-00:10 | 3390.97 | 3390.97 | 20.27 | 15.74 |
May | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-MAY-00:10 | 3390.97 | 3390.97 | 18.90 | 15.74 |
June | 0.966930E+10 | 0.878939E+10 | 3730.44 | 01-JUN-00:10 | 3390.97 | 3390.97 | 19.40 | 15.74 |
July | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-JUL-00:10 | 3390.97 | 3390.97 | 19.88 | 15.74 |
August | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-AUG-00:03 | 3390.97 | 3390.97 | 24.95 | 15.74 |
September | 0.966930E+10 | 0.878939E+10 | 3730.44 | 01-SEP-00:05 | 3390.97 | 3390.97 | 18.95 | 15.74 |
October | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-OCT-00:10 | 3390.97 | 3390.97 | 19.34 | 15.74 |
November | 0.966930E+10 | 0.878939E+10 | 3730.44 | 01-NOV-00:10 | 3390.97 | 3390.97 | 19.72 | 15.74 |
December | 0.999161E+10 | 0.908237E+10 | 3730.44 | 01-DEC-00:10 | 3390.97 | 3390.97 | 20.20 | 15.74 |
Annual Sum or Average | 0.117643E+12 | 0.106938E+12 | ||||||
Minimum of Months | 0.902468E+10 | 0.820343E+10 | 3730.44 | 3390.97 | 3390.97 | 18.48 | 15.74 | |
Maximum of Months | 0.999161E+10 | 0.908237E+10 | 3730.44 | 3390.97 | 3390.97 | 24.95 | 15.74 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.98 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 57.00 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 57.07 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.13 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.34 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.28 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.30 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.42 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.41 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.12 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.31 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.20 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.98 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.42 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.238704E+10 | 0.216982E+10 | 12407.32 | 27-JAN-11:30 | 11278.25 | 11278.25 | 21.16 | 50.80 |
February | 0.474027E+10 | 0.430891E+10 | 12437.38 | 27-FEB-15:10 | 11305.58 | 11305.58 | 24.53 | 50.80 |
March | 0.744550E+10 | 0.676796E+10 | 12434.27 | 14-MAR-16:00 | 11302.75 | 11302.75 | 24.18 | 50.80 |
April | 0.716279E+10 | 0.651098E+10 | 24900.82 | 27-APR-13:20 | 22634.84 | 22634.84 | 25.84 | 101.60 |
May | 0.104430E+11 | 0.949267E+10 | 24904.27 | 04-MAY-14:05 | 22637.98 | 22637.98 | 26.00 | 101.60 |
June | 0.159386E+11 | 0.144882E+11 | 24901.77 | 22-JUN-14:50 | 22635.71 | 22635.71 | 25.89 | 101.60 |
July | 0.227799E+11 | 0.207069E+11 | 24951.22 | 31-JUL-16:00 | 22680.66 | 22680.66 | 28.25 | 101.60 |
August | 0.274923E+11 | 0.249905E+11 | 24969.60 | 29-AUG-14:30 | 22697.36 | 22697.36 | 29.13 | 101.60 |
September | 0.146017E+11 | 0.132729E+11 | 24925.25 | 11-SEP-15:25 | 22657.05 | 22657.05 | 27.01 | 101.60 |
October | 0.621613E+10 | 0.565046E+10 | 24868.77 | 04-OCT-13:20 | 22605.71 | 22605.71 | 24.19 | 101.60 |
November | 0.539922E+10 | 0.490789E+10 | 12429.51 | 04-NOV-14:10 | 11298.42 | 11298.42 | 23.65 | 50.80 |
December | 0.618384E+10 | 0.562111E+10 | 12408.32 | 06-DEC-15:10 | 11279.16 | 11279.16 | 21.28 | 50.80 |
Annual Sum or Average | 0.130790E+12 | 0.118888E+12 | ||||||
Minimum of Months | 0.238704E+10 | 0.216982E+10 | 12407.32 | 11278.25 | 11278.25 | 21.16 | 50.80 | |
Maximum of Months | 0.274923E+11 | 0.249905E+11 | 24969.60 | 22697.36 | 22697.36 | 29.13 | 101.60 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 46.28 | 46.28 | 99624.66 | 1286711.37 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29.78 | 29.78 | 60568.80 | 979699.44 | 15-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.91 | 24.91 | 22119.62 | 926247.28 | 06-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.74 | 23.74 | 9829.62 | 350590.30 | 03-APR-13:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24.85 | 24.85 | 2437.72 | 285163.83 | 17-MAY-13:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.48 | 26.48 | 117.49 | 192785.50 | 13-JUN-09:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.70 | 26.70 | 26.96 | 114609.62 | 12-JUL-09:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 27.54 | 27.54 | 22.40 | 133347.78 | 03-AUG-09:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.10 | 28.10 | 432.72 | 248533.80 | 27-SEP-09:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.36 | 26.36 | 5200.66 | 409461.33 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.68 | 27.68 | 38145.54 | 1030791.32 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32.01 | 32.01 | 75265.56 | 1130970.57 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 26020.04 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.74 | 23.74 | 22.40 | 114609.62 | ||
Maximum of Months | 0.00 | 0.00 | 46.28 | 46.28 | 99624.66 | 1286711.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 429.34 | 21288.50 | 11-JAN-07:14 | 6.88 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 8883.72 | 640170.33 | 27-FEB-15:05 | 12.15 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 25595.48 | 572939.84 | 14-MAR-16:00 | 11.57 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 47378.14 | 1317024.53 | 27-APR-14:40 | 12.30 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 71774.02 | 1756309.84 | 04-MAY-14:05 | 14.17 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 133223.29 | 1713836.18 | 21-JUN-14:05 | 13.99 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 229669.18 | 1601653.38 | 31-JUL-16:00 | 13.51 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 302953.51 | 1669905.24 | 29-AUG-14:30 | 13.81 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 118206.11 | 1702435.79 | 11-SEP-15:25 | 13.94 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 37889.17 | 1081058.33 | 04-OCT-15:10 | 11.30 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6759.95 | 475047.10 | 04-NOV-14:10 | 10.74 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2724.33 | 62655.96 | 16-DEC-07:13 | 7.23 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 82788.64 | 0.00 | ||||||
Minimum of Months | 429.34 | 21288.50 | 6.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 302953.51 | 1756309.84 | 14.17 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 224.34 | 23145.10 | 11-JAN-07:12 | 14.14 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 8440.15 | 649662.78 | 27-FEB-15:05 | 14.31 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 24977.50 | 571271.13 | 14-MAR-16:00 | 13.72 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46849.55 | 1314942.98 | 27-APR-14:40 | 16.22 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 71531.67 | 1853833.21 | 04-MAY-14:00 | 17.62 | 11.81 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 133170.27 | 1741435.94 | 20-JUN-13:40 | 17.44 | 11.57 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 229087.33 | 1990006.80 | 20-JUL-12:20 | 15.79 | 11.21 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 303122.91 | 1910278.93 | 09-AUG-10:00 | 14.85 | 12.05 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 120221.60 | 1953818.87 | 11-SEP-15:20 | 15.02 | 10.85 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 37370.15 | 1109391.77 | 04-OCT-13:20 | 16.90 | 9.26 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6283.87 | 480273.28 | 04-NOV-14:05 | 16.65 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2193.02 | 84602.60 | 16-DEC-07:12 | 16.15 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 82618.62 | 0.00 | ||||||
Minimum of Months | 224.34 | 23145.10 | 13.72 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 303122.91 | 1990006.80 | 17.62 | 12.05 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15825.42 | 32930.79 | 12-JAN-20:20 | 18.93 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49299.01 | 197913.38 | 27-FEB-15:00 | 21.95 | 20.50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 84185.34 | 460338.37 | 18-MAR-16:00 | 26.71 | 22.18 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 171172.63 | 1396849.38 | 27-APR-16:00 | 43.36 | 31.47 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53511.99 | 566858.58 | 05-MAY-16:00 | 28.63 | 25.94 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 121528.06 | 937169.74 | 28-JUN-17:00 | 35.26 | 28.94 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 313229.84 | 1404740.43 | 24-JUL-15:00 | 43.50 | 34.01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 587074.39 | 1688014.39 | 10-AUG-17:00 | 48.43 | 36.23 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 59981.53 | 568776.16 | 22-SEP-16:00 | 28.66 | 25.95 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 56878.89 | 396727.08 | 04-OCT-15:00 | 25.56 | 22.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80398.43 | 579995.73 | 04-NOV-15:00 | 28.87 | 23.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102640.60 | 118351.00 | 05-DEC-16:00 | 20.50 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 142428.86 | 0.00 | ||||||
Minimum of Months | 15825.42 | 32930.79 | 18.93 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 587074.39 | 1688014.39 | 48.43 | 36.23 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.13 | 58.13 | 14332.43 | 51088.77 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.62 | 57.62 | 14518.51 | 51150.72 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 15258.69 | 50975.57 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.67 | 57.67 | 13905.14 | 49837.65 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 13845.35 | 48284.37 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.84 | 57.84 | 13658.88 | 46383.74 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 12219.48 | 44763.74 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.95 | 57.95 | 13273.49 | 44110.86 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.95 | 57.95 | 12602.97 | 45073.86 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.90 | 57.90 | 12975.99 | 46819.57 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.82 | 57.82 | 13675.01 | 48660.72 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.73 | 57.73 | 13648.71 | 50167.44 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 13654.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.62 | 57.62 | 12219.48 | 44110.86 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 15258.69 | 51150.72 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19.57 | 13542.58 | 27-JAN-11:30 | 21.16 | 20.54 | 2388.66 | 114057.98 | 09-JAN-06:40 |
February | 7311.12 | 727988.72 | 27-FEB-15:10 | 24.53 | 21.10 | 3222.69 | 106975.32 | 14-FEB-14:10 |
March | 25692.02 | 654108.48 | 14-MAR-16:00 | 24.18 | 21.10 | 2875.54 | 115501.15 | 25-MAR-10:20 |
April | 55242.99 | 2012446.78 | 27-APR-13:20 | 25.84 | 21.63 | 1188.21 | 90281.21 | 24-APR-07:00 |
May | 82627.64 | 2082646.06 | 04-MAY-14:05 | 26.00 | 21.27 | 1159.86 | 87095.10 | 18-MAY-08:00 |
June | 158560.32 | 2031796.66 | 22-JUN-14:50 | 25.89 | 21.13 | 1218.22 | 71141.49 | 06-JUN-13:30 |
July | 290154.33 | 3036299.07 | 31-JUL-16:00 | 28.25 | 23.87 | 1365.26 | 61001.71 | 05-JUL-20:10 |
August | 416735.04 | 3408623.84 | 29-AUG-14:30 | 29.13 | 24.55 | 1648.51 | 54102.30 | 12-AUG-05:30 |
September | 142968.70 | 2509185.84 | 11-SEP-15:25 | 27.01 | 22.05 | 995.14 | 60229.61 | 19-SEP-19:20 |
October | 42030.93 | 1310132.64 | 04-OCT-13:20 | 24.19 | 22.62 | 660.71 | 76899.06 | 13-OCT-09:40 |
November | 5318.92 | 541067.29 | 04-NOV-14:10 | 23.65 | 21.10 | 3975.65 | 103289.52 | 16-NOV-08:50 |
December | 272.53 | 37356.96 | 06-DEC-15:10 | 21.28 | 20.51 | 5206.09 | 105900.39 | 21-DEC-15:10 |
Annual Sum or Average | 103153.24 | 2153.41 | ||||||
Minimum of Months | 19.57 | 13542.58 | 21.16 | 20.51 | 660.71 | 54102.30 | ||
Maximum of Months | 416735.04 | 3408623.84 | 29.13 | 24.55 | 5206.09 | 115501.15 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.105507E+11 | 0.00 | 0.662817E+09 | 0.298771E+10 | 0.00 | 0.00 |
February | 0.612950E+10 | 0.00 | 0.484643E+10 | 0.380679E+10 | 0.00 | 0.00 |
March | 0.155890E+10 | 0.00 | 0.555053E+10 | 0.640259E+10 | 0.00 | 0.00 |
April | 0.433108E+09 | 0.00 | 0.103958E+11 | 0.853373E+10 | 0.00 | 0.00 |
May | 0.205463E+09 | 0.00 | 0.160577E+11 | 0.773967E+10 | 0.00 | 0.00 |
June | 2373.51 | 0.00 | 0.314536E+11 | 0.959131E+10 | 0.00 | 0.00 |
July | 1879.58 | 0.00 | 0.572943E+11 | 0.117247E+11 | 0.00 | 0.00 |
August | 1101.32 | 0.00 | 0.778205E+11 | 0.135093E+11 | 0.00 | 0.00 |
September | 16896838.74 | 0.00 | 0.249290E+11 | 0.787689E+10 | 0.00 | 0.00 |
October | 0.236335E+09 | 0.00 | 0.465388E+10 | 0.634296E+10 | 0.00 | 0.00 |
November | 0.259919E+10 | 0.00 | 0.496308E+10 | 0.464842E+10 | 0.00 | 0.00 |
December | 0.555755E+10 | 0.00 | 0.583333E+10 | 0.441681E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.272877E+11 | 0.00 | 0.244461E+12 | 0.875808E+11 | 0.00 | 0.00 |
Minimum of Months | 1101.32 | 0.00 | 0.662817E+09 | 0.298771E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105507E+11 | 0.00 | 0.778205E+11 | 0.135093E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.218497E+12 | 0.00 | 30746.79 | 0.212418E+11 | 0.00 | 0.00 |
February | 0.118615E+12 | 0.00 | 0.142385E+11 | 0.229624E+11 | 0.00 | 0.00 |
March | 0.478963E+11 | 0.00 | 0.598878E+11 | 0.342378E+11 | 0.00 | 0.00 |
April | 0.212475E+11 | 0.00 | 0.966835E+11 | 0.431877E+11 | 0.00 | 0.00 |
May | 0.538729E+10 | 0.00 | 0.146480E+12 | 0.566557E+11 | 0.00 | 0.00 |
June | 0.261183E+09 | 0.00 | 0.258587E+12 | 0.653667E+11 | 0.00 | 0.00 |
July | 69717979.03 | 0.00 | 0.453434E+12 | 0.759957E+11 | 0.00 | 0.00 |
August | 58466055.14 | 0.00 | 0.599350E+12 | 0.861516E+11 | 0.00 | 0.00 |
September | 0.894890E+09 | 0.00 | 0.235719E+12 | 0.591615E+11 | 0.00 | 0.00 |
October | 0.100942E+11 | 0.00 | 0.881890E+11 | 0.378919E+11 | 0.00 | 0.00 |
November | 0.800066E+11 | 0.00 | 0.103491E+11 | 0.236868E+11 | 0.00 | 0.00 |
December | 0.165905E+12 | 0.00 | 28104.41 | 0.222098E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.668933E+12 | 0.00 | 0.196292E+13 | 0.548749E+12 | 0.00 | 0.00 |
Minimum of Months | 58466055.14 | 0.00 | 28104.41 | 0.212418E+11 | 0.00 | 0.00 |
Maximum of Months | 0.218497E+12 | 0.00 | 0.599350E+12 | 0.861516E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.386596E+11 | 0.00 | 0.00 | 0.260802E+10 | 0.00 | 0.00 |
February | 0.225732E+11 | 0.00 | 0.390035E+09 | 0.227017E+10 | 0.00 | 0.00 |
March | 0.103182E+11 | 0.00 | 0.101644E+10 | 0.269275E+10 | 0.00 | 0.00 |
April | 0.402313E+10 | 0.00 | 0.764622E+10 | 0.347707E+10 | 0.00 | 0.00 |
May | 0.988789E+09 | 0.00 | 0.141105E+11 | 0.475903E+10 | 0.00 | 0.00 |
June | 45248181.10 | 0.00 | 0.268694E+11 | 0.587594E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.481077E+11 | 0.716347E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.632128E+11 | 0.796032E+10 | 0.00 | 0.00 |
September | 0.226341E+09 | 0.00 | 0.215210E+11 | 0.486559E+10 | 0.00 | 0.00 |
October | 0.371852E+10 | 0.00 | 0.309679E+10 | 0.284448E+10 | 0.00 | 0.00 |
November | 0.171442E+11 | 0.00 | 0.516383E+09 | 0.213329E+10 | 0.00 | 0.00 |
December | 0.318468E+11 | 0.00 | 26462.81 | 0.232991E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.129544E+12 | 0.00 | 0.186487E+12 | 0.489800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213329E+10 | 0.00 | 0.00 |
Maximum of Months | 0.386596E+11 | 0.00 | 0.632128E+11 | 0.796032E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.161601E+10 | 0.00 | 44228642.85 | 0.421154E+10 | 0.00 | 0.00 |
February | 0.572126E+09 | 0.00 | 0.969962E+09 | 0.643575E+10 | 0.00 | 0.00 |
March | 10994398.98 | 0.00 | 0.674618E+09 | 0.114253E+11 | 0.00 | 0.00 |
April | 255.55 | 0.00 | 0.456647E+10 | 0.131443E+11 | 0.00 | 0.00 |
May | 125523.05 | 0.00 | 0.970129E+10 | 0.128127E+11 | 0.00 | 0.00 |
June | 1292.43 | 0.00 | 0.206019E+11 | 0.116715E+11 | 0.00 | 0.00 |
July | 1384.97 | 0.00 | 0.374619E+11 | 0.956931E+10 | 0.00 | 0.00 |
August | 591.71 | 0.00 | 0.481420E+11 | 0.118823E+11 | 0.00 | 0.00 |
September | 552.23 | 0.00 | 0.172572E+11 | 0.114890E+11 | 0.00 | 0.00 |
October | 571.52 | 0.00 | 0.288060E+10 | 0.133507E+11 | 0.00 | 0.00 |
November | 17.83 | 0.00 | 0.560913E+09 | 0.130382E+11 | 0.00 | 0.00 |
December | 0.105634E+09 | 0.00 | 9118321.70 | 0.112970E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.230490E+10 | 0.00 | 0.142870E+12 | 0.130328E+12 | 0.00 | 0.00 |
Minimum of Months | 17.83 | 0.00 | 9118321.70 | 0.421154E+10 | 0.00 | 0.00 |
Maximum of Months | 0.161601E+10 | 0.00 | 0.481420E+11 | 0.133507E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.822913E+10 | 0.206435E+12 | 0.00 | 34.66 |
February | 0.00 | 0.00 | 0.109224E+11 | 0.236101E+12 | 0.00 | 49.49 |
March | 0.00 | 0.00 | 0.176526E+11 | 0.296476E+12 | 0.00 | 67.37 |
April | 0.00 | 0.00 | 0.100504E+12 | 0.286467E+12 | 0.00 | 58.27 |
May | 0.00 | 0.00 | 0.813806E+10 | 0.149624E+12 | 0.00 | 13.48 |
June | 0.00 | 0.00 | 0.454491E+11 | 0.141222E+12 | 0.00 | 8.53 |
July | 0.00 | 0.00 | 0.267712E+12 | 0.190877E+12 | 0.00 | 8.22 |
August | 0.00 | 0.00 | 0.677334E+12 | 0.253603E+12 | 0.00 | 0.29 |
September | 0.00 | 0.00 | 0.728504E+10 | 0.111637E+12 | 0.00 | 0.64 |
October | 0.00 | 0.00 | 0.752828E+10 | 0.168773E+12 | 0.00 | 20.65 |
November | 0.00 | 0.00 | 0.151615E+11 | 0.230822E+12 | 0.00 | 44.50 |
December | 0.00 | 0.00 | 0.192834E+11 | 0.336944E+12 | 0.00 | 82.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.118520E+13 | 0.260898E+13 | 0.00 | 388.36 |
Minimum of Months | 0.00 | 0.00 | 0.728504E+10 | 0.111637E+12 | 0.00 | 0.29 |
Maximum of Months | 0.00 | 0.00 | 0.677334E+12 | 0.336944E+12 | 0.00 | 82.26 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.505833E+10 | 0.249225E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107559E+11 | 0.332828E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185279E+11 | 0.475370E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.240802E+11 | 0.555573E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.690316E+10 | 0.280466E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128624E+11 | 0.377736E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198336E+11 | 0.508229E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260375E+11 | 0.626678E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.687447E+10 | 0.273860E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126731E+11 | 0.376043E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.177712E+11 | 0.453328E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241430E+11 | 0.562435E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185521E+12 | 0.507177E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.505833E+10 | 0.249225E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260375E+11 | 0.626678E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.194049E+11 | 0.185349E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.824425E+11 | 0.283939E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.162826E+12 | 0.432538E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.221621E+12 | 0.519128E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.597064E+11 | 0.257848E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118334E+12 | 0.354276E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.186590E+12 | 0.481928E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246595E+12 | 0.596455E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.599508E+11 | 0.252523E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108832E+12 | 0.339968E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150076E+12 | 0.402871E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.203969E+12 | 0.497602E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162035E+13 | 0.460442E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.194049E+11 | 0.185349E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.246595E+12 | 0.596455E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.617230E+09 | 0.160818E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.628086E+10 | 0.251142E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.147449E+11 | 0.410057E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.212909E+11 | 0.508620E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.539862E+10 | 0.250035E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115980E+11 | 0.352835E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.185399E+11 | 0.482973E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.245236E+11 | 0.597650E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.541176E+10 | 0.244604E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.949598E+10 | 0.319071E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.130177E+11 | 0.373062E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.180771E+11 | 0.463850E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148996E+12 | 0.441472E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.617230E+09 | 0.160818E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.245236E+11 | 0.597650E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.298771E+10 | 0.662817E+09 | 0.105507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380679E+10 | 0.484643E+10 | 0.612950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640259E+10 | 0.555053E+10 | 0.155890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853373E+10 | 0.103958E+11 | 0.433108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.773967E+10 | 0.160577E+11 | 0.205463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.959131E+10 | 0.314536E+11 | 2373.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117247E+11 | 0.572943E+11 | 1879.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135093E+11 | 0.778205E+11 | 1101.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.787689E+10 | 0.249290E+11 | 16896838.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634296E+10 | 0.465388E+10 | 0.236335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464842E+10 | 0.496308E+10 | 0.259919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441681E+10 | 0.583333E+10 | 0.555755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.875808E+11 | 0.244461E+12 | 0.272877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298771E+10 | 0.662817E+09 | 1101.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135093E+11 | 0.778205E+11 | 0.105507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.212418E+11 | 30746.79 | 0.218497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229624E+11 | 0.142385E+11 | 0.118615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342378E+11 | 0.598878E+11 | 0.478963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.431877E+11 | 0.966835E+11 | 0.212475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566557E+11 | 0.146480E+12 | 0.538729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653667E+11 | 0.258587E+12 | 0.261183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.759957E+11 | 0.453434E+12 | 69717979.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.861516E+11 | 0.599350E+12 | 58466055.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.591615E+11 | 0.235719E+12 | 0.894890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378919E+11 | 0.881890E+11 | 0.100942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236868E+11 | 0.103491E+11 | 0.800066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222098E+11 | 28104.41 | 0.165905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548749E+12 | 0.196292E+13 | 0.668933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212418E+11 | 28104.41 | 58466055.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.861516E+11 | 0.599350E+12 | 0.218497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.260802E+10 | 0.00 | 0.386596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227017E+10 | 0.390035E+09 | 0.225732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269275E+10 | 0.101644E+10 | 0.103182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347707E+10 | 0.764622E+10 | 0.402313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.475903E+10 | 0.141105E+11 | 0.988789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587594E+10 | 0.268694E+11 | 45248181.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716347E+10 | 0.481077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.796032E+10 | 0.632128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.486559E+10 | 0.215210E+11 | 0.226341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284448E+10 | 0.309679E+10 | 0.371852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213329E+10 | 0.516383E+09 | 0.171442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232991E+10 | 26462.81 | 0.318468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489800E+11 | 0.186487E+12 | 0.129544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.213329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.796032E+10 | 0.632128E+11 | 0.386596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.421154E+10 | 44228642.85 | 0.161601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.643575E+10 | 0.969962E+09 | 0.572126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114253E+11 | 0.674618E+09 | 10994398.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131443E+11 | 0.456647E+10 | 255.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128127E+11 | 0.970129E+10 | 125523.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116715E+11 | 0.206019E+11 | 1292.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.956931E+10 | 0.374619E+11 | 1384.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118823E+11 | 0.481420E+11 | 591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114890E+11 | 0.172572E+11 | 552.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133507E+11 | 0.288060E+10 | 571.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130382E+11 | 0.560913E+09 | 17.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112970E+11 | 9118321.70 | 0.105634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130328E+12 | 0.142870E+12 | 0.230490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421154E+10 | 9118321.70 | 17.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133507E+11 | 0.481420E+11 | 0.161601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109549E+12 | 0.451994E+10 | 0.00 | 0.00 | 0.00 | 0.927592E+11 | 0.00 | 0.00 |
February | 0.989479E+11 | 0.679760E+10 | 0.00 | 0.00 | 0.00 | 0.132432E+12 | 0.00 | 0.00 |
March | 0.109549E+12 | 0.118246E+11 | 0.00 | 0.00 | 0.00 | 0.180287E+12 | 0.00 | 0.00 |
April | 0.106016E+12 | 0.766841E+11 | 0.00 | 0.00 | 0.00 | 0.155929E+12 | 0.00 | 0.00 |
May | 0.109549E+12 | 0.430446E+10 | 0.00 | 0.00 | 0.00 | 0.360784E+11 | 0.00 | 0.00 |
June | 0.106016E+12 | 0.331722E+11 | 0.00 | 0.00 | 0.00 | 0.228271E+11 | 0.00 | 0.00 |
July | 0.109549E+12 | 0.208486E+12 | 0.00 | 0.00 | 0.00 | 0.220017E+11 | 0.00 | 0.00 |
August | 0.109549E+12 | 0.534071E+12 | 0.00 | 0.00 | 0.00 | 0.786639E+09 | 0.00 | 0.00 |
September | 0.106016E+12 | 0.339362E+10 | 0.00 | 0.00 | 0.00 | 0.172204E+10 | 0.00 | 0.00 |
October | 0.109549E+12 | 0.380186E+10 | 0.00 | 0.00 | 0.00 | 0.552489E+11 | 0.00 | 0.00 |
November | 0.106016E+12 | 0.997547E+10 | 0.00 | 0.00 | 0.00 | 0.119084E+12 | 0.00 | 0.00 |
December | 0.109549E+12 | 0.130203E+11 | 0.00 | 0.00 | 0.00 | 0.220141E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.128986E+13 | 0.910050E+12 | 0.00 | 0.00 | 0.00 | 0.103930E+13 | 0.00 | 0.00 |
Minimum of Months | 0.989479E+11 | 0.339362E+10 | 0.00 | 0.00 | 0.00 | 0.786639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109549E+12 | 0.534071E+12 | 0.00 | 0.00 | 0.00 | 0.220141E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151276E+10 | 0.407884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136636E+10 | 0.879396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151276E+10 | 0.152870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146396E+10 | 0.199884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151276E+10 | 0.561126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146396E+10 | 0.105490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151276E+10 | 0.162641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151276E+10 | 0.212835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146396E+10 | 0.559983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151276E+10 | 0.104255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146396E+10 | 0.147019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151276E+10 | 0.200314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178115E+11 | 0.152615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136636E+10 | 0.407884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151276E+10 | 0.212835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145267E+11 | 0.153967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131209E+11 | 0.671695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145267E+11 | 0.134099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140581E+11 | 0.183766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145267E+11 | 0.484483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140581E+11 | 0.969641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145267E+11 | 0.152924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145267E+11 | 0.201476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140581E+11 | 0.487566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145267E+11 | 0.893620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140581E+11 | 0.123847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145267E+11 | 0.168736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171040E+12 | 0.133094E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131209E+11 | 0.153967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145267E+11 | 0.201476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147436E+10 | 0.483413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133168E+10 | 0.510112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147436E+10 | 0.121187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142680E+10 | 0.176315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147436E+10 | 0.437263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142680E+10 | 0.949641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147436E+10 | 0.151845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147436E+10 | 0.200214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142680E+10 | 0.439253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147436E+10 | 0.777963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142680E+10 | 0.107139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147436E+10 | 0.149130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173594E+11 | 0.122209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133168E+10 | 0.483413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147436E+10 | 0.200214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.298771E+10 | 0.105507E+11 | 0.662817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380679E+10 | 0.612950E+10 | 0.484643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640259E+10 | 0.155890E+10 | 0.555053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853373E+10 | 0.433108E+09 | 0.103958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.773967E+10 | 0.205463E+09 | 0.160577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.959131E+10 | 2373.51 | 0.314536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117247E+11 | 1879.58 | 0.572943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135093E+11 | 1101.32 | 0.778205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.787689E+10 | 16896838.74 | 0.249290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634296E+10 | 0.236335E+09 | 0.465388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464842E+10 | 0.259919E+10 | 0.496308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441681E+10 | 0.555755E+10 | 0.583333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.875808E+11 | 0.272877E+11 | 0.244461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298771E+10 | 1101.32 | 0.662817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135093E+11 | 0.105507E+11 | 0.778205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.212418E+11 | 0.218497E+12 | 30746.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229624E+11 | 0.118615E+12 | 0.142385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342378E+11 | 0.478963E+11 | 0.598878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.431877E+11 | 0.212475E+11 | 0.966835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566557E+11 | 0.538729E+10 | 0.146480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653667E+11 | 0.261183E+09 | 0.258587E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.759957E+11 | 69717979.03 | 0.453434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.861516E+11 | 58466055.14 | 0.599350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.591615E+11 | 0.894890E+09 | 0.235719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378919E+11 | 0.100942E+11 | 0.881890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236868E+11 | 0.800066E+11 | 0.103491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222098E+11 | 0.165905E+12 | 28104.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548749E+12 | 0.668933E+12 | 0.196292E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212418E+11 | 58466055.14 | 28104.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.861516E+11 | 0.218497E+12 | 0.599350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.260802E+10 | 0.386596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227017E+10 | 0.225732E+11 | 0.390035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269275E+10 | 0.103182E+11 | 0.101644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347707E+10 | 0.402313E+10 | 0.764622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.475903E+10 | 0.988789E+09 | 0.141105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587594E+10 | 45248181.10 | 0.268694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716347E+10 | 0.00 | 0.481077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.796032E+10 | 0.00 | 0.632128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.486559E+10 | 0.226341E+09 | 0.215210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284448E+10 | 0.371852E+10 | 0.309679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213329E+10 | 0.171442E+11 | 0.516383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232991E+10 | 0.318468E+11 | 26462.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489800E+11 | 0.129544E+12 | 0.186487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.213329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.796032E+10 | 0.386596E+11 | 0.632128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.421154E+10 | 0.161601E+10 | 44228642.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.643575E+10 | 0.572126E+09 | 0.969962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114253E+11 | 10994398.98 | 0.674618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131443E+11 | 255.55 | 0.456647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128127E+11 | 125523.05 | 0.970129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116715E+11 | 1292.43 | 0.206019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.956931E+10 | 1384.97 | 0.374619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118823E+11 | 591.71 | 0.481420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114890E+11 | 552.23 | 0.172572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133507E+11 | 571.52 | 0.288060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130382E+11 | 17.83 | 0.560913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112970E+11 | 0.105634E+09 | 9118321.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130328E+12 | 0.230490E+10 | 0.142870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421154E+10 | 17.83 | 9118321.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133507E+11 | 0.161601E+10 | 0.481420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109549E+12 | 0.00 | 0.822913E+10 | 0.00 | 0.370919E+10 | 0.00 | 0.00 | 0.00 | 0.931767E+11 | 0.00 | 0.00 | 0.00 |
February | 0.989479E+11 | 0.00 | 0.109224E+11 | 0.00 | 0.412479E+10 | 0.00 | 0.00 | 0.00 | 0.133028E+12 | 0.00 | 0.00 | 0.00 |
March | 0.109549E+12 | 0.00 | 0.176526E+11 | 0.00 | 0.582800E+10 | 0.00 | 0.00 | 0.00 | 0.181099E+12 | 0.00 | 0.00 | 0.00 |
April | 0.106016E+12 | 0.00 | 0.100504E+12 | 0.00 | 0.238198E+11 | 0.00 | 0.00 | 0.00 | 0.156631E+12 | 0.00 | 0.00 | 0.00 |
May | 0.109549E+12 | 0.00 | 0.813806E+10 | 0.00 | 0.383360E+10 | 0.00 | 0.00 | 0.00 | 0.362408E+11 | 0.00 | 0.00 | 0.00 |
June | 0.106016E+12 | 0.00 | 0.454491E+11 | 0.00 | 0.122768E+11 | 0.00 | 0.00 | 0.00 | 0.229298E+11 | 0.00 | 0.00 | 0.00 |
July | 0.109549E+12 | 0.00 | 0.267712E+12 | 0.00 | 0.592265E+11 | 0.00 | 0.00 | 0.00 | 0.221007E+11 | 0.00 | 0.00 | 0.00 |
August | 0.109549E+12 | 0.00 | 0.677334E+12 | 0.00 | 0.143263E+12 | 0.00 | 0.00 | 0.00 | 0.790180E+09 | 0.00 | 0.00 | 0.00 |
September | 0.106016E+12 | 0.00 | 0.728504E+10 | 0.00 | 0.389142E+10 | 0.00 | 0.00 | 0.00 | 0.172979E+10 | 0.00 | 0.00 | 0.00 |
October | 0.109549E+12 | 0.00 | 0.752828E+10 | 0.00 | 0.372642E+10 | 0.00 | 0.00 | 0.00 | 0.554976E+11 | 0.00 | 0.00 | 0.00 |
November | 0.106016E+12 | 0.00 | 0.151615E+11 | 0.00 | 0.518603E+10 | 0.00 | 0.00 | 0.00 | 0.119620E+12 | 0.00 | 0.00 | 0.00 |
December | 0.109549E+12 | 0.00 | 0.192834E+11 | 0.00 | 0.626312E+10 | 0.00 | 0.00 | 0.00 | 0.221132E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128986E+13 | 0.00 | 0.118520E+13 | 0.00 | 0.275149E+12 | 0.00 | 0.00 | 0.00 | 0.104398E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.989479E+11 | 0.00 | 0.728504E+10 | 0.00 | 0.370919E+10 | 0.00 | 0.00 | 0.00 | 0.790180E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109549E+12 | 0.00 | 0.677334E+12 | 0.00 | 0.143263E+12 | 0.00 | 0.00 | 0.00 | 0.221132E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151276E+10 | 0.00 | 0.505833E+10 | 0.00 | 0.979488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136636E+10 | 0.00 | 0.107559E+11 | 0.00 | 0.196192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151276E+10 | 0.00 | 0.185279E+11 | 0.00 | 0.324094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146396E+10 | 0.00 | 0.240802E+11 | 0.00 | 0.409177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151276E+10 | 0.00 | 0.690316E+10 | 0.00 | 0.129190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146396E+10 | 0.00 | 0.128624E+11 | 0.00 | 0.231340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151276E+10 | 0.00 | 0.198336E+11 | 0.00 | 0.356953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151276E+10 | 0.00 | 0.260375E+11 | 0.00 | 0.475402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146396E+10 | 0.00 | 0.687447E+10 | 0.00 | 0.127464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151276E+10 | 0.00 | 0.126731E+11 | 0.00 | 0.224767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146396E+10 | 0.00 | 0.177712E+11 | 0.00 | 0.306932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151276E+10 | 0.00 | 0.241430E+11 | 0.00 | 0.411159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178115E+11 | 0.00 | 0.185521E+12 | 0.00 | 0.329062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136636E+10 | 0.00 | 0.505833E+10 | 0.00 | 0.979488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151276E+10 | 0.00 | 0.260375E+11 | 0.00 | 0.475402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145267E+11 | 0.00 | 0.194049E+11 | 0.00 | 0.400823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131209E+11 | 0.00 | 0.824425E+11 | 0.00 | 0.152730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145267E+11 | 0.00 | 0.162826E+12 | 0.00 | 0.287271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140581E+11 | 0.00 | 0.221621E+12 | 0.00 | 0.378548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145267E+11 | 0.00 | 0.597064E+11 | 0.00 | 0.112581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140581E+11 | 0.00 | 0.118334E+12 | 0.00 | 0.213695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145267E+11 | 0.00 | 0.186590E+12 | 0.00 | 0.336661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145267E+11 | 0.00 | 0.246595E+12 | 0.00 | 0.451188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140581E+11 | 0.00 | 0.599508E+11 | 0.00 | 0.111942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145267E+11 | 0.00 | 0.108832E+12 | 0.00 | 0.194702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140581E+11 | 0.00 | 0.150076E+12 | 0.00 | 0.262290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145267E+11 | 0.00 | 0.203969E+12 | 0.00 | 0.352336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171040E+12 | 0.00 | 0.162035E+13 | 0.00 | 0.289403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131209E+11 | 0.00 | 0.194049E+11 | 0.00 | 0.400823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145267E+11 | 0.00 | 0.246595E+12 | 0.00 | 0.451188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147436E+10 | 0.00 | 0.617230E+09 | 0.00 | 0.133817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133168E+10 | 0.00 | 0.628086E+10 | 0.00 | 0.117974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147436E+10 | 0.00 | 0.147449E+11 | 0.00 | 0.262621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142680E+10 | 0.00 | 0.212909E+11 | 0.00 | 0.365939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147436E+10 | 0.00 | 0.539862E+10 | 0.00 | 0.102599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142680E+10 | 0.00 | 0.115980E+11 | 0.00 | 0.210155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147436E+10 | 0.00 | 0.185399E+11 | 0.00 | 0.335536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147436E+10 | 0.00 | 0.245236E+11 | 0.00 | 0.450214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142680E+10 | 0.00 | 0.541176E+10 | 0.00 | 0.101924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147436E+10 | 0.00 | 0.949598E+10 | 0.00 | 0.171635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142680E+10 | 0.00 | 0.130177E+11 | 0.00 | 0.230381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147436E+10 | 0.00 | 0.180771E+11 | 0.00 | 0.316414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173594E+11 | 0.00 | 0.148996E+12 | 0.00 | 0.267877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133168E+10 | 0.00 | 0.617230E+09 | 0.00 | 0.133817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147436E+10 | 0.00 | 0.245236E+11 | 0.00 | 0.450214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 81063558.94 | 0.00 | 0.00 | 0.536014E+11 | 0.00 | 0.44 |
February | 0.00 | 0.00 | 0.00 | 81705285.48 | 0.00 | 0.00 | 0.519371E+11 | 0.00 | 0.56 |
March | 0.00 | 0.00 | 0.00 | 0.107170E+09 | 0.00 | 0.00 | 0.688105E+11 | 0.00 | 0.76 |
April | 0.00 | 23488631.05 | 0.00 | 0.102212E+09 | 0.00 | 0.00 | 0.639458E+11 | 0.00 | 0.88 |
May | 0.00 | 9329317.63 | 0.00 | 0.118260E+09 | 0.00 | 0.00 | 0.604925E+11 | 0.00 | 1.03 |
June | 0.00 | 13641715.23 | 0.00 | 0.129662E+09 | 0.00 | 0.00 | 0.506447E+11 | 0.00 | 1.15 |
July | 0.00 | 0.478724E+09 | 0.00 | 0.126507E+09 | 0.00 | 0.00 | 0.320262E+11 | 0.00 | 0.95 |
August | 0.00 | 0.686978E+09 | 0.00 | 0.127494E+09 | 0.00 | 0.00 | 0.300391E+11 | 0.00 | 0.98 |
September | 0.00 | 0.00 | 0.00 | 0.121101E+09 | 0.00 | 0.00 | 0.512592E+11 | 0.00 | 1.10 |
October | 0.00 | 0.00 | 0.00 | 0.117949E+09 | 0.00 | 0.00 | 0.690120E+11 | 0.00 | 0.95 |
November | 0.00 | 0.00 | 0.00 | 0.105575E+09 | 0.00 | 0.00 | 0.682478E+11 | 0.00 | 0.74 |
December | 0.00 | 0.00 | 0.00 | 95140853.77 | 0.00 | 0.00 | 0.644312E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.00 | 0.121216E+10 | 0.00 | 0.131384E+10 | 0.00 | 0.00 | 0.664448E+12 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 81063558.94 | 0.00 | 0.00 | 0.300391E+11 | 0.00 | 0.44 |
Maximum of Months | 0.00 | 0.686978E+09 | 0.00 | 0.129662E+09 | 0.00 | 0.00 | 0.690120E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201658E+10 | 0.00 | 0.00 | 58615907.63 | 0.00 | 0.00 | 0.465961E+11 | 0.00 | 0.38 |
February | 0.165351E+10 | 0.00 | 0.00 | 69823779.62 | 0.00 | 0.00 | 0.438718E+11 | 0.00 | 0.46 |
March | 0.159916E+10 | 0.00 | 0.00 | 0.102234E+09 | 0.00 | 0.00 | 0.578852E+11 | 0.00 | 0.61 |
April | 0.465654E+10 | 17062322.38 | 0.00 | 0.102231E+09 | 0.00 | 0.00 | 0.565114E+11 | 0.00 | 0.79 |
May | 0.323114E+10 | 499077.79 | 0.00 | 96719026.90 | 0.00 | 0.00 | 0.512657E+11 | 0.00 | 0.83 |
June | 0.297146E+10 | 16645631.03 | 0.00 | 0.107950E+09 | 5959544.45 | 0.00 | 0.488485E+11 | 0.00 | 1.01 |
July | 0.766528E+10 | 0.150487E+09 | 0.00 | 0.104576E+09 | 3561673.20 | 0.00 | 0.371459E+11 | 0.00 | 1.04 |
August | 0.868931E+10 | 0.533953E+09 | 0.00 | 0.102409E+09 | 6981390.21 | 0.00 | 0.346062E+11 | 0.00 | 1.08 |
September | 0.254856E+10 | 0.00 | 0.00 | 96094254.54 | 0.00 | 0.00 | 0.449850E+11 | 0.00 | 0.88 |
October | 0.226188E+10 | 0.00 | 0.00 | 95533838.02 | 0.00 | 0.00 | 0.551488E+11 | 0.00 | 0.73 |
November | 0.172931E+10 | 0.00 | 0.00 | 87976549.75 | 0.00 | 0.00 | 0.518260E+11 | 0.00 | 0.54 |
December | 0.159617E+10 | 0.00 | 0.00 | 87546745.31 | 0.00 | 0.00 | 0.504487E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.406189E+11 | 0.718647E+09 | 0.00 | 0.111171E+10 | 16502607.86 | 0.00 | 0.579139E+12 | 0.00 | 0.73 |
Minimum of Months | 0.159617E+10 | 0.00 | 0.00 | 58615907.63 | 0.00 | 0.00 | 0.346062E+11 | 0.00 | 0.38 |
Maximum of Months | 0.868931E+10 | 0.533953E+09 | 0.00 | 0.107950E+09 | 6981390.21 | 0.00 | 0.578852E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251895E+12 | 0.00 | 0.00 | 91114725.99 | 0.00 | 0.169363E+10 | 0.109093E+12 | 0.00 | 0.30 |
February | 0.158665E+12 | 0.00 | 0.00 | 0.206113E+09 | 0.00 | 0.00 | 0.174465E+12 | 0.00 | 0.33 |
March | 0.900257E+11 | 0.00 | 0.00 | 0.448309E+09 | 0.00 | 0.00 | 0.301934E+12 | 0.00 | 0.39 |
April | 0.476393E+11 | 0.161823E+09 | 0.00 | 0.512921E+09 | 39922542.36 | 0.00 | 0.328093E+12 | 0.00 | 0.49 |
May | 0.319445E+11 | 5014107.88 | 0.00 | 0.697740E+09 | 0.00 | 0.00 | 0.393066E+12 | 0.00 | 0.66 |
June | 0.235184E+11 | 0.134810E+09 | 0.00 | 0.773113E+09 | 26350896.77 | 0.00 | 0.366405E+12 | 0.00 | 0.77 |
July | 0.299093E+11 | 0.111913E+10 | 0.00 | 0.730413E+09 | 39111949.37 | 0.00 | 0.271058E+12 | 0.00 | 0.73 |
August | 0.191532E+11 | 0.456136E+10 | 0.00 | 0.751325E+09 | 44407693.18 | 0.00 | 0.255149E+12 | 0.00 | 0.72 |
September | 0.260235E+11 | 0.00 | 0.00 | 0.691634E+09 | 0.00 | 0.00 | 0.332163E+12 | 0.00 | 0.68 |
October | 0.602020E+11 | 0.00 | 0.00 | 0.504179E+09 | 0.00 | 0.00 | 0.303772E+12 | 0.00 | 0.45 |
November | 0.118190E+12 | 0.00 | 0.00 | 0.288549E+09 | 0.00 | 0.00 | 0.242847E+12 | 0.00 | 0.36 |
December | 0.197670E+12 | 0.00 | 0.00 | 0.168135E+09 | 0.00 | 16442322.04 | 0.166646E+12 | 0.00 | 0.31 |
Annual Sum or Average | 0.105484E+13 | 0.598215E+10 | 0.00 | 0.586354E+10 | 0.149793E+09 | 0.171007E+10 | 0.324469E+13 | 0.00 | 0.52 |
Minimum of Months | 0.191532E+11 | 0.00 | 0.00 | 91114725.99 | 0.00 | 0.00 | 0.109093E+12 | 0.00 | 0.30 |
Maximum of Months | 0.251895E+12 | 0.456136E+10 | 0.00 | 0.773113E+09 | 44407693.18 | 0.169363E+10 | 0.393066E+12 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297180E+11 | 0.00 | 0.00 | 151718.25 | 0.00 | 0.157030E+10 | 0.503929E+09 | 0.00 | 0.29 |
February | 0.237086E+11 | 0.00 | 0.00 | 3489805.56 | 0.00 | 0.746779E+09 | 0.381377E+10 | 0.00 | 0.31 |
March | 0.193962E+11 | 0.00 | 0.00 | 14229502.84 | 0.00 | 0.133095E+09 | 0.135353E+11 | 0.00 | 0.36 |
April | 0.113977E+11 | 4332014.68 | 0.00 | 29071743.05 | 834274.49 | 0.00 | 0.212792E+11 | 0.00 | 0.44 |
May | 0.762823E+10 | 0.00 | 0.00 | 48933580.31 | 0.00 | 0.00 | 0.312409E+11 | 0.00 | 0.61 |
June | 0.429617E+10 | 5307721.03 | 0.00 | 62730322.96 | 1396648.56 | 0.00 | 0.331151E+11 | 0.00 | 0.75 |
July | 0.349376E+10 | 58240279.99 | 0.00 | 64638459.10 | 2215727.42 | 0.00 | 0.259533E+11 | 0.00 | 0.74 |
August | 0.294884E+10 | 0.295314E+09 | 0.00 | 65378637.28 | 11962029.03 | 0.00 | 0.223574E+11 | 0.00 | 0.70 |
September | 0.679160E+10 | 0.00 | 0.00 | 45299321.37 | 0.00 | 0.00 | 0.243637E+11 | 0.00 | 0.62 |
October | 0.135421E+11 | 0.00 | 0.00 | 20595644.61 | 0.00 | 16365201.51 | 0.163813E+11 | 0.00 | 0.40 |
November | 0.225162E+11 | 0.00 | 0.00 | 4916130.57 | 0.00 | 0.412998E+09 | 0.547099E+10 | 0.00 | 0.31 |
December | 0.283839E+11 | 0.00 | 0.00 | 267615.68 | 0.00 | 0.103547E+10 | 0.820919E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.173821E+12 | 0.363194E+09 | 0.00 | 0.359702E+09 | 16408679.50 | 0.391501E+10 | 0.198836E+12 | 0.00 | 0.49 |
Minimum of Months | 0.294884E+10 | 0.00 | 0.00 | 151718.25 | 0.00 | 0.00 | 0.503929E+09 | 0.00 | 0.29 |
Maximum of Months | 0.297180E+11 | 0.295314E+09 | 0.00 | 65378637.28 | 11962029.03 | 0.157030E+10 | 0.331151E+11 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412716E+10 | 0.00 | 0.00 | 77906.75 | 0.00 | 0.00 | 0.160716E+09 | 0.00 | 0.27 |
February | 0.295690E+10 | 0.00 | 0.00 | 1053079.07 | 0.00 | 0.00 | 0.870750E+09 | 0.00 | 0.31 |
March | 0.203195E+10 | 0.00 | 0.00 | 4177858.54 | 0.00 | 0.00 | 0.298444E+10 | 0.00 | 0.42 |
April | 0.146769E+10 | 2781644.59 | 0.00 | 7117872.79 | 0.00 | 0.00 | 0.461327E+10 | 0.00 | 0.66 |
May | 0.102589E+10 | 132685.15 | 0.00 | 9428170.56 | 0.00 | 0.00 | 0.547224E+10 | 0.00 | 0.85 |
June | 0.562313E+09 | 3035837.66 | 0.00 | 12750454.68 | 748802.56 | 0.00 | 0.607674E+10 | 0.00 | 1.11 |
July | 0.106938E+10 | 27885729.28 | 0.00 | 13350698.83 | 447515.75 | 0.00 | 0.490262E+10 | 0.00 | 1.19 |
August | 0.119041E+10 | 95685989.01 | 0.00 | 12234154.04 | 877195.04 | 0.00 | 0.417183E+10 | 0.00 | 1.15 |
September | 0.951281E+09 | 0.00 | 0.00 | 7875766.40 | 0.00 | 0.00 | 0.401514E+10 | 0.00 | 0.79 |
October | 0.173254E+10 | 0.00 | 0.00 | 4484951.13 | 0.00 | 0.00 | 0.320239E+10 | 0.00 | 0.51 |
November | 0.228475E+10 | 0.00 | 0.00 | 2155157.62 | 0.00 | 0.00 | 0.176368E+10 | 0.00 | 0.33 |
December | 0.313817E+10 | 0.00 | 0.00 | 592951.91 | 0.00 | 0.00 | 0.691125E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.225384E+11 | 0.129522E+09 | 0.00 | 75299022.31 | 2073513.35 | 0.00 | 0.389249E+11 | 0.00 | 0.66 |
Minimum of Months | 0.562313E+09 | 0.00 | 0.00 | 77906.75 | 0.00 | 0.00 | 0.160716E+09 | 0.00 | 0.25 |
Maximum of Months | 0.412716E+10 | 95685989.01 | 0.00 | 13350698.83 | 877195.04 | 0.00 | 0.607674E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261820E+10 | 0.00 | 0.00 | 182810.24 | 0.00 | 8404943.59 | 0.161546E+09 | 0.00 | 0.27 |
February | 0.178138E+10 | 0.00 | 0.00 | 1441401.77 | 0.00 | 162027.69 | 0.861975E+09 | 0.00 | 0.33 |
March | 0.127815E+10 | 0.00 | 0.00 | 4720580.96 | 0.00 | 0.00 | 0.267037E+10 | 0.00 | 0.50 |
April | 0.908919E+09 | 2137245.41 | 0.00 | 7930300.25 | 0.00 | 0.00 | 0.465788E+10 | 0.00 | 0.93 |
May | 0.608500E+09 | 106448.49 | 0.00 | 10352901.04 | 0.00 | 0.00 | 0.535783E+10 | 0.00 | 1.20 |
June | 0.341003E+09 | 1928048.70 | 0.00 | 13863732.28 | 483964.46 | 0.00 | 0.628719E+10 | 0.00 | 1.64 |
July | 0.665781E+09 | 21704911.91 | 0.00 | 13942141.93 | 289237.42 | 0.00 | 0.460644E+10 | 0.00 | 1.62 |
August | 0.800237E+09 | 74468855.83 | 0.00 | 13122677.29 | 98436.46 | 0.00 | 0.401990E+10 | 0.00 | 1.62 |
September | 0.555832E+09 | 0.00 | 0.00 | 9414692.89 | 0.00 | 0.00 | 0.430964E+10 | 0.00 | 1.20 |
October | 0.108620E+10 | 0.00 | 0.00 | 4870966.49 | 0.00 | 0.00 | 0.307108E+10 | 0.00 | 0.67 |
November | 0.160960E+10 | 0.00 | 0.00 | 1468468.94 | 0.00 | 0.00 | 0.102359E+10 | 0.00 | 0.33 |
December | 0.222213E+10 | 0.00 | 0.00 | 497770.42 | 0.00 | 0.00 | 0.289749E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.144759E+11 | 0.100346E+09 | 0.00 | 81808444.50 | 871638.34 | 8566971.28 | 0.373172E+11 | 0.00 | 0.88 |
Minimum of Months | 0.341003E+09 | 0.00 | 0.00 | 182810.24 | 0.00 | 0.00 | 0.161546E+09 | 0.00 | 0.25 |
Maximum of Months | 0.261820E+10 | 74468855.83 | 0.00 | 13942141.93 | 483964.46 | 8404943.59 | 0.628719E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.342018E+10 | 0.00 | 0.00 | 2692372.44 | 0.00 | 0.132449E+09 | 0.176821E+10 | 0.00 | 0.33 |
February | 0.243192E+10 | 0.00 | 0.00 | 6653142.23 | 0.00 | 26788640.66 | 0.326771E+10 | 0.00 | 0.48 |
March | 0.173353E+10 | 0.00 | 0.00 | 11921247.78 | 0.00 | 0.00 | 0.729539E+10 | 0.00 | 0.78 |
April | 0.130765E+10 | 7221232.01 | 0.00 | 14677040.86 | 0.00 | 0.00 | 0.842566E+10 | 0.00 | 1.14 |
May | 0.101232E+10 | 249237.54 | 0.00 | 15790558.26 | 0.00 | 0.00 | 0.798701E+10 | 0.00 | 1.25 |
June | 0.633918E+09 | 3577794.08 | 0.00 | 16934325.17 | 750370.88 | 0.00 | 0.738968E+10 | 0.00 | 1.42 |
July | 0.101159E+10 | 48003681.76 | 0.00 | 18883447.01 | 448453.05 | 0.00 | 0.618744E+10 | 0.00 | 1.58 |
August | 0.119919E+10 | 0.184915E+09 | 0.00 | 18644983.46 | 82497.40 | 0.00 | 0.542383E+10 | 0.00 | 1.58 |
September | 0.764946E+09 | 0.00 | 0.00 | 21240081.24 | 0.00 | 0.00 | 0.797529E+10 | 0.00 | 1.61 |
October | 0.133066E+10 | 0.00 | 0.00 | 14321153.22 | 0.00 | 0.00 | 0.829066E+10 | 0.00 | 1.08 |
November | 0.232674E+10 | 0.00 | 0.00 | 5623924.93 | 0.00 | 0.00 | 0.287328E+10 | 0.00 | 0.45 |
December | 0.284293E+10 | 0.00 | 0.00 | 4804071.95 | 0.00 | 28179340.90 | 0.244064E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.200156E+11 | 0.243967E+09 | 0.00 | 0.152186E+09 | 1281321.32 | 0.187417E+09 | 0.693248E+11 | 0.00 | 1.01 |
Minimum of Months | 0.633918E+09 | 0.00 | 0.00 | 2692372.44 | 0.00 | 0.00 | 0.176821E+10 | 0.00 | 0.33 |
Maximum of Months | 0.342018E+10 | 0.184915E+09 | 0.00 | 21240081.24 | 750370.88 | 0.132449E+09 | 0.842566E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178473E+10 | 0.00 | 0.00 | 1586207.65 | 0.00 | 0.00 | 0.132798E+10 | 0.00 | 0.30 |
February | 0.644246E+09 | 0.00 | 0.00 | 5033504.68 | 0.00 | 0.00 | 0.322480E+10 | 0.00 | 0.51 |
March | 0.154582E+09 | 0.00 | 0.00 | 11853642.34 | 0.00 | 0.00 | 0.727160E+10 | 0.00 | 1.00 |
April | 0.159831E+09 | 5142477.65 | 0.00 | 18321521.96 | 0.00 | 0.00 | 0.952356E+10 | 0.00 | 1.69 |
May | 0.189321E+09 | 140311.65 | 0.00 | 18683814.45 | 0.00 | 0.00 | 0.756147E+10 | 0.00 | 1.71 |
June | 0.129910E+09 | 8872256.41 | 0.00 | 20539709.41 | 342534.40 | 0.00 | 0.780999E+10 | 0.00 | 2.19 |
July | 0.292952E+09 | 57664077.68 | 0.00 | 25412358.52 | 37026.95 | 0.00 | 0.749262E+10 | 0.00 | 2.61 |
August | 0.275000E+09 | 0.175012E+09 | 0.00 | 25181451.38 | 79160.58 | 0.00 | 0.689633E+10 | 0.00 | 2.47 |
September | 0.161854E+09 | 0.00 | 0.00 | 15798411.48 | 0.00 | 0.00 | 0.599602E+10 | 0.00 | 1.69 |
October | 0.186213E+09 | 0.00 | 0.00 | 10267312.44 | 0.00 | 0.00 | 0.616662E+10 | 0.00 | 1.08 |
November | 0.152118E+09 | 0.00 | 0.00 | 7655299.84 | 0.00 | 0.00 | 0.476764E+10 | 0.00 | 0.65 |
December | 0.160657E+09 | 0.00 | 0.00 | 7628233.77 | 0.00 | 0.00 | 0.472520E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.429142E+10 | 0.246831E+09 | 0.00 | 0.167961E+09 | 458721.93 | 0.00 | 0.727638E+11 | 0.00 | 1.37 |
Minimum of Months | 0.129910E+09 | 0.00 | 0.00 | 1586207.65 | 0.00 | 0.00 | 0.132798E+10 | 0.00 | 0.30 |
Maximum of Months | 0.178473E+10 | 0.175012E+09 | 0.00 | 25412358.52 | 342534.40 | 0.00 | 0.952356E+10 | 0.00 | 2.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219605E+11 | 0.00 | 0.00 | 0.30 |
February | 0.283145E+11 | 0.00 | 0.00 | 613268.19 | 0.00 | 0.966948E+10 | 0.372979E+09 | 0.00 | 0.30 |
March | 0.340350E+11 | 0.00 | 0.00 | 3081676.35 | 0.00 | 0.192422E+10 | 0.291144E+10 | 0.00 | 0.31 |
April | 0.231697E+11 | 25894542.92 | 0.00 | 21428700.54 | 5024152.38 | 63823098.52 | 0.142577E+11 | 0.00 | 0.40 |
May | 0.152826E+11 | 1365253.24 | 0.00 | 58798606.20 | 0.00 | 0.00 | 0.339331E+11 | 0.00 | 0.66 |
June | 0.831859E+10 | 26119612.11 | 0.00 | 83691708.24 | 3316194.63 | 0.00 | 0.402818E+11 | 0.00 | 0.83 |
July | 0.757264E+10 | 0.225842E+09 | 0.00 | 88134011.73 | 4922141.27 | 0.00 | 0.322750E+11 | 0.00 | 0.85 |
August | 0.719147E+10 | 0.861350E+09 | 0.00 | 76670839.61 | 5588597.42 | 0.00 | 0.255894E+11 | 0.00 | 0.76 |
September | 0.162660E+11 | 0.00 | 0.00 | 45142015.50 | 0.00 | 0.00 | 0.207005E+11 | 0.00 | 0.60 |
October | 0.286450E+11 | 0.00 | 0.00 | 9242455.25 | 0.00 | 0.216852E+09 | 0.581878E+10 | 0.00 | 0.34 |
November | 0.332517E+11 | 0.00 | 0.00 | 25871.47 | 0.00 | 0.507935E+10 | 78670462.27 | 0.00 | 0.30 |
December | 0.265634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163847E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.251624E+12 | 0.114057E+10 | 0.00 | 0.386829E+09 | 18851085.70 | 0.552990E+11 | 0.176219E+12 | 0.00 | 0.50 |
Minimum of Months | 0.719147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.340350E+11 | 0.861350E+09 | 0.00 | 88134011.73 | 5588597.42 | 0.219605E+11 | 0.402818E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116737E+11 | 0.00 | 0.00 | 0.24 |
February | 0.140990E+11 | 0.00 | 0.00 | 3255952.87 | 0.00 | 0.460769E+10 | 0.208563E+10 | 0.00 | 0.26 |
March | 0.142790E+11 | 0.00 | 0.00 | 23540988.91 | 0.00 | 0.816801E+09 | 0.127112E+11 | 0.00 | 0.34 |
April | 0.831503E+10 | 29364581.77 | 0.00 | 57059060.12 | 0.00 | 54150182.01 | 0.318818E+11 | 0.00 | 0.68 |
May | 0.699455E+10 | 1402332.50 | 0.00 | 88840501.90 | 0.00 | 0.00 | 0.426192E+11 | 0.00 | 1.03 |
June | 0.367670E+10 | 19358781.47 | 0.00 | 0.126739E+09 | 2131861.64 | 0.00 | 0.545476E+11 | 0.00 | 1.47 |
July | 0.351386E+10 | 0.205327E+09 | 0.00 | 0.132008E+09 | 3164266.68 | 0.00 | 0.399962E+11 | 0.00 | 1.41 |
August | 0.285549E+10 | 0.787659E+09 | 0.00 | 0.125176E+09 | 403721.89 | 0.00 | 0.356966E+11 | 0.00 | 1.39 |
September | 0.701824E+10 | 0.00 | 0.00 | 78880928.61 | 0.00 | 0.00 | 0.326055E+11 | 0.00 | 1.02 |
October | 0.126218E+11 | 0.00 | 0.00 | 28514183.42 | 0.00 | 0.130777E+09 | 0.149398E+11 | 0.00 | 0.44 |
November | 0.163598E+11 | 0.00 | 0.00 | 1756804.64 | 0.00 | 0.289483E+10 | 0.117286E+10 | 0.00 | 0.25 |
December | 0.137998E+11 | 0.00 | 0.00 | 49701.39 | 0.00 | 0.871768E+10 | 43875374.71 | 0.00 | 0.23 |
Annual Sum or Average | 0.115343E+12 | 0.104311E+10 | 0.00 | 0.665821E+09 | 5699850.21 | 0.288956E+11 | 0.268300E+12 | 0.00 | 0.73 |
Minimum of Months | 0.285549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.163598E+11 | 0.787659E+09 | 0.00 | 0.132008E+09 | 3164266.68 | 0.116737E+11 | 0.545476E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274944E+11 | 0.00 | 0.00 | 18047590.80 | 0.00 | 0.115812E+11 | 0.142964E+11 | 0.00 | 0.35 |
February | 0.252824E+11 | 0.00 | 0.00 | 58306555.23 | 0.00 | 0.442492E+10 | 0.312509E+11 | 0.00 | 0.49 |
March | 0.230124E+11 | 0.00 | 0.00 | 98436517.26 | 0.00 | 0.525130E+09 | 0.506267E+11 | 0.00 | 0.62 |
April | 0.142418E+11 | 0.115264E+09 | 0.00 | 0.117570E+09 | 0.00 | 8129976.52 | 0.613251E+11 | 0.00 | 0.90 |
May | 0.121765E+11 | 2959763.74 | 0.00 | 0.144029E+09 | 0.00 | 0.00 | 0.681962E+11 | 0.00 | 1.14 |
June | 0.843890E+10 | 34512980.78 | 0.00 | 0.143074E+09 | 3307353.35 | 0.00 | 0.596584E+11 | 0.00 | 1.23 |
July | 0.758417E+10 | 0.468031E+09 | 0.00 | 0.155480E+09 | 4909018.39 | 0.00 | 0.489964E+11 | 0.00 | 1.33 |
August | 0.518416E+10 | 0.199101E+10 | 0.00 | 0.159873E+09 | 228903.52 | 0.00 | 0.437947E+11 | 0.00 | 1.29 |
September | 0.993367E+10 | 0.00 | 0.00 | 0.207274E+09 | 0.00 | 0.00 | 0.700841E+11 | 0.00 | 1.53 |
October | 0.174250E+11 | 0.00 | 0.00 | 0.126622E+09 | 0.00 | 3523533.58 | 0.578818E+11 | 0.00 | 0.84 |
November | 0.267500E+11 | 0.00 | 0.00 | 39127790.91 | 0.00 | 0.290318E+10 | 0.205659E+11 | 0.00 | 0.42 |
December | 0.263287E+11 | 0.00 | 0.00 | 31478606.40 | 0.00 | 0.993993E+10 | 0.213299E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.203852E+12 | 0.261178E+10 | 0.00 | 0.129932E+10 | 8445275.26 | 0.293860E+11 | 0.548007E+12 | 0.00 | 0.88 |
Minimum of Months | 0.518416E+10 | 0.00 | 0.00 | 18047590.80 | 0.00 | 0.00 | 0.142964E+11 | 0.00 | 0.35 |
Maximum of Months | 0.274944E+11 | 0.199101E+10 | 0.00 | 0.207274E+09 | 4909018.39 | 0.115812E+11 | 0.700841E+11 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198909E+11 | 0.00 | 0.00 | 443244.09 | 0.00 | 0.850015E+10 | 0.475592E+09 | 0.00 | 0.30 |
February | 0.187264E+11 | 0.00 | 0.00 | 7407400.37 | 0.00 | 0.342345E+10 | 0.448591E+10 | 0.00 | 0.33 |
March | 0.182923E+11 | 0.00 | 0.00 | 24068776.76 | 0.00 | 0.139611E+09 | 0.134313E+11 | 0.00 | 0.41 |
April | 0.961234E+10 | 59410459.34 | 0.00 | 58001523.73 | 0.00 | 2332096.54 | 0.305864E+11 | 0.00 | 0.75 |
May | 0.600361E+10 | 1266340.62 | 0.00 | 0.137813E+09 | 0.00 | 0.00 | 0.481247E+11 | 0.00 | 1.28 |
June | 0.364823E+10 | 84879336.58 | 0.00 | 0.126494E+09 | 2125423.76 | 0.00 | 0.446943E+11 | 0.00 | 1.45 |
July | 0.219998E+10 | 0.528294E+09 | 0.00 | 0.147115E+09 | 384439.52 | 0.00 | 0.420075E+11 | 0.00 | 1.70 |
August | 0.238282E+10 | 0.150850E+10 | 0.00 | 0.124632E+09 | 3581857.84 | 0.00 | 0.311678E+11 | 0.00 | 1.35 |
September | 0.575874E+10 | 0.00 | 0.00 | 0.102239E+09 | 0.00 | 0.00 | 0.348719E+11 | 0.00 | 1.21 |
October | 0.143434E+11 | 0.00 | 0.00 | 28644911.32 | 0.00 | 0.00 | 0.152031E+11 | 0.00 | 0.50 |
November | 0.211271E+11 | 0.00 | 0.00 | 3747505.24 | 0.00 | 0.156828E+10 | 0.264314E+10 | 0.00 | 0.32 |
December | 0.210718E+11 | 0.00 | 0.00 | 1495181.56 | 0.00 | 0.541548E+10 | 0.139161E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.143058E+12 | 0.218235E+10 | 0.00 | 0.762102E+09 | 6091721.12 | 0.190493E+11 | 0.269083E+12 | 0.00 | 0.83 |
Minimum of Months | 0.219998E+10 | 0.00 | 0.00 | 443244.09 | 0.00 | 0.00 | 0.475592E+09 | 0.00 | 0.29 |
Maximum of Months | 0.211271E+11 | 0.150850E+10 | 0.00 | 0.147115E+09 | 3581857.84 | 0.850015E+10 | 0.481247E+11 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312712E+10 | 0.00 | 0.00 | 0.30 |
February | 0.154292E+10 | 0.00 | 0.00 | 2051.05 | 0.00 | 0.205419E+10 | 17589814.88 | 0.00 | 0.31 |
March | 0.311194E+10 | 0.00 | 0.00 | 59558.31 | 0.00 | 0.753893E+09 | 57549447.72 | 0.00 | 0.34 |
April | 0.234060E+10 | 671898.56 | 0.00 | 1477632.29 | 104865.26 | 0.263178E+09 | 0.100471E+10 | 0.00 | 0.39 |
May | 0.174868E+10 | 0.00 | 0.00 | 4841163.81 | 0.00 | 19481302.19 | 0.292766E+10 | 0.00 | 0.62 |
June | 0.103048E+10 | 927858.11 | 0.00 | 7587097.80 | 175553.63 | 0.00 | 0.373815E+10 | 0.00 | 0.83 |
July | 0.824986E+09 | 10897075.03 | 0.00 | 8782997.24 | 278508.85 | 0.00 | 0.319974E+10 | 0.00 | 0.86 |
August | 0.825882E+09 | 53616972.01 | 0.00 | 7553173.72 | 1503583.39 | 0.00 | 0.232134E+10 | 0.00 | 0.75 |
September | 0.179579E+10 | 0.00 | 0.00 | 3486057.13 | 0.00 | 26578550.70 | 0.163821E+10 | 0.00 | 0.57 |
October | 0.268329E+10 | 0.00 | 0.00 | 346944.89 | 0.00 | 0.378232E+09 | 0.298588E+09 | 0.00 | 0.36 |
November | 0.193579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163314E+10 | 0.00 | 0.00 | 0.31 |
December | 0.110191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283743E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.199819E+11 | 66113803.71 | 0.00 | 34136676.24 | 2062511.12 | 0.110933E+11 | 0.152035E+11 | 0.00 | 0.50 |
Minimum of Months | 0.824986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.311194E+10 | 53616972.01 | 0.00 | 8782997.24 | 1503583.39 | 0.312712E+10 | 0.373815E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.879215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181801E+10 | 0.00 | 0.00 | 0.31 |
February | 0.117887E+10 | 0.00 | 0.00 | 55920.68 | 0.00 | 0.108735E+10 | 65910004.46 | 0.00 | 0.32 |
March | 0.165298E+10 | 0.00 | 0.00 | 1366499.63 | 0.00 | 0.326060E+09 | 0.943897E+09 | 0.00 | 0.39 |
April | 0.101176E+10 | 749719.93 | 0.00 | 4831347.98 | 0.00 | 97531696.79 | 0.292038E+10 | 0.00 | 0.70 |
May | 0.793317E+09 | 0.00 | 0.00 | 8407165.55 | 0.00 | 12547492.38 | 0.424664E+10 | 0.00 | 1.04 |
June | 0.395589E+09 | 701083.49 | 0.00 | 12418088.31 | 113237.78 | 0.00 | 0.565723E+10 | 0.00 | 1.53 |
July | 0.366970E+09 | 9784564.80 | 0.00 | 13314024.11 | 65800.56 | 0.00 | 0.424212E+10 | 0.00 | 1.49 |
August | 0.305549E+09 | 50553480.85 | 0.00 | 13424125.86 | 147783.11 | 0.00 | 0.360742E+10 | 0.00 | 1.46 |
September | 0.832759E+09 | 0.00 | 0.00 | 7344863.82 | 0.00 | 9169613.23 | 0.311740E+10 | 0.00 | 1.04 |
October | 0.130851E+10 | 0.00 | 0.00 | 2084864.17 | 0.00 | 0.202338E+09 | 0.129051E+10 | 0.00 | 0.47 |
November | 0.133693E+10 | 0.00 | 0.00 | 36484.39 | 0.00 | 0.934018E+09 | 37776079.21 | 0.00 | 0.31 |
December | 0.899093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166201E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.109615E+11 | 61788849.06 | 0.00 | 63283384.49 | 326821.44 | 0.614905E+10 | 0.261293E+11 | 0.00 | 0.78 |
Minimum of Months | 0.305549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.165298E+10 | 50553480.85 | 0.00 | 13424125.86 | 147783.11 | 0.181801E+10 | 0.565723E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175470E+10 | 0.00 | 0.00 | 967791.79 | 0.00 | 0.201750E+10 | 0.790979E+09 | 0.00 | 0.33 |
February | 0.178988E+10 | 0.00 | 0.00 | 3954103.38 | 0.00 | 0.109457E+10 | 0.259475E+10 | 0.00 | 0.49 |
March | 0.211709E+10 | 0.00 | 0.00 | 7626163.19 | 0.00 | 0.458008E+09 | 0.515994E+10 | 0.00 | 0.68 |
April | 0.144676E+10 | 2686263.64 | 0.00 | 10154808.70 | 0.00 | 0.196365E+09 | 0.589672E+10 | 0.00 | 0.90 |
May | 0.132641E+10 | 0.00 | 0.00 | 13241039.44 | 0.00 | 17688549.87 | 0.666129E+10 | 0.00 | 1.10 |
June | 0.917978E+09 | 1253642.17 | 0.00 | 13573821.98 | 176086.45 | 0.00 | 0.604640E+10 | 0.00 | 1.23 |
July | 0.748852E+09 | 22254785.48 | 0.00 | 17053319.41 | 62289.54 | 0.00 | 0.525861E+10 | 0.00 | 1.36 |
August | 0.639188E+09 | 0.124221E+09 | 0.00 | 17400116.02 | 39734.96 | 0.00 | 0.435081E+10 | 0.00 | 1.33 |
September | 0.112548E+10 | 0.00 | 0.00 | 19610173.21 | 0.00 | 8642106.62 | 0.692959E+10 | 0.00 | 1.52 |
October | 0.168500E+10 | 0.00 | 0.00 | 10026458.17 | 0.00 | 0.220209E+09 | 0.591776E+10 | 0.00 | 0.90 |
November | 0.208694E+10 | 0.00 | 0.00 | 2262543.85 | 0.00 | 0.104536E+10 | 0.117740E+10 | 0.00 | 0.41 |
December | 0.166081E+10 | 0.00 | 0.00 | 1810650.39 | 0.00 | 0.179117E+10 | 0.132739E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.172991E+11 | 0.150416E+09 | 0.00 | 0.117681E+09 | 278110.95 | 0.684951E+10 | 0.521117E+11 | 0.00 | 0.89 |
Minimum of Months | 0.639188E+09 | 0.00 | 0.00 | 967791.79 | 0.00 | 0.00 | 0.790979E+09 | 0.00 | 0.33 |
Maximum of Months | 0.211709E+10 | 0.124221E+09 | 0.00 | 19610173.21 | 176086.45 | 0.201750E+10 | 0.692959E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114041E+10 | 0.00 | 0.00 | 18466.80 | 0.00 | 0.147060E+10 | 21342540.01 | 0.00 | 0.30 |
February | 0.131498E+10 | 0.00 | 0.00 | 483172.51 | 0.00 | 0.758429E+09 | 0.389842E+09 | 0.00 | 0.34 |
March | 0.169586E+10 | 0.00 | 0.00 | 1777061.20 | 0.00 | 0.259583E+09 | 0.135439E+10 | 0.00 | 0.45 |
April | 0.109151E+10 | 1466113.67 | 0.00 | 4975811.21 | 0.00 | 76342998.22 | 0.284158E+10 | 0.00 | 0.76 |
May | 0.721045E+09 | 0.00 | 0.00 | 12631299.28 | 0.00 | 9558230.12 | 0.469283E+10 | 0.00 | 1.24 |
June | 0.436327E+09 | 2883472.68 | 0.00 | 12040372.41 | 112686.98 | 0.00 | 0.448915E+10 | 0.00 | 1.48 |
July | 0.292635E+09 | 25247734.14 | 0.00 | 16408515.53 | 9109.92 | 0.00 | 0.436425E+10 | 0.00 | 1.75 |
August | 0.262662E+09 | 91651711.32 | 0.00 | 13563432.19 | 347216.14 | 0.00 | 0.306490E+10 | 0.00 | 1.35 |
September | 0.732109E+09 | 0.00 | 0.00 | 9467310.73 | 0.00 | 0.00 | 0.325442E+10 | 0.00 | 1.19 |
October | 0.144763E+10 | 0.00 | 0.00 | 2132027.29 | 0.00 | 0.115038E+09 | 0.140481E+10 | 0.00 | 0.53 |
November | 0.156508E+10 | 0.00 | 0.00 | 200159.97 | 0.00 | 0.623574E+09 | 0.125134E+09 | 0.00 | 0.32 |
December | 0.119989E+10 | 0.00 | 0.00 | 47424.84 | 0.00 | 0.123285E+10 | 52601219.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.119001E+11 | 0.121249E+09 | 0.00 | 73745053.94 | 469013.04 | 0.454597E+10 | 0.260553E+11 | 0.00 | 0.84 |
Minimum of Months | 0.262662E+09 | 0.00 | 0.00 | 18466.80 | 0.00 | 0.00 | 21342540.01 | 0.00 | 0.29 |
Maximum of Months | 0.169586E+10 | 91651711.32 | 0.00 | 16408515.53 | 347216.14 | 0.147060E+10 | 0.469283E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3146798.52 | 0.00 | 0.00 | 0.620796E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7563202.36 | 0.00 | 0.00 | 0.513916E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14855647.36 | 0.00 | 0.00 | 0.540741E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18456483.94 | 0.00 | 0.00 | 0.419651E+09 | 0.00 | 0.29 |
May | 0.00 | 16066.02 | 0.00 | 4424817.98 | 0.00 | 0.00 | 0.379263E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 9599604.23 | 0.00 | 0.00 | 0.294543E+09 | 0.00 | 0.30 |
July | 0.00 | 4137326.26 | 0.00 | 12759101.12 | 0.00 | 0.00 | 0.166720E+09 | 0.00 | 0.28 |
August | 0.00 | 13418243.98 | 0.00 | 16495542.44 | 0.00 | 0.00 | 0.124580E+09 | 0.00 | 0.31 |
September | 0.00 | 90351.96 | 0.00 | 4263706.95 | 0.00 | 0.00 | 0.255518E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8889775.63 | 0.00 | 0.00 | 0.424703E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12580225.63 | 0.00 | 0.00 | 0.494765E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17541980.61 | 0.00 | 0.00 | 0.575315E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 17661988.22 | 0.00 | 0.130577E+09 | 0.00 | 0.00 | 0.481051E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3146798.52 | 0.00 | 0.00 | 0.124580E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 13418243.98 | 0.00 | 18456483.94 | 0.00 | 0.00 | 0.620796E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384142E+09 | 0.00 | 0.00 | 12471059.83 | 0.00 | 0.00 | 0.584339E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 59864001.02 | 0.00 | 0.00 | 0.515693E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.132470E+09 | 0.00 | 0.00 | 0.542239E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.171433E+09 | 0.00 | 0.00 | 0.420798E+10 | 0.00 | 0.29 |
May | 0.00 | 139816.42 | 0.00 | 38393036.33 | 0.00 | 0.00 | 0.380344E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 88978246.16 | 0.00 | 0.00 | 0.295352E+10 | 0.00 | 0.30 |
July | 0.00 | 40986577.91 | 0.00 | 0.120569E+09 | 0.00 | 0.00 | 0.167477E+10 | 0.00 | 0.28 |
August | 0.00 | 0.133522E+09 | 0.00 | 0.156839E+09 | 0.00 | 0.00 | 0.125420E+10 | 0.00 | 0.31 |
September | 0.00 | 784376.71 | 0.00 | 37133014.12 | 0.00 | 0.00 | 0.257759E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 77257613.93 | 0.00 | 0.00 | 0.425943E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.108083E+09 | 0.00 | 0.00 | 0.496486E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.151356E+09 | 0.00 | 0.00 | 0.577702E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.384142E+09 | 0.175432E+09 | 0.00 | 0.115485E+10 | 0.00 | 0.00 | 0.478955E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 12471059.83 | 0.00 | 0.00 | 0.125420E+10 | 0.00 | 0.28 |
Maximum of Months | 0.384142E+09 | 0.133522E+09 | 0.00 | 0.171433E+09 | 0.00 | 0.00 | 0.584339E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271056E+09 | 0.00 | 0.00 | 469331.64 | 0.00 | 0.00 | 0.344084E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4943294.90 | 0.00 | 0.00 | 0.516868E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12208336.22 | 0.00 | 0.00 | 0.543359E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16586750.59 | 0.00 | 0.00 | 0.421413E+09 | 0.00 | 0.29 |
May | 0.00 | 14200.62 | 0.00 | 3510186.00 | 0.00 | 0.00 | 0.380920E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8753723.07 | 0.00 | 0.00 | 0.295566E+09 | 0.00 | 0.30 |
July | 0.00 | 4118655.76 | 0.00 | 11988459.01 | 0.00 | 0.00 | 0.167553E+09 | 0.00 | 0.28 |
August | 0.00 | 13390133.68 | 0.00 | 15572510.60 | 0.00 | 0.00 | 0.125563E+09 | 0.00 | 0.31 |
September | 0.00 | 76947.60 | 0.00 | 3344829.76 | 0.00 | 0.00 | 0.259315E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6857412.52 | 0.00 | 0.00 | 0.427212E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9640132.54 | 0.00 | 0.00 | 0.497886E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13844929.30 | 0.00 | 0.00 | 0.579014E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.271056E+09 | 17599937.66 | 0.00 | 0.107720E+09 | 0.00 | 0.00 | 0.455875E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 469331.64 | 0.00 | 0.00 | 0.125563E+09 | 0.00 | 0.28 |
Maximum of Months | 0.271056E+09 | 13390133.68 | 0.00 | 16586750.59 | 0.00 | 0.00 | 0.579014E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.516241E+09 | 0.00 | 0.00 | 0.435954E+12 | 0.00 | 9.49 |
February | 0.00 | 0.00 | 0.00 | 0.940057E+09 | 0.00 | 0.00 | 0.660668E+12 | 0.00 | 17.79 |
March | 0.00 | 0.00 | 0.00 | 0.149114E+10 | 0.00 | 0.00 | 0.100776E+13 | 0.00 | 27.91 |
April | 0.00 | 31793.33 | 0.00 | 0.215506E+10 | 0.00 | 0.00 | 0.112828E+13 | 0.00 | 39.30 |
May | 0.00 | 0.00 | 0.00 | 0.565765E+09 | 0.00 | 0.00 | 0.383739E+12 | 0.00 | 17.17 |
June | 0.00 | 0.00 | 0.00 | 0.111310E+10 | 0.00 | 0.00 | 0.566800E+12 | 0.00 | 32.62 |
July | 0.00 | 0.829135E+09 | 0.00 | 0.191613E+10 | 0.00 | 0.00 | 0.656494E+12 | 0.00 | 42.98 |
August | 0.00 | 0.324523E+10 | 0.00 | 0.247123E+10 | 0.00 | 0.00 | 0.557292E+12 | 0.00 | 44.90 |
September | 0.00 | 0.00 | 0.00 | 0.534212E+09 | 0.00 | 0.00 | 0.340476E+12 | 0.00 | 19.87 |
October | 0.00 | 0.00 | 0.00 | 0.101811E+10 | 0.00 | 0.00 | 0.647826E+12 | 0.00 | 24.00 |
November | 0.00 | 0.00 | 0.00 | 0.144295E+10 | 0.00 | 0.00 | 0.922488E+12 | 0.00 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.204673E+10 | 0.00 | 0.00 | 0.129141E+13 | 0.00 | 30.70 |
Annual Sum or Average | 0.00 | 0.407439E+10 | 0.00 | 0.162107E+11 | 0.00 | 0.00 | 0.859919E+13 | 0.00 | 27.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.516241E+09 | 0.00 | 0.00 | 0.340476E+12 | 0.00 | 9.49 |
Maximum of Months | 0.00 | 0.324523E+10 | 0.00 | 0.247123E+10 | 0.00 | 0.00 | 0.129141E+13 | 0.00 | 44.90 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.115340E+12 | 0.108353E+11 | 0.00 | 0.202033E+13 | 0.127683E+12 |
February | 0.226653E+12 | 0.991251E+10 | 0.00 | 0.226152E+13 | 0.197824E+12 |
March | 0.415773E+12 | 0.948432E+10 | 0.00 | 0.291382E+13 | 0.339799E+12 |
April | 0.643571E+12 | 0.914229E+10 | 0.00 | 0.309877E+13 | 0.557891E+12 |
May | 0.847280E+12 | 0.725817E+10 | 0.00 | 0.242974E+13 | 0.333246E+12 |
June | 0.860686E+12 | 0.595290E+10 | 0.00 | 0.242791E+13 | 0.650953E+12 |
July | 0.904766E+12 | 0.521831E+10 | 0.00 | 0.249735E+13 | 0.128579E+13 |
August | 0.709500E+12 | 0.411813E+10 | 0.00 | 0.209798E+13 | 0.202803E+13 |
September | 0.492460E+12 | 0.346400E+10 | 0.00 | 0.234077E+13 | 0.472040E+12 |
October | 0.313081E+12 | 0.770494E+10 | 0.00 | 0.265269E+13 | 0.279869E+12 |
November | 0.133241E+12 | 0.881619E+10 | 0.00 | 0.278887E+13 | 0.272174E+12 |
December | 0.853733E+11 | 0.933099E+10 | 0.00 | 0.302507E+13 | 0.361714E+12 |
Annual Sum or Average | 0.574772E+13 | 0.912380E+11 | 0.00 | 0.305548E+14 | 0.690701E+13 |
Minimum of Months | 0.853733E+11 | 0.346400E+10 | 0.00 | 0.202033E+13 | 0.127683E+12 |
Maximum of Months | 0.904766E+12 | 0.108353E+11 | 0.00 | 0.309877E+13 | 0.202803E+13 |