Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2024-07-03 12:21:42


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 26509.71 572.31 572.31
Net Site Energy 26509.71 572.31 572.31
Total Source Energy 81640.16 1762.51 1762.51
Net Source Energy 81640.16 1762.51 1762.51


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1111.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 951.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2470.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 356.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2566.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2311.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 289.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 293.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1893.49
Humidification 1043.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 388.36
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 438.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 25397.81 1111.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4562.02
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1111.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 951.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2470.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 356.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 2505.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2311.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 289.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 293.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1893.49
Humidification General 1043.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 388.36
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 438.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1111.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 951.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2470.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 356.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 2566.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2311.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 289.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 293.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1893.49
Humidification Unassigned 1043.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 388.36
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 438.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 61.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 115.03 24.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10
Other 372.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 548.31 24.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 61.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 115.03 24.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10
Other 372.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 548.31 24.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.10


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 25397.807 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 25397.807 100.00
     
Total On-Site and Utility Electric Sources 25397.807 100.00
Total Electricity End Uses 25397.807 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 4562.02 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 4562.02 100.00
Total Water End Uses 4562.02 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 15.50
Time Setpoint Not Met During Occupied Cooling 503.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 6.5999 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 6.5999 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.5999 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.5999 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 6.5999 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.5999 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.5999 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.5999 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 9.7790 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 9.7790 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 9.7790 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 6.5999 18.58 484.4232  
Total 46320.38             6.6297 9.29 17.8789  
Conditioned Total 46320.38             6.6297 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.0382 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-AUG-15:20 02-JAN-06:10 - - - - - - - - - - 10-AUG-15:00
Heating 0.00 1281357.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 404381.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 233266.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 270536.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37784.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 72883.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34477.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2044516.27 1281357.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1281357.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 404381.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3394.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 270536.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 37784.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 72883.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 34477.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1205.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3013.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7824.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1128.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 8127.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7321.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 915.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 929.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 3306.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1388.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 80434.86 1205.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 65.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 175.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 158.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 19.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 20.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 71.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 29.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1736.49 26.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 65.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 175.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 158.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 19.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 20.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 71.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 29.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1736.49 26.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

AirTerminal:SingleDuct:VAV:NoReheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s]
BASEMENT PSZ-VAV DIFFUSER 5.11 0.414630 0.000000 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.46 0.348208 0.296000 1.62 0.928554 0.500000 0.001094 0.000140 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 51.13 0.372000 0.316000 16.16 0.992000 0.500000 0.001024 0.003169 16.16 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 4.93 0.385856 0.328000 1.62 1.00 0.500000 0.000987 0.000623 2.15 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.832604 0.286836 0.244000 0.203155 0.764896 0.500000 0.001328 0.000069 0.237946 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.27 0.120730 0.103000 0.131303 0.321947 0.500000 0.003156 0.000050 0.173147 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.77 0.134909 0.115000 0.203581 0.359758 0.500000 0.002824 0.000090 0.309089 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.53 0.100337 0.085000 0.130380 0.300000 0.500000 0.003797 0.000032 0.130380 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 7.59 0.314773 0.268000 2.03 0.839394 0.500000 0.001210 0.001550 5.36 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 13.34       0.307694 0.500000 0.003302 0.001030 3.56 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 18.27 0.130724 0.111000 2.03 0.348597 0.500000 0.002915 0.001536 5.31 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 14.01 0.109830 0.093000 1.30 0.300000 0.500000 0.003469 0.000948 3.28 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.853916 0.279677 0.238000 0.203232 0.745805 0.500000 0.001362 0.000200 0.692859 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.32 0.116229 0.099000 0.131091 0.309944 0.500000 0.003278 0.000132 0.457280 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.92 0.124188 0.106000 0.203849 0.331167 0.500000 0.003068 0.000199 0.687735 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.47 0.104999 0.089000 0.130454 0.300000 0.500000 0.003629 0.000125 0.433721 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K] User-Specified Rated Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 16047.69 0.000140 323.51  
CORE_MID VAV BOX REHEAT COIL 362266.50 0.003169 8349.49  
CORE_TOP VAV BOX REHEAT COIL 71160.21 0.000623 1879.60  
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 7892.99 0.000069 208.52  
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5739.65 0.000050 151.58  
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 10238.83 0.000090 270.32  
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3636.93 0.000032 89.59  
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 177162.05 0.001550 4673.42  
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 117682.54 0.001030 3104.28  
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 175606.35 0.001536 4632.43  
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 108313.60 0.000948 2857.39  
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 22897.36 0.000200 603.86  
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 15111.30 0.000132 398.51  
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 22728.36 0.000199 599.41  
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 14334.07 0.000125 378.03  
VAV_BOT WITH REHEAT HEATING COIL 44204.58 0.000387 737.81  
VAV_MID WITH REHEAT HEATING COIL 375848.69 0.003288 6313.17  
VAV_TOP WITH REHEAT HEATING COIL 36741.74 0.000321 623.41  
CAV_BAS HEATING COIL 249715.87 0.000875 2622.59 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DATACENTER_BOT_ZN_6 DIRECT AIR 0.504237
DATACENTER_MID_ZN_6 DIRECT AIR 4.84
DATACENTER_TOP_ZN_6 DIRECT AIR 0.491439
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 24.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.44 2.29 10.87 2.29 9.02 9.02 0.300000 0.253451 9.02
VAV_MID WITH REHEAT 52.17 22.83 104.34 28.28 83.07 83.07 0.300000 0.340451 83.07
VAV_TOP WITH REHEAT 5.25 2.29 10.50 4.42 9.31 9.31 0.300000 0.474383 9.31
CAV_BAS 0.000000 0.000000 5.11 1.20 5.11 5.11 1.00 0.234957 5.11
AIRLOOP DATACENTER BASEMENT 24.80 24.80 24.80 24.80 24.80 24.80 1.00 0.999996 24.80
AIRLOOP DATACENTER BOT 0.504237 0.504237 0.504237 0.504237 0.504237 0.504237 1.00 1.00 0.504237
AIRLOOP DATACENTER MID 4.84 4.84 4.84 4.84 4.84 4.84 1.00 1.00 4.84
AIRLOOP DATACENTER TOP 0.491439 0.491439 0.491439 0.491439 0.491439 0.491439 1.00 1.00 0.491439
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.02  
VAV_MID WITH REHEAT_OA_CONTROLLER 83.07  
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.31  
CAV_BAS_OA_CONTROLLER 5.11 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 24.80 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.504237 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.84 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.491439 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 25.22 6.67 11.02 0.008845 0.008500 164488.21 0.004704 9.02
VAV_MID WITH REHEAT COOLING COIL 25.33 6.67 11.02 0.008869 0.008500 1533301.03 0.043852 83.07
VAV_TOP WITH REHEAT COOLING COIL 25.18 6.67 11.02 0.008837 0.008500 169230.09 0.004840 9.31
CAV_BAS COOLING COIL 25.29 6.67 11.01 0.008989 0.008500 95943.47 0.002744 5.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.02
VAV_MID WITH REHEAT FAN 83.07
VAV_TOP WITH REHEAT FAN 9.31
CAV_BAS FAN 5.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.004704 0.000101
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000387  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.043852 0.000011
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.003288  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.004840 0.000098
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000321  
CAV_BAS_COOLC_CONTROLLER 0.002744 0.000174
CAV_BAS_HEATC_CONTROLLER 0.000875  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 24.80 490344.31 351281.93 0.012009
AIRLOOP DATACENTER BOT COOLING COIL 0.504237 9744.96 7061.29 0.000239
AIRLOOP DATACENTER MID COOLING COIL 4.84 93616.61 67819.88 0.002293
AIRLOOP DATACENTER TOP COOLING COIL 0.491439 9503.89 6884.14 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 24.80 24.80 24.80 24.80 490344.31 490344.31 17840.03 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.504237 0.504237 0.504237 0.504237 9744.96 9744.96 824.14 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.84 4.84 4.84 4.84 93616.61 93616.61 8241.36 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.491439 0.491439 0.491439 0.491439 9503.89 9503.89 824.14 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 24.80
AIRLOOP DATACENTER BOT SUPPLY FAN 0.504237
AIRLOOP DATACENTER MID SUPPLY FAN 4.84
AIRLOOP DATACENTER TOP SUPPLY FAN 0.491439
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 24.80 490344.31 0.012009
AIRLOOP DATACENTER BOT HEATING COIL 0.504237 9744.96 0.000239
AIRLOOP DATACENTER MID HEATING COIL 4.84 93616.61 0.002293
AIRLOOP DATACENTER TOP HEATING COIL 0.491439 9503.89 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 17840.03
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 824.14
AIRLOOP DATACENTER MID_SUPPHEATCOIL 8241.36
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 824.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000165 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.056140 9075.27  
HEATSYS1 PUMP 0.014764 4402.24 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.056140 6.74
HEATSYS1 0.014764 1.77
COOLSYS1_SUPPLY 0.056140 6.74
SINGLE WATER PLANT LOOP 0.014773 1.77
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.056140 0.056140 235649.79 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1687613.43 1687613.43 0.014764
CENTRAL BOILER 608503.17 596268.42 0.014773
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.028070 3141.56
COOLSYS1 CHILLER2 PUMP 0.028070 3141.56
PLANT CIRC PUMP 0.014773 3730.44
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.056140 0.028388 992588.32 992587.72 0.051017
COOLSYS1 CHILLER2 0.056140 0.028388 992588.32 992587.72 0.051017
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] U-factor Times Area Value at High Fan Speed [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/K]
CENTRAL TOWER 0.014773 146680.64 74254.09 73340.32 7004.20 44552.45
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.102034 12.24
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.102034 25011.29
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 38.86 1189621.49 7.77 148702.69
TOWERWATERSYS COOLTOWER 2 38.86 1189621.49 7.77 148702.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.051472
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 6.600 4.842 0.000 0.000 0.000 0.000 11.442 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 6.600 484.423 0.000 0.000 0.000 0.000 491.023 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 18343.827 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18343.827
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5172.174 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5172.174
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.075 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.028 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.266 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7632
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8055
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6228
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 -0.34463022E-15 0.36894385E-16 -0.14288780E-09 0.12757077E-17
51 8 0.20913840E-07 0.14359092E-12 0.36762620E-03 -0.23779757E-09
52 7 -0.11937955E-01 0.75343451E-08 -0.22648608E-01 0.13573889E-03
53 6 0.39710065 0.26364580E-05 0.46505929 -0.46505182E-02
54 5 -5.1100523 0.98937734E-04 -4.3872286 0.62185548E-01
55 4 32.646709 0.81302423E-03 21.229086 -0.41739428
56 3 -110.46842 0.17791168E-02 -55.206350 1.5042464
57 2 196.38009 0.10043743E-02 77.491871 -2.8887901
58 1 -170.88709 0.10757908E-03 -55.143519 2.7407251
59 0 57.057407 0.61468164E-06 15.577169  
60 9 -0.22955380E-15 0.37743381E-16 -0.14509256E-09 0.32676096E-18
61 8 0.21224167E-07 0.13772622E-12 0.37092755E-03 -0.24132609E-09
62 7 -0.12036605E-01 0.72012381E-08 -0.22790691E-01 0.13686058E-03
63 6 0.39978134 0.25163753E-05 0.46734577 -0.46821170E-02
64 5 -5.1362151 0.94318005E-04 -4.4048053 0.62509952E-01
65 4 32.762449 0.77422319E-03 21.297824 -0.41893096
66 3 -110.71472 0.16925811E-02 -55.342260 1.5078047
67 2 196.62425 0.95470525E-03 77.616458 -2.8926672
68 1 -170.97729 0.10217823E-03 -55.179630 2.7423060
69 0 57.057407 0.58332056E-06 15.571109  
70 9 0.11276195E-14 0.47405760E-16 -0.13382366E-09 -0.64614724E-17
71 8 0.19634610E-07 0.16705312E-12 0.35383761E-03 -0.22325229E-09
72 7 -0.11525316E-01 0.88979655E-08 -0.22054087E-01 0.13104703E-03
73 6 0.38588679 0.31323747E-05 0.45547913 -0.45183345E-02
74 5 -5.0005974 0.11815564E-03 -4.3135163 0.60828376E-01
75 4 32.162433 0.97545471E-03 20.940665 -0.41096462
76 3 -109.43770 0.21433374E-02 -54.636007 1.4893559
77 2 195.35810 0.12144036E-02 76.969321 -2.8725616
78 1 -170.50942 0.13051365E-03 -54.992579 2.7341060
79 0 57.057407 0.74839837E-06 15.602923  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.363_SHGC_EAST_0.359 35 1 VerySmooth 2.062 2.062 1.000 0.360    
2 WINDOW_U_0.363_SHGC_SOUTH_0.359 36 1 VerySmooth 2.062 2.062 1.000 0.360    
3 WINDOW_U_0.363_SHGC_WEST_0.359 37 1 VerySmooth 2.062 2.062 1.000 0.360    
4 WINDOW_U_0.363_SHGC_NORTH_0.359 38 1 VerySmooth 2.062 2.062 1.000 0.360    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 13.342 0.7435


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 5.142E-002 1.641E-004 2.467E-004 0.215 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 3.428E-002 1.697E-004 2.490E-004 0.223 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 5.142E-002 1.641E-004 2.467E-004 0.215 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 3.428E-002 1.697E-004 2.490E-004 0.223 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 7.615E-002 2.137E-005 2.563E-004 6.311E-002 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 7.615E-002 2.137E-005 2.563E-004 6.311E-002 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 7.615E-002 2.137E-005 1.973E-005 6.311E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000
2 Zone DATACENTER_BASEMENT_ZN_6 1.1500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000
2 Zone DATACENTER_BASEMENT_ZN_6 1.1500


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.1581E-003
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.1604E-003
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.0740E-003
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.0760E-003
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4338E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4353E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.4917E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.4924E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.2102E-003
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3666E-003
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1190E-003
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2595E-003
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4714E-003
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5818E-003
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.5122E-003
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.5645E-003
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1656
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.4328E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1907
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1105
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1057
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4306E-002
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5025E-002
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.5661E-002
25 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.2131E-003
26 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.3810E-003
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1221E-003
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2747E-003
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4737E-003
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5906E-003
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.5127E-003
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.5660E-003
33 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.1578E-003
34 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.1602E-003
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.0737E-003
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.0758E-003
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4336E-003
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4352E-003
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.4916E-003
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.4923E-003
41 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8123E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.2136E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.5904E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.0559E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.0969E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.2306E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2602E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2962E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.4527E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.2086E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.0695E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9501E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1274E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5728E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.6880E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7537E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.6597E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.7745E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.3865E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.4705E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.0538E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.0850E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2603E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2968E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7919E-003
66 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7941E-003
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.3600E-003
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3618E-003
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0538E-003
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0551E-003
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4917E-003
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4925E-003
73 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8407E-003
74 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9685E-003
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4004E-003
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5030E-003
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0861E-003
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1585E-003
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5127E-003
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5660E-003
81 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6691E-002
82 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4699E-002
83 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.5878E-002
84 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8765E-002
85 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1795E-002
86 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2296E-002
87 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5025E-002
88 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5656E-002
89 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8394E-003
90 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9661E-003
91 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.3990E-003
92 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4998E-003
93 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0842E-003
94 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1529E-003
95 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5122E-003
96 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5645E-003
97 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7918E-003
98 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7939E-003
99 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.3599E-003
100 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3617E-003
101 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0537E-003
102 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0549E-003
103 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4916E-003
104 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4923E-003
105 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.4935E-003
106 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.6096E-003
107 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.1706E-003
108 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.2553E-003
109 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9426E-003
110 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.9730E-003
111 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.2604E-003
112 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.2969E-003
113 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.1654E-002
114 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0876E-002
115 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6984E-002
116 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7932E-002
117 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9224E-002
118 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4878E-002
119 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.6880E-002
120 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.7537E-002
121 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6324E-003
122 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.9942E-003
123 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3565E-003
124 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.7699E-003
125 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9846E-003
126 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.1141E-003
127 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.2601E-003
128 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.2961E-003
129 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1623
130 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1238
131 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1806
132 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1426
133 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1183
134 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.4902E-002
135 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.5140E-002
136 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.7277E-002
137 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.6832E-002
138 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.6077E-002
139 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.2581E-002
140 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.3012E-002
141 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.2604E-002
142 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.7796E-002
143 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.6552E-002
144 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7590E-002
145 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.7396E-002
146 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.8170E-002
147 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.5184E-002
148 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0086E-002
149 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.0755E-002
150 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.1989E-002
151 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.5140E-002
152 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.7273E-002
153 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.3573E-002
154 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.4395E-002
155 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.8368E-002
156 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.0827E-002
157 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 7.0308E-002
158 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6676E-002
159 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.6552E-002
160 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.7590E-002
161 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1623
162 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1240
163 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1806
164 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1428
165 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1185
166 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.5053E-002
167 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.5258E-002
168 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.7338E-002
169 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.6874E-002
170 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.6146E-002
171 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.2629E-002
172 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.3078E-002
173 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.2712E-002
174 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.7876E-002
175 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.6670E-002
176 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7650E-002
177 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.7399E-002
178 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.8215E-002
179 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.5191E-002
180 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0121E-002
181 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.0821E-002
182 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.2031E-002
183 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.5258E-002
184 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.7333E-002
185 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.3611E-002
186 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.4460E-002
187 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.8411E-002
188 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.0889E-002
189 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 7.0413E-002
190 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6752E-002
191 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.6670E-002
192 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.7650E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 69959.15132 69959.15132 5.10799 5.10799 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:10:00 -4.20000 2.69032E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 74812.31154 74812.31154 5.46238 5.46238 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 -4.20000 2.69032E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 700486.03664 700486.03664 51.13022 51.13022 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 201903.72968 201903.72968 8.61196 10.77825 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 67540.44936 67540.44936 4.92942 4.92942 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 49861.21837 49861.21837 2.14595 2.14595 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 11296.19481 11296.19481 0.83260 0.83260 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 29.40000 8.82150E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 5534.73902 5534.73902 0.23795 0.23795 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 17295.60073 17295.60073 1.27479 1.27479 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:40:00 23.02133 8.81136E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 4023.28003 4023.28003 0.17315 0.17315 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 24017.99423 24017.99423 1.77027 1.77027 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 28.96667 8.82080E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 7174.02643 7174.02643 0.30909 0.30909 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 20810.86180 20810.86180 1.53388 1.53388 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 2346.11647 2346.11647 0.10041 0.10041 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 102936.16332 102936.16332 7.58708 7.58708 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 29.40000 8.82150E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 124023.18076 124023.18076 5.35779 5.35779 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 180967.59270 180967.59270 13.33835 13.33835 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 23.68000 8.81240E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 82381.19796 82381.19796 3.55927 3.55927 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 247870.41363 247870.41363 18.26951 18.26951 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 122935.78115 122935.78115 5.31063 5.31063 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 190121.18272 190121.18272 14.01303 14.01303 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 27.77067 8.81889E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 75832.27457 75832.27457 3.27528 3.27528 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 11585.34840 11585.34840 0.85392 0.85392 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 16025.02230 16025.02230 0.69286 0.69286 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 17965.38946 17965.38946 1.32415 1.32415 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 23.68000 8.81240E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 10575.64507 10575.64507 0.45728 0.45728 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 26091.56820 26091.56820 1.92310 1.92310 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 15906.87550 15906.87550 0.68774 0.68774 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 19886.79722 19886.79722 1.46577 1.46577 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 27.77067 8.81889E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 10032.25166 10032.25166 0.43372 0.43372 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8673.55330 8673.55330 0.50424 0.50424 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 25.60400 8.81543E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -4.20000 2.69032E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 83289.58467 83289.58467 4.84207 4.84207 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 25.60400 8.81543E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -4.20000 2.69032E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8453.37172 8453.37172 0.49144 0.49144 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 25.86400 8.81585E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -4.20000 2.69032E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370951.57498 426594.31123 21.56501 24.79977 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 19.93600 8.80655E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 03:00:00 -4.20000 2.69032E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 133521.11 9.01668 9.01668 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 38493.86 1.89841 1.89841 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1230287.89 83.06976 83.06976 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 411113.23 28.28122 28.28122 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 137449.63 9.31221 9.31221 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 41145.79 4.41755 4.41755 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:50:00
7 CAV_BAS Cooling Sensible 67575.99 5.10799 5.10799 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 63272.12 1.20016 1.20016 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 420581.78 24.79985 24.79985 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 17840.03 0.33839 0.33839 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8513.43 0.50424 0.50424 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 824.14 1.56323E-002 1.56323E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 81741.66 4.84207 4.84207 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 8241.36 0.15632 0.15632 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8301.50 0.49144 0.49144 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 824.14 1.56323E-002 1.56323E-002 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Maximum Air Flow Rate [m3/s] 5.10799
2 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Constant Minimum Air Flow Fraction 0.41463
3 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER User-Specified Constant Minimum Air Flow Fraction 0.00000
4 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Minimum Air Flow Rate [m3/s] 0.00000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.46238
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34821
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29600
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61687
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.92855
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09417E-003
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40392E-004
13 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61687
14 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
15 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
16 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16047.68860
17 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40392E-004
18 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 323.50881
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 51.13022
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37200
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31600
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.15715
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99200
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.02419E-003
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.16927E-003
27 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.15715
28 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
29 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
30 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 362266.50167
31 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.16927E-003
32 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8349.49311
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.92942
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38586
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32800
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61685
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.87416E-004
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.22541E-004
41 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.14595
42 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
43 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
44 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 71160.20528
45 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.22541E-004
46 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1879.60414
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.83260
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28684
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24400
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20316
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.76490
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.32829E-003
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.90513E-005
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23795
56 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
58 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7892.99033
59 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.90513E-005
60 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 208.51544
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.27479
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12073
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10300
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13130
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32195
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.15580E-003
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.02130E-005
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17315
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
72 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5739.64945
73 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.02130E-005
74 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 151.58200
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.77027
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13491
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11500
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20358
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35976
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.82412E-003
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.95738E-005
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.30909
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
86 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10238.83379
87 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.95738E-005
88 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 270.31695
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.53388
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10034
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.50000E-002
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13038
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.79719E-003
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.18175E-005
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13038
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
100 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3636.93013
101 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.18175E-005
102 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 89.59219
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.58708
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31477
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26800
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03334
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83939
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.21040E-003
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54989E-003
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.35779
112 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
114 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 177162.04630
115 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54989E-003
116 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4673.41915
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.33835
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30769
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.30198E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.02954E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.55927
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 117682.53507
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.02954E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3104.28054
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 18.26951
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13072
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11100
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02792
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34860
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.91454E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.53628E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.31063
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 175606.35487
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.53628E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4632.42735
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.01303
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10983
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.30000E-002
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30321
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.46900E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.47575E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.27528
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 108313.60072
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.47575E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2857.39191
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.85392
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27968
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23800
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20323
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74581
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36229E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.00316E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.69286
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22897.36286
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.00316E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 603.86206
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.32415
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11623
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.90000E-002
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13109
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30994
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.27801E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.32200E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.45728
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15111.29587
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.32200E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 398.51461
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.92310
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12419
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10600
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20385
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33117
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.06793E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98838E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68774
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22728.36305
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98838E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 599.40914
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.46577
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10500
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.90000E-002
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13045
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.62859E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25401E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43372
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14334.06607
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25401E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 378.03353
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.50424
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.84207
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49144
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 24.79977
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.43696
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28528
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.87392
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.28528
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.01668
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.01668
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.25345
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 52.16909
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.82877
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 104.33819
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 28.28122
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 83.06976
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 83.06976
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34045
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.24818
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28547
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.49636
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 4.41755
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.31221
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.31221
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.47438
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.00000
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.00000
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.10799
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 1.20016
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.10799
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.10799
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 0.23496
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 24.79977
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 24.79977
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.79977
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 24.79977
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 24.79985
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 24.79985
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.50424
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.50424
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.50424
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.50424
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.50424
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.50424
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.84207
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.84207
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.84207
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.84207
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.84207
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.84207
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49144
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49144
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49144
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.49144
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.49144
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.49144
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.01668
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 83.06976
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.31221
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.10799
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 24.79985
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.50424
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.84207
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.49144
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.01668
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.21512
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.01741
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84463E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 164488.20690
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.70434E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.01668
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 44204.57716
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.86721E-004
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 737.80578
300 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.01668
301 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.70434E-003
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.01224E-004
303 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.86721E-004
304 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 83.06976
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.33125
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.01749
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.86932E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1533301.02796
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.38522E-002
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 83.06976
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 375848.69363
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.28809E-003
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 6313.16932
316 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 83.06976
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.38522E-002
318 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.08590E-005
319 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.28809E-003
320 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.31221
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.17670
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.01739
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.83697E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 169230.08975
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.83996E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.31221
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 36741.73542
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.21433E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 623.40659
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.31221
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.83996E-003
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 9.83873E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.21433E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.10799
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.29019
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.00638
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.98880E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 95943.46725
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.74397E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.10799
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 249715.86621
347 Coil:Heating:Water CAV_BAS HEATING COIL User-Specified Rated Capacity [W] 100000.00000
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.74844E-004
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 2622.58834
350 Fan:VariableVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.10799
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.74397E-003
352 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.73541E-004
353 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.74844E-004
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.79985
355 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 24.79985
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 490344.30579
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 351281.92830
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.20085E-002
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 24.79985
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 24.79985
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 24.79985
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 24.79985
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 490344.30579
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 490344.30579
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 17840.03233
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
368 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 24.79985
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 24.79985
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 490344.30579
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.20085E-002
372 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 17840.03233
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.64754E-004
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.50424
378 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.50424
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9744.95532
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 7061.29467
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.38653E-004
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.50424
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.50424
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.50424
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.50424
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9744.95532
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9744.95532
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 824.13559
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
391 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.50424
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.50424
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9744.95532
394 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.38653E-004
395 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 824.13559
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.84207
397 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.84207
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 93616.61326
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 67819.88010
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.29266E-003
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.84207
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.84207
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.84207
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.84207
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 93616.61326
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 93616.61326
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 8241.35587
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
410 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.84207
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.84207
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 93616.61326
413 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.29266E-003
414 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 8241.35587
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49144
416 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49144
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9503.89035
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6884.13555
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.32750E-004
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49144
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49144
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49144
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49144
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9503.89035
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9503.89035
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 824.13559
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
429 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49144
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49144
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9503.89035
432 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.32750E-004
433 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 824.13559
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 5.61405E-002
435 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 9075.27339
436 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 5.61405E-002
437 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 6.73686
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 5.61405E-002
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 5.61405E-002
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 235649.79494
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
442 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.47640E-002
443 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.77168
444 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.47640E-002
445 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 4402.23957
446 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
447 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1687613.43028
448 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1687613.43000
449 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.47640E-002
450 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 5.61405E-002
451 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 6.73686
452 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 2.80702E-002
453 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 3141.55891
454 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 2.80702E-002
455 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 3141.55891
456 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 5.61405E-002
457 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 2.83879E-002
458 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 992588.31966
459 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 992587.72000
460 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 5.10171E-002
461 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 5.61405E-002
462 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 2.83879E-002
463 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 992588.31966
464 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 992587.72000
465 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Condenser Fluid Flow Rate [m3/s] 5.10171E-002
466 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.47726E-002
467 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.77271
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.47726E-002
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3730.43927
470 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.47726E-002
471 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 146680.64435
472 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at High Fan Speed [W/K] 74254.09110
473 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 73340.32218
474 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/K] 44552.45466
476 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 608503.16860
477 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 596268.42000
478 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.47726E-002
479 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
480 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
483 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
484 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.10203
485 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 12.24410
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.10203
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 25011.28637
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 38.85715
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1189621.49004
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 7.77143
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 148702.68625
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 38.85715
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1189621.49004
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 7.77143
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 148702.68625
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.14725E-002
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.14725E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 15216.49
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 343248.76
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 67440.53
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 7480.63
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5439.47
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9702.77
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3444.82
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 167860.77
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 111503.30
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 166387.07
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 102627.98
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 21694.17
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 14317.18
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 21534.08
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 13580.90
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 35004.55
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 301445.32
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 30060.73
19 Coil:Heating:Water CAV_BAS HEATING COIL 94837.70


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 207059.05 150996.28 56062.77 0.73 34746.73 352.42
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 1918031.36 1395192.54 522838.82 0.73 319636.84 3241.93
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 213465.34 155796.90 57668.44 0.73 35905.74 364.18
4 Coil:Cooling:Water CAV_BAS COOLING COIL 119104.57 86271.32 32833.25 0.72 19778.00 200.60


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 7.93 27.04
2 Chiller:Electric:EIR COOLSYS1 CHILLER2 7.93 27.04


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.075 0.926   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.028 0.891   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.266 1.064   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 8.3976537693E-004 1.4125647447E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.9581449569E-003 6.1368949569E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 4.2785648518E-003 7.1472769967E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 1.4672863029E-002 1.1939220306E-002 Pass Pass 1.9622226632 17.2886949254 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 1.3215234839E-002 1.3693063226E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 1.4589915631E-002 1.4881791285E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 1.4511005192E-002 1.5545920411E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 1.3711987988E-002 1.4222945687E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 1.5993563034E-002 1.5291570361E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 1.7343056924E-002 1.6610623645E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 1.7944044082E-002 1.8077061942E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 1.6894838341E-002 1.6427400625E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.2534727705 0.2313932387 Pass Pass 19.3193891080 44.4252445421 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2621454944 0.2406043569 Pass Pass 19.5861013153 45.0216681540 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2438203149 0.2249487567 Pass Pass 19.0703755226 43.8388219753 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1242211188 0.1403617161 Pass Pass 21.7408781635 52.5866087474 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.5201578953E-003 2.4761906072E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.1165994303E-003 3.1475304117E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 7.7547617023E-002 4.5596662720E-002 Pass Pass 0.4108962438 0.4751546896 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.9466877508E-006 5.8622992137E-006 Pass Pass 1.6463737000E-003 1.3176667925E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 6.9404672623E-003 3.6719513364E-003 Pass Pass 1.3553158773E-003 9.8238945799E-004 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 6.6573705352E-003 3.9837661609E-003 Pass Pass 1.5986496131E-003 1.3338851564E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.0809980080E-006 2.8356243219E-006 Pass Pass 2.8286877362E-005 1.0859343910E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5747.72 91.24 0.00 30554.96 6907.01 43300.94



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.891 1.028 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.891 1.028 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.926 1.075 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.926 1.075 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.891 1.028 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.891 1.028 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.891 1.028 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.064 1.266 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.064 1.266 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.363_SHGC_NORTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.363_SHGC_NORTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.363_SHGC_NORTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.363_SHGC_NORTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.363_SHGC_NORTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.363_SHGC_EAST_0.359   25.75 0.00 0.00 25.75 25.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.363_SHGC_EAST_0.359   25.75 0.00 0.00 25.75 25.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.363_SHGC_EAST_0.359   25.75 0.00 0.00 25.75 25.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.363_SHGC_SOUTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.363_SHGC_SOUTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.363_SHGC_SOUTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.363_SHGC_SOUTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.363_SHGC_SOUTH_0.359   23.18 0.00 0.00 23.18 23.18 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.363_SHGC_WEST_0.359   25.75 0.00 0.00 25.75 25.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.363_SHGC_WEST_0.359   25.75 0.00 0.00 25.75 25.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.363_SHGC_WEST_0.359   25.75 0.00 0.00 25.75 25.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.359   115.90 0.00 0.00 115.90 1158.95 2.062 0.360 0.396             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.359   77.26 0.00 0.00 77.26 772.63 2.062 0.360 0.396             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.359   115.90 0.00 0.00 115.90 1158.95 2.062 0.360 0.396             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.359   77.26 0.00 0.00 77.26 772.63 2.062 0.360 0.396             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.359   115.90 0.00 0.00 115.90 115.90 2.062 0.360 0.396             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.359   77.26 0.00 0.00 77.26 77.26 2.062 0.360 0.396             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.359   115.90 0.00 0.00 115.90 115.90 2.062 0.360 0.396             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.359   77.26 0.00 0.00 77.26 77.26 2.062 0.360 0.396             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.062 0.360 0.396                      
North Total or Average             1390.74 2.062 0.360 0.396                      
Non-North Total or Average             3245.06 2.062 0.360 0.396                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.5999 2779.43 18343.83 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 165.73
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.5999 24961.20 164740.46 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 1488.36
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.22 0.0000 Y 10.96
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.95 0.0000 Y 6.99
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.70 0.0000 Y 10.75
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.89 0.0000 Y 6.98
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.5999 3134.13 20684.81 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.15 0.0000 Y 109.32
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.91 0.0000 Y 69.83
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.5999 3134.20 20685.26 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.67 0.0000 Y 107.44
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.85 0.0000 Y 69.68
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 28.15 0.0000 Y 10.93
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.91 0.0000 Y 6.98
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.67 0.0000 Y 10.74
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.84 0.0000 Y 6.97
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 6.5999 783.68 5172.17 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 47.61
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 9.7790 362.03 3540.27 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 36.26
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
Interior Lighting Total       6.6297 46320.38 307089.14               777.66


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13271.55 AstronomicalClock -   42.59 42.59 106.11
EXTERIOR_LIGHTS_B 989.48 AstronomicalClock -   83.55 63.07 11.71
EXTERIOR_LIGHTS_C 26594.85 AstronomicalClock -   83.55 47.80 238.62
Exterior Lighting Total 40855.88           356.44



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 1956916.69          
HEATSYS1 BOILER Boiler:HotWater 1687613.43 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 992587.72 5.17 989226.48 5.11 7.93 27.04
COOLSYS1 CHILLER2 Chiller:Electric:EIR 992587.72 5.17 989226.48 5.11 7.93 27.04
CENTRAL TOWER FluidCooler:TwoSpeed 611291.59          
CENTRAL BOILER Boiler:HotWater 596268.42 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1189621.49          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1189621.49          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 164488.21 207059.05 150996.28 56062.77 0.73 - 34746.73 352.42
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1533301.03 1918031.36 1395192.54 522838.82 0.73 - 319636.84 3241.93
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 169230.09 213465.34 155796.90 57668.44 0.73 - 35905.74 364.18
CAV_BAS COOLING COIL Coil:Cooling:Water 95943.47 119104.57 86271.32 32833.25 0.72 - 19778.00 200.60
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   490344.31 351281.93 139062.38 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9744.96 7061.29 2683.66 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   93616.61 67819.88 25796.73 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9503.89 6884.14 2619.75 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16047.69 15216.49 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 362266.50 343248.76 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 71160.21 67440.53 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 7892.99 7480.63 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 5739.65 5439.47 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 10238.83 9702.77 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 3636.93 3444.82 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 177162.05 167860.77 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 117682.54 111503.30 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 175606.35 166387.07 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 108313.60 102627.98 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 22897.36 21694.17 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 15111.30 14317.18 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 22728.36 21534.08 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 14334.07 13580.90 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 44204.58 35004.55 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 375848.69 301445.32 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 36741.74 30060.73 -
CAV_BAS HEATING COIL Coil:Heating:Water 100000.00 94837.70 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   490344.31 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9744.96 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   93616.61 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9503.89 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   17840.03 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   824.14 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   8241.36 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   824.14 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.02 19484.57 2160.95 1.00 1.12 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 83.07 179509.32 2160.95 1.00 1.08 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.31 20123.19 2160.95 1.00 1.12 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00
CAV_BAS FAN Fan:VariableVolume 0.60 1314.72 5.11 11109.30 2174.89 1.00 1.14 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 24.80 40901.08 1649.25 1.00 1.14 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 564.80 1120.11 1.00 1.60 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.84 5423.64 1120.11 1.00 1.16 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 550.46 1120.11 1.00 1.61 General SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.056140 9075.27 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.014764 4402.24 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.028070 3141.56 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.028070 3141.56 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.014773 3730.44 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.102034 25011.29 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 1.00 13.34 0.74



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 69959.15 69959.15 25.17 5.108 5.108 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00900 21.70 0.00881 1.200 0.00
CORE_BOTTOM 74812.31 74812.31 29.97 5.462 5.462 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00892 21.70 0.00881 1.078 0.00
CORE_MID 700486.04 700486.04 280.63 51.130 51.130 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00895 21.70 0.00881 10.778 0.00
CORE_TOP 67540.45 67540.45 27.06 4.929 4.929 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 21.70 0.00881 1.078 0.00
PERIMETER_BOT_ZN_3 11296.19 11296.19 36.04 0.833 0.833 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00884 29.40 0.00882 0.135 0.00
PERIMETER_BOT_ZN_2 17295.60 17295.60 85.63 1.275 1.275 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:40:00 24.00 24.00 0.00864 23.02 0.00881 0.087 0.00
PERIMETER_BOT_ZN_1 24017.99 24017.99 76.63 1.770 1.770 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00866 28.97 0.00882 0.135 0.00
PERIMETER_BOT_ZN_4 20810.86 20810.86 103.04 1.534 1.534 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00862 27.94 0.00882 0.087 0.00
PERIMETER_MID_ZN_3 102936.16 102936.16 328.44 7.587 7.587 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00887 29.40 0.00882 1.353 0.00
PERIMETER_MID_ZN_2 180967.59 180967.59 895.99 13.338 13.338 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 24.00 24.00 0.00864 23.68 0.00881 0.872 0.00
PERIMETER_MID_ZN_1 247870.41 247870.41 790.86 18.270 18.270 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00866 29.14 0.00882 1.353 0.00
PERIMETER_MID_ZN_4 190121.18 190121.18 941.31 14.013 14.013 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00863 27.77 0.00882 0.872 0.00
PERIMETER_TOP_ZN_3 11585.35 11585.35 36.97 0.854 0.854 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00883 29.40 0.00882 0.135 0.00
PERIMETER_TOP_ZN_2 17965.39 17965.39 88.95 1.324 1.324 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 24.00 24.00 0.00864 23.68 0.00881 0.087 0.00
PERIMETER_TOP_ZN_1 26091.57 26091.57 83.25 1.923 1.923 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00865 29.14 0.00882 0.135 0.00
PERIMETER_TOP_ZN_4 19886.80 19886.80 98.46 1.466 1.466 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00863 27.77 0.00882 0.087 0.00
DATACENTER_BOT_ZN_6 8673.55 8673.55 239.58 0.504 0.504 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 27.00 27.00 0.00858 25.60 0.00882 0.016 0.00
DATACENTER_MID_ZN_6 83289.58 83289.58 2300.64 4.842 4.842 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 27.00 27.00 0.00859 25.60 0.00882 0.156 0.00
DATACENTER_TOP_ZN_6 8453.37 8453.37 233.50 0.491 0.491 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 25.86 0.00882 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370951.57 426594.31 544.35 21.565 24.800 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 19.94 0.00881 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 24.49 0.00269 -4.20 0.00269 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 19.60 22.18 0.00269 -4.20 0.00269 1.078 0.00
CORE_MID 201903.73 201903.73 80.89 8.612 10.778 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 10.778 0.00
CORE_TOP 49861.22 49861.22 19.98 2.146 2.146 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 1.078 0.00
PERIMETER_BOT_ZN_3 5534.74 5534.74 17.66 0.238 0.238 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00730 -4.20 0.00269 0.135 0.00
PERIMETER_BOT_ZN_2 4023.28 4023.28 19.92 0.173 0.173 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00740 -4.20 0.00269 0.087 0.00
PERIMETER_BOT_ZN_1 7174.03 7174.03 22.89 0.309 0.309 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00755 -4.20 0.00269 0.135 0.00
PERIMETER_BOT_ZN_4 2346.12 2346.12 11.62 0.100 0.100 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00673 -4.20 0.00269 0.087 0.00
PERIMETER_MID_ZN_3 124023.18 124023.18 395.72 5.358 5.358 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00768 -4.20 0.00269 1.353 0.00
PERIMETER_MID_ZN_2 82381.20 82381.20 407.88 3.559 3.559 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00769 -4.20 0.00269 0.872 0.00
PERIMETER_MID_ZN_1 122935.78 122935.78 392.24 5.311 5.311 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00768 -4.20 0.00269 1.353 0.00
PERIMETER_MID_ZN_4 75832.27 75832.27 375.45 3.275 3.275 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00764 -4.20 0.00269 0.872 0.00
PERIMETER_TOP_ZN_3 16025.02 16025.02 51.13 0.693 0.693 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00773 -4.20 0.00269 0.135 0.00
PERIMETER_TOP_ZN_2 10575.65 10575.65 52.36 0.457 0.457 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00772 -4.20 0.00269 0.087 0.00
PERIMETER_TOP_ZN_1 15906.88 15906.88 50.75 0.688 0.688 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00772 -4.20 0.00269 0.135 0.00
PERIMETER_TOP_ZN_4 10032.25 10032.25 49.67 0.434 0.434 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00771 -4.20 0.00269 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00 18.00 26.72 0.00850 -4.20 0.00269 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 23.44 0.00574 -4.20 0.00269 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 21.79 0.00302 -4.20 0.00269 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 03:00:00 18.00 27.00 0.00850 -4.20 0.00269 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.02 9.02 1.90 1.90 9.0167 2.2853 9.0167 0.2535 0.3000
VAV_MID WITH REHEAT 83.07 83.07 28.28 28.28 83.0698 28.2812 83.0698 0.3405 0.3000
VAV_TOP WITH REHEAT 9.31 9.31 4.42 4.42 9.3122 4.4175 9.3122 0.4744 0.3000
CAV_BAS 5.11 5.11 1.20 1.20 5.1080 1.2002 5.1080 0.2350 1.0000
AIRLOOP DATACENTER BASEMENT 24.80 24.80 0.34 0.34 24.7999 24.7998 24.7999 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.50 0.50 0.02 0.02 0.5042 0.5042 0.5042 1.0000 1.0000
AIRLOOP DATACENTER MID 4.84 4.84 0.16 0.16 4.8421 4.8421 4.8421 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.49 0.49 0.02 0.02 0.4914 0.4914 0.4914 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16047.689 16047.689 1.616866 0.00014039 323.509 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 16047.69 16047.69 1.616866 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 0.00 0.00 16106.86 16106.86
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 362266.502 362266.502 16.157148 0.00316927 8349.493 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 362266.50 362266.50 16.157148 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 201903.73 0.00 363467.10 363467.10
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 71160.205 71160.205 2.145954 0.00062254 1879.604 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 71160.21 71160.21 2.145954 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 49861.22 0.00 71414.66 71414.66
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 7892.990 7892.990 0.237946 0.00006905 208.515 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7892.99 7892.99 0.237946 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00730057 46.5782 5534.74 0.00 7921.45 7921.45
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 5739.649 5739.649 0.173147 0.00005021 151.582 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5739.65 5739.65 0.173147 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00740339 47.2263 4023.28 0.00 5760.01 5760.01
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 10238.834 10238.834 0.309089 0.00008957 270.317 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10238.83 10238.83 0.309089 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00754589 48.1239 7174.03 0.00 10274.52 10274.52
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 3636.930 3636.930 0.130380 0.00003182 89.592 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3636.93 3636.93 0.130380 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00673349 42.9994 2346.12 0.00 3648.36 3648.36
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 177162.046 177162.046 5.357794 0.00154989 4673.419 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 177162.05 177162.05 5.357794 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00768322 48.9892 124023.18 0.00 177751.85 177751.85
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 117682.535 117682.535 3.559265 0.00102954 3104.281 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 117682.54 117682.54 3.559265 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00768869 49.0236 82381.20 0.00 118073.55 118073.55
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 175606.355 175606.355 5.310630 0.00153628 4632.427 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 175606.35 175606.35 5.310630 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00767851 48.9595 122935.78 0.00 176191.32 176191.32
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 108313.601 108313.601 3.275281 0.00094757 2857.392 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 108313.60 108313.60 3.275281 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00763955 48.7144 75832.27 0.00 108675.28 108675.28
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 22897.363 22897.363 0.692859 0.00020032 603.862 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 22897.36 22897.36 0.692859 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00772642 49.2613 16025.02 0.00 22972.47 22972.47
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 15111.296 15111.296 0.457280 0.00013220 398.515 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 15111.30 15111.30 0.457280 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00772470 49.2505 10575.65 0.00 15160.80 15160.80
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 22728.363 22728.363 0.687735 0.00019884 599.409 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 22728.36 22728.36 0.687735 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00772420 49.2473 15906.88 0.00 22802.95 22802.95
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 14334.066 14334.066 0.433721 0.00012540 378.034 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14334.07 14334.07 0.433721 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00770744 49.1419 10032.25 0.00 14381.14 14381.14
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 164488.207 -999.000 9.016681 0.00470434 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 164488.21 154857.72 9.016681 25.22 16.96 0.00884463 11.02 11.02 0.00850000 29.40 0.00882150 18.34 22.5194 24.00 0.00885136 46.9452 122331.63 0.00 166483.14 150921.49
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 44204.577 44204.577 2.705004 0.00038672 737.806 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 44204.58 44204.58 2.705004 -0.90 -1.46 0.00319204 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 75.0646 21.44 0.00568004 35.3709 19078.16 0.00 42356.60 42356.60
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1533301.028 -999.000 83.069756 0.04385221 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 1533301.03 1438241.86 83.069756 25.33 17.02 0.00886932 11.02 11.02 0.00850000 29.40 0.00882150 18.34 24.4445 24.00 0.00888497 47.1210 1116738.31 0.00 1551685.12 1402037.27
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 375848.694 375848.694 24.920927 0.00328809 6313.169 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 375848.69 375848.69 24.920927 0.16 -0.27 0.00359113 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 81.4817 19.62 0.00712242 49.5119 266628.98 0.00 364798.39 364798.39
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 169230.090 -999.000 9.312209 0.00483996 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 169230.09 159504.49 9.312209 25.18 16.94 0.00883697 11.02 11.02 0.00850000 29.40 0.00882150 18.34 21.8047 24.00 0.00884128 46.8925 126321.85 0.00 171290.36 155437.95
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 36741.735 36741.735 2.793663 0.00032143 623.407 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:50:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 36741.74 36741.74 2.793663 1.77 1.32 0.00403421 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 72.6824 17.60 0.00730333 57.5879 31345.56 0.00 36382.81 36382.81
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 95943.467 -999.000 5.107985 0.00274397 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 95943.47 88205.02 5.107985 25.29 17.10 0.00898880 11.01 11.01 0.00850000 28.88 0.00882066 18.17 23.4957 24.00 0.00904929 47.9803 61539.98 0.00 97080.29 86040.77
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 100000.000 100000.000 3.082328 0.00087484 2622.588 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 100000.00 100000.00 3.082328 -0.99 -2.30 0.00269032 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 38.9367 24.54 0.00269032 13.9492 0.00 0.00 100078.78 100078.78
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 490344.306 351281.928 24.799853 0.01200850 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 456118.50 453051.59 -999.0 28.44 17.81 0.00854616 12.80 11.97 0.00850000 29.40 0.00882150 18.34 -999.0000 27.00 0.00854235 37.9340 370610.90 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9744.955 7061.295 0.504237 0.00023865 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 9029.97 8907.80 -999.0 27.91 17.67 0.00859066 12.80 11.97 0.00850000 25.60 0.00881543 17.07 -999.0000 27.00 0.00858346 38.1116 8673.55 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93616.613 67819.880 4.842066 0.00229266 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 86753.50 85533.21 -999.0 27.91 17.67 0.00859429 12.80 11.97 0.00850000 25.60 0.00881543 17.07 -999.0000 27.00 0.00858692 38.1268 83289.58 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9503.890 6884.136 0.491439 0.00023275 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8807.57 8685.79 -999.0 27.92 17.67 0.00859271 12.80 11.97 0.00850000 25.86 0.00881585 17.16 -999.0000 27.00 0.00858538 38.1201 8453.37 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 490344.306 490344.306 24.799853 0.01200850 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 490344.31 490344.31 24.799853 -4.20 -4.20 0.00269032 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 1.3645 27.00 0.00850000 37.7427 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9744.955 9744.955 0.504237 0.00023865 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9744.96 9744.96 0.504237 -4.20 -4.20 0.00269032 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 3.1002 26.97 0.00850000 37.8111 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93616.613 93616.613 4.842066 0.00229266 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 93616.61 93616.61 4.842066 -4.20 -4.20 0.00269032 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 3.2284 24.63 0.00573895 29.4465 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9503.890 9503.890 0.491439 0.00023275 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9503.89 9503.89 0.491439 -4.20 -4.20 0.00269032 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 3.1809 23.59 0.00301667 16.5532 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 17840.032 17840.032 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 17840.03 17840.03 24.799853 -0.06 -0.06 0.00842073 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 1.3645 27.00 0.00850000 37.7427 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 824.136 824.136 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 824.14 824.14 0.504237 -0.13 -0.13 0.00831989 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 3.1002 26.97 0.00850000 37.8111 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 8241.356 8241.356 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 8241.36 8241.36 4.842066 -0.14 -0.14 0.00564053 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 3.2284 24.63 0.00573895 29.4465 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 824.136 824.136 -999.0 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 824.14 824.14 0.491439 -0.13 -1.32 0.00300629 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 3.1809 23.59 0.00301667 16.5532 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16047.689 16047.689 1.616866 0.00014039 323.509 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.9322 0.950910 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 Sensible 16047.69 16047.69 1.0000 1.91920460 1.616866 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.14037786 60.00 32.22 27.78 0.000 16047.69 -4.20 0.00269032 -4.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.9797 0.00 0.00 16106.86 16106.86 1.91920460 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 362266.502 362266.502 16.157148 0.00316927 8349.493 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 21.0427 21.466202 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 362266.50 362266.50 1.0000 19.17838631 16.157148 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 3.16894209 60.00 32.22 27.78 0.000 362266.50 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 50.9797 201903.73 0.00 363467.10 363467.10 19.17838631 12.80 11.60 0.00800000 33059.8 31.39 18.50 0.00800000 52011.7
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 71160.205 71160.205 2.145954 0.00062254 1879.604 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 4.1334 4.216618 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 71160.21 71160.21 1.0000 2.54722750 2.145954 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.62247701 60.00 32.22 27.78 0.000 71160.21 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 50.9797 49861.22 0.00 71414.66 71414.66 2.54722750 12.80 11.60 0.00800000 33059.8 40.29 21.27 0.00800000 61096.1
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 7892.990 7892.990 0.237946 0.00006905 208.515 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.4585 0.467701 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7892.99 7892.99 1.0000 0.28243949 0.237946 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06904428 60.00 32.22 27.78 0.000 7892.99 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.86 0.00730057 21.00 0.00730057 46.5782 5534.74 0.00 7921.45 7921.45 0.28243949 12.80 11.60 0.00800000 33059.8 40.30 21.27 0.00800000 61106.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 5739.649 5739.649 0.173147 0.00005021 151.582 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.3334 0.340105 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5739.65 5739.65 1.0000 0.20552352 0.173147 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.05020784 60.00 32.22 27.78 0.000 5739.65 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.92 0.00740339 21.00 0.00740339 47.2263 4023.28 0.00 5760.01 5760.01 0.20552352 12.80 11.60 0.00800000 33059.8 40.28 21.27 0.00800000 61085.8
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 10238.834 10238.834 0.309089 0.00008957 270.317 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.5947 0.606705 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10238.83 10238.83 1.0000 0.36688537 0.309089 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.08956465 60.00 32.22 27.78 0.000 10238.83 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.91 0.00754589 21.00 0.00754589 48.1239 7174.03 0.00 10274.52 10274.52 0.36688537 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61064.6
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 3636.930 3636.930 0.130380 0.00003182 89.592 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.2113 0.215507 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 3636.93 3636.93 1.0000 0.15475931 0.130380 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.03181421 60.00 32.22 27.78 0.000 3636.93 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.87 0.00673349 21.00 0.00673349 42.9994 2346.12 0.00 3648.36 3648.36 0.15475931 12.80 11.60 0.00800000 33059.8 35.92 19.94 0.00800000 56634.3
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 177162.046 177162.046 5.357794 0.00154989 4673.419 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 10.2907 10.497786 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 177162.05 177162.05 1.0000 6.35965210 5.357794 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 1.54973276 60.00 32.22 27.78 0.000 177162.05 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00768322 21.00 0.00768322 48.9892 124023.18 0.00 177751.85 177751.85 6.35965210 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61009.8
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 117682.535 117682.535 3.559265 0.00102954 3104.281 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 6.8357 6.973311 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 117682.54 117682.54 1.0000 4.22481486 3.559265 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 1.02943313 60.00 32.22 27.78 0.000 117682.54 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00768869 21.00 0.00768869 49.0236 82381.20 0.00 118073.55 118073.55 4.22481486 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61007.5
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 175606.355 175606.355 5.310630 0.00153628 4632.427 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 10.2003 10.405603 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 175606.35 175606.35 1.0000 6.30366913 5.310630 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 1.53612428 60.00 32.22 27.78 0.000 175606.35 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00767851 21.00 0.00767851 48.9595 122935.78 0.00 176191.32 176191.32 6.30366913 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61010.4
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 108313.601 108313.601 3.275281 0.00094757 2857.392 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 6.2915 6.418152 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 108313.60 108313.60 1.0000 3.88772836 3.275281 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.94747797 60.00 32.22 27.78 0.000 108313.60 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00763955 21.00 0.00763955 48.7144 75832.27 0.00 108675.28 108675.28 3.88772836 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.2
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 22897.363 22897.363 0.692859 0.00020032 603.862 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 1.3300 1.356790 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 22897.36 22897.36 1.0000 0.82241774 0.692859 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.20029568 60.00 32.22 27.78 0.000 22897.36 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00772642 21.00 0.00772642 49.2613 16025.02 0.00 22972.47 22972.47 0.82241774 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60992.7
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 15111.296 15111.296 0.457280 0.00013220 398.515 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.8778 0.895424 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 15111.30 15111.30 1.0000 0.54278771 0.457280 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.13218672 60.00 32.22 27.78 0.000 15111.30 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00772470 21.00 0.00772470 49.2505 10575.65 0.00 15160.80 15160.80 0.54278771 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.2
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 22728.363 22728.363 0.687735 0.00019884 599.409 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 1.3202 1.346775 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 22728.36 22728.36 1.0000 0.81633566 0.687735 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.19881735 60.00 32.22 27.78 0.000 22728.36 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00772420 21.00 0.00772420 49.2473 15906.88 0.00 22802.95 22802.95 0.81633566 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.1
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 14334.066 14334.066 0.433721 0.00012540 378.034 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 0.8326 0.849369 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14334.07 14334.07 1.0000 0.51482247 0.433721 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.12538787 60.00 32.22 27.78 0.000 14334.07 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00770744 21.00 0.00770744 49.1419 10032.25 0.00 14381.14 14381.14 0.51482247 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60994.0
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 164488.207 -999.000 9.016681 0.00470434 -999.000 -999.0000 1.00000 1.00000 1021.2817 1004.8586 1.1870 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.016681 10.70271761   4197.9300 999.8980 56.13476045 15.00 6.67 8.33 1962962.79 8.3796 8.379589 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 Sensible 164488.21 154857.72 1.0000 10.70271761 9.016681 25.22 16.96 0.00884463 47871.6 11.02 11.02 0.00850000 32502.8 4.70386200 6.67 15.00 8.33 19484.568 145003.64 29.40 0.00882150 18.34 2.03050000 22.5194 24.00 0.00885136 24.00 0.00885136 46.9452 122331.63 0.00 166483.14 150921.49 10.70271761 25.22 17.11 0.00884463 47871.6 11.41 11.28 0.00826814 32316.4
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 44204.577 44204.577 2.705004 0.00038672 737.806 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.016681 10.70271761   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 2.5677 2.619354 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 44204.58 44204.58 1.0000 3.21081528 2.705004 -0.90 -1.46 0.00319204 7072.6 12.80 11.47 0.00800000 33059.8 0.38668148 60.00 32.22 27.78 0.000 44204.58 -4.20 0.00269032 -4.20 2.03050000 75.0646 9.03 0.00470242 21.44 0.00568004 35.3709 19078.16 0.00 42356.60 42356.60 3.21081528 2.80 0.80 0.00319204 10813.3 15.85 7.69 0.00319204 24005.1
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1533301.028 -999.000 83.069756 0.04385221 -999.000 -999.0000 1.00000 1.00000 1021.3276 1004.8586 1.1870 VAV_MID WITH REHEAT FAN Fan:VariableVolume 83.069756 98.60303486   4197.9300 999.8980 56.13476045 15.00 6.67 8.33 1962962.79 78.1116 78.111569 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 1533301.03 1438241.86 1.0000 98.60303486 83.069756 25.33 17.02 0.00886932 48053.1 11.02 11.02 0.00850000 32502.9 43.84774192 6.67 15.00 8.33 179509.319 1353791.71 29.40 0.00882150 18.34 20.30600000 24.4445 24.00 0.00888497 24.00 0.00888497 47.1210 1116738.31 0.00 1551685.12 1402037.27 98.60303486 25.33 17.17 0.00886932 48053.1 11.41 11.28 0.00826758 32316.4
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 375848.694 375848.694 24.920927 0.00328809 6313.169 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 VAV_MID WITH REHEAT FAN Fan:VariableVolume 83.069756 98.60303486   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 21.8316 22.271018 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 375848.69 375848.69 1.0000 29.58091046 24.920927 0.16 -0.27 0.00359113 9138.6 12.80 11.47 0.00800000 33059.8 3.28775291 60.00 32.22 27.78 0.000 375848.69 -4.20 0.00269032 -4.20 20.30600000 81.4817 19.32 0.00755478 19.62 0.00712242 49.5119 266628.98 0.00 364798.39 364798.39 29.58091046 2.80 1.37 0.00359113 11813.5 14.99 7.75 0.00359113 24145.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 169230.090 -999.000 9.312209 0.00483996 -999.000 -999.0000 1.00000 1.00000 1021.2675 1004.8586 1.1870 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.312209 11.05350625   4197.9300 999.8980 56.13476045 15.00 6.67 8.33 1962962.79 8.6212 8.621156 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 169230.09 159504.49 1.0000 11.05350625 9.312209 25.18 16.94 0.00883697 47812.9 11.02 11.02 0.00850000 32502.8 4.83946542 6.67 15.00 8.33 20123.188 149106.90 29.40 0.00882150 18.34 2.03050000 21.8047 24.00 0.00884128 24.00 0.00884128 46.8925 126321.85 0.00 171290.36 155437.95 11.05350625 25.18 17.09 0.00883697 47812.9 11.41 11.28 0.00826834 32316.4
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 36741.735 36741.735 2.793663 0.00032143 623.407 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.312209 11.05350625   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 2.1342 2.177142 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:50:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 36741.74 36741.74 1.0000 3.31605187 2.793663 1.77 1.32 0.00403421 11884.8 12.80 11.47 0.00800000 33059.8 0.32139994 60.00 32.22 27.78 0.000 36741.74 -4.20 0.00269032 -4.20 2.03050000 72.6824 17.67 0.00760981 17.60 0.00730333 57.5879 31345.56 0.00 36382.81 36382.81 3.31605187 2.80 1.99 0.00403421 12923.9 13.64 7.63 0.00403421 23895.6
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 95943.467 -999.000 5.107985 0.00274397 -999.000 -999.0000 1.00000 1.00000 1021.5497 1004.8586 1.1870 CAV_BAS FAN Fan:VariableVolume 5.107985 6.06313131   4197.9300 999.8980 56.13476045 15.00 6.67 8.33 1962962.79 4.8877 4.887686 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 95943.47 88205.02 1.0000 6.06313131 5.107985 25.29 17.10 0.00898880 48315.6 11.01 11.01 0.00850000 32491.6 2.74369110 6.67 15.00 8.33 11109.297 84834.17 28.88 0.00882066 18.17 1.20015641 23.4957 24.00 0.00904929 24.00 0.00904929 47.9803 61539.98 0.00 97080.29 86040.77 6.06313131 25.29 17.25 0.00898880 48315.6 11.40 11.28 0.00826688 32304.1
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100000.000 100000.000 3.082328 0.00087484 2622.588 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 CAV_BAS FAN Fan:VariableVolume 5.107985 6.06313131   4197.9300 999.8980 14.76247241 54.44 82.22 27.78 1721577.32 5.8086 5.925528 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 100000.00 100000.00 1.0000 3.65869449 3.082328 -0.99 -2.30 0.00269032 5731.8 40.00 21.01 0.00800000 60796.0 0.87475438 60.00 32.22 27.78 0.000 100000.00 -4.20 0.00269032 -4.20 1.20015641 38.9367 0.00 0.00269032 24.54 0.00269032 13.9492 0.00 0.00 100078.78 100078.78 3.65869449 12.80 1.98 0.00000000 12887.2 40.02 14.59 0.00000000 40240.9
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 490344.306 351281.928 24.799853 0.01200850 -999.000 -999.0000 -999.00000 -999.00000 1020.7269 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 Sensible 456118.50 453051.59 0.9302 -999.0 -999.0 28.44 17.81 0.00854616 50406.2 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 456118.50 29.40 0.00882150 18.34 0.33839277 -999.0000 27.00 0.00854235 27.00 0.00854235 37.9340 370610.90 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9744.955 7061.295 0.504237 0.00023865 -999.000 -999.0000 -999.00000 -999.00000 1020.8096 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 9029.97 8907.80 0.9266 -999.0 -999.0 27.91 17.67 0.00859066 49980.3 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 9029.97 25.60 0.00881543 17.07 0.01563234 -999.0000 27.00 0.00858346 27.00 0.00858346 38.1116 8673.55 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 93616.613 67819.880 4.842066 0.00229266 -999.000 -999.0000 -999.00000 -999.00000 1020.8164 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 86753.50 85533.21 0.9267 -999.0 -999.0 27.91 17.67 0.00859429 49987.6 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 86753.50 25.60 0.00881543 17.07 0.15632344 -999.0000 27.00 0.00858692 27.00 0.00858692 38.1268 83289.58 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9503.890 6884.136 0.491439 0.00023275 -999.000 -999.0000 -999.00000 -999.00000 1020.8134 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8807.57 8685.79 0.9267 -999.0 -999.0 27.92 17.67 0.00859271 49992.8 12.80 11.97 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8807.57 25.86 0.00881585 17.16 0.01563234 -999.0000 27.00 0.00858538 27.00 0.00858538 38.1201 8453.37 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 490344.306 490344.306 24.799853 0.01200850 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 490344.31 490344.31 1.0000 29.43719668 24.799853 -4.20 -4.20 0.00269032 2487.0 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 490344.31 -4.20 0.00269032 -4.20 0.33839277 1.3645 0.00 0.00850000 27.00 0.00850000 37.7427 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9744.955 9744.955 0.504237 0.00023865 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9744.96 9744.96 1.0000 0.59852504 0.504237 -4.20 -4.20 0.00269032 2487.0 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9744.96 -4.20 0.00269032 -4.20 0.01563234 3.1002 0.00 0.00850000 26.97 0.00850000 37.8111 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 93616.613 93616.613 4.842066 0.00229266 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 93616.61 93616.61 1.0000 5.74748741 4.842066 -4.20 -4.20 0.00269032 2487.0 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 93616.61 -4.20 0.00269032 -4.20 0.15632344 3.2284 0.00 0.00573895 24.63 0.00573895 29.4465 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9503.890 9503.890 0.491439 0.00023275 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9503.89 9503.89 1.0000 0.58333321 0.491439 -4.20 -4.20 0.00269032 2487.0 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9503.89 -4.20 0.00269032 -4.20 0.01563234 3.1809 0.00 0.00301667 23.59 0.00301667 16.5532 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 17840.032 17840.032 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 24.799853 29.43719668   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 17840.03 17840.03 1.0000 29.43719668 24.799853 -0.06 -0.06 0.00842073 21001.3 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 17840.03 -4.20 0.00269032 -4.20 0.33839277 1.3645 0.00 0.00850000 27.00 0.00850000 37.7427 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 824.136 824.136 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.504237 0.59852504   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 824.14 824.14 1.0000 0.59852504 0.504237 -0.13 -0.13 0.00831989 20674.7 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 824.14 -4.20 0.00269032 -4.20 0.01563234 3.1002 0.00 0.00850000 26.97 0.00850000 37.8111 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8241.356 8241.356 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.842066 5.74748741   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 8241.36 8241.36 1.0000 5.74748741 4.842066 -0.14 -0.14 0.00564053 13968.9 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8241.36 -4.20 0.00269032 -4.20 0.15632344 3.2284 0.00 0.00573895 24.63 0.00573895 29.4465 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 824.136 824.136 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.491439 0.58333321   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 824.14 824.14 1.0000 0.58333321 0.491439 -0.13 -1.32 0.00300629 7383.6 40.00 21.01 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 824.14 -4.20 0.00269032 -4.20 0.01563234 3.1809 0.00 0.00301667 23.59 0.00301667 16.5532 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.02 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 83.07 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.31 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 5.11 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 24.80 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2970.00 214.17 47.17
CORE_BOTTOM 2566.50 379.83 13.00
CORE_MID 1378.33 2364.83 12.00
CORE_TOP 1444.00 3503.00 371.83
PERIMETER_BOT_ZN_3 1477.50 2866.67 16.83
PERIMETER_BOT_ZN_2 1817.33 2869.67 85.67
PERIMETER_BOT_ZN_1 2220.17 2580.33 154.00
PERIMETER_BOT_ZN_4 3087.83 1230.50 218.33
PERIMETER_MID_ZN_3 1660.00 4045.67 790.00
PERIMETER_MID_ZN_2 1852.50 3097.50 706.67
PERIMETER_MID_ZN_1 2281.00 3180.83 518.33
PERIMETER_MID_ZN_4 2165.33 3374.67 567.50
PERIMETER_TOP_ZN_3 2311.33 4385.67 1530.00
PERIMETER_TOP_ZN_2 2718.50 3841.50 1393.67
PERIMETER_TOP_ZN_1 2635.67 3614.50 1094.50
PERIMETER_TOP_ZN_4 2581.50 3786.67 1169.17
DATACENTER_BOT_ZN_6 5943.00 710.67 710.67
DATACENTER_MID_ZN_6 5855.50 139.50 125.17
DATACENTER_TOP_ZN_6 5521.83 327.50 202.17
DATACENTER_BASEMENT_ZN_6 5943.00 5749.50 5749.50
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 782.17 0.00 381.67
CORE_BOTTOM 0.00 1.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 4.67 0.00 0.83 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 0.00 18.83 0.00 18.83
PERIMETER_BOT_ZN_1 0.00 34.83 0.00 34.17
PERIMETER_BOT_ZN_4 0.00 88.67 0.00 49.67
PERIMETER_MID_ZN_3 2.50 0.00 0.33 0.00
PERIMETER_MID_ZN_2 5.33 18.67 0.00 18.67
PERIMETER_MID_ZN_1 1.17 31.33 0.00 30.33
PERIMETER_MID_ZN_4 0.83 32.50 0.00 19.00
PERIMETER_TOP_ZN_3 53.00 0.00 15.50 0.00
PERIMETER_TOP_ZN_2 29.00 19.50 2.33 19.00
PERIMETER_TOP_ZN_1 18.17 26.33 0.83 25.00
PERIMETER_TOP_ZN_4 12.17 31.00 0.33 17.33
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 58.50 936.50 15.50 503.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.22 149.60 6779.02 1.241 0.000 0.000 0.000
CORE_BOTTOM 55.88 134.35 6849.35 1.026 0.000 0.000 0.000
CORE_MID 55.88 134.35 6849.35 0.746 0.000 0.000 0.000
CORE_TOP 55.88 134.35 6849.35 0.705 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.02 16.87 860.00 0.917 0.018 0.000 0.000
PERIMETER_BOT_ZN_2 4.52 10.87 554.22 1.252 0.019 0.000 0.000
PERIMETER_BOT_ZN_1 7.02 16.87 860.02 1.436 0.018 0.000 0.000
PERIMETER_BOT_ZN_4 4.52 10.87 554.22 1.940 0.019 0.000 0.000
PERIMETER_MID_ZN_3 7.02 16.87 860.00 0.715 0.043 0.000 0.000
PERIMETER_MID_ZN_2 3.95 10.87 554.22 1.036 0.047 0.000 0.000
PERIMETER_MID_ZN_1 7.02 16.87 860.02 1.282 0.043 0.000 0.000
PERIMETER_MID_ZN_4 4.52 10.87 554.22 1.189 0.044 0.000 0.000
PERIMETER_TOP_ZN_3 7.02 16.87 860.00 0.716 0.053 0.000 0.000
PERIMETER_TOP_ZN_2 4.52 10.87 554.22 1.138 0.055 0.000 0.000
PERIMETER_TOP_ZN_1 7.02 16.87 860.02 1.291 0.053 0.000 0.000
PERIMETER_TOP_ZN_4 4.52 10.87 554.22 1.203 0.055 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.54 42.18 1911.37 28.890 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.22 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.95 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.54 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.22 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.95 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.54 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1031.21 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 48929021.12 0.00 48929021.12 0.00 48929021.12 37848132.68 4480.55 335.01 3944.44 0.00
CORE_BOTTOM 43006295.06 0.00 43006295.06 0.00 43006295.06 33990283.35 3780.12 117.99 4861.89 393.52
CORE_MID 0.30E+09 0.00 0.30E+09 0.00 0.30E+09 0.34E+09 4310.76 648.55 3800.69 145.32
CORE_TOP 28649984.55 0.00 28649984.55 0.00 28649984.55 33990283.35 4492.26 1179.84 3087.90 205.52
PERIMETER_BOT_ZN_3 4831703.84 0.00 4831703.84 189059.25 5020763.09 4267819.30 5037.46 180.67 3541.87 393.52
PERIMETER_BOT_ZN_2 4196674.59 0.00 4196674.59 126039.41 4322714.00 2750345.05 4920.83 156.96 3682.21 393.52
PERIMETER_BOT_ZN_1 7431104.13 0.00 7431104.13 189059.25 7620163.38 4267912.63 4769.71 166.15 3824.14 393.52
PERIMETER_BOT_ZN_4 6513842.17 0.00 6513842.17 126039.41 6639881.58 2750345.05 3974.07 141.96 4643.97 393.52
PERIMETER_MID_ZN_3 36654343.19 0.00 36654343.19 443394.83 37097738.02 42678193.03 4826.46 591.40 3342.14 145.32
PERIMETER_MID_ZN_2 34883757.86 0.00 34883757.86 295596.35 35179354.22 27503450.52 4950.48 662.57 3146.95 680.46
PERIMETER_MID_ZN_1 65025867.81 0.00 65025867.81 443394.83 65469262.64 42679126.28 4399.29 690.05 3670.67 145.32
PERIMETER_MID_ZN_4 39278563.66 0.00 39278563.66 295596.35 39574160.02 27503450.52 4650.94 822.28 3286.78 145.32
PERIMETER_TOP_ZN_3 3667628.50 0.00 3667628.50 550519.38 4218147.88 4267819.30 4396.53 1082.47 3280.99 205.52
PERIMETER_TOP_ZN_2 3724204.53 0.00 3724204.53 367012.67 4091217.19 2750345.05 4294.41 999.89 3465.70 205.52
PERIMETER_TOP_ZN_1 6543392.75 0.00 6543392.75 550519.38 7093912.13 4267912.63 4189.65 794.26 3776.09 205.52
PERIMETER_TOP_ZN_4 3974686.33 0.00 3974686.33 367012.67 4341698.99 2750345.05 4417.96 1356.58 2985.45 205.52
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.45E+09 0.00 0.45E+09 0.00 0.45E+09 10671554.30 9.00 60.17 8690.83 2816.67
Total Facility 0.54E+10 0.00 0.54E+10 17245085.19 0.55E+10 0.50E+10 6537.43 4380.11 8753.80 3352.11


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.2870 0.0000 2.2870 0.0000 2.2870 1.2002 1663.55 335.01 3944.44
CORE_BOTTOM 1.9087 0.0000 1.9087 0.0000 1.9087 1.0778 1292.44 114.15 4536.41
CORE_MID 13.8795 0.0000 13.8795 0.0000 13.8795 10.7782 1600.63 648.10 3694.28
CORE_TOP 1.3130 0.0000 1.3130 0.0000 1.3130 1.0778 1746.81 1179.82 3016.37
PERIMETER_BOT_ZN_3 0.2143 0.0000 0.2143 0.0043 0.2186 0.1353 2539.95 176.52 3226.53
PERIMETER_BOT_ZN_2 0.1887 0.0000 0.1887 0.0029 0.1916 0.0872 2424.12 152.29 3366.59
PERIMETER_BOT_ZN_1 0.3358 0.0000 0.3358 0.0043 0.3401 0.1353 2273.00 161.42 3508.58
PERIMETER_BOT_ZN_4 0.2921 0.0000 0.2921 0.0029 0.2950 0.0872 1482.61 138.94 4321.45
PERIMETER_MID_ZN_3 1.6740 0.0000 1.6740 0.0101 1.6841 1.3533 2117.28 590.80 3234.92
PERIMETER_MID_ZN_2 1.5631 0.0000 1.5631 0.0071 1.5703 0.8721 1754.37 660.62 2619.02
PERIMETER_MID_ZN_1 2.9997 0.0000 2.9997 0.0101 3.0098 1.3533 1690.38 689.56 3563.06
PERIMETER_MID_ZN_4 1.7925 0.0000 1.7925 0.0067 1.7992 0.8721 1941.51 821.66 3179.83
PERIMETER_TOP_ZN_3 0.1680 0.0000 0.1680 0.0125 0.1805 0.1353 1653.35 1082.29 3207.37
PERIMETER_TOP_ZN_2 0.1717 0.0000 0.1717 0.0083 0.1801 0.0872 1556.62 999.71 3386.67
PERIMETER_TOP_ZN_1 0.3022 0.0000 0.3022 0.0125 0.3147 0.1353 1449.50 794.04 3699.47
PERIMETER_TOP_ZN_4 0.1814 0.0000 0.1814 0.0083 0.1897 0.0872 1675.79 1356.43 2910.78
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 14.8593 0.0000 14.8593 0.0000 14.8593 0.3384 8.67 60.17 5874.17
Total Facility 242.4757 0.0000 242.4757 0.3961 242.8718 158.4706 3720.43 4372.75 5936.83


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 92961795.39 0.00 92961795.39 48026705.38 3497.28 7.95 5254.77 393.52
VAV_MID WITH REHEAT 0.68E+09 0.00 0.68E+09 0.48E+09 3931.06 4.16 4824.78 145.32
VAV_TOP WITH REHEAT 65600432.24 0.00 65600432.24 48026705.38 4034.03 7.52 4718.45 205.43
CAV_BAS 68938404.43 0.00 68938404.43 37848132.68 4479.00 0.13 4280.87 0.00
AIRLOOP DATACENTER BASEMENT 0.64E+09 0.00 0.64E+09 10671554.30 9.00 0.00 8751.00 2816.67
AIRLOOP DATACENTER BOT 344200.17 0.00 344200.17 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3442001.72 0.00 3442001.72 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 344200.17 0.00 344200.17 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 4.1418 0.0000 4.1418 1.5229 1054.17 5.31 4883.53
VAV_MID WITH REHEAT 30.9274 0.0000 30.9274 15.2292 1225.82 4.12 4713.05
VAV_TOP WITH REHEAT 3.0099 0.0000 3.0099 1.5229 1294.09 6.78 4642.13
CAV_BAS 3.2222 0.0000 3.2222 1.2002 1662.00 0.13 4280.87
AIRLOOP DATACENTER BASEMENT 20.9359 0.0000 20.9359 0.3384 8.67 0.00 5934.33
AIRLOOP DATACENTER BOT 0.0161 0.0000 0.0161 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1609 0.0000 0.1609 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0161 0.0000 0.0161 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 603.44 3935.92 0.00 0.00 0.00 781.09 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 346.13 3361.86 0.00 0.00 0.00 1248.53 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 30.21 3063.11 0.00 0.00 0.00 1925.17 0.00 0.00 0.00
CAV_BAS 0.00 328.40 3950.71 0.00 9.92 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 60.17 8690.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.8687 5.9334 0.0000 0.0000 0.0000 2.3932 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 28.5634 45.2857 0.0000 0.0000 0.0000 22.6828 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.8327 4.7501 0.0000 0.0000 0.0000 2.1985 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6930 4.7050 0.0000 1.0411 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4781 21.1770 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0220 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2203 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0220 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1515
Defaulted Fields 1185
Fields with Defaults 3880
Autosized Fields 335
Autosizable Fields 413
Autocalculated Fields 227
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
Electricity:Building 17146.87 216479.19 07-MAY-17:20 1025582.59 01-DEC-16:20
Electricity:Zone:BASEMENT 590.13 14055.89 01-JAN-00:10 28201.58 02-JAN-08:10
Electricity:SpaceType:GENERAL 17146.87 216479.19 07-MAY-17:20 1025582.59 01-DEC-16:20
InteriorLights:Electricity 2470.48 9223.03 23-APR-17:20 247210.90 02-JAN-16:30
InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2470.48 9223.03 23-APR-17:20 247210.90 02-JAN-16:30
LightsWired:InteriorLights:Electricity 2470.48 9223.03 23-APR-17:20 247210.90 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2470.48 9223.03 23-APR-17:20 247210.90 02-JAN-16:30
Electricity:Zone:CORE_BOTTOM 438.45 4990.59 01-JAN-00:10 30447.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:CORE_MID 4384.49 49905.77 01-JAN-00:10 304477.41 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
Electricity:Zone:CORE_TOP 438.45 4990.58 01-JAN-00:10 30447.74 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 47.32 603.11 19-MAR-17:10 3823.11 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.96 43.94 08-JAN-10:20 1662.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.96 43.94 08-JAN-10:20 1662.56 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_2 30.43 388.67 09-APR-17:10 2463.76 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.99 28.32 01-JAN-09:50 1071.42 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.99 28.32 01-JAN-09:50 1071.42 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_1 47.12 603.12 19-MAR-17:10 3823.18 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.75 43.94 01-JAN-09:40 1662.60 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.75 43.94 01-JAN-09:40 1662.60 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_4 30.41 388.67 19-MAR-17:10 2463.75 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.98 28.32 01-JAN-10:30 1071.42 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.98 28.32 01-JAN-10:30 1071.42 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_3 472.97 6031.15 19-MAR-17:10 38231.14 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 109.32 439.44 08-JAN-10:10 16625.62 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 109.32 439.44 08-JAN-10:10 16625.62 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_2 304.18 3886.70 09-APR-17:10 24637.60 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 69.83 283.19 01-JAN-09:50 10714.18 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 69.83 283.19 01-JAN-09:50 10714.18 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_1 471.10 6031.24 19-MAR-17:10 38231.83 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 107.44 439.45 01-JAN-09:40 16625.99 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 107.44 439.45 01-JAN-09:40 16625.99 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_4 304.03 3886.68 19-MAR-17:10 24637.51 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 69.68 283.19 01-JAN-10:20 10714.18 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 69.68 283.19 01-JAN-10:20 10714.18 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_3 47.30 603.11 19-MAR-17:10 3823.11 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.93 43.94 08-JAN-10:10 1662.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.93 43.94 08-JAN-10:10 1662.56 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_2 30.42 388.67 09-APR-17:10 2463.76 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.98 28.32 01-JAN-09:50 1071.42 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.98 28.32 01-JAN-09:50 1071.42 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_1 47.11 603.12 19-MAR-17:10 3823.18 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.74 43.94 01-JAN-09:40 1662.60 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.74 43.94 01-JAN-09:40 1662.60 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_4 30.40 388.67 19-MAR-17:10 2463.75 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.97 28.32 01-JAN-10:20 1071.42 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.97 28.32 01-JAN-10:20 1071.42 02-JAN-16:30
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7542.47 95139.07 01-JAN-00:10 383789.71 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1575.07 19661.97 01-JAN-00:10 81110.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1348.29 3835.18 16-JAN-05:50 405558.11 29-AUG-12:30
HeatRejection:Electricity 293.39 85.61 07-JAN-08:00 72883.01 27-APR-12:20
General:HeatRejection:Electricity 293.39 85.61 07-JAN-08:00 72883.01 27-APR-12:20
Electricity:HVAC 4034.61 52609.74 12-JAN-02:20 439625.18 29-AUG-15:20
ExteriorEquipment:Electricity 2566.28 20217.42 01-JAN-00:10 233396.85 28-DEC-08:20
Transformer:ExteriorEquipment:Electricity 54.68 979.82 01-JAN-00:10 3412.97 01-DEC-16:30
ElectricityPurchased:Facility 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
ElectricityPurchased:Plant 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
Cogeneration:ElectricityPurchased 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
General:Cogeneration:ElectricityPurchased 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
ElectricityNet:Plant 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
Cogeneration:ElectricityNet 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
General:Cogeneration:ElectricityNet 25397.81 294517.03 29-MAY-04:50 2044516.27 29-AUG-15:20
Fans:Electricity 2311.71 47439.98 02-JAN-05:50 277574.26 11-SEP-14:40
General:Fans:Electricity 2311.71 47439.98 02-JAN-05:50 277574.26 11-SEP-14:40
ExteriorLights:Electricity 356.44 0.00 01-JAN-08:10 40855.88 01-JAN-06:10
General:ExteriorLights:Electricity 356.44 0.00 01-JAN-08:10 40855.88 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 2505.76 19200.00 01-JAN-00:10 229608.34 02-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 951.53 1498.10 03-JAN-08:00 421316.31 29-AUG-14:30
General:Cooling:Electricity 951.53 1498.10 03-JAN-08:00 421316.31 29-AUG-14:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1043.98 0.00 11-JAN-20:10 100000.00 11-FEB-17:10
General:Humidifier:Electricity 1043.98 0.00 11-JAN-20:10 100000.00 11-FEB-17:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 438.44 0.00 01-JAN-00:10 52005.65 10-FEB-12:20
Water Heater:WaterSystems:Electricity 438.44 0.00 01-JAN-00:10 52005.65 10-FEB-12:20
Pumps:Electricity 289.18 3730.44 01-JAN-00:10 42585.91 20-JUL-12:20
General:Pumps:Electricity 289.18 3730.44 01-JAN-00:10 42585.91 20-JUL-12:20
WIRED_LTG_ELECTRICITY 69.42 0.00 01-JAN-00:10 6946.63 02-JAN-16:40
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1111.90 0.00 01-JAN-00:10 1281357.61 02-JAN-06:10
NaturalGas:Plant 1111.90 0.00 01-JAN-00:10 1281357.61 02-JAN-06:10
Heating:NaturalGas 1111.90 0.00 01-JAN-00:10 1281357.61 02-JAN-06:10
Boiler:Heating:NaturalGas 1111.90 0.00 01-JAN-00:10 1281357.61 02-JAN-06:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 5676.80 3686.43 03-JAN-08:00 2342686.28 29-AUG-14:30
PlantLoopCoolingDemand:HVAC 5676.80 3686.43 03-JAN-08:00 2342686.28 29-AUG-14:30
CoolingCoils:PlantLoopCoolingDemand 5676.80 3686.43 03-JAN-08:00 2342686.28 29-AUG-14:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 4562.02 0.00 12-JAN-01:20 0.00 10-AUG-16:00
Water:HVAC 388.36 0.00 11-JAN-20:10 0.00 13-FEB-05:10
Humidifier:Water 388.36 0.00 11-JAN-20:10 0.00 13-FEB-05:10
General:Humidifier:Water 388.36 0.00 11-JAN-20:10 0.00 13-FEB-05:10
MainsWater:Facility 4562.02 0.00 12-JAN-01:20 0.00 10-AUG-16:00
MainsWater:HVAC 388.36 0.00 11-JAN-20:10 0.00 13-FEB-05:10
Humidifier:MainsWater 388.36 0.00 11-JAN-20:10 0.00 13-FEB-05:10
General:Humidifier:MainsWater 388.36 0.00 11-JAN-20:10 0.00 13-FEB-05:10
Water:Plant 4173.66 0.00 01-JAN-00:10 0.00 10-AUG-16:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 4173.66 0.00 01-JAN-00:10 0.00 10-AUG-16:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 1893.49 0.00 01-JAN-00:10 0.00 10-AUG-16:00
General:HeatRejection:Water 1893.49 0.00 01-JAN-00:10 0.00 10-AUG-16:00
HeatRejection:MainsWater 1893.49 0.00 01-JAN-00:10 0.00 10-AUG-16:00
General:HeatRejection:MainsWater 1893.49 0.00 01-JAN-00:10 0.00 10-AUG-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 32352.12 96817.38 22-JAN-06:00 9079727.84 29-AUG-14:30
EnergyTransfer:Building 17156.41 88495.62 22-JAN-13:20 1622210.89 10-AUG-15:10
EnergyTransfer:Zone:BASEMENT 604.58 0.00 01-JAN-00:10 93444.35 13-NOV-07:10
Heating:EnergyTransfer 201.75 0.00 11-JAN-22:10 860366.09 02-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 201.75 0.00 11-JAN-22:10 860366.09 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 16954.65 87342.36 17-JAN-04:30 1622210.89 10-AUG-15:10
Cooling:EnergyTransfer:Zone:BASEMENT 604.58 0.00 01-JAN-00:10 93444.35 13-NOV-07:10
General:Cooling:EnergyTransfer 16954.65 87342.36 17-JAN-04:30 1622210.89 10-AUG-15:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 604.58 0.00 01-JAN-00:10 93444.35 13-NOV-07:10
EnergyTransfer:Zone:CORE_BOTTOM 581.38 0.00 01-JAN-00:10 52007.30 10-OCT-07:40
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 581.38 0.00 01-JAN-00:10 52007.30 10-OCT-07:40
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 581.38 0.00 01-JAN-00:10 52007.30 10-OCT-07:40
EnergyTransfer:Zone:CORE_MID 3925.78 0.00 01-JAN-00:10 409797.21 20-JUL-12:30
Heating:EnergyTransfer:Zone:CORE_MID 1.42 0.00 01-JAN-00:10 277920.64 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 1.42 0.00 01-JAN-00:10 277920.64 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 3924.37 0.00 01-JAN-00:10 409797.21 20-JUL-12:30
General:Cooling:EnergyTransfer:Zone:CORE_MID 3924.37 0.00 01-JAN-00:10 409797.21 20-JUL-12:30
EnergyTransfer:Zone:CORE_TOP 336.65 0.00 01-JAN-00:10 65807.71 02-JAN-05:20
Heating:EnergyTransfer:Zone:CORE_TOP 5.32 0.00 01-JAN-00:10 65807.71 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 5.32 0.00 01-JAN-00:10 65807.71 02-JAN-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 331.34 0.00 01-JAN-00:10 45764.24 10-AUG-15:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 331.34 0.00 01-JAN-00:10 45764.24 10-AUG-15:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 59.99 0.00 01-JAN-00:10 9687.31 24-JUL-14:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 59.99 0.00 01-JAN-00:10 9687.31 24-JUL-14:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 59.99 0.00 01-JAN-00:10 9687.31 24-JUL-14:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 51.48 0.00 01-JAN-00:10 15268.83 31-JUL-08:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 404.38 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 404.38 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 51.48 0.00 01-JAN-00:10 15268.83 31-JUL-08:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 51.48 0.00 01-JAN-00:10 15268.83 31-JUL-08:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 94.51 0.00 01-JAN-00:10 23683.61 04-OCT-12:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.04 0.00 01-JAN-00:10 5013.26 17-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.04 0.00 01-JAN-00:10 5013.26 17-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 94.47 0.00 01-JAN-00:10 23683.61 04-OCT-12:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 94.47 0.00 01-JAN-00:10 23683.61 04-OCT-12:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 85.08 0.00 01-JAN-00:10 18987.16 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 85.08 0.00 01-JAN-00:10 18987.16 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 85.08 0.00 01-JAN-00:10 18987.16 10-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 416.41 0.00 01-JAN-00:10 99674.01 02-JAN-05:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 26.30 0.00 01-JAN-00:10 99674.01 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 26.30 0.00 01-JAN-00:10 99674.01 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 390.11 0.00 01-JAN-00:10 84255.15 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 390.11 0.00 01-JAN-00:10 84255.15 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 418.23 0.00 01-JAN-00:10 155458.27 31-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 16.52 0.00 01-JAN-00:10 83248.13 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 16.52 0.00 01-JAN-00:10 83248.13 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 401.71 0.00 01-JAN-00:10 155458.27 31-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 401.71 0.00 01-JAN-00:10 155458.27 31-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 829.49 0.00 01-JAN-00:10 251006.94 04-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 15.73 0.00 01-JAN-00:10 125204.50 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 15.73 0.00 01-JAN-00:10 125204.50 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 813.76 0.00 01-JAN-00:10 251006.94 04-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 813.76 0.00 01-JAN-00:10 251006.94 04-OCT-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 484.01 0.00 01-JAN-00:10 169102.05 10-AUG-16:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 8.30 0.00 01-JAN-00:10 65654.99 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 8.30 0.00 01-JAN-00:10 65654.99 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 475.70 0.00 01-JAN-00:10 169102.05 10-AUG-16:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 475.70 0.00 01-JAN-00:10 169102.05 10-AUG-16:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.95 0.00 01-JAN-00:10 11589.71 02-JAN-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 12.58 0.00 01-JAN-00:10 11589.71 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 12.58 0.00 01-JAN-00:10 11589.71 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 33.37 0.00 01-JAN-00:10 9337.52 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 33.37 0.00 01-JAN-00:10 9337.52 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 45.91 0.00 01-JAN-00:10 15448.44 31-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 7.49 0.00 01-JAN-00:10 12394.30 17-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 7.49 0.00 01-JAN-00:10 12394.30 17-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 38.42 0.00 01-JAN-00:10 15448.44 31-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 38.42 0.00 01-JAN-00:10 15448.44 31-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 80.98 0.00 01-JAN-00:10 25609.16 04-OCT-13:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 8.47 0.00 01-JAN-00:10 18479.29 17-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 8.47 0.00 01-JAN-00:10 18479.29 17-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 72.52 0.00 01-JAN-00:10 25609.16 04-OCT-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 72.52 0.00 01-JAN-00:10 25609.16 04-OCT-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 48.14 0.00 01-JAN-00:10 17513.29 10-AUG-16:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 4.59 0.00 01-JAN-00:10 11366.82 17-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 4.59 0.00 01-JAN-00:10 11366.82 17-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 43.55 0.00 01-JAN-00:10 17513.29 10-AUG-16:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 43.55 0.00 01-JAN-00:10 17513.29 10-AUG-16:40
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 49.86 0.00 01-JAN-00:10 8745.81 14-AUG-13:50
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.45 0.00 01-JAN-00:10 3699.42 19-FEB-12:00
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.45 0.00 01-JAN-00:10 3699.42 19-FEB-12:00
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 48.41 0.00 01-JAN-00:10 8745.81 14-AUG-13:50
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 48.41 0.00 01-JAN-00:10 8745.81 14-AUG-13:50
EnergyTransfer:Zone:MIDFLOOR_PLENUM 316.42 0.00 01-JAN-00:10 83374.83 02-JAN-06:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 64.15 0.00 01-JAN-00:10 83374.83 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 64.15 0.00 01-JAN-00:10 83374.83 02-JAN-06:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 252.28 0.00 01-JAN-00:10 66595.22 10-AUG-15:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 252.28 0.00 01-JAN-00:10 66595.22 10-AUG-15:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 65.04 0.00 01-JAN-00:10 20319.47 17-JAN-05:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 26.59 0.00 01-JAN-00:10 20319.47 17-JAN-05:30
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 26.59 0.00 01-JAN-00:10 20319.47 17-JAN-05:30
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 38.45 0.00 01-JAN-00:10 18474.35 10-AUG-14:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 38.45 0.00 01-JAN-00:10 18474.35 10-AUG-14:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.52 755.92 16-JAN-06:00 8689.36 06-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.52 755.92 16-JAN-06:00 8689.36 06-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.52 755.92 16-JAN-06:00 8689.36 06-AUG-18:40
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1201.24 5.32 07-JAN-22:20 81573.52 06-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 2.05 0.00 02-JAN-14:10 5480.18 01-JAN-19:40
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 2.05 0.00 02-JAN-14:10 5480.18 01-JAN-19:40
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1199.19 0.00 01-JAN-00:10 81573.52 06-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1199.19 0.00 01-JAN-00:10 81573.52 06-AUG-18:40
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 110.06 0.39 07-JAN-09:10 8356.47 06-AUG-18:30
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.75 0.00 02-JAN-16:40 608.87 08-JAN-17:30
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.75 0.00 02-JAN-16:40 608.87 08-JAN-17:30
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 109.31 0.00 01-JAN-00:10 8356.47 06-AUG-18:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 109.31 0.00 01-JAN-00:10 8356.47 06-AUG-18:30
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.68 86523.86 17-JAN-05:00 368286.52 14-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.68 86523.86 17-JAN-05:00 368286.52 14-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.68 86523.86 17-JAN-05:00 368286.52 14-AUG-16:00
PlantLoopHeatingDemand:Facility 1261.17 0.00 01-JAN-00:10 1040787.00 02-JAN-06:10
PlantLoopHeatingDemand:Plant 433.10 0.00 01-JAN-00:10 51259.06 10-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 433.10 0.00 01-JAN-00:10 51259.06 10-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 433.10 0.00 01-JAN-00:10 51259.06 10-FEB-12:10
EnergyTransfer:HVAC 5880.62 2490.45 01-JAN-07:30 2180703.68 29-AUG-14:30
HeatingCoils:EnergyTransfer 828.07 0.00 01-JAN-00:10 1034592.08 02-JAN-06:10
PlantLoopHeatingDemand:HVAC 828.07 0.00 01-JAN-00:10 1034592.08 02-JAN-06:10
HeatingCoils:PlantLoopHeatingDemand 828.07 0.00 01-JAN-00:10 1034592.08 02-JAN-06:10
CoolingCoils:EnergyTransfer 5052.55 2188.33 03-JAN-08:00 2180703.68 29-AUG-14:30
EnergyTransfer:Plant 9315.09 0.00 01-JAN-00:10 5296720.41 29-AUG-14:30
LoopToLoop:EnergyTransfer 2567.16 0.00 01-JAN-00:10 1671997.13 29-AUG-14:30
WaterSystems:EnergyTransfer 433.10 0.00 01-JAN-00:10 51259.06 10-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 433.10 0.00 01-JAN-00:10 51259.06 10-FEB-12:10
Boilers:EnergyTransfer 820.57 0.00 01-JAN-00:10 1061145.29 02-JAN-06:10
Chillers:EnergyTransfer 2583.48 0.00 01-JAN-00:10 1669905.24 29-AUG-14:30
HeatRejection:EnergyTransfer 2910.77 0.00 01-JAN-00:10 1929238.95 29-AUG-14:30
General:HeatRejection:EnergyTransfer 2910.77 0.00 01-JAN-00:10 1929238.95 29-AUG-14:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -604.576 0.000 0.000 92.435 165.729 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -77.985
CORE_BOTTOM 0.000 0.000 0.000 -581.381 0.000 0.000 83.408 148.837 289.614 0.000 0.000 0.000 59.523 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 1.415 -3924.355 0.000 0.000 843.314 1488.366 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1304.868
CORE_TOP 0.000 0.000 5.316 -331.333 0.000 0.000 87.211 148.837 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -199.643
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -59.994 0.000 0.000 10.688 10.957 36.365 22.747 0.000 0.006 43.436 0.000 -61.227 0.000 -2.979 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.001 -51.478 0.000 0.000 6.898 6.994 23.435 45.371 0.000 0.004 9.178 0.000 -38.442 0.000 -1.961 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.045 -94.464 0.000 0.000 10.695 10.754 36.366 98.900 0.000 0.006 0.001 0.000 -57.573 0.000 -2.969 -1.760
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -85.080 0.000 0.000 6.762 6.979 23.435 48.064 0.000 0.004 46.502 0.000 -44.467 0.000 -2.199 0.000
PERIMETER_MID_ZN_3 0.000 0.000 26.303 -390.105 0.000 0.000 112.528 109.320 363.654 237.324 0.000 0.163 146.068 0.000 -543.305 0.000 -61.951 -0.003
PERIMETER_MID_ZN_2 0.000 0.000 16.523 -401.712 0.000 0.000 52.444 69.831 234.352 454.033 0.000 0.082 0.010 0.000 -354.820 0.000 -42.402 -28.331
PERIMETER_MID_ZN_1 0.000 0.000 15.731 -813.748 0.000 0.000 109.419 107.443 363.660 987.218 0.000 0.122 0.022 0.000 -549.683 0.000 -65.872 -154.290
PERIMETER_MID_ZN_4 0.000 0.000 8.304 -475.696 0.000 0.000 71.249 69.677 234.351 490.213 0.000 0.081 24.379 0.000 -378.429 0.000 -44.128 -0.002
PERIMETER_TOP_ZN_3 0.000 0.000 12.580 -33.369 0.000 0.000 11.504 10.931 36.365 24.390 0.000 0.018 0.000 0.000 -50.188 0.000 -7.148 -5.084
PERIMETER_TOP_ZN_2 0.000 0.000 7.495 -38.418 0.000 0.000 7.284 6.983 23.435 46.039 0.000 0.010 0.000 0.000 -32.856 0.000 -4.893 -15.079
PERIMETER_TOP_ZN_1 0.000 0.000 8.467 -72.515 0.000 0.000 11.178 10.744 36.366 99.504 0.000 0.014 0.000 0.000 -51.165 0.000 -7.636 -34.956
PERIMETER_TOP_ZN_4 0.000 0.000 4.593 -43.548 0.000 0.000 7.277 6.967 23.435 49.310 0.000 0.009 0.000 0.000 -35.449 0.000 -5.158 -7.435
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -138.521 0.000 0.000 0.950 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -19.936
DATACENTER_MID_ZN_6 0.000 0.000 2.051 -1199.184 0.000 0.000 9.503 36.263 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -387.439
DATACENTER_TOP_ZN_6 0.000 0.000 0.746 -109.314 0.000 0.000 0.952 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -49.891
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7166.682 0.000 0.000 20.565 47.611 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -396.351
GROUNDFLOOR_PLENUM 1.446 -48.410 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 53.283 0.000 0.000 0.000 -6.329 0.000
MIDFLOOR_PLENUM 64.150 -252.275 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.199 295.017 0.000 0.000 0.000 -107.092 -0.006
TOPFLOOR_PLENUM 26.592 -38.446 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.011 23.064 0.000 0.000 0.000 -11.221 -0.002
Total Facility 92.188 -339.131 109.569 -16615.475 0.000 0.000 1556.265 2470.476 14676.396 2603.112 0.000 0.741 700.484 0.000 -2197.605 0.000 -373.937 -2683.062


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 05-SEP-06:11 0.00 0.00 0.00 -108275.09 0.00 0.00 1492.95 4914.68 13457.54 0.00 0.00 0.00 88409.91 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 12-JUN-04:13 0.00 0.00 0.00 -89812.27 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 83337.26 0.00 -0.00 0.00 0.00 0.00
CORE_MID 28-AUG-04:11 0.00 0.00 0.00 -783309.00 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 718559.16 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 12-JUN-04:12 0.00 0.00 0.00 -73205.49 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 66730.51 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 23-JUL-18:31 0.00 0.00 0.00 -13931.17 0.00 0.00 0.00 43.94 559.17 5777.18 0.00 0.00 7583.55 0.00 -0.00 0.00 -32.67 0.00
PERIMETER_BOT_ZN_2 23-JUL-08:31 0.00 0.00 0.00 -24786.59 0.00 0.00 19.82 28.32 464.11 18968.83 0.00 0.00 5405.24 0.00 -0.00 0.00 -99.74 0.00
PERIMETER_BOT_ZN_1 08-OCT-13:01 0.00 0.00 0.00 -33337.67 0.00 0.00 33.21 43.94 720.19 27509.35 0.00 0.00 5137.29 0.00 -0.00 0.00 -106.33 0.00
PERIMETER_BOT_ZN_4 23-JUL-16:31 0.00 0.00 0.00 -32409.84 0.00 0.00 13.87 28.32 464.11 21676.67 0.00 0.00 10280.98 0.00 -0.00 0.00 -54.11 0.00
PERIMETER_MID_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -84252.60 0.00 0.00 11143.86 7910.47 21605.52 63649.80 0.00 364.75 0.00 0.00 -0.00 0.00 0.00 -20421.80
PERIMETER_MID_ZN_2 30-JUL-08:41 0.00 0.00 0.00 -265566.51 0.00 0.00 186.36 283.19 4641.14 187029.32 0.00 0.00 74588.04 0.00 -0.00 0.00 -1161.54 0.00
PERIMETER_MID_ZN_1 30-JUL-12:41 0.00 0.00 0.00 -346189.69 0.00 0.00 322.58 439.45 7201.95 223743.06 0.00 0.00 115212.01 0.00 -0.00 0.00 -729.36 0.00
PERIMETER_MID_ZN_4 23-JUL-17:11 0.00 0.00 0.00 -292758.06 0.00 0.00 0.00 283.19 3603.49 203661.88 0.00 0.00 86415.89 0.00 -0.00 0.00 -1206.39 0.00
PERIMETER_TOP_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -9337.32 0.00 0.00 1114.38 791.05 2160.55 6309.65 0.00 44.53 0.00 0.00 -0.00 0.00 0.00 -1082.84
PERIMETER_TOP_ZN_2 06-AUG-10:01 0.00 0.00 0.00 -24902.37 0.00 0.00 21.13 28.32 464.11 12532.70 0.00 0.00 12066.46 0.00 -0.00 0.00 -210.35 0.00
PERIMETER_TOP_ZN_1 10-SEP-12:21 0.00 0.00 0.00 -38300.81 0.00 0.00 28.71 43.94 720.19 28075.97 0.00 0.00 9665.70 0.00 -0.00 0.00 -233.72 0.00
PERIMETER_TOP_ZN_4 06-AUG-16:41 0.00 0.00 0.00 -30204.87 0.00 0.00 15.68 28.32 464.11 20832.50 0.00 0.00 9066.68 0.00 -0.00 0.00 -202.42 0.00
DATACENTER_BOT_ZN_6 06-AUG-18:41 0.00 0.00 0.00 -8697.08 0.00 0.00 0.00 17.59 7794.42 0.00 0.00 0.00 885.07 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 06-AUG-18:35 0.00 0.00 0.00 -81573.52 0.00 0.00 0.00 175.92 77944.22 0.00 0.00 0.00 3453.39 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 06-AUG-18:30 0.00 0.00 0.00 -8356.47 0.00 0.00 0.00 17.59 7794.42 0.00 0.00 0.00 544.45 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 14-AUG-16:00 0.00 0.00 0.00 -368288.73 0.00 0.00 2183.01 4157.19 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17683.99
GROUNDFLOOR_PLENUM 14-AUG-05:15 0.00 -10957.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10987.60 0.00 -0.00 0.00 -30.13 0.00
MIDFLOOR_PLENUM 14-JAN-05:11 0.00 -71686.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84485.78 0.00 -0.00 0.00 -12799.61 0.00
TOPFLOOR_PLENUM 10-AUG-14:40 0.00 -18475.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.18 18439.86 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-AUG-05:03 0.00 -3853.27 0.00 -1701343.98 0.00 0.00 15725.69 10593.62 616289.16 67981.12 0.00 0.00 1032213.46 0.00 -35591.71 0.00 -2014.09 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 02-JAN-05:11 0.00 0.00 324717.16 0.00 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -389466.99
CORE_TOP 02-JAN-05:11 0.00 0.00 70893.26 0.00 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -77368.24
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 09-JAN-06:01 0.00 0.00 2865.07 0.00 0.00 0.00 90.71 43.48 618.82 0.00 0.00 0.00 0.00 0.00 -3262.44 0.00 -39.61 -316.02
PERIMETER_BOT_ZN_1 17-JAN-05:01 0.00 0.00 10911.17 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -3670.43 0.00 -138.24 -7915.55
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 02-JAN-05:11 0.00 0.00 108380.52 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -21412.43 0.00 -4624.64 -90473.77
PERIMETER_MID_ZN_2 02-JAN-05:11 0.00 0.00 147436.88 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -14110.88 0.00 -3150.24 -135415.24
PERIMETER_MID_ZN_1 02-JAN-05:11 0.00 0.00 211916.05 0.00 0.00 0.00 0.00 674.72 7455.72 0.00 0.00 0.00 0.00 0.00 -21993.52 0.00 -4762.55 -193290.42
PERIMETER_MID_ZN_4 02-JAN-05:11 0.00 0.00 134600.95 0.00 0.00 0.00 0.00 434.81 4804.65 0.00 0.00 0.00 0.00 0.00 -15834.95 0.00 -3423.75 -120581.70
PERIMETER_TOP_ZN_3 16-JAN-08:33 0.00 0.00 12639.26 0.00 0.00 0.00 88.24 68.62 720.18 0.00 0.00 0.00 0.00 0.00 -2619.47 0.00 -682.34 -10214.48
PERIMETER_TOP_ZN_2 02-JAN-05:11 0.00 0.00 17388.60 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -1250.11 0.00 -372.78 -16289.65
PERIMETER_TOP_ZN_1 02-JAN-05:11 0.00 0.00 25756.96 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -1928.52 0.00 -558.10 -24083.39
PERIMETER_TOP_ZN_4 02-JAN-05:11 0.00 0.00 17458.48 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -1341.50 0.00 -380.69 -16260.24
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 01-JAN-19:15 0.00 0.00 5480.40 0.00 0.00 0.00 0.00 175.92 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25142.37
DATACENTER_TOP_ZN_6 08-JAN-17:30 0.00 0.00 608.88 0.00 0.00 0.00 5.58 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2580.66
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-04:01 11467.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -452.15 -11015.03
MIDFLOOR_PLENUM 30-JUL-16:01 129254.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1335.79 0.00 0.00 -0.00 0.00 0.00 -130590.58
TOPFLOOR_PLENUM 17-JAN-05:23 23646.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -499.27 -23146.98
Total Facility 02-JAN-05:11 -177627.79 177531.94 1077117.20 -177531.94 0.00 0.00 0.00 10593.62 232425.23 0.00 0.00 0.00 0.00 0.00 -90961.03 0.00 -28475.81 -1023071.41



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.8739 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.0167 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 104.3382 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 83.0698 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.4964 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.3122 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.1080 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.1080 0.2350 1.0000 Not calculated 1.2002 0.2350    
AIRLOOP DATACENTER BASEMENT 24.7998 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.7999 0.0136 1.0000 Not calculated 0.3384 0.0136    
AIRLOOP DATACENTER BOT 0.5042 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5042 0.0310 1.0000 Not calculated 0.0156 0.0310    
AIRLOOP DATACENTER MID 4.8421 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.8421 0.0323 1.0000 Not calculated 0.1563 0.0323    
AIRLOOP DATACENTER TOP 0.4914 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4914 0.0318 1.0000 Not calculated 0.0156 0.0318    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.4370 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2853 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 52.1691 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8288 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.2482 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2855 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 0.0000 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 0.0000 1.0000 1.0000 Not calculated 1.2002      
AIRLOOP DATACENTER BASEMENT 24.7998 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.7998 1.0000 1.0000 Not calculated 0.3384 0.0136    
AIRLOOP DATACENTER BOT 0.5042 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5042 1.0000 1.0000 Not calculated 0.0156 0.0310    
AIRLOOP DATACENTER MID 4.8421 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.8421 1.0000 1.0000 Not calculated 0.1563 0.0323    
AIRLOOP DATACENTER TOP 0.4914 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4914 1.0000 1.0000 Not calculated 0.0156 0.0318    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 5.1080 5.1080 0.0000 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4624 5.4624 1.6169 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 51.1302 51.1302 16.1571 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.9294 4.9294 1.6168 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8326 0.8326 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2748 1.2748 0.1313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7703 1.7703 0.2036 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5339 1.5339 0.1304 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.5871 7.5871 2.0333 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.3384 13.3384 1.3072 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 18.2695 18.2695 2.0279 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.0130 14.0130 1.3032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8539 0.8539 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3242 1.3242 0.1311 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9231 1.9231 0.2038 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4658 1.4658 0.1305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5042 0.5042 0.5042 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.8421 4.8421 4.8421 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4914 0.4914 0.4914 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.7998 24.7998 24.7998 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.8739 9.0167 10.8739 2.2853 0.0000 1.0000
VAV_MID WITH REHEAT 104.3382 83.0698 104.3382 22.8288 0.0000 1.0000
VAV_TOP WITH REHEAT 10.4964 9.3122 10.4964 2.2855 0.0000 1.0000
CAV_BAS 5.1080 5.1080 5.1080 0.0000 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.7998 24.7999 24.7998 24.7998 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5042 0.5042 0.5042 0.5042 0.0156 1.0000
AIRLOOP DATACENTER MID 4.8421 4.8421 4.8421 4.8421 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4914 0.4914 0.4914 0.4914 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 0.0000 0.0000 0.0000 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7312 2.7312 1.6169 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 25.5651 25.5651 16.1571 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4647 2.4647 1.6168 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4163 0.4163 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6374 0.6374 0.1313 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8851 0.8851 0.2036 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7669 0.7669 0.1304 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.7935 3.7935 2.0333 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.6692 6.6692 1.3072 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.1348 9.1348 2.0279 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.0065 7.0065 1.3032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4270 0.4270 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6621 0.6621 0.1311 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9616 0.9616 0.2038 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7329 0.7329 0.1305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5042 0.5042 0.5042 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.8421 4.8421 4.8421 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4914 0.4914 0.4914 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.7998 24.7998 24.7998 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.4370 2.2853 2.2853 2.2853 0.0000 1.0000
VAV_MID WITH REHEAT 52.1691 22.8288 22.8288 22.8288 0.0000 1.0000
VAV_TOP WITH REHEAT 5.2482 2.2855 2.2855 2.2855 0.0000 1.0000
CAV_BAS 0.0000 0.0000 0.0000 0.0000 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.7998 24.7998 24.7998 24.7998 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5042 0.5042 0.5042 0.5042 0.0156 1.0000
AIRLOOP DATACENTER MID 4.8421 4.8421 4.8421 4.8421 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4914 0.4914 0.4914 0.4914 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 15.50
Number of hours cooling loads not met 503.50
Number of hours not met 508.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1111.90 1281357.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 951.53 421316.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2470.48 247210.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 356.44 40855.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.68 3412.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 2505.76 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2311.71 277574.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 289.18 42585.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 293.39 72883.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1043.98 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 438.44 52005.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 25397.81
Natural Gas 0.00 1111.90
Additional 0.00 0.00
Total 14676.40 26509.71


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 53.33
Space Heating 0.00
Space Cooling 20.54
Fans (All) 49.91
Service Water Heating 9.47
Receptacle Equipment 316.85
Miscellaneous (All) 548.31
Subtotal 548.31


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 24.00
Service Water Heating 0.00
Miscellaneous (All) 24.00
Subtotal 24.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 9.32
Space Heating 4.19
Space Cooling 3.59
Fans (All) 8.72
Service Water Heating 1.65
Receptacle Equipment 55.36
Miscellaneous 17.16


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 675. 3744.
ELEVATOR_STANDBY_SCH 7740. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 767. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8292.83 467.17 0.00 0.00 0.00
CORE_BOTTOM 8721.50 38.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8759.17 0.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8730.83 29.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8721.50 38.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8448.00 312.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8730.50 29.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8716.83 43.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8690.67 69.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8759.50 0.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8732.17 27.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8722.33 37.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8697.50 62.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7885.17 874.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7850.17 909.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7830.33 929.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7355.33 1404.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8732.00 28.00 0.00 0.00 0.00
Min 7355.33 0.00 0.00 0.00 0.00
Max 8760.00 1404.67 0.00 0.00 0.00
Average 8529.41 230.59 0.00 0.00 0.00
Sum 196176.33 5303.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367136.00 1480.00 0.00 0.00 0.00
CORE_BOTTOM 330742.00 71.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1733.17 534.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1704.00 564.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1690.33 577.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 86139.83 17255.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367136.00 17255.17 0.00 0.00 0.00
Average 79444.36 890.55 0.00 0.00 0.00
Sum 1827220.33 20482.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8089.17 670.83 0.00 0.00 0.00
CORE_BOTTOM 8556.33 203.67 0.00 0.00 0.00
CORE_MID 8598.83 161.17 0.00 0.00 0.00
CORE_TOP 8673.33 86.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8747.83 12.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8726.50 33.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8699.67 60.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8389.67 370.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8753.33 6.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8710.00 50.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8681.50 78.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8631.33 128.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8752.33 7.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8717.17 42.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8693.17 66.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8653.00 107.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8493.83 266.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8474.67 285.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8470.17 289.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7767.50 992.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8721.83 38.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8756.17 3.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 8627.00 133.00 0.00 0.00 0.00
Min 7767.50 3.83 0.00 0.00 0.00
Max 8756.17 992.50 0.00 0.00 0.00
Average 8581.93 178.07 0.00 0.00 0.00
Sum 197384.33 4095.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 366490.17 2125.83 0.00 0.00 0.00
CORE_BOTTOM 330474.00 339.00 0.00 0.00 0.00
CORE_MID 330542.00 271.00 0.00 0.00 0.00
CORE_TOP 330637.00 176.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2080.83 187.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2065.33 202.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2062.00 206.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 90989.17 12405.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 366490.17 12405.83 0.00 0.00 0.00
Average 79643.02 691.89 0.00 0.00 0.00
Sum 1831789.50 15913.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:21:42

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.418551E+11 99070.82 02-JAN-07:05 6.20 5.35 0.567818E+10 7499.22 11-JAN-14:09 14.40 10.49
February 0.407121E+11 97020.67 28-FEB-07:11 10.60 9.82 0.515260E+10 7499.21 22-FEB-14:09 10.60 9.82
March 0.518875E+11 96019.99 20-MAR-06:05 6.70 4.63 0.615349E+10 7499.28 31-MAR-13:09 8.98 7.53
April 0.498482E+11 102046.60 03-APR-06:11 10.40 9.80 0.547080E+10 7499.30 27-APR-13:20 26.10 16.46
May 0.514077E+11 104221.64 30-MAY-06:11 10.77 9.90 0.592495E+10 7499.32 05-MAY-09:09 10.77 9.90
June 0.536825E+11 103391.10 05-JUN-06:11 11.30 9.68 0.590834E+10 7499.35 09-JUN-13:09 21.78 13.51
July 0.540318E+11 103938.26 03-JUL-06:11 12.07 8.59 0.550097E+10 7566.75 31-JUL-09:30 22.75 17.29
August 0.595172E+11 98693.28 07-AUG-06:11 13.60 12.49 0.616698E+10 7758.08 21-AUG-13:50 23.70 15.41
September 0.515454E+11 108289.39 05-SEP-06:11 10.93 9.52 0.547850E+10 7522.70 11-SEP-15:20 23.30 15.94
October 0.526268E+11 107636.21 10-OCT-06:11 12.03 10.85 0.569424E+10 7499.25 05-OCT-09:00 12.03 10.85
November 0.499762E+11 105127.67 06-NOV-07:11 12.20 8.87 0.563526E+10 7499.22 02-NOV-09:20 12.20 8.87
December 0.474900E+11 99735.73 26-DEC-07:03 -1.6 -1.6 0.548810E+10 7499.45 13-DEC-14:09 -1.6 -1.6
                     
Annual Sum or Average 0.604581E+12         0.682524E+11        
Minimum of Months 0.407121E+11 96019.99   -1.6 -1.6 0.515260E+10 7499.21   -1.6 -1.6
Maximum of Months 0.595172E+11 108289.39   13.60 12.49 0.616698E+10 7758.08   26.10 17.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.334244E+11 81888.98 02-JAN-05:11 6.10 5.29 0.506114E+10 6734.78 20-JAN-10:09 4.18 2.79
February 0.355499E+11 81830.01 27-FEB-05:12 6.50 5.53 0.460115E+10 6734.80 08-FEB-10:20 6.50 5.53
March 0.491668E+11 84394.40 13-MAR-04:11 6.30 5.39 0.550163E+10 6734.80 02-MAR-10:20 6.30 5.39
April 0.526250E+11 85509.77 17-APR-04:12 6.10 5.14 0.488345E+10 6734.78 27-APR-13:20 26.10 16.46
May 0.493511E+11 85886.66 01-MAY-04:12 12.20 10.35 0.528787E+10 6734.83 05-MAY-09:09 15.97 13.48
June 0.538781E+11 89813.94 12-JUN-04:13 14.80 13.61 0.527174E+10 6734.85 05-JUN-09:00 14.80 13.61
July 0.595811E+11 87992.45 10-JUL-04:13 13.30 11.94 0.489752E+10 6734.77 18-JUL-09:20 17.43 12.11
August 0.671640E+11 85104.43 22-AUG-04:12 12.00 10.91 0.549727E+10 6832.01 21-AUG-13:50 12.00 10.91
September 0.473682E+11 89444.21 05-SEP-04:12 11.33 9.63 0.488638E+10 6734.82 14-SEP-09:09 17.38 15.51
October 0.469884E+11 89795.70 10-OCT-04:12 12.20 11.04 0.508019E+10 6734.77 12-OCT-09:09 9.18 7.86
November 0.438620E+11 87812.82 06-NOV-05:12 10.77 8.10 0.503081E+10 6734.76 02-NOV-09:20 10.77 8.10
December 0.424227E+11 85213.59 04-DEC-05:12 3.70 1.47 0.490160E+10 6734.79 12-DEC-10:09 3.58 3.51
                     
Annual Sum or Average 0.581382E+12         0.609007E+11        
Minimum of Months 0.334244E+11 81830.01   3.70 1.47 0.460115E+10 6734.76   3.58 2.79
Maximum of Months 0.671640E+11 89813.94   14.80 13.61 0.550163E+10 6832.01   26.10 16.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.208055E+11 23919.56 12-JAN-17:00 7.20 5.41 0.471405E+10 6734.59 27-JAN-14:09 9.72 8.09
February 0.223967E+11 67754.35 28-FEB-06:02 10.60 9.74 0.446716E+10 6734.77 08-FEB-10:20 10.60 9.74
March 0.315615E+11 69520.65 03-MAR-06:02 6.60 6.18 0.545005E+10 6734.78 02-MAR-10:20 6.60 6.18
April 0.325993E+11 74168.15 29-APR-05:02 8.40 8.40 0.485728E+10 6734.80 14-APR-09:20 8.40 8.40
May 0.390245E+11 74452.72 01-MAY-04:12 12.20 10.35 0.527496E+10 6734.83 05-MAY-09:20 16.33 13.64
June 0.411186E+11 76226.49 12-JUN-04:12 14.80 13.61 0.526377E+10 6734.82 09-JUN-13:09 14.80 13.61
July 0.417308E+11 76852.43 17-JUL-04:12 14.23 12.63 0.489252E+10 6734.82 14-JUL-09:20 14.23 12.63
August 0.451830E+11 78340.42 28-AUG-04:11 15.40 14.02 0.549383E+10 6735.08 09-AUG-09:00 15.40 14.02
September 0.374759E+11 74675.92 25-SEP-04:12 13.30 13.30 0.487507E+10 6734.81 14-SEP-09:09 13.30 13.30
October 0.321627E+11 74001.68 06-OCT-05:02 11.10 10.49 0.504359E+10 6734.78 05-OCT-13:20 11.10 10.49
November 0.256061E+11 69705.18 07-NOV-06:02 12.12 9.85 0.494130E+10 6734.75 02-NOV-09:20 12.12 9.85
December 0.227722E+11 35889.06 07-DEC-06:02 4.27 2.78 0.470351E+10 6734.75 12-DEC-10:39 4.43 4.12
                     
Annual Sum or Average 0.392437E+12         0.599771E+11        
Minimum of Months 0.208055E+11 23919.56   4.27 2.78 0.446716E+10 6734.59   4.43 4.12
Maximum of Months 0.451830E+11 78340.42   15.40 14.02 0.549383E+10 6735.08   16.33 14.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150640E+11 16011.75 11-JAN-17:00 12.20 9.27 0.419091E+10 6482.97 12-JAN-14:00 7.20 5.88
February 0.163878E+11 27019.27 28-FEB-17:00 14.40 10.82 0.399943E+10 6734.55 28-FEB-14:20 14.40 10.82
March 0.234678E+11 29864.23 15-MAR-16:00 11.10 7.72 0.513297E+10 6734.70 09-MAR-14:30 11.10 7.72
April 0.270395E+11 68147.37 28-APR-05:03 11.10 9.92 0.472575E+10 6734.81 14-APR-09:20 11.10 9.92
May 0.348787E+11 68071.81 05-MAY-05:03 12.98 10.75 0.522287E+10 6734.81 05-MAY-09:20 16.33 13.64
June 0.392779E+11 73202.65 12-JUN-04:12 14.80 13.61 0.524443E+10 6734.82 09-JUN-13:09 14.80 13.61
July 0.412433E+11 71963.88 25-JUL-04:12 13.90 13.04 0.488243E+10 6734.81 11-JUL-09:20 13.90 13.04
August 0.440780E+11 72360.26 11-AUG-04:12 12.73 11.87 0.548203E+10 6735.06 09-AUG-09:00 12.73 11.87
September 0.324027E+11 68402.37 14-SEP-05:03 12.62 12.25 0.482424E+10 6734.79 14-SEP-09:20 17.57 15.54
October 0.240163E+11 36504.72 04-OCT-15:40 21.30 11.43 0.483120E+10 6734.71 05-OCT-09:20 12.43 7.97
November 0.179276E+11 24028.13 02-NOV-16:00 13.30 10.88 0.445861E+10 6734.63 02-NOV-13:20 13.30 10.88
December 0.155521E+11 16003.69 06-DEC-16:40 1.83 1.63 0.410282E+10 6540.01 06-DEC-14:00 1.83 1.63
                     
Annual Sum or Average 0.331336E+12         0.570977E+11        
Minimum of Months 0.150640E+11 16003.69   1.83 1.63 0.399943E+10 6482.97   1.83 1.63
Maximum of Months 0.440780E+11 73202.65   21.30 13.61 0.548203E+10 6735.06   17.57 15.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.230301E+10 2361.79 12-JAN-06:02 6.70 6.36 0.566520E+09 845.61 11-JAN-14:20 6.70 6.36
February 0.253117E+10 4659.47 27-FEB-15:30 19.70 12.30 0.538427E+09 845.62 27-FEB-10:20 19.70 12.30
March 0.387843E+10 5152.91 20-MAR-13:40 12.03 7.87 0.674110E+09 845.63 09-MAR-14:09 12.03 7.87
April 0.525674E+10 7448.05 27-APR-15:20 27.20 17.16 0.607467E+09 845.63 27-APR-13:20 27.20 17.16
May 0.605634E+10 7564.39 15-MAY-13:50 23.22 13.56 0.660076E+09 845.63 05-MAY-09:09 23.22 13.56
June 0.734779E+10 11276.83 12-JUN-04:12 14.80 13.61 0.661043E+09 845.64 09-JUN-13:09 14.80 13.61
July 0.864739E+10 13930.80 23-JUL-18:31 24.97 15.79 0.614755E+09 845.89 20-JUL-13:00 24.97 15.79
August 0.926285E+10 11059.87 14-AUG-05:03 15.37 13.48 0.689909E+09 873.67 21-AUG-13:50 23.70 15.41
September 0.518543E+10 8438.61 11-SEP-15:25 23.30 15.99 0.609424E+09 845.63 14-SEP-09:09 17.38 15.51
October 0.391926E+10 6103.68 10-OCT-05:03 12.20 11.22 0.626469E+09 845.63 12-OCT-09:09 9.18 7.86
November 0.300045E+10 4653.39 06-NOV-11:40 13.70 9.94 0.608797E+09 845.62 02-NOV-09:20 13.70 9.94
December 0.260546E+10 2827.27 29-DEC-13:30 11.10 9.04 0.574722E+09 845.61 14-DEC-14:09 11.10 9.04
                     
Annual Sum or Average 0.599943E+11         0.743172E+10        
Minimum of Months 0.230301E+10 2361.79   6.70 6.36 0.538427E+09 845.61   6.70 6.36
Maximum of Months 0.926285E+10 13930.80   27.20 17.16 0.689909E+09 873.67   27.20 17.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147669E+10 2875.71 05-JAN-09:25 1.10 0.98 0.366136E+09 544.95 20-JAN-10:09 4.18 2.79
February 0.179174E+10 4907.61 08-FEB-09:45 1.93 0.91 0.349972E+09 544.96 08-FEB-10:20 2.77 1.67
March 0.317120E+10 9407.21 14-MAR-08:55 7.80 5.89 0.434366E+09 544.96 02-MAR-10:09 7.80 5.89
April 0.482082E+10 12502.73 27-APR-08:30 16.95 12.18 0.391567E+09 544.96 20-APR-09:00 16.95 12.18
May 0.556990E+10 19910.37 14-MAY-08:32 15.93 11.13 0.425811E+09 544.97 15-MAY-09:00 18.90 13.25
June 0.699524E+10 21475.11 25-JUN-08:32 16.33 11.87 0.426278E+09 545.14 19-JUN-09:09 16.33 11.87
July 0.749962E+10 24785.51 23-JUL-08:31 18.53 13.73 0.396461E+09 546.43 31-JUL-09:50 23.12 17.56
August 0.818461E+10 22548.21 13-AUG-08:42 20.67 15.77 0.444569E+09 549.95 21-AUG-13:50 23.70 15.41
September 0.507691E+10 24016.70 10-SEP-08:31 15.53 13.26 0.393376E+09 544.97 14-SEP-09:09 17.38 15.51
October 0.331585E+10 10348.54 04-OCT-08:50 15.32 10.37 0.403102E+09 544.96 05-OCT-09:00 13.90 9.28
November 0.192636E+10 4415.06 15-NOV-09:10 6.78 5.27 0.387254E+09 544.95 15-NOV-10:20 7.40 5.77
December 0.164887E+10 3847.66 05-DEC-10:00 6.70 5.10 0.359920E+09 544.95 12-DEC-10:09 3.58 3.51
                     
Annual Sum or Average 0.514778E+11         0.477881E+10        
Minimum of Months 0.147669E+10 2875.71   1.10 0.91 0.349972E+09 544.95   2.77 1.67
Maximum of Months 0.818461E+10 24785.51   20.67 15.77 0.444569E+09 549.95   23.70 17.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.305049E+10 16607.66 20-JAN-13:05 6.70 4.72 0.569339E+09 845.64 11-JAN-14:09 6.70 4.72
February 0.460753E+10 29406.20 12-FEB-11:53 5.60 0.67 0.544402E+09 846.84 27-FEB-14:00 20.00 12.17
March 0.743753E+10 20344.15 01-MAR-13:30 11.15 5.98 0.672616E+09 846.94 01-MAR-14:00 13.30 7.37
April 0.882086E+10 23822.44 02-APR-14:02 19.18 11.40 0.606223E+09 846.62 27-APR-13:00 26.10 16.83
May 0.872264E+10 30381.21 07-MAY-13:02 20.68 16.03 0.659112E+09 845.67 15-MAY-13:09 22.88 13.76
June 0.933704E+10 21183.62 04-JUN-13:53 17.20 12.45 0.660901E+09 845.68 28-JUN-13:39 24.80 15.68
July 0.117040E+11 31021.73 23-JUL-13:52 27.80 16.97 0.615392E+09 846.64 31-JUL-13:00 28.30 18.92
August 0.137914E+11 30542.27 13-AUG-12:42 26.43 18.35 0.690513E+09 855.57 21-AUG-13:50 23.70 15.41
September 0.104567E+11 32470.92 10-SEP-12:31 20.20 13.87 0.611034E+09 921.79 11-SEP-14:50 23.22 15.82
October 0.809978E+10 33339.48 08-OCT-13:01 18.17 13.70 0.626028E+09 846.59 02-OCT-13:39 18.17 13.70
November 0.430100E+10 21802.03 11-NOV-12:53 6.70 5.18 0.601793E+09 845.64 15-NOV-10:20 7.40 5.77
December 0.413618E+10 28464.59 03-DEC-12:43 12.12 6.49 0.566916E+09 845.64 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.944651E+11         0.742427E+10        
Minimum of Months 0.305049E+10 16607.66   5.60 0.67 0.544402E+09 845.64   6.70 4.72
Maximum of Months 0.137914E+11 33339.48   27.80 18.35 0.690513E+09 921.79   28.30 18.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.197699E+10 5663.89 05-JAN-15:30 6.40 4.89 0.393539E+09 544.95 27-JAN-14:09 9.72 8.09
February 0.314472E+10 13009.60 28-FEB-06:02 10.60 9.74 0.369301E+09 544.95 08-FEB-10:20 10.60 9.74
March 0.616011E+10 15416.32 18-MAR-17:06 19.22 9.55 0.445112E+09 544.96 09-MAR-14:09 19.22 9.55
April 0.893264E+10 26376.70 02-APR-15:22 20.60 11.92 0.396291E+09 544.96 27-APR-13:39 26.10 16.65
May 0.786883E+10 30738.30 07-MAY-17:01 21.60 16.13 0.428336E+09 544.96 05-MAY-09:09 21.60 16.13
June 0.954392E+10 27429.59 18-JUN-16:52 17.20 12.22 0.427570E+09 544.97 28-JUN-13:39 24.80 15.68
July 0.128026E+11 32410.13 23-JUL-16:31 27.07 15.77 0.398196E+09 544.97 28-JUL-13:50 20.55 15.38
August 0.138673E+11 28932.76 06-AUG-16:51 23.40 15.11 0.446536E+09 552.00 21-AUG-13:50 23.70 15.41
September 0.720050E+10 30410.61 10-SEP-16:31 22.20 14.28 0.395941E+09 579.12 11-SEP-15:30 23.30 15.99
October 0.537008E+10 22793.61 08-OCT-13:42 19.63 14.09 0.411109E+09 544.96 05-OCT-09:00 19.63 14.09
November 0.413712E+10 14989.20 03-NOV-05:02 10.60 9.38 0.406697E+09 544.95 02-NOV-09:20 10.60 9.38
December 0.407583E+10 15583.63 04-DEC-05:11 3.70 1.47 0.396225E+09 544.96 13-DEC-14:09 7.10 5.11
                     
Annual Sum or Average 0.850806E+11         0.491485E+10        
Minimum of Months 0.197699E+10 5663.89   3.70 1.47 0.369301E+09 544.95   7.10 5.11
Maximum of Months 0.138673E+11 32410.13   27.07 16.13 0.446536E+09 579.12   26.10 16.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.786947E+09 1704.11 11-JAN-16:10 14.03 10.30 0.477348E+09 731.53 11-JAN-14:00 14.03 10.30
February 0.129029E+10 2174.24 28-FEB-15:00 13.90 10.81 0.457835E+09 845.60 28-FEB-14:50 13.90 10.81
March 0.232465E+10 3020.62 10-MAR-14:30 16.40 11.76 0.602873E+09 845.60 10-MAR-14:20 16.40 11.76
April 0.299634E+10 6066.39 27-APR-15:20 27.20 17.16 0.572809E+09 845.63 27-APR-13:20 27.20 17.16
May 0.460455E+10 6711.41 05-MAY-13:30 23.85 16.52 0.648262E+09 845.63 24-MAY-13:20 15.00 10.87
June 0.551605E+10 7261.87 21-JUN-15:30 24.70 15.68 0.656316E+09 845.64 09-JUN-13:09 24.70 15.68
July 0.618090E+10 8425.52 24-JUL-15:00 30.60 18.78 0.612007E+09 846.58 24-JUL-13:20 30.60 18.78
August 0.625546E+10 7988.82 25-AUG-14:00 27.40 18.74 0.686120E+09 846.39 25-AUG-13:20 27.40 18.74
September 0.391379E+10 6392.69 11-SEP-15:25 23.30 15.99 0.596569E+09 845.63 14-SEP-09:09 17.38 15.51
October 0.254488E+10 3757.83 04-OCT-15:00 21.70 11.49 0.576121E+09 845.62 05-OCT-13:20 16.10 10.57
November 0.165190E+10 2159.53 04-NOV-05:03 12.80 11.49 0.514196E+09 817.88 02-NOV-13:00 12.80 11.49
December 0.944945E+09 1617.01 29-DEC-16:10 10.40 8.63 0.466081E+09 706.34 29-DEC-14:00 10.40 8.63
                     
Annual Sum or Average 0.390107E+11         0.686654E+10        
Minimum of Months 0.786947E+09 1617.01   10.40 8.63 0.457835E+09 706.34   10.40 8.63
Maximum of Months 0.625546E+10 8425.52   30.60 18.78 0.686120E+09 846.58   30.60 18.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.433336E+09 1234.83 20-JAN-11:10 5.60 3.32 0.230249E+09 507.15 20-JAN-11:09 5.60 3.32
February 0.831160E+09 4339.39 27-FEB-11:05 14.37 10.03 0.230400E+09 548.49 08-FEB-11:09 14.37 10.03
March 0.198074E+10 9490.76 14-MAR-10:05 10.28 7.92 0.301441E+09 548.50 14-MAR-10:09 10.28 7.92
April 0.362628E+10 13283.24 27-APR-10:05 19.27 13.13 0.282327E+09 548.50 20-APR-10:09 19.27 13.13
May 0.483697E+10 23868.15 14-MAY-07:42 14.03 10.08 0.310187E+09 548.52 15-MAY-10:09 19.18 13.24
June 0.639220E+10 22909.34 25-JUN-08:52 16.70 12.03 0.313083E+09 548.51 07-JUN-10:09 16.70 12.03
July 0.669825E+10 26560.55 30-JUL-08:41 20.22 15.61 0.292706E+09 548.51 07-JUL-12:09 20.22 15.61
August 0.721439E+10 23971.41 13-AUG-09:22 21.80 16.25 0.327104E+09 552.48 09-AUG-10:09 21.80 16.25
September 0.440432E+10 21784.99 10-SEP-08:42 15.82 13.36 0.286674E+09 548.50 11-SEP-10:09 19.08 14.37
October 0.229466E+10 10400.80 04-OCT-10:05 17.48 10.97 0.282811E+09 548.51 05-OCT-10:09 14.08 9.36
November 0.920139E+09 4878.95 04-NOV-10:05 16.38 13.96 0.252308E+09 548.49 15-NOV-11:09 7.88 5.98
December 0.538531E+09 2821.23 05-DEC-11:05 8.58 5.53 0.228049E+09 546.04 05-DEC-11:09 8.58 5.53
                     
Annual Sum or Average 0.401710E+11         0.333734E+10        
Minimum of Months 0.433336E+09 1234.83   5.60 3.32 0.228049E+09 507.15   5.60 3.32
Maximum of Months 0.721439E+10 26560.55   21.80 16.25 0.327104E+09 552.48   21.80 16.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.205661E+10 16758.90 20-JAN-13:15 6.70 4.72 0.525391E+09 845.64 20-JAN-14:09 6.78 4.76
February 0.396335E+10 32118.37 12-FEB-12:22 5.85 0.79 0.512509E+09 846.31 27-FEB-14:00 20.00 12.17
March 0.649972E+10 21843.25 01-MAR-13:25 11.15 5.98 0.645068E+09 846.45 01-MAR-14:00 13.30 7.37
April 0.724223E+10 22391.00 02-APR-13:43 18.90 11.23 0.591805E+09 847.17 25-APR-13:20 15.77 9.31
May 0.799433E+10 32165.04 14-MAY-12:22 21.65 12.39 0.652021E+09 845.68 19-MAY-13:30 14.15 8.68
June 0.816538E+10 31305.73 11-JUN-13:02 21.78 15.29 0.656696E+09 845.68 28-JUN-13:30 24.70 15.69
July 0.100185E+11 34619.12 30-JUL-12:41 26.10 17.66 0.613194E+09 847.32 31-JUL-13:20 27.57 18.47
August 0.116869E+11 31833.92 13-AUG-12:42 26.43 18.35 0.688250E+09 847.60 09-AUG-13:20 26.43 18.35
September 0.102696E+11 33320.92 10-SEP-12:42 20.40 13.99 0.606094E+09 942.56 11-SEP-14:00 23.30 15.83
October 0.747151E+10 31841.22 08-OCT-13:12 18.53 13.81 0.606774E+09 863.42 04-OCT-13:20 18.53 13.81
November 0.325673E+10 32146.31 11-NOV-14:02 7.80 5.52 0.560814E+09 845.66 02-NOV-13:39 7.80 5.52
December 0.275073E+10 27290.38 03-DEC-13:32 12.20 6.14 0.519251E+09 845.65 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.813756E+11         0.717787E+10        
Minimum of Months 0.205661E+10 16758.90   5.85 0.79 0.512509E+09 845.64   6.78 4.76
Maximum of Months 0.116869E+11 34619.12   26.43 18.35 0.688250E+09 942.56   27.57 18.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.781327E+09 2270.37 05-JAN-15:40 6.30 4.80 0.320691E+09 541.90 05-JAN-14:00 6.30 4.80
February 0.134172E+10 8463.46 27-FEB-15:30 19.70 12.30 0.314343E+09 544.94 06-FEB-14:30 19.70 12.30
March 0.252192E+10 11118.87 14-MAR-16:00 17.20 10.94 0.406927E+09 544.95 09-MAR-14:30 17.20 10.94
April 0.394024E+10 16104.51 01-APR-17:05 26.52 12.40 0.380287E+09 544.96 13-APR-13:20 16.87 9.00
May 0.583034E+10 28424.58 07-MAY-17:01 21.60 16.13 0.421899E+09 544.96 24-MAY-13:20 15.00 10.87
June 0.637875E+10 27594.89 18-JUN-17:11 17.03 12.24 0.424825E+09 544.97 28-JUN-13:30 24.70 15.69
July 0.846327E+10 29276.63 23-JUL-17:11 26.50 15.70 0.396664E+09 544.96 28-JUL-13:50 20.55 15.38
August 0.804623E+10 25938.03 06-AUG-16:51 23.40 15.11 0.444554E+09 545.00 09-AUG-09:00 23.80 15.92
September 0.523710E+10 24850.86 10-SEP-16:42 22.20 14.22 0.390668E+09 585.90 11-SEP-15:30 23.30 15.99
October 0.268406E+10 12266.31 04-OCT-16:00 21.10 11.40 0.384743E+09 544.95 05-OCT-13:20 16.10 10.57
November 0.136727E+10 6324.78 04-NOV-15:30 20.55 15.94 0.347850E+09 544.94 02-NOV-13:20 20.55 15.94
December 0.978185E+09 3459.42 05-DEC-15:30 8.05 5.82 0.318453E+09 544.94 05-DEC-14:00 8.05 5.82
                     
Annual Sum or Average 0.475704E+11         0.455190E+10        
Minimum of Months 0.781327E+09 2270.37   6.30 4.80 0.314343E+09 541.90   6.30 4.80
Maximum of Months 0.846327E+10 29276.63   26.52 16.13 0.444554E+09 585.90   24.70 15.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294665E+09 1555.76 11-JAN-16:20 13.67 10.10 0.465935E+09 684.35 11-JAN-14:00 13.67 10.10
February 0.681704E+09 1984.66 28-FEB-15:00 13.90 10.81 0.437084E+09 817.49 28-FEB-14:00 13.90 10.81
March 0.164808E+10 2485.22 10-MAR-14:40 16.30 11.68 0.558772E+09 845.60 10-MAR-14:20 16.30 11.68
April 0.250059E+10 6632.66 27-APR-15:20 27.20 17.16 0.543944E+09 845.63 27-APR-13:20 27.20 17.16
May 0.417471E+10 7125.02 15-MAY-14:30 23.30 13.06 0.630558E+09 845.63 05-MAY-09:20 23.30 13.06
June 0.529522E+10 7862.29 21-JUN-15:30 24.70 15.68 0.648725E+09 845.64 09-JUN-13:09 24.70 15.68
July 0.611745E+10 9337.52 24-JUL-15:00 30.60 18.78 0.608538E+09 845.63 20-JUL-13:09 30.60 18.78
August 0.614117E+10 8520.46 09-AUG-14:40 28.17 18.42 0.680965E+09 845.67 09-AUG-09:00 28.17 18.42
September 0.349295E+10 6206.50 12-SEP-14:40 24.40 16.65 0.576727E+09 845.63 14-SEP-09:20 17.57 15.54
October 0.187884E+10 3537.12 04-OCT-15:20 21.50 11.47 0.534353E+09 845.61 05-OCT-13:20 16.10 10.57
November 0.857315E+09 1855.24 02-NOV-14:40 13.67 11.26 0.479650E+09 773.74 02-NOV-13:00 13.67 11.26
December 0.286665E+09 1476.00 29-DEC-16:10 10.40 8.63 0.449665E+09 663.94 29-DEC-14:00 10.40 8.63
                     
Annual Sum or Average 0.333694E+11         0.661492E+10        
Minimum of Months 0.286665E+09 1476.00   10.40 8.63 0.437084E+09 663.94   10.40 8.63
Maximum of Months 0.614117E+10 9337.52   30.60 18.78 0.680965E+09 845.67   30.60 18.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.281435E+09 1029.94 20-JAN-10:50 5.32 3.17 0.301755E+09 453.97 20-JAN-10:00 5.60 3.25
February 0.623717E+09 1555.13 27-FEB-15:40 19.60 12.34 0.295155E+09 544.93 27-FEB-14:00 19.60 12.34
March 0.164469E+10 6068.79 14-MAR-09:50 9.63 7.44 0.389043E+09 544.96 14-MAR-09:00 10.00 7.75
April 0.333103E+10 12271.57 27-APR-09:10 17.98 12.34 0.374488E+09 544.96 20-APR-09:00 17.98 12.34
May 0.469342E+10 23801.52 14-MAY-10:12 19.47 12.42 0.415484E+09 544.98 15-MAY-09:00 18.90 13.25
June 0.642183E+10 21615.52 25-JUN-09:12 17.07 12.34 0.423068E+09 544.97 09-JUN-13:09 17.07 12.34
July 0.681900E+10 23677.64 30-JUL-08:52 20.60 15.79 0.394739E+09 545.86 31-JUL-09:00 23.30 17.69
August 0.739449E+10 24902.13 06-AUG-10:01 17.23 13.62 0.442500E+09 545.98 14-AUG-09:00 21.10 15.94
September 0.427072E+10 24060.84 10-SEP-09:02 16.28 13.48 0.381386E+09 544.97 14-SEP-09:09 17.38 15.51
October 0.195462E+10 8426.86 04-OCT-09:20 16.13 10.66 0.365743E+09 544.96 05-OCT-09:00 13.90 9.28
November 0.665532E+09 1596.96 04-NOV-10:10 16.38 13.96 0.315977E+09 538.60 02-NOV-13:00 16.38 13.96
December 0.317660E+09 1101.42 05-DEC-10:40 7.77 5.32 0.293016E+09 474.82 05-DEC-10:50 8.03 5.37
                     
Annual Sum or Average 0.384182E+11         0.439236E+10        
Minimum of Months 0.281435E+09 1029.94   5.32 3.17 0.293016E+09 453.97   5.60 3.25
Maximum of Months 0.739449E+10 24902.13   20.60 15.79 0.442500E+09 545.98   23.30 17.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.126098E+10 14891.81 20-JAN-13:25 6.70 4.72 0.501405E+09 845.63 11-JAN-14:39 6.70 4.72
February 0.289544E+10 18535.84 27-FEB-14:20 18.87 11.68 0.486969E+09 845.64 08-FEB-10:20 18.87 11.68
March 0.527316E+10 20677.40 01-MAR-13:40 11.33 6.09 0.612676E+09 846.23 01-MAR-14:50 13.03 7.20
April 0.640291E+10 25267.72 02-APR-14:02 19.18 11.40 0.573249E+09 846.50 27-APR-13:00 26.10 16.83
May 0.743211E+10 34532.53 14-MAY-13:32 22.60 12.25 0.638143E+09 845.67 15-MAY-13:09 22.88 13.76
June 0.792154E+10 19762.41 11-JUN-15:13 22.43 15.08 0.649490E+09 845.67 09-JUN-13:09 22.43 15.08
July 0.991476E+10 33424.43 30-JUL-13:32 26.50 17.71 0.609794E+09 846.52 31-JUL-13:00 28.30 18.92
August 0.116244E+11 36033.95 06-AUG-13:21 22.15 15.53 0.684123E+09 847.51 29-AUG-13:39 29.43 20.04
September 0.968034E+10 38298.05 10-SEP-12:21 20.00 13.75 0.593086E+09 907.79 11-SEP-14:50 23.22 15.82
October 0.623772E+10 31519.92 08-OCT-13:12 18.53 13.81 0.578791E+09 846.12 04-OCT-13:00 18.53 13.81
November 0.214570E+10 19320.28 11-NOV-13:12 7.07 5.29 0.522513E+09 845.64 15-NOV-14:00 8.90 6.49
December 0.172744E+10 14453.75 05-DEC-12:30 10.30 6.13 0.491746E+09 845.65 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.725165E+11         0.694199E+10        
Minimum of Months 0.126098E+10 14453.75   6.70 4.72 0.486969E+09 845.63   6.70 4.72
Maximum of Months 0.116244E+11 38298.05   26.50 17.71 0.684123E+09 907.79   29.43 20.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.436617E+09 1794.11 05-JAN-15:30 6.40 4.89 0.308736E+09 521.18 05-JAN-16:19 5.37 4.14
February 0.911954E+09 7832.68 27-FEB-15:30 19.70 12.30 0.299141E+09 544.94 28-FEB-14:20 14.23 11.32
March 0.203275E+10 10828.53 14-MAR-16:00 17.20 10.94 0.382276E+09 544.94 15-MAR-13:20 11.83 7.46
April 0.354854E+10 18505.58 02-APR-15:22 20.60 11.92 0.365776E+09 544.96 27-APR-13:39 26.10 16.65
May 0.550932E+10 29865.19 14-MAY-16:51 22.80 11.74 0.413709E+09 544.96 15-MAY-13:09 22.88 13.76
June 0.622813E+10 28216.97 18-JUN-18:01 16.60 12.33 0.421404E+09 544.97 09-JUN-13:09 16.60 12.33
July 0.837619E+10 27722.38 23-JUL-16:41 26.88 15.68 0.395517E+09 544.96 20-JUL-13:09 26.88 15.68
August 0.798441E+10 30201.34 06-AUG-16:41 23.47 15.19 0.442796E+09 545.00 09-AUG-09:00 23.80 15.92
September 0.490915E+10 29096.56 10-SEP-16:21 22.20 14.33 0.382252E+09 562.68 11-SEP-15:30 23.30 15.99
October 0.220872E+10 12211.92 04-OCT-16:00 21.10 11.40 0.362880E+09 544.95 19-OCT-13:20 13.50 10.13
November 0.889182E+09 5762.47 04-NOV-15:30 20.55 15.94 0.323559E+09 544.93 08-NOV-14:00 9.40 8.82
December 0.513985E+09 2469.43 05-DEC-15:30 8.05 5.82 0.301856E+09 544.92 05-DEC-14:00 8.05 5.82
                     
Annual Sum or Average 0.435489E+11         0.439990E+10        
Minimum of Months 0.436617E+09 1794.11   6.40 4.89 0.299141E+09 521.18   5.37 4.14
Maximum of Months 0.837619E+10 30201.34   26.88 15.94 0.442796E+09 562.68   26.88 16.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.436795E+09 2228.07 12-JAN-06:10 6.70 6.36 0.00 0.00 01-JAN-00:10 6.70 6.36
February 0.110251E+10 4305.94 28-FEB-06:15 10.60 9.74 0.00 0.00 01-FEB-00:10 10.60 9.74
March 0.303773E+10 4887.41 20-MAR-05:15 5.97 4.27 0.00 0.00 01-MAR-00:10 5.97 4.27
April 0.453866E+10 6471.51 27-APR-14:40 26.83 17.14 0.00 0.00 01-APR-00:10 26.83 17.14
May 0.484157E+10 7024.38 08-MAY-05:15 9.60 9.49 0.00 0.00 01-MAY-00:10 9.60 9.49
June 0.628598E+10 10061.76 12-JUN-05:15 14.40 13.42 0.00 0.00 01-JUN-00:10 14.40 13.42
July 0.751801E+10 8438.91 31-JUL-14:10 28.30 18.91 0.00 0.00 01-JUL-00:10 28.30 18.91
August 0.838199E+10 10957.68 14-AUG-05:15 15.33 13.50 0.00 0.00 01-AUG-00:10 15.33 13.50
September 0.521757E+10 8940.36 05-SEP-05:15 10.77 9.27 0.00 0.00 01-SEP-00:10 10.77 9.27
October 0.362047E+10 8414.68 10-OCT-05:15 12.20 11.16 0.00 0.00 01-OCT-00:10 12.20 11.16
November 0.211266E+10 6703.56 06-NOV-06:15 11.47 8.44 0.00 0.00 01-NOV-00:10 11.47 8.44
December 0.131594E+10 3630.88 04-DEC-06:08 3.22 1.95 0.00 0.00 01-DEC-00:10 3.22 1.95
                     
Annual Sum or Average 0.484099E+11         0.00        
Minimum of Months 0.436795E+09 2228.07   3.22 1.95 0.00 0.00   3.22 1.95
Maximum of Months 0.838199E+10 10957.68   28.30 18.91 0.00 0.00   28.30 18.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101352E+09 7168.64 14-JAN-05:11 2.20 1.37 0.00 0.00 01-JAN-00:10 2.20 1.37
February 0.304998E+09 5813.95 18-FEB-05:01 -1.2 -2.4 0.00 0.00 01-FEB-00:10 -1.2 -2.4
March 0.737667E+09 5389.17 06-MAR-06:02 6.70 6.18 0.00 0.00 01-MAR-00:10 6.70 6.18
April 0.153526E+10 4290.57 27-APR-15:10 27.20 17.22 0.00 0.00 01-APR-00:10 27.20 17.22
May 0.288738E+10 4571.35 15-MAY-14:20 23.30 13.21 0.00 0.00 01-MAY-00:10 23.30 13.21
June 0.385906E+10 5162.88 28-JUN-15:30 26.10 15.92 0.00 0.00 01-JUN-00:10 26.10 15.92
July 0.477803E+10 6225.20 31-JUL-14:20 28.30 18.91 0.00 0.00 01-JUL-00:10 28.30 18.91
August 0.543812E+10 6659.52 10-AUG-15:00 30.20 18.90 0.00 0.00 01-AUG-00:10 30.20 18.90
September 0.340344E+10 6072.74 11-SEP-15:35 23.30 16.04 0.00 0.00 01-SEP-00:10 23.30 16.04
October 0.147191E+10 3745.80 04-OCT-15:40 21.30 11.43 0.00 0.00 01-OCT-00:10 21.30 11.43
November 0.472427E+09 6584.49 13-NOV-06:01 1.70 1.50 0.00 0.00 01-NOV-00:10 1.70 1.50
December 0.237939E+09 6754.66 26-DEC-05:01 -0.6 -0.6 0.00 0.00 01-DEC-00:10 -0.6 -0.6
                     
Annual Sum or Average 0.252276E+11         0.00        
Minimum of Months 0.101352E+09 3745.80   -1.2 -2.4 0.00 0.00   -1.2 -2.4
Maximum of Months 0.543812E+10 7168.64   30.20 18.91 0.00 0.00   30.20 18.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92 4.99 0.00 0.00 01-JAN-00:10 5.92 4.99
February 75732614.91 2854.15 27-FEB-15:30 19.70 12.30 0.00 0.00 01-FEB-00:10 19.70 12.30
March 0.653198E+09 5649.95 14-MAR-15:00 16.10 10.31 0.00 0.00 01-MAR-00:10 16.10 10.31
April 0.273604E+10 15301.62 27-APR-14:40 26.83 17.14 0.00 0.00 01-APR-00:10 26.83 17.14
May 0.513722E+10 15930.39 15-MAY-14:20 23.30 13.21 0.00 0.00 01-MAY-00:10 23.30 13.21
June 0.684514E+10 16049.18 28-JUN-14:20 25.37 15.62 0.00 0.00 01-JUN-00:10 25.37 15.62
July 0.891023E+10 17355.35 31-JUL-14:20 28.30 18.91 0.00 0.00 01-JUL-00:10 28.30 18.91
August 0.862367E+10 18474.35 10-AUG-14:40 29.93 18.99 0.00 0.00 01-AUG-00:10 29.93 18.99
September 0.434456E+10 14518.23 11-SEP-14:07 22.88 15.76 0.00 0.00 01-SEP-00:10 22.88 15.76
October 0.106131E+10 8830.17 04-OCT-14:50 21.60 11.48 0.00 0.00 01-OCT-00:10 21.60 11.48
November 60016470.09 3125.58 04-NOV-14:10 21.10 15.94 0.00 0.00 01-NOV-00:10 21.10 15.94
December 0.00 0.00 01-DEC-00:10 4.40 3.48 0.00 0.00 01-DEC-00:10 4.40 3.48
                     
Annual Sum or Average 0.384471E+11         0.00        
Minimum of Months 0.00 0.00   4.40 3.48 0.00 0.00   4.40 3.48
Maximum of Months 0.891023E+10 18474.35   29.93 18.99 0.00 0.00   29.93 18.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.309244E+10 1947.92 05-JAN-16:10 5.73 4.38 95230010.77 126.82 19-JAN-14:09 5.40 2.91
February 0.786249E+10 4033.73 07-FEB-16:50 7.30 3.84 86397220.64 126.83 24-FEB-10:00 13.30 12.07
March 0.142260E+11 7009.32 31-MAR-24:00 8.00 7.45 0.103237E+09 126.83 09-MAR-14:00 8.00 7.45
April 0.188705E+11 8154.66 26-APR-18:00 22.80 13.49 91605327.89 126.83 28-APR-09:00 11.70 11.07
May 0.437997E+10 3446.05 31-MAY-24:00 13.00 10.11 99236075.69 126.84 31-MAY-13:00 13.00 10.11
June 0.928446E+10 5322.30 30-JUN-24:00 15.50 12.58 98960960.82 126.84 12-JUN-13:00 15.50 12.58
July 0.148138E+11 7270.17 31-JUL-24:00 17.40 14.08 91884493.15 126.84 11-JUL-09:09 17.40 14.08
August 0.197736E+11 8697.08 06-AUG-18:41 22.13 15.01 0.103239E+09 126.83 02-AUG-09:00 22.13 15.01
September 0.430041E+10 3332.13 30-SEP-24:00 14.30 12.32 91611881.20 126.84 13-SEP-13:00 14.30 12.32
October 0.924846E+10 5051.92 31-OCT-24:00 9.10 7.85 95231783.80 126.83 26-OCT-13:00 9.10 7.85
November 0.136487E+11 5839.70 11-NOV-15:55 6.70 5.18 94301428.37 126.83 01-NOV-13:00 6.70 5.18
December 0.190202E+11 7754.83 05-DEC-15:50 6.75 4.97 91880905.38 126.82 28-DEC-14:00 11.10 9.78
                     
Annual Sum or Average 0.138521E+12         0.114282E+10        
Minimum of Months 0.309244E+10 1947.92   5.73 3.84 86397220.64 126.82   5.40 2.91
Maximum of Months 0.197736E+11 8697.08   22.80 15.01 0.103239E+09 126.84   22.13 15.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.818758E+09 1538.25 05-JAN-16:20 5.37 4.14 95064891.44 126.82 09-JAN-10:09 2.57 1.11
February 0.583989E+10 3705.58 07-FEB-17:00 7.20 3.36 86397173.31 126.83 24-FEB-10:00 13.30 12.07
March 0.124090E+11 6252.31 31-MAR-23:50 8.05 7.50 0.103237E+09 126.83 09-MAR-14:00 8.05 7.50
April 0.173167E+11 7786.17 26-APR-18:00 22.80 13.49 91605377.00 126.83 28-APR-13:09 16.97 14.14
May 0.367426E+10 3218.45 31-MAY-24:00 13.00 10.11 99235928.56 126.84 31-MAY-13:00 13.00 10.11
June 0.849034E+10 5001.88 30-JUN-24:00 15.50 12.58 98960733.63 126.84 12-JUN-13:00 15.50 12.58
July 0.139032E+11 6991.99 31-JUL-24:00 17.40 14.08 91884520.55 126.84 11-JUL-09:39 17.40 14.08
August 0.186988E+11 8157.35 06-AUG-18:35 22.47 15.07 0.103240E+09 126.83 02-AUG-09:00 22.47 15.07
September 0.363626E+10 2998.48 30-SEP-23:50 14.25 12.27 91611556.59 126.84 13-SEP-13:00 14.25 12.27
October 0.781939E+10 4251.72 31-OCT-24:00 9.10 7.85 95231692.67 126.83 26-OCT-13:00 9.10 7.85
November 0.113896E+11 5328.70 10-NOV-16:10 8.53 6.27 94301330.22 126.83 01-NOV-13:00 8.53 6.27
December 0.159223E+11 7168.58 05-DEC-16:00 6.10 4.53 91880925.02 126.82 28-DEC-14:00 11.10 9.78
                     
Annual Sum or Average 0.119919E+12         0.114265E+10        
Minimum of Months 0.818758E+09 1538.25   5.37 3.36 86397173.31 126.82   2.57 1.11
Maximum of Months 0.186988E+11 8157.35   22.80 15.07 0.103240E+09 126.84   22.47 15.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.262574E+09 1398.62 05-JAN-16:20 5.37 4.14 93079403.06 127.95 10-JAN-10:30 6.95 3.86
February 0.421815E+10 3580.71 08-FEB-17:00 6.70 3.26 86397292.98 126.83 24-FEB-10:00 13.30 12.07
March 0.110960E+11 5758.96 31-MAR-23:20 8.20 7.64 0.103237E+09 126.83 09-MAR-14:00 8.20 7.64
April 0.165506E+11 7851.74 26-APR-18:00 22.80 13.49 91605401.05 126.83 28-APR-13:09 16.97 14.14
May 0.318054E+10 3130.34 31-MAY-23:30 13.50 10.66 99235927.59 126.84 31-MAY-13:00 13.50 10.66
June 0.826932E+10 4910.45 30-JUN-23:40 15.63 12.81 98960766.18 126.84 12-JUN-13:00 15.63 12.81
July 0.137735E+11 6956.94 31-JUL-24:00 17.40 14.08 91884613.63 126.84 11-JUL-09:39 17.40 14.08
August 0.185509E+11 8356.47 06-AUG-18:30 22.80 15.13 0.103240E+09 126.83 02-AUG-09:00 22.80 15.13
September 0.313320E+10 2595.43 30-SEP-23:20 14.10 12.13 91611242.57 126.84 13-SEP-13:00 14.10 12.13
October 0.664148E+10 4162.74 04-OCT-16:50 20.68 11.37 95231648.87 126.83 26-OCT-13:00 13.30 12.35
November 0.969801E+10 5215.44 04-NOV-16:02 19.82 15.68 94301342.21 126.83 01-NOV-13:00 19.82 15.68
December 0.139400E+11 6971.48 05-DEC-16:00 6.10 4.53 91880939.65 126.82 28-DEC-14:00 11.10 9.78
                     
Annual Sum or Average 0.109314E+12         0.114066E+10        
Minimum of Months 0.262574E+09 1398.62   5.37 3.26 86397292.98 126.82   6.95 3.86
Maximum of Months 0.185509E+11 8356.47   22.80 15.68 0.103240E+09 127.95   22.80 15.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236639E+12 91053.20 12-JAN-17:00 7.20 5.41 0.206144E+10 2745.29 09-JAN-14:00 7.20 5.41
February 0.435158E+12 183297.66 27-FEB-17:00 18.90 12.17 0.187022E+10 2745.79 22-FEB-14:39 18.90 12.17
March 0.729110E+12 358391.21 31-MAR-24:00 8.00 7.45 0.223480E+10 2747.22 10-MAR-14:00 8.00 7.45
April 0.943176E+12 367369.74 27-APR-16:00 27.20 16.90 0.198320E+10 2750.82 28-APR-13:39 17.77 13.44
May 0.240803E+12 176106.82 31-MAY-24:00 13.00 10.11 0.214809E+10 2746.25 05-MAY-13:00 13.00 10.11
June 0.470149E+12 267641.67 30-JUN-24:00 15.50 12.58 0.214219E+10 2746.93 19-JUN-13:39 15.50 12.58
July 0.732173E+12 360243.33 31-JUL-24:00 17.40 14.08 0.198995E+10 2750.45 11-JUL-13:09 17.40 14.08
August 0.977459E+12 368286.52 14-AUG-16:00 27.50 16.95 0.223707E+10 2751.89 30-AUG-09:09 19.33 17.24
September 0.234656E+12 175662.23 30-SEP-24:00 14.30 12.32 0.198297E+10 2746.42 14-SEP-13:00 14.30 12.32
October 0.485787E+12 267221.64 31-OCT-24:00 9.10 7.85 0.206144E+10 2746.60 02-OCT-13:20 9.10 7.85
November 0.706788E+12 275762.42 06-NOV-17:00 11.70 10.80 0.204134E+10 2747.84 17-NOV-14:30 10.30 8.83
December 0.974784E+12 367135.29 04-DEC-17:00 6.70 4.39 0.198900E+10 2747.14 28-DEC-10:09 10.10 8.95
                     
Annual Sum or Average 0.716668E+13         0.247417E+11        
Minimum of Months 0.234656E+12 91053.20   6.70 4.39 0.187022E+10 2745.29   7.20 5.41
Maximum of Months 0.977459E+12 368286.52   27.50 16.95 0.223707E+10 2751.89   19.33 17.24



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141249E+09 32478.14 02-JAN-05:11 6.10
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 301710.29 2514.25 26-DEC-06:02 -0.8
         
Annual Sum or Average 0.141551E+09      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.141249E+09 32478.14   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237230E+10 70893.35 02-JAN-05:11 6.10
February 0.913900E+09 67356.87 21-FEB-04:51 1.70
March 0.166823E+09 61382.50 06-MAR-05:11 6.70
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 18943305.46 42834.02 30-OCT-05:03 7.20
November 0.578207E+09 63617.27 13-NOV-05:01 1.20
December 0.126581E+10 68935.49 26-DEC-04:01 -1.0
         
Annual Sum or Average 0.531599E+10      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 0.237230E+10 70893.35   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 735708.93 2865.07 09-JAN-06:01 -1.5
February 44034.49 513.74 18-FEB-06:01 -1.8
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 779743.42      
Minimum of Months 0.00 0.00   -1.8
Maximum of Months 735708.93 2865.07   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35328936.23 10911.09 17-JAN-05:01 1.60
February 4848860.87 7787.02 18-FEB-06:01 -1.8
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 4718770.39 7652.66 26-DEC-06:02 -0.8
         
Annual Sum or Average 44896567.49      
Minimum of Months 0.00 0.00   -1.8
Maximum of Months 35328936.23 10911.09   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124142E+10 10838.06 02-JAN-05:11 6.10
February 0.458056E+09 10036.73 21-FEB-05:01 1.70
March 53516804.95 9241.83 06-MAR-05:11 6.70
April 2339376.16 4897.74 19-APR-05:03 1.78
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 6739550.26 8683.39 30-OCT-05:03 7.20
November 0.174711E+09 9342.65 24-NOV-05:11 2.60
December 0.693564E+09 10280.80 26-DEC-04:01 -1.0
         
Annual Sum or Average 0.263034E+10      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 0.124142E+10 10838.06   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.765154E+09 14743.71 02-JAN-05:11 6.10
February 0.261691E+09 13124.04 21-FEB-05:01 1.70
March 26244604.76 11836.14 06-MAR-05:11 6.70
April 1721938.51 2903.80 19-APR-05:03 1.78
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 3130788.36 4156.50 31-OCT-05:03 8.58
November 0.120134E+09 12102.85 24-NOV-05:11 2.60
December 0.474178E+09 13131.10 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.165225E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.765154E+09 14743.71   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.768376E+09 21191.64 02-JAN-05:11 6.10
February 0.205853E+09 18072.01 21-FEB-05:01 1.70
March 16741387.19 16606.95 06-MAR-06:02 6.70
April 274826.83 1811.79 18-APR-05:03 3.30
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 315551.61 2103.68 28-OCT-05:03 8.22
November 0.105752E+09 17339.83 24-NOV-05:11 2.60
December 0.475779E+09 19115.54 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.157309E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.768376E+09 21191.64   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.443677E+09 13460.12 02-JAN-05:11 6.10
February 0.131070E+09 11677.97 21-FEB-05:01 1.70
March 5265128.82 10309.18 06-MAR-06:02 6.70
April 3170.03 21.13 19-APR-05:05 1.78
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 44425988.40 10670.21 13-NOV-06:01 1.70
December 0.205928E+09 12417.70 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.830370E+09      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.443677E+09 13460.12   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.406247E+10 12639.24 16-JAN-08:33 -0.8
February 0.234485E+10 12608.49 20-FEB-05:43 -0.6
March 0.806999E+09 12215.82 06-MAR-05:11 6.70
April 0.220335E+09 10522.66 18-APR-04:12 2.97
May 11133502.89 10104.44 18-MAY-05:02 5.60
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 5304347.25 6431.40 27-SEP-05:03 7.38
October 0.327166E+09 11191.70 30-OCT-04:11 7.20
November 0.152360E+10 12457.77 13-NOV-04:01 1.60
December 0.327768E+10 12614.67 26-DEC-03:43 -0.9
         
Annual Sum or Average 0.125795E+11      
Minimum of Months 0.00 0.00   -0.9
Maximum of Months 0.406247E+10 12639.24   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249681E+10 17388.48 02-JAN-05:11 6.10
February 0.128657E+10 17041.77 13-FEB-04:11 0.77
March 0.425873E+09 16955.27 06-MAR-05:11 6.70
April 0.109017E+09 13442.66 01-APR-05:02 7.38
May 7945624.37 13457.29 18-MAY-05:02 5.60
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 3434248.91 5303.33 27-SEP-05:03 7.38
October 0.194789E+09 14819.15 30-OCT-04:11 7.20
November 0.937688E+09 17104.05 13-NOV-04:01 1.60
December 0.203257E+10 17026.31 18-DEC-05:11 3.50
         
Annual Sum or Average 0.749470E+10      
Minimum of Months 0.00 0.00   0.77
Maximum of Months 0.249681E+10 17388.48   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.280327E+10 25756.80 02-JAN-05:11 6.10
February 0.134193E+10 25058.59 21-FEB-04:51 1.70
March 0.511113E+09 24870.86 06-MAR-05:11 6.70
April 0.157612E+09 19972.76 01-APR-05:02 7.38
May 12427638.19 20072.77 18-MAY-05:02 5.60
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 1602942.04 4091.56 27-SEP-05:03 7.38
October 0.193806E+09 21520.69 16-OCT-04:12 7.20
November 0.107114E+10 24921.39 24-NOV-05:11 2.60
December 0.237416E+10 25235.51 18-DEC-05:11 3.50
         
Annual Sum or Average 0.846706E+10      
Minimum of Months 0.00 0.00   1.70
Maximum of Months 0.280327E+10 25756.80   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171537E+10 17458.34 02-JAN-05:11 6.10
February 0.770106E+09 16978.39 21-FEB-04:51 1.70
March 0.246434E+09 16006.43 06-MAR-05:11 6.70
April 51111697.13 11422.89 01-APR-05:02 7.38
May 3914574.61 10516.30 18-MAY-05:02 5.60
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 81310269.58 10816.46 23-OCT-05:02 10.60
November 0.529240E+09 16128.85 24-NOV-05:11 2.60
December 0.119551E+10 17097.70 26-DEC-04:01 -1.0
         
Annual Sum or Average 0.459299E+10      
Minimum of Months 0.00 0.00   -1.0
Maximum of Months 0.171537E+10 17458.34   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.324628E+09 10480.22 02-JAN-05:11 6.10
February 0.117950E+09 9285.52 06-FEB-05:11 4.23
March 82300533.85 10211.78 06-MAR-05:11 6.70
April 0.140205E+09 11343.89 10-APR-04:12 9.63
May 93545833.58 10044.85 14-MAY-14:32 23.13
June 83254746.70 7862.96 26-JUN-04:12 12.80
July 0.136086E+09 11426.80 23-JUL-15:51 27.80
August 0.117312E+09 10740.70 06-AUG-15:31 23.77
September 64761931.71 10717.59 10-SEP-14:31 22.60
October 0.107591E+09 10065.82 08-OCT-13:42 19.63
November 91869293.83 11219.01 27-NOV-05:11 12.03
December 86698279.09 11462.87 26-DEC-04:01 -1.0
         
Annual Sum or Average 0.144620E+10      
Minimum of Months 64761931.71 7862.96   -1.0
Maximum of Months 0.324628E+09 11462.87   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.220670E+10 9163.81 02-JAN-06:10 6.10
February 0.118316E+10 11629.78 12-FEB-11:43 5.60
March 0.343383E+09 6165.86 29-MAR-05:02 4.40
April 70307726.00 8035.36 02-APR-15:02 20.60
May 77322100.43 12359.02 14-MAY-15:01 23.30
June 57711623.25 6619.62 25-JUN-16:12 21.70
July 73943878.79 12925.64 30-JUL-16:01 27.62
August 54308237.59 11265.02 06-AUG-15:31 23.77
September 50498304.03 11312.28 10-SEP-14:42 22.70
October 0.161038E+09 8724.94 29-OCT-14:23 11.70
November 0.754755E+09 9403.78 11-NOV-12:42 6.42
December 0.138169E+10 10284.13 03-DEC-13:32 12.20
         
Annual Sum or Average 0.641481E+10      
Minimum of Months 50498304.03 6165.86   4.40
Maximum of Months 0.220670E+10 12925.64   27.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.643962E+10 23646.26 17-JAN-05:23 1.40
February 0.403755E+10 20222.41 21-FEB-06:13 1.70
March 0.240894E+10 12610.03 06-MAR-06:02 6.70
April 0.118135E+10 11795.15 27-APR-05:03 9.37
May 0.623751E+09 12715.62 04-MAY-05:02 10.78
June 0.313184E+09 12944.40 02-JUN-05:03 10.18
July 0.182191E+09 11745.40 18-JUL-05:03 12.80
August 0.232286E+09 11847.22 21-AUG-05:03 11.20
September 0.613621E+09 12366.29 08-SEP-05:02 10.18
October 0.168044E+10 9824.95 05-OCT-05:03 8.30
November 0.338969E+10 16628.98 13-NOV-06:13 1.70
December 0.548872E+10 21895.92 26-DEC-05:12 -0.6
         
Annual Sum or Average 0.265914E+11      
Minimum of Months 0.182191E+09 9824.95   -0.6
Maximum of Months 0.643962E+10 23646.26   12.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.205091E+09 548.04 01-JAN-19:15 6.10
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.205091E+09      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.205091E+09 548.04   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.732074E+09 608.87 08-JAN-17:30 2.75
February 13755665.80 415.39 19-FEB-06:43 -5.1
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.745829E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.732074E+09 608.87   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:03 17.17
September 0.00 0.00 01-SEP-00:05 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 0.00 0.00   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.138227E+11 14744.03 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.125395E+11 14744.03 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.149226E+11 14744.03 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.133065E+11 14744.03 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.143726E+11 14744.03 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.143114E+11 14744.03 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.133677E+11 14744.03 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.149224E+11 14744.03 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.133065E+11 14744.03 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.138228E+11 14744.03 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.136668E+11 14744.03 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.133678E+11 14744.03 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.165729E+12     0.424397E+12    
Minimum of Months 0.125395E+11 14744.03   0.325565E+11 13457.54  
Maximum of Months 0.149226E+11 14744.03   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289614E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.63  
Maximum of Months 0.134015E+11 13241.18   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.107059E+10 1662.56 02-JAN-16:30 0.305979E+10 2160.55 02-JAN-08:09
February 0.875263E+09 1500.21 02-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.957407E+09 1306.38 22-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.811478E+09 927.82 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.854166E+09 852.96 17-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.835677E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.785076E+09 917.45 12-JUL-08:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.886656E+09 908.20 02-AUG-07:30 0.318369E+10 2160.55 01-AUG-07:10
September 0.837440E+09 1317.30 25-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.935264E+09 1640.38 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.103462E+10 1662.56 06-NOV-16:49 0.299314E+10 2160.55 01-NOV-07:10
December 0.107335E+10 1662.56 01-DEC-16:19 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.109570E+11     0.363654E+11    
Minimum of Months 0.785076E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.107335E+10 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.670623E+09 1071.42 02-JAN-16:30 0.197184E+10 1392.34 02-JAN-08:09
February 0.557062E+09 978.00 02-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.614091E+09 802.58 22-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.523113E+09 570.29 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.552959E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.541511E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.508427E+09 545.08 12-JUL-08:30 0.193969E+10 1392.34 03-JUL-07:10
August 0.573871E+09 567.93 02-AUG-07:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.535949E+09 812.37 25-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.594990E+09 1053.47 31-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.653254E+09 1071.42 06-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.668274E+09 1071.42 01-DEC-16:19 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.699412E+10     0.234352E+11    
Minimum of Months 0.508427E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.670623E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101677E+10 1662.60 02-JAN-16:30 0.305983E+10 2160.58 02-JAN-08:09
February 0.847322E+09 1461.58 02-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.947774E+09 1290.29 22-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.812166E+09 924.57 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.857820E+09 854.69 17-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.839761E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.791287E+09 909.06 12-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.891944E+09 906.16 02-AUG-07:30 0.318374E+10 2160.58 01-AUG-07:10
September 0.833442E+09 1305.23 25-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.914087E+09 1636.19 31-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.992688E+09 1662.60 06-NOV-16:49 0.299318E+10 2160.58 01-NOV-07:10
December 0.100932E+10 1662.60 01-DEC-16:19 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.107544E+11     0.363660E+11    
Minimum of Months 0.791287E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.101677E+10 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.670014E+09 1071.42 02-JAN-16:30 0.197183E+10 1392.33 02-JAN-08:09
February 0.552020E+09 940.18 02-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.613707E+09 856.72 22-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.522797E+09 718.61 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.550887E+09 566.83 17-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.538594E+09 556.42 29-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.507891E+09 742.06 12-JUL-07:30 0.193968E+10 1392.33 03-JUL-07:10
August 0.571974E+09 729.21 28-AUG-07:30 0.205168E+10 1392.33 01-AUG-07:10
September 0.538941E+09 862.04 25-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.595275E+09 1057.46 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.649974E+09 1071.42 06-NOV-16:49 0.192888E+10 1392.33 01-NOV-07:10
December 0.667421E+09 1071.42 01-DEC-16:19 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.697949E+10     0.234351E+11    
Minimum of Months 0.507891E+09 556.42   0.178514E+10 1392.33  
Maximum of Months 0.670014E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.106639E+10 1662.56 02-JAN-16:30 0.305979E+10 2160.55 02-JAN-08:09
February 0.872514E+09 1498.31 02-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.955370E+09 1302.48 22-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.810755E+09 922.45 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.853746E+09 843.30 17-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.835046E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.784186E+09 911.38 12-JUL-08:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.885875E+09 901.66 02-AUG-07:30 0.318369E+10 2160.55 01-AUG-07:10
September 0.835943E+09 1313.48 25-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.932711E+09 1640.12 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.103026E+10 1662.56 06-NOV-16:49 0.299314E+10 2160.55 01-NOV-07:10
December 0.106921E+10 1662.56 01-DEC-16:19 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.109320E+11     0.363654E+11    
Minimum of Months 0.784186E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.106921E+10 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.668928E+09 1071.42 02-JAN-16:30 0.197184E+10 1392.34 02-JAN-08:09
February 0.555876E+09 975.61 02-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.613022E+09 796.55 22-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.522684E+09 566.30 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.552553E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.541160E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.508155E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.573443E+09 563.39 02-AUG-07:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.535449E+09 806.55 25-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.593880E+09 1053.08 31-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.651506E+09 1071.42 06-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.666438E+09 1071.42 01-DEC-16:19 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.698309E+10     0.234352E+11    
Minimum of Months 0.508155E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.668928E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101555E+10 1662.60 02-JAN-16:30 0.305983E+10 2160.58 02-JAN-08:09
February 0.846317E+09 1459.28 02-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.946796E+09 1286.31 22-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.811608E+09 919.04 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.857211E+09 845.11 17-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.839358E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.790687E+09 902.62 12-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.891179E+09 899.52 02-AUG-07:30 0.318374E+10 2160.58 01-AUG-07:10
September 0.832730E+09 1301.33 25-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.913071E+09 1635.93 31-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.991647E+09 1662.60 06-NOV-16:49 0.299318E+10 2160.58 01-NOV-07:10
December 0.100817E+10 1662.60 01-DEC-16:19 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.107443E+11     0.363660E+11    
Minimum of Months 0.790687E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.101555E+10 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.668204E+09 1071.42 02-JAN-16:30 0.197183E+10 1392.33 02-JAN-08:09
February 0.551031E+09 936.80 02-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.612560E+09 851.14 22-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.522241E+09 709.30 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.550481E+09 561.71 17-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.538196E+09 550.71 29-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.507388E+09 732.72 12-JUL-07:30 0.193968E+10 1392.33 03-JUL-07:10
August 0.571503E+09 719.64 28-AUG-07:30 0.205168E+10 1392.33 01-AUG-07:10
September 0.538300E+09 856.59 25-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.594240E+09 1057.10 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.647998E+09 1071.42 06-NOV-16:49 0.192888E+10 1392.33 01-NOV-07:10
December 0.665537E+09 1071.42 01-DEC-16:19 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.696768E+10     0.234351E+11    
Minimum of Months 0.507388E+09 550.71   0.178514E+10 1392.33  
Maximum of Months 0.668204E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.106618E+10 1662.56 02-JAN-16:30 0.305979E+10 2160.55 02-JAN-08:09
February 0.872394E+09 1498.00 02-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.955230E+09 1301.75 22-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.810714E+09 922.24 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.853727E+09 842.92 17-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.835018E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.784167E+09 911.15 12-JUL-08:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.885817E+09 901.39 02-AUG-07:30 0.318369E+10 2160.55 01-AUG-07:10
September 0.835908E+09 1312.77 25-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.932626E+09 1640.08 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.103005E+10 1662.56 06-NOV-16:49 0.299314E+10 2160.55 01-NOV-07:10
December 0.106891E+10 1662.56 01-DEC-16:19 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.109307E+11     0.363654E+11    
Minimum of Months 0.784167E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.106891E+10 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.668825E+09 1071.42 02-JAN-16:30 0.197184E+10 1392.34 02-JAN-08:09
February 0.555832E+09 975.43 02-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.612974E+09 796.04 22-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.522708E+09 566.11 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.552539E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.541143E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.508150E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.573431E+09 563.18 02-AUG-07:30 0.205169E+10 1392.34 01-AUG-07:10
September 0.535448E+09 806.05 25-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.593959E+09 1053.04 31-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.651400E+09 1071.42 06-NOV-16:49 0.192889E+10 1392.34 01-NOV-07:10
December 0.666355E+09 1071.42 01-DEC-16:19 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.698276E+10     0.234352E+11    
Minimum of Months 0.508150E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.668825E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101545E+10 1662.60 02-JAN-16:30 0.305983E+10 2160.58 02-JAN-08:09
February 0.846278E+09 1458.92 02-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.946743E+09 1285.56 22-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.811558E+09 918.82 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.857185E+09 844.73 17-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.839339E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.790670E+09 902.37 12-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.891155E+09 899.25 02-AUG-07:30 0.318374E+10 2160.58 01-AUG-07:10
September 0.832697E+09 1300.60 25-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.913020E+09 1635.88 31-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.991583E+09 1662.60 06-NOV-16:49 0.299318E+10 2160.58 01-NOV-07:10
December 0.100806E+10 1662.60 01-DEC-16:19 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.107437E+11     0.363660E+11    
Minimum of Months 0.790670E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.101545E+10 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.668040E+09 1071.42 02-JAN-16:30 0.197183E+10 1392.33 02-JAN-08:09
February 0.550979E+09 936.53 02-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.612494E+09 850.69 22-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.522225E+09 708.59 03-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.550463E+09 561.51 17-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.538187E+09 550.49 29-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.507318E+09 732.12 12-JUL-07:30 0.193968E+10 1392.33 03-JUL-07:10
August 0.571491E+09 719.17 28-AUG-07:30 0.205168E+10 1392.33 01-AUG-07:10
September 0.538274E+09 856.15 25-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.594182E+09 1057.07 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.647902E+09 1071.42 06-NOV-16:49 0.192888E+10 1392.33 01-NOV-07:10
December 0.665300E+09 1071.42 01-DEC-16:19 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.696685E+10     0.234351E+11    
Minimum of Months 0.507318E+09 550.49   0.178514E+10 1392.33  
Maximum of Months 0.668040E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.397259E+10 4157.19 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.360343E+10 4157.19 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.428189E+10 4157.19 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.382459E+10 4157.19 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.412724E+10 4157.19 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.410728E+10 4157.19 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.384455E+10 4157.19 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.428189E+10 4157.19 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.382459E+10 4157.19 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.397259E+10 4157.19 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.392603E+10 4157.19 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.384455E+10 4157.19 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.476112E+11     0.749486E+13    
Minimum of Months 0.360343E+10 4157.19   0.246344E+12 94908.13  
Maximum of Months 0.428189E+10 4157.19   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.138227E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.143726E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.143114E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.133677E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.149224E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.138228E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.136668E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.133678E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.165729E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.107059E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.367566E+09
February 0.136985E+10 0.875263E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.327767E+09
March 0.163685E+10 0.957407E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.315011E+09
April 0.145243E+10 0.811478E+09 0.295462E+10 0.00 0.00 0.00 0.00 404540.49 0.297434E+09
May 0.157338E+10 0.854166E+09 0.312174E+10 0.00 0.00 0.00 0.00 17302.75 0.227485E+09
June 0.156900E+10 0.835677E+09 0.306580E+10 0.00 0.00 0.00 0.00 173865.07 0.188766E+09
July 0.145680E+10 0.785076E+09 0.300989E+10 0.00 0.00 0.00 0.00 2044530.23 0.155760E+09
August 0.163685E+10 0.886656E+09 0.318369E+10 0.00 0.00 0.00 0.00 3655159.61 0.125142E+09
September 0.145243E+10 0.837440E+09 0.295328E+10 0.00 0.00 0.00 0.00 17241.75 0.106193E+09
October 0.150991E+10 0.935264E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.252763E+09
November 0.149516E+10 0.103462E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.293863E+09
December 0.145680E+10 0.107335E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.320781E+09
                   
Annual Sum or Average 0.181194E+11 0.109570E+11 0.363654E+11 0.00 0.00 0.00 0.00 6312639.89 0.297853E+10
Minimum of Months 0.136985E+10 0.785076E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.106193E+09
Maximum of Months 0.163685E+10 0.107335E+10 0.318369E+10 0.00 0.00 0.00 0.00 3655159.61 0.367566E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.670623E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.242376E+09
February 0.882782E+09 0.557062E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.217660E+09
March 0.105485E+10 0.614091E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.206786E+09
April 0.936002E+09 0.523113E+09 0.190407E+10 0.00 0.00 0.00 0.00 268858.67 0.195211E+09
May 0.101394E+10 0.552959E+09 0.201177E+10 0.00 0.00 0.00 0.00 11534.73 0.152460E+09
June 0.101113E+10 0.541511E+09 0.197572E+10 0.00 0.00 0.00 0.00 115907.67 0.126089E+09
July 0.938820E+09 0.508427E+09 0.193969E+10 0.00 0.00 0.00 0.00 1084637.59 0.102534E+09
August 0.105485E+10 0.573871E+09 0.205169E+10 0.00 0.00 0.00 0.00 2368406.75 81986600.46
September 0.936002E+09 0.535949E+09 0.190321E+10 0.00 0.00 0.00 0.00 11493.80 71101229.47
October 0.973041E+09 0.594990E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.166715E+09
November 0.963541E+09 0.653254E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.190619E+09
December 0.938820E+09 0.668274E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.207022E+09
                   
Annual Sum or Average 0.116768E+11 0.699412E+10 0.234352E+11 0.00 0.00 0.00 0.00 3860839.20 0.196056E+10
Minimum of Months 0.882782E+09 0.508427E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 71101229.47
Maximum of Months 0.105485E+10 0.670623E+09 0.205169E+10 0.00 0.00 0.00 0.00 2368406.75 0.242376E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.101677E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.356352E+09
February 0.136988E+10 0.847322E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.330484E+09
March 0.163688E+10 0.947774E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.314410E+09
April 0.145246E+10 0.812166E+09 0.295467E+10 0.00 0.00 0.00 0.00 297036.40 0.297790E+09
May 0.157341E+10 0.857820E+09 0.312179E+10 0.00 0.00 0.00 0.00 17300.29 0.229470E+09
June 0.156904E+10 0.839761E+09 0.306585E+10 0.00 0.00 0.00 0.00 173856.28 0.190344E+09
July 0.145684E+10 0.791287E+09 0.300994E+10 0.00 0.00 0.00 0.00 1519704.34 0.158382E+09
August 0.163688E+10 0.891944E+09 0.318374E+10 0.00 0.00 0.00 0.00 3523114.80 0.128768E+09
September 0.145246E+10 0.833442E+09 0.295333E+10 0.00 0.00 0.00 0.00 17148.64 0.109683E+09
October 0.150994E+10 0.914087E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.255084E+09
November 0.149520E+10 0.992688E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.286370E+09
December 0.145684E+10 0.100932E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.311421E+09
                   
Annual Sum or Average 0.181198E+11 0.107544E+11 0.363660E+11 0.00 0.00 0.00 0.00 5548160.76 0.296856E+10
Minimum of Months 0.136988E+10 0.791287E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.109683E+09
Maximum of Months 0.163688E+10 0.101677E+10 0.318374E+10 0.00 0.00 0.00 0.00 3523114.80 0.356352E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.670014E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.258360E+09
February 0.882782E+09 0.552020E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.238532E+09
March 0.105485E+10 0.613707E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.231641E+09
April 0.936002E+09 0.522797E+09 0.190406E+10 0.00 0.00 0.00 0.00 155809.75 0.222930E+09
May 0.101394E+10 0.550887E+09 0.201175E+10 0.00 0.00 0.00 0.00 11534.36 0.164925E+09
June 0.101113E+10 0.538594E+09 0.197570E+10 0.00 0.00 0.00 0.00 115867.25 0.139898E+09
July 0.938820E+09 0.507891E+09 0.193968E+10 0.00 0.00 0.00 0.00 967033.77 0.122038E+09
August 0.105485E+10 0.571974E+09 0.205168E+10 0.00 0.00 0.00 0.00 2337646.54 0.100651E+09
September 0.936002E+09 0.538941E+09 0.190319E+10 0.00 0.00 0.00 0.00 11492.26 78580641.57
October 0.973041E+09 0.595275E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.185606E+09
November 0.963541E+09 0.649974E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.216312E+09
December 0.938820E+09 0.667421E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.239679E+09
                   
Annual Sum or Average 0.116768E+11 0.697949E+10 0.234351E+11 0.00 0.00 0.00 0.00 3599383.94 0.219915E+10
Minimum of Months 0.882782E+09 0.507891E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 78580641.57
Maximum of Months 0.105485E+10 0.670014E+09 0.205168E+10 0.00 0.00 0.00 0.00 2337646.54 0.258360E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.106639E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.729839E+09
February 0.136985E+10 0.872514E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.662118E+09
March 0.163685E+10 0.955370E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.653196E+09
April 0.145243E+10 0.810755E+09 0.295462E+10 0.00 0.00 0.00 0.00 1331495.76 0.629624E+09
May 0.157338E+10 0.853746E+09 0.312174E+10 0.00 0.00 0.00 0.00 28809.71 0.502666E+09
June 0.156900E+10 0.835046E+09 0.306580E+10 0.00 0.00 0.00 0.00 358102.02 0.417175E+09
July 0.145680E+10 0.784186E+09 0.300989E+10 0.00 0.00 0.00 0.00 5756887.68 0.348774E+09
August 0.163685E+10 0.885875E+09 0.318369E+10 0.00 0.00 0.00 0.00 8833281.62 0.283729E+09
September 0.145243E+10 0.835943E+09 0.295328E+10 0.00 0.00 0.00 0.00 30209.17 0.230797E+09
October 0.150991E+10 0.932711E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.522531E+09
November 0.149516E+10 0.103026E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.585881E+09
December 0.145680E+10 0.106921E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.628732E+09
                   
Annual Sum or Average 0.181194E+11 0.109320E+11 0.363654E+11 0.00 0.00 0.00 0.00 16338785.96 0.619506E+10
Minimum of Months 0.136985E+10 0.784186E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.230797E+09
Maximum of Months 0.163685E+10 0.106921E+10 0.318369E+10 0.00 0.00 0.00 0.00 8833281.62 0.729839E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.668928E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.487977E+09
February 0.649041E+09 0.555876E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.454594E+09
March 0.773965E+09 0.613022E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.448323E+09
April 0.688021E+09 0.522684E+09 0.190407E+10 0.00 0.00 0.00 0.00 630691.14 0.435890E+09
May 0.744847E+09 0.552553E+09 0.201177E+10 0.00 0.00 0.00 0.00 18048.00 0.346406E+09
June 0.742030E+09 0.541160E+09 0.197572E+10 0.00 0.00 0.00 0.00 229387.93 0.290040E+09
July 0.690839E+09 0.508155E+09 0.193969E+10 0.00 0.00 0.00 0.00 2221460.02 0.241575E+09
August 0.773965E+09 0.573443E+09 0.205169E+10 0.00 0.00 0.00 0.00 5123752.31 0.198587E+09
September 0.688021E+09 0.535449E+09 0.190321E+10 0.00 0.00 0.00 0.00 19311.77 0.160517E+09
October 0.715730E+09 0.593880E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.359730E+09
November 0.708685E+09 0.651506E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.394529E+09
December 0.690839E+09 0.666438E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.422033E+09
                   
Annual Sum or Average 0.858171E+10 0.698309E+10 0.234352E+11 0.00 0.00 0.00 0.00 8242651.17 0.424020E+10
Minimum of Months 0.649041E+09 0.508155E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.160517E+09
Maximum of Months 0.773965E+09 0.668928E+09 0.205169E+10 0.00 0.00 0.00 0.00 5123752.31 0.487977E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.101555E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.765569E+09
February 0.136988E+10 0.846317E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.730131E+09
March 0.163688E+10 0.946796E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.698459E+09
April 0.145246E+10 0.811608E+09 0.295467E+10 0.00 0.00 0.00 0.00 639982.70 0.665758E+09
May 0.157341E+10 0.857211E+09 0.312179E+10 0.00 0.00 0.00 0.00 28803.45 0.523501E+09
June 0.156904E+10 0.839358E+09 0.306585E+10 0.00 0.00 0.00 0.00 358073.59 0.431850E+09
July 0.145684E+10 0.790687E+09 0.300994E+10 0.00 0.00 0.00 0.00 3257207.39 0.365746E+09
August 0.163688E+10 0.891179E+09 0.318374E+10 0.00 0.00 0.00 0.00 7932436.71 0.302625E+09
September 0.145246E+10 0.832730E+09 0.295333E+10 0.00 0.00 0.00 0.00 29803.02 0.251412E+09
October 0.150994E+10 0.913071E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.570849E+09
November 0.149520E+10 0.991647E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.617414E+09
December 0.145684E+10 0.100817E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.663920E+09
                   
Annual Sum or Average 0.181198E+11 0.107443E+11 0.363660E+11 0.00 0.00 0.00 0.00 12246306.85 0.658723E+10
Minimum of Months 0.136988E+10 0.790687E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.251412E+09
Maximum of Months 0.163688E+10 0.101555E+10 0.318374E+10 0.00 0.00 0.00 0.00 7932436.71 0.765569E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.668204E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.504668E+09
February 0.882782E+09 0.551031E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.468336E+09
March 0.105485E+10 0.612560E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.462972E+09
April 0.936002E+09 0.522241E+09 0.190406E+10 0.00 0.00 0.00 0.00 342273.45 0.450792E+09
May 0.101394E+10 0.550481E+09 0.201175E+10 0.00 0.00 0.00 0.00 19179.96 0.361557E+09
June 0.101113E+10 0.538196E+09 0.197570E+10 0.00 0.00 0.00 0.00 238627.33 0.299081E+09
July 0.938820E+09 0.507388E+09 0.193968E+10 0.00 0.00 0.00 0.00 2160237.09 0.261751E+09
August 0.105485E+10 0.571503E+09 0.205168E+10 0.00 0.00 0.00 0.00 5287807.30 0.213034E+09
September 0.936002E+09 0.538300E+09 0.190319E+10 0.00 0.00 0.00 0.00 20133.94 0.170462E+09
October 0.973041E+09 0.594240E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.373886E+09
November 0.963541E+09 0.647998E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.408097E+09
December 0.938820E+09 0.665537E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.438134E+09
                   
Annual Sum or Average 0.116768E+11 0.696768E+10 0.234351E+11 0.00 0.00 0.00 0.00 8068259.07 0.441277E+10
Minimum of Months 0.882782E+09 0.507388E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.170462E+09
Maximum of Months 0.105485E+10 0.668204E+09 0.205168E+10 0.00 0.00 0.00 0.00 5287807.30 0.504668E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.106618E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.838415E+09
February 0.136985E+10 0.872394E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.749284E+09
March 0.163685E+10 0.955230E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.741243E+09
April 0.145243E+10 0.810714E+09 0.295462E+10 0.00 0.00 0.00 0.00 1712956.94 0.729770E+09
May 0.157338E+10 0.853727E+09 0.312174E+10 0.00 0.00 0.00 0.00 23381.88 0.598093E+09
June 0.156900E+10 0.835018E+09 0.306580E+10 0.00 0.00 0.00 0.00 387706.96 0.506289E+09
July 0.145680E+10 0.784167E+09 0.300989E+10 0.00 0.00 0.00 0.00 6173756.45 0.426576E+09
August 0.163685E+10 0.885817E+09 0.318369E+10 0.00 0.00 0.00 0.00 10060238.17 0.345672E+09
September 0.145243E+10 0.835908E+09 0.295328E+10 0.00 0.00 0.00 0.00 26052.82 0.271248E+09
October 0.150991E+10 0.932626E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.584257E+09
November 0.149516E+10 0.103005E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.652036E+09
December 0.145680E+10 0.106891E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.704623E+09
                   
Annual Sum or Average 0.181194E+11 0.109307E+11 0.363654E+11 0.00 0.00 0.00 0.00 18384093.22 0.714750E+10
Minimum of Months 0.136985E+10 0.784167E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.271248E+09
Maximum of Months 0.163685E+10 0.106891E+10 0.318369E+10 0.00 0.00 0.00 0.00 10060238.17 0.838415E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.668825E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.559760E+09
February 0.882782E+09 0.555832E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.510818E+09
March 0.105485E+10 0.612974E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.509586E+09
April 0.936002E+09 0.522708E+09 0.190407E+10 0.00 0.00 0.00 0.00 767032.24 0.507757E+09
May 0.101394E+10 0.552539E+09 0.201177E+10 0.00 0.00 0.00 0.00 15586.32 0.413268E+09
June 0.101113E+10 0.541143E+09 0.197572E+10 0.00 0.00 0.00 0.00 258460.13 0.352523E+09
July 0.938820E+09 0.508150E+09 0.193969E+10 0.00 0.00 0.00 0.00 2607700.00 0.295514E+09
August 0.105485E+10 0.573431E+09 0.205169E+10 0.00 0.00 0.00 0.00 6318482.63 0.241859E+09
September 0.936002E+09 0.535448E+09 0.190321E+10 0.00 0.00 0.00 0.00 17366.22 0.189226E+09
October 0.973041E+09 0.593959E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.403672E+09
November 0.963541E+09 0.651400E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.437732E+09
December 0.938820E+09 0.666355E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.471746E+09
                   
Annual Sum or Average 0.116768E+11 0.698276E+10 0.234352E+11 0.00 0.00 0.00 0.00 9984627.54 0.489346E+10
Minimum of Months 0.882782E+09 0.508150E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.189226E+09
Maximum of Months 0.105485E+10 0.668825E+09 0.205169E+10 0.00 0.00 0.00 0.00 6318482.63 0.559760E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.101545E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.872369E+09
February 0.136988E+10 0.846278E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.825030E+09
March 0.163688E+10 0.946743E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.802246E+09
April 0.145246E+10 0.811558E+09 0.295467E+10 0.00 0.00 0.00 0.00 742220.69 0.780104E+09
May 0.157341E+10 0.857185E+09 0.312179E+10 0.00 0.00 0.00 0.00 23375.62 0.625952E+09
June 0.156904E+10 0.839339E+09 0.306585E+10 0.00 0.00 0.00 0.00 387679.03 0.524659E+09
July 0.145684E+10 0.790670E+09 0.300994E+10 0.00 0.00 0.00 0.00 3793747.33 0.448078E+09
August 0.163688E+10 0.891155E+09 0.318374E+10 0.00 0.00 0.00 0.00 9449574.55 0.369608E+09
September 0.145246E+10 0.832697E+09 0.295333E+10 0.00 0.00 0.00 0.00 25776.05 0.299508E+09
October 0.150994E+10 0.913020E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.652587E+09
November 0.149520E+10 0.991583E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.690372E+09
December 0.145684E+10 0.100806E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.745298E+09
                   
Annual Sum or Average 0.181198E+11 0.107437E+11 0.363660E+11 0.00 0.00 0.00 0.00 14422373.26 0.763581E+10
Minimum of Months 0.136988E+10 0.790670E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.299508E+09
Maximum of Months 0.163688E+10 0.101545E+10 0.318374E+10 0.00 0.00 0.00 0.00 9449574.55 0.872369E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.668040E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.578708E+09
February 0.882782E+09 0.550979E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.535944E+09
March 0.105485E+10 0.612494E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.535720E+09
April 0.936002E+09 0.522225E+09 0.190406E+10 0.00 0.00 0.00 0.00 395786.19 0.531234E+09
May 0.101394E+10 0.550463E+09 0.201175E+10 0.00 0.00 0.00 0.00 15550.55 0.434850E+09
June 0.101113E+10 0.538187E+09 0.197570E+10 0.00 0.00 0.00 0.00 258424.11 0.364301E+09
July 0.938820E+09 0.507318E+09 0.193968E+10 0.00 0.00 0.00 0.00 2497616.71 0.320922E+09
August 0.105485E+10 0.571491E+09 0.205168E+10 0.00 0.00 0.00 0.00 6291091.97 0.260635E+09
September 0.936002E+09 0.538274E+09 0.190319E+10 0.00 0.00 0.00 0.00 17365.79 0.204150E+09
October 0.973041E+09 0.594182E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.429091E+09
November 0.963541E+09 0.647902E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.463444E+09
December 0.938820E+09 0.665300E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.499494E+09
                   
Annual Sum or Average 0.116768E+11 0.696685E+10 0.234351E+11 0.00 0.00 0.00 0.00 9475835.33 0.515849E+10
Minimum of Months 0.882782E+09 0.507318E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.204150E+09
Maximum of Months 0.105485E+10 0.668040E+09 0.205168E+10 0.00 0.00 0.00 0.00 6291091.97 0.578708E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.397259E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.360343E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.428189E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.382459E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.412724E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.410728E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.384455E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.428189E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.382459E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.397259E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.392603E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.384455E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.476112E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.360343E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.428189E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.790076E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.702207E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.667744E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 603209.56 0.625427E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2376.15 0.478327E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 136465.26 0.394533E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3395473.85 0.329309E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5867747.60 0.271584E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1349.17 0.225802E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.537619E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.623065E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.683695E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10006621.61 0.632939E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.225802E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5867747.60 0.790076E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.127437E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.116965E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.114017E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1480238.04 0.107318E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3691.86 0.841481E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 244933.62 0.691061E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7232666.74 0.576067E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10943681.29 0.478466E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1851.47 0.395764E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.918326E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.103566E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111499E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19907063.01 0.107092E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.395764E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10943681.29 0.127437E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.126890E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117255E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117877E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1052770.85 0.115777E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.944144E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70827.42 0.794058E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2373789.63 0.670636E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7740205.37 0.544761E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.432292E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.940433E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.102468E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109185E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11237593.27 0.112208E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.432292E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7740205.37 0.126890E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 14744.03 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 14744.03 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 14744.03 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 14744.03 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 14744.03 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 14744.03 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 14744.03 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 14744.03 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 14744.03 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 14744.03 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 14744.03 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 14744.03 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1662.56 02-JAN-16:30 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 601.99 28-JAN-04:00
February 2010.79 01-FEB-10:09 1500.21 02-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 564.11 16-FEB-04:00
March 2010.79 01-MAR-10:09 1306.38 22-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 528.78 28-MAR-24:00
April 2010.79 03-APR-09:09 927.82 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 44.57 01-APR-17:10 542.54 07-APR-24:00
May 2010.79 01-MAY-09:09 852.96 17-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 2.05 05-MAY-16:00 390.10 18-MAY-05:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 7.61 28-JUN-16:00 532.59 13-JUN-03:00
July 2010.79 03-JUL-09:09 917.45 12-JUL-08:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 46.46 23-JUL-16:00 271.52 02-JUL-04:00
August 2010.79 01-AUG-09:09 908.20 02-AUG-07:30 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 30.26 08-AUG-17:00 342.50 04-AUG-24:00
September 2010.79 01-SEP-09:09 1317.30 25-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 2.45 14-SEP-17:00 257.08 18-SEP-23:00
October 2010.79 02-OCT-09:09 1640.38 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 474.65 31-OCT-21:10
November 2010.79 01-NOV-09:09 1662.56 06-NOV-16:49 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 576.44 29-NOV-23:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:19 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 475.40 17-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   257.08  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 46.46   601.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:30 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 393.28 28-JAN-04:00
February 1295.83 01-FEB-10:09 978.00 02-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 366.88 16-FEB-04:00
March 1295.83 01-MAR-10:09 802.58 22-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 348.38 28-MAR-24:00
April 1295.83 03-APR-09:09 570.29 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 29.32 01-APR-17:10 356.58 07-APR-24:00
May 1295.83 01-MAY-09:09 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 1.37 05-MAY-16:00 255.87 18-MAY-05:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 5.07 28-JUN-16:00 347.90 13-JUN-03:00
July 1295.83 03-JUL-09:09 545.08 12-JUL-08:30 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 31.34 23-JUL-15:54 174.47 02-JUL-04:00
August 1295.83 01-AUG-09:09 567.93 02-AUG-07:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 20.17 08-AUG-17:00 222.63 11-AUG-04:00
September 1295.83 01-SEP-09:09 812.37 25-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 1.64 14-SEP-17:00 168.33 18-SEP-23:00
October 1295.83 02-OCT-09:09 1053.47 31-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 308.60 31-OCT-21:10
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 371.78 29-NOV-23:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:19 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 304.53 17-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   168.33  
Maximum of Months 1295.83   1071.42   1392.34   0.00 0.00 0.00 0.00 31.34   393.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1662.60 02-JAN-16:30 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 579.19 12-JAN-24:00
February 2010.83 01-FEB-10:09 1461.58 02-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 575.18 19-FEB-11:50
March 2010.83 01-MAR-10:09 1290.29 22-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 535.55 28-MAR-24:00
April 2010.83 03-APR-09:09 924.57 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 20.67 01-APR-17:10 542.95 07-APR-24:00
May 2010.83 01-MAY-09:09 854.69 17-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 2.05 05-MAY-16:00 382.55 22-MAY-24:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 7.61 28-JUN-16:00 520.99 13-JUN-03:00
July 2010.83 03-JUL-09:09 909.06 12-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 34.58 23-JUL-15:53 268.30 02-JUL-04:00
August 2010.83 01-AUG-09:09 906.16 02-AUG-07:30 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 30.26 08-AUG-17:00 350.29 11-AUG-04:00
September 2010.83 01-SEP-09:09 1305.23 25-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 2.45 14-SEP-17:00 252.04 18-SEP-23:00
October 2010.83 02-OCT-09:09 1636.19 31-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 459.30 31-OCT-21:10
November 2010.83 01-NOV-09:09 1662.60 06-NOV-16:49 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 555.26 29-NOV-23:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:19 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 439.61 02-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   252.04  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 34.58   579.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:30 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 424.15 28-JAN-04:00
February 1295.83 01-FEB-10:09 940.18 02-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 404.50 16-FEB-04:00
March 1295.83 01-MAR-10:09 856.72 22-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 392.60 28-MAR-24:00
April 1295.83 03-APR-09:09 718.61 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 11.98 01-APR-16:00 406.12 07-APR-24:00
May 1295.83 01-MAY-09:09 566.83 17-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 1.37 05-MAY-16:00 272.90 22-MAY-24:00
June 1295.83 01-JUN-09:09 556.42 29-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 5.07 28-JUN-16:00 387.18 13-JUN-03:00
July 1295.83 03-JUL-09:09 742.06 12-JUL-07:30 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 18.84 23-JUL-15:57 210.63 02-JUL-04:00
August 1295.83 01-AUG-09:09 729.21 28-AUG-07:30 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 20.17 08-AUG-17:00 277.65 04-AUG-24:00
September 1295.83 01-SEP-09:09 862.04 25-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 1.63 14-SEP-17:00 183.43 18-SEP-23:00
October 1295.83 02-OCT-09:09 1057.46 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 341.66 31-OCT-21:10
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:49 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 422.87 29-NOV-23:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:19 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 355.02 17-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   556.42   1392.33   0.00 0.00 0.00 0.00 0.00   183.43  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 20.17   424.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1662.56 02-JAN-16:30 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1232.62 12-JAN-24:00
February 2010.79 01-FEB-10:09 1498.31 02-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1131.81 16-FEB-04:00
March 2010.79 01-MAR-10:09 1302.48 22-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1094.55 28-MAR-24:00
April 2010.79 03-APR-09:09 922.45 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 160.21 01-APR-17:02 1146.66 07-APR-24:00
May 2010.79 01-MAY-09:09 843.30 17-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 4.29 05-MAY-16:00 843.87 18-MAY-04:55
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 16.92 28-JUN-16:00 1127.34 13-JUN-03:00
July 2010.79 03-JUL-09:09 911.38 12-JUL-08:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 142.24 23-JUL-14:00 571.82 02-JUL-04:00
August 2010.79 01-AUG-09:09 901.66 02-AUG-07:30 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 79.72 13-AUG-14:53 793.84 11-AUG-03:55
September 2010.79 01-SEP-09:09 1313.48 25-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 5.13 14-SEP-17:00 551.06 18-SEP-23:00
October 2010.79 02-OCT-09:09 1640.12 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 986.07 31-OCT-21:10
November 2010.79 01-NOV-09:09 1662.56 06-NOV-16:49 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1166.00 29-NOV-23:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:19 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 925.46 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   551.06  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 160.21   1232.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1071.42 02-JAN-16:30 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 817.46 12-JAN-24:00
February 1239.33 01-FEB-08:09 975.61 02-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 762.50 19-FEB-10:00
March 1239.33 01-MAR-08:09 796.55 22-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 752.26 28-MAR-24:00
April 1239.33 03-APR-07:10 566.30 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 73.46 01-APR-17:02 787.10 07-APR-24:00
May 1239.33 01-MAY-07:10 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 2.86 05-MAY-16:00 564.40 22-MAY-24:00
June 1239.33 01-JUN-07:10 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 11.28 28-JUN-16:00 754.79 13-JUN-03:00
July 1239.33 03-JUL-07:10 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 69.55 23-JUL-15:53 386.93 02-JUL-10:00
August 1239.33 01-AUG-07:10 563.39 02-AUG-07:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 46.42 08-AUG-17:00 541.13 11-AUG-03:55
September 1239.33 01-SEP-07:10 806.55 25-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 3.42 14-SEP-17:00 367.89 18-SEP-23:00
October 1239.33 02-OCT-07:10 1053.08 31-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 655.99 31-OCT-21:03
November 1239.33 01-NOV-07:10 1071.42 06-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 773.57 29-NOV-23:00
December 1239.33 01-DEC-08:09 1071.42 01-DEC-16:19 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 615.03 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   367.89  
Maximum of Months 1239.33   1071.42   1392.34   0.00 0.00 0.00 0.00 73.46   817.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1662.60 02-JAN-16:30 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1242.05 12-JAN-24:00
February 2010.83 01-FEB-10:09 1459.28 02-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1330.52 19-FEB-12:10
March 2010.83 01-MAR-10:09 1286.31 22-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1169.27 28-MAR-24:00
April 2010.83 03-APR-09:09 919.04 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 40.72 01-APR-16:00 1184.33 07-APR-24:00
May 2010.83 01-MAY-09:09 845.11 17-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 4.29 05-MAY-16:00 851.47 22-MAY-24:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 16.92 28-JUN-16:00 1125.76 13-JUN-03:00
July 2010.83 03-JUL-09:09 902.62 12-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 69.80 23-JUL-15:53 583.99 02-JUL-04:00
August 2010.83 01-AUG-09:09 899.52 02-AUG-07:30 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 69.63 08-AUG-17:00 825.82 11-AUG-03:55
September 2010.83 01-SEP-09:09 1301.33 25-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 5.13 14-SEP-17:00 557.80 18-SEP-23:00
October 2010.83 02-OCT-09:09 1635.93 31-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 989.58 31-OCT-21:10
November 2010.83 01-NOV-09:09 1662.60 06-NOV-16:49 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1171.03 29-NOV-23:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:19 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 952.42 02-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   557.80  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 69.80   1330.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:30 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 833.09 12-JAN-24:00
February 1295.83 01-FEB-10:09 936.80 02-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 766.26 16-FEB-04:00
March 1295.83 01-MAR-10:09 851.14 22-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 767.15 28-MAR-24:00
April 1295.83 03-APR-09:09 709.30 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 27.15 01-APR-16:00 789.11 07-APR-24:00
May 1295.83 01-MAY-09:09 561.71 17-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 2.86 05-MAY-16:00 578.53 22-MAY-24:00
June 1295.83 01-JUN-09:09 550.71 29-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 11.28 28-JUN-16:00 761.39 13-JUN-03:00
July 1295.83 03-JUL-09:09 732.72 12-JUL-07:30 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 61.56 23-JUL-13:53 409.23 02-JUL-04:00
August 1295.83 01-AUG-09:09 719.64 28-AUG-07:30 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 46.42 08-AUG-17:00 580.69 11-AUG-03:55
September 1295.83 01-SEP-09:09 856.59 25-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 3.42 14-SEP-17:00 376.33 18-SEP-23:00
October 1295.83 02-OCT-09:09 1057.10 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 668.38 31-OCT-21:10
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:49 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 789.47 29-NOV-23:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:19 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 630.73 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   550.71   1392.33   0.00 0.00 0.00 0.00 0.00   376.33  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 61.56   833.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1662.56 02-JAN-16:30 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1415.83 12-JAN-24:00
February 2010.79 01-FEB-10:09 1498.00 02-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1309.32 16-FEB-22:03
March 2010.79 01-MAR-10:09 1301.75 22-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1269.94 29-MAR-05:00
April 2010.79 03-APR-09:09 922.24 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 206.50 01-APR-17:02 1349.54 07-APR-24:00
May 2010.79 01-MAY-09:09 842.92 17-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 4.68 05-MAY-16:00 1005.30 22-MAY-24:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 19.86 28-JUN-16:00 1311.02 13-JUN-03:00
July 2010.79 03-JUL-09:09 911.15 12-JUL-08:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 147.88 23-JUL-13:52 665.52 02-JUL-04:00
August 2010.79 01-AUG-09:09 901.39 02-AUG-07:30 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 84.80 08-AUG-17:00 962.23 11-AUG-03:55
September 2010.79 01-SEP-09:09 1312.77 25-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 5.59 14-SEP-17:00 628.87 18-SEP-23:00
October 2010.79 02-OCT-09:09 1640.08 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1216.22 31-OCT-21:03
November 2010.79 01-NOV-09:09 1662.56 06-NOV-16:49 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1344.66 29-NOV-23:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:19 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1082.10 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   628.87  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 206.50   1415.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:30 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 937.88 12-JAN-24:00
February 1295.83 01-FEB-10:09 975.43 02-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 872.27 16-FEB-22:03
March 1295.83 01-MAR-10:09 796.04 22-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 866.43 28-MAR-24:00
April 1295.83 03-APR-09:09 566.11 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 91.11 01-APR-17:02 931.64 07-APR-24:00
May 1295.83 01-MAY-09:09 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 3.12 05-MAY-16:00 675.07 22-MAY-24:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 13.24 28-JUN-16:00 877.22 13-JUN-03:00
July 1295.83 03-JUL-09:09 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 54.26 23-JUL-16:04 452.79 02-JUL-09:40
August 1295.83 01-AUG-09:09 563.18 02-AUG-07:30 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 56.53 08-AUG-17:00 656.62 11-AUG-03:55
September 1295.83 01-SEP-09:09 806.05 25-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 3.73 14-SEP-17:00 419.97 18-SEP-23:00
October 1295.83 02-OCT-09:09 1053.04 31-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 810.08 31-OCT-21:03
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:49 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 891.48 29-NOV-23:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:19 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 719.80 22-DEC-22:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   419.97  
Maximum of Months 1295.83   1071.42   1392.34   0.00 0.00 0.00 0.00 91.11   937.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1662.60 02-JAN-16:30 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1425.42 12-JAN-24:00
February 2010.83 01-FEB-10:09 1458.92 02-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1448.74 19-FEB-12:20
March 2010.83 01-MAR-10:09 1285.56 22-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1355.93 28-MAR-24:00
April 2010.83 03-APR-09:09 918.82 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 48.78 01-APR-16:00 1402.03 07-APR-24:00
May 2010.83 01-MAY-09:09 844.73 17-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 4.68 05-MAY-16:00 1019.98 22-MAY-24:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 19.86 28-JUN-16:00 1308.13 13-JUN-03:00
July 2010.83 03-JUL-09:09 902.37 12-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 85.90 23-JUL-16:04 681.65 02-JUL-04:00
August 2010.83 01-AUG-09:09 899.25 02-AUG-07:30 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 84.80 08-AUG-17:00 1003.79 11-AUG-03:55
September 2010.83 01-SEP-09:09 1300.60 25-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 5.59 14-SEP-17:00 639.60 18-SEP-23:00
October 2010.83 02-OCT-09:09 1635.88 31-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1216.71 31-OCT-21:03
November 2010.83 01-NOV-09:09 1662.60 06-NOV-16:49 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1346.85 29-NOV-23:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:19 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1095.52 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   639.60  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 85.90   1448.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:30 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 967.40 12-JAN-24:00
February 1295.83 01-FEB-10:09 936.53 02-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 875.16 16-FEB-22:03
March 1295.83 01-MAR-10:09 850.69 22-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 891.42 28-MAR-24:00
April 1295.83 03-APR-09:09 708.59 03-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 32.52 01-APR-16:00 938.37 10-APR-21:10
May 1295.83 01-MAY-09:09 561.51 17-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 3.12 05-MAY-16:00 695.46 22-MAY-24:00
June 1295.83 01-JUN-09:09 550.49 29-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 13.24 28-JUN-16:00 889.67 13-JUN-03:00
July 1295.83 03-JUL-09:09 732.12 12-JUL-07:30 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 42.53 23-JUL-14:05 483.04 22-JUL-22:55
August 1295.83 01-AUG-09:09 719.17 28-AUG-07:30 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 56.53 08-AUG-17:00 707.03 11-AUG-03:55
September 1295.83 01-SEP-09:09 856.15 25-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 3.73 14-SEP-17:00 437.42 18-SEP-23:00
October 1295.83 02-OCT-09:09 1057.07 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 813.64 31-OCT-21:03
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:49 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 919.94 29-NOV-23:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:19 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 743.58 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   550.49   1392.33   0.00 0.00 0.00 0.00 0.00   437.42  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 56.53   967.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4157.19 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4157.19 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4157.19 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4157.19 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4157.19 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4157.19 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4157.19 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4157.19 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4157.19 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4157.19 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4157.19 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4157.19 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4157.19   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4157.19   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1299.70 28-JAN-04:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1208.60 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1128.35 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.25 01-APR-17:02 1144.78 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.55 05-MAY-16:00 843.81 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.25 28-JUN-15:00 1131.70 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91.50 23-JUL-15:51 569.73 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.02 13-AUG-15:00 737.92 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.15 14-SEP-17:00 533.56 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1015.30 31-OCT-21:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1230.41 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1013.09 17-DEC-21:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   533.56  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91.50   1299.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2185.88 28-JAN-04:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2026.22 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1931.57 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.21 01-APR-17:02 1987.05 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.56 05-MAY-16:00 1494.33 18-MAY-04:55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.37 28-JUN-15:00 1968.75 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 200.07 23-JUL-15:51 989.74 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.65 13-AUG-15:10 1334.01 11-AUG-03:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.76 14-SEP-17:00 926.39 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1730.48 31-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2050.47 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1625.88 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   926.39  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 200.07   2185.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2233.63 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2014.74 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1987.92 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 165.00 01-APR-17:02 2143.52 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1534.33 22-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.62 28-JUN-17:00 2034.33 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.20 24-JUL-14:05 1030.00 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.94 08-AUG-17:00 1488.21 11-AUG-03:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:05 967.51 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1844.73 31-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2098.87 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1705.45 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   967.51  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 165.00   2233.63  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 99070.82 02-JAN-07:05 7180.90 9829.36 26915.09 0.00 0.00 0.00 0.00 0.00 0.00
February 97020.67 28-FEB-07:11 25133.15 34402.75 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 96019.99 20-MAR-06:05 7180.90 9829.36 26915.09 0.00 0.00 0.00 0.00 0.00 0.00
April 102046.60 03-APR-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
May 104221.64 30-MAY-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
June 103391.10 05-JUN-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
July 103938.26 03-JUL-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
August 98693.28 07-AUG-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
September 108289.39 05-SEP-06:11 35904.50 49146.78 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
October 107636.21 10-OCT-06:11 35904.50 49146.78 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
November 105127.67 06-NOV-07:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
December 99735.73 26-DEC-07:03 10771.35 14744.03 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 96019.99   7180.90 9829.36 26915.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 108289.39   35904.50 49146.78 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 81888.98 02-JAN-05:11 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
February 81830.01 27-FEB-05:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
March 84394.40 13-MAR-04:11 0.00 4836.24 53438.81 0.00 0.00 0.00 0.00 0.00 0.00
April 85509.77 17-APR-04:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
May 85886.66 01-MAY-04:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
June 89813.94 12-JUN-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 87992.45 10-JUL-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
August 85104.43 22-AUG-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
September 89444.21 05-SEP-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 89795.70 10-OCT-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
November 87812.82 06-NOV-05:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
December 85213.59 04-DEC-05:12 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 81830.01   0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 89813.94   0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 23919.56 12-JAN-17:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 67754.35 28-FEB-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 69520.65 03-MAR-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 74168.15 29-APR-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 74452.72 01-MAY-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
June 76226.49 12-JUN-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 76852.43 17-JUL-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 78340.42 28-AUG-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
September 74675.92 25-SEP-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 74001.68 06-OCT-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 69705.18 07-NOV-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 35889.06 07-DEC-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 23919.56   0.00 2686.80 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 78340.42   15316.26 13241.18 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16011.75 11-JAN-17:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 27019.27 28-FEB-17:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 29864.23 15-MAR-16:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
April 68147.37 28-APR-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
May 68071.81 05-MAY-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
June 73202.65 12-JUN-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 71963.88 25-JUL-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
August 72360.26 11-AUG-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
September 68402.37 14-SEP-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
October 36504.72 04-OCT-15:40 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
November 24028.13 02-NOV-16:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 16003.69 06-DEC-16:40 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16003.69   0.00 2149.44 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73202.65   15316.26 13241.18 35625.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2361.79 12-JAN-06:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 68.05
February 4659.47 27-FEB-15:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 8.98
March 5152.91 20-MAR-13:40 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 45.71
April 7448.05 27-APR-15:20 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 10.25 0.00
May 7564.39 15-MAY-13:50 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 2.54
June 11276.83 12-JUN-04:12 0.00 404.83 4473.37 0.00 0.00 0.00 0.00 0.00 125.71
July 13930.80 23-JUL-18:31 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 0.00 32.67
August 11059.87 14-AUG-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 11.92
September 8438.61 11-SEP-15:25 3846.22 1582.09 4321.10 0.00 0.00 0.00 0.00 0.00 1.50
October 6103.68 10-OCT-05:03 607.30 202.41 2880.74 0.00 0.00 0.00 0.00 0.00 30.12
November 4653.39 06-NOV-11:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 40.52
December 2827.27 29-DEC-13:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 64.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2361.79   0.00 202.41 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13930.80   3846.22 1582.09 5591.71 0.00 0.00 0.00 0.00 10.25 125.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2875.71 05-JAN-09:25 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 30.69
February 4907.61 08-FEB-09:45 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 25.30
March 9407.21 14-MAR-08:55 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 23.67
April 12502.73 27-APR-08:30 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 8.96
May 19910.37 14-MAY-08:32 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 93.74
June 21475.11 25-JUN-08:32 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 52.16
July 24785.51 23-JUL-08:31 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 0.00 99.74
August 22548.21 13-AUG-08:42 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 72.64
September 24016.70 10-SEP-08:31 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 39.08
October 10348.54 04-OCT-08:50 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 16.58
November 4415.06 15-NOV-09:10 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 14.03
December 3847.66 05-DEC-10:00 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 44.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2875.71   326.14 141.60 1392.34 0.00 0.00 0.00 0.00 0.00 8.96
Maximum of Months 24785.51   2478.65 1019.56 3712.91 0.00 0.00 0.00 0.00 0.00 99.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16607.66 20-JAN-13:05 3846.30 1582.13 4321.17 0.00 0.00 0.00 0.00 0.00 3.67
February 29406.20 12-FEB-11:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 291.34
March 20344.15 01-MAR-13:30 3846.30 1582.13 4321.17 0.00 0.00 0.00 0.00 0.00 25.25
April 23822.44 02-APR-14:02 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 105.66
May 30381.21 07-MAY-13:02 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 113.28
June 21183.62 04-JUN-13:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 208.74
July 31021.73 23-JUL-13:52 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 4.30 0.00
August 30542.27 13-AUG-12:42 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 10.40
September 32470.92 10-SEP-12:31 910.97 395.50 6481.75 0.00 0.00 0.00 0.00 0.00 69.38
October 33339.48 08-OCT-13:01 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 106.33
November 21802.03 11-NOV-12:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 176.93
December 28464.59 03-DEC-12:43 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 170.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16607.66   404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33339.48   3846.30 1582.13 6481.75 0.00 0.00 0.00 0.00 4.30 291.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5663.89 05-JAN-15:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 28.08
February 13009.60 28-FEB-06:02 652.28 217.40 3094.07 0.00 0.00 0.00 0.00 0.00 11.98
March 15416.32 18-MAR-17:06 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 99.42
April 26376.70 02-APR-15:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 68.95
May 30738.30 07-MAY-17:01 0.00 254.87 3243.14 0.00 0.00 0.00 0.00 0.00 68.53
June 27429.59 18-JUN-16:52 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 117.87
July 32410.13 23-JUL-16:31 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 54.11
August 28932.76 06-AUG-16:51 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 49.65
September 30410.61 10-SEP-16:31 587.05 254.87 4177.00 0.00 0.00 0.00 0.00 0.00 40.04
October 22793.61 08-OCT-13:42 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 54.19
November 14989.20 03-NOV-05:02 652.28 217.40 3094.07 0.00 0.00 0.00 0.00 0.00 20.20
December 15583.63 04-DEC-05:11 0.00 434.81 4804.65 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5663.89   0.00 141.60 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32410.13   1239.33 509.78 4804.65 0.00 0.00 0.00 0.00 0.00 117.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1704.11 11-JAN-16:10 1923.11 1448.05 2160.55 0.00 0.00 0.00 0.00 0.00 99.46
February 2174.24 28-FEB-15:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
March 3020.62 10-MAR-14:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 68.10
April 6066.39 27-APR-15:20 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 23.21 0.00
May 6711.41 05-MAY-13:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 1.48
June 7261.87 21-JUN-15:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 3.68 0.00
July 8425.52 24-JUL-15:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 36.48 0.00
August 7988.82 25-AUG-14:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 15.62 0.00
September 6392.69 11-SEP-15:25 3846.22 1582.09 4321.10 0.00 0.00 0.00 0.00 0.00 3.95
October 3757.83 04-OCT-15:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 23.28
November 2159.53 04-NOV-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 63.49
December 1617.01 29-DEC-16:10 1923.11 1550.77 2160.55 0.00 0.00 0.00 0.00 0.00 83.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1617.01   809.73 269.88 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8425.52   3846.22 1582.09 4321.10 0.00 0.00 0.00 0.00 36.48 99.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1234.83 20-JAN-11:10 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 40.37
February 4339.39 27-FEB-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 27.38
March 9490.76 14-MAR-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 31.79
April 13283.24 27-APR-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 15.05
May 23868.15 14-MAY-07:42 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 278.29
June 22909.34 25-JUN-08:52 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 111.61
July 26560.55 30-JUL-08:41 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 0.00 116.15
August 23971.41 13-AUG-09:22 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 130.89
September 21784.99 10-SEP-08:42 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 100.25
October 10400.80 04-OCT-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 29.16
November 4878.95 04-NOV-10:05 782.73 339.85 1547.05 0.00 0.00 0.00 0.00 0.00 21.49
December 2821.23 05-DEC-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 45.74
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1234.83   326.14 141.60 1392.34 0.00 0.00 0.00 0.00 0.00 15.05
Maximum of Months 26560.55   2478.65 1019.56 3712.91 0.00 0.00 0.00 0.00 0.00 278.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16758.90 20-JAN-13:15 3846.30 1582.13 4321.17 0.00 0.00 0.00 0.00 0.00 17.34
February 32118.37 12-FEB-12:22 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 879.25
March 21843.25 01-MAR-13:25 3846.30 1582.13 4321.17 0.00 0.00 0.00 0.00 0.00 59.72
April 22391.00 02-APR-13:43 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 261.03
May 32165.04 14-MAY-12:22 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 313.58
June 31305.73 11-JUN-13:02 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 146.01
July 34619.12 30-JUL-12:41 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 72.94
August 31833.92 13-AUG-12:42 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 31.91
September 33320.92 10-SEP-12:42 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 168.85
October 31841.22 08-OCT-13:12 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 218.47
November 32146.31 11-NOV-14:02 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 340.70
December 27290.38 03-DEC-13:32 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 409.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16758.90   404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 17.34
Maximum of Months 34619.12   3846.30 1582.13 5041.36 0.00 0.00 0.00 0.00 0.00 879.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2270.37 05-JAN-15:40 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 68.60
February 8463.46 27-FEB-15:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 14.40
March 11118.87 14-MAR-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 18.41
April 16104.51 01-APR-17:05 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 12.90
May 28424.58 07-MAY-17:01 0.00 254.87 3243.14 0.00 0.00 0.00 0.00 0.00 168.52
June 27594.89 18-JUN-17:11 0.00 226.55 2882.79 0.00 0.00 0.00 0.00 0.00 300.75
July 29276.63 23-JUL-17:11 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 0.00 120.64
August 25938.03 06-AUG-16:51 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 112.72
September 24850.86 10-SEP-16:42 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 72.12
October 12266.31 04-OCT-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 19.41
November 6324.78 04-NOV-15:30 130.46 84.96 541.46 0.00 0.00 0.00 0.00 0.00 4.69
December 3459.42 05-DEC-15:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 59.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2270.37   0.00 84.96 541.46 0.00 0.00 0.00 0.00 0.00 4.69
Maximum of Months 29276.63   1239.33 509.78 3603.49 0.00 0.00 0.00 0.00 0.00 300.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1555.76 11-JAN-16:20 1923.11 1535.47 2160.55 0.00 0.00 0.00 0.00 0.00 118.50
February 1984.66 28-FEB-15:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
March 2485.22 10-MAR-14:40 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 83.46
April 6632.66 27-APR-15:20 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 27.80 0.00
May 7125.02 15-MAY-14:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 7.07
June 7862.29 21-JUN-15:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 3.72 0.00
July 9337.52 24-JUL-15:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 44.53 0.00
August 8520.46 09-AUG-14:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 44.95 0.00
September 6206.50 12-SEP-14:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 1.31 0.00
October 3537.12 04-OCT-15:20 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 32.62
November 1855.24 02-NOV-14:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 64.38
December 1476.00 29-DEC-16:10 1923.11 1550.55 2160.55 0.00 0.00 0.00 0.00 0.00 100.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1476.00   1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9337.52   2010.79 1550.55 2160.55 0.00 0.00 0.00 0.00 44.95 118.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1029.94 20-JAN-10:50 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 42.37
February 1555.13 27-FEB-15:40 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 18.73
March 6068.79 14-MAR-09:50 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 51.74
April 12271.57 27-APR-09:10 2591.66 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 25.43
May 23801.52 14-MAY-10:12 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 242.87
June 21615.52 25-JUN-09:12 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 154.75
July 23677.64 30-JUL-08:52 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 116.86
August 24902.13 06-AUG-10:01 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 210.35
September 24060.84 10-SEP-09:02 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 148.43
October 8426.86 04-OCT-09:20 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 45.90
November 1596.96 04-NOV-10:10 782.73 339.85 1547.05 0.00 0.00 0.00 0.00 0.00 26.87
December 1101.42 05-DEC-10:40 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 71.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1029.94   326.14 141.60 1392.34 0.00 0.00 0.00 0.00 0.00 18.73
Maximum of Months 24902.13   2591.66 1019.56 3248.80 0.00 0.00 0.00 0.00 0.00 242.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14891.81 20-JAN-13:25 3846.30 1582.13 4321.17 0.00 0.00 0.00 0.00 0.00 32.49
February 18535.84 27-FEB-14:20 2010.83 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 32.63
March 20677.40 01-MAR-13:40 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 71.07
April 25267.72 02-APR-14:02 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 315.93
May 34532.53 14-MAY-13:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 405.70
June 19762.41 11-JUN-15:13 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 124.46
July 33424.43 30-JUL-13:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 37.60
August 36033.95 06-AUG-13:21 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 218.93
September 38298.05 10-SEP-12:21 809.75 351.56 5761.56 0.00 0.00 0.00 0.00 0.00 233.72
October 31519.92 08-OCT-13:12 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 264.23
November 19320.28 11-NOV-13:12 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 475.37
December 14453.75 05-DEC-12:30 1058.33 791.06 1920.52 0.00 0.00 0.00 0.00 0.00 86.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14453.75   404.87 175.78 1920.52 0.00 0.00 0.00 0.00 0.00 32.49
Maximum of Months 38298.05   3846.30 1582.13 5761.56 0.00 0.00 0.00 0.00 0.00 475.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1794.11 05-JAN-15:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 82.77
February 7832.68 27-FEB-15:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 18.32
March 10828.53 14-MAR-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 23.22
April 18505.58 02-APR-15:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 196.27
May 29865.19 14-MAY-16:51 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 333.24
June 28216.97 18-JUN-18:01 0.00 226.55 2882.79 0.00 0.00 0.00 0.00 0.00 335.77
July 27722.38 23-JUL-16:41 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 81.35
August 30201.34 06-AUG-16:41 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 202.42
September 29096.56 10-SEP-16:21 587.05 254.87 4177.00 0.00 0.00 0.00 0.00 0.00 120.84
October 12211.92 04-OCT-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 24.97
November 5762.47 04-NOV-15:30 130.46 84.96 541.46 0.00 0.00 0.00 0.00 0.00 6.00
December 2469.43 05-DEC-15:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 74.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1794.11   0.00 84.96 541.46 0.00 0.00 0.00 0.00 0.00 6.00
Maximum of Months 30201.34   1239.33 509.78 4641.11 0.00 0.00 0.00 0.00 0.00 335.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2228.07 12-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.19
February 4305.94 28-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.57
March 4887.41 20-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.90
April 6471.51 27-APR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.45 0.00
May 7024.38 08-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.68
June 10061.76 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.16
July 8438.91 31-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.65 0.00
August 10957.68 14-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.13
September 8940.36 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.06
October 8414.68 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.08
November 6703.56 06-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 101.98
December 3630.88 04-DEC-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2228.07   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10957.68   0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.65 147.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7168.64 14-JAN-05:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1279.96
February 5813.95 18-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 429.70
March 5389.17 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 209.86
April 4290.57 27-APR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.03 0.00
May 4571.35 15-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.54
June 5162.88 28-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.32 0.00
July 6225.20 31-JUL-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.76 0.00
August 6659.52 10-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.51 0.00
September 6072.74 11-SEP-15:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.78
October 3745.80 04-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.17
November 6584.49 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.23
December 6754.66 26-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3745.80   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7168.64   0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.51 1279.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 947.74
February 2854.15 27-FEB-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.98
March 5649.95 14-MAR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.48
April 15301.62 27-APR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.72 0.00
May 15930.39 15-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.50
June 16049.18 28-JUN-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.58
July 17355.35 31-JUL-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.29 0.00
August 18474.35 10-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.18 0.00
September 14518.23 11-SEP-14:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.39
October 8830.17 04-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.30
November 3125.58 04-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.84
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 484.74
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18474.35   0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.29 947.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1947.92 05-JAN-16:10 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4033.73 07-FEB-16:50 222.14 316.63 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7009.32 31-MAR-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8154.66 26-APR-18:00 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3446.05 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5322.30 30-JUN-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7270.17 31-JUL-24:00 0.00 35.18 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8697.08 06-AUG-18:41 0.00 158.32 70149.80 0.00 0.00 0.00 0.00 0.00 0.00
September 3332.13 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5051.92 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5839.70 11-NOV-15:55 23.38 35.18 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
December 7754.83 05-DEC-15:50 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1947.92   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8697.08   222.14 316.63 70149.80 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1538.25 05-JAN-16:20 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3705.58 07-FEB-17:00 222.14 316.63 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6252.31 31-MAR-23:50 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7786.17 26-APR-18:00 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3218.45 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5001.88 30-JUN-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6991.99 31-JUL-24:00 0.00 35.18 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8157.35 06-AUG-18:35 0.00 140.73 62355.38 0.00 0.00 0.00 0.00 0.00 0.00
September 2998.48 30-SEP-23:50 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4251.72 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5328.70 10-NOV-16:10 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7168.58 05-DEC-16:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1538.25   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8157.35   222.14 316.63 62355.38 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1398.62 05-JAN-16:20 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3580.71 08-FEB-17:00 222.14 316.63 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5758.96 31-MAR-23:20 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7851.74 26-APR-18:00 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3130.34 31-MAY-23:30 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 4910.45 30-JUN-23:40 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6956.94 31-JUL-24:00 0.00 35.18 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8356.47 06-AUG-18:30 0.00 35.18 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 2595.43 30-SEP-23:20 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4162.74 04-OCT-16:50 70.15 175.91 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5215.44 04-NOV-16:02 70.15 105.55 35074.90 0.00 0.00 0.00 0.00 0.00 0.00
December 6971.48 05-DEC-16:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1398.62   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8356.47   222.14 316.63 35074.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91053.20 12-JAN-17:00 4808.68 4157.19 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183297.66 27-FEB-17:00 4808.68 4157.19 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358391.21 31-MAR-24:00 0.00 230.94 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367369.74 27-APR-16:00 4808.68 4157.19 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 176106.82 31-MAY-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267641.67 30-JUN-24:00 0.00 230.94 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 360243.33 31-JUL-24:00 0.00 461.88 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
August 368286.52 14-AUG-16:00 4808.68 4157.19 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 175662.23 30-SEP-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267221.64 31-OCT-24:00 0.00 230.94 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 275762.42 06-NOV-17:00 4808.68 4157.19 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367135.29 04-DEC-17:00 4808.68 4157.19 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91053.20   0.00 230.94 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 368286.52   4808.68 4157.19 759265.04 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.154926E+13 1131748.64 10-JAN-16:00 0.349230E+12 1281357.61 02-JAN-06:10
February 0.176005E+13 1387221.62 27-FEB-15:09 0.195157E+12 619653.17 18-FEB-07:10
March 0.237365E+13 1518879.04 14-MAR-15:00 0.864843E+11 482279.39 29-MAR-13:20
April 0.259661E+13 1918772.92 27-APR-14:39 0.378604E+11 428483.55 03-APR-13:20
May 0.159102E+13 1464786.37 15-MAY-15:09 0.993947E+10 264641.43 17-MAY-09:00
June 0.192935E+13 1565803.12 09-JUN-15:20 0.440673E+09 252555.18 13-JUN-09:20
July 0.239089E+13 1849062.89 31-JUL-15:09 0.104597E+09 165400.95 12-JUL-09:20
August 0.292605E+13 2044516.27 29-AUG-15:20 87100423.82 93145.58 03-AUG-09:09
September 0.152870E+13 1442199.34 11-SEP-15:20 0.169952E+10 314706.07 27-SEP-09:20
October 0.188253E+13 1551864.96 04-OCT-15:09 0.211772E+11 233691.30 10-OCT-09:50
November 0.219661E+13 1436241.79 16-NOV-16:30 0.138730E+12 501487.66 24-NOV-07:10
December 0.267309E+13 1572696.72 05-DEC-16:19 0.270993E+12 769018.81 26-DEC-07:10
             
Annual Sum or Average 0.253978E+14     0.111190E+13    
Minimum of Months 0.152870E+13 1131748.64   87100423.82 93145.58  
Maximum of Months 0.292605E+13 2044516.27   0.349230E+12 1281357.61  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.211428E+12 0.441256E+11 0.766053E+12 0.213317E+12 0.158112E+12 0.142694E+11 0.00 0.896903E+10 0.751376E+09 0.931767E+11 0.00 0.390568E+11 0.00
February 0.188487E+12 0.343652E+11 0.978954E+12 0.195309E+12 0.150242E+12 0.157333E+11 0.00 0.251291E+11 0.307203E+10 0.133028E+12 0.00 0.357280E+11 0.00
March 0.221474E+12 0.307121E+11 0.141687E+13 0.226028E+12 0.181822E+12 0.197104E+11 0.00 0.485701E+11 0.581669E+10 0.181099E+12 0.00 0.415407E+11 0.00
April 0.196038E+12 0.231133E+11 0.165903E+13 0.211475E+12 0.191307E+12 0.189748E+11 0.00 0.845783E+11 0.187805E+11 0.156631E+12 0.00 0.366859E+11 0.00
May 0.210933E+12 0.194367E+11 0.774844E+12 0.219671E+12 0.209030E+12 0.234035E+11 0.00 0.408758E+11 0.188373E+11 0.362408E+11 0.00 0.377491E+11 0.00
June 0.209451E+12 0.168813E+11 0.106252E+13 0.217906E+12 0.215470E+12 0.301380E+11 0.00 0.808156E+11 0.371963E+11 0.229298E+11 0.00 0.360473E+11 0.00
July 0.195875E+12 0.181386E+11 0.139340E+13 0.213239E+12 0.231516E+12 0.392972E+11 0.00 0.177131E+12 0.668030E+11 0.221007E+11 0.00 0.333862E+11 0.00
August 0.219001E+12 0.215466E+11 0.173200E+13 0.226028E+12 0.246567E+12 0.454918E+11 0.00 0.301988E+12 0.964241E+11 0.790180E+09 0.00 0.362148E+11 0.00
September 0.196941E+12 0.266127E+11 0.740713E+12 0.211475E+12 0.206357E+12 0.284393E+11 0.00 0.555002E+11 0.276227E+11 0.172979E+10 0.00 0.333050E+11 0.00
October 0.206805E+12 0.349330E+11 0.108340E+13 0.213315E+12 0.187493E+12 0.180116E+11 0.00 0.394465E+11 0.821424E+10 0.554976E+11 0.00 0.354161E+11 0.00
November 0.208332E+12 0.406597E+11 0.135889E+13 0.205270E+12 0.166471E+12 0.169745E+11 0.00 0.388757E+11 0.542738E+10 0.119620E+12 0.00 0.360879E+11 0.00
December 0.205710E+12 0.459151E+11 0.170972E+13 0.213242E+12 0.167317E+12 0.187328E+11 0.00 0.496491E+11 0.444864E+10 0.221132E+12 0.00 0.372214E+11 0.00
                           
Annual Sum or Average 0.247048E+13 0.356440E+12 0.146764E+14 0.256628E+13 0.231171E+13 0.289177E+12 0.00 0.951529E+12 0.293394E+12 0.104398E+13 0.00 0.438439E+12 0.00
Minimum of Months 0.188487E+12 0.168813E+11 0.740713E+12 0.195309E+12 0.150242E+12 0.142694E+11 0.00 0.896903E+10 0.751376E+09 0.790180E+09 0.00 0.333050E+11 0.00
Maximum of Months 0.221474E+12 0.459151E+11 0.173200E+13 0.226028E+12 0.246567E+12 0.454918E+11 0.00 0.301988E+12 0.964241E+11 0.221132E+12 0.00 0.415407E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.349230E+12 0.00 0.00 0.00 0.00
February 0.00 0.00 0.195157E+12 0.00 0.00 0.00 0.00
March 0.00 0.00 0.864843E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.378604E+11 0.00 0.00 0.00 0.00
May 0.00 0.00 0.993947E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.440673E+09 0.00 0.00 0.00 0.00
July 0.00 0.00 0.104597E+09 0.00 0.00 0.00 0.00
August 0.00 0.00 87100423.82 0.00 0.00 0.00 0.00
September 0.00 0.00 0.169952E+10 0.00 0.00 0.00 0.00
October 0.00 0.00 0.211772E+11 0.00 0.00 0.00 0.00
November 0.00 0.00 0.138730E+12 0.00 0.00 0.00 0.00
December 0.00 0.00 0.270993E+12 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.111190E+13 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 87100423.82 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.349230E+12 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 247210.90 02-JAN-16:30 40855.88 01-JAN-06:10 423497.50 02-JAN-08:09 233394.81 04-JAN-08:20 90649.18 02-JAN-06:10 21342.75 09-JAN-06:10 0.00 01-JAN-00:10
February 239816.34 02-FEB-16:00 40855.88 01-FEB-06:10 541788.89 01-FEB-08:09 233392.41 02-FEB-08:20 137981.97 27-FEB-15:09 20390.85 06-FEB-10:20 0.00 01-FEB-00:10
March 232449.70 22-MAR-07:10 40855.88 01-MAR-06:10 660080.29 01-MAR-08:09 233389.48 22-MAR-07:19 154949.17 14-MAR-15:20 20242.41 25-MAR-13:20 0.00 01-MAR-00:10
April 219022.99 03-APR-07:10 40855.88 01-APR-05:10 778371.69 03-APR-07:10 233382.37 03-APR-07:19 239317.40 27-APR-14:39 38570.55 26-APR-14:39 0.00 01-APR-00:10
May 214737.25 17-MAY-07:10 27558.46 01-MAY-19:19 423497.50 01-MAY-07:10 233380.11 17-MAY-07:19 227850.01 15-MAY-14:30 39021.67 04-MAY-13:00 0.00 01-MAY-00:10
June 213311.67 29-JUN-07:10 27558.46 01-JUN-19:00 541788.89 01-JUN-07:10 233379.35 29-JUN-07:19 214092.61 28-JUN-15:20 38814.25 27-JUN-15:09 0.00 01-JUN-00:10
July 218153.98 12-JUL-07:30 27558.46 01-JUL-20:10 660080.29 03-JUL-07:10 233381.91 12-JUL-07:40 262761.66 20-JUL-12:20 42585.91 20-JUL-12:20 0.00 01-JUL-00:10
August 217315.09 28-AUG-07:30 40855.88 16-AUG-05:10 778371.69 01-AUG-07:10 233381.47 28-AUG-07:40 274484.96 10-AUG-14:39 38711.38 29-AUG-12:30 0.00 01-AUG-00:10
September 232947.01 25-SEP-07:10 40855.88 01-SEP-05:10 423497.50 01-SEP-07:10 233389.74 25-SEP-07:19 277574.26 11-SEP-14:39 39333.99 11-SEP-15:30 0.00 01-SEP-00:10
October 246230.77 31-OCT-07:10 40855.88 01-OCT-05:10 541788.89 02-OCT-07:10 233396.79 31-OCT-07:19 212029.34 04-OCT-15:39 36342.37 04-OCT-13:20 0.00 01-OCT-00:10
November 247210.90 06-NOV-16:49 40855.88 01-NOV-05:10 660080.29 01-NOV-07:10 233396.80 03-NOV-07:19 109947.96 15-NOV-13:00 20723.10 24-NOV-06:10 0.00 01-NOV-00:10
December 247210.90 01-DEC-16:19 40855.88 01-DEC-06:10 778371.69 01-DEC-08:09 233396.85 28-DEC-08:20 105305.77 05-DEC-11:00 21585.69 26-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 213311.67   27558.46   423497.50   233379.35   90649.18   20242.41   0.00  
Maximum of Months 247210.90   40855.88   778371.69   233396.85   277574.26   42585.91   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 7455.60 20-JAN-15:39 1399.07 11-JAN-15:30 64331.37 09-JAN-11:00 0.00 51962.28 31-JAN-12:00 0.00
February 96810.48 27-FEB-15:09 45048.17 27-FEB-15:30 100000.00 11-FEB-17:10 0.00 52005.65 10-FEB-12:20 0.00
March 98301.20 18-MAR-15:00 44009.10 18-MAR-13:39 100000.00 01-MAR-06:10 0.00 51854.47 03-MAR-12:50 0.00
April 318448.06 27-APR-14:00 72883.01 27-APR-12:20 100000.00 01-APR-17:10 0.00 50575.06 06-APR-11:39 0.00
May 224116.92 04-MAY-14:09 72883.01 04-MAY-13:00 100000.00 14-MAY-12:50 0.00 48763.98 01-MAY-11:00 0.00
June 240817.02 21-JUN-14:09 72883.01 20-JUN-13:39 100000.00 01-JUN-14:09 0.00 46818.54 02-JUN-11:20 0.00
July 362705.34 31-JUL-15:00 72883.01 07-JUL-12:30 100000.00 18-JUL-14:30 0.00 45392.54 03-JUL-11:00 0.00
August 421316.31 29-AUG-14:30 72883.01 07-AUG-10:30 100000.00 09-AUG-08:00 0.00 44766.81 31-AUG-11:30 0.00
September 209803.50 11-SEP-15:30 72883.01 12-SEP-13:20 38380.78 08-SEP-14:00 0.00 45683.79 29-SEP-11:39 0.00
October 178344.11 04-OCT-14:20 45687.54 04-OCT-14:30 100000.00 03-OCT-11:20 0.00 47250.75 31-OCT-11:00 0.00
November 118666.89 04-NOV-14:09 45593.84 04-NOV-14:20 100000.00 13-NOV-22:10 0.00 49235.58 30-NOV-12:00 0.00
December 25772.76 05-DEC-14:39 3591.92 14-DEC-11:00 100000.00 02-DEC-05:30 0.00 51100.98 27-DEC-12:00 0.00
                     
Annual Sum or Average             0.00     0.00
Minimum of Months 7455.60   1399.07   38380.78   0.00 44766.81   0.00
Maximum of Months 421316.31   72883.01   100000.00   0.00 52005.65   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1131748.64 10-JAN-16:00 247210.90 423497.50 40855.88 233284.51 68771.48 19429.29 0.00 5788.86 654.26
February 1387221.62 27-FEB-15:09 212815.01 541788.89 0.00 233115.89 137981.97 20135.55 0.00 96810.48 44975.79
March 1518879.04 14-MAR-15:00 212815.01 660080.29 0.00 233266.29 150082.33 20089.05 0.00 92875.29 28819.29
April 1918772.92 27-APR-14:39 212815.01 778371.69 0.00 233115.89 239317.40 37410.82 0.00 316349.05 72883.01
May 1464786.37 15-MAY-15:09 212815.01 423497.50 0.00 233266.29 225172.64 35665.11 0.00 154073.03 44446.55
June 1565803.12 09-JUN-15:20 212815.01 541788.89 0.00 233266.29 193604.32 35573.96 0.00 180020.16 46289.94
July 1849062.89 31-JUL-15:09 212815.01 660080.29 0.00 233266.29 255414.90 37558.41 0.00 343762.36 72883.01
August 2044516.27 29-AUG-15:20 212815.01 778371.69 0.00 233266.29 270536.85 37784.73 0.00 404381.15 72883.01
September 1442199.34 11-SEP-15:20 212815.01 423497.50 0.00 233266.29 277574.26 28527.70 0.00 173792.59 58329.63
October 1551864.96 04-OCT-15:09 212815.01 541788.89 0.00 233266.29 181152.05 35707.12 0.00 168554.85 44052.71
November 1436241.79 16-NOV-16:30 247210.90 660080.29 40855.88 233281.95 84854.80 19552.69 0.00 17118.97 1533.36
December 1572696.72 05-DEC-16:19 247210.90 778371.69 40855.88 233279.28 89639.23 19533.97 0.00 23812.14 1883.95
                       
Annual Sum or Average                      
Minimum of Months 1131748.64   212815.01 423497.50 0.00 233115.89 68771.48 19429.29 0.00 5788.86 654.26
Maximum of Months 2044516.27   247210.90 778371.69 40855.88 233284.51 277574.26 37784.73 0.00 404381.15 72883.01



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 1281357.61 02-JAN-06:10 0.00 0.00 0.00
February 0.00 0.00 619653.17 18-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 482279.39 29-MAR-13:20 0.00 0.00 0.00
April 0.00 0.00 428483.55 03-APR-13:20 0.00 0.00 0.00
May 0.00 0.00 264641.43 17-MAY-09:00 0.00 0.00 0.00
June 0.00 0.00 252555.18 13-JUN-09:20 0.00 0.00 0.00
July 0.00 0.00 165400.95 12-JUL-09:20 0.00 0.00 0.00
August 0.00 0.00 93145.58 03-AUG-09:09 0.00 0.00 0.00
September 0.00 0.00 314706.07 27-SEP-09:20 0.00 0.00 0.00
October 0.00 0.00 233691.30 10-OCT-09:50 0.00 0.00 0.00
November 0.00 0.00 501487.66 24-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 769018.81 26-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 93145.58   0.00 0.00 0.00
Maximum of Months 0.00 0.00 1281357.61   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 74.33 26.46 37.33 26.45
February 0.00 0.00 0.00 0.00 45.83 26.11 24.33 26.11
March 0.00 0.00 0.00 0.00 51.17 26.27 28.33 26.27
April 0.00 0.00 0.00 0.00 47.50 26.40 26.67 26.40
May 0.00 0.00 0.00 0.00 62.83 26.56 30.00 26.51
June 0.00 0.00 0.00 0.00 57.50 26.55 30.83 26.52
July 0.00 0.00 0.00 0.00 81.00 26.89 30.67 26.82
August 0.00 0.00 0.00 0.00 81.00 26.80 34.17 26.71
September 0.00 0.00 0.00 0.00 83.50 26.96 41.00 26.91
October 0.00 0.00 0.00 0.00 78.17 26.95 40.67 26.91
November 0.00 0.00 0.00 0.00 69.17 26.78 31.33 26.72
December 0.00 0.00 0.00 0.00 50.17 26.31 26.33 26.31
                 
Annual Sum or Average 0.00   0.00   782.17 26.64 381.67 26.60
Minimum of Months 0.00 0.00 0.00 0.00 45.83 26.11 24.33 26.11
Maximum of Months 0.00 0.00 0.00 0.00 83.50 26.96 41.00 26.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 25.60 0.00 25.60
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
October 0.00 0.00 0.00 0.00 0.17 25.61 0.00 25.61
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 25.60 0.00 25.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 19.02 0.67 19.19 0.00 19.19 0.00 19.19
February 0.67 19.26 0.17 19.48 0.00 19.48 0.00 19.48
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.27 0.00 19.27 0.00 19.27 0.00 19.27
December 0.83 18.65 0.00 18.65 0.00 18.65 0.00 18.65
                 
Annual Sum or Average 4.67 19.00 0.83 19.15 0.00 19.15 0.00 19.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 19.27 0.67 19.48 0.00 19.48 0.00 19.48



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.37 0.83 27.37
May 0.00 0.00 0.00 0.00 2.33 27.83 2.33 27.83
June 0.00 0.00 0.00 0.00 4.33 27.78 4.33 27.78
July 0.00 0.00 0.00 0.00 5.00 28.01 5.00 28.01
August 0.00 0.00 0.00 0.00 4.00 28.12 4.00 28.12
September 0.00 0.00 0.00 0.00 2.00 28.01 2.00 28.01
October 0.00 0.00 0.00 0.00 0.33 27.31 0.33 27.31
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   18.83 27.92 18.83 27.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.00 28.12 5.00 28.12



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 27.42 0.67 27.42
February 0.00 0.00 0.00 0.00 2.17 27.69 2.17 27.69
March 0.00 0.00 0.00 0.00 0.50 27.44 0.50 27.44
April 0.00 0.00 0.00 0.00 2.33 27.81 2.33 27.81
May 0.00 0.00 0.00 0.00 3.83 27.78 3.83 27.78
June 0.00 0.00 0.00 0.00 4.33 27.62 4.33 27.62
July 0.00 0.00 0.00 0.00 6.50 27.79 6.33 27.80
August 0.00 0.00 0.00 0.00 4.50 28.04 4.17 28.07
September 0.00 0.00 0.00 0.00 4.50 27.26 4.33 27.26
October 0.00 0.00 0.00 0.00 3.00 27.83 3.00 27.83
November 0.00 0.00 0.00 0.00 1.33 27.88 1.33 27.88
December 0.00 0.00 0.00 0.00 1.17 27.67 1.17 27.67
                 
Annual Sum or Average 0.00   0.00   34.83 27.72 34.17 27.72
Minimum of Months 0.00 0.00 0.00 0.00 0.50 27.26 0.50 27.26
Maximum of Months 0.00 0.00 0.00 0.00 6.50 28.04 6.33 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.17 27.46 1.17 27.46
March 0.00 0.00 0.00 0.00 1.83 27.50 1.83 27.50
April 0.00 0.00 0.00 0.00 10.00 27.63 6.33 27.71
May 0.00 0.00 0.00 0.00 8.00 28.42 4.50 28.45
June 0.00 0.00 0.00 0.00 8.67 27.73 4.67 27.87
July 0.00 0.00 0.00 0.00 25.33 27.66 11.83 27.77
August 0.00 0.00 0.00 0.00 22.33 27.49 9.67 27.63
September 0.00 0.00 0.00 0.00 6.17 27.59 4.50 27.58
October 0.00 0.00 0.00 0.00 2.83 27.59 2.83 27.59
November 0.00 0.00 0.00 0.00 1.33 27.47 1.33 27.47
December 0.00 0.00 0.00 0.00 1.00 27.50 1.00 27.50
                 
Annual Sum or Average 0.00   0.00   88.67 27.67 49.67 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 25.33 28.42 11.83 28.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.83 19.00 0.33 19.17 0.00 19.17 0.00 19.17
February 0.50 19.30 0.00 19.30 0.00 19.30 0.00 19.30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.06 0.00 19.06 0.00 19.06 0.00 19.06
                 
Annual Sum or Average 2.50 19.07 0.33 19.19 0.00 19.19 0.00 19.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.83 19.30 0.33 19.30 0.00 19.30 0.00 19.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 19.34 0.00 19.34 0.00 19.34 0.00 19.34
February 0.33 19.34 0.00 19.34 0.00 19.34 0.00 19.34
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
May 0.00 0.00 0.00 0.00 2.50 27.86 2.50 27.86
June 0.00 0.00 0.00 0.00 4.17 27.86 4.17 27.86
July 0.00 0.00 0.00 0.00 5.50 28.10 5.50 28.10
August 0.00 0.00 0.00 0.00 4.50 28.20 4.50 28.20
September 0.00 0.00 0.00 0.00 1.83 28.03 1.83 28.03
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 2.00 19.52 0.00 19.52 0.00 19.52 0.00 19.52
                 
Annual Sum or Average 5.33 19.40 0.00 19.40 18.67 26.11 18.67 26.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 19.52 0.00 19.52 5.50 28.20 5.50 28.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 19.05 0.00 19.05 0.50 22.21 0.50 23.65
February 0.00 0.00 0.00 0.00 1.67 27.97 1.67 27.97
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.17 27.79 2.17 27.79
May 0.00 0.00 0.00 0.00 3.83 27.83 3.83 27.83
June 0.00 0.00 0.00 0.00 3.83 27.59 3.83 27.59
July 0.00 0.00 0.00 0.00 5.83 27.83 5.50 27.84
August 0.00 0.00 0.00 0.00 4.00 28.17 3.67 28.21
September 0.00 0.00 0.00 0.00 4.67 27.44 4.33 27.44
October 0.00 0.00 0.00 0.00 3.00 27.90 3.00 27.90
November 0.00 0.00 0.00 0.00 1.17 28.03 1.17 28.03
December 0.33 19.33 0.00 19.33 0.67 24.90 0.67 26.01
                 
Annual Sum or Average 1.17 19.13 0.00 19.13 31.33 27.49 30.33 27.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 19.33 0.00 19.33 5.83 28.17 5.50 28.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 18.92 0.00 18.92 0.00 18.92 0.00 18.92
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.00 27.67 1.67 27.67
May 0.00 0.00 0.00 0.00 6.83 28.46 3.50 28.51
June 0.00 0.00 0.00 0.00 4.17 28.14 2.50 28.11
July 0.00 0.00 0.00 0.00 9.50 28.26 4.67 28.26
August 0.00 0.00 0.00 0.00 5.00 28.40 2.50 28.44
September 0.00 0.00 0.00 0.00 4.67 27.61 3.83 27.58
October 0.00 0.00 0.00 0.00 0.33 27.39 0.33 27.39
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.35 0.00 19.35 0.00 19.35 0.00 19.35
                 
Annual Sum or Average 0.83 19.01 0.00 19.01 32.50 27.94 19.00 28.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 19.35 0.00 19.35 9.50 28.46 4.67 28.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.83 17.70 7.33 17.89 0.00 17.89 0.00 17.89
February 12.00 18.06 3.83 18.11 0.00 18.11 0.00 18.11
March 1.67 19.20 0.17 19.31 0.00 19.31 0.00 19.31
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 19.29 0.00 19.29 0.00 19.29 0.00 19.29
November 4.50 19.06 0.83 19.22 0.00 19.22 0.00 19.22
December 12.67 18.48 3.33 18.63 0.00 18.63 0.00 18.63
                 
Annual Sum or Average 53.00 18.14 15.50 18.26 0.00 18.26 0.00 18.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21.83 19.29 7.33 19.31 0.00 19.31 0.00 19.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.83 16.56 1.67 16.38 0.00 16.38 0.00 16.38
February 5.50 17.48 0.67 17.21 0.00 17.21 0.00 17.21
March 0.67 19.05 0.00 19.05 0.00 19.05 0.00 19.05
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.50 27.76 2.50 27.76
June 0.00 0.00 0.00 0.00 4.33 27.74 4.33 27.74
July 0.00 0.00 0.00 0.00 5.83 28.07 5.50 28.09
August 0.00 0.00 0.00 0.00 5.33 28.05 5.17 28.06
September 0.00 0.00 0.00 0.00 1.50 27.93 1.50 27.93
October 0.33 19.34 0.00 19.34 0.00 19.34 0.00 19.34
November 2.83 18.87 0.00 18.87 0.00 18.87 0.00 18.87
December 6.83 17.54 0.00 17.54 0.00 17.54 0.00 17.54
                 
Annual Sum or Average 29.00 17.28 2.33 17.11 19.50 21.26 19.00 23.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.83 19.34 1.67 19.34 5.83 28.07 5.50 28.09



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.17 17.34 0.83 17.15 0.00 17.15 0.00 17.15
February 2.33 18.59 0.00 18.59 0.67 20.57 0.67 21.83
March 0.50 19.01 0.00 19.01 0.00 19.01 0.00 19.01
April 0.00 0.00 0.00 0.00 1.50 27.89 1.50 27.89
May 0.00 0.00 0.00 0.00 3.83 27.84 3.83 27.84
June 0.00 0.00 0.00 0.00 3.83 27.62 3.83 27.62
July 0.00 0.00 0.00 0.00 5.83 27.89 5.17 27.92
August 0.00 0.00 0.00 0.00 4.00 28.26 3.50 28.32
September 0.00 0.00 0.00 0.00 4.17 27.29 4.00 27.29
October 0.00 0.00 0.00 0.00 1.83 27.72 1.83 27.72
November 1.83 19.01 0.00 19.01 0.67 21.28 0.67 22.60
December 4.33 18.67 0.00 18.67 0.00 18.67 0.00 18.67
                 
Annual Sum or Average 18.17 18.03 0.83 17.90 26.33 23.64 25.00 25.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.15 0.00 17.15
Maximum of Months 9.17 19.01 0.83 19.01 5.83 28.26 5.17 28.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.33 18.41 0.33 18.21 0.00 18.21 0.00 18.21
February 2.33 18.72 0.00 18.72 0.00 18.72 0.00 18.72
March 0.33 19.18 0.00 19.18 0.00 19.18 0.00 19.18
April 0.00 0.00 0.00 0.00 1.50 27.69 1.17 27.71
May 0.00 0.00 0.00 0.00 6.67 28.48 3.33 28.53
June 0.00 0.00 0.00 0.00 4.33 28.17 2.50 28.15
July 0.00 0.00 0.00 0.00 9.50 28.34 4.67 28.35
August 0.00 0.00 0.00 0.00 5.00 28.50 2.67 28.52
September 0.00 0.00 0.00 0.00 4.00 27.79 3.00 27.79
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.00 19.01 0.00 19.01 0.00 19.01 0.00 19.01
December 3.17 18.86 0.00 18.86 0.00 18.86 0.00 18.86
                 
Annual Sum or Average 12.17 18.66 0.33 18.56 31.00 25.48 17.33 26.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.33 19.18 0.33 19.18 9.50 28.50 4.67 28.53



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 76.50 24.57 114.17 25.43 13.33 25.54
February 43.83 24.00 132.83 25.26 0.00 25.26
March 34.50 24.00 129.50 25.55 0.00 25.55
April 3.50 24.00 184.00 25.62 0.00 25.62
May 0.50 27.54 261.17 25.20 0.50 25.20
June 0.00 0.00 294.50 25.02 0.00 25.02
July 4.33 27.43 424.50 24.91 4.33 24.94
August 2.33 27.54 475.17 24.70 2.33 24.71
September 14.67 27.62 381.83 24.99 14.67 25.08
October 10.83 27.75 215.33 25.77 10.83 25.86
November 3.17 25.30 219.83 25.53 1.17 25.54
December 20.00 24.00 137.17 25.96 0.00 25.96
             
Annual Sum or Average 214.17 24.78 2970.00 25.20 47.17 25.24
Minimum of Months 0.00 0.00 114.17 24.70 0.00 24.71
Maximum of Months 76.50 27.75 475.17 25.96 14.67 25.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 187.33 23.97 25.33 24.13 13.00 24.21
February 95.00 23.96 65.83 24.37 0.00 24.37
March 32.33 24.01 104.50 25.03 0.00 25.03
April 2.67 24.00 168.83 24.89 0.00 24.89
May 1.67 23.95 215.83 24.64 0.00 24.64
June 0.00 0.00 284.83 24.49 0.00 24.49
July 0.00 0.00 415.83 24.37 0.00 24.37
August 0.00 0.00 479.17 24.25 0.00 24.25
September 0.00 0.00 352.50 24.49 0.00 24.49
October 0.83 23.88 178.50 25.05 0.00 25.05
November 9.00 23.98 180.50 24.96 0.00 24.96
December 51.00 23.98 94.83 25.12 0.00 25.12
             
Annual Sum or Average 379.83 23.97 2566.50 24.56 13.00 24.56
Minimum of Months 0.00 0.00 25.33 24.13 0.00 24.21
Maximum of Months 187.33 24.01 479.17 25.12 13.00 25.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 488.67 22.79 12.00 22.71 12.00 22.64
February 385.17 23.30 0.00 23.30 0.00 23.30
March 297.33 23.71 3.83 23.72 0.00 23.72
April 161.33 23.69 49.50 23.95 0.00 23.95
May 66.33 23.75 126.33 24.26 0.00 24.26
June 12.67 23.73 153.83 24.46 0.00 24.46
July 0.67 23.60 300.00 24.37 0.00 24.37
August 3.33 23.64 400.17 24.25 0.00 24.25
September 8.67 23.59 260.50 24.40 0.00 24.40
October 145.00 23.58 48.67 23.94 0.00 23.94
November 330.00 23.53 23.50 23.60 0.00 23.60
December 465.67 23.21 0.00 23.21 0.00 23.21
             
Annual Sum or Average 2364.83 23.32 1378.33 23.71 12.00 23.70
Minimum of Months 0.67 22.79 0.00 22.71 0.00 22.64
Maximum of Months 488.67 23.75 400.17 24.46 12.00 24.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.26 142.17 20.86 142.17 20.61
February 441.83 21.86 78.00 21.55 78.00 21.32
March 465.17 22.81 14.33 22.74 14.33 22.67
April 317.17 23.18 31.50 23.29 0.00 23.29
May 189.67 23.41 80.50 23.67 0.00 23.67
June 72.50 23.55 133.50 24.07 0.00 24.07
July 27.50 23.62 287.67 24.23 0.00 24.23
August 31.67 23.49 367.00 24.16 0.00 24.16
September 124.83 23.33 168.50 23.84 0.00 23.84
October 375.83 22.89 1.67 22.90 0.00 22.90
November 457.83 22.16 36.17 22.02 34.33 21.90
December 497.00 21.55 103.00 21.28 103.00 21.09
             
Annual Sum or Average 3503.00 22.32 1444.00 22.55 371.83 22.36
Minimum of Months 27.50 21.26 1.67 20.86 0.00 20.61
Maximum of Months 502.00 23.62 367.00 24.23 142.17 24.23



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.31 12.67 22.28 12.67 22.24
February 407.67 22.72 5.67 22.71 3.83 22.69
March 392.00 23.38 0.00 23.38 0.00 23.38
April 201.33 23.63 60.50 23.83 0.00 23.83
May 122.17 23.58 128.83 24.05 0.00 24.05
June 18.33 23.66 215.00 24.37 0.00 24.37
July 0.00 0.00 381.67 24.36 0.00 24.36
August 0.33 27.00 423.50 24.24 0.33 24.24
September 80.83 23.46 210.83 24.11 0.00 24.11
October 277.17 23.39 24.33 23.53 0.00 23.53
November 377.17 23.15 14.50 23.20 0.00 23.20
December 487.67 22.92 0.00 22.92 0.00 22.92
             
Annual Sum or Average 2866.67 23.02 1477.50 23.47 16.83 23.46
Minimum of Months 0.00 0.00 0.00 22.28 0.00 22.24
Maximum of Months 502.00 27.00 423.50 24.37 12.67 24.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.33 22.26 15.33 22.22 15.33 22.17
February 393.50 22.69 11.67 22.70 6.00 22.67
March 354.67 23.19 10.50 23.22 0.00 23.22
April 171.67 23.44 125.33 23.86 0.50 23.87
May 122.33 23.74 202.17 24.24 8.00 24.30
June 45.50 24.66 295.00 24.49 14.00 24.59
July 21.00 26.41 384.50 24.52 16.67 24.62
August 28.67 25.62 419.00 24.36 17.17 24.46
September 85.00 23.74 267.17 24.26 7.67 24.32
October 262.50 23.27 68.33 23.56 0.33 23.56
November 392.67 22.88 18.33 22.95 0.00 22.95
December 490.83 22.53 0.00 22.53 0.00 22.53
             
Annual Sum or Average 2869.67 22.94 1817.33 23.50 85.67 23.53
Minimum of Months 21.00 22.26 0.00 22.22 0.00 22.17
Maximum of Months 501.33 26.41 419.00 24.52 17.17 24.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 454.33 22.07 50.17 22.03 36.33 21.92
February 331.00 22.61 81.00 22.92 15.33 22.87
March 312.50 23.19 86.33 23.44 0.33 23.44
April 170.83 23.57 157.17 24.00 5.67 24.06
May 142.50 23.77 206.83 24.19 12.83 24.29
June 57.33 24.40 279.00 24.45 13.67 24.55
July 24.33 26.52 382.83 24.58 20.50 24.70
August 25.50 25.95 434.67 24.42 17.50 24.52
September 74.50 24.02 298.33 24.38 14.17 24.48
October 212.83 23.36 142.83 23.87 9.33 23.95
November 357.67 22.86 58.17 23.14 4.83 23.19
December 417.00 22.45 42.83 22.63 3.50 22.63
             
Annual Sum or Average 2580.33 22.93 2220.17 23.60 154.00 23.64
Minimum of Months 24.33 22.07 42.83 22.03 0.33 21.92
Maximum of Months 454.33 26.52 434.67 24.58 36.33 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 443.33 23.12 1.50 23.13 0.00 23.13
February 246.33 23.68 76.50 23.96 2.00 23.97
March 68.17 24.06 147.67 24.66 2.17 24.68
April 25.17 26.78 309.00 25.01 23.33 25.14
May 41.00 25.46 312.50 24.74 20.83 24.87
June 19.83 27.04 441.17 24.65 19.83 24.74
July 53.33 26.81 489.00 24.90 53.33 25.07
August 62.50 26.27 514.00 24.73 62.50 24.88
September 25.33 26.40 390.33 24.69 21.17 24.80
October 29.83 24.77 197.33 24.95 9.00 25.03
November 87.83 24.08 136.83 24.62 3.50 24.66
December 127.83 24.00 72.00 24.49 0.67 24.50
             
Annual Sum or Average 1230.50 24.09 3087.83 24.53 218.33 24.64
Minimum of Months 19.83 23.12 1.50 23.13 0.00 23.13
Maximum of Months 443.33 27.04 514.00 25.01 62.50 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.58 287.33 20.41 287.33 20.33
February 451.00 21.11 151.67 20.87 151.67 20.72
March 509.17 22.12 29.17 22.04 29.17 21.96
April 400.17 22.77 18.00 22.84 0.00 22.84
May 254.00 23.17 63.50 23.38 0.00 23.38
June 118.00 23.43 107.67 23.83 0.00 23.83
July 60.33 23.52 267.50 24.11 0.00 24.11
August 73.50 23.38 311.17 24.03 0.00 24.03
September 227.83 23.11 101.50 23.43 0.00 23.43
October 463.67 22.44 3.67 22.43 3.00 22.42
November 489.00 21.51 92.67 21.33 92.67 21.20
December 497.00 20.82 226.17 20.67 226.17 20.58
             
Annual Sum or Average 4045.67 21.89 1660.00 22.01 790.00 21.80
Minimum of Months 60.33 20.58 3.67 20.41 0.00 20.33
Maximum of Months 509.17 23.52 311.17 24.11 287.33 24.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.59 248.33 20.38 248.33 20.29
February 376.17 21.45 108.83 21.20 108.83 21.05
March 389.83 22.38 18.33 22.31 16.00 22.24
April 229.00 22.86 72.50 23.27 0.00 23.27
May 172.67 23.31 127.67 23.88 7.67 23.96
June 84.33 24.01 201.00 24.42 14.50 24.55
July 54.17 24.87 289.67 24.61 20.33 24.75
August 55.00 24.59 319.83 24.44 17.67 24.56
September 159.17 23.35 168.67 23.95 7.33 24.02
October 320.33 22.49 31.17 22.67 0.50 22.67
November 407.83 21.62 75.17 21.44 74.17 21.30
December 422.00 20.92 191.33 20.72 191.33 20.62
             
Annual Sum or Average 3097.50 22.00 1852.50 22.39 706.67 22.20
Minimum of Months 54.17 20.59 18.33 20.38 0.00 20.29
Maximum of Months 427.00 24.87 319.83 24.61 248.33 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 466.83 21.17 181.33 20.96 172.67 20.80
February 362.33 21.86 121.67 22.05 65.17 21.89
March 351.83 22.42 91.00 22.73 9.83 22.69
April 247.33 22.93 133.33 23.50 5.00 23.54
May 200.67 23.37 181.17 23.89 12.50 23.99
June 124.67 23.69 222.33 24.17 12.00 24.26
July 79.50 24.29 331.50 24.43 18.17 24.55
August 59.50 24.35 373.33 24.35 16.50 24.45
September 130.00 23.57 268.17 24.16 14.33 24.26
October 299.00 22.87 131.50 23.41 10.83 23.50
November 416.50 22.03 75.33 22.16 39.50 22.10
December 442.67 21.41 170.33 21.35 141.83 21.18
             
Annual Sum or Average 3180.83 22.30 2281.00 22.89 518.33 22.78
Minimum of Months 59.50 21.17 75.33 20.96 5.00 20.80
Maximum of Months 466.83 24.35 373.33 24.43 172.67 24.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.96 202.50 20.73 202.50 20.60
February 420.67 21.61 95.33 21.42 89.33 21.25
March 423.00 22.52 35.67 22.58 10.00 22.54
April 274.17 23.11 95.17 23.50 5.83 23.55
May 170.17 23.64 183.67 24.09 17.00 24.23
June 73.83 23.98 252.83 24.33 11.33 24.42
July 38.50 25.65 391.00 24.63 23.17 24.75
August 34.67 24.76 417.17 24.40 14.33 24.48
September 123.00 23.77 250.00 24.22 17.50 24.35
October 365.67 22.78 57.50 23.03 1.50 23.04
November 457.83 21.89 48.33 21.84 38.83 21.75
December 491.17 21.29 136.17 21.10 136.17 20.98
             
Annual Sum or Average 3374.67 22.18 2165.33 22.72 567.50 22.59
Minimum of Months 34.67 20.96 35.67 20.73 1.50 20.60
Maximum of Months 502.00 25.65 417.17 24.63 202.50 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.08 389.83 19.95 389.83 19.90
February 454.00 20.50 266.67 20.27 266.67 20.16
March 511.50 21.34 150.50 21.10 150.50 20.95
April 428.17 22.20 53.33 22.09 42.50 21.97
May 301.50 22.67 57.33 22.89 2.83 22.87
June 170.00 23.13 102.00 23.55 0.00 23.55
July 114.67 23.33 255.83 23.95 0.00 23.95
August 130.00 23.17 282.00 23.85 0.33 23.86
September 293.83 22.62 76.50 22.93 0.00 22.93
October 494.00 21.69 65.17 21.50 65.17 21.36
November 489.00 20.70 228.50 20.45 228.50 20.32
December 497.00 20.21 383.67 20.10 383.67 20.06
             
Annual Sum or Average 4385.67 21.38 2311.33 21.38 1530.00 21.12
Minimum of Months 114.67 20.08 53.33 19.95 0.00 19.90
Maximum of Months 511.50 23.33 389.83 23.95 389.83 23.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.13 365.67 19.98 365.67 19.92
February 454.00 20.86 229.67 20.57 229.67 20.42
March 483.17 21.81 100.17 21.53 99.00 21.33
April 292.50 22.40 99.67 22.64 25.67 22.52
May 215.33 22.78 154.33 23.47 9.83 23.51
June 110.00 23.61 244.67 24.19 14.83 24.31
July 91.00 24.22 345.33 24.39 21.17 24.51
August 90.17 24.07 378.50 24.27 20.00 24.38
September 210.67 22.73 182.83 23.49 5.83 23.55
October 409.17 21.86 61.33 21.77 45.67 21.63
November 486.50 20.87 204.83 20.59 204.83 20.44
December 497.00 20.29 351.50 20.14 351.50 20.08
             
Annual Sum or Average 3841.50 21.48 2718.50 21.79 1393.67 21.52
Minimum of Months 90.17 20.13 61.33 19.98 5.83 19.92
Maximum of Months 502.00 24.22 378.50 24.39 365.67 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 486.33 20.59 290.00 20.30 286.33 20.16
February 386.33 21.17 197.67 21.09 161.83 20.88
March 388.17 21.72 143.83 21.75 87.83 21.53
April 285.33 22.35 144.17 22.80 33.83 22.70
May 238.33 22.80 168.67 23.46 15.50 23.54
June 162.83 23.32 206.33 23.94 12.83 24.04
July 118.00 23.80 312.00 24.27 17.83 24.38
August 110.33 23.71 349.33 24.19 15.00 24.29
September 196.33 22.99 230.00 23.77 11.67 23.85
October 337.33 22.07 133.50 22.51 34.00 22.42
November 444.83 21.21 179.67 21.11 150.00 20.90
December 460.33 20.69 280.50 20.48 267.83 20.34
             
Annual Sum or Average 3614.50 21.74 2635.67 22.15 1094.50 21.91
Minimum of Months 110.33 20.59 133.50 20.30 11.67 20.16
Maximum of Months 486.33 23.80 349.33 24.27 286.33 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.35 313.00 20.13 313.00 20.03
February 434.00 21.00 202.83 20.73 199.67 20.58
March 452.00 21.83 100.00 21.70 82.83 21.53
April 319.50 22.54 99.33 22.88 19.83 22.86
May 228.67 23.13 169.67 23.71 16.67 23.85
June 121.00 23.54 232.00 24.11 12.00 24.21
July 76.00 24.52 363.00 24.51 24.00 24.63
August 70.17 24.03 381.83 24.31 19.67 24.38
September 200.33 23.22 211.17 23.84 16.50 23.96
October 413.33 22.12 65.83 22.20 28.83 22.11
November 473.17 21.14 156.83 20.93 150.17 20.77
December 496.50 20.65 286.00 20.44 286.00 20.35
             
Annual Sum or Average 3786.67 21.69 2581.50 22.06 1169.17 21.83
Minimum of Months 70.17 20.35 65.83 20.13 12.00 20.03
Maximum of Months 502.00 24.52 381.83 24.51 313.00 24.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 1.50 27.00 454.00 27.00 1.50 27.00
March 9.17 27.00 514.00 27.00 9.17 27.00
April 94.83 27.00 485.00 27.00 94.83 27.00
May 3.83 27.00 508.00 27.00 3.83 27.00
June 38.00 27.00 496.00 27.00 38.00 27.00
July 181.00 27.00 497.00 27.00 181.00 27.00
August 330.33 27.00 514.00 27.00 330.33 27.00
September 28.67 27.00 485.00 27.00 28.67 27.00
October 10.33 27.00 502.00 27.00 10.33 27.00
November 8.17 27.00 489.00 27.00 8.17 27.00
December 4.83 27.00 497.00 27.00 4.83 27.00
             
Annual Sum or Average 710.67 27.00 5943.00 27.00 710.67 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 330.33 27.00 514.00 27.00 330.33 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.33 25.36 438.50 26.95 0.00 26.95
February 0.00 0.00 430.00 27.00 0.00 27.00
March 0.67 27.00 514.00 27.00 0.67 27.00
April 8.17 27.00 485.00 27.00 8.17 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 7.33 27.00 496.00 27.00 7.33 27.00
July 33.50 27.00 497.00 27.00 33.50 27.00
August 62.17 27.00 514.00 27.00 62.17 27.00
September 9.83 27.00 485.00 27.00 9.83 27.00
October 3.50 27.00 502.00 27.00 3.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 139.50 26.83 5855.50 27.00 125.17 27.00
Minimum of Months 0.00 0.00 430.00 26.95 0.00 26.95
Maximum of Months 62.17 27.00 514.00 27.00 62.17 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 112.67 24.56 311.67 26.21 13.67 26.10
February 21.33 27.01 352.17 27.00 0.00 27.00
March 0.67 27.00 483.67 27.00 0.67 27.00
April 10.83 27.00 485.00 27.00 10.83 27.00
May 2.50 27.00 508.00 27.00 2.50 27.00
June 15.17 27.00 496.00 27.00 15.17 27.00
July 61.17 27.00 497.00 27.00 61.17 27.00
August 81.33 27.00 514.00 27.00 81.33 27.00
September 13.50 27.00 485.00 27.00 13.50 27.00
October 3.33 27.00 502.00 27.00 3.33 27.00
November 0.00 0.00 465.00 27.00 0.00 27.00
December 5.00 27.00 422.33 27.00 0.00 27.00
             
Annual Sum or Average 327.50 26.16 5521.83 26.94 202.17 26.93
Minimum of Months 0.00 0.00 311.67 26.21 0.00 26.10
Maximum of Months 112.67 27.01 514.00 27.00 81.33 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 308.50 27.00 502.00 27.00 308.50 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.01 497.00 27.01 497.00 27.01
August 514.00 27.01 514.00 27.01 514.00 27.01
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5749.50 27.00 5943.00 27.00 5749.50 27.00
Minimum of Months 308.50 27.00 454.00 27.00 308.50 27.00
Maximum of Months 514.00 27.01 514.00 27.01 514.00 27.01



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 26.82456 0.78235 17.99153
February 454.00000 27.00006 27.11667 0.84657 20.24082
March 514.00000 27.00003 28.03201 0.91083 22.58678
April 485.00000 27.00002 30.77601 0.98724 25.63789
May 508.00000 27.00023 33.75893 0.25054 6.39290
June 496.00000 27.00026 35.04277 0.32334 7.23919
July 497.00000 27.00029 36.25542 0.40234 8.44935
August 514.00000 27.00066 36.85465 0.44005 9.12406
September 485.00000 27.00060 36.59854 0.28249 6.75198
October 502.00000 27.00012 33.28876 0.93253 23.40825
November 489.00000 27.00009 31.33036 0.92616 23.16782
December 497.00000 27.00000 27.21633 0.91008 22.52940
           
Annual Sum or Average 5943.00000 27.00020 31.95575 0.66434 16.07677
Minimum of Months 454.00000 27.00000 26.82456 0.25054 6.39290
Maximum of Months 514.00000 27.00066 36.85465 0.98724 25.63789



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.94677 26.98546 0.63438 13.67783
February 454.00000 27.00006 27.11624 0.71092 15.84390
March 514.00000 27.00003 28.01099 0.78768 18.20049
April 485.00000 27.00002 30.75475 0.86474 20.88977
May 508.00000 27.00022 33.77480 0.17441 5.77027
June 496.00000 27.00025 35.04069 0.22856 6.18375
July 497.00000 27.00030 36.25521 0.28999 6.86417
August 514.00000 27.00071 36.85580 0.31161 7.15375
September 485.00000 27.00057 36.69479 0.20789 6.03113
October 502.00000 27.00011 33.28278 0.83478 19.78284
November 489.00000 27.00008 31.31523 0.77492 17.76414
December 497.00000 27.00000 27.20482 0.71466 15.84020
           
Annual Sum or Average 5943.00000 26.99570 31.97216 0.54278 12.79628
Minimum of Months 454.00000 26.94677 26.98546 0.17441 5.77027
Maximum of Months 514.00000 27.00071 36.85580 0.86474 20.88977



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.38126 27.51587 0.45294 11.31918
February 454.00000 27.00036 27.12872 0.63328 13.78738
March 514.00000 27.00003 28.02091 0.72361 16.25458
April 485.00000 27.00002 30.76199 0.82401 19.54257
May 508.00000 27.00023 33.79256 0.14284 5.72815
June 496.00000 27.00025 35.04676 0.21707 6.17626
July 497.00000 27.00031 36.25435 0.28635 6.91959
August 514.00000 27.00061 36.85527 0.30363 7.15262
September 485.00000 27.00055 36.76571 0.17152 5.88363
October 502.00000 27.00011 33.30826 0.77582 17.85435
November 489.00000 27.00009 31.33235 0.69255 15.28513
December 497.00000 27.00000 27.20985 0.62655 13.40908
           
Annual Sum or Average 5943.00000 26.94795 32.03104 0.48591 11.57979
Minimum of Months 454.00000 26.38126 27.12872 0.14284 5.72815
Maximum of Months 514.00000 27.00061 36.85527 0.82401 19.54257



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99998 30.01443 1.03063 27.43619
February 454.00000 27.00016 30.49244 1.20676 35.59037
March 514.00000 27.00026 28.85015 1.35034 42.89623
April 485.00000 27.00165 29.80154 1.49958 50.87956
May 508.00000 27.00011 32.17890 0.50329 10.35666
June 496.00000 27.00059 32.83461 0.73599 16.43404
July 497.00000 27.00539 35.87609 0.97517 25.12260
August 514.00000 27.01133 36.82310 1.17706 34.15084
September 485.00000 27.00007 36.86777 0.56947 11.86694
October 502.00000 27.00020 31.22688 1.24673 37.56805
November 489.00000 27.00049 31.23209 1.38134 44.52708
December 497.00000 27.00041 28.52533 1.48039 49.83862
           
Annual Sum or Average 5943.00000 27.00175 32.06970 1.09545 32.18347
Minimum of Months 454.00000 26.99998 28.52533 0.50329 10.35666
Maximum of Months 514.00000 27.01133 36.86777 1.49958 50.87956



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.55699 28.77209 0.39906 9.03993
February 454.00000 24.55972 28.61657 0.40508 8.87478
March 514.00000 24.52739 28.24823 0.40808 8.90752
April 485.00000 24.63720 31.69408 0.46153 10.08831
May 508.00000 24.62012 36.32828 -0.3560 8.78358
June 496.00000 24.60549 38.22945 -0.3356 8.39972
July 497.00000 24.75694 43.15899 -0.2493 7.69898
August 514.00000 24.62974 47.00004 -0.2529 7.46640
September 485.00000 24.69698 44.04377 -0.2657 7.96116
October 502.00000 24.72017 34.90549 0.50615 11.15925
November 489.00000 24.69737 33.16000 0.48426 10.65259
December 497.00000 24.65142 27.79271 0.42730 9.39661
           
Annual Sum or Average 5943.00000 24.63830 35.21173 0.13310 9.03134
Minimum of Months 454.00000 24.52739 27.79271 -0.3560 7.46640
Maximum of Months 514.00000 24.75694 47.00004 0.50615 11.15925



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.16164 31.60972 0.32084 7.60864
February 454.00000 24.25181 30.32558 0.34949 7.78581
March 514.00000 24.31386 29.87420 0.38297 8.32202
April 485.00000 24.32683 32.72224 0.42233 8.99413
May 508.00000 24.29873 37.79206 -0.4279 9.28994
June 496.00000 24.28323 39.87347 -0.3969 8.68968
July 497.00000 24.30784 44.64583 -0.3431 7.80285
August 514.00000 24.23302 48.49725 -0.3300 7.52080
September 485.00000 24.35778 45.43533 -0.3505 8.17926
October 502.00000 24.38665 36.59726 0.44763 9.52979
November 489.00000 24.39554 35.29693 0.43265 9.25276
December 497.00000 24.37830 30.23634 0.38634 8.42687
           
Annual Sum or Average 5943.00000 24.30782 36.95933 0.07156 8.45208
Minimum of Months 454.00000 24.16164 29.87420 -0.4279 7.52080
Maximum of Months 514.00000 24.39554 48.49725 0.44763 9.52979



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.82428 34.51212 -0.0350 5.96031
February 454.00000 23.40916 32.94668 0.11712 5.97791
March 514.00000 23.88903 32.32054 0.25077 6.51777
April 485.00000 24.05913 34.73310 0.32056 7.38567
May 508.00000 24.13631 38.74610 -0.5136 10.81641
June 496.00000 24.15686 40.70446 -0.4789 10.02008
July 497.00000 24.22616 45.81219 -0.4191 8.99880
August 514.00000 24.19039 49.43631 -0.3977 8.58853
September 485.00000 24.20605 46.45202 -0.4332 9.27250
October 502.00000 24.02010 38.90226 0.33451 7.56350
November 489.00000 23.71104 38.18418 0.23134 6.52134
December 497.00000 23.25665 33.49729 0.07601 5.61849
           
Annual Sum or Average 5943.00000 23.84348 38.89802 -0.0812 7.78482
Minimum of Months 454.00000 22.82428 32.32054 -0.5136 5.61849
Maximum of Months 514.00000 24.22616 49.43631 0.33451 10.81641



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.25841 35.24093 -0.4364 12.15685
February 454.00000 21.91650 35.62465 -0.2580 9.24296
March 514.00000 22.92102 34.48632 -0.0020 6.25015
April 485.00000 23.50244 36.32428 0.17546 6.44332
May 508.00000 23.85323 39.71347 -0.6199 13.84607
June 496.00000 24.05344 41.04442 -0.5160 10.88281
July 497.00000 24.15708 46.02239 -0.4379 9.33083
August 514.00000 24.11671 49.73444 -0.4232 9.06765
September 485.00000 23.90192 47.71515 -0.5510 11.95589
October 502.00000 23.18056 41.42178 0.11474 6.26771
November 489.00000 22.27154 41.99962 -0.1311 7.18717
December 497.00000 21.54541 36.69552 -0.3540 9.29801
           
Annual Sum or Average 5943.00000 23.06576 40.53306 -0.2874 9.32982
Minimum of Months 454.00000 21.25841 34.48632 -0.6199 6.25015
Maximum of Months 514.00000 24.15708 49.73444 0.17546 13.84607



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.31314 31.83938 -0.1596 6.48176
February 454.00000 22.85661 31.98663 -0.0184 6.21962
March 514.00000 23.54606 30.91878 0.15380 5.99845
April 485.00000 23.94485 32.90619 0.29266 7.17102
May 508.00000 24.04978 37.42351 -0.5346 11.72484
June 496.00000 24.20005 39.23313 -0.4358 9.38384
July 497.00000 24.28659 43.90836 -0.3503 7.99434
August 514.00000 24.19815 47.83873 -0.3540 7.96514
September 485.00000 24.07334 45.47262 -0.4873 10.60655
October 502.00000 23.74063 37.62366 0.24938 6.72541
November 489.00000 23.36647 37.14683 0.13947 6.10987
December 497.00000 22.93700 32.38201 -0.0038 5.50660
           
Annual Sum or Average 5943.00000 23.63151 37.42880 -0.1272 7.66640
Minimum of Months 454.00000 22.31314 30.91878 -0.5346 5.50660
Maximum of Months 514.00000 24.28659 47.83873 0.29266 11.72484



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.26330 31.94700 -0.1710 6.59252
February 454.00000 22.89315 31.90170 -0.0046 6.40513
March 514.00000 23.46831 30.84801 0.15382 6.22119
April 485.00000 23.92730 32.67170 0.32586 7.98142
May 508.00000 24.12876 37.04209 -0.4542 11.03067
June 496.00000 24.26646 38.83638 -0.3410 8.92324
July 497.00000 24.33933 43.66310 -0.2712 8.03521
August 514.00000 24.21338 47.67243 -0.2786 8.01253
September 485.00000 24.14049 45.03668 -0.4058 10.03381
October 502.00000 23.71862 37.44143 0.26458 7.22933
November 489.00000 23.12475 37.66391 0.08626 6.13822
December 497.00000 22.55103 33.03984 -0.0903 5.92356
           
Annual Sum or Average 5943.00000 23.59141 37.35212 -0.1002 7.71809
Minimum of Months 454.00000 22.26330 30.84801 -0.4542 5.92356
Maximum of Months 514.00000 24.33933 47.67243 0.32586 11.03067



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.27764 31.71970 -0.1608 7.54626
February 454.00000 23.10879 31.12200 0.06901 7.69876
March 514.00000 23.57544 30.29488 0.20892 7.17691
April 485.00000 23.98980 32.36255 0.35566 8.72808
May 508.00000 24.08259 37.03417 -0.4688 11.57585
June 496.00000 24.24214 38.92778 -0.3808 9.32071
July 497.00000 24.36592 43.51160 -0.2628 7.87577
August 514.00000 24.27242 47.34821 -0.2429 7.62327
September 485.00000 24.22006 44.61212 -0.3289 9.40962
October 502.00000 23.88151 36.74686 0.34073 8.88129
November 489.00000 23.24678 37.06934 0.12918 7.20439
December 497.00000 22.74649 32.32262 -0.0279 6.89283
           
Annual Sum or Average 5943.00000 23.67146 36.96431 -0.0658 8.33123
Minimum of Months 454.00000 22.27764 30.29488 -0.4688 6.89283
Maximum of Months 514.00000 24.36592 47.34821 0.35566 11.57585



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.23348 30.01696 0.06030 5.83979
February 454.00000 23.98678 29.23649 0.27374 7.42754
March 514.00000 24.31649 28.43041 0.40564 8.88561
April 485.00000 24.55597 30.94514 0.55148 12.34744
May 508.00000 24.40900 36.13944 -0.3007 8.77012
June 496.00000 24.47801 38.14028 -0.2018 7.41444
July 497.00000 24.67620 42.51482 -0.0229 7.26550
August 514.00000 24.54560 46.43016 -0.0288 6.94954
September 485.00000 24.46247 43.82224 -0.2359 7.89891
October 502.00000 24.41078 35.23872 0.46423 10.16687
November 489.00000 24.33863 34.00382 0.40689 9.05480
December 497.00000 24.31193 28.63922 0.35668 7.98384
           
Annual Sum or Average 5943.00000 24.31197 35.34243 0.14240 8.33009
Minimum of Months 454.00000 23.23348 28.43041 -0.3007 5.83979
Maximum of Months 514.00000 24.67620 46.43016 0.55148 12.34744



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.58209 34.21851 -0.6180 14.66482
February 454.00000 21.12991 34.66210 -0.4514 11.28956
March 514.00000 22.14055 34.45843 -0.1859 6.91690
April 485.00000 23.00133 35.79073 0.05038 6.27819
May 508.00000 23.62128 38.82448 -0.7000 16.65848
June 496.00000 23.94477 40.22975 -0.5543 12.01975
July 497.00000 24.09565 44.79090 -0.4565 9.84671
August 514.00000 24.01491 48.84911 -0.4611 10.03022
September 485.00000 23.61327 47.26568 -0.6627 15.34548
October 502.00000 22.56312 41.42579 -0.0342 6.08807
November 489.00000 21.50934 40.87004 -0.3148 8.44115
December 497.00000 20.82193 35.50472 -0.5394 11.83396
           
Annual Sum or Average 5943.00000 22.59838 39.77480 -0.4108 10.78059
Minimum of Months 454.00000 20.58209 34.21851 -0.7000 6.08807
Maximum of Months 514.00000 24.09565 48.84911 0.05038 16.65848



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.58613 33.56279 -0.6172 14.79019
February 385.00000 21.50531 33.32291 -0.3620 9.90633
March 433.00000 22.53927 32.92829 -0.0815 6.75759
April 410.00000 23.48810 33.64845 0.19653 7.43212
May 430.00000 23.87891 37.40530 -0.5657 14.58525
June 418.00000 24.20544 38.93695 -0.3896 10.39073
July 422.00000 24.36501 43.48502 -0.2971 8.99622
August 433.00000 24.25367 47.39790 -0.2988 8.88399
September 410.00000 23.89928 45.62710 -0.5144 13.09821
October 427.00000 22.91134 39.76703 0.06048 6.64985
November 417.00000 21.66999 39.86792 -0.2789 8.36539
December 422.00000 20.92004 34.77275 -0.5178 11.65178
           
Annual Sum or Average 5034.00000 22.85968 38.42570 -0.3056 10.12632
Minimum of Months 385.00000 20.58613 32.92829 -0.6172 6.64985
Maximum of Months 433.00000 24.36501 47.39790 0.19653 14.79019



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.39753 32.80724 -0.3968 11.41758
February 454.00000 22.38991 32.15430 -0.1108 9.07509
March 514.00000 22.98509 32.10716 0.06873 7.53767
April 485.00000 23.58041 33.69417 0.24720 8.33852
May 508.00000 23.85591 37.74543 -0.5527 14.29097
June 496.00000 24.06322 39.55518 -0.4594 11.21641
July 497.00000 24.26261 44.04400 -0.3238 9.10416
August 514.00000 24.19557 47.83609 -0.2961 8.76586
September 485.00000 24.05177 45.30289 -0.3864 11.14481
October 502.00000 23.43834 38.48837 0.23811 8.69311
November 489.00000 22.37811 38.81696 -0.0861 8.17995
December 497.00000 21.73755 33.64231 -0.2927 9.78138
           
Annual Sum or Average 5943.00000 23.20112 38.05796 -0.1971 9.80218
Minimum of Months 454.00000 21.39753 32.10716 -0.5527 7.53767
Maximum of Months 514.00000 24.26261 47.83609 0.24720 14.29097



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.95652 33.56854 -0.5118 12.11308
February 454.00000 21.79882 33.27424 -0.2770 9.10333
March 514.00000 22.81006 32.78018 -0.0078 6.69134
April 485.00000 23.59767 33.97790 0.23342 7.84744
May 508.00000 23.98152 37.60623 -0.4985 13.07729
June 496.00000 24.16330 39.36985 -0.3961 9.88892
July 497.00000 24.41602 43.57107 -0.2219 8.13240
August 514.00000 24.28409 47.64681 -0.2570 8.17400
September 485.00000 24.07647 45.46141 -0.4222 11.05133
October 502.00000 23.18313 39.53773 0.13245 6.85733
November 489.00000 22.03720 39.64839 -0.1826 7.45239
December 497.00000 21.31882 34.56290 -0.4062 9.62259
           
Annual Sum or Average 5943.00000 23.06194 38.45288 -0.2347 9.16698
Minimum of Months 454.00000 20.95652 32.78018 -0.5118 6.69134
Maximum of Months 514.00000 24.41602 47.64681 0.23342 13.07729



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.07512 35.24658 -0.7901 21.02337
February 454.00000 20.49813 35.74236 -0.6488 17.00732
March 514.00000 21.34989 35.57303 -0.4009 10.20719
April 485.00000 22.41203 36.92061 -0.1013 7.27281
May 508.00000 23.23687 39.82294 -0.8348 22.36229
June 496.00000 23.76712 40.72673 -0.6152 14.23116
July 497.00000 23.97265 45.08406 -0.4946 11.11131
August 514.00000 23.88168 49.27929 -0.5057 11.51999
September 485.00000 23.17559 48.59836 -0.8170 21.31413
October 502.00000 21.72754 43.20742 -0.2514 7.98648
November 489.00000 20.70069 42.67358 -0.5491 13.68384
December 497.00000 20.20848 36.85294 -0.7425 18.64169
           
Annual Sum or Average 5943.00000 22.09719 40.84171 -0.5622 14.67509
Minimum of Months 454.00000 20.07512 35.24658 -0.8348 7.27281
Maximum of Months 514.00000 23.97265 49.27929 -0.1013 22.36229



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13176 35.14277 -0.7679 20.26596
February 454.00000 20.86337 35.15228 -0.5498 14.52863
March 514.00000 21.94488 34.42515 -0.2443 8.98586
April 485.00000 23.09315 34.86906 0.09930 7.65696
May 508.00000 23.59981 38.53003 -0.6509 17.95883
June 496.00000 24.06368 39.42189 -0.4214 11.27712
July 497.00000 24.22130 44.10086 -0.3214 9.48457
August 514.00000 24.12296 48.14017 -0.3213 9.44490
September 485.00000 23.55289 47.05325 -0.6242 17.01105
October 502.00000 22.26536 41.57791 -0.1078 7.72272
November 489.00000 20.88918 42.21232 -0.4992 12.88552
December 497.00000 20.29459 36.69624 -0.7127 17.79435
           
Annual Sum or Average 5943.00000 22.43329 39.80621 -0.4261 12.89902
Minimum of Months 454.00000 20.13176 34.42515 -0.7679 7.65696
Maximum of Months 514.00000 24.22130 48.14017 0.09930 20.26596



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.69957 34.12252 -0.6051 16.96321
February 454.00000 21.63886 33.35898 -0.3302 12.24147
March 514.00000 22.32133 33.12271 -0.1185 9.25405
April 485.00000 23.12167 34.60752 0.12256 8.58755
May 508.00000 23.52433 38.59845 -0.6721 19.14184
June 496.00000 23.88959 40.01394 -0.5187 13.41079
July 497.00000 24.14029 44.33527 -0.3613 10.36832
August 514.00000 24.07648 48.23424 -0.3359 10.06653
September 485.00000 23.72367 46.31821 -0.5082 15.23528
October 502.00000 22.79861 39.83645 0.06135 8.84834
November 489.00000 21.51784 40.73330 -0.3283 11.34337
December 497.00000 20.95146 35.29779 -0.5266 15.07847
           
Annual Sum or Average 5943.00000 22.70924 39.08632 -0.3439 12.54747
Minimum of Months 454.00000 20.69957 33.12271 -0.6721 8.58755
Maximum of Months 514.00000 24.14029 48.23424 0.12256 19.14184



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.35414 34.72309 -0.6935 18.09811
February 454.00000 21.13674 34.38207 -0.4669 13.15747
March 514.00000 22.11604 33.79202 -0.1938 8.48936
April 485.00000 23.10995 34.94793 0.10740 8.04760
May 508.00000 23.68315 38.39497 -0.6058 17.20231
June 496.00000 24.01928 39.77426 -0.4463 11.57993
July 497.00000 24.31941 43.79949 -0.2519 8.97249
August 514.00000 24.19215 47.97198 -0.2893 9.10225
September 485.00000 23.76821 46.43833 -0.5361 14.75340
October 502.00000 22.48468 41.01112 -0.0493 7.36275
November 489.00000 21.24009 41.34466 -0.4013 10.75415
December 497.00000 20.65344 35.93540 -0.6048 14.63610
           
Annual Sum or Average 5943.00000 22.60172 39.40864 -0.3689 11.83410
Minimum of Months 454.00000 20.35414 33.79202 -0.6935 7.36275
Maximum of Months 514.00000 24.31941 47.97198 0.10740 18.09811



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.138302E+09 2557.84 11-JAN-07:14 53.45 0.114994E+10 0.00 0.128824E+10 0.60 8.40 06-JAN-06:50 0.00 0.00
February 0.258965E+10 81684.00 27-FEB-15:05 106.12 0.214915E+11 0.00 0.240811E+11 1.31 8.66 27-FEB-13:00 0.00 0.00
March 0.814785E+10 70473.68 14-MAR-16:00 166.64 0.685549E+11 0.00 0.767028E+11 1.87 8.68 01-MAR-14:00 0.00 0.00
April 0.132145E+11 156607.94 27-APR-17:10 152.90 0.106735E+12 0.00 0.119950E+12 1.76 8.68 19-APR-15:50 0.00 0.00
May 0.215507E+11 159337.42 31-MAY-15:50 225.69 0.173634E+12 0.00 0.195185E+12 2.51 8.68 14-MAY-17:02 0.00 0.00
June 0.393448E+11 158760.36 20-JUN-13:05 342.38 0.314498E+12 0.00 0.353843E+12 3.92 8.68 19-JUN-11:30 0.00 0.00
July 0.660809E+11 161142.09 11-JUL-15:00 467.12 0.520582E+12 0.00 0.586663E+12 5.14 8.68 30-JUL-13:26 0.00 0.00
August 0.786909E+11 161013.90 25-AUG-10:00 526.87 0.608349E+12 0.00 0.687040E+12 5.74 8.68 10-AUG-05:03 0.00 0.00
September 0.337586E+11 160008.97 12-SEP-12:40 308.90 0.268305E+12 0.00 0.302064E+12 3.53 8.68 13-SEP-09:10 0.00 0.00
October 0.121264E+11 148060.70 04-OCT-14:20 138.24 0.999698E+11 0.00 0.112096E+12 1.55 8.68 02-OCT-11:50 0.00 0.00
November 0.208756E+10 55923.65 04-NOV-14:10 120.88 0.175218E+11 0.00 0.196094E+11 1.40 8.67 04-NOV-15:50 0.00 0.00
December 0.876658E+09 7511.79 16-DEC-07:13 138.46 0.729685E+10 0.00 0.817350E+10 1.55 8.40 05-DEC-16:00 0.00 0.00
                         
Annual Sum or Average 0.278607E+12     2747.67 0.220809E+13 0.00 0.248669E+13 2.58     0.00 0.00
Minimum of Months 0.138302E+09 2557.84   53.45 0.114994E+10 0.00 0.128824E+10 0.60 8.40   0.00 0.00
Maximum of Months 0.786909E+11 161142.09   526.87 0.608349E+12 0.00 0.687040E+12 5.74 8.68   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.193802E+10 85555.39 27-APR-14:40 7.33 0.153949E+11 0.00 0.173329E+11 0.08 8.63 27-APR-11:50 0.00 0.00
May 0.191547E+10 129764.95 04-MAY-14:05 7.92 0.154520E+11 0.00 0.173674E+11 0.09 8.64 15-MAY-12:20 0.00 0.00
June 0.340949E+10 124577.12 21-JUN-14:05 14.00 0.274168E+11 0.00 0.308263E+11 0.16 8.67 21-JUN-14:00 0.00 0.00
July 0.112324E+11 119876.84 31-JUL-16:00 42.00 0.869970E+11 0.00 0.982295E+11 0.44 8.96 19-JUL-13:30 0.00 0.00
August 0.256592E+11 129666.85 29-AUG-14:30 87.58 0.194047E+12 0.00 0.219706E+12 0.90 8.53 23-AUG-17:30 0.00 0.00
September 0.436203E+10 126655.58 11-SEP-15:25 17.67 0.347985E+11 0.00 0.391605E+11 0.20 8.50 11-SEP-16:20 0.00 0.00
October 0.159546E+09 67509.62 04-OCT-15:10 0.83 0.129060E+10 0.00 0.145015E+10 0.01 8.62 04-OCT-14:30 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.486763E+11     177.33 0.375397E+12 0.00 0.424073E+12 0.16     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.256592E+11 129764.95   87.58 0.194047E+12 0.00 0.219706E+12 0.90 8.96   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.751376E+09 744.00 1399.07 11-JAN-15:30 32930.79 12-JAN-20:20 18.62 18.33 15.73
February 0.305700E+10 672.00 43776.24 27-FEB-13:15 81995.08 27-FEB-15:05 19.24 18.34 15.73
March 0.579249E+10 744.00 43776.24 18-MAR-13:05 253581.12 18-MAR-16:01 19.87 18.35 15.74
April 0.181654E+11 720.00 43776.24 01-APR-10:30 663412.68 27-APR-16:00 21.45 18.79 15.74
May 0.180775E+11 744.00 43776.24 02-MAY-15:40 147943.64 05-MAY-16:00 19.31 18.71 15.73
June 0.358690E+11 720.00 43776.24 01-JUN-14:20 349762.70 28-JUN-17:00 20.55 19.17 15.73
July 0.606972E+11 744.00 43776.24 01-JUL-12:30 561951.19 31-JUL-18:00 24.01 20.59 15.74
August 0.849890E+11 744.00 43776.24 01-AUG-00:03 738720.34 25-AUG-15:00 28.94 22.23 15.74
September 0.249028E+11 720.00 43776.24 01-SEP-14:20 149352.10 22-SEP-16:00 19.43 18.82 15.74
October 0.813001E+10 744.00 43776.24 03-OCT-12:40 157073.89 04-OCT-15:00 19.37 18.37 15.74
November 0.539957E+10 720.00 43776.24 04-NOV-10:50 316543.95 04-NOV-15:00 19.80 18.36 15.74
December 0.444864E+10 744.00 3591.92 14-DEC-12:00 118351.00 05-DEC-16:00 20.21 18.33 15.74
                   
Annual Sum or Average 0.270280E+12 8760.00         20.92 19.04 15.73
Minimum of Months 0.751376E+09 672.00 1399.07   32930.79   18.62 18.33 15.73
Maximum of Months 0.849890E+11 744.00 43776.24   738720.34   28.94 22.23 15.74



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 197097.44 06-JAN-05:07 20.99 20.99 0.25
February 15021154.40 8.83 1271.93 27-FEB-15:30 727988.72 27-FEB-15:10 20.98 20.93 2.75
March 24201502.40 59.93 785.01 14-MAR-16:00 654108.48 14-MAR-16:00 21.15 21.00 6.75
April 0.418590E+09 80.48 14553.39 27-APR-11:40 1080964.43 27-APR-17:20 21.40 21.16 8.14
May 0.684250E+09 138.35 14553.39 04-MAY-13:00 1126746.19 31-MAY-15:50 21.58 21.21 12.71
June 0.114850E+10 238.20 14553.39 20-JUN-12:20 1145713.45 20-JUN-13:05 21.82 21.13 20.87
July 0.446509E+10 334.22 14553.39 06-JUL-15:40 1093017.37 21-JUL-16:00 22.25 21.17 27.58
August 0.750084E+10 367.41 14553.39 07-AUG-09:30 1095688.80 07-AUG-18:00 22.53 21.27 30.08
September 0.204882E+10 204.07 14553.39 11-SEP-12:50 1153739.66 12-SEP-12:50 21.79 21.21 18.75
October 84225408.59 85.34 1911.30 04-OCT-14:30 1103525.32 04-OCT-13:40 21.26 21.05 7.59
November 27814462.83 12.33 1817.60 04-NOV-14:20 541067.29 04-NOV-14:10 21.03 20.99 2.26
December 0.00 0.00 0.00 01-DEC-00:10 197221.28 26-DEC-06:50 20.99 20.97 1.59
                   
Annual Sum or Average 0.164174E+11 1529.18         21.49 21.09 11.67
Minimum of Months 0.00 0.00 0.00   197097.44   20.98 20.93 0.25
Maximum of Months 0.750084E+10 367.41 14553.39   1153739.66   22.53 21.27 30.08



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 20.99 20.99 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 20.98 20.98 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.15 21.15 0.00
April 0.196526E+09 6.42 14553.39 27-APR-12:20 978234.25 26-APR-15:00 21.40 21.36 0.45
May 75572349.95 4.25 14553.39 04-MAY-14:00 1004812.75 04-MAY-14:05 21.58 21.56 0.29
June 0.178837E+09 12.25 14553.39 20-JUN-13:40 1008885.73 22-JUN-14:50 21.82 21.75 0.86
July 0.164074E+10 35.42 14553.39 07-JUL-12:30 955469.64 18-JUL-14:05 22.25 22.07 2.41
August 0.393426E+10 78.58 14553.39 07-AUG-10:30 989992.40 21-AUG-15:00 22.53 22.14 5.36
September 0.671110E+09 13.58 14553.39 11-SEP-15:25 1053721.10 11-SEP-15:25 21.79 21.72 0.96
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 21.26 21.26 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.03 21.03 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.99 20.99 0.00
                   
Annual Sum or Average 0.669704E+10 150.50         21.49 21.42 0.87
Minimum of Months 0.00 0.00 0.00   0.00   20.98 20.98 0.00
Maximum of Months 0.393426E+10 78.58 14553.39   1053721.10   22.53 22.14 5.36



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.266835E+12 0.00 466.25 1286711.37 02-JAN-06:03 0.00 34.30 63.99 0.52 0.00 0.06 0.76 02-JAN-06:03
February 0.146528E+12 0.00 342.66 979699.44 15-FEB-06:02 0.00 30.92 56.28 0.31 0.00 0.04 0.58 15-FEB-06:02
March 0.592452E+11 0.00 296.44 926247.28 06-MAR-06:02 0.00 27.82 49.27 0.10 0.00 0.01 0.55 06-MAR-06:02
April 0.254784E+11 0.00 174.90 350590.30 03-APR-13:20 0.00 27.21 40.29 0.04 0.00 0.01 0.21 03-APR-13:20
May 0.652918E+10 0.00 68.84 285163.83 17-MAY-13:10 0.00 26.14 31.28 0.01 0.00 0.00 0.17 17-MAY-13:10
June 0.304543E+09 0.00 10.60 192785.50 13-JUN-09:20 0.00 26.53 27.33 0.00 0.00 0.00 0.11 13-JUN-09:20
July 72197734.44 0.00 0.33 114609.62 12-JUL-09:20 0.00 27.20 27.22 0.00 0.00 0.00 0.07 12-JUL-09:20
August 60002624.20 0.00 0.17 133347.78 03-AUG-09:05 0.00 28.05 28.06 0.00 0.00 0.00 0.08 03-AUG-09:05
September 0.112161E+10 0.00 25.38 248533.80 27-SEP-09:20 0.00 27.26 29.19 0.00 0.00 0.00 0.15 27-SEP-09:20
October 0.139294E+11 0.00 168.77 409461.33 30-OCT-05:03 0.00 25.32 38.05 0.02 0.00 0.00 0.24 30-OCT-05:03
November 0.988732E+11 0.00 315.40 1030791.32 24-NOV-05:11 0.00 28.31 51.55 0.18 0.00 0.02 0.61 24-NOV-05:11
December 0.201591E+12 0.00 418.38 1130970.57 18-DEC-05:11 0.00 31.34 59.69 0.38 0.00 0.04 0.67 18-DEC-05:11
                           
Annual Sum or Average 0.820568E+12 0.00 2288.13     0.00 28.36 41.78 0.13 0.00 0.02    
Minimum of Months 60002624.20 0.00 0.17 114609.62   0.00 25.32 27.22 0.00 0.00 0.00 0.07  
Maximum of Months 0.266835E+12 0.00 466.25 1286711.37   0.00 34.30 63.99 0.52 0.00 0.06 0.76  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 18.62 18.62 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 19.24 19.24 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 19.87 19.87 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 21.45 21.45 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 19.31 19.31 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 20.55 20.55 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 24.01 24.01 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 28.94 28.94 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 19.43 19.43 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 19.37 19.37 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 19.80 19.80 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 20.21 20.21 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 20.92 20.92 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 18.62 18.62 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 28.94 28.94 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.662817E+09 0.00 39.58 0.662817E+09 0.00 0.00 0.00 0.00 18269.41 20-JAN-13:30 18269.41 20-JAN-13:30 0.00 0.00 0.00
February 0.484643E+10 0.00 76.82 0.484643E+10 0.00 0.00 0.00 0.00 54544.12 27-FEB-15:00 54544.12 27-FEB-15:00 0.00 0.00 0.00
March 0.555053E+10 0.00 102.28 0.555053E+10 0.00 0.00 0.00 0.00 50819.24 02-MAR-13:05 50819.24 02-MAR-13:05 0.00 0.00 0.00
April 0.103958E+11 0.00 106.94 0.103958E+11 0.00 0.00 0.00 0.00 120823.86 27-APR-14:40 120823.86 27-APR-14:40 0.00 0.00 0.00
May 0.160577E+11 0.00 181.97 0.160521E+11 0.00 0.00 0.00 0.00 97110.43 04-MAY-15:00 97110.43 04-MAY-15:00 0.00 0.00 0.00
June 0.314536E+11 0.00 295.58 0.314473E+11 0.00 0.00 0.00 0.00 108733.24 28-JUN-15:20 108733.24 28-JUN-15:20 0.00 0.00 0.00
July 0.572943E+11 0.00 425.30 0.565424E+11 0.00 0.00 0.00 0.00 142506.68 31-JUL-15:40 130390.44 31-JUL-15:10 0.00 0.00 0.00
August 0.778205E+11 0.00 493.96 0.756300E+11 0.00 0.00 0.00 0.00 147818.13 29-AUG-14:30 134791.38 29-AUG-15:10 0.00 0.00 0.00
September 0.249290E+11 0.00 250.77 0.245608E+11 0.00 0.00 0.00 0.00 124308.12 11-SEP-15:25 124308.12 11-SEP-15:25 0.00 0.00 0.00
October 0.465388E+10 0.00 77.50 0.465388E+10 0.00 0.00 0.00 0.00 75816.72 04-OCT-15:00 75816.72 04-OCT-15:00 0.00 0.00 0.00
November 0.496308E+10 0.00 101.38 0.496308E+10 0.00 0.00 0.00 0.00 41919.84 15-NOV-14:00 41919.84 15-NOV-14:00 0.00 0.00 0.00
December 0.583333E+10 0.00 128.36 0.583333E+10 0.00 0.00 0.00 0.00 46213.73 05-DEC-14:30 46213.73 05-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.244461E+12 0.00 2280.43 0.241138E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.662817E+09 0.00 39.58 0.662817E+09 0.00 0.00 0.00 0.00 18269.41   18269.41   0.00 0.00 0.00
Maximum of Months 0.778205E+11 0.00 493.96 0.756300E+11 0.00 0.00 0.00 0.00 147818.13   134791.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 30746.79 0.00 10.25 30746.79 0.00 0.00 0.00 0.00 2.46 02-JAN-07:00 2.46 02-JAN-07:00 0.00 0.00 0.00
February 0.142385E+11 0.00 36.87 0.142385E+11 0.00 0.00 0.00 0.00 537474.20 27-FEB-15:05 537474.20 27-FEB-15:05 0.00 0.00 0.00
March 0.598878E+11 0.00 100.56 0.598878E+11 0.00 0.00 0.00 0.00 520792.56 14-MAR-15:40 520792.56 14-MAR-15:40 0.00 0.00 0.00
April 0.966835E+11 0.00 128.30 0.966835E+11 0.00 0.00 0.00 0.00 1021709.20 27-APR-14:40 1021709.20 27-APR-14:40 0.00 0.00 0.00
May 0.146480E+12 0.00 191.23 0.146420E+12 0.00 0.00 0.00 0.00 915515.04 04-MAY-15:00 915515.04 04-MAY-15:00 0.00 0.00 0.00
June 0.258587E+12 0.00 292.52 0.258563E+12 0.00 0.00 0.00 0.00 973877.44 28-JUN-15:20 973877.44 28-JUN-15:20 0.00 0.00 0.00
July 0.453434E+12 0.00 381.67 0.449046E+12 0.00 0.00 0.00 0.00 1237752.84 31-JUL-16:00 1118556.51 31-JUL-14:30 0.00 0.00 0.00
August 0.599350E+12 0.00 398.90 0.584434E+12 0.00 0.00 0.00 0.00 1305463.20 29-AUG-14:30 1210309.55 29-AUG-15:20 0.00 0.00 0.00
September 0.235719E+12 0.00 261.88 0.231243E+12 0.00 0.00 0.00 0.00 1102687.18 11-SEP-15:25 1041412.31 11-SEP-15:25 0.00 0.00 0.00
October 0.881890E+11 0.00 121.35 0.881890E+11 0.00 0.00 0.00 0.00 723952.10 04-OCT-13:20 723952.10 04-OCT-13:20 0.00 0.00 0.00
November 0.103491E+11 0.00 27.89 0.103491E+11 0.00 0.00 0.00 0.00 392871.01 04-NOV-14:05 392871.01 04-NOV-14:05 0.00 0.00 0.00
December 28104.41 0.00 9.82 28104.41 0.00 0.00 0.00 0.00 2.99 26-DEC-06:02 2.99 26-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.196292E+13 0.00 1961.24 0.193905E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 28104.41 0.00 9.82 28104.41 0.00 0.00 0.00 0.00 2.46   2.46   0.00 0.00 0.00
Maximum of Months 0.599350E+12 0.00 398.90 0.584434E+12 0.00 0.00 0.00 0.00 1305463.20   1210309.55   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.390035E+09 0.00 10.42 0.390035E+09 0.00 0.00 0.00 0.00 27486.27 27-FEB-15:00 27486.27 27-FEB-15:00 0.00 0.00 0.00
March 0.101644E+10 0.00 31.30 0.101644E+10 0.00 0.00 0.00 0.00 33301.00 01-MAR-15:00 33301.00 01-MAR-15:00 0.00 0.00 0.00
April 0.764622E+10 0.00 80.78 0.764622E+10 0.00 0.00 0.00 0.00 119309.40 27-APR-14:40 119309.40 27-APR-14:40 0.00 0.00 0.00
May 0.141105E+11 0.00 169.23 0.141086E+11 0.00 0.00 0.00 0.00 100532.12 04-MAY-15:00 100532.12 04-MAY-15:00 0.00 0.00 0.00
June 0.268694E+11 0.00 280.26 0.268676E+11 0.00 0.00 0.00 0.00 116132.20 28-JUN-15:20 116132.20 28-JUN-15:20 0.00 0.00 0.00
July 0.481077E+11 0.00 367.41 0.477006E+11 0.00 0.00 0.00 0.00 142173.58 31-JUL-16:00 131635.89 31-JUL-14:30 0.00 0.00 0.00
August 0.632128E+11 0.00 388.53 0.618101E+11 0.00 0.00 0.00 0.00 146685.64 10-AUG-15:40 140257.68 10-AUG-15:10 0.00 0.00 0.00
September 0.215210E+11 0.00 237.42 0.212331E+11 0.00 0.00 0.00 0.00 111213.88 11-SEP-15:25 111213.88 11-SEP-15:25 0.00 0.00 0.00
October 0.309679E+10 0.00 60.65 0.309679E+10 0.00 0.00 0.00 0.00 66071.09 04-OCT-15:00 66071.09 04-OCT-15:00 0.00 0.00 0.00
November 0.516383E+09 0.00 9.83 0.516383E+09 0.00 0.00 0.00 0.00 29528.85 04-NOV-14:10 29528.85 04-NOV-14:10 0.00 0.00 0.00
December 26462.81 0.00 0.02 26462.81 0.00 0.00 0.00 0.00 441.05 26-DEC-05:01 441.05 26-DEC-05:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.186487E+12 0.00 1635.85 0.184386E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.632128E+11 0.00 388.53 0.618101E+11 0.00 0.00 0.00 0.00 146685.64   140257.68   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 44228642.85 0.00 5.23 44228642.85 0.00 0.00 0.00 0.00 7411.38 11-JAN-07:14 7411.38 11-JAN-07:14 0.00 0.00 0.00
February 0.969962E+09 0.00 31.10 0.883147E+09 0.00 0.00 0.00 0.00 45234.39 24-FEB-07:12 34568.59 27-FEB-15:00 0.00 0.00 0.00
March 0.674618E+09 0.00 29.33 0.668730E+09 0.00 0.00 0.00 0.00 34735.90 10-MAR-07:13 20151.57 09-MAR-07:13 0.00 0.00 0.00
April 0.456647E+10 0.00 59.21 0.455548E+10 0.00 0.00 0.00 0.00 58214.48 27-APR-15:00 58214.48 27-APR-15:00 0.00 0.00 0.00
May 0.970129E+10 0.00 139.06 0.965838E+10 0.00 0.00 0.00 0.00 57941.51 15-MAY-16:00 57941.51 15-MAY-16:00 0.00 0.00 0.00
June 0.206019E+11 0.00 253.10 0.200158E+11 0.00 0.00 0.00 0.00 60255.75 12-JUN-06:35 54056.69 20-JUN-16:00 0.00 0.00 0.00
July 0.374619E+11 0.00 323.88 0.350854E+11 0.00 0.00 0.00 0.00 96175.88 31-JUL-10:10 74507.27 24-JUL-11:00 0.00 0.00 0.00
August 0.481420E+11 0.00 351.14 0.456342E+11 0.00 0.00 0.00 0.00 79037.71 07-AUG-12:05 78128.18 21-AUG-15:05 0.00 0.00 0.00
September 0.172572E+11 0.00 228.31 0.166330E+11 0.00 0.00 0.00 0.00 76932.25 11-SEP-15:25 74437.60 11-SEP-15:25 0.00 0.00 0.00
October 0.288060E+10 0.00 63.88 0.282953E+10 0.00 0.00 0.00 0.00 41515.20 04-OCT-15:00 41515.20 04-OCT-15:00 0.00 0.00 0.00
November 0.560913E+09 0.00 12.02 0.540625E+09 0.00 0.00 0.00 0.00 38483.62 04-NOV-06:14 24654.03 06-NOV-07:25 0.00 0.00 0.00
December 9118321.70 0.00 0.28 7223948.90 0.00 0.00 0.00 0.00 22536.97 16-DEC-07:13 13587.33 16-DEC-07:13 0.00 0.00 0.00
                               
Annual Sum or Average 0.142870E+12 0.00 1496.55 0.136556E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 9118321.70 0.00 0.28 7223948.90 0.00 0.00 0.00 0.00 7411.38   7411.38   0.00 0.00 0.00
Maximum of Months 0.481420E+11 0.00 351.14 0.456342E+11 0.00 0.00 0.00 0.00 96175.88   78128.18   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.451994E+10 0.370919E+10 740.92 0.451991E+10 24252.20 0.00 0.02 09-JAN-12:00 0.01 11-JAN-22:40 3119.97 09-JAN-12:00 3119.97 09-JAN-12:00 8.35 11-JAN-23:00 1747.42 09-JAN-12:00 0.00
February 0.679760E+10 0.412479E+10 597.87 0.676016E+10 37442340.00 0.00 0.06 27-FEB-15:00 0.01 28-FEB-08:65 18252.01 27-FEB-15:00 18252.01 27-FEB-15:00 69.41 26-FEB-16:40 6092.76 27-FEB-15:00 0.00
March 0.118246E+11 0.582800E+10 689.88 0.114416E+11 0.383008E+09 0.00 0.36 18-MAR-16:00 0.01 11-MAR-06:02 126263.66 18-MAR-16:00 126263.66 18-MAR-16:00 4681.13 09-MAR-12:00 37958.10 18-MAR-16:00 0.00
April 0.766841E+11 0.238198E+11 629.46 0.723599E+11 0.432416E+10 0.00 1.00 01-APR-16:25 0.01 02-APR-22:40 408346.75 27-APR-16:00 408346.75 27-APR-16:00 61327.91 28-APR-13:00 129862.29 01-APR-16:25 0.00
May 0.430446E+10 0.383360E+10 491.93 0.407864E+10 0.225816E+09 0.00 0.21 05-MAY-16:00 0.01 26-MAY-10:05 84113.33 05-MAY-16:00 72610.43 05-MAY-16:00 11502.89 05-MAY-16:00 24969.32 05-MAY-16:00 0.00
June 0.331722E+11 0.122768E+11 375.93 0.316610E+11 0.151122E+10 0.00 0.52 28-JUN-17:00 0.00 19-JUN-00:40 214401.62 28-JUN-17:00 214401.62 28-JUN-17:00 16922.20 21-JUN-17:00 64863.59 28-JUN-17:00 0.00
July 0.208486E+12 0.592265E+11 564.95 0.177262E+12 0.312237E+11 0.00 0.78 31-JUL-17:50 0.01 19-JUL-22:40 357081.26 27-JUL-16:00 318322.62 24-JUL-15:00 84851.24 27-JUL-18:50 104382.47 24-JUL-15:00 0.00
August 0.534071E+12 0.143263E+12 684.58 0.426856E+12 0.107215E+12 0.00 1.00 24-AUG-12:05 0.01 31-AUG-23:25 473401.08 29-AUG-11:00 411051.13 29-AUG-12:05 158390.79 30-AUG-09:00 136475.63 10-AUG-17:00 0.00
September 0.339362E+10 0.389142E+10 233.21 0.286077E+10 0.532846E+09 0.00 0.22 22-SEP-16:00 0.01 28-SEP-21:03 86201.97 22-SEP-16:00 73177.16 22-SEP-16:00 13024.81 22-SEP-16:00 25437.91 22-SEP-16:00 0.00
October 0.380186E+10 0.372642E+10 501.66 0.372578E+10 76086205.53 0.00 0.21 04-OCT-15:00 0.01 25-OCT-08:25 71684.43 04-OCT-15:00 71684.43 04-OCT-15:00 2258.12 08-OCT-13:52 22369.58 04-OCT-15:00 0.00
November 0.997547E+10 0.518603E+10 550.38 0.866579E+10 0.130968E+10 0.00 0.44 04-NOV-14:10 0.01 01-NOV-21:30 180788.58 04-NOV-14:10 135467.22 04-NOV-14:10 49531.40 04-NOV-13:00 47533.52 04-NOV-15:00 0.00
December 0.130203E+11 0.626312E+10 721.90 0.121201E+11 0.900175E+09 0.00 0.03 13-DEC-24:00 0.01 29-DEC-00:10 6025.50 27-DEC-00:40 5621.12 04-DEC-05:11 608.41 10-DEC-21:30 2646.03 18-DEC-19:40 0.00
                                       
Annual Sum or Average 0.910050E+12 0.275149E+12 6782.67 0.762311E+12 0.147739E+12 0.00                         0.00
Minimum of Months 0.339362E+10 0.370919E+10 233.21 0.286077E+10 24252.20 0.00 0.02   0.00   3119.97   3119.97   8.35   1747.42   0.00
Maximum of Months 0.534071E+12 0.143263E+12 740.92 0.426856E+12 0.107215E+12 0.00 1.00   0.01   473401.08   411051.13   158390.79   136475.63   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.407884E+10 0.979488E+09 744.00 0.407851E+10 326849.25 0.00 0.27 08-JAN-16:15 0.12 07-JAN-08:00 2127.82 08-JAN-16:15 2127.82 08-JAN-16:15 16.34 02-JAN-07:05 509.92 08-JAN-16:15 0.00
February 0.879396E+10 0.196192E+10 672.00 0.878354E+10 10423281.98 0.00 0.54 12-FEB-16:45 0.37 18-FEB-08:00 4449.77 12-FEB-16:45 4449.77 12-FEB-16:45 128.12 24-FEB-11:10 1007.82 12-FEB-16:45 0.00
March 0.152870E+11 0.324094E+10 744.00 0.152789E+11 8065868.49 0.00 0.81 31-MAR-24:00 0.58 01-MAR-07:05 7574.12 31-MAR-24:00 7574.12 31-MAR-24:00 136.81 09-MAR-17:00 1518.65 31-MAR-24:00 0.00
April 0.199884E+11 0.409177E+10 720.00 0.199748E+11 13662674.14 0.00 0.99 01-APR-17:32 0.30 30-APR-24:00 8685.55 23-APR-18:03 8685.55 23-APR-18:03 167.24 28-APR-13:00 2439.23 01-APR-17:02 0.00
May 0.561126E+10 0.129190E+10 744.00 0.557495E+10 36311755.53 0.00 0.46 31-MAY-24:00 0.18 18-MAY-06:05 4018.83 31-MAY-24:00 4010.92 31-MAY-24:00 132.35 05-MAY-17:00 851.31 31-MAY-24:00 0.00
June 0.105490E+11 0.231340E+10 720.00 0.104970E+11 52060233.64 0.00 0.64 30-JUN-24:00 0.42 07-JUN-06:10 5888.96 30-JUN-24:00 5887.11 30-JUN-24:00 194.08 12-JUN-15:00 1279.61 28-JUN-17:00 0.00
July 0.162641E+11 0.356953E+10 744.00 0.161491E+11 0.115001E+09 0.00 0.85 30-JUL-18:31 0.61 01-JUL-07:00 7864.50 31-JUL-23:55 7835.07 31-JUL-24:00 246.14 11-JUL-10:00 2056.83 30-JUL-18:01 0.00
August 0.212835E+11 0.475402E+10 744.00 0.211227E+11 0.160804E+09 0.00 1.00 06-AUG-18:01 0.29 31-AUG-24:00 9269.74 06-AUG-18:41 9269.74 06-AUG-18:41 277.51 30-AUG-08:00 2731.94 10-AUG-17:40 0.00
September 0.559983E+10 0.127464E+10 720.00 0.550915E+10 90686769.88 0.00 0.44 30-SEP-24:00 0.19 28-SEP-06:05 3897.99 30-SEP-24:00 3896.94 30-SEP-24:00 173.33 14-SEP-11:00 828.45 30-SEP-24:00 0.00
October 0.104255E+11 0.224767E+10 744.00 0.104028E+11 22721046.94 0.00 0.63 31-OCT-24:00 0.39 28-OCT-07:00 5616.72 31-OCT-24:00 5616.72 31-OCT-24:00 135.98 26-OCT-14:10 1168.67 31-OCT-24:00 0.00
November 0.147019E+11 0.306932E+10 720.00 0.146783E+11 23593369.15 0.00 0.71 11-NOV-15:55 0.59 24-NOV-07:05 6404.48 11-NOV-15:55 6404.48 11-NOV-15:55 165.38 03-NOV-16:00 1425.25 04-NOV-15:50 0.00
December 0.200314E+11 0.411159E+10 744.00 0.200290E+11 2451667.76 0.00 0.91 03-DEC-15:25 0.77 18-DEC-07:05 8191.42 10-DEC-15:35 8191.42 10-DEC-15:35 85.63 28-DEC-15:00 1688.56 03-DEC-15:35 0.00
                                       
Annual Sum or Average 0.152615E+12 0.329062E+11 8760.00 0.152079E+12 0.536109E+09 0.00                         0.00
Minimum of Months 0.407884E+10 0.979488E+09 672.00 0.407851E+10 326849.25 0.00 0.27   0.12   2127.82   2127.82   16.34   509.92   0.00
Maximum of Months 0.212835E+11 0.475402E+10 744.00 0.211227E+11 0.160804E+09 0.00 1.00   0.77   9269.74   9269.74   277.51   2731.94   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.153967E+11 0.400823E+10 688.95 0.153967E+11 -0.0 0.00 0.22 20-JAN-16:20 0.00 01-JAN-00:05 16735.79 05-JAN-16:20 16735.79 05-JAN-16:20 0.00 26-JAN-07:40 3927.88 20-JAN-16:20 0.00
February 0.671695E+11 0.152730E+11 672.00 0.670671E+11 0.102401E+09 0.00 0.48 08-FEB-16:50 0.24 21-FEB-07:10 40321.11 27-FEB-16:20 40122.04 27-FEB-16:20 1250.11 24-FEB-11:10 8917.34 27-FEB-16:20 0.00
March 0.134099E+12 0.287271E+11 744.00 0.134018E+12 81224517.44 0.00 0.77 31-MAR-23:50 0.50 06-MAR-07:10 67946.72 31-MAR-23:50 67946.72 31-MAR-23:50 1359.47 09-MAR-17:00 13742.43 31-MAR-23:50 0.00
April 0.183766E+12 0.378548E+11 720.00 0.183628E+12 0.138071E+09 0.00 0.97 01-APR-17:32 0.23 30-APR-24:00 82486.09 26-APR-18:00 82486.09 26-APR-18:00 1662.88 28-APR-13:00 22935.29 01-APR-17:02 0.00
May 0.484483E+11 0.112581E+11 744.00 0.480915E+11 0.356750E+09 0.00 0.45 31-MAY-23:50 0.13 18-MAY-06:05 37707.65 31-MAY-23:40 37608.81 31-MAY-24:00 1301.62 05-MAY-16:10 8004.39 31-MAY-23:50 0.00
June 0.969641E+11 0.213695E+11 720.00 0.964471E+11 0.516967E+09 0.00 0.63 30-JUN-24:00 0.38 14-JUN-06:25 55462.70 30-JUN-24:00 55442.60 30-JUN-24:00 1928.83 12-JUN-15:00 12223.54 28-JUN-17:00 0.00
July 0.152924E+12 0.336661E+11 744.00 0.151785E+12 0.113925E+10 0.00 0.84 31-JUL-23:20 0.59 18-JUL-06:10 75632.06 31-JUL-23:55 75344.48 31-JUL-24:00 2447.00 11-JUL-10:00 19516.49 30-JUL-18:01 0.00
August 0.201476E+12 0.451188E+11 744.00 0.199879E+12 0.159715E+10 0.00 1.00 10-AUG-17:50 0.25 31-AUG-24:00 86997.16 06-AUG-18:35 86997.16 06-AUG-18:40 2763.16 30-AUG-08:00 26210.98 10-AUG-17:50 0.00
September 0.487566E+11 0.111942E+11 720.00 0.478683E+11 0.888258E+09 0.00 0.42 30-SEP-23:50 0.14 28-SEP-06:55 35424.38 30-SEP-23:50 35408.62 30-SEP-23:50 1712.98 14-SEP-13:20 7568.48 30-SEP-23:50 0.00
October 0.893620E+11 0.194702E+11 744.00 0.891362E+11 0.225711E+09 0.00 0.56 31-OCT-24:00 0.32 28-OCT-07:00 47940.88 31-OCT-24:00 47940.88 31-OCT-24:00 1335.53 26-OCT-14:10 10813.00 04-OCT-16:50 0.00
November 0.123847E+12 0.262290E+11 720.00 0.123611E+12 0.235398E+09 0.00 0.67 04-NOV-16:00 0.48 24-NOV-07:05 58347.95 04-NOV-16:00 57159.55 04-NOV-16:02 1644.88 03-NOV-16:00 13254.36 04-NOV-15:50 0.00
December 0.168736E+12 0.352336E+11 744.00 0.168711E+12 24831517.33 0.00 0.83 05-DEC-15:50 0.63 26-DEC-07:03 73202.89 05-DEC-15:50 73202.89 05-DEC-15:50 846.54 28-DEC-15:00 14898.41 05-DEC-15:50 0.00
                                       
Annual Sum or Average 0.133094E+13 0.289403E+12 8704.95 0.132564E+13 0.530602E+10 0.00                         0.00
Minimum of Months 0.153967E+11 0.400823E+10 672.00 0.153967E+11 -0.0 0.00 0.22   0.00   16735.79   16735.79   0.00   3927.88   0.00
Maximum of Months 0.201476E+12 0.451188E+11 744.00 0.199879E+12 0.159715E+10 0.00 1.00   0.63   86997.16   86997.16   2763.16   26210.98   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.483413E+09 0.133817E+09 346.28 0.483413E+09 0.00 0.00 0.20 05-JAN-16:20 0.00 01-JAN-00:05 1542.07 05-JAN-16:20 1542.07 05-JAN-16:20 0.00 31-JAN-22:00 364.16 05-JAN-16:20 0.00
February 0.510112E+10 0.117974E+10 671.36 0.509103E+10 10096918.39 0.00 0.47 27-FEB-16:20 0.00 19-FEB-06:15 3992.71 27-FEB-16:30 3971.46 27-FEB-16:20 123.63 24-FEB-11:20 884.92 27-FEB-16:20 0.00
March 0.121187E+11 0.262621E+10 744.00 0.121106E+11 8053573.12 0.00 0.71 31-MAR-23:20 0.36 06-MAR-05:14 6309.42 31-MAR-23:20 6309.42 31-MAR-23:20 135.47 09-MAR-17:00 1340.47 18-MAR-17:02 0.00
April 0.176315E+11 0.365939E+10 720.00 0.176177E+11 13754113.27 0.00 0.95 01-APR-17:32 0.19 30-APR-24:00 8322.28 26-APR-18:00 8322.28 26-APR-18:00 166.37 28-APR-13:00 2297.09 27-APR-16:00 0.00
May 0.437263E+10 0.102599E+10 744.00 0.433714E+10 35497396.88 0.00 0.43 31-MAY-23:20 0.05 18-MAY-06:05 3696.53 31-MAY-23:20 3680.91 31-MAY-23:30 131.23 05-MAY-16:10 787.05 31-MAY-23:20 0.00
June 0.949641E+10 0.210155E+10 720.00 0.944469E+10 51721553.40 0.00 0.61 30-JUN-23:40 0.32 14-JUN-06:40 5464.44 30-JUN-23:40 5460.94 30-JUN-23:40 192.90 12-JUN-15:00 1246.59 28-JUN-17:00 0.00
July 0.151845E+11 0.335536E+10 744.00 0.150704E+11 0.114060E+09 0.00 0.85 30-JUL-18:31 0.56 18-JUL-06:10 7536.45 31-JUL-23:55 7507.50 31-JUL-24:00 244.78 11-JUL-10:00 2011.76 30-JUL-18:01 0.00
August 0.200214E+11 0.450214E+10 744.00 0.198617E+11 0.159709E+09 0.00 1.00 10-AUG-17:50 0.23 31-AUG-24:00 8906.93 06-AUG-18:30 8906.93 06-AUG-18:30 275.48 30-AUG-08:00 2660.91 10-AUG-17:50 0.00
September 0.439253E+10 0.101924E+10 720.00 0.430478E+10 87748187.89 0.00 0.38 10-SEP-17:22 0.07 27-SEP-06:40 3149.17 30-SEP-23:20 3145.92 30-SEP-23:20 174.32 14-SEP-13:20 757.86 10-SEP-17:22 0.00
October 0.777963E+10 0.171635E+10 744.00 0.775745E+10 22180321.42 0.00 0.55 04-OCT-16:50 0.21 16-OCT-06:05 4593.85 04-OCT-16:50 4593.85 04-OCT-16:50 131.51 26-OCT-14:10 1088.79 04-OCT-16:50 0.00
November 0.107139E+11 0.230381E+10 720.00 0.106906E+11 23308230.66 0.00 0.65 04-NOV-16:00 0.34 13-NOV-05:00 5749.04 04-NOV-16:00 5630.62 04-NOV-16:02 164.01 03-NOV-16:00 1310.12 04-NOV-15:50 0.00
December 0.149130E+11 0.316414E+10 744.00 0.149105E+11 2455978.31 0.00 0.80 05-DEC-16:00 0.46 26-DEC-04:07 7128.11 05-DEC-16:00 7128.11 05-DEC-16:00 84.09 28-DEC-15:10 1458.66 05-DEC-16:00 0.00
                                       
Annual Sum or Average 0.122209E+12 0.267877E+11 8361.64 0.121680E+12 0.528586E+09 0.00                         0.00
Minimum of Months 0.483413E+09 0.133817E+09 346.28 0.483413E+09 0.00 0.00 0.20   0.00   1542.07   1542.07   0.00   364.16   0.00
Maximum of Months 0.200214E+11 0.450214E+10 744.00 0.198617E+11 0.159709E+09 0.00 1.00   0.56   8906.93   8906.93   275.48   2660.91   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.32 0.00 85.32 0.79 627.07 0.00 0.00 0.00
February 132.76 0.00 132.76 15.61 553.92 0.00 0.00 0.00
March 195.60 0.00 195.60 64.75 450.41 0.00 0.00 0.00
April 276.80 0.98 275.81 162.21 352.43 0.00 0.00 0.00
May 356.17 10.58 345.59 278.66 270.22 0.00 0.00 0.00
June 374.50 24.73 349.77 327.67 207.62 0.00 0.00 0.00
July 355.94 27.91 328.04 354.02 185.40 0.00 0.00 0.00
August 288.14 7.79 280.35 290.43 181.88 0.00 0.00 0.00
September 223.82 0.07 223.75 163.95 276.87 0.00 0.00 0.00
October 153.35 0.00 153.35 56.06 394.83 0.00 0.00 0.00
November 96.60 0.00 96.60 7.08 522.10 0.00 0.00 0.00
December 72.50 0.00 72.50 0.16 646.61 0.00 0.00 0.00
                 
Annual Sum or Average 218.04 6.05 212.00 144.26 388.30 0.00 0.00 0.00
Minimum of Months 72.50 0.00 72.50 0.16 181.88 0.00 0.00 0.00
Maximum of Months 374.50 27.91 349.77 354.02 646.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.32 0.00 85.32 0.79 627.07 0.00 0.00 0.00
February 132.76 0.00 132.76 15.61 553.92 0.00 0.00 0.00
March 195.60 0.00 195.60 64.75 450.41 0.00 0.00 0.00
April 276.80 0.98 275.81 162.21 352.43 0.00 0.00 0.00
May 356.17 10.58 345.59 278.66 270.22 0.00 0.00 0.00
June 374.50 24.73 349.77 327.67 207.62 0.00 0.00 0.00
July 355.94 27.91 328.04 354.02 185.40 0.00 0.00 0.00
August 288.14 7.79 280.35 290.43 181.88 0.00 0.00 0.00
September 223.82 0.07 223.75 163.95 276.87 0.00 0.00 0.00
October 153.35 0.00 153.35 56.06 394.83 0.00 0.00 0.00
November 96.60 0.00 96.60 7.08 522.10 0.00 0.00 0.00
December 72.50 0.00 72.50 0.16 646.61 0.00 0.00 0.00
                 
Annual Sum or Average 218.04 6.05 212.00 144.26 388.30 0.00 0.00 0.00
Minimum of Months 72.50 0.00 72.50 0.16 181.88 0.00 0.00 0.00
Maximum of Months 374.50 27.91 349.77 354.02 646.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.32 0.00 85.32 0.79 627.07 0.00 0.00 0.00
February 132.76 0.00 132.76 15.61 553.92 0.00 0.00 0.00
March 195.60 0.00 195.60 64.75 450.41 0.00 0.00 0.00
April 276.80 0.98 275.81 162.21 352.43 0.00 0.00 0.00
May 356.17 10.58 345.59 278.66 270.22 0.00 0.00 0.00
June 374.50 24.73 349.77 327.67 207.62 0.00 0.00 0.00
July 355.94 27.91 328.04 354.02 185.40 0.00 0.00 0.00
August 288.14 7.79 280.35 290.43 181.88 0.00 0.00 0.00
September 223.82 0.07 223.75 163.95 276.87 0.00 0.00 0.00
October 153.35 0.00 153.35 56.06 394.83 0.00 0.00 0.00
November 96.60 0.00 96.60 7.08 522.10 0.00 0.00 0.00
December 72.50 0.00 72.50 0.16 646.61 0.00 0.00 0.00
                 
Annual Sum or Average 218.04 6.05 212.00 144.26 388.30 0.00 0.00 0.00
Minimum of Months 72.50 0.00 72.50 0.16 181.88 0.00 0.00 0.00
Maximum of Months 374.50 27.91 349.77 354.02 646.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.32 0.00 85.32 0.79 627.07 0.00 0.00 0.00
February 132.76 0.00 132.76 15.61 553.92 0.00 0.00 0.00
March 195.60 0.00 195.60 64.75 450.41 0.00 0.00 0.00
April 276.80 0.98 275.81 162.21 352.43 0.00 0.00 0.00
May 356.17 10.58 345.59 278.66 270.22 0.00 0.00 0.00
June 374.50 24.73 349.77 327.67 207.62 0.00 0.00 0.00
July 355.94 27.91 328.04 354.02 185.40 0.00 0.00 0.00
August 288.14 7.79 280.35 290.43 181.88 0.00 0.00 0.00
September 223.82 0.07 223.75 163.95 276.87 0.00 0.00 0.00
October 153.35 0.00 153.35 56.06 394.83 0.00 0.00 0.00
November 96.60 0.00 96.60 7.08 522.10 0.00 0.00 0.00
December 72.50 0.00 72.50 0.16 646.61 0.00 0.00 0.00
                 
Annual Sum or Average 218.04 6.05 212.00 144.26 388.30 0.00 0.00 0.00
Minimum of Months 72.50 0.00 72.50 0.16 181.88 0.00 0.00 0.00
Maximum of Months 374.50 27.91 349.77 354.02 646.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.32 0.00 85.32 0.79 627.04 0.00 0.00 0.00
February 132.76 0.00 132.76 15.61 553.90 0.00 0.00 0.00
March 195.59 0.00 195.59 64.75 450.39 0.00 0.00 0.00
April 276.79 0.98 275.80 162.20 352.42 0.00 0.00 0.00
May 356.15 10.58 345.57 278.65 270.20 0.00 0.00 0.00
June 374.49 24.73 349.76 327.66 207.61 0.00 0.00 0.00
July 355.93 27.91 328.02 354.01 185.40 0.00 0.00 0.00
August 288.13 7.79 280.34 290.41 181.87 0.00 0.00 0.00
September 223.81 0.07 223.74 163.95 276.85 0.00 0.00 0.00
October 153.34 0.00 153.34 56.06 394.81 0.00 0.00 0.00
November 96.59 0.00 96.59 7.08 522.08 0.00 0.00 0.00
December 72.50 0.00 72.50 0.16 646.58 0.00 0.00 0.00
                 
Annual Sum or Average 218.04 6.05 211.99 144.26 388.28 0.00 0.00 0.00
Minimum of Months 72.50 0.00 72.50 0.16 181.87 0.00 0.00 0.00
Maximum of Months 374.49 27.91 349.76 354.01 646.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.33 38.62 113.71 45.34 653.72 0.00 0.00 0.00
February 279.51 99.20 180.31 162.10 566.25 0.00 0.00 0.00
March 417.33 151.08 266.25 327.94 464.71 0.00 0.00 0.00
April 646.93 268.81 378.12 639.00 363.85 0.00 0.00 0.00
May 688.39 239.34 449.06 721.60 299.77 0.00 0.00 0.00
June 824.43 358.72 465.71 936.53 232.45 0.00 0.00 0.00
July 767.74 344.60 423.13 912.30 201.55 0.00 0.00 0.00
August 754.58 377.48 377.09 928.86 195.01 0.00 0.00 0.00
September 557.90 257.31 300.59 604.82 293.32 0.00 0.00 0.00
October 363.64 154.51 209.13 315.72 412.22 0.00 0.00 0.00
November 178.24 50.32 127.92 81.96 539.73 0.00 0.00 0.00
December 146.19 47.06 99.13 59.04 662.62 0.00 0.00 0.00
                 
Annual Sum or Average 482.32 199.36 282.96 479.57 406.34 0.00 0.00 0.00
Minimum of Months 146.19 38.62 99.13 45.34 195.01 0.00 0.00 0.00
Maximum of Months 824.43 377.48 465.71 936.53 662.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.33 38.62 113.71 45.34 653.72 0.00 0.00 0.00
February 279.51 99.20 180.31 162.10 566.25 0.00 0.00 0.00
March 417.33 151.08 266.25 327.94 464.71 0.00 0.00 0.00
April 646.93 268.81 378.12 639.00 363.85 0.00 0.00 0.00
May 688.39 239.34 449.06 721.60 299.77 0.00 0.00 0.00
June 824.43 358.72 465.71 936.53 232.45 0.00 0.00 0.00
July 767.74 344.60 423.13 912.30 201.55 0.00 0.00 0.00
August 754.58 377.48 377.09 928.86 195.01 0.00 0.00 0.00
September 557.90 257.31 300.59 604.82 293.32 0.00 0.00 0.00
October 363.64 154.51 209.13 315.72 412.22 0.00 0.00 0.00
November 178.24 50.32 127.92 81.96 539.73 0.00 0.00 0.00
December 146.19 47.06 99.13 59.04 662.62 0.00 0.00 0.00
                 
Annual Sum or Average 482.32 199.36 282.96 479.57 406.34 0.00 0.00 0.00
Minimum of Months 146.19 38.62 99.13 45.34 195.01 0.00 0.00 0.00
Maximum of Months 824.43 377.48 465.71 936.53 662.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.33 38.62 113.71 45.34 653.71 0.00 0.00 0.00
February 279.51 99.20 180.30 162.10 566.24 0.00 0.00 0.00
March 417.32 151.07 266.25 327.94 464.70 0.00 0.00 0.00
April 646.92 268.81 378.12 638.99 363.84 0.00 0.00 0.00
May 688.38 239.33 449.05 721.59 299.77 0.00 0.00 0.00
June 824.41 358.71 465.71 936.51 232.45 0.00 0.00 0.00
July 767.72 344.60 423.12 912.28 201.54 0.00 0.00 0.00
August 754.56 377.48 377.09 928.84 195.01 0.00 0.00 0.00
September 557.89 257.30 300.59 604.81 293.31 0.00 0.00 0.00
October 363.63 154.51 209.12 315.71 412.21 0.00 0.00 0.00
November 178.23 50.32 127.92 81.95 539.72 0.00 0.00 0.00
December 146.19 47.06 99.13 59.04 662.61 0.00 0.00 0.00
                 
Annual Sum or Average 482.31 199.36 282.96 479.56 406.33 0.00 0.00 0.00
Minimum of Months 146.19 38.62 99.13 45.34 195.01 0.00 0.00 0.00
Maximum of Months 824.41 377.48 465.71 936.51 662.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.97 223.85 153.12 321.01 533.75 0.00 0.00 0.00
February 579.72 358.86 220.87 570.07 483.32 0.00 0.00 0.00
March 623.62 332.57 291.05 648.63 425.09 0.00 0.00 0.00
April 658.42 285.88 372.54 728.04 356.05 0.00 0.00 0.00
May 602.04 179.35 422.69 676.59 288.14 0.00 0.00 0.00
June 550.81 147.89 402.92 632.70 228.52 0.00 0.00 0.00
July 600.68 220.00 380.68 763.66 205.64 0.00 0.00 0.00
August 645.36 300.94 344.42 848.88 198.91 0.00 0.00 0.00
September 715.03 394.86 320.17 881.32 278.20 0.00 0.00 0.00
October 647.69 399.90 247.79 724.12 373.01 0.00 0.00 0.00
November 382.94 219.46 163.48 350.45 459.46 0.00 0.00 0.00
December 400.66 259.29 141.38 378.40 558.47 0.00 0.00 0.00
                 
Annual Sum or Average 565.08 276.39 288.69 627.23 365.13 0.00 0.00 0.00
Minimum of Months 376.97 147.89 141.38 321.01 198.91 0.00 0.00 0.00
Maximum of Months 715.03 399.90 422.69 881.32 558.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.97 223.85 153.12 321.00 533.75 0.00 0.00 0.00
February 579.72 358.86 220.87 570.07 483.32 0.00 0.00 0.00
March 623.62 332.57 291.05 648.63 425.09 0.00 0.00 0.00
April 658.42 285.88 372.54 728.04 356.05 0.00 0.00 0.00
May 602.04 179.35 422.69 676.59 288.14 0.00 0.00 0.00
June 550.81 147.89 402.92 632.70 228.52 0.00 0.00 0.00
July 600.68 220.00 380.68 763.65 205.64 0.00 0.00 0.00
August 645.36 300.94 344.42 848.88 198.91 0.00 0.00 0.00
September 715.03 394.86 320.17 881.31 278.20 0.00 0.00 0.00
October 647.69 399.90 247.79 724.12 373.01 0.00 0.00 0.00
November 382.94 219.46 163.48 350.45 459.46 0.00 0.00 0.00
December 400.66 259.28 141.38 378.40 558.47 0.00 0.00 0.00
                 
Annual Sum or Average 565.08 276.39 288.69 627.23 365.13 0.00 0.00 0.00
Minimum of Months 376.97 147.89 141.38 321.00 198.91 0.00 0.00 0.00
Maximum of Months 715.03 399.90 422.69 881.31 558.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.97 223.85 153.12 321.01 533.75 0.00 0.00 0.00
February 579.72 358.86 220.87 570.07 483.32 0.00 0.00 0.00
March 623.62 332.57 291.05 648.63 425.09 0.00 0.00 0.00
April 658.42 285.88 372.54 728.04 356.05 0.00 0.00 0.00
May 602.04 179.35 422.69 676.59 288.14 0.00 0.00 0.00
June 550.81 147.89 402.92 632.70 228.52 0.00 0.00 0.00
July 600.68 220.00 380.68 763.66 205.64 0.00 0.00 0.00
August 645.36 300.94 344.42 848.88 198.91 0.00 0.00 0.00
September 715.03 394.86 320.17 881.32 278.20 0.00 0.00 0.00
October 647.69 399.90 247.79 724.12 373.01 0.00 0.00 0.00
November 382.94 219.46 163.48 350.45 459.46 0.00 0.00 0.00
December 400.66 259.29 141.38 378.40 558.47 0.00 0.00 0.00
                 
Annual Sum or Average 565.08 276.39 288.69 627.23 365.13 0.00 0.00 0.00
Minimum of Months 376.97 147.89 141.38 321.01 198.91 0.00 0.00 0.00
Maximum of Months 715.03 399.90 422.69 881.32 558.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.97 223.85 153.12 321.00 533.75 0.00 0.00 0.00
February 579.72 358.86 220.87 570.07 483.32 0.00 0.00 0.00
March 623.62 332.57 291.05 648.63 425.09 0.00 0.00 0.00
April 658.42 285.88 372.54 728.04 356.05 0.00 0.00 0.00
May 602.04 179.35 422.69 676.59 288.14 0.00 0.00 0.00
June 550.81 147.89 402.92 632.70 228.52 0.00 0.00 0.00
July 600.68 220.00 380.68 763.65 205.64 0.00 0.00 0.00
August 645.36 300.94 344.42 848.88 198.91 0.00 0.00 0.00
September 715.03 394.86 320.17 881.31 278.20 0.00 0.00 0.00
October 647.69 399.90 247.79 724.12 373.01 0.00 0.00 0.00
November 382.94 219.46 163.48 350.45 459.46 0.00 0.00 0.00
December 400.66 259.28 141.38 378.40 558.47 0.00 0.00 0.00
                 
Annual Sum or Average 565.08 276.39 288.69 627.23 365.13 0.00 0.00 0.00
Minimum of Months 376.97 147.89 141.38 321.00 198.91 0.00 0.00 0.00
Maximum of Months 715.03 399.90 422.69 881.31 558.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.96 223.84 153.12 320.99 533.73 0.00 0.00 0.00
February 579.70 358.84 220.86 570.05 483.30 0.00 0.00 0.00
March 623.59 332.55 291.04 648.61 425.07 0.00 0.00 0.00
April 658.39 285.87 372.52 728.01 356.03 0.00 0.00 0.00
May 602.02 179.35 422.67 676.56 288.12 0.00 0.00 0.00
June 550.79 147.88 402.91 632.68 228.51 0.00 0.00 0.00
July 600.66 219.99 380.66 763.62 205.63 0.00 0.00 0.00
August 645.33 300.93 344.40 848.85 198.90 0.00 0.00 0.00
September 715.00 394.85 320.15 881.28 278.19 0.00 0.00 0.00
October 647.67 399.89 247.78 724.09 372.99 0.00 0.00 0.00
November 382.92 219.45 163.48 350.44 459.44 0.00 0.00 0.00
December 400.65 259.27 141.37 378.39 558.44 0.00 0.00 0.00
                 
Annual Sum or Average 565.06 276.38 288.68 627.20 365.12 0.00 0.00 0.00
Minimum of Months 376.96 147.88 141.37 320.99 198.90 0.00 0.00 0.00
Maximum of Months 715.00 399.89 422.67 881.28 558.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 160.67 47.38 113.29 57.28 705.64 0.00 0.00 0.00
February 288.07 108.27 179.81 176.90 636.72 0.00 0.00 0.00
March 403.66 136.25 267.41 307.00 538.18 0.00 0.00 0.00
April 614.13 234.80 379.32 581.48 441.71 0.00 0.00 0.00
May 790.24 321.03 469.21 852.33 337.83 0.00 0.00 0.00
June 759.99 295.08 464.91 835.87 274.52 0.00 0.00 0.00
July 938.87 493.52 445.35 1138.03 257.09 0.00 0.00 0.00
August 776.67 396.59 380.08 949.66 256.91 0.00 0.00 0.00
September 632.48 303.48 329.00 714.06 334.61 0.00 0.00 0.00
October 360.07 146.71 213.36 308.51 472.77 0.00 0.00 0.00
November 179.31 50.57 128.74 80.58 618.82 0.00 0.00 0.00
December 150.75 51.66 99.09 68.49 774.72 0.00 0.00 0.00
                 
Annual Sum or Average 505.90 216.26 289.63 508.04 470.01 0.00 0.00 0.00
Minimum of Months 150.75 47.38 99.09 57.28 256.91 0.00 0.00 0.00
Maximum of Months 938.87 493.52 469.21 1138.03 774.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 160.67 47.38 113.29 57.28 705.64 0.00 0.00 0.00
February 288.07 108.27 179.81 176.90 636.72 0.00 0.00 0.00
March 403.66 136.25 267.41 307.00 538.18 0.00 0.00 0.00
April 614.13 234.80 379.32 581.48 441.71 0.00 0.00 0.00
May 790.24 321.03 469.21 852.33 337.83 0.00 0.00 0.00
June 759.99 295.08 464.91 835.87 274.52 0.00 0.00 0.00
July 938.87 493.52 445.35 1138.03 257.09 0.00 0.00 0.00
August 776.67 396.59 380.08 949.66 256.91 0.00 0.00 0.00
September 632.48 303.48 329.00 714.06 334.61 0.00 0.00 0.00
October 360.07 146.71 213.36 308.51 472.77 0.00 0.00 0.00
November 179.31 50.57 128.74 80.58 618.82 0.00 0.00 0.00
December 150.75 51.66 99.09 68.49 774.72 0.00 0.00 0.00
                 
Annual Sum or Average 505.90 216.26 289.63 508.04 470.01 0.00 0.00 0.00
Minimum of Months 150.75 47.38 99.09 57.28 256.91 0.00 0.00 0.00
Maximum of Months 938.87 493.52 469.21 1138.03 774.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 160.67 47.38 113.29 57.28 705.63 0.00 0.00 0.00
February 288.07 108.26 179.80 176.90 636.71 0.00 0.00 0.00
March 403.65 136.24 267.41 307.00 538.17 0.00 0.00 0.00
April 614.12 234.80 379.32 581.47 441.71 0.00 0.00 0.00
May 790.22 321.03 469.20 852.31 337.82 0.00 0.00 0.00
June 759.98 295.07 464.90 835.86 274.51 0.00 0.00 0.00
July 938.85 493.51 445.34 1138.01 257.09 0.00 0.00 0.00
August 776.65 396.58 380.07 949.64 256.90 0.00 0.00 0.00
September 632.47 303.47 329.00 714.05 334.61 0.00 0.00 0.00
October 360.07 146.71 213.36 308.51 472.76 0.00 0.00 0.00
November 179.31 50.57 128.74 80.57 618.81 0.00 0.00 0.00
December 150.74 51.66 99.09 68.49 774.71 0.00 0.00 0.00
                 
Annual Sum or Average 505.89 216.26 289.63 508.03 470.01 0.00 0.00 0.00
Minimum of Months 150.74 47.38 99.09 57.28 256.90 0.00 0.00 0.00
Maximum of Months 938.85 493.51 469.20 1138.01 774.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 426.60 0.00 426.60 12.05 2693.89 0.00 0.00 0.00
February 663.80 0.00 663.80 117.37 2410.36 0.00 0.00 0.00
March 978.00 0.00 978.00 382.88 2002.10 0.00 0.00 0.00
April 1383.97 4.91 1379.06 870.35 1594.50 0.00 0.00 0.00
May 1780.82 52.91 1727.91 1420.72 1282.98 0.00 0.00 0.00
June 1872.49 123.65 1748.83 1661.51 984.92 0.00 0.00 0.00
July 1779.69 139.54 1640.16 1798.04 881.00 0.00 0.00 0.00
August 1440.68 38.95 1401.73 1482.35 862.69 0.00 0.00 0.00
September 1119.07 0.33 1118.74 845.76 1295.52 0.00 0.00 0.00
October 766.75 0.00 766.75 328.67 1757.67 0.00 0.00 0.00
November 482.97 0.00 482.97 57.89 2223.28 0.00 0.00 0.00
December 362.50 0.00 362.50 5.26 2725.76 0.00 0.00 0.00
                 
Annual Sum or Average 1090.21 30.25 1059.96 752.55 1722.81 0.00 0.00 0.00
Minimum of Months 362.50 0.00 362.50 5.26 862.69 0.00 0.00 0.00
Maximum of Months 1872.49 139.54 1748.83 1798.04 2725.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 456.99 115.86 341.13 154.01 1713.23 0.00 0.00 0.00
February 838.53 297.61 540.92 517.09 1539.22 0.00 0.00 0.00
March 1251.98 453.23 798.75 995.39 1298.46 0.00 0.00 0.00
April 1940.78 806.42 1134.36 1913.38 1041.43 0.00 0.00 0.00
May 2065.16 718.01 1347.15 2152.83 872.57 0.00 0.00 0.00
June 2473.26 1076.14 1397.13 2785.65 683.27 0.00 0.00 0.00
July 2303.18 1033.80 1269.38 2715.87 597.97 0.00 0.00 0.00
August 2263.71 1132.44 1131.27 2763.07 586.08 0.00 0.00 0.00
September 1673.68 771.92 901.76 1806.52 848.05 0.00 0.00 0.00
October 1090.90 463.53 627.37 958.13 1148.44 0.00 0.00 0.00
November 534.70 150.95 383.75 263.81 1443.24 0.00 0.00 0.00
December 438.57 141.19 297.38 194.31 1754.01 0.00 0.00 0.00
                 
Annual Sum or Average 1446.95 598.07 848.88 1439.73 1125.13 0.00 0.00 0.00
Minimum of Months 438.57 115.86 297.38 154.01 586.08 0.00 0.00 0.00
Maximum of Months 2473.26 1132.44 1397.13 2785.65 1754.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1884.84 1119.22 765.61 1622.95 2495.80 0.00 0.00 0.00
February 2898.59 1794.27 1104.32 2859.15 2306.82 0.00 0.00 0.00
March 3118.04 1662.82 1455.23 3236.60 2033.37 0.00 0.00 0.00
April 3292.06 1429.40 1862.67 3627.78 1710.34 0.00 0.00 0.00
May 3010.17 896.76 2113.41 3359.07 1412.63 0.00 0.00 0.00
June 2754.01 739.42 2014.59 3146.69 1110.09 0.00 0.00 0.00
July 3003.37 1099.99 1903.38 3801.70 1001.53 0.00 0.00 0.00
August 3226.74 1504.68 1722.06 4227.83 973.78 0.00 0.00 0.00
September 3575.10 1974.29 1600.81 4385.67 1366.82 0.00 0.00 0.00
October 3238.43 1999.49 1238.94 3604.36 1798.25 0.00 0.00 0.00
November 1914.67 1097.27 817.40 1768.16 2153.54 0.00 0.00 0.00
December 2003.29 1296.41 706.88 1912.25 2587.64 0.00 0.00 0.00
                 
Annual Sum or Average 2825.39 1381.95 1443.44 3130.45 1743.03 0.00 0.00 0.00
Minimum of Months 1884.84 739.42 706.88 1622.95 973.78 0.00 0.00 0.00
Maximum of Months 3575.10 1999.49 2113.41 4385.67 2587.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 482.01 142.14 339.87 192.61 1778.75 0.00 0.00 0.00
February 864.20 324.79 539.41 574.64 1601.94 0.00 0.00 0.00
March 1210.97 408.74 802.24 969.10 1367.50 0.00 0.00 0.00
April 1842.36 704.41 1137.96 1800.70 1137.31 0.00 0.00 0.00
May 2370.69 963.08 1407.61 2564.72 948.08 0.00 0.00 0.00
June 2279.96 885.23 1394.72 2528.47 746.71 0.00 0.00 0.00
July 2816.58 1480.54 1336.04 3437.52 693.09 0.00 0.00 0.00
August 2329.98 1189.76 1140.23 2885.62 674.98 0.00 0.00 0.00
September 1897.41 910.42 986.99 2154.47 929.01 0.00 0.00 0.00
October 1080.20 440.13 640.07 961.89 1222.67 0.00 0.00 0.00
November 537.94 151.72 386.21 275.14 1494.88 0.00 0.00 0.00
December 452.24 154.97 297.27 231.23 1827.98 0.00 0.00 0.00
                 
Annual Sum or Average 1517.67 648.79 868.89 1554.46 1199.99 0.00 0.00 0.00
Minimum of Months 452.24 142.14 297.27 192.61 674.98 0.00 0.00 0.00
Maximum of Months 2816.58 1480.54 1407.61 3437.52 1827.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 426.60 0.00 426.60 20.60 2479.79 0.00 0.00 0.00
February 663.80 0.00 663.80 146.26 2197.45 0.00 0.00 0.00
March 978.00 0.00 978.00 431.30 1825.23 0.00 0.00 0.00
April 1383.97 4.91 1379.06 912.18 1489.26 0.00 0.00 0.00
May 1780.82 52.91 1727.91 1446.25 1222.88 0.00 0.00 0.00
June 1872.49 123.65 1748.83 1665.05 958.11 0.00 0.00 0.00
July 1779.69 139.54 1640.16 1792.54 863.62 0.00 0.00 0.00
August 1440.68 38.95 1401.73 1481.57 841.30 0.00 0.00 0.00
September 1119.07 0.33 1118.74 869.16 1219.31 0.00 0.00 0.00
October 766.75 0.00 766.75 375.94 1585.66 0.00 0.00 0.00
November 482.97 0.00 482.97 80.27 1978.82 0.00 0.00 0.00
December 362.50 0.00 362.50 12.85 2471.28 0.00 0.00 0.00
                 
Annual Sum or Average 1090.21 30.25 1059.96 773.39 1591.44 0.00 0.00 0.00
Minimum of Months 362.50 0.00 362.50 12.85 841.30 0.00 0.00 0.00
Maximum of Months 1872.49 139.54 1748.83 1792.54 2479.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 456.99 115.86 341.13 169.99 1574.69 0.00 0.00 0.00
February 838.53 297.61 540.92 554.35 1399.50 0.00 0.00 0.00
March 1251.98 453.23 798.75 1035.27 1187.78 0.00 0.00 0.00
April 1940.78 806.42 1134.36 1942.22 980.34 0.00 0.00 0.00
May 2065.16 718.01 1347.15 2169.52 835.74 0.00 0.00 0.00
June 2473.26 1076.14 1397.13 2787.50 667.04 0.00 0.00 0.00
July 2303.18 1033.80 1269.38 2715.38 588.31 0.00 0.00 0.00
August 2263.71 1132.44 1131.27 2764.33 573.79 0.00 0.00 0.00
September 1673.68 771.92 901.76 1824.36 803.13 0.00 0.00 0.00
October 1090.90 463.53 627.37 995.13 1042.85 0.00 0.00 0.00
November 534.70 150.95 383.75 291.88 1282.22 0.00 0.00 0.00
December 438.57 141.19 297.38 213.62 1587.51 0.00 0.00 0.00
                 
Annual Sum or Average 1446.95 598.07 848.88 1459.89 1041.86 0.00 0.00 0.00
Minimum of Months 438.57 115.86 297.38 169.99 573.79 0.00 0.00 0.00
Maximum of Months 2473.26 1132.44 1397.13 2787.50 1587.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1884.84 1119.22 765.61 1667.41 2289.38 0.00 0.00 0.00
February 2898.59 1794.27 1104.32 2920.29 2111.20 0.00 0.00 0.00
March 3118.04 1662.82 1455.23 3275.96 1873.09 0.00 0.00 0.00
April 3292.06 1429.40 1862.67 3653.74 1614.80 0.00 0.00 0.00
May 3010.17 896.76 2113.41 3370.15 1351.59 0.00 0.00 0.00
June 2754.01 739.42 2014.59 3141.21 1080.59 0.00 0.00 0.00
July 3003.37 1099.99 1903.38 3789.73 983.74 0.00 0.00 0.00
August 3226.74 1504.68 1722.06 4218.25 952.62 0.00 0.00 0.00
September 3575.10 1974.29 1600.81 4398.01 1301.75 0.00 0.00 0.00
October 3238.43 1999.49 1238.94 3642.78 1652.35 0.00 0.00 0.00
November 1914.67 1097.27 817.40 1819.14 1935.36 0.00 0.00 0.00
December 2003.29 1296.41 706.88 1956.03 2352.20 0.00 0.00 0.00
                 
Annual Sum or Average 2825.39 1381.95 1443.44 3155.24 1622.45 0.00 0.00 0.00
Minimum of Months 1884.84 739.42 706.88 1667.41 952.62 0.00 0.00 0.00
Maximum of Months 3575.10 1999.49 2113.41 4398.01 2352.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 482.01 142.14 339.87 204.13 1642.76 0.00 0.00 0.00
February 864.20 324.79 539.41 597.20 1480.32 0.00 0.00 0.00
March 1210.97 408.74 802.24 993.75 1267.95 0.00 0.00 0.00
April 1842.36 704.41 1137.96 1817.93 1078.00 0.00 0.00 0.00
May 2370.69 963.08 1407.61 2568.39 911.75 0.00 0.00 0.00
June 2279.96 885.23 1394.72 2521.59 728.27 0.00 0.00 0.00
July 2816.58 1480.54 1336.04 3425.53 680.98 0.00 0.00 0.00
August 2329.98 1189.76 1140.23 2877.16 661.48 0.00 0.00 0.00
September 1897.41 910.42 986.99 2160.16 888.40 0.00 0.00 0.00
October 1080.20 440.13 640.07 985.34 1127.71 0.00 0.00 0.00
November 537.94 151.72 386.21 293.55 1358.80 0.00 0.00 0.00
December 452.24 154.97 297.27 242.29 1682.77 0.00 0.00 0.00
                 
Annual Sum or Average 1517.67 648.79 868.89 1563.60 1124.08 0.00 0.00 0.00
Minimum of Months 452.24 142.14 297.27 204.13 661.48 0.00 0.00 0.00
Maximum of Months 2816.58 1480.54 1407.61 3425.53 1682.77 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228522E+09 0.00 0.228522E+09 2114124.55 0.167954E+10
February 0.321175E+09 0.00 0.321175E+09 37761299.84 0.134004E+10
March 0.523901E+09 0.00 0.523901E+09 0.173438E+09 0.120636E+10
April 0.717457E+09 2545038.93 0.714912E+09 0.420443E+09 0.913507E+09
May 0.953960E+09 28340757.90 0.925619E+09 0.746372E+09 0.723744E+09
June 0.970708E+09 64101511.40 0.906607E+09 0.849326E+09 0.538157E+09
July 0.953358E+09 74747816.12 0.878611E+09 0.948218E+09 0.496585E+09
August 0.771750E+09 20862733.60 0.750888E+09 0.777879E+09 0.487150E+09
September 0.580131E+09 171071.71 0.579959E+09 0.424965E+09 0.717637E+09
October 0.410735E+09 0.00 0.410735E+09 0.150147E+09 0.105751E+10
November 0.250377E+09 0.00 0.250377E+09 18363197.03 0.135329E+10
December 0.194185E+09 0.00 0.194185E+09 437064.00 0.173188E+10
           
Annual Sum or Average 0.687626E+10 0.190769E+09 0.668549E+10 0.454946E+10 0.122454E+11
Minimum of Months 0.194185E+09 0.00 0.194185E+09 437064.00 0.487150E+09
Maximum of Months 0.970708E+09 74747816.12 0.925619E+09 0.948218E+09 0.173188E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228522E+09 0.00 0.228522E+09 2114105.85 0.167954E+10
February 0.321174E+09 0.00 0.321174E+09 37761176.55 0.134004E+10
March 0.523900E+09 0.00 0.523900E+09 0.173438E+09 0.120636E+10
April 0.717457E+09 2545035.87 0.714911E+09 0.420442E+09 0.913507E+09
May 0.953959E+09 28340723.90 0.925618E+09 0.746371E+09 0.723744E+09
June 0.970707E+09 64101434.48 0.906606E+09 0.849325E+09 0.538157E+09
July 0.953358E+09 74747726.43 0.878610E+09 0.948217E+09 0.496585E+09
August 0.771750E+09 20862708.56 0.750887E+09 0.777878E+09 0.487150E+09
September 0.580130E+09 171071.50 0.579959E+09 0.424965E+09 0.717637E+09
October 0.410735E+09 0.00 0.410735E+09 0.150147E+09 0.105751E+10
November 0.250377E+09 0.00 0.250377E+09 18363130.89 0.135329E+10
December 0.194185E+09 0.00 0.194185E+09 437059.26 0.173188E+10
           
Annual Sum or Average 0.687625E+10 0.190769E+09 0.668549E+10 0.454946E+10 0.122454E+11
Minimum of Months 0.194185E+09 0.00 0.194185E+09 437059.26 0.487150E+09
Maximum of Months 0.970707E+09 74747726.43 0.925618E+09 0.948217E+09 0.173188E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228522E+09 0.00 0.228522E+09 2114124.55 0.167954E+10
February 0.321175E+09 0.00 0.321175E+09 37761299.84 0.134004E+10
March 0.523901E+09 0.00 0.523901E+09 0.173438E+09 0.120636E+10
April 0.717457E+09 2545038.93 0.714912E+09 0.420443E+09 0.913507E+09
May 0.953960E+09 28340757.90 0.925619E+09 0.746372E+09 0.723744E+09
June 0.970708E+09 64101511.40 0.906607E+09 0.849326E+09 0.538157E+09
July 0.953358E+09 74747816.12 0.878611E+09 0.948218E+09 0.496585E+09
August 0.771750E+09 20862733.60 0.750888E+09 0.777879E+09 0.487150E+09
September 0.580131E+09 171071.71 0.579959E+09 0.424965E+09 0.717637E+09
October 0.410735E+09 0.00 0.410735E+09 0.150147E+09 0.105751E+10
November 0.250377E+09 0.00 0.250377E+09 18363197.03 0.135329E+10
December 0.194185E+09 0.00 0.194185E+09 437064.00 0.173188E+10
           
Annual Sum or Average 0.687626E+10 0.190769E+09 0.668549E+10 0.454946E+10 0.122454E+11
Minimum of Months 0.194185E+09 0.00 0.194185E+09 437064.00 0.487150E+09
Maximum of Months 0.970708E+09 74747816.12 0.925619E+09 0.948218E+09 0.173188E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228522E+09 0.00 0.228522E+09 2114105.85 0.167954E+10
February 0.321174E+09 0.00 0.321174E+09 37761176.55 0.134004E+10
March 0.523900E+09 0.00 0.523900E+09 0.173438E+09 0.120636E+10
April 0.717457E+09 2545035.87 0.714911E+09 0.420442E+09 0.913507E+09
May 0.953959E+09 28340723.90 0.925618E+09 0.746371E+09 0.723744E+09
June 0.970707E+09 64101434.48 0.906606E+09 0.849325E+09 0.538157E+09
July 0.953358E+09 74747726.43 0.878610E+09 0.948217E+09 0.496585E+09
August 0.771750E+09 20862708.56 0.750887E+09 0.777878E+09 0.487150E+09
September 0.580130E+09 171071.50 0.579959E+09 0.424965E+09 0.717637E+09
October 0.410735E+09 0.00 0.410735E+09 0.150147E+09 0.105751E+10
November 0.250377E+09 0.00 0.250377E+09 18363130.89 0.135329E+10
December 0.194185E+09 0.00 0.194185E+09 437059.26 0.173188E+10
           
Annual Sum or Average 0.687625E+10 0.190769E+09 0.668549E+10 0.454946E+10 0.122454E+11
Minimum of Months 0.194185E+09 0.00 0.194185E+09 437059.26 0.487150E+09
Maximum of Months 0.970707E+09 74747726.43 0.925618E+09 0.948217E+09 0.173188E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228513E+09 0.00 0.228513E+09 2114039.34 0.167947E+10
February 0.321162E+09 0.00 0.321162E+09 37759777.90 0.133998E+10
March 0.523879E+09 0.00 0.523879E+09 0.173431E+09 0.120632E+10
April 0.717428E+09 2544936.35 0.714883E+09 0.420426E+09 0.913470E+09
May 0.953921E+09 28339615.65 0.925582E+09 0.746342E+09 0.723715E+09
June 0.970669E+09 64098927.82 0.906570E+09 0.849292E+09 0.538135E+09
July 0.953320E+09 74744803.46 0.878575E+09 0.948180E+09 0.496565E+09
August 0.771719E+09 20861892.74 0.750857E+09 0.777847E+09 0.487130E+09
September 0.580107E+09 171064.81 0.579936E+09 0.424948E+09 0.717608E+09
October 0.410719E+09 0.00 0.410719E+09 0.150141E+09 0.105746E+10
November 0.250367E+09 0.00 0.250367E+09 18362456.92 0.135324E+10
December 0.194177E+09 0.00 0.194177E+09 437046.39 0.173181E+10
           
Annual Sum or Average 0.687598E+10 0.190761E+09 0.668522E+10 0.454928E+10 0.122449E+11
Minimum of Months 0.194177E+09 0.00 0.194177E+09 437046.39 0.487130E+09
Maximum of Months 0.970669E+09 74744803.46 0.925582E+09 0.948180E+09 0.173181E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.408002E+09 0.103442E+09 0.304560E+09 0.121428E+09 0.175093E+10
February 0.676194E+09 0.239995E+09 0.436198E+09 0.392158E+09 0.136987E+10
March 0.111778E+10 0.404645E+09 0.713132E+09 0.878359E+09 0.124467E+10
April 0.167685E+10 0.696756E+09 0.980094E+09 0.165629E+10 0.943088E+09
May 0.184380E+10 0.641045E+09 0.120275E+10 0.193274E+10 0.802905E+09
June 0.213692E+10 0.929790E+09 0.120713E+10 0.242748E+10 0.602518E+09
July 0.205630E+10 0.922987E+09 0.113332E+10 0.244350E+10 0.539824E+09
August 0.202106E+10 0.101105E+10 0.101001E+10 0.248785E+10 0.522324E+09
September 0.144607E+10 0.666942E+09 0.779132E+09 0.156769E+10 0.760276E+09
October 0.973968E+09 0.413845E+09 0.560123E+09 0.845618E+09 0.110408E+10
November 0.461985E+09 0.130423E+09 0.331562E+09 0.212429E+09 0.139897E+10
December 0.391563E+09 0.126056E+09 0.265507E+09 0.158127E+09 0.177476E+10
           
Annual Sum or Average 0.152105E+11 0.628698E+10 0.892352E+10 0.151237E+11 0.128142E+11
Minimum of Months 0.391563E+09 0.103442E+09 0.265507E+09 0.121428E+09 0.522324E+09
Maximum of Months 0.213692E+10 0.101105E+10 0.120713E+10 0.248785E+10 0.177476E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.408002E+09 0.103442E+09 0.304560E+09 0.121428E+09 0.175093E+10
February 0.676194E+09 0.239995E+09 0.436198E+09 0.392158E+09 0.136987E+10
March 0.111778E+10 0.404645E+09 0.713132E+09 0.878359E+09 0.124467E+10
April 0.167685E+10 0.696756E+09 0.980094E+09 0.165629E+10 0.943088E+09
May 0.184380E+10 0.641045E+09 0.120275E+10 0.193274E+10 0.802905E+09
June 0.213692E+10 0.929790E+09 0.120713E+10 0.242748E+10 0.602518E+09
July 0.205630E+10 0.922987E+09 0.113332E+10 0.244350E+10 0.539824E+09
August 0.202106E+10 0.101105E+10 0.101001E+10 0.248785E+10 0.522324E+09
September 0.144607E+10 0.666942E+09 0.779132E+09 0.156769E+10 0.760276E+09
October 0.973968E+09 0.413845E+09 0.560123E+09 0.845618E+09 0.110408E+10
November 0.461985E+09 0.130423E+09 0.331562E+09 0.212429E+09 0.139897E+10
December 0.391563E+09 0.126056E+09 0.265507E+09 0.158127E+09 0.177476E+10
           
Annual Sum or Average 0.152105E+11 0.628698E+10 0.892352E+10 0.151237E+11 0.128142E+11
Minimum of Months 0.391563E+09 0.103442E+09 0.265507E+09 0.121428E+09 0.522324E+09
Maximum of Months 0.213692E+10 0.101105E+10 0.120713E+10 0.248785E+10 0.177476E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.407994E+09 0.103440E+09 0.304554E+09 0.121426E+09 0.175090E+10
February 0.676181E+09 0.239991E+09 0.436190E+09 0.392151E+09 0.136985E+10
March 0.111776E+10 0.404637E+09 0.713119E+09 0.878343E+09 0.124465E+10
April 0.167682E+10 0.696743E+09 0.980077E+09 0.165626E+10 0.943070E+09
May 0.184376E+10 0.641034E+09 0.120273E+10 0.193271E+10 0.802891E+09
June 0.213688E+10 0.929773E+09 0.120711E+10 0.242744E+10 0.602507E+09
July 0.205627E+10 0.922970E+09 0.113330E+10 0.244346E+10 0.539814E+09
August 0.202102E+10 0.101103E+10 0.100999E+10 0.248781E+10 0.522315E+09
September 0.144605E+10 0.666930E+09 0.779118E+09 0.156766E+10 0.760262E+09
October 0.973950E+09 0.413837E+09 0.560113E+09 0.845602E+09 0.110406E+10
November 0.461977E+09 0.130421E+09 0.331556E+09 0.212425E+09 0.139895E+10
December 0.391556E+09 0.126053E+09 0.265502E+09 0.158124E+09 0.177472E+10
           
Annual Sum or Average 0.152102E+11 0.628686E+10 0.892335E+10 0.151234E+11 0.128140E+11
Minimum of Months 0.391556E+09 0.103440E+09 0.265502E+09 0.121426E+09 0.522315E+09
Maximum of Months 0.213688E+10 0.101103E+10 0.120711E+10 0.248781E+10 0.177472E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100968E+10 0.599553E+09 0.410128E+09 0.859780E+09 0.142960E+10
February 0.140247E+10 0.868148E+09 0.534322E+09 0.137911E+10 0.116925E+10
March 0.167029E+10 0.890750E+09 0.779544E+09 0.173730E+10 0.113855E+10
April 0.170663E+10 0.741008E+09 0.965618E+09 0.188709E+10 0.922873E+09
May 0.161251E+10 0.480382E+09 0.113212E+10 0.181218E+10 0.771745E+09
June 0.142770E+10 0.383319E+09 0.104438E+10 0.163997E+10 0.592331E+09
July 0.160886E+10 0.589252E+09 0.101961E+10 0.204537E+10 0.550776E+09
August 0.172852E+10 0.806038E+09 0.922483E+09 0.227364E+10 0.532766E+09
September 0.185335E+10 0.102348E+10 0.829870E+09 0.228437E+10 0.721100E+09
October 0.173478E+10 0.107110E+10 0.663683E+09 0.193949E+10 0.999066E+09
November 0.992577E+09 0.568830E+09 0.423747E+09 0.908367E+09 0.119093E+10
December 0.107314E+10 0.694469E+09 0.378667E+09 0.101352E+10 0.149579E+10
           
Annual Sum or Average 0.178205E+11 0.871633E+10 0.910418E+10 0.197802E+11 0.115148E+11
Minimum of Months 0.992577E+09 0.383319E+09 0.378667E+09 0.859780E+09 0.532766E+09
Maximum of Months 0.185335E+10 0.107110E+10 0.113212E+10 0.228437E+10 0.149579E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100968E+10 0.599553E+09 0.410128E+09 0.859779E+09 0.142960E+10
February 0.140247E+10 0.868147E+09 0.534322E+09 0.137911E+10 0.116925E+10
March 0.167029E+10 0.890748E+09 0.779544E+09 0.173730E+10 0.113855E+10
April 0.170662E+10 0.741007E+09 0.965618E+09 0.188709E+10 0.922873E+09
May 0.161251E+10 0.480382E+09 0.113212E+10 0.181218E+10 0.771745E+09
June 0.142770E+10 0.383318E+09 0.104438E+10 0.163997E+10 0.592331E+09
July 0.160886E+10 0.589251E+09 0.101961E+10 0.204537E+10 0.550776E+09
August 0.172852E+10 0.806038E+09 0.922483E+09 0.227364E+10 0.532766E+09
September 0.185335E+10 0.102348E+10 0.829869E+09 0.228437E+10 0.721100E+09
October 0.173478E+10 0.107110E+10 0.663682E+09 0.193949E+10 0.999066E+09
November 0.992575E+09 0.568829E+09 0.423746E+09 0.908365E+09 0.119093E+10
December 0.107314E+10 0.694468E+09 0.378667E+09 0.101352E+10 0.149579E+10
           
Annual Sum or Average 0.178205E+11 0.871632E+10 0.910417E+10 0.197802E+11 0.115148E+11
Minimum of Months 0.992575E+09 0.383318E+09 0.378667E+09 0.859779E+09 0.532766E+09
Maximum of Months 0.185335E+10 0.107110E+10 0.113212E+10 0.228437E+10 0.149579E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100968E+10 0.599553E+09 0.410128E+09 0.859780E+09 0.142960E+10
February 0.140247E+10 0.868148E+09 0.534322E+09 0.137911E+10 0.116925E+10
March 0.167029E+10 0.890750E+09 0.779544E+09 0.173730E+10 0.113855E+10
April 0.170663E+10 0.741008E+09 0.965618E+09 0.188709E+10 0.922873E+09
May 0.161251E+10 0.480382E+09 0.113212E+10 0.181218E+10 0.771745E+09
June 0.142770E+10 0.383319E+09 0.104438E+10 0.163997E+10 0.592331E+09
July 0.160886E+10 0.589252E+09 0.101961E+10 0.204537E+10 0.550776E+09
August 0.172852E+10 0.806038E+09 0.922483E+09 0.227364E+10 0.532766E+09
September 0.185335E+10 0.102348E+10 0.829870E+09 0.228437E+10 0.721100E+09
October 0.173478E+10 0.107110E+10 0.663683E+09 0.193949E+10 0.999066E+09
November 0.992577E+09 0.568830E+09 0.423747E+09 0.908367E+09 0.119093E+10
December 0.107314E+10 0.694469E+09 0.378667E+09 0.101352E+10 0.149579E+10
           
Annual Sum or Average 0.178205E+11 0.871633E+10 0.910418E+10 0.197802E+11 0.115148E+11
Minimum of Months 0.992577E+09 0.383319E+09 0.378667E+09 0.859780E+09 0.532766E+09
Maximum of Months 0.185335E+10 0.107110E+10 0.113212E+10 0.228437E+10 0.149579E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100968E+10 0.599553E+09 0.410128E+09 0.859779E+09 0.142960E+10
February 0.140247E+10 0.868147E+09 0.534322E+09 0.137911E+10 0.116925E+10
March 0.167029E+10 0.890748E+09 0.779544E+09 0.173730E+10 0.113855E+10
April 0.170662E+10 0.741007E+09 0.965618E+09 0.188709E+10 0.922873E+09
May 0.161251E+10 0.480382E+09 0.113212E+10 0.181218E+10 0.771745E+09
June 0.142770E+10 0.383318E+09 0.104438E+10 0.163997E+10 0.592331E+09
July 0.160886E+10 0.589251E+09 0.101961E+10 0.204537E+10 0.550776E+09
August 0.172852E+10 0.806038E+09 0.922483E+09 0.227364E+10 0.532766E+09
September 0.185335E+10 0.102348E+10 0.829869E+09 0.228437E+10 0.721100E+09
October 0.173478E+10 0.107110E+10 0.663682E+09 0.193949E+10 0.999066E+09
November 0.992575E+09 0.568829E+09 0.423746E+09 0.908365E+09 0.119093E+10
December 0.107314E+10 0.694468E+09 0.378667E+09 0.101352E+10 0.149579E+10
           
Annual Sum or Average 0.178205E+11 0.871632E+10 0.910417E+10 0.197802E+11 0.115148E+11
Minimum of Months 0.992575E+09 0.383318E+09 0.378667E+09 0.859779E+09 0.532766E+09
Maximum of Months 0.185335E+10 0.107110E+10 0.113212E+10 0.228437E+10 0.149579E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100964E+10 0.599529E+09 0.410112E+09 0.859746E+09 0.142955E+10
February 0.140241E+10 0.868113E+09 0.534301E+09 0.137906E+10 0.116921E+10
March 0.167023E+10 0.890714E+09 0.779513E+09 0.173723E+10 0.113850E+10
April 0.170656E+10 0.740978E+09 0.965579E+09 0.188701E+10 0.922836E+09
May 0.161244E+10 0.480363E+09 0.113208E+10 0.181211E+10 0.771714E+09
June 0.142764E+10 0.383303E+09 0.104434E+10 0.163990E+10 0.592308E+09
July 0.160880E+10 0.589228E+09 0.101957E+10 0.204529E+10 0.550754E+09
August 0.172845E+10 0.806006E+09 0.922446E+09 0.227355E+10 0.532745E+09
September 0.185328E+10 0.102344E+10 0.829837E+09 0.228428E+10 0.721071E+09
October 0.173471E+10 0.107106E+10 0.663656E+09 0.193941E+10 0.999026E+09
November 0.992537E+09 0.568807E+09 0.423730E+09 0.908330E+09 0.119088E+10
December 0.107309E+10 0.694441E+09 0.378652E+09 0.101348E+10 0.149573E+10
           
Annual Sum or Average 0.178198E+11 0.871598E+10 0.910381E+10 0.197794E+11 0.115143E+11
Minimum of Months 0.992537E+09 0.383303E+09 0.378652E+09 0.859746E+09 0.532745E+09
Maximum of Months 0.185328E+10 0.107106E+10 0.113208E+10 0.228428E+10 0.149573E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.430342E+09 0.126900E+09 0.303442E+09 0.153428E+09 0.189000E+10
February 0.696902E+09 0.261915E+09 0.434986E+09 0.427953E+09 0.154035E+10
March 0.108117E+10 0.364923E+09 0.716244E+09 0.822273E+09 0.144146E+10
April 0.159182E+10 0.608613E+09 0.983205E+09 0.150719E+10 0.114492E+10
May 0.211658E+10 0.859850E+09 0.125673E+10 0.228288E+10 0.904834E+09
June 0.196990E+10 0.764848E+09 0.120505E+10 0.216658E+10 0.711555E+09
July 0.251466E+10 0.132184E+10 0.119283E+10 0.304811E+10 0.688591E+09
August 0.208023E+10 0.106223E+10 0.101800E+10 0.254356E+10 0.688095E+09
September 0.163938E+10 0.786612E+09 0.852771E+09 0.185086E+10 0.867313E+09
October 0.964416E+09 0.392954E+09 0.571463E+09 0.826326E+09 0.126626E+10
November 0.464781E+09 0.131087E+09 0.333693E+09 0.208854E+09 0.160398E+10
December 0.403763E+09 0.138359E+09 0.265403E+09 0.183456E+09 0.207501E+10
           
Annual Sum or Average 0.159539E+11 0.682012E+10 0.913382E+10 0.160215E+11 0.148224E+11
Minimum of Months 0.403763E+09 0.126900E+09 0.265403E+09 0.153428E+09 0.688095E+09
Maximum of Months 0.251466E+10 0.132184E+10 0.125673E+10 0.304811E+10 0.207501E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.430342E+09 0.126900E+09 0.303442E+09 0.153428E+09 0.189000E+10
February 0.696902E+09 0.261915E+09 0.434986E+09 0.427953E+09 0.154035E+10
March 0.108117E+10 0.364923E+09 0.716244E+09 0.822273E+09 0.144146E+10
April 0.159182E+10 0.608613E+09 0.983205E+09 0.150719E+10 0.114492E+10
May 0.211658E+10 0.859850E+09 0.125673E+10 0.228288E+10 0.904834E+09
June 0.196990E+10 0.764848E+09 0.120505E+10 0.216658E+10 0.711555E+09
July 0.251466E+10 0.132184E+10 0.119283E+10 0.304811E+10 0.688591E+09
August 0.208023E+10 0.106223E+10 0.101800E+10 0.254356E+10 0.688095E+09
September 0.163938E+10 0.786612E+09 0.852771E+09 0.185086E+10 0.867313E+09
October 0.964416E+09 0.392954E+09 0.571463E+09 0.826326E+09 0.126626E+10
November 0.464781E+09 0.131087E+09 0.333693E+09 0.208854E+09 0.160398E+10
December 0.403763E+09 0.138359E+09 0.265403E+09 0.183456E+09 0.207501E+10
           
Annual Sum or Average 0.159539E+11 0.682012E+10 0.913382E+10 0.160215E+11 0.148224E+11
Minimum of Months 0.403763E+09 0.126900E+09 0.265403E+09 0.153428E+09 0.688095E+09
Maximum of Months 0.251466E+10 0.132184E+10 0.125673E+10 0.304811E+10 0.207501E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.430334E+09 0.126898E+09 0.303437E+09 0.153425E+09 0.188996E+10
February 0.696889E+09 0.261911E+09 0.434979E+09 0.427946E+09 0.154032E+10
March 0.108115E+10 0.364916E+09 0.716231E+09 0.822258E+09 0.144143E+10
April 0.159179E+10 0.608602E+09 0.983187E+09 0.150717E+10 0.114490E+10
May 0.211654E+10 0.859835E+09 0.125670E+10 0.228283E+10 0.904818E+09
June 0.196987E+10 0.764834E+09 0.120503E+10 0.216654E+10 0.711542E+09
July 0.251462E+10 0.132181E+10 0.119281E+10 0.304805E+10 0.688578E+09
August 0.208019E+10 0.106221E+10 0.101799E+10 0.254351E+10 0.688082E+09
September 0.163935E+10 0.786597E+09 0.852756E+09 0.185082E+10 0.867297E+09
October 0.964399E+09 0.392946E+09 0.571452E+09 0.826311E+09 0.126623E+10
November 0.464772E+09 0.131085E+09 0.333687E+09 0.208850E+09 0.160395E+10
December 0.403755E+09 0.138357E+09 0.265399E+09 0.183452E+09 0.207498E+10
           
Annual Sum or Average 0.159537E+11 0.682000E+10 0.913365E+10 0.160212E+11 0.148221E+11
Minimum of Months 0.403755E+09 0.126898E+09 0.265399E+09 0.153425E+09 0.688082E+09
Maximum of Months 0.251462E+10 0.132181E+10 0.125670E+10 0.304805E+10 0.207498E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114260E+10 0.00 0.114260E+10 32266911.94 0.721531E+10
February 0.160585E+10 0.00 0.160585E+10 0.283952E+09 0.583114E+10
March 0.261947E+10 0.00 0.261947E+10 0.102551E+10 0.536242E+10
April 0.358724E+10 12725040.77 0.357452E+10 0.225595E+10 0.413295E+10
May 0.476974E+10 0.141702E+09 0.462804E+10 0.380524E+10 0.343632E+10
June 0.485348E+10 0.320504E+09 0.453298E+10 0.430663E+10 0.255290E+10
July 0.476673E+10 0.373735E+09 0.439300E+10 0.481586E+10 0.235967E+10
August 0.385871E+10 0.104312E+09 0.375439E+10 0.397032E+10 0.231064E+10
September 0.290062E+10 855348.19 0.289976E+10 0.219222E+10 0.335799E+10
October 0.205365E+10 0.00 0.205365E+10 0.880319E+09 0.470775E+10
November 0.125187E+10 0.00 0.125187E+10 0.150046E+09 0.576275E+10
December 0.970912E+09 0.00 0.970912E+09 14081962.67 0.730067E+10
           
Annual Sum or Average 0.343809E+11 0.953833E+09 0.334270E+11 0.237324E+11 0.543305E+11
Minimum of Months 0.970912E+09 0.00 0.970912E+09 14081962.67 0.231064E+10
Maximum of Months 0.485348E+10 0.373735E+09 0.462804E+10 0.481586E+10 0.730067E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122399E+10 0.310323E+09 0.913670E+09 0.412505E+09 0.458872E+10
February 0.202856E+10 0.719979E+09 0.130858E+10 0.125095E+10 0.372368E+10
March 0.335330E+10 0.121392E+10 0.213937E+10 0.266605E+10 0.347780E+10
April 0.503050E+10 0.209025E+10 0.294025E+10 0.495947E+10 0.269939E+10
May 0.553133E+10 0.192312E+10 0.360821E+10 0.576614E+10 0.233709E+10
June 0.641070E+10 0.278934E+10 0.362136E+10 0.722041E+10 0.177104E+10
July 0.616885E+10 0.276893E+10 0.339991E+10 0.727418E+10 0.160161E+10
August 0.606311E+10 0.303312E+10 0.303000E+10 0.740060E+10 0.156975E+10
September 0.433818E+10 0.200081E+10 0.233737E+10 0.468250E+10 0.219814E+10
October 0.292187E+10 0.124152E+10 0.168035E+10 0.256627E+10 0.307598E+10
November 0.138594E+10 0.391265E+09 0.994677E+09 0.683808E+09 0.374089E+10
December 0.117468E+10 0.378163E+09 0.796514E+09 0.520432E+09 0.469793E+10
           
Annual Sum or Average 0.456310E+11 0.188607E+11 0.267703E+11 0.454033E+11 0.354820E+11
Minimum of Months 0.117468E+10 0.310323E+09 0.796514E+09 0.412505E+09 0.156975E+10
Maximum of Months 0.641070E+10 0.303312E+10 0.362136E+10 0.740060E+10 0.469793E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.504835E+10 0.299773E+10 0.205062E+10 0.434692E+10 0.668476E+10
February 0.701227E+10 0.434069E+10 0.267158E+10 0.691686E+10 0.558066E+10
March 0.835137E+10 0.445369E+10 0.389768E+10 0.866890E+10 0.544619E+10
April 0.853303E+10 0.370499E+10 0.482803E+10 0.940321E+10 0.443320E+10
May 0.806244E+10 0.240188E+10 0.566056E+10 0.899692E+10 0.378358E+10
June 0.713840E+10 0.191657E+10 0.522183E+10 0.815623E+10 0.287736E+10
July 0.804422E+10 0.294622E+10 0.509800E+10 0.101825E+11 0.268249E+10
August 0.864250E+10 0.403014E+10 0.461236E+10 0.113238E+11 0.260816E+10
September 0.926665E+10 0.511735E+10 0.414930E+10 0.113677E+11 0.354279E+10
October 0.867382E+10 0.535544E+10 0.331838E+10 0.965393E+10 0.481643E+10
November 0.496282E+10 0.284412E+10 0.211871E+10 0.458306E+10 0.558198E+10
December 0.536562E+10 0.347230E+10 0.189331E+10 0.512177E+10 0.693073E+10
           
Annual Sum or Average 0.891015E+11 0.435811E+11 0.455203E+11 0.987218E+11 0.549683E+11
Minimum of Months 0.496282E+10 0.191657E+10 0.189331E+10 0.434692E+10 0.260816E+10
Maximum of Months 0.926665E+10 0.535544E+10 0.566056E+10 0.113677E+11 0.693073E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129101E+10 0.380696E+09 0.910317E+09 0.515883E+09 0.476422E+10
February 0.209068E+10 0.785738E+09 0.130495E+10 0.139016E+10 0.387541E+10
March 0.324347E+10 0.109476E+10 0.214871E+10 0.259564E+10 0.366271E+10
April 0.477540E+10 0.182582E+10 0.294958E+10 0.466743E+10 0.294791E+10
May 0.634966E+10 0.257952E+10 0.377014E+10 0.686935E+10 0.253935E+10
June 0.590965E+10 0.229452E+10 0.361513E+10 0.655379E+10 0.193546E+10
July 0.754391E+10 0.396547E+10 0.357845E+10 0.920705E+10 0.185637E+10
August 0.624062E+10 0.318664E+10 0.305398E+10 0.772883E+10 0.180785E+10
September 0.491810E+10 0.235981E+10 0.255829E+10 0.558438E+10 0.240800E+10
October 0.289322E+10 0.117885E+10 0.171437E+10 0.257632E+10 0.327480E+10
November 0.139433E+10 0.393258E+09 0.100107E+10 0.713175E+09 0.387472E+10
December 0.121128E+10 0.415073E+09 0.796202E+09 0.619316E+09 0.489607E+10
           
Annual Sum or Average 0.478613E+11 0.204602E+11 0.274012E+11 0.490213E+11 0.378429E+11
Minimum of Months 0.121128E+10 0.380696E+09 0.796202E+09 0.515883E+09 0.180785E+10
Maximum of Months 0.754391E+10 0.396547E+10 0.377014E+10 0.920705E+10 0.489607E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114260E+10 0.00 0.114260E+10 55170184.89 0.664188E+10
February 0.160585E+10 0.00 0.160585E+10 0.353837E+09 0.531606E+10
March 0.261947E+10 0.00 0.261947E+10 0.115520E+10 0.488870E+10
April 0.358724E+10 12725040.77 0.357452E+10 0.236437E+10 0.386017E+10
May 0.476974E+10 0.141702E+09 0.462804E+10 0.387363E+10 0.327537E+10
June 0.485348E+10 0.320504E+09 0.453298E+10 0.431581E+10 0.248343E+10
July 0.476673E+10 0.373735E+09 0.439300E+10 0.480115E+10 0.231311E+10
August 0.385871E+10 0.104312E+09 0.375439E+10 0.396824E+10 0.225334E+10
September 0.290062E+10 855348.19 0.289976E+10 0.225287E+10 0.316044E+10
October 0.205365E+10 0.00 0.205365E+10 0.100691E+10 0.424703E+10
November 0.125187E+10 0.00 0.125187E+10 0.208048E+09 0.512910E+10
December 0.970912E+09 0.00 0.970912E+09 34418847.21 0.661908E+10
           
Annual Sum or Average 0.343809E+11 0.953833E+09 0.334270E+11 0.243896E+11 0.501877E+11
Minimum of Months 0.970912E+09 0.00 0.970912E+09 34418847.21 0.225334E+10
Maximum of Months 0.485348E+10 0.373735E+09 0.462804E+10 0.480115E+10 0.664188E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122399E+10 0.310323E+09 0.913670E+09 0.455295E+09 0.421766E+10
February 0.202856E+10 0.719979E+09 0.130858E+10 0.134109E+10 0.338568E+10
March 0.335330E+10 0.121392E+10 0.213937E+10 0.277286E+10 0.318136E+10
April 0.503050E+10 0.209025E+10 0.294025E+10 0.503424E+10 0.254105E+10
May 0.553133E+10 0.192312E+10 0.360821E+10 0.581084E+10 0.223845E+10
June 0.641070E+10 0.278934E+10 0.362136E+10 0.722519E+10 0.172897E+10
July 0.616885E+10 0.276893E+10 0.339991E+10 0.727287E+10 0.157572E+10
August 0.606311E+10 0.303312E+10 0.303000E+10 0.740398E+10 0.153684E+10
September 0.433818E+10 0.200081E+10 0.233737E+10 0.472874E+10 0.208171E+10
October 0.292187E+10 0.124152E+10 0.168035E+10 0.266534E+10 0.279317E+10
November 0.138594E+10 0.391265E+09 0.994677E+09 0.756558E+09 0.332353E+10
December 0.117468E+10 0.378163E+09 0.796514E+09 0.572161E+09 0.425200E+10
           
Annual Sum or Average 0.456310E+11 0.188607E+11 0.267703E+11 0.460392E+11 0.328561E+11
Minimum of Months 0.117468E+10 0.310323E+09 0.796514E+09 0.455295E+09 0.153684E+10
Maximum of Months 0.641070E+10 0.303312E+10 0.362136E+10 0.740398E+10 0.425200E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.504835E+10 0.299773E+10 0.205062E+10 0.446599E+10 0.613188E+10
February 0.701227E+10 0.434069E+10 0.267158E+10 0.706477E+10 0.510742E+10
March 0.835137E+10 0.445369E+10 0.389768E+10 0.877433E+10 0.501689E+10
April 0.853303E+10 0.370499E+10 0.482803E+10 0.947051E+10 0.418556E+10
May 0.806244E+10 0.240188E+10 0.566056E+10 0.902662E+10 0.362010E+10
June 0.713840E+10 0.191657E+10 0.522183E+10 0.814202E+10 0.280089E+10
July 0.804422E+10 0.294622E+10 0.509800E+10 0.101504E+11 0.263486E+10
August 0.864250E+10 0.403014E+10 0.461236E+10 0.112982E+11 0.255151E+10
September 0.926665E+10 0.511735E+10 0.414930E+10 0.113996E+11 0.337413E+10
October 0.867382E+10 0.535544E+10 0.331838E+10 0.975683E+10 0.442565E+10
November 0.496282E+10 0.284412E+10 0.211871E+10 0.471520E+10 0.501646E+10
December 0.536562E+10 0.347230E+10 0.189331E+10 0.523903E+10 0.630014E+10
           
Annual Sum or Average 0.891015E+11 0.435811E+11 0.455203E+11 0.995035E+11 0.511655E+11
Minimum of Months 0.496282E+10 0.191657E+10 0.189331E+10 0.446599E+10 0.255151E+10
Maximum of Months 0.926665E+10 0.535544E+10 0.566056E+10 0.113996E+11 0.630014E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129101E+10 0.380696E+09 0.910317E+09 0.546738E+09 0.439998E+10
February 0.209068E+10 0.785738E+09 0.130495E+10 0.144474E+10 0.358120E+10
March 0.324347E+10 0.109476E+10 0.214871E+10 0.266166E+10 0.339607E+10
April 0.477540E+10 0.182582E+10 0.294958E+10 0.471208E+10 0.279419E+10
May 0.634966E+10 0.257952E+10 0.377014E+10 0.687918E+10 0.244203E+10
June 0.590965E+10 0.229452E+10 0.361513E+10 0.653596E+10 0.188766E+10
July 0.754391E+10 0.396547E+10 0.357845E+10 0.917493E+10 0.182393E+10
August 0.624062E+10 0.318664E+10 0.305398E+10 0.770618E+10 0.177172E+10
September 0.491810E+10 0.235981E+10 0.255829E+10 0.559913E+10 0.230274E+10
October 0.289322E+10 0.117885E+10 0.171437E+10 0.263914E+10 0.302046E+10
November 0.139433E+10 0.393258E+09 0.100107E+10 0.760892E+09 0.352200E+10
December 0.121128E+10 0.415073E+09 0.796202E+09 0.648963E+09 0.450714E+10
           
Annual Sum or Average 0.478613E+11 0.204602E+11 0.274012E+11 0.493096E+11 0.354491E+11
Minimum of Months 0.121128E+10 0.380696E+09 0.796202E+09 0.546738E+09 0.177172E+10
Maximum of Months 0.754391E+10 0.396547E+10 0.377014E+10 0.917493E+10 0.450714E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3.95 3135.31 426.60 0.00 426.60 0.00 0.00
February 78.04 2769.56 663.80 0.00 663.80 0.00 0.00
March 323.77 2252.01 978.00 0.00 978.00 0.00 0.00
April 811.03 1762.15 1383.97 4.91 1379.06 0.00 0.00
May 1393.30 1351.07 1780.82 52.91 1727.92 0.00 0.00
June 1638.35 1038.10 1872.49 123.65 1748.84 0.00 0.00
July 1770.10 927.01 1779.70 139.54 1640.16 0.00 0.00
August 1452.12 909.40 1440.68 38.95 1401.74 0.00 0.00
September 819.76 1384.32 1119.07 0.33 1118.74 0.00 0.00
October 280.29 1974.12 766.75 0.00 766.75 0.00 0.00
November 35.42 2610.50 482.98 0.00 482.98 0.00 0.00
December 0.82 3233.02 362.50 0.00 362.50 0.00 0.00
               
Annual Sum or Average 721.31 1941.48 1090.21 30.25 1059.97 0.00 0.00
Minimum of Months 0.82 909.40 362.50 0.00 362.50 0.00 0.00
Maximum of Months 1770.10 3233.02 1872.49 139.54 1748.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 136.01 1961.16 456.99 115.86 341.13 0.00 0.00
February 486.30 1698.74 838.53 297.61 540.92 0.00 0.00
March 983.82 1394.11 1251.98 453.23 798.75 0.00 0.00
April 1917.00 1091.53 1940.79 806.43 1134.36 0.00 0.00
May 2164.80 899.31 2065.17 718.01 1347.16 0.00 0.00
June 2809.57 697.35 2473.27 1076.14 1397.14 0.00 0.00
July 2736.88 604.64 2303.19 1033.81 1269.39 0.00 0.00
August 2786.56 585.04 2263.72 1132.44 1131.28 0.00 0.00
September 1814.45 879.94 1673.69 771.92 901.77 0.00 0.00
October 947.15 1236.64 1090.91 463.53 627.37 0.00 0.00
November 245.87 1619.17 534.70 150.95 383.75 0.00 0.00
December 177.11 1987.84 438.58 141.19 297.39 0.00 0.00
               
Annual Sum or Average 1438.70 1219.00 1446.96 598.07 848.88 0.00 0.00
Minimum of Months 136.01 585.04 438.58 115.86 297.39 0.00 0.00
Maximum of Months 2809.57 1987.84 2473.27 1132.44 1397.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1605.01 2668.74 1884.84 1119.23 765.61 0.00 0.00
February 2850.33 2416.59 2898.60 1794.27 1104.33 0.00 0.00
March 3243.14 2125.41 3118.06 1662.82 1455.23 0.00 0.00
April 3640.19 1780.22 3292.07 1429.40 1862.67 0.00 0.00
May 3382.93 1440.67 3010.18 896.76 2113.42 0.00 0.00
June 3163.49 1142.61 2754.02 739.42 2014.60 0.00 0.00
July 3818.24 1028.17 3003.38 1100.00 1903.38 0.00 0.00
August 4244.37 994.55 3226.75 1504.69 1722.06 0.00 0.00
September 4406.54 1391.00 3575.11 1974.29 1600.82 0.00 0.00
October 3620.59 1865.03 3238.44 1999.50 1238.94 0.00 0.00
November 1752.24 2297.29 1914.68 1097.27 817.41 0.00 0.00
December 1892.00 2792.31 2003.30 1296.41 706.89 0.00 0.00
               
Annual Sum or Average 3136.10 1825.64 2825.40 1381.95 1443.45 0.00 0.00
Minimum of Months 1605.01 994.55 1884.84 739.42 706.89 0.00 0.00
Maximum of Months 4406.54 2792.31 3575.11 1999.50 2113.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 171.85 2116.92 482.01 142.14 339.87 0.00 0.00
February 530.69 1910.15 864.21 324.79 539.41 0.00 0.00
March 921.00 1614.53 1210.98 408.74 802.24 0.00 0.00
April 1744.43 1325.13 1842.37 704.41 1137.96 0.00 0.00
May 2556.97 1013.47 2370.70 963.09 1407.61 0.00 0.00
June 2507.60 823.55 2279.97 885.24 1394.73 0.00 0.00
July 3414.08 771.27 2816.59 1480.54 1336.04 0.00 0.00
August 2848.95 770.71 2329.99 1189.76 1140.23 0.00 0.00
September 2142.18 1003.83 1897.42 910.42 987.00 0.00 0.00
October 925.54 1418.29 1080.21 440.13 640.08 0.00 0.00
November 241.73 1856.44 537.94 151.72 386.22 0.00 0.00
December 205.48 2324.15 452.24 154.97 297.27 0.00 0.00
               
Annual Sum or Average 1524.10 1410.03 1517.68 648.79 868.89 0.00 0.00
Minimum of Months 171.85 770.71 452.24 142.14 297.27 0.00 0.00
Maximum of Months 3414.08 2324.15 2816.59 1480.54 1407.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.05 2693.89 426.60 0.00 426.60 0.00 0.00
February 117.37 2410.36 663.80 0.00 663.80 0.00 0.00
March 382.88 2002.10 978.00 0.00 978.00 0.00 0.00
April 870.35 1594.50 1383.97 4.91 1379.06 0.00 0.00
May 1420.72 1282.98 1780.82 52.91 1727.91 0.00 0.00
June 1661.51 984.92 1872.49 123.65 1748.83 0.00 0.00
July 1798.04 881.00 1779.69 139.54 1640.16 0.00 0.00
August 1482.35 862.69 1440.68 38.95 1401.73 0.00 0.00
September 845.76 1295.52 1119.07 0.33 1118.74 0.00 0.00
October 328.67 1757.67 766.75 0.00 766.75 0.00 0.00
November 57.89 2223.28 482.97 0.00 482.97 0.00 0.00
December 5.26 2725.76 362.50 0.00 362.50 0.00 0.00
               
Annual Sum or Average 752.55 1722.81 1090.21 30.25 1059.96 0.00 0.00
Minimum of Months 5.26 862.69 362.50 0.00 362.50 0.00 0.00
Maximum of Months 1798.04 2725.76 1872.49 139.54 1748.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 154.01 1713.23 456.99 115.86 341.13 0.00 0.00
February 517.09 1539.22 838.53 297.61 540.92 0.00 0.00
March 995.39 1298.46 1251.98 453.23 798.75 0.00 0.00
April 1913.38 1041.43 1940.78 806.42 1134.36 0.00 0.00
May 2152.83 872.57 2065.16 718.01 1347.15 0.00 0.00
June 2785.65 683.27 2473.26 1076.14 1397.13 0.00 0.00
July 2715.87 597.97 2303.18 1033.80 1269.38 0.00 0.00
August 2763.07 586.08 2263.71 1132.44 1131.27 0.00 0.00
September 1806.52 848.05 1673.68 771.92 901.76 0.00 0.00
October 958.13 1148.44 1090.90 463.53 627.37 0.00 0.00
November 263.81 1443.24 534.70 150.95 383.75 0.00 0.00
December 194.31 1754.01 438.57 141.19 297.38 0.00 0.00
               
Annual Sum or Average 1439.73 1125.13 1446.95 598.07 848.88 0.00 0.00
Minimum of Months 154.01 586.08 438.57 115.86 297.38 0.00 0.00
Maximum of Months 2785.65 1754.01 2473.26 1132.44 1397.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1622.95 2495.80 1884.84 1119.22 765.61 0.00 0.00
February 2859.15 2306.82 2898.59 1794.27 1104.32 0.00 0.00
March 3236.60 2033.37 3118.04 1662.82 1455.23 0.00 0.00
April 3627.78 1710.34 3292.06 1429.40 1862.67 0.00 0.00
May 3359.07 1412.63 3010.17 896.76 2113.41 0.00 0.00
June 3146.69 1110.09 2754.01 739.42 2014.59 0.00 0.00
July 3801.70 1001.53 3003.37 1099.99 1903.38 0.00 0.00
August 4227.83 973.78 3226.74 1504.68 1722.06 0.00 0.00
September 4385.67 1366.82 3575.10 1974.29 1600.81 0.00 0.00
October 3604.36 1798.25 3238.43 1999.49 1238.94 0.00 0.00
November 1768.16 2153.54 1914.67 1097.27 817.40 0.00 0.00
December 1912.25 2587.64 2003.29 1296.41 706.88 0.00 0.00
               
Annual Sum or Average 3130.45 1743.03 2825.39 1381.95 1443.44 0.00 0.00
Minimum of Months 1622.95 973.78 1884.84 739.42 706.88 0.00 0.00
Maximum of Months 4385.67 2587.64 3575.10 1999.49 2113.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 192.61 1778.75 482.01 142.14 339.87 0.00 0.00
February 574.64 1601.94 864.20 324.79 539.41 0.00 0.00
March 969.10 1367.50 1210.97 408.74 802.24 0.00 0.00
April 1800.70 1137.31 1842.36 704.41 1137.96 0.00 0.00
May 2564.72 948.08 2370.69 963.08 1407.61 0.00 0.00
June 2528.47 746.71 2279.96 885.23 1394.72 0.00 0.00
July 3437.52 693.09 2816.58 1480.54 1336.04 0.00 0.00
August 2885.62 674.98 2329.98 1189.76 1140.23 0.00 0.00
September 2154.47 929.01 1897.41 910.42 986.99 0.00 0.00
October 961.89 1222.67 1080.20 440.13 640.07 0.00 0.00
November 275.14 1494.88 537.94 151.72 386.21 0.00 0.00
December 231.23 1827.98 452.24 154.97 297.27 0.00 0.00
               
Annual Sum or Average 1554.46 1199.99 1517.67 648.79 868.89 0.00 0.00
Minimum of Months 192.61 674.98 452.24 142.14 297.27 0.00 0.00
Maximum of Months 3437.52 1827.98 2816.58 1480.54 1407.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 20.60 2479.79 426.60 0.00 426.60 0.00 0.00
February 146.26 2197.45 663.80 0.00 663.80 0.00 0.00
March 431.30 1825.23 978.00 0.00 978.00 0.00 0.00
April 912.18 1489.26 1383.97 4.91 1379.06 0.00 0.00
May 1446.25 1222.88 1780.82 52.91 1727.91 0.00 0.00
June 1665.05 958.11 1872.49 123.65 1748.83 0.00 0.00
July 1792.54 863.62 1779.69 139.54 1640.16 0.00 0.00
August 1481.57 841.30 1440.68 38.95 1401.73 0.00 0.00
September 869.16 1219.31 1119.07 0.33 1118.74 0.00 0.00
October 375.94 1585.66 766.75 0.00 766.75 0.00 0.00
November 80.27 1978.82 482.97 0.00 482.97 0.00 0.00
December 12.85 2471.28 362.50 0.00 362.50 0.00 0.00
               
Annual Sum or Average 773.39 1591.44 1090.21 30.25 1059.96 0.00 0.00
Minimum of Months 12.85 841.30 362.50 0.00 362.50 0.00 0.00
Maximum of Months 1792.54 2479.79 1872.49 139.54 1748.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 169.99 1574.69 456.99 115.86 341.13 0.00 0.00
February 554.35 1399.50 838.53 297.61 540.92 0.00 0.00
March 1035.27 1187.78 1251.98 453.23 798.75 0.00 0.00
April 1942.22 980.34 1940.78 806.42 1134.36 0.00 0.00
May 2169.52 835.74 2065.16 718.01 1347.15 0.00 0.00
June 2787.50 667.04 2473.26 1076.14 1397.13 0.00 0.00
July 2715.38 588.31 2303.18 1033.80 1269.38 0.00 0.00
August 2764.33 573.79 2263.71 1132.44 1131.27 0.00 0.00
September 1824.36 803.13 1673.68 771.92 901.76 0.00 0.00
October 995.13 1042.85 1090.90 463.53 627.37 0.00 0.00
November 291.88 1282.22 534.70 150.95 383.75 0.00 0.00
December 213.62 1587.51 438.57 141.19 297.38 0.00 0.00
               
Annual Sum or Average 1459.89 1041.86 1446.95 598.07 848.88 0.00 0.00
Minimum of Months 169.99 573.79 438.57 115.86 297.38 0.00 0.00
Maximum of Months 2787.50 1587.51 2473.26 1132.44 1397.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1667.41 2289.38 1884.84 1119.22 765.61 0.00 0.00
February 2920.29 2111.20 2898.59 1794.27 1104.32 0.00 0.00
March 3275.96 1873.09 3118.04 1662.82 1455.23 0.00 0.00
April 3653.74 1614.80 3292.06 1429.40 1862.67 0.00 0.00
May 3370.15 1351.59 3010.17 896.76 2113.41 0.00 0.00
June 3141.21 1080.59 2754.01 739.42 2014.59 0.00 0.00
July 3789.73 983.74 3003.37 1099.99 1903.38 0.00 0.00
August 4218.25 952.62 3226.74 1504.68 1722.06 0.00 0.00
September 4398.01 1301.75 3575.10 1974.29 1600.81 0.00 0.00
October 3642.78 1652.35 3238.43 1999.49 1238.94 0.00 0.00
November 1819.14 1935.36 1914.67 1097.27 817.40 0.00 0.00
December 1956.03 2352.20 2003.29 1296.41 706.88 0.00 0.00
               
Annual Sum or Average 3155.24 1622.45 2825.39 1381.95 1443.44 0.00 0.00
Minimum of Months 1667.41 952.62 1884.84 739.42 706.88 0.00 0.00
Maximum of Months 4398.01 2352.20 3575.10 1999.49 2113.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 204.13 1642.76 482.01 142.14 339.87 0.00 0.00
February 597.20 1480.32 864.20 324.79 539.41 0.00 0.00
March 993.75 1267.95 1210.97 408.74 802.24 0.00 0.00
April 1817.93 1078.00 1842.36 704.41 1137.96 0.00 0.00
May 2568.39 911.75 2370.69 963.08 1407.61 0.00 0.00
June 2521.59 728.27 2279.96 885.23 1394.72 0.00 0.00
July 3425.53 680.98 2816.58 1480.54 1336.04 0.00 0.00
August 2877.16 661.48 2329.98 1189.76 1140.23 0.00 0.00
September 2160.16 888.40 1897.41 910.42 986.99 0.00 0.00
October 985.34 1127.71 1080.20 440.13 640.07 0.00 0.00
November 293.55 1358.80 537.94 151.72 386.21 0.00 0.00
December 242.29 1682.77 452.24 154.97 297.27 0.00 0.00
               
Annual Sum or Average 1563.60 1124.08 1517.67 648.79 868.89 0.00 0.00
Minimum of Months 204.13 661.48 452.24 142.14 297.27 0.00 0.00
Maximum of Months 3425.53 1682.77 2816.58 1480.54 1407.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 10570500.16 0.839762E+10 0.114260E+10 0.00 0.114260E+10 0.00 0.00
February 0.188805E+09 0.670013E+10 0.160586E+10 0.00 0.160586E+10 0.00 0.00
March 0.867182E+09 0.603178E+10 0.261948E+10 0.00 0.261948E+10 0.00 0.00
April 0.210220E+10 0.456750E+10 0.358726E+10 12725085.96 0.357453E+10 0.00 0.00
May 0.373183E+10 0.361869E+10 0.476976E+10 0.141703E+09 0.462806E+10 0.00 0.00
June 0.424660E+10 0.269076E+10 0.485350E+10 0.320505E+09 0.453300E+10 0.00 0.00
July 0.474105E+10 0.248291E+10 0.476675E+10 0.373736E+09 0.439302E+10 0.00 0.00
August 0.388936E+10 0.243573E+10 0.385872E+10 0.104313E+09 0.375441E+10 0.00 0.00
September 0.212481E+10 0.358816E+10 0.290063E+10 855351.23 0.289977E+10 0.00 0.00
October 0.750728E+09 0.528749E+10 0.205366E+10 0.00 0.205366E+10 0.00 0.00
November 91815112.76 0.676642E+10 0.125188E+10 0.00 0.125188E+10 0.00 0.00
December 2185292.91 0.865933E+10 0.970916E+09 0.00 0.970916E+09 0.00 0.00
               
Annual Sum or Average 0.227471E+11 0.612265E+11 0.343810E+11 0.953837E+09 0.334272E+11 0.00 0.00
Minimum of Months 2185292.91 0.243573E+10 0.970916E+09 0.00 0.970916E+09 0.00 0.00
Maximum of Months 0.474105E+10 0.865933E+10 0.485350E+10 0.373736E+09 0.462806E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.364282E+09 0.525277E+10 0.122400E+10 0.310324E+09 0.913673E+09 0.00 0.00
February 0.117647E+10 0.410960E+10 0.202857E+10 0.719982E+09 0.130859E+10 0.00 0.00
March 0.263506E+10 0.373398E+10 0.335331E+10 0.121393E+10 0.213938E+10 0.00 0.00
April 0.496885E+10 0.282925E+10 0.503052E+10 0.209025E+10 0.294027E+10 0.00 0.00
May 0.579820E+10 0.240870E+10 0.553135E+10 0.192312E+10 0.360823E+10 0.00 0.00
June 0.728240E+10 0.180754E+10 0.641073E+10 0.278935E+10 0.362137E+10 0.00 0.00
July 0.733046E+10 0.161946E+10 0.616887E+10 0.276895E+10 0.339993E+10 0.00 0.00
August 0.746351E+10 0.156696E+10 0.606314E+10 0.303313E+10 0.303001E+10 0.00 0.00
September 0.470305E+10 0.228081E+10 0.433820E+10 0.200081E+10 0.233738E+10 0.00 0.00
October 0.253684E+10 0.331222E+10 0.292188E+10 0.124153E+10 0.168036E+10 0.00 0.00
November 0.637282E+09 0.419690E+10 0.138595E+10 0.391267E+09 0.994681E+09 0.00 0.00
December 0.474378E+09 0.532423E+10 0.117468E+10 0.378165E+09 0.796517E+09 0.00 0.00
               
Annual Sum or Average 0.453708E+11 0.384424E+11 0.456312E+11 0.188608E+11 0.267704E+11 0.00 0.00
Minimum of Months 0.364282E+09 0.156696E+10 0.117468E+10 0.310324E+09 0.796517E+09 0.00 0.00
Maximum of Months 0.746351E+10 0.532423E+10 0.641073E+10 0.303313E+10 0.362137E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.429886E+10 0.714796E+10 0.504836E+10 0.299774E+10 0.205062E+10 0.00 0.00
February 0.689551E+10 0.584623E+10 0.701229E+10 0.434070E+10 0.267159E+10 0.00 0.00
March 0.868643E+10 0.569271E+10 0.835140E+10 0.445371E+10 0.389769E+10 0.00 0.00
April 0.943536E+10 0.461433E+10 0.853306E+10 0.370501E+10 0.482805E+10 0.00 0.00
May 0.906084E+10 0.385869E+10 0.806247E+10 0.240189E+10 0.566058E+10 0.00 0.00
June 0.819978E+10 0.296163E+10 0.713842E+10 0.191658E+10 0.522185E+10 0.00 0.00
July 0.102268E+11 0.275386E+10 0.804425E+10 0.294623E+10 0.509802E+10 0.00 0.00
August 0.113681E+11 0.266381E+10 0.864254E+10 0.403016E+10 0.461238E+10 0.00 0.00
September 0.114217E+11 0.360547E+10 0.926669E+10 0.511737E+10 0.414932E+10 0.00 0.00
October 0.969738E+10 0.499529E+10 0.867385E+10 0.535546E+10 0.331839E+10 0.00 0.00
November 0.454179E+10 0.595459E+10 0.496284E+10 0.284413E+10 0.211872E+10 0.00 0.00
December 0.506755E+10 0.747891E+10 0.536564E+10 0.347232E+10 0.189332E+10 0.00 0.00
               
Annual Sum or Average 0.989002E+11 0.575735E+11 0.891018E+11 0.435813E+11 0.455205E+11 0.00 0.00
Minimum of Months 0.429886E+10 0.266381E+10 0.496284E+10 0.191658E+10 0.189332E+10 0.00 0.00
Maximum of Months 0.114217E+11 0.747891E+10 0.926669E+10 0.535546E+10 0.566058E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.460281E+09 0.566996E+10 0.129102E+10 0.380698E+09 0.910321E+09 0.00 0.00
February 0.128385E+10 0.462103E+10 0.209069E+10 0.785741E+09 0.130495E+10 0.00 0.00
March 0.246680E+10 0.432435E+10 0.324348E+10 0.109476E+10 0.214872E+10 0.00 0.00
April 0.452155E+10 0.343474E+10 0.477542E+10 0.182583E+10 0.294960E+10 0.00 0.00
May 0.684859E+10 0.271449E+10 0.634969E+10 0.257953E+10 0.377015E+10 0.00 0.00
June 0.649971E+10 0.213465E+10 0.590967E+10 0.229453E+10 0.361514E+10 0.00 0.00
July 0.914426E+10 0.206576E+10 0.754395E+10 0.396548E+10 0.357846E+10 0.00 0.00
August 0.763063E+10 0.206427E+10 0.624065E+10 0.318666E+10 0.305399E+10 0.00 0.00
September 0.555254E+10 0.260192E+10 0.491812E+10 0.235982E+10 0.255830E+10 0.00 0.00
October 0.247896E+10 0.379874E+10 0.289323E+10 0.117885E+10 0.171438E+10 0.00 0.00
November 0.626558E+09 0.481190E+10 0.139433E+10 0.393260E+09 0.100107E+10 0.00 0.00
December 0.550364E+09 0.622500E+10 0.121128E+10 0.415075E+09 0.796205E+09 0.00 0.00
               
Annual Sum or Average 0.480641E+11 0.444668E+11 0.478615E+11 0.204602E+11 0.274013E+11 0.00 0.00
Minimum of Months 0.460281E+09 0.206427E+10 0.121128E+10 0.380698E+09 0.796205E+09 0.00 0.00
Maximum of Months 0.914426E+10 0.622500E+10 0.754395E+10 0.396548E+10 0.377015E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 32266911.94 0.721531E+10 0.114260E+10 0.00 0.114260E+10 0.00 0.00
February 0.283952E+09 0.583114E+10 0.160585E+10 0.00 0.160585E+10 0.00 0.00
March 0.102551E+10 0.536242E+10 0.261947E+10 0.00 0.261947E+10 0.00 0.00
April 0.225595E+10 0.413295E+10 0.358724E+10 12725040.77 0.357452E+10 0.00 0.00
May 0.380524E+10 0.343632E+10 0.476974E+10 0.141702E+09 0.462804E+10 0.00 0.00
June 0.430663E+10 0.255290E+10 0.485348E+10 0.320504E+09 0.453298E+10 0.00 0.00
July 0.481586E+10 0.235967E+10 0.476673E+10 0.373735E+09 0.439300E+10 0.00 0.00
August 0.397032E+10 0.231064E+10 0.385871E+10 0.104312E+09 0.375439E+10 0.00 0.00
September 0.219222E+10 0.335799E+10 0.290062E+10 855348.19 0.289976E+10 0.00 0.00
October 0.880319E+09 0.470775E+10 0.205365E+10 0.00 0.205365E+10 0.00 0.00
November 0.150046E+09 0.576275E+10 0.125187E+10 0.00 0.125187E+10 0.00 0.00
December 14081962.67 0.730067E+10 0.970912E+09 0.00 0.970912E+09 0.00 0.00
               
Annual Sum or Average 0.237324E+11 0.543305E+11 0.343809E+11 0.953833E+09 0.334270E+11 0.00 0.00
Minimum of Months 14081962.67 0.231064E+10 0.970912E+09 0.00 0.970912E+09 0.00 0.00
Maximum of Months 0.481586E+10 0.730067E+10 0.485348E+10 0.373735E+09 0.462804E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.412505E+09 0.458872E+10 0.122399E+10 0.310323E+09 0.913670E+09 0.00 0.00
February 0.125095E+10 0.372368E+10 0.202856E+10 0.719979E+09 0.130858E+10 0.00 0.00
March 0.266605E+10 0.347780E+10 0.335330E+10 0.121392E+10 0.213937E+10 0.00 0.00
April 0.495947E+10 0.269939E+10 0.503050E+10 0.209025E+10 0.294025E+10 0.00 0.00
May 0.576614E+10 0.233709E+10 0.553133E+10 0.192312E+10 0.360821E+10 0.00 0.00
June 0.722041E+10 0.177104E+10 0.641070E+10 0.278934E+10 0.362136E+10 0.00 0.00
July 0.727418E+10 0.160161E+10 0.616885E+10 0.276893E+10 0.339991E+10 0.00 0.00
August 0.740060E+10 0.156975E+10 0.606311E+10 0.303312E+10 0.303000E+10 0.00 0.00
September 0.468250E+10 0.219814E+10 0.433818E+10 0.200081E+10 0.233737E+10 0.00 0.00
October 0.256627E+10 0.307598E+10 0.292187E+10 0.124152E+10 0.168035E+10 0.00 0.00
November 0.683808E+09 0.374089E+10 0.138594E+10 0.391265E+09 0.994677E+09 0.00 0.00
December 0.520432E+09 0.469793E+10 0.117468E+10 0.378163E+09 0.796514E+09 0.00 0.00
               
Annual Sum or Average 0.454033E+11 0.354820E+11 0.456310E+11 0.188607E+11 0.267703E+11 0.00 0.00
Minimum of Months 0.412505E+09 0.156975E+10 0.117468E+10 0.310323E+09 0.796514E+09 0.00 0.00
Maximum of Months 0.740060E+10 0.469793E+10 0.641070E+10 0.303312E+10 0.362136E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.434692E+10 0.668476E+10 0.504835E+10 0.299773E+10 0.205062E+10 0.00 0.00
February 0.691686E+10 0.558066E+10 0.701227E+10 0.434069E+10 0.267158E+10 0.00 0.00
March 0.866890E+10 0.544619E+10 0.835137E+10 0.445369E+10 0.389768E+10 0.00 0.00
April 0.940321E+10 0.443320E+10 0.853303E+10 0.370499E+10 0.482803E+10 0.00 0.00
May 0.899692E+10 0.378358E+10 0.806244E+10 0.240188E+10 0.566056E+10 0.00 0.00
June 0.815623E+10 0.287736E+10 0.713840E+10 0.191657E+10 0.522183E+10 0.00 0.00
July 0.101825E+11 0.268249E+10 0.804422E+10 0.294622E+10 0.509800E+10 0.00 0.00
August 0.113238E+11 0.260816E+10 0.864250E+10 0.403014E+10 0.461236E+10 0.00 0.00
September 0.113677E+11 0.354279E+10 0.926665E+10 0.511735E+10 0.414930E+10 0.00 0.00
October 0.965393E+10 0.481643E+10 0.867382E+10 0.535544E+10 0.331838E+10 0.00 0.00
November 0.458306E+10 0.558198E+10 0.496282E+10 0.284412E+10 0.211871E+10 0.00 0.00
December 0.512177E+10 0.693073E+10 0.536562E+10 0.347230E+10 0.189331E+10 0.00 0.00
               
Annual Sum or Average 0.987218E+11 0.549683E+11 0.891015E+11 0.435811E+11 0.455203E+11 0.00 0.00
Minimum of Months 0.434692E+10 0.260816E+10 0.496282E+10 0.191657E+10 0.189331E+10 0.00 0.00
Maximum of Months 0.113677E+11 0.693073E+10 0.926665E+10 0.535544E+10 0.566056E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.515883E+09 0.476422E+10 0.129101E+10 0.380696E+09 0.910317E+09 0.00 0.00
February 0.139016E+10 0.387541E+10 0.209068E+10 0.785738E+09 0.130495E+10 0.00 0.00
March 0.259564E+10 0.366271E+10 0.324347E+10 0.109476E+10 0.214871E+10 0.00 0.00
April 0.466743E+10 0.294791E+10 0.477540E+10 0.182582E+10 0.294958E+10 0.00 0.00
May 0.686935E+10 0.253935E+10 0.634966E+10 0.257952E+10 0.377014E+10 0.00 0.00
June 0.655379E+10 0.193546E+10 0.590965E+10 0.229452E+10 0.361513E+10 0.00 0.00
July 0.920705E+10 0.185637E+10 0.754391E+10 0.396547E+10 0.357845E+10 0.00 0.00
August 0.772883E+10 0.180785E+10 0.624062E+10 0.318664E+10 0.305398E+10 0.00 0.00
September 0.558438E+10 0.240800E+10 0.491810E+10 0.235981E+10 0.255829E+10 0.00 0.00
October 0.257632E+10 0.327480E+10 0.289322E+10 0.117885E+10 0.171437E+10 0.00 0.00
November 0.713175E+09 0.387472E+10 0.139433E+10 0.393258E+09 0.100107E+10 0.00 0.00
December 0.619316E+09 0.489607E+10 0.121128E+10 0.415073E+09 0.796202E+09 0.00 0.00
               
Annual Sum or Average 0.490213E+11 0.378429E+11 0.478613E+11 0.204602E+11 0.274012E+11 0.00 0.00
Minimum of Months 0.515883E+09 0.180785E+10 0.121128E+10 0.380696E+09 0.796202E+09 0.00 0.00
Maximum of Months 0.920705E+10 0.489607E+10 0.754391E+10 0.396547E+10 0.377014E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 55170184.89 0.664188E+10 0.114260E+10 0.00 0.114260E+10 0.00 0.00
February 0.353837E+09 0.531606E+10 0.160585E+10 0.00 0.160585E+10 0.00 0.00
March 0.115520E+10 0.488870E+10 0.261947E+10 0.00 0.261947E+10 0.00 0.00
April 0.236437E+10 0.386017E+10 0.358724E+10 12725040.77 0.357452E+10 0.00 0.00
May 0.387363E+10 0.327537E+10 0.476974E+10 0.141702E+09 0.462804E+10 0.00 0.00
June 0.431581E+10 0.248343E+10 0.485348E+10 0.320504E+09 0.453298E+10 0.00 0.00
July 0.480115E+10 0.231311E+10 0.476673E+10 0.373735E+09 0.439300E+10 0.00 0.00
August 0.396824E+10 0.225334E+10 0.385871E+10 0.104312E+09 0.375439E+10 0.00 0.00
September 0.225287E+10 0.316044E+10 0.290062E+10 855348.19 0.289976E+10 0.00 0.00
October 0.100691E+10 0.424703E+10 0.205365E+10 0.00 0.205365E+10 0.00 0.00
November 0.208048E+09 0.512910E+10 0.125187E+10 0.00 0.125187E+10 0.00 0.00
December 34418847.21 0.661908E+10 0.970912E+09 0.00 0.970912E+09 0.00 0.00
               
Annual Sum or Average 0.243896E+11 0.501877E+11 0.343809E+11 0.953833E+09 0.334270E+11 0.00 0.00
Minimum of Months 34418847.21 0.225334E+10 0.970912E+09 0.00 0.970912E+09 0.00 0.00
Maximum of Months 0.480115E+10 0.664188E+10 0.485348E+10 0.373735E+09 0.462804E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.455295E+09 0.421766E+10 0.122399E+10 0.310323E+09 0.913670E+09 0.00 0.00
February 0.134109E+10 0.338568E+10 0.202856E+10 0.719979E+09 0.130858E+10 0.00 0.00
March 0.277286E+10 0.318136E+10 0.335330E+10 0.121392E+10 0.213937E+10 0.00 0.00
April 0.503424E+10 0.254105E+10 0.503050E+10 0.209025E+10 0.294025E+10 0.00 0.00
May 0.581084E+10 0.223845E+10 0.553133E+10 0.192312E+10 0.360821E+10 0.00 0.00
June 0.722519E+10 0.172897E+10 0.641070E+10 0.278934E+10 0.362136E+10 0.00 0.00
July 0.727287E+10 0.157572E+10 0.616885E+10 0.276893E+10 0.339991E+10 0.00 0.00
August 0.740398E+10 0.153684E+10 0.606311E+10 0.303312E+10 0.303000E+10 0.00 0.00
September 0.472874E+10 0.208171E+10 0.433818E+10 0.200081E+10 0.233737E+10 0.00 0.00
October 0.266534E+10 0.279317E+10 0.292187E+10 0.124152E+10 0.168035E+10 0.00 0.00
November 0.756558E+09 0.332353E+10 0.138594E+10 0.391265E+09 0.994677E+09 0.00 0.00
December 0.572161E+09 0.425200E+10 0.117468E+10 0.378163E+09 0.796514E+09 0.00 0.00
               
Annual Sum or Average 0.460392E+11 0.328561E+11 0.456310E+11 0.188607E+11 0.267703E+11 0.00 0.00
Minimum of Months 0.455295E+09 0.153684E+10 0.117468E+10 0.310323E+09 0.796514E+09 0.00 0.00
Maximum of Months 0.740398E+10 0.425200E+10 0.641070E+10 0.303312E+10 0.362136E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.446599E+10 0.613188E+10 0.504835E+10 0.299773E+10 0.205062E+10 0.00 0.00
February 0.706477E+10 0.510742E+10 0.701227E+10 0.434069E+10 0.267158E+10 0.00 0.00
March 0.877433E+10 0.501689E+10 0.835137E+10 0.445369E+10 0.389768E+10 0.00 0.00
April 0.947051E+10 0.418556E+10 0.853303E+10 0.370499E+10 0.482803E+10 0.00 0.00
May 0.902662E+10 0.362010E+10 0.806244E+10 0.240188E+10 0.566056E+10 0.00 0.00
June 0.814202E+10 0.280089E+10 0.713840E+10 0.191657E+10 0.522183E+10 0.00 0.00
July 0.101504E+11 0.263486E+10 0.804422E+10 0.294622E+10 0.509800E+10 0.00 0.00
August 0.112982E+11 0.255151E+10 0.864250E+10 0.403014E+10 0.461236E+10 0.00 0.00
September 0.113996E+11 0.337413E+10 0.926665E+10 0.511735E+10 0.414930E+10 0.00 0.00
October 0.975683E+10 0.442565E+10 0.867382E+10 0.535544E+10 0.331838E+10 0.00 0.00
November 0.471520E+10 0.501646E+10 0.496282E+10 0.284412E+10 0.211871E+10 0.00 0.00
December 0.523903E+10 0.630014E+10 0.536562E+10 0.347230E+10 0.189331E+10 0.00 0.00
               
Annual Sum or Average 0.995035E+11 0.511655E+11 0.891015E+11 0.435811E+11 0.455203E+11 0.00 0.00
Minimum of Months 0.446599E+10 0.255151E+10 0.496282E+10 0.191657E+10 0.189331E+10 0.00 0.00
Maximum of Months 0.113996E+11 0.630014E+10 0.926665E+10 0.535544E+10 0.566056E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.546738E+09 0.439998E+10 0.129101E+10 0.380696E+09 0.910317E+09 0.00 0.00
February 0.144474E+10 0.358120E+10 0.209068E+10 0.785738E+09 0.130495E+10 0.00 0.00
March 0.266166E+10 0.339607E+10 0.324347E+10 0.109476E+10 0.214871E+10 0.00 0.00
April 0.471208E+10 0.279419E+10 0.477540E+10 0.182582E+10 0.294958E+10 0.00 0.00
May 0.687918E+10 0.244203E+10 0.634966E+10 0.257952E+10 0.377014E+10 0.00 0.00
June 0.653596E+10 0.188766E+10 0.590965E+10 0.229452E+10 0.361513E+10 0.00 0.00
July 0.917493E+10 0.182393E+10 0.754391E+10 0.396547E+10 0.357845E+10 0.00 0.00
August 0.770618E+10 0.177172E+10 0.624062E+10 0.318664E+10 0.305398E+10 0.00 0.00
September 0.559913E+10 0.230274E+10 0.491810E+10 0.235981E+10 0.255829E+10 0.00 0.00
October 0.263914E+10 0.302046E+10 0.289322E+10 0.117885E+10 0.171437E+10 0.00 0.00
November 0.760892E+09 0.352200E+10 0.139433E+10 0.393258E+09 0.100107E+10 0.00 0.00
December 0.648963E+09 0.450714E+10 0.121128E+10 0.415073E+09 0.796202E+09 0.00 0.00
               
Annual Sum or Average 0.493096E+11 0.354491E+11 0.478613E+11 0.204602E+11 0.274012E+11 0.00 0.00
Minimum of Months 0.546738E+09 0.177172E+10 0.121128E+10 0.380696E+09 0.796202E+09 0.00 0.00
Maximum of Months 0.917493E+10 0.450714E+10 0.754391E+10 0.396547E+10 0.377014E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.390572E+11 -0.386122E+11 0.00 0.00 744.00 0.00 -444988680.5 60.05 0.00 0.00
February 0.357278E+11 -0.353262E+11 0.00 0.00 672.00 0.00 -401598665.0 60.05 0.00 0.00
March 0.415409E+11 -0.410963E+11 0.00 0.00 744.00 0.00 -444580974.8 60.05 0.00 0.00
April 0.366859E+11 -0.362576E+11 0.00 0.00 720.00 0.00 -428329567.5 60.05 0.00 0.00
May 0.377491E+11 -0.373060E+11 0.00 0.00 744.00 0.00 -443097607.1 60.05 0.00 0.00
June 0.360474E+11 -0.356186E+11 0.00 0.00 720.00 0.00 -428741640.9 60.05 0.00 0.00
July 0.333860E+11 -0.329455E+11 0.00 0.00 744.00 0.00 -440537883.2 60.05 0.00 0.00
August 0.362146E+11 -0.357723E+11 0.00 0.00 744.00 0.00 -442296893.5 60.05 0.00 0.00
September 0.333052E+11 -0.328780E+11 0.00 0.00 720.00 0.00 -427243879.2 60.05 0.00 0.00
October 0.354159E+11 -0.349745E+11 0.00 0.00 744.00 0.00 -441336177.6 60.05 0.00 0.00
November 0.360882E+11 -0.356606E+11 0.00 0.00 720.00 0.00 -427648144.9 60.05 0.00 0.00
December 0.372213E+11 -0.367784E+11 0.00 0.00 744.00 0.00 -442829617.1 60.05 0.00 0.00
                     
Annual Sum or Average 0.438439E+12 -0.433226E+12 0.00 0.00 8760.00 0.00 -0.521323E+10 60.05 0.00 0.00
Minimum of Months 0.333052E+11 -0.410963E+11 0.00 0.00 672.00 0.00 -444988680.5 60.05 0.00 0.00
Maximum of Months 0.415409E+11 -0.328780E+11 0.00 0.00 744.00 0.00 -401598665.0 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.50 0.48 01-JAN-09:39 2756.62 32.57 224.33 219.67 2173.73 33.68 226.67 187.33
February 259.50 0.50 0.48 01-FEB-08:30 4688.14 33.54 245.83 244.00 2034.17 29.26 224.33 218.83
March 247.00 0.50 0.48 01-MAR-07:30 7763.86 33.51 209.67 313.00 1660.48 22.71 204.00 267.83
April 379.50 0.51 0.48 01-APR-06:00 2218.16 20.35 170.67 345.33 1212.63 21.77 250.00 308.17
May 427.83 0.51 0.48 01-MAY-07:10 2038.95 20.20 160.83 386.00 1100.56 21.58 278.17 344.17
June 375.17 0.51 0.48 01-JUN-05:00 1789.61 19.74 112.33 396.33 1017.01 21.15 265.83 346.17
July 471.00 0.53 0.48 01-JUL-05:30 1590.99 18.58 117.17 395.50 923.34 19.97 191.67 340.83
August 366.67 0.51 0.48 01-AUG-05:00 1879.74 19.63 117.00 374.50 1111.35 21.04 209.17 328.33
September 301.17 0.50 0.48 01-SEP-07:40 3010.85 22.37 143.67 320.17 1461.86 22.54 226.00 288.17
October 245.33 0.51 0.48 01-OCT-07:49 7206.81 34.96 224.33 285.00 1937.98 23.90 187.17 256.17
November 242.67 0.50 0.48 01-NOV-08:09 3072.27 32.12 226.83 225.17 2440.53 33.30 230.50 193.67
December 160.33 0.50 0.48 01-DEC-09:39 3700.35 35.79 149.50 207.33 3110.51 37.05 149.67 167.00
                         
Annual Sum or Average 3714.00 0.51     3130.76 25.12 2102.17 3712.00 1512.29 24.35 2643.17 3246.67
Minimum of Months 160.33 0.50 0.48   1590.99 18.58 112.33 207.33 923.34 19.97 149.67 167.00
Maximum of Months 471.00 0.53 0.48   7763.86 35.79 245.83 396.33 3110.51 37.05 278.17 346.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-09:50 933.44 21.20 70.33 200.50 572.67 22.53 94.00 132.00
February 259.50 0.51 0.48 01-FEB-08:30 1524.18 23.19 98.50 228.67 793.55 23.33 136.00 181.83
March 247.00 0.51 0.48 01-MAR-07:30 2743.39 25.62 117.17 304.17 1198.53 24.50 158.50 255.83
April 379.50 0.50 0.48 01-APR-06:19 2863.42 24.33 148.33 347.83 1592.66 24.70 229.17 308.50
May 427.83 0.50 0.48 01-MAY-06:00 2943.71 23.64 160.67 391.50 1283.58 23.41 248.00 351.83
June 375.17 0.51 0.48 01-JUN-05:10 3095.30 23.54 107.33 404.17 1694.29 23.99 208.33 359.00
July 471.00 0.52 0.48 01-JUL-04:00 2908.98 23.76 170.33 410.83 1315.22 23.34 221.17 373.33
August 366.67 0.51 0.48 01-AUG-05:30 3385.51 24.42 127.50 379.50 1472.71 23.72 177.50 340.33
September 301.17 0.50 0.48 01-SEP-07:40 2778.60 24.19 99.33 323.83 1541.04 24.53 163.67 286.33
October 245.33 0.52 0.48 01-OCT-07:40 2516.40 25.23 108.83 272.00 1100.58 24.04 139.33 227.00
November 242.67 0.52 0.48 01-NOV-07:00 1158.69 22.44 87.83 208.33 601.01 22.59 93.33 146.83
December 160.33 0.52 0.48 01-DEC-09:39 1093.97 23.41 64.83 185.83 586.52 23.34 71.50 107.67
                         
Annual Sum or Average 3714.00 0.51     2510.69 23.80 1361.00 3657.17 1228.01 23.71 1940.50 3070.50
Minimum of Months 160.33 0.50 0.48   933.44 21.20 64.83 185.83 572.67 22.53 71.50 107.67
Maximum of Months 471.00 0.52 0.48   3385.51 25.62 170.33 410.83 1694.29 24.70 248.00 373.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.55 0.48 02-JAN-10:50 506.54 16.03 0.00 179.67 275.32 17.36 0.00 53.67
February 259.50 0.53 0.48 01-FEB-09:20 644.35 17.21 0.00 215.50 363.52 18.62 1.50 131.67
March 247.00 0.51 0.48 01-MAR-08:09 870.97 18.63 0.00 298.67 514.77 20.08 68.17 217.67
April 379.50 0.50 0.48 01-APR-07:10 1020.91 19.31 0.50 349.00 590.14 20.65 162.00 302.00
May 427.83 0.50 0.48 01-MAY-07:10 1253.28 21.40 93.50 399.67 717.49 22.13 273.67 365.33
June 375.17 0.50 0.48 01-JUN-05:19 1332.20 22.47 125.83 413.83 756.05 22.46 261.67 380.50
July 471.00 0.51 0.48 01-JUL-04:00 1124.24 21.62 126.83 423.50 645.66 21.55 230.67 378.00
August 366.67 0.50 0.48 01-AUG-05:49 976.04 19.35 15.33 388.83 608.15 20.70 131.33 345.50
September 301.17 0.50 0.48 01-SEP-07:40 948.85 19.41 0.00 314.17 574.27 20.84 101.33 256.83
October 245.33 0.53 0.48 01-OCT-08:09 707.02 17.69 0.00 260.67 426.98 19.21 13.17 170.67
November 242.67 0.54 0.48 01-NOV-09:00 545.83 16.34 0.00 193.17 296.72 17.63 0.17 69.17
December 160.33 0.56 0.48 01-DEC-09:00 475.05 16.03 0.00 155.33 276.36 17.62 0.00 40.83
                         
Annual Sum or Average 3714.00 0.51     937.39 19.33 362.00 3592.00 544.60 20.32 1243.67 2711.83
Minimum of Months 160.33 0.50 0.48   475.05 16.03 0.00 155.33 275.32 17.36 0.00 40.83
Maximum of Months 471.00 0.56 0.48   1332.20 22.47 126.83 423.50 756.05 22.46 273.67 380.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-10:30 1062.71 22.55 87.33 201.83 564.79 22.66 94.67 138.50
February 259.50 0.51 0.48 01-FEB-09:20 1509.03 23.16 95.00 232.17 773.63 23.23 126.17 184.33
March 247.00 0.50 0.48 01-MAR-08:09 2398.88 24.40 112.33 306.67 1279.64 24.59 152.17 253.50
April 379.50 0.50 0.48 01-APR-07:30 2867.28 23.20 133.67 345.83 1250.08 22.64 208.17 308.67
May 427.83 0.50 0.48 01-MAY-07:19 2973.53 20.76 88.17 392.67 1589.77 20.96 222.83 357.17
June 375.17 0.51 0.48 01-JUN-06:10 3033.87 20.34 51.83 403.50 1367.81 20.72 188.83 363.17
July 471.00 0.52 0.48 01-JUL-05:00 3326.90 19.59 75.50 405.00 1457.75 19.65 156.50 363.83
August 366.67 0.50 0.48 01-AUG-06:19 3174.65 22.00 92.83 383.83 1823.04 22.69 160.50 345.67
September 301.17 0.50 0.48 01-SEP-07:49 3510.48 25.44 124.67 316.50 1949.38 25.50 180.33 273.83
October 245.33 0.51 0.48 01-OCT-08:20 2420.89 25.91 116.33 274.50 1075.29 24.69 153.17 228.00
November 242.67 0.52 0.48 01-NOV-09:39 1128.96 22.03 79.17 210.17 588.37 22.11 91.33 142.83
December 160.33 0.53 0.48 01-DEC-09:00 1115.30 22.55 55.67 185.83 590.02 22.54 66.00 103.50
                         
Annual Sum or Average 3714.00 0.51     2576.83 22.35 1112.50 3658.50 1282.23 22.38 1800.67 3063.00
Minimum of Months 160.33 0.50 0.48   1062.71 19.59 51.83 185.83 564.79 19.65 66.00 103.50
Maximum of Months 471.00 0.53 0.48   3510.48 25.91 133.67 405.00 1949.38 25.50 222.83 363.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.50 0.48 01-JAN-09:39 2760.85 31.99 220.33 219.67 2235.21 33.12 221.33 190.33
February 259.50 0.50 0.48 01-FEB-08:30 4711.16 32.96 238.83 244.50 2126.80 27.47 156.50 223.17
March 247.00 0.50 0.48 01-MAR-07:30 7803.57 32.30 208.50 313.00 1771.56 17.99 8.50 272.00
April 379.50 0.50 0.48 01-APR-06:00 2248.24 13.83 0.00 345.67 1295.51 17.29 0.67 312.00
May 427.83 0.50 0.48 01-MAY-07:10 2063.76 13.83 0.00 386.33 1173.44 17.24 0.00 349.50
June 375.17 0.51 0.48 01-JUN-05:49 1820.97 13.70 0.00 396.50 1086.63 17.11 0.00 351.50
July 471.00 0.53 0.48 01-JUL-05:19 1623.42 12.32 0.00 396.33 988.91 15.77 0.00 348.00
August 366.67 0.51 0.48 01-AUG-05:00 1922.77 13.42 0.00 374.67 1193.48 16.94 1.33 333.00
September 301.17 0.50 0.48 01-SEP-07:40 3057.54 16.44 27.00 320.33 1567.48 18.15 11.17 291.83
October 245.33 0.50 0.48 01-OCT-07:49 7248.74 34.05 220.33 285.00 2048.55 19.37 26.17 258.67
November 242.67 0.50 0.48 01-NOV-07:00 3084.69 31.49 221.67 225.50 2503.98 32.76 226.17 197.00
December 160.33 0.50 0.48 01-DEC-09:39 3717.24 34.96 149.17 207.67 3198.07 36.43 149.67 171.00
                         
Annual Sum or Average 3714.00 0.51     3160.84 20.93 1285.83 3715.17 1594.20 20.86 801.50 3298.00
Minimum of Months 160.33 0.50 0.48   1623.42 12.32 0.00 207.67 988.91 15.77 0.00 171.00
Maximum of Months 471.00 0.53 0.48   7803.57 34.96 238.83 396.50 3198.07 36.43 226.17 351.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-09:50 949.57 18.35 61.33 202.17 596.49 20.65 71.33 137.83
February 259.50 0.51 0.48 01-FEB-08:30 1550.38 20.50 81.17 230.17 829.80 21.28 61.67 188.17
March 247.00 0.50 0.48 01-MAR-07:30 2791.73 23.13 91.50 304.67 1257.06 22.33 51.50 260.50
April 379.50 0.50 0.48 01-APR-06:19 2913.28 21.51 118.33 348.83 1657.09 22.52 91.67 313.50
May 427.83 0.50 0.48 01-MAY-06:00 2986.18 20.40 132.67 392.83 1348.11 20.93 79.50 356.50
June 375.17 0.51 0.48 01-JUN-04:00 3145.62 20.40 98.83 405.33 1772.28 21.56 73.67 364.17
July 471.00 0.52 0.48 01-JUL-04:00 2950.12 20.05 148.50 411.00 1380.03 20.90 99.33 379.17
August 366.67 0.51 0.48 01-AUG-05:30 3440.35 21.54 116.33 380.50 1545.34 21.19 66.50 345.33
September 301.17 0.50 0.48 01-SEP-07:40 2832.24 21.34 84.33 324.17 1604.96 22.31 61.50 290.00
October 245.33 0.52 0.48 01-OCT-07:40 2556.25 22.88 93.33 273.17 1152.05 22.00 58.00 232.00
November 242.67 0.52 0.48 01-NOV-07:00 1177.86 19.78 78.83 210.17 627.75 20.54 62.83 154.33
December 160.33 0.52 0.48 01-DEC-09:39 1112.43 21.01 56.33 186.67 613.49 21.60 52.67 114.17
                         
Annual Sum or Average 3714.00 0.51     2551.51 20.86 1161.50 3669.67 1284.74 21.46 830.17 3135.67
Minimum of Months 160.33 0.50 0.48   949.57 18.35 56.33 186.67 596.49 20.54 51.50 114.17
Maximum of Months 471.00 0.52 0.48   3440.35 23.13 148.50 411.00 1772.28 22.52 99.33 379.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.54 0.48 02-JAN-10:39 511.49 9.50 0.00 180.00 292.01 12.98 0.00 67.50
February 259.50 0.52 0.48 01-FEB-09:09 652.10 11.06 0.00 216.33 386.04 14.56 0.00 142.17
March 247.00 0.51 0.48 01-MAR-08:09 884.58 12.96 0.00 298.83 547.55 16.43 0.00 228.83
April 379.50 0.50 0.48 01-APR-07:10 1037.32 13.66 0.00 349.00 628.06 17.06 0.00 309.67
May 427.83 0.50 0.48 01-MAY-07:10 1289.72 16.17 39.00 399.67 767.94 19.32 44.67 371.00
June 375.17 0.50 0.48 01-JUN-05:19 1357.26 17.80 60.17 414.17 830.52 20.87 62.00 388.33
July 471.00 0.51 0.48 01-JUL-04:00 1151.12 16.75 78.00 424.00 717.63 19.88 80.00 389.33
August 366.67 0.50 0.48 01-AUG-05:49 1017.74 13.88 0.00 391.83 648.60 17.44 0.50 354.00
September 301.17 0.50 0.48 01-SEP-07:40 964.69 14.15 0.00 314.83 611.52 17.60 0.00 264.83
October 245.33 0.53 0.48 01-OCT-08:09 717.51 12.07 0.00 261.67 454.17 15.60 0.00 186.50
November 242.67 0.54 0.48 01-NOV-08:30 551.46 9.86 0.00 193.33 314.81 13.29 0.00 83.00
December 160.33 0.56 0.48 01-DEC-09:00 479.56 9.78 0.00 156.00 293.19 13.49 0.00 51.00
                         
Annual Sum or Average 3714.00 0.51     957.63 13.81 177.17 3599.67 586.48 17.17 187.17 2836.17
Minimum of Months 160.33 0.50 0.48   479.56 9.50 0.00 156.00 292.01 12.98 0.00 51.00
Maximum of Months 471.00 0.56 0.48   1357.26 17.80 78.00 424.00 830.52 20.87 80.00 389.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-10:20 1080.07 19.99 79.17 203.67 589.73 20.70 64.17 145.17
February 259.50 0.51 0.48 01-FEB-09:20 1524.12 19.33 66.50 232.17 810.96 21.15 59.67 190.00
March 247.00 0.50 0.48 01-MAR-08:09 2436.52 21.61 78.17 307.50 1335.36 22.54 59.83 258.00
April 379.50 0.50 0.48 01-APR-07:19 2915.14 20.19 105.33 346.50 1311.99 20.01 51.00 313.17
May 427.83 0.50 0.48 01-MAY-07:19 3009.64 16.83 52.17 392.83 1660.94 17.67 0.00 360.83
June 375.17 0.50 0.48 01-JUN-05:00 3080.87 16.45 42.83 404.00 1439.81 17.45 0.00 367.33
July 471.00 0.52 0.48 01-JUL-05:49 3375.83 15.57 58.83 406.33 1533.28 16.25 3.67 367.50
August 366.67 0.50 0.48 01-AUG-06:10 3208.24 18.52 75.83 384.00 1900.01 19.93 50.17 350.17
September 301.17 0.50 0.48 01-SEP-07:40 3546.00 22.41 100.50 316.67 2024.72 23.30 76.83 279.67
October 245.33 0.51 0.48 01-OCT-08:20 2431.61 22.21 89.83 275.00 1127.09 22.70 64.50 232.33
November 242.67 0.52 0.48 01-NOV-08:30 1148.08 19.30 70.50 211.50 615.39 20.00 52.17 149.50
December 160.33 0.53 0.48 01-DEC-09:50 1133.58 19.89 48.67 186.50 616.83 20.65 45.33 110.83
                         
Annual Sum or Average 3714.00 0.51     2610.44 18.94 868.33 3666.67 1341.57 19.76 527.33 3124.50
Minimum of Months 160.33 0.50 0.48   1080.07 15.57 42.83 186.50 589.73 16.25 0.00 110.83
Maximum of Months 471.00 0.53 0.48   3546.00 22.41 105.33 406.33 2024.72 23.30 76.83 367.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.50 0.48 01-JAN-09:39 2762.01 31.99 220.33 219.67 2236.67 33.12 221.33 190.33
February 259.50 0.50 0.48 01-FEB-08:30 4712.94 32.95 238.83 244.50 2128.86 27.46 156.50 223.17
March 247.00 0.50 0.48 01-MAR-07:30 7806.60 32.29 208.50 313.33 1774.13 17.97 8.50 272.17
April 379.50 0.50 0.48 01-APR-06:00 2251.62 13.80 0.00 345.67 1297.60 17.28 0.67 312.50
May 427.83 0.50 0.48 01-MAY-07:10 2067.02 13.80 0.00 386.83 1175.35 17.23 0.00 349.67
June 375.17 0.51 0.48 01-JUN-05:49 1823.49 13.67 0.00 396.67 1088.20 17.10 0.00 351.83
July 471.00 0.53 0.48 01-JUL-05:19 1625.64 12.29 0.00 396.33 990.27 15.75 0.00 348.17
August 366.67 0.51 0.48 01-AUG-05:00 1925.22 13.39 0.00 374.83 1195.06 16.93 1.33 333.00
September 301.17 0.50 0.48 01-SEP-07:40 3060.64 16.42 27.00 320.33 1569.76 18.13 11.00 291.83
October 245.33 0.50 0.48 01-OCT-07:49 7250.69 34.04 220.33 285.00 2050.89 19.36 26.17 258.83
November 242.67 0.50 0.48 01-NOV-07:00 3085.97 31.49 221.50 225.50 2505.63 32.76 226.17 197.33
December 160.33 0.50 0.48 01-DEC-09:39 3717.99 34.95 149.17 207.83 3199.53 36.42 149.67 171.17
                         
Annual Sum or Average 3714.00 0.51     3163.23 20.90 1285.67 3716.50 1596.04 20.84 801.33 3300.00
Minimum of Months 160.33 0.50 0.48   1625.64 12.29 0.00 207.83 990.27 15.75 0.00 171.17
Maximum of Months 471.00 0.53 0.48   7806.60 34.95 238.83 396.67 3199.53 36.42 226.17 351.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-09:50 950.55 18.33 61.33 202.33 597.30 20.64 71.33 138.33
February 259.50 0.51 0.48 01-FEB-08:30 1551.59 20.47 81.00 230.33 830.85 21.26 61.50 188.17
March 247.00 0.50 0.48 01-MAR-07:30 2793.39 23.10 91.50 304.67 1258.52 22.32 51.33 260.83
April 379.50 0.50 0.48 01-APR-06:19 2890.27 20.41 105.17 348.50 1658.69 22.50 91.67 313.67
May 427.83 0.50 0.48 01-MAY-06:00 2988.57 20.37 132.50 393.17 1349.81 20.92 79.50 356.83
June 375.17 0.51 0.48 01-JUN-04:00 3147.66 20.37 98.83 405.33 1773.97 21.55 73.67 364.17
July 471.00 0.52 0.48 01-JUL-04:00 2951.80 20.03 148.50 411.00 1381.35 20.89 99.33 379.33
August 366.67 0.51 0.48 01-AUG-05:30 3441.77 21.51 116.33 380.50 1546.74 21.17 66.50 345.33
September 301.17 0.50 0.48 01-SEP-07:40 2829.19 21.11 82.67 324.00 1606.36 22.30 61.33 290.17
October 245.33 0.52 0.48 01-OCT-07:40 2517.97 21.42 83.00 273.33 1153.20 21.99 57.67 232.17
November 242.67 0.52 0.48 01-NOV-07:00 1178.93 19.76 78.83 210.17 628.62 20.53 62.67 154.83
December 160.33 0.52 0.48 01-DEC-09:39 1113.15 20.99 56.33 186.67 614.26 21.59 52.50 114.17
                         
Annual Sum or Average 3714.00 0.51     2547.57 20.62 1136.00 3670.00 1286.08 21.45 829.00 3138.00
Minimum of Months 160.33 0.50 0.48   950.55 18.33 56.33 186.67 597.30 20.53 51.33 114.17
Maximum of Months 471.00 0.52 0.48   3441.77 23.10 148.50 411.00 1773.97 22.50 99.33 379.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.54 0.48 02-JAN-10:39 512.19 9.47 0.00 180.33 292.50 12.97 0.00 68.00
February 259.50 0.52 0.48 01-FEB-09:09 652.89 11.03 0.00 216.33 386.64 14.54 0.00 142.67
March 247.00 0.51 0.48 01-MAR-08:09 885.47 12.92 0.00 298.83 548.30 16.42 0.00 229.17
April 379.50 0.50 0.48 01-APR-07:10 1038.47 13.63 0.00 349.00 628.96 17.05 0.00 310.00
May 427.83 0.50 0.48 01-MAY-07:10 1291.25 16.14 39.00 400.00 769.05 19.30 44.50 371.00
June 375.17 0.50 0.48 01-JUN-05:19 1358.51 17.77 60.17 414.17 831.56 20.86 62.00 388.33
July 471.00 0.51 0.48 01-JUL-04:00 1152.22 16.73 78.00 424.00 718.51 19.86 79.83 389.33
August 366.67 0.50 0.48 01-AUG-05:49 1018.58 13.85 0.00 391.83 649.37 17.42 0.50 354.00
September 301.17 0.50 0.48 01-SEP-07:40 965.55 14.12 0.00 314.83 612.31 17.59 0.00 265.33
October 245.33 0.53 0.48 01-OCT-08:09 718.14 12.04 0.00 262.00 454.76 15.59 0.00 186.83
November 242.67 0.54 0.48 01-NOV-08:30 552.22 9.84 0.00 193.33 315.34 13.28 0.00 83.33
December 160.33 0.56 0.48 01-DEC-09:00 480.01 9.75 0.00 156.17 293.61 13.47 0.00 51.33
                         
Annual Sum or Average 3714.00 0.51     958.61 13.78 177.17 3600.83 587.27 17.16 186.83 2839.33
Minimum of Months 160.33 0.50 0.48   480.01 9.47 0.00 156.17 292.50 12.97 0.00 51.33
Maximum of Months 471.00 0.56 0.48   1358.51 17.77 78.00 424.00 831.56 20.86 79.83 389.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-10:20 1081.04 19.97 79.17 203.83 590.53 20.69 63.83 145.33
February 259.50 0.51 0.48 01-FEB-09:20 1525.32 19.31 66.50 232.33 812.01 21.14 59.33 190.33
March 247.00 0.50 0.48 01-MAR-08:09 2438.13 21.58 78.17 307.67 1336.84 22.53 59.67 258.67
April 379.50 0.50 0.48 01-APR-07:19 2917.08 20.16 105.33 346.50 1313.60 19.99 51.00 313.17
May 427.83 0.50 0.48 01-MAY-07:19 3012.06 16.80 52.17 392.83 1662.78 17.65 0.00 361.17
June 375.17 0.50 0.48 01-JUN-05:00 3082.91 16.42 42.83 404.00 1441.48 17.44 0.00 367.50
July 471.00 0.52 0.48 01-JUL-05:40 3377.59 15.54 58.83 406.33 1534.72 16.23 3.67 367.67
August 366.67 0.50 0.48 01-AUG-06:10 3209.68 18.49 75.83 384.00 1901.43 19.92 50.17 350.50
September 301.17 0.50 0.48 01-SEP-07:40 3547.73 22.38 100.50 316.67 2026.45 23.29 76.83 280.00
October 245.33 0.51 0.48 01-OCT-08:20 2432.72 22.19 89.83 275.00 1128.29 22.69 64.50 232.33
November 242.67 0.52 0.48 01-NOV-08:30 1149.15 19.27 70.50 211.50 616.26 19.99 52.00 150.00
December 160.33 0.53 0.48 01-DEC-09:50 1134.27 19.87 48.67 186.67 617.59 20.63 45.17 111.00
                         
Annual Sum or Average 3714.00 0.51     2612.06 18.91 868.33 3667.33 1342.97 19.75 526.17 3127.67
Minimum of Months 160.33 0.50 0.48   1081.04 15.54 42.83 186.67 590.53 16.23 0.00 111.00
Maximum of Months 471.00 0.53 0.48   3547.73 22.38 105.33 406.33 2026.45 23.29 76.83 367.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.103357E+11 28225.93 06-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.608426E+10 23820.76 18-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.155890E+10 21092.70 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.433108E+09 14778.24 19-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.205463E+09 8650.22 18-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 2373.51 0.85 12-JUN-14:30 0.00 0.00 0.00 0.00 0.00
July 1879.58 1.93 27-JUL-13:10 0.00 0.00 0.00 0.00 0.00
August 1101.32 0.85 05-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 16896838.74 3013.57 28-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.236335E+09 6648.84 13-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.259644E+10 18681.03 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.553117E+10 25120.54 26-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.269983E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1101.32 0.85   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103357E+11 28225.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 21094641.39 1808.89 09-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 443845.34 184.85 18-FEB-07:07 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 21538486.72     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 21094641.39 1808.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 32346246.55 4069.88 09-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 5606500.52 1727.94 18-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 113718.96 101.15 22-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 38066466.03     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 32346246.55 4069.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161586E+09 15934.19 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 39190869.33 15953.62 21-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2753382.91 963.76 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 26266208.69 15975.81 26-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.229796E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.161586E+09 15975.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152241E+12 292365.51 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.941387E+11 249384.61 18-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.433724E+11 317081.41 29-MAR-13:20 0.00 0.00 0.00 0.00 0.00
April 0.205646E+11 287089.62 18-APR-11:30 0.00 0.00 0.00 0.00 0.00
May 0.538729E+10 251527.87 17-MAY-13:10 0.00 0.00 0.00 0.00 0.00
June 0.261183E+09 171157.19 13-JUN-09:20 0.00 0.00 0.00 0.00 0.00
July 69717979.03 109826.31 12-JUL-09:20 0.00 0.00 0.00 0.00 0.00
August 58466055.14 126548.93 03-AUG-09:05 0.00 0.00 0.00 0.00 0.00
September 0.894890E+09 208505.27 27-SEP-09:20 0.00 0.00 0.00 0.00 0.00
October 0.902572E+10 179073.62 18-OCT-11:20 0.00 0.00 0.00 0.00 0.00
November 0.659131E+11 203718.23 13-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.122686E+12 266808.03 26-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.514613E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 58466055.14 109826.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152241E+12 317081.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.370785E+10 431536.37 02-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 54448169.06 127135.77 26-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376230E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.370785E+10 431536.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.240713E+11 112990.41 02-JAN-05:53 0.00 0.00 0.00 0.00 0.00
February 0.105698E+11 112323.92 22-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.221347E+10 121794.62 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.327613E+09 68958.17 19-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.514407E+09 111357.16 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.569897E+10 112298.32 13-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.167590E+11 112306.75 26-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.601546E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.240713E+11 121794.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.137966E+11 153280.80 02-JAN-05:14 0.00 0.00 0.00 0.00 0.00
February 0.540524E+10 153233.10 21-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.997289E+09 152930.51 06-MAR-05:11 0.00 0.00 0.00 0.00 0.00
April 0.150248E+09 41215.04 19-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.315496E+09 52560.59 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.335874E+10 153035.13 27-NOV-05:11 0.00 0.00 0.00 0.00 0.00
December 0.976595E+10 153185.15 18-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.337896E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137966E+11 153280.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.148832E+11 220886.59 02-JAN-05:14 0.00 0.00 0.00 0.00 0.00
February 0.508085E+10 220037.56 22-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.882059E+09 220053.88 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.177818E+09 37038.71 18-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.183305E+09 33534.31 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.326366E+10 220169.24 28-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.108421E+11 220745.93 18-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.353130E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148832E+11 220886.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.979694E+10 148138.47 02-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.342043E+10 147799.66 22-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.431136E+09 143489.95 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 27220877.89 9426.34 19-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 55308249.41 5536.59 31-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.177211E+10 147779.12 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.579761E+10 148115.70 26-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213008E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.979694E+10 148138.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.171688E+11 33383.46 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.114209E+11 29892.42 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.636860E+10 23917.52 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.290419E+10 19046.65 19-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.851915E+09 12060.82 18-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 43596261.86 3967.26 15-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.153767E+09 6917.69 27-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.183487E+10 12401.30 16-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.861773E+10 24343.97 24-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.148368E+11 30786.01 26-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.642012E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171688E+11 33383.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.542142E+10 72917.00 23-JAN-05:24 0.00 0.00 0.00 0.00 0.00
February 0.228252E+10 72660.56 21-FEB-05:24 0.00 0.00 0.00 0.00 0.00
March 0.391510E+09 73192.37 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.162330E+09 54821.54 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.147030E+10 73225.39 27-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.348310E+10 73187.11 18-DEC-05:34 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.132112E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.542142E+10 73225.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.579583E+10 12653.35 30-JAN-05:54 0.00 0.00 0.00 0.00 0.00
February 0.354016E+10 12652.18 06-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.145765E+10 12651.06 06-MAR-05:54 0.00 0.00 0.00 0.00 0.00
April 0.458454E+09 12574.50 04-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 47515445.96 12504.45 18-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 369926.18 222.78 14-JUN-05:40 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 30410215.83 8253.78 27-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.713750E+09 12624.52 21-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.262008E+10 12677.10 27-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.497450E+10 12652.33 26-DEC-04:23 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.196387E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.579583E+10 12677.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.357249E+10 17614.40 18-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.195211E+10 17624.38 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.716516E+09 17621.23 06-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.198248E+09 17574.65 17-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 28131138.86 17572.23 18-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 956491.99 359.84 14-JUN-05:08 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 15430586.96 6801.65 27-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.379136E+09 17590.67 24-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.158157E+10 17617.70 27-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.304069E+10 17629.63 11-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114853E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.357249E+10 17629.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.408318E+10 26063.14 18-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.208457E+10 26078.14 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.912085E+09 26073.53 06-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.335023E+09 26005.03 17-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 48312532.17 26001.37 18-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 325501.08 174.60 14-JUN-06:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 23406920.06 5421.46 27-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.415426E+09 26003.92 16-OCT-04:12 0.00 0.00 0.00 0.00 0.00
November 0.184709E+10 26068.77 27-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.352175E+10 26085.93 11-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.132712E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.408318E+10 26085.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.261791E+10 17886.20 30-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.129289E+10 17865.67 06-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.471866E+09 17863.21 06-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.127215E+09 14579.92 01-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 12915375.67 13441.12 18-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 3325737.32 382.00 28-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.213010E+09 13820.81 23-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.100742E+10 17885.28 24-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.198995E+10 17868.97 18-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.773650E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261791E+10 17886.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161601E+10 13342.93 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.572126E+09 11322.62 18-FEB-17:00 0.00 0.00 0.00 0.00 0.00
March 10994398.98 7978.08 24-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 255.55 0.85 27-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 125523.05 416.99 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 1292.43 0.86 07-JUN-06:25 0.00 0.00 0.00 0.00 0.00
July 1384.97 0.90 05-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 591.71 0.34 18-AUG-06:40 0.00 0.00 0.00 0.00 0.00
September 552.23 0.80 22-SEP-06:25 0.00 0.00 0.00 0.00 0.00
October 571.52 0.82 06-OCT-06:25 0.00 0.00 0.00 0.00 0.00
November 17.83 0.21 08-NOV-07:17 0.00 0.00 0.00 0.00 0.00
December 0.105634E+09 10655.14 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.230490E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 17.83 0.21   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.161601E+10 13342.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.662817E+09 0.662817E+09 18269.41 20-JAN-13:30 18269.41 0.02
February 0.00 0.00 0.484643E+10 0.484643E+10 54544.12 27-FEB-15:00 54544.12 0.02
March 0.00 0.00 0.555053E+10 0.555053E+10 50819.24 02-MAR-13:05 50819.24 0.03
April 0.00 0.00 0.103958E+11 0.103958E+11 120823.86 27-APR-14:40 120823.86 0.05
May 0.00 0.00 0.160577E+11 0.160521E+11 97110.43 04-MAY-15:00 97110.43 0.16
June 0.00 0.00 0.314536E+11 0.314473E+11 108733.24 28-JUN-15:20 108733.24 0.34
July 0.00 0.00 0.572943E+11 0.565424E+11 142506.68 31-JUL-15:40 124821.17 0.54
August 0.00 0.00 0.778205E+11 0.756300E+11 147818.13 29-AUG-14:30 130154.39 0.66
September 0.00 0.00 0.249290E+11 0.245608E+11 124308.12 11-SEP-15:25 124308.12 0.34
October 0.00 0.00 0.465388E+10 0.465388E+10 75816.72 04-OCT-15:00 75816.72 0.06
November 0.00 0.00 0.496308E+10 0.496308E+10 41919.84 15-NOV-14:00 41919.84 0.03
December 0.00 0.00 0.583333E+10 0.583333E+10 46213.73 05-DEC-14:30 46213.73 0.02
                 
Annual Sum or Average 0.00 0.00 0.244461E+12 0.241138E+12       0.19
Minimum of Months 0.00 0.00 0.662817E+09 0.662817E+09 18269.41   18269.41 0.02
Maximum of Months 0.00 0.00 0.778205E+11 0.756300E+11 147818.13   130154.39 0.66



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 30746.79 30746.79 2.46 02-JAN-07:00 2.46 0.00
February 0.00 0.00 0.142385E+11 0.142385E+11 537474.20 27-FEB-15:05 537474.20 0.02
March 0.00 0.00 0.598878E+11 0.598878E+11 520792.56 14-MAR-15:40 520792.56 0.03
April 0.00 0.00 0.966835E+11 0.966835E+11 1021709.20 27-APR-14:40 1021709.20 0.06
May 0.00 0.00 0.146480E+12 0.146420E+12 915515.04 04-MAY-15:00 915515.04 0.17
June 0.00 0.00 0.258587E+12 0.258563E+12 973877.44 28-JUN-15:20 973877.44 0.33
July 0.00 0.00 0.453434E+12 0.449046E+12 1237752.84 31-JUL-16:00 1058815.49 0.48
August 0.00 0.00 0.599350E+12 0.584434E+12 1305463.20 29-AUG-14:30 1141245.44 0.53
September 0.00 0.00 0.235719E+12 0.231243E+12 1102687.18 11-SEP-15:25 1041412.31 0.36
October 0.00 0.00 0.881890E+11 0.881890E+11 723952.10 04-OCT-13:20 723952.10 0.11
November 0.00 0.00 0.103491E+11 0.103491E+11 392871.01 04-NOV-14:05 392871.01 0.02
December 0.00 0.00 28104.41 28104.41 2.99 26-DEC-06:02 2.99 0.00
                 
Annual Sum or Average 0.00 0.00 0.196292E+13 0.193905E+13       0.18
Minimum of Months 0.00 0.00 28104.41 28104.41 2.46   2.46 0.00
Maximum of Months 0.00 0.00 0.599350E+12 0.584434E+12 1305463.20   1141245.44 0.53



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.390035E+09 0.390035E+09 27486.27 27-FEB-15:00 27486.27 0.01
March 0.00 0.00 0.101644E+10 0.101644E+10 33301.00 01-MAR-15:00 33301.00 0.01
April 0.00 0.00 0.764622E+10 0.764622E+10 119309.40 27-APR-14:40 119309.40 0.05
May 0.00 0.00 0.141105E+11 0.141086E+11 100532.12 04-MAY-15:00 100532.12 0.15
June 0.00 0.00 0.268694E+11 0.268676E+11 116132.20 28-JUN-15:20 116132.20 0.32
July 0.00 0.00 0.481077E+11 0.477006E+11 142173.58 31-JUL-16:00 123454.55 0.47
August 0.00 0.00 0.632128E+11 0.618101E+11 146685.64 10-AUG-15:40 134604.51 0.52
September 0.00 0.00 0.215210E+11 0.212331E+11 111213.88 11-SEP-15:25 111213.88 0.33
October 0.00 0.00 0.309679E+10 0.309679E+10 66071.09 04-OCT-15:00 66071.09 0.04
November 0.00 0.00 0.516383E+09 0.516383E+09 29528.85 04-NOV-14:10 29528.85 0.01
December 0.00 0.00 26462.81 26462.81 441.05 26-DEC-05:01 441.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.186487E+12 0.184386E+12       0.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.632128E+11 0.618101E+11 146685.64   134604.51 0.52



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 44228642.85 44228642.85 7411.38 11-JAN-07:14 7411.38 0.00
February 0.00 0.00 0.969962E+09 0.883147E+09 45234.39 24-FEB-07:12 30748.47 0.02
March 0.00 0.00 0.674618E+09 0.668730E+09 34735.90 10-MAR-07:13 19119.57 0.01
April 0.00 0.00 0.456647E+10 0.455548E+10 58214.48 27-APR-15:00 58214.48 0.04
May 0.00 0.00 0.970129E+10 0.965838E+10 57941.51 15-MAY-16:00 57941.51 0.15
June 0.00 0.00 0.206019E+11 0.200158E+11 60255.75 12-JUN-06:35 33779.70 0.29
July 0.00 0.00 0.374619E+11 0.350854E+11 96175.88 31-JUL-10:10 70946.81 0.41
August 0.00 0.00 0.481420E+11 0.456342E+11 79037.71 07-AUG-12:05 71764.62 0.47
September 0.00 0.00 0.172572E+11 0.166330E+11 76932.25 11-SEP-15:25 74437.60 0.31
October 0.00 0.00 0.288060E+10 0.282953E+10 41515.20 04-OCT-15:00 41515.20 0.04
November 0.00 0.00 0.560913E+09 0.540625E+09 38483.62 04-NOV-06:14 24399.94 0.01
December 0.00 0.00 9118321.70 7223948.90 22536.97 16-DEC-07:13 13587.33 0.00
                 
Annual Sum or Average 0.00 0.00 0.142870E+12 0.136556E+12       0.15
Minimum of Months 0.00 0.00 9118321.70 7223948.90 7411.38   7411.38 0.00
Maximum of Months 0.00 0.00 0.481420E+11 0.456342E+11 96175.88   74437.60 0.47



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.451994E+10 0.451991E+10 3119.97 09-JAN-12:00 3119.97 0.00
February 0.00 0.00 0.679760E+10 0.676016E+10 18252.01 27-FEB-15:00 18252.01 0.00
March 0.00 0.00 0.118246E+11 0.114416E+11 126263.66 18-MAR-16:00 126263.66 0.00
April 0.00 0.00 0.766841E+11 0.723599E+11 408346.75 27-APR-16:00 408346.75 0.00
May 0.00 0.00 0.430446E+10 0.407864E+10 84113.33 05-MAY-16:00 72610.43 0.00
June 0.00 0.00 0.331722E+11 0.316610E+11 214401.62 28-JUN-17:00 214401.62 0.00
July 0.00 0.00 0.208486E+12 0.177262E+12 357081.26 27-JUL-16:00 289700.75 0.00
August 0.00 0.00 0.534071E+12 0.426856E+12 473401.08 29-AUG-11:00 388848.37 0.00
September 0.00 0.00 0.339362E+10 0.286077E+10 86201.97 22-SEP-16:00 73177.16 0.00
October 0.00 0.00 0.380186E+10 0.372578E+10 71684.43 04-OCT-15:00 71684.43 0.00
November 0.00 0.00 0.997547E+10 0.866579E+10 180788.58 04-NOV-14:10 135467.22 0.00
December 0.00 0.00 0.130203E+11 0.121201E+11 6025.50 27-DEC-00:40 5490.08 0.00
                 
Annual Sum or Average 0.00 0.00 0.910050E+12 0.762311E+12       0.00
Minimum of Months 0.00 0.00 0.339362E+10 0.286077E+10 3119.97   3119.97 0.00
Maximum of Months 0.00 0.00 0.534071E+12 0.426856E+12 473401.08   408346.75 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.407884E+10 0.407851E+10 2127.82 08-JAN-16:15 2127.82 0.00
February 0.00 0.00 0.879396E+10 0.878354E+10 4449.77 12-FEB-16:45 4449.77 0.00
March 0.00 0.00 0.152870E+11 0.152789E+11 7574.12 31-MAR-24:00 7574.12 0.00
April 0.00 0.00 0.199884E+11 0.199748E+11 8685.55 23-APR-18:03 8685.55 0.00
May 0.00 0.00 0.561126E+10 0.557495E+10 4018.83 31-MAY-24:00 4010.92 0.00
June 0.00 0.00 0.105490E+11 0.104970E+11 5888.96 30-JUN-24:00 5887.11 0.00
July 0.00 0.00 0.162641E+11 0.161491E+11 7864.50 31-JUL-23:55 7834.92 0.00
August 0.00 0.00 0.212835E+11 0.211227E+11 9269.74 06-AUG-18:41 9269.74 0.00
September 0.00 0.00 0.559983E+10 0.550915E+10 3897.99 30-SEP-24:00 3896.94 0.00
October 0.00 0.00 0.104255E+11 0.104028E+11 5616.72 31-OCT-24:00 5616.72 0.00
November 0.00 0.00 0.147019E+11 0.146783E+11 6404.48 11-NOV-15:55 6404.48 0.00
December 0.00 0.00 0.200314E+11 0.200290E+11 8191.42 10-DEC-15:35 8191.42 0.00
                 
Annual Sum or Average 0.00 0.00 0.152615E+12 0.152079E+12       0.00
Minimum of Months 0.00 0.00 0.407884E+10 0.407851E+10 2127.82   2127.82 0.00
Maximum of Months 0.00 0.00 0.212835E+11 0.211227E+11 9269.74   9269.74 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.153967E+11 0.153967E+11 16735.79 05-JAN-16:20 16735.79 0.00
February 0.00 0.00 0.671695E+11 0.670671E+11 40321.11 27-FEB-16:20 40122.04 0.00
March 0.00 0.00 0.134099E+12 0.134018E+12 67946.72 31-MAR-23:50 67946.72 0.00
April 0.00 0.00 0.183766E+12 0.183628E+12 82486.09 26-APR-18:00 82486.09 0.00
May 0.00 0.00 0.484483E+11 0.480915E+11 37707.65 31-MAY-23:40 37589.47 0.00
June 0.00 0.00 0.969641E+11 0.964471E+11 55462.70 30-JUN-24:00 55442.60 0.00
July 0.00 0.00 0.152924E+12 0.151785E+12 75632.06 31-JUL-23:55 75342.90 0.00
August 0.00 0.00 0.201476E+12 0.199879E+12 86997.16 06-AUG-18:35 86997.16 0.00
September 0.00 0.00 0.487566E+11 0.478683E+11 35424.38 30-SEP-23:50 35408.62 0.00
October 0.00 0.00 0.893620E+11 0.891362E+11 47940.88 31-OCT-24:00 47940.88 0.00
November 0.00 0.00 0.123847E+12 0.123611E+12 58347.95 04-NOV-16:00 57152.12 0.00
December 0.00 0.00 0.168736E+12 0.168711E+12 73202.89 05-DEC-15:50 73202.89 0.00
                 
Annual Sum or Average 0.00 0.00 0.133094E+13 0.132564E+13       0.00
Minimum of Months 0.00 0.00 0.153967E+11 0.153967E+11 16735.79   16735.79 0.00
Maximum of Months 0.00 0.00 0.201476E+12 0.199879E+12 86997.16   86997.16 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.483413E+09 0.483413E+09 1542.07 05-JAN-16:20 1542.07 0.00
February 0.00 0.00 0.510112E+10 0.509103E+10 3992.71 27-FEB-16:30 3966.34 0.00
March 0.00 0.00 0.121187E+11 0.121106E+11 6309.42 31-MAR-23:20 6309.42 0.00
April 0.00 0.00 0.176315E+11 0.176177E+11 8322.28 26-APR-18:00 8322.28 0.00
May 0.00 0.00 0.437263E+10 0.433714E+10 3696.53 31-MAY-23:20 3679.97 0.00
June 0.00 0.00 0.949641E+10 0.944469E+10 5464.44 30-JUN-23:40 5460.94 0.00
July 0.00 0.00 0.151845E+11 0.150704E+11 7536.45 31-JUL-23:55 7507.35 0.00
August 0.00 0.00 0.200214E+11 0.198617E+11 8906.93 06-AUG-18:30 8906.93 0.00
September 0.00 0.00 0.439253E+10 0.430478E+10 3149.17 30-SEP-23:20 3145.92 0.00
October 0.00 0.00 0.777963E+10 0.775745E+10 4593.85 04-OCT-16:50 4593.85 0.00
November 0.00 0.00 0.107139E+11 0.106906E+11 5749.04 04-NOV-16:00 5630.19 0.00
December 0.00 0.00 0.149130E+11 0.149105E+11 7128.11 05-DEC-16:00 7128.11 0.00
                 
Annual Sum or Average 0.00 0.00 0.122209E+12 0.121680E+12       0.00
Minimum of Months 0.00 0.00 0.483413E+09 0.483413E+09 1542.07   1542.07 0.00
Maximum of Months 0.00 0.00 0.200214E+11 0.198617E+11 8906.93   8906.93 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 99624.66 1286711.37 02-JAN-06:03
February 0.00 0.00 01-FEB-00:10 60568.80 979699.44 15-FEB-06:02
March 0.00 0.00 01-MAR-00:10 22119.62 926247.28 06-MAR-06:02
April 0.00 0.00 01-APR-00:10 9829.62 350590.30 03-APR-13:20
May 0.00 0.00 01-MAY-00:10 2437.72 285163.83 17-MAY-13:10
June 0.00 0.00 01-JUN-00:10 117.49 192785.50 13-JUN-09:20
July 0.00 0.00 01-JUL-00:10 26.96 114609.62 12-JUL-09:20
August 0.00 0.00 01-AUG-00:03 22.40 133347.78 03-AUG-09:05
September 0.00 0.00 01-SEP-00:05 432.72 248533.80 27-SEP-09:20
October 0.00 0.00 01-OCT-00:10 5200.66 409461.33 30-OCT-05:03
November 0.00 0.00 01-NOV-00:10 38145.54 1030791.32 24-NOV-05:11
December 0.00 0.00 01-DEC-00:10 75265.56 1130970.57 18-DEC-05:11
             
Annual Sum or Average 0.00     26020.04    
Minimum of Months 0.00 0.00   22.40 114609.62  
Maximum of Months 0.00 0.00   99624.66 1286711.37  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 429.34 21288.50 11-JAN-07:14 0.00 0.00 01-JAN-00:05
February 8883.72 640170.33 27-FEB-15:05 0.00 0.00 01-FEB-00:10
March 25595.48 572939.84 14-MAR-16:00 0.00 0.00 01-MAR-00:10
April 47378.14 1317024.53 27-APR-14:40 0.00 0.00 01-APR-00:10
May 71774.02 1756309.84 04-MAY-14:05 0.00 0.00 01-MAY-00:10
June 133223.29 1713836.18 21-JUN-14:05 0.00 0.00 01-JUN-00:10
July 229669.18 1601653.38 31-JUL-16:00 0.00 0.00 01-JUL-00:10
August 302953.51 1669905.24 29-AUG-14:30 0.00 0.00 01-AUG-00:03
September 118206.11 1702435.79 11-SEP-15:25 0.00 0.00 01-SEP-00:05
October 37889.17 1081058.33 04-OCT-15:10 0.00 0.00 01-OCT-00:10
November 6759.95 475047.10 04-NOV-14:10 0.00 0.00 01-NOV-00:10
December 2724.33 62655.96 16-DEC-07:13 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 82788.64     0.00    
Minimum of Months 429.34 21288.50   0.00 0.00  
Maximum of Months 302953.51 1756309.84   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 224.34 23145.10 11-JAN-07:12 0.00 0.00 01-JAN-00:05
February 8440.15 649662.78 27-FEB-15:05 0.00 0.00 01-FEB-00:10
March 24977.50 571271.13 14-MAR-16:00 0.00 0.00 01-MAR-00:10
April 46849.55 1314942.98 27-APR-14:40 0.00 0.00 01-APR-00:10
May 71531.67 1853833.21 04-MAY-14:00 0.00 0.00 01-MAY-00:10
June 133170.27 1741435.94 20-JUN-13:40 0.00 0.00 01-JUN-00:10
July 229087.33 1990006.80 20-JUL-12:20 0.00 0.00 01-JUL-00:10
August 303122.91 1910278.93 09-AUG-10:00 0.00 0.00 01-AUG-00:03
September 120221.60 1953818.87 11-SEP-15:20 0.00 0.00 01-SEP-00:05
October 37370.15 1109391.77 04-OCT-13:20 0.00 0.00 01-OCT-00:10
November 6283.87 480273.28 04-NOV-14:05 0.00 0.00 01-NOV-00:10
December 2193.02 84602.60 16-DEC-07:12 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 82618.62     0.00    
Minimum of Months 224.34 23145.10   0.00 0.00  
Maximum of Months 303122.91 1990006.80   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 15825.42 32930.79 12-JAN-20:20 0.00 0.00 01-JAN-00:05
February 49299.01 197913.38 27-FEB-15:00 0.00 0.00 01-FEB-00:10
March 84185.34 460338.37 18-MAR-16:00 0.00 0.00 01-MAR-00:10
April 171172.63 1396849.38 27-APR-16:00 0.00 0.00 01-APR-00:10
May 53511.99 566858.58 05-MAY-16:00 0.00 0.00 01-MAY-00:10
June 121528.06 937169.74 28-JUN-17:00 0.00 0.00 01-JUN-00:10
July 313229.84 1404740.43 24-JUL-15:00 0.00 0.00 01-JUL-00:10
August 587074.39 1688014.39 10-AUG-17:00 0.00 0.00 01-AUG-00:03
September 59981.53 568776.16 22-SEP-16:00 0.00 0.00 01-SEP-00:05
October 56878.89 396727.08 04-OCT-15:00 0.00 0.00 01-OCT-00:10
November 80398.43 579995.73 04-NOV-15:00 0.00 0.00 01-NOV-00:10
December 102640.60 118351.00 05-DEC-16:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 142428.86     0.00    
Minimum of Months 15825.42 32930.79   0.00 0.00  
Maximum of Months 587074.39 1688014.39   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 14332.43 51088.77 31-JAN-12:30
February 0.00 0.00 01-FEB-00:10 14518.51 51150.72 10-FEB-12:40
March 0.00 0.00 01-MAR-00:10 15258.69 50975.57 01-MAR-12:40
April 0.00 0.00 01-APR-00:10 13905.14 49837.65 03-APR-12:00
May 0.00 0.00 01-MAY-00:10 13845.35 48284.37 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 13658.88 46383.74 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 12219.48 44763.74 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 13273.49 44110.86 31-AUG-11:20
September 0.00 0.00 01-SEP-00:05 12602.97 45073.86 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 12975.99 46819.57 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 13675.01 48660.72 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 13648.71 50167.44 29-DEC-12:40
             
Annual Sum or Average 0.00     13654.68    
Minimum of Months 0.00 0.00   12219.48 44110.86  
Maximum of Months 0.00 0.00   15258.69 51150.72  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 19.57 13542.58 27-JAN-11:30 2388.66 114057.98 09-JAN-06:40
February 7311.12 727988.72 27-FEB-15:10 3222.69 106975.32 14-FEB-14:10
March 25692.02 654108.48 14-MAR-16:00 2875.54 115501.15 25-MAR-10:20
April 55242.99 2012446.78 27-APR-13:20 1188.21 90281.21 24-APR-07:00
May 82627.64 2082646.06 04-MAY-14:05 1159.86 87095.10 18-MAY-08:00
June 158560.32 2031796.66 22-JUN-14:50 1218.22 71141.49 06-JUN-13:30
July 290154.33 3036299.07 31-JUL-16:00 1365.26 61001.71 05-JUL-20:10
August 416735.04 3408623.84 29-AUG-14:30 1648.51 54102.30 12-AUG-05:30
September 142968.70 2509185.84 11-SEP-15:25 995.14 60229.61 19-SEP-19:20
October 42030.93 1310132.64 04-OCT-13:20 660.71 76899.06 13-OCT-09:40
November 5318.92 541067.29 04-NOV-14:10 3975.65 103289.52 16-NOV-08:50
December 272.53 37356.96 06-DEC-15:10 5206.09 105900.39 21-DEC-15:10
             
Annual Sum or Average 103153.24     2153.41    
Minimum of Months 19.57 13542.58   660.71 54102.30  
Maximum of Months 416735.04 3408623.84   5206.09 115501.15  



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.298771E+10 0.29 9209.68 02-JAN-06:03 1.12
February 0.380679E+10 0.34 13304.14 27-FEB-15:00 1.41
March 0.640259E+10 0.42 13014.32 14-MAR-14:50 1.39
April 0.853373E+10 0.50 19200.93 27-APR-14:40 1.77
May 0.773967E+10 0.46 16371.73 15-MAY-14:30 1.61
June 0.959131E+10 0.54 19476.77 12-JUN-04:12 1.78
July 0.117247E+11 0.61 19476.77 31-JUL-14:10 1.78
August 0.135093E+11 0.69 19476.77 07-AUG-10:40 1.78
September 0.787689E+10 0.46 19476.77 11-SEP-14:03 1.78
October 0.634296E+10 0.40 15561.95 04-OCT-15:20 1.56
November 0.464842E+10 0.35 10268.08 03-NOV-05:02 1.20
December 0.441681E+10 0.34 10267.68 04-DEC-05:11 1.20
           
Annual Sum or Average 0.875808E+11 0.45      
Minimum of Months 0.298771E+10 0.29 9209.68   1.12
Maximum of Months 0.135093E+11 0.69 19476.77   1.78



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.212418E+11 0.28 54043.04 02-JAN-05:52 0.86
February 0.229624E+11 0.29 69051.03 28-FEB-06:02 0.99
March 0.342378E+11 0.33 80134.19 02-MAR-15:05 1.08
April 0.431877E+11 0.36 146923.63 27-APR-14:40 1.57
May 0.566557E+11 0.41 142674.15 15-MAY-14:05 1.55
June 0.653667E+11 0.45 134351.74 28-JUN-14:05 1.48
July 0.759957E+11 0.47 179437.52 20-JUL-12:20 1.78
August 0.861516E+11 0.51 179437.52 09-AUG-10:00 1.78
September 0.591615E+11 0.41 179437.52 11-SEP-14:03 1.78
October 0.378919E+11 0.33 129617.48 04-OCT-15:40 1.46
November 0.236868E+11 0.28 70727.21 10-NOV-06:03 1.01
December 0.222098E+11 0.28 47744.22 07-DEC-06:02 0.80
           
Annual Sum or Average 0.548749E+12 0.37      
Minimum of Months 0.212418E+11 0.28 47744.22   0.80
Maximum of Months 0.861516E+11 0.51 179437.52   1.78



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.260802E+10 0.34 4752.46 02-JAN-05:11 0.75
February 0.227017E+10 0.32 4752.46 06-FEB-05:11 0.75
March 0.269275E+10 0.31 5413.37 14-MAR-15:40 0.81
April 0.347707E+10 0.32 15531.43 27-APR-14:40 1.51
May 0.475903E+10 0.36 14992.15 15-MAY-14:50 1.49
June 0.587594E+10 0.41 14788.38 28-JUN-15:20 1.47
July 0.716347E+10 0.43 17905.11 31-JUL-14:30 1.65
August 0.796032E+10 0.46 19339.35 10-AUG-14:40 1.73
September 0.486559E+10 0.36 20115.14 11-SEP-14:07 1.78
October 0.284448E+10 0.30 11054.53 04-OCT-15:30 1.23
November 0.213329E+10 0.29 4752.46 13-NOV-05:01 0.75
December 0.232991E+10 0.30 4752.46 01-DEC-06:02 0.75
           
Annual Sum or Average 0.489800E+11 0.35      
Minimum of Months 0.213329E+10 0.29 4752.46   0.75
Maximum of Months 0.796032E+10 0.46 20115.14   1.78



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.421154E+10 0.39 11104.85 02-JAN-07:05 1.80
February 0.643575E+10 0.53 11104.85 01-FEB-07:10 1.80
March 0.114253E+11 0.75 11104.85 01-MAR-07:05 1.81
April 0.131443E+11 0.84 11104.85 01-APR-06:05 1.81
May 0.128127E+11 0.81 11104.85 01-MAY-06:10 1.79
June 0.116715E+11 0.78 11104.85 01-JUN-06:05 1.80
July 0.956931E+10 0.65 11104.85 01-JUL-06:10 1.79
August 0.118823E+11 0.78 11104.85 01-AUG-06:10 1.79
September 0.114890E+11 0.76 11104.85 01-SEP-06:10 1.79
October 0.133507E+11 0.83 11104.85 02-OCT-06:05 1.80
November 0.130382E+11 0.83 11104.85 01-NOV-06:10 1.80
December 0.112970E+11 0.73 11104.85 01-DEC-07:05 1.81
           
Annual Sum or Average 0.130328E+12 0.72      
Minimum of Months 0.421154E+10 0.39 11104.85   1.79
Maximum of Months 0.133507E+11 0.84 11104.85   1.81



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.109549E+12 1.37 40901.08 01-JAN-00:05 1.37
February 0.989479E+11 1.37 40901.08 01-FEB-00:20 1.37
March 0.109549E+12 1.37 40901.08 01-MAR-00:10 1.37
April 0.106016E+12 1.37 40901.08 01-APR-00:10 1.37
May 0.109549E+12 1.37 40901.08 01-MAY-00:10 1.37
June 0.106016E+12 1.36 40901.08 01-JUN-00:10 1.37
July 0.109549E+12 1.36 40901.08 01-JUL-00:30 1.36
August 0.109549E+12 1.36 40901.08 01-AUG-00:03 1.36
September 0.106016E+12 1.36 40901.08 01-SEP-00:05 1.36
October 0.109549E+12 1.37 40901.08 01-OCT-00:10 1.36
November 0.106016E+12 1.37 40901.08 01-NOV-00:10 1.37
December 0.109549E+12 1.37 40901.08 01-DEC-00:20 1.37
           
Annual Sum or Average 0.128986E+13 1.37      
Minimum of Months 0.989479E+11 1.36 40901.08   1.36
Maximum of Months 0.109549E+12 1.37 40901.08   1.37



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.151276E+10 0.93 564.80 01-JAN-00:05 0.93
February 0.136636E+10 0.93 564.80 01-FEB-00:10 0.93
March 0.151276E+10 0.93 564.80 01-MAR-00:10 0.93
April 0.146396E+10 0.93 564.80 01-APR-00:10 0.93
May 0.151276E+10 0.93 564.80 01-MAY-00:10 0.93
June 0.146396E+10 0.93 564.80 01-JUN-00:10 0.93
July 0.151276E+10 0.93 564.80 01-JUL-00:10 0.93
August 0.151276E+10 0.93 564.80 01-AUG-00:03 0.93
September 0.146396E+10 0.93 564.80 01-SEP-00:05 0.93
October 0.151276E+10 0.93 564.80 01-OCT-00:10 0.93
November 0.146396E+10 0.93 564.80 01-NOV-00:10 0.93
December 0.151276E+10 0.93 564.80 01-DEC-00:10 0.93
           
Annual Sum or Average 0.178115E+11 0.93      
Minimum of Months 0.136636E+10 0.93 564.80   0.93
Maximum of Months 0.151276E+10 0.93 564.80   0.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.145267E+11 0.93 5423.64 01-JAN-00:05 0.92
February 0.131209E+11 0.93 5423.64 01-FEB-00:10 0.93
March 0.145267E+11 0.93 5423.64 01-MAR-00:10 0.93
April 0.140581E+11 0.93 5423.64 01-APR-00:10 0.93
May 0.145267E+11 0.93 5423.64 01-MAY-00:10 0.93
June 0.140581E+11 0.93 5423.64 01-JUN-00:10 0.93
July 0.145267E+11 0.93 5423.64 01-JUL-00:10 0.93
August 0.145267E+11 0.93 5423.64 01-AUG-00:03 0.93
September 0.140581E+11 0.93 5423.64 01-SEP-00:05 0.93
October 0.145267E+11 0.93 5423.64 01-OCT-00:10 0.93
November 0.140581E+11 0.93 5423.64 01-NOV-00:10 0.93
December 0.145267E+11 0.93 5423.64 01-DEC-00:10 0.93
           
Annual Sum or Average 0.171040E+12 0.93      
Minimum of Months 0.131209E+11 0.93 5423.64   0.92
Maximum of Months 0.145267E+11 0.93 5423.64   0.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147436E+10 0.93 550.46 01-JAN-00:05 0.93
February 0.133168E+10 0.93 550.46 01-FEB-00:10 0.93
March 0.147436E+10 0.93 550.46 01-MAR-00:10 0.93
April 0.142680E+10 0.93 550.46 01-APR-00:10 0.93
May 0.147436E+10 0.93 550.46 01-MAY-00:10 0.93
June 0.142680E+10 0.93 550.46 01-JUN-00:10 0.93
July 0.147436E+10 0.93 550.46 01-JUL-00:10 0.93
August 0.147436E+10 0.93 550.46 01-AUG-00:03 0.93
September 0.142680E+10 0.93 550.46 01-SEP-00:05 0.93
October 0.147436E+10 0.93 550.46 01-OCT-00:10 0.93
November 0.142680E+10 0.93 550.46 01-NOV-00:10 0.93
December 0.147436E+10 0.93 550.46 01-DEC-00:10 0.93
           
Annual Sum or Average 0.173594E+11 0.93      
Minimum of Months 0.133168E+10 0.93 550.46   0.93
Maximum of Months 0.147436E+10 0.93 550.46   0.93



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.117326E+10 0.106649E+10 3462.08 02-JAN-06:03 3147.03 3147.03 46.66 8.71
February 0.654464E+09 0.594908E+09 3023.25 21-FEB-06:01 2748.13 2748.13 44.14 5.53
March 0.252928E+09 0.229911E+09 3002.70 06-MAR-06:02 2729.45 2729.45 41.31 5.45
April 0.107968E+09 98142959.30 1418.70 18-APR-11:30 1289.60 1289.60 34.29 1.74
May 26775644.20 24339060.58 1177.34 17-MAY-13:10 1070.21 1070.21 32.99 1.39
June 1246513.30 1133080.59 758.11 13-JUN-09:20 689.13 689.13 27.68 0.85
July 291507.57 264980.38 461.91 12-JUL-09:20 419.88 419.88 27.10 0.50
August 244741.66 222470.17 539.47 03-AUG-09:05 490.37 490.37 27.79 0.59
September 4605805.16 4186676.89 975.42 27-SEP-09:20 886.66 886.66 29.05 1.12
October 57187843.77 51983749.99 1539.57 30-OCT-05:03 1399.47 1399.47 31.09 1.92
November 0.424827E+09 0.386168E+09 3005.30 24-NOV-06:03 2731.82 2731.82 42.07 5.46
December 0.877916E+09 0.798026E+09 3145.35 26-DEC-06:02 2859.12 2859.12 45.59 6.13
                 
Annual Sum or Average 0.358171E+10 0.325578E+10            
Minimum of Months 244741.66 222470.17 461.91   419.88 419.88 27.10 0.50
Maximum of Months 0.117326E+10 0.106649E+10 3462.08   3147.03 3147.03 46.66 8.71



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 78260.58 71138.87 3.14 11-JAN-07:14 2.85 2.85 6.70 0.74
February 11660886.01 10599745.38 809.31 27-FEB-15:05 735.66 735.66 6.71 20.39
March 22826269.66 20749079.12 741.44 14-MAR-15:40 673.97 673.97 6.71 19.60
April 0.109444E+09 99484272.08 3604.96 26-APR-14:40 3276.91 3276.91 6.72 38.68
May 0.162800E+09 0.147985E+09 4780.64 04-MAY-14:05 4345.60 4345.60 8.02 43.39
June 0.367396E+09 0.333963E+09 4367.95 22-JUN-14:30 3970.47 3970.47 9.03 41.83
July 0.612138E+09 0.556434E+09 7647.90 20-JUL-12:20 6951.94 6951.94 11.14 52.34
August 0.892678E+09 0.811445E+09 9093.74 09-AUG-10:00 8266.21 8266.21 11.96 56.03
September 0.338510E+09 0.307706E+09 9128.82 11-SEP-14:03 8298.10 8298.10 10.53 56.13
October 60901450.27 55359418.30 1403.84 04-OCT-13:20 1276.09 1276.09 8.72 26.00
November 4730673.17 4300181.91 240.68 04-NOV-14:05 218.78 218.78 6.70 11.53
December 601329.73 546608.72 12.88 16-DEC-07:13 11.71 11.71 6.70 2.15
                 
Annual Sum or Average 0.258377E+10 0.234864E+10            
Minimum of Months 78260.58 71138.87 3.14   2.85 2.85 6.70 0.74
Maximum of Months 0.892678E+09 0.811445E+09 9128.82   8298.10 8298.10 11.96 56.13



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.604499E+09 0.549489E+09 3141.56 02-JAN-08:20 2855.68 2855.68 6.72 28.07
February 0.120020E+10 0.109098E+10 3141.56 01-FEB-07:12 2855.68 2855.68 6.82 28.07
March 0.188465E+10 0.171315E+10 3141.56 01-MAR-06:00 2855.68 2855.68 6.76 28.07
April 0.172928E+10 0.157191E+10 3141.56 01-APR-05:02 2855.68 2855.68 7.21 28.07
May 0.255243E+10 0.232016E+10 3141.56 01-MAY-04:12 2855.68 2855.68 6.74 28.07
June 0.387222E+10 0.351984E+10 3141.56 01-JUN-04:12 2855.68 2855.68 6.91 28.07
July 0.528293E+10 0.480219E+10 3141.56 01-JUL-04:12 2855.68 2855.68 7.34 28.07
August 0.595875E+10 0.541650E+10 3141.56 01-AUG-00:25 2855.68 2855.68 6.79 28.07
September 0.349358E+10 0.317566E+10 3141.56 01-SEP-00:05 2855.68 2855.68 6.75 28.07
October 0.156340E+10 0.142113E+10 3141.56 01-OCT-12:15 2855.68 2855.68 6.83 28.07
November 0.136712E+10 0.124271E+10 3141.56 01-NOV-06:12 2855.68 2855.68 6.93 28.07
December 0.156597E+10 0.142347E+10 3141.56 01-DEC-09:40 2855.68 2855.68 6.73 28.07
                 
Annual Sum or Average 0.310750E+11 0.282472E+11            
Minimum of Months 0.604499E+09 0.549489E+09 3141.56   2855.68 2855.68 6.72 28.07
Maximum of Months 0.595875E+10 0.541650E+10 3141.56   2855.68 2855.68 7.34 28.07



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00 6.70 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 6.73 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 6.88 0.00
April 86707025.90 78816686.54 3141.56 26-APR-13:20 2855.68 2855.68 14.96 14.03
May 0.114039E+09 0.103661E+09 3141.56 04-MAY-13:50 2855.68 2855.68 14.68 14.03
June 0.180011E+09 0.163630E+09 3141.56 09-JUN-14:30 2855.68 2855.68 15.15 14.03
July 0.517415E+09 0.470330E+09 3141.56 06-JUL-15:50 2855.68 2855.68 17.29 14.03
August 0.104331E+10 0.948370E+09 3141.56 07-AUG-10:00 2855.68 2855.68 15.35 14.03
September 0.222422E+09 0.202182E+09 3141.56 08-SEP-14:40 2855.68 2855.68 13.81 14.03
October 9424676.73 8567031.15 3141.56 04-OCT-13:20 2855.68 2855.68 15.86 14.03
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 6.81 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.74 0.00
                 
Annual Sum or Average 0.217333E+10 0.197556E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.70 0.00
Maximum of Months 0.104331E+10 0.948370E+09 3141.56   2855.68 2855.68 17.29 14.03



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.999161E+10 0.908237E+10 3730.44 01-JAN-00:05 3390.97 3390.97 18.48 15.74
February 0.902468E+10 0.820343E+10 3730.44 01-FEB-00:10 3390.97 3390.97 19.11 15.74
March 0.999161E+10 0.908237E+10 3730.44 01-MAR-00:10 3390.97 3390.97 19.80 15.74
April 0.966930E+10 0.878939E+10 3730.44 01-APR-00:10 3390.97 3390.97 20.27 15.74
May 0.999161E+10 0.908237E+10 3730.44 01-MAY-00:10 3390.97 3390.97 18.90 15.74
June 0.966930E+10 0.878939E+10 3730.44 01-JUN-00:10 3390.97 3390.97 19.40 15.74
July 0.999161E+10 0.908237E+10 3730.44 01-JUL-00:10 3390.97 3390.97 19.88 15.74
August 0.999161E+10 0.908237E+10 3730.44 01-AUG-00:03 3390.97 3390.97 24.95 15.74
September 0.966930E+10 0.878939E+10 3730.44 01-SEP-00:05 3390.97 3390.97 18.95 15.74
October 0.999161E+10 0.908237E+10 3730.44 01-OCT-00:10 3390.97 3390.97 19.34 15.74
November 0.966930E+10 0.878939E+10 3730.44 01-NOV-00:10 3390.97 3390.97 19.72 15.74
December 0.999161E+10 0.908237E+10 3730.44 01-DEC-00:10 3390.97 3390.97 20.20 15.74
                 
Annual Sum or Average 0.117643E+12 0.106938E+12            
Minimum of Months 0.902468E+10 0.820343E+10 3730.44   3390.97 3390.97 18.48 15.74
Maximum of Months 0.999161E+10 0.908237E+10 3730.44   3390.97 3390.97 24.95 15.74



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 56.98 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:03 16.86 16.86 57.00 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:02 16.86 16.86 57.07 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:02 16.86 16.86 57.13 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 57.34 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 57.28 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 57.30 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 57.42 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 57.41 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 57.12 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 57.31 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:02 16.86 16.86 57.20 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.98 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.42 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.238704E+10 0.216982E+10 12407.32 27-JAN-11:30 11278.25 11278.25 21.16 50.80
February 0.474027E+10 0.430891E+10 12437.38 27-FEB-15:10 11305.58 11305.58 24.53 50.80
March 0.744550E+10 0.676796E+10 12434.27 14-MAR-16:00 11302.75 11302.75 24.18 50.80
April 0.716279E+10 0.651098E+10 24900.82 27-APR-13:20 22634.84 22634.84 25.84 101.60
May 0.104430E+11 0.949267E+10 24904.27 04-MAY-14:05 22637.98 22637.98 26.00 101.60
June 0.159386E+11 0.144882E+11 24901.77 22-JUN-14:50 22635.71 22635.71 25.89 101.60
July 0.227799E+11 0.207069E+11 24951.22 31-JUL-16:00 22680.66 22680.66 28.25 101.60
August 0.274923E+11 0.249905E+11 24969.60 29-AUG-14:30 22697.36 22697.36 29.13 101.60
September 0.146017E+11 0.132729E+11 24925.25 11-SEP-15:25 22657.05 22657.05 27.01 101.60
October 0.621613E+10 0.565046E+10 24868.77 04-OCT-13:20 22605.71 22605.71 24.19 101.60
November 0.539922E+10 0.490789E+10 12429.51 04-NOV-14:10 11298.42 11298.42 23.65 50.80
December 0.618384E+10 0.562111E+10 12408.32 06-DEC-15:10 11279.16 11279.16 21.28 50.80
                 
Annual Sum or Average 0.130790E+12 0.118888E+12            
Minimum of Months 0.238704E+10 0.216982E+10 12407.32   11278.25 11278.25 21.16 50.80
Maximum of Months 0.274923E+11 0.249905E+11 24969.60   22697.36 22697.36 29.13 101.60



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 46.28 46.28 99624.66 1286711.37 02-JAN-06:03
February 0.00 0.00 01-FEB-00:10 29.78 29.78 60568.80 979699.44 15-FEB-06:02
March 0.00 0.00 01-MAR-00:10 24.91 24.91 22119.62 926247.28 06-MAR-06:02
April 0.00 0.00 01-APR-00:10 23.74 23.74 9829.62 350590.30 03-APR-13:20
May 0.00 0.00 01-MAY-00:10 24.85 24.85 2437.72 285163.83 17-MAY-13:10
June 0.00 0.00 01-JUN-00:10 26.48 26.48 117.49 192785.50 13-JUN-09:20
July 0.00 0.00 01-JUL-00:10 26.70 26.70 26.96 114609.62 12-JUL-09:20
August 0.00 0.00 01-AUG-00:03 27.54 27.54 22.40 133347.78 03-AUG-09:05
September 0.00 0.00 01-SEP-00:05 28.10 28.10 432.72 248533.80 27-SEP-09:20
October 0.00 0.00 01-OCT-00:10 26.36 26.36 5200.66 409461.33 30-OCT-05:03
November 0.00 0.00 01-NOV-00:10 27.68 27.68 38145.54 1030791.32 24-NOV-05:11
December 0.00 0.00 01-DEC-00:10 32.01 32.01 75265.56 1130970.57 18-DEC-05:11
                 
Annual Sum or Average 0.00         26020.04    
Minimum of Months 0.00 0.00   23.74 23.74 22.40 114609.62  
Maximum of Months 0.00 0.00   46.28 46.28 99624.66 1286711.37  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 429.34 21288.50 11-JAN-07:14 6.88 6.70 0.00 0.00 01-JAN-00:05
February 8883.72 640170.33 27-FEB-15:05 12.15 6.70 0.00 0.00 01-FEB-00:10
March 25595.48 572939.84 14-MAR-16:00 11.57 6.70 0.00 0.00 01-MAR-00:10
April 47378.14 1317024.53 27-APR-14:40 12.30 6.70 0.00 0.00 01-APR-00:10
May 71774.02 1756309.84 04-MAY-14:05 14.17 6.70 0.00 0.00 01-MAY-00:10
June 133223.29 1713836.18 21-JUN-14:05 13.99 6.70 0.00 0.00 01-JUN-00:10
July 229669.18 1601653.38 31-JUL-16:00 13.51 6.70 0.00 0.00 01-JUL-00:10
August 302953.51 1669905.24 29-AUG-14:30 13.81 6.70 0.00 0.00 01-AUG-00:03
September 118206.11 1702435.79 11-SEP-15:25 13.94 6.70 0.00 0.00 01-SEP-00:05
October 37889.17 1081058.33 04-OCT-15:10 11.30 6.70 0.00 0.00 01-OCT-00:10
November 6759.95 475047.10 04-NOV-14:10 10.74 6.70 0.00 0.00 01-NOV-00:10
December 2724.33 62655.96 16-DEC-07:13 7.23 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 82788.64         0.00    
Minimum of Months 429.34 21288.50   6.88 6.70 0.00 0.00  
Maximum of Months 302953.51 1756309.84   14.17 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 224.34 23145.10 11-JAN-07:12 14.14 6.70 0.00 0.00 01-JAN-00:05
February 8440.15 649662.78 27-FEB-15:05 14.31 6.70 0.00 0.00 01-FEB-00:10
March 24977.50 571271.13 14-MAR-16:00 13.72 6.70 0.00 0.00 01-MAR-00:10
April 46849.55 1314942.98 27-APR-14:40 16.22 6.70 0.00 0.00 01-APR-00:10
May 71531.67 1853833.21 04-MAY-14:00 17.62 11.81 0.00 0.00 01-MAY-00:10
June 133170.27 1741435.94 20-JUN-13:40 17.44 11.57 0.00 0.00 01-JUN-00:10
July 229087.33 1990006.80 20-JUL-12:20 15.79 11.21 0.00 0.00 01-JUL-00:10
August 303122.91 1910278.93 09-AUG-10:00 14.85 12.05 0.00 0.00 01-AUG-00:03
September 120221.60 1953818.87 11-SEP-15:20 15.02 10.85 0.00 0.00 01-SEP-00:05
October 37370.15 1109391.77 04-OCT-13:20 16.90 9.26 0.00 0.00 01-OCT-00:10
November 6283.87 480273.28 04-NOV-14:05 16.65 6.70 0.00 0.00 01-NOV-00:10
December 2193.02 84602.60 16-DEC-07:12 16.15 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 82618.62         0.00    
Minimum of Months 224.34 23145.10   13.72 6.70 0.00 0.00  
Maximum of Months 303122.91 1990006.80   17.62 12.05 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 15825.42 32930.79 12-JAN-20:20 18.93 18.33 0.00 0.00 01-JAN-00:05
February 49299.01 197913.38 27-FEB-15:00 21.95 20.50 0.00 0.00 01-FEB-00:10
March 84185.34 460338.37 18-MAR-16:00 26.71 22.18 0.00 0.00 01-MAR-00:10
April 171172.63 1396849.38 27-APR-16:00 43.36 31.47 0.00 0.00 01-APR-00:10
May 53511.99 566858.58 05-MAY-16:00 28.63 25.94 0.00 0.00 01-MAY-00:10
June 121528.06 937169.74 28-JUN-17:00 35.26 28.94 0.00 0.00 01-JUN-00:10
July 313229.84 1404740.43 24-JUL-15:00 43.50 34.01 0.00 0.00 01-JUL-00:10
August 587074.39 1688014.39 10-AUG-17:00 48.43 36.23 0.00 0.00 01-AUG-00:03
September 59981.53 568776.16 22-SEP-16:00 28.66 25.95 0.00 0.00 01-SEP-00:05
October 56878.89 396727.08 04-OCT-15:00 25.56 22.70 0.00 0.00 01-OCT-00:10
November 80398.43 579995.73 04-NOV-15:00 28.87 23.12 0.00 0.00 01-NOV-00:10
December 102640.60 118351.00 05-DEC-16:00 20.50 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 142428.86         0.00    
Minimum of Months 15825.42 32930.79   18.93 18.33 0.00 0.00  
Maximum of Months 587074.39 1688014.39   48.43 36.23 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 58.13 58.13 14332.43 51088.77 31-JAN-12:30
February 0.00 0.00 01-FEB-00:10 57.62 57.62 14518.51 51150.72 10-FEB-12:40
March 0.00 0.00 01-MAR-00:10 57.62 57.62 15258.69 50975.57 01-MAR-12:40
April 0.00 0.00 01-APR-00:10 57.67 57.67 13905.14 49837.65 03-APR-12:00
May 0.00 0.00 01-MAY-00:10 58.21 58.21 13845.35 48284.37 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 57.84 57.84 13658.88 46383.74 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.91 57.91 12219.48 44763.74 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 57.95 57.95 13273.49 44110.86 31-AUG-11:20
September 0.00 0.00 01-SEP-00:05 57.95 57.95 12602.97 45073.86 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 57.90 57.90 12975.99 46819.57 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 57.82 57.82 13675.01 48660.72 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 57.73 57.73 13648.71 50167.44 29-DEC-12:40
                 
Annual Sum or Average 0.00         13654.68    
Minimum of Months 0.00 0.00   57.62 57.62 12219.48 44110.86  
Maximum of Months 0.00 0.00   58.21 58.21 15258.69 51150.72  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 19.57 13542.58 27-JAN-11:30 21.16 20.54 2388.66 114057.98 09-JAN-06:40
February 7311.12 727988.72 27-FEB-15:10 24.53 21.10 3222.69 106975.32 14-FEB-14:10
March 25692.02 654108.48 14-MAR-16:00 24.18 21.10 2875.54 115501.15 25-MAR-10:20
April 55242.99 2012446.78 27-APR-13:20 25.84 21.63 1188.21 90281.21 24-APR-07:00
May 82627.64 2082646.06 04-MAY-14:05 26.00 21.27 1159.86 87095.10 18-MAY-08:00
June 158560.32 2031796.66 22-JUN-14:50 25.89 21.13 1218.22 71141.49 06-JUN-13:30
July 290154.33 3036299.07 31-JUL-16:00 28.25 23.87 1365.26 61001.71 05-JUL-20:10
August 416735.04 3408623.84 29-AUG-14:30 29.13 24.55 1648.51 54102.30 12-AUG-05:30
September 142968.70 2509185.84 11-SEP-15:25 27.01 22.05 995.14 60229.61 19-SEP-19:20
October 42030.93 1310132.64 04-OCT-13:20 24.19 22.62 660.71 76899.06 13-OCT-09:40
November 5318.92 541067.29 04-NOV-14:10 23.65 21.10 3975.65 103289.52 16-NOV-08:50
December 272.53 37356.96 06-DEC-15:10 21.28 20.51 5206.09 105900.39 21-DEC-15:10
                 
Annual Sum or Average 103153.24         2153.41    
Minimum of Months 19.57 13542.58   21.16 20.51 660.71 54102.30  
Maximum of Months 416735.04 3408623.84   29.13 24.55 5206.09 115501.15  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.105507E+11 0.00 0.662817E+09 0.298771E+10 0.00 0.00
February 0.612950E+10 0.00 0.484643E+10 0.380679E+10 0.00 0.00
March 0.155890E+10 0.00 0.555053E+10 0.640259E+10 0.00 0.00
April 0.433108E+09 0.00 0.103958E+11 0.853373E+10 0.00 0.00
May 0.205463E+09 0.00 0.160577E+11 0.773967E+10 0.00 0.00
June 2373.51 0.00 0.314536E+11 0.959131E+10 0.00 0.00
July 1879.58 0.00 0.572943E+11 0.117247E+11 0.00 0.00
August 1101.32 0.00 0.778205E+11 0.135093E+11 0.00 0.00
September 16896838.74 0.00 0.249290E+11 0.787689E+10 0.00 0.00
October 0.236335E+09 0.00 0.465388E+10 0.634296E+10 0.00 0.00
November 0.259919E+10 0.00 0.496308E+10 0.464842E+10 0.00 0.00
December 0.555755E+10 0.00 0.583333E+10 0.441681E+10 0.00 0.00
             
Annual Sum or Average 0.272877E+11 0.00 0.244461E+12 0.875808E+11 0.00 0.00
Minimum of Months 1101.32 0.00 0.662817E+09 0.298771E+10 0.00 0.00
Maximum of Months 0.105507E+11 0.00 0.778205E+11 0.135093E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.218497E+12 0.00 30746.79 0.212418E+11 0.00 0.00
February 0.118615E+12 0.00 0.142385E+11 0.229624E+11 0.00 0.00
March 0.478963E+11 0.00 0.598878E+11 0.342378E+11 0.00 0.00
April 0.212475E+11 0.00 0.966835E+11 0.431877E+11 0.00 0.00
May 0.538729E+10 0.00 0.146480E+12 0.566557E+11 0.00 0.00
June 0.261183E+09 0.00 0.258587E+12 0.653667E+11 0.00 0.00
July 69717979.03 0.00 0.453434E+12 0.759957E+11 0.00 0.00
August 58466055.14 0.00 0.599350E+12 0.861516E+11 0.00 0.00
September 0.894890E+09 0.00 0.235719E+12 0.591615E+11 0.00 0.00
October 0.100942E+11 0.00 0.881890E+11 0.378919E+11 0.00 0.00
November 0.800066E+11 0.00 0.103491E+11 0.236868E+11 0.00 0.00
December 0.165905E+12 0.00 28104.41 0.222098E+11 0.00 0.00
             
Annual Sum or Average 0.668933E+12 0.00 0.196292E+13 0.548749E+12 0.00 0.00
Minimum of Months 58466055.14 0.00 28104.41 0.212418E+11 0.00 0.00
Maximum of Months 0.218497E+12 0.00 0.599350E+12 0.861516E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.386596E+11 0.00 0.00 0.260802E+10 0.00 0.00
February 0.225732E+11 0.00 0.390035E+09 0.227017E+10 0.00 0.00
March 0.103182E+11 0.00 0.101644E+10 0.269275E+10 0.00 0.00
April 0.402313E+10 0.00 0.764622E+10 0.347707E+10 0.00 0.00
May 0.988789E+09 0.00 0.141105E+11 0.475903E+10 0.00 0.00
June 45248181.10 0.00 0.268694E+11 0.587594E+10 0.00 0.00
July 0.00 0.00 0.481077E+11 0.716347E+10 0.00 0.00
August 0.00 0.00 0.632128E+11 0.796032E+10 0.00 0.00
September 0.226341E+09 0.00 0.215210E+11 0.486559E+10 0.00 0.00
October 0.371852E+10 0.00 0.309679E+10 0.284448E+10 0.00 0.00
November 0.171442E+11 0.00 0.516383E+09 0.213329E+10 0.00 0.00
December 0.318468E+11 0.00 26462.81 0.232991E+10 0.00 0.00
             
Annual Sum or Average 0.129544E+12 0.00 0.186487E+12 0.489800E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.213329E+10 0.00 0.00
Maximum of Months 0.386596E+11 0.00 0.632128E+11 0.796032E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.161601E+10 0.00 44228642.85 0.421154E+10 0.00 0.00
February 0.572126E+09 0.00 0.969962E+09 0.643575E+10 0.00 0.00
March 10994398.98 0.00 0.674618E+09 0.114253E+11 0.00 0.00
April 255.55 0.00 0.456647E+10 0.131443E+11 0.00 0.00
May 125523.05 0.00 0.970129E+10 0.128127E+11 0.00 0.00
June 1292.43 0.00 0.206019E+11 0.116715E+11 0.00 0.00
July 1384.97 0.00 0.374619E+11 0.956931E+10 0.00 0.00
August 591.71 0.00 0.481420E+11 0.118823E+11 0.00 0.00
September 552.23 0.00 0.172572E+11 0.114890E+11 0.00 0.00
October 571.52 0.00 0.288060E+10 0.133507E+11 0.00 0.00
November 17.83 0.00 0.560913E+09 0.130382E+11 0.00 0.00
December 0.105634E+09 0.00 9118321.70 0.112970E+11 0.00 0.00
             
Annual Sum or Average 0.230490E+10 0.00 0.142870E+12 0.130328E+12 0.00 0.00
Minimum of Months 17.83 0.00 9118321.70 0.421154E+10 0.00 0.00
Maximum of Months 0.161601E+10 0.00 0.481420E+11 0.133507E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.822913E+10 0.206435E+12 0.00 34.66
February 0.00 0.00 0.109224E+11 0.236101E+12 0.00 49.49
March 0.00 0.00 0.176526E+11 0.296476E+12 0.00 67.37
April 0.00 0.00 0.100504E+12 0.286467E+12 0.00 58.27
May 0.00 0.00 0.813806E+10 0.149624E+12 0.00 13.48
June 0.00 0.00 0.454491E+11 0.141222E+12 0.00 8.53
July 0.00 0.00 0.267712E+12 0.190877E+12 0.00 8.22
August 0.00 0.00 0.677334E+12 0.253603E+12 0.00 0.29
September 0.00 0.00 0.728504E+10 0.111637E+12 0.00 0.64
October 0.00 0.00 0.752828E+10 0.168773E+12 0.00 20.65
November 0.00 0.00 0.151615E+11 0.230822E+12 0.00 44.50
December 0.00 0.00 0.192834E+11 0.336944E+12 0.00 82.26
             
Annual Sum or Average 0.00 0.00 0.118520E+13 0.260898E+13 0.00 388.36
Minimum of Months 0.00 0.00 0.728504E+10 0.111637E+12 0.00 0.29
Maximum of Months 0.00 0.00 0.677334E+12 0.336944E+12 0.00 82.26



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.505833E+10 0.249225E+10 0.00 0.00
February 0.00 0.00 0.107559E+11 0.332828E+10 0.00 0.00
March 0.00 0.00 0.185279E+11 0.475370E+10 0.00 0.00
April 0.00 0.00 0.240802E+11 0.555573E+10 0.00 0.00
May 0.00 0.00 0.690316E+10 0.280466E+10 0.00 0.00
June 0.00 0.00 0.128624E+11 0.377736E+10 0.00 0.00
July 0.00 0.00 0.198336E+11 0.508229E+10 0.00 0.00
August 0.00 0.00 0.260375E+11 0.626678E+10 0.00 0.00
September 0.00 0.00 0.687447E+10 0.273860E+10 0.00 0.00
October 0.00 0.00 0.126731E+11 0.376043E+10 0.00 0.00
November 0.00 0.00 0.177712E+11 0.453328E+10 0.00 0.00
December 0.00 0.00 0.241430E+11 0.562435E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.185521E+12 0.507177E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.505833E+10 0.249225E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.260375E+11 0.626678E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.194049E+11 0.185349E+11 0.00 0.00
February 0.00 0.00 0.824425E+11 0.283939E+11 0.00 0.00
March 0.00 0.00 0.162826E+12 0.432538E+11 0.00 0.00
April 0.00 0.00 0.221621E+12 0.519128E+11 0.00 0.00
May 0.00 0.00 0.597064E+11 0.257848E+11 0.00 0.00
June 0.00 0.00 0.118334E+12 0.354276E+11 0.00 0.00
July 0.00 0.00 0.186590E+12 0.481928E+11 0.00 0.00
August 0.00 0.00 0.246595E+12 0.596455E+11 0.00 0.00
September 0.00 0.00 0.599508E+11 0.252523E+11 0.00 0.00
October 0.00 0.00 0.108832E+12 0.339968E+11 0.00 0.00
November 0.00 0.00 0.150076E+12 0.402871E+11 0.00 0.00
December 0.00 0.00 0.203969E+12 0.497602E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.162035E+13 0.460442E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.194049E+11 0.185349E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.246595E+12 0.596455E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.617230E+09 0.160818E+10 0.00 0.00
February 0.00 0.00 0.628086E+10 0.251142E+10 0.00 0.00
March 0.00 0.00 0.147449E+11 0.410057E+10 0.00 0.00
April 0.00 0.00 0.212909E+11 0.508620E+10 0.00 0.00
May 0.00 0.00 0.539862E+10 0.250035E+10 0.00 0.00
June 0.00 0.00 0.115980E+11 0.352835E+10 0.00 0.00
July 0.00 0.00 0.185399E+11 0.482973E+10 0.00 0.00
August 0.00 0.00 0.245236E+11 0.597650E+10 0.00 0.00
September 0.00 0.00 0.541176E+10 0.244604E+10 0.00 0.00
October 0.00 0.00 0.949598E+10 0.319071E+10 0.00 0.00
November 0.00 0.00 0.130177E+11 0.373062E+10 0.00 0.00
December 0.00 0.00 0.180771E+11 0.463850E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.148996E+12 0.441472E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.617230E+09 0.160818E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.245236E+11 0.597650E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.298771E+10 0.662817E+09 0.105507E+11 0.00 0.00 0.00 0.00 0.00
February 0.380679E+10 0.484643E+10 0.612950E+10 0.00 0.00 0.00 0.00 0.00
March 0.640259E+10 0.555053E+10 0.155890E+10 0.00 0.00 0.00 0.00 0.00
April 0.853373E+10 0.103958E+11 0.433108E+09 0.00 0.00 0.00 0.00 0.00
May 0.773967E+10 0.160577E+11 0.205463E+09 0.00 0.00 0.00 0.00 0.00
June 0.959131E+10 0.314536E+11 2373.51 0.00 0.00 0.00 0.00 0.00
July 0.117247E+11 0.572943E+11 1879.58 0.00 0.00 0.00 0.00 0.00
August 0.135093E+11 0.778205E+11 1101.32 0.00 0.00 0.00 0.00 0.00
September 0.787689E+10 0.249290E+11 16896838.74 0.00 0.00 0.00 0.00 0.00
October 0.634296E+10 0.465388E+10 0.236335E+09 0.00 0.00 0.00 0.00 0.00
November 0.464842E+10 0.496308E+10 0.259919E+10 0.00 0.00 0.00 0.00 0.00
December 0.441681E+10 0.583333E+10 0.555755E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.875808E+11 0.244461E+12 0.272877E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.298771E+10 0.662817E+09 1101.32 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135093E+11 0.778205E+11 0.105507E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.212418E+11 30746.79 0.218497E+12 0.00 0.00 0.00 0.00 0.00
February 0.229624E+11 0.142385E+11 0.118615E+12 0.00 0.00 0.00 0.00 0.00
March 0.342378E+11 0.598878E+11 0.478963E+11 0.00 0.00 0.00 0.00 0.00
April 0.431877E+11 0.966835E+11 0.212475E+11 0.00 0.00 0.00 0.00 0.00
May 0.566557E+11 0.146480E+12 0.538729E+10 0.00 0.00 0.00 0.00 0.00
June 0.653667E+11 0.258587E+12 0.261183E+09 0.00 0.00 0.00 0.00 0.00
July 0.759957E+11 0.453434E+12 69717979.03 0.00 0.00 0.00 0.00 0.00
August 0.861516E+11 0.599350E+12 58466055.14 0.00 0.00 0.00 0.00 0.00
September 0.591615E+11 0.235719E+12 0.894890E+09 0.00 0.00 0.00 0.00 0.00
October 0.378919E+11 0.881890E+11 0.100942E+11 0.00 0.00 0.00 0.00 0.00
November 0.236868E+11 0.103491E+11 0.800066E+11 0.00 0.00 0.00 0.00 0.00
December 0.222098E+11 28104.41 0.165905E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.548749E+12 0.196292E+13 0.668933E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.212418E+11 28104.41 58466055.14 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.861516E+11 0.599350E+12 0.218497E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.260802E+10 0.00 0.386596E+11 0.00 0.00 0.00 0.00 0.00
February 0.227017E+10 0.390035E+09 0.225732E+11 0.00 0.00 0.00 0.00 0.00
March 0.269275E+10 0.101644E+10 0.103182E+11 0.00 0.00 0.00 0.00 0.00
April 0.347707E+10 0.764622E+10 0.402313E+10 0.00 0.00 0.00 0.00 0.00
May 0.475903E+10 0.141105E+11 0.988789E+09 0.00 0.00 0.00 0.00 0.00
June 0.587594E+10 0.268694E+11 45248181.10 0.00 0.00 0.00 0.00 0.00
July 0.716347E+10 0.481077E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.796032E+10 0.632128E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.486559E+10 0.215210E+11 0.226341E+09 0.00 0.00 0.00 0.00 0.00
October 0.284448E+10 0.309679E+10 0.371852E+10 0.00 0.00 0.00 0.00 0.00
November 0.213329E+10 0.516383E+09 0.171442E+11 0.00 0.00 0.00 0.00 0.00
December 0.232991E+10 26462.81 0.318468E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.489800E+11 0.186487E+12 0.129544E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.213329E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.796032E+10 0.632128E+11 0.386596E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.421154E+10 44228642.85 0.161601E+10 0.00 0.00 0.00 0.00 0.00
February 0.643575E+10 0.969962E+09 0.572126E+09 0.00 0.00 0.00 0.00 0.00
March 0.114253E+11 0.674618E+09 10994398.98 0.00 0.00 0.00 0.00 0.00
April 0.131443E+11 0.456647E+10 255.55 0.00 0.00 0.00 0.00 0.00
May 0.128127E+11 0.970129E+10 125523.05 0.00 0.00 0.00 0.00 0.00
June 0.116715E+11 0.206019E+11 1292.43 0.00 0.00 0.00 0.00 0.00
July 0.956931E+10 0.374619E+11 1384.97 0.00 0.00 0.00 0.00 0.00
August 0.118823E+11 0.481420E+11 591.71 0.00 0.00 0.00 0.00 0.00
September 0.114890E+11 0.172572E+11 552.23 0.00 0.00 0.00 0.00 0.00
October 0.133507E+11 0.288060E+10 571.52 0.00 0.00 0.00 0.00 0.00
November 0.130382E+11 0.560913E+09 17.83 0.00 0.00 0.00 0.00 0.00
December 0.112970E+11 9118321.70 0.105634E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.130328E+12 0.142870E+12 0.230490E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.421154E+10 9118321.70 17.83 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133507E+11 0.481420E+11 0.161601E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.109549E+12 0.451994E+10 0.00 0.00 0.00 0.927592E+11 0.00 0.00
February 0.989479E+11 0.679760E+10 0.00 0.00 0.00 0.132432E+12 0.00 0.00
March 0.109549E+12 0.118246E+11 0.00 0.00 0.00 0.180287E+12 0.00 0.00
April 0.106016E+12 0.766841E+11 0.00 0.00 0.00 0.155929E+12 0.00 0.00
May 0.109549E+12 0.430446E+10 0.00 0.00 0.00 0.360784E+11 0.00 0.00
June 0.106016E+12 0.331722E+11 0.00 0.00 0.00 0.228271E+11 0.00 0.00
July 0.109549E+12 0.208486E+12 0.00 0.00 0.00 0.220017E+11 0.00 0.00
August 0.109549E+12 0.534071E+12 0.00 0.00 0.00 0.786639E+09 0.00 0.00
September 0.106016E+12 0.339362E+10 0.00 0.00 0.00 0.172204E+10 0.00 0.00
October 0.109549E+12 0.380186E+10 0.00 0.00 0.00 0.552489E+11 0.00 0.00
November 0.106016E+12 0.997547E+10 0.00 0.00 0.00 0.119084E+12 0.00 0.00
December 0.109549E+12 0.130203E+11 0.00 0.00 0.00 0.220141E+12 0.00 0.00
                 
Annual Sum or Average 0.128986E+13 0.910050E+12 0.00 0.00 0.00 0.103930E+13 0.00 0.00
Minimum of Months 0.989479E+11 0.339362E+10 0.00 0.00 0.00 0.786639E+09 0.00 0.00
Maximum of Months 0.109549E+12 0.534071E+12 0.00 0.00 0.00 0.220141E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.151276E+10 0.407884E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136636E+10 0.879396E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.151276E+10 0.152870E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.146396E+10 0.199884E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.151276E+10 0.561126E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.146396E+10 0.105490E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.151276E+10 0.162641E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.151276E+10 0.212835E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.146396E+10 0.559983E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.151276E+10 0.104255E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.146396E+10 0.147019E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.151276E+10 0.200314E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178115E+11 0.152615E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136636E+10 0.407884E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.151276E+10 0.212835E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.145267E+11 0.153967E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.131209E+11 0.671695E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145267E+11 0.134099E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.140581E+11 0.183766E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.145267E+11 0.484483E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140581E+11 0.969641E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.145267E+11 0.152924E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145267E+11 0.201476E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.140581E+11 0.487566E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145267E+11 0.893620E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.140581E+11 0.123847E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.145267E+11 0.168736E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.171040E+12 0.133094E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.131209E+11 0.153967E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145267E+11 0.201476E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.147436E+10 0.483413E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133168E+10 0.510112E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147436E+10 0.121187E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142680E+10 0.176315E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147436E+10 0.437263E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142680E+10 0.949641E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147436E+10 0.151845E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147436E+10 0.200214E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142680E+10 0.439253E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147436E+10 0.777963E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142680E+10 0.107139E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147436E+10 0.149130E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173594E+11 0.122209E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133168E+10 0.483413E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147436E+10 0.200214E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.298771E+10 0.105507E+11 0.662817E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.380679E+10 0.612950E+10 0.484643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.640259E+10 0.155890E+10 0.555053E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.853373E+10 0.433108E+09 0.103958E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.773967E+10 0.205463E+09 0.160577E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.959131E+10 2373.51 0.314536E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.117247E+11 1879.58 0.572943E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135093E+11 1101.32 0.778205E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.787689E+10 16896838.74 0.249290E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.634296E+10 0.236335E+09 0.465388E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.464842E+10 0.259919E+10 0.496308E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.441681E+10 0.555755E+10 0.583333E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.875808E+11 0.272877E+11 0.244461E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.298771E+10 1101.32 0.662817E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135093E+11 0.105507E+11 0.778205E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.212418E+11 0.218497E+12 30746.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.229624E+11 0.118615E+12 0.142385E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.342378E+11 0.478963E+11 0.598878E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.431877E+11 0.212475E+11 0.966835E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.566557E+11 0.538729E+10 0.146480E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.653667E+11 0.261183E+09 0.258587E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.759957E+11 69717979.03 0.453434E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.861516E+11 58466055.14 0.599350E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.591615E+11 0.894890E+09 0.235719E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.378919E+11 0.100942E+11 0.881890E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.236868E+11 0.800066E+11 0.103491E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.222098E+11 0.165905E+12 28104.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.548749E+12 0.668933E+12 0.196292E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.212418E+11 58466055.14 28104.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.861516E+11 0.218497E+12 0.599350E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.260802E+10 0.386596E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.227017E+10 0.225732E+11 0.390035E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.269275E+10 0.103182E+11 0.101644E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.347707E+10 0.402313E+10 0.764622E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.475903E+10 0.988789E+09 0.141105E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.587594E+10 45248181.10 0.268694E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.716347E+10 0.00 0.481077E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.796032E+10 0.00 0.632128E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.486559E+10 0.226341E+09 0.215210E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.284448E+10 0.371852E+10 0.309679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.213329E+10 0.171442E+11 0.516383E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.232991E+10 0.318468E+11 26462.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.489800E+11 0.129544E+12 0.186487E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.213329E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.796032E+10 0.386596E+11 0.632128E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.421154E+10 0.161601E+10 44228642.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643575E+10 0.572126E+09 0.969962E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.114253E+11 10994398.98 0.674618E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131443E+11 255.55 0.456647E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.128127E+11 125523.05 0.970129E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.116715E+11 1292.43 0.206019E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.956931E+10 1384.97 0.374619E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.118823E+11 591.71 0.481420E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.114890E+11 552.23 0.172572E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133507E+11 571.52 0.288060E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.130382E+11 17.83 0.560913E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.112970E+11 0.105634E+09 9118321.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.130328E+12 0.230490E+10 0.142870E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.421154E+10 17.83 9118321.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133507E+11 0.161601E+10 0.481420E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.109549E+12 0.00 0.822913E+10 0.00 0.370919E+10 0.00 0.00 0.00 0.931767E+11 0.00 0.00 0.00
February 0.989479E+11 0.00 0.109224E+11 0.00 0.412479E+10 0.00 0.00 0.00 0.133028E+12 0.00 0.00 0.00
March 0.109549E+12 0.00 0.176526E+11 0.00 0.582800E+10 0.00 0.00 0.00 0.181099E+12 0.00 0.00 0.00
April 0.106016E+12 0.00 0.100504E+12 0.00 0.238198E+11 0.00 0.00 0.00 0.156631E+12 0.00 0.00 0.00
May 0.109549E+12 0.00 0.813806E+10 0.00 0.383360E+10 0.00 0.00 0.00 0.362408E+11 0.00 0.00 0.00
June 0.106016E+12 0.00 0.454491E+11 0.00 0.122768E+11 0.00 0.00 0.00 0.229298E+11 0.00 0.00 0.00
July 0.109549E+12 0.00 0.267712E+12 0.00 0.592265E+11 0.00 0.00 0.00 0.221007E+11 0.00 0.00 0.00
August 0.109549E+12 0.00 0.677334E+12 0.00 0.143263E+12 0.00 0.00 0.00 0.790180E+09 0.00 0.00 0.00
September 0.106016E+12 0.00 0.728504E+10 0.00 0.389142E+10 0.00 0.00 0.00 0.172979E+10 0.00 0.00 0.00
October 0.109549E+12 0.00 0.752828E+10 0.00 0.372642E+10 0.00 0.00 0.00 0.554976E+11 0.00 0.00 0.00
November 0.106016E+12 0.00 0.151615E+11 0.00 0.518603E+10 0.00 0.00 0.00 0.119620E+12 0.00 0.00 0.00
December 0.109549E+12 0.00 0.192834E+11 0.00 0.626312E+10 0.00 0.00 0.00 0.221132E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.128986E+13 0.00 0.118520E+13 0.00 0.275149E+12 0.00 0.00 0.00 0.104398E+13 0.00 0.00 0.00
Minimum of Months 0.989479E+11 0.00 0.728504E+10 0.00 0.370919E+10 0.00 0.00 0.00 0.790180E+09 0.00 0.00 0.00
Maximum of Months 0.109549E+12 0.00 0.677334E+12 0.00 0.143263E+12 0.00 0.00 0.00 0.221132E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.151276E+10 0.00 0.505833E+10 0.00 0.979488E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136636E+10 0.00 0.107559E+11 0.00 0.196192E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.151276E+10 0.00 0.185279E+11 0.00 0.324094E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.146396E+10 0.00 0.240802E+11 0.00 0.409177E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.151276E+10 0.00 0.690316E+10 0.00 0.129190E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.146396E+10 0.00 0.128624E+11 0.00 0.231340E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.151276E+10 0.00 0.198336E+11 0.00 0.356953E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.151276E+10 0.00 0.260375E+11 0.00 0.475402E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.146396E+10 0.00 0.687447E+10 0.00 0.127464E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.151276E+10 0.00 0.126731E+11 0.00 0.224767E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.146396E+10 0.00 0.177712E+11 0.00 0.306932E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.151276E+10 0.00 0.241430E+11 0.00 0.411159E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.178115E+11 0.00 0.185521E+12 0.00 0.329062E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136636E+10 0.00 0.505833E+10 0.00 0.979488E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.151276E+10 0.00 0.260375E+11 0.00 0.475402E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.145267E+11 0.00 0.194049E+11 0.00 0.400823E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.131209E+11 0.00 0.824425E+11 0.00 0.152730E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145267E+11 0.00 0.162826E+12 0.00 0.287271E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.140581E+11 0.00 0.221621E+12 0.00 0.378548E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.145267E+11 0.00 0.597064E+11 0.00 0.112581E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140581E+11 0.00 0.118334E+12 0.00 0.213695E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.145267E+11 0.00 0.186590E+12 0.00 0.336661E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145267E+11 0.00 0.246595E+12 0.00 0.451188E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.140581E+11 0.00 0.599508E+11 0.00 0.111942E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145267E+11 0.00 0.108832E+12 0.00 0.194702E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.140581E+11 0.00 0.150076E+12 0.00 0.262290E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.145267E+11 0.00 0.203969E+12 0.00 0.352336E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.171040E+12 0.00 0.162035E+13 0.00 0.289403E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.131209E+11 0.00 0.194049E+11 0.00 0.400823E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145267E+11 0.00 0.246595E+12 0.00 0.451188E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.147436E+10 0.00 0.617230E+09 0.00 0.133817E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133168E+10 0.00 0.628086E+10 0.00 0.117974E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147436E+10 0.00 0.147449E+11 0.00 0.262621E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142680E+10 0.00 0.212909E+11 0.00 0.365939E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147436E+10 0.00 0.539862E+10 0.00 0.102599E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142680E+10 0.00 0.115980E+11 0.00 0.210155E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147436E+10 0.00 0.185399E+11 0.00 0.335536E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147436E+10 0.00 0.245236E+11 0.00 0.450214E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142680E+10 0.00 0.541176E+10 0.00 0.101924E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147436E+10 0.00 0.949598E+10 0.00 0.171635E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142680E+10 0.00 0.130177E+11 0.00 0.230381E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147436E+10 0.00 0.180771E+11 0.00 0.316414E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.173594E+11 0.00 0.148996E+12 0.00 0.267877E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133168E+10 0.00 0.617230E+09 0.00 0.133817E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147436E+10 0.00 0.245236E+11 0.00 0.450214E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 81063558.94 0.00 0.00 0.536014E+11 0.00 0.44
February 0.00 0.00 0.00 81705285.48 0.00 0.00 0.519371E+11 0.00 0.56
March 0.00 0.00 0.00 0.107170E+09 0.00 0.00 0.688105E+11 0.00 0.76
April 0.00 23488631.05 0.00 0.102212E+09 0.00 0.00 0.639458E+11 0.00 0.88
May 0.00 9329317.63 0.00 0.118260E+09 0.00 0.00 0.604925E+11 0.00 1.03
June 0.00 13641715.23 0.00 0.129662E+09 0.00 0.00 0.506447E+11 0.00 1.15
July 0.00 0.478724E+09 0.00 0.126507E+09 0.00 0.00 0.320262E+11 0.00 0.95
August 0.00 0.686978E+09 0.00 0.127494E+09 0.00 0.00 0.300391E+11 0.00 0.98
September 0.00 0.00 0.00 0.121101E+09 0.00 0.00 0.512592E+11 0.00 1.10
October 0.00 0.00 0.00 0.117949E+09 0.00 0.00 0.690120E+11 0.00 0.95
November 0.00 0.00 0.00 0.105575E+09 0.00 0.00 0.682478E+11 0.00 0.74
December 0.00 0.00 0.00 95140853.77 0.00 0.00 0.644312E+11 0.00 0.56
                   
Annual Sum or Average 0.00 0.121216E+10 0.00 0.131384E+10 0.00 0.00 0.664448E+12 0.00 0.84
Minimum of Months 0.00 0.00 0.00 81063558.94 0.00 0.00 0.300391E+11 0.00 0.44
Maximum of Months 0.00 0.686978E+09 0.00 0.129662E+09 0.00 0.00 0.690120E+11 0.00 1.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.201658E+10 0.00 0.00 58615907.63 0.00 0.00 0.465961E+11 0.00 0.38
February 0.165351E+10 0.00 0.00 69823779.62 0.00 0.00 0.438718E+11 0.00 0.46
March 0.159916E+10 0.00 0.00 0.102234E+09 0.00 0.00 0.578852E+11 0.00 0.61
April 0.465654E+10 17062322.38 0.00 0.102231E+09 0.00 0.00 0.565114E+11 0.00 0.79
May 0.323114E+10 499077.79 0.00 96719026.90 0.00 0.00 0.512657E+11 0.00 0.83
June 0.297146E+10 16645631.03 0.00 0.107950E+09 5959544.45 0.00 0.488485E+11 0.00 1.01
July 0.766528E+10 0.150487E+09 0.00 0.104576E+09 3561673.20 0.00 0.371459E+11 0.00 1.04
August 0.868931E+10 0.533953E+09 0.00 0.102409E+09 6981390.21 0.00 0.346062E+11 0.00 1.08
September 0.254856E+10 0.00 0.00 96094254.54 0.00 0.00 0.449850E+11 0.00 0.88
October 0.226188E+10 0.00 0.00 95533838.02 0.00 0.00 0.551488E+11 0.00 0.73
November 0.172931E+10 0.00 0.00 87976549.75 0.00 0.00 0.518260E+11 0.00 0.54
December 0.159617E+10 0.00 0.00 87546745.31 0.00 0.00 0.504487E+11 0.00 0.43
                   
Annual Sum or Average 0.406189E+11 0.718647E+09 0.00 0.111171E+10 16502607.86 0.00 0.579139E+12 0.00 0.73
Minimum of Months 0.159617E+10 0.00 0.00 58615907.63 0.00 0.00 0.346062E+11 0.00 0.38
Maximum of Months 0.868931E+10 0.533953E+09 0.00 0.107950E+09 6981390.21 0.00 0.578852E+11 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.251895E+12 0.00 0.00 91114725.99 0.00 0.169363E+10 0.109093E+12 0.00 0.30
February 0.158665E+12 0.00 0.00 0.206113E+09 0.00 0.00 0.174465E+12 0.00 0.33
March 0.900257E+11 0.00 0.00 0.448309E+09 0.00 0.00 0.301934E+12 0.00 0.39
April 0.476393E+11 0.161823E+09 0.00 0.512921E+09 39922542.36 0.00 0.328093E+12 0.00 0.49
May 0.319445E+11 5014107.88 0.00 0.697740E+09 0.00 0.00 0.393066E+12 0.00 0.66
June 0.235184E+11 0.134810E+09 0.00 0.773113E+09 26350896.77 0.00 0.366405E+12 0.00 0.77
July 0.299093E+11 0.111913E+10 0.00 0.730413E+09 39111949.37 0.00 0.271058E+12 0.00 0.73
August 0.191532E+11 0.456136E+10 0.00 0.751325E+09 44407693.18 0.00 0.255149E+12 0.00 0.72
September 0.260235E+11 0.00 0.00 0.691634E+09 0.00 0.00 0.332163E+12 0.00 0.68
October 0.602020E+11 0.00 0.00 0.504179E+09 0.00 0.00 0.303772E+12 0.00 0.45
November 0.118190E+12 0.00 0.00 0.288549E+09 0.00 0.00 0.242847E+12 0.00 0.36
December 0.197670E+12 0.00 0.00 0.168135E+09 0.00 16442322.04 0.166646E+12 0.00 0.31
                   
Annual Sum or Average 0.105484E+13 0.598215E+10 0.00 0.586354E+10 0.149793E+09 0.171007E+10 0.324469E+13 0.00 0.52
Minimum of Months 0.191532E+11 0.00 0.00 91114725.99 0.00 0.00 0.109093E+12 0.00 0.30
Maximum of Months 0.251895E+12 0.456136E+10 0.00 0.773113E+09 44407693.18 0.169363E+10 0.393066E+12 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.297180E+11 0.00 0.00 151718.25 0.00 0.157030E+10 0.503929E+09 0.00 0.29
February 0.237086E+11 0.00 0.00 3489805.56 0.00 0.746779E+09 0.381377E+10 0.00 0.31
March 0.193962E+11 0.00 0.00 14229502.84 0.00 0.133095E+09 0.135353E+11 0.00 0.36
April 0.113977E+11 4332014.68 0.00 29071743.05 834274.49 0.00 0.212792E+11 0.00 0.44
May 0.762823E+10 0.00 0.00 48933580.31 0.00 0.00 0.312409E+11 0.00 0.61
June 0.429617E+10 5307721.03 0.00 62730322.96 1396648.56 0.00 0.331151E+11 0.00 0.75
July 0.349376E+10 58240279.99 0.00 64638459.10 2215727.42 0.00 0.259533E+11 0.00 0.74
August 0.294884E+10 0.295314E+09 0.00 65378637.28 11962029.03 0.00 0.223574E+11 0.00 0.70
September 0.679160E+10 0.00 0.00 45299321.37 0.00 0.00 0.243637E+11 0.00 0.62
October 0.135421E+11 0.00 0.00 20595644.61 0.00 16365201.51 0.163813E+11 0.00 0.40
November 0.225162E+11 0.00 0.00 4916130.57 0.00 0.412998E+09 0.547099E+10 0.00 0.31
December 0.283839E+11 0.00 0.00 267615.68 0.00 0.103547E+10 0.820919E+09 0.00 0.29
                   
Annual Sum or Average 0.173821E+12 0.363194E+09 0.00 0.359702E+09 16408679.50 0.391501E+10 0.198836E+12 0.00 0.49
Minimum of Months 0.294884E+10 0.00 0.00 151718.25 0.00 0.00 0.503929E+09 0.00 0.29
Maximum of Months 0.297180E+11 0.295314E+09 0.00 65378637.28 11962029.03 0.157030E+10 0.331151E+11 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.412716E+10 0.00 0.00 77906.75 0.00 0.00 0.160716E+09 0.00 0.27
February 0.295690E+10 0.00 0.00 1053079.07 0.00 0.00 0.870750E+09 0.00 0.31
March 0.203195E+10 0.00 0.00 4177858.54 0.00 0.00 0.298444E+10 0.00 0.42
April 0.146769E+10 2781644.59 0.00 7117872.79 0.00 0.00 0.461327E+10 0.00 0.66
May 0.102589E+10 132685.15 0.00 9428170.56 0.00 0.00 0.547224E+10 0.00 0.85
June 0.562313E+09 3035837.66 0.00 12750454.68 748802.56 0.00 0.607674E+10 0.00 1.11
July 0.106938E+10 27885729.28 0.00 13350698.83 447515.75 0.00 0.490262E+10 0.00 1.19
August 0.119041E+10 95685989.01 0.00 12234154.04 877195.04 0.00 0.417183E+10 0.00 1.15
September 0.951281E+09 0.00 0.00 7875766.40 0.00 0.00 0.401514E+10 0.00 0.79
October 0.173254E+10 0.00 0.00 4484951.13 0.00 0.00 0.320239E+10 0.00 0.51
November 0.228475E+10 0.00 0.00 2155157.62 0.00 0.00 0.176368E+10 0.00 0.33
December 0.313817E+10 0.00 0.00 592951.91 0.00 0.00 0.691125E+09 0.00 0.25
                   
Annual Sum or Average 0.225384E+11 0.129522E+09 0.00 75299022.31 2073513.35 0.00 0.389249E+11 0.00 0.66
Minimum of Months 0.562313E+09 0.00 0.00 77906.75 0.00 0.00 0.160716E+09 0.00 0.25
Maximum of Months 0.412716E+10 95685989.01 0.00 13350698.83 877195.04 0.00 0.607674E+10 0.00 1.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.261820E+10 0.00 0.00 182810.24 0.00 8404943.59 0.161546E+09 0.00 0.27
February 0.178138E+10 0.00 0.00 1441401.77 0.00 162027.69 0.861975E+09 0.00 0.33
March 0.127815E+10 0.00 0.00 4720580.96 0.00 0.00 0.267037E+10 0.00 0.50
April 0.908919E+09 2137245.41 0.00 7930300.25 0.00 0.00 0.465788E+10 0.00 0.93
May 0.608500E+09 106448.49 0.00 10352901.04 0.00 0.00 0.535783E+10 0.00 1.20
June 0.341003E+09 1928048.70 0.00 13863732.28 483964.46 0.00 0.628719E+10 0.00 1.64
July 0.665781E+09 21704911.91 0.00 13942141.93 289237.42 0.00 0.460644E+10 0.00 1.62
August 0.800237E+09 74468855.83 0.00 13122677.29 98436.46 0.00 0.401990E+10 0.00 1.62
September 0.555832E+09 0.00 0.00 9414692.89 0.00 0.00 0.430964E+10 0.00 1.20
October 0.108620E+10 0.00 0.00 4870966.49 0.00 0.00 0.307108E+10 0.00 0.67
November 0.160960E+10 0.00 0.00 1468468.94 0.00 0.00 0.102359E+10 0.00 0.33
December 0.222213E+10 0.00 0.00 497770.42 0.00 0.00 0.289749E+09 0.00 0.25
                   
Annual Sum or Average 0.144759E+11 0.100346E+09 0.00 81808444.50 871638.34 8566971.28 0.373172E+11 0.00 0.88
Minimum of Months 0.341003E+09 0.00 0.00 182810.24 0.00 0.00 0.161546E+09 0.00 0.25
Maximum of Months 0.261820E+10 74468855.83 0.00 13942141.93 483964.46 8404943.59 0.628719E+10 0.00 1.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.342018E+10 0.00 0.00 2692372.44 0.00 0.132449E+09 0.176821E+10 0.00 0.33
February 0.243192E+10 0.00 0.00 6653142.23 0.00 26788640.66 0.326771E+10 0.00 0.48
March 0.173353E+10 0.00 0.00 11921247.78 0.00 0.00 0.729539E+10 0.00 0.78
April 0.130765E+10 7221232.01 0.00 14677040.86 0.00 0.00 0.842566E+10 0.00 1.14
May 0.101232E+10 249237.54 0.00 15790558.26 0.00 0.00 0.798701E+10 0.00 1.25
June 0.633918E+09 3577794.08 0.00 16934325.17 750370.88 0.00 0.738968E+10 0.00 1.42
July 0.101159E+10 48003681.76 0.00 18883447.01 448453.05 0.00 0.618744E+10 0.00 1.58
August 0.119919E+10 0.184915E+09 0.00 18644983.46 82497.40 0.00 0.542383E+10 0.00 1.58
September 0.764946E+09 0.00 0.00 21240081.24 0.00 0.00 0.797529E+10 0.00 1.61
October 0.133066E+10 0.00 0.00 14321153.22 0.00 0.00 0.829066E+10 0.00 1.08
November 0.232674E+10 0.00 0.00 5623924.93 0.00 0.00 0.287328E+10 0.00 0.45
December 0.284293E+10 0.00 0.00 4804071.95 0.00 28179340.90 0.244064E+10 0.00 0.36
                   
Annual Sum or Average 0.200156E+11 0.243967E+09 0.00 0.152186E+09 1281321.32 0.187417E+09 0.693248E+11 0.00 1.01
Minimum of Months 0.633918E+09 0.00 0.00 2692372.44 0.00 0.00 0.176821E+10 0.00 0.33
Maximum of Months 0.342018E+10 0.184915E+09 0.00 21240081.24 750370.88 0.132449E+09 0.842566E+10 0.00 1.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.178473E+10 0.00 0.00 1586207.65 0.00 0.00 0.132798E+10 0.00 0.30
February 0.644246E+09 0.00 0.00 5033504.68 0.00 0.00 0.322480E+10 0.00 0.51
March 0.154582E+09 0.00 0.00 11853642.34 0.00 0.00 0.727160E+10 0.00 1.00
April 0.159831E+09 5142477.65 0.00 18321521.96 0.00 0.00 0.952356E+10 0.00 1.69
May 0.189321E+09 140311.65 0.00 18683814.45 0.00 0.00 0.756147E+10 0.00 1.71
June 0.129910E+09 8872256.41 0.00 20539709.41 342534.40 0.00 0.780999E+10 0.00 2.19
July 0.292952E+09 57664077.68 0.00 25412358.52 37026.95 0.00 0.749262E+10 0.00 2.61
August 0.275000E+09 0.175012E+09 0.00 25181451.38 79160.58 0.00 0.689633E+10 0.00 2.47
September 0.161854E+09 0.00 0.00 15798411.48 0.00 0.00 0.599602E+10 0.00 1.69
October 0.186213E+09 0.00 0.00 10267312.44 0.00 0.00 0.616662E+10 0.00 1.08
November 0.152118E+09 0.00 0.00 7655299.84 0.00 0.00 0.476764E+10 0.00 0.65
December 0.160657E+09 0.00 0.00 7628233.77 0.00 0.00 0.472520E+10 0.00 0.51
                   
Annual Sum or Average 0.429142E+10 0.246831E+09 0.00 0.167961E+09 458721.93 0.00 0.727638E+11 0.00 1.37
Minimum of Months 0.129910E+09 0.00 0.00 1586207.65 0.00 0.00 0.132798E+10 0.00 0.30
Maximum of Months 0.178473E+10 0.175012E+09 0.00 25412358.52 342534.40 0.00 0.952356E+10 0.00 2.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.230131E+11 0.00 0.00 0.00 0.00 0.219605E+11 0.00 0.00 0.30
February 0.283145E+11 0.00 0.00 613268.19 0.00 0.966948E+10 0.372979E+09 0.00 0.30
March 0.340350E+11 0.00 0.00 3081676.35 0.00 0.192422E+10 0.291144E+10 0.00 0.31
April 0.231697E+11 25894542.92 0.00 21428700.54 5024152.38 63823098.52 0.142577E+11 0.00 0.40
May 0.152826E+11 1365253.24 0.00 58798606.20 0.00 0.00 0.339331E+11 0.00 0.66
June 0.831859E+10 26119612.11 0.00 83691708.24 3316194.63 0.00 0.402818E+11 0.00 0.83
July 0.757264E+10 0.225842E+09 0.00 88134011.73 4922141.27 0.00 0.322750E+11 0.00 0.85
August 0.719147E+10 0.861350E+09 0.00 76670839.61 5588597.42 0.00 0.255894E+11 0.00 0.76
September 0.162660E+11 0.00 0.00 45142015.50 0.00 0.00 0.207005E+11 0.00 0.60
October 0.286450E+11 0.00 0.00 9242455.25 0.00 0.216852E+09 0.581878E+10 0.00 0.34
November 0.332517E+11 0.00 0.00 25871.47 0.00 0.507935E+10 78670462.27 0.00 0.30
December 0.265634E+11 0.00 0.00 0.00 0.00 0.163847E+11 0.00 0.00 0.29
                   
Annual Sum or Average 0.251624E+12 0.114057E+10 0.00 0.386829E+09 18851085.70 0.552990E+11 0.176219E+12 0.00 0.50
Minimum of Months 0.719147E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.340350E+11 0.861350E+09 0.00 88134011.73 5588597.42 0.219605E+11 0.402818E+11 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.118099E+11 0.00 0.00 0.00 0.00 0.116737E+11 0.00 0.00 0.24
February 0.140990E+11 0.00 0.00 3255952.87 0.00 0.460769E+10 0.208563E+10 0.00 0.26
March 0.142790E+11 0.00 0.00 23540988.91 0.00 0.816801E+09 0.127112E+11 0.00 0.34
April 0.831503E+10 29364581.77 0.00 57059060.12 0.00 54150182.01 0.318818E+11 0.00 0.68
May 0.699455E+10 1402332.50 0.00 88840501.90 0.00 0.00 0.426192E+11 0.00 1.03
June 0.367670E+10 19358781.47 0.00 0.126739E+09 2131861.64 0.00 0.545476E+11 0.00 1.47
July 0.351386E+10 0.205327E+09 0.00 0.132008E+09 3164266.68 0.00 0.399962E+11 0.00 1.41
August 0.285549E+10 0.787659E+09 0.00 0.125176E+09 403721.89 0.00 0.356966E+11 0.00 1.39
September 0.701824E+10 0.00 0.00 78880928.61 0.00 0.00 0.326055E+11 0.00 1.02
October 0.126218E+11 0.00 0.00 28514183.42 0.00 0.130777E+09 0.149398E+11 0.00 0.44
November 0.163598E+11 0.00 0.00 1756804.64 0.00 0.289483E+10 0.117286E+10 0.00 0.25
December 0.137998E+11 0.00 0.00 49701.39 0.00 0.871768E+10 43875374.71 0.00 0.23
                   
Annual Sum or Average 0.115343E+12 0.104311E+10 0.00 0.665821E+09 5699850.21 0.288956E+11 0.268300E+12 0.00 0.73
Minimum of Months 0.285549E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.23
Maximum of Months 0.163598E+11 0.787659E+09 0.00 0.132008E+09 3164266.68 0.116737E+11 0.545476E+11 0.00 1.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.274944E+11 0.00 0.00 18047590.80 0.00 0.115812E+11 0.142964E+11 0.00 0.35
February 0.252824E+11 0.00 0.00 58306555.23 0.00 0.442492E+10 0.312509E+11 0.00 0.49
March 0.230124E+11 0.00 0.00 98436517.26 0.00 0.525130E+09 0.506267E+11 0.00 0.62
April 0.142418E+11 0.115264E+09 0.00 0.117570E+09 0.00 8129976.52 0.613251E+11 0.00 0.90
May 0.121765E+11 2959763.74 0.00 0.144029E+09 0.00 0.00 0.681962E+11 0.00 1.14
June 0.843890E+10 34512980.78 0.00 0.143074E+09 3307353.35 0.00 0.596584E+11 0.00 1.23
July 0.758417E+10 0.468031E+09 0.00 0.155480E+09 4909018.39 0.00 0.489964E+11 0.00 1.33
August 0.518416E+10 0.199101E+10 0.00 0.159873E+09 228903.52 0.00 0.437947E+11 0.00 1.29
September 0.993367E+10 0.00 0.00 0.207274E+09 0.00 0.00 0.700841E+11 0.00 1.53
October 0.174250E+11 0.00 0.00 0.126622E+09 0.00 3523533.58 0.578818E+11 0.00 0.84
November 0.267500E+11 0.00 0.00 39127790.91 0.00 0.290318E+10 0.205659E+11 0.00 0.42
December 0.263287E+11 0.00 0.00 31478606.40 0.00 0.993993E+10 0.213299E+11 0.00 0.40
                   
Annual Sum or Average 0.203852E+12 0.261178E+10 0.00 0.129932E+10 8445275.26 0.293860E+11 0.548007E+12 0.00 0.88
Minimum of Months 0.518416E+10 0.00 0.00 18047590.80 0.00 0.00 0.142964E+11 0.00 0.35
Maximum of Months 0.274944E+11 0.199101E+10 0.00 0.207274E+09 4909018.39 0.115812E+11 0.700841E+11 0.00 1.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.198909E+11 0.00 0.00 443244.09 0.00 0.850015E+10 0.475592E+09 0.00 0.30
February 0.187264E+11 0.00 0.00 7407400.37 0.00 0.342345E+10 0.448591E+10 0.00 0.33
March 0.182923E+11 0.00 0.00 24068776.76 0.00 0.139611E+09 0.134313E+11 0.00 0.41
April 0.961234E+10 59410459.34 0.00 58001523.73 0.00 2332096.54 0.305864E+11 0.00 0.75
May 0.600361E+10 1266340.62 0.00 0.137813E+09 0.00 0.00 0.481247E+11 0.00 1.28
June 0.364823E+10 84879336.58 0.00 0.126494E+09 2125423.76 0.00 0.446943E+11 0.00 1.45
July 0.219998E+10 0.528294E+09 0.00 0.147115E+09 384439.52 0.00 0.420075E+11 0.00 1.70
August 0.238282E+10 0.150850E+10 0.00 0.124632E+09 3581857.84 0.00 0.311678E+11 0.00 1.35
September 0.575874E+10 0.00 0.00 0.102239E+09 0.00 0.00 0.348719E+11 0.00 1.21
October 0.143434E+11 0.00 0.00 28644911.32 0.00 0.00 0.152031E+11 0.00 0.50
November 0.211271E+11 0.00 0.00 3747505.24 0.00 0.156828E+10 0.264314E+10 0.00 0.32
December 0.210718E+11 0.00 0.00 1495181.56 0.00 0.541548E+10 0.139161E+10 0.00 0.29
                   
Annual Sum or Average 0.143058E+12 0.218235E+10 0.00 0.762102E+09 6091721.12 0.190493E+11 0.269083E+12 0.00 0.83
Minimum of Months 0.219998E+10 0.00 0.00 443244.09 0.00 0.00 0.475592E+09 0.00 0.29
Maximum of Months 0.211271E+11 0.150850E+10 0.00 0.147115E+09 3581857.84 0.850015E+10 0.481247E+11 0.00 1.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103967E+10 0.00 0.00 0.00 0.00 0.312712E+10 0.00 0.00 0.30
February 0.154292E+10 0.00 0.00 2051.05 0.00 0.205419E+10 17589814.88 0.00 0.31
March 0.311194E+10 0.00 0.00 59558.31 0.00 0.753893E+09 57549447.72 0.00 0.34
April 0.234060E+10 671898.56 0.00 1477632.29 104865.26 0.263178E+09 0.100471E+10 0.00 0.39
May 0.174868E+10 0.00 0.00 4841163.81 0.00 19481302.19 0.292766E+10 0.00 0.62
June 0.103048E+10 927858.11 0.00 7587097.80 175553.63 0.00 0.373815E+10 0.00 0.83
July 0.824986E+09 10897075.03 0.00 8782997.24 278508.85 0.00 0.319974E+10 0.00 0.86
August 0.825882E+09 53616972.01 0.00 7553173.72 1503583.39 0.00 0.232134E+10 0.00 0.75
September 0.179579E+10 0.00 0.00 3486057.13 0.00 26578550.70 0.163821E+10 0.00 0.57
October 0.268329E+10 0.00 0.00 346944.89 0.00 0.378232E+09 0.298588E+09 0.00 0.36
November 0.193579E+10 0.00 0.00 0.00 0.00 0.163314E+10 0.00 0.00 0.31
December 0.110191E+10 0.00 0.00 0.00 0.00 0.283743E+10 0.00 0.00 0.30
                   
Annual Sum or Average 0.199819E+11 66113803.71 0.00 34136676.24 2062511.12 0.110933E+11 0.152035E+11 0.00 0.50
Minimum of Months 0.824986E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.311194E+10 53616972.01 0.00 8782997.24 1503583.39 0.312712E+10 0.373815E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.879215E+09 0.00 0.00 0.00 0.00 0.181801E+10 0.00 0.00 0.31
February 0.117887E+10 0.00 0.00 55920.68 0.00 0.108735E+10 65910004.46 0.00 0.32
March 0.165298E+10 0.00 0.00 1366499.63 0.00 0.326060E+09 0.943897E+09 0.00 0.39
April 0.101176E+10 749719.93 0.00 4831347.98 0.00 97531696.79 0.292038E+10 0.00 0.70
May 0.793317E+09 0.00 0.00 8407165.55 0.00 12547492.38 0.424664E+10 0.00 1.04
June 0.395589E+09 701083.49 0.00 12418088.31 113237.78 0.00 0.565723E+10 0.00 1.53
July 0.366970E+09 9784564.80 0.00 13314024.11 65800.56 0.00 0.424212E+10 0.00 1.49
August 0.305549E+09 50553480.85 0.00 13424125.86 147783.11 0.00 0.360742E+10 0.00 1.46
September 0.832759E+09 0.00 0.00 7344863.82 0.00 9169613.23 0.311740E+10 0.00 1.04
October 0.130851E+10 0.00 0.00 2084864.17 0.00 0.202338E+09 0.129051E+10 0.00 0.47
November 0.133693E+10 0.00 0.00 36484.39 0.00 0.934018E+09 37776079.21 0.00 0.31
December 0.899093E+09 0.00 0.00 0.00 0.00 0.166201E+10 0.00 0.00 0.30
                   
Annual Sum or Average 0.109615E+11 61788849.06 0.00 63283384.49 326821.44 0.614905E+10 0.261293E+11 0.00 0.78
Minimum of Months 0.305549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.165298E+10 50553480.85 0.00 13424125.86 147783.11 0.181801E+10 0.565723E+10 0.00 1.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.175470E+10 0.00 0.00 967791.79 0.00 0.201750E+10 0.790979E+09 0.00 0.33
February 0.178988E+10 0.00 0.00 3954103.38 0.00 0.109457E+10 0.259475E+10 0.00 0.49
March 0.211709E+10 0.00 0.00 7626163.19 0.00 0.458008E+09 0.515994E+10 0.00 0.68
April 0.144676E+10 2686263.64 0.00 10154808.70 0.00 0.196365E+09 0.589672E+10 0.00 0.90
May 0.132641E+10 0.00 0.00 13241039.44 0.00 17688549.87 0.666129E+10 0.00 1.10
June 0.917978E+09 1253642.17 0.00 13573821.98 176086.45 0.00 0.604640E+10 0.00 1.23
July 0.748852E+09 22254785.48 0.00 17053319.41 62289.54 0.00 0.525861E+10 0.00 1.36
August 0.639188E+09 0.124221E+09 0.00 17400116.02 39734.96 0.00 0.435081E+10 0.00 1.33
September 0.112548E+10 0.00 0.00 19610173.21 0.00 8642106.62 0.692959E+10 0.00 1.52
October 0.168500E+10 0.00 0.00 10026458.17 0.00 0.220209E+09 0.591776E+10 0.00 0.90
November 0.208694E+10 0.00 0.00 2262543.85 0.00 0.104536E+10 0.117740E+10 0.00 0.41
December 0.166081E+10 0.00 0.00 1810650.39 0.00 0.179117E+10 0.132739E+10 0.00 0.36
                   
Annual Sum or Average 0.172991E+11 0.150416E+09 0.00 0.117681E+09 278110.95 0.684951E+10 0.521117E+11 0.00 0.89
Minimum of Months 0.639188E+09 0.00 0.00 967791.79 0.00 0.00 0.790979E+09 0.00 0.33
Maximum of Months 0.211709E+10 0.124221E+09 0.00 19610173.21 176086.45 0.201750E+10 0.692959E+10 0.00 1.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114041E+10 0.00 0.00 18466.80 0.00 0.147060E+10 21342540.01 0.00 0.30
February 0.131498E+10 0.00 0.00 483172.51 0.00 0.758429E+09 0.389842E+09 0.00 0.34
March 0.169586E+10 0.00 0.00 1777061.20 0.00 0.259583E+09 0.135439E+10 0.00 0.45
April 0.109151E+10 1466113.67 0.00 4975811.21 0.00 76342998.22 0.284158E+10 0.00 0.76
May 0.721045E+09 0.00 0.00 12631299.28 0.00 9558230.12 0.469283E+10 0.00 1.24
June 0.436327E+09 2883472.68 0.00 12040372.41 112686.98 0.00 0.448915E+10 0.00 1.48
July 0.292635E+09 25247734.14 0.00 16408515.53 9109.92 0.00 0.436425E+10 0.00 1.75
August 0.262662E+09 91651711.32 0.00 13563432.19 347216.14 0.00 0.306490E+10 0.00 1.35
September 0.732109E+09 0.00 0.00 9467310.73 0.00 0.00 0.325442E+10 0.00 1.19
October 0.144763E+10 0.00 0.00 2132027.29 0.00 0.115038E+09 0.140481E+10 0.00 0.53
November 0.156508E+10 0.00 0.00 200159.97 0.00 0.623574E+09 0.125134E+09 0.00 0.32
December 0.119989E+10 0.00 0.00 47424.84 0.00 0.123285E+10 52601219.00 0.00 0.29
                   
Annual Sum or Average 0.119001E+11 0.121249E+09 0.00 73745053.94 469013.04 0.454597E+10 0.260553E+11 0.00 0.84
Minimum of Months 0.262662E+09 0.00 0.00 18466.80 0.00 0.00 21342540.01 0.00 0.29
Maximum of Months 0.169586E+10 91651711.32 0.00 16408515.53 347216.14 0.147060E+10 0.469283E+10 0.00 1.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3146798.52 0.00 0.00 0.620796E+09 0.00 0.28
February 0.00 0.00 0.00 7563202.36 0.00 0.00 0.513916E+09 0.00 0.29
March 0.00 0.00 0.00 14855647.36 0.00 0.00 0.540741E+09 0.00 0.31
April 0.00 0.00 0.00 18456483.94 0.00 0.00 0.419651E+09 0.00 0.29
May 0.00 16066.02 0.00 4424817.98 0.00 0.00 0.379263E+09 0.00 0.29
June 0.00 0.00 0.00 9599604.23 0.00 0.00 0.294543E+09 0.00 0.30
July 0.00 4137326.26 0.00 12759101.12 0.00 0.00 0.166720E+09 0.00 0.28
August 0.00 13418243.98 0.00 16495542.44 0.00 0.00 0.124580E+09 0.00 0.31
September 0.00 90351.96 0.00 4263706.95 0.00 0.00 0.255518E+09 0.00 0.29
October 0.00 0.00 0.00 8889775.63 0.00 0.00 0.424703E+09 0.00 0.28
November 0.00 0.00 0.00 12580225.63 0.00 0.00 0.494765E+09 0.00 0.28
December 0.00 0.00 0.00 17541980.61 0.00 0.00 0.575315E+09 0.00 0.28
                   
Annual Sum or Average 0.00 17661988.22 0.00 0.130577E+09 0.00 0.00 0.481051E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 3146798.52 0.00 0.00 0.124580E+09 0.00 0.28
Maximum of Months 0.00 13418243.98 0.00 18456483.94 0.00 0.00 0.620796E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.384142E+09 0.00 0.00 12471059.83 0.00 0.00 0.584339E+10 0.00 0.28
February 0.00 0.00 0.00 59864001.02 0.00 0.00 0.515693E+10 0.00 0.29
March 0.00 0.00 0.00 0.132470E+09 0.00 0.00 0.542239E+10 0.00 0.31
April 0.00 0.00 0.00 0.171433E+09 0.00 0.00 0.420798E+10 0.00 0.29
May 0.00 139816.42 0.00 38393036.33 0.00 0.00 0.380344E+10 0.00 0.29
June 0.00 0.00 0.00 88978246.16 0.00 0.00 0.295352E+10 0.00 0.30
July 0.00 40986577.91 0.00 0.120569E+09 0.00 0.00 0.167477E+10 0.00 0.28
August 0.00 0.133522E+09 0.00 0.156839E+09 0.00 0.00 0.125420E+10 0.00 0.31
September 0.00 784376.71 0.00 37133014.12 0.00 0.00 0.257759E+10 0.00 0.29
October 0.00 0.00 0.00 77257613.93 0.00 0.00 0.425943E+10 0.00 0.28
November 0.00 0.00 0.00 0.108083E+09 0.00 0.00 0.496486E+10 0.00 0.28
December 0.00 0.00 0.00 0.151356E+09 0.00 0.00 0.577702E+10 0.00 0.28
                   
Annual Sum or Average 0.384142E+09 0.175432E+09 0.00 0.115485E+10 0.00 0.00 0.478955E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 12471059.83 0.00 0.00 0.125420E+10 0.00 0.28
Maximum of Months 0.384142E+09 0.133522E+09 0.00 0.171433E+09 0.00 0.00 0.584339E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.271056E+09 0.00 0.00 469331.64 0.00 0.00 0.344084E+09 0.00 0.28
February 0.00 0.00 0.00 4943294.90 0.00 0.00 0.516868E+09 0.00 0.29
March 0.00 0.00 0.00 12208336.22 0.00 0.00 0.543359E+09 0.00 0.31
April 0.00 0.00 0.00 16586750.59 0.00 0.00 0.421413E+09 0.00 0.29
May 0.00 14200.62 0.00 3510186.00 0.00 0.00 0.380920E+09 0.00 0.29
June 0.00 0.00 0.00 8753723.07 0.00 0.00 0.295566E+09 0.00 0.30
July 0.00 4118655.76 0.00 11988459.01 0.00 0.00 0.167553E+09 0.00 0.28
August 0.00 13390133.68 0.00 15572510.60 0.00 0.00 0.125563E+09 0.00 0.31
September 0.00 76947.60 0.00 3344829.76 0.00 0.00 0.259315E+09 0.00 0.29
October 0.00 0.00 0.00 6857412.52 0.00 0.00 0.427212E+09 0.00 0.28
November 0.00 0.00 0.00 9640132.54 0.00 0.00 0.497886E+09 0.00 0.28
December 0.00 0.00 0.00 13844929.30 0.00 0.00 0.579014E+09 0.00 0.28
                   
Annual Sum or Average 0.271056E+09 17599937.66 0.00 0.107720E+09 0.00 0.00 0.455875E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 469331.64 0.00 0.00 0.125563E+09 0.00 0.28
Maximum of Months 0.271056E+09 13390133.68 0.00 16586750.59 0.00 0.00 0.579014E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.516241E+09 0.00 0.00 0.435954E+12 0.00 9.49
February 0.00 0.00 0.00 0.940057E+09 0.00 0.00 0.660668E+12 0.00 17.79
March 0.00 0.00 0.00 0.149114E+10 0.00 0.00 0.100776E+13 0.00 27.91
April 0.00 31793.33 0.00 0.215506E+10 0.00 0.00 0.112828E+13 0.00 39.30
May 0.00 0.00 0.00 0.565765E+09 0.00 0.00 0.383739E+12 0.00 17.17
June 0.00 0.00 0.00 0.111310E+10 0.00 0.00 0.566800E+12 0.00 32.62
July 0.00 0.829135E+09 0.00 0.191613E+10 0.00 0.00 0.656494E+12 0.00 42.98
August 0.00 0.324523E+10 0.00 0.247123E+10 0.00 0.00 0.557292E+12 0.00 44.90
September 0.00 0.00 0.00 0.534212E+09 0.00 0.00 0.340476E+12 0.00 19.87
October 0.00 0.00 0.00 0.101811E+10 0.00 0.00 0.647826E+12 0.00 24.00
November 0.00 0.00 0.00 0.144295E+10 0.00 0.00 0.922488E+12 0.00 27.66
December 0.00 0.00 0.00 0.204673E+10 0.00 0.00 0.129141E+13 0.00 30.70
                   
Annual Sum or Average 0.00 0.407439E+10 0.00 0.162107E+11 0.00 0.00 0.859919E+13 0.00 27.93
Minimum of Months 0.00 0.00 0.00 0.516241E+09 0.00 0.00 0.340476E+12 0.00 9.49
Maximum of Months 0.00 0.324523E+10 0.00 0.247123E+10 0.00 0.00 0.129141E+13 0.00 44.90



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:21:42

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.115340E+12 0.108353E+11 0.00 0.202033E+13 0.127683E+12
February 0.226653E+12 0.991251E+10 0.00 0.226152E+13 0.197824E+12
March 0.415773E+12 0.948432E+10 0.00 0.291382E+13 0.339799E+12
April 0.643571E+12 0.914229E+10 0.00 0.309877E+13 0.557891E+12
May 0.847280E+12 0.725817E+10 0.00 0.242974E+13 0.333246E+12
June 0.860686E+12 0.595290E+10 0.00 0.242791E+13 0.650953E+12
July 0.904766E+12 0.521831E+10 0.00 0.249735E+13 0.128579E+13
August 0.709500E+12 0.411813E+10 0.00 0.209798E+13 0.202803E+13
September 0.492460E+12 0.346400E+10 0.00 0.234077E+13 0.472040E+12
October 0.313081E+12 0.770494E+10 0.00 0.265269E+13 0.279869E+12
November 0.133241E+12 0.881619E+10 0.00 0.278887E+13 0.272174E+12
December 0.853733E+11 0.933099E+10 0.00 0.302507E+13 0.361714E+12
           
Annual Sum or Average 0.574772E+13 0.912380E+11 0.00 0.305548E+14 0.690701E+13
Minimum of Months 0.853733E+11 0.346400E+10 0.00 0.202033E+13 0.127683E+12
Maximum of Months 0.904766E+12 0.108353E+11 0.00 0.309877E+13 0.202803E+13