Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:21:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30952.55 | 668.23 | 668.23 |
Net Site Energy | 30952.55 | 668.23 | 668.23 |
Total Source Energy | 91192.22 | 1968.73 | 1968.73 |
Net Source Energy | 91192.22 | 1968.73 | 1968.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3281.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1301.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2726.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 330.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3382.84 |
Humidification | 2428.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.43 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 478.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27671.46 | 3281.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6566.43 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3281.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1301.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2726.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 330.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3382.84 |
Humidification | General | 2428.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.43 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 478.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3281.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1301.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2726.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 342.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 330.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3382.84 |
Humidification | Unassigned | 2428.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.43 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 478.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 164.25 | 70.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 597.39 | 70.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 164.25 | 70.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 597.39 | 70.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27671.458 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27671.458 | 100.00 |
Total On-Site and Utility Electric Sources | 27671.458 | 100.00 |
Total Electricity End Uses | 27671.458 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6566.43 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6566.43 | 100.00 |
Total Water End Uses | 6566.43 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 112.33 |
Time Setpoint Not Met During Occupied Cooling | 975.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5934.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:00 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 25-JUL-12:00 |
Heating | 0.00 | 2405335.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 414626.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 332285.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46313.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 74189.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4634.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 36020.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2132523.49 | 2405335.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2405335.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 414626.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 332285.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 46313.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 74189.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 4634.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 36020.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3556.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7804.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1129.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8635.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1046.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7691.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1514.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 87635.51 | 3556.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 76.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1891.94 | 76.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 76.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1891.94 | 76.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.74 | 0.368797 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.19 | 0.307225 | 0.261000 | 1.62 | 0.819266 | 0.500000 | 0.001240 | 0.000176 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 58.09 | 0.327419 | 0.278000 | 16.15 | 0.873117 | 0.500000 | 0.001164 | 0.003930 | 16.15 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.72 | 0.332796 | 0.283000 | 1.62 | 0.887457 | 0.500000 | 0.001145 | 0.000945 | 3.68 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.06 | 0.225903 | 0.192000 | 0.202979 | 0.602409 | 0.500000 | 0.001687 | 0.000163 | 0.634918 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.50 | 0.102877 | 0.087000 | 0.130153 | 0.300000 | 0.500000 | 0.003703 | 0.000112 | 0.436038 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.82 | 0.131001 | 0.111000 | 0.202362 | 0.349336 | 0.500000 | 0.002908 | 0.000181 | 0.704084 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.84 | 0.083567 | 0.071000 | 0.130761 | 0.300000 | 0.500000 | 0.004559 | 0.000091 | 0.355019 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.88 | 0.241818 | 0.206000 | 2.03 | 0.644847 | 0.500000 | 0.001576 | 0.002285 | 8.91 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.01 | 0.300000 | 0.500000 | 0.003963 | 0.001516 | 5.91 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.48 | 0.129253 | 0.110000 | 2.03 | 0.344676 | 0.500000 | 0.002948 | 0.002315 | 9.03 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 17.13 | 0.089863 | 0.076000 | 1.30 | 0.300000 | 0.500000 | 0.004240 | 0.001483 | 5.78 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.15 | 0.206941 | 0.181000 | 0.208884 | 0.551841 | 0.500000 | 0.001841 | 0.000296 | 1.15 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.60 | 0.096060 | 0.082000 | 0.131378 | 0.300000 | 0.500000 | 0.003966 | 0.000195 | 0.761087 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.98 | 0.120743 | 0.103000 | 0.203731 | 0.321981 | 0.500000 | 0.003155 | 0.000299 | 1.17 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.81 | 0.085256 | 0.072000 | 0.129975 | 0.300000 | 0.500000 | 0.004469 | 0.000194 | 0.757042 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20083.16 | 0.000176 | 421.98 | |
CORE_MID VAV BOX REHEAT COIL | 449229.87 | 0.003930 | 11577.63 | |
CORE_TOP VAV BOX REHEAT COIL | 108069.56 | 0.000945 | 2851.64 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18620.86 | 0.000163 | 491.13 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12786.38 | 0.000112 | 337.23 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20645.33 | 0.000181 | 544.48 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10415.46 | 0.000091 | 274.75 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 261150.67 | 0.002285 | 6885.91 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 173323.20 | 0.001516 | 4570.02 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 264672.71 | 0.002315 | 6978.71 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 169464.35 | 0.001483 | 4468.32 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33812.76 | 0.000296 | 891.42 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22298.56 | 0.000195 | 587.86 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34202.95 | 0.000299 | 901.71 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22180.03 | 0.000194 | 584.74 | |
VAV_BOT WITH REHEAT HEATING COIL | 79307.88 | 0.000694 | 1249.97 | |
VAV_MID WITH REHEAT HEATING COIL | 816454.67 | 0.007143 | 12712.10 | |
VAV_TOP WITH REHEAT HEATING COIL | 79344.00 | 0.000694 | 1258.82 | |
CAV_BAS HEATING COIL | 278147.73 | 0.000875 | 2621.31 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.563594 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.42 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.551363 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 28.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.20 | 2.28 | 12.41 | 3.21 | 10.31 | 10.31 | 0.300000 | 0.311286 | 10.31 |
VAV_MID WITH REHEAT | 59.79 | 22.83 | 119.58 | 44.48 | 95.81 | 95.81 | 0.300000 | 0.464284 | 95.81 |
VAV_TOP WITH REHEAT | 6.13 | 2.29 | 12.25 | 7.52 | 10.92 | 10.92 | 0.300000 | 0.688769 | 10.92 |
CAV_BAS | 0.000000 | 0.000000 | 5.74 | 1.20 | 5.74 | 5.74 | 1.00 | 0.208985 | 5.74 |
AIRLOOP DATACENTER BASEMENT | 28.03 | 28.03 | 28.03 | 28.03 | 28.03 | 28.03 | 1.00 | 0.999994 | 28.03 |
AIRLOOP DATACENTER BOT | 0.563594 | 0.563594 | 0.563594 | 0.563594 | 0.563594 | 0.563594 | 1.00 | 1.00 | 0.563594 |
AIRLOOP DATACENTER MID | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 1.00 | 1.00 | 5.42 |
AIRLOOP DATACENTER TOP | 0.551363 | 0.551363 | 0.551363 | 0.551363 | 0.551363 | 0.551363 | 1.00 | 1.00 | 0.551363 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.31 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 95.81 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.92 | |
CAV_BAS_OA_CONTROLLER | 5.74 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 28.03 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.563594 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.42 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.551363 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.85 | 6.67 | 10.68 | 0.007139 | 0.007000 | 171416.14 | 0.004902 | 10.31 |
VAV_MID WITH REHEAT COOLING COIL | 26.03 | 6.67 | 10.68 | 0.007140 | 0.007000 | 1612093.07 | 0.046106 | 95.81 |
VAV_TOP WITH REHEAT COOLING COIL | 25.75 | 6.67 | 10.68 | 0.007130 | 0.007000 | 180218.70 | 0.005154 | 10.92 |
CAV_BAS COOLING COIL | 26.02 | 6.67 | 10.66 | 0.007258 | 0.007000 | 98584.16 | 0.002819 | 5.74 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.31 |
VAV_MID WITH REHEAT FAN | 95.81 |
VAV_TOP WITH REHEAT FAN | 10.92 |
CAV_BAS FAN | 5.74 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004902 | 0.000097 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000694 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.046106 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007143 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005154 | 0.000092 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000694 | |
CAV_BAS_COOLC_CONTROLLER | 0.002819 | 0.000169 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 28.03 | 532339.42 | 299666.29 | 0.013037 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.563594 | 10407.73 | 5919.68 | 0.000255 |
AIRLOOP DATACENTER MID COOLING COIL | 5.42 | 100061.75 | 56902.50 | 0.002451 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.551363 | 10183.54 | 5791.55 | 0.000249 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 28.03 | 28.03 | 28.03 | 28.03 | 532339.42 | 532339.42 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.563594 | 0.563594 | 0.563594 | 0.563594 | 10407.73 | 10407.73 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.42 | 5.42 | 5.42 | 5.42 | 100061.75 | 100061.75 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.551363 | 0.551363 | 0.551363 | 0.551363 | 10183.54 | 10183.54 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 28.03 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.563594 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.42 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.551363 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 28.03 | 532339.42 | 0.013037 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.563594 | 10407.73 | 0.000255 |
AIRLOOP DATACENTER MID HEATING COIL | 5.42 | 100061.75 | 0.002451 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.551363 | 10183.54 | 0.000249 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000218 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.058982 | 9534.59 | |
HEATSYS1 PUMP | 0.023586 | 7032.84 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.058982 | 7.08 |
HEATSYS1 | 0.023586 | 2.83 |
COOLSYS1_SUPPLY | 0.058982 | 7.08 |
SINGLE WATER PLANT LOOP | 0.015992 | 1.92 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.058982 | 0.058982 | 247576.48 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2696062.39 | 2696062.39 | 0.023586 |
CENTRAL BOILER | 658722.70 | 644329.78 | 0.015992 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.029491 | 3300.56 |
COOLSYS1 CHILLER2 PUMP | 0.029491 | 3300.56 |
PLANT CIRC PUMP | 0.015992 | 4038.31 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.058982 | 0.029662 | 1037137.47 | 1037137.53 | 0.053307 |
COOLSYS1 CHILLER2 | 0.058982 | 0.029662 | 1037137.47 | 1037137.53 | 0.053307 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015992 | 158786.14 | 80384.38 | 79393.07 | 7004.20 | 48230.63 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.106614 | 12.79 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.106614 | 26133.86 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 45.76 | 1243009.72 | 9.15 | 155376.21 |
TOWERWATERSYS COOLTOWER 2 | 45.76 | 1243009.72 | 9.15 | 155376.21 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.053782 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8952 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8506 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.077 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9497 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.008 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7608 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.25194710E-14 | 0.31545203E-16 | -0.15133332E-09 | 0.44281407E-16 |
51 | 8 | 0.22101568E-07 | 0.12077324E-12 | 0.38017447E-03 | -0.25130244E-09 |
52 | 7 | -0.12312625E-01 | 0.62550027E-08 | -0.23188143E-01 | 0.13999903E-03 |
53 | 6 | 0.40728147 | 0.21773539E-05 | 0.47373573 | -0.47705255E-02 |
54 | 5 | -5.2094091 | 0.81341902E-04 | -4.4538940 | 0.63417525E-01 |
55 | 4 | 33.086216 | 0.66572093E-03 | 21.489723 | -0.42322968 |
56 | 3 | -111.40360 | 0.14515221E-02 | -55.721658 | 1.5177572 |
57 | 2 | 197.30704 | 0.81680373E-03 | 77.964377 | -2.9035099 |
58 | 1 | -171.22951 | 0.87228510E-04 | -55.280715 | 2.7467265 |
59 | 0 | 57.057407 | 0.49677855E-06 | 15.554344 | |
60 | 9 | -0.24471812E-14 | 0.33150161E-16 | -0.15341684E-09 | 0.41895861E-16 |
61 | 8 | 0.22394247E-07 | 0.11501389E-12 | 0.38323131E-03 | -0.25463030E-09 |
62 | 7 | -0.12403778E-01 | 0.59379868E-08 | -0.23319368E-01 | 0.14103548E-03 |
63 | 6 | 0.40975819 | 0.20644311E-05 | 0.47584355 | -0.47997200E-02 |
64 | 5 | -5.2335779 | 0.77040749E-04 | -4.4700764 | 0.63717207E-01 |
65 | 4 | 33.193114 | 0.62990908E-03 | 21.552961 | -0.42464900 |
66 | 3 | -111.63102 | 0.13722529E-02 | -55.846672 | 1.5210429 |
67 | 2 | 197.53241 | 0.77160263E-03 | 78.079059 | -2.9070889 |
68 | 1 | -171.31275 | 0.82342669E-04 | -55.314112 | 2.7481854 |
69 | 0 | 57.057407 | 0.46858505E-06 | 15.548868 | |
70 | 9 | -0.15654789E-15 | 0.36780279E-16 | -0.14275499E-09 | -0.53833073E-18 |
71 | 8 | 0.20895136E-07 | 0.14393424E-12 | 0.36742668E-03 | -0.23758489E-09 |
72 | 7 | -0.11931991E-01 | 0.75543961E-08 | -0.22640018E-01 | 0.13567108E-03 |
73 | 6 | 0.39693859 | 0.26436989E-05 | 0.46492102 | -0.46486079E-02 |
74 | 5 | -5.1084706 | 0.99216708E-04 | -4.3861655 | 0.62165936E-01 |
75 | 4 | 32.639712 | 0.81537030E-03 | 21.224928 | -0.41730137 |
76 | 3 | -110.45353 | 0.17843548E-02 | -55.198128 | 1.5040313 |
77 | 2 | 196.36533 | 0.10073836E-02 | 77.484335 | -2.8885557 |
78 | 1 | -170.88163 | 0.10790658E-03 | -55.141337 | 2.7406295 |
79 | 0 | 57.057407 | 0.61658484E-06 | 15.577537 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3093E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3116E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1817E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1836E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7111E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7125E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6293E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6301E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3606E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5081E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2248E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3532E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7469E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8525E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6510E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7062E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1729 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4524E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1983 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1097 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1134 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6933E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7533E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6532E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3722E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5706E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2378E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4231E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7565E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8895E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6516E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7078E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3091E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3118E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1815E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1838E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7110E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7127E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6292E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6300E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5567E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0294E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4478E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0025E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6481E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7972E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4956E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5336E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.6012E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6946E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4278E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5140E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9759E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9143E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9489E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8512E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4067E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5210E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2495E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3336E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6024E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6364E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4957E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5342E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8902E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8925E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4496E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4515E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1436E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1450E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6294E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6302E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9423E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0738E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4934E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6004E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1799E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2611E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6516E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7079E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7816E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5253E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6801E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9208E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2854E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2743E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7533E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6527E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9396E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0746E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4892E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5944E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1723E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2373E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6511E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7062E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8900E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8923E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4494E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4512E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1434E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1446E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6293E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6301E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4291E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5502E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9909E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0787E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9235E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9535E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4958E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5343E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8894E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9861E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2362E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6040E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7206E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4002E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9489E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8512E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5282E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8138E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1232E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4337E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9646E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0909E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4955E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5335E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1776 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1307 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1988 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1504 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1275 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9340E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8206E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8791E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.9955E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.2808E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.8065E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0828E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2319E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2531E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9696E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9121E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8957E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9199E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6504E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0956E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2200E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2855E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8206E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8786E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0602E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3050E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3274E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8275E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8265E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5743E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9696E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9121E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1777 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1310 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1988 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1506 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1277 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9505E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8330E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8854E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.0015E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.2891E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.8135E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.0912E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2443E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2623E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9821E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9184E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8961E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9244E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6511E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0991E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2267E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2898E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8331E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8850E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0636E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3111E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3312E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8330E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8368E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5816E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9821E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9184E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69559.95576 | 69559.95576 | 5.74279 | 5.74279 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 74989.82506 | 74989.82506 | 6.19105 | 6.19105 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 5854.17579 | 5854.17579 | 0.28426 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 703828.57538 | 703828.57538 | 58.09206 | 58.09206 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 307017.01721 | 307017.01721 | 14.84581 | 14.84581 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 68608.37164 | 68608.37164 | 5.71534 | 5.71534 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 75652.05336 | 75652.05336 | 3.68131 | 3.68131 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12690.91989 | 12690.91989 | 1.05718 | 1.05718 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13031.34618 | 13031.34618 | 0.63492 | 0.63492 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17959.03171 | 17959.03171 | 1.49601 | 1.49601 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.09333 | 6.29258E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8947.62921 | 8947.62921 | 0.43604 | 0.43604 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 21885.35679 | 21885.35679 | 1.82308 | 1.82308 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.00000 | 6.30621E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14446.64867 | 14446.64867 | 0.70408 | 0.70408 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 22108.99133 | 22108.99133 | 1.84170 | 1.84170 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7290.43611 | 7290.43611 | 0.35502 | 0.35502 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 118557.79718 | 118557.79718 | 9.87607 | 9.87607 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 182720.39043 | 182720.39043 | 8.91030 | 8.91030 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 192175.93420 | 192175.93420 | 16.00839 | 16.00839 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 121267.58421 | 121267.58421 | 5.91394 | 5.91394 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 221813.61015 | 221813.61015 | 18.47732 | 18.47732 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 185182.71169 | 185182.71169 | 9.03065 | 9.03065 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 205599.57168 | 205599.57168 | 17.12658 | 17.12658 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.09333 | 6.30170E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 118569.51867 | 118569.51867 | 5.78212 | 5.78212 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13485.15429 | 13485.15429 | 1.12333 | 1.12333 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 23654.55716 | 23654.55716 | 1.15405 | 1.15405 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 19233.67327 | 19233.67327 | 1.60218 | 1.60218 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15599.36886 | 15599.36886 | 0.76109 | 0.76109 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 23744.86366 | 23744.86366 | 1.97797 | 1.97797 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 23927.35468 | 23927.35468 | 1.16739 | 1.16739 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 21671.11723 | 21671.11723 | 1.80521 | 1.80521 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 15516.46448 | 15516.46448 | 0.75704 | 0.75704 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8577.80478 | 8577.80478 | 0.56359 | 0.56359 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 82445.03714 | 82445.03714 | 5.41698 | 5.41698 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8391.63186 | 8391.63186 | 0.55136 | 0.55136 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370909.78082 | 426546.24794 | 24.36984 | 28.02531 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 142273.93 | 10.30525 | 10.30525 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 86549.16 | 3.20788 | 3.20788 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1317511.55 | 95.80955 | 95.80955 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 865464.27 | 44.48282 | 44.48282 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 149110.28 | 10.91930 | 10.91930 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 86793.03 | 7.52088 | 7.52088 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 |
7 | CAV_BAS | Cooling | Sensible | 71298.45 | 5.74279 | 5.74279 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422910.12 | 28.02549 | 28.02549 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8456.41 | 0.56359 | 0.56359 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81273.70 | 5.41698 | 5.41698 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8272.62 | 0.55136 | 0.55136 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.74279 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.36880 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.19105 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30722 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61586 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81927 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24013E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75696E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61586 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20083.16494 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75696E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 421.98113 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 58.09206 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32742 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.14959 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87312 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16365E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.93006E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.14959 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 449229.87449 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.93006E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11577.63091 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.71534 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33280 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61744 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88746 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14484E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.45440E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.68131 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108069.56015 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.45440E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2851.63912 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05718 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22590 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19200 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20298 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60241 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68656E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62903E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63492 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18620.86280 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62903E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 491.13299 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49601 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10288 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.70000E-002 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13015 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70345E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11861E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43604 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12786.37580 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11861E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.22501 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82308 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13100 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20236 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34934 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90837E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80614E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70408 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20645.33483 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80614E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 544.48078 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.84170 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.35669E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.10000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13076 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.55922E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.11190E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35502 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10415.46281 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.11190E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.75414 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.87607 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24182 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20600 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03447 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64485 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57557E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28466E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.91030 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 261150.66823 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28466E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6885.90645 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.00839 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.96296E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51631E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.91394 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 173323.20148 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51631E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4570.01613 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.47732 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12925 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03251 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34468 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94770E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.31547E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.03065 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 264672.70937 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.31547E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6978.71064 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.12658 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.98633E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.60000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30162 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23978E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48255E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.78212 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 169464.34992 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48255E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4468.32467 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15405 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20694 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20888 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55184 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84111E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.95809E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15405 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33812.75591 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.95809E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 891.42434 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60218 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.60601E-002 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.20000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13138 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.96627E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.95078E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76109 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22298.55746 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.95078E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 587.86170 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97797 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12074 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20373 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32198 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15546E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.99222E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16739 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34202.94567 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.99222E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 901.70579 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80521 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.52558E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.20000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12998 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.46890E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94041E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75704 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22180.03001 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94041E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 584.73692 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56359 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.41698 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55136 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 28.02531 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.20451 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28212 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.40902 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.20788 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.30525 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.30525 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31129 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.79021 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.83088 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 119.58042 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 44.48282 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 95.80955 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 95.80955 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46428 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.12737 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.29141 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.25475 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.52088 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.91930 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.91930 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.68877 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74279 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.74279 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.74279 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20899 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 28.02531 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.02531 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 28.02531 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.02531 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 28.02549 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 28.02549 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56359 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56359 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56359 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56359 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56359 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.56359 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.41698 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.41698 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.41698 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.41698 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.41698 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.41698 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55136 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55136 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55136 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55136 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55136 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.55136 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.30525 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 95.80955 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.91930 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.74279 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 28.02549 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.56359 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.41698 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.55136 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.30525 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.85199 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68140 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13853E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 171416.13575 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.90248E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.30525 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 79307.87552 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.93820E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1249.96764 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.30525 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.90248E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.71326E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.93820E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 95.80955 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.02694 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68140 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14024E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1612093.07095 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.61057E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 95.80955 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 816454.66712 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.14270E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 12712.10160 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 95.80955 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.61057E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.03282E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.14270E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.91930 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.75374 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68136 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.12961E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 180218.69594 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.15423E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.91930 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 79343.99704 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.94136E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1258.81518 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.91930 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.15423E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.23883E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.94136E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.74279 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.02491 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.65681 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.25808E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 98584.16179 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.81949E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.74279 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 278147.73299 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2621.30818 |
350 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.74279 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.81949E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.68892E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 28.02549 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 28.02549 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 532339.41904 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 299666.28803 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.30370E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 28.02549 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 28.02549 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 28.02549 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 28.02549 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 532339.41904 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 532339.41904 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 28.02549 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 28.02549 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 532339.41904 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.30370E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.18236E-004 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56359 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56359 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10407.73372 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5919.68274 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54885E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56359 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56359 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56359 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56359 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10407.73372 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10407.73372 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56359 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56359 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10407.73372 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54885E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.41698 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.41698 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 100061.74525 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 56902.50289 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.45051E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.41698 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.41698 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.41698 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.41698 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 100061.74525 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 100061.74525 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.41698 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.41698 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 100061.74525 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.45051E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55136 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55136 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10183.54001 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5791.55005 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49394E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.55136 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.55136 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.55136 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.55136 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10183.54001 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10183.54001 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55136 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55136 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10183.54001 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49394E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.89819E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9534.59020 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.89819E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.07782 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.89819E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.89819E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 247576.47832 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.35863E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.83036 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.35863E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7032.83840 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2696062.39354 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2696062.39000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.35863E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.89819E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.07782 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.94909E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3300.55917 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.94909E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3300.55917 |
456 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.89819E-002 |
457 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.96620E-002 |
458 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1037137.46835 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1037137.53000 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.33069E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.89819E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.96620E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1037137.46835 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1037137.53000 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.33069E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.59917E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.91901 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.59917E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 4038.31101 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.59917E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 158786.14235 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 80384.37764 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 79393.07117 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 48230.62658 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 658722.70451 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 644329.78000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.59917E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10661 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.79364 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10661 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 26133.85522 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 45.76126 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1243009.71952 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.15225 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 155376.21494 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 45.76126 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1243009.71952 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.15225 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 155376.21494 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.37825E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.37825E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 19042.07 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 425566.26 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 102426.23 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17647.03 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12117.53 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19565.30 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9871.04 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 247479.17 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 164248.92 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 250816.40 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 160592.47 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32041.71 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21130.55 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32411.42 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21018.23 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 55735.03 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 558342.21 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 56574.11 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94845.12 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 183716.48 | 130625.37 | 53091.11 | 0.71 | 18915.47 | 191.85 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1716964.48 | 1217998.26 | 498966.21 | 0.71 | 176248.81 | 1787.61 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 193897.88 | 138087.61 | 55810.27 | 0.71 | 19991.78 | 202.77 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 104558.81 | 73816.04 | 30742.78 | 0.71 | 10807.29 | 109.61 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3493743875E-003 | 1.4641878582E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.3621945815E-002 | 0.1427699229 | Pass | Pass | 9.1003637499E-002 | 0.2874001397 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.1245706287E-002 | 6.8851941093E-002 | Pass | Pass | 6.3025036470E-002 | 0.2428514575 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.9951894106E-002 | 2.7700968310E-002 | Pass | Pass | 0.3975036534 | 0.4847551993 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9873006235E-002 | 9.2136391473E-002 | Pass | Pass | 9.0553458710E-002 | 0.2864300595 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.1764157627E-002 | 0.1427565772 | Pass | Pass | 9.1868138532E-002 | 0.2898962306 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2078723626 | 0.3980018767 | Pass | Pass | 0.1141796788 | 0.3715102764 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.1477826942E-002 | 0.1143251286 | Pass | Pass | 8.9818962970E-002 | 0.2828468930 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7561389149E-002 | 2.9503966742E-002 | Pass | Pass | 6.2301791265E-002 | 0.2396267947 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.0212468888E-002 | 9.9889309328E-002 | Pass | Pass | 6.3712088127E-002 | 0.2453526793 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1967578745 | 0.3055635113 | Pass | Pass | 7.4361978768E-002 | 0.3042044093 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9119916137E-002 | 7.2408000500E-002 | Pass | Pass | 6.0607385235E-002 | 0.2304896376 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2600667991 | 0.2934265092 | Pass | Pass | 29.1029816182 | 91.6931306499 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1805815609 | 0.2407501187 | Pass | Pass | 32.4794471723 | 198.2700639197 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1982685923 | 0.1747118369 | Pass | Pass | 4.1284965877 | 35.0596732326 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1381353408 | 0.1652997593 | Pass | Pass | 9.4598657623 | 54.9742270954 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.5630562587E-002 | 2.7615303525E-002 | Pass | Pass | 0.1671074534 | 0.6030413833 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9550869611E-002 | 3.8565698409E-002 | Pass | Pass | 8.6728564623E-002 | 0.3875306753 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.2785039438E-002 | 6.3849192014E-002 | Pass | Pass | 0.3993028324 | 0.4774174067 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.5730520167E-006 | 5.9641966847E-006 | Pass | Pass | 3.3322107309E-003 | 3.2842861245E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7467847423E-006 | 8.6125483498E-006 | Pass | Pass | 0.1413092603 | 0.4571247461 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.4427643789E-002 | 2.6705722189E-002 | Pass | Pass | 7.0005912941E-003 | 7.5008975394E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9551266861E-005 | 2.5151317127E-005 | Pass | Pass | 6.1879592023E-005 | 1.0595176955E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6686.15 | 145.33 | 0.00 | 30327.72 | 9722.49 | 46881.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.342_SHGC_EAST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 1390.74 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.76 | 0.0000 | Y | 10.78 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.48 | 0.0000 | Y | 6.88 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 10.60 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.53 | 0.0000 | Y | 6.89 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.72 | 0.0000 | Y | 107.61 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.45 | 0.0000 | Y | 68.70 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.28 | 0.0000 | Y | 105.93 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.50 | 0.0000 | Y | 68.81 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.71 | 0.0000 | Y | 10.76 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.45 | 0.0000 | Y | 6.87 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.28 | 0.0000 | Y | 10.59 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.50 | 0.0000 | Y | 6.88 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 776.08 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.11 | 42.11 | 104.90 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.57 | 62.84 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.57 | 48.07 | 239.97 | |
Exterior Lighting Total | 40855.88 | 356.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2055959.96 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2696062.39 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1037137.53 | 5.17 | 1033625.43 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1037137.53 | 5.17 | 1033625.43 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 661741.25 | |||||
CENTRAL BOILER | Boiler:HotWater | 644329.78 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1243009.72 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1243009.72 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 171416.14 | 183716.48 | 130625.37 | 53091.11 | 0.71 | - | 18915.47 | 191.85 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1612093.07 | 1716964.48 | 1217998.26 | 498966.21 | 0.71 | - | 176248.81 | 1787.61 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 180218.70 | 193897.88 | 138087.61 | 55810.27 | 0.71 | - | 19991.78 | 202.77 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 98584.16 | 104558.81 | 73816.04 | 30742.78 | 0.71 | - | 10807.29 | 109.61 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 532339.42 | 299666.29 | 232673.13 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10407.73 | 5919.68 | 4488.05 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 100061.75 | 56902.50 | 43159.24 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10183.54 | 5791.55 | 4391.99 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 20083.16 | 19042.07 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 449229.87 | 425566.26 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 108069.56 | 102426.23 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18620.86 | 17647.03 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12786.38 | 12117.53 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20645.33 | 19565.30 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10415.46 | 9871.04 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 261150.67 | 247479.17 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 173323.20 | 164248.92 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 264672.71 | 250816.40 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 169464.35 | 160592.47 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 33812.76 | 32041.71 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22298.56 | 21130.55 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34202.95 | 32411.42 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22180.03 | 21018.23 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 79307.88 | 55735.03 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 816454.67 | 558342.21 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 79344.00 | 56574.11 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94845.12 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 532339.42 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10407.73 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 100061.75 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10183.54 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.31 | 23409.35 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 95.81 | 217640.32 | 2271.59 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.92 | 24804.22 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.74 | 13199.58 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 28.03 | 46027.15 | 1642.33 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 631.29 | 1120.11 | 1.00 | 1.55 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.42 | 6067.60 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 617.59 | 1120.11 | 1.00 | 1.56 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.058982 | 9534.59 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.023586 | 7032.84 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029491 | 3300.56 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.029491 | 3300.56 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015992 | 4038.31 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.106614 | 26133.86 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69559.96 | 69559.96 | 25.03 | 5.743 | 5.743 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00750 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 74989.83 | 74989.83 | 30.04 | 6.191 | 6.191 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 703828.58 | 703828.58 | 281.97 | 58.092 | 58.092 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00744 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 68608.37 | 68608.37 | 27.49 | 5.715 | 5.715 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00744 | 33.24 | 0.00631 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12690.92 | 12690.92 | 40.49 | 1.057 | 1.057 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00729 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17959.03 | 17959.03 | 88.92 | 1.496 | 1.496 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00713 | 24.09 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 21885.36 | 21885.36 | 69.83 | 1.823 | 1.823 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00717 | 33.00 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 22108.99 | 22108.99 | 109.46 | 1.842 | 1.842 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00711 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 118557.80 | 118557.80 | 378.28 | 9.876 | 9.876 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00729 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 192175.93 | 192175.93 | 951.48 | 16.008 | 16.008 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00712 | 25.51 | 0.00629 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 221813.61 | 221813.61 | 707.72 | 18.477 | 18.477 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00716 | 33.13 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 205599.57 | 205599.57 | 1017.94 | 17.127 | 17.127 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00711 | 30.09 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13485.15 | 13485.15 | 43.03 | 1.123 | 1.123 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00725 | 33.24 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19233.67 | 19233.67 | 95.23 | 1.602 | 1.602 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00711 | 25.96 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23744.86 | 23744.86 | 75.76 | 1.978 | 1.978 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00714 | 33.27 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 21671.12 | 21671.12 | 107.30 | 1.805 | 1.805 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8577.80 | 8577.80 | 236.94 | 0.564 | 0.564 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 82445.04 | 82445.04 | 2277.31 | 5.417 | 5.417 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8391.63 | 8391.63 | 231.80 | 0.551 | 0.551 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370909.78 | 426546.25 | 544.29 | 24.370 | 28.025 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.00 | 22.83 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 5854.18 | 5854.18 | 2.35 | 0.284 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 307017.02 | 307017.02 | 123.00 | 14.846 | 14.846 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 75652.05 | 75652.05 | 30.31 | 3.681 | 3.681 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13031.35 | 13031.35 | 41.58 | 0.635 | 0.635 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8947.63 | 8947.63 | 44.30 | 0.436 | 0.436 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14446.65 | 14446.65 | 46.09 | 0.704 | 0.704 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7290.44 | 7290.44 | 36.10 | 0.355 | 0.355 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 182720.39 | 182720.39 | 583.00 | 8.910 | 8.910 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 121267.58 | 121267.58 | 600.41 | 5.914 | 5.914 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 185182.71 | 185182.71 | 590.85 | 9.031 | 9.031 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 118569.52 | 118569.52 | 587.05 | 5.782 | 5.782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 23654.56 | 23654.56 | 75.47 | 1.154 | 1.154 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15599.37 | 15599.37 | 77.23 | 0.761 | 0.761 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23927.35 | 23927.35 | 76.34 | 1.167 | 1.167 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15516.46 | 15516.46 | 76.82 | 0.757 | 0.757 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.45 | 0.00097 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.44 | 0.00097 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 19.93 | 0.00097 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.31 | 10.31 | 3.21 | 3.21 | 10.3053 | 3.2079 | 10.3053 | 0.3113 | 0.3000 |
VAV_MID WITH REHEAT | 95.81 | 95.81 | 44.48 | 44.48 | 95.8095 | 44.4828 | 95.8095 | 0.4643 | 0.3000 |
VAV_TOP WITH REHEAT | 10.92 | 10.92 | 7.52 | 7.52 | 10.9193 | 7.5209 | 10.9193 | 0.6888 | 0.3000 |
CAV_BAS | 5.74 | 5.74 | 1.20 | 1.20 | 5.7428 | 1.2002 | 5.7428 | 0.2090 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 28.03 | 28.03 | 0.34 | 0.34 | 28.0255 | 28.0253 | 28.0255 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.56 | 0.56 | 0.02 | 0.02 | 0.5636 | 0.5636 | 0.5636 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.42 | 5.42 | 0.16 | 0.16 | 5.4170 | 5.4170 | 5.4170 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.55 | 0.55 | 0.02 | 0.02 | 0.5514 | 0.5514 | 0.5514 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20083.165 | 20083.165 | 1.615864 | 0.00017570 | 421.981 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20083.16 | 20083.16 | 1.615864 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799004 | 45.1754 | 5854.18 | 0.00 | 20155.77 | 20155.77 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 449229.874 | 449229.874 | 16.149593 | 0.00393006 | 11577.631 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 449229.87 | 449229.87 | 16.149593 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 307017.02 | 0.00 | 450609.61 | 450609.61 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 108069.560 | 108069.560 | 3.681310 | 0.00094544 | 2851.639 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 108069.56 | 108069.56 | 3.681310 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 75652.05 | 0.00 | 108435.35 | 108435.35 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18620.863 | 18620.863 | 0.634918 | 0.00016290 | 491.133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18620.86 | 18620.86 | 0.634918 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788115 | 44.5688 | 13031.35 | 0.00 | 18682.33 | 18682.33 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12786.376 | 12786.376 | 0.436038 | 0.00011186 | 337.225 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12786.38 | 12786.38 | 0.436038 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789006 | 44.6185 | 8947.63 | 0.00 | 12828.43 | 12828.43 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20645.335 | 20645.335 | 0.704084 | 0.00018061 | 544.481 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20645.33 | 20645.33 | 0.704084 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00790040 | 44.6761 | 14446.65 | 0.00 | 20713.13 | 20713.13 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10415.463 | 10415.463 | 0.355019 | 0.00009112 | 274.754 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10415.46 | 10415.46 | 0.355019 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782639 | 44.2635 | 7290.44 | 0.00 | 10450.15 | 10450.15 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 261150.668 | 261150.668 | 8.910296 | 0.00228466 | 6885.906 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 261150.67 | 261150.67 | 8.910296 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782597 | 44.2617 | 182720.39 | 0.00 | 261997.91 | 261997.91 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 173323.201 | 173323.201 | 5.913945 | 0.00151631 | 4570.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 173323.20 | 173323.20 | 5.913945 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782556 | 44.2594 | 121267.58 | 0.00 | 173884.83 | 173884.83 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 264672.709 | 264672.709 | 9.030646 | 0.00231547 | 6978.711 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 264672.71 | 264672.71 | 9.030646 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782840 | 44.2753 | 185182.71 | 0.00 | 265530.92 | 265530.92 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 169464.350 | 169464.350 | 5.782122 | 0.00148255 | 4468.325 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 169464.35 | 169464.35 | 5.782122 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782138 | 44.2362 | 118569.52 | 0.00 | 170013.87 | 170013.87 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 33812.756 | 33812.756 | 1.154054 | 0.00029581 | 891.424 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33812.76 | 33709.98 | 1.154054 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783422 | 44.3082 | 23654.56 | 0.00 | 33921.48 | 33921.48 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22298.557 | 22298.557 | 0.761087 | 0.00019508 | 587.862 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22298.56 | 22298.56 | 0.761087 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783244 | 44.2983 | 15599.37 | 0.00 | 22370.20 | 22370.20 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 34202.946 | 34202.946 | 1.167387 | 0.00029922 | 901.706 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34202.95 | 34202.95 | 1.167387 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783608 | 44.3185 | 23927.35 | 0.00 | 34312.88 | 34312.88 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22180.030 | 22180.030 | 0.757042 | 0.00019404 | 584.737 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22180.03 | 22180.03 | 0.757042 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783164 | 44.2938 | 15516.46 | 0.00 | 22251.29 | 22251.29 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 171416.136 | -999.000 | 10.305254 | 0.00490248 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 171416.14 | 168355.67 | 10.305254 | 25.85 | 14.51 | 0.00713853 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 19.7035 | 24.00 | 0.00734273 | 34.6353 | 123651.16 | 0.00 | 124976.11 | 124976.11 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 79307.876 | 79307.876 | 3.091576 | 0.00069382 | 1249.968 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79307.88 | 79307.88 | 3.091576 | -11.44 | -11.44 | 0.00290252 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 65.6785 | 19.73 | 0.00775291 | 47.4274 | 23424.11 | 0.00 | 67393.80 | 67393.80 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1612093.071 | -999.000 | 95.809545 | 0.04610566 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1612093.07 | 1583218.99 | 95.809545 | 26.03 | 14.58 | 0.00714024 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 21.1941 | 24.00 | 0.00736949 | 34.7600 | 1129913.41 | 0.00 | 1176621.43 | 1176621.43 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 816454.667 | 816454.667 | 28.742864 | 0.00714270 | 12712.102 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 816454.67 | 816454.67 | 28.742864 | -14.04 | -14.04 | 0.00251092 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 70.6471 | 17.92 | 0.00770382 | 52.7875 | 244539.91 | 0.00 | 674964.45 | 674964.45 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 180218.696 | -999.000 | 10.919304 | 0.00515423 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 180218.70 | 177189.80 | 10.919304 | 25.75 | 14.47 | 0.00712961 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 18.5955 | 24.00 | 0.00731845 | 34.5220 | 130575.99 | 0.00 | 131260.52 | 131260.52 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 79343.997 | 79343.997 | 3.275791 | 0.00069414 | 1258.815 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79344.00 | 79344.00 | 3.275791 | -10.09 | -10.09 | 0.00313932 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 61.9850 | 16.42 | 0.00775259 | 58.3997 | 24953.77 | 0.00 | 68417.63 | 68417.63 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 98584.162 | -999.000 | 5.742787 | 0.00281949 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 98584.16 | 95382.46 | 5.742787 | 26.02 | 14.68 | 0.00725808 | 10.66 | 8.50 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 20.8985 | 24.00 | 0.00755163 | 35.6092 | 61154.71 | 0.00 | 72396.21 | 72396.21 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.474082 | -5.77 | -9.97 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 34.5460 | 22.93 | 0.00034190 | 1.7392 | 0.00 | 0.00 | 100050.95 | 100050.95 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 532339.419 | 299666.288 | 28.025486 | 0.01303696 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 462503.95 | 460742.41 | -999.0 | 28.66 | 15.39 | 0.00703336 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704225 | 27.8125 | 370483.76 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10407.734 | 5919.683 | 0.563594 | 0.00025488 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 8995.07 | 8929.62 | -999.0 | 28.06 | 15.21 | 0.00706221 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708408 | 27.9739 | 8577.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100061.745 | 56902.503 | 5.416976 | 0.00245051 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 86484.37 | 85831.28 | -999.0 | 28.06 | 15.21 | 0.00706459 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708743 | 27.9871 | 82445.04 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10183.540 | 5791.550 | 0.551363 | 0.00024939 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 8801.56 | 8736.11 | -999.0 | 28.06 | 15.21 | 0.00706360 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708600 | 27.9814 | 8391.63 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 532339.419 | 532339.419 | 28.025486 | 0.01303696 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 532339.42 | 532339.42 | 28.025486 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.2074 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10407.734 | 10407.734 | 0.563594 | 0.00025488 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10407.73 | 10407.73 | 0.563594 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7737 | 25.24 | 0.00097295 | 4.3040 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100061.745 | 100061.745 | 5.416976 | 0.00245051 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100061.75 | 100061.75 | 5.416976 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8858 | 23.65 | 0.00097296 | 4.7349 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10183.540 | 10183.540 | 0.551363 | 0.00024939 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10183.54 | 10183.54 | 0.551363 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8352 | 22.14 | 0.00097241 | 5.1845 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 28.025486 | -0.33 | -0.33 | 0.00691961 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.2074 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.563594 | -0.77 | -5.62 | 0.00095544 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7737 | 25.24 | 0.00097295 | 4.3040 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.416976 | -0.80 | -5.64 | 0.00095475 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8858 | 23.65 | 0.00097296 | 4.7349 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.551363 | -0.78 | -5.64 | 0.00095453 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8352 | 22.14 | 0.00097241 | 5.1845 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 20083.165 | 20083.165 | 1.615864 | 0.00017570 | 421.981 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.7302 | 0.744907 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20083.16 | 20083.16 | 1.0000 | 1.70173074 | 1.615864 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.17567837 | 60.00 | 32.22 | 27.78 | 0.000 | 20083.16 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.85 | 0.00799004 | 21.00 | 0.00799004 | 45.1754 | 5854.18 | 0.00 | 20155.77 | 20155.77 | 1.70173074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.42 | 16.10 | 0.00800000 | 44904.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 449229.874 | 449229.874 | 16.149593 | 0.00393006 | 11577.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 16.3337 | 16.662444 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 449229.87 | 449229.87 | 1.0000 | 17.00778080 | 16.149593 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 3.92965801 | 60.00 | 32.22 | 27.78 | 0.000 | 449229.87 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 307017.02 | 0.00 | 450609.61 | 450609.61 | 17.00778080 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.78 | 20.82 | 0.00800000 | 59554.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 108069.560 | 108069.560 | 3.681310 | 0.00094544 | 2851.639 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 3.9293 | 4.008422 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 108069.56 | 108069.56 | 1.0000 | 3.87693392 | 3.681310 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.94534321 | 60.00 | 32.22 | 27.78 | 0.000 | 108069.56 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 75652.05 | 0.00 | 108435.35 | 108435.35 | 3.87693392 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61029.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18620.863 | 18620.863 | 0.634918 | 0.00016290 | 491.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.6770 | 0.690669 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18620.86 | 18620.86 | 1.0000 | 0.66865787 | 0.634918 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.16288681 | 60.00 | 32.22 | 27.78 | 0.000 | 18620.86 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00788115 | 21.00 | 0.00788115 | 44.5688 | 13031.35 | 0.00 | 18682.33 | 18682.33 | 0.66865787 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12786.376 | 12786.376 | 0.436038 | 0.00011186 | 337.225 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.4649 | 0.474261 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12786.38 | 12786.38 | 1.0000 | 0.45920928 | 0.436038 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11184938 | 60.00 | 32.22 | 27.78 | 0.000 | 12786.38 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00789006 | 21.00 | 0.00789006 | 44.6185 | 8947.63 | 0.00 | 12828.43 | 12828.43 | 0.45920928 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20645.335 | 20645.335 | 0.704084 | 0.00018061 | 544.481 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.7507 | 0.765759 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20645.33 | 20645.33 | 1.0000 | 0.74149918 | 0.704084 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.18059597 | 60.00 | 32.22 | 27.78 | 0.000 | 20645.33 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00790040 | 21.00 | 0.00790040 | 44.6761 | 14446.65 | 0.00 | 20713.13 | 20713.13 | 0.74149918 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10415.463 | 10415.463 | 0.355019 | 0.00009112 | 274.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.3787 | 0.386321 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10415.46 | 10415.46 | 1.0000 | 0.37388471 | 0.355019 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09110972 | 60.00 | 32.22 | 27.78 | 0.000 | 10415.46 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782639 | 21.00 | 0.00782639 | 44.2635 | 7290.44 | 0.00 | 10450.15 | 10450.15 | 0.37388471 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 261150.668 | 261150.668 | 8.910296 | 0.00228466 | 6885.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 9.4953 | 9.686373 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 261150.67 | 261150.67 | 1.0000 | 9.38378822 | 8.910296 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.28442691 | 60.00 | 32.22 | 27.78 | 0.000 | 261150.67 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782597 | 21.00 | 0.00782597 | 44.2617 | 182720.39 | 0.00 | 261997.91 | 261997.91 | 9.38378822 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 173323.201 | 173323.201 | 5.913945 | 0.00151631 | 4570.016 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 6.3019 | 6.428753 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 173323.20 | 173323.20 | 1.0000 | 6.22821127 | 5.913945 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.51615230 | 60.00 | 32.22 | 27.78 | 0.000 | 173323.20 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782556 | 21.00 | 0.00782556 | 44.2594 | 121267.58 | 0.00 | 173884.83 | 173884.83 | 6.22821127 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 264672.709 | 264672.709 | 9.030646 | 0.00231547 | 6978.711 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 9.6233 | 9.817010 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 264672.71 | 264672.71 | 1.0000 | 9.51053307 | 9.030646 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.31523612 | 60.00 | 32.22 | 27.78 | 0.000 | 264672.71 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782840 | 21.00 | 0.00782840 | 44.2753 | 185182.71 | 0.00 | 265530.92 | 265530.92 | 9.51053307 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 169464.350 | 169464.350 | 5.782122 | 0.00148255 | 4468.325 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 6.1616 | 6.285624 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 169464.35 | 169464.35 | 1.0000 | 6.08938308 | 5.782122 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.48239682 | 60.00 | 32.22 | 27.78 | 0.000 | 169464.35 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782138 | 21.00 | 0.00782138 | 44.2362 | 118569.52 | 0.00 | 170013.87 | 170013.87 | 6.08938308 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33812.756 | 33812.756 | 1.154054 | 0.00029581 | 891.424 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 1.2294 | 1.254153 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33812.76 | 33709.98 | 1.0000 | 1.21538039 | 1.154054 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.29577856 | 60.00 | 32.22 | 27.78 | 0.000 | 33812.76 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783422 | 21.00 | 0.00783422 | 44.3082 | 23654.56 | 0.00 | 33921.48 | 33921.48 | 1.21538039 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22298.557 | 22298.557 | 0.761087 | 0.00019508 | 587.862 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.8108 | 0.827079 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22298.56 | 22298.56 | 1.0000 | 0.80153135 | 0.761087 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19505761 | 60.00 | 32.22 | 27.78 | 0.000 | 22298.56 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783244 | 21.00 | 0.00783244 | 44.2983 | 15599.37 | 0.00 | 22370.20 | 22370.20 | 0.80153135 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34202.946 | 34202.946 | 1.167387 | 0.00029922 | 901.706 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 1.2436 | 1.268626 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34202.95 | 34202.95 | 1.0000 | 1.22942148 | 1.167387 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.29919177 | 60.00 | 32.22 | 27.78 | 0.000 | 34202.95 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783608 | 21.00 | 0.00783608 | 44.3185 | 23927.35 | 0.00 | 34312.88 | 34312.88 | 1.22942148 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22180.030 | 22180.030 | 0.757042 | 0.00019404 | 584.737 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 0.8065 | 0.822682 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22180.03 | 22180.03 | 1.0000 | 0.79727088 | 0.757042 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19402078 | 60.00 | 32.22 | 27.78 | 0.000 | 22180.03 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783164 | 21.00 | 0.00783164 | 44.2938 | 15516.46 | 0.00 | 22251.29 | 22251.29 | 0.79727088 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 171416.136 | -999.000 | 10.305254 | 0.00490248 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1102 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.305254 | 10.85287415 | 4197.9300 | 999.8980 | 58.97584722 | 15.00 | 6.67 | 8.33 | 2062312.06 | 8.3118 | 8.311843 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 171416.14 | 168355.67 | 1.0000 | 10.85287415 | 10.305254 | 25.85 | 14.51 | 0.00713853 | 44173.2 | 10.68 | 8.51 | 0.00700000 | 28378.7 | 4.90197968 | 6.67 | 15.00 | 8.33 | 23409.346 | 148006.79 | 33.40 | 0.00630683 | 16.37 | 2.03050000 | 19.7035 | 24.00 | 0.00734273 | 24.00 | 0.00734273 | 34.6353 | 123651.16 | 0.00 | 124976.11 | 124976.11 | 10.85287415 | 25.85 | 15.87 | 0.00713853 | 44173.2 | 14.54 | 11.45 | 0.00713853 | 32657.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 79307.876 | 79307.876 | 3.091576 | 0.00069382 | 1249.968 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.305254 | 10.85287415 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 2.8836 | 2.941619 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 79307.88 | 79307.88 | 1.0000 | 3.25586224 | 3.091576 | -11.44 | -11.44 | 0.00290252 | -4298.8 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.69374912 | 60.00 | 32.22 | 27.78 | 0.000 | 79307.88 | -27.60 | 0.00034190 | -27.60 | 2.03050000 | 65.6785 | 19.48 | 0.00780259 | 19.73 | 0.00775291 | 47.4274 | 23424.11 | 0.00 | 67393.80 | 67393.80 | 3.25586224 | 2.80 | 0.38 | 0.00290252 | 10087.7 | 23.29 | 10.75 | 0.00290252 | 30786.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1612093.071 | -999.000 | 95.809545 | 0.04610566 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1133 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.809545 | 100.90085323 | 4197.9300 | 999.8980 | 58.97584722 | 15.00 | 6.67 | 8.33 | 2062312.06 | 78.1692 | 78.169211 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1612093.07 | 1583218.99 | 1.0000 | 100.90085323 | 95.809545 | 26.03 | 14.58 | 0.00714024 | 44355.7 | 10.68 | 8.51 | 0.00700000 | 28378.7 | 46.10095451 | 6.67 | 15.00 | 8.33 | 217640.315 | 1394452.76 | 33.40 | 0.00630683 | 16.37 | 20.30600000 | 21.1941 | 24.00 | 0.00736949 | 24.00 | 0.00736949 | 34.7600 | 1129913.41 | 0.00 | 1176621.43 | 1176621.43 | 100.90085323 | 26.03 | 15.93 | 0.00714024 | 44355.7 | 14.57 | 11.46 | 0.00714024 | 32694.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 816454.667 | 816454.667 | 28.742864 | 0.00714270 | 12712.102 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.809545 | 100.90085323 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 29.6858 | 30.283226 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 816454.67 | 816454.67 | 1.0000 | 30.27025597 | 28.742864 | -14.04 | -14.04 | 0.00251092 | -7895.6 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 7.14197297 | 60.00 | 32.22 | 27.78 | 0.000 | 816454.67 | -27.60 | 0.00034190 | -27.60 | 20.30600000 | 70.6471 | 18.59 | 0.00773135 | 17.92 | 0.00770382 | 52.7875 | 244539.91 | 0.00 | 674964.45 | 674964.45 | 30.27025597 | 2.80 | -0.40 | 0.00251092 | 9106.3 | 24.89 | 11.02 | 0.00251092 | 31404.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 180218.696 | -999.000 | 10.919304 | 0.00515423 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0936 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.919304 | 11.49955454 | 4197.9300 | 999.8980 | 58.97584722 | 15.00 | 6.67 | 8.33 | 2062312.06 | 8.7387 | 8.738672 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 180218.70 | 177189.80 | 1.0000 | 11.49955454 | 10.919304 | 25.75 | 14.47 | 0.00712961 | 44050.4 | 10.68 | 8.51 | 0.00700000 | 28378.6 | 5.15370611 | 6.67 | 15.00 | 8.33 | 24804.217 | 155414.48 | 33.40 | 0.00630683 | 16.37 | 2.03050000 | 18.5955 | 24.00 | 0.00731845 | 24.00 | 0.00731845 | 34.5220 | 130575.99 | 0.00 | 131260.52 | 131260.52 | 11.49955454 | 25.75 | 15.82 | 0.00712961 | 44050.4 | 14.54 | 11.44 | 0.00712961 | 32636.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 79343.997 | 79343.997 | 3.275791 | 0.00069414 | 1258.815 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.919304 | 11.49955454 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 2.8849 | 2.942958 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 79344.00 | 79344.00 | 1.0000 | 3.44986636 | 3.275791 | -10.09 | -10.09 | 0.00313932 | -2344.4 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.69406509 | 60.00 | 32.22 | 27.78 | 0.000 | 79344.00 | -27.60 | 0.00034190 | -27.60 | 2.03050000 | 61.9850 | 18.47 | 0.00770062 | 16.42 | 0.00775259 | 58.3997 | 24953.77 | 0.00 | 68417.63 | 68417.63 | 3.44986636 | 2.80 | 0.72 | 0.00313932 | 10681.1 | 22.42 | 10.62 | 0.00313932 | 30513.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 98584.162 | -999.000 | 5.742787 | 0.00281949 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3324 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:VariableVolume | 5.742787 | 6.04795806 | 4197.9300 | 999.8980 | 58.97584722 | 15.00 | 6.67 | 8.33 | 2062312.06 | 4.7803 | 4.780274 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 98584.16 | 95382.46 | 1.0000 | 6.04795806 | 5.742787 | 26.02 | 14.68 | 0.00725808 | 44654.0 | 10.66 | 8.50 | 0.00700000 | 28353.6 | 2.81920693 | 6.67 | 15.00 | 8.33 | 13199.575 | 85384.59 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 20.8985 | 24.00 | 0.00755163 | 24.00 | 0.00755163 | 35.6092 | 61154.71 | 0.00 | 72396.21 | 72396.21 | 6.04795806 | 26.02 | 16.03 | 0.00725808 | 44654.0 | 14.27 | 11.46 | 0.00725808 | 32683.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:VariableVolume | 5.742787 | 6.04795806 | 4197.9300 | 999.8980 | 23.58392390 | 54.44 | 82.22 | 27.78 | 2750321.72 | 3.6359 | 3.709113 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.474082 | -5.77 | -9.97 | 0.00034190 | -4944.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 34.5460 | 0.00 | 0.00034190 | 22.93 | 0.00034190 | 1.7392 | 0.00 | 0.00 | 100050.95 | 100050.95 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40233.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 532339.419 | 299666.288 | 28.025486 | 0.01303696 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9147 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 462503.95 | 460742.41 | 0.8688 | -999.0 | -999.0 | 28.66 | 15.39 | 0.00703336 | 46764.7 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 462503.95 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704225 | 27.00 | 0.00704225 | 27.8125 | 370483.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10407.734 | 5919.683 | 0.563594 | 0.00025488 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9683 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 8995.07 | 8929.62 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706221 | 46226.6 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8995.07 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708408 | 27.00 | 0.00708408 | 27.9739 | 8577.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 100061.745 | 56902.503 | 5.416976 | 0.00245051 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9727 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 86484.37 | 85831.28 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706459 | 46231.8 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86484.37 | 26.28 | 0.00629588 | 13.94 | 0.15632344 | -999.0000 | 27.00 | 0.00708743 | 27.00 | 0.00708743 | 27.9871 | 82445.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10183.540 | 5791.550 | 0.551363 | 0.00024939 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9709 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 8801.56 | 8736.11 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706360 | 46229.7 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8801.56 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708600 | 27.00 | 0.00708600 | 27.9814 | 8391.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 532339.419 | 532339.419 | 28.025486 | 0.01303696 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 532339.42 | 532339.42 | 1.0000 | 29.51475702 | 28.025486 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 532339.42 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.2074 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10407.734 | 10407.734 | 0.563594 | 0.00025488 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10407.73 | 10407.73 | 1.0000 | 0.59354313 | 0.563594 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10407.73 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7737 | 0.00 | 0.00097295 | 25.24 | 0.00097295 | 4.3040 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100061.745 | 100061.745 | 5.416976 | 0.00245051 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100061.75 | 100061.75 | 1.0000 | 5.70483369 | 5.416976 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100061.75 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8858 | 0.00 | 0.00097296 | 23.65 | 0.00097296 | 4.7349 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10183.540 | 10183.540 | 0.551363 | 0.00024939 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10183.54 | 10183.54 | 1.0000 | 0.58066216 | 0.551363 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10183.54 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8352 | 0.00 | 0.00097241 | 22.14 | 0.00097241 | 5.1845 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 28.025486 | 29.51475702 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 29.51475702 | 28.025486 | -0.33 | -0.33 | 0.00691961 | 16966.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.2074 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.563594 | 0.59354313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.59354313 | 0.563594 | -0.77 | -5.62 | 0.00095544 | 1618.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7737 | 0.00 | 0.00097295 | 25.24 | 0.00097295 | 4.3040 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.416976 | 5.70483369 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.70483369 | 5.416976 | -0.80 | -5.64 | 0.00095475 | 1586.0 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8858 | 0.00 | 0.00097296 | 23.65 | 0.00097296 | 4.7349 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.551363 | 0.58066216 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.58066216 | 0.551363 | -0.78 | -5.64 | 0.00095453 | 1599.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8352 | 0.00 | 0.00097241 | 22.14 | 0.00097241 | 5.1845 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.31 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 95.81 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.92 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.74 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 28.03 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2002.83 | 1526.00 | 325.67 |
CORE_BOTTOM | 1459.83 | 1597.83 | 5.83 |
CORE_MID | 913.00 | 3313.00 | 136.17 |
CORE_TOP | 1839.83 | 4059.83 | 1109.50 |
PERIMETER_BOT_ZN_3 | 1685.83 | 3727.00 | 582.50 |
PERIMETER_BOT_ZN_2 | 2146.17 | 3371.83 | 688.50 |
PERIMETER_BOT_ZN_1 | 2447.50 | 2974.00 | 715.67 |
PERIMETER_BOT_ZN_4 | 2529.50 | 2305.67 | 495.17 |
PERIMETER_MID_ZN_3 | 2593.17 | 4287.33 | 1818.83 |
PERIMETER_MID_ZN_2 | 2432.83 | 3257.83 | 1403.67 |
PERIMETER_MID_ZN_1 | 2703.67 | 3291.33 | 1130.17 |
PERIMETER_MID_ZN_4 | 2776.67 | 3662.33 | 1430.33 |
PERIMETER_TOP_ZN_3 | 3275.17 | 4490.00 | 2550.00 |
PERIMETER_TOP_ZN_2 | 3398.67 | 3981.67 | 2186.50 |
PERIMETER_TOP_ZN_1 | 3105.33 | 3662.50 | 1733.00 |
PERIMETER_TOP_ZN_4 | 3291.50 | 3960.83 | 2061.83 |
DATACENTER_BOT_ZN_6 | 5834.50 | 419.00 | 419.00 |
DATACENTER_MID_ZN_6 | 5340.83 | 207.17 | 89.33 |
DATACENTER_TOP_ZN_6 | 4546.33 | 575.67 | 170.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5718.33 | 5718.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5942.67 | 5934.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1376.67 | 0.00 | 771.83 |
CORE_BOTTOM | 0.00 | 87.17 | 0.00 | 80.83 |
CORE_MID | 0.00 | 11.67 | 0.00 | 11.67 |
CORE_TOP | 18.50 | 30.00 | 4.50 | 30.00 |
PERIMETER_BOT_ZN_3 | 3.33 | 118.33 | 0.17 | 113.67 |
PERIMETER_BOT_ZN_2 | 4.17 | 91.33 | 0.00 | 86.17 |
PERIMETER_BOT_ZN_1 | 5.17 | 200.17 | 0.17 | 192.50 |
PERIMETER_BOT_ZN_4 | 2.17 | 181.00 | 0.00 | 114.17 |
PERIMETER_MID_ZN_3 | 84.50 | 45.00 | 31.17 | 43.83 |
PERIMETER_MID_ZN_2 | 95.50 | 64.17 | 5.83 | 53.17 |
PERIMETER_MID_ZN_1 | 31.67 | 145.67 | 3.83 | 139.83 |
PERIMETER_MID_ZN_4 | 32.83 | 78.17 | 4.67 | 52.50 |
PERIMETER_TOP_ZN_3 | 264.50 | 43.67 | 106.00 | 41.00 |
PERIMETER_TOP_ZN_2 | 134.50 | 69.17 | 21.33 | 63.00 |
PERIMETER_TOP_ZN_1 | 107.50 | 121.33 | 13.67 | 113.50 |
PERIMETER_TOP_ZN_4 | 98.50 | 80.33 | 15.50 | 54.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 11.33 | 0.00 | 7.50 |
DATACENTER_MID_ZN_6 | 0.00 | 5.33 | 0.00 | 2.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 8.17 | 0.00 | 4.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 341.50 | 1617.67 | 112.33 | 975.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.071 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.972 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.705 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.658 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.873 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.398 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.504 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.852 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.705 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.196 | 0.068 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.390 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.191 | 0.064 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.745 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.329 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.405 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.221 | 0.080 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 27.939 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 42331817.51 | 0.00 | 42331817.51 | 0.00 | 42331817.51 | 37848132.68 | 4723.62 | 899.71 | 3136.67 | 0.00 |
CORE_BOTTOM | 41383574.10 | 0.00 | 41383574.10 | 0.00 | 41383574.10 | 33990283.35 | 4137.54 | 92.11 | 4530.36 | 502.94 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 4977.06 | 549.49 | 3233.45 | 318.39 |
CORE_TOP | 27134109.15 | 0.00 | 27134109.15 | 0.00 | 27134109.15 | 33990283.35 | 5366.04 | 799.59 | 2594.37 | 366.81 |
PERIMETER_BOT_ZN_3 | 4679502.07 | 0.00 | 4679502.07 | 266213.26 | 4945715.33 | 4267819.30 | 5550.05 | 130.05 | 3079.90 | 502.94 |
PERIMETER_BOT_ZN_2 | 4712888.55 | 0.00 | 4712888.55 | 177475.38 | 4890363.93 | 2750345.05 | 5290.63 | 172.46 | 3296.91 | 502.94 |
PERIMETER_BOT_ZN_1 | 7846314.07 | 0.00 | 7846314.07 | 266213.26 | 8112527.33 | 4267912.63 | 4961.08 | 142.92 | 3656.00 | 502.94 |
PERIMETER_BOT_ZN_4 | 6318704.77 | 0.00 | 6318704.77 | 177475.38 | 6496180.15 | 2750345.05 | 4348.36 | 125.57 | 4286.06 | 502.94 |
PERIMETER_MID_ZN_3 | 36693895.06 | 0.00 | 36693895.06 | 624345.56 | 37318240.61 | 42678193.03 | 5257.50 | 385.17 | 3117.33 | 318.39 |
PERIMETER_MID_ZN_2 | 41089368.95 | 0.00 | 41089368.95 | 416230.09 | 41505599.04 | 27503450.52 | 5096.00 | 303.78 | 3360.22 | 871.34 |
PERIMETER_MID_ZN_1 | 71024172.93 | 0.00 | 71024172.93 | 624345.56 | 71648518.49 | 42679126.28 | 4517.27 | 432.29 | 3810.44 | 318.39 |
PERIMETER_MID_ZN_4 | 39914181.25 | 0.00 | 39914181.25 | 416230.09 | 40330411.34 | 27503450.52 | 4961.26 | 791.06 | 3007.67 | 318.39 |
PERIMETER_TOP_ZN_3 | 3863278.80 | 0.00 | 3863278.80 | 775192.66 | 4638471.45 | 4267819.30 | 4599.89 | 95.90 | 4064.21 | 366.81 |
PERIMETER_TOP_ZN_2 | 4376566.17 | 0.00 | 4376566.17 | 516794.75 | 4893360.92 | 2750345.05 | 4537.05 | 437.50 | 3785.45 | 366.81 |
PERIMETER_TOP_ZN_1 | 7168935.76 | 0.00 | 7168935.76 | 775192.66 | 7944128.41 | 4267912.63 | 4364.82 | 537.18 | 3858.00 | 366.81 |
PERIMETER_TOP_ZN_4 | 4088692.56 | 0.00 | 4088692.56 | 516794.75 | 4605487.31 | 2750345.05 | 4691.37 | 1145.56 | 2923.07 | 366.81 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.44E+09 | 0.00 | 0.44E+09 | 0.00 | 0.44E+09 | 10671554.30 | 65.67 | 261.17 | 8433.17 | 2796.50 |
Total Facility | 0.54E+10 | 0.00 | 0.54E+10 | 24282864.96 | 0.54E+10 | 0.50E+10 | 7449.49 | 4372.85 | 8694.99 | 3349.69 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9786 | 0.0000 | 1.9786 | 0.0000 | 1.9786 | 1.2002 | 1906.62 | 899.71 | 3136.67 |
CORE_BOTTOM | 1.8150 | 0.0000 | 1.8150 | 0.0000 | 1.8150 | 1.0778 | 1699.90 | 89.20 | 4153.89 |
CORE_MID | 13.1689 | 0.0000 | 13.1689 | 0.0000 | 13.1689 | 10.7782 | 2282.60 | 548.02 | 3112.38 |
CORE_TOP | 1.2312 | 0.0000 | 1.2312 | 0.0000 | 1.2312 | 1.0778 | 2656.04 | 799.31 | 2487.65 |
PERIMETER_BOT_ZN_3 | 0.2048 | 0.0000 | 0.2048 | 0.0062 | 0.2111 | 0.1353 | 3098.71 | 126.32 | 2717.97 |
PERIMETER_BOT_ZN_2 | 0.2114 | 0.0000 | 0.2114 | 0.0042 | 0.2155 | 0.0872 | 2839.26 | 168.69 | 2935.05 |
PERIMETER_BOT_ZN_1 | 0.3527 | 0.0000 | 0.3527 | 0.0062 | 0.3589 | 0.1353 | 2509.73 | 139.65 | 3293.62 |
PERIMETER_BOT_ZN_4 | 0.2797 | 0.0000 | 0.2797 | 0.0042 | 0.2839 | 0.0872 | 1910.22 | 122.98 | 3909.80 |
PERIMETER_MID_ZN_3 | 1.6584 | 0.0000 | 1.6584 | 0.0146 | 1.6730 | 1.3533 | 2565.71 | 383.55 | 2993.74 |
PERIMETER_MID_ZN_2 | 1.8088 | 0.0000 | 1.8088 | 0.0103 | 1.8192 | 0.8721 | 1954.24 | 298.63 | 2781.13 |
PERIMETER_MID_ZN_1 | 3.2618 | 0.0000 | 3.2618 | 0.0146 | 3.2764 | 1.3533 | 1825.44 | 430.61 | 3686.95 |
PERIMETER_MID_ZN_4 | 1.8011 | 0.0000 | 1.8011 | 0.0098 | 1.8108 | 0.8721 | 2270.50 | 789.51 | 2882.99 |
PERIMETER_TOP_ZN_3 | 0.1755 | 0.0000 | 0.1755 | 0.0182 | 0.1936 | 0.1353 | 1892.54 | 95.56 | 3954.90 |
PERIMETER_TOP_ZN_2 | 0.2012 | 0.0000 | 0.2012 | 0.0121 | 0.2133 | 0.0872 | 1832.24 | 437.30 | 3673.47 |
PERIMETER_TOP_ZN_1 | 0.3299 | 0.0000 | 0.3299 | 0.0182 | 0.3481 | 0.1353 | 1657.70 | 536.71 | 3748.59 |
PERIMETER_TOP_ZN_4 | 0.1847 | 0.0000 | 0.1847 | 0.0121 | 0.1969 | 0.0872 | 1983.93 | 1145.27 | 2813.81 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.3890 | 0.0000 | 14.3890 | 0.0000 | 14.3890 | 0.3384 | 45.17 | 261.17 | 5636.67 |
Total Facility | 239.5079 | 0.0000 | 239.5079 | 0.5750 | 240.0829 | 158.4706 | 4632.49 | 4364.29 | 5898.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 72026151.60 | 0.00 | 72026151.60 | 48026705.38 | 3581.53 | 10.47 | 5168.00 | 502.94 |
VAV_MID WITH REHEAT | 0.53E+09 | 0.00 | 0.53E+09 | 0.48E+09 | 4005.56 | 4.47 | 4749.96 | 318.39 |
VAV_TOP WITH REHEAT | 51719107.71 | 0.00 | 51719107.71 | 48026705.38 | 4076.63 | 4.54 | 4678.82 | 366.31 |
CAV_BAS | 46950383.84 | 0.00 | 46950383.84 | 37848132.68 | 4705.61 | 2.83 | 4051.56 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.49E+09 | 0.00 | 0.49E+09 | 10671554.30 | 65.67 | 0.00 | 8694.33 | 2796.50 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.1760 | 0.0000 | 3.1760 | 1.5229 | 1157.34 | 8.86 | 4776.81 |
VAV_MID WITH REHEAT | 24.1482 | 0.0000 | 24.1482 | 15.2292 | 1318.91 | 2.58 | 4621.51 |
VAV_TOP WITH REHEAT | 2.3541 | 0.0000 | 2.3541 | 1.5229 | 1368.42 | 4.11 | 4570.47 |
CAV_BAS | 2.1945 | 0.0000 | 2.1945 | 1.2002 | 1888.61 | 2.83 | 4051.56 |
AIRLOOP DATACENTER BASEMENT | 15.9589 | 0.0000 | 15.9589 | 0.3384 | 45.17 | 0.00 | 5897.83 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1095.97 | 3106.44 | 0.00 | 0.00 | 0.00 | 1256.53 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 711.37 | 2895.73 | 0.00 | 0.00 | 0.00 | 1596.30 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 205.28 | 2532.77 | 0.00 | 0.00 | 0.00 | 2490.85 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 887.93 | 3147.38 | 0.00 | 45.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 261.17 | 8433.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3184 | 5.3557 | 0.0000 | 0.0000 | 0.0000 | 1.9027 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 22.5102 | 38.1660 | 0.0000 | 0.0000 | 0.0000 | 18.2571 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.2731 | 4.1640 | 0.0000 | 0.0000 | 0.0000 | 1.8078 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3325 | 3.7538 | 0.0000 | 1.0395 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3756 | 16.8108 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1185 |
Fields with Defaults | 3880 |
Autosized Fields | 335 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
Electricity:Building | 17140.58 | 216479.19 | 06-MAY-18:20 | 1025582.59 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17140.58 | 216479.19 | 06-MAY-18:20 | 1025582.59 | 01-DEC-16:40 |
InteriorLights:Electricity | 2464.19 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2464.19 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2464.19 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2464.19 | 9223.03 | 26-MAR-17:20 | 247210.90 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.14 | 603.11 | 12-MAR-17:10 | 3823.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.78 | 43.94 | 01-JAN-10:00 | 1662.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.78 | 43.94 | 01-JAN-10:00 | 1662.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.31 | 388.67 | 26-MAR-17:10 | 2463.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.88 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.88 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.97 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.60 | 43.94 | 01-JAN-08:50 | 1662.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.60 | 43.94 | 01-JAN-08:50 | 1662.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.89 | 28.32 | 01-JAN-10:00 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.89 | 28.32 | 01-JAN-10:00 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 471.27 | 6031.15 | 12-MAR-17:10 | 38231.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 107.61 | 439.44 | 01-JAN-09:50 | 16625.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 107.61 | 439.44 | 01-JAN-09:50 | 16625.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 303.05 | 3886.70 | 19-MAR-17:10 | 24637.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.70 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.70 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 469.59 | 6031.24 | 12-MAR-17:10 | 38231.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.93 | 439.45 | 01-JAN-08:50 | 16625.99 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.93 | 439.45 | 01-JAN-08:50 | 16625.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 303.16 | 3886.68 | 12-MAR-17:10 | 24637.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.81 | 283.19 | 01-JAN-09:50 | 10714.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.81 | 283.19 | 01-JAN-09:50 | 10714.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.13 | 603.11 | 12-MAR-17:10 | 3823.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.76 | 43.94 | 01-JAN-09:50 | 1662.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.76 | 43.94 | 01-JAN-09:50 | 1662.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.31 | 388.67 | 19-MAR-17:10 | 2463.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.87 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.87 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.96 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.59 | 43.94 | 01-JAN-08:50 | 1662.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.59 | 43.94 | 01-JAN-08:50 | 1662.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.88 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.88 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1649.34 | 4076.49 | 29-JAN-04:10 | 517196.00 | 07-SEP-15:10 |
HeatRejection:Electricity | 330.59 | 31.69 | 10-JAN-22:00 | 74189.28 | 19-MAY-14:00 |
General:HeatRejection:Electricity | 330.59 | 31.69 | 10-JAN-22:00 | 74189.28 | 19-MAY-14:00 |
Electricity:HVAC | 6013.41 | 60634.33 | 11-SEP-22:40 | 584961.47 | 30-AUG-15:40 |
ExteriorEquipment:Electricity | 2566.27 | 20217.42 | 01-JAN-00:10 | 233397.31 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
ElectricityPurchased:Plant | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
Cogeneration:ElectricityPurchased | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
ElectricityNet:Plant | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
Cogeneration:ElectricityNet | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
General:Cogeneration:ElectricityNet | 27671.46 | 307422.08 | 10-SEP-17:20 | 2132523.49 | 08-AUG-16:00 |
Fans:Electricity | 2726.61 | 53343.62 | 10-JAN-22:10 | 332285.45 | 22-JUN-09:20 |
General:Fans:Electricity | 2726.61 | 53343.62 | 10-JAN-22:10 | 332285.45 | 22-JUN-09:20 |
ExteriorLights:Electricity | 356.53 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.53 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1301.14 | 1666.87 | 10-JAN-22:00 | 424184.24 | 10-AUG-15:00 |
General:Cooling:Electricity | 1301.14 | 1666.87 | 10-JAN-22:00 | 424184.24 | 10-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2428.56 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:20 |
General:Humidifier:Electricity | 2428.56 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 478.33 | 0.00 | 01-JAN-00:10 | 58671.08 | 17-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 478.33 | 0.00 | 01-JAN-00:10 | 58671.08 | 17-FEB-12:20 |
Pumps:Electricity | 342.83 | 4038.31 | 01-JAN-00:40 | 46383.75 | 07-SEP-14:50 |
General:Pumps:Electricity | 342.83 | 4038.31 | 01-JAN-00:40 | 46383.75 | 07-SEP-14:50 |
WIRED_LTG_ELECTRICITY | 69.24 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3281.10 | 0.00 | 01-JAN-00:40 | 2405335.49 | 09-JAN-07:10 |
NaturalGas:Plant | 3281.10 | 0.00 | 01-JAN-00:40 | 2405335.49 | 09-JAN-07:10 |
Heating:NaturalGas | 3281.10 | 0.00 | 01-JAN-00:40 | 2405335.49 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 3281.10 | 0.00 | 01-JAN-00:40 | 2405335.49 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7541.42 | 4131.46 | 10-JAN-22:00 | 2364997.53 | 10-AUG-15:00 |
PlantLoopCoolingDemand:HVAC | 7541.42 | 4131.46 | 10-JAN-22:00 | 2364997.53 | 10-AUG-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 7541.42 | 4131.46 | 10-JAN-22:00 | 2364997.53 | 10-AUG-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6566.43 | 0.00 | 20-MAY-23:10 | 0.00 | 25-JUL-13:00 |
Water:HVAC | 903.43 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
Humidifier:Water | 903.43 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
General:Humidifier:Water | 903.43 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
MainsWater:Facility | 6566.43 | 0.00 | 20-MAY-23:10 | 0.00 | 25-JUL-13:00 |
MainsWater:HVAC | 903.43 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
Humidifier:MainsWater | 903.43 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
General:Humidifier:MainsWater | 903.43 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
Water:Plant | 5663.01 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 5663.01 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3382.84 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-16:20 |
General:HeatRejection:Water | 3382.84 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-16:20 |
HeatRejection:MainsWater | 3382.84 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-16:20 |
General:HeatRejection:MainsWater | 3382.84 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-16:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 42410.82 | 95236.63 | 30-JAN-01:30 | 9965826.82 | 07-SEP-14:40 |
EnergyTransfer:Building | 17895.76 | 87725.04 | 29-JAN-17:30 | 1704430.79 | 10-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 568.13 | 0.00 | 01-JAN-00:10 | 98665.80 | 02-JAN-07:10 |
Heating:EnergyTransfer | 717.28 | 0.00 | 13-JAN-22:10 | 1128929.73 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 717.28 | 0.00 | 13-JAN-22:10 | 1128929.73 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 17178.48 | 84038.48 | 09-JAN-05:40 | 1704430.79 | 10-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 568.13 | 0.00 | 01-JAN-00:10 | 98665.80 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 17178.48 | 84038.48 | 09-JAN-05:40 | 1704430.79 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 568.13 | 0.00 | 01-JAN-00:10 | 98665.80 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 581.28 | 0.00 | 01-JAN-00:10 | 63074.29 | 20-JUL-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 581.28 | 0.00 | 01-JAN-00:10 | 63074.29 | 20-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 581.28 | 0.00 | 01-JAN-00:10 | 63074.29 | 20-JUL-07:20 |
EnergyTransfer:Zone:CORE_MID | 3872.90 | 0.00 | 01-JAN-00:10 | 479771.07 | 22-JUN-10:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 4.31 | 0.00 | 01-JAN-00:10 | 285751.47 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 4.31 | 0.00 | 01-JAN-00:10 | 285751.47 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3868.59 | 0.00 | 01-JAN-00:10 | 479771.07 | 22-JUN-10:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3868.59 | 0.00 | 01-JAN-00:10 | 479771.07 | 22-JUN-10:10 |
EnergyTransfer:Zone:CORE_TOP | 332.06 | 0.00 | 01-JAN-00:40 | 66549.98 | 09-JAN-05:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 20.72 | 0.00 | 01-JAN-00:10 | 66549.98 | 09-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 20.72 | 0.00 | 01-JAN-00:10 | 66549.98 | 09-JAN-05:40 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 311.34 | 0.00 | 01-JAN-00:40 | 54191.93 | 21-JUN-12:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 311.34 | 0.00 | 01-JAN-00:40 | 54191.93 | 21-JUN-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.37 | 0.00 | 01-JAN-00:10 | 11389.95 | 20-JUL-19:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.27 | 0.00 | 01-JAN-00:10 | 10858.27 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.27 | 0.00 | 01-JAN-00:10 | 10858.27 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.10 | 0.00 | 01-JAN-00:10 | 11389.95 | 20-JUL-19:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.10 | 0.00 | 01-JAN-00:10 | 11389.95 | 20-JUL-19:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.54 | 0.00 | 01-JAN-00:10 | 16576.77 | 07-AUG-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.64 | 0.00 | 01-JAN-00:10 | 8389.65 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.64 | 0.00 | 01-JAN-00:10 | 8389.65 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.90 | 0.00 | 01-JAN-00:10 | 16576.77 | 07-AUG-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.90 | 0.00 | 01-JAN-00:10 | 16576.77 | 07-AUG-07:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.34 | 0.00 | 01-JAN-00:10 | 24015.18 | 18-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.56 | 0.00 | 01-JAN-00:10 | 13716.38 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.56 | 0.00 | 01-JAN-00:10 | 13716.38 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.78 | 0.00 | 01-JAN-00:10 | 24015.18 | 18-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 108.78 | 0.00 | 01-JAN-00:10 | 24015.18 | 18-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 88.32 | 0.00 | 01-JAN-00:10 | 21895.65 | 31-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.51 | 0.00 | 01-JAN-00:10 | 6275.35 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.51 | 0.00 | 01-JAN-00:10 | 6275.35 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 87.82 | 0.00 | 01-JAN-00:10 | 21895.65 | 31-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 87.82 | 0.00 | 01-JAN-00:10 | 21895.65 | 31-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 538.88 | 0.00 | 01-JAN-00:10 | 125191.21 | 09-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 153.36 | 0.00 | 01-JAN-00:10 | 125191.21 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 153.36 | 0.00 | 01-JAN-00:10 | 125191.21 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 385.53 | 0.00 | 01-JAN-00:10 | 106373.85 | 25-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 385.53 | 0.00 | 01-JAN-00:10 | 106373.85 | 25-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 577.89 | 0.00 | 01-JAN-00:10 | 178195.47 | 23-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 84.09 | 0.00 | 01-JAN-00:10 | 140394.47 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 84.09 | 0.00 | 01-JAN-00:10 | 140394.47 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 493.80 | 0.00 | 01-JAN-00:10 | 178195.47 | 23-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 493.80 | 0.00 | 01-JAN-00:10 | 178195.47 | 23-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1062.45 | 0.00 | 01-JAN-00:10 | 252993.48 | 18-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 84.57 | 0.00 | 01-JAN-00:10 | 191353.24 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 84.57 | 0.00 | 01-JAN-00:10 | 191353.24 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 977.88 | 0.00 | 01-JAN-00:10 | 252993.48 | 18-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 977.88 | 0.00 | 01-JAN-00:10 | 252993.48 | 18-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 586.77 | 0.00 | 01-JAN-00:10 | 207279.65 | 31-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 69.92 | 0.00 | 01-JAN-00:10 | 131060.85 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 69.92 | 0.00 | 01-JAN-00:10 | 131060.85 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 516.84 | 0.00 | 01-JAN-00:10 | 207279.65 | 31-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 516.84 | 0.00 | 01-JAN-00:10 | 207279.65 | 31-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.03 | 0.00 | 01-JAN-00:40 | 15572.24 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.64 | 0.00 | 01-JAN-00:40 | 15572.24 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.64 | 0.00 | 01-JAN-00:40 | 15572.24 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.40 | 0.00 | 01-JAN-00:20 | 11151.95 | 25-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.40 | 0.00 | 01-JAN-00:20 | 11151.95 | 25-JUL-17:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.84 | 0.00 | 01-JAN-00:40 | 18105.74 | 14-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.80 | 0.00 | 01-JAN-00:40 | 17962.11 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.80 | 0.00 | 01-JAN-00:40 | 17962.11 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.04 | 0.00 | 01-JAN-00:20 | 18105.74 | 14-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.04 | 0.00 | 01-JAN-00:20 | 18105.74 | 14-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 111.24 | 0.00 | 01-JAN-00:40 | 25820.62 | 18-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 24.47 | 0.00 | 01-JAN-00:10 | 22913.49 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 24.47 | 0.00 | 01-JAN-00:10 | 22913.49 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.77 | 0.00 | 01-JAN-00:40 | 25820.62 | 18-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.77 | 0.00 | 01-JAN-00:40 | 25820.62 | 18-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 65.66 | 0.00 | 01-JAN-00:40 | 21510.43 | 31-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.75 | 0.00 | 01-JAN-00:40 | 18991.18 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.75 | 0.00 | 01-JAN-00:40 | 18991.18 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.91 | 0.00 | 01-JAN-00:10 | 21510.43 | 31-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.91 | 0.00 | 01-JAN-00:10 | 21510.43 | 31-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.81 | 0.00 | 01-JAN-00:10 | 11541.94 | 08-AUG-19:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.82 | 0.00 | 01-JAN-00:10 | 6078.87 | 30-JAN-13:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.82 | 0.00 | 01-JAN-00:10 | 6078.87 | 30-JAN-13:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 48.99 | 0.00 | 01-JAN-00:10 | 11541.94 | 08-AUG-19:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 48.99 | 0.00 | 01-JAN-00:10 | 11541.94 | 08-AUG-19:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 390.57 | 0.00 | 01-JAN-00:10 | 90588.00 | 30-JAN-13:40 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 124.98 | 0.00 | 01-JAN-00:10 | 90588.00 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 124.98 | 0.00 | 01-JAN-00:10 | 90588.00 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 265.59 | 0.00 | 01-JAN-00:10 | 83107.17 | 25-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 265.59 | 0.00 | 01-JAN-00:10 | 83107.17 | 25-JUL-17:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 100.15 | 0.00 | 01-JAN-00:40 | 32904.30 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.26 | 0.00 | 01-JAN-00:40 | 32904.30 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.26 | 0.00 | 01-JAN-00:40 | 32904.30 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 44.89 | 0.00 | 01-JAN-00:10 | 20799.66 | 14-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 44.89 | 0.00 | 01-JAN-00:10 | 20799.66 | 14-JUL-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.11 | 5.72 | 08-JAN-03:30 | 8437.95 | 22-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.02 | 0.00 | 01-JAN-00:10 | 343.03 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.02 | 0.00 | 01-JAN-00:10 | 343.03 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.10 | 0.00 | 08-JAN-03:50 | 8437.95 | 22-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.10 | 0.00 | 08-JAN-03:50 | 8437.95 | 22-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1182.65 | 5.08 | 31-JAN-08:30 | 80346.06 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.54 | 0.00 | 01-JAN-14:40 | 6462.83 | 29-JAN-18:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.54 | 0.00 | 01-JAN-14:40 | 6462.83 | 29-JAN-18:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1178.12 | 0.00 | 01-JAN-00:10 | 80346.06 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1178.12 | 0.00 | 01-JAN-00:10 | 80346.06 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.53 | 1.13 | 18-JAN-08:30 | 8096.98 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.07 | 0.00 | 02-JAN-13:40 | 702.28 | 29-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.07 | 0.00 | 02-JAN-13:40 | 702.28 | 29-JAN-18:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.47 | 0.00 | 01-JAN-00:10 | 8096.98 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.47 | 0.00 | 01-JAN-00:10 | 8096.98 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.24 | 84023.15 | 09-JAN-05:00 | 370021.99 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.24 | 84023.15 | 09-JAN-05:00 | 370021.99 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7163.24 | 84023.15 | 09-JAN-05:00 | 370021.99 | 07-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 3021.28 | 0.00 | 01-JAN-00:40 | 1992298.36 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:20 |
EnergyTransfer:HVAC | 9286.18 | 3138.80 | 29-JAN-08:10 | 2260020.84 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2548.31 | 0.00 | 01-JAN-00:40 | 1973348.82 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2548.31 | 0.00 | 01-JAN-00:40 | 1973348.82 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2548.31 | 0.00 | 01-JAN-00:40 | 1973348.82 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 6737.87 | 2464.59 | 10-JAN-22:00 | 2260020.84 | 07-SEP-15:00 |
EnergyTransfer:Plant | 15228.88 | 0.00 | 01-JAN-00:40 | 6634435.53 | 07-SEP-14:40 |
LoopToLoop:EnergyTransfer | 3889.33 | 0.00 | 01-JAN-00:10 | 2101984.87 | 07-SEP-14:40 |
WaterSystems:EnergyTransfer | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:20 |
Boilers:EnergyTransfer | 2535.07 | 0.00 | 01-JAN-00:40 | 1980467.61 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3916.96 | 0.00 | 01-JAN-00:10 | 2074275.06 | 07-SEP-14:40 |
HeatRejection:EnergyTransfer | 4414.55 | 0.00 | 01-JAN-00:10 | 2436128.60 | 07-SEP-15:10 |
General:HeatRejection:EnergyTransfer | 4414.55 | 0.00 | 01-JAN-00:10 | 2436128.60 | 07-SEP-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -568.113 | 0.000 | 0.000 | 90.567 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -112.581 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -581.276 | 0.000 | 0.000 | 83.259 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 59.567 | 0.000 | 0.000 | 0.000 | 0.000 | -0.007 |
CORE_MID | 0.000 | 0.000 | 4.310 | -3868.577 | 0.000 | 0.000 | 846.698 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1366.925 |
CORE_TOP | 0.000 | 0.000 | 20.719 | -311.340 | 0.000 | 0.000 | 88.185 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -236.013 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.268 | -59.097 | 0.000 | 0.000 | 10.849 | 10.778 | 36.365 | 27.815 | 0.000 | 0.036 | 55.711 | 0.000 | -79.974 | 0.000 | -4.752 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.644 | -59.896 | 0.000 | 0.000 | 6.951 | 6.877 | 23.435 | 65.279 | 0.000 | 0.024 | 8.339 | 0.000 | -49.483 | 0.000 | -3.170 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.556 | -108.781 | 0.000 | 0.000 | 10.698 | 10.601 | 36.366 | 142.073 | 0.000 | 0.034 | 0.002 | 0.000 | -72.967 | 0.000 | -4.812 | -15.767 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.506 | -87.817 | 0.000 | 0.000 | 6.822 | 6.888 | 23.435 | 61.263 | 0.000 | 0.023 | 48.597 | 0.000 | -56.279 | 0.000 | -3.439 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 153.356 | -385.524 | 0.000 | 0.000 | 113.772 | 107.613 | 363.654 | 290.100 | 0.000 | 0.874 | 192.568 | 0.000 | -735.939 | 0.000 | -100.474 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 84.091 | -493.799 | 0.000 | 0.000 | 52.613 | 68.699 | 234.352 | 653.592 | 0.000 | 0.540 | 0.019 | 0.000 | -467.941 | 0.000 | -69.273 | -62.874 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 84.574 | -977.871 | 0.000 | 0.000 | 108.945 | 105.926 | 363.660 | 1415.694 | 0.000 | 0.785 | 0.066 | 0.000 | -710.652 | 0.000 | -108.316 | -282.744 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 69.922 | -516.834 | 0.000 | 0.000 | 71.875 | 68.806 | 234.351 | 623.506 | 0.000 | 0.538 | 21.417 | 0.000 | -502.683 | 0.000 | -70.899 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 38.637 | -34.395 | 0.000 | 0.000 | 11.615 | 10.761 | 36.365 | 29.758 | 0.000 | 0.105 | 0.001 | 0.000 | -69.453 | 0.000 | -11.717 | -11.676 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 21.797 | -47.039 | 0.000 | 0.000 | 7.285 | 6.870 | 23.435 | 66.064 | 0.000 | 0.066 | 0.000 | 0.000 | -44.287 | 0.000 | -8.087 | -26.104 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 24.470 | -86.765 | 0.000 | 0.000 | 11.111 | 10.592 | 36.366 | 142.461 | 0.000 | 0.094 | 0.004 | 0.000 | -67.211 | 0.000 | -12.658 | -58.460 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 17.746 | -47.910 | 0.000 | 0.000 | 7.325 | 6.880 | 23.435 | 62.720 | 0.000 | 0.065 | 0.001 | 0.000 | -47.841 | 0.000 | -8.342 | -14.078 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.017 | -137.095 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.379 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 4.538 | -1178.114 | 0.000 | 0.000 | 9.521 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -411.014 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.067 | -105.467 | 0.000 | 0.000 | 0.958 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.065 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7163.240 | 0.000 | 0.000 | 20.565 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -399.794 |
GROUNDFLOOR_PLENUM | 4.820 | -48.991 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.067 | 54.236 | 0.000 | 0.000 | 0.000 | -10.132 | -0.000 |
MIDFLOOR_PLENUM | 124.979 | -265.594 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.269 | 311.928 | 0.000 | 0.000 | 0.000 | -172.581 | -0.006 |
TOPFLOOR_PLENUM | 55.264 | -44.885 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.109 | 7.513 | 0.000 | 0.000 | 0.000 | -18.001 | -0.002 |
Total Facility | 185.063 | -359.470 | 532.218 | -16818.947 | 0.000 | 0.000 | 1560.565 | 2464.187 | 14676.396 | 3580.326 | 0.000 | 4.626 | 759.970 | 0.000 | -2904.711 | 0.000 | -606.654 | -3073.491 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-JUL-06:11 | 0.00 | 0.00 | 0.00 | -113003.61 | 0.00 | 0.00 | 1136.38 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 93495.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-JUL-04:13 | 0.00 | 0.00 | 0.00 | -92826.21 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 86351.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:13 | 0.00 | 0.00 | 0.00 | -814688.90 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 749939.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-04:13 | 0.00 | 0.00 | 0.00 | -83793.99 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 77319.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-15:42 | 0.00 | 0.00 | 0.00 | -16341.77 | 0.00 | 0.00 | 40.13 | 43.94 | 720.18 | 5840.95 | 0.00 | 115.11 | 9581.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-08:21 | 0.00 | 0.00 | 0.00 | -27590.61 | 0.00 | 0.00 | 15.43 | 28.32 | 464.11 | 23777.54 | 0.00 | 0.00 | 3334.39 | 0.00 | -0.00 | 0.00 | -29.18 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-SEP-13:01 | 0.00 | 0.00 | 0.00 | -32874.79 | 0.00 | 0.00 | 25.46 | 43.94 | 720.19 | 29153.05 | 0.00 | 69.84 | 2862.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-AUG-16:21 | 0.00 | 0.00 | 0.00 | -34814.52 | 0.00 | 0.00 | 11.67 | 28.32 | 464.11 | 21402.31 | 0.00 | 42.37 | 12865.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:52 | 0.00 | 0.00 | 0.00 | -147446.13 | 0.00 | 0.00 | 0.00 | 439.44 | 5591.71 | 57883.58 | 0.00 | 1035.15 | 82496.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:31 | 0.00 | 0.00 | 0.00 | -301768.68 | 0.00 | 0.00 | 145.51 | 283.19 | 4641.14 | 233218.68 | 0.00 | 0.00 | 64175.99 | 0.00 | -0.00 | 0.00 | -695.83 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-13:11 | 0.00 | 0.00 | 0.00 | -354950.25 | 0.00 | 0.00 | 224.58 | 439.45 | 7201.95 | 346428.29 | 0.00 | 0.00 | 6011.04 | 0.00 | -0.00 | 0.00 | -5355.06 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-18:11 | 0.00 | 0.00 | 0.00 | -313346.13 | 0.00 | 0.00 | 0.00 | 283.19 | 3603.49 | 217260.58 | 0.00 | 0.00 | 92966.98 | 0.00 | -0.00 | 0.00 | -768.10 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-18:22 | 0.00 | 0.00 | 0.00 | -17557.23 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 6728.95 | 0.00 | 0.00 | 10278.06 | 0.00 | -0.00 | 0.00 | -52.89 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:21 | 0.00 | 0.00 | 0.00 | -29706.65 | 0.00 | 0.00 | 15.87 | 28.32 | 464.11 | 22414.63 | 0.00 | 0.00 | 7023.77 | 0.00 | -0.00 | 0.00 | -240.05 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -33749.49 | 0.00 | 0.00 | 21.83 | 43.94 | 720.19 | 30200.26 | 0.00 | 260.56 | 2502.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:41 | 0.00 | 0.00 | 0.00 | -34097.55 | 0.00 | 0.00 | 0.00 | 28.32 | 360.35 | 22978.80 | 0.00 | 0.00 | 10836.65 | 0.00 | -0.00 | 0.00 | -106.57 | 0.00 |
DATACENTER_BOT_ZN_6 | 22-APR-18:12 | 0.00 | 0.00 | 0.00 | -8437.95 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 625.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -80343.46 | 0.00 | 0.00 | 106.16 | 1055.42 | 77944.22 | 0.00 | 0.00 | 0.00 | 1237.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -8096.72 | 0.00 | 0.00 | 10.62 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 186.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | -370022.08 | 0.00 | 0.00 | 2181.35 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15948.98 |
GROUNDFLOOR_PLENUM | 17-JUL-05:15 | 0.00 | -14730.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14752.57 | 0.00 | -0.00 | 0.00 | -22.00 | 0.00 |
MIDFLOOR_PLENUM | 27-NOV-04:11 | 0.00 | -139095.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162643.12 | 0.00 | -0.00 | 0.00 | -23548.02 | 0.00 |
TOPFLOOR_PLENUM | 25-JUL-17:04 | 0.00 | -24363.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 | 24272.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -79173.80 | 0.00 | -1756960.84 | 0.00 | 0.00 | 16109.22 | 10593.62 | 616289.16 | 0.00 | 0.00 | 0.00 | 1276845.88 | 0.00 | -81135.01 | 0.00 | -2568.22 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 476849.48 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -541599.31 |
CORE_TOP | 09-JAN-04:11 | 0.00 | 0.00 | 75434.23 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -81909.21 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 13101.67 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8408.04 | 0.00 | -383.82 | -5122.84 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 15289.92 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5565.22 | 0.00 | -255.92 | -9992.72 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 22124.32 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8050.25 | 0.00 | -381.38 | -14505.74 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 12747.32 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5649.28 | 0.00 | -264.73 | -7357.26 |
PERIMETER_MID_ZN_3 | 29-JAN-06:51 | 0.00 | 0.00 | 135250.94 | 0.00 | 0.00 | 0.00 | 898.55 | 923.58 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84925.57 | 0.00 | -9250.32 | -50099.02 |
PERIMETER_MID_ZN_2 | 29-JAN-06:51 | 0.00 | 0.00 | 201583.89 | 0.00 | 0.00 | 0.00 | 579.64 | 595.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -56607.25 | 0.00 | -6271.95 | -144520.66 |
PERIMETER_MID_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 244141.04 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -78016.08 | 0.00 | -8718.31 | -165537.09 |
PERIMETER_MID_ZN_4 | 29-JAN-06:51 | 0.00 | 0.00 | 202378.70 | 0.00 | 0.00 | 0.00 | 574.65 | 595.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58763.86 | 0.00 | -6327.14 | -143098.65 |
PERIMETER_TOP_ZN_3 | 09-JAN-04:11 | 0.00 | 0.00 | 16935.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7696.03 | 0.00 | -1013.89 | -9039.05 |
PERIMETER_TOP_ZN_2 | 09-JAN-04:11 | 0.00 | 0.00 | 23032.17 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5128.54 | 0.00 | -685.70 | -17741.88 |
PERIMETER_TOP_ZN_1 | 09-JAN-04:11 | 0.00 | 0.00 | 28437.72 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7503.86 | 0.00 | -1028.52 | -20718.39 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:11 | 0.00 | 0.00 | 25517.49 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5019.97 | 0.00 | -692.99 | -20328.47 |
DATACENTER_BOT_ZN_6 | 30-JAN-02:06 | 0.00 | 0.00 | 528.18 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2494.38 |
DATACENTER_MID_ZN_6 | 29-JAN-19:15 | 0.00 | 0.00 | 6532.63 | 0.00 | 0.00 | 0.00 | 0.00 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26194.60 |
DATACENTER_TOP_ZN_6 | 29-JAN-17:55 | 0.00 | 0.00 | 726.66 | 0.00 | 0.00 | 0.00 | 6.54 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2699.39 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-AUG-15:41 | 14271.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14507.96 |
MIDFLOOR_PLENUM | 15-OCT-14:31 | 153937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1582.19 | -152355.20 |
TOPFLOOR_PLENUM | 11-JAN-05:31 | 34122.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -345.04 | -33777.52 |
Total Facility | 09-JAN-05:01 | -42407.76 | 95526.86 | 1374142.43 | -95526.86 | 0.00 | 0.00 | 0.00 | 10593.62 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -331295.64 | 0.00 | -52565.88 | -1190891.99 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.4090 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.3053 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 119.5804 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 95.8095 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.2547 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.9193 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7428 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7428 | 0.2090 | 1.0000 | Not calculated | 1.2002 | 0.2090 | ||
AIRLOOP DATACENTER BASEMENT | 28.0253 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 28.0255 | 0.0121 | 1.0000 | Not calculated | 0.3384 | 0.0121 | ||
AIRLOOP DATACENTER BOT | 0.5636 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5636 | 0.0277 | 1.0000 | Not calculated | 0.0156 | 0.0277 | ||
AIRLOOP DATACENTER MID | 5.4170 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4170 | 0.0289 | 1.0000 | Not calculated | 0.1563 | 0.0289 | ||
AIRLOOP DATACENTER TOP | 0.5514 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5514 | 0.0284 | 1.0000 | Not calculated | 0.0156 | 0.0284 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.2045 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2821 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.7902 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8309 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1274 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2914 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 28.0253 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 28.0253 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0121 | ||
AIRLOOP DATACENTER BOT | 0.5636 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5636 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0277 | ||
AIRLOOP DATACENTER MID | 5.4170 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4170 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0289 | ||
AIRLOOP DATACENTER TOP | 0.5514 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5514 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0284 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.7428 | 5.7428 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1910 | 6.1910 | 1.6159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 58.0921 | 58.0921 | 16.1496 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7153 | 5.7153 | 1.6174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0572 | 1.0572 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4960 | 1.4960 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8231 | 1.8231 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8417 | 1.8417 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8761 | 9.8761 | 2.0345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.0084 | 16.0084 | 1.3127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.4773 | 18.4773 | 2.0325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.1266 | 17.1266 | 1.3016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1541 | 1.1541 | 0.2089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6022 | 1.6022 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9780 | 1.9780 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8052 | 1.8052 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5636 | 0.5636 | 0.5636 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4170 | 5.4170 | 5.4170 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5514 | 0.5514 | 0.5514 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 28.0253 | 28.0253 | 28.0253 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.4090 | 10.3053 | 12.4090 | 2.2821 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 119.5804 | 95.8095 | 119.5804 | 22.8309 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.2547 | 10.9193 | 12.2547 | 2.2914 | 0.0000 | 1.0000 |
CAV_BAS | 5.7428 | 5.7428 | 5.7428 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 28.0253 | 28.0255 | 28.0253 | 28.0253 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5636 | 0.5636 | 0.5636 | 0.5636 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4170 | 5.4170 | 5.4170 | 5.4170 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5514 | 0.5514 | 0.5514 | 0.5514 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0955 | 3.0955 | 1.6159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.0460 | 29.0460 | 16.1496 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8577 | 2.8577 | 1.6174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5286 | 0.5286 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7480 | 0.7480 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9115 | 0.9115 | 0.2024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9208 | 0.9208 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9380 | 4.9380 | 2.0345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.0042 | 8.0042 | 1.3127 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2387 | 9.2387 | 2.0325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5633 | 8.5633 | 1.3016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5770 | 0.5770 | 0.2089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8011 | 0.8011 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9890 | 0.9890 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9026 | 0.9026 | 0.1300 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5636 | 0.5636 | 0.5636 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4170 | 5.4170 | 5.4170 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5514 | 0.5514 | 0.5514 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 28.0253 | 28.0253 | 28.0253 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.2045 | 2.2821 | 2.2821 | 2.2821 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.7902 | 22.8309 | 22.8309 | 22.8309 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1274 | 2.2914 | 2.2914 | 2.2914 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 28.0253 | 28.0253 | 28.0253 | 28.0253 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5636 | 0.5636 | 0.5636 | 0.5636 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4170 | 5.4170 | 5.4170 | 5.4170 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5514 | 0.5514 | 0.5514 | 0.5514 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 112.33 |
Number of hours cooling loads not met | 975.33 |
Number of hours not met | 1049.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3281.10 | 2405335.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1301.14 | 424184.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2464.19 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.53 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2726.61 | 332285.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 342.83 | 46383.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 330.59 | 74189.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2428.56 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 478.33 | 58671.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27671.46 |
Natural Gas | 0.00 | 3281.10 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30952.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.20 |
Space Heating | 0.00 |
Space Cooling | 28.09 |
Fans (All) | 58.86 |
Service Water Heating | 10.33 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 597.39 |
Subtotal | 597.39 |
Natural Gas [MJ/m2] | |
Space Heating | 70.83 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 70.83 |
Subtotal | 70.83 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.96 |
Space Heating | 10.60 |
Space Cooling | 4.20 |
Fans (All) | 8.81 |
Service Water Heating | 1.55 |
Receptacle Equipment | 47.42 |
Miscellaneous | 19.46 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 642. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8172.50 | 350.33 | 104.00 | 133.17 | 0.00 |
CORE_BOTTOM | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8722.17 | 37.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8660.50 | 99.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8719.50 | 40.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8718.17 | 41.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8610.33 | 149.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8714.17 | 45.83 | 0.00 | 0.00 | 0.00 |
Min | 8172.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 350.33 | 104.00 | 133.17 | 0.00 |
Average | 8707.23 | 42.46 | 4.52 | 5.79 | 0.00 |
Sum | 200266.33 | 976.50 | 104.00 | 133.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 349812.33 | 8783.67 | 3250.83 | 6769.17 | 0.00 |
CORE_BOTTOM | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38895.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38914.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24904.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38917.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2267.33 | 0.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101923.00 | 1472.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 349812.33 | 8783.67 | 3250.83 | 6769.17 | 0.00 |
Average | 79450.14 | 449.12 | 141.34 | 294.31 | 0.00 |
Sum | 1827353.17 | 10329.83 | 3250.83 | 6769.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8262.00 | 266.00 | 95.50 | 134.33 | 2.17 |
CORE_BOTTOM | 8717.67 | 42.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8686.50 | 73.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8646.67 | 113.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8743.50 | 16.50 | 0.00 | 0.00 | 0.00 |
Min | 8262.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 266.00 | 95.50 | 134.33 | 2.17 |
Average | 8712.25 | 37.66 | 4.15 | 5.84 | 0.09 |
Sum | 200381.83 | 866.17 | 95.50 | 134.33 | 2.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 350250.50 | 8819.83 | 2569.33 | 6667.67 | 308.67 |
CORE_BOTTOM | 330750.00 | 63.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330725.00 | 88.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330762.00 | 51.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38919.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 102234.00 | 1161.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 350250.50 | 8819.83 | 2569.33 | 6667.67 | 308.67 |
Average | 79476.13 | 443.75 | 111.71 | 289.90 | 13.42 |
Sum | 1827951.00 | 10206.33 | 2569.33 | 6667.67 | 308.67 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:24
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383903E+11 | 108902.81 | 02-JAN-07:03 | -2.2 | -4.3 | 0.567719E+10 | 7499.20 | 09-JAN-10:20 | -26.1 | -26.5 |
February | 0.377691E+11 | 100737.77 | 21-FEB-07:11 | 6.70 | 0.52 | 0.514923E+10 | 7499.18 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.480127E+11 | 92635.89 | 20-MAR-06:05 | -1.1 | -3.2 | 0.614781E+10 | 7499.21 | 14-MAR-09:30 | -1.1 | -3.2 |
April | 0.468576E+11 | 97262.47 | 24-APR-06:03 | 4.45 | 3.48 | 0.546609E+10 | 7499.23 | 04-APR-09:09 | 4.45 | 3.48 |
May | 0.489635E+11 | 99743.18 | 15-MAY-06:11 | 6.70 | 2.03 | 0.592213E+10 | 7542.11 | 30-MAY-09:50 | 18.53 | 11.67 |
June | 0.506582E+11 | 98297.24 | 05-JUN-06:11 | 13.17 | 8.04 | 0.610969E+10 | 10582.85 | 23-JUN-13:00 | 31.70 | 15.26 |
July | 0.425827E+11 | 113102.21 | 21-JUL-06:11 | 15.73 | 9.54 | 0.654984E+10 | 12771.07 | 20-JUL-13:00 | 15.73 | 9.54 |
August | 0.522817E+11 | 109163.24 | 12-AUG-06:11 | 15.33 | 8.28 | 0.673517E+10 | 11781.60 | 07-AUG-13:00 | 15.33 | 8.28 |
September | 0.528235E+11 | 101484.38 | 11-SEP-06:11 | 10.40 | 9.65 | 0.554741E+10 | 11004.74 | 05-SEP-08:30 | 10.40 | 9.65 |
October | 0.540753E+11 | 103072.01 | 23-OCT-06:11 | 10.00 | 4.07 | 0.569597E+10 | 7609.47 | 18-OCT-13:50 | 10.00 | 4.07 |
November | 0.499326E+11 | 99982.64 | 13-NOV-07:03 | -5.9 | -8.5 | 0.563501E+10 | 7499.27 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.457790E+11 | 96635.40 | 26-DEC-07:03 | -8.5 | -9.6 | 0.548440E+10 | 7499.19 | 19-DEC-10:20 | -8.5 | -9.6 |
Annual Sum or Average | 0.568126E+12 | 0.701199E+11 | ||||||||
Minimum of Months | 0.377691E+11 | 92635.89 | -8.5 | -9.6 | 0.514923E+10 | 7499.18 | -26.1 | -26.5 | ||
Maximum of Months | 0.540753E+11 | 113102.21 | 15.73 | 9.65 | 0.673517E+10 | 12771.07 | 31.70 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305062E+11 | 87944.59 | 02-JAN-04:01 | -0.5 | -3.0 | 0.503367E+10 | 6734.83 | 11-JAN-10:20 | -6.5 | -8.4 |
February | 0.329295E+11 | 81978.65 | 27-FEB-05:11 | 4.07 | 0.00 | 0.459005E+10 | 6734.77 | 23-FEB-10:39 | 4.07 | 0.00 |
March | 0.456145E+11 | 81030.10 | 20-MAR-04:01 | -1.1 | -3.1 | 0.549640E+10 | 6734.81 | 14-MAR-09:30 | -1.1 | -3.1 |
April | 0.496289E+11 | 85496.78 | 10-APR-04:11 | 4.23 | 0.21 | 0.488424E+10 | 6734.76 | 04-APR-09:09 | 4.23 | 0.21 |
May | 0.463642E+11 | 89649.61 | 30-MAY-04:13 | 15.60 | 10.93 | 0.529005E+10 | 6735.26 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.568859E+11 | 90678.88 | 22-JUN-04:13 | 16.10 | 12.27 | 0.528364E+10 | 7608.97 | 22-JUN-09:00 | 25.60 | 16.64 |
July | 0.679713E+11 | 92828.44 | 21-JUL-04:13 | 11.83 | 7.66 | 0.500061E+10 | 7548.01 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.710963E+11 | 88615.07 | 07-AUG-04:23 | 18.90 | 10.50 | 0.557563E+10 | 7813.94 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.497259E+11 | 88064.62 | 05-SEP-04:13 | 18.30 | 11.92 | 0.489010E+10 | 7014.34 | 01-SEP-13:00 | 18.30 | 11.92 |
October | 0.472411E+11 | 84761.66 | 10-OCT-03:01 | -4.1 | -4.8 | 0.508070E+10 | 6775.34 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.434393E+11 | 82771.03 | 06-NOV-04:03 | -2.8 | -3.9 | 0.502930E+10 | 6734.78 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.398740E+11 | 82032.97 | 11-DEC-04:01 | -2.6 | -4.7 | 0.489537E+10 | 6734.83 | 07-DEC-10:20 | -2.6 | -4.7 |
Annual Sum or Average | 0.581277E+12 | 0.610498E+11 | ||||||||
Minimum of Months | 0.305062E+11 | 81030.10 | -4.1 | -4.8 | 0.459005E+10 | 6734.76 | -6.5 | -8.4 | ||
Maximum of Months | 0.710963E+11 | 92828.44 | 18.90 | 12.27 | 0.557563E+10 | 7813.94 | 33.90 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193465E+11 | 19421.30 | 04-JAN-17:00 | 1.10 | -3.1 | 0.460056E+10 | 6734.68 | 05-JAN-14:30 | -17.8 | -18.4 |
February | 0.204750E+11 | 54192.68 | 28-FEB-06:03 | -3.9 | -4.3 | 0.435187E+10 | 6734.75 | 23-FEB-10:39 | -3.9 | -4.3 |
March | 0.284965E+11 | 67625.60 | 30-MAR-05:03 | 0.00 | -2.1 | 0.538353E+10 | 6734.77 | 14-MAR-09:30 | 0.00 | -2.1 |
April | 0.310043E+11 | 73658.26 | 26-APR-05:02 | 5.37 | 2.97 | 0.485177E+10 | 6734.77 | 04-APR-09:09 | 5.37 | 2.97 |
May | 0.352358E+11 | 75239.94 | 30-MAY-04:12 | 15.60 | 10.93 | 0.527255E+10 | 6735.28 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.431776E+11 | 75986.24 | 23-JUN-04:12 | 18.13 | 11.74 | 0.526987E+10 | 7254.85 | 22-JUN-09:00 | 18.13 | 11.74 |
July | 0.451983E+11 | 77149.40 | 05-JUL-04:12 | 9.40 | 8.79 | 0.491475E+10 | 7252.44 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.469767E+11 | 76590.75 | 14-AUG-04:12 | 12.20 | 9.88 | 0.551125E+10 | 7148.08 | 07-AUG-13:00 | 12.20 | 9.88 |
September | 0.380483E+11 | 81475.70 | 05-SEP-04:13 | 18.30 | 11.92 | 0.487495E+10 | 6754.30 | 01-SEP-13:00 | 18.30 | 11.92 |
October | 0.320774E+11 | 73523.65 | 20-OCT-05:02 | 2.70 | 0.86 | 0.505303E+10 | 6734.83 | 18-OCT-13:00 | 2.70 | 0.86 |
November | 0.255869E+11 | 68329.85 | 04-NOV-05:02 | 9.43 | 5.60 | 0.491686E+10 | 6734.77 | 03-NOV-09:09 | 9.43 | 5.60 |
December | 0.212359E+11 | 27175.94 | 07-DEC-16:20 | 5.93 | 1.89 | 0.463766E+10 | 6734.80 | 07-DEC-10:20 | 5.93 | 1.89 |
Annual Sum or Average | 0.386859E+12 | 0.596386E+11 | ||||||||
Minimum of Months | 0.193465E+11 | 19421.30 | -3.9 | -4.3 | 0.435187E+10 | 6734.68 | -17.8 | -18.4 | ||
Maximum of Months | 0.469767E+11 | 81475.70 | 18.30 | 11.92 | 0.551125E+10 | 7254.85 | 27.33 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102682E+11 | 13848.92 | 13-JAN-16:50 | 7.98 | 4.06 | 0.394865E+10 | 6245.39 | 13-JAN-14:00 | 7.98 | 4.06 |
February | 0.126982E+11 | 22918.24 | 28-FEB-17:00 | 10.00 | 4.31 | 0.384018E+10 | 6733.53 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.188216E+11 | 27021.79 | 29-MAR-16:00 | 12.20 | 4.07 | 0.492216E+10 | 6734.61 | 22-MAR-13:39 | 12.20 | 4.07 |
April | 0.230040E+11 | 45463.18 | 07-APR-05:02 | 12.20 | 5.15 | 0.464615E+10 | 6734.72 | 06-APR-09:09 | 12.20 | 5.15 |
May | 0.296135E+11 | 70813.26 | 30-MAY-05:03 | 15.60 | 11.34 | 0.511036E+10 | 6735.27 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.420775E+11 | 74858.65 | 22-JUN-04:12 | 16.10 | 12.27 | 0.525651E+10 | 7272.29 | 22-JUN-09:00 | 25.60 | 16.64 |
July | 0.461121E+11 | 74140.35 | 27-JUL-04:12 | 14.23 | 9.88 | 0.492637E+10 | 7513.92 | 25-JUL-13:00 | 14.23 | 9.88 |
August | 0.455556E+11 | 82418.25 | 07-AUG-04:13 | 19.47 | 10.72 | 0.551458E+10 | 7554.74 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.324676E+11 | 83800.45 | 05-SEP-04:13 | 18.30 | 11.92 | 0.479834E+10 | 6815.88 | 01-SEP-13:00 | 18.30 | 11.92 |
October | 0.224656E+11 | 43280.34 | 19-OCT-05:02 | 12.20 | 5.54 | 0.480003E+10 | 6734.77 | 18-OCT-13:00 | 12.20 | 5.54 |
November | 0.161009E+11 | 24583.54 | 03-NOV-16:00 | 14.30 | 7.69 | 0.438394E+10 | 6734.63 | 02-NOV-13:20 | 14.30 | 7.69 |
December | 0.121576E+11 | 16847.23 | 06-DEC-16:30 | 8.05 | 3.45 | 0.397620E+10 | 6723.29 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.311343E+12 | 0.561235E+11 | ||||||||
Minimum of Months | 0.102682E+11 | 13848.92 | 7.98 | 3.45 | 0.384018E+10 | 6245.39 | 7.98 | 2.55 | ||
Maximum of Months | 0.461121E+11 | 83800.45 | 19.47 | 12.27 | 0.551458E+10 | 7554.74 | 32.80 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115766E+10 | 2459.85 | 02-JAN-14:30 | 6.40 | 1.35 | 0.510635E+09 | 845.60 | 02-JAN-14:09 | 6.40 | 1.35 |
February | 0.177311E+10 | 4322.98 | 27-FEB-16:00 | 18.90 | 7.06 | 0.500468E+09 | 845.61 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.303186E+10 | 5062.43 | 27-MAR-14:00 | 8.90 | 2.28 | 0.651044E+09 | 845.63 | 14-MAR-09:30 | 8.90 | 2.28 |
April | 0.437774E+10 | 7234.21 | 07-APR-14:00 | 23.30 | 9.68 | 0.601273E+09 | 845.63 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.530431E+10 | 12862.40 | 30-MAY-04:12 | 15.60 | 10.93 | 0.655074E+09 | 845.69 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.876233E+10 | 15484.33 | 25-JUN-18:11 | 22.77 | 14.07 | 0.663365E+09 | 963.82 | 22-JUN-09:00 | 22.77 | 14.07 |
July | 0.108064E+11 | 15712.41 | 30-JUL-16:51 | 31.10 | 14.91 | 0.633843E+09 | 996.33 | 25-JUL-13:00 | 31.10 | 14.91 |
August | 0.101361E+11 | 16341.67 | 06-AUG-15:42 | 35.40 | 16.19 | 0.701482E+09 | 1007.86 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.555466E+10 | 15453.70 | 03-SEP-13:41 | 33.80 | 16.23 | 0.608146E+09 | 873.73 | 01-SEP-13:00 | 33.80 | 16.23 |
October | 0.373318E+10 | 5902.38 | 19-OCT-14:30 | 21.40 | 10.24 | 0.622237E+09 | 846.20 | 18-OCT-13:39 | 21.40 | 10.24 |
November | 0.261513E+10 | 4249.96 | 24-NOV-14:30 | 14.90 | 6.43 | 0.587422E+09 | 845.62 | 16-NOV-14:09 | 14.90 | 6.43 |
December | 0.184473E+10 | 2911.17 | 06-DEC-13:30 | 12.25 | 6.08 | 0.535040E+09 | 845.62 | 06-DEC-10:39 | 12.25 | 6.08 |
Annual Sum or Average | 0.590972E+11 | 0.727003E+10 | ||||||||
Minimum of Months | 0.115766E+10 | 2459.85 | 6.40 | 1.35 | 0.500468E+09 | 845.60 | 6.40 | 1.35 | ||
Maximum of Months | 0.108064E+11 | 16341.67 | 35.40 | 16.23 | 0.701482E+09 | 1007.86 | 33.80 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.932253E+09 | 3960.67 | 17-JAN-10:10 | 4.68 | 0.96 | 0.342066E+09 | 544.95 | 19-JAN-10:00 | -11.1 | -11.8 |
February | 0.169749E+10 | 9954.85 | 26-FEB-10:43 | 11.42 | 4.08 | 0.336699E+09 | 544.95 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.311247E+10 | 11628.11 | 28-MAR-09:05 | 5.37 | 0.68 | 0.425538E+09 | 544.96 | 10-MAR-10:20 | 5.37 | 0.68 |
April | 0.466762E+10 | 20610.25 | 16-APR-08:42 | 11.83 | 5.16 | 0.386758E+09 | 546.14 | 24-APR-09:30 | 13.05 | 8.33 |
May | 0.591067E+10 | 14026.93 | 19-MAY-08:30 | 16.95 | 11.09 | 0.423230E+09 | 545.80 | 19-MAY-09:09 | 18.17 | 11.56 |
June | 0.912385E+10 | 26260.07 | 25-JUN-08:11 | 15.97 | 11.51 | 0.428192E+09 | 684.12 | 22-JUN-09:00 | 15.97 | 11.51 |
July | 0.113422E+11 | 24525.50 | 02-JUL-08:31 | 21.67 | 15.15 | 0.404600E+09 | 704.52 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.102423E+11 | 27585.68 | 06-AUG-08:21 | 25.25 | 14.09 | 0.450792E+09 | 681.35 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.591467E+10 | 24062.74 | 03-SEP-09:41 | 27.33 | 14.61 | 0.393748E+09 | 563.38 | 01-SEP-09:30 | 27.33 | 14.61 |
October | 0.372495E+10 | 12596.91 | 15-OCT-09:23 | 14.75 | 7.52 | 0.403676E+09 | 545.39 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.203253E+10 | 7542.61 | 06-NOV-09:25 | 0.80 | -1.3 | 0.382659E+09 | 544.95 | 03-NOV-09:09 | 0.80 | -1.3 |
December | 0.119437E+10 | 3789.58 | 20-DEC-10:05 | 3.48 | -0.5 | 0.348111E+09 | 544.95 | 07-DEC-10:20 | 3.48 | -0.5 |
Annual Sum or Average | 0.598954E+11 | 0.472607E+10 | ||||||||
Minimum of Months | 0.932253E+09 | 3789.58 | 0.80 | -1.3 | 0.336699E+09 | 544.95 | -11.1 | -11.8 | ||
Maximum of Months | 0.113422E+11 | 27585.68 | 27.33 | 15.15 | 0.450792E+09 | 704.52 | 30.60 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348652E+10 | 27449.37 | 01-JAN-13:32 | 8.13 | 2.98 | 0.552432E+09 | 845.65 | 13-JAN-14:30 | 8.90 | 4.37 |
February | 0.604799E+10 | 29696.09 | 26-FEB-13:22 | 15.30 | 5.63 | 0.539382E+09 | 854.71 | 27-FEB-14:09 | 18.40 | 7.06 |
March | 0.786389E+10 | 27747.46 | 26-MAR-13:32 | 9.63 | 1.94 | 0.659601E+09 | 870.06 | 01-MAR-14:09 | 9.63 | 1.94 |
April | 0.802584E+10 | 28445.60 | 23-APR-11:52 | 16.10 | 8.81 | 0.597621E+09 | 847.60 | 04-APR-13:09 | 16.10 | 8.81 |
May | 0.808562E+10 | 25948.60 | 14-MAY-11:53 | 16.10 | 6.95 | 0.649253E+09 | 846.37 | 19-MAY-13:00 | 27.20 | 15.02 |
June | 0.111073E+11 | 27768.57 | 11-JUN-13:02 | 25.82 | 13.32 | 0.662993E+09 | 969.94 | 21-JUN-12:30 | 26.15 | 17.35 |
July | 0.144089E+11 | 28242.66 | 16-JUL-13:02 | 29.78 | 18.22 | 0.633791E+09 | 1057.53 | 25-JUL-13:50 | 33.90 | 15.43 |
August | 0.158943E+11 | 31621.13 | 06-AUG-13:41 | 34.32 | 15.27 | 0.717365E+09 | 1155.61 | 07-AUG-13:39 | 32.80 | 15.78 |
September | 0.120066E+11 | 32874.86 | 03-SEP-13:01 | 33.40 | 15.99 | 0.616152E+09 | 1082.85 | 01-SEP-13:50 | 33.40 | 15.99 |
October | 0.102296E+11 | 30329.94 | 15-OCT-13:21 | 22.75 | 10.91 | 0.627999E+09 | 1068.01 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.699579E+10 | 29148.60 | 12-NOV-11:32 | -3.9 | -5.8 | 0.602298E+09 | 869.01 | 03-NOV-13:20 | -3.9 | -5.8 |
December | 0.462919E+10 | 24905.00 | 17-DEC-13:13 | -1.5 | -4.1 | 0.562444E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.108781E+12 | 0.742133E+10 | ||||||||
Minimum of Months | 0.348652E+10 | 24905.00 | -3.9 | -5.8 | 0.539382E+09 | 845.64 | -3.9 | -5.8 | ||
Maximum of Months | 0.158943E+11 | 32874.86 | 34.32 | 18.22 | 0.717365E+09 | 1155.61 | 33.90 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132201E+10 | 6443.80 | 13-JAN-15:30 | 9.45 | 4.93 | 0.354561E+09 | 544.95 | 02-JAN-10:30 | 9.45 | 4.93 |
February | 0.298683E+10 | 21113.48 | 26-FEB-15:22 | 16.40 | 6.36 | 0.354079E+09 | 544.95 | 24-FEB-10:20 | 16.40 | 6.36 |
March | 0.557929E+10 | 19908.11 | 12-MAR-15:52 | 6.10 | -0.7 | 0.441360E+09 | 544.95 | 14-MAR-09:30 | 8.90 | 3.33 |
April | 0.856145E+10 | 30753.82 | 16-APR-16:41 | 20.00 | 8.94 | 0.395986E+09 | 544.96 | 13-APR-13:39 | 20.00 | 8.94 |
May | 0.784487E+10 | 33457.86 | 28-MAY-17:11 | 20.73 | 10.39 | 0.426974E+09 | 545.00 | 02-MAY-13:09 | 20.73 | 10.39 |
June | 0.114541E+11 | 30077.60 | 25-JUN-18:11 | 22.77 | 14.07 | 0.428583E+09 | 604.94 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.142350E+11 | 32891.19 | 30-JUL-16:51 | 31.10 | 14.91 | 0.404525E+09 | 655.25 | 25-JUL-15:00 | 31.10 | 14.91 |
August | 0.147137E+11 | 34814.70 | 06-AUG-16:21 | 35.30 | 16.02 | 0.451980E+09 | 660.09 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.750782E+10 | 29727.83 | 24-SEP-16:31 | 24.40 | 13.62 | 0.395931E+09 | 589.36 | 01-SEP-15:00 | 24.40 | 13.62 |
October | 0.587708E+10 | 27826.74 | 15-OCT-16:02 | 22.02 | 10.75 | 0.410378E+09 | 545.64 | 18-OCT-13:39 | 24.80 | 11.21 |
November | 0.442515E+10 | 12225.80 | 17-NOV-06:02 | 12.43 | 7.17 | 0.403589E+09 | 544.96 | 16-NOV-14:09 | 12.43 | 7.17 |
December | 0.331055E+10 | 9851.76 | 06-DEC-15:30 | 10.25 | 4.94 | 0.386443E+09 | 544.96 | 07-DEC-10:20 | 3.90 | 1.50 |
Annual Sum or Average | 0.878178E+11 | 0.485439E+10 | ||||||||
Minimum of Months | 0.132201E+10 | 6443.80 | 6.10 | -0.7 | 0.354079E+09 | 544.95 | 3.90 | 1.50 | ||
Maximum of Months | 0.147137E+11 | 34814.70 | 35.30 | 16.02 | 0.451980E+09 | 660.09 | 32.20 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184029E+09 | 1285.01 | 15-JAN-13:12 | 5.20 | -0.5 | 0.464515E+09 | 655.78 | 03-JAN-14:50 | 5.20 | -0.5 |
February | 0.675878E+09 | 2226.79 | 27-FEB-14:20 | 18.50 | 7.10 | 0.439428E+09 | 791.11 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.158799E+10 | 2605.97 | 29-MAR-15:50 | 12.30 | 4.10 | 0.565987E+09 | 845.60 | 29-MAR-13:39 | 12.30 | 4.10 |
April | 0.240934E+10 | 5618.64 | 07-APR-14:30 | 22.50 | 9.29 | 0.554414E+09 | 845.62 | 17-APR-13:20 | 14.80 | 7.60 |
May | 0.388419E+10 | 7334.51 | 19-MAY-16:00 | 27.80 | 14.54 | 0.626320E+09 | 845.70 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.689506E+10 | 11419.29 | 23-JUN-05:03 | 17.88 | 11.72 | 0.658429E+09 | 925.93 | 22-JUN-09:00 | 17.88 | 11.72 |
July | 0.796141E+10 | 14745.18 | 16-JUL-18:52 | 32.20 | 17.25 | 0.620649E+09 | 974.75 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.690490E+10 | 14159.55 | 06-AUG-15:51 | 35.60 | 16.36 | 0.690364E+09 | 946.48 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.406791E+10 | 13752.31 | 03-SEP-15:51 | 34.40 | 16.27 | 0.588188E+09 | 848.51 | 01-SEP-13:00 | 34.40 | 16.27 |
October | 0.233134E+10 | 4556.23 | 19-OCT-14:30 | 21.40 | 10.24 | 0.572104E+09 | 845.63 | 18-OCT-13:00 | 21.40 | 10.24 |
November | 0.122875E+10 | 2207.44 | 03-NOV-14:10 | 14.93 | 7.82 | 0.505422E+09 | 836.90 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.421890E+09 | 1486.55 | 06-DEC-16:00 | 9.40 | 4.51 | 0.456330E+09 | 726.43 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.385527E+11 | 0.674215E+10 | ||||||||
Minimum of Months | 0.184029E+09 | 1285.01 | 5.20 | -0.5 | 0.439428E+09 | 655.78 | 5.20 | -0.5 | ||
Maximum of Months | 0.796141E+10 | 14745.18 | 35.60 | 17.25 | 0.690364E+09 | 974.75 | 34.40 | 16.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229474E+09 | 1133.94 | 20-JAN-11:05 | -1.9 | -4.9 | 0.224380E+09 | 516.26 | 20-JAN-11:09 | -1.9 | -4.9 |
February | 0.780380E+09 | 7151.91 | 27-FEB-11:05 | 14.68 | 5.50 | 0.226224E+09 | 548.49 | 28-FEB-11:09 | 4.37 | 1.41 |
March | 0.191416E+10 | 11535.84 | 23-MAR-10:05 | 8.40 | 1.62 | 0.292218E+09 | 548.50 | 22-MAR-10:09 | 8.40 | 1.62 |
April | 0.365499E+10 | 18823.23 | 16-APR-09:22 | 13.60 | 5.94 | 0.274627E+09 | 548.50 | 12-APR-10:09 | 13.60 | 5.94 |
May | 0.518933E+10 | 14939.28 | 19-MAY-08:50 | 17.52 | 11.29 | 0.305535E+09 | 548.56 | 02-MAY-12:09 | 17.52 | 11.29 |
June | 0.872010E+10 | 26603.60 | 18-JUN-09:31 | 17.77 | 12.44 | 0.314427E+09 | 637.99 | 22-JUN-10:09 | 25.87 | 16.63 |
July | 0.105393E+11 | 30122.45 | 02-JUL-08:51 | 22.20 | 15.44 | 0.296397E+09 | 657.97 | 14-JUL-08:00 | 25.00 | 16.36 |
August | 0.928869E+10 | 30170.44 | 06-AUG-08:31 | 25.90 | 14.14 | 0.329696E+09 | 638.12 | 07-AUG-10:20 | 30.60 | 15.25 |
September | 0.515105E+10 | 26039.24 | 03-SEP-09:51 | 27.80 | 14.77 | 0.286539E+09 | 551.55 | 01-SEP-14:09 | 27.80 | 14.77 |
October | 0.261696E+10 | 13522.84 | 15-OCT-11:11 | 19.23 | 10.02 | 0.287688E+09 | 548.50 | 27-OCT-10:09 | 10.18 | 4.94 |
November | 0.958265E+09 | 7239.62 | 03-NOV-10:05 | 9.10 | 5.57 | 0.258806E+09 | 548.50 | 03-NOV-10:09 | 9.10 | 5.57 |
December | 0.337020E+09 | 2136.43 | 07-DEC-11:05 | 6.38 | 2.62 | 0.223885E+09 | 540.42 | 07-DEC-11:09 | 6.38 | 2.62 |
Annual Sum or Average | 0.493797E+11 | 0.332042E+10 | ||||||||
Minimum of Months | 0.229474E+09 | 1133.94 | -1.9 | -4.9 | 0.223885E+09 | 516.26 | -1.9 | -4.9 | ||
Maximum of Months | 0.105393E+11 | 30170.44 | 27.80 | 15.44 | 0.329696E+09 | 657.97 | 30.60 | 16.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278385E+10 | 27665.85 | 15-JAN-13:12 | 5.20 | -0.5 | 0.529683E+09 | 845.80 | 19-JAN-14:09 | -5.5 | -7.4 |
February | 0.556458E+10 | 31386.47 | 26-FEB-13:41 | 15.50 | 5.72 | 0.522682E+09 | 890.35 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.715367E+10 | 28885.03 | 26-MAR-13:52 | 10.00 | 2.16 | 0.632192E+09 | 909.78 | 01-MAR-14:09 | 10.00 | 2.16 |
April | 0.687591E+10 | 28454.69 | 16-APR-14:42 | 19.40 | 8.41 | 0.575201E+09 | 846.65 | 05-APR-13:20 | 19.40 | 8.41 |
May | 0.746687E+10 | 28676.74 | 14-MAY-13:42 | 16.52 | 6.74 | 0.635420E+09 | 847.25 | 19-MAY-13:20 | 26.47 | 14.93 |
June | 0.992796E+10 | 28387.23 | 18-JUN-13:32 | 22.93 | 15.33 | 0.658632E+09 | 963.81 | 21-JUN-12:30 | 26.15 | 17.35 |
July | 0.123869E+11 | 29158.59 | 16-JUL-10:51 | 25.60 | 16.84 | 0.625681E+09 | 1057.64 | 31-JUL-13:00 | 30.60 | 14.62 |
August | 0.140861E+11 | 30265.71 | 06-AUG-11:11 | 31.33 | 14.80 | 0.705202E+09 | 1137.93 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.119741E+11 | 34085.46 | 03-SEP-13:12 | 33.50 | 16.05 | 0.607551E+09 | 1083.66 | 01-SEP-13:00 | 33.50 | 16.05 |
October | 0.100031E+11 | 35493.70 | 15-OCT-13:11 | 22.57 | 10.82 | 0.618042E+09 | 1051.85 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.620776E+10 | 31323.91 | 11-NOV-13:11 | -1.3 | -3.7 | 0.580772E+09 | 892.14 | 03-NOV-13:39 | -1.3 | -3.7 |
December | 0.335717E+10 | 16802.19 | 10-DEC-13:32 | 7.20 | 1.04 | 0.534258E+09 | 845.64 | 07-DEC-10:30 | 7.20 | 1.04 |
Annual Sum or Average | 0.977879E+11 | 0.722531E+10 | ||||||||
Minimum of Months | 0.278385E+10 | 16802.19 | -1.3 | -3.7 | 0.522682E+09 | 845.64 | -5.5 | -7.4 | ||
Maximum of Months | 0.140861E+11 | 35493.70 | 33.50 | 16.84 | 0.705202E+09 | 1137.93 | 33.50 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370222E+09 | 3096.43 | 13-JAN-15:40 | 9.27 | 4.85 | 0.310013E+09 | 544.87 | 13-JAN-14:00 | 9.27 | 4.85 |
February | 0.115593E+10 | 13467.96 | 26-FEB-16:22 | 15.85 | 6.07 | 0.304664E+09 | 544.94 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.227728E+10 | 12208.18 | 28-MAR-17:00 | 10.60 | 2.97 | 0.387370E+09 | 544.95 | 02-MAR-14:30 | 10.60 | 2.97 |
April | 0.385849E+10 | 27684.37 | 16-APR-17:21 | 19.70 | 8.86 | 0.370845E+09 | 544.96 | 17-APR-13:20 | 14.80 | 7.60 |
May | 0.589374E+10 | 29252.34 | 14-MAY-17:01 | 14.13 | 5.05 | 0.411050E+09 | 545.00 | 02-MAY-13:09 | 14.13 | 5.05 |
June | 0.839324E+10 | 31099.84 | 18-JUN-17:31 | 25.20 | 14.48 | 0.425451E+09 | 608.32 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.997388E+10 | 31342.34 | 02-JUL-18:11 | 25.03 | 14.25 | 0.400243E+09 | 647.57 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.898259E+10 | 30593.26 | 06-AUG-16:31 | 35.20 | 15.91 | 0.446520E+09 | 635.05 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.549733E+10 | 27860.45 | 03-SEP-15:51 | 34.40 | 16.27 | 0.385784E+09 | 590.48 | 01-SEP-15:00 | 34.40 | 16.27 |
October | 0.309806E+10 | 26318.65 | 15-OCT-16:31 | 21.47 | 10.56 | 0.384275E+09 | 544.96 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.155143E+10 | 7617.85 | 03-NOV-15:40 | 14.40 | 7.69 | 0.350196E+09 | 544.95 | 17-NOV-14:00 | 16.50 | 8.23 |
December | 0.632297E+09 | 4836.83 | 06-DEC-15:40 | 9.97 | 4.80 | 0.312870E+09 | 544.93 | 01-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.516845E+11 | 0.448928E+10 | ||||||||
Minimum of Months | 0.370222E+09 | 3096.43 | 9.27 | 2.97 | 0.304664E+09 | 544.87 | 9.27 | 2.97 | ||
Maximum of Months | 0.997388E+10 | 31342.34 | 35.20 | 16.27 | 0.446520E+09 | 647.57 | 34.40 | 16.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36507630.08 | 1225.36 | 13-JAN-16:20 | 8.53 | 4.43 | 0.458540E+09 | 626.10 | 13-JAN-14:00 | 8.53 | 4.43 |
February | 0.303493E+09 | 2031.45 | 27-FEB-13:40 | 17.93 | 6.85 | 0.425583E+09 | 742.57 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.948241E+09 | 2194.30 | 23-MAR-13:30 | 9.70 | 2.18 | 0.531768E+09 | 807.48 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.180944E+10 | 5458.10 | 07-APR-14:30 | 22.50 | 9.29 | 0.518267E+09 | 845.62 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.341907E+10 | 8063.26 | 19-MAY-16:00 | 27.80 | 14.54 | 0.599293E+09 | 845.70 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.679673E+10 | 16757.00 | 25-JUN-18:41 | 21.97 | 13.95 | 0.650991E+09 | 901.99 | 22-JUN-09:00 | 21.97 | 13.95 |
July | 0.816325E+10 | 17556.34 | 02-JUL-18:22 | 24.75 | 14.30 | 0.618030E+09 | 967.14 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.688117E+10 | 16566.89 | 06-AUG-16:01 | 35.50 | 16.24 | 0.682149E+09 | 950.62 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.366761E+10 | 16450.37 | 03-SEP-16:01 | 33.67 | 16.10 | 0.565363E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.162120E+10 | 4069.48 | 19-OCT-14:40 | 21.50 | 10.24 | 0.531601E+09 | 845.62 | 18-OCT-13:00 | 21.50 | 10.24 |
November | 0.611607E+09 | 2002.35 | 03-NOV-13:30 | 14.35 | 7.74 | 0.475662E+09 | 772.40 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.137108E+09 | 1373.45 | 06-DEC-16:00 | 9.40 | 4.51 | 0.447529E+09 | 673.10 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.343954E+11 | 0.650478E+10 | ||||||||
Minimum of Months | 36507630.08 | 1225.36 | 8.53 | 2.18 | 0.425583E+09 | 626.10 | 8.53 | 4.43 | ||
Maximum of Months | 0.816325E+10 | 17556.34 | 35.50 | 16.24 | 0.682149E+09 | 967.14 | 33.90 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125962E+09 | 959.93 | 31-JAN-10:50 | -5.4 | -8.1 | 0.300641E+09 | 468.05 | 31-JAN-10:50 | -5.4 | -8.1 |
February | 0.548067E+09 | 3995.82 | 28-FEB-10:20 | 2.03 | 0.11 | 0.294778E+09 | 544.95 | 17-FEB-10:20 | 2.03 | 0.11 |
March | 0.147082E+10 | 8396.30 | 23-MAR-10:10 | 8.40 | 1.62 | 0.380436E+09 | 544.95 | 22-MAR-09:00 | 8.40 | 1.62 |
April | 0.312693E+10 | 16524.18 | 16-APR-09:43 | 14.53 | 6.22 | 0.358777E+09 | 544.96 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.484908E+10 | 14478.88 | 19-MAY-09:05 | 18.17 | 11.56 | 0.407787E+09 | 545.48 | 19-MAY-09:09 | 18.17 | 11.56 |
June | 0.882569E+10 | 27738.35 | 25-JUN-09:21 | 18.05 | 12.22 | 0.424554E+09 | 666.33 | 22-JUN-09:00 | 18.05 | 12.22 |
July | 0.108527E+11 | 29709.72 | 02-JUL-08:21 | 21.40 | 15.01 | 0.399971E+09 | 703.77 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.947625E+10 | 26959.47 | 06-AUG-09:21 | 28.60 | 14.63 | 0.444778E+09 | 653.46 | 07-AUG-09:00 | 30.60 | 15.43 |
September | 0.488752E+10 | 24524.15 | 04-SEP-09:02 | 26.88 | 14.90 | 0.380574E+09 | 544.98 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.201138E+10 | 8624.75 | 18-OCT-09:40 | 19.07 | 8.41 | 0.378285E+09 | 544.95 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.670553E+09 | 3608.79 | 03-NOV-09:50 | 8.30 | 5.09 | 0.328215E+09 | 544.95 | 03-NOV-09:09 | 8.30 | 5.09 |
December | 0.194197E+09 | 1009.17 | 20-DEC-10:40 | 4.03 | -0.3 | 0.293413E+09 | 484.91 | 20-DEC-10:39 | 4.03 | -0.3 |
Annual Sum or Average | 0.470392E+11 | 0.439221E+10 | ||||||||
Minimum of Months | 0.125962E+09 | 959.93 | -5.4 | -8.1 | 0.293413E+09 | 468.05 | -5.4 | -8.1 | ||
Maximum of Months | 0.108527E+11 | 29709.72 | 28.60 | 15.01 | 0.444778E+09 | 703.77 | 30.60 | 16.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181035E+10 | 16166.71 | 15-JAN-13:52 | 5.60 | -0.5 | 0.510586E+09 | 845.64 | 30-JAN-14:20 | -6.3 | -9.2 |
February | 0.414890E+10 | 32315.77 | 26-FEB-14:21 | 16.15 | 6.12 | 0.504871E+09 | 845.90 | 28-FEB-14:00 | 10.60 | 4.78 |
March | 0.567329E+10 | 23731.56 | 01-MAR-14:00 | 6.70 | 2.77 | 0.601769E+09 | 849.40 | 01-MAR-14:09 | 6.97 | 2.89 |
April | 0.571503E+10 | 28257.01 | 16-APR-13:42 | 19.22 | 8.29 | 0.549116E+09 | 846.20 | 06-APR-13:00 | 19.22 | 8.29 |
May | 0.677512E+10 | 30348.50 | 14-MAY-13:42 | 16.52 | 6.74 | 0.616007E+09 | 846.36 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.982641E+10 | 30281.47 | 18-JUN-13:42 | 23.12 | 15.42 | 0.651440E+09 | 948.19 | 21-JUN-12:30 | 26.15 | 17.35 |
July | 0.125906E+11 | 31427.61 | 02-JUL-15:01 | 24.90 | 14.06 | 0.623558E+09 | 1051.04 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.140563E+11 | 31791.47 | 06-AUG-13:22 | 34.15 | 15.08 | 0.698319E+09 | 1139.03 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.112552E+11 | 33749.45 | 03-SEP-12:41 | 33.22 | 15.94 | 0.590754E+09 | 1059.87 | 01-SEP-13:00 | 33.22 | 15.94 |
October | 0.825912E+10 | 33105.54 | 15-OCT-14:01 | 23.22 | 11.15 | 0.595931E+09 | 983.40 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.443314E+10 | 30326.14 | 11-NOV-13:11 | -1.3 | -3.7 | 0.556550E+09 | 846.08 | 09-NOV-14:50 | -1.3 | -3.7 |
December | 0.222222E+10 | 13308.69 | 12-DEC-14:25 | -2.2 | -5.4 | 0.509519E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.867657E+11 | 0.700842E+10 | ||||||||
Minimum of Months | 0.181035E+10 | 13308.69 | -2.2 | -5.4 | 0.504871E+09 | 845.64 | -6.3 | -9.2 | ||
Maximum of Months | 0.140563E+11 | 33749.45 | 34.15 | 15.94 | 0.698319E+09 | 1139.03 | 33.90 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178112E+09 | 2646.91 | 13-JAN-15:40 | 9.27 | 4.85 | 0.305446E+09 | 531.39 | 13-JAN-14:00 | 9.27 | 4.85 |
February | 0.798937E+09 | 8720.40 | 28-FEB-16:40 | 10.37 | 4.49 | 0.294132E+09 | 544.93 | 27-FEB-14:20 | 10.37 | 4.49 |
March | 0.174684E+10 | 11737.23 | 28-MAR-17:00 | 10.60 | 2.97 | 0.366363E+09 | 544.94 | 29-MAR-13:20 | 12.40 | 4.30 |
April | 0.328424E+10 | 27914.25 | 22-APR-17:41 | 16.10 | 8.34 | 0.351288E+09 | 544.95 | 13-APR-13:20 | 16.10 | 8.34 |
May | 0.552445E+10 | 33108.80 | 28-MAY-18:01 | 19.82 | 10.31 | 0.397544E+09 | 551.93 | 19-MAY-15:00 | 19.82 | 10.31 |
June | 0.834481E+10 | 31485.46 | 18-JUN-17:41 | 25.10 | 14.47 | 0.421794E+09 | 606.50 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.100967E+11 | 34097.37 | 02-JUL-17:41 | 25.60 | 14.12 | 0.399033E+09 | 642.63 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.893992E+10 | 29208.03 | 06-AUG-16:01 | 35.50 | 16.24 | 0.443311E+09 | 632.35 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.516525E+10 | 28602.52 | 24-SEP-16:41 | 24.40 | 13.66 | 0.374117E+09 | 572.79 | 01-SEP-15:00 | 24.40 | 13.66 |
October | 0.247230E+10 | 20401.45 | 15-OCT-16:02 | 22.02 | 10.75 | 0.363831E+09 | 544.95 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.101584E+10 | 6740.89 | 03-NOV-15:40 | 14.40 | 7.69 | 0.332499E+09 | 544.94 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.343277E+09 | 3986.48 | 06-DEC-15:40 | 9.97 | 4.80 | 0.302449E+09 | 544.92 | 06-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.479107E+11 | 0.435181E+10 | ||||||||
Minimum of Months | 0.178112E+09 | 2646.91 | 9.27 | 2.97 | 0.294132E+09 | 531.39 | 9.27 | 4.30 | ||
Maximum of Months | 0.100967E+11 | 34097.37 | 35.50 | 16.24 | 0.443311E+09 | 642.63 | 33.90 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426399E+09 | 11798.91 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.701344E+09 | 6275.59 | 10-FEB-06:01 | -19.9 | -20.2 | 0.00 | 0.00 | 01-FEB-00:10 | -19.9 | -20.2 |
March | 0.191725E+10 | 6060.51 | 04-MAR-06:01 | -20.1 | -20.7 | 0.00 | 0.00 | 01-MAR-00:10 | -20.1 | -20.7 |
April | 0.379695E+10 | 6336.69 | 24-APR-15:10 | 17.98 | 9.61 | 0.00 | 0.00 | 01-APR-00:10 | 17.98 | 9.61 |
May | 0.382630E+10 | 10027.73 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.736491E+10 | 10334.54 | 26-JUN-10:40 | 25.20 | 13.71 | 0.00 | 0.00 | 01-JUN-00:10 | 25.20 | 13.71 |
July | 0.974793E+10 | 14730.37 | 17-JUL-05:15 | 16.83 | 12.38 | 0.00 | 0.00 | 01-JUL-00:10 | 16.83 | 12.38 |
August | 0.953762E+10 | 13905.82 | 07-AUG-05:15 | 17.77 | 10.09 | 0.00 | 0.00 | 01-AUG-00:10 | 17.77 | 10.09 |
September | 0.536666E+10 | 11606.10 | 05-SEP-11:30 | 21.65 | 13.62 | 0.00 | 0.00 | 01-SEP-00:10 | 21.65 | 13.62 |
October | 0.368892E+10 | 6233.21 | 16-OCT-16:00 | 19.40 | 8.07 | 0.00 | 0.00 | 01-OCT-00:10 | 19.40 | 8.07 |
November | 0.192783E+10 | 4825.21 | 06-NOV-06:15 | -3.4 | -4.3 | 0.00 | 0.00 | 01-NOV-00:10 | -3.4 | -4.3 |
December | 0.688661E+09 | 6326.36 | 29-DEC-05:01 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.489908E+11 | 0.00 | ||||||||
Minimum of Months | 0.426399E+09 | 4825.21 | -25.0 | -25.3 | 0.00 | 0.00 | -25.0 | -25.3 | ||
Maximum of Months | 0.974793E+10 | 14730.37 | 25.20 | 13.71 | 0.00 | 0.00 | 25.20 | 13.71 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212181E+09 | 13573.30 | 26-JAN-04:01 | -21.8 | -22.3 | 0.00 | 0.00 | 01-JAN-00:10 | -21.8 | -22.3 |
February | 0.160046E+09 | 12930.68 | 04-FEB-04:01 | -21.9 | -22.2 | 0.00 | 0.00 | 01-FEB-00:10 | -21.9 | -22.2 |
March | 0.402332E+09 | 12065.65 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.107343E+10 | 7050.23 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.196050E+10 | 7144.42 | 08-MAY-04:02 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.490943E+10 | 8250.51 | 22-JUN-10:20 | 26.13 | 16.61 | 0.00 | 0.00 | 01-JUN-00:10 | 26.13 | 16.61 |
July | 0.642963E+10 | 10650.35 | 25-JUL-16:56 | 33.90 | 15.42 | 0.00 | 0.00 | 01-JUL-00:10 | 33.90 | 15.42 |
August | 0.618585E+10 | 8227.85 | 10-AUG-15:50 | 32.07 | 13.71 | 0.00 | 0.00 | 01-AUG-00:10 | 32.07 | 13.71 |
September | 0.335867E+10 | 7992.94 | 05-SEP-10:20 | 18.50 | 12.51 | 0.00 | 0.00 | 01-SEP-00:10 | 18.50 | 12.51 |
October | 0.131313E+10 | 7133.97 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.424274E+09 | 13909.70 | 27-NOV-04:11 | -15.7 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.7 | -16.7 |
December | 0.130021E+09 | 11785.39 | 30-DEC-04:01 | -20.1 | -20.6 | 0.00 | 0.00 | 01-DEC-00:10 | -20.1 | -20.6 |
Annual Sum or Average | 0.265595E+11 | 0.00 | ||||||||
Minimum of Months | 0.130021E+09 | 7050.23 | -21.9 | -22.3 | 0.00 | 0.00 | -21.9 | -22.3 | ||
Maximum of Months | 0.642963E+10 | 13909.70 | 33.90 | 16.61 | 0.00 | 0.00 | 33.90 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 144646.00 | 189.92 | 15-JAN-14:10 | 5.60 | -0.5 | 0.00 | 0.00 | 01-JAN-00:10 | 5.60 | -0.5 |
February | 63757830.04 | 2855.15 | 26-FEB-14:24 | 16.15 | 6.12 | 0.00 | 0.00 | 01-FEB-00:10 | 16.15 | 6.12 |
March | 0.456225E+09 | 4796.05 | 23-MAR-14:00 | 10.00 | 2.51 | 0.00 | 0.00 | 01-MAR-00:10 | 10.00 | 2.51 |
April | 0.196344E+10 | 11512.50 | 25-APR-15:20 | 17.27 | 7.54 | 0.00 | 0.00 | 01-APR-00:10 | 17.27 | 7.54 |
May | 0.445285E+10 | 17800.72 | 19-MAY-14:40 | 27.93 | 14.94 | 0.00 | 0.00 | 01-MAY-00:10 | 27.93 | 14.94 |
June | 0.930070E+10 | 20643.57 | 21-JUN-12:40 | 26.33 | 17.53 | 0.00 | 0.00 | 01-JUN-00:10 | 26.33 | 17.53 |
July | 0.122987E+11 | 24364.57 | 25-JUL-17:04 | 33.80 | 15.36 | 0.00 | 0.00 | 01-JUL-00:10 | 33.80 | 15.36 |
August | 0.105172E+11 | 22270.05 | 10-AUG-12:55 | 32.20 | 13.79 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 13.79 |
September | 0.472535E+10 | 15213.71 | 01-SEP-16:17 | 28.13 | 13.81 | 0.00 | 0.00 | 01-SEP-00:10 | 28.13 | 13.81 |
October | 0.107144E+10 | 8910.42 | 18-OCT-15:30 | 24.70 | 11.32 | 0.00 | 0.00 | 01-OCT-00:10 | 24.70 | 11.32 |
November | 36449864.00 | 1913.72 | 03-NOV-14:50 | 14.67 | 7.71 | 0.00 | 0.00 | 01-NOV-00:10 | 14.67 | 7.71 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.448862E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.122987E+11 | 24364.57 | 33.80 | 17.53 | 0.00 | 0.00 | 33.80 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235158E+10 | 2117.35 | 19-JAN-16:50 | -6.4 | -8.0 | 95215962.29 | 126.82 | 03-JAN-14:09 | -6.4 | -8.0 |
February | 0.751041E+10 | 4603.42 | 26-FEB-17:24 | 13.35 | 5.05 | 86396431.05 | 126.82 | 08-FEB-14:09 | 13.35 | 5.05 |
March | 0.139511E+11 | 6901.01 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 03-MAR-10:09 | 2.50 | 0.99 |
April | 0.188171E+11 | 8437.95 | 22-APR-18:15 | 15.17 | 8.10 | 91605283.04 | 126.82 | 24-APR-09:00 | 14.40 | 8.99 |
May | 0.431891E+10 | 3488.78 | 31-MAY-24:00 | 15.50 | 10.27 | 99234975.61 | 126.84 | 30-MAY-09:50 | 15.50 | 10.27 |
June | 0.941063E+10 | 5390.51 | 30-JUN-24:00 | 19.60 | 12.23 | 98962690.32 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.150271E+11 | 7349.52 | 31-JUL-24:00 | 19.20 | 11.32 | 91884002.80 | 126.84 | 07-JUL-09:09 | 19.20 | 11.32 |
August | 0.199143E+11 | 8360.27 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103322E+09 | 127.18 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.431249E+10 | 3340.85 | 30-SEP-24:00 | 11.80 | 6.26 | 91610400.10 | 126.85 | 06-SEP-13:00 | 11.80 | 6.26 |
October | 0.927672E+10 | 5034.81 | 31-OCT-24:00 | 4.70 | 1.47 | 95230914.37 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.135686E+11 | 6177.52 | 13-NOV-16:30 | 3.15 | -2.5 | 94300334.64 | 126.83 | 08-NOV-14:00 | 3.15 | -2.5 |
December | 0.186365E+11 | 7900.85 | 06-DEC-16:10 | 8.95 | 4.16 | 91880763.04 | 126.82 | 15-DEC-14:09 | -10.6 | -10.9 |
Annual Sum or Average | 0.137095E+12 | 0.114288E+10 | ||||||||
Minimum of Months | 0.235158E+10 | 2117.35 | -6.4 | -8.0 | 86396431.05 | 126.82 | -10.6 | -10.9 | ||
Maximum of Months | 0.199143E+11 | 8437.95 | 24.60 | 12.54 | 0.103322E+09 | 127.18 | 32.20 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542882E+09 | 1795.36 | 19-JAN-16:50 | -6.4 | -8.0 | 93312082.64 | 126.82 | 03-JAN-14:09 | -6.4 | -8.0 |
February | 0.528676E+10 | 4084.69 | 28-FEB-17:00 | 10.00 | 4.31 | 86396453.56 | 126.82 | 08-FEB-14:09 | 10.00 | 4.31 |
March | 0.117785E+11 | 6106.40 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 03-MAR-10:09 | 9.18 | 2.32 |
April | 0.171221E+11 | 7936.63 | 25-APR-18:10 | 16.73 | 7.64 | 91605309.64 | 126.82 | 24-APR-09:00 | 16.73 | 7.64 |
May | 0.351418E+10 | 3302.91 | 31-MAY-24:00 | 15.50 | 10.27 | 99234906.51 | 126.84 | 30-MAY-09:50 | 15.50 | 10.27 |
June | 0.868271E+10 | 5244.13 | 30-JUN-24:00 | 19.60 | 12.23 | 98962495.32 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.141018E+11 | 7051.50 | 31-JUL-24:00 | 19.20 | 11.32 | 91884199.74 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.187922E+11 | 8034.61 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103254E+09 | 126.83 | 22-AUG-09:50 | 17.62 | 12.68 |
September | 0.362010E+10 | 3029.37 | 30-SEP-23:30 | 12.50 | 6.83 | 91609737.41 | 126.84 | 11-SEP-13:00 | 12.50 | 6.83 |
October | 0.785400E+10 | 4305.53 | 15-OCT-17:03 | 20.45 | 10.12 | 95230885.83 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.113077E+11 | 5642.06 | 03-NOV-16:00 | 14.30 | 7.69 | 94300363.17 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.152087E+11 | 7305.30 | 06-DEC-16:10 | 8.95 | 4.16 | 91880809.48 | 126.82 | 15-DEC-14:09 | -10.6 | -10.9 |
Annual Sum or Average | 0.117812E+12 | 0.114091E+10 | ||||||||
Minimum of Months | 0.542882E+09 | 1795.36 | -6.4 | -8.0 | 86396453.56 | 126.82 | -10.6 | -10.9 | ||
Maximum of Months | 0.187922E+11 | 8034.61 | 24.60 | 12.54 | 0.103254E+09 | 126.85 | 19.60 | 12.68 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187394E+09 | 1512.11 | 13-JAN-16:40 | 8.17 | 4.18 | 87568698.97 | 127.74 | 17-JAN-14:39 | -2.6 | -4.1 |
February | 0.361964E+10 | 4001.44 | 28-FEB-17:00 | 10.00 | 4.31 | 86391899.18 | 126.82 | 08-FEB-14:09 | 10.00 | 4.31 |
March | 0.999888E+10 | 6058.13 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 03-MAR-10:09 | 9.18 | 2.32 |
April | 0.159472E+11 | 7984.85 | 25-APR-18:10 | 16.73 | 7.64 | 91605342.09 | 126.83 | 24-APR-09:00 | 16.73 | 7.64 |
May | 0.289244E+10 | 3215.94 | 31-MAY-23:40 | 15.70 | 10.35 | 99011153.38 | 126.84 | 30-MAY-09:50 | 15.70 | 10.35 |
June | 0.847730E+10 | 5244.18 | 30-JUN-24:00 | 19.60 | 12.23 | 98962596.58 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.140508E+11 | 7039.61 | 31-JUL-24:00 | 19.20 | 11.32 | 91884270.04 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.186471E+11 | 8096.98 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103261E+09 | 126.83 | 22-AUG-09:50 | 17.62 | 12.68 |
September | 0.308025E+10 | 3066.63 | 04-SEP-17:54 | 31.70 | 16.34 | 91608745.29 | 126.84 | 11-SEP-13:00 | 9.40 | 9.40 |
October | 0.644735E+10 | 4169.94 | 18-OCT-17:00 | 21.70 | 10.27 | 95230867.69 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.926229E+10 | 5557.27 | 03-NOV-16:00 | 14.30 | 7.69 | 94300374.88 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.128565E+11 | 7181.25 | 06-DEC-16:20 | 8.50 | 3.80 | 91880824.34 | 126.82 | 15-DEC-14:09 | -10.6 | -10.9 |
Annual Sum or Average | 0.105467E+12 | 0.113494E+10 | ||||||||
Minimum of Months | 0.187394E+09 | 1512.11 | 8.17 | 2.32 | 86391899.18 | 126.82 | -10.6 | -10.9 | ||
Maximum of Months | 0.186471E+11 | 8096.98 | 31.70 | 16.34 | 0.103261E+09 | 127.74 | 19.60 | 12.68 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235001E+12 | 91953.23 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206151E+10 | 2745.43 | 03-JAN-10:00 | 2.20 | -2.7 |
February | 0.433941E+12 | 183303.97 | 27-FEB-17:00 | 12.20 | 5.32 | 0.187030E+10 | 2745.66 | 24-FEB-10:20 | 12.20 | 5.32 |
March | 0.727362E+12 | 357803.27 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223479E+10 | 2745.54 | 16-MAR-09:09 | 2.50 | 0.99 |
April | 0.941602E+12 | 366920.08 | 25-APR-16:00 | 17.80 | 7.70 | 0.198308E+10 | 2747.20 | 24-APR-13:09 | 17.80 | 7.70 |
May | 0.239996E+12 | 176094.95 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214818E+10 | 2746.90 | 19-MAY-13:09 | 15.50 | 10.27 |
June | 0.470145E+12 | 268065.28 | 30-JUN-23:55 | 19.60 | 12.23 | 0.214249E+10 | 2750.96 | 26-JUN-09:00 | 19.60 | 12.23 |
July | 0.733738E+12 | 360737.06 | 31-JUL-23:55 | 19.20 | 11.32 | 0.199010E+10 | 2752.83 | 06-JUL-09:00 | 19.20 | 11.32 |
August | 0.978756E+12 | 370021.99 | 07-AUG-16:00 | 32.20 | 16.16 | 0.223624E+10 | 2753.98 | 22-AUG-09:50 | 17.62 | 12.68 |
September | 0.235281E+12 | 175885.10 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198306E+10 | 2746.65 | 05-SEP-13:39 | 11.80 | 6.26 |
October | 0.486631E+12 | 267716.34 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206152E+10 | 2745.52 | 31-OCT-09:30 | 4.70 | 1.47 |
November | 0.706934E+12 | 276096.60 | 06-NOV-17:00 | 6.70 | 2.26 | 0.204136E+10 | 2745.56 | 03-NOV-13:39 | 6.70 | 2.26 |
December | 0.973851E+12 | 367232.78 | 06-DEC-17:00 | 6.70 | 2.38 | 0.198896E+10 | 2745.58 | 11-DEC-10:39 | 0.93 | -2.6 |
Annual Sum or Average | 0.716324E+13 | 0.247416E+11 | ||||||||
Minimum of Months | 0.235001E+12 | 91953.23 | 2.20 | -1.7 | 0.187030E+10 | 2745.43 | 0.93 | -2.7 | ||
Maximum of Months | 0.978756E+12 | 370021.99 | 32.20 | 16.16 | 0.223624E+10 | 2753.98 | 19.60 | 12.68 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320447E+09 | 47685.00 | 09-JAN-05:01 | -27.2 |
February | 93873151.15 | 46238.52 | 06-FEB-05:01 | -0.4 |
March | 10165448.72 | 43528.22 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 879447.91 | 5862.99 | 27-NOV-06:03 | -14.5 |
December | 5630873.56 | 42270.59 | 26-DEC-06:01 | -7.9 |
Annual Sum or Average | 0.430996E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.320447E+09 | 47685.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897808E+10 | 75433.64 | 09-JAN-04:11 | -27.2 |
February | 0.295457E+10 | 73288.03 | 06-FEB-04:01 | -0.6 |
March | 0.154888E+10 | 73351.23 | 06-MAR-04:01 | -18.4 |
April | 19300227.34 | 58209.25 | 29-APR-05:01 | -7.7 |
May | 0.356143E+09 | 64078.86 | 01-MAY-04:01 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.210113E+09 | 64665.60 | 10-OCT-04:01 | -5.2 |
November | 0.201225E+10 | 73182.18 | 27-NOV-04:11 | -15.7 |
December | 0.463926E+10 | 72938.71 | 26-DEC-04:01 | -6.3 |
Annual Sum or Average | 0.207186E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.897808E+10 | 75433.64 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157841E+10 | 13101.56 | 09-JAN-04:01 | -27.2 |
February | 0.361657E+09 | 11763.37 | 04-FEB-05:01 | -20.4 |
March | 59023571.49 | 11571.14 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 16111947.23 | 10761.19 | 27-NOV-06:03 | -14.5 |
December | 0.252941E+09 | 11608.81 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.226814E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.157841E+10 | 13101.56 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100746E+10 | 15289.59 | 09-JAN-04:01 | -27.2 |
February | 0.279559E+09 | 13364.55 | 04-FEB-05:01 | -20.4 |
March | 51539383.32 | 13172.43 | 06-MAR-05:01 | -18.4 |
April | 101158.45 | 1180.18 | 29-APR-05:01 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 23555235.36 | 10776.45 | 28-NOV-06:01 | -5.1 |
December | 0.282245E+09 | 13383.09 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.164446E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.100746E+10 | 15289.59 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158753E+10 | 22123.97 | 09-JAN-04:01 | -27.2 |
February | 0.366962E+09 | 19995.00 | 04-FEB-05:01 | -20.4 |
March | 0.110429E+09 | 20262.18 | 06-MAR-05:01 | -18.4 |
April | 1002705.61 | 7571.14 | 29-APR-05:01 | -7.7 |
May | 5722290.46 | 11705.51 | 08-MAY-05:02 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 1575069.92 | 13661.14 | 10-OCT-05:01 | -6.1 |
November | 71256023.17 | 19732.02 | 27-NOV-05:01 | -15.4 |
December | 0.411280E+09 | 20030.72 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.255576E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.158753E+10 | 22123.97 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483275E+09 | 12747.06 | 09-JAN-05:01 | -27.2 |
February | 21049904.36 | 10254.62 | 01-FEB-06:01 | -25.0 |
March | 605509.03 | 9342.42 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 941810.50 | 6517.38 | 30-DEC-06:01 | -20.5 |
Annual Sum or Average | 0.505872E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.483275E+09 | 12747.06 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.658436E+10 | 13525.13 | 29-JAN-06:51 | -30.0 |
February | 0.287803E+10 | 13016.06 | 05-FEB-19:22 | -18.1 |
March | 0.107246E+10 | 12891.22 | 06-MAR-03:51 | -18.3 |
April | 64201156.17 | 10735.39 | 29-APR-04:01 | -7.8 |
May | 74409027.96 | 10927.42 | 08-MAY-04:02 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 3851455.18 | 5624.70 | 19-SEP-05:03 | 2.20 |
October | 84724916.21 | 10923.92 | 10-OCT-04:01 | -5.2 |
November | 0.103199E+10 | 12889.28 | 27-NOV-04:11 | -15.7 |
December | 0.354169E+10 | 13111.72 | 31-DEC-21:21 | -24.1 |
Annual Sum or Average | 0.153357E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.658436E+10 | 13525.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370910E+10 | 20158.42 | 29-JAN-06:51 | -30.0 |
February | 0.147723E+10 | 19186.36 | 06-FEB-04:01 | -0.6 |
March | 0.528321E+09 | 18874.68 | 06-MAR-04:01 | -18.4 |
April | 31589689.23 | 13532.31 | 29-APR-05:01 | -7.7 |
May | 46350789.47 | 15024.81 | 01-MAY-05:01 | -0.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 968296.75 | 2445.13 | 19-SEP-05:03 | 2.20 |
October | 43605098.56 | 15949.24 | 10-OCT-04:01 | -5.2 |
November | 0.586603E+09 | 19282.05 | 27-NOV-04:11 | -15.7 |
December | 0.198539E+10 | 19050.83 | 30-DEC-04:01 | -20.1 |
Annual Sum or Average | 0.840915E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.370910E+10 | 20158.42 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394321E+10 | 24414.07 | 09-JAN-04:01 | -27.2 |
February | 0.131794E+10 | 23228.51 | 06-FEB-04:01 | -0.6 |
March | 0.540004E+09 | 23226.46 | 06-MAR-04:01 | -18.4 |
April | 51750361.94 | 18779.64 | 29-APR-05:01 | -7.7 |
May | 75172611.76 | 19090.37 | 08-MAY-04:02 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 122274.36 | 815.16 | 19-SEP-05:03 | 2.20 |
October | 36739851.41 | 18953.50 | 10-OCT-05:01 | -6.1 |
November | 0.535855E+09 | 23348.24 | 27-NOV-04:11 | -15.7 |
December | 0.195665E+10 | 24016.22 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.845744E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.394321E+10 | 24414.07 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341537E+10 | 20237.89 | 29-JAN-06:51 | -30.0 |
February | 0.114588E+10 | 19256.35 | 06-FEB-04:01 | -0.6 |
March | 0.397463E+09 | 19163.24 | 06-MAR-04:01 | -18.4 |
April | 14186146.52 | 13133.42 | 29-APR-05:01 | -7.7 |
May | 27327587.28 | 12627.08 | 09-MAY-05:01 | -2.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 113826.12 | 758.84 | 19-SEP-05:03 | 2.20 |
October | 23689133.25 | 15137.65 | 10-OCT-05:01 | -6.1 |
November | 0.406973E+09 | 19394.87 | 27-NOV-04:11 | -15.7 |
December | 0.156126E+10 | 19159.37 | 30-DEC-04:01 | -20.1 |
Annual Sum or Average | 0.699226E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.341537E+10 | 20237.89 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127913E+11 | 16936.06 | 09-JAN-04:11 | -27.2 |
February | 0.632762E+10 | 15940.50 | 05-FEB-09:22 | -20.0 |
March | 0.373424E+10 | 16257.27 | 06-MAR-02:42 | -18.2 |
April | 0.845616E+09 | 13650.95 | 29-APR-03:02 | -6.9 |
May | 0.580469E+09 | 14810.26 | 01-MAY-03:01 | -0.7 |
June | 7107702.40 | 11981.29 | 17-JUN-05:02 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 3532880.94 | 11847.73 | 18-AUG-05:02 | 7.30 |
September | 0.178168E+09 | 13039.43 | 19-SEP-04:12 | 2.20 |
October | 0.890029E+09 | 15031.01 | 10-OCT-03:01 | -4.1 |
November | 0.406719E+10 | 15955.86 | 26-NOV-22:12 | -14.3 |
December | 0.921203E+10 | 16318.18 | 31-DEC-16:52 | -21.7 |
Annual Sum or Average | 0.386373E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.127913E+11 | 16936.06 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761592E+10 | 23032.50 | 09-JAN-04:11 | -27.2 |
February | 0.341730E+10 | 21327.17 | 05-FEB-04:02 | -20.0 |
March | 0.196127E+10 | 21799.44 | 06-MAR-02:42 | -18.2 |
April | 0.401079E+09 | 18445.81 | 28-APR-04:01 | -6.7 |
May | 0.316320E+09 | 19964.90 | 01-MAY-03:01 | -0.7 |
June | 4271869.36 | 10482.88 | 17-JUN-05:02 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 2202987.31 | 9978.51 | 18-AUG-05:02 | 7.30 |
September | 81652067.83 | 17370.19 | 19-SEP-04:12 | 2.20 |
October | 0.421691E+09 | 20315.28 | 10-OCT-03:01 | -4.1 |
November | 0.221903E+10 | 21444.76 | 27-NOV-04:11 | -15.7 |
December | 0.535671E+10 | 21844.71 | 31-DEC-02:52 | -24.4 |
Annual Sum or Average | 0.217975E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.761592E+10 | 23032.50 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.862236E+10 | 28438.09 | 09-JAN-04:11 | -27.2 |
February | 0.357901E+10 | 26463.90 | 05-FEB-04:02 | -20.0 |
March | 0.243663E+10 | 26931.03 | 06-MAR-02:42 | -18.2 |
April | 0.654046E+09 | 22818.47 | 28-APR-04:01 | -6.7 |
May | 0.569955E+09 | 24563.47 | 08-MAY-03:01 | -2.7 |
June | 16514461.72 | 20272.35 | 17-JUN-05:02 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 5858507.71 | 14353.75 | 18-AUG-05:02 | 7.30 |
September | 0.102151E+09 | 21437.79 | 19-SEP-04:12 | 2.20 |
October | 0.459820E+09 | 24967.44 | 10-OCT-03:01 | -4.1 |
November | 0.229018E+10 | 26497.24 | 27-NOV-04:11 | -15.7 |
December | 0.573316E+10 | 27034.75 | 31-DEC-02:52 | -24.4 |
Annual Sum or Average | 0.244697E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.862236E+10 | 28438.09 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696374E+10 | 25517.86 | 09-JAN-04:11 | -27.2 |
February | 0.272903E+10 | 23203.50 | 06-FEB-04:01 | -0.6 |
March | 0.154862E+10 | 23739.67 | 06-MAR-02:42 | -18.2 |
April | 0.266844E+09 | 19922.47 | 29-APR-04:01 | -7.8 |
May | 0.240238E+09 | 21766.39 | 08-MAY-03:01 | -2.7 |
June | 4542488.09 | 9481.87 | 17-JUN-05:02 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 1224245.84 | 4931.86 | 18-AUG-05:02 | 7.30 |
September | 50535245.08 | 13866.57 | 19-SEP-04:12 | 2.20 |
October | 0.283940E+09 | 21690.71 | 10-OCT-03:01 | -4.1 |
November | 0.157791E+10 | 23644.40 | 27-NOV-04:11 | -15.7 |
December | 0.407906E+10 | 23887.82 | 31-DEC-02:52 | -24.4 |
Annual Sum or Average | 0.177457E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.696374E+10 | 25517.86 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191150E+10 | 9448.77 | 24-JAN-06:03 | 8.22 |
February | 0.900781E+09 | 12649.95 | 26-FEB-15:22 | 16.40 |
March | 0.330845E+09 | 10940.96 | 12-MAR-15:52 | 6.10 |
April | 0.208098E+09 | 13913.05 | 16-APR-15:21 | 19.70 |
May | 80480118.38 | 9459.07 | 28-MAY-16:31 | 20.73 |
June | 0.114886E+09 | 10611.84 | 18-JUN-15:51 | 25.00 |
July | 0.151381E+09 | 12994.97 | 30-JUL-16:11 | 30.77 |
August | 0.123750E+09 | 14271.78 | 06-AUG-15:41 | 35.40 |
September | 0.109041E+09 | 12328.10 | 03-SEP-15:41 | 34.03 |
October | 0.124250E+09 | 13419.81 | 15-OCT-14:41 | 22.88 |
November | 0.271922E+09 | 11064.95 | 24-NOV-05:11 | 12.20 |
December | 0.492946E+09 | 11698.49 | 19-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.481988E+10 | |||
Minimum of Months | 80480118.38 | 9448.77 | 3.50 | |
Maximum of Months | 0.191150E+10 | 14271.78 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398168E+10 | 13328.29 | 01-JAN-13:22 | 8.05 |
February | 0.249250E+10 | 12801.49 | 26-FEB-15:42 | 16.20 |
March | 0.131697E+10 | 10583.93 | 26-MAR-13:12 | 9.27 |
April | 0.212649E+09 | 15327.19 | 16-APR-16:01 | 20.00 |
May | 0.304827E+09 | 11174.18 | 14-MAY-15:01 | 16.60 |
June | 86826280.51 | 14255.07 | 18-JUN-16:51 | 25.60 |
July | 0.116059E+09 | 14035.99 | 16-JUL-16:11 | 32.97 |
August | 69249413.61 | 15300.49 | 06-AUG-15:51 | 35.60 |
September | 0.106923E+09 | 13874.07 | 03-SEP-15:51 | 34.40 |
October | 0.277112E+09 | 15393.79 | 15-OCT-14:31 | 22.97 |
November | 0.114462E+10 | 10311.02 | 12-NOV-13:02 | -1.4 |
December | 0.238822E+10 | 7760.08 | 17-DEC-12:53 | -1.7 |
Annual Sum or Average | 0.124976E+11 | |||
Minimum of Months | 69249413.61 | 7760.08 | -1.7 | |
Maximum of Months | 0.398168E+10 | 15393.79 | 35.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155374E+11 | 34122.56 | 11-JAN-05:31 | -31.5 |
February | 0.795303E+10 | 29213.10 | 04-FEB-05:22 | -20.0 |
March | 0.564659E+10 | 30185.08 | 06-MAR-05:32 | -16.7 |
April | 0.230924E+10 | 12951.12 | 29-APR-05:01 | -7.7 |
May | 0.165504E+10 | 18777.26 | 08-MAY-05:02 | -2.8 |
June | 0.484612E+09 | 13588.11 | 05-JUN-05:03 | 10.97 |
July | 0.228016E+09 | 13817.86 | 12-JUL-05:03 | 6.85 |
August | 0.397304E+09 | 13867.88 | 03-AUG-05:03 | 8.12 |
September | 0.108071E+10 | 14098.54 | 28-SEP-05:03 | 8.90 |
October | 0.247222E+10 | 20470.99 | 10-OCT-05:13 | -6.1 |
November | 0.605079E+10 | 29713.90 | 27-NOV-05:13 | -15.3 |
December | 0.114493E+11 | 31898.51 | 29-DEC-05:22 | -25.0 |
Annual Sum or Average | 0.552642E+11 | |||
Minimum of Months | 0.228016E+09 | 12951.12 | -31.5 | |
Maximum of Months | 0.155374E+11 | 34122.56 | 10.97 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16969011.86 | 528.18 | 30-JAN-02:06 | -25.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 16969011.86 | |||
Minimum of Months | 0.00 | 0.00 | -25.3 | |
Maximum of Months | 16969011.86 | 528.18 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453750E+09 | 653.26 | 29-JAN-19:15 | -25.8 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.453750E+09 | |||
Minimum of Months | 0.00 | 0.00 | -25.8 | |
Maximum of Months | 0.453750E+09 | 653.26 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.889594E+09 | 726.66 | 29-JAN-17:55 | -22.2 |
February | 62447058.55 | 636.41 | 05-FEB-20:30 | -18.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2328331.57 | 657.30 | 30-APR-23:40 | -1.2 |
May | 99586285.99 | 654.22 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 13147951.39 | 484.33 | 17-SEP-09:58 | 9.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.106710E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.889594E+09 | 726.66 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105926E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.851541E+09 | 1397.22 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.949735E+09 | 1574.96 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.809143E+09 | 1178.13 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.844938E+09 | 921.98 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.824186E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785660E+09 | 884.50 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.881207E+09 | 905.15 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.829835E+09 | 1201.79 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.915651E+09 | 1662.56 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.996200E+09 | 1662.56 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.103096E+10 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.107783E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785660E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.105926E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.663378E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.541147E+09 | 839.73 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.607129E+09 | 1014.53 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.519732E+09 | 718.65 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.545595E+09 | 583.12 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.535008E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.507483E+09 | 553.38 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.569576E+09 | 560.96 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.532012E+09 | 596.81 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.579974E+09 | 1071.42 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.629283E+09 | 1071.42 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.646381E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.687670E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.507483E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.663378E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101273E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.827933E+09 | 1202.71 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.940655E+09 | 1575.00 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.810257E+09 | 1175.35 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.848757E+09 | 923.60 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.829670E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.789081E+09 | 887.06 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.885910E+09 | 906.92 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.826913E+09 | 1164.91 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.894692E+09 | 1662.60 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.954198E+09 | 1662.60 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.979721E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.106005E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.789081E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.101273E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669855E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.540572E+09 | 919.32 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.609971E+09 | 1014.53 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.522976E+09 | 777.82 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.545344E+09 | 599.23 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.531187E+09 | 547.46 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507416E+09 | 577.72 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.568759E+09 | 592.65 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.534095E+09 | 844.28 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.585574E+09 | 1071.42 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.625471E+09 | 1071.42 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.647094E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.688831E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507416E+09 | 547.46 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.669855E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105652E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.849608E+09 | 1393.03 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.948506E+09 | 1574.08 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.808311E+09 | 1172.87 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.844522E+09 | 916.25 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.823966E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785426E+09 | 876.60 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.880902E+09 | 898.49 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.828926E+09 | 1195.59 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.913655E+09 | 1662.56 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.993118E+09 | 1662.56 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.102785E+10 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.107613E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785426E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.105652E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.662334E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.540460E+09 | 836.59 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.606739E+09 | 1013.06 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.519339E+09 | 710.94 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.545218E+09 | 579.25 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.534692E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.507285E+09 | 547.96 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.569308E+09 | 556.27 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.531610E+09 | 593.77 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.579302E+09 | 1071.42 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.628416E+09 | 1071.42 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.645201E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.686990E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.507285E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.662334E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101182E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.827140E+09 | 1191.76 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.940006E+09 | 1574.12 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.809458E+09 | 1170.06 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.848235E+09 | 917.95 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.829157E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.788640E+09 | 879.29 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.885300E+09 | 900.34 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.826381E+09 | 1158.37 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.893490E+09 | 1662.60 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.953768E+09 | 1662.60 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.979244E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105926E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.788640E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.101182E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668432E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.539869E+09 | 915.85 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.609122E+09 | 1013.06 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.522349E+09 | 770.17 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.544899E+09 | 595.93 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.531003E+09 | 541.26 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507185E+09 | 573.22 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.568468E+09 | 588.99 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.533638E+09 | 838.15 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.584754E+09 | 1071.42 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.624492E+09 | 1071.42 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.646402E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.688061E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507185E+09 | 541.26 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.668432E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105637E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.849558E+09 | 1392.90 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.948455E+09 | 1573.89 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.808284E+09 | 1171.86 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.844507E+09 | 916.02 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.823960E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.785408E+09 | 876.29 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.880865E+09 | 898.22 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.828844E+09 | 1194.77 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.913611E+09 | 1662.56 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.993060E+09 | 1662.56 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.102774E+10 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.107607E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.785408E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.105637E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.662299E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.540437E+09 | 836.53 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.606720E+09 | 1012.94 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.519324E+09 | 710.24 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.545199E+09 | 579.07 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.534673E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.507262E+09 | 547.71 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.569276E+09 | 556.05 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.531590E+09 | 593.63 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.579327E+09 | 1071.42 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.628564E+09 | 1071.42 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.645122E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.686979E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.507262E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.662299E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101178E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.827096E+09 | 1191.22 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.939976E+09 | 1573.93 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.809433E+09 | 1169.04 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.848199E+09 | 917.72 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.829135E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.788629E+09 | 878.98 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.885278E+09 | 900.08 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.826359E+09 | 1157.49 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.893471E+09 | 1662.60 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.953723E+09 | 1662.60 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.979220E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105923E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.788629E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.101178E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668387E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.539850E+09 | 915.63 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.609099E+09 | 1012.94 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.522313E+09 | 769.55 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.544883E+09 | 595.80 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.530999E+09 | 541.02 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.507178E+09 | 573.04 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.568460E+09 | 588.84 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.533622E+09 | 837.72 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.584734E+09 | 1071.42 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.624470E+09 | 1071.42 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.646369E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.688036E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.507178E+09 | 541.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.668387E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.105926E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707303E+09 |
February | 0.136985E+10 | 0.851541E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568485E+09 |
March | 0.163685E+10 | 0.949735E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515282E+09 |
April | 0.145243E+10 | 0.809143E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375030E+09 |
May | 0.157338E+10 | 0.844938E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 814446.55 | 0.367466E+09 |
June | 0.156900E+10 | 0.824186E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4040079.80 | 0.182250E+09 |
July | 0.145680E+10 | 0.785660E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12363320.04 | 0.121975E+09 |
August | 0.163685E+10 | 0.881207E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11335958.66 | 0.132188E+09 |
September | 0.145243E+10 | 0.829835E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7229924.96 | 0.241342E+09 |
October | 0.150991E+10 | 0.915651E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48725.27 | 0.366130E+09 |
November | 0.149516E+10 | 0.996200E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516663E+09 |
December | 0.145680E+10 | 0.103096E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657711E+09 |
Annual Sum or Average | 0.181194E+11 | 0.107783E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35832455.28 | 0.475183E+10 |
Minimum of Months | 0.136985E+10 | 0.785660E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121975E+09 |
Maximum of Months | 0.163685E+10 | 0.105926E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12363320.04 | 0.707303E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.663378E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473743E+09 |
February | 0.882782E+09 | 0.541147E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383006E+09 |
March | 0.105485E+10 | 0.607129E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343481E+09 |
April | 0.936002E+09 | 0.519732E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249562E+09 |
May | 0.101394E+10 | 0.545595E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540374.89 | 0.244682E+09 |
June | 0.101113E+10 | 0.535008E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2695480.25 | 0.121833E+09 |
July | 0.938820E+09 | 0.507483E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8493152.89 | 81766373.11 |
August | 0.105485E+10 | 0.569576E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7598809.38 | 87366298.06 |
September | 0.936002E+09 | 0.532012E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4611076.59 | 0.163089E+09 |
October | 0.973041E+09 | 0.579974E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32478.29 | 0.246485E+09 |
November | 0.963541E+09 | 0.629283E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341631E+09 |
December | 0.938820E+09 | 0.646381E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433644E+09 |
Annual Sum or Average | 0.116768E+11 | 0.687670E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23971372.30 | 0.317029E+10 |
Minimum of Months | 0.882782E+09 | 0.507483E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81766373.11 |
Maximum of Months | 0.105485E+10 | 0.663378E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8493152.89 | 0.473743E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.101273E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713134E+09 |
February | 0.136988E+10 | 0.827933E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585098E+09 |
March | 0.163688E+10 | 0.940655E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520607E+09 |
April | 0.145246E+10 | 0.810257E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376935E+09 |
May | 0.157341E+10 | 0.848757E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 796162.77 | 0.365774E+09 |
June | 0.156904E+10 | 0.829670E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3995882.03 | 0.182419E+09 |
July | 0.145684E+10 | 0.789081E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12075196.36 | 0.123519E+09 |
August | 0.163688E+10 | 0.885910E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10542074.53 | 0.135111E+09 |
September | 0.145246E+10 | 0.826913E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6203069.78 | 0.247787E+09 |
October | 0.150994E+10 | 0.894692E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22805.50 | 0.377254E+09 |
November | 0.149520E+10 | 0.954198E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521821E+09 |
December | 0.145684E+10 | 0.979721E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662130E+09 |
Annual Sum or Average | 0.181198E+11 | 0.106005E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33635190.97 | 0.481159E+10 |
Minimum of Months | 0.136988E+10 | 0.789081E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123519E+09 |
Maximum of Months | 0.163688E+10 | 0.101273E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12075196.36 | 0.713134E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.669855E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488863E+09 |
February | 0.882782E+09 | 0.540572E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409637E+09 |
March | 0.105485E+10 | 0.609971E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371111E+09 |
April | 0.936002E+09 | 0.522976E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278793E+09 |
May | 0.101394E+10 | 0.545344E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 506347.22 | 0.262689E+09 |
June | 0.101113E+10 | 0.531187E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2661846.56 | 0.133851E+09 |
July | 0.938820E+09 | 0.507416E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7930705.92 | 93974198.16 |
August | 0.105485E+10 | 0.568759E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7308380.38 | 0.101047E+09 |
September | 0.936002E+09 | 0.534095E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4368856.54 | 0.173837E+09 |
October | 0.973041E+09 | 0.585574E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32463.04 | 0.267177E+09 |
November | 0.963541E+09 | 0.625471E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376597E+09 |
December | 0.938820E+09 | 0.647094E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481573E+09 |
Annual Sum or Average | 0.116768E+11 | 0.688831E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22808599.65 | 0.343915E+10 |
Minimum of Months | 0.882782E+09 | 0.507416E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93974198.16 |
Maximum of Months | 0.105485E+10 | 0.669855E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7930705.92 | 0.488863E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.105652E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150855E+10 |
February | 0.136985E+10 | 0.849608E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117732E+10 |
March | 0.163685E+10 | 0.948506E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109285E+10 |
April | 0.145243E+10 | 0.808311E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792794E+09 |
May | 0.157338E+10 | 0.844522E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1841961.91 | 0.806460E+09 |
June | 0.156900E+10 | 0.823966E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9367031.15 | 0.408770E+09 |
July | 0.145680E+10 | 0.785426E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31392251.98 | 0.275780E+09 |
August | 0.163685E+10 | 0.880902E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27425151.96 | 0.298526E+09 |
September | 0.145243E+10 | 0.828926E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17155552.47 | 0.528752E+09 |
October | 0.150991E+10 | 0.913655E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192453.78 | 0.759664E+09 |
November | 0.149516E+10 | 0.993118E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106407E+10 |
December | 0.145680E+10 | 0.102785E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133387E+10 |
Annual Sum or Average | 0.181194E+11 | 0.107613E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87374403.26 | 0.100474E+11 |
Minimum of Months | 0.136985E+10 | 0.785426E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275780E+09 |
Maximum of Months | 0.163685E+10 | 0.105652E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31392251.98 | 0.150855E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.662334E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101902E+10 |
February | 0.649041E+09 | 0.540460E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817838E+09 |
March | 0.773965E+09 | 0.606739E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756913E+09 |
April | 0.688021E+09 | 0.519339E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555786E+09 |
May | 0.744847E+09 | 0.545218E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1157755.75 | 0.548796E+09 |
June | 0.742030E+09 | 0.534692E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5975573.22 | 0.282748E+09 |
July | 0.690839E+09 | 0.507285E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19171719.58 | 0.194390E+09 |
August | 0.773965E+09 | 0.569308E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17312485.69 | 0.208516E+09 |
September | 0.688021E+09 | 0.531610E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10299967.07 | 0.370625E+09 |
October | 0.715730E+09 | 0.579302E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49132.41 | 0.538255E+09 |
November | 0.708685E+09 | 0.628416E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729643E+09 |
December | 0.690839E+09 | 0.645201E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904791E+09 |
Annual Sum or Average | 0.858171E+10 | 0.686990E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53966633.71 | 0.692732E+10 |
Minimum of Months | 0.649041E+09 | 0.507285E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194390E+09 |
Maximum of Months | 0.773965E+09 | 0.662334E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19171719.58 | 0.101902E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.101182E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160408E+10 |
February | 0.136988E+10 | 0.827140E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131308E+10 |
March | 0.163688E+10 | 0.940006E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117445E+10 |
April | 0.145246E+10 | 0.809458E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847684E+09 |
May | 0.157341E+10 | 0.848235E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1769906.08 | 0.829915E+09 |
June | 0.156904E+10 | 0.829157E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9158870.84 | 0.417578E+09 |
July | 0.145684E+10 | 0.788640E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28392823.68 | 0.287563E+09 |
August | 0.163688E+10 | 0.885300E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25183269.00 | 0.315238E+09 |
September | 0.145246E+10 | 0.826381E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13984323.47 | 0.568281E+09 |
October | 0.150994E+10 | 0.893490E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14084.93 | 0.854805E+09 |
November | 0.149520E+10 | 0.953768E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116390E+10 |
December | 0.145684E+10 | 0.979244E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145507E+10 |
Annual Sum or Average | 0.181198E+11 | 0.105926E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78503278.01 | 0.108316E+11 |
Minimum of Months | 0.136988E+10 | 0.788640E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287563E+09 |
Maximum of Months | 0.163688E+10 | 0.101182E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28392823.68 | 0.160408E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.668432E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103151E+10 |
February | 0.882782E+09 | 0.539869E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832394E+09 |
March | 0.105485E+10 | 0.609122E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767967E+09 |
April | 0.936002E+09 | 0.522349E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573479E+09 |
May | 0.101394E+10 | 0.544899E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1135379.58 | 0.573992E+09 |
June | 0.101113E+10 | 0.531003E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6090153.05 | 0.292439E+09 |
July | 0.938820E+09 | 0.507185E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18962401.50 | 0.206561E+09 |
August | 0.105485E+10 | 0.568468E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17408981.56 | 0.216885E+09 |
September | 0.936002E+09 | 0.533638E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10135735.89 | 0.377990E+09 |
October | 0.973041E+09 | 0.584754E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65003.84 | 0.545928E+09 |
November | 0.963541E+09 | 0.624492E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745225E+09 |
December | 0.938820E+09 | 0.646402E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925541E+09 |
Annual Sum or Average | 0.116768E+11 | 0.688061E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53797655.43 | 0.708991E+10 |
Minimum of Months | 0.882782E+09 | 0.507185E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206561E+09 |
Maximum of Months | 0.105485E+10 | 0.668432E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18962401.50 | 0.103151E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.105637E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179693E+10 |
February | 0.136985E+10 | 0.849558E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135330E+10 |
March | 0.163685E+10 | 0.948455E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127267E+10 |
April | 0.145243E+10 | 0.808284E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907697E+09 |
May | 0.157338E+10 | 0.844507E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2133310.21 | 0.948853E+09 |
June | 0.156900E+10 | 0.823960E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11179479.19 | 0.497772E+09 |
July | 0.145680E+10 | 0.785408E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37197455.01 | 0.338307E+09 |
August | 0.163685E+10 | 0.880865E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33042300.71 | 0.361366E+09 |
September | 0.145243E+10 | 0.828844E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20263711.45 | 0.618070E+09 |
October | 0.150991E+10 | 0.913611E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1190479.49 | 0.842687E+09 |
November | 0.149516E+10 | 0.993060E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121063E+10 |
December | 0.145680E+10 | 0.102774E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156851E+10 |
Annual Sum or Average | 0.181194E+11 | 0.107607E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105007E+09 | 0.117168E+11 |
Minimum of Months | 0.136985E+10 | 0.785408E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338307E+09 |
Maximum of Months | 0.163685E+10 | 0.105637E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37197455.01 | 0.179693E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.662299E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121203E+10 |
February | 0.882782E+09 | 0.540437E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938802E+09 |
March | 0.105485E+10 | 0.606720E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882448E+09 |
April | 0.936002E+09 | 0.519324E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642639E+09 |
May | 0.101394E+10 | 0.545199E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1390507.21 | 0.648949E+09 |
June | 0.101113E+10 | 0.534673E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7386815.96 | 0.345104E+09 |
July | 0.938820E+09 | 0.507262E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23270415.08 | 0.239231E+09 |
August | 0.105485E+10 | 0.569276E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21324101.17 | 0.253396E+09 |
September | 0.936002E+09 | 0.531590E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12444429.19 | 0.437940E+09 |
October | 0.973041E+09 | 0.579327E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67023.56 | 0.604679E+09 |
November | 0.963541E+09 | 0.628564E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825818E+09 |
December | 0.938820E+09 | 0.645122E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105558E+10 |
Annual Sum or Average | 0.116768E+11 | 0.686979E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65883292.17 | 0.808661E+10 |
Minimum of Months | 0.882782E+09 | 0.507262E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239231E+09 |
Maximum of Months | 0.105485E+10 | 0.662299E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23270415.08 | 0.121203E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.101178E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188825E+10 |
February | 0.136988E+10 | 0.827096E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152479E+10 |
March | 0.163688E+10 | 0.939976E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137902E+10 |
April | 0.145246E+10 | 0.809433E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986269E+09 |
May | 0.157341E+10 | 0.848199E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2031705.22 | 0.982059E+09 |
June | 0.156904E+10 | 0.829135E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10951597.75 | 0.508902E+09 |
July | 0.145684E+10 | 0.788629E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33939097.21 | 0.353214E+09 |
August | 0.163688E+10 | 0.885278E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30491144.57 | 0.383653E+09 |
September | 0.145246E+10 | 0.826359E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16940046.56 | 0.673961E+09 |
October | 0.150994E+10 | 0.893471E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34133.01 | 0.978021E+09 |
November | 0.149520E+10 | 0.953723E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132727E+10 |
December | 0.145684E+10 | 0.979220E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167304E+10 |
Annual Sum or Average | 0.181198E+11 | 0.105923E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94387724.32 | 0.126584E+11 |
Minimum of Months | 0.136988E+10 | 0.788629E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353214E+09 |
Maximum of Months | 0.163688E+10 | 0.101178E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33939097.21 | 0.188825E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.668387E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122496E+10 |
February | 0.882782E+09 | 0.539850E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970953E+09 |
March | 0.105485E+10 | 0.609099E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904318E+09 |
April | 0.936002E+09 | 0.522313E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671490E+09 |
May | 0.101394E+10 | 0.544883E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1295792.85 | 0.683242E+09 |
June | 0.101113E+10 | 0.530999E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7308655.80 | 0.357216E+09 |
July | 0.938820E+09 | 0.507178E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22785629.33 | 0.253665E+09 |
August | 0.105485E+10 | 0.568460E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21083873.67 | 0.264411E+09 |
September | 0.936002E+09 | 0.533622E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12151156.83 | 0.448590E+09 |
October | 0.973041E+09 | 0.584734E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67041.60 | 0.624074E+09 |
November | 0.963541E+09 | 0.624470E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857574E+09 |
December | 0.938820E+09 | 0.646369E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108149E+10 |
Annual Sum or Average | 0.116768E+11 | 0.688036E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64692150.09 | 0.834198E+10 |
Minimum of Months | 0.882782E+09 | 0.507178E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253665E+09 |
Maximum of Months | 0.105485E+10 | 0.668387E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22785629.33 | 0.122496E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151798E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122122E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109318E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791075E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277535.90 | 0.769786E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6616912.65 | 0.380521E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23771294.03 | 0.259130E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20971575.15 | 0.284221E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13876791.63 | 0.515756E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16043.26 | 0.780227E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110707E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141160E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66530152.63 | 0.101318E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259130E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23771294.03 | 0.151798E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254580E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204331E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187728E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136302E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2310209.14 | 0.134854E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12052658.42 | 0.669250E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46540039.14 | 0.449866E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39693445.33 | 0.498036E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26229839.92 | 0.909095E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24068.67 | 0.133999E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187423E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233973E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126850E+09 | 0.172581E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449866E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46540039.14 | 0.254580E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264082E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208744E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196932E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143878E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1486471.31 | 0.147510E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10272484.46 | 0.766851E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38532858.38 | 0.519381E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36786164.83 | 0.560141E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21571922.41 | 0.979594E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135807E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186502E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234004E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108650E+09 | 0.180006E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519381E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38532858.38 | 0.264082E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1131.37 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1397.22 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 730.49 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1574.96 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 882.17 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1178.13 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 628.15 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 921.98 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 20-MAY-17:03 | 1212.60 | 22-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.46 | 29-JUN-15:00 | 504.01 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 884.50 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.08 | 30-JUL-14:16 | 302.59 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 905.15 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.17 | 06-AUG-17:45 | 386.68 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1201.79 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.31 | 03-SEP-12:51 | 676.73 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1662.56 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 18-OCT-14:00 | 581.00 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 690.11 | 28-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1093.41 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.59 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 160.31 | 1212.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 754.01 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 839.73 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 480.28 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1014.53 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 581.83 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 718.65 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 411.94 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 583.12 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 | 20-MAY-17:03 | 801.96 | 22-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 29-JUN-15:00 | 328.78 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 553.38 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.49 | 30-JUL-14:54 | 197.32 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 560.96 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 | 06-AUG-17:44 | 250.01 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 596.81 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.04 | 03-SEP-13:03 | 446.52 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 18-OCT-14:00 | 384.03 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 456.97 | 26-NOV-20:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 707.22 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.32 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 107.04 | 801.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1130.65 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1202.71 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 748.89 | 19-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 1575.00 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 898.64 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1175.35 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 622.96 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 923.60 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 19-MAY-16:00 | 1185.34 | 22-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.46 | 29-JUN-15:00 | 496.76 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 887.06 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.09 | 30-JUL-14:16 | 299.37 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 906.92 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.23 | 06-AUG-17:44 | 385.95 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1164.91 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.47 | 03-SEP-13:08 | 663.58 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1662.60 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 18-OCT-15:00 | 611.75 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 688.44 | 26-NOV-13:50 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1056.39 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.37 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 149.47 | 1185.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 755.29 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 919.32 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 522.79 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1014.53 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 631.90 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 777.82 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 458.97 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 599.23 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 19-MAY-16:00 | 829.36 | 22-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 547.46 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 29-JUN-15:00 | 366.32 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 577.72 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.02 | 30-JUL-14:14 | 227.16 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 592.65 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.44 | 06-AUG-17:44 | 299.95 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 844.28 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.51 | 03-SEP-13:03 | 469.74 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 18-OCT-14:00 | 424.25 | 08-OCT-15:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 498.02 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 803.78 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 547.46 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.16 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 106.51 | 829.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2648.84 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1393.03 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1495.10 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1574.08 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1929.06 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1172.87 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1359.97 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 916.25 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.79 | 20-MAY-17:03 | 2587.84 | 22-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 | 29-JUN-15:00 | 1097.53 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 876.60 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.52 | 30-JUL-11:53 | 654.41 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 898.49 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.42 | 06-AUG-17:55 | 809.83 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1195.59 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.25 | 03-SEP-12:51 | 1446.72 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1662.56 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 15-OCT-14:00 | 1229.17 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1588.06 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2269.42 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.41 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 389.25 | 2648.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1765.67 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 836.59 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1003.46 | 17-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 1013.06 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1296.72 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 710.94 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 915.46 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 579.25 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 | 20-MAY-17:03 | 1720.87 | 22-MAY-03:55 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 | 29-JUN-15:00 | 728.00 | 14-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 547.96 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.47 | 30-JUL-14:44 | 440.04 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 556.27 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.62 | 06-AUG-17:54 | 545.96 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 593.77 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.04 | 03-SEP-12:52 | 964.95 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1071.42 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 18-OCT-14:40 | 836.10 | 30-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1058.69 | 28-NOV-05:45 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1535.48 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.04 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 243.04 | 1765.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2650.14 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1191.76 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1755.31 | 19-FEB-12:30 |
March | 2010.83 | 01-MAR-10:09 | 1574.12 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2029.47 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1170.06 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1379.87 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 917.95 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.48 | 19-MAY-16:00 | 2601.99 | 22-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 | 29-JUN-15:00 | 1096.71 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 879.29 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.09 | 30-JUL-14:04 | 665.83 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 900.34 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.81 | 06-AUG-17:54 | 834.42 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1158.37 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.56 | 03-SEP-12:55 | 1455.18 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1662.60 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 18-OCT-15:40 | 1424.51 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1588.07 | 28-NOV-05:45 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2292.08 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.83 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 364.56 | 2650.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1766.09 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 915.85 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1031.83 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1013.06 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1345.45 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 770.17 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 933.14 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 595.93 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.64 | 19-MAY-16:00 | 1728.85 | 22-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 541.26 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 | 29-JUN-15:00 | 751.88 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 573.22 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.12 | 30-JUL-12:06 | 472.28 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 588.99 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.91 | 06-AUG-17:54 | 565.78 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 838.15 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.44 | 03-SEP-12:51 | 969.55 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 18-OCT-14:00 | 862.08 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1058.69 | 28-NOV-05:45 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1516.78 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 541.26 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.28 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 243.44 | 1766.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3284.18 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1392.90 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1808.90 | 08-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 1573.89 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2286.67 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1171.86 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1586.44 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 916.02 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.58 | 20-MAY-17:03 | 3196.32 | 22-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1290.93 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 876.29 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.16 | 30-JUL-11:53 | 767.38 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 898.22 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.91 | 06-AUG-17:24 | 951.11 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1194.77 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.83 | 03-SEP-12:51 | 1637.96 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1662.56 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.98 | 15-OCT-13:51 | 1439.42 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1979.84 | 28-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2833.98 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.38 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 458.83 | 3284.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2189.41 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 836.53 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1205.61 | 17-FEB-05:45 |
March | 1295.83 | 01-MAR-10:09 | 1012.94 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1535.72 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 710.24 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1071.34 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 579.07 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.11 | 19-MAY-16:00 | 2163.98 | 22-MAY-04:45 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 871.26 | 04-JUN-13:55 |
July | 1295.83 | 03-JUL-09:09 | 547.71 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.13 | 30-JUL-14:25 | 516.86 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 556.05 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.09 | 06-AUG-17:24 | 646.28 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 593.63 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.78 | 03-SEP-12:51 | 1092.34 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 18-OCT-14:00 | 964.06 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1326.96 | 28-NOV-05:52 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1893.27 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.86 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 296.78 | 2189.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3285.78 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1191.22 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1985.37 | 19-FEB-12:58 |
March | 2010.83 | 01-MAR-10:09 | 1573.93 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2412.81 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1169.04 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1616.40 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 917.72 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.87 | 19-MAY-16:00 | 3203.52 | 22-MAY-04:45 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1289.36 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 878.98 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.58 | 30-JUL-11:53 | 782.67 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 900.08 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.15 | 06-AUG-17:23 | 991.58 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1157.49 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.03 | 03-SEP-12:58 | 1649.40 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1662.60 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 | 18-OCT-15:20 | 1553.58 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1990.45 | 28-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2834.08 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.67 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 445.03 | 3285.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2190.09 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 915.63 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1210.04 | 17-FEB-05:23 |
March | 1295.83 | 01-MAR-10:09 | 1012.94 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1603.34 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 769.55 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1099.61 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 595.80 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 | 19-MAY-16:10 | 2172.17 | 22-MAY-04:03 |
June | 1295.83 | 01-JUN-09:09 | 541.02 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 888.80 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 573.04 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.80 | 30-JUL-11:53 | 561.06 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 588.84 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.25 | 06-AUG-17:44 | 677.09 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 837.72 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.95 | 03-SEP-12:51 | 1107.85 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 18-OCT-14:00 | 1000.15 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1326.93 | 28-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1892.87 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 541.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.06 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 296.95 | 2190.09 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2362.60 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1595.39 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1877.05 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1334.63 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.45 | 20-MAY-17:03 | 2676.39 | 22-MAY-03:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.47 | 29-JUN-15:00 | 1063.38 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.60 | 30-JUL-12:00 | 625.88 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.24 | 06-AUG-18:00 | 815.26 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.95 | 03-SEP-12:51 | 1460.05 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 | 18-OCT-15:00 | 1238.68 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1506.64 | 28-NOV-05:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2380.52 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.95 | 2676.39 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4159.69 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2730.71 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3308.30 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2348.29 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.53 | 20-MAY-17:03 | 4707.11 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.25 | 29-JUN-15:00 | 1871.02 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.56 | 30-JUL-11:53 | 1091.76 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.38 | 06-AUG-17:41 | 1414.77 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.06 | 03-SEP-13:00 | 2571.89 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 18-OCT-15:00 | 2142.12 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2551.21 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3916.39 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.06 | 4707.11 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4622.86 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2633.69 | 17-FEB-04:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3607.49 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2490.94 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.81 | 20-MAY-17:03 | 4803.46 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 29-JUN-15:00 | 1968.89 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.40 | 30-JUL-12:00 | 1170.07 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.09 | 06-AUG-17:50 | 1480.20 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.27 | 03-SEP-13:00 | 2610.22 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2232.68 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2614.32 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3853.05 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.27 | 4803.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 108902.81 | 02-JAN-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 100737.77 | 21-FEB-07:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92635.89 | 20-MAR-06:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97262.47 | 24-APR-06:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99743.18 | 15-MAY-06:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98297.24 | 05-JUN-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 113102.21 | 21-JUL-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 109163.24 | 12-AUG-06:11 | 17952.25 | 16382.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 101484.38 | 11-SEP-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 103072.01 | 23-OCT-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99982.64 | 13-NOV-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96635.40 | 26-DEC-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92635.89 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113102.21 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 87944.59 | 02-JAN-04:01 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81978.65 | 27-FEB-05:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81030.10 | 20-MAR-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85496.78 | 10-APR-04:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89649.61 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90678.88 | 22-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92828.44 | 21-JUL-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88615.07 | 07-AUG-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88064.62 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84761.66 | 10-OCT-03:01 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82771.03 | 06-NOV-04:03 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82032.97 | 11-DEC-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81030.10 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92828.44 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19421.30 | 04-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54192.68 | 28-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67625.60 | 30-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73658.26 | 26-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75239.94 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75986.24 | 23-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77149.40 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76590.75 | 14-AUG-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81475.70 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73523.65 | 20-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68329.85 | 04-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27175.94 | 07-DEC-16:20 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19421.30 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81475.70 | 15316.26 | 13241.18 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13848.92 | 13-JAN-16:50 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22918.24 | 28-FEB-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27021.79 | 29-MAR-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45463.18 | 07-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70813.26 | 30-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74858.65 | 22-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74140.35 | 27-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82418.25 | 07-AUG-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83800.45 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43280.34 | 19-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24583.54 | 03-NOV-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16847.23 | 06-DEC-16:30 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13848.92 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83800.45 | 15316.26 | 13241.18 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2459.85 | 02-JAN-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.39 |
February | 4322.98 | 27-FEB-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
March | 5062.43 | 27-MAR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 |
April | 7234.21 | 07-APR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
May | 12862.40 | 30-MAY-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.56 |
June | 15484.33 | 25-JUN-18:11 | 0.00 | 351.55 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.86 |
July | 15712.41 | 30-JUL-16:51 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 58.89 | 0.00 |
August | 16341.67 | 06-AUG-15:42 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 115.11 | 0.00 |
September | 15453.70 | 03-SEP-13:41 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 106.02 | 0.00 |
October | 5902.38 | 19-OCT-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 |
November | 4249.96 | 24-NOV-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.09 |
December | 2911.17 | 06-DEC-13:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2459.85 | 0.00 | 351.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16341.67 | 2010.79 | 791.05 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 115.11 | 165.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3960.67 | 17-JAN-10:10 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.11 |
February | 9954.85 | 26-FEB-10:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.91 |
March | 11628.11 | 28-MAR-09:05 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.30 |
April | 20610.25 | 16-APR-08:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.80 |
May | 14026.93 | 19-MAY-08:30 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 |
June | 26260.07 | 25-JUN-08:11 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 |
July | 24525.50 | 02-JUL-08:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 |
August | 27585.68 | 06-AUG-08:21 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
September | 24062.74 | 03-SEP-09:41 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 |
October | 12596.91 | 15-OCT-09:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.19 |
November | 7542.61 | 06-NOV-09:25 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 |
December | 3789.58 | 20-DEC-10:05 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3789.58 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | |
Maximum of Months | 27585.68 | 2591.66 | 1019.56 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27449.37 | 01-JAN-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.60 |
February | 29696.09 | 26-FEB-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.05 |
March | 27747.46 | 26-MAR-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.92 |
April | 28445.60 | 23-APR-11:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.60 |
May | 25948.60 | 14-MAY-11:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.67 |
June | 27768.57 | 11-JUN-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 |
July | 28242.66 | 16-JUL-13:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 | 0.00 |
August | 31621.13 | 06-AUG-13:41 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 | 0.00 |
September | 32874.86 | 03-SEP-13:01 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 0.00 |
October | 30329.94 | 15-OCT-13:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.71 |
November | 29148.60 | 12-NOV-11:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.84 |
December | 24905.00 | 17-DEC-13:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24905.00 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32874.86 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 646.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6443.80 | 13-JAN-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 |
February | 21113.48 | 26-FEB-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.32 |
March | 19908.11 | 12-MAR-15:52 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.43 |
April | 30753.82 | 16-APR-16:41 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.97 |
May | 33457.86 | 28-MAY-17:11 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.54 |
June | 30077.60 | 25-JUN-18:11 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 |
July | 32891.19 | 30-JUL-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 | 0.00 |
August | 34814.70 | 06-AUG-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 | 0.00 |
September | 29727.83 | 24-SEP-16:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
October | 27826.74 | 15-OCT-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.12 |
November | 12225.80 | 17-NOV-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.86 |
December | 9851.76 | 06-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6443.80 | 0.00 | 141.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34814.70 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 | 426.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1285.01 | 15-JAN-13:12 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.42 |
February | 2226.79 | 27-FEB-14:20 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 |
March | 2605.97 | 29-MAR-15:50 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.88 |
April | 5618.64 | 07-APR-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 |
May | 7334.51 | 19-MAY-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 80.48 | 0.00 |
June | 11419.29 | 23-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.04 |
July | 14745.18 | 16-JUL-18:52 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 103.51 | 0.00 |
August | 14159.55 | 06-AUG-15:51 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 265.04 | 0.00 |
September | 13752.31 | 03-SEP-15:51 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 280.19 | 0.00 |
October | 4556.23 | 19-OCT-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.24 |
November | 2207.44 | 03-NOV-14:10 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.50 |
December | 1486.55 | 06-DEC-16:00 | 1923.11 | 1157.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1285.01 | 0.00 | 219.72 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14745.18 | 3846.22 | 1582.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 280.19 | 532.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1133.94 | 20-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.27 |
February | 7151.91 | 27-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.92 |
March | 11535.84 | 23-MAR-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.07 |
April | 18823.23 | 16-APR-09:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.42 |
May | 14939.28 | 19-MAY-08:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 |
June | 26603.60 | 18-JUN-09:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.59 |
July | 30122.45 | 02-JUL-08:51 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.62 |
August | 30170.44 | 06-AUG-08:31 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.58 |
September | 26039.24 | 03-SEP-09:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 |
October | 13522.84 | 15-OCT-11:11 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.75 |
November | 7239.62 | 03-NOV-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.44 |
December | 2136.43 | 07-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1133.94 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 30170.44 | 2478.65 | 1019.56 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27665.85 | 15-JAN-13:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.66 |
February | 31386.47 | 26-FEB-13:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.07 |
March | 28885.03 | 26-MAR-13:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.56 |
April | 28454.69 | 16-APR-14:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.75 |
May | 28676.74 | 14-MAY-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.67 |
June | 28387.23 | 18-JUN-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 |
July | 29158.59 | 16-JUL-10:51 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 |
August | 30265.71 | 06-AUG-11:11 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 91.21 | 0.00 |
September | 34085.46 | 03-SEP-13:12 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 194.43 | 0.00 |
October | 35493.70 | 15-OCT-13:11 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.51 |
November | 31323.91 | 11-NOV-13:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.39 |
December | 16802.19 | 10-DEC-13:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1506.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16802.19 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35493.70 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 194.43 | 1506.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3096.43 | 13-JAN-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.19 |
February | 13467.96 | 26-FEB-16:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.90 |
March | 12208.18 | 28-MAR-17:00 | 391.37 | 283.21 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.40 |
April | 27684.37 | 16-APR-17:21 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.18 |
May | 29252.34 | 14-MAY-17:01 | 0.00 | 254.87 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.63 |
June | 31099.84 | 18-JUN-17:31 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.26 |
July | 31342.34 | 02-JUL-18:11 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.81 |
August | 30593.26 | 06-AUG-16:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 101.50 | 0.00 |
September | 27860.45 | 03-SEP-15:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.43 | 0.00 |
October | 26318.65 | 15-OCT-16:31 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.77 |
November | 7617.85 | 03-NOV-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.11 |
December | 4836.83 | 06-DEC-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3096.43 | 0.00 | 141.60 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31342.34 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 129.43 | 789.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1225.36 | 13-JAN-16:20 | 1923.11 | 1408.49 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.23 |
February | 2031.45 | 27-FEB-13:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 |
March | 2194.30 | 23-MAR-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.43 |
April | 5458.10 | 07-APR-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 |
May | 8063.26 | 19-MAY-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 96.33 | 0.00 |
June | 16757.00 | 25-JUN-18:41 | 0.00 | 351.55 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.81 |
July | 17556.34 | 02-JUL-18:22 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 |
August | 16566.89 | 06-AUG-16:01 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 341.48 | 0.00 |
September | 16450.37 | 03-SEP-16:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 373.48 | 0.00 |
October | 4069.48 | 19-OCT-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.14 |
November | 2002.35 | 03-NOV-13:30 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.73 |
December | 1373.45 | 06-DEC-16:00 | 1923.11 | 1157.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1225.36 | 0.00 | 307.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17556.34 | 4021.58 | 1582.09 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 373.48 | 331.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 959.93 | 31-JAN-10:50 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.06 |
February | 3995.82 | 28-FEB-10:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.23 |
March | 8396.30 | 23-MAR-10:10 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.72 |
April | 16524.18 | 16-APR-09:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.61 |
May | 14478.88 | 19-MAY-09:05 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 |
June | 27738.35 | 25-JUN-09:21 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.10 |
July | 29709.72 | 02-JUL-08:21 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.05 |
August | 26959.47 | 06-AUG-09:21 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
September | 24524.15 | 04-SEP-09:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 |
October | 8624.75 | 18-OCT-09:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.20 |
November | 3608.79 | 03-NOV-09:50 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.30 |
December | 1009.17 | 20-DEC-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 959.93 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | |
Maximum of Months | 29709.72 | 2591.66 | 1019.56 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16166.71 | 15-JAN-13:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.78 |
February | 32315.77 | 26-FEB-14:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.59 |
March | 23731.56 | 01-MAR-14:00 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.84 |
April | 28257.01 | 16-APR-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.41 |
May | 30348.50 | 14-MAY-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 989.06 |
June | 30281.47 | 18-JUN-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.06 |
July | 31427.61 | 02-JUL-15:01 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.54 |
August | 31791.47 | 06-AUG-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 240.55 | 0.00 |
September | 33749.45 | 03-SEP-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 260.56 | 0.00 |
October | 33105.54 | 15-OCT-14:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.96 |
November | 30326.14 | 11-NOV-13:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 909.16 |
December | 13308.69 | 12-DEC-14:25 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13308.69 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33749.45 | 4021.67 | 1582.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 260.56 | 989.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2646.91 | 13-JAN-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.85 |
February | 8720.40 | 28-FEB-16:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 |
March | 11737.23 | 28-MAR-17:00 | 391.37 | 283.21 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.76 |
April | 27914.25 | 22-APR-17:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.70 |
May | 33108.80 | 28-MAY-18:01 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.00 |
June | 31485.46 | 18-JUN-17:41 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.61 |
July | 34097.37 | 02-JUL-17:41 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.57 |
August | 29208.03 | 06-AUG-16:01 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 180.32 | 0.00 |
September | 28602.52 | 24-SEP-16:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 |
October | 20401.45 | 15-OCT-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.65 |
November | 6740.89 | 03-NOV-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.00 |
December | 3986.48 | 06-DEC-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2646.91 | 0.00 | 169.91 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34097.37 | 1239.33 | 509.78 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 180.32 | 505.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11798.91 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1187.02 |
February | 6275.59 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.87 |
March | 6060.51 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.74 |
April | 6336.69 | 24-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 |
May | 10027.73 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.24 |
June | 10334.54 | 26-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 0.00 |
July | 14730.37 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
August | 13905.82 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.84 |
September | 11606.10 | 05-SEP-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
October | 6233.21 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 |
November | 4825.21 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.67 |
December | 6326.36 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4825.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14730.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 1187.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13573.30 | 26-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2063.61 |
February | 12930.68 | 04-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.72 |
March | 12065.65 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.03 |
April | 7050.23 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.93 |
May | 7144.42 | 08-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1979.25 |
June | 8250.51 | 22-JUN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 | 0.00 |
July | 10650.35 | 25-JUL-16:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.87 | 0.00 |
August | 8227.85 | 10-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 0.00 |
September | 7992.94 | 05-SEP-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.15 |
October | 7133.97 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1255.75 |
November | 13909.70 | 27-NOV-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2354.80 |
December | 11785.39 | 30-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7050.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13909.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.87 | 2354.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 189.92 | 15-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.99 |
February | 2855.15 | 26-FEB-14:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.08 |
March | 4796.05 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.11 |
April | 11512.50 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.15 |
May | 17800.72 | 19-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
June | 20643.57 | 21-JUN-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
July | 24364.57 | 25-JUL-17:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 | 0.00 |
August | 22270.05 | 10-AUG-12:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 | 0.00 |
September | 15213.71 | 01-SEP-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.46 | 0.00 |
October | 8910.42 | 18-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
November | 1913.72 | 03-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.43 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2382.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24364.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 | 2382.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2117.35 | 19-JAN-16:50 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4603.42 | 26-FEB-17:24 | 58.46 | 87.96 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6901.01 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8437.95 | 22-APR-18:15 | 0.00 | 140.73 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3488.78 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5390.51 | 30-JUN-24:00 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7349.52 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8360.27 | 03-AUG-18:50 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3340.85 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5034.81 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6177.52 | 13-NOV-16:30 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7900.85 | 06-DEC-16:10 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2117.35 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8437.95 | 222.14 | 316.63 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1795.36 | 19-JAN-16:50 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4084.69 | 28-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6106.40 | 28-MAR-17:50 | 23.38 | 105.54 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7936.63 | 25-APR-18:10 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3302.91 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5244.13 | 30-JUN-24:00 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7051.50 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8034.61 | 03-AUG-18:50 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3029.37 | 30-SEP-23:30 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4305.53 | 15-OCT-17:03 | 0.00 | 105.55 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5642.06 | 03-NOV-16:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7305.30 | 06-DEC-16:10 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1795.36 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8034.61 | 222.14 | 316.63 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1512.11 | 13-JAN-16:40 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4001.44 | 28-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6058.13 | 28-MAR-17:50 | 23.38 | 105.54 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7984.85 | 25-APR-18:10 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3215.94 | 31-MAY-23:40 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5244.18 | 30-JUN-24:00 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7039.61 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8096.98 | 03-AUG-18:50 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3066.63 | 04-SEP-17:54 | 0.00 | 158.32 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4169.94 | 18-OCT-17:00 | 70.15 | 175.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5557.27 | 03-NOV-16:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7181.25 | 06-DEC-16:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1512.11 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8096.98 | 222.14 | 316.63 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91953.23 | 02-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183303.97 | 27-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357803.27 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366920.08 | 25-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176094.95 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268065.28 | 30-JUN-23:55 | 0.00 | 461.88 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360737.06 | 31-JUL-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370021.99 | 07-AUG-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175885.10 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267716.34 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276096.60 | 06-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367232.78 | 06-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91953.23 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370021.99 | 4808.68 | 4157.19 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.165291E+13 | 1185801.10 | 02-JAN-16:40 | 0.105880E+13 | 2405335.49 | 09-JAN-07:10 |
February | 0.188888E+13 | 1430361.74 | 27-FEB-15:00 | 0.568856E+12 | 1643704.29 | 01-FEB-07:10 |
March | 0.248056E+13 | 1512764.19 | 28-MAR-15:00 | 0.368198E+12 | 1598496.75 | 06-MAR-07:10 |
April | 0.271280E+13 | 1918543.88 | 06-APR-15:00 | 0.124787E+12 | 583921.03 | 29-APR-06:10 |
May | 0.175754E+13 | 1580174.00 | 19-MAY-15:20 | 0.765914E+11 | 556799.27 | 08-MAY-06:19 |
June | 0.221728E+13 | 1828173.54 | 22-JUN-10:09 | 0.500507E+10 | 253239.14 | 16-JUN-06:00 |
July | 0.275960E+13 | 1955035.36 | 17-JUL-15:00 | 21897387.08 | 4050.79 | 05-JUL-06:19 |
August | 0.322323E+13 | 2132523.49 | 08-AUG-15:00 | 0.134909E+10 | 442970.91 | 17-AUG-13:20 |
September | 0.173031E+13 | 1755764.62 | 07-SEP-15:09 | 0.246004E+11 | 380189.54 | 11-SEP-09:20 |
October | 0.213583E+13 | 1606738.36 | 18-OCT-15:00 | 0.906192E+11 | 664469.70 | 10-OCT-06:30 |
November | 0.237321E+13 | 1538661.51 | 17-NOV-16:00 | 0.279457E+12 | 1310219.39 | 27-NOV-07:19 |
December | 0.273932E+13 | 1586331.77 | 07-DEC-16:30 | 0.682806E+12 | 1807328.16 | 29-DEC-07:00 |
Annual Sum or Average | 0.276715E+14 | 0.328110E+13 | ||||
Minimum of Months | 0.165291E+13 | 1185801.10 | 21897387.08 | 4050.79 | ||
Maximum of Months | 0.322323E+13 | 2132523.49 | 0.105880E+13 | 2405335.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.211186E+12 | 0.439785E+11 | 0.766053E+12 | 0.213317E+12 | 0.183954E+12 | 0.135157E+11 | 0.00 | 0.908763E+10 | 0.443964E+09 | 0.167481E+12 | 0.00 | 0.438920E+11 | 0.00 |
February | 0.187662E+12 | 0.343652E+11 | 0.978954E+12 | 0.195308E+12 | 0.169651E+12 | 0.161555E+11 | 0.00 | 0.285849E+11 | 0.208289E+10 | 0.235553E+12 | 0.00 | 0.405627E+11 | 0.00 |
March | 0.221192E+12 | 0.309919E+11 | 0.141687E+13 | 0.226028E+12 | 0.196507E+12 | 0.208425E+11 | 0.00 | 0.502303E+11 | 0.284440E+10 | 0.267840E+12 | 0.00 | 0.472084E+11 | 0.00 |
April | 0.195944E+12 | 0.234963E+11 | 0.165903E+13 | 0.211475E+12 | 0.204928E+12 | 0.228996E+11 | 0.00 | 0.812440E+11 | 0.144972E+11 | 0.257983E+12 | 0.00 | 0.413089E+11 | 0.00 |
May | 0.210560E+12 | 0.190970E+11 | 0.774844E+12 | 0.219671E+12 | 0.225466E+12 | 0.288397E+11 | 0.00 | 0.506424E+11 | 0.222474E+11 | 0.164430E+12 | 0.00 | 0.417474E+11 | 0.00 |
June | 0.209031E+12 | 0.165593E+11 | 0.106252E+13 | 0.217906E+12 | 0.279395E+12 | 0.392253E+11 | 0.00 | 0.158703E+12 | 0.547300E+11 | 0.140319E+12 | 0.00 | 0.388884E+11 | 0.00 |
July | 0.195851E+12 | 0.178083E+11 | 0.139340E+13 | 0.213239E+12 | 0.321366E+12 | 0.543162E+11 | 0.00 | 0.324224E+12 | 0.890774E+11 | 0.115134E+12 | 0.00 | 0.351802E+11 | 0.00 |
August | 0.218784E+12 | 0.218398E+11 | 0.173200E+13 | 0.226028E+12 | 0.314938E+12 | 0.512763E+11 | 0.00 | 0.345722E+12 | 0.830540E+11 | 0.191942E+12 | 0.00 | 0.376441E+11 | 0.00 |
September | 0.196677E+12 | 0.269399E+11 | 0.740713E+12 | 0.211475E+12 | 0.238174E+12 | 0.341374E+11 | 0.00 | 0.928483E+11 | 0.420933E+11 | 0.112613E+12 | 0.00 | 0.346346E+11 | 0.00 |
October | 0.206052E+12 | 0.349085E+11 | 0.108340E+13 | 0.213315E+12 | 0.215344E+12 | 0.257470E+11 | 0.00 | 0.585638E+11 | 0.129201E+11 | 0.248230E+12 | 0.00 | 0.373447E+11 | 0.00 |
November | 0.206869E+12 | 0.406352E+11 | 0.135889E+13 | 0.205270E+12 | 0.191717E+12 | 0.193702E+11 | 0.00 | 0.486220E+11 | 0.374736E+10 | 0.259199E+12 | 0.00 | 0.388855E+11 | 0.00 |
December | 0.204379E+12 | 0.459151E+11 | 0.170972E+13 | 0.213242E+12 | 0.185172E+12 | 0.165019E+11 | 0.00 | 0.526670E+11 | 0.285483E+10 | 0.267840E+12 | 0.00 | 0.410306E+11 | 0.00 |
Annual Sum or Average | 0.246419E+13 | 0.356535E+12 | 0.146764E+14 | 0.256627E+13 | 0.272661E+13 | 0.342827E+12 | 0.00 | 0.130114E+13 | 0.330593E+12 | 0.242856E+13 | 0.00 | 0.478328E+12 | 0.00 |
Minimum of Months | 0.187662E+12 | 0.165593E+11 | 0.740713E+12 | 0.195308E+12 | 0.169651E+12 | 0.135157E+11 | 0.00 | 0.908763E+10 | 0.443964E+09 | 0.112613E+12 | 0.00 | 0.346346E+11 | 0.00 |
Maximum of Months | 0.221192E+12 | 0.459151E+11 | 0.173200E+13 | 0.226028E+12 | 0.321366E+12 | 0.543162E+11 | 0.00 | 0.345722E+12 | 0.890774E+11 | 0.267840E+12 | 0.00 | 0.472084E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.105880E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.568856E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.368198E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124787E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.765914E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.500507E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 21897387.08 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.134909E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.246004E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.906192E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.279457E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.682806E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.328110E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 21897387.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.105880E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233397.31 | 02-JAN-08:20 | 105179.12 | 02-JAN-13:09 | 20493.79 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 231397.24 | 02-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233388.92 | 02-FEB-08:20 | 169402.88 | 28-FEB-16:30 | 21019.27 | 27-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 243690.86 | 17-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233395.44 | 17-MAR-07:19 | 166721.71 | 28-MAR-15:00 | 20773.82 | 28-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 227505.95 | 14-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233386.86 | 14-APR-07:19 | 240294.89 | 25-APR-15:39 | 22483.02 | 06-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 217725.22 | 03-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233381.69 | 03-MAY-07:19 | 324833.20 | 19-MAY-15:20 | 45889.95 | 19-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 213198.74 | 16-JUN-07:10 | 27558.46 | 01-JUN-20:10 | 541788.89 | 01-JUN-07:10 | 233379.29 | 16-JUN-07:19 | 332285.45 | 22-JUN-09:20 | 46308.03 | 30-JUN-13:30 | 0.00 | 01-JUN-00:10 |
July | 216144.34 | 07-JUL-07:30 | 27558.46 | 01-JUL-20:30 | 660080.29 | 03-JUL-07:10 | 233380.85 | 07-JUL-07:40 | 332285.45 | 11-JUL-13:50 | 46308.16 | 24-JUL-12:50 | 0.00 | 01-JUL-00:10 |
August | 216944.68 | 17-AUG-07:10 | 40855.88 | 03-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233381.27 | 17-AUG-07:19 | 332285.45 | 08-AUG-15:09 | 46313.77 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 226481.10 | 11-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233386.32 | 11-SEP-07:19 | 332285.45 | 01-SEP-13:00 | 46383.75 | 07-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 247210.90 | 30-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233397.31 | 30-OCT-07:19 | 212592.45 | 18-OCT-13:39 | 46270.54 | 18-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233397.31 | 01-NOV-07:19 | 168618.17 | 03-NOV-15:39 | 21124.03 | 03-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-16:40 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233397.31 | 13-DEC-08:20 | 124533.22 | 06-DEC-15:09 | 20637.58 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 213198.74 | 27558.46 | 423497.50 | 233379.29 | 105179.12 | 20493.79 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233397.31 | 332285.45 | 46383.75 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 11815.61 | 02-JAN-14:30 | 767.46 | 13-JAN-15:00 | 100000.00 | 03-JAN-14:50 | 0.00 | 58516.06 | 31-JAN-12:30 | 0.00 |
February | 94854.23 | 27-FEB-15:30 | 44073.56 | 27-FEB-15:30 | 100000.00 | 01-FEB-17:19 | 0.00 | 58671.08 | 17-FEB-12:20 | 0.00 |
March | 72370.71 | 28-MAR-15:00 | 4182.91 | 14-MAR-13:00 | 100000.00 | 01-MAR-06:10 | 0.00 | 58619.04 | 01-MAR-12:20 | 0.00 |
April | 276781.80 | 07-APR-13:00 | 45582.15 | 06-APR-15:00 | 100000.00 | 01-APR-05:10 | 0.00 | 57219.98 | 03-APR-11:50 | 0.00 |
May | 245506.24 | 19-MAY-15:20 | 74189.28 | 19-MAY-13:00 | 100000.00 | 02-MAY-21:19 | 0.00 | 54864.69 | 02-MAY-11:00 | 0.00 |
June | 367290.68 | 22-JUN-10:09 | 74189.28 | 06-JUN-14:30 | 100000.00 | 04-JUN-12:00 | 0.00 | 51479.05 | 01-JUN-11:50 | 0.00 |
July | 406706.23 | 14-JUL-09:00 | 74189.28 | 10-JUL-14:30 | 100000.00 | 07-JUL-21:10 | 0.00 | 47968.51 | 03-JUL-11:30 | 0.00 |
August | 424184.24 | 10-AUG-14:00 | 74189.28 | 05-AUG-12:50 | 100000.00 | 02-AUG-21:10 | 0.00 | 46516.78 | 01-AUG-11:00 | 0.00 |
September | 410692.09 | 07-SEP-15:09 | 74189.28 | 02-SEP-10:39 | 100000.00 | 01-SEP-21:10 | 0.00 | 47426.15 | 28-SEP-11:00 | 0.00 |
October | 249882.35 | 18-OCT-13:50 | 47392.30 | 18-OCT-13:00 | 100000.00 | 02-OCT-21:10 | 0.00 | 50848.00 | 31-OCT-11:00 | 0.00 |
November | 91544.40 | 03-NOV-14:30 | 28965.64 | 17-NOV-16:00 | 100000.00 | 01-NOV-04:19 | 0.00 | 53571.00 | 30-NOV-12:50 | 0.00 |
December | 34668.61 | 07-DEC-11:00 | 4157.88 | 10-DEC-01:00 | 100000.00 | 01-DEC-05:30 | 0.00 | 56255.20 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 11815.61 | 767.46 | 100000.00 | 0.00 | 46516.78 | 0.00 | ||||
Maximum of Months | 424184.24 | 74189.28 | 100000.00 | 0.00 | 58671.08 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1185801.10 | 02-JAN-16:40 | 247210.90 | 423497.50 | 40855.88 | 233281.85 | 89283.20 | 20363.77 | 0.00 | 9205.59 | 426.30 |
February | 1430361.74 | 27-FEB-15:00 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 156441.16 | 20737.66 | 0.00 | 88044.72 | 44019.55 |
March | 1512764.19 | 28-MAR-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 166721.71 | 20631.52 | 0.00 | 72370.71 | 2304.97 |
April | 1918543.88 | 06-APR-15:00 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 215141.21 | 22483.02 | 0.00 | 267498.82 | 45582.15 |
May | 1580174.00 | 19-MAY-15:20 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 324833.20 | 45887.45 | 0.00 | 245506.24 | 49178.05 |
June | 1828173.54 | 22-JUN-10:09 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 313177.09 | 46200.99 | 0.00 | 367290.68 | 74189.28 |
July | 1955035.36 | 17-JUL-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 319091.16 | 45184.27 | 0.00 | 373521.76 | 74189.28 |
August | 2132523.49 | 08-AUG-15:00 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 332285.45 | 46313.77 | 0.00 | 414626.74 | 74189.28 |
September | 1755764.62 | 07-SEP-15:09 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 320151.26 | 46307.58 | 0.00 | 410692.09 | 74189.28 |
October | 1606738.36 | 18-OCT-15:00 | 213905.24 | 541788.89 | 0.00 | 233266.34 | 188627.60 | 39245.54 | 0.00 | 204903.61 | 47392.30 |
November | 1538661.51 | 17-NOV-16:00 | 247210.90 | 660080.29 | 40855.88 | 233284.51 | 105876.98 | 20452.65 | 0.00 | 61719.90 | 28965.64 |
December | 1586331.77 | 07-DEC-16:30 | 247210.90 | 778371.69 | 40855.88 | 233276.35 | 94246.18 | 20365.11 | 0.00 | 28350.55 | 1738.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1185801.10 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 89283.20 | 20363.77 | 0.00 | 9205.59 | 426.30 | |
Maximum of Months | 2132523.49 | 247210.90 | 778371.69 | 40855.88 | 233284.51 | 332285.45 | 46313.77 | 0.00 | 414626.74 | 74189.28 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2405335.49 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1643704.29 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1598496.75 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 583921.03 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 556799.27 | 08-MAY-06:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 253239.14 | 16-JUN-06:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4050.79 | 05-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 442970.91 | 17-AUG-13:20 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 380189.54 | 11-SEP-09:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 664469.70 | 10-OCT-06:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1310219.39 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1807328.16 | 29-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4050.79 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2405335.49 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 27.09 | 38.17 | 26.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 41.50 | 25.99 | 23.50 | 25.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 58.17 | 26.10 | 27.50 | 26.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 26.26 | 25.83 | 26.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 71.83 | 26.56 | 34.33 | 26.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 121.50 | 27.06 | 77.83 | 27.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 341.33 | 27.96 | 215.50 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 271.67 | 27.53 | 170.33 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 27.00 | 64.33 | 26.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 90.17 | 26.91 | 37.33 | 26.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 26.72 | 31.33 | 26.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 26.24 | 25.83 | 26.23 |
Annual Sum or Average | 0.00 | 0.00 | 1376.67 | 27.18 | 771.83 | 27.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.50 | 25.99 | 23.50 | 25.97 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 341.33 | 27.96 | 215.50 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.93 | 3.50 | 24.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 24.86 | 51.33 | 24.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 25.02 | 26.00 | 24.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.77 | 0.00 | 25.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 25.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Annual Sum or Average | 0.00 | 0.00 | 87.17 | 24.93 | 80.83 | 24.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 25.77 | 51.33 | 25.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.71 | 1.50 | 24.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.77 | 6.50 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.67 | 3.67 | 24.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.67 | 24.73 | 11.67 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.77 | 6.50 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 18.82 | 2.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 1.83 | 18.89 | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
March | 1.67 | 18.81 | 0.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.72 | 4.50 | 24.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 24.89 | 16.50 | 24.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.94 | 9.00 | 24.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
November | 2.00 | 18.62 | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 3.17 | 18.64 | 0.33 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
Annual Sum or Average | 18.50 | 18.78 | 4.50 | 19.02 | 30.00 | 22.34 | 30.00 | 23.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.33 | 19.32 | 2.67 | 19.32 | 16.50 | 24.94 | 16.50 | 24.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.65 | 0.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
February | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.99 | 7.17 | 24.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 25.31 | 70.50 | 25.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 25.24 | 33.67 | 25.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.33 | 2.33 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 18.69 | 0.17 | 18.75 | 118.33 | 25.13 | 113.67 | 25.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.36 | 0.17 | 19.36 | 73.17 | 27.33 | 70.50 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
February | 0.50 | 19.31 | 0.00 | 19.31 | 0.50 | 23.44 | 0.50 | 24.82 |
March | 0.17 | 19.32 | 0.00 | 19.32 | 0.50 | 25.36 | 0.50 | 26.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.07 | 2.00 | 28.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 26.84 | 15.00 | 26.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 26.36 | 36.17 | 26.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 26.04 | 22.17 | 26.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.72 | 8.00 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.84 | 1.17 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 4.17 | 18.63 | 0.00 | 18.63 | 91.33 | 26.22 | 86.17 | 26.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.32 | 0.00 | 19.32 | 39.17 | 28.07 | 36.17 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.37 | 0.17 | 18.45 | 2.00 | 21.76 | 2.00 | 23.38 |
February | 0.50 | 19.23 | 0.00 | 19.23 | 4.67 | 27.30 | 4.67 | 27.71 |
March | 0.33 | 19.19 | 0.00 | 19.19 | 2.00 | 26.88 | 2.00 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.96 | 4.17 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 2.33 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.12 | 13.50 | 26.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 25.93 | 57.33 | 25.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 25.84 | 66.83 | 25.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 26.46 | 25.67 | 26.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.20 | 8.17 | 27.19 |
November | 0.17 | 19.26 | 0.00 | 19.26 | 3.67 | 27.69 | 3.67 | 27.88 |
December | 0.50 | 19.10 | 0.00 | 19.10 | 2.17 | 26.07 | 2.17 | 26.79 |
Annual Sum or Average | 5.17 | 18.60 | 0.17 | 18.66 | 200.17 | 26.06 | 192.50 | 26.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.76 | 2.00 | 23.38 |
Maximum of Months | 3.67 | 19.26 | 0.17 | 19.26 | 68.50 | 27.96 | 66.83 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.07 | 2.00 | 28.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.92 | 1.83 | 27.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.97 | 4.67 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.22 | 3.50 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.41 | 10.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 | 27.00 | 43.83 | 26.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 26.76 | 34.50 | 26.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.53 | 8.67 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.15 | 2.83 | 28.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.58 | 1.50 | 27.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
Annual Sum or Average | 2.17 | 19.11 | 0.00 | 19.11 | 181.00 | 27.06 | 114.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | 0.00 | 19.11 |
Maximum of Months | 2.17 | 19.11 | 0.00 | 19.11 | 67.00 | 28.22 | 43.83 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.50 | 17.29 | 20.67 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
February | 13.17 | 17.49 | 3.33 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
March | 5.00 | 18.07 | 1.67 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
April | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
May | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.82 | 3.50 | 24.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 25.22 | 24.67 | 25.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 25.19 | 14.00 | 25.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.67 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.17 | 18.38 | 0.67 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
December | 14.33 | 17.26 | 4.83 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
Annual Sum or Average | 84.50 | 17.43 | 31.17 | 17.66 | 45.00 | 19.79 | 43.83 | 20.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.50 | 19.44 | 20.67 | 19.44 | 25.33 | 27.36 | 24.67 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.50 | 17.49 | 3.33 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
February | 15.83 | 18.13 | 0.50 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
March | 4.33 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.88 | 1.83 | 27.88 |
May | 0.17 | 19.35 | 0.00 | 19.35 | 0.50 | 25.32 | 0.50 | 26.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.39 | 11.17 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.13 | 20.50 | 27.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.70 | 11.00 | 26.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.05 | 7.33 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.57 | 0.83 | 27.57 |
November | 5.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 22.00 | 17.80 | 2.00 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
Annual Sum or Average | 95.50 | 17.81 | 5.83 | 17.66 | 64.17 | 21.37 | 53.17 | 22.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 0.00 | 17.36 |
Maximum of Months | 47.50 | 19.35 | 3.33 | 19.35 | 25.17 | 28.05 | 20.50 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 16.37 | 2.17 | 16.24 | 1.67 | 17.20 | 1.67 | 18.01 |
February | 4.83 | 17.51 | 0.50 | 17.27 | 5.50 | 22.54 | 5.50 | 24.26 |
March | 1.33 | 18.28 | 0.00 | 18.28 | 4.00 | 24.58 | 4.00 | 25.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.00 | 3.67 | 28.01 |
May | 0.17 | 19.43 | 0.00 | 19.43 | 2.00 | 27.18 | 2.00 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.36 | 11.00 | 26.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.83 | 26.35 | 36.50 | 26.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 26.07 | 38.50 | 26.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.05 | 18.17 | 27.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.42 | 13.83 | 26.41 |
November | 1.17 | 17.99 | 0.00 | 17.99 | 3.67 | 25.58 | 3.67 | 26.62 |
December | 7.67 | 16.56 | 1.17 | 16.32 | 1.33 | 17.78 | 1.33 | 18.90 |
Annual Sum or Average | 31.67 | 16.75 | 3.83 | 16.56 | 145.67 | 24.61 | 139.83 | 25.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 17.20 | 1.33 | 18.01 |
Maximum of Months | 16.50 | 19.43 | 2.17 | 19.43 | 39.83 | 28.00 | 38.50 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 15.93 | 3.00 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
February | 3.83 | 18.29 | 0.00 | 18.29 | 0.67 | 19.71 | 0.67 | 20.76 |
March | 1.17 | 18.10 | 0.00 | 18.10 | 0.17 | 19.25 | 0.17 | 20.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.50 | 1.17 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.34 | 2.67 | 28.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.68 | 5.67 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.04 | 23.83 | 26.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.79 | 11.67 | 26.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.80 | 5.50 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.01 | 1.17 | 27.98 |
November | 1.33 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
December | 8.33 | 16.56 | 1.67 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
Annual Sum or Average | 32.83 | 16.53 | 4.67 | 16.34 | 78.17 | 23.76 | 52.50 | 24.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 0.00 | 15.81 |
Maximum of Months | 18.17 | 18.29 | 3.00 | 18.29 | 33.17 | 28.50 | 23.83 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.17 | 16.81 | 47.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
February | 40.67 | 17.48 | 15.50 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
March | 23.50 | 16.88 | 7.50 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
April | 2.00 | 18.95 | 0.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
May | 2.83 | 18.35 | 0.50 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.72 | 2.00 | 24.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 25.49 | 26.00 | 25.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 25.42 | 10.50 | 25.36 |
September | 0.33 | 19.35 | 0.00 | 19.35 | 3.00 | 26.69 | 2.50 | 27.05 |
October | 2.67 | 18.75 | 0.50 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
November | 26.50 | 16.77 | 9.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
December | 64.83 | 16.56 | 25.67 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
Annual Sum or Average | 264.50 | 16.91 | 106.00 | 17.21 | 43.67 | 18.09 | 41.00 | 18.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 | 16.78 |
Maximum of Months | 101.17 | 19.35 | 47.00 | 19.35 | 27.50 | 26.69 | 26.00 | 27.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.17 | 14.99 | 8.17 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 19.17 | 15.86 | 1.83 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
March | 14.00 | 16.20 | 1.33 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
April | 1.50 | 18.70 | 0.00 | 18.70 | 0.67 | 21.48 | 0.67 | 22.96 |
May | 2.00 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.26 | 13.33 | 27.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 26.70 | 29.67 | 26.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.74 | 12.50 | 26.70 |
September | 0.17 | 19.33 | 0.00 | 19.33 | 8.00 | 27.86 | 6.83 | 27.98 |
October | 1.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
November | 15.00 | 15.82 | 2.50 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
December | 38.00 | 15.31 | 7.50 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
Annual Sum or Average | 134.50 | 15.55 | 21.33 | 15.40 | 69.17 | 18.96 | 63.00 | 20.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 | 0.00 | 14.88 |
Maximum of Months | 43.17 | 19.33 | 8.17 | 19.33 | 32.83 | 27.86 | 29.67 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.83 | 15.67 | 6.00 | 15.66 | 0.33 | 15.75 | 0.33 | 15.84 |
February | 15.00 | 16.29 | 0.67 | 16.20 | 1.67 | 17.40 | 1.67 | 18.40 |
March | 12.83 | 16.49 | 1.17 | 16.45 | 0.83 | 17.08 | 0.83 | 17.65 |
April | 1.33 | 18.70 | 0.00 | 18.70 | 2.67 | 24.79 | 2.67 | 26.01 |
May | 1.67 | 17.96 | 0.00 | 17.96 | 2.00 | 23.31 | 2.00 | 24.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.49 | 10.50 | 26.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 26.30 | 38.83 | 26.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 26.10 | 36.33 | 26.07 |
September | 0.17 | 19.43 | 0.00 | 19.43 | 15.50 | 27.35 | 13.33 | 27.37 |
October | 1.17 | 18.48 | 0.00 | 18.48 | 5.83 | 25.74 | 5.67 | 26.39 |
November | 9.00 | 16.41 | 0.83 | 16.27 | 1.33 | 17.63 | 1.33 | 18.70 |
December | 29.50 | 15.67 | 5.00 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
Annual Sum or Average | 107.50 | 16.03 | 13.67 | 15.94 | 121.33 | 21.25 | 113.50 | 22.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 0.00 | 15.55 |
Maximum of Months | 36.83 | 19.43 | 6.00 | 19.43 | 42.00 | 27.35 | 38.83 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.33 | 15.04 | 5.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
February | 15.33 | 16.15 | 1.83 | 15.98 | 0.50 | 16.31 | 0.50 | 16.62 |
March | 10.83 | 16.40 | 1.17 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 1.00 | 19.11 | 0.00 | 19.11 | 1.67 | 25.01 | 1.00 | 25.99 |
May | 1.50 | 18.41 | 0.00 | 18.41 | 6.00 | 26.18 | 3.00 | 26.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.70 | 6.33 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.11 | 24.83 | 26.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 26.80 | 12.67 | 26.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.89 | 5.50 | 27.87 |
October | 0.83 | 18.31 | 0.00 | 18.31 | 0.83 | 23.19 | 0.67 | 24.60 |
November | 8.83 | 16.22 | 1.67 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
December | 25.83 | 15.69 | 5.00 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
Annual Sum or Average | 98.50 | 15.76 | 15.50 | 15.58 | 80.33 | 20.44 | 54.50 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 0.00 | 14.90 |
Maximum of Months | 34.33 | 19.11 | 5.83 | 19.11 | 34.67 | 27.89 | 24.83 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.91 | 7.50 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.33 | 27.91 | 7.50 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.91 | 7.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.84 | 2.83 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.33 | 27.84 | 2.83 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.84 | 2.83 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.92 | 4.33 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.17 | 27.92 | 4.33 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.92 | 4.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 337.33 | 24.29 | 47.83 | 24.60 | 13.50 | 24.74 |
February | 235.50 | 24.03 | 60.67 | 24.48 | 0.00 | 24.48 |
March | 205.00 | 24.00 | 62.67 | 24.51 | 0.00 | 24.51 |
April | 78.33 | 24.00 | 108.50 | 25.29 | 0.00 | 25.29 |
May | 72.00 | 24.06 | 132.17 | 25.36 | 1.17 | 25.37 |
June | 45.67 | 27.04 | 253.33 | 25.90 | 43.33 | 26.06 |
July | 149.33 | 28.87 | 429.83 | 27.10 | 149.33 | 27.47 |
August | 95.00 | 28.43 | 326.00 | 26.76 | 95.00 | 27.07 |
September | 29.00 | 26.67 | 246.17 | 25.69 | 22.33 | 25.82 |
October | 14.33 | 24.26 | 141.33 | 26.31 | 1.00 | 26.32 |
November | 82.83 | 24.00 | 116.00 | 25.47 | 0.00 | 25.47 |
December | 181.67 | 24.01 | 78.33 | 24.71 | 0.00 | 24.71 |
Annual Sum or Average | 1526.00 | 24.97 | 2002.83 | 25.66 | 325.67 | 25.89 |
Minimum of Months | 14.33 | 24.00 | 47.83 | 24.48 | 0.00 | 24.48 |
Maximum of Months | 337.33 | 28.87 | 429.83 | 27.10 | 149.33 | 27.47 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.83 | 23.83 | 15.83 | 23.92 | 0.00 | 23.92 |
February | 295.67 | 23.96 | 6.17 | 23.99 | 0.00 | 23.99 |
March | 238.67 | 24.03 | 22.33 | 24.19 | 0.00 | 24.19 |
April | 73.17 | 24.01 | 63.33 | 24.89 | 0.00 | 24.89 |
May | 95.33 | 24.00 | 88.50 | 24.69 | 0.00 | 24.69 |
June | 0.33 | 24.00 | 229.33 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 397.83 | 24.59 | 0.00 | 24.59 |
August | 0.00 | 0.00 | 274.00 | 24.67 | 0.00 | 24.67 |
September | 23.67 | 24.06 | 202.83 | 24.65 | 5.83 | 24.64 |
October | 39.83 | 24.00 | 82.83 | 25.33 | 0.00 | 25.33 |
November | 151.83 | 24.01 | 51.83 | 24.49 | 0.00 | 24.49 |
December | 262.50 | 24.02 | 25.00 | 24.18 | 0.00 | 24.18 |
Annual Sum or Average | 1597.83 | 23.96 | 1459.83 | 24.42 | 5.83 | 24.42 |
Minimum of Months | 0.00 | 0.00 | 6.17 | 23.92 | 0.00 | 23.92 |
Maximum of Months | 416.83 | 24.06 | 397.83 | 25.33 | 5.83 | 25.33 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.49 | 67.67 | 22.28 | 67.67 | 22.11 |
February | 446.17 | 23.01 | 23.17 | 22.88 | 23.17 | 22.77 |
March | 487.17 | 23.59 | 4.67 | 23.57 | 4.67 | 23.54 |
April | 317.67 | 23.81 | 0.83 | 23.81 | 0.00 | 23.81 |
May | 218.00 | 23.92 | 47.67 | 24.17 | 0.00 | 24.17 |
June | 46.83 | 23.92 | 151.67 | 24.28 | 0.00 | 24.28 |
July | 17.00 | 23.98 | 271.17 | 24.42 | 0.83 | 24.42 |
August | 7.67 | 23.92 | 154.00 | 24.62 | 0.00 | 24.62 |
September | 89.17 | 23.90 | 147.33 | 24.33 | 6.33 | 24.32 |
October | 276.00 | 23.88 | 11.33 | 23.94 | 0.00 | 23.94 |
November | 408.33 | 23.60 | 2.00 | 23.58 | 2.00 | 23.57 |
December | 497.00 | 22.96 | 31.50 | 22.81 | 31.50 | 22.68 |
Annual Sum or Average | 3313.00 | 23.33 | 913.00 | 23.48 | 136.17 | 23.40 |
Minimum of Months | 7.67 | 22.49 | 0.83 | 22.28 | 0.00 | 22.11 |
Maximum of Months | 502.00 | 23.98 | 271.17 | 24.62 | 67.67 | 24.62 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.74 | 333.17 | 20.52 | 333.17 | 20.42 |
February | 454.00 | 21.51 | 190.00 | 21.18 | 190.00 | 21.01 |
March | 514.00 | 22.28 | 103.67 | 21.95 | 103.67 | 21.71 |
April | 436.67 | 22.96 | 31.00 | 22.82 | 31.00 | 22.69 |
May | 300.67 | 23.27 | 46.67 | 23.36 | 11.50 | 23.29 |
June | 109.33 | 23.63 | 158.50 | 24.05 | 0.00 | 24.05 |
July | 40.17 | 23.92 | 279.50 | 24.39 | 5.17 | 24.40 |
August | 62.33 | 23.75 | 150.83 | 24.33 | 0.00 | 24.33 |
September | 209.83 | 23.34 | 119.50 | 23.77 | 8.00 | 23.78 |
October | 449.50 | 22.95 | 18.83 | 22.86 | 18.83 | 22.77 |
November | 484.33 | 22.01 | 130.00 | 21.67 | 130.00 | 21.44 |
December | 497.00 | 21.05 | 278.17 | 20.71 | 278.17 | 20.55 |
Annual Sum or Average | 4059.83 | 22.17 | 1839.83 | 22.11 | 1109.50 | 21.83 |
Minimum of Months | 40.17 | 20.74 | 18.83 | 20.52 | 0.00 | 20.42 |
Maximum of Months | 514.00 | 23.92 | 333.17 | 24.39 | 333.17 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.33 | 256.50 | 21.04 | 256.50 | 20.90 |
February | 454.00 | 22.10 | 111.83 | 21.81 | 111.83 | 21.62 |
March | 511.17 | 22.95 | 39.83 | 22.79 | 39.83 | 22.65 |
April | 361.17 | 23.54 | 5.50 | 23.57 | 0.00 | 23.57 |
May | 266.33 | 23.57 | 65.83 | 23.87 | 0.00 | 23.87 |
June | 39.33 | 23.85 | 243.67 | 24.40 | 0.00 | 24.40 |
July | 12.50 | 26.17 | 405.83 | 24.78 | 9.17 | 24.83 |
August | 27.00 | 24.31 | 250.17 | 24.67 | 3.83 | 24.71 |
September | 184.33 | 23.60 | 145.83 | 24.08 | 6.50 | 24.12 |
October | 396.50 | 23.48 | 6.00 | 23.51 | 0.00 | 23.51 |
November | 475.67 | 22.85 | 25.83 | 22.75 | 25.83 | 22.66 |
December | 497.00 | 22.02 | 129.00 | 21.73 | 129.00 | 21.55 |
Annual Sum or Average | 3727.00 | 22.71 | 1685.83 | 22.90 | 582.50 | 22.70 |
Minimum of Months | 12.50 | 21.33 | 5.50 | 21.04 | 0.00 | 20.90 |
Maximum of Months | 511.17 | 26.17 | 405.83 | 24.78 | 256.50 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.00 | 21.52 | 233.17 | 21.21 | 229.50 | 21.04 |
February | 407.33 | 22.23 | 108.00 | 22.02 | 97.17 | 21.81 |
March | 425.17 | 22.80 | 58.17 | 22.75 | 34.17 | 22.61 |
April | 296.17 | 23.40 | 72.33 | 23.69 | 5.17 | 23.73 |
May | 189.33 | 23.43 | 141.33 | 23.96 | 0.67 | 23.96 |
June | 74.00 | 25.09 | 304.67 | 24.67 | 30.67 | 24.84 |
July | 63.67 | 26.52 | 428.33 | 24.94 | 58.00 | 25.13 |
August | 55.17 | 25.21 | 343.17 | 24.65 | 29.83 | 24.78 |
September | 143.50 | 24.08 | 223.33 | 24.47 | 27.17 | 24.64 |
October | 299.00 | 23.37 | 54.33 | 23.62 | 2.33 | 23.65 |
November | 440.33 | 22.80 | 37.67 | 22.70 | 32.17 | 22.58 |
December | 489.17 | 21.95 | 141.67 | 21.65 | 141.67 | 21.46 |
Annual Sum or Average | 3371.83 | 22.78 | 2146.17 | 23.12 | 688.50 | 22.99 |
Minimum of Months | 55.17 | 21.52 | 37.67 | 21.21 | 0.67 | 21.04 |
Maximum of Months | 489.17 | 26.52 | 428.33 | 24.94 | 229.50 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 423.00 | 21.60 | 232.67 | 21.44 | 207.33 | 21.25 |
February | 323.83 | 22.33 | 147.00 | 22.41 | 95.17 | 22.23 |
March | 367.83 | 22.82 | 112.50 | 22.92 | 39.33 | 22.80 |
April | 284.33 | 23.36 | 84.67 | 23.66 | 11.00 | 23.73 |
May | 226.33 | 23.29 | 138.33 | 23.79 | 9.50 | 23.80 |
June | 86.67 | 24.35 | 267.50 | 24.49 | 18.83 | 24.61 |
July | 65.67 | 26.28 | 404.17 | 24.99 | 56.17 | 25.17 |
August | 82.67 | 25.57 | 347.33 | 24.95 | 57.00 | 25.12 |
September | 146.50 | 24.25 | 266.50 | 24.61 | 42.00 | 24.80 |
October | 246.50 | 23.55 | 151.67 | 24.00 | 16.33 | 24.12 |
November | 324.00 | 22.86 | 122.17 | 23.12 | 40.00 | 23.03 |
December | 396.67 | 22.06 | 173.00 | 21.99 | 123.00 | 21.74 |
Annual Sum or Average | 2974.00 | 22.91 | 2447.50 | 23.37 | 715.67 | 23.28 |
Minimum of Months | 65.67 | 21.60 | 84.67 | 21.44 | 9.50 | 21.25 |
Maximum of Months | 423.00 | 26.28 | 404.17 | 24.99 | 207.33 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.33 | 22.03 | 174.33 | 21.67 | 171.50 | 21.44 |
February | 351.67 | 23.05 | 72.83 | 23.01 | 44.83 | 22.86 |
March | 263.83 | 23.75 | 64.00 | 23.88 | 9.33 | 23.84 |
April | 67.33 | 24.70 | 181.00 | 25.08 | 15.17 | 25.20 |
May | 123.83 | 24.11 | 204.00 | 24.59 | 13.17 | 24.69 |
June | 36.17 | 26.45 | 382.33 | 24.82 | 30.83 | 24.96 |
July | 94.00 | 26.56 | 480.17 | 25.14 | 94.00 | 25.34 |
August | 61.33 | 26.45 | 475.33 | 24.90 | 61.33 | 25.05 |
September | 87.17 | 24.78 | 257.83 | 24.80 | 27.33 | 24.96 |
October | 126.50 | 24.09 | 128.50 | 24.63 | 7.33 | 24.70 |
November | 254.00 | 23.77 | 70.00 | 24.11 | 1.00 | 24.12 |
December | 359.50 | 23.43 | 39.17 | 23.41 | 19.33 | 23.30 |
Annual Sum or Average | 2305.67 | 23.57 | 2529.50 | 24.04 | 495.17 | 24.02 |
Minimum of Months | 36.17 | 22.03 | 39.17 | 21.67 | 1.00 | 21.44 |
Maximum of Months | 480.33 | 26.56 | 480.17 | 25.14 | 171.50 | 25.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 479.00 | 20.11 | 479.00 | 20.10 |
February | 454.00 | 20.70 | 342.17 | 20.56 | 342.17 | 20.51 |
March | 514.00 | 21.42 | 210.17 | 21.13 | 210.17 | 20.98 |
April | 471.83 | 22.46 | 49.33 | 22.29 | 49.33 | 22.15 |
May | 349.83 | 22.93 | 68.17 | 22.97 | 26.67 | 22.83 |
June | 111.67 | 23.51 | 184.00 | 24.04 | 0.00 | 24.04 |
July | 31.67 | 24.06 | 304.00 | 24.54 | 3.33 | 24.56 |
August | 103.67 | 23.54 | 160.33 | 24.18 | 0.67 | 24.19 |
September | 273.83 | 22.92 | 96.67 | 23.37 | 8.17 | 23.37 |
October | 488.83 | 22.38 | 39.17 | 22.25 | 39.17 | 22.14 |
November | 489.00 | 21.19 | 237.50 | 20.89 | 237.50 | 20.75 |
December | 497.00 | 20.29 | 422.67 | 20.20 | 422.67 | 20.17 |
Annual Sum or Average | 4287.33 | 21.60 | 2593.17 | 21.59 | 1818.83 | 21.31 |
Minimum of Months | 31.67 | 20.13 | 39.17 | 20.11 | 0.00 | 20.10 |
Maximum of Months | 514.00 | 24.06 | 479.00 | 24.54 | 479.00 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.30 | 366.83 | 20.20 | 366.83 | 20.16 |
February | 374.33 | 21.22 | 227.83 | 20.92 | 225.00 | 20.77 |
March | 396.33 | 21.85 | 138.17 | 21.54 | 130.83 | 21.32 |
April | 290.17 | 22.61 | 73.50 | 22.82 | 27.50 | 22.73 |
May | 207.67 | 22.86 | 120.50 | 23.30 | 21.67 | 23.14 |
June | 93.83 | 24.72 | 238.50 | 24.71 | 32.50 | 24.92 |
July | 65.17 | 26.38 | 338.33 | 25.06 | 53.50 | 25.28 |
August | 68.50 | 24.61 | 255.17 | 24.68 | 22.33 | 24.83 |
September | 174.17 | 23.57 | 160.17 | 24.23 | 28.00 | 24.42 |
October | 329.50 | 22.66 | 36.83 | 22.70 | 18.67 | 22.61 |
November | 409.17 | 21.69 | 156.67 | 21.34 | 156.50 | 21.14 |
December | 422.00 | 20.45 | 320.33 | 20.26 | 320.33 | 20.19 |
Annual Sum or Average | 3257.83 | 21.91 | 2432.83 | 22.13 | 1403.67 | 21.89 |
Minimum of Months | 65.17 | 20.30 | 36.83 | 20.20 | 18.67 | 20.16 |
Maximum of Months | 427.00 | 26.38 | 366.83 | 25.06 | 366.83 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.50 | 21.10 | 307.17 | 20.92 | 287.83 | 20.77 |
February | 345.67 | 21.85 | 214.33 | 21.83 | 165.83 | 21.62 |
March | 386.33 | 22.13 | 180.33 | 22.16 | 109.50 | 21.94 |
April | 313.33 | 22.64 | 104.33 | 22.94 | 33.00 | 22.91 |
May | 254.33 | 22.87 | 139.33 | 23.31 | 25.33 | 23.24 |
June | 132.00 | 23.85 | 237.33 | 24.29 | 17.67 | 24.41 |
July | 84.33 | 25.44 | 362.50 | 24.86 | 49.67 | 25.05 |
August | 105.67 | 24.62 | 309.50 | 24.70 | 37.67 | 24.86 |
September | 177.00 | 23.79 | 251.17 | 24.39 | 39.00 | 24.59 |
October | 277.83 | 23.06 | 153.50 | 23.56 | 29.00 | 23.64 |
November | 351.00 | 22.22 | 180.67 | 22.34 | 104.33 | 22.14 |
December | 424.33 | 21.29 | 263.50 | 21.10 | 231.33 | 20.88 |
Annual Sum or Average | 3291.33 | 22.37 | 2703.67 | 22.77 | 1130.17 | 22.58 |
Minimum of Months | 84.33 | 21.10 | 104.33 | 20.92 | 17.67 | 20.77 |
Maximum of Months | 439.50 | 25.44 | 362.50 | 24.86 | 287.83 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.00 | 20.54 | 408.50 | 20.41 | 408.50 | 20.36 |
February | 425.33 | 21.28 | 243.17 | 21.03 | 235.50 | 20.88 |
March | 454.00 | 21.92 | 149.83 | 21.70 | 128.00 | 21.48 |
April | 340.67 | 22.82 | 69.33 | 23.00 | 20.33 | 22.96 |
May | 224.00 | 23.10 | 155.67 | 23.63 | 22.83 | 23.63 |
June | 78.33 | 24.16 | 291.33 | 24.43 | 18.50 | 24.54 |
July | 59.33 | 26.04 | 402.00 | 24.88 | 47.33 | 25.04 |
August | 66.17 | 24.52 | 309.17 | 24.62 | 22.17 | 24.72 |
September | 198.33 | 23.43 | 196.17 | 24.11 | 22.17 | 24.24 |
October | 373.33 | 22.77 | 61.17 | 22.89 | 20.17 | 22.84 |
November | 448.50 | 21.81 | 153.33 | 21.48 | 147.83 | 21.26 |
December | 493.33 | 20.79 | 337.00 | 20.55 | 337.00 | 20.44 |
Annual Sum or Average | 3662.33 | 21.98 | 2776.67 | 22.26 | 1430.33 | 22.01 |
Minimum of Months | 59.33 | 20.54 | 61.17 | 20.41 | 18.50 | 20.36 |
Maximum of Months | 501.00 | 26.04 | 408.50 | 24.88 | 408.50 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 495.17 | 19.70 | 495.17 | 19.69 |
February | 454.00 | 20.17 | 418.00 | 20.12 | 418.00 | 20.10 |
March | 514.00 | 20.72 | 339.67 | 20.50 | 339.67 | 20.40 |
April | 475.17 | 21.68 | 162.83 | 21.31 | 162.83 | 21.10 |
May | 382.00 | 22.41 | 106.00 | 22.26 | 73.17 | 22.00 |
June | 148.33 | 23.08 | 178.00 | 23.78 | 0.33 | 23.77 |
July | 69.00 | 23.91 | 291.00 | 24.44 | 10.33 | 24.51 |
August | 142.67 | 23.26 | 159.00 | 23.92 | 4.00 | 23.96 |
September | 316.17 | 22.44 | 122.17 | 22.76 | 43.17 | 22.67 |
October | 500.67 | 21.53 | 165.67 | 21.21 | 165.67 | 21.01 |
November | 489.00 | 20.39 | 362.33 | 20.22 | 362.33 | 20.14 |
December | 497.00 | 19.89 | 475.33 | 19.86 | 475.33 | 19.85 |
Annual Sum or Average | 4490.00 | 21.09 | 3275.17 | 21.06 | 2550.00 | 20.81 |
Minimum of Months | 69.00 | 19.71 | 106.00 | 19.70 | 0.33 | 19.69 |
Maximum of Months | 514.00 | 23.91 | 495.17 | 24.44 | 495.17 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 473.00 | 19.94 | 473.00 | 19.92 |
February | 451.33 | 20.78 | 321.50 | 20.51 | 321.50 | 20.40 |
March | 491.00 | 21.40 | 236.33 | 21.01 | 235.17 | 20.81 |
April | 352.33 | 21.95 | 151.33 | 21.85 | 103.50 | 21.58 |
May | 257.83 | 22.45 | 152.50 | 22.71 | 48.50 | 22.43 |
June | 122.33 | 24.31 | 292.67 | 24.50 | 37.50 | 24.70 |
July | 85.00 | 25.83 | 403.33 | 24.86 | 60.33 | 25.08 |
August | 89.83 | 24.05 | 322.00 | 24.42 | 22.17 | 24.54 |
September | 220.33 | 23.03 | 199.67 | 23.69 | 44.50 | 23.75 |
October | 425.67 | 22.13 | 101.83 | 21.82 | 95.83 | 21.58 |
November | 487.00 | 20.91 | 295.33 | 20.59 | 295.33 | 20.45 |
December | 497.00 | 20.05 | 449.17 | 19.97 | 449.17 | 19.94 |
Annual Sum or Average | 3981.67 | 21.45 | 3398.67 | 21.64 | 2186.50 | 21.38 |
Minimum of Months | 85.00 | 19.98 | 101.83 | 19.94 | 22.17 | 19.92 |
Maximum of Months | 502.00 | 25.83 | 473.00 | 24.86 | 473.00 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.33 | 20.62 | 366.83 | 20.40 | 360.83 | 20.28 |
February | 368.83 | 21.30 | 259.33 | 21.17 | 223.17 | 20.96 |
March | 404.33 | 21.38 | 264.50 | 21.31 | 204.83 | 21.07 |
April | 344.83 | 21.91 | 179.17 | 21.94 | 117.67 | 21.70 |
May | 288.00 | 22.38 | 166.67 | 22.61 | 68.17 | 22.37 |
June | 159.50 | 23.40 | 231.17 | 24.06 | 20.17 | 24.18 |
July | 108.00 | 24.89 | 342.33 | 24.76 | 52.17 | 24.96 |
August | 138.50 | 24.16 | 300.67 | 24.51 | 41.17 | 24.68 |
September | 208.33 | 23.13 | 243.83 | 23.87 | 53.17 | 23.97 |
October | 325.33 | 22.26 | 185.17 | 22.52 | 82.33 | 22.33 |
November | 399.33 | 21.52 | 239.33 | 21.38 | 190.83 | 21.12 |
December | 452.17 | 20.68 | 326.33 | 20.40 | 318.50 | 20.26 |
Annual Sum or Average | 3662.50 | 21.81 | 3105.33 | 22.08 | 1733.00 | 21.82 |
Minimum of Months | 108.00 | 20.62 | 166.67 | 20.40 | 20.17 | 20.26 |
Maximum of Months | 465.33 | 24.89 | 366.83 | 24.76 | 360.83 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 20.11 | 455.33 | 20.02 | 455.33 | 19.99 |
February | 434.17 | 20.80 | 314.83 | 20.57 | 309.83 | 20.46 |
March | 469.00 | 21.28 | 253.00 | 21.01 | 237.67 | 20.83 |
April | 370.33 | 22.11 | 146.33 | 22.05 | 102.17 | 21.83 |
May | 256.83 | 22.56 | 171.33 | 22.91 | 58.67 | 22.75 |
June | 124.50 | 23.68 | 281.83 | 24.24 | 19.83 | 24.36 |
July | 90.00 | 25.24 | 382.83 | 24.80 | 54.17 | 24.97 |
August | 106.50 | 24.01 | 296.50 | 24.45 | 24.50 | 24.56 |
September | 234.00 | 22.84 | 197.00 | 23.56 | 40.67 | 23.59 |
October | 412.17 | 22.04 | 125.00 | 21.93 | 93.17 | 21.72 |
November | 466.83 | 21.08 | 259.33 | 20.75 | 257.67 | 20.59 |
December | 495.17 | 20.28 | 408.17 | 20.11 | 408.17 | 20.05 |
Annual Sum or Average | 3960.83 | 21.50 | 3291.50 | 21.72 | 2061.83 | 21.46 |
Minimum of Months | 90.00 | 20.11 | 125.00 | 20.02 | 19.83 | 19.99 |
Maximum of Months | 501.33 | 25.24 | 455.33 | 24.80 | 455.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 404.33 | 27.00 | 0.00 | 27.00 |
February | 2.83 | 27.00 | 443.17 | 27.00 | 2.83 | 27.00 |
March | 6.33 | 27.00 | 514.00 | 27.00 | 6.33 | 27.00 |
April | 23.50 | 27.00 | 485.00 | 27.00 | 23.50 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 21.83 | 27.00 | 496.00 | 27.00 | 21.83 | 27.00 |
July | 141.83 | 27.00 | 497.00 | 27.00 | 141.83 | 27.00 |
August | 185.83 | 27.06 | 514.00 | 27.03 | 185.83 | 27.04 |
September | 13.83 | 27.00 | 485.00 | 27.00 | 13.83 | 27.00 |
October | 9.83 | 27.00 | 502.00 | 27.00 | 9.83 | 27.00 |
November | 8.17 | 27.00 | 489.00 | 27.00 | 8.17 | 27.00 |
December | 3.00 | 27.00 | 497.00 | 27.00 | 3.00 | 27.00 |
Annual Sum or Average | 419.00 | 27.03 | 5834.50 | 27.00 | 419.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 404.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 185.83 | 27.06 | 514.00 | 27.03 | 185.83 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.33 | 25.59 | 229.67 | 26.60 | 0.00 | 26.60 |
February | 10.33 | 27.00 | 331.83 | 27.00 | 0.00 | 27.00 |
March | 4.33 | 27.00 | 473.67 | 27.00 | 1.17 | 27.00 |
April | 4.83 | 27.00 | 485.00 | 27.00 | 4.83 | 27.00 |
May | 1.33 | 27.00 | 505.00 | 27.00 | 1.33 | 27.00 |
June | 9.00 | 27.00 | 496.00 | 27.00 | 9.00 | 27.00 |
July | 28.67 | 27.00 | 497.00 | 27.00 | 28.67 | 27.00 |
August | 34.83 | 27.13 | 514.00 | 27.02 | 34.83 | 27.02 |
September | 6.17 | 27.00 | 485.00 | 27.00 | 6.17 | 27.00 |
October | 3.33 | 27.00 | 502.00 | 27.00 | 3.33 | 27.00 |
November | 0.00 | 0.00 | 461.00 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 360.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 207.17 | 26.39 | 5340.83 | 26.98 | 89.33 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 229.67 | 26.60 | 0.00 | 26.60 |
Maximum of Months | 92.33 | 27.13 | 514.00 | 27.02 | 34.83 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 284.67 | 24.70 | 108.50 | 24.97 | 27.67 | 24.76 |
February | 36.67 | 26.93 | 188.67 | 26.99 | 0.00 | 26.99 |
March | 20.33 | 27.00 | 363.17 | 27.00 | 0.17 | 27.00 |
April | 5.50 | 27.00 | 440.67 | 27.00 | 5.50 | 27.00 |
May | 9.33 | 25.95 | 474.67 | 26.98 | 2.00 | 26.98 |
June | 14.17 | 27.00 | 496.00 | 27.00 | 14.17 | 27.00 |
July | 52.83 | 27.00 | 497.00 | 27.00 | 52.83 | 27.00 |
August | 55.33 | 27.10 | 514.00 | 27.02 | 55.33 | 27.03 |
September | 10.50 | 27.00 | 478.33 | 27.00 | 10.50 | 27.00 |
October | 2.50 | 27.00 | 466.00 | 27.00 | 2.50 | 27.00 |
November | 21.33 | 27.00 | 324.50 | 27.00 | 0.00 | 27.00 |
December | 62.50 | 27.00 | 194.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 575.67 | 25.85 | 4546.33 | 26.84 | 170.67 | 26.82 |
Minimum of Months | 2.50 | 24.70 | 108.50 | 24.97 | 0.00 | 24.76 |
Maximum of Months | 284.67 | 27.10 | 514.00 | 27.02 | 55.33 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.67 | 27.00 | 502.00 | 27.00 | 288.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 496.67 | 27.00 | 508.00 | 27.00 | 496.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5718.33 | 27.00 | 5943.00 | 27.00 | 5718.33 | 27.00 |
Minimum of Months | 288.67 | 27.00 | 454.00 | 27.00 | 288.67 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99865 | 13.67257 | 0.63433 | 13.67767 |
February | 454.00000 | 27.00000 | 14.91825 | 0.72625 | 16.26868 |
March | 514.00000 | 26.99999 | 16.87698 | 0.80307 | 18.70750 |
April | 485.00000 | 27.00002 | 19.95483 | 0.89159 | 21.85415 |
May | 508.00000 | 27.00015 | 22.20435 | 0.15457 | 5.64637 |
June | 496.00000 | 27.00045 | 25.45180 | 0.26355 | 6.53953 |
July | 497.00000 | 27.00028 | 26.34816 | 0.34791 | 7.63589 |
August | 514.00000 | 27.02104 | 25.82270 | 0.37417 | 8.09217 |
September | 485.00000 | 27.00047 | 25.28438 | 0.19082 | 5.90561 |
October | 502.00000 | 27.00006 | 22.32452 | 0.84622 | 20.16905 |
November | 489.00000 | 27.00000 | 18.47138 | 0.82009 | 19.27493 |
December | 497.00000 | 26.99999 | 14.80873 | 0.78494 | 18.12392 |
Annual Sum or Average | 5943.00000 | 27.00182 | 20.54913 | 0.56812 | 13.45374 |
Minimum of Months | 454.00000 | 26.99865 | 13.67257 | 0.15457 | 5.64637 |
Maximum of Months | 514.00000 | 27.02104 | 26.34816 | 0.89159 | 21.85415 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.71203 | 13.66011 | 0.44993 | 10.03395 |
February | 454.00000 | 27.00000 | 14.91066 | 0.58529 | 12.43759 |
March | 514.00000 | 26.99999 | 16.86166 | 0.66606 | 14.54809 |
April | 485.00000 | 27.00002 | 19.92750 | 0.76216 | 17.39364 |
May | 508.00000 | 27.00015 | 22.21315 | 0.07204 | 5.37675 |
June | 496.00000 | 27.00043 | 25.46578 | 0.17341 | 5.77111 |
July | 497.00000 | 27.00029 | 26.35576 | 0.23126 | 6.25624 |
August | 514.00000 | 27.00889 | 25.83267 | 0.23849 | 6.36585 |
September | 485.00000 | 27.00041 | 25.36703 | 0.11240 | 5.48374 |
October | 502.00000 | 27.00006 | 22.30609 | 0.74994 | 16.95878 |
November | 489.00000 | 27.00000 | 18.44816 | 0.67274 | 14.70951 |
December | 497.00000 | 26.99999 | 14.78514 | 0.58429 | 12.40553 |
Annual Sum or Average | 5943.00000 | 26.97656 | 20.54866 | 0.43986 | 10.61821 |
Minimum of Months | 454.00000 | 26.71203 | 13.66011 | 0.07204 | 5.37675 |
Maximum of Months | 514.00000 | 27.00889 | 26.35576 | 0.76216 | 17.39364 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.64922 | 14.11983 | 0.16662 | 8.55082 |
February | 454.00000 | 26.99465 | 14.91198 | 0.50460 | 10.69815 |
March | 514.00000 | 26.99999 | 16.86850 | 0.58745 | 12.62241 |
April | 485.00000 | 27.00002 | 19.94295 | 0.70063 | 15.66728 |
May | 508.00000 | 26.97596 | 22.24098 | 0.01718 | 5.77725 |
June | 496.00000 | 27.00044 | 25.47663 | 0.16475 | 5.86730 |
July | 497.00000 | 27.00030 | 26.36336 | 0.23509 | 6.42153 |
August | 514.00000 | 27.01120 | 25.83813 | 0.23230 | 6.45656 |
September | 485.00000 | 27.00039 | 25.43559 | 0.07279 | 5.58309 |
October | 502.00000 | 27.00006 | 22.32876 | 0.68164 | 15.02584 |
November | 489.00000 | 27.00001 | 18.45983 | 0.57824 | 12.34606 |
December | 497.00000 | 27.00000 | 14.79604 | 0.48809 | 10.34842 |
Annual Sum or Average | 5943.00000 | 26.88450 | 20.60322 | 0.36749 | 9.59488 |
Minimum of Months | 454.00000 | 25.64922 | 14.11983 | 0.01718 | 5.58309 |
Maximum of Months | 514.00000 | 27.01120 | 26.36336 | 0.70063 | 15.66728 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00040 | 30.00064 | 1.00627 | 26.41460 |
February | 454.00000 | 27.00047 | 27.06471 | 1.16418 | 33.53426 |
March | 514.00000 | 27.00017 | 22.06956 | 1.27942 | 39.22309 |
April | 485.00000 | 27.00056 | 21.45593 | 1.41775 | 46.47084 |
May | 508.00000 | 27.00046 | 29.01166 | 0.46267 | 9.51476 |
June | 496.00000 | 27.00170 | 29.55972 | 0.70969 | 15.62998 |
July | 497.00000 | 27.00555 | 30.17987 | 0.94713 | 23.98209 |
August | 514.00000 | 27.00688 | 28.43058 | 1.12038 | 31.47118 |
September | 485.00000 | 27.00050 | 31.04811 | 0.52970 | 10.96004 |
October | 502.00000 | 27.00045 | 27.02663 | 1.21906 | 36.19209 |
November | 489.00000 | 27.00020 | 22.43080 | 1.30908 | 40.74382 |
December | 497.00000 | 27.00003 | 19.42064 | 1.39693 | 45.35464 |
Annual Sum or Average | 5943.00000 | 27.00147 | 26.47758 | 1.04591 | 29.91991 |
Minimum of Months | 454.00000 | 27.00003 | 19.42064 | 0.46267 | 9.51476 |
Maximum of Months | 514.00000 | 27.00688 | 31.04811 | 1.41775 | 46.47084 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54462 | 14.03024 | 0.28229 | 7.95410 |
February | 454.00000 | 24.52472 | 14.43785 | 0.28735 | 7.15241 |
March | 514.00000 | 24.47177 | 15.70998 | 0.29671 | 7.14287 |
April | 485.00000 | 24.58603 | 19.20770 | 0.35195 | 8.03875 |
May | 508.00000 | 24.60446 | 22.93588 | -0.4650 | 10.73173 |
June | 496.00000 | 24.87424 | 33.57356 | -0.2866 | 10.10546 |
July | 497.00000 | 26.15600 | 47.66454 | 0.24261 | 18.95756 |
August | 514.00000 | 25.44517 | 37.13032 | -0.0652 | 12.50742 |
September | 485.00000 | 24.80717 | 30.11169 | -0.3254 | 9.23568 |
October | 502.00000 | 24.73630 | 21.08096 | 0.41304 | 9.30752 |
November | 489.00000 | 24.70070 | 16.63047 | 0.36538 | 8.42285 |
December | 497.00000 | 24.60654 | 13.92347 | 0.31289 | 7.51565 |
Annual Sum or Average | 5943.00000 | 24.84108 | 23.94513 | 0.11573 | 9.78140 |
Minimum of Months | 454.00000 | 24.47177 | 13.92347 | -0.4650 | 7.14287 |
Maximum of Months | 514.00000 | 26.15600 | 47.66454 | 0.41304 | 18.95756 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99468 | 13.76256 | 0.14232 | 6.01025 |
February | 454.00000 | 24.14074 | 15.54111 | 0.20989 | 6.15197 |
March | 514.00000 | 24.23779 | 16.60428 | 0.26177 | 6.59455 |
April | 485.00000 | 24.34016 | 19.86472 | 0.32608 | 7.46706 |
May | 508.00000 | 24.33246 | 23.86751 | -0.5267 | 11.41833 |
June | 496.00000 | 24.28450 | 32.24936 | -0.4416 | 9.51725 |
July | 497.00000 | 24.47630 | 35.91160 | -0.3224 | 7.82709 |
August | 514.00000 | 24.36599 | 31.69351 | -0.3898 | 8.71827 |
September | 485.00000 | 24.32782 | 31.60201 | -0.4510 | 9.86778 |
October | 502.00000 | 24.39404 | 22.78725 | 0.35232 | 7.91251 |
November | 489.00000 | 24.36927 | 18.13119 | 0.30390 | 7.17280 |
December | 497.00000 | 24.28610 | 15.06500 | 0.24951 | 6.53308 |
Annual Sum or Average | 5943.00000 | 24.29662 | 23.13848 | -0.0264 | 7.94649 |
Minimum of Months | 454.00000 | 23.99468 | 13.76256 | -0.5267 | 6.01025 |
Maximum of Months | 514.00000 | 24.47630 | 35.91160 | 0.35232 | 11.41833 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48821 | 15.54761 | -0.2463 | 7.70095 |
February | 454.00000 | 23.02889 | 17.44414 | -0.0890 | 6.42606 |
March | 514.00000 | 23.62842 | 18.53832 | 0.08049 | 5.82242 |
April | 485.00000 | 23.97779 | 21.62428 | 0.20487 | 6.11454 |
May | 508.00000 | 24.16766 | 24.80136 | -0.6186 | 13.56637 |
June | 496.00000 | 24.16214 | 32.96906 | -0.5239 | 11.02195 |
July | 497.00000 | 24.26758 | 36.90644 | -0.4530 | 9.68690 |
August | 514.00000 | 24.22681 | 32.32371 | -0.4980 | 10.45438 |
September | 485.00000 | 24.19424 | 32.45022 | -0.5335 | 11.42586 |
October | 502.00000 | 24.06872 | 24.58254 | 0.24639 | 6.42321 |
November | 489.00000 | 23.71090 | 20.26174 | 0.10730 | 5.80344 |
December | 497.00000 | 22.95895 | 17.12971 | -0.1106 | 6.57316 |
Annual Sum or Average | 5943.00000 | 23.74483 | 24.59194 | -0.2046 | 8.43999 |
Minimum of Months | 454.00000 | 22.48821 | 15.54761 | -0.6186 | 5.80344 |
Maximum of Months | 514.00000 | 24.26758 | 36.90644 | 0.24639 | 13.56637 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74450 | 16.40207 | -0.7003 | 17.90570 |
February | 454.00000 | 21.51272 | 18.94984 | -0.4791 | 12.17493 |
March | 514.00000 | 22.28207 | 20.32422 | -0.2672 | 9.16314 |
April | 485.00000 | 23.07884 | 23.34339 | -0.0287 | 6.62517 |
May | 508.00000 | 23.68952 | 25.64994 | -0.8016 | 20.79356 |
June | 496.00000 | 24.06580 | 33.04073 | -0.5576 | 12.17041 |
July | 497.00000 | 24.26051 | 36.79780 | -0.4484 | 9.73729 |
August | 514.00000 | 24.18521 | 32.45032 | -0.5142 | 10.98674 |
September | 485.00000 | 23.87707 | 33.26587 | -0.6613 | 15.90421 |
October | 502.00000 | 23.06296 | 26.63024 | -0.0181 | 6.31154 |
November | 489.00000 | 22.02720 | 22.27889 | -0.3235 | 9.85868 |
December | 497.00000 | 21.04780 | 18.47355 | -0.6003 | 15.87115 |
Annual Sum or Average | 5943.00000 | 22.82961 | 25.67216 | -0.4505 | 12.30291 |
Minimum of Months | 454.00000 | 20.74450 | 16.40207 | -0.8016 | 6.31154 |
Maximum of Months | 514.00000 | 24.26051 | 36.79780 | -0.0181 | 20.79356 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.32872 | 14.36785 | -0.5369 | 13.55301 |
February | 454.00000 | 22.10056 | 16.76296 | -0.3123 | 9.09409 |
March | 514.00000 | 22.95453 | 17.55856 | -0.0868 | 6.61642 |
April | 485.00000 | 23.70285 | 20.27176 | 0.13309 | 5.94010 |
May | 508.00000 | 23.94980 | 23.83810 | -0.6795 | 16.36965 |
June | 496.00000 | 24.26433 | 31.52002 | -0.4368 | 9.85196 |
July | 497.00000 | 24.61818 | 34.91654 | -0.2551 | 7.73064 |
August | 514.00000 | 24.37281 | 31.08133 | -0.3928 | 9.30779 |
September | 485.00000 | 24.04010 | 31.68555 | -0.5848 | 14.02187 |
October | 502.00000 | 23.62794 | 23.42349 | 0.12432 | 5.87607 |
November | 489.00000 | 22.89174 | 19.48544 | -0.0939 | 6.49245 |
December | 497.00000 | 22.01619 | 16.43182 | -0.3333 | 9.21344 |
Annual Sum or Average | 5943.00000 | 23.33105 | 23.48545 | -0.2885 | 9.51491 |
Minimum of Months | 454.00000 | 21.32872 | 14.36785 | -0.6795 | 5.87607 |
Maximum of Months | 514.00000 | 24.61818 | 34.91654 | 0.13309 | 16.36965 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.61384 | 14.12033 | -0.4656 | 12.82493 |
February | 454.00000 | 22.47511 | 16.22719 | -0.2117 | 9.02966 |
March | 514.00000 | 23.05486 | 17.07307 | -0.0352 | 7.20496 |
April | 485.00000 | 23.75331 | 19.95253 | 0.19163 | 7.29122 |
May | 508.00000 | 23.99372 | 23.31491 | -0.5843 | 14.63107 |
June | 496.00000 | 24.35393 | 31.17064 | -0.2968 | 9.38718 |
July | 497.00000 | 24.61888 | 34.67462 | -0.1194 | 7.94844 |
August | 514.00000 | 24.38522 | 30.80453 | -0.2755 | 8.78972 |
September | 485.00000 | 24.20923 | 31.07948 | -0.4482 | 12.21853 |
October | 502.00000 | 23.74734 | 22.84143 | 0.18481 | 6.82907 |
November | 489.00000 | 22.95354 | 19.23270 | -0.0698 | 6.81794 |
December | 497.00000 | 21.98960 | 16.43509 | -0.3403 | 9.75528 |
Annual Sum or Average | 5943.00000 | 23.43566 | 23.11837 | -0.2066 | 9.40108 |
Minimum of Months | 454.00000 | 21.61384 | 14.12033 | -0.5843 | 6.81794 |
Maximum of Months | 514.00000 | 24.61888 | 34.67462 | 0.19163 | 14.63107 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.06548 | 13.43775 | -0.3338 | 12.81973 |
February | 454.00000 | 22.93638 | 15.12011 | -0.0546 | 9.95497 |
March | 514.00000 | 23.20449 | 16.49085 | 0.03479 | 8.14657 |
April | 485.00000 | 23.73036 | 19.85825 | 0.19381 | 7.64474 |
May | 508.00000 | 23.87124 | 23.52147 | -0.6478 | 17.19342 |
June | 496.00000 | 24.26734 | 31.31513 | -0.3888 | 10.16374 |
July | 497.00000 | 24.63987 | 34.68363 | -0.1759 | 8.14614 |
August | 514.00000 | 24.54616 | 30.43359 | -0.2255 | 9.02794 |
September | 485.00000 | 24.29882 | 30.72539 | -0.3641 | 12.14872 |
October | 502.00000 | 23.92161 | 22.16778 | 0.28458 | 8.79225 |
November | 489.00000 | 23.38131 | 18.06868 | 0.08071 | 8.39577 |
December | 497.00000 | 22.54221 | 15.26834 | -0.1760 | 10.13505 |
Annual Sum or Average | 5943.00000 | 23.62153 | 22.63733 | -0.1493 | 10.22430 |
Minimum of Months | 454.00000 | 22.06548 | 13.43775 | -0.6478 | 7.64474 |
Maximum of Months | 514.00000 | 24.63987 | 34.68363 | 0.28458 | 17.19342 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.12779 | 13.62407 | -0.3276 | 10.36101 |
February | 454.00000 | 23.36403 | 14.87232 | 0.02645 | 7.58010 |
March | 514.00000 | 24.02788 | 15.42174 | 0.23307 | 7.21370 |
April | 485.00000 | 24.49879 | 18.47306 | 0.43785 | 9.96382 |
May | 508.00000 | 24.34306 | 22.68493 | -0.4199 | 11.12139 |
June | 496.00000 | 24.51737 | 30.70081 | -0.1900 | 7.82467 |
July | 497.00000 | 24.83225 | 34.21141 | 0.00615 | 8.16508 |
August | 514.00000 | 24.64324 | 30.10629 | -0.0871 | 7.64121 |
September | 485.00000 | 24.43644 | 30.42882 | -0.3325 | 10.01476 |
October | 502.00000 | 24.34580 | 21.53931 | 0.36426 | 8.53997 |
November | 489.00000 | 24.12573 | 17.11124 | 0.24703 | 7.23562 |
December | 497.00000 | 23.70557 | 14.13445 | 0.09831 | 6.72605 |
Annual Sum or Average | 5943.00000 | 24.08467 | 21.98716 | 0.00365 | 8.53517 |
Minimum of Months | 454.00000 | 22.12779 | 13.62407 | -0.4199 | 6.72605 |
Maximum of Months | 514.00000 | 24.83225 | 34.21141 | 0.43785 | 11.12139 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13425 | 14.42096 | -0.9074 | 24.29057 |
February | 454.00000 | 20.70065 | 17.47053 | -0.7037 | 17.18121 |
March | 514.00000 | 21.41685 | 19.20909 | -0.4750 | 11.90269 |
April | 485.00000 | 22.50285 | 22.57362 | -0.1649 | 7.30626 |
May | 508.00000 | 23.35617 | 25.09096 | -0.8998 | 25.11572 |
June | 496.00000 | 24.05329 | 32.14576 | -0.5408 | 12.16222 |
July | 497.00000 | 24.37112 | 35.49606 | -0.3869 | 9.21760 |
August | 514.00000 | 24.12868 | 31.63668 | -0.5272 | 11.87970 |
September | 485.00000 | 23.53914 | 32.96980 | -0.7773 | 20.98537 |
October | 502.00000 | 22.41871 | 25.89754 | -0.1695 | 7.08685 |
November | 489.00000 | 21.18608 | 21.05873 | -0.5258 | 13.17550 |
December | 497.00000 | 20.29438 | 17.04519 | -0.8138 | 21.19205 |
Annual Sum or Average | 5943.00000 | 22.35480 | 24.62494 | -0.5740 | 15.11778 |
Minimum of Months | 454.00000 | 20.13425 | 14.42096 | -0.9074 | 7.08685 |
Maximum of Months | 514.00000 | 24.37112 | 35.49606 | -0.1649 | 25.11572 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.30190 | 13.70453 | -0.8548 | 22.74355 |
February | 385.00000 | 21.31939 | 16.33603 | -0.5408 | 14.86532 |
March | 433.00000 | 22.05432 | 17.63781 | -0.3055 | 10.54785 |
April | 410.00000 | 23.13618 | 20.74413 | 0.02433 | 7.99348 |
May | 430.00000 | 23.64474 | 23.74464 | -0.7311 | 20.59887 |
June | 418.00000 | 24.35333 | 30.98163 | -0.3246 | 10.63118 |
July | 422.00000 | 24.65173 | 34.38270 | -0.1526 | 8.84616 |
August | 433.00000 | 24.39450 | 30.33686 | -0.3187 | 9.87226 |
September | 410.00000 | 24.01954 | 31.38816 | -0.5454 | 16.21069 |
October | 427.00000 | 23.03317 | 23.99160 | -0.0045 | 7.11483 |
November | 417.00000 | 21.73829 | 19.69622 | -0.3916 | 11.15879 |
December | 422.00000 | 20.44929 | 16.22623 | -0.7689 | 20.08765 |
Annual Sum or Average | 5034.00000 | 22.76572 | 23.29434 | -0.4095 | 13.38954 |
Minimum of Months | 385.00000 | 20.30190 | 13.70453 | -0.8548 | 7.11483 |
Maximum of Months | 433.00000 | 24.65173 | 34.38270 | 0.02433 | 22.74355 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.52151 | 13.17671 | -0.5011 | 16.45459 |
February | 454.00000 | 22.46991 | 15.17764 | -0.1857 | 12.33184 |
March | 514.00000 | 22.64713 | 17.13907 | -0.1036 | 10.01298 |
April | 485.00000 | 23.20772 | 20.93435 | 0.06586 | 8.28099 |
May | 508.00000 | 23.57893 | 24.11215 | -0.7513 | 21.47498 |
June | 496.00000 | 24.12476 | 31.69361 | -0.4555 | 11.96892 |
July | 497.00000 | 24.50673 | 34.95623 | -0.2533 | 9.13875 |
August | 514.00000 | 24.38845 | 30.61607 | -0.3030 | 10.13075 |
September | 485.00000 | 24.12609 | 31.17011 | -0.4197 | 14.50625 |
October | 502.00000 | 23.59197 | 23.12204 | 0.21156 | 9.23664 |
November | 489.00000 | 22.83866 | 18.53252 | -0.0593 | 10.13177 |
December | 497.00000 | 21.75570 | 15.30599 | -0.3985 | 14.33384 |
Annual Sum or Average | 5943.00000 | 23.23507 | 23.04243 | -0.2643 | 12.34520 |
Minimum of Months | 454.00000 | 21.52151 | 13.17671 | -0.7513 | 8.28099 |
Maximum of Months | 514.00000 | 24.50673 | 34.95623 | 0.21156 | 21.47498 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54981 | 14.15200 | -0.7810 | 20.29604 |
February | 454.00000 | 21.48306 | 16.55201 | -0.4815 | 13.70021 |
March | 514.00000 | 22.18230 | 18.02863 | -0.2616 | 9.90258 |
April | 485.00000 | 23.25580 | 21.13591 | 0.06225 | 7.60933 |
May | 508.00000 | 23.77699 | 24.00810 | -0.6605 | 18.86273 |
June | 496.00000 | 24.24854 | 31.50031 | -0.3631 | 10.30261 |
July | 497.00000 | 24.56999 | 34.88533 | -0.1897 | 8.69750 |
August | 514.00000 | 24.35375 | 30.80953 | -0.3228 | 9.52075 |
September | 485.00000 | 23.98028 | 31.75093 | -0.5414 | 15.81083 |
October | 502.00000 | 23.15257 | 24.27169 | 0.03710 | 7.18845 |
November | 489.00000 | 21.99811 | 19.82370 | -0.3116 | 10.31695 |
December | 497.00000 | 20.81290 | 16.52557 | -0.6628 | 17.30544 |
Annual Sum or Average | 5943.00000 | 22.87385 | 23.66171 | -0.3729 | 12.45504 |
Minimum of Months | 454.00000 | 20.54981 | 14.15200 | -0.7810 | 7.18845 |
Maximum of Months | 514.00000 | 24.56999 | 34.88533 | 0.06225 | 20.29604 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70636 | 14.46173 | -1.0788 | 31.79816 |
February | 454.00000 | 20.17208 | 17.62664 | -0.8866 | 23.81264 |
March | 514.00000 | 20.71880 | 19.57833 | -0.6879 | 17.61696 |
April | 485.00000 | 21.72317 | 23.41065 | -0.3737 | 11.06534 |
May | 508.00000 | 22.87169 | 25.65289 | -1.0808 | 32.96622 |
June | 496.00000 | 23.87731 | 32.40505 | -0.5994 | 14.69316 |
July | 497.00000 | 24.28812 | 35.58327 | -0.4071 | 10.13913 |
August | 514.00000 | 23.97153 | 31.97141 | -0.5779 | 13.93092 |
September | 485.00000 | 23.09530 | 33.66766 | -0.9390 | 28.41555 |
October | 502.00000 | 21.53283 | 26.77883 | -0.4080 | 11.04271 |
November | 489.00000 | 20.39454 | 21.69829 | -0.7703 | 20.42106 |
December | 497.00000 | 19.89001 | 17.18962 | -0.9879 | 28.06419 |
Annual Sum or Average | 5943.00000 | 21.86765 | 25.04257 | -0.7324 | 20.30767 |
Minimum of Months | 454.00000 | 19.70636 | 14.46173 | -1.0808 | 10.13913 |
Maximum of Months | 514.00000 | 24.28812 | 35.58327 | -0.3737 | 32.96622 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97600 | 14.42509 | -0.9894 | 28.01257 |
February | 454.00000 | 20.79853 | 17.12349 | -0.7066 | 19.12846 |
March | 514.00000 | 21.51936 | 18.58199 | -0.4666 | 14.07753 |
April | 485.00000 | 22.57948 | 21.74639 | -0.1231 | 9.92745 |
May | 508.00000 | 23.34952 | 24.31545 | -0.8345 | 24.61426 |
June | 496.00000 | 24.20592 | 31.32033 | -0.3523 | 11.51260 |
July | 497.00000 | 24.52089 | 34.73639 | -0.1597 | 8.87834 |
August | 514.00000 | 24.24580 | 30.90281 | -0.3355 | 10.48585 |
September | 485.00000 | 23.71343 | 32.11351 | -0.6468 | 19.91697 |
October | 502.00000 | 22.43510 | 25.15993 | -0.1690 | 9.00232 |
November | 489.00000 | 20.92177 | 21.17697 | -0.6265 | 16.80249 |
December | 497.00000 | 20.05348 | 17.12658 | -0.9261 | 25.84167 |
Annual Sum or Average | 5943.00000 | 22.37257 | 24.09920 | -0.5271 | 16.49882 |
Minimum of Months | 454.00000 | 19.97600 | 14.42509 | -0.9894 | 8.87834 |
Maximum of Months | 514.00000 | 24.52089 | 34.73639 | -0.1231 | 28.01257 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89376 | 13.57833 | -0.7126 | 21.71653 |
February | 454.00000 | 21.88364 | 15.63910 | -0.3783 | 15.51570 |
March | 514.00000 | 21.99216 | 17.64712 | -0.3056 | 13.38056 |
April | 485.00000 | 22.59886 | 21.66459 | -0.1078 | 10.54989 |
May | 508.00000 | 23.19832 | 24.58129 | -0.9025 | 27.86252 |
June | 496.00000 | 23.95743 | 31.92679 | -0.5115 | 14.51848 |
July | 497.00000 | 24.42212 | 35.05789 | -0.2740 | 10.22307 |
August | 514.00000 | 24.25833 | 30.91049 | -0.3454 | 11.74995 |
September | 485.00000 | 23.80135 | 31.71227 | -0.5470 | 19.42978 |
October | 502.00000 | 22.95824 | 23.78215 | 0.02637 | 10.24698 |
November | 489.00000 | 22.04070 | 19.33354 | -0.3011 | 13.14191 |
December | 497.00000 | 20.99112 | 16.00746 | -0.6408 | 19.94218 |
Annual Sum or Average | 5943.00000 | 22.75646 | 23.53324 | -0.4177 | 15.70266 |
Minimum of Months | 454.00000 | 20.89376 | 13.57833 | -0.9025 | 10.22307 |
Maximum of Months | 514.00000 | 24.42212 | 35.05789 | 0.02637 | 27.86252 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11698 | 14.31314 | -0.9465 | 26.78122 |
February | 454.00000 | 20.95747 | 16.83256 | -0.6503 | 18.22133 |
March | 514.00000 | 21.53248 | 18.47895 | -0.4523 | 13.74120 |
April | 485.00000 | 22.62438 | 21.89536 | -0.1090 | 9.53737 |
May | 508.00000 | 23.40119 | 24.46383 | -0.8044 | 25.00101 |
June | 496.00000 | 24.10926 | 31.69353 | -0.4105 | 12.34974 |
July | 497.00000 | 24.50030 | 34.97396 | -0.2065 | 9.54714 |
August | 514.00000 | 24.24839 | 31.08085 | -0.3582 | 10.91546 |
September | 485.00000 | 23.62949 | 32.33960 | -0.6724 | 21.44190 |
October | 502.00000 | 22.43435 | 25.03885 | -0.1579 | 9.15794 |
November | 489.00000 | 21.21557 | 20.60074 | -0.5381 | 15.27273 |
December | 497.00000 | 20.29333 | 16.95517 | -0.8432 | 23.43137 |
Annual Sum or Average | 5943.00000 | 22.43359 | 24.09634 | -0.5119 | 16.27075 |
Minimum of Months | 454.00000 | 20.11698 | 14.31314 | -0.9465 | 9.15794 |
Maximum of Months | 514.00000 | 24.50030 | 34.97396 | -0.1090 | 26.78122 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.235282E+09 | 6321.31 | 02-JAN-14:10 | 39.11 | 0.195930E+10 | 0.00 | 0.219458E+10 | 0.44 | 8.43 | 02-JAN-15:10 | 0.00 | 0.00 |
February | 0.399316E+10 | 80912.16 | 27-FEB-15:30 | 105.65 | 0.334876E+11 | 0.00 | 0.374808E+11 | 1.31 | 8.68 | 27-FEB-12:20 | 0.00 | 0.00 |
March | 0.747483E+10 | 54408.05 | 28-MAR-16:00 | 168.35 | 0.632157E+11 | 0.00 | 0.706905E+11 | 1.89 | 8.68 | 14-MAR-13:20 | 0.00 | 0.00 |
April | 0.137188E+11 | 160257.98 | 06-APR-16:00 | 209.41 | 0.112860E+12 | 0.00 | 0.126579E+12 | 2.42 | 8.68 | 25-APR-15:20 | 0.00 | 0.00 |
May | 0.260149E+11 | 161673.80 | 18-MAY-15:10 | 292.56 | 0.211929E+12 | 0.00 | 0.237944E+12 | 3.26 | 8.68 | 02-MAY-13:05 | 0.00 | 0.00 |
June | 0.662268E+11 | 165556.41 | 22-JUN-09:50 | 392.18 | 0.516602E+12 | 0.00 | 0.582829E+12 | 4.42 | 8.68 | 21-JUN-04:13 | 0.00 | 0.00 |
July | 0.102087E+12 | 167248.95 | 19-JUL-08:30 | 539.20 | 0.791774E+12 | 0.00 | 0.893860E+12 | 5.85 | 8.69 | 25-JUL-04:12 | 0.00 | 0.00 |
August | 0.900736E+11 | 163219.43 | 03-AUG-17:20 | 511.78 | 0.700152E+12 | 0.00 | 0.790225E+12 | 5.56 | 8.72 | 07-AUG-04:12 | 0.00 | 0.00 |
September | 0.493352E+11 | 181749.79 | 07-SEP-15:10 | 343.11 | 0.389745E+12 | 0.00 | 0.439080E+12 | 3.91 | 8.69 | 05-SEP-04:13 | 0.00 | 0.00 |
October | 0.231745E+11 | 162510.33 | 18-OCT-13:30 | 245.86 | 0.189192E+12 | 0.00 | 0.212367E+12 | 2.75 | 8.68 | 15-OCT-12:34 | 0.00 | 0.00 |
November | 0.752591E+10 | 74141.66 | 03-NOV-14:30 | 149.44 | 0.631480E+11 | 0.00 | 0.706739E+11 | 1.73 | 8.68 | 09-NOV-15:05 | 0.00 | 0.00 |
December | 0.765252E+09 | 14249.41 | 07-DEC-12:00 | 93.33 | 0.637934E+10 | 0.00 | 0.714460E+10 | 1.04 | 8.44 | 21-DEC-14:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390625E+12 | 3089.98 | 0.308044E+13 | 0.00 | 0.347107E+13 | 2.89 | 0.00 | 0.00 | ||||
Minimum of Months | 0.235282E+09 | 6321.31 | 39.11 | 0.195930E+10 | 0.00 | 0.219458E+10 | 0.44 | 8.43 | 0.00 | 0.00 | ||
Maximum of Months | 0.102087E+12 | 181749.79 | 539.20 | 0.791774E+12 | 0.00 | 0.893860E+12 | 5.85 | 8.72 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.203756E+10 | 100208.45 | 19-MAY-12:05 | 7.92 | 0.163116E+11 | 0.00 | 0.183491E+11 | 0.09 | 8.62 | 31-MAY-13:30 | 0.00 | 0.00 |
June | 0.197411E+11 | 164223.88 | 20-JUN-12:13 | 68.50 | 0.154890E+12 | 0.00 | 0.174631E+12 | 0.75 | 8.62 | 24-JUN-13:10 | 0.00 | 0.00 |
July | 0.398012E+11 | 161800.06 | 14-JUL-09:52 | 135.26 | 0.311168E+12 | 0.00 | 0.350969E+12 | 1.43 | 8.63 | 18-JUL-07:20 | 0.00 | 0.00 |
August | 0.343215E+11 | 137346.46 | 31-AUG-12:02 | 117.00 | 0.269122E+12 | 0.00 | 0.303443E+12 | 1.24 | 8.63 | 08-AUG-18:40 | 0.00 | 0.00 |
September | 0.104292E+11 | 181749.79 | 07-SEP-15:10 | 35.08 | 0.798507E+11 | 0.00 | 0.902799E+11 | 0.38 | 8.64 | 02-SEP-09:50 | 0.00 | 0.00 |
October | 0.633884E+09 | 142901.46 | 18-OCT-13:43 | 2.50 | 0.517898E+10 | 0.00 | 0.581287E+10 | 0.03 | 8.36 | 18-OCT-13:50 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106964E+12 | 366.26 | 0.836520E+12 | 0.00 | 0.943485E+12 | 0.33 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.398012E+11 | 181749.79 | 135.26 | 0.311168E+12 | 0.00 | 0.350969E+12 | 1.43 | 8.64 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.443964E+09 | 744.00 | 767.46 | 13-JAN-16:00 | 37488.96 | 13-JAN-16:30 | 18.59 | 18.33 | 17.03 |
February | 0.207787E+10 | 672.00 | 43776.24 | 27-FEB-13:50 | 81864.40 | 27-FEB-16:10 | 19.19 | 18.33 | 17.03 |
March | 0.283357E+10 | 744.00 | 4028.21 | 14-MAR-14:00 | 132434.75 | 15-MAR-18:50 | 19.74 | 18.33 | 17.03 |
April | 0.144418E+11 | 720.00 | 43776.24 | 01-APR-13:45 | 528323.31 | 07-APR-14:05 | 20.83 | 18.51 | 17.03 |
May | 0.219112E+11 | 744.00 | 43776.24 | 02-MAY-11:40 | 246220.37 | 20-MAY-17:03 | 19.59 | 18.90 | 17.03 |
June | 0.509062E+11 | 720.00 | 43776.24 | 01-JUN-15:00 | 498437.70 | 20-JUN-19:00 | 22.95 | 20.78 | 17.03 |
July | 0.816148E+11 | 744.00 | 43776.24 | 01-JUL-00:03 | 654976.35 | 19-JUL-10:50 | 28.93 | 23.88 | 17.03 |
August | 0.795670E+11 | 744.00 | 43776.24 | 01-AUG-00:10 | 757832.91 | 08-AUG-12:10 | 29.49 | 23.19 | 17.03 |
September | 0.394891E+11 | 720.00 | 43776.24 | 01-SEP-00:05 | 328565.67 | 07-SEP-16:00 | 21.02 | 20.05 | 17.02 |
October | 0.127763E+11 | 744.00 | 43776.24 | 12-OCT-10:50 | 303943.62 | 18-OCT-15:00 | 19.66 | 18.54 | 17.03 |
November | 0.373335E+10 | 720.00 | 28809.41 | 17-NOV-17:00 | 134218.28 | 17-NOV-17:00 | 19.73 | 18.33 | 17.03 |
December | 0.285483E+10 | 744.00 | 4157.88 | 10-DEC-02:00 | 153394.02 | 08-DEC-20:10 | 20.05 | 18.33 | 17.03 |
Annual Sum or Average | 0.312650E+12 | 8760.00 | 21.67 | 19.64 | 17.03 | ||||
Minimum of Months | 0.443964E+09 | 672.00 | 767.46 | 37488.96 | 18.59 | 18.33 | 17.02 | ||
Maximum of Months | 0.816148E+11 | 744.00 | 43776.24 | 757832.91 | 29.49 | 23.88 | 17.03 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 207215.93 | 03-JAN-15:50 | 20.94 | 20.94 | 0.34 |
February | 5024440.56 | 9.67 | 297.32 | 27-FEB-15:30 | 731590.79 | 27-FEB-15:30 | 21.05 | 20.98 | 2.89 |
March | 10832777.96 | 46.17 | 157.92 | 14-MAR-13:30 | 531685.51 | 28-MAR-16:00 | 20.99 | 20.86 | 5.40 |
April | 55357972.73 | 70.34 | 1805.91 | 06-APR-16:00 | 1154916.46 | 06-APR-16:00 | 21.23 | 21.00 | 8.63 |
May | 0.278120E+09 | 142.90 | 15206.52 | 19-MAY-14:00 | 1190365.02 | 18-MAY-16:00 | 21.46 | 21.03 | 14.61 |
June | 0.259799E+10 | 289.01 | 15206.52 | 06-JUN-13:55 | 1187773.97 | 26-JUN-09:40 | 22.19 | 21.09 | 25.12 |
July | 0.482407E+10 | 418.33 | 15206.52 | 01-JUL-12:20 | 1189621.73 | 12-JUL-18:30 | 22.80 | 21.15 | 33.34 |
August | 0.231959E+10 | 358.69 | 15206.52 | 01-AUG-12:40 | 1202849.29 | 03-AUG-17:20 | 22.54 | 21.08 | 30.09 |
September | 0.176381E+10 | 237.60 | 15206.52 | 02-SEP-10:20 | 1229654.48 | 07-SEP-15:10 | 21.99 | 21.17 | 20.95 |
October | 0.128539E+09 | 124.48 | 2024.13 | 18-OCT-13:20 | 1202148.29 | 18-OCT-13:30 | 21.42 | 21.04 | 12.61 |
November | 14013009.49 | 47.50 | 306.84 | 03-NOV-14:30 | 685188.04 | 03-NOV-14:30 | 21.11 | 20.98 | 5.75 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 207163.73 | 12-DEC-13:30 | 21.00 | 20.98 | 1.14 |
Annual Sum or Average | 0.119973E+11 | 1744.68 | 21.57 | 21.02 | 13.47 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 207163.73 | 20.94 | 20.86 | 0.34 | ||
Maximum of Months | 0.482407E+10 | 418.33 | 15206.52 | 1229654.48 | 22.80 | 21.17 | 33.34 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.94 | 20.94 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.05 | 21.05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.99 | 20.99 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.23 | 21.23 | 0.00 |
May | 58002042.68 | 6.08 | 15206.52 | 19-MAY-14:00 | 1058395.59 | 19-MAY-14:00 | 21.46 | 21.43 | 0.43 |
June | 0.122573E+10 | 60.33 | 15206.52 | 06-JUN-14:10 | 1083591.91 | 29-JUN-10:30 | 22.19 | 21.85 | 4.44 |
July | 0.263863E+10 | 123.54 | 15206.52 | 10-JUL-14:30 | 1162554.04 | 13-JUL-18:32 | 22.80 | 22.12 | 8.71 |
August | 0.116743E+10 | 101.25 | 15206.52 | 05-AUG-12:50 | 1086274.77 | 04-AUG-11:20 | 22.54 | 21.99 | 7.22 |
September | 0.840456E+09 | 32.75 | 15206.52 | 02-SEP-10:40 | 1229654.48 | 07-SEP-15:10 | 21.99 | 21.80 | 2.39 |
October | 15187449.00 | 2.33 | 1808.03 | 18-OCT-13:43 | 997282.76 | 18-OCT-13:43 | 21.42 | 21.41 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.11 | 21.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.00 | 21.00 | 0.00 |
Annual Sum or Average | 0.594545E+10 | 326.29 | 21.57 | 21.41 | 1.97 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 20.94 | 0.00 | ||
Maximum of Months | 0.263863E+10 | 123.54 | 15206.52 | 1229654.48 | 22.80 | 22.12 | 8.71 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.851279E+12 | 0.00 | 566.81 | 1997492.73 | 09-JAN-07:03 | 0.00 | 37.42 | 70.21 | 2.06 | 0.00 | 0.12 | 0.74 | 09-JAN-07:03 |
February | 0.445005E+12 | 0.00 | 412.85 | 1766035.39 | 06-FEB-05:01 | 0.00 | 32.76 | 61.80 | 1.05 | 0.00 | 0.07 | 0.66 | 06-FEB-05:01 |
March | 0.273232E+12 | 0.00 | 409.03 | 1610030.13 | 06-MAR-06:01 | 0.00 | 29.80 | 57.66 | 0.53 | 0.00 | 0.04 | 0.60 | 06-MAR-06:01 |
April | 0.855770E+11 | 0.00 | 240.99 | 1199794.39 | 29-APR-05:01 | 0.00 | 25.84 | 44.24 | 0.15 | 0.00 | 0.01 | 0.45 | 29-APR-05:01 |
May | 0.528165E+11 | 0.00 | 163.89 | 1210289.50 | 09-MAY-05:01 | 0.00 | 25.07 | 37.16 | 0.09 | 0.00 | 0.01 | 0.45 | 09-MAY-05:01 |
June | 0.324529E+10 | 0.00 | 33.52 | 173230.01 | 16-JUN-07:00 | 0.00 | 23.38 | 26.10 | 0.01 | 0.00 | 0.00 | 0.06 | 16-JUN-07:00 |
July | 14029706.61 | 0.00 | 1.92 | 2598.73 | 05-JUL-06:11 | 0.00 | 23.82 | 23.97 | 0.00 | 0.00 | 0.00 | 0.00 | 05-JUL-06:11 |
August | 0.931501E+09 | 0.00 | 18.47 | 343416.23 | 17-AUG-13:20 | 0.00 | 24.23 | 25.63 | 0.00 | 0.00 | 0.00 | 0.13 | 17-AUG-13:20 |
September | 0.160263E+11 | 0.00 | 93.25 | 407971.39 | 19-SEP-13:10 | 0.00 | 24.09 | 31.46 | 0.03 | 0.00 | 0.00 | 0.15 | 19-SEP-13:10 |
October | 0.622543E+11 | 0.00 | 212.84 | 1331680.98 | 10-OCT-04:01 | 0.00 | 25.32 | 41.12 | 0.11 | 0.00 | 0.01 | 0.49 | 10-OCT-04:01 |
November | 0.208886E+12 | 0.00 | 367.65 | 1308623.02 | 30-NOV-05:01 | 0.00 | 29.18 | 55.34 | 0.40 | 0.00 | 0.03 | 0.49 | 30-NOV-05:01 |
December | 0.535799E+12 | 0.00 | 531.62 | 1572169.23 | 26-DEC-06:01 | 0.00 | 34.80 | 67.74 | 1.16 | 0.00 | 0.07 | 0.58 | 26-DEC-06:01 |
Annual Sum or Average | 0.253507E+13 | 0.00 | 3052.83 | 0.00 | 27.96 | 45.13 | 0.46 | 0.00 | 0.03 | ||||
Minimum of Months | 14029706.61 | 0.00 | 1.92 | 2598.73 | 0.00 | 23.38 | 23.97 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.851279E+12 | 0.00 | 566.81 | 1997492.73 | 0.00 | 37.42 | 70.21 | 2.06 | 0.00 | 0.12 | 0.74 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.59 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.19 | 19.19 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.74 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.83 | 20.83 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.59 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 22.95 | 22.95 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 28.93 | 28.93 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 29.49 | 29.49 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 21.02 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.66 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.73 | 19.73 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.05 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 21.67 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 | 29.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.168075E+10 | 0.00 | 28.00 | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50026.59 | 02-JAN-14:10 | 50026.59 | 02-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.500525E+10 | 0.00 | 82.26 | 0.500525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59442.49 | 28-FEB-15:50 | 59442.49 | 28-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.606236E+10 | 0.00 | 98.02 | 0.606236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56374.96 | 01-MAR-16:10 | 56374.96 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 |
April | 0.893683E+10 | 0.00 | 137.47 | 0.893683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84125.88 | 06-APR-16:00 | 84125.88 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.192438E+11 | 0.00 | 205.58 | 0.192438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112862.12 | 19-MAY-15:20 | 112862.12 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.620964E+11 | 0.00 | 364.26 | 0.617413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145293.47 | 21-JUN-12:45 | 139022.28 | 26-JUN-10:25 | 0.00 | 0.00 | 0.00 |
July | 0.109701E+12 | 0.00 | 507.45 | 0.108903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 153443.32 | 19-JUL-09:30 | 153000.37 | 25-JUL-17:06 | 0.00 | 0.00 | 0.00 |
August | 0.959222E+11 | 0.00 | 478.63 | 0.959218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152304.71 | 10-AUG-12:43 | 152304.71 | 10-AUG-12:43 | 0.00 | 0.00 | 0.00 |
September | 0.422725E+11 | 0.00 | 294.82 | 0.405609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188702.78 | 07-SEP-15:10 | 134319.77 | 01-SEP-10:53 | 0.00 | 0.00 | 0.00 |
October | 0.165245E+11 | 0.00 | 171.88 | 0.165245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106078.93 | 18-OCT-13:43 | 106078.93 | 18-OCT-13:43 | 0.00 | 0.00 | 0.00 |
November | 0.845911E+10 | 0.00 | 100.04 | 0.845911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68189.04 | 03-NOV-14:00 | 68189.04 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.498470E+10 | 0.00 | 80.25 | 0.498470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46551.94 | 07-DEC-14:10 | 46551.94 | 07-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380889E+12 | 0.00 | 2548.66 | 0.378024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.168075E+10 | 0.00 | 28.00 | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46551.94 | 46551.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109701E+12 | 0.00 | 507.45 | 0.108903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 188702.78 | 153000.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 28319.24 | 0.00 | 12.94 | 28319.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 02-JAN-06:01 | 1.31 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.259507E+11 | 0.00 | 47.07 | 0.259507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 545336.68 | 27-FEB-15:30 | 545336.68 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.532920E+11 | 0.00 | 94.54 | 0.532920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 433546.38 | 28-MAR-16:00 | 433546.38 | 28-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.901903E+11 | 0.00 | 133.84 | 0.901903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 691506.27 | 06-APR-16:00 | 691506.27 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.175443E+12 | 0.00 | 212.72 | 0.175443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1127732.88 | 19-MAY-15:20 | 1127732.88 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.511067E+12 | 0.00 | 340.28 | 0.508449E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1349295.08 | 21-JUN-12:45 | 1247550.30 | 22-JUN-10:13 | 0.00 | 0.00 | 0.00 |
July | 0.848319E+12 | 0.00 | 429.07 | 0.844861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1430663.28 | 25-JUL-16:36 | 1430663.28 | 25-JUL-16:36 | 0.00 | 0.00 | 0.00 |
August | 0.740113E+12 | 0.00 | 399.93 | 0.740113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1395100.58 | 10-AUG-12:23 | 1395100.58 | 10-AUG-12:23 | 0.00 | 0.00 | 0.00 |
September | 0.362161E+12 | 0.00 | 280.64 | 0.347767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1683755.86 | 07-SEP-14:35 | 1111405.01 | 03-SEP-15:51 | 0.00 | 0.00 | 0.00 |
October | 0.159021E+12 | 0.00 | 200.74 | 0.159021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 904207.79 | 18-OCT-15:20 | 904207.79 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.517635E+11 | 0.00 | 100.88 | 0.517635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 501246.71 | 03-NOV-14:05 | 501246.71 | 03-NOV-14:05 | 0.00 | 0.00 | 0.00 |
December | 0.419038E+09 | 0.00 | 15.66 | 0.419038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78950.72 | 07-DEC-12:00 | 78950.72 | 07-DEC-12:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301774E+13 | 0.00 | 2268.31 | 0.299727E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 28319.24 | 0.00 | 12.94 | 28319.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 1.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.848319E+12 | 0.00 | 429.07 | 0.844861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1683755.86 | 1430663.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.905366E+09 | 0.00 | 21.62 | 0.905366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27231.11 | 28-FEB-16:10 | 27231.11 | 28-FEB-16:10 | 0.00 | 0.00 | 0.00 |
March | 0.193020E+10 | 0.00 | 41.17 | 0.193020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38203.41 | 28-MAR-16:00 | 38203.41 | 28-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.656492E+10 | 0.00 | 92.03 | 0.656492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69169.20 | 06-APR-16:00 | 69169.20 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.164679E+11 | 0.00 | 170.16 | 0.164679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131823.06 | 19-MAY-14:40 | 131823.06 | 19-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.556772E+11 | 0.00 | 329.63 | 0.553686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157735.51 | 21-JUN-12:32 | 147209.74 | 21-JUN-12:32 | 0.00 | 0.00 | 0.00 |
July | 0.932269E+11 | 0.00 | 427.64 | 0.929026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168589.02 | 25-JUL-16:56 | 168589.02 | 25-JUL-16:56 | 0.00 | 0.00 | 0.00 |
August | 0.791588E+11 | 0.00 | 387.88 | 0.791588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161484.64 | 10-AUG-12:55 | 161484.64 | 10-AUG-12:55 | 0.00 | 0.00 | 0.00 |
September | 0.349673E+11 | 0.00 | 248.05 | 0.335355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198972.19 | 07-SEP-15:10 | 131235.59 | 03-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.824500E+10 | 0.00 | 114.63 | 0.824500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91834.08 | 18-OCT-15:10 | 91834.08 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.115887E+10 | 0.00 | 39.87 | 0.115887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35720.10 | 03-NOV-15:30 | 35720.10 | 03-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 58897.10 | 0.00 | 0.20 | 58897.10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.34 | 04-DEC-05:11 | 631.34 | 04-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298302E+12 | 0.00 | 1872.87 | 0.296238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.932269E+11 | 0.00 | 427.64 | 0.929026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198972.19 | 168589.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2165872.57 | 0.00 | 0.83 | 2165872.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1505.02 | 13-JAN-15:00 | 1505.02 | 13-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.585109E+09 | 0.00 | 17.17 | 0.585109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30669.61 | 27-FEB-15:00 | 30669.61 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.259040E+09 | 0.00 | 18.00 | 0.259040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9693.10 | 29-MAR-14:00 | 9693.10 | 29-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.452755E+10 | 0.00 | 80.33 | 0.452755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49244.17 | 07-APR-14:00 | 49244.17 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.134114E+11 | 0.00 | 179.35 | 0.133785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57774.38 | 19-MAY-15:00 | 57774.38 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.316774E+11 | 0.00 | 237.73 | 0.313985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81456.70 | 22-JUN-10:13 | 77239.90 | 24-JUN-14:05 | 0.00 | 0.00 | 0.00 |
July | 0.374466E+11 | 0.00 | 228.53 | 0.374064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84133.64 | 31-JUL-15:35 | 84133.64 | 31-JUL-15:35 | 0.00 | 0.00 | 0.00 |
August | 0.409388E+11 | 0.00 | 265.86 | 0.409331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83099.37 | 09-AUG-18:15 | 83099.37 | 09-AUG-18:15 | 0.00 | 0.00 | 0.00 |
September | 0.243872E+11 | 0.00 | 198.02 | 0.231250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102559.36 | 07-SEP-14:35 | 77288.23 | 01-SEP-11:10 | 0.00 | 0.00 | 0.00 |
October | 0.770630E+10 | 0.00 | 93.41 | 0.770630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68614.62 | 18-OCT-13:43 | 68614.62 | 18-OCT-13:43 | 0.00 | 0.00 | 0.00 |
November | 0.326130E+09 | 0.00 | 14.86 | 0.326130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25171.65 | 17-NOV-07:11 | 25171.65 | 17-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161268E+12 | 0.00 | 1334.09 | 0.159648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.409388E+11 | 0.00 | 265.86 | 0.409331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102559.36 | 84133.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.929632E+10 | 0.515780E+10 | 744.00 | 0.812160E+10 | 0.117472E+10 | 0.00 | 0.02 | 03-JAN-14:50 | 0.02 | 10-JAN-22:01 | 5354.27 | 03-JAN-14:50 | 4854.58 | 03-JAN-15:00 | 511.02 | 22-JAN-14:00 | 2418.28 | 03-JAN-14:50 | 0.00 |
February | 0.133877E+11 | 0.610361E+10 | 672.00 | 0.119159E+11 | 0.147178E+10 | 0.00 | 0.03 | 22-FEB-19:00 | 0.02 | 01-FEB-08:10 | 5993.46 | 22-FEB-19:00 | 5143.89 | 13-FEB-05:22 | 934.77 | 22-FEB-20:00 | 2620.59 | 22-FEB-19:00 | 0.00 |
March | 0.147364E+11 | 0.702059E+10 | 744.00 | 0.141166E+11 | 0.619793E+09 | 0.00 | 0.03 | 31-MAR-23:10 | 0.02 | 06-MAR-09:05 | 6532.19 | 31-MAR-23:10 | 5498.27 | 31-MAR-23:10 | 1095.25 | 01-MAR-00:10 | 2934.64 | 31-MAR-23:10 | 0.00 |
April | 0.570053E+11 | 0.193167E+11 | 720.00 | 0.547926E+11 | 0.221268E+10 | 0.00 | 0.78 | 07-APR-14:00 | 0.02 | 30-APR-23:20 | 306725.97 | 07-APR-14:00 | 306725.97 | 07-APR-14:00 | 16498.93 | 24-APR-11:00 | 98952.97 | 07-APR-14:00 | 0.00 |
May | 0.175753E+11 | 0.801520E+10 | 729.59 | 0.163862E+11 | 0.118916E+10 | 0.00 | 0.35 | 19-MAY-15:00 | 0.00 | 04-MAY-18:00 | 144886.87 | 19-MAY-13:50 | 138390.66 | 19-MAY-16:00 | 9365.17 | 19-MAY-12:30 | 49270.81 | 20-MAY-16:00 | 0.00 |
June | 0.128505E+12 | 0.424267E+11 | 641.32 | 0.116170E+12 | 0.123349E+11 | 0.00 | 0.69 | 20-JUN-18:50 | 0.00 | 17-JUN-24:00 | 334317.54 | 20-JUN-18:50 | 233671.79 | 23-JUN-15:50 | 113974.40 | 20-JUN-20:00 | 94883.38 | 20-JUN-18:50 | 0.00 |
July | 0.422146E+12 | 0.132776E+12 | 678.02 | 0.380236E+12 | 0.419104E+11 | 0.00 | 0.87 | 19-JUL-10:50 | 0.00 | 03-JUL-04:53 | 427442.70 | 19-JUL-10:50 | 327281.29 | 17-JUL-16:00 | 140205.64 | 18-JUL-20:00 | 134025.20 | 17-JUL-16:00 | 0.00 |
August | 0.525113E+12 | 0.160648E+12 | 732.76 | 0.483889E+12 | 0.412236E+11 | 0.00 | 1.00 | 08-AUG-12:00 | 0.01 | 01-AUG-04:00 | 483446.55 | 08-AUG-12:00 | 418013.86 | 07-AUG-16:00 | 112868.49 | 01-AUG-01:00 | 161502.09 | 05-AUG-16:00 | 0.00 |
September | 0.454691E+11 | 0.174096E+11 | 642.27 | 0.414661E+11 | 0.400299E+10 | 0.00 | 0.46 | 07-SEP-16:00 | 0.00 | 24-SEP-10:53 | 222638.67 | 07-SEP-16:00 | 143974.79 | 01-SEP-13:10 | 92167.07 | 07-SEP-16:00 | 62429.64 | 07-SEP-16:00 | 0.00 |
October | 0.220628E+11 | 0.908020E+10 | 743.50 | 0.205518E+11 | 0.151094E+10 | 0.00 | 0.45 | 18-OCT-14:00 | 0.01 | 01-OCT-01:10 | 175294.15 | 18-OCT-15:00 | 175294.15 | 18-OCT-15:00 | 942.99 | 14-OCT-08:50 | 58144.63 | 18-OCT-14:00 | 0.00 |
November | 0.147836E+11 | 0.692906E+10 | 720.00 | 0.140190E+11 | 0.764554E+09 | 0.00 | 0.10 | 17-NOV-17:00 | 0.02 | 18-NOV-13:05 | 34678.30 | 17-NOV-17:00 | 32958.31 | 17-NOV-17:00 | 1719.99 | 17-NOV-17:00 | 10709.82 | 17-NOV-17:00 | 0.00 |
December | 0.150009E+11 | 0.737992E+10 | 744.00 | 0.147473E+11 | 0.253608E+09 | 0.00 | 0.08 | 10-DEC-02:00 | 0.03 | 10-DEC-09:25 | 22829.09 | 10-DEC-02:00 | 22829.09 | 10-DEC-02:00 | 1389.35 | 19-DEC-19:20 | 8118.27 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.128508E+13 | 0.422263E+12 | 8511.47 | 0.117641E+13 | 0.108669E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.929632E+10 | 0.515780E+10 | 641.32 | 0.812160E+10 | 0.253608E+09 | 0.00 | 0.02 | 0.00 | 5354.27 | 4854.58 | 511.02 | 2418.28 | 0.00 | ||||||
Maximum of Months | 0.525113E+12 | 0.160648E+12 | 744.00 | 0.483889E+12 | 0.419104E+11 | 0.00 | 1.00 | 0.03 | 483446.55 | 418013.86 | 140205.64 | 161502.09 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.327360E+10 | 0.862204E+09 | 738.27 | 0.327328E+10 | 319122.54 | 0.00 | 0.30 | 29-JAN-16:42 | 0.00 | 08-JAN-03:32 | 2405.45 | 01-JAN-16:05 | 2398.92 | 01-JAN-16:10 | 15.04 | 02-JAN-07:03 | 597.82 | 29-JAN-16:42 | 0.00 |
February | 0.847012E+10 | 0.205086E+10 | 672.00 | 0.847012E+10 | -0.0 | 0.00 | 0.62 | 26-FEB-17:11 | 0.28 | 01-FEB-07:02 | 5234.71 | 26-FEB-17:24 | 5234.71 | 26-FEB-17:24 | 0.00 | 14-FEB-04:35 | 1225.43 | 26-FEB-17:11 | 0.00 |
March | 0.150718E+11 | 0.344338E+10 | 744.00 | 0.150718E+11 | 0.00 | 0.00 | 0.83 | 31-MAR-24:00 | 0.55 | 06-MAR-07:03 | 7532.30 | 31-MAR-24:00 | 7532.30 | 31-MAR-24:00 | 0.00 | 02-MAR-05:00 | 1636.60 | 31-MAR-24:00 | 0.00 |
April | 0.200687E+11 | 0.435912E+10 | 720.00 | 0.200598E+11 | 8917641.25 | 0.00 | 1.00 | 16-APR-17:11 | 0.31 | 30-APR-24:00 | 9069.24 | 22-APR-18:15 | 9069.24 | 22-APR-18:15 | 128.87 | 17-APR-16:10 | 2207.50 | 07-APR-14:00 | 0.00 |
May | 0.569934E+10 | 0.141535E+10 | 744.00 | 0.567399E+10 | 25354194.37 | 0.00 | 0.48 | 31-MAY-24:00 | 0.15 | 08-MAY-06:05 | 4120.07 | 31-MAY-24:00 | 4120.07 | 31-MAY-24:00 | 151.43 | 30-MAY-09:40 | 948.85 | 31-MAY-24:00 | 0.00 |
June | 0.109607E+11 | 0.269593E+10 | 720.00 | 0.108692E+11 | 91503146.92 | 0.00 | 0.67 | 30-JUN-23:20 | 0.41 | 17-JUN-06:10 | 6038.56 | 30-JUN-23:55 | 6021.89 | 30-JUN-24:00 | 333.36 | 06-JUN-16:40 | 1641.46 | 29-JUN-15:00 | 0.00 |
July | 0.167563E+11 | 0.435419E+10 | 744.00 | 0.166504E+11 | 0.105936E+09 | 0.00 | 0.90 | 16-JUL-18:41 | 0.63 | 08-JUL-06:11 | 7980.80 | 31-JUL-24:00 | 7980.80 | 31-JUL-24:00 | 361.40 | 03-JUL-16:50 | 2763.37 | 17-JUL-16:00 | 0.00 |
August | 0.215640E+11 | 0.531106E+10 | 744.00 | 0.214823E+11 | 81759347.32 | 0.00 | 1.00 | 04-AUG-17:40 | 0.31 | 31-AUG-24:00 | 9032.49 | 05-AUG-19:55 | 9032.49 | 05-AUG-19:55 | 401.12 | 22-AUG-15:50 | 3145.20 | 06-AUG-16:00 | 0.00 |
September | 0.579887E+10 | 0.148025E+10 | 720.00 | 0.571078E+10 | 88087434.56 | 0.00 | 0.46 | 04-SEP-17:41 | 0.18 | 19-SEP-06:30 | 3972.14 | 30-SEP-24:00 | 3972.14 | 30-SEP-24:00 | 352.45 | 07-SEP-15:30 | 1297.05 | 04-SEP-17:31 | 0.00 |
October | 0.106196E+11 | 0.245906E+10 | 744.00 | 0.106078E+11 | 11733230.05 | 0.00 | 0.66 | 31-OCT-24:00 | 0.38 | 10-OCT-06:03 | 5666.10 | 31-OCT-24:00 | 5666.10 | 31-OCT-24:00 | 110.67 | 25-OCT-11:00 | 1383.18 | 15-OCT-17:00 | 0.00 |
November | 0.147445E+11 | 0.332654E+10 | 720.00 | 0.147421E+11 | 2342729.70 | 0.00 | 0.75 | 12-NOV-16:25 | 0.55 | 27-NOV-07:03 | 6800.10 | 12-NOV-16:30 | 6800.10 | 12-NOV-16:30 | 76.30 | 17-NOV-17:05 | 1493.07 | 12-NOV-16:25 | 0.00 |
December | 0.196892E+11 | 0.440005E+10 | 744.00 | 0.196889E+11 | 307851.25 | 0.00 | 0.93 | 10-DEC-16:03 | 0.74 | 29-DEC-07:02 | 8484.54 | 10-DEC-16:07 | 8484.54 | 10-DEC-16:07 | 54.52 | 19-DEC-17:05 | 1838.55 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.152717E+12 | 0.361580E+11 | 8754.27 | 0.152300E+12 | 0.416261E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.327360E+10 | 0.862204E+09 | 672.00 | 0.327328E+10 | -0.0 | 0.00 | 0.30 | 0.00 | 2405.45 | 2398.92 | 0.00 | 597.82 | 0.00 | ||||||
Maximum of Months | 0.215640E+11 | 0.531106E+10 | 744.00 | 0.214823E+11 | 0.105936E+09 | 0.00 | 1.00 | 0.74 | 9069.24 | 9069.24 | 401.12 | 3145.20 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.967726E+10 | 0.276624E+10 | 516.07 | 0.967400E+10 | 3253861.41 | 0.00 | 0.25 | 19-JAN-16:50 | 0.00 | 02-JAN-07:03 | 18707.70 | 13-JAN-16:30 | 18707.70 | 13-JAN-16:30 | 97.68 | 01-JAN-15:45 | 4715.57 | 19-JAN-16:50 | 0.00 |
February | 0.618720E+11 | 0.153055E+11 | 672.00 | 0.618720E+11 | -0.0 | 0.00 | 0.58 | 26-FEB-17:22 | 0.14 | 06-FEB-04:02 | 46816.66 | 26-FEB-17:24 | 46816.66 | 26-FEB-17:24 | 0.00 | 08-FEB-18:40 | 11049.50 | 26-FEB-17:22 | 0.00 |
March | 0.128335E+12 | 0.296911E+11 | 744.00 | 0.128335E+12 | 0.00 | 0.00 | 0.77 | 31-MAR-23:40 | 0.38 | 06-MAR-07:03 | 66300.06 | 31-MAR-23:40 | 66300.06 | 31-MAR-23:40 | 0.00 | 17-MAR-02:00 | 14577.23 | 31-MAR-23:40 | 0.00 |
April | 0.183102E+12 | 0.400576E+11 | 720.00 | 0.183012E+12 | 90254491.01 | 0.00 | 1.00 | 16-APR-17:51 | 0.18 | 30-APR-24:00 | 85224.42 | 22-APR-18:12 | 85224.42 | 22-APR-18:12 | 1286.71 | 17-APR-16:10 | 21032.94 | 07-APR-14:00 | 0.00 |
May | 0.482843E+11 | 0.121120E+11 | 744.00 | 0.480358E+11 | 0.248521E+09 | 0.00 | 0.47 | 31-MAY-24:00 | 0.05 | 08-MAY-06:05 | 39096.69 | 31-MAY-24:00 | 39096.69 | 31-MAY-24:00 | 1467.53 | 30-MAY-09:40 | 9019.69 | 31-MAY-24:00 | 0.00 |
June | 0.101685E+12 | 0.251298E+11 | 720.00 | 0.100777E+12 | 0.907462E+09 | 0.00 | 0.68 | 30-JUN-23:20 | 0.35 | 17-JUN-06:10 | 58673.39 | 30-JUN-23:55 | 58509.85 | 30-JUN-24:00 | 3259.23 | 06-JUN-16:40 | 15717.25 | 28-JUN-19:00 | 0.00 |
July | 0.157647E+12 | 0.410847E+11 | 744.00 | 0.156594E+12 | 0.105312E+10 | 0.00 | 0.89 | 16-JUL-18:41 | 0.60 | 08-JUL-06:10 | 76582.56 | 31-JUL-24:00 | 76582.56 | 31-JUL-24:00 | 3535.07 | 03-JUL-16:50 | 25751.27 | 17-JUL-16:00 | 0.00 |
August | 0.203761E+12 | 0.503390E+11 | 744.00 | 0.202947E+12 | 0.813818E+09 | 0.00 | 1.00 | 04-AUG-17:50 | 0.27 | 31-AUG-24:00 | 86324.17 | 05-AUG-19:55 | 86047.70 | 05-AUG-19:55 | 3935.44 | 22-AUG-15:50 | 30226.32 | 06-AUG-16:00 | 0.00 |
September | 0.504107E+11 | 0.130102E+11 | 720.00 | 0.495482E+11 | 0.862473E+09 | 0.00 | 0.46 | 04-SEP-17:41 | 0.11 | 19-SEP-06:05 | 36361.35 | 30-SEP-23:30 | 36361.35 | 30-SEP-23:30 | 3504.00 | 07-SEP-15:30 | 12304.10 | 04-SEP-17:31 | 0.00 |
October | 0.913124E+11 | 0.213738E+11 | 744.00 | 0.911946E+11 | 0.117736E+09 | 0.00 | 0.61 | 15-OCT-17:00 | 0.26 | 10-OCT-06:03 | 49122.94 | 15-OCT-17:03 | 49122.94 | 15-OCT-17:03 | 1096.81 | 25-OCT-11:00 | 12672.76 | 15-OCT-17:00 | 0.00 |
November | 0.124202E+12 | 0.284185E+11 | 720.00 | 0.124178E+12 | 24004832.48 | 0.00 | 0.70 | 13-NOV-16:30 | 0.39 | 27-NOV-07:03 | 60914.69 | 03-NOV-16:00 | 60366.81 | 03-NOV-16:00 | 749.99 | 08-NOV-15:05 | 13243.78 | 13-NOV-16:30 | 0.00 |
December | 0.161958E+12 | 0.369026E+11 | 744.00 | 0.161955E+12 | 3837656.29 | 0.00 | 0.85 | 10-DEC-16:03 | 0.57 | 31-DEC-23:50 | 76412.30 | 06-DEC-16:10 | 76104.31 | 06-DEC-16:10 | 558.49 | 19-DEC-17:05 | 16068.29 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.132225E+13 | 0.316191E+12 | 8532.07 | 0.131812E+13 | 0.412448E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.967726E+10 | 0.276624E+10 | 516.07 | 0.967400E+10 | -0.0 | 0.00 | 0.25 | 0.00 | 18707.70 | 18707.70 | 0.00 | 4715.57 | 0.00 | ||||||
Maximum of Months | 0.203761E+12 | 0.503390E+11 | 744.00 | 0.202947E+12 | 0.105312E+10 | 0.00 | 1.00 | 0.60 | 86324.17 | 86047.70 | 3935.44 | 30226.32 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.222441E+09 | 66099338.03 | 157.02 | 0.222441E+09 | -0.0 | 0.00 | 0.23 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1817.41 | 13-JAN-16:30 | 1817.41 | 13-JAN-16:30 | 0.00 | 24-JAN-17:20 | 445.37 | 13-JAN-16:30 | 0.00 |
February | 0.448391E+10 | 0.113174E+10 | 651.92 | 0.448391E+10 | -0.0 | 0.00 | 0.53 | 26-FEB-17:22 | 0.00 | 04-FEB-02:32 | 4335.50 | 28-FEB-17:00 | 4335.50 | 28-FEB-17:00 | 0.00 | 13-FEB-19:50 | 1031.75 | 26-FEB-17:22 | 0.00 |
March | 0.110830E+11 | 0.260040E+10 | 744.00 | 0.110830E+11 | -0.0 | 0.00 | 0.74 | 28-MAR-17:50 | 0.20 | 06-MAR-04:12 | 6379.06 | 28-MAR-17:50 | 6379.06 | 28-MAR-17:50 | 0.00 | 01-MAR-06:00 | 1422.51 | 28-MAR-17:50 | 0.00 |
April | 0.171611E+11 | 0.379174E+10 | 719.17 | 0.171522E+11 | 8906000.14 | 0.00 | 0.97 | 16-APR-17:51 | 0.00 | 30-APR-23:20 | 8461.98 | 22-APR-18:14 | 8461.98 | 22-APR-18:14 | 127.79 | 17-APR-16:10 | 2115.34 | 07-APR-14:00 | 0.00 |
May | 0.413642E+10 | 0.104738E+10 | 708.75 | 0.411180E+10 | 24614683.70 | 0.00 | 0.46 | 31-MAY-23:40 | 0.00 | 01-MAY-00:10 | 3833.53 | 31-MAY-23:40 | 3833.53 | 31-MAY-23:40 | 144.63 | 30-MAY-09:40 | 887.38 | 31-MAY-23:40 | 0.00 |
June | 0.999107E+10 | 0.248312E+10 | 720.00 | 0.990039E+10 | 90676467.88 | 0.00 | 0.67 | 30-JUN-23:20 | 0.26 | 17-JUN-06:10 | 5879.02 | 30-JUN-23:45 | 5861.87 | 30-JUN-24:00 | 328.77 | 06-JUN-16:40 | 1603.86 | 28-JUN-19:00 | 0.00 |
July | 0.157426E+11 | 0.412103E+10 | 744.00 | 0.156374E+11 | 0.105212E+09 | 0.00 | 0.92 | 16-JUL-18:41 | 0.55 | 08-JUL-06:10 | 7657.19 | 31-JUL-24:00 | 7657.19 | 31-JUL-24:00 | 354.11 | 03-JUL-16:50 | 2650.69 | 17-JUL-16:00 | 0.00 |
August | 0.202598E+11 | 0.502934E+10 | 744.00 | 0.201786E+11 | 81278457.58 | 0.00 | 1.00 | 04-AUG-17:50 | 0.25 | 31-AUG-24:00 | 8828.84 | 05-AUG-19:55 | 8820.18 | 05-AUG-19:55 | 394.67 | 22-AUG-15:50 | 3077.11 | 06-AUG-16:00 | 0.00 |
September | 0.451520E+10 | 0.118392E+10 | 718.65 | 0.442995E+10 | 85248206.81 | 0.00 | 0.48 | 04-SEP-17:51 | 0.00 | 13-SEP-01:25 | 3684.21 | 04-SEP-17:54 | 3684.21 | 04-SEP-17:54 | 351.52 | 07-SEP-15:20 | 1325.26 | 04-SEP-17:21 | 0.00 |
October | 0.775339E+10 | 0.184233E+10 | 744.00 | 0.774186E+10 | 11531699.26 | 0.00 | 0.58 | 15-OCT-17:02 | 0.11 | 10-OCT-06:03 | 4734.99 | 15-OCT-17:03 | 4734.99 | 15-OCT-17:07 | 109.27 | 25-OCT-11:00 | 1272.15 | 18-OCT-16:00 | 0.00 |
November | 0.104028E+11 | 0.242200E+10 | 720.00 | 0.104005E+11 | 2344550.61 | 0.00 | 0.67 | 03-NOV-16:00 | 0.20 | 27-NOV-04:25 | 6017.60 | 03-NOV-16:00 | 5962.75 | 03-NOV-16:00 | 74.73 | 08-NOV-15:05 | 1301.56 | 03-NOV-16:00 | 0.00 |
December | 0.138727E+11 | 0.321920E+10 | 744.00 | 0.138724E+11 | 342891.71 | 0.00 | 0.82 | 06-DEC-16:10 | 0.40 | 31-DEC-23:52 | 7524.10 | 06-DEC-16:10 | 7494.58 | 06-DEC-16:10 | 53.63 | 19-DEC-17:05 | 1587.29 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.119625E+12 | 0.289383E+11 | 8115.50 | 0.119214E+12 | 0.410155E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.222441E+09 | 66099338.03 | 157.02 | 0.222441E+09 | -0.0 | 0.00 | 0.23 | 0.00 | 1817.41 | 1817.41 | 0.00 | 445.37 | 0.00 | ||||||
Maximum of Months | 0.202598E+11 | 0.502934E+10 | 744.00 | 0.201786E+11 | 0.105212E+09 | 0.00 | 1.00 | 0.55 | 8828.84 | 8820.18 | 394.67 | 3077.11 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.40 | 1019.55 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 16.91 | 769.21 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 74.14 | 625.64 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 140.72 | 449.31 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 278.42 | 323.85 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 455.30 | 202.44 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 491.06 | 170.59 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 356.34 | 195.23 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 206.61 | 301.50 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 70.31 | 462.73 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.27 | 670.44 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.46 | 908.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.21 | 176.40 | 507.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.46 | 170.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 491.06 | 1019.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.40 | 1019.55 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 16.91 | 769.21 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 74.14 | 625.64 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 140.72 | 449.31 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 278.42 | 323.85 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 455.30 | 202.44 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 491.06 | 170.59 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 356.34 | 195.23 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 206.61 | 301.50 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 70.31 | 462.73 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.27 | 670.44 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.46 | 908.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.20 | 176.40 | 507.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.46 | 170.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 491.06 | 1019.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.40 | 1019.55 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 16.91 | 769.21 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 74.14 | 625.64 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 140.72 | 449.31 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 278.42 | 323.85 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 455.30 | 202.44 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 491.06 | 170.59 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 356.34 | 195.23 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 206.61 | 301.50 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 70.31 | 462.73 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.27 | 670.44 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.46 | 908.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.21 | 176.40 | 507.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.46 | 170.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 491.06 | 1019.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.40 | 1019.55 | 0.00 | 0.00 | 0.00 |
February | 158.48 | 0.00 | 158.48 | 16.91 | 769.21 | 0.00 | 0.00 | 0.00 |
March | 257.44 | 0.00 | 257.44 | 74.14 | 625.64 | 0.00 | 0.00 | 0.00 |
April | 293.53 | 1.71 | 291.82 | 140.72 | 449.31 | 0.00 | 0.00 | 0.00 |
May | 385.48 | 22.84 | 362.64 | 278.42 | 323.85 | 0.00 | 0.00 | 0.00 |
June | 448.87 | 51.59 | 397.27 | 455.30 | 202.44 | 0.00 | 0.00 | 0.00 |
July | 410.07 | 38.41 | 371.66 | 491.06 | 170.59 | 0.00 | 0.00 | 0.00 |
August | 328.59 | 8.81 | 319.78 | 356.34 | 195.23 | 0.00 | 0.00 | 0.00 |
September | 246.09 | 0.09 | 246.00 | 206.61 | 301.50 | 0.00 | 0.00 | 0.00 |
October | 179.51 | 0.00 | 179.51 | 70.31 | 462.73 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.27 | 670.44 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.46 | 908.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.54 | 10.34 | 243.20 | 176.40 | 507.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.46 | 170.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.87 | 51.59 | 397.27 | 491.06 | 1019.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.24 | 0.00 | 112.24 | 1.40 | 1019.51 | 0.00 | 0.00 | 0.00 |
February | 158.47 | 0.00 | 158.47 | 16.91 | 769.18 | 0.00 | 0.00 | 0.00 |
March | 257.43 | 0.00 | 257.43 | 74.14 | 625.61 | 0.00 | 0.00 | 0.00 |
April | 293.52 | 1.71 | 291.81 | 140.71 | 449.29 | 0.00 | 0.00 | 0.00 |
May | 385.46 | 22.84 | 362.62 | 278.41 | 323.84 | 0.00 | 0.00 | 0.00 |
June | 448.85 | 51.59 | 397.26 | 455.29 | 202.43 | 0.00 | 0.00 | 0.00 |
July | 410.05 | 38.41 | 371.64 | 491.04 | 170.58 | 0.00 | 0.00 | 0.00 |
August | 328.57 | 8.81 | 319.77 | 356.33 | 195.23 | 0.00 | 0.00 | 0.00 |
September | 246.08 | 0.09 | 245.99 | 206.60 | 301.49 | 0.00 | 0.00 | 0.00 |
October | 179.50 | 0.00 | 179.50 | 70.31 | 462.71 | 0.00 | 0.00 | 0.00 |
November | 122.03 | 0.00 | 122.03 | 13.27 | 670.41 | 0.00 | 0.00 | 0.00 |
December | 94.12 | 0.00 | 94.12 | 0.46 | 908.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.53 | 10.34 | 243.20 | 176.39 | 507.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.12 | 0.00 | 94.12 | 0.46 | 170.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 448.85 | 51.59 | 397.26 | 491.04 | 1019.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 286.37 | 131.29 | 155.08 | 144.29 | 1039.17 | 0.00 | 0.00 | 0.00 |
February | 447.90 | 222.37 | 225.53 | 323.32 | 778.92 | 0.00 | 0.00 | 0.00 |
March | 602.25 | 249.19 | 353.05 | 479.22 | 644.42 | 0.00 | 0.00 | 0.00 |
April | 768.41 | 380.82 | 387.59 | 737.94 | 466.38 | 0.00 | 0.00 | 0.00 |
May | 848.81 | 377.67 | 471.14 | 881.33 | 361.21 | 0.00 | 0.00 | 0.00 |
June | 1098.67 | 565.37 | 533.29 | 1321.03 | 229.68 | 0.00 | 0.00 | 0.00 |
July | 1153.08 | 651.87 | 501.21 | 1493.78 | 188.02 | 0.00 | 0.00 | 0.00 |
August | 1002.08 | 558.33 | 443.75 | 1268.11 | 210.09 | 0.00 | 0.00 | 0.00 |
September | 708.87 | 365.92 | 342.96 | 810.32 | 315.53 | 0.00 | 0.00 | 0.00 |
October | 508.58 | 258.25 | 250.33 | 473.68 | 476.05 | 0.00 | 0.00 | 0.00 |
November | 322.33 | 150.48 | 171.84 | 211.88 | 668.37 | 0.00 | 0.00 | 0.00 |
December | 237.74 | 102.11 | 135.63 | 110.00 | 910.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 666.56 | 335.05 | 331.51 | 690.00 | 523.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.74 | 102.11 | 135.63 | 110.00 | 188.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1153.08 | 651.87 | 533.29 | 1493.78 | 1039.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 286.37 | 131.29 | 155.08 | 144.29 | 1039.17 | 0.00 | 0.00 | 0.00 |
February | 447.90 | 222.37 | 225.53 | 323.32 | 778.92 | 0.00 | 0.00 | 0.00 |
March | 602.25 | 249.19 | 353.05 | 479.22 | 644.42 | 0.00 | 0.00 | 0.00 |
April | 768.41 | 380.82 | 387.59 | 737.94 | 466.38 | 0.00 | 0.00 | 0.00 |
May | 848.81 | 377.67 | 471.14 | 881.33 | 361.21 | 0.00 | 0.00 | 0.00 |
June | 1098.67 | 565.37 | 533.29 | 1321.03 | 229.68 | 0.00 | 0.00 | 0.00 |
July | 1153.08 | 651.87 | 501.21 | 1493.78 | 188.02 | 0.00 | 0.00 | 0.00 |
August | 1002.08 | 558.33 | 443.75 | 1268.11 | 210.09 | 0.00 | 0.00 | 0.00 |
September | 708.87 | 365.92 | 342.96 | 810.32 | 315.53 | 0.00 | 0.00 | 0.00 |
October | 508.58 | 258.25 | 250.33 | 473.68 | 476.05 | 0.00 | 0.00 | 0.00 |
November | 322.33 | 150.48 | 171.84 | 211.88 | 668.37 | 0.00 | 0.00 | 0.00 |
December | 237.74 | 102.11 | 135.63 | 110.00 | 910.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 666.56 | 335.05 | 331.51 | 690.00 | 523.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.74 | 102.11 | 135.63 | 110.00 | 188.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1153.08 | 651.87 | 533.29 | 1493.78 | 1039.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 286.36 | 131.29 | 155.08 | 144.29 | 1039.15 | 0.00 | 0.00 | 0.00 |
February | 447.89 | 222.37 | 225.53 | 323.31 | 778.91 | 0.00 | 0.00 | 0.00 |
March | 602.24 | 249.19 | 353.05 | 479.21 | 644.41 | 0.00 | 0.00 | 0.00 |
April | 768.39 | 380.81 | 387.58 | 737.92 | 466.37 | 0.00 | 0.00 | 0.00 |
May | 848.79 | 377.66 | 471.13 | 881.31 | 361.21 | 0.00 | 0.00 | 0.00 |
June | 1098.65 | 565.36 | 533.28 | 1321.01 | 229.68 | 0.00 | 0.00 | 0.00 |
July | 1153.06 | 651.86 | 501.21 | 1493.75 | 188.01 | 0.00 | 0.00 | 0.00 |
August | 1002.06 | 558.32 | 443.74 | 1268.09 | 210.09 | 0.00 | 0.00 | 0.00 |
September | 708.86 | 365.91 | 342.95 | 810.31 | 315.52 | 0.00 | 0.00 | 0.00 |
October | 508.57 | 258.24 | 250.33 | 473.67 | 476.04 | 0.00 | 0.00 | 0.00 |
November | 322.32 | 150.48 | 171.84 | 211.88 | 668.35 | 0.00 | 0.00 | 0.00 |
December | 237.73 | 102.11 | 135.63 | 110.00 | 910.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 666.55 | 335.05 | 331.50 | 689.99 | 523.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.73 | 102.11 | 135.63 | 110.00 | 188.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1153.06 | 651.86 | 533.28 | 1493.75 | 1039.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 736.61 | 854.51 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1034.77 | 654.52 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 921.67 | 588.83 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 768.48 | 446.03 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 696.91 | 345.32 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 792.20 | 233.63 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 950.47 | 187.89 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1098.03 | 211.33 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1133.59 | 301.59 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1084.08 | 431.40 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 895.32 | 559.78 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 712.66 | 746.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 901.03 | 462.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 696.91 | 187.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1133.59 | 854.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 736.61 | 854.51 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1034.76 | 654.52 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 921.67 | 588.83 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 768.48 | 446.03 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 696.91 | 345.32 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 792.20 | 233.63 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 950.47 | 187.89 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1098.03 | 211.33 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1133.59 | 301.59 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1084.08 | 431.40 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 895.32 | 559.78 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 712.66 | 746.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 901.03 | 462.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 696.91 | 187.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1133.59 | 854.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 736.61 | 854.51 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1034.77 | 654.52 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 921.67 | 588.83 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 768.48 | 446.03 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 696.91 | 345.32 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 792.20 | 233.63 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 950.47 | 187.89 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1098.03 | 211.33 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1133.59 | 301.59 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1084.08 | 431.40 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 895.32 | 559.78 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 712.66 | 746.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 901.03 | 462.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 696.91 | 187.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1133.59 | 854.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.17 | 565.07 | 226.10 | 736.61 | 854.51 | 0.00 | 0.00 | 0.00 |
February | 1007.54 | 724.66 | 282.88 | 1034.76 | 654.52 | 0.00 | 0.00 | 0.00 |
March | 900.61 | 505.74 | 394.87 | 921.67 | 588.83 | 0.00 | 0.00 | 0.00 |
April | 723.94 | 346.26 | 377.67 | 768.48 | 446.03 | 0.00 | 0.00 | 0.00 |
May | 643.20 | 213.62 | 429.58 | 696.91 | 345.32 | 0.00 | 0.00 | 0.00 |
June | 639.08 | 186.39 | 452.70 | 792.20 | 233.63 | 0.00 | 0.00 | 0.00 |
July | 689.00 | 254.51 | 434.48 | 950.47 | 187.89 | 0.00 | 0.00 | 0.00 |
August | 818.83 | 412.84 | 405.99 | 1098.03 | 211.33 | 0.00 | 0.00 | 0.00 |
September | 908.18 | 556.47 | 351.71 | 1133.59 | 301.59 | 0.00 | 0.00 | 0.00 |
October | 949.45 | 656.53 | 292.92 | 1084.08 | 431.40 | 0.00 | 0.00 | 0.00 |
November | 865.62 | 627.02 | 238.60 | 895.32 | 559.78 | 0.00 | 0.00 | 0.00 |
December | 752.35 | 543.28 | 209.08 | 712.66 | 746.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 806.02 | 464.31 | 341.71 | 901.03 | 462.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.08 | 186.39 | 209.08 | 696.91 | 187.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.54 | 724.66 | 452.70 | 1133.59 | 854.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.13 | 565.04 | 226.09 | 736.58 | 854.47 | 0.00 | 0.00 | 0.00 |
February | 1007.50 | 724.63 | 282.87 | 1034.72 | 654.50 | 0.00 | 0.00 | 0.00 |
March | 900.57 | 505.72 | 394.85 | 921.63 | 588.81 | 0.00 | 0.00 | 0.00 |
April | 723.91 | 346.25 | 377.66 | 768.45 | 446.01 | 0.00 | 0.00 | 0.00 |
May | 643.17 | 213.62 | 429.56 | 696.88 | 345.30 | 0.00 | 0.00 | 0.00 |
June | 639.06 | 186.38 | 452.68 | 792.17 | 233.62 | 0.00 | 0.00 | 0.00 |
July | 688.97 | 254.50 | 434.47 | 950.44 | 187.89 | 0.00 | 0.00 | 0.00 |
August | 818.79 | 412.82 | 405.97 | 1097.99 | 211.32 | 0.00 | 0.00 | 0.00 |
September | 908.14 | 556.45 | 351.69 | 1133.55 | 301.58 | 0.00 | 0.00 | 0.00 |
October | 949.41 | 656.51 | 292.91 | 1084.04 | 431.38 | 0.00 | 0.00 | 0.00 |
November | 865.58 | 626.99 | 238.59 | 895.28 | 559.76 | 0.00 | 0.00 | 0.00 |
December | 752.32 | 543.25 | 209.07 | 712.63 | 746.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 805.99 | 464.29 | 341.70 | 900.99 | 462.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 639.06 | 186.38 | 209.07 | 696.88 | 187.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1007.50 | 724.63 | 452.68 | 1133.55 | 854.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.39 | 104.54 | 154.85 | 124.43 | 1115.82 | 0.00 | 0.00 | 0.00 |
February | 442.74 | 217.63 | 225.11 | 319.05 | 854.19 | 0.00 | 0.00 | 0.00 |
March | 566.59 | 207.61 | 358.98 | 426.98 | 734.41 | 0.00 | 0.00 | 0.00 |
April | 739.69 | 327.72 | 411.97 | 695.90 | 553.11 | 0.00 | 0.00 | 0.00 |
May | 914.94 | 417.26 | 497.68 | 969.87 | 406.26 | 0.00 | 0.00 | 0.00 |
June | 995.42 | 457.24 | 538.19 | 1183.58 | 278.98 | 0.00 | 0.00 | 0.00 |
July | 1019.70 | 515.27 | 504.43 | 1314.84 | 237.98 | 0.00 | 0.00 | 0.00 |
August | 865.86 | 424.95 | 440.92 | 1080.55 | 264.95 | 0.00 | 0.00 | 0.00 |
September | 696.53 | 352.14 | 344.39 | 800.62 | 360.45 | 0.00 | 0.00 | 0.00 |
October | 497.83 | 247.34 | 250.49 | 465.07 | 544.16 | 0.00 | 0.00 | 0.00 |
November | 352.42 | 174.83 | 177.59 | 257.05 | 763.58 | 0.00 | 0.00 | 0.00 |
December | 236.89 | 99.98 | 136.90 | 112.09 | 1035.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 633.19 | 295.83 | 337.37 | 647.55 | 594.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.89 | 99.98 | 136.90 | 112.09 | 237.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1019.70 | 515.27 | 538.19 | 1314.84 | 1115.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.39 | 104.54 | 154.85 | 124.43 | 1115.82 | 0.00 | 0.00 | 0.00 |
February | 442.74 | 217.63 | 225.11 | 319.05 | 854.19 | 0.00 | 0.00 | 0.00 |
March | 566.59 | 207.61 | 358.98 | 426.98 | 734.41 | 0.00 | 0.00 | 0.00 |
April | 739.69 | 327.72 | 411.97 | 695.90 | 553.11 | 0.00 | 0.00 | 0.00 |
May | 914.94 | 417.26 | 497.68 | 969.87 | 406.26 | 0.00 | 0.00 | 0.00 |
June | 995.42 | 457.24 | 538.19 | 1183.58 | 278.98 | 0.00 | 0.00 | 0.00 |
July | 1019.70 | 515.27 | 504.43 | 1314.84 | 237.98 | 0.00 | 0.00 | 0.00 |
August | 865.86 | 424.95 | 440.92 | 1080.55 | 264.95 | 0.00 | 0.00 | 0.00 |
September | 696.53 | 352.14 | 344.39 | 800.62 | 360.45 | 0.00 | 0.00 | 0.00 |
October | 497.83 | 247.34 | 250.49 | 465.07 | 544.16 | 0.00 | 0.00 | 0.00 |
November | 352.42 | 174.83 | 177.59 | 257.05 | 763.58 | 0.00 | 0.00 | 0.00 |
December | 236.89 | 99.98 | 136.90 | 112.09 | 1035.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 633.19 | 295.83 | 337.37 | 647.55 | 594.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.89 | 99.98 | 136.90 | 112.09 | 237.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1019.70 | 515.27 | 538.19 | 1314.84 | 1115.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.38 | 104.53 | 154.85 | 124.43 | 1115.80 | 0.00 | 0.00 | 0.00 |
February | 442.73 | 217.62 | 225.10 | 319.04 | 854.17 | 0.00 | 0.00 | 0.00 |
March | 566.58 | 207.60 | 358.98 | 426.97 | 734.39 | 0.00 | 0.00 | 0.00 |
April | 739.68 | 327.71 | 411.97 | 695.88 | 553.10 | 0.00 | 0.00 | 0.00 |
May | 914.93 | 417.26 | 497.67 | 969.85 | 406.25 | 0.00 | 0.00 | 0.00 |
June | 995.41 | 457.23 | 538.18 | 1183.55 | 278.97 | 0.00 | 0.00 | 0.00 |
July | 1019.68 | 515.26 | 504.42 | 1314.82 | 237.97 | 0.00 | 0.00 | 0.00 |
August | 865.85 | 424.94 | 440.91 | 1080.53 | 264.95 | 0.00 | 0.00 | 0.00 |
September | 696.52 | 352.13 | 344.39 | 800.61 | 360.45 | 0.00 | 0.00 | 0.00 |
October | 497.82 | 247.34 | 250.48 | 465.06 | 544.15 | 0.00 | 0.00 | 0.00 |
November | 352.41 | 174.83 | 177.58 | 257.05 | 763.57 | 0.00 | 0.00 | 0.00 |
December | 236.88 | 99.98 | 136.90 | 112.09 | 1035.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 633.18 | 295.82 | 337.36 | 647.54 | 594.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 236.88 | 99.98 | 136.90 | 112.09 | 237.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1019.68 | 515.26 | 538.18 | 1314.82 | 1115.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 561.19 | 0.00 | 561.19 | 16.33 | 4756.85 | 0.00 | 0.00 | 0.00 |
February | 792.37 | 0.00 | 792.37 | 133.36 | 3533.74 | 0.00 | 0.00 | 0.00 |
March | 1287.17 | 0.00 | 1287.17 | 441.85 | 2868.78 | 0.00 | 0.00 | 0.00 |
April | 1467.64 | 8.56 | 1459.08 | 768.28 | 2052.47 | 0.00 | 0.00 | 0.00 |
May | 1927.37 | 114.21 | 1813.16 | 1424.85 | 1532.49 | 0.00 | 0.00 | 0.00 |
June | 2244.31 | 257.96 | 1986.35 | 2302.05 | 974.61 | 0.00 | 0.00 | 0.00 |
July | 2050.30 | 192.04 | 1858.27 | 2502.07 | 810.96 | 0.00 | 0.00 | 0.00 |
August | 1642.92 | 44.04 | 1598.88 | 1823.27 | 927.38 | 0.00 | 0.00 | 0.00 |
September | 1230.43 | 0.44 | 1229.99 | 1061.97 | 1420.88 | 0.00 | 0.00 | 0.00 |
October | 897.53 | 0.00 | 897.53 | 403.49 | 2106.68 | 0.00 | 0.00 | 0.00 |
November | 610.15 | 0.00 | 610.15 | 94.33 | 2993.37 | 0.00 | 0.00 | 0.00 |
December | 470.59 | 0.00 | 470.59 | 8.51 | 4080.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.70 | 51.69 | 1216.01 | 919.90 | 2333.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.59 | 0.00 | 470.59 | 8.51 | 810.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2244.31 | 257.96 | 1986.35 | 2502.07 | 4756.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 859.09 | 393.86 | 465.23 | 456.89 | 2925.56 | 0.00 | 0.00 | 0.00 |
February | 1343.70 | 667.11 | 676.58 | 996.78 | 2192.53 | 0.00 | 0.00 | 0.00 |
March | 1806.72 | 747.57 | 1059.15 | 1453.05 | 1831.61 | 0.00 | 0.00 | 0.00 |
April | 2305.20 | 1142.44 | 1162.76 | 2212.65 | 1334.99 | 0.00 | 0.00 | 0.00 |
May | 2546.39 | 1132.98 | 1413.41 | 2631.26 | 1045.60 | 0.00 | 0.00 | 0.00 |
June | 3295.97 | 1696.11 | 1599.87 | 3937.80 | 680.05 | 0.00 | 0.00 | 0.00 |
July | 3459.22 | 1955.59 | 1503.63 | 4464.08 | 555.10 | 0.00 | 0.00 | 0.00 |
August | 3006.21 | 1674.97 | 1331.24 | 3785.31 | 627.09 | 0.00 | 0.00 | 0.00 |
September | 2126.60 | 1097.74 | 1028.86 | 2417.36 | 918.77 | 0.00 | 0.00 | 0.00 |
October | 1525.72 | 774.74 | 750.99 | 1427.80 | 1352.36 | 0.00 | 0.00 | 0.00 |
November | 966.97 | 451.45 | 515.52 | 657.53 | 1859.93 | 0.00 | 0.00 | 0.00 |
December | 713.20 | 306.32 | 406.88 | 355.89 | 2514.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1999.67 | 1005.15 | 994.52 | 2072.53 | 1483.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.20 | 306.32 | 406.88 | 355.89 | 555.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3459.22 | 1955.59 | 1599.87 | 4464.08 | 2925.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3955.78 | 2825.30 | 1130.48 | 3674.35 | 4182.86 | 0.00 | 0.00 | 0.00 |
February | 5037.63 | 3623.25 | 1414.38 | 5147.38 | 3193.19 | 0.00 | 0.00 | 0.00 |
March | 4502.98 | 2528.67 | 1974.31 | 4583.95 | 2869.07 | 0.00 | 0.00 | 0.00 |
April | 3619.64 | 1731.30 | 1888.35 | 3830.26 | 2153.43 | 0.00 | 0.00 | 0.00 |
May | 3215.96 | 1068.11 | 2147.85 | 3465.45 | 1690.51 | 0.00 | 0.00 | 0.00 |
June | 3195.38 | 931.93 | 2263.46 | 3948.07 | 1143.40 | 0.00 | 0.00 | 0.00 |
July | 3444.94 | 1272.55 | 2172.39 | 4754.14 | 911.37 | 0.00 | 0.00 | 0.00 |
August | 4094.09 | 2064.17 | 2029.92 | 5480.45 | 1033.11 | 0.00 | 0.00 | 0.00 |
September | 4540.83 | 2782.32 | 1758.52 | 5625.78 | 1488.45 | 0.00 | 0.00 | 0.00 |
October | 4747.20 | 3282.63 | 1464.57 | 5383.79 | 2113.77 | 0.00 | 0.00 | 0.00 |
November | 4328.04 | 3135.06 | 1192.98 | 4464.29 | 2717.59 | 0.00 | 0.00 | 0.00 |
December | 3761.73 | 2716.35 | 1045.38 | 3572.58 | 3586.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4030.07 | 2321.53 | 1708.53 | 4489.14 | 2253.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3195.38 | 931.93 | 1045.38 | 3465.45 | 911.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5037.63 | 3623.25 | 2263.46 | 5625.78 | 4182.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 778.15 | 313.60 | 464.55 | 394.81 | 3094.37 | 0.00 | 0.00 | 0.00 |
February | 1328.19 | 652.87 | 675.32 | 1004.87 | 2293.78 | 0.00 | 0.00 | 0.00 |
March | 1699.76 | 622.82 | 1076.94 | 1336.27 | 1949.66 | 0.00 | 0.00 | 0.00 |
April | 2219.05 | 983.14 | 1235.91 | 2141.72 | 1455.74 | 0.00 | 0.00 | 0.00 |
May | 2744.81 | 1251.78 | 1493.03 | 2919.86 | 1140.68 | 0.00 | 0.00 | 0.00 |
June | 2986.24 | 1371.69 | 1614.55 | 3569.81 | 777.90 | 0.00 | 0.00 | 0.00 |
July | 3059.07 | 1545.79 | 1513.28 | 3978.54 | 653.73 | 0.00 | 0.00 | 0.00 |
August | 2597.57 | 1274.83 | 1322.74 | 3284.24 | 709.11 | 0.00 | 0.00 | 0.00 |
September | 2089.58 | 1056.41 | 1033.17 | 2413.11 | 1009.81 | 0.00 | 0.00 | 0.00 |
October | 1493.48 | 742.03 | 751.45 | 1433.42 | 1457.07 | 0.00 | 0.00 | 0.00 |
November | 1057.24 | 524.48 | 532.76 | 814.02 | 1971.69 | 0.00 | 0.00 | 0.00 |
December | 710.66 | 299.95 | 410.71 | 373.98 | 2644.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1899.56 | 887.47 | 1012.09 | 1977.13 | 1594.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 710.66 | 299.95 | 410.71 | 373.98 | 653.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3059.07 | 1545.79 | 1614.55 | 3978.54 | 3094.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 561.19 | 0.00 | 561.19 | 25.67 | 4564.26 | 0.00 | 0.00 | 0.00 |
February | 792.37 | 0.00 | 792.37 | 164.75 | 3349.78 | 0.00 | 0.00 | 0.00 |
March | 1287.17 | 0.00 | 1287.17 | 493.84 | 2688.23 | 0.00 | 0.00 | 0.00 |
April | 1467.64 | 8.56 | 1459.08 | 823.57 | 1899.59 | 0.00 | 0.00 | 0.00 |
May | 1927.37 | 114.21 | 1813.16 | 1458.98 | 1444.78 | 0.00 | 0.00 | 0.00 |
June | 2244.31 | 257.96 | 1986.35 | 2305.78 | 951.84 | 0.00 | 0.00 | 0.00 |
July | 2050.30 | 192.04 | 1858.27 | 2493.71 | 802.72 | 0.00 | 0.00 | 0.00 |
August | 1642.92 | 44.04 | 1598.88 | 1823.31 | 904.38 | 0.00 | 0.00 | 0.00 |
September | 1230.43 | 0.44 | 1229.99 | 1083.62 | 1343.88 | 0.00 | 0.00 | 0.00 |
October | 897.53 | 0.00 | 897.53 | 458.89 | 1922.42 | 0.00 | 0.00 | 0.00 |
November | 610.15 | 0.00 | 610.15 | 121.69 | 2744.38 | 0.00 | 0.00 | 0.00 |
December | 470.59 | 0.00 | 470.59 | 12.20 | 3862.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.70 | 51.69 | 1216.01 | 943.61 | 2202.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.59 | 0.00 | 470.59 | 12.20 | 802.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2244.31 | 257.96 | 1986.35 | 2493.71 | 4564.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 859.09 | 393.86 | 465.23 | 476.51 | 2813.42 | 0.00 | 0.00 | 0.00 |
February | 1343.70 | 667.11 | 676.58 | 1034.44 | 2078.24 | 0.00 | 0.00 | 0.00 |
March | 1806.72 | 747.57 | 1059.15 | 1498.37 | 1719.00 | 0.00 | 0.00 | 0.00 |
April | 2305.20 | 1142.44 | 1162.76 | 2249.00 | 1244.32 | 0.00 | 0.00 | 0.00 |
May | 2546.39 | 1132.98 | 1413.41 | 2648.95 | 992.72 | 0.00 | 0.00 | 0.00 |
June | 3295.97 | 1696.11 | 1599.87 | 3938.47 | 666.94 | 0.00 | 0.00 | 0.00 |
July | 3459.22 | 1955.59 | 1503.63 | 4458.55 | 550.19 | 0.00 | 0.00 | 0.00 |
August | 3006.21 | 1674.97 | 1331.24 | 3785.39 | 614.60 | 0.00 | 0.00 | 0.00 |
September | 2126.60 | 1097.74 | 1028.86 | 2431.67 | 877.21 | 0.00 | 0.00 | 0.00 |
October | 1525.72 | 774.74 | 750.99 | 1468.98 | 1244.99 | 0.00 | 0.00 | 0.00 |
November | 966.97 | 451.45 | 515.52 | 699.65 | 1702.35 | 0.00 | 0.00 | 0.00 |
December | 713.20 | 306.32 | 406.88 | 376.38 | 2377.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1999.67 | 1005.15 | 994.52 | 2094.89 | 1404.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.20 | 306.32 | 406.88 | 376.38 | 550.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3459.22 | 1955.59 | 1599.87 | 4458.55 | 2813.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3955.78 | 2825.30 | 1130.48 | 3719.88 | 3987.01 | 0.00 | 0.00 | 0.00 |
February | 5037.63 | 3623.25 | 1414.38 | 5195.50 | 3022.78 | 0.00 | 0.00 | 0.00 |
March | 4502.98 | 2528.67 | 1974.31 | 4632.89 | 2698.91 | 0.00 | 0.00 | 0.00 |
April | 3619.64 | 1731.30 | 1888.35 | 3866.79 | 2012.62 | 0.00 | 0.00 | 0.00 |
May | 3215.96 | 1068.11 | 2147.85 | 3481.68 | 1603.55 | 0.00 | 0.00 | 0.00 |
June | 3195.38 | 931.93 | 2263.46 | 3941.43 | 1115.99 | 0.00 | 0.00 | 0.00 |
July | 3444.94 | 1272.55 | 2172.39 | 4738.55 | 900.33 | 0.00 | 0.00 | 0.00 |
August | 4094.09 | 2064.17 | 2029.92 | 5469.51 | 1010.46 | 0.00 | 0.00 | 0.00 |
September | 4540.83 | 2782.32 | 1758.52 | 5632.08 | 1423.02 | 0.00 | 0.00 | 0.00 |
October | 4747.20 | 3282.63 | 1464.57 | 5426.06 | 1961.48 | 0.00 | 0.00 | 0.00 |
November | 4328.04 | 3135.06 | 1192.98 | 4533.00 | 2508.35 | 0.00 | 0.00 | 0.00 |
December | 3761.73 | 2716.35 | 1045.38 | 3634.03 | 3369.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4030.07 | 2321.53 | 1708.53 | 4517.41 | 2131.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3195.38 | 931.93 | 1045.38 | 3481.68 | 900.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5037.63 | 3623.25 | 2263.46 | 5632.08 | 3987.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 778.15 | 313.60 | 464.55 | 406.93 | 2974.33 | 0.00 | 0.00 | 0.00 |
February | 1328.19 | 652.87 | 675.32 | 1026.25 | 2189.07 | 0.00 | 0.00 | 0.00 |
March | 1699.76 | 622.82 | 1076.94 | 1364.45 | 1844.98 | 0.00 | 0.00 | 0.00 |
April | 2219.05 | 983.14 | 1235.91 | 2166.16 | 1370.20 | 0.00 | 0.00 | 0.00 |
May | 2744.81 | 1251.78 | 1493.03 | 2928.38 | 1087.71 | 0.00 | 0.00 | 0.00 |
June | 2986.24 | 1371.69 | 1614.55 | 3562.61 | 760.57 | 0.00 | 0.00 | 0.00 |
July | 3059.07 | 1545.79 | 1513.28 | 3967.33 | 645.98 | 0.00 | 0.00 | 0.00 |
August | 2597.57 | 1274.83 | 1322.74 | 3276.97 | 694.48 | 0.00 | 0.00 | 0.00 |
September | 2089.58 | 1056.41 | 1033.17 | 2418.81 | 965.78 | 0.00 | 0.00 | 0.00 |
October | 1493.48 | 742.03 | 751.45 | 1460.93 | 1355.42 | 0.00 | 0.00 | 0.00 |
November | 1057.24 | 524.48 | 532.76 | 839.78 | 1831.30 | 0.00 | 0.00 | 0.00 |
December | 710.66 | 299.95 | 410.71 | 387.47 | 2512.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1899.56 | 887.47 | 1012.09 | 1988.83 | 1517.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 710.66 | 299.95 | 410.71 | 387.47 | 645.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3059.07 | 1545.79 | 1614.55 | 3967.33 | 2974.33 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 3739719.66 | 0.273075E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 40902346.62 | 0.186086E+10 |
March | 0.689519E+09 | 0.00 | 0.689519E+09 | 0.198572E+09 | 0.167571E+10 |
April | 0.760836E+09 | 4440069.61 | 0.756396E+09 | 0.364742E+09 | 0.116461E+10 |
May | 0.103247E+10 | 61179947.39 | 0.971285E+09 | 0.745728E+09 | 0.867396E+09 |
June | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.118015E+10 | 0.524726E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995449E+09 | 0.131525E+10 | 0.456910E+09 |
August | 0.880089E+09 | 23590500.52 | 0.856499E+09 | 0.954423E+09 | 0.522913E+09 |
September | 0.637864E+09 | 228900.10 | 0.637635E+09 | 0.535528E+09 | 0.781489E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.188327E+09 | 0.123938E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 34385556.89 | 0.173778E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222962.59 | 0.243230E+10 |
Annual Sum or Average | 0.799576E+10 | 0.326041E+09 | 0.766971E+10 | 0.556297E+10 | 0.159948E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222962.59 | 0.456910E+09 |
Maximum of Months | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.131525E+10 | 0.273075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 3739696.02 | 0.273075E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 40902231.81 | 0.186086E+10 |
March | 0.689518E+09 | 0.00 | 0.689518E+09 | 0.198572E+09 | 0.167571E+10 |
April | 0.760836E+09 | 4440064.28 | 0.756395E+09 | 0.364742E+09 | 0.116461E+10 |
May | 0.103246E+10 | 61179873.98 | 0.971284E+09 | 0.745727E+09 | 0.867396E+09 |
June | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.118015E+10 | 0.524726E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995448E+09 | 0.131525E+10 | 0.456910E+09 |
August | 0.880089E+09 | 23590472.21 | 0.856498E+09 | 0.954422E+09 | 0.522913E+09 |
September | 0.637863E+09 | 228899.82 | 0.637634E+09 | 0.535527E+09 | 0.781488E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.188327E+09 | 0.123938E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 34385454.58 | 0.173778E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222955.04 | 0.243230E+10 |
Annual Sum or Average | 0.799575E+10 | 0.326040E+09 | 0.766971E+10 | 0.556296E+10 | 0.159948E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222955.04 | 0.456910E+09 |
Maximum of Months | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.131525E+10 | 0.273075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 3739719.66 | 0.273075E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 40902346.62 | 0.186086E+10 |
March | 0.689519E+09 | 0.00 | 0.689519E+09 | 0.198572E+09 | 0.167571E+10 |
April | 0.760836E+09 | 4440069.61 | 0.756396E+09 | 0.364742E+09 | 0.116461E+10 |
May | 0.103247E+10 | 61179947.39 | 0.971285E+09 | 0.745728E+09 | 0.867396E+09 |
June | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.118015E+10 | 0.524726E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995449E+09 | 0.131525E+10 | 0.456910E+09 |
August | 0.880089E+09 | 23590500.52 | 0.856499E+09 | 0.954423E+09 | 0.522913E+09 |
September | 0.637864E+09 | 228900.10 | 0.637635E+09 | 0.535528E+09 | 0.781489E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.188327E+09 | 0.123938E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 34385556.89 | 0.173778E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222962.59 | 0.243230E+10 |
Annual Sum or Average | 0.799576E+10 | 0.326041E+09 | 0.766971E+10 | 0.556297E+10 | 0.159948E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222962.59 | 0.456910E+09 |
Maximum of Months | 0.116347E+10 | 0.133731E+09 | 0.102974E+10 | 0.131525E+10 | 0.273075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300623E+09 | 0.00 | 0.300623E+09 | 3739696.02 | 0.273075E+10 |
February | 0.383384E+09 | 0.00 | 0.383384E+09 | 40902231.81 | 0.186086E+10 |
March | 0.689518E+09 | 0.00 | 0.689518E+09 | 0.198572E+09 | 0.167571E+10 |
April | 0.760836E+09 | 4440064.28 | 0.756395E+09 | 0.364742E+09 | 0.116461E+10 |
May | 0.103246E+10 | 61179873.98 | 0.971284E+09 | 0.745727E+09 | 0.867396E+09 |
June | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.118015E+10 | 0.524726E+09 |
July | 0.109832E+10 | 0.102871E+09 | 0.995448E+09 | 0.131525E+10 | 0.456910E+09 |
August | 0.880089E+09 | 23590472.21 | 0.856498E+09 | 0.954422E+09 | 0.522913E+09 |
September | 0.637863E+09 | 228899.82 | 0.637634E+09 | 0.535527E+09 | 0.781488E+09 |
October | 0.480794E+09 | 0.00 | 0.480794E+09 | 0.188327E+09 | 0.123938E+10 |
November | 0.316305E+09 | 0.00 | 0.316305E+09 | 34385454.58 | 0.173778E+10 |
December | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222955.04 | 0.243230E+10 |
Annual Sum or Average | 0.799575E+10 | 0.326040E+09 | 0.766971E+10 | 0.556296E+10 | 0.159948E+11 |
Minimum of Months | 0.252090E+09 | 0.00 | 0.252090E+09 | 1222955.04 | 0.456910E+09 |
Maximum of Months | 0.116347E+10 | 0.133730E+09 | 0.102973E+10 | 0.131525E+10 | 0.273075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300611E+09 | 0.00 | 0.300611E+09 | 3739568.93 | 0.273064E+10 |
February | 0.383369E+09 | 0.00 | 0.383369E+09 | 40900698.08 | 0.186079E+10 |
March | 0.689491E+09 | 0.00 | 0.689491E+09 | 0.198564E+09 | 0.167564E+10 |
April | 0.760805E+09 | 4439890.66 | 0.756366E+09 | 0.364727E+09 | 0.116456E+10 |
May | 0.103242E+10 | 61177481.56 | 0.971246E+09 | 0.745698E+09 | 0.867361E+09 |
June | 0.116342E+10 | 0.133725E+09 | 0.102969E+10 | 0.118010E+10 | 0.524704E+09 |
July | 0.109828E+10 | 0.102867E+09 | 0.995409E+09 | 0.131520E+10 | 0.456891E+09 |
August | 0.880054E+09 | 23589549.72 | 0.856464E+09 | 0.954384E+09 | 0.522892E+09 |
September | 0.637838E+09 | 228890.87 | 0.637609E+09 | 0.535506E+09 | 0.781457E+09 |
October | 0.480775E+09 | 0.00 | 0.480775E+09 | 0.188320E+09 | 0.123933E+10 |
November | 0.316292E+09 | 0.00 | 0.316292E+09 | 34384171.00 | 0.173771E+10 |
December | 0.252080E+09 | 0.00 | 0.252080E+09 | 1222913.30 | 0.243220E+10 |
Annual Sum or Average | 0.799543E+10 | 0.326028E+09 | 0.766941E+10 | 0.556275E+10 | 0.159942E+11 |
Minimum of Months | 0.252080E+09 | 0.00 | 0.252080E+09 | 1222913.30 | 0.456891E+09 |
Maximum of Months | 0.116342E+10 | 0.133725E+09 | 0.102969E+10 | 0.131520E+10 | 0.273064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.767004E+09 | 0.351640E+09 | 0.415364E+09 | 0.386474E+09 | 0.278330E+10 |
February | 0.108357E+10 | 0.537965E+09 | 0.545602E+09 | 0.782173E+09 | 0.188436E+10 |
March | 0.161306E+10 | 0.667438E+09 | 0.945619E+09 | 0.128355E+10 | 0.172602E+10 |
April | 0.199171E+10 | 0.987077E+09 | 0.100463E+10 | 0.191273E+10 | 0.120887E+10 |
May | 0.227344E+10 | 0.101154E+10 | 0.126190E+10 | 0.236054E+10 | 0.967474E+09 |
June | 0.284775E+10 | 0.146545E+10 | 0.138230E+10 | 0.342411E+10 | 0.595330E+09 |
July | 0.308842E+10 | 0.174597E+10 | 0.134245E+10 | 0.400094E+10 | 0.503580E+09 |
August | 0.268397E+10 | 0.149543E+10 | 0.118855E+10 | 0.339652E+10 | 0.562709E+09 |
September | 0.183740E+10 | 0.948459E+09 | 0.888942E+09 | 0.210035E+10 | 0.817844E+09 |
October | 0.136218E+10 | 0.691694E+09 | 0.670486E+09 | 0.126871E+10 | 0.127506E+10 |
November | 0.835475E+09 | 0.390057E+09 | 0.445418E+09 | 0.549190E+09 | 0.173241E+10 |
December | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.294619E+09 | 0.243764E+10 |
Annual Sum or Average | 0.210207E+11 | 0.105662E+11 | 0.104545E+11 | 0.217599E+11 | 0.164946E+11 |
Minimum of Months | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.294619E+09 | 0.503580E+09 |
Maximum of Months | 0.308842E+10 | 0.174597E+10 | 0.138230E+10 | 0.400094E+10 | 0.278330E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.767004E+09 | 0.351640E+09 | 0.415364E+09 | 0.386474E+09 | 0.278330E+10 |
February | 0.108357E+10 | 0.537965E+09 | 0.545602E+09 | 0.782173E+09 | 0.188436E+10 |
March | 0.161306E+10 | 0.667438E+09 | 0.945619E+09 | 0.128355E+10 | 0.172602E+10 |
April | 0.199171E+10 | 0.987077E+09 | 0.100463E+10 | 0.191273E+10 | 0.120887E+10 |
May | 0.227344E+10 | 0.101154E+10 | 0.126190E+10 | 0.236054E+10 | 0.967474E+09 |
June | 0.284775E+10 | 0.146545E+10 | 0.138230E+10 | 0.342411E+10 | 0.595330E+09 |
July | 0.308842E+10 | 0.174597E+10 | 0.134245E+10 | 0.400094E+10 | 0.503580E+09 |
August | 0.268397E+10 | 0.149543E+10 | 0.118855E+10 | 0.339652E+10 | 0.562709E+09 |
September | 0.183740E+10 | 0.948459E+09 | 0.888942E+09 | 0.210035E+10 | 0.817844E+09 |
October | 0.136218E+10 | 0.691694E+09 | 0.670486E+09 | 0.126871E+10 | 0.127506E+10 |
November | 0.835475E+09 | 0.390057E+09 | 0.445418E+09 | 0.549190E+09 | 0.173241E+10 |
December | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.294619E+09 | 0.243764E+10 |
Annual Sum or Average | 0.210207E+11 | 0.105662E+11 | 0.104545E+11 | 0.217599E+11 | 0.164946E+11 |
Minimum of Months | 0.636751E+09 | 0.273486E+09 | 0.363265E+09 | 0.294619E+09 | 0.503580E+09 |
Maximum of Months | 0.308842E+10 | 0.174597E+10 | 0.138230E+10 | 0.400094E+10 | 0.278330E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.766990E+09 | 0.351634E+09 | 0.415356E+09 | 0.386467E+09 | 0.278325E+10 |
February | 0.108355E+10 | 0.537955E+09 | 0.545592E+09 | 0.782159E+09 | 0.188433E+10 |
March | 0.161303E+10 | 0.667425E+09 | 0.945601E+09 | 0.128353E+10 | 0.172599E+10 |
April | 0.199167E+10 | 0.987059E+09 | 0.100462E+10 | 0.191270E+10 | 0.120884E+10 |
May | 0.227340E+10 | 0.101152E+10 | 0.126188E+10 | 0.236050E+10 | 0.967456E+09 |
June | 0.284770E+10 | 0.146542E+10 | 0.138227E+10 | 0.342405E+10 | 0.595319E+09 |
July | 0.308836E+10 | 0.174593E+10 | 0.134243E+10 | 0.400087E+10 | 0.503570E+09 |
August | 0.268392E+10 | 0.149540E+10 | 0.118853E+10 | 0.339646E+10 | 0.562699E+09 |
September | 0.183737E+10 | 0.948442E+09 | 0.888925E+09 | 0.210031E+10 | 0.817829E+09 |
October | 0.136216E+10 | 0.691681E+09 | 0.670474E+09 | 0.126869E+10 | 0.127503E+10 |
November | 0.835459E+09 | 0.390050E+09 | 0.445410E+09 | 0.549180E+09 | 0.173238E+10 |
December | 0.636740E+09 | 0.273481E+09 | 0.363259E+09 | 0.294614E+09 | 0.243760E+10 |
Annual Sum or Average | 0.210203E+11 | 0.105660E+11 | 0.104543E+11 | 0.217595E+11 | 0.164943E+11 |
Minimum of Months | 0.636740E+09 | 0.273481E+09 | 0.363259E+09 | 0.294614E+09 | 0.503570E+09 |
Maximum of Months | 0.308836E+10 | 0.174593E+10 | 0.138227E+10 | 0.400087E+10 | 0.278325E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605585E+09 | 0.197295E+10 | 0.228872E+10 |
February | 0.243744E+10 | 0.175310E+10 | 0.684341E+09 | 0.250331E+10 | 0.158342E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.246859E+10 | 0.157713E+10 |
April | 0.187645E+10 | 0.897516E+09 | 0.978930E+09 | 0.199191E+10 | 0.115611E+10 |
May | 0.172275E+10 | 0.572172E+09 | 0.115058E+10 | 0.186661E+10 | 0.924898E+09 |
June | 0.165651E+10 | 0.483116E+09 | 0.117339E+10 | 0.205338E+10 | 0.605570E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.254575E+10 | 0.503254E+09 |
August | 0.219315E+10 | 0.110575E+10 | 0.108740E+10 | 0.294097E+10 | 0.566019E+09 |
September | 0.235400E+10 | 0.144237E+10 | 0.911627E+09 | 0.293827E+10 | 0.781722E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290361E+10 | 0.115546E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232066E+10 | 0.145096E+10 |
December | 0.201511E+10 | 0.145511E+10 | 0.559996E+09 | 0.190880E+10 | 0.200035E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146426E+11 | 0.107762E+11 | 0.284148E+11 | 0.145936E+11 |
Minimum of Months | 0.165651E+10 | 0.483116E+09 | 0.559996E+09 | 0.186661E+10 | 0.503254E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294097E+10 | 0.228872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605584E+09 | 0.197294E+10 | 0.228872E+10 |
February | 0.243743E+10 | 0.175309E+10 | 0.684341E+09 | 0.250330E+10 | 0.158342E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.246859E+10 | 0.157713E+10 |
April | 0.187644E+10 | 0.897515E+09 | 0.978929E+09 | 0.199190E+10 | 0.115611E+10 |
May | 0.172275E+10 | 0.572171E+09 | 0.115057E+10 | 0.186661E+10 | 0.924898E+09 |
June | 0.165650E+10 | 0.483116E+09 | 0.117339E+10 | 0.205338E+10 | 0.605570E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.254575E+10 | 0.503254E+09 |
August | 0.219315E+10 | 0.110574E+10 | 0.108740E+10 | 0.294097E+10 | 0.566019E+09 |
September | 0.235399E+10 | 0.144237E+10 | 0.911626E+09 | 0.293827E+10 | 0.781722E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290361E+10 | 0.115546E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232066E+10 | 0.145096E+10 |
December | 0.201510E+10 | 0.145511E+10 | 0.559995E+09 | 0.190879E+10 | 0.200035E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146425E+11 | 0.107762E+11 | 0.284148E+11 | 0.145936E+11 |
Minimum of Months | 0.165650E+10 | 0.483116E+09 | 0.559995E+09 | 0.186661E+10 | 0.503254E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294097E+10 | 0.228872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605585E+09 | 0.197295E+10 | 0.228872E+10 |
February | 0.243744E+10 | 0.175310E+10 | 0.684341E+09 | 0.250331E+10 | 0.158342E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.246859E+10 | 0.157713E+10 |
April | 0.187645E+10 | 0.897516E+09 | 0.978930E+09 | 0.199191E+10 | 0.115611E+10 |
May | 0.172275E+10 | 0.572172E+09 | 0.115058E+10 | 0.186661E+10 | 0.924898E+09 |
June | 0.165651E+10 | 0.483116E+09 | 0.117339E+10 | 0.205338E+10 | 0.605570E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.254575E+10 | 0.503254E+09 |
August | 0.219315E+10 | 0.110575E+10 | 0.108740E+10 | 0.294097E+10 | 0.566019E+09 |
September | 0.235400E+10 | 0.144237E+10 | 0.911627E+09 | 0.293827E+10 | 0.781722E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290361E+10 | 0.115546E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232066E+10 | 0.145096E+10 |
December | 0.201511E+10 | 0.145511E+10 | 0.559996E+09 | 0.190880E+10 | 0.200035E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146426E+11 | 0.107762E+11 | 0.284148E+11 | 0.145936E+11 |
Minimum of Months | 0.165651E+10 | 0.483116E+09 | 0.559996E+09 | 0.186661E+10 | 0.503254E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294097E+10 | 0.228872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211906E+10 | 0.151347E+10 | 0.605584E+09 | 0.197294E+10 | 0.228872E+10 |
February | 0.243743E+10 | 0.175309E+10 | 0.684341E+09 | 0.250330E+10 | 0.158342E+10 |
March | 0.241219E+10 | 0.135457E+10 | 0.105761E+10 | 0.246859E+10 | 0.157713E+10 |
April | 0.187644E+10 | 0.897515E+09 | 0.978929E+09 | 0.199190E+10 | 0.115611E+10 |
May | 0.172275E+10 | 0.572171E+09 | 0.115057E+10 | 0.186661E+10 | 0.924898E+09 |
June | 0.165650E+10 | 0.483116E+09 | 0.117339E+10 | 0.205338E+10 | 0.605570E+09 |
July | 0.184541E+10 | 0.681688E+09 | 0.116372E+10 | 0.254575E+10 | 0.503254E+09 |
August | 0.219315E+10 | 0.110574E+10 | 0.108740E+10 | 0.294097E+10 | 0.566019E+09 |
September | 0.235399E+10 | 0.144237E+10 | 0.911626E+09 | 0.293827E+10 | 0.781722E+09 |
October | 0.254301E+10 | 0.175846E+10 | 0.784551E+09 | 0.290361E+10 | 0.115546E+10 |
November | 0.224368E+10 | 0.162523E+10 | 0.618449E+09 | 0.232066E+10 | 0.145096E+10 |
December | 0.201510E+10 | 0.145511E+10 | 0.559995E+09 | 0.190879E+10 | 0.200035E+10 |
Annual Sum or Average | 0.254187E+11 | 0.146425E+11 | 0.107762E+11 | 0.284148E+11 | 0.145936E+11 |
Minimum of Months | 0.165650E+10 | 0.483116E+09 | 0.559995E+09 | 0.186661E+10 | 0.503254E+09 |
Maximum of Months | 0.254301E+10 | 0.175846E+10 | 0.117339E+10 | 0.294097E+10 | 0.228872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.211897E+10 | 0.151341E+10 | 0.605560E+09 | 0.197287E+10 | 0.228862E+10 |
February | 0.243734E+10 | 0.175302E+10 | 0.684314E+09 | 0.250321E+10 | 0.158335E+10 |
March | 0.241209E+10 | 0.135452E+10 | 0.105757E+10 | 0.246849E+10 | 0.157707E+10 |
April | 0.187637E+10 | 0.897480E+09 | 0.978891E+09 | 0.199183E+10 | 0.115606E+10 |
May | 0.172268E+10 | 0.572149E+09 | 0.115053E+10 | 0.186653E+10 | 0.924860E+09 |
June | 0.165644E+10 | 0.483097E+09 | 0.117334E+10 | 0.205330E+10 | 0.605546E+09 |
July | 0.184533E+10 | 0.681661E+09 | 0.116367E+10 | 0.254565E+10 | 0.503234E+09 |
August | 0.219306E+10 | 0.110570E+10 | 0.108736E+10 | 0.294085E+10 | 0.565997E+09 |
September | 0.235390E+10 | 0.144231E+10 | 0.911590E+09 | 0.293816E+10 | 0.781691E+09 |
October | 0.254291E+10 | 0.175839E+10 | 0.784520E+09 | 0.290349E+10 | 0.115541E+10 |
November | 0.224359E+10 | 0.162517E+10 | 0.618424E+09 | 0.232057E+10 | 0.145090E+10 |
December | 0.201503E+10 | 0.145505E+10 | 0.559973E+09 | 0.190872E+10 | 0.200027E+10 |
Annual Sum or Average | 0.254177E+11 | 0.146420E+11 | 0.107757E+11 | 0.284137E+11 | 0.145930E+11 |
Minimum of Months | 0.165644E+10 | 0.483097E+09 | 0.559973E+09 | 0.186653E+10 | 0.503234E+09 |
Maximum of Months | 0.254291E+10 | 0.175839E+10 | 0.117334E+10 | 0.294085E+10 | 0.228862E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694743E+09 | 0.279987E+09 | 0.414756E+09 | 0.333277E+09 | 0.298861E+10 |
February | 0.107106E+10 | 0.526483E+09 | 0.544582E+09 | 0.771839E+09 | 0.206646E+10 |
March | 0.151756E+10 | 0.556058E+09 | 0.961505E+09 | 0.114361E+10 | 0.196704E+10 |
April | 0.191728E+10 | 0.849443E+09 | 0.106784E+10 | 0.180377E+10 | 0.143366E+10 |
May | 0.245059E+10 | 0.111760E+10 | 0.133299E+10 | 0.259769E+10 | 0.108813E+10 |
June | 0.258014E+10 | 0.118515E+10 | 0.139499E+10 | 0.306783E+10 | 0.723105E+09 |
July | 0.273117E+10 | 0.138010E+10 | 0.135107E+10 | 0.352168E+10 | 0.637401E+09 |
August | 0.231913E+10 | 0.113818E+10 | 0.118095E+10 | 0.289416E+10 | 0.709648E+09 |
September | 0.180541E+10 | 0.912744E+09 | 0.892670E+09 | 0.207521E+10 | 0.934291E+09 |
October | 0.133339E+10 | 0.662489E+09 | 0.670899E+09 | 0.124564E+10 | 0.145748E+10 |
November | 0.913463E+09 | 0.453156E+09 | 0.460307E+09 | 0.666279E+09 | 0.197920E+10 |
December | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.300220E+09 | 0.277471E+10 |
Annual Sum or Average | 0.199684E+11 | 0.932919E+10 | 0.106392E+11 | 0.204212E+11 | 0.187597E+11 |
Minimum of Months | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.300220E+09 | 0.637401E+09 |
Maximum of Months | 0.273117E+10 | 0.138010E+10 | 0.139499E+10 | 0.352168E+10 | 0.298861E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694743E+09 | 0.279987E+09 | 0.414756E+09 | 0.333277E+09 | 0.298861E+10 |
February | 0.107106E+10 | 0.526483E+09 | 0.544582E+09 | 0.771839E+09 | 0.206646E+10 |
March | 0.151756E+10 | 0.556058E+09 | 0.961505E+09 | 0.114361E+10 | 0.196704E+10 |
April | 0.191728E+10 | 0.849443E+09 | 0.106784E+10 | 0.180377E+10 | 0.143366E+10 |
May | 0.245059E+10 | 0.111760E+10 | 0.133299E+10 | 0.259769E+10 | 0.108813E+10 |
June | 0.258014E+10 | 0.118515E+10 | 0.139499E+10 | 0.306783E+10 | 0.723105E+09 |
July | 0.273117E+10 | 0.138010E+10 | 0.135107E+10 | 0.352168E+10 | 0.637401E+09 |
August | 0.231913E+10 | 0.113818E+10 | 0.118095E+10 | 0.289416E+10 | 0.709648E+09 |
September | 0.180541E+10 | 0.912744E+09 | 0.892670E+09 | 0.207521E+10 | 0.934291E+09 |
October | 0.133339E+10 | 0.662489E+09 | 0.670899E+09 | 0.124564E+10 | 0.145748E+10 |
November | 0.913463E+09 | 0.453156E+09 | 0.460307E+09 | 0.666279E+09 | 0.197920E+10 |
December | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.300220E+09 | 0.277471E+10 |
Annual Sum or Average | 0.199684E+11 | 0.932919E+10 | 0.106392E+11 | 0.204212E+11 | 0.187597E+11 |
Minimum of Months | 0.634481E+09 | 0.267797E+09 | 0.366685E+09 | 0.300220E+09 | 0.637401E+09 |
Maximum of Months | 0.273117E+10 | 0.138010E+10 | 0.139499E+10 | 0.352168E+10 | 0.298861E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694730E+09 | 0.279982E+09 | 0.414749E+09 | 0.333271E+09 | 0.298856E+10 |
February | 0.107105E+10 | 0.526473E+09 | 0.544572E+09 | 0.771825E+09 | 0.206642E+10 |
March | 0.151754E+10 | 0.556048E+09 | 0.961488E+09 | 0.114359E+10 | 0.196700E+10 |
April | 0.191724E+10 | 0.849427E+09 | 0.106782E+10 | 0.180373E+10 | 0.143363E+10 |
May | 0.245054E+10 | 0.111758E+10 | 0.133296E+10 | 0.259764E+10 | 0.108811E+10 |
June | 0.258009E+10 | 0.118513E+10 | 0.139496E+10 | 0.306777E+10 | 0.723092E+09 |
July | 0.273112E+10 | 0.138007E+10 | 0.135104E+10 | 0.352161E+10 | 0.637390E+09 |
August | 0.231909E+10 | 0.113816E+10 | 0.118093E+10 | 0.289410E+10 | 0.709635E+09 |
September | 0.180538E+10 | 0.912728E+09 | 0.892654E+09 | 0.207517E+10 | 0.934274E+09 |
October | 0.133336E+10 | 0.662477E+09 | 0.670887E+09 | 0.124562E+10 | 0.145745E+10 |
November | 0.913446E+09 | 0.453147E+09 | 0.460299E+09 | 0.666267E+09 | 0.197917E+10 |
December | 0.634470E+09 | 0.267792E+09 | 0.366678E+09 | 0.300214E+09 | 0.277466E+10 |
Annual Sum or Average | 0.199681E+11 | 0.932902E+10 | 0.106390E+11 | 0.204208E+11 | 0.187594E+11 |
Minimum of Months | 0.634470E+09 | 0.267792E+09 | 0.366678E+09 | 0.300214E+09 | 0.637390E+09 |
Maximum of Months | 0.273112E+10 | 0.138007E+10 | 0.139496E+10 | 0.352161E+10 | 0.298856E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150310E+10 | 0.00 | 0.150310E+10 | 43734439.99 | 0.127407E+11 |
February | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.322618E+09 | 0.854882E+10 |
March | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.118346E+10 | 0.768374E+10 |
April | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.199138E+10 | 0.532000E+10 |
May | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.381631E+10 | 0.410463E+10 |
June | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.596691E+10 | 0.252619E+10 |
July | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.670155E+10 | 0.217208E+10 |
August | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.488344E+10 | 0.248389E+10 |
September | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.275262E+10 | 0.368291E+10 |
October | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.108072E+10 | 0.564252E+10 |
November | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.244510E+09 | 0.775883E+10 |
December | 0.126043E+10 | 0.00 | 0.126043E+10 | 22796551.86 | 0.109296E+11 |
Annual Sum or Average | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.290100E+11 | 0.735939E+11 |
Minimum of Months | 0.126043E+10 | 0.00 | 0.126043E+10 | 22796551.86 | 0.217208E+10 |
Maximum of Months | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.670155E+10 | 0.127407E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.122372E+10 | 0.783582E+10 |
February | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.241142E+10 | 0.530416E+10 |
March | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.389184E+10 | 0.490577E+10 |
April | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.573518E+10 | 0.346030E+10 |
May | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.704757E+10 | 0.280053E+10 |
June | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.102068E+11 | 0.176269E+10 |
July | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.119566E+11 | 0.148678E+10 |
August | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.101386E+11 | 0.167959E+10 |
September | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.626580E+10 | 0.238146E+10 |
October | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.382422E+10 | 0.362217E+10 |
November | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.170432E+10 | 0.482094E+10 |
December | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.953211E+09 | 0.673391E+10 |
Annual Sum or Average | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.653592E+11 | 0.467941E+11 |
Minimum of Months | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.953211E+09 | 0.148678E+10 |
Maximum of Months | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.119566E+11 | 0.783582E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.984137E+10 | 0.112034E+11 |
February | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.124525E+11 | 0.772498E+10 |
March | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.122776E+11 | 0.768452E+10 |
April | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.992803E+10 | 0.558168E+10 |
May | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.928185E+10 | 0.452786E+10 |
June | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.102334E+11 | 0.296368E+10 |
July | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.127335E+11 | 0.244102E+10 |
August | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.146788E+11 | 0.276708E+10 |
September | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.145820E+11 | 0.385807E+10 |
October | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.144199E+11 | 0.566153E+10 |
November | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.115714E+11 | 0.704399E+10 |
December | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.956879E+10 | 0.960739E+10 |
Annual Sum or Average | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.141569E+12 | 0.710652E+11 |
Minimum of Months | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.928185E+10 | 0.244102E+10 |
Maximum of Months | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.146788E+11 | 0.112034E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.105746E+10 | 0.828797E+10 |
February | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.243098E+10 | 0.554911E+10 |
March | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.357908E+10 | 0.522198E+10 |
April | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.555135E+10 | 0.377327E+10 |
May | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.782055E+10 | 0.305520E+10 |
June | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.925294E+10 | 0.201631E+10 |
July | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.106561E+11 | 0.175094E+10 |
August | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.879652E+10 | 0.189928E+10 |
September | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.625478E+10 | 0.261743E+10 |
October | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.383927E+10 | 0.390262E+10 |
November | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.210993E+10 | 0.511062E+10 |
December | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.100168E+10 | 0.708356E+10 |
Annual Sum or Average | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.623506E+11 | 0.502683E+11 |
Minimum of Months | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.100168E+10 | 0.175094E+10 |
Maximum of Months | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.106561E+11 | 0.828797E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150310E+10 | 0.00 | 0.150310E+10 | 68758582.03 | 0.122249E+11 |
February | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.398558E+09 | 0.810379E+10 |
March | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.132269E+10 | 0.720016E+10 |
April | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.213469E+10 | 0.492372E+10 |
May | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.390772E+10 | 0.386970E+10 |
June | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.597659E+10 | 0.246716E+10 |
July | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.667915E+10 | 0.215001E+10 |
August | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.488357E+10 | 0.242228E+10 |
September | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.280874E+10 | 0.348335E+10 |
October | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.122909E+10 | 0.514900E+10 |
November | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.315431E+09 | 0.711344E+10 |
December | 0.126043E+10 | 0.00 | 0.126043E+10 | 32667854.08 | 0.103456E+11 |
Annual Sum or Average | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.297576E+11 | 0.694532E+11 |
Minimum of Months | 0.126043E+10 | 0.00 | 0.126043E+10 | 32667854.08 | 0.215001E+10 |
Maximum of Months | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.667915E+10 | 0.122249E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.127629E+10 | 0.753546E+10 |
February | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.250251E+10 | 0.502768E+10 |
March | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.401322E+10 | 0.460417E+10 |
April | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.582942E+10 | 0.322528E+10 |
May | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.709495E+10 | 0.265890E+10 |
June | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.102085E+11 | 0.172870E+10 |
July | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.119418E+11 | 0.147363E+10 |
August | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.101388E+11 | 0.164615E+10 |
September | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.630289E+10 | 0.227373E+10 |
October | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.393452E+10 | 0.333457E+10 |
November | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.181350E+10 | 0.441250E+10 |
December | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.100810E+10 | 0.636663E+10 |
Annual Sum or Average | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.660645E+11 | 0.442874E+11 |
Minimum of Months | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.100810E+10 | 0.147363E+10 |
Maximum of Months | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.119418E+11 | 0.753546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.996333E+10 | 0.106788E+11 |
February | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.125690E+11 | 0.731270E+10 |
March | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.124087E+11 | 0.722877E+10 |
April | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.100227E+11 | 0.521670E+10 |
May | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.932532E+10 | 0.429496E+10 |
June | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.102162E+11 | 0.289265E+10 |
July | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.126917E+11 | 0.241144E+10 |
August | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.146495E+11 | 0.270642E+10 |
September | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.145984E+11 | 0.368847E+10 |
October | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.145332E+11 | 0.525362E+10 |
November | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.117495E+11 | 0.650163E+10 |
December | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.973337E+10 | 0.902493E+10 |
Annual Sum or Average | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.142461E+12 | 0.672111E+11 |
Minimum of Months | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.932532E+10 | 0.241144E+10 |
Maximum of Months | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.146495E+11 | 0.106788E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.108992E+10 | 0.796645E+10 |
February | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.248270E+10 | 0.529581E+10 |
March | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.365455E+10 | 0.494159E+10 |
April | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.561470E+10 | 0.355157E+10 |
May | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.784338E+10 | 0.291331E+10 |
June | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.923429E+10 | 0.197140E+10 |
July | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.106261E+11 | 0.173018E+10 |
August | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.877703E+10 | 0.186010E+10 |
September | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.626955E+10 | 0.250330E+10 |
October | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.391295E+10 | 0.363036E+10 |
November | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.217671E+10 | 0.474673E+10 |
December | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.103779E+10 | 0.673002E+10 |
Annual Sum or Average | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.627197E+11 | 0.478408E+11 |
Minimum of Months | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.103779E+10 | 0.173018E+10 |
Maximum of Months | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.106261E+11 | 0.796645E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.98 | 5097.69 | 561.19 | 0.00 | 561.19 | 0.00 | 0.00 |
February | 84.54 | 3846.00 | 792.37 | 0.00 | 792.37 | 0.00 | 0.00 |
March | 370.69 | 3128.17 | 1287.17 | 0.00 | 1287.17 | 0.00 | 0.00 |
April | 703.59 | 2246.53 | 1467.65 | 8.56 | 1459.09 | 0.00 | 0.00 |
May | 1392.10 | 1619.23 | 1927.38 | 114.21 | 1813.17 | 0.00 | 0.00 |
June | 2276.50 | 1012.19 | 2244.32 | 257.97 | 1986.36 | 0.00 | 0.00 |
July | 2455.28 | 852.95 | 2050.31 | 192.04 | 1858.27 | 0.00 | 0.00 |
August | 1781.69 | 976.16 | 1642.92 | 44.04 | 1598.89 | 0.00 | 0.00 |
September | 1033.03 | 1507.49 | 1230.44 | 0.44 | 1230.00 | 0.00 | 0.00 |
October | 351.56 | 2313.64 | 897.53 | 0.00 | 897.53 | 0.00 | 0.00 |
November | 66.33 | 3352.17 | 610.15 | 0.00 | 610.15 | 0.00 | 0.00 |
December | 2.28 | 4540.55 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Annual Sum or Average | 882.00 | 2535.94 | 1267.71 | 51.69 | 1216.02 | 0.00 | 0.00 |
Minimum of Months | 2.28 | 852.95 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Maximum of Months | 2455.28 | 5097.69 | 2244.32 | 257.97 | 1986.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.88 | 3117.48 | 859.09 | 393.86 | 465.23 | 0.00 | 0.00 |
February | 969.95 | 2336.75 | 1343.70 | 667.12 | 676.59 | 0.00 | 0.00 |
March | 1437.66 | 1933.25 | 1806.73 | 747.57 | 1059.15 | 0.00 | 0.00 |
April | 2213.80 | 1399.14 | 2305.21 | 1142.44 | 1162.76 | 0.00 | 0.00 |
May | 2643.96 | 1083.63 | 2546.40 | 1132.99 | 1413.41 | 0.00 | 0.00 |
June | 3963.07 | 689.03 | 3295.99 | 1696.11 | 1599.87 | 0.00 | 0.00 |
July | 4481.31 | 564.04 | 3459.23 | 1955.60 | 1503.63 | 0.00 | 0.00 |
August | 3804.32 | 630.27 | 3006.22 | 1674.98 | 1331.25 | 0.00 | 0.00 |
September | 2430.95 | 946.57 | 2126.61 | 1097.75 | 1028.86 | 0.00 | 0.00 |
October | 1421.04 | 1428.15 | 1525.73 | 774.74 | 750.99 | 0.00 | 0.00 |
November | 635.63 | 2005.09 | 966.98 | 451.45 | 515.53 | 0.00 | 0.00 |
December | 329.99 | 2730.32 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Annual Sum or Average | 2069.99 | 1569.11 | 1999.68 | 1005.15 | 994.53 | 0.00 | 0.00 |
Minimum of Months | 329.99 | 564.04 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Maximum of Months | 4481.31 | 3117.48 | 3459.23 | 1955.60 | 1599.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3683.04 | 4272.51 | 3955.80 | 2825.31 | 1130.49 | 0.00 | 0.00 |
February | 5173.79 | 3272.58 | 5037.65 | 3623.26 | 1414.38 | 0.00 | 0.00 |
March | 4608.30 | 2944.15 | 4503.00 | 2528.68 | 1974.32 | 0.00 | 0.00 |
April | 3842.38 | 2230.13 | 3619.66 | 1731.31 | 1888.35 | 0.00 | 0.00 |
May | 3484.53 | 1726.57 | 3215.97 | 1068.11 | 2147.86 | 0.00 | 0.00 |
June | 3960.96 | 1168.14 | 3195.39 | 931.93 | 2263.46 | 0.00 | 0.00 |
July | 4752.33 | 939.46 | 3444.95 | 1272.56 | 2172.40 | 0.00 | 0.00 |
August | 5490.12 | 1056.63 | 4094.10 | 2064.17 | 2029.93 | 0.00 | 0.00 |
September | 5667.92 | 1507.94 | 4540.85 | 2782.33 | 1758.52 | 0.00 | 0.00 |
October | 5420.38 | 2156.98 | 4747.22 | 3282.64 | 1464.58 | 0.00 | 0.00 |
November | 4476.54 | 2798.90 | 4328.06 | 3135.07 | 1192.99 | 0.00 | 0.00 |
December | 3563.28 | 3734.19 | 3761.74 | 2716.36 | 1045.38 | 0.00 | 0.00 |
Annual Sum or Average | 4505.10 | 2313.78 | 4030.08 | 2321.54 | 1708.54 | 0.00 | 0.00 |
Minimum of Months | 3484.53 | 939.46 | 3195.39 | 931.93 | 1045.38 | 0.00 | 0.00 |
Maximum of Months | 5667.92 | 4272.51 | 5037.65 | 3623.26 | 2263.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.29 | 3347.44 | 778.16 | 313.60 | 464.55 | 0.00 | 0.00 |
February | 957.14 | 2562.55 | 1328.20 | 652.88 | 675.32 | 0.00 | 0.00 |
March | 1280.92 | 2203.21 | 1699.77 | 622.82 | 1076.95 | 0.00 | 0.00 |
April | 2087.68 | 1659.31 | 2219.06 | 983.15 | 1235.91 | 0.00 | 0.00 |
May | 2909.58 | 1218.77 | 2744.82 | 1251.78 | 1493.03 | 0.00 | 0.00 |
June | 3550.71 | 836.92 | 2986.25 | 1371.70 | 1614.56 | 0.00 | 0.00 |
July | 3944.51 | 713.93 | 3059.09 | 1545.80 | 1513.28 | 0.00 | 0.00 |
August | 3241.64 | 794.85 | 2597.58 | 1274.84 | 1322.74 | 0.00 | 0.00 |
September | 2401.85 | 1081.35 | 2089.59 | 1056.41 | 1033.18 | 0.00 | 0.00 |
October | 1395.20 | 1632.47 | 1493.48 | 742.03 | 751.45 | 0.00 | 0.00 |
November | 771.15 | 2290.73 | 1057.24 | 524.48 | 532.76 | 0.00 | 0.00 |
December | 336.27 | 3107.85 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Annual Sum or Average | 1942.64 | 1784.59 | 1899.57 | 887.47 | 1012.10 | 0.00 | 0.00 |
Minimum of Months | 336.27 | 713.93 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Maximum of Months | 3944.51 | 3347.44 | 3059.09 | 1545.80 | 1614.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.33 | 4756.85 | 561.19 | 0.00 | 561.19 | 0.00 | 0.00 |
February | 133.36 | 3533.74 | 792.37 | 0.00 | 792.37 | 0.00 | 0.00 |
March | 441.85 | 2868.78 | 1287.17 | 0.00 | 1287.17 | 0.00 | 0.00 |
April | 768.28 | 2052.47 | 1467.64 | 8.56 | 1459.08 | 0.00 | 0.00 |
May | 1424.85 | 1532.49 | 1927.37 | 114.21 | 1813.16 | 0.00 | 0.00 |
June | 2302.05 | 974.61 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
July | 2502.07 | 810.96 | 2050.30 | 192.04 | 1858.27 | 0.00 | 0.00 |
August | 1823.27 | 927.38 | 1642.92 | 44.04 | 1598.88 | 0.00 | 0.00 |
September | 1061.97 | 1420.88 | 1230.43 | 0.44 | 1229.99 | 0.00 | 0.00 |
October | 403.49 | 2106.68 | 897.53 | 0.00 | 897.53 | 0.00 | 0.00 |
November | 94.33 | 2993.37 | 610.15 | 0.00 | 610.15 | 0.00 | 0.00 |
December | 8.51 | 4080.63 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Annual Sum or Average | 919.90 | 2333.65 | 1267.70 | 51.69 | 1216.01 | 0.00 | 0.00 |
Minimum of Months | 8.51 | 810.96 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Maximum of Months | 2502.07 | 4756.85 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.89 | 2925.56 | 859.09 | 393.86 | 465.23 | 0.00 | 0.00 |
February | 996.78 | 2192.53 | 1343.70 | 667.11 | 676.58 | 0.00 | 0.00 |
March | 1453.05 | 1831.61 | 1806.72 | 747.57 | 1059.15 | 0.00 | 0.00 |
April | 2212.65 | 1334.99 | 2305.20 | 1142.44 | 1162.76 | 0.00 | 0.00 |
May | 2631.26 | 1045.60 | 2546.39 | 1132.98 | 1413.41 | 0.00 | 0.00 |
June | 3937.80 | 680.05 | 3295.97 | 1696.11 | 1599.87 | 0.00 | 0.00 |
July | 4464.08 | 555.10 | 3459.22 | 1955.59 | 1503.63 | 0.00 | 0.00 |
August | 3785.31 | 627.09 | 3006.21 | 1674.97 | 1331.24 | 0.00 | 0.00 |
September | 2417.36 | 918.77 | 2126.60 | 1097.74 | 1028.86 | 0.00 | 0.00 |
October | 1427.80 | 1352.36 | 1525.72 | 774.74 | 750.99 | 0.00 | 0.00 |
November | 657.53 | 1859.93 | 966.97 | 451.45 | 515.52 | 0.00 | 0.00 |
December | 355.89 | 2514.15 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Annual Sum or Average | 2072.53 | 1483.83 | 1999.67 | 1005.15 | 994.52 | 0.00 | 0.00 |
Minimum of Months | 355.89 | 555.10 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Maximum of Months | 4464.08 | 2925.56 | 3459.22 | 1955.59 | 1599.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3674.35 | 4182.86 | 3955.78 | 2825.30 | 1130.48 | 0.00 | 0.00 |
February | 5147.38 | 3193.19 | 5037.63 | 3623.25 | 1414.38 | 0.00 | 0.00 |
March | 4583.95 | 2869.07 | 4502.98 | 2528.67 | 1974.31 | 0.00 | 0.00 |
April | 3830.26 | 2153.43 | 3619.64 | 1731.30 | 1888.35 | 0.00 | 0.00 |
May | 3465.45 | 1690.51 | 3215.96 | 1068.11 | 2147.85 | 0.00 | 0.00 |
June | 3948.07 | 1143.40 | 3195.38 | 931.93 | 2263.46 | 0.00 | 0.00 |
July | 4754.14 | 911.37 | 3444.94 | 1272.55 | 2172.39 | 0.00 | 0.00 |
August | 5480.45 | 1033.11 | 4094.09 | 2064.17 | 2029.92 | 0.00 | 0.00 |
September | 5625.78 | 1488.45 | 4540.83 | 2782.32 | 1758.52 | 0.00 | 0.00 |
October | 5383.79 | 2113.77 | 4747.20 | 3282.63 | 1464.57 | 0.00 | 0.00 |
November | 4464.29 | 2717.59 | 4328.04 | 3135.06 | 1192.98 | 0.00 | 0.00 |
December | 3572.58 | 3586.99 | 3761.73 | 2716.35 | 1045.38 | 0.00 | 0.00 |
Annual Sum or Average | 4489.14 | 2253.46 | 4030.07 | 2321.53 | 1708.53 | 0.00 | 0.00 |
Minimum of Months | 3465.45 | 911.37 | 3195.38 | 931.93 | 1045.38 | 0.00 | 0.00 |
Maximum of Months | 5625.78 | 4182.86 | 5037.63 | 3623.25 | 2263.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.81 | 3094.37 | 778.15 | 313.60 | 464.55 | 0.00 | 0.00 |
February | 1004.87 | 2293.78 | 1328.19 | 652.87 | 675.32 | 0.00 | 0.00 |
March | 1336.27 | 1949.66 | 1699.76 | 622.82 | 1076.94 | 0.00 | 0.00 |
April | 2141.72 | 1455.74 | 2219.05 | 983.14 | 1235.91 | 0.00 | 0.00 |
May | 2919.86 | 1140.68 | 2744.81 | 1251.78 | 1493.03 | 0.00 | 0.00 |
June | 3569.81 | 777.90 | 2986.24 | 1371.69 | 1614.55 | 0.00 | 0.00 |
July | 3978.54 | 653.73 | 3059.07 | 1545.79 | 1513.28 | 0.00 | 0.00 |
August | 3284.24 | 709.11 | 2597.57 | 1274.83 | 1322.74 | 0.00 | 0.00 |
September | 2413.11 | 1009.81 | 2089.58 | 1056.41 | 1033.17 | 0.00 | 0.00 |
October | 1433.42 | 1457.07 | 1493.48 | 742.03 | 751.45 | 0.00 | 0.00 |
November | 814.02 | 1971.69 | 1057.24 | 524.48 | 532.76 | 0.00 | 0.00 |
December | 373.98 | 2644.70 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Annual Sum or Average | 1977.13 | 1594.00 | 1899.56 | 887.47 | 1012.09 | 0.00 | 0.00 |
Minimum of Months | 373.98 | 653.73 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Maximum of Months | 3978.54 | 3094.37 | 3059.07 | 1545.79 | 1614.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 25.67 | 4564.26 | 561.19 | 0.00 | 561.19 | 0.00 | 0.00 |
February | 164.75 | 3349.78 | 792.37 | 0.00 | 792.37 | 0.00 | 0.00 |
March | 493.84 | 2688.23 | 1287.17 | 0.00 | 1287.17 | 0.00 | 0.00 |
April | 823.57 | 1899.59 | 1467.64 | 8.56 | 1459.08 | 0.00 | 0.00 |
May | 1458.98 | 1444.78 | 1927.37 | 114.21 | 1813.16 | 0.00 | 0.00 |
June | 2305.78 | 951.84 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
July | 2493.71 | 802.72 | 2050.30 | 192.04 | 1858.27 | 0.00 | 0.00 |
August | 1823.31 | 904.38 | 1642.92 | 44.04 | 1598.88 | 0.00 | 0.00 |
September | 1083.62 | 1343.88 | 1230.43 | 0.44 | 1229.99 | 0.00 | 0.00 |
October | 458.89 | 1922.42 | 897.53 | 0.00 | 897.53 | 0.00 | 0.00 |
November | 121.69 | 2744.38 | 610.15 | 0.00 | 610.15 | 0.00 | 0.00 |
December | 12.20 | 3862.62 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Annual Sum or Average | 943.61 | 2202.35 | 1267.70 | 51.69 | 1216.01 | 0.00 | 0.00 |
Minimum of Months | 12.20 | 802.72 | 470.59 | 0.00 | 470.59 | 0.00 | 0.00 |
Maximum of Months | 2493.71 | 4564.26 | 2244.31 | 257.96 | 1986.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 476.51 | 2813.42 | 859.09 | 393.86 | 465.23 | 0.00 | 0.00 |
February | 1034.44 | 2078.24 | 1343.70 | 667.11 | 676.58 | 0.00 | 0.00 |
March | 1498.37 | 1719.00 | 1806.72 | 747.57 | 1059.15 | 0.00 | 0.00 |
April | 2249.00 | 1244.32 | 2305.20 | 1142.44 | 1162.76 | 0.00 | 0.00 |
May | 2648.95 | 992.72 | 2546.39 | 1132.98 | 1413.41 | 0.00 | 0.00 |
June | 3938.47 | 666.94 | 3295.97 | 1696.11 | 1599.87 | 0.00 | 0.00 |
July | 4458.55 | 550.19 | 3459.22 | 1955.59 | 1503.63 | 0.00 | 0.00 |
August | 3785.39 | 614.60 | 3006.21 | 1674.97 | 1331.24 | 0.00 | 0.00 |
September | 2431.67 | 877.21 | 2126.60 | 1097.74 | 1028.86 | 0.00 | 0.00 |
October | 1468.98 | 1244.99 | 1525.72 | 774.74 | 750.99 | 0.00 | 0.00 |
November | 699.65 | 1702.35 | 966.97 | 451.45 | 515.52 | 0.00 | 0.00 |
December | 376.38 | 2377.03 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Annual Sum or Average | 2094.89 | 1404.34 | 1999.67 | 1005.15 | 994.52 | 0.00 | 0.00 |
Minimum of Months | 376.38 | 550.19 | 713.20 | 306.32 | 406.88 | 0.00 | 0.00 |
Maximum of Months | 4458.55 | 2813.42 | 3459.22 | 1955.59 | 1599.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3719.88 | 3987.01 | 3955.78 | 2825.30 | 1130.48 | 0.00 | 0.00 |
February | 5195.50 | 3022.78 | 5037.63 | 3623.25 | 1414.38 | 0.00 | 0.00 |
March | 4632.89 | 2698.91 | 4502.98 | 2528.67 | 1974.31 | 0.00 | 0.00 |
April | 3866.79 | 2012.62 | 3619.64 | 1731.30 | 1888.35 | 0.00 | 0.00 |
May | 3481.68 | 1603.55 | 3215.96 | 1068.11 | 2147.85 | 0.00 | 0.00 |
June | 3941.43 | 1115.99 | 3195.38 | 931.93 | 2263.46 | 0.00 | 0.00 |
July | 4738.55 | 900.33 | 3444.94 | 1272.55 | 2172.39 | 0.00 | 0.00 |
August | 5469.51 | 1010.46 | 4094.09 | 2064.17 | 2029.92 | 0.00 | 0.00 |
September | 5632.08 | 1423.02 | 4540.83 | 2782.32 | 1758.52 | 0.00 | 0.00 |
October | 5426.06 | 1961.48 | 4747.20 | 3282.63 | 1464.57 | 0.00 | 0.00 |
November | 4533.00 | 2508.35 | 4328.04 | 3135.06 | 1192.98 | 0.00 | 0.00 |
December | 3634.03 | 3369.52 | 3761.73 | 2716.35 | 1045.38 | 0.00 | 0.00 |
Annual Sum or Average | 4517.41 | 2131.25 | 4030.07 | 2321.53 | 1708.53 | 0.00 | 0.00 |
Minimum of Months | 3481.68 | 900.33 | 3195.38 | 931.93 | 1045.38 | 0.00 | 0.00 |
Maximum of Months | 5632.08 | 3987.01 | 5037.63 | 3623.25 | 2263.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 406.93 | 2974.33 | 778.15 | 313.60 | 464.55 | 0.00 | 0.00 |
February | 1026.25 | 2189.07 | 1328.19 | 652.87 | 675.32 | 0.00 | 0.00 |
March | 1364.45 | 1844.98 | 1699.76 | 622.82 | 1076.94 | 0.00 | 0.00 |
April | 2166.16 | 1370.20 | 2219.05 | 983.14 | 1235.91 | 0.00 | 0.00 |
May | 2928.38 | 1087.71 | 2744.81 | 1251.78 | 1493.03 | 0.00 | 0.00 |
June | 3562.61 | 760.57 | 2986.24 | 1371.69 | 1614.55 | 0.00 | 0.00 |
July | 3967.33 | 645.98 | 3059.07 | 1545.79 | 1513.28 | 0.00 | 0.00 |
August | 3276.97 | 694.48 | 2597.57 | 1274.83 | 1322.74 | 0.00 | 0.00 |
September | 2418.81 | 965.78 | 2089.58 | 1056.41 | 1033.17 | 0.00 | 0.00 |
October | 1460.93 | 1355.42 | 1493.48 | 742.03 | 751.45 | 0.00 | 0.00 |
November | 839.78 | 1831.30 | 1057.24 | 524.48 | 532.76 | 0.00 | 0.00 |
December | 387.47 | 2512.70 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Annual Sum or Average | 1988.83 | 1517.02 | 1899.56 | 887.47 | 1012.09 | 0.00 | 0.00 |
Minimum of Months | 387.47 | 645.98 | 710.66 | 299.95 | 410.71 | 0.00 | 0.00 |
Maximum of Months | 3967.33 | 2974.33 | 3059.07 | 1545.79 | 1614.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18698400.28 | 0.136537E+11 | 0.150310E+10 | 0.00 | 0.150310E+10 | 0.00 | 0.00 |
February | 0.204510E+09 | 0.930425E+10 | 0.191691E+10 | 0.00 | 0.191691E+10 | 0.00 | 0.00 |
March | 0.992852E+09 | 0.837848E+10 | 0.344757E+10 | 0.00 | 0.344757E+10 | 0.00 | 0.00 |
April | 0.182369E+10 | 0.582301E+10 | 0.380415E+10 | 22200158.45 | 0.378195E+10 | 0.00 | 0.00 |
May | 0.372861E+10 | 0.433694E+10 | 0.516228E+10 | 0.305897E+09 | 0.485639E+10 | 0.00 | 0.00 |
June | 0.590068E+10 | 0.262361E+10 | 0.581728E+10 | 0.668647E+09 | 0.514864E+10 | 0.00 | 0.00 |
July | 0.657621E+10 | 0.228453E+10 | 0.549155E+10 | 0.514350E+09 | 0.497720E+10 | 0.00 | 0.00 |
August | 0.477207E+10 | 0.261454E+10 | 0.440041E+10 | 0.117951E+09 | 0.428246E+10 | 0.00 | 0.00 |
September | 0.267762E+10 | 0.390741E+10 | 0.318929E+10 | 1144490.71 | 0.318815E+10 | 0.00 | 0.00 |
October | 0.941629E+09 | 0.619685E+10 | 0.240395E+10 | 0.00 | 0.240395E+10 | 0.00 | 0.00 |
November | 0.171926E+09 | 0.868884E+10 | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.00 | 0.00 |
December | 6114748.56 | 0.121614E+11 | 0.126044E+10 | 0.00 | 0.126044E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.278146E+11 | 0.799735E+11 | 0.399784E+11 | 0.163019E+10 | 0.383483E+11 | 0.00 | 0.00 |
Minimum of Months | 6114748.56 | 0.228453E+10 | 0.126044E+10 | 0.00 | 0.126044E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657621E+10 | 0.136537E+11 | 0.581728E+10 | 0.668647E+09 | 0.514864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115942E+10 | 0.834985E+10 | 0.230100E+10 | 0.105492E+10 | 0.124608E+10 | 0.00 | 0.00 |
February | 0.234651E+10 | 0.565306E+10 | 0.325068E+10 | 0.161389E+10 | 0.163679E+10 | 0.00 | 0.00 |
March | 0.385062E+10 | 0.517802E+10 | 0.483914E+10 | 0.200230E+10 | 0.283684E+10 | 0.00 | 0.00 |
April | 0.573817E+10 | 0.362657E+10 | 0.597510E+10 | 0.296121E+10 | 0.301388E+10 | 0.00 | 0.00 |
May | 0.708159E+10 | 0.290240E+10 | 0.682028E+10 | 0.303460E+10 | 0.378568E+10 | 0.00 | 0.00 |
June | 0.102723E+11 | 0.178598E+10 | 0.854320E+10 | 0.439632E+10 | 0.414687E+10 | 0.00 | 0.00 |
July | 0.120027E+11 | 0.151073E+10 | 0.926520E+10 | 0.523787E+10 | 0.402734E+10 | 0.00 | 0.00 |
August | 0.101895E+11 | 0.168812E+10 | 0.805187E+10 | 0.448625E+10 | 0.356562E+10 | 0.00 | 0.00 |
September | 0.630102E+10 | 0.245352E+10 | 0.551217E+10 | 0.284536E+10 | 0.266681E+10 | 0.00 | 0.00 |
October | 0.380611E+10 | 0.382515E+10 | 0.408652E+10 | 0.207507E+10 | 0.201145E+10 | 0.00 | 0.00 |
November | 0.164756E+10 | 0.519719E+10 | 0.250641E+10 | 0.117016E+10 | 0.133625E+10 | 0.00 | 0.00 |
December | 0.883853E+09 | 0.731289E+10 | 0.191024E+10 | 0.820453E+09 | 0.108979E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.652794E+11 | 0.494835E+11 | 0.630618E+11 | 0.316984E+11 | 0.313634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.883853E+09 | 0.151073E+10 | 0.191024E+10 | 0.820453E+09 | 0.108979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.120027E+11 | 0.834985E+10 | 0.926520E+10 | 0.523787E+10 | 0.414687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.986465E+10 | 0.114435E+11 | 0.105952E+11 | 0.756731E+10 | 0.302790E+10 | 0.00 | 0.00 |
February | 0.125164E+11 | 0.791703E+10 | 0.121871E+11 | 0.876540E+10 | 0.342168E+10 | 0.00 | 0.00 |
March | 0.123429E+11 | 0.788561E+10 | 0.120608E+11 | 0.677281E+10 | 0.528802E+10 | 0.00 | 0.00 |
April | 0.995945E+10 | 0.578050E+10 | 0.938215E+10 | 0.448754E+10 | 0.489461E+10 | 0.00 | 0.00 |
May | 0.933296E+10 | 0.462445E+10 | 0.861366E+10 | 0.286083E+10 | 0.575283E+10 | 0.00 | 0.00 |
June | 0.102668E+11 | 0.302783E+10 | 0.828246E+10 | 0.241556E+10 | 0.586690E+10 | 0.00 | 0.00 |
July | 0.127287E+11 | 0.251625E+10 | 0.922697E+10 | 0.340841E+10 | 0.581855E+10 | 0.00 | 0.00 |
August | 0.147047E+11 | 0.283007E+10 | 0.109656E+11 | 0.552868E+10 | 0.543696E+10 | 0.00 | 0.00 |
September | 0.146912E+11 | 0.390858E+10 | 0.117699E+11 | 0.721179E+10 | 0.455810E+10 | 0.00 | 0.00 |
October | 0.145179E+11 | 0.577724E+10 | 0.127149E+11 | 0.879222E+10 | 0.392272E+10 | 0.00 | 0.00 |
November | 0.116032E+11 | 0.725474E+10 | 0.112183E+11 | 0.812610E+10 | 0.309222E+10 | 0.00 | 0.00 |
December | 0.954390E+10 | 0.100017E+11 | 0.100754E+11 | 0.727549E+10 | 0.279996E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142073E+12 | 0.729674E+11 | 0.127093E+12 | 0.732122E+11 | 0.538805E+11 | 0.00 | 0.00 |
Minimum of Months | 0.933296E+10 | 0.251625E+10 | 0.828246E+10 | 0.241556E+10 | 0.279996E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147047E+11 | 0.114435E+11 | 0.127149E+11 | 0.879222E+10 | 0.586690E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999826E+09 | 0.896578E+10 | 0.208422E+10 | 0.839955E+09 | 0.124426E+10 | 0.00 | 0.00 |
February | 0.231550E+10 | 0.619933E+10 | 0.321318E+10 | 0.157944E+10 | 0.163374E+10 | 0.00 | 0.00 |
March | 0.343081E+10 | 0.590108E+10 | 0.455266E+10 | 0.166816E+10 | 0.288450E+10 | 0.00 | 0.00 |
April | 0.541126E+10 | 0.430094E+10 | 0.575180E+10 | 0.254831E+10 | 0.320349E+10 | 0.00 | 0.00 |
May | 0.779301E+10 | 0.326437E+10 | 0.735172E+10 | 0.335278E+10 | 0.399894E+10 | 0.00 | 0.00 |
June | 0.920344E+10 | 0.216930E+10 | 0.774037E+10 | 0.355544E+10 | 0.418493E+10 | 0.00 | 0.00 |
July | 0.105650E+11 | 0.191219E+10 | 0.819346E+10 | 0.414027E+10 | 0.405318E+10 | 0.00 | 0.00 |
August | 0.868242E+10 | 0.212893E+10 | 0.695735E+10 | 0.341452E+10 | 0.354283E+10 | 0.00 | 0.00 |
September | 0.622560E+10 | 0.280286E+10 | 0.541621E+10 | 0.273822E+10 | 0.267799E+10 | 0.00 | 0.00 |
October | 0.373691E+10 | 0.437241E+10 | 0.400014E+10 | 0.198745E+10 | 0.201269E+10 | 0.00 | 0.00 |
November | 0.199882E+10 | 0.593757E+10 | 0.274037E+10 | 0.135946E+10 | 0.138091E+10 | 0.00 | 0.00 |
December | 0.900653E+09 | 0.832407E+10 | 0.190343E+10 | 0.803385E+09 | 0.110005E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.612632E+11 | 0.562788E+11 | 0.599049E+11 | 0.279874E+11 | 0.319175E+11 | 0.00 | 0.00 |
Minimum of Months | 0.900653E+09 | 0.191219E+10 | 0.190343E+10 | 0.803385E+09 | 0.110005E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105650E+11 | 0.896578E+10 | 0.819346E+10 | 0.414027E+10 | 0.418493E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 43734439.99 | 0.127407E+11 | 0.150310E+10 | 0.00 | 0.150310E+10 | 0.00 | 0.00 |
February | 0.322618E+09 | 0.854882E+10 | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.00 | 0.00 |
March | 0.118346E+10 | 0.768374E+10 | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.00 | 0.00 |
April | 0.199138E+10 | 0.532000E+10 | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.00 | 0.00 |
May | 0.381631E+10 | 0.410463E+10 | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.00 | 0.00 |
June | 0.596691E+10 | 0.252619E+10 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
July | 0.670155E+10 | 0.217208E+10 | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.00 | 0.00 |
August | 0.488344E+10 | 0.248389E+10 | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.00 | 0.00 |
September | 0.275262E+10 | 0.368291E+10 | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.00 | 0.00 |
October | 0.108072E+10 | 0.564252E+10 | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.00 | 0.00 |
November | 0.244510E+09 | 0.775883E+10 | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.00 | 0.00 |
December | 22796551.86 | 0.109296E+11 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290100E+11 | 0.735939E+11 | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.00 | 0.00 |
Minimum of Months | 22796551.86 | 0.217208E+10 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Maximum of Months | 0.670155E+10 | 0.127407E+11 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122372E+10 | 0.783582E+10 | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.00 | 0.00 |
February | 0.241142E+10 | 0.530416E+10 | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.00 | 0.00 |
March | 0.389184E+10 | 0.490577E+10 | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.00 | 0.00 |
April | 0.573518E+10 | 0.346030E+10 | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.00 | 0.00 |
May | 0.704757E+10 | 0.280053E+10 | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.00 | 0.00 |
June | 0.102068E+11 | 0.176269E+10 | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.00 | 0.00 |
July | 0.119566E+11 | 0.148678E+10 | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.00 | 0.00 |
August | 0.101386E+11 | 0.167959E+10 | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.00 | 0.00 |
September | 0.626580E+10 | 0.238146E+10 | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.00 | 0.00 |
October | 0.382422E+10 | 0.362217E+10 | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.00 | 0.00 |
November | 0.170432E+10 | 0.482094E+10 | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.00 | 0.00 |
December | 0.953211E+09 | 0.673391E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.653592E+11 | 0.467941E+11 | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.00 | 0.00 |
Minimum of Months | 0.953211E+09 | 0.148678E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119566E+11 | 0.783582E+10 | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.984137E+10 | 0.112034E+11 | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.00 | 0.00 |
February | 0.124525E+11 | 0.772498E+10 | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.00 | 0.00 |
March | 0.122776E+11 | 0.768452E+10 | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.00 | 0.00 |
April | 0.992803E+10 | 0.558168E+10 | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.00 | 0.00 |
May | 0.928185E+10 | 0.452786E+10 | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.00 | 0.00 |
June | 0.102334E+11 | 0.296368E+10 | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.00 | 0.00 |
July | 0.127335E+11 | 0.244102E+10 | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.00 | 0.00 |
August | 0.146788E+11 | 0.276708E+10 | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.00 | 0.00 |
September | 0.145820E+11 | 0.385807E+10 | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.00 | 0.00 |
October | 0.144199E+11 | 0.566153E+10 | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.00 | 0.00 |
November | 0.115714E+11 | 0.704399E+10 | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.00 | 0.00 |
December | 0.956879E+10 | 0.960739E+10 | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141569E+12 | 0.710652E+11 | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.928185E+10 | 0.244102E+10 | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.146788E+11 | 0.112034E+11 | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105746E+10 | 0.828797E+10 | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.00 | 0.00 |
February | 0.243098E+10 | 0.554911E+10 | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.00 | 0.00 |
March | 0.357908E+10 | 0.522198E+10 | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.00 | 0.00 |
April | 0.555135E+10 | 0.377327E+10 | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.00 | 0.00 |
May | 0.782055E+10 | 0.305520E+10 | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.00 | 0.00 |
June | 0.925294E+10 | 0.201631E+10 | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.00 | 0.00 |
July | 0.106561E+11 | 0.175094E+10 | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.00 | 0.00 |
August | 0.879652E+10 | 0.189928E+10 | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.00 | 0.00 |
September | 0.625478E+10 | 0.261743E+10 | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.00 | 0.00 |
October | 0.383927E+10 | 0.390262E+10 | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.00 | 0.00 |
November | 0.210993E+10 | 0.511062E+10 | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.00 | 0.00 |
December | 0.100168E+10 | 0.708356E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.623506E+11 | 0.502683E+11 | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100168E+10 | 0.175094E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106561E+11 | 0.828797E+10 | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 68758582.03 | 0.122249E+11 | 0.150310E+10 | 0.00 | 0.150310E+10 | 0.00 | 0.00 |
February | 0.398558E+09 | 0.810379E+10 | 0.191690E+10 | 0.00 | 0.191690E+10 | 0.00 | 0.00 |
March | 0.132269E+10 | 0.720016E+10 | 0.344755E+10 | 0.00 | 0.344755E+10 | 0.00 | 0.00 |
April | 0.213469E+10 | 0.492372E+10 | 0.380413E+10 | 22200079.62 | 0.378193E+10 | 0.00 | 0.00 |
May | 0.390772E+10 | 0.386970E+10 | 0.516226E+10 | 0.305896E+09 | 0.485637E+10 | 0.00 | 0.00 |
June | 0.597659E+10 | 0.246716E+10 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
July | 0.667915E+10 | 0.215001E+10 | 0.549153E+10 | 0.514348E+09 | 0.497718E+10 | 0.00 | 0.00 |
August | 0.488357E+10 | 0.242228E+10 | 0.440039E+10 | 0.117951E+09 | 0.428244E+10 | 0.00 | 0.00 |
September | 0.280874E+10 | 0.348335E+10 | 0.318928E+10 | 1144486.65 | 0.318814E+10 | 0.00 | 0.00 |
October | 0.122909E+10 | 0.514900E+10 | 0.240394E+10 | 0.00 | 0.240394E+10 | 0.00 | 0.00 |
November | 0.315431E+09 | 0.711344E+10 | 0.158151E+10 | 0.00 | 0.158151E+10 | 0.00 | 0.00 |
December | 32667854.08 | 0.103456E+11 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.297576E+11 | 0.694532E+11 | 0.399783E+11 | 0.163018E+10 | 0.383481E+11 | 0.00 | 0.00 |
Minimum of Months | 32667854.08 | 0.215001E+10 | 0.126043E+10 | 0.00 | 0.126043E+10 | 0.00 | 0.00 |
Maximum of Months | 0.667915E+10 | 0.122249E+11 | 0.581726E+10 | 0.668645E+09 | 0.514862E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127629E+10 | 0.753546E+10 | 0.230099E+10 | 0.105491E+10 | 0.124608E+10 | 0.00 | 0.00 |
February | 0.250251E+10 | 0.502768E+10 | 0.325067E+10 | 0.161388E+10 | 0.163679E+10 | 0.00 | 0.00 |
March | 0.401322E+10 | 0.460417E+10 | 0.483912E+10 | 0.200229E+10 | 0.283683E+10 | 0.00 | 0.00 |
April | 0.582942E+10 | 0.322528E+10 | 0.597507E+10 | 0.296120E+10 | 0.301387E+10 | 0.00 | 0.00 |
May | 0.709495E+10 | 0.265890E+10 | 0.682025E+10 | 0.303459E+10 | 0.378567E+10 | 0.00 | 0.00 |
June | 0.102085E+11 | 0.172870E+10 | 0.854316E+10 | 0.439630E+10 | 0.414686E+10 | 0.00 | 0.00 |
July | 0.119418E+11 | 0.147363E+10 | 0.926516E+10 | 0.523784E+10 | 0.402732E+10 | 0.00 | 0.00 |
August | 0.101388E+11 | 0.164615E+10 | 0.805184E+10 | 0.448624E+10 | 0.356560E+10 | 0.00 | 0.00 |
September | 0.630289E+10 | 0.227373E+10 | 0.551215E+10 | 0.284535E+10 | 0.266680E+10 | 0.00 | 0.00 |
October | 0.393452E+10 | 0.333457E+10 | 0.408650E+10 | 0.207506E+10 | 0.201144E+10 | 0.00 | 0.00 |
November | 0.181350E+10 | 0.441250E+10 | 0.250640E+10 | 0.117016E+10 | 0.133624E+10 | 0.00 | 0.00 |
December | 0.100810E+10 | 0.636663E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.660645E+11 | 0.442874E+11 | 0.630615E+11 | 0.316983E+11 | 0.313633E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100810E+10 | 0.147363E+10 | 0.191023E+10 | 0.820450E+09 | 0.108978E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119418E+11 | 0.753546E+10 | 0.926516E+10 | 0.523784E+10 | 0.414686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.996333E+10 | 0.106788E+11 | 0.105952E+11 | 0.756728E+10 | 0.302789E+10 | 0.00 | 0.00 |
February | 0.125690E+11 | 0.731270E+10 | 0.121870E+11 | 0.876537E+10 | 0.342166E+10 | 0.00 | 0.00 |
March | 0.124087E+11 | 0.722877E+10 | 0.120608E+11 | 0.677279E+10 | 0.528801E+10 | 0.00 | 0.00 |
April | 0.100227E+11 | 0.521670E+10 | 0.938212E+10 | 0.448753E+10 | 0.489459E+10 | 0.00 | 0.00 |
May | 0.932532E+10 | 0.429496E+10 | 0.861363E+10 | 0.286082E+10 | 0.575281E+10 | 0.00 | 0.00 |
June | 0.102162E+11 | 0.289265E+10 | 0.828243E+10 | 0.241555E+10 | 0.586688E+10 | 0.00 | 0.00 |
July | 0.126917E+11 | 0.241144E+10 | 0.922693E+10 | 0.340840E+10 | 0.581853E+10 | 0.00 | 0.00 |
August | 0.146495E+11 | 0.270642E+10 | 0.109656E+11 | 0.552866E+10 | 0.543694E+10 | 0.00 | 0.00 |
September | 0.145984E+11 | 0.368847E+10 | 0.117698E+11 | 0.721176E+10 | 0.455808E+10 | 0.00 | 0.00 |
October | 0.145332E+11 | 0.525362E+10 | 0.127149E+11 | 0.879219E+10 | 0.392271E+10 | 0.00 | 0.00 |
November | 0.117495E+11 | 0.650163E+10 | 0.112183E+11 | 0.812607E+10 | 0.309221E+10 | 0.00 | 0.00 |
December | 0.973337E+10 | 0.902493E+10 | 0.100754E+11 | 0.727546E+10 | 0.279995E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142461E+12 | 0.672111E+11 | 0.127092E+12 | 0.732119E+11 | 0.538803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.932532E+10 | 0.241144E+10 | 0.828243E+10 | 0.241555E+10 | 0.279995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.146495E+11 | 0.106788E+11 | 0.127149E+11 | 0.879219E+10 | 0.586688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108992E+10 | 0.796645E+10 | 0.208421E+10 | 0.839952E+09 | 0.124426E+10 | 0.00 | 0.00 |
February | 0.248270E+10 | 0.529581E+10 | 0.321316E+10 | 0.157943E+10 | 0.163373E+10 | 0.00 | 0.00 |
March | 0.365455E+10 | 0.494159E+10 | 0.455264E+10 | 0.166816E+10 | 0.288449E+10 | 0.00 | 0.00 |
April | 0.561470E+10 | 0.355157E+10 | 0.575178E+10 | 0.254830E+10 | 0.320347E+10 | 0.00 | 0.00 |
May | 0.784338E+10 | 0.291331E+10 | 0.735169E+10 | 0.335276E+10 | 0.399892E+10 | 0.00 | 0.00 |
June | 0.923429E+10 | 0.197140E+10 | 0.774034E+10 | 0.355543E+10 | 0.418491E+10 | 0.00 | 0.00 |
July | 0.106261E+11 | 0.173018E+10 | 0.819342E+10 | 0.414026E+10 | 0.405317E+10 | 0.00 | 0.00 |
August | 0.877703E+10 | 0.186010E+10 | 0.695732E+10 | 0.341451E+10 | 0.354281E+10 | 0.00 | 0.00 |
September | 0.626955E+10 | 0.250330E+10 | 0.541619E+10 | 0.273821E+10 | 0.267798E+10 | 0.00 | 0.00 |
October | 0.391295E+10 | 0.363036E+10 | 0.400012E+10 | 0.198745E+10 | 0.201268E+10 | 0.00 | 0.00 |
November | 0.217671E+10 | 0.474673E+10 | 0.274036E+10 | 0.135945E+10 | 0.138091E+10 | 0.00 | 0.00 |
December | 0.103779E+10 | 0.673002E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.627197E+11 | 0.478408E+11 | 0.599047E+11 | 0.279873E+11 | 0.319174E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103779E+10 | 0.173018E+10 | 0.190342E+10 | 0.803382E+09 | 0.110004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106261E+11 | 0.796645E+10 | 0.819342E+10 | 0.414026E+10 | 0.418491E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.438920E+11 | -0.434465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445506919.5 | 60.05 | 0.00 | 0.00 |
February | 0.405627E+11 | -0.401603E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -402432552.1 | 60.05 | 0.00 | 0.00 |
March | 0.472086E+11 | -0.467627E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445898269.9 | 60.05 | 0.00 | 0.00 |
April | 0.413089E+11 | -0.408794E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429434105.9 | 60.05 | 0.00 | 0.00 |
May | 0.417472E+11 | -0.413036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443543976.2 | 60.05 | 0.00 | 0.00 |
June | 0.388886E+11 | -0.384626E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -425958330.8 | 60.05 | 0.00 | 0.00 |
July | 0.351800E+11 | -0.347545E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -425530586.9 | 60.05 | 0.00 | 0.00 |
August | 0.376444E+11 | -0.372113E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -433068360.2 | 60.05 | 0.00 | 0.00 |
September | 0.346346E+11 | -0.342090E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -425654327.9 | 60.05 | 0.00 | 0.00 |
October | 0.373446E+11 | -0.369037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440928075.5 | 60.05 | 0.00 | 0.00 |
November | 0.388855E+11 | -0.384580E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427568661.2 | 60.05 | 0.00 | 0.00 |
December | 0.410305E+11 | -0.405868E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443752493.3 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.478328E+12 | -0.473138E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.518928E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.346346E+11 | -0.467627E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -445898269.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.472086E+11 | -0.342090E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -402432552.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5939.79 | 36.96 | 219.17 | 230.83 | 4966.50 | 37.82 | 223.83 | 213.00 |
February | 275.00 | 0.49 | 0.48 | 01-FEB-08:20 | 8039.44 | 37.30 | 268.33 | 258.50 | 3424.37 | 31.65 | 234.00 | 244.67 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9384.36 | 33.31 | 270.67 | 322.83 | 1937.80 | 23.33 | 251.67 | 295.50 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2382.45 | 20.93 | 149.00 | 348.00 | 1359.49 | 22.37 | 230.83 | 314.17 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2110.05 | 20.66 | 148.17 | 397.00 | 1182.89 | 22.08 | 269.00 | 356.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1812.13 | 20.12 | 152.83 | 411.00 | 1050.83 | 21.56 | 279.17 | 364.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1949.50 | 20.52 | 128.17 | 404.67 | 1162.89 | 21.99 | 264.83 | 369.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:30 | 2078.99 | 20.05 | 145.83 | 383.50 | 1240.93 | 21.48 | 233.83 | 347.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2923.99 | 21.46 | 140.83 | 326.83 | 1452.36 | 21.69 | 208.00 | 297.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 8140.78 | 35.00 | 288.83 | 301.50 | 2226.71 | 24.26 | 210.83 | 280.83 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6063.89 | 37.30 | 262.50 | 249.83 | 5336.88 | 38.48 | 263.83 | 239.50 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4719.31 | 37.66 | 237.17 | 231.67 | 4109.69 | 38.83 | 240.83 | 218.50 |
Annual Sum or Average | 3965.83 | 0.50 | 4247.24 | 26.96 | 2411.50 | 3866.17 | 2181.29 | 25.89 | 2910.67 | 3541.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1812.13 | 20.05 | 128.17 | 230.83 | 1050.83 | 21.48 | 208.00 | 213.00 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9384.36 | 37.66 | 288.83 | 411.00 | 5336.88 | 38.83 | 279.17 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:39 | 1878.36 | 25.34 | 102.00 | 216.17 | 1064.46 | 25.00 | 132.50 | 182.17 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2104.37 | 24.44 | 116.67 | 246.50 | 1132.73 | 24.35 | 147.67 | 214.83 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:40 | 3305.61 | 25.66 | 148.33 | 319.50 | 1841.32 | 25.84 | 227.33 | 288.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3294.85 | 24.30 | 105.83 | 356.50 | 1827.19 | 24.68 | 178.33 | 321.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3621.31 | 24.45 | 133.17 | 407.00 | 1586.69 | 23.92 | 211.50 | 369.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4406.47 | 25.53 | 149.33 | 423.00 | 1911.33 | 24.85 | 255.00 | 391.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 4778.57 | 25.65 | 144.00 | 421.50 | 2045.32 | 24.77 | 206.17 | 395.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3815.67 | 24.97 | 148.00 | 391.33 | 2190.41 | 25.24 | 209.50 | 360.33 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2875.65 | 24.13 | 136.83 | 327.17 | 1591.39 | 24.43 | 182.17 | 294.83 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-07:00 | 2582.84 | 24.64 | 138.00 | 290.00 | 1466.42 | 24.81 | 172.67 | 254.83 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1673.39 | 24.35 | 113.83 | 232.17 | 920.35 | 24.22 | 138.67 | 200.00 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1461.29 | 25.26 | 107.33 | 210.33 | 862.35 | 25.03 | 126.17 | 168.33 |
Annual Sum or Average | 3965.83 | 0.50 | 3183.09 | 24.91 | 1543.33 | 3841.17 | 1614.77 | 24.76 | 2187.67 | 3440.50 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 1461.29 | 24.13 | 102.00 | 210.33 | 862.35 | 23.92 | 126.17 | 168.33 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4778.57 | 25.66 | 149.33 | 423.00 | 2190.41 | 25.84 | 255.00 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-09:00 | 621.92 | 16.58 | 0.00 | 192.00 | 365.60 | 18.22 | 1.67 | 125.17 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:09 | 684.11 | 17.58 | 0.00 | 231.67 | 418.89 | 19.23 | 10.83 | 174.83 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1073.88 | 19.48 | 0.00 | 311.00 | 628.93 | 20.96 | 141.17 | 269.67 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1120.76 | 20.09 | 14.00 | 351.00 | 666.58 | 21.47 | 161.67 | 311.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1381.71 | 21.95 | 99.33 | 411.33 | 806.66 | 23.16 | 273.17 | 377.17 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1446.07 | 24.01 | 189.83 | 440.50 | 810.10 | 23.26 | 333.33 | 412.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1411.97 | 22.97 | 138.83 | 425.50 | 812.74 | 22.24 | 274.83 | 397.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1097.85 | 19.72 | 28.33 | 398.83 | 695.36 | 21.12 | 202.83 | 376.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 898.56 | 18.76 | 0.17 | 323.33 | 555.58 | 20.23 | 98.50 | 276.67 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:50 | 739.91 | 17.91 | 0.00 | 274.17 | 448.92 | 19.50 | 29.67 | 212.17 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:39 | 584.69 | 16.72 | 0.00 | 210.50 | 349.66 | 18.37 | 0.33 | 137.50 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:39 | 508.08 | 16.09 | 0.00 | 186.50 | 301.82 | 17.80 | 0.00 | 86.83 |
Annual Sum or Average | 3965.83 | 0.51 | 1024.31 | 19.78 | 470.50 | 3756.33 | 606.47 | 20.79 | 1528.00 | 3158.50 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 508.08 | 16.09 | 0.00 | 186.50 | 301.82 | 17.80 | 0.00 | 86.83 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1446.07 | 24.01 | 189.83 | 440.50 | 812.74 | 23.26 | 333.33 | 412.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-09:00 | 1748.73 | 24.11 | 95.17 | 209.00 | 1013.66 | 24.05 | 127.00 | 172.83 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:09 | 2256.90 | 25.11 | 123.17 | 244.33 | 1223.80 | 24.97 | 149.17 | 215.50 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-08:09 | 3104.10 | 25.42 | 146.00 | 317.33 | 1699.59 | 25.70 | 224.17 | 285.50 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 3210.69 | 23.24 | 108.17 | 348.67 | 1792.61 | 23.77 | 181.33 | 313.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:30 | 3659.12 | 22.40 | 97.17 | 402.50 | 2143.42 | 23.22 | 210.67 | 367.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3748.45 | 20.82 | 62.50 | 424.67 | 1690.80 | 21.19 | 219.00 | 391.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4345.80 | 22.47 | 91.33 | 410.33 | 1962.76 | 21.49 | 185.00 | 382.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3377.81 | 22.30 | 112.50 | 389.50 | 1862.29 | 22.87 | 186.33 | 359.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 3365.91 | 24.94 | 140.67 | 328.50 | 1407.17 | 23.97 | 180.67 | 296.33 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 2262.88 | 24.47 | 137.00 | 287.50 | 1245.30 | 24.58 | 177.83 | 253.00 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:39 | 1948.87 | 25.16 | 118.00 | 230.17 | 1100.98 | 25.00 | 142.33 | 197.00 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1373.87 | 24.52 | 104.17 | 210.50 | 767.08 | 24.26 | 121.33 | 171.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3034.89 | 23.51 | 1335.83 | 3803.00 | 1563.47 | 23.54 | 2104.83 | 3406.17 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1373.87 | 20.82 | 62.50 | 209.00 | 767.08 | 21.19 | 121.33 | 171.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4345.80 | 25.42 | 146.00 | 424.67 | 2143.42 | 25.70 | 224.17 | 391.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5985.54 | 36.48 | 216.17 | 231.00 | 5091.00 | 37.35 | 215.17 | 214.83 |
February | 275.00 | 0.49 | 0.48 | 01-FEB-08:09 | 8102.63 | 36.82 | 265.83 | 258.67 | 3589.21 | 29.95 | 179.67 | 247.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9441.24 | 32.11 | 254.00 | 323.33 | 2068.46 | 18.60 | 12.33 | 297.50 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 2428.63 | 14.56 | 0.00 | 349.00 | 1457.25 | 18.09 | 4.00 | 318.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2145.01 | 14.52 | 0.00 | 397.67 | 1264.26 | 17.98 | 0.17 | 360.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1846.79 | 14.13 | 0.00 | 411.33 | 1123.84 | 17.67 | 0.00 | 369.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1992.45 | 14.51 | 0.00 | 405.50 | 1246.68 | 18.08 | 0.67 | 374.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 2130.70 | 13.77 | 0.00 | 384.00 | 1333.62 | 17.32 | 1.33 | 351.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2985.83 | 15.35 | 29.50 | 327.00 | 1578.41 | 17.41 | 10.50 | 301.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:09 | 8196.83 | 34.08 | 282.83 | 301.67 | 2449.97 | 21.83 | 80.17 | 285.83 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6114.87 | 36.85 | 261.83 | 250.17 | 5453.50 | 38.12 | 262.83 | 241.00 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4755.25 | 37.23 | 231.33 | 231.67 | 4217.31 | 38.50 | 231.83 | 219.50 |
Annual Sum or Average | 3965.83 | 0.50 | 4295.19 | 23.06 | 1541.50 | 3871.00 | 2295.88 | 22.73 | 998.67 | 3580.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1846.79 | 13.77 | 0.00 | 231.00 | 1123.84 | 17.32 | 0.00 | 214.83 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9441.24 | 37.23 | 282.83 | 411.33 | 5453.50 | 38.50 | 262.83 | 374.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:39 | 1908.52 | 23.19 | 89.67 | 217.00 | 1106.50 | 23.39 | 74.83 | 186.33 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2100.36 | 20.53 | 75.00 | 247.17 | 1187.27 | 22.42 | 71.17 | 218.50 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:40 | 3335.87 | 22.10 | 94.00 | 319.67 | 1916.11 | 23.84 | 85.00 | 291.00 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3356.22 | 21.21 | 85.17 | 356.83 | 1905.85 | 22.26 | 60.17 | 325.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3680.88 | 21.49 | 112.67 | 407.17 | 1666.21 | 21.31 | 57.83 | 373.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4451.51 | 21.84 | 134.17 | 423.17 | 2002.24 | 22.36 | 89.33 | 393.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 4849.64 | 22.73 | 134.00 | 422.50 | 2145.65 | 22.14 | 75.50 | 397.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3883.05 | 22.07 | 131.33 | 392.33 | 2277.58 | 22.95 | 100.50 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2931.82 | 21.26 | 104.17 | 327.17 | 1660.58 | 22.18 | 77.33 | 299.83 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-07:00 | 2625.95 | 22.12 | 110.50 | 290.50 | 1520.61 | 22.90 | 97.50 | 258.50 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1703.25 | 22.04 | 95.17 | 232.17 | 961.11 | 22.50 | 78.67 | 203.83 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1483.31 | 23.25 | 101.83 | 210.67 | 894.29 | 23.59 | 86.50 | 173.67 |
Annual Sum or Average | 3965.83 | 0.50 | 3229.03 | 21.95 | 1267.67 | 3846.33 | 1685.81 | 22.58 | 954.33 | 3484.00 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 1483.31 | 20.53 | 75.00 | 210.67 | 894.29 | 21.31 | 57.83 | 173.67 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4849.64 | 23.25 | 134.17 | 423.17 | 2277.58 | 23.84 | 100.50 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-09:50 | 629.35 | 10.71 | 0.00 | 192.67 | 388.33 | 14.28 | 0.00 | 135.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-09:00 | 694.15 | 11.79 | 0.00 | 232.33 | 445.64 | 15.43 | 0.00 | 183.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1090.42 | 13.88 | 0.00 | 311.50 | 668.98 | 17.34 | 0.00 | 274.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1140.52 | 14.67 | 0.00 | 351.83 | 710.11 | 18.15 | 2.33 | 316.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1406.66 | 16.80 | 38.50 | 411.67 | 858.16 | 20.01 | 44.00 | 381.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1474.73 | 19.70 | 107.33 | 441.00 | 864.61 | 19.97 | 36.33 | 416.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1441.99 | 18.27 | 72.17 | 425.83 | 868.63 | 18.83 | 17.00 | 401.17 |
August | 421.33 | 0.49 | 0.48 | 01-AUG-05:40 | 1120.22 | 14.23 | 0.00 | 399.00 | 740.08 | 17.80 | 2.83 | 380.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 914.82 | 13.33 | 0.00 | 323.83 | 592.08 | 16.82 | 0.00 | 283.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:39 | 750.99 | 12.24 | 0.00 | 274.83 | 477.68 | 15.83 | 0.00 | 223.17 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:30 | 592.23 | 10.78 | 0.00 | 211.33 | 371.60 | 14.45 | 0.00 | 152.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:30 | 513.00 | 9.97 | 0.00 | 187.50 | 320.33 | 13.68 | 0.00 | 105.33 |
Annual Sum or Average | 3965.83 | 0.51 | 1042.56 | 14.41 | 218.00 | 3763.33 | 646.02 | 17.27 | 102.50 | 3251.67 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 513.00 | 9.97 | 0.00 | 187.50 | 320.33 | 13.68 | 0.00 | 105.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1474.73 | 19.70 | 107.33 | 441.00 | 868.63 | 20.01 | 44.00 | 416.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-09:50 | 1776.53 | 22.00 | 85.00 | 210.17 | 1052.60 | 22.47 | 70.33 | 176.33 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-09:00 | 2296.53 | 22.66 | 95.17 | 244.67 | 1276.43 | 23.13 | 84.33 | 219.17 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-08:09 | 3134.09 | 21.81 | 92.50 | 318.00 | 1768.59 | 23.69 | 84.17 | 288.67 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 3270.64 | 19.92 | 75.83 | 349.50 | 1872.31 | 21.13 | 48.00 | 317.83 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:30 | 3716.00 | 18.80 | 75.00 | 403.50 | 2228.38 | 20.35 | 46.00 | 371.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3801.02 | 16.85 | 52.00 | 425.50 | 1773.12 | 17.85 | 0.00 | 394.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4408.61 | 18.90 | 79.67 | 411.17 | 2057.66 | 18.19 | 3.67 | 384.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 3438.60 | 18.88 | 90.83 | 390.50 | 1941.19 | 20.14 | 58.00 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3422.08 | 22.29 | 116.67 | 328.17 | 1476.64 | 21.64 | 66.50 | 300.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 2306.62 | 21.83 | 100.50 | 288.33 | 1300.52 | 22.57 | 87.00 | 257.33 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-08:39 | 1978.30 | 22.68 | 102.67 | 231.00 | 1142.80 | 23.32 | 92.83 | 201.50 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1358.91 | 20.71 | 78.50 | 210.67 | 799.90 | 22.74 | 83.33 | 176.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3080.40 | 20.31 | 1044.33 | 3811.17 | 1632.21 | 21.10 | 724.17 | 3452.17 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1358.91 | 16.85 | 52.00 | 210.17 | 799.90 | 17.85 | 0.00 | 176.33 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4408.61 | 22.68 | 116.67 | 425.50 | 2228.38 | 23.69 | 92.83 | 394.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5986.66 | 36.48 | 216.17 | 231.00 | 5092.97 | 37.35 | 215.17 | 214.83 |
February | 275.00 | 0.49 | 0.48 | 01-FEB-08:09 | 8104.21 | 36.81 | 265.83 | 258.67 | 3591.55 | 29.94 | 179.67 | 247.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9444.85 | 32.10 | 254.00 | 323.33 | 2071.47 | 18.58 | 12.17 | 297.67 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 2431.98 | 14.53 | 0.00 | 349.00 | 1459.38 | 18.07 | 3.67 | 318.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2148.11 | 14.49 | 0.00 | 397.67 | 1266.15 | 17.97 | 0.17 | 360.67 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1849.19 | 14.10 | 0.00 | 411.33 | 1125.38 | 17.65 | 0.00 | 369.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1994.88 | 14.48 | 0.00 | 405.50 | 1248.28 | 18.07 | 0.50 | 374.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 2133.37 | 13.74 | 0.00 | 384.00 | 1335.35 | 17.30 | 1.33 | 351.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2988.70 | 15.32 | 29.50 | 327.00 | 1580.48 | 17.39 | 10.33 | 301.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:09 | 8198.71 | 34.07 | 282.83 | 301.67 | 2452.27 | 21.82 | 80.17 | 286.00 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6115.87 | 36.84 | 261.83 | 250.33 | 5455.49 | 38.12 | 262.83 | 241.17 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4755.88 | 37.22 | 231.33 | 231.83 | 4218.89 | 38.49 | 231.83 | 219.50 |
Annual Sum or Average | 3965.83 | 0.50 | 4297.53 | 23.04 | 1541.50 | 3871.33 | 2297.86 | 22.72 | 997.83 | 3582.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1849.19 | 13.74 | 0.00 | 231.00 | 1125.38 | 17.30 | 0.00 | 214.83 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9444.85 | 37.22 | 282.83 | 411.33 | 5455.49 | 38.49 | 262.83 | 374.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:39 | 1909.49 | 23.16 | 89.67 | 217.00 | 1107.48 | 23.38 | 74.67 | 186.50 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2101.31 | 20.50 | 75.00 | 247.00 | 1188.36 | 22.40 | 70.67 | 218.50 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:40 | 3337.87 | 22.07 | 94.00 | 319.67 | 1917.88 | 23.83 | 84.67 | 291.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3357.98 | 21.18 | 85.17 | 356.83 | 1907.49 | 22.25 | 60.17 | 325.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3683.04 | 21.46 | 112.67 | 407.33 | 1667.95 | 21.29 | 57.83 | 373.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4453.36 | 21.81 | 134.17 | 423.17 | 2003.98 | 22.35 | 89.33 | 394.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 4851.21 | 22.71 | 134.00 | 422.50 | 2147.25 | 22.13 | 75.50 | 397.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3884.58 | 22.04 | 131.33 | 392.50 | 2279.10 | 22.94 | 100.50 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2933.19 | 21.23 | 104.17 | 327.17 | 1661.98 | 22.17 | 77.33 | 300.00 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-07:00 | 2612.56 | 21.74 | 107.00 | 290.33 | 1521.78 | 22.89 | 97.17 | 258.50 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1655.73 | 20.47 | 83.00 | 231.83 | 962.01 | 22.49 | 78.50 | 203.83 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1484.01 | 23.23 | 101.83 | 210.67 | 895.08 | 23.58 | 86.50 | 173.67 |
Annual Sum or Average | 3965.83 | 0.50 | 3226.06 | 21.79 | 1252.00 | 3846.00 | 1687.23 | 22.56 | 952.83 | 3485.33 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 1484.01 | 20.47 | 75.00 | 210.67 | 895.08 | 21.29 | 57.83 | 173.67 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4851.21 | 23.23 | 134.17 | 423.17 | 2279.10 | 23.83 | 100.50 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-09:50 | 629.97 | 10.68 | 0.00 | 192.83 | 388.88 | 14.26 | 0.00 | 135.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-09:00 | 694.71 | 11.75 | 0.00 | 232.33 | 446.20 | 15.42 | 0.00 | 183.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1091.59 | 13.85 | 0.00 | 311.50 | 669.92 | 17.32 | 0.00 | 274.50 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1141.69 | 14.64 | 0.00 | 351.83 | 711.07 | 18.13 | 2.33 | 316.50 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1408.06 | 16.77 | 38.50 | 411.83 | 859.29 | 20.00 | 43.83 | 381.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1475.87 | 19.67 | 107.33 | 441.17 | 865.67 | 19.95 | 35.83 | 416.83 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1443.01 | 18.24 | 72.17 | 425.83 | 869.63 | 18.81 | 16.17 | 401.17 |
August | 421.33 | 0.49 | 0.48 | 01-AUG-05:40 | 1121.12 | 14.20 | 0.00 | 399.00 | 740.92 | 17.79 | 2.83 | 380.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 915.58 | 13.30 | 0.00 | 323.83 | 592.79 | 16.80 | 0.00 | 283.33 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:39 | 751.65 | 12.21 | 0.00 | 275.00 | 478.29 | 15.81 | 0.00 | 223.17 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:30 | 592.76 | 10.75 | 0.00 | 211.33 | 372.10 | 14.43 | 0.00 | 152.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:30 | 513.44 | 9.94 | 0.00 | 187.50 | 320.77 | 13.66 | 0.00 | 105.67 |
Annual Sum or Average | 3965.83 | 0.51 | 1043.47 | 14.38 | 218.00 | 3764.00 | 646.83 | 17.25 | 101.00 | 3252.67 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 513.44 | 9.94 | 0.00 | 187.50 | 320.77 | 13.66 | 0.00 | 105.67 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1475.87 | 19.67 | 107.33 | 441.17 | 869.63 | 20.00 | 43.83 | 416.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-09:50 | 1777.52 | 21.97 | 85.00 | 210.17 | 1053.58 | 22.45 | 70.17 | 176.33 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-09:00 | 2297.51 | 22.63 | 95.17 | 244.67 | 1277.51 | 23.12 | 83.67 | 219.17 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-08:09 | 3136.16 | 21.79 | 92.50 | 318.17 | 1770.37 | 23.68 | 82.67 | 288.83 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 3272.55 | 19.89 | 75.83 | 349.50 | 1874.12 | 21.12 | 48.00 | 318.00 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:30 | 3718.15 | 18.77 | 75.00 | 403.50 | 2230.30 | 20.34 | 46.00 | 372.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3802.97 | 16.82 | 52.00 | 425.50 | 1774.85 | 17.84 | 0.00 | 394.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4410.35 | 18.87 | 79.67 | 411.17 | 2059.38 | 18.17 | 3.67 | 384.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:30 | 3440.22 | 18.85 | 90.83 | 390.67 | 1942.74 | 20.12 | 58.00 | 363.17 |
September | 352.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3423.42 | 22.27 | 116.50 | 328.17 | 1478.02 | 21.63 | 66.50 | 300.33 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 2307.70 | 21.80 | 100.33 | 288.33 | 1301.69 | 22.56 | 86.50 | 257.50 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-08:39 | 1979.14 | 22.66 | 102.67 | 231.00 | 1143.74 | 23.31 | 92.67 | 201.67 |
December | 236.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1359.61 | 20.69 | 78.33 | 210.67 | 800.68 | 22.73 | 83.00 | 176.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3081.92 | 20.28 | 1043.83 | 3811.50 | 1633.67 | 21.09 | 720.83 | 3453.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1359.61 | 16.82 | 52.00 | 210.17 | 800.68 | 17.84 | 0.00 | 176.33 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 4410.35 | 22.66 | 116.50 | 425.50 | 2230.30 | 23.68 | 92.67 | 394.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.398152E+11 | 73941.78 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219909E+11 | 70130.83 | 01-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120161E+11 | 57520.76 | 06-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274258E+10 | 31359.14 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183194E+10 | 23314.06 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75257288.35 | 12922.97 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.600859E+09 | 14109.38 | 19-SEP-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245276E+10 | 28995.97 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.873496E+10 | 48261.55 | 27-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239252E+11 | 82066.23 | 29-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398152E+11 | 82066.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237546E+10 | 14766.08 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.662486E+09 | 14773.13 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121754E+09 | 13700.98 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45075227.54 | 14773.97 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.506775E+09 | 14867.36 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237546E+10 | 14867.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147657E+10 | 16428.38 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.462293E+09 | 16433.49 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100829E+09 | 16012.24 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1144782.35 | 2261.63 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67832607.93 | 16436.61 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.503562E+09 | 16484.11 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147657E+10 | 16484.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225842E+10 | 23390.81 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.599466E+09 | 23449.84 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191930E+09 | 22744.21 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6608928.54 | 10679.27 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20379284.39 | 16497.57 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7606400.94 | 19269.73 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154858E+09 | 23439.43 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.693196E+09 | 23453.80 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225842E+10 | 23453.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.788509E+09 | 15198.43 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54163382.83 | 15177.22 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4637871.33 | 12413.41 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7893245.40 | 8349.81 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.855204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.788509E+09 | 15198.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.444947E+12 | 825811.60 | 09-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262291E+12 | 717420.25 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182472E+12 | 618284.12 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661914E+11 | 300575.99 | 18-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385846E+11 | 327320.68 | 09-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.251675E+10 | 139326.27 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.739045E+09 | 315069.01 | 17-AUG-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121086E+11 | 349432.27 | 19-SEP-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.455256E+11 | 288140.40 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126757E+12 | 500612.41 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304804E+12 | 793765.06 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148694E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.444947E+12 | 825811.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.831609E+10 | 572524.00 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201811E+10 | 573311.21 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.558547E+09 | 572006.01 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54399249.48 | 149640.26 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.565718E+09 | 568944.35 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.831609E+10 | 573311.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.851720E+11 | 142561.94 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.403165E+11 | 129662.57 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165726E+11 | 139864.93 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199478E+10 | 137943.73 | 15-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138558E+10 | 139492.92 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251297E+09 | 78996.13 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200800E+10 | 138668.42 | 05-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168692E+11 | 139525.02 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498778E+11 | 129284.10 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.851720E+11 | 142561.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473569E+11 | 195739.76 | 09-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201483E+11 | 195754.84 | 06-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.803117E+10 | 195153.63 | 06-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866512E+09 | 181675.37 | 15-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.824447E+09 | 195013.75 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86124838.80 | 35229.91 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.889093E+09 | 195019.23 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.892066E+10 | 195199.07 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270410E+11 | 195841.62 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.473569E+11 | 195841.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.517237E+11 | 242127.22 | 11-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188700E+11 | 242054.42 | 06-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.857241E+10 | 240306.12 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131674E+10 | 238276.92 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140940E+10 | 239401.37 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92995685.98 | 24846.02 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.853020E+09 | 238769.77 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.853690E+10 | 240848.95 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270376E+11 | 242169.93 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.517237E+11 | 242169.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.448220E+11 | 199646.43 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165168E+11 | 199038.74 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641195E+10 | 198993.57 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.456695E+09 | 167593.12 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604402E+09 | 161330.19 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39829866.43 | 18279.01 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.608119E+09 | 198790.51 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663595E+10 | 199047.93 | 27-NOV-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223840E+11 | 199095.07 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.448220E+11 | 199646.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.503622E+11 | 84212.75 | 11-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294224E+11 | 78192.55 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210605E+11 | 70677.16 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.857568E+10 | 35141.66 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.526158E+10 | 29633.67 | 08-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587797E+09 | 16105.40 | 16-JUN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14834955.52 | 2734.23 | 05-JUL-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158632E+09 | 6496.17 | 28-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217109E+10 | 17182.43 | 19-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.649714E+10 | 37127.52 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156435E+11 | 51792.40 | 27-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352264E+11 | 81414.87 | 29-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14834955.52 | 2734.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.503622E+11 | 84212.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151357E+11 | 75069.21 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583637E+10 | 75027.47 | 21-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288325E+10 | 74812.23 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198096E+09 | 73266.32 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609949E+09 | 75040.92 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.380476E+09 | 75075.43 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356394E+10 | 74830.68 | 20-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.906665E+10 | 74805.13 | 04-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151357E+11 | 75075.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154657E+11 | 17630.70 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812161E+10 | 15222.98 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.501233E+10 | 15166.54 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135783E+10 | 15115.57 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.883509E+09 | 15115.88 | 01-MAY-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22097531.68 | 15096.08 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10579859.52 | 15107.40 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334267E+09 | 15150.16 | 13-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145099E+10 | 15213.16 | 10-OCT-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.540091E+10 | 15118.10 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114247E+11 | 16331.07 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154657E+11 | 17630.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.937366E+10 | 20987.72 | 12-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.436882E+10 | 20998.41 | 13-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255916E+10 | 20898.42 | 04-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625668E+09 | 20877.71 | 28-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.454795E+09 | 20829.69 | 08-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10042520.17 | 13450.28 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3806349.92 | 12852.77 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143582E+09 | 20822.33 | 19-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.649092E+09 | 20891.79 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291616E+10 | 20879.69 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671782E+10 | 20944.97 | 19-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.937366E+10 | 20998.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106545E+11 | 25902.52 | 18-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460003E+10 | 25825.82 | 02-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322207E+10 | 25814.29 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101738E+10 | 25903.16 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.848673E+09 | 25894.85 | 09-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37032156.58 | 25872.41 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14356932.03 | 18493.87 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197070E+09 | 25696.10 | 19-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.717933E+09 | 25883.20 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304340E+10 | 25970.97 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.716926E+10 | 25898.01 | 12-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106545E+11 | 25970.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.865565E+10 | 23498.72 | 25-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356401E+10 | 23490.74 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209938E+10 | 23363.25 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.447161E+09 | 23348.67 | 01-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360964E+09 | 23460.11 | 08-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11422705.89 | 12178.84 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5559393.19 | 6363.31 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101060E+09 | 16829.31 | 19-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476920E+09 | 23372.42 | 10-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215937E+10 | 23373.98 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521465E+10 | 23505.64 | 19-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.865565E+10 | 23505.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171053E+11 | 47221.01 | 27-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752468E+10 | 38216.18 | 01-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275697E+10 | 32948.75 | 04-MAR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251091E+09 | 11479.14 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20619354.00 | 7996.52 | 23-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 315000.73 | 1050.00 | 17-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 100.14 | 0.63 | 17-AUG-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 186910.98 | 621.90 | 21-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8018038.13 | 12534.09 | 05-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.447374E+09 | 20575.67 | 27-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.636440E+10 | 37865.60 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171053E+11 | 47221.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.168075E+10 | 0.168075E+10 | 50026.59 | 02-JAN-14:10 | 50026.59 | 0.00 |
February | 0.00 | 0.00 | 0.500525E+10 | 0.500525E+10 | 59442.49 | 28-FEB-15:50 | 59442.49 | 0.00 |
March | 0.00 | 0.00 | 0.606236E+10 | 0.606236E+10 | 56374.96 | 01-MAR-16:10 | 56374.96 | 0.00 |
April | 0.00 | 0.00 | 0.893683E+10 | 0.893683E+10 | 84125.88 | 06-APR-16:00 | 84125.88 | 0.00 |
May | 0.00 | 0.00 | 0.192438E+11 | 0.192438E+11 | 112862.12 | 19-MAY-15:20 | 112862.12 | 0.05 |
June | 0.00 | 0.00 | 0.620964E+11 | 0.617413E+11 | 145293.47 | 21-JUN-12:45 | 132664.57 | 0.22 |
July | 0.00 | 0.00 | 0.109701E+12 | 0.108903E+12 | 153443.32 | 19-JUL-09:30 | 126006.85 | 0.39 |
August | 0.00 | 0.00 | 0.959222E+11 | 0.959218E+11 | 152304.71 | 10-AUG-12:43 | 152304.71 | 0.21 |
September | 0.00 | 0.00 | 0.422725E+11 | 0.405609E+11 | 188702.78 | 07-SEP-15:10 | 104881.13 | 0.17 |
October | 0.00 | 0.00 | 0.165245E+11 | 0.165245E+11 | 106078.93 | 18-OCT-13:43 | 106078.93 | 0.00 |
November | 0.00 | 0.00 | 0.845911E+10 | 0.845911E+10 | 68189.04 | 03-NOV-14:00 | 68189.04 | 0.00 |
December | 0.00 | 0.00 | 0.498470E+10 | 0.498470E+10 | 46551.94 | 07-DEC-14:10 | 46551.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.380889E+12 | 0.378024E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.168075E+10 | 0.168075E+10 | 46551.94 | 46551.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109701E+12 | 0.108903E+12 | 188702.78 | 152304.71 | 0.39 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28319.24 | 28319.24 | 1.31 | 02-JAN-06:01 | 1.31 | 0.00 |
February | 0.00 | 0.00 | 0.259507E+11 | 0.259507E+11 | 545336.68 | 27-FEB-15:30 | 545336.68 | 0.00 |
March | 0.00 | 0.00 | 0.532920E+11 | 0.532920E+11 | 433546.38 | 28-MAR-16:00 | 433546.38 | 0.00 |
April | 0.00 | 0.00 | 0.901903E+11 | 0.901903E+11 | 691506.27 | 06-APR-16:00 | 691506.27 | 0.00 |
May | 0.00 | 0.00 | 0.175443E+12 | 0.175443E+12 | 1127732.88 | 19-MAY-15:20 | 1127732.88 | 0.05 |
June | 0.00 | 0.00 | 0.511067E+12 | 0.508449E+12 | 1349295.08 | 21-JUN-12:45 | 1231040.87 | 0.20 |
July | 0.00 | 0.00 | 0.848319E+12 | 0.844861E+12 | 1430663.28 | 25-JUL-16:36 | 1430663.28 | 0.33 |
August | 0.00 | 0.00 | 0.740113E+12 | 0.740113E+12 | 1395100.58 | 10-AUG-12:23 | 1395100.58 | 0.17 |
September | 0.00 | 0.00 | 0.362161E+12 | 0.347767E+12 | 1683755.86 | 07-SEP-14:35 | 872895.92 | 0.16 |
October | 0.00 | 0.00 | 0.159021E+12 | 0.159021E+12 | 904207.79 | 18-OCT-15:20 | 904207.79 | 0.00 |
November | 0.00 | 0.00 | 0.517635E+11 | 0.517635E+11 | 501246.71 | 03-NOV-14:05 | 501246.71 | 0.00 |
December | 0.00 | 0.00 | 0.419038E+09 | 0.419038E+09 | 78950.72 | 07-DEC-12:00 | 78950.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.301774E+13 | 0.299727E+13 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 28319.24 | 28319.24 | 1.31 | 1.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.848319E+12 | 0.844861E+12 | 1683755.86 | 1430663.28 | 0.33 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.905366E+09 | 0.905366E+09 | 27231.11 | 28-FEB-16:10 | 27231.11 | 0.00 |
March | 0.00 | 0.00 | 0.193020E+10 | 0.193020E+10 | 38203.41 | 28-MAR-16:00 | 38203.41 | 0.00 |
April | 0.00 | 0.00 | 0.656492E+10 | 0.656492E+10 | 69169.20 | 06-APR-16:00 | 69169.20 | 0.00 |
May | 0.00 | 0.00 | 0.164679E+11 | 0.164679E+11 | 131823.06 | 19-MAY-14:40 | 131823.06 | 0.04 |
June | 0.00 | 0.00 | 0.556772E+11 | 0.553686E+11 | 157735.51 | 21-JUN-12:32 | 147209.74 | 0.20 |
July | 0.00 | 0.00 | 0.932269E+11 | 0.929026E+11 | 168589.02 | 25-JUL-16:56 | 168589.02 | 0.33 |
August | 0.00 | 0.00 | 0.791588E+11 | 0.791588E+11 | 161484.64 | 10-AUG-12:55 | 161484.64 | 0.17 |
September | 0.00 | 0.00 | 0.349673E+11 | 0.335355E+11 | 198972.19 | 07-SEP-15:10 | 110676.77 | 0.14 |
October | 0.00 | 0.00 | 0.824500E+10 | 0.824500E+10 | 91834.08 | 18-OCT-15:10 | 91834.08 | 0.00 |
November | 0.00 | 0.00 | 0.115887E+10 | 0.115887E+10 | 35720.10 | 03-NOV-15:30 | 35720.10 | 0.00 |
December | 0.00 | 0.00 | 58897.10 | 58897.10 | 631.34 | 04-DEC-05:11 | 631.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.298302E+12 | 0.296238E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.932269E+11 | 0.929026E+11 | 198972.19 | 168589.02 | 0.33 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2165872.57 | 2165872.57 | 1505.02 | 13-JAN-15:00 | 1505.02 | 0.00 |
February | 0.00 | 0.00 | 0.585109E+09 | 0.585109E+09 | 30669.61 | 27-FEB-15:00 | 30669.61 | 0.00 |
March | 0.00 | 0.00 | 0.259040E+09 | 0.259040E+09 | 9693.10 | 29-MAR-14:00 | 9693.10 | 0.00 |
April | 0.00 | 0.00 | 0.452755E+10 | 0.452755E+10 | 49244.17 | 07-APR-14:00 | 49244.17 | 0.00 |
May | 0.00 | 0.00 | 0.134114E+11 | 0.133785E+11 | 57774.38 | 19-MAY-15:00 | 57774.38 | 0.04 |
June | 0.00 | 0.00 | 0.316774E+11 | 0.313985E+11 | 81456.70 | 22-JUN-10:13 | 75051.65 | 0.12 |
July | 0.00 | 0.00 | 0.374466E+11 | 0.374064E+11 | 84133.64 | 31-JUL-15:35 | 84133.64 | 0.17 |
August | 0.00 | 0.00 | 0.409388E+11 | 0.409331E+11 | 83099.37 | 09-AUG-18:15 | 83099.37 | 0.12 |
September | 0.00 | 0.00 | 0.243872E+11 | 0.231250E+11 | 102559.36 | 07-SEP-14:35 | 53002.71 | 0.12 |
October | 0.00 | 0.00 | 0.770630E+10 | 0.770630E+10 | 68614.62 | 18-OCT-13:43 | 68614.62 | 0.00 |
November | 0.00 | 0.00 | 0.326130E+09 | 0.326130E+09 | 25171.65 | 17-NOV-07:11 | 25171.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161268E+12 | 0.159648E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.409388E+11 | 0.409331E+11 | 102559.36 | 84133.64 | 0.17 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.929632E+10 | 0.812160E+10 | 5354.27 | 03-JAN-14:50 | 4854.43 | 0.00 |
February | 0.00 | 0.00 | 0.133877E+11 | 0.119159E+11 | 5993.46 | 22-FEB-19:00 | 5059.78 | 0.00 |
March | 0.00 | 0.00 | 0.147364E+11 | 0.141166E+11 | 6532.19 | 31-MAR-23:10 | 5498.27 | 0.00 |
April | 0.00 | 0.00 | 0.570053E+11 | 0.547926E+11 | 306725.97 | 07-APR-14:00 | 306725.97 | 0.00 |
May | 0.00 | 0.00 | 0.175753E+11 | 0.163862E+11 | 144886.87 | 19-MAY-13:50 | 137797.90 | 0.00 |
June | 0.00 | 0.00 | 0.128505E+12 | 0.116170E+12 | 334317.54 | 20-JUN-18:50 | 225818.66 | 0.00 |
July | 0.00 | 0.00 | 0.422146E+12 | 0.380236E+12 | 427442.70 | 19-JUL-10:50 | 321065.62 | 0.00 |
August | 0.00 | 0.00 | 0.525113E+12 | 0.483889E+12 | 483446.55 | 08-AUG-12:00 | 400386.47 | 0.00 |
September | 0.00 | 0.00 | 0.454691E+11 | 0.414661E+11 | 222638.67 | 07-SEP-16:00 | 130471.61 | 0.00 |
October | 0.00 | 0.00 | 0.220628E+11 | 0.205518E+11 | 175294.15 | 18-OCT-15:00 | 175294.15 | 0.00 |
November | 0.00 | 0.00 | 0.147836E+11 | 0.140190E+11 | 34678.30 | 17-NOV-17:00 | 32958.31 | 0.00 |
December | 0.00 | 0.00 | 0.150009E+11 | 0.147473E+11 | 22829.09 | 10-DEC-02:00 | 22829.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128508E+13 | 0.117641E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.929632E+10 | 0.812160E+10 | 5354.27 | 4854.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.525113E+12 | 0.483889E+12 | 483446.55 | 400386.47 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.327360E+10 | 0.327328E+10 | 2405.45 | 01-JAN-16:05 | 2398.92 | 0.00 |
February | 0.00 | 0.00 | 0.847012E+10 | 0.847012E+10 | 5234.71 | 26-FEB-17:24 | 5234.71 | 0.00 |
March | 0.00 | 0.00 | 0.150718E+11 | 0.150718E+11 | 7532.30 | 31-MAR-24:00 | 7532.30 | 0.00 |
April | 0.00 | 0.00 | 0.200687E+11 | 0.200598E+11 | 9069.24 | 22-APR-18:15 | 9069.24 | 0.00 |
May | 0.00 | 0.00 | 0.569934E+10 | 0.567399E+10 | 4120.07 | 31-MAY-24:00 | 4120.07 | 0.00 |
June | 0.00 | 0.00 | 0.109607E+11 | 0.108692E+11 | 6038.56 | 30-JUN-23:55 | 6021.79 | 0.00 |
July | 0.00 | 0.00 | 0.167563E+11 | 0.166504E+11 | 7980.80 | 31-JUL-24:00 | 7980.80 | 0.00 |
August | 0.00 | 0.00 | 0.215640E+11 | 0.214823E+11 | 9032.49 | 05-AUG-19:55 | 9032.49 | 0.00 |
September | 0.00 | 0.00 | 0.579887E+10 | 0.571078E+10 | 3972.14 | 30-SEP-24:00 | 3972.14 | 0.00 |
October | 0.00 | 0.00 | 0.106196E+11 | 0.106078E+11 | 5666.10 | 31-OCT-24:00 | 5666.10 | 0.00 |
November | 0.00 | 0.00 | 0.147445E+11 | 0.147421E+11 | 6800.10 | 12-NOV-16:30 | 6800.10 | 0.00 |
December | 0.00 | 0.00 | 0.196892E+11 | 0.196889E+11 | 8484.54 | 10-DEC-16:07 | 8484.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152717E+12 | 0.152300E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.327360E+10 | 0.327328E+10 | 2405.45 | 2398.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215640E+11 | 0.214823E+11 | 9069.24 | 9069.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.967726E+10 | 0.967400E+10 | 18707.70 | 13-JAN-16:30 | 18707.70 | 0.00 |
February | 0.00 | 0.00 | 0.618720E+11 | 0.618720E+11 | 46816.66 | 26-FEB-17:24 | 46816.66 | 0.00 |
March | 0.00 | 0.00 | 0.128335E+12 | 0.128335E+12 | 66300.06 | 31-MAR-23:40 | 66300.06 | 0.00 |
April | 0.00 | 0.00 | 0.183102E+12 | 0.183012E+12 | 85224.42 | 22-APR-18:12 | 85224.42 | 0.00 |
May | 0.00 | 0.00 | 0.482843E+11 | 0.480358E+11 | 39096.69 | 31-MAY-24:00 | 39096.69 | 0.00 |
June | 0.00 | 0.00 | 0.101685E+12 | 0.100777E+12 | 58673.39 | 30-JUN-23:55 | 58508.79 | 0.00 |
July | 0.00 | 0.00 | 0.157647E+12 | 0.156594E+12 | 76582.56 | 31-JUL-24:00 | 76582.56 | 0.00 |
August | 0.00 | 0.00 | 0.203761E+12 | 0.202947E+12 | 86324.17 | 05-AUG-19:55 | 86047.70 | 0.00 |
September | 0.00 | 0.00 | 0.504107E+11 | 0.495482E+11 | 36361.35 | 30-SEP-23:30 | 36361.35 | 0.00 |
October | 0.00 | 0.00 | 0.913124E+11 | 0.911946E+11 | 49122.94 | 15-OCT-17:03 | 49122.94 | 0.00 |
November | 0.00 | 0.00 | 0.124202E+12 | 0.124178E+12 | 60914.69 | 03-NOV-16:00 | 60366.81 | 0.00 |
December | 0.00 | 0.00 | 0.161958E+12 | 0.161955E+12 | 76412.30 | 06-DEC-16:10 | 76104.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132225E+13 | 0.131812E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.967726E+10 | 0.967400E+10 | 18707.70 | 18707.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203761E+12 | 0.202947E+12 | 86324.17 | 86047.70 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.222441E+09 | 0.222441E+09 | 1817.41 | 13-JAN-16:30 | 1817.41 | 0.00 |
February | 0.00 | 0.00 | 0.448391E+10 | 0.448391E+10 | 4335.50 | 28-FEB-17:00 | 4335.50 | 0.00 |
March | 0.00 | 0.00 | 0.110830E+11 | 0.110830E+11 | 6379.06 | 28-MAR-17:50 | 6379.06 | 0.00 |
April | 0.00 | 0.00 | 0.171611E+11 | 0.171522E+11 | 8461.98 | 22-APR-18:14 | 8461.98 | 0.00 |
May | 0.00 | 0.00 | 0.413642E+10 | 0.411180E+10 | 3833.53 | 31-MAY-23:40 | 3833.53 | 0.00 |
June | 0.00 | 0.00 | 0.999107E+10 | 0.990039E+10 | 5879.02 | 30-JUN-23:45 | 5861.50 | 0.00 |
July | 0.00 | 0.00 | 0.157426E+11 | 0.156374E+11 | 7657.19 | 31-JUL-24:00 | 7657.19 | 0.00 |
August | 0.00 | 0.00 | 0.202598E+11 | 0.201786E+11 | 8828.84 | 05-AUG-19:55 | 8820.18 | 0.00 |
September | 0.00 | 0.00 | 0.451520E+10 | 0.442995E+10 | 3684.21 | 04-SEP-17:54 | 3684.21 | 0.00 |
October | 0.00 | 0.00 | 0.775339E+10 | 0.774186E+10 | 4734.99 | 15-OCT-17:03 | 4734.99 | 0.00 |
November | 0.00 | 0.00 | 0.104028E+11 | 0.104005E+11 | 6017.60 | 03-NOV-16:00 | 5962.75 | 0.00 |
December | 0.00 | 0.00 | 0.138727E+11 | 0.138724E+11 | 7524.10 | 06-DEC-16:10 | 7494.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119625E+12 | 0.119214E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.222441E+09 | 0.222441E+09 | 1817.41 | 1817.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202598E+11 | 0.201786E+11 | 8828.84 | 8820.18 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 317831.29 | 1997492.73 | 09-JAN-07:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 183947.12 | 1766035.39 | 06-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 102013.00 | 1610030.13 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33015.83 | 1199794.39 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19719.43 | 1210289.50 | 09-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1252.04 | 173230.01 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 5.24 | 2598.73 | 05-JUL-06:11 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 347.78 | 343416.23 | 17-AUG-13:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 6182.97 | 407971.39 | 19-SEP-13:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23243.09 | 1331680.98 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 80588.66 | 1308623.02 | 30-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 200044.30 | 1572169.23 | 26-DEC-06:01 |
Annual Sum or Average | 0.00 | 80386.39 | ||||
Minimum of Months | 0.00 | 0.00 | 5.24 | 2598.73 | ||
Maximum of Months | 0.00 | 0.00 | 317831.29 | 1997492.73 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 731.52 | 52606.08 | 02-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 13842.44 | 643010.13 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23602.04 | 466495.79 | 28-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43541.54 | 1023362.27 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 85480.52 | 1500494.53 | 19-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 260120.95 | 2052890.56 | 20-JUN-12:13 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 413656.26 | 2393762.50 | 14-JUL-09:52 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 363976.18 | 1854555.89 | 31-AUG-12:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 182255.69 | 2380564.45 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 72569.99 | 1887208.25 | 18-OCT-13:43 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24362.66 | 601816.64 | 03-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2381.77 | 119792.12 | 07-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 124740.71 | 0.00 | ||||
Minimum of Months | 731.52 | 52606.08 | 0.00 | 0.00 | ||
Maximum of Months | 413656.26 | 2393762.50 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 573.99 | 49642.18 | 02-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 13382.92 | 645182.81 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 22939.88 | 464888.45 | 28-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 42731.15 | 1136308.35 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 85876.39 | 1809252.69 | 19-MAY-17:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 273205.08 | 2375418.81 | 20-JUN-12:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 437365.67 | 2496770.08 | 14-JUL-09:50 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 378621.55 | 2287311.51 | 01-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 189771.05 | 2383865.78 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 76484.69 | 2153651.76 | 18-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23757.13 | 607723.69 | 03-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2005.61 | 118305.25 | 07-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 129804.26 | 0.00 | ||||
Minimum of Months | 573.99 | 49642.18 | 0.00 | 0.00 | ||
Maximum of Months | 437365.67 | 2496770.08 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15368.62 | 37488.96 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50495.80 | 129378.14 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82924.83 | 132434.75 | 15-MAR-18:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 147829.79 | 1013387.00 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74358.90 | 1006203.09 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 275630.08 | 1376506.44 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 635945.18 | 1936718.65 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 669819.61 | 2027878.99 | 05-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 159995.66 | 1300482.84 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 78372.36 | 809625.65 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82958.78 | 134218.28 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 101815.16 | 153394.02 | 08-DEC-20:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 199515.22 | 0.00 | ||||
Minimum of Months | 15368.62 | 37488.96 | 0.00 | 0.00 | ||
Maximum of Months | 669819.61 | 2027878.99 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 16135.06 | 57877.02 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16514.12 | 58184.06 | 17-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17371.52 | 58080.80 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15686.02 | 56501.36 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15336.02 | 54000.04 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14754.70 | 50704.93 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 12894.00 | 47668.63 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13810.05 | 45986.74 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 13115.78 | 47092.10 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13695.34 | 49894.31 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14752.91 | 53085.33 | 30-NOV-12:45 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15068.80 | 55889.83 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 14918.66 | ||||
Minimum of Months | 0.00 | 0.00 | 12894.00 | 45986.74 | ||
Maximum of Months | 0.00 | 0.00 | 17371.52 | 58184.06 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 91.46 | 43669.56 | 02-JAN-12:40 | 1880.21 | 128375.12 | 03-JAN-16:00 |
February | 13497.59 | 731590.79 | 27-FEB-15:30 | 4012.24 | 131499.21 | 28-FEB-06:40 |
March | 22908.95 | 531685.51 | 28-MAR-16:00 | 5075.20 | 130982.46 | 04-MAR-06:40 |
April | 44430.35 | 1154916.46 | 06-APR-16:00 | 4614.90 | 130664.16 | 27-APR-12:50 |
May | 95874.17 | 2136202.01 | 19-MAY-14:00 | 3818.78 | 119966.96 | 22-MAY-09:40 |
June | 332346.11 | 2899747.26 | 20-JUN-15:10 | 1673.14 | 106168.60 | 16-JUN-08:40 |
July | 539221.11 | 3286976.56 | 15-JUL-15:52 | 1790.89 | 84090.03 | 08-JUL-08:20 |
August | 457144.26 | 2283006.43 | 08-AUG-16:00 | 2600.44 | 106331.85 | 17-AUG-06:11 |
September | 235378.96 | 4444214.65 | 07-SEP-15:10 | 2174.94 | 109744.64 | 16-SEP-08:70 |
October | 79608.57 | 1994565.53 | 18-OCT-13:43 | 3048.21 | 122460.81 | 14-OCT-05:40 |
November | 23864.72 | 685188.04 | 03-NOV-14:30 | 3768.67 | 132455.58 | 26-NOV-23:32 |
December | 317.10 | 104569.85 | 07-DEC-12:00 | 4304.04 | 129372.74 | 08-DEC-15:10 |
Annual Sum or Average | 154818.28 | 3225.60 | ||||
Minimum of Months | 91.46 | 43669.56 | 1673.14 | 84090.03 | ||
Maximum of Months | 539221.11 | 4444214.65 | 5075.20 | 132455.58 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358428E+10 | 0.38 | 13932.71 | 20-JAN-06:01 | 1.54 |
February | 0.434804E+10 | 0.41 | 14728.90 | 27-FEB-15:50 | 1.59 |
March | 0.669239E+10 | 0.48 | 15893.54 | 28-MAR-15:50 | 1.67 |
April | 0.896465E+10 | 0.56 | 22108.16 | 24-APR-15:10 | 2.05 |
May | 0.840362E+10 | 0.53 | 21400.55 | 30-MAY-04:12 | 2.00 |
June | 0.143413E+11 | 0.74 | 23399.98 | 06-JUN-13:45 | 2.11 |
July | 0.208587E+11 | 0.95 | 23399.98 | 03-JUL-08:17 | 2.11 |
August | 0.204308E+11 | 0.96 | 23399.98 | 01-AUG-10:05 | 2.11 |
September | 0.100783E+11 | 0.60 | 23399.98 | 01-SEP-09:10 | 2.12 |
October | 0.792780E+10 | 0.49 | 23399.98 | 18-OCT-13:30 | 2.13 |
November | 0.608712E+10 | 0.45 | 14797.36 | 06-NOV-15:10 | 1.59 |
December | 0.499447E+10 | 0.40 | 13932.71 | 23-DEC-06:01 | 1.54 |
Annual Sum or Average | 0.116712E+12 | 0.58 | |||
Minimum of Months | 0.358428E+10 | 0.38 | 13932.71 | 1.54 | |
Maximum of Months | 0.208587E+11 | 0.96 | 23399.98 | 2.13 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.299578E+11 | 0.41 | 64568.63 | 09-JAN-06:04 | 1.02 |
February | 0.290623E+11 | 0.40 | 91965.76 | 28-FEB-06:03 | 1.25 |
March | 0.381656E+11 | 0.41 | 149940.16 | 31-MAR-05:02 | 1.68 |
April | 0.464269E+11 | 0.41 | 151913.82 | 25-APR-15:40 | 1.70 |
May | 0.603693E+11 | 0.46 | 217553.26 | 19-MAY-15:20 | 2.11 |
June | 0.102383E+12 | 0.62 | 217553.26 | 20-JUN-10:33 | 2.11 |
July | 0.132933E+12 | 0.70 | 217553.26 | 03-JUL-08:45 | 2.11 |
August | 0.126539E+12 | 0.68 | 217553.26 | 01-AUG-10:20 | 2.11 |
September | 0.702071E+11 | 0.51 | 217553.26 | 01-SEP-10:15 | 2.12 |
October | 0.467683E+11 | 0.40 | 115550.55 | 18-OCT-13:40 | 1.43 |
November | 0.330392E+11 | 0.38 | 105013.77 | 10-NOV-06:02 | 1.35 |
December | 0.281114E+11 | 0.38 | 64568.63 | 26-DEC-06:01 | 1.02 |
Annual Sum or Average | 0.743962E+12 | 0.48 | |||
Minimum of Months | 0.281114E+11 | 0.38 | 64568.63 | 1.02 | |
Maximum of Months | 0.132933E+12 | 0.70 | 217553.26 | 2.12 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403965E+10 | 0.52 | 5803.65 | 02-JAN-04:01 | 0.89 |
February | 0.308677E+10 | 0.45 | 5803.65 | 01-FEB-05:01 | 0.89 |
March | 0.352384E+10 | 0.45 | 6499.29 | 28-MAR-15:50 | 0.95 |
April | 0.370377E+10 | 0.41 | 13473.46 | 25-APR-15:20 | 1.45 |
May | 0.514967E+10 | 0.44 | 24794.30 | 19-MAY-14:50 | 2.11 |
June | 0.963126E+10 | 0.57 | 24794.30 | 06-JUN-13:50 | 2.11 |
July | 0.133572E+11 | 0.65 | 24794.30 | 03-JUL-13:50 | 2.11 |
August | 0.119185E+11 | 0.62 | 24794.30 | 01-AUG-12:25 | 2.11 |
September | 0.588631E+10 | 0.47 | 24794.30 | 01-SEP-14:00 | 2.11 |
October | 0.348243E+10 | 0.39 | 9882.91 | 18-OCT-16:00 | 1.20 |
November | 0.315834E+10 | 0.44 | 5803.65 | 13-NOV-04:01 | 0.89 |
December | 0.368656E+10 | 0.50 | 5803.65 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.706242E+11 | 0.49 | |||
Minimum of Months | 0.308677E+10 | 0.39 | 5803.65 | 0.89 | |
Maximum of Months | 0.133572E+11 | 0.65 | 24794.30 | 2.11 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349682E+10 | 0.40 | 13194.30 | 02-JAN-07:03 | 2.14 |
February | 0.410455E+10 | 0.45 | 13194.30 | 01-FEB-07:02 | 2.17 |
March | 0.525005E+10 | 0.50 | 13194.30 | 01-MAR-07:03 | 2.16 |
April | 0.756639E+10 | 0.61 | 13194.30 | 01-APR-06:05 | 2.16 |
May | 0.866789E+10 | 0.65 | 13194.30 | 01-MAY-06:05 | 2.16 |
June | 0.147725E+11 | 0.95 | 13194.30 | 01-JUN-06:10 | 2.15 |
July | 0.113413E+11 | 0.69 | 13194.30 | 01-JUL-06:10 | 2.14 |
August | 0.131749E+11 | 0.83 | 13194.30 | 01-AUG-06:10 | 2.15 |
September | 0.137358E+11 | 0.91 | 13194.30 | 01-SEP-06:05 | 2.14 |
October | 0.142904E+11 | 0.91 | 13194.30 | 02-OCT-06:05 | 2.15 |
November | 0.111659E+11 | 0.79 | 13194.30 | 01-NOV-06:10 | 2.16 |
December | 0.550445E+10 | 0.49 | 13194.30 | 01-DEC-07:05 | 2.16 |
Annual Sum or Average | 0.113071E+12 | 0.68 | |||
Minimum of Months | 0.349682E+10 | 0.40 | 13194.30 | 2.14 | |
Maximum of Months | 0.147725E+11 | 0.95 | 13194.30 | 2.17 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123279E+12 | 1.53 | 46027.15 | 01-JAN-00:05 | 1.53 |
February | 0.111349E+12 | 1.54 | 46027.15 | 01-FEB-00:10 | 1.53 |
March | 0.123279E+12 | 1.54 | 46027.15 | 01-MAR-00:10 | 1.54 |
April | 0.119302E+12 | 1.54 | 46027.15 | 01-APR-00:10 | 1.54 |
May | 0.123279E+12 | 1.53 | 46027.15 | 01-MAY-00:10 | 1.53 |
June | 0.119302E+12 | 1.53 | 46027.15 | 01-JUN-00:20 | 1.53 |
July | 0.123279E+12 | 1.53 | 46027.15 | 01-JUL-00:03 | 1.53 |
August | 0.123279E+12 | 1.53 | 46027.15 | 01-AUG-00:10 | 1.53 |
September | 0.119302E+12 | 1.53 | 46027.15 | 01-SEP-00:05 | 1.53 |
October | 0.123279E+12 | 1.54 | 46027.15 | 01-OCT-00:10 | 1.53 |
November | 0.119302E+12 | 1.54 | 46027.15 | 01-NOV-00:20 | 1.54 |
December | 0.123279E+12 | 1.54 | 46027.15 | 01-DEC-00:10 | 1.54 |
Annual Sum or Average | 0.145151E+13 | 1.54 | |||
Minimum of Months | 0.111349E+12 | 1.53 | 46027.15 | 1.53 | |
Maximum of Months | 0.123279E+12 | 1.54 | 46027.15 | 1.54 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169084E+10 | 1.05 | 631.29 | 01-JAN-00:05 | 1.05 |
February | 0.152721E+10 | 1.05 | 631.29 | 01-FEB-00:10 | 1.05 |
March | 0.169084E+10 | 1.05 | 631.29 | 01-MAR-00:10 | 1.05 |
April | 0.163629E+10 | 1.05 | 631.29 | 01-APR-00:10 | 1.05 |
May | 0.169084E+10 | 1.05 | 631.29 | 01-MAY-00:10 | 1.05 |
June | 0.163629E+10 | 1.05 | 631.29 | 01-JUN-00:10 | 1.05 |
July | 0.169084E+10 | 1.05 | 631.29 | 01-JUL-00:03 | 1.05 |
August | 0.169084E+10 | 1.05 | 631.29 | 01-AUG-00:10 | 1.05 |
September | 0.163629E+10 | 1.05 | 631.29 | 01-SEP-00:05 | 1.05 |
October | 0.169084E+10 | 1.05 | 631.29 | 01-OCT-00:10 | 1.05 |
November | 0.163629E+10 | 1.05 | 631.29 | 01-NOV-00:10 | 1.05 |
December | 0.169084E+10 | 1.05 | 631.29 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.199082E+11 | 1.05 | |||
Minimum of Months | 0.152721E+10 | 1.05 | 631.29 | 1.05 | |
Maximum of Months | 0.169084E+10 | 1.05 | 631.29 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162515E+11 | 1.05 | 6067.60 | 01-JAN-00:05 | 1.05 |
February | 0.146787E+11 | 1.05 | 6067.60 | 01-FEB-00:10 | 1.05 |
March | 0.162515E+11 | 1.05 | 6067.60 | 01-MAR-00:10 | 1.05 |
April | 0.157272E+11 | 1.05 | 6067.60 | 01-APR-00:10 | 1.05 |
May | 0.162515E+11 | 1.05 | 6067.60 | 01-MAY-00:20 | 1.05 |
June | 0.157272E+11 | 1.05 | 6067.60 | 01-JUN-00:10 | 1.05 |
July | 0.162515E+11 | 1.05 | 6067.60 | 01-JUL-00:03 | 1.05 |
August | 0.162515E+11 | 1.05 | 6067.60 | 01-AUG-00:20 | 1.05 |
September | 0.157272E+11 | 1.05 | 6067.60 | 01-SEP-00:05 | 1.05 |
October | 0.162515E+11 | 1.05 | 6067.60 | 01-OCT-00:20 | 1.05 |
November | 0.157272E+11 | 1.05 | 6067.60 | 01-NOV-00:10 | 1.05 |
December | 0.162515E+11 | 1.05 | 6067.60 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.191348E+12 | 1.05 | |||
Minimum of Months | 0.146787E+11 | 1.05 | 6067.60 | 1.05 | |
Maximum of Months | 0.162515E+11 | 1.05 | 6067.60 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165414E+10 | 1.05 | 617.59 | 01-JAN-00:05 | 1.05 |
February | 0.149406E+10 | 1.05 | 617.59 | 01-FEB-00:10 | 1.05 |
March | 0.165414E+10 | 1.05 | 617.59 | 01-MAR-00:10 | 1.05 |
April | 0.160078E+10 | 1.05 | 617.59 | 01-APR-00:10 | 1.05 |
May | 0.165414E+10 | 1.05 | 617.59 | 01-MAY-00:10 | 1.05 |
June | 0.160078E+10 | 1.05 | 617.59 | 01-JUN-00:10 | 1.05 |
July | 0.165414E+10 | 1.05 | 617.59 | 01-JUL-00:03 | 1.05 |
August | 0.165414E+10 | 1.05 | 617.59 | 01-AUG-00:10 | 1.05 |
September | 0.160078E+10 | 1.05 | 617.59 | 01-SEP-00:05 | 1.05 |
October | 0.165414E+10 | 1.05 | 617.59 | 01-OCT-00:10 | 1.05 |
November | 0.160078E+10 | 1.05 | 617.59 | 01-NOV-00:10 | 1.05 |
December | 0.165414E+10 | 1.05 | 617.59 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.194762E+11 | 1.05 | |||
Minimum of Months | 0.149406E+10 | 1.05 | 617.59 | 1.05 | |
Maximum of Months | 0.165414E+10 | 1.05 | 617.59 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.296634E+09 | 0.269641E+09 | 2256.94 | 09-JAN-07:10 | 2051.56 | 2051.56 | 49.68 | 14.71 |
February | 80817104.66 | 73462748.14 | 1194.12 | 06-FEB-06:01 | 1085.45 | 1085.45 | 45.90 | 11.26 |
March | 30707825.54 | 27913413.42 | 1215.26 | 06-MAR-06:01 | 1104.67 | 1104.67 | 48.02 | 11.33 |
April | 4222818.71 | 3838542.21 | 382.54 | 29-APR-05:01 | 347.73 | 347.73 | 39.69 | 6.78 |
May | 2760874.98 | 2509635.36 | 367.89 | 09-MAY-05:01 | 334.41 | 334.41 | 38.55 | 6.66 |
June | 107287.50 | 97524.33 | 7.77 | 16-JUN-07:00 | 7.06 | 7.06 | 27.23 | 0.76 |
July | 356.82 | 324.35 | 0.07 | 05-JUL-06:11 | 0.06 | 0.06 | 23.91 | 0.01 |
August | 39699.49 | 36086.83 | 22.84 | 17-AUG-13:20 | 20.76 | 20.76 | 28.44 | 1.53 |
September | 596124.90 | 541877.53 | 28.28 | 19-SEP-13:10 | 25.71 | 25.71 | 26.10 | 1.75 |
October | 3196155.10 | 2905304.99 | 426.59 | 10-OCT-05:01 | 387.77 | 387.77 | 40.04 | 7.13 |
November | 19198633.14 | 17451557.52 | 533.68 | 27-NOV-06:03 | 485.11 | 485.11 | 48.34 | 7.88 |
December | 0.108117E+09 | 98278617.97 | 1437.57 | 29-DEC-08:00 | 1306.75 | 1306.75 | 52.41 | 12.15 |
Annual Sum or Average | 0.546399E+09 | 0.496676E+09 | ||||||
Minimum of Months | 356.82 | 324.35 | 0.07 | 0.06 | 0.06 | 23.91 | 0.01 | |
Maximum of Months | 0.296634E+09 | 0.269641E+09 | 2256.94 | 2051.56 | 2051.56 | 52.41 | 14.71 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 171354.91 | 155761.62 | 5.82 | 02-JAN-14:10 | 5.29 | 5.29 | 6.70 | 1.23 |
February | 16610972.80 | 15099374.28 | 650.66 | 27-FEB-15:05 | 591.45 | 591.45 | 6.71 | 18.98 |
March | 23743296.44 | 21582656.46 | 394.05 | 28-MAR-14:50 | 358.20 | 358.20 | 6.71 | 15.02 |
April | 53417003.22 | 48556055.92 | 2073.67 | 06-APR-16:00 | 1884.97 | 1884.97 | 7.17 | 31.61 |
May | 0.304378E+09 | 0.276679E+09 | 9198.39 | 19-MAY-15:30 | 8361.34 | 8361.34 | 6.73 | 58.01 |
June | 0.162575E+10 | 0.147781E+10 | 9590.84 | 06-JUN-13:45 | 8718.08 | 8718.08 | 9.92 | 58.98 |
July | 0.380079E+10 | 0.345492E+10 | 9590.84 | 03-JUL-08:23 | 8718.08 | 8718.08 | 9.34 | 58.98 |
August | 0.344314E+10 | 0.312981E+10 | 9590.84 | 01-AUG-12:25 | 8718.08 | 8718.08 | 9.32 | 58.98 |
September | 0.137920E+10 | 0.125369E+10 | 9590.84 | 01-SEP-10:35 | 8718.08 | 8718.08 | 6.74 | 58.98 |
October | 0.264071E+09 | 0.240040E+09 | 9590.84 | 18-OCT-12:25 | 8718.08 | 8718.08 | 10.37 | 58.98 |
November | 22357239.10 | 20322730.35 | 757.86 | 03-NOV-14:05 | 688.90 | 688.90 | 6.71 | 20.34 |
December | 562763.58 | 511552.09 | 20.23 | 07-DEC-12:00 | 18.39 | 18.39 | 6.70 | 2.95 |
Annual Sum or Average | 0.109342E+11 | 0.993917E+10 | ||||||
Minimum of Months | 171354.91 | 155761.62 | 5.82 | 5.29 | 5.29 | 6.70 | 1.23 | |
Maximum of Months | 0.380079E+10 | 0.345492E+10 | 9590.84 | 8718.08 | 8718.08 | 10.37 | 58.98 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.464719E+09 | 0.422429E+09 | 3300.56 | 02-JAN-08:10 | 3000.21 | 3000.21 | 6.72 | 29.49 |
February | 0.125529E+10 | 0.114106E+10 | 3300.56 | 01-FEB-04:01 | 3000.21 | 3000.21 | 6.72 | 29.49 |
March | 0.200031E+10 | 0.181828E+10 | 3300.56 | 01-MAR-06:50 | 3000.21 | 3000.21 | 6.73 | 29.49 |
April | 0.248818E+10 | 0.226176E+10 | 3300.56 | 01-APR-06:20 | 3000.21 | 3000.21 | 7.16 | 29.49 |
May | 0.347618E+10 | 0.315984E+10 | 3300.56 | 01-MAY-07:07 | 3000.21 | 3000.21 | 6.76 | 29.49 |
June | 0.465994E+10 | 0.423588E+10 | 3300.56 | 01-JUN-04:12 | 3000.21 | 3000.21 | 7.63 | 29.49 |
July | 0.640678E+10 | 0.582377E+10 | 3300.56 | 01-JUL-00:25 | 3000.21 | 3000.21 | 6.86 | 29.49 |
August | 0.608103E+10 | 0.552766E+10 | 3300.56 | 01-AUG-00:10 | 3000.21 | 3000.21 | 6.85 | 29.49 |
September | 0.407679E+10 | 0.370580E+10 | 3300.56 | 01-SEP-00:05 | 3000.21 | 3000.21 | 6.80 | 29.49 |
October | 0.292135E+10 | 0.265551E+10 | 3300.56 | 02-OCT-05:08 | 3000.21 | 3000.21 | 6.78 | 29.49 |
November | 0.177566E+10 | 0.161408E+10 | 3300.56 | 01-NOV-06:11 | 3000.21 | 3000.21 | 6.97 | 29.49 |
December | 0.110895E+10 | 0.100803E+10 | 3300.56 | 01-DEC-09:35 | 3000.21 | 3000.21 | 6.73 | 29.49 |
Annual Sum or Average | 0.367152E+11 | 0.333741E+11 | ||||||
Minimum of Months | 0.464719E+09 | 0.422429E+09 | 3300.56 | 3000.21 | 3000.21 | 6.72 | 29.49 | |
Maximum of Months | 0.640678E+10 | 0.582377E+10 | 3300.56 | 3000.21 | 3000.21 | 7.63 | 29.49 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 94065936.30 | 85505936.10 | 3300.56 | 18-MAY-15:20 | 3000.21 | 3000.21 | 15.36 | 14.74 |
June | 0.826790E+09 | 0.751552E+09 | 3300.56 | 05-JUN-12:20 | 3000.21 | 3000.21 | 15.32 | 14.74 |
July | 0.163391E+10 | 0.148522E+10 | 3300.56 | 03-JUL-09:50 | 3000.21 | 3000.21 | 15.20 | 14.74 |
August | 0.142650E+10 | 0.129669E+10 | 3300.56 | 01-AUG-11:50 | 3000.21 | 3000.21 | 12.77 | 14.74 |
September | 0.428743E+09 | 0.389727E+09 | 3300.56 | 01-SEP-09:40 | 3000.21 | 3000.21 | 15.29 | 14.74 |
October | 29705032.52 | 27001874.56 | 3300.56 | 18-OCT-13:40 | 3000.21 | 3000.21 | 15.40 | 14.74 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
Annual Sum or Average | 0.443971E+10 | 0.403570E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.163391E+10 | 0.148522E+10 | 3300.56 | 3000.21 | 3000.21 | 15.40 | 14.74 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-JAN-00:05 | 3670.82 | 3670.82 | 18.61 | 17.03 |
February | 0.976948E+10 | 0.888046E+10 | 4038.31 | 01-FEB-00:10 | 3670.82 | 3670.82 | 19.04 | 17.03 |
March | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-MAR-00:10 | 3670.82 | 3670.82 | 19.77 | 17.03 |
April | 0.104673E+11 | 0.951478E+10 | 4038.31 | 01-APR-00:10 | 3670.82 | 3670.82 | 20.19 | 17.03 |
May | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-MAY-00:10 | 3670.82 | 3670.82 | 18.81 | 17.03 |
June | 0.104673E+11 | 0.951478E+10 | 4038.31 | 01-JUN-00:10 | 3670.82 | 3670.82 | 19.44 | 17.03 |
July | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-JUL-00:03 | 3670.82 | 3670.82 | 25.16 | 17.03 |
August | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-AUG-00:10 | 3670.82 | 3670.82 | 27.80 | 17.03 |
September | 0.104673E+11 | 0.951478E+10 | 4038.31 | 01-SEP-00:05 | 3670.82 | 3670.82 | 19.36 | 17.03 |
October | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-OCT-00:10 | 3670.82 | 3670.82 | 19.42 | 17.03 |
November | 0.104673E+11 | 0.951478E+10 | 4038.31 | 01-NOV-00:10 | 3670.82 | 3670.82 | 19.76 | 17.03 |
December | 0.108162E+11 | 0.983194E+10 | 4038.31 | 01-DEC-00:10 | 3670.82 | 3670.82 | 20.05 | 17.03 |
Annual Sum or Average | 0.127352E+12 | 0.115763E+12 | ||||||
Minimum of Months | 0.976948E+10 | 0.888046E+10 | 4038.31 | 3670.82 | 3670.82 | 18.61 | 17.03 | |
Maximum of Months | 0.108162E+11 | 0.983194E+10 | 4038.31 | 3670.82 | 3670.82 | 27.80 | 17.03 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.77 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.77 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.65 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.74 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.33 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.02 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 57.25 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.30 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.37 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.99 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.13 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.08 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.65 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.37 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.182507E+10 | 0.165899E+10 | 12965.43 | 02-JAN-12:40 | 11785.57 | 11785.57 | 21.30 | 53.08 |
February | 0.493137E+10 | 0.448261E+10 | 12994.38 | 27-FEB-15:30 | 11811.89 | 11811.89 | 24.40 | 53.08 |
March | 0.785863E+10 | 0.714350E+10 | 12985.95 | 28-MAR-16:00 | 11804.23 | 11804.23 | 23.50 | 53.08 |
April | 0.977717E+10 | 0.888745E+10 | 13014.27 | 06-APR-16:00 | 11829.97 | 11829.97 | 26.31 | 53.08 |
May | 0.140332E+11 | 0.127562E+11 | 26020.07 | 19-MAY-14:00 | 23652.25 | 23652.25 | 25.91 | 106.16 |
June | 0.215362E+11 | 0.195764E+11 | 26057.64 | 20-JUN-15:10 | 23686.40 | 23686.40 | 27.64 | 106.16 |
July | 0.315456E+11 | 0.286750E+11 | 26076.74 | 15-JUL-15:52 | 23703.75 | 23703.75 | 28.51 | 106.16 |
August | 0.293965E+11 | 0.267214E+11 | 26027.29 | 08-AUG-16:00 | 23658.81 | 23658.81 | 26.25 | 106.16 |
September | 0.176755E+11 | 0.160670E+11 | 26097.27 | 07-SEP-14:25 | 23722.42 | 23722.42 | 29.61 | 106.16 |
October | 0.115995E+11 | 0.105440E+11 | 26013.12 | 18-OCT-13:43 | 23645.92 | 23645.92 | 25.60 | 106.16 |
November | 0.697645E+10 | 0.634160E+10 | 12992.42 | 03-NOV-14:30 | 11810.11 | 11810.11 | 24.19 | 53.08 |
December | 0.435515E+10 | 0.395883E+10 | 12967.99 | 07-DEC-12:00 | 11787.90 | 11787.90 | 21.57 | 53.08 |
Annual Sum or Average | 0.161510E+12 | 0.146813E+12 | ||||||
Minimum of Months | 0.182507E+10 | 0.165899E+10 | 12965.43 | 11785.57 | 11785.57 | 21.30 | 53.08 | |
Maximum of Months | 0.315456E+11 | 0.286750E+11 | 26097.27 | 23722.42 | 23722.42 | 29.61 | 106.16 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 43.15 | 82.00 | 317831.29 | 1997492.73 | 09-JAN-07:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 35.43 | 35.43 | 183947.12 | 1766035.39 | 06-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29.44 | 29.44 | 102013.00 | 1610030.13 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.97 | 29.97 | 33015.83 | 1199794.39 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 25.39 | 25.39 | 19719.43 | 1210289.50 | 09-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.67 | 23.67 | 1252.04 | 173230.01 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 23.92 | 23.92 | 5.24 | 2598.73 | 05-JUL-06:11 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.80 | 23.80 | 347.78 | 343416.23 | 17-AUG-13:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.54 | 24.54 | 6182.97 | 407971.39 | 19-SEP-13:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.79 | 21.79 | 23243.09 | 1331680.98 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 30.82 | 30.82 | 80588.66 | 1308623.02 | 30-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33.41 | 33.41 | 200044.30 | 1572169.23 | 26-DEC-06:01 |
Annual Sum or Average | 0.00 | 80386.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.79 | 21.79 | 5.24 | 2598.73 | ||
Maximum of Months | 0.00 | 0.00 | 43.15 | 82.00 | 317831.29 | 1997492.73 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 731.52 | 52606.08 | 02-JAN-14:10 | 7.13 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 13842.44 | 643010.13 | 27-FEB-15:30 | 11.91 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23602.04 | 466495.79 | 28-MAR-16:00 | 10.48 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43541.54 | 1023362.27 | 06-APR-16:00 | 14.99 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 85480.52 | 1500494.53 | 19-MAY-12:05 | 12.78 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 260120.95 | 2052890.56 | 20-JUN-12:13 | 15.02 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 413656.26 | 2393762.50 | 14-JUL-09:52 | 16.40 | 7.99 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 363976.18 | 1854555.89 | 31-AUG-12:02 | 14.21 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 182255.69 | 2380564.45 | 07-SEP-15:00 | 16.35 | 7.94 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 72569.99 | 1887208.25 | 18-OCT-13:43 | 14.34 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 24362.66 | 601816.64 | 03-NOV-14:30 | 11.57 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2381.77 | 119792.12 | 07-DEC-12:00 | 7.67 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 124740.71 | 0.00 | ||||||
Minimum of Months | 731.52 | 52606.08 | 7.13 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 413656.26 | 2393762.50 | 16.40 | 7.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 573.99 | 49642.18 | 02-JAN-14:10 | 16.36 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 13382.92 | 645182.81 | 27-FEB-15:30 | 15.06 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 22939.88 | 464888.45 | 28-MAR-16:00 | 15.91 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 42731.15 | 1136308.35 | 06-APR-16:00 | 15.29 | 7.26 | 0.00 | 0.00 | 01-APR-00:10 |
May | 85876.39 | 1809252.69 | 19-MAY-17:00 | 15.26 | 11.40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 273205.08 | 2375418.81 | 20-JUN-12:10 | 16.33 | 12.65 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 437365.67 | 2496770.08 | 14-JUL-09:50 | 17.33 | 13.20 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 378621.55 | 2287311.51 | 01-AUG-12:50 | 15.97 | 11.32 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 189771.05 | 2383865.78 | 07-SEP-15:00 | 16.36 | 7.92 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 76484.69 | 2153651.76 | 18-OCT-13:40 | 15.43 | 11.05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23757.13 | 607723.69 | 03-NOV-14:05 | 13.84 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2005.61 | 118305.25 | 07-DEC-12:00 | 16.29 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 129804.26 | 0.00 | ||||||
Minimum of Months | 573.99 | 49642.18 | 13.84 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 437365.67 | 2496770.08 | 17.33 | 13.20 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15368.62 | 37488.96 | 13-JAN-16:30 | 18.97 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50495.80 | 129378.14 | 27-FEB-16:00 | 20.52 | 19.32 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 82924.83 | 132434.75 | 15-MAR-18:50 | 20.57 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 147829.79 | 1013387.00 | 07-APR-14:00 | 35.24 | 26.42 | 0.00 | 0.00 | 01-APR-00:10 |
May | 74358.90 | 1006203.09 | 20-MAY-16:00 | 35.12 | 31.34 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 275630.08 | 1376506.44 | 29-JUN-15:00 | 41.16 | 34.56 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 635945.18 | 1936718.65 | 17-JUL-16:00 | 50.18 | 40.66 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 669819.61 | 2027878.99 | 05-AUG-16:00 | 51.64 | 39.88 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 159995.66 | 1300482.84 | 02-SEP-17:00 | 39.93 | 35.86 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 78372.36 | 809625.65 | 18-OCT-15:00 | 31.88 | 26.79 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82958.78 | 134218.28 | 17-NOV-17:00 | 20.60 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 101815.16 | 153394.02 | 08-DEC-20:10 | 20.92 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 199515.22 | 0.00 | ||||||
Minimum of Months | 15368.62 | 37488.96 | 18.97 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 669819.61 | 2027878.99 | 51.64 | 40.66 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.91 | 57.91 | 16135.06 | 57877.02 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.29 | 57.29 | 16514.12 | 58184.06 | 17-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.28 | 57.28 | 17371.52 | 58080.80 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.35 | 57.35 | 15686.02 | 56501.36 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.99 | 57.99 | 15336.02 | 54000.04 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.63 | 57.63 | 14754.70 | 50704.93 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.77 | 57.77 | 12894.00 | 47668.63 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.86 | 57.86 | 13810.05 | 45986.74 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.87 | 57.87 | 13115.78 | 47092.10 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.80 | 57.80 | 13695.34 | 49894.31 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.67 | 57.67 | 14752.91 | 53085.33 | 30-NOV-12:45 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.52 | 57.52 | 15068.80 | 55889.83 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 14918.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.28 | 57.28 | 12894.00 | 45986.74 | ||
Maximum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 17371.52 | 58184.06 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 91.46 | 43669.56 | 02-JAN-12:40 | 21.30 | 20.45 | 1880.21 | 128375.12 | 03-JAN-16:00 |
February | 13497.59 | 731590.79 | 27-FEB-15:30 | 24.40 | 21.10 | 4012.24 | 131499.21 | 28-FEB-06:40 |
March | 22908.95 | 531685.51 | 28-MAR-16:00 | 23.50 | 21.10 | 5075.20 | 130982.46 | 04-MAR-06:40 |
April | 44430.35 | 1154916.46 | 06-APR-16:00 | 26.31 | 21.10 | 4614.90 | 130664.16 | 27-APR-12:50 |
May | 95874.17 | 2136202.01 | 19-MAY-14:00 | 25.91 | 21.14 | 3818.78 | 119966.96 | 22-MAY-09:40 |
June | 332346.11 | 2899747.26 | 20-JUN-15:10 | 27.64 | 23.57 | 1673.14 | 106168.60 | 16-JUN-08:40 |
July | 539221.11 | 3286976.56 | 15-JUL-15:52 | 28.51 | 23.60 | 1790.89 | 84090.03 | 08-JUL-08:20 |
August | 457144.26 | 2283006.43 | 08-AUG-16:00 | 26.25 | 21.95 | 2600.44 | 106331.85 | 17-AUG-06:11 |
September | 235378.96 | 4444214.65 | 07-SEP-15:10 | 31.12 | 25.57 | 2174.94 | 109744.64 | 16-SEP-08:70 |
October | 79608.57 | 1994565.53 | 18-OCT-13:43 | 25.60 | 21.10 | 3048.21 | 122460.81 | 14-OCT-05:40 |
November | 23864.72 | 685188.04 | 03-NOV-14:30 | 24.19 | 21.10 | 3768.67 | 132455.58 | 26-NOV-23:32 |
December | 317.10 | 104569.85 | 07-DEC-12:00 | 21.57 | 20.75 | 4304.04 | 129372.74 | 08-DEC-15:10 |
Annual Sum or Average | 154818.28 | 3225.60 | ||||||
Minimum of Months | 91.46 | 43669.56 | 21.30 | 20.45 | 1673.14 | 84090.03 | ||
Maximum of Months | 539221.11 | 4444214.65 | 31.12 | 25.57 | 5075.20 | 132455.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.467141E+11 | 0.00 | 0.168075E+10 | 0.358428E+10 | 0.00 | 0.00 |
February | 0.237693E+11 | 0.00 | 0.500525E+10 | 0.434804E+10 | 0.00 | 0.00 |
March | 0.124352E+11 | 0.00 | 0.606236E+10 | 0.669239E+10 | 0.00 | 0.00 |
April | 0.275033E+10 | 0.00 | 0.893683E+10 | 0.896465E+10 | 0.00 | 0.00 |
May | 0.185232E+10 | 0.00 | 0.192438E+11 | 0.840362E+10 | 0.00 | 0.00 |
June | 75257288.35 | 0.00 | 0.620964E+11 | 0.143413E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109701E+12 | 0.208587E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.959222E+11 | 0.204308E+11 | 0.00 | 0.00 |
September | 0.600859E+09 | 0.00 | 0.422725E+11 | 0.100783E+11 | 0.00 | 0.00 |
October | 0.246037E+10 | 0.00 | 0.165245E+11 | 0.792780E+10 | 0.00 | 0.00 |
November | 0.900273E+10 | 0.00 | 0.845911E+10 | 0.608712E+10 | 0.00 | 0.00 |
December | 0.256367E+11 | 0.00 | 0.498470E+10 | 0.499447E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125297E+12 | 0.00 | 0.380889E+12 | 0.116712E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.168075E+10 | 0.358428E+10 | 0.00 | 0.00 |
Maximum of Months | 0.467141E+11 | 0.00 | 0.109701E+12 | 0.208587E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.682338E+12 | 0.00 | 28319.24 | 0.299578E+11 | 0.00 | 0.00 |
February | 0.360161E+12 | 0.00 | 0.259507E+11 | 0.290623E+11 | 0.00 | 0.00 |
March | 0.222619E+12 | 0.00 | 0.532920E+11 | 0.381656E+11 | 0.00 | 0.00 |
April | 0.708261E+11 | 0.00 | 0.901903E+11 | 0.464269E+11 | 0.00 | 0.00 |
May | 0.428085E+11 | 0.00 | 0.175443E+12 | 0.603693E+11 | 0.00 | 0.00 |
June | 0.251675E+10 | 0.00 | 0.511067E+12 | 0.102383E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.848319E+12 | 0.132933E+12 | 0.00 | 0.00 |
August | 0.739045E+09 | 0.00 | 0.740113E+12 | 0.126539E+12 | 0.00 | 0.00 |
September | 0.125788E+11 | 0.00 | 0.362161E+12 | 0.702071E+11 | 0.00 | 0.00 |
October | 0.498839E+11 | 0.00 | 0.159021E+12 | 0.467683E+11 | 0.00 | 0.00 |
November | 0.167775E+12 | 0.00 | 0.517635E+11 | 0.330392E+11 | 0.00 | 0.00 |
December | 0.431710E+12 | 0.00 | 0.419038E+09 | 0.281114E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.204396E+13 | 0.00 | 0.301774E+13 | 0.743962E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 28319.24 | 0.281114E+11 | 0.00 | 0.00 |
Maximum of Months | 0.682338E+12 | 0.00 | 0.848319E+12 | 0.132933E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.109647E+12 | 0.00 | 0.00 | 0.403965E+10 | 0.00 | 0.00 |
February | 0.559132E+11 | 0.00 | 0.905366E+09 | 0.308677E+10 | 0.00 | 0.00 |
March | 0.368367E+11 | 0.00 | 0.193020E+10 | 0.352384E+10 | 0.00 | 0.00 |
April | 0.122218E+11 | 0.00 | 0.656492E+10 | 0.370377E+10 | 0.00 | 0.00 |
May | 0.841947E+10 | 0.00 | 0.164679E+11 | 0.514967E+10 | 0.00 | 0.00 |
June | 0.668392E+09 | 0.00 | 0.556772E+11 | 0.963126E+10 | 0.00 | 0.00 |
July | 14834955.52 | 0.00 | 0.932269E+11 | 0.133572E+11 | 0.00 | 0.00 |
August | 0.192935E+09 | 0.00 | 0.791588E+11 | 0.119185E+11 | 0.00 | 0.00 |
September | 0.294707E+10 | 0.00 | 0.349673E+11 | 0.588631E+10 | 0.00 | 0.00 |
October | 0.101726E+11 | 0.00 | 0.824500E+10 | 0.348243E+10 | 0.00 | 0.00 |
November | 0.327273E+11 | 0.00 | 0.115887E+10 | 0.315834E+10 | 0.00 | 0.00 |
December | 0.748195E+11 | 0.00 | 58897.10 | 0.368656E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.344581E+12 | 0.00 | 0.298302E+12 | 0.706242E+11 | 0.00 | 0.00 |
Minimum of Months | 14834955.52 | 0.00 | 0.00 | 0.308677E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109647E+12 | 0.00 | 0.932269E+11 | 0.133572E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.171053E+11 | 0.00 | 2165872.57 | 0.349682E+10 | 0.00 | 0.00 |
February | 0.752468E+10 | 0.00 | 0.585109E+09 | 0.410455E+10 | 0.00 | 0.00 |
March | 0.275697E+10 | 0.00 | 0.259040E+09 | 0.525005E+10 | 0.00 | 0.00 |
April | 0.251091E+09 | 0.00 | 0.452755E+10 | 0.756639E+10 | 0.00 | 0.00 |
May | 20619354.00 | 0.00 | 0.134114E+11 | 0.866789E+10 | 0.00 | 0.00 |
June | 315000.73 | 0.00 | 0.316774E+11 | 0.147725E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.374466E+11 | 0.113413E+11 | 0.00 | 0.00 |
August | 100.14 | 0.00 | 0.409388E+11 | 0.131749E+11 | 0.00 | 0.00 |
September | 186910.98 | 0.00 | 0.243872E+11 | 0.137358E+11 | 0.00 | 0.00 |
October | 8018038.13 | 0.00 | 0.770630E+10 | 0.142904E+11 | 0.00 | 0.00 |
November | 0.447374E+09 | 0.00 | 0.326130E+09 | 0.111659E+11 | 0.00 | 0.00 |
December | 0.636440E+10 | 0.00 | 0.00 | 0.550445E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.344790E+11 | 0.00 | 0.161268E+12 | 0.113071E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.349682E+10 | 0.00 | 0.00 |
Maximum of Months | 0.171053E+11 | 0.00 | 0.409388E+11 | 0.147725E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.144541E+11 | 0.295918E+12 | 0.00 | 62.30 |
February | 0.00 | 0.00 | 0.194913E+11 | 0.353006E+12 | 0.00 | 87.63 |
March | 0.00 | 0.00 | 0.217570E+11 | 0.398140E+12 | 0.00 | 99.64 |
April | 0.00 | 0.00 | 0.763220E+11 | 0.396602E+12 | 0.00 | 95.97 |
May | 0.00 | 0.00 | 0.255905E+11 | 0.295725E+12 | 0.00 | 61.17 |
June | 0.00 | 0.00 | 0.170931E+12 | 0.302048E+12 | 0.00 | 52.20 |
July | 0.00 | 0.00 | 0.554923E+12 | 0.371190E+12 | 0.00 | 42.83 |
August | 0.00 | 0.00 | 0.685760E+12 | 0.475869E+12 | 0.00 | 71.40 |
September | 0.00 | 0.00 | 0.628787E+11 | 0.249324E+12 | 0.00 | 41.89 |
October | 0.00 | 0.00 | 0.311430E+11 | 0.380589E+12 | 0.00 | 92.34 |
November | 0.00 | 0.00 | 0.217126E+11 | 0.385430E+12 | 0.00 | 96.42 |
December | 0.00 | 0.00 | 0.223808E+11 | 0.398499E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.170734E+13 | 0.430234E+13 | 0.00 | 903.43 |
Minimum of Months | 0.00 | 0.00 | 0.144541E+11 | 0.249324E+12 | 0.00 | 41.89 |
Maximum of Months | 0.00 | 0.00 | 0.685760E+12 | 0.475869E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.413580E+10 | 0.255304E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.105210E+11 | 0.357807E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185152E+11 | 0.513422E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.244279E+11 | 0.599542E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.711469E+10 | 0.310618E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136567E+11 | 0.433222E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211105E+11 | 0.604502E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268751E+11 | 0.700190E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.727912E+10 | 0.311654E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.130786E+11 | 0.414990E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180710E+11 | 0.496283E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.240892E+11 | 0.609088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188875E+12 | 0.560662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.413580E+10 | 0.255304E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268751E+11 | 0.700190E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.124435E+11 | 0.190177E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.771775E+11 | 0.299842E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.158027E+12 | 0.459426E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223160E+12 | 0.557849E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.603963E+11 | 0.283634E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126815E+12 | 0.408570E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198732E+12 | 0.573361E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254100E+12 | 0.665905E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.634209E+11 | 0.287374E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112686E+12 | 0.376253E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.152620E+12 | 0.441457E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.198861E+12 | 0.531541E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163844E+13 | 0.507539E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.124435E+11 | 0.190177E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.254100E+12 | 0.665905E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.288540E+09 | 0.172024E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.561565E+10 | 0.262581E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.136834E+11 | 0.425454E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209528E+11 | 0.539252E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.518379E+10 | 0.270152E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124742E+11 | 0.408390E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198636E+11 | 0.577517E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.252892E+11 | 0.668348E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.569911E+10 | 0.278470E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.959572E+10 | 0.349647E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.128248E+11 | 0.402279E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.170919E+11 | 0.487335E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148563E+12 | 0.484145E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.288540E+09 | 0.172024E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252892E+11 | 0.668348E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.358428E+10 | 0.168075E+10 | 0.467141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.434804E+10 | 0.500525E+10 | 0.237693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.669239E+10 | 0.606236E+10 | 0.124352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.896465E+10 | 0.893683E+10 | 0.275033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840362E+10 | 0.192438E+11 | 0.185232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143413E+11 | 0.620964E+11 | 75257288.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208587E+11 | 0.109701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204308E+11 | 0.959222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100783E+11 | 0.422725E+11 | 0.600859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792780E+10 | 0.165245E+11 | 0.246037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608712E+10 | 0.845911E+10 | 0.900273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.499447E+10 | 0.498470E+10 | 0.256367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116712E+12 | 0.380889E+12 | 0.125297E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358428E+10 | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208587E+11 | 0.109701E+12 | 0.467141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.299578E+11 | 28319.24 | 0.682338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290623E+11 | 0.259507E+11 | 0.360161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381656E+11 | 0.532920E+11 | 0.222619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464269E+11 | 0.901903E+11 | 0.708261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603693E+11 | 0.175443E+12 | 0.428085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102383E+12 | 0.511067E+12 | 0.251675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132933E+12 | 0.848319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126539E+12 | 0.740113E+12 | 0.739045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.702071E+11 | 0.362161E+12 | 0.125788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.467683E+11 | 0.159021E+12 | 0.498839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330392E+11 | 0.517635E+11 | 0.167775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281114E+11 | 0.419038E+09 | 0.431710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.743962E+12 | 0.301774E+13 | 0.204396E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281114E+11 | 28319.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132933E+12 | 0.848319E+12 | 0.682338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.403965E+10 | 0.00 | 0.109647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308677E+10 | 0.905366E+09 | 0.559132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352384E+10 | 0.193020E+10 | 0.368367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370377E+10 | 0.656492E+10 | 0.122218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.514967E+10 | 0.164679E+11 | 0.841947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963126E+10 | 0.556772E+11 | 0.668392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133572E+11 | 0.932269E+11 | 14834955.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119185E+11 | 0.791588E+11 | 0.192935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.588631E+10 | 0.349673E+11 | 0.294707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348243E+10 | 0.824500E+10 | 0.101726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315834E+10 | 0.115887E+10 | 0.327273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368656E+10 | 58897.10 | 0.748195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706242E+11 | 0.298302E+12 | 0.344581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308677E+10 | 0.00 | 14834955.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133572E+11 | 0.932269E+11 | 0.109647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349682E+10 | 2165872.57 | 0.171053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410455E+10 | 0.585109E+09 | 0.752468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525005E+10 | 0.259040E+09 | 0.275697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756639E+10 | 0.452825E+10 | 0.251091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.866789E+10 | 0.134115E+11 | 20619354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147725E+11 | 0.316774E+11 | 315000.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113413E+11 | 0.374466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131749E+11 | 0.409388E+11 | 100.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137358E+11 | 0.243872E+11 | 186910.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142904E+11 | 0.770630E+10 | 8018038.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111659E+11 | 0.326130E+09 | 0.447374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.550445E+10 | 0.00 | 0.636440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113071E+12 | 0.161268E+12 | 0.344790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147725E+11 | 0.409388E+11 | 0.171053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123279E+12 | 0.929632E+10 | 0.00 | 0.00 | 0.00 | 0.166731E+12 | 0.00 | 0.00 |
February | 0.111349E+12 | 0.133877E+11 | 0.00 | 0.00 | 0.00 | 0.234497E+12 | 0.00 | 0.00 |
March | 0.123279E+12 | 0.147364E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
April | 0.119302E+12 | 0.570053E+11 | 0.00 | 0.00 | 0.00 | 0.256827E+12 | 0.00 | 0.00 |
May | 0.123279E+12 | 0.175753E+11 | 0.00 | 0.00 | 0.00 | 0.163694E+12 | 0.00 | 0.00 |
June | 0.119302E+12 | 0.128505E+12 | 0.00 | 0.00 | 0.00 | 0.139691E+12 | 0.00 | 0.00 |
July | 0.123279E+12 | 0.422146E+12 | 0.00 | 0.00 | 0.00 | 0.114618E+12 | 0.00 | 0.00 |
August | 0.123279E+12 | 0.525113E+12 | 0.00 | 0.00 | 0.00 | 0.191082E+12 | 0.00 | 0.00 |
September | 0.119302E+12 | 0.454691E+11 | 0.00 | 0.00 | 0.00 | 0.112108E+12 | 0.00 | 0.00 |
October | 0.123279E+12 | 0.220628E+11 | 0.00 | 0.00 | 0.00 | 0.247117E+12 | 0.00 | 0.00 |
November | 0.119302E+12 | 0.147836E+11 | 0.00 | 0.00 | 0.00 | 0.258038E+12 | 0.00 | 0.00 |
December | 0.123279E+12 | 0.150009E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.145151E+13 | 0.128508E+13 | 0.00 | 0.00 | 0.00 | 0.241768E+13 | 0.00 | 0.00 |
Minimum of Months | 0.111349E+12 | 0.929632E+10 | 0.00 | 0.00 | 0.00 | 0.112108E+12 | 0.00 | 0.00 |
Maximum of Months | 0.123279E+12 | 0.525113E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169084E+10 | 0.327360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152721E+10 | 0.847012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169084E+10 | 0.150718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163629E+10 | 0.200687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169084E+10 | 0.569934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163629E+10 | 0.109607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169084E+10 | 0.167563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169084E+10 | 0.215640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163629E+10 | 0.579887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169084E+10 | 0.106196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163629E+10 | 0.147445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169084E+10 | 0.196892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199082E+11 | 0.152717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152721E+10 | 0.327360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169084E+10 | 0.215640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162515E+11 | 0.967726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146787E+11 | 0.618720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162515E+11 | 0.128335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157272E+11 | 0.183102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162515E+11 | 0.482843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157272E+11 | 0.101685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162515E+11 | 0.157647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162515E+11 | 0.203761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157272E+11 | 0.504107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162515E+11 | 0.913124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157272E+11 | 0.124202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162515E+11 | 0.161958E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191348E+12 | 0.132225E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146787E+11 | 0.967726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162515E+11 | 0.203761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165414E+10 | 0.222441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149406E+10 | 0.448391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165414E+10 | 0.110830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160078E+10 | 0.171611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165414E+10 | 0.413642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160078E+10 | 0.999107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165414E+10 | 0.157426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165414E+10 | 0.202598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160078E+10 | 0.451520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165414E+10 | 0.775339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160078E+10 | 0.104028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165414E+10 | 0.138727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194762E+11 | 0.119625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149406E+10 | 0.222441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165414E+10 | 0.202598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.358428E+10 | 0.467141E+11 | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.434804E+10 | 0.237693E+11 | 0.500525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.669239E+10 | 0.124352E+11 | 0.606236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.896465E+10 | 0.275033E+10 | 0.893683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840362E+10 | 0.185232E+10 | 0.192438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143413E+11 | 75257288.35 | 0.620964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.208587E+11 | 0.00 | 0.109701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.204308E+11 | 0.00 | 0.959222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100783E+11 | 0.600859E+09 | 0.422725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.792780E+10 | 0.246037E+10 | 0.165245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608712E+10 | 0.900273E+10 | 0.845911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.499447E+10 | 0.256367E+11 | 0.498470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116712E+12 | 0.125297E+12 | 0.380889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358428E+10 | 0.00 | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208587E+11 | 0.467141E+11 | 0.109701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.299578E+11 | 0.682338E+12 | 28319.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290623E+11 | 0.360161E+12 | 0.259507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381656E+11 | 0.222619E+12 | 0.532920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464269E+11 | 0.708261E+11 | 0.901903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603693E+11 | 0.428085E+11 | 0.175443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102383E+12 | 0.251675E+10 | 0.511067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132933E+12 | 0.00 | 0.848319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126539E+12 | 0.739045E+09 | 0.740113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.702071E+11 | 0.125788E+11 | 0.362161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.467683E+11 | 0.498839E+11 | 0.159021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330392E+11 | 0.167775E+12 | 0.517635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281114E+11 | 0.431710E+12 | 0.419038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.743962E+12 | 0.204396E+13 | 0.301774E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281114E+11 | 0.00 | 28319.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132933E+12 | 0.682338E+12 | 0.848319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.403965E+10 | 0.109647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308677E+10 | 0.559132E+11 | 0.905366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352384E+10 | 0.368367E+11 | 0.193020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370377E+10 | 0.122218E+11 | 0.656492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.514967E+10 | 0.841947E+10 | 0.164679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963126E+10 | 0.668392E+09 | 0.556772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133572E+11 | 14834955.52 | 0.932269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119185E+11 | 0.192935E+09 | 0.791588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.588631E+10 | 0.294707E+10 | 0.349673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348243E+10 | 0.101726E+11 | 0.824500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315834E+10 | 0.327273E+11 | 0.115887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368656E+10 | 0.748195E+11 | 58897.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706242E+11 | 0.344581E+12 | 0.298302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308677E+10 | 14834955.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133572E+11 | 0.109647E+12 | 0.932269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.349682E+10 | 0.171053E+11 | 2165872.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410455E+10 | 0.752468E+10 | 0.585109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.525005E+10 | 0.275697E+10 | 0.259040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756639E+10 | 0.251091E+09 | 0.452755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.866789E+10 | 20619354.00 | 0.134114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147725E+11 | 315000.73 | 0.316774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113413E+11 | 0.00 | 0.374466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131749E+11 | 100.14 | 0.409388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137358E+11 | 186910.98 | 0.243872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142904E+11 | 8018038.13 | 0.770630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111659E+11 | 0.447374E+09 | 0.326130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.550445E+10 | 0.636440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113071E+12 | 0.344790E+11 | 0.161268E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147725E+11 | 0.171053E+11 | 0.409388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123279E+12 | 0.00 | 0.144541E+11 | 0.00 | 0.515780E+10 | 0.00 | 0.00 | 0.00 | 0.167481E+12 | 0.00 | 0.00 | 0.00 |
February | 0.111349E+12 | 0.00 | 0.194913E+11 | 0.00 | 0.610361E+10 | 0.00 | 0.00 | 0.00 | 0.235553E+12 | 0.00 | 0.00 | 0.00 |
March | 0.123279E+12 | 0.00 | 0.217570E+11 | 0.00 | 0.702059E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
April | 0.119302E+12 | 0.00 | 0.763220E+11 | 0.00 | 0.193167E+11 | 0.00 | 0.00 | 0.00 | 0.257983E+12 | 0.00 | 0.00 | 0.00 |
May | 0.123279E+12 | 0.00 | 0.255905E+11 | 0.00 | 0.801520E+10 | 0.00 | 0.00 | 0.00 | 0.164430E+12 | 0.00 | 0.00 | 0.00 |
June | 0.119302E+12 | 0.00 | 0.170931E+12 | 0.00 | 0.424267E+11 | 0.00 | 0.00 | 0.00 | 0.140319E+12 | 0.00 | 0.00 | 0.00 |
July | 0.123279E+12 | 0.00 | 0.554923E+12 | 0.00 | 0.132776E+12 | 0.00 | 0.00 | 0.00 | 0.115134E+12 | 0.00 | 0.00 | 0.00 |
August | 0.123279E+12 | 0.00 | 0.685760E+12 | 0.00 | 0.160648E+12 | 0.00 | 0.00 | 0.00 | 0.191942E+12 | 0.00 | 0.00 | 0.00 |
September | 0.119302E+12 | 0.00 | 0.628787E+11 | 0.00 | 0.174096E+11 | 0.00 | 0.00 | 0.00 | 0.112613E+12 | 0.00 | 0.00 | 0.00 |
October | 0.123279E+12 | 0.00 | 0.311430E+11 | 0.00 | 0.908020E+10 | 0.00 | 0.00 | 0.00 | 0.248230E+12 | 0.00 | 0.00 | 0.00 |
November | 0.119302E+12 | 0.00 | 0.217126E+11 | 0.00 | 0.692906E+10 | 0.00 | 0.00 | 0.00 | 0.259199E+12 | 0.00 | 0.00 | 0.00 |
December | 0.123279E+12 | 0.00 | 0.223808E+11 | 0.00 | 0.737992E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145151E+13 | 0.00 | 0.170734E+13 | 0.00 | 0.422263E+12 | 0.00 | 0.00 | 0.00 | 0.242856E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111349E+12 | 0.00 | 0.144541E+11 | 0.00 | 0.515780E+10 | 0.00 | 0.00 | 0.00 | 0.112613E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123279E+12 | 0.00 | 0.685760E+12 | 0.00 | 0.160648E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169084E+10 | 0.00 | 0.413580E+10 | 0.00 | 0.862204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152721E+10 | 0.00 | 0.105210E+11 | 0.00 | 0.205086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169084E+10 | 0.00 | 0.185152E+11 | 0.00 | 0.344338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163629E+10 | 0.00 | 0.244279E+11 | 0.00 | 0.435912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169084E+10 | 0.00 | 0.711469E+10 | 0.00 | 0.141535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163629E+10 | 0.00 | 0.136567E+11 | 0.00 | 0.269593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169084E+10 | 0.00 | 0.211105E+11 | 0.00 | 0.435419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169084E+10 | 0.00 | 0.268751E+11 | 0.00 | 0.531106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163629E+10 | 0.00 | 0.727912E+10 | 0.00 | 0.148025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169084E+10 | 0.00 | 0.130786E+11 | 0.00 | 0.245906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163629E+10 | 0.00 | 0.180710E+11 | 0.00 | 0.332654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169084E+10 | 0.00 | 0.240892E+11 | 0.00 | 0.440005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199082E+11 | 0.00 | 0.188875E+12 | 0.00 | 0.361580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152721E+10 | 0.00 | 0.413580E+10 | 0.00 | 0.862204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169084E+10 | 0.00 | 0.268751E+11 | 0.00 | 0.531106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162515E+11 | 0.00 | 0.124435E+11 | 0.00 | 0.276624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146787E+11 | 0.00 | 0.771775E+11 | 0.00 | 0.153055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162515E+11 | 0.00 | 0.158027E+12 | 0.00 | 0.296911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157272E+11 | 0.00 | 0.223160E+12 | 0.00 | 0.400576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162515E+11 | 0.00 | 0.603963E+11 | 0.00 | 0.121120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157272E+11 | 0.00 | 0.126815E+12 | 0.00 | 0.251298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162515E+11 | 0.00 | 0.198732E+12 | 0.00 | 0.410847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162515E+11 | 0.00 | 0.254100E+12 | 0.00 | 0.503390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157272E+11 | 0.00 | 0.634209E+11 | 0.00 | 0.130102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162515E+11 | 0.00 | 0.112686E+12 | 0.00 | 0.213738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157272E+11 | 0.00 | 0.152620E+12 | 0.00 | 0.284185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162515E+11 | 0.00 | 0.198861E+12 | 0.00 | 0.369026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191348E+12 | 0.00 | 0.163844E+13 | 0.00 | 0.316191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146787E+11 | 0.00 | 0.124435E+11 | 0.00 | 0.276624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162515E+11 | 0.00 | 0.254100E+12 | 0.00 | 0.503390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165414E+10 | 0.00 | 0.288540E+09 | 0.00 | 66099338.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149406E+10 | 0.00 | 0.561565E+10 | 0.00 | 0.113174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165414E+10 | 0.00 | 0.136834E+11 | 0.00 | 0.260040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160078E+10 | 0.00 | 0.209528E+11 | 0.00 | 0.379174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165414E+10 | 0.00 | 0.518379E+10 | 0.00 | 0.104738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160078E+10 | 0.00 | 0.124742E+11 | 0.00 | 0.248312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165414E+10 | 0.00 | 0.198636E+11 | 0.00 | 0.412103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165414E+10 | 0.00 | 0.252892E+11 | 0.00 | 0.502934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160078E+10 | 0.00 | 0.569911E+10 | 0.00 | 0.118392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165414E+10 | 0.00 | 0.959572E+10 | 0.00 | 0.184233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160078E+10 | 0.00 | 0.128248E+11 | 0.00 | 0.242200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165414E+10 | 0.00 | 0.170919E+11 | 0.00 | 0.321920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194762E+11 | 0.00 | 0.148563E+12 | 0.00 | 0.289383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149406E+10 | 0.00 | 0.288540E+09 | 0.00 | 66099338.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165414E+10 | 0.00 | 0.252892E+11 | 0.00 | 0.502934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 91025085.80 | 0.00 | 0.00 | 0.650101E+11 | 0.00 | 0.37 |
February | 0.00 | 0.00 | 0.00 | 84732353.50 | 0.00 | 0.00 | 0.538407E+11 | 0.00 | 0.46 |
March | 0.00 | 0.00 | 0.00 | 0.101320E+09 | 0.00 | 0.00 | 0.618653E+11 | 0.00 | 0.54 |
April | 0.00 | 0.00 | 0.00 | 96405981.91 | 0.00 | 0.00 | 0.556071E+11 | 0.00 | 0.72 |
May | 0.00 | 38405351.73 | 0.00 | 0.105169E+09 | 0.00 | 0.00 | 0.502380E+11 | 0.00 | 0.79 |
June | 0.00 | 0.438954E+09 | 0.00 | 0.115821E+09 | 0.00 | 0.00 | 0.405026E+11 | 0.00 | 1.04 |
July | 0.00 | 0.361718E+09 | 0.00 | 0.148451E+09 | 0.00 | 0.00 | 0.226664E+11 | 0.00 | 0.72 |
August | 0.00 | 0.289695E+09 | 0.00 | 0.142755E+09 | 0.00 | 0.00 | 0.313852E+11 | 0.00 | 0.92 |
September | 0.00 | 0.684302E+09 | 0.00 | 0.131368E+09 | 0.00 | 0.00 | 0.489263E+11 | 0.00 | 1.02 |
October | 0.00 | 0.00 | 0.00 | 0.127269E+09 | 0.00 | 0.00 | 0.665352E+11 | 0.00 | 0.96 |
November | 0.00 | 0.00 | 0.00 | 0.111510E+09 | 0.00 | 0.00 | 0.668733E+11 | 0.00 | 0.72 |
December | 0.00 | 0.00 | 0.00 | 0.100662E+09 | 0.00 | 0.00 | 0.630624E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.00 | 0.181307E+10 | 0.00 | 0.135649E+10 | 0.00 | 0.00 | 0.626513E+12 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 84732353.50 | 0.00 | 0.00 | 0.226664E+11 | 0.00 | 0.37 |
Maximum of Months | 0.00 | 0.684302E+09 | 0.00 | 0.148451E+09 | 0.00 | 0.00 | 0.668733E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136250E+11 | 0.00 | 0.00 | 55193427.85 | 0.00 | 0.00 | 0.508244E+11 | 0.00 | 0.36 |
February | 0.484309E+10 | 0.00 | 0.00 | 66684350.14 | 0.00 | 0.00 | 0.490174E+11 | 0.00 | 0.42 |
March | 0.234479E+10 | 0.00 | 0.00 | 96739515.96 | 0.00 | 0.00 | 0.600922E+11 | 0.00 | 0.51 |
April | 0.371732E+10 | 0.00 | 0.00 | 99480725.66 | 0.00 | 0.00 | 0.563919E+11 | 0.00 | 0.74 |
May | 0.212026E+10 | 16106113.24 | 0.00 | 91876810.08 | 7608304.36 | 0.00 | 0.484667E+11 | 0.00 | 0.75 |
June | 0.359889E+10 | 0.282778E+09 | 0.00 | 0.104535E+09 | 11256556.33 | 0.00 | 0.380962E+11 | 0.00 | 1.00 |
July | 0.717881E+10 | 0.557144E+09 | 0.00 | 0.119171E+09 | 72871214.04 | 0.00 | 0.240016E+11 | 0.00 | 0.99 |
August | 0.878178E+10 | 0.339276E+09 | 0.00 | 0.125260E+09 | 48707890.80 | 0.00 | 0.337462E+11 | 0.00 | 1.12 |
September | 0.212220E+10 | 0.490993E+09 | 0.00 | 95106832.80 | 35969526.37 | 0.00 | 0.406331E+11 | 0.00 | 0.85 |
October | 0.184263E+10 | 0.00 | 0.00 | 0.102830E+09 | 0.00 | 0.00 | 0.513574E+11 | 0.00 | 0.71 |
November | 0.209491E+10 | 0.00 | 0.00 | 93211230.15 | 0.00 | 0.00 | 0.539001E+11 | 0.00 | 0.55 |
December | 0.254798E+10 | 0.00 | 0.00 | 87584953.81 | 0.00 | 0.00 | 0.613171E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.548177E+11 | 0.168630E+10 | 0.00 | 0.113767E+10 | 0.176413E+09 | 0.00 | 0.567844E+12 | 0.00 | 0.70 |
Minimum of Months | 0.184263E+10 | 0.00 | 0.00 | 55193427.85 | 0.00 | 0.00 | 0.240016E+11 | 0.00 | 0.36 |
Maximum of Months | 0.136250E+11 | 0.557144E+09 | 0.00 | 0.125260E+09 | 72871214.04 | 0.00 | 0.613171E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396926E+12 | 0.00 | 0.00 | 63128055.46 | 0.00 | 0.593378E+10 | 0.112326E+12 | 0.00 | 0.30 |
February | 0.266778E+12 | 0.00 | 0.00 | 0.154198E+09 | 0.00 | 0.100901E+10 | 0.143750E+12 | 0.00 | 0.32 |
March | 0.155573E+12 | 0.00 | 0.00 | 0.373528E+09 | 0.00 | 59792313.33 | 0.299833E+12 | 0.00 | 0.36 |
April | 0.551952E+11 | 0.00 | 0.00 | 0.504068E+09 | 0.00 | 0.00 | 0.337627E+12 | 0.00 | 0.47 |
May | 0.350620E+11 | 0.163108E+09 | 0.00 | 0.624540E+09 | 84727747.30 | 0.00 | 0.352861E+12 | 0.00 | 0.59 |
June | 0.213211E+11 | 0.277374E+10 | 0.00 | 0.755109E+09 | 72502092.13 | 0.00 | 0.291150E+12 | 0.00 | 0.76 |
July | 0.231281E+11 | 0.589709E+10 | 0.00 | 0.731187E+09 | 0.270131E+09 | 0.00 | 0.160191E+12 | 0.00 | 0.64 |
August | 0.190852E+11 | 0.394812E+10 | 0.00 | 0.829766E+09 | 0.497069E+09 | 0.00 | 0.239448E+12 | 0.00 | 0.74 |
September | 0.172631E+11 | 0.416407E+10 | 0.00 | 0.677993E+09 | 0.368203E+09 | 0.00 | 0.304007E+12 | 0.00 | 0.63 |
October | 0.365061E+11 | 0.00 | 0.00 | 0.577908E+09 | 0.00 | 0.00 | 0.316774E+12 | 0.00 | 0.46 |
November | 0.142071E+12 | 0.00 | 0.00 | 0.335507E+09 | 0.00 | 14679127.12 | 0.234209E+12 | 0.00 | 0.35 |
December | 0.300459E+12 | 0.00 | 0.00 | 0.154935E+09 | 0.00 | 62981952.38 | 0.163400E+12 | 0.00 | 0.31 |
Annual Sum or Average | 0.146937E+13 | 0.169461E+11 | 0.00 | 0.578187E+10 | 0.129263E+10 | 0.708024E+10 | 0.295558E+13 | 0.00 | 0.49 |
Minimum of Months | 0.172631E+11 | 0.00 | 0.00 | 63128055.46 | 0.00 | 0.00 | 0.112326E+12 | 0.00 | 0.30 |
Maximum of Months | 0.396926E+12 | 0.589709E+10 | 0.00 | 0.829766E+09 | 0.497069E+09 | 0.593378E+10 | 0.352861E+12 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.304489E+11 | 0.00 | 0.00 | 7154.29 | 0.00 | 0.124026E+11 | 60592197.93 | 0.00 | 0.27 |
February | 0.297461E+11 | 0.00 | 0.00 | 1230267.24 | 0.00 | 0.349180E+10 | 0.140293E+10 | 0.00 | 0.29 |
March | 0.266556E+11 | 0.00 | 0.00 | 7712679.39 | 0.00 | 0.244265E+10 | 0.756127E+10 | 0.00 | 0.31 |
April | 0.147686E+11 | 0.00 | 0.00 | 22954489.84 | 0.00 | 14486661.07 | 0.171449E+11 | 0.00 | 0.41 |
May | 0.950945E+10 | 9578650.69 | 0.00 | 39719509.26 | 5090298.55 | 0.249640E+09 | 0.245579E+11 | 0.00 | 0.55 |
June | 0.384230E+10 | 0.196407E+09 | 0.00 | 67607649.22 | 5491675.19 | 0.00 | 0.252184E+11 | 0.00 | 0.76 |
July | 0.269301E+10 | 0.374888E+09 | 0.00 | 72601918.71 | 20244088.13 | 0.00 | 0.143086E+11 | 0.00 | 0.65 |
August | 0.253053E+10 | 0.248872E+09 | 0.00 | 77630687.46 | 39400208.43 | 0.00 | 0.201881E+11 | 0.00 | 0.71 |
September | 0.663985E+10 | 0.379741E+09 | 0.00 | 44604618.82 | 28136284.08 | 0.00 | 0.201041E+11 | 0.00 | 0.57 |
October | 0.145790E+11 | 0.00 | 0.00 | 21085903.70 | 0.00 | 0.166802E+09 | 0.140134E+11 | 0.00 | 0.41 |
November | 0.232469E+11 | 0.00 | 0.00 | 5413651.39 | 0.00 | 0.192345E+10 | 0.468812E+10 | 0.00 | 0.31 |
December | 0.294156E+11 | 0.00 | 0.00 | 711654.52 | 0.00 | 0.720056E+10 | 0.998129E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.194076E+12 | 0.120949E+10 | 0.00 | 0.361280E+09 | 98362554.38 | 0.278920E+11 | 0.150246E+12 | 0.00 | 0.46 |
Minimum of Months | 0.253053E+10 | 0.00 | 0.00 | 7154.29 | 0.00 | 0.00 | 60592197.93 | 0.00 | 0.27 |
Maximum of Months | 0.304489E+11 | 0.379741E+09 | 0.00 | 77630687.46 | 39400208.43 | 0.124026E+11 | 0.252184E+11 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285341E+10 | 0.00 | 0.00 | 95543.38 | 0.00 | 0.325487E+10 | 52271746.98 | 0.00 | 0.26 |
February | 0.296881E+10 | 0.00 | 0.00 | 627213.18 | 0.00 | 0.104119E+10 | 0.467004E+09 | 0.00 | 0.28 |
March | 0.283051E+10 | 0.00 | 0.00 | 2733920.61 | 0.00 | 0.158362E+09 | 0.191051E+10 | 0.00 | 0.32 |
April | 0.167990E+10 | 0.00 | 0.00 | 5774792.34 | 0.00 | 0.00 | 0.372052E+10 | 0.00 | 0.59 |
May | 0.107369E+10 | 5041129.29 | 0.00 | 8146478.16 | 955725.80 | 0.00 | 0.429644E+10 | 0.00 | 0.74 |
June | 0.592709E+09 | 56439850.01 | 0.00 | 14689502.44 | 1271352.70 | 0.00 | 0.503462E+10 | 0.00 | 1.19 |
July | 0.972287E+09 | 0.103843E+09 | 0.00 | 18360048.22 | 7947554.15 | 0.00 | 0.327178E+10 | 0.00 | 1.17 |
August | 0.122143E+10 | 73322561.79 | 0.00 | 16069237.89 | 6118497.07 | 0.00 | 0.390220E+10 | 0.00 | 1.21 |
September | 0.951126E+09 | 88876531.23 | 0.00 | 7908285.41 | 4518352.94 | 0.00 | 0.318925E+10 | 0.00 | 0.75 |
October | 0.166939E+10 | 0.00 | 0.00 | 4647147.05 | 0.00 | 0.00 | 0.263866E+10 | 0.00 | 0.50 |
November | 0.276585E+10 | 0.00 | 0.00 | 1738900.83 | 0.00 | 38859082.20 | 0.120966E+10 | 0.00 | 0.32 |
December | 0.347408E+10 | 0.00 | 0.00 | 427648.51 | 0.00 | 0.812134E+09 | 0.333588E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.230532E+11 | 0.327523E+09 | 0.00 | 81218718.01 | 20811482.67 | 0.530542E+10 | 0.300265E+11 | 0.00 | 0.63 |
Minimum of Months | 0.592709E+09 | 0.00 | 0.00 | 95543.38 | 0.00 | 0.00 | 52271746.98 | 0.00 | 0.24 |
Maximum of Months | 0.347408E+10 | 0.103843E+09 | 0.00 | 18360048.22 | 7947554.15 | 0.325487E+10 | 0.503462E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203016E+10 | 0.00 | 0.00 | 484376.29 | 0.00 | 0.180404E+10 | 0.272570E+09 | 0.00 | 0.27 |
February | 0.164104E+10 | 0.00 | 0.00 | 2295514.33 | 0.00 | 0.663571E+09 | 0.112580E+10 | 0.00 | 0.36 |
March | 0.158258E+10 | 0.00 | 0.00 | 5328075.45 | 0.00 | 0.134125E+09 | 0.259240E+10 | 0.00 | 0.45 |
April | 0.993826E+09 | 0.00 | 0.00 | 8574559.91 | 0.00 | 147983.40 | 0.471364E+10 | 0.00 | 0.94 |
May | 0.586972E+09 | 3495218.53 | 0.00 | 10844405.40 | 612824.62 | 0.00 | 0.563823E+10 | 0.00 | 1.24 |
June | 0.343475E+09 | 46131352.52 | 0.00 | 20404870.54 | 897159.30 | 0.00 | 0.581623E+10 | 0.00 | 1.99 |
July | 0.582334E+09 | 0.102089E+09 | 0.00 | 24592186.79 | 4928233.97 | 0.00 | 0.420265E+10 | 0.00 | 2.04 |
August | 0.765503E+09 | 66049185.97 | 0.00 | 17286393.19 | 3691634.72 | 0.00 | 0.465621E+10 | 0.00 | 1.96 |
September | 0.499063E+09 | 69124349.18 | 0.00 | 10764861.47 | 2034007.13 | 0.00 | 0.396657E+10 | 0.00 | 1.24 |
October | 0.937657E+09 | 0.00 | 0.00 | 6817696.86 | 0.00 | 0.00 | 0.310275E+10 | 0.00 | 0.73 |
November | 0.159266E+10 | 0.00 | 0.00 | 2484618.87 | 0.00 | 79245145.93 | 0.123830E+10 | 0.00 | 0.35 |
December | 0.191191E+10 | 0.00 | 0.00 | 644512.99 | 0.00 | 0.763265E+09 | 0.376165E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.134672E+11 | 0.286889E+09 | 0.00 | 0.110522E+09 | 12163859.74 | 0.344440E+10 | 0.377015E+11 | 0.00 | 0.99 |
Minimum of Months | 0.343475E+09 | 0.00 | 0.00 | 484376.29 | 0.00 | 0.00 | 0.272570E+09 | 0.00 | 0.24 |
Maximum of Months | 0.203016E+10 | 0.102089E+09 | 0.00 | 24592186.79 | 4928233.97 | 0.180404E+10 | 0.581623E+10 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269839E+10 | 0.00 | 0.00 | 6575915.70 | 0.00 | 0.251760E+10 | 0.417818E+10 | 0.00 | 0.42 |
February | 0.221512E+10 | 0.00 | 0.00 | 13884382.22 | 0.00 | 0.690306E+09 | 0.586070E+10 | 0.00 | 0.66 |
March | 0.218489E+10 | 0.00 | 0.00 | 14656888.07 | 0.00 | 0.198552E+09 | 0.783039E+10 | 0.00 | 0.76 |
April | 0.150962E+10 | 0.00 | 0.00 | 14954008.12 | 0.00 | 2798066.30 | 0.791282E+10 | 0.00 | 1.12 |
May | 0.111441E+10 | 7195795.96 | 0.00 | 13917758.91 | 952823.74 | 16845643.80 | 0.684569E+10 | 0.00 | 1.15 |
June | 0.702700E+09 | 82745880.49 | 0.00 | 20064655.88 | 1320694.10 | 0.00 | 0.574136E+10 | 0.00 | 1.47 |
July | 0.957266E+09 | 0.158507E+09 | 0.00 | 24152646.85 | 6654234.52 | 0.00 | 0.376333E+10 | 0.00 | 1.45 |
August | 0.115113E+10 | 0.144419E+09 | 0.00 | 29232859.83 | 2656535.58 | 0.00 | 0.561549E+10 | 0.00 | 1.79 |
September | 0.749949E+09 | 0.210513E+09 | 0.00 | 22166870.39 | 876559.80 | 0.00 | 0.702230E+10 | 0.00 | 1.56 |
October | 0.111086E+10 | 0.00 | 0.00 | 22562335.73 | 0.00 | 3765780.85 | 0.863475E+10 | 0.00 | 1.25 |
November | 0.191279E+10 | 0.00 | 0.00 | 13831774.45 | 0.00 | 0.144611E+09 | 0.592295E+10 | 0.00 | 0.67 |
December | 0.246073E+10 | 0.00 | 0.00 | 7507678.59 | 0.00 | 0.940807E+09 | 0.410946E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.187678E+11 | 0.603380E+09 | 0.00 | 0.203508E+09 | 12460847.73 | 0.451528E+10 | 0.734374E+11 | 0.00 | 1.06 |
Minimum of Months | 0.702700E+09 | 0.00 | 0.00 | 6575915.70 | 0.00 | 0.00 | 0.376333E+10 | 0.00 | 0.42 |
Maximum of Months | 0.269839E+10 | 0.210513E+09 | 0.00 | 29232859.83 | 6654234.52 | 0.251760E+10 | 0.863475E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230112E+10 | 0.00 | 0.00 | 934786.26 | 0.00 | 0.118563E+10 | 0.707615E+09 | 0.00 | 0.29 |
February | 0.166382E+10 | 0.00 | 0.00 | 5198972.38 | 0.00 | 80681476.84 | 0.272855E+10 | 0.00 | 0.50 |
March | 0.639215E+09 | 0.00 | 0.00 | 10635180.01 | 0.00 | 1116353.64 | 0.663340E+10 | 0.00 | 0.82 |
April | 0.164831E+09 | 0.00 | 0.00 | 19283975.00 | 0.00 | 0.00 | 0.964405E+10 | 0.00 | 1.72 |
May | 0.268674E+09 | 5778985.66 | 0.00 | 17116411.02 | 486167.86 | 0.00 | 0.728844E+10 | 0.00 | 1.64 |
June | 0.160895E+09 | 81725980.89 | 0.00 | 24730415.64 | 103438.21 | 0.00 | 0.660969E+10 | 0.00 | 2.31 |
July | 0.191779E+09 | 0.165757E+09 | 0.00 | 29715764.34 | 2486160.84 | 0.00 | 0.467584E+10 | 0.00 | 2.19 |
August | 0.224829E+09 | 0.118086E+09 | 0.00 | 29203211.47 | 285225.15 | 0.00 | 0.663320E+10 | 0.00 | 2.57 |
September | 0.234207E+09 | 0.153795E+09 | 0.00 | 13216279.38 | 205341.56 | 0.00 | 0.481032E+10 | 0.00 | 1.51 |
October | 0.278699E+09 | 0.00 | 0.00 | 12255317.57 | 0.00 | 0.00 | 0.580604E+10 | 0.00 | 1.16 |
November | 0.530133E+09 | 0.00 | 0.00 | 8290708.48 | 0.00 | 0.00 | 0.483621E+10 | 0.00 | 0.72 |
December | 0.130535E+10 | 0.00 | 0.00 | 5411499.99 | 0.00 | 1496054.01 | 0.358864E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.796354E+10 | 0.525142E+09 | 0.00 | 0.175993E+09 | 3566333.62 | 0.126892E+10 | 0.639620E+11 | 0.00 | 1.33 |
Minimum of Months | 0.160895E+09 | 0.00 | 0.00 | 934786.26 | 0.00 | 0.00 | 0.707615E+09 | 0.00 | 0.29 |
Maximum of Months | 0.230112E+10 | 0.165757E+09 | 0.00 | 29715764.34 | 2486160.84 | 0.118563E+10 | 0.964405E+10 | 0.00 | 2.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.869576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742523E+11 | 0.00 | 0.00 | 0.36 |
February | 0.158193E+11 | 0.00 | 0.00 | 40353.73 | 0.00 | 0.372814E+11 | 40198815.17 | 0.00 | 0.32 |
March | 0.319757E+11 | 0.00 | 0.00 | 1337060.49 | 0.00 | 0.149948E+11 | 0.106055E+10 | 0.00 | 0.30 |
April | 0.252686E+11 | 0.00 | 0.00 | 16481102.00 | 0.00 | 0.163895E+10 | 0.101454E+11 | 0.00 | 0.37 |
May | 0.173407E+11 | 60589115.13 | 0.00 | 46390000.98 | 10673706.78 | 0.116478E+10 | 0.228934E+11 | 0.00 | 0.57 |
June | 0.659691E+10 | 0.604692E+09 | 0.00 | 0.102617E+09 | 9133561.29 | 0.00 | 0.352566E+11 | 0.00 | 0.93 |
July | 0.413256E+10 | 0.133981E+10 | 0.00 | 0.113615E+09 | 34030201.84 | 0.00 | 0.211331E+11 | 0.00 | 0.81 |
August | 0.656921E+10 | 0.101424E+10 | 0.00 | 95059146.15 | 62619051.54 | 0.00 | 0.229084E+11 | 0.00 | 0.80 |
September | 0.152966E+11 | 0.794711E+09 | 0.00 | 43522321.79 | 46384892.45 | 0.183420E+09 | 0.154280E+11 | 0.00 | 0.55 |
October | 0.242714E+11 | 0.00 | 0.00 | 12606371.06 | 0.00 | 0.206668E+10 | 0.648173E+10 | 0.00 | 0.34 |
November | 0.239192E+11 | 0.00 | 0.00 | 366253.16 | 0.00 | 0.163108E+11 | 0.306918E+09 | 0.00 | 0.29 |
December | 0.136391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467341E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.193525E+12 | 0.381404E+10 | 0.00 | 0.432034E+09 | 0.162841E+09 | 0.194627E+12 | 0.135654E+12 | 0.00 | 0.49 |
Minimum of Months | 0.413256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.319757E+11 | 0.133981E+10 | 0.00 | 0.113615E+09 | 62619051.54 | 0.742523E+11 | 0.352566E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378723E+11 | 0.00 | 0.00 | 0.30 |
February | 0.999290E+10 | 0.00 | 0.00 | 8186710.49 | 0.00 | 0.169357E+11 | 0.433566E+10 | 0.00 | 0.30 |
March | 0.140977E+11 | 0.00 | 0.00 | 29778699.28 | 0.00 | 0.689978E+10 | 0.145788E+11 | 0.00 | 0.36 |
April | 0.100500E+11 | 0.00 | 0.00 | 65777051.42 | 0.00 | 0.606207E+09 | 0.320578E+11 | 0.00 | 0.70 |
May | 0.631920E+10 | 46795970.56 | 0.00 | 91644786.62 | 6886927.16 | 0.678880E+09 | 0.464598E+11 | 0.00 | 1.10 |
June | 0.247202E+10 | 0.562916E+09 | 0.00 | 0.194596E+09 | 3452320.39 | 0.00 | 0.534495E+11 | 0.00 | 1.88 |
July | 0.187604E+10 | 0.127341E+10 | 0.00 | 0.246932E+09 | 13501162.97 | 0.00 | 0.382954E+11 | 0.00 | 1.84 |
August | 0.262949E+10 | 0.105836E+10 | 0.00 | 0.156825E+09 | 40403287.80 | 0.00 | 0.419360E+11 | 0.00 | 1.74 |
September | 0.601095E+10 | 0.719999E+09 | 0.00 | 89500906.20 | 21404084.88 | 43640369.83 | 0.310146E+11 | 0.00 | 1.05 |
October | 0.103904E+11 | 0.00 | 0.00 | 42407720.78 | 0.00 | 0.912217E+09 | 0.178011E+11 | 0.00 | 0.51 |
November | 0.118822E+11 | 0.00 | 0.00 | 7964055.37 | 0.00 | 0.771857E+10 | 0.407273E+10 | 0.00 | 0.26 |
December | 0.976299E+10 | 0.00 | 0.00 | 65262.12 | 0.00 | 0.231668E+11 | 83173778.36 | 0.00 | 0.26 |
Annual Sum or Average | 0.927152E+11 | 0.366149E+10 | 0.00 | 0.933679E+09 | 85647783.19 | 0.948341E+11 | 0.284085E+12 | 0.00 | 0.86 |
Minimum of Months | 0.187604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.140977E+11 | 0.127341E+10 | 0.00 | 0.246932E+09 | 40403287.80 | 0.378723E+11 | 0.534495E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206566E+11 | 0.00 | 0.00 | 53974816.32 | 0.00 | 0.434640E+11 | 0.427001E+11 | 0.00 | 0.49 |
February | 0.186085E+11 | 0.00 | 0.00 | 0.136677E+09 | 0.00 | 0.170370E+11 | 0.606965E+11 | 0.00 | 0.70 |
March | 0.244511E+11 | 0.00 | 0.00 | 0.136274E+09 | 0.00 | 0.780692E+10 | 0.638962E+11 | 0.00 | 0.68 |
April | 0.181285E+11 | 0.00 | 0.00 | 0.130134E+09 | 0.00 | 0.118816E+10 | 0.576674E+11 | 0.00 | 0.91 |
May | 0.129947E+11 | 99924114.01 | 0.00 | 0.126590E+09 | 10663401.91 | 0.113130E+10 | 0.583045E+11 | 0.00 | 1.06 |
June | 0.677703E+10 | 0.985383E+09 | 0.00 | 0.166279E+09 | 5072629.04 | 0.00 | 0.477991E+11 | 0.00 | 1.29 |
July | 0.441500E+10 | 0.213214E+10 | 0.00 | 0.195685E+09 | 7579662.51 | 0.00 | 0.288918E+11 | 0.00 | 1.16 |
August | 0.514882E+10 | 0.236606E+10 | 0.00 | 0.243838E+09 | 32260919.41 | 0.00 | 0.453803E+11 | 0.00 | 1.53 |
September | 0.903484E+10 | 0.245051E+10 | 0.00 | 0.213098E+09 | 6885700.59 | 3982781.96 | 0.626874E+11 | 0.00 | 1.48 |
October | 0.134552E+11 | 0.00 | 0.00 | 0.239654E+09 | 0.00 | 0.721430E+09 | 0.716505E+11 | 0.00 | 1.08 |
November | 0.191482E+11 | 0.00 | 0.00 | 0.128732E+09 | 0.00 | 0.711236E+10 | 0.549054E+11 | 0.00 | 0.63 |
December | 0.229797E+11 | 0.00 | 0.00 | 51269921.54 | 0.00 | 0.236008E+11 | 0.404412E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.175798E+12 | 0.803401E+10 | 0.00 | 0.182221E+10 | 62462313.46 | 0.102066E+12 | 0.635020E+12 | 0.00 | 0.96 |
Minimum of Months | 0.441500E+10 | 0.00 | 0.00 | 51269921.54 | 0.00 | 0.00 | 0.288918E+11 | 0.00 | 0.49 |
Maximum of Months | 0.244511E+11 | 0.245051E+10 | 0.00 | 0.243838E+09 | 32260919.41 | 0.434640E+11 | 0.716505E+11 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101421E+11 | 0.00 | 0.00 | 841281.16 | 0.00 | 0.396540E+11 | 0.851180E+09 | 0.00 | 0.34 |
February | 0.145377E+11 | 0.00 | 0.00 | 12554479.88 | 0.00 | 0.158459E+11 | 0.571122E+10 | 0.00 | 0.36 |
March | 0.190302E+11 | 0.00 | 0.00 | 25206087.51 | 0.00 | 0.631005E+10 | 0.148180E+11 | 0.00 | 0.41 |
April | 0.115702E+11 | 0.00 | 0.00 | 69677012.01 | 0.00 | 0.422450E+09 | 0.333653E+11 | 0.00 | 0.85 |
May | 0.730338E+10 | 62144273.06 | 0.00 | 0.123175E+09 | 6828863.07 | 0.500549E+09 | 0.469186E+11 | 0.00 | 1.24 |
June | 0.303831E+10 | 0.836859E+09 | 0.00 | 0.152818E+09 | 1136013.04 | 0.00 | 0.407160E+11 | 0.00 | 1.64 |
July | 0.145430E+10 | 0.207895E+10 | 0.00 | 0.182148E+09 | 1583810.54 | 0.00 | 0.244359E+11 | 0.00 | 1.41 |
August | 0.221481E+10 | 0.146188E+10 | 0.00 | 0.143341E+09 | 8665362.97 | 0.00 | 0.292504E+11 | 0.00 | 1.48 |
September | 0.657149E+10 | 0.143914E+10 | 0.00 | 81531485.68 | 1818497.74 | 2550581.21 | 0.262686E+11 | 0.00 | 1.04 |
October | 0.120636E+11 | 0.00 | 0.00 | 46776026.00 | 0.00 | 0.449085E+09 | 0.192469E+11 | 0.00 | 0.59 |
November | 0.166648E+11 | 0.00 | 0.00 | 13935498.25 | 0.00 | 0.568930E+10 | 0.744859E+10 | 0.00 | 0.34 |
December | 0.144611E+11 | 0.00 | 0.00 | 2227717.80 | 0.00 | 0.216403E+11 | 0.201876E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.119052E+12 | 0.587898E+10 | 0.00 | 0.854231E+09 | 20032547.37 | 0.905142E+11 | 0.251049E+12 | 0.00 | 0.84 |
Minimum of Months | 0.145430E+10 | 0.00 | 0.00 | 841281.16 | 0.00 | 0.00 | 0.851180E+09 | 0.00 | 0.31 |
Maximum of Months | 0.190302E+11 | 0.207895E+10 | 0.00 | 0.182148E+09 | 8665362.97 | 0.396540E+11 | 0.469186E+11 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905269E+10 | 0.00 | 0.00 | 0.42 |
February | 0.871395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488710E+10 | 0.00 | 0.00 | 0.36 |
March | 0.217092E+10 | 0.00 | 0.00 | 11728.31 | 0.00 | 0.286666E+10 | 28860504.62 | 0.00 | 0.33 |
April | 0.236908E+10 | 0.00 | 0.00 | 955491.38 | 0.00 | 0.786499E+09 | 0.598940E+09 | 0.00 | 0.38 |
May | 0.175201E+10 | 3124546.20 | 0.00 | 3864079.43 | 657384.90 | 0.485232E+09 | 0.194344E+10 | 0.00 | 0.57 |
June | 0.795141E+09 | 39996288.20 | 0.00 | 10228560.30 | 709220.55 | 6820221.69 | 0.325254E+10 | 0.00 | 0.94 |
July | 0.453028E+09 | 82040298.00 | 0.00 | 12443324.54 | 1513282.47 | 0.00 | 0.198778E+10 | 0.00 | 0.83 |
August | 0.765357E+09 | 63385727.95 | 0.00 | 9767269.34 | 5088326.69 | 4060219.98 | 0.203191E+10 | 0.00 | 0.78 |
September | 0.158114E+10 | 69532421.26 | 0.00 | 3638258.16 | 3633650.96 | 0.194138E+09 | 0.120432E+10 | 0.00 | 0.54 |
October | 0.214914E+10 | 0.00 | 0.00 | 530150.19 | 0.00 | 0.925889E+09 | 0.313230E+09 | 0.00 | 0.37 |
November | 0.127954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289695E+10 | 0.00 | 0.00 | 0.33 |
December | 0.467095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621945E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.148369E+11 | 0.258079E+09 | 0.00 | 41438861.65 | 11601865.57 | 0.283255E+11 | 0.113610E+11 | 0.00 | 0.52 |
Minimum of Months | 0.183040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.236908E+10 | 82040298.00 | 0.00 | 12443324.54 | 5088326.69 | 0.905269E+10 | 0.325254E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.410630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502914E+10 | 0.00 | 0.00 | 0.39 |
February | 0.911778E+09 | 0.00 | 0.00 | 334575.46 | 0.00 | 0.243987E+10 | 0.194459E+09 | 0.00 | 0.36 |
March | 0.142697E+10 | 0.00 | 0.00 | 1831279.47 | 0.00 | 0.123581E+10 | 0.108295E+10 | 0.00 | 0.40 |
April | 0.110487E+10 | 0.00 | 0.00 | 5220904.63 | 0.00 | 0.316657E+09 | 0.287416E+10 | 0.00 | 0.72 |
May | 0.686806E+09 | 2356442.29 | 0.00 | 8302086.75 | 413465.05 | 0.212998E+09 | 0.454578E+10 | 0.00 | 1.14 |
June | 0.290460E+09 | 37762248.44 | 0.00 | 20288275.04 | 425064.13 | 2813494.91 | 0.534439E+10 | 0.00 | 1.97 |
July | 0.177935E+09 | 79929027.99 | 0.00 | 25223087.20 | 718725.45 | 0.00 | 0.389163E+10 | 0.00 | 1.95 |
August | 0.283982E+09 | 70628649.08 | 0.00 | 16235052.29 | 2523094.37 | 1773193.42 | 0.411352E+10 | 0.00 | 1.80 |
September | 0.658947E+09 | 64895246.84 | 0.00 | 7934735.86 | 1549627.12 | 78138764.33 | 0.281723E+10 | 0.00 | 1.05 |
October | 0.104854E+10 | 0.00 | 0.00 | 2665254.85 | 0.00 | 0.343772E+09 | 0.136465E+10 | 0.00 | 0.52 |
November | 0.110491E+10 | 0.00 | 0.00 | 170252.22 | 0.00 | 0.139376E+10 | 0.116502E+09 | 0.00 | 0.32 |
December | 0.546053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354718E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.865187E+10 | 0.255572E+09 | 0.00 | 88205503.76 | 5629976.12 | 0.146019E+11 | 0.263453E+11 | 0.00 | 0.92 |
Minimum of Months | 0.177935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.142697E+10 | 79929027.99 | 0.00 | 25223087.20 | 2523094.37 | 0.502914E+10 | 0.534439E+10 | 0.00 | 1.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116144E+10 | 0.00 | 0.00 | 3122982.25 | 0.00 | 0.549399E+10 | 0.265577E+10 | 0.00 | 0.45 |
February | 0.136908E+10 | 0.00 | 0.00 | 9390783.94 | 0.00 | 0.240986E+10 | 0.481757E+10 | 0.00 | 0.69 |
March | 0.193624E+10 | 0.00 | 0.00 | 9972435.10 | 0.00 | 0.156656E+10 | 0.591617E+10 | 0.00 | 0.69 |
April | 0.158069E+10 | 0.00 | 0.00 | 10407745.23 | 0.00 | 0.589633E+09 | 0.523978E+10 | 0.00 | 0.87 |
May | 0.120864E+10 | 4689535.66 | 0.00 | 11411088.12 | 641167.40 | 0.422932E+09 | 0.577709E+10 | 0.00 | 1.06 |
June | 0.743290E+09 | 62062968.65 | 0.00 | 18190024.87 | 659154.30 | 15479440.33 | 0.479325E+10 | 0.00 | 1.34 |
July | 0.452080E+09 | 0.125057E+09 | 0.00 | 21996972.55 | 615104.05 | 0.00 | 0.304231E+10 | 0.00 | 1.22 |
August | 0.549083E+09 | 0.148007E+09 | 0.00 | 25708101.78 | 1710120.75 | 11572716.38 | 0.456917E+10 | 0.00 | 1.55 |
September | 0.994674E+09 | 0.206900E+09 | 0.00 | 19315460.94 | 571780.39 | 96272934.74 | 0.611986E+10 | 0.00 | 1.49 |
October | 0.124030E+10 | 0.00 | 0.00 | 17940235.71 | 0.00 | 0.376713E+09 | 0.722459E+10 | 0.00 | 1.18 |
November | 0.136693E+10 | 0.00 | 0.00 | 7929604.95 | 0.00 | 0.143251E+10 | 0.446599E+10 | 0.00 | 0.61 |
December | 0.147978E+10 | 0.00 | 0.00 | 2914265.01 | 0.00 | 0.353806E+10 | 0.256373E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.140822E+11 | 0.546717E+09 | 0.00 | 0.158300E+09 | 4197326.89 | 0.159536E+11 | 0.571853E+11 | 0.00 | 0.97 |
Minimum of Months | 0.452080E+09 | 0.00 | 0.00 | 2914265.01 | 0.00 | 0.00 | 0.256373E+10 | 0.00 | 0.45 |
Maximum of Months | 0.193624E+10 | 0.206900E+09 | 0.00 | 25708101.78 | 1710120.75 | 0.549399E+10 | 0.722459E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.484515E+09 | 0.00 | 0.00 | 33257.56 | 0.00 | 0.485111E+10 | 33751709.03 | 0.00 | 0.38 |
February | 0.947660E+09 | 0.00 | 0.00 | 854649.98 | 0.00 | 0.213122E+10 | 0.499458E+09 | 0.00 | 0.38 |
March | 0.149926E+10 | 0.00 | 0.00 | 1905540.55 | 0.00 | 0.112156E+10 | 0.134428E+10 | 0.00 | 0.43 |
April | 0.115957E+10 | 0.00 | 0.00 | 5779488.52 | 0.00 | 0.263135E+09 | 0.290803E+10 | 0.00 | 0.81 |
May | 0.758457E+09 | 3135027.14 | 0.00 | 11857678.83 | 385153.25 | 0.164904E+09 | 0.469032E+10 | 0.00 | 1.27 |
June | 0.344305E+09 | 52182740.23 | 0.00 | 18264920.31 | 39596.16 | 8704491.26 | 0.409330E+10 | 0.00 | 1.72 |
July | 0.169574E+09 | 0.119118E+09 | 0.00 | 19732819.21 | 95628.02 | 0.00 | 0.245836E+10 | 0.00 | 1.45 |
August | 0.301623E+09 | 85880135.68 | 0.00 | 15028546.32 | 662684.90 | 3016256.65 | 0.277661E+10 | 0.00 | 1.48 |
September | 0.750396E+09 | 0.124346E+09 | 0.00 | 7377201.76 | 169019.63 | 45706391.87 | 0.243861E+10 | 0.00 | 1.04 |
October | 0.116616E+10 | 0.00 | 0.00 | 3350831.79 | 0.00 | 0.296521E+09 | 0.167727E+10 | 0.00 | 0.62 |
November | 0.107579E+10 | 0.00 | 0.00 | 801054.46 | 0.00 | 0.116151E+10 | 0.565309E+09 | 0.00 | 0.35 |
December | 0.759891E+09 | 0.00 | 0.00 | 88172.70 | 0.00 | 0.293049E+10 | 97568228.84 | 0.00 | 0.33 |
Annual Sum or Average | 0.941719E+10 | 0.384661E+09 | 0.00 | 85074161.98 | 1352081.95 | 0.129779E+11 | 0.235829E+11 | 0.00 | 0.86 |
Minimum of Months | 0.169574E+09 | 0.00 | 0.00 | 33257.56 | 0.00 | 0.00 | 33751709.03 | 0.00 | 0.33 |
Maximum of Months | 0.149926E+10 | 0.124346E+09 | 0.00 | 19732819.21 | 662684.90 | 0.485111E+10 | 0.469032E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5501680.74 | 0.00 | 0.00 | 3029679.90 | 0.00 | 0.00 | 0.844665E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8251388.94 | 0.00 | 0.00 | 0.644924E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 15211963.00 | 0.00 | 0.00 | 0.660428E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18826372.58 | 0.00 | 0.00 | 0.460741E+09 | 0.00 | 0.29 |
May | 0.00 | 151850.46 | 0.00 | 4349035.27 | 0.00 | 0.00 | 0.407658E+09 | 0.00 | 0.29 |
June | 0.00 | 14118618.78 | 0.00 | 8375085.59 | 0.00 | 0.00 | 0.197051E+09 | 0.00 | 0.30 |
July | 0.00 | 23524273.72 | 0.00 | 10733224.45 | 0.00 | 0.00 | 74376563.44 | 0.00 | 0.28 |
August | 0.00 | 6619701.91 | 0.00 | 18590858.42 | 0.00 | 0.00 | 0.140450E+09 | 0.00 | 0.31 |
September | 0.00 | 11478224.84 | 0.00 | 4021404.78 | 0.00 | 0.00 | 0.256303E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 9547536.64 | 0.00 | 0.00 | 0.438119E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13619050.77 | 0.00 | 0.00 | 0.542250E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19352752.36 | 0.00 | 0.00 | 0.714178E+09 | 0.00 | 0.28 |
Annual Sum or Average | 5501680.74 | 55892669.69 | 0.00 | 0.133908E+09 | 0.00 | 0.00 | 0.538114E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3029679.90 | 0.00 | 0.00 | 74376563.44 | 0.00 | 0.28 |
Maximum of Months | 5501680.74 | 23524273.72 | 0.00 | 19352752.36 | 0.00 | 0.00 | 0.844665E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289006E+10 | 0.00 | 0.00 | 9510225.12 | 0.00 | 0.00 | 0.555696E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 63009162.63 | 0.00 | 0.00 | 0.646893E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.132315E+09 | 0.00 | 0.00 | 0.662362E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.173717E+09 | 0.00 | 0.00 | 0.461959E+10 | 0.00 | 0.29 |
May | 0.00 | 1453627.13 | 0.00 | 36442179.05 | 0.00 | 0.00 | 0.408690E+10 | 0.00 | 0.29 |
June | 0.00 | 0.139742E+09 | 0.00 | 78073469.22 | 0.00 | 0.00 | 0.197820E+10 | 0.00 | 0.30 |
July | 0.00 | 0.233894E+09 | 0.00 | 0.101420E+09 | 0.00 | 0.00 | 0.750447E+09 | 0.00 | 0.28 |
August | 0.00 | 67862121.87 | 0.00 | 0.175991E+09 | 0.00 | 0.00 | 0.141234E+10 | 0.00 | 0.31 |
September | 0.00 | 0.112123E+09 | 0.00 | 34202836.57 | 0.00 | 0.00 | 0.258137E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 83272829.04 | 0.00 | 0.00 | 0.439241E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.117444E+09 | 0.00 | 0.00 | 0.544036E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.164986E+09 | 0.00 | 0.00 | 0.716830E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.289006E+10 | 0.555075E+09 | 0.00 | 0.117038E+10 | 0.00 | 0.00 | 0.510794E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9510225.12 | 0.00 | 0.00 | 0.750447E+09 | 0.00 | 0.28 |
Maximum of Months | 0.289006E+10 | 0.233894E+09 | 0.00 | 0.175991E+09 | 0.00 | 0.00 | 0.716830E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.652873E+09 | 0.00 | 0.00 | 253951.20 | 0.00 | 0.00 | 0.171246E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5007695.79 | 0.00 | 0.00 | 0.648128E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 11862892.86 | 0.00 | 0.00 | 0.663752E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16498183.64 | 0.00 | 0.00 | 0.462995E+09 | 0.00 | 0.29 |
May | 26410359.01 | 147758.60 | 0.00 | 3111686.99 | 0.00 | 0.00 | 0.382259E+09 | 0.00 | 0.29 |
June | 0.00 | 14013571.40 | 0.00 | 7661123.37 | 0.00 | 0.00 | 0.198138E+09 | 0.00 | 0.30 |
July | 0.00 | 23398744.89 | 0.00 | 10104681.42 | 0.00 | 0.00 | 75184838.01 | 0.00 | 0.28 |
August | 0.00 | 6769762.68 | 0.00 | 17499517.12 | 0.00 | 0.00 | 0.141468E+09 | 0.00 | 0.31 |
September | 5327890.22 | 11216976.28 | 0.00 | 2930802.88 | 0.00 | 0.00 | 0.254376E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 7236862.24 | 0.00 | 0.00 | 0.440595E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10330777.52 | 0.00 | 0.00 | 0.545510E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14891333.40 | 0.00 | 0.00 | 0.718534E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.684611E+09 | 55546813.86 | 0.00 | 0.107390E+09 | 0.00 | 0.00 | 0.470219E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 253951.20 | 0.00 | 0.00 | 75184838.01 | 0.00 | 0.28 |
Maximum of Months | 0.652873E+09 | 23398744.89 | 0.00 | 17499517.12 | 0.00 | 0.00 | 0.718534E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.790561E+09 | 0.00 | 0.00 | 0.516985E+12 | 0.00 | 7.73 |
February | 0.00 | 0.00 | 0.00 | 0.122116E+10 | 0.00 | 0.00 | 0.766925E+12 | 0.00 | 15.89 |
March | 0.00 | 0.00 | 0.00 | 0.178289E+10 | 0.00 | 0.00 | 0.110295E+13 | 0.00 | 23.30 |
April | 0.00 | 0.00 | 0.00 | 0.225709E+10 | 0.00 | 0.00 | 0.126042E+13 | 0.00 | 37.98 |
May | 0.00 | 0.00 | 0.00 | 0.550281E+09 | 0.00 | 0.00 | 0.510951E+12 | 0.00 | 18.31 |
June | 0.00 | 0.228417E+10 | 0.00 | 0.126099E+10 | 0.00 | 0.00 | 0.603922E+12 | 0.00 | 35.40 |
July | 0.00 | 0.246569E+10 | 0.00 | 0.200682E+10 | 0.00 | 0.00 | 0.552118E+12 | 0.00 | 41.26 |
August | 0.00 | 0.455964E+09 | 0.00 | 0.257371E+10 | 0.00 | 0.00 | 0.768498E+12 | 0.00 | 45.40 |
September | 0.00 | 0.852096E+09 | 0.00 | 0.541132E+09 | 0.00 | 0.00 | 0.423558E+12 | 0.00 | 22.50 |
October | 0.00 | 0.00 | 0.00 | 0.110921E+10 | 0.00 | 0.00 | 0.835825E+12 | 0.00 | 25.38 |
November | 0.00 | 0.00 | 0.00 | 0.174166E+10 | 0.00 | 0.00 | 0.106971E+13 | 0.00 | 26.60 |
December | 0.00 | 0.00 | 0.00 | 0.281834E+10 | 0.00 | 0.00 | 0.134796E+13 | 0.00 | 26.28 |
Annual Sum or Average | 0.00 | 0.605792E+10 | 0.00 | 0.186539E+11 | 0.00 | 0.00 | 0.975982E+13 | 0.00 | 27.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.541132E+09 | 0.00 | 0.00 | 0.423558E+12 | 0.00 | 7.73 |
Maximum of Months | 0.00 | 0.246569E+10 | 0.00 | 0.281834E+10 | 0.00 | 0.00 | 0.134796E+13 | 0.00 | 45.40 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:24
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.251692E+12 | 0.215477E+11 | 0.00 | 0.221549E+13 | 0.252383E+12 |
February | 0.344868E+12 | 0.170445E+11 | 0.00 | 0.232452E+13 | 0.288836E+12 |
March | 0.602723E+12 | 0.160404E+11 | 0.00 | 0.296934E+13 | 0.396768E+12 |
April | 0.650436E+12 | 0.115259E+11 | 0.00 | 0.320730E+13 | 0.544829E+12 |
May | 0.862968E+12 | 0.113337E+11 | 0.00 | 0.242431E+13 | 0.431319E+12 |
June | 0.944545E+12 | 0.582583E+10 | 0.00 | 0.221234E+13 | 0.121464E+13 |
July | 0.936862E+12 | 0.390304E+10 | 0.00 | 0.186636E+13 | 0.227139E+13 |
August | 0.776721E+12 | 0.422788E+10 | 0.00 | 0.223277E+13 | 0.229268E+13 |
September | 0.581216E+12 | 0.765130E+10 | 0.00 | 0.208612E+13 | 0.779235E+12 |
October | 0.375402E+12 | 0.112399E+11 | 0.00 | 0.283538E+13 | 0.451862E+12 |
November | 0.199252E+12 | 0.155117E+11 | 0.00 | 0.287844E+13 | 0.365239E+12 |
December | 0.159465E+12 | 0.194775E+11 | 0.00 | 0.307507E+13 | 0.433308E+12 |
Annual Sum or Average | 0.668615E+13 | 0.145329E+12 | 0.00 | 0.303274E+14 | 0.972249E+13 |
Minimum of Months | 0.159465E+12 | 0.390304E+10 | 0.00 | 0.186636E+13 | 0.252383E+12 |
Maximum of Months | 0.944545E+12 | 0.215477E+11 | 0.00 | 0.320730E+13 | 0.229268E+13 |