Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280

Simulation Timestamp: 2024-07-03 12:26:29


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 27749.93 599.09 599.09
Net Site Energy 27749.93 599.09 599.09
Total Source Energy 85486.38 1845.55 1845.55
Net Source Energy 85486.38 1845.55 1845.55


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1151.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1396.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2461.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 353.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2566.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2360.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 346.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 477.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3339.94
Humidification 1463.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 544.26
Heat Recovery 36.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 459.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 26598.87 1151.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6164.37
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1151.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1396.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2461.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 353.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 2505.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2360.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 346.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 477.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3339.94
Humidification General 1463.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 544.26
Heat Recovery General 36.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 459.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1151.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1396.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2461.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 353.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 2566.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2360.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 346.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 477.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3339.94
Humidification Unassigned 1463.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 544.26
Heat Recovery Unassigned 36.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 459.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 60.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 140.44 24.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13
Other 373.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 574.24 24.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 60.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 140.44 24.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13
Other 373.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 574.24 24.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 26598.874 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 26598.874 100.00
     
Total On-Site and Utility Electric Sources 26598.874 100.00
Total Electricity End Uses 26598.874 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 114.16 5.34
Air to Air Heat Recovery for Heating 2021.97 94.66
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2136.12 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6164.37 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6164.37 100.00
Total Water End Uses 6164.37 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 82.50
Time Setpoint Not Met During Occupied Cooling 986.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 5936.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
RunPeriod RUNPERIOD 1
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Latitude [deg] 42.93
Longitude [deg] -78.7
Elevation [m] 215.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 6.5999 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 6.5999 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.5999 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.5999 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 6.5999 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.5999 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.5999 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.5999 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 9.7790 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 9.7790 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 9.7790 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 6.5999 18.58 484.4232  
Total 46320.38             6.6297 9.29 17.8789  
Conditioned Total 46320.38             6.6297 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.0382 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 15-AUG-14:39 02-JAN-05:10 - - - - - - - - - - 17-AUG-12:50
Heating 0.00 1582955.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 519084.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 233115.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 215937.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 46481.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 79472.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25737.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2111016.45 1582955.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1582955.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 519084.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3394.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 112.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 215937.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 46481.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 79472.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 25737.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1247.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4422.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7794.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1118.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 8127.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7477.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1098.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1513.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 4633.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 116.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1456.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 84238.63 1247.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 95.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 175.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 161.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 23.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 32.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 100.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 2.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 31.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1818.61 26.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 95.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 175.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 161.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 23.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 32.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 100.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 2.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 31.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1818.61 26.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

AirTerminal:SingleDuct:VAV:NoReheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s]
BASEMENT PSZ-VAV DIFFUSER 5.10 0.415178 0.000000 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.52 0.344645 0.293000 1.62 0.919054 0.500000 0.001105 0.000143 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 51.80 0.367167 0.312000 16.16 0.979111 0.500000 0.001038 0.003813 16.16 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.14 0.370173 0.315000 1.62 0.987129 0.500000 0.001029 0.000809 2.83 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.932871 0.256006 0.218000 0.203366 0.682683 0.500000 0.001488 0.000136 0.474426 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.28 0.120534 0.102000 0.130240 0.321423 0.500000 0.003161 0.000093 0.324722 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.46 0.163873 0.139000 0.202577 0.436994 0.500000 0.002325 0.000152 0.532682 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.56 0.098532 0.084000 0.131206 0.300000 0.500000 0.003867 0.000072 0.251115 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.71 0.274309 0.233000 2.03 0.731490 0.500000 0.001389 0.002105 7.36 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 13.64       0.300906 0.500000 0.003376 0.001379 4.82 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 14.46 0.165117 0.140000 2.02 0.440311 0.500000 0.002307 0.002105 7.36 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 14.32 0.107485 0.091000 1.30 0.300000 0.500000 0.003545 0.001338 4.68 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.989574 0.241337 0.205000 0.202863 0.643565 0.500000 0.001579 0.000269 0.941333 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.38 0.111913 0.095000 0.130646 0.300000 0.500000 0.003404 0.000176 0.614218 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.56 0.153302 0.130000 0.202524 0.408805 0.500000 0.002485 0.000269 0.941341 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.51 0.101888 0.087000 0.131416 0.300000 0.500000 0.003739 0.000173 0.606169 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K] User-Specified Rated Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 16322.64 0.000143 329.97  
CORE_MID VAV BOX REHEAT COIL 435881.87 0.003813 10653.97  
CORE_TOP VAV BOX REHEAT COIL 92520.59 0.000809 2442.26  
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 15519.47 0.000136 409.45  
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 10620.65 0.000093 280.18  
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 17420.63 0.000152 459.55  
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8218.43 0.000072 216.87  
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 240574.18 0.002105 6344.03  
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 157600.80 0.001379 4155.93  
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 240575.57 0.002105 6344.06  
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 152919.73 0.001338 4032.57  
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 30748.75 0.000269 810.71  
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 20063.05 0.000176 528.97  
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 30749.00 0.000269 810.72  
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 19800.36 0.000173 522.05  
VAV_BOT WITH REHEAT HEATING COIL 62573.55 0.000547 1012.69  
VAV_MID WITH REHEAT HEATING COIL 656277.62 0.005741 10485.17  
VAV_TOP WITH REHEAT HEATING COIL 64351.66 0.000563 1040.57  
CAV_BAS HEATING COIL 263779.46 0.000875 2622.48 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DATACENTER_BOT_ZN_6 DIRECT AIR 0.493751
DATACENTER_MID_ZN_6 DIRECT AIR 4.74
DATACENTER_TOP_ZN_6 DIRECT AIR 0.481719
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 25.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.37 2.28 10.75 2.66 9.22 9.22 0.300000 0.288439 9.22
VAV_MID WITH REHEAT 51.47 22.83 102.93 36.22 85.94 85.94 0.300000 0.421422 85.94
VAV_TOP WITH REHEAT 5.29 2.29 10.57 5.93 9.44 9.44 0.300000 0.627876 9.44
CAV_BAS 0.000000 0.000000 5.10 1.20 5.10 5.10 1.00 0.235267 5.10
AIRLOOP DATACENTER BASEMENT 25.05 25.05 25.05 25.05 25.05 25.05 1.00 0.999993 25.05
AIRLOOP DATACENTER BOT 0.493751 0.493751 0.493751 0.493751 0.493751 0.493751 1.00 1.00 0.493751
AIRLOOP DATACENTER MID 4.74 4.74 4.74 4.74 4.74 4.74 1.00 1.00 4.74
AIRLOOP DATACENTER TOP 0.481719 0.481719 0.481719 0.481719 0.481719 0.481719 1.00 1.00 0.481719
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.22  
VAV_MID WITH REHEAT_OA_CONTROLLER 85.94  
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.44  
CAV_BAS_OA_CONTROLLER 5.10 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 25.05 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.493751 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.74 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.481719 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.03
VAV_MID WITH REHEAT OA HEAT RECOVERY 20.31
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 25.42 6.67 10.90 0.009896 0.008500 199062.20 0.005693 9.22
VAV_MID WITH REHEAT COOLING COIL 25.57 6.67 10.90 0.010054 0.008500 1910140.56 0.054630 85.94
VAV_TOP WITH REHEAT COOLING COIL 25.36 6.67 10.90 0.009867 0.008500 202158.94 0.005782 9.44
CAV_BAS COOLING COIL 25.33 6.67 10.89 0.010173 0.008500 113769.83 0.003254 5.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.22
VAV_MID WITH REHEAT FAN 85.94
VAV_TOP WITH REHEAT FAN 9.44
CAV_BAS FAN 5.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.005693 0.000084
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000547  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.054630 0.000009
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.005741  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.005782 0.000082
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000563  
CAV_BAS_COOLC_CONTROLLER 0.003254 0.000146
CAV_BAS_HEATC_CONTROLLER 0.000875  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 25.05 496305.63 349488.48 0.012154
AIRLOOP DATACENTER BOT COOLING COIL 0.493751 9679.56 6845.93 0.000237
AIRLOOP DATACENTER MID COOLING COIL 4.74 92966.77 65704.12 0.002277
AIRLOOP DATACENTER TOP COOLING COIL 0.481719 9453.48 6682.26 0.000232
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 25.05 25.05 25.05 25.05 496305.63 496305.63 22473.72 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.493751 0.493751 0.493751 0.493751 9679.56 9679.56 1038.19 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.74 4.74 4.74 4.74 92966.77 92966.77 10381.93 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.481719 0.481719 0.481719 0.481719 9453.48 9453.48 1038.19 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 25.05
AIRLOOP DATACENTER BOT SUPPLY FAN 0.493751
AIRLOOP DATACENTER MID SUPPLY FAN 4.74
AIRLOOP DATACENTER TOP SUPPLY FAN 0.481719
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 25.05 496305.63 0.012154
AIRLOOP DATACENTER BOT HEATING COIL 0.493751 9679.56 0.000237
AIRLOOP DATACENTER MID HEATING COIL 4.74 92966.77 0.002277
AIRLOOP DATACENTER TOP HEATING COIL 0.481719 9453.48 0.000232
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 22473.72
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1038.19
AIRLOOP DATACENTER MID_SUPPHEATCOIL 10381.93
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1038.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000215 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.069358 11212.00  
HEATSYS1 PUMP 0.020758 6189.43 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.069358 8.32
HEATSYS1 0.020758 2.49
COOLSYS1_SUPPLY 0.069358 8.32
SINGLE WATER PLANT LOOP 0.014900 1.79
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.069358 0.069358 291132.24 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2372738.58 2372738.58 0.020758
CENTRAL BOILER 613744.43 601379.40 0.014900
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.034679 3881.22
COOLSYS1 CHILLER2 PUMP 0.034679 3881.22
PLANT CIRC PUMP 0.014900 3762.57
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.069358 0.034814 1217264.14 1217264.50 0.061295
COOLSYS1 CHILLER2 0.069358 0.034814 1217264.14 1217264.50 0.061295
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] U-factor Times Area Value at High Fan Speed [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/K]
CENTRAL TOWER 0.014900 147944.06 74893.84 73972.03 7004.20 44936.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.122591 14.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.122591 30050.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 48.18 1457149.06 9.64 182143.63
TOWERWATERSYS COOLTOWER 2 48.18 1457149.06 9.64 182143.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.063125
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.70 6.00 -2.20 -3.40 -4.20 2.70 7.50 13.70 18.60 22.00 20.70 16.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 42.93 -78.73 -5.00 215.00 98769 1.1739


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 8.97 26.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 6.600 4.842 0.000 0.000 0.000 0.000 11.442 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 6.600 484.423 0.000 0.000 0.000 0.000 491.023 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 18343.827 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18343.827
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5172.174 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5172.174
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 0.9689 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 0.9235 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.155 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8647
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9155
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6987
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 -0.61082983E-15 0.35276446E-16 -0.14787207E-09 0.18036823E-17
51 8 0.21615122E-07 0.13022774E-12 0.37506347E-03 -0.24577139E-09
52 7 -0.12160115E-01 0.67804000E-08 -0.22968555E-01 0.13826493E-03
53 6 0.40313748 0.23652218E-05 0.47020644 -0.47216777E-02
54 5 -5.1689687 0.88520675E-04 -4.4267872 0.62916081E-01
55 4 32.907337 0.72566064E-03 21.383769 -0.42085466
56 3 -111.02301 0.15845227E-02 -55.512186 1.5122587
57 2 196.92983 0.89280554E-03 77.772262 -2.8975199
58 1 -171.09018 0.95459611E-04 -55.224854 2.7442846
59 0 57.057407 0.54436501E-06 15.563573  
60 9 -0.28033836E-14 0.31423843E-16 -0.15000593E-09 0.49342508E-16
61 8 0.21915022E-07 0.12441777E-12 0.37821899E-03 -0.24918134E-09
62 7 -0.12254290E-01 0.64567074E-08 -0.23104155E-01 0.13933574E-03
63 6 0.40569641 0.22493722E-05 0.47238617 -0.47518414E-02
64 5 -5.1939411 0.84090406E-04 -4.4435303 0.63225727E-01
65 4 33.017798 0.68864468E-03 21.449218 -0.42232128
66 3 -111.25804 0.15023393E-02 -55.641580 1.5156542
67 2 197.16277 0.84581883E-03 77.890928 -2.9012190
68 1 -171.17623 0.90368420E-04 -55.259345 2.7457926
69 0 57.057407 0.51494858E-06 15.557864  
70 9 0.16475985E-14 0.40698495E-16 -0.13909959E-09 -0.62647149E-17
71 8 0.20378875E-07 0.15355384E-12 0.36189576E-03 -0.23171482E-09
72 7 -0.11766586E-01 0.81065314E-08 -0.22401745E-01 0.13379037E-03
73 6 0.39244372 0.28436739E-05 0.46108386 -0.45956244E-02
74 5 -5.0645996 0.10693990E-03 -4.3566540 0.61621961E-01
75 4 32.445620 0.88045565E-03 21.109484 -0.41472443
76 3 -110.04047 0.19299305E-02 -54.969854 1.4980638
77 2 195.95581 0.10911488E-02 77.275137 -2.8820526
78 1 -170.73031 0.11703553E-03 -55.080813 2.7379774
79 0 57.057407 0.66971377E-06 15.587784  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.363_SHGC_EAST_0.378 35 1 VerySmooth 2.062 2.062 1.000 0.379    
2 WINDOW_U_0.363_SHGC_SOUTH_0.378 36 1 VerySmooth 2.062 2.062 1.000 0.379    
3 WINDOW_U_0.363_SHGC_WEST_0.378 37 1 VerySmooth 2.062 2.062 1.000 0.379    
4 WINDOW_U_0.363_SHGC_NORTH_0.378 38 1 VerySmooth 2.062 2.062 1.000 0.379    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 13.342 0.7435


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 5.142E-002 1.641E-004 2.467E-004 0.215 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 3.428E-002 1.697E-004 2.490E-004 0.223 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 5.142E-002 1.641E-004 2.467E-004 0.215 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 3.428E-002 1.697E-004 2.490E-004 0.223 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 5.142E-002 1.641E-004 2.563E-004 0.215 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 3.428E-002 1.697E-004 2.563E-004 0.223 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 7.615E-002 2.137E-005 2.563E-004 6.311E-002 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 7.615E-002 2.137E-005 2.563E-004 6.311E-002 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 7.615E-002 2.137E-005 1.973E-005 6.311E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000
2 Zone DATACENTER_BASEMENT_ZN_6 1.1500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000
2 Zone DATACENTER_BASEMENT_ZN_6 1.1500


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.9711E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.9733E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7029E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7047E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7604E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7618E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6225E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6233E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0211E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.1665E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7448E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.8708E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7958E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9006E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6441E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6991E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1690
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.5323E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1920
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.7001E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1162
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.6850E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7407E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6489E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0293E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.2095E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7538E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9179E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.8031E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9288E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6446E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7007E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.9709E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.9733E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7026E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7048E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7603E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7619E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6224E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6232E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1587E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.5280E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9523E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.3690E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.4722E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.6137E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.4838E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.5217E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.0030E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3903E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.6810E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.1426E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.6647E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7667E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.9359E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.8463E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.0464E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.1548E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8060E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8851E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.4282E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.4598E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.4839E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.5223E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7816E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7838E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.3613E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3631E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0808E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0822E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6225E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6233E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8311E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9573E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4023E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5035E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1147E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1901E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6447E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7008E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5023E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3766E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.4554E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8016E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1047E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2079E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.7407E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6484E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8288E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9561E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.3991E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4981E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1090E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1723E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6441E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6992E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7815E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7836E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.3612E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3629E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0807E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0818E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6224E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6232E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3693E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.4822E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9508E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.0323E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9114E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.9403E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4840E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.5224E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.8213E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.9167E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.1982E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5470E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.7098E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3837E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9359E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.8463E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.4561E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.7262E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.0647E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.3543E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9525E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.0786E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4837E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.5217E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1697
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1177
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1874
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1324
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1291
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.9209E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.8052E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.8715E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.3178E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.8708E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.9604E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.5790E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.8841E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.0631E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.9539E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.9044E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.5810E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.7169E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.3959E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.9319E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.0121E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.1882E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.8053E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.8710E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.9814E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.2179E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2823E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.7563E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.8143E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.5550E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.9539E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.9044E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1698
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1179
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1875
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1327
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1293
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.9380E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.8177E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.8779E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.3238E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.8784E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.9673E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.5864E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.8962E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.0718E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.9663E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.9108E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.5814E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.7212E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.3966E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.9353E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.0185E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.1922E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.8177E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.8774E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.9853E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.2240E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2867E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.7618E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.8247E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.5624E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.9663E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.9108E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 69097.62976 69097.62976 5.10124 5.10124 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:10:00 -16.30000 9.24091E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 74750.56502 74750.56502 5.51884 5.51884 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 650.01306 650.01306 2.84929E-002 1.07782 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 701857.15696 701857.15696 51.80328 51.80328 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 277230.59499 277230.59499 11.98959 11.98959 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 69614.59560 69614.59560 5.13825 5.13825 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.41800 1.33548E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 64789.87944 64789.87944 2.82507 2.82507 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12516.96403 12516.96403 0.93287 0.93287 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30000 1.33670E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 10866.31956 10866.31956 0.47443 0.47443 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 17132.72015 17132.72015 1.27686 1.27686 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 25.18500 1.33579E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 7435.56298 7435.56298 0.32472 0.32472 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 19554.84933 19554.84933 1.45739 1.45739 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 29.99000 1.33664E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 12195.09531 12195.09531 0.53268 0.53268 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 20958.40542 20958.40542 1.56198 1.56198 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 5756.53853 5756.53853 0.25111 0.25111 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 116814.33586 116814.33586 8.70627 8.70627 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 30.30000 1.33670E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 168369.76461 168369.76461 7.36198 7.36198 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 183003.57686 183003.57686 13.63924 13.63924 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 25.71200 1.33588E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 110298.54650 110298.54650 4.82301 4.82301 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 194069.55630 194069.55630 14.46407 14.46407 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 30.06750 1.33665E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 168370.73932 168370.73932 7.36202 7.36202 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 192121.66183 192121.66183 14.31879 14.31879 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 28.68800 1.33641E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 107025.75927 107025.75927 4.67955 4.67955 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13277.23835 13277.23835 0.98957 0.98957 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.30000 1.33670E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 21516.33885 21516.33885 0.94133 0.94133 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 18451.72576 18451.72576 1.37522 1.37522 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 25.97550 1.33593E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 14039.03313 14039.03313 0.61422 0.61422 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 20902.39472 20902.39472 1.55788 1.55788 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 30.14500 1.33667E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 21516.51500 21516.51500 0.94134 0.94134 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 20267.17296 20267.17296 1.51053 1.51053 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 28.84300 1.33644E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 13855.33634 13855.33634 0.60617 0.60617 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30000 9.24091E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8399.66474 8399.66474 0.49375 0.49375 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.50250 1.33602E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -16.30000 9.24091E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 80568.54399 80568.54399 4.73603 4.73603 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.50250 1.33602E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -16.30000 9.24091E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8194.94764 8194.94764 0.48172 0.48172 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 26.50250 1.33602E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -16.30000 9.24091E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370641.09221 426237.25605 21.78679 25.05481 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 21.83700 1.33520E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 -16.30000 9.24091E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 133662.48 9.22472 9.22472 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 69389.34 2.66077 2.66077 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00
3 VAV_MID WITH REHEAT Cooling Sensible 1227114.22 85.93799 85.93799 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 691593.28 36.21616 36.21616 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00
5 VAV_TOP WITH REHEAT Cooling Sensible 139618.04 9.44156 9.44156 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 69653.24 5.92813 5.92813 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:50:00
7 CAV_BAS Cooling Sensible 68034.02 5.10124 5.10124 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 79706.12 1.20016 1.20016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 420492.69 25.05499 25.05499 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 22473.72 0.33839 0.33839 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8260.63 0.49375 0.49375 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1038.19 1.56323E-002 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 79231.25 4.73603 4.73603 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 10381.93 0.15632 0.15632 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8061.14 0.48172 0.48172 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1038.19 1.56323E-002 1.56323E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Maximum Air Flow Rate [m3/s] 5.10124
2 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Constant Minimum Air Flow Fraction 0.41518
3 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER User-Specified Constant Minimum Air Flow Fraction 0.00000
4 AirTerminal:SingleDuct:VAV:NoReheat BASEMENT PSZ-VAV DIFFUSER Design Size Minimum Air Flow Rate [m3/s] 0.00000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.51884
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34465
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29300
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61702
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91905
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.10548E-003
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.42798E-004
13 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61702
14 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
15 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
16 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16322.63891
17 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.42798E-004
18 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 329.96972
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 51.80328
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36717
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31200
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.16262
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.97911
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.03768E-003
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.81328E-003
27 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.16262
28 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
29 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
30 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 435881.86667
31 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.81328E-003
32 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 10653.97046
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.13825
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37017
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31500
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61855
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.98713
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.02925E-003
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.09411E-004
41 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.82507
42 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
43 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
44 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 92520.59416
45 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.09411E-004
46 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2442.25876
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.93287
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25601
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21800
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20337
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68268
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.48825E-003
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35771E-004
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.47443
56 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
58 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15519.47099
59 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35771E-004
60 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 409.44989
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.27686
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12053
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10200
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13024
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32142
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.16094E-003
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.29141E-005
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32472
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
72 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10620.65236
73 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.29141E-005
74 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 280.18396
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.45739
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16387
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13900
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20258
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43699
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.32498E-003
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.52403E-004
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.53268
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
86 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17420.63104
87 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.52403E-004
88 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 459.55379
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.56198
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.85322E-002
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.40000E-002
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13121
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.86676E-003
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.18984E-005
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.25111
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
100 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8218.43356
101 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.18984E-005
102 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 216.87438
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.70627
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27431
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23300
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02856
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73149
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.38895E-003
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.10465E-003
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.36198
112 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
114 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 240574.18268
115 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.10465E-003
116 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6344.02806
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.63924
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30091
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.37647E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.37876E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.82301
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 157600.80434
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.37876E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4155.92787
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.46407
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16512
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02497
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44031
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.30746E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.10466E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.36202
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 240575.57254
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.10466E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6344.06480
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.31879
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10748
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.10000E-002
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30301
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.54469E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.33781E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.67955
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 152919.73155
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.33781E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4032.57147
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.98957
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24134
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20500
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20286
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64356
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.57871E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.69003E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.94133
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30748.75162
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.69003E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 810.71042
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.37522
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11191
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.50000E-002
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13065
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.40443E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.75520E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.61422
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20063.05254
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.75520E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 528.96993
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.55788
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15330
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20252
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40881
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.48529E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.69006E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.94134
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30749.00317
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.69006E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 810.71706
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.51053
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10189
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.70000E-002
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13142
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.73939E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.73222E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.60617
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19800.35822
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.73222E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 522.04643
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49375
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.73603
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48172
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 25.05481
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.37397
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28441
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.74794
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.66077
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.22472
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.22472
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.28844
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 51.46583
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.82853
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 102.93166
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 36.21616
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 85.93799
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 85.93799
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.42142
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.28573
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28600
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.57145
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.92813
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.44156
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.44156
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.62788
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.00000
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.00000
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.10124
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 1.20016
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.10124
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.10124
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 0.23527
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 25.05481
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 25.05481
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 25.05481
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 25.05481
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 25.05499
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 25.05499
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49375
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49375
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49375
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49375
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49375
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49375
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.73603
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.73603
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.73603
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.73603
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.73603
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.73603
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48172
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48172
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48172
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.48172
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.48172
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.48172
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.22472
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 85.93799
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.44156
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.10124
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 25.05499
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49375
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.73603
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.48172
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.22472
289 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.03050
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.42420
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.89880
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.89584E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 199062.20462
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.69315E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.22472
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 62573.55168
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.47421E-004
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1012.68661
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.22472
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.69315E-003
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 8.36427E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.47421E-004
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 85.93799
306 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 20.30600
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.56919
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.89935
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.00544E-002
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1910140.55615
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.46298E-002
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 85.93799
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 656277.62167
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.74140E-003
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 10485.17148
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 85.93799
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.46298E-002
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 8.71668E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.74140E-003
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.44156
323 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.03050
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.35583
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.89870
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 9.86722E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 202158.94469
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.78172E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.44156
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 64351.66423
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.62976E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1040.56866
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.44156
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.78172E-003
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 8.23614E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.62976E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.10124
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.32601
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 10.88749
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.01725E-002
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 113769.82997
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.25380E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.10124
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 263779.46432
350 Coil:Heating:Water CAV_BAS HEATING COIL User-Specified Rated Capacity [W] 100000.00000
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.74844E-004
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 2622.47617
353 Fan:VariableVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.10124
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.25380E-003
355 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.46349E-004
356 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.74844E-004
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 25.05499
358 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 25.05499
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 496305.62674
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 349488.48470
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.21545E-002
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 25.05499
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 25.05499
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 25.05499
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 25.05499
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 496305.62674
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 496305.62674
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 22473.71574
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
371 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 25.05499
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 25.05499
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 496305.62674
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.21545E-002
375 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 22473.71574
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 2.14634E-004
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49375
381 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49375
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9679.55954
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6845.92923
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.37052E-004
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49375
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49375
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49375
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49375
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9679.55954
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9679.55954
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1038.19256
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
394 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49375
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49375
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9679.55954
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.37052E-004
398 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1038.19256
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.73603
400 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.73603
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 92966.76501
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 65704.12427
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.27675E-003
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.73603
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.73603
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.73603
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.73603
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 92966.76501
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 92966.76501
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 10381.92564
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
413 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.73603
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.73603
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 92966.76501
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.27675E-003
417 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 10381.92564
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48172
419 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48172
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9453.47957
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6682.25988
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.31515E-004
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48172
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48172
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48172
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48172
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9453.47957
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9453.47957
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1038.19256
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
432 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48172
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48172
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9453.47957
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.31515E-004
436 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1038.19256
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 6.93585E-002
438 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 11211.99636
439 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 6.93585E-002
440 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 8.32301
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 6.93585E-002
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 6.93585E-002
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 291132.23715
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
445 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.07578E-002
446 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.49093
447 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.07578E-002
448 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 6189.42910
449 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
450 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2372738.58194
451 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2372738.58000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.07578E-002
453 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 6.93585E-002
454 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 8.32301
455 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 3.46792E-002
456 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 3881.22160
457 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 3.46792E-002
458 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 3881.22160
459 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 6.93585E-002
460 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.48136E-002
461 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1217264.14161
462 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1217264.50000
463 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 6.12954E-002
464 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 6.93585E-002
465 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.48136E-002
466 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1217264.14161
467 Chiller:Electric:EIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1217264.50000
468 Chiller:Electric:EIR COOLSYS1 CHILLER2 Design Size Reference Condenser Fluid Flow Rate [m3/s] 6.12954E-002
469 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.48998E-002
470 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.78798
471 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.48998E-002
472 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3762.57090
473 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.48998E-002
474 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 147944.05834
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at High Fan Speed [W/K] 74893.84215
476 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 73972.02917
477 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
478 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/K] 44936.30529
479 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 613744.42876
480 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 601379.40000
481 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.48998E-002
482 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
483 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
484 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
485 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
486 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
487 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.12259
488 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 14.71089
489 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.12259
490 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 30050.24609
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 48.18412
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1457149.05790
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 9.63682
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 182143.63224
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 48.18412
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1457149.05790
497 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 9.63682
498 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 182143.63224
499 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 6.31250E-002
500 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 6.31250E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 15477.13
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 412907.44
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 87675.88
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 14705.37
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 10063.39
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 16506.43
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 7787.64
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 227934.01
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 149319.78
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 227935.33
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 144885.23
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 29132.18
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 19008.23
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 29132.42
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 18759.37
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 46500.35
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 474696.98
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 47759.63
19 Coil:Heating:Water CAV_BAS HEATING COIL 94838.35


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 232422.57 161697.30 70725.27 0.70 38298.26 388.44
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2193609.17 1518015.41 675593.75 0.69 358032.42 3631.36
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 237043.03 165152.37 71890.66 0.70 39153.74 397.12
4 Coil:Cooling:Water CAV_BAS COOLING COIL 130640.07 90298.50 40341.57 0.69 21428.90 217.34


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 8.97 30.62
2 Chiller:Electric:EIR COOLSYS1 CHILLER2 8.97 30.62


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.924 0.811   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.155 0.985   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 9.3309557413E-004 1.4002821530E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 3.3421652633E-003 6.1646518187E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 4.0347383169E-002 2.0139620593E-002 Pass Pass 0.4760147335 0.4985147116 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 3.6865056071E-002 4.3739137357E-002 Pass Pass 20.6447018177 45.2299290004 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 1.8452195248E-002 1.4746916914E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 1.8523373232E-002 1.4900365385E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.1889622254E-002 1.9382252454E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 1.9672182096E-002 1.7103640621E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.2635174686 0.2412891909 Pass Pass 44.0818078388 142.3510552346 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.2668379332 0.2457714128 Pass Pass 41.9237074927 120.8053055367 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.2197217372 0.2232258666 Pass Pass 70.1073928465 279.9490152212 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1401674464 0.1563738381 Pass Pass 31.3976744999 110.2527493729 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.3759688175 0.3709960603 Pass Pass 43.8449090064 333.2043174369 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.4157901287 0.3942323371 Pass Pass 55.2489516188 117.6410664007 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3775698834 0.3706134878 Pass Pass 59.3641148078 134.3406768825 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.3025320284 0.3041293671 Pass Pass 67.5297700242 178.9443607093 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.5575408816E-003 2.8845534172E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.3664834305E-002 2.0603230235E-002 Pass Pass 0.4759256929 0.4603030221 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.4939161614E-002 6.3839081521E-002 Pass Pass 0.4884524063 0.4774228163 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 6.0368703829E-006 5.9629272726E-006 Pass Pass 3.7147755125E-003 2.7836682153E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 6.0970869694E-003 4.0621355925E-003 Pass Pass 1.8125392384E-003 1.6084828021E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 8.7348785432E-003 6.5139429519E-003 Pass Pass 2.9255012466E-003 2.6382677120E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 5.1666297644E-006 2.5753070052E-006 Pass Pass 4.2306560814E-005 1.0851766858E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6686.12 148.33 0.00 26450.13 10431.32 43715.89



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 5.10 270.00
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 30.30 9.30 21.80 Wetbulb [C] 5.70 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 44.00 33      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 67.00 33      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.811 0.924 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.811 0.924 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.811 0.924 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.811 0.924 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.811 0.924 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.985 1.155 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.985 1.155 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.363_SHGC_NORTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.363_SHGC_EAST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.363_SHGC_EAST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.363_SHGC_EAST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.363_SHGC_SOUTH_0.378   23.18 0.00 0.00 23.18 23.18 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.363_SHGC_WEST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.363_SHGC_WEST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.363_SHGC_WEST_0.378   25.75 0.00 0.00 25.75 25.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.378   115.90 0.00 0.00 115.90 1158.95 2.062 0.379 0.417             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.378   77.26 0.00 0.00 77.26 772.63 2.062 0.379 0.417             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.378   115.90 0.00 0.00 115.90 1158.95 2.062 0.379 0.417             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.378   77.26 0.00 0.00 77.26 772.63 2.062 0.379 0.417             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.378   115.90 0.00 0.00 115.90 115.90 2.062 0.379 0.417             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.378   77.26 0.00 0.00 77.26 77.26 2.062 0.379 0.417             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.378   115.90 0.00 0.00 115.90 115.90 2.062 0.379 0.417             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.378   77.26 0.00 0.00 77.26 77.26 2.062 0.379 0.417             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.062 0.379 0.417                      
North Total or Average             1390.74 2.062 0.379 0.417                      
Non-North Total or Average             3245.06 2.062 0.379 0.417                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.5999 2779.43 18343.83 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 165.73
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.5999 24961.20 164740.46 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 1488.36
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.48 0.0000 Y 10.67
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.34 0.0000 Y 6.84
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.18 0.0000 Y 10.55
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.30 0.0000 Y 6.83
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.5999 3134.13 20684.81 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.43 0.0000 Y 106.52
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.31 0.0000 Y 68.33
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.5999 3134.20 20685.26 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.16 0.0000 Y 105.46
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.26 0.0000 Y 68.21
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.43 0.0000 Y 10.65
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.31 0.0000 Y 6.83
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.16 0.0000 Y 10.55
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.26 0.0000 Y 6.82
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 6.5999 783.68 5172.17 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 47.61
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 9.7790 362.03 3540.27 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 36.26
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
Interior Lighting Total       6.6297 46320.38 307089.14               775.32


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13271.55 AstronomicalClock -   42.04 42.04 104.74
EXTERIOR_LIGHTS_B 989.48 AstronomicalClock -   83.67 62.85 11.67
EXTERIOR_LIGHTS_C 26594.85 AstronomicalClock -   83.67 47.45 236.87
Exterior Lighting Total 40855.88           353.28



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2417661.91          
HEATSYS1 BOILER Boiler:HotWater 2372738.58 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1217264.50 5.91 1210235.40 5.88 8.97 30.62
COOLSYS1 CHILLER2 Chiller:Electric:EIR 1217264.50 5.91 1210235.40 5.88 8.97 30.62
CENTRAL TOWER FluidCooler:TwoSpeed 616556.86          
CENTRAL BOILER Boiler:HotWater 601379.40 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1457149.06          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1457149.06          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 199062.20 232422.57 161697.30 70725.27 0.70 - 38298.26 388.44
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1910140.56 2193609.17 1518015.41 675593.75 0.69 - 358032.42 3631.36
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 202158.94 237043.03 165152.37 71890.66 0.70 - 39153.74 397.12
CAV_BAS COOLING COIL Coil:Cooling:Water 113769.83 130640.07 90298.50 40341.57 0.69 - 21428.90 217.34
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   496305.63 349488.48 146817.14 0.70 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9679.56 6845.93 2833.63 0.71 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   92966.77 65704.12 27262.64 0.71 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9453.48 6682.26 2771.22 0.71 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16322.64 15477.13 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 435881.87 412907.44 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 92520.59 87675.88 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 15519.47 14705.37 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 10620.65 10063.39 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 17420.63 16506.43 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8218.43 7787.64 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 240574.18 227934.01 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 157600.80 149319.78 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 240575.57 227935.33 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 152919.73 144885.23 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 30748.75 29132.18 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 20063.05 19008.23 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 30749.00 29132.42 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 19800.36 18759.37 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 62573.55 46500.35 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 656277.62 474696.98 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 64351.66 47759.63 -
CAV_BAS HEATING COIL Coil:Heating:Water 100000.00 94838.35 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   496305.63 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9679.56 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   92966.77 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9453.48 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   22473.72 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1038.19 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   10381.93 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1038.19 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.22 21066.75 2283.73 1.00 1.12 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 85.94 196258.98 2283.73 1.00 1.07 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.44 21561.95 2283.73 1.00 1.11 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00
CAV_BAS FAN Fan:VariableVolume 0.60 1389.42 5.10 11725.01 2298.46 1.00 1.13 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 25.05 41321.86 1649.25 1.00 1.14 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.49 553.05 1120.11 1.00 1.61 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.74 5304.86 1120.11 1.00 1.16 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 539.58 1120.11 1.00 1.62 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.069358 11212.00 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.020758 6189.43 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.034679 3881.22 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.034679 3881.22 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.014900 3762.57 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.122591 30050.25 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 1.00 13.34 0.74



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 69097.63 69097.63 24.86 5.101 5.101 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00901 23.42 0.01335 1.200 0.00
CORE_BOTTOM 74750.57 74750.57 29.95 5.519 5.519 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00892 23.42 0.01335 1.078 0.00
CORE_MID 701857.16 701857.16 281.18 51.803 51.803 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00895 23.42 0.01335 10.778 0.00
CORE_TOP 69614.60 69614.60 27.89 5.138 5.138 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00895 23.42 0.01335 1.078 0.00
PERIMETER_BOT_ZN_3 12516.96 12516.96 39.94 0.933 0.933 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00887 30.30 0.01337 0.135 0.00
PERIMETER_BOT_ZN_2 17132.72 17132.72 84.83 1.277 1.277 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00868 25.18 0.01336 0.087 0.00
PERIMETER_BOT_ZN_1 19554.85 19554.85 62.39 1.457 1.457 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00874 29.99 0.01337 0.135 0.00
PERIMETER_BOT_ZN_4 20958.41 20958.41 103.77 1.562 1.562 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00865 28.84 0.01336 0.087 0.00
PERIMETER_MID_ZN_3 116814.34 116814.34 372.72 8.706 8.706 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00900 30.30 0.01337 1.353 0.00
PERIMETER_MID_ZN_2 183003.58 183003.58 906.07 13.639 13.639 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00871 25.71 0.01336 0.872 0.00
PERIMETER_MID_ZN_1 194069.56 194069.56 619.20 14.464 14.464 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00880 30.07 0.01337 1.353 0.00
PERIMETER_MID_ZN_4 192121.66 192121.66 951.21 14.319 14.319 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00870 28.69 0.01336 0.872 0.00
PERIMETER_TOP_ZN_3 13277.24 13277.24 42.36 0.990 0.990 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00897 30.30 0.01337 0.135 0.00
PERIMETER_TOP_ZN_2 18451.73 18451.73 91.36 1.375 1.375 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00873 25.98 0.01336 0.087 0.00
PERIMETER_TOP_ZN_1 20902.39 20902.39 66.69 1.558 1.558 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00881 30.14 0.01337 0.135 0.00
PERIMETER_TOP_ZN_4 20267.17 20267.17 100.34 1.511 1.511 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00871 28.84 0.01336 0.087 0.00
DATACENTER_BOT_ZN_6 8399.66 8399.66 232.02 0.494 0.494 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 26.50 0.01336 0.016 0.00
DATACENTER_MID_ZN_6 80568.54 80568.54 2225.48 4.736 4.736 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 26.50 0.01336 0.156 0.00
DATACENTER_TOP_ZN_6 8194.95 8194.95 226.36 0.482 0.482 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 27.00 27.00 0.00859 26.50 0.01336 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370641.09 426237.26 543.89 21.787 25.055 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 21.84 0.01335 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:10:00 21.00 23.26 0.00092 -16.30 0.00092 1.200 0.00
CORE_BOTTOM 650.01 650.01 0.26 0.028 1.078 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00110 -16.30 0.00092 1.078 0.00
CORE_MID 277230.59 277230.59 111.06 11.990 11.990 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -16.30 0.00092 10.778 0.00
CORE_TOP 64789.88 64789.88 25.96 2.825 2.825 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -16.30 0.00092 1.078 0.00
PERIMETER_BOT_ZN_3 10866.32 10866.32 34.67 0.474 0.474 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00764 -16.30 0.00092 0.135 0.00
PERIMETER_BOT_ZN_2 7435.56 7435.56 36.81 0.325 0.325 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -16.30 0.00092 0.087 0.00
PERIMETER_BOT_ZN_1 12195.10 12195.10 38.91 0.533 0.533 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00773 -16.30 0.00092 0.135 0.00
PERIMETER_BOT_ZN_4 5756.54 5756.54 28.50 0.251 0.251 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -16.30 0.00092 0.087 0.00
PERIMETER_MID_ZN_3 168369.76 168369.76 537.21 7.362 7.362 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -16.30 0.00092 1.353 0.00
PERIMETER_MID_ZN_2 110298.55 110298.55 546.10 4.823 4.823 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -16.30 0.00092 0.872 0.00
PERIMETER_MID_ZN_1 168370.74 168370.74 537.21 7.362 7.362 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -16.30 0.00092 1.353 0.00
PERIMETER_MID_ZN_4 107025.76 107025.76 529.90 4.680 4.680 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00763 -16.30 0.00092 0.872 0.00
PERIMETER_TOP_ZN_3 21516.34 21516.34 68.65 0.941 0.941 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -16.30 0.00092 0.135 0.00
PERIMETER_TOP_ZN_2 14039.03 14039.03 69.51 0.614 0.614 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -16.30 0.00092 0.087 0.00
PERIMETER_TOP_ZN_1 21516.52 21516.52 68.65 0.941 0.941 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -16.30 0.00092 0.135 0.00
PERIMETER_TOP_ZN_4 13855.34 13855.34 68.60 0.606 0.606 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -16.30 0.00092 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 25.14 0.00611 -16.30 0.00092 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.77 0.00154 -16.30 0.00092 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 20.70 0.00148 -16.30 0.00092 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 18.00 27.00 0.00850 -16.30 0.00092 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.22 9.22 2.66 2.66 9.2247 2.6608 9.2247 0.2884 0.3000
VAV_MID WITH REHEAT 85.94 85.94 36.22 36.22 85.9380 36.2162 85.9380 0.4214 0.3000
VAV_TOP WITH REHEAT 9.44 9.44 5.93 5.93 9.4416 5.9281 9.4416 0.6279 0.3000
CAV_BAS 5.10 5.10 1.20 1.20 5.1012 1.2002 5.1012 0.2353 1.0000
AIRLOOP DATACENTER BASEMENT 25.05 25.05 0.34 0.34 25.0550 25.0548 25.0550 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.49 0.49 0.02 0.02 0.4938 0.4938 0.4938 1.0000 1.0000
AIRLOOP DATACENTER MID 4.74 4.74 0.16 0.16 4.7360 4.7360 4.7360 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.48 0.48 0.02 0.02 0.4817 0.4817 0.4817 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16322.639 16322.639 1.617021 0.00014280 329.970 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16322.64 16322.64 1.617021 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00109934 7.0052 650.01 0.00 16382.73 16382.73
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 435881.867 435881.867 16.162624 0.00381328 10653.970 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 435881.87 435881.87 16.162624 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00800000 50.4185 277230.59 0.00 437285.21 437285.21
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 92520.594 92520.594 2.825071 0.00080941 2442.259 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 92520.59 92520.59 2.825071 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00800000 50.4185 64789.88 0.00 92840.30 92840.30
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 15519.471 15519.471 0.474426 0.00013577 409.450 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15519.47 15519.47 0.474426 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00764327 48.2015 10866.32 0.00 15571.54 15571.54
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 10620.652 10620.652 0.324722 0.00009291 280.184 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10620.65 10620.65 0.324722 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00767655 48.4086 7435.56 0.00 10656.14 10656.14
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 17420.631 17420.631 0.532682 0.00015240 459.554 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17420.63 17420.63 0.532682 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00773153 48.7505 12195.10 0.00 17478.69 17478.69
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8218.434 8218.434 0.251115 0.00007190 216.874 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8218.43 8218.43 0.251115 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00744282 46.9536 5756.54 0.00 8246.35 8246.35
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 240574.183 240574.183 7.361982 0.00210465 6344.028 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 240574.18 240574.18 7.361982 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00765114 48.2514 168369.76 0.00 241359.53 241359.53
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 157600.804 157600.804 4.823012 0.00137876 4155.928 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 157600.80 157600.80 4.823012 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00764635 48.2217 110298.55 0.00 158114.84 158114.84
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 240575.573 240575.573 7.362024 0.00210466 6344.065 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 240575.57 240575.57 7.362024 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00765114 48.2514 168370.74 0.00 241360.92 241360.92
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 152919.732 152919.732 4.679547 0.00133781 4032.571 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 152919.73 152919.73 4.679547 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00763373 48.1432 107025.76 0.00 153419.10 153419.10
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 30748.752 30748.752 0.941333 0.00026900 810.710 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30748.75 30748.75 0.941333 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00766911 48.3641 21516.34 0.00 30848.08 30848.08
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 20063.053 20063.053 0.614218 0.00017552 528.970 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20063.05 20063.05 0.614218 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00766239 48.3223 14039.03 0.00 20127.83 20127.83
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 30749.003 30749.003 0.941341 0.00026901 810.717 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30749.00 30749.00 0.941341 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00766912 48.3641 21516.52 0.00 30848.33 30848.33
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 19800.358 19800.358 0.606169 0.00017322 522.046 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19800.36 19800.36 0.606169 12.80 11.37 0.00800000 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 0.0000 21.00 0.00765793 48.2946 13855.34 0.00 19864.30 19864.30
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 199062.205 -999.000 9.224722 0.00569315 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 199062.20 159856.95 9.224722 25.42 17.77 0.00989584 10.90 10.90 0.00850000 30.30 0.01336696 21.83 22.0115 24.00 0.00888100 46.5821 120431.59 0.00 202826.78 157128.78
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 62573.552 62573.552 2.767417 0.00054742 1012.687 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 62573.55 62573.55 2.767417 -6.37 -7.19 0.00180950 12.80 11.37 0.00800000 -16.30 0.00092409 -16.30 73.3717 20.21 0.00537456 35.7120 22402.53 0.00 56234.53 56234.53
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1910140.556 -999.000 85.937991 0.05462978 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1910140.56 1503604.16 85.937991 25.57 17.95 0.01005436 10.90 10.90 0.00850000 30.30 0.01336696 21.83 23.6287 24.00 0.00895453 46.9628 1093073.28 0.00 1945437.69 1479485.63
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 656277.622 656277.622 25.781397 0.00574140 10485.171 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 656277.62 656277.62 25.781397 -8.78 -8.78 0.00232147 12.80 11.37 0.00800000 -16.30 0.00092409 -16.30 78.7622 18.05 0.00740353 56.0962 280580.38 0.00 574082.78 574082.78
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 202158.945 -999.000 9.441561 0.00578172 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 202158.94 162851.04 9.441561 25.36 17.73 0.00986722 10.90 10.90 0.00850000 30.30 0.01336696 21.83 21.5060 24.00 0.00890640 46.7141 126480.16 0.00 205953.31 160011.31
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 64351.664 64351.664 2.832468 0.00056298 1040.569 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 64351.66 64351.66 2.832468 -6.46 -6.46 0.00279493 12.80 11.37 0.00800000 -16.30 0.00092409 -16.30 71.6866 15.93 0.00755524 65.4838 28040.12 0.00 57772.27 57772.27
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 113769.830 -999.000 5.101242 0.00325380 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 113769.83 87793.01 5.101242 25.33 17.96 0.01017251 10.89 10.89 0.00850000 29.09 0.01336481 21.48 23.5267 24.00 0.00904705 47.4407 61779.91 0.00 115874.01 86416.59
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 100000.000 100000.000 3.116633 0.00087484 2622.476 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 100000.00 100000.00 3.116633 -3.83 -7.16 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 38.5081 23.36 0.00092409 5.1020 0.00 0.00 100076.34 100076.34
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 496305.627 349488.485 25.054988 0.01215449 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 460920.88 453838.57 -999.0 28.47 17.75 0.00860762 12.80 11.87 0.00850000 30.30 0.01336696 21.83 -999.0000 27.00 0.00854239 37.5167 370224.32 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9679.560 6845.929 0.493751 0.00023705 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 8972.85 8665.53 -999.0 27.95 17.68 0.00873733 12.80 11.87 0.00850000 26.50 0.01336023 20.72 -999.0000 27.00 0.00858618 37.7040 8399.66 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92966.765 65704.124 4.736027 0.00227675 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 86197.53 83125.96 -999.0 27.95 17.69 0.00874726 12.80 11.87 0.00850000 26.50 0.01336023 20.72 -999.0000 27.00 0.00858980 37.7198 80568.54 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9453.480 6682.260 0.481719 0.00023152 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 8764.80 8457.67 -999.0 27.96 17.69 0.00874308 12.80 11.87 0.00850000 26.67 0.01336053 20.77 -999.0000 27.00 0.00858819 37.7128 8193.85 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 496305.627 496305.627 25.054988 0.01215449 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 496305.63 496305.63 25.054988 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 1.3506 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9679.560 9679.560 0.493751 0.00023705 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9679.56 9679.56 0.493751 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.1660 25.76 0.00611149 28.9859 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92966.765 92966.765 4.736027 0.00227675 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 92966.77 92966.77 4.736027 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.3007 23.94 0.00154420 8.2246 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9453.480 9453.480 0.481719 0.00023152 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9453.48 9453.48 0.481719 -16.30 -16.30 0.00092409 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.2451 22.71 0.00147926 8.4873 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 22473.716 22473.716 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 22473.72 22473.72 25.054988 -0.22 -0.22 0.00839768 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 1.3506 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1038.193 1038.193 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1038.19 1038.19 0.493751 -0.52 -0.52 0.00594726 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.1660 25.76 0.00611149 28.9859 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 10381.926 10381.926 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10381.93 10381.93 4.736027 -0.54 -4.02 0.00152373 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.3007 23.94 0.00154420 8.2246 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1038.193 1038.193 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1038.19 1038.19 0.481719 -0.53 -4.12 0.00146125 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 3.2451 22.71 0.00147926 8.4873 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16322.639 16322.639 1.617021 0.00014280 329.970 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.6744 0.687924 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16322.64 16322.64 1.0000 1.89826245 1.617021 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.14278300 60.00 32.22 27.78 0.000 16322.64 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00109934 21.00 0.00109934 7.0052 650.01 0.00 16382.73 16382.73 1.89826245 12.80 11.60 0.00800000 33059.8 21.26 14.95 0.00800000 41690.2
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 435881.867 435881.867 16.162624 0.00381328 10653.970 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 18.0080 18.370413 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 435881.87 435881.87 1.0000 18.97371380 16.162624 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 3.81289572 60.00 32.22 27.78 0.000 435881.87 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.81 0.00800000 21.00 0.00800000 50.4185 277230.59 0.00 437285.21 437285.21 18.97371380 12.80 11.60 0.00800000 33059.8 35.40 19.78 0.00800000 56106.7
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 92520.594 92520.594 2.825071 0.00080941 2442.259 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 3.8224 3.899317 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 92520.59 92520.59 1.0000 3.31642249 2.825071 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.80932795 60.00 32.22 27.78 0.000 92520.59 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 50.4185 64789.88 0.00 92840.30 92840.30 3.31642249 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61053.9
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 15519.471 15519.471 0.474426 0.00013577 409.450 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.6412 0.654074 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15519.47 15519.47 1.0000 0.55694070 0.474426 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.13575725 60.00 32.22 27.78 0.000 15519.47 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00764327 21.00 0.00764327 48.2015 10866.32 0.00 15571.54 15571.54 0.55694070 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61018.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 10620.652 10620.652 0.324722 0.00009291 280.184 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.4388 0.447612 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10620.65 10620.65 1.0000 0.38119976 0.324722 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.09290462 60.00 32.22 27.78 0.000 10620.65 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00767655 21.00 0.00767655 48.4086 7435.56 0.00 10656.14 10656.14 0.38119976 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.0
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 17420.631 17420.631 0.532682 0.00015240 459.554 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.7197 0.734199 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17420.63 17420.63 1.0000 0.62532838 0.532682 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.15238773 60.00 32.22 27.78 0.000 17420.63 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00773153 21.00 0.00773153 48.7505 12195.10 0.00 17478.69 17478.69 0.62532838 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61011.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 8218.434 8218.434 0.251115 0.00007190 216.874 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.3395 0.346369 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8218.43 8218.43 1.0000 0.29479011 0.251115 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.07189111 60.00 32.22 27.78 0.000 8218.43 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.91 0.00744282 21.00 0.00744282 46.9536 5756.54 0.00 8246.35 8246.35 0.29479011 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61033.5
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 240574.183 240574.183 7.361982 0.00210465 6344.028 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 9.9391 10.139093 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 240574.18 240574.18 1.0000 8.64241679 7.361982 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 2.10443320 60.00 32.22 27.78 0.000 240574.18 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00765114 21.00 0.00765114 48.2514 168369.76 0.00 241359.53 241359.53 8.64241679 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.1
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 157600.804 157600.804 4.823012 0.00137876 4155.928 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 6.5111 6.642148 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 157600.80 157600.80 1.0000 5.66185635 4.823012 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.37861994 60.00 32.22 27.78 0.000 157600.80 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00764635 21.00 0.00764635 48.2217 110298.55 0.00 158114.84 158114.84 5.66185635 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.2
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 240575.573 240575.573 7.362024 0.00210466 6344.065 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 9.9391 10.139152 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 240575.57 240575.57 1.0000 8.64246644 7.362024 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 2.10444536 60.00 32.22 27.78 0.000 240575.57 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00765114 21.00 0.00765114 48.2514 168370.74 0.00 241360.92 241360.92 8.64246644 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.1
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 152919.732 152919.732 4.679547 0.00133781 4032.571 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 6.3177 6.444862 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 152919.73 152919.73 1.0000 5.49343904 4.679547 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.33767205 60.00 32.22 27.78 0.000 152919.73 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00763373 21.00 0.00763373 48.1432 107025.76 0.00 153419.10 153419.10 5.49343904 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.5
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 30748.752 30748.752 0.941333 0.00026900 810.710 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 1.2704 1.295918 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30748.75 30748.75 1.0000 1.10505514 0.941333 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.26897605 60.00 32.22 27.78 0.000 30748.75 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00766911 21.00 0.00766911 48.3641 21516.34 0.00 30848.08 30848.08 1.10505514 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60975.3
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 20063.053 20063.053 0.614218 0.00017552 528.970 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.8289 0.845565 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20063.05 20063.05 1.0000 0.72104582 0.614218 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.17550243 60.00 32.22 27.78 0.000 20063.05 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00766239 21.00 0.00766239 48.3223 14039.03 0.00 20127.83 20127.83 0.72104582 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60974.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 30749.003 30749.003 0.941341 0.00026901 810.717 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 1.2704 1.295929 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30749.00 30749.00 1.0000 1.10506416 0.941341 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.26897825 60.00 32.22 27.78 0.000 30749.00 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00766912 21.00 0.00766912 48.3641 21516.52 0.00 30848.33 30848.33 1.10506416 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60975.3
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 19800.358 19800.358 0.606169 0.00017322 522.046 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 0.8180 0.834494 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19800.36 19800.36 1.0000 0.71159731 0.606169 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.17320450 60.00 32.22 27.78 0.000 19800.36 -16.30 0.00092409 -16.30 0.00000000 0.0000 20.95 0.00765793 21.00 0.00765793 48.2946 13855.34 0.00 19864.30 19864.30 0.71159731 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60974.9
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 199062.205 -999.000 9.224722 0.00569315 -999.000 -999.0000 1.00000 1.00000 1023.2359 1004.8586 1.1739 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.224722 10.82913449   4197.9300 999.8980 69.35137964 15.00 6.67 8.33 2425131.54 8.2083 8.208305 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 199062.20 159856.95 1.0000 10.82913449 9.224722 25.42 17.77 0.00989584 50763.8 10.90 10.90 0.00850000 32381.8 5.69257309 6.67 15.00 8.33 21066.754 177995.45 30.30 0.01336696 21.83 2.03050000 22.0115 24.00 0.00888100 24.00 0.00888100 46.5821 120431.59 0.00 202826.78 157128.78 10.82913449 25.42 18.04 0.00989584 50763.8 11.24 11.16 0.00822249 32034.1
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 62573.552 62573.552 2.767417 0.00054742 1012.687 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.224722 10.82913449   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 2.5852 2.637187 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 62573.55 62573.55 1.0000 3.24874035 2.767417 -6.37 -7.19 0.00180950 -1894.5 12.80 11.37 0.00800000 33059.8 0.54736488 60.00 32.22 27.78 0.000 62573.55 -16.30 0.00092409 -16.30 2.03050000 73.3717 21.00 0.00424917 20.21 0.00537456 35.7120 22402.53 0.00 56234.53 56234.53 3.24874035 2.80 -1.48 0.00180950 7348.4 19.97 8.02 0.00180950 24658.1
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1910140.556 -999.000 85.937991 0.05462978 -999.000 -999.0000 1.00000 1.00000 1023.5305 1004.8586 1.1739 VAV_MID WITH REHEAT FAN Fan:VariableVolume 85.937991 100.88478251   4197.9300 999.8980 69.35137964 15.00 6.67 8.33 2425131.54 78.7644 78.764410 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1910140.56 1503604.16 1.0000 100.88478251 85.937991 25.57 17.95 0.01005436 51316.2 10.90 10.90 0.00850000 32382.3 54.62420530 6.67 15.00 8.33 196258.979 1713881.58 30.30 0.01336696 21.83 20.30600000 23.6287 24.00 0.00895453 24.00 0.00895453 46.9628 1093073.28 0.00 1945437.69 1479485.63 100.88478251 25.57 18.22 0.01005436 51316.2 11.24 11.16 0.00822289 32032.4
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 656277.622 656277.622 25.781397 0.00574140 10485.171 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV_MID WITH REHEAT FAN Fan:VariableVolume 85.937991 100.88478251   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 27.1134 27.659078 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 656277.62 656277.62 1.0000 30.26543475 25.781397 -8.78 -8.78 0.00232147 -3053.8 12.80 11.37 0.00800000 33059.8 5.74081725 60.00 32.22 27.78 0.000 656277.62 -16.30 0.00092409 -16.30 20.30600000 78.7622 19.11 0.00750375 18.05 0.00740353 56.0962 280580.38 0.00 574082.78 574082.78 30.26543475 2.80 -0.69 0.00232147 8631.5 21.60 9.36 0.00232147 27599.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 202158.945 -999.000 9.441561 0.00578172 -999.000 -999.0000 1.00000 1.00000 1023.1827 1004.8586 1.1739 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.441561 11.08368709   4197.9300 999.8980 69.35137964 15.00 6.67 8.33 2425131.54 8.3360 8.335999 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 202158.94 162851.04 1.0000 11.08368709 9.441561 25.36 17.73 0.00986722 50621.0 10.90 10.90 0.00850000 32381.7 5.78113043 6.67 15.00 8.33 21561.955 180596.99 30.30 0.01336696 21.83 2.03050000 21.5060 24.00 0.00890640 24.00 0.00890640 46.7141 126480.16 0.00 205953.31 160011.31 11.08368709 25.36 18.00 0.00986722 50621.0 11.25 11.17 0.00822358 32039.3
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 64351.664 64351.664 2.832468 0.00056298 1040.569 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.441561 11.08368709   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 2.6586 2.712126 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 04:50:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 64351.66 64351.66 1.0000 3.32510613 2.832468 -6.46 -6.46 0.00279493 465.4 12.80 11.37 0.00800000 33059.8 0.56291900 60.00 32.22 27.78 0.000 64351.66 -16.30 0.00092409 -16.30 2.03050000 71.6866 18.45 0.00753171 15.93 0.00755524 65.4838 28040.12 0.00 57772.27 57772.27 3.32510613 2.80 0.22 0.00279493 9818.1 20.00 9.17 0.00279493 27192.6
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 113769.830 -999.000 5.101242 0.00325380 -999.000 -999.0000 1.00000 1.00000 1023.7502 1004.8586 1.1739 CAV_BAS FAN Fan:VariableVolume 5.101242 5.98847732   4197.9300 999.8980 69.35137964 15.00 6.67 8.33 2425131.54 4.6913 4.691285 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 113769.83 87793.01 1.0000 5.98847732 5.101242 25.33 17.96 0.01017251 51368.3 10.89 10.89 0.00850000 32370.2 3.25347081 6.67 15.00 8.33 11725.009 102044.82 29.09 0.01336481 21.48 1.20015641 23.5267 24.00 0.00904705 24.00 0.00904705 47.4407 61779.91 0.00 115874.01 86416.59 5.98847732 25.33 18.23 0.01017251 51368.3 11.23 11.16 0.00822192 32018.8
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100000.000 100000.000 3.116633 0.00087484 2622.476 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 CAV_BAS FAN Fan:VariableVolume 5.101242 5.98847732   4197.9300 999.8980 20.75563469 54.44 82.22 27.78 2420490.89 4.1314 4.214539 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 100000.00 100000.00 1.0000 3.65869449 3.116633 -3.83 -7.16 0.00092409 -1548.9 40.00 20.89 0.00800000 60796.0 0.87475438 60.00 32.22 27.78 0.000 100000.00 -16.30 0.00092409 -16.30 1.20015641 38.5081 0.00 0.00092409 23.36 0.00092409 5.1020 0.00 0.00 100076.34 100076.34 3.65869449 12.80 1.98 0.00000000 12887.2 40.02 14.59 0.00000000 40240.2
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 496305.627 349488.485 25.054988 0.01215449 -999.000 -999.0000 -999.00000 -999.00000 1020.8411 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 460920.88 453838.57 0.9287 -999.0 -999.0 28.47 17.75 0.00860762 50591.3 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 460920.88 30.30 0.01336696 21.83 0.33839277 -999.0000 27.00 0.00854239 27.00 0.00854239 37.5167 370224.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9679.560 6845.929 0.493751 0.00023705 -999.000 -999.0000 -999.00000 -999.00000 1021.0823 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 8972.85 8665.53 0.9270 -999.0 -999.0 27.95 17.68 0.00873733 50393.7 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8972.85 26.50 0.01336023 20.72 0.01563234 -999.0000 27.00 0.00858618 27.00 0.00858618 37.7040 8399.66 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 92966.765 65704.124 4.736027 0.00227675 -999.000 -999.0000 -999.00000 -999.00000 1021.1007 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 86197.53 83125.96 0.9272 -999.0 -999.0 27.95 17.69 0.00874726 50418.3 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 86197.53 26.50 0.01336023 20.72 0.15632344 -999.0000 27.00 0.00858980 27.00 0.00858980 37.7198 80568.54 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9453.480 6682.260 0.481719 0.00023152 -999.000 -999.0000 -999.00000 -999.00000 1021.0929 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 8764.80 8457.67 0.9272 -999.0 -999.0 27.96 17.69 0.00874308 50413.6 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8764.80 26.67 0.01336053 20.77 0.01563234 -999.0000 27.00 0.00858819 27.00 0.00858819 37.7128 8193.85 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 496305.627 496305.627 25.054988 0.01215449 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 496305.63 496305.63 1.0000 29.41268437 25.054988 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 496305.63 -16.30 0.00092409 -16.30 0.33839277 1.3506 0.00 0.00850000 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9679.560 9679.560 0.493751 0.00023705 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9679.56 9679.56 1.0000 0.57962705 0.493751 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9679.56 -16.30 0.00092409 -16.30 0.01563234 3.1660 0.00 0.00611149 25.76 0.00611149 28.9859 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 92966.765 92966.765 4.736027 0.00227675 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 92966.77 92966.77 1.0000 5.55974242 4.736027 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 92966.77 -16.30 0.00092409 -16.30 0.15632344 3.3007 0.00 0.00154420 23.94 0.00154420 8.2246 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9453.480 9453.480 0.481719 0.00023152 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1739 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9453.48 9453.48 1.0000 0.56550178 0.481719 -16.30 -16.30 0.00092409 -14095.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9453.48 -16.30 0.00092409 -16.30 0.01563234 3.2451 0.00 0.00147926 22.71 0.00147926 8.4873 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 22473.716 22473.716 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 25.054988 29.41268437   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 22473.72 22473.72 1.0000 29.41268437 25.054988 -0.22 -0.22 0.00839768 20777.4 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 22473.72 -16.30 0.00092409 -16.30 0.33839277 1.3506 0.00 0.00850000 27.00 0.00850000 37.3272 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1038.193 1038.193 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.493751 0.57962705   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1038.19 1038.19 1.0000 0.57962705 0.493751 -0.52 -0.52 0.00594726 14349.5 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1038.19 -16.30 0.00092409 -16.30 0.01563234 3.1660 0.00 0.00611149 25.76 0.00611149 28.9859 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10381.926 10381.926 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.736027 5.55974242   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10381.93 10381.93 1.0000 5.55974242 4.736027 -0.54 -4.02 0.00152373 3268.6 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10381.93 -16.30 0.00092409 -16.30 0.15632344 3.3007 0.00 0.00154420 23.94 0.00154420 8.2246 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1038.193 1038.193 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.481719 0.56550178   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1038.19 1038.19 1.0000 0.56550178 0.481719 -0.53 -4.12 0.00146125 3121.5 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1038.19 -16.30 0.00092409 -16.30 0.01563234 3.2451 0.00 0.00147926 22.71 0.00147926 8.4873 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.22 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 85.94 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.44 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 5.10 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 25.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2744.83 1574.83 544.67
CORE_BOTTOM 2449.83 1321.67 12.83
CORE_MID 1824.50 2883.83 96.17
CORE_TOP 2469.83 3559.50 936.50
PERIMETER_BOT_ZN_3 2222.00 3211.83 468.83
PERIMETER_BOT_ZN_2 2549.83 3084.33 555.83
PERIMETER_BOT_ZN_1 2730.33 2855.50 593.50
PERIMETER_BOT_ZN_4 2889.50 2131.33 402.67
PERIMETER_MID_ZN_3 3147.50 3869.67 1752.67
PERIMETER_MID_ZN_2 2909.67 3073.17 1457.67
PERIMETER_MID_ZN_1 3099.17 3238.67 1181.67
PERIMETER_MID_ZN_4 3291.00 3455.50 1461.00
PERIMETER_TOP_ZN_3 3591.67 4109.17 2298.67
PERIMETER_TOP_ZN_2 3805.00 3724.67 2111.33
PERIMETER_TOP_ZN_1 3442.33 3553.67 1719.50
PERIMETER_TOP_ZN_4 3641.83 3728.50 1940.33
DATACENTER_BOT_ZN_6 5925.17 824.00 824.00
DATACENTER_MID_ZN_6 5171.00 221.67 133.83
DATACENTER_TOP_ZN_6 4647.00 667.83 283.17
DATACENTER_BASEMENT_ZN_6 5943.00 5516.50 5516.50
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5936.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 1461.83 0.00 860.67
CORE_BOTTOM 0.00 4.17 0.00 0.00
CORE_MID 1.50 0.00 0.67 0.00
CORE_TOP 14.67 0.00 2.83 0.00
PERIMETER_BOT_ZN_3 0.50 6.67 0.00 4.50
PERIMETER_BOT_ZN_2 0.83 35.67 0.00 34.67
PERIMETER_BOT_ZN_1 1.83 44.83 0.00 41.33
PERIMETER_BOT_ZN_4 0.00 115.83 0.00 54.00
PERIMETER_MID_ZN_3 71.50 1.00 19.83 1.00
PERIMETER_MID_ZN_2 71.17 33.67 0.17 33.00
PERIMETER_MID_ZN_1 27.50 41.33 0.50 40.17
PERIMETER_MID_ZN_4 24.00 45.50 0.17 25.33
PERIMETER_TOP_ZN_3 230.67 5.50 81.83 4.33
PERIMETER_TOP_ZN_2 113.50 34.50 14.67 31.83
PERIMETER_TOP_ZN_1 103.00 33.50 10.67 30.67
PERIMETER_TOP_ZN_4 79.00 48.00 8.33 26.83
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 127.67 0.00 92.50
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 282.83 1624.83 82.50 986.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 149.60 6779.02 0.977 0.000 0.000 0.000
CORE_BOTTOM 55.32 134.35 6849.35 0.954 0.000 0.000 0.000
CORE_MID 55.32 134.35 6849.35 0.708 0.000 0.000 0.000
CORE_TOP 55.32 134.35 6849.35 0.692 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.95 16.87 860.00 0.915 0.027 0.000 0.000
PERIMETER_BOT_ZN_2 4.48 10.87 554.22 1.270 0.028 0.000 0.000
PERIMETER_BOT_ZN_1 6.95 16.87 860.02 1.281 0.027 0.000 0.000
PERIMETER_BOT_ZN_4 4.48 10.87 554.22 1.779 0.028 0.000 0.000
PERIMETER_MID_ZN_3 6.95 16.87 860.00 0.750 0.062 0.000 0.000
PERIMETER_MID_ZN_2 3.91 10.87 554.22 1.086 0.068 0.000 0.000
PERIMETER_MID_ZN_1 6.95 16.87 860.02 1.167 0.062 0.000 0.000
PERIMETER_MID_ZN_4 4.48 10.87 554.22 1.181 0.064 0.000 0.000
PERIMETER_TOP_ZN_3 6.95 16.87 860.00 0.779 0.077 0.000 0.000
PERIMETER_TOP_ZN_2 4.48 10.87 554.22 1.217 0.080 0.000 0.000
PERIMETER_TOP_ZN_1 6.95 16.87 860.02 1.188 0.077 0.000 0.000
PERIMETER_TOP_ZN_4 4.48 10.87 554.22 1.220 0.080 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.37 42.18 1911.37 27.303 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.32 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.32 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.32 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.95 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.95 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.95 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.91 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.95 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.95 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.95 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.48 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.37 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 61.60 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.32 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.32 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.32 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.95 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.95 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.95 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.91 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.95 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.95 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.95 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.80 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.37 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1020.85 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 38520511.34 0.00 38520511.34 0.00 38520511.34 37848132.68 4851.01 1093.19 2815.80 0.00
CORE_BOTTOM 40767808.32 0.00 40767808.32 0.00 40767808.32 33990283.35 3945.69 141.39 4672.93 516.18
CORE_MID 0.29E+09 0.00 0.29E+09 0.00 0.29E+09 0.34E+09 4655.47 749.07 3355.47 314.73
CORE_TOP 28468448.96 0.00 28468448.96 0.00 28468448.96 33990283.35 4879.75 1064.37 2815.89 409.54
PERIMETER_BOT_ZN_3 4906409.58 0.00 4906409.58 263099.47 5169509.06 4267819.30 5135.21 179.62 3445.18 516.18
PERIMETER_BOT_ZN_2 4306643.67 0.00 4306643.67 175399.53 4482043.20 2750345.05 5020.79 317.71 3421.50 516.18
PERIMETER_BOT_ZN_1 6744574.17 0.00 6744574.17 263099.47 7007673.64 4267912.63 4818.84 266.63 3674.53 516.18
PERIMETER_BOT_ZN_4 6076624.08 0.00 6076624.08 175399.53 6252023.61 2750345.05 4149.27 143.64 4467.09 516.18
PERIMETER_MID_ZN_3 38871482.97 0.00 38871482.97 617042.04 39488525.01 42678193.03 4732.57 732.57 3294.85 314.73
PERIMETER_MID_ZN_2 36854229.70 0.00 36854229.70 411361.08 37265590.78 27503450.52 4828.97 570.29 3360.74 832.79
PERIMETER_MID_ZN_1 59784463.85 0.00 59784463.85 617042.04 60401505.89 42679126.28 4329.55 921.64 3508.81 314.73
PERIMETER_MID_ZN_4 39425018.36 0.00 39425018.36 411361.08 39836379.44 27503450.52 4550.01 984.71 3225.27 314.73
PERIMETER_TOP_ZN_3 4025814.92 0.00 4025814.92 766123.54 4791938.46 4267819.30 4411.96 1056.33 3291.71 409.54
PERIMETER_TOP_ZN_2 4007199.74 0.00 4007199.74 510748.68 4517948.42 2750345.05 4364.31 1162.73 3232.96 409.54
PERIMETER_TOP_ZN_1 6073239.34 0.00 6073239.34 766123.54 6839362.88 4267912.63 4275.70 1262.72 3221.57 409.54
PERIMETER_TOP_ZN_4 4072982.99 0.00 4072982.99 510748.68 4583731.66 2750345.05 4314.07 761.12 3684.81 409.54
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.43E+09 0.00 0.43E+09 0.00 0.43E+09 10671554.30 18.83 123.42 8617.75 2815.33
Total Facility 0.53E+10 0.00 0.53E+10 23998804.81 0.53E+10 0.50E+10 7088.33 4363.68 8746.53 3334.56


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.8005 0.0000 1.8005 0.0000 1.8005 1.2002 2034.01 1093.19 2815.80
CORE_BOTTOM 1.7750 0.0000 1.7750 0.0000 1.7750 1.0778 1555.22 139.29 4248.49
CORE_MID 13.1955 0.0000 13.1955 0.0000 13.1955 10.7782 1971.58 748.62 3222.80
CORE_TOP 1.2896 0.0000 1.2896 0.0000 1.2896 1.0778 2183.44 1064.12 2695.44
PERIMETER_BOT_ZN_3 0.2138 0.0000 0.2138 0.0062 0.2201 0.1353 2736.65 177.38 3028.98
PERIMETER_BOT_ZN_2 0.1914 0.0000 0.1914 0.0042 0.1956 0.0872 2622.35 314.15 3006.50
PERIMETER_BOT_ZN_1 0.2998 0.0000 0.2998 0.0062 0.3060 0.1353 2421.16 263.20 3258.64
PERIMETER_BOT_ZN_4 0.2680 0.0000 0.2680 0.0042 0.2721 0.0872 1758.18 141.81 4043.01
PERIMETER_MID_ZN_3 1.7571 0.0000 1.7571 0.0146 1.7717 1.3533 2050.28 731.68 3161.04
PERIMETER_MID_ZN_2 1.6380 0.0000 1.6380 0.0103 1.6484 0.8721 1688.57 567.37 2778.05
PERIMETER_MID_ZN_1 2.7341 0.0000 2.7341 0.0146 2.7488 1.3533 1649.29 921.31 3372.40
PERIMETER_MID_ZN_4 1.7812 0.0000 1.7812 0.0098 1.7909 0.8721 1872.24 984.41 3086.35
PERIMETER_TOP_ZN_3 0.1827 0.0000 0.1827 0.0182 0.2009 0.1353 1716.98 1055.91 3170.11
PERIMETER_TOP_ZN_2 0.1837 0.0000 0.1837 0.0121 0.1958 0.0872 1672.02 1162.37 3108.61
PERIMETER_TOP_ZN_1 0.2783 0.0000 0.2783 0.0182 0.2965 0.1353 1581.85 1262.45 3098.70
PERIMETER_TOP_ZN_4 0.1840 0.0000 0.1840 0.0121 0.1962 0.0872 1620.56 761.00 3561.43
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 14.0226 0.0000 14.0226 0.0000 14.0226 0.3384 17.17 123.42 5802.42
Total Facility 232.9128 0.0000 232.9128 0.5751 233.4879 158.4706 4271.33 4357.80 5930.03


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 86547775.73 0.00 86547775.73 48026705.38 3482.76 3.87 5273.37 516.18
VAV_MID WITH REHEAT 0.64E+09 0.00 0.64E+09 0.48E+09 3952.10 2.46 4805.43 314.73
VAV_TOP WITH REHEAT 64285617.39 0.00 64285617.39 48026705.38 3995.56 1.89 4762.55 409.07
CAV_BAS 53085145.75 0.00 53085145.75 37848132.68 4824.42 0.08 3935.50 0.00
AIRLOOP DATACENTER BASEMENT 0.60E+09 0.00 0.60E+09 10671554.30 18.83 0.00 8741.17 2815.33
AIRLOOP DATACENTER BOT 336664.50 0.00 336664.50 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3366645.00 0.00 3366645.00 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 336664.50 0.00 336664.50 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.7870 0.0000 3.7870 1.5229 1123.27 2.40 4817.32
VAV_MID WITH REHEAT 29.1475 0.0000 29.1475 15.2292 1275.76 2.24 4665.00
VAV_TOP WITH REHEAT 2.9193 0.0000 2.9193 1.5229 1302.85 1.74 4638.42
CAV_BAS 2.4812 0.0000 2.4812 1.2002 2007.42 0.08 3935.50
AIRLOOP DATACENTER BASEMENT 19.3245 0.0000 19.3245 0.3384 17.17 0.00 5925.83
AIRLOOP DATACENTER BOT 0.0157 0.0000 0.0157 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1574 0.0000 0.1574 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0157 0.0000 0.0157 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 783.88 3287.79 0.00 0.00 0.00 1372.59 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 314.21 2707.26 0.00 0.00 0.00 2121.98 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 56.49 2881.03 0.00 0.00 0.00 2353.35 0.00 0.00 0.00
CAV_BAS 0.00 1074.06 2830.11 0.00 47.84 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 123.42 8617.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.8153 6.1698 0.0000 0.0000 0.0000 2.3336 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 27.6836 49.0606 0.0000 0.0000 0.0000 22.2332 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.7179 4.8666 0.0000 0.0000 0.0000 2.1979 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6540 4.5612 0.0000 1.3020 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4679 19.7843 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2155 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1521
Defaulted Fields 1185
Fields with Defaults 3940
Autosized Fields 338
Autosizable Fields 416
Autocalculated Fields 227
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
Electricity:Building 17137.56 216479.19 07-MAY-17:20 1025582.59 01-DEC-16:40
Electricity:Zone:BASEMENT 590.13 14055.89 01-JAN-00:10 28201.58 02-JAN-08:10
Electricity:SpaceType:GENERAL 17137.56 216479.19 07-MAY-17:20 1025582.59 01-DEC-16:40
InteriorLights:Electricity 2461.16 9223.03 26-MAR-17:20 247210.90 02-JAN-16:50
InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2461.16 9223.03 26-MAR-17:20 247210.90 02-JAN-16:50
LightsWired:InteriorLights:Electricity 2461.16 9223.03 26-MAR-17:20 247210.90 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2461.16 9223.03 26-MAR-17:20 247210.90 02-JAN-16:50
Electricity:Zone:CORE_BOTTOM 438.45 4990.59 01-JAN-00:10 30447.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:CORE_MID 4384.49 49905.77 01-JAN-00:10 304477.41 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
Electricity:Zone:CORE_TOP 438.45 4990.58 01-JAN-00:10 30447.74 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 47.03 603.11 12-MAR-17:10 3823.11 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.67 43.94 01-JAN-10:10 1662.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.67 43.94 01-JAN-10:10 1662.56 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_2 30.28 388.67 26-MAR-17:10 2463.76 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.84 28.32 01-JAN-09:10 1071.42 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.84 28.32 01-JAN-09:10 1071.42 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_1 46.92 603.12 12-MAR-17:10 3823.18 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.55 43.94 01-JAN-09:10 1662.60 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.55 43.94 01-JAN-09:10 1662.60 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_4 30.27 388.67 12-MAR-17:10 2463.75 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.83 28.32 01-JAN-09:50 1071.42 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.83 28.32 01-JAN-09:50 1071.42 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_3 470.18 6031.15 12-MAR-17:10 38231.14 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 106.52 439.44 01-JAN-10:00 16625.62 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 106.52 439.44 01-JAN-10:00 16625.62 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_2 302.68 3886.70 26-MAR-17:10 24637.60 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 68.33 283.19 01-JAN-09:00 10714.18 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 68.33 283.19 01-JAN-09:00 10714.18 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_1 469.12 6031.24 12-MAR-17:10 38231.83 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 105.46 439.45 01-JAN-09:00 16625.99 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 105.46 439.45 01-JAN-09:00 16625.99 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_4 302.56 3886.68 12-MAR-17:10 24637.51 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 68.21 283.19 01-JAN-09:40 10714.18 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 68.21 283.19 01-JAN-09:40 10714.18 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_3 47.02 603.11 12-MAR-17:10 3823.11 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.65 43.94 01-JAN-10:00 1662.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.65 43.94 01-JAN-10:00 1662.56 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_2 30.27 388.67 26-MAR-17:10 2463.76 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.83 28.32 01-JAN-09:00 1071.42 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.83 28.32 01-JAN-09:00 1071.42 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_1 46.91 603.12 12-MAR-17:10 3823.18 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.55 43.94 01-JAN-09:00 1662.60 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.55 43.94 01-JAN-09:00 1662.60 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_4 30.26 388.67 12-MAR-17:10 2463.75 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.82 28.32 01-JAN-09:40 1071.42 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.82 28.32 01-JAN-09:40 1071.42 02-JAN-16:50
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7542.47 95139.07 01-JAN-00:10 383789.71 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1575.07 19661.97 01-JAN-00:10 81110.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1813.43 3824.30 31-JAN-02:00 556952.44 05-JUL-15:50
HeatRejection:Electricity 477.95 56.85 06-JAN-08:00 79472.29 14-MAR-12:20
General:HeatRejection:Electricity 477.95 56.85 06-JAN-08:00 79472.29 14-MAR-12:20
Electricity:HVAC 4783.01 53884.28 29-SEP-05:00 468191.28 03-AUG-15:30
ExteriorEquipment:Electricity 2566.27 20217.42 01-JAN-00:10 233396.00 02-NOV-07:20
Transformer:ExteriorEquipment:Electricity 54.68 979.82 01-JAN-00:10 3412.97 01-DEC-16:50
ElectricityPurchased:Facility 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
ElectricityPurchased:Plant 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
Cogeneration:ElectricityPurchased 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
General:Cogeneration:ElectricityPurchased 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
ElectricityNet:Plant 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
Cogeneration:ElectricityNet 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
General:Cogeneration:ElectricityNet 26598.87 296344.49 21-MAY-05:00 2111016.45 15-AUG-14:40
Fans:Electricity 2360.91 47719.36 02-JAN-22:10 274878.55 10-AUG-15:20
General:Fans:Electricity 2360.91 47719.36 02-JAN-22:10 274878.55 10-AUG-15:20
ExteriorLights:Electricity 353.28 0.00 01-JAN-08:00 40855.88 01-JAN-06:10
General:ExteriorLights:Electricity 353.28 0.00 01-JAN-08:00 40855.88 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 2505.76 19200.00 01-JAN-00:10 229608.34 02-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 36.73 0.00 01-JAN-00:10 4520.72 02-JAN-07:10
General:HeatRecovery:Electricity 36.73 0.00 01-JAN-00:10 4520.72 02-JAN-07:10
Cooling:Electricity 1396.53 1651.97 07-JAN-09:00 528085.65 05-JUL-15:50
General:Cooling:Electricity 1396.53 1651.97 07-JAN-09:00 528085.65 05-JUL-15:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1463.05 0.00 11-JAN-13:10 100000.00 14-FEB-22:10
General:Humidifier:Electricity 1463.05 0.00 11-JAN-13:10 100000.00 14-FEB-22:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 459.85 0.00 01-JAN-00:10 56293.54 13-FEB-12:30
Water Heater:WaterSystems:Electricity 459.85 0.00 01-JAN-00:10 56293.54 13-FEB-12:30
Pumps:Electricity 346.74 3762.57 01-JAN-00:40 48849.73 05-JUL-16:00
General:Pumps:Electricity 346.74 3762.57 01-JAN-00:40 48849.73 05-JUL-16:00
WIRED_LTG_ELECTRICITY 69.16 0.00 01-JAN-00:10 6946.63 02-JAN-17:00
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1151.06 0.00 01-JAN-00:40 1582955.37 02-JAN-05:10
NaturalGas:Plant 1151.06 0.00 01-JAN-00:40 1582955.37 02-JAN-05:10
Heating:NaturalGas 1151.06 0.00 01-JAN-00:40 1582955.37 02-JAN-05:10
Boiler:Heating:NaturalGas 1151.06 0.00 01-JAN-00:40 1582955.37 02-JAN-05:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 8710.40 4292.24 07-JAN-09:00 3187674.13 15-AUG-14:40
PlantLoopCoolingDemand:HVAC 8710.40 4292.24 07-JAN-09:00 3187674.13 15-AUG-14:40
CoolingCoils:PlantLoopCoolingDemand 8710.40 4292.24 07-JAN-09:00 3187674.13 15-AUG-14:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 6164.37 0.00 11-MAR-01:00 0.00 17-AUG-12:50
Water:HVAC 544.26 0.00 11-JAN-13:10 0.00 22-FEB-04:10
Humidifier:Water 544.26 0.00 11-JAN-13:10 0.00 22-FEB-04:10
General:Humidifier:Water 544.26 0.00 11-JAN-13:10 0.00 22-FEB-04:10
MainsWater:Facility 6164.37 0.00 11-MAR-01:00 0.00 17-AUG-12:50
MainsWater:HVAC 544.26 0.00 11-JAN-13:10 0.00 22-FEB-04:10
Humidifier:MainsWater 544.26 0.00 11-JAN-13:10 0.00 22-FEB-04:10
General:Humidifier:MainsWater 544.26 0.00 11-JAN-13:10 0.00 22-FEB-04:10
Water:Plant 5620.11 0.00 01-JAN-00:10 0.00 17-AUG-12:50
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 5620.11 0.00 01-JAN-00:10 0.00 17-AUG-12:50
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 3339.94 0.00 01-JAN-00:10 0.00 04-AUG-13:30
General:HeatRejection:Water 3339.94 0.00 01-JAN-00:10 0.00 04-AUG-13:30
HeatRejection:MainsWater 3339.94 0.00 01-JAN-00:10 0.00 04-AUG-13:30
General:HeatRejection:MainsWater 3339.94 0.00 01-JAN-00:10 0.00 04-AUG-13:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 43841.73 94811.77 30-JAN-05:40 12186338.00 05-JUL-16:00
EnergyTransfer:Building 17563.12 88273.84 21-JAN-18:10 1667975.50 09-AUG-15:30
EnergyTransfer:Zone:BASEMENT 548.57 0.00 01-JAN-00:10 97434.21 13-JUN-06:10
Heating:EnergyTransfer 708.45 0.00 01-FEB-00:20 1173490.52 02-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 708.45 0.00 01-FEB-00:20 1173490.52 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 16854.67 85673.48 30-JAN-05:00 1667975.50 09-AUG-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 548.57 0.00 01-JAN-00:10 97434.21 13-JUN-06:10
General:Cooling:EnergyTransfer 16854.67 85673.48 30-JAN-05:00 1667975.50 09-AUG-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 548.57 0.00 01-JAN-00:10 97434.21 13-JUN-06:10
EnergyTransfer:Zone:CORE_BOTTOM 582.68 0.00 01-JAN-00:10 59980.76 15-AUG-16:00
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 582.68 0.00 01-JAN-00:10 59980.76 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 582.68 0.00 01-JAN-00:10 59980.76 15-AUG-16:00
EnergyTransfer:Zone:CORE_MID 3862.23 0.00 01-JAN-00:40 427637.51 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_MID 8.69 0.00 01-JAN-00:10 427637.51 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 8.69 0.00 01-JAN-00:10 427637.51 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 3853.54 0.00 01-JAN-00:40 399559.86 24-JUL-13:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 3853.54 0.00 01-JAN-00:40 399559.86 24-JUL-13:10
EnergyTransfer:Zone:CORE_TOP 350.05 0.00 01-JAN-00:40 65849.95 26-DEC-05:20
Heating:EnergyTransfer:Zone:CORE_TOP 17.85 0.00 01-JAN-00:40 65849.95 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 17.85 0.00 01-JAN-00:40 65849.95 26-DEC-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 332.20 0.00 01-JAN-00:20 47163.06 21-JUL-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 332.20 0.00 01-JAN-00:20 47163.06 21-JUL-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 64.67 0.00 01-JAN-00:10 11942.72 21-JUL-13:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.90 0.00 01-JAN-00:10 6894.19 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.90 0.00 01-JAN-00:10 6894.19 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 63.77 0.00 01-JAN-00:10 11942.72 21-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 63.77 0.00 01-JAN-00:10 11942.72 21-JUL-13:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 56.67 0.00 01-JAN-00:10 15146.09 10-JUL-07:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.79 0.00 01-JAN-00:10 5186.30 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.79 0.00 01-JAN-00:10 5186.30 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 55.88 0.00 01-JAN-00:10 15146.09 10-JUL-07:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 55.88 0.00 01-JAN-00:10 15146.09 10-JUL-07:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 94.12 0.00 01-JAN-00:10 20916.70 31-OCT-13:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 1.66 0.00 01-JAN-00:10 9536.84 07-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 1.66 0.00 01-JAN-00:10 9536.84 07-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 92.46 0.00 01-JAN-00:10 20916.70 31-OCT-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 92.46 0.00 01-JAN-00:10 20916.70 31-OCT-13:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 85.82 0.00 01-JAN-00:10 18276.29 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.08 0.00 01-JAN-00:10 2636.75 30-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.08 0.00 01-JAN-00:10 2636.75 30-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 85.74 0.00 01-JAN-00:10 18276.29 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 85.74 0.00 01-JAN-00:10 18276.29 10-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 560.39 0.00 01-JAN-00:40 121064.35 06-FEB-04:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 149.82 0.00 01-JAN-00:40 121064.35 06-FEB-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 149.82 0.00 01-JAN-00:40 121064.35 06-FEB-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 410.57 0.00 01-JAN-00:10 97970.18 21-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 410.57 0.00 01-JAN-00:10 97970.18 21-JUL-13:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 520.77 0.00 01-JAN-00:40 156409.12 13-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 81.64 0.00 01-JAN-00:40 120244.52 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 81.64 0.00 01-JAN-00:40 120244.52 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 439.13 0.00 01-JAN-00:10 156409.12 13-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 439.13 0.00 01-JAN-00:10 156409.12 13-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 856.79 0.00 01-JAN-00:40 218072.79 31-OCT-13:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 89.89 0.00 01-JAN-00:40 167791.14 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 89.89 0.00 01-JAN-00:40 167791.14 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 766.90 0.00 01-JAN-00:10 218072.79 31-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 766.90 0.00 01-JAN-00:10 218072.79 31-OCT-13:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 557.01 0.00 01-JAN-00:40 168133.15 02-JUL-17:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 66.04 0.00 01-JAN-00:40 111456.37 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 66.04 0.00 01-JAN-00:40 111456.37 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 490.97 0.00 01-JAN-00:10 168133.15 02-JUL-17:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 490.97 0.00 01-JAN-00:10 168133.15 02-JUL-17:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 71.94 0.00 01-JAN-00:40 14289.01 26-DEC-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 34.30 0.00 01-JAN-00:40 14289.01 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 34.30 0.00 01-JAN-00:40 14289.01 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 37.65 0.00 01-JAN-00:10 10824.59 21-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 37.65 0.00 01-JAN-00:10 10824.59 21-JUL-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 62.48 0.00 01-JAN-00:40 16604.20 06-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 19.51 0.00 01-JAN-00:40 16604.20 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 19.51 0.00 01-JAN-00:40 16604.20 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 42.98 0.00 01-JAN-00:20 15375.36 03-JUL-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 42.98 0.00 01-JAN-00:20 15375.36 03-JUL-08:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 93.16 0.00 01-JAN-00:40 22116.54 31-OCT-13:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 23.26 0.00 01-JAN-00:40 20778.01 26-DEC-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 23.26 0.00 01-JAN-00:40 20778.01 26-DEC-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 69.90 0.00 01-JAN-00:20 22116.54 31-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 69.90 0.00 01-JAN-00:20 22116.54 31-OCT-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 62.02 0.00 01-JAN-00:40 17468.80 02-JUL-17:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 15.52 0.00 01-JAN-00:40 15423.61 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 15.52 0.00 01-JAN-00:40 15423.61 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 46.50 0.00 01-JAN-00:20 17468.80 02-JUL-17:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 46.50 0.00 01-JAN-00:20 17468.80 02-JUL-17:10
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 53.64 0.00 01-JAN-00:10 10245.07 17-JUL-07:10
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.50 0.00 01-JAN-00:10 4431.46 10-DEC-12:30
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.50 0.00 01-JAN-00:10 4431.46 10-DEC-12:30
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 49.15 0.00 01-JAN-00:10 10245.07 17-JUL-07:10
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 49.15 0.00 01-JAN-00:10 10245.07 17-JUL-07:10
EnergyTransfer:Zone:MIDFLOOR_PLENUM 420.75 0.00 01-JAN-00:40 152807.24 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 140.11 0.00 01-JAN-00:40 152807.24 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 140.11 0.00 01-JAN-00:40 152807.24 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 280.64 0.00 01-JAN-00:10 69523.96 17-JUL-14:20
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 280.64 0.00 01-JAN-00:10 69523.96 17-JUL-14:20
EnergyTransfer:Zone:TOPFLOOR_PLENUM 93.05 0.00 01-JAN-00:40 27886.41 06-FEB-05:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 47.79 0.00 01-JAN-00:40 27886.41 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 47.79 0.00 01-JAN-00:40 27886.41 06-FEB-05:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 45.26 0.00 01-JAN-00:10 18465.07 12-JUN-13:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 45.26 0.00 01-JAN-00:10 18465.07 12-JUN-13:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.60 294.18 30-JAN-06:00 8244.54 02-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.60 294.18 30-JAN-06:00 8244.54 02-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 136.60 294.18 30-JAN-06:00 8244.54 02-AUG-18:40
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1167.23 6.04 10-JAN-21:50 79120.02 02-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 5.24 0.00 03-JAN-07:30 5497.74 03-JAN-01:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 5.24 0.00 03-JAN-07:30 5497.74 03-JAN-01:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1161.99 0.00 01-JAN-00:10 79120.02 02-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1161.99 0.00 01-JAN-00:10 79120.02 02-AUG-18:40
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 106.46 0.05 26-JAN-20:30 7965.22 02-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.89 0.00 03-JAN-07:40 588.75 15-JAN-18:50
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.89 0.00 03-JAN-07:40 588.75 15-JAN-18:50
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 105.57 0.00 01-JAN-00:10 7965.22 02-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 105.57 0.00 01-JAN-00:10 7965.22 02-AUG-18:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7156.02 85367.36 30-JAN-05:00 375075.88 15-AUG-17:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7156.02 85367.36 30-JAN-05:00 375075.88 15-AUG-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7156.02 85367.36 30-JAN-05:00 375075.88 15-AUG-17:00
PlantLoopHeatingDemand:Facility 1294.59 0.00 01-JAN-00:40 1274776.93 02-JAN-06:20
PlantLoopHeatingDemand:Plant 454.52 0.00 01-JAN-00:10 56067.89 15-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 454.52 0.00 01-JAN-00:10 56067.89 15-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 454.52 0.00 01-JAN-00:10 56067.89 15-FEB-12:10
EnergyTransfer:HVAC 10818.96 3339.86 30-JAN-01:40 3033142.30 15-AUG-14:40
HeatingCoils:EnergyTransfer 840.07 0.00 01-JAN-00:40 1268093.58 02-JAN-06:20
PlantLoopHeatingDemand:HVAC 840.07 0.00 01-JAN-00:40 1268093.58 02-JAN-06:20
HeatingCoils:PlantLoopHeatingDemand 840.07 0.00 01-JAN-00:40 1268093.58 02-JAN-06:20
CoolingCoils:EnergyTransfer 7842.77 2640.27 07-JAN-09:00 3033142.30 15-AUG-14:40
HeatRecoveryForHeating:EnergyTransfer 2021.97 0.00 01-JAN-00:10 727067.77 07-FEB-07:10
HeatRecoveryForCooling:EnergyTransfer 114.16 0.00 01-JAN-00:10 349030.47 15-JUL-14:00
EnergyTransfer:Plant 15459.64 0.00 01-JAN-00:40 7789062.13 05-JUL-16:00
LoopToLoop:EnergyTransfer 4542.13 0.00 01-JAN-00:10 2495423.53 05-JUL-16:00
WaterSystems:EnergyTransfer 454.52 0.00 01-JAN-00:10 56067.89 15-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 454.52 0.00 01-JAN-00:10 56067.89 15-FEB-12:10
Boilers:EnergyTransfer 835.77 0.00 01-JAN-00:40 1315873.58 02-JAN-05:10
Chillers:EnergyTransfer 4549.17 0.00 01-JAN-00:10 2434529.00 05-JUL-15:50
HeatRejection:EnergyTransfer 5078.06 0.00 01-JAN-00:10 2829301.86 05-JUL-15:50
General:HeatRejection:EnergyTransfer 5078.06 0.00 01-JAN-00:10 2829301.86 05-JUL-15:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -548.560 0.000 0.000 90.115 165.729 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -131.682
CORE_BOTTOM 0.000 0.000 0.000 -582.679 0.000 0.000 83.469 148.837 289.614 0.000 0.000 0.000 60.760 0.000 0.000 0.000 0.000 -0.008
CORE_MID 0.000 0.000 8.687 -3853.532 0.000 0.000 854.143 1488.366 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1393.792
CORE_TOP 0.000 0.000 17.847 -332.200 0.000 0.000 88.491 148.837 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -212.587
PERIMETER_BOT_ZN_3 0.000 0.000 0.896 -63.770 0.000 0.000 10.913 10.669 36.365 27.919 0.000 0.022 53.226 0.000 -71.334 0.000 -4.907 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.786 -55.881 0.000 0.000 6.999 6.840 23.435 53.444 0.000 0.015 11.760 0.000 -44.145 0.000 -3.254 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 1.661 -92.456 0.000 0.000 10.809 10.554 36.366 99.836 0.000 0.021 3.058 0.000 -64.954 0.000 -4.895 -0.002
PERIMETER_BOT_ZN_4 0.000 0.000 0.075 -85.741 0.000 0.000 6.835 6.830 23.435 52.633 0.000 0.014 49.968 0.000 -50.488 0.000 -3.561 0.000
PERIMETER_MID_ZN_3 0.000 0.000 149.819 -410.570 0.000 0.000 113.824 106.521 363.654 288.996 0.000 0.504 134.694 0.000 -644.508 0.000 -102.934 -0.003
PERIMETER_MID_ZN_2 0.000 0.000 81.639 -439.125 0.000 0.000 52.997 68.327 234.352 534.936 0.000 0.302 0.003 0.000 -410.082 0.000 -70.283 -53.064
PERIMETER_MID_ZN_1 0.000 0.000 89.892 -766.898 0.000 0.000 110.476 105.460 363.660 996.832 0.000 0.468 0.017 0.000 -622.299 0.000 -108.520 -169.071
PERIMETER_MID_ZN_4 0.000 0.000 66.041 -490.964 0.000 0.000 72.236 68.214 234.351 536.265 0.000 0.306 23.530 0.000 -437.744 0.000 -72.234 -0.004
PERIMETER_TOP_ZN_3 0.000 0.000 34.295 -37.647 0.000 0.000 11.549 10.651 36.365 29.406 0.000 0.057 0.001 0.000 -60.866 0.000 -12.136 -11.675
PERIMETER_TOP_ZN_2 0.000 0.000 19.507 -42.975 0.000 0.000 7.307 6.832 23.435 54.035 0.000 0.037 0.001 0.000 -38.792 0.000 -8.287 -21.098
PERIMETER_TOP_ZN_1 0.000 0.000 23.262 -69.897 0.000 0.000 11.229 10.545 36.366 100.373 0.000 0.055 0.001 0.000 -58.773 0.000 -12.751 -40.410
PERIMETER_TOP_ZN_4 0.000 0.000 15.517 -46.504 0.000 0.000 7.329 6.821 23.435 53.852 0.000 0.036 0.000 0.000 -41.646 0.000 -8.554 -10.284
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -136.601 0.000 0.000 0.950 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -21.856
DATACENTER_MID_ZN_6 0.000 0.000 5.238 -1161.991 0.000 0.000 9.521 36.263 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -427.837
DATACENTER_TOP_ZN_6 0.000 0.000 0.890 -105.567 0.000 0.000 0.957 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -53.787
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7156.018 0.000 0.000 20.485 47.611 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -406.935
GROUNDFLOOR_PLENUM 4.498 -49.145 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.037 55.085 0.000 0.000 0.000 -10.476 -0.000
MIDFLOOR_PLENUM 140.116 -280.637 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.715 315.589 0.000 0.000 0.000 -175.783 -0.003
TOPFLOOR_PLENUM 47.792 -45.258 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 16.009 0.000 0.000 0.000 -18.588 -0.000
Total Facility 192.406 -375.040 516.053 -16479.576 0.000 0.000 1570.632 2461.162 14676.396 2828.528 0.000 2.634 723.702 0.000 -2545.631 0.000 -617.164 -2954.099


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 09-AUG-06:11 0.00 0.00 0.00 -109360.79 0.00 0.00 1273.58 4914.68 13457.54 0.00 0.00 0.00 89715.00 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 28-JUN-04:13 0.00 0.00 0.00 -91540.87 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 85065.86 0.00 -0.00 0.00 0.00 0.00
CORE_MID 18-SEP-04:12 0.00 0.00 0.00 -783177.72 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 718427.89 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 22-JUL-05:04 0.00 0.00 0.00 -76611.32 0.00 0.00 835.86 537.36 7647.36 0.00 0.00 0.00 67590.74 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 16-JUL-16:22 0.00 0.00 0.00 -16109.11 0.00 0.00 41.60 43.94 720.18 4821.01 0.00 36.85 10445.52 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-JUL-07:51 0.00 0.00 0.00 -24804.59 0.00 0.00 19.53 28.32 464.11 21212.84 0.00 0.00 3192.41 0.00 -0.00 0.00 -112.61 0.00
PERIMETER_BOT_ZN_1 10-SEP-12:11 0.00 0.00 0.00 -27597.83 0.00 0.00 33.22 43.94 720.19 26693.59 0.00 0.00 270.75 0.00 -0.00 0.00 -163.87 0.00
PERIMETER_BOT_ZN_4 11-JUN-16:41 0.00 0.00 0.00 -31449.87 0.00 0.00 15.78 28.32 464.11 18932.49 0.00 0.00 12074.95 0.00 -0.00 0.00 -65.78 0.00
PERIMETER_MID_ZN_3 16-JUL-16:31 0.00 0.00 0.00 -139702.03 0.00 0.00 426.73 439.44 7201.84 44450.02 0.00 648.36 86535.64 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 11-JUN-10:01 0.00 0.00 0.00 -255992.46 0.00 0.00 204.60 283.19 4641.14 128255.28 0.00 0.00 124396.77 0.00 -0.00 0.00 -1788.52 0.00
PERIMETER_MID_ZN_1 03-SEP-12:32 0.00 0.00 0.00 -268755.95 0.00 0.00 340.47 439.45 7201.95 225966.74 0.00 0.00 37517.23 0.00 -0.00 0.00 -2709.89 0.00
PERIMETER_MID_ZN_4 02-JUL-17:01 0.00 0.00 0.00 -303798.52 0.00 0.00 0.00 283.19 3603.49 210462.39 0.00 0.00 91167.98 0.00 -0.00 0.00 -1718.52 0.00
PERIMETER_TOP_ZN_3 02-JUL-18:21 0.00 0.00 0.00 -16615.25 0.00 0.00 0.00 43.94 559.17 5527.83 0.00 0.00 10617.73 0.00 -0.00 0.00 -133.42 0.00
PERIMETER_TOP_ZN_2 04-JUL-09:22 0.00 0.00 0.00 -24820.55 0.00 0.00 17.33 28.32 464.11 17736.57 0.00 0.00 6755.24 0.00 -0.00 0.00 -181.03 0.00
PERIMETER_TOP_ZN_1 10-SEP-12:41 0.00 0.00 0.00 -30074.49 0.00 0.00 31.32 43.94 720.19 26204.41 0.00 0.00 3591.07 0.00 -0.00 0.00 -516.45 0.00
PERIMETER_TOP_ZN_4 02-JUL-17:01 0.00 0.00 0.00 -31911.83 0.00 0.00 0.00 28.32 360.35 20948.22 0.00 0.00 10798.82 0.00 -0.00 0.00 -223.89 0.00
DATACENTER_BOT_ZN_6 02-AUG-18:40 0.00 0.00 0.00 -8244.25 0.00 0.00 10.62 105.54 7794.42 0.00 0.00 0.00 333.67 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 02-AUG-18:40 0.00 0.00 0.00 -79117.28 0.00 0.00 106.16 1055.42 77944.22 0.00 0.00 0.00 11.48 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 02-AUG-18:40 0.00 0.00 0.00 -7964.95 0.00 0.00 10.62 105.54 7794.42 0.00 0.00 0.00 54.36 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 15-AUG-16:41 0.00 0.00 0.00 -378560.04 0.00 0.00 665.66 2309.53 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4047.67
GROUNDFLOOR_PLENUM 24-JUL-05:10 0.00 -12843.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12849.08 0.00 -0.00 0.00 -5.20 0.00
MIDFLOOR_PLENUM 21-FEB-04:11 0.00 -102614.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 140099.71 0.00 -0.00 0.00 -37485.64 0.00
TOPFLOOR_PLENUM 12-JUN-13:40 0.00 -18464.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.13 18330.43 0.00 -0.00 0.00 0.00 0.00
Total Facility 11-AUG-05:03 0.00 -28555.99 0.00 -1805983.62 0.00 0.00 15998.46 10593.62 616289.16 0.00 0.00 0.00 1267843.12 0.00 -73808.06 0.00 -2376.68 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 02-JAN-04:01 0.00 0.00 490351.59 0.00 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -555101.42
CORE_TOP 02-JAN-04:01 0.00 0.00 73857.78 0.00 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -80332.76
PERIMETER_BOT_ZN_3 06-FEB-05:01 0.00 0.00 11882.31 0.00 0.00 0.00 0.00 67.47 745.56 0.00 0.00 0.00 0.00 0.00 -7173.05 0.00 -929.87 -4592.43
PERIMETER_BOT_ZN_2 06-FEB-05:01 0.00 0.00 11938.27 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -4626.13 0.00 -619.64 -7216.45
PERIMETER_BOT_ZN_1 07-FEB-05:01 0.00 0.00 17663.47 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -7105.26 0.00 -938.30 -10432.95
PERIMETER_BOT_ZN_4 06-FEB-05:01 0.00 0.00 8780.86 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -4989.35 0.00 -645.88 -3669.58
PERIMETER_MID_ZN_3 06-FEB-04:11 0.00 0.00 128606.92 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -64648.81 0.00 -18900.76 -53187.68
PERIMETER_MID_ZN_2 13-FEB-04:01 0.00 0.00 182202.44 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -33608.41 0.00 -18272.98 -135560.54
PERIMETER_MID_ZN_1 06-FEB-04:11 0.00 0.00 210153.41 0.00 0.00 0.00 0.00 674.72 7455.72 0.00 0.00 0.00 0.00 0.00 -65404.90 0.00 -19150.69 -133728.26
PERIMETER_MID_ZN_4 06-FEB-04:11 0.00 0.00 181410.99 0.00 0.00 0.00 0.00 434.81 4804.65 0.00 0.00 0.00 0.00 0.00 -43825.77 0.00 -12900.09 -129924.59
PERIMETER_TOP_ZN_3 06-FEB-03:42 0.00 0.00 15699.49 0.00 0.00 0.00 0.00 67.47 745.56 0.00 0.00 0.00 0.00 0.00 -6116.35 0.00 -2250.62 -8145.55
PERIMETER_TOP_ZN_2 06-FEB-03:42 0.00 0.00 21150.95 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -3952.87 0.00 -1544.93 -16177.10
PERIMETER_TOP_ZN_1 06-FEB-03:42 0.00 0.00 24162.18 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -6161.79 0.00 -2296.51 -16516.93
PERIMETER_TOP_ZN_4 06-FEB-03:42 0.00 0.00 22354.19 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -4170.69 0.00 -1574.57 -17132.87
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 03-JAN-01:20 0.00 0.00 5497.74 0.00 0.00 0.00 0.00 175.92 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25159.71
DATACENTER_TOP_ZN_6 15-JAN-18:50 0.00 0.00 588.75 0.00 0.00 0.00 0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2554.95
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 14-DEC-06:02 11749.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -94.45 -11655.16
MIDFLOOR_PLENUM 02-JAN-06:13 174586.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -2398.20 -172188.31
TOPFLOOR_PLENUM 11-DEC-05:42 29319.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1086.15 -28233.76
Total Facility 02-JAN-05:21 19342.73 105293.32 1250513.95 -105293.32 0.00 0.00 0.00 10593.62 232425.23 0.00 0.00 0.00 0.00 0.00 -146557.96 0.00 -35431.27 -1330886.30



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.7479 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.2247 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 102.9317 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 85.9380 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.5715 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.4416 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.1012 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.1012 0.2353 1.0000 Not calculated 1.2002 0.2353    
AIRLOOP DATACENTER BASEMENT 25.0548 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 25.0550 0.0135 1.0000 Not calculated 0.3384 0.0135    
AIRLOOP DATACENTER BOT 0.4938 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4938 0.0317 1.0000 Not calculated 0.0156 0.0317    
AIRLOOP DATACENTER MID 4.7360 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7360 0.0330 1.0000 Not calculated 0.1563 0.0330    
AIRLOOP DATACENTER TOP 0.4817 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4817 0.0325 1.0000 Not calculated 0.0156 0.0325    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.3740 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2844 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 51.4658 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8285 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.2857 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2860 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 0.0000 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 0.0000 1.0000 1.0000 Not calculated 1.2002      
AIRLOOP DATACENTER BASEMENT 25.0548 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 25.0548 1.0000 1.0000 Not calculated 0.3384 0.0135    
AIRLOOP DATACENTER BOT 0.4938 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4938 1.0000 1.0000 Not calculated 0.0156 0.0317    
AIRLOOP DATACENTER MID 4.7360 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7360 1.0000 1.0000 Not calculated 0.1563 0.0330    
AIRLOOP DATACENTER TOP 0.4817 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4817 1.0000 1.0000 Not calculated 0.0156 0.0325    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 5.1012 5.1012 0.0000 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.5188 5.5188 1.6170 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 51.8033 51.8033 16.1626 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1383 5.1383 1.6185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9329 0.9329 0.2034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2769 1.2769 0.1302 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4574 1.4574 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5620 1.5620 0.1312 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.7063 8.7063 2.0286 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.6392 13.6392 1.3094 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.4641 14.4641 2.0250 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.3188 14.3188 1.3030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9896 0.9896 0.2029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3752 1.3752 0.1306 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5579 1.5579 0.2025 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5105 1.5105 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4938 0.4938 0.4938 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7360 4.7360 4.7360 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4817 0.4817 0.4817 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 25.0548 25.0548 25.0548 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.7479 9.2247 10.7479 2.2844 0.0000 1.0000
VAV_MID WITH REHEAT 102.9317 85.9380 102.9317 22.8285 0.0000 1.0000
VAV_TOP WITH REHEAT 10.5715 9.4416 10.5715 2.2860 0.0000 1.0000
CAV_BAS 5.1012 5.1012 5.1012 0.0000 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 25.0548 25.0550 25.0548 25.0548 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4938 0.4938 0.4938 0.4938 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7360 4.7360 4.7360 4.7360 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4817 0.4817 0.4817 0.4817 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT 0.0000 0.0000 0.0000 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7594 2.7594 1.6170 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 25.9016 25.9016 16.1626 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5691 2.5691 1.6185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4664 0.4664 0.2034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6384 0.6384 0.1302 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7287 0.7287 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7810 0.7810 0.1312 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.3531 4.3531 2.0286 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.8196 6.8196 1.3094 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.2320 7.2320 2.0250 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.1594 7.1594 1.3030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4948 0.4948 0.2029 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6876 0.6876 0.1306 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7789 0.7789 0.2025 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7553 0.7553 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4938 0.4938 0.4938 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7360 4.7360 4.7360 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4817 0.4817 0.4817 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 25.0548 25.0548 25.0548 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.3740 2.2844 2.2844 2.2844 0.0000 1.0000
VAV_MID WITH REHEAT 51.4658 22.8285 22.8285 22.8285 0.0000 1.0000
VAV_TOP WITH REHEAT 5.2857 2.2860 2.2860 2.2860 0.0000 1.0000
CAV_BAS 0.0000 0.0000 0.0000 0.0000 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 25.0548 25.0548 25.0548 25.0548 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4938 0.4938 0.4938 0.4938 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7360 4.7360 4.7360 4.7360 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4817 0.4817 0.4817 0.4817 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 82.50
Number of hours cooling loads not met 986.50
Number of hours not met 1027.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1151.06 1582955.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1396.53 528085.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2461.16 247210.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 353.28 40855.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.68 3412.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 2505.76 229608.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2360.91 274878.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 346.74 48849.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 477.95 79472.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1463.05 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 36.73 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 459.85 56293.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 26598.87
Natural Gas 0.00 1151.06
Additional 0.00 0.00
Total 14676.40 27749.93


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 53.13
Space Heating 0.00
Space Cooling 30.15
Fans (All) 50.97
Service Water Heating 9.93
Receptacle Equipment 316.85
Miscellaneous (All) 574.24
Subtotal 574.24


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 24.85
Service Water Heating 0.00
Miscellaneous (All) 24.85
Subtotal 24.85


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.87
Space Heating 4.15
Space Cooling 5.03
Fans (All) 8.51
Service Water Heating 1.66
Receptacle Equipment 52.89
Miscellaneous 18.90


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 675. 3744.
ELEVATOR_STANDBY_SCH 7740. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 751. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7636.33 785.17 234.33 104.17 0.00
CORE_BOTTOM 8729.50 30.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8729.17 30.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8679.17 80.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8673.83 86.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8295.83 464.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8749.00 11.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8661.00 99.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8679.17 80.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8522.00 238.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8731.17 28.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8653.83 106.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8668.67 91.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8525.33 234.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7833.67 926.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7818.00 942.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7802.83 957.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6643.83 2113.00 3.17 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8664.00 96.00 0.00 0.00 0.00
Min 6643.83 0.00 0.00 0.00 0.00
Max 8760.00 2113.00 234.33 104.17 0.00
Average 8423.32 321.83 10.33 4.53 0.00
Sum 193736.33 7402.00 237.50 104.17 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 338308.67 13953.33 8841.17 7512.83 0.00
CORE_BOTTOM 330804.00 9.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1759.17 508.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1746.00 522.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1736.00 532.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 78851.33 24539.33 4.33 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 338308.67 24539.33 8841.17 7512.83 0.00
Average 77881.75 1741.93 384.59 326.64 0.00
Sum 1791280.17 40064.50 8845.50 7512.83 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7433.83 990.83 172.00 163.33 0.00
CORE_BOTTOM 8177.00 583.00 0.00 0.00 0.00
CORE_MID 8269.83 490.17 0.00 0.00 0.00
CORE_TOP 8253.33 506.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8247.50 512.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8280.67 479.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8212.00 548.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7901.50 858.50 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8255.83 504.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8183.17 576.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8191.83 568.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8085.00 675.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8261.17 498.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8193.83 566.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8203.33 556.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8103.17 656.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8347.33 412.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8328.33 431.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8326.67 433.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6868.17 1891.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8107.00 653.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8156.17 603.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 7882.67 877.33 0.00 0.00 0.00
Min 6868.17 412.67 0.00 0.00 0.00
Max 8347.33 1891.83 172.00 163.33 0.00
Average 8098.67 646.75 7.48 7.10 0.00
Sum 186269.33 14875.33 172.00 163.33 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 336786.17 15996.00 6433.17 9400.67 0.00
CORE_BOTTOM 329715.33 1097.67 0.00 0.00 0.00
CORE_MID 330086.00 727.00 0.00 0.00 0.00
CORE_TOP 329985.00 828.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38924.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18353.83 0.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38924.33 0.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38923.33 1.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38923.83 1.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24908.17 0.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1996.17 271.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1982.83 285.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1981.17 286.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 81230.67 22164.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 336786.17 22164.33 6433.17 9400.67 0.00
Average 77835.04 1811.45 279.70 408.72 0.00
Sum 1790205.83 41663.33 6433.17 9400.67 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:26:29

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.366165E+11 95466.94 02-JAN-07:03 -1.1 -1.7 0.567059E+10 7499.30 11-JAN-10:09 7.98 6.90
February 0.343449E+11 95269.64 21-FEB-07:03 -13.9 -14.7 0.514447E+10 7499.25 01-FEB-10:20 -13.9 -14.7
March 0.468002E+11 94908.78 16-MAR-06:12 11.67 10.33 0.614718E+10 7499.41 16-MAR-13:00 18.90 15.16
April 0.465160E+11 97142.47 24-APR-06:03 1.38 0.25 0.546618E+10 7499.30 12-APR-13:09 1.38 0.25
May 0.482391E+11 100437.07 30-MAY-06:11 12.20 11.93 0.594553E+10 9744.98 17-MAY-09:00 12.20 11.93
June 0.451004E+11 103603.03 13-JUN-06:05 8.80 7.96 0.646468E+10 11462.71 27-JUN-13:00 27.20 22.77
July 0.399046E+11 106495.86 12-JUL-06:11 14.83 11.88 0.648485E+10 11930.13 21-JUL-13:00 31.70 21.73
August 0.521446E+11 109450.30 09-AUG-06:11 17.77 14.04 0.682268E+10 11899.30 15-AUG-13:00 26.10 22.23
September 0.509019E+11 108406.19 18-SEP-06:11 10.57 9.34 0.561268E+10 10417.70 14-SEP-08:39 10.57 9.34
October 0.533378E+11 105165.75 10-OCT-06:11 10.20 8.82 0.569466E+10 7499.33 27-OCT-13:09 9.78 7.31
November 0.503463E+11 98739.53 13-NOV-07:05 6.20 5.12 0.563457E+10 7499.39 16-NOV-14:09 17.20 13.27
December 0.443201E+11 98729.88 26-DEC-07:03 -12.3 -13.4 0.548377E+10 7499.18 26-DEC-14:30 -9.4 -11.0
                     
Annual Sum or Average 0.548573E+12         0.705718E+11        
Minimum of Months 0.343449E+11 94908.78   -13.9 -14.7 0.514447E+10 7499.18   -13.9 -14.7
Maximum of Months 0.533378E+11 109450.30   17.77 14.04 0.682268E+10 11930.13   31.70 22.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294439E+11 74601.69 17-JAN-06:01 7.20 2.95 0.503396E+10 6748.38 17-JAN-10:50 6.97 4.36
February 0.287002E+11 76431.62 24-FEB-06:02 -7.2 -8.2 0.458099E+10 6734.82 06-FEB-10:20 -7.2 -8.2
March 0.447490E+11 80819.06 15-MAR-04:12 15.00 11.89 0.549659E+10 6734.93 16-MAR-13:00 18.90 15.16
April 0.492160E+11 86045.33 10-APR-04:12 3.50 2.94 0.488356E+10 6734.82 19-APR-09:20 9.07 6.91
May 0.485220E+11 88340.68 30-MAY-04:12 12.20 11.68 0.528672E+10 6734.89 10-MAY-09:09 12.20 11.68
June 0.601643E+11 91565.91 28-JUN-04:13 17.60 15.52 0.527074E+10 6735.16 22-JUN-13:09 17.60 15.52
July 0.706143E+11 88999.17 12-JUL-04:13 12.93 10.99 0.489838E+10 6759.91 24-JUL-09:00 23.90 17.87
August 0.741769E+11 84482.61 31-AUG-04:13 11.50 11.15 0.549863E+10 6812.49 03-AUG-13:30 11.50 11.15
September 0.502626E+11 89448.97 05-SEP-04:12 6.70 6.07 0.488384E+10 6735.20 12-SEP-13:09 21.10 16.55
October 0.464437E+11 85853.16 23-OCT-04:12 12.77 10.74 0.507938E+10 6734.78 10-OCT-09:20 12.77 10.74
November 0.432269E+11 86960.57 13-NOV-05:11 5.57 4.40 0.503077E+10 6734.89 16-NOV-14:09 17.20 13.27
December 0.371606E+11 80588.25 18-DEC-05:01 1.70 0.81 0.489642E+10 6734.79 12-DEC-10:20 1.70 0.81
                     
Annual Sum or Average 0.582681E+12         0.608400E+11        
Minimum of Months 0.287002E+11 74601.69   -7.2 -8.2 0.458099E+10 6734.78   -7.2 -8.2
Maximum of Months 0.741769E+11 91565.91   17.60 15.52 0.549863E+10 6812.49   23.90 17.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.186216E+11 19194.39 25-JAN-11:10 -7.1 -7.8 0.441889E+10 6695.41 20-JAN-14:00 -7.1 -7.8
February 0.180765E+11 19084.65 03-FEB-09:00 -7.8 -8.7 0.408278E+10 6734.52 17-FEB-14:00 3.30 1.08
March 0.277406E+11 73671.05 17-MAR-05:02 10.50 9.94 0.535055E+10 6734.87 16-MAR-13:00 10.50 9.94
April 0.302231E+11 70875.89 27-APR-05:03 5.00 3.27 0.483862E+10 6876.51 10-APR-13:50 5.00 3.27
May 0.386212E+11 76302.41 30-MAY-04:12 12.20 11.68 0.527553E+10 6734.89 10-MAY-09:09 12.20 11.68
June 0.442619E+11 76161.75 29-JUN-04:11 19.80 17.63 0.526402E+10 6735.15 22-JUN-13:09 19.80 17.63
July 0.453721E+11 77139.98 25-JUL-04:11 15.00 13.80 0.489263E+10 6734.81 03-JUL-13:30 15.00 13.80
August 0.473400E+11 76597.13 01-AUG-04:11 12.23 11.69 0.549467E+10 6735.15 02-AUG-13:09 23.90 16.41
September 0.389583E+11 78339.64 18-SEP-04:12 10.20 9.28 0.487398E+10 6735.20 12-SEP-13:09 10.20 9.28
October 0.311082E+11 74368.67 13-OCT-05:02 10.50 10.16 0.503739E+10 6750.32 27-OCT-09:30 7.20 5.20
November 0.248931E+11 68453.56 01-NOV-05:02 5.68 3.03 0.493195E+10 6737.99 06-NOV-10:20 8.17 4.21
December 0.201379E+11 23641.53 01-DEC-17:00 7.20 4.89 0.443313E+10 6734.73 01-DEC-10:09 7.20 4.89
                     
Annual Sum or Average 0.385354E+12         0.588941E+11        
Minimum of Months 0.180765E+11 19084.65   -7.8 -8.7 0.408278E+10 6695.41   -7.1 -7.8
Maximum of Months 0.473400E+11 78339.64   19.80 17.63 0.549467E+10 6876.51   23.90 17.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117822E+11 14300.52 12-JAN-17:00 -6.7 -8.2 0.394848E+10 6009.70 12-JAN-14:00 -6.7 -8.2
February 0.121038E+11 14845.84 28-FEB-14:10 0.00 -3.0 0.366578E+10 6164.98 17-FEB-14:00 0.00 -3.0
March 0.210889E+11 71641.12 16-MAR-05:02 14.03 11.42 0.486809E+10 6734.85 16-MAR-13:00 18.90 15.16
April 0.238950E+11 35983.03 21-APR-16:00 13.30 8.77 0.461313E+10 6749.36 11-APR-13:09 13.30 8.77
May 0.346709E+11 70725.03 17-MAY-05:02 16.05 11.54 0.522264E+10 6734.90 10-MAY-09:09 16.05 11.54
June 0.447026E+11 75064.15 19-JUN-04:12 16.70 15.97 0.525608E+10 6735.15 22-JUN-13:09 20.60 15.40
July 0.479249E+11 76635.19 22-JUL-05:04 21.10 20.28 0.489427E+10 6734.76 12-JUL-09:00 21.10 20.28
August 0.477503E+11 74842.92 01-AUG-04:11 12.23 11.69 0.549207E+10 6735.14 02-AUG-13:09 23.90 16.41
September 0.350242E+11 74871.31 18-SEP-04:12 10.20 9.28 0.483991E+10 6735.16 12-SEP-13:09 10.20 9.28
October 0.234089E+11 67473.44 13-OCT-05:02 10.50 10.16 0.475954E+10 6734.73 12-OCT-09:20 10.50 10.16
November 0.170902E+11 23577.45 01-NOV-16:00 9.40 6.91 0.439960E+10 6734.79 16-NOV-14:30 17.20 13.27
December 0.127604E+11 15211.66 01-DEC-17:00 7.20 4.89 0.385766E+10 6302.65 01-DEC-14:00 7.20 4.89
                     
Annual Sum or Average 0.332202E+12         0.558173E+11        
Minimum of Months 0.117822E+11 14300.52   -6.7 -8.2 0.366578E+10 6009.70   -6.7 -8.2
Maximum of Months 0.479249E+11 76635.19   21.10 20.28 0.549207E+10 6749.36   23.90 20.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139520E+10 2193.99 17-JAN-06:02 7.20 2.95 0.504090E+09 787.81 17-JAN-14:00 6.70 5.64
February 0.151202E+10 2093.73 23-FEB-06:03 2.30 1.81 0.475940E+09 806.05 22-FEB-14:00 2.30 1.81
March 0.335518E+10 7631.35 15-MAR-14:00 26.10 16.06 0.640047E+09 845.65 16-MAR-13:00 18.90 15.16
April 0.441734E+10 6878.56 07-APR-13:30 20.00 10.05 0.601698E+09 845.63 21-APR-13:00 14.40 8.43
May 0.588281E+10 8733.79 17-MAY-05:02 16.05 11.54 0.660368E+09 845.64 10-MAY-09:09 16.05 11.54
June 0.944453E+10 15780.79 11-JUN-18:41 24.08 17.29 0.662020E+09 845.82 27-JUN-13:00 27.20 22.77
July 0.116469E+11 16112.57 16-JUL-16:22 28.90 21.75 0.616033E+09 849.27 24-JUL-09:00 23.90 17.87
August 0.112438E+11 15622.46 06-AUG-16:21 27.80 18.95 0.690759E+09 866.40 03-AUG-13:30 27.80 18.95
September 0.610119E+10 11642.57 15-SEP-05:02 18.30 16.87 0.610461E+09 845.69 12-SEP-13:09 18.30 16.87
October 0.395634E+10 6362.21 23-OCT-05:03 11.70 9.96 0.622496E+09 845.63 10-OCT-09:20 11.70 9.96
November 0.285037E+10 4692.97 27-NOV-12:00 15.00 10.52 0.601293E+09 845.64 16-NOV-14:09 15.00 10.52
December 0.196411E+10 2753.88 01-DEC-13:10 12.97 11.34 0.520679E+09 845.58 01-DEC-14:39 7.57 6.05
                     
Annual Sum or Average 0.637698E+11         0.720588E+10        
Minimum of Months 0.139520E+10 2093.73   2.30 1.81 0.475940E+09 787.81   2.30 1.81
Maximum of Months 0.116469E+11 16112.57   28.90 21.75 0.690759E+09 866.40   27.80 22.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.974984E+09 1764.99 12-JAN-10:05 -9.8 -12.2 0.336940E+09 544.95 06-JAN-10:50 -9.8 -12.2
February 0.110875E+10 6143.57 28-FEB-09:35 -5.2 -6.5 0.319869E+09 544.95 17-FEB-10:20 -5.2 -6.5
March 0.290647E+10 9201.90 21-MAR-08:55 1.70 -0.5 0.426635E+09 544.97 14-MAR-09:50 1.70 -0.5
April 0.441242E+10 16101.26 23-APR-10:32 14.80 7.30 0.389480E+09 545.76 24-APR-09:09 6.28 2.92
May 0.619058E+10 18246.37 07-MAY-07:33 8.90 6.12 0.426479E+09 545.67 31-MAY-09:39 18.13 13.58
June 0.857635E+10 23682.58 11-JUN-08:41 23.03 15.86 0.427011E+09 546.16 12-JUN-09:00 27.80 19.41
July 0.100193E+11 24818.55 04-JUL-07:51 21.10 17.80 0.397329E+09 549.21 24-JUL-09:00 23.90 17.87
August 0.928149E+10 21814.50 06-AUG-09:01 24.18 17.35 0.445180E+09 553.12 09-AUG-09:00 25.60 18.67
September 0.593876E+10 22114.95 10-SEP-08:12 13.67 10.66 0.394224E+09 544.99 12-SEP-13:09 21.10 16.55
October 0.342493E+10 11049.97 11-OCT-08:50 14.53 11.11 0.403724E+09 544.96 03-OCT-09:00 14.53 11.11
November 0.194209E+10 6576.78 03-NOV-08:55 3.90 1.83 0.382956E+09 544.96 16-NOV-14:09 17.20 13.27
December 0.110458E+10 3619.18 04-DEC-09:50 -1.8 -3.7 0.328470E+09 544.95 04-DEC-10:39 -1.3 -3.6
                     
Annual Sum or Average 0.558807E+11         0.467830E+10        
Minimum of Months 0.974984E+09 1764.99   -9.8 -12.2 0.319869E+09 544.95   -9.8 -12.2
Maximum of Months 0.100193E+11 24818.55   24.18 17.80 0.445180E+09 553.12   27.80 19.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.246528E+10 24096.96 15-JAN-13:53 5.00 2.25 0.543238E+09 845.69 12-JAN-14:09 5.00 2.25
February 0.281140E+10 17297.88 28-FEB-13:20 0.00 -2.8 0.511142E+09 846.16 28-FEB-14:00 0.00 -2.8
March 0.660476E+10 19020.78 15-MAR-13:30 25.55 15.84 0.661486E+09 847.29 14-MAR-13:00 25.55 15.84
April 0.704292E+10 20694.66 23-APR-14:32 15.20 9.59 0.599627E+09 846.60 24-APR-13:00 12.80 6.89
May 0.808216E+10 24643.34 14-MAY-13:13 24.27 17.84 0.659117E+09 845.67 10-MAY-13:09 24.27 17.84
June 0.109735E+11 24329.45 25-JUN-13:02 26.10 17.26 0.661799E+09 845.71 22-JUN-13:09 26.10 17.26
July 0.137828E+11 25284.44 16-JUL-15:41 30.40 23.08 0.616364E+09 849.97 24-JUL-09:00 23.90 17.87
August 0.148269E+11 26085.88 27-AUG-13:22 23.60 18.96 0.691358E+09 939.75 03-AUG-13:30 23.60 18.96
September 0.108380E+11 27594.25 10-SEP-12:11 16.87 10.71 0.611805E+09 858.66 21-SEP-13:30 25.30 16.56
October 0.782230E+10 24692.50 22-OCT-12:53 21.70 14.82 0.626207E+09 912.80 31-OCT-13:09 15.00 10.18
November 0.460755E+10 18246.11 03-NOV-12:30 8.35 4.56 0.596655E+09 846.97 15-NOV-14:50 11.60 6.55
December 0.259907E+10 16985.61 17-DEC-11:33 1.50 -0.3 0.532108E+09 845.64 11-DEC-14:20 1.50 -0.3
                     
Annual Sum or Average 0.924566E+11         0.731091E+10        
Minimum of Months 0.246528E+10 16985.61   0.00 -2.8 0.511142E+09 845.64   0.00 -2.8
Maximum of Months 0.148269E+11 27594.25   30.40 23.08 0.691358E+09 939.75   26.10 18.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141050E+10 4698.28 12-JAN-15:40 -5.9 -8.2 0.357607E+09 544.95 17-JAN-14:50 6.52 5.42
February 0.191494E+10 9567.37 28-FEB-16:30 0.00 -2.6 0.346123E+09 544.95 22-FEB-14:50 0.00 -2.6
March 0.561475E+10 19058.94 26-MAR-16:22 -1.7 -4.7 0.441334E+09 544.98 16-MAR-13:00 -1.7 -4.7
April 0.824609E+10 27168.38 02-APR-16:22 7.50 5.68 0.395986E+09 544.97 21-APR-13:00 14.40 8.43
May 0.786707E+10 30065.42 07-MAY-16:11 15.00 5.96 0.428464E+09 544.97 10-MAY-09:09 18.68 14.82
June 0.120048E+11 31453.37 11-JUN-16:41 25.60 17.82 0.427857E+09 545.00 22-JUN-13:09 20.60 15.40
July 0.140105E+11 31342.55 16-JUL-16:21 28.90 21.75 0.398364E+09 547.86 24-JUL-09:00 23.90 17.87
August 0.150724E+11 31309.21 06-AUG-16:21 27.80 18.95 0.446643E+09 552.49 16-AUG-13:20 25.20 15.34
September 0.744766E+10 28565.40 10-SEP-17:31 16.10 10.54 0.395789E+09 545.00 12-SEP-13:09 21.10 16.55
October 0.539358E+10 17785.31 09-OCT-16:33 12.97 9.03 0.410214E+09 544.96 12-OCT-13:00 18.30 14.87
November 0.404880E+10 15422.75 27-NOV-05:12 17.97 12.28 0.405934E+09 544.97 16-NOV-14:09 17.97 12.28
December 0.271009E+10 9006.41 14-DEC-06:02 5.68 5.18 0.387785E+09 544.95 12-DEC-14:30 5.68 5.18
                     
Annual Sum or Average 0.857411E+11         0.484210E+10        
Minimum of Months 0.141050E+10 4698.28   -5.9 -8.2 0.346123E+09 544.95   -1.7 -4.7
Maximum of Months 0.150724E+11 31453.37   28.90 21.75 0.446643E+09 552.49   25.20 17.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.137616E+09 1372.35 11-JAN-17:00 11.10 9.84 0.464876E+09 632.09 11-JAN-14:00 11.10 9.84
February 0.221798E+09 1413.87 17-FEB-15:00 3.30 1.08 0.422957E+09 658.64 17-FEB-14:00 3.30 1.08
March 0.167977E+10 5998.96 15-MAR-14:00 26.10 16.06 0.563896E+09 845.64 16-MAR-13:00 18.90 15.16
April 0.245714E+10 4588.61 07-APR-13:50 20.00 10.11 0.547852E+09 845.63 20-APR-13:20 12.97 9.40
May 0.447244E+10 7075.61 23-MAY-14:40 23.90 13.32 0.648702E+09 845.64 10-MAY-09:09 23.90 13.32
June 0.729915E+10 13443.28 11-JUN-18:41 24.08 17.29 0.660098E+09 846.65 27-JUN-13:20 29.47 23.48
July 0.834608E+10 13972.79 16-JUL-16:31 28.33 21.22 0.615365E+09 846.57 27-JUL-13:20 29.40 21.64
August 0.765742E+10 10340.83 11-AUG-05:03 17.80 15.36 0.688744E+09 846.48 15-AUG-13:20 27.23 22.54
September 0.462000E+10 7604.32 14-SEP-05:03 20.60 19.14 0.600734E+09 845.68 12-SEP-13:09 20.60 19.14
October 0.250974E+10 4215.76 12-OCT-14:40 18.30 15.11 0.569512E+09 845.62 06-OCT-13:39 18.30 15.11
November 0.141758E+10 2241.39 07-NOV-10:00 2.80 1.42 0.503282E+09 814.69 16-NOV-14:00 17.20 13.27
December 0.238562E+09 1635.70 01-DEC-13:30 11.10 9.57 0.450975E+09 711.07 01-DEC-14:09 8.12 6.69
                     
Annual Sum or Average 0.410573E+11         0.673699E+10        
Minimum of Months 0.137616E+09 1372.35   2.80 1.08 0.422957E+09 632.09   3.30 1.08
Maximum of Months 0.834608E+10 13972.79   28.33 21.22 0.688744E+09 846.65   29.47 23.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158408E+09 1379.93 06-JAN-09:55 -7.2 -8.7 0.219731E+09 452.46 06-JAN-11:09 -5.3 -7.0
February 0.269962E+09 4094.80 28-FEB-11:05 -2.0 -4.1 0.207542E+09 548.48 28-FEB-11:09 -2.0 -4.1
March 0.167428E+10 8820.38 21-MAR-10:05 2.88 0.57 0.291572E+09 548.51 14-MAR-10:09 2.88 0.57
April 0.327243E+10 17112.54 23-APR-10:32 14.80 7.30 0.277310E+09 548.51 07-APR-12:09 14.80 7.30
May 0.556596E+10 18423.83 21-MAY-09:12 16.50 11.82 0.312007E+09 548.51 26-MAY-10:09 18.98 12.55
June 0.783886E+10 25602.51 11-JUN-10:01 24.50 16.94 0.314586E+09 548.52 22-JUN-12:09 19.18 13.72
July 0.869200E+10 24752.49 09-JUL-08:12 20.77 17.49 0.294174E+09 548.52 12-JUL-10:09 20.87 14.79
August 0.795686E+10 23258.94 20-AUG-09:42 20.40 14.16 0.328057E+09 548.61 17-AUG-10:09 20.40 14.16
September 0.518081E+10 21265.43 04-SEP-09:02 16.88 13.13 0.288642E+09 548.53 12-SEP-12:09 20.68 15.09
October 0.227149E+10 10814.20 11-OCT-10:05 17.15 12.50 0.286280E+09 549.13 16-OCT-10:09 7.20 4.92
November 0.874424E+09 5985.88 03-NOV-10:05 5.78 3.09 0.248984E+09 548.49 16-NOV-13:09 18.62 13.01
December 0.157192E+09 1123.55 01-DEC-13:10 12.97 11.34 0.213116E+09 474.74 04-DEC-11:09 -0.9 -3.4
                     
Annual Sum or Average 0.439127E+11         0.328200E+10        
Minimum of Months 0.157192E+09 1123.55   -7.2 -8.7 0.207542E+09 452.46   -5.3 -7.0
Maximum of Months 0.869200E+10 25602.51   24.50 17.49 0.328057E+09 549.13   20.87 15.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157780E+10 17399.86 15-JAN-13:23 4.70 2.09 0.510698E+09 845.71 12-JAN-14:09 4.70 2.09
February 0.202033E+10 18210.59 28-FEB-13:40 0.00 -2.9 0.475967E+09 845.72 28-FEB-14:00 0.00 -2.8
March 0.559692E+10 19323.81 01-MAR-13:50 -0.1 -2.5 0.633554E+09 866.56 01-MAR-10:39 -0.1 -2.5
April 0.564227E+10 21962.05 23-APR-14:32 15.20 9.59 0.577166E+09 846.65 21-APR-13:20 15.20 9.59
May 0.733961E+10 24723.18 14-MAY-13:23 24.45 17.92 0.651884E+09 845.67 19-MAY-13:30 15.85 9.67
June 0.935115E+10 24232.81 11-JUN-15:21 25.85 18.02 0.659530E+09 847.14 12-JUN-13:20 29.80 19.89
July 0.109740E+11 24941.68 30-JUL-12:32 25.60 19.52 0.615830E+09 847.23 19-JUL-13:20 25.60 19.52
August 0.119379E+11 25474.50 27-AUG-12:32 22.93 18.66 0.690108E+09 886.85 03-AUG-13:30 22.93 18.66
September 0.103269E+11 26875.01 03-SEP-12:32 19.03 12.28 0.608442E+09 891.30 21-SEP-13:39 25.40 16.58
October 0.704633E+10 24653.79 22-OCT-13:02 21.70 14.72 0.613956E+09 962.67 31-OCT-13:39 15.00 10.41
November 0.357456E+10 19280.53 03-NOV-12:30 8.35 4.56 0.554900E+09 847.19 06-NOV-10:20 8.17 4.21
December 0.130255E+10 12762.79 04-DEC-11:50 -0.2 -2.9 0.480168E+09 845.65 11-DEC-14:30 -8.1 -9.1
                     
Annual Sum or Average 0.766903E+11         0.707220E+10        
Minimum of Months 0.130255E+10 12762.79   -0.2 -2.9 0.475967E+09 845.65   -8.1 -9.1
Maximum of Months 0.119379E+11 26875.01   25.85 19.52 0.690108E+09 962.67   29.80 19.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266169E+09 1614.76 12-JAN-15:50 -6.0 -8.3 0.305242E+09 521.18 12-JAN-16:30 -6.4 -8.3
February 0.481012E+09 6135.30 28-FEB-16:30 0.00 -2.6 0.283313E+09 544.91 28-FEB-14:00 0.00 -2.6
March 0.220515E+10 9137.18 21-MAR-16:00 4.40 1.34 0.388767E+09 544.97 16-MAR-13:00 4.40 1.34
April 0.351863E+10 24082.70 02-APR-16:11 7.77 5.85 0.370272E+09 544.96 20-APR-13:30 13.05 9.56
May 0.591821E+10 25120.69 07-MAY-16:32 15.00 5.92 0.422747E+09 544.96 10-MAY-09:09 18.68 14.82
June 0.888246E+10 28912.02 11-JUN-16:41 25.60 17.82 0.426496E+09 544.99 22-JUN-13:09 20.60 15.40
July 0.928912E+10 30376.78 02-JUL-17:01 24.82 16.94 0.397561E+09 544.98 03-JUL-13:30 25.00 16.74
August 0.884337E+10 26139.43 27-AUG-16:31 22.57 18.97 0.445435E+09 545.00 02-AUG-13:09 22.57 18.97
September 0.538282E+10 24839.14 04-SEP-17:02 18.03 12.75 0.391385E+09 545.00 12-SEP-13:09 21.10 16.55
October 0.264866E+10 11945.32 11-OCT-16:00 21.70 14.52 0.382596E+09 544.95 12-OCT-09:20 16.13 13.62
November 0.129432E+10 5256.25 15-NOV-15:20 11.70 6.66 0.343461E+09 544.96 16-NOV-14:09 17.20 13.27
December 0.366947E+09 2063.44 04-DEC-15:50 -0.5 -3.2 0.295983E+09 524.02 04-DEC-14:00 -0.5 -3.2
                     
Annual Sum or Average 0.490969E+11         0.445326E+10        
Minimum of Months 0.266169E+09 1614.76   -6.0 -8.3 0.283313E+09 521.18   -6.4 -8.3
Maximum of Months 0.928912E+10 30376.78   25.60 18.97 0.445435E+09 545.00   25.00 18.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 22431150.95 1204.97 07-JAN-17:02 -2.7 -3.8 0.462739E+09 625.93 23-JAN-10:30 -6.7 -8.5
February 58537842.05 1313.41 22-FEB-16:50 11.52 5.47 0.419399E+09 625.97 21-FEB-10:09 11.52 5.47
March 0.114643E+10 6437.12 15-MAR-14:30 25.85 16.15 0.541877E+09 845.64 16-MAR-13:00 18.90 15.16
April 0.190243E+10 4297.17 20-APR-15:40 14.80 10.94 0.515394E+09 845.62 20-APR-13:20 14.80 10.94
May 0.404996E+10 7314.80 23-MAY-14:40 23.90 13.32 0.631347E+09 845.64 10-MAY-13:39 23.90 13.32
June 0.733538E+10 11795.70 18-JUN-11:43 26.02 20.76 0.657227E+09 846.14 12-JUN-13:50 26.02 20.76
July 0.866932E+10 16614.75 02-JUL-18:21 23.35 16.56 0.615193E+09 845.75 27-JUL-13:39 29.40 20.89
August 0.773192E+10 16267.50 13-AUG-15:31 29.60 23.37 0.686541E+09 845.69 02-AUG-13:09 29.60 23.37
September 0.423101E+10 7282.64 15-SEP-14:00 25.60 21.03 0.587729E+09 845.68 12-SEP-13:09 25.60 21.03
October 0.181944E+10 4082.56 12-OCT-15:00 18.30 15.23 0.533690E+09 845.62 12-OCT-13:00 18.30 15.23
November 0.613581E+09 1832.39 16-NOV-17:00 18.30 13.48 0.473195E+09 768.54 16-NOV-14:00 18.30 13.48
December 67026658.67 1386.39 01-DEC-13:40 10.17 8.68 0.446130E+09 639.19 01-DEC-14:09 8.12 6.69
                     
Annual Sum or Average 0.376475E+11         0.657046E+10        
Minimum of Months 22431150.95 1204.97   -2.7 -3.8 0.419399E+09 625.93   -6.7 -8.5
Maximum of Months 0.866932E+10 16614.75   29.60 23.37 0.686541E+09 846.14   29.60 23.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 38190803.42 906.01 20-JAN-06:04 -0.7 -3.0 0.299061E+09 414.28 12-JAN-10:39 -0.7 -3.0
February 0.213341E+09 1691.94 28-FEB-10:05 -3.6 -5.3 0.277299E+09 544.95 28-FEB-10:09 -3.6 -5.3
March 0.140327E+10 6143.01 15-MAR-09:30 20.25 14.29 0.378077E+09 544.97 15-MAR-13:30 25.55 15.84
April 0.288278E+10 11752.89 23-APR-10:32 14.80 7.30 0.363265E+09 544.96 21-APR-13:00 14.80 7.30
May 0.535661E+10 16595.04 21-MAY-10:53 16.70 11.75 0.418855E+09 545.37 31-MAY-09:30 18.05 13.49
June 0.806931E+10 23380.60 11-JUN-09:32 24.03 16.62 0.426088E+09 546.05 20-JUN-09:00 23.30 16.76
July 0.919715E+10 24829.26 04-JUL-09:22 21.65 17.37 0.397372E+09 546.06 13-JUL-09:50 20.92 15.73
August 0.828256E+10 21194.35 06-AUG-09:12 24.47 17.45 0.444443E+09 546.04 04-AUG-09:00 24.47 17.45
September 0.504242E+10 23292.14 10-SEP-10:02 15.68 10.52 0.387349E+09 544.99 12-SEP-13:09 21.10 16.55
October 0.186782E+10 8286.01 11-OCT-09:30 15.85 11.81 0.373215E+09 544.95 27-OCT-13:20 10.17 7.43
November 0.561825E+09 2379.07 03-NOV-09:20 4.47 2.22 0.316525E+09 544.95 03-NOV-09:09 4.47 2.22
December 60659147.24 912.61 13-DEC-06:04 1.20 0.92 0.288547E+09 419.62 04-DEC-10:30 1.20 0.92
                     
Annual Sum or Average 0.429759E+11         0.437009E+10        
Minimum of Months 38190803.42 906.01   -3.6 -5.3 0.277299E+09 414.28   -3.6 -5.3
Maximum of Months 0.919715E+10 24829.26   24.47 17.45 0.444443E+09 546.06   25.55 17.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100837E+10 12506.53 12-JAN-13:40 -6.5 -9.0 0.497343E+09 845.64 30-JAN-14:20 -8.2 -9.8
February 0.146110E+10 16917.51 28-FEB-13:40 0.00 -2.9 0.460396E+09 845.72 28-FEB-14:00 0.00 -2.8
March 0.443264E+10 19161.43 15-MAR-13:30 25.55 15.84 0.607348E+09 846.53 15-MAR-13:00 26.10 16.06
April 0.474807E+10 19071.43 23-APR-14:32 15.20 9.59 0.551693E+09 850.04 11-APR-13:09 15.20 9.59
May 0.680752E+10 27034.74 14-MAY-13:42 24.82 18.07 0.637813E+09 845.69 10-MAY-13:39 24.82 18.07
June 0.940334E+10 26109.99 25-JUN-13:02 26.10 17.26 0.656272E+09 846.15 12-JUN-13:39 26.10 17.26
July 0.113724E+11 26866.37 30-JUL-12:32 25.60 19.52 0.615169E+09 846.63 31-JUL-13:00 25.00 19.43
August 0.120547E+11 27690.40 13-AUG-12:52 30.00 22.88 0.688234E+09 846.61 03-AUG-13:00 30.00 22.88
September 0.976567E+10 30069.93 10-SEP-12:41 17.12 10.59 0.599826E+09 869.73 21-SEP-13:39 25.40 16.58
October 0.574569E+10 23401.03 22-OCT-14:02 21.70 14.26 0.589120E+09 902.23 31-OCT-13:39 15.00 10.41
November 0.236907E+10 17065.84 03-NOV-12:40 8.53 4.68 0.521092E+09 845.66 16-NOV-14:09 17.20 13.27
December 0.728806E+09 10211.40 16-DEC-13:30 5.60 3.03 0.466064E+09 845.64 11-DEC-14:30 5.60 3.03
                     
Annual Sum or Average 0.698974E+11         0.689037E+10        
Minimum of Months 0.728806E+09 10211.40   -6.5 -9.0 0.460396E+09 845.64   -8.2 -9.8
Maximum of Months 0.120547E+11 30069.93   30.00 22.88 0.688234E+09 902.23   30.00 22.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128531E+09 1240.72 12-JAN-16:00 -6.1 -8.3 0.301512E+09 499.49 12-JAN-16:10 -6.2 -8.3
February 0.317867E+09 5790.24 28-FEB-16:30 0.00 -2.6 0.278646E+09 544.64 28-FEB-14:00 0.00 -2.6
March 0.175415E+10 8492.86 21-MAR-16:00 4.40 1.34 0.373110E+09 544.97 15-MAR-13:30 4.40 1.34
April 0.305478E+10 18170.84 02-APR-16:11 7.77 5.85 0.351785E+09 544.96 21-APR-13:00 14.40 8.43
May 0.563037E+10 28528.34 07-MAY-17:41 14.08 5.36 0.414388E+09 544.97 10-MAY-13:39 25.73 17.72
June 0.891140E+10 27778.09 11-JUN-16:51 25.60 17.82 0.425092E+09 544.99 22-JUN-13:09 20.60 15.40
July 0.955612E+10 31908.73 02-JUL-17:01 24.82 16.94 0.397368E+09 544.96 12-JUL-09:00 20.60 14.64
August 0.891213E+10 27334.99 13-AUG-15:31 29.60 23.37 0.444684E+09 545.00 02-AUG-13:09 29.60 23.37
September 0.510000E+10 27796.25 10-SEP-16:01 17.52 11.16 0.385701E+09 545.00 12-SEP-13:09 21.10 16.55
October 0.216386E+10 11895.48 11-OCT-16:00 21.70 14.52 0.363246E+09 544.95 12-OCT-13:00 18.30 14.87
November 0.803620E+09 4300.60 15-NOV-15:20 11.70 6.66 0.321777E+09 544.93 09-NOV-14:00 11.70 6.66
December 0.172149E+09 1261.55 04-DEC-16:00 -0.6 -3.3 0.290980E+09 505.31 04-DEC-16:10 -0.9 -3.5
                     
Annual Sum or Average 0.465050E+11         0.434829E+10        
Minimum of Months 0.128531E+09 1240.72   -6.1 -8.3 0.278646E+09 499.49   -6.2 -8.3
Maximum of Months 0.955612E+10 31908.73   29.60 23.37 0.444684E+09 545.00   29.60 23.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 97895249.81 5987.37 04-JAN-06:01 -12.3 -12.9 0.00 0.00 01-JAN-00:10 -12.3 -12.9
February 87649072.63 7857.63 06-FEB-05:01 -14.8 -15.7 0.00 0.00 01-FEB-00:10 -14.8 -15.7
March 0.166166E+10 5182.22 15-MAR-14:20 25.93 16.12 0.00 0.00 01-MAR-00:10 25.93 16.12
April 0.350816E+10 6819.18 10-APR-05:15 4.07 3.41 0.00 0.00 01-APR-00:10 4.07 3.41
May 0.469262E+10 8263.10 30-MAY-05:15 12.20 11.93 0.00 0.00 01-MAY-00:10 12.20 11.93
June 0.797408E+10 11145.22 28-JUN-05:10 17.20 15.14 0.00 0.00 01-JUN-00:10 17.20 15.14
July 0.986378E+10 12845.41 24-JUL-05:10 16.10 15.07 0.00 0.00 01-JUL-00:10 16.10 15.07
August 0.981307E+10 11277.43 07-AUG-05:15 20.20 18.58 0.00 0.00 01-AUG-00:10 20.20 18.58
September 0.584853E+10 9469.96 18-SEP-05:15 9.60 8.73 0.00 0.00 01-SEP-00:10 9.60 8.73
October 0.336236E+10 6728.57 23-OCT-05:15 11.70 10.06 0.00 0.00 01-OCT-00:10 11.70 10.06
November 0.197449E+10 5303.58 06-NOV-06:15 8.90 6.78 0.00 0.00 01-NOV-00:10 8.90 6.78
December 0.260738E+09 4126.10 11-DEC-05:01 -17.5 -18.0 0.00 0.00 01-DEC-00:10 -17.5 -18.0
                     
Annual Sum or Average 0.491450E+11         0.00        
Minimum of Months 87649072.63 4126.10   -17.5 -18.0 0.00 0.00   -17.5 -18.0
Maximum of Months 0.986378E+10 12845.41   25.93 18.58 0.00 0.00   25.93 18.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 98459458.07 9275.03 24-JAN-04:01 -11.7 -13.2 0.00 0.00 01-JAN-00:10 -11.7 -13.2
February 0.107699E+09 10261.78 21-FEB-04:11 -11.3 -12.5 0.00 0.00 01-FEB-00:10 -11.3 -12.5
March 0.499719E+09 9326.32 04-MAR-05:01 -10.1 -11.1 0.00 0.00 01-MAR-00:10 -10.1 -11.1
April 0.955760E+09 5250.72 17-APR-05:01 -4.0 -5.3 0.00 0.00 01-APR-00:10 -4.0 -5.3
May 0.277446E+10 4532.71 30-MAY-14:20 17.80 14.42 0.00 0.00 01-MAY-00:10 17.80 14.42
June 0.528668E+10 6272.22 21-JUN-05:15 18.30 16.18 0.00 0.00 01-JUN-00:10 18.30 16.18
July 0.654211E+10 7335.10 22-JUL-05:15 21.10 20.28 0.00 0.00 01-JUL-00:10 21.10 20.28
August 0.635455E+10 7220.90 07-AUG-05:15 20.20 18.58 0.00 0.00 01-AUG-00:10 20.20 18.58
September 0.376716E+10 6081.97 18-SEP-05:15 9.60 8.73 0.00 0.00 01-SEP-00:10 9.60 8.73
October 0.116675E+10 6007.82 30-OCT-05:01 -0.1 -0.9 0.00 0.00 01-OCT-00:10 -0.1 -0.9
November 0.357111E+09 7898.18 24-NOV-05:01 -3.0 -3.7 0.00 0.00 01-NOV-00:10 -3.0 -3.7
December 0.153384E+09 8691.14 27-DEC-04:01 -11.7 -12.1 0.00 0.00 01-DEC-00:10 -11.7 -12.1
                     
Annual Sum or Average 0.280638E+11         0.00        
Minimum of Months 98459458.07 4532.71   -11.7 -13.2 0.00 0.00   -11.7 -13.2
Maximum of Months 0.654211E+10 10261.78   21.10 20.28 0.00 0.00   21.10 20.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0 -1.6 0.00 0.00 01-JAN-00:10 -1.0 -1.6
February 0.00 0.00 01-FEB-00:03 -3.3 -4.7 0.00 0.00 01-FEB-00:10 -3.3 -4.7
March 0.528810E+09 11293.19 15-MAR-14:20 25.93 16.12 0.00 0.00 01-MAR-00:10 25.93 16.12
April 0.175444E+10 9464.76 21-APR-14:00 14.40 8.43 0.00 0.00 01-APR-00:10 14.40 8.43
May 0.508459E+10 13803.20 31-MAY-14:20 21.70 14.12 0.00 0.00 01-MAY-00:10 21.70 14.12
June 0.972571E+10 18465.07 12-JUN-13:40 30.20 20.07 0.00 0.00 01-JUN-00:10 30.20 20.07
July 0.118064E+11 18103.35 21-JUL-13:40 31.33 21.85 0.00 0.00 01-JUL-00:10 31.33 21.85
August 0.103473E+11 17722.85 09-AUG-15:20 29.40 18.24 0.00 0.00 01-AUG-00:10 29.40 18.24
September 0.506687E+10 13464.76 21-SEP-15:40 26.10 17.00 0.00 0.00 01-SEP-00:10 26.10 17.00
October 0.917992E+09 7606.42 11-OCT-15:40 21.87 14.55 0.00 0.00 01-OCT-00:10 21.87 14.55
November 26856393.46 990.12 04-NOV-15:20 18.30 13.65 0.00 0.00 01-NOV-00:10 18.30 13.65
December 0.00 0.00 01-DEC-00:10 4.95 3.07 0.00 0.00 01-DEC-00:10 4.95 3.07
                     
Annual Sum or Average 0.452589E+11         0.00        
Minimum of Months 0.00 0.00   -3.3 -4.7 0.00 0.00   -3.3 -4.7
Maximum of Months 0.118064E+11 18465.07   31.33 21.85 0.00 0.00   31.33 21.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237660E+10 1949.33 12-JAN-16:40 -6.5 -8.3 95230014.50 126.82 12-JAN-10:09 -6.5 -8.3
February 0.712219E+10 4162.10 28-FEB-17:00 -0.6 -3.0 86396456.92 126.82 21-FEB-10:39 -0.6 -3.0
March 0.139776E+11 7000.82 31-MAR-24:00 4.20 3.93 0.103237E+09 126.83 14-MAR-09:00 4.20 3.93
April 0.187885E+11 8202.92 02-APR-17:55 6.10 4.84 91605147.90 126.82 28-APR-13:00 10.00 9.06
May 0.436855E+10 3473.67 31-MAY-24:00 17.10 14.03 99235875.78 126.85 17-MAY-13:39 17.10 14.03
June 0.944783E+10 5391.38 30-JUN-24:00 16.90 13.02 98966808.37 126.86 27-JUN-09:00 16.90 13.02
July 0.149098E+11 7288.10 31-JUL-24:00 19.10 16.93 91888647.92 126.84 05-JUL-13:00 19.10 16.93
August 0.198774E+11 8244.54 02-AUG-18:40 22.07 14.68 0.103238E+09 126.83 30-AUG-09:00 17.80 17.48
September 0.435024E+10 3239.89 30-SEP-24:00 14.40 12.09 91610997.50 126.85 25-SEP-13:50 14.40 12.09
October 0.918240E+10 5165.97 31-OCT-24:00 6.60 4.77 95232267.05 126.84 12-OCT-13:00 6.60 4.77
November 0.135959E+11 5848.98 24-NOV-16:20 3.87 1.42 94300313.42 126.82 10-NOV-14:00 3.87 1.42
December 0.186039E+11 7739.65 04-DEC-16:20 -1.1 -3.7 91880848.04 126.82 01-DEC-14:09 -1.1 -3.7
                     
Annual Sum or Average 0.136601E+12         0.114282E+10        
Minimum of Months 0.237660E+10 1949.33   -6.5 -8.3 86396456.92 126.82   -6.5 -8.3
Maximum of Months 0.198774E+11 8244.54   22.07 16.93 0.103238E+09 126.86   19.10 17.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.370758E+09 1573.33 12-JAN-16:50 -6.6 -8.3 93271687.91 126.82 12-JAN-10:00 -6.6 -8.3
February 0.433855E+10 3665.92 28-FEB-17:00 -0.6 -3.0 86396470.85 126.82 21-FEB-10:39 -0.6 -3.0
March 0.117645E+11 6263.13 31-MAR-23:40 4.40 4.06 0.103237E+09 126.83 14-MAR-09:00 4.40 4.06
April 0.170119E+11 7686.50 24-APR-18:00 11.70 8.10 91605168.18 126.82 28-APR-13:00 10.00 9.06
May 0.371887E+10 3284.75 31-MAY-24:00 17.10 14.03 99235728.88 126.84 17-MAY-13:09 17.10 14.03
June 0.876665E+10 5137.03 30-JUN-24:00 16.90 13.02 98966491.24 126.86 27-JUN-13:00 16.90 13.02
July 0.140675E+11 6998.38 31-JUL-24:00 19.10 16.93 91889188.58 126.85 05-JUL-13:09 19.10 16.93
August 0.188070E+11 7912.00 02-AUG-18:40 22.07 14.68 0.103239E+09 126.83 30-AUG-13:09 18.58 18.07
September 0.368803E+10 2786.09 30-SEP-24:00 14.40 12.09 91609604.19 126.84 08-SEP-13:00 14.40 12.09
October 0.764965E+10 4553.12 31-OCT-23:40 6.73 4.84 95232176.79 126.84 12-OCT-13:00 6.73 4.84
November 0.112300E+11 5396.34 15-NOV-16:20 10.93 6.40 94300329.84 126.82 10-NOV-14:00 10.93 6.40
December 0.147858E+11 6976.12 04-DEC-16:30 -1.4 -3.9 91880866.06 126.82 01-DEC-14:09 -1.4 -3.9
                     
Annual Sum or Average 0.116199E+12         0.114086E+10        
Minimum of Months 0.370758E+09 1573.33   -6.6 -8.3 86396470.85 126.82   -6.6 -8.3
Maximum of Months 0.188070E+11 7912.00   22.07 16.93 0.103239E+09 126.86   19.10 18.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.133312E+09 1343.83 12-JAN-16:40 -6.5 -8.3 88490048.58 126.82 20-JAN-14:09 -0.4 -3.5
February 0.277069E+10 3601.06 28-FEB-17:00 -0.6 -3.0 86395817.87 126.82 21-FEB-10:39 -0.6 -3.0
March 0.101367E+11 5828.53 31-MAR-23:20 4.60 4.18 0.103237E+09 126.83 14-MAR-09:00 4.60 4.18
April 0.159434E+11 7678.97 24-APR-18:00 11.70 8.10 91605175.02 126.82 28-APR-13:00 10.00 9.06
May 0.327502E+10 3186.87 31-MAY-23:40 17.17 13.97 99235708.73 126.84 30-MAY-13:00 17.17 13.97
June 0.867334E+10 5062.17 30-JUN-23:40 17.07 12.89 98966754.05 126.86 27-JUN-13:00 17.07 12.89
July 0.140984E+11 6982.71 31-JUL-24:00 19.10 16.93 91889395.19 126.85 05-JUL-13:09 19.10 16.93
August 0.187614E+11 7965.22 02-AUG-18:40 22.07 14.68 0.103239E+09 126.83 30-AUG-13:09 18.58 18.07
September 0.330017E+10 2498.60 04-SEP-17:48 16.97 12.18 91609312.72 126.85 08-SEP-13:00 22.80 18.10
October 0.629010E+10 4141.12 31-OCT-23:20 6.87 4.91 95232144.01 126.84 12-OCT-13:00 6.87 4.91
November 0.940683E+10 5264.94 15-NOV-16:30 10.55 6.20 94300331.10 126.82 10-NOV-14:00 10.55 6.20
December 0.127772E+11 6620.59 04-DEC-16:30 -1.4 -3.9 91880872.99 126.82 01-DEC-14:09 -1.4 -3.9
                     
Annual Sum or Average 0.105567E+12         0.113608E+10        
Minimum of Months 0.133312E+09 1343.83   -6.5 -8.3 86395817.87 126.82   -1.4 -3.9
Maximum of Months 0.187614E+11 7965.22   22.07 16.93 0.103239E+09 126.86   22.80 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234599E+12 90431.45 18-JAN-17:00 1.70 1.21 0.206144E+10 2745.29 13-JAN-14:00 1.70 1.21
February 0.432421E+12 182056.92 23-FEB-17:00 -0.6 -1.8 0.187023E+10 2745.34 22-FEB-14:50 -0.6 -1.8
March 0.726731E+12 357897.66 31-MAR-24:00 4.20 3.93 0.223487E+10 2749.26 14-MAR-13:09 4.20 3.93
April 0.941346E+12 366736.29 24-APR-16:00 13.30 7.63 0.198305E+10 2748.64 28-APR-09:09 10.00 8.84
May 0.239361E+12 175662.99 31-MAY-24:00 17.10 14.03 0.214808E+10 2745.71 10-MAY-13:09 17.10 14.03
June 0.470127E+12 267991.02 30-JUN-24:00 16.90 13.02 0.214234E+10 2748.51 01-JUN-13:00 16.90 13.02
July 0.732428E+12 360089.58 31-JUL-24:00 19.10 16.93 0.199617E+10 2992.02 21-JUL-09:09 19.10 16.93
August 0.977071E+12 378592.97 15-AUG-16:41 20.87 19.23 0.231147E+10 3747.77 15-AUG-13:09 20.87 19.23
September 0.235392E+12 175484.92 30-SEP-24:00 14.40 12.09 0.198297E+10 2746.05 21-SEP-13:00 14.40 12.09
October 0.486215E+12 268099.09 31-OCT-24:00 6.60 4.77 0.206145E+10 2746.13 23-OCT-09:30 6.60 4.77
November 0.706965E+12 275752.75 06-NOV-17:00 6.10 3.25 0.204137E+10 2746.86 16-NOV-14:09 17.20 13.27
December 0.973366E+12 366624.61 04-DEC-16:55 -2.2 -4.4 0.198898E+10 2747.44 01-DEC-10:00 -2.2 -4.4
                     
Annual Sum or Average 0.715602E+13         0.248224E+11        
Minimum of Months 0.234599E+12 90431.45   -2.2 -4.4 0.187023E+10 2745.29   -2.2 -4.4
Maximum of Months 0.977071E+12 378592.97   20.87 19.23 0.231147E+10 3747.77   20.87 19.23



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.709911E+09 49035.25 02-JAN-04:01 -1.0
February 88026934.40 40305.12 06-FEB-05:01 -14.8
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 70806337.63 40236.89 11-DEC-05:01 -17.5
         
Annual Sum or Average 0.868744E+09      
Minimum of Months 0.00 0.00   -17.5
Maximum of Months 0.709911E+09 49035.25   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.587608E+10 73857.90 02-JAN-04:01 -1.0
February 0.478198E+10 73179.71 06-FEB-04:01 -15.0
March 0.155632E+10 70342.94 06-MAR-04:01 -11.1
April 0.254265E+09 65763.24 17-APR-04:01 -3.4
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.239764E+09 64307.77 30-OCT-04:01 -0.5
November 0.813278E+09 66900.50 24-NOV-05:01 -3.0
December 0.432551E+10 73624.61 11-DEC-04:11 -17.2
         
Annual Sum or Average 0.178472E+11      
Minimum of Months 0.00 0.00   -17.2
Maximum of Months 0.587608E+10 73857.90   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.449304E+09 11453.11 30-JAN-05:01 -9.5
February 0.303786E+09 11882.15 06-FEB-05:01 -14.8
March 39192335.47 10882.86 07-MAR-06:01 -13.3
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.103520E+09 11220.63 11-DEC-05:01 -17.5
         
Annual Sum or Average 0.895803E+09      
Minimum of Months 0.00 0.00   -17.5
Maximum of Months 0.449304E+09 11882.15   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.332030E+09 11324.13 30-JAN-05:01 -9.5
February 0.256371E+09 11937.88 06-FEB-05:01 -14.8
March 24996099.87 10259.86 06-MAR-06:01 -11.1
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.173007E+09 11316.48 11-DEC-05:01 -17.5
         
Annual Sum or Average 0.786404E+09      
Minimum of Months 0.00 0.00   -17.5
Maximum of Months 0.332030E+09 11937.88   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.709959E+09 17642.41 30-JAN-05:01 -9.5
February 0.588110E+09 17663.26 07-FEB-05:01 -15.7
March 66581591.99 16176.45 06-MAR-05:01 -11.1
April 1109767.99 7076.80 17-APR-05:01 -4.0
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 626481.88 8123.23 30-OCT-05:01 -0.1
November 6991330.04 13900.06 24-NOV-06:01 -3.8
December 0.287995E+09 16998.55 11-DEC-05:01 -17.5
         
Annual Sum or Average 0.166137E+10      
Minimum of Months 0.00 0.00   -17.5
Maximum of Months 0.709959E+09 17663.26   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 55531155.81 8294.50 09-JAN-06:01 -9.4
February 19898868.03 8780.51 06-FEB-05:01 -14.8
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 75430023.84      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 55531155.81 8780.51   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.516068E+10 12831.74 09-JAN-02:62 -8.5
February 0.407504E+10 12860.64 06-FEB-04:11 -15.0
March 0.127641E+10 12558.14 06-MAR-04:01 -11.1
April 99817227.35 10962.26 17-APR-04:01 -3.4
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 77131668.07 10618.60 30-OCT-04:01 -0.5
November 0.410947E+09 11303.29 24-NOV-05:01 -3.0
December 0.388192E+10 12688.02 26-DEC-03:42 -11.7
         
Annual Sum or Average 0.149819E+11      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.516068E+10 12860.64   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.281560E+10 18047.13 02-JAN-04:01 -1.0
February 0.221255E+10 18220.07 13-FEB-04:01 -8.9
March 0.475455E+09 17202.09 06-MAR-04:01 -11.1
April 39826239.24 15040.81 17-APR-04:01 -3.4
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 42713305.35 14714.59 30-OCT-04:01 -0.5
November 0.250850E+09 15897.28 24-NOV-05:01 -3.0
December 0.232685E+10 17812.49 12-DEC-04:01 -10.9
         
Annual Sum or Average 0.816386E+10      
Minimum of Months 0.00 0.00   -11.1
Maximum of Months 0.281560E+10 18220.07   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.313691E+10 20848.20 02-JAN-04:01 -1.0
February 0.256836E+10 21015.18 06-FEB-04:11 -15.0
March 0.488404E+09 18568.52 06-MAR-05:01 -11.1
April 57970260.80 17191.09 17-APR-04:01 -3.4
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 32169685.62 16664.11 30-OCT-05:01 -0.1
November 0.249337E+09 18259.04 24-NOV-05:01 -3.0
December 0.245601E+10 20273.93 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.898916E+10      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.313691E+10 21015.18   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248436E+10 17994.95 02-JAN-04:01 -1.0
February 0.184996E+10 18140.86 06-FEB-04:11 -15.0
March 0.364210E+09 16050.81 06-MAR-04:01 -11.1
April 14555105.27 13887.57 17-APR-05:01 -4.0
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 21524077.20 13955.12 16-OCT-05:01 1.20
November 0.143626E+09 15164.53 24-NOV-05:01 -3.0
December 0.172584E+10 17421.68 26-DEC-04:01 -11.8
         
Annual Sum or Average 0.660408E+10      
Minimum of Months 0.00 0.00   -15.0
Maximum of Months 0.248436E+10 18140.86   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.980476E+10 15290.11 09-JAN-02:62 -8.5
February 0.825493E+10 15699.99 06-FEB-03:42 -14.8
March 0.375087E+10 14941.56 06-MAR-03:42 -11.0
April 0.783413E+09 14277.43 17-APR-03:01 -2.9
May 15009280.44 11576.76 01-MAY-05:02 1.70
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 13012825.40 11327.15 30-SEP-05:03 7.20
October 0.732168E+09 14214.27 30-OCT-03:01 -0.1
November 0.225141E+10 14374.70 24-NOV-04:01 -3.2
December 0.868966E+10 15365.81 26-DEC-01:12 -11.3
         
Annual Sum or Average 0.342952E+11      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 0.980476E+10 15699.99   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.565613E+10 20467.77 09-JAN-02:62 -8.5
February 0.475918E+10 21151.59 06-FEB-03:42 -14.8
March 0.165011E+10 19434.83 20-MAR-03:01 -2.3
April 0.334393E+09 19311.67 17-APR-03:01 -2.9
May 5566001.79 13507.48 01-MAY-05:02 1.70
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 7819381.33 9391.57 30-SEP-05:03 7.20
October 0.359259E+09 19414.35 30-OCT-03:01 -0.1
November 0.129492E+10 19612.67 24-NOV-04:01 -3.2
December 0.543929E+10 20643.22 26-DEC-01:12 -11.3
         
Annual Sum or Average 0.195067E+11      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 0.565613E+10 21151.59   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.663325E+10 23314.12 29-JAN-23:02 -9.0
February 0.584267E+10 24163.07 06-FEB-03:42 -14.8
March 0.197903E+10 22241.42 20-MAR-03:01 -2.3
April 0.568692E+09 21984.37 17-APR-03:01 -2.9
May 12370427.76 13454.32 01-MAY-05:02 1.70
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 7094509.09 8896.99 30-SEP-05:03 7.20
October 0.406368E+09 21574.05 30-OCT-03:01 -0.1
November 0.154278E+10 22366.57 24-NOV-04:01 -3.2
December 0.627001E+10 23661.80 26-DEC-01:12 -11.3
         
Annual Sum or Average 0.232623E+11      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 0.663325E+10 24163.07   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.508353E+10 21854.58 09-JAN-02:62 -8.5
February 0.385159E+10 22354.71 06-FEB-03:42 -14.8
March 0.127787E+10 20617.61 06-MAR-04:01 -11.1
April 0.219415E+09 18744.79 17-APR-03:01 -2.9
May 82672.96 551.15 12-MAY-05:03 8.90
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 1220436.62 2335.34 30-SEP-05:03 7.20
October 0.238616E+09 18555.51 30-OCT-04:01 -0.5
November 0.862731E+09 20649.59 24-NOV-04:01 -3.2
December 0.398231E+10 21847.67 26-DEC-05:11 -12.2
         
Annual Sum or Average 0.155174E+11      
Minimum of Months 0.00 0.00   -14.8
Maximum of Months 0.508353E+10 22354.71   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143475E+10 10595.52 11-JAN-06:02 5.68
February 0.129730E+10 10975.97 15-FEB-06:02 5.60
March 0.247773E+09 10737.16 02-MAR-06:01 1.10
April 0.138016E+09 10793.36 20-APR-04:12 11.50
May 88056474.30 8996.47 14-MAY-14:32 25.73
June 0.109249E+09 11537.28 11-JUN-15:21 25.85
July 0.152628E+09 11096.42 16-JUL-16:21 28.90
August 0.120003E+09 11723.07 13-AUG-15:01 29.90
September 83628102.20 9221.32 10-SEP-14:51 17.20
October 0.103603E+09 9249.63 10-OCT-04:12 10.00
November 89424383.37 11404.37 27-NOV-05:12 17.97
December 0.633655E+09 11749.23 14-DEC-06:02 5.68
         
Annual Sum or Average 0.449809E+10      
Minimum of Months 83628102.20 8996.47   1.10
Maximum of Months 0.143475E+10 11749.23   29.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.420679E+10 17458.72 02-JAN-06:13 -1.1
February 0.330465E+10 7461.77 08-FEB-11:05 -7.1
March 0.173179E+10 6494.53 23-MAR-05:02 4.72
April 0.393241E+09 8387.00 02-APR-16:11 7.77
May 62290392.93 8858.66 14-MAY-14:42 25.92
June 66860832.32 11786.41 11-JUN-16:01 25.60
July 79288689.64 9483.80 16-JUL-16:31 28.33
August 50705573.15 10091.74 13-AUG-15:12 29.80
September 66812815.11 9307.94 10-SEP-15:42 17.70
October 0.304340E+09 7333.27 09-OCT-12:32 12.03
November 0.886082E+09 6474.97 16-NOV-06:02 11.78
December 0.285837E+10 7064.65 11-DEC-14:10 -7.9
         
Annual Sum or Average 0.140112E+11      
Minimum of Months 50705573.15 6474.97   -7.9
Maximum of Months 0.420679E+10 17458.72   29.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118564E+11 27210.71 30-JAN-05:12 -9.6
February 0.101954E+11 28981.39 06-FEB-05:12 -14.6
March 0.521944E+10 26780.77 06-MAR-05:13 -11.1
April 0.202162E+10 21079.24 17-APR-05:13 -4.1
May 0.672744E+09 13850.66 16-MAY-05:02 11.10
June 0.202433E+09 12663.87 06-JUN-05:03 6.78
July 0.103886E+09 12077.91 03-JUL-04:12 11.70
August 0.143440E+09 12037.32 03-AUG-05:03 11.10
September 0.533624E+09 13068.48 19-SEP-05:02 10.60
October 0.198769E+10 17246.31 30-OCT-05:13 -0.2
November 0.416783E+10 21619.16 24-NOV-06:13 -3.7
December 0.106871E+11 29319.93 11-DEC-05:42 -18.6
         
Annual Sum or Average 0.477915E+11      
Minimum of Months 0.103886E+09 12037.32   -18.6
Maximum of Months 0.118564E+11 29319.93   11.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.523769E+09 549.77 03-JAN-01:20 -2.8
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.523769E+09      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.523769E+09 549.77   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.775933E+09 588.75 15-JAN-18:50 0.18
February 0.113785E+09 551.12 05-FEB-20:05 -11.2
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.889718E+09      
Minimum of Months 0.00 0.00   -11.2
Maximum of Months 0.775933E+09 588.75   18.85



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:03 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:05 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:05 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.138227E+11 14744.03 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.125395E+11 14744.03 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.149226E+11 14744.03 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.133065E+11 14744.03 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.143726E+11 14744.03 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.143114E+11 14744.03 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.133677E+11 14744.03 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.149224E+11 14744.03 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.133065E+11 14744.03 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.138228E+11 14744.03 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.136668E+11 14744.03 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.133678E+11 14744.03 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.165729E+12     0.424397E+12    
Minimum of Months 0.125395E+11 14744.03   0.325565E+11 13457.54  
Maximum of Months 0.149226E+11 14744.03   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289614E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.63  
Maximum of Months 0.134015E+11 13241.18   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.991120E+09 1662.56 02-JAN-16:49 0.305979E+10 2160.55 02-JAN-08:09
February 0.844542E+09 1441.39 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.940217E+09 1158.25 17-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.808427E+09 919.49 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.850114E+09 868.10 11-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.835587E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.785674E+09 854.52 11-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.887196E+09 867.08 24-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.827411E+09 1108.99 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.908775E+09 1599.74 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.995068E+09 1662.56 06-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.994497E+09 1662.56 01-DEC-16:40 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.106686E+11     0.363654E+11    
Minimum of Months 0.785674E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.995068E+09 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.628351E+09 1071.42 02-JAN-16:49 0.197184E+10 1392.34 02-JAN-08:09
February 0.540904E+09 937.96 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.603751E+09 595.23 01-MAR-17:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.521509E+09 571.78 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.550495E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.541232E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.508626E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.573967E+09 552.00 28-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.532096E+09 588.53 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.579121E+09 852.94 26-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.630978E+09 1071.42 06-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.629339E+09 1071.42 01-DEC-16:40 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.684037E+10     0.234352E+11    
Minimum of Months 0.508626E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.630978E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.958072E+09 1662.60 02-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.831512E+09 1406.83 01-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.934185E+09 1120.64 17-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.810031E+09 918.02 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.854845E+09 872.62 11-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.839872E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.790160E+09 859.72 11-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.890733E+09 870.20 24-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.825741E+09 1080.68 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.893740E+09 1398.09 30-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.964382E+09 1662.60 06-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.961115E+09 1662.60 01-DEC-16:40 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.105544E+11     0.363660E+11    
Minimum of Months 0.790160E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.964382E+09 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.626159E+09 1071.42 02-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.538992E+09 924.55 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.603691E+09 791.13 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.520972E+09 600.05 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.548526E+09 574.40 11-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.538492E+09 547.64 21-JUN-08:09 0.197570E+10 1392.33 01-JUN-07:10
July 0.507042E+09 567.65 11-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.572104E+09 578.15 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.533139E+09 759.61 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.582489E+09 1030.67 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.629438E+09 1071.42 06-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.628997E+09 1071.42 01-DEC-16:40 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.683004E+10     0.234351E+11    
Minimum of Months 0.507042E+09 547.64   0.178514E+10 1392.33  
Maximum of Months 0.629438E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.987912E+09 1662.56 02-JAN-16:49 0.305979E+10 2160.55 02-JAN-08:09
February 0.843195E+09 1438.89 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.939053E+09 1152.32 17-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.808023E+09 913.64 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.849585E+09 859.33 11-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.835220E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.785352E+09 844.92 11-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.886675E+09 858.30 24-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.826645E+09 1102.39 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.907201E+09 1598.83 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.991742E+09 1662.56 06-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.991522E+09 1662.56 01-DEC-16:40 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.106521E+11     0.363654E+11    
Minimum of Months 0.785352E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.991742E+09 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.627207E+09 1071.42 02-JAN-16:49 0.197184E+10 1392.34 02-JAN-08:09
February 0.540171E+09 934.52 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.603173E+09 595.23 01-MAR-17:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.521164E+09 567.65 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.550077E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.540940E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.508374E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.573501E+09 546.03 28-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.531659E+09 585.18 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.578549E+09 848.25 26-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.629791E+09 1071.42 06-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.628144E+09 1071.42 01-DEC-16:40 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.683275E+10     0.234352E+11    
Minimum of Months 0.508374E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.629791E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.956996E+09 1662.60 02-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.830607E+09 1404.29 01-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.933508E+09 1114.53 17-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.809533E+09 912.10 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.854220E+09 864.06 11-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.839454E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.789614E+09 850.38 11-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.890125E+09 861.57 24-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.825012E+09 1073.88 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.893203E+09 1392.44 30-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.963542E+09 1662.60 06-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.960234E+09 1662.60 01-DEC-16:40 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.105460E+11     0.363660E+11    
Minimum of Months 0.789614E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.963542E+09 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.624882E+09 1071.42 02-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.538205E+09 920.76 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.603017E+09 783.78 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.520575E+09 596.81 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.548061E+09 569.72 11-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.538272E+09 541.12 21-JUN-08:09 0.197570E+10 1392.33 01-JUN-07:10
July 0.506736E+09 562.57 11-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.571690E+09 573.68 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.532657E+09 751.42 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.581528E+09 1030.09 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.628098E+09 1071.42 06-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.627684E+09 1071.42 01-DEC-16:40 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.682140E+10     0.234351E+11    
Minimum of Months 0.506736E+09 541.12   0.178514E+10 1392.33  
Maximum of Months 0.628098E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.987754E+09 1662.56 02-JAN-16:49 0.305979E+10 2160.55 02-JAN-08:09
February 0.843143E+09 1438.45 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.939014E+09 1151.35 17-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.808004E+09 913.40 12-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.849529E+09 858.97 11-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.835207E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.785341E+09 844.54 11-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.886663E+09 857.94 24-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.826614E+09 1101.30 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.907142E+09 1598.80 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.991643E+09 1662.56 06-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.991330E+09 1662.56 01-DEC-16:40 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.106514E+11     0.363654E+11    
Minimum of Months 0.785341E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.991643E+09 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.627156E+09 1071.42 02-JAN-16:49 0.197184E+10 1392.34 02-JAN-08:09
February 0.540145E+09 934.25 01-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.603169E+09 595.23 01-MAR-17:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.521153E+09 567.46 12-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.550063E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.540932E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.508364E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.573488E+09 545.79 28-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.531643E+09 585.01 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.578527E+09 847.86 26-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.629709E+09 1071.42 06-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.628090E+09 1071.42 01-DEC-16:40 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.683244E+10     0.234352E+11    
Minimum of Months 0.508364E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.629709E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.956865E+09 1662.60 02-JAN-16:49 0.305983E+10 2160.58 02-JAN-08:09
February 0.830551E+09 1403.80 01-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.933441E+09 1113.50 17-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.809513E+09 911.86 12-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.854170E+09 863.71 11-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.839430E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.789593E+09 850.01 11-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.890078E+09 861.22 24-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.824986E+09 1072.74 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.893172E+09 1392.40 30-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.963492E+09 1662.60 06-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.960104E+09 1662.60 01-DEC-16:40 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.105454E+11     0.363660E+11    
Minimum of Months 0.789593E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.963492E+09 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.624751E+09 1071.42 02-JAN-16:49 0.197183E+10 1392.33 02-JAN-08:09
February 0.538145E+09 920.46 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.602988E+09 783.22 17-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.520544E+09 596.68 12-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.548047E+09 569.53 11-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.538265E+09 540.92 21-JUN-08:09 0.197570E+10 1392.33 01-JUN-07:10
July 0.506728E+09 562.37 11-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.571649E+09 573.51 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.532622E+09 750.79 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.581466E+09 1030.07 31-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.628035E+09 1071.42 06-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.627580E+09 1071.42 01-DEC-16:40 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.682082E+10     0.234351E+11    
Minimum of Months 0.506728E+09 540.92   0.178514E+10 1392.33  
Maximum of Months 0.628035E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.397259E+10 4157.19 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.360343E+10 4157.19 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.428189E+10 4157.19 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.382459E+10 4157.19 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.412724E+10 4157.19 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.410728E+10 4157.19 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.384455E+10 4157.19 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.428189E+10 4157.19 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.382459E+10 4157.19 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.397259E+10 4157.19 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.392603E+10 4157.19 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.384455E+10 4157.19 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.476112E+11     0.749486E+13    
Minimum of Months 0.360343E+10 4157.19   0.246344E+12 94908.13  
Maximum of Months 0.428189E+10 4157.19   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.138227E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.143726E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.143114E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.133677E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.149224E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.138228E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.136668E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.133678E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.165729E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.991120E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.776799E+09
February 0.136985E+10 0.844542E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.826422E+09
March 0.163685E+10 0.940217E+09 0.318369E+10 0.00 0.00 0.00 0.00 162078.32 0.521924E+09
April 0.145243E+10 0.808427E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.430104E+09
May 0.157338E+10 0.850114E+09 0.312174E+10 0.00 0.00 0.00 0.00 78996.41 0.245463E+09
June 0.156900E+10 0.835587E+09 0.306580E+10 0.00 0.00 0.00 0.00 3835364.15 0.138856E+09
July 0.145680E+10 0.785674E+09 0.300989E+10 0.00 0.00 0.00 0.00 9828079.20 78357636.67
August 0.163685E+10 0.887196E+09 0.318369E+10 0.00 0.00 0.00 0.00 7358982.19 89727311.27
September 0.145243E+10 0.827411E+09 0.295328E+10 0.00 0.00 0.00 0.00 540075.83 0.144421E+09
October 0.150991E+10 0.908775E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.336856E+09
November 0.149516E+10 0.995068E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.466001E+09
December 0.145680E+10 0.994497E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.852062E+09
                   
Annual Sum or Average 0.181194E+11 0.106686E+11 0.363654E+11 0.00 0.00 0.00 0.00 21803576.09 0.490699E+10
Minimum of Months 0.136985E+10 0.785674E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 78357636.67
Maximum of Months 0.163685E+10 0.995068E+09 0.318369E+10 0.00 0.00 0.00 0.00 9828079.20 0.852062E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.628351E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.518420E+09
February 0.882782E+09 0.540904E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.548488E+09
March 0.105485E+10 0.603751E+09 0.205169E+10 0.00 0.00 0.00 0.00 108048.31 0.347688E+09
April 0.936002E+09 0.521509E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.283892E+09
May 0.101394E+10 0.550495E+09 0.201177E+10 0.00 0.00 0.00 0.00 49208.65 0.166902E+09
June 0.101113E+10 0.541232E+09 0.197572E+10 0.00 0.00 0.00 0.00 2553036.25 92964928.02
July 0.938820E+09 0.508626E+09 0.193969E+10 0.00 0.00 0.00 0.00 6587563.37 51597993.39
August 0.105485E+10 0.573967E+09 0.205169E+10 0.00 0.00 0.00 0.00 4856290.07 58706491.52
September 0.936002E+09 0.532096E+09 0.190321E+10 0.00 0.00 0.00 0.00 352820.73 97482775.72
October 0.973041E+09 0.579121E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.224713E+09
November 0.963541E+09 0.630978E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.305424E+09
December 0.938820E+09 0.629339E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.557699E+09
                   
Annual Sum or Average 0.116768E+11 0.684037E+10 0.234352E+11 0.00 0.00 0.00 0.00 14506967.37 0.325398E+10
Minimum of Months 0.882782E+09 0.508626E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 51597993.39
Maximum of Months 0.105485E+10 0.630978E+09 0.205169E+10 0.00 0.00 0.00 0.00 6587563.37 0.557699E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.958072E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.774070E+09
February 0.136988E+10 0.831512E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.815615E+09
March 0.163688E+10 0.934185E+09 0.318374E+10 0.00 0.00 0.00 0.00 161497.36 0.528912E+09
April 0.145246E+10 0.810031E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.428641E+09
May 0.157341E+10 0.854845E+09 0.312179E+10 0.00 0.00 0.00 0.00 73810.98 0.248767E+09
June 0.156904E+10 0.839872E+09 0.306585E+10 0.00 0.00 0.00 0.00 3810392.73 0.139147E+09
July 0.145684E+10 0.790160E+09 0.300994E+10 0.00 0.00 0.00 0.00 9656713.92 79530198.75
August 0.163688E+10 0.890733E+09 0.318374E+10 0.00 0.00 0.00 0.00 6957699.08 92978273.93
September 0.145246E+10 0.825741E+09 0.295333E+10 0.00 0.00 0.00 0.00 495257.81 0.149351E+09
October 0.150994E+10 0.893740E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.340880E+09
November 0.149520E+10 0.964382E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.458263E+09
December 0.145684E+10 0.961115E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.839190E+09
                   
Annual Sum or Average 0.181198E+11 0.105544E+11 0.363660E+11 0.00 0.00 0.00 0.00 21155371.88 0.489535E+10
Minimum of Months 0.136988E+10 0.790160E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 79530198.75
Maximum of Months 0.163688E+10 0.964382E+09 0.318374E+10 0.00 0.00 0.00 0.00 9656713.92 0.839190E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.626159E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.538785E+09
February 0.882782E+09 0.538992E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.583075E+09
March 0.105485E+10 0.603691E+09 0.205168E+10 0.00 0.00 0.00 0.00 108048.17 0.381833E+09
April 0.936002E+09 0.520972E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.318339E+09
May 0.101394E+10 0.548526E+09 0.201175E+10 0.00 0.00 0.00 0.00 49208.21 0.180067E+09
June 0.101113E+10 0.538492E+09 0.197570E+10 0.00 0.00 0.00 0.00 2429136.94 0.106057E+09
July 0.938820E+09 0.507042E+09 0.193968E+10 0.00 0.00 0.00 0.00 6066529.00 64772230.62
August 0.105485E+10 0.572104E+09 0.205168E+10 0.00 0.00 0.00 0.00 4542456.22 74341962.60
September 0.936002E+09 0.533139E+09 0.190319E+10 0.00 0.00 0.00 0.00 325372.46 0.106595E+09
October 0.973041E+09 0.582489E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.245389E+09
November 0.963541E+09 0.629438E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.339694E+09
December 0.938820E+09 0.628997E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.621714E+09
                   
Annual Sum or Average 0.116768E+11 0.683004E+10 0.234351E+11 0.00 0.00 0.00 0.00 13520751.00 0.356066E+10
Minimum of Months 0.882782E+09 0.507042E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 64772230.62
Maximum of Months 0.105485E+10 0.629438E+09 0.205168E+10 0.00 0.00 0.00 0.00 6066529.00 0.621714E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.987912E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.162914E+10
February 0.136985E+10 0.843195E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.173444E+10
March 0.163685E+10 0.939053E+09 0.318369E+10 0.00 0.00 0.00 0.00 337496.86 0.109635E+10
April 0.145243E+10 0.808023E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.903033E+09
May 0.157338E+10 0.849585E+09 0.312174E+10 0.00 0.00 0.00 0.00 213803.84 0.541758E+09
June 0.156900E+10 0.835220E+09 0.306580E+10 0.00 0.00 0.00 0.00 8878618.56 0.310154E+09
July 0.145680E+10 0.785352E+09 0.300989E+10 0.00 0.00 0.00 0.00 22149579.18 0.181801E+09
August 0.163685E+10 0.886675E+09 0.318369E+10 0.00 0.00 0.00 0.00 17520597.88 0.208119E+09
September 0.145243E+10 0.826645E+09 0.295328E+10 0.00 0.00 0.00 0.00 1260324.41 0.313785E+09
October 0.150991E+10 0.907201E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.696288E+09
November 0.149516E+10 0.991742E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.936550E+09
December 0.145680E+10 0.991522E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.174194E+10
                   
Annual Sum or Average 0.181194E+11 0.106521E+11 0.363654E+11 0.00 0.00 0.00 0.00 50360420.72 0.102934E+11
Minimum of Months 0.136985E+10 0.785352E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.181801E+09
Maximum of Months 0.163685E+10 0.991742E+09 0.318369E+10 0.00 0.00 0.00 0.00 22149579.18 0.174194E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.627207E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.109321E+10
February 0.649041E+09 0.540171E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.116429E+10
March 0.773965E+09 0.603173E+09 0.205169E+10 0.00 0.00 0.00 0.00 178403.64 0.755003E+09
April 0.688021E+09 0.521164E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.625381E+09
May 0.744847E+09 0.550077E+09 0.201177E+10 0.00 0.00 0.00 0.00 93977.98 0.382564E+09
June 0.742030E+09 0.540940E+09 0.197572E+10 0.00 0.00 0.00 0.00 5370249.85 0.217553E+09
July 0.690839E+09 0.508374E+09 0.193969E+10 0.00 0.00 0.00 0.00 13535218.85 0.129026E+09
August 0.773965E+09 0.573501E+09 0.205169E+10 0.00 0.00 0.00 0.00 10261842.35 0.148324E+09
September 0.688021E+09 0.531659E+09 0.190321E+10 0.00 0.00 0.00 0.00 714022.27 0.221729E+09
October 0.715730E+09 0.578549E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.488097E+09
November 0.708685E+09 0.629791E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.638385E+09
December 0.690839E+09 0.628144E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.116471E+10
                   
Annual Sum or Average 0.858171E+10 0.683275E+10 0.234352E+11 0.00 0.00 0.00 0.00 30153714.93 0.702827E+10
Minimum of Months 0.649041E+09 0.508374E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.129026E+09
Maximum of Months 0.773965E+09 0.629791E+09 0.205169E+10 0.00 0.00 0.00 0.00 13535218.85 0.116471E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.956996E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.170295E+10
February 0.136988E+10 0.830607E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.179091E+10
March 0.163688E+10 0.933508E+09 0.318374E+10 0.00 0.00 0.00 0.00 336555.70 0.118542E+10
April 0.145246E+10 0.809533E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.950650E+09
May 0.157341E+10 0.854220E+09 0.312179E+10 0.00 0.00 0.00 0.00 158292.23 0.568219E+09
June 0.156904E+10 0.839454E+09 0.306585E+10 0.00 0.00 0.00 0.00 8549299.02 0.318171E+09
July 0.145684E+10 0.789614E+09 0.300994E+10 0.00 0.00 0.00 0.00 21138900.77 0.190417E+09
August 0.163688E+10 0.890125E+09 0.318374E+10 0.00 0.00 0.00 0.00 15607465.93 0.224603E+09
September 0.145246E+10 0.825012E+09 0.295333E+10 0.00 0.00 0.00 0.00 1053788.40 0.341802E+09
October 0.150994E+10 0.893203E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.765462E+09
November 0.149520E+10 0.963542E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.998295E+09
December 0.145684E+10 0.960234E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.181510E+10
                   
Annual Sum or Average 0.181198E+11 0.105460E+11 0.363660E+11 0.00 0.00 0.00 0.00 46844302.07 0.108520E+11
Minimum of Months 0.136988E+10 0.789614E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.190417E+09
Maximum of Months 0.163688E+10 0.963542E+09 0.318374E+10 0.00 0.00 0.00 0.00 21138900.77 0.181510E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.624882E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.110942E+10
February 0.882782E+09 0.538205E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.118728E+10
March 0.105485E+10 0.603017E+09 0.205168E+10 0.00 0.00 0.00 0.00 224988.77 0.782309E+09
April 0.936002E+09 0.520575E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.647775E+09
May 0.101394E+10 0.548061E+09 0.201175E+10 0.00 0.00 0.00 0.00 105531.94 0.395934E+09
June 0.101113E+10 0.538272E+09 0.197570E+10 0.00 0.00 0.00 0.00 5412792.05 0.230873E+09
July 0.938820E+09 0.506736E+09 0.193968E+10 0.00 0.00 0.00 0.00 13806997.98 0.142326E+09
August 0.105485E+10 0.571690E+09 0.205168E+10 0.00 0.00 0.00 0.00 10369358.47 0.161994E+09
September 0.936002E+09 0.532657E+09 0.190319E+10 0.00 0.00 0.00 0.00 717950.63 0.228843E+09
October 0.973041E+09 0.581528E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.494567E+09
November 0.963541E+09 0.628098E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.650095E+09
December 0.938820E+09 0.627684E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.119200E+10
                   
Annual Sum or Average 0.116768E+11 0.682140E+10 0.234351E+11 0.00 0.00 0.00 0.00 30637619.84 0.722341E+10
Minimum of Months 0.882782E+09 0.506736E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.142326E+09
Maximum of Months 0.105485E+10 0.628098E+09 0.205168E+10 0.00 0.00 0.00 0.00 13806997.98 0.119200E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.987754E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.195524E+10
February 0.136985E+10 0.843143E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.207924E+10
March 0.163685E+10 0.939014E+09 0.318369E+10 0.00 0.00 0.00 0.00 368921.16 0.127632E+10
April 0.145243E+10 0.808004E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.104237E+10
May 0.157338E+10 0.849529E+09 0.312174E+10 0.00 0.00 0.00 0.00 179864.81 0.648712E+09
June 0.156900E+10 0.835207E+09 0.306580E+10 0.00 0.00 0.00 0.00 10048048.58 0.383370E+09
July 0.145680E+10 0.785341E+09 0.300989E+10 0.00 0.00 0.00 0.00 25361866.31 0.231233E+09
August 0.163685E+10 0.886663E+09 0.318369E+10 0.00 0.00 0.00 0.00 19843013.67 0.260487E+09
September 0.145243E+10 0.826614E+09 0.295328E+10 0.00 0.00 0.00 0.00 1400729.60 0.372160E+09
October 0.150991E+10 0.907142E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.776666E+09
November 0.149516E+10 0.991643E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.104944E+10
December 0.145680E+10 0.991330E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.206125E+10
                   
Annual Sum or Average 0.181194E+11 0.106514E+11 0.363654E+11 0.00 0.00 0.00 0.00 57202444.14 0.121365E+11
Minimum of Months 0.136985E+10 0.785341E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.231233E+09
Maximum of Months 0.163685E+10 0.991643E+09 0.318369E+10 0.00 0.00 0.00 0.00 25361866.31 0.207924E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.627156E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.131064E+10
February 0.882782E+09 0.540145E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.139657E+10
March 0.105485E+10 0.603169E+09 0.205169E+10 0.00 0.00 0.00 0.00 245919.06 0.872910E+09
April 0.936002E+09 0.521153E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.723761E+09
May 0.101394E+10 0.550063E+09 0.201177E+10 0.00 0.00 0.00 0.00 119586.53 0.461303E+09
June 0.101113E+10 0.540932E+09 0.197572E+10 0.00 0.00 0.00 0.00 6608065.66 0.268271E+09
July 0.938820E+09 0.508364E+09 0.193969E+10 0.00 0.00 0.00 0.00 16460898.40 0.162303E+09
August 0.105485E+10 0.573488E+09 0.205169E+10 0.00 0.00 0.00 0.00 12523685.78 0.184528E+09
September 0.936002E+09 0.531643E+09 0.190321E+10 0.00 0.00 0.00 0.00 892415.86 0.264690E+09
October 0.973041E+09 0.578527E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.548529E+09
November 0.963541E+09 0.629709E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.713466E+09
December 0.938820E+09 0.628090E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.138031E+10
                   
Annual Sum or Average 0.116768E+11 0.683244E+10 0.234352E+11 0.00 0.00 0.00 0.00 36850571.29 0.828728E+10
Minimum of Months 0.882782E+09 0.508364E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.162303E+09
Maximum of Months 0.105485E+10 0.629709E+09 0.205169E+10 0.00 0.00 0.00 0.00 16460898.40 0.139657E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.956865E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.201597E+10
February 0.136988E+10 0.830551E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.212624E+10
March 0.163688E+10 0.933441E+09 0.318374E+10 0.00 0.00 0.00 0.00 367884.23 0.137674E+10
April 0.145246E+10 0.809513E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.110483E+10
May 0.157341E+10 0.854170E+09 0.312179E+10 0.00 0.00 0.00 0.00 179375.78 0.683378E+09
June 0.156904E+10 0.839430E+09 0.306585E+10 0.00 0.00 0.00 0.00 9940416.20 0.392450E+09
July 0.145684E+10 0.789593E+09 0.300994E+10 0.00 0.00 0.00 0.00 24693353.85 0.239982E+09
August 0.163688E+10 0.890078E+09 0.318374E+10 0.00 0.00 0.00 0.00 18252803.75 0.280059E+09
September 0.145246E+10 0.824986E+09 0.295333E+10 0.00 0.00 0.00 0.00 1250594.23 0.411003E+09
October 0.150994E+10 0.893172E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.873357E+09
November 0.149520E+10 0.963492E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.112387E+10
December 0.145684E+10 0.960104E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.212349E+10
                   
Annual Sum or Average 0.181198E+11 0.105454E+11 0.363660E+11 0.00 0.00 0.00 0.00 54684428.03 0.127514E+11
Minimum of Months 0.136988E+10 0.789593E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.239982E+09
Maximum of Months 0.163688E+10 0.963492E+09 0.318374E+10 0.00 0.00 0.00 0.00 24693353.85 0.212624E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.624751E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.132559E+10
February 0.882782E+09 0.538145E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.141831E+10
March 0.105485E+10 0.602988E+09 0.205168E+10 0.00 0.00 0.00 0.00 245943.64 0.917089E+09
April 0.936002E+09 0.520544E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.759984E+09
May 0.101394E+10 0.548047E+09 0.201175E+10 0.00 0.00 0.00 0.00 119589.37 0.478576E+09
June 0.101113E+10 0.538265E+09 0.197570E+10 0.00 0.00 0.00 0.00 6357840.13 0.284579E+09
July 0.938820E+09 0.506728E+09 0.193968E+10 0.00 0.00 0.00 0.00 16200917.29 0.177984E+09
August 0.105485E+10 0.571649E+09 0.205168E+10 0.00 0.00 0.00 0.00 12269301.82 0.201293E+09
September 0.936002E+09 0.532622E+09 0.190319E+10 0.00 0.00 0.00 0.00 836760.15 0.275167E+09
October 0.973041E+09 0.581466E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.566148E+09
November 0.963541E+09 0.628035E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.741606E+09
December 0.938820E+09 0.627580E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.140788E+10
                   
Annual Sum or Average 0.116768E+11 0.682082E+10 0.234351E+11 0.00 0.00 0.00 0.00 36030352.41 0.855421E+10
Minimum of Months 0.882782E+09 0.506728E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.177984E+09
Maximum of Months 0.105485E+10 0.628035E+09 0.205168E+10 0.00 0.00 0.00 0.00 16200917.29 0.141831E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.397259E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.360343E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.428189E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.382459E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.412724E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.410728E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.384455E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.428189E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.382459E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.397259E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.392603E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.384455E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.476112E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.360343E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.428189E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.167699E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.177144E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 164245.73 0.111675E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.906612E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 178953.62 0.512061E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6192520.75 0.289598E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16258688.86 0.167676E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13730113.89 0.196626E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 718848.85 0.306729E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.713995E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.988766E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.182873E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37243371.70 0.104760E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.167676E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16258688.86 0.182873E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.276375E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.293302E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 442242.58 0.189762E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.155233E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 513867.03 0.896985E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12713024.26 0.504366E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30411667.79 0.287811E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26116637.90 0.343956E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1331332.19 0.535905E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121833E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.164897E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.299530E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71528771.75 0.175783E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.287811E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30411667.79 0.299530E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.289046E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.307750E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34876.54 0.198484E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.165846E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35912.18 0.102919E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7198495.95 0.603208E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21571597.52 0.362237E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16039472.86 0.410774E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 681774.13 0.599410E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124713E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.164524E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.307953E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45562129.19 0.185880E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.362237E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21571597.52 0.307953E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 14744.03 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 14744.03 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 14744.03 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 14744.03 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 14744.03 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 14744.03 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 14744.03 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 14744.03 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 14744.03 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 14744.03 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 14744.03 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 14744.03 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1662.56 02-JAN-16:49 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 1381.28 12-JAN-02:00
February 2010.79 01-FEB-10:09 1441.39 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1420.16 13-FEB-05:52
March 2010.79 01-MAR-10:09 1158.25 17-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 10.95 15-MAR-14:00 890.67 02-MAR-01:00
April 2010.79 03-APR-09:09 919.49 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 855.72 16-APR-02:00
May 2010.79 01-MAY-09:09 868.10 11-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 8.58 14-MAY-15:00 472.98 29-MAY-14:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 56.19 17-JUN-17:02 425.59 13-JUN-03:00
July 2010.79 03-JUL-09:09 854.52 11-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 94.96 21-JUL-03:06 303.90 06-JUL-02:00
August 2010.79 01-AUG-09:09 867.08 24-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 119.01 13-AUG-13:05 192.18 30-AUG-21:10
September 2010.79 01-SEP-09:09 1108.99 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 21.87 16-SEP-13:00 359.54 29-SEP-04:00
October 2010.79 02-OCT-09:09 1599.74 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 477.74 08-OCT-09:00
November 2010.79 01-NOV-09:09 1662.56 06-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 841.30 17-NOV-02:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:40 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1361.68 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   192.18  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 119.01   1420.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:49 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 910.93 12-JAN-05:54
February 1295.83 01-FEB-10:09 937.96 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 946.77 13-FEB-05:56
March 1295.83 01-MAR-10:09 595.23 01-MAR-17:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 7.30 15-MAR-14:00 598.81 26-MAR-10:00
April 1295.83 03-APR-09:09 571.78 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 556.38 16-APR-02:00
May 1295.83 01-MAY-09:09 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 5.60 10-MAY-14:00 333.80 29-MAY-14:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 39.04 17-JUN-17:02 283.67 13-JUN-03:00
July 1295.83 03-JUL-09:09 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 63.39 21-JUL-02:50 195.35 06-JUL-02:00
August 1295.83 01-AUG-09:09 552.00 28-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 91.16 13-AUG-13:05 123.95 30-AUG-21:10
September 1295.83 01-SEP-09:09 588.53 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 14.58 16-SEP-13:00 234.86 29-SEP-04:00
October 1295.83 02-OCT-09:09 852.94 26-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 327.69 08-OCT-09:00
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 546.12 17-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:40 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 893.08 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   123.95  
Maximum of Months 1295.83   1071.42   1392.34   0.00 0.00 0.00 0.00 91.16   946.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1662.60 02-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 1366.38 12-JAN-05:54
February 2010.83 01-FEB-10:09 1406.83 01-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1420.16 13-FEB-05:54
March 2010.83 01-MAR-10:09 1120.64 17-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 10.82 15-MAR-14:00 922.54 02-MAR-01:00
April 2010.83 03-APR-09:09 918.02 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 816.13 16-APR-02:00
May 2010.83 01-MAY-09:09 872.62 11-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 8.40 10-MAY-14:00 504.68 29-MAY-14:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 56.40 17-JUN-17:02 423.86 13-JUN-03:00
July 2010.83 03-JUL-09:09 859.72 11-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 95.05 21-JUL-03:06 301.93 06-JUL-02:00
August 2010.83 01-AUG-09:09 870.20 24-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 122.08 13-AUG-13:05 191.77 30-AUG-21:10
September 2010.83 01-SEP-09:09 1080.68 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 21.87 16-SEP-13:00 349.84 29-SEP-04:00
October 2010.83 02-OCT-09:09 1398.09 30-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 473.73 08-OCT-09:00
November 2010.83 01-NOV-09:09 1662.60 06-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 826.44 17-NOV-02:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:40 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1347.71 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   191.77  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 122.08   1420.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 955.82 12-JAN-02:00
February 1295.83 01-FEB-10:09 924.55 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 951.83 13-FEB-03:52
March 1295.83 01-MAR-10:09 791.13 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 7.30 15-MAR-14:00 666.38 02-MAR-01:00
April 1295.83 03-APR-09:09 600.05 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 627.64 16-APR-02:00
May 1295.83 01-MAY-09:09 574.40 11-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 5.60 10-MAY-14:00 372.66 29-MAY-15:20
June 1295.83 01-JUN-09:09 547.64 21-JUN-08:09 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 32.62 12-JUN-13:00 304.83 13-JUN-03:00
July 1295.83 03-JUL-09:09 567.65 11-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 65.31 21-JUL-03:06 239.77 06-JUL-02:00
August 1295.83 01-AUG-09:09 578.15 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 79.18 13-AUG-13:03 168.86 27-AUG-16:40
September 1295.83 01-SEP-09:09 759.61 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 14.58 16-SEP-13:00 255.15 29-SEP-04:00
October 1295.83 02-OCT-09:09 1030.67 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 344.94 08-OCT-09:00
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 616.17 17-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:40 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 988.27 09-DEC-18:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   547.64   1392.33   0.00 0.00 0.00 0.00 0.00   168.86  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 79.18   988.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1662.56 02-JAN-16:49 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 3198.29 12-JAN-05:47
February 2010.79 01-FEB-10:09 1438.89 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3171.01 13-FEB-05:50
March 2010.79 01-MAR-10:09 1152.32 17-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 24.35 15-MAR-14:00 1840.74 02-MAR-05:10
April 2010.79 03-APR-09:09 913.64 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1712.21 16-APR-02:00
May 2010.79 01-MAY-09:09 859.33 11-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 40.21 14-MAY-15:00 1061.62 29-MAY-14:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 144.16 17-JUN-17:02 904.15 13-JUN-03:00
July 2010.79 03-JUL-09:09 844.92 11-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 212.33 21-JUL-03:10 656.57 06-JUL-02:00
August 2010.79 01-AUG-09:09 858.30 24-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 287.75 13-AUG-12:52 423.20 30-AUG-21:10
September 2010.79 01-SEP-09:09 1102.39 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 55.38 16-SEP-17:02 757.15 29-SEP-04:00
October 2010.79 02-OCT-09:09 1598.83 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 961.61 08-OCT-09:00
November 2010.79 01-NOV-09:09 1662.56 06-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1703.89 17-NOV-02:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:40 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2928.31 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   423.20  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 287.75   3198.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1071.42 02-JAN-16:49 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2132.19 12-JAN-05:47
February 1239.33 01-FEB-08:09 934.52 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2198.95 13-FEB-05:51
March 1239.33 01-MAR-08:09 595.23 01-MAR-17:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 14.70 15-MAR-14:10 1239.73 26-MAR-10:00
April 1239.33 03-APR-07:10 567.65 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1151.65 16-APR-06:55
May 1239.33 01-MAY-07:10 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 12.45 10-MAY-14:30 805.94 29-MAY-14:00
June 1239.33 01-JUN-07:10 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 91.90 17-JUN-17:02 613.55 13-JUN-03:00
July 1239.33 03-JUL-07:10 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 152.98 21-JUL-03:06 440.11 06-JUL-02:00
August 1239.33 01-AUG-07:10 546.03 28-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 176.31 13-AUG-13:15 282.72 30-AUG-21:10
September 1239.33 01-SEP-07:10 585.18 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 33.03 16-SEP-13:00 502.57 29-SEP-04:00
October 1239.33 02-OCT-07:10 848.25 26-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 680.16 08-OCT-09:00
November 1239.33 01-NOV-07:10 1071.42 06-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1141.66 17-NOV-02:00
December 1239.33 01-DEC-08:09 1071.42 01-DEC-16:40 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1943.66 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   282.72  
Maximum of Months 1239.33   1071.42   1392.34   0.00 0.00 0.00 0.00 176.31   2198.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1662.60 02-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 3198.30 12-JAN-05:42
February 2010.83 01-FEB-10:09 1404.29 01-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3299.57 13-FEB-05:51
March 2010.83 01-MAR-10:09 1114.53 17-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 24.17 15-MAR-14:00 2137.25 26-MAR-13:00
April 2010.83 03-APR-09:09 912.10 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1720.91 16-APR-02:00
May 2010.83 01-MAY-09:09 864.06 11-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 18.68 10-MAY-14:00 1197.14 29-MAY-14:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 141.74 17-JUN-17:02 917.01 13-JUN-03:00
July 2010.83 03-JUL-09:09 850.38 11-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 229.62 21-JUL-03:06 661.78 06-JUL-02:00
August 2010.83 01-AUG-09:09 861.57 24-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 260.27 13-AUG-12:52 427.01 20-AUG-15:00
September 2010.83 01-SEP-09:09 1073.88 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 49.54 16-SEP-13:05 763.58 29-SEP-04:00
October 2010.83 02-OCT-09:09 1392.44 30-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1028.19 08-OCT-09:00
November 2010.83 01-NOV-09:09 1662.60 06-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1752.81 17-NOV-02:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:40 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2974.59 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   427.01  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 260.27   3299.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2132.19 12-JAN-05:47
February 1295.83 01-FEB-10:09 920.76 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2202.14 13-FEB-05:51
March 1295.83 01-MAR-10:09 783.78 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 16.23 15-MAR-14:00 1371.04 25-MAR-17:04
April 1295.83 03-APR-09:09 596.81 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1166.72 16-APR-02:00
May 1295.83 01-MAY-09:09 569.72 11-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 12.45 10-MAY-14:00 827.25 29-MAY-15:10
June 1295.83 01-JUN-09:09 541.12 21-JUN-08:09 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 74.95 12-JUN-13:00 628.39 13-JUN-03:00
July 1295.83 03-JUL-09:09 562.57 11-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 154.60 21-JUL-03:06 465.21 06-JUL-02:00
August 1295.83 01-AUG-09:09 573.68 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 176.77 13-AUG-13:15 368.49 27-AUG-16:30
September 1295.83 01-SEP-09:09 751.42 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 33.03 16-SEP-13:00 509.70 29-SEP-04:00
October 1295.83 02-OCT-09:09 1030.09 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 665.43 08-OCT-09:00
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1166.92 17-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:40 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1995.64 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   541.12   1392.33   0.00 0.00 0.00 0.00 0.00   368.49  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 176.77   2202.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1662.56 02-JAN-16:49 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 3933.68 12-JAN-06:00
February 2010.79 01-FEB-10:09 1438.45 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3731.81 13-FEB-05:50
March 2010.79 01-MAR-10:09 1151.35 17-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 28.58 15-MAR-14:00 2298.58 02-MAR-05:09
April 2010.79 03-APR-09:09 913.40 12-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1878.96 04-APR-21:03
May 2010.79 01-MAY-09:09 858.97 11-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 21.92 10-MAY-14:00 1300.73 29-MAY-14:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 158.85 17-JUN-17:02 1102.28 13-JUN-03:00
July 2010.79 03-JUL-09:09 844.54 11-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 246.59 21-JUL-03:08 788.03 06-JUL-02:00
August 2010.79 01-AUG-09:09 857.94 24-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 370.33 13-AUG-12:55 515.20 30-AUG-21:10
September 2010.79 01-SEP-09:09 1101.30 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 59.35 16-SEP-13:00 836.78 29-SEP-04:00
October 2010.79 02-OCT-09:09 1598.80 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1035.82 30-OCT-04:52
November 2010.79 01-NOV-09:09 1662.56 06-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1979.55 17-NOV-06:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:40 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3510.45 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   515.20  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 370.33   3933.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:49 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2673.96 12-JAN-05:54
February 1295.83 01-FEB-10:09 934.25 01-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2735.60 13-FEB-05:50
March 1295.83 01-MAR-10:09 595.23 01-MAR-17:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 19.05 15-MAR-14:00 1542.45 02-MAR-05:04
April 1295.83 03-APR-09:09 567.46 12-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1252.58 04-APR-21:03
May 1295.83 01-MAY-09:09 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 14.61 10-MAY-14:00 996.32 29-MAY-13:53
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 102.31 17-JUN-17:02 748.00 13-JUN-03:00
July 1295.83 03-JUL-09:09 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 179.42 21-JUL-03:06 527.49 06-JUL-02:00
August 1295.83 01-AUG-09:09 545.79 28-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 267.18 13-AUG-12:55 343.45 30-AUG-21:10
September 1295.83 01-SEP-09:09 585.01 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 39.57 16-SEP-13:00 554.95 29-SEP-04:00
October 1295.83 02-OCT-09:09 847.86 26-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 709.85 08-OCT-09:00
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1319.69 17-NOV-06:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:40 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2338.23 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   343.45  
Maximum of Months 1295.83   1071.42   1392.34   0.00 0.00 0.00 0.00 267.18   2735.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1662.60 02-JAN-16:49 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 4010.77 12-JAN-05:56
February 2010.83 01-FEB-10:09 1403.80 01-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4034.23 13-FEB-05:50
March 2010.83 01-MAR-10:09 1113.50 17-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 28.30 15-MAR-14:00 2423.65 26-MAR-13:00
April 2010.83 03-APR-09:09 911.86 12-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1879.27 04-APR-21:03
May 2010.83 01-MAY-09:09 863.71 11-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 21.92 10-MAY-14:00 1466.19 29-MAY-14:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 156.03 17-JUN-17:02 1118.13 13-JUN-03:00
July 2010.83 03-JUL-09:09 850.01 11-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 269.59 21-JUL-03:06 794.17 06-JUL-02:00
August 2010.83 01-AUG-09:09 861.22 24-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 338.13 13-AUG-12:55 525.52 20-AUG-15:20
September 2010.83 01-SEP-09:09 1072.74 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 59.35 16-SEP-13:00 847.54 29-SEP-04:00
October 2010.83 02-OCT-09:09 1392.40 30-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1146.56 09-OCT-11:48
November 2010.83 01-NOV-09:09 1662.60 06-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2006.38 17-NOV-02:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:40 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3558.14 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   525.52  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 338.13   4034.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1071.42 02-JAN-16:49 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2673.91 12-JAN-06:00
February 1295.83 01-FEB-10:09 920.46 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2735.42 13-FEB-05:50
March 1295.83 01-MAR-10:09 783.22 17-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 19.05 15-MAR-14:00 1709.69 25-MAR-17:10
April 1295.83 03-APR-09:09 596.68 12-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1283.35 16-APR-02:00
May 1295.83 01-MAY-09:09 569.53 11-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 14.61 10-MAY-14:00 1027.46 29-MAY-15:10
June 1295.83 01-JUN-09:09 540.92 21-JUN-08:09 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 91.14 12-JUN-13:00 766.26 13-JUN-03:00
July 1295.83 03-JUL-09:09 562.37 11-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 180.70 21-JUL-03:06 560.08 06-JUL-02:00
August 1295.83 01-AUG-09:09 573.51 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 273.62 13-AUG-12:55 470.74 27-AUG-16:50
September 1295.83 01-SEP-09:09 750.79 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 39.57 16-SEP-13:00 572.44 29-SEP-04:00
October 1295.83 02-OCT-09:09 1030.07 31-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 716.79 08-OCT-09:00
November 1295.83 01-NOV-09:09 1071.42 06-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1343.27 17-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:40 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2400.91 09-DEC-18:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   540.92   1392.33   0.00 0.00 0.00 0.00 0.00   470.74  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 273.62   2735.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4157.19 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4157.19 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4157.19 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4157.19 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4157.19 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4157.19 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4157.19 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4157.19 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4157.19 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4157.19 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4157.19 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4157.19 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4157.19   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4157.19   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 2990.88 12-JAN-02:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3031.71 13-FEB-05:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.79 15-MAR-14:00 1960.90 02-MAR-01:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1842.21 16-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.88 14-MAY-15:00 878.40 29-MAY-13:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.49 17-JUN-17:02 869.92 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 171.96 21-JUL-02:53 628.11 06-JUL-02:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 282.07 13-AUG-12:53 394.00 30-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.71 16-SEP-13:00 771.56 29-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 999.36 08-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1794.25 17-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2954.68 09-DEC-18:03
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   394.00  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 282.07   3031.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 4983.47 12-JAN-05:52
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4947.69 13-FEB-05:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.63 15-MAR-14:00 3245.87 02-MAR-01:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3118.25 16-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 110.71 14-MAY-15:00 1502.98 29-MAY-14:40
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 253.70 17-JUN-17:02 1505.18 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 319.38 21-JUL-02:53 1097.02 06-JUL-02:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 544.67 13-AUG-13:00 703.65 30-AUG-21:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.30 16-SEP-17:02 1354.26 29-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1708.11 08-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3044.40 17-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4966.16 09-DEC-18:03
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   703.65  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 544.67   4983.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 5393.64 12-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 5285.02 13-FEB-05:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.53 15-MAR-14:00 3297.12 02-MAR-01:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2966.94 16-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.51 10-MAY-15:00 2066.32 29-MAY-14:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 204.62 17-JUN-17:02 1706.02 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 305.20 21-JUL-02:00 1204.70 06-JUL-02:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 345.29 13-AUG-13:10 790.02 30-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.47 16-SEP-13:00 1345.39 29-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1595.41 08-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3147.96 17-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5501.45 09-DEC-18:03
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   790.02  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 345.29   5501.45  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95466.94 02-JAN-07:03 10771.35 14744.03 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
February 95269.64 21-FEB-07:03 14361.80 19658.71 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
March 94908.78 16-MAR-06:12 21542.70 29488.07 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
April 97142.47 24-APR-06:03 10771.35 14744.03 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
May 100437.07 30-MAY-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
June 103603.03 13-JUN-06:05 7180.90 9829.36 26915.09 0.00 0.00 0.00 0.00 0.00 0.00
July 106495.86 12-JUL-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
August 109450.30 09-AUG-06:11 32314.05 44232.10 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
September 108406.19 18-SEP-06:11 35904.50 49146.78 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
October 105165.75 10-OCT-06:11 35904.50 49146.78 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
November 98739.53 13-NOV-07:05 7180.90 9829.36 26915.09 0.00 0.00 0.00 0.00 0.00 0.00
December 98729.88 26-DEC-07:03 14361.80 19658.71 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 94908.78   7180.90 9829.36 26915.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 109450.30   35904.50 49146.78 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 74601.69 17-JAN-06:01 12897.91 4298.88 61179.12 0.00 0.00 0.00 0.00 0.00 0.00
February 76431.62 24-FEB-06:02 12897.91 4298.88 61179.12 0.00 0.00 0.00 0.00 0.00 0.00
March 80819.06 15-MAR-04:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
April 86045.33 10-APR-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
May 88340.68 30-MAY-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 91565.91 28-JUN-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 88999.17 12-JUL-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
August 84482.61 31-AUG-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
September 89448.97 05-SEP-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 85853.16 23-OCT-04:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
November 86960.57 13-NOV-05:11 0.00 5373.60 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
December 80588.25 18-DEC-05:01 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 74601.69   0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 91565.91   12897.91 5373.60 61179.12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19194.39 25-JAN-11:10 76581.32 66205.89 86032.81 0.00 0.00 0.00 0.00 0.00 0.00
February 19084.65 03-FEB-09:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 73671.05 17-MAR-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 70875.89 27-APR-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
May 76302.41 30-MAY-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 76161.75 29-JUN-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
July 77139.98 25-JUL-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
August 76597.13 01-AUG-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
September 78339.64 18-SEP-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 74368.67 13-OCT-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 68453.56 01-NOV-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 23641.53 01-DEC-17:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 19084.65   0.00 2149.44 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 78339.64   76581.32 66205.89 86032.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 14300.52 12-JAN-17:00 30632.53 26482.36 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
February 14845.84 28-FEB-14:10 32029.16 26482.36 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
March 71641.12 16-MAR-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 35983.03 21-APR-16:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 70725.03 17-MAY-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 75064.15 19-JUN-04:12 0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
July 76635.19 22-JUL-05:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
August 74842.92 01-AUG-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
September 74871.31 18-SEP-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 67473.44 13-OCT-05:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 23577.45 01-NOV-16:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 15211.66 01-DEC-17:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 14300.52   0.00 2149.44 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 76635.19   32029.16 26482.36 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2193.99 17-JAN-06:02 1619.46 539.77 7681.96 0.00 0.00 0.00 0.00 0.00 53.96
February 2093.73 23-FEB-06:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 126.21
March 7631.35 15-MAR-14:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 10.95 0.00
April 6878.56 07-APR-13:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 24.61
May 8733.79 17-MAY-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 23.85
June 15780.79 11-JUN-18:41 0.00 395.49 5032.54 0.00 0.00 0.00 0.00 0.00 49.76
July 16112.57 16-JUL-16:22 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 36.85 0.00
August 15622.46 06-AUG-16:21 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 10.49 0.00
September 11642.57 15-SEP-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 11.28
October 6362.21 23-OCT-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 38.91
November 4692.97 27-NOV-12:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 77.45
December 2753.88 01-DEC-13:10 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 97.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2093.73   0.00 269.88 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16112.57   2010.79 791.05 7681.96 0.00 0.00 0.00 0.00 36.85 126.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1764.99 12-JAN-10:05 2591.66 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 265.21
February 6143.57 28-FEB-09:35 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 58.33
March 9201.90 21-MAR-08:55 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 45.59
April 16101.26 23-APR-10:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 145.30
May 18246.37 07-MAY-07:33 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 116.66
June 23682.58 11-JUN-08:41 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 101.44
July 24818.55 04-JUL-07:51 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 0.00 112.61
August 21814.50 06-AUG-09:01 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 46.12
September 22114.95 10-SEP-08:12 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 77.51
October 11049.97 11-OCT-08:50 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 16.32
November 6576.78 03-NOV-08:55 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 80.90
December 3619.18 04-DEC-09:50 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 113.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1764.99   260.91 113.28 1392.34 0.00 0.00 0.00 0.00 0.00 16.32
Maximum of Months 24818.55   2591.66 1019.56 3712.91 0.00 0.00 0.00 0.00 0.00 265.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 24096.96 15-JAN-13:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 457.17
February 17297.88 28-FEB-13:20 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 130.51
March 19020.78 15-MAR-13:30 2010.83 791.06 2160.58 0.00 0.00 0.00 0.00 8.70 0.00
April 20694.66 23-APR-14:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 165.81
May 24643.34 14-MAY-13:13 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 83.54
June 24329.45 25-JUN-13:02 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 15.26
July 25284.44 16-JUL-15:41 910.97 395.50 6481.75 0.00 0.00 0.00 0.00 37.51 0.00
August 26085.88 27-AUG-13:22 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 104.60
September 27594.25 10-SEP-12:11 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 163.87
October 24692.50 22-OCT-12:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 156.59
November 18246.11 03-NOV-12:30 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 70.36
December 16985.61 17-DEC-11:33 303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 750.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16985.61   303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27594.25   2010.83 791.06 6481.75 0.00 0.00 0.00 0.00 37.51 750.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4698.28 12-JAN-15:40 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 192.45
February 9567.37 28-FEB-16:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 80.98
March 19058.94 26-MAR-16:22 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 442.79
April 27168.38 02-APR-16:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 318.03
May 30065.42 07-MAY-16:11 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 0.00 146.32
June 31453.37 11-JUN-16:41 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 65.78
July 31342.55 16-JUL-16:21 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 12.65
August 31309.21 06-AUG-16:21 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 29.57
September 28565.40 10-SEP-17:31 0.00 198.23 2522.44 0.00 0.00 0.00 0.00 0.00 98.81
October 17785.31 09-OCT-16:33 260.91 113.28 1856.44 0.00 0.00 0.00 0.00 0.00 208.92
November 15422.75 27-NOV-05:12 0.00 217.40 2402.32 0.00 0.00 0.00 0.00 0.00 143.07
December 9006.41 14-DEC-06:02 652.28 217.40 3094.07 0.00 0.00 0.00 0.00 0.00 32.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4698.28   0.00 113.28 1392.33 0.00 0.00 0.00 0.00 0.00 12.65
Maximum of Months 31453.37   1239.33 509.78 4641.11 0.00 0.00 0.00 0.00 0.00 442.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1372.35 11-JAN-17:00 1923.11 1662.56 2160.55 0.00 0.00 0.00 0.00 0.00 239.45
February 1413.87 17-FEB-15:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 206.10
March 5998.96 15-MAR-14:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 24.35 0.00
April 4588.61 07-APR-13:50 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 67.19
May 7075.61 23-MAY-14:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 3.14
June 13443.28 11-JUN-18:41 0.00 395.49 5032.54 0.00 0.00 0.00 0.00 0.00 106.02
July 13972.79 16-JUL-16:31 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 64.84 0.00
August 10340.83 11-AUG-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 39.03
September 7604.32 14-SEP-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 24.83
October 4215.76 12-OCT-14:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 109.74
November 2241.39 07-NOV-10:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 223.09
December 1635.70 01-DEC-13:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 273.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1372.35   0.00 269.88 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13972.79   2010.79 1662.56 5041.29 0.00 0.00 0.00 0.00 64.84 273.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1379.93 06-JAN-09:55 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 144.38
February 4094.80 28-FEB-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 171.58
March 8820.38 21-MAR-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 151.71
April 17112.54 23-APR-10:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 344.10
May 18423.83 21-MAY-09:12 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 463.70
June 25602.51 11-JUN-10:01 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 178.85
July 24752.49 09-JUL-08:12 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 37.28
August 23258.94 20-AUG-09:42 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 190.23
September 21265.43 04-SEP-09:02 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 186.49
October 10814.20 11-OCT-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 27.49
November 5985.88 03-NOV-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 148.63
December 1123.55 01-DEC-13:10 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 137.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1123.55   260.91 113.28 1392.34 0.00 0.00 0.00 0.00 0.00 27.49
Maximum of Months 25602.51   2478.65 1019.56 3248.80 0.00 0.00 0.00 0.00 0.00 463.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17399.86 15-JAN-13:23 303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 1093.61
February 18210.59 28-FEB-13:40 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 315.12
March 19323.81 01-MAR-13:50 3846.30 1582.13 4321.17 0.00 0.00 0.00 0.00 0.00 556.11
April 21962.05 23-APR-14:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 392.37
May 24723.18 14-MAY-13:23 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 197.31
June 24232.81 11-JUN-15:21 910.97 395.50 6481.75 0.00 0.00 0.00 0.00 0.00 98.45
July 24941.68 30-JUL-12:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 92.86
August 25474.50 27-AUG-12:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 264.53
September 26875.01 03-SEP-12:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 270.99
October 24653.79 22-OCT-13:02 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 382.55
November 19280.53 03-NOV-12:30 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 166.25
December 12762.79 04-DEC-11:50 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 417.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12762.79   303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 92.86
Maximum of Months 26875.01   3846.30 1582.13 6481.75 0.00 0.00 0.00 0.00 0.00 1093.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1614.76 12-JAN-15:50 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 450.94
February 6135.30 28-FEB-16:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 190.78
March 9137.18 21-MAR-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 174.18
April 24082.70 02-APR-16:11 587.05 254.87 4177.00 0.00 0.00 0.00 0.00 0.00 738.59
May 25120.69 07-MAY-16:32 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 323.66
June 28912.02 11-JUN-16:41 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 157.32
July 30376.78 02-JUL-17:01 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 0.00 171.85
August 26139.43 27-AUG-16:31 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 0.00 258.92
September 24839.14 04-SEP-17:02 0.00 169.91 2162.09 0.00 0.00 0.00 0.00 0.00 217.28
October 11945.32 11-OCT-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 6.23
November 5256.25 15-NOV-15:20 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 88.18
December 2063.44 04-DEC-15:50 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 181.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1614.76   0.00 169.91 1392.33 0.00 0.00 0.00 0.00 0.00 6.23
Maximum of Months 30376.78   1239.33 509.78 4641.11 0.00 0.00 0.00 0.00 0.00 738.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1204.97 07-JAN-17:02 506.08 461.79 3600.92 0.00 0.00 0.00 0.00 0.00 776.36
February 1313.41 22-FEB-16:50 1923.11 850.46 2160.55 0.00 0.00 0.00 0.00 0.00 261.06
March 6437.12 15-MAR-14:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 20.90 0.00
April 4297.17 20-APR-15:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 101.84
May 7314.80 23-MAY-14:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 5.94
June 11795.70 18-JUN-11:43 404.87 175.78 2880.74 0.00 0.00 0.00 0.00 0.00 86.38
July 16614.75 02-JUL-18:21 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 0.00 133.42
August 16267.50 13-AUG-15:31 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 218.74 0.00
September 7282.64 15-SEP-14:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 9.76 0.00
October 4082.56 12-OCT-15:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 141.09
November 1832.39 16-NOV-17:00 1923.11 1662.56 2160.55 0.00 0.00 0.00 0.00 0.00 89.25
December 1386.39 01-DEC-13:40 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 364.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1204.97   0.00 175.78 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16614.75   2010.79 1662.56 7201.84 0.00 0.00 0.00 0.00 218.74 776.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 906.01 20-JAN-06:04 913.19 304.37 4331.73 0.00 0.00 0.00 0.00 0.00 281.47
February 1691.94 28-FEB-10:05 2591.66 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 176.57
March 6143.01 15-MAR-09:30 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 23.85
April 11752.89 23-APR-10:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 427.74
May 16595.04 21-MAY-10:53 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 566.84
June 23380.60 11-JUN-09:32 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 174.82
July 24829.26 04-JUL-09:22 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 181.03
August 21194.35 06-AUG-09:12 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 121.88
September 23292.14 10-SEP-10:02 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 330.03
October 8286.01 11-OCT-09:30 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 40.71
November 2379.07 03-NOV-09:20 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 220.39
December 912.61 13-DEC-06:04 913.19 304.37 4331.73 0.00 0.00 0.00 0.00 0.00 174.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 906.01   260.91 113.28 1392.34 0.00 0.00 0.00 0.00 0.00 23.85
Maximum of Months 24829.26   2591.66 1019.56 4331.73 0.00 0.00 0.00 0.00 0.00 566.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12506.53 12-JAN-13:40 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 930.41
February 16917.51 28-FEB-13:40 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 393.04
March 19161.43 15-MAR-13:30 2010.83 791.06 2160.58 0.00 0.00 0.00 0.00 21.77 0.00
April 19071.43 23-APR-14:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 490.43
May 27034.74 14-MAY-13:42 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 238.37
June 26109.99 25-JUN-13:02 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 56.67
July 26866.37 30-JUL-12:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 123.10
August 27690.40 13-AUG-12:52 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 173.18 0.00
September 30069.93 10-SEP-12:41 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 516.45
October 23401.03 22-OCT-14:02 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 476.66
November 17065.84 03-NOV-12:40 1923.15 791.06 2160.58 0.00 0.00 0.00 0.00 0.00 202.01
December 10211.40 16-DEC-13:30 202.44 131.84 840.23 0.00 0.00 0.00 0.00 0.00 163.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10211.40   202.44 131.84 840.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30069.93   2010.83 791.06 5041.36 0.00 0.00 0.00 0.00 173.18 930.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1240.72 12-JAN-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 551.01
February 5790.24 28-FEB-16:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 237.95
March 8492.86 21-MAR-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 217.46
April 18170.84 02-APR-16:11 587.05 254.87 4177.00 0.00 0.00 0.00 0.00 0.00 912.57
May 28528.34 07-MAY-17:41 0.00 226.55 2882.79 0.00 0.00 0.00 0.00 0.00 443.21
June 27778.09 11-JUN-16:51 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 116.60
July 31908.73 02-JUL-17:01 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 0.00 223.89
August 27334.99 13-AUG-15:31 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 62.86 0.00
September 27796.25 10-SEP-16:01 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 285.28
October 11895.48 11-OCT-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 8.08
November 4300.60 15-NOV-15:20 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 110.44
December 1261.55 04-DEC-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 210.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1240.72   0.00 198.23 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31908.73   1239.33 509.78 4641.11 0.00 0.00 0.00 0.00 62.86 912.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5987.37 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.40
February 7857.63 06-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2034.53
March 5182.22 15-MAR-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.82 0.00
April 6819.18 10-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.81
May 8263.10 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82.81
June 11145.22 28-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.11
July 12845.41 24-JUL-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.20
August 11277.43 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.66
September 9469.96 18-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.67
October 6728.57 23-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.50
November 5303.58 06-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 152.74
December 4126.10 11-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 471.47
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4126.10   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12845.41   0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.82 2034.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9275.03 24-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3533.52
February 10261.78 21-FEB-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3748.56
March 9326.32 04-MAR-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1238.02
April 5250.72 17-APR-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.65
May 4532.71 30-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 152.42
June 6272.22 21-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.66
July 7335.10 22-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.76
August 7220.90 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.90
September 6081.97 18-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.79
October 6007.82 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 346.10
November 7898.18 24-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 770.66
December 8691.14 27-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3099.84
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4532.71   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.65
Maximum of Months 10261.78   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3748.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 975.29
February 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1442.78
March 11293.19 15-MAR-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.98 0.00
April 9464.76 21-APR-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 283.26
May 13803.20 31-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.88
June 18465.07 12-JUN-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.13 0.00
July 18103.35 21-JUL-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.89 0.00
August 17722.85 09-AUG-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.76 0.00
September 13464.76 21-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.53 0.00
October 7606.42 11-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.49
November 990.12 04-NOV-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.76
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1236.76
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18465.07   0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.13 1442.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1949.33 12-JAN-16:40 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4162.10 28-FEB-17:00 222.14 316.63 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7000.82 31-MAR-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8202.92 02-APR-17:55 0.00 35.18 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3473.67 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5391.38 30-JUN-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7288.10 31-JUL-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8244.54 02-AUG-18:40 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3239.89 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5165.97 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5848.98 24-NOV-16:20 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7739.65 04-DEC-16:20 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1949.33   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8244.54   222.14 316.63 15588.84 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1573.33 12-JAN-16:50 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3665.92 28-FEB-17:00 222.14 316.63 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6263.13 31-MAR-23:40 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7686.50 24-APR-18:00 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3284.75 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5137.03 30-JUN-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6998.38 31-JUL-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7912.00 02-AUG-18:40 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2786.09 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4553.12 31-OCT-23:40 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5396.34 15-NOV-16:20 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6976.12 04-DEC-16:30 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1573.33   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7912.00   222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1343.83 12-JAN-16:40 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3601.06 28-FEB-17:00 222.14 316.63 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5828.53 31-MAR-23:20 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7678.97 24-APR-18:00 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3186.87 31-MAY-23:40 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5062.17 30-JUN-23:40 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6982.71 31-JUL-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7965.22 02-AUG-18:40 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2498.60 04-SEP-17:48 0.00 87.96 9743.03 0.00 0.00 0.00 0.00 0.00 0.00
October 4141.12 31-OCT-23:20 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5264.94 15-NOV-16:30 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6620.59 04-DEC-16:30 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1343.83   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7965.22   222.14 316.63 9743.03 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 90431.45 18-JAN-17:00 4808.68 4157.19 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 182056.92 23-FEB-17:00 4808.68 4157.19 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357897.66 31-MAR-24:00 0.00 230.94 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 366736.29 24-APR-16:00 4808.68 4157.19 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175662.99 31-MAY-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267991.02 30-JUN-24:00 0.00 230.94 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 360089.58 31-JUL-24:00 0.00 230.94 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
August 378592.97 15-AUG-16:41 12148.24 18476.25 3037060.17 0.00 0.00 0.00 0.00 0.00 0.00
September 175484.92 30-SEP-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268099.09 31-OCT-24:00 0.00 230.94 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 275752.75 06-NOV-17:00 4808.68 4157.19 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 366624.61 04-DEC-16:55 9617.36 8314.37 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 90431.45   0.00 230.94 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 378592.97   12148.24 18476.25 3037060.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.159402E+13 1142228.99 13-JAN-16:00 0.379344E+12 1582955.37 02-JAN-05:10
February 0.182033E+13 1255375.17 28-FEB-16:10 0.293776E+12 1206922.70 06-FEB-06:10
March 0.239966E+13 1675183.36 15-MAR-14:30 0.952545E+11 701868.43 06-MAR-05:10
April 0.261452E+13 1694241.92 07-APR-14:09 0.181631E+11 537210.15 11-APR-13:30
May 0.165195E+13 1459249.92 23-MAY-14:20 0.173625E+10 376726.55 11-MAY-13:20
June 0.213332E+13 1692698.58 27-JUN-07:40 0.247228E+09 175273.88 13-JUN-11:09
July 0.273082E+13 2011554.08 05-JUL-15:50 3086.16 5.14 02-JUL-22:00
August 0.310373E+13 2111016.45 15-AUG-14:39 3144979.35 5240.98 31-AUG-11:09
September 0.160754E+13 1502027.89 15-SEP-10:30 0.517143E+09 149085.79 28-SEP-09:00
October 0.193825E+13 1381849.13 11-OCT-15:00 0.148571E+11 405146.88 30-OCT-05:10
November 0.230214E+13 1471053.35 15-NOV-16:49 0.561611E+11 614642.23 24-NOV-05:10
December 0.270260E+13 1561779.38 18-DEC-16:40 0.291000E+12 1210366.87 11-DEC-06:10
             
Annual Sum or Average 0.265989E+14     0.115106E+13    
Minimum of Months 0.159402E+13 1142228.99   3086.16 5.14  
Maximum of Months 0.310373E+13 2111016.45   0.379344E+12 1582955.37  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.208761E+12 0.418459E+11 0.766053E+12 0.213316E+12 0.161985E+12 0.113320E+11 0.00 0.672433E+10 0.357029E+09 0.135489E+12 0.579087E+10 0.423658E+11 0.00
February 0.187603E+12 0.331640E+11 0.978954E+12 0.195308E+12 0.146445E+12 0.105466E+11 0.00 0.199553E+11 0.106205E+10 0.203006E+12 0.525097E+10 0.390359E+11 0.00
March 0.220884E+12 0.306117E+11 0.141687E+13 0.226028E+12 0.173457E+12 0.191459E+11 0.00 0.529230E+11 0.906699E+10 0.200431E+12 0.495231E+10 0.452818E+11 0.00
April 0.195941E+12 0.239964E+11 0.165903E+13 0.211475E+12 0.181207E+12 0.206688E+11 0.00 0.638795E+11 0.105213E+11 0.205584E+12 0.270912E+10 0.395101E+11 0.00
May 0.210789E+12 0.203868E+11 0.774844E+12 0.219671E+12 0.210798E+12 0.286500E+11 0.00 0.417277E+11 0.241317E+11 0.805646E+11 0.529980E+09 0.398586E+11 0.00
June 0.209452E+12 0.181304E+11 0.106252E+13 0.217906E+12 0.240744E+12 0.456288E+11 0.00 0.174385E+12 0.860417E+11 0.404814E+11 0.914091E+09 0.371224E+11 0.00
July 0.195870E+12 0.192056E+11 0.139340E+13 0.213239E+12 0.259362E+12 0.621490E+11 0.00 0.408040E+12 0.141160E+12 0.242952E+10 0.229989E+10 0.336581E+11 0.00
August 0.219001E+12 0.227669E+11 0.173200E+13 0.226028E+12 0.259353E+12 0.582126E+11 0.00 0.417301E+12 0.126788E+12 0.439043E+10 0.173410E+10 0.361503E+11 0.00
September 0.196622E+12 0.269873E+11 0.740713E+12 0.211475E+12 0.210890E+12 0.365960E+11 0.00 0.830596E+11 0.569076E+11 0.105034E+11 0.389954E+09 0.333998E+11 0.00
October 0.205922E+12 0.340751E+11 0.108340E+13 0.213315E+12 0.185567E+12 0.225178E+11 0.00 0.388531E+11 0.113462E+11 0.104880E+12 0.224887E+10 0.361217E+11 0.00
November 0.207031E+12 0.387231E+11 0.135889E+13 0.205270E+12 0.167920E+12 0.192821E+11 0.00 0.414216E+11 0.765912E+10 0.214037E+12 0.425265E+10 0.376516E+11 0.00
December 0.203286E+12 0.433902E+11 0.170972E+13 0.213241E+12 0.163185E+12 0.120058E+11 0.00 0.482555E+11 0.290385E+10 0.261257E+12 0.566115E+10 0.396972E+11 0.00
                           
Annual Sum or Average 0.246116E+13 0.353283E+12 0.146764E+14 0.256627E+13 0.236091E+13 0.346735E+12 0.00 0.139653E+13 0.477945E+12 0.146305E+13 0.367340E+11 0.459853E+12 0.00
Minimum of Months 0.187603E+12 0.181304E+11 0.740713E+12 0.195308E+12 0.146445E+12 0.105466E+11 0.00 0.672433E+10 0.357029E+09 0.242952E+10 0.389954E+09 0.333998E+11 0.00
Maximum of Months 0.220884E+12 0.433902E+11 0.173200E+13 0.226028E+12 0.259362E+12 0.621490E+11 0.00 0.417301E+12 0.141160E+12 0.261257E+12 0.579087E+10 0.452818E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.379344E+12 0.00 0.00 0.00 0.00
February 0.00 0.00 0.293776E+12 0.00 0.00 0.00 0.00
March 0.00 0.00 0.952545E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.181631E+11 0.00 0.00 0.00 0.00
May 0.00 0.00 0.173625E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.247228E+09 0.00 0.00 0.00 0.00
July 0.00 0.00 3086.16 0.00 0.00 0.00 0.00
August 0.00 0.00 3144979.35 0.00 0.00 0.00 0.00
September 0.00 0.00 0.517143E+09 0.00 0.00 0.00 0.00
October 0.00 0.00 0.148571E+11 0.00 0.00 0.00 0.00
November 0.00 0.00 0.561611E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.291000E+12 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.115106E+13 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 3086.16 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.379344E+12 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 247210.90 02-JAN-16:49 40855.88 01-JAN-06:10 423497.50 02-JAN-08:09 233392.71 11-JAN-08:20 97244.99 02-JAN-06:19 22690.32 24-JAN-21:00 0.00 01-JAN-00:10
February 237543.70 01-FEB-16:00 40855.88 01-FEB-06:10 541788.89 01-FEB-08:09 233391.96 01-FEB-08:20 88022.13 28-FEB-15:30 22821.68 06-FEB-05:49 0.00 01-FEB-00:10
March 225303.82 17-MAR-07:10 40855.88 01-MAR-06:10 660080.29 01-MAR-08:09 233385.70 17-MAR-07:19 174346.37 15-MAR-14:30 43491.63 15-MAR-13:30 0.00 01-MAR-00:10
April 217495.61 12-APR-07:10 40855.88 01-APR-05:10 778371.69 03-APR-07:10 233381.57 12-APR-07:19 178018.78 21-APR-14:00 22901.25 20-APR-13:20 0.00 01-APR-00:10
May 215250.65 11-MAY-07:10 40855.88 01-MAY-05:10 423497.50 01-MAY-07:10 233380.38 11-MAY-07:19 199356.33 23-MAY-14:30 42988.66 10-MAY-14:50 0.00 01-MAY-00:10
June 213197.40 21-JUN-08:09 27558.46 01-JUN-19:49 541788.89 01-JUN-07:10 233379.11 19-JUN-07:19 233316.58 28-JUN-15:39 47145.70 01-JUN-15:20 0.00 01-JUN-00:10
July 214802.79 11-JUL-07:30 27558.46 01-JUL-19:00 660080.29 03-JUL-07:10 233380.14 11-JUL-07:40 254310.68 18-JUL-15:30 48849.73 05-JUL-15:00 0.00 01-JUL-00:10
August 215255.89 24-AUG-07:10 40855.88 02-AUG-05:10 778371.69 01-AUG-07:10 233380.38 24-AUG-07:19 274878.55 10-AUG-15:20 48040.12 03-AUG-13:30 0.00 01-AUG-00:10
September 223771.33 26-SEP-07:10 40855.88 01-SEP-05:10 423497.50 01-SEP-07:10 233384.89 26-SEP-07:19 221722.90 19-SEP-15:50 45270.29 20-SEP-13:00 0.00 01-SEP-00:10
October 239882.01 30-OCT-07:10 40855.88 01-OCT-05:10 541788.89 02-OCT-07:10 233393.42 30-OCT-07:19 165117.22 11-OCT-15:00 24137.41 11-OCT-14:30 0.00 01-OCT-00:10
November 247210.90 06-NOV-16:00 40855.88 01-NOV-05:10 660080.29 01-NOV-07:10 233396.00 02-NOV-07:19 122873.48 03-NOV-15:09 22806.74 16-NOV-13:09 0.00 01-NOV-00:10
December 247210.90 01-DEC-16:40 40855.88 01-DEC-06:10 778371.69 01-DEC-08:09 233393.44 18-DEC-08:20 88883.77 11-DEC-06:10 22656.65 04-DEC-07:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 213197.40   27558.46   423497.50   233379.11   88022.13   22656.65   0.00  
Maximum of Months 247210.90   40855.88   778371.69   233396.00   274878.55   48849.73   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 6168.22 12-JAN-16:40 571.39 11-JAN-15:00 78825.19 13-JAN-17:00 4520.72 02-JAN-07:10 56183.54 31-JAN-12:00 0.00
February 14864.03 22-FEB-16:00 2006.27 22-FEB-17:00 100000.00 14-FEB-22:10 4520.72 01-FEB-07:10 56293.54 13-FEB-12:30 0.00
March 285357.31 14-MAR-13:20 79472.29 14-MAR-12:20 100000.00 01-MAR-04:49 4520.72 01-MAR-07:10 56194.37 01-MAR-12:30 0.00
April 128373.85 07-APR-13:00 44804.94 08-APR-13:20 100000.00 01-APR-05:10 4520.72 01-APR-06:10 54960.36 04-APR-11:39 0.00
May 214372.35 10-MAY-13:00 79472.29 10-MAY-13:39 100000.00 07-MAY-13:39 4520.72 01-MAY-06:10 52289.29 01-MAY-11:39 0.00
June 401446.42 27-JUN-07:40 79472.29 01-JUN-14:30 100000.00 03-JUN-17:49 4520.72 01-JUN-16:49 48862.36 01-JUN-11:20 0.00
July 528085.65 05-JUL-15:50 79472.29 03-JUL-12:20 100000.00 06-JUL-13:20 4520.72 03-JUL-14:09 46097.26 03-JUL-11:00 0.00
August 519084.85 15-AUG-14:39 79472.29 02-AUG-13:30 88811.05 22-AUG-13:00 4520.72 03-AUG-11:00 44705.39 01-AUG-11:39 0.00
September 299900.55 15-SEP-10:00 79472.29 08-SEP-12:50 70653.04 19-SEP-13:00 4520.72 06-SEP-06:10 46042.68 29-SEP-11:30 0.00
October 135460.93 11-OCT-14:00 48215.67 11-OCT-14:00 100000.00 30-OCT-21:10 4520.72 02-OCT-06:10 48758.19 31-OCT-11:20 0.00
November 69159.78 16-NOV-13:09 44517.05 16-NOV-13:09 100000.00 01-NOV-04:19 4520.72 01-NOV-06:10 52161.86 30-NOV-12:39 0.00
December 34995.16 01-DEC-10:00 6320.38 01-DEC-10:00 100000.00 01-DEC-22:10 4520.72 01-DEC-17:10 54873.32 28-DEC-12:39 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 6168.22   571.39   70653.04   4520.72   44705.39   0.00
Maximum of Months 528085.65   79472.29   100000.00   4520.72   56293.54   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1142228.99 13-JAN-16:00 247210.90 423497.50 40855.88 233278.49 68357.12 3819.14 0.00 5031.12 344.20
February 1255375.17 28-FEB-16:10 212815.01 541788.89 0.00 233266.29 85181.93 22604.44 0.00 12467.77 718.39
March 1675183.36 15-MAR-14:30 212815.01 660080.29 0.00 233115.89 174346.37 42456.01 0.00 236390.54 79472.29
April 1694241.92 07-APR-14:09 212815.01 778371.69 0.00 233115.89 146406.02 22754.39 0.00 124965.67 44275.93
May 1459249.92 23-MAY-14:20 212815.01 423497.50 0.00 233115.89 194926.00 23299.13 0.00 181025.08 61624.27
June 1692698.58 27-JUN-07:40 212815.01 541788.89 0.00 233379.09 150425.25 44581.28 0.00 401446.42 79472.29
July 2011554.08 05-JUL-15:50 212815.01 660080.29 0.00 233266.29 215127.25 47143.35 0.00 528085.65 79472.29
August 2111016.45 15-AUG-14:39 212815.01 778371.69 0.00 233115.89 215937.80 46481.66 0.00 519084.85 79472.29
September 1502027.89 15-SEP-10:30 212815.01 423497.50 0.00 233115.89 195332.41 44294.74 0.00 275799.99 79472.29
October 1381849.13 11-OCT-15:00 212815.01 541788.89 0.00 233266.29 165117.22 23554.75 0.00 121418.01 47177.57
November 1471053.35 15-NOV-16:49 247210.90 660080.29 40855.88 233280.27 95011.63 22627.39 0.00 29428.79 2064.72
December 1561779.38 18-DEC-16:40 247210.90 778371.69 40855.88 233282.27 79289.83 22604.29 0.00 18886.09 1419.79
                       
Annual Sum or Average                      
Minimum of Months 1142228.99   212815.01 423497.50 0.00 233115.89 68357.12 3819.14 0.00 5031.12 344.20
Maximum of Months 2111016.45   247210.90 778371.69 40855.88 233379.09 215937.80 47143.35 0.00 528085.65 79472.29



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 1582955.37 02-JAN-05:10 0.00 0.00 0.00
February 0.00 0.00 1206922.70 06-FEB-06:10 0.00 0.00 0.00
March 0.00 0.00 701868.43 06-MAR-05:10 0.00 0.00 0.00
April 0.00 0.00 537210.15 11-APR-13:30 0.00 0.00 0.00
May 0.00 0.00 376726.55 11-MAY-13:20 0.00 0.00 0.00
June 0.00 0.00 175273.88 13-JUN-11:09 0.00 0.00 0.00
July 0.00 0.00 5.14 02-JUL-22:00 0.00 0.00 0.00
August 0.00 0.00 5240.98 31-AUG-11:09 0.00 0.00 0.00
September 0.00 0.00 149085.79 28-SEP-09:00 0.00 0.00 0.00
October 0.00 0.00 405146.88 30-OCT-05:10 0.00 0.00 0.00
November 0.00 0.00 614642.23 24-NOV-05:10 0.00 0.00 0.00
December 0.00 0.00 1210366.87 11-DEC-06:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 5.14   0.00 0.00 0.00
Maximum of Months 0.00 0.00 1582955.37   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 39.67 25.74 25.00 25.73
February 0.00 0.00 0.00 0.00 42.00 25.76 23.00 25.75
March 0.00 0.00 0.00 0.00 54.67 26.03 27.83 26.03
April 0.00 0.00 0.00 0.00 50.00 26.26 26.00 26.26
May 0.00 0.00 0.00 0.00 68.00 26.47 35.17 26.42
June 0.00 0.00 0.00 0.00 195.00 27.49 134.83 27.49
July 0.00 0.00 0.00 0.00 395.83 27.78 251.00 27.76
August 0.00 0.00 0.00 0.00 252.83 27.74 156.33 27.74
September 0.00 0.00 0.00 0.00 153.17 27.24 85.67 27.20
October 0.00 0.00 0.00 0.00 80.33 26.88 37.50 26.84
November 0.00 0.00 0.00 0.00 74.17 26.75 32.67 26.72
December 0.00 0.00 0.00 0.00 56.17 26.17 25.67 26.16
                 
Annual Sum or Average 0.00   0.00   1461.83 27.22 860.67 27.23
Minimum of Months 0.00 0.00 0.00 0.00 39.67 25.74 23.00 25.73
Maximum of Months 0.00 0.00 0.00 0.00 395.83 27.78 251.00 27.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 25.60 0.00 25.60
July 0.00 0.00 0.00 0.00 1.67 25.67 0.00 25.67
August 0.00 0.00 0.00 0.00 1.33 25.68 0.00 25.68
September 0.00 0.00 0.00 0.00 0.33 25.59 0.00 25.59
October 0.00 0.00 0.00 0.00 0.33 25.57 0.00 25.57
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.17 25.65 0.00 25.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.67 25.68 0.00 25.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 19.36 0.67 19.54 0.00 19.54 0.00 19.54
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.50 19.36 0.67 19.54 0.00 19.54 0.00 19.54
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 19.36 0.67 19.54 0.00 19.54 0.00 19.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.83 18.76 1.33 19.00 0.00 19.00 0.00 19.00
February 4.00 18.80 0.83 19.03 0.00 19.03 0.00 19.03
March 0.50 19.02 0.00 19.02 0.00 19.02 0.00 19.02
April 0.17 19.09 0.00 19.09 0.00 19.09 0.00 19.09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.25 0.00 19.25 0.00 19.25 0.00 19.25
December 3.67 18.60 0.67 18.83 0.00 18.83 0.00 18.83
                 
Annual Sum or Average 14.67 18.76 2.83 18.98 0.00 18.98 0.00 18.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.83 19.25 1.33 19.25 0.00 19.25 0.00 19.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.50 19.21 0.00 19.21 0.00 19.21 0.00 19.21
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.17 26.99 2.67 27.14
August 0.00 0.00 0.00 0.00 2.50 26.92 1.83 27.11
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 19.21 0.00 19.21 6.67 26.42 4.50 26.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 19.21 0.00 19.21 4.17 26.99 2.67 27.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
February 0.50 19.09 0.00 19.09 0.00 19.09 0.00 19.09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.94 1.00 27.94
May 0.00 0.00 0.00 0.00 3.50 27.71 3.50 27.71
June 0.00 0.00 0.00 0.00 7.83 27.72 7.83 27.72
July 0.00 0.00 0.00 0.00 12.83 27.70 11.83 27.76
August 0.00 0.00 0.00 0.00 5.50 27.60 5.50 27.60
September 0.00 0.00 0.00 0.00 4.33 27.85 4.33 27.85
October 0.00 0.00 0.00 0.00 0.67 27.63 0.67 27.63
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
                 
Annual Sum or Average 0.83 19.23 0.00 19.23 35.67 27.52 34.67 27.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 19.44 0.00 19.44 12.83 27.94 11.83 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 19.18 0.00 19.18 0.67 23.37 0.67 24.77
February 0.83 18.93 0.00 18.93 0.00 18.93 0.00 18.93
March 0.00 0.00 0.00 0.00 0.83 27.57 0.83 27.57
April 0.00 0.00 0.00 0.00 2.33 27.69 2.33 27.69
May 0.00 0.00 0.00 0.00 3.00 27.57 3.00 27.57
June 0.00 0.00 0.00 0.00 5.33 27.61 5.33 27.61
July 0.00 0.00 0.00 0.00 11.67 27.55 9.50 27.66
August 0.00 0.00 0.00 0.00 8.83 27.55 7.50 27.65
September 0.00 0.00 0.00 0.00 5.50 28.08 5.50 28.08
October 0.00 0.00 0.00 0.00 5.17 26.30 5.17 26.30
November 0.00 0.00 0.00 0.00 0.83 27.36 0.83 27.36
December 0.33 19.26 0.00 19.26 0.67 24.87 0.67 25.99
                 
Annual Sum or Average 1.83 19.08 0.00 19.08 44.83 27.16 41.33 27.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.93 0.00 18.93
Maximum of Months 0.83 19.26 0.00 19.26 11.67 28.08 9.50 28.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 2.67 27.69 2.00 27.79
April 0.00 0.00 0.00 0.00 9.33 27.98 6.83 28.03
May 0.00 0.00 0.00 0.00 6.17 28.17 4.00 28.21
June 0.00 0.00 0.00 0.00 17.50 27.85 8.50 27.98
July 0.00 0.00 0.00 0.00 37.50 27.69 15.00 27.81
August 0.00 0.00 0.00 0.00 34.67 27.58 12.00 27.72
September 0.00 0.00 0.00 0.00 6.17 28.11 4.17 28.17
October 0.00 0.00 0.00 0.00 1.50 27.67 1.33 27.67
November 0.00 0.00 0.00 0.00 0.33 26.43 0.17 26.71
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   115.83 27.75 54.00 27.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 37.50 28.17 15.00 28.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.83 18.40 6.83 18.72 0.00 18.72 0.00 18.72
February 23.50 18.34 7.17 18.72 0.00 18.72 0.00 18.72
March 4.33 18.82 0.67 19.00 0.00 19.00 0.00 19.00
April 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 27.33 1.00 27.33
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.28 0.00 19.28 0.00 19.28 0.00 19.28
December 18.33 18.33 5.17 18.70 0.00 18.70 0.00 18.70
                 
Annual Sum or Average 71.50 18.39 19.83 18.73 1.00 18.83 1.00 18.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24.83 19.43 7.17 19.43 1.00 27.33 1.00 27.33



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.17 18.49 0.00 18.49 0.00 18.49 0.00 18.49
February 18.50 18.08 0.17 18.10 0.00 18.10 0.00 18.10
March 2.33 18.77 0.00 18.77 0.00 18.77 0.00 18.77
April 0.00 0.00 0.00 0.00 1.00 27.79 1.00 27.79
May 0.00 0.00 0.00 0.00 2.83 27.80 2.83 27.80
June 0.00 0.00 0.00 0.00 8.17 27.82 8.17 27.82
July 0.00 0.00 0.00 0.00 12.00 27.91 11.50 27.92
August 0.00 0.00 0.00 0.00 6.00 27.71 5.83 27.71
September 0.00 0.00 0.00 0.00 3.67 27.92 3.67 27.92
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.22 0.00 19.22 0.00 19.22 0.00 19.22
December 23.83 18.67 0.00 18.67 0.00 18.67 0.00 18.67
                 
Annual Sum or Average 71.17 18.45 0.17 18.46 33.67 21.47 33.00 22.99
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26.17 19.22 0.17 19.22 12.00 27.92 11.50 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.50 17.93 0.17 17.97 0.50 18.44 0.50 18.87
February 8.83 17.65 0.17 17.69 0.00 17.69 0.00 17.69
March 1.50 19.06 0.00 19.06 0.67 21.67 0.67 23.05
April 0.00 0.00 0.00 0.00 1.83 27.71 1.83 27.71
May 0.00 0.00 0.00 0.00 2.67 27.61 2.67 27.61
June 0.00 0.00 0.00 0.00 4.50 27.61 4.50 27.61
July 0.00 0.00 0.00 0.00 9.00 27.72 8.50 27.73
August 0.00 0.00 0.00 0.00 6.33 27.85 5.67 27.88
September 0.00 0.00 0.00 0.00 6.00 27.93 6.00 27.93
October 0.00 0.00 0.00 0.00 9.50 25.81 9.50 25.81
November 0.17 19.29 0.00 19.29 0.17 23.33 0.17 24.68
December 7.50 18.12 0.17 18.17 0.17 18.37 0.17 18.56
                 
Annual Sum or Average 27.50 17.96 0.50 18.00 41.33 23.55 40.17 24.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.69 0.00 17.69
Maximum of Months 9.50 19.29 0.17 19.29 9.50 27.93 9.50 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.50 18.22 0.00 18.22 0.00 18.22 0.00 18.22
February 8.50 17.80 0.17 17.85 0.00 17.85 0.00 17.85
March 1.67 19.07 0.00 19.07 0.17 19.82 0.17 20.44
April 0.00 0.00 0.00 0.00 3.33 27.73 2.33 27.73
May 0.00 0.00 0.00 0.00 5.33 28.12 3.00 28.15
June 0.00 0.00 0.00 0.00 9.17 28.37 4.67 28.42
July 0.00 0.00 0.00 0.00 14.50 28.12 7.33 28.15
August 0.00 0.00 0.00 0.00 8.50 27.98 4.83 28.05
September 0.00 0.00 0.00 0.00 4.50 28.22 3.00 28.26
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
December 6.17 18.23 0.00 18.23 0.00 18.23 0.00 18.23
                 
Annual Sum or Average 24.00 18.14 0.17 18.15 45.50 24.66 25.33 25.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.50 19.43 0.17 19.43 14.50 28.37 7.33 28.42



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 72.00 17.12 27.33 17.39 0.00 17.39 0.00 17.39
February 65.83 17.00 24.33 17.34 0.00 17.34 0.00 17.34
March 24.00 17.83 7.50 18.16 0.00 18.16 0.00 18.16
April 2.67 19.08 0.67 19.28 0.00 19.28 0.00 19.28
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.00 27.33 1.00 27.33
July 0.00 0.00 0.00 0.00 2.50 27.51 1.50 27.53
August 0.00 0.00 0.00 0.00 2.00 27.39 1.83 27.40
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 2.00 18.86 0.33 19.07 0.00 19.07 0.00 19.07
November 7.17 18.93 1.17 19.09 0.00 19.09 0.00 19.09
December 57.00 17.07 20.50 17.38 0.00 17.38 0.00 17.38
                 
Annual Sum or Average 230.67 17.24 81.83 17.53 5.50 17.70 4.33 17.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 72.00 19.08 27.33 19.28 2.50 27.51 1.83 27.53



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 34.00 15.52 5.67 15.42 0.00 15.42 0.00 15.42
February 31.00 15.50 3.33 15.46 0.00 15.46 0.00 15.46
March 11.00 16.71 0.33 16.65 0.00 16.65 0.00 16.65
April 1.33 18.57 0.00 18.57 0.50 21.02 0.50 22.42
May 0.00 0.00 0.00 0.00 1.67 27.78 1.67 27.78
June 0.00 0.00 0.00 0.00 8.67 27.84 8.33 27.85
July 0.00 0.00 0.00 0.00 13.67 27.93 12.00 27.97
August 0.00 0.00 0.00 0.00 7.67 27.70 7.00 27.71
September 0.00 0.00 0.00 0.00 2.33 27.85 2.33 27.85
October 1.33 18.45 0.00 18.45 0.00 18.45 0.00 18.45
November 4.00 18.35 0.00 18.35 0.00 18.35 0.00 18.35
December 30.83 15.60 5.33 15.49 0.00 15.49 0.00 15.49
                 
Annual Sum or Average 113.50 15.82 14.67 15.71 34.50 18.29 31.83 19.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.42 0.00 15.42
Maximum of Months 34.00 18.57 5.67 18.57 13.67 27.93 12.00 27.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 31.83 16.06 3.83 16.03 0.00 16.03 0.00 16.03
February 32.33 16.18 3.67 16.23 0.00 16.23 0.00 16.23
March 8.00 17.47 0.33 17.37 0.00 17.37 0.00 17.37
April 1.33 18.70 0.00 18.70 1.17 22.87 1.17 24.39
May 0.00 0.00 0.00 0.00 2.17 27.70 2.17 27.70
June 0.00 0.00 0.00 0.00 5.50 27.68 5.00 27.70
July 0.00 0.00 0.00 0.00 10.33 27.82 9.00 27.85
August 0.00 0.00 0.00 0.00 6.83 27.96 6.00 27.98
September 0.00 0.00 0.00 0.00 5.00 28.19 4.83 28.20
October 1.00 18.39 0.00 18.39 2.50 23.82 2.50 24.73
November 3.33 18.71 0.00 18.71 0.00 18.71 0.00 18.71
December 25.17 16.26 2.83 16.27 0.00 16.27 0.00 16.27
                 
Annual Sum or Average 103.00 16.40 10.67 16.38 33.50 18.96 30.67 20.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.03 0.00 16.03
Maximum of Months 32.33 18.71 3.83 18.71 10.33 28.19 9.00 28.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 29.67 15.71 4.67 15.60 0.00 15.60 0.00 15.60
February 20.83 16.06 1.67 16.01 0.00 16.01 0.00 16.01
March 5.67 17.68 0.00 17.68 0.00 17.68 0.00 17.68
April 0.50 18.84 0.00 18.84 2.33 26.09 1.67 26.67
May 0.00 0.00 0.00 0.00 5.50 28.08 3.50 28.12
June 0.00 0.00 0.00 0.00 10.00 28.39 5.00 28.45
July 0.00 0.00 0.00 0.00 15.83 28.20 8.33 28.24
August 0.00 0.00 0.00 0.00 9.33 28.05 5.17 28.14
September 0.00 0.00 0.00 0.00 5.00 28.09 3.17 28.15
October 0.83 18.80 0.00 18.80 0.00 18.80 0.00 18.80
November 2.83 18.80 0.00 18.80 0.00 18.80 0.00 18.80
December 18.67 16.18 2.00 16.05 0.00 16.05 0.00 16.05
                 
Annual Sum or Average 79.00 16.22 8.33 16.10 48.00 20.38 26.83 21.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.60 0.00 15.60
Maximum of Months 29.67 18.84 4.67 18.84 15.83 28.39 8.33 28.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 28.33 28.42 14.17 28.35
August 0.00 0.00 0.00 0.00 99.33 29.24 78.33 29.20
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   127.67 29.05 92.50 29.04
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 99.33 29.24 78.33 29.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 312.83 24.11 42.67 24.33 13.83 24.41
February 273.50 24.01 24.83 24.19 0.00 24.19
March 187.50 24.00 115.17 24.47 0.00 24.47
April 31.50 24.00 122.83 25.71 0.00 25.71
May 23.33 24.00 204.17 25.29 0.00 25.29
June 118.33 27.50 373.17 26.22 118.33 26.46
July 211.83 28.09 487.00 26.81 211.83 27.10
August 139.67 27.93 481.17 26.12 139.67 26.45
September 57.83 27.31 394.17 25.45 57.83 25.66
October 4.33 25.04 242.50 25.47 1.17 25.48
November 38.67 24.19 156.67 25.66 2.00 25.68
December 175.50 24.00 100.50 24.79 0.00 24.79
             
Annual Sum or Average 1574.83 25.31 2744.83 25.57 544.67 25.82
Minimum of Months 4.33 24.00 24.83 24.19 0.00 24.19
Maximum of Months 312.83 28.09 487.00 26.81 211.83 27.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 430.17 23.89 12.83 23.91 12.83 23.93
February 349.83 23.93 7.00 23.96 0.00 23.96
March 187.33 24.00 94.50 24.24 0.00 24.24
April 24.83 24.01 94.83 25.14 0.00 25.14
May 33.67 24.00 172.17 24.60 0.00 24.60
June 0.00 0.00 368.83 24.35 0.00 24.35
July 0.00 0.00 488.33 24.32 0.00 24.32
August 0.00 0.00 489.83 24.26 0.00 24.26
September 0.00 0.00 363.17 24.44 0.00 24.44
October 13.33 23.99 205.00 24.83 0.00 24.83
November 59.00 24.00 102.50 25.00 0.00 25.00
December 223.50 23.98 50.83 24.27 0.00 24.27
             
Annual Sum or Average 1321.67 23.94 2449.83 24.34 12.83 24.34
Minimum of Months 0.00 0.00 7.00 23.91 0.00 23.93
Maximum of Months 430.17 24.01 489.83 25.14 12.83 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.09 54.83 21.89 54.83 21.73
February 454.00 22.36 21.50 22.30 21.50 22.25
March 414.83 23.38 30.83 23.43 0.00 23.43
April 268.50 23.69 12.83 23.76 0.00 23.76
May 119.67 23.84 133.50 24.21 0.00 24.21
June 21.17 23.89 298.00 24.21 0.00 24.21
July 0.00 0.00 475.67 24.23 0.00 24.23
August 0.00 0.00 445.67 24.23 0.00 24.23
September 18.50 23.64 263.83 24.32 0.00 24.32
October 217.83 23.70 62.50 23.87 0.00 23.87
November 377.83 23.52 5.50 23.54 0.00 23.54
December 489.50 22.50 19.83 22.44 19.83 22.38
             
Annual Sum or Average 2883.83 22.94 1824.50 23.39 96.17 23.33
Minimum of Months 0.00 0.00 5.50 21.89 0.00 21.73
Maximum of Months 502.00 23.89 475.67 24.32 54.83 24.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.76 277.33 20.50 277.33 20.38
February 454.00 20.99 219.50 20.69 219.50 20.54
March 457.50 22.00 127.83 21.81 105.67 21.60
April 402.17 22.90 18.33 22.79 17.50 22.69
May 212.67 23.54 84.50 23.75 0.00 23.75
June 47.33 23.70 292.67 24.15 0.00 24.15
July 0.50 23.77 469.17 24.28 0.00 24.28
August 4.50 23.56 432.50 24.24 0.00 24.24
September 116.00 23.39 216.67 23.95 2.67 23.96
October 381.50 22.62 37.50 22.59 20.00 22.50
November 484.33 22.07 64.33 21.87 64.33 21.71
December 497.00 20.92 229.50 20.65 229.50 20.51
             
Annual Sum or Average 3559.50 21.89 2469.83 22.22 936.50 21.94
Minimum of Months 0.50 20.76 18.33 20.50 0.00 20.38
Maximum of Months 502.00 23.77 469.17 24.28 277.33 24.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.30 197.17 21.15 197.17 21.06
February 454.00 21.60 121.00 21.43 121.00 21.31
March 424.50 22.57 68.67 22.54 37.17 22.43
April 309.00 23.44 21.00 23.55 0.00 23.55
May 167.17 23.68 115.67 24.06 0.00 24.06
June 12.83 25.31 353.83 24.43 6.50 24.47
July 27.00 26.72 486.67 24.57 27.00 24.68
August 12.00 26.67 467.83 24.38 11.50 24.43
September 60.83 23.47 267.67 24.19 0.00 24.19
October 319.17 23.34 44.83 23.48 0.00 23.48
November 430.67 23.05 9.17 23.09 0.00 23.09
December 492.67 21.92 68.50 21.78 68.50 21.67
             
Annual Sum or Average 3211.83 22.50 2222.00 22.99 468.83 22.86
Minimum of Months 12.00 21.30 9.17 21.15 0.00 21.06
Maximum of Months 502.00 26.72 486.67 24.57 197.17 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.51 177.17 21.31 177.17 21.19
February 449.50 21.77 113.33 21.57 113.33 21.43
March 396.67 22.72 63.50 22.73 26.00 22.64
April 249.83 23.29 78.67 23.62 2.33 23.65
May 125.83 23.90 213.17 24.35 11.17 24.43
June 42.00 26.12 403.83 24.59 30.50 24.74
July 50.00 26.92 490.00 24.71 50.00 24.90
August 32.83 26.29 464.33 24.47 27.50 24.59
September 59.50 24.17 332.83 24.42 13.00 24.51
October 263.50 23.19 94.67 23.57 1.00 23.58
November 416.83 22.81 14.50 22.90 0.00 22.90
December 495.83 21.68 103.83 21.52 103.83 21.41
             
Annual Sum or Average 3084.33 22.54 2549.83 23.14 555.83 23.06
Minimum of Months 32.83 21.51 14.50 21.31 0.00 21.19
Maximum of Months 502.00 26.92 490.00 24.71 177.17 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 465.50 21.52 190.67 21.31 184.00 21.15
February 413.17 21.79 137.33 21.54 131.33 21.37
March 334.00 22.67 96.83 22.88 25.83 22.77
April 252.00 23.25 97.17 23.60 9.50 23.61
May 157.33 23.67 188.00 24.18 8.00 24.24
June 46.00 25.08 377.67 24.47 19.67 24.58
July 42.83 26.91 480.50 24.69 42.83 24.85
August 30.17 26.68 472.00 24.51 27.33 24.64
September 66.17 24.59 353.50 24.51 22.00 24.64
October 225.33 23.20 148.83 23.75 7.17 23.81
November 362.83 22.73 60.67 23.01 2.00 23.00
December 460.17 21.82 127.17 21.70 113.83 21.55
             
Annual Sum or Average 2855.50 22.56 2730.33 23.19 593.50 23.09
Minimum of Months 30.17 21.52 60.67 21.31 2.00 21.15
Maximum of Months 465.50 26.91 480.50 24.69 184.00 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 494.33 22.11 71.83 21.98 69.50 21.86
February 425.17 22.84 24.33 22.78 19.83 22.70
March 215.67 23.77 132.83 24.08 6.33 24.14
April 47.50 25.29 226.00 25.05 19.33 25.19
May 58.33 25.08 272.00 24.81 22.50 24.95
June 43.17 27.01 457.33 24.79 43.17 24.97
July 107.50 26.62 497.00 25.03 107.50 25.27
August 79.50 26.48 514.00 24.81 79.50 25.01
September 35.67 26.46 395.83 24.72 30.17 24.87
October 86.33 24.04 204.33 24.50 4.83 24.54
November 178.50 23.92 81.50 24.30 0.00 24.30
December 359.67 23.56 12.50 23.61 0.00 23.61
             
Annual Sum or Average 2131.33 23.61 2889.50 24.16 402.67 24.25
Minimum of Months 35.67 22.11 12.50 21.98 0.00 21.86
Maximum of Months 494.33 27.01 514.00 25.05 107.50 25.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.11 463.83 20.08 463.83 20.06
February 454.00 20.25 399.83 20.20 399.83 20.18
March 477.00 21.23 236.50 21.05 218.17 20.90
April 444.50 22.30 36.33 22.16 35.17 22.04
May 265.67 23.25 73.83 23.50 0.00 23.50
June 64.50 24.02 291.33 24.25 9.67 24.29
July 23.00 25.72 466.67 24.46 22.00 24.52
August 33.00 23.95 406.50 24.25 5.83 24.28
September 177.33 23.22 175.17 23.72 9.50 23.78
October 442.67 22.17 45.17 22.09 36.33 21.99
November 489.00 21.29 141.83 21.09 141.83 20.97
December 497.00 20.25 410.50 20.17 410.50 20.14
             
Annual Sum or Average 3869.67 21.41 3147.50 21.70 1752.67 21.43
Minimum of Months 23.00 20.11 36.33 20.08 0.00 20.06
Maximum of Months 502.00 25.72 466.67 24.46 463.83 24.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.10 388.17 20.05 388.17 20.03
February 385.00 20.37 305.00 20.22 305.00 20.17
March 389.50 21.72 138.00 21.53 117.67 21.33
April 287.33 22.50 61.33 22.77 12.83 22.71
May 163.50 23.55 153.33 24.13 10.83 24.23
June 61.33 25.44 317.50 24.67 33.83 24.85
July 62.50 26.73 413.50 24.90 62.50 25.11
August 44.67 25.69 369.50 24.61 29.50 24.76
September 111.50 23.75 239.50 24.31 20.67 24.44
October 314.83 22.43 65.67 22.61 18.50 22.52
November 404.00 21.48 104.50 21.26 104.50 21.11
December 422.00 20.21 353.67 20.13 353.67 20.10
             
Annual Sum or Average 3073.17 21.64 2909.67 22.09 1457.67 21.85
Minimum of Months 44.67 20.10 61.33 20.05 10.83 20.03
Maximum of Months 427.00 26.73 413.50 24.90 388.17 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 476.17 20.78 321.33 20.56 315.00 20.44
February 421.67 20.90 254.83 20.65 249.33 20.51
March 363.67 21.96 145.83 22.08 79.83 21.88
April 319.83 22.57 96.50 22.90 19.67 22.84
May 206.50 23.34 162.50 23.88 8.17 23.95
June 83.17 24.31 339.00 24.35 22.67 24.46
July 59.17 26.16 467.83 24.67 52.17 24.84
August 44.83 25.36 443.33 24.47 24.50 24.59
September 117.00 24.11 319.00 24.38 30.67 24.55
October 277.33 22.67 142.33 23.19 23.17 23.19
November 395.00 21.83 113.50 21.90 70.50 21.74
December 474.33 20.79 293.17 20.61 286.00 20.50
             
Annual Sum or Average 3238.67 21.93 3099.17 22.48 1181.67 22.26
Minimum of Months 44.83 20.78 96.50 20.56 8.17 20.44
Maximum of Months 476.17 26.16 467.83 24.67 315.00 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.36 411.83 20.26 411.83 20.22
February 450.67 20.64 315.00 20.47 315.00 20.40
March 417.83 21.83 145.67 21.75 110.00 21.56
April 331.33 22.76 80.83 23.00 19.67 22.97
May 183.00 23.76 193.00 24.21 19.00 24.34
June 59.33 25.21 391.83 24.56 29.17 24.70
July 54.50 26.73 483.83 24.80 54.50 24.97
August 30.00 26.47 473.83 24.55 26.00 24.67
September 117.50 24.01 286.17 24.32 25.67 24.47
October 346.00 22.50 76.00 22.68 17.33 22.60
November 466.33 21.75 85.50 21.57 85.33 21.44
December 497.00 20.54 347.50 20.41 347.50 20.35
             
Annual Sum or Average 3455.50 21.77 3291.00 22.28 1461.00 22.05
Minimum of Months 30.00 20.36 76.00 20.26 17.33 20.22
Maximum of Months 502.00 26.73 483.83 24.80 411.83 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.83 488.83 19.81 488.83 19.81
February 454.00 19.88 434.17 19.86 434.17 19.85
March 485.00 20.68 317.33 20.50 302.50 20.38
April 465.17 21.66 112.50 21.36 112.50 21.15
May 313.83 22.85 66.50 23.03 7.50 22.99
June 90.33 23.71 286.67 24.16 12.83 24.23
July 46.00 25.71 459.83 24.53 39.17 24.65
August 61.83 23.72 383.17 24.20 10.33 24.25
September 234.67 22.79 158.00 23.35 12.00 23.41
October 470.33 21.40 125.83 21.10 120.00 20.88
November 489.00 20.52 291.83 20.32 291.83 20.24
December 497.00 19.84 467.00 19.80 467.00 19.79
             
Annual Sum or Average 4109.17 21.02 3591.67 21.27 2298.67 21.00
Minimum of Months 46.00 19.83 66.50 19.80 7.50 19.79
Maximum of Months 502.00 25.71 488.83 24.53 488.83 24.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.92 487.33 19.90 487.33 19.90
February 454.00 20.07 386.83 19.95 386.83 19.90
March 468.17 21.15 236.33 20.90 210.50 20.68
April 353.83 21.91 106.33 21.89 64.17 21.64
May 198.83 23.14 179.50 23.80 12.67 23.87
June 75.00 24.94 378.00 24.50 32.67 24.67
July 67.50 26.67 483.67 24.79 66.67 25.00
August 58.17 25.21 436.33 24.48 32.50 24.63
September 159.67 23.21 281.83 23.98 20.33 24.07
October 401.50 21.80 111.67 21.64 80.50 21.40
November 489.00 20.81 252.67 20.55 252.67 20.42
December 497.00 19.92 464.50 19.89 464.50 19.87
             
Annual Sum or Average 3724.67 21.22 3805.00 21.67 2111.33 21.40
Minimum of Months 58.17 19.92 106.33 19.89 12.67 19.87
Maximum of Months 502.00 26.67 487.33 24.79 487.33 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 484.17 20.32 387.17 20.13 384.33 20.04
February 430.83 20.34 319.67 20.10 315.67 19.98
March 401.00 21.36 206.33 21.23 162.00 20.99
April 351.00 21.89 142.33 21.96 83.00 21.74
May 243.33 22.90 149.17 23.47 13.17 23.50
June 103.67 23.89 331.83 24.25 23.67 24.37
July 71.33 25.75 458.83 24.65 55.17 24.83
August 66.33 24.64 421.33 24.42 25.00 24.54
September 153.83 23.47 290.17 24.12 30.33 24.29
October 331.83 21.91 155.67 22.14 65.00 21.91
November 432.17 21.12 194.67 20.90 178.00 20.71
December 484.17 20.27 385.17 20.11 384.17 20.04
             
Annual Sum or Average 3553.67 21.44 3442.33 21.89 1719.50 21.62
Minimum of Months 66.33 20.27 142.33 20.10 13.17 19.98
Maximum of Months 484.17 25.75 458.83 24.65 384.33 24.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.03 453.00 19.96 453.00 19.93
February 451.83 20.22 365.17 20.07 365.17 20.02
March 437.83 21.26 227.83 21.10 197.00 20.90
April 369.50 22.11 116.17 22.18 63.33 22.01
May 225.33 23.30 173.33 23.85 19.33 24.00
June 75.00 24.68 379.83 24.48 29.67 24.63
July 69.67 26.24 478.67 24.78 63.50 24.96
August 56.33 25.24 455.83 24.52 32.17 24.65
September 167.50 23.43 259.67 24.03 26.67 24.19
October 396.67 21.82 114.50 21.75 72.67 21.52
November 479.83 21.03 199.67 20.75 199.67 20.61
December 497.00 20.09 418.17 19.99 418.17 19.96
             
Annual Sum or Average 3728.50 21.37 3641.83 21.82 1940.33 21.56
Minimum of Months 56.33 20.03 114.50 19.96 19.33 19.93
Maximum of Months 502.00 26.24 478.67 24.78 453.00 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 484.17 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 7.33 27.00 514.00 27.00 7.33 27.00
April 43.83 27.00 485.00 27.00 43.83 27.00
May 7.33 27.00 508.00 27.00 7.33 27.00
June 94.17 27.00 496.00 27.00 94.17 27.00
July 276.67 27.00 497.00 27.00 276.67 27.00
August 365.67 27.00 514.00 27.00 365.67 27.00
September 19.00 27.00 485.00 27.00 19.00 27.00
October 8.00 27.00 502.00 27.00 8.00 27.00
November 2.00 27.00 489.00 27.00 2.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 824.00 27.00 5925.17 27.00 824.00 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 365.67 27.00 514.00 27.00 365.67 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 87.50 25.47 158.17 26.45 0.00 26.45
February 0.33 27.00 225.17 27.00 0.00 27.00
March 0.00 0.00 461.50 27.00 0.00 27.00
April 2.50 27.00 485.00 27.00 2.50 27.00
May 4.00 27.00 508.00 27.00 4.00 27.00
June 11.50 27.00 496.00 27.00 11.50 27.00
July 44.17 27.00 497.00 27.00 44.17 27.00
August 66.83 27.00 514.00 27.00 66.83 27.00
September 3.33 27.00 485.00 27.00 3.33 27.00
October 1.50 27.00 502.00 27.00 1.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 350.17 27.00 0.00 27.00
             
Annual Sum or Average 221.67 26.40 5171.00 26.98 133.83 26.98
Minimum of Months 0.00 0.00 158.17 26.45 0.00 26.45
Maximum of Months 87.50 27.00 514.00 27.00 66.83 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 284.17 24.96 92.17 25.13 28.00 24.95
February 69.33 27.00 129.67 27.00 0.00 27.00
March 11.67 27.00 360.83 27.00 0.00 27.00
April 2.50 27.00 469.83 27.00 2.50 27.00
May 5.50 27.00 508.00 27.00 5.50 27.00
June 43.50 27.00 496.00 27.00 43.50 27.00
July 97.50 27.00 497.00 27.00 97.50 27.00
August 97.00 27.00 514.00 27.00 97.00 27.00
September 7.50 27.00 485.00 27.00 7.50 27.00
October 1.67 27.00 473.17 27.00 1.67 27.00
November 0.00 0.00 410.00 27.00 0.00 27.00
December 47.50 27.00 211.33 27.00 0.00 27.00
             
Annual Sum or Average 667.83 26.13 4647.00 26.87 283.17 26.85
Minimum of Months 0.00 0.00 92.17 25.13 0.00 24.95
Maximum of Months 284.17 27.00 514.00 27.00 97.50 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 88.17 27.00 502.00 27.00 88.17 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 495.33 27.00 508.00 27.00 495.33 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.05 497.00 27.05 497.00 27.05
August 514.00 27.35 514.00 27.35 514.00 27.35
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5516.50 27.04 5943.00 27.04 5516.50 27.04
Minimum of Months 88.17 27.00 454.00 27.00 88.17 27.00
Maximum of Months 514.00 27.35 514.00 27.35 514.00 27.35



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 16.97709 0.65995 14.27836
February 454.00000 27.00000 16.10377 0.70814 15.64799
March 514.00000 27.00006 21.76732 0.84470 20.24259
April 485.00000 27.00001 26.60579 0.94442 23.90534
May 508.00000 27.00022 30.36838 0.22373 6.16419
June 496.00000 27.00083 34.76396 0.34467 7.56319
July 497.00000 27.00077 37.05430 0.42208 8.78148
August 514.00000 27.00024 36.29060 0.44803 9.26584
September 485.00000 27.00055 35.84662 0.28020 6.72161
October 502.00000 27.00016 30.19023 0.90328 22.29904
November 489.00000 27.00001 26.02613 0.87997 21.42469
December 497.00000 27.00000 19.05301 0.81319 19.04091
           
Annual Sum or Average 5943.00000 27.00024 27.66321 0.62148 14.58432
Minimum of Months 454.00000 27.00000 16.10377 0.22373 6.16419
Maximum of Months 514.00000 27.00083 37.05430 0.94442 23.90534



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.66891 17.28067 0.45247 9.97760
February 454.00000 27.00000 16.08989 0.54139 11.28572
March 514.00000 27.00006 21.75723 0.70461 15.77379
April 485.00000 27.00001 26.58268 0.81099 19.01633
May 508.00000 27.00021 30.37199 0.15306 5.66359
June 496.00000 27.00081 34.77758 0.25818 6.51514
July 497.00000 27.00081 37.07168 0.31509 7.15189
August 514.00000 27.00023 36.28011 0.32094 7.24730
September 485.00000 27.00046 35.94687 0.20513 6.00774
October 502.00000 27.00016 30.17144 0.80165 18.68670
November 489.00000 27.00001 25.98855 0.72411 16.17699
December 497.00000 27.00000 19.02858 0.59233 12.51841
           
Annual Sum or Average 5943.00000 26.97226 27.68849 0.48901 11.32055
Minimum of Months 454.00000 26.66891 16.08989 0.15306 5.66359
Maximum of Months 514.00000 27.00081 37.07168 0.81099 19.01633



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.75679 17.64617 0.21648 8.11375
February 454.00000 27.00007 16.08899 0.47344 9.94537
March 514.00000 27.00006 21.76596 0.63490 13.99601
April 485.00000 27.00001 26.59227 0.75642 17.35163
May 508.00000 27.00021 30.39650 0.12489 5.65848
June 496.00000 27.00083 34.78600 0.25937 6.63614
July 497.00000 27.00082 37.07840 0.32694 7.38188
August 514.00000 27.00026 36.29329 0.32321 7.35819
September 485.00000 27.00044 35.99452 0.17873 5.93510
October 502.00000 27.00016 30.19571 0.73784 16.76024
November 489.00000 27.00001 26.00551 0.63766 13.76745
December 497.00000 27.00000 19.03867 0.51315 10.74940
           
Annual Sum or Average 5943.00000 26.89523 27.73351 0.43100 10.29474
Minimum of Months 454.00000 25.75679 16.08899 0.12489 5.65848
Maximum of Months 514.00000 27.00083 37.07840 0.75642 17.35163



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99998 30.02992 1.00166 26.20038
February 454.00000 27.00016 29.84271 1.17019 33.81204
March 514.00000 27.00059 27.44822 1.31883 41.26506
April 485.00000 27.00076 27.10913 1.46290 48.89504
May 508.00000 27.00001 32.40224 0.47944 9.86821
June 496.00000 27.00136 40.00035 0.79646 18.54684
July 497.00000 27.05133 44.34102 1.06712 29.15901
August 514.00000 27.34749 38.33832 1.29953 40.31144
September 485.00000 27.00004 39.51221 0.60318 12.81125
October 502.00000 27.00014 31.38916 1.25166 37.82315
November 489.00000 27.00047 28.78444 1.36235 43.52333
December 497.00000 27.00020 24.32069 1.43312 47.29112
           
Annual Sum or Average 5943.00000 27.03466 32.81299 1.10344 32.44813
Minimum of Months 454.00000 26.99998 24.32069 0.47944 9.86821
Maximum of Months 514.00000 27.34749 44.34102 1.46290 48.89504



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.47303 18.84629 0.29552 7.56677
February 454.00000 24.46873 16.80045 0.28176 6.94311
March 514.00000 24.46108 23.69402 0.34798 7.94184
April 485.00000 24.58782 26.79347 0.40629 8.96371
May 508.00000 24.60532 32.09159 -0.4025 9.47989
June 496.00000 25.36411 48.11320 -0.0310 11.68399
July 497.00000 26.20151 61.03939 0.34171 16.67240
August 514.00000 25.49310 54.47327 0.08080 13.07185
September 485.00000 24.95548 45.84712 -0.1670 8.76870
October 502.00000 24.72231 32.06820 0.48719 10.72195
November 489.00000 24.69531 25.47122 0.42892 9.55879
December 497.00000 24.60580 19.48150 0.34895 8.03749
           
Annual Sum or Average 5943.00000 24.88931 33.86104 0.20032 9.97820
Minimum of Months 454.00000 24.46108 16.80045 -0.4025 6.94311
Maximum of Months 514.00000 26.20151 61.03939 0.48719 16.67240



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.94713 24.16207 0.20182 6.27730
February 454.00000 24.07852 21.53664 0.22063 6.19825
March 514.00000 24.23850 25.61181 0.32287 7.48285
April 485.00000 24.32641 28.03721 0.38096 8.29365
May 508.00000 24.27832 33.95328 -0.4628 9.98987
June 496.00000 24.26690 45.16146 -0.3482 7.99134
July 497.00000 24.31336 53.21937 -0.2520 6.73430
August 514.00000 24.24830 50.19857 -0.2951 7.13583
September 485.00000 24.33376 45.59535 -0.3459 8.08787
October 502.00000 24.37579 34.31346 0.42695 9.12769
November 489.00000 24.39478 28.28975 0.38082 8.35377
December 497.00000 24.30621 22.82240 0.30050 7.12839
           
Annual Sum or Average 5943.00000 24.25962 34.50875 0.04201 7.74351
Minimum of Months 454.00000 23.94713 21.53664 -0.4628 6.19825
Maximum of Months 514.00000 24.39478 53.21937 0.42695 9.98987



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.08505 26.26276 -0.2777 8.22265
February 454.00000 22.36213 25.80543 -0.2085 6.75575
March 514.00000 23.51283 28.94411 0.12126 6.17852
April 485.00000 23.91798 30.90735 0.25145 6.57363
May 508.00000 24.14554 34.69133 -0.5390 11.51334
June 496.00000 24.15224 46.26931 -0.4309 9.21975
July 497.00000 24.22327 54.81211 -0.3415 7.70882
August 514.00000 24.19885 51.58704 -0.3713 8.12546
September 485.00000 24.18726 46.60616 -0.4317 9.33774
October 502.00000 23.97057 36.57251 0.30301 7.18722
November 489.00000 23.65144 32.01865 0.17173 6.04641
December 497.00000 22.52423 28.40696 -0.1488 6.47063
           
Annual Sum or Average 5943.00000 23.58601 36.99071 -0.1590 7.79030
Minimum of Months 454.00000 22.08505 25.80543 -0.5390 6.04641
Maximum of Months 514.00000 24.22327 54.81211 0.30301 11.51334



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.75696 27.84739 -0.6218 15.66140
February 454.00000 20.98735 27.13000 -0.5641 14.22486
March 514.00000 22.22765 31.48621 -0.2021 8.83838
April 485.00000 23.09456 32.96363 0.04048 6.51241
May 508.00000 23.91286 35.44923 -0.6292 14.19743
June 496.00000 24.11837 46.43297 -0.4355 9.48931
July 497.00000 24.26227 54.55432 -0.3170 7.44882
August 514.00000 24.19776 51.48761 -0.3685 8.13001
September 485.00000 23.96420 47.57097 -0.5164 11.50904
October 502.00000 22.96212 39.72028 0.04777 6.78193
November 489.00000 22.08968 36.67148 -0.2143 7.58997
December 497.00000 20.92391 30.77790 -0.5568 13.71853
           
Annual Sum or Average 5943.00000 22.80519 38.58746 -0.3606 10.32096
Minimum of Months 454.00000 20.75696 27.13000 -0.6292 6.51241
Maximum of Months 514.00000 24.26227 54.55432 0.04777 15.66140



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.30347 23.46121 -0.4673 10.40827
February 454.00000 21.59883 22.83682 -0.3933 9.19949
March 514.00000 22.83206 26.92812 -0.0457 7.14604
April 485.00000 23.71887 28.49931 0.19581 6.46597
May 508.00000 24.06292 33.76070 -0.5579 12.48828
June 496.00000 24.30020 44.34652 -0.3216 8.02524
July 497.00000 24.43959 52.20341 -0.1799 6.74334
August 514.00000 24.29069 49.39242 -0.2726 7.33226
September 485.00000 24.14298 45.42720 -0.4384 9.93941
October 502.00000 23.63455 35.05569 0.20977 6.67448
November 489.00000 23.18823 29.71024 0.04793 5.93005
December 497.00000 21.93679 24.69291 -0.2940 7.88020
           
Annual Sum or Average 5943.00000 23.29864 34.78354 -0.2093 8.18489
Minimum of Months 454.00000 21.30347 22.83682 -0.5579 5.93005
Maximum of Months 514.00000 24.43959 52.20341 0.20977 12.48828



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.50546 23.33224 -0.4197 9.73869
February 454.00000 21.79356 22.61818 -0.3453 8.92914
March 514.00000 23.03279 26.57567 0.01921 6.98840
April 485.00000 23.73669 28.15228 0.23990 7.38355
May 508.00000 24.18622 33.15333 -0.4409 11.08818
June 496.00000 24.36536 43.94273 -0.2229 7.76489
July 497.00000 24.48373 51.84622 -0.0886 7.04887
August 514.00000 24.30131 49.17669 -0.2071 7.26691
September 485.00000 24.26921 44.83403 -0.3293 9.13474
October 502.00000 23.69692 34.64063 0.24617 7.48164
November 489.00000 23.03730 29.90725 0.01797 6.26644
December 497.00000 21.68922 25.07020 -0.3553 8.64700
           
Annual Sum or Average 5943.00000 23.35243 34.52729 -0.1565 8.14174
Minimum of Months 454.00000 21.50546 22.61818 -0.4409 6.26644
Maximum of Months 514.00000 24.48373 51.84622 0.24617 11.08818



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.73851 22.82278 -0.3595 10.48184
February 454.00000 21.98540 22.03802 -0.2929 9.42161
March 514.00000 23.22379 25.83356 0.08518 7.77782
April 485.00000 23.72792 28.09043 0.23689 7.72435
May 508.00000 24.09227 33.45601 -0.5025 12.27587
June 496.00000 24.30164 44.24951 -0.2899 8.18951
July 497.00000 24.47113 51.93903 -0.1275 6.97452
August 514.00000 24.34305 49.01703 -0.1870 7.15725
September 485.00000 24.30172 44.64383 -0.2860 8.92382
October 502.00000 23.78134 34.11732 0.29778 8.68778
November 489.00000 23.16596 29.33660 0.06587 7.11483
December 497.00000 22.02530 24.55871 -0.2720 8.87232
           
Annual Sum or Average 5943.00000 23.44026 34.26668 -0.1355 8.63280
Minimum of Months 454.00000 21.73851 22.03802 -0.5025 6.97452
Maximum of Months 514.00000 24.47113 51.93903 0.29778 12.27587



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.15307 22.41003 -0.2554 7.73727
February 454.00000 22.92750 20.91825 -0.0639 6.48157
March 514.00000 24.07558 24.24998 0.30840 8.17369
April 485.00000 24.49224 26.26943 0.48914 11.05019
May 508.00000 24.42882 32.52049 -0.3154 9.11133
June 496.00000 24.53382 43.42871 -0.0786 7.29175
July 497.00000 24.69118 51.10995 0.07303 7.59189
August 514.00000 24.55643 48.20681 0.01751 7.09444
September 485.00000 24.46427 44.18590 -0.2217 7.84042
October 502.00000 24.30969 32.90886 0.42521 9.47996
November 489.00000 24.25460 26.90042 0.33672 7.93300
December 497.00000 23.78655 21.73152 0.15616 6.26982
           
Annual Sum or Average 5943.00000 24.06305 32.99649 0.07284 8.01097
Minimum of Months 454.00000 22.15307 20.91825 -0.3154 6.26982
Maximum of Months 514.00000 24.69118 51.10995 0.48914 11.05019



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.11112 25.39238 -0.8402 21.95238
February 454.00000 20.25061 25.21049 -0.7894 19.91170
March 514.00000 21.42538 29.93220 -0.4084 11.83602
April 485.00000 22.45128 31.88360 -0.1162 7.13547
May 508.00000 23.68072 35.14561 -0.7061 17.05782
June 496.00000 24.15100 45.53503 -0.4055 9.39235
July 497.00000 24.37255 53.91862 -0.2471 7.12370
August 514.00000 24.18206 50.80211 -0.3577 8.43097
September 485.00000 23.75202 47.09589 -0.5941 14.05278
October 502.00000 22.39171 38.26589 -0.0927 7.03478
November 489.00000 21.28735 33.55246 -0.4154 9.87455
December 497.00000 20.24994 28.38974 -0.7674 19.33477
           
Annual Sum or Average 5943.00000 22.37533 37.17958 -0.4766 12.71874
Minimum of Months 454.00000 20.11112 25.21049 -0.8402 7.03478
Maximum of Months 514.00000 24.37255 53.91862 -0.0927 21.95238



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.09884 24.72788 -0.8326 21.64281
February 385.00000 20.37119 24.45781 -0.7460 18.91049
March 433.00000 21.95291 28.60416 -0.2618 9.64888
April 410.00000 23.05464 29.91723 0.06030 7.69026
May 430.00000 24.03535 33.55512 -0.5176 13.68035
June 418.00000 24.38352 44.46237 -0.2457 8.59411
July 422.00000 24.61211 52.81276 -0.0820 7.56545
August 433.00000 24.38240 49.73011 -0.2180 7.88717
September 410.00000 24.12928 45.57144 -0.4090 11.39768
October 427.00000 22.91321 36.40375 0.04266 7.35508
November 417.00000 21.56645 32.26953 -0.3496 9.40266
December 422.00000 20.21378 27.70957 -0.7757 19.51947
           
Annual Sum or Average 5034.00000 22.65691 35.92359 -0.3592 11.90056
Minimum of Months 385.00000 20.09884 24.45781 -0.8326 7.35508
Maximum of Months 433.00000 24.61211 52.81276 0.06030 21.64281



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.96748 24.31067 -0.5808 16.28596
February 454.00000 21.12128 23.93125 -0.5236 14.64045
March 514.00000 22.62880 27.77519 -0.0609 8.99717
April 485.00000 23.14916 29.99984 0.09461 7.96576
May 508.00000 23.87892 34.24382 -0.5806 14.80064
June 496.00000 24.18475 45.22350 -0.3519 9.38655
July 497.00000 24.44196 53.41645 -0.1710 7.34917
August 514.00000 24.29959 50.06923 -0.2352 7.81996
September 485.00000 24.16754 45.36578 -0.3372 10.42839
October 502.00000 23.37139 35.47954 0.19986 8.81460
November 489.00000 22.32296 31.42576 -0.1383 8.54114
December 497.00000 20.96317 27.47981 -0.5578 14.65633
           
Annual Sum or Average 5943.00000 22.97247 35.81410 -0.2689 10.78584
Minimum of Months 454.00000 20.96317 23.93125 -0.5808 7.34917
Maximum of Months 514.00000 24.44196 53.41645 0.19986 16.28596



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.36101 25.07679 -0.7526 19.07079
February 454.00000 20.66293 24.64146 -0.6586 16.28439
March 514.00000 22.27049 28.39986 -0.1747 9.27298
April 485.00000 23.22216 30.00680 0.10799 7.86378
May 508.00000 24.05578 33.99068 -0.4913 12.93105
June 496.00000 24.34695 44.73572 -0.2203 8.29715
July 497.00000 24.55979 53.01225 -0.0751 7.35777
August 514.00000 24.39036 49.82502 -0.1766 7.53391
September 485.00000 24.11827 45.77873 -0.3965 10.78173
October 502.00000 23.00719 36.56313 0.07383 7.26855
November 489.00000 21.85800 32.42377 -0.2694 8.29280
December 497.00000 20.54318 27.96180 -0.6709 16.09508
           
Annual Sum or Average 5943.00000 22.79939 36.11804 -0.3065 10.88556
Minimum of Months 454.00000 20.36101 24.64146 -0.7526 7.26855
Maximum of Months 514.00000 24.55979 53.01225 0.10799 19.07079



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.82667 26.27514 -0.9613 27.09806
February 454.00000 19.88379 25.98553 -0.9286 25.89887
March 514.00000 20.86465 31.31985 -0.5800 16.57678
April 485.00000 21.75910 33.19939 -0.2991 9.80362
May 508.00000 23.33956 36.00894 -0.8266 22.08265
June 496.00000 24.06968 45.84481 -0.4273 10.45889
July 497.00000 24.37313 53.92103 -0.2367 7.35911
August 514.00000 24.12782 50.92812 -0.3724 9.12117
September 485.00000 23.43826 48.14321 -0.7049 18.40226
October 502.00000 21.55973 40.28277 -0.3102 10.39308
November 489.00000 20.52088 35.78558 -0.6412 15.89300
December 497.00000 19.83706 29.61699 -0.9231 25.83527
           
Annual Sum or Average 5943.00000 21.98423 38.19371 -0.5987 16.51390
Minimum of Months 454.00000 19.82667 25.98553 -0.9613 7.35911
Maximum of Months 514.00000 24.37313 53.92103 -0.2367 27.09806



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.92047 26.19912 -0.9166 25.32537
February 454.00000 20.06592 25.84774 -0.8558 23.61468
March 514.00000 21.40503 30.55132 -0.4150 13.48143
April 485.00000 22.54261 31.30171 -0.0712 9.15284
May 508.00000 23.81543 34.33752 -0.5828 15.85854
June 496.00000 24.27828 44.79332 -0.2551 8.79575
July 497.00000 24.51314 52.99694 -0.0803 7.44784
August 514.00000 24.28215 50.02299 -0.2231 8.03905
September 485.00000 23.88926 46.33408 -0.4793 13.43191
October 502.00000 22.25829 38.56898 -0.1270 9.18356
November 489.00000 20.81135 35.26054 -0.5619 14.29611
December 497.00000 19.92481 29.52259 -0.8927 24.52576
           
Annual Sum or Average 5943.00000 22.32694 37.22574 -0.4524 14.36315
Minimum of Months 454.00000 19.92047 25.84774 -0.9166 7.44784
Maximum of Months 514.00000 24.51314 52.99694 -0.0712 25.32537



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.46559 25.49059 -0.7440 21.34729
February 454.00000 20.52962 25.05176 -0.7045 20.83613
March 514.00000 21.96416 29.34963 -0.2511 11.90623
April 485.00000 22.53833 31.21884 -0.0711 9.46786
May 508.00000 23.58711 35.00098 -0.6868 19.06182
June 496.00000 24.09217 45.57905 -0.3766 10.61872
July 497.00000 24.41670 53.51268 -0.1678 7.72719
August 514.00000 24.24476 50.21062 -0.2497 8.47024
September 485.00000 23.94142 46.11789 -0.4228 13.15696
October 502.00000 22.68708 37.21158 0.01300 9.83568
November 489.00000 21.46881 33.81788 -0.3783 12.19307
December 497.00000 20.37193 28.94847 -0.7485 20.66173
           
Annual Sum or Average 5943.00000 22.54204 36.87702 -0.3971 13.72741
Minimum of Months 454.00000 20.37193 25.05176 -0.7485 7.72719
Maximum of Months 514.00000 24.41670 53.51268 0.01300 21.34729



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.02513 26.02867 -0.8797 24.05424
February 454.00000 20.23911 25.50779 -0.7967 21.64807
March 514.00000 21.68997 29.82987 -0.3389 12.31471
April 485.00000 22.61463 31.20047 -0.0507 9.15172
May 508.00000 23.78580 34.71773 -0.5884 16.62533
June 496.00000 24.27222 45.03905 -0.2399 9.19229
July 497.00000 24.54189 53.08795 -0.0707 7.62908
August 514.00000 24.34826 49.93374 -0.1876 7.99214
September 485.00000 23.88094 46.59924 -0.4829 13.67299
October 502.00000 22.29419 38.30621 -0.1109 9.00092
November 489.00000 21.08282 34.62868 -0.4822 12.42132
December 497.00000 20.09185 29.23781 -0.8212 21.88732
           
Annual Sum or Average 5943.00000 22.42328 37.09125 -0.4182 13.74362
Minimum of Months 454.00000 20.02513 25.50779 -0.8797 7.62908
Maximum of Months 514.00000 24.54189 53.08795 -0.0507 24.05424



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 23319615.51 620.84 11-JAN-16:40 16.28 0.227384E+09 0.00 0.250704E+09 0.21 9.83 25-JAN-11:40 0.00 0.00
February 64837127.20 2977.40 22-FEB-17:00 19.46 0.632599E+09 0.00 0.697437E+09 0.28 9.83 28-FEB-13:40 0.00 0.00
March 0.748493E+10 179868.03 14-MAR-13:20 130.41 0.646111E+11 0.00 0.720960E+11 1.69 10.00 14-MAR-16:40 0.00 0.00
April 0.655075E+10 58388.00 19-APR-15:10 159.53 0.640748E+11 0.00 0.706255E+11 2.16 10.00 20-APR-13:20 0.00 0.00
May 0.228823E+11 170445.04 10-MAY-14:00 269.70 0.214592E+12 0.00 0.237475E+12 3.51 10.00 27-MAY-14:40 0.00 0.00
June 0.809601E+11 182863.77 01-JUN-14:30 456.89 0.705206E+12 0.00 0.786166E+12 5.90 10.00 06-JUN-11:05 0.00 0.00
July 0.131438E+12 197710.97 05-JUL-15:40 609.09 0.109537E+13 0.00 0.122681E+13 7.35 10.03 24-JUL-05:03 0.00 0.00
August 0.114606E+12 195866.32 15-AUG-14:40 592.74 0.970904E+12 0.00 0.108551E+13 7.29 10.02 16-AUG-05:03 0.00 0.00
September 0.530242E+11 179370.64 15-SEP-12:00 356.80 0.473102E+12 0.00 0.526127E+12 4.68 10.00 09-SEP-12:40 0.00 0.00
October 0.106448E+11 98170.90 11-OCT-14:30 181.40 0.102854E+12 0.00 0.113498E+12 2.37 10.00 05-OCT-14:30 0.00 0.00
November 0.248593E+10 34199.05 16-NOV-13:10 139.18 0.242024E+11 0.00 0.266883E+11 1.88 9.83 28-NOV-11:20 0.00 0.00
December 66242914.05 4127.30 01-DEC-07:13 26.49 0.646332E+09 0.00 0.712575E+09 0.35 9.83 04-DEC-10:40 0.00 0.00
                         
Annual Sum or Average 0.430231E+12     2957.97 0.371642E+13 0.00 0.414665E+13 3.16     0.00 0.00
Minimum of Months 23319615.51 620.84   16.28 0.227384E+09 0.00 0.250704E+09 0.21 9.83   0.00 0.00
Maximum of Months 0.131438E+12 197710.97   609.09 0.109537E+13 0.00 0.122681E+13 7.35 10.03   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.193487E+09 81112.76 15-MAR-14:05 1.25 0.178986E+10 0.00 0.198335E+10 0.02 10.45 15-MAR-14:20 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.272770E+09 74075.61 10-MAY-14:05 1.08 0.250548E+10 0.00 0.277825E+10 0.01 9.32 10-MAY-14:20 0.00 0.00
June 0.168877E+11 153751.68 27-JUN-07:40 59.90 0.147007E+12 0.00 0.163895E+12 0.73 10.67 30-JUN-14:20 0.00 0.00
July 0.432075E+11 197710.97 05-JUL-15:40 136.85 0.358565E+12 0.00 0.401772E+12 1.56 10.51 14-JUL-10:00 0.00 0.00
August 0.295494E+11 195866.32 15-AUG-14:40 96.29 0.248191E+12 0.00 0.277741E+12 1.12 10.49 01-AUG-14:05 0.00 0.00
September 0.854932E+10 160188.65 21-SEP-12:52 30.20 0.746865E+11 0.00 0.832359E+11 0.37 10.65 20-SEP-15:40 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.986602E+11     325.58 0.832745E+12 0.00 0.931405E+12 0.32     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.432075E+11 197710.97   136.85 0.358565E+12 0.00 0.401772E+12 1.56 10.67   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.357029E+09 744.00 571.39 11-JAN-16:00 30167.91 12-JAN-16:40 18.54 18.33 15.87
February 0.106205E+10 672.00 2006.27 22-FEB-18:00 65601.86 28-FEB-17:00 19.07 18.33 15.87
March 0.823602E+10 744.00 43776.24 12-MAR-13:00 496288.71 14-MAR-13:05 20.17 18.56 15.87
April 0.104842E+11 720.00 43776.24 07-APR-10:20 413242.64 08-APR-13:20 20.62 18.39 15.87
May 0.231770E+11 744.00 43776.24 09-MAY-11:50 203832.86 10-MAY-15:00 19.37 18.74 15.87
June 0.698732E+11 720.00 43776.24 01-JUN-09:50 621664.91 27-JUN-14:20 23.82 21.21 15.87
July 0.104782E+12 744.00 43776.24 01-JUL-07:00 798821.64 21-JUL-03:02 32.82 25.11 15.87
August 0.101339E+12 744.00 43776.24 01-AUG-00:05 817041.46 13-AUG-16:01 33.61 24.48 15.87
September 0.478401E+11 720.00 43776.24 01-SEP-12:50 264874.21 15-SEP-12:05 20.26 19.54 15.87
October 0.111440E+11 744.00 43776.24 03-OCT-13:05 179464.71 11-OCT-15:00 19.45 18.43 15.87
November 0.764013E+10 720.00 43776.24 04-NOV-13:50 214867.45 05-NOV-14:00 19.84 18.36 15.87
December 0.290385E+10 744.00 6320.38 01-DEC-11:00 185719.46 01-DEC-11:00 20.10 18.33 15.87
                   
Annual Sum or Average 0.388838E+12 8760.00         22.35 19.83 15.87
Minimum of Months 0.357029E+09 672.00 571.39   30167.91   18.54 18.33 15.87
Maximum of Months 0.104782E+12 744.00 43776.24   817041.46   33.61 25.11 15.87



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:03 214976.75 25-JAN-11:10 20.97 20.97 0.09
February 0.00 0.00 0.00 01-FEB-00:03 215174.78 28-FEB-15:20 20.93 20.93 0.09
March 0.718522E+09 32.33 17848.03 14-MAR-10:50 1297260.47 15-MAR-12:50 21.09 20.98 4.35
April 37067691.29 47.50 1028.70 08-APR-13:20 639105.21 19-APR-15:20 21.18 21.06 7.68
May 0.852971E+09 165.85 17848.03 10-MAY-11:00 1277826.87 23-MAY-14:20 21.52 21.15 18.69
June 0.116428E+11 388.38 17848.03 01-JUN-12:50 1275506.70 30-JUN-14:40 22.93 21.71 36.13
July 0.248458E+11 539.66 17848.03 01-JUL-13:50 1422218.36 05-JUL-16:00 24.36 22.54 46.32
August 0.187018E+11 488.32 17848.03 01-AUG-11:50 1371962.80 15-AUG-14:45 23.53 21.89 44.06
September 0.692738E+10 287.62 17848.03 08-SEP-10:30 1261586.98 22-SEP-14:05 22.40 21.58 28.12
October 0.202223E+09 87.83 4439.43 11-OCT-15:00 946306.03 11-OCT-14:40 21.32 21.14 10.87
November 18997725.00 23.25 762.41 16-NOV-13:10 377302.48 16-NOV-13:10 21.05 21.00 4.39
December 0.00 0.00 0.00 01-DEC-00:10 215186.63 04-DEC-07:13 20.96 20.96 0.09
                   
Annual Sum or Average 0.639477E+11 2060.74         21.86 21.33 16.85
Minimum of Months 0.00 0.00 0.00   214976.75   20.93 20.93 0.09
Maximum of Months 0.248458E+11 539.66 17848.03   1422218.36   24.36 22.54 46.32



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 20.97 20.97 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 20.93 20.93 0.00
March 0.112443E+09 1.75 17848.03 14-MAR-12:20 963646.23 15-MAR-14:05 21.09 21.08 0.11
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.18 21.18 0.00
May 0.101734E+09 1.58 17848.03 10-MAY-13:40 887748.15 10-MAY-14:05 21.52 21.51 0.11
June 0.452571E+10 71.28 17848.03 01-JUN-14:30 1199008.75 27-JUN-07:40 22.93 22.58 5.44
July 0.115322E+11 179.48 17848.03 03-JUL-12:05 1422218.36 05-JUL-16:00 24.36 23.49 12.94
August 0.674699E+10 105.43 17848.03 02-AUG-13:05 1371962.80 15-AUG-14:45 23.53 23.01 7.96
September 0.214012E+10 33.45 17848.03 08-SEP-12:50 1130658.17 15-SEP-11:00 22.40 22.24 2.65
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 21.32 21.32 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.05 21.05 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.96 20.96 0.00
                   
Annual Sum or Average 0.251592E+11 392.98         21.86 21.70 2.46
Minimum of Months 0.00 0.00 0.00   0.00   20.93 20.93 0.00
Maximum of Months 0.115322E+11 179.48 17848.03   1422218.36   24.36 23.49 12.94



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.280778E+12 0.00 545.28 1925048.11 02-JAN-04:01 0.00 33.61 69.12 0.59 0.00 0.04 0.81 02-JAN-04:01
February 0.216458E+12 0.00 493.36 1536938.75 14-FEB-06:01 0.00 31.54 68.06 0.50 0.00 0.04 0.65 14-FEB-06:01
March 0.664026E+11 0.00 372.92 1349036.32 21-MAR-04:01 0.00 27.14 53.63 0.13 0.00 0.01 0.57 21-MAR-04:01
April 0.122662E+11 0.00 202.82 1147875.06 17-APR-05:01 0.00 27.08 42.30 0.02 0.00 0.00 0.48 17-APR-05:01
May 0.121995E+10 0.00 43.10 290462.63 11-MAY-13:20 0.00 28.57 31.66 0.00 0.00 0.00 0.12 11-MAY-13:20
June 0.183743E+09 0.00 4.39 266980.70 13-JUN-11:05 0.00 29.29 29.61 0.00 0.00 0.00 0.11 13-JUN-11:05
July 1977.31 0.00 0.17 3.30 02-JUL-23:00 0.00 29.62 29.63 0.00 0.00 0.00 0.00 02-JUL-23:00
August 2015062.53 0.00 0.12 6715.82 31-AUG-11:05 0.00 29.62 29.63 0.00 0.00 0.00 0.00 31-AUG-11:05
September 0.331484E+09 0.00 16.62 95519.61 28-SEP-10:00 0.00 28.43 29.68 0.00 0.00 0.00 0.04 28-SEP-10:00
October 0.995672E+10 0.00 181.15 1180245.45 30-OCT-05:01 0.00 27.94 40.75 0.02 0.00 0.00 0.50 30-OCT-05:01
November 0.377954E+11 0.00 337.61 1271376.51 25-NOV-05:01 0.00 26.23 51.60 0.07 0.00 0.01 0.54 25-NOV-05:01
December 0.210373E+12 0.00 519.47 1578205.58 11-DEC-05:01 0.00 31.39 66.06 0.44 0.00 0.03 0.67 11-DEC-05:01
                           
Annual Sum or Average 0.835767E+12 0.00 2717.01     0.00 29.20 45.03 0.15 0.00 0.01    
Minimum of Months 1977.31 0.00 0.12 3.30   0.00 26.23 29.61 0.00 0.00 0.00 0.00  
Maximum of Months 0.280778E+12 0.00 545.28 1925048.11   0.00 33.61 69.12 0.59 0.00 0.04 0.81  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 18.54 18.54 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 19.07 19.07 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 20.17 20.17 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 20.62 20.62 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 19.37 19.37 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 23.82 23.82 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 32.82 32.82 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 33.61 33.61 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 20.26 20.26 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 19.45 19.45 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 19.84 19.84 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 20.10 20.10 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 22.35 22.35 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 18.54 18.54 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 33.61 33.61 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 11550518.54 0.00 10.46 11550518.54 0.00 0.00 0.00 0.00 8069.66 17-JAN-08:15 8069.66 17-JAN-08:15 0.00 0.00 0.00
February 0.389478E+09 0.00 17.11 0.389478E+09 0.00 0.00 0.00 0.00 25189.58 22-FEB-15:00 25189.58 22-FEB-15:00 0.00 0.00 0.00
March 0.897677E+10 0.00 112.78 0.879373E+10 0.00 0.00 0.00 0.00 105754.51 14-MAR-13:05 100329.84 15-MAR-14:20 0.00 0.00 0.00
April 0.474962E+10 0.00 94.45 0.474962E+10 0.00 0.00 0.00 0.00 52416.76 07-APR-14:00 52416.76 07-APR-14:00 0.00 0.00 0.00
May 0.185430E+11 0.00 222.79 0.183236E+11 0.00 0.00 0.00 0.00 95113.08 10-MAY-14:40 89646.74 23-MAY-14:30 0.00 0.00 0.00
June 0.851655E+11 0.00 437.79 0.677548E+11 0.00 0.00 0.00 0.00 255306.43 27-JUN-07:50 126882.97 27-JUN-16:00 0.00 0.00 0.00
July 0.156732E+12 0.00 584.73 0.113354E+12 0.00 0.00 0.00 0.00 302187.78 21-JUL-05:02 154819.16 21-JUL-04:23 0.00 0.00 0.00
August 0.132182E+12 0.00 569.85 0.103611E+12 0.00 0.00 0.00 0.00 277132.82 15-AUG-08:20 138789.32 08-AUG-16:00 0.00 0.00 0.00
September 0.509929E+11 0.00 325.65 0.406113E+11 0.00 0.00 0.00 0.00 192486.60 14-SEP-04:12 106011.23 21-SEP-15:40 0.00 0.00 0.00
October 0.102865E+11 0.00 142.46 0.102831E+11 0.00 0.00 0.00 0.00 79136.30 11-OCT-15:00 79136.30 11-OCT-15:00 0.00 0.00 0.00
November 0.533096E+10 0.00 126.48 0.533096E+10 0.00 0.00 0.00 0.00 52275.44 27-NOV-06:03 52275.44 27-NOV-06:03 0.00 0.00 0.00
December 0.264578E+09 0.00 25.89 0.264578E+09 0.00 0.00 0.00 0.00 13376.96 04-DEC-14:50 13376.96 04-DEC-14:50 0.00 0.00 0.00
                               
Annual Sum or Average 0.473624E+12 0.00 2670.42 0.373478E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11550518.54 0.00 10.46 11550518.54 0.00 0.00 0.00 0.00 8069.66   8069.66   0.00 0.00 0.00
Maximum of Months 0.156732E+12 0.00 584.73 0.113354E+12 0.00 0.00 0.00 0.00 302187.78   154819.16   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 8897611.50 0.00 8.09 8897611.50 0.00 0.00 0.00 0.00 3639.50 11-JAN-15:10 3639.50 11-JAN-15:10 0.00 0.00 0.00
February 56474678.37 0.00 9.38 56474678.37 0.00 0.00 0.00 0.00 9622.53 28-FEB-15:20 9622.53 28-FEB-15:20 0.00 0.00 0.00
March 0.452818E+11 0.00 96.46 0.440767E+11 0.00 0.00 0.00 0.00 798843.98 15-MAR-14:05 798843.98 15-MAR-14:05 0.00 0.00 0.00
April 0.544718E+11 0.00 130.92 0.544718E+11 0.00 0.00 0.00 0.00 498112.52 19-APR-14:50 498112.52 19-APR-14:50 0.00 0.00 0.00
May 0.167717E+12 0.00 232.86 0.166016E+12 0.00 0.00 0.00 0.00 854582.07 10-MAY-14:40 816226.86 23-MAY-14:30 0.00 0.00 0.00
June 0.646351E+12 0.00 400.02 0.526022E+12 0.00 0.00 0.00 0.00 1692600.57 27-JUN-07:40 1049871.98 12-JUN-04:12 0.00 0.00 0.00
July 0.108265E+13 0.00 458.73 0.811091E+12 0.00 0.00 0.00 0.00 2466925.98 17-JUL-05:02 1369414.31 21-JUL-05:02 0.00 0.00 0.00
August 0.905340E+12 0.00 440.87 0.738184E+12 0.00 0.00 0.00 0.00 2530010.68 14-AUG-05:02 1105566.48 09-AUG-15:20 0.00 0.00 0.00
September 0.412795E+12 0.00 318.91 0.337720E+12 0.00 0.00 0.00 0.00 1547580.92 14-SEP-05:03 976004.59 21-SEP-16:00 0.00 0.00 0.00
October 0.804732E+11 0.00 148.05 0.804242E+11 0.00 0.00 0.00 0.00 645677.67 11-OCT-15:00 645677.67 11-OCT-15:00 0.00 0.00 0.00
November 0.157286E+11 0.00 105.42 0.157286E+11 0.00 0.00 0.00 0.00 281678.55 16-NOV-13:05 281678.55 16-NOV-13:05 0.00 0.00 0.00
December 42848555.41 0.00 18.31 42848555.41 0.00 0.00 0.00 0.00 8116.47 04-DEC-11:10 8116.47 04-DEC-11:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.341092E+13 0.00 2368.00 0.277384E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 8897611.50 0.00 8.09 8897611.50 0.00 0.00 0.00 0.00 3639.50   3639.50   0.00 0.00 0.00
Maximum of Months 0.108265E+13 0.00 458.73 0.811091E+12 0.00 0.00 0.00 0.00 2530010.68   1369414.31   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1117683.74 0.00 7.51 1117683.74 0.00 0.00 0.00 0.00 601.73 02-JAN-07:03 601.73 02-JAN-07:03 0.00 0.00 0.00
February 5331679.48 0.00 7.10 5331679.48 0.00 0.00 0.00 0.00 862.06 28-FEB-15:00 862.06 28-FEB-15:00 0.00 0.00 0.00
March 0.407671E+10 0.00 98.46 0.407559E+10 0.00 0.00 0.00 0.00 93787.89 15-MAR-14:20 93787.89 15-MAR-14:20 0.00 0.00 0.00
April 0.150635E+10 0.00 95.50 0.150635E+10 0.00 0.00 0.00 0.00 35456.09 07-APR-14:00 35456.09 07-APR-14:00 0.00 0.00 0.00
May 0.156220E+11 0.00 213.78 0.154989E+11 0.00 0.00 0.00 0.00 100957.35 14-MAY-15:02 93734.94 10-MAY-14:30 0.00 0.00 0.00
June 0.699716E+11 0.00 396.05 0.568114E+11 0.00 0.00 0.00 0.00 173036.85 27-JUN-05:03 129278.85 12-JUN-14:00 0.00 0.00 0.00
July 0.119770E+12 0.00 458.92 0.899215E+11 0.00 0.00 0.00 0.00 308070.74 21-JUL-05:02 137826.71 21-JUL-03:02 0.00 0.00 0.00
August 0.981338E+11 0.00 435.49 0.796226E+11 0.00 0.00 0.00 0.00 272971.29 14-AUG-05:02 133696.19 09-AUG-15:30 0.00 0.00 0.00
September 0.399541E+11 0.00 310.35 0.325316E+11 0.00 0.00 0.00 0.00 168837.85 15-SEP-13:10 113066.24 21-SEP-15:50 0.00 0.00 0.00
October 0.445403E+10 0.00 128.67 0.445403E+10 0.00 0.00 0.00 0.00 62207.58 11-OCT-15:00 62207.58 11-OCT-15:00 0.00 0.00 0.00
November 0.554335E+09 0.00 101.99 0.554335E+09 0.00 0.00 0.00 0.00 12134.76 16-NOV-13:00 12134.76 16-NOV-13:00 0.00 0.00 0.00
December 4194387.81 0.00 18.01 4194387.81 0.00 0.00 0.00 0.00 421.65 04-DEC-11:00 421.65 04-DEC-11:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.354053E+12 0.00 2271.83 0.284987E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1117683.74 0.00 7.10 1117683.74 0.00 0.00 0.00 0.00 421.65   421.65   0.00 0.00 0.00
Maximum of Months 0.119770E+12 0.00 458.92 0.899215E+11 0.00 0.00 0.00 0.00 308070.74   137826.71   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 41389778.29 0.00 4.00 41389778.29 0.00 0.00 0.00 0.00 5270.03 11-JAN-16:00 5270.03 11-JAN-16:00 0.00 0.00 0.00
February 38811114.69 0.00 4.17 38811114.69 0.00 0.00 0.00 0.00 6068.56 22-FEB-17:00 6068.56 22-FEB-17:00 0.00 0.00 0.00
March 0.390107E+10 0.00 42.37 0.388490E+10 0.00 0.00 0.00 0.00 55155.19 15-MAR-14:00 55155.19 15-MAR-14:00 0.00 0.00 0.00
April 0.153861E+10 0.00 42.83 0.153861E+10 0.00 0.00 0.00 0.00 27505.39 07-APR-13:20 27505.39 07-APR-13:20 0.00 0.00 0.00
May 0.121745E+11 0.00 180.00 0.115031E+11 0.00 0.00 0.00 0.00 85701.42 24-MAY-06:25 52973.97 10-MAY-14:00 0.00 0.00 0.00
June 0.319718E+11 0.00 233.76 0.249510E+11 0.00 0.00 0.00 0.00 124828.76 28-JUN-14:20 84173.60 28-JUN-15:20 0.00 0.00 0.00
July 0.532899E+11 0.00 210.56 0.393413E+11 0.00 0.00 0.00 0.00 173433.53 29-JUL-10:53 86287.24 24-JUL-12:20 0.00 0.00 0.00
August 0.564729E+11 0.00 284.19 0.463323E+11 0.00 0.00 0.00 0.00 136451.30 28-AUG-12:05 92416.01 09-AUG-14:00 0.00 0.00 0.00
September 0.331419E+11 0.00 241.75 0.261229E+11 0.00 0.00 0.00 0.00 133426.63 14-SEP-16:00 68850.36 25-SEP-12:05 0.00 0.00 0.00
October 0.555058E+10 0.00 92.05 0.529696E+10 0.00 0.00 0.00 0.00 73083.92 26-OCT-06:25 49951.00 11-OCT-13:10 0.00 0.00 0.00
November 0.877442E+09 0.00 19.59 0.873236E+09 0.00 0.00 0.00 0.00 55196.25 27-NOV-07:11 55196.25 27-NOV-07:11 0.00 0.00 0.00
December 6140035.17 0.00 0.17 5949607.27 0.00 0.00 0.00 0.00 17374.01 01-DEC-07:13 16395.00 01-DEC-07:13 0.00 0.00 0.00
                               
Annual Sum or Average 0.199005E+12 0.00 1355.44 0.159930E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 6140035.17 0.00 0.17 5949607.27 0.00 0.00 0.00 0.00 5270.03   5270.03   0.00 0.00 0.00
Maximum of Months 0.564729E+11 0.00 284.19 0.463323E+11 0.00 0.00 0.00 0.00 173433.53   92416.01   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.656980E+10 0.425978E+10 739.67 0.656975E+10 46674.08 0.00 0.02 13-JAN-18:00 0.01 11-JAN-18:10 3825.74 13-JAN-18:00 3825.74 13-JAN-18:00 18.18 11-JAN-18:40 1941.07 13-JAN-18:00 0.00
February 0.102825E+11 0.503325E+10 672.00 0.102722E+11 10314106.28 0.00 0.02 22-FEB-18:00 0.01 01-FEB-05:11 5069.26 14-FEB-17:15 5069.26 14-FEB-17:15 87.67 01-FEB-08:00 2335.14 22-FEB-18:00 0.00
March 0.314528E+11 0.112696E+11 681.04 0.283874E+11 0.306541E+10 0.00 0.70 14-MAR-13:00 0.01 11-MAR-01:10 313928.95 14-MAR-13:00 288759.86 15-MAR-14:00 86435.32 14-MAR-11:00 86928.16 14-MAR-13:00 0.00
April 0.364164E+11 0.125096E+11 687.78 0.339235E+11 0.249295E+10 0.00 0.58 08-APR-13:00 0.01 30-APR-19:17 234047.96 08-APR-14:00 228179.82 08-APR-13:00 33663.45 08-APR-17:55 64592.83 08-APR-13:00 0.00
May 0.723110E+10 0.471073E+10 531.76 0.677721E+10 0.453885E+09 0.00 0.30 10-MAY-15:00 0.01 13-MAY-22:50 124780.53 10-MAY-15:00 105356.98 10-MAY-15:00 19441.44 14-MAY-13:53 36795.66 10-MAY-15:00 0.00
June 0.166936E+12 0.476443E+11 548.31 0.118666E+12 0.482707E+11 0.00 0.84 27-JUN-14:05 0.01 25-JUN-06:50 432272.86 27-JUN-14:05 226853.25 27-JUN-13:00 222937.49 27-JUN-15:00 111447.70 27-JUN-14:10 0.00
July 0.711245E+12 0.185580E+12 695.84 0.442307E+12 0.268938E+12 0.00 1.00 08-JUL-13:50 0.01 12-JUL-06:22 543995.15 20-JUL-22:13 345375.08 16-JUL-09:31 355306.61 20-JUL-22:00 141614.75 21-JUL-02:50 0.00
August 0.826201E+12 0.214316E+12 709.02 0.554696E+12 0.271505E+12 0.00 1.00 06-AUG-17:42 0.01 02-AUG-04:53 527717.42 14-AUG-00:53 428594.08 10-AUG-12:53 326793.33 25-AUG-19:00 144407.42 13-AUG-15:00 0.00
September 0.150678E+11 0.728209E+10 368.38 0.112554E+11 0.381243E+10 0.00 0.39 15-SEP-12:00 0.01 02-SEP-22:40 177632.62 15-SEP-12:00 131353.14 16-SEP-13:00 71365.74 15-SEP-12:00 48880.06 16-SEP-14:30 0.00
October 0.854372E+10 0.496625E+10 577.35 0.822278E+10 0.320943E+09 0.00 0.23 11-OCT-15:00 0.00 10-OCT-23:50 88289.70 11-OCT-15:00 81952.95 11-OCT-14:00 9107.28 22-OCT-12:53 25668.57 11-OCT-15:00 0.00
November 0.172421E+11 0.714028E+10 702.81 0.159210E+11 0.132107E+10 0.00 0.27 05-NOV-14:00 0.01 04-NOV-12:20 104722.61 05-NOV-13:55 85768.31 05-NOV-13:55 19838.12 05-NOV-14:25 28070.31 05-NOV-14:00 0.00
December 0.150363E+11 0.697884E+10 742.14 0.146524E+11 0.383869E+09 0.00 0.18 01-DEC-11:00 0.01 01-DEC-07:30 67559.13 01-DEC-11:00 45291.36 01-DEC-11:00 22267.77 01-DEC-11:00 17849.11 01-DEC-11:00 0.00
                                       
Annual Sum or Average 0.185223E+13 0.511691E+12 7656.10 0.125165E+13 0.600575E+12 0.00                         0.00
Minimum of Months 0.656980E+10 0.425978E+10 368.38 0.656975E+10 46674.08 0.00 0.02   0.00   3825.74   3825.74   18.18   1941.07   0.00
Maximum of Months 0.826201E+12 0.214316E+12 742.14 0.554696E+12 0.271505E+12 0.00 1.00   0.01   543995.15   428594.08   355306.61   144407.42   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.312890E+10 0.803230E+09 744.00 0.312860E+10 294138.99 0.00 0.28 15-JAN-16:35 0.04 30-JAN-07:03 2202.93 15-JAN-16:35 2202.93 15-JAN-16:35 10.30 02-JAN-07:03 524.09 15-JAN-16:35 0.00
February 0.778657E+10 0.185230E+10 672.00 0.778657E+10 -0.0 0.00 0.52 28-FEB-17:00 0.30 06-FEB-07:03 4203.69 28-FEB-17:00 4203.69 28-FEB-17:00 0.00 23-FEB-09:30 965.09 28-FEB-17:00 0.00
March 0.148841E+11 0.328320E+10 744.00 0.148628E+11 21298719.46 0.00 0.83 25-MAR-17:55 0.58 01-MAR-07:03 7553.87 31-MAR-24:00 7553.87 31-MAR-24:00 266.71 16-MAR-15:40 1738.23 15-MAR-14:05 0.00
April 0.197920E+11 0.407007E+10 720.00 0.197891E+11 2912362.76 0.00 0.96 02-APR-17:55 0.30 30-APR-23:55 8755.97 02-APR-17:55 8755.97 02-APR-17:55 99.05 12-APR-16:10 1841.53 07-APR-14:00 0.00
May 0.558575E+10 0.130650E+10 744.00 0.555033E+10 35424135.62 0.00 0.46 31-MAY-24:00 0.19 12-MAY-06:10 4026.73 31-MAY-24:00 4026.73 31-MAY-24:00 221.05 17-MAY-15:20 857.40 31-MAY-24:00 0.00
June 0.108868E+11 0.255962E+10 720.00 0.107049E+11 0.181900E+09 0.00 0.67 30-JUN-24:00 0.42 10-JUN-06:40 5944.43 30-JUN-24:00 5944.43 30-JUN-24:00 482.17 27-JUN-14:00 1509.71 27-JUN-13:00 0.00
July 0.166302E+11 0.418324E+10 744.00 0.163163E+11 0.313866E+09 0.00 0.86 31-JUL-23:20 0.63 07-JUL-06:40 7880.61 31-JUL-24:00 7841.22 31-JUL-24:00 482.41 20-JUL-14:40 2160.98 21-JUL-14:00 0.00
August 0.214771E+11 0.514032E+10 744.00 0.212387E+11 0.238322E+09 0.00 1.00 13-AUG-15:21 0.29 31-AUG-24:00 8788.70 14-AUG-15:50 8744.36 04-AUG-18:40 474.27 14-AUG-10:00 2687.58 13-AUG-15:12 0.00
September 0.570663E+10 0.133541E+10 720.00 0.557413E+10 0.132502E+09 0.00 0.45 30-SEP-24:00 0.18 30-SEP-06:45 3792.95 30-SEP-24:00 3792.95 30-SEP-24:00 341.15 15-SEP-15:20 825.69 30-SEP-24:00 0.00
October 0.103083E+11 0.225965E+10 744.00 0.102776E+11 30673272.34 0.00 0.64 31-OCT-24:00 0.39 30-OCT-06:05 5719.02 31-OCT-24:00 5719.02 31-OCT-24:00 184.76 12-OCT-15:30 1183.36 31-OCT-24:00 0.00
November 0.145502E+11 0.311737E+10 720.00 0.145482E+11 2022490.50 0.00 0.73 26-NOV-14:00 0.59 15-NOV-07:05 6072.37 15-NOV-16:20 6072.37 15-NOV-16:20 144.08 16-NOV-16:20 1395.55 26-NOV-14:00 0.00
December 0.194012E+11 0.415544E+10 744.00 0.194007E+11 501643.61 0.00 0.90 10-DEC-16:03 0.76 11-DEC-07:03 7846.97 17-DEC-16:10 7846.97 17-DEC-16:10 88.07 01-DEC-13:30 1660.74 10-DEC-16:03 0.00
                                       
Annual Sum or Average 0.150138E+12 0.340664E+11 8760.00 0.149178E+12 0.959717E+09 0.00                         0.00
Minimum of Months 0.312890E+10 0.803230E+09 672.00 0.312860E+10 -0.0 0.00 0.28   0.04   2202.93   2202.93   0.00   524.09   0.00
Maximum of Months 0.214771E+11 0.514032E+10 744.00 0.212387E+11 0.313866E+09 0.00 1.00   0.76   8788.70   8755.97   482.41   2687.58   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.543361E+10 0.160871E+10 443.77 0.543358E+10 31911.24 0.00 0.21 12-JAN-16:50 0.00 01-JAN-00:03 14825.06 12-JAN-16:50 14825.06 12-JAN-16:50 17.62 11-JAN-18:10 3745.53 12-JAN-16:50 0.00
February 0.494842E+11 0.121758E+11 672.00 0.494842E+11 -0.0 0.00 0.48 28-FEB-17:00 0.12 06-FEB-07:03 36849.82 28-FEB-17:00 36849.82 28-FEB-17:00 0.00 04-FEB-06:06 8539.83 28-FEB-17:00 0.00
March 0.126105E+12 0.281971E+11 744.00 0.125892E+12 0.212743E+09 0.00 0.80 25-MAR-17:55 0.43 06-MAR-07:03 67936.13 31-MAR-23:40 67936.13 31-MAR-23:40 2627.41 16-MAR-15:40 16477.31 15-MAR-14:05 0.00
April 0.179571E+12 0.372122E+11 720.00 0.179540E+12 30582603.64 0.00 0.93 22-APR-18:23 0.23 30-APR-23:55 80484.82 02-APR-18:00 80484.82 02-APR-18:00 991.67 12-APR-16:10 17461.74 07-APR-14:00 0.00
May 0.487521E+11 0.114959E+11 744.00 0.484021E+11 0.350044E+09 0.00 0.46 31-MAY-24:00 0.13 01-MAY-06:05 38152.36 31-MAY-24:00 38152.36 31-MAY-24:00 2170.36 17-MAY-15:20 8135.70 31-MAY-24:00 0.00
June 0.101461E+12 0.239458E+11 720.00 0.996523E+11 0.180825E+10 0.00 0.67 30-JUN-24:00 0.39 14-JUN-06:05 56675.14 30-JUN-24:00 56675.14 30-JUN-24:00 4767.22 27-JUN-14:00 14349.71 27-JUN-13:00 0.00
July 0.157261E+12 0.396426E+11 744.00 0.154136E+12 0.312553E+10 0.00 0.86 31-JUL-23:20 0.61 06-JUL-06:20 75673.10 31-JUL-24:00 75289.22 31-JUL-24:00 4805.92 20-JUL-14:40 20441.12 21-JUL-14:00 0.00
August 0.203456E+12 0.487980E+11 744.00 0.201079E+12 0.237684E+10 0.00 0.99 04-AUG-18:40 0.24 31-AUG-24:00 83926.86 04-AUG-18:40 83926.86 04-AUG-18:40 4725.02 14-AUG-10:00 25202.64 13-AUG-15:21 0.00
September 0.498360E+11 0.117674E+11 720.00 0.485340E+11 0.130200E+10 0.00 0.41 30-SEP-24:00 0.13 30-SEP-06:55 33165.80 30-SEP-24:00 33165.80 30-SEP-24:00 3363.66 15-SEP-15:20 7583.42 21-SEP-17:00 0.00
October 0.871519E+11 0.193243E+11 744.00 0.868448E+11 0.307110E+09 0.00 0.60 31-OCT-23:40 0.28 30-OCT-06:05 50836.09 31-OCT-23:40 50836.09 31-OCT-23:40 1837.86 12-OCT-15:30 10915.53 11-OCT-17:00 0.00
November 0.121261E+12 0.263923E+11 720.00 0.121239E+12 22062379.09 0.00 0.67 15-NOV-16:20 0.47 24-NOV-07:03 56275.49 15-NOV-16:20 56275.49 15-NOV-16:20 1433.57 16-NOV-16:10 11926.41 16-NOV-13:00 0.00
December 0.155227E+12 0.340358E+11 744.00 0.155222E+12 5763976.51 0.00 0.84 04-DEC-16:20 0.58 11-DEC-07:03 69826.01 04-DEC-16:20 69826.01 04-DEC-16:20 904.54 01-DEC-13:30 14912.89 04-DEC-16:20 0.00
                                       
Annual Sum or Average 0.128500E+13 0.294596E+12 8459.77 0.127546E+13 0.954097E+10 0.00                         0.00
Minimum of Months 0.543361E+10 0.160871E+10 443.77 0.543358E+10 -0.0 0.00 0.21   0.00   14825.06   14825.06   0.00   3745.53   0.00
Maximum of Months 0.203456E+12 0.487980E+11 744.00 0.201079E+12 0.312553E+10 0.00 0.99   0.61   83926.86   83926.86   4805.92   25202.64   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 96147635.28 29286744.75 92.34 96147635.28 0.00 0.00 0.18 12-JAN-16:40 0.00 01-JAN-00:03 1264.02 12-JAN-16:40 1264.02 12-JAN-16:40 0.00 20-JAN-22:18 324.50 12-JAN-16:40 0.00
February 0.328890E+10 0.829128E+09 644.97 0.328890E+10 0.00 0.00 0.47 28-FEB-17:00 0.00 01-FEB-00:03 3629.23 28-FEB-17:00 3629.23 28-FEB-17:00 0.00 10-FEB-01:30 843.67 28-FEB-17:00 0.00
March 0.110070E+11 0.249476E+10 744.00 0.109859E+11 21152198.99 0.00 0.75 25-MAR-17:42 0.26 06-MAR-04:01 6368.10 31-MAR-23:20 6368.10 31-MAR-23:20 262.75 16-MAR-15:40 1668.69 15-MAR-14:05 0.00
April 0.169121E+11 0.353692E+10 720.00 0.169091E+11 2993998.49 0.00 0.91 22-APR-18:15 0.17 30-APR-23:55 7947.10 09-APR-17:57 7947.10 09-APR-17:57 98.54 12-APR-16:10 1756.69 07-APR-14:00 0.00
May 0.445542E+10 0.105952E+10 744.00 0.442072E+10 34705434.24 0.00 0.44 31-MAY-23:40 0.04 01-MAY-06:05 3726.44 31-MAY-23:40 3726.44 31-MAY-23:40 216.69 17-MAY-15:20 797.68 31-MAY-23:40 0.00
June 0.100764E+11 0.238740E+10 720.00 0.989549E+10 0.180879E+09 0.00 0.65 30-JUN-23:40 0.33 14-JUN-06:05 5601.74 30-JUN-23:40 5601.74 30-JUN-23:40 479.49 27-JUN-14:00 1461.00 27-JUN-13:00 0.00
July 0.157813E+11 0.398842E+10 744.00 0.154688E+11 0.312493E+09 0.00 0.85 31-JUL-23:20 0.58 07-JUL-06:20 7560.96 31-JUL-24:00 7522.35 31-JUL-24:00 480.90 20-JUL-14:40 2076.89 21-JUL-14:00 0.00
August 0.203241E+11 0.489143E+10 744.00 0.200867E+11 0.237416E+09 0.00 0.99 13-AUG-15:52 0.21 31-AUG-24:00 8474.26 04-AUG-18:40 8474.26 04-AUG-18:40 472.36 14-AUG-10:00 2587.88 13-AUG-15:41 0.00
September 0.461874E+10 0.110109E+10 720.00 0.448911E+10 0.129623E+09 0.00 0.37 04-SEP-17:44 0.05 30-SEP-06:55 3038.18 04-SEP-17:42 3038.18 04-SEP-17:50 338.04 15-SEP-15:20 776.44 21-SEP-17:00 0.00
October 0.737969E+10 0.165812E+10 744.00 0.734931E+10 30376159.79 0.00 0.55 31-OCT-23:20 0.13 30-OCT-06:05 4680.70 31-OCT-23:20 4680.70 31-OCT-23:20 184.05 12-OCT-15:30 1099.99 11-OCT-17:00 0.00
November 0.103265E+11 0.228568E+10 720.00 0.103244E+11 2083452.05 0.00 0.65 03-NOV-16:00 0.30 24-NOV-04:15 5503.03 15-NOV-16:20 5503.03 15-NOV-16:20 140.64 16-NOV-16:20 1168.33 16-NOV-17:00 0.00
December 0.135386E+11 0.301926E+10 744.00 0.135381E+11 542611.93 0.00 0.80 04-DEC-16:20 0.43 26-DEC-04:01 6636.26 04-DEC-16:20 6636.26 04-DEC-16:20 85.85 01-DEC-13:30 1429.90 04-DEC-16:20 0.00
                                       
Annual Sum or Average 0.117805E+12 0.272810E+11 8081.31 0.116853E+12 0.952265E+09 0.00                         0.00
Minimum of Months 96147635.28 29286744.75 92.34 96147635.28 0.00 0.00 0.18   0.00   1264.02   1264.02   0.00   324.50   0.00
Maximum of Months 0.203241E+11 0.489143E+10 744.00 0.200867E+11 0.312493E+09 0.00 0.99   0.58   8474.26   8474.26   480.90   2587.88   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.06 0.00 128.06 0.02 852.12 0.00 0.00 0.00
February 195.11 0.00 195.11 5.22 801.08 0.00 0.00 0.00
March 236.61 0.00 236.61 61.97 592.04 0.00 0.00 0.00
April 301.50 1.20 300.29 140.87 426.45 0.00 0.00 0.00
May 350.32 14.86 335.47 264.43 256.48 0.00 0.00 0.00
June 421.37 35.87 385.50 447.26 163.78 0.00 0.00 0.00
July 390.87 25.23 365.64 479.61 114.26 0.00 0.00 0.00
August 338.21 5.15 333.07 391.03 151.27 0.00 0.00 0.00
September 257.39 0.05 257.33 225.90 253.56 0.00 0.00 0.00
October 192.41 0.00 192.41 78.30 425.45 0.00 0.00 0.00
November 129.29 0.00 129.29 16.93 572.47 0.00 0.00 0.00
December 119.86 0.00 119.86 0.58 840.89 0.00 0.00 0.00
                 
Annual Sum or Average 255.33 6.89 248.44 177.07 452.40 0.00 0.00 0.00
Minimum of Months 119.86 0.00 119.86 0.02 114.26 0.00 0.00 0.00
Maximum of Months 421.37 35.87 385.50 479.61 852.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.06 0.00 128.06 0.02 852.12 0.00 0.00 0.00
February 195.11 0.00 195.11 5.22 801.08 0.00 0.00 0.00
March 236.61 0.00 236.61 61.97 592.04 0.00 0.00 0.00
April 301.50 1.20 300.29 140.87 426.45 0.00 0.00 0.00
May 350.32 14.86 335.47 264.43 256.48 0.00 0.00 0.00
June 421.36 35.87 385.50 447.26 163.78 0.00 0.00 0.00
July 390.87 25.23 365.64 479.61 114.26 0.00 0.00 0.00
August 338.21 5.15 333.07 391.03 151.27 0.00 0.00 0.00
September 257.39 0.05 257.33 225.90 253.56 0.00 0.00 0.00
October 192.41 0.00 192.41 78.30 425.45 0.00 0.00 0.00
November 129.29 0.00 129.29 16.93 572.47 0.00 0.00 0.00
December 119.86 0.00 119.86 0.58 840.89 0.00 0.00 0.00
                 
Annual Sum or Average 255.33 6.89 248.44 177.07 452.40 0.00 0.00 0.00
Minimum of Months 119.86 0.00 119.86 0.02 114.26 0.00 0.00 0.00
Maximum of Months 421.36 35.87 385.50 479.61 852.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.06 0.00 128.06 0.02 852.12 0.00 0.00 0.00
February 195.11 0.00 195.11 5.22 801.08 0.00 0.00 0.00
March 236.61 0.00 236.61 61.97 592.04 0.00 0.00 0.00
April 301.50 1.20 300.29 140.87 426.45 0.00 0.00 0.00
May 350.32 14.86 335.47 264.43 256.48 0.00 0.00 0.00
June 421.37 35.87 385.50 447.26 163.78 0.00 0.00 0.00
July 390.87 25.23 365.64 479.61 114.26 0.00 0.00 0.00
August 338.21 5.15 333.07 391.03 151.27 0.00 0.00 0.00
September 257.39 0.05 257.33 225.90 253.56 0.00 0.00 0.00
October 192.41 0.00 192.41 78.30 425.45 0.00 0.00 0.00
November 129.29 0.00 129.29 16.93 572.47 0.00 0.00 0.00
December 119.86 0.00 119.86 0.58 840.89 0.00 0.00 0.00
                 
Annual Sum or Average 255.33 6.89 248.44 177.07 452.40 0.00 0.00 0.00
Minimum of Months 119.86 0.00 119.86 0.02 114.26 0.00 0.00 0.00
Maximum of Months 421.37 35.87 385.50 479.61 852.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.06 0.00 128.06 0.02 852.12 0.00 0.00 0.00
February 195.11 0.00 195.11 5.22 801.08 0.00 0.00 0.00
March 236.61 0.00 236.61 61.97 592.04 0.00 0.00 0.00
April 301.50 1.20 300.29 140.87 426.45 0.00 0.00 0.00
May 350.32 14.86 335.47 264.43 256.48 0.00 0.00 0.00
June 421.36 35.87 385.50 447.26 163.78 0.00 0.00 0.00
July 390.87 25.23 365.64 479.61 114.26 0.00 0.00 0.00
August 338.21 5.15 333.07 391.03 151.27 0.00 0.00 0.00
September 257.39 0.05 257.33 225.90 253.56 0.00 0.00 0.00
October 192.41 0.00 192.41 78.30 425.45 0.00 0.00 0.00
November 129.29 0.00 129.29 16.93 572.47 0.00 0.00 0.00
December 119.86 0.00 119.86 0.58 840.89 0.00 0.00 0.00
                 
Annual Sum or Average 255.33 6.89 248.44 177.07 452.40 0.00 0.00 0.00
Minimum of Months 119.86 0.00 119.86 0.02 114.26 0.00 0.00 0.00
Maximum of Months 421.36 35.87 385.50 479.61 852.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.05 0.00 128.05 0.02 852.08 0.00 0.00 0.00
February 195.10 0.00 195.10 5.22 801.05 0.00 0.00 0.00
March 236.61 0.00 236.61 61.97 592.02 0.00 0.00 0.00
April 301.48 1.20 300.28 140.86 426.43 0.00 0.00 0.00
May 350.31 14.86 335.45 264.42 256.47 0.00 0.00 0.00
June 421.35 35.87 385.48 447.24 163.78 0.00 0.00 0.00
July 390.86 25.23 365.63 479.59 114.25 0.00 0.00 0.00
August 338.20 5.14 333.05 391.02 151.27 0.00 0.00 0.00
September 257.38 0.05 257.32 225.89 253.55 0.00 0.00 0.00
October 192.40 0.00 192.40 78.30 425.44 0.00 0.00 0.00
November 129.29 0.00 129.29 16.93 572.45 0.00 0.00 0.00
December 119.85 0.00 119.85 0.58 840.85 0.00 0.00 0.00
                 
Annual Sum or Average 255.32 6.89 248.43 177.06 452.38 0.00 0.00 0.00
Minimum of Months 119.85 0.00 119.85 0.02 114.25 0.00 0.00 0.00
Maximum of Months 421.35 35.87 385.48 479.59 852.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 260.38 83.96 176.42 92.59 861.37 0.00 0.00 0.00
February 382.06 114.65 267.41 165.34 811.58 0.00 0.00 0.00
March 548.24 229.60 318.64 409.64 597.39 0.00 0.00 0.00
April 725.63 320.62 405.01 662.23 435.78 0.00 0.00 0.00
May 812.97 359.62 453.35 874.26 287.48 0.00 0.00 0.00
June 907.95 401.27 506.68 1098.06 183.42 0.00 0.00 0.00
July 871.87 383.87 488.00 1132.97 125.18 0.00 0.00 0.00
August 787.40 330.51 456.89 1002.02 161.89 0.00 0.00 0.00
September 655.25 290.64 364.61 748.96 267.93 0.00 0.00 0.00
October 444.64 183.92 260.73 380.79 438.39 0.00 0.00 0.00
November 252.21 80.91 171.30 140.16 591.09 0.00 0.00 0.00
December 203.04 41.95 161.09 45.76 858.70 0.00 0.00 0.00
                 
Annual Sum or Average 571.82 235.70 336.12 564.91 466.61 0.00 0.00 0.00
Minimum of Months 203.04 41.95 161.09 45.76 125.18 0.00 0.00 0.00
Maximum of Months 907.95 401.27 506.68 1132.97 861.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 260.38 83.96 176.42 92.59 861.37 0.00 0.00 0.00
February 382.06 114.65 267.41 165.34 811.58 0.00 0.00 0.00
March 548.24 229.60 318.64 409.64 597.39 0.00 0.00 0.00
April 725.63 320.62 405.01 662.23 435.78 0.00 0.00 0.00
May 812.97 359.62 453.35 874.26 287.48 0.00 0.00 0.00
June 907.95 401.27 506.68 1098.06 183.42 0.00 0.00 0.00
July 871.87 383.87 488.00 1132.97 125.18 0.00 0.00 0.00
August 787.40 330.51 456.89 1002.02 161.89 0.00 0.00 0.00
September 655.25 290.64 364.61 748.96 267.93 0.00 0.00 0.00
October 444.64 183.92 260.73 380.79 438.39 0.00 0.00 0.00
November 252.21 80.91 171.30 140.16 591.09 0.00 0.00 0.00
December 203.04 41.95 161.09 45.76 858.70 0.00 0.00 0.00
                 
Annual Sum or Average 571.82 235.70 336.12 564.91 466.61 0.00 0.00 0.00
Minimum of Months 203.04 41.95 161.09 45.76 125.18 0.00 0.00 0.00
Maximum of Months 907.95 401.27 506.68 1132.97 861.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 260.38 83.96 176.42 92.59 861.35 0.00 0.00 0.00
February 382.05 114.64 267.41 165.34 811.56 0.00 0.00 0.00
March 548.23 229.60 318.64 409.63 597.38 0.00 0.00 0.00
April 725.62 320.62 405.00 662.22 435.77 0.00 0.00 0.00
May 812.96 359.61 453.34 874.24 287.48 0.00 0.00 0.00
June 907.93 401.26 506.67 1098.04 183.42 0.00 0.00 0.00
July 871.85 383.87 487.99 1132.95 125.18 0.00 0.00 0.00
August 787.38 330.50 456.88 1002.01 161.88 0.00 0.00 0.00
September 655.24 290.64 364.60 748.94 267.92 0.00 0.00 0.00
October 444.63 183.91 260.72 380.78 438.39 0.00 0.00 0.00
November 252.20 80.90 171.30 140.16 591.08 0.00 0.00 0.00
December 203.04 41.95 161.09 45.76 858.68 0.00 0.00 0.00
                 
Annual Sum or Average 571.81 235.69 336.11 564.90 466.60 0.00 0.00 0.00
Minimum of Months 203.04 41.95 161.09 45.76 125.18 0.00 0.00 0.00
Maximum of Months 907.93 401.26 506.67 1132.95 861.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 550.65 321.43 229.22 434.80 706.70 0.00 0.00 0.00
February 628.70 303.15 325.55 487.57 692.90 0.00 0.00 0.00
March 767.37 431.18 336.19 739.30 527.72 0.00 0.00 0.00
April 635.51 253.95 381.56 637.07 422.92 0.00 0.00 0.00
May 556.12 161.52 394.60 613.45 278.84 0.00 0.00 0.00
June 540.37 114.51 425.87 667.13 179.93 0.00 0.00 0.00
July 551.63 133.84 417.79 752.78 124.25 0.00 0.00 0.00
August 619.30 200.79 418.51 832.57 160.31 0.00 0.00 0.00
September 720.06 350.72 369.34 894.37 255.20 0.00 0.00 0.00
October 688.99 393.56 295.43 734.18 393.48 0.00 0.00 0.00
November 493.44 278.56 214.88 454.36 509.23 0.00 0.00 0.00
December 460.45 238.30 222.15 340.16 709.95 0.00 0.00 0.00
                 
Annual Sum or Average 600.86 264.99 335.88 633.16 411.94 0.00 0.00 0.00
Minimum of Months 460.45 114.51 214.88 340.16 124.25 0.00 0.00 0.00
Maximum of Months 767.37 431.18 425.87 894.37 709.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 550.65 321.43 229.22 434.80 706.70 0.00 0.00 0.00
February 628.70 303.15 325.55 487.57 692.90 0.00 0.00 0.00
March 767.37 431.18 336.19 739.30 527.72 0.00 0.00 0.00
April 635.50 253.95 381.56 637.07 422.92 0.00 0.00 0.00
May 556.12 161.52 394.60 613.45 278.84 0.00 0.00 0.00
June 540.37 114.51 425.86 667.13 179.93 0.00 0.00 0.00
July 551.63 133.84 417.79 752.78 124.25 0.00 0.00 0.00
August 619.30 200.79 418.51 832.56 160.31 0.00 0.00 0.00
September 720.06 350.72 369.34 894.37 255.20 0.00 0.00 0.00
October 688.99 393.56 295.43 734.18 393.48 0.00 0.00 0.00
November 493.44 278.56 214.88 454.36 509.23 0.00 0.00 0.00
December 460.45 238.30 222.15 340.16 709.95 0.00 0.00 0.00
                 
Annual Sum or Average 600.86 264.99 335.88 633.16 411.94 0.00 0.00 0.00
Minimum of Months 460.45 114.51 214.88 340.16 124.25 0.00 0.00 0.00
Maximum of Months 767.37 431.18 425.86 894.37 709.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 550.65 321.43 229.22 434.80 706.70 0.00 0.00 0.00
February 628.70 303.15 325.55 487.57 692.90 0.00 0.00 0.00
March 767.37 431.18 336.19 739.30 527.72 0.00 0.00 0.00
April 635.51 253.95 381.56 637.07 422.92 0.00 0.00 0.00
May 556.12 161.52 394.60 613.45 278.84 0.00 0.00 0.00
June 540.37 114.51 425.87 667.13 179.93 0.00 0.00 0.00
July 551.63 133.84 417.79 752.78 124.25 0.00 0.00 0.00
August 619.30 200.79 418.51 832.57 160.31 0.00 0.00 0.00
September 720.06 350.72 369.34 894.37 255.20 0.00 0.00 0.00
October 688.99 393.56 295.43 734.18 393.48 0.00 0.00 0.00
November 493.44 278.56 214.88 454.36 509.23 0.00 0.00 0.00
December 460.45 238.30 222.15 340.16 709.95 0.00 0.00 0.00
                 
Annual Sum or Average 600.86 264.99 335.88 633.16 411.94 0.00 0.00 0.00
Minimum of Months 460.45 114.51 214.88 340.16 124.25 0.00 0.00 0.00
Maximum of Months 767.37 431.18 425.87 894.37 709.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 550.65 321.43 229.22 434.80 706.70 0.00 0.00 0.00
February 628.70 303.15 325.55 487.57 692.90 0.00 0.00 0.00
March 767.37 431.18 336.19 739.30 527.72 0.00 0.00 0.00
April 635.50 253.95 381.56 637.07 422.92 0.00 0.00 0.00
May 556.12 161.52 394.60 613.45 278.84 0.00 0.00 0.00
June 540.37 114.51 425.86 667.13 179.93 0.00 0.00 0.00
July 551.63 133.84 417.79 752.78 124.25 0.00 0.00 0.00
August 619.30 200.79 418.51 832.56 160.31 0.00 0.00 0.00
September 720.06 350.72 369.34 894.37 255.20 0.00 0.00 0.00
October 688.99 393.56 295.43 734.18 393.48 0.00 0.00 0.00
November 493.44 278.56 214.88 454.36 509.23 0.00 0.00 0.00
December 460.45 238.30 222.15 340.16 709.95 0.00 0.00 0.00
                 
Annual Sum or Average 600.86 264.99 335.88 633.16 411.94 0.00 0.00 0.00
Minimum of Months 460.45 114.51 214.88 340.16 124.25 0.00 0.00 0.00
Maximum of Months 767.37 431.18 425.86 894.37 709.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 550.63 321.42 229.21 434.78 706.67 0.00 0.00 0.00
February 628.68 303.14 325.53 487.56 692.87 0.00 0.00 0.00
March 767.34 431.16 336.18 739.27 527.70 0.00 0.00 0.00
April 635.48 253.94 381.54 637.04 422.90 0.00 0.00 0.00
May 556.10 161.52 394.59 613.43 278.83 0.00 0.00 0.00
June 540.35 114.50 425.85 667.10 179.92 0.00 0.00 0.00
July 551.61 133.84 417.77 752.75 124.24 0.00 0.00 0.00
August 619.27 200.78 418.49 832.53 160.30 0.00 0.00 0.00
September 720.03 350.71 369.32 894.33 255.19 0.00 0.00 0.00
October 688.96 393.55 295.41 734.15 393.46 0.00 0.00 0.00
November 493.42 278.55 214.87 454.34 509.21 0.00 0.00 0.00
December 460.43 238.29 222.14 340.15 709.92 0.00 0.00 0.00
                 
Annual Sum or Average 600.84 264.98 335.86 633.14 411.92 0.00 0.00 0.00
Minimum of Months 460.43 114.50 214.87 340.15 124.24 0.00 0.00 0.00
Maximum of Months 767.34 431.16 425.85 894.33 709.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 223.40 52.45 170.96 54.11 934.28 0.00 0.00 0.00
February 362.07 93.06 269.02 133.65 898.97 0.00 0.00 0.00
March 567.49 242.98 324.50 420.64 677.16 0.00 0.00 0.00
April 694.81 284.90 409.91 611.59 518.80 0.00 0.00 0.00
May 819.64 370.42 449.21 878.61 327.81 0.00 0.00 0.00
June 988.92 465.15 523.77 1198.14 223.61 0.00 0.00 0.00
July 884.13 387.63 496.50 1136.47 164.29 0.00 0.00 0.00
August 799.64 340.02 459.63 1007.13 210.96 0.00 0.00 0.00
September 627.97 271.19 356.78 710.92 304.97 0.00 0.00 0.00
October 407.08 143.40 263.68 328.57 500.57 0.00 0.00 0.00
November 241.24 69.52 171.72 121.15 678.71 0.00 0.00 0.00
December 209.13 45.57 163.56 47.53 985.93 0.00 0.00 0.00
                 
Annual Sum or Average 569.73 231.19 338.54 556.33 533.66 0.00 0.00 0.00
Minimum of Months 209.13 45.57 163.56 47.53 164.29 0.00 0.00 0.00
Maximum of Months 988.92 465.15 523.77 1198.14 985.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 223.40 52.45 170.96 54.11 934.28 0.00 0.00 0.00
February 362.07 93.06 269.02 133.65 898.97 0.00 0.00 0.00
March 567.49 242.98 324.50 420.64 677.16 0.00 0.00 0.00
April 694.81 284.90 409.91 611.59 518.80 0.00 0.00 0.00
May 819.64 370.42 449.21 878.61 327.81 0.00 0.00 0.00
June 988.92 465.15 523.77 1198.14 223.61 0.00 0.00 0.00
July 884.13 387.63 496.50 1136.47 164.29 0.00 0.00 0.00
August 799.64 340.02 459.63 1007.13 210.96 0.00 0.00 0.00
September 627.97 271.19 356.78 710.92 304.97 0.00 0.00 0.00
October 407.08 143.40 263.68 328.57 500.57 0.00 0.00 0.00
November 241.24 69.52 171.72 121.15 678.71 0.00 0.00 0.00
December 209.13 45.57 163.56 47.53 985.93 0.00 0.00 0.00
                 
Annual Sum or Average 569.73 231.19 338.54 556.33 533.66 0.00 0.00 0.00
Minimum of Months 209.13 45.57 163.56 47.53 164.29 0.00 0.00 0.00
Maximum of Months 988.92 465.15 523.77 1198.14 985.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 223.40 52.45 170.95 54.11 934.26 0.00 0.00 0.00
February 362.07 93.05 269.01 133.64 898.95 0.00 0.00 0.00
March 567.48 242.98 324.50 420.63 677.15 0.00 0.00 0.00
April 694.80 284.89 409.90 611.58 518.79 0.00 0.00 0.00
May 819.62 370.42 449.21 878.59 327.80 0.00 0.00 0.00
June 988.90 465.14 523.76 1198.12 223.60 0.00 0.00 0.00
July 884.11 387.63 496.49 1136.45 164.28 0.00 0.00 0.00
August 799.63 340.01 459.62 1007.11 210.96 0.00 0.00 0.00
September 627.96 271.19 356.77 710.90 304.96 0.00 0.00 0.00
October 407.07 143.39 263.68 328.57 500.56 0.00 0.00 0.00
November 241.23 69.51 171.72 121.15 678.69 0.00 0.00 0.00
December 209.13 45.57 163.56 47.52 985.91 0.00 0.00 0.00
                 
Annual Sum or Average 569.72 231.19 338.53 556.32 533.65 0.00 0.00 0.00
Minimum of Months 209.13 45.57 163.56 47.52 164.28 0.00 0.00 0.00
Maximum of Months 988.90 465.14 523.76 1198.12 985.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 640.28 0.00 640.28 5.46 3860.64 0.00 0.00 0.00
February 975.54 0.00 975.54 54.35 3624.35 0.00 0.00 0.00
March 1183.06 0.00 1183.06 359.84 2668.22 0.00 0.00 0.00
April 1507.46 6.02 1501.45 776.47 1920.08 0.00 0.00 0.00
May 1751.60 74.28 1677.32 1347.37 1219.36 0.00 0.00 0.00
June 2106.80 179.34 1927.46 2254.02 781.43 0.00 0.00 0.00
July 1954.34 126.16 1828.18 2424.00 543.70 0.00 0.00 0.00
August 1691.04 25.73 1665.32 1981.03 722.01 0.00 0.00 0.00
September 1286.92 0.27 1286.65 1153.05 1184.91 0.00 0.00 0.00
October 962.03 0.00 962.03 446.42 1909.45 0.00 0.00 0.00
November 646.46 0.00 646.46 124.05 2477.52 0.00 0.00 0.00
December 599.28 0.00 599.28 8.03 3707.52 0.00 0.00 0.00
                 
Annual Sum or Average 1276.64 34.46 1242.18 916.40 2043.72 0.00 0.00 0.00
Minimum of Months 599.28 0.00 599.28 5.46 543.70 0.00 0.00 0.00
Maximum of Months 2106.80 179.34 1927.46 2424.00 3860.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 781.13 251.88 529.25 298.60 2344.39 0.00 0.00 0.00
February 1146.16 343.94 802.23 530.30 2234.27 0.00 0.00 0.00
March 1644.71 688.79 955.92 1244.31 1673.23 0.00 0.00 0.00
April 2176.88 961.86 1215.02 1989.00 1238.39 0.00 0.00 0.00
May 2438.88 1078.85 1360.04 2601.81 840.88 0.00 0.00 0.00
June 2723.82 1203.80 1520.03 3269.36 539.71 0.00 0.00 0.00
July 2615.59 1151.61 1463.98 3378.38 373.92 0.00 0.00 0.00
August 2362.16 991.51 1370.65 2982.70 489.60 0.00 0.00 0.00
September 1965.73 871.92 1093.81 2233.03 775.76 0.00 0.00 0.00
October 1333.91 551.74 782.17 1152.66 1229.32 0.00 0.00 0.00
November 756.62 242.71 513.90 444.83 1598.69 0.00 0.00 0.00
December 609.12 125.86 483.26 154.57 2322.72 0.00 0.00 0.00
                 
Annual Sum or Average 1715.44 707.09 1008.35 1696.27 1300.36 0.00 0.00 0.00
Minimum of Months 609.12 125.86 483.26 154.57 373.92 0.00 0.00 0.00
Maximum of Months 2723.82 1203.80 1520.03 3378.38 2344.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2753.21 1607.13 1146.08 2186.84 3367.54 0.00 0.00 0.00
February 3143.47 1515.75 1627.72 2452.17 3315.49 0.00 0.00 0.00
March 3836.82 2155.88 1680.93 3681.66 2546.64 0.00 0.00 0.00
April 3177.49 1269.73 1907.75 3181.72 2026.47 0.00 0.00 0.00
May 2780.58 807.60 1972.99 3045.48 1365.45 0.00 0.00 0.00
June 2701.83 572.53 2129.30 3324.14 869.14 0.00 0.00 0.00
July 2758.13 669.21 2088.92 3759.89 600.80 0.00 0.00 0.00
August 3096.46 1003.95 2092.51 4151.89 783.05 0.00 0.00 0.00
September 3600.26 1753.59 1846.66 4443.99 1248.25 0.00 0.00 0.00
October 3444.91 1967.80 1477.11 3651.08 1904.31 0.00 0.00 0.00
November 2467.18 1392.80 1074.37 2278.97 2410.32 0.00 0.00 0.00
December 2302.23 1191.51 1110.72 1723.66 3328.81 0.00 0.00 0.00
                 
Annual Sum or Average 3004.28 1324.92 1679.36 3160.94 1973.30 0.00 0.00 0.00
Minimum of Months 2302.23 572.53 1074.37 1723.66 600.80 0.00 0.00 0.00
Maximum of Months 3836.82 2155.88 2129.30 4443.99 3367.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 670.20 157.34 512.86 178.99 2484.58 0.00 0.00 0.00
February 1086.21 279.16 807.05 448.63 2357.05 0.00 0.00 0.00
March 1702.44 728.94 973.49 1313.85 1759.59 0.00 0.00 0.00
April 2084.41 854.69 1229.72 1896.15 1339.79 0.00 0.00 0.00
May 2458.89 1111.26 1347.63 2642.61 921.99 0.00 0.00 0.00
June 2966.72 1395.42 1571.30 3602.59 615.56 0.00 0.00 0.00
July 2652.36 1162.89 1489.48 3434.86 439.97 0.00 0.00 0.00
August 2398.91 1020.04 1378.87 3056.82 554.13 0.00 0.00 0.00
September 1883.89 813.57 1070.32 2144.96 842.52 0.00 0.00 0.00
October 1221.23 430.19 791.04 1030.58 1305.99 0.00 0.00 0.00
November 723.70 208.55 515.16 405.07 1671.50 0.00 0.00 0.00
December 627.39 136.70 490.69 169.76 2423.07 0.00 0.00 0.00
                 
Annual Sum or Average 1709.18 693.57 1015.61 1700.48 1388.08 0.00 0.00 0.00
Minimum of Months 627.39 136.70 490.69 169.76 439.97 0.00 0.00 0.00
Maximum of Months 2966.72 1395.42 1571.30 3602.59 2484.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 640.28 0.00 640.28 12.56 3707.02 0.00 0.00 0.00
February 975.54 0.00 975.54 72.00 3466.74 0.00 0.00 0.00
March 1183.06 0.00 1183.06 393.33 2494.27 0.00 0.00 0.00
April 1507.46 6.02 1501.45 828.62 1782.36 0.00 0.00 0.00
May 1751.60 74.28 1677.32 1370.42 1165.37 0.00 0.00 0.00
June 2106.80 179.34 1927.46 2243.71 770.48 0.00 0.00 0.00
July 1954.34 126.16 1828.18 2400.78 545.96 0.00 0.00 0.00
August 1691.04 25.73 1665.32 1968.35 714.66 0.00 0.00 0.00
September 1286.92 0.27 1286.65 1166.90 1127.92 0.00 0.00 0.00
October 962.03 0.00 962.03 499.21 1728.35 0.00 0.00 0.00
November 646.46 0.00 646.46 158.36 2238.21 0.00 0.00 0.00
December 599.28 0.00 599.28 13.43 3509.71 0.00 0.00 0.00
                 
Annual Sum or Average 1276.64 34.46 1242.18 932.45 1930.04 0.00 0.00 0.00
Minimum of Months 599.28 0.00 599.28 12.56 545.96 0.00 0.00 0.00
Maximum of Months 2106.80 179.34 1927.46 2400.78 3707.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 781.13 251.88 529.25 312.02 2253.14 0.00 0.00 0.00
February 1146.16 343.94 802.23 554.68 2138.63 0.00 0.00 0.00
March 1644.71 688.79 955.92 1282.72 1555.97 0.00 0.00 0.00
April 2176.88 961.86 1215.02 2028.99 1156.85 0.00 0.00 0.00
May 2438.88 1078.85 1360.04 2613.43 809.54 0.00 0.00 0.00
June 2723.82 1203.80 1520.03 3264.47 533.21 0.00 0.00 0.00
July 2615.59 1151.61 1463.98 3367.78 375.39 0.00 0.00 0.00
August 2362.16 991.51 1370.65 2977.54 485.14 0.00 0.00 0.00
September 1965.73 871.92 1093.81 2243.52 744.21 0.00 0.00 0.00
October 1333.91 551.74 782.17 1195.79 1118.63 0.00 0.00 0.00
November 756.62 242.71 513.90 480.76 1439.90 0.00 0.00 0.00
December 609.12 125.86 483.26 164.99 2204.76 0.00 0.00 0.00
                 
Annual Sum or Average 1715.44 707.09 1008.35 1713.44 1230.10 0.00 0.00 0.00
Minimum of Months 609.12 125.86 483.26 164.99 375.39 0.00 0.00 0.00
Maximum of Months 2723.82 1203.80 1520.03 3367.78 2253.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2753.21 1607.13 1146.08 2221.49 3206.48 0.00 0.00 0.00
February 3143.47 1515.75 1627.72 2496.67 3156.34 0.00 0.00 0.00
March 3836.82 2155.88 1680.93 3730.87 2375.38 0.00 0.00 0.00
April 3177.49 1269.73 1907.75 3223.31 1896.09 0.00 0.00 0.00
May 2780.58 807.60 1972.99 3053.53 1309.33 0.00 0.00 0.00
June 2701.83 572.53 2129.30 3308.10 854.92 0.00 0.00 0.00
July 2758.13 669.21 2088.92 3734.34 601.86 0.00 0.00 0.00
August 3096.46 1003.95 2092.51 4133.40 775.45 0.00 0.00 0.00
September 3600.26 1753.59 1846.66 4446.09 1200.19 0.00 0.00 0.00
October 3444.91 1967.80 1477.11 3700.19 1747.55 0.00 0.00 0.00
November 2467.18 1392.80 1074.37 2335.06 2186.60 0.00 0.00 0.00
December 2302.23 1191.51 1110.72 1762.96 3136.39 0.00 0.00 0.00
                 
Annual Sum or Average 3004.28 1324.92 1679.36 3182.81 1863.66 0.00 0.00 0.00
Minimum of Months 2302.23 572.53 1074.37 1762.96 601.86 0.00 0.00 0.00
Maximum of Months 3836.82 2155.88 2129.30 4446.09 3206.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 670.20 157.34 512.86 187.81 2384.20 0.00 0.00 0.00
February 1086.21 279.16 807.05 463.35 2263.21 0.00 0.00 0.00
March 1702.44 728.94 973.49 1335.23 1655.65 0.00 0.00 0.00
April 2084.41 854.69 1229.72 1920.78 1260.95 0.00 0.00 0.00
May 2458.89 1111.26 1347.63 2644.89 887.90 0.00 0.00 0.00
June 2966.72 1395.42 1571.30 3587.63 605.78 0.00 0.00 0.00
July 2652.36 1162.89 1489.48 3416.08 438.70 0.00 0.00 0.00
August 2398.91 1020.04 1378.87 3043.70 548.53 0.00 0.00 0.00
September 1883.89 813.57 1070.32 2146.54 811.09 0.00 0.00 0.00
October 1221.23 430.19 791.04 1058.61 1205.64 0.00 0.00 0.00
November 723.70 208.55 515.16 428.35 1534.58 0.00 0.00 0.00
December 627.39 136.70 490.69 178.51 2307.68 0.00 0.00 0.00
                 
Annual Sum or Average 1709.18 693.57 1015.61 1707.62 1320.60 0.00 0.00 0.00
Minimum of Months 627.39 136.70 490.69 178.51 438.70 0.00 0.00 0.00
Maximum of Months 2966.72 1395.42 1571.30 3587.63 2384.20 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.342989E+09 0.00 0.342989E+09 49417.70 0.228231E+10
February 0.472013E+09 0.00 0.472013E+09 12621050.52 0.193797E+10
March 0.633749E+09 0.00 0.633749E+09 0.165981E+09 0.158573E+10
April 0.781477E+09 3118403.21 0.778359E+09 0.365133E+09 0.110535E+10
May 0.938306E+09 39789500.73 0.898516E+09 0.708244E+09 0.686954E+09
June 0.109218E+10 92971783.14 0.999207E+09 0.115931E+10 0.424529E+09
July 0.104691E+10 67580513.96 0.979331E+09 0.128458E+10 0.306021E+09
August 0.905870E+09 13780841.18 0.892089E+09 0.104734E+10 0.405167E+09
September 0.667148E+09 138604.48 0.667009E+09 0.585535E+09 0.657224E+09
October 0.515346E+09 0.00 0.515346E+09 0.209717E+09 0.113954E+10
November 0.335129E+09 0.00 0.335129E+09 43885408.62 0.148385E+10
December 0.321027E+09 0.00 0.321027E+09 1557362.25 0.225224E+10
           
Annual Sum or Average 0.805214E+10 0.217380E+09 0.783476E+10 0.558395E+10 0.142669E+11
Minimum of Months 0.321027E+09 0.00 0.321027E+09 49417.70 0.306021E+09
Maximum of Months 0.109218E+10 92971783.14 0.999207E+09 0.128458E+10 0.228231E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.342988E+09 0.00 0.342988E+09 49416.32 0.228232E+10
February 0.472013E+09 0.00 0.472013E+09 12620949.82 0.193797E+10
March 0.633749E+09 0.00 0.633749E+09 0.165980E+09 0.158573E+10
April 0.781476E+09 3118399.47 0.778358E+09 0.365132E+09 0.110535E+10
May 0.938305E+09 39789452.98 0.898516E+09 0.708244E+09 0.686954E+09
June 0.109218E+10 92971671.58 0.999206E+09 0.115930E+10 0.424529E+09
July 0.104691E+10 67580432.87 0.979331E+09 0.128458E+10 0.306021E+09
August 0.905869E+09 13780824.64 0.892088E+09 0.104734E+10 0.405167E+09
September 0.667148E+09 138604.32 0.667009E+09 0.585534E+09 0.657224E+09
October 0.515345E+09 0.00 0.515345E+09 0.209717E+09 0.113954E+10
November 0.335128E+09 0.00 0.335128E+09 43885288.27 0.148385E+10
December 0.321027E+09 0.00 0.321027E+09 1557352.44 0.225224E+10
           
Annual Sum or Average 0.805214E+10 0.217379E+09 0.783476E+10 0.558394E+10 0.142669E+11
Minimum of Months 0.321027E+09 0.00 0.321027E+09 49416.32 0.306021E+09
Maximum of Months 0.109218E+10 92971671.58 0.999206E+09 0.128458E+10 0.228232E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.342989E+09 0.00 0.342989E+09 49417.70 0.228231E+10
February 0.472013E+09 0.00 0.472013E+09 12621050.52 0.193797E+10
March 0.633749E+09 0.00 0.633749E+09 0.165981E+09 0.158573E+10
April 0.781477E+09 3118403.21 0.778359E+09 0.365133E+09 0.110535E+10
May 0.938306E+09 39789500.73 0.898516E+09 0.708244E+09 0.686954E+09
June 0.109218E+10 92971783.14 0.999207E+09 0.115931E+10 0.424529E+09
July 0.104691E+10 67580513.96 0.979331E+09 0.128458E+10 0.306021E+09
August 0.905870E+09 13780841.18 0.892089E+09 0.104734E+10 0.405167E+09
September 0.667148E+09 138604.48 0.667009E+09 0.585535E+09 0.657224E+09
October 0.515346E+09 0.00 0.515346E+09 0.209717E+09 0.113954E+10
November 0.335129E+09 0.00 0.335129E+09 43885408.62 0.148385E+10
December 0.321027E+09 0.00 0.321027E+09 1557362.25 0.225224E+10
           
Annual Sum or Average 0.805214E+10 0.217380E+09 0.783476E+10 0.558395E+10 0.142669E+11
Minimum of Months 0.321027E+09 0.00 0.321027E+09 49417.70 0.306021E+09
Maximum of Months 0.109218E+10 92971783.14 0.999207E+09 0.128458E+10 0.228231E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.342988E+09 0.00 0.342988E+09 49416.32 0.228232E+10
February 0.472013E+09 0.00 0.472013E+09 12620949.82 0.193797E+10
March 0.633749E+09 0.00 0.633749E+09 0.165980E+09 0.158573E+10
April 0.781476E+09 3118399.47 0.778358E+09 0.365132E+09 0.110535E+10
May 0.938305E+09 39789452.98 0.898516E+09 0.708244E+09 0.686954E+09
June 0.109218E+10 92971671.58 0.999206E+09 0.115930E+10 0.424529E+09
July 0.104691E+10 67580432.87 0.979331E+09 0.128458E+10 0.306021E+09
August 0.905869E+09 13780824.64 0.892088E+09 0.104734E+10 0.405167E+09
September 0.667148E+09 138604.32 0.667009E+09 0.585534E+09 0.657224E+09
October 0.515345E+09 0.00 0.515345E+09 0.209717E+09 0.113954E+10
November 0.335128E+09 0.00 0.335128E+09 43885288.27 0.148385E+10
December 0.321027E+09 0.00 0.321027E+09 1557352.44 0.225224E+10
           
Annual Sum or Average 0.805214E+10 0.217379E+09 0.783476E+10 0.558394E+10 0.142669E+11
Minimum of Months 0.321027E+09 0.00 0.321027E+09 49416.32 0.306021E+09
Maximum of Months 0.109218E+10 92971671.58 0.999206E+09 0.128458E+10 0.228232E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.342975E+09 0.00 0.342975E+09 49415.71 0.228222E+10
February 0.471994E+09 0.00 0.471994E+09 12620541.83 0.193789E+10
March 0.633724E+09 0.00 0.633724E+09 0.165974E+09 0.158567E+10
April 0.781446E+09 3118277.53 0.778327E+09 0.365118E+09 0.110531E+10
May 0.938268E+09 39787897.04 0.898480E+09 0.708216E+09 0.686926E+09
June 0.109213E+10 92968035.97 0.999166E+09 0.115926E+10 0.424512E+09
July 0.104687E+10 67577790.16 0.979292E+09 0.128453E+10 0.306009E+09
August 0.905833E+09 13780285.75 0.892053E+09 0.104730E+10 0.405151E+09
September 0.667121E+09 138598.90 0.666983E+09 0.585511E+09 0.657198E+09
October 0.515325E+09 0.00 0.515325E+09 0.209709E+09 0.113949E+10
November 0.335115E+09 0.00 0.335115E+09 43883639.85 0.148379E+10
December 0.321014E+09 0.00 0.321014E+09 1557299.48 0.225214E+10
           
Annual Sum or Average 0.805182E+10 0.217371E+09 0.783445E+10 0.558372E+10 0.142663E+11
Minimum of Months 0.321014E+09 0.00 0.321014E+09 49415.71 0.306009E+09
Maximum of Months 0.109213E+10 92968035.97 0.999166E+09 0.128453E+10 0.228222E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.697404E+09 0.224882E+09 0.472522E+09 0.248005E+09 0.230709E+10
February 0.924275E+09 0.277352E+09 0.646923E+09 0.399991E+09 0.196337E+10
March 0.146841E+10 0.614962E+09 0.853451E+09 0.109718E+10 0.160004E+10
April 0.188084E+10 0.831058E+09 0.104979E+10 0.171651E+10 0.112955E+10
May 0.217746E+10 0.963207E+09 0.121425E+10 0.234161E+10 0.769994E+09
June 0.235341E+10 0.104009E+10 0.131332E+10 0.284617E+10 0.475427E+09
July 0.233522E+10 0.102816E+10 0.130705E+10 0.303454E+10 0.335282E+09
August 0.210896E+10 0.885226E+09 0.122373E+10 0.268382E+10 0.433598E+09
September 0.169841E+10 0.753348E+09 0.945059E+09 0.194130E+10 0.694464E+09
October 0.119093E+10 0.492599E+09 0.698327E+09 0.101991E+10 0.117419E+10
November 0.653724E+09 0.209707E+09 0.444017E+09 0.363293E+09 0.153209E+10
December 0.543824E+09 0.112366E+09 0.431458E+09 0.122563E+09 0.229993E+10
           
Annual Sum or Average 0.180329E+11 0.743296E+10 0.105999E+11 0.178149E+11 0.147150E+11
Minimum of Months 0.543824E+09 0.112366E+09 0.431458E+09 0.122563E+09 0.335282E+09
Maximum of Months 0.235341E+10 0.104009E+10 0.131332E+10 0.303454E+10 0.230709E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.697404E+09 0.224882E+09 0.472522E+09 0.248005E+09 0.230709E+10
February 0.924275E+09 0.277352E+09 0.646923E+09 0.399991E+09 0.196337E+10
March 0.146841E+10 0.614962E+09 0.853451E+09 0.109718E+10 0.160004E+10
April 0.188084E+10 0.831058E+09 0.104979E+10 0.171651E+10 0.112955E+10
May 0.217746E+10 0.963207E+09 0.121425E+10 0.234161E+10 0.769994E+09
June 0.235341E+10 0.104009E+10 0.131332E+10 0.284617E+10 0.475427E+09
July 0.233522E+10 0.102816E+10 0.130705E+10 0.303454E+10 0.335282E+09
August 0.210896E+10 0.885226E+09 0.122373E+10 0.268382E+10 0.433598E+09
September 0.169841E+10 0.753348E+09 0.945059E+09 0.194130E+10 0.694464E+09
October 0.119093E+10 0.492599E+09 0.698327E+09 0.101991E+10 0.117419E+10
November 0.653724E+09 0.209707E+09 0.444017E+09 0.363293E+09 0.153209E+10
December 0.543824E+09 0.112366E+09 0.431458E+09 0.122563E+09 0.229993E+10
           
Annual Sum or Average 0.180329E+11 0.743296E+10 0.105999E+11 0.178149E+11 0.147150E+11
Minimum of Months 0.543824E+09 0.112366E+09 0.431458E+09 0.122563E+09 0.335282E+09
Maximum of Months 0.235341E+10 0.104009E+10 0.131332E+10 0.303454E+10 0.230709E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.697391E+09 0.224878E+09 0.472513E+09 0.248001E+09 0.230705E+10
February 0.924258E+09 0.277347E+09 0.646911E+09 0.399984E+09 0.196334E+10
March 0.146839E+10 0.614951E+09 0.853435E+09 0.109716E+10 0.160002E+10
April 0.188081E+10 0.831042E+09 0.104977E+10 0.171648E+10 0.112952E+10
May 0.217742E+10 0.963189E+09 0.121423E+10 0.234157E+10 0.769980E+09
June 0.235336E+10 0.104007E+10 0.131329E+10 0.284611E+10 0.475418E+09
July 0.233518E+10 0.102815E+10 0.130703E+10 0.303449E+10 0.335276E+09
August 0.210892E+10 0.885210E+09 0.122371E+10 0.268377E+10 0.433590E+09
September 0.169838E+10 0.753334E+09 0.945041E+09 0.194126E+10 0.694451E+09
October 0.119090E+10 0.492590E+09 0.698315E+09 0.101989E+10 0.117417E+10
November 0.653712E+09 0.209703E+09 0.444009E+09 0.363287E+09 0.153207E+10
December 0.543814E+09 0.112364E+09 0.431450E+09 0.122560E+09 0.229989E+10
           
Annual Sum or Average 0.180325E+11 0.743283E+10 0.105997E+11 0.178146E+11 0.147148E+11
Minimum of Months 0.543814E+09 0.112364E+09 0.431450E+09 0.122560E+09 0.335276E+09
Maximum of Months 0.235336E+10 0.104007E+10 0.131329E+10 0.303449E+10 0.230705E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147486E+10 0.860917E+09 0.613939E+09 0.116456E+10 0.189283E+10
February 0.152096E+10 0.733392E+09 0.787564E+09 0.117954E+10 0.167625E+10
March 0.205533E+10 0.115488E+10 0.900453E+09 0.198013E+10 0.141345E+10
April 0.164723E+10 0.658238E+09 0.988992E+09 0.165128E+10 0.109620E+10
May 0.148952E+10 0.432620E+09 0.105690E+10 0.164307E+10 0.746849E+09
June 0.140065E+10 0.296804E+09 0.110384E+10 0.172920E+10 0.466372E+09
July 0.147749E+10 0.358488E+09 0.111901E+10 0.201624E+10 0.332787E+09
August 0.165873E+10 0.537802E+09 0.112093E+10 0.222994E+10 0.429375E+09
September 0.186640E+10 0.909074E+09 0.957322E+09 0.231821E+10 0.661466E+09
October 0.184539E+10 0.105412E+10 0.791269E+09 0.196642E+10 0.105390E+10
November 0.127900E+10 0.722038E+09 0.556961E+09 0.117769E+10 0.131993E+10
December 0.123327E+10 0.638274E+09 0.594998E+09 0.911091E+09 0.190153E+10
           
Annual Sum or Average 0.189488E+11 0.835665E+10 0.105922E+11 0.199674E+11 0.129909E+11
Minimum of Months 0.123327E+10 0.296804E+09 0.556961E+09 0.911091E+09 0.332787E+09
Maximum of Months 0.205533E+10 0.115488E+10 0.112093E+10 0.231821E+10 0.190153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147485E+10 0.860916E+09 0.613938E+09 0.116456E+10 0.189283E+10
February 0.152095E+10 0.733391E+09 0.787563E+09 0.117954E+10 0.167625E+10
March 0.205533E+10 0.115488E+10 0.900452E+09 0.198013E+10 0.141345E+10
April 0.164723E+10 0.658237E+09 0.988991E+09 0.165128E+10 0.109620E+10
May 0.148952E+10 0.432619E+09 0.105690E+10 0.164307E+10 0.746849E+09
June 0.140065E+10 0.296804E+09 0.110384E+10 0.172920E+10 0.466372E+09
July 0.147749E+10 0.358488E+09 0.111900E+10 0.201623E+10 0.332787E+09
August 0.165873E+10 0.537801E+09 0.112093E+10 0.222994E+10 0.429375E+09
September 0.186639E+10 0.909072E+09 0.957322E+09 0.231821E+10 0.661466E+09
October 0.184539E+10 0.105412E+10 0.791268E+09 0.196642E+10 0.105390E+10
November 0.127900E+10 0.722037E+09 0.556961E+09 0.117769E+10 0.131993E+10
December 0.123327E+10 0.638273E+09 0.594997E+09 0.911089E+09 0.190153E+10
           
Annual Sum or Average 0.189488E+11 0.835664E+10 0.105922E+11 0.199673E+11 0.129909E+11
Minimum of Months 0.123327E+10 0.296804E+09 0.556961E+09 0.911089E+09 0.332787E+09
Maximum of Months 0.205533E+10 0.115488E+10 0.112093E+10 0.231821E+10 0.190153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147486E+10 0.860917E+09 0.613939E+09 0.116456E+10 0.189283E+10
February 0.152096E+10 0.733392E+09 0.787564E+09 0.117954E+10 0.167625E+10
March 0.205533E+10 0.115488E+10 0.900453E+09 0.198013E+10 0.141345E+10
April 0.164723E+10 0.658238E+09 0.988992E+09 0.165128E+10 0.109620E+10
May 0.148952E+10 0.432620E+09 0.105690E+10 0.164307E+10 0.746849E+09
June 0.140065E+10 0.296804E+09 0.110384E+10 0.172920E+10 0.466372E+09
July 0.147749E+10 0.358488E+09 0.111901E+10 0.201624E+10 0.332787E+09
August 0.165873E+10 0.537802E+09 0.112093E+10 0.222994E+10 0.429375E+09
September 0.186640E+10 0.909074E+09 0.957322E+09 0.231821E+10 0.661466E+09
October 0.184539E+10 0.105412E+10 0.791269E+09 0.196642E+10 0.105390E+10
November 0.127900E+10 0.722038E+09 0.556961E+09 0.117769E+10 0.131993E+10
December 0.123327E+10 0.638274E+09 0.594998E+09 0.911091E+09 0.190153E+10
           
Annual Sum or Average 0.189488E+11 0.835665E+10 0.105922E+11 0.199674E+11 0.129909E+11
Minimum of Months 0.123327E+10 0.296804E+09 0.556961E+09 0.911091E+09 0.332787E+09
Maximum of Months 0.205533E+10 0.115488E+10 0.112093E+10 0.231821E+10 0.190153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147485E+10 0.860916E+09 0.613938E+09 0.116456E+10 0.189283E+10
February 0.152095E+10 0.733391E+09 0.787563E+09 0.117954E+10 0.167625E+10
March 0.205533E+10 0.115488E+10 0.900452E+09 0.198013E+10 0.141345E+10
April 0.164723E+10 0.658237E+09 0.988991E+09 0.165128E+10 0.109620E+10
May 0.148952E+10 0.432619E+09 0.105690E+10 0.164307E+10 0.746849E+09
June 0.140065E+10 0.296804E+09 0.110384E+10 0.172920E+10 0.466372E+09
July 0.147749E+10 0.358488E+09 0.111900E+10 0.201623E+10 0.332787E+09
August 0.165873E+10 0.537801E+09 0.112093E+10 0.222994E+10 0.429375E+09
September 0.186639E+10 0.909072E+09 0.957322E+09 0.231821E+10 0.661466E+09
October 0.184539E+10 0.105412E+10 0.791268E+09 0.196642E+10 0.105390E+10
November 0.127900E+10 0.722037E+09 0.556961E+09 0.117769E+10 0.131993E+10
December 0.123327E+10 0.638273E+09 0.594997E+09 0.911089E+09 0.190153E+10
           
Annual Sum or Average 0.189488E+11 0.835664E+10 0.105922E+11 0.199673E+11 0.129909E+11
Minimum of Months 0.123327E+10 0.296804E+09 0.556961E+09 0.911089E+09 0.332787E+09
Maximum of Months 0.205533E+10 0.115488E+10 0.112093E+10 0.231821E+10 0.190153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147480E+10 0.860882E+09 0.613914E+09 0.116451E+10 0.189275E+10
February 0.152089E+10 0.733362E+09 0.787532E+09 0.117949E+10 0.167619E+10
March 0.205525E+10 0.115483E+10 0.900417E+09 0.198005E+10 0.141339E+10
April 0.164716E+10 0.658211E+09 0.988952E+09 0.165121E+10 0.109615E+10
May 0.148946E+10 0.432602E+09 0.105686E+10 0.164300E+10 0.746818E+09
June 0.140059E+10 0.296792E+09 0.110380E+10 0.172913E+10 0.466353E+09
July 0.147743E+10 0.358474E+09 0.111896E+10 0.201615E+10 0.332774E+09
August 0.165866E+10 0.537780E+09 0.112088E+10 0.222985E+10 0.429358E+09
September 0.186632E+10 0.909037E+09 0.957284E+09 0.231812E+10 0.661440E+09
October 0.184532E+10 0.105408E+10 0.791237E+09 0.196634E+10 0.105386E+10
November 0.127895E+10 0.722009E+09 0.556939E+09 0.117764E+10 0.131988E+10
December 0.123322E+10 0.638249E+09 0.594974E+09 0.911054E+09 0.190145E+10
           
Annual Sum or Average 0.189481E+11 0.835631E+10 0.105917E+11 0.199666E+11 0.129904E+11
Minimum of Months 0.123322E+10 0.296792E+09 0.556939E+09 0.911054E+09 0.332774E+09
Maximum of Months 0.205525E+10 0.115483E+10 0.112088E+10 0.231812E+10 0.190145E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.598360E+09 0.140472E+09 0.457889E+09 0.144930E+09 0.250238E+10
February 0.875928E+09 0.225120E+09 0.650808E+09 0.323319E+09 0.217479E+10
March 0.151995E+10 0.650808E+09 0.869145E+09 0.112664E+10 0.181372E+10
April 0.180095E+10 0.738460E+09 0.106249E+10 0.158524E+10 0.134474E+10
May 0.219532E+10 0.992142E+09 0.120318E+10 0.235327E+10 0.878001E+09
June 0.256328E+10 0.120566E+10 0.135762E+10 0.310557E+10 0.579585E+09
July 0.236805E+10 0.103824E+10 0.132982E+10 0.304391E+10 0.440021E+09
August 0.214177E+10 0.910699E+09 0.123107E+10 0.269749E+10 0.565042E+09
September 0.162769E+10 0.702930E+09 0.924764E+09 0.184269E+10 0.790480E+09
October 0.109032E+10 0.384073E+09 0.706247E+09 0.880053E+09 0.134072E+10
November 0.625285E+09 0.180185E+09 0.445100E+09 0.314032E+09 0.175921E+10
December 0.560136E+09 0.122047E+09 0.438088E+09 0.127293E+09 0.264072E+10
           
Annual Sum or Average 0.179670E+11 0.729083E+10 0.106762E+11 0.175445E+11 0.168294E+11
Minimum of Months 0.560136E+09 0.122047E+09 0.438088E+09 0.127293E+09 0.440021E+09
Maximum of Months 0.256328E+10 0.120566E+10 0.135762E+10 0.310557E+10 0.264072E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.598360E+09 0.140472E+09 0.457889E+09 0.144930E+09 0.250238E+10
February 0.875928E+09 0.225120E+09 0.650808E+09 0.323319E+09 0.217479E+10
March 0.151995E+10 0.650808E+09 0.869145E+09 0.112664E+10 0.181372E+10
April 0.180095E+10 0.738460E+09 0.106249E+10 0.158524E+10 0.134474E+10
May 0.219532E+10 0.992142E+09 0.120318E+10 0.235327E+10 0.878001E+09
June 0.256328E+10 0.120566E+10 0.135762E+10 0.310557E+10 0.579585E+09
July 0.236805E+10 0.103824E+10 0.132982E+10 0.304391E+10 0.440021E+09
August 0.214177E+10 0.910699E+09 0.123107E+10 0.269749E+10 0.565042E+09
September 0.162769E+10 0.702930E+09 0.924764E+09 0.184269E+10 0.790480E+09
October 0.109032E+10 0.384073E+09 0.706247E+09 0.880053E+09 0.134072E+10
November 0.625285E+09 0.180185E+09 0.445100E+09 0.314032E+09 0.175921E+10
December 0.560136E+09 0.122047E+09 0.438088E+09 0.127293E+09 0.264072E+10
           
Annual Sum or Average 0.179670E+11 0.729083E+10 0.106762E+11 0.175445E+11 0.168294E+11
Minimum of Months 0.560136E+09 0.122047E+09 0.438088E+09 0.127293E+09 0.440021E+09
Maximum of Months 0.256328E+10 0.120566E+10 0.135762E+10 0.310557E+10 0.264072E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.598349E+09 0.140469E+09 0.457880E+09 0.144927E+09 0.250233E+10
February 0.875912E+09 0.225116E+09 0.650796E+09 0.323313E+09 0.217475E+10
March 0.151993E+10 0.650797E+09 0.869129E+09 0.112662E+10 0.181368E+10
April 0.180091E+10 0.738447E+09 0.106247E+10 0.158521E+10 0.134471E+10
May 0.219528E+10 0.992124E+09 0.120315E+10 0.235323E+10 0.877985E+09
June 0.256323E+10 0.120564E+10 0.135759E+10 0.310551E+10 0.579575E+09
July 0.236801E+10 0.103822E+10 0.132979E+10 0.304386E+10 0.440013E+09
August 0.214173E+10 0.910683E+09 0.123104E+10 0.269744E+10 0.565032E+09
September 0.162766E+10 0.702917E+09 0.924747E+09 0.184266E+10 0.790465E+09
October 0.109030E+10 0.384066E+09 0.706234E+09 0.880037E+09 0.134070E+10
November 0.625274E+09 0.180182E+09 0.445092E+09 0.314026E+09 0.175918E+10
December 0.560125E+09 0.122045E+09 0.438080E+09 0.127291E+09 0.264067E+10
           
Annual Sum or Average 0.179667E+11 0.729070E+10 0.106760E+11 0.175441E+11 0.168291E+11
Minimum of Months 0.560125E+09 0.122045E+09 0.438080E+09 0.127291E+09 0.440013E+09
Maximum of Months 0.256323E+10 0.120564E+10 0.135759E+10 0.310551E+10 0.264067E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171492E+10 0.00 0.171492E+10 14627437.81 0.103403E+11
February 0.236004E+10 0.00 0.236004E+10 0.131483E+09 0.876803E+10
March 0.316871E+10 0.00 0.316871E+10 0.963786E+09 0.714657E+10
April 0.390734E+10 15591827.53 0.389175E+10 0.201260E+10 0.497685E+10
May 0.469147E+10 0.198945E+09 0.449253E+10 0.360880E+10 0.326593E+10
June 0.546083E+10 0.464853E+09 0.499597E+10 0.584242E+10 0.202547E+10
July 0.523450E+10 0.337898E+09 0.489660E+10 0.649244E+10 0.145625E+10
August 0.452929E+10 68903372.72 0.446039E+10 0.530600E+10 0.193383E+10
September 0.333570E+10 693014.03 0.333501E+10 0.298871E+10 0.307128E+10
October 0.257670E+10 0.00 0.257670E+10 0.119568E+10 0.511427E+10
November 0.167562E+10 0.00 0.167562E+10 0.321538E+09 0.642174E+10
December 0.160512E+10 0.00 0.160512E+10 21513712.81 0.993023E+10
           
Annual Sum or Average 0.402602E+11 0.108689E+10 0.391733E+11 0.288996E+11 0.644508E+11
Minimum of Months 0.160512E+10 0.00 0.160512E+10 14627437.81 0.145625E+10
Maximum of Months 0.546083E+10 0.464853E+09 0.499597E+10 0.649244E+10 0.103403E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209219E+10 0.674639E+09 0.141755E+10 0.799779E+09 0.627921E+10
February 0.277280E+10 0.832048E+09 0.194075E+10 0.128291E+10 0.540514E+10
March 0.440520E+10 0.184487E+10 0.256033E+10 0.333277E+10 0.448157E+10
April 0.564247E+10 0.249315E+10 0.314932E+10 0.515549E+10 0.320991E+10
May 0.653231E+10 0.288959E+10 0.364272E+10 0.696868E+10 0.225223E+10
June 0.706015E+10 0.312024E+10 0.393991E+10 0.847419E+10 0.139892E+10
July 0.700558E+10 0.308446E+10 0.392112E+10 0.904866E+10 0.100151E+10
August 0.632681E+10 0.265565E+10 0.367116E+10 0.798886E+10 0.131136E+10
September 0.509517E+10 0.226002E+10 0.283515E+10 0.578802E+10 0.201076E+10
October 0.357274E+10 0.147778E+10 0.209496E+10 0.308728E+10 0.329260E+10
November 0.196115E+10 0.629115E+09 0.133204E+10 0.115300E+10 0.414381E+10
December 0.163145E+10 0.337094E+09 0.129436E+10 0.414001E+09 0.622118E+10
           
Annual Sum or Average 0.540980E+11 0.222987E+11 0.317994E+11 0.534936E+11 0.410082E+11
Minimum of Months 0.163145E+10 0.337094E+09 0.129436E+10 0.414001E+09 0.100151E+10
Maximum of Months 0.706015E+10 0.312024E+10 0.393991E+10 0.904866E+10 0.627921E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.737419E+10 0.430453E+10 0.306966E+10 0.585723E+10 0.901962E+10
February 0.760469E+10 0.366691E+10 0.393777E+10 0.593230E+10 0.802082E+10
March 0.102765E+11 0.577432E+10 0.450221E+10 0.986097E+10 0.682093E+10
April 0.823605E+10 0.329115E+10 0.494490E+10 0.824702E+10 0.525261E+10
May 0.744752E+10 0.216307E+10 0.528444E+10 0.815700E+10 0.365721E+10
June 0.700315E+10 0.148400E+10 0.551915E+10 0.861618E+10 0.225281E+10
July 0.738738E+10 0.179242E+10 0.559496E+10 0.100705E+11 0.160918E+10
August 0.829355E+10 0.268898E+10 0.560457E+10 0.111204E+11 0.209733E+10
September 0.933187E+10 0.454531E+10 0.478655E+10 0.115188E+11 0.323547E+10
October 0.922686E+10 0.527056E+10 0.395630E+10 0.977905E+10 0.510051E+10
November 0.639492E+10 0.361015E+10 0.278477E+10 0.590710E+10 0.624755E+10
December 0.616629E+10 0.319133E+10 0.297495E+10 0.461665E+10 0.891589E+10
           
Annual Sum or Average 0.947430E+11 0.417827E+11 0.529602E+11 0.996832E+11 0.622299E+11
Minimum of Months 0.616629E+10 0.148400E+10 0.278477E+10 0.461665E+10 0.160918E+10
Maximum of Months 0.102765E+11 0.577432E+10 0.560457E+10 0.115188E+11 0.901962E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.179506E+10 0.421410E+09 0.137365E+10 0.479416E+09 0.665471E+10
February 0.262776E+10 0.675353E+09 0.195240E+10 0.108533E+10 0.570217E+10
March 0.455981E+10 0.195241E+10 0.260741E+10 0.351902E+10 0.471289E+10
April 0.540278E+10 0.221536E+10 0.318742E+10 0.491481E+10 0.347273E+10
May 0.658589E+10 0.297640E+10 0.360949E+10 0.707798E+10 0.246947E+10
June 0.768975E+10 0.361694E+10 0.407281E+10 0.933791E+10 0.159552E+10
July 0.710409E+10 0.311468E+10 0.398941E+10 0.919992E+10 0.117843E+10
August 0.642523E+10 0.273207E+10 0.369316E+10 0.818738E+10 0.148418E+10
September 0.488303E+10 0.210877E+10 0.277426E+10 0.555974E+10 0.218381E+10
October 0.327093E+10 0.115221E+10 0.211872E+10 0.276031E+10 0.349798E+10
November 0.187584E+10 0.540549E+09 0.133529E+10 0.104995E+10 0.433254E+10
December 0.168039E+10 0.366138E+09 0.131425E+10 0.454693E+09 0.648995E+10
           
Annual Sum or Average 0.539006E+11 0.218723E+11 0.320283E+11 0.536265E+11 0.437744E+11
Minimum of Months 0.168039E+10 0.366138E+09 0.131425E+10 0.454693E+09 0.117843E+10
Maximum of Months 0.768975E+10 0.361694E+10 0.407281E+10 0.933791E+10 0.665471E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171492E+10 0.00 0.171492E+10 33652015.24 0.992887E+10
February 0.236004E+10 0.00 0.236004E+10 0.174191E+09 0.838675E+10
March 0.316871E+10 0.00 0.316871E+10 0.105348E+10 0.668064E+10
April 0.390734E+10 15591827.53 0.389175E+10 0.214778E+10 0.461988E+10
May 0.469147E+10 0.198945E+09 0.449253E+10 0.367053E+10 0.312134E+10
June 0.546083E+10 0.464853E+09 0.499597E+10 0.581570E+10 0.199708E+10
July 0.523450E+10 0.337898E+09 0.489660E+10 0.643025E+10 0.146231E+10
August 0.452929E+10 68903372.72 0.446039E+10 0.527204E+10 0.191415E+10
September 0.333570E+10 693014.03 0.333501E+10 0.302462E+10 0.292356E+10
October 0.257670E+10 0.00 0.257670E+10 0.133708E+10 0.462922E+10
November 0.167562E+10 0.00 0.167562E+10 0.410474E+09 0.580144E+10
December 0.160512E+10 0.00 0.160512E+10 35981068.18 0.940041E+10
           
Annual Sum or Average 0.402602E+11 0.108689E+10 0.391733E+11 0.294058E+11 0.608656E+11
Minimum of Months 0.160512E+10 0.00 0.160512E+10 33652015.24 0.146231E+10
Maximum of Months 0.546083E+10 0.464853E+09 0.499597E+10 0.643025E+10 0.992887E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209219E+10 0.674639E+09 0.141755E+10 0.835702E+09 0.603481E+10
February 0.277280E+10 0.832048E+09 0.194075E+10 0.134187E+10 0.517379E+10
March 0.440520E+10 0.184487E+10 0.256033E+10 0.343564E+10 0.416751E+10
April 0.564247E+10 0.249315E+10 0.314932E+10 0.525915E+10 0.299855E+10
May 0.653231E+10 0.288959E+10 0.364272E+10 0.699981E+10 0.216828E+10
June 0.706015E+10 0.312024E+10 0.393991E+10 0.846152E+10 0.138207E+10
July 0.700558E+10 0.308446E+10 0.392112E+10 0.902026E+10 0.100543E+10
August 0.632681E+10 0.265565E+10 0.367116E+10 0.797503E+10 0.129941E+10
September 0.509517E+10 0.226002E+10 0.283515E+10 0.581520E+10 0.192900E+10
October 0.357274E+10 0.147778E+10 0.209496E+10 0.320281E+10 0.299613E+10
November 0.196115E+10 0.629115E+09 0.133204E+10 0.124613E+10 0.373223E+10
December 0.163145E+10 0.337094E+09 0.129436E+10 0.441918E+09 0.590524E+10
           
Annual Sum or Average 0.540980E+11 0.222987E+11 0.317994E+11 0.540350E+11 0.387925E+11
Minimum of Months 0.163145E+10 0.337094E+09 0.129436E+10 0.441918E+09 0.100543E+10
Maximum of Months 0.706015E+10 0.312024E+10 0.393991E+10 0.902026E+10 0.603481E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.737419E+10 0.430453E+10 0.306966E+10 0.595005E+10 0.858824E+10
February 0.760469E+10 0.366691E+10 0.393777E+10 0.603994E+10 0.763583E+10
March 0.102765E+11 0.577432E+10 0.450221E+10 0.999277E+10 0.636220E+10
April 0.823605E+10 0.329115E+10 0.494490E+10 0.835482E+10 0.491466E+10
May 0.744752E+10 0.216307E+10 0.528444E+10 0.817857E+10 0.350691E+10
June 0.700315E+10 0.148400E+10 0.551915E+10 0.857461E+10 0.221596E+10
July 0.738738E+10 0.179242E+10 0.559496E+10 0.100021E+11 0.161202E+10
August 0.829355E+10 0.268898E+10 0.560457E+10 0.110709E+11 0.207697E+10
September 0.933187E+10 0.454531E+10 0.478655E+10 0.115243E+11 0.311088E+10
October 0.922686E+10 0.527056E+10 0.395630E+10 0.991060E+10 0.468063E+10
November 0.639492E+10 0.361015E+10 0.278477E+10 0.605248E+10 0.566768E+10
December 0.616629E+10 0.319133E+10 0.297495E+10 0.472190E+10 0.840052E+10
           
Annual Sum or Average 0.947430E+11 0.417827E+11 0.529602E+11 0.100373E+12 0.587725E+11
Minimum of Months 0.616629E+10 0.148400E+10 0.278477E+10 0.472190E+10 0.161202E+10
Maximum of Months 0.102765E+11 0.577432E+10 0.560457E+10 0.115243E+11 0.858824E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.179506E+10 0.421410E+09 0.137365E+10 0.503026E+09 0.638585E+10
February 0.262776E+10 0.675353E+09 0.195240E+10 0.112094E+10 0.547515E+10
March 0.455981E+10 0.195241E+10 0.260741E+10 0.357628E+10 0.443449E+10
April 0.540278E+10 0.221536E+10 0.318742E+10 0.497865E+10 0.326839E+10
May 0.658589E+10 0.297640E+10 0.360949E+10 0.708406E+10 0.237815E+10
June 0.768975E+10 0.361694E+10 0.407281E+10 0.929915E+10 0.157018E+10
July 0.710409E+10 0.311468E+10 0.398941E+10 0.914962E+10 0.117501E+10
August 0.642523E+10 0.273207E+10 0.369316E+10 0.815224E+10 0.146918E+10
September 0.488303E+10 0.210877E+10 0.277426E+10 0.556384E+10 0.210234E+10
October 0.327093E+10 0.115221E+10 0.211872E+10 0.283537E+10 0.322919E+10
November 0.187584E+10 0.540549E+09 0.133529E+10 0.111028E+10 0.397764E+10
December 0.168039E+10 0.366138E+09 0.131425E+10 0.478120E+09 0.618088E+10
           
Annual Sum or Average 0.539006E+11 0.218723E+11 0.320283E+11 0.538516E+11 0.416465E+11
Minimum of Months 0.168039E+10 0.366138E+09 0.131425E+10 0.478120E+09 0.117501E+10
Maximum of Months 0.768975E+10 0.361694E+10 0.407281E+10 0.929915E+10 0.638585E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.09 4260.56 640.28 0.00 640.28 0.00 0.00
February 26.08 4005.36 975.55 0.00 975.55 0.00 0.00
March 309.85 2960.20 1183.06 0.00 1183.06 0.00 0.00
April 704.34 2132.22 1507.47 6.02 1501.45 0.00 0.00
May 1322.13 1282.39 1751.60 74.28 1677.32 0.00 0.00
June 2236.30 818.92 2106.81 179.34 1927.47 0.00 0.00
July 2398.01 571.27 1954.34 126.16 1828.19 0.00 0.00
August 1955.14 756.35 1691.05 25.73 1665.33 0.00 0.00
September 1129.49 1267.78 1286.93 0.27 1286.66 0.00 0.00
October 391.49 2127.25 962.03 0.00 962.03 0.00 0.00
November 84.65 2862.34 646.46 0.00 646.46 0.00 0.00
December 2.91 4204.41 599.28 0.00 599.28 0.00 0.00
               
Annual Sum or Average 885.32 2261.98 1276.65 34.47 1242.18 0.00 0.00
Minimum of Months 0.09 571.27 599.28 0.00 599.28 0.00 0.00
Maximum of Months 2398.01 4260.56 2106.81 179.34 1927.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 277.78 2584.09 781.14 251.88 529.26 0.00 0.00
February 496.02 2434.72 1146.17 343.94 802.23 0.00 0.00
March 1228.91 1792.15 1644.72 688.80 955.92 0.00 0.00
April 1986.69 1307.34 2176.89 961.87 1215.02 0.00 0.00
May 2622.76 862.44 2438.89 1078.85 1360.04 0.00 0.00
June 3294.15 550.26 2723.83 1203.80 1520.03 0.00 0.00
July 3398.89 375.54 2615.60 1151.61 1463.99 0.00 0.00
August 3006.06 485.66 2362.17 991.51 1370.66 0.00 0.00
September 2246.86 803.77 1965.74 871.93 1093.81 0.00 0.00
October 1142.37 1315.17 1333.92 551.74 782.17 0.00 0.00
November 420.48 1773.25 756.62 242.72 513.91 0.00 0.00
December 137.28 2576.08 609.12 125.86 483.26 0.00 0.00
               
Annual Sum or Average 1694.71 1399.82 1715.44 707.09 1008.36 0.00 0.00
Minimum of Months 137.28 375.54 609.12 125.86 483.26 0.00 0.00
Maximum of Months 3398.89 2584.09 2723.83 1203.80 1520.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2173.97 3533.47 2753.22 1607.13 1146.08 0.00 0.00
February 2437.85 3464.45 3143.48 1515.76 1627.72 0.00 0.00
March 3696.45 2638.59 3836.83 2155.89 1680.94 0.00 0.00
April 3185.31 2114.56 3177.50 1269.74 1907.76 0.00 0.00
May 3067.23 1394.20 2780.59 807.60 1972.99 0.00 0.00
June 3335.63 899.63 2701.84 572.53 2129.31 0.00 0.00
July 3763.85 621.24 2758.14 669.22 2088.93 0.00 0.00
August 4162.79 801.54 3096.47 1003.95 2092.52 0.00 0.00
September 4471.82 1275.97 3600.27 1753.60 1846.67 0.00 0.00
October 3670.85 1967.39 3444.93 1967.81 1477.12 0.00 0.00
November 2271.76 2546.14 2467.18 1392.81 1074.38 0.00 0.00
December 1700.80 3549.71 2302.24 1191.51 1110.72 0.00 0.00
               
Annual Sum or Average 3165.78 2059.68 3004.29 1324.93 1679.36 0.00 0.00
Minimum of Months 1700.80 621.24 2302.24 572.53 1074.38 0.00 0.00
Maximum of Months 4471.82 3549.71 3836.83 2155.89 2129.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 162.33 2802.82 670.20 157.34 512.87 0.00 0.00
February 400.94 2696.89 1086.21 279.16 807.05 0.00 0.00
March 1261.91 2031.48 1702.45 728.95 973.50 0.00 0.00
April 1834.76 1556.40 2084.41 854.69 1229.72 0.00 0.00
May 2635.81 983.42 2458.90 1111.26 1347.64 0.00 0.00
June 3594.39 670.81 2966.74 1395.43 1571.31 0.00 0.00
July 3409.38 492.85 2652.38 1162.89 1489.48 0.00 0.00
August 3021.37 632.88 2398.92 1020.04 1378.87 0.00 0.00
September 2132.73 914.90 1883.89 813.57 1070.32 0.00 0.00
October 985.72 1501.69 1221.23 430.19 791.04 0.00 0.00
November 363.46 2036.11 723.71 208.55 515.16 0.00 0.00
December 142.58 2957.77 627.39 136.70 490.69 0.00 0.00
               
Annual Sum or Average 1668.98 1600.96 1709.18 693.57 1015.61 0.00 0.00
Minimum of Months 142.58 492.85 627.39 136.70 490.69 0.00 0.00
Maximum of Months 3594.39 2957.77 2966.74 1395.43 1571.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5.46 3860.64 640.28 0.00 640.28 0.00 0.00
February 54.35 3624.35 975.54 0.00 975.54 0.00 0.00
March 359.84 2668.22 1183.06 0.00 1183.06 0.00 0.00
April 776.47 1920.08 1507.46 6.02 1501.45 0.00 0.00
May 1347.37 1219.36 1751.60 74.28 1677.32 0.00 0.00
June 2254.02 781.43 2106.80 179.34 1927.46 0.00 0.00
July 2424.00 543.70 1954.34 126.16 1828.18 0.00 0.00
August 1981.03 722.01 1691.04 25.73 1665.32 0.00 0.00
September 1153.05 1184.91 1286.92 0.27 1286.65 0.00 0.00
October 446.42 1909.45 962.03 0.00 962.03 0.00 0.00
November 124.05 2477.52 646.46 0.00 646.46 0.00 0.00
December 8.03 3707.52 599.28 0.00 599.28 0.00 0.00
               
Annual Sum or Average 916.40 2043.72 1276.64 34.46 1242.18 0.00 0.00
Minimum of Months 5.46 543.70 599.28 0.00 599.28 0.00 0.00
Maximum of Months 2424.00 3860.64 2106.80 179.34 1927.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 298.60 2344.39 781.13 251.88 529.25 0.00 0.00
February 530.30 2234.27 1146.16 343.94 802.23 0.00 0.00
March 1244.31 1673.23 1644.71 688.79 955.92 0.00 0.00
April 1989.00 1238.39 2176.88 961.86 1215.02 0.00 0.00
May 2601.81 840.88 2438.88 1078.85 1360.04 0.00 0.00
June 3269.36 539.71 2723.82 1203.80 1520.03 0.00 0.00
July 3378.38 373.92 2615.59 1151.61 1463.98 0.00 0.00
August 2982.70 489.60 2362.16 991.51 1370.65 0.00 0.00
September 2233.03 775.76 1965.73 871.92 1093.81 0.00 0.00
October 1152.66 1229.32 1333.91 551.74 782.17 0.00 0.00
November 444.83 1598.69 756.62 242.71 513.90 0.00 0.00
December 154.57 2322.72 609.12 125.86 483.26 0.00 0.00
               
Annual Sum or Average 1696.27 1300.36 1715.44 707.09 1008.35 0.00 0.00
Minimum of Months 154.57 373.92 609.12 125.86 483.26 0.00 0.00
Maximum of Months 3378.38 2344.39 2723.82 1203.80 1520.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2186.84 3367.54 2753.21 1607.13 1146.08 0.00 0.00
February 2452.17 3315.49 3143.47 1515.75 1627.72 0.00 0.00
March 3681.66 2546.64 3836.82 2155.88 1680.93 0.00 0.00
April 3181.72 2026.47 3177.49 1269.73 1907.75 0.00 0.00
May 3045.48 1365.45 2780.58 807.60 1972.99 0.00 0.00
June 3324.14 869.14 2701.83 572.53 2129.30 0.00 0.00
July 3759.89 600.80 2758.13 669.21 2088.92 0.00 0.00
August 4151.89 783.05 3096.46 1003.95 2092.51 0.00 0.00
September 4443.99 1248.25 3600.26 1753.59 1846.66 0.00 0.00
October 3651.08 1904.31 3444.91 1967.80 1477.11 0.00 0.00
November 2278.97 2410.32 2467.18 1392.80 1074.37 0.00 0.00
December 1723.66 3328.81 2302.23 1191.51 1110.72 0.00 0.00
               
Annual Sum or Average 3160.94 1973.30 3004.28 1324.92 1679.36 0.00 0.00
Minimum of Months 1723.66 600.80 2302.23 572.53 1074.37 0.00 0.00
Maximum of Months 4443.99 3367.54 3836.82 2155.88 2129.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 178.99 2484.58 670.20 157.34 512.86 0.00 0.00
February 448.63 2357.05 1086.21 279.16 807.05 0.00 0.00
March 1313.85 1759.59 1702.44 728.94 973.49 0.00 0.00
April 1896.15 1339.79 2084.41 854.69 1229.72 0.00 0.00
May 2642.61 921.99 2458.89 1111.26 1347.63 0.00 0.00
June 3602.59 615.56 2966.72 1395.42 1571.30 0.00 0.00
July 3434.86 439.97 2652.36 1162.89 1489.48 0.00 0.00
August 3056.82 554.13 2398.91 1020.04 1378.87 0.00 0.00
September 2144.96 842.52 1883.89 813.57 1070.32 0.00 0.00
October 1030.58 1305.99 1221.23 430.19 791.04 0.00 0.00
November 405.07 1671.50 723.70 208.55 515.16 0.00 0.00
December 169.76 2423.07 627.39 136.70 490.69 0.00 0.00
               
Annual Sum or Average 1700.48 1388.08 1709.18 693.57 1015.61 0.00 0.00
Minimum of Months 169.76 439.97 627.39 136.70 490.69 0.00 0.00
Maximum of Months 3602.59 2484.58 2966.72 1395.42 1571.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.56 3707.02 640.28 0.00 640.28 0.00 0.00
February 72.00 3466.74 975.54 0.00 975.54 0.00 0.00
March 393.33 2494.27 1183.06 0.00 1183.06 0.00 0.00
April 828.62 1782.36 1507.46 6.02 1501.45 0.00 0.00
May 1370.42 1165.37 1751.60 74.28 1677.32 0.00 0.00
June 2243.71 770.48 2106.80 179.34 1927.46 0.00 0.00
July 2400.78 545.96 1954.34 126.16 1828.18 0.00 0.00
August 1968.35 714.66 1691.04 25.73 1665.32 0.00 0.00
September 1166.90 1127.92 1286.92 0.27 1286.65 0.00 0.00
October 499.21 1728.35 962.03 0.00 962.03 0.00 0.00
November 158.36 2238.21 646.46 0.00 646.46 0.00 0.00
December 13.43 3509.71 599.28 0.00 599.28 0.00 0.00
               
Annual Sum or Average 932.45 1930.04 1276.64 34.46 1242.18 0.00 0.00
Minimum of Months 12.56 545.96 599.28 0.00 599.28 0.00 0.00
Maximum of Months 2400.78 3707.02 2106.80 179.34 1927.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 312.02 2253.14 781.13 251.88 529.25 0.00 0.00
February 554.68 2138.63 1146.16 343.94 802.23 0.00 0.00
March 1282.72 1555.97 1644.71 688.79 955.92 0.00 0.00
April 2028.99 1156.85 2176.88 961.86 1215.02 0.00 0.00
May 2613.43 809.54 2438.88 1078.85 1360.04 0.00 0.00
June 3264.47 533.21 2723.82 1203.80 1520.03 0.00 0.00
July 3367.78 375.39 2615.59 1151.61 1463.98 0.00 0.00
August 2977.54 485.14 2362.16 991.51 1370.65 0.00 0.00
September 2243.52 744.21 1965.73 871.92 1093.81 0.00 0.00
October 1195.79 1118.63 1333.91 551.74 782.17 0.00 0.00
November 480.76 1439.90 756.62 242.71 513.90 0.00 0.00
December 164.99 2204.76 609.12 125.86 483.26 0.00 0.00
               
Annual Sum or Average 1713.44 1230.10 1715.44 707.09 1008.35 0.00 0.00
Minimum of Months 164.99 375.39 609.12 125.86 483.26 0.00 0.00
Maximum of Months 3367.78 2253.14 2723.82 1203.80 1520.03 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2221.49 3206.48 2753.21 1607.13 1146.08 0.00 0.00
February 2496.67 3156.34 3143.47 1515.75 1627.72 0.00 0.00
March 3730.87 2375.38 3836.82 2155.88 1680.93 0.00 0.00
April 3223.31 1896.09 3177.49 1269.73 1907.75 0.00 0.00
May 3053.53 1309.33 2780.58 807.60 1972.99 0.00 0.00
June 3308.10 854.92 2701.83 572.53 2129.30 0.00 0.00
July 3734.34 601.86 2758.13 669.21 2088.92 0.00 0.00
August 4133.40 775.45 3096.46 1003.95 2092.51 0.00 0.00
September 4446.09 1200.19 3600.26 1753.59 1846.66 0.00 0.00
October 3700.19 1747.55 3444.91 1967.80 1477.11 0.00 0.00
November 2335.06 2186.60 2467.18 1392.80 1074.37 0.00 0.00
December 1762.96 3136.39 2302.23 1191.51 1110.72 0.00 0.00
               
Annual Sum or Average 3182.81 1863.66 3004.28 1324.92 1679.36 0.00 0.00
Minimum of Months 1762.96 601.86 2302.23 572.53 1074.37 0.00 0.00
Maximum of Months 4446.09 3206.48 3836.82 2155.88 2129.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 187.81 2384.20 670.20 157.34 512.86 0.00 0.00
February 463.35 2263.21 1086.21 279.16 807.05 0.00 0.00
March 1335.23 1655.65 1702.44 728.94 973.49 0.00 0.00
April 1920.78 1260.95 2084.41 854.69 1229.72 0.00 0.00
May 2644.89 887.90 2458.89 1111.26 1347.63 0.00 0.00
June 3587.63 605.78 2966.72 1395.42 1571.30 0.00 0.00
July 3416.08 438.70 2652.36 1162.89 1489.48 0.00 0.00
August 3043.70 548.53 2398.91 1020.04 1378.87 0.00 0.00
September 2146.54 811.09 1883.89 813.57 1070.32 0.00 0.00
October 1058.61 1205.64 1221.23 430.19 791.04 0.00 0.00
November 428.35 1534.58 723.70 208.55 515.16 0.00 0.00
December 178.51 2307.68 627.39 136.70 490.69 0.00 0.00
               
Annual Sum or Average 1707.62 1320.60 1709.18 693.57 1015.61 0.00 0.00
Minimum of Months 178.51 438.70 627.39 136.70 490.69 0.00 0.00
Maximum of Months 3587.63 2384.20 2966.72 1395.42 1571.30 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 247083.74 0.114115E+11 0.171493E+10 0.00 0.171493E+10 0.00 0.00
February 63104542.50 0.968977E+10 0.236005E+10 0.00 0.236005E+10 0.00 0.00
March 0.829896E+09 0.792859E+10 0.316872E+10 0.00 0.316872E+10 0.00 0.00
April 0.182565E+10 0.552671E+10 0.390735E+10 15591882.90 0.389176E+10 0.00 0.00
May 0.354119E+10 0.343474E+10 0.469149E+10 0.198946E+09 0.449254E+10 0.00 0.00
June 0.579648E+10 0.212263E+10 0.546085E+10 0.464855E+09 0.499599E+10 0.00 0.00
July 0.642284E+10 0.153009E+10 0.523452E+10 0.337900E+09 0.489662E+10 0.00 0.00
August 0.523665E+10 0.202582E+10 0.452931E+10 68903617.40 0.446041E+10 0.00 0.00
September 0.292765E+10 0.328610E+10 0.333571E+10 693016.49 0.333502E+10 0.00 0.00
October 0.104858E+10 0.569764E+10 0.257671E+10 0.00 0.257671E+10 0.00 0.00
November 0.219425E+09 0.741919E+10 0.167563E+10 0.00 0.167563E+10 0.00 0.00
December 7786728.87 0.112611E+11 0.160512E+10 0.00 0.160512E+10 0.00 0.00
               
Annual Sum or Average 0.279195E+11 0.713338E+11 0.402604E+11 0.108689E+10 0.391735E+11 0.00 0.00
Minimum of Months 247083.74 0.153009E+10 0.160512E+10 0.00 0.160512E+10 0.00 0.00
Maximum of Months 0.642284E+10 0.114115E+11 0.546085E+10 0.464855E+09 0.499599E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.744011E+09 0.692122E+10 0.209220E+10 0.674642E+09 0.141756E+10 0.00 0.00
February 0.119997E+10 0.589008E+10 0.277281E+10 0.832051E+09 0.194076E+10 0.00 0.00
March 0.329151E+10 0.480010E+10 0.440521E+10 0.184488E+10 0.256034E+10 0.00 0.00
April 0.514950E+10 0.338862E+10 0.564249E+10 0.249316E+10 0.314934E+10 0.00 0.00
May 0.702480E+10 0.230997E+10 0.653234E+10 0.288960E+10 0.364273E+10 0.00 0.00
June 0.853845E+10 0.142627E+10 0.706018E+10 0.312025E+10 0.393993E+10 0.00 0.00
July 0.910357E+10 0.100584E+10 0.700561E+10 0.308447E+10 0.392114E+10 0.00 0.00
August 0.805142E+10 0.130079E+10 0.632684E+10 0.265566E+10 0.367118E+10 0.00 0.00
September 0.582386E+10 0.208338E+10 0.509519E+10 0.226003E+10 0.283516E+10 0.00 0.00
October 0.305972E+10 0.352256E+10 0.357276E+10 0.147779E+10 0.209497E+10 0.00 0.00
November 0.108987E+10 0.459626E+10 0.196116E+10 0.629118E+09 0.133204E+10 0.00 0.00
December 0.367686E+09 0.689976E+10 0.163146E+10 0.337095E+09 0.129437E+10 0.00 0.00
               
Annual Sum or Average 0.534444E+11 0.441448E+11 0.540982E+11 0.222987E+11 0.317995E+11 0.00 0.00
Minimum of Months 0.367686E+09 0.100584E+10 0.163146E+10 0.337095E+09 0.129437E+10 0.00 0.00
Maximum of Months 0.910357E+10 0.692122E+10 0.706018E+10 0.312025E+10 0.393993E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.582275E+10 0.946405E+10 0.737422E+10 0.430455E+10 0.306967E+10 0.00 0.00
February 0.589765E+10 0.838120E+10 0.760471E+10 0.366693E+10 0.393779E+10 0.00 0.00
March 0.990057E+10 0.706719E+10 0.102766E+11 0.577434E+10 0.450223E+10 0.00 0.00
April 0.825633E+10 0.548093E+10 0.823608E+10 0.329116E+10 0.494492E+10 0.00 0.00
May 0.821527E+10 0.373421E+10 0.744754E+10 0.216308E+10 0.528446E+10 0.00 0.00
June 0.864595E+10 0.233184E+10 0.700317E+10 0.148401E+10 0.551917E+10 0.00 0.00
July 0.100811E+11 0.166392E+10 0.738741E+10 0.179243E+10 0.559498E+10 0.00 0.00
August 0.111496E+11 0.214686E+10 0.829358E+10 0.268899E+10 0.560459E+10 0.00 0.00
September 0.115909E+11 0.330731E+10 0.933190E+10 0.454533E+10 0.478657E+10 0.00 0.00
October 0.983201E+10 0.526945E+10 0.922689E+10 0.527058E+10 0.395631E+10 0.00 0.00
November 0.588840E+10 0.659960E+10 0.639494E+10 0.361016E+10 0.278478E+10 0.00 0.00
December 0.455541E+10 0.950755E+10 0.616631E+10 0.319134E+10 0.297496E+10 0.00 0.00
               
Annual Sum or Average 0.998360E+11 0.649541E+11 0.947433E+11 0.417829E+11 0.529604E+11 0.00 0.00
Minimum of Months 0.455541E+10 0.166392E+10 0.616631E+10 0.148401E+10 0.278478E+10 0.00 0.00
Maximum of Months 0.115909E+11 0.950755E+10 0.102766E+11 0.577434E+10 0.560459E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.434786E+09 0.750708E+10 0.179507E+10 0.421412E+09 0.137366E+10 0.00 0.00
February 0.969951E+09 0.652432E+10 0.262777E+10 0.675356E+09 0.195241E+10 0.00 0.00
March 0.337991E+10 0.544112E+10 0.455983E+10 0.195241E+10 0.260742E+10 0.00 0.00
April 0.475570E+10 0.403419E+10 0.540280E+10 0.221537E+10 0.318744E+10 0.00 0.00
May 0.705977E+10 0.263399E+10 0.658592E+10 0.297641E+10 0.360951E+10 0.00 0.00
June 0.931666E+10 0.173874E+10 0.768978E+10 0.361696E+10 0.407283E+10 0.00 0.00
July 0.913168E+10 0.132006E+10 0.710412E+10 0.311469E+10 0.398943E+10 0.00 0.00
August 0.809243E+10 0.169512E+10 0.642526E+10 0.273208E+10 0.369318E+10 0.00 0.00
September 0.552804E+10 0.237142E+10 0.488305E+10 0.210878E+10 0.277427E+10 0.00 0.00
October 0.264014E+10 0.402214E+10 0.327094E+10 0.115221E+10 0.211873E+10 0.00 0.00
November 0.942091E+09 0.527760E+10 0.187584E+10 0.540552E+09 0.133529E+10 0.00 0.00
December 0.381878E+09 0.792210E+10 0.168040E+10 0.366140E+09 0.131426E+10 0.00 0.00
               
Annual Sum or Average 0.526330E+11 0.504879E+11 0.539008E+11 0.218724E+11 0.320284E+11 0.00 0.00
Minimum of Months 0.381878E+09 0.132006E+10 0.168040E+10 0.366140E+09 0.131426E+10 0.00 0.00
Maximum of Months 0.931666E+10 0.792210E+10 0.768978E+10 0.361696E+10 0.407283E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 14627437.81 0.103403E+11 0.171492E+10 0.00 0.171492E+10 0.00 0.00
February 0.131483E+09 0.876803E+10 0.236004E+10 0.00 0.236004E+10 0.00 0.00
March 0.963786E+09 0.714657E+10 0.316871E+10 0.00 0.316871E+10 0.00 0.00
April 0.201260E+10 0.497685E+10 0.390734E+10 15591827.53 0.389175E+10 0.00 0.00
May 0.360880E+10 0.326593E+10 0.469147E+10 0.198945E+09 0.449253E+10 0.00 0.00
June 0.584242E+10 0.202547E+10 0.546083E+10 0.464853E+09 0.499597E+10 0.00 0.00
July 0.649244E+10 0.145625E+10 0.523450E+10 0.337898E+09 0.489660E+10 0.00 0.00
August 0.530600E+10 0.193383E+10 0.452929E+10 68903372.72 0.446039E+10 0.00 0.00
September 0.298871E+10 0.307128E+10 0.333570E+10 693014.03 0.333501E+10 0.00 0.00
October 0.119568E+10 0.511427E+10 0.257670E+10 0.00 0.257670E+10 0.00 0.00
November 0.321538E+09 0.642174E+10 0.167562E+10 0.00 0.167562E+10 0.00 0.00
December 21513712.81 0.993023E+10 0.160512E+10 0.00 0.160512E+10 0.00 0.00
               
Annual Sum or Average 0.288996E+11 0.644508E+11 0.402602E+11 0.108689E+10 0.391733E+11 0.00 0.00
Minimum of Months 14627437.81 0.145625E+10 0.160512E+10 0.00 0.160512E+10 0.00 0.00
Maximum of Months 0.649244E+10 0.103403E+11 0.546083E+10 0.464853E+09 0.499597E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.799779E+09 0.627921E+10 0.209219E+10 0.674639E+09 0.141755E+10 0.00 0.00
February 0.128291E+10 0.540514E+10 0.277280E+10 0.832048E+09 0.194075E+10 0.00 0.00
March 0.333277E+10 0.448157E+10 0.440520E+10 0.184487E+10 0.256033E+10 0.00 0.00
April 0.515549E+10 0.320991E+10 0.564247E+10 0.249315E+10 0.314932E+10 0.00 0.00
May 0.696868E+10 0.225223E+10 0.653231E+10 0.288959E+10 0.364272E+10 0.00 0.00
June 0.847419E+10 0.139892E+10 0.706015E+10 0.312024E+10 0.393991E+10 0.00 0.00
July 0.904866E+10 0.100151E+10 0.700558E+10 0.308446E+10 0.392112E+10 0.00 0.00
August 0.798886E+10 0.131136E+10 0.632681E+10 0.265565E+10 0.367116E+10 0.00 0.00
September 0.578802E+10 0.201076E+10 0.509517E+10 0.226002E+10 0.283515E+10 0.00 0.00
October 0.308728E+10 0.329260E+10 0.357274E+10 0.147778E+10 0.209496E+10 0.00 0.00
November 0.115300E+10 0.414381E+10 0.196115E+10 0.629115E+09 0.133204E+10 0.00 0.00
December 0.414001E+09 0.622118E+10 0.163145E+10 0.337094E+09 0.129436E+10 0.00 0.00
               
Annual Sum or Average 0.534936E+11 0.410082E+11 0.540980E+11 0.222987E+11 0.317994E+11 0.00 0.00
Minimum of Months 0.414001E+09 0.100151E+10 0.163145E+10 0.337094E+09 0.129436E+10 0.00 0.00
Maximum of Months 0.904866E+10 0.627921E+10 0.706015E+10 0.312024E+10 0.393991E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.585723E+10 0.901962E+10 0.737419E+10 0.430453E+10 0.306966E+10 0.00 0.00
February 0.593230E+10 0.802082E+10 0.760469E+10 0.366691E+10 0.393777E+10 0.00 0.00
March 0.986097E+10 0.682093E+10 0.102765E+11 0.577432E+10 0.450221E+10 0.00 0.00
April 0.824702E+10 0.525261E+10 0.823605E+10 0.329115E+10 0.494490E+10 0.00 0.00
May 0.815700E+10 0.365721E+10 0.744752E+10 0.216307E+10 0.528444E+10 0.00 0.00
June 0.861618E+10 0.225281E+10 0.700315E+10 0.148400E+10 0.551915E+10 0.00 0.00
July 0.100705E+11 0.160918E+10 0.738738E+10 0.179242E+10 0.559496E+10 0.00 0.00
August 0.111204E+11 0.209733E+10 0.829355E+10 0.268898E+10 0.560457E+10 0.00 0.00
September 0.115188E+11 0.323547E+10 0.933187E+10 0.454531E+10 0.478655E+10 0.00 0.00
October 0.977905E+10 0.510051E+10 0.922686E+10 0.527056E+10 0.395630E+10 0.00 0.00
November 0.590710E+10 0.624755E+10 0.639492E+10 0.361015E+10 0.278477E+10 0.00 0.00
December 0.461665E+10 0.891589E+10 0.616629E+10 0.319133E+10 0.297495E+10 0.00 0.00
               
Annual Sum or Average 0.996832E+11 0.622299E+11 0.947430E+11 0.417827E+11 0.529602E+11 0.00 0.00
Minimum of Months 0.461665E+10 0.160918E+10 0.616629E+10 0.148400E+10 0.278477E+10 0.00 0.00
Maximum of Months 0.115188E+11 0.901962E+10 0.102765E+11 0.577432E+10 0.560457E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.479416E+09 0.665471E+10 0.179506E+10 0.421410E+09 0.137365E+10 0.00 0.00
February 0.108533E+10 0.570217E+10 0.262776E+10 0.675353E+09 0.195240E+10 0.00 0.00
March 0.351902E+10 0.471289E+10 0.455981E+10 0.195241E+10 0.260741E+10 0.00 0.00
April 0.491481E+10 0.347273E+10 0.540278E+10 0.221536E+10 0.318742E+10 0.00 0.00
May 0.707798E+10 0.246947E+10 0.658589E+10 0.297640E+10 0.360949E+10 0.00 0.00
June 0.933791E+10 0.159552E+10 0.768975E+10 0.361694E+10 0.407281E+10 0.00 0.00
July 0.919992E+10 0.117843E+10 0.710409E+10 0.311468E+10 0.398941E+10 0.00 0.00
August 0.818738E+10 0.148418E+10 0.642523E+10 0.273207E+10 0.369316E+10 0.00 0.00
September 0.555974E+10 0.218381E+10 0.488303E+10 0.210877E+10 0.277426E+10 0.00 0.00
October 0.276031E+10 0.349798E+10 0.327093E+10 0.115221E+10 0.211872E+10 0.00 0.00
November 0.104995E+10 0.433254E+10 0.187584E+10 0.540549E+09 0.133529E+10 0.00 0.00
December 0.454693E+09 0.648995E+10 0.168039E+10 0.366138E+09 0.131425E+10 0.00 0.00
               
Annual Sum or Average 0.536265E+11 0.437744E+11 0.539006E+11 0.218723E+11 0.320283E+11 0.00 0.00
Minimum of Months 0.454693E+09 0.117843E+10 0.168039E+10 0.366138E+09 0.131425E+10 0.00 0.00
Maximum of Months 0.933791E+10 0.665471E+10 0.768975E+10 0.361694E+10 0.407281E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 33652015.24 0.992887E+10 0.171492E+10 0.00 0.171492E+10 0.00 0.00
February 0.174191E+09 0.838675E+10 0.236004E+10 0.00 0.236004E+10 0.00 0.00
March 0.105348E+10 0.668064E+10 0.316871E+10 0.00 0.316871E+10 0.00 0.00
April 0.214778E+10 0.461988E+10 0.390734E+10 15591827.53 0.389175E+10 0.00 0.00
May 0.367053E+10 0.312134E+10 0.469147E+10 0.198945E+09 0.449253E+10 0.00 0.00
June 0.581570E+10 0.199708E+10 0.546083E+10 0.464853E+09 0.499597E+10 0.00 0.00
July 0.643025E+10 0.146231E+10 0.523450E+10 0.337898E+09 0.489660E+10 0.00 0.00
August 0.527204E+10 0.191415E+10 0.452929E+10 68903372.72 0.446039E+10 0.00 0.00
September 0.302462E+10 0.292356E+10 0.333570E+10 693014.03 0.333501E+10 0.00 0.00
October 0.133708E+10 0.462922E+10 0.257670E+10 0.00 0.257670E+10 0.00 0.00
November 0.410474E+09 0.580144E+10 0.167562E+10 0.00 0.167562E+10 0.00 0.00
December 35981068.18 0.940041E+10 0.160512E+10 0.00 0.160512E+10 0.00 0.00
               
Annual Sum or Average 0.294058E+11 0.608656E+11 0.402602E+11 0.108689E+10 0.391733E+11 0.00 0.00
Minimum of Months 33652015.24 0.146231E+10 0.160512E+10 0.00 0.160512E+10 0.00 0.00
Maximum of Months 0.643025E+10 0.992887E+10 0.546083E+10 0.464853E+09 0.499597E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.835702E+09 0.603481E+10 0.209219E+10 0.674639E+09 0.141755E+10 0.00 0.00
February 0.134187E+10 0.517379E+10 0.277280E+10 0.832048E+09 0.194075E+10 0.00 0.00
March 0.343564E+10 0.416751E+10 0.440520E+10 0.184487E+10 0.256033E+10 0.00 0.00
April 0.525915E+10 0.299855E+10 0.564247E+10 0.249315E+10 0.314932E+10 0.00 0.00
May 0.699981E+10 0.216828E+10 0.653231E+10 0.288959E+10 0.364272E+10 0.00 0.00
June 0.846152E+10 0.138207E+10 0.706015E+10 0.312024E+10 0.393991E+10 0.00 0.00
July 0.902026E+10 0.100543E+10 0.700558E+10 0.308446E+10 0.392112E+10 0.00 0.00
August 0.797503E+10 0.129941E+10 0.632681E+10 0.265565E+10 0.367116E+10 0.00 0.00
September 0.581520E+10 0.192900E+10 0.509517E+10 0.226002E+10 0.283515E+10 0.00 0.00
October 0.320281E+10 0.299613E+10 0.357274E+10 0.147778E+10 0.209496E+10 0.00 0.00
November 0.124613E+10 0.373223E+10 0.196115E+10 0.629115E+09 0.133204E+10 0.00 0.00
December 0.441918E+09 0.590524E+10 0.163145E+10 0.337094E+09 0.129436E+10 0.00 0.00
               
Annual Sum or Average 0.540350E+11 0.387925E+11 0.540980E+11 0.222987E+11 0.317994E+11 0.00 0.00
Minimum of Months 0.441918E+09 0.100543E+10 0.163145E+10 0.337094E+09 0.129436E+10 0.00 0.00
Maximum of Months 0.902026E+10 0.603481E+10 0.706015E+10 0.312024E+10 0.393991E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.595005E+10 0.858824E+10 0.737419E+10 0.430453E+10 0.306966E+10 0.00 0.00
February 0.603994E+10 0.763583E+10 0.760469E+10 0.366691E+10 0.393777E+10 0.00 0.00
March 0.999277E+10 0.636220E+10 0.102765E+11 0.577432E+10 0.450221E+10 0.00 0.00
April 0.835482E+10 0.491466E+10 0.823605E+10 0.329115E+10 0.494490E+10 0.00 0.00
May 0.817857E+10 0.350691E+10 0.744752E+10 0.216307E+10 0.528444E+10 0.00 0.00
June 0.857461E+10 0.221596E+10 0.700315E+10 0.148400E+10 0.551915E+10 0.00 0.00
July 0.100021E+11 0.161202E+10 0.738738E+10 0.179242E+10 0.559496E+10 0.00 0.00
August 0.110709E+11 0.207697E+10 0.829355E+10 0.268898E+10 0.560457E+10 0.00 0.00
September 0.115243E+11 0.311088E+10 0.933187E+10 0.454531E+10 0.478655E+10 0.00 0.00
October 0.991060E+10 0.468063E+10 0.922686E+10 0.527056E+10 0.395630E+10 0.00 0.00
November 0.605248E+10 0.566768E+10 0.639492E+10 0.361015E+10 0.278477E+10 0.00 0.00
December 0.472190E+10 0.840052E+10 0.616629E+10 0.319133E+10 0.297495E+10 0.00 0.00
               
Annual Sum or Average 0.100373E+12 0.587725E+11 0.947430E+11 0.417827E+11 0.529602E+11 0.00 0.00
Minimum of Months 0.472190E+10 0.161202E+10 0.616629E+10 0.148400E+10 0.278477E+10 0.00 0.00
Maximum of Months 0.115243E+11 0.858824E+10 0.102765E+11 0.577432E+10 0.560457E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.503026E+09 0.638585E+10 0.179506E+10 0.421410E+09 0.137365E+10 0.00 0.00
February 0.112094E+10 0.547515E+10 0.262776E+10 0.675353E+09 0.195240E+10 0.00 0.00
March 0.357628E+10 0.443449E+10 0.455981E+10 0.195241E+10 0.260741E+10 0.00 0.00
April 0.497865E+10 0.326839E+10 0.540278E+10 0.221536E+10 0.318742E+10 0.00 0.00
May 0.708406E+10 0.237815E+10 0.658589E+10 0.297640E+10 0.360949E+10 0.00 0.00
June 0.929915E+10 0.157018E+10 0.768975E+10 0.361694E+10 0.407281E+10 0.00 0.00
July 0.914962E+10 0.117501E+10 0.710409E+10 0.311468E+10 0.398941E+10 0.00 0.00
August 0.815224E+10 0.146918E+10 0.642523E+10 0.273207E+10 0.369316E+10 0.00 0.00
September 0.556384E+10 0.210234E+10 0.488303E+10 0.210877E+10 0.277426E+10 0.00 0.00
October 0.283537E+10 0.322919E+10 0.327093E+10 0.115221E+10 0.211872E+10 0.00 0.00
November 0.111028E+10 0.397764E+10 0.187584E+10 0.540549E+09 0.133529E+10 0.00 0.00
December 0.478120E+09 0.618088E+10 0.168039E+10 0.366138E+09 0.131425E+10 0.00 0.00
               
Annual Sum or Average 0.538516E+11 0.416465E+11 0.539006E+11 0.218723E+11 0.320283E+11 0.00 0.00
Minimum of Months 0.478120E+09 0.117501E+10 0.168039E+10 0.366138E+09 0.131425E+10 0.00 0.00
Maximum of Months 0.929915E+10 0.638585E+10 0.768975E+10 0.361694E+10 0.407281E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -3.4 -4.9 -8.7 5.96 -14.4 41.15 62.17 0.00
February -4.2 -5.4 -8.1 6.66 -15.1 65.72 71.39 0.00
March 2.67 0.66 -2.8 5.20 -8.9 69.76 141.76 0.00
April 7.47 4.95 1.92 5.29 -2.7 89.32 159.79 0.00
May 13.73 9.66 5.81 4.79 3.34 93.75 203.34 0.03
June 18.63 14.47 11.49 5.10 8.69 105.42 236.95 0.00
July 22.03 18.19 16.11 4.43 13.39 102.98 214.28 0.00
August 20.69 16.39 13.72 4.23 11.88 99.24 178.64 0.00
September 16.55 13.42 11.22 4.10 7.08 75.66 154.97 0.03
October 9.73 7.36 4.97 4.79 0.13 58.70 104.01 0.00
November 6.03 3.70 0.77 5.87 -3.2 41.19 58.47 0.00
December -2.2 -3.2 -5.3 6.59 -12.0 40.52 44.30 0.00
                 
Annual Sum or Average 9.05 6.33 3.49 5.24 -0.9 73.64 136.19 0.01
Minimum of Months -4.2 -5.4 -8.7 4.10 -15.1 40.52 44.30 0.00
Maximum of Months 22.03 18.19 16.11 6.66 13.39 105.42 236.95 0.03



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 11-JAN-15:00 10.14 8.90 13.40 7.15 65.50 1.00
February 12.80 22-FEB-17:00 6.18 -2.2 14.90 3.48 0.00 0.00
March 26.10 15-MAR-13:00 16.06 9.40 6.70 14.65 249.50 400.00
April 21.10 08-APR-12:00 13.43 7.80 8.20 11.46 330.00 283.50
May 26.10 10-MAY-13:00 17.84 13.30 5.20 13.35 258.50 457.00
June 30.60 12-JUN-13:00 20.23 15.00 8.20 17.93 252.00 572.00
July 31.70 21-JUL-13:00 21.73 17.20 5.20 22.47 330.00 231.00
August 30.60 10-AUG-13:00 20.24 15.00 5.70 19.70 220.50 635.00
September 27.20 16-SEP-13:09 19.53 15.68 8.80 17.30 207.00 564.67
October 22.20 11-OCT-12:00 14.14 8.30 6.20 6.95 121.00 665.00
November 19.40 05-NOV-13:00 13.85 10.00 12.40 14.84 133.00 3.50
December 15.00 01-DEC-10:00 12.41 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 11.70   6.18 -2.2 5.20 3.48 0.00 0.00
Maximum of Months 31.70   21.73 17.20 14.90 22.47 330.00 665.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -13.9 31-JAN-01:00 -14.5 -17.2 1.50 -25.9 0.00 0.00
February -16.7 07-FEB-06:00 -17.3 -20.6 6.20 -35.1 0.00 0.00
March -13.3 07-MAR-05:19 -13.9 -16.7 2.43 -32.2 0.00 0.00
April -4.4 17-APR-05:00 -5.4 -7.8 2.10 -20.5 35.00 151.50
May 1.70 01-MAY-04:00 0.96 0.00 0.00 -14.2 0.00 0.00
June 6.70 04-JUN-04:00 5.40 3.90 2.10 -7.3 20.00 104.00
July 11.70 03-JUL-03:00 11.07 10.60 2.10 -1.2 0.00 0.00
August 11.10 01-AUG-04:00 10.75 10.60 2.10 -0.8 0.00 0.00
September 6.10 05-SEP-05:00 5.59 5.00 2.10 -6.2 24.50 41.00
October -2.8 17-OCT-04:10 -3.2 -4.0 2.18 -19.4 0.00 0.00
November -3.9 24-NOV-05:00 -4.5 -5.6 2.10 -18.1 0.00 0.00
December -18.9 11-DEC-05:00 -19.4 -23.3 2.10 -35.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -18.9   -19.4 -23.3 0.00 -35.1 0.00 0.00
Maximum of Months 11.70   11.07 10.60 6.20 -0.8 35.00 151.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.21 11-JAN-17:00 11.10 9.40 10.30 6.55 0.00 0.00
February 6.89 01-FEB-03:00 7.20 6.70 3.60 2.22 0.00 0.00
March 17.83 14-MAR-12:00 25.00 13.90 6.20 14.10 197.00 562.50
April 13.78 08-APR-13:00 20.60 8.90 10.30 9.72 268.50 325.50
May 18.19 10-MAY-14:00 26.10 13.90 5.20 16.85 273.00 238.00
June 23.75 27-JUN-12:00 30.60 21.10 9.30 21.09 304.00 606.00
July 24.79 21-JUL-01:00 28.90 23.30 8.80 27.46 0.00 0.00
August 23.42 13-AUG-15:00 29.40 21.10 9.80 19.87 212.00 276.00
September 21.17 15-SEP-11:00 26.10 18.90 3.60 16.30 204.00 464.50
October 15.23 12-OCT-14:00 18.30 13.30 10.30 9.13 148.00 367.50
November 13.96 05-NOV-14:00 18.30 11.10 11.30 14.10 72.00 6.00
December 12.41 01-DEC-10:00 15.00 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 6.89   7.20 6.70 3.60 2.22 0.00 0.00
Maximum of Months 24.79   30.60 23.30 12.90 27.46 304.00 606.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 11-JAN-13:00 10.00 9.66 12.90 5.54 95.50 2.00
February 6.70 01-FEB-04:10 7.20 6.89 3.52 2.22 0.00 0.00
March 15.00 14-MAR-10:20 20.33 16.97 4.80 10.50 159.17 592.83
April 11.10 08-APR-21:00 13.90 12.23 12.90 9.72 0.00 0.00
May 15.60 17-MAY-12:00 16.70 15.97 6.70 13.54 184.00 0.00
June 21.70 27-JUN-14:00 25.60 22.78 8.20 16.85 255.50 530.00
July 23.30 20-JUL-20:00 25.60 24.03 4.60 24.16 0.00 0.00
August 21.70 14-AUG-03:20 23.70 22.19 5.00 21.90 0.00 0.00
September 20.00 15-SEP-18:00 21.70 20.51 0.00 19.52 0.00 0.00
October 14.40 01-OCT-07:19 14.60 14.50 3.77 10.56 67.50 30.17
November 11.70 05-NOV-15:00 12.80 12.14 7.20 8.74 28.00 4.50
December 11.10 01-DEC-12:00 13.90 12.22 10.30 6.35 158.00 84.50
                 
Annual Sum or Average                
Minimum of Months 6.70   7.20 6.89 0.00 2.22 0.00 0.00
Maximum of Months 23.30   25.60 24.03 12.90 24.16 255.50 592.83



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 7.32 12.49 0.00
February 18.00 13.00 16.00 6.57 19.26 0.00
March 18.00 13.00 16.00 7.29 28.63 0.00
April 18.00 13.00 16.00 9.34 37.44 0.00
May 18.00 13.00 16.00 12.19 46.60 0.00
June 18.00 13.00 16.00 15.07 54.01 0.00
July 18.00 13.00 16.00 17.20 50.29 0.00
August 18.00 13.00 16.00 18.01 43.20 0.00
September 18.00 13.00 16.00 17.27 32.93 0.00
October 18.00 13.00 16.00 15.18 21.28 0.00
November 18.00 13.00 16.00 12.32 12.54 0.00
December 18.00 13.00 16.00 9.45 10.96 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.30 30.86 0.00
Minimum of Months 18.00 13.00 16.00 6.57 10.96 0.00
Maximum of Months 18.00 13.00 16.00 18.01 54.01 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.423658E+11 -0.419189E+11 0.00 0.00 744.00 0.00 -446912206.1 60.05 0.00 0.00
February 0.390361E+11 -0.386325E+11 0.00 0.00 672.00 0.00 -403600846.2 60.05 0.00 0.00
March 0.452819E+11 -0.448357E+11 0.00 0.00 744.00 0.00 -446228522.9 60.05 0.00 0.00
April 0.395098E+11 -0.390803E+11 0.00 0.00 720.00 0.00 -429451430.7 60.05 0.00 0.00
May 0.398587E+11 -0.394149E+11 0.00 0.00 744.00 0.00 -443792871.7 60.05 0.00 0.00
June 0.371225E+11 -0.367014E+11 0.00 0.00 720.00 0.00 -421069796.2 60.05 0.00 0.00
July 0.336581E+11 -0.332332E+11 0.00 0.00 744.00 0.00 -424880546.1 60.05 0.00 0.00
August 0.361504E+11 -0.357176E+11 0.00 0.00 744.00 0.00 -432734335.1 60.05 0.00 0.00
September 0.334000E+11 -0.329757E+11 0.00 0.00 720.00 0.00 -424285390.7 60.05 0.00 0.00
October 0.361214E+11 -0.356802E+11 0.00 0.00 744.00 0.00 -441265841.5 60.05 0.00 0.00
November 0.376516E+11 -0.372240E+11 0.00 0.00 720.00 0.00 -427625531.1 60.05 0.00 0.00
December 0.396971E+11 -0.392532E+11 0.00 0.00 744.00 0.00 -443859996.4 60.05 0.00 0.00
                     
Annual Sum or Average 0.459853E+12 -0.454668E+12 0.00 0.00 8760.00 0.00 -0.518571E+10 60.05 0.00 0.00
Minimum of Months 0.334000E+11 -0.448357E+11 0.00 0.00 672.00 0.00 -446912206.1 60.05 0.00 0.00
Maximum of Months 0.452819E+11 -0.329757E+11 0.00 0.00 744.00 0.00 -403600846.2 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.49 0.48 01-JAN-09:09 4421.25 32.94 239.17 251.33 3523.72 33.90 243.67 223.67
February 262.50 0.49 0.48 01-FEB-09:39 5558.69 33.10 251.67 256.83 1787.44 26.25 228.17 233.50
March 339.33 0.49 0.48 01-MAR-07:40 7928.68 30.46 270.00 327.50 1469.56 22.61 233.50 293.67
April 371.17 0.50 0.48 01-APR-06:00 2108.09 20.44 152.00 346.67 1164.55 21.82 251.67 312.17
May 332.17 0.50 0.48 01-MAY-06:30 1928.19 20.48 119.33 385.67 1121.20 21.91 251.17 338.83
June 430.67 0.50 0.48 01-JUN-06:10 1743.49 20.25 139.50 394.67 992.53 21.66 285.50 354.67
July 439.00 0.50 0.48 01-JUL-06:10 1823.91 20.30 162.67 401.83 1023.05 21.71 279.50 356.17
August 406.00 0.50 0.48 01-AUG-06:19 2149.77 20.80 201.33 378.33 1176.85 22.19 290.83 338.33
September 289.17 0.50 0.48 01-SEP-07:40 3037.97 22.24 174.83 325.67 1532.12 22.84 256.50 292.67
October 314.33 0.49 0.48 01-OCT-07:19 6416.85 32.63 283.33 298.83 1558.11 23.31 230.67 276.83
November 258.33 0.50 0.48 01-NOV-07:40 4168.44 32.78 243.50 241.50 1668.95 28.44 232.33 217.00
December 230.67 0.49 0.48 01-DEC-08:09 3740.64 32.03 219.50 239.50 2890.37 33.26 227.00 208.00
                         
Annual Sum or Average 3928.50 0.50     3553.59 25.57 2456.83 3848.33 1541.73 24.29 3010.50 3445.50
Minimum of Months 230.67 0.49 0.48   1743.49 20.25 119.33 239.50 992.53 21.66 227.00 208.00
Maximum of Months 439.00 0.50 0.48   7928.68 33.10 283.33 401.83 3523.72 33.90 290.83 356.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:09 1545.78 23.03 97.00 238.00 763.99 23.03 135.83 190.33
February 262.50 0.50 0.48 01-FEB-09:39 2133.33 24.04 129.83 248.83 1095.46 24.24 175.83 218.50
March 339.33 0.49 0.48 01-MAR-07:19 2893.60 24.69 147.00 321.33 1251.40 24.00 191.67 287.67
April 371.17 0.50 0.48 01-APR-06:30 3129.52 24.13 139.00 352.00 1749.58 24.63 219.17 318.33
May 332.17 0.49 0.48 01-MAY-05:30 4151.88 24.83 108.33 394.00 1755.13 24.12 211.50 350.50
June 430.67 0.50 0.48 01-JUN-05:49 3779.99 24.08 142.50 404.50 1656.21 23.85 230.17 374.67
July 439.00 0.50 0.48 01-JUL-04:00 3580.14 24.28 146.17 411.50 1567.59 23.85 247.33 374.67
August 406.00 0.50 0.48 01-AUG-05:49 3328.10 24.56 151.00 381.00 1461.57 24.07 258.50 347.50
September 289.17 0.50 0.48 01-SEP-07:40 3361.73 25.07 124.17 326.33 1831.96 25.31 205.17 289.33
October 314.33 0.50 0.48 01-OCT-06:00 2159.24 23.95 125.50 290.67 1140.43 24.11 185.50 256.50
November 258.33 0.51 0.48 01-NOV-07:40 1554.74 23.28 105.33 231.67 843.53 23.45 137.33 179.50
December 230.67 0.50 0.48 01-DEC-07:00 1339.82 22.86 89.83 227.00 666.70 23.06 124.33 175.17
                         
Annual Sum or Average 3928.50 0.50     2899.16 24.14 1505.67 3826.83 1373.11 24.01 2322.33 3362.67
Minimum of Months 230.67 0.49 0.48   1339.82 22.86 89.83 227.00 666.70 23.03 124.33 175.17
Maximum of Months 439.00 0.51 0.48   4151.88 25.07 151.00 411.50 1831.96 25.31 258.50 374.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-10:09 675.95 17.63 0.00 222.50 376.23 19.04 0.50 142.33
February 262.50 0.51 0.48 01-FEB-10:20 887.79 18.62 0.00 243.00 491.89 19.96 48.83 194.33
March 339.33 0.50 0.48 01-MAR-08:09 945.30 19.13 0.00 315.67 551.73 20.56 84.67 267.33
April 371.17 0.50 0.48 01-APR-06:49 1095.02 19.63 6.67 350.83 639.04 20.95 171.83 316.67
May 332.17 0.49 0.48 01-MAY-05:00 1314.37 21.69 90.00 402.83 789.95 22.88 249.67 363.33
June 430.67 0.49 0.48 01-JUN-05:00 1462.21 23.01 173.50 413.33 822.76 22.17 308.33 385.17
July 439.00 0.49 0.48 01-JUL-05:19 1391.56 22.69 158.83 419.50 808.59 22.98 313.67 389.17
August 406.00 0.49 0.48 01-AUG-05:00 1234.54 20.33 57.50 388.00 729.18 21.67 268.00 354.00
September 289.17 0.50 0.48 01-SEP-07:40 1038.23 19.85 1.17 322.50 638.49 21.28 147.83 273.67
October 314.33 0.51 0.48 01-OCT-07:40 827.60 18.39 0.00 282.33 474.32 19.81 33.33 225.17
November 258.33 0.53 0.48 01-NOV-08:20 655.42 17.08 0.00 218.50 363.17 18.41 1.50 130.33
December 230.67 0.51 0.48 01-DEC-11:00 678.92 17.56 0.00 208.17 369.54 18.88 1.50 121.33
                         
Annual Sum or Average 3928.50 0.50     1068.46 19.98 487.67 3787.17 618.57 20.97 1629.67 3162.83
Minimum of Months 230.67 0.49 0.48   655.42 17.08 0.00 208.17 363.17 18.41 0.50 121.33
Maximum of Months 439.00 0.53 0.48   1462.21 23.01 173.50 419.50 822.76 22.98 313.67 389.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:50 1450.50 23.30 105.00 237.50 781.71 23.62 142.00 191.50
February 262.50 0.50 0.48 01-FEB-10:09 1994.06 23.88 126.83 249.17 1046.13 24.22 177.00 218.33
March 339.33 0.49 0.48 01-MAR-08:09 2842.91 24.52 143.17 324.17 1598.40 24.93 203.50 289.33
April 371.17 0.50 0.48 01-APR-07:10 3328.04 23.25 131.17 347.83 1402.88 22.80 193.33 314.83
May 332.17 0.49 0.48 01-MAY-06:30 3578.51 21.19 52.17 392.50 1958.75 21.25 175.83 355.67
June 430.67 0.50 0.48 01-JUN-06:19 3767.46 20.99 64.00 402.67 1614.32 21.23 214.83 371.50
July 439.00 0.50 0.48 01-JUL-06:10 3367.44 21.01 74.83 408.83 1522.14 21.35 218.33 373.00
August 406.00 0.49 0.48 01-AUG-06:30 3156.61 22.56 119.17 384.17 1697.89 23.18 234.67 349.50
September 289.17 0.50 0.48 01-SEP-07:49 3485.23 24.81 116.67 323.50 1508.91 23.99 197.67 291.83
October 314.33 0.50 0.48 01-OCT-07:49 2026.91 23.74 125.50 289.83 1063.88 24.02 181.83 255.83
November 258.33 0.52 0.48 01-NOV-08:20 1487.39 22.86 102.50 230.50 784.38 23.02 134.17 184.00
December 230.67 0.50 0.48 01-DEC-11:39 1396.86 22.82 91.33 223.50 731.65 23.21 129.17 175.33
                         
Annual Sum or Average 3928.50 0.50     2804.12 22.76 1252.33 3814.17 1370.18 22.93 2202.33 3370.67
Minimum of Months 230.67 0.49 0.48   1396.86 20.99 52.17 223.50 731.65 21.23 129.17 175.33
Maximum of Months 439.00 0.52 0.48   3767.46 24.81 143.17 408.83 1958.75 24.93 234.67 373.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.49 0.48 01-JAN-08:00 4435.75 32.12 233.00 251.50 3611.30 33.12 231.83 226.17
February 262.50 0.49 0.48 01-FEB-09:39 5578.25 32.40 241.33 256.83 1934.82 24.28 106.33 239.50
March 339.33 0.49 0.48 01-MAR-07:30 7974.67 28.59 228.50 327.67 1584.66 18.07 11.33 297.17
April 371.17 0.50 0.48 01-APR-06:49 2141.69 14.09 0.00 347.67 1244.90 17.54 1.33 317.33
May 332.17 0.50 0.48 01-MAY-06:30 1966.89 14.42 0.00 385.67 1199.75 17.95 0.00 343.50
June 430.67 0.50 0.48 01-JUN-06:10 1772.96 14.29 0.00 394.83 1059.34 17.75 0.00 360.00
July 439.00 0.50 0.48 01-JUL-05:00 1853.17 14.23 0.00 402.83 1091.64 17.69 0.00 362.17
August 406.00 0.50 0.48 01-AUG-06:10 2180.57 14.62 0.00 378.33 1255.74 18.06 0.67 342.33
September 289.17 0.50 0.48 01-SEP-07:40 3083.52 16.27 17.00 326.00 1640.50 18.60 7.17 295.67
October 314.33 0.49 0.48 01-OCT-07:10 6449.09 31.60 269.67 299.00 1745.40 18.81 25.33 279.33
November 258.33 0.50 0.48 01-NOV-07:40 4179.28 32.08 237.33 241.50 2030.10 27.51 160.50 220.17
December 230.67 0.49 0.48 01-DEC-07:00 3738.53 30.70 203.67 239.50 2970.83 32.59 216.00 210.50
                         
Annual Sum or Average 3928.50 0.50     3582.46 21.58 1430.50 3851.33 1656.03 20.90 760.50 3493.83
Minimum of Months 230.67 0.49 0.48   1772.96 14.09 0.00 239.50 1059.34 17.54 0.00 210.50
Maximum of Months 439.00 0.50 0.48   7974.67 32.40 269.67 402.83 3611.30 33.12 231.83 362.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-08:00 1571.55 20.20 70.17 239.00 801.18 20.89 66.67 196.50
February 262.50 0.50 0.48 01-FEB-09:39 2170.24 21.37 83.00 250.00 1144.30 22.16 70.00 221.50
March 339.33 0.49 0.48 01-MAR-07:19 2944.56 22.02 115.33 321.67 1312.51 21.66 61.50 291.17
April 371.17 0.50 0.48 01-APR-06:19 3162.35 20.39 104.00 352.00 1820.78 22.35 87.50 321.83
May 332.17 0.49 0.48 01-MAY-05:30 4205.63 21.89 103.50 395.17 1841.06 21.51 55.83 353.83
June 430.67 0.50 0.48 01-JUN-05:49 3828.26 21.15 132.67 405.00 1735.49 21.28 75.83 377.50
July 439.00 0.50 0.48 01-JUL-04:00 3627.44 21.36 135.83 412.83 1645.72 21.29 75.50 377.67
August 406.00 0.49 0.48 01-AUG-05:49 3380.42 21.62 122.67 382.17 1535.91 21.51 67.33 351.33
September 289.17 0.49 0.48 01-SEP-07:40 3423.63 22.24 86.50 326.83 1908.08 23.06 63.17 293.33
October 314.33 0.50 0.48 01-OCT-06:00 2200.27 21.17 91.67 291.83 1192.56 21.96 65.83 260.83
November 258.33 0.51 0.48 01-NOV-07:40 1579.49 20.59 86.83 232.67 878.82 21.49 73.83 185.67
December 230.67 0.50 0.48 01-DEC-07:00 1358.33 19.48 59.67 227.67 699.37 21.01 60.83 180.67
                         
Annual Sum or Average 3928.50 0.50     2941.88 21.19 1191.83 3836.83 1437.18 21.67 823.83 3411.83
Minimum of Months 230.67 0.49 0.48   1358.33 19.48 59.67 227.67 699.37 20.89 55.83 180.67
Maximum of Months 439.00 0.51 0.48   4205.63 22.24 135.83 412.83 1908.08 23.06 87.50 377.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-09:00 683.53 11.40 0.00 222.83 399.33 14.92 0.00 153.17
February 262.50 0.51 0.48 01-FEB-10:09 899.64 12.75 0.00 243.00 522.40 16.11 0.00 201.00
March 339.33 0.50 0.48 01-MAR-07:00 959.79 13.47 0.00 316.50 587.03 16.92 0.00 273.33
April 371.17 0.50 0.48 01-APR-06:49 1113.32 14.03 0.00 351.00 680.14 17.44 0.00 321.00
May 332.17 0.49 0.48 01-MAY-05:00 1341.52 16.57 26.17 403.00 845.41 19.86 28.83 367.83
June 430.67 0.49 0.48 01-JUN-05:00 1489.62 18.33 74.33 413.67 906.31 19.95 41.33 391.50
July 439.00 0.49 0.48 01-JUL-05:19 1416.63 17.96 71.00 419.83 860.56 19.70 45.00 391.33
August 406.00 0.49 0.48 01-AUG-05:00 1255.96 14.76 0.00 388.33 775.94 18.23 2.67 357.50
September 289.17 0.50 0.48 01-SEP-07:40 1056.95 14.70 0.00 322.83 680.28 18.15 0.00 279.33
October 314.33 0.51 0.48 01-OCT-07:40 839.02 12.56 0.00 282.83 504.16 16.00 0.00 235.17
November 258.33 0.53 0.48 01-NOV-08:09 662.80 10.93 0.00 218.83 385.52 14.31 0.00 140.33
December 230.67 0.51 0.48 01-DEC-11:50 686.45 11.27 0.00 209.17 392.07 14.73 0.00 132.17
                         
Annual Sum or Average 3928.50 0.50     1086.26 14.49 171.50 3791.83 661.79 17.53 117.83 3243.67
Minimum of Months 230.67 0.49 0.48   662.80 10.93 0.00 209.17 385.52 14.31 0.00 132.17
Maximum of Months 439.00 0.53 0.48   1489.62 18.33 74.33 419.83 906.31 19.95 45.00 391.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:39 1473.48 20.84 85.17 238.83 814.71 21.76 76.17 196.17
February 262.50 0.50 0.48 01-FEB-10:09 2029.49 21.18 81.67 249.50 1093.24 22.15 68.83 221.67
March 339.33 0.49 0.48 01-MAR-07:00 2871.65 21.00 101.67 325.00 1661.88 22.81 85.83 293.50
April 371.17 0.50 0.48 01-APR-07:10 3380.06 20.18 104.33 349.33 1470.85 20.09 49.33 318.67
May 332.17 0.49 0.48 01-MAY-06:30 3617.56 17.24 43.00 393.50 2044.84 17.88 0.00 359.00
June 430.67 0.50 0.48 01-JUN-06:19 3816.63 17.00 52.50 403.50 1698.03 17.84 0.00 373.83
July 439.00 0.50 0.48 01-JUL-05:00 3415.10 17.08 54.50 409.67 1599.53 18.06 3.67 376.50
August 406.00 0.49 0.48 01-AUG-06:30 3205.06 19.16 85.17 384.67 1771.95 20.49 53.67 353.17
September 289.17 0.50 0.48 01-SEP-07:49 3509.63 21.92 84.67 324.33 1584.33 21.45 41.67 294.67
October 314.33 0.50 0.48 01-OCT-07:49 2064.11 20.91 89.50 290.83 1113.02 21.83 64.33 260.67
November 258.33 0.51 0.48 01-NOV-08:09 1511.11 20.32 87.00 231.17 818.10 21.05 68.67 190.17
December 230.67 0.50 0.48 01-DEC-11:39 1419.85 20.15 63.67 225.17 764.60 21.21 66.17 179.00
                         
Annual Sum or Average 3928.50 0.50     2842.08 19.50 932.83 3825.50 1433.77 20.32 578.33 3417.00
Minimum of Months 230.67 0.49 0.48   1419.85 17.00 43.00 225.17 764.60 17.84 0.00 179.00
Maximum of Months 439.00 0.51 0.48   3816.63 21.92 104.33 409.67 2044.84 22.81 85.83 376.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.49 0.48 01-JAN-08:00 4437.52 32.11 233.00 251.50 3613.53 33.11 231.83 226.33
February 262.50 0.49 0.48 01-FEB-09:39 5581.26 32.39 241.33 256.83 1937.72 24.27 106.33 239.50
March 339.33 0.49 0.48 01-MAR-07:30 7978.04 28.58 228.33 327.67 1586.98 18.06 11.17 297.17
April 371.17 0.50 0.48 01-APR-06:49 2144.89 14.06 0.00 347.67 1246.85 17.52 1.17 317.67
May 332.17 0.50 0.48 01-MAY-06:30 1969.46 14.39 0.00 385.67 1201.38 17.94 0.00 343.67
June 430.67 0.50 0.48 01-JUN-06:10 1775.35 14.26 0.00 394.83 1060.86 17.74 0.00 360.17
July 439.00 0.50 0.48 01-JUL-05:00 1855.78 14.20 0.00 402.83 1093.26 17.68 0.00 362.17
August 406.00 0.50 0.48 01-AUG-06:10 2183.84 14.59 0.00 378.33 1257.73 18.05 0.67 342.33
September 289.17 0.50 0.48 01-SEP-07:40 3087.24 16.24 17.00 326.00 1642.96 18.58 7.00 295.67
October 314.33 0.49 0.48 01-OCT-07:10 6451.90 31.59 269.67 299.00 1841.00 19.07 28.83 279.33
November 258.33 0.50 0.48 01-NOV-07:40 4181.22 32.07 237.33 241.50 2298.75 29.22 186.50 220.50
December 230.67 0.49 0.48 01-DEC-07:00 3740.25 30.69 203.67 239.50 2973.05 32.59 216.00 210.67
                         
Annual Sum or Average 3928.50 0.50     3585.21 21.56 1430.33 3851.33 1683.07 21.02 789.50 3495.17
Minimum of Months 230.67 0.49 0.48   1775.35 14.06 0.00 239.50 1060.86 17.52 0.00 210.67
Maximum of Months 439.00 0.50 0.48   7978.04 32.39 269.67 402.83 3613.53 33.11 231.83 362.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-08:00 1572.86 20.17 70.17 239.00 802.33 20.87 66.33 196.67
February 262.50 0.50 0.48 01-FEB-09:39 2172.13 21.34 83.00 250.00 1145.84 22.15 69.83 221.50
March 339.33 0.49 0.48 01-MAR-07:19 2916.41 21.00 103.17 321.83 1314.00 21.65 61.50 291.33
April 371.17 0.50 0.48 01-APR-06:19 3164.34 20.36 104.00 352.17 1822.43 22.33 87.50 322.00
May 332.17 0.49 0.48 01-MAY-05:30 4207.62 21.86 103.50 395.33 1842.81 21.50 55.83 353.83
June 430.67 0.50 0.48 01-JUN-05:49 3830.38 21.12 132.67 405.00 1737.25 21.26 75.83 377.50
July 439.00 0.50 0.48 01-JUL-04:00 3629.52 21.34 135.83 412.83 1647.45 21.27 75.50 377.67
August 406.00 0.49 0.48 01-AUG-05:49 3382.59 21.59 122.67 382.17 1537.72 21.50 67.33 351.50
September 289.17 0.49 0.48 01-SEP-07:40 3425.42 22.21 86.50 326.83 1909.88 23.05 63.17 293.67
October 314.33 0.50 0.48 01-OCT-06:00 2201.84 21.14 91.50 291.83 1193.91 21.95 65.83 260.83
November 258.33 0.51 0.48 01-NOV-07:40 1580.79 20.57 86.83 232.67 879.91 21.48 73.33 186.00
December 230.67 0.50 0.48 01-DEC-07:00 1359.72 19.45 59.67 228.00 700.49 21.00 60.67 180.67
                         
Annual Sum or Average 3928.50 0.50     2941.13 21.07 1179.50 3837.67 1438.74 21.66 822.67 3413.17
Minimum of Months 230.67 0.49 0.48   1359.72 19.45 59.67 228.00 700.49 20.87 55.83 180.67
Maximum of Months 439.00 0.51 0.48   4207.62 22.21 135.83 412.83 1909.88 23.05 87.50 377.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.51 0.48 01-JAN-09:00 684.39 11.37 0.00 223.33 399.97 14.91 0.00 153.50
February 262.50 0.51 0.48 01-FEB-10:09 900.82 12.72 0.00 243.17 523.24 16.10 0.00 201.33
March 339.33 0.50 0.48 01-MAR-07:00 960.85 13.44 0.00 316.67 587.86 16.91 0.00 273.50
April 371.17 0.50 0.48 01-APR-06:49 1114.58 14.00 0.00 351.00 681.10 17.42 0.00 321.50
May 332.17 0.49 0.48 01-MAY-05:00 1342.63 16.54 26.17 403.00 846.41 19.85 28.67 368.00
June 430.67 0.49 0.48 01-JUN-05:00 1491.05 18.31 74.33 413.67 907.48 19.94 40.50 391.50
July 439.00 0.49 0.48 01-JUL-05:19 1418.06 17.93 71.00 419.83 861.70 19.69 44.50 391.33
August 406.00 0.49 0.48 01-AUG-05:00 1257.28 14.73 0.00 388.33 776.99 18.21 2.17 357.50
September 289.17 0.50 0.48 01-SEP-07:40 1057.81 14.66 0.00 322.83 681.12 18.13 0.00 279.67
October 314.33 0.51 0.48 01-OCT-07:40 839.99 12.53 0.00 283.00 504.91 15.98 0.00 235.50
November 258.33 0.53 0.48 01-NOV-08:09 663.66 10.90 0.00 219.00 386.14 14.30 0.00 141.17
December 230.67 0.51 0.48 01-DEC-11:50 687.38 11.24 0.00 209.67 392.73 14.71 0.00 132.17
                         
Annual Sum or Average 3928.50 0.50     1087.41 14.46 171.50 3793.50 662.70 17.51 115.83 3246.67
Minimum of Months 230.67 0.49 0.48   663.66 10.90 0.00 209.67 386.14 14.30 0.00 132.17
Maximum of Months 439.00 0.53 0.48   1491.05 18.31 74.33 419.83 907.48 19.94 44.50 391.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.50 0.48 01-JAN-09:39 1474.79 20.81 85.17 238.83 815.80 21.75 76.17 196.33
February 262.50 0.50 0.48 01-FEB-10:09 2031.36 21.16 81.67 249.50 1094.79 22.14 68.17 222.00
March 339.33 0.49 0.48 01-MAR-07:00 2873.40 20.98 101.67 325.00 1663.40 22.79 85.83 293.67
April 371.17 0.50 0.48 01-APR-07:10 3382.09 20.16 104.33 349.33 1472.51 20.08 49.33 318.67
May 332.17 0.49 0.48 01-MAY-06:30 3619.45 17.21 43.00 393.67 2046.55 17.86 0.00 359.00
June 430.67 0.50 0.48 01-JUN-06:19 3818.73 16.96 52.50 403.83 1699.87 17.83 0.00 373.83
July 439.00 0.50 0.48 01-JUL-05:00 3417.29 17.04 54.50 409.83 1601.33 18.04 3.67 376.83
August 406.00 0.49 0.48 01-AUG-06:30 3207.33 19.13 85.00 384.67 1773.81 20.48 53.67 353.17
September 289.17 0.50 0.48 01-SEP-07:49 3511.36 21.89 84.67 324.33 1586.00 21.43 41.67 294.83
October 314.33 0.50 0.48 01-OCT-07:49 2065.73 20.89 89.50 290.83 1114.40 21.82 64.00 260.67
November 258.33 0.51 0.48 01-NOV-08:09 1512.42 20.30 87.00 231.17 819.17 21.04 68.17 190.17
December 230.67 0.50 0.48 01-DEC-11:39 1421.24 20.13 63.67 225.17 765.74 21.19 66.17 179.00
                         
Annual Sum or Average 3928.50 0.50     2843.93 19.48 932.67 3826.17 1435.34 20.31 576.83 3418.17
Minimum of Months 230.67 0.49 0.48   1421.24 16.96 43.00 225.17 765.74 17.83 0.00 179.00
Maximum of Months 439.00 0.51 0.48   3818.73 21.89 104.33 409.83 2046.55 22.79 85.83 376.83



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123890E+09 15268.39 18-JAN-08:20 0.00 0.00 0.00 0.00 0.00
February 0.191844E+09 17502.60 16-FEB-08:20 0.00 0.00 0.00 0.00 0.00
March 0.211252E+09 14505.96 27-MAR-16:10 0.00 0.00 0.00 0.00 0.00
April 84507925.33 15507.44 03-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 9697546.79 1751.04 12-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 2164065.33 2276.34 06-SEP-06:20 0.00 0.00 0.00 0.00 0.00
October 72196269.14 12100.59 17-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 0.129073E+09 12221.56 03-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.221176E+09 12957.04 19-DEC-08:65 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104580E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.221176E+09 17502.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106512E+10 14631.70 03-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.701844E+09 14632.33 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.118290E+09 14944.15 07-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.319150E+09 14706.57 08-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.220441E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106512E+10 14944.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.698378E+09 14453.21 03-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.531106E+09 14476.81 24-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 71961500.92 14494.36 08-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5192774.65 1118.40 25-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.429839E+09 14523.94 22-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173648E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.698378E+09 14523.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128283E+10 20319.94 20-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.102361E+10 20326.32 16-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.159842E+09 20379.56 20-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 7629451.80 10005.21 17-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 7279767.96 11413.20 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 27035695.84 20381.42 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.639176E+09 20389.78 07-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.314741E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128283E+10 20389.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.176366E+09 12654.45 12-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 53535077.36 12651.27 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.229901E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.176366E+09 12654.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.885433E+10 302698.81 09-JAN-15:02 0.00 0.00 0.00 0.00 0.00
February 0.720008E+10 294520.21 03-FEB-09:00 0.00 0.00 0.00 0.00 0.00
March 0.386518E+10 239645.93 28-MAR-08:15 0.00 0.00 0.00 0.00 0.00
April 0.315041E+10 383471.74 11-APR-13:30 0.00 0.00 0.00 0.00 0.00
May 0.103818E+10 272579.05 11-MAY-13:20 0.00 0.00 0.00 0.00 0.00
June 0.177616E+09 251672.86 13-JUN-13:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 2441003.07 8135.32 31-AUG-11:05 0.00 0.00 0.00 0.00 0.00
September 0.236230E+09 98567.44 28-SEP-10:00 0.00 0.00 0.00 0.00 0.00
October 0.210534E+10 250671.98 27-OCT-13:10 0.00 0.00 0.00 0.00 0.00
November 0.227555E+10 189398.26 25-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.530961E+10 375545.31 28-DEC-13:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.342150E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.885433E+10 383471.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.174901E+11 526337.67 03-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.449899E+10 525090.25 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.294654E+10 525425.26 11-DEC-06:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.249357E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174901E+11 526337.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.710718E+11 127344.29 04-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.575781E+11 127355.83 21-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.210575E+11 126706.53 11-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.236158E+10 129075.45 14-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.195404E+10 136006.28 18-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.956403E+10 128778.65 03-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.564262E+11 127327.32 27-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.220013E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.710718E+11 136006.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.382374E+11 187533.95 09-JAN-15:02 0.00 0.00 0.00 0.00 0.00
February 0.304282E+11 181758.80 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.769993E+10 181416.21 27-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.868746E+09 181261.96 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.898696E+09 181255.41 30-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.523830E+10 182546.64 03-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.327746E+11 181651.58 12-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116146E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.382374E+11 187533.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.444609E+11 211790.32 04-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.358369E+11 210713.68 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.797090E+10 210418.52 07-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.156072E+10 208235.83 17-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.834725E+09 208620.63 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.557410E+10 214090.61 03-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.371864E+11 210587.02 12-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.133425E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.444609E+11 214090.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.357374E+11 182760.79 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.269724E+11 182777.80 14-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.621048E+10 182321.67 07-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.493260E+09 182032.46 17-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.565017E+09 182120.10 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.354281E+10 182084.19 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.266421E+11 182766.11 12-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100163E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.357374E+11 182777.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.319397E+10 12081.77 09-JAN-04:01 0.00 0.00 0.00 0.00 0.00
February 0.283643E+10 15680.47 06-FEB-04:21 0.00 0.00 0.00 0.00 0.00
March 0.691857E+09 11185.40 07-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 90442074.40 8672.15 13-APR-16:20 0.00 0.00 0.00 0.00 0.00
May 26379139.82 5085.14 12-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 2670160.63 2760.19 15-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 159.23 0.27 02-JUL-23:00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 8838641.24 3766.27 12-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 66257499.40 7288.67 19-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 54145610.41 7317.85 14-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.242251E+10 16585.59 11-DEC-04:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.939350E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.319397E+10 16585.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.119148E+11 75106.81 03-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.961993E+10 75074.36 02-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.330699E+10 74895.26 20-MAR-04:04 0.00 0.00 0.00 0.00 0.00
April 0.469279E+09 74874.28 17-APR-04:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.552213E+09 75128.78 30-OCT-05:04 0.00 0.00 0.00 0.00 0.00
November 0.197640E+10 75485.80 13-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.948369E+10 75101.21 09-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.373233E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119148E+11 75485.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122080E+11 14492.68 03-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.103618E+11 14490.64 03-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.516891E+10 14464.86 13-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 0.128763E+10 14488.09 03-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 59956524.90 14422.49 01-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 45158640.11 14389.54 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.125732E+10 14498.76 30-OCT-04:23 0.00 0.00 0.00 0.00 0.00
November 0.358948E+10 14493.51 14-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.109368E+11 14497.11 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.449150E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122080E+11 14498.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.723715E+10 20018.48 04-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.603845E+10 20087.04 03-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.228635E+10 20005.55 08-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.521967E+09 19991.83 17-APR-04:03 0.00 0.00 0.00 0.00 0.00
May 18829048.97 17252.65 01-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 19304861.89 12039.40 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.588386E+09 20003.02 30-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.205651E+10 20097.18 13-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.694740E+10 20085.45 09-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.257144E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.723715E+10 20097.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.854099E+10 22807.08 03-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.740241E+10 22803.61 03-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.275273E+10 22732.69 21-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.922983E+09 22708.56 17-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 62764808.19 17221.22 01-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 1077555.72 712.04 14-JUN-05:08 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 25621783.61 11422.54 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.685226E+09 22810.51 16-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.241369E+10 22802.53 29-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.817934E+10 22796.34 13-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.309868E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.854099E+10 22810.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.653845E+10 21454.55 28-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.502253E+10 21457.44 01-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.183431E+10 21449.29 08-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.392113E+09 21396.86 05-APR-04:11 0.00 0.00 0.00 0.00 0.00
May 6533564.27 1399.88 12-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 12686999.65 3184.31 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.417947E+09 21394.29 17-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.144805E+10 21432.13 21-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.529117E+10 21428.08 06-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.209638E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.653845E+10 21457.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.133695E+11 30628.79 31-JAN-20:20 0.00 0.00 0.00 0.00 0.00
February 0.113473E+11 34525.08 06-FEB-22:00 0.00 0.00 0.00 0.00 0.00
March 0.333298E+10 24170.37 07-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.118347E+09 17012.13 17-APR-06:20 0.00 0.00 0.00 0.00 0.00
May 1076750.42 2823.59 04-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 396.97 0.67 09-JUN-06:25 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 242.49 0.36 04-AUG-06:40 0.00 0.00 0.00 0.00 0.00
September 653.52 0.84 28-SEP-06:25 0.00 0.00 0.00 0.00 0.00
October 3033337.42 10110.84 17-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 0.101905E+09 9031.91 22-NOV-22:00 0.00 0.00 0.00 0.00 0.00
December 0.523659E+10 29612.68 28-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.335107E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133695E+11 34525.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 11550518.54 11550518.54 8069.66 17-JAN-08:15 8069.66 0.00
February 0.00 0.00 0.389478E+09 0.389478E+09 25189.58 22-FEB-15:00 25189.58 0.00
March 0.00 0.00 0.897677E+10 0.879373E+10 105754.51 14-MAR-13:05 90666.21 0.06
April 0.00 0.00 0.474962E+10 0.474962E+10 52416.76 07-APR-14:00 52416.76 0.02
May 0.00 0.00 0.185430E+11 0.183236E+11 95113.08 10-MAY-14:40 87239.43 0.15
June 0.00 0.00 0.851655E+11 0.677548E+11 255306.43 27-JUN-07:50 110101.79 0.51
July 0.00 0.00 0.156732E+12 0.113354E+12 302187.78 21-JUL-05:02 122012.80 0.78
August 0.00 0.00 0.132182E+12 0.103611E+12 277132.82 15-AUG-08:20 120156.94 0.75
September 0.00 0.00 0.509929E+11 0.406113E+11 192486.60 14-SEP-04:12 83986.01 0.41
October 0.00 0.00 0.102865E+11 0.102831E+11 79136.30 11-OCT-15:00 79136.30 0.11
November 0.00 0.00 0.533096E+10 0.533096E+10 52275.44 27-NOV-06:03 52275.44 0.05
December 0.00 0.00 0.264578E+09 0.264578E+09 13376.96 04-DEC-14:50 13376.96 0.00
                 
Annual Sum or Average 0.00 0.00 0.473624E+12 0.373478E+12       0.24
Minimum of Months 0.00 0.00 11550518.54 11550518.54 8069.66   8069.66 0.00
Maximum of Months 0.00 0.00 0.156732E+12 0.113354E+12 302187.78   122012.80 0.78



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8897611.50 8897611.50 3639.50 11-JAN-15:10 3639.50 0.01
February 0.00 0.00 56474678.37 56474678.37 9622.53 28-FEB-15:20 9622.53 0.00
March 0.00 0.00 0.452818E+11 0.440767E+11 798843.98 15-MAR-14:05 798843.98 0.06
April 0.00 0.00 0.544718E+11 0.544718E+11 498112.52 19-APR-14:50 498112.52 0.03
May 0.00 0.00 0.167717E+12 0.166016E+12 854582.07 10-MAY-14:40 788655.97 0.15
June 0.00 0.00 0.646351E+12 0.526022E+12 1692600.57 27-JUN-07:40 737453.36 0.46
July 0.00 0.00 0.108265E+13 0.811091E+12 2466925.98 17-JUL-05:02 983523.96 0.61
August 0.00 0.00 0.905340E+12 0.738184E+12 2530010.68 14-AUG-05:02 960719.71 0.58
September 0.00 0.00 0.412795E+12 0.337720E+12 1547580.92 14-SEP-05:03 674260.31 0.40
October 0.00 0.00 0.804732E+11 0.804242E+11 645677.67 11-OCT-15:00 645677.67 0.12
November 0.00 0.00 0.157286E+11 0.157286E+11 281678.55 16-NOV-13:05 281678.55 0.04
December 0.00 0.00 42848555.41 42848555.41 8116.47 04-DEC-11:10 8116.47 0.01
                 
Annual Sum or Average 0.00 0.00 0.341092E+13 0.277384E+13       0.21
Minimum of Months 0.00 0.00 8897611.50 8897611.50 3639.50   3639.50 0.00
Maximum of Months 0.00 0.00 0.108265E+13 0.811091E+12 2530010.68   983523.96 0.61



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1117683.74 1117683.74 601.73 02-JAN-07:03 601.73 0.01
February 0.00 0.00 5331679.48 5331679.48 862.06 28-FEB-15:00 862.06 0.00
March 0.00 0.00 0.407671E+10 0.407559E+10 93787.89 15-MAR-14:20 93787.89 0.06
April 0.00 0.00 0.150635E+10 0.150635E+10 35456.09 07-APR-14:00 35456.09 0.02
May 0.00 0.00 0.156220E+11 0.154989E+11 100957.35 14-MAY-15:02 88754.95 0.14
June 0.00 0.00 0.699716E+11 0.568114E+11 173036.85 27-JUN-05:03 74437.39 0.46
July 0.00 0.00 0.119770E+12 0.899215E+11 308070.74 21-JUL-05:02 124427.04 0.61
August 0.00 0.00 0.981338E+11 0.796226E+11 272971.29 14-AUG-05:02 103623.74 0.57
September 0.00 0.00 0.399541E+11 0.325316E+11 168837.85 15-SEP-13:10 92475.79 0.39
October 0.00 0.00 0.445403E+10 0.445403E+10 62207.58 11-OCT-15:00 62207.58 0.10
November 0.00 0.00 0.554335E+09 0.554335E+09 12134.76 16-NOV-13:00 12134.76 0.04
December 0.00 0.00 4194387.81 4194387.81 421.65 04-DEC-11:00 421.65 0.01
                 
Annual Sum or Average 0.00 0.00 0.354053E+12 0.284987E+12       0.20
Minimum of Months 0.00 0.00 1117683.74 1117683.74 421.65   421.65 0.00
Maximum of Months 0.00 0.00 0.119770E+12 0.899215E+11 308070.74   124427.04 0.61



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 41389778.29 41389778.29 5270.03 11-JAN-16:00 5270.03 0.01
February 0.00 0.00 38811114.69 38811114.69 6068.56 22-FEB-17:00 6068.56 0.00
March 0.00 0.00 0.390107E+10 0.388490E+10 55155.19 15-MAR-14:00 55155.19 0.04
April 0.00 0.00 0.153861E+10 0.153861E+10 27505.39 07-APR-13:20 27505.39 0.01
May 0.00 0.00 0.121745E+11 0.115031E+11 85701.42 24-MAY-06:25 44821.78 0.12
June 0.00 0.00 0.319718E+11 0.249510E+11 124828.76 28-JUN-14:20 76215.89 0.25
July 0.00 0.00 0.532899E+11 0.393413E+11 173433.53 29-JUL-10:53 63286.68 0.27
August 0.00 0.00 0.564729E+11 0.463323E+11 136451.30 28-AUG-12:05 71039.36 0.37
September 0.00 0.00 0.331419E+11 0.261229E+11 133426.63 14-SEP-16:00 66919.67 0.31
October 0.00 0.00 0.555058E+10 0.529696E+10 73083.92 26-OCT-06:25 34522.40 0.10
November 0.00 0.00 0.877442E+09 0.873236E+09 55196.25 27-NOV-07:11 55196.25 0.02
December 0.00 0.00 6140035.17 5949607.27 17374.01 01-DEC-07:13 16395.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.199005E+12 0.159930E+12       0.13
Minimum of Months 0.00 0.00 6140035.17 5949607.27 5270.03   5270.03 0.00
Maximum of Months 0.00 0.00 0.564729E+11 0.463323E+11 173433.53   76215.89 0.37



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.656980E+10 0.656975E+10 3825.74 13-JAN-18:00 3825.74 0.00
February 0.00 0.00 0.102825E+11 0.102722E+11 5069.26 14-FEB-17:15 5069.26 0.00
March 0.00 0.00 0.314528E+11 0.283874E+11 313928.95 14-MAR-13:00 255009.50 0.00
April 0.00 0.00 0.364164E+11 0.339235E+11 234047.96 08-APR-14:00 212400.65 0.00
May 0.00 0.00 0.723110E+10 0.677721E+10 124780.53 10-MAY-15:00 105356.98 0.00
June 0.00 0.00 0.166936E+12 0.118666E+12 432272.86 27-JUN-14:05 226014.03 0.00
July 0.00 0.00 0.711245E+12 0.442307E+12 543995.15 20-JUL-22:13 191812.49 0.00
August 0.00 0.00 0.826201E+12 0.554696E+12 527717.42 14-AUG-00:53 210657.15 0.00
September 0.00 0.00 0.150678E+11 0.112554E+11 177632.62 15-SEP-12:00 106266.88 0.00
October 0.00 0.00 0.854372E+10 0.822278E+10 88289.70 11-OCT-15:00 81933.08 0.00
November 0.00 0.00 0.172421E+11 0.159210E+11 104722.61 05-NOV-13:55 85768.31 0.00
December 0.00 0.00 0.150363E+11 0.146524E+11 67559.13 01-DEC-11:00 45291.36 0.00
                 
Annual Sum or Average 0.00 0.00 0.185223E+13 0.125165E+13       0.00
Minimum of Months 0.00 0.00 0.656980E+10 0.656975E+10 3825.74   3825.74 0.00
Maximum of Months 0.00 0.00 0.826201E+12 0.554696E+12 543995.15   255009.50 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.312890E+10 0.312860E+10 2202.93 15-JAN-16:35 2202.93 0.00
February 0.00 0.00 0.778657E+10 0.778657E+10 4203.69 28-FEB-17:00 4203.69 0.00
March 0.00 0.00 0.148841E+11 0.148628E+11 7553.87 31-MAR-24:00 7553.87 0.00
April 0.00 0.00 0.197920E+11 0.197891E+11 8755.97 02-APR-17:55 8755.97 0.00
May 0.00 0.00 0.558575E+10 0.555033E+10 4026.73 31-MAY-24:00 4026.73 0.00
June 0.00 0.00 0.108868E+11 0.107049E+11 5944.43 30-JUN-24:00 5944.43 0.00
July 0.00 0.00 0.166302E+11 0.163163E+11 7880.61 31-JUL-24:00 7841.22 0.00
August 0.00 0.00 0.214771E+11 0.212387E+11 8788.70 14-AUG-15:50 8439.56 0.00
September 0.00 0.00 0.570663E+10 0.557413E+10 3792.95 30-SEP-24:00 3792.95 0.00
October 0.00 0.00 0.103083E+11 0.102776E+11 5719.02 31-OCT-24:00 5719.02 0.00
November 0.00 0.00 0.145502E+11 0.145482E+11 6072.37 15-NOV-16:20 6072.37 0.00
December 0.00 0.00 0.194012E+11 0.194007E+11 7846.97 17-DEC-16:10 7846.97 0.00
                 
Annual Sum or Average 0.00 0.00 0.150138E+12 0.149178E+12       0.00
Minimum of Months 0.00 0.00 0.312890E+10 0.312860E+10 2202.93   2202.93 0.00
Maximum of Months 0.00 0.00 0.214771E+11 0.212387E+11 8788.70   8755.97 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.543361E+10 0.543358E+10 14825.06 12-JAN-16:50 14825.06 0.00
February 0.00 0.00 0.494842E+11 0.494842E+11 36849.82 28-FEB-17:00 36849.82 0.00
March 0.00 0.00 0.126105E+12 0.125892E+12 67936.13 31-MAR-23:40 67936.13 0.00
April 0.00 0.00 0.179571E+12 0.179540E+12 80484.82 02-APR-18:00 80484.82 0.00
May 0.00 0.00 0.487521E+11 0.484021E+11 38152.36 31-MAY-24:00 38152.36 0.00
June 0.00 0.00 0.101461E+12 0.996523E+11 56675.14 30-JUN-24:00 56675.14 0.00
July 0.00 0.00 0.157261E+12 0.154136E+12 75673.10 31-JUL-24:00 75289.22 0.00
August 0.00 0.00 0.203456E+12 0.201079E+12 83926.86 04-AUG-18:40 83926.86 0.00
September 0.00 0.00 0.498360E+11 0.485340E+11 33165.80 30-SEP-24:00 33165.80 0.00
October 0.00 0.00 0.871519E+11 0.868448E+11 50836.09 31-OCT-23:40 50836.09 0.00
November 0.00 0.00 0.121261E+12 0.121239E+12 56275.49 15-NOV-16:20 56275.49 0.00
December 0.00 0.00 0.155227E+12 0.155222E+12 69826.01 04-DEC-16:20 69826.01 0.00
                 
Annual Sum or Average 0.00 0.00 0.128500E+13 0.127546E+13       0.00
Minimum of Months 0.00 0.00 0.543361E+10 0.543358E+10 14825.06   14825.06 0.00
Maximum of Months 0.00 0.00 0.203456E+12 0.201079E+12 83926.86   83926.86 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 96147635.28 96147635.28 1264.02 12-JAN-16:40 1264.02 0.00
February 0.00 0.00 0.328890E+10 0.328890E+10 3629.23 28-FEB-17:00 3629.23 0.00
March 0.00 0.00 0.110070E+11 0.109859E+11 6368.10 31-MAR-23:20 6368.10 0.00
April 0.00 0.00 0.169121E+11 0.169091E+11 7947.10 09-APR-17:57 7947.10 0.00
May 0.00 0.00 0.445542E+10 0.442072E+10 3726.44 31-MAY-23:40 3726.44 0.00
June 0.00 0.00 0.100764E+11 0.989549E+10 5601.74 30-JUN-23:40 5601.74 0.00
July 0.00 0.00 0.157813E+11 0.154688E+11 7560.96 31-JUL-24:00 7522.35 0.00
August 0.00 0.00 0.203241E+11 0.200867E+11 8474.26 04-AUG-18:40 8474.26 0.00
September 0.00 0.00 0.461874E+10 0.448911E+10 3038.18 04-SEP-17:42 3038.18 0.00
October 0.00 0.00 0.737969E+10 0.734931E+10 4680.70 31-OCT-23:20 4680.70 0.00
November 0.00 0.00 0.103265E+11 0.103244E+11 5503.03 15-NOV-16:20 5503.03 0.00
December 0.00 0.00 0.135386E+11 0.135381E+11 6636.26 04-DEC-16:20 6636.26 0.00
                 
Annual Sum or Average 0.00 0.00 0.117805E+12 0.116853E+12       0.00
Minimum of Months 0.00 0.00 96147635.28 96147635.28 1264.02   1264.02 0.00
Maximum of Months 0.00 0.00 0.203241E+11 0.200867E+11 8474.26   8474.26 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 104830.60 1925048.11 02-JAN-04:01
February 0.00 0.00 01-FEB-00:03 89475.01 1536938.75 14-FEB-06:01
March 0.00 0.00 01-MAR-00:10 24791.89 1349036.32 21-MAR-04:01
April 0.00 0.00 01-APR-00:10 4732.34 1147875.06 17-APR-05:01
May 0.00 0.00 01-MAY-00:05 455.48 290462.63 11-MAY-13:20
June 0.00 0.00 01-JUN-00:10 70.89 266980.70 13-JUN-11:05
July 0.00 0.00 01-JUL-00:10 0.00 3.30 02-JUL-23:00
August 0.00 0.00 01-AUG-00:05 0.75 6715.82 31-AUG-11:05
September 0.00 0.00 01-SEP-00:10 127.89 95519.61 28-SEP-10:00
October 0.00 0.00 01-OCT-00:10 3717.41 1180245.45 30-OCT-05:01
November 0.00 0.00 01-NOV-00:10 14581.55 1271376.51 25-NOV-05:01
December 0.00 0.00 01-DEC-00:10 78544.14 1578205.58 11-DEC-05:01
             
Annual Sum or Average 0.00     26502.00    
Minimum of Months 0.00 0.00   0.00 3.30  
Maximum of Months 0.00 0.00   104830.60 1925048.11  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 84.90 6051.85 11-JAN-16:50 0.00 0.00 01-JAN-00:03
February 261.49 28978.45 22-FEB-17:00 0.00 0.00 01-FEB-00:03
March 25184.93 1456153.93 15-MAR-14:05 0.00 0.00 01-MAR-00:10
April 24720.21 567293.73 19-APR-15:10 0.00 0.00 01-APR-00:10
May 82086.29 1342058.50 10-MAY-14:50 0.00 0.00 01-MAY-00:05
June 333724.85 2082972.73 27-JUN-07:40 0.00 0.00 01-JUN-00:10
July 548567.49 2830692.47 05-JUL-16:00 0.00 0.00 01-JUL-00:10
August 462173.16 2542021.81 15-AUG-05:03 0.00 0.00 01-AUG-00:05
September 213381.30 2261495.91 21-SEP-12:52 0.00 0.00 01-SEP-00:10
October 38401.15 835702.04 11-OCT-14:30 0.00 0.00 01-OCT-00:10
November 9337.35 333603.93 16-NOV-13:10 0.00 0.00 01-NOV-00:10
December 241.31 40222.44 01-DEC-07:13 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 146030.55     0.00    
Minimum of Months 84.90 6051.85   0.00 0.00  
Maximum of Months 548567.49 2830692.47   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 7.83 2524.20 11-JAN-16:50 0.00 0.00 01-JAN-00:03
February 159.38 25537.99 22-FEB-17:00 0.00 0.00 01-FEB-00:03
March 24541.90 1286687.90 15-MAR-14:20 0.00 0.00 01-MAR-00:10
April 23953.39 564599.76 19-APR-15:00 0.00 0.00 01-APR-00:10
May 80742.57 1382157.36 10-MAY-14:50 0.00 0.00 01-MAY-00:05
June 332046.15 2995747.60 27-JUN-05:03 0.00 0.00 01-JUN-00:10
July 546548.93 3282820.77 17-JUL-05:02 0.00 0.00 01-JUL-00:10
August 463827.25 3381110.40 15-AUG-04:12 0.00 0.00 01-AUG-00:05
September 213357.30 2921040.14 14-SEP-05:03 0.00 0.00 01-SEP-00:10
October 37573.62 837961.74 11-OCT-14:30 0.00 0.00 01-OCT-00:10
November 8654.07 339755.82 16-NOV-13:05 0.00 0.00 01-NOV-00:10
December 115.73 52466.15 01-DEC-07:12 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 145476.39     0.00    
Minimum of Months 7.83 2524.20   0.00 0.00  
Maximum of Months 546548.93 3381110.40   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 11601.91 30167.91 12-JAN-16:40 0.00 0.00 01-JAN-00:03
February 40952.58 65601.86 28-FEB-17:00 0.00 0.00 01-FEB-00:03
March 101659.21 1072809.82 15-MAR-14:00 0.00 0.00 01-MAR-00:10
April 126425.30 708120.08 08-APR-13:05 0.00 0.00 01-APR-00:10
May 57064.49 707842.00 10-MAY-15:00 0.00 0.00 01-MAY-00:05
June 305419.24 1319261.78 27-JUN-14:10 0.00 0.00 01-JUN-00:10
July 810782.51 1671759.99 21-JUL-02:50 0.00 0.00 01-JUL-00:10
August 855883.62 1752281.09 13-AUG-15:00 0.00 0.00 01-AUG-00:05
September 106823.43 823578.63 16-SEP-14:30 0.00 0.00 01-SEP-00:10
October 61568.34 456508.56 11-OCT-15:00 0.00 0.00 01-OCT-00:10
November 83089.00 348795.83 05-NOV-14:00 0.00 0.00 01-NOV-00:10
December 97440.33 185719.46 01-DEC-11:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 223768.20     0.00    
Minimum of Months 11601.91 30167.91   0.00 0.00  
Maximum of Months 855883.62 1752281.09   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 15565.49 55761.21 31-JAN-12:20
February 0.00 0.00 01-FEB-00:03 15883.48 55957.89 15-FEB-13:00
March 0.00 0.00 01-MAR-00:10 16653.05 55779.51 01-MAR-13:00
April 0.00 0.00 01-APR-00:10 14992.80 54071.93 03-APR-12:00
May 0.00 0.00 01-MAY-00:05 14631.73 51559.61 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 14076.09 48363.93 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 12326.75 45521.93 03-JUL-11:40
August 0.00 0.00 01-AUG-00:05 13253.10 44047.86 01-AUG-11:30
September 0.00 0.00 01-SEP-00:10 12640.60 45462.23 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 13239.12 48280.13 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 14277.44 51375.07 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 14571.55 54008.75 29-DEC-12:15
             
Annual Sum or Average 0.00     14333.73    
Minimum of Months 0.00 0.00   12326.75 44047.86  
Maximum of Months 0.00 0.00   16653.05 55957.89  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8.79 15185.59 11-JAN-13:40 791.25 131345.16 24-JAN-07:03
February 13.18 35031.95 22-FEB-15:40 1350.07 144048.12 22-FEB-06:01
March 30160.85 2361943.00 14-MAR-12:50 3843.88 134194.80 01-MAR-15:40
April 23027.34 639105.21 19-APR-15:20 3145.80 127391.17 03-APR-08:30
May 90559.84 2643910.76 10-MAY-14:05 1203.51 96955.51 01-MAY-06:50
June 554003.41 5424218.53 27-JUN-07:40 576.45 79503.79 14-JUN-13:00
July 1110667.70 6037121.13 05-JUL-16:00 283.49 44432.12 07-JUL-07:00
August 804475.18 5886693.55 14-AUG-10:05 957.13 66790.61 12-AUG-22:50
September 325295.37 4499093.94 15-SEP-11:00 550.05 70306.19 06-SEP-08:50
October 40339.12 946306.03 11-OCT-14:40 1949.93 111968.00 17-OCT-16:50
November 7557.32 377302.48 16-NOV-13:10 4444.86 130469.92 28-NOV-16:10
December 9.34 16115.84 14-DEC-14:50 1475.60 139195.14 29-DEC-07:03
             
Annual Sum or Average 251122.51     1712.23    
Minimum of Months 8.79 15185.59   283.49 44432.12  
Maximum of Months 1110667.70 6037121.13   4444.86 144048.12  



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.281282E+10 0.31 11967.39 03-JAN-06:01 1.35
February 0.285544E+10 0.32 11967.39 03-FEB-06:01 1.35
March 0.575392E+10 0.41 14279.79 15-MAR-14:20 1.49
April 0.762825E+10 0.48 15970.50 24-APR-14:50 1.61
May 0.795645E+10 0.49 16248.37 17-MAY-05:02 1.62
June 0.128400E+11 0.67 21058.33 12-JUN-04:12 1.90
July 0.160289E+11 0.79 21058.33 17-JUL-04:22 1.90
August 0.162295E+11 0.81 21058.33 03-AUG-13:13 1.91
September 0.886544E+10 0.52 21058.33 14-SEP-04:12 1.90
October 0.634007E+10 0.42 14982.15 10-OCT-15:40 1.54
November 0.496353E+10 0.37 11351.02 27-NOV-11:00 1.30
December 0.368853E+10 0.33 11967.39 07-DEC-06:01 1.35
           
Annual Sum or Average 0.959628E+11 0.49      
Minimum of Months 0.281282E+10 0.31 11351.02   1.30
Maximum of Months 0.162295E+11 0.81 21058.33   1.91



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.259210E+11 0.34 52999.09 02-JAN-04:01 0.87
February 0.231590E+11 0.33 52999.09 06-FEB-05:01 0.87
March 0.318961E+11 0.34 92884.68 15-MAR-14:30 1.19
April 0.375049E+11 0.35 128988.64 05-APR-05:02 1.47
May 0.584056E+11 0.43 116839.06 23-MAY-14:30 1.38
June 0.860121E+11 0.54 196180.48 26-JUN-05:02 1.90
July 0.973406E+11 0.56 196180.48 17-JUL-04:12 1.90
August 0.951701E+11 0.56 196180.48 07-AUG-04:12 1.90
September 0.620371E+11 0.44 163788.09 14-SEP-05:03 1.69
October 0.360519E+11 0.33 89242.22 12-OCT-14:30 1.16
November 0.252497E+11 0.30 138470.56 03-NOV-05:02 1.54
December 0.241563E+11 0.32 52999.09 11-DEC-05:01 0.87
           
Annual Sum or Average 0.602904E+12 0.41      
Minimum of Months 0.231590E+11 0.30 52999.09   0.87
Maximum of Months 0.973406E+11 0.56 196180.48   1.90



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.335999E+10 0.42 5019.64 02-JAN-04:01 0.80
February 0.306673E+10 0.42 5019.64 01-FEB-05:11 0.80
March 0.318846E+10 0.37 10341.57 15-MAR-14:20 1.20
April 0.310946E+10 0.34 8925.82 21-APR-15:20 1.11
May 0.501386E+10 0.39 12302.14 31-MAY-15:50 1.34
June 0.850764E+10 0.51 20031.37 12-JUN-04:12 1.82
July 0.101574E+11 0.55 21553.33 21-JUL-05:02 1.90
August 0.940128E+10 0.53 21553.33 07-AUG-04:12 1.90
September 0.536997E+10 0.40 14796.47 21-SEP-16:00 1.50
October 0.288890E+10 0.31 8641.24 11-OCT-16:00 1.08
November 0.235096E+10 0.32 5019.64 13-NOV-05:11 0.80
December 0.315996E+10 0.40 5019.64 04-DEC-04:01 0.80
           
Annual Sum or Average 0.595746E+11 0.41      
Minimum of Months 0.235096E+10 0.31 5019.64   0.80
Maximum of Months 0.101574E+11 0.55 21553.33   1.90



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.207956E+10 0.31 11720.32 02-JAN-07:03 1.92
February 0.192139E+10 0.31 11720.32 01-FEB-07:05 1.93
March 0.480676E+10 0.45 11720.32 01-MAR-07:03 1.94
April 0.927541E+10 0.67 11720.32 01-APR-06:05 1.93
May 0.116105E+11 0.77 11720.32 01-MAY-06:05 1.93
June 0.969575E+10 0.65 11720.32 01-JUN-06:10 1.92
July 0.802382E+10 0.51 11720.32 01-JUL-06:10 1.92
August 0.107407E+11 0.69 11720.32 01-AUG-06:10 1.91
September 0.109285E+11 0.74 11720.32 01-SEP-06:10 1.92
October 0.124746E+11 0.81 11720.32 02-OCT-06:05 1.93
November 0.116675E+11 0.79 11720.32 01-NOV-06:05 1.93
December 0.436914E+10 0.41 11720.32 01-DEC-07:10 1.93
           
Annual Sum or Average 0.975937E+11 0.60      
Minimum of Months 0.192139E+10 0.31 11720.32   1.91
Maximum of Months 0.124746E+11 0.81 11720.32   1.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.110676E+12 1.38 41321.86 01-JAN-00:05 1.38
February 0.999658E+11 1.38 41321.86 01-FEB-00:03 1.38
March 0.110676E+12 1.38 41321.86 01-MAR-00:10 1.39
April 0.107106E+12 1.38 41321.86 01-APR-00:10 1.38
May 0.110676E+12 1.38 41321.86 01-MAY-00:05 1.38
June 0.107106E+12 1.37 41321.86 01-JUN-00:10 1.38
July 0.110676E+12 1.37 41321.86 01-JUL-00:10 1.38
August 0.110676E+12 1.37 41321.86 01-AUG-00:10 1.37
September 0.107106E+12 1.38 41321.86 01-SEP-00:10 1.38
October 0.110676E+12 1.38 41321.86 01-OCT-00:10 1.38
November 0.107106E+12 1.38 41321.86 01-NOV-00:10 1.38
December 0.110676E+12 1.39 41321.86 01-DEC-00:10 1.39
           
Annual Sum or Average 0.130313E+13 1.38      
Minimum of Months 0.999658E+11 1.37 41321.86   1.37
Maximum of Months 0.110676E+12 1.39 41321.86   1.39



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148130E+10 0.94 553.05 01-JAN-00:03 0.94
February 0.133795E+10 0.94 553.05 01-FEB-00:03 0.95
March 0.148130E+10 0.94 553.05 01-MAR-00:10 0.94
April 0.143352E+10 0.94 553.05 01-APR-00:10 0.94
May 0.148130E+10 0.94 553.05 01-MAY-00:05 0.94
June 0.143352E+10 0.94 553.05 01-JUN-00:10 0.94
July 0.148130E+10 0.94 553.05 01-JUL-00:10 0.94
August 0.148130E+10 0.94 553.05 01-AUG-00:05 0.94
September 0.143352E+10 0.94 553.05 01-SEP-00:10 0.94
October 0.148130E+10 0.94 553.05 01-OCT-00:10 0.94
November 0.143352E+10 0.94 553.05 01-NOV-00:10 0.94
December 0.148130E+10 0.94 553.05 01-DEC-00:10 0.94
           
Annual Sum or Average 0.174411E+11 0.94      
Minimum of Months 0.133795E+10 0.94 553.05   0.94
Maximum of Months 0.148130E+10 0.94 553.05   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.142085E+11 0.94 5304.86 01-JAN-00:03 0.94
February 0.128335E+11 0.94 5304.86 01-FEB-00:07 0.95
March 0.142085E+11 0.94 5304.86 01-MAR-00:10 0.94
April 0.137502E+11 0.94 5304.86 01-APR-00:20 0.94
May 0.142085E+11 0.94 5304.86 01-MAY-00:05 0.94
June 0.137502E+11 0.94 5304.86 01-JUN-00:20 0.94
July 0.142085E+11 0.94 5304.86 01-JUL-00:10 0.94
August 0.142085E+11 0.94 5304.86 01-AUG-00:05 0.94
September 0.137502E+11 0.94 5304.86 01-SEP-00:10 0.94
October 0.142085E+11 0.94 5304.86 01-OCT-00:10 0.94
November 0.137502E+11 0.94 5304.86 01-NOV-00:10 0.94
December 0.142085E+11 0.94 5304.86 01-DEC-00:10 0.94
           
Annual Sum or Average 0.167294E+12 0.94      
Minimum of Months 0.128335E+11 0.94 5304.86   0.94
Maximum of Months 0.142085E+11 0.94 5304.86   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144520E+10 0.94 539.58 01-JAN-00:03 0.94
February 0.130534E+10 0.94 539.58 01-FEB-00:03 0.95
March 0.144520E+10 0.94 539.58 01-MAR-00:10 0.94
April 0.139858E+10 0.94 539.58 01-APR-00:10 0.94
May 0.144520E+10 0.94 539.58 01-MAY-00:05 0.94
June 0.139858E+10 0.94 539.58 01-JUN-00:10 0.94
July 0.144520E+10 0.94 539.58 01-JUL-00:10 0.94
August 0.144520E+10 0.94 539.58 01-AUG-00:05 0.94
September 0.139858E+10 0.94 539.58 01-SEP-00:10 0.94
October 0.144520E+10 0.94 539.58 01-OCT-00:10 0.94
November 0.139858E+10 0.94 539.58 01-NOV-00:10 0.94
December 0.144520E+10 0.94 539.58 01-DEC-00:10 0.94
           
Annual Sum or Average 0.170161E+11 0.94      
Minimum of Months 0.130534E+10 0.94 539.58   0.94
Maximum of Months 0.144520E+10 0.94 539.58   0.95



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 40096375.47 36447605.31 1239.38 09-JAN-06:02 1126.60 1126.60 48.35 10.62
February 28798703.50 26178021.48 1245.05 06-FEB-05:01 1131.75 1131.75 47.54 10.65
March 5722222.37 5201500.13 441.39 07-MAR-06:01 401.22 401.22 45.52 6.75
April 680456.77 618535.21 399.05 17-APR-05:01 362.74 362.74 39.48 6.46
May 59506.79 54091.67 19.92 11-MAY-13:20 18.10 18.10 30.21 1.34
June 10656.13 9686.43 16.72 13-JUN-11:05 15.20 15.20 28.99 1.20
July 0.06 0.05 0.00 02-JUL-23:00 0.00 0.00 29.62 0.00
August 58.14 52.85 0.19 31-AUG-11:05 0.18 0.18 29.58 0.03
September 10766.35 9786.61 3.68 28-SEP-10:00 3.34 3.34 27.88 0.42
October 561565.42 510462.96 402.71 30-OCT-05:01 366.07 366.07 38.48 6.49
November 2423620.56 2203071.09 413.57 24-NOV-06:01 375.94 375.94 43.75 6.55
December 23952554.70 21772872.22 1221.92 11-DEC-05:01 1110.72 1110.72 46.28 10.57
                 
Annual Sum or Average 0.102316E+09 93005686.00            
Minimum of Months 0.06 0.05 0.00   0.00 0.00 27.88 0.00
Maximum of Months 40096375.47 36447605.31 1245.05   1131.75 1131.75 48.35 10.65



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 14041.42 12763.65 1.40 11-JAN-16:10 1.27 1.27 6.70 0.38
February 49164.21 44690.27 2.92 22-FEB-17:00 2.66 2.66 6.70 0.73
March 43845418.71 39855485.61 2039.73 15-MAR-13:30 1854.11 1854.11 6.71 34.45
April 14493508.50 13174599.23 278.70 20-APR-13:20 253.34 253.34 6.70 13.80
May 0.102542E+09 93210637.73 1549.55 26-MAY-15:00 1408.54 1408.54 6.71 30.59
June 0.650271E+09 0.591097E+09 9985.12 27-JUN-05:03 9076.47 9076.47 9.91 66.10
July 0.126057E+10 0.114586E+10 9986.54 29-JUL-05:03 9077.76 9077.76 10.44 66.10
August 0.118685E+10 0.107885E+10 10240.93 03-AUG-13:13 9309.00 9309.00 10.20 66.76
September 0.470663E+09 0.427832E+09 10249.83 21-SEP-12:52 9317.09 9317.09 9.40 66.78
October 58836777.13 53482630.41 1491.47 11-OCT-14:30 1355.75 1355.75 6.71 30.08
November 4983524.15 4530023.46 192.78 16-NOV-13:05 175.23 175.23 6.70 11.46
December 36039.98 32760.34 9.51 01-DEC-07:13 8.64 8.64 6.70 1.85
                 
Annual Sum or Average 0.379315E+10 0.344798E+10            
Minimum of Months 14041.42 12763.65 1.40   1.27 1.27 6.70 0.38
Maximum of Months 0.126057E+10 0.114586E+10 10249.83   9317.09 9317.09 10.44 66.78



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.227539E+09 0.206833E+09 3881.22 02-JAN-07:03 3528.03 3528.03 6.71 34.68
February 0.271957E+09 0.247209E+09 3881.22 03-FEB-07:03 3528.03 3528.03 6.72 34.68
March 0.182215E+10 0.165633E+10 3881.22 01-MAR-07:03 3528.03 3528.03 6.73 34.68
April 0.222897E+10 0.202613E+10 3881.22 01-APR-08:00 3528.03 3528.03 6.73 34.68
May 0.376835E+10 0.342543E+10 3881.22 01-MAY-06:33 3528.03 3528.03 6.77 34.68
June 0.638380E+10 0.580287E+10 3881.22 01-JUN-04:12 3528.03 3528.03 8.18 34.68
July 0.851042E+10 0.773597E+10 3881.22 01-JUL-04:12 3528.03 3528.03 7.86 34.68
August 0.828194E+10 0.752829E+10 3881.22 01-AUG-00:20 3528.03 3528.03 6.81 34.68
September 0.498538E+10 0.453171E+10 3881.22 01-SEP-04:12 3528.03 3528.03 7.58 34.68
October 0.253464E+10 0.230399E+10 3881.22 01-OCT-12:55 3528.03 3528.03 6.77 34.68
November 0.194475E+10 0.176778E+10 3881.22 01-NOV-07:10 3528.03 3528.03 6.97 34.68
December 0.370074E+09 0.336398E+09 3881.22 01-DEC-07:12 3528.03 3528.03 6.84 34.68
                 
Annual Sum or Average 0.413300E+11 0.375689E+11            
Minimum of Months 0.227539E+09 0.206833E+09 3881.22   3528.03 3528.03 6.71 34.68
Maximum of Months 0.851042E+10 0.773597E+10 3881.22   3528.03 3528.03 8.18 34.68



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00 6.70 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00 6.72 0.00
March 19794230.14 17992955.20 3881.22 14-MAR-12:50 3528.03 3528.03 15.15 17.34
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 6.73 0.00
May 38424093.81 34927501.27 3881.22 10-MAY-14:05 3528.03 3528.03 11.30 34.68
June 0.928970E+09 0.844434E+09 3881.22 01-JUN-14:40 3528.03 3528.03 15.29 17.34
July 0.201032E+10 0.182738E+10 3881.22 03-JUL-12:05 3528.03 3528.03 11.36 34.68
August 0.147580E+10 0.134150E+10 3881.22 01-AUG-14:05 3528.03 3528.03 15.25 17.34
September 0.465048E+09 0.422729E+09 3881.22 08-SEP-12:50 3528.03 3528.03 15.56 17.34
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 6.84 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 7.36 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.73 0.00
                 
Annual Sum or Average 0.493835E+10 0.448896E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.70 0.00
Maximum of Months 0.201032E+10 0.182738E+10 3881.22   3528.03 3528.03 15.56 34.68



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.100777E+11 0.916060E+10 3762.57 01-JAN-00:03 3420.18 3420.18 18.49 15.87
February 0.910241E+10 0.827409E+10 3762.57 01-FEB-00:03 3420.18 3420.18 18.87 15.87
March 0.100777E+11 0.916060E+10 3762.57 01-MAR-00:10 3420.18 3420.18 19.65 15.87
April 0.975258E+10 0.886510E+10 3762.57 01-APR-00:10 3420.18 3420.18 20.33 15.87
May 0.100777E+11 0.916060E+10 3762.57 01-MAY-00:05 3420.18 3420.18 18.91 15.87
June 0.975258E+10 0.886510E+10 3762.57 01-JUN-00:10 3420.18 3420.18 19.41 15.87
July 0.100777E+11 0.916060E+10 3762.57 01-JUL-00:10 3420.18 3420.18 20.05 15.87
August 0.100777E+11 0.916060E+10 3762.57 01-AUG-00:05 3420.18 3420.18 30.98 15.87
September 0.975258E+10 0.886510E+10 3762.57 01-SEP-00:10 3420.18 3420.18 18.90 15.87
October 0.100777E+11 0.916060E+10 3762.57 01-OCT-00:10 3420.18 3420.18 19.28 15.87
November 0.975258E+10 0.886510E+10 3762.57 01-NOV-00:10 3420.18 3420.18 19.87 15.87
December 0.100777E+11 0.916060E+10 3762.57 01-DEC-00:10 3420.18 3420.18 20.18 15.87
                 
Annual Sum or Average 0.118656E+12 0.107859E+12            
Minimum of Months 0.910241E+10 0.827409E+10 3762.57   3420.18 3420.18 18.49 15.87
Maximum of Months 0.100777E+11 0.916060E+10 3762.57   3420.18 3420.18 30.98 15.87



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:03 16.86 16.86 56.88 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 56.79 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:01 16.86 16.86 56.93 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:02 16.86 16.86 56.88 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:02 16.86 16.86 57.25 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 57.16 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 57.32 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 57.47 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 57.42 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 57.09 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 57.22 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:03 16.86 16.86 56.98 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.79 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.47 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.873805E+09 0.794289E+09 14906.94 11-JAN-13:40 13550.41 13550.41 21.16 61.04
February 0.104137E+10 0.946603E+09 14907.78 22-FEB-15:40 13551.17 13551.17 21.24 61.04
March 0.706386E+10 0.642104E+10 29914.78 14-MAR-12:50 27192.53 27192.53 25.73 122.07
April 0.856279E+10 0.778358E+10 14933.18 19-APR-15:20 13574.26 13574.26 23.61 61.04
May 0.145500E+11 0.132260E+11 29928.63 10-MAY-14:05 27205.13 27205.13 26.28 122.07
June 0.278039E+11 0.252737E+11 30008.18 27-JUN-07:20 27277.43 27277.43 30.96 122.07
July 0.401771E+11 0.365210E+11 30008.18 05-JUL-09:50 27277.43 27277.43 29.98 122.07
August 0.370774E+11 0.337034E+11 30008.18 07-AUG-12:05 27277.43 27277.43 29.61 122.07
September 0.208131E+11 0.189191E+11 30008.18 15-SEP-10:40 27277.43 27277.43 29.59 122.07
October 0.973318E+10 0.884746E+10 14946.13 11-OCT-14:40 13586.03 13586.03 24.81 61.04
November 0.746810E+10 0.678850E+10 14922.16 16-NOV-13:10 13564.25 13564.25 22.58 61.04
December 0.142115E+10 0.129183E+10 14906.98 14-DEC-14:50 13550.45 13550.45 21.16 61.04
                 
Annual Sum or Average 0.176586E+12 0.160516E+12            
Minimum of Months 0.873805E+09 0.794289E+09 14906.94   13550.41 13550.41 21.16 61.04
Maximum of Months 0.401771E+11 0.365210E+11 30008.18   27277.43 27277.43 30.96 122.07



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 32.86 32.86 104830.60 1925048.11 02-JAN-04:01
February 0.00 0.00 01-FEB-00:03 39.58 39.58 89475.01 1536938.75 14-FEB-06:01
March 0.00 0.00 01-MAR-00:10 27.16 27.16 24791.89 1349036.32 21-MAR-04:01
April 0.00 0.00 01-APR-00:10 28.41 28.41 4732.34 1147875.06 17-APR-05:01
May 0.00 0.00 01-MAY-00:05 28.44 28.44 455.48 290462.63 11-MAY-13:20
June 0.00 0.00 01-JUN-00:10 28.98 28.98 70.89 266980.70 13-JUN-11:05
July 0.00 0.00 01-JUL-00:10 29.62 29.62 0.00 3.30 02-JUL-23:00
August 0.00 0.00 01-AUG-00:05 29.62 29.62 0.75 6715.82 31-AUG-11:05
September 0.00 0.00 01-SEP-00:10 29.54 29.54 127.89 95519.61 28-SEP-10:00
October 0.00 0.00 01-OCT-00:10 26.33 26.33 3717.41 1180245.45 30-OCT-05:01
November 0.00 0.00 01-NOV-00:10 26.43 26.43 14581.55 1271376.51 25-NOV-05:01
December 0.00 0.00 01-DEC-00:10 25.45 25.45 78544.14 1578205.58 11-DEC-05:01
                 
Annual Sum or Average 0.00         26502.00    
Minimum of Months 0.00 0.00   25.45 25.45 0.00 3.30  
Maximum of Months 0.00 0.00   39.58 39.58 104830.60 1925048.11  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 84.90 6051.85 11-JAN-16:50 6.74 6.70 0.00 0.00 01-JAN-00:03
February 261.49 28978.45 22-FEB-17:00 6.90 6.70 0.00 0.00 01-FEB-00:03
March 25184.93 1456153.93 15-MAR-14:05 11.71 6.70 0.00 0.00 01-MAR-00:10
April 24720.21 567293.73 19-APR-15:10 10.60 6.70 0.00 0.00 01-APR-00:10
May 82086.29 1342058.50 10-MAY-14:50 15.95 6.70 0.00 0.00 01-MAY-00:05
June 333724.85 2082972.73 27-JUN-07:40 13.87 6.70 0.00 0.00 01-JUN-00:10
July 548567.49 2830692.47 05-JUL-16:00 16.46 8.07 0.00 0.00 01-JUL-00:10
August 462173.16 2542021.81 15-AUG-05:03 15.46 7.07 0.00 0.00 01-AUG-00:05
September 213381.30 2261495.91 21-SEP-12:52 14.49 6.70 0.00 0.00 01-SEP-00:10
October 38401.15 835702.04 11-OCT-14:30 12.45 6.70 0.00 0.00 01-OCT-00:10
November 9337.35 333603.93 16-NOV-13:10 8.99 6.70 0.00 0.00 01-NOV-00:10
December 241.31 40222.44 01-DEC-07:13 6.98 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 146030.55         0.00    
Minimum of Months 84.90 6051.85   6.74 6.70 0.00 0.00  
Maximum of Months 548567.49 2830692.47   16.46 8.07 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 7.83 2524.20 11-JAN-16:50 8.55 6.70 0.00 0.00 01-JAN-00:03
February 159.38 25537.99 22-FEB-17:00 15.10 6.70 0.00 0.00 01-FEB-00:03
March 24541.90 1286687.90 15-MAR-14:20 16.28 6.70 0.00 0.00 01-MAR-00:10
April 23953.39 564599.76 19-APR-15:00 19.09 6.70 0.00 0.00 01-APR-00:10
May 80742.57 1382157.36 10-MAY-14:50 17.68 6.70 0.00 0.00 01-MAY-00:05
June 332046.15 2995747.60 27-JUN-05:03 17.54 11.83 0.00 0.00 01-JUN-00:10
July 546548.93 3282820.77 17-JUL-05:02 18.58 6.70 0.00 0.00 01-JUL-00:10
August 463827.25 3381110.40 15-AUG-04:12 18.93 12.49 0.00 0.00 01-AUG-00:05
September 213357.30 2921040.14 14-SEP-05:03 17.26 11.71 0.00 0.00 01-SEP-00:10
October 37573.62 837961.74 11-OCT-14:30 13.35 6.70 0.00 0.00 01-OCT-00:10
November 8654.07 339755.82 16-NOV-13:05 13.78 6.70 0.00 0.00 01-NOV-00:10
December 115.73 52466.15 01-DEC-07:12 13.54 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 145476.39         0.00    
Minimum of Months 7.83 2524.20   8.55 6.70 0.00 0.00  
Maximum of Months 546548.93 3381110.40   19.09 12.49 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 11601.91 30167.91 12-JAN-16:40 18.88 18.33 0.00 0.00 01-JAN-00:03
February 40952.58 65601.86 28-FEB-17:00 19.52 18.33 0.00 0.00 01-FEB-00:03
March 101659.21 1072809.82 15-MAR-14:00 37.50 29.09 0.00 0.00 01-MAR-00:10
April 126425.30 708120.08 08-APR-13:05 31.06 23.63 0.00 0.00 01-APR-00:10
May 57064.49 707842.00 10-MAY-15:00 31.05 27.39 0.00 0.00 01-MAY-00:05
June 305419.24 1319261.78 27-JUN-14:10 41.80 30.86 0.00 0.00 01-JUN-00:10
July 810782.51 1671759.99 21-JUL-02:50 47.90 33.95 0.00 0.00 01-JUL-00:10
August 855883.62 1752281.09 13-AUG-15:00 49.29 35.14 0.00 0.00 01-AUG-00:05
September 106823.43 823578.63 16-SEP-14:30 33.11 28.56 0.00 0.00 01-SEP-00:10
October 61568.34 456508.56 11-OCT-15:00 26.57 23.33 0.00 0.00 01-OCT-00:10
November 83089.00 348795.83 05-NOV-14:00 24.64 20.75 0.00 0.00 01-NOV-00:10
December 97440.33 185719.46 01-DEC-11:00 21.70 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 223768.20         0.00    
Minimum of Months 11601.91 30167.91   18.88 18.33 0.00 0.00  
Maximum of Months 855883.62 1752281.09   49.29 35.14 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 57.99 57.99 15565.49 55761.21 31-JAN-12:20
February 0.00 0.00 01-FEB-00:03 57.39 57.39 15883.48 55957.89 15-FEB-13:00
March 0.00 0.00 01-MAR-00:10 57.39 57.39 16653.05 55779.51 01-MAR-13:00
April 0.00 0.00 01-APR-00:10 57.46 57.46 14992.80 54071.93 03-APR-12:00
May 0.00 0.00 01-MAY-00:05 58.08 58.08 14631.73 51559.61 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 57.74 57.74 14076.09 48363.93 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 57.87 57.87 12326.75 45521.93 03-JUL-11:40
August 0.00 0.00 01-AUG-00:05 57.95 57.95 13253.10 44047.86 01-AUG-11:30
September 0.00 0.00 01-SEP-00:10 57.95 57.95 12640.60 45462.23 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 57.88 57.88 13239.12 48280.13 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 57.75 57.75 14277.44 51375.07 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 57.60 57.60 14571.55 54008.75 29-DEC-12:15
                 
Annual Sum or Average 0.00         14333.73    
Minimum of Months 0.00 0.00   57.39 57.39 12326.75 44047.86  
Maximum of Months 0.00 0.00   58.08 58.08 16653.05 55957.89  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8.79 15185.59 11-JAN-13:40 21.16 20.65 791.25 131345.16 24-JAN-07:03
February 13.18 35031.95 22-FEB-15:40 21.24 20.58 1350.07 144048.12 22-FEB-06:01
March 30160.85 2361943.00 14-MAR-12:50 25.73 22.46 3843.88 134194.80 01-MAR-15:40
April 23027.34 639105.21 19-APR-15:20 23.61 21.10 3145.80 127391.17 03-APR-08:30
May 90559.84 2643910.76 10-MAY-14:05 26.28 22.80 1203.51 96955.51 01-MAY-06:50
June 554003.41 5424218.53 27-JUN-07:40 31.73 27.03 576.45 79503.79 14-JUN-13:00
July 1110667.70 6037121.13 05-JUL-16:00 32.93 27.36 283.49 44432.12 07-JUL-07:00
August 804475.18 5886693.55 14-AUG-10:05 32.64 27.51 957.13 66790.61 12-AUG-22:50
September 325295.37 4499093.94 15-SEP-11:00 29.92 25.49 550.05 70306.19 06-SEP-08:50
October 40339.12 946306.03 11-OCT-14:40 24.81 21.10 1949.93 111968.00 17-OCT-16:50
November 7557.32 377302.48 16-NOV-13:10 22.58 21.10 4444.86 130469.92 28-NOV-16:10
December 9.34 16115.84 14-DEC-14:50 21.16 20.52 1475.60 139195.14 29-DEC-07:03
                 
Annual Sum or Average 251122.51         1712.23    
Minimum of Months 8.79 15185.59   21.16 20.52 283.49 44432.12  
Maximum of Months 1110667.70 6037121.13   32.93 27.51 4444.86 144048.12  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.334659E+10 0.00 11550518.54 0.281282E+10 0.00 0.00
February 0.250194E+10 0.00 0.389478E+09 0.285544E+10 0.00 0.00
March 0.561346E+09 0.00 0.897677E+10 0.575392E+10 0.00 0.00
April 92137377.13 0.00 0.474962E+10 0.762825E+10 0.00 0.00
May 9697546.79 0.00 0.185430E+11 0.795645E+10 0.00 0.00
June 0.00 0.00 0.851655E+11 0.128400E+11 0.00 0.00
July 0.00 0.00 0.156732E+12 0.160289E+11 0.00 0.00
August 0.00 0.00 0.132182E+12 0.162295E+11 0.00 0.00
September 2164065.33 0.00 0.509929E+11 0.886544E+10 0.00 0.00
October 79476037.10 0.00 0.102865E+11 0.634007E+10 0.00 0.00
November 0.161302E+09 0.00 0.533096E+10 0.496353E+10 0.00 0.00
December 0.160934E+10 0.00 0.264578E+09 0.368853E+10 0.00 0.00
             
Annual Sum or Average 0.836399E+10 0.00 0.473624E+12 0.959628E+11 0.00 0.00
Minimum of Months 0.00 0.00 11550518.54 0.281282E+10 0.00 0.00
Maximum of Months 0.334659E+10 0.00 0.156732E+12 0.162295E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.215852E+12 0.00 8897611.50 0.259210E+11 0.00 0.00
February 0.162515E+12 0.00 56474678.37 0.231590E+11 0.00 0.00
March 0.468040E+11 0.00 0.452818E+11 0.318961E+11 0.00 0.00
April 0.843472E+10 0.00 0.544718E+11 0.375049E+11 0.00 0.00
May 0.103818E+10 0.00 0.167717E+12 0.584056E+11 0.00 0.00
June 0.177616E+09 0.00 0.646351E+12 0.860121E+11 0.00 0.00
July 0.00 0.00 0.108265E+13 0.973406E+11 0.00 0.00
August 2441003.07 0.00 0.905340E+12 0.951701E+11 0.00 0.00
September 0.236230E+09 0.00 0.412795E+12 0.620371E+11 0.00 0.00
October 0.635782E+10 0.00 0.804732E+11 0.360519E+11 0.00 0.00
November 0.261948E+11 0.00 0.157286E+11 0.252497E+11 0.00 0.00
December 0.161285E+12 0.00 42848555.41 0.241563E+11 0.00 0.00
             
Annual Sum or Average 0.628898E+12 0.00 0.341092E+13 0.602904E+12 0.00 0.00
Minimum of Months 0.00 0.00 8897611.50 0.231590E+11 0.00 0.00
Maximum of Months 0.215852E+12 0.00 0.108265E+13 0.973406E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.496334E+11 0.00 1117683.74 0.335999E+10 0.00 0.00
February 0.412816E+11 0.00 5331679.48 0.306673E+10 0.00 0.00
March 0.160412E+11 0.00 0.407671E+10 0.318846E+10 0.00 0.00
April 0.368441E+10 0.00 0.150635E+10 0.310946E+10 0.00 0.00
May 0.174463E+09 0.00 0.156220E+11 0.501386E+10 0.00 0.00
June 3747716.35 0.00 0.699716E+11 0.850764E+10 0.00 0.00
July 159.23 0.00 0.119770E+12 0.101574E+11 0.00 0.00
August 0.00 0.00 0.981338E+11 0.940128E+10 0.00 0.00
September 0.111611E+09 0.00 0.399541E+11 0.536997E+10 0.00 0.00
October 0.356734E+10 0.00 0.445403E+10 0.288890E+10 0.00 0.00
November 0.115383E+11 0.00 0.554335E+09 0.235096E+10 0.00 0.00
December 0.432609E+11 0.00 4194387.81 0.315996E+10 0.00 0.00
             
Annual Sum or Average 0.169297E+12 0.00 0.354053E+12 0.595746E+11 0.00 0.00
Minimum of Months 0.00 0.00 1117683.74 0.235096E+10 0.00 0.00
Maximum of Months 0.496334E+11 0.00 0.119770E+12 0.101574E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.133695E+11 0.00 41389778.29 0.207956E+10 0.00 0.00
February 0.113473E+11 0.00 38811114.69 0.192139E+10 0.00 0.00
March 0.333298E+10 0.00 0.390107E+10 0.480676E+10 0.00 0.00
April 0.118347E+09 0.00 0.153861E+10 0.927541E+10 0.00 0.00
May 1076750.42 0.00 0.121745E+11 0.116105E+11 0.00 0.00
June 396.97 0.00 0.319718E+11 0.969575E+10 0.00 0.00
July 0.00 0.00 0.532899E+11 0.802382E+10 0.00 0.00
August 242.49 0.00 0.564729E+11 0.107407E+11 0.00 0.00
September 653.52 0.00 0.331419E+11 0.109285E+11 0.00 0.00
October 3033337.42 0.00 0.555058E+10 0.124746E+11 0.00 0.00
November 0.101905E+09 0.00 0.877442E+09 0.116675E+11 0.00 0.00
December 0.523659E+10 0.00 6140035.17 0.436914E+10 0.00 0.00
             
Annual Sum or Average 0.335107E+11 0.00 0.199005E+12 0.975937E+11 0.00 0.00
Minimum of Months 0.00 0.00 6140035.17 0.192139E+10 0.00 0.00
Maximum of Months 0.133695E+11 0.00 0.564729E+11 0.124746E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.108296E+11 0.250425E+12 0.00 50.40
February 0.00 0.00 0.153158E+11 0.308005E+12 0.00 75.52
March 0.00 0.00 0.427223E+11 0.322377E+12 0.00 74.56
April 0.00 0.00 0.489260E+11 0.325200E+12 0.00 76.48
May 0.00 0.00 0.119418E+11 0.195952E+12 0.00 29.97
June 0.00 0.00 0.214581E+12 0.195232E+12 0.00 15.06
July 0.00 0.00 0.896825E+12 0.298686E+12 0.00 0.90
August 0.00 0.00 0.104052E+13 0.329383E+12 0.00 1.63
September 0.00 0.00 0.223499E+11 0.124892E+12 0.00 3.91
October 0.00 0.00 0.135100E+11 0.220523E+12 0.00 39.02
November 0.00 0.00 0.243824E+11 0.328284E+12 0.00 79.62
December 0.00 0.00 0.220151E+11 0.378912E+12 0.00 97.19
             
Annual Sum or Average 0.00 0.00 0.236392E+13 0.327787E+13 0.00 544.26
Minimum of Months 0.00 0.00 0.108296E+11 0.124892E+12 0.00 0.90
Maximum of Months 0.00 0.00 0.104052E+13 0.378912E+12 0.00 97.19



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.393213E+10 0.228453E+10 0.00 0.00
February 0.00 0.00 0.963887E+10 0.319025E+10 0.00 0.00
March 0.00 0.00 0.181673E+11 0.476450E+10 0.00 0.00
April 0.00 0.00 0.238621E+11 0.550359E+10 0.00 0.00
May 0.00 0.00 0.689225E+10 0.278780E+10 0.00 0.00
June 0.00 0.00 0.134464E+11 0.399314E+10 0.00 0.00
July 0.00 0.00 0.208134E+11 0.566455E+10 0.00 0.00
August 0.00 0.00 0.266174E+11 0.662162E+10 0.00 0.00
September 0.00 0.00 0.704204E+10 0.276893E+10 0.00 0.00
October 0.00 0.00 0.125680E+11 0.374096E+10 0.00 0.00
November 0.00 0.00 0.176676E+11 0.455089E+10 0.00 0.00
December 0.00 0.00 0.235566E+11 0.563674E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.184204E+12 0.515075E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.393213E+10 0.228453E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.266174E+11 0.662162E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.704233E+10 0.158173E+11 0.00 0.00
February 0.00 0.00 0.616601E+11 0.250093E+11 0.00 0.00
March 0.00 0.00 0.154302E+12 0.424056E+11 0.00 0.00
April 0.00 0.00 0.216783E+12 0.509624E+11 0.00 0.00
May 0.00 0.00 0.602480E+11 0.257044E+11 0.00 0.00
June 0.00 0.00 0.125406E+12 0.376960E+11 0.00 0.00
July 0.00 0.00 0.196904E+12 0.538511E+11 0.00 0.00
August 0.00 0.00 0.252254E+12 0.630065E+11 0.00 0.00
September 0.00 0.00 0.616034E+11 0.255176E+11 0.00 0.00
October 0.00 0.00 0.106476E+12 0.335328E+11 0.00 0.00
November 0.00 0.00 0.147654E+12 0.401425E+11 0.00 0.00
December 0.00 0.00 0.189263E+12 0.482443E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.157960E+13 0.461890E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.704233E+10 0.158173E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.252254E+12 0.630065E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.125434E+09 0.147449E+10 0.00 0.00
February 0.00 0.00 0.411803E+10 0.213447E+10 0.00 0.00
March 0.00 0.00 0.135018E+11 0.393996E+10 0.00 0.00
April 0.00 0.00 0.204490E+11 0.493550E+10 0.00 0.00
May 0.00 0.00 0.551494E+10 0.250472E+10 0.00 0.00
June 0.00 0.00 0.124638E+11 0.378599E+10 0.00 0.00
July 0.00 0.00 0.197697E+11 0.543363E+10 0.00 0.00
August 0.00 0.00 0.252156E+11 0.633664E+10 0.00 0.00
September 0.00 0.00 0.571983E+10 0.249967E+10 0.00 0.00
October 0.00 0.00 0.903781E+10 0.310332E+10 0.00 0.00
November 0.00 0.00 0.126122E+11 0.368426E+10 0.00 0.00
December 0.00 0.00 0.165579E+11 0.446447E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.145086E+12 0.442971E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.125434E+09 0.147449E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.252156E+11 0.633664E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.281282E+10 11550518.54 0.334659E+10 0.413478E+11 0.00 0.00 0.00 0.00
February 0.285544E+10 0.389478E+09 0.250194E+10 0.361545E+11 0.00 0.00 0.00 0.00
March 0.575392E+10 0.897677E+10 0.561346E+09 0.144503E+11 1535711.07 0.00 0.00 0.00
April 0.762825E+10 0.474962E+10 92137377.13 0.277888E+10 0.00 0.00 0.00 0.00
May 0.795645E+10 0.185430E+11 9697546.79 0.145453E+09 239314.54 0.00 0.00 0.00
June 0.128400E+11 0.851655E+11 0.00 0.139215E+09 0.189468E+10 0.00 0.00 0.00
July 0.160289E+11 0.156732E+12 0.00 0.135390E+09 0.552746E+10 0.00 0.00 0.00
August 0.162295E+11 0.132182E+12 0.00 0.557533E+09 0.221850E+10 0.00 0.00 0.00
September 0.886544E+10 0.509929E+11 2164065.33 63706298.60 0.275864E+09 0.00 0.00 0.00
October 0.634007E+10 0.102865E+11 79476037.10 0.190893E+10 0.00 0.00 0.00 0.00
November 0.496353E+10 0.533096E+10 0.161302E+09 0.580063E+10 0.00 0.00 0.00 0.00
December 0.368853E+10 0.264578E+09 0.160934E+10 0.291827E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.959628E+11 0.473624E+12 0.836399E+10 0.132665E+12 0.991827E+10 0.00 0.00 0.00
Minimum of Months 0.281282E+10 11550518.54 0.00 63706298.60 0.00 0.00 0.00 0.00
Maximum of Months 0.162295E+11 0.156732E+12 0.334659E+10 0.413478E+11 0.552746E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.259210E+11 8897611.50 0.215852E+12 0.435156E+12 0.00 0.00 0.00 0.00
February 0.231590E+11 56474678.37 0.162515E+12 0.398606E+12 0.00 0.00 0.00 0.00
March 0.318961E+11 0.452818E+11 0.468040E+11 0.236505E+12 0.00 0.00 0.00 0.00
April 0.375049E+11 0.544718E+11 0.843472E+10 0.679003E+11 0.00 0.00 0.00 0.00
May 0.584056E+11 0.167717E+12 0.103818E+10 0.404671E+10 4281243.80 0.00 0.00 0.00
June 0.860121E+11 0.646351E+12 0.177616E+09 0.181664E+10 0.187709E+11 0.00 0.00 0.00
July 0.973406E+11 0.108265E+13 0.00 0.189956E+10 0.538306E+11 0.00 0.00 0.00
August 0.951701E+11 0.905340E+12 2441003.07 0.664572E+10 0.210470E+11 0.00 0.00 0.00
September 0.620371E+11 0.412795E+12 0.236230E+09 0.124456E+10 0.295558E+10 0.00 0.00 0.00
October 0.360519E+11 0.804732E+11 0.635782E+10 0.395726E+11 0.00 0.00 0.00 0.00
November 0.252497E+11 0.157286E+11 0.261948E+11 0.133981E+12 0.00 0.00 0.00 0.00
December 0.241563E+11 42848555.41 0.161285E+12 0.376701E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.602904E+12 0.341092E+13 0.628898E+12 0.170408E+13 0.966083E+11 0.00 0.00 0.00
Minimum of Months 0.231590E+11 8897611.50 0.00 0.124456E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.973406E+11 0.108265E+13 0.215852E+12 0.435156E+12 0.538306E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.335999E+10 1117683.74 0.496334E+11 0.446914E+11 0.00 0.00 0.00 0.00
February 0.306673E+10 5331679.48 0.412816E+11 0.406427E+11 0.00 0.00 0.00 0.00
March 0.318846E+10 0.407671E+10 0.160412E+11 0.260220E+11 0.00 0.00 0.00 0.00
April 0.310946E+10 0.150635E+10 0.368441E+10 0.910620E+10 0.00 0.00 0.00 0.00
May 0.501386E+10 0.156220E+11 0.174463E+09 0.743275E+09 0.00 0.00 0.00 0.00
June 0.850764E+10 0.699716E+11 3747716.35 0.223280E+09 0.150172E+10 0.00 0.00 0.00
July 0.101574E+11 0.119770E+12 159.23 0.151318E+09 0.439458E+10 0.00 0.00 0.00
August 0.940128E+10 0.981338E+11 0.00 0.667131E+09 0.155807E+10 0.00 0.00 0.00
September 0.536997E+10 0.399541E+11 0.111611E+09 0.242348E+09 0.176646E+09 0.00 0.00 0.00
October 0.288890E+10 0.445403E+10 0.356734E+10 0.614156E+10 0.00 0.00 0.00 0.00
November 0.235096E+10 0.554335E+09 0.115383E+11 0.170211E+11 0.00 0.00 0.00 0.00
December 0.315996E+10 4194387.81 0.432609E+11 0.395727E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.595746E+11 0.354053E+12 0.169297E+12 0.185225E+12 0.763102E+10 0.00 0.00 0.00
Minimum of Months 0.235096E+10 1117683.74 0.00 0.151318E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.101574E+11 0.119770E+12 0.496334E+11 0.446914E+11 0.439458E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.207956E+10 41389778.29 0.133695E+11 0.00 0.00 0.00 0.00 0.00
February 0.192139E+10 38811114.69 0.113473E+11 0.00 0.00 0.00 0.00 0.00
March 0.480676E+10 0.390107E+10 0.333298E+10 0.00 0.00 0.00 0.00 0.00
April 0.927541E+10 0.153861E+10 0.118347E+09 0.00 0.00 0.00 0.00 0.00
May 0.116105E+11 0.121745E+11 1076750.42 0.00 0.00 0.00 0.00 0.00
June 0.969575E+10 0.319718E+11 396.97 0.00 0.00 0.00 0.00 0.00
July 0.802382E+10 0.532899E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.107407E+11 0.564729E+11 242.49 0.00 0.00 0.00 0.00 0.00
September 0.109285E+11 0.331419E+11 653.52 0.00 0.00 0.00 0.00 0.00
October 0.124746E+11 0.555058E+10 3033337.42 0.00 0.00 0.00 0.00 0.00
November 0.116675E+11 0.877442E+09 0.101905E+09 0.00 0.00 0.00 0.00 0.00
December 0.436914E+10 6140035.17 0.523659E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.975937E+11 0.199005E+12 0.335107E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.192139E+10 6140035.17 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124746E+11 0.564729E+11 0.133695E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.110676E+12 0.656980E+10 0.00 0.00 0.00 0.134881E+12 0.00 0.00
February 0.999658E+11 0.102825E+11 0.00 0.00 0.00 0.202096E+12 0.00 0.00
March 0.110676E+12 0.314528E+11 0.00 0.00 0.00 0.199533E+12 0.00 0.00
April 0.107106E+12 0.364164E+11 0.00 0.00 0.00 0.204663E+12 0.00 0.00
May 0.110676E+12 0.723110E+10 0.00 0.00 0.00 0.802036E+11 0.00 0.00
June 0.107106E+12 0.166936E+12 0.00 0.00 0.00 0.403000E+11 0.00 0.00
July 0.110676E+12 0.711245E+12 0.00 0.00 0.00 0.241863E+10 0.00 0.00
August 0.110676E+12 0.826201E+12 0.00 0.00 0.00 0.437075E+10 0.00 0.00
September 0.107106E+12 0.150678E+11 0.00 0.00 0.00 0.104563E+11 0.00 0.00
October 0.110676E+12 0.854372E+10 0.00 0.00 0.00 0.104410E+12 0.00 0.00
November 0.107106E+12 0.172421E+11 0.00 0.00 0.00 0.213078E+12 0.00 0.00
December 0.110676E+12 0.150363E+11 0.00 0.00 0.00 0.260086E+12 0.00 0.00
                 
Annual Sum or Average 0.130313E+13 0.185223E+13 0.00 0.00 0.00 0.145650E+13 0.00 0.00
Minimum of Months 0.999658E+11 0.656980E+10 0.00 0.00 0.00 0.241863E+10 0.00 0.00
Maximum of Months 0.110676E+12 0.826201E+12 0.00 0.00 0.00 0.260086E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.148130E+10 0.312890E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133795E+10 0.778657E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148130E+10 0.148841E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143352E+10 0.197920E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148130E+10 0.558575E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143352E+10 0.108868E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148130E+10 0.166302E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148130E+10 0.214771E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143352E+10 0.570663E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148130E+10 0.103083E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143352E+10 0.145502E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148130E+10 0.194012E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.174411E+11 0.150138E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133795E+10 0.312890E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148130E+10 0.214771E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.142085E+11 0.543361E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128335E+11 0.494842E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142085E+11 0.126105E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137502E+11 0.179571E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.142085E+11 0.487521E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137502E+11 0.101461E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.142085E+11 0.157261E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.142085E+11 0.203456E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137502E+11 0.498360E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.142085E+11 0.871519E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137502E+11 0.121261E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.142085E+11 0.155227E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.167294E+12 0.128500E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128335E+11 0.543361E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142085E+11 0.203456E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.144520E+10 96147635.28 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130534E+10 0.328890E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144520E+10 0.110070E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139858E+10 0.169121E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144520E+10 0.445542E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139858E+10 0.100764E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144520E+10 0.157813E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144520E+10 0.203241E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139858E+10 0.461874E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144520E+10 0.737969E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139858E+10 0.103265E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144520E+10 0.135386E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170161E+11 0.117805E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130534E+10 96147635.28 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144520E+10 0.203241E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.281282E+10 0.334659E+10 11550518.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.285544E+10 0.250194E+10 0.389478E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.575392E+10 0.561346E+09 0.897677E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.762825E+10 92137377.13 0.474962E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.795645E+10 9697546.79 0.185430E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.128400E+11 0.00 0.851655E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.160289E+11 0.00 0.156732E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162295E+11 0.00 0.132182E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.886544E+10 2164065.33 0.509929E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.634007E+10 79476037.10 0.102865E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.496353E+10 0.161302E+09 0.533096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.368853E+10 0.160934E+10 0.264578E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.959628E+11 0.836399E+10 0.473624E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.281282E+10 0.00 11550518.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162295E+11 0.334659E+10 0.156732E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.259210E+11 0.215852E+12 8897611.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.231590E+11 0.162515E+12 56474678.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.318961E+11 0.468040E+11 0.452818E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.375049E+11 0.843472E+10 0.544718E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.584056E+11 0.103818E+10 0.167717E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.860121E+11 0.177616E+09 0.646351E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.973406E+11 0.00 0.108265E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.951701E+11 2441003.07 0.905340E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.620371E+11 0.236230E+09 0.412795E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.360519E+11 0.635782E+10 0.804732E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.252497E+11 0.261948E+11 0.157286E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.241563E+11 0.161285E+12 42848555.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.602904E+12 0.628898E+12 0.341092E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.231590E+11 0.00 8897611.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.973406E+11 0.215852E+12 0.108265E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.335999E+10 0.496334E+11 1117683.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.306673E+10 0.412816E+11 5331679.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.318846E+10 0.160412E+11 0.407671E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.310946E+10 0.368441E+10 0.150635E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.501386E+10 0.174463E+09 0.156220E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.850764E+10 3747716.35 0.699716E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.101574E+11 159.23 0.119770E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.940128E+10 0.00 0.981338E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.536997E+10 0.111611E+09 0.399541E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288890E+10 0.356734E+10 0.445403E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.235096E+10 0.115383E+11 0.554335E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.315996E+10 0.432609E+11 4194387.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.595746E+11 0.169297E+12 0.354053E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.235096E+10 0.00 1117683.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101574E+11 0.496334E+11 0.119770E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.207956E+10 0.133695E+11 41389778.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.192139E+10 0.113473E+11 38811114.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.480676E+10 0.333298E+10 0.390107E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.927541E+10 0.118347E+09 0.153861E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.116105E+11 1076750.42 0.121745E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.969575E+10 396.97 0.319718E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.802382E+10 0.00 0.532899E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.107407E+11 242.49 0.564729E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.109285E+11 653.52 0.331419E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.124746E+11 3033337.42 0.555058E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.116675E+11 0.101905E+09 0.877442E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.436914E+10 0.523659E+10 6140035.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.975937E+11 0.335107E+11 0.199005E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.192139E+10 0.00 6140035.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124746E+11 0.133695E+11 0.564729E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.110676E+12 0.00 0.108296E+11 0.00 0.425978E+10 0.00 0.00 0.00 0.135489E+12 0.00 0.00 0.00
February 0.999658E+11 0.00 0.153158E+11 0.00 0.503325E+10 0.00 0.00 0.00 0.203006E+12 0.00 0.00 0.00
March 0.110676E+12 0.00 0.427223E+11 0.00 0.112696E+11 0.00 0.00 0.00 0.200431E+12 0.00 0.00 0.00
April 0.107106E+12 0.00 0.489260E+11 0.00 0.125096E+11 0.00 0.00 0.00 0.205584E+12 0.00 0.00 0.00
May 0.110676E+12 0.00 0.119418E+11 0.00 0.471073E+10 0.00 0.00 0.00 0.805646E+11 0.00 0.00 0.00
June 0.107106E+12 0.00 0.214581E+12 0.00 0.476443E+11 0.00 0.00 0.00 0.404814E+11 0.00 0.00 0.00
July 0.110676E+12 0.00 0.896825E+12 0.00 0.185580E+12 0.00 0.00 0.00 0.242952E+10 0.00 0.00 0.00
August 0.110676E+12 0.00 0.104052E+13 0.00 0.214316E+12 0.00 0.00 0.00 0.439043E+10 0.00 0.00 0.00
September 0.107106E+12 0.00 0.223499E+11 0.00 0.728209E+10 0.00 0.00 0.00 0.105034E+11 0.00 0.00 0.00
October 0.110676E+12 0.00 0.135100E+11 0.00 0.496625E+10 0.00 0.00 0.00 0.104880E+12 0.00 0.00 0.00
November 0.107106E+12 0.00 0.243824E+11 0.00 0.714028E+10 0.00 0.00 0.00 0.214037E+12 0.00 0.00 0.00
December 0.110676E+12 0.00 0.220151E+11 0.00 0.697884E+10 0.00 0.00 0.00 0.261257E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.130313E+13 0.00 0.236392E+13 0.00 0.511691E+12 0.00 0.00 0.00 0.146305E+13 0.00 0.00 0.00
Minimum of Months 0.999658E+11 0.00 0.108296E+11 0.00 0.425978E+10 0.00 0.00 0.00 0.242952E+10 0.00 0.00 0.00
Maximum of Months 0.110676E+12 0.00 0.104052E+13 0.00 0.214316E+12 0.00 0.00 0.00 0.261257E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.148130E+10 0.00 0.393213E+10 0.00 0.803230E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133795E+10 0.00 0.963887E+10 0.00 0.185230E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148130E+10 0.00 0.181673E+11 0.00 0.328320E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143352E+10 0.00 0.238621E+11 0.00 0.407007E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148130E+10 0.00 0.689225E+10 0.00 0.130650E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143352E+10 0.00 0.134464E+11 0.00 0.255962E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148130E+10 0.00 0.208134E+11 0.00 0.418324E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148130E+10 0.00 0.266174E+11 0.00 0.514032E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143352E+10 0.00 0.704204E+10 0.00 0.133541E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148130E+10 0.00 0.125680E+11 0.00 0.225965E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143352E+10 0.00 0.176676E+11 0.00 0.311737E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148130E+10 0.00 0.235566E+11 0.00 0.415544E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.174411E+11 0.00 0.184204E+12 0.00 0.340664E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133795E+10 0.00 0.393213E+10 0.00 0.803230E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148130E+10 0.00 0.266174E+11 0.00 0.514032E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.142085E+11 0.00 0.704233E+10 0.00 0.160871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128335E+11 0.00 0.616601E+11 0.00 0.121758E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142085E+11 0.00 0.154302E+12 0.00 0.281971E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137502E+11 0.00 0.216783E+12 0.00 0.372122E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.142085E+11 0.00 0.602480E+11 0.00 0.114959E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137502E+11 0.00 0.125406E+12 0.00 0.239458E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.142085E+11 0.00 0.196904E+12 0.00 0.396426E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.142085E+11 0.00 0.252254E+12 0.00 0.487980E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137502E+11 0.00 0.616034E+11 0.00 0.117674E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.142085E+11 0.00 0.106476E+12 0.00 0.193243E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137502E+11 0.00 0.147654E+12 0.00 0.263923E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.142085E+11 0.00 0.189263E+12 0.00 0.340358E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.167294E+12 0.00 0.157960E+13 0.00 0.294596E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128335E+11 0.00 0.704233E+10 0.00 0.160871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142085E+11 0.00 0.252254E+12 0.00 0.487980E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.144520E+10 0.00 0.125434E+09 0.00 29286744.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130534E+10 0.00 0.411803E+10 0.00 0.829128E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144520E+10 0.00 0.135018E+11 0.00 0.249476E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139858E+10 0.00 0.204490E+11 0.00 0.353692E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144520E+10 0.00 0.551494E+10 0.00 0.105952E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139858E+10 0.00 0.124638E+11 0.00 0.238740E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144520E+10 0.00 0.197697E+11 0.00 0.398842E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144520E+10 0.00 0.252156E+11 0.00 0.489143E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139858E+10 0.00 0.571983E+10 0.00 0.110109E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144520E+10 0.00 0.903781E+10 0.00 0.165812E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139858E+10 0.00 0.126122E+11 0.00 0.228568E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144520E+10 0.00 0.165579E+11 0.00 0.301926E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.170161E+11 0.00 0.145086E+12 0.00 0.272810E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130534E+10 0.00 0.125434E+09 0.00 29286744.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144520E+10 0.00 0.252156E+11 0.00 0.489143E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 78430169.75 0.00 0.00 0.580219E+11 0.00 0.33
February 0.00 0.00 0.00 74226476.04 0.00 0.00 0.525561E+11 0.00 0.33
March 0.00 0.00 0.00 0.102729E+09 0.00 0.00 0.570500E+11 0.00 0.50
April 0.00 0.00 0.00 95269003.64 0.00 0.00 0.597944E+11 0.00 0.69
May 0.00 13259692.83 0.00 0.104486E+09 0.00 0.00 0.536788E+11 0.00 0.96
June 0.00 0.174144E+10 0.00 0.105803E+09 0.00 0.00 0.313427E+11 0.00 0.90
July 0.00 0.863782E+10 0.00 92257285.36 0.00 0.00 0.890809E+10 0.00 0.54
August 0.00 0.470358E+10 0.00 0.120117E+09 0.00 0.00 0.178584E+11 0.00 0.78
September 0.00 0.375602E+10 0.00 0.120056E+09 0.00 0.00 0.382419E+11 0.00 1.01
October 0.00 0.00 0.00 0.125315E+09 0.00 0.00 0.660353E+11 0.00 0.87
November 0.00 0.00 0.00 0.106784E+09 0.00 0.00 0.669758E+11 0.00 0.66
December 0.00 0.00 0.00 95415818.16 0.00 0.00 0.593394E+11 0.00 0.37
                   
Annual Sum or Average 0.00 0.188521E+11 0.00 0.122089E+10 0.00 0.00 0.569803E+12 0.00 0.66
Minimum of Months 0.00 0.00 0.00 74226476.04 0.00 0.00 0.890809E+10 0.00 0.33
Maximum of Months 0.00 0.863782E+10 0.00 0.125315E+09 0.00 0.00 0.669758E+11 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.758742E+10 0.00 0.00 44083416.95 0.00 0.00 0.277440E+11 0.00 0.35
February 0.393584E+10 0.00 0.00 49023829.77 0.00 0.00 0.300113E+11 0.00 0.36
March 0.189017E+10 92153.83 0.00 95245226.40 0.00 0.00 0.482237E+11 0.00 0.49
April 0.392862E+10 0.00 0.00 98705777.05 0.00 0.00 0.551615E+11 0.00 0.66
May 0.318747E+10 14497182.71 0.00 93524982.82 27493594.62 0.00 0.485866E+11 0.00 0.85
June 0.247621E+10 0.313009E+10 0.00 87802619.51 0.750878E+09 0.00 0.305994E+11 0.00 1.03
July 0.431046E+10 0.127404E+11 0.00 52741501.18 0.255167E+10 0.00 0.105368E+11 0.00 0.97
August 0.678528E+10 0.753568E+10 0.00 85874955.92 0.128815E+10 0.00 0.212510E+11 0.00 1.13
September 0.269904E+10 0.261064E+10 0.00 86729708.86 99295613.12 0.00 0.348753E+11 0.00 0.93
October 0.197759E+10 0.00 0.00 97731052.21 0.00 0.00 0.508597E+11 0.00 0.65
November 0.123925E+10 0.00 0.00 91036805.99 0.00 0.00 0.493394E+11 0.00 0.50
December 0.138559E+10 0.00 0.00 78369049.89 0.00 0.00 0.430406E+11 0.00 0.39
                   
Annual Sum or Average 0.414029E+11 0.260314E+11 0.00 0.960869E+09 0.471748E+10 0.00 0.450229E+12 0.00 0.69
Minimum of Months 0.123925E+10 0.00 0.00 44083416.95 0.00 0.00 0.105368E+11 0.00 0.35
Maximum of Months 0.758742E+10 0.127404E+11 0.00 98705777.05 0.255167E+10 0.00 0.551615E+11 0.00 1.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.205210E+12 0.00 0.00 11084419.80 0.00 0.637475E+10 0.170171E+11 0.00 0.30
February 0.192418E+12 0.00 0.00 16243174.92 0.00 0.136685E+10 0.218796E+11 0.00 0.30
March 0.124092E+12 0.00 0.00 0.296139E+09 0.00 0.00 0.190963E+12 0.00 0.37
April 0.679189E+11 0.00 0.00 0.428516E+09 0.00 0.00 0.280243E+12 0.00 0.42
May 0.292924E+11 86769996.67 0.00 0.682800E+09 0.202424E+09 0.00 0.372631E+12 0.00 0.67
June 0.164843E+11 0.190035E+11 0.00 0.640900E+09 0.268443E+10 0.00 0.228870E+12 0.00 0.76
July 0.108901E+11 0.769959E+11 0.00 0.384922E+09 0.939572E+10 0.00 0.790651E+11 0.00 0.63
August 0.122810E+11 0.419302E+11 0.00 0.653829E+09 0.498944E+10 0.00 0.160669E+12 0.00 0.72
September 0.308837E+11 0.172516E+11 0.00 0.613932E+09 0.268259E+09 0.00 0.254360E+12 0.00 0.72
October 0.556061E+11 0.00 0.00 0.479066E+09 0.00 0.00 0.293651E+12 0.00 0.44
November 0.100083E+12 0.00 0.00 0.282469E+09 94084995.08 0.00 0.198040E+12 0.00 0.35
December 0.196699E+12 0.00 0.00 35757651.92 0.00 0.115000E+10 0.410796E+11 0.00 0.30
                   
Annual Sum or Average 0.104186E+13 0.155268E+12 0.00 0.452566E+10 0.176344E+11 0.889160E+10 0.213847E+13 0.00 0.50
Minimum of Months 0.108901E+11 0.00 0.00 11084419.80 0.00 0.00 0.170171E+11 0.00 0.30
Maximum of Months 0.205210E+12 0.769959E+11 0.00 0.682800E+09 0.939572E+10 0.637475E+10 0.372631E+12 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.148555E+11 0.00 0.00 0.00 0.00 0.302898E+10 0.00 0.00 0.28
February 0.146954E+11 0.00 0.00 0.00 0.00 0.251308E+10 0.00 0.00 0.29
March 0.167631E+11 0.00 0.00 10427220.26 0.00 0.679683E+09 0.715661E+10 0.00 0.35
April 0.129151E+11 0.00 0.00 19495396.01 0.00 91122392.60 0.162254E+11 0.00 0.39
May 0.700110E+10 10821838.01 0.00 48573152.73 8992573.37 0.00 0.300057E+11 0.00 0.63
June 0.230468E+10 0.206382E+10 0.00 57679330.39 0.335032E+09 0.00 0.219496E+11 0.00 0.80
July 0.136597E+10 0.845179E+10 0.00 35872714.66 0.111113E+10 0.00 0.761486E+10 0.00 0.68
August 0.138502E+10 0.488228E+10 0.00 60175308.02 0.597269E+09 0.00 0.146991E+11 0.00 0.74
September 0.545982E+10 0.161952E+10 0.00 43703636.81 31859975.90 0.00 0.193869E+11 0.00 0.67
October 0.125580E+11 0.00 0.00 19295031.95 0.00 0.163371E+09 0.145704E+11 0.00 0.39
November 0.169907E+11 0.00 0.00 3187016.29 25403272.13 0.379902E+09 0.352407E+10 0.00 0.31
December 0.156294E+11 0.00 0.00 0.00 0.00 0.222933E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.121924E+12 0.170282E+11 0.00 0.298409E+09 0.210969E+10 0.908547E+10 0.135133E+12 0.00 0.48
Minimum of Months 0.136597E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.169907E+11 0.845179E+10 0.00 60175308.02 0.111113E+10 0.302898E+10 0.300057E+11 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.262588E+10 0.00 0.00 0.00 0.00 0.761618E+09 0.00 0.00 0.27
February 0.258792E+10 0.00 0.00 0.00 0.00 0.475024E+09 0.00 0.00 0.26
March 0.252503E+10 14326.83 0.00 2675270.92 0.00 93737383.09 0.156107E+10 0.00 0.36
April 0.171352E+10 0.00 0.00 5460268.49 0.00 0.00 0.377058E+10 0.00 0.52
May 0.983301E+09 573765.97 0.00 9146712.53 4275208.38 0.00 0.505148E+10 0.00 0.84
June 0.385039E+09 0.582396E+09 0.00 11656846.76 81813122.01 0.00 0.415366E+10 0.00 1.26
July 0.568563E+09 0.220664E+10 0.00 7671838.35 0.306529E+09 0.00 0.150917E+10 0.00 1.20
August 0.913841E+09 0.125091E+10 0.00 11571348.57 0.160423E+09 0.00 0.266564E+10 0.00 1.30
September 0.798697E+09 0.388820E+09 0.00 7645606.26 12554762.14 0.00 0.325262E+10 0.00 0.91
October 0.167011E+10 0.00 0.00 4676356.69 0.00 0.00 0.299838E+10 0.00 0.48
November 0.229805E+10 0.00 0.00 1886243.10 0.00 0.00 0.139472E+10 0.00 0.31
December 0.305705E+10 0.00 0.00 82767.93 0.00 0.234843E+09 0.109134E+09 0.00 0.25
                   
Annual Sum or Average 0.201270E+11 0.442935E+10 0.00 62473259.60 0.565596E+09 0.156522E+10 0.264665E+11 0.00 0.67
Minimum of Months 0.385039E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.305705E+10 0.220664E+10 0.00 11656846.76 0.306529E+09 0.761618E+09 0.505148E+10 0.00 1.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.164961E+10 0.00 0.00 55749.16 0.00 0.496643E+09 32699750.35 0.00 0.27
February 0.149345E+10 0.00 0.00 576700.79 0.00 0.331182E+09 0.271308E+09 0.00 0.28
March 0.138004E+10 10372.49 0.00 4301827.99 0.00 42141828.63 0.199980E+10 0.00 0.44
April 0.100279E+10 0.00 0.00 7582010.70 0.00 0.00 0.428227E+10 0.00 0.76
May 0.518073E+09 1610669.74 0.00 11618851.04 1769536.61 0.00 0.599168E+10 0.00 1.36
June 0.218860E+09 0.514586E+09 0.00 11850516.80 38406464.60 0.00 0.458250E+10 0.00 1.79
July 0.348866E+09 0.173713E+10 0.00 10133867.69 0.195630E+09 0.00 0.190385E+10 0.00 1.68
August 0.601753E+09 0.847485E+09 0.00 11123763.13 0.102707E+09 0.00 0.264411E+10 0.00 1.69
September 0.422010E+09 0.297886E+09 0.00 9998692.72 8119236.99 0.00 0.387370E+10 0.00 1.37
October 0.959999E+09 0.00 0.00 5566617.15 0.00 0.00 0.293208E+10 0.00 0.63
November 0.159693E+10 0.00 0.00 1581307.75 0.00 0.00 0.940653E+09 0.00 0.32
December 0.181775E+10 0.00 0.00 93326.65 0.00 0.323401E+09 57363735.51 0.00 0.25
                   
Annual Sum or Average 0.120101E+11 0.339871E+10 0.00 74483231.58 0.346632E+09 0.119337E+10 0.295120E+11 0.00 0.91
Minimum of Months 0.218860E+09 0.00 0.00 55749.16 0.00 0.00 32699750.35 0.00 0.25
Maximum of Months 0.181775E+10 0.173713E+10 0.00 11850516.80 0.195630E+09 0.496643E+09 0.599168E+10 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209003E+10 0.00 0.00 2724267.02 0.00 0.778248E+09 0.155198E+10 0.00 0.34
February 0.179569E+10 0.00 0.00 3517616.57 0.00 0.587400E+09 0.205946E+10 0.00 0.36
March 0.173650E+10 39317.83 0.00 10981222.48 0.00 0.122117E+09 0.541545E+10 0.00 0.57
April 0.156697E+10 0.00 0.00 11289681.20 0.00 5233554.02 0.701274E+10 0.00 0.85
May 0.993362E+09 4436323.71 0.00 13567631.45 2818771.04 0.00 0.704572E+10 0.00 1.18
June 0.467190E+09 0.648335E+09 0.00 13244794.91 74821533.35 0.00 0.461236E+10 0.00 1.45
July 0.558550E+09 0.241928E+10 0.00 9766442.10 0.296898E+09 0.00 0.159120E+10 0.00 1.34
August 0.905119E+09 0.144354E+10 0.00 16591881.80 0.151998E+09 0.00 0.324439E+10 0.00 1.60
September 0.624124E+09 0.536893E+09 0.00 19865337.74 12300014.38 0.00 0.628785E+10 0.00 1.58
October 0.129782E+10 0.00 0.00 13910271.22 0.00 1242763.23 0.688882E+10 0.00 0.92
November 0.210027E+10 0.00 0.00 6323034.86 0.00 15394147.46 0.338422E+10 0.00 0.45
December 0.254832E+10 0.00 0.00 2639165.15 0.00 0.347267E+09 0.136838E+10 0.00 0.30
                   
Annual Sum or Average 0.166839E+11 0.505252E+10 0.00 0.124421E+09 0.538835E+09 0.185690E+10 0.504626E+11 0.00 0.91
Minimum of Months 0.467190E+09 0.00 0.00 2639165.15 0.00 0.00 0.136838E+10 0.00 0.30
Maximum of Months 0.254832E+10 0.241928E+10 0.00 19865337.74 0.296898E+09 0.778248E+09 0.704572E+10 0.00 1.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.181338E+10 0.00 0.00 376080.07 0.00 0.112090E+09 0.336232E+09 0.00 0.28
February 0.126180E+10 0.00 0.00 1847379.03 0.00 30920001.00 0.123618E+10 0.00 0.33
March 0.412585E+09 16607.38 0.00 10639667.77 0.00 0.00 0.566894E+10 0.00 0.75
April 0.140835E+09 0.00 0.00 17474438.20 0.00 0.00 0.960960E+10 0.00 1.46
May 0.203436E+09 4399781.80 0.00 16419540.07 1318076.77 0.00 0.757300E+10 0.00 1.74
June 0.113275E+09 0.670693E+09 0.00 19711928.91 24163171.08 0.00 0.559893E+10 0.00 2.45
July 0.144646E+09 0.260034E+10 0.00 14609131.79 36493063.99 0.00 0.211791E+10 0.00 2.11
August 0.203280E+09 0.161048E+10 0.00 21053357.80 8242881.81 0.00 0.424109E+10 0.00 2.53
September 0.183521E+09 0.379812E+09 0.00 14421207.12 3481510.39 0.00 0.467256E+10 0.00 1.69
October 0.261813E+09 0.00 0.00 10235004.48 0.00 0.00 0.562727E+10 0.00 1.00
November 0.266985E+09 0.00 0.00 7351677.54 0.00 0.00 0.436566E+10 0.00 0.59
December 0.746357E+09 0.00 0.00 4009000.14 0.00 0.00 0.259782E+10 0.00 0.36
                   
Annual Sum or Average 0.575192E+10 0.526574E+10 0.00 0.138148E+09 73698704.05 0.143010E+09 0.536452E+11 0.00 1.28
Minimum of Months 0.113275E+09 0.00 0.00 376080.07 0.00 0.00 0.336232E+09 0.00 0.28
Maximum of Months 0.181338E+10 0.260034E+10 0.00 21053357.80 36493063.99 0.112090E+09 0.960960E+10 0.00 2.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.393006E+10 0.00 0.00 0.00 0.00 0.274135E+11 0.00 0.00 0.31
February 0.657236E+10 0.00 0.00 0.00 0.00 0.230500E+11 0.00 0.00 0.32
March 0.212237E+11 0.00 0.00 8136096.03 0.00 0.111386E+11 0.336366E+10 0.00 0.33
April 0.254369E+11 0.00 0.00 10936757.19 0.00 0.152275E+10 0.789282E+10 0.00 0.34
May 0.143838E+11 4249013.01 0.00 57707461.47 27734328.67 0.00 0.310504E+11 0.00 0.65
June 0.453727E+10 0.399563E+10 0.00 83645611.72 0.329984E+09 0.00 0.291648E+11 0.00 0.97
July 0.184307E+10 0.151390E+11 0.00 56463899.61 0.117489E+10 0.00 0.111405E+11 0.00 0.85
August 0.432187E+10 0.776492E+10 0.00 81058219.98 0.617097E+09 0.00 0.176629E+11 0.00 0.87
September 0.128989E+11 0.262389E+10 0.00 45576300.47 37456800.56 0.00 0.176797E+11 0.00 0.69
October 0.258664E+11 0.00 0.00 11046578.57 0.00 0.114175E+10 0.730992E+10 0.00 0.36
November 0.256493E+11 0.00 0.00 36707.18 11808553.42 0.602321E+10 0.188577E+09 0.00 0.30
December 0.641101E+10 0.00 0.00 0.00 0.00 0.253714E+11 0.00 0.00 0.31
                   
Annual Sum or Average 0.153075E+12 0.295277E+11 0.00 0.354608E+09 0.219898E+10 0.956613E+11 0.125453E+12 0.00 0.53
Minimum of Months 0.184307E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.258664E+11 0.151390E+11 0.00 83645611.72 0.117489E+10 0.274135E+11 0.310504E+11 0.00 0.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.360110E+10 0.00 0.00 0.00 0.00 0.136257E+11 0.00 0.00 0.26
February 0.458289E+10 0.00 0.00 771519.75 0.00 0.113657E+11 0.312750E+09 0.00 0.26
March 0.109875E+11 0.00 0.00 21204392.00 0.00 0.378712E+10 0.870137E+10 0.00 0.36
April 0.946203E+10 0.00 0.00 52694297.25 0.00 0.523100E+09 0.276161E+11 0.00 0.57
May 0.582115E+10 4207769.95 0.00 0.101907E+09 16842738.71 0.00 0.502152E+11 0.00 1.20
June 0.197119E+10 0.391172E+10 0.00 0.109844E+09 83229360.40 0.00 0.417052E+11 0.00 1.61
July 0.872326E+09 0.133690E+11 0.00 0.100316E+09 0.660025E+09 0.00 0.188014E+11 0.00 1.45
August 0.187725E+10 0.603147E+10 0.00 0.107914E+09 0.384598E+09 0.00 0.245663E+11 0.00 1.42
September 0.532125E+10 0.218290E+10 0.00 84252908.63 21653549.40 0.00 0.309570E+11 0.00 1.17
October 0.100513E+11 0.00 0.00 30423440.65 0.00 0.600817E+09 0.158490E+11 0.00 0.45
November 0.120624E+11 0.00 0.00 3537893.99 7622017.46 0.336127E+10 0.206197E+10 0.00 0.25
December 0.368045E+10 0.00 0.00 0.00 0.00 0.136688E+11 0.00 0.00 0.25
                   
Annual Sum or Average 0.702908E+11 0.254993E+11 0.00 0.612865E+09 0.117397E+10 0.469324E+11 0.220786E+12 0.00 0.77
Minimum of Months 0.872326E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.120624E+11 0.133690E+11 0.00 0.109844E+09 0.660025E+09 0.136688E+11 0.502152E+11 0.00 1.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.107897E+11 0.00 0.00 19693763.69 0.00 0.164870E+11 0.948697E+10 0.00 0.37
February 0.114224E+11 0.00 0.00 25410043.20 0.00 0.135038E+11 0.134319E+11 0.00 0.41
March 0.176335E+11 0.00 0.00 91087646.26 0.00 0.376464E+10 0.440678E+11 0.00 0.60
April 0.165672E+11 0.00 0.00 86296279.18 0.00 0.112741E+10 0.464450E+11 0.00 0.66
May 0.118130E+11 46983066.32 0.00 0.118171E+09 11873948.57 0.00 0.593354E+11 0.00 1.06
June 0.531144E+10 0.462498E+10 0.00 0.111483E+09 0.282440E+09 0.00 0.374420E+11 0.00 1.23
July 0.225356E+10 0.180855E+11 0.00 82323713.60 0.104867E+10 0.00 0.127829E+11 0.00 1.04
August 0.370095E+10 0.993838E+10 0.00 0.143507E+09 0.573959E+09 0.00 0.263264E+11 0.00 1.26
September 0.824525E+10 0.427343E+10 0.00 0.193097E+09 33487756.10 0.00 0.548184E+11 0.00 1.47
October 0.135585E+11 0.00 0.00 0.125565E+09 0.00 0.540158E+09 0.557480E+11 0.00 0.80
November 0.200539E+11 4091296.84 0.00 46373679.00 8978655.14 0.384327E+10 0.253748E+11 0.00 0.45
December 0.124928E+11 0.00 0.00 14102488.62 0.00 0.166843E+11 0.624603E+10 0.00 0.34
                   
Annual Sum or Average 0.133842E+12 0.369734E+11 0.00 0.105711E+10 0.195941E+10 0.559505E+11 0.391506E+12 0.00 0.81
Minimum of Months 0.225356E+10 0.00 0.00 14102488.62 0.00 0.00 0.624603E+10 0.00 0.34
Maximum of Months 0.200539E+11 0.180855E+11 0.00 0.193097E+09 0.104867E+10 0.166843E+11 0.593354E+11 0.00 1.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.517665E+10 0.00 0.00 102773.29 0.00 0.145496E+11 77496846.06 0.00 0.31
February 0.708767E+10 0.00 0.00 1900195.70 0.00 0.110208E+11 0.118191E+10 0.00 0.32
March 0.136071E+11 0.00 0.00 23965122.48 0.00 0.305314E+10 0.131082E+11 0.00 0.42
April 0.108782E+11 0.00 0.00 55626435.04 0.00 0.247800E+09 0.288559E+11 0.00 0.63
May 0.545824E+10 13567429.24 0.00 0.114986E+09 12981165.47 0.00 0.510456E+11 0.00 1.32
June 0.213525E+10 0.431705E+10 0.00 0.132005E+09 0.136177E+09 0.00 0.370658E+11 0.00 1.79
July 0.780625E+09 0.154229E+11 0.00 93741702.60 0.306017E+09 0.00 0.114305E+11 0.00 1.38
August 0.117787E+10 0.770801E+10 0.00 0.112428E+09 0.157722E+09 0.00 0.200389E+11 0.00 1.44
September 0.532496E+10 0.242204E+10 0.00 93852315.93 8541259.08 0.00 0.272221E+11 0.00 1.20
October 0.120186E+11 0.00 0.00 30497867.02 0.00 0.367834E+09 0.164550E+11 0.00 0.50
November 0.160744E+11 0.00 0.00 5092377.30 7585013.12 0.253701E+10 0.321991E+10 0.00 0.31
December 0.767575E+10 0.00 0.00 158906.82 0.00 0.123386E+11 0.116919E+09 0.00 0.30
                   
Annual Sum or Average 0.873954E+11 0.298835E+11 0.00 0.664356E+09 0.629024E+09 0.441148E+11 0.209818E+12 0.00 0.83
Minimum of Months 0.780625E+09 0.00 0.00 102773.29 0.00 0.00 77496846.06 0.00 0.30
Maximum of Months 0.160744E+11 0.154229E+11 0.00 0.132005E+09 0.306017E+09 0.145496E+11 0.510456E+11 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 66080084.54 0.00 0.00 0.00 0.00 0.271579E+10 0.00 0.00 0.34
February 0.225723E+09 0.00 0.00 0.00 0.00 0.239067E+10 0.00 0.00 0.34
March 0.142363E+10 0.00 0.00 642590.72 0.00 0.149832E+10 0.242699E+09 0.00 0.36
April 0.236130E+10 0.00 0.00 668318.81 0.00 0.465352E+09 0.522631E+09 0.00 0.36
May 0.164120E+10 81417.29 0.00 4701705.70 1976295.94 26276608.99 0.268798E+10 0.00 0.62
June 0.501929E+09 0.438570E+09 0.00 8300942.21 30726427.58 0.00 0.289832E+10 0.00 1.01
July 0.218446E+09 0.164543E+10 0.00 5828381.89 0.129166E+09 0.00 0.111545E+10 0.00 0.91
August 0.479957E+09 0.887643E+09 0.00 8139359.45 75654557.95 0.00 0.169568E+10 0.00 0.91
September 0.132037E+10 0.236357E+09 0.00 3894607.89 11299242.17 25874480.50 0.151034E+10 0.00 0.67
October 0.222627E+10 0.00 0.00 607235.90 0.00 0.453780E+09 0.432400E+09 0.00 0.36
November 0.128195E+10 0.00 3075034.19 0.00 257511.20 0.139276E+10 0.00 44125.22 0.31
December 0.171531E+09 0.00 0.00 0.00 0.00 0.252155E+10 0.00 0.00 0.34
                   
Annual Sum or Average 0.119184E+11 0.320809E+10 3075034.19 32783142.56 0.249080E+09 0.114904E+11 0.111055E+11 44125.22 0.54
Minimum of Months 66080084.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.236130E+10 0.164543E+10 3075034.19 8300942.21 0.129166E+09 0.271579E+10 0.289832E+10 44125.22 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 93404110.71 0.00 0.00 0.00 0.00 0.163729E+10 0.00 0.00 0.33
February 0.369835E+09 0.00 0.00 19108.91 0.00 0.124961E+10 7710801.01 0.00 0.33
March 0.104623E+10 0.00 0.00 1431091.32 0.00 0.579281E+09 0.573649E+09 0.00 0.40
April 0.106541E+10 0.00 0.00 4175033.58 0.00 0.152396E+09 0.251477E+10 0.00 0.62
May 0.660879E+09 391969.34 0.00 9372810.13 955079.45 7386295.30 0.498274E+10 0.00 1.21
June 0.190883E+09 0.430344E+09 0.00 11340218.85 9403276.93 0.00 0.438770E+10 0.00 1.73
July 72078714.95 0.153494E+10 0.00 10881220.64 72697929.02 0.00 0.201991E+10 0.00 1.61
August 0.177516E+09 0.715306E+09 0.00 11675365.21 42799616.84 0.00 0.255503E+10 0.00 1.55
September 0.569828E+09 0.211251E+09 0.00 7719331.73 3021195.20 13511468.76 0.299588E+10 0.00 1.19
October 0.110388E+10 0.00 0.00 2058257.44 0.00 0.189941E+09 0.115634E+10 0.00 0.45
November 0.932836E+09 0.00 1933756.05 67867.35 244260.78 0.747322E+09 54352312.62 19856.87 0.31
December 0.134509E+09 0.00 0.00 0.00 0.00 0.157359E+10 0.00 0.00 0.33
                   
Annual Sum or Average 0.641729E+10 0.289223E+10 1933756.05 58740305.15 0.129121E+09 0.615033E+10 0.212481E+11 19856.87 0.84
Minimum of Months 72078714.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.110388E+10 0.153494E+10 1933756.05 11675365.21 72697929.02 0.163729E+10 0.498274E+10 19856.87 1.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.561591E+09 0.00 0.00 1196125.58 0.00 0.177956E+10 0.578015E+09 0.00 0.35
February 0.755957E+09 0.00 0.00 1852668.51 0.00 0.138984E+10 0.992526E+09 0.00 0.39
March 0.132029E+10 0.00 0.00 6958419.00 0.00 0.635616E+09 0.347670E+10 0.00 0.59
April 0.153162E+10 0.00 0.00 6901677.51 0.00 0.304762E+09 0.472546E+10 0.00 0.69
May 0.127208E+10 572280.01 0.00 11032478.37 1618455.00 26388999.08 0.581340E+10 0.00 1.02
June 0.535289E+09 0.513678E+09 0.00 11488350.54 25310612.77 0.00 0.396256E+10 0.00 1.28
July 0.261815E+09 0.201376E+10 0.00 9726170.51 0.122214E+09 0.00 0.141811E+10 0.00 1.15
August 0.406435E+09 0.115495E+10 0.00 15870610.71 59480449.01 0.00 0.273580E+10 0.00 1.34
September 0.804092E+09 0.390317E+09 0.00 18198036.45 3288907.81 15235015.50 0.551458E+10 0.00 1.45
October 0.131619E+10 0.00 0.00 9229202.06 0.00 0.223064E+09 0.497834E+10 0.00 0.81
November 0.128023E+10 0.00 500069.06 3005954.48 2675340.56 0.821307E+09 0.178209E+10 3224.74 0.42
December 0.535643E+09 0.00 0.00 740182.65 0.00 0.184826E+10 0.331507E+09 0.00 0.34
                   
Annual Sum or Average 0.105812E+11 0.407328E+10 500069.06 96199876.38 0.214588E+09 0.704403E+10 0.363091E+11 3224.74 0.82
Minimum of Months 0.261815E+09 0.00 0.00 740182.65 0.00 0.00 0.331507E+09 0.00 0.34
Maximum of Months 0.153162E+10 0.201376E+10 500069.06 18198036.45 0.122214E+09 0.184826E+10 0.581340E+10 3224.74 1.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.259984E+09 0.00 0.00 0.00 0.00 0.143673E+10 0.00 0.00 0.32
February 0.447041E+09 0.00 0.00 139780.76 0.00 0.108404E+10 95182323.83 0.00 0.33
March 0.102759E+10 0.00 0.00 1840129.09 0.00 0.466170E+09 0.104839E+10 0.00 0.44
April 0.109813E+10 0.00 0.00 4390996.49 0.00 0.135616E+09 0.284875E+10 0.00 0.67
May 0.663011E+09 650696.71 0.00 11070450.07 824816.74 161906.49 0.502863E+10 0.00 1.28
June 0.229294E+09 0.467583E+09 0.00 14395882.29 11524552.39 0.00 0.390890E+10 0.00 1.87
July 93561066.89 0.167632E+10 0.00 10588121.68 32544884.99 0.00 0.123056E+10 0.00 1.48
August 0.171753E+09 0.912674E+09 0.00 12677346.53 16491287.09 0.00 0.197737E+10 0.00 1.52
September 0.567945E+09 0.220729E+09 0.00 8933917.55 872728.65 6087443.83 0.264053E+10 0.00 1.18
October 0.117431E+10 0.00 0.00 2198904.62 0.00 0.142105E+09 0.139123E+10 0.00 0.51
November 0.106908E+10 0.00 0.00 254821.70 2062582.36 0.519569E+09 0.200444E+09 0.00 0.32
December 0.346914E+09 0.00 0.00 337.27 0.00 0.126731E+10 1610159.75 0.00 0.31
                   
Annual Sum or Average 0.714861E+10 0.327795E+10 0.00 66490688.06 64320852.22 0.505779E+10 0.203716E+11 0.00 0.86
Minimum of Months 93561066.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.117431E+10 0.167632E+10 0.00 14395882.29 32544884.99 0.143673E+10 0.502863E+10 0.00 1.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2808013.18 0.00 0.00 0.828766E+09 0.00 0.28
February 0.00 0.00 0.00 7686924.00 0.00 0.00 0.751977E+09 0.00 0.28
March 0.00 335895.87 0.00 15338860.38 0.00 0.00 0.661906E+09 0.00 0.30
April 0.00 0.00 0.00 18415579.52 0.00 0.00 0.502719E+09 0.00 0.29
May 0.00 193234.68 0.00 4348606.33 0.00 0.00 0.361176E+09 0.00 0.29
June 0.00 58097728.04 0.00 6299106.35 0.00 0.00 0.158545E+09 0.00 0.30
July 0.00 0.162907E+09 0.00 3683229.73 0.00 0.00 27184227.14 0.00 0.28
August 0.00 83871284.34 0.00 11642087.37 0.00 0.00 71625160.04 0.00 0.31
September 0.00 23263588.67 0.00 3514430.82 0.00 0.00 0.195880E+09 0.00 0.29
October 0.00 0.00 0.00 9134075.53 0.00 0.00 0.443267E+09 0.00 0.28
November 0.00 0.00 0.00 12972036.42 0.00 0.00 0.563304E+09 0.00 0.28
December 0.00 0.00 0.00 18508321.23 0.00 0.00 0.759921E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.328669E+09 0.00 0.114351E+09 0.00 0.00 0.532627E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2808013.18 0.00 0.00 27184227.14 0.00 0.28
Maximum of Months 0.00 0.162907E+09 0.00 18508321.23 0.00 0.00 0.828766E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.308158E+10 0.00 0.00 6025021.96 0.00 0.00 0.515072E+10 0.00 0.28
February 0.00 0.00 0.00 53141393.52 0.00 0.00 0.754335E+10 0.00 0.28
March 0.00 3245494.69 0.00 0.132661E+09 0.00 0.00 0.663998E+10 0.00 0.30
April 0.00 0.00 0.00 0.169200E+09 0.00 0.00 0.504043E+10 0.00 0.29
May 0.00 1771674.41 0.00 38038256.49 0.00 0.00 0.362033E+10 0.00 0.29
June 0.00 0.575773E+09 0.00 58944651.86 0.00 0.00 0.158859E+10 0.00 0.30
July 0.00 0.162397E+10 0.00 34939306.48 0.00 0.00 0.273352E+09 0.00 0.28
August 0.00 0.837183E+09 0.00 0.110771E+09 0.00 0.00 0.719861E+09 0.00 0.31
September 0.00 0.223770E+09 0.00 30456496.58 0.00 0.00 0.197262E+10 0.00 0.29
October 0.00 0.00 0.00 78879004.24 0.00 0.00 0.444421E+10 0.00 0.28
November 0.00 0.00 0.00 0.111003E+09 0.00 0.00 0.564891E+10 0.00 0.28
December 0.00 0.00 0.00 0.153415E+09 0.00 0.00 0.762913E+10 0.00 0.28
                   
Annual Sum or Average 0.308158E+10 0.326571E+10 0.00 0.977473E+09 0.00 0.00 0.502715E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 6025021.96 0.00 0.00 0.273352E+09 0.00 0.28
Maximum of Months 0.308158E+10 0.162397E+10 0.00 0.169200E+09 0.00 0.00 0.762913E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.632917E+09 0.00 0.00 153429.86 0.00 0.00 0.170231E+09 0.00 0.28
February 378466.96 0.00 0.00 4320837.99 0.00 0.00 0.754856E+09 0.00 0.28
March 0.00 317565.45 0.00 12046270.80 0.00 0.00 0.665287E+09 0.00 0.30
April 0.00 0.00 0.00 16145785.65 0.00 0.00 0.504891E+09 0.00 0.29
May 0.00 185066.67 0.00 3483850.76 0.00 0.00 0.362702E+09 0.00 0.29
June 0.00 57640000.18 0.00 5841043.28 0.00 0.00 0.159044E+09 0.00 0.30
July 0.00 0.162361E+09 0.00 3477668.31 0.00 0.00 27397075.87 0.00 0.28
August 0.00 83633103.37 0.00 11042095.35 0.00 0.00 72152057.57 0.00 0.31
September 0.00 22399879.38 0.00 2764069.55 0.00 0.00 0.198267E+09 0.00 0.29
October 0.00 0.00 0.00 6925498.75 0.00 0.00 0.445727E+09 0.00 0.28
November 0.00 0.00 0.00 9826185.63 0.00 0.00 0.566304E+09 0.00 0.28
December 0.00 0.00 0.00 14090322.75 0.00 0.00 0.764239E+09 0.00 0.28
                   
Annual Sum or Average 0.633296E+09 0.326536E+09 0.00 90117058.69 0.00 0.00 0.469110E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 153429.86 0.00 0.00 27397075.87 0.00 0.28
Maximum of Months 0.632917E+09 0.162361E+09 0.00 16145785.65 0.00 0.00 0.764239E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.654522E+09 0.00 0.00 0.474986E+12 0.00 7.17
February 0.00 0.00 0.00 0.122298E+10 0.00 0.00 0.724833E+12 0.00 11.96
March 0.00 0.00 0.00 0.173435E+10 0.00 0.00 0.100597E+13 0.00 23.03
April 0.00 0.00 0.00 0.213709E+10 0.00 0.00 0.121653E+13 0.00 35.03
May 0.00 0.00 0.00 0.548085E+09 0.00 0.00 0.424483E+12 0.00 18.46
June 0.00 0.144385E+11 0.00 0.106788E+10 0.00 0.00 0.466510E+12 0.00 38.40
July 0.00 0.948316E+11 0.00 0.130891E+10 0.00 0.00 0.230320E+12 0.00 43.69
August 0.00 0.585420E+11 0.00 0.179942E+10 0.00 0.00 0.325240E+12 0.00 45.28
September 0.00 0.686861E+09 0.00 0.562954E+09 0.00 0.00 0.340010E+12 0.00 24.38
October 0.00 0.00 0.00 0.103583E+10 0.00 0.00 0.693844E+12 0.00 23.08
November 0.00 0.00 0.00 0.147708E+10 0.00 0.00 0.101053E+13 0.00 26.04
December 0.00 0.00 0.00 0.261839E+10 0.00 0.00 0.132852E+13 0.00 23.63
                   
Annual Sum or Average 0.00 0.168499E+12 0.00 0.161675E+11 0.00 0.00 0.824177E+13 0.00 26.75
Minimum of Months 0.00 0.00 0.00 0.548085E+09 0.00 0.00 0.230320E+12 0.00 7.17
Maximum of Months 0.00 0.948316E+11 0.00 0.261839E+10 0.00 0.00 0.132852E+13 0.00 45.28



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:26:29

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.248921E+12 0.249001E+11 0.00 0.215886E+13 0.130607E+12
February 0.386076E+12 0.260544E+11 0.00 0.230449E+13 0.178144E+12
March 0.580728E+12 0.164865E+11 0.00 0.288907E+13 0.356700E+12
April 0.703406E+12 0.134666E+11 0.00 0.320607E+13 0.413902E+12
May 0.867763E+12 0.753296E+10 0.00 0.232008E+13 0.371087E+12
June 0.933917E+12 0.320908E+10 0.00 0.156735E+13 0.143324E+13
July 0.867216E+12 -332693997.1 0.00 0.365767E+12 0.295703E+13
August 0.739686E+12 0.138549E+10 0.00 0.108077E+13 0.289522E+13
September 0.559618E+12 0.432292E+10 0.00 0.188786E+13 0.790175E+12
October 0.374018E+12 0.103765E+11 0.00 0.270609E+13 0.289538E+12
November 0.200225E+12 0.144567E+11 0.00 0.288519E+13 0.270531E+12
December 0.224540E+12 0.264714E+11 0.00 0.307849E+13 0.345142E+12
           
Annual Sum or Average 0.668612E+13 0.148330E+12 0.00 0.264501E+14 0.104313E+14
Minimum of Months 0.200225E+12 -332693997.1 0.00 0.365767E+12 0.130607E+12
Maximum of Months 0.933917E+12 0.264714E+11 0.00 0.320607E+13 0.295703E+13