Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:26:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27749.93 | 599.09 | 599.09 |
Net Site Energy | 27749.93 | 599.09 | 599.09 |
Total Source Energy | 85486.38 | 1845.55 | 1845.55 |
Net Source Energy | 85486.38 | 1845.55 | 1845.55 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1151.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1396.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2461.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2360.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 346.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 477.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.94 |
Humidification | 1463.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.26 |
Heat Recovery | 36.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 459.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26598.87 | 1151.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6164.37 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1151.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1396.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2461.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 353.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2360.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 346.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 477.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.94 |
Humidification | General | 1463.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.26 |
Heat Recovery | General | 36.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 459.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1151.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1396.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2461.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 353.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2360.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 346.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 477.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.94 |
Humidification | Unassigned | 1463.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.26 |
Heat Recovery | Unassigned | 36.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 459.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 140.44 | 24.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 373.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 574.24 | 24.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 140.44 | 24.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 373.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 574.24 | 24.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26598.874 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26598.874 | 100.00 |
Total On-Site and Utility Electric Sources | 26598.874 | 100.00 |
Total Electricity End Uses | 26598.874 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 114.16 | 5.34 |
Air to Air Heat Recovery for Heating | 2021.97 | 94.66 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2136.12 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6164.37 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6164.37 | 100.00 |
Total Water End Uses | 6164.37 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 82.50 |
Time Setpoint Not Met During Occupied Cooling | 986.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5936.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-AUG-14:39 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 17-AUG-12:50 |
Heating | 0.00 | 1582955.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 519084.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233115.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 215937.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79472.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25737.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2111016.45 | 1582955.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1582955.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 519084.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 215937.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 46481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 79472.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 25737.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1247.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4422.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7794.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1118.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7477.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1098.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1513.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4633.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 116.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1456.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84238.63 | 1247.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1818.61 | 26.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 95.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1818.61 | 26.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.10 | 0.415178 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.52 | 0.344645 | 0.293000 | 1.62 | 0.919054 | 0.500000 | 0.001105 | 0.000143 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 51.80 | 0.367167 | 0.312000 | 16.16 | 0.979111 | 0.500000 | 0.001038 | 0.003813 | 16.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.14 | 0.370173 | 0.315000 | 1.62 | 0.987129 | 0.500000 | 0.001029 | 0.000809 | 2.83 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.932871 | 0.256006 | 0.218000 | 0.203366 | 0.682683 | 0.500000 | 0.001488 | 0.000136 | 0.474426 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.28 | 0.120534 | 0.102000 | 0.130240 | 0.321423 | 0.500000 | 0.003161 | 0.000093 | 0.324722 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.46 | 0.163873 | 0.139000 | 0.202577 | 0.436994 | 0.500000 | 0.002325 | 0.000152 | 0.532682 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.56 | 0.098532 | 0.084000 | 0.131206 | 0.300000 | 0.500000 | 0.003867 | 0.000072 | 0.251115 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.71 | 0.274309 | 0.233000 | 2.03 | 0.731490 | 0.500000 | 0.001389 | 0.002105 | 7.36 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.64 | 0.300906 | 0.500000 | 0.003376 | 0.001379 | 4.82 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.46 | 0.165117 | 0.140000 | 2.02 | 0.440311 | 0.500000 | 0.002307 | 0.002105 | 7.36 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.32 | 0.107485 | 0.091000 | 1.30 | 0.300000 | 0.500000 | 0.003545 | 0.001338 | 4.68 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.989574 | 0.241337 | 0.205000 | 0.202863 | 0.643565 | 0.500000 | 0.001579 | 0.000269 | 0.941333 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.38 | 0.111913 | 0.095000 | 0.130646 | 0.300000 | 0.500000 | 0.003404 | 0.000176 | 0.614218 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.56 | 0.153302 | 0.130000 | 0.202524 | 0.408805 | 0.500000 | 0.002485 | 0.000269 | 0.941341 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.51 | 0.101888 | 0.087000 | 0.131416 | 0.300000 | 0.500000 | 0.003739 | 0.000173 | 0.606169 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16322.64 | 0.000143 | 329.97 | |
CORE_MID VAV BOX REHEAT COIL | 435881.87 | 0.003813 | 10653.97 | |
CORE_TOP VAV BOX REHEAT COIL | 92520.59 | 0.000809 | 2442.26 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15519.47 | 0.000136 | 409.45 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10620.65 | 0.000093 | 280.18 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17420.63 | 0.000152 | 459.55 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8218.43 | 0.000072 | 216.87 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 240574.18 | 0.002105 | 6344.03 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 157600.80 | 0.001379 | 4155.93 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 240575.57 | 0.002105 | 6344.06 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 152919.73 | 0.001338 | 4032.57 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30748.75 | 0.000269 | 810.71 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20063.05 | 0.000176 | 528.97 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30749.00 | 0.000269 | 810.72 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19800.36 | 0.000173 | 522.05 | |
VAV_BOT WITH REHEAT HEATING COIL | 62573.55 | 0.000547 | 1012.69 | |
VAV_MID WITH REHEAT HEATING COIL | 656277.62 | 0.005741 | 10485.17 | |
VAV_TOP WITH REHEAT HEATING COIL | 64351.66 | 0.000563 | 1040.57 | |
CAV_BAS HEATING COIL | 263779.46 | 0.000875 | 2622.48 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.493751 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.74 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.481719 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.37 | 2.28 | 10.75 | 2.66 | 9.22 | 9.22 | 0.300000 | 0.288439 | 9.22 |
VAV_MID WITH REHEAT | 51.47 | 22.83 | 102.93 | 36.22 | 85.94 | 85.94 | 0.300000 | 0.421422 | 85.94 |
VAV_TOP WITH REHEAT | 5.29 | 2.29 | 10.57 | 5.93 | 9.44 | 9.44 | 0.300000 | 0.627876 | 9.44 |
CAV_BAS | 0.000000 | 0.000000 | 5.10 | 1.20 | 5.10 | 5.10 | 1.00 | 0.235267 | 5.10 |
AIRLOOP DATACENTER BASEMENT | 25.05 | 25.05 | 25.05 | 25.05 | 25.05 | 25.05 | 1.00 | 0.999993 | 25.05 |
AIRLOOP DATACENTER BOT | 0.493751 | 0.493751 | 0.493751 | 0.493751 | 0.493751 | 0.493751 | 1.00 | 1.00 | 0.493751 |
AIRLOOP DATACENTER MID | 4.74 | 4.74 | 4.74 | 4.74 | 4.74 | 4.74 | 1.00 | 1.00 | 4.74 |
AIRLOOP DATACENTER TOP | 0.481719 | 0.481719 | 0.481719 | 0.481719 | 0.481719 | 0.481719 | 1.00 | 1.00 | 0.481719 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.22 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 85.94 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.44 | |
CAV_BAS_OA_CONTROLLER | 5.10 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.05 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.493751 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.74 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.481719 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.42 | 6.67 | 10.90 | 0.009896 | 0.008500 | 199062.20 | 0.005693 | 9.22 |
VAV_MID WITH REHEAT COOLING COIL | 25.57 | 6.67 | 10.90 | 0.010054 | 0.008500 | 1910140.56 | 0.054630 | 85.94 |
VAV_TOP WITH REHEAT COOLING COIL | 25.36 | 6.67 | 10.90 | 0.009867 | 0.008500 | 202158.94 | 0.005782 | 9.44 |
CAV_BAS COOLING COIL | 25.33 | 6.67 | 10.89 | 0.010173 | 0.008500 | 113769.83 | 0.003254 | 5.10 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.22 |
VAV_MID WITH REHEAT FAN | 85.94 |
VAV_TOP WITH REHEAT FAN | 9.44 |
CAV_BAS FAN | 5.10 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005693 | 0.000084 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000547 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.054630 | 0.000009 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.005741 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005782 | 0.000082 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000563 | |
CAV_BAS_COOLC_CONTROLLER | 0.003254 | 0.000146 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.05 | 496305.63 | 349488.48 | 0.012154 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.493751 | 9679.56 | 6845.93 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.74 | 92966.77 | 65704.12 | 0.002277 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.481719 | 9453.48 | 6682.26 | 0.000232 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.05 | 25.05 | 25.05 | 25.05 | 496305.63 | 496305.63 | 22473.72 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.493751 | 0.493751 | 0.493751 | 0.493751 | 9679.56 | 9679.56 | 1038.19 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.74 | 4.74 | 4.74 | 4.74 | 92966.77 | 92966.77 | 10381.93 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.481719 | 0.481719 | 0.481719 | 0.481719 | 9453.48 | 9453.48 | 1038.19 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.05 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.493751 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.74 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.481719 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.05 | 496305.63 | 0.012154 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.493751 | 9679.56 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.74 | 92966.77 | 0.002277 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.481719 | 9453.48 | 0.000232 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 22473.72 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1038.19 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 10381.93 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1038.19 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000215 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.069358 | 11212.00 | |
HEATSYS1 PUMP | 0.020758 | 6189.43 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.069358 | 8.32 |
HEATSYS1 | 0.020758 | 2.49 |
COOLSYS1_SUPPLY | 0.069358 | 8.32 |
SINGLE WATER PLANT LOOP | 0.014900 | 1.79 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.069358 | 0.069358 | 291132.24 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2372738.58 | 2372738.58 | 0.020758 |
CENTRAL BOILER | 613744.43 | 601379.40 | 0.014900 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.034679 | 3881.22 |
COOLSYS1 CHILLER2 PUMP | 0.034679 | 3881.22 |
PLANT CIRC PUMP | 0.014900 | 3762.57 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.069358 | 0.034814 | 1217264.14 | 1217264.50 | 0.061295 |
COOLSYS1 CHILLER2 | 0.069358 | 0.034814 | 1217264.14 | 1217264.50 | 0.061295 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014900 | 147944.06 | 74893.84 | 73972.03 | 7004.20 | 44936.31 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.122591 | 14.71 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.122591 | 30050.25 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 48.18 | 1457149.06 | 9.64 | 182143.63 |
TOWERWATERSYS COOLTOWER 2 | 48.18 | 1457149.06 | 9.64 | 182143.63 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.063125 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9711E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9733E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7029E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7047E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7604E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7618E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6225E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6233E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0211E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1665E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7448E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8708E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7958E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9006E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6441E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6991E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1690 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5323E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1920 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7001E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1162 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6850E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7407E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6489E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0293E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2095E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7538E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9179E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8031E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9288E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6446E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7007E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9709E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9733E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7026E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7048E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7603E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7619E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6224E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6232E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1587E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5280E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9523E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3690E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4722E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6137E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4838E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5217E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.0030E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3903E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6810E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1426E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6647E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7667E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9359E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8463E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0464E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1548E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8060E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8851E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4282E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4598E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4839E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5223E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7816E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7838E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3613E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3631E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0808E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0822E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6225E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6233E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8311E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9573E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4023E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5035E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1147E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1901E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6447E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7008E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5023E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3766E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4554E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8016E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1047E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2079E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7407E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6484E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8288E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9561E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3991E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4981E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1090E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1723E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6441E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6992E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7815E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7836E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3612E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3629E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0807E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0818E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6224E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6232E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3693E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4822E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9508E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0323E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9114E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9403E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4840E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5224E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8213E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9167E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1982E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5470E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7098E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3837E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9359E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8463E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4561E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7262E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0647E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3543E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9525E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0786E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4837E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5217E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1697 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1177 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1874 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1324 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1291 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9209E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8052E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8715E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.3178E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8708E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9604E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5790E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.8841E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0631E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9539E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9044E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5810E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7169E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.3959E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9319E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0121E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1882E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8053E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8710E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9814E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.2179E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2823E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7563E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8143E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5550E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9539E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9044E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1698 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1179 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1875 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1327 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1293 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9380E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8177E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8779E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.3238E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8784E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9673E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5864E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.8962E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0718E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9663E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9108E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5814E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7212E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.3966E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9353E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0185E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1922E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8177E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8774E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9853E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.2240E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2867E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7618E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8247E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5624E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9663E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9108E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69097.62976 | 69097.62976 | 5.10124 | 5.10124 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -16.30000 | 9.24091E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 74750.56502 | 74750.56502 | 5.51884 | 5.51884 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 650.01306 | 650.01306 | 2.84929E-002 | 1.07782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 701857.15696 | 701857.15696 | 51.80328 | 51.80328 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 277230.59499 | 277230.59499 | 11.98959 | 11.98959 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 69614.59560 | 69614.59560 | 5.13825 | 5.13825 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 64789.87944 | 64789.87944 | 2.82507 | 2.82507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12516.96403 | 12516.96403 | 0.93287 | 0.93287 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 10866.31956 | 10866.31956 | 0.47443 | 0.47443 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17132.72015 | 17132.72015 | 1.27686 | 1.27686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7435.56298 | 7435.56298 | 0.32472 | 0.32472 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19554.84933 | 19554.84933 | 1.45739 | 1.45739 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 12195.09531 | 12195.09531 | 0.53268 | 0.53268 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20958.40542 | 20958.40542 | 1.56198 | 1.56198 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5756.53853 | 5756.53853 | 0.25111 | 0.25111 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 116814.33586 | 116814.33586 | 8.70627 | 8.70627 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 168369.76461 | 168369.76461 | 7.36198 | 7.36198 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 183003.57686 | 183003.57686 | 13.63924 | 13.63924 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 110298.54650 | 110298.54650 | 4.82301 | 4.82301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 194069.55630 | 194069.55630 | 14.46407 | 14.46407 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 168370.73932 | 168370.73932 | 7.36202 | 7.36202 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 192121.66183 | 192121.66183 | 14.31879 | 14.31879 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 28.68800 | 1.33641E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 107025.75927 | 107025.75927 | 4.67955 | 4.67955 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13277.23835 | 13277.23835 | 0.98957 | 0.98957 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 21516.33885 | 21516.33885 | 0.94133 | 0.94133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18451.72576 | 18451.72576 | 1.37522 | 1.37522 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 14039.03313 | 14039.03313 | 0.61422 | 0.61422 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20902.39472 | 20902.39472 | 1.55788 | 1.55788 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 21516.51500 | 21516.51500 | 0.94134 | 0.94134 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20267.17296 | 20267.17296 | 1.51053 | 1.51053 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13855.33634 | 13855.33634 | 0.60617 | 0.60617 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8399.66474 | 8399.66474 | 0.49375 | 0.49375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80568.54399 | 80568.54399 | 4.73603 | 4.73603 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8194.94764 | 8194.94764 | 0.48172 | 0.48172 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370641.09221 | 426237.25605 | 21.78679 | 25.05481 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | -16.30000 | 9.24091E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 133662.48 | 9.22472 | 9.22472 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 69389.34 | 2.66077 | 2.66077 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1227114.22 | 85.93799 | 85.93799 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 691593.28 | 36.21616 | 36.21616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 139618.04 | 9.44156 | 9.44156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 69653.24 | 5.92813 | 5.92813 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 |
7 | CAV_BAS | Cooling | Sensible | 68034.02 | 5.10124 | 5.10124 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 79706.12 | 1.20016 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 420492.69 | 25.05499 | 25.05499 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 22473.72 | 0.33839 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8260.63 | 0.49375 | 0.49375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79231.25 | 4.73603 | 4.73603 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 10381.93 | 0.15632 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8061.14 | 0.48172 | 0.48172 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.10124 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.41518 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.51884 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34465 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61702 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91905 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10548E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42798E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61702 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16322.63891 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42798E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 329.96972 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 51.80328 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36717 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.16262 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97911 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03768E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.81328E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.16262 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 435881.86667 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.81328E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10653.97046 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.13825 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37017 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61855 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98713 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02925E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.09411E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.82507 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 92520.59416 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.09411E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2442.25876 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93287 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25601 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21800 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20337 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68268 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48825E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35771E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47443 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15519.47099 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35771E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 409.44989 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27686 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12053 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13024 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32142 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16094E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.29141E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32472 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10620.65236 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.29141E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 280.18396 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45739 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16387 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13900 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20258 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43699 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32498E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52403E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53268 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17420.63104 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52403E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 459.55379 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56198 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.85322E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.40000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13121 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.86676E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.18984E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25111 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8218.43356 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18984E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.87438 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.70627 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27431 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02856 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73149 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38895E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.10465E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.36198 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 240574.18268 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10465E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6344.02806 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.63924 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30091 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37647E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37876E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.82301 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 157600.80434 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37876E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4155.92787 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.46407 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16512 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02497 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44031 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30746E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.10466E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.36202 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 240575.57254 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10466E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6344.06480 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.31879 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10748 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.10000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30301 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54469E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33781E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.67955 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 152919.73155 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33781E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4032.57147 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98957 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24134 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20286 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64356 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57871E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.69003E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94133 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30748.75162 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69003E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 810.71042 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37522 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11191 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.50000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13065 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40443E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75520E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61422 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20063.05254 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75520E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 528.96993 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.55788 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15330 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20252 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40881 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48529E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.69006E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94134 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30749.00317 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69006E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 810.71706 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51053 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10189 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.70000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13142 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.73939E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73222E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60617 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19800.35822 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73222E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 522.04643 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49375 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.73603 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48172 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.05481 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.37397 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28441 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.74794 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.66077 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.22472 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.22472 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28844 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 51.46583 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.82853 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 102.93166 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 36.21616 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 85.93799 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 85.93799 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42142 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.28573 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28600 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.57145 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.92813 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.44156 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.44156 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.62788 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.10124 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.10124 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.10124 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.23527 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.05481 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.05481 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.05481 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.05481 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.05499 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.05499 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49375 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49375 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49375 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49375 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49375 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49375 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.73603 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.73603 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.73603 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.73603 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.73603 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.73603 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48172 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48172 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48172 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48172 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48172 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48172 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.22472 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 85.93799 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.44156 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.10124 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.05499 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49375 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.73603 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48172 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.22472 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.42420 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89880 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.89584E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 199062.20462 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.69315E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.22472 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 62573.55168 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.47421E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1012.68661 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.22472 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.69315E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.36427E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.47421E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 85.93799 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.56919 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89935 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00544E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1910140.55615 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.46298E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 85.93799 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 656277.62167 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.74140E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 10485.17148 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 85.93799 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.46298E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.71668E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.74140E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.44156 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.35583 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89870 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.86722E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 202158.94469 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.78172E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.44156 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 64351.66423 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.62976E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1040.56866 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.44156 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.78172E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.23614E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.62976E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.10124 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.32601 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.88749 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01725E-002 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 113769.82997 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25380E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.10124 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 263779.46432 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.47617 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.10124 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.25380E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.46349E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.05499 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.05499 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 496305.62674 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 349488.48470 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.21545E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.05499 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.05499 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.05499 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.05499 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 496305.62674 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 496305.62674 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 22473.71574 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.05499 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.05499 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 496305.62674 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.21545E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 22473.71574 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.14634E-004 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49375 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49375 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9679.55954 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6845.92923 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37052E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49375 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49375 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49375 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49375 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9679.55954 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9679.55954 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49375 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49375 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9679.55954 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37052E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.73603 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.73603 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92966.76501 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65704.12427 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27675E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.73603 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.73603 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.73603 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.73603 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92966.76501 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92966.76501 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 10381.92564 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.73603 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.73603 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92966.76501 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27675E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10381.92564 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48172 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48172 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9453.47957 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6682.25988 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31515E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48172 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48172 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48172 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48172 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9453.47957 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9453.47957 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48172 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48172 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9453.47957 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31515E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.93585E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11211.99636 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.93585E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 8.32301 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.93585E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.93585E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 291132.23715 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.07578E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.49093 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.07578E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6189.42910 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2372738.58194 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2372738.58000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.07578E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.93585E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 8.32301 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.46792E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3881.22160 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.46792E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3881.22160 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.93585E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.48136E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1217264.14161 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1217264.50000 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.12954E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.93585E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.48136E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1217264.14161 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1217264.50000 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.12954E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.48998E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.78798 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.48998E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3762.57090 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.48998E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 147944.05834 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74893.84215 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73972.02917 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44936.30529 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 613744.42876 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 601379.40000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.48998E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12259 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 14.71089 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12259 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 30050.24609 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 48.18412 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1457149.05790 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.63682 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 182143.63224 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 48.18412 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1457149.05790 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.63682 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 182143.63224 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.31250E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.31250E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15477.13 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 412907.44 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 87675.88 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14705.37 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10063.39 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16506.43 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7787.64 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 227934.01 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 149319.78 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 227935.33 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 144885.23 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29132.18 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19008.23 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 29132.42 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18759.37 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 46500.35 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 474696.98 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 47759.63 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94838.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 232422.57 | 161697.30 | 70725.27 | 0.70 | 38298.26 | 388.44 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2193609.17 | 1518015.41 | 675593.75 | 0.69 | 358032.42 | 3631.36 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 237043.03 | 165152.37 | 71890.66 | 0.70 | 39153.74 | 397.12 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 130640.07 | 90298.50 | 40341.57 | 0.69 | 21428.90 | 217.34 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.3309557413E-004 | 1.4002821530E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.3421652633E-003 | 6.1646518187E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.0347383169E-002 | 2.0139620593E-002 | Pass | Pass | 0.4760147335 | 0.4985147116 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.6865056071E-002 | 4.3739137357E-002 | Pass | Pass | 20.6447018177 | 45.2299290004 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8452195248E-002 | 1.4746916914E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.8523373232E-002 | 1.4900365385E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.1889622254E-002 | 1.9382252454E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9672182096E-002 | 1.7103640621E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2635174686 | 0.2412891909 | Pass | Pass | 44.0818078388 | 142.3510552346 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2668379332 | 0.2457714128 | Pass | Pass | 41.9237074927 | 120.8053055367 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2197217372 | 0.2232258666 | Pass | Pass | 70.1073928465 | 279.9490152212 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1401674464 | 0.1563738381 | Pass | Pass | 31.3976744999 | 110.2527493729 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3759688175 | 0.3709960603 | Pass | Pass | 43.8449090064 | 333.2043174369 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4157901287 | 0.3942323371 | Pass | Pass | 55.2489516188 | 117.6410664007 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3775698834 | 0.3706134878 | Pass | Pass | 59.3641148078 | 134.3406768825 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3025320284 | 0.3041293671 | Pass | Pass | 67.5297700242 | 178.9443607093 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5575408816E-003 | 2.8845534172E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.3664834305E-002 | 2.0603230235E-002 | Pass | Pass | 0.4759256929 | 0.4603030221 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.4939161614E-002 | 6.3839081521E-002 | Pass | Pass | 0.4884524063 | 0.4774228163 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.0368703829E-006 | 5.9629272726E-006 | Pass | Pass | 3.7147755125E-003 | 2.7836682153E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.0970869694E-003 | 4.0621355925E-003 | Pass | Pass | 1.8125392384E-003 | 1.6084828021E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.7348785432E-003 | 6.5139429519E-003 | Pass | Pass | 2.9255012466E-003 | 2.6382677120E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.1666297644E-006 | 2.5753070052E-006 | Pass | Pass | 4.2306560814E-005 | 1.0851766858E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6686.12 | 148.33 | 0.00 | 26450.13 | 10431.32 | 43715.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.48 | 0.0000 | Y | 10.67 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.34 | 0.0000 | Y | 6.84 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 10.55 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 6.83 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.43 | 0.0000 | Y | 106.52 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.31 | 0.0000 | Y | 68.33 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.16 | 0.0000 | Y | 105.46 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.26 | 0.0000 | Y | 68.21 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.43 | 0.0000 | Y | 10.65 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.31 | 0.0000 | Y | 6.83 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.16 | 0.0000 | Y | 10.55 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.26 | 0.0000 | Y | 6.82 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 775.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.04 | 42.04 | 104.74 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.67 | 62.85 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.67 | 47.45 | 236.87 | |
Exterior Lighting Total | 40855.88 | 353.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2417661.91 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2372738.58 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1217264.50 | 5.91 | 1210235.40 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1217264.50 | 5.91 | 1210235.40 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 616556.86 | |||||
CENTRAL BOILER | Boiler:HotWater | 601379.40 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1457149.06 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1457149.06 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 199062.20 | 232422.57 | 161697.30 | 70725.27 | 0.70 | - | 38298.26 | 388.44 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1910140.56 | 2193609.17 | 1518015.41 | 675593.75 | 0.69 | - | 358032.42 | 3631.36 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 202158.94 | 237043.03 | 165152.37 | 71890.66 | 0.70 | - | 39153.74 | 397.12 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 113769.83 | 130640.07 | 90298.50 | 40341.57 | 0.69 | - | 21428.90 | 217.34 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 496305.63 | 349488.48 | 146817.14 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9679.56 | 6845.93 | 2833.63 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92966.77 | 65704.12 | 27262.64 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9453.48 | 6682.26 | 2771.22 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16322.64 | 15477.13 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 435881.87 | 412907.44 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 92520.59 | 87675.88 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15519.47 | 14705.37 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10620.65 | 10063.39 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17420.63 | 16506.43 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8218.43 | 7787.64 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 240574.18 | 227934.01 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 157600.80 | 149319.78 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 240575.57 | 227935.33 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 152919.73 | 144885.23 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 30748.75 | 29132.18 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20063.05 | 19008.23 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30749.00 | 29132.42 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19800.36 | 18759.37 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 62573.55 | 46500.35 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 656277.62 | 474696.98 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 64351.66 | 47759.63 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94838.35 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 496305.63 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9679.56 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92966.77 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9453.48 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 22473.72 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 10381.93 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.22 | 21066.75 | 2283.73 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 85.94 | 196258.98 | 2283.73 | 1.00 | 1.07 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.44 | 21561.95 | 2283.73 | 1.00 | 1.11 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.10 | 11725.01 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.05 | 41321.86 | 1649.25 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 553.05 | 1120.11 | 1.00 | 1.61 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.74 | 5304.86 | 1120.11 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 539.58 | 1120.11 | 1.00 | 1.62 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.069358 | 11212.00 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.020758 | 6189.43 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.034679 | 3881.22 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.034679 | 3881.22 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014900 | 3762.57 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.122591 | 30050.25 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69097.63 | 69097.63 | 24.86 | 5.101 | 5.101 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00901 | 23.42 | 0.01335 | 1.200 | 0.00 |
CORE_BOTTOM | 74750.57 | 74750.57 | 29.95 | 5.519 | 5.519 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 23.42 | 0.01335 | 1.078 | 0.00 |
CORE_MID | 701857.16 | 701857.16 | 281.18 | 51.803 | 51.803 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 23.42 | 0.01335 | 10.778 | 0.00 |
CORE_TOP | 69614.60 | 69614.60 | 27.89 | 5.138 | 5.138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 23.42 | 0.01335 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12516.96 | 12516.96 | 39.94 | 0.933 | 0.933 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00887 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17132.72 | 17132.72 | 84.83 | 1.277 | 1.277 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00868 | 25.18 | 0.01336 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19554.85 | 19554.85 | 62.39 | 1.457 | 1.457 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00874 | 29.99 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20958.41 | 20958.41 | 103.77 | 1.562 | 1.562 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 28.84 | 0.01336 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 116814.34 | 116814.34 | 372.72 | 8.706 | 8.706 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00900 | 30.30 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 183003.58 | 183003.58 | 906.07 | 13.639 | 13.639 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00871 | 25.71 | 0.01336 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 194069.56 | 194069.56 | 619.20 | 14.464 | 14.464 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00880 | 30.07 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 192121.66 | 192121.66 | 951.21 | 14.319 | 14.319 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00870 | 28.69 | 0.01336 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13277.24 | 13277.24 | 42.36 | 0.990 | 0.990 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00897 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18451.73 | 18451.73 | 91.36 | 1.375 | 1.375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00873 | 25.98 | 0.01336 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20902.39 | 20902.39 | 66.69 | 1.558 | 1.558 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00881 | 30.14 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20267.17 | 20267.17 | 100.34 | 1.511 | 1.511 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 28.84 | 0.01336 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8399.66 | 8399.66 | 232.02 | 0.494 | 0.494 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80568.54 | 80568.54 | 2225.48 | 4.736 | 4.736 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8194.95 | 8194.95 | 226.36 | 0.482 | 0.482 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370641.09 | 426237.26 | 543.89 | 21.787 | 25.055 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.84 | 0.01335 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 23.26 | 0.00092 | -16.30 | 0.00092 | 1.200 | 0.00 |
CORE_BOTTOM | 650.01 | 650.01 | 0.26 | 0.028 | 1.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00110 | -16.30 | 0.00092 | 1.078 | 0.00 |
CORE_MID | 277230.59 | 277230.59 | 111.06 | 11.990 | 11.990 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 10.778 | 0.00 |
CORE_TOP | 64789.88 | 64789.88 | 25.96 | 2.825 | 2.825 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10866.32 | 10866.32 | 34.67 | 0.474 | 0.474 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7435.56 | 7435.56 | 36.81 | 0.325 | 0.325 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12195.10 | 12195.10 | 38.91 | 0.533 | 0.533 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5756.54 | 5756.54 | 28.50 | 0.251 | 0.251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 168369.76 | 168369.76 | 537.21 | 7.362 | 7.362 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 110298.55 | 110298.55 | 546.10 | 4.823 | 4.823 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 168370.74 | 168370.74 | 537.21 | 7.362 | 7.362 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 107025.76 | 107025.76 | 529.90 | 4.680 | 4.680 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 21516.34 | 21516.34 | 68.65 | 0.941 | 0.941 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14039.03 | 14039.03 | 69.51 | 0.614 | 0.614 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21516.52 | 21516.52 | 68.65 | 0.941 | 0.941 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13855.34 | 13855.34 | 68.60 | 0.606 | 0.606 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 25.14 | 0.00611 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.77 | 0.00154 | -16.30 | 0.00092 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.70 | 0.00148 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | 18.00 | 27.00 | 0.00850 | -16.30 | 0.00092 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.22 | 9.22 | 2.66 | 2.66 | 9.2247 | 2.6608 | 9.2247 | 0.2884 | 0.3000 |
VAV_MID WITH REHEAT | 85.94 | 85.94 | 36.22 | 36.22 | 85.9380 | 36.2162 | 85.9380 | 0.4214 | 0.3000 |
VAV_TOP WITH REHEAT | 9.44 | 9.44 | 5.93 | 5.93 | 9.4416 | 5.9281 | 9.4416 | 0.6279 | 0.3000 |
CAV_BAS | 5.10 | 5.10 | 1.20 | 1.20 | 5.1012 | 1.2002 | 5.1012 | 0.2353 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.05 | 25.05 | 0.34 | 0.34 | 25.0550 | 25.0548 | 25.0550 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4938 | 0.4938 | 0.4938 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.74 | 4.74 | 0.16 | 0.16 | 4.7360 | 4.7360 | 4.7360 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4817 | 0.4817 | 0.4817 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16322.639 | 16322.639 | 1.617021 | 0.00014280 | 329.970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16322.64 | 16322.64 | 1.617021 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00109934 | 7.0052 | 650.01 | 0.00 | 16382.73 | 16382.73 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 435881.867 | 435881.867 | 16.162624 | 0.00381328 | 10653.970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 435881.87 | 435881.87 | 16.162624 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 277230.59 | 0.00 | 437285.21 | 437285.21 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 92520.594 | 92520.594 | 2.825071 | 0.00080941 | 2442.259 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 92520.59 | 92520.59 | 2.825071 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 64789.88 | 0.00 | 92840.30 | 92840.30 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15519.471 | 15519.471 | 0.474426 | 0.00013577 | 409.450 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15519.47 | 15519.47 | 0.474426 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764327 | 48.2015 | 10866.32 | 0.00 | 15571.54 | 15571.54 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10620.652 | 10620.652 | 0.324722 | 0.00009291 | 280.184 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10620.65 | 10620.65 | 0.324722 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00767655 | 48.4086 | 7435.56 | 0.00 | 10656.14 | 10656.14 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17420.631 | 17420.631 | 0.532682 | 0.00015240 | 459.554 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17420.63 | 17420.63 | 0.532682 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773153 | 48.7505 | 12195.10 | 0.00 | 17478.69 | 17478.69 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8218.434 | 8218.434 | 0.251115 | 0.00007190 | 216.874 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8218.43 | 8218.43 | 0.251115 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00744282 | 46.9536 | 5756.54 | 0.00 | 8246.35 | 8246.35 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 240574.183 | 240574.183 | 7.361982 | 0.00210465 | 6344.028 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 240574.18 | 240574.18 | 7.361982 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765114 | 48.2514 | 168369.76 | 0.00 | 241359.53 | 241359.53 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 157600.804 | 157600.804 | 4.823012 | 0.00137876 | 4155.928 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 157600.80 | 157600.80 | 4.823012 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764635 | 48.2217 | 110298.55 | 0.00 | 158114.84 | 158114.84 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 240575.573 | 240575.573 | 7.362024 | 0.00210466 | 6344.065 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 240575.57 | 240575.57 | 7.362024 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765114 | 48.2514 | 168370.74 | 0.00 | 241360.92 | 241360.92 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 152919.732 | 152919.732 | 4.679547 | 0.00133781 | 4032.571 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 152919.73 | 152919.73 | 4.679547 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00763373 | 48.1432 | 107025.76 | 0.00 | 153419.10 | 153419.10 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 30748.752 | 30748.752 | 0.941333 | 0.00026900 | 810.710 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30748.75 | 30748.75 | 0.941333 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766911 | 48.3641 | 21516.34 | 0.00 | 30848.08 | 30848.08 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 20063.053 | 20063.053 | 0.614218 | 0.00017552 | 528.970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20063.05 | 20063.05 | 0.614218 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766239 | 48.3223 | 14039.03 | 0.00 | 20127.83 | 20127.83 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 30749.003 | 30749.003 | 0.941341 | 0.00026901 | 810.717 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30749.00 | 30749.00 | 0.941341 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766912 | 48.3641 | 21516.52 | 0.00 | 30848.33 | 30848.33 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 19800.358 | 19800.358 | 0.606169 | 0.00017322 | 522.046 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19800.36 | 19800.36 | 0.606169 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765793 | 48.2946 | 13855.34 | 0.00 | 19864.30 | 19864.30 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 199062.205 | -999.000 | 9.224722 | 0.00569315 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 199062.20 | 159856.95 | 9.224722 | 25.42 | 17.77 | 0.00989584 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.0115 | 24.00 | 0.00888100 | 46.5821 | 120431.59 | 0.00 | 202826.78 | 157128.78 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 62573.552 | 62573.552 | 2.767417 | 0.00054742 | 1012.687 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62573.55 | 62573.55 | 2.767417 | -6.37 | -7.19 | 0.00180950 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 73.3717 | 20.21 | 0.00537456 | 35.7120 | 22402.53 | 0.00 | 56234.53 | 56234.53 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1910140.556 | -999.000 | 85.937991 | 0.05462978 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1910140.56 | 1503604.16 | 85.937991 | 25.57 | 17.95 | 0.01005436 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 23.6287 | 24.00 | 0.00895453 | 46.9628 | 1093073.28 | 0.00 | 1945437.69 | 1479485.63 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 656277.622 | 656277.622 | 25.781397 | 0.00574140 | 10485.171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 656277.62 | 656277.62 | 25.781397 | -8.78 | -8.78 | 0.00232147 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 78.7622 | 18.05 | 0.00740353 | 56.0962 | 280580.38 | 0.00 | 574082.78 | 574082.78 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 202158.945 | -999.000 | 9.441561 | 0.00578172 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 202158.94 | 162851.04 | 9.441561 | 25.36 | 17.73 | 0.00986722 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 21.5060 | 24.00 | 0.00890640 | 46.7141 | 126480.16 | 0.00 | 205953.31 | 160011.31 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 64351.664 | 64351.664 | 2.832468 | 0.00056298 | 1040.569 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 64351.66 | 64351.66 | 2.832468 | -6.46 | -6.46 | 0.00279493 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 71.6866 | 15.93 | 0.00755524 | 65.4838 | 28040.12 | 0.00 | 57772.27 | 57772.27 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 113769.830 | -999.000 | 5.101242 | 0.00325380 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 113769.83 | 87793.01 | 5.101242 | 25.33 | 17.96 | 0.01017251 | 10.89 | 10.89 | 0.00850000 | 29.09 | 0.01336481 | 21.48 | 23.5267 | 24.00 | 0.00904705 | 47.4407 | 61779.91 | 0.00 | 115874.01 | 86416.59 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.116633 | -3.83 | -7.16 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 38.5081 | 23.36 | 0.00092409 | 5.1020 | 0.00 | 0.00 | 100076.34 | 100076.34 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 496305.627 | 349488.485 | 25.054988 | 0.01215449 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 460920.88 | 453838.57 | -999.0 | 28.47 | 17.75 | 0.00860762 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | -999.0000 | 27.00 | 0.00854239 | 37.5167 | 370224.32 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9679.560 | 6845.929 | 0.493751 | 0.00023705 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8972.85 | 8665.53 | -999.0 | 27.95 | 17.68 | 0.00873733 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | -999.0000 | 27.00 | 0.00858618 | 37.7040 | 8399.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92966.765 | 65704.124 | 4.736027 | 0.00227675 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 86197.53 | 83125.96 | -999.0 | 27.95 | 17.69 | 0.00874726 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | -999.0000 | 27.00 | 0.00858980 | 37.7198 | 80568.54 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9453.480 | 6682.260 | 0.481719 | 0.00023152 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8764.80 | 8457.67 | -999.0 | 27.96 | 17.69 | 0.00874308 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858819 | 37.7128 | 8193.85 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 496305.627 | 496305.627 | 25.054988 | 0.01215449 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 496305.63 | 496305.63 | 25.054988 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.3506 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9679.560 | 9679.560 | 0.493751 | 0.00023705 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9679.56 | 9679.56 | 0.493751 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1660 | 25.76 | 0.00611149 | 28.9859 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92966.765 | 92966.765 | 4.736027 | 0.00227675 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92966.77 | 92966.77 | 4.736027 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.3007 | 23.94 | 0.00154420 | 8.2246 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9453.480 | 9453.480 | 0.481719 | 0.00023152 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9453.48 | 9453.48 | 0.481719 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2451 | 22.71 | 0.00147926 | 8.4873 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 22473.72 | 22473.72 | 25.054988 | -0.22 | -0.22 | 0.00839768 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.3506 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.493751 | -0.52 | -0.52 | 0.00594726 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1660 | 25.76 | 0.00611149 | 28.9859 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10381.93 | 10381.93 | 4.736027 | -0.54 | -4.02 | 0.00152373 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.3007 | 23.94 | 0.00154420 | 8.2246 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.481719 | -0.53 | -4.12 | 0.00146125 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2451 | 22.71 | 0.00147926 | 8.4873 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16322.639 | 16322.639 | 1.617021 | 0.00014280 | 329.970 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.6744 | 0.687924 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16322.64 | 16322.64 | 1.0000 | 1.89826245 | 1.617021 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.14278300 | 60.00 | 32.22 | 27.78 | 0.000 | 16322.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00109934 | 21.00 | 0.00109934 | 7.0052 | 650.01 | 0.00 | 16382.73 | 16382.73 | 1.89826245 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.26 | 14.95 | 0.00800000 | 41690.2 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 435881.867 | 435881.867 | 16.162624 | 0.00381328 | 10653.970 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 18.0080 | 18.370413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 435881.87 | 435881.87 | 1.0000 | 18.97371380 | 16.162624 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.81289572 | 60.00 | 32.22 | 27.78 | 0.000 | 435881.87 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 277230.59 | 0.00 | 437285.21 | 437285.21 | 18.97371380 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.40 | 19.78 | 0.00800000 | 56106.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 92520.594 | 92520.594 | 2.825071 | 0.00080941 | 2442.259 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 3.8224 | 3.899317 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 92520.59 | 92520.59 | 1.0000 | 3.31642249 | 2.825071 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.80932795 | 60.00 | 32.22 | 27.78 | 0.000 | 92520.59 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 64789.88 | 0.00 | 92840.30 | 92840.30 | 3.31642249 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61053.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15519.471 | 15519.471 | 0.474426 | 0.00013577 | 409.450 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.6412 | 0.654074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15519.47 | 15519.47 | 1.0000 | 0.55694070 | 0.474426 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.13575725 | 60.00 | 32.22 | 27.78 | 0.000 | 15519.47 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764327 | 21.00 | 0.00764327 | 48.2015 | 10866.32 | 0.00 | 15571.54 | 15571.54 | 0.55694070 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10620.652 | 10620.652 | 0.324722 | 0.00009291 | 280.184 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.4388 | 0.447612 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10620.65 | 10620.65 | 1.0000 | 0.38119976 | 0.324722 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09290462 | 60.00 | 32.22 | 27.78 | 0.000 | 10620.65 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00767655 | 21.00 | 0.00767655 | 48.4086 | 7435.56 | 0.00 | 10656.14 | 10656.14 | 0.38119976 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17420.631 | 17420.631 | 0.532682 | 0.00015240 | 459.554 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.7197 | 0.734199 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17420.63 | 17420.63 | 1.0000 | 0.62532838 | 0.532682 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15238773 | 60.00 | 32.22 | 27.78 | 0.000 | 17420.63 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773153 | 21.00 | 0.00773153 | 48.7505 | 12195.10 | 0.00 | 17478.69 | 17478.69 | 0.62532838 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8218.434 | 8218.434 | 0.251115 | 0.00007190 | 216.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.3395 | 0.346369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8218.43 | 8218.43 | 1.0000 | 0.29479011 | 0.251115 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.07189111 | 60.00 | 32.22 | 27.78 | 0.000 | 8218.43 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00744282 | 21.00 | 0.00744282 | 46.9536 | 5756.54 | 0.00 | 8246.35 | 8246.35 | 0.29479011 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 240574.183 | 240574.183 | 7.361982 | 0.00210465 | 6344.028 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 9.9391 | 10.139093 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 240574.18 | 240574.18 | 1.0000 | 8.64241679 | 7.361982 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.10443320 | 60.00 | 32.22 | 27.78 | 0.000 | 240574.18 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765114 | 21.00 | 0.00765114 | 48.2514 | 168369.76 | 0.00 | 241359.53 | 241359.53 | 8.64241679 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 157600.804 | 157600.804 | 4.823012 | 0.00137876 | 4155.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 6.5111 | 6.642148 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 157600.80 | 157600.80 | 1.0000 | 5.66185635 | 4.823012 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.37861994 | 60.00 | 32.22 | 27.78 | 0.000 | 157600.80 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764635 | 21.00 | 0.00764635 | 48.2217 | 110298.55 | 0.00 | 158114.84 | 158114.84 | 5.66185635 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 240575.573 | 240575.573 | 7.362024 | 0.00210466 | 6344.065 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 9.9391 | 10.139152 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 240575.57 | 240575.57 | 1.0000 | 8.64246644 | 7.362024 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.10444536 | 60.00 | 32.22 | 27.78 | 0.000 | 240575.57 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765114 | 21.00 | 0.00765114 | 48.2514 | 168370.74 | 0.00 | 241360.92 | 241360.92 | 8.64246644 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 152919.732 | 152919.732 | 4.679547 | 0.00133781 | 4032.571 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 6.3177 | 6.444862 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 152919.73 | 152919.73 | 1.0000 | 5.49343904 | 4.679547 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.33767205 | 60.00 | 32.22 | 27.78 | 0.000 | 152919.73 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763373 | 21.00 | 0.00763373 | 48.1432 | 107025.76 | 0.00 | 153419.10 | 153419.10 | 5.49343904 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30748.752 | 30748.752 | 0.941333 | 0.00026900 | 810.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 1.2704 | 1.295918 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30748.75 | 30748.75 | 1.0000 | 1.10505514 | 0.941333 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.26897605 | 60.00 | 32.22 | 27.78 | 0.000 | 30748.75 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766911 | 21.00 | 0.00766911 | 48.3641 | 21516.34 | 0.00 | 30848.08 | 30848.08 | 1.10505514 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20063.053 | 20063.053 | 0.614218 | 0.00017552 | 528.970 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.8289 | 0.845565 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20063.05 | 20063.05 | 1.0000 | 0.72104582 | 0.614218 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17550243 | 60.00 | 32.22 | 27.78 | 0.000 | 20063.05 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766239 | 21.00 | 0.00766239 | 48.3223 | 14039.03 | 0.00 | 20127.83 | 20127.83 | 0.72104582 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30749.003 | 30749.003 | 0.941341 | 0.00026901 | 810.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 1.2704 | 1.295929 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30749.00 | 30749.00 | 1.0000 | 1.10506416 | 0.941341 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.26897825 | 60.00 | 32.22 | 27.78 | 0.000 | 30749.00 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766912 | 21.00 | 0.00766912 | 48.3641 | 21516.52 | 0.00 | 30848.33 | 30848.33 | 1.10506416 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19800.358 | 19800.358 | 0.606169 | 0.00017322 | 522.046 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 0.8180 | 0.834494 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19800.36 | 19800.36 | 1.0000 | 0.71159731 | 0.606169 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17320450 | 60.00 | 32.22 | 27.78 | 0.000 | 19800.36 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765793 | 21.00 | 0.00765793 | 48.2946 | 13855.34 | 0.00 | 19864.30 | 19864.30 | 0.71159731 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 199062.205 | -999.000 | 9.224722 | 0.00569315 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2359 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.224722 | 10.82913449 | 4197.9300 | 999.8980 | 69.35137964 | 15.00 | 6.67 | 8.33 | 2425131.54 | 8.2083 | 8.208305 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 199062.20 | 159856.95 | 1.0000 | 10.82913449 | 9.224722 | 25.42 | 17.77 | 0.00989584 | 50763.8 | 10.90 | 10.90 | 0.00850000 | 32381.8 | 5.69257309 | 6.67 | 15.00 | 8.33 | 21066.754 | 177995.45 | 30.30 | 0.01336696 | 21.83 | 2.03050000 | 22.0115 | 24.00 | 0.00888100 | 24.00 | 0.00888100 | 46.5821 | 120431.59 | 0.00 | 202826.78 | 157128.78 | 10.82913449 | 25.42 | 18.04 | 0.00989584 | 50763.8 | 11.24 | 11.16 | 0.00822249 | 32034.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 62573.552 | 62573.552 | 2.767417 | 0.00054742 | 1012.687 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.224722 | 10.82913449 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 2.5852 | 2.637187 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62573.55 | 62573.55 | 1.0000 | 3.24874035 | 2.767417 | -6.37 | -7.19 | 0.00180950 | -1894.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.54736488 | 60.00 | 32.22 | 27.78 | 0.000 | 62573.55 | -16.30 | 0.00092409 | -16.30 | 2.03050000 | 73.3717 | 21.00 | 0.00424917 | 20.21 | 0.00537456 | 35.7120 | 22402.53 | 0.00 | 56234.53 | 56234.53 | 3.24874035 | 2.80 | -1.48 | 0.00180950 | 7348.4 | 19.97 | 8.02 | 0.00180950 | 24658.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1910140.556 | -999.000 | 85.937991 | 0.05462978 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5305 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 85.937991 | 100.88478251 | 4197.9300 | 999.8980 | 69.35137964 | 15.00 | 6.67 | 8.33 | 2425131.54 | 78.7644 | 78.764410 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1910140.56 | 1503604.16 | 1.0000 | 100.88478251 | 85.937991 | 25.57 | 17.95 | 0.01005436 | 51316.2 | 10.90 | 10.90 | 0.00850000 | 32382.3 | 54.62420530 | 6.67 | 15.00 | 8.33 | 196258.979 | 1713881.58 | 30.30 | 0.01336696 | 21.83 | 20.30600000 | 23.6287 | 24.00 | 0.00895453 | 24.00 | 0.00895453 | 46.9628 | 1093073.28 | 0.00 | 1945437.69 | 1479485.63 | 100.88478251 | 25.57 | 18.22 | 0.01005436 | 51316.2 | 11.24 | 11.16 | 0.00822289 | 32032.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 656277.622 | 656277.622 | 25.781397 | 0.00574140 | 10485.171 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 85.937991 | 100.88478251 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 27.1134 | 27.659078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 656277.62 | 656277.62 | 1.0000 | 30.26543475 | 25.781397 | -8.78 | -8.78 | 0.00232147 | -3053.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 5.74081725 | 60.00 | 32.22 | 27.78 | 0.000 | 656277.62 | -16.30 | 0.00092409 | -16.30 | 20.30600000 | 78.7622 | 19.11 | 0.00750375 | 18.05 | 0.00740353 | 56.0962 | 280580.38 | 0.00 | 574082.78 | 574082.78 | 30.26543475 | 2.80 | -0.69 | 0.00232147 | 8631.5 | 21.60 | 9.36 | 0.00232147 | 27599.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 202158.945 | -999.000 | 9.441561 | 0.00578172 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1827 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.441561 | 11.08368709 | 4197.9300 | 999.8980 | 69.35137964 | 15.00 | 6.67 | 8.33 | 2425131.54 | 8.3360 | 8.335999 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 202158.94 | 162851.04 | 1.0000 | 11.08368709 | 9.441561 | 25.36 | 17.73 | 0.00986722 | 50621.0 | 10.90 | 10.90 | 0.00850000 | 32381.7 | 5.78113043 | 6.67 | 15.00 | 8.33 | 21561.955 | 180596.99 | 30.30 | 0.01336696 | 21.83 | 2.03050000 | 21.5060 | 24.00 | 0.00890640 | 24.00 | 0.00890640 | 46.7141 | 126480.16 | 0.00 | 205953.31 | 160011.31 | 11.08368709 | 25.36 | 18.00 | 0.00986722 | 50621.0 | 11.25 | 11.17 | 0.00822358 | 32039.3 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 64351.664 | 64351.664 | 2.832468 | 0.00056298 | 1040.569 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.441561 | 11.08368709 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 2.6586 | 2.712126 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 64351.66 | 64351.66 | 1.0000 | 3.32510613 | 2.832468 | -6.46 | -6.46 | 0.00279493 | 465.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.56291900 | 60.00 | 32.22 | 27.78 | 0.000 | 64351.66 | -16.30 | 0.00092409 | -16.30 | 2.03050000 | 71.6866 | 18.45 | 0.00753171 | 15.93 | 0.00755524 | 65.4838 | 28040.12 | 0.00 | 57772.27 | 57772.27 | 3.32510613 | 2.80 | 0.22 | 0.00279493 | 9818.1 | 20.00 | 9.17 | 0.00279493 | 27192.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 113769.830 | -999.000 | 5.101242 | 0.00325380 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7502 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:VariableVolume | 5.101242 | 5.98847732 | 4197.9300 | 999.8980 | 69.35137964 | 15.00 | 6.67 | 8.33 | 2425131.54 | 4.6913 | 4.691285 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 113769.83 | 87793.01 | 1.0000 | 5.98847732 | 5.101242 | 25.33 | 17.96 | 0.01017251 | 51368.3 | 10.89 | 10.89 | 0.00850000 | 32370.2 | 3.25347081 | 6.67 | 15.00 | 8.33 | 11725.009 | 102044.82 | 29.09 | 0.01336481 | 21.48 | 1.20015641 | 23.5267 | 24.00 | 0.00904705 | 24.00 | 0.00904705 | 47.4407 | 61779.91 | 0.00 | 115874.01 | 86416.59 | 5.98847732 | 25.33 | 18.23 | 0.01017251 | 51368.3 | 11.23 | 11.16 | 0.00822192 | 32018.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:VariableVolume | 5.101242 | 5.98847732 | 4197.9300 | 999.8980 | 20.75563469 | 54.44 | 82.22 | 27.78 | 2420490.89 | 4.1314 | 4.214539 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.116633 | -3.83 | -7.16 | 0.00092409 | -1548.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -16.30 | 0.00092409 | -16.30 | 1.20015641 | 38.5081 | 0.00 | 0.00092409 | 23.36 | 0.00092409 | 5.1020 | 0.00 | 0.00 | 100076.34 | 100076.34 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.2 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 496305.627 | 349488.485 | 25.054988 | 0.01215449 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8411 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 460920.88 | 453838.57 | 0.9287 | -999.0 | -999.0 | 28.47 | 17.75 | 0.00860762 | 50591.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 460920.88 | 30.30 | 0.01336696 | 21.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854239 | 27.00 | 0.00854239 | 37.5167 | 370224.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9679.560 | 6845.929 | 0.493751 | 0.00023705 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0823 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8972.85 | 8665.53 | 0.9270 | -999.0 | -999.0 | 27.95 | 17.68 | 0.00873733 | 50393.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8972.85 | 26.50 | 0.01336023 | 20.72 | 0.01563234 | -999.0000 | 27.00 | 0.00858618 | 27.00 | 0.00858618 | 37.7040 | 8399.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92966.765 | 65704.124 | 4.736027 | 0.00227675 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1007 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 86197.53 | 83125.96 | 0.9272 | -999.0 | -999.0 | 27.95 | 17.69 | 0.00874726 | 50418.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86197.53 | 26.50 | 0.01336023 | 20.72 | 0.15632344 | -999.0000 | 27.00 | 0.00858980 | 27.00 | 0.00858980 | 37.7198 | 80568.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9453.480 | 6682.260 | 0.481719 | 0.00023152 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0929 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8764.80 | 8457.67 | 0.9272 | -999.0 | -999.0 | 27.96 | 17.69 | 0.00874308 | 50413.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8764.80 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858819 | 27.00 | 0.00858819 | 37.7128 | 8193.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 496305.627 | 496305.627 | 25.054988 | 0.01215449 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 496305.63 | 496305.63 | 1.0000 | 29.41268437 | 25.054988 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 496305.63 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.3506 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9679.560 | 9679.560 | 0.493751 | 0.00023705 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9679.56 | 9679.56 | 1.0000 | 0.57962705 | 0.493751 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9679.56 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1660 | 0.00 | 0.00611149 | 25.76 | 0.00611149 | 28.9859 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92966.765 | 92966.765 | 4.736027 | 0.00227675 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92966.77 | 92966.77 | 1.0000 | 5.55974242 | 4.736027 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92966.77 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.3007 | 0.00 | 0.00154420 | 23.94 | 0.00154420 | 8.2246 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9453.480 | 9453.480 | 0.481719 | 0.00023152 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9453.48 | 9453.48 | 1.0000 | 0.56550178 | 0.481719 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9453.48 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2451 | 0.00 | 0.00147926 | 22.71 | 0.00147926 | 8.4873 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.054988 | 29.41268437 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 22473.72 | 22473.72 | 1.0000 | 29.41268437 | 25.054988 | -0.22 | -0.22 | 0.00839768 | 20777.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22473.72 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.3506 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.493751 | 0.57962705 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.57962705 | 0.493751 | -0.52 | -0.52 | 0.00594726 | 14349.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1660 | 0.00 | 0.00611149 | 25.76 | 0.00611149 | 28.9859 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.736027 | 5.55974242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10381.93 | 10381.93 | 1.0000 | 5.55974242 | 4.736027 | -0.54 | -4.02 | 0.00152373 | 3268.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10381.93 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.3007 | 0.00 | 0.00154420 | 23.94 | 0.00154420 | 8.2246 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.481719 | 0.56550178 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.56550178 | 0.481719 | -0.53 | -4.12 | 0.00146125 | 3121.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2451 | 0.00 | 0.00147926 | 22.71 | 0.00147926 | 8.4873 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.22 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 85.94 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.44 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.10 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2744.83 | 1574.83 | 544.67 |
CORE_BOTTOM | 2449.83 | 1321.67 | 12.83 |
CORE_MID | 1824.50 | 2883.83 | 96.17 |
CORE_TOP | 2469.83 | 3559.50 | 936.50 |
PERIMETER_BOT_ZN_3 | 2222.00 | 3211.83 | 468.83 |
PERIMETER_BOT_ZN_2 | 2549.83 | 3084.33 | 555.83 |
PERIMETER_BOT_ZN_1 | 2730.33 | 2855.50 | 593.50 |
PERIMETER_BOT_ZN_4 | 2889.50 | 2131.33 | 402.67 |
PERIMETER_MID_ZN_3 | 3147.50 | 3869.67 | 1752.67 |
PERIMETER_MID_ZN_2 | 2909.67 | 3073.17 | 1457.67 |
PERIMETER_MID_ZN_1 | 3099.17 | 3238.67 | 1181.67 |
PERIMETER_MID_ZN_4 | 3291.00 | 3455.50 | 1461.00 |
PERIMETER_TOP_ZN_3 | 3591.67 | 4109.17 | 2298.67 |
PERIMETER_TOP_ZN_2 | 3805.00 | 3724.67 | 2111.33 |
PERIMETER_TOP_ZN_1 | 3442.33 | 3553.67 | 1719.50 |
PERIMETER_TOP_ZN_4 | 3641.83 | 3728.50 | 1940.33 |
DATACENTER_BOT_ZN_6 | 5925.17 | 824.00 | 824.00 |
DATACENTER_MID_ZN_6 | 5171.00 | 221.67 | 133.83 |
DATACENTER_TOP_ZN_6 | 4647.00 | 667.83 | 283.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5516.50 | 5516.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5936.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1461.83 | 0.00 | 860.67 |
CORE_BOTTOM | 0.00 | 4.17 | 0.00 | 0.00 |
CORE_MID | 1.50 | 0.00 | 0.67 | 0.00 |
CORE_TOP | 14.67 | 0.00 | 2.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.50 | 6.67 | 0.00 | 4.50 |
PERIMETER_BOT_ZN_2 | 0.83 | 35.67 | 0.00 | 34.67 |
PERIMETER_BOT_ZN_1 | 1.83 | 44.83 | 0.00 | 41.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 115.83 | 0.00 | 54.00 |
PERIMETER_MID_ZN_3 | 71.50 | 1.00 | 19.83 | 1.00 |
PERIMETER_MID_ZN_2 | 71.17 | 33.67 | 0.17 | 33.00 |
PERIMETER_MID_ZN_1 | 27.50 | 41.33 | 0.50 | 40.17 |
PERIMETER_MID_ZN_4 | 24.00 | 45.50 | 0.17 | 25.33 |
PERIMETER_TOP_ZN_3 | 230.67 | 5.50 | 81.83 | 4.33 |
PERIMETER_TOP_ZN_2 | 113.50 | 34.50 | 14.67 | 31.83 |
PERIMETER_TOP_ZN_1 | 103.00 | 33.50 | 10.67 | 30.67 |
PERIMETER_TOP_ZN_4 | 79.00 | 48.00 | 8.33 | 26.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 127.67 | 0.00 | 92.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 282.83 | 1624.83 | 82.50 | 986.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 149.60 | 6779.02 | 0.977 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.32 | 134.35 | 6849.35 | 0.954 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.32 | 134.35 | 6849.35 | 0.708 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.32 | 134.35 | 6849.35 | 0.692 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.95 | 16.87 | 860.00 | 0.915 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 1.270 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.95 | 16.87 | 860.02 | 1.281 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 1.779 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.95 | 16.87 | 860.00 | 0.750 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 1.086 | 0.068 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.95 | 16.87 | 860.02 | 1.167 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 1.181 | 0.064 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.95 | 16.87 | 860.00 | 0.779 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 1.217 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.95 | 16.87 | 860.02 | 1.188 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 1.220 | 0.080 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.37 | 42.18 | 1911.37 | 27.303 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.60 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.32 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.95 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.95 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.37 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.60 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.32 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.91 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.95 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.95 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.37 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1020.85 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38520511.34 | 0.00 | 38520511.34 | 0.00 | 38520511.34 | 37848132.68 | 4851.01 | 1093.19 | 2815.80 | 0.00 |
CORE_BOTTOM | 40767808.32 | 0.00 | 40767808.32 | 0.00 | 40767808.32 | 33990283.35 | 3945.69 | 141.39 | 4672.93 | 516.18 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 4655.47 | 749.07 | 3355.47 | 314.73 |
CORE_TOP | 28468448.96 | 0.00 | 28468448.96 | 0.00 | 28468448.96 | 33990283.35 | 4879.75 | 1064.37 | 2815.89 | 409.54 |
PERIMETER_BOT_ZN_3 | 4906409.58 | 0.00 | 4906409.58 | 263099.47 | 5169509.06 | 4267819.30 | 5135.21 | 179.62 | 3445.18 | 516.18 |
PERIMETER_BOT_ZN_2 | 4306643.67 | 0.00 | 4306643.67 | 175399.53 | 4482043.20 | 2750345.05 | 5020.79 | 317.71 | 3421.50 | 516.18 |
PERIMETER_BOT_ZN_1 | 6744574.17 | 0.00 | 6744574.17 | 263099.47 | 7007673.64 | 4267912.63 | 4818.84 | 266.63 | 3674.53 | 516.18 |
PERIMETER_BOT_ZN_4 | 6076624.08 | 0.00 | 6076624.08 | 175399.53 | 6252023.61 | 2750345.05 | 4149.27 | 143.64 | 4467.09 | 516.18 |
PERIMETER_MID_ZN_3 | 38871482.97 | 0.00 | 38871482.97 | 617042.04 | 39488525.01 | 42678193.03 | 4732.57 | 732.57 | 3294.85 | 314.73 |
PERIMETER_MID_ZN_2 | 36854229.70 | 0.00 | 36854229.70 | 411361.08 | 37265590.78 | 27503450.52 | 4828.97 | 570.29 | 3360.74 | 832.79 |
PERIMETER_MID_ZN_1 | 59784463.85 | 0.00 | 59784463.85 | 617042.04 | 60401505.89 | 42679126.28 | 4329.55 | 921.64 | 3508.81 | 314.73 |
PERIMETER_MID_ZN_4 | 39425018.36 | 0.00 | 39425018.36 | 411361.08 | 39836379.44 | 27503450.52 | 4550.01 | 984.71 | 3225.27 | 314.73 |
PERIMETER_TOP_ZN_3 | 4025814.92 | 0.00 | 4025814.92 | 766123.54 | 4791938.46 | 4267819.30 | 4411.96 | 1056.33 | 3291.71 | 409.54 |
PERIMETER_TOP_ZN_2 | 4007199.74 | 0.00 | 4007199.74 | 510748.68 | 4517948.42 | 2750345.05 | 4364.31 | 1162.73 | 3232.96 | 409.54 |
PERIMETER_TOP_ZN_1 | 6073239.34 | 0.00 | 6073239.34 | 766123.54 | 6839362.88 | 4267912.63 | 4275.70 | 1262.72 | 3221.57 | 409.54 |
PERIMETER_TOP_ZN_4 | 4072982.99 | 0.00 | 4072982.99 | 510748.68 | 4583731.66 | 2750345.05 | 4314.07 | 761.12 | 3684.81 | 409.54 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.43E+09 | 0.00 | 0.43E+09 | 0.00 | 0.43E+09 | 10671554.30 | 18.83 | 123.42 | 8617.75 | 2815.33 |
Total Facility | 0.53E+10 | 0.00 | 0.53E+10 | 23998804.81 | 0.53E+10 | 0.50E+10 | 7088.33 | 4363.68 | 8746.53 | 3334.56 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.8005 | 0.0000 | 1.8005 | 0.0000 | 1.8005 | 1.2002 | 2034.01 | 1093.19 | 2815.80 |
CORE_BOTTOM | 1.7750 | 0.0000 | 1.7750 | 0.0000 | 1.7750 | 1.0778 | 1555.22 | 139.29 | 4248.49 |
CORE_MID | 13.1955 | 0.0000 | 13.1955 | 0.0000 | 13.1955 | 10.7782 | 1971.58 | 748.62 | 3222.80 |
CORE_TOP | 1.2896 | 0.0000 | 1.2896 | 0.0000 | 1.2896 | 1.0778 | 2183.44 | 1064.12 | 2695.44 |
PERIMETER_BOT_ZN_3 | 0.2138 | 0.0000 | 0.2138 | 0.0062 | 0.2201 | 0.1353 | 2736.65 | 177.38 | 3028.98 |
PERIMETER_BOT_ZN_2 | 0.1914 | 0.0000 | 0.1914 | 0.0042 | 0.1956 | 0.0872 | 2622.35 | 314.15 | 3006.50 |
PERIMETER_BOT_ZN_1 | 0.2998 | 0.0000 | 0.2998 | 0.0062 | 0.3060 | 0.1353 | 2421.16 | 263.20 | 3258.64 |
PERIMETER_BOT_ZN_4 | 0.2680 | 0.0000 | 0.2680 | 0.0042 | 0.2721 | 0.0872 | 1758.18 | 141.81 | 4043.01 |
PERIMETER_MID_ZN_3 | 1.7571 | 0.0000 | 1.7571 | 0.0146 | 1.7717 | 1.3533 | 2050.28 | 731.68 | 3161.04 |
PERIMETER_MID_ZN_2 | 1.6380 | 0.0000 | 1.6380 | 0.0103 | 1.6484 | 0.8721 | 1688.57 | 567.37 | 2778.05 |
PERIMETER_MID_ZN_1 | 2.7341 | 0.0000 | 2.7341 | 0.0146 | 2.7488 | 1.3533 | 1649.29 | 921.31 | 3372.40 |
PERIMETER_MID_ZN_4 | 1.7812 | 0.0000 | 1.7812 | 0.0098 | 1.7909 | 0.8721 | 1872.24 | 984.41 | 3086.35 |
PERIMETER_TOP_ZN_3 | 0.1827 | 0.0000 | 0.1827 | 0.0182 | 0.2009 | 0.1353 | 1716.98 | 1055.91 | 3170.11 |
PERIMETER_TOP_ZN_2 | 0.1837 | 0.0000 | 0.1837 | 0.0121 | 0.1958 | 0.0872 | 1672.02 | 1162.37 | 3108.61 |
PERIMETER_TOP_ZN_1 | 0.2783 | 0.0000 | 0.2783 | 0.0182 | 0.2965 | 0.1353 | 1581.85 | 1262.45 | 3098.70 |
PERIMETER_TOP_ZN_4 | 0.1840 | 0.0000 | 0.1840 | 0.0121 | 0.1962 | 0.0872 | 1620.56 | 761.00 | 3561.43 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.0226 | 0.0000 | 14.0226 | 0.0000 | 14.0226 | 0.3384 | 17.17 | 123.42 | 5802.42 |
Total Facility | 232.9128 | 0.0000 | 232.9128 | 0.5751 | 233.4879 | 158.4706 | 4271.33 | 4357.80 | 5930.03 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 86547775.73 | 0.00 | 86547775.73 | 48026705.38 | 3482.76 | 3.87 | 5273.37 | 516.18 |
VAV_MID WITH REHEAT | 0.64E+09 | 0.00 | 0.64E+09 | 0.48E+09 | 3952.10 | 2.46 | 4805.43 | 314.73 |
VAV_TOP WITH REHEAT | 64285617.39 | 0.00 | 64285617.39 | 48026705.38 | 3995.56 | 1.89 | 4762.55 | 409.07 |
CAV_BAS | 53085145.75 | 0.00 | 53085145.75 | 37848132.68 | 4824.42 | 0.08 | 3935.50 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.60E+09 | 0.00 | 0.60E+09 | 10671554.30 | 18.83 | 0.00 | 8741.17 | 2815.33 |
AIRLOOP DATACENTER BOT | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3366645.00 | 0.00 | 3366645.00 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.7870 | 0.0000 | 3.7870 | 1.5229 | 1123.27 | 2.40 | 4817.32 |
VAV_MID WITH REHEAT | 29.1475 | 0.0000 | 29.1475 | 15.2292 | 1275.76 | 2.24 | 4665.00 |
VAV_TOP WITH REHEAT | 2.9193 | 0.0000 | 2.9193 | 1.5229 | 1302.85 | 1.74 | 4638.42 |
CAV_BAS | 2.4812 | 0.0000 | 2.4812 | 1.2002 | 2007.42 | 0.08 | 3935.50 |
AIRLOOP DATACENTER BASEMENT | 19.3245 | 0.0000 | 19.3245 | 0.3384 | 17.17 | 0.00 | 5925.83 |
AIRLOOP DATACENTER BOT | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1574 | 0.0000 | 0.1574 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 783.88 | 3287.79 | 0.00 | 0.00 | 0.00 | 1372.59 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 314.21 | 2707.26 | 0.00 | 0.00 | 0.00 | 2121.98 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 56.49 | 2881.03 | 0.00 | 0.00 | 0.00 | 2353.35 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1074.06 | 2830.11 | 0.00 | 47.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 123.42 | 8617.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.8153 | 6.1698 | 0.0000 | 0.0000 | 0.0000 | 2.3336 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 27.6836 | 49.0606 | 0.0000 | 0.0000 | 0.0000 | 22.2332 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.7179 | 4.8666 | 0.0000 | 0.0000 | 0.0000 | 2.1979 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6540 | 4.5612 | 0.0000 | 1.3020 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4679 | 19.7843 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2155 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1521 |
Defaulted Fields | 1185 |
Fields with Defaults | 3940 |
Autosized Fields | 338 |
Autosizable Fields | 416 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
Electricity:Building | 17137.56 | 216479.19 | 07-MAY-17:20 | 1025582.59 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17137.56 | 216479.19 | 07-MAY-17:20 | 1025582.59 | 01-DEC-16:40 |
InteriorLights:Electricity | 2461.16 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2461.16 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 2461.16 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2461.16 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.03 | 603.11 | 12-MAR-17:10 | 3823.11 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.67 | 43.94 | 01-JAN-10:10 | 1662.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.67 | 43.94 | 01-JAN-10:10 | 1662.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.28 | 388.67 | 26-MAR-17:10 | 2463.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.84 | 28.32 | 01-JAN-09:10 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.84 | 28.32 | 01-JAN-09:10 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.92 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.55 | 43.94 | 01-JAN-09:10 | 1662.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.55 | 43.94 | 01-JAN-09:10 | 1662.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.27 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.83 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.83 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 470.18 | 6031.15 | 12-MAR-17:10 | 38231.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.52 | 439.44 | 01-JAN-10:00 | 16625.62 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.52 | 439.44 | 01-JAN-10:00 | 16625.62 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.68 | 3886.70 | 26-MAR-17:10 | 24637.60 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.33 | 283.19 | 01-JAN-09:00 | 10714.18 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.33 | 283.19 | 01-JAN-09:00 | 10714.18 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 469.12 | 6031.24 | 12-MAR-17:10 | 38231.83 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.46 | 439.45 | 01-JAN-09:00 | 16625.99 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.46 | 439.45 | 01-JAN-09:00 | 16625.99 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 302.56 | 3886.68 | 12-MAR-17:10 | 24637.51 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.21 | 283.19 | 01-JAN-09:40 | 10714.18 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.21 | 283.19 | 01-JAN-09:40 | 10714.18 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.02 | 603.11 | 12-MAR-17:10 | 3823.11 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.65 | 43.94 | 01-JAN-10:00 | 1662.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.65 | 43.94 | 01-JAN-10:00 | 1662.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.27 | 388.67 | 26-MAR-17:10 | 2463.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.83 | 28.32 | 01-JAN-09:00 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.83 | 28.32 | 01-JAN-09:00 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.91 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.55 | 43.94 | 01-JAN-09:00 | 1662.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.55 | 43.94 | 01-JAN-09:00 | 1662.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.26 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.82 | 28.32 | 01-JAN-09:40 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.82 | 28.32 | 01-JAN-09:40 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1813.43 | 3824.30 | 31-JAN-02:00 | 556952.44 | 05-JUL-15:50 |
HeatRejection:Electricity | 477.95 | 56.85 | 06-JAN-08:00 | 79472.29 | 14-MAR-12:20 |
General:HeatRejection:Electricity | 477.95 | 56.85 | 06-JAN-08:00 | 79472.29 | 14-MAR-12:20 |
Electricity:HVAC | 4783.01 | 53884.28 | 29-SEP-05:00 | 468191.28 | 03-AUG-15:30 |
ExteriorEquipment:Electricity | 2566.27 | 20217.42 | 01-JAN-00:10 | 233396.00 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
ElectricityPurchased:Plant | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
Cogeneration:ElectricityPurchased | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
General:Cogeneration:ElectricityPurchased | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
ElectricityNet:Plant | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
Cogeneration:ElectricityNet | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
General:Cogeneration:ElectricityNet | 26598.87 | 296344.49 | 21-MAY-05:00 | 2111016.45 | 15-AUG-14:40 |
Fans:Electricity | 2360.91 | 47719.36 | 02-JAN-22:10 | 274878.55 | 10-AUG-15:20 |
General:Fans:Electricity | 2360.91 | 47719.36 | 02-JAN-22:10 | 274878.55 | 10-AUG-15:20 |
ExteriorLights:Electricity | 353.28 | 0.00 | 01-JAN-08:00 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 353.28 | 0.00 | 01-JAN-08:00 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 36.73 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 36.73 | 0.00 | 01-JAN-00:10 | 4520.72 | 02-JAN-07:10 |
Cooling:Electricity | 1396.53 | 1651.97 | 07-JAN-09:00 | 528085.65 | 05-JUL-15:50 |
General:Cooling:Electricity | 1396.53 | 1651.97 | 07-JAN-09:00 | 528085.65 | 05-JUL-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1463.05 | 0.00 | 11-JAN-13:10 | 100000.00 | 14-FEB-22:10 |
General:Humidifier:Electricity | 1463.05 | 0.00 | 11-JAN-13:10 | 100000.00 | 14-FEB-22:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 459.85 | 0.00 | 01-JAN-00:10 | 56293.54 | 13-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 459.85 | 0.00 | 01-JAN-00:10 | 56293.54 | 13-FEB-12:30 |
Pumps:Electricity | 346.74 | 3762.57 | 01-JAN-00:40 | 48849.73 | 05-JUL-16:00 |
General:Pumps:Electricity | 346.74 | 3762.57 | 01-JAN-00:40 | 48849.73 | 05-JUL-16:00 |
WIRED_LTG_ELECTRICITY | 69.16 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1151.06 | 0.00 | 01-JAN-00:40 | 1582955.37 | 02-JAN-05:10 |
NaturalGas:Plant | 1151.06 | 0.00 | 01-JAN-00:40 | 1582955.37 | 02-JAN-05:10 |
Heating:NaturalGas | 1151.06 | 0.00 | 01-JAN-00:40 | 1582955.37 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 1151.06 | 0.00 | 01-JAN-00:40 | 1582955.37 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8710.40 | 4292.24 | 07-JAN-09:00 | 3187674.13 | 15-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 8710.40 | 4292.24 | 07-JAN-09:00 | 3187674.13 | 15-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 8710.40 | 4292.24 | 07-JAN-09:00 | 3187674.13 | 15-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6164.37 | 0.00 | 11-MAR-01:00 | 0.00 | 17-AUG-12:50 |
Water:HVAC | 544.26 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Humidifier:Water | 544.26 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
General:Humidifier:Water | 544.26 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
MainsWater:Facility | 6164.37 | 0.00 | 11-MAR-01:00 | 0.00 | 17-AUG-12:50 |
MainsWater:HVAC | 544.26 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Humidifier:MainsWater | 544.26 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
General:Humidifier:MainsWater | 544.26 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Water:Plant | 5620.11 | 0.00 | 01-JAN-00:10 | 0.00 | 17-AUG-12:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5620.11 | 0.00 | 01-JAN-00:10 | 0.00 | 17-AUG-12:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3339.94 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:30 |
General:HeatRejection:Water | 3339.94 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:30 |
HeatRejection:MainsWater | 3339.94 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:30 |
General:HeatRejection:MainsWater | 3339.94 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-13:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 43841.73 | 94811.77 | 30-JAN-05:40 | 12186338.00 | 05-JUL-16:00 |
EnergyTransfer:Building | 17563.12 | 88273.84 | 21-JAN-18:10 | 1667975.50 | 09-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 548.57 | 0.00 | 01-JAN-00:10 | 97434.21 | 13-JUN-06:10 |
Heating:EnergyTransfer | 708.45 | 0.00 | 01-FEB-00:20 | 1173490.52 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 708.45 | 0.00 | 01-FEB-00:20 | 1173490.52 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 16854.67 | 85673.48 | 30-JAN-05:00 | 1667975.50 | 09-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 548.57 | 0.00 | 01-JAN-00:10 | 97434.21 | 13-JUN-06:10 |
General:Cooling:EnergyTransfer | 16854.67 | 85673.48 | 30-JAN-05:00 | 1667975.50 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 548.57 | 0.00 | 01-JAN-00:10 | 97434.21 | 13-JUN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 582.68 | 0.00 | 01-JAN-00:10 | 59980.76 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 582.68 | 0.00 | 01-JAN-00:10 | 59980.76 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 582.68 | 0.00 | 01-JAN-00:10 | 59980.76 | 15-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 3862.23 | 0.00 | 01-JAN-00:40 | 427637.51 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.69 | 0.00 | 01-JAN-00:10 | 427637.51 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.69 | 0.00 | 01-JAN-00:10 | 427637.51 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3853.54 | 0.00 | 01-JAN-00:40 | 399559.86 | 24-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3853.54 | 0.00 | 01-JAN-00:40 | 399559.86 | 24-JUL-13:10 |
EnergyTransfer:Zone:CORE_TOP | 350.05 | 0.00 | 01-JAN-00:40 | 65849.95 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 17.85 | 0.00 | 01-JAN-00:40 | 65849.95 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 17.85 | 0.00 | 01-JAN-00:40 | 65849.95 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 332.20 | 0.00 | 01-JAN-00:20 | 47163.06 | 21-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 332.20 | 0.00 | 01-JAN-00:20 | 47163.06 | 21-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.67 | 0.00 | 01-JAN-00:10 | 11942.72 | 21-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.90 | 0.00 | 01-JAN-00:10 | 6894.19 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.90 | 0.00 | 01-JAN-00:10 | 6894.19 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.77 | 0.00 | 01-JAN-00:10 | 11942.72 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.77 | 0.00 | 01-JAN-00:10 | 11942.72 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.67 | 0.00 | 01-JAN-00:10 | 15146.09 | 10-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.79 | 0.00 | 01-JAN-00:10 | 5186.30 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.79 | 0.00 | 01-JAN-00:10 | 5186.30 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.88 | 0.00 | 01-JAN-00:10 | 15146.09 | 10-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 55.88 | 0.00 | 01-JAN-00:10 | 15146.09 | 10-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 94.12 | 0.00 | 01-JAN-00:10 | 20916.70 | 31-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.66 | 0.00 | 01-JAN-00:10 | 9536.84 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.66 | 0.00 | 01-JAN-00:10 | 9536.84 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 92.46 | 0.00 | 01-JAN-00:10 | 20916.70 | 31-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 92.46 | 0.00 | 01-JAN-00:10 | 20916.70 | 31-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.82 | 0.00 | 01-JAN-00:10 | 18276.29 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2636.75 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2636.75 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.74 | 0.00 | 01-JAN-00:10 | 18276.29 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 85.74 | 0.00 | 01-JAN-00:10 | 18276.29 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 560.39 | 0.00 | 01-JAN-00:40 | 121064.35 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 149.82 | 0.00 | 01-JAN-00:40 | 121064.35 | 06-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 149.82 | 0.00 | 01-JAN-00:40 | 121064.35 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 410.57 | 0.00 | 01-JAN-00:10 | 97970.18 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 410.57 | 0.00 | 01-JAN-00:10 | 97970.18 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 520.77 | 0.00 | 01-JAN-00:40 | 156409.12 | 13-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 81.64 | 0.00 | 01-JAN-00:40 | 120244.52 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 81.64 | 0.00 | 01-JAN-00:40 | 120244.52 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 439.13 | 0.00 | 01-JAN-00:10 | 156409.12 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 439.13 | 0.00 | 01-JAN-00:10 | 156409.12 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 856.79 | 0.00 | 01-JAN-00:40 | 218072.79 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.89 | 0.00 | 01-JAN-00:40 | 167791.14 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.89 | 0.00 | 01-JAN-00:40 | 167791.14 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 766.90 | 0.00 | 01-JAN-00:10 | 218072.79 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 766.90 | 0.00 | 01-JAN-00:10 | 218072.79 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 557.01 | 0.00 | 01-JAN-00:40 | 168133.15 | 02-JUL-17:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 66.04 | 0.00 | 01-JAN-00:40 | 111456.37 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 66.04 | 0.00 | 01-JAN-00:40 | 111456.37 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 490.97 | 0.00 | 01-JAN-00:10 | 168133.15 | 02-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 490.97 | 0.00 | 01-JAN-00:10 | 168133.15 | 02-JUL-17:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 71.94 | 0.00 | 01-JAN-00:40 | 14289.01 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.30 | 0.00 | 01-JAN-00:40 | 14289.01 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.30 | 0.00 | 01-JAN-00:40 | 14289.01 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.65 | 0.00 | 01-JAN-00:10 | 10824.59 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.65 | 0.00 | 01-JAN-00:10 | 10824.59 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 62.48 | 0.00 | 01-JAN-00:40 | 16604.20 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.51 | 0.00 | 01-JAN-00:40 | 16604.20 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.51 | 0.00 | 01-JAN-00:40 | 16604.20 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.98 | 0.00 | 01-JAN-00:20 | 15375.36 | 03-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.98 | 0.00 | 01-JAN-00:20 | 15375.36 | 03-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.16 | 0.00 | 01-JAN-00:40 | 22116.54 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 23.26 | 0.00 | 01-JAN-00:40 | 20778.01 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 23.26 | 0.00 | 01-JAN-00:40 | 20778.01 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.90 | 0.00 | 01-JAN-00:20 | 22116.54 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.90 | 0.00 | 01-JAN-00:20 | 22116.54 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 62.02 | 0.00 | 01-JAN-00:40 | 17468.80 | 02-JUL-17:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 15.52 | 0.00 | 01-JAN-00:40 | 15423.61 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 15.52 | 0.00 | 01-JAN-00:40 | 15423.61 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.50 | 0.00 | 01-JAN-00:20 | 17468.80 | 02-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.50 | 0.00 | 01-JAN-00:20 | 17468.80 | 02-JUL-17:10 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.64 | 0.00 | 01-JAN-00:10 | 10245.07 | 17-JUL-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.50 | 0.00 | 01-JAN-00:10 | 4431.46 | 10-DEC-12:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.50 | 0.00 | 01-JAN-00:10 | 4431.46 | 10-DEC-12:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.15 | 0.00 | 01-JAN-00:10 | 10245.07 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.15 | 0.00 | 01-JAN-00:10 | 10245.07 | 17-JUL-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 420.75 | 0.00 | 01-JAN-00:40 | 152807.24 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 140.11 | 0.00 | 01-JAN-00:40 | 152807.24 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 140.11 | 0.00 | 01-JAN-00:40 | 152807.24 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 280.64 | 0.00 | 01-JAN-00:10 | 69523.96 | 17-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 280.64 | 0.00 | 01-JAN-00:10 | 69523.96 | 17-JUL-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 93.05 | 0.00 | 01-JAN-00:40 | 27886.41 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.79 | 0.00 | 01-JAN-00:40 | 27886.41 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.79 | 0.00 | 01-JAN-00:40 | 27886.41 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.26 | 0.00 | 01-JAN-00:10 | 18465.07 | 12-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.26 | 0.00 | 01-JAN-00:10 | 18465.07 | 12-JUN-13:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.60 | 294.18 | 30-JAN-06:00 | 8244.54 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.60 | 294.18 | 30-JAN-06:00 | 8244.54 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.60 | 294.18 | 30-JAN-06:00 | 8244.54 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1167.23 | 6.04 | 10-JAN-21:50 | 79120.02 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.24 | 0.00 | 03-JAN-07:30 | 5497.74 | 03-JAN-01:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.24 | 0.00 | 03-JAN-07:30 | 5497.74 | 03-JAN-01:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1161.99 | 0.00 | 01-JAN-00:10 | 79120.02 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1161.99 | 0.00 | 01-JAN-00:10 | 79120.02 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.46 | 0.05 | 26-JAN-20:30 | 7965.22 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.89 | 0.00 | 03-JAN-07:40 | 588.75 | 15-JAN-18:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.89 | 0.00 | 03-JAN-07:40 | 588.75 | 15-JAN-18:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.57 | 0.00 | 01-JAN-00:10 | 7965.22 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.57 | 0.00 | 01-JAN-00:10 | 7965.22 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.02 | 85367.36 | 30-JAN-05:00 | 375075.88 | 15-AUG-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.02 | 85367.36 | 30-JAN-05:00 | 375075.88 | 15-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.02 | 85367.36 | 30-JAN-05:00 | 375075.88 | 15-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 1294.59 | 0.00 | 01-JAN-00:40 | 1274776.93 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
EnergyTransfer:HVAC | 10818.96 | 3339.86 | 30-JAN-01:40 | 3033142.30 | 15-AUG-14:40 |
HeatingCoils:EnergyTransfer | 840.07 | 0.00 | 01-JAN-00:40 | 1268093.58 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 840.07 | 0.00 | 01-JAN-00:40 | 1268093.58 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 840.07 | 0.00 | 01-JAN-00:40 | 1268093.58 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 7842.77 | 2640.27 | 07-JAN-09:00 | 3033142.30 | 15-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 2021.97 | 0.00 | 01-JAN-00:10 | 727067.77 | 07-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 114.16 | 0.00 | 01-JAN-00:10 | 349030.47 | 15-JUL-14:00 |
EnergyTransfer:Plant | 15459.64 | 0.00 | 01-JAN-00:40 | 7789062.13 | 05-JUL-16:00 |
LoopToLoop:EnergyTransfer | 4542.13 | 0.00 | 01-JAN-00:10 | 2495423.53 | 05-JUL-16:00 |
WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:10 |
Boilers:EnergyTransfer | 835.77 | 0.00 | 01-JAN-00:40 | 1315873.58 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 4549.17 | 0.00 | 01-JAN-00:10 | 2434529.00 | 05-JUL-15:50 |
HeatRejection:EnergyTransfer | 5078.06 | 0.00 | 01-JAN-00:10 | 2829301.86 | 05-JUL-15:50 |
General:HeatRejection:EnergyTransfer | 5078.06 | 0.00 | 01-JAN-00:10 | 2829301.86 | 05-JUL-15:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -548.560 | 0.000 | 0.000 | 90.115 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -131.682 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -582.679 | 0.000 | 0.000 | 83.469 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 60.760 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_MID | 0.000 | 0.000 | 8.687 | -3853.532 | 0.000 | 0.000 | 854.143 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1393.792 |
CORE_TOP | 0.000 | 0.000 | 17.847 | -332.200 | 0.000 | 0.000 | 88.491 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -212.587 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.896 | -63.770 | 0.000 | 0.000 | 10.913 | 10.669 | 36.365 | 27.919 | 0.000 | 0.022 | 53.226 | 0.000 | -71.334 | 0.000 | -4.907 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.786 | -55.881 | 0.000 | 0.000 | 6.999 | 6.840 | 23.435 | 53.444 | 0.000 | 0.015 | 11.760 | 0.000 | -44.145 | 0.000 | -3.254 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.661 | -92.456 | 0.000 | 0.000 | 10.809 | 10.554 | 36.366 | 99.836 | 0.000 | 0.021 | 3.058 | 0.000 | -64.954 | 0.000 | -4.895 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.075 | -85.741 | 0.000 | 0.000 | 6.835 | 6.830 | 23.435 | 52.633 | 0.000 | 0.014 | 49.968 | 0.000 | -50.488 | 0.000 | -3.561 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 149.819 | -410.570 | 0.000 | 0.000 | 113.824 | 106.521 | 363.654 | 288.996 | 0.000 | 0.504 | 134.694 | 0.000 | -644.508 | 0.000 | -102.934 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 81.639 | -439.125 | 0.000 | 0.000 | 52.997 | 68.327 | 234.352 | 534.936 | 0.000 | 0.302 | 0.003 | 0.000 | -410.082 | 0.000 | -70.283 | -53.064 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 89.892 | -766.898 | 0.000 | 0.000 | 110.476 | 105.460 | 363.660 | 996.832 | 0.000 | 0.468 | 0.017 | 0.000 | -622.299 | 0.000 | -108.520 | -169.071 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 66.041 | -490.964 | 0.000 | 0.000 | 72.236 | 68.214 | 234.351 | 536.265 | 0.000 | 0.306 | 23.530 | 0.000 | -437.744 | 0.000 | -72.234 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 34.295 | -37.647 | 0.000 | 0.000 | 11.549 | 10.651 | 36.365 | 29.406 | 0.000 | 0.057 | 0.001 | 0.000 | -60.866 | 0.000 | -12.136 | -11.675 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 19.507 | -42.975 | 0.000 | 0.000 | 7.307 | 6.832 | 23.435 | 54.035 | 0.000 | 0.037 | 0.001 | 0.000 | -38.792 | 0.000 | -8.287 | -21.098 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 23.262 | -69.897 | 0.000 | 0.000 | 11.229 | 10.545 | 36.366 | 100.373 | 0.000 | 0.055 | 0.001 | 0.000 | -58.773 | 0.000 | -12.751 | -40.410 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 15.517 | -46.504 | 0.000 | 0.000 | 7.329 | 6.821 | 23.435 | 53.852 | 0.000 | 0.036 | 0.000 | 0.000 | -41.646 | 0.000 | -8.554 | -10.284 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -136.601 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.856 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.238 | -1161.991 | 0.000 | 0.000 | 9.521 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -427.837 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.890 | -105.567 | 0.000 | 0.000 | 0.957 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.787 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7156.018 | 0.000 | 0.000 | 20.485 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -406.935 |
GROUNDFLOOR_PLENUM | 4.498 | -49.145 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.037 | 55.085 | 0.000 | 0.000 | 0.000 | -10.476 | -0.000 |
MIDFLOOR_PLENUM | 140.116 | -280.637 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.715 | 315.589 | 0.000 | 0.000 | 0.000 | -175.783 | -0.003 |
TOPFLOOR_PLENUM | 47.792 | -45.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.046 | 16.009 | 0.000 | 0.000 | 0.000 | -18.588 | -0.000 |
Total Facility | 192.406 | -375.040 | 516.053 | -16479.576 | 0.000 | 0.000 | 1570.632 | 2461.162 | 14676.396 | 2828.528 | 0.000 | 2.634 | 723.702 | 0.000 | -2545.631 | 0.000 | -617.164 | -2954.099 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-AUG-06:11 | 0.00 | 0.00 | 0.00 | -109360.79 | 0.00 | 0.00 | 1273.58 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 89715.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 28-JUN-04:13 | 0.00 | 0.00 | 0.00 | -91540.87 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 85065.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-SEP-04:12 | 0.00 | 0.00 | 0.00 | -783177.72 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 718427.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 22-JUL-05:04 | 0.00 | 0.00 | 0.00 | -76611.32 | 0.00 | 0.00 | 835.86 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 67590.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-16:22 | 0.00 | 0.00 | 0.00 | -16109.11 | 0.00 | 0.00 | 41.60 | 43.94 | 720.18 | 4821.01 | 0.00 | 36.85 | 10445.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-07:51 | 0.00 | 0.00 | 0.00 | -24804.59 | 0.00 | 0.00 | 19.53 | 28.32 | 464.11 | 21212.84 | 0.00 | 0.00 | 3192.41 | 0.00 | -0.00 | 0.00 | -112.61 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:11 | 0.00 | 0.00 | 0.00 | -27597.83 | 0.00 | 0.00 | 33.22 | 43.94 | 720.19 | 26693.59 | 0.00 | 0.00 | 270.75 | 0.00 | -0.00 | 0.00 | -163.87 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -31449.87 | 0.00 | 0.00 | 15.78 | 28.32 | 464.11 | 18932.49 | 0.00 | 0.00 | 12074.95 | 0.00 | -0.00 | 0.00 | -65.78 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-16:31 | 0.00 | 0.00 | 0.00 | -139702.03 | 0.00 | 0.00 | 426.73 | 439.44 | 7201.84 | 44450.02 | 0.00 | 648.36 | 86535.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 11-JUN-10:01 | 0.00 | 0.00 | 0.00 | -255992.46 | 0.00 | 0.00 | 204.60 | 283.19 | 4641.14 | 128255.28 | 0.00 | 0.00 | 124396.77 | 0.00 | -0.00 | 0.00 | -1788.52 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-12:32 | 0.00 | 0.00 | 0.00 | -268755.95 | 0.00 | 0.00 | 340.47 | 439.45 | 7201.95 | 225966.74 | 0.00 | 0.00 | 37517.23 | 0.00 | -0.00 | 0.00 | -2709.89 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-17:01 | 0.00 | 0.00 | 0.00 | -303798.52 | 0.00 | 0.00 | 0.00 | 283.19 | 3603.49 | 210462.39 | 0.00 | 0.00 | 91167.98 | 0.00 | -0.00 | 0.00 | -1718.52 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -16615.25 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 5527.83 | 0.00 | 0.00 | 10617.73 | 0.00 | -0.00 | 0.00 | -133.42 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:22 | 0.00 | 0.00 | 0.00 | -24820.55 | 0.00 | 0.00 | 17.33 | 28.32 | 464.11 | 17736.57 | 0.00 | 0.00 | 6755.24 | 0.00 | -0.00 | 0.00 | -181.03 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-12:41 | 0.00 | 0.00 | 0.00 | -30074.49 | 0.00 | 0.00 | 31.32 | 43.94 | 720.19 | 26204.41 | 0.00 | 0.00 | 3591.07 | 0.00 | -0.00 | 0.00 | -516.45 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:01 | 0.00 | 0.00 | 0.00 | -31911.83 | 0.00 | 0.00 | 0.00 | 28.32 | 360.35 | 20948.22 | 0.00 | 0.00 | 10798.82 | 0.00 | -0.00 | 0.00 | -223.89 | 0.00 |
DATACENTER_BOT_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8244.25 | 0.00 | 0.00 | 10.62 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 333.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -79117.28 | 0.00 | 0.00 | 106.16 | 1055.42 | 77944.22 | 0.00 | 0.00 | 0.00 | 11.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7964.95 | 0.00 | 0.00 | 10.62 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 54.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-16:41 | 0.00 | 0.00 | 0.00 | -378560.04 | 0.00 | 0.00 | 665.66 | 2309.53 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4047.67 |
GROUNDFLOOR_PLENUM | 24-JUL-05:10 | 0.00 | -12843.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12849.08 | 0.00 | -0.00 | 0.00 | -5.20 | 0.00 |
MIDFLOOR_PLENUM | 21-FEB-04:11 | 0.00 | -102614.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140099.71 | 0.00 | -0.00 | 0.00 | -37485.64 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:40 | 0.00 | -18464.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.13 | 18330.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-05:03 | 0.00 | -28555.99 | 0.00 | -1805983.62 | 0.00 | 0.00 | 15998.46 | 10593.62 | 616289.16 | 0.00 | 0.00 | 0.00 | 1267843.12 | 0.00 | -73808.06 | 0.00 | -2376.68 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 490351.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -555101.42 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 73857.78 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -80332.76 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 11882.31 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7173.05 | 0.00 | -929.87 | -4592.43 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 11938.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4626.13 | 0.00 | -619.64 | -7216.45 |
PERIMETER_BOT_ZN_1 | 07-FEB-05:01 | 0.00 | 0.00 | 17663.47 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7105.26 | 0.00 | -938.30 | -10432.95 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 8780.86 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4989.35 | 0.00 | -645.88 | -3669.58 |
PERIMETER_MID_ZN_3 | 06-FEB-04:11 | 0.00 | 0.00 | 128606.92 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64648.81 | 0.00 | -18900.76 | -53187.68 |
PERIMETER_MID_ZN_2 | 13-FEB-04:01 | 0.00 | 0.00 | 182202.44 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33608.41 | 0.00 | -18272.98 | -135560.54 |
PERIMETER_MID_ZN_1 | 06-FEB-04:11 | 0.00 | 0.00 | 210153.41 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65404.90 | 0.00 | -19150.69 | -133728.26 |
PERIMETER_MID_ZN_4 | 06-FEB-04:11 | 0.00 | 0.00 | 181410.99 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43825.77 | 0.00 | -12900.09 | -129924.59 |
PERIMETER_TOP_ZN_3 | 06-FEB-03:42 | 0.00 | 0.00 | 15699.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6116.35 | 0.00 | -2250.62 | -8145.55 |
PERIMETER_TOP_ZN_2 | 06-FEB-03:42 | 0.00 | 0.00 | 21150.95 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3952.87 | 0.00 | -1544.93 | -16177.10 |
PERIMETER_TOP_ZN_1 | 06-FEB-03:42 | 0.00 | 0.00 | 24162.18 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6161.79 | 0.00 | -2296.51 | -16516.93 |
PERIMETER_TOP_ZN_4 | 06-FEB-03:42 | 0.00 | 0.00 | 22354.19 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4170.69 | 0.00 | -1574.57 | -17132.87 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-01:20 | 0.00 | 0.00 | 5497.74 | 0.00 | 0.00 | 0.00 | 0.00 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25159.71 |
DATACENTER_TOP_ZN_6 | 15-JAN-18:50 | 0.00 | 0.00 | 588.75 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2554.95 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 14-DEC-06:02 | 11749.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -94.45 | -11655.16 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 174586.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2398.20 | -172188.31 |
TOPFLOOR_PLENUM | 11-DEC-05:42 | 29319.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1086.15 | -28233.76 |
Total Facility | 02-JAN-05:21 | 19342.73 | 105293.32 | 1250513.95 | -105293.32 | 0.00 | 0.00 | 0.00 | 10593.62 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -146557.96 | 0.00 | -35431.27 | -1330886.30 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.7479 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2247 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 102.9317 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 85.9380 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.5715 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.4416 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1012 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1012 | 0.2353 | 1.0000 | Not calculated | 1.2002 | 0.2353 | ||
AIRLOOP DATACENTER BASEMENT | 25.0548 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.0550 | 0.0135 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.4938 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4938 | 0.0317 | 1.0000 | Not calculated | 0.0156 | 0.0317 | ||
AIRLOOP DATACENTER MID | 4.7360 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7360 | 0.0330 | 1.0000 | Not calculated | 0.1563 | 0.0330 | ||
AIRLOOP DATACENTER TOP | 0.4817 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4817 | 0.0325 | 1.0000 | Not calculated | 0.0156 | 0.0325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.3740 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2844 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 51.4658 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8285 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.2857 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2860 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.0548 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.0548 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.4938 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4938 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0317 | ||
AIRLOOP DATACENTER MID | 4.7360 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7360 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0330 | ||
AIRLOOP DATACENTER TOP | 0.4817 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4817 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.1012 | 5.1012 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5188 | 5.5188 | 1.6170 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 51.8033 | 51.8033 | 16.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1383 | 5.1383 | 1.6185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9329 | 0.9329 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2769 | 1.2769 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4574 | 1.4574 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5620 | 1.5620 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.7063 | 8.7063 | 2.0286 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.6392 | 13.6392 | 1.3094 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4641 | 14.4641 | 2.0250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.3188 | 14.3188 | 1.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9896 | 0.9896 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3752 | 1.3752 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5579 | 1.5579 | 0.2025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5105 | 1.5105 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4938 | 0.4938 | 0.4938 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7360 | 4.7360 | 4.7360 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4817 | 0.4817 | 0.4817 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.0548 | 25.0548 | 25.0548 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.7479 | 9.2247 | 10.7479 | 2.2844 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 102.9317 | 85.9380 | 102.9317 | 22.8285 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.5715 | 9.4416 | 10.5715 | 2.2860 | 0.0000 | 1.0000 |
CAV_BAS | 5.1012 | 5.1012 | 5.1012 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.0548 | 25.0550 | 25.0548 | 25.0548 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4938 | 0.4938 | 0.4938 | 0.4938 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7360 | 4.7360 | 4.7360 | 4.7360 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4817 | 0.4817 | 0.4817 | 0.4817 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7594 | 2.7594 | 1.6170 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.9016 | 25.9016 | 16.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5691 | 2.5691 | 1.6185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4664 | 0.4664 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6384 | 0.6384 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7287 | 0.7287 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7810 | 0.7810 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3531 | 4.3531 | 2.0286 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8196 | 6.8196 | 1.3094 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2320 | 7.2320 | 2.0250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1594 | 7.1594 | 1.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4948 | 0.4948 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6876 | 0.6876 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7789 | 0.7789 | 0.2025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7553 | 0.7553 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4938 | 0.4938 | 0.4938 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7360 | 4.7360 | 4.7360 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4817 | 0.4817 | 0.4817 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.0548 | 25.0548 | 25.0548 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.3740 | 2.2844 | 2.2844 | 2.2844 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 51.4658 | 22.8285 | 22.8285 | 22.8285 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.2857 | 2.2860 | 2.2860 | 2.2860 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.0548 | 25.0548 | 25.0548 | 25.0548 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4938 | 0.4938 | 0.4938 | 0.4938 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7360 | 4.7360 | 4.7360 | 4.7360 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4817 | 0.4817 | 0.4817 | 0.4817 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 82.50 |
Number of hours cooling loads not met | 986.50 |
Number of hours not met | 1027.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1151.06 | 1582955.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1396.53 | 528085.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2461.16 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 353.28 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2360.91 | 274878.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 346.74 | 48849.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 477.95 | 79472.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1463.05 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 36.73 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 459.85 | 56293.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26598.87 |
Natural Gas | 0.00 | 1151.06 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27749.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.13 |
Space Heating | 0.00 |
Space Cooling | 30.15 |
Fans (All) | 50.97 |
Service Water Heating | 9.93 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 574.24 |
Subtotal | 574.24 |
Natural Gas [MJ/m2] | |
Space Heating | 24.85 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 24.85 |
Subtotal | 24.85 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.87 |
Space Heating | 4.15 |
Space Cooling | 5.03 |
Fans (All) | 8.51 |
Service Water Heating | 1.66 |
Receptacle Equipment | 52.89 |
Miscellaneous | 18.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 751. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7636.33 | 785.17 | 234.33 | 104.17 | 0.00 |
CORE_BOTTOM | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8679.17 | 80.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8295.83 | 464.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8661.00 | 99.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8679.17 | 80.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8522.00 | 238.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8731.17 | 28.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8653.83 | 106.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8668.67 | 91.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8525.33 | 234.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7833.67 | 926.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7818.00 | 942.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7802.83 | 957.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6643.83 | 2113.00 | 3.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8664.00 | 96.00 | 0.00 | 0.00 | 0.00 |
Min | 6643.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2113.00 | 234.33 | 104.17 | 0.00 |
Average | 8423.32 | 321.83 | 10.33 | 4.53 | 0.00 |
Sum | 193736.33 | 7402.00 | 237.50 | 104.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 338308.67 | 13953.33 | 8841.17 | 7512.83 | 0.00 |
CORE_BOTTOM | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1759.17 | 508.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1746.00 | 522.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1736.00 | 532.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 78851.33 | 24539.33 | 4.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 338308.67 | 24539.33 | 8841.17 | 7512.83 | 0.00 |
Average | 77881.75 | 1741.93 | 384.59 | 326.64 | 0.00 |
Sum | 1791280.17 | 40064.50 | 8845.50 | 7512.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7433.83 | 990.83 | 172.00 | 163.33 | 0.00 |
CORE_BOTTOM | 8177.00 | 583.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8269.83 | 490.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8253.33 | 506.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8247.50 | 512.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8280.67 | 479.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8212.00 | 548.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7901.50 | 858.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8255.83 | 504.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8183.17 | 576.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8191.83 | 568.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8085.00 | 675.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8261.17 | 498.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8193.83 | 566.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8203.33 | 556.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8103.17 | 656.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8347.33 | 412.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8328.33 | 431.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8326.67 | 433.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6868.17 | 1891.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8107.00 | 653.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8156.17 | 603.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7882.67 | 877.33 | 0.00 | 0.00 | 0.00 |
Min | 6868.17 | 412.67 | 0.00 | 0.00 | 0.00 |
Max | 8347.33 | 1891.83 | 172.00 | 163.33 | 0.00 |
Average | 8098.67 | 646.75 | 7.48 | 7.10 | 0.00 |
Sum | 186269.33 | 14875.33 | 172.00 | 163.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 336786.17 | 15996.00 | 6433.17 | 9400.67 | 0.00 |
CORE_BOTTOM | 329715.33 | 1097.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330086.00 | 727.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329985.00 | 828.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38923.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.17 | 0.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1996.17 | 271.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1982.83 | 285.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1981.17 | 286.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81230.67 | 22164.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 336786.17 | 22164.33 | 6433.17 | 9400.67 | 0.00 |
Average | 77835.04 | 1811.45 | 279.70 | 408.72 | 0.00 |
Sum | 1790205.83 | 41663.33 | 6433.17 | 9400.67 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:29
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366165E+11 | 95466.94 | 02-JAN-07:03 | -1.1 | -1.7 | 0.567059E+10 | 7499.30 | 11-JAN-10:09 | 7.98 | 6.90 |
February | 0.343449E+11 | 95269.64 | 21-FEB-07:03 | -13.9 | -14.7 | 0.514447E+10 | 7499.25 | 01-FEB-10:20 | -13.9 | -14.7 |
March | 0.468002E+11 | 94908.78 | 16-MAR-06:12 | 11.67 | 10.33 | 0.614718E+10 | 7499.41 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.465160E+11 | 97142.47 | 24-APR-06:03 | 1.38 | 0.25 | 0.546618E+10 | 7499.30 | 12-APR-13:09 | 1.38 | 0.25 |
May | 0.482391E+11 | 100437.07 | 30-MAY-06:11 | 12.20 | 11.93 | 0.594553E+10 | 9744.98 | 17-MAY-09:00 | 12.20 | 11.93 |
June | 0.451004E+11 | 103603.03 | 13-JUN-06:05 | 8.80 | 7.96 | 0.646468E+10 | 11462.71 | 27-JUN-13:00 | 27.20 | 22.77 |
July | 0.399046E+11 | 106495.86 | 12-JUL-06:11 | 14.83 | 11.88 | 0.648485E+10 | 11930.13 | 21-JUL-13:00 | 31.70 | 21.73 |
August | 0.521446E+11 | 109450.30 | 09-AUG-06:11 | 17.77 | 14.04 | 0.682268E+10 | 11899.30 | 15-AUG-13:00 | 26.10 | 22.23 |
September | 0.509019E+11 | 108406.19 | 18-SEP-06:11 | 10.57 | 9.34 | 0.561268E+10 | 10417.70 | 14-SEP-08:39 | 10.57 | 9.34 |
October | 0.533378E+11 | 105165.75 | 10-OCT-06:11 | 10.20 | 8.82 | 0.569466E+10 | 7499.33 | 27-OCT-13:09 | 9.78 | 7.31 |
November | 0.503463E+11 | 98739.53 | 13-NOV-07:05 | 6.20 | 5.12 | 0.563457E+10 | 7499.39 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.443201E+11 | 98729.88 | 26-DEC-07:03 | -12.3 | -13.4 | 0.548377E+10 | 7499.18 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.548573E+12 | 0.705718E+11 | ||||||||
Minimum of Months | 0.343449E+11 | 94908.78 | -13.9 | -14.7 | 0.514447E+10 | 7499.18 | -13.9 | -14.7 | ||
Maximum of Months | 0.533378E+11 | 109450.30 | 17.77 | 14.04 | 0.682268E+10 | 11930.13 | 31.70 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294439E+11 | 74601.69 | 17-JAN-06:01 | 7.20 | 2.95 | 0.503396E+10 | 6748.38 | 17-JAN-10:50 | 6.97 | 4.36 |
February | 0.287002E+11 | 76431.62 | 24-FEB-06:02 | -7.2 | -8.2 | 0.458099E+10 | 6734.82 | 06-FEB-10:20 | -7.2 | -8.2 |
March | 0.447490E+11 | 80819.06 | 15-MAR-04:12 | 15.00 | 11.89 | 0.549659E+10 | 6734.93 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.492160E+11 | 86045.33 | 10-APR-04:12 | 3.50 | 2.94 | 0.488356E+10 | 6734.82 | 19-APR-09:20 | 9.07 | 6.91 |
May | 0.485220E+11 | 88340.68 | 30-MAY-04:12 | 12.20 | 11.68 | 0.528672E+10 | 6734.89 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.601643E+11 | 91565.91 | 28-JUN-04:13 | 17.60 | 15.52 | 0.527074E+10 | 6735.16 | 22-JUN-13:09 | 17.60 | 15.52 |
July | 0.706143E+11 | 88999.17 | 12-JUL-04:13 | 12.93 | 10.99 | 0.489838E+10 | 6759.91 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.741769E+11 | 84482.61 | 31-AUG-04:13 | 11.50 | 11.15 | 0.549863E+10 | 6812.49 | 03-AUG-13:30 | 11.50 | 11.15 |
September | 0.502626E+11 | 89448.97 | 05-SEP-04:12 | 6.70 | 6.07 | 0.488384E+10 | 6735.20 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.464437E+11 | 85853.16 | 23-OCT-04:12 | 12.77 | 10.74 | 0.507938E+10 | 6734.78 | 10-OCT-09:20 | 12.77 | 10.74 |
November | 0.432269E+11 | 86960.57 | 13-NOV-05:11 | 5.57 | 4.40 | 0.503077E+10 | 6734.89 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.371606E+11 | 80588.25 | 18-DEC-05:01 | 1.70 | 0.81 | 0.489642E+10 | 6734.79 | 12-DEC-10:20 | 1.70 | 0.81 |
Annual Sum or Average | 0.582681E+12 | 0.608400E+11 | ||||||||
Minimum of Months | 0.287002E+11 | 74601.69 | -7.2 | -8.2 | 0.458099E+10 | 6734.78 | -7.2 | -8.2 | ||
Maximum of Months | 0.741769E+11 | 91565.91 | 17.60 | 15.52 | 0.549863E+10 | 6812.49 | 23.90 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186216E+11 | 19194.39 | 25-JAN-11:10 | -7.1 | -7.8 | 0.441889E+10 | 6695.41 | 20-JAN-14:00 | -7.1 | -7.8 |
February | 0.180765E+11 | 19084.65 | 03-FEB-09:00 | -7.8 | -8.7 | 0.408278E+10 | 6734.52 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.277406E+11 | 73671.05 | 17-MAR-05:02 | 10.50 | 9.94 | 0.535055E+10 | 6734.87 | 16-MAR-13:00 | 10.50 | 9.94 |
April | 0.302231E+11 | 70875.89 | 27-APR-05:03 | 5.00 | 3.27 | 0.483862E+10 | 6876.51 | 10-APR-13:50 | 5.00 | 3.27 |
May | 0.386212E+11 | 76302.41 | 30-MAY-04:12 | 12.20 | 11.68 | 0.527553E+10 | 6734.89 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.442619E+11 | 76161.75 | 29-JUN-04:11 | 19.80 | 17.63 | 0.526402E+10 | 6735.15 | 22-JUN-13:09 | 19.80 | 17.63 |
July | 0.453721E+11 | 77139.98 | 25-JUL-04:11 | 15.00 | 13.80 | 0.489263E+10 | 6734.81 | 03-JUL-13:30 | 15.00 | 13.80 |
August | 0.473400E+11 | 76597.13 | 01-AUG-04:11 | 12.23 | 11.69 | 0.549467E+10 | 6735.15 | 02-AUG-13:09 | 23.90 | 16.41 |
September | 0.389583E+11 | 78339.64 | 18-SEP-04:12 | 10.20 | 9.28 | 0.487398E+10 | 6735.20 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.311082E+11 | 74368.67 | 13-OCT-05:02 | 10.50 | 10.16 | 0.503739E+10 | 6750.32 | 27-OCT-09:30 | 7.20 | 5.20 |
November | 0.248931E+11 | 68453.56 | 01-NOV-05:02 | 5.68 | 3.03 | 0.493195E+10 | 6737.99 | 06-NOV-10:20 | 8.17 | 4.21 |
December | 0.201379E+11 | 23641.53 | 01-DEC-17:00 | 7.20 | 4.89 | 0.443313E+10 | 6734.73 | 01-DEC-10:09 | 7.20 | 4.89 |
Annual Sum or Average | 0.385354E+12 | 0.588941E+11 | ||||||||
Minimum of Months | 0.180765E+11 | 19084.65 | -7.8 | -8.7 | 0.408278E+10 | 6695.41 | -7.1 | -7.8 | ||
Maximum of Months | 0.473400E+11 | 78339.64 | 19.80 | 17.63 | 0.549467E+10 | 6876.51 | 23.90 | 17.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117822E+11 | 14300.52 | 12-JAN-17:00 | -6.7 | -8.2 | 0.394848E+10 | 6009.70 | 12-JAN-14:00 | -6.7 | -8.2 |
February | 0.121038E+11 | 14845.84 | 28-FEB-14:10 | 0.00 | -3.0 | 0.366578E+10 | 6164.98 | 17-FEB-14:00 | 0.00 | -3.0 |
March | 0.210889E+11 | 71641.12 | 16-MAR-05:02 | 14.03 | 11.42 | 0.486809E+10 | 6734.85 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.238950E+11 | 35983.03 | 21-APR-16:00 | 13.30 | 8.77 | 0.461313E+10 | 6749.36 | 11-APR-13:09 | 13.30 | 8.77 |
May | 0.346709E+11 | 70725.03 | 17-MAY-05:02 | 16.05 | 11.54 | 0.522264E+10 | 6734.90 | 10-MAY-09:09 | 16.05 | 11.54 |
June | 0.447026E+11 | 75064.15 | 19-JUN-04:12 | 16.70 | 15.97 | 0.525608E+10 | 6735.15 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.479249E+11 | 76635.19 | 22-JUL-05:04 | 21.10 | 20.28 | 0.489427E+10 | 6734.76 | 12-JUL-09:00 | 21.10 | 20.28 |
August | 0.477503E+11 | 74842.92 | 01-AUG-04:11 | 12.23 | 11.69 | 0.549207E+10 | 6735.14 | 02-AUG-13:09 | 23.90 | 16.41 |
September | 0.350242E+11 | 74871.31 | 18-SEP-04:12 | 10.20 | 9.28 | 0.483991E+10 | 6735.16 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.234089E+11 | 67473.44 | 13-OCT-05:02 | 10.50 | 10.16 | 0.475954E+10 | 6734.73 | 12-OCT-09:20 | 10.50 | 10.16 |
November | 0.170902E+11 | 23577.45 | 01-NOV-16:00 | 9.40 | 6.91 | 0.439960E+10 | 6734.79 | 16-NOV-14:30 | 17.20 | 13.27 |
December | 0.127604E+11 | 15211.66 | 01-DEC-17:00 | 7.20 | 4.89 | 0.385766E+10 | 6302.65 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.332202E+12 | 0.558173E+11 | ||||||||
Minimum of Months | 0.117822E+11 | 14300.52 | -6.7 | -8.2 | 0.366578E+10 | 6009.70 | -6.7 | -8.2 | ||
Maximum of Months | 0.479249E+11 | 76635.19 | 21.10 | 20.28 | 0.549207E+10 | 6749.36 | 23.90 | 20.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139520E+10 | 2193.99 | 17-JAN-06:02 | 7.20 | 2.95 | 0.504090E+09 | 787.81 | 17-JAN-14:00 | 6.70 | 5.64 |
February | 0.151202E+10 | 2093.73 | 23-FEB-06:03 | 2.30 | 1.81 | 0.475940E+09 | 806.05 | 22-FEB-14:00 | 2.30 | 1.81 |
March | 0.335518E+10 | 7631.35 | 15-MAR-14:00 | 26.10 | 16.06 | 0.640047E+09 | 845.65 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.441734E+10 | 6878.56 | 07-APR-13:30 | 20.00 | 10.05 | 0.601698E+09 | 845.63 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.588281E+10 | 8733.79 | 17-MAY-05:02 | 16.05 | 11.54 | 0.660368E+09 | 845.64 | 10-MAY-09:09 | 16.05 | 11.54 |
June | 0.944453E+10 | 15780.79 | 11-JUN-18:41 | 24.08 | 17.29 | 0.662020E+09 | 845.82 | 27-JUN-13:00 | 27.20 | 22.77 |
July | 0.116469E+11 | 16112.57 | 16-JUL-16:22 | 28.90 | 21.75 | 0.616033E+09 | 849.27 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.112438E+11 | 15622.46 | 06-AUG-16:21 | 27.80 | 18.95 | 0.690759E+09 | 866.40 | 03-AUG-13:30 | 27.80 | 18.95 |
September | 0.610119E+10 | 11642.57 | 15-SEP-05:02 | 18.30 | 16.87 | 0.610461E+09 | 845.69 | 12-SEP-13:09 | 18.30 | 16.87 |
October | 0.395634E+10 | 6362.21 | 23-OCT-05:03 | 11.70 | 9.96 | 0.622496E+09 | 845.63 | 10-OCT-09:20 | 11.70 | 9.96 |
November | 0.285037E+10 | 4692.97 | 27-NOV-12:00 | 15.00 | 10.52 | 0.601293E+09 | 845.64 | 16-NOV-14:09 | 15.00 | 10.52 |
December | 0.196411E+10 | 2753.88 | 01-DEC-13:10 | 12.97 | 11.34 | 0.520679E+09 | 845.58 | 01-DEC-14:39 | 7.57 | 6.05 |
Annual Sum or Average | 0.637698E+11 | 0.720588E+10 | ||||||||
Minimum of Months | 0.139520E+10 | 2093.73 | 2.30 | 1.81 | 0.475940E+09 | 787.81 | 2.30 | 1.81 | ||
Maximum of Months | 0.116469E+11 | 16112.57 | 28.90 | 21.75 | 0.690759E+09 | 866.40 | 27.80 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.974984E+09 | 1764.99 | 12-JAN-10:05 | -9.8 | -12.2 | 0.336940E+09 | 544.95 | 06-JAN-10:50 | -9.8 | -12.2 |
February | 0.110875E+10 | 6143.57 | 28-FEB-09:35 | -5.2 | -6.5 | 0.319869E+09 | 544.95 | 17-FEB-10:20 | -5.2 | -6.5 |
March | 0.290647E+10 | 9201.90 | 21-MAR-08:55 | 1.70 | -0.5 | 0.426635E+09 | 544.97 | 14-MAR-09:50 | 1.70 | -0.5 |
April | 0.441242E+10 | 16101.26 | 23-APR-10:32 | 14.80 | 7.30 | 0.389480E+09 | 545.76 | 24-APR-09:09 | 6.28 | 2.92 |
May | 0.619058E+10 | 18246.37 | 07-MAY-07:33 | 8.90 | 6.12 | 0.426479E+09 | 545.67 | 31-MAY-09:39 | 18.13 | 13.58 |
June | 0.857635E+10 | 23682.58 | 11-JUN-08:41 | 23.03 | 15.86 | 0.427011E+09 | 546.16 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.100193E+11 | 24818.55 | 04-JUL-07:51 | 21.10 | 17.80 | 0.397329E+09 | 549.21 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.928149E+10 | 21814.50 | 06-AUG-09:01 | 24.18 | 17.35 | 0.445180E+09 | 553.12 | 09-AUG-09:00 | 25.60 | 18.67 |
September | 0.593876E+10 | 22114.95 | 10-SEP-08:12 | 13.67 | 10.66 | 0.394224E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.342493E+10 | 11049.97 | 11-OCT-08:50 | 14.53 | 11.11 | 0.403724E+09 | 544.96 | 03-OCT-09:00 | 14.53 | 11.11 |
November | 0.194209E+10 | 6576.78 | 03-NOV-08:55 | 3.90 | 1.83 | 0.382956E+09 | 544.96 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.110458E+10 | 3619.18 | 04-DEC-09:50 | -1.8 | -3.7 | 0.328470E+09 | 544.95 | 04-DEC-10:39 | -1.3 | -3.6 |
Annual Sum or Average | 0.558807E+11 | 0.467830E+10 | ||||||||
Minimum of Months | 0.974984E+09 | 1764.99 | -9.8 | -12.2 | 0.319869E+09 | 544.95 | -9.8 | -12.2 | ||
Maximum of Months | 0.100193E+11 | 24818.55 | 24.18 | 17.80 | 0.445180E+09 | 553.12 | 27.80 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246528E+10 | 24096.96 | 15-JAN-13:53 | 5.00 | 2.25 | 0.543238E+09 | 845.69 | 12-JAN-14:09 | 5.00 | 2.25 |
February | 0.281140E+10 | 17297.88 | 28-FEB-13:20 | 0.00 | -2.8 | 0.511142E+09 | 846.16 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.660476E+10 | 19020.78 | 15-MAR-13:30 | 25.55 | 15.84 | 0.661486E+09 | 847.29 | 14-MAR-13:00 | 25.55 | 15.84 |
April | 0.704292E+10 | 20694.66 | 23-APR-14:32 | 15.20 | 9.59 | 0.599627E+09 | 846.60 | 24-APR-13:00 | 12.80 | 6.89 |
May | 0.808216E+10 | 24643.34 | 14-MAY-13:13 | 24.27 | 17.84 | 0.659117E+09 | 845.67 | 10-MAY-13:09 | 24.27 | 17.84 |
June | 0.109735E+11 | 24329.45 | 25-JUN-13:02 | 26.10 | 17.26 | 0.661799E+09 | 845.71 | 22-JUN-13:09 | 26.10 | 17.26 |
July | 0.137828E+11 | 25284.44 | 16-JUL-15:41 | 30.40 | 23.08 | 0.616364E+09 | 849.97 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.148269E+11 | 26085.88 | 27-AUG-13:22 | 23.60 | 18.96 | 0.691358E+09 | 939.75 | 03-AUG-13:30 | 23.60 | 18.96 |
September | 0.108380E+11 | 27594.25 | 10-SEP-12:11 | 16.87 | 10.71 | 0.611805E+09 | 858.66 | 21-SEP-13:30 | 25.30 | 16.56 |
October | 0.782230E+10 | 24692.50 | 22-OCT-12:53 | 21.70 | 14.82 | 0.626207E+09 | 912.80 | 31-OCT-13:09 | 15.00 | 10.18 |
November | 0.460755E+10 | 18246.11 | 03-NOV-12:30 | 8.35 | 4.56 | 0.596655E+09 | 846.97 | 15-NOV-14:50 | 11.60 | 6.55 |
December | 0.259907E+10 | 16985.61 | 17-DEC-11:33 | 1.50 | -0.3 | 0.532108E+09 | 845.64 | 11-DEC-14:20 | 1.50 | -0.3 |
Annual Sum or Average | 0.924566E+11 | 0.731091E+10 | ||||||||
Minimum of Months | 0.246528E+10 | 16985.61 | 0.00 | -2.8 | 0.511142E+09 | 845.64 | 0.00 | -2.8 | ||
Maximum of Months | 0.148269E+11 | 27594.25 | 30.40 | 23.08 | 0.691358E+09 | 939.75 | 26.10 | 18.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141050E+10 | 4698.28 | 12-JAN-15:40 | -5.9 | -8.2 | 0.357607E+09 | 544.95 | 17-JAN-14:50 | 6.52 | 5.42 |
February | 0.191494E+10 | 9567.37 | 28-FEB-16:30 | 0.00 | -2.6 | 0.346123E+09 | 544.95 | 22-FEB-14:50 | 0.00 | -2.6 |
March | 0.561475E+10 | 19058.94 | 26-MAR-16:22 | -1.7 | -4.7 | 0.441334E+09 | 544.98 | 16-MAR-13:00 | -1.7 | -4.7 |
April | 0.824609E+10 | 27168.38 | 02-APR-16:22 | 7.50 | 5.68 | 0.395986E+09 | 544.97 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.786707E+10 | 30065.42 | 07-MAY-16:11 | 15.00 | 5.96 | 0.428464E+09 | 544.97 | 10-MAY-09:09 | 18.68 | 14.82 |
June | 0.120048E+11 | 31453.37 | 11-JUN-16:41 | 25.60 | 17.82 | 0.427857E+09 | 545.00 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.140105E+11 | 31342.55 | 16-JUL-16:21 | 28.90 | 21.75 | 0.398364E+09 | 547.86 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.150724E+11 | 31309.21 | 06-AUG-16:21 | 27.80 | 18.95 | 0.446643E+09 | 552.49 | 16-AUG-13:20 | 25.20 | 15.34 |
September | 0.744766E+10 | 28565.40 | 10-SEP-17:31 | 16.10 | 10.54 | 0.395789E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.539358E+10 | 17785.31 | 09-OCT-16:33 | 12.97 | 9.03 | 0.410214E+09 | 544.96 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.404880E+10 | 15422.75 | 27-NOV-05:12 | 17.97 | 12.28 | 0.405934E+09 | 544.97 | 16-NOV-14:09 | 17.97 | 12.28 |
December | 0.271009E+10 | 9006.41 | 14-DEC-06:02 | 5.68 | 5.18 | 0.387785E+09 | 544.95 | 12-DEC-14:30 | 5.68 | 5.18 |
Annual Sum or Average | 0.857411E+11 | 0.484210E+10 | ||||||||
Minimum of Months | 0.141050E+10 | 4698.28 | -5.9 | -8.2 | 0.346123E+09 | 544.95 | -1.7 | -4.7 | ||
Maximum of Months | 0.150724E+11 | 31453.37 | 28.90 | 21.75 | 0.446643E+09 | 552.49 | 25.20 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137616E+09 | 1372.35 | 11-JAN-17:00 | 11.10 | 9.84 | 0.464876E+09 | 632.09 | 11-JAN-14:00 | 11.10 | 9.84 |
February | 0.221798E+09 | 1413.87 | 17-FEB-15:00 | 3.30 | 1.08 | 0.422957E+09 | 658.64 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.167977E+10 | 5998.96 | 15-MAR-14:00 | 26.10 | 16.06 | 0.563896E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.245714E+10 | 4588.61 | 07-APR-13:50 | 20.00 | 10.11 | 0.547852E+09 | 845.63 | 20-APR-13:20 | 12.97 | 9.40 |
May | 0.447244E+10 | 7075.61 | 23-MAY-14:40 | 23.90 | 13.32 | 0.648702E+09 | 845.64 | 10-MAY-09:09 | 23.90 | 13.32 |
June | 0.729915E+10 | 13443.28 | 11-JUN-18:41 | 24.08 | 17.29 | 0.660098E+09 | 846.65 | 27-JUN-13:20 | 29.47 | 23.48 |
July | 0.834608E+10 | 13972.79 | 16-JUL-16:31 | 28.33 | 21.22 | 0.615365E+09 | 846.57 | 27-JUL-13:20 | 29.40 | 21.64 |
August | 0.765742E+10 | 10340.83 | 11-AUG-05:03 | 17.80 | 15.36 | 0.688744E+09 | 846.48 | 15-AUG-13:20 | 27.23 | 22.54 |
September | 0.462000E+10 | 7604.32 | 14-SEP-05:03 | 20.60 | 19.14 | 0.600734E+09 | 845.68 | 12-SEP-13:09 | 20.60 | 19.14 |
October | 0.250974E+10 | 4215.76 | 12-OCT-14:40 | 18.30 | 15.11 | 0.569512E+09 | 845.62 | 06-OCT-13:39 | 18.30 | 15.11 |
November | 0.141758E+10 | 2241.39 | 07-NOV-10:00 | 2.80 | 1.42 | 0.503282E+09 | 814.69 | 16-NOV-14:00 | 17.20 | 13.27 |
December | 0.238562E+09 | 1635.70 | 01-DEC-13:30 | 11.10 | 9.57 | 0.450975E+09 | 711.07 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.410573E+11 | 0.673699E+10 | ||||||||
Minimum of Months | 0.137616E+09 | 1372.35 | 2.80 | 1.08 | 0.422957E+09 | 632.09 | 3.30 | 1.08 | ||
Maximum of Months | 0.834608E+10 | 13972.79 | 28.33 | 21.22 | 0.688744E+09 | 846.65 | 29.47 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158408E+09 | 1379.93 | 06-JAN-09:55 | -7.2 | -8.7 | 0.219731E+09 | 452.46 | 06-JAN-11:09 | -5.3 | -7.0 |
February | 0.269962E+09 | 4094.80 | 28-FEB-11:05 | -2.0 | -4.1 | 0.207542E+09 | 548.48 | 28-FEB-11:09 | -2.0 | -4.1 |
March | 0.167428E+10 | 8820.38 | 21-MAR-10:05 | 2.88 | 0.57 | 0.291572E+09 | 548.51 | 14-MAR-10:09 | 2.88 | 0.57 |
April | 0.327243E+10 | 17112.54 | 23-APR-10:32 | 14.80 | 7.30 | 0.277310E+09 | 548.51 | 07-APR-12:09 | 14.80 | 7.30 |
May | 0.556596E+10 | 18423.83 | 21-MAY-09:12 | 16.50 | 11.82 | 0.312007E+09 | 548.51 | 26-MAY-10:09 | 18.98 | 12.55 |
June | 0.783886E+10 | 25602.51 | 11-JUN-10:01 | 24.50 | 16.94 | 0.314586E+09 | 548.52 | 22-JUN-12:09 | 19.18 | 13.72 |
July | 0.869200E+10 | 24752.49 | 09-JUL-08:12 | 20.77 | 17.49 | 0.294174E+09 | 548.52 | 12-JUL-10:09 | 20.87 | 14.79 |
August | 0.795686E+10 | 23258.94 | 20-AUG-09:42 | 20.40 | 14.16 | 0.328057E+09 | 548.61 | 17-AUG-10:09 | 20.40 | 14.16 |
September | 0.518081E+10 | 21265.43 | 04-SEP-09:02 | 16.88 | 13.13 | 0.288642E+09 | 548.53 | 12-SEP-12:09 | 20.68 | 15.09 |
October | 0.227149E+10 | 10814.20 | 11-OCT-10:05 | 17.15 | 12.50 | 0.286280E+09 | 549.13 | 16-OCT-10:09 | 7.20 | 4.92 |
November | 0.874424E+09 | 5985.88 | 03-NOV-10:05 | 5.78 | 3.09 | 0.248984E+09 | 548.49 | 16-NOV-13:09 | 18.62 | 13.01 |
December | 0.157192E+09 | 1123.55 | 01-DEC-13:10 | 12.97 | 11.34 | 0.213116E+09 | 474.74 | 04-DEC-11:09 | -0.9 | -3.4 |
Annual Sum or Average | 0.439127E+11 | 0.328200E+10 | ||||||||
Minimum of Months | 0.157192E+09 | 1123.55 | -7.2 | -8.7 | 0.207542E+09 | 452.46 | -5.3 | -7.0 | ||
Maximum of Months | 0.869200E+10 | 25602.51 | 24.50 | 17.49 | 0.328057E+09 | 549.13 | 20.87 | 15.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157780E+10 | 17399.86 | 15-JAN-13:23 | 4.70 | 2.09 | 0.510698E+09 | 845.71 | 12-JAN-14:09 | 4.70 | 2.09 |
February | 0.202033E+10 | 18210.59 | 28-FEB-13:40 | 0.00 | -2.9 | 0.475967E+09 | 845.72 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.559692E+10 | 19323.81 | 01-MAR-13:50 | -0.1 | -2.5 | 0.633554E+09 | 866.56 | 01-MAR-10:39 | -0.1 | -2.5 |
April | 0.564227E+10 | 21962.05 | 23-APR-14:32 | 15.20 | 9.59 | 0.577166E+09 | 846.65 | 21-APR-13:20 | 15.20 | 9.59 |
May | 0.733961E+10 | 24723.18 | 14-MAY-13:23 | 24.45 | 17.92 | 0.651884E+09 | 845.67 | 19-MAY-13:30 | 15.85 | 9.67 |
June | 0.935115E+10 | 24232.81 | 11-JUN-15:21 | 25.85 | 18.02 | 0.659530E+09 | 847.14 | 12-JUN-13:20 | 29.80 | 19.89 |
July | 0.109740E+11 | 24941.68 | 30-JUL-12:32 | 25.60 | 19.52 | 0.615830E+09 | 847.23 | 19-JUL-13:20 | 25.60 | 19.52 |
August | 0.119379E+11 | 25474.50 | 27-AUG-12:32 | 22.93 | 18.66 | 0.690108E+09 | 886.85 | 03-AUG-13:30 | 22.93 | 18.66 |
September | 0.103269E+11 | 26875.01 | 03-SEP-12:32 | 19.03 | 12.28 | 0.608442E+09 | 891.30 | 21-SEP-13:39 | 25.40 | 16.58 |
October | 0.704633E+10 | 24653.79 | 22-OCT-13:02 | 21.70 | 14.72 | 0.613956E+09 | 962.67 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.357456E+10 | 19280.53 | 03-NOV-12:30 | 8.35 | 4.56 | 0.554900E+09 | 847.19 | 06-NOV-10:20 | 8.17 | 4.21 |
December | 0.130255E+10 | 12762.79 | 04-DEC-11:50 | -0.2 | -2.9 | 0.480168E+09 | 845.65 | 11-DEC-14:30 | -8.1 | -9.1 |
Annual Sum or Average | 0.766903E+11 | 0.707220E+10 | ||||||||
Minimum of Months | 0.130255E+10 | 12762.79 | -0.2 | -2.9 | 0.475967E+09 | 845.65 | -8.1 | -9.1 | ||
Maximum of Months | 0.119379E+11 | 26875.01 | 25.85 | 19.52 | 0.690108E+09 | 962.67 | 29.80 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266169E+09 | 1614.76 | 12-JAN-15:50 | -6.0 | -8.3 | 0.305242E+09 | 521.18 | 12-JAN-16:30 | -6.4 | -8.3 |
February | 0.481012E+09 | 6135.30 | 28-FEB-16:30 | 0.00 | -2.6 | 0.283313E+09 | 544.91 | 28-FEB-14:00 | 0.00 | -2.6 |
March | 0.220515E+10 | 9137.18 | 21-MAR-16:00 | 4.40 | 1.34 | 0.388767E+09 | 544.97 | 16-MAR-13:00 | 4.40 | 1.34 |
April | 0.351863E+10 | 24082.70 | 02-APR-16:11 | 7.77 | 5.85 | 0.370272E+09 | 544.96 | 20-APR-13:30 | 13.05 | 9.56 |
May | 0.591821E+10 | 25120.69 | 07-MAY-16:32 | 15.00 | 5.92 | 0.422747E+09 | 544.96 | 10-MAY-09:09 | 18.68 | 14.82 |
June | 0.888246E+10 | 28912.02 | 11-JUN-16:41 | 25.60 | 17.82 | 0.426496E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.928912E+10 | 30376.78 | 02-JUL-17:01 | 24.82 | 16.94 | 0.397561E+09 | 544.98 | 03-JUL-13:30 | 25.00 | 16.74 |
August | 0.884337E+10 | 26139.43 | 27-AUG-16:31 | 22.57 | 18.97 | 0.445435E+09 | 545.00 | 02-AUG-13:09 | 22.57 | 18.97 |
September | 0.538282E+10 | 24839.14 | 04-SEP-17:02 | 18.03 | 12.75 | 0.391385E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.264866E+10 | 11945.32 | 11-OCT-16:00 | 21.70 | 14.52 | 0.382596E+09 | 544.95 | 12-OCT-09:20 | 16.13 | 13.62 |
November | 0.129432E+10 | 5256.25 | 15-NOV-15:20 | 11.70 | 6.66 | 0.343461E+09 | 544.96 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.366947E+09 | 2063.44 | 04-DEC-15:50 | -0.5 | -3.2 | 0.295983E+09 | 524.02 | 04-DEC-14:00 | -0.5 | -3.2 |
Annual Sum or Average | 0.490969E+11 | 0.445326E+10 | ||||||||
Minimum of Months | 0.266169E+09 | 1614.76 | -6.0 | -8.3 | 0.283313E+09 | 521.18 | -6.4 | -8.3 | ||
Maximum of Months | 0.928912E+10 | 30376.78 | 25.60 | 18.97 | 0.445435E+09 | 545.00 | 25.00 | 18.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22431150.95 | 1204.97 | 07-JAN-17:02 | -2.7 | -3.8 | 0.462739E+09 | 625.93 | 23-JAN-10:30 | -6.7 | -8.5 |
February | 58537842.05 | 1313.41 | 22-FEB-16:50 | 11.52 | 5.47 | 0.419399E+09 | 625.97 | 21-FEB-10:09 | 11.52 | 5.47 |
March | 0.114643E+10 | 6437.12 | 15-MAR-14:30 | 25.85 | 16.15 | 0.541877E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.190243E+10 | 4297.17 | 20-APR-15:40 | 14.80 | 10.94 | 0.515394E+09 | 845.62 | 20-APR-13:20 | 14.80 | 10.94 |
May | 0.404996E+10 | 7314.80 | 23-MAY-14:40 | 23.90 | 13.32 | 0.631347E+09 | 845.64 | 10-MAY-13:39 | 23.90 | 13.32 |
June | 0.733538E+10 | 11795.70 | 18-JUN-11:43 | 26.02 | 20.76 | 0.657227E+09 | 846.14 | 12-JUN-13:50 | 26.02 | 20.76 |
July | 0.866932E+10 | 16614.75 | 02-JUL-18:21 | 23.35 | 16.56 | 0.615193E+09 | 845.75 | 27-JUL-13:39 | 29.40 | 20.89 |
August | 0.773192E+10 | 16267.50 | 13-AUG-15:31 | 29.60 | 23.37 | 0.686541E+09 | 845.69 | 02-AUG-13:09 | 29.60 | 23.37 |
September | 0.423101E+10 | 7282.64 | 15-SEP-14:00 | 25.60 | 21.03 | 0.587729E+09 | 845.68 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.181944E+10 | 4082.56 | 12-OCT-15:00 | 18.30 | 15.23 | 0.533690E+09 | 845.62 | 12-OCT-13:00 | 18.30 | 15.23 |
November | 0.613581E+09 | 1832.39 | 16-NOV-17:00 | 18.30 | 13.48 | 0.473195E+09 | 768.54 | 16-NOV-14:00 | 18.30 | 13.48 |
December | 67026658.67 | 1386.39 | 01-DEC-13:40 | 10.17 | 8.68 | 0.446130E+09 | 639.19 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.376475E+11 | 0.657046E+10 | ||||||||
Minimum of Months | 22431150.95 | 1204.97 | -2.7 | -3.8 | 0.419399E+09 | 625.93 | -6.7 | -8.5 | ||
Maximum of Months | 0.866932E+10 | 16614.75 | 29.60 | 23.37 | 0.686541E+09 | 846.14 | 29.60 | 23.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38190803.42 | 906.01 | 20-JAN-06:04 | -0.7 | -3.0 | 0.299061E+09 | 414.28 | 12-JAN-10:39 | -0.7 | -3.0 |
February | 0.213341E+09 | 1691.94 | 28-FEB-10:05 | -3.6 | -5.3 | 0.277299E+09 | 544.95 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.140327E+10 | 6143.01 | 15-MAR-09:30 | 20.25 | 14.29 | 0.378077E+09 | 544.97 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.288278E+10 | 11752.89 | 23-APR-10:32 | 14.80 | 7.30 | 0.363265E+09 | 544.96 | 21-APR-13:00 | 14.80 | 7.30 |
May | 0.535661E+10 | 16595.04 | 21-MAY-10:53 | 16.70 | 11.75 | 0.418855E+09 | 545.37 | 31-MAY-09:30 | 18.05 | 13.49 |
June | 0.806931E+10 | 23380.60 | 11-JUN-09:32 | 24.03 | 16.62 | 0.426088E+09 | 546.05 | 20-JUN-09:00 | 23.30 | 16.76 |
July | 0.919715E+10 | 24829.26 | 04-JUL-09:22 | 21.65 | 17.37 | 0.397372E+09 | 546.06 | 13-JUL-09:50 | 20.92 | 15.73 |
August | 0.828256E+10 | 21194.35 | 06-AUG-09:12 | 24.47 | 17.45 | 0.444443E+09 | 546.04 | 04-AUG-09:00 | 24.47 | 17.45 |
September | 0.504242E+10 | 23292.14 | 10-SEP-10:02 | 15.68 | 10.52 | 0.387349E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.186782E+10 | 8286.01 | 11-OCT-09:30 | 15.85 | 11.81 | 0.373215E+09 | 544.95 | 27-OCT-13:20 | 10.17 | 7.43 |
November | 0.561825E+09 | 2379.07 | 03-NOV-09:20 | 4.47 | 2.22 | 0.316525E+09 | 544.95 | 03-NOV-09:09 | 4.47 | 2.22 |
December | 60659147.24 | 912.61 | 13-DEC-06:04 | 1.20 | 0.92 | 0.288547E+09 | 419.62 | 04-DEC-10:30 | 1.20 | 0.92 |
Annual Sum or Average | 0.429759E+11 | 0.437009E+10 | ||||||||
Minimum of Months | 38190803.42 | 906.01 | -3.6 | -5.3 | 0.277299E+09 | 414.28 | -3.6 | -5.3 | ||
Maximum of Months | 0.919715E+10 | 24829.26 | 24.47 | 17.45 | 0.444443E+09 | 546.06 | 25.55 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100837E+10 | 12506.53 | 12-JAN-13:40 | -6.5 | -9.0 | 0.497343E+09 | 845.64 | 30-JAN-14:20 | -8.2 | -9.8 |
February | 0.146110E+10 | 16917.51 | 28-FEB-13:40 | 0.00 | -2.9 | 0.460396E+09 | 845.72 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.443264E+10 | 19161.43 | 15-MAR-13:30 | 25.55 | 15.84 | 0.607348E+09 | 846.53 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.474807E+10 | 19071.43 | 23-APR-14:32 | 15.20 | 9.59 | 0.551693E+09 | 850.04 | 11-APR-13:09 | 15.20 | 9.59 |
May | 0.680752E+10 | 27034.74 | 14-MAY-13:42 | 24.82 | 18.07 | 0.637813E+09 | 845.69 | 10-MAY-13:39 | 24.82 | 18.07 |
June | 0.940334E+10 | 26109.99 | 25-JUN-13:02 | 26.10 | 17.26 | 0.656272E+09 | 846.15 | 12-JUN-13:39 | 26.10 | 17.26 |
July | 0.113724E+11 | 26866.37 | 30-JUL-12:32 | 25.60 | 19.52 | 0.615169E+09 | 846.63 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.120547E+11 | 27690.40 | 13-AUG-12:52 | 30.00 | 22.88 | 0.688234E+09 | 846.61 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.976567E+10 | 30069.93 | 10-SEP-12:41 | 17.12 | 10.59 | 0.599826E+09 | 869.73 | 21-SEP-13:39 | 25.40 | 16.58 |
October | 0.574569E+10 | 23401.03 | 22-OCT-14:02 | 21.70 | 14.26 | 0.589120E+09 | 902.23 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.236907E+10 | 17065.84 | 03-NOV-12:40 | 8.53 | 4.68 | 0.521092E+09 | 845.66 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.728806E+09 | 10211.40 | 16-DEC-13:30 | 5.60 | 3.03 | 0.466064E+09 | 845.64 | 11-DEC-14:30 | 5.60 | 3.03 |
Annual Sum or Average | 0.698974E+11 | 0.689037E+10 | ||||||||
Minimum of Months | 0.728806E+09 | 10211.40 | -6.5 | -9.0 | 0.460396E+09 | 845.64 | -8.2 | -9.8 | ||
Maximum of Months | 0.120547E+11 | 30069.93 | 30.00 | 22.88 | 0.688234E+09 | 902.23 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128531E+09 | 1240.72 | 12-JAN-16:00 | -6.1 | -8.3 | 0.301512E+09 | 499.49 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.317867E+09 | 5790.24 | 28-FEB-16:30 | 0.00 | -2.6 | 0.278646E+09 | 544.64 | 28-FEB-14:00 | 0.00 | -2.6 |
March | 0.175415E+10 | 8492.86 | 21-MAR-16:00 | 4.40 | 1.34 | 0.373110E+09 | 544.97 | 15-MAR-13:30 | 4.40 | 1.34 |
April | 0.305478E+10 | 18170.84 | 02-APR-16:11 | 7.77 | 5.85 | 0.351785E+09 | 544.96 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.563037E+10 | 28528.34 | 07-MAY-17:41 | 14.08 | 5.36 | 0.414388E+09 | 544.97 | 10-MAY-13:39 | 25.73 | 17.72 |
June | 0.891140E+10 | 27778.09 | 11-JUN-16:51 | 25.60 | 17.82 | 0.425092E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.955612E+10 | 31908.73 | 02-JUL-17:01 | 24.82 | 16.94 | 0.397368E+09 | 544.96 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.891213E+10 | 27334.99 | 13-AUG-15:31 | 29.60 | 23.37 | 0.444684E+09 | 545.00 | 02-AUG-13:09 | 29.60 | 23.37 |
September | 0.510000E+10 | 27796.25 | 10-SEP-16:01 | 17.52 | 11.16 | 0.385701E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.216386E+10 | 11895.48 | 11-OCT-16:00 | 21.70 | 14.52 | 0.363246E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.803620E+09 | 4300.60 | 15-NOV-15:20 | 11.70 | 6.66 | 0.321777E+09 | 544.93 | 09-NOV-14:00 | 11.70 | 6.66 |
December | 0.172149E+09 | 1261.55 | 04-DEC-16:00 | -0.6 | -3.3 | 0.290980E+09 | 505.31 | 04-DEC-16:10 | -0.9 | -3.5 |
Annual Sum or Average | 0.465050E+11 | 0.434829E+10 | ||||||||
Minimum of Months | 0.128531E+09 | 1240.72 | -6.1 | -8.3 | 0.278646E+09 | 499.49 | -6.2 | -8.3 | ||
Maximum of Months | 0.955612E+10 | 31908.73 | 29.60 | 23.37 | 0.444684E+09 | 545.00 | 29.60 | 23.37 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97895249.81 | 5987.37 | 04-JAN-06:01 | -12.3 | -12.9 | 0.00 | 0.00 | 01-JAN-00:10 | -12.3 | -12.9 |
February | 87649072.63 | 7857.63 | 06-FEB-05:01 | -14.8 | -15.7 | 0.00 | 0.00 | 01-FEB-00:10 | -14.8 | -15.7 |
March | 0.166166E+10 | 5182.22 | 15-MAR-14:20 | 25.93 | 16.12 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 16.12 |
April | 0.350816E+10 | 6819.18 | 10-APR-05:15 | 4.07 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.07 | 3.41 |
May | 0.469262E+10 | 8263.10 | 30-MAY-05:15 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.797408E+10 | 11145.22 | 28-JUN-05:10 | 17.20 | 15.14 | 0.00 | 0.00 | 01-JUN-00:10 | 17.20 | 15.14 |
July | 0.986378E+10 | 12845.41 | 24-JUL-05:10 | 16.10 | 15.07 | 0.00 | 0.00 | 01-JUL-00:10 | 16.10 | 15.07 |
August | 0.981307E+10 | 11277.43 | 07-AUG-05:15 | 20.20 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 20.20 | 18.58 |
September | 0.584853E+10 | 9469.96 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.336236E+10 | 6728.57 | 23-OCT-05:15 | 11.70 | 10.06 | 0.00 | 0.00 | 01-OCT-00:10 | 11.70 | 10.06 |
November | 0.197449E+10 | 5303.58 | 06-NOV-06:15 | 8.90 | 6.78 | 0.00 | 0.00 | 01-NOV-00:10 | 8.90 | 6.78 |
December | 0.260738E+09 | 4126.10 | 11-DEC-05:01 | -17.5 | -18.0 | 0.00 | 0.00 | 01-DEC-00:10 | -17.5 | -18.0 |
Annual Sum or Average | 0.491450E+11 | 0.00 | ||||||||
Minimum of Months | 87649072.63 | 4126.10 | -17.5 | -18.0 | 0.00 | 0.00 | -17.5 | -18.0 | ||
Maximum of Months | 0.986378E+10 | 12845.41 | 25.93 | 18.58 | 0.00 | 0.00 | 25.93 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98459458.07 | 9275.03 | 24-JAN-04:01 | -11.7 | -13.2 | 0.00 | 0.00 | 01-JAN-00:10 | -11.7 | -13.2 |
February | 0.107699E+09 | 10261.78 | 21-FEB-04:11 | -11.3 | -12.5 | 0.00 | 0.00 | 01-FEB-00:10 | -11.3 | -12.5 |
March | 0.499719E+09 | 9326.32 | 04-MAR-05:01 | -10.1 | -11.1 | 0.00 | 0.00 | 01-MAR-00:10 | -10.1 | -11.1 |
April | 0.955760E+09 | 5250.72 | 17-APR-05:01 | -4.0 | -5.3 | 0.00 | 0.00 | 01-APR-00:10 | -4.0 | -5.3 |
May | 0.277446E+10 | 4532.71 | 30-MAY-14:20 | 17.80 | 14.42 | 0.00 | 0.00 | 01-MAY-00:10 | 17.80 | 14.42 |
June | 0.528668E+10 | 6272.22 | 21-JUN-05:15 | 18.30 | 16.18 | 0.00 | 0.00 | 01-JUN-00:10 | 18.30 | 16.18 |
July | 0.654211E+10 | 7335.10 | 22-JUL-05:15 | 21.10 | 20.28 | 0.00 | 0.00 | 01-JUL-00:10 | 21.10 | 20.28 |
August | 0.635455E+10 | 7220.90 | 07-AUG-05:15 | 20.20 | 18.58 | 0.00 | 0.00 | 01-AUG-00:10 | 20.20 | 18.58 |
September | 0.376716E+10 | 6081.97 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.116675E+10 | 6007.82 | 30-OCT-05:01 | -0.1 | -0.9 | 0.00 | 0.00 | 01-OCT-00:10 | -0.1 | -0.9 |
November | 0.357111E+09 | 7898.18 | 24-NOV-05:01 | -3.0 | -3.7 | 0.00 | 0.00 | 01-NOV-00:10 | -3.0 | -3.7 |
December | 0.153384E+09 | 8691.14 | 27-DEC-04:01 | -11.7 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.7 | -12.1 |
Annual Sum or Average | 0.280638E+11 | 0.00 | ||||||||
Minimum of Months | 98459458.07 | 4532.71 | -11.7 | -13.2 | 0.00 | 0.00 | -11.7 | -13.2 | ||
Maximum of Months | 0.654211E+10 | 10261.78 | 21.10 | 20.28 | 0.00 | 0.00 | 21.10 | 20.28 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.528810E+09 | 11293.19 | 15-MAR-14:20 | 25.93 | 16.12 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 16.12 |
April | 0.175444E+10 | 9464.76 | 21-APR-14:00 | 14.40 | 8.43 | 0.00 | 0.00 | 01-APR-00:10 | 14.40 | 8.43 |
May | 0.508459E+10 | 13803.20 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.972571E+10 | 18465.07 | 12-JUN-13:40 | 30.20 | 20.07 | 0.00 | 0.00 | 01-JUN-00:10 | 30.20 | 20.07 |
July | 0.118064E+11 | 18103.35 | 21-JUL-13:40 | 31.33 | 21.85 | 0.00 | 0.00 | 01-JUL-00:10 | 31.33 | 21.85 |
August | 0.103473E+11 | 17722.85 | 09-AUG-15:20 | 29.40 | 18.24 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.24 |
September | 0.506687E+10 | 13464.76 | 21-SEP-15:40 | 26.10 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.00 |
October | 0.917992E+09 | 7606.42 | 11-OCT-15:40 | 21.87 | 14.55 | 0.00 | 0.00 | 01-OCT-00:10 | 21.87 | 14.55 |
November | 26856393.46 | 990.12 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.452589E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.00 | 0.00 | -3.3 | -4.7 | ||
Maximum of Months | 0.118064E+11 | 18465.07 | 31.33 | 21.85 | 0.00 | 0.00 | 31.33 | 21.85 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237660E+10 | 1949.33 | 12-JAN-16:40 | -6.5 | -8.3 | 95230014.50 | 126.82 | 12-JAN-10:09 | -6.5 | -8.3 |
February | 0.712219E+10 | 4162.10 | 28-FEB-17:00 | -0.6 | -3.0 | 86396456.92 | 126.82 | 21-FEB-10:39 | -0.6 | -3.0 |
March | 0.139776E+11 | 7000.82 | 31-MAR-24:00 | 4.20 | 3.93 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.20 | 3.93 |
April | 0.187885E+11 | 8202.92 | 02-APR-17:55 | 6.10 | 4.84 | 91605147.90 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.436855E+10 | 3473.67 | 31-MAY-24:00 | 17.10 | 14.03 | 99235875.78 | 126.85 | 17-MAY-13:39 | 17.10 | 14.03 |
June | 0.944783E+10 | 5391.38 | 30-JUN-24:00 | 16.90 | 13.02 | 98966808.37 | 126.86 | 27-JUN-09:00 | 16.90 | 13.02 |
July | 0.149098E+11 | 7288.10 | 31-JUL-24:00 | 19.10 | 16.93 | 91888647.92 | 126.84 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.198774E+11 | 8244.54 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103238E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.435024E+10 | 3239.89 | 30-SEP-24:00 | 14.40 | 12.09 | 91610997.50 | 126.85 | 25-SEP-13:50 | 14.40 | 12.09 |
October | 0.918240E+10 | 5165.97 | 31-OCT-24:00 | 6.60 | 4.77 | 95232267.05 | 126.84 | 12-OCT-13:00 | 6.60 | 4.77 |
November | 0.135959E+11 | 5848.98 | 24-NOV-16:20 | 3.87 | 1.42 | 94300313.42 | 126.82 | 10-NOV-14:00 | 3.87 | 1.42 |
December | 0.186039E+11 | 7739.65 | 04-DEC-16:20 | -1.1 | -3.7 | 91880848.04 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.136601E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.237660E+10 | 1949.33 | -6.5 | -8.3 | 86396456.92 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.198774E+11 | 8244.54 | 22.07 | 16.93 | 0.103238E+09 | 126.86 | 19.10 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370758E+09 | 1573.33 | 12-JAN-16:50 | -6.6 | -8.3 | 93271687.91 | 126.82 | 12-JAN-10:00 | -6.6 | -8.3 |
February | 0.433855E+10 | 3665.92 | 28-FEB-17:00 | -0.6 | -3.0 | 86396470.85 | 126.82 | 21-FEB-10:39 | -0.6 | -3.0 |
March | 0.117645E+11 | 6263.13 | 31-MAR-23:40 | 4.40 | 4.06 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.40 | 4.06 |
April | 0.170119E+11 | 7686.50 | 24-APR-18:00 | 11.70 | 8.10 | 91605168.18 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.371887E+10 | 3284.75 | 31-MAY-24:00 | 17.10 | 14.03 | 99235728.88 | 126.84 | 17-MAY-13:09 | 17.10 | 14.03 |
June | 0.876665E+10 | 5137.03 | 30-JUN-24:00 | 16.90 | 13.02 | 98966491.24 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.140675E+11 | 6998.38 | 31-JUL-24:00 | 19.10 | 16.93 | 91889188.58 | 126.85 | 05-JUL-13:09 | 19.10 | 16.93 |
August | 0.188070E+11 | 7912.00 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-13:09 | 18.58 | 18.07 |
September | 0.368803E+10 | 2786.09 | 30-SEP-24:00 | 14.40 | 12.09 | 91609604.19 | 126.84 | 08-SEP-13:00 | 14.40 | 12.09 |
October | 0.764965E+10 | 4553.12 | 31-OCT-23:40 | 6.73 | 4.84 | 95232176.79 | 126.84 | 12-OCT-13:00 | 6.73 | 4.84 |
November | 0.112300E+11 | 5396.34 | 15-NOV-16:20 | 10.93 | 6.40 | 94300329.84 | 126.82 | 10-NOV-14:00 | 10.93 | 6.40 |
December | 0.147858E+11 | 6976.12 | 04-DEC-16:30 | -1.4 | -3.9 | 91880866.06 | 126.82 | 01-DEC-14:09 | -1.4 | -3.9 |
Annual Sum or Average | 0.116199E+12 | 0.114086E+10 | ||||||||
Minimum of Months | 0.370758E+09 | 1573.33 | -6.6 | -8.3 | 86396470.85 | 126.82 | -6.6 | -8.3 | ||
Maximum of Months | 0.188070E+11 | 7912.00 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.10 | 18.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133312E+09 | 1343.83 | 12-JAN-16:40 | -6.5 | -8.3 | 88490048.58 | 126.82 | 20-JAN-14:09 | -0.4 | -3.5 |
February | 0.277069E+10 | 3601.06 | 28-FEB-17:00 | -0.6 | -3.0 | 86395817.87 | 126.82 | 21-FEB-10:39 | -0.6 | -3.0 |
March | 0.101367E+11 | 5828.53 | 31-MAR-23:20 | 4.60 | 4.18 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.60 | 4.18 |
April | 0.159434E+11 | 7678.97 | 24-APR-18:00 | 11.70 | 8.10 | 91605175.02 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.327502E+10 | 3186.87 | 31-MAY-23:40 | 17.17 | 13.97 | 99235708.73 | 126.84 | 30-MAY-13:00 | 17.17 | 13.97 |
June | 0.867334E+10 | 5062.17 | 30-JUN-23:40 | 17.07 | 12.89 | 98966754.05 | 126.86 | 27-JUN-13:00 | 17.07 | 12.89 |
July | 0.140984E+11 | 6982.71 | 31-JUL-24:00 | 19.10 | 16.93 | 91889395.19 | 126.85 | 05-JUL-13:09 | 19.10 | 16.93 |
August | 0.187614E+11 | 7965.22 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-13:09 | 18.58 | 18.07 |
September | 0.330017E+10 | 2498.60 | 04-SEP-17:48 | 16.97 | 12.18 | 91609312.72 | 126.85 | 08-SEP-13:00 | 22.80 | 18.10 |
October | 0.629010E+10 | 4141.12 | 31-OCT-23:20 | 6.87 | 4.91 | 95232144.01 | 126.84 | 12-OCT-13:00 | 6.87 | 4.91 |
November | 0.940683E+10 | 5264.94 | 15-NOV-16:30 | 10.55 | 6.20 | 94300331.10 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.127772E+11 | 6620.59 | 04-DEC-16:30 | -1.4 | -3.9 | 91880872.99 | 126.82 | 01-DEC-14:09 | -1.4 | -3.9 |
Annual Sum or Average | 0.105567E+12 | 0.113608E+10 | ||||||||
Minimum of Months | 0.133312E+09 | 1343.83 | -6.5 | -8.3 | 86395817.87 | 126.82 | -1.4 | -3.9 | ||
Maximum of Months | 0.187614E+11 | 7965.22 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 22.80 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234599E+12 | 90431.45 | 18-JAN-17:00 | 1.70 | 1.21 | 0.206144E+10 | 2745.29 | 13-JAN-14:00 | 1.70 | 1.21 |
February | 0.432421E+12 | 182056.92 | 23-FEB-17:00 | -0.6 | -1.8 | 0.187023E+10 | 2745.34 | 22-FEB-14:50 | -0.6 | -1.8 |
March | 0.726731E+12 | 357897.66 | 31-MAR-24:00 | 4.20 | 3.93 | 0.223487E+10 | 2749.26 | 14-MAR-13:09 | 4.20 | 3.93 |
April | 0.941346E+12 | 366736.29 | 24-APR-16:00 | 13.30 | 7.63 | 0.198305E+10 | 2748.64 | 28-APR-09:09 | 10.00 | 8.84 |
May | 0.239361E+12 | 175662.99 | 31-MAY-24:00 | 17.10 | 14.03 | 0.214808E+10 | 2745.71 | 10-MAY-13:09 | 17.10 | 14.03 |
June | 0.470127E+12 | 267991.02 | 30-JUN-24:00 | 16.90 | 13.02 | 0.214234E+10 | 2748.51 | 01-JUN-13:00 | 16.90 | 13.02 |
July | 0.732428E+12 | 360089.58 | 31-JUL-24:00 | 19.10 | 16.93 | 0.199617E+10 | 2992.02 | 21-JUL-09:09 | 19.10 | 16.93 |
August | 0.977071E+12 | 378592.97 | 15-AUG-16:41 | 20.87 | 19.23 | 0.231147E+10 | 3747.77 | 15-AUG-13:09 | 20.87 | 19.23 |
September | 0.235392E+12 | 175484.92 | 30-SEP-24:00 | 14.40 | 12.09 | 0.198297E+10 | 2746.05 | 21-SEP-13:00 | 14.40 | 12.09 |
October | 0.486215E+12 | 268099.09 | 31-OCT-24:00 | 6.60 | 4.77 | 0.206145E+10 | 2746.13 | 23-OCT-09:30 | 6.60 | 4.77 |
November | 0.706965E+12 | 275752.75 | 06-NOV-17:00 | 6.10 | 3.25 | 0.204137E+10 | 2746.86 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.973366E+12 | 366624.61 | 04-DEC-16:55 | -2.2 | -4.4 | 0.198898E+10 | 2747.44 | 01-DEC-10:00 | -2.2 | -4.4 |
Annual Sum or Average | 0.715602E+13 | 0.248224E+11 | ||||||||
Minimum of Months | 0.234599E+12 | 90431.45 | -2.2 | -4.4 | 0.187023E+10 | 2745.29 | -2.2 | -4.4 | ||
Maximum of Months | 0.977071E+12 | 378592.97 | 20.87 | 19.23 | 0.231147E+10 | 3747.77 | 20.87 | 19.23 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709911E+09 | 49035.25 | 02-JAN-04:01 | -1.0 |
February | 88026934.40 | 40305.12 | 06-FEB-05:01 | -14.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 70806337.63 | 40236.89 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.868744E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.709911E+09 | 49035.25 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.587608E+10 | 73857.90 | 02-JAN-04:01 | -1.0 |
February | 0.478198E+10 | 73179.71 | 06-FEB-04:01 | -15.0 |
March | 0.155632E+10 | 70342.94 | 06-MAR-04:01 | -11.1 |
April | 0.254265E+09 | 65763.24 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.239764E+09 | 64307.77 | 30-OCT-04:01 | -0.5 |
November | 0.813278E+09 | 66900.50 | 24-NOV-05:01 | -3.0 |
December | 0.432551E+10 | 73624.61 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.178472E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.587608E+10 | 73857.90 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449304E+09 | 11453.11 | 30-JAN-05:01 | -9.5 |
February | 0.303786E+09 | 11882.15 | 06-FEB-05:01 | -14.8 |
March | 39192335.47 | 10882.86 | 07-MAR-06:01 | -13.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.103520E+09 | 11220.63 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.895803E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.449304E+09 | 11882.15 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332030E+09 | 11324.13 | 30-JAN-05:01 | -9.5 |
February | 0.256371E+09 | 11937.88 | 06-FEB-05:01 | -14.8 |
March | 24996099.87 | 10259.86 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.173007E+09 | 11316.48 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.786404E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.332030E+09 | 11937.88 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709959E+09 | 17642.41 | 30-JAN-05:01 | -9.5 |
February | 0.588110E+09 | 17663.26 | 07-FEB-05:01 | -15.7 |
March | 66581591.99 | 16176.45 | 06-MAR-05:01 | -11.1 |
April | 1109767.99 | 7076.80 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 626481.88 | 8123.23 | 30-OCT-05:01 | -0.1 |
November | 6991330.04 | 13900.06 | 24-NOV-06:01 | -3.8 |
December | 0.287995E+09 | 16998.55 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.166137E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.709959E+09 | 17663.26 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55531155.81 | 8294.50 | 09-JAN-06:01 | -9.4 |
February | 19898868.03 | 8780.51 | 06-FEB-05:01 | -14.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 75430023.84 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 55531155.81 | 8780.51 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516068E+10 | 12831.74 | 09-JAN-02:62 | -8.5 |
February | 0.407504E+10 | 12860.64 | 06-FEB-04:11 | -15.0 |
March | 0.127641E+10 | 12558.14 | 06-MAR-04:01 | -11.1 |
April | 99817227.35 | 10962.26 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 77131668.07 | 10618.60 | 30-OCT-04:01 | -0.5 |
November | 0.410947E+09 | 11303.29 | 24-NOV-05:01 | -3.0 |
December | 0.388192E+10 | 12688.02 | 26-DEC-03:42 | -11.7 |
Annual Sum or Average | 0.149819E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.516068E+10 | 12860.64 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281560E+10 | 18047.13 | 02-JAN-04:01 | -1.0 |
February | 0.221255E+10 | 18220.07 | 13-FEB-04:01 | -8.9 |
March | 0.475455E+09 | 17202.09 | 06-MAR-04:01 | -11.1 |
April | 39826239.24 | 15040.81 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 42713305.35 | 14714.59 | 30-OCT-04:01 | -0.5 |
November | 0.250850E+09 | 15897.28 | 24-NOV-05:01 | -3.0 |
December | 0.232685E+10 | 17812.49 | 12-DEC-04:01 | -10.9 |
Annual Sum or Average | 0.816386E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.1 | |
Maximum of Months | 0.281560E+10 | 18220.07 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313691E+10 | 20848.20 | 02-JAN-04:01 | -1.0 |
February | 0.256836E+10 | 21015.18 | 06-FEB-04:11 | -15.0 |
March | 0.488404E+09 | 18568.52 | 06-MAR-05:01 | -11.1 |
April | 57970260.80 | 17191.09 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 32169685.62 | 16664.11 | 30-OCT-05:01 | -0.1 |
November | 0.249337E+09 | 18259.04 | 24-NOV-05:01 | -3.0 |
December | 0.245601E+10 | 20273.93 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.898916E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.313691E+10 | 21015.18 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248436E+10 | 17994.95 | 02-JAN-04:01 | -1.0 |
February | 0.184996E+10 | 18140.86 | 06-FEB-04:11 | -15.0 |
March | 0.364210E+09 | 16050.81 | 06-MAR-04:01 | -11.1 |
April | 14555105.27 | 13887.57 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 21524077.20 | 13955.12 | 16-OCT-05:01 | 1.20 |
November | 0.143626E+09 | 15164.53 | 24-NOV-05:01 | -3.0 |
December | 0.172584E+10 | 17421.68 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.660408E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.248436E+10 | 18140.86 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.980476E+10 | 15290.11 | 09-JAN-02:62 | -8.5 |
February | 0.825493E+10 | 15699.99 | 06-FEB-03:42 | -14.8 |
March | 0.375087E+10 | 14941.56 | 06-MAR-03:42 | -11.0 |
April | 0.783413E+09 | 14277.43 | 17-APR-03:01 | -2.9 |
May | 15009280.44 | 11576.76 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 13012825.40 | 11327.15 | 30-SEP-05:03 | 7.20 |
October | 0.732168E+09 | 14214.27 | 30-OCT-03:01 | -0.1 |
November | 0.225141E+10 | 14374.70 | 24-NOV-04:01 | -3.2 |
December | 0.868966E+10 | 15365.81 | 26-DEC-01:12 | -11.3 |
Annual Sum or Average | 0.342952E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.980476E+10 | 15699.99 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565613E+10 | 20467.77 | 09-JAN-02:62 | -8.5 |
February | 0.475918E+10 | 21151.59 | 06-FEB-03:42 | -14.8 |
March | 0.165011E+10 | 19434.83 | 20-MAR-03:01 | -2.3 |
April | 0.334393E+09 | 19311.67 | 17-APR-03:01 | -2.9 |
May | 5566001.79 | 13507.48 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 7819381.33 | 9391.57 | 30-SEP-05:03 | 7.20 |
October | 0.359259E+09 | 19414.35 | 30-OCT-03:01 | -0.1 |
November | 0.129492E+10 | 19612.67 | 24-NOV-04:01 | -3.2 |
December | 0.543929E+10 | 20643.22 | 26-DEC-01:12 | -11.3 |
Annual Sum or Average | 0.195067E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.565613E+10 | 21151.59 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663325E+10 | 23314.12 | 29-JAN-23:02 | -9.0 |
February | 0.584267E+10 | 24163.07 | 06-FEB-03:42 | -14.8 |
March | 0.197903E+10 | 22241.42 | 20-MAR-03:01 | -2.3 |
April | 0.568692E+09 | 21984.37 | 17-APR-03:01 | -2.9 |
May | 12370427.76 | 13454.32 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 7094509.09 | 8896.99 | 30-SEP-05:03 | 7.20 |
October | 0.406368E+09 | 21574.05 | 30-OCT-03:01 | -0.1 |
November | 0.154278E+10 | 22366.57 | 24-NOV-04:01 | -3.2 |
December | 0.627001E+10 | 23661.80 | 26-DEC-01:12 | -11.3 |
Annual Sum or Average | 0.232623E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.663325E+10 | 24163.07 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508353E+10 | 21854.58 | 09-JAN-02:62 | -8.5 |
February | 0.385159E+10 | 22354.71 | 06-FEB-03:42 | -14.8 |
March | 0.127787E+10 | 20617.61 | 06-MAR-04:01 | -11.1 |
April | 0.219415E+09 | 18744.79 | 17-APR-03:01 | -2.9 |
May | 82672.96 | 551.15 | 12-MAY-05:03 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 1220436.62 | 2335.34 | 30-SEP-05:03 | 7.20 |
October | 0.238616E+09 | 18555.51 | 30-OCT-04:01 | -0.5 |
November | 0.862731E+09 | 20649.59 | 24-NOV-04:01 | -3.2 |
December | 0.398231E+10 | 21847.67 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.155174E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.508353E+10 | 22354.71 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143475E+10 | 10595.52 | 11-JAN-06:02 | 5.68 |
February | 0.129730E+10 | 10975.97 | 15-FEB-06:02 | 5.60 |
March | 0.247773E+09 | 10737.16 | 02-MAR-06:01 | 1.10 |
April | 0.138016E+09 | 10793.36 | 20-APR-04:12 | 11.50 |
May | 88056474.30 | 8996.47 | 14-MAY-14:32 | 25.73 |
June | 0.109249E+09 | 11537.28 | 11-JUN-15:21 | 25.85 |
July | 0.152628E+09 | 11096.42 | 16-JUL-16:21 | 28.90 |
August | 0.120003E+09 | 11723.07 | 13-AUG-15:01 | 29.90 |
September | 83628102.20 | 9221.32 | 10-SEP-14:51 | 17.20 |
October | 0.103603E+09 | 9249.63 | 10-OCT-04:12 | 10.00 |
November | 89424383.37 | 11404.37 | 27-NOV-05:12 | 17.97 |
December | 0.633655E+09 | 11749.23 | 14-DEC-06:02 | 5.68 |
Annual Sum or Average | 0.449809E+10 | |||
Minimum of Months | 83628102.20 | 8996.47 | 1.10 | |
Maximum of Months | 0.143475E+10 | 11749.23 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420679E+10 | 17458.72 | 02-JAN-06:13 | -1.1 |
February | 0.330465E+10 | 7461.77 | 08-FEB-11:05 | -7.1 |
March | 0.173179E+10 | 6494.53 | 23-MAR-05:02 | 4.72 |
April | 0.393241E+09 | 8387.00 | 02-APR-16:11 | 7.77 |
May | 62290392.93 | 8858.66 | 14-MAY-14:42 | 25.92 |
June | 66860832.32 | 11786.41 | 11-JUN-16:01 | 25.60 |
July | 79288689.64 | 9483.80 | 16-JUL-16:31 | 28.33 |
August | 50705573.15 | 10091.74 | 13-AUG-15:12 | 29.80 |
September | 66812815.11 | 9307.94 | 10-SEP-15:42 | 17.70 |
October | 0.304340E+09 | 7333.27 | 09-OCT-12:32 | 12.03 |
November | 0.886082E+09 | 6474.97 | 16-NOV-06:02 | 11.78 |
December | 0.285837E+10 | 7064.65 | 11-DEC-14:10 | -7.9 |
Annual Sum or Average | 0.140112E+11 | |||
Minimum of Months | 50705573.15 | 6474.97 | -7.9 | |
Maximum of Months | 0.420679E+10 | 17458.72 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118564E+11 | 27210.71 | 30-JAN-05:12 | -9.6 |
February | 0.101954E+11 | 28981.39 | 06-FEB-05:12 | -14.6 |
March | 0.521944E+10 | 26780.77 | 06-MAR-05:13 | -11.1 |
April | 0.202162E+10 | 21079.24 | 17-APR-05:13 | -4.1 |
May | 0.672744E+09 | 13850.66 | 16-MAY-05:02 | 11.10 |
June | 0.202433E+09 | 12663.87 | 06-JUN-05:03 | 6.78 |
July | 0.103886E+09 | 12077.91 | 03-JUL-04:12 | 11.70 |
August | 0.143440E+09 | 12037.32 | 03-AUG-05:03 | 11.10 |
September | 0.533624E+09 | 13068.48 | 19-SEP-05:02 | 10.60 |
October | 0.198769E+10 | 17246.31 | 30-OCT-05:13 | -0.2 |
November | 0.416783E+10 | 21619.16 | 24-NOV-06:13 | -3.7 |
December | 0.106871E+11 | 29319.93 | 11-DEC-05:42 | -18.6 |
Annual Sum or Average | 0.477915E+11 | |||
Minimum of Months | 0.103886E+09 | 12037.32 | -18.6 | |
Maximum of Months | 0.118564E+11 | 29319.93 | 11.70 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523769E+09 | 549.77 | 03-JAN-01:20 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.523769E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.523769E+09 | 549.77 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.775933E+09 | 588.75 | 15-JAN-18:50 | 0.18 |
February | 0.113785E+09 | 551.12 | 05-FEB-20:05 | -11.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.889718E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.2 | |
Maximum of Months | 0.775933E+09 | 588.75 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.991120E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.844542E+09 | 1441.39 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.940217E+09 | 1158.25 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.808427E+09 | 919.49 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.850114E+09 | 868.10 | 11-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.835587E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785674E+09 | 854.52 | 11-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.887196E+09 | 867.08 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.827411E+09 | 1108.99 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.908775E+09 | 1599.74 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.995068E+09 | 1662.56 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.994497E+09 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106686E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785674E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.995068E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.628351E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.540904E+09 | 937.96 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603751E+09 | 595.23 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.521509E+09 | 571.78 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.550495E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.541232E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.508626E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.573967E+09 | 552.00 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.532096E+09 | 588.53 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.579121E+09 | 852.94 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.630978E+09 | 1071.42 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.629339E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.684037E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.508626E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.630978E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.958072E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.831512E+09 | 1406.83 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.934185E+09 | 1120.64 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.810031E+09 | 918.02 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.854845E+09 | 872.62 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.839872E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.790160E+09 | 859.72 | 11-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.890733E+09 | 870.20 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.825741E+09 | 1080.68 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.893740E+09 | 1398.09 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.964382E+09 | 1662.60 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.961115E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105544E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.790160E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.964382E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.626159E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.538992E+09 | 924.55 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.603691E+09 | 791.13 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.520972E+09 | 600.05 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.548526E+09 | 574.40 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.538492E+09 | 547.64 | 21-JUN-08:09 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507042E+09 | 567.65 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.572104E+09 | 578.15 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.533139E+09 | 759.61 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.582489E+09 | 1030.67 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.629438E+09 | 1071.42 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.628997E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.683004E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507042E+09 | 547.64 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.629438E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.987912E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.843195E+09 | 1438.89 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.939053E+09 | 1152.32 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.808023E+09 | 913.64 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.849585E+09 | 859.33 | 11-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.835220E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785352E+09 | 844.92 | 11-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.886675E+09 | 858.30 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.826645E+09 | 1102.39 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.907201E+09 | 1598.83 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.991742E+09 | 1662.56 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.991522E+09 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106521E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785352E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.991742E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.627207E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.540171E+09 | 934.52 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603173E+09 | 595.23 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.521164E+09 | 567.65 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.550077E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.540940E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.508374E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.573501E+09 | 546.03 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.531659E+09 | 585.18 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.578549E+09 | 848.25 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.629791E+09 | 1071.42 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.628144E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.683275E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.508374E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.629791E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.956996E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.830607E+09 | 1404.29 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.933508E+09 | 1114.53 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.809533E+09 | 912.10 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.854220E+09 | 864.06 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.839454E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.789614E+09 | 850.38 | 11-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.890125E+09 | 861.57 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.825012E+09 | 1073.88 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.893203E+09 | 1392.44 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.963542E+09 | 1662.60 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.960234E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105460E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.789614E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.963542E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.624882E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.538205E+09 | 920.76 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.603017E+09 | 783.78 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.520575E+09 | 596.81 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.548061E+09 | 569.72 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.538272E+09 | 541.12 | 21-JUN-08:09 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.506736E+09 | 562.57 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.571690E+09 | 573.68 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.532657E+09 | 751.42 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.581528E+09 | 1030.09 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.628098E+09 | 1071.42 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.627684E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.682140E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.506736E+09 | 541.12 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.628098E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.987754E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.843143E+09 | 1438.45 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.939014E+09 | 1151.35 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.808004E+09 | 913.40 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.849529E+09 | 858.97 | 11-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.835207E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785341E+09 | 844.54 | 11-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.886663E+09 | 857.94 | 24-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.826614E+09 | 1101.30 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.907142E+09 | 1598.80 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.991643E+09 | 1662.56 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.991330E+09 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106514E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785341E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.991643E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.627156E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.540145E+09 | 934.25 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603169E+09 | 595.23 | 01-MAR-17:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.521153E+09 | 567.46 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.550063E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.540932E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.508364E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.573488E+09 | 545.79 | 28-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.531643E+09 | 585.01 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.578527E+09 | 847.86 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.629709E+09 | 1071.42 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.628090E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.683244E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.508364E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.629709E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.956865E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.830551E+09 | 1403.80 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.933441E+09 | 1113.50 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.809513E+09 | 911.86 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.854170E+09 | 863.71 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.839430E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.789593E+09 | 850.01 | 11-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.890078E+09 | 861.22 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.824986E+09 | 1072.74 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.893172E+09 | 1392.40 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.963492E+09 | 1662.60 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.960104E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105454E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.789593E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.963492E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.624751E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.538145E+09 | 920.46 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.602988E+09 | 783.22 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.520544E+09 | 596.68 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.548047E+09 | 569.53 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.538265E+09 | 540.92 | 21-JUN-08:09 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.506728E+09 | 562.37 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.571649E+09 | 573.51 | 24-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.532622E+09 | 750.79 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.581466E+09 | 1030.07 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.628035E+09 | 1071.42 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.627580E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.682082E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.506728E+09 | 540.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.628035E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.991120E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776799E+09 |
February | 0.136985E+10 | 0.844542E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826422E+09 |
March | 0.163685E+10 | 0.940217E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162078.32 | 0.521924E+09 |
April | 0.145243E+10 | 0.808427E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430104E+09 |
May | 0.157338E+10 | 0.850114E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78996.41 | 0.245463E+09 |
June | 0.156900E+10 | 0.835587E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3835364.15 | 0.138856E+09 |
July | 0.145680E+10 | 0.785674E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9828079.20 | 78357636.67 |
August | 0.163685E+10 | 0.887196E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7358982.19 | 89727311.27 |
September | 0.145243E+10 | 0.827411E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540075.83 | 0.144421E+09 |
October | 0.150991E+10 | 0.908775E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336856E+09 |
November | 0.149516E+10 | 0.995068E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466001E+09 |
December | 0.145680E+10 | 0.994497E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852062E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106686E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21803576.09 | 0.490699E+10 |
Minimum of Months | 0.136985E+10 | 0.785674E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78357636.67 |
Maximum of Months | 0.163685E+10 | 0.995068E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9828079.20 | 0.852062E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.628351E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518420E+09 |
February | 0.882782E+09 | 0.540904E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548488E+09 |
March | 0.105485E+10 | 0.603751E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108048.31 | 0.347688E+09 |
April | 0.936002E+09 | 0.521509E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283892E+09 |
May | 0.101394E+10 | 0.550495E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49208.65 | 0.166902E+09 |
June | 0.101113E+10 | 0.541232E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2553036.25 | 92964928.02 |
July | 0.938820E+09 | 0.508626E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6587563.37 | 51597993.39 |
August | 0.105485E+10 | 0.573967E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4856290.07 | 58706491.52 |
September | 0.936002E+09 | 0.532096E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352820.73 | 97482775.72 |
October | 0.973041E+09 | 0.579121E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224713E+09 |
November | 0.963541E+09 | 0.630978E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305424E+09 |
December | 0.938820E+09 | 0.629339E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557699E+09 |
Annual Sum or Average | 0.116768E+11 | 0.684037E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14506967.37 | 0.325398E+10 |
Minimum of Months | 0.882782E+09 | 0.508626E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51597993.39 |
Maximum of Months | 0.105485E+10 | 0.630978E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6587563.37 | 0.557699E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.958072E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774070E+09 |
February | 0.136988E+10 | 0.831512E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815615E+09 |
March | 0.163688E+10 | 0.934185E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161497.36 | 0.528912E+09 |
April | 0.145246E+10 | 0.810031E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428641E+09 |
May | 0.157341E+10 | 0.854845E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73810.98 | 0.248767E+09 |
June | 0.156904E+10 | 0.839872E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3810392.73 | 0.139147E+09 |
July | 0.145684E+10 | 0.790160E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9656713.92 | 79530198.75 |
August | 0.163688E+10 | 0.890733E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6957699.08 | 92978273.93 |
September | 0.145246E+10 | 0.825741E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495257.81 | 0.149351E+09 |
October | 0.150994E+10 | 0.893740E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340880E+09 |
November | 0.149520E+10 | 0.964382E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458263E+09 |
December | 0.145684E+10 | 0.961115E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839190E+09 |
Annual Sum or Average | 0.181198E+11 | 0.105544E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21155371.88 | 0.489535E+10 |
Minimum of Months | 0.136988E+10 | 0.790160E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79530198.75 |
Maximum of Months | 0.163688E+10 | 0.964382E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9656713.92 | 0.839190E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.626159E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538785E+09 |
February | 0.882782E+09 | 0.538992E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583075E+09 |
March | 0.105485E+10 | 0.603691E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108048.17 | 0.381833E+09 |
April | 0.936002E+09 | 0.520972E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318339E+09 |
May | 0.101394E+10 | 0.548526E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49208.21 | 0.180067E+09 |
June | 0.101113E+10 | 0.538492E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2429136.94 | 0.106057E+09 |
July | 0.938820E+09 | 0.507042E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6066529.00 | 64772230.62 |
August | 0.105485E+10 | 0.572104E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4542456.22 | 74341962.60 |
September | 0.936002E+09 | 0.533139E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 325372.46 | 0.106595E+09 |
October | 0.973041E+09 | 0.582489E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245389E+09 |
November | 0.963541E+09 | 0.629438E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339694E+09 |
December | 0.938820E+09 | 0.628997E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621714E+09 |
Annual Sum or Average | 0.116768E+11 | 0.683004E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13520751.00 | 0.356066E+10 |
Minimum of Months | 0.882782E+09 | 0.507042E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64772230.62 |
Maximum of Months | 0.105485E+10 | 0.629438E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6066529.00 | 0.621714E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.987912E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162914E+10 |
February | 0.136985E+10 | 0.843195E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173444E+10 |
March | 0.163685E+10 | 0.939053E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337496.86 | 0.109635E+10 |
April | 0.145243E+10 | 0.808023E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903033E+09 |
May | 0.157338E+10 | 0.849585E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213803.84 | 0.541758E+09 |
June | 0.156900E+10 | 0.835220E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8878618.56 | 0.310154E+09 |
July | 0.145680E+10 | 0.785352E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22149579.18 | 0.181801E+09 |
August | 0.163685E+10 | 0.886675E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17520597.88 | 0.208119E+09 |
September | 0.145243E+10 | 0.826645E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260324.41 | 0.313785E+09 |
October | 0.150991E+10 | 0.907201E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696288E+09 |
November | 0.149516E+10 | 0.991742E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936550E+09 |
December | 0.145680E+10 | 0.991522E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174194E+10 |
Annual Sum or Average | 0.181194E+11 | 0.106521E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50360420.72 | 0.102934E+11 |
Minimum of Months | 0.136985E+10 | 0.785352E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181801E+09 |
Maximum of Months | 0.163685E+10 | 0.991742E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22149579.18 | 0.174194E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.627207E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109321E+10 |
February | 0.649041E+09 | 0.540171E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116429E+10 |
March | 0.773965E+09 | 0.603173E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 178403.64 | 0.755003E+09 |
April | 0.688021E+09 | 0.521164E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625381E+09 |
May | 0.744847E+09 | 0.550077E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93977.98 | 0.382564E+09 |
June | 0.742030E+09 | 0.540940E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5370249.85 | 0.217553E+09 |
July | 0.690839E+09 | 0.508374E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13535218.85 | 0.129026E+09 |
August | 0.773965E+09 | 0.573501E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10261842.35 | 0.148324E+09 |
September | 0.688021E+09 | 0.531659E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 714022.27 | 0.221729E+09 |
October | 0.715730E+09 | 0.578549E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488097E+09 |
November | 0.708685E+09 | 0.629791E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638385E+09 |
December | 0.690839E+09 | 0.628144E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116471E+10 |
Annual Sum or Average | 0.858171E+10 | 0.683275E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30153714.93 | 0.702827E+10 |
Minimum of Months | 0.649041E+09 | 0.508374E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129026E+09 |
Maximum of Months | 0.773965E+09 | 0.629791E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13535218.85 | 0.116471E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.956996E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170295E+10 |
February | 0.136988E+10 | 0.830607E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179091E+10 |
March | 0.163688E+10 | 0.933508E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336555.70 | 0.118542E+10 |
April | 0.145246E+10 | 0.809533E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950650E+09 |
May | 0.157341E+10 | 0.854220E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 158292.23 | 0.568219E+09 |
June | 0.156904E+10 | 0.839454E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8549299.02 | 0.318171E+09 |
July | 0.145684E+10 | 0.789614E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21138900.77 | 0.190417E+09 |
August | 0.163688E+10 | 0.890125E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15607465.93 | 0.224603E+09 |
September | 0.145246E+10 | 0.825012E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053788.40 | 0.341802E+09 |
October | 0.150994E+10 | 0.893203E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765462E+09 |
November | 0.149520E+10 | 0.963542E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998295E+09 |
December | 0.145684E+10 | 0.960234E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181510E+10 |
Annual Sum or Average | 0.181198E+11 | 0.105460E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46844302.07 | 0.108520E+11 |
Minimum of Months | 0.136988E+10 | 0.789614E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190417E+09 |
Maximum of Months | 0.163688E+10 | 0.963542E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21138900.77 | 0.181510E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.624882E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110942E+10 |
February | 0.882782E+09 | 0.538205E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118728E+10 |
March | 0.105485E+10 | 0.603017E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 224988.77 | 0.782309E+09 |
April | 0.936002E+09 | 0.520575E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647775E+09 |
May | 0.101394E+10 | 0.548061E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105531.94 | 0.395934E+09 |
June | 0.101113E+10 | 0.538272E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5412792.05 | 0.230873E+09 |
July | 0.938820E+09 | 0.506736E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13806997.98 | 0.142326E+09 |
August | 0.105485E+10 | 0.571690E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10369358.47 | 0.161994E+09 |
September | 0.936002E+09 | 0.532657E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 717950.63 | 0.228843E+09 |
October | 0.973041E+09 | 0.581528E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494567E+09 |
November | 0.963541E+09 | 0.628098E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650095E+09 |
December | 0.938820E+09 | 0.627684E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119200E+10 |
Annual Sum or Average | 0.116768E+11 | 0.682140E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30637619.84 | 0.722341E+10 |
Minimum of Months | 0.882782E+09 | 0.506736E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142326E+09 |
Maximum of Months | 0.105485E+10 | 0.628098E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13806997.98 | 0.119200E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.987754E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195524E+10 |
February | 0.136985E+10 | 0.843143E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207924E+10 |
March | 0.163685E+10 | 0.939014E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368921.16 | 0.127632E+10 |
April | 0.145243E+10 | 0.808004E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104237E+10 |
May | 0.157338E+10 | 0.849529E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179864.81 | 0.648712E+09 |
June | 0.156900E+10 | 0.835207E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10048048.58 | 0.383370E+09 |
July | 0.145680E+10 | 0.785341E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25361866.31 | 0.231233E+09 |
August | 0.163685E+10 | 0.886663E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19843013.67 | 0.260487E+09 |
September | 0.145243E+10 | 0.826614E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1400729.60 | 0.372160E+09 |
October | 0.150991E+10 | 0.907142E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776666E+09 |
November | 0.149516E+10 | 0.991643E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104944E+10 |
December | 0.145680E+10 | 0.991330E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206125E+10 |
Annual Sum or Average | 0.181194E+11 | 0.106514E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57202444.14 | 0.121365E+11 |
Minimum of Months | 0.136985E+10 | 0.785341E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231233E+09 |
Maximum of Months | 0.163685E+10 | 0.991643E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25361866.31 | 0.207924E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.627156E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131064E+10 |
February | 0.882782E+09 | 0.540145E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139657E+10 |
March | 0.105485E+10 | 0.603169E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245919.06 | 0.872910E+09 |
April | 0.936002E+09 | 0.521153E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723761E+09 |
May | 0.101394E+10 | 0.550063E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119586.53 | 0.461303E+09 |
June | 0.101113E+10 | 0.540932E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6608065.66 | 0.268271E+09 |
July | 0.938820E+09 | 0.508364E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16460898.40 | 0.162303E+09 |
August | 0.105485E+10 | 0.573488E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12523685.78 | 0.184528E+09 |
September | 0.936002E+09 | 0.531643E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 892415.86 | 0.264690E+09 |
October | 0.973041E+09 | 0.578527E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548529E+09 |
November | 0.963541E+09 | 0.629709E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713466E+09 |
December | 0.938820E+09 | 0.628090E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138031E+10 |
Annual Sum or Average | 0.116768E+11 | 0.683244E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36850571.29 | 0.828728E+10 |
Minimum of Months | 0.882782E+09 | 0.508364E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162303E+09 |
Maximum of Months | 0.105485E+10 | 0.629709E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16460898.40 | 0.139657E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.956865E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201597E+10 |
February | 0.136988E+10 | 0.830551E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212624E+10 |
March | 0.163688E+10 | 0.933441E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 367884.23 | 0.137674E+10 |
April | 0.145246E+10 | 0.809513E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110483E+10 |
May | 0.157341E+10 | 0.854170E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179375.78 | 0.683378E+09 |
June | 0.156904E+10 | 0.839430E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9940416.20 | 0.392450E+09 |
July | 0.145684E+10 | 0.789593E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24693353.85 | 0.239982E+09 |
August | 0.163688E+10 | 0.890078E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18252803.75 | 0.280059E+09 |
September | 0.145246E+10 | 0.824986E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1250594.23 | 0.411003E+09 |
October | 0.150994E+10 | 0.893172E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873357E+09 |
November | 0.149520E+10 | 0.963492E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112387E+10 |
December | 0.145684E+10 | 0.960104E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212349E+10 |
Annual Sum or Average | 0.181198E+11 | 0.105454E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54684428.03 | 0.127514E+11 |
Minimum of Months | 0.136988E+10 | 0.789593E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239982E+09 |
Maximum of Months | 0.163688E+10 | 0.963492E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24693353.85 | 0.212624E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.624751E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132559E+10 |
February | 0.882782E+09 | 0.538145E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141831E+10 |
March | 0.105485E+10 | 0.602988E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245943.64 | 0.917089E+09 |
April | 0.936002E+09 | 0.520544E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759984E+09 |
May | 0.101394E+10 | 0.548047E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119589.37 | 0.478576E+09 |
June | 0.101113E+10 | 0.538265E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6357840.13 | 0.284579E+09 |
July | 0.938820E+09 | 0.506728E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16200917.29 | 0.177984E+09 |
August | 0.105485E+10 | 0.571649E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12269301.82 | 0.201293E+09 |
September | 0.936002E+09 | 0.532622E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836760.15 | 0.275167E+09 |
October | 0.973041E+09 | 0.581466E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566148E+09 |
November | 0.963541E+09 | 0.628035E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741606E+09 |
December | 0.938820E+09 | 0.627580E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140788E+10 |
Annual Sum or Average | 0.116768E+11 | 0.682082E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36030352.41 | 0.855421E+10 |
Minimum of Months | 0.882782E+09 | 0.506728E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177984E+09 |
Maximum of Months | 0.105485E+10 | 0.628035E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16200917.29 | 0.141831E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167699E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177144E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164245.73 | 0.111675E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906612E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178953.62 | 0.512061E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6192520.75 | 0.289598E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16258688.86 | 0.167676E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13730113.89 | 0.196626E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718848.85 | 0.306729E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713995E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988766E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182873E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37243371.70 | 0.104760E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167676E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16258688.86 | 0.182873E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276375E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293302E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442242.58 | 0.189762E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155233E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513867.03 | 0.896985E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12713024.26 | 0.504366E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30411667.79 | 0.287811E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26116637.90 | 0.343956E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331332.19 | 0.535905E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121833E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164897E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299530E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71528771.75 | 0.175783E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287811E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30411667.79 | 0.299530E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289046E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307750E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34876.54 | 0.198484E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165846E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35912.18 | 0.102919E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7198495.95 | 0.603208E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21571597.52 | 0.362237E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16039472.86 | 0.410774E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681774.13 | 0.599410E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124713E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164524E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307953E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45562129.19 | 0.185880E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362237E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21571597.52 | 0.307953E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1381.28 | 12-JAN-02:00 |
February | 2010.79 | 01-FEB-10:09 | 1441.39 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1420.16 | 13-FEB-05:52 |
March | 2010.79 | 01-MAR-10:09 | 1158.25 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 15-MAR-14:00 | 890.67 | 02-MAR-01:00 |
April | 2010.79 | 03-APR-09:09 | 919.49 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 855.72 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 868.10 | 11-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 | 14-MAY-15:00 | 472.98 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 17-JUN-17:02 | 425.59 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 854.52 | 11-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.96 | 21-JUL-03:06 | 303.90 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 867.08 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.01 | 13-AUG-13:05 | 192.18 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1108.99 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 16-SEP-13:00 | 359.54 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1599.74 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 477.74 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 841.30 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1361.68 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.18 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 119.01 | 1420.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 910.93 | 12-JAN-05:54 |
February | 1295.83 | 01-FEB-10:09 | 937.96 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 946.77 | 13-FEB-05:56 |
March | 1295.83 | 01-MAR-10:09 | 595.23 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 15-MAR-14:00 | 598.81 | 26-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 571.78 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 556.38 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 10-MAY-14:00 | 333.80 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.04 | 17-JUN-17:02 | 283.67 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 | 21-JUL-02:50 | 195.35 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 552.00 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.16 | 13-AUG-13:05 | 123.95 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 588.53 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 16-SEP-13:00 | 234.86 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 852.94 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 327.69 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 546.12 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 893.08 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.95 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 91.16 | 946.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1366.38 | 12-JAN-05:54 |
February | 2010.83 | 01-FEB-10:09 | 1406.83 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1420.16 | 13-FEB-05:54 |
March | 2010.83 | 01-MAR-10:09 | 1120.64 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 15-MAR-14:00 | 922.54 | 02-MAR-01:00 |
April | 2010.83 | 03-APR-09:09 | 918.02 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 816.13 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 872.62 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 10-MAY-14:00 | 504.68 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.40 | 17-JUN-17:02 | 423.86 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 859.72 | 11-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.05 | 21-JUL-03:06 | 301.93 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 870.20 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 | 13-AUG-13:05 | 191.77 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1080.68 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 16-SEP-13:00 | 349.84 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1398.09 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 473.73 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 826.44 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1347.71 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.77 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 | 1420.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 955.82 | 12-JAN-02:00 |
February | 1295.83 | 01-FEB-10:09 | 924.55 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 951.83 | 13-FEB-03:52 |
March | 1295.83 | 01-MAR-10:09 | 791.13 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 15-MAR-14:00 | 666.38 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 600.05 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 627.64 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 574.40 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 10-MAY-14:00 | 372.66 | 29-MAY-15:20 |
June | 1295.83 | 01-JUN-09:09 | 547.64 | 21-JUN-08:09 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 12-JUN-13:00 | 304.83 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 567.65 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.31 | 21-JUL-03:06 | 239.77 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 578.15 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.18 | 13-AUG-13:03 | 168.86 | 27-AUG-16:40 |
September | 1295.83 | 01-SEP-09:09 | 759.61 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 16-SEP-13:00 | 255.15 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1030.67 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 344.94 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 616.17 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 988.27 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 547.64 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.86 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 79.18 | 988.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3198.29 | 12-JAN-05:47 |
February | 2010.79 | 01-FEB-10:09 | 1438.89 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3171.01 | 13-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 1152.32 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 15-MAR-14:00 | 1840.74 | 02-MAR-05:10 |
April | 2010.79 | 03-APR-09:09 | 913.64 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1712.21 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 859.33 | 11-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.21 | 14-MAY-15:00 | 1061.62 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.16 | 17-JUN-17:02 | 904.15 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 844.92 | 11-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.33 | 21-JUL-03:10 | 656.57 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 858.30 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.75 | 13-AUG-12:52 | 423.20 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1102.39 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 16-SEP-17:02 | 757.15 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1598.83 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 961.61 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1703.89 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2928.31 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.20 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 287.75 | 3198.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2132.19 | 12-JAN-05:47 |
February | 1239.33 | 01-FEB-08:09 | 934.52 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2198.95 | 13-FEB-05:51 |
March | 1239.33 | 01-MAR-08:09 | 595.23 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 | 15-MAR-14:10 | 1239.73 | 26-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 567.65 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1151.65 | 16-APR-06:55 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 10-MAY-14:30 | 805.94 | 29-MAY-14:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.90 | 17-JUN-17:02 | 613.55 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 21-JUL-03:06 | 440.11 | 06-JUL-02:00 |
August | 1239.33 | 01-AUG-07:10 | 546.03 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.31 | 13-AUG-13:15 | 282.72 | 30-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 585.18 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 16-SEP-13:00 | 502.57 | 29-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 848.25 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 680.16 | 08-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1141.66 | 17-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1943.66 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.72 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 176.31 | 2198.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3198.30 | 12-JAN-05:42 |
February | 2010.83 | 01-FEB-10:09 | 1404.29 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3299.57 | 13-FEB-05:51 |
March | 2010.83 | 01-MAR-10:09 | 1114.53 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 15-MAR-14:00 | 2137.25 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 912.10 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1720.91 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 864.06 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 10-MAY-14:00 | 1197.14 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.74 | 17-JUN-17:02 | 917.01 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 850.38 | 11-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.62 | 21-JUL-03:06 | 661.78 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 861.57 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.27 | 13-AUG-12:52 | 427.01 | 20-AUG-15:00 |
September | 2010.83 | 01-SEP-09:09 | 1073.88 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 | 16-SEP-13:05 | 763.58 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1392.44 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1028.19 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1752.81 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2974.59 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.01 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 260.27 | 3299.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2132.19 | 12-JAN-05:47 |
February | 1295.83 | 01-FEB-10:09 | 920.76 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2202.14 | 13-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 783.78 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 15-MAR-14:00 | 1371.04 | 25-MAR-17:04 |
April | 1295.83 | 03-APR-09:09 | 596.81 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1166.72 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 569.72 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 10-MAY-14:00 | 827.25 | 29-MAY-15:10 |
June | 1295.83 | 01-JUN-09:09 | 541.12 | 21-JUN-08:09 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 12-JUN-13:00 | 628.39 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 562.57 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.60 | 21-JUL-03:06 | 465.21 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 573.68 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.77 | 13-AUG-13:15 | 368.49 | 27-AUG-16:30 |
September | 1295.83 | 01-SEP-09:09 | 751.42 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 16-SEP-13:00 | 509.70 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1030.09 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 665.43 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1166.92 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1995.64 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 541.12 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.49 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 176.77 | 2202.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3933.68 | 12-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1438.45 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3731.81 | 13-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 1151.35 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 15-MAR-14:00 | 2298.58 | 02-MAR-05:09 |
April | 2010.79 | 03-APR-09:09 | 913.40 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1878.96 | 04-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 858.97 | 11-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 10-MAY-14:00 | 1300.73 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 | 17-JUN-17:02 | 1102.28 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 844.54 | 11-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.59 | 21-JUL-03:08 | 788.03 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 857.94 | 24-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.33 | 13-AUG-12:55 | 515.20 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1101.30 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 16-SEP-13:00 | 836.78 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1598.80 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1035.82 | 30-OCT-04:52 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1979.55 | 17-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3510.45 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.20 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 370.33 | 3933.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2673.96 | 12-JAN-05:54 |
February | 1295.83 | 01-FEB-10:09 | 934.25 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2735.60 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 595.23 | 01-MAR-17:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 15-MAR-14:00 | 1542.45 | 02-MAR-05:04 |
April | 1295.83 | 03-APR-09:09 | 567.46 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1252.58 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 10-MAY-14:00 | 996.32 | 29-MAY-13:53 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.31 | 17-JUN-17:02 | 748.00 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.42 | 21-JUL-03:06 | 527.49 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 545.79 | 28-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.18 | 13-AUG-12:55 | 343.45 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 585.01 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 16-SEP-13:00 | 554.95 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 847.86 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 709.85 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1319.69 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2338.23 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.45 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 267.18 | 2735.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4010.77 | 12-JAN-05:56 |
February | 2010.83 | 01-FEB-10:09 | 1403.80 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4034.23 | 13-FEB-05:50 |
March | 2010.83 | 01-MAR-10:09 | 1113.50 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 15-MAR-14:00 | 2423.65 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 911.86 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1879.27 | 04-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 863.71 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 10-MAY-14:00 | 1466.19 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.03 | 17-JUN-17:02 | 1118.13 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 850.01 | 11-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.59 | 21-JUL-03:06 | 794.17 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 861.22 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.13 | 13-AUG-12:55 | 525.52 | 20-AUG-15:20 |
September | 2010.83 | 01-SEP-09:09 | 1072.74 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 16-SEP-13:00 | 847.54 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1392.40 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1146.56 | 09-OCT-11:48 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2006.38 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3558.14 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.52 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 338.13 | 4034.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2673.91 | 12-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 920.46 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2735.42 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 783.22 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 15-MAR-14:00 | 1709.69 | 25-MAR-17:10 |
April | 1295.83 | 03-APR-09:09 | 596.68 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1283.35 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 569.53 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 10-MAY-14:00 | 1027.46 | 29-MAY-15:10 |
June | 1295.83 | 01-JUN-09:09 | 540.92 | 21-JUN-08:09 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.14 | 12-JUN-13:00 | 766.26 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 562.37 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.70 | 21-JUL-03:06 | 560.08 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 573.51 | 24-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.62 | 13-AUG-12:55 | 470.74 | 27-AUG-16:50 |
September | 1295.83 | 01-SEP-09:09 | 750.79 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 16-SEP-13:00 | 572.44 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1030.07 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 716.79 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1343.27 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2400.91 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 540.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.74 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 273.62 | 2735.42 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2990.88 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3031.71 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 15-MAR-14:00 | 1960.90 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1842.21 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 14-MAY-15:00 | 878.40 | 29-MAY-13:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.49 | 17-JUN-17:02 | 869.92 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.96 | 21-JUL-02:53 | 628.11 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.07 | 13-AUG-12:53 | 394.00 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 16-SEP-13:00 | 771.56 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 999.36 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1794.25 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2954.68 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.07 | 3031.71 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4983.47 | 12-JAN-05:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4947.69 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 | 15-MAR-14:00 | 3245.87 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3118.25 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.71 | 14-MAY-15:00 | 1502.98 | 29-MAY-14:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.70 | 17-JUN-17:02 | 1505.18 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.38 | 21-JUL-02:53 | 1097.02 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.67 | 13-AUG-13:00 | 703.65 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.30 | 16-SEP-17:02 | 1354.26 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1708.11 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3044.40 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4966.16 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.67 | 4983.47 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5393.64 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5285.02 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 | 15-MAR-14:00 | 3297.12 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2966.94 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 10-MAY-15:00 | 2066.32 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.62 | 17-JUN-17:02 | 1706.02 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.20 | 21-JUL-02:00 | 1204.70 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.29 | 13-AUG-13:10 | 790.02 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 16-SEP-13:00 | 1345.39 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1595.41 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3147.96 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5501.45 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.02 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.29 | 5501.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95466.94 | 02-JAN-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95269.64 | 21-FEB-07:03 | 14361.80 | 19658.71 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94908.78 | 16-MAR-06:12 | 21542.70 | 29488.07 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97142.47 | 24-APR-06:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 100437.07 | 30-MAY-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103603.03 | 13-JUN-06:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 106495.86 | 12-JUL-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 109450.30 | 09-AUG-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 108406.19 | 18-SEP-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 105165.75 | 10-OCT-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98739.53 | 13-NOV-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98729.88 | 26-DEC-07:03 | 14361.80 | 19658.71 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94908.78 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 109450.30 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 74601.69 | 17-JAN-06:01 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76431.62 | 24-FEB-06:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80819.06 | 15-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86045.33 | 10-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88340.68 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91565.91 | 28-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88999.17 | 12-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84482.61 | 31-AUG-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89448.97 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85853.16 | 23-OCT-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86960.57 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80588.25 | 18-DEC-05:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 74601.69 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91565.91 | 12897.91 | 5373.60 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19194.39 | 25-JAN-11:10 | 76581.32 | 66205.89 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19084.65 | 03-FEB-09:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73671.05 | 17-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70875.89 | 27-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76302.41 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76161.75 | 29-JUN-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77139.98 | 25-JUL-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76597.13 | 01-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78339.64 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74368.67 | 13-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68453.56 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23641.53 | 01-DEC-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19084.65 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78339.64 | 76581.32 | 66205.89 | 86032.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14300.52 | 12-JAN-17:00 | 30632.53 | 26482.36 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14845.84 | 28-FEB-14:10 | 32029.16 | 26482.36 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71641.12 | 16-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35983.03 | 21-APR-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70725.03 | 17-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75064.15 | 19-JUN-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76635.19 | 22-JUL-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74842.92 | 01-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74871.31 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67473.44 | 13-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23577.45 | 01-NOV-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15211.66 | 01-DEC-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14300.52 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76635.19 | 32029.16 | 26482.36 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2193.99 | 17-JAN-06:02 | 1619.46 | 539.77 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.96 |
February | 2093.73 | 23-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.21 |
March | 7631.35 | 15-MAR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 0.00 |
April | 6878.56 | 07-APR-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
May | 8733.79 | 17-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
June | 15780.79 | 11-JUN-18:41 | 0.00 | 395.49 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.76 |
July | 16112.57 | 16-JUL-16:22 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 0.00 |
August | 15622.46 | 06-AUG-16:21 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 0.00 |
September | 11642.57 | 15-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 |
October | 6362.21 | 23-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 |
November | 4692.97 | 27-NOV-12:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 |
December | 2753.88 | 01-DEC-13:10 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2093.73 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16112.57 | 2010.79 | 791.05 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 126.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1764.99 | 12-JAN-10:05 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.21 |
February | 6143.57 | 28-FEB-09:35 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 |
March | 9201.90 | 21-MAR-08:55 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 |
April | 16101.26 | 23-APR-10:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.30 |
May | 18246.37 | 07-MAY-07:33 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.66 |
June | 23682.58 | 11-JUN-08:41 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.44 |
July | 24818.55 | 04-JUL-07:51 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.61 |
August | 21814.50 | 06-AUG-09:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 |
September | 22114.95 | 10-SEP-08:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 |
October | 11049.97 | 11-OCT-08:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 |
November | 6576.78 | 03-NOV-08:55 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 |
December | 3619.18 | 04-DEC-09:50 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1764.99 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | |
Maximum of Months | 24818.55 | 2591.66 | 1019.56 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24096.96 | 15-JAN-13:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.17 |
February | 17297.88 | 28-FEB-13:20 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.51 |
March | 19020.78 | 15-MAR-13:30 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
April | 20694.66 | 23-APR-14:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.81 |
May | 24643.34 | 14-MAY-13:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 |
June | 24329.45 | 25-JUN-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 |
July | 25284.44 | 16-JUL-15:41 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 | 0.00 |
August | 26085.88 | 27-AUG-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.60 |
September | 27594.25 | 10-SEP-12:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.87 |
October | 24692.50 | 22-OCT-12:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 |
November | 18246.11 | 03-NOV-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.36 |
December | 16985.61 | 17-DEC-11:33 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16985.61 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27594.25 | 2010.83 | 791.06 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 | 750.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4698.28 | 12-JAN-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.45 |
February | 9567.37 | 28-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 |
March | 19058.94 | 26-MAR-16:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.79 |
April | 27168.38 | 02-APR-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.03 |
May | 30065.42 | 07-MAY-16:11 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.32 |
June | 31453.37 | 11-JUN-16:41 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.78 |
July | 31342.55 | 16-JUL-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
August | 31309.21 | 06-AUG-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 |
September | 28565.40 | 10-SEP-17:31 | 0.00 | 198.23 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.81 |
October | 17785.31 | 09-OCT-16:33 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.92 |
November | 15422.75 | 27-NOV-05:12 | 0.00 | 217.40 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.07 |
December | 9006.41 | 14-DEC-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4698.28 | 0.00 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | |
Maximum of Months | 31453.37 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1372.35 | 11-JAN-17:00 | 1923.11 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 |
February | 1413.87 | 17-FEB-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.10 |
March | 5998.96 | 15-MAR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
April | 4588.61 | 07-APR-13:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
May | 7075.61 | 23-MAY-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
June | 13443.28 | 11-JUN-18:41 | 0.00 | 395.49 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.02 |
July | 13972.79 | 16-JUL-16:31 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 | 0.00 |
August | 10340.83 | 11-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
September | 7604.32 | 14-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 |
October | 4215.76 | 12-OCT-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.74 |
November | 2241.39 | 07-NOV-10:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.09 |
December | 1635.70 | 01-DEC-13:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1372.35 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13972.79 | 2010.79 | 1662.56 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 | 273.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1379.93 | 06-JAN-09:55 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.38 |
February | 4094.80 | 28-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.58 |
March | 8820.38 | 21-MAR-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.71 |
April | 17112.54 | 23-APR-10:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.10 |
May | 18423.83 | 21-MAY-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.70 |
June | 25602.51 | 11-JUN-10:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.85 |
July | 24752.49 | 09-JUL-08:12 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 |
August | 23258.94 | 20-AUG-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.23 |
September | 21265.43 | 04-SEP-09:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.49 |
October | 10814.20 | 11-OCT-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
November | 5985.88 | 03-NOV-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 |
December | 1123.55 | 01-DEC-13:10 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1123.55 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | |
Maximum of Months | 25602.51 | 2478.65 | 1019.56 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17399.86 | 15-JAN-13:23 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.61 |
February | 18210.59 | 28-FEB-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.12 |
March | 19323.81 | 01-MAR-13:50 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.11 |
April | 21962.05 | 23-APR-14:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.37 |
May | 24723.18 | 14-MAY-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.31 |
June | 24232.81 | 11-JUN-15:21 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 |
July | 24941.68 | 30-JUL-12:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.86 |
August | 25474.50 | 27-AUG-12:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.53 |
September | 26875.01 | 03-SEP-12:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.99 |
October | 24653.79 | 22-OCT-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.55 |
November | 19280.53 | 03-NOV-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.25 |
December | 12762.79 | 04-DEC-11:50 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12762.79 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.86 | |
Maximum of Months | 26875.01 | 3846.30 | 1582.13 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1614.76 | 12-JAN-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.94 |
February | 6135.30 | 28-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.78 |
March | 9137.18 | 21-MAR-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.18 |
April | 24082.70 | 02-APR-16:11 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.59 |
May | 25120.69 | 07-MAY-16:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.66 |
June | 28912.02 | 11-JUN-16:41 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.32 |
July | 30376.78 | 02-JUL-17:01 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.85 |
August | 26139.43 | 27-AUG-16:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.92 |
September | 24839.14 | 04-SEP-17:02 | 0.00 | 169.91 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.28 |
October | 11945.32 | 11-OCT-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
November | 5256.25 | 15-NOV-15:20 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.18 |
December | 2063.44 | 04-DEC-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1614.76 | 0.00 | 169.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | |
Maximum of Months | 30376.78 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1204.97 | 07-JAN-17:02 | 506.08 | 461.79 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.36 |
February | 1313.41 | 22-FEB-16:50 | 1923.11 | 850.46 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.06 |
March | 6437.12 | 15-MAR-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 0.00 |
April | 4297.17 | 20-APR-15:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.84 |
May | 7314.80 | 23-MAY-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
June | 11795.70 | 18-JUN-11:43 | 404.87 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 |
July | 16614.75 | 02-JUL-18:21 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.42 |
August | 16267.50 | 13-AUG-15:31 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 218.74 | 0.00 |
September | 7282.64 | 15-SEP-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 | 0.00 |
October | 4082.56 | 12-OCT-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.09 |
November | 1832.39 | 16-NOV-17:00 | 1923.11 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.25 |
December | 1386.39 | 01-DEC-13:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1204.97 | 0.00 | 175.78 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16614.75 | 2010.79 | 1662.56 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 218.74 | 776.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 906.01 | 20-JAN-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.47 |
February | 1691.94 | 28-FEB-10:05 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.57 |
March | 6143.01 | 15-MAR-09:30 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
April | 11752.89 | 23-APR-10:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.74 |
May | 16595.04 | 21-MAY-10:53 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.84 |
June | 23380.60 | 11-JUN-09:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.82 |
July | 24829.26 | 04-JUL-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.03 |
August | 21194.35 | 06-AUG-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.88 |
September | 23292.14 | 10-SEP-10:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.03 |
October | 8286.01 | 11-OCT-09:30 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 |
November | 2379.07 | 03-NOV-09:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.39 |
December | 912.61 | 13-DEC-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 906.01 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | |
Maximum of Months | 24829.26 | 2591.66 | 1019.56 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12506.53 | 12-JAN-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 930.41 |
February | 16917.51 | 28-FEB-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.04 |
March | 19161.43 | 15-MAR-13:30 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
April | 19071.43 | 23-APR-14:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.43 |
May | 27034.74 | 14-MAY-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.37 |
June | 26109.99 | 25-JUN-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 |
July | 26866.37 | 30-JUL-12:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.10 |
August | 27690.40 | 13-AUG-12:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 173.18 | 0.00 |
September | 30069.93 | 10-SEP-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.45 |
October | 23401.03 | 22-OCT-14:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.66 |
November | 17065.84 | 03-NOV-12:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.01 |
December | 10211.40 | 16-DEC-13:30 | 202.44 | 131.84 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10211.40 | 202.44 | 131.84 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30069.93 | 2010.83 | 791.06 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 173.18 | 930.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1240.72 | 12-JAN-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.01 |
February | 5790.24 | 28-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.95 |
March | 8492.86 | 21-MAR-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.46 |
April | 18170.84 | 02-APR-16:11 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.57 |
May | 28528.34 | 07-MAY-17:41 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.21 |
June | 27778.09 | 11-JUN-16:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.60 |
July | 31908.73 | 02-JUL-17:01 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.89 |
August | 27334.99 | 13-AUG-15:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | 0.00 |
September | 27796.25 | 10-SEP-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.28 |
October | 11895.48 | 11-OCT-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
November | 4300.60 | 15-NOV-15:20 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 |
December | 1261.55 | 04-DEC-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1240.72 | 0.00 | 198.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31908.73 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | 912.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5987.37 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.40 |
February | 7857.63 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2034.53 |
March | 5182.22 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 0.00 |
April | 6819.18 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.81 |
May | 8263.10 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 |
June | 11145.22 | 28-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.11 |
July | 12845.41 | 24-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 |
August | 11277.43 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 |
September | 9469.96 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 |
October | 6728.57 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.50 |
November | 5303.58 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.74 |
December | 4126.10 | 11-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4126.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12845.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 2034.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9275.03 | 24-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3533.52 |
February | 10261.78 | 21-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3748.56 |
March | 9326.32 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.02 |
April | 5250.72 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
May | 4532.71 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.42 |
June | 6272.22 | 21-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.66 |
July | 7335.10 | 22-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.76 |
August | 7220.90 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.90 |
September | 6081.97 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.79 |
October | 6007.82 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.10 |
November | 7898.18 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.66 |
December | 8691.14 | 27-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3099.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4532.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | |
Maximum of Months | 10261.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3748.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.29 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1442.78 |
March | 11293.19 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
April | 9464.76 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.26 |
May | 13803.20 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.88 |
June | 18465.07 | 12-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.13 | 0.00 |
July | 18103.35 | 21-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.89 | 0.00 |
August | 17722.85 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 | 0.00 |
September | 13464.76 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
October | 7606.42 | 11-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 |
November | 990.12 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18465.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.13 | 1442.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1949.33 | 12-JAN-16:40 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4162.10 | 28-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7000.82 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8202.92 | 02-APR-17:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3473.67 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5391.38 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7288.10 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8244.54 | 02-AUG-18:40 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3239.89 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5165.97 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5848.98 | 24-NOV-16:20 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7739.65 | 04-DEC-16:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1949.33 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8244.54 | 222.14 | 316.63 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1573.33 | 12-JAN-16:50 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3665.92 | 28-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6263.13 | 31-MAR-23:40 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7686.50 | 24-APR-18:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3284.75 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5137.03 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6998.38 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7912.00 | 02-AUG-18:40 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2786.09 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4553.12 | 31-OCT-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5396.34 | 15-NOV-16:20 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6976.12 | 04-DEC-16:30 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1573.33 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7912.00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1343.83 | 12-JAN-16:40 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3601.06 | 28-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5828.53 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7678.97 | 24-APR-18:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3186.87 | 31-MAY-23:40 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5062.17 | 30-JUN-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6982.71 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7965.22 | 02-AUG-18:40 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2498.60 | 04-SEP-17:48 | 0.00 | 87.96 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4141.12 | 31-OCT-23:20 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5264.94 | 15-NOV-16:30 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6620.59 | 04-DEC-16:30 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1343.83 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7965.22 | 222.14 | 316.63 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90431.45 | 18-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182056.92 | 23-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357897.66 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366736.29 | 24-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175662.99 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267991.02 | 30-JUN-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360089.58 | 31-JUL-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 378592.97 | 15-AUG-16:41 | 12148.24 | 18476.25 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175484.92 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268099.09 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275752.75 | 06-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366624.61 | 04-DEC-16:55 | 9617.36 | 8314.37 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90431.45 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 378592.97 | 12148.24 | 18476.25 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.159402E+13 | 1142228.99 | 13-JAN-16:00 | 0.379344E+12 | 1582955.37 | 02-JAN-05:10 |
February | 0.182033E+13 | 1255375.17 | 28-FEB-16:10 | 0.293776E+12 | 1206922.70 | 06-FEB-06:10 |
March | 0.239966E+13 | 1675183.36 | 15-MAR-14:30 | 0.952545E+11 | 701868.43 | 06-MAR-05:10 |
April | 0.261452E+13 | 1694241.92 | 07-APR-14:09 | 0.181631E+11 | 537210.15 | 11-APR-13:30 |
May | 0.165195E+13 | 1459249.92 | 23-MAY-14:20 | 0.173625E+10 | 376726.55 | 11-MAY-13:20 |
June | 0.213332E+13 | 1692698.58 | 27-JUN-07:40 | 0.247228E+09 | 175273.88 | 13-JUN-11:09 |
July | 0.273082E+13 | 2011554.08 | 05-JUL-15:50 | 3086.16 | 5.14 | 02-JUL-22:00 |
August | 0.310373E+13 | 2111016.45 | 15-AUG-14:39 | 3144979.35 | 5240.98 | 31-AUG-11:09 |
September | 0.160754E+13 | 1502027.89 | 15-SEP-10:30 | 0.517143E+09 | 149085.79 | 28-SEP-09:00 |
October | 0.193825E+13 | 1381849.13 | 11-OCT-15:00 | 0.148571E+11 | 405146.88 | 30-OCT-05:10 |
November | 0.230214E+13 | 1471053.35 | 15-NOV-16:49 | 0.561611E+11 | 614642.23 | 24-NOV-05:10 |
December | 0.270260E+13 | 1561779.38 | 18-DEC-16:40 | 0.291000E+12 | 1210366.87 | 11-DEC-06:10 |
Annual Sum or Average | 0.265989E+14 | 0.115106E+13 | ||||
Minimum of Months | 0.159402E+13 | 1142228.99 | 3086.16 | 5.14 | ||
Maximum of Months | 0.310373E+13 | 2111016.45 | 0.379344E+12 | 1582955.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.208761E+12 | 0.418459E+11 | 0.766053E+12 | 0.213316E+12 | 0.161985E+12 | 0.113320E+11 | 0.00 | 0.672433E+10 | 0.357029E+09 | 0.135489E+12 | 0.579087E+10 | 0.423658E+11 | 0.00 |
February | 0.187603E+12 | 0.331640E+11 | 0.978954E+12 | 0.195308E+12 | 0.146445E+12 | 0.105466E+11 | 0.00 | 0.199553E+11 | 0.106205E+10 | 0.203006E+12 | 0.525097E+10 | 0.390359E+11 | 0.00 |
March | 0.220884E+12 | 0.306117E+11 | 0.141687E+13 | 0.226028E+12 | 0.173457E+12 | 0.191459E+11 | 0.00 | 0.529230E+11 | 0.906699E+10 | 0.200431E+12 | 0.495231E+10 | 0.452818E+11 | 0.00 |
April | 0.195941E+12 | 0.239964E+11 | 0.165903E+13 | 0.211475E+12 | 0.181207E+12 | 0.206688E+11 | 0.00 | 0.638795E+11 | 0.105213E+11 | 0.205584E+12 | 0.270912E+10 | 0.395101E+11 | 0.00 |
May | 0.210789E+12 | 0.203868E+11 | 0.774844E+12 | 0.219671E+12 | 0.210798E+12 | 0.286500E+11 | 0.00 | 0.417277E+11 | 0.241317E+11 | 0.805646E+11 | 0.529980E+09 | 0.398586E+11 | 0.00 |
June | 0.209452E+12 | 0.181304E+11 | 0.106252E+13 | 0.217906E+12 | 0.240744E+12 | 0.456288E+11 | 0.00 | 0.174385E+12 | 0.860417E+11 | 0.404814E+11 | 0.914091E+09 | 0.371224E+11 | 0.00 |
July | 0.195870E+12 | 0.192056E+11 | 0.139340E+13 | 0.213239E+12 | 0.259362E+12 | 0.621490E+11 | 0.00 | 0.408040E+12 | 0.141160E+12 | 0.242952E+10 | 0.229989E+10 | 0.336581E+11 | 0.00 |
August | 0.219001E+12 | 0.227669E+11 | 0.173200E+13 | 0.226028E+12 | 0.259353E+12 | 0.582126E+11 | 0.00 | 0.417301E+12 | 0.126788E+12 | 0.439043E+10 | 0.173410E+10 | 0.361503E+11 | 0.00 |
September | 0.196622E+12 | 0.269873E+11 | 0.740713E+12 | 0.211475E+12 | 0.210890E+12 | 0.365960E+11 | 0.00 | 0.830596E+11 | 0.569076E+11 | 0.105034E+11 | 0.389954E+09 | 0.333998E+11 | 0.00 |
October | 0.205922E+12 | 0.340751E+11 | 0.108340E+13 | 0.213315E+12 | 0.185567E+12 | 0.225178E+11 | 0.00 | 0.388531E+11 | 0.113462E+11 | 0.104880E+12 | 0.224887E+10 | 0.361217E+11 | 0.00 |
November | 0.207031E+12 | 0.387231E+11 | 0.135889E+13 | 0.205270E+12 | 0.167920E+12 | 0.192821E+11 | 0.00 | 0.414216E+11 | 0.765912E+10 | 0.214037E+12 | 0.425265E+10 | 0.376516E+11 | 0.00 |
December | 0.203286E+12 | 0.433902E+11 | 0.170972E+13 | 0.213241E+12 | 0.163185E+12 | 0.120058E+11 | 0.00 | 0.482555E+11 | 0.290385E+10 | 0.261257E+12 | 0.566115E+10 | 0.396972E+11 | 0.00 |
Annual Sum or Average | 0.246116E+13 | 0.353283E+12 | 0.146764E+14 | 0.256627E+13 | 0.236091E+13 | 0.346735E+12 | 0.00 | 0.139653E+13 | 0.477945E+12 | 0.146305E+13 | 0.367340E+11 | 0.459853E+12 | 0.00 |
Minimum of Months | 0.187603E+12 | 0.181304E+11 | 0.740713E+12 | 0.195308E+12 | 0.146445E+12 | 0.105466E+11 | 0.00 | 0.672433E+10 | 0.357029E+09 | 0.242952E+10 | 0.389954E+09 | 0.333998E+11 | 0.00 |
Maximum of Months | 0.220884E+12 | 0.433902E+11 | 0.173200E+13 | 0.226028E+12 | 0.259362E+12 | 0.621490E+11 | 0.00 | 0.417301E+12 | 0.141160E+12 | 0.261257E+12 | 0.579087E+10 | 0.452818E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.379344E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.293776E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.952545E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.181631E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.173625E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.247228E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3086.16 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3144979.35 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.517143E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148571E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.561611E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.291000E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115106E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3086.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.379344E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-16:49 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233392.71 | 11-JAN-08:20 | 97244.99 | 02-JAN-06:19 | 22690.32 | 24-JAN-21:00 | 0.00 | 01-JAN-00:10 |
February | 237543.70 | 01-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233391.96 | 01-FEB-08:20 | 88022.13 | 28-FEB-15:30 | 22821.68 | 06-FEB-05:49 | 0.00 | 01-FEB-00:10 |
March | 225303.82 | 17-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233385.70 | 17-MAR-07:19 | 174346.37 | 15-MAR-14:30 | 43491.63 | 15-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 217495.61 | 12-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233381.57 | 12-APR-07:19 | 178018.78 | 21-APR-14:00 | 22901.25 | 20-APR-13:20 | 0.00 | 01-APR-00:10 |
May | 215250.65 | 11-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233380.38 | 11-MAY-07:19 | 199356.33 | 23-MAY-14:30 | 42988.66 | 10-MAY-14:50 | 0.00 | 01-MAY-00:10 |
June | 213197.40 | 21-JUN-08:09 | 27558.46 | 01-JUN-19:49 | 541788.89 | 01-JUN-07:10 | 233379.11 | 19-JUN-07:19 | 233316.58 | 28-JUN-15:39 | 47145.70 | 01-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 214802.79 | 11-JUL-07:30 | 27558.46 | 01-JUL-19:00 | 660080.29 | 03-JUL-07:10 | 233380.14 | 11-JUL-07:40 | 254310.68 | 18-JUL-15:30 | 48849.73 | 05-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 215255.89 | 24-AUG-07:10 | 40855.88 | 02-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233380.38 | 24-AUG-07:19 | 274878.55 | 10-AUG-15:20 | 48040.12 | 03-AUG-13:30 | 0.00 | 01-AUG-00:10 |
September | 223771.33 | 26-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233384.89 | 26-SEP-07:19 | 221722.90 | 19-SEP-15:50 | 45270.29 | 20-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 239882.01 | 30-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233393.42 | 30-OCT-07:19 | 165117.22 | 11-OCT-15:00 | 24137.41 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 06-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233396.00 | 02-NOV-07:19 | 122873.48 | 03-NOV-15:09 | 22806.74 | 16-NOV-13:09 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-16:40 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233393.44 | 18-DEC-08:20 | 88883.77 | 11-DEC-06:10 | 22656.65 | 04-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 213197.40 | 27558.46 | 423497.50 | 233379.11 | 88022.13 | 22656.65 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233396.00 | 274878.55 | 48849.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6168.22 | 12-JAN-16:40 | 571.39 | 11-JAN-15:00 | 78825.19 | 13-JAN-17:00 | 4520.72 | 02-JAN-07:10 | 56183.54 | 31-JAN-12:00 | 0.00 |
February | 14864.03 | 22-FEB-16:00 | 2006.27 | 22-FEB-17:00 | 100000.00 | 14-FEB-22:10 | 4520.72 | 01-FEB-07:10 | 56293.54 | 13-FEB-12:30 | 0.00 |
March | 285357.31 | 14-MAR-13:20 | 79472.29 | 14-MAR-12:20 | 100000.00 | 01-MAR-04:49 | 4520.72 | 01-MAR-07:10 | 56194.37 | 01-MAR-12:30 | 0.00 |
April | 128373.85 | 07-APR-13:00 | 44804.94 | 08-APR-13:20 | 100000.00 | 01-APR-05:10 | 4520.72 | 01-APR-06:10 | 54960.36 | 04-APR-11:39 | 0.00 |
May | 214372.35 | 10-MAY-13:00 | 79472.29 | 10-MAY-13:39 | 100000.00 | 07-MAY-13:39 | 4520.72 | 01-MAY-06:10 | 52289.29 | 01-MAY-11:39 | 0.00 |
June | 401446.42 | 27-JUN-07:40 | 79472.29 | 01-JUN-14:30 | 100000.00 | 03-JUN-17:49 | 4520.72 | 01-JUN-16:49 | 48862.36 | 01-JUN-11:20 | 0.00 |
July | 528085.65 | 05-JUL-15:50 | 79472.29 | 03-JUL-12:20 | 100000.00 | 06-JUL-13:20 | 4520.72 | 03-JUL-14:09 | 46097.26 | 03-JUL-11:00 | 0.00 |
August | 519084.85 | 15-AUG-14:39 | 79472.29 | 02-AUG-13:30 | 88811.05 | 22-AUG-13:00 | 4520.72 | 03-AUG-11:00 | 44705.39 | 01-AUG-11:39 | 0.00 |
September | 299900.55 | 15-SEP-10:00 | 79472.29 | 08-SEP-12:50 | 70653.04 | 19-SEP-13:00 | 4520.72 | 06-SEP-06:10 | 46042.68 | 29-SEP-11:30 | 0.00 |
October | 135460.93 | 11-OCT-14:00 | 48215.67 | 11-OCT-14:00 | 100000.00 | 30-OCT-21:10 | 4520.72 | 02-OCT-06:10 | 48758.19 | 31-OCT-11:20 | 0.00 |
November | 69159.78 | 16-NOV-13:09 | 44517.05 | 16-NOV-13:09 | 100000.00 | 01-NOV-04:19 | 4520.72 | 01-NOV-06:10 | 52161.86 | 30-NOV-12:39 | 0.00 |
December | 34995.16 | 01-DEC-10:00 | 6320.38 | 01-DEC-10:00 | 100000.00 | 01-DEC-22:10 | 4520.72 | 01-DEC-17:10 | 54873.32 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 6168.22 | 571.39 | 70653.04 | 4520.72 | 44705.39 | 0.00 | |||||
Maximum of Months | 528085.65 | 79472.29 | 100000.00 | 4520.72 | 56293.54 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1142228.99 | 13-JAN-16:00 | 247210.90 | 423497.50 | 40855.88 | 233278.49 | 68357.12 | 3819.14 | 0.00 | 5031.12 | 344.20 |
February | 1255375.17 | 28-FEB-16:10 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 85181.93 | 22604.44 | 0.00 | 12467.77 | 718.39 |
March | 1675183.36 | 15-MAR-14:30 | 212815.01 | 660080.29 | 0.00 | 233115.89 | 174346.37 | 42456.01 | 0.00 | 236390.54 | 79472.29 |
April | 1694241.92 | 07-APR-14:09 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 146406.02 | 22754.39 | 0.00 | 124965.67 | 44275.93 |
May | 1459249.92 | 23-MAY-14:20 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 194926.00 | 23299.13 | 0.00 | 181025.08 | 61624.27 |
June | 1692698.58 | 27-JUN-07:40 | 212815.01 | 541788.89 | 0.00 | 233379.09 | 150425.25 | 44581.28 | 0.00 | 401446.42 | 79472.29 |
July | 2011554.08 | 05-JUL-15:50 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 215127.25 | 47143.35 | 0.00 | 528085.65 | 79472.29 |
August | 2111016.45 | 15-AUG-14:39 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 215937.80 | 46481.66 | 0.00 | 519084.85 | 79472.29 |
September | 1502027.89 | 15-SEP-10:30 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 195332.41 | 44294.74 | 0.00 | 275799.99 | 79472.29 |
October | 1381849.13 | 11-OCT-15:00 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 165117.22 | 23554.75 | 0.00 | 121418.01 | 47177.57 |
November | 1471053.35 | 15-NOV-16:49 | 247210.90 | 660080.29 | 40855.88 | 233280.27 | 95011.63 | 22627.39 | 0.00 | 29428.79 | 2064.72 |
December | 1561779.38 | 18-DEC-16:40 | 247210.90 | 778371.69 | 40855.88 | 233282.27 | 79289.83 | 22604.29 | 0.00 | 18886.09 | 1419.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1142228.99 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 68357.12 | 3819.14 | 0.00 | 5031.12 | 344.20 | |
Maximum of Months | 2111016.45 | 247210.90 | 778371.69 | 40855.88 | 233379.09 | 215937.80 | 47143.35 | 0.00 | 528085.65 | 79472.29 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1582955.37 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1206922.70 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 701868.43 | 06-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 537210.15 | 11-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 376726.55 | 11-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 175273.88 | 13-JUN-11:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5.14 | 02-JUL-22:00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5240.98 | 31-AUG-11:09 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 149085.79 | 28-SEP-09:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 405146.88 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 614642.23 | 24-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1210366.87 | 11-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 5.14 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1582955.37 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 25.74 | 25.00 | 25.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 25.76 | 23.00 | 25.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 26.03 | 27.83 | 26.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 26.26 | 26.00 | 26.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 68.00 | 26.47 | 35.17 | 26.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 195.00 | 27.49 | 134.83 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 395.83 | 27.78 | 251.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 252.83 | 27.74 | 156.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 153.17 | 27.24 | 85.67 | 27.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 26.88 | 37.50 | 26.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 26.75 | 32.67 | 26.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 | 26.17 | 25.67 | 26.16 |
Annual Sum or Average | 0.00 | 0.00 | 1461.83 | 27.22 | 860.67 | 27.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 25.74 | 23.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 395.83 | 27.78 | 251.00 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.67 | 0.00 | 25.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.68 | 0.00 | 25.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 25.65 | 0.00 | 25.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.68 | 0.00 | 25.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.36 | 0.67 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 19.36 | 0.67 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.36 | 0.67 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 18.76 | 1.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 4.00 | 18.80 | 0.83 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
March | 0.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
April | 0.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 3.67 | 18.60 | 0.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Annual Sum or Average | 14.67 | 18.76 | 2.83 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 19.25 | 1.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.99 | 2.67 | 27.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.92 | 1.83 | 27.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.21 | 0.00 | 19.21 | 6.67 | 26.42 | 4.50 | 26.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.21 | 0.00 | 19.21 | 4.17 | 26.99 | 2.67 | 27.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
February | 0.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.94 | 1.00 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 3.50 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 7.83 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.70 | 11.83 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.60 | 5.50 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.85 | 4.33 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.63 | 0.67 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Annual Sum or Average | 0.83 | 19.23 | 0.00 | 19.23 | 35.67 | 27.52 | 34.67 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.44 | 0.00 | 19.44 | 12.83 | 27.94 | 11.83 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.18 | 0.00 | 19.18 | 0.67 | 23.37 | 0.67 | 24.77 |
February | 0.83 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.57 | 0.83 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.69 | 2.33 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 3.00 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.61 | 5.33 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.55 | 9.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.55 | 7.50 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.08 | 5.50 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.30 | 5.17 | 26.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
December | 0.33 | 19.26 | 0.00 | 19.26 | 0.67 | 24.87 | 0.67 | 25.99 |
Annual Sum or Average | 1.83 | 19.08 | 0.00 | 19.08 | 44.83 | 27.16 | 41.33 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 | 0.00 | 18.93 |
Maximum of Months | 0.83 | 19.26 | 0.00 | 19.26 | 11.67 | 28.08 | 9.50 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.69 | 2.00 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.98 | 6.83 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.17 | 4.00 | 28.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.85 | 8.50 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 27.69 | 15.00 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.58 | 12.00 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.11 | 4.17 | 28.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.67 | 1.33 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.43 | 0.17 | 26.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 115.83 | 27.75 | 54.00 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 28.17 | 15.00 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.83 | 18.40 | 6.83 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
February | 23.50 | 18.34 | 7.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 4.33 | 18.82 | 0.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
April | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 18.33 | 18.33 | 5.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
Annual Sum or Average | 71.50 | 18.39 | 19.83 | 18.73 | 1.00 | 18.83 | 1.00 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.83 | 19.43 | 7.17 | 19.43 | 1.00 | 27.33 | 1.00 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
February | 18.50 | 18.08 | 0.17 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
March | 2.33 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.79 | 1.00 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.80 | 2.83 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.82 | 8.17 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.91 | 11.50 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.71 | 5.83 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.92 | 3.67 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 23.83 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
Annual Sum or Average | 71.17 | 18.45 | 0.17 | 18.46 | 33.67 | 21.47 | 33.00 | 22.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.17 | 19.22 | 0.17 | 19.22 | 12.00 | 27.92 | 11.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 17.93 | 0.17 | 17.97 | 0.50 | 18.44 | 0.50 | 18.87 |
February | 8.83 | 17.65 | 0.17 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
March | 1.50 | 19.06 | 0.00 | 19.06 | 0.67 | 21.67 | 0.67 | 23.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.71 | 1.83 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.61 | 2.67 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.61 | 4.50 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.72 | 8.50 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.85 | 5.67 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.93 | 6.00 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.81 | 9.50 | 25.81 |
November | 0.17 | 19.29 | 0.00 | 19.29 | 0.17 | 23.33 | 0.17 | 24.68 |
December | 7.50 | 18.12 | 0.17 | 18.17 | 0.17 | 18.37 | 0.17 | 18.56 |
Annual Sum or Average | 27.50 | 17.96 | 0.50 | 18.00 | 41.33 | 23.55 | 40.17 | 24.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 | 17.69 |
Maximum of Months | 9.50 | 19.29 | 0.17 | 19.29 | 9.50 | 27.93 | 9.50 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
February | 8.50 | 17.80 | 0.17 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
March | 1.67 | 19.07 | 0.00 | 19.07 | 0.17 | 19.82 | 0.17 | 20.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 2.33 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.12 | 3.00 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.37 | 4.67 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.12 | 7.33 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.98 | 4.83 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.22 | 3.00 | 28.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 6.17 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
Annual Sum or Average | 24.00 | 18.14 | 0.17 | 18.15 | 45.50 | 24.66 | 25.33 | 25.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 19.43 | 0.17 | 19.43 | 14.50 | 28.37 | 7.33 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.00 | 17.12 | 27.33 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
February | 65.83 | 17.00 | 24.33 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
March | 24.00 | 17.83 | 7.50 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
April | 2.67 | 19.08 | 0.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.51 | 1.50 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.39 | 1.83 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 18.86 | 0.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
November | 7.17 | 18.93 | 1.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
December | 57.00 | 17.07 | 20.50 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
Annual Sum or Average | 230.67 | 17.24 | 81.83 | 17.53 | 5.50 | 17.70 | 4.33 | 17.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.00 | 19.08 | 27.33 | 19.28 | 2.50 | 27.51 | 1.83 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 15.52 | 5.67 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
February | 31.00 | 15.50 | 3.33 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
March | 11.00 | 16.71 | 0.33 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
April | 1.33 | 18.57 | 0.00 | 18.57 | 0.50 | 21.02 | 0.50 | 22.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.78 | 1.67 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.84 | 8.33 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.93 | 12.00 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.70 | 7.00 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.85 | 2.33 | 27.85 |
October | 1.33 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
November | 4.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
December | 30.83 | 15.60 | 5.33 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
Annual Sum or Average | 113.50 | 15.82 | 14.67 | 15.71 | 34.50 | 18.29 | 31.83 | 19.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 0.00 | 15.42 |
Maximum of Months | 34.00 | 18.57 | 5.67 | 18.57 | 13.67 | 27.93 | 12.00 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.83 | 16.06 | 3.83 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
February | 32.33 | 16.18 | 3.67 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
March | 8.00 | 17.47 | 0.33 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
April | 1.33 | 18.70 | 0.00 | 18.70 | 1.17 | 22.87 | 1.17 | 24.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.70 | 2.17 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.68 | 5.00 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.82 | 9.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.96 | 6.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.19 | 4.83 | 28.20 |
October | 1.00 | 18.39 | 0.00 | 18.39 | 2.50 | 23.82 | 2.50 | 24.73 |
November | 3.33 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
December | 25.17 | 16.26 | 2.83 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
Annual Sum or Average | 103.00 | 16.40 | 10.67 | 16.38 | 33.50 | 18.96 | 30.67 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 0.00 | 16.03 |
Maximum of Months | 32.33 | 18.71 | 3.83 | 18.71 | 10.33 | 28.19 | 9.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.67 | 15.71 | 4.67 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
February | 20.83 | 16.06 | 1.67 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
March | 5.67 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
April | 0.50 | 18.84 | 0.00 | 18.84 | 2.33 | 26.09 | 1.67 | 26.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.08 | 3.50 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.39 | 5.00 | 28.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 28.20 | 8.33 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.05 | 5.17 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.09 | 3.17 | 28.15 |
October | 0.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
November | 2.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
December | 18.67 | 16.18 | 2.00 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
Annual Sum or Average | 79.00 | 16.22 | 8.33 | 16.10 | 48.00 | 20.38 | 26.83 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 | 15.60 |
Maximum of Months | 29.67 | 18.84 | 4.67 | 18.84 | 15.83 | 28.39 | 8.33 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 28.42 | 14.17 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 99.33 | 29.24 | 78.33 | 29.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 127.67 | 29.05 | 92.50 | 29.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 99.33 | 29.24 | 78.33 | 29.20 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.83 | 24.11 | 42.67 | 24.33 | 13.83 | 24.41 |
February | 273.50 | 24.01 | 24.83 | 24.19 | 0.00 | 24.19 |
March | 187.50 | 24.00 | 115.17 | 24.47 | 0.00 | 24.47 |
April | 31.50 | 24.00 | 122.83 | 25.71 | 0.00 | 25.71 |
May | 23.33 | 24.00 | 204.17 | 25.29 | 0.00 | 25.29 |
June | 118.33 | 27.50 | 373.17 | 26.22 | 118.33 | 26.46 |
July | 211.83 | 28.09 | 487.00 | 26.81 | 211.83 | 27.10 |
August | 139.67 | 27.93 | 481.17 | 26.12 | 139.67 | 26.45 |
September | 57.83 | 27.31 | 394.17 | 25.45 | 57.83 | 25.66 |
October | 4.33 | 25.04 | 242.50 | 25.47 | 1.17 | 25.48 |
November | 38.67 | 24.19 | 156.67 | 25.66 | 2.00 | 25.68 |
December | 175.50 | 24.00 | 100.50 | 24.79 | 0.00 | 24.79 |
Annual Sum or Average | 1574.83 | 25.31 | 2744.83 | 25.57 | 544.67 | 25.82 |
Minimum of Months | 4.33 | 24.00 | 24.83 | 24.19 | 0.00 | 24.19 |
Maximum of Months | 312.83 | 28.09 | 487.00 | 26.81 | 211.83 | 27.10 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 430.17 | 23.89 | 12.83 | 23.91 | 12.83 | 23.93 |
February | 349.83 | 23.93 | 7.00 | 23.96 | 0.00 | 23.96 |
March | 187.33 | 24.00 | 94.50 | 24.24 | 0.00 | 24.24 |
April | 24.83 | 24.01 | 94.83 | 25.14 | 0.00 | 25.14 |
May | 33.67 | 24.00 | 172.17 | 24.60 | 0.00 | 24.60 |
June | 0.00 | 0.00 | 368.83 | 24.35 | 0.00 | 24.35 |
July | 0.00 | 0.00 | 488.33 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 489.83 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 363.17 | 24.44 | 0.00 | 24.44 |
October | 13.33 | 23.99 | 205.00 | 24.83 | 0.00 | 24.83 |
November | 59.00 | 24.00 | 102.50 | 25.00 | 0.00 | 25.00 |
December | 223.50 | 23.98 | 50.83 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 1321.67 | 23.94 | 2449.83 | 24.34 | 12.83 | 24.34 |
Minimum of Months | 0.00 | 0.00 | 7.00 | 23.91 | 0.00 | 23.93 |
Maximum of Months | 430.17 | 24.01 | 489.83 | 25.14 | 12.83 | 25.14 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.09 | 54.83 | 21.89 | 54.83 | 21.73 |
February | 454.00 | 22.36 | 21.50 | 22.30 | 21.50 | 22.25 |
March | 414.83 | 23.38 | 30.83 | 23.43 | 0.00 | 23.43 |
April | 268.50 | 23.69 | 12.83 | 23.76 | 0.00 | 23.76 |
May | 119.67 | 23.84 | 133.50 | 24.21 | 0.00 | 24.21 |
June | 21.17 | 23.89 | 298.00 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 475.67 | 24.23 | 0.00 | 24.23 |
August | 0.00 | 0.00 | 445.67 | 24.23 | 0.00 | 24.23 |
September | 18.50 | 23.64 | 263.83 | 24.32 | 0.00 | 24.32 |
October | 217.83 | 23.70 | 62.50 | 23.87 | 0.00 | 23.87 |
November | 377.83 | 23.52 | 5.50 | 23.54 | 0.00 | 23.54 |
December | 489.50 | 22.50 | 19.83 | 22.44 | 19.83 | 22.38 |
Annual Sum or Average | 2883.83 | 22.94 | 1824.50 | 23.39 | 96.17 | 23.33 |
Minimum of Months | 0.00 | 0.00 | 5.50 | 21.89 | 0.00 | 21.73 |
Maximum of Months | 502.00 | 23.89 | 475.67 | 24.32 | 54.83 | 24.32 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.76 | 277.33 | 20.50 | 277.33 | 20.38 |
February | 454.00 | 20.99 | 219.50 | 20.69 | 219.50 | 20.54 |
March | 457.50 | 22.00 | 127.83 | 21.81 | 105.67 | 21.60 |
April | 402.17 | 22.90 | 18.33 | 22.79 | 17.50 | 22.69 |
May | 212.67 | 23.54 | 84.50 | 23.75 | 0.00 | 23.75 |
June | 47.33 | 23.70 | 292.67 | 24.15 | 0.00 | 24.15 |
July | 0.50 | 23.77 | 469.17 | 24.28 | 0.00 | 24.28 |
August | 4.50 | 23.56 | 432.50 | 24.24 | 0.00 | 24.24 |
September | 116.00 | 23.39 | 216.67 | 23.95 | 2.67 | 23.96 |
October | 381.50 | 22.62 | 37.50 | 22.59 | 20.00 | 22.50 |
November | 484.33 | 22.07 | 64.33 | 21.87 | 64.33 | 21.71 |
December | 497.00 | 20.92 | 229.50 | 20.65 | 229.50 | 20.51 |
Annual Sum or Average | 3559.50 | 21.89 | 2469.83 | 22.22 | 936.50 | 21.94 |
Minimum of Months | 0.50 | 20.76 | 18.33 | 20.50 | 0.00 | 20.38 |
Maximum of Months | 502.00 | 23.77 | 469.17 | 24.28 | 277.33 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.30 | 197.17 | 21.15 | 197.17 | 21.06 |
February | 454.00 | 21.60 | 121.00 | 21.43 | 121.00 | 21.31 |
March | 424.50 | 22.57 | 68.67 | 22.54 | 37.17 | 22.43 |
April | 309.00 | 23.44 | 21.00 | 23.55 | 0.00 | 23.55 |
May | 167.17 | 23.68 | 115.67 | 24.06 | 0.00 | 24.06 |
June | 12.83 | 25.31 | 353.83 | 24.43 | 6.50 | 24.47 |
July | 27.00 | 26.72 | 486.67 | 24.57 | 27.00 | 24.68 |
August | 12.00 | 26.67 | 467.83 | 24.38 | 11.50 | 24.43 |
September | 60.83 | 23.47 | 267.67 | 24.19 | 0.00 | 24.19 |
October | 319.17 | 23.34 | 44.83 | 23.48 | 0.00 | 23.48 |
November | 430.67 | 23.05 | 9.17 | 23.09 | 0.00 | 23.09 |
December | 492.67 | 21.92 | 68.50 | 21.78 | 68.50 | 21.67 |
Annual Sum or Average | 3211.83 | 22.50 | 2222.00 | 22.99 | 468.83 | 22.86 |
Minimum of Months | 12.00 | 21.30 | 9.17 | 21.15 | 0.00 | 21.06 |
Maximum of Months | 502.00 | 26.72 | 486.67 | 24.57 | 197.17 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.51 | 177.17 | 21.31 | 177.17 | 21.19 |
February | 449.50 | 21.77 | 113.33 | 21.57 | 113.33 | 21.43 |
March | 396.67 | 22.72 | 63.50 | 22.73 | 26.00 | 22.64 |
April | 249.83 | 23.29 | 78.67 | 23.62 | 2.33 | 23.65 |
May | 125.83 | 23.90 | 213.17 | 24.35 | 11.17 | 24.43 |
June | 42.00 | 26.12 | 403.83 | 24.59 | 30.50 | 24.74 |
July | 50.00 | 26.92 | 490.00 | 24.71 | 50.00 | 24.90 |
August | 32.83 | 26.29 | 464.33 | 24.47 | 27.50 | 24.59 |
September | 59.50 | 24.17 | 332.83 | 24.42 | 13.00 | 24.51 |
October | 263.50 | 23.19 | 94.67 | 23.57 | 1.00 | 23.58 |
November | 416.83 | 22.81 | 14.50 | 22.90 | 0.00 | 22.90 |
December | 495.83 | 21.68 | 103.83 | 21.52 | 103.83 | 21.41 |
Annual Sum or Average | 3084.33 | 22.54 | 2549.83 | 23.14 | 555.83 | 23.06 |
Minimum of Months | 32.83 | 21.51 | 14.50 | 21.31 | 0.00 | 21.19 |
Maximum of Months | 502.00 | 26.92 | 490.00 | 24.71 | 177.17 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.50 | 21.52 | 190.67 | 21.31 | 184.00 | 21.15 |
February | 413.17 | 21.79 | 137.33 | 21.54 | 131.33 | 21.37 |
March | 334.00 | 22.67 | 96.83 | 22.88 | 25.83 | 22.77 |
April | 252.00 | 23.25 | 97.17 | 23.60 | 9.50 | 23.61 |
May | 157.33 | 23.67 | 188.00 | 24.18 | 8.00 | 24.24 |
June | 46.00 | 25.08 | 377.67 | 24.47 | 19.67 | 24.58 |
July | 42.83 | 26.91 | 480.50 | 24.69 | 42.83 | 24.85 |
August | 30.17 | 26.68 | 472.00 | 24.51 | 27.33 | 24.64 |
September | 66.17 | 24.59 | 353.50 | 24.51 | 22.00 | 24.64 |
October | 225.33 | 23.20 | 148.83 | 23.75 | 7.17 | 23.81 |
November | 362.83 | 22.73 | 60.67 | 23.01 | 2.00 | 23.00 |
December | 460.17 | 21.82 | 127.17 | 21.70 | 113.83 | 21.55 |
Annual Sum or Average | 2855.50 | 22.56 | 2730.33 | 23.19 | 593.50 | 23.09 |
Minimum of Months | 30.17 | 21.52 | 60.67 | 21.31 | 2.00 | 21.15 |
Maximum of Months | 465.50 | 26.91 | 480.50 | 24.69 | 184.00 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.33 | 22.11 | 71.83 | 21.98 | 69.50 | 21.86 |
February | 425.17 | 22.84 | 24.33 | 22.78 | 19.83 | 22.70 |
March | 215.67 | 23.77 | 132.83 | 24.08 | 6.33 | 24.14 |
April | 47.50 | 25.29 | 226.00 | 25.05 | 19.33 | 25.19 |
May | 58.33 | 25.08 | 272.00 | 24.81 | 22.50 | 24.95 |
June | 43.17 | 27.01 | 457.33 | 24.79 | 43.17 | 24.97 |
July | 107.50 | 26.62 | 497.00 | 25.03 | 107.50 | 25.27 |
August | 79.50 | 26.48 | 514.00 | 24.81 | 79.50 | 25.01 |
September | 35.67 | 26.46 | 395.83 | 24.72 | 30.17 | 24.87 |
October | 86.33 | 24.04 | 204.33 | 24.50 | 4.83 | 24.54 |
November | 178.50 | 23.92 | 81.50 | 24.30 | 0.00 | 24.30 |
December | 359.67 | 23.56 | 12.50 | 23.61 | 0.00 | 23.61 |
Annual Sum or Average | 2131.33 | 23.61 | 2889.50 | 24.16 | 402.67 | 24.25 |
Minimum of Months | 35.67 | 22.11 | 12.50 | 21.98 | 0.00 | 21.86 |
Maximum of Months | 494.33 | 27.01 | 514.00 | 25.05 | 107.50 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 463.83 | 20.08 | 463.83 | 20.06 |
February | 454.00 | 20.25 | 399.83 | 20.20 | 399.83 | 20.18 |
March | 477.00 | 21.23 | 236.50 | 21.05 | 218.17 | 20.90 |
April | 444.50 | 22.30 | 36.33 | 22.16 | 35.17 | 22.04 |
May | 265.67 | 23.25 | 73.83 | 23.50 | 0.00 | 23.50 |
June | 64.50 | 24.02 | 291.33 | 24.25 | 9.67 | 24.29 |
July | 23.00 | 25.72 | 466.67 | 24.46 | 22.00 | 24.52 |
August | 33.00 | 23.95 | 406.50 | 24.25 | 5.83 | 24.28 |
September | 177.33 | 23.22 | 175.17 | 23.72 | 9.50 | 23.78 |
October | 442.67 | 22.17 | 45.17 | 22.09 | 36.33 | 21.99 |
November | 489.00 | 21.29 | 141.83 | 21.09 | 141.83 | 20.97 |
December | 497.00 | 20.25 | 410.50 | 20.17 | 410.50 | 20.14 |
Annual Sum or Average | 3869.67 | 21.41 | 3147.50 | 21.70 | 1752.67 | 21.43 |
Minimum of Months | 23.00 | 20.11 | 36.33 | 20.08 | 0.00 | 20.06 |
Maximum of Months | 502.00 | 25.72 | 466.67 | 24.46 | 463.83 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.10 | 388.17 | 20.05 | 388.17 | 20.03 |
February | 385.00 | 20.37 | 305.00 | 20.22 | 305.00 | 20.17 |
March | 389.50 | 21.72 | 138.00 | 21.53 | 117.67 | 21.33 |
April | 287.33 | 22.50 | 61.33 | 22.77 | 12.83 | 22.71 |
May | 163.50 | 23.55 | 153.33 | 24.13 | 10.83 | 24.23 |
June | 61.33 | 25.44 | 317.50 | 24.67 | 33.83 | 24.85 |
July | 62.50 | 26.73 | 413.50 | 24.90 | 62.50 | 25.11 |
August | 44.67 | 25.69 | 369.50 | 24.61 | 29.50 | 24.76 |
September | 111.50 | 23.75 | 239.50 | 24.31 | 20.67 | 24.44 |
October | 314.83 | 22.43 | 65.67 | 22.61 | 18.50 | 22.52 |
November | 404.00 | 21.48 | 104.50 | 21.26 | 104.50 | 21.11 |
December | 422.00 | 20.21 | 353.67 | 20.13 | 353.67 | 20.10 |
Annual Sum or Average | 3073.17 | 21.64 | 2909.67 | 22.09 | 1457.67 | 21.85 |
Minimum of Months | 44.67 | 20.10 | 61.33 | 20.05 | 10.83 | 20.03 |
Maximum of Months | 427.00 | 26.73 | 413.50 | 24.90 | 388.17 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.17 | 20.78 | 321.33 | 20.56 | 315.00 | 20.44 |
February | 421.67 | 20.90 | 254.83 | 20.65 | 249.33 | 20.51 |
March | 363.67 | 21.96 | 145.83 | 22.08 | 79.83 | 21.88 |
April | 319.83 | 22.57 | 96.50 | 22.90 | 19.67 | 22.84 |
May | 206.50 | 23.34 | 162.50 | 23.88 | 8.17 | 23.95 |
June | 83.17 | 24.31 | 339.00 | 24.35 | 22.67 | 24.46 |
July | 59.17 | 26.16 | 467.83 | 24.67 | 52.17 | 24.84 |
August | 44.83 | 25.36 | 443.33 | 24.47 | 24.50 | 24.59 |
September | 117.00 | 24.11 | 319.00 | 24.38 | 30.67 | 24.55 |
October | 277.33 | 22.67 | 142.33 | 23.19 | 23.17 | 23.19 |
November | 395.00 | 21.83 | 113.50 | 21.90 | 70.50 | 21.74 |
December | 474.33 | 20.79 | 293.17 | 20.61 | 286.00 | 20.50 |
Annual Sum or Average | 3238.67 | 21.93 | 3099.17 | 22.48 | 1181.67 | 22.26 |
Minimum of Months | 44.83 | 20.78 | 96.50 | 20.56 | 8.17 | 20.44 |
Maximum of Months | 476.17 | 26.16 | 467.83 | 24.67 | 315.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.36 | 411.83 | 20.26 | 411.83 | 20.22 |
February | 450.67 | 20.64 | 315.00 | 20.47 | 315.00 | 20.40 |
March | 417.83 | 21.83 | 145.67 | 21.75 | 110.00 | 21.56 |
April | 331.33 | 22.76 | 80.83 | 23.00 | 19.67 | 22.97 |
May | 183.00 | 23.76 | 193.00 | 24.21 | 19.00 | 24.34 |
June | 59.33 | 25.21 | 391.83 | 24.56 | 29.17 | 24.70 |
July | 54.50 | 26.73 | 483.83 | 24.80 | 54.50 | 24.97 |
August | 30.00 | 26.47 | 473.83 | 24.55 | 26.00 | 24.67 |
September | 117.50 | 24.01 | 286.17 | 24.32 | 25.67 | 24.47 |
October | 346.00 | 22.50 | 76.00 | 22.68 | 17.33 | 22.60 |
November | 466.33 | 21.75 | 85.50 | 21.57 | 85.33 | 21.44 |
December | 497.00 | 20.54 | 347.50 | 20.41 | 347.50 | 20.35 |
Annual Sum or Average | 3455.50 | 21.77 | 3291.00 | 22.28 | 1461.00 | 22.05 |
Minimum of Months | 30.00 | 20.36 | 76.00 | 20.26 | 17.33 | 20.22 |
Maximum of Months | 502.00 | 26.73 | 483.83 | 24.80 | 411.83 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 488.83 | 19.81 | 488.83 | 19.81 |
February | 454.00 | 19.88 | 434.17 | 19.86 | 434.17 | 19.85 |
March | 485.00 | 20.68 | 317.33 | 20.50 | 302.50 | 20.38 |
April | 465.17 | 21.66 | 112.50 | 21.36 | 112.50 | 21.15 |
May | 313.83 | 22.85 | 66.50 | 23.03 | 7.50 | 22.99 |
June | 90.33 | 23.71 | 286.67 | 24.16 | 12.83 | 24.23 |
July | 46.00 | 25.71 | 459.83 | 24.53 | 39.17 | 24.65 |
August | 61.83 | 23.72 | 383.17 | 24.20 | 10.33 | 24.25 |
September | 234.67 | 22.79 | 158.00 | 23.35 | 12.00 | 23.41 |
October | 470.33 | 21.40 | 125.83 | 21.10 | 120.00 | 20.88 |
November | 489.00 | 20.52 | 291.83 | 20.32 | 291.83 | 20.24 |
December | 497.00 | 19.84 | 467.00 | 19.80 | 467.00 | 19.79 |
Annual Sum or Average | 4109.17 | 21.02 | 3591.67 | 21.27 | 2298.67 | 21.00 |
Minimum of Months | 46.00 | 19.83 | 66.50 | 19.80 | 7.50 | 19.79 |
Maximum of Months | 502.00 | 25.71 | 488.83 | 24.53 | 488.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.92 | 487.33 | 19.90 | 487.33 | 19.90 |
February | 454.00 | 20.07 | 386.83 | 19.95 | 386.83 | 19.90 |
March | 468.17 | 21.15 | 236.33 | 20.90 | 210.50 | 20.68 |
April | 353.83 | 21.91 | 106.33 | 21.89 | 64.17 | 21.64 |
May | 198.83 | 23.14 | 179.50 | 23.80 | 12.67 | 23.87 |
June | 75.00 | 24.94 | 378.00 | 24.50 | 32.67 | 24.67 |
July | 67.50 | 26.67 | 483.67 | 24.79 | 66.67 | 25.00 |
August | 58.17 | 25.21 | 436.33 | 24.48 | 32.50 | 24.63 |
September | 159.67 | 23.21 | 281.83 | 23.98 | 20.33 | 24.07 |
October | 401.50 | 21.80 | 111.67 | 21.64 | 80.50 | 21.40 |
November | 489.00 | 20.81 | 252.67 | 20.55 | 252.67 | 20.42 |
December | 497.00 | 19.92 | 464.50 | 19.89 | 464.50 | 19.87 |
Annual Sum or Average | 3724.67 | 21.22 | 3805.00 | 21.67 | 2111.33 | 21.40 |
Minimum of Months | 58.17 | 19.92 | 106.33 | 19.89 | 12.67 | 19.87 |
Maximum of Months | 502.00 | 26.67 | 487.33 | 24.79 | 487.33 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.17 | 20.32 | 387.17 | 20.13 | 384.33 | 20.04 |
February | 430.83 | 20.34 | 319.67 | 20.10 | 315.67 | 19.98 |
March | 401.00 | 21.36 | 206.33 | 21.23 | 162.00 | 20.99 |
April | 351.00 | 21.89 | 142.33 | 21.96 | 83.00 | 21.74 |
May | 243.33 | 22.90 | 149.17 | 23.47 | 13.17 | 23.50 |
June | 103.67 | 23.89 | 331.83 | 24.25 | 23.67 | 24.37 |
July | 71.33 | 25.75 | 458.83 | 24.65 | 55.17 | 24.83 |
August | 66.33 | 24.64 | 421.33 | 24.42 | 25.00 | 24.54 |
September | 153.83 | 23.47 | 290.17 | 24.12 | 30.33 | 24.29 |
October | 331.83 | 21.91 | 155.67 | 22.14 | 65.00 | 21.91 |
November | 432.17 | 21.12 | 194.67 | 20.90 | 178.00 | 20.71 |
December | 484.17 | 20.27 | 385.17 | 20.11 | 384.17 | 20.04 |
Annual Sum or Average | 3553.67 | 21.44 | 3442.33 | 21.89 | 1719.50 | 21.62 |
Minimum of Months | 66.33 | 20.27 | 142.33 | 20.10 | 13.17 | 19.98 |
Maximum of Months | 484.17 | 25.75 | 458.83 | 24.65 | 384.33 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 453.00 | 19.96 | 453.00 | 19.93 |
February | 451.83 | 20.22 | 365.17 | 20.07 | 365.17 | 20.02 |
March | 437.83 | 21.26 | 227.83 | 21.10 | 197.00 | 20.90 |
April | 369.50 | 22.11 | 116.17 | 22.18 | 63.33 | 22.01 |
May | 225.33 | 23.30 | 173.33 | 23.85 | 19.33 | 24.00 |
June | 75.00 | 24.68 | 379.83 | 24.48 | 29.67 | 24.63 |
July | 69.67 | 26.24 | 478.67 | 24.78 | 63.50 | 24.96 |
August | 56.33 | 25.24 | 455.83 | 24.52 | 32.17 | 24.65 |
September | 167.50 | 23.43 | 259.67 | 24.03 | 26.67 | 24.19 |
October | 396.67 | 21.82 | 114.50 | 21.75 | 72.67 | 21.52 |
November | 479.83 | 21.03 | 199.67 | 20.75 | 199.67 | 20.61 |
December | 497.00 | 20.09 | 418.17 | 19.99 | 418.17 | 19.96 |
Annual Sum or Average | 3728.50 | 21.37 | 3641.83 | 21.82 | 1940.33 | 21.56 |
Minimum of Months | 56.33 | 20.03 | 114.50 | 19.96 | 19.33 | 19.93 |
Maximum of Months | 502.00 | 26.24 | 478.67 | 24.78 | 453.00 | 24.96 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 484.17 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 7.33 | 27.00 | 514.00 | 27.00 | 7.33 | 27.00 |
April | 43.83 | 27.00 | 485.00 | 27.00 | 43.83 | 27.00 |
May | 7.33 | 27.00 | 508.00 | 27.00 | 7.33 | 27.00 |
June | 94.17 | 27.00 | 496.00 | 27.00 | 94.17 | 27.00 |
July | 276.67 | 27.00 | 497.00 | 27.00 | 276.67 | 27.00 |
August | 365.67 | 27.00 | 514.00 | 27.00 | 365.67 | 27.00 |
September | 19.00 | 27.00 | 485.00 | 27.00 | 19.00 | 27.00 |
October | 8.00 | 27.00 | 502.00 | 27.00 | 8.00 | 27.00 |
November | 2.00 | 27.00 | 489.00 | 27.00 | 2.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 824.00 | 27.00 | 5925.17 | 27.00 | 824.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 365.67 | 27.00 | 514.00 | 27.00 | 365.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.50 | 25.47 | 158.17 | 26.45 | 0.00 | 26.45 |
February | 0.33 | 27.00 | 225.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 461.50 | 27.00 | 0.00 | 27.00 |
April | 2.50 | 27.00 | 485.00 | 27.00 | 2.50 | 27.00 |
May | 4.00 | 27.00 | 508.00 | 27.00 | 4.00 | 27.00 |
June | 11.50 | 27.00 | 496.00 | 27.00 | 11.50 | 27.00 |
July | 44.17 | 27.00 | 497.00 | 27.00 | 44.17 | 27.00 |
August | 66.83 | 27.00 | 514.00 | 27.00 | 66.83 | 27.00 |
September | 3.33 | 27.00 | 485.00 | 27.00 | 3.33 | 27.00 |
October | 1.50 | 27.00 | 502.00 | 27.00 | 1.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 350.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 221.67 | 26.40 | 5171.00 | 26.98 | 133.83 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 158.17 | 26.45 | 0.00 | 26.45 |
Maximum of Months | 87.50 | 27.00 | 514.00 | 27.00 | 66.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 284.17 | 24.96 | 92.17 | 25.13 | 28.00 | 24.95 |
February | 69.33 | 27.00 | 129.67 | 27.00 | 0.00 | 27.00 |
March | 11.67 | 27.00 | 360.83 | 27.00 | 0.00 | 27.00 |
April | 2.50 | 27.00 | 469.83 | 27.00 | 2.50 | 27.00 |
May | 5.50 | 27.00 | 508.00 | 27.00 | 5.50 | 27.00 |
June | 43.50 | 27.00 | 496.00 | 27.00 | 43.50 | 27.00 |
July | 97.50 | 27.00 | 497.00 | 27.00 | 97.50 | 27.00 |
August | 97.00 | 27.00 | 514.00 | 27.00 | 97.00 | 27.00 |
September | 7.50 | 27.00 | 485.00 | 27.00 | 7.50 | 27.00 |
October | 1.67 | 27.00 | 473.17 | 27.00 | 1.67 | 27.00 |
November | 0.00 | 0.00 | 410.00 | 27.00 | 0.00 | 27.00 |
December | 47.50 | 27.00 | 211.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 667.83 | 26.13 | 4647.00 | 26.87 | 283.17 | 26.85 |
Minimum of Months | 0.00 | 0.00 | 92.17 | 25.13 | 0.00 | 24.95 |
Maximum of Months | 284.17 | 27.00 | 514.00 | 27.00 | 97.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 88.17 | 27.00 | 502.00 | 27.00 | 88.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 495.33 | 27.00 | 508.00 | 27.00 | 495.33 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.05 | 497.00 | 27.05 | 497.00 | 27.05 |
August | 514.00 | 27.35 | 514.00 | 27.35 | 514.00 | 27.35 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5516.50 | 27.04 | 5943.00 | 27.04 | 5516.50 | 27.04 |
Minimum of Months | 88.17 | 27.00 | 454.00 | 27.00 | 88.17 | 27.00 |
Maximum of Months | 514.00 | 27.35 | 514.00 | 27.35 | 514.00 | 27.35 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.97709 | 0.65995 | 14.27836 |
February | 454.00000 | 27.00000 | 16.10377 | 0.70814 | 15.64799 |
March | 514.00000 | 27.00006 | 21.76732 | 0.84470 | 20.24259 |
April | 485.00000 | 27.00001 | 26.60579 | 0.94442 | 23.90534 |
May | 508.00000 | 27.00022 | 30.36838 | 0.22373 | 6.16419 |
June | 496.00000 | 27.00083 | 34.76396 | 0.34467 | 7.56319 |
July | 497.00000 | 27.00077 | 37.05430 | 0.42208 | 8.78148 |
August | 514.00000 | 27.00024 | 36.29060 | 0.44803 | 9.26584 |
September | 485.00000 | 27.00055 | 35.84662 | 0.28020 | 6.72161 |
October | 502.00000 | 27.00016 | 30.19023 | 0.90328 | 22.29904 |
November | 489.00000 | 27.00001 | 26.02613 | 0.87997 | 21.42469 |
December | 497.00000 | 27.00000 | 19.05301 | 0.81319 | 19.04091 |
Annual Sum or Average | 5943.00000 | 27.00024 | 27.66321 | 0.62148 | 14.58432 |
Minimum of Months | 454.00000 | 27.00000 | 16.10377 | 0.22373 | 6.16419 |
Maximum of Months | 514.00000 | 27.00083 | 37.05430 | 0.94442 | 23.90534 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.66891 | 17.28067 | 0.45247 | 9.97760 |
February | 454.00000 | 27.00000 | 16.08989 | 0.54139 | 11.28572 |
March | 514.00000 | 27.00006 | 21.75723 | 0.70461 | 15.77379 |
April | 485.00000 | 27.00001 | 26.58268 | 0.81099 | 19.01633 |
May | 508.00000 | 27.00021 | 30.37199 | 0.15306 | 5.66359 |
June | 496.00000 | 27.00081 | 34.77758 | 0.25818 | 6.51514 |
July | 497.00000 | 27.00081 | 37.07168 | 0.31509 | 7.15189 |
August | 514.00000 | 27.00023 | 36.28011 | 0.32094 | 7.24730 |
September | 485.00000 | 27.00046 | 35.94687 | 0.20513 | 6.00774 |
October | 502.00000 | 27.00016 | 30.17144 | 0.80165 | 18.68670 |
November | 489.00000 | 27.00001 | 25.98855 | 0.72411 | 16.17699 |
December | 497.00000 | 27.00000 | 19.02858 | 0.59233 | 12.51841 |
Annual Sum or Average | 5943.00000 | 26.97226 | 27.68849 | 0.48901 | 11.32055 |
Minimum of Months | 454.00000 | 26.66891 | 16.08989 | 0.15306 | 5.66359 |
Maximum of Months | 514.00000 | 27.00081 | 37.07168 | 0.81099 | 19.01633 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.75679 | 17.64617 | 0.21648 | 8.11375 |
February | 454.00000 | 27.00007 | 16.08899 | 0.47344 | 9.94537 |
March | 514.00000 | 27.00006 | 21.76596 | 0.63490 | 13.99601 |
April | 485.00000 | 27.00001 | 26.59227 | 0.75642 | 17.35163 |
May | 508.00000 | 27.00021 | 30.39650 | 0.12489 | 5.65848 |
June | 496.00000 | 27.00083 | 34.78600 | 0.25937 | 6.63614 |
July | 497.00000 | 27.00082 | 37.07840 | 0.32694 | 7.38188 |
August | 514.00000 | 27.00026 | 36.29329 | 0.32321 | 7.35819 |
September | 485.00000 | 27.00044 | 35.99452 | 0.17873 | 5.93510 |
October | 502.00000 | 27.00016 | 30.19571 | 0.73784 | 16.76024 |
November | 489.00000 | 27.00001 | 26.00551 | 0.63766 | 13.76745 |
December | 497.00000 | 27.00000 | 19.03867 | 0.51315 | 10.74940 |
Annual Sum or Average | 5943.00000 | 26.89523 | 27.73351 | 0.43100 | 10.29474 |
Minimum of Months | 454.00000 | 25.75679 | 16.08899 | 0.12489 | 5.65848 |
Maximum of Months | 514.00000 | 27.00083 | 37.07840 | 0.75642 | 17.35163 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 30.02992 | 1.00166 | 26.20038 |
February | 454.00000 | 27.00016 | 29.84271 | 1.17019 | 33.81204 |
March | 514.00000 | 27.00059 | 27.44822 | 1.31883 | 41.26506 |
April | 485.00000 | 27.00076 | 27.10913 | 1.46290 | 48.89504 |
May | 508.00000 | 27.00001 | 32.40224 | 0.47944 | 9.86821 |
June | 496.00000 | 27.00136 | 40.00035 | 0.79646 | 18.54684 |
July | 497.00000 | 27.05133 | 44.34102 | 1.06712 | 29.15901 |
August | 514.00000 | 27.34749 | 38.33832 | 1.29953 | 40.31144 |
September | 485.00000 | 27.00004 | 39.51221 | 0.60318 | 12.81125 |
October | 502.00000 | 27.00014 | 31.38916 | 1.25166 | 37.82315 |
November | 489.00000 | 27.00047 | 28.78444 | 1.36235 | 43.52333 |
December | 497.00000 | 27.00020 | 24.32069 | 1.43312 | 47.29112 |
Annual Sum or Average | 5943.00000 | 27.03466 | 32.81299 | 1.10344 | 32.44813 |
Minimum of Months | 454.00000 | 26.99998 | 24.32069 | 0.47944 | 9.86821 |
Maximum of Months | 514.00000 | 27.34749 | 44.34102 | 1.46290 | 48.89504 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.47303 | 18.84629 | 0.29552 | 7.56677 |
February | 454.00000 | 24.46873 | 16.80045 | 0.28176 | 6.94311 |
March | 514.00000 | 24.46108 | 23.69402 | 0.34798 | 7.94184 |
April | 485.00000 | 24.58782 | 26.79347 | 0.40629 | 8.96371 |
May | 508.00000 | 24.60532 | 32.09159 | -0.4025 | 9.47989 |
June | 496.00000 | 25.36411 | 48.11320 | -0.0310 | 11.68399 |
July | 497.00000 | 26.20151 | 61.03939 | 0.34171 | 16.67240 |
August | 514.00000 | 25.49310 | 54.47327 | 0.08080 | 13.07185 |
September | 485.00000 | 24.95548 | 45.84712 | -0.1670 | 8.76870 |
October | 502.00000 | 24.72231 | 32.06820 | 0.48719 | 10.72195 |
November | 489.00000 | 24.69531 | 25.47122 | 0.42892 | 9.55879 |
December | 497.00000 | 24.60580 | 19.48150 | 0.34895 | 8.03749 |
Annual Sum or Average | 5943.00000 | 24.88931 | 33.86104 | 0.20032 | 9.97820 |
Minimum of Months | 454.00000 | 24.46108 | 16.80045 | -0.4025 | 6.94311 |
Maximum of Months | 514.00000 | 26.20151 | 61.03939 | 0.48719 | 16.67240 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94713 | 24.16207 | 0.20182 | 6.27730 |
February | 454.00000 | 24.07852 | 21.53664 | 0.22063 | 6.19825 |
March | 514.00000 | 24.23850 | 25.61181 | 0.32287 | 7.48285 |
April | 485.00000 | 24.32641 | 28.03721 | 0.38096 | 8.29365 |
May | 508.00000 | 24.27832 | 33.95328 | -0.4628 | 9.98987 |
June | 496.00000 | 24.26690 | 45.16146 | -0.3482 | 7.99134 |
July | 497.00000 | 24.31336 | 53.21937 | -0.2520 | 6.73430 |
August | 514.00000 | 24.24830 | 50.19857 | -0.2951 | 7.13583 |
September | 485.00000 | 24.33376 | 45.59535 | -0.3459 | 8.08787 |
October | 502.00000 | 24.37579 | 34.31346 | 0.42695 | 9.12769 |
November | 489.00000 | 24.39478 | 28.28975 | 0.38082 | 8.35377 |
December | 497.00000 | 24.30621 | 22.82240 | 0.30050 | 7.12839 |
Annual Sum or Average | 5943.00000 | 24.25962 | 34.50875 | 0.04201 | 7.74351 |
Minimum of Months | 454.00000 | 23.94713 | 21.53664 | -0.4628 | 6.19825 |
Maximum of Months | 514.00000 | 24.39478 | 53.21937 | 0.42695 | 9.98987 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.08505 | 26.26276 | -0.2777 | 8.22265 |
February | 454.00000 | 22.36213 | 25.80543 | -0.2085 | 6.75575 |
March | 514.00000 | 23.51283 | 28.94411 | 0.12126 | 6.17852 |
April | 485.00000 | 23.91798 | 30.90735 | 0.25145 | 6.57363 |
May | 508.00000 | 24.14554 | 34.69133 | -0.5390 | 11.51334 |
June | 496.00000 | 24.15224 | 46.26931 | -0.4309 | 9.21975 |
July | 497.00000 | 24.22327 | 54.81211 | -0.3415 | 7.70882 |
August | 514.00000 | 24.19885 | 51.58704 | -0.3713 | 8.12546 |
September | 485.00000 | 24.18726 | 46.60616 | -0.4317 | 9.33774 |
October | 502.00000 | 23.97057 | 36.57251 | 0.30301 | 7.18722 |
November | 489.00000 | 23.65144 | 32.01865 | 0.17173 | 6.04641 |
December | 497.00000 | 22.52423 | 28.40696 | -0.1488 | 6.47063 |
Annual Sum or Average | 5943.00000 | 23.58601 | 36.99071 | -0.1590 | 7.79030 |
Minimum of Months | 454.00000 | 22.08505 | 25.80543 | -0.5390 | 6.04641 |
Maximum of Months | 514.00000 | 24.22327 | 54.81211 | 0.30301 | 11.51334 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75696 | 27.84739 | -0.6218 | 15.66140 |
February | 454.00000 | 20.98735 | 27.13000 | -0.5641 | 14.22486 |
March | 514.00000 | 22.22765 | 31.48621 | -0.2021 | 8.83838 |
April | 485.00000 | 23.09456 | 32.96363 | 0.04048 | 6.51241 |
May | 508.00000 | 23.91286 | 35.44923 | -0.6292 | 14.19743 |
June | 496.00000 | 24.11837 | 46.43297 | -0.4355 | 9.48931 |
July | 497.00000 | 24.26227 | 54.55432 | -0.3170 | 7.44882 |
August | 514.00000 | 24.19776 | 51.48761 | -0.3685 | 8.13001 |
September | 485.00000 | 23.96420 | 47.57097 | -0.5164 | 11.50904 |
October | 502.00000 | 22.96212 | 39.72028 | 0.04777 | 6.78193 |
November | 489.00000 | 22.08968 | 36.67148 | -0.2143 | 7.58997 |
December | 497.00000 | 20.92391 | 30.77790 | -0.5568 | 13.71853 |
Annual Sum or Average | 5943.00000 | 22.80519 | 38.58746 | -0.3606 | 10.32096 |
Minimum of Months | 454.00000 | 20.75696 | 27.13000 | -0.6292 | 6.51241 |
Maximum of Months | 514.00000 | 24.26227 | 54.55432 | 0.04777 | 15.66140 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.30347 | 23.46121 | -0.4673 | 10.40827 |
February | 454.00000 | 21.59883 | 22.83682 | -0.3933 | 9.19949 |
March | 514.00000 | 22.83206 | 26.92812 | -0.0457 | 7.14604 |
April | 485.00000 | 23.71887 | 28.49931 | 0.19581 | 6.46597 |
May | 508.00000 | 24.06292 | 33.76070 | -0.5579 | 12.48828 |
June | 496.00000 | 24.30020 | 44.34652 | -0.3216 | 8.02524 |
July | 497.00000 | 24.43959 | 52.20341 | -0.1799 | 6.74334 |
August | 514.00000 | 24.29069 | 49.39242 | -0.2726 | 7.33226 |
September | 485.00000 | 24.14298 | 45.42720 | -0.4384 | 9.93941 |
October | 502.00000 | 23.63455 | 35.05569 | 0.20977 | 6.67448 |
November | 489.00000 | 23.18823 | 29.71024 | 0.04793 | 5.93005 |
December | 497.00000 | 21.93679 | 24.69291 | -0.2940 | 7.88020 |
Annual Sum or Average | 5943.00000 | 23.29864 | 34.78354 | -0.2093 | 8.18489 |
Minimum of Months | 454.00000 | 21.30347 | 22.83682 | -0.5579 | 5.93005 |
Maximum of Months | 514.00000 | 24.43959 | 52.20341 | 0.20977 | 12.48828 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.50546 | 23.33224 | -0.4197 | 9.73869 |
February | 454.00000 | 21.79356 | 22.61818 | -0.3453 | 8.92914 |
March | 514.00000 | 23.03279 | 26.57567 | 0.01921 | 6.98840 |
April | 485.00000 | 23.73669 | 28.15228 | 0.23990 | 7.38355 |
May | 508.00000 | 24.18622 | 33.15333 | -0.4409 | 11.08818 |
June | 496.00000 | 24.36536 | 43.94273 | -0.2229 | 7.76489 |
July | 497.00000 | 24.48373 | 51.84622 | -0.0886 | 7.04887 |
August | 514.00000 | 24.30131 | 49.17669 | -0.2071 | 7.26691 |
September | 485.00000 | 24.26921 | 44.83403 | -0.3293 | 9.13474 |
October | 502.00000 | 23.69692 | 34.64063 | 0.24617 | 7.48164 |
November | 489.00000 | 23.03730 | 29.90725 | 0.01797 | 6.26644 |
December | 497.00000 | 21.68922 | 25.07020 | -0.3553 | 8.64700 |
Annual Sum or Average | 5943.00000 | 23.35243 | 34.52729 | -0.1565 | 8.14174 |
Minimum of Months | 454.00000 | 21.50546 | 22.61818 | -0.4409 | 6.26644 |
Maximum of Months | 514.00000 | 24.48373 | 51.84622 | 0.24617 | 11.08818 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.73851 | 22.82278 | -0.3595 | 10.48184 |
February | 454.00000 | 21.98540 | 22.03802 | -0.2929 | 9.42161 |
March | 514.00000 | 23.22379 | 25.83356 | 0.08518 | 7.77782 |
April | 485.00000 | 23.72792 | 28.09043 | 0.23689 | 7.72435 |
May | 508.00000 | 24.09227 | 33.45601 | -0.5025 | 12.27587 |
June | 496.00000 | 24.30164 | 44.24951 | -0.2899 | 8.18951 |
July | 497.00000 | 24.47113 | 51.93903 | -0.1275 | 6.97452 |
August | 514.00000 | 24.34305 | 49.01703 | -0.1870 | 7.15725 |
September | 485.00000 | 24.30172 | 44.64383 | -0.2860 | 8.92382 |
October | 502.00000 | 23.78134 | 34.11732 | 0.29778 | 8.68778 |
November | 489.00000 | 23.16596 | 29.33660 | 0.06587 | 7.11483 |
December | 497.00000 | 22.02530 | 24.55871 | -0.2720 | 8.87232 |
Annual Sum or Average | 5943.00000 | 23.44026 | 34.26668 | -0.1355 | 8.63280 |
Minimum of Months | 454.00000 | 21.73851 | 22.03802 | -0.5025 | 6.97452 |
Maximum of Months | 514.00000 | 24.47113 | 51.93903 | 0.29778 | 12.27587 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15307 | 22.41003 | -0.2554 | 7.73727 |
February | 454.00000 | 22.92750 | 20.91825 | -0.0639 | 6.48157 |
March | 514.00000 | 24.07558 | 24.24998 | 0.30840 | 8.17369 |
April | 485.00000 | 24.49224 | 26.26943 | 0.48914 | 11.05019 |
May | 508.00000 | 24.42882 | 32.52049 | -0.3154 | 9.11133 |
June | 496.00000 | 24.53382 | 43.42871 | -0.0786 | 7.29175 |
July | 497.00000 | 24.69118 | 51.10995 | 0.07303 | 7.59189 |
August | 514.00000 | 24.55643 | 48.20681 | 0.01751 | 7.09444 |
September | 485.00000 | 24.46427 | 44.18590 | -0.2217 | 7.84042 |
October | 502.00000 | 24.30969 | 32.90886 | 0.42521 | 9.47996 |
November | 489.00000 | 24.25460 | 26.90042 | 0.33672 | 7.93300 |
December | 497.00000 | 23.78655 | 21.73152 | 0.15616 | 6.26982 |
Annual Sum or Average | 5943.00000 | 24.06305 | 32.99649 | 0.07284 | 8.01097 |
Minimum of Months | 454.00000 | 22.15307 | 20.91825 | -0.3154 | 6.26982 |
Maximum of Months | 514.00000 | 24.69118 | 51.10995 | 0.48914 | 11.05019 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11112 | 25.39238 | -0.8402 | 21.95238 |
February | 454.00000 | 20.25061 | 25.21049 | -0.7894 | 19.91170 |
March | 514.00000 | 21.42538 | 29.93220 | -0.4084 | 11.83602 |
April | 485.00000 | 22.45128 | 31.88360 | -0.1162 | 7.13547 |
May | 508.00000 | 23.68072 | 35.14561 | -0.7061 | 17.05782 |
June | 496.00000 | 24.15100 | 45.53503 | -0.4055 | 9.39235 |
July | 497.00000 | 24.37255 | 53.91862 | -0.2471 | 7.12370 |
August | 514.00000 | 24.18206 | 50.80211 | -0.3577 | 8.43097 |
September | 485.00000 | 23.75202 | 47.09589 | -0.5941 | 14.05278 |
October | 502.00000 | 22.39171 | 38.26589 | -0.0927 | 7.03478 |
November | 489.00000 | 21.28735 | 33.55246 | -0.4154 | 9.87455 |
December | 497.00000 | 20.24994 | 28.38974 | -0.7674 | 19.33477 |
Annual Sum or Average | 5943.00000 | 22.37533 | 37.17958 | -0.4766 | 12.71874 |
Minimum of Months | 454.00000 | 20.11112 | 25.21049 | -0.8402 | 7.03478 |
Maximum of Months | 514.00000 | 24.37255 | 53.91862 | -0.0927 | 21.95238 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.09884 | 24.72788 | -0.8326 | 21.64281 |
February | 385.00000 | 20.37119 | 24.45781 | -0.7460 | 18.91049 |
March | 433.00000 | 21.95291 | 28.60416 | -0.2618 | 9.64888 |
April | 410.00000 | 23.05464 | 29.91723 | 0.06030 | 7.69026 |
May | 430.00000 | 24.03535 | 33.55512 | -0.5176 | 13.68035 |
June | 418.00000 | 24.38352 | 44.46237 | -0.2457 | 8.59411 |
July | 422.00000 | 24.61211 | 52.81276 | -0.0820 | 7.56545 |
August | 433.00000 | 24.38240 | 49.73011 | -0.2180 | 7.88717 |
September | 410.00000 | 24.12928 | 45.57144 | -0.4090 | 11.39768 |
October | 427.00000 | 22.91321 | 36.40375 | 0.04266 | 7.35508 |
November | 417.00000 | 21.56645 | 32.26953 | -0.3496 | 9.40266 |
December | 422.00000 | 20.21378 | 27.70957 | -0.7757 | 19.51947 |
Annual Sum or Average | 5034.00000 | 22.65691 | 35.92359 | -0.3592 | 11.90056 |
Minimum of Months | 385.00000 | 20.09884 | 24.45781 | -0.8326 | 7.35508 |
Maximum of Months | 433.00000 | 24.61211 | 52.81276 | 0.06030 | 21.64281 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.96748 | 24.31067 | -0.5808 | 16.28596 |
February | 454.00000 | 21.12128 | 23.93125 | -0.5236 | 14.64045 |
March | 514.00000 | 22.62880 | 27.77519 | -0.0609 | 8.99717 |
April | 485.00000 | 23.14916 | 29.99984 | 0.09461 | 7.96576 |
May | 508.00000 | 23.87892 | 34.24382 | -0.5806 | 14.80064 |
June | 496.00000 | 24.18475 | 45.22350 | -0.3519 | 9.38655 |
July | 497.00000 | 24.44196 | 53.41645 | -0.1710 | 7.34917 |
August | 514.00000 | 24.29959 | 50.06923 | -0.2352 | 7.81996 |
September | 485.00000 | 24.16754 | 45.36578 | -0.3372 | 10.42839 |
October | 502.00000 | 23.37139 | 35.47954 | 0.19986 | 8.81460 |
November | 489.00000 | 22.32296 | 31.42576 | -0.1383 | 8.54114 |
December | 497.00000 | 20.96317 | 27.47981 | -0.5578 | 14.65633 |
Annual Sum or Average | 5943.00000 | 22.97247 | 35.81410 | -0.2689 | 10.78584 |
Minimum of Months | 454.00000 | 20.96317 | 23.93125 | -0.5808 | 7.34917 |
Maximum of Months | 514.00000 | 24.44196 | 53.41645 | 0.19986 | 16.28596 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36101 | 25.07679 | -0.7526 | 19.07079 |
February | 454.00000 | 20.66293 | 24.64146 | -0.6586 | 16.28439 |
March | 514.00000 | 22.27049 | 28.39986 | -0.1747 | 9.27298 |
April | 485.00000 | 23.22216 | 30.00680 | 0.10799 | 7.86378 |
May | 508.00000 | 24.05578 | 33.99068 | -0.4913 | 12.93105 |
June | 496.00000 | 24.34695 | 44.73572 | -0.2203 | 8.29715 |
July | 497.00000 | 24.55979 | 53.01225 | -0.0751 | 7.35777 |
August | 514.00000 | 24.39036 | 49.82502 | -0.1766 | 7.53391 |
September | 485.00000 | 24.11827 | 45.77873 | -0.3965 | 10.78173 |
October | 502.00000 | 23.00719 | 36.56313 | 0.07383 | 7.26855 |
November | 489.00000 | 21.85800 | 32.42377 | -0.2694 | 8.29280 |
December | 497.00000 | 20.54318 | 27.96180 | -0.6709 | 16.09508 |
Annual Sum or Average | 5943.00000 | 22.79939 | 36.11804 | -0.3065 | 10.88556 |
Minimum of Months | 454.00000 | 20.36101 | 24.64146 | -0.7526 | 7.26855 |
Maximum of Months | 514.00000 | 24.55979 | 53.01225 | 0.10799 | 19.07079 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82667 | 26.27514 | -0.9613 | 27.09806 |
February | 454.00000 | 19.88379 | 25.98553 | -0.9286 | 25.89887 |
March | 514.00000 | 20.86465 | 31.31985 | -0.5800 | 16.57678 |
April | 485.00000 | 21.75910 | 33.19939 | -0.2991 | 9.80362 |
May | 508.00000 | 23.33956 | 36.00894 | -0.8266 | 22.08265 |
June | 496.00000 | 24.06968 | 45.84481 | -0.4273 | 10.45889 |
July | 497.00000 | 24.37313 | 53.92103 | -0.2367 | 7.35911 |
August | 514.00000 | 24.12782 | 50.92812 | -0.3724 | 9.12117 |
September | 485.00000 | 23.43826 | 48.14321 | -0.7049 | 18.40226 |
October | 502.00000 | 21.55973 | 40.28277 | -0.3102 | 10.39308 |
November | 489.00000 | 20.52088 | 35.78558 | -0.6412 | 15.89300 |
December | 497.00000 | 19.83706 | 29.61699 | -0.9231 | 25.83527 |
Annual Sum or Average | 5943.00000 | 21.98423 | 38.19371 | -0.5987 | 16.51390 |
Minimum of Months | 454.00000 | 19.82667 | 25.98553 | -0.9613 | 7.35911 |
Maximum of Months | 514.00000 | 24.37313 | 53.92103 | -0.2367 | 27.09806 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92047 | 26.19912 | -0.9166 | 25.32537 |
February | 454.00000 | 20.06592 | 25.84774 | -0.8558 | 23.61468 |
March | 514.00000 | 21.40503 | 30.55132 | -0.4150 | 13.48143 |
April | 485.00000 | 22.54261 | 31.30171 | -0.0712 | 9.15284 |
May | 508.00000 | 23.81543 | 34.33752 | -0.5828 | 15.85854 |
June | 496.00000 | 24.27828 | 44.79332 | -0.2551 | 8.79575 |
July | 497.00000 | 24.51314 | 52.99694 | -0.0803 | 7.44784 |
August | 514.00000 | 24.28215 | 50.02299 | -0.2231 | 8.03905 |
September | 485.00000 | 23.88926 | 46.33408 | -0.4793 | 13.43191 |
October | 502.00000 | 22.25829 | 38.56898 | -0.1270 | 9.18356 |
November | 489.00000 | 20.81135 | 35.26054 | -0.5619 | 14.29611 |
December | 497.00000 | 19.92481 | 29.52259 | -0.8927 | 24.52576 |
Annual Sum or Average | 5943.00000 | 22.32694 | 37.22574 | -0.4524 | 14.36315 |
Minimum of Months | 454.00000 | 19.92047 | 25.84774 | -0.9166 | 7.44784 |
Maximum of Months | 514.00000 | 24.51314 | 52.99694 | -0.0712 | 25.32537 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46559 | 25.49059 | -0.7440 | 21.34729 |
February | 454.00000 | 20.52962 | 25.05176 | -0.7045 | 20.83613 |
March | 514.00000 | 21.96416 | 29.34963 | -0.2511 | 11.90623 |
April | 485.00000 | 22.53833 | 31.21884 | -0.0711 | 9.46786 |
May | 508.00000 | 23.58711 | 35.00098 | -0.6868 | 19.06182 |
June | 496.00000 | 24.09217 | 45.57905 | -0.3766 | 10.61872 |
July | 497.00000 | 24.41670 | 53.51268 | -0.1678 | 7.72719 |
August | 514.00000 | 24.24476 | 50.21062 | -0.2497 | 8.47024 |
September | 485.00000 | 23.94142 | 46.11789 | -0.4228 | 13.15696 |
October | 502.00000 | 22.68708 | 37.21158 | 0.01300 | 9.83568 |
November | 489.00000 | 21.46881 | 33.81788 | -0.3783 | 12.19307 |
December | 497.00000 | 20.37193 | 28.94847 | -0.7485 | 20.66173 |
Annual Sum or Average | 5943.00000 | 22.54204 | 36.87702 | -0.3971 | 13.72741 |
Minimum of Months | 454.00000 | 20.37193 | 25.05176 | -0.7485 | 7.72719 |
Maximum of Months | 514.00000 | 24.41670 | 53.51268 | 0.01300 | 21.34729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02513 | 26.02867 | -0.8797 | 24.05424 |
February | 454.00000 | 20.23911 | 25.50779 | -0.7967 | 21.64807 |
March | 514.00000 | 21.68997 | 29.82987 | -0.3389 | 12.31471 |
April | 485.00000 | 22.61463 | 31.20047 | -0.0507 | 9.15172 |
May | 508.00000 | 23.78580 | 34.71773 | -0.5884 | 16.62533 |
June | 496.00000 | 24.27222 | 45.03905 | -0.2399 | 9.19229 |
July | 497.00000 | 24.54189 | 53.08795 | -0.0707 | 7.62908 |
August | 514.00000 | 24.34826 | 49.93374 | -0.1876 | 7.99214 |
September | 485.00000 | 23.88094 | 46.59924 | -0.4829 | 13.67299 |
October | 502.00000 | 22.29419 | 38.30621 | -0.1109 | 9.00092 |
November | 489.00000 | 21.08282 | 34.62868 | -0.4822 | 12.42132 |
December | 497.00000 | 20.09185 | 29.23781 | -0.8212 | 21.88732 |
Annual Sum or Average | 5943.00000 | 22.42328 | 37.09125 | -0.4182 | 13.74362 |
Minimum of Months | 454.00000 | 20.02513 | 25.50779 | -0.8797 | 7.62908 |
Maximum of Months | 514.00000 | 24.54189 | 53.08795 | -0.0507 | 24.05424 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 23319615.51 | 620.84 | 11-JAN-16:40 | 16.28 | 0.227384E+09 | 0.00 | 0.250704E+09 | 0.21 | 9.83 | 25-JAN-11:40 | 0.00 | 0.00 |
February | 64837127.20 | 2977.40 | 22-FEB-17:00 | 19.46 | 0.632599E+09 | 0.00 | 0.697437E+09 | 0.28 | 9.83 | 28-FEB-13:40 | 0.00 | 0.00 |
March | 0.748493E+10 | 179868.03 | 14-MAR-13:20 | 130.41 | 0.646111E+11 | 0.00 | 0.720960E+11 | 1.69 | 10.00 | 14-MAR-16:40 | 0.00 | 0.00 |
April | 0.655075E+10 | 58388.00 | 19-APR-15:10 | 159.53 | 0.640748E+11 | 0.00 | 0.706255E+11 | 2.16 | 10.00 | 20-APR-13:20 | 0.00 | 0.00 |
May | 0.228823E+11 | 170445.04 | 10-MAY-14:00 | 269.70 | 0.214592E+12 | 0.00 | 0.237475E+12 | 3.51 | 10.00 | 27-MAY-14:40 | 0.00 | 0.00 |
June | 0.809601E+11 | 182863.77 | 01-JUN-14:30 | 456.89 | 0.705206E+12 | 0.00 | 0.786166E+12 | 5.90 | 10.00 | 06-JUN-11:05 | 0.00 | 0.00 |
July | 0.131438E+12 | 197710.97 | 05-JUL-15:40 | 609.09 | 0.109537E+13 | 0.00 | 0.122681E+13 | 7.35 | 10.03 | 24-JUL-05:03 | 0.00 | 0.00 |
August | 0.114606E+12 | 195866.32 | 15-AUG-14:40 | 592.74 | 0.970904E+12 | 0.00 | 0.108551E+13 | 7.29 | 10.02 | 16-AUG-05:03 | 0.00 | 0.00 |
September | 0.530242E+11 | 179370.64 | 15-SEP-12:00 | 356.80 | 0.473102E+12 | 0.00 | 0.526127E+12 | 4.68 | 10.00 | 09-SEP-12:40 | 0.00 | 0.00 |
October | 0.106448E+11 | 98170.90 | 11-OCT-14:30 | 181.40 | 0.102854E+12 | 0.00 | 0.113498E+12 | 2.37 | 10.00 | 05-OCT-14:30 | 0.00 | 0.00 |
November | 0.248593E+10 | 34199.05 | 16-NOV-13:10 | 139.18 | 0.242024E+11 | 0.00 | 0.266883E+11 | 1.88 | 9.83 | 28-NOV-11:20 | 0.00 | 0.00 |
December | 66242914.05 | 4127.30 | 01-DEC-07:13 | 26.49 | 0.646332E+09 | 0.00 | 0.712575E+09 | 0.35 | 9.83 | 04-DEC-10:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.430231E+12 | 2957.97 | 0.371642E+13 | 0.00 | 0.414665E+13 | 3.16 | 0.00 | 0.00 | ||||
Minimum of Months | 23319615.51 | 620.84 | 16.28 | 0.227384E+09 | 0.00 | 0.250704E+09 | 0.21 | 9.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.131438E+12 | 197710.97 | 609.09 | 0.109537E+13 | 0.00 | 0.122681E+13 | 7.35 | 10.03 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.193487E+09 | 81112.76 | 15-MAR-14:05 | 1.25 | 0.178986E+10 | 0.00 | 0.198335E+10 | 0.02 | 10.45 | 15-MAR-14:20 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.272770E+09 | 74075.61 | 10-MAY-14:05 | 1.08 | 0.250548E+10 | 0.00 | 0.277825E+10 | 0.01 | 9.32 | 10-MAY-14:20 | 0.00 | 0.00 |
June | 0.168877E+11 | 153751.68 | 27-JUN-07:40 | 59.90 | 0.147007E+12 | 0.00 | 0.163895E+12 | 0.73 | 10.67 | 30-JUN-14:20 | 0.00 | 0.00 |
July | 0.432075E+11 | 197710.97 | 05-JUL-15:40 | 136.85 | 0.358565E+12 | 0.00 | 0.401772E+12 | 1.56 | 10.51 | 14-JUL-10:00 | 0.00 | 0.00 |
August | 0.295494E+11 | 195866.32 | 15-AUG-14:40 | 96.29 | 0.248191E+12 | 0.00 | 0.277741E+12 | 1.12 | 10.49 | 01-AUG-14:05 | 0.00 | 0.00 |
September | 0.854932E+10 | 160188.65 | 21-SEP-12:52 | 30.20 | 0.746865E+11 | 0.00 | 0.832359E+11 | 0.37 | 10.65 | 20-SEP-15:40 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.986602E+11 | 325.58 | 0.832745E+12 | 0.00 | 0.931405E+12 | 0.32 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.432075E+11 | 197710.97 | 136.85 | 0.358565E+12 | 0.00 | 0.401772E+12 | 1.56 | 10.67 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.357029E+09 | 744.00 | 571.39 | 11-JAN-16:00 | 30167.91 | 12-JAN-16:40 | 18.54 | 18.33 | 15.87 |
February | 0.106205E+10 | 672.00 | 2006.27 | 22-FEB-18:00 | 65601.86 | 28-FEB-17:00 | 19.07 | 18.33 | 15.87 |
March | 0.823602E+10 | 744.00 | 43776.24 | 12-MAR-13:00 | 496288.71 | 14-MAR-13:05 | 20.17 | 18.56 | 15.87 |
April | 0.104842E+11 | 720.00 | 43776.24 | 07-APR-10:20 | 413242.64 | 08-APR-13:20 | 20.62 | 18.39 | 15.87 |
May | 0.231770E+11 | 744.00 | 43776.24 | 09-MAY-11:50 | 203832.86 | 10-MAY-15:00 | 19.37 | 18.74 | 15.87 |
June | 0.698732E+11 | 720.00 | 43776.24 | 01-JUN-09:50 | 621664.91 | 27-JUN-14:20 | 23.82 | 21.21 | 15.87 |
July | 0.104782E+12 | 744.00 | 43776.24 | 01-JUL-07:00 | 798821.64 | 21-JUL-03:02 | 32.82 | 25.11 | 15.87 |
August | 0.101339E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 817041.46 | 13-AUG-16:01 | 33.61 | 24.48 | 15.87 |
September | 0.478401E+11 | 720.00 | 43776.24 | 01-SEP-12:50 | 264874.21 | 15-SEP-12:05 | 20.26 | 19.54 | 15.87 |
October | 0.111440E+11 | 744.00 | 43776.24 | 03-OCT-13:05 | 179464.71 | 11-OCT-15:00 | 19.45 | 18.43 | 15.87 |
November | 0.764013E+10 | 720.00 | 43776.24 | 04-NOV-13:50 | 214867.45 | 05-NOV-14:00 | 19.84 | 18.36 | 15.87 |
December | 0.290385E+10 | 744.00 | 6320.38 | 01-DEC-11:00 | 185719.46 | 01-DEC-11:00 | 20.10 | 18.33 | 15.87 |
Annual Sum or Average | 0.388838E+12 | 8760.00 | 22.35 | 19.83 | 15.87 | ||||
Minimum of Months | 0.357029E+09 | 672.00 | 571.39 | 30167.91 | 18.54 | 18.33 | 15.87 | ||
Maximum of Months | 0.104782E+12 | 744.00 | 43776.24 | 817041.46 | 33.61 | 25.11 | 15.87 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 214976.75 | 25-JAN-11:10 | 20.97 | 20.97 | 0.09 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 215174.78 | 28-FEB-15:20 | 20.93 | 20.93 | 0.09 |
March | 0.718522E+09 | 32.33 | 17848.03 | 14-MAR-10:50 | 1297260.47 | 15-MAR-12:50 | 21.09 | 20.98 | 4.35 |
April | 37067691.29 | 47.50 | 1028.70 | 08-APR-13:20 | 639105.21 | 19-APR-15:20 | 21.18 | 21.06 | 7.68 |
May | 0.852971E+09 | 165.85 | 17848.03 | 10-MAY-11:00 | 1277826.87 | 23-MAY-14:20 | 21.52 | 21.15 | 18.69 |
June | 0.116428E+11 | 388.38 | 17848.03 | 01-JUN-12:50 | 1275506.70 | 30-JUN-14:40 | 22.93 | 21.71 | 36.13 |
July | 0.248458E+11 | 539.66 | 17848.03 | 01-JUL-13:50 | 1422218.36 | 05-JUL-16:00 | 24.36 | 22.54 | 46.32 |
August | 0.187018E+11 | 488.32 | 17848.03 | 01-AUG-11:50 | 1371962.80 | 15-AUG-14:45 | 23.53 | 21.89 | 44.06 |
September | 0.692738E+10 | 287.62 | 17848.03 | 08-SEP-10:30 | 1261586.98 | 22-SEP-14:05 | 22.40 | 21.58 | 28.12 |
October | 0.202223E+09 | 87.83 | 4439.43 | 11-OCT-15:00 | 946306.03 | 11-OCT-14:40 | 21.32 | 21.14 | 10.87 |
November | 18997725.00 | 23.25 | 762.41 | 16-NOV-13:10 | 377302.48 | 16-NOV-13:10 | 21.05 | 21.00 | 4.39 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 215186.63 | 04-DEC-07:13 | 20.96 | 20.96 | 0.09 |
Annual Sum or Average | 0.639477E+11 | 2060.74 | 21.86 | 21.33 | 16.85 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 214976.75 | 20.93 | 20.93 | 0.09 | ||
Maximum of Months | 0.248458E+11 | 539.66 | 17848.03 | 1422218.36 | 24.36 | 22.54 | 46.32 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 20.97 | 20.97 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.93 | 20.93 | 0.00 |
March | 0.112443E+09 | 1.75 | 17848.03 | 14-MAR-12:20 | 963646.23 | 15-MAR-14:05 | 21.09 | 21.08 | 0.11 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.18 | 21.18 | 0.00 |
May | 0.101734E+09 | 1.58 | 17848.03 | 10-MAY-13:40 | 887748.15 | 10-MAY-14:05 | 21.52 | 21.51 | 0.11 |
June | 0.452571E+10 | 71.28 | 17848.03 | 01-JUN-14:30 | 1199008.75 | 27-JUN-07:40 | 22.93 | 22.58 | 5.44 |
July | 0.115322E+11 | 179.48 | 17848.03 | 03-JUL-12:05 | 1422218.36 | 05-JUL-16:00 | 24.36 | 23.49 | 12.94 |
August | 0.674699E+10 | 105.43 | 17848.03 | 02-AUG-13:05 | 1371962.80 | 15-AUG-14:45 | 23.53 | 23.01 | 7.96 |
September | 0.214012E+10 | 33.45 | 17848.03 | 08-SEP-12:50 | 1130658.17 | 15-SEP-11:00 | 22.40 | 22.24 | 2.65 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.32 | 21.32 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.05 | 21.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.96 | 20.96 | 0.00 |
Annual Sum or Average | 0.251592E+11 | 392.98 | 21.86 | 21.70 | 2.46 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 20.93 | 0.00 | ||
Maximum of Months | 0.115322E+11 | 179.48 | 17848.03 | 1422218.36 | 24.36 | 23.49 | 12.94 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.280778E+12 | 0.00 | 545.28 | 1925048.11 | 02-JAN-04:01 | 0.00 | 33.61 | 69.12 | 0.59 | 0.00 | 0.04 | 0.81 | 02-JAN-04:01 |
February | 0.216458E+12 | 0.00 | 493.36 | 1536938.75 | 14-FEB-06:01 | 0.00 | 31.54 | 68.06 | 0.50 | 0.00 | 0.04 | 0.65 | 14-FEB-06:01 |
March | 0.664026E+11 | 0.00 | 372.92 | 1349036.32 | 21-MAR-04:01 | 0.00 | 27.14 | 53.63 | 0.13 | 0.00 | 0.01 | 0.57 | 21-MAR-04:01 |
April | 0.122662E+11 | 0.00 | 202.82 | 1147875.06 | 17-APR-05:01 | 0.00 | 27.08 | 42.30 | 0.02 | 0.00 | 0.00 | 0.48 | 17-APR-05:01 |
May | 0.121995E+10 | 0.00 | 43.10 | 290462.63 | 11-MAY-13:20 | 0.00 | 28.57 | 31.66 | 0.00 | 0.00 | 0.00 | 0.12 | 11-MAY-13:20 |
June | 0.183743E+09 | 0.00 | 4.39 | 266980.70 | 13-JUN-11:05 | 0.00 | 29.29 | 29.61 | 0.00 | 0.00 | 0.00 | 0.11 | 13-JUN-11:05 |
July | 1977.31 | 0.00 | 0.17 | 3.30 | 02-JUL-23:00 | 0.00 | 29.62 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 02-JUL-23:00 |
August | 2015062.53 | 0.00 | 0.12 | 6715.82 | 31-AUG-11:05 | 0.00 | 29.62 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 31-AUG-11:05 |
September | 0.331484E+09 | 0.00 | 16.62 | 95519.61 | 28-SEP-10:00 | 0.00 | 28.43 | 29.68 | 0.00 | 0.00 | 0.00 | 0.04 | 28-SEP-10:00 |
October | 0.995672E+10 | 0.00 | 181.15 | 1180245.45 | 30-OCT-05:01 | 0.00 | 27.94 | 40.75 | 0.02 | 0.00 | 0.00 | 0.50 | 30-OCT-05:01 |
November | 0.377954E+11 | 0.00 | 337.61 | 1271376.51 | 25-NOV-05:01 | 0.00 | 26.23 | 51.60 | 0.07 | 0.00 | 0.01 | 0.54 | 25-NOV-05:01 |
December | 0.210373E+12 | 0.00 | 519.47 | 1578205.58 | 11-DEC-05:01 | 0.00 | 31.39 | 66.06 | 0.44 | 0.00 | 0.03 | 0.67 | 11-DEC-05:01 |
Annual Sum or Average | 0.835767E+12 | 0.00 | 2717.01 | 0.00 | 29.20 | 45.03 | 0.15 | 0.00 | 0.01 | ||||
Minimum of Months | 1977.31 | 0.00 | 0.12 | 3.30 | 0.00 | 26.23 | 29.61 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.280778E+12 | 0.00 | 545.28 | 1925048.11 | 0.00 | 33.61 | 69.12 | 0.59 | 0.00 | 0.04 | 0.81 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.54 | 18.54 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.07 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.17 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.62 | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.37 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.82 | 23.82 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 32.82 | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 33.61 | 33.61 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20.26 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.45 | 19.45 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.84 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.10 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 | 22.35 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 18.54 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.61 | 33.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11550518.54 | 0.00 | 10.46 | 11550518.54 | 0.00 | 0.00 | 0.00 | 0.00 | 8069.66 | 17-JAN-08:15 | 8069.66 | 17-JAN-08:15 | 0.00 | 0.00 | 0.00 |
February | 0.389478E+09 | 0.00 | 17.11 | 0.389478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25189.58 | 22-FEB-15:00 | 25189.58 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.897677E+10 | 0.00 | 112.78 | 0.879373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105754.51 | 14-MAR-13:05 | 100329.84 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.474962E+10 | 0.00 | 94.45 | 0.474962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52416.76 | 07-APR-14:00 | 52416.76 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.185430E+11 | 0.00 | 222.79 | 0.183236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95113.08 | 10-MAY-14:40 | 89646.74 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.851655E+11 | 0.00 | 437.79 | 0.677548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 255306.43 | 27-JUN-07:50 | 126882.97 | 27-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.156732E+12 | 0.00 | 584.73 | 0.113354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 302187.78 | 21-JUL-05:02 | 154819.16 | 21-JUL-04:23 | 0.00 | 0.00 | 0.00 |
August | 0.132182E+12 | 0.00 | 569.85 | 0.103611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277132.82 | 15-AUG-08:20 | 138789.32 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.509929E+11 | 0.00 | 325.65 | 0.406113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192486.60 | 14-SEP-04:12 | 106011.23 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.102865E+11 | 0.00 | 142.46 | 0.102831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79136.30 | 11-OCT-15:00 | 79136.30 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.533096E+10 | 0.00 | 126.48 | 0.533096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52275.44 | 27-NOV-06:03 | 52275.44 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.264578E+09 | 0.00 | 25.89 | 0.264578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13376.96 | 04-DEC-14:50 | 13376.96 | 04-DEC-14:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473624E+12 | 0.00 | 2670.42 | 0.373478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11550518.54 | 0.00 | 10.46 | 11550518.54 | 0.00 | 0.00 | 0.00 | 0.00 | 8069.66 | 8069.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.156732E+12 | 0.00 | 584.73 | 0.113354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 302187.78 | 154819.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8897611.50 | 0.00 | 8.09 | 8897611.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3639.50 | 11-JAN-15:10 | 3639.50 | 11-JAN-15:10 | 0.00 | 0.00 | 0.00 |
February | 56474678.37 | 0.00 | 9.38 | 56474678.37 | 0.00 | 0.00 | 0.00 | 0.00 | 9622.53 | 28-FEB-15:20 | 9622.53 | 28-FEB-15:20 | 0.00 | 0.00 | 0.00 |
March | 0.452818E+11 | 0.00 | 96.46 | 0.440767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 798843.98 | 15-MAR-14:05 | 798843.98 | 15-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.544718E+11 | 0.00 | 130.92 | 0.544718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 498112.52 | 19-APR-14:50 | 498112.52 | 19-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.167717E+12 | 0.00 | 232.86 | 0.166016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 854582.07 | 10-MAY-14:40 | 816226.86 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.646351E+12 | 0.00 | 400.02 | 0.526022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1692600.57 | 27-JUN-07:40 | 1049871.98 | 12-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.108265E+13 | 0.00 | 458.73 | 0.811091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2466925.98 | 17-JUL-05:02 | 1369414.31 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.905340E+12 | 0.00 | 440.87 | 0.738184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2530010.68 | 14-AUG-05:02 | 1105566.48 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.412795E+12 | 0.00 | 318.91 | 0.337720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1547580.92 | 14-SEP-05:03 | 976004.59 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.804732E+11 | 0.00 | 148.05 | 0.804242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 645677.67 | 11-OCT-15:00 | 645677.67 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.157286E+11 | 0.00 | 105.42 | 0.157286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 281678.55 | 16-NOV-13:05 | 281678.55 | 16-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 42848555.41 | 0.00 | 18.31 | 42848555.41 | 0.00 | 0.00 | 0.00 | 0.00 | 8116.47 | 04-DEC-11:10 | 8116.47 | 04-DEC-11:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341092E+13 | 0.00 | 2368.00 | 0.277384E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8897611.50 | 0.00 | 8.09 | 8897611.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3639.50 | 3639.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108265E+13 | 0.00 | 458.73 | 0.811091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2530010.68 | 1369414.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1117683.74 | 0.00 | 7.51 | 1117683.74 | 0.00 | 0.00 | 0.00 | 0.00 | 601.73 | 02-JAN-07:03 | 601.73 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 |
February | 5331679.48 | 0.00 | 7.10 | 5331679.48 | 0.00 | 0.00 | 0.00 | 0.00 | 862.06 | 28-FEB-15:00 | 862.06 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.407671E+10 | 0.00 | 98.46 | 0.407559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93787.89 | 15-MAR-14:20 | 93787.89 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.150635E+10 | 0.00 | 95.50 | 0.150635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35456.09 | 07-APR-14:00 | 35456.09 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.156220E+11 | 0.00 | 213.78 | 0.154989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100957.35 | 14-MAY-15:02 | 93734.94 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.699716E+11 | 0.00 | 396.05 | 0.568114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173036.85 | 27-JUN-05:03 | 129278.85 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.119770E+12 | 0.00 | 458.92 | 0.899215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 308070.74 | 21-JUL-05:02 | 137826.71 | 21-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.981338E+11 | 0.00 | 435.49 | 0.796226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 272971.29 | 14-AUG-05:02 | 133696.19 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.399541E+11 | 0.00 | 310.35 | 0.325316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168837.85 | 15-SEP-13:10 | 113066.24 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.445403E+10 | 0.00 | 128.67 | 0.445403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62207.58 | 11-OCT-15:00 | 62207.58 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.554335E+09 | 0.00 | 101.99 | 0.554335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12134.76 | 16-NOV-13:00 | 12134.76 | 16-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 4194387.81 | 0.00 | 18.01 | 4194387.81 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 04-DEC-11:00 | 421.65 | 04-DEC-11:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354053E+12 | 0.00 | 2271.83 | 0.284987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1117683.74 | 0.00 | 7.10 | 1117683.74 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 421.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.119770E+12 | 0.00 | 458.92 | 0.899215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 308070.74 | 137826.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 41389778.29 | 0.00 | 4.00 | 41389778.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5270.03 | 11-JAN-16:00 | 5270.03 | 11-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 38811114.69 | 0.00 | 4.17 | 38811114.69 | 0.00 | 0.00 | 0.00 | 0.00 | 6068.56 | 22-FEB-17:00 | 6068.56 | 22-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.390107E+10 | 0.00 | 42.37 | 0.388490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55155.19 | 15-MAR-14:00 | 55155.19 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.153861E+10 | 0.00 | 42.83 | 0.153861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27505.39 | 07-APR-13:20 | 27505.39 | 07-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.121745E+11 | 0.00 | 180.00 | 0.115031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85701.42 | 24-MAY-06:25 | 52973.97 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.319718E+11 | 0.00 | 233.76 | 0.249510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124828.76 | 28-JUN-14:20 | 84173.60 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.532899E+11 | 0.00 | 210.56 | 0.393413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173433.53 | 29-JUL-10:53 | 86287.24 | 24-JUL-12:20 | 0.00 | 0.00 | 0.00 |
August | 0.564729E+11 | 0.00 | 284.19 | 0.463323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136451.30 | 28-AUG-12:05 | 92416.01 | 09-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.331419E+11 | 0.00 | 241.75 | 0.261229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133426.63 | 14-SEP-16:00 | 68850.36 | 25-SEP-12:05 | 0.00 | 0.00 | 0.00 |
October | 0.555058E+10 | 0.00 | 92.05 | 0.529696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73083.92 | 26-OCT-06:25 | 49951.00 | 11-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.877442E+09 | 0.00 | 19.59 | 0.873236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55196.25 | 27-NOV-07:11 | 55196.25 | 27-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 6140035.17 | 0.00 | 0.17 | 5949607.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17374.01 | 01-DEC-07:13 | 16395.00 | 01-DEC-07:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199005E+12 | 0.00 | 1355.44 | 0.159930E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6140035.17 | 0.00 | 0.17 | 5949607.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5270.03 | 5270.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.564729E+11 | 0.00 | 284.19 | 0.463323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173433.53 | 92416.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.656980E+10 | 0.425978E+10 | 739.67 | 0.656975E+10 | 46674.08 | 0.00 | 0.02 | 13-JAN-18:00 | 0.01 | 11-JAN-18:10 | 3825.74 | 13-JAN-18:00 | 3825.74 | 13-JAN-18:00 | 18.18 | 11-JAN-18:40 | 1941.07 | 13-JAN-18:00 | 0.00 |
February | 0.102825E+11 | 0.503325E+10 | 672.00 | 0.102722E+11 | 10314106.28 | 0.00 | 0.02 | 22-FEB-18:00 | 0.01 | 01-FEB-05:11 | 5069.26 | 14-FEB-17:15 | 5069.26 | 14-FEB-17:15 | 87.67 | 01-FEB-08:00 | 2335.14 | 22-FEB-18:00 | 0.00 |
March | 0.314528E+11 | 0.112696E+11 | 681.04 | 0.283874E+11 | 0.306541E+10 | 0.00 | 0.70 | 14-MAR-13:00 | 0.01 | 11-MAR-01:10 | 313928.95 | 14-MAR-13:00 | 288759.86 | 15-MAR-14:00 | 86435.32 | 14-MAR-11:00 | 86928.16 | 14-MAR-13:00 | 0.00 |
April | 0.364164E+11 | 0.125096E+11 | 687.78 | 0.339235E+11 | 0.249295E+10 | 0.00 | 0.58 | 08-APR-13:00 | 0.01 | 30-APR-19:17 | 234047.96 | 08-APR-14:00 | 228179.82 | 08-APR-13:00 | 33663.45 | 08-APR-17:55 | 64592.83 | 08-APR-13:00 | 0.00 |
May | 0.723110E+10 | 0.471073E+10 | 531.76 | 0.677721E+10 | 0.453885E+09 | 0.00 | 0.30 | 10-MAY-15:00 | 0.01 | 13-MAY-22:50 | 124780.53 | 10-MAY-15:00 | 105356.98 | 10-MAY-15:00 | 19441.44 | 14-MAY-13:53 | 36795.66 | 10-MAY-15:00 | 0.00 |
June | 0.166936E+12 | 0.476443E+11 | 548.31 | 0.118666E+12 | 0.482707E+11 | 0.00 | 0.84 | 27-JUN-14:05 | 0.01 | 25-JUN-06:50 | 432272.86 | 27-JUN-14:05 | 226853.25 | 27-JUN-13:00 | 222937.49 | 27-JUN-15:00 | 111447.70 | 27-JUN-14:10 | 0.00 |
July | 0.711245E+12 | 0.185580E+12 | 695.84 | 0.442307E+12 | 0.268938E+12 | 0.00 | 1.00 | 08-JUL-13:50 | 0.01 | 12-JUL-06:22 | 543995.15 | 20-JUL-22:13 | 345375.08 | 16-JUL-09:31 | 355306.61 | 20-JUL-22:00 | 141614.75 | 21-JUL-02:50 | 0.00 |
August | 0.826201E+12 | 0.214316E+12 | 709.02 | 0.554696E+12 | 0.271505E+12 | 0.00 | 1.00 | 06-AUG-17:42 | 0.01 | 02-AUG-04:53 | 527717.42 | 14-AUG-00:53 | 428594.08 | 10-AUG-12:53 | 326793.33 | 25-AUG-19:00 | 144407.42 | 13-AUG-15:00 | 0.00 |
September | 0.150678E+11 | 0.728209E+10 | 368.38 | 0.112554E+11 | 0.381243E+10 | 0.00 | 0.39 | 15-SEP-12:00 | 0.01 | 02-SEP-22:40 | 177632.62 | 15-SEP-12:00 | 131353.14 | 16-SEP-13:00 | 71365.74 | 15-SEP-12:00 | 48880.06 | 16-SEP-14:30 | 0.00 |
October | 0.854372E+10 | 0.496625E+10 | 577.35 | 0.822278E+10 | 0.320943E+09 | 0.00 | 0.23 | 11-OCT-15:00 | 0.00 | 10-OCT-23:50 | 88289.70 | 11-OCT-15:00 | 81952.95 | 11-OCT-14:00 | 9107.28 | 22-OCT-12:53 | 25668.57 | 11-OCT-15:00 | 0.00 |
November | 0.172421E+11 | 0.714028E+10 | 702.81 | 0.159210E+11 | 0.132107E+10 | 0.00 | 0.27 | 05-NOV-14:00 | 0.01 | 04-NOV-12:20 | 104722.61 | 05-NOV-13:55 | 85768.31 | 05-NOV-13:55 | 19838.12 | 05-NOV-14:25 | 28070.31 | 05-NOV-14:00 | 0.00 |
December | 0.150363E+11 | 0.697884E+10 | 742.14 | 0.146524E+11 | 0.383869E+09 | 0.00 | 0.18 | 01-DEC-11:00 | 0.01 | 01-DEC-07:30 | 67559.13 | 01-DEC-11:00 | 45291.36 | 01-DEC-11:00 | 22267.77 | 01-DEC-11:00 | 17849.11 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.185223E+13 | 0.511691E+12 | 7656.10 | 0.125165E+13 | 0.600575E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.656980E+10 | 0.425978E+10 | 368.38 | 0.656975E+10 | 46674.08 | 0.00 | 0.02 | 0.00 | 3825.74 | 3825.74 | 18.18 | 1941.07 | 0.00 | ||||||
Maximum of Months | 0.826201E+12 | 0.214316E+12 | 742.14 | 0.554696E+12 | 0.271505E+12 | 0.00 | 1.00 | 0.01 | 543995.15 | 428594.08 | 355306.61 | 144407.42 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.312890E+10 | 0.803230E+09 | 744.00 | 0.312860E+10 | 294138.99 | 0.00 | 0.28 | 15-JAN-16:35 | 0.04 | 30-JAN-07:03 | 2202.93 | 15-JAN-16:35 | 2202.93 | 15-JAN-16:35 | 10.30 | 02-JAN-07:03 | 524.09 | 15-JAN-16:35 | 0.00 |
February | 0.778657E+10 | 0.185230E+10 | 672.00 | 0.778657E+10 | -0.0 | 0.00 | 0.52 | 28-FEB-17:00 | 0.30 | 06-FEB-07:03 | 4203.69 | 28-FEB-17:00 | 4203.69 | 28-FEB-17:00 | 0.00 | 23-FEB-09:30 | 965.09 | 28-FEB-17:00 | 0.00 |
March | 0.148841E+11 | 0.328320E+10 | 744.00 | 0.148628E+11 | 21298719.46 | 0.00 | 0.83 | 25-MAR-17:55 | 0.58 | 01-MAR-07:03 | 7553.87 | 31-MAR-24:00 | 7553.87 | 31-MAR-24:00 | 266.71 | 16-MAR-15:40 | 1738.23 | 15-MAR-14:05 | 0.00 |
April | 0.197920E+11 | 0.407007E+10 | 720.00 | 0.197891E+11 | 2912362.76 | 0.00 | 0.96 | 02-APR-17:55 | 0.30 | 30-APR-23:55 | 8755.97 | 02-APR-17:55 | 8755.97 | 02-APR-17:55 | 99.05 | 12-APR-16:10 | 1841.53 | 07-APR-14:00 | 0.00 |
May | 0.558575E+10 | 0.130650E+10 | 744.00 | 0.555033E+10 | 35424135.62 | 0.00 | 0.46 | 31-MAY-24:00 | 0.19 | 12-MAY-06:10 | 4026.73 | 31-MAY-24:00 | 4026.73 | 31-MAY-24:00 | 221.05 | 17-MAY-15:20 | 857.40 | 31-MAY-24:00 | 0.00 |
June | 0.108868E+11 | 0.255962E+10 | 720.00 | 0.107049E+11 | 0.181900E+09 | 0.00 | 0.67 | 30-JUN-24:00 | 0.42 | 10-JUN-06:40 | 5944.43 | 30-JUN-24:00 | 5944.43 | 30-JUN-24:00 | 482.17 | 27-JUN-14:00 | 1509.71 | 27-JUN-13:00 | 0.00 |
July | 0.166302E+11 | 0.418324E+10 | 744.00 | 0.163163E+11 | 0.313866E+09 | 0.00 | 0.86 | 31-JUL-23:20 | 0.63 | 07-JUL-06:40 | 7880.61 | 31-JUL-24:00 | 7841.22 | 31-JUL-24:00 | 482.41 | 20-JUL-14:40 | 2160.98 | 21-JUL-14:00 | 0.00 |
August | 0.214771E+11 | 0.514032E+10 | 744.00 | 0.212387E+11 | 0.238322E+09 | 0.00 | 1.00 | 13-AUG-15:21 | 0.29 | 31-AUG-24:00 | 8788.70 | 14-AUG-15:50 | 8744.36 | 04-AUG-18:40 | 474.27 | 14-AUG-10:00 | 2687.58 | 13-AUG-15:12 | 0.00 |
September | 0.570663E+10 | 0.133541E+10 | 720.00 | 0.557413E+10 | 0.132502E+09 | 0.00 | 0.45 | 30-SEP-24:00 | 0.18 | 30-SEP-06:45 | 3792.95 | 30-SEP-24:00 | 3792.95 | 30-SEP-24:00 | 341.15 | 15-SEP-15:20 | 825.69 | 30-SEP-24:00 | 0.00 |
October | 0.103083E+11 | 0.225965E+10 | 744.00 | 0.102776E+11 | 30673272.34 | 0.00 | 0.64 | 31-OCT-24:00 | 0.39 | 30-OCT-06:05 | 5719.02 | 31-OCT-24:00 | 5719.02 | 31-OCT-24:00 | 184.76 | 12-OCT-15:30 | 1183.36 | 31-OCT-24:00 | 0.00 |
November | 0.145502E+11 | 0.311737E+10 | 720.00 | 0.145482E+11 | 2022490.50 | 0.00 | 0.73 | 26-NOV-14:00 | 0.59 | 15-NOV-07:05 | 6072.37 | 15-NOV-16:20 | 6072.37 | 15-NOV-16:20 | 144.08 | 16-NOV-16:20 | 1395.55 | 26-NOV-14:00 | 0.00 |
December | 0.194012E+11 | 0.415544E+10 | 744.00 | 0.194007E+11 | 501643.61 | 0.00 | 0.90 | 10-DEC-16:03 | 0.76 | 11-DEC-07:03 | 7846.97 | 17-DEC-16:10 | 7846.97 | 17-DEC-16:10 | 88.07 | 01-DEC-13:30 | 1660.74 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.150138E+12 | 0.340664E+11 | 8760.00 | 0.149178E+12 | 0.959717E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.312890E+10 | 0.803230E+09 | 672.00 | 0.312860E+10 | -0.0 | 0.00 | 0.28 | 0.04 | 2202.93 | 2202.93 | 0.00 | 524.09 | 0.00 | ||||||
Maximum of Months | 0.214771E+11 | 0.514032E+10 | 744.00 | 0.212387E+11 | 0.313866E+09 | 0.00 | 1.00 | 0.76 | 8788.70 | 8755.97 | 482.41 | 2687.58 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.543361E+10 | 0.160871E+10 | 443.77 | 0.543358E+10 | 31911.24 | 0.00 | 0.21 | 12-JAN-16:50 | 0.00 | 01-JAN-00:03 | 14825.06 | 12-JAN-16:50 | 14825.06 | 12-JAN-16:50 | 17.62 | 11-JAN-18:10 | 3745.53 | 12-JAN-16:50 | 0.00 |
February | 0.494842E+11 | 0.121758E+11 | 672.00 | 0.494842E+11 | -0.0 | 0.00 | 0.48 | 28-FEB-17:00 | 0.12 | 06-FEB-07:03 | 36849.82 | 28-FEB-17:00 | 36849.82 | 28-FEB-17:00 | 0.00 | 04-FEB-06:06 | 8539.83 | 28-FEB-17:00 | 0.00 |
March | 0.126105E+12 | 0.281971E+11 | 744.00 | 0.125892E+12 | 0.212743E+09 | 0.00 | 0.80 | 25-MAR-17:55 | 0.43 | 06-MAR-07:03 | 67936.13 | 31-MAR-23:40 | 67936.13 | 31-MAR-23:40 | 2627.41 | 16-MAR-15:40 | 16477.31 | 15-MAR-14:05 | 0.00 |
April | 0.179571E+12 | 0.372122E+11 | 720.00 | 0.179540E+12 | 30582603.64 | 0.00 | 0.93 | 22-APR-18:23 | 0.23 | 30-APR-23:55 | 80484.82 | 02-APR-18:00 | 80484.82 | 02-APR-18:00 | 991.67 | 12-APR-16:10 | 17461.74 | 07-APR-14:00 | 0.00 |
May | 0.487521E+11 | 0.114959E+11 | 744.00 | 0.484021E+11 | 0.350044E+09 | 0.00 | 0.46 | 31-MAY-24:00 | 0.13 | 01-MAY-06:05 | 38152.36 | 31-MAY-24:00 | 38152.36 | 31-MAY-24:00 | 2170.36 | 17-MAY-15:20 | 8135.70 | 31-MAY-24:00 | 0.00 |
June | 0.101461E+12 | 0.239458E+11 | 720.00 | 0.996523E+11 | 0.180825E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.39 | 14-JUN-06:05 | 56675.14 | 30-JUN-24:00 | 56675.14 | 30-JUN-24:00 | 4767.22 | 27-JUN-14:00 | 14349.71 | 27-JUN-13:00 | 0.00 |
July | 0.157261E+12 | 0.396426E+11 | 744.00 | 0.154136E+12 | 0.312553E+10 | 0.00 | 0.86 | 31-JUL-23:20 | 0.61 | 06-JUL-06:20 | 75673.10 | 31-JUL-24:00 | 75289.22 | 31-JUL-24:00 | 4805.92 | 20-JUL-14:40 | 20441.12 | 21-JUL-14:00 | 0.00 |
August | 0.203456E+12 | 0.487980E+11 | 744.00 | 0.201079E+12 | 0.237684E+10 | 0.00 | 0.99 | 04-AUG-18:40 | 0.24 | 31-AUG-24:00 | 83926.86 | 04-AUG-18:40 | 83926.86 | 04-AUG-18:40 | 4725.02 | 14-AUG-10:00 | 25202.64 | 13-AUG-15:21 | 0.00 |
September | 0.498360E+11 | 0.117674E+11 | 720.00 | 0.485340E+11 | 0.130200E+10 | 0.00 | 0.41 | 30-SEP-24:00 | 0.13 | 30-SEP-06:55 | 33165.80 | 30-SEP-24:00 | 33165.80 | 30-SEP-24:00 | 3363.66 | 15-SEP-15:20 | 7583.42 | 21-SEP-17:00 | 0.00 |
October | 0.871519E+11 | 0.193243E+11 | 744.00 | 0.868448E+11 | 0.307110E+09 | 0.00 | 0.60 | 31-OCT-23:40 | 0.28 | 30-OCT-06:05 | 50836.09 | 31-OCT-23:40 | 50836.09 | 31-OCT-23:40 | 1837.86 | 12-OCT-15:30 | 10915.53 | 11-OCT-17:00 | 0.00 |
November | 0.121261E+12 | 0.263923E+11 | 720.00 | 0.121239E+12 | 22062379.09 | 0.00 | 0.67 | 15-NOV-16:20 | 0.47 | 24-NOV-07:03 | 56275.49 | 15-NOV-16:20 | 56275.49 | 15-NOV-16:20 | 1433.57 | 16-NOV-16:10 | 11926.41 | 16-NOV-13:00 | 0.00 |
December | 0.155227E+12 | 0.340358E+11 | 744.00 | 0.155222E+12 | 5763976.51 | 0.00 | 0.84 | 04-DEC-16:20 | 0.58 | 11-DEC-07:03 | 69826.01 | 04-DEC-16:20 | 69826.01 | 04-DEC-16:20 | 904.54 | 01-DEC-13:30 | 14912.89 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.128500E+13 | 0.294596E+12 | 8459.77 | 0.127546E+13 | 0.954097E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.543361E+10 | 0.160871E+10 | 443.77 | 0.543358E+10 | -0.0 | 0.00 | 0.21 | 0.00 | 14825.06 | 14825.06 | 0.00 | 3745.53 | 0.00 | ||||||
Maximum of Months | 0.203456E+12 | 0.487980E+11 | 744.00 | 0.201079E+12 | 0.312553E+10 | 0.00 | 0.99 | 0.61 | 83926.86 | 83926.86 | 4805.92 | 25202.64 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 96147635.28 | 29286744.75 | 92.34 | 96147635.28 | 0.00 | 0.00 | 0.18 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 1264.02 | 12-JAN-16:40 | 1264.02 | 12-JAN-16:40 | 0.00 | 20-JAN-22:18 | 324.50 | 12-JAN-16:40 | 0.00 |
February | 0.328890E+10 | 0.829128E+09 | 644.97 | 0.328890E+10 | 0.00 | 0.00 | 0.47 | 28-FEB-17:00 | 0.00 | 01-FEB-00:03 | 3629.23 | 28-FEB-17:00 | 3629.23 | 28-FEB-17:00 | 0.00 | 10-FEB-01:30 | 843.67 | 28-FEB-17:00 | 0.00 |
March | 0.110070E+11 | 0.249476E+10 | 744.00 | 0.109859E+11 | 21152198.99 | 0.00 | 0.75 | 25-MAR-17:42 | 0.26 | 06-MAR-04:01 | 6368.10 | 31-MAR-23:20 | 6368.10 | 31-MAR-23:20 | 262.75 | 16-MAR-15:40 | 1668.69 | 15-MAR-14:05 | 0.00 |
April | 0.169121E+11 | 0.353692E+10 | 720.00 | 0.169091E+11 | 2993998.49 | 0.00 | 0.91 | 22-APR-18:15 | 0.17 | 30-APR-23:55 | 7947.10 | 09-APR-17:57 | 7947.10 | 09-APR-17:57 | 98.54 | 12-APR-16:10 | 1756.69 | 07-APR-14:00 | 0.00 |
May | 0.445542E+10 | 0.105952E+10 | 744.00 | 0.442072E+10 | 34705434.24 | 0.00 | 0.44 | 31-MAY-23:40 | 0.04 | 01-MAY-06:05 | 3726.44 | 31-MAY-23:40 | 3726.44 | 31-MAY-23:40 | 216.69 | 17-MAY-15:20 | 797.68 | 31-MAY-23:40 | 0.00 |
June | 0.100764E+11 | 0.238740E+10 | 720.00 | 0.989549E+10 | 0.180879E+09 | 0.00 | 0.65 | 30-JUN-23:40 | 0.33 | 14-JUN-06:05 | 5601.74 | 30-JUN-23:40 | 5601.74 | 30-JUN-23:40 | 479.49 | 27-JUN-14:00 | 1461.00 | 27-JUN-13:00 | 0.00 |
July | 0.157813E+11 | 0.398842E+10 | 744.00 | 0.154688E+11 | 0.312493E+09 | 0.00 | 0.85 | 31-JUL-23:20 | 0.58 | 07-JUL-06:20 | 7560.96 | 31-JUL-24:00 | 7522.35 | 31-JUL-24:00 | 480.90 | 20-JUL-14:40 | 2076.89 | 21-JUL-14:00 | 0.00 |
August | 0.203241E+11 | 0.489143E+10 | 744.00 | 0.200867E+11 | 0.237416E+09 | 0.00 | 0.99 | 13-AUG-15:52 | 0.21 | 31-AUG-24:00 | 8474.26 | 04-AUG-18:40 | 8474.26 | 04-AUG-18:40 | 472.36 | 14-AUG-10:00 | 2587.88 | 13-AUG-15:41 | 0.00 |
September | 0.461874E+10 | 0.110109E+10 | 720.00 | 0.448911E+10 | 0.129623E+09 | 0.00 | 0.37 | 04-SEP-17:44 | 0.05 | 30-SEP-06:55 | 3038.18 | 04-SEP-17:42 | 3038.18 | 04-SEP-17:50 | 338.04 | 15-SEP-15:20 | 776.44 | 21-SEP-17:00 | 0.00 |
October | 0.737969E+10 | 0.165812E+10 | 744.00 | 0.734931E+10 | 30376159.79 | 0.00 | 0.55 | 31-OCT-23:20 | 0.13 | 30-OCT-06:05 | 4680.70 | 31-OCT-23:20 | 4680.70 | 31-OCT-23:20 | 184.05 | 12-OCT-15:30 | 1099.99 | 11-OCT-17:00 | 0.00 |
November | 0.103265E+11 | 0.228568E+10 | 720.00 | 0.103244E+11 | 2083452.05 | 0.00 | 0.65 | 03-NOV-16:00 | 0.30 | 24-NOV-04:15 | 5503.03 | 15-NOV-16:20 | 5503.03 | 15-NOV-16:20 | 140.64 | 16-NOV-16:20 | 1168.33 | 16-NOV-17:00 | 0.00 |
December | 0.135386E+11 | 0.301926E+10 | 744.00 | 0.135381E+11 | 542611.93 | 0.00 | 0.80 | 04-DEC-16:20 | 0.43 | 26-DEC-04:01 | 6636.26 | 04-DEC-16:20 | 6636.26 | 04-DEC-16:20 | 85.85 | 01-DEC-13:30 | 1429.90 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.117805E+12 | 0.272810E+11 | 8081.31 | 0.116853E+12 | 0.952265E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 96147635.28 | 29286744.75 | 92.34 | 96147635.28 | 0.00 | 0.00 | 0.18 | 0.00 | 1264.02 | 1264.02 | 0.00 | 324.50 | 0.00 | ||||||
Maximum of Months | 0.203241E+11 | 0.489143E+10 | 744.00 | 0.200867E+11 | 0.312493E+09 | 0.00 | 0.99 | 0.58 | 8474.26 | 8474.26 | 480.90 | 2587.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.12 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.22 | 801.08 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.97 | 592.04 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.87 | 426.45 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.43 | 256.48 | 0.00 | 0.00 | 0.00 |
June | 421.37 | 35.87 | 385.50 | 447.26 | 163.78 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 479.61 | 114.26 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.03 | 151.27 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 225.90 | 253.56 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.30 | 425.45 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.93 | 572.47 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.58 | 840.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.07 | 452.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 114.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.37 | 35.87 | 385.50 | 479.61 | 852.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.12 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.22 | 801.08 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.97 | 592.04 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.87 | 426.45 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.43 | 256.48 | 0.00 | 0.00 | 0.00 |
June | 421.36 | 35.87 | 385.50 | 447.26 | 163.78 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 479.61 | 114.26 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.03 | 151.27 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 225.90 | 253.56 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.30 | 425.45 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.93 | 572.47 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.58 | 840.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.07 | 452.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 114.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.36 | 35.87 | 385.50 | 479.61 | 852.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.12 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.22 | 801.08 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.97 | 592.04 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.87 | 426.45 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.43 | 256.48 | 0.00 | 0.00 | 0.00 |
June | 421.37 | 35.87 | 385.50 | 447.26 | 163.78 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 479.61 | 114.26 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.03 | 151.27 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 225.90 | 253.56 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.30 | 425.45 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.93 | 572.47 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.58 | 840.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.07 | 452.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 114.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.37 | 35.87 | 385.50 | 479.61 | 852.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.06 | 0.00 | 128.06 | 0.02 | 852.12 | 0.00 | 0.00 | 0.00 |
February | 195.11 | 0.00 | 195.11 | 5.22 | 801.08 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.97 | 592.04 | 0.00 | 0.00 | 0.00 |
April | 301.50 | 1.20 | 300.29 | 140.87 | 426.45 | 0.00 | 0.00 | 0.00 |
May | 350.32 | 14.86 | 335.47 | 264.43 | 256.48 | 0.00 | 0.00 | 0.00 |
June | 421.36 | 35.87 | 385.50 | 447.26 | 163.78 | 0.00 | 0.00 | 0.00 |
July | 390.87 | 25.23 | 365.64 | 479.61 | 114.26 | 0.00 | 0.00 | 0.00 |
August | 338.21 | 5.15 | 333.07 | 391.03 | 151.27 | 0.00 | 0.00 | 0.00 |
September | 257.39 | 0.05 | 257.33 | 225.90 | 253.56 | 0.00 | 0.00 | 0.00 |
October | 192.41 | 0.00 | 192.41 | 78.30 | 425.45 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.93 | 572.47 | 0.00 | 0.00 | 0.00 |
December | 119.86 | 0.00 | 119.86 | 0.58 | 840.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.33 | 6.89 | 248.44 | 177.07 | 452.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 0.00 | 119.86 | 0.02 | 114.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.36 | 35.87 | 385.50 | 479.61 | 852.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.05 | 0.00 | 128.05 | 0.02 | 852.08 | 0.00 | 0.00 | 0.00 |
February | 195.10 | 0.00 | 195.10 | 5.22 | 801.05 | 0.00 | 0.00 | 0.00 |
March | 236.61 | 0.00 | 236.61 | 61.97 | 592.02 | 0.00 | 0.00 | 0.00 |
April | 301.48 | 1.20 | 300.28 | 140.86 | 426.43 | 0.00 | 0.00 | 0.00 |
May | 350.31 | 14.86 | 335.45 | 264.42 | 256.47 | 0.00 | 0.00 | 0.00 |
June | 421.35 | 35.87 | 385.48 | 447.24 | 163.78 | 0.00 | 0.00 | 0.00 |
July | 390.86 | 25.23 | 365.63 | 479.59 | 114.25 | 0.00 | 0.00 | 0.00 |
August | 338.20 | 5.14 | 333.05 | 391.02 | 151.27 | 0.00 | 0.00 | 0.00 |
September | 257.38 | 0.05 | 257.32 | 225.89 | 253.55 | 0.00 | 0.00 | 0.00 |
October | 192.40 | 0.00 | 192.40 | 78.30 | 425.44 | 0.00 | 0.00 | 0.00 |
November | 129.29 | 0.00 | 129.29 | 16.93 | 572.45 | 0.00 | 0.00 | 0.00 |
December | 119.85 | 0.00 | 119.85 | 0.58 | 840.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.32 | 6.89 | 248.43 | 177.06 | 452.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.85 | 0.00 | 119.85 | 0.02 | 114.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.35 | 35.87 | 385.48 | 479.59 | 852.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.38 | 83.96 | 176.42 | 92.59 | 861.37 | 0.00 | 0.00 | 0.00 |
February | 382.06 | 114.65 | 267.41 | 165.34 | 811.58 | 0.00 | 0.00 | 0.00 |
March | 548.24 | 229.60 | 318.64 | 409.64 | 597.39 | 0.00 | 0.00 | 0.00 |
April | 725.63 | 320.62 | 405.01 | 662.23 | 435.78 | 0.00 | 0.00 | 0.00 |
May | 812.97 | 359.62 | 453.35 | 874.26 | 287.48 | 0.00 | 0.00 | 0.00 |
June | 907.95 | 401.27 | 506.68 | 1098.06 | 183.42 | 0.00 | 0.00 | 0.00 |
July | 871.87 | 383.87 | 488.00 | 1132.97 | 125.18 | 0.00 | 0.00 | 0.00 |
August | 787.40 | 330.51 | 456.89 | 1002.02 | 161.89 | 0.00 | 0.00 | 0.00 |
September | 655.25 | 290.64 | 364.61 | 748.96 | 267.93 | 0.00 | 0.00 | 0.00 |
October | 444.64 | 183.92 | 260.73 | 380.79 | 438.39 | 0.00 | 0.00 | 0.00 |
November | 252.21 | 80.91 | 171.30 | 140.16 | 591.09 | 0.00 | 0.00 | 0.00 |
December | 203.04 | 41.95 | 161.09 | 45.76 | 858.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.82 | 235.70 | 336.12 | 564.91 | 466.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.04 | 41.95 | 161.09 | 45.76 | 125.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 907.95 | 401.27 | 506.68 | 1132.97 | 861.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.38 | 83.96 | 176.42 | 92.59 | 861.37 | 0.00 | 0.00 | 0.00 |
February | 382.06 | 114.65 | 267.41 | 165.34 | 811.58 | 0.00 | 0.00 | 0.00 |
March | 548.24 | 229.60 | 318.64 | 409.64 | 597.39 | 0.00 | 0.00 | 0.00 |
April | 725.63 | 320.62 | 405.01 | 662.23 | 435.78 | 0.00 | 0.00 | 0.00 |
May | 812.97 | 359.62 | 453.35 | 874.26 | 287.48 | 0.00 | 0.00 | 0.00 |
June | 907.95 | 401.27 | 506.68 | 1098.06 | 183.42 | 0.00 | 0.00 | 0.00 |
July | 871.87 | 383.87 | 488.00 | 1132.97 | 125.18 | 0.00 | 0.00 | 0.00 |
August | 787.40 | 330.51 | 456.89 | 1002.02 | 161.89 | 0.00 | 0.00 | 0.00 |
September | 655.25 | 290.64 | 364.61 | 748.96 | 267.93 | 0.00 | 0.00 | 0.00 |
October | 444.64 | 183.92 | 260.73 | 380.79 | 438.39 | 0.00 | 0.00 | 0.00 |
November | 252.21 | 80.91 | 171.30 | 140.16 | 591.09 | 0.00 | 0.00 | 0.00 |
December | 203.04 | 41.95 | 161.09 | 45.76 | 858.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.82 | 235.70 | 336.12 | 564.91 | 466.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.04 | 41.95 | 161.09 | 45.76 | 125.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 907.95 | 401.27 | 506.68 | 1132.97 | 861.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.38 | 83.96 | 176.42 | 92.59 | 861.35 | 0.00 | 0.00 | 0.00 |
February | 382.05 | 114.64 | 267.41 | 165.34 | 811.56 | 0.00 | 0.00 | 0.00 |
March | 548.23 | 229.60 | 318.64 | 409.63 | 597.38 | 0.00 | 0.00 | 0.00 |
April | 725.62 | 320.62 | 405.00 | 662.22 | 435.77 | 0.00 | 0.00 | 0.00 |
May | 812.96 | 359.61 | 453.34 | 874.24 | 287.48 | 0.00 | 0.00 | 0.00 |
June | 907.93 | 401.26 | 506.67 | 1098.04 | 183.42 | 0.00 | 0.00 | 0.00 |
July | 871.85 | 383.87 | 487.99 | 1132.95 | 125.18 | 0.00 | 0.00 | 0.00 |
August | 787.38 | 330.50 | 456.88 | 1002.01 | 161.88 | 0.00 | 0.00 | 0.00 |
September | 655.24 | 290.64 | 364.60 | 748.94 | 267.92 | 0.00 | 0.00 | 0.00 |
October | 444.63 | 183.91 | 260.72 | 380.78 | 438.39 | 0.00 | 0.00 | 0.00 |
November | 252.20 | 80.90 | 171.30 | 140.16 | 591.08 | 0.00 | 0.00 | 0.00 |
December | 203.04 | 41.95 | 161.09 | 45.76 | 858.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.81 | 235.69 | 336.11 | 564.90 | 466.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.04 | 41.95 | 161.09 | 45.76 | 125.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 907.93 | 401.26 | 506.67 | 1132.95 | 861.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.80 | 706.70 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.57 | 692.90 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.30 | 527.72 | 0.00 | 0.00 | 0.00 |
April | 635.51 | 253.95 | 381.56 | 637.07 | 422.92 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.45 | 278.84 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.87 | 667.13 | 179.93 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 752.78 | 124.25 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 832.57 | 160.31 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.37 | 255.20 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.18 | 393.48 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.36 | 509.23 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.16 | 709.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.16 | 411.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.16 | 124.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.87 | 894.37 | 709.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.80 | 706.70 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.57 | 692.90 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.30 | 527.72 | 0.00 | 0.00 | 0.00 |
April | 635.50 | 253.95 | 381.56 | 637.07 | 422.92 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.45 | 278.84 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.86 | 667.13 | 179.93 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 752.78 | 124.25 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 832.56 | 160.31 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.37 | 255.20 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.18 | 393.48 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.36 | 509.23 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.16 | 709.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.16 | 411.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.16 | 124.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.86 | 894.37 | 709.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.80 | 706.70 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.57 | 692.90 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.30 | 527.72 | 0.00 | 0.00 | 0.00 |
April | 635.51 | 253.95 | 381.56 | 637.07 | 422.92 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.45 | 278.84 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.87 | 667.13 | 179.93 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 752.78 | 124.25 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 832.57 | 160.31 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.37 | 255.20 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.18 | 393.48 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.36 | 509.23 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.16 | 709.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.16 | 411.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.16 | 124.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.87 | 894.37 | 709.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.65 | 321.43 | 229.22 | 434.80 | 706.70 | 0.00 | 0.00 | 0.00 |
February | 628.70 | 303.15 | 325.55 | 487.57 | 692.90 | 0.00 | 0.00 | 0.00 |
March | 767.37 | 431.18 | 336.19 | 739.30 | 527.72 | 0.00 | 0.00 | 0.00 |
April | 635.50 | 253.95 | 381.56 | 637.07 | 422.92 | 0.00 | 0.00 | 0.00 |
May | 556.12 | 161.52 | 394.60 | 613.45 | 278.84 | 0.00 | 0.00 | 0.00 |
June | 540.37 | 114.51 | 425.86 | 667.13 | 179.93 | 0.00 | 0.00 | 0.00 |
July | 551.63 | 133.84 | 417.79 | 752.78 | 124.25 | 0.00 | 0.00 | 0.00 |
August | 619.30 | 200.79 | 418.51 | 832.56 | 160.31 | 0.00 | 0.00 | 0.00 |
September | 720.06 | 350.72 | 369.34 | 894.37 | 255.20 | 0.00 | 0.00 | 0.00 |
October | 688.99 | 393.56 | 295.43 | 734.18 | 393.48 | 0.00 | 0.00 | 0.00 |
November | 493.44 | 278.56 | 214.88 | 454.36 | 509.23 | 0.00 | 0.00 | 0.00 |
December | 460.45 | 238.30 | 222.15 | 340.16 | 709.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.86 | 264.99 | 335.88 | 633.16 | 411.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.45 | 114.51 | 214.88 | 340.16 | 124.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.37 | 431.18 | 425.86 | 894.37 | 709.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 550.63 | 321.42 | 229.21 | 434.78 | 706.67 | 0.00 | 0.00 | 0.00 |
February | 628.68 | 303.14 | 325.53 | 487.56 | 692.87 | 0.00 | 0.00 | 0.00 |
March | 767.34 | 431.16 | 336.18 | 739.27 | 527.70 | 0.00 | 0.00 | 0.00 |
April | 635.48 | 253.94 | 381.54 | 637.04 | 422.90 | 0.00 | 0.00 | 0.00 |
May | 556.10 | 161.52 | 394.59 | 613.43 | 278.83 | 0.00 | 0.00 | 0.00 |
June | 540.35 | 114.50 | 425.85 | 667.10 | 179.92 | 0.00 | 0.00 | 0.00 |
July | 551.61 | 133.84 | 417.77 | 752.75 | 124.24 | 0.00 | 0.00 | 0.00 |
August | 619.27 | 200.78 | 418.49 | 832.53 | 160.30 | 0.00 | 0.00 | 0.00 |
September | 720.03 | 350.71 | 369.32 | 894.33 | 255.19 | 0.00 | 0.00 | 0.00 |
October | 688.96 | 393.55 | 295.41 | 734.15 | 393.46 | 0.00 | 0.00 | 0.00 |
November | 493.42 | 278.55 | 214.87 | 454.34 | 509.21 | 0.00 | 0.00 | 0.00 |
December | 460.43 | 238.29 | 222.14 | 340.15 | 709.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.84 | 264.98 | 335.86 | 633.14 | 411.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.43 | 114.50 | 214.87 | 340.15 | 124.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.34 | 431.16 | 425.85 | 894.33 | 709.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.40 | 52.45 | 170.96 | 54.11 | 934.28 | 0.00 | 0.00 | 0.00 |
February | 362.07 | 93.06 | 269.02 | 133.65 | 898.97 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 242.98 | 324.50 | 420.64 | 677.16 | 0.00 | 0.00 | 0.00 |
April | 694.81 | 284.90 | 409.91 | 611.59 | 518.80 | 0.00 | 0.00 | 0.00 |
May | 819.64 | 370.42 | 449.21 | 878.61 | 327.81 | 0.00 | 0.00 | 0.00 |
June | 988.92 | 465.15 | 523.77 | 1198.14 | 223.61 | 0.00 | 0.00 | 0.00 |
July | 884.13 | 387.63 | 496.50 | 1136.47 | 164.29 | 0.00 | 0.00 | 0.00 |
August | 799.64 | 340.02 | 459.63 | 1007.13 | 210.96 | 0.00 | 0.00 | 0.00 |
September | 627.97 | 271.19 | 356.78 | 710.92 | 304.97 | 0.00 | 0.00 | 0.00 |
October | 407.08 | 143.40 | 263.68 | 328.57 | 500.57 | 0.00 | 0.00 | 0.00 |
November | 241.24 | 69.52 | 171.72 | 121.15 | 678.71 | 0.00 | 0.00 | 0.00 |
December | 209.13 | 45.57 | 163.56 | 47.53 | 985.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.73 | 231.19 | 338.54 | 556.33 | 533.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.13 | 45.57 | 163.56 | 47.53 | 164.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.92 | 465.15 | 523.77 | 1198.14 | 985.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.40 | 52.45 | 170.96 | 54.11 | 934.28 | 0.00 | 0.00 | 0.00 |
February | 362.07 | 93.06 | 269.02 | 133.65 | 898.97 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 242.98 | 324.50 | 420.64 | 677.16 | 0.00 | 0.00 | 0.00 |
April | 694.81 | 284.90 | 409.91 | 611.59 | 518.80 | 0.00 | 0.00 | 0.00 |
May | 819.64 | 370.42 | 449.21 | 878.61 | 327.81 | 0.00 | 0.00 | 0.00 |
June | 988.92 | 465.15 | 523.77 | 1198.14 | 223.61 | 0.00 | 0.00 | 0.00 |
July | 884.13 | 387.63 | 496.50 | 1136.47 | 164.29 | 0.00 | 0.00 | 0.00 |
August | 799.64 | 340.02 | 459.63 | 1007.13 | 210.96 | 0.00 | 0.00 | 0.00 |
September | 627.97 | 271.19 | 356.78 | 710.92 | 304.97 | 0.00 | 0.00 | 0.00 |
October | 407.08 | 143.40 | 263.68 | 328.57 | 500.57 | 0.00 | 0.00 | 0.00 |
November | 241.24 | 69.52 | 171.72 | 121.15 | 678.71 | 0.00 | 0.00 | 0.00 |
December | 209.13 | 45.57 | 163.56 | 47.53 | 985.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.73 | 231.19 | 338.54 | 556.33 | 533.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.13 | 45.57 | 163.56 | 47.53 | 164.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.92 | 465.15 | 523.77 | 1198.14 | 985.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.40 | 52.45 | 170.95 | 54.11 | 934.26 | 0.00 | 0.00 | 0.00 |
February | 362.07 | 93.05 | 269.01 | 133.64 | 898.95 | 0.00 | 0.00 | 0.00 |
March | 567.48 | 242.98 | 324.50 | 420.63 | 677.15 | 0.00 | 0.00 | 0.00 |
April | 694.80 | 284.89 | 409.90 | 611.58 | 518.79 | 0.00 | 0.00 | 0.00 |
May | 819.62 | 370.42 | 449.21 | 878.59 | 327.80 | 0.00 | 0.00 | 0.00 |
June | 988.90 | 465.14 | 523.76 | 1198.12 | 223.60 | 0.00 | 0.00 | 0.00 |
July | 884.11 | 387.63 | 496.49 | 1136.45 | 164.28 | 0.00 | 0.00 | 0.00 |
August | 799.63 | 340.01 | 459.62 | 1007.11 | 210.96 | 0.00 | 0.00 | 0.00 |
September | 627.96 | 271.19 | 356.77 | 710.90 | 304.96 | 0.00 | 0.00 | 0.00 |
October | 407.07 | 143.39 | 263.68 | 328.57 | 500.56 | 0.00 | 0.00 | 0.00 |
November | 241.23 | 69.51 | 171.72 | 121.15 | 678.69 | 0.00 | 0.00 | 0.00 |
December | 209.13 | 45.57 | 163.56 | 47.52 | 985.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.72 | 231.19 | 338.53 | 556.32 | 533.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.13 | 45.57 | 163.56 | 47.52 | 164.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.90 | 465.14 | 523.76 | 1198.12 | 985.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.28 | 0.00 | 640.28 | 5.46 | 3860.64 | 0.00 | 0.00 | 0.00 |
February | 975.54 | 0.00 | 975.54 | 54.35 | 3624.35 | 0.00 | 0.00 | 0.00 |
March | 1183.06 | 0.00 | 1183.06 | 359.84 | 2668.22 | 0.00 | 0.00 | 0.00 |
April | 1507.46 | 6.02 | 1501.45 | 776.47 | 1920.08 | 0.00 | 0.00 | 0.00 |
May | 1751.60 | 74.28 | 1677.32 | 1347.37 | 1219.36 | 0.00 | 0.00 | 0.00 |
June | 2106.80 | 179.34 | 1927.46 | 2254.02 | 781.43 | 0.00 | 0.00 | 0.00 |
July | 1954.34 | 126.16 | 1828.18 | 2424.00 | 543.70 | 0.00 | 0.00 | 0.00 |
August | 1691.04 | 25.73 | 1665.32 | 1981.03 | 722.01 | 0.00 | 0.00 | 0.00 |
September | 1286.92 | 0.27 | 1286.65 | 1153.05 | 1184.91 | 0.00 | 0.00 | 0.00 |
October | 962.03 | 0.00 | 962.03 | 446.42 | 1909.45 | 0.00 | 0.00 | 0.00 |
November | 646.46 | 0.00 | 646.46 | 124.05 | 2477.52 | 0.00 | 0.00 | 0.00 |
December | 599.28 | 0.00 | 599.28 | 8.03 | 3707.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1276.64 | 34.46 | 1242.18 | 916.40 | 2043.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.28 | 0.00 | 599.28 | 5.46 | 543.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2106.80 | 179.34 | 1927.46 | 2424.00 | 3860.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.13 | 251.88 | 529.25 | 298.60 | 2344.39 | 0.00 | 0.00 | 0.00 |
February | 1146.16 | 343.94 | 802.23 | 530.30 | 2234.27 | 0.00 | 0.00 | 0.00 |
March | 1644.71 | 688.79 | 955.92 | 1244.31 | 1673.23 | 0.00 | 0.00 | 0.00 |
April | 2176.88 | 961.86 | 1215.02 | 1989.00 | 1238.39 | 0.00 | 0.00 | 0.00 |
May | 2438.88 | 1078.85 | 1360.04 | 2601.81 | 840.88 | 0.00 | 0.00 | 0.00 |
June | 2723.82 | 1203.80 | 1520.03 | 3269.36 | 539.71 | 0.00 | 0.00 | 0.00 |
July | 2615.59 | 1151.61 | 1463.98 | 3378.38 | 373.92 | 0.00 | 0.00 | 0.00 |
August | 2362.16 | 991.51 | 1370.65 | 2982.70 | 489.60 | 0.00 | 0.00 | 0.00 |
September | 1965.73 | 871.92 | 1093.81 | 2233.03 | 775.76 | 0.00 | 0.00 | 0.00 |
October | 1333.91 | 551.74 | 782.17 | 1152.66 | 1229.32 | 0.00 | 0.00 | 0.00 |
November | 756.62 | 242.71 | 513.90 | 444.83 | 1598.69 | 0.00 | 0.00 | 0.00 |
December | 609.12 | 125.86 | 483.26 | 154.57 | 2322.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1715.44 | 707.09 | 1008.35 | 1696.27 | 1300.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 609.12 | 125.86 | 483.26 | 154.57 | 373.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2723.82 | 1203.80 | 1520.03 | 3378.38 | 2344.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2753.21 | 1607.13 | 1146.08 | 2186.84 | 3367.54 | 0.00 | 0.00 | 0.00 |
February | 3143.47 | 1515.75 | 1627.72 | 2452.17 | 3315.49 | 0.00 | 0.00 | 0.00 |
March | 3836.82 | 2155.88 | 1680.93 | 3681.66 | 2546.64 | 0.00 | 0.00 | 0.00 |
April | 3177.49 | 1269.73 | 1907.75 | 3181.72 | 2026.47 | 0.00 | 0.00 | 0.00 |
May | 2780.58 | 807.60 | 1972.99 | 3045.48 | 1365.45 | 0.00 | 0.00 | 0.00 |
June | 2701.83 | 572.53 | 2129.30 | 3324.14 | 869.14 | 0.00 | 0.00 | 0.00 |
July | 2758.13 | 669.21 | 2088.92 | 3759.89 | 600.80 | 0.00 | 0.00 | 0.00 |
August | 3096.46 | 1003.95 | 2092.51 | 4151.89 | 783.05 | 0.00 | 0.00 | 0.00 |
September | 3600.26 | 1753.59 | 1846.66 | 4443.99 | 1248.25 | 0.00 | 0.00 | 0.00 |
October | 3444.91 | 1967.80 | 1477.11 | 3651.08 | 1904.31 | 0.00 | 0.00 | 0.00 |
November | 2467.18 | 1392.80 | 1074.37 | 2278.97 | 2410.32 | 0.00 | 0.00 | 0.00 |
December | 2302.23 | 1191.51 | 1110.72 | 1723.66 | 3328.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3004.28 | 1324.92 | 1679.36 | 3160.94 | 1973.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2302.23 | 572.53 | 1074.37 | 1723.66 | 600.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3836.82 | 2155.88 | 2129.30 | 4443.99 | 3367.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 670.20 | 157.34 | 512.86 | 178.99 | 2484.58 | 0.00 | 0.00 | 0.00 |
February | 1086.21 | 279.16 | 807.05 | 448.63 | 2357.05 | 0.00 | 0.00 | 0.00 |
March | 1702.44 | 728.94 | 973.49 | 1313.85 | 1759.59 | 0.00 | 0.00 | 0.00 |
April | 2084.41 | 854.69 | 1229.72 | 1896.15 | 1339.79 | 0.00 | 0.00 | 0.00 |
May | 2458.89 | 1111.26 | 1347.63 | 2642.61 | 921.99 | 0.00 | 0.00 | 0.00 |
June | 2966.72 | 1395.42 | 1571.30 | 3602.59 | 615.56 | 0.00 | 0.00 | 0.00 |
July | 2652.36 | 1162.89 | 1489.48 | 3434.86 | 439.97 | 0.00 | 0.00 | 0.00 |
August | 2398.91 | 1020.04 | 1378.87 | 3056.82 | 554.13 | 0.00 | 0.00 | 0.00 |
September | 1883.89 | 813.57 | 1070.32 | 2144.96 | 842.52 | 0.00 | 0.00 | 0.00 |
October | 1221.23 | 430.19 | 791.04 | 1030.58 | 1305.99 | 0.00 | 0.00 | 0.00 |
November | 723.70 | 208.55 | 515.16 | 405.07 | 1671.50 | 0.00 | 0.00 | 0.00 |
December | 627.39 | 136.70 | 490.69 | 169.76 | 2423.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1709.18 | 693.57 | 1015.61 | 1700.48 | 1388.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 627.39 | 136.70 | 490.69 | 169.76 | 439.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2966.72 | 1395.42 | 1571.30 | 3602.59 | 2484.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.28 | 0.00 | 640.28 | 12.56 | 3707.02 | 0.00 | 0.00 | 0.00 |
February | 975.54 | 0.00 | 975.54 | 72.00 | 3466.74 | 0.00 | 0.00 | 0.00 |
March | 1183.06 | 0.00 | 1183.06 | 393.33 | 2494.27 | 0.00 | 0.00 | 0.00 |
April | 1507.46 | 6.02 | 1501.45 | 828.62 | 1782.36 | 0.00 | 0.00 | 0.00 |
May | 1751.60 | 74.28 | 1677.32 | 1370.42 | 1165.37 | 0.00 | 0.00 | 0.00 |
June | 2106.80 | 179.34 | 1927.46 | 2243.71 | 770.48 | 0.00 | 0.00 | 0.00 |
July | 1954.34 | 126.16 | 1828.18 | 2400.78 | 545.96 | 0.00 | 0.00 | 0.00 |
August | 1691.04 | 25.73 | 1665.32 | 1968.35 | 714.66 | 0.00 | 0.00 | 0.00 |
September | 1286.92 | 0.27 | 1286.65 | 1166.90 | 1127.92 | 0.00 | 0.00 | 0.00 |
October | 962.03 | 0.00 | 962.03 | 499.21 | 1728.35 | 0.00 | 0.00 | 0.00 |
November | 646.46 | 0.00 | 646.46 | 158.36 | 2238.21 | 0.00 | 0.00 | 0.00 |
December | 599.28 | 0.00 | 599.28 | 13.43 | 3509.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1276.64 | 34.46 | 1242.18 | 932.45 | 1930.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.28 | 0.00 | 599.28 | 12.56 | 545.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2106.80 | 179.34 | 1927.46 | 2400.78 | 3707.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.13 | 251.88 | 529.25 | 312.02 | 2253.14 | 0.00 | 0.00 | 0.00 |
February | 1146.16 | 343.94 | 802.23 | 554.68 | 2138.63 | 0.00 | 0.00 | 0.00 |
March | 1644.71 | 688.79 | 955.92 | 1282.72 | 1555.97 | 0.00 | 0.00 | 0.00 |
April | 2176.88 | 961.86 | 1215.02 | 2028.99 | 1156.85 | 0.00 | 0.00 | 0.00 |
May | 2438.88 | 1078.85 | 1360.04 | 2613.43 | 809.54 | 0.00 | 0.00 | 0.00 |
June | 2723.82 | 1203.80 | 1520.03 | 3264.47 | 533.21 | 0.00 | 0.00 | 0.00 |
July | 2615.59 | 1151.61 | 1463.98 | 3367.78 | 375.39 | 0.00 | 0.00 | 0.00 |
August | 2362.16 | 991.51 | 1370.65 | 2977.54 | 485.14 | 0.00 | 0.00 | 0.00 |
September | 1965.73 | 871.92 | 1093.81 | 2243.52 | 744.21 | 0.00 | 0.00 | 0.00 |
October | 1333.91 | 551.74 | 782.17 | 1195.79 | 1118.63 | 0.00 | 0.00 | 0.00 |
November | 756.62 | 242.71 | 513.90 | 480.76 | 1439.90 | 0.00 | 0.00 | 0.00 |
December | 609.12 | 125.86 | 483.26 | 164.99 | 2204.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1715.44 | 707.09 | 1008.35 | 1713.44 | 1230.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 609.12 | 125.86 | 483.26 | 164.99 | 375.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2723.82 | 1203.80 | 1520.03 | 3367.78 | 2253.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2753.21 | 1607.13 | 1146.08 | 2221.49 | 3206.48 | 0.00 | 0.00 | 0.00 |
February | 3143.47 | 1515.75 | 1627.72 | 2496.67 | 3156.34 | 0.00 | 0.00 | 0.00 |
March | 3836.82 | 2155.88 | 1680.93 | 3730.87 | 2375.38 | 0.00 | 0.00 | 0.00 |
April | 3177.49 | 1269.73 | 1907.75 | 3223.31 | 1896.09 | 0.00 | 0.00 | 0.00 |
May | 2780.58 | 807.60 | 1972.99 | 3053.53 | 1309.33 | 0.00 | 0.00 | 0.00 |
June | 2701.83 | 572.53 | 2129.30 | 3308.10 | 854.92 | 0.00 | 0.00 | 0.00 |
July | 2758.13 | 669.21 | 2088.92 | 3734.34 | 601.86 | 0.00 | 0.00 | 0.00 |
August | 3096.46 | 1003.95 | 2092.51 | 4133.40 | 775.45 | 0.00 | 0.00 | 0.00 |
September | 3600.26 | 1753.59 | 1846.66 | 4446.09 | 1200.19 | 0.00 | 0.00 | 0.00 |
October | 3444.91 | 1967.80 | 1477.11 | 3700.19 | 1747.55 | 0.00 | 0.00 | 0.00 |
November | 2467.18 | 1392.80 | 1074.37 | 2335.06 | 2186.60 | 0.00 | 0.00 | 0.00 |
December | 2302.23 | 1191.51 | 1110.72 | 1762.96 | 3136.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3004.28 | 1324.92 | 1679.36 | 3182.81 | 1863.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2302.23 | 572.53 | 1074.37 | 1762.96 | 601.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3836.82 | 2155.88 | 2129.30 | 4446.09 | 3206.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 670.20 | 157.34 | 512.86 | 187.81 | 2384.20 | 0.00 | 0.00 | 0.00 |
February | 1086.21 | 279.16 | 807.05 | 463.35 | 2263.21 | 0.00 | 0.00 | 0.00 |
March | 1702.44 | 728.94 | 973.49 | 1335.23 | 1655.65 | 0.00 | 0.00 | 0.00 |
April | 2084.41 | 854.69 | 1229.72 | 1920.78 | 1260.95 | 0.00 | 0.00 | 0.00 |
May | 2458.89 | 1111.26 | 1347.63 | 2644.89 | 887.90 | 0.00 | 0.00 | 0.00 |
June | 2966.72 | 1395.42 | 1571.30 | 3587.63 | 605.78 | 0.00 | 0.00 | 0.00 |
July | 2652.36 | 1162.89 | 1489.48 | 3416.08 | 438.70 | 0.00 | 0.00 | 0.00 |
August | 2398.91 | 1020.04 | 1378.87 | 3043.70 | 548.53 | 0.00 | 0.00 | 0.00 |
September | 1883.89 | 813.57 | 1070.32 | 2146.54 | 811.09 | 0.00 | 0.00 | 0.00 |
October | 1221.23 | 430.19 | 791.04 | 1058.61 | 1205.64 | 0.00 | 0.00 | 0.00 |
November | 723.70 | 208.55 | 515.16 | 428.35 | 1534.58 | 0.00 | 0.00 | 0.00 |
December | 627.39 | 136.70 | 490.69 | 178.51 | 2307.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1709.18 | 693.57 | 1015.61 | 1707.62 | 1320.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 627.39 | 136.70 | 490.69 | 178.51 | 438.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2966.72 | 1395.42 | 1571.30 | 3587.63 | 2384.20 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342989E+09 | 0.00 | 0.342989E+09 | 49417.70 | 0.228231E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12621050.52 | 0.193797E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.165981E+09 | 0.158573E+10 |
April | 0.781477E+09 | 3118403.21 | 0.778359E+09 | 0.365133E+09 | 0.110535E+10 |
May | 0.938306E+09 | 39789500.73 | 0.898516E+09 | 0.708244E+09 | 0.686954E+09 |
June | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.115931E+10 | 0.424529E+09 |
July | 0.104691E+10 | 67580513.96 | 0.979331E+09 | 0.128458E+10 | 0.306021E+09 |
August | 0.905870E+09 | 13780841.18 | 0.892089E+09 | 0.104734E+10 | 0.405167E+09 |
September | 0.667148E+09 | 138604.48 | 0.667009E+09 | 0.585535E+09 | 0.657224E+09 |
October | 0.515346E+09 | 0.00 | 0.515346E+09 | 0.209717E+09 | 0.113954E+10 |
November | 0.335129E+09 | 0.00 | 0.335129E+09 | 43885408.62 | 0.148385E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1557362.25 | 0.225224E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217380E+09 | 0.783476E+10 | 0.558395E+10 | 0.142669E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 49417.70 | 0.306021E+09 |
Maximum of Months | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.128458E+10 | 0.228231E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342988E+09 | 0.00 | 0.342988E+09 | 49416.32 | 0.228232E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12620949.82 | 0.193797E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.165980E+09 | 0.158573E+10 |
April | 0.781476E+09 | 3118399.47 | 0.778358E+09 | 0.365132E+09 | 0.110535E+10 |
May | 0.938305E+09 | 39789452.98 | 0.898516E+09 | 0.708244E+09 | 0.686954E+09 |
June | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.115930E+10 | 0.424529E+09 |
July | 0.104691E+10 | 67580432.87 | 0.979331E+09 | 0.128458E+10 | 0.306021E+09 |
August | 0.905869E+09 | 13780824.64 | 0.892088E+09 | 0.104734E+10 | 0.405167E+09 |
September | 0.667148E+09 | 138604.32 | 0.667009E+09 | 0.585534E+09 | 0.657224E+09 |
October | 0.515345E+09 | 0.00 | 0.515345E+09 | 0.209717E+09 | 0.113954E+10 |
November | 0.335128E+09 | 0.00 | 0.335128E+09 | 43885288.27 | 0.148385E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1557352.44 | 0.225224E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217379E+09 | 0.783476E+10 | 0.558394E+10 | 0.142669E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 49416.32 | 0.306021E+09 |
Maximum of Months | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.128458E+10 | 0.228232E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342989E+09 | 0.00 | 0.342989E+09 | 49417.70 | 0.228231E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12621050.52 | 0.193797E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.165981E+09 | 0.158573E+10 |
April | 0.781477E+09 | 3118403.21 | 0.778359E+09 | 0.365133E+09 | 0.110535E+10 |
May | 0.938306E+09 | 39789500.73 | 0.898516E+09 | 0.708244E+09 | 0.686954E+09 |
June | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.115931E+10 | 0.424529E+09 |
July | 0.104691E+10 | 67580513.96 | 0.979331E+09 | 0.128458E+10 | 0.306021E+09 |
August | 0.905870E+09 | 13780841.18 | 0.892089E+09 | 0.104734E+10 | 0.405167E+09 |
September | 0.667148E+09 | 138604.48 | 0.667009E+09 | 0.585535E+09 | 0.657224E+09 |
October | 0.515346E+09 | 0.00 | 0.515346E+09 | 0.209717E+09 | 0.113954E+10 |
November | 0.335129E+09 | 0.00 | 0.335129E+09 | 43885408.62 | 0.148385E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1557362.25 | 0.225224E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217380E+09 | 0.783476E+10 | 0.558395E+10 | 0.142669E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 49417.70 | 0.306021E+09 |
Maximum of Months | 0.109218E+10 | 92971783.14 | 0.999207E+09 | 0.128458E+10 | 0.228231E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342988E+09 | 0.00 | 0.342988E+09 | 49416.32 | 0.228232E+10 |
February | 0.472013E+09 | 0.00 | 0.472013E+09 | 12620949.82 | 0.193797E+10 |
March | 0.633749E+09 | 0.00 | 0.633749E+09 | 0.165980E+09 | 0.158573E+10 |
April | 0.781476E+09 | 3118399.47 | 0.778358E+09 | 0.365132E+09 | 0.110535E+10 |
May | 0.938305E+09 | 39789452.98 | 0.898516E+09 | 0.708244E+09 | 0.686954E+09 |
June | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.115930E+10 | 0.424529E+09 |
July | 0.104691E+10 | 67580432.87 | 0.979331E+09 | 0.128458E+10 | 0.306021E+09 |
August | 0.905869E+09 | 13780824.64 | 0.892088E+09 | 0.104734E+10 | 0.405167E+09 |
September | 0.667148E+09 | 138604.32 | 0.667009E+09 | 0.585534E+09 | 0.657224E+09 |
October | 0.515345E+09 | 0.00 | 0.515345E+09 | 0.209717E+09 | 0.113954E+10 |
November | 0.335128E+09 | 0.00 | 0.335128E+09 | 43885288.27 | 0.148385E+10 |
December | 0.321027E+09 | 0.00 | 0.321027E+09 | 1557352.44 | 0.225224E+10 |
Annual Sum or Average | 0.805214E+10 | 0.217379E+09 | 0.783476E+10 | 0.558394E+10 | 0.142669E+11 |
Minimum of Months | 0.321027E+09 | 0.00 | 0.321027E+09 | 49416.32 | 0.306021E+09 |
Maximum of Months | 0.109218E+10 | 92971671.58 | 0.999206E+09 | 0.128458E+10 | 0.228232E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.342975E+09 | 0.00 | 0.342975E+09 | 49415.71 | 0.228222E+10 |
February | 0.471994E+09 | 0.00 | 0.471994E+09 | 12620541.83 | 0.193789E+10 |
March | 0.633724E+09 | 0.00 | 0.633724E+09 | 0.165974E+09 | 0.158567E+10 |
April | 0.781446E+09 | 3118277.53 | 0.778327E+09 | 0.365118E+09 | 0.110531E+10 |
May | 0.938268E+09 | 39787897.04 | 0.898480E+09 | 0.708216E+09 | 0.686926E+09 |
June | 0.109213E+10 | 92968035.97 | 0.999166E+09 | 0.115926E+10 | 0.424512E+09 |
July | 0.104687E+10 | 67577790.16 | 0.979292E+09 | 0.128453E+10 | 0.306009E+09 |
August | 0.905833E+09 | 13780285.75 | 0.892053E+09 | 0.104730E+10 | 0.405151E+09 |
September | 0.667121E+09 | 138598.90 | 0.666983E+09 | 0.585511E+09 | 0.657198E+09 |
October | 0.515325E+09 | 0.00 | 0.515325E+09 | 0.209709E+09 | 0.113949E+10 |
November | 0.335115E+09 | 0.00 | 0.335115E+09 | 43883639.85 | 0.148379E+10 |
December | 0.321014E+09 | 0.00 | 0.321014E+09 | 1557299.48 | 0.225214E+10 |
Annual Sum or Average | 0.805182E+10 | 0.217371E+09 | 0.783445E+10 | 0.558372E+10 | 0.142663E+11 |
Minimum of Months | 0.321014E+09 | 0.00 | 0.321014E+09 | 49415.71 | 0.306009E+09 |
Maximum of Months | 0.109213E+10 | 92968035.97 | 0.999166E+09 | 0.128453E+10 | 0.228222E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.697404E+09 | 0.224882E+09 | 0.472522E+09 | 0.248005E+09 | 0.230709E+10 |
February | 0.924275E+09 | 0.277352E+09 | 0.646923E+09 | 0.399991E+09 | 0.196337E+10 |
March | 0.146841E+10 | 0.614962E+09 | 0.853451E+09 | 0.109718E+10 | 0.160004E+10 |
April | 0.188084E+10 | 0.831058E+09 | 0.104979E+10 | 0.171651E+10 | 0.112955E+10 |
May | 0.217746E+10 | 0.963207E+09 | 0.121425E+10 | 0.234161E+10 | 0.769994E+09 |
June | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.284617E+10 | 0.475427E+09 |
July | 0.233522E+10 | 0.102816E+10 | 0.130705E+10 | 0.303454E+10 | 0.335282E+09 |
August | 0.210896E+10 | 0.885226E+09 | 0.122373E+10 | 0.268382E+10 | 0.433598E+09 |
September | 0.169841E+10 | 0.753348E+09 | 0.945059E+09 | 0.194130E+10 | 0.694464E+09 |
October | 0.119093E+10 | 0.492599E+09 | 0.698327E+09 | 0.101991E+10 | 0.117419E+10 |
November | 0.653724E+09 | 0.209707E+09 | 0.444017E+09 | 0.363293E+09 | 0.153209E+10 |
December | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122563E+09 | 0.229993E+10 |
Annual Sum or Average | 0.180329E+11 | 0.743296E+10 | 0.105999E+11 | 0.178149E+11 | 0.147150E+11 |
Minimum of Months | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122563E+09 | 0.335282E+09 |
Maximum of Months | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.303454E+10 | 0.230709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.697404E+09 | 0.224882E+09 | 0.472522E+09 | 0.248005E+09 | 0.230709E+10 |
February | 0.924275E+09 | 0.277352E+09 | 0.646923E+09 | 0.399991E+09 | 0.196337E+10 |
March | 0.146841E+10 | 0.614962E+09 | 0.853451E+09 | 0.109718E+10 | 0.160004E+10 |
April | 0.188084E+10 | 0.831058E+09 | 0.104979E+10 | 0.171651E+10 | 0.112955E+10 |
May | 0.217746E+10 | 0.963207E+09 | 0.121425E+10 | 0.234161E+10 | 0.769994E+09 |
June | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.284617E+10 | 0.475427E+09 |
July | 0.233522E+10 | 0.102816E+10 | 0.130705E+10 | 0.303454E+10 | 0.335282E+09 |
August | 0.210896E+10 | 0.885226E+09 | 0.122373E+10 | 0.268382E+10 | 0.433598E+09 |
September | 0.169841E+10 | 0.753348E+09 | 0.945059E+09 | 0.194130E+10 | 0.694464E+09 |
October | 0.119093E+10 | 0.492599E+09 | 0.698327E+09 | 0.101991E+10 | 0.117419E+10 |
November | 0.653724E+09 | 0.209707E+09 | 0.444017E+09 | 0.363293E+09 | 0.153209E+10 |
December | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122563E+09 | 0.229993E+10 |
Annual Sum or Average | 0.180329E+11 | 0.743296E+10 | 0.105999E+11 | 0.178149E+11 | 0.147150E+11 |
Minimum of Months | 0.543824E+09 | 0.112366E+09 | 0.431458E+09 | 0.122563E+09 | 0.335282E+09 |
Maximum of Months | 0.235341E+10 | 0.104009E+10 | 0.131332E+10 | 0.303454E+10 | 0.230709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.697391E+09 | 0.224878E+09 | 0.472513E+09 | 0.248001E+09 | 0.230705E+10 |
February | 0.924258E+09 | 0.277347E+09 | 0.646911E+09 | 0.399984E+09 | 0.196334E+10 |
March | 0.146839E+10 | 0.614951E+09 | 0.853435E+09 | 0.109716E+10 | 0.160002E+10 |
April | 0.188081E+10 | 0.831042E+09 | 0.104977E+10 | 0.171648E+10 | 0.112952E+10 |
May | 0.217742E+10 | 0.963189E+09 | 0.121423E+10 | 0.234157E+10 | 0.769980E+09 |
June | 0.235336E+10 | 0.104007E+10 | 0.131329E+10 | 0.284611E+10 | 0.475418E+09 |
July | 0.233518E+10 | 0.102815E+10 | 0.130703E+10 | 0.303449E+10 | 0.335276E+09 |
August | 0.210892E+10 | 0.885210E+09 | 0.122371E+10 | 0.268377E+10 | 0.433590E+09 |
September | 0.169838E+10 | 0.753334E+09 | 0.945041E+09 | 0.194126E+10 | 0.694451E+09 |
October | 0.119090E+10 | 0.492590E+09 | 0.698315E+09 | 0.101989E+10 | 0.117417E+10 |
November | 0.653712E+09 | 0.209703E+09 | 0.444009E+09 | 0.363287E+09 | 0.153207E+10 |
December | 0.543814E+09 | 0.112364E+09 | 0.431450E+09 | 0.122560E+09 | 0.229989E+10 |
Annual Sum or Average | 0.180325E+11 | 0.743283E+10 | 0.105997E+11 | 0.178146E+11 | 0.147148E+11 |
Minimum of Months | 0.543814E+09 | 0.112364E+09 | 0.431450E+09 | 0.122560E+09 | 0.335276E+09 |
Maximum of Months | 0.235336E+10 | 0.104007E+10 | 0.131329E+10 | 0.303449E+10 | 0.230705E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147486E+10 | 0.860917E+09 | 0.613939E+09 | 0.116456E+10 | 0.189283E+10 |
February | 0.152096E+10 | 0.733392E+09 | 0.787564E+09 | 0.117954E+10 | 0.167625E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900453E+09 | 0.198013E+10 | 0.141345E+10 |
April | 0.164723E+10 | 0.658238E+09 | 0.988992E+09 | 0.165128E+10 | 0.109620E+10 |
May | 0.148952E+10 | 0.432620E+09 | 0.105690E+10 | 0.164307E+10 | 0.746849E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.172920E+10 | 0.466372E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111901E+10 | 0.201624E+10 | 0.332787E+09 |
August | 0.165873E+10 | 0.537802E+09 | 0.112093E+10 | 0.222994E+10 | 0.429375E+09 |
September | 0.186640E+10 | 0.909074E+09 | 0.957322E+09 | 0.231821E+10 | 0.661466E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791269E+09 | 0.196642E+10 | 0.105390E+10 |
November | 0.127900E+10 | 0.722038E+09 | 0.556961E+09 | 0.117769E+10 | 0.131993E+10 |
December | 0.123327E+10 | 0.638274E+09 | 0.594998E+09 | 0.911091E+09 | 0.190153E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835665E+10 | 0.105922E+11 | 0.199674E+11 | 0.129909E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.911091E+09 | 0.332787E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231821E+10 | 0.190153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147485E+10 | 0.860916E+09 | 0.613938E+09 | 0.116456E+10 | 0.189283E+10 |
February | 0.152095E+10 | 0.733391E+09 | 0.787563E+09 | 0.117954E+10 | 0.167625E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900452E+09 | 0.198013E+10 | 0.141345E+10 |
April | 0.164723E+10 | 0.658237E+09 | 0.988991E+09 | 0.165128E+10 | 0.109620E+10 |
May | 0.148952E+10 | 0.432619E+09 | 0.105690E+10 | 0.164307E+10 | 0.746849E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.172920E+10 | 0.466372E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111900E+10 | 0.201623E+10 | 0.332787E+09 |
August | 0.165873E+10 | 0.537801E+09 | 0.112093E+10 | 0.222994E+10 | 0.429375E+09 |
September | 0.186639E+10 | 0.909072E+09 | 0.957322E+09 | 0.231821E+10 | 0.661466E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791268E+09 | 0.196642E+10 | 0.105390E+10 |
November | 0.127900E+10 | 0.722037E+09 | 0.556961E+09 | 0.117769E+10 | 0.131993E+10 |
December | 0.123327E+10 | 0.638273E+09 | 0.594997E+09 | 0.911089E+09 | 0.190153E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835664E+10 | 0.105922E+11 | 0.199673E+11 | 0.129909E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.911089E+09 | 0.332787E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231821E+10 | 0.190153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147486E+10 | 0.860917E+09 | 0.613939E+09 | 0.116456E+10 | 0.189283E+10 |
February | 0.152096E+10 | 0.733392E+09 | 0.787564E+09 | 0.117954E+10 | 0.167625E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900453E+09 | 0.198013E+10 | 0.141345E+10 |
April | 0.164723E+10 | 0.658238E+09 | 0.988992E+09 | 0.165128E+10 | 0.109620E+10 |
May | 0.148952E+10 | 0.432620E+09 | 0.105690E+10 | 0.164307E+10 | 0.746849E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.172920E+10 | 0.466372E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111901E+10 | 0.201624E+10 | 0.332787E+09 |
August | 0.165873E+10 | 0.537802E+09 | 0.112093E+10 | 0.222994E+10 | 0.429375E+09 |
September | 0.186640E+10 | 0.909074E+09 | 0.957322E+09 | 0.231821E+10 | 0.661466E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791269E+09 | 0.196642E+10 | 0.105390E+10 |
November | 0.127900E+10 | 0.722038E+09 | 0.556961E+09 | 0.117769E+10 | 0.131993E+10 |
December | 0.123327E+10 | 0.638274E+09 | 0.594998E+09 | 0.911091E+09 | 0.190153E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835665E+10 | 0.105922E+11 | 0.199674E+11 | 0.129909E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.911091E+09 | 0.332787E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231821E+10 | 0.190153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147485E+10 | 0.860916E+09 | 0.613938E+09 | 0.116456E+10 | 0.189283E+10 |
February | 0.152095E+10 | 0.733391E+09 | 0.787563E+09 | 0.117954E+10 | 0.167625E+10 |
March | 0.205533E+10 | 0.115488E+10 | 0.900452E+09 | 0.198013E+10 | 0.141345E+10 |
April | 0.164723E+10 | 0.658237E+09 | 0.988991E+09 | 0.165128E+10 | 0.109620E+10 |
May | 0.148952E+10 | 0.432619E+09 | 0.105690E+10 | 0.164307E+10 | 0.746849E+09 |
June | 0.140065E+10 | 0.296804E+09 | 0.110384E+10 | 0.172920E+10 | 0.466372E+09 |
July | 0.147749E+10 | 0.358488E+09 | 0.111900E+10 | 0.201623E+10 | 0.332787E+09 |
August | 0.165873E+10 | 0.537801E+09 | 0.112093E+10 | 0.222994E+10 | 0.429375E+09 |
September | 0.186639E+10 | 0.909072E+09 | 0.957322E+09 | 0.231821E+10 | 0.661466E+09 |
October | 0.184539E+10 | 0.105412E+10 | 0.791268E+09 | 0.196642E+10 | 0.105390E+10 |
November | 0.127900E+10 | 0.722037E+09 | 0.556961E+09 | 0.117769E+10 | 0.131993E+10 |
December | 0.123327E+10 | 0.638273E+09 | 0.594997E+09 | 0.911089E+09 | 0.190153E+10 |
Annual Sum or Average | 0.189488E+11 | 0.835664E+10 | 0.105922E+11 | 0.199673E+11 | 0.129909E+11 |
Minimum of Months | 0.123327E+10 | 0.296804E+09 | 0.556961E+09 | 0.911089E+09 | 0.332787E+09 |
Maximum of Months | 0.205533E+10 | 0.115488E+10 | 0.112093E+10 | 0.231821E+10 | 0.190153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147480E+10 | 0.860882E+09 | 0.613914E+09 | 0.116451E+10 | 0.189275E+10 |
February | 0.152089E+10 | 0.733362E+09 | 0.787532E+09 | 0.117949E+10 | 0.167619E+10 |
March | 0.205525E+10 | 0.115483E+10 | 0.900417E+09 | 0.198005E+10 | 0.141339E+10 |
April | 0.164716E+10 | 0.658211E+09 | 0.988952E+09 | 0.165121E+10 | 0.109615E+10 |
May | 0.148946E+10 | 0.432602E+09 | 0.105686E+10 | 0.164300E+10 | 0.746818E+09 |
June | 0.140059E+10 | 0.296792E+09 | 0.110380E+10 | 0.172913E+10 | 0.466353E+09 |
July | 0.147743E+10 | 0.358474E+09 | 0.111896E+10 | 0.201615E+10 | 0.332774E+09 |
August | 0.165866E+10 | 0.537780E+09 | 0.112088E+10 | 0.222985E+10 | 0.429358E+09 |
September | 0.186632E+10 | 0.909037E+09 | 0.957284E+09 | 0.231812E+10 | 0.661440E+09 |
October | 0.184532E+10 | 0.105408E+10 | 0.791237E+09 | 0.196634E+10 | 0.105386E+10 |
November | 0.127895E+10 | 0.722009E+09 | 0.556939E+09 | 0.117764E+10 | 0.131988E+10 |
December | 0.123322E+10 | 0.638249E+09 | 0.594974E+09 | 0.911054E+09 | 0.190145E+10 |
Annual Sum or Average | 0.189481E+11 | 0.835631E+10 | 0.105917E+11 | 0.199666E+11 | 0.129904E+11 |
Minimum of Months | 0.123322E+10 | 0.296792E+09 | 0.556939E+09 | 0.911054E+09 | 0.332774E+09 |
Maximum of Months | 0.205525E+10 | 0.115483E+10 | 0.112088E+10 | 0.231812E+10 | 0.190145E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598360E+09 | 0.140472E+09 | 0.457889E+09 | 0.144930E+09 | 0.250238E+10 |
February | 0.875928E+09 | 0.225120E+09 | 0.650808E+09 | 0.323319E+09 | 0.217479E+10 |
March | 0.151995E+10 | 0.650808E+09 | 0.869145E+09 | 0.112664E+10 | 0.181372E+10 |
April | 0.180095E+10 | 0.738460E+09 | 0.106249E+10 | 0.158524E+10 | 0.134474E+10 |
May | 0.219532E+10 | 0.992142E+09 | 0.120318E+10 | 0.235327E+10 | 0.878001E+09 |
June | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310557E+10 | 0.579585E+09 |
July | 0.236805E+10 | 0.103824E+10 | 0.132982E+10 | 0.304391E+10 | 0.440021E+09 |
August | 0.214177E+10 | 0.910699E+09 | 0.123107E+10 | 0.269749E+10 | 0.565042E+09 |
September | 0.162769E+10 | 0.702930E+09 | 0.924764E+09 | 0.184269E+10 | 0.790480E+09 |
October | 0.109032E+10 | 0.384073E+09 | 0.706247E+09 | 0.880053E+09 | 0.134072E+10 |
November | 0.625285E+09 | 0.180185E+09 | 0.445100E+09 | 0.314032E+09 | 0.175921E+10 |
December | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127293E+09 | 0.264072E+10 |
Annual Sum or Average | 0.179670E+11 | 0.729083E+10 | 0.106762E+11 | 0.175445E+11 | 0.168294E+11 |
Minimum of Months | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127293E+09 | 0.440021E+09 |
Maximum of Months | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310557E+10 | 0.264072E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598360E+09 | 0.140472E+09 | 0.457889E+09 | 0.144930E+09 | 0.250238E+10 |
February | 0.875928E+09 | 0.225120E+09 | 0.650808E+09 | 0.323319E+09 | 0.217479E+10 |
March | 0.151995E+10 | 0.650808E+09 | 0.869145E+09 | 0.112664E+10 | 0.181372E+10 |
April | 0.180095E+10 | 0.738460E+09 | 0.106249E+10 | 0.158524E+10 | 0.134474E+10 |
May | 0.219532E+10 | 0.992142E+09 | 0.120318E+10 | 0.235327E+10 | 0.878001E+09 |
June | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310557E+10 | 0.579585E+09 |
July | 0.236805E+10 | 0.103824E+10 | 0.132982E+10 | 0.304391E+10 | 0.440021E+09 |
August | 0.214177E+10 | 0.910699E+09 | 0.123107E+10 | 0.269749E+10 | 0.565042E+09 |
September | 0.162769E+10 | 0.702930E+09 | 0.924764E+09 | 0.184269E+10 | 0.790480E+09 |
October | 0.109032E+10 | 0.384073E+09 | 0.706247E+09 | 0.880053E+09 | 0.134072E+10 |
November | 0.625285E+09 | 0.180185E+09 | 0.445100E+09 | 0.314032E+09 | 0.175921E+10 |
December | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127293E+09 | 0.264072E+10 |
Annual Sum or Average | 0.179670E+11 | 0.729083E+10 | 0.106762E+11 | 0.175445E+11 | 0.168294E+11 |
Minimum of Months | 0.560136E+09 | 0.122047E+09 | 0.438088E+09 | 0.127293E+09 | 0.440021E+09 |
Maximum of Months | 0.256328E+10 | 0.120566E+10 | 0.135762E+10 | 0.310557E+10 | 0.264072E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.598349E+09 | 0.140469E+09 | 0.457880E+09 | 0.144927E+09 | 0.250233E+10 |
February | 0.875912E+09 | 0.225116E+09 | 0.650796E+09 | 0.323313E+09 | 0.217475E+10 |
March | 0.151993E+10 | 0.650797E+09 | 0.869129E+09 | 0.112662E+10 | 0.181368E+10 |
April | 0.180091E+10 | 0.738447E+09 | 0.106247E+10 | 0.158521E+10 | 0.134471E+10 |
May | 0.219528E+10 | 0.992124E+09 | 0.120315E+10 | 0.235323E+10 | 0.877985E+09 |
June | 0.256323E+10 | 0.120564E+10 | 0.135759E+10 | 0.310551E+10 | 0.579575E+09 |
July | 0.236801E+10 | 0.103822E+10 | 0.132979E+10 | 0.304386E+10 | 0.440013E+09 |
August | 0.214173E+10 | 0.910683E+09 | 0.123104E+10 | 0.269744E+10 | 0.565032E+09 |
September | 0.162766E+10 | 0.702917E+09 | 0.924747E+09 | 0.184266E+10 | 0.790465E+09 |
October | 0.109030E+10 | 0.384066E+09 | 0.706234E+09 | 0.880037E+09 | 0.134070E+10 |
November | 0.625274E+09 | 0.180182E+09 | 0.445092E+09 | 0.314026E+09 | 0.175918E+10 |
December | 0.560125E+09 | 0.122045E+09 | 0.438080E+09 | 0.127291E+09 | 0.264067E+10 |
Annual Sum or Average | 0.179667E+11 | 0.729070E+10 | 0.106760E+11 | 0.175441E+11 | 0.168291E+11 |
Minimum of Months | 0.560125E+09 | 0.122045E+09 | 0.438080E+09 | 0.127291E+09 | 0.440013E+09 |
Maximum of Months | 0.256323E+10 | 0.120564E+10 | 0.135759E+10 | 0.310551E+10 | 0.264067E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171492E+10 | 0.00 | 0.171492E+10 | 14627437.81 | 0.103403E+11 |
February | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.131483E+09 | 0.876803E+10 |
March | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.963786E+09 | 0.714657E+10 |
April | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.201260E+10 | 0.497685E+10 |
May | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.360880E+10 | 0.326593E+10 |
June | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.584242E+10 | 0.202547E+10 |
July | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.649244E+10 | 0.145625E+10 |
August | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.530600E+10 | 0.193383E+10 |
September | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.298871E+10 | 0.307128E+10 |
October | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.119568E+10 | 0.511427E+10 |
November | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.321538E+09 | 0.642174E+10 |
December | 0.160512E+10 | 0.00 | 0.160512E+10 | 21513712.81 | 0.993023E+10 |
Annual Sum or Average | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.288996E+11 | 0.644508E+11 |
Minimum of Months | 0.160512E+10 | 0.00 | 0.160512E+10 | 14627437.81 | 0.145625E+10 |
Maximum of Months | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.649244E+10 | 0.103403E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.799779E+09 | 0.627921E+10 |
February | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.128291E+10 | 0.540514E+10 |
March | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.333277E+10 | 0.448157E+10 |
April | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.515549E+10 | 0.320991E+10 |
May | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.696868E+10 | 0.225223E+10 |
June | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.847419E+10 | 0.139892E+10 |
July | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.904866E+10 | 0.100151E+10 |
August | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.798886E+10 | 0.131136E+10 |
September | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.578802E+10 | 0.201076E+10 |
October | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.308728E+10 | 0.329260E+10 |
November | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.115300E+10 | 0.414381E+10 |
December | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.414001E+09 | 0.622118E+10 |
Annual Sum or Average | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.534936E+11 | 0.410082E+11 |
Minimum of Months | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.414001E+09 | 0.100151E+10 |
Maximum of Months | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.904866E+10 | 0.627921E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.585723E+10 | 0.901962E+10 |
February | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.593230E+10 | 0.802082E+10 |
March | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.986097E+10 | 0.682093E+10 |
April | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.824702E+10 | 0.525261E+10 |
May | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.815700E+10 | 0.365721E+10 |
June | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.861618E+10 | 0.225281E+10 |
July | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.100705E+11 | 0.160918E+10 |
August | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.111204E+11 | 0.209733E+10 |
September | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.115188E+11 | 0.323547E+10 |
October | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.977905E+10 | 0.510051E+10 |
November | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.590710E+10 | 0.624755E+10 |
December | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.461665E+10 | 0.891589E+10 |
Annual Sum or Average | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.996832E+11 | 0.622299E+11 |
Minimum of Months | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.461665E+10 | 0.160918E+10 |
Maximum of Months | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.115188E+11 | 0.901962E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.479416E+09 | 0.665471E+10 |
February | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.108533E+10 | 0.570217E+10 |
March | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.351902E+10 | 0.471289E+10 |
April | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.491481E+10 | 0.347273E+10 |
May | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.707798E+10 | 0.246947E+10 |
June | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.933791E+10 | 0.159552E+10 |
July | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.919992E+10 | 0.117843E+10 |
August | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.818738E+10 | 0.148418E+10 |
September | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.555974E+10 | 0.218381E+10 |
October | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.276031E+10 | 0.349798E+10 |
November | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.104995E+10 | 0.433254E+10 |
December | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.454693E+09 | 0.648995E+10 |
Annual Sum or Average | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.536265E+11 | 0.437744E+11 |
Minimum of Months | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.454693E+09 | 0.117843E+10 |
Maximum of Months | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.933791E+10 | 0.665471E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171492E+10 | 0.00 | 0.171492E+10 | 33652015.24 | 0.992887E+10 |
February | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.174191E+09 | 0.838675E+10 |
March | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.105348E+10 | 0.668064E+10 |
April | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.214778E+10 | 0.461988E+10 |
May | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.367053E+10 | 0.312134E+10 |
June | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.581570E+10 | 0.199708E+10 |
July | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.643025E+10 | 0.146231E+10 |
August | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.527204E+10 | 0.191415E+10 |
September | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.302462E+10 | 0.292356E+10 |
October | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.133708E+10 | 0.462922E+10 |
November | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.410474E+09 | 0.580144E+10 |
December | 0.160512E+10 | 0.00 | 0.160512E+10 | 35981068.18 | 0.940041E+10 |
Annual Sum or Average | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.294058E+11 | 0.608656E+11 |
Minimum of Months | 0.160512E+10 | 0.00 | 0.160512E+10 | 33652015.24 | 0.146231E+10 |
Maximum of Months | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.643025E+10 | 0.992887E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.835702E+09 | 0.603481E+10 |
February | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.134187E+10 | 0.517379E+10 |
March | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.343564E+10 | 0.416751E+10 |
April | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.525915E+10 | 0.299855E+10 |
May | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.699981E+10 | 0.216828E+10 |
June | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.846152E+10 | 0.138207E+10 |
July | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.902026E+10 | 0.100543E+10 |
August | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.797503E+10 | 0.129941E+10 |
September | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.581520E+10 | 0.192900E+10 |
October | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.320281E+10 | 0.299613E+10 |
November | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.124613E+10 | 0.373223E+10 |
December | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.441918E+09 | 0.590524E+10 |
Annual Sum or Average | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.540350E+11 | 0.387925E+11 |
Minimum of Months | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.441918E+09 | 0.100543E+10 |
Maximum of Months | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.902026E+10 | 0.603481E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.595005E+10 | 0.858824E+10 |
February | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.603994E+10 | 0.763583E+10 |
March | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.999277E+10 | 0.636220E+10 |
April | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.835482E+10 | 0.491466E+10 |
May | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.817857E+10 | 0.350691E+10 |
June | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.857461E+10 | 0.221596E+10 |
July | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.100021E+11 | 0.161202E+10 |
August | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.110709E+11 | 0.207697E+10 |
September | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.115243E+11 | 0.311088E+10 |
October | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.991060E+10 | 0.468063E+10 |
November | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.605248E+10 | 0.566768E+10 |
December | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.472190E+10 | 0.840052E+10 |
Annual Sum or Average | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.100373E+12 | 0.587725E+11 |
Minimum of Months | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.472190E+10 | 0.161202E+10 |
Maximum of Months | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.115243E+11 | 0.858824E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.503026E+09 | 0.638585E+10 |
February | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.112094E+10 | 0.547515E+10 |
March | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.357628E+10 | 0.443449E+10 |
April | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.497865E+10 | 0.326839E+10 |
May | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.708406E+10 | 0.237815E+10 |
June | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.929915E+10 | 0.157018E+10 |
July | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.914962E+10 | 0.117501E+10 |
August | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.815224E+10 | 0.146918E+10 |
September | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.556384E+10 | 0.210234E+10 |
October | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.283537E+10 | 0.322919E+10 |
November | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.111028E+10 | 0.397764E+10 |
December | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.478120E+09 | 0.618088E+10 |
Annual Sum or Average | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.538516E+11 | 0.416465E+11 |
Minimum of Months | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.478120E+09 | 0.117501E+10 |
Maximum of Months | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.929915E+10 | 0.638585E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.09 | 4260.56 | 640.28 | 0.00 | 640.28 | 0.00 | 0.00 |
February | 26.08 | 4005.36 | 975.55 | 0.00 | 975.55 | 0.00 | 0.00 |
March | 309.85 | 2960.20 | 1183.06 | 0.00 | 1183.06 | 0.00 | 0.00 |
April | 704.34 | 2132.22 | 1507.47 | 6.02 | 1501.45 | 0.00 | 0.00 |
May | 1322.13 | 1282.39 | 1751.60 | 74.28 | 1677.32 | 0.00 | 0.00 |
June | 2236.30 | 818.92 | 2106.81 | 179.34 | 1927.47 | 0.00 | 0.00 |
July | 2398.01 | 571.27 | 1954.34 | 126.16 | 1828.19 | 0.00 | 0.00 |
August | 1955.14 | 756.35 | 1691.05 | 25.73 | 1665.33 | 0.00 | 0.00 |
September | 1129.49 | 1267.78 | 1286.93 | 0.27 | 1286.66 | 0.00 | 0.00 |
October | 391.49 | 2127.25 | 962.03 | 0.00 | 962.03 | 0.00 | 0.00 |
November | 84.65 | 2862.34 | 646.46 | 0.00 | 646.46 | 0.00 | 0.00 |
December | 2.91 | 4204.41 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Annual Sum or Average | 885.32 | 2261.98 | 1276.65 | 34.47 | 1242.18 | 0.00 | 0.00 |
Minimum of Months | 0.09 | 571.27 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Maximum of Months | 2398.01 | 4260.56 | 2106.81 | 179.34 | 1927.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.78 | 2584.09 | 781.14 | 251.88 | 529.26 | 0.00 | 0.00 |
February | 496.02 | 2434.72 | 1146.17 | 343.94 | 802.23 | 0.00 | 0.00 |
March | 1228.91 | 1792.15 | 1644.72 | 688.80 | 955.92 | 0.00 | 0.00 |
April | 1986.69 | 1307.34 | 2176.89 | 961.87 | 1215.02 | 0.00 | 0.00 |
May | 2622.76 | 862.44 | 2438.89 | 1078.85 | 1360.04 | 0.00 | 0.00 |
June | 3294.15 | 550.26 | 2723.83 | 1203.80 | 1520.03 | 0.00 | 0.00 |
July | 3398.89 | 375.54 | 2615.60 | 1151.61 | 1463.99 | 0.00 | 0.00 |
August | 3006.06 | 485.66 | 2362.17 | 991.51 | 1370.66 | 0.00 | 0.00 |
September | 2246.86 | 803.77 | 1965.74 | 871.93 | 1093.81 | 0.00 | 0.00 |
October | 1142.37 | 1315.17 | 1333.92 | 551.74 | 782.17 | 0.00 | 0.00 |
November | 420.48 | 1773.25 | 756.62 | 242.72 | 513.91 | 0.00 | 0.00 |
December | 137.28 | 2576.08 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Annual Sum or Average | 1694.71 | 1399.82 | 1715.44 | 707.09 | 1008.36 | 0.00 | 0.00 |
Minimum of Months | 137.28 | 375.54 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Maximum of Months | 3398.89 | 2584.09 | 2723.83 | 1203.80 | 1520.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2173.97 | 3533.47 | 2753.22 | 1607.13 | 1146.08 | 0.00 | 0.00 |
February | 2437.85 | 3464.45 | 3143.48 | 1515.76 | 1627.72 | 0.00 | 0.00 |
March | 3696.45 | 2638.59 | 3836.83 | 2155.89 | 1680.94 | 0.00 | 0.00 |
April | 3185.31 | 2114.56 | 3177.50 | 1269.74 | 1907.76 | 0.00 | 0.00 |
May | 3067.23 | 1394.20 | 2780.59 | 807.60 | 1972.99 | 0.00 | 0.00 |
June | 3335.63 | 899.63 | 2701.84 | 572.53 | 2129.31 | 0.00 | 0.00 |
July | 3763.85 | 621.24 | 2758.14 | 669.22 | 2088.93 | 0.00 | 0.00 |
August | 4162.79 | 801.54 | 3096.47 | 1003.95 | 2092.52 | 0.00 | 0.00 |
September | 4471.82 | 1275.97 | 3600.27 | 1753.60 | 1846.67 | 0.00 | 0.00 |
October | 3670.85 | 1967.39 | 3444.93 | 1967.81 | 1477.12 | 0.00 | 0.00 |
November | 2271.76 | 2546.14 | 2467.18 | 1392.81 | 1074.38 | 0.00 | 0.00 |
December | 1700.80 | 3549.71 | 2302.24 | 1191.51 | 1110.72 | 0.00 | 0.00 |
Annual Sum or Average | 3165.78 | 2059.68 | 3004.29 | 1324.93 | 1679.36 | 0.00 | 0.00 |
Minimum of Months | 1700.80 | 621.24 | 2302.24 | 572.53 | 1074.38 | 0.00 | 0.00 |
Maximum of Months | 4471.82 | 3549.71 | 3836.83 | 2155.89 | 2129.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 162.33 | 2802.82 | 670.20 | 157.34 | 512.87 | 0.00 | 0.00 |
February | 400.94 | 2696.89 | 1086.21 | 279.16 | 807.05 | 0.00 | 0.00 |
March | 1261.91 | 2031.48 | 1702.45 | 728.95 | 973.50 | 0.00 | 0.00 |
April | 1834.76 | 1556.40 | 2084.41 | 854.69 | 1229.72 | 0.00 | 0.00 |
May | 2635.81 | 983.42 | 2458.90 | 1111.26 | 1347.64 | 0.00 | 0.00 |
June | 3594.39 | 670.81 | 2966.74 | 1395.43 | 1571.31 | 0.00 | 0.00 |
July | 3409.38 | 492.85 | 2652.38 | 1162.89 | 1489.48 | 0.00 | 0.00 |
August | 3021.37 | 632.88 | 2398.92 | 1020.04 | 1378.87 | 0.00 | 0.00 |
September | 2132.73 | 914.90 | 1883.89 | 813.57 | 1070.32 | 0.00 | 0.00 |
October | 985.72 | 1501.69 | 1221.23 | 430.19 | 791.04 | 0.00 | 0.00 |
November | 363.46 | 2036.11 | 723.71 | 208.55 | 515.16 | 0.00 | 0.00 |
December | 142.58 | 2957.77 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Annual Sum or Average | 1668.98 | 1600.96 | 1709.18 | 693.57 | 1015.61 | 0.00 | 0.00 |
Minimum of Months | 142.58 | 492.85 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Maximum of Months | 3594.39 | 2957.77 | 2966.74 | 1395.43 | 1571.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.46 | 3860.64 | 640.28 | 0.00 | 640.28 | 0.00 | 0.00 |
February | 54.35 | 3624.35 | 975.54 | 0.00 | 975.54 | 0.00 | 0.00 |
March | 359.84 | 2668.22 | 1183.06 | 0.00 | 1183.06 | 0.00 | 0.00 |
April | 776.47 | 1920.08 | 1507.46 | 6.02 | 1501.45 | 0.00 | 0.00 |
May | 1347.37 | 1219.36 | 1751.60 | 74.28 | 1677.32 | 0.00 | 0.00 |
June | 2254.02 | 781.43 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
July | 2424.00 | 543.70 | 1954.34 | 126.16 | 1828.18 | 0.00 | 0.00 |
August | 1981.03 | 722.01 | 1691.04 | 25.73 | 1665.32 | 0.00 | 0.00 |
September | 1153.05 | 1184.91 | 1286.92 | 0.27 | 1286.65 | 0.00 | 0.00 |
October | 446.42 | 1909.45 | 962.03 | 0.00 | 962.03 | 0.00 | 0.00 |
November | 124.05 | 2477.52 | 646.46 | 0.00 | 646.46 | 0.00 | 0.00 |
December | 8.03 | 3707.52 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Annual Sum or Average | 916.40 | 2043.72 | 1276.64 | 34.46 | 1242.18 | 0.00 | 0.00 |
Minimum of Months | 5.46 | 543.70 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Maximum of Months | 2424.00 | 3860.64 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.60 | 2344.39 | 781.13 | 251.88 | 529.25 | 0.00 | 0.00 |
February | 530.30 | 2234.27 | 1146.16 | 343.94 | 802.23 | 0.00 | 0.00 |
March | 1244.31 | 1673.23 | 1644.71 | 688.79 | 955.92 | 0.00 | 0.00 |
April | 1989.00 | 1238.39 | 2176.88 | 961.86 | 1215.02 | 0.00 | 0.00 |
May | 2601.81 | 840.88 | 2438.88 | 1078.85 | 1360.04 | 0.00 | 0.00 |
June | 3269.36 | 539.71 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
July | 3378.38 | 373.92 | 2615.59 | 1151.61 | 1463.98 | 0.00 | 0.00 |
August | 2982.70 | 489.60 | 2362.16 | 991.51 | 1370.65 | 0.00 | 0.00 |
September | 2233.03 | 775.76 | 1965.73 | 871.92 | 1093.81 | 0.00 | 0.00 |
October | 1152.66 | 1229.32 | 1333.91 | 551.74 | 782.17 | 0.00 | 0.00 |
November | 444.83 | 1598.69 | 756.62 | 242.71 | 513.90 | 0.00 | 0.00 |
December | 154.57 | 2322.72 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Annual Sum or Average | 1696.27 | 1300.36 | 1715.44 | 707.09 | 1008.35 | 0.00 | 0.00 |
Minimum of Months | 154.57 | 373.92 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Maximum of Months | 3378.38 | 2344.39 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2186.84 | 3367.54 | 2753.21 | 1607.13 | 1146.08 | 0.00 | 0.00 |
February | 2452.17 | 3315.49 | 3143.47 | 1515.75 | 1627.72 | 0.00 | 0.00 |
March | 3681.66 | 2546.64 | 3836.82 | 2155.88 | 1680.93 | 0.00 | 0.00 |
April | 3181.72 | 2026.47 | 3177.49 | 1269.73 | 1907.75 | 0.00 | 0.00 |
May | 3045.48 | 1365.45 | 2780.58 | 807.60 | 1972.99 | 0.00 | 0.00 |
June | 3324.14 | 869.14 | 2701.83 | 572.53 | 2129.30 | 0.00 | 0.00 |
July | 3759.89 | 600.80 | 2758.13 | 669.21 | 2088.92 | 0.00 | 0.00 |
August | 4151.89 | 783.05 | 3096.46 | 1003.95 | 2092.51 | 0.00 | 0.00 |
September | 4443.99 | 1248.25 | 3600.26 | 1753.59 | 1846.66 | 0.00 | 0.00 |
October | 3651.08 | 1904.31 | 3444.91 | 1967.80 | 1477.11 | 0.00 | 0.00 |
November | 2278.97 | 2410.32 | 2467.18 | 1392.80 | 1074.37 | 0.00 | 0.00 |
December | 1723.66 | 3328.81 | 2302.23 | 1191.51 | 1110.72 | 0.00 | 0.00 |
Annual Sum or Average | 3160.94 | 1973.30 | 3004.28 | 1324.92 | 1679.36 | 0.00 | 0.00 |
Minimum of Months | 1723.66 | 600.80 | 2302.23 | 572.53 | 1074.37 | 0.00 | 0.00 |
Maximum of Months | 4443.99 | 3367.54 | 3836.82 | 2155.88 | 2129.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.99 | 2484.58 | 670.20 | 157.34 | 512.86 | 0.00 | 0.00 |
February | 448.63 | 2357.05 | 1086.21 | 279.16 | 807.05 | 0.00 | 0.00 |
March | 1313.85 | 1759.59 | 1702.44 | 728.94 | 973.49 | 0.00 | 0.00 |
April | 1896.15 | 1339.79 | 2084.41 | 854.69 | 1229.72 | 0.00 | 0.00 |
May | 2642.61 | 921.99 | 2458.89 | 1111.26 | 1347.63 | 0.00 | 0.00 |
June | 3602.59 | 615.56 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
July | 3434.86 | 439.97 | 2652.36 | 1162.89 | 1489.48 | 0.00 | 0.00 |
August | 3056.82 | 554.13 | 2398.91 | 1020.04 | 1378.87 | 0.00 | 0.00 |
September | 2144.96 | 842.52 | 1883.89 | 813.57 | 1070.32 | 0.00 | 0.00 |
October | 1030.58 | 1305.99 | 1221.23 | 430.19 | 791.04 | 0.00 | 0.00 |
November | 405.07 | 1671.50 | 723.70 | 208.55 | 515.16 | 0.00 | 0.00 |
December | 169.76 | 2423.07 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Annual Sum or Average | 1700.48 | 1388.08 | 1709.18 | 693.57 | 1015.61 | 0.00 | 0.00 |
Minimum of Months | 169.76 | 439.97 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Maximum of Months | 3602.59 | 2484.58 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.56 | 3707.02 | 640.28 | 0.00 | 640.28 | 0.00 | 0.00 |
February | 72.00 | 3466.74 | 975.54 | 0.00 | 975.54 | 0.00 | 0.00 |
March | 393.33 | 2494.27 | 1183.06 | 0.00 | 1183.06 | 0.00 | 0.00 |
April | 828.62 | 1782.36 | 1507.46 | 6.02 | 1501.45 | 0.00 | 0.00 |
May | 1370.42 | 1165.37 | 1751.60 | 74.28 | 1677.32 | 0.00 | 0.00 |
June | 2243.71 | 770.48 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
July | 2400.78 | 545.96 | 1954.34 | 126.16 | 1828.18 | 0.00 | 0.00 |
August | 1968.35 | 714.66 | 1691.04 | 25.73 | 1665.32 | 0.00 | 0.00 |
September | 1166.90 | 1127.92 | 1286.92 | 0.27 | 1286.65 | 0.00 | 0.00 |
October | 499.21 | 1728.35 | 962.03 | 0.00 | 962.03 | 0.00 | 0.00 |
November | 158.36 | 2238.21 | 646.46 | 0.00 | 646.46 | 0.00 | 0.00 |
December | 13.43 | 3509.71 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Annual Sum or Average | 932.45 | 1930.04 | 1276.64 | 34.46 | 1242.18 | 0.00 | 0.00 |
Minimum of Months | 12.56 | 545.96 | 599.28 | 0.00 | 599.28 | 0.00 | 0.00 |
Maximum of Months | 2400.78 | 3707.02 | 2106.80 | 179.34 | 1927.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 312.02 | 2253.14 | 781.13 | 251.88 | 529.25 | 0.00 | 0.00 |
February | 554.68 | 2138.63 | 1146.16 | 343.94 | 802.23 | 0.00 | 0.00 |
March | 1282.72 | 1555.97 | 1644.71 | 688.79 | 955.92 | 0.00 | 0.00 |
April | 2028.99 | 1156.85 | 2176.88 | 961.86 | 1215.02 | 0.00 | 0.00 |
May | 2613.43 | 809.54 | 2438.88 | 1078.85 | 1360.04 | 0.00 | 0.00 |
June | 3264.47 | 533.21 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
July | 3367.78 | 375.39 | 2615.59 | 1151.61 | 1463.98 | 0.00 | 0.00 |
August | 2977.54 | 485.14 | 2362.16 | 991.51 | 1370.65 | 0.00 | 0.00 |
September | 2243.52 | 744.21 | 1965.73 | 871.92 | 1093.81 | 0.00 | 0.00 |
October | 1195.79 | 1118.63 | 1333.91 | 551.74 | 782.17 | 0.00 | 0.00 |
November | 480.76 | 1439.90 | 756.62 | 242.71 | 513.90 | 0.00 | 0.00 |
December | 164.99 | 2204.76 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Annual Sum or Average | 1713.44 | 1230.10 | 1715.44 | 707.09 | 1008.35 | 0.00 | 0.00 |
Minimum of Months | 164.99 | 375.39 | 609.12 | 125.86 | 483.26 | 0.00 | 0.00 |
Maximum of Months | 3367.78 | 2253.14 | 2723.82 | 1203.80 | 1520.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2221.49 | 3206.48 | 2753.21 | 1607.13 | 1146.08 | 0.00 | 0.00 |
February | 2496.67 | 3156.34 | 3143.47 | 1515.75 | 1627.72 | 0.00 | 0.00 |
March | 3730.87 | 2375.38 | 3836.82 | 2155.88 | 1680.93 | 0.00 | 0.00 |
April | 3223.31 | 1896.09 | 3177.49 | 1269.73 | 1907.75 | 0.00 | 0.00 |
May | 3053.53 | 1309.33 | 2780.58 | 807.60 | 1972.99 | 0.00 | 0.00 |
June | 3308.10 | 854.92 | 2701.83 | 572.53 | 2129.30 | 0.00 | 0.00 |
July | 3734.34 | 601.86 | 2758.13 | 669.21 | 2088.92 | 0.00 | 0.00 |
August | 4133.40 | 775.45 | 3096.46 | 1003.95 | 2092.51 | 0.00 | 0.00 |
September | 4446.09 | 1200.19 | 3600.26 | 1753.59 | 1846.66 | 0.00 | 0.00 |
October | 3700.19 | 1747.55 | 3444.91 | 1967.80 | 1477.11 | 0.00 | 0.00 |
November | 2335.06 | 2186.60 | 2467.18 | 1392.80 | 1074.37 | 0.00 | 0.00 |
December | 1762.96 | 3136.39 | 2302.23 | 1191.51 | 1110.72 | 0.00 | 0.00 |
Annual Sum or Average | 3182.81 | 1863.66 | 3004.28 | 1324.92 | 1679.36 | 0.00 | 0.00 |
Minimum of Months | 1762.96 | 601.86 | 2302.23 | 572.53 | 1074.37 | 0.00 | 0.00 |
Maximum of Months | 4446.09 | 3206.48 | 3836.82 | 2155.88 | 2129.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 187.81 | 2384.20 | 670.20 | 157.34 | 512.86 | 0.00 | 0.00 |
February | 463.35 | 2263.21 | 1086.21 | 279.16 | 807.05 | 0.00 | 0.00 |
March | 1335.23 | 1655.65 | 1702.44 | 728.94 | 973.49 | 0.00 | 0.00 |
April | 1920.78 | 1260.95 | 2084.41 | 854.69 | 1229.72 | 0.00 | 0.00 |
May | 2644.89 | 887.90 | 2458.89 | 1111.26 | 1347.63 | 0.00 | 0.00 |
June | 3587.63 | 605.78 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
July | 3416.08 | 438.70 | 2652.36 | 1162.89 | 1489.48 | 0.00 | 0.00 |
August | 3043.70 | 548.53 | 2398.91 | 1020.04 | 1378.87 | 0.00 | 0.00 |
September | 2146.54 | 811.09 | 1883.89 | 813.57 | 1070.32 | 0.00 | 0.00 |
October | 1058.61 | 1205.64 | 1221.23 | 430.19 | 791.04 | 0.00 | 0.00 |
November | 428.35 | 1534.58 | 723.70 | 208.55 | 515.16 | 0.00 | 0.00 |
December | 178.51 | 2307.68 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Annual Sum or Average | 1707.62 | 1320.60 | 1709.18 | 693.57 | 1015.61 | 0.00 | 0.00 |
Minimum of Months | 178.51 | 438.70 | 627.39 | 136.70 | 490.69 | 0.00 | 0.00 |
Maximum of Months | 3587.63 | 2384.20 | 2966.72 | 1395.42 | 1571.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 247083.74 | 0.114115E+11 | 0.171493E+10 | 0.00 | 0.171493E+10 | 0.00 | 0.00 |
February | 63104542.50 | 0.968977E+10 | 0.236005E+10 | 0.00 | 0.236005E+10 | 0.00 | 0.00 |
March | 0.829896E+09 | 0.792859E+10 | 0.316872E+10 | 0.00 | 0.316872E+10 | 0.00 | 0.00 |
April | 0.182565E+10 | 0.552671E+10 | 0.390735E+10 | 15591882.90 | 0.389176E+10 | 0.00 | 0.00 |
May | 0.354119E+10 | 0.343474E+10 | 0.469149E+10 | 0.198946E+09 | 0.449254E+10 | 0.00 | 0.00 |
June | 0.579648E+10 | 0.212263E+10 | 0.546085E+10 | 0.464855E+09 | 0.499599E+10 | 0.00 | 0.00 |
July | 0.642284E+10 | 0.153009E+10 | 0.523452E+10 | 0.337900E+09 | 0.489662E+10 | 0.00 | 0.00 |
August | 0.523665E+10 | 0.202582E+10 | 0.452931E+10 | 68903617.40 | 0.446041E+10 | 0.00 | 0.00 |
September | 0.292765E+10 | 0.328610E+10 | 0.333571E+10 | 693016.49 | 0.333502E+10 | 0.00 | 0.00 |
October | 0.104858E+10 | 0.569764E+10 | 0.257671E+10 | 0.00 | 0.257671E+10 | 0.00 | 0.00 |
November | 0.219425E+09 | 0.741919E+10 | 0.167563E+10 | 0.00 | 0.167563E+10 | 0.00 | 0.00 |
December | 7786728.87 | 0.112611E+11 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.279195E+11 | 0.713338E+11 | 0.402604E+11 | 0.108689E+10 | 0.391735E+11 | 0.00 | 0.00 |
Minimum of Months | 247083.74 | 0.153009E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.642284E+10 | 0.114115E+11 | 0.546085E+10 | 0.464855E+09 | 0.499599E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.744011E+09 | 0.692122E+10 | 0.209220E+10 | 0.674642E+09 | 0.141756E+10 | 0.00 | 0.00 |
February | 0.119997E+10 | 0.589008E+10 | 0.277281E+10 | 0.832051E+09 | 0.194076E+10 | 0.00 | 0.00 |
March | 0.329151E+10 | 0.480010E+10 | 0.440521E+10 | 0.184488E+10 | 0.256034E+10 | 0.00 | 0.00 |
April | 0.514950E+10 | 0.338862E+10 | 0.564249E+10 | 0.249316E+10 | 0.314934E+10 | 0.00 | 0.00 |
May | 0.702480E+10 | 0.230997E+10 | 0.653234E+10 | 0.288960E+10 | 0.364273E+10 | 0.00 | 0.00 |
June | 0.853845E+10 | 0.142627E+10 | 0.706018E+10 | 0.312025E+10 | 0.393993E+10 | 0.00 | 0.00 |
July | 0.910357E+10 | 0.100584E+10 | 0.700561E+10 | 0.308447E+10 | 0.392114E+10 | 0.00 | 0.00 |
August | 0.805142E+10 | 0.130079E+10 | 0.632684E+10 | 0.265566E+10 | 0.367118E+10 | 0.00 | 0.00 |
September | 0.582386E+10 | 0.208338E+10 | 0.509519E+10 | 0.226003E+10 | 0.283516E+10 | 0.00 | 0.00 |
October | 0.305972E+10 | 0.352256E+10 | 0.357276E+10 | 0.147779E+10 | 0.209497E+10 | 0.00 | 0.00 |
November | 0.108987E+10 | 0.459626E+10 | 0.196116E+10 | 0.629118E+09 | 0.133204E+10 | 0.00 | 0.00 |
December | 0.367686E+09 | 0.689976E+10 | 0.163146E+10 | 0.337095E+09 | 0.129437E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534444E+11 | 0.441448E+11 | 0.540982E+11 | 0.222987E+11 | 0.317995E+11 | 0.00 | 0.00 |
Minimum of Months | 0.367686E+09 | 0.100584E+10 | 0.163146E+10 | 0.337095E+09 | 0.129437E+10 | 0.00 | 0.00 |
Maximum of Months | 0.910357E+10 | 0.692122E+10 | 0.706018E+10 | 0.312025E+10 | 0.393993E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.582275E+10 | 0.946405E+10 | 0.737422E+10 | 0.430455E+10 | 0.306967E+10 | 0.00 | 0.00 |
February | 0.589765E+10 | 0.838120E+10 | 0.760471E+10 | 0.366693E+10 | 0.393779E+10 | 0.00 | 0.00 |
March | 0.990057E+10 | 0.706719E+10 | 0.102766E+11 | 0.577434E+10 | 0.450223E+10 | 0.00 | 0.00 |
April | 0.825633E+10 | 0.548093E+10 | 0.823608E+10 | 0.329116E+10 | 0.494492E+10 | 0.00 | 0.00 |
May | 0.821527E+10 | 0.373421E+10 | 0.744754E+10 | 0.216308E+10 | 0.528446E+10 | 0.00 | 0.00 |
June | 0.864595E+10 | 0.233184E+10 | 0.700317E+10 | 0.148401E+10 | 0.551917E+10 | 0.00 | 0.00 |
July | 0.100811E+11 | 0.166392E+10 | 0.738741E+10 | 0.179243E+10 | 0.559498E+10 | 0.00 | 0.00 |
August | 0.111496E+11 | 0.214686E+10 | 0.829358E+10 | 0.268899E+10 | 0.560459E+10 | 0.00 | 0.00 |
September | 0.115909E+11 | 0.330731E+10 | 0.933190E+10 | 0.454533E+10 | 0.478657E+10 | 0.00 | 0.00 |
October | 0.983201E+10 | 0.526945E+10 | 0.922689E+10 | 0.527058E+10 | 0.395631E+10 | 0.00 | 0.00 |
November | 0.588840E+10 | 0.659960E+10 | 0.639494E+10 | 0.361016E+10 | 0.278478E+10 | 0.00 | 0.00 |
December | 0.455541E+10 | 0.950755E+10 | 0.616631E+10 | 0.319134E+10 | 0.297496E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.998360E+11 | 0.649541E+11 | 0.947433E+11 | 0.417829E+11 | 0.529604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.455541E+10 | 0.166392E+10 | 0.616631E+10 | 0.148401E+10 | 0.278478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115909E+11 | 0.950755E+10 | 0.102766E+11 | 0.577434E+10 | 0.560459E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434786E+09 | 0.750708E+10 | 0.179507E+10 | 0.421412E+09 | 0.137366E+10 | 0.00 | 0.00 |
February | 0.969951E+09 | 0.652432E+10 | 0.262777E+10 | 0.675356E+09 | 0.195241E+10 | 0.00 | 0.00 |
March | 0.337991E+10 | 0.544112E+10 | 0.455983E+10 | 0.195241E+10 | 0.260742E+10 | 0.00 | 0.00 |
April | 0.475570E+10 | 0.403419E+10 | 0.540280E+10 | 0.221537E+10 | 0.318744E+10 | 0.00 | 0.00 |
May | 0.705977E+10 | 0.263399E+10 | 0.658592E+10 | 0.297641E+10 | 0.360951E+10 | 0.00 | 0.00 |
June | 0.931666E+10 | 0.173874E+10 | 0.768978E+10 | 0.361696E+10 | 0.407283E+10 | 0.00 | 0.00 |
July | 0.913168E+10 | 0.132006E+10 | 0.710412E+10 | 0.311469E+10 | 0.398943E+10 | 0.00 | 0.00 |
August | 0.809243E+10 | 0.169512E+10 | 0.642526E+10 | 0.273208E+10 | 0.369318E+10 | 0.00 | 0.00 |
September | 0.552804E+10 | 0.237142E+10 | 0.488305E+10 | 0.210878E+10 | 0.277427E+10 | 0.00 | 0.00 |
October | 0.264014E+10 | 0.402214E+10 | 0.327094E+10 | 0.115221E+10 | 0.211873E+10 | 0.00 | 0.00 |
November | 0.942091E+09 | 0.527760E+10 | 0.187584E+10 | 0.540552E+09 | 0.133529E+10 | 0.00 | 0.00 |
December | 0.381878E+09 | 0.792210E+10 | 0.168040E+10 | 0.366140E+09 | 0.131426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526330E+11 | 0.504879E+11 | 0.539008E+11 | 0.218724E+11 | 0.320284E+11 | 0.00 | 0.00 |
Minimum of Months | 0.381878E+09 | 0.132006E+10 | 0.168040E+10 | 0.366140E+09 | 0.131426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.931666E+10 | 0.792210E+10 | 0.768978E+10 | 0.361696E+10 | 0.407283E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14627437.81 | 0.103403E+11 | 0.171492E+10 | 0.00 | 0.171492E+10 | 0.00 | 0.00 |
February | 0.131483E+09 | 0.876803E+10 | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.00 | 0.00 |
March | 0.963786E+09 | 0.714657E+10 | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.00 | 0.00 |
April | 0.201260E+10 | 0.497685E+10 | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.00 | 0.00 |
May | 0.360880E+10 | 0.326593E+10 | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.00 | 0.00 |
June | 0.584242E+10 | 0.202547E+10 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
July | 0.649244E+10 | 0.145625E+10 | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.00 | 0.00 |
August | 0.530600E+10 | 0.193383E+10 | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.00 | 0.00 |
September | 0.298871E+10 | 0.307128E+10 | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.00 | 0.00 |
October | 0.119568E+10 | 0.511427E+10 | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.00 | 0.00 |
November | 0.321538E+09 | 0.642174E+10 | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.00 | 0.00 |
December | 21513712.81 | 0.993023E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.288996E+11 | 0.644508E+11 | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.00 | 0.00 |
Minimum of Months | 14627437.81 | 0.145625E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649244E+10 | 0.103403E+11 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.799779E+09 | 0.627921E+10 | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.00 | 0.00 |
February | 0.128291E+10 | 0.540514E+10 | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.00 | 0.00 |
March | 0.333277E+10 | 0.448157E+10 | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.00 | 0.00 |
April | 0.515549E+10 | 0.320991E+10 | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.00 | 0.00 |
May | 0.696868E+10 | 0.225223E+10 | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.00 | 0.00 |
June | 0.847419E+10 | 0.139892E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
July | 0.904866E+10 | 0.100151E+10 | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.00 | 0.00 |
August | 0.798886E+10 | 0.131136E+10 | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.00 | 0.00 |
September | 0.578802E+10 | 0.201076E+10 | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.00 | 0.00 |
October | 0.308728E+10 | 0.329260E+10 | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.00 | 0.00 |
November | 0.115300E+10 | 0.414381E+10 | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.00 | 0.00 |
December | 0.414001E+09 | 0.622118E+10 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534936E+11 | 0.410082E+11 | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.414001E+09 | 0.100151E+10 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.904866E+10 | 0.627921E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.585723E+10 | 0.901962E+10 | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.00 | 0.00 |
February | 0.593230E+10 | 0.802082E+10 | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.00 | 0.00 |
March | 0.986097E+10 | 0.682093E+10 | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.00 | 0.00 |
April | 0.824702E+10 | 0.525261E+10 | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.00 | 0.00 |
May | 0.815700E+10 | 0.365721E+10 | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.00 | 0.00 |
June | 0.861618E+10 | 0.225281E+10 | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.00 | 0.00 |
July | 0.100705E+11 | 0.160918E+10 | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.00 | 0.00 |
August | 0.111204E+11 | 0.209733E+10 | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.00 | 0.00 |
September | 0.115188E+11 | 0.323547E+10 | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.00 | 0.00 |
October | 0.977905E+10 | 0.510051E+10 | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.00 | 0.00 |
November | 0.590710E+10 | 0.624755E+10 | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.00 | 0.00 |
December | 0.461665E+10 | 0.891589E+10 | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.996832E+11 | 0.622299E+11 | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.461665E+10 | 0.160918E+10 | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115188E+11 | 0.901962E+10 | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.479416E+09 | 0.665471E+10 | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.00 | 0.00 |
February | 0.108533E+10 | 0.570217E+10 | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.00 | 0.00 |
March | 0.351902E+10 | 0.471289E+10 | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.00 | 0.00 |
April | 0.491481E+10 | 0.347273E+10 | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.00 | 0.00 |
May | 0.707798E+10 | 0.246947E+10 | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.00 | 0.00 |
June | 0.933791E+10 | 0.159552E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
July | 0.919992E+10 | 0.117843E+10 | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.00 | 0.00 |
August | 0.818738E+10 | 0.148418E+10 | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.00 | 0.00 |
September | 0.555974E+10 | 0.218381E+10 | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.00 | 0.00 |
October | 0.276031E+10 | 0.349798E+10 | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.00 | 0.00 |
November | 0.104995E+10 | 0.433254E+10 | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.00 | 0.00 |
December | 0.454693E+09 | 0.648995E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.536265E+11 | 0.437744E+11 | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454693E+09 | 0.117843E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.933791E+10 | 0.665471E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 33652015.24 | 0.992887E+10 | 0.171492E+10 | 0.00 | 0.171492E+10 | 0.00 | 0.00 |
February | 0.174191E+09 | 0.838675E+10 | 0.236004E+10 | 0.00 | 0.236004E+10 | 0.00 | 0.00 |
March | 0.105348E+10 | 0.668064E+10 | 0.316871E+10 | 0.00 | 0.316871E+10 | 0.00 | 0.00 |
April | 0.214778E+10 | 0.461988E+10 | 0.390734E+10 | 15591827.53 | 0.389175E+10 | 0.00 | 0.00 |
May | 0.367053E+10 | 0.312134E+10 | 0.469147E+10 | 0.198945E+09 | 0.449253E+10 | 0.00 | 0.00 |
June | 0.581570E+10 | 0.199708E+10 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
July | 0.643025E+10 | 0.146231E+10 | 0.523450E+10 | 0.337898E+09 | 0.489660E+10 | 0.00 | 0.00 |
August | 0.527204E+10 | 0.191415E+10 | 0.452929E+10 | 68903372.72 | 0.446039E+10 | 0.00 | 0.00 |
September | 0.302462E+10 | 0.292356E+10 | 0.333570E+10 | 693014.03 | 0.333501E+10 | 0.00 | 0.00 |
October | 0.133708E+10 | 0.462922E+10 | 0.257670E+10 | 0.00 | 0.257670E+10 | 0.00 | 0.00 |
November | 0.410474E+09 | 0.580144E+10 | 0.167562E+10 | 0.00 | 0.167562E+10 | 0.00 | 0.00 |
December | 35981068.18 | 0.940041E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.294058E+11 | 0.608656E+11 | 0.402602E+11 | 0.108689E+10 | 0.391733E+11 | 0.00 | 0.00 |
Minimum of Months | 33652015.24 | 0.146231E+10 | 0.160512E+10 | 0.00 | 0.160512E+10 | 0.00 | 0.00 |
Maximum of Months | 0.643025E+10 | 0.992887E+10 | 0.546083E+10 | 0.464853E+09 | 0.499597E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.835702E+09 | 0.603481E+10 | 0.209219E+10 | 0.674639E+09 | 0.141755E+10 | 0.00 | 0.00 |
February | 0.134187E+10 | 0.517379E+10 | 0.277280E+10 | 0.832048E+09 | 0.194075E+10 | 0.00 | 0.00 |
March | 0.343564E+10 | 0.416751E+10 | 0.440520E+10 | 0.184487E+10 | 0.256033E+10 | 0.00 | 0.00 |
April | 0.525915E+10 | 0.299855E+10 | 0.564247E+10 | 0.249315E+10 | 0.314932E+10 | 0.00 | 0.00 |
May | 0.699981E+10 | 0.216828E+10 | 0.653231E+10 | 0.288959E+10 | 0.364272E+10 | 0.00 | 0.00 |
June | 0.846152E+10 | 0.138207E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
July | 0.902026E+10 | 0.100543E+10 | 0.700558E+10 | 0.308446E+10 | 0.392112E+10 | 0.00 | 0.00 |
August | 0.797503E+10 | 0.129941E+10 | 0.632681E+10 | 0.265565E+10 | 0.367116E+10 | 0.00 | 0.00 |
September | 0.581520E+10 | 0.192900E+10 | 0.509517E+10 | 0.226002E+10 | 0.283515E+10 | 0.00 | 0.00 |
October | 0.320281E+10 | 0.299613E+10 | 0.357274E+10 | 0.147778E+10 | 0.209496E+10 | 0.00 | 0.00 |
November | 0.124613E+10 | 0.373223E+10 | 0.196115E+10 | 0.629115E+09 | 0.133204E+10 | 0.00 | 0.00 |
December | 0.441918E+09 | 0.590524E+10 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540350E+11 | 0.387925E+11 | 0.540980E+11 | 0.222987E+11 | 0.317994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.441918E+09 | 0.100543E+10 | 0.163145E+10 | 0.337094E+09 | 0.129436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.902026E+10 | 0.603481E+10 | 0.706015E+10 | 0.312024E+10 | 0.393991E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595005E+10 | 0.858824E+10 | 0.737419E+10 | 0.430453E+10 | 0.306966E+10 | 0.00 | 0.00 |
February | 0.603994E+10 | 0.763583E+10 | 0.760469E+10 | 0.366691E+10 | 0.393777E+10 | 0.00 | 0.00 |
March | 0.999277E+10 | 0.636220E+10 | 0.102765E+11 | 0.577432E+10 | 0.450221E+10 | 0.00 | 0.00 |
April | 0.835482E+10 | 0.491466E+10 | 0.823605E+10 | 0.329115E+10 | 0.494490E+10 | 0.00 | 0.00 |
May | 0.817857E+10 | 0.350691E+10 | 0.744752E+10 | 0.216307E+10 | 0.528444E+10 | 0.00 | 0.00 |
June | 0.857461E+10 | 0.221596E+10 | 0.700315E+10 | 0.148400E+10 | 0.551915E+10 | 0.00 | 0.00 |
July | 0.100021E+11 | 0.161202E+10 | 0.738738E+10 | 0.179242E+10 | 0.559496E+10 | 0.00 | 0.00 |
August | 0.110709E+11 | 0.207697E+10 | 0.829355E+10 | 0.268898E+10 | 0.560457E+10 | 0.00 | 0.00 |
September | 0.115243E+11 | 0.311088E+10 | 0.933187E+10 | 0.454531E+10 | 0.478655E+10 | 0.00 | 0.00 |
October | 0.991060E+10 | 0.468063E+10 | 0.922686E+10 | 0.527056E+10 | 0.395630E+10 | 0.00 | 0.00 |
November | 0.605248E+10 | 0.566768E+10 | 0.639492E+10 | 0.361015E+10 | 0.278477E+10 | 0.00 | 0.00 |
December | 0.472190E+10 | 0.840052E+10 | 0.616629E+10 | 0.319133E+10 | 0.297495E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100373E+12 | 0.587725E+11 | 0.947430E+11 | 0.417827E+11 | 0.529602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.472190E+10 | 0.161202E+10 | 0.616629E+10 | 0.148400E+10 | 0.278477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115243E+11 | 0.858824E+10 | 0.102765E+11 | 0.577432E+10 | 0.560457E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.503026E+09 | 0.638585E+10 | 0.179506E+10 | 0.421410E+09 | 0.137365E+10 | 0.00 | 0.00 |
February | 0.112094E+10 | 0.547515E+10 | 0.262776E+10 | 0.675353E+09 | 0.195240E+10 | 0.00 | 0.00 |
March | 0.357628E+10 | 0.443449E+10 | 0.455981E+10 | 0.195241E+10 | 0.260741E+10 | 0.00 | 0.00 |
April | 0.497865E+10 | 0.326839E+10 | 0.540278E+10 | 0.221536E+10 | 0.318742E+10 | 0.00 | 0.00 |
May | 0.708406E+10 | 0.237815E+10 | 0.658589E+10 | 0.297640E+10 | 0.360949E+10 | 0.00 | 0.00 |
June | 0.929915E+10 | 0.157018E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
July | 0.914962E+10 | 0.117501E+10 | 0.710409E+10 | 0.311468E+10 | 0.398941E+10 | 0.00 | 0.00 |
August | 0.815224E+10 | 0.146918E+10 | 0.642523E+10 | 0.273207E+10 | 0.369316E+10 | 0.00 | 0.00 |
September | 0.556384E+10 | 0.210234E+10 | 0.488303E+10 | 0.210877E+10 | 0.277426E+10 | 0.00 | 0.00 |
October | 0.283537E+10 | 0.322919E+10 | 0.327093E+10 | 0.115221E+10 | 0.211872E+10 | 0.00 | 0.00 |
November | 0.111028E+10 | 0.397764E+10 | 0.187584E+10 | 0.540549E+09 | 0.133529E+10 | 0.00 | 0.00 |
December | 0.478120E+09 | 0.618088E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.538516E+11 | 0.416465E+11 | 0.539006E+11 | 0.218723E+11 | 0.320283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.478120E+09 | 0.117501E+10 | 0.168039E+10 | 0.366138E+09 | 0.131425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.929915E+10 | 0.638585E+10 | 0.768975E+10 | 0.361694E+10 | 0.407281E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.423658E+11 | -0.419189E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446912206.1 | 60.05 | 0.00 | 0.00 |
February | 0.390361E+11 | -0.386325E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -403600846.2 | 60.05 | 0.00 | 0.00 |
March | 0.452819E+11 | -0.448357E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446228522.9 | 60.05 | 0.00 | 0.00 |
April | 0.395098E+11 | -0.390803E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429451430.7 | 60.05 | 0.00 | 0.00 |
May | 0.398587E+11 | -0.394149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443792871.7 | 60.05 | 0.00 | 0.00 |
June | 0.371225E+11 | -0.367014E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -421069796.2 | 60.05 | 0.00 | 0.00 |
July | 0.336581E+11 | -0.332332E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -424880546.1 | 60.05 | 0.00 | 0.00 |
August | 0.361504E+11 | -0.357176E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -432734335.1 | 60.05 | 0.00 | 0.00 |
September | 0.334000E+11 | -0.329757E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -424285390.7 | 60.05 | 0.00 | 0.00 |
October | 0.361214E+11 | -0.356802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441265841.5 | 60.05 | 0.00 | 0.00 |
November | 0.376516E+11 | -0.372240E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427625531.1 | 60.05 | 0.00 | 0.00 |
December | 0.396971E+11 | -0.392532E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443859996.4 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.459853E+12 | -0.454668E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.518571E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.334000E+11 | -0.448357E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -446912206.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.452819E+11 | -0.329757E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -403600846.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4421.25 | 32.94 | 239.17 | 251.33 | 3523.72 | 33.90 | 243.67 | 223.67 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5558.69 | 33.10 | 251.67 | 256.83 | 1787.44 | 26.25 | 228.17 | 233.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:40 | 7928.68 | 30.46 | 270.00 | 327.50 | 1469.56 | 22.61 | 233.50 | 293.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:00 | 2108.09 | 20.44 | 152.00 | 346.67 | 1164.55 | 21.82 | 251.67 | 312.17 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1928.19 | 20.48 | 119.33 | 385.67 | 1121.20 | 21.91 | 251.17 | 338.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1743.49 | 20.25 | 139.50 | 394.67 | 992.53 | 21.66 | 285.50 | 354.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1823.91 | 20.30 | 162.67 | 401.83 | 1023.05 | 21.71 | 279.50 | 356.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2149.77 | 20.80 | 201.33 | 378.33 | 1176.85 | 22.19 | 290.83 | 338.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3037.97 | 22.24 | 174.83 | 325.67 | 1532.12 | 22.84 | 256.50 | 292.67 |
October | 314.33 | 0.49 | 0.48 | 01-OCT-07:19 | 6416.85 | 32.63 | 283.33 | 298.83 | 1558.11 | 23.31 | 230.67 | 276.83 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4168.44 | 32.78 | 243.50 | 241.50 | 1668.95 | 28.44 | 232.33 | 217.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3740.64 | 32.03 | 219.50 | 239.50 | 2890.37 | 33.26 | 227.00 | 208.00 |
Annual Sum or Average | 3928.50 | 0.50 | 3553.59 | 25.57 | 2456.83 | 3848.33 | 1541.73 | 24.29 | 3010.50 | 3445.50 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1743.49 | 20.25 | 119.33 | 239.50 | 992.53 | 21.66 | 227.00 | 208.00 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7928.68 | 33.10 | 283.33 | 401.83 | 3523.72 | 33.90 | 290.83 | 356.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1545.78 | 23.03 | 97.00 | 238.00 | 763.99 | 23.03 | 135.83 | 190.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2133.33 | 24.04 | 129.83 | 248.83 | 1095.46 | 24.24 | 175.83 | 218.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:19 | 2893.60 | 24.69 | 147.00 | 321.33 | 1251.40 | 24.00 | 191.67 | 287.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 3129.52 | 24.13 | 139.00 | 352.00 | 1749.58 | 24.63 | 219.17 | 318.33 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:30 | 4151.88 | 24.83 | 108.33 | 394.00 | 1755.13 | 24.12 | 211.50 | 350.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3779.99 | 24.08 | 142.50 | 404.50 | 1656.21 | 23.85 | 230.17 | 374.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3580.14 | 24.28 | 146.17 | 411.50 | 1567.59 | 23.85 | 247.33 | 374.67 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3328.10 | 24.56 | 151.00 | 381.00 | 1461.57 | 24.07 | 258.50 | 347.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3361.73 | 25.07 | 124.17 | 326.33 | 1831.96 | 25.31 | 205.17 | 289.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2159.24 | 23.95 | 125.50 | 290.67 | 1140.43 | 24.11 | 185.50 | 256.50 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1554.74 | 23.28 | 105.33 | 231.67 | 843.53 | 23.45 | 137.33 | 179.50 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1339.82 | 22.86 | 89.83 | 227.00 | 666.70 | 23.06 | 124.33 | 175.17 |
Annual Sum or Average | 3928.50 | 0.50 | 2899.16 | 24.14 | 1505.67 | 3826.83 | 1373.11 | 24.01 | 2322.33 | 3362.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1339.82 | 22.86 | 89.83 | 227.00 | 666.70 | 23.03 | 124.33 | 175.17 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4151.88 | 25.07 | 151.00 | 411.50 | 1831.96 | 25.31 | 258.50 | 374.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-10:09 | 675.95 | 17.63 | 0.00 | 222.50 | 376.23 | 19.04 | 0.50 | 142.33 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:20 | 887.79 | 18.62 | 0.00 | 243.00 | 491.89 | 19.96 | 48.83 | 194.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 945.30 | 19.13 | 0.00 | 315.67 | 551.73 | 20.56 | 84.67 | 267.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1095.02 | 19.63 | 6.67 | 350.83 | 639.04 | 20.95 | 171.83 | 316.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1314.37 | 21.69 | 90.00 | 402.83 | 789.95 | 22.88 | 249.67 | 363.33 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1462.21 | 23.01 | 173.50 | 413.33 | 822.76 | 22.17 | 308.33 | 385.17 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1391.56 | 22.69 | 158.83 | 419.50 | 808.59 | 22.98 | 313.67 | 389.17 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1234.54 | 20.33 | 57.50 | 388.00 | 729.18 | 21.67 | 268.00 | 354.00 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 1038.23 | 19.85 | 1.17 | 322.50 | 638.49 | 21.28 | 147.83 | 273.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 827.60 | 18.39 | 0.00 | 282.33 | 474.32 | 19.81 | 33.33 | 225.17 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 655.42 | 17.08 | 0.00 | 218.50 | 363.17 | 18.41 | 1.50 | 130.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:00 | 678.92 | 17.56 | 0.00 | 208.17 | 369.54 | 18.88 | 1.50 | 121.33 |
Annual Sum or Average | 3928.50 | 0.50 | 1068.46 | 19.98 | 487.67 | 3787.17 | 618.57 | 20.97 | 1629.67 | 3162.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 655.42 | 17.08 | 0.00 | 208.17 | 363.17 | 18.41 | 0.50 | 121.33 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1462.21 | 23.01 | 173.50 | 419.50 | 822.76 | 22.98 | 313.67 | 389.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:50 | 1450.50 | 23.30 | 105.00 | 237.50 | 781.71 | 23.62 | 142.00 | 191.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 1994.06 | 23.88 | 126.83 | 249.17 | 1046.13 | 24.22 | 177.00 | 218.33 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-08:09 | 2842.91 | 24.52 | 143.17 | 324.17 | 1598.40 | 24.93 | 203.50 | 289.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:10 | 3328.04 | 23.25 | 131.17 | 347.83 | 1402.88 | 22.80 | 193.33 | 314.83 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:30 | 3578.51 | 21.19 | 52.17 | 392.50 | 1958.75 | 21.25 | 175.83 | 355.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3767.46 | 20.99 | 64.00 | 402.67 | 1614.32 | 21.23 | 214.83 | 371.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3367.44 | 21.01 | 74.83 | 408.83 | 1522.14 | 21.35 | 218.33 | 373.00 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-06:30 | 3156.61 | 22.56 | 119.17 | 384.17 | 1697.89 | 23.18 | 234.67 | 349.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3485.23 | 24.81 | 116.67 | 323.50 | 1508.91 | 23.99 | 197.67 | 291.83 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:49 | 2026.91 | 23.74 | 125.50 | 289.83 | 1063.88 | 24.02 | 181.83 | 255.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1487.39 | 22.86 | 102.50 | 230.50 | 784.38 | 23.02 | 134.17 | 184.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1396.86 | 22.82 | 91.33 | 223.50 | 731.65 | 23.21 | 129.17 | 175.33 |
Annual Sum or Average | 3928.50 | 0.50 | 2804.12 | 22.76 | 1252.33 | 3814.17 | 1370.18 | 22.93 | 2202.33 | 3370.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1396.86 | 20.99 | 52.17 | 223.50 | 731.65 | 21.23 | 129.17 | 175.33 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3767.46 | 24.81 | 143.17 | 408.83 | 1958.75 | 24.93 | 234.67 | 373.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-08:00 | 4435.75 | 32.12 | 233.00 | 251.50 | 3611.30 | 33.12 | 231.83 | 226.17 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5578.25 | 32.40 | 241.33 | 256.83 | 1934.82 | 24.28 | 106.33 | 239.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7974.67 | 28.59 | 228.50 | 327.67 | 1584.66 | 18.07 | 11.33 | 297.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 2141.69 | 14.09 | 0.00 | 347.67 | 1244.90 | 17.54 | 1.33 | 317.33 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1966.89 | 14.42 | 0.00 | 385.67 | 1199.75 | 17.95 | 0.00 | 343.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1772.96 | 14.29 | 0.00 | 394.83 | 1059.34 | 17.75 | 0.00 | 360.00 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1853.17 | 14.23 | 0.00 | 402.83 | 1091.64 | 17.69 | 0.00 | 362.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:10 | 2180.57 | 14.62 | 0.00 | 378.33 | 1255.74 | 18.06 | 0.67 | 342.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3083.52 | 16.27 | 17.00 | 326.00 | 1640.50 | 18.60 | 7.17 | 295.67 |
October | 314.33 | 0.49 | 0.48 | 01-OCT-07:10 | 6449.09 | 31.60 | 269.67 | 299.00 | 1745.40 | 18.81 | 25.33 | 279.33 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4179.28 | 32.08 | 237.33 | 241.50 | 2030.10 | 27.51 | 160.50 | 220.17 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-07:00 | 3738.53 | 30.70 | 203.67 | 239.50 | 2970.83 | 32.59 | 216.00 | 210.50 |
Annual Sum or Average | 3928.50 | 0.50 | 3582.46 | 21.58 | 1430.50 | 3851.33 | 1656.03 | 20.90 | 760.50 | 3493.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1772.96 | 14.09 | 0.00 | 239.50 | 1059.34 | 17.54 | 0.00 | 210.50 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7974.67 | 32.40 | 269.67 | 402.83 | 3611.30 | 33.12 | 231.83 | 362.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-08:00 | 1571.55 | 20.20 | 70.17 | 239.00 | 801.18 | 20.89 | 66.67 | 196.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2170.24 | 21.37 | 83.00 | 250.00 | 1144.30 | 22.16 | 70.00 | 221.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:19 | 2944.56 | 22.02 | 115.33 | 321.67 | 1312.51 | 21.66 | 61.50 | 291.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:19 | 3162.35 | 20.39 | 104.00 | 352.00 | 1820.78 | 22.35 | 87.50 | 321.83 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:30 | 4205.63 | 21.89 | 103.50 | 395.17 | 1841.06 | 21.51 | 55.83 | 353.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3828.26 | 21.15 | 132.67 | 405.00 | 1735.49 | 21.28 | 75.83 | 377.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3627.44 | 21.36 | 135.83 | 412.83 | 1645.72 | 21.29 | 75.50 | 377.67 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:49 | 3380.42 | 21.62 | 122.67 | 382.17 | 1535.91 | 21.51 | 67.33 | 351.33 |
September | 289.17 | 0.49 | 0.48 | 01-SEP-07:40 | 3423.63 | 22.24 | 86.50 | 326.83 | 1908.08 | 23.06 | 63.17 | 293.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2200.27 | 21.17 | 91.67 | 291.83 | 1192.56 | 21.96 | 65.83 | 260.83 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1579.49 | 20.59 | 86.83 | 232.67 | 878.82 | 21.49 | 73.83 | 185.67 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1358.33 | 19.48 | 59.67 | 227.67 | 699.37 | 21.01 | 60.83 | 180.67 |
Annual Sum or Average | 3928.50 | 0.50 | 2941.88 | 21.19 | 1191.83 | 3836.83 | 1437.18 | 21.67 | 823.83 | 3411.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1358.33 | 19.48 | 59.67 | 227.67 | 699.37 | 20.89 | 55.83 | 180.67 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4205.63 | 22.24 | 135.83 | 412.83 | 1908.08 | 23.06 | 87.50 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 683.53 | 11.40 | 0.00 | 222.83 | 399.33 | 14.92 | 0.00 | 153.17 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:09 | 899.64 | 12.75 | 0.00 | 243.00 | 522.40 | 16.11 | 0.00 | 201.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:00 | 959.79 | 13.47 | 0.00 | 316.50 | 587.03 | 16.92 | 0.00 | 273.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1113.32 | 14.03 | 0.00 | 351.00 | 680.14 | 17.44 | 0.00 | 321.00 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1341.52 | 16.57 | 26.17 | 403.00 | 845.41 | 19.86 | 28.83 | 367.83 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1489.62 | 18.33 | 74.33 | 413.67 | 906.31 | 19.95 | 41.33 | 391.50 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1416.63 | 17.96 | 71.00 | 419.83 | 860.56 | 19.70 | 45.00 | 391.33 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1255.96 | 14.76 | 0.00 | 388.33 | 775.94 | 18.23 | 2.67 | 357.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 1056.95 | 14.70 | 0.00 | 322.83 | 680.28 | 18.15 | 0.00 | 279.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 839.02 | 12.56 | 0.00 | 282.83 | 504.16 | 16.00 | 0.00 | 235.17 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:09 | 662.80 | 10.93 | 0.00 | 218.83 | 385.52 | 14.31 | 0.00 | 140.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 686.45 | 11.27 | 0.00 | 209.17 | 392.07 | 14.73 | 0.00 | 132.17 |
Annual Sum or Average | 3928.50 | 0.50 | 1086.26 | 14.49 | 171.50 | 3791.83 | 661.79 | 17.53 | 117.83 | 3243.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 662.80 | 10.93 | 0.00 | 209.17 | 385.52 | 14.31 | 0.00 | 132.17 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1489.62 | 18.33 | 74.33 | 419.83 | 906.31 | 19.95 | 45.00 | 391.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:39 | 1473.48 | 20.84 | 85.17 | 238.83 | 814.71 | 21.76 | 76.17 | 196.17 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 2029.49 | 21.18 | 81.67 | 249.50 | 1093.24 | 22.15 | 68.83 | 221.67 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:00 | 2871.65 | 21.00 | 101.67 | 325.00 | 1661.88 | 22.81 | 85.83 | 293.50 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:10 | 3380.06 | 20.18 | 104.33 | 349.33 | 1470.85 | 20.09 | 49.33 | 318.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:30 | 3617.56 | 17.24 | 43.00 | 393.50 | 2044.84 | 17.88 | 0.00 | 359.00 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3816.63 | 17.00 | 52.50 | 403.50 | 1698.03 | 17.84 | 0.00 | 373.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3415.10 | 17.08 | 54.50 | 409.67 | 1599.53 | 18.06 | 3.67 | 376.50 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-06:30 | 3205.06 | 19.16 | 85.17 | 384.67 | 1771.95 | 20.49 | 53.67 | 353.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3509.63 | 21.92 | 84.67 | 324.33 | 1584.33 | 21.45 | 41.67 | 294.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:49 | 2064.11 | 20.91 | 89.50 | 290.83 | 1113.02 | 21.83 | 64.33 | 260.67 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-08:09 | 1511.11 | 20.32 | 87.00 | 231.17 | 818.10 | 21.05 | 68.67 | 190.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1419.85 | 20.15 | 63.67 | 225.17 | 764.60 | 21.21 | 66.17 | 179.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2842.08 | 19.50 | 932.83 | 3825.50 | 1433.77 | 20.32 | 578.33 | 3417.00 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1419.85 | 17.00 | 43.00 | 225.17 | 764.60 | 17.84 | 0.00 | 179.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 3816.63 | 21.92 | 104.33 | 409.67 | 2044.84 | 22.81 | 85.83 | 376.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-08:00 | 4437.52 | 32.11 | 233.00 | 251.50 | 3613.53 | 33.11 | 231.83 | 226.33 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5581.26 | 32.39 | 241.33 | 256.83 | 1937.72 | 24.27 | 106.33 | 239.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7978.04 | 28.58 | 228.33 | 327.67 | 1586.98 | 18.06 | 11.17 | 297.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 2144.89 | 14.06 | 0.00 | 347.67 | 1246.85 | 17.52 | 1.17 | 317.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1969.46 | 14.39 | 0.00 | 385.67 | 1201.38 | 17.94 | 0.00 | 343.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1775.35 | 14.26 | 0.00 | 394.83 | 1060.86 | 17.74 | 0.00 | 360.17 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1855.78 | 14.20 | 0.00 | 402.83 | 1093.26 | 17.68 | 0.00 | 362.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:10 | 2183.84 | 14.59 | 0.00 | 378.33 | 1257.73 | 18.05 | 0.67 | 342.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3087.24 | 16.24 | 17.00 | 326.00 | 1642.96 | 18.58 | 7.00 | 295.67 |
October | 314.33 | 0.49 | 0.48 | 01-OCT-07:10 | 6451.90 | 31.59 | 269.67 | 299.00 | 1841.00 | 19.07 | 28.83 | 279.33 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4181.22 | 32.07 | 237.33 | 241.50 | 2298.75 | 29.22 | 186.50 | 220.50 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-07:00 | 3740.25 | 30.69 | 203.67 | 239.50 | 2973.05 | 32.59 | 216.00 | 210.67 |
Annual Sum or Average | 3928.50 | 0.50 | 3585.21 | 21.56 | 1430.33 | 3851.33 | 1683.07 | 21.02 | 789.50 | 3495.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1775.35 | 14.06 | 0.00 | 239.50 | 1060.86 | 17.52 | 0.00 | 210.67 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7978.04 | 32.39 | 269.67 | 402.83 | 3613.53 | 33.11 | 231.83 | 362.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-08:00 | 1572.86 | 20.17 | 70.17 | 239.00 | 802.33 | 20.87 | 66.33 | 196.67 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2172.13 | 21.34 | 83.00 | 250.00 | 1145.84 | 22.15 | 69.83 | 221.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:19 | 2916.41 | 21.00 | 103.17 | 321.83 | 1314.00 | 21.65 | 61.50 | 291.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:19 | 3164.34 | 20.36 | 104.00 | 352.17 | 1822.43 | 22.33 | 87.50 | 322.00 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:30 | 4207.62 | 21.86 | 103.50 | 395.33 | 1842.81 | 21.50 | 55.83 | 353.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3830.38 | 21.12 | 132.67 | 405.00 | 1737.25 | 21.26 | 75.83 | 377.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3629.52 | 21.34 | 135.83 | 412.83 | 1647.45 | 21.27 | 75.50 | 377.67 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:49 | 3382.59 | 21.59 | 122.67 | 382.17 | 1537.72 | 21.50 | 67.33 | 351.50 |
September | 289.17 | 0.49 | 0.48 | 01-SEP-07:40 | 3425.42 | 22.21 | 86.50 | 326.83 | 1909.88 | 23.05 | 63.17 | 293.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2201.84 | 21.14 | 91.50 | 291.83 | 1193.91 | 21.95 | 65.83 | 260.83 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1580.79 | 20.57 | 86.83 | 232.67 | 879.91 | 21.48 | 73.33 | 186.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1359.72 | 19.45 | 59.67 | 228.00 | 700.49 | 21.00 | 60.67 | 180.67 |
Annual Sum or Average | 3928.50 | 0.50 | 2941.13 | 21.07 | 1179.50 | 3837.67 | 1438.74 | 21.66 | 822.67 | 3413.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1359.72 | 19.45 | 59.67 | 228.00 | 700.49 | 20.87 | 55.83 | 180.67 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4207.62 | 22.21 | 135.83 | 412.83 | 1909.88 | 23.05 | 87.50 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 684.39 | 11.37 | 0.00 | 223.33 | 399.97 | 14.91 | 0.00 | 153.50 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:09 | 900.82 | 12.72 | 0.00 | 243.17 | 523.24 | 16.10 | 0.00 | 201.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:00 | 960.85 | 13.44 | 0.00 | 316.67 | 587.86 | 16.91 | 0.00 | 273.50 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1114.58 | 14.00 | 0.00 | 351.00 | 681.10 | 17.42 | 0.00 | 321.50 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1342.63 | 16.54 | 26.17 | 403.00 | 846.41 | 19.85 | 28.67 | 368.00 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1491.05 | 18.31 | 74.33 | 413.67 | 907.48 | 19.94 | 40.50 | 391.50 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1418.06 | 17.93 | 71.00 | 419.83 | 861.70 | 19.69 | 44.50 | 391.33 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1257.28 | 14.73 | 0.00 | 388.33 | 776.99 | 18.21 | 2.17 | 357.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 1057.81 | 14.66 | 0.00 | 322.83 | 681.12 | 18.13 | 0.00 | 279.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 839.99 | 12.53 | 0.00 | 283.00 | 504.91 | 15.98 | 0.00 | 235.50 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:09 | 663.66 | 10.90 | 0.00 | 219.00 | 386.14 | 14.30 | 0.00 | 141.17 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 687.38 | 11.24 | 0.00 | 209.67 | 392.73 | 14.71 | 0.00 | 132.17 |
Annual Sum or Average | 3928.50 | 0.50 | 1087.41 | 14.46 | 171.50 | 3793.50 | 662.70 | 17.51 | 115.83 | 3246.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 663.66 | 10.90 | 0.00 | 209.67 | 386.14 | 14.30 | 0.00 | 132.17 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1491.05 | 18.31 | 74.33 | 419.83 | 907.48 | 19.94 | 44.50 | 391.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:39 | 1474.79 | 20.81 | 85.17 | 238.83 | 815.80 | 21.75 | 76.17 | 196.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 2031.36 | 21.16 | 81.67 | 249.50 | 1094.79 | 22.14 | 68.17 | 222.00 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:00 | 2873.40 | 20.98 | 101.67 | 325.00 | 1663.40 | 22.79 | 85.83 | 293.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:10 | 3382.09 | 20.16 | 104.33 | 349.33 | 1472.51 | 20.08 | 49.33 | 318.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:30 | 3619.45 | 17.21 | 43.00 | 393.67 | 2046.55 | 17.86 | 0.00 | 359.00 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3818.73 | 16.96 | 52.50 | 403.83 | 1699.87 | 17.83 | 0.00 | 373.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3417.29 | 17.04 | 54.50 | 409.83 | 1601.33 | 18.04 | 3.67 | 376.83 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-06:30 | 3207.33 | 19.13 | 85.00 | 384.67 | 1773.81 | 20.48 | 53.67 | 353.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3511.36 | 21.89 | 84.67 | 324.33 | 1586.00 | 21.43 | 41.67 | 294.83 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:49 | 2065.73 | 20.89 | 89.50 | 290.83 | 1114.40 | 21.82 | 64.00 | 260.67 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-08:09 | 1512.42 | 20.30 | 87.00 | 231.17 | 819.17 | 21.04 | 68.17 | 190.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1421.24 | 20.13 | 63.67 | 225.17 | 765.74 | 21.19 | 66.17 | 179.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2843.93 | 19.48 | 932.67 | 3826.17 | 1435.34 | 20.31 | 576.83 | 3418.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1421.24 | 16.96 | 43.00 | 225.17 | 765.74 | 17.83 | 0.00 | 179.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 3818.73 | 21.89 | 104.33 | 409.83 | 2046.55 | 22.79 | 85.83 | 376.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123890E+09 | 15268.39 | 18-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191844E+09 | 17502.60 | 16-FEB-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211252E+09 | 14505.96 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84507925.33 | 15507.44 | 03-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9697546.79 | 1751.04 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2164065.33 | 2276.34 | 06-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72196269.14 | 12100.59 | 17-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129073E+09 | 12221.56 | 03-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221176E+09 | 12957.04 | 19-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221176E+09 | 17502.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106512E+10 | 14631.70 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701844E+09 | 14632.33 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118290E+09 | 14944.15 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319150E+09 | 14706.57 | 08-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106512E+10 | 14944.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.698378E+09 | 14453.21 | 03-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531106E+09 | 14476.81 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71961500.92 | 14494.36 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5192774.65 | 1118.40 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429839E+09 | 14523.94 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.698378E+09 | 14523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128283E+10 | 20319.94 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102361E+10 | 20326.32 | 16-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159842E+09 | 20379.56 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7629451.80 | 10005.21 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7279767.96 | 11413.20 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27035695.84 | 20381.42 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.639176E+09 | 20389.78 | 07-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128283E+10 | 20389.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176366E+09 | 12654.45 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53535077.36 | 12651.27 | 14-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176366E+09 | 12654.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.885433E+10 | 302698.81 | 09-JAN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.720008E+10 | 294520.21 | 03-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386518E+10 | 239645.93 | 28-MAR-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.315041E+10 | 383471.74 | 11-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103818E+10 | 272579.05 | 11-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177616E+09 | 251672.86 | 13-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2441003.07 | 8135.32 | 31-AUG-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236230E+09 | 98567.44 | 28-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210534E+10 | 250671.98 | 27-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227555E+10 | 189398.26 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.530961E+10 | 375545.31 | 28-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.885433E+10 | 383471.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174901E+11 | 526337.67 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.449899E+10 | 525090.25 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294654E+10 | 525425.26 | 11-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174901E+11 | 526337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.710718E+11 | 127344.29 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575781E+11 | 127355.83 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210575E+11 | 126706.53 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236158E+10 | 129075.45 | 14-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195404E+10 | 136006.28 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.956403E+10 | 128778.65 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.564262E+11 | 127327.32 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.710718E+11 | 136006.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382374E+11 | 187533.95 | 09-JAN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304282E+11 | 181758.80 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769993E+10 | 181416.21 | 27-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.868746E+09 | 181261.96 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.898696E+09 | 181255.41 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523830E+10 | 182546.64 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327746E+11 | 181651.58 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382374E+11 | 187533.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.444609E+11 | 211790.32 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358369E+11 | 210713.68 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.797090E+10 | 210418.52 | 07-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156072E+10 | 208235.83 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.834725E+09 | 208620.63 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557410E+10 | 214090.61 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.371864E+11 | 210587.02 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.444609E+11 | 214090.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357374E+11 | 182760.79 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269724E+11 | 182777.80 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.621048E+10 | 182321.67 | 07-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.493260E+09 | 182032.46 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.565017E+09 | 182120.10 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354281E+10 | 182084.19 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266421E+11 | 182766.11 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357374E+11 | 182777.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319397E+10 | 12081.77 | 09-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283643E+10 | 15680.47 | 06-FEB-04:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691857E+09 | 11185.40 | 07-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90442074.40 | 8672.15 | 13-APR-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26379139.82 | 5085.14 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2670160.63 | 2760.19 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 159.23 | 0.27 | 02-JUL-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8838641.24 | 3766.27 | 12-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66257499.40 | 7288.67 | 19-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54145610.41 | 7317.85 | 14-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242251E+10 | 16585.59 | 11-DEC-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.939350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319397E+10 | 16585.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119148E+11 | 75106.81 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.961993E+10 | 75074.36 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330699E+10 | 74895.26 | 20-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469279E+09 | 74874.28 | 17-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.552213E+09 | 75128.78 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197640E+10 | 75485.80 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.948369E+10 | 75101.21 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119148E+11 | 75485.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122080E+11 | 14492.68 | 03-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103618E+11 | 14490.64 | 03-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.516891E+10 | 14464.86 | 13-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128763E+10 | 14488.09 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59956524.90 | 14422.49 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45158640.11 | 14389.54 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125732E+10 | 14498.76 | 30-OCT-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358948E+10 | 14493.51 | 14-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109368E+11 | 14497.11 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122080E+11 | 14498.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.723715E+10 | 20018.48 | 04-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603845E+10 | 20087.04 | 03-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228635E+10 | 20005.55 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.521967E+09 | 19991.83 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18829048.97 | 17252.65 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19304861.89 | 12039.40 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.588386E+09 | 20003.02 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205651E+10 | 20097.18 | 13-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694740E+10 | 20085.45 | 09-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.723715E+10 | 20097.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.854099E+10 | 22807.08 | 03-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740241E+10 | 22803.61 | 03-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275273E+10 | 22732.69 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922983E+09 | 22708.56 | 17-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62764808.19 | 17221.22 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1077555.72 | 712.04 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25621783.61 | 11422.54 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.685226E+09 | 22810.51 | 16-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241369E+10 | 22802.53 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817934E+10 | 22796.34 | 13-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.854099E+10 | 22810.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.653845E+10 | 21454.55 | 28-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502253E+10 | 21457.44 | 01-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183431E+10 | 21449.29 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392113E+09 | 21396.86 | 05-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6533564.27 | 1399.88 | 12-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12686999.65 | 3184.31 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417947E+09 | 21394.29 | 17-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144805E+10 | 21432.13 | 21-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.529117E+10 | 21428.08 | 06-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.653845E+10 | 21457.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133695E+11 | 30628.79 | 31-JAN-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113473E+11 | 34525.08 | 06-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333298E+10 | 24170.37 | 07-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118347E+09 | 17012.13 | 17-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1076750.42 | 2823.59 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 396.97 | 0.67 | 09-JUN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 242.49 | 0.36 | 04-AUG-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 653.52 | 0.84 | 28-SEP-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3033337.42 | 10110.84 | 17-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101905E+09 | 9031.91 | 22-NOV-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.523659E+10 | 29612.68 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133695E+11 | 34525.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11550518.54 | 11550518.54 | 8069.66 | 17-JAN-08:15 | 8069.66 | 0.00 |
February | 0.00 | 0.00 | 0.389478E+09 | 0.389478E+09 | 25189.58 | 22-FEB-15:00 | 25189.58 | 0.00 |
March | 0.00 | 0.00 | 0.897677E+10 | 0.879373E+10 | 105754.51 | 14-MAR-13:05 | 90666.21 | 0.06 |
April | 0.00 | 0.00 | 0.474962E+10 | 0.474962E+10 | 52416.76 | 07-APR-14:00 | 52416.76 | 0.02 |
May | 0.00 | 0.00 | 0.185430E+11 | 0.183236E+11 | 95113.08 | 10-MAY-14:40 | 87239.43 | 0.15 |
June | 0.00 | 0.00 | 0.851655E+11 | 0.677548E+11 | 255306.43 | 27-JUN-07:50 | 110101.79 | 0.51 |
July | 0.00 | 0.00 | 0.156732E+12 | 0.113354E+12 | 302187.78 | 21-JUL-05:02 | 122012.80 | 0.78 |
August | 0.00 | 0.00 | 0.132182E+12 | 0.103611E+12 | 277132.82 | 15-AUG-08:20 | 120156.94 | 0.75 |
September | 0.00 | 0.00 | 0.509929E+11 | 0.406113E+11 | 192486.60 | 14-SEP-04:12 | 83986.01 | 0.41 |
October | 0.00 | 0.00 | 0.102865E+11 | 0.102831E+11 | 79136.30 | 11-OCT-15:00 | 79136.30 | 0.11 |
November | 0.00 | 0.00 | 0.533096E+10 | 0.533096E+10 | 52275.44 | 27-NOV-06:03 | 52275.44 | 0.05 |
December | 0.00 | 0.00 | 0.264578E+09 | 0.264578E+09 | 13376.96 | 04-DEC-14:50 | 13376.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.473624E+12 | 0.373478E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 11550518.54 | 11550518.54 | 8069.66 | 8069.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156732E+12 | 0.113354E+12 | 302187.78 | 122012.80 | 0.78 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8897611.50 | 8897611.50 | 3639.50 | 11-JAN-15:10 | 3639.50 | 0.01 |
February | 0.00 | 0.00 | 56474678.37 | 56474678.37 | 9622.53 | 28-FEB-15:20 | 9622.53 | 0.00 |
March | 0.00 | 0.00 | 0.452818E+11 | 0.440767E+11 | 798843.98 | 15-MAR-14:05 | 798843.98 | 0.06 |
April | 0.00 | 0.00 | 0.544718E+11 | 0.544718E+11 | 498112.52 | 19-APR-14:50 | 498112.52 | 0.03 |
May | 0.00 | 0.00 | 0.167717E+12 | 0.166016E+12 | 854582.07 | 10-MAY-14:40 | 788655.97 | 0.15 |
June | 0.00 | 0.00 | 0.646351E+12 | 0.526022E+12 | 1692600.57 | 27-JUN-07:40 | 737453.36 | 0.46 |
July | 0.00 | 0.00 | 0.108265E+13 | 0.811091E+12 | 2466925.98 | 17-JUL-05:02 | 983523.96 | 0.61 |
August | 0.00 | 0.00 | 0.905340E+12 | 0.738184E+12 | 2530010.68 | 14-AUG-05:02 | 960719.71 | 0.58 |
September | 0.00 | 0.00 | 0.412795E+12 | 0.337720E+12 | 1547580.92 | 14-SEP-05:03 | 674260.31 | 0.40 |
October | 0.00 | 0.00 | 0.804732E+11 | 0.804242E+11 | 645677.67 | 11-OCT-15:00 | 645677.67 | 0.12 |
November | 0.00 | 0.00 | 0.157286E+11 | 0.157286E+11 | 281678.55 | 16-NOV-13:05 | 281678.55 | 0.04 |
December | 0.00 | 0.00 | 42848555.41 | 42848555.41 | 8116.47 | 04-DEC-11:10 | 8116.47 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.341092E+13 | 0.277384E+13 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 8897611.50 | 8897611.50 | 3639.50 | 3639.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108265E+13 | 0.811091E+12 | 2530010.68 | 983523.96 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1117683.74 | 1117683.74 | 601.73 | 02-JAN-07:03 | 601.73 | 0.01 |
February | 0.00 | 0.00 | 5331679.48 | 5331679.48 | 862.06 | 28-FEB-15:00 | 862.06 | 0.00 |
March | 0.00 | 0.00 | 0.407671E+10 | 0.407559E+10 | 93787.89 | 15-MAR-14:20 | 93787.89 | 0.06 |
April | 0.00 | 0.00 | 0.150635E+10 | 0.150635E+10 | 35456.09 | 07-APR-14:00 | 35456.09 | 0.02 |
May | 0.00 | 0.00 | 0.156220E+11 | 0.154989E+11 | 100957.35 | 14-MAY-15:02 | 88754.95 | 0.14 |
June | 0.00 | 0.00 | 0.699716E+11 | 0.568114E+11 | 173036.85 | 27-JUN-05:03 | 74437.39 | 0.46 |
July | 0.00 | 0.00 | 0.119770E+12 | 0.899215E+11 | 308070.74 | 21-JUL-05:02 | 124427.04 | 0.61 |
August | 0.00 | 0.00 | 0.981338E+11 | 0.796226E+11 | 272971.29 | 14-AUG-05:02 | 103623.74 | 0.57 |
September | 0.00 | 0.00 | 0.399541E+11 | 0.325316E+11 | 168837.85 | 15-SEP-13:10 | 92475.79 | 0.39 |
October | 0.00 | 0.00 | 0.445403E+10 | 0.445403E+10 | 62207.58 | 11-OCT-15:00 | 62207.58 | 0.10 |
November | 0.00 | 0.00 | 0.554335E+09 | 0.554335E+09 | 12134.76 | 16-NOV-13:00 | 12134.76 | 0.04 |
December | 0.00 | 0.00 | 4194387.81 | 4194387.81 | 421.65 | 04-DEC-11:00 | 421.65 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.354053E+12 | 0.284987E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 1117683.74 | 1117683.74 | 421.65 | 421.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119770E+12 | 0.899215E+11 | 308070.74 | 124427.04 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 41389778.29 | 41389778.29 | 5270.03 | 11-JAN-16:00 | 5270.03 | 0.01 |
February | 0.00 | 0.00 | 38811114.69 | 38811114.69 | 6068.56 | 22-FEB-17:00 | 6068.56 | 0.00 |
March | 0.00 | 0.00 | 0.390107E+10 | 0.388490E+10 | 55155.19 | 15-MAR-14:00 | 55155.19 | 0.04 |
April | 0.00 | 0.00 | 0.153861E+10 | 0.153861E+10 | 27505.39 | 07-APR-13:20 | 27505.39 | 0.01 |
May | 0.00 | 0.00 | 0.121745E+11 | 0.115031E+11 | 85701.42 | 24-MAY-06:25 | 44821.78 | 0.12 |
June | 0.00 | 0.00 | 0.319718E+11 | 0.249510E+11 | 124828.76 | 28-JUN-14:20 | 76215.89 | 0.25 |
July | 0.00 | 0.00 | 0.532899E+11 | 0.393413E+11 | 173433.53 | 29-JUL-10:53 | 63286.68 | 0.27 |
August | 0.00 | 0.00 | 0.564729E+11 | 0.463323E+11 | 136451.30 | 28-AUG-12:05 | 71039.36 | 0.37 |
September | 0.00 | 0.00 | 0.331419E+11 | 0.261229E+11 | 133426.63 | 14-SEP-16:00 | 66919.67 | 0.31 |
October | 0.00 | 0.00 | 0.555058E+10 | 0.529696E+10 | 73083.92 | 26-OCT-06:25 | 34522.40 | 0.10 |
November | 0.00 | 0.00 | 0.877442E+09 | 0.873236E+09 | 55196.25 | 27-NOV-07:11 | 55196.25 | 0.02 |
December | 0.00 | 0.00 | 6140035.17 | 5949607.27 | 17374.01 | 01-DEC-07:13 | 16395.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199005E+12 | 0.159930E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 6140035.17 | 5949607.27 | 5270.03 | 5270.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.564729E+11 | 0.463323E+11 | 173433.53 | 76215.89 | 0.37 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.656980E+10 | 0.656975E+10 | 3825.74 | 13-JAN-18:00 | 3825.74 | 0.00 |
February | 0.00 | 0.00 | 0.102825E+11 | 0.102722E+11 | 5069.26 | 14-FEB-17:15 | 5069.26 | 0.00 |
March | 0.00 | 0.00 | 0.314528E+11 | 0.283874E+11 | 313928.95 | 14-MAR-13:00 | 255009.50 | 0.00 |
April | 0.00 | 0.00 | 0.364164E+11 | 0.339235E+11 | 234047.96 | 08-APR-14:00 | 212400.65 | 0.00 |
May | 0.00 | 0.00 | 0.723110E+10 | 0.677721E+10 | 124780.53 | 10-MAY-15:00 | 105356.98 | 0.00 |
June | 0.00 | 0.00 | 0.166936E+12 | 0.118666E+12 | 432272.86 | 27-JUN-14:05 | 226014.03 | 0.00 |
July | 0.00 | 0.00 | 0.711245E+12 | 0.442307E+12 | 543995.15 | 20-JUL-22:13 | 191812.49 | 0.00 |
August | 0.00 | 0.00 | 0.826201E+12 | 0.554696E+12 | 527717.42 | 14-AUG-00:53 | 210657.15 | 0.00 |
September | 0.00 | 0.00 | 0.150678E+11 | 0.112554E+11 | 177632.62 | 15-SEP-12:00 | 106266.88 | 0.00 |
October | 0.00 | 0.00 | 0.854372E+10 | 0.822278E+10 | 88289.70 | 11-OCT-15:00 | 81933.08 | 0.00 |
November | 0.00 | 0.00 | 0.172421E+11 | 0.159210E+11 | 104722.61 | 05-NOV-13:55 | 85768.31 | 0.00 |
December | 0.00 | 0.00 | 0.150363E+11 | 0.146524E+11 | 67559.13 | 01-DEC-11:00 | 45291.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185223E+13 | 0.125165E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.656980E+10 | 0.656975E+10 | 3825.74 | 3825.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.826201E+12 | 0.554696E+12 | 543995.15 | 255009.50 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.312890E+10 | 0.312860E+10 | 2202.93 | 15-JAN-16:35 | 2202.93 | 0.00 |
February | 0.00 | 0.00 | 0.778657E+10 | 0.778657E+10 | 4203.69 | 28-FEB-17:00 | 4203.69 | 0.00 |
March | 0.00 | 0.00 | 0.148841E+11 | 0.148628E+11 | 7553.87 | 31-MAR-24:00 | 7553.87 | 0.00 |
April | 0.00 | 0.00 | 0.197920E+11 | 0.197891E+11 | 8755.97 | 02-APR-17:55 | 8755.97 | 0.00 |
May | 0.00 | 0.00 | 0.558575E+10 | 0.555033E+10 | 4026.73 | 31-MAY-24:00 | 4026.73 | 0.00 |
June | 0.00 | 0.00 | 0.108868E+11 | 0.107049E+11 | 5944.43 | 30-JUN-24:00 | 5944.43 | 0.00 |
July | 0.00 | 0.00 | 0.166302E+11 | 0.163163E+11 | 7880.61 | 31-JUL-24:00 | 7841.22 | 0.00 |
August | 0.00 | 0.00 | 0.214771E+11 | 0.212387E+11 | 8788.70 | 14-AUG-15:50 | 8439.56 | 0.00 |
September | 0.00 | 0.00 | 0.570663E+10 | 0.557413E+10 | 3792.95 | 30-SEP-24:00 | 3792.95 | 0.00 |
October | 0.00 | 0.00 | 0.103083E+11 | 0.102776E+11 | 5719.02 | 31-OCT-24:00 | 5719.02 | 0.00 |
November | 0.00 | 0.00 | 0.145502E+11 | 0.145482E+11 | 6072.37 | 15-NOV-16:20 | 6072.37 | 0.00 |
December | 0.00 | 0.00 | 0.194012E+11 | 0.194007E+11 | 7846.97 | 17-DEC-16:10 | 7846.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150138E+12 | 0.149178E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.312890E+10 | 0.312860E+10 | 2202.93 | 2202.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214771E+11 | 0.212387E+11 | 8788.70 | 8755.97 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.543361E+10 | 0.543358E+10 | 14825.06 | 12-JAN-16:50 | 14825.06 | 0.00 |
February | 0.00 | 0.00 | 0.494842E+11 | 0.494842E+11 | 36849.82 | 28-FEB-17:00 | 36849.82 | 0.00 |
March | 0.00 | 0.00 | 0.126105E+12 | 0.125892E+12 | 67936.13 | 31-MAR-23:40 | 67936.13 | 0.00 |
April | 0.00 | 0.00 | 0.179571E+12 | 0.179540E+12 | 80484.82 | 02-APR-18:00 | 80484.82 | 0.00 |
May | 0.00 | 0.00 | 0.487521E+11 | 0.484021E+11 | 38152.36 | 31-MAY-24:00 | 38152.36 | 0.00 |
June | 0.00 | 0.00 | 0.101461E+12 | 0.996523E+11 | 56675.14 | 30-JUN-24:00 | 56675.14 | 0.00 |
July | 0.00 | 0.00 | 0.157261E+12 | 0.154136E+12 | 75673.10 | 31-JUL-24:00 | 75289.22 | 0.00 |
August | 0.00 | 0.00 | 0.203456E+12 | 0.201079E+12 | 83926.86 | 04-AUG-18:40 | 83926.86 | 0.00 |
September | 0.00 | 0.00 | 0.498360E+11 | 0.485340E+11 | 33165.80 | 30-SEP-24:00 | 33165.80 | 0.00 |
October | 0.00 | 0.00 | 0.871519E+11 | 0.868448E+11 | 50836.09 | 31-OCT-23:40 | 50836.09 | 0.00 |
November | 0.00 | 0.00 | 0.121261E+12 | 0.121239E+12 | 56275.49 | 15-NOV-16:20 | 56275.49 | 0.00 |
December | 0.00 | 0.00 | 0.155227E+12 | 0.155222E+12 | 69826.01 | 04-DEC-16:20 | 69826.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128500E+13 | 0.127546E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.543361E+10 | 0.543358E+10 | 14825.06 | 14825.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203456E+12 | 0.201079E+12 | 83926.86 | 83926.86 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 96147635.28 | 96147635.28 | 1264.02 | 12-JAN-16:40 | 1264.02 | 0.00 |
February | 0.00 | 0.00 | 0.328890E+10 | 0.328890E+10 | 3629.23 | 28-FEB-17:00 | 3629.23 | 0.00 |
March | 0.00 | 0.00 | 0.110070E+11 | 0.109859E+11 | 6368.10 | 31-MAR-23:20 | 6368.10 | 0.00 |
April | 0.00 | 0.00 | 0.169121E+11 | 0.169091E+11 | 7947.10 | 09-APR-17:57 | 7947.10 | 0.00 |
May | 0.00 | 0.00 | 0.445542E+10 | 0.442072E+10 | 3726.44 | 31-MAY-23:40 | 3726.44 | 0.00 |
June | 0.00 | 0.00 | 0.100764E+11 | 0.989549E+10 | 5601.74 | 30-JUN-23:40 | 5601.74 | 0.00 |
July | 0.00 | 0.00 | 0.157813E+11 | 0.154688E+11 | 7560.96 | 31-JUL-24:00 | 7522.35 | 0.00 |
August | 0.00 | 0.00 | 0.203241E+11 | 0.200867E+11 | 8474.26 | 04-AUG-18:40 | 8474.26 | 0.00 |
September | 0.00 | 0.00 | 0.461874E+10 | 0.448911E+10 | 3038.18 | 04-SEP-17:42 | 3038.18 | 0.00 |
October | 0.00 | 0.00 | 0.737969E+10 | 0.734931E+10 | 4680.70 | 31-OCT-23:20 | 4680.70 | 0.00 |
November | 0.00 | 0.00 | 0.103265E+11 | 0.103244E+11 | 5503.03 | 15-NOV-16:20 | 5503.03 | 0.00 |
December | 0.00 | 0.00 | 0.135386E+11 | 0.135381E+11 | 6636.26 | 04-DEC-16:20 | 6636.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117805E+12 | 0.116853E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 96147635.28 | 96147635.28 | 1264.02 | 1264.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203241E+11 | 0.200867E+11 | 8474.26 | 8474.26 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 104830.60 | 1925048.11 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 89475.01 | 1536938.75 | 14-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24791.89 | 1349036.32 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4732.34 | 1147875.06 | 17-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 455.48 | 290462.63 | 11-MAY-13:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 70.89 | 266980.70 | 13-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 3.30 | 02-JUL-23:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.75 | 6715.82 | 31-AUG-11:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 127.89 | 95519.61 | 28-SEP-10:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3717.41 | 1180245.45 | 30-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14581.55 | 1271376.51 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 78544.14 | 1578205.58 | 11-DEC-05:01 |
Annual Sum or Average | 0.00 | 26502.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 3.30 | ||
Maximum of Months | 0.00 | 0.00 | 104830.60 | 1925048.11 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 84.90 | 6051.85 | 11-JAN-16:50 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 261.49 | 28978.45 | 22-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 25184.93 | 1456153.93 | 15-MAR-14:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24720.21 | 567293.73 | 19-APR-15:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82086.29 | 1342058.50 | 10-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 333724.85 | 2082972.73 | 27-JUN-07:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 548567.49 | 2830692.47 | 05-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 462173.16 | 2542021.81 | 15-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 213381.30 | 2261495.91 | 21-SEP-12:52 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38401.15 | 835702.04 | 11-OCT-14:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9337.35 | 333603.93 | 16-NOV-13:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 241.31 | 40222.44 | 01-DEC-07:13 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 146030.55 | 0.00 | ||||
Minimum of Months | 84.90 | 6051.85 | 0.00 | 0.00 | ||
Maximum of Months | 548567.49 | 2830692.47 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.83 | 2524.20 | 11-JAN-16:50 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 159.38 | 25537.99 | 22-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 24541.90 | 1286687.90 | 15-MAR-14:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23953.39 | 564599.76 | 19-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80742.57 | 1382157.36 | 10-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 332046.15 | 2995747.60 | 27-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 546548.93 | 3282820.77 | 17-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 463827.25 | 3381110.40 | 15-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 213357.30 | 2921040.14 | 14-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 37573.62 | 837961.74 | 11-OCT-14:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8654.07 | 339755.82 | 16-NOV-13:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 115.73 | 52466.15 | 01-DEC-07:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 145476.39 | 0.00 | ||||
Minimum of Months | 7.83 | 2524.20 | 0.00 | 0.00 | ||
Maximum of Months | 546548.93 | 3381110.40 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11601.91 | 30167.91 | 12-JAN-16:40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 40952.58 | 65601.86 | 28-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 101659.21 | 1072809.82 | 15-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 126425.30 | 708120.08 | 08-APR-13:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57064.49 | 707842.00 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 305419.24 | 1319261.78 | 27-JUN-14:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 810782.51 | 1671759.99 | 21-JUL-02:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 855883.62 | 1752281.09 | 13-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 106823.43 | 823578.63 | 16-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 61568.34 | 456508.56 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83089.00 | 348795.83 | 05-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 97440.33 | 185719.46 | 01-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 223768.20 | 0.00 | ||||
Minimum of Months | 11601.91 | 30167.91 | 0.00 | 0.00 | ||
Maximum of Months | 855883.62 | 1752281.09 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 15565.49 | 55761.21 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 15883.48 | 55957.89 | 15-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16653.05 | 55779.51 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14992.80 | 54071.93 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14631.73 | 51559.61 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14076.09 | 48363.93 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12326.75 | 45521.93 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13253.10 | 44047.86 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12640.60 | 45462.23 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13239.12 | 48280.13 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14277.44 | 51375.07 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14571.55 | 54008.75 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 14333.73 | ||||
Minimum of Months | 0.00 | 0.00 | 12326.75 | 44047.86 | ||
Maximum of Months | 0.00 | 0.00 | 16653.05 | 55957.89 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8.79 | 15185.59 | 11-JAN-13:40 | 791.25 | 131345.16 | 24-JAN-07:03 |
February | 13.18 | 35031.95 | 22-FEB-15:40 | 1350.07 | 144048.12 | 22-FEB-06:01 |
March | 30160.85 | 2361943.00 | 14-MAR-12:50 | 3843.88 | 134194.80 | 01-MAR-15:40 |
April | 23027.34 | 639105.21 | 19-APR-15:20 | 3145.80 | 127391.17 | 03-APR-08:30 |
May | 90559.84 | 2643910.76 | 10-MAY-14:05 | 1203.51 | 96955.51 | 01-MAY-06:50 |
June | 554003.41 | 5424218.53 | 27-JUN-07:40 | 576.45 | 79503.79 | 14-JUN-13:00 |
July | 1110667.70 | 6037121.13 | 05-JUL-16:00 | 283.49 | 44432.12 | 07-JUL-07:00 |
August | 804475.18 | 5886693.55 | 14-AUG-10:05 | 957.13 | 66790.61 | 12-AUG-22:50 |
September | 325295.37 | 4499093.94 | 15-SEP-11:00 | 550.05 | 70306.19 | 06-SEP-08:50 |
October | 40339.12 | 946306.03 | 11-OCT-14:40 | 1949.93 | 111968.00 | 17-OCT-16:50 |
November | 7557.32 | 377302.48 | 16-NOV-13:10 | 4444.86 | 130469.92 | 28-NOV-16:10 |
December | 9.34 | 16115.84 | 14-DEC-14:50 | 1475.60 | 139195.14 | 29-DEC-07:03 |
Annual Sum or Average | 251122.51 | 1712.23 | ||||
Minimum of Months | 8.79 | 15185.59 | 283.49 | 44432.12 | ||
Maximum of Months | 1110667.70 | 6037121.13 | 4444.86 | 144048.12 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.281282E+10 | 0.31 | 11967.39 | 03-JAN-06:01 | 1.35 |
February | 0.285544E+10 | 0.32 | 11967.39 | 03-FEB-06:01 | 1.35 |
March | 0.575392E+10 | 0.41 | 14279.79 | 15-MAR-14:20 | 1.49 |
April | 0.762825E+10 | 0.48 | 15970.50 | 24-APR-14:50 | 1.61 |
May | 0.795645E+10 | 0.49 | 16248.37 | 17-MAY-05:02 | 1.62 |
June | 0.128400E+11 | 0.67 | 21058.33 | 12-JUN-04:12 | 1.90 |
July | 0.160289E+11 | 0.79 | 21058.33 | 17-JUL-04:22 | 1.90 |
August | 0.162295E+11 | 0.81 | 21058.33 | 03-AUG-13:13 | 1.91 |
September | 0.886544E+10 | 0.52 | 21058.33 | 14-SEP-04:12 | 1.90 |
October | 0.634007E+10 | 0.42 | 14982.15 | 10-OCT-15:40 | 1.54 |
November | 0.496353E+10 | 0.37 | 11351.02 | 27-NOV-11:00 | 1.30 |
December | 0.368853E+10 | 0.33 | 11967.39 | 07-DEC-06:01 | 1.35 |
Annual Sum or Average | 0.959628E+11 | 0.49 | |||
Minimum of Months | 0.281282E+10 | 0.31 | 11351.02 | 1.30 | |
Maximum of Months | 0.162295E+11 | 0.81 | 21058.33 | 1.91 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.259210E+11 | 0.34 | 52999.09 | 02-JAN-04:01 | 0.87 |
February | 0.231590E+11 | 0.33 | 52999.09 | 06-FEB-05:01 | 0.87 |
March | 0.318961E+11 | 0.34 | 92884.68 | 15-MAR-14:30 | 1.19 |
April | 0.375049E+11 | 0.35 | 128988.64 | 05-APR-05:02 | 1.47 |
May | 0.584056E+11 | 0.43 | 116839.06 | 23-MAY-14:30 | 1.38 |
June | 0.860121E+11 | 0.54 | 196180.48 | 26-JUN-05:02 | 1.90 |
July | 0.973406E+11 | 0.56 | 196180.48 | 17-JUL-04:12 | 1.90 |
August | 0.951701E+11 | 0.56 | 196180.48 | 07-AUG-04:12 | 1.90 |
September | 0.620371E+11 | 0.44 | 163788.09 | 14-SEP-05:03 | 1.69 |
October | 0.360519E+11 | 0.33 | 89242.22 | 12-OCT-14:30 | 1.16 |
November | 0.252497E+11 | 0.30 | 138470.56 | 03-NOV-05:02 | 1.54 |
December | 0.241563E+11 | 0.32 | 52999.09 | 11-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.602904E+12 | 0.41 | |||
Minimum of Months | 0.231590E+11 | 0.30 | 52999.09 | 0.87 | |
Maximum of Months | 0.973406E+11 | 0.56 | 196180.48 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.335999E+10 | 0.42 | 5019.64 | 02-JAN-04:01 | 0.80 |
February | 0.306673E+10 | 0.42 | 5019.64 | 01-FEB-05:11 | 0.80 |
March | 0.318846E+10 | 0.37 | 10341.57 | 15-MAR-14:20 | 1.20 |
April | 0.310946E+10 | 0.34 | 8925.82 | 21-APR-15:20 | 1.11 |
May | 0.501386E+10 | 0.39 | 12302.14 | 31-MAY-15:50 | 1.34 |
June | 0.850764E+10 | 0.51 | 20031.37 | 12-JUN-04:12 | 1.82 |
July | 0.101574E+11 | 0.55 | 21553.33 | 21-JUL-05:02 | 1.90 |
August | 0.940128E+10 | 0.53 | 21553.33 | 07-AUG-04:12 | 1.90 |
September | 0.536997E+10 | 0.40 | 14796.47 | 21-SEP-16:00 | 1.50 |
October | 0.288890E+10 | 0.31 | 8641.24 | 11-OCT-16:00 | 1.08 |
November | 0.235096E+10 | 0.32 | 5019.64 | 13-NOV-05:11 | 0.80 |
December | 0.315996E+10 | 0.40 | 5019.64 | 04-DEC-04:01 | 0.80 |
Annual Sum or Average | 0.595746E+11 | 0.41 | |||
Minimum of Months | 0.235096E+10 | 0.31 | 5019.64 | 0.80 | |
Maximum of Months | 0.101574E+11 | 0.55 | 21553.33 | 1.90 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207956E+10 | 0.31 | 11720.32 | 02-JAN-07:03 | 1.92 |
February | 0.192139E+10 | 0.31 | 11720.32 | 01-FEB-07:05 | 1.93 |
March | 0.480676E+10 | 0.45 | 11720.32 | 01-MAR-07:03 | 1.94 |
April | 0.927541E+10 | 0.67 | 11720.32 | 01-APR-06:05 | 1.93 |
May | 0.116105E+11 | 0.77 | 11720.32 | 01-MAY-06:05 | 1.93 |
June | 0.969575E+10 | 0.65 | 11720.32 | 01-JUN-06:10 | 1.92 |
July | 0.802382E+10 | 0.51 | 11720.32 | 01-JUL-06:10 | 1.92 |
August | 0.107407E+11 | 0.69 | 11720.32 | 01-AUG-06:10 | 1.91 |
September | 0.109285E+11 | 0.74 | 11720.32 | 01-SEP-06:10 | 1.92 |
October | 0.124746E+11 | 0.81 | 11720.32 | 02-OCT-06:05 | 1.93 |
November | 0.116675E+11 | 0.79 | 11720.32 | 01-NOV-06:05 | 1.93 |
December | 0.436914E+10 | 0.41 | 11720.32 | 01-DEC-07:10 | 1.93 |
Annual Sum or Average | 0.975937E+11 | 0.60 | |||
Minimum of Months | 0.192139E+10 | 0.31 | 11720.32 | 1.91 | |
Maximum of Months | 0.124746E+11 | 0.81 | 11720.32 | 1.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110676E+12 | 1.38 | 41321.86 | 01-JAN-00:05 | 1.38 |
February | 0.999658E+11 | 1.38 | 41321.86 | 01-FEB-00:03 | 1.38 |
March | 0.110676E+12 | 1.38 | 41321.86 | 01-MAR-00:10 | 1.39 |
April | 0.107106E+12 | 1.38 | 41321.86 | 01-APR-00:10 | 1.38 |
May | 0.110676E+12 | 1.38 | 41321.86 | 01-MAY-00:05 | 1.38 |
June | 0.107106E+12 | 1.37 | 41321.86 | 01-JUN-00:10 | 1.38 |
July | 0.110676E+12 | 1.37 | 41321.86 | 01-JUL-00:10 | 1.38 |
August | 0.110676E+12 | 1.37 | 41321.86 | 01-AUG-00:10 | 1.37 |
September | 0.107106E+12 | 1.38 | 41321.86 | 01-SEP-00:10 | 1.38 |
October | 0.110676E+12 | 1.38 | 41321.86 | 01-OCT-00:10 | 1.38 |
November | 0.107106E+12 | 1.38 | 41321.86 | 01-NOV-00:10 | 1.38 |
December | 0.110676E+12 | 1.39 | 41321.86 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.130313E+13 | 1.38 | |||
Minimum of Months | 0.999658E+11 | 1.37 | 41321.86 | 1.37 | |
Maximum of Months | 0.110676E+12 | 1.39 | 41321.86 | 1.39 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148130E+10 | 0.94 | 553.05 | 01-JAN-00:03 | 0.94 |
February | 0.133795E+10 | 0.94 | 553.05 | 01-FEB-00:03 | 0.95 |
March | 0.148130E+10 | 0.94 | 553.05 | 01-MAR-00:10 | 0.94 |
April | 0.143352E+10 | 0.94 | 553.05 | 01-APR-00:10 | 0.94 |
May | 0.148130E+10 | 0.94 | 553.05 | 01-MAY-00:05 | 0.94 |
June | 0.143352E+10 | 0.94 | 553.05 | 01-JUN-00:10 | 0.94 |
July | 0.148130E+10 | 0.94 | 553.05 | 01-JUL-00:10 | 0.94 |
August | 0.148130E+10 | 0.94 | 553.05 | 01-AUG-00:05 | 0.94 |
September | 0.143352E+10 | 0.94 | 553.05 | 01-SEP-00:10 | 0.94 |
October | 0.148130E+10 | 0.94 | 553.05 | 01-OCT-00:10 | 0.94 |
November | 0.143352E+10 | 0.94 | 553.05 | 01-NOV-00:10 | 0.94 |
December | 0.148130E+10 | 0.94 | 553.05 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.174411E+11 | 0.94 | |||
Minimum of Months | 0.133795E+10 | 0.94 | 553.05 | 0.94 | |
Maximum of Months | 0.148130E+10 | 0.94 | 553.05 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142085E+11 | 0.94 | 5304.86 | 01-JAN-00:03 | 0.94 |
February | 0.128335E+11 | 0.94 | 5304.86 | 01-FEB-00:07 | 0.95 |
March | 0.142085E+11 | 0.94 | 5304.86 | 01-MAR-00:10 | 0.94 |
April | 0.137502E+11 | 0.94 | 5304.86 | 01-APR-00:20 | 0.94 |
May | 0.142085E+11 | 0.94 | 5304.86 | 01-MAY-00:05 | 0.94 |
June | 0.137502E+11 | 0.94 | 5304.86 | 01-JUN-00:20 | 0.94 |
July | 0.142085E+11 | 0.94 | 5304.86 | 01-JUL-00:10 | 0.94 |
August | 0.142085E+11 | 0.94 | 5304.86 | 01-AUG-00:05 | 0.94 |
September | 0.137502E+11 | 0.94 | 5304.86 | 01-SEP-00:10 | 0.94 |
October | 0.142085E+11 | 0.94 | 5304.86 | 01-OCT-00:10 | 0.94 |
November | 0.137502E+11 | 0.94 | 5304.86 | 01-NOV-00:10 | 0.94 |
December | 0.142085E+11 | 0.94 | 5304.86 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.167294E+12 | 0.94 | |||
Minimum of Months | 0.128335E+11 | 0.94 | 5304.86 | 0.94 | |
Maximum of Months | 0.142085E+11 | 0.94 | 5304.86 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144520E+10 | 0.94 | 539.58 | 01-JAN-00:03 | 0.94 |
February | 0.130534E+10 | 0.94 | 539.58 | 01-FEB-00:03 | 0.95 |
March | 0.144520E+10 | 0.94 | 539.58 | 01-MAR-00:10 | 0.94 |
April | 0.139858E+10 | 0.94 | 539.58 | 01-APR-00:10 | 0.94 |
May | 0.144520E+10 | 0.94 | 539.58 | 01-MAY-00:05 | 0.94 |
June | 0.139858E+10 | 0.94 | 539.58 | 01-JUN-00:10 | 0.94 |
July | 0.144520E+10 | 0.94 | 539.58 | 01-JUL-00:10 | 0.94 |
August | 0.144520E+10 | 0.94 | 539.58 | 01-AUG-00:05 | 0.94 |
September | 0.139858E+10 | 0.94 | 539.58 | 01-SEP-00:10 | 0.94 |
October | 0.144520E+10 | 0.94 | 539.58 | 01-OCT-00:10 | 0.94 |
November | 0.139858E+10 | 0.94 | 539.58 | 01-NOV-00:10 | 0.94 |
December | 0.144520E+10 | 0.94 | 539.58 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.170161E+11 | 0.94 | |||
Minimum of Months | 0.130534E+10 | 0.94 | 539.58 | 0.94 | |
Maximum of Months | 0.144520E+10 | 0.94 | 539.58 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 40096375.47 | 36447605.31 | 1239.38 | 09-JAN-06:02 | 1126.60 | 1126.60 | 48.35 | 10.62 |
February | 28798703.50 | 26178021.48 | 1245.05 | 06-FEB-05:01 | 1131.75 | 1131.75 | 47.54 | 10.65 |
March | 5722222.37 | 5201500.13 | 441.39 | 07-MAR-06:01 | 401.22 | 401.22 | 45.52 | 6.75 |
April | 680456.77 | 618535.21 | 399.05 | 17-APR-05:01 | 362.74 | 362.74 | 39.48 | 6.46 |
May | 59506.79 | 54091.67 | 19.92 | 11-MAY-13:20 | 18.10 | 18.10 | 30.21 | 1.34 |
June | 10656.13 | 9686.43 | 16.72 | 13-JUN-11:05 | 15.20 | 15.20 | 28.99 | 1.20 |
July | 0.06 | 0.05 | 0.00 | 02-JUL-23:00 | 0.00 | 0.00 | 29.62 | 0.00 |
August | 58.14 | 52.85 | 0.19 | 31-AUG-11:05 | 0.18 | 0.18 | 29.58 | 0.03 |
September | 10766.35 | 9786.61 | 3.68 | 28-SEP-10:00 | 3.34 | 3.34 | 27.88 | 0.42 |
October | 561565.42 | 510462.96 | 402.71 | 30-OCT-05:01 | 366.07 | 366.07 | 38.48 | 6.49 |
November | 2423620.56 | 2203071.09 | 413.57 | 24-NOV-06:01 | 375.94 | 375.94 | 43.75 | 6.55 |
December | 23952554.70 | 21772872.22 | 1221.92 | 11-DEC-05:01 | 1110.72 | 1110.72 | 46.28 | 10.57 |
Annual Sum or Average | 0.102316E+09 | 93005686.00 | ||||||
Minimum of Months | 0.06 | 0.05 | 0.00 | 0.00 | 0.00 | 27.88 | 0.00 | |
Maximum of Months | 40096375.47 | 36447605.31 | 1245.05 | 1131.75 | 1131.75 | 48.35 | 10.65 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 14041.42 | 12763.65 | 1.40 | 11-JAN-16:10 | 1.27 | 1.27 | 6.70 | 0.38 |
February | 49164.21 | 44690.27 | 2.92 | 22-FEB-17:00 | 2.66 | 2.66 | 6.70 | 0.73 |
March | 43845418.71 | 39855485.61 | 2039.73 | 15-MAR-13:30 | 1854.11 | 1854.11 | 6.71 | 34.45 |
April | 14493508.50 | 13174599.23 | 278.70 | 20-APR-13:20 | 253.34 | 253.34 | 6.70 | 13.80 |
May | 0.102542E+09 | 93210637.73 | 1549.55 | 26-MAY-15:00 | 1408.54 | 1408.54 | 6.71 | 30.59 |
June | 0.650271E+09 | 0.591097E+09 | 9985.12 | 27-JUN-05:03 | 9076.47 | 9076.47 | 9.91 | 66.10 |
July | 0.126057E+10 | 0.114586E+10 | 9986.54 | 29-JUL-05:03 | 9077.76 | 9077.76 | 10.44 | 66.10 |
August | 0.118685E+10 | 0.107885E+10 | 10240.93 | 03-AUG-13:13 | 9309.00 | 9309.00 | 10.20 | 66.76 |
September | 0.470663E+09 | 0.427832E+09 | 10249.83 | 21-SEP-12:52 | 9317.09 | 9317.09 | 9.40 | 66.78 |
October | 58836777.13 | 53482630.41 | 1491.47 | 11-OCT-14:30 | 1355.75 | 1355.75 | 6.71 | 30.08 |
November | 4983524.15 | 4530023.46 | 192.78 | 16-NOV-13:05 | 175.23 | 175.23 | 6.70 | 11.46 |
December | 36039.98 | 32760.34 | 9.51 | 01-DEC-07:13 | 8.64 | 8.64 | 6.70 | 1.85 |
Annual Sum or Average | 0.379315E+10 | 0.344798E+10 | ||||||
Minimum of Months | 14041.42 | 12763.65 | 1.40 | 1.27 | 1.27 | 6.70 | 0.38 | |
Maximum of Months | 0.126057E+10 | 0.114586E+10 | 10249.83 | 9317.09 | 9317.09 | 10.44 | 66.78 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.227539E+09 | 0.206833E+09 | 3881.22 | 02-JAN-07:03 | 3528.03 | 3528.03 | 6.71 | 34.68 |
February | 0.271957E+09 | 0.247209E+09 | 3881.22 | 03-FEB-07:03 | 3528.03 | 3528.03 | 6.72 | 34.68 |
March | 0.182215E+10 | 0.165633E+10 | 3881.22 | 01-MAR-07:03 | 3528.03 | 3528.03 | 6.73 | 34.68 |
April | 0.222897E+10 | 0.202613E+10 | 3881.22 | 01-APR-08:00 | 3528.03 | 3528.03 | 6.73 | 34.68 |
May | 0.376835E+10 | 0.342543E+10 | 3881.22 | 01-MAY-06:33 | 3528.03 | 3528.03 | 6.77 | 34.68 |
June | 0.638380E+10 | 0.580287E+10 | 3881.22 | 01-JUN-04:12 | 3528.03 | 3528.03 | 8.18 | 34.68 |
July | 0.851042E+10 | 0.773597E+10 | 3881.22 | 01-JUL-04:12 | 3528.03 | 3528.03 | 7.86 | 34.68 |
August | 0.828194E+10 | 0.752829E+10 | 3881.22 | 01-AUG-00:20 | 3528.03 | 3528.03 | 6.81 | 34.68 |
September | 0.498538E+10 | 0.453171E+10 | 3881.22 | 01-SEP-04:12 | 3528.03 | 3528.03 | 7.58 | 34.68 |
October | 0.253464E+10 | 0.230399E+10 | 3881.22 | 01-OCT-12:55 | 3528.03 | 3528.03 | 6.77 | 34.68 |
November | 0.194475E+10 | 0.176778E+10 | 3881.22 | 01-NOV-07:10 | 3528.03 | 3528.03 | 6.97 | 34.68 |
December | 0.370074E+09 | 0.336398E+09 | 3881.22 | 01-DEC-07:12 | 3528.03 | 3528.03 | 6.84 | 34.68 |
Annual Sum or Average | 0.413300E+11 | 0.375689E+11 | ||||||
Minimum of Months | 0.227539E+09 | 0.206833E+09 | 3881.22 | 3528.03 | 3528.03 | 6.71 | 34.68 | |
Maximum of Months | 0.851042E+10 | 0.773597E+10 | 3881.22 | 3528.03 | 3528.03 | 8.18 | 34.68 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 19794230.14 | 17992955.20 | 3881.22 | 14-MAR-12:50 | 3528.03 | 3528.03 | 15.15 | 17.34 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 38424093.81 | 34927501.27 | 3881.22 | 10-MAY-14:05 | 3528.03 | 3528.03 | 11.30 | 34.68 |
June | 0.928970E+09 | 0.844434E+09 | 3881.22 | 01-JUN-14:40 | 3528.03 | 3528.03 | 15.29 | 17.34 |
July | 0.201032E+10 | 0.182738E+10 | 3881.22 | 03-JUL-12:05 | 3528.03 | 3528.03 | 11.36 | 34.68 |
August | 0.147580E+10 | 0.134150E+10 | 3881.22 | 01-AUG-14:05 | 3528.03 | 3528.03 | 15.25 | 17.34 |
September | 0.465048E+09 | 0.422729E+09 | 3881.22 | 08-SEP-12:50 | 3528.03 | 3528.03 | 15.56 | 17.34 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.84 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 7.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
Annual Sum or Average | 0.493835E+10 | 0.448896E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.201032E+10 | 0.182738E+10 | 3881.22 | 3528.03 | 3528.03 | 15.56 | 34.68 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-JAN-00:03 | 3420.18 | 3420.18 | 18.49 | 15.87 |
February | 0.910241E+10 | 0.827409E+10 | 3762.57 | 01-FEB-00:03 | 3420.18 | 3420.18 | 18.87 | 15.87 |
March | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-MAR-00:10 | 3420.18 | 3420.18 | 19.65 | 15.87 |
April | 0.975258E+10 | 0.886510E+10 | 3762.57 | 01-APR-00:10 | 3420.18 | 3420.18 | 20.33 | 15.87 |
May | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-MAY-00:05 | 3420.18 | 3420.18 | 18.91 | 15.87 |
June | 0.975258E+10 | 0.886510E+10 | 3762.57 | 01-JUN-00:10 | 3420.18 | 3420.18 | 19.41 | 15.87 |
July | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-JUL-00:10 | 3420.18 | 3420.18 | 20.05 | 15.87 |
August | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-AUG-00:05 | 3420.18 | 3420.18 | 30.98 | 15.87 |
September | 0.975258E+10 | 0.886510E+10 | 3762.57 | 01-SEP-00:10 | 3420.18 | 3420.18 | 18.90 | 15.87 |
October | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-OCT-00:10 | 3420.18 | 3420.18 | 19.28 | 15.87 |
November | 0.975258E+10 | 0.886510E+10 | 3762.57 | 01-NOV-00:10 | 3420.18 | 3420.18 | 19.87 | 15.87 |
December | 0.100777E+11 | 0.916060E+10 | 3762.57 | 01-DEC-00:10 | 3420.18 | 3420.18 | 20.18 | 15.87 |
Annual Sum or Average | 0.118656E+12 | 0.107859E+12 | ||||||
Minimum of Months | 0.910241E+10 | 0.827409E+10 | 3762.57 | 3420.18 | 3420.18 | 18.49 | 15.87 | |
Maximum of Months | 0.100777E+11 | 0.916060E+10 | 3762.57 | 3420.18 | 3420.18 | 30.98 | 15.87 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.88 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.79 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.93 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.88 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.25 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.16 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.32 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.47 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.42 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.09 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.22 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.98 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.79 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.47 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.873805E+09 | 0.794289E+09 | 14906.94 | 11-JAN-13:40 | 13550.41 | 13550.41 | 21.16 | 61.04 |
February | 0.104137E+10 | 0.946603E+09 | 14907.78 | 22-FEB-15:40 | 13551.17 | 13551.17 | 21.24 | 61.04 |
March | 0.706386E+10 | 0.642104E+10 | 29914.78 | 14-MAR-12:50 | 27192.53 | 27192.53 | 25.73 | 122.07 |
April | 0.856279E+10 | 0.778358E+10 | 14933.18 | 19-APR-15:20 | 13574.26 | 13574.26 | 23.61 | 61.04 |
May | 0.145500E+11 | 0.132260E+11 | 29928.63 | 10-MAY-14:05 | 27205.13 | 27205.13 | 26.28 | 122.07 |
June | 0.278039E+11 | 0.252737E+11 | 30008.18 | 27-JUN-07:20 | 27277.43 | 27277.43 | 30.96 | 122.07 |
July | 0.401771E+11 | 0.365210E+11 | 30008.18 | 05-JUL-09:50 | 27277.43 | 27277.43 | 29.98 | 122.07 |
August | 0.370774E+11 | 0.337034E+11 | 30008.18 | 07-AUG-12:05 | 27277.43 | 27277.43 | 29.61 | 122.07 |
September | 0.208131E+11 | 0.189191E+11 | 30008.18 | 15-SEP-10:40 | 27277.43 | 27277.43 | 29.59 | 122.07 |
October | 0.973318E+10 | 0.884746E+10 | 14946.13 | 11-OCT-14:40 | 13586.03 | 13586.03 | 24.81 | 61.04 |
November | 0.746810E+10 | 0.678850E+10 | 14922.16 | 16-NOV-13:10 | 13564.25 | 13564.25 | 22.58 | 61.04 |
December | 0.142115E+10 | 0.129183E+10 | 14906.98 | 14-DEC-14:50 | 13550.45 | 13550.45 | 21.16 | 61.04 |
Annual Sum or Average | 0.176586E+12 | 0.160516E+12 | ||||||
Minimum of Months | 0.873805E+09 | 0.794289E+09 | 14906.94 | 13550.41 | 13550.41 | 21.16 | 61.04 | |
Maximum of Months | 0.401771E+11 | 0.365210E+11 | 30008.18 | 27277.43 | 27277.43 | 30.96 | 122.07 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 32.86 | 32.86 | 104830.60 | 1925048.11 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 39.58 | 39.58 | 89475.01 | 1536938.75 | 14-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.16 | 27.16 | 24791.89 | 1349036.32 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28.41 | 28.41 | 4732.34 | 1147875.06 | 17-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.44 | 28.44 | 455.48 | 290462.63 | 11-MAY-13:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.98 | 28.98 | 70.89 | 266980.70 | 13-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.62 | 29.62 | 0.00 | 3.30 | 02-JUL-23:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.62 | 29.62 | 0.75 | 6715.82 | 31-AUG-11:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.54 | 29.54 | 127.89 | 95519.61 | 28-SEP-10:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.33 | 26.33 | 3717.41 | 1180245.45 | 30-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.43 | 26.43 | 14581.55 | 1271376.51 | 25-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.45 | 25.45 | 78544.14 | 1578205.58 | 11-DEC-05:01 |
Annual Sum or Average | 0.00 | 26502.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.45 | 25.45 | 0.00 | 3.30 | ||
Maximum of Months | 0.00 | 0.00 | 39.58 | 39.58 | 104830.60 | 1925048.11 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 84.90 | 6051.85 | 11-JAN-16:50 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 261.49 | 28978.45 | 22-FEB-17:00 | 6.90 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 25184.93 | 1456153.93 | 15-MAR-14:05 | 11.71 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24720.21 | 567293.73 | 19-APR-15:10 | 10.60 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82086.29 | 1342058.50 | 10-MAY-14:50 | 15.95 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 333724.85 | 2082972.73 | 27-JUN-07:40 | 13.87 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 548567.49 | 2830692.47 | 05-JUL-16:00 | 16.46 | 8.07 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 462173.16 | 2542021.81 | 15-AUG-05:03 | 15.46 | 7.07 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 213381.30 | 2261495.91 | 21-SEP-12:52 | 14.49 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 38401.15 | 835702.04 | 11-OCT-14:30 | 12.45 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9337.35 | 333603.93 | 16-NOV-13:10 | 8.99 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 241.31 | 40222.44 | 01-DEC-07:13 | 6.98 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 146030.55 | 0.00 | ||||||
Minimum of Months | 84.90 | 6051.85 | 6.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 548567.49 | 2830692.47 | 16.46 | 8.07 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.83 | 2524.20 | 11-JAN-16:50 | 8.55 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 159.38 | 25537.99 | 22-FEB-17:00 | 15.10 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 24541.90 | 1286687.90 | 15-MAR-14:20 | 16.28 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23953.39 | 564599.76 | 19-APR-15:00 | 19.09 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80742.57 | 1382157.36 | 10-MAY-14:50 | 17.68 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 332046.15 | 2995747.60 | 27-JUN-05:03 | 17.54 | 11.83 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 546548.93 | 3282820.77 | 17-JUL-05:02 | 18.58 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 463827.25 | 3381110.40 | 15-AUG-04:12 | 18.93 | 12.49 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 213357.30 | 2921040.14 | 14-SEP-05:03 | 17.26 | 11.71 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 37573.62 | 837961.74 | 11-OCT-14:30 | 13.35 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8654.07 | 339755.82 | 16-NOV-13:05 | 13.78 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 115.73 | 52466.15 | 01-DEC-07:12 | 13.54 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 145476.39 | 0.00 | ||||||
Minimum of Months | 7.83 | 2524.20 | 8.55 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 546548.93 | 3381110.40 | 19.09 | 12.49 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11601.91 | 30167.91 | 12-JAN-16:40 | 18.88 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 40952.58 | 65601.86 | 28-FEB-17:00 | 19.52 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 101659.21 | 1072809.82 | 15-MAR-14:00 | 37.50 | 29.09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 126425.30 | 708120.08 | 08-APR-13:05 | 31.06 | 23.63 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57064.49 | 707842.00 | 10-MAY-15:00 | 31.05 | 27.39 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 305419.24 | 1319261.78 | 27-JUN-14:10 | 41.80 | 30.86 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 810782.51 | 1671759.99 | 21-JUL-02:50 | 47.90 | 33.95 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 855883.62 | 1752281.09 | 13-AUG-15:00 | 49.29 | 35.14 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 106823.43 | 823578.63 | 16-SEP-14:30 | 33.11 | 28.56 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 61568.34 | 456508.56 | 11-OCT-15:00 | 26.57 | 23.33 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83089.00 | 348795.83 | 05-NOV-14:00 | 24.64 | 20.75 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 97440.33 | 185719.46 | 01-DEC-11:00 | 21.70 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 223768.20 | 0.00 | ||||||
Minimum of Months | 11601.91 | 30167.91 | 18.88 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 855883.62 | 1752281.09 | 49.29 | 35.14 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.99 | 57.99 | 15565.49 | 55761.21 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.39 | 57.39 | 15883.48 | 55957.89 | 15-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.39 | 57.39 | 16653.05 | 55779.51 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.46 | 57.46 | 14992.80 | 54071.93 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.08 | 58.08 | 14631.73 | 51559.61 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.74 | 57.74 | 14076.09 | 48363.93 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.87 | 57.87 | 12326.75 | 45521.93 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.95 | 57.95 | 13253.10 | 44047.86 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 12640.60 | 45462.23 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.88 | 57.88 | 13239.12 | 48280.13 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.75 | 57.75 | 14277.44 | 51375.07 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.60 | 57.60 | 14571.55 | 54008.75 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 14333.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.39 | 57.39 | 12326.75 | 44047.86 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 16653.05 | 55957.89 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8.79 | 15185.59 | 11-JAN-13:40 | 21.16 | 20.65 | 791.25 | 131345.16 | 24-JAN-07:03 |
February | 13.18 | 35031.95 | 22-FEB-15:40 | 21.24 | 20.58 | 1350.07 | 144048.12 | 22-FEB-06:01 |
March | 30160.85 | 2361943.00 | 14-MAR-12:50 | 25.73 | 22.46 | 3843.88 | 134194.80 | 01-MAR-15:40 |
April | 23027.34 | 639105.21 | 19-APR-15:20 | 23.61 | 21.10 | 3145.80 | 127391.17 | 03-APR-08:30 |
May | 90559.84 | 2643910.76 | 10-MAY-14:05 | 26.28 | 22.80 | 1203.51 | 96955.51 | 01-MAY-06:50 |
June | 554003.41 | 5424218.53 | 27-JUN-07:40 | 31.73 | 27.03 | 576.45 | 79503.79 | 14-JUN-13:00 |
July | 1110667.70 | 6037121.13 | 05-JUL-16:00 | 32.93 | 27.36 | 283.49 | 44432.12 | 07-JUL-07:00 |
August | 804475.18 | 5886693.55 | 14-AUG-10:05 | 32.64 | 27.51 | 957.13 | 66790.61 | 12-AUG-22:50 |
September | 325295.37 | 4499093.94 | 15-SEP-11:00 | 29.92 | 25.49 | 550.05 | 70306.19 | 06-SEP-08:50 |
October | 40339.12 | 946306.03 | 11-OCT-14:40 | 24.81 | 21.10 | 1949.93 | 111968.00 | 17-OCT-16:50 |
November | 7557.32 | 377302.48 | 16-NOV-13:10 | 22.58 | 21.10 | 4444.86 | 130469.92 | 28-NOV-16:10 |
December | 9.34 | 16115.84 | 14-DEC-14:50 | 21.16 | 20.52 | 1475.60 | 139195.14 | 29-DEC-07:03 |
Annual Sum or Average | 251122.51 | 1712.23 | ||||||
Minimum of Months | 8.79 | 15185.59 | 21.16 | 20.52 | 283.49 | 44432.12 | ||
Maximum of Months | 1110667.70 | 6037121.13 | 32.93 | 27.51 | 4444.86 | 144048.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.334659E+10 | 0.00 | 11550518.54 | 0.281282E+10 | 0.00 | 0.00 |
February | 0.250194E+10 | 0.00 | 0.389478E+09 | 0.285544E+10 | 0.00 | 0.00 |
March | 0.561346E+09 | 0.00 | 0.897677E+10 | 0.575392E+10 | 0.00 | 0.00 |
April | 92137377.13 | 0.00 | 0.474962E+10 | 0.762825E+10 | 0.00 | 0.00 |
May | 9697546.79 | 0.00 | 0.185430E+11 | 0.795645E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.851655E+11 | 0.128400E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.156732E+12 | 0.160289E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.132182E+12 | 0.162295E+11 | 0.00 | 0.00 |
September | 2164065.33 | 0.00 | 0.509929E+11 | 0.886544E+10 | 0.00 | 0.00 |
October | 79476037.10 | 0.00 | 0.102865E+11 | 0.634007E+10 | 0.00 | 0.00 |
November | 0.161302E+09 | 0.00 | 0.533096E+10 | 0.496353E+10 | 0.00 | 0.00 |
December | 0.160934E+10 | 0.00 | 0.264578E+09 | 0.368853E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.836399E+10 | 0.00 | 0.473624E+12 | 0.959628E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 11550518.54 | 0.281282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.334659E+10 | 0.00 | 0.156732E+12 | 0.162295E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.215852E+12 | 0.00 | 8897611.50 | 0.259210E+11 | 0.00 | 0.00 |
February | 0.162515E+12 | 0.00 | 56474678.37 | 0.231590E+11 | 0.00 | 0.00 |
March | 0.468040E+11 | 0.00 | 0.452818E+11 | 0.318961E+11 | 0.00 | 0.00 |
April | 0.843472E+10 | 0.00 | 0.544718E+11 | 0.375049E+11 | 0.00 | 0.00 |
May | 0.103818E+10 | 0.00 | 0.167717E+12 | 0.584056E+11 | 0.00 | 0.00 |
June | 0.177616E+09 | 0.00 | 0.646351E+12 | 0.860121E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.108265E+13 | 0.973406E+11 | 0.00 | 0.00 |
August | 2441003.07 | 0.00 | 0.905340E+12 | 0.951701E+11 | 0.00 | 0.00 |
September | 0.236230E+09 | 0.00 | 0.412795E+12 | 0.620371E+11 | 0.00 | 0.00 |
October | 0.635782E+10 | 0.00 | 0.804732E+11 | 0.360519E+11 | 0.00 | 0.00 |
November | 0.261948E+11 | 0.00 | 0.157286E+11 | 0.252497E+11 | 0.00 | 0.00 |
December | 0.161285E+12 | 0.00 | 42848555.41 | 0.241563E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.628898E+12 | 0.00 | 0.341092E+13 | 0.602904E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 8897611.50 | 0.231590E+11 | 0.00 | 0.00 |
Maximum of Months | 0.215852E+12 | 0.00 | 0.108265E+13 | 0.973406E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.496334E+11 | 0.00 | 1117683.74 | 0.335999E+10 | 0.00 | 0.00 |
February | 0.412816E+11 | 0.00 | 5331679.48 | 0.306673E+10 | 0.00 | 0.00 |
March | 0.160412E+11 | 0.00 | 0.407671E+10 | 0.318846E+10 | 0.00 | 0.00 |
April | 0.368441E+10 | 0.00 | 0.150635E+10 | 0.310946E+10 | 0.00 | 0.00 |
May | 0.174463E+09 | 0.00 | 0.156220E+11 | 0.501386E+10 | 0.00 | 0.00 |
June | 3747716.35 | 0.00 | 0.699716E+11 | 0.850764E+10 | 0.00 | 0.00 |
July | 159.23 | 0.00 | 0.119770E+12 | 0.101574E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.981338E+11 | 0.940128E+10 | 0.00 | 0.00 |
September | 0.111611E+09 | 0.00 | 0.399541E+11 | 0.536997E+10 | 0.00 | 0.00 |
October | 0.356734E+10 | 0.00 | 0.445403E+10 | 0.288890E+10 | 0.00 | 0.00 |
November | 0.115383E+11 | 0.00 | 0.554335E+09 | 0.235096E+10 | 0.00 | 0.00 |
December | 0.432609E+11 | 0.00 | 4194387.81 | 0.315996E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.169297E+12 | 0.00 | 0.354053E+12 | 0.595746E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1117683.74 | 0.235096E+10 | 0.00 | 0.00 |
Maximum of Months | 0.496334E+11 | 0.00 | 0.119770E+12 | 0.101574E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.133695E+11 | 0.00 | 41389778.29 | 0.207956E+10 | 0.00 | 0.00 |
February | 0.113473E+11 | 0.00 | 38811114.69 | 0.192139E+10 | 0.00 | 0.00 |
March | 0.333298E+10 | 0.00 | 0.390107E+10 | 0.480676E+10 | 0.00 | 0.00 |
April | 0.118347E+09 | 0.00 | 0.153861E+10 | 0.927541E+10 | 0.00 | 0.00 |
May | 1076750.42 | 0.00 | 0.121745E+11 | 0.116105E+11 | 0.00 | 0.00 |
June | 396.97 | 0.00 | 0.319718E+11 | 0.969575E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.532899E+11 | 0.802382E+10 | 0.00 | 0.00 |
August | 242.49 | 0.00 | 0.564729E+11 | 0.107407E+11 | 0.00 | 0.00 |
September | 653.52 | 0.00 | 0.331419E+11 | 0.109285E+11 | 0.00 | 0.00 |
October | 3033337.42 | 0.00 | 0.555058E+10 | 0.124746E+11 | 0.00 | 0.00 |
November | 0.101905E+09 | 0.00 | 0.877442E+09 | 0.116675E+11 | 0.00 | 0.00 |
December | 0.523659E+10 | 0.00 | 6140035.17 | 0.436914E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335107E+11 | 0.00 | 0.199005E+12 | 0.975937E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 6140035.17 | 0.192139E+10 | 0.00 | 0.00 |
Maximum of Months | 0.133695E+11 | 0.00 | 0.564729E+11 | 0.124746E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.108296E+11 | 0.250425E+12 | 0.00 | 50.40 |
February | 0.00 | 0.00 | 0.153158E+11 | 0.308005E+12 | 0.00 | 75.52 |
March | 0.00 | 0.00 | 0.427223E+11 | 0.322377E+12 | 0.00 | 74.56 |
April | 0.00 | 0.00 | 0.489260E+11 | 0.325200E+12 | 0.00 | 76.48 |
May | 0.00 | 0.00 | 0.119418E+11 | 0.195952E+12 | 0.00 | 29.97 |
June | 0.00 | 0.00 | 0.214581E+12 | 0.195232E+12 | 0.00 | 15.06 |
July | 0.00 | 0.00 | 0.896825E+12 | 0.298686E+12 | 0.00 | 0.90 |
August | 0.00 | 0.00 | 0.104052E+13 | 0.329383E+12 | 0.00 | 1.63 |
September | 0.00 | 0.00 | 0.223499E+11 | 0.124892E+12 | 0.00 | 3.91 |
October | 0.00 | 0.00 | 0.135100E+11 | 0.220523E+12 | 0.00 | 39.02 |
November | 0.00 | 0.00 | 0.243824E+11 | 0.328284E+12 | 0.00 | 79.62 |
December | 0.00 | 0.00 | 0.220151E+11 | 0.378912E+12 | 0.00 | 97.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.236392E+13 | 0.327787E+13 | 0.00 | 544.26 |
Minimum of Months | 0.00 | 0.00 | 0.108296E+11 | 0.124892E+12 | 0.00 | 0.90 |
Maximum of Months | 0.00 | 0.00 | 0.104052E+13 | 0.378912E+12 | 0.00 | 97.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.393213E+10 | 0.228453E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.963887E+10 | 0.319025E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.181673E+11 | 0.476450E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238621E+11 | 0.550359E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.689225E+10 | 0.278780E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134464E+11 | 0.399314E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.208134E+11 | 0.566455E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266174E+11 | 0.662162E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.704204E+10 | 0.276893E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125680E+11 | 0.374096E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.176676E+11 | 0.455089E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.235566E+11 | 0.563674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184204E+12 | 0.515075E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.393213E+10 | 0.228453E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266174E+11 | 0.662162E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.704233E+10 | 0.158173E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.616601E+11 | 0.250093E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.154302E+12 | 0.424056E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.216783E+12 | 0.509624E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.602480E+11 | 0.257044E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125406E+12 | 0.376960E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.196904E+12 | 0.538511E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.252254E+12 | 0.630065E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.616034E+11 | 0.255176E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.106476E+12 | 0.335328E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.147654E+12 | 0.401425E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.189263E+12 | 0.482443E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157960E+13 | 0.461890E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.704233E+10 | 0.158173E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252254E+12 | 0.630065E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.125434E+09 | 0.147449E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.411803E+10 | 0.213447E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135018E+11 | 0.393996E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204490E+11 | 0.493550E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.551494E+10 | 0.250472E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124638E+11 | 0.378599E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.197697E+11 | 0.543363E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.252156E+11 | 0.633664E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.571983E+10 | 0.249967E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.903781E+10 | 0.310332E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.126122E+11 | 0.368426E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.165579E+11 | 0.446447E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145086E+12 | 0.442971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.125434E+09 | 0.147449E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252156E+11 | 0.633664E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.281282E+10 | 11550518.54 | 0.334659E+10 | 0.413478E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285544E+10 | 0.389478E+09 | 0.250194E+10 | 0.361545E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.575392E+10 | 0.897677E+10 | 0.561346E+09 | 0.144503E+11 | 1535711.07 | 0.00 | 0.00 | 0.00 |
April | 0.762825E+10 | 0.474962E+10 | 92137377.13 | 0.277888E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.795645E+10 | 0.185430E+11 | 9697546.79 | 0.145453E+09 | 239314.54 | 0.00 | 0.00 | 0.00 |
June | 0.128400E+11 | 0.851655E+11 | 0.00 | 0.139215E+09 | 0.189468E+10 | 0.00 | 0.00 | 0.00 |
July | 0.160289E+11 | 0.156732E+12 | 0.00 | 0.135390E+09 | 0.552746E+10 | 0.00 | 0.00 | 0.00 |
August | 0.162295E+11 | 0.132182E+12 | 0.00 | 0.557533E+09 | 0.221850E+10 | 0.00 | 0.00 | 0.00 |
September | 0.886544E+10 | 0.509929E+11 | 2164065.33 | 63706298.60 | 0.275864E+09 | 0.00 | 0.00 | 0.00 |
October | 0.634007E+10 | 0.102865E+11 | 79476037.10 | 0.190893E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496353E+10 | 0.533096E+10 | 0.161302E+09 | 0.580063E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368853E+10 | 0.264578E+09 | 0.160934E+10 | 0.291827E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959628E+11 | 0.473624E+12 | 0.836399E+10 | 0.132665E+12 | 0.991827E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281282E+10 | 11550518.54 | 0.00 | 63706298.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162295E+11 | 0.156732E+12 | 0.334659E+10 | 0.413478E+11 | 0.552746E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.259210E+11 | 8897611.50 | 0.215852E+12 | 0.435156E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231590E+11 | 56474678.37 | 0.162515E+12 | 0.398606E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318961E+11 | 0.452818E+11 | 0.468040E+11 | 0.236505E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375049E+11 | 0.544718E+11 | 0.843472E+10 | 0.679003E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.584056E+11 | 0.167717E+12 | 0.103818E+10 | 0.404671E+10 | 4281243.80 | 0.00 | 0.00 | 0.00 |
June | 0.860121E+11 | 0.646351E+12 | 0.177616E+09 | 0.181664E+10 | 0.187709E+11 | 0.00 | 0.00 | 0.00 |
July | 0.973406E+11 | 0.108265E+13 | 0.00 | 0.189956E+10 | 0.538306E+11 | 0.00 | 0.00 | 0.00 |
August | 0.951701E+11 | 0.905340E+12 | 2441003.07 | 0.664572E+10 | 0.210470E+11 | 0.00 | 0.00 | 0.00 |
September | 0.620371E+11 | 0.412795E+12 | 0.236230E+09 | 0.124456E+10 | 0.295558E+10 | 0.00 | 0.00 | 0.00 |
October | 0.360519E+11 | 0.804732E+11 | 0.635782E+10 | 0.395726E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252497E+11 | 0.157286E+11 | 0.261948E+11 | 0.133981E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241563E+11 | 42848555.41 | 0.161285E+12 | 0.376701E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602904E+12 | 0.341092E+13 | 0.628898E+12 | 0.170408E+13 | 0.966083E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231590E+11 | 8897611.50 | 0.00 | 0.124456E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.973406E+11 | 0.108265E+13 | 0.215852E+12 | 0.435156E+12 | 0.538306E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.335999E+10 | 1117683.74 | 0.496334E+11 | 0.446914E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306673E+10 | 5331679.48 | 0.412816E+11 | 0.406427E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318846E+10 | 0.407671E+10 | 0.160412E+11 | 0.260220E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310946E+10 | 0.150635E+10 | 0.368441E+10 | 0.910620E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.501386E+10 | 0.156220E+11 | 0.174463E+09 | 0.743275E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.850764E+10 | 0.699716E+11 | 3747716.35 | 0.223280E+09 | 0.150172E+10 | 0.00 | 0.00 | 0.00 |
July | 0.101574E+11 | 0.119770E+12 | 159.23 | 0.151318E+09 | 0.439458E+10 | 0.00 | 0.00 | 0.00 |
August | 0.940128E+10 | 0.981338E+11 | 0.00 | 0.667131E+09 | 0.155807E+10 | 0.00 | 0.00 | 0.00 |
September | 0.536997E+10 | 0.399541E+11 | 0.111611E+09 | 0.242348E+09 | 0.176646E+09 | 0.00 | 0.00 | 0.00 |
October | 0.288890E+10 | 0.445403E+10 | 0.356734E+10 | 0.614156E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235096E+10 | 0.554335E+09 | 0.115383E+11 | 0.170211E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315996E+10 | 4194387.81 | 0.432609E+11 | 0.395727E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.595746E+11 | 0.354053E+12 | 0.169297E+12 | 0.185225E+12 | 0.763102E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235096E+10 | 1117683.74 | 0.00 | 0.151318E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101574E+11 | 0.119770E+12 | 0.496334E+11 | 0.446914E+11 | 0.439458E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207956E+10 | 41389778.29 | 0.133695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192139E+10 | 38811114.69 | 0.113473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.480676E+10 | 0.390107E+10 | 0.333298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.927541E+10 | 0.153861E+10 | 0.118347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116105E+11 | 0.121745E+11 | 1076750.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.969575E+10 | 0.319718E+11 | 396.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.802382E+10 | 0.532899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107407E+11 | 0.564729E+11 | 242.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109285E+11 | 0.331419E+11 | 653.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124746E+11 | 0.555058E+10 | 3033337.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116675E+11 | 0.877442E+09 | 0.101905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.436914E+10 | 6140035.17 | 0.523659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.975937E+11 | 0.199005E+12 | 0.335107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192139E+10 | 6140035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124746E+11 | 0.564729E+11 | 0.133695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110676E+12 | 0.656980E+10 | 0.00 | 0.00 | 0.00 | 0.134881E+12 | 0.00 | 0.00 |
February | 0.999658E+11 | 0.102825E+11 | 0.00 | 0.00 | 0.00 | 0.202096E+12 | 0.00 | 0.00 |
March | 0.110676E+12 | 0.314528E+11 | 0.00 | 0.00 | 0.00 | 0.199533E+12 | 0.00 | 0.00 |
April | 0.107106E+12 | 0.364164E+11 | 0.00 | 0.00 | 0.00 | 0.204663E+12 | 0.00 | 0.00 |
May | 0.110676E+12 | 0.723110E+10 | 0.00 | 0.00 | 0.00 | 0.802036E+11 | 0.00 | 0.00 |
June | 0.107106E+12 | 0.166936E+12 | 0.00 | 0.00 | 0.00 | 0.403000E+11 | 0.00 | 0.00 |
July | 0.110676E+12 | 0.711245E+12 | 0.00 | 0.00 | 0.00 | 0.241863E+10 | 0.00 | 0.00 |
August | 0.110676E+12 | 0.826201E+12 | 0.00 | 0.00 | 0.00 | 0.437075E+10 | 0.00 | 0.00 |
September | 0.107106E+12 | 0.150678E+11 | 0.00 | 0.00 | 0.00 | 0.104563E+11 | 0.00 | 0.00 |
October | 0.110676E+12 | 0.854372E+10 | 0.00 | 0.00 | 0.00 | 0.104410E+12 | 0.00 | 0.00 |
November | 0.107106E+12 | 0.172421E+11 | 0.00 | 0.00 | 0.00 | 0.213078E+12 | 0.00 | 0.00 |
December | 0.110676E+12 | 0.150363E+11 | 0.00 | 0.00 | 0.00 | 0.260086E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.130313E+13 | 0.185223E+13 | 0.00 | 0.00 | 0.00 | 0.145650E+13 | 0.00 | 0.00 |
Minimum of Months | 0.999658E+11 | 0.656980E+10 | 0.00 | 0.00 | 0.00 | 0.241863E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110676E+12 | 0.826201E+12 | 0.00 | 0.00 | 0.00 | 0.260086E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148130E+10 | 0.312890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133795E+10 | 0.778657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148130E+10 | 0.148841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143352E+10 | 0.197920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148130E+10 | 0.558575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143352E+10 | 0.108868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148130E+10 | 0.166302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148130E+10 | 0.214771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143352E+10 | 0.570663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148130E+10 | 0.103083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143352E+10 | 0.145502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148130E+10 | 0.194012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174411E+11 | 0.150138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133795E+10 | 0.312890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148130E+10 | 0.214771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142085E+11 | 0.543361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128335E+11 | 0.494842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142085E+11 | 0.126105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137502E+11 | 0.179571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142085E+11 | 0.487521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137502E+11 | 0.101461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142085E+11 | 0.157261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142085E+11 | 0.203456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137502E+11 | 0.498360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142085E+11 | 0.871519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137502E+11 | 0.121261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142085E+11 | 0.155227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167294E+12 | 0.128500E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128335E+11 | 0.543361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142085E+11 | 0.203456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144520E+10 | 96147635.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130534E+10 | 0.328890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144520E+10 | 0.110070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139858E+10 | 0.169121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144520E+10 | 0.445542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139858E+10 | 0.100764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144520E+10 | 0.157813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144520E+10 | 0.203241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139858E+10 | 0.461874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144520E+10 | 0.737969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139858E+10 | 0.103265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144520E+10 | 0.135386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170161E+11 | 0.117805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130534E+10 | 96147635.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144520E+10 | 0.203241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.281282E+10 | 0.334659E+10 | 11550518.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285544E+10 | 0.250194E+10 | 0.389478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.575392E+10 | 0.561346E+09 | 0.897677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762825E+10 | 92137377.13 | 0.474962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.795645E+10 | 9697546.79 | 0.185430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128400E+11 | 0.00 | 0.851655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160289E+11 | 0.00 | 0.156732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162295E+11 | 0.00 | 0.132182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.886544E+10 | 2164065.33 | 0.509929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634007E+10 | 79476037.10 | 0.102865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496353E+10 | 0.161302E+09 | 0.533096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368853E+10 | 0.160934E+10 | 0.264578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959628E+11 | 0.836399E+10 | 0.473624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281282E+10 | 0.00 | 11550518.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162295E+11 | 0.334659E+10 | 0.156732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.259210E+11 | 0.215852E+12 | 8897611.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231590E+11 | 0.162515E+12 | 56474678.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318961E+11 | 0.468040E+11 | 0.452818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375049E+11 | 0.843472E+10 | 0.544718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.584056E+11 | 0.103818E+10 | 0.167717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.860121E+11 | 0.177616E+09 | 0.646351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.973406E+11 | 0.00 | 0.108265E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.951701E+11 | 2441003.07 | 0.905340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.620371E+11 | 0.236230E+09 | 0.412795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360519E+11 | 0.635782E+10 | 0.804732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252497E+11 | 0.261948E+11 | 0.157286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241563E+11 | 0.161285E+12 | 42848555.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602904E+12 | 0.628898E+12 | 0.341092E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.231590E+11 | 0.00 | 8897611.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.973406E+11 | 0.215852E+12 | 0.108265E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.335999E+10 | 0.496334E+11 | 1117683.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306673E+10 | 0.412816E+11 | 5331679.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318846E+10 | 0.160412E+11 | 0.407671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310946E+10 | 0.368441E+10 | 0.150635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.501386E+10 | 0.174463E+09 | 0.156220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.850764E+10 | 3747716.35 | 0.699716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101574E+11 | 159.23 | 0.119770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.940128E+10 | 0.00 | 0.981338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536997E+10 | 0.111611E+09 | 0.399541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288890E+10 | 0.356734E+10 | 0.445403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235096E+10 | 0.115383E+11 | 0.554335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315996E+10 | 0.432609E+11 | 4194387.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.595746E+11 | 0.169297E+12 | 0.354053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235096E+10 | 0.00 | 1117683.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101574E+11 | 0.496334E+11 | 0.119770E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.207956E+10 | 0.133695E+11 | 41389778.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192139E+10 | 0.113473E+11 | 38811114.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.480676E+10 | 0.333298E+10 | 0.390107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.927541E+10 | 0.118347E+09 | 0.153861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116105E+11 | 1076750.42 | 0.121745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.969575E+10 | 396.97 | 0.319718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.802382E+10 | 0.00 | 0.532899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107407E+11 | 242.49 | 0.564729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109285E+11 | 653.52 | 0.331419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124746E+11 | 3033337.42 | 0.555058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116675E+11 | 0.101905E+09 | 0.877442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.436914E+10 | 0.523659E+10 | 6140035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.975937E+11 | 0.335107E+11 | 0.199005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192139E+10 | 0.00 | 6140035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124746E+11 | 0.133695E+11 | 0.564729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.110676E+12 | 0.00 | 0.108296E+11 | 0.00 | 0.425978E+10 | 0.00 | 0.00 | 0.00 | 0.135489E+12 | 0.00 | 0.00 | 0.00 |
February | 0.999658E+11 | 0.00 | 0.153158E+11 | 0.00 | 0.503325E+10 | 0.00 | 0.00 | 0.00 | 0.203006E+12 | 0.00 | 0.00 | 0.00 |
March | 0.110676E+12 | 0.00 | 0.427223E+11 | 0.00 | 0.112696E+11 | 0.00 | 0.00 | 0.00 | 0.200431E+12 | 0.00 | 0.00 | 0.00 |
April | 0.107106E+12 | 0.00 | 0.489260E+11 | 0.00 | 0.125096E+11 | 0.00 | 0.00 | 0.00 | 0.205584E+12 | 0.00 | 0.00 | 0.00 |
May | 0.110676E+12 | 0.00 | 0.119418E+11 | 0.00 | 0.471073E+10 | 0.00 | 0.00 | 0.00 | 0.805646E+11 | 0.00 | 0.00 | 0.00 |
June | 0.107106E+12 | 0.00 | 0.214581E+12 | 0.00 | 0.476443E+11 | 0.00 | 0.00 | 0.00 | 0.404814E+11 | 0.00 | 0.00 | 0.00 |
July | 0.110676E+12 | 0.00 | 0.896825E+12 | 0.00 | 0.185580E+12 | 0.00 | 0.00 | 0.00 | 0.242952E+10 | 0.00 | 0.00 | 0.00 |
August | 0.110676E+12 | 0.00 | 0.104052E+13 | 0.00 | 0.214316E+12 | 0.00 | 0.00 | 0.00 | 0.439043E+10 | 0.00 | 0.00 | 0.00 |
September | 0.107106E+12 | 0.00 | 0.223499E+11 | 0.00 | 0.728209E+10 | 0.00 | 0.00 | 0.00 | 0.105034E+11 | 0.00 | 0.00 | 0.00 |
October | 0.110676E+12 | 0.00 | 0.135100E+11 | 0.00 | 0.496625E+10 | 0.00 | 0.00 | 0.00 | 0.104880E+12 | 0.00 | 0.00 | 0.00 |
November | 0.107106E+12 | 0.00 | 0.243824E+11 | 0.00 | 0.714028E+10 | 0.00 | 0.00 | 0.00 | 0.214037E+12 | 0.00 | 0.00 | 0.00 |
December | 0.110676E+12 | 0.00 | 0.220151E+11 | 0.00 | 0.697884E+10 | 0.00 | 0.00 | 0.00 | 0.261257E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130313E+13 | 0.00 | 0.236392E+13 | 0.00 | 0.511691E+12 | 0.00 | 0.00 | 0.00 | 0.146305E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.999658E+11 | 0.00 | 0.108296E+11 | 0.00 | 0.425978E+10 | 0.00 | 0.00 | 0.00 | 0.242952E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110676E+12 | 0.00 | 0.104052E+13 | 0.00 | 0.214316E+12 | 0.00 | 0.00 | 0.00 | 0.261257E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148130E+10 | 0.00 | 0.393213E+10 | 0.00 | 0.803230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133795E+10 | 0.00 | 0.963887E+10 | 0.00 | 0.185230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148130E+10 | 0.00 | 0.181673E+11 | 0.00 | 0.328320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143352E+10 | 0.00 | 0.238621E+11 | 0.00 | 0.407007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148130E+10 | 0.00 | 0.689225E+10 | 0.00 | 0.130650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143352E+10 | 0.00 | 0.134464E+11 | 0.00 | 0.255962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148130E+10 | 0.00 | 0.208134E+11 | 0.00 | 0.418324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148130E+10 | 0.00 | 0.266174E+11 | 0.00 | 0.514032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143352E+10 | 0.00 | 0.704204E+10 | 0.00 | 0.133541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148130E+10 | 0.00 | 0.125680E+11 | 0.00 | 0.225965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143352E+10 | 0.00 | 0.176676E+11 | 0.00 | 0.311737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148130E+10 | 0.00 | 0.235566E+11 | 0.00 | 0.415544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174411E+11 | 0.00 | 0.184204E+12 | 0.00 | 0.340664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133795E+10 | 0.00 | 0.393213E+10 | 0.00 | 0.803230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148130E+10 | 0.00 | 0.266174E+11 | 0.00 | 0.514032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142085E+11 | 0.00 | 0.704233E+10 | 0.00 | 0.160871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128335E+11 | 0.00 | 0.616601E+11 | 0.00 | 0.121758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142085E+11 | 0.00 | 0.154302E+12 | 0.00 | 0.281971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137502E+11 | 0.00 | 0.216783E+12 | 0.00 | 0.372122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142085E+11 | 0.00 | 0.602480E+11 | 0.00 | 0.114959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137502E+11 | 0.00 | 0.125406E+12 | 0.00 | 0.239458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142085E+11 | 0.00 | 0.196904E+12 | 0.00 | 0.396426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142085E+11 | 0.00 | 0.252254E+12 | 0.00 | 0.487980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137502E+11 | 0.00 | 0.616034E+11 | 0.00 | 0.117674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142085E+11 | 0.00 | 0.106476E+12 | 0.00 | 0.193243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137502E+11 | 0.00 | 0.147654E+12 | 0.00 | 0.263923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142085E+11 | 0.00 | 0.189263E+12 | 0.00 | 0.340358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167294E+12 | 0.00 | 0.157960E+13 | 0.00 | 0.294596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128335E+11 | 0.00 | 0.704233E+10 | 0.00 | 0.160871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142085E+11 | 0.00 | 0.252254E+12 | 0.00 | 0.487980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144520E+10 | 0.00 | 0.125434E+09 | 0.00 | 29286744.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130534E+10 | 0.00 | 0.411803E+10 | 0.00 | 0.829128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144520E+10 | 0.00 | 0.135018E+11 | 0.00 | 0.249476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139858E+10 | 0.00 | 0.204490E+11 | 0.00 | 0.353692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144520E+10 | 0.00 | 0.551494E+10 | 0.00 | 0.105952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139858E+10 | 0.00 | 0.124638E+11 | 0.00 | 0.238740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144520E+10 | 0.00 | 0.197697E+11 | 0.00 | 0.398842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144520E+10 | 0.00 | 0.252156E+11 | 0.00 | 0.489143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139858E+10 | 0.00 | 0.571983E+10 | 0.00 | 0.110109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144520E+10 | 0.00 | 0.903781E+10 | 0.00 | 0.165812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139858E+10 | 0.00 | 0.126122E+11 | 0.00 | 0.228568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144520E+10 | 0.00 | 0.165579E+11 | 0.00 | 0.301926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170161E+11 | 0.00 | 0.145086E+12 | 0.00 | 0.272810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130534E+10 | 0.00 | 0.125434E+09 | 0.00 | 29286744.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144520E+10 | 0.00 | 0.252156E+11 | 0.00 | 0.489143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 78430169.75 | 0.00 | 0.00 | 0.580219E+11 | 0.00 | 0.33 |
February | 0.00 | 0.00 | 0.00 | 74226476.04 | 0.00 | 0.00 | 0.525561E+11 | 0.00 | 0.33 |
March | 0.00 | 0.00 | 0.00 | 0.102729E+09 | 0.00 | 0.00 | 0.570500E+11 | 0.00 | 0.50 |
April | 0.00 | 0.00 | 0.00 | 95269003.64 | 0.00 | 0.00 | 0.597944E+11 | 0.00 | 0.69 |
May | 0.00 | 13259692.83 | 0.00 | 0.104486E+09 | 0.00 | 0.00 | 0.536788E+11 | 0.00 | 0.96 |
June | 0.00 | 0.174144E+10 | 0.00 | 0.105803E+09 | 0.00 | 0.00 | 0.313427E+11 | 0.00 | 0.90 |
July | 0.00 | 0.863782E+10 | 0.00 | 92257285.36 | 0.00 | 0.00 | 0.890809E+10 | 0.00 | 0.54 |
August | 0.00 | 0.470358E+10 | 0.00 | 0.120117E+09 | 0.00 | 0.00 | 0.178584E+11 | 0.00 | 0.78 |
September | 0.00 | 0.375602E+10 | 0.00 | 0.120056E+09 | 0.00 | 0.00 | 0.382419E+11 | 0.00 | 1.01 |
October | 0.00 | 0.00 | 0.00 | 0.125315E+09 | 0.00 | 0.00 | 0.660353E+11 | 0.00 | 0.87 |
November | 0.00 | 0.00 | 0.00 | 0.106784E+09 | 0.00 | 0.00 | 0.669758E+11 | 0.00 | 0.66 |
December | 0.00 | 0.00 | 0.00 | 95415818.16 | 0.00 | 0.00 | 0.593394E+11 | 0.00 | 0.37 |
Annual Sum or Average | 0.00 | 0.188521E+11 | 0.00 | 0.122089E+10 | 0.00 | 0.00 | 0.569803E+12 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 74226476.04 | 0.00 | 0.00 | 0.890809E+10 | 0.00 | 0.33 |
Maximum of Months | 0.00 | 0.863782E+10 | 0.00 | 0.125315E+09 | 0.00 | 0.00 | 0.669758E+11 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.758742E+10 | 0.00 | 0.00 | 44083416.95 | 0.00 | 0.00 | 0.277440E+11 | 0.00 | 0.35 |
February | 0.393584E+10 | 0.00 | 0.00 | 49023829.77 | 0.00 | 0.00 | 0.300113E+11 | 0.00 | 0.36 |
March | 0.189017E+10 | 92153.83 | 0.00 | 95245226.40 | 0.00 | 0.00 | 0.482237E+11 | 0.00 | 0.49 |
April | 0.392862E+10 | 0.00 | 0.00 | 98705777.05 | 0.00 | 0.00 | 0.551615E+11 | 0.00 | 0.66 |
May | 0.318747E+10 | 14497182.71 | 0.00 | 93524982.82 | 27493594.62 | 0.00 | 0.485866E+11 | 0.00 | 0.85 |
June | 0.247621E+10 | 0.313009E+10 | 0.00 | 87802619.51 | 0.750878E+09 | 0.00 | 0.305994E+11 | 0.00 | 1.03 |
July | 0.431046E+10 | 0.127404E+11 | 0.00 | 52741501.18 | 0.255167E+10 | 0.00 | 0.105368E+11 | 0.00 | 0.97 |
August | 0.678528E+10 | 0.753568E+10 | 0.00 | 85874955.92 | 0.128815E+10 | 0.00 | 0.212510E+11 | 0.00 | 1.13 |
September | 0.269904E+10 | 0.261064E+10 | 0.00 | 86729708.86 | 99295613.12 | 0.00 | 0.348753E+11 | 0.00 | 0.93 |
October | 0.197759E+10 | 0.00 | 0.00 | 97731052.21 | 0.00 | 0.00 | 0.508597E+11 | 0.00 | 0.65 |
November | 0.123925E+10 | 0.00 | 0.00 | 91036805.99 | 0.00 | 0.00 | 0.493394E+11 | 0.00 | 0.50 |
December | 0.138559E+10 | 0.00 | 0.00 | 78369049.89 | 0.00 | 0.00 | 0.430406E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.414029E+11 | 0.260314E+11 | 0.00 | 0.960869E+09 | 0.471748E+10 | 0.00 | 0.450229E+12 | 0.00 | 0.69 |
Minimum of Months | 0.123925E+10 | 0.00 | 0.00 | 44083416.95 | 0.00 | 0.00 | 0.105368E+11 | 0.00 | 0.35 |
Maximum of Months | 0.758742E+10 | 0.127404E+11 | 0.00 | 98705777.05 | 0.255167E+10 | 0.00 | 0.551615E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205210E+12 | 0.00 | 0.00 | 11084419.80 | 0.00 | 0.637475E+10 | 0.170171E+11 | 0.00 | 0.30 |
February | 0.192418E+12 | 0.00 | 0.00 | 16243174.92 | 0.00 | 0.136685E+10 | 0.218796E+11 | 0.00 | 0.30 |
March | 0.124092E+12 | 0.00 | 0.00 | 0.296139E+09 | 0.00 | 0.00 | 0.190963E+12 | 0.00 | 0.37 |
April | 0.679189E+11 | 0.00 | 0.00 | 0.428516E+09 | 0.00 | 0.00 | 0.280243E+12 | 0.00 | 0.42 |
May | 0.292924E+11 | 86769996.67 | 0.00 | 0.682800E+09 | 0.202424E+09 | 0.00 | 0.372631E+12 | 0.00 | 0.67 |
June | 0.164843E+11 | 0.190035E+11 | 0.00 | 0.640900E+09 | 0.268443E+10 | 0.00 | 0.228870E+12 | 0.00 | 0.76 |
July | 0.108901E+11 | 0.769959E+11 | 0.00 | 0.384922E+09 | 0.939572E+10 | 0.00 | 0.790651E+11 | 0.00 | 0.63 |
August | 0.122810E+11 | 0.419302E+11 | 0.00 | 0.653829E+09 | 0.498944E+10 | 0.00 | 0.160669E+12 | 0.00 | 0.72 |
September | 0.308837E+11 | 0.172516E+11 | 0.00 | 0.613932E+09 | 0.268259E+09 | 0.00 | 0.254360E+12 | 0.00 | 0.72 |
October | 0.556061E+11 | 0.00 | 0.00 | 0.479066E+09 | 0.00 | 0.00 | 0.293651E+12 | 0.00 | 0.44 |
November | 0.100083E+12 | 0.00 | 0.00 | 0.282469E+09 | 94084995.08 | 0.00 | 0.198040E+12 | 0.00 | 0.35 |
December | 0.196699E+12 | 0.00 | 0.00 | 35757651.92 | 0.00 | 0.115000E+10 | 0.410796E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.104186E+13 | 0.155268E+12 | 0.00 | 0.452566E+10 | 0.176344E+11 | 0.889160E+10 | 0.213847E+13 | 0.00 | 0.50 |
Minimum of Months | 0.108901E+11 | 0.00 | 0.00 | 11084419.80 | 0.00 | 0.00 | 0.170171E+11 | 0.00 | 0.30 |
Maximum of Months | 0.205210E+12 | 0.769959E+11 | 0.00 | 0.682800E+09 | 0.939572E+10 | 0.637475E+10 | 0.372631E+12 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302898E+10 | 0.00 | 0.00 | 0.28 |
February | 0.146954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251308E+10 | 0.00 | 0.00 | 0.29 |
March | 0.167631E+11 | 0.00 | 0.00 | 10427220.26 | 0.00 | 0.679683E+09 | 0.715661E+10 | 0.00 | 0.35 |
April | 0.129151E+11 | 0.00 | 0.00 | 19495396.01 | 0.00 | 91122392.60 | 0.162254E+11 | 0.00 | 0.39 |
May | 0.700110E+10 | 10821838.01 | 0.00 | 48573152.73 | 8992573.37 | 0.00 | 0.300057E+11 | 0.00 | 0.63 |
June | 0.230468E+10 | 0.206382E+10 | 0.00 | 57679330.39 | 0.335032E+09 | 0.00 | 0.219496E+11 | 0.00 | 0.80 |
July | 0.136597E+10 | 0.845179E+10 | 0.00 | 35872714.66 | 0.111113E+10 | 0.00 | 0.761486E+10 | 0.00 | 0.68 |
August | 0.138502E+10 | 0.488228E+10 | 0.00 | 60175308.02 | 0.597269E+09 | 0.00 | 0.146991E+11 | 0.00 | 0.74 |
September | 0.545982E+10 | 0.161952E+10 | 0.00 | 43703636.81 | 31859975.90 | 0.00 | 0.193869E+11 | 0.00 | 0.67 |
October | 0.125580E+11 | 0.00 | 0.00 | 19295031.95 | 0.00 | 0.163371E+09 | 0.145704E+11 | 0.00 | 0.39 |
November | 0.169907E+11 | 0.00 | 0.00 | 3187016.29 | 25403272.13 | 0.379902E+09 | 0.352407E+10 | 0.00 | 0.31 |
December | 0.156294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222933E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.121924E+12 | 0.170282E+11 | 0.00 | 0.298409E+09 | 0.210969E+10 | 0.908547E+10 | 0.135133E+12 | 0.00 | 0.48 |
Minimum of Months | 0.136597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.169907E+11 | 0.845179E+10 | 0.00 | 60175308.02 | 0.111113E+10 | 0.302898E+10 | 0.300057E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761618E+09 | 0.00 | 0.00 | 0.27 |
February | 0.258792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475024E+09 | 0.00 | 0.00 | 0.26 |
March | 0.252503E+10 | 14326.83 | 0.00 | 2675270.92 | 0.00 | 93737383.09 | 0.156107E+10 | 0.00 | 0.36 |
April | 0.171352E+10 | 0.00 | 0.00 | 5460268.49 | 0.00 | 0.00 | 0.377058E+10 | 0.00 | 0.52 |
May | 0.983301E+09 | 573765.97 | 0.00 | 9146712.53 | 4275208.38 | 0.00 | 0.505148E+10 | 0.00 | 0.84 |
June | 0.385039E+09 | 0.582396E+09 | 0.00 | 11656846.76 | 81813122.01 | 0.00 | 0.415366E+10 | 0.00 | 1.26 |
July | 0.568563E+09 | 0.220664E+10 | 0.00 | 7671838.35 | 0.306529E+09 | 0.00 | 0.150917E+10 | 0.00 | 1.20 |
August | 0.913841E+09 | 0.125091E+10 | 0.00 | 11571348.57 | 0.160423E+09 | 0.00 | 0.266564E+10 | 0.00 | 1.30 |
September | 0.798697E+09 | 0.388820E+09 | 0.00 | 7645606.26 | 12554762.14 | 0.00 | 0.325262E+10 | 0.00 | 0.91 |
October | 0.167011E+10 | 0.00 | 0.00 | 4676356.69 | 0.00 | 0.00 | 0.299838E+10 | 0.00 | 0.48 |
November | 0.229805E+10 | 0.00 | 0.00 | 1886243.10 | 0.00 | 0.00 | 0.139472E+10 | 0.00 | 0.31 |
December | 0.305705E+10 | 0.00 | 0.00 | 82767.93 | 0.00 | 0.234843E+09 | 0.109134E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.201270E+11 | 0.442935E+10 | 0.00 | 62473259.60 | 0.565596E+09 | 0.156522E+10 | 0.264665E+11 | 0.00 | 0.67 |
Minimum of Months | 0.385039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.305705E+10 | 0.220664E+10 | 0.00 | 11656846.76 | 0.306529E+09 | 0.761618E+09 | 0.505148E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164961E+10 | 0.00 | 0.00 | 55749.16 | 0.00 | 0.496643E+09 | 32699750.35 | 0.00 | 0.27 |
February | 0.149345E+10 | 0.00 | 0.00 | 576700.79 | 0.00 | 0.331182E+09 | 0.271308E+09 | 0.00 | 0.28 |
March | 0.138004E+10 | 10372.49 | 0.00 | 4301827.99 | 0.00 | 42141828.63 | 0.199980E+10 | 0.00 | 0.44 |
April | 0.100279E+10 | 0.00 | 0.00 | 7582010.70 | 0.00 | 0.00 | 0.428227E+10 | 0.00 | 0.76 |
May | 0.518073E+09 | 1610669.74 | 0.00 | 11618851.04 | 1769536.61 | 0.00 | 0.599168E+10 | 0.00 | 1.36 |
June | 0.218860E+09 | 0.514586E+09 | 0.00 | 11850516.80 | 38406464.60 | 0.00 | 0.458250E+10 | 0.00 | 1.79 |
July | 0.348866E+09 | 0.173713E+10 | 0.00 | 10133867.69 | 0.195630E+09 | 0.00 | 0.190385E+10 | 0.00 | 1.68 |
August | 0.601753E+09 | 0.847485E+09 | 0.00 | 11123763.13 | 0.102707E+09 | 0.00 | 0.264411E+10 | 0.00 | 1.69 |
September | 0.422010E+09 | 0.297886E+09 | 0.00 | 9998692.72 | 8119236.99 | 0.00 | 0.387370E+10 | 0.00 | 1.37 |
October | 0.959999E+09 | 0.00 | 0.00 | 5566617.15 | 0.00 | 0.00 | 0.293208E+10 | 0.00 | 0.63 |
November | 0.159693E+10 | 0.00 | 0.00 | 1581307.75 | 0.00 | 0.00 | 0.940653E+09 | 0.00 | 0.32 |
December | 0.181775E+10 | 0.00 | 0.00 | 93326.65 | 0.00 | 0.323401E+09 | 57363735.51 | 0.00 | 0.25 |
Annual Sum or Average | 0.120101E+11 | 0.339871E+10 | 0.00 | 74483231.58 | 0.346632E+09 | 0.119337E+10 | 0.295120E+11 | 0.00 | 0.91 |
Minimum of Months | 0.218860E+09 | 0.00 | 0.00 | 55749.16 | 0.00 | 0.00 | 32699750.35 | 0.00 | 0.25 |
Maximum of Months | 0.181775E+10 | 0.173713E+10 | 0.00 | 11850516.80 | 0.195630E+09 | 0.496643E+09 | 0.599168E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209003E+10 | 0.00 | 0.00 | 2724267.02 | 0.00 | 0.778248E+09 | 0.155198E+10 | 0.00 | 0.34 |
February | 0.179569E+10 | 0.00 | 0.00 | 3517616.57 | 0.00 | 0.587400E+09 | 0.205946E+10 | 0.00 | 0.36 |
March | 0.173650E+10 | 39317.83 | 0.00 | 10981222.48 | 0.00 | 0.122117E+09 | 0.541545E+10 | 0.00 | 0.57 |
April | 0.156697E+10 | 0.00 | 0.00 | 11289681.20 | 0.00 | 5233554.02 | 0.701274E+10 | 0.00 | 0.85 |
May | 0.993362E+09 | 4436323.71 | 0.00 | 13567631.45 | 2818771.04 | 0.00 | 0.704572E+10 | 0.00 | 1.18 |
June | 0.467190E+09 | 0.648335E+09 | 0.00 | 13244794.91 | 74821533.35 | 0.00 | 0.461236E+10 | 0.00 | 1.45 |
July | 0.558550E+09 | 0.241928E+10 | 0.00 | 9766442.10 | 0.296898E+09 | 0.00 | 0.159120E+10 | 0.00 | 1.34 |
August | 0.905119E+09 | 0.144354E+10 | 0.00 | 16591881.80 | 0.151998E+09 | 0.00 | 0.324439E+10 | 0.00 | 1.60 |
September | 0.624124E+09 | 0.536893E+09 | 0.00 | 19865337.74 | 12300014.38 | 0.00 | 0.628785E+10 | 0.00 | 1.58 |
October | 0.129782E+10 | 0.00 | 0.00 | 13910271.22 | 0.00 | 1242763.23 | 0.688882E+10 | 0.00 | 0.92 |
November | 0.210027E+10 | 0.00 | 0.00 | 6323034.86 | 0.00 | 15394147.46 | 0.338422E+10 | 0.00 | 0.45 |
December | 0.254832E+10 | 0.00 | 0.00 | 2639165.15 | 0.00 | 0.347267E+09 | 0.136838E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.166839E+11 | 0.505252E+10 | 0.00 | 0.124421E+09 | 0.538835E+09 | 0.185690E+10 | 0.504626E+11 | 0.00 | 0.91 |
Minimum of Months | 0.467190E+09 | 0.00 | 0.00 | 2639165.15 | 0.00 | 0.00 | 0.136838E+10 | 0.00 | 0.30 |
Maximum of Months | 0.254832E+10 | 0.241928E+10 | 0.00 | 19865337.74 | 0.296898E+09 | 0.778248E+09 | 0.704572E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181338E+10 | 0.00 | 0.00 | 376080.07 | 0.00 | 0.112090E+09 | 0.336232E+09 | 0.00 | 0.28 |
February | 0.126180E+10 | 0.00 | 0.00 | 1847379.03 | 0.00 | 30920001.00 | 0.123618E+10 | 0.00 | 0.33 |
March | 0.412585E+09 | 16607.38 | 0.00 | 10639667.77 | 0.00 | 0.00 | 0.566894E+10 | 0.00 | 0.75 |
April | 0.140835E+09 | 0.00 | 0.00 | 17474438.20 | 0.00 | 0.00 | 0.960960E+10 | 0.00 | 1.46 |
May | 0.203436E+09 | 4399781.80 | 0.00 | 16419540.07 | 1318076.77 | 0.00 | 0.757300E+10 | 0.00 | 1.74 |
June | 0.113275E+09 | 0.670693E+09 | 0.00 | 19711928.91 | 24163171.08 | 0.00 | 0.559893E+10 | 0.00 | 2.45 |
July | 0.144646E+09 | 0.260034E+10 | 0.00 | 14609131.79 | 36493063.99 | 0.00 | 0.211791E+10 | 0.00 | 2.11 |
August | 0.203280E+09 | 0.161048E+10 | 0.00 | 21053357.80 | 8242881.81 | 0.00 | 0.424109E+10 | 0.00 | 2.53 |
September | 0.183521E+09 | 0.379812E+09 | 0.00 | 14421207.12 | 3481510.39 | 0.00 | 0.467256E+10 | 0.00 | 1.69 |
October | 0.261813E+09 | 0.00 | 0.00 | 10235004.48 | 0.00 | 0.00 | 0.562727E+10 | 0.00 | 1.00 |
November | 0.266985E+09 | 0.00 | 0.00 | 7351677.54 | 0.00 | 0.00 | 0.436566E+10 | 0.00 | 0.59 |
December | 0.746357E+09 | 0.00 | 0.00 | 4009000.14 | 0.00 | 0.00 | 0.259782E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.575192E+10 | 0.526574E+10 | 0.00 | 0.138148E+09 | 73698704.05 | 0.143010E+09 | 0.536452E+11 | 0.00 | 1.28 |
Minimum of Months | 0.113275E+09 | 0.00 | 0.00 | 376080.07 | 0.00 | 0.00 | 0.336232E+09 | 0.00 | 0.28 |
Maximum of Months | 0.181338E+10 | 0.260034E+10 | 0.00 | 21053357.80 | 36493063.99 | 0.112090E+09 | 0.960960E+10 | 0.00 | 2.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.393006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274135E+11 | 0.00 | 0.00 | 0.31 |
February | 0.657236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230500E+11 | 0.00 | 0.00 | 0.32 |
March | 0.212237E+11 | 0.00 | 0.00 | 8136096.03 | 0.00 | 0.111386E+11 | 0.336366E+10 | 0.00 | 0.33 |
April | 0.254369E+11 | 0.00 | 0.00 | 10936757.19 | 0.00 | 0.152275E+10 | 0.789282E+10 | 0.00 | 0.34 |
May | 0.143838E+11 | 4249013.01 | 0.00 | 57707461.47 | 27734328.67 | 0.00 | 0.310504E+11 | 0.00 | 0.65 |
June | 0.453727E+10 | 0.399563E+10 | 0.00 | 83645611.72 | 0.329984E+09 | 0.00 | 0.291648E+11 | 0.00 | 0.97 |
July | 0.184307E+10 | 0.151390E+11 | 0.00 | 56463899.61 | 0.117489E+10 | 0.00 | 0.111405E+11 | 0.00 | 0.85 |
August | 0.432187E+10 | 0.776492E+10 | 0.00 | 81058219.98 | 0.617097E+09 | 0.00 | 0.176629E+11 | 0.00 | 0.87 |
September | 0.128989E+11 | 0.262389E+10 | 0.00 | 45576300.47 | 37456800.56 | 0.00 | 0.176797E+11 | 0.00 | 0.69 |
October | 0.258664E+11 | 0.00 | 0.00 | 11046578.57 | 0.00 | 0.114175E+10 | 0.730992E+10 | 0.00 | 0.36 |
November | 0.256493E+11 | 0.00 | 0.00 | 36707.18 | 11808553.42 | 0.602321E+10 | 0.188577E+09 | 0.00 | 0.30 |
December | 0.641101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253714E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.153075E+12 | 0.295277E+11 | 0.00 | 0.354608E+09 | 0.219898E+10 | 0.956613E+11 | 0.125453E+12 | 0.00 | 0.53 |
Minimum of Months | 0.184307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.258664E+11 | 0.151390E+11 | 0.00 | 83645611.72 | 0.117489E+10 | 0.274135E+11 | 0.310504E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.360110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136257E+11 | 0.00 | 0.00 | 0.26 |
February | 0.458289E+10 | 0.00 | 0.00 | 771519.75 | 0.00 | 0.113657E+11 | 0.312750E+09 | 0.00 | 0.26 |
March | 0.109875E+11 | 0.00 | 0.00 | 21204392.00 | 0.00 | 0.378712E+10 | 0.870137E+10 | 0.00 | 0.36 |
April | 0.946203E+10 | 0.00 | 0.00 | 52694297.25 | 0.00 | 0.523100E+09 | 0.276161E+11 | 0.00 | 0.57 |
May | 0.582115E+10 | 4207769.95 | 0.00 | 0.101907E+09 | 16842738.71 | 0.00 | 0.502152E+11 | 0.00 | 1.20 |
June | 0.197119E+10 | 0.391172E+10 | 0.00 | 0.109844E+09 | 83229360.40 | 0.00 | 0.417052E+11 | 0.00 | 1.61 |
July | 0.872326E+09 | 0.133690E+11 | 0.00 | 0.100316E+09 | 0.660025E+09 | 0.00 | 0.188014E+11 | 0.00 | 1.45 |
August | 0.187725E+10 | 0.603147E+10 | 0.00 | 0.107914E+09 | 0.384598E+09 | 0.00 | 0.245663E+11 | 0.00 | 1.42 |
September | 0.532125E+10 | 0.218290E+10 | 0.00 | 84252908.63 | 21653549.40 | 0.00 | 0.309570E+11 | 0.00 | 1.17 |
October | 0.100513E+11 | 0.00 | 0.00 | 30423440.65 | 0.00 | 0.600817E+09 | 0.158490E+11 | 0.00 | 0.45 |
November | 0.120624E+11 | 0.00 | 0.00 | 3537893.99 | 7622017.46 | 0.336127E+10 | 0.206197E+10 | 0.00 | 0.25 |
December | 0.368045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136688E+11 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.702908E+11 | 0.254993E+11 | 0.00 | 0.612865E+09 | 0.117397E+10 | 0.469324E+11 | 0.220786E+12 | 0.00 | 0.77 |
Minimum of Months | 0.872326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.120624E+11 | 0.133690E+11 | 0.00 | 0.109844E+09 | 0.660025E+09 | 0.136688E+11 | 0.502152E+11 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107897E+11 | 0.00 | 0.00 | 19693763.69 | 0.00 | 0.164870E+11 | 0.948697E+10 | 0.00 | 0.37 |
February | 0.114224E+11 | 0.00 | 0.00 | 25410043.20 | 0.00 | 0.135038E+11 | 0.134319E+11 | 0.00 | 0.41 |
March | 0.176335E+11 | 0.00 | 0.00 | 91087646.26 | 0.00 | 0.376464E+10 | 0.440678E+11 | 0.00 | 0.60 |
April | 0.165672E+11 | 0.00 | 0.00 | 86296279.18 | 0.00 | 0.112741E+10 | 0.464450E+11 | 0.00 | 0.66 |
May | 0.118130E+11 | 46983066.32 | 0.00 | 0.118171E+09 | 11873948.57 | 0.00 | 0.593354E+11 | 0.00 | 1.06 |
June | 0.531144E+10 | 0.462498E+10 | 0.00 | 0.111483E+09 | 0.282440E+09 | 0.00 | 0.374420E+11 | 0.00 | 1.23 |
July | 0.225356E+10 | 0.180855E+11 | 0.00 | 82323713.60 | 0.104867E+10 | 0.00 | 0.127829E+11 | 0.00 | 1.04 |
August | 0.370095E+10 | 0.993838E+10 | 0.00 | 0.143507E+09 | 0.573959E+09 | 0.00 | 0.263264E+11 | 0.00 | 1.26 |
September | 0.824525E+10 | 0.427343E+10 | 0.00 | 0.193097E+09 | 33487756.10 | 0.00 | 0.548184E+11 | 0.00 | 1.47 |
October | 0.135585E+11 | 0.00 | 0.00 | 0.125565E+09 | 0.00 | 0.540158E+09 | 0.557480E+11 | 0.00 | 0.80 |
November | 0.200539E+11 | 4091296.84 | 0.00 | 46373679.00 | 8978655.14 | 0.384327E+10 | 0.253748E+11 | 0.00 | 0.45 |
December | 0.124928E+11 | 0.00 | 0.00 | 14102488.62 | 0.00 | 0.166843E+11 | 0.624603E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.133842E+12 | 0.369734E+11 | 0.00 | 0.105711E+10 | 0.195941E+10 | 0.559505E+11 | 0.391506E+12 | 0.00 | 0.81 |
Minimum of Months | 0.225356E+10 | 0.00 | 0.00 | 14102488.62 | 0.00 | 0.00 | 0.624603E+10 | 0.00 | 0.34 |
Maximum of Months | 0.200539E+11 | 0.180855E+11 | 0.00 | 0.193097E+09 | 0.104867E+10 | 0.166843E+11 | 0.593354E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.517665E+10 | 0.00 | 0.00 | 102773.29 | 0.00 | 0.145496E+11 | 77496846.06 | 0.00 | 0.31 |
February | 0.708767E+10 | 0.00 | 0.00 | 1900195.70 | 0.00 | 0.110208E+11 | 0.118191E+10 | 0.00 | 0.32 |
March | 0.136071E+11 | 0.00 | 0.00 | 23965122.48 | 0.00 | 0.305314E+10 | 0.131082E+11 | 0.00 | 0.42 |
April | 0.108782E+11 | 0.00 | 0.00 | 55626435.04 | 0.00 | 0.247800E+09 | 0.288559E+11 | 0.00 | 0.63 |
May | 0.545824E+10 | 13567429.24 | 0.00 | 0.114986E+09 | 12981165.47 | 0.00 | 0.510456E+11 | 0.00 | 1.32 |
June | 0.213525E+10 | 0.431705E+10 | 0.00 | 0.132005E+09 | 0.136177E+09 | 0.00 | 0.370658E+11 | 0.00 | 1.79 |
July | 0.780625E+09 | 0.154229E+11 | 0.00 | 93741702.60 | 0.306017E+09 | 0.00 | 0.114305E+11 | 0.00 | 1.38 |
August | 0.117787E+10 | 0.770801E+10 | 0.00 | 0.112428E+09 | 0.157722E+09 | 0.00 | 0.200389E+11 | 0.00 | 1.44 |
September | 0.532496E+10 | 0.242204E+10 | 0.00 | 93852315.93 | 8541259.08 | 0.00 | 0.272221E+11 | 0.00 | 1.20 |
October | 0.120186E+11 | 0.00 | 0.00 | 30497867.02 | 0.00 | 0.367834E+09 | 0.164550E+11 | 0.00 | 0.50 |
November | 0.160744E+11 | 0.00 | 0.00 | 5092377.30 | 7585013.12 | 0.253701E+10 | 0.321991E+10 | 0.00 | 0.31 |
December | 0.767575E+10 | 0.00 | 0.00 | 158906.82 | 0.00 | 0.123386E+11 | 0.116919E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.873954E+11 | 0.298835E+11 | 0.00 | 0.664356E+09 | 0.629024E+09 | 0.441148E+11 | 0.209818E+12 | 0.00 | 0.83 |
Minimum of Months | 0.780625E+09 | 0.00 | 0.00 | 102773.29 | 0.00 | 0.00 | 77496846.06 | 0.00 | 0.30 |
Maximum of Months | 0.160744E+11 | 0.154229E+11 | 0.00 | 0.132005E+09 | 0.306017E+09 | 0.145496E+11 | 0.510456E+11 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66080084.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271579E+10 | 0.00 | 0.00 | 0.34 |
February | 0.225723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239067E+10 | 0.00 | 0.00 | 0.34 |
March | 0.142363E+10 | 0.00 | 0.00 | 642590.72 | 0.00 | 0.149832E+10 | 0.242699E+09 | 0.00 | 0.36 |
April | 0.236130E+10 | 0.00 | 0.00 | 668318.81 | 0.00 | 0.465352E+09 | 0.522631E+09 | 0.00 | 0.36 |
May | 0.164120E+10 | 81417.29 | 0.00 | 4701705.70 | 1976295.94 | 26276608.99 | 0.268798E+10 | 0.00 | 0.62 |
June | 0.501929E+09 | 0.438570E+09 | 0.00 | 8300942.21 | 30726427.58 | 0.00 | 0.289832E+10 | 0.00 | 1.01 |
July | 0.218446E+09 | 0.164543E+10 | 0.00 | 5828381.89 | 0.129166E+09 | 0.00 | 0.111545E+10 | 0.00 | 0.91 |
August | 0.479957E+09 | 0.887643E+09 | 0.00 | 8139359.45 | 75654557.95 | 0.00 | 0.169568E+10 | 0.00 | 0.91 |
September | 0.132037E+10 | 0.236357E+09 | 0.00 | 3894607.89 | 11299242.17 | 25874480.50 | 0.151034E+10 | 0.00 | 0.67 |
October | 0.222627E+10 | 0.00 | 0.00 | 607235.90 | 0.00 | 0.453780E+09 | 0.432400E+09 | 0.00 | 0.36 |
November | 0.128195E+10 | 0.00 | 3075034.19 | 0.00 | 257511.20 | 0.139276E+10 | 0.00 | 44125.22 | 0.31 |
December | 0.171531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252155E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.119184E+11 | 0.320809E+10 | 3075034.19 | 32783142.56 | 0.249080E+09 | 0.114904E+11 | 0.111055E+11 | 44125.22 | 0.54 |
Minimum of Months | 66080084.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.236130E+10 | 0.164543E+10 | 3075034.19 | 8300942.21 | 0.129166E+09 | 0.271579E+10 | 0.289832E+10 | 44125.22 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93404110.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163729E+10 | 0.00 | 0.00 | 0.33 |
February | 0.369835E+09 | 0.00 | 0.00 | 19108.91 | 0.00 | 0.124961E+10 | 7710801.01 | 0.00 | 0.33 |
March | 0.104623E+10 | 0.00 | 0.00 | 1431091.32 | 0.00 | 0.579281E+09 | 0.573649E+09 | 0.00 | 0.40 |
April | 0.106541E+10 | 0.00 | 0.00 | 4175033.58 | 0.00 | 0.152396E+09 | 0.251477E+10 | 0.00 | 0.62 |
May | 0.660879E+09 | 391969.34 | 0.00 | 9372810.13 | 955079.45 | 7386295.30 | 0.498274E+10 | 0.00 | 1.21 |
June | 0.190883E+09 | 0.430344E+09 | 0.00 | 11340218.85 | 9403276.93 | 0.00 | 0.438770E+10 | 0.00 | 1.73 |
July | 72078714.95 | 0.153494E+10 | 0.00 | 10881220.64 | 72697929.02 | 0.00 | 0.201991E+10 | 0.00 | 1.61 |
August | 0.177516E+09 | 0.715306E+09 | 0.00 | 11675365.21 | 42799616.84 | 0.00 | 0.255503E+10 | 0.00 | 1.55 |
September | 0.569828E+09 | 0.211251E+09 | 0.00 | 7719331.73 | 3021195.20 | 13511468.76 | 0.299588E+10 | 0.00 | 1.19 |
October | 0.110388E+10 | 0.00 | 0.00 | 2058257.44 | 0.00 | 0.189941E+09 | 0.115634E+10 | 0.00 | 0.45 |
November | 0.932836E+09 | 0.00 | 1933756.05 | 67867.35 | 244260.78 | 0.747322E+09 | 54352312.62 | 19856.87 | 0.31 |
December | 0.134509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157359E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.641729E+10 | 0.289223E+10 | 1933756.05 | 58740305.15 | 0.129121E+09 | 0.615033E+10 | 0.212481E+11 | 19856.87 | 0.84 |
Minimum of Months | 72078714.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.110388E+10 | 0.153494E+10 | 1933756.05 | 11675365.21 | 72697929.02 | 0.163729E+10 | 0.498274E+10 | 19856.87 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.561591E+09 | 0.00 | 0.00 | 1196125.58 | 0.00 | 0.177956E+10 | 0.578015E+09 | 0.00 | 0.35 |
February | 0.755957E+09 | 0.00 | 0.00 | 1852668.51 | 0.00 | 0.138984E+10 | 0.992526E+09 | 0.00 | 0.39 |
March | 0.132029E+10 | 0.00 | 0.00 | 6958419.00 | 0.00 | 0.635616E+09 | 0.347670E+10 | 0.00 | 0.59 |
April | 0.153162E+10 | 0.00 | 0.00 | 6901677.51 | 0.00 | 0.304762E+09 | 0.472546E+10 | 0.00 | 0.69 |
May | 0.127208E+10 | 572280.01 | 0.00 | 11032478.37 | 1618455.00 | 26388999.08 | 0.581340E+10 | 0.00 | 1.02 |
June | 0.535289E+09 | 0.513678E+09 | 0.00 | 11488350.54 | 25310612.77 | 0.00 | 0.396256E+10 | 0.00 | 1.28 |
July | 0.261815E+09 | 0.201376E+10 | 0.00 | 9726170.51 | 0.122214E+09 | 0.00 | 0.141811E+10 | 0.00 | 1.15 |
August | 0.406435E+09 | 0.115495E+10 | 0.00 | 15870610.71 | 59480449.01 | 0.00 | 0.273580E+10 | 0.00 | 1.34 |
September | 0.804092E+09 | 0.390317E+09 | 0.00 | 18198036.45 | 3288907.81 | 15235015.50 | 0.551458E+10 | 0.00 | 1.45 |
October | 0.131619E+10 | 0.00 | 0.00 | 9229202.06 | 0.00 | 0.223064E+09 | 0.497834E+10 | 0.00 | 0.81 |
November | 0.128023E+10 | 0.00 | 500069.06 | 3005954.48 | 2675340.56 | 0.821307E+09 | 0.178209E+10 | 3224.74 | 0.42 |
December | 0.535643E+09 | 0.00 | 0.00 | 740182.65 | 0.00 | 0.184826E+10 | 0.331507E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.105812E+11 | 0.407328E+10 | 500069.06 | 96199876.38 | 0.214588E+09 | 0.704403E+10 | 0.363091E+11 | 3224.74 | 0.82 |
Minimum of Months | 0.261815E+09 | 0.00 | 0.00 | 740182.65 | 0.00 | 0.00 | 0.331507E+09 | 0.00 | 0.34 |
Maximum of Months | 0.153162E+10 | 0.201376E+10 | 500069.06 | 18198036.45 | 0.122214E+09 | 0.184826E+10 | 0.581340E+10 | 3224.74 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143673E+10 | 0.00 | 0.00 | 0.32 |
February | 0.447041E+09 | 0.00 | 0.00 | 139780.76 | 0.00 | 0.108404E+10 | 95182323.83 | 0.00 | 0.33 |
March | 0.102759E+10 | 0.00 | 0.00 | 1840129.09 | 0.00 | 0.466170E+09 | 0.104839E+10 | 0.00 | 0.44 |
April | 0.109813E+10 | 0.00 | 0.00 | 4390996.49 | 0.00 | 0.135616E+09 | 0.284875E+10 | 0.00 | 0.67 |
May | 0.663011E+09 | 650696.71 | 0.00 | 11070450.07 | 824816.74 | 161906.49 | 0.502863E+10 | 0.00 | 1.28 |
June | 0.229294E+09 | 0.467583E+09 | 0.00 | 14395882.29 | 11524552.39 | 0.00 | 0.390890E+10 | 0.00 | 1.87 |
July | 93561066.89 | 0.167632E+10 | 0.00 | 10588121.68 | 32544884.99 | 0.00 | 0.123056E+10 | 0.00 | 1.48 |
August | 0.171753E+09 | 0.912674E+09 | 0.00 | 12677346.53 | 16491287.09 | 0.00 | 0.197737E+10 | 0.00 | 1.52 |
September | 0.567945E+09 | 0.220729E+09 | 0.00 | 8933917.55 | 872728.65 | 6087443.83 | 0.264053E+10 | 0.00 | 1.18 |
October | 0.117431E+10 | 0.00 | 0.00 | 2198904.62 | 0.00 | 0.142105E+09 | 0.139123E+10 | 0.00 | 0.51 |
November | 0.106908E+10 | 0.00 | 0.00 | 254821.70 | 2062582.36 | 0.519569E+09 | 0.200444E+09 | 0.00 | 0.32 |
December | 0.346914E+09 | 0.00 | 0.00 | 337.27 | 0.00 | 0.126731E+10 | 1610159.75 | 0.00 | 0.31 |
Annual Sum or Average | 0.714861E+10 | 0.327795E+10 | 0.00 | 66490688.06 | 64320852.22 | 0.505779E+10 | 0.203716E+11 | 0.00 | 0.86 |
Minimum of Months | 93561066.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.117431E+10 | 0.167632E+10 | 0.00 | 14395882.29 | 32544884.99 | 0.143673E+10 | 0.502863E+10 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2808013.18 | 0.00 | 0.00 | 0.828766E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7686924.00 | 0.00 | 0.00 | 0.751977E+09 | 0.00 | 0.28 |
March | 0.00 | 335895.87 | 0.00 | 15338860.38 | 0.00 | 0.00 | 0.661906E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18415579.52 | 0.00 | 0.00 | 0.502719E+09 | 0.00 | 0.29 |
May | 0.00 | 193234.68 | 0.00 | 4348606.33 | 0.00 | 0.00 | 0.361176E+09 | 0.00 | 0.29 |
June | 0.00 | 58097728.04 | 0.00 | 6299106.35 | 0.00 | 0.00 | 0.158545E+09 | 0.00 | 0.30 |
July | 0.00 | 0.162907E+09 | 0.00 | 3683229.73 | 0.00 | 0.00 | 27184227.14 | 0.00 | 0.28 |
August | 0.00 | 83871284.34 | 0.00 | 11642087.37 | 0.00 | 0.00 | 71625160.04 | 0.00 | 0.31 |
September | 0.00 | 23263588.67 | 0.00 | 3514430.82 | 0.00 | 0.00 | 0.195880E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 9134075.53 | 0.00 | 0.00 | 0.443267E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12972036.42 | 0.00 | 0.00 | 0.563304E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18508321.23 | 0.00 | 0.00 | 0.759921E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.328669E+09 | 0.00 | 0.114351E+09 | 0.00 | 0.00 | 0.532627E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2808013.18 | 0.00 | 0.00 | 27184227.14 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.162907E+09 | 0.00 | 18508321.23 | 0.00 | 0.00 | 0.828766E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308158E+10 | 0.00 | 0.00 | 6025021.96 | 0.00 | 0.00 | 0.515072E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 53141393.52 | 0.00 | 0.00 | 0.754335E+10 | 0.00 | 0.28 |
March | 0.00 | 3245494.69 | 0.00 | 0.132661E+09 | 0.00 | 0.00 | 0.663998E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.169200E+09 | 0.00 | 0.00 | 0.504043E+10 | 0.00 | 0.29 |
May | 0.00 | 1771674.41 | 0.00 | 38038256.49 | 0.00 | 0.00 | 0.362033E+10 | 0.00 | 0.29 |
June | 0.00 | 0.575773E+09 | 0.00 | 58944651.86 | 0.00 | 0.00 | 0.158859E+10 | 0.00 | 0.30 |
July | 0.00 | 0.162397E+10 | 0.00 | 34939306.48 | 0.00 | 0.00 | 0.273352E+09 | 0.00 | 0.28 |
August | 0.00 | 0.837183E+09 | 0.00 | 0.110771E+09 | 0.00 | 0.00 | 0.719861E+09 | 0.00 | 0.31 |
September | 0.00 | 0.223770E+09 | 0.00 | 30456496.58 | 0.00 | 0.00 | 0.197262E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 78879004.24 | 0.00 | 0.00 | 0.444421E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.111003E+09 | 0.00 | 0.00 | 0.564891E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.153415E+09 | 0.00 | 0.00 | 0.762913E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.308158E+10 | 0.326571E+10 | 0.00 | 0.977473E+09 | 0.00 | 0.00 | 0.502715E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6025021.96 | 0.00 | 0.00 | 0.273352E+09 | 0.00 | 0.28 |
Maximum of Months | 0.308158E+10 | 0.162397E+10 | 0.00 | 0.169200E+09 | 0.00 | 0.00 | 0.762913E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.632917E+09 | 0.00 | 0.00 | 153429.86 | 0.00 | 0.00 | 0.170231E+09 | 0.00 | 0.28 |
February | 378466.96 | 0.00 | 0.00 | 4320837.99 | 0.00 | 0.00 | 0.754856E+09 | 0.00 | 0.28 |
March | 0.00 | 317565.45 | 0.00 | 12046270.80 | 0.00 | 0.00 | 0.665287E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16145785.65 | 0.00 | 0.00 | 0.504891E+09 | 0.00 | 0.29 |
May | 0.00 | 185066.67 | 0.00 | 3483850.76 | 0.00 | 0.00 | 0.362702E+09 | 0.00 | 0.29 |
June | 0.00 | 57640000.18 | 0.00 | 5841043.28 | 0.00 | 0.00 | 0.159044E+09 | 0.00 | 0.30 |
July | 0.00 | 0.162361E+09 | 0.00 | 3477668.31 | 0.00 | 0.00 | 27397075.87 | 0.00 | 0.28 |
August | 0.00 | 83633103.37 | 0.00 | 11042095.35 | 0.00 | 0.00 | 72152057.57 | 0.00 | 0.31 |
September | 0.00 | 22399879.38 | 0.00 | 2764069.55 | 0.00 | 0.00 | 0.198267E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6925498.75 | 0.00 | 0.00 | 0.445727E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9826185.63 | 0.00 | 0.00 | 0.566304E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14090322.75 | 0.00 | 0.00 | 0.764239E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.633296E+09 | 0.326536E+09 | 0.00 | 90117058.69 | 0.00 | 0.00 | 0.469110E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 153429.86 | 0.00 | 0.00 | 27397075.87 | 0.00 | 0.28 |
Maximum of Months | 0.632917E+09 | 0.162361E+09 | 0.00 | 16145785.65 | 0.00 | 0.00 | 0.764239E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.654522E+09 | 0.00 | 0.00 | 0.474986E+12 | 0.00 | 7.17 |
February | 0.00 | 0.00 | 0.00 | 0.122298E+10 | 0.00 | 0.00 | 0.724833E+12 | 0.00 | 11.96 |
March | 0.00 | 0.00 | 0.00 | 0.173435E+10 | 0.00 | 0.00 | 0.100597E+13 | 0.00 | 23.03 |
April | 0.00 | 0.00 | 0.00 | 0.213709E+10 | 0.00 | 0.00 | 0.121653E+13 | 0.00 | 35.03 |
May | 0.00 | 0.00 | 0.00 | 0.548085E+09 | 0.00 | 0.00 | 0.424483E+12 | 0.00 | 18.46 |
June | 0.00 | 0.144385E+11 | 0.00 | 0.106788E+10 | 0.00 | 0.00 | 0.466510E+12 | 0.00 | 38.40 |
July | 0.00 | 0.948316E+11 | 0.00 | 0.130891E+10 | 0.00 | 0.00 | 0.230320E+12 | 0.00 | 43.69 |
August | 0.00 | 0.585420E+11 | 0.00 | 0.179942E+10 | 0.00 | 0.00 | 0.325240E+12 | 0.00 | 45.28 |
September | 0.00 | 0.686861E+09 | 0.00 | 0.562954E+09 | 0.00 | 0.00 | 0.340010E+12 | 0.00 | 24.38 |
October | 0.00 | 0.00 | 0.00 | 0.103583E+10 | 0.00 | 0.00 | 0.693844E+12 | 0.00 | 23.08 |
November | 0.00 | 0.00 | 0.00 | 0.147708E+10 | 0.00 | 0.00 | 0.101053E+13 | 0.00 | 26.04 |
December | 0.00 | 0.00 | 0.00 | 0.261839E+10 | 0.00 | 0.00 | 0.132852E+13 | 0.00 | 23.63 |
Annual Sum or Average | 0.00 | 0.168499E+12 | 0.00 | 0.161675E+11 | 0.00 | 0.00 | 0.824177E+13 | 0.00 | 26.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.548085E+09 | 0.00 | 0.00 | 0.230320E+12 | 0.00 | 7.17 |
Maximum of Months | 0.00 | 0.948316E+11 | 0.00 | 0.261839E+10 | 0.00 | 0.00 | 0.132852E+13 | 0.00 | 45.28 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:29
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.248921E+12 | 0.249001E+11 | 0.00 | 0.215886E+13 | 0.130607E+12 |
February | 0.386076E+12 | 0.260544E+11 | 0.00 | 0.230449E+13 | 0.178144E+12 |
March | 0.580728E+12 | 0.164865E+11 | 0.00 | 0.288907E+13 | 0.356700E+12 |
April | 0.703406E+12 | 0.134666E+11 | 0.00 | 0.320607E+13 | 0.413902E+12 |
May | 0.867763E+12 | 0.753296E+10 | 0.00 | 0.232008E+13 | 0.371087E+12 |
June | 0.933917E+12 | 0.320908E+10 | 0.00 | 0.156735E+13 | 0.143324E+13 |
July | 0.867216E+12 | -332693997.1 | 0.00 | 0.365767E+12 | 0.295703E+13 |
August | 0.739686E+12 | 0.138549E+10 | 0.00 | 0.108077E+13 | 0.289522E+13 |
September | 0.559618E+12 | 0.432292E+10 | 0.00 | 0.188786E+13 | 0.790175E+12 |
October | 0.374018E+12 | 0.103765E+11 | 0.00 | 0.270609E+13 | 0.289538E+12 |
November | 0.200225E+12 | 0.144567E+11 | 0.00 | 0.288519E+13 | 0.270531E+12 |
December | 0.224540E+12 | 0.264714E+11 | 0.00 | 0.307849E+13 | 0.345142E+12 |
Annual Sum or Average | 0.668612E+13 | 0.148330E+12 | 0.00 | 0.264501E+14 | 0.104313E+14 |
Minimum of Months | 0.200225E+12 | -332693997.1 | 0.00 | 0.365767E+12 | 0.130607E+12 |
Maximum of Months | 0.933917E+12 | 0.264714E+11 | 0.00 | 0.320607E+13 | 0.295703E+13 |