Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2024-07-03 12:21:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31735.17 | 685.12 | 685.12 |
Net Site Energy | 31735.17 | 685.12 | 685.12 |
Total Source Energy | 100505.27 | 2169.79 | 2169.79 |
Net Source Energy | 100505.27 | 2169.79 | 2169.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5872.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2459.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2801.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 830.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1733.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18764.58 |
Humidification | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 307.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31735.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21079.15 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 5872.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2459.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2801.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 830.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1733.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18764.58 |
Humidification | General | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 307.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5872.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2459.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2801.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 830.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1733.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18764.58 |
Humidification | Unassigned | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 307.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 252.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 685.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 252.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 685.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31735.166 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31735.166 | 100.00 |
Total On-Site and Utility Electric Sources | 31735.166 | 100.00 |
Total Electricity End Uses | 31735.166 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 21079.15 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 21079.15 | 100.00 |
Total Water End Uses | 21079.15 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 3416.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:30 | - | - | - | - | - | - | - | - | - | - | - | 12-JUN-15:30 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 559357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240144.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49669.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 84051.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 20243.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2177920.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 559357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 240144.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 49669.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 84051.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 20243.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 144.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18599.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7789.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1106.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8871.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2629.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5489.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 292.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 974.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 100505.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 3.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 401.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 118.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 21.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2169.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 3.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 401.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 118.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 21.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2169.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.35 | 0.396141 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.95 | 0.319903 | 0.272000 | 1.62 | 0.853074 | 0.500000 | 0.001191 |
CORE_MID VAV BOX COMPONENT | 56.80 | 0.334876 | 0.285000 | 16.19 | 0.893002 | 0.500000 | 0.001138 |
CORE_TOP VAV BOX COMPONENT | 5.80 | 0.327734 | 0.279000 | 1.62 | 0.873957 | 0.500000 | 0.001163 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.29 | 0.184699 | 0.157000 | 0.203005 | 0.492532 | 0.500000 | 0.002063 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.03 | 0.149977 | 0.127000 | 0.130326 | 0.399939 | 0.500000 | 0.002540 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.31 | 0.182983 | 0.156000 | 0.203608 | 0.487954 | 0.500000 | 0.002082 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.34 | 0.114519 | 0.097000 | 0.130361 | 0.305383 | 0.500000 | 0.003327 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.73 | 0.187570 | 0.159000 | 2.02 | 0.500186 | 0.500000 | 0.002031 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.69 | 0.383897 | 0.500000 | 0.002647 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.72 | 0.187701 | 0.160000 | 2.04 | 0.500535 | 0.500000 | 0.002030 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.74 | 0.131132 | 0.111000 | 1.30 | 0.349685 | 0.500000 | 0.002905 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.43 | 0.167425 | 0.142000 | 0.202554 | 0.446467 | 0.500000 | 0.002276 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.11 | 0.138678 | 0.118000 | 0.130956 | 0.369808 | 0.500000 | 0.002747 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.42 | 0.167904 | 0.143000 | 0.203402 | 0.447744 | 0.500000 | 0.002269 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.27 | 0.120997 | 0.103000 | 0.131014 | 0.322658 | 0.500000 | 0.003149 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 52650.95 |
CORE_MID VAV BOX REHEAT COIL | 527007.26 |
CORE_TOP VAV BOX REHEAT COIL | 67249.46 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6890.83 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5026.31 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9164.88 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4244.08 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 160168.38 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 105850.12 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 160169.40 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 96902.87 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19892.10 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13054.68 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19892.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12396.72 |
VAV_BOT WITH REHEAT HEATING COIL | 20474.16 |
VAV_MID WITH REHEAT HEATING COIL | 91305.69 |
VAV_TOP WITH REHEAT HEATING COIL | 8549.59 |
CAV_BAS HEATING COIL | 243321.82 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 13450.69 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 621.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6213.66 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 621.37 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.481893 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.60 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.465016 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.46 | 2.28 | 10.91 | 2.28 | 9.98 | 9.98 | 0.300000 | 0.229018 | 9.98 |
VAV_MID WITH REHEAT | 52.34 | 22.85 | 104.68 | 26.85 | 95.19 | 95.19 | 0.300000 | 0.282012 | 95.19 |
VAV_TOP WITH REHEAT | 5.52 | 2.29 | 11.03 | 4.07 | 10.89 | 10.89 | 0.300000 | 0.373752 | 10.89 |
CAV_BAS | 0.000000 | 0.000000 | 5.35 | 1.20 | 5.35 | 5.35 | 1.00 | 0.224480 | 5.35 |
AIRLOOP DATACENTER BASEMENT | 25.15 | 25.15 | 25.15 | 25.15 | 25.15 | 25.15 | 1.00 | 0.999990 | 25.15 |
AIRLOOP DATACENTER BOT | 0.481893 | 0.481893 | 0.481893 | 0.481893 | 0.481893 | 0.481893 | 1.00 | 1.00 | 0.481893 |
AIRLOOP DATACENTER MID | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 1.00 | 1.00 | 4.60 |
AIRLOOP DATACENTER TOP | 0.465016 | 0.465016 | 0.465016 | 0.465016 | 0.465016 | 0.465016 | 1.00 | 1.00 | 0.465016 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.98 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 95.19 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.89 | |
CAV_BAS_OA_CONTROLLER | 5.35 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.15 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.481893 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.60 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.465016 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.67 | 6.67 | 10.99 | 0.007700 | 0.007000 | 219632.23 | 0.006281 | 9.98 |
VAV_MID WITH REHEAT COOLING COIL | 27.96 | 6.67 | 10.99 | 0.007756 | 0.007000 | 2145362.07 | 0.061357 | 95.19 |
VAV_TOP WITH REHEAT COOLING COIL | 27.35 | 6.67 | 11.00 | 0.007654 | 0.007000 | 233936.93 | 0.006691 | 10.89 |
CAV_BAS COOLING COIL | 27.86 | 6.67 | 10.98 | 0.007915 | 0.007000 | 122464.51 | 0.003502 | 5.35 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.98 |
VAV_MID WITH REHEAT FAN | 95.19 |
VAV_TOP WITH REHEAT FAN | 10.89 |
CAV_BAS FAN | 5.35 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006281 | 0.000076 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.061357 | 0.000008 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006691 | 0.000071 |
CAV_BAS_COOLC_CONTROLLER | 0.003502 | 0.000136 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.15 | 517011.50 | 322278.09 | 0.012662 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.481893 | 9909.42 | 6163.64 | 0.000243 |
AIRLOOP DATACENTER MID COOLING COIL | 4.60 | 92222.95 | 58101.44 | 0.002259 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.465016 | 9569.38 | 5949.94 | 0.000234 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.15 | 25.15 | 25.15 | 25.15 | 517011.50 | 517011.50 | 13450.69 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.481893 | 0.481893 | 0.481893 | 0.481893 | 9909.42 | 9909.42 | 621.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.60 | 4.60 | 4.60 | 4.60 | 92222.95 | 92222.95 | 6213.66 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.465016 | 0.465016 | 0.465016 | 0.465016 | 9569.38 | 9569.38 | 621.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.15 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.481893 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.60 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.465016 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.15 | 517011.50 | 0.012662 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.481893 | 9909.42 | 0.000243 |
AIRLOOP DATACENTER MID HEATING COIL | 4.60 | 92222.95 | 0.002259 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.465016 | 9569.38 | 0.000234 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000055 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.077832 | 12581.70 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.077832 | 9.34 |
COOLSYS1_SUPPLY | 0.077832 | 9.34 |
SINGLE WATER PLANT LOOP | 0.015397 | 1.85 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.077832 | 0.077832 | 326698.17 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.038916 | 4355.37 |
COOLSYS1 CHILLER2 PUMP | 0.038916 | 4355.37 |
PLANT CIRC PUMP | 0.015397 | 3888.16 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.077832 | 0.039280 | 1373415.18 | 1373414.49 | 0.069158 |
COOLSYS1 CHILLER2 | 0.077832 | 0.039280 | 1373415.18 | 1373414.49 | 0.069158 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015397 | 152882.25 | 77393.71 | 76441.12 | 7004.20 | 46436.23 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 634230.46 | 621574.96 | 0.015397 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.138317 | 16.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.138317 | 33905.07 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 54.37 | 1644021.05 | 10.87 | 205502.63 |
TOWERWATERSYS COOLTOWER 2 | 54.37 | 1644021.05 | 10.87 | 205502.63 |
Design Water Flow Rate [m3/s] Equipment # 27 | |
WSHPPLANT OPERATION SCHEME | 0.071222 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4306E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4319E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6212E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6222E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7737E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7744E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6123E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6128E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4593E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5392E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6446E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7116E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7921E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8461E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6259E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6600E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5698E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4573E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3962E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6486E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7735E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4606E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8968E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0048E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4651E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5672E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6508E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7417E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7978E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8678E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6263E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6610E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4305E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4320E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6211E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6223E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7737E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7746E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6122E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6127E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5778E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7177E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4166E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5609E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2396E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3127E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7571E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7807E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0105E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8837E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7658E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7088E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8360E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5461E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0167E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.1262E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5454E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6026E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3763E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4182E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2176E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2352E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7572E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7811E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5795E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5808E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3590E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3601E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2057E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2065E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6123E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6128E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6088E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6812E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3831E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4407E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2248E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2661E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6263E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6611E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4232E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2556E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8773E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5976E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6679E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.4991E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8968E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0045E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6068E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6786E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3805E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4355E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2203E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2526E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6260E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6601E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5794E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5806E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3589E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3599E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2056E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2062E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6123E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6128E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0666E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1262E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7967E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8398E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7693E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7851E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7572E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7811E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1848E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5773E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7761E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3423E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0214E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2396E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0167E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1262E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0924E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2024E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8293E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9373E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7898E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8541E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7570E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7806E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9629E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0849E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.6005E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3564E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.5176E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7626E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.5538E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7566E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7829E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7353E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5105E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5228E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5624E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3125E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6430E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7769E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0510E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0150E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4296E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6083E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1934E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2154E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5538E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7563E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8473E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3098E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3878E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0123E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6469E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8983E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6430E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7769E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9738E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0958E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.6136E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3687E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.5313E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7720E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.5614E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7605E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7875E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7397E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5157E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5270E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5701E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3174E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6507E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7808E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0515E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0172E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4303E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6102E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1969E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2175E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5614E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7602E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8499E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3131E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3906E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0152E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6529E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9021E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6507E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7808E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72199.53974 | 72199.53974 | 5.34638 | 5.34638 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 80280.99367 | 80280.99367 | 5.94569 | 5.94569 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 767070.72162 | 767070.72162 | 56.79848 | 56.79848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 225191.21001 | 225191.21001 | 9.72795 | 10.77825 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77649.90666 | 77649.90666 | 5.80362 | 5.80362 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 47477.52584 | 47477.52584 | 2.06564 | 2.06564 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 17300.27990 | 17300.27990 | 1.29302 | 1.29302 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4872.35916 | 4872.35916 | 0.21166 | 0.21166 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13730.17621 | 13730.17621 | 1.02619 | 1.02619 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.15255E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3550.79718 | 3550.79718 | 0.15439 | 0.15439 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17462.97068 | 17462.97068 | 1.30518 | 1.30518 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6465.45011 | 6465.45011 | 0.28151 | 0.28151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17981.52858 | 17981.52858 | 1.34393 | 1.34393 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2060.21933 | 2060.21933 | 8.90256E-002 | 8.90256E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 170354.31075 | 170354.31075 | 12.73237 | 12.73237 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 41.28867 | 9.15671E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 112646.10477 | 112646.10477 | 4.91974 | 4.91974 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 143038.30713 | 143038.30713 | 10.69072 | 10.69072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 39.04150 | 9.15295E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 74436.69131 | 74436.69131 | 3.25129 | 3.25129 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 170238.94227 | 170238.94227 | 12.72375 | 12.72375 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 112646.83219 | 112646.83219 | 4.91977 | 4.91977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 157032.96453 | 157032.96453 | 11.73667 | 11.73667 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 68167.43836 | 68167.43836 | 2.97647 | 2.97647 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19085.11711 | 19085.11711 | 1.42643 | 1.42643 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13979.25926 | 13979.25926 | 0.61101 | 0.61101 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14848.72428 | 14848.72428 | 1.10980 | 1.10980 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 39.28400 | 9.15337E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9173.68919 | 9173.68919 | 0.40099 | 0.40099 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19031.07015 | 19031.07015 | 1.42239 | 1.42239 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13979.39491 | 13979.39491 | 0.61101 | 0.61101 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17018.63413 | 17018.63413 | 1.27198 | 1.27198 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8712.73320 | 8712.73320 | 0.38078 | 0.38078 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8175.46786 | 8175.46786 | 0.48189 | 0.48189 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78052.46228 | 78052.46228 | 4.60071 | 4.60071 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7888.21923 | 7888.21923 | 0.46502 | 0.46502 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 40.77133 | 9.15585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370999.53422 | 426649.46436 | 21.87020 | 25.15074 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 33.17300 | 9.14325E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 6.30000 | 6.07234E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 174707.97 | 9.97531 | 9.97531 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 13910.46 | 1.81441 | 1.81441 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1649406.83 | 95.19274 | 95.19274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 153209.13 | 26.84552 | 26.84552 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 186331.03 | 10.88803 | 10.88803 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 15425.43 | 4.06942 | 4.06942 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
7 | CAV_BAS | Cooling | Sensible | 87081.70 | 5.34638 | 5.34638 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 47704.73 | 1.20016 | 1.20016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 426662.83 | 25.15099 | 25.15099 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13450.69 | 0.33839 | 0.33839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8176.78 | 0.48189 | 0.48189 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78045.18 | 4.60071 | 4.60071 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.66 | 0.15632 | 0.15632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8044.84 | 0.46502 | 0.46502 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.34638 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.39614 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.94569 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31990 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27200 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61723 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85307 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19099E-003 |
12 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 52650.94837 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.79848 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33488 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18757 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13774E-003 |
20 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 527007.25752 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.80362 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32773 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27900 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61921 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87396 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16253E-003 |
28 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 67249.45862 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29302 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18470 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49253 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06281E-003 |
36 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6890.82614 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02619 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14998 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13033 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39994 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54039E-003 |
44 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5026.30567 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30518 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18298 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15600 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20361 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48795 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08216E-003 |
52 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9164.87816 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34393 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11452 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.70000E-002 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13036 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30538 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32697E-003 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4244.07921 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.73237 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18757 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15900 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02445 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50019 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03125E-003 |
68 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 160168.37833 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.69072 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38390 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64654E-003 |
73 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 105850.11733 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.72375 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18770 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03580 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50054 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02983E-003 |
81 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 160169.40233 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.73667 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13113 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30277 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34968 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90547E-003 |
89 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 96902.86539 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42643 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16743 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20255 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44647 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27565E-003 |
97 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19892.09795 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10980 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13868 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11800 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13096 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36981 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74737E-003 |
105 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13054.67889 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42239 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16790 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14300 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20340 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44774 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.26915E-003 |
113 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19892.29014 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27198 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12100 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13101 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32266 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14885E-003 |
121 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12396.71523 |
122 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48189 |
123 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.60071 |
124 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46502 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.15074 |
126 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.45701 |
127 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28453 |
128 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.91402 |
129 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28453 |
130 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.97531 |
131 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.97531 |
132 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22902 |
134 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.34100 |
135 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85485 |
136 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.68200 |
137 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.84552 |
138 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 95.19274 |
139 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 95.19274 |
140 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28201 |
142 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.51711 |
143 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28714 |
144 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.03422 |
145 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.06942 |
146 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.88803 |
147 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.88803 |
148 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
149 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.37375 |
150 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
151 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
152 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.34638 |
153 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
154 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.34638 |
155 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.34638 |
156 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.22448 |
158 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.15074 |
159 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.15074 |
160 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.15074 |
161 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.15074 |
162 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.15099 |
163 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.15099 |
164 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
166 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48189 |
167 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48189 |
168 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48189 |
169 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48189 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48189 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48189 |
172 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
173 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
174 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.60071 |
175 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.60071 |
176 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60071 |
177 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.60071 |
178 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60071 |
179 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.60071 |
180 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
181 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
182 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46502 |
183 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46502 |
184 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46502 |
185 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46502 |
186 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46502 |
187 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46502 |
188 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
189 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
190 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.97531 |
191 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 95.19274 |
192 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.88803 |
193 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.34638 |
194 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.15099 |
195 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48189 |
196 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.60071 |
197 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46502 |
198 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.97531 |
199 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.66761 |
200 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
201 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99359 |
202 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.69977E-003 |
203 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
204 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 219632.23300 |
205 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.28145E-003 |
206 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.97531 |
207 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 20474.16264 |
208 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.97531 |
209 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.28145E-003 |
210 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.58090E-005 |
211 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 95.19274 |
212 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.96195 |
213 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
214 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99378 |
215 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.75568E-003 |
216 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
217 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2145362.07100 |
218 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.13571E-002 |
219 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 95.19274 |
220 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 91305.68514 |
221 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 95.19274 |
222 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.13571E-002 |
223 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.76097E-006 |
224 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.88803 |
225 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.34622 |
226 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
227 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00304 |
228 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.65432E-003 |
229 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
230 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 233936.92661 |
231 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.69057E-003 |
232 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.88803 |
233 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 8549.58944 |
234 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.88803 |
235 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.69057E-003 |
236 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.11734E-005 |
237 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.34638 |
238 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
239 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.85920 |
240 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
241 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98265 |
242 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.91543E-003 |
243 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
244 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 122464.50726 |
245 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.50247E-003 |
246 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.34638 |
247 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 243321.82247 |
248 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.34638 |
249 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.50247E-003 |
250 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.35958E-004 |
251 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.15099 |
252 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
253 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.15099 |
254 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 517011.50241 |
255 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 322278.09123 |
256 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26616E-002 |
257 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.15099 |
258 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.15099 |
259 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.15099 |
260 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.15099 |
261 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 517011.50241 |
262 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 517011.50241 |
263 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13450.69260 |
264 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
265 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.15099 |
266 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.15099 |
267 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 517011.50241 |
268 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26616E-002 |
269 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13450.69260 |
270 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 5.49206E-005 |
271 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
272 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
273 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
274 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48189 |
275 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
276 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48189 |
277 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9909.42465 |
278 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6163.63841 |
279 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42681E-004 |
280 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48189 |
281 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48189 |
282 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48189 |
283 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48189 |
284 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9909.42465 |
285 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9909.42465 |
286 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
287 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
288 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48189 |
289 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48189 |
290 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9909.42465 |
291 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42681E-004 |
292 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
293 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60071 |
294 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
295 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60071 |
296 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92222.95192 |
297 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58101.44406 |
298 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25853E-003 |
299 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.60071 |
300 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.60071 |
301 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.60071 |
302 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.60071 |
303 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92222.95192 |
304 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92222.95192 |
305 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.66275 |
306 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
307 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.60071 |
308 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60071 |
309 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92222.95192 |
310 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25853E-003 |
311 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6213.66275 |
312 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46502 |
313 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
314 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46502 |
315 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9569.37784 |
316 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5949.94117 |
317 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34353E-004 |
318 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46502 |
319 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46502 |
320 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46502 |
321 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46502 |
322 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9569.37784 |
323 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9569.37784 |
324 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
325 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
326 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46502 |
327 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46502 |
328 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9569.37784 |
329 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34353E-004 |
330 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
331 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.78316E-002 |
332 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 12581.70069 |
333 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.78316E-002 |
334 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.33979 |
335 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.78316E-002 |
336 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.78316E-002 |
337 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 326698.16781 |
338 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
339 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.78316E-002 |
340 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.33979 |
341 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.89158E-002 |
342 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4355.36785 |
343 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.89158E-002 |
344 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4355.36785 |
345 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.78316E-002 |
346 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.92795E-002 |
347 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1373415.18401 |
348 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1373414.48500 |
349 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.91583E-002 |
350 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.78316E-002 |
351 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.92795E-002 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1373415.18401 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1373414.48500 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.91583E-002 |
355 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.53971E-002 |
356 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.84766 |
357 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.53971E-002 |
358 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3888.16090 |
359 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.53971E-002 |
360 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 152882.24929 |
361 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 77393.70855 |
362 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 76441.12464 |
363 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
364 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46436.22513 |
365 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 634230.46391 |
366 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 621574.96000 |
367 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.53971E-002 |
368 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
369 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
370 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
371 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
372 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
373 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13832 |
374 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.59799 |
375 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13832 |
376 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33905.07425 |
377 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 54.37153 |
378 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1644021.05389 |
379 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.87431 |
380 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 205502.63174 |
381 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 54.37153 |
382 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1644021.05389 |
383 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.87431 |
384 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 205502.63174 |
385 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 7.12225E-002 |
386 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 7.12225E-002 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 280122.87 | 187486.12 | 92636.75 | 0.67 | 71756.31 | 727.79 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2696348.29 | 1798836.79 | 897511.50 | 0.67 | 672368.47 | 6819.53 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 302914.63 | 203457.80 | 99456.83 | 0.67 | 79972.47 | 811.13 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 152665.88 | 101547.17 | 51118.71 | 0.67 | 37878.89 | 384.19 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2332181546 | 0.1619372792 | Pass | Pass | 1.0255780980 | 3.0972979278 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.8347458407E-003 | 5.8069218259E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.4910604199E-003 | 6.2945541554E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.8471887526E-002 | 5.5480566455E-002 | Pass | Pass | 0.1344115512 | 0.3383518491 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7228071987E-002 | 1.8010510827E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.6092885233E-002 | 3.8577612736E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.1300932353E-002 | 4.5499756812E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.2720894962E-002 | 3.6733928074E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0343369011E-002 | 1.9016437028E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.0595669539E-002 | 3.8176853187E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.0578172389E-002 | 4.9323065491E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.6938285862E-002 | 3.8167504263E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.7640350112E-002 | 0.1363951175 | Pass | Pass | 0.3314883843 | 1.0358600955 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9685233513E-002 | 8.2364199468E-002 | Pass | Pass | 0.2621624466 | 0.8159939268 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.5472636603E-002 | 6.1184972187E-002 | Pass | Pass | 0.1890615696 | 0.5622492536 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.6001346376E-002 | 5.0040051528E-002 | Pass | Pass | 0.5849088099 | 3.1497923833 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3895660651E-003 | 4.7612729361E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7144182244E-003 | 5.0614107138E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9653728374E-002 | 5.7027401846E-002 | Pass | Pass | 0.1368926204 | 0.3360544596 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.9440226208E-005 | 6.5276836095E-005 | Pass | Pass | 4.3758981026E-003 | 2.5661092688E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.0774659196E-003 | 1.0178558719E-002 | Pass | Pass | 0.1380137489 | 0.4148960119 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0066697046E-002 | 1.9712231167E-002 | Pass | Pass | 1.1631984682E-002 | 8.1844031903E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.4357805706E-004 | 1.7159001899E-004 | Pass | Pass | 7.4890913479E-005 | 1.0561465211E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4340.52 | -19.8 | 0.00 | -4192.0 | 41095.15 | 41223.92 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.230 | 0.253 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.36 | 0.0000 | Y | 10.62 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.23 | 0.0000 | Y | 6.81 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.06 | 0.0000 | Y | 10.51 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.22 | 0.0000 | Y | 6.81 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.31 | 0.0000 | Y | 106.05 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 68.06 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.04 | 0.0000 | Y | 104.98 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 68.00 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.31 | 0.0000 | Y | 10.60 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 6.81 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 10.50 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.17 | 0.0000 | Y | 6.80 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 774.90 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.75 | 41.75 | 104.02 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.75 | 62.75 | 11.66 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.75 | 46.80 | 233.63 | |
Exterior Lighting Total | 40855.88 | 349.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2713013.60 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1373414.49 | 5.91 | 1365483.70 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1373414.49 | 5.91 | 1365483.70 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 637136.77 | |||||
CENTRAL BOILER | Boiler:HotWater | 621574.96 | 1.00 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1644021.05 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1644021.05 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 219632.23 | 280122.87 | 187486.12 | 92636.75 | 0.67 | - | 71756.31 | 727.79 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2145362.07 | 2696348.29 | 1798836.79 | 897511.50 | 0.67 | - | 672368.47 | 6819.53 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 233936.93 | 302914.63 | 203457.80 | 99456.83 | 0.67 | - | 79972.47 | 811.13 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 122464.51 | 152665.88 | 101547.17 | 51118.71 | 0.67 | - | 37878.89 | 384.19 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 517011.50 | 322278.09 | 194733.41 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9909.42 | 6163.64 | 3745.79 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92222.95 | 58101.44 | 34121.51 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9569.38 | 5949.94 | 3619.44 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 52650.95 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 527007.26 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 67249.46 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6890.83 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5026.31 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9164.88 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4244.08 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 160168.38 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 105850.12 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 160169.40 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 96902.87 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19892.10 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13054.68 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19892.29 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12396.72 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 20474.16 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 91305.69 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 8549.59 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 243321.82 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 517011.50 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9909.42 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92222.95 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9569.38 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 13450.69 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6213.66 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.98 | 21556.12 | 2160.95 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 95.19 | 205706.45 | 2160.95 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.89 | 23403.44 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.35 | 11627.79 | 2174.89 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.15 | 41480.20 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 539.77 | 1120.11 | 1.00 | 1.62 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.60 | 5153.29 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 520.87 | 1120.11 | 1.00 | 1.64 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.077832 | 12581.70 | 161652.92 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.038916 | 4355.37 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.038916 | 4355.37 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015397 | 3888.16 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.138317 | 33905.07 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72199.54 | 72199.54 | 25.98 | 5.346 | 5.346 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 34.82 | 0.00915 | 1.200 | 0.00 |
CORE_BOTTOM | 80280.99 | 80280.99 | 32.16 | 5.946 | 5.946 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 34.82 | 0.00915 | 1.078 | 0.00 |
CORE_MID | 767070.72 | 767070.72 | 307.31 | 56.798 | 56.798 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 34.82 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 77649.91 | 77649.91 | 31.11 | 5.804 | 5.804 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00739 | 41.90 | 0.00916 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17300.28 | 17300.28 | 55.20 | 1.293 | 1.293 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 24.00 | 24.00 | 0.00723 | 41.52 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13730.18 | 13730.18 | 67.98 | 1.026 | 1.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00719 | 38.80 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17462.97 | 17462.97 | 55.72 | 1.305 | 1.305 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00723 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17981.53 | 17981.53 | 89.03 | 1.344 | 1.344 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00714 | 41.16 | 0.00916 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 170354.31 | 170354.31 | 543.55 | 12.732 | 12.732 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 24.00 | 24.00 | 0.00725 | 41.29 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 143038.31 | 143038.31 | 708.20 | 10.691 | 10.691 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 24.00 | 24.00 | 0.00719 | 39.04 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 170238.94 | 170238.94 | 543.17 | 12.724 | 12.724 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 24.00 | 24.00 | 0.00725 | 42.00 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 157032.96 | 157032.96 | 777.49 | 11.737 | 11.737 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00718 | 41.03 | 0.00916 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19085.12 | 19085.12 | 60.89 | 1.426 | 1.426 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 24.00 | 24.00 | 0.00723 | 41.52 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14848.72 | 14848.72 | 73.52 | 1.110 | 1.110 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 24.00 | 24.00 | 0.00719 | 39.28 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19031.07 | 19031.07 | 60.72 | 1.422 | 1.422 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00723 | 41.90 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17018.63 | 17018.63 | 84.26 | 1.272 | 1.272 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00717 | 41.03 | 0.00916 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8175.47 | 8175.47 | 225.82 | 0.482 | 0.482 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78052.46 | 78052.46 | 2155.98 | 4.601 | 4.601 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7888.22 | 7888.22 | 217.89 | 0.465 | 0.465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 27.00 | 27.00 | 0.00709 | 40.77 | 0.00916 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370999.53 | 426649.46 | 544.42 | 21.870 | 25.151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.17 | 0.00914 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.76 | 0.00607 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.17 | 0.00607 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 225191.21 | 225191.21 | 90.22 | 9.728 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 47477.53 | 47477.53 | 19.02 | 2.066 | 2.066 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4872.36 | 4872.36 | 15.55 | 0.212 | 0.212 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3550.80 | 3550.80 | 17.58 | 0.154 | 0.154 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6465.45 | 6465.45 | 20.63 | 0.282 | 0.282 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2060.22 | 2060.22 | 10.20 | 0.089 | 0.089 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 112646.10 | 112646.10 | 359.42 | 4.920 | 4.920 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 74436.69 | 74436.69 | 368.54 | 3.251 | 3.251 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 112646.83 | 112646.83 | 359.41 | 4.920 | 4.920 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 68167.44 | 68167.44 | 337.50 | 2.976 | 2.976 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13979.26 | 13979.26 | 44.60 | 0.611 | 0.611 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9173.69 | 9173.69 | 45.42 | 0.401 | 0.401 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13979.39 | 13979.39 | 44.60 | 0.611 | 0.611 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8712.73 | 8712.73 | 43.14 | 0.381 | 0.381 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 26.91 | 0.00700 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.62 | 0.00663 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.78 | 0.00614 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.98 | 9.98 | 1.81 | 1.81 | 9.9753 | 2.2845 | 9.9753 | 0.2290 | 0.3000 |
VAV_MID WITH REHEAT | 95.19 | 95.19 | 26.85 | 26.85 | 95.1927 | 26.8455 | 95.1927 | 0.2820 | 0.3000 |
VAV_TOP WITH REHEAT | 10.89 | 10.89 | 4.07 | 4.07 | 10.8880 | 4.0694 | 10.8880 | 0.3738 | 0.3000 |
CAV_BAS | 5.35 | 5.35 | 1.20 | 1.20 | 5.3464 | 1.2002 | 5.3464 | 0.2245 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.15 | 25.15 | 0.34 | 0.34 | 25.1510 | 25.1507 | 25.1510 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4819 | 0.4819 | 0.4819 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.60 | 4.60 | 0.16 | 0.16 | 4.6007 | 4.6007 | 4.6007 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4650 | 0.4650 | 0.4650 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 52650.948 | 52650.948 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 52650.95 | 35089.98 | 1.077825 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 527007.258 | 527007.258 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 527007.26 | 350899.84 | 10.778248 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 225191.21 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 67249.459 | 67249.459 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 67249.46 | 67249.46 | 2.065636 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 47477.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6890.826 | 6890.826 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6890.83 | 6890.83 | 0.211659 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795573 | 50.1373 | 4872.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5026.306 | 5026.306 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5026.31 | 5026.31 | 0.154388 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796107 | 50.1706 | 3550.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9164.878 | 9164.878 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9164.88 | 9164.88 | 0.281509 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797000 | 50.2261 | 6465.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4244.079 | 4244.079 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4244.08 | 2898.34 | 0.089026 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792514 | 49.9469 | 2060.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 160168.378 | 160168.378 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160168.38 | 160168.38 | 4.919736 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797868 | 50.2801 | 112646.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 105850.117 | 105850.117 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105850.12 | 105850.12 | 3.251295 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797908 | 50.2826 | 74436.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 160169.402 | 160169.402 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160169.40 | 160169.40 | 4.919767 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797868 | 50.2801 | 112646.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 96902.865 | 96902.865 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 96902.87 | 96902.87 | 2.976471 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797438 | 50.2534 | 68167.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19892.098 | 19892.098 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19892.10 | 19892.10 | 0.611006 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798455 | 50.3166 | 13979.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13054.679 | 13054.679 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13054.68 | 13054.68 | 0.400988 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798455 | 50.3166 | 9173.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19892.290 | 19892.290 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19892.29 | 19892.29 | 0.611012 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798455 | 50.3166 | 13979.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12396.715 | 12396.715 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12396.72 | 12396.72 | 0.380778 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798225 | 50.3023 | 8712.73 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 219632.233 | -999.000 | 9.975311 | 0.00628145 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 219632.23 | 201338.25 | 9.975311 | 27.67 | 16.73 | 0.00769977 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 20.3553 | 24.00 | 0.00732651 | 38.5187 | 133297.63 | 0.00 | 224132.49 | 215675.20 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 20474.163 | 20474.163 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20474.16 | 20474.16 | 2.992593 | 7.00 | 6.93 | 0.00631853 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 67.8508 | 21.42 | 0.00723648 | 44.4941 | 16948.83 | 0.00 | -999.00 | -999.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2145362.071 | -999.000 | 95.192743 | 0.06135708 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2145362.07 | 1956251.62 | 95.192743 | 27.96 | 16.88 | 0.00775568 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.3315 | 24.00 | 0.00735981 | 38.6918 | 1234017.63 | 0.00 | 2188540.11 | 2091907.38 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 91305.685 | 91305.685 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 91305.69 | 91305.69 | 28.557823 | 10.09 | 8.72 | 0.00661926 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 71.1049 | 19.60 | 0.00794003 | 54.5622 | 298828.37 | 0.00 | -999.00 | -999.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 233936.927 | -999.000 | 10.888033 | 0.00669057 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 233936.93 | 215336.58 | 10.888033 | 27.35 | 16.58 | 0.00765432 | 11.00 | 9.55 | 0.00700000 | 41.90 | 0.00915774 | 22.24 | 18.6489 | 24.00 | 0.00730859 | 38.4257 | 145306.20 | 0.00 | 238881.92 | 231171.95 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 8549.589 | 8549.589 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8549.59 | 8549.59 | 3.266410 | 10.58 | 9.14 | 0.00678991 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 62.1631 | 19.50 | 0.00795555 | 55.0201 | 38574.64 | 0.00 | -999.00 | -999.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 122464.507 | -999.000 | 5.346384 | 0.00350247 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 122464.51 | 109567.03 | 5.346384 | 27.86 | 16.97 | 0.00791543 | 10.98 | 9.54 | 0.00700000 | 39.77 | 0.00915417 | 21.63 | 22.4480 | 24.00 | 0.00751389 | 39.4923 | 65595.07 | 0.00 | 124905.55 | 116906.29 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 243321.822 | 243321.822 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 243321.82 | 243321.82 | 5.346384 | 1.41 | 1.41 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 22.4480 | 24.76 | 0.00607234 | 30.5633 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 517011.502 | 322278.091 | 25.150993 | 0.01266158 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | 464198.72 | 460169.62 | -999.0 | 28.63 | 16.53 | 0.00707074 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | -999.0000 | 27.00 | 0.00704224 | 30.9984 | 370534.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9909.425 | 6163.638 | 0.481893 | 0.00024268 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8898.80 | 8726.04 | -999.0 | 28.43 | 16.54 | 0.00715844 | 12.80 | 10.34 | 0.00700000 | 41.03 | 0.00915628 | 21.99 | -999.0000 | 27.00 | 0.00709012 | 31.2049 | 8020.45 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92222.952 | 58101.444 | 4.600708 | 0.00225853 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 82418.59 | 81665.53 | -999.0 | 28.15 | 16.37 | 0.00707278 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 76445.67 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9569.378 | 5949.941 | 0.465016 | 0.00023435 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 8594.63 | 8425.13 | -999.0 | 28.44 | 16.54 | 0.00716107 | 12.80 | 10.34 | 0.00700000 | 41.03 | 0.00915628 | 21.99 | -999.0000 | 27.00 | 0.00709165 | 31.2116 | 7886.81 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 517011.502 | 517011.502 | 25.150993 | 0.01266158 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 517011.50 | 517011.50 | 25.150993 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.3454 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9909.425 | 9909.425 | 0.481893 | 0.00024268 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9909.42 | 9909.42 | 0.481893 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2439 | 26.91 | 0.00700000 | 30.9761 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92222.952 | 92222.952 | 4.600708 | 0.00225853 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92222.95 | 92222.95 | 4.600708 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3978 | 24.62 | 0.00662543 | 33.6020 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9569.378 | 9569.378 | 0.465016 | 0.00023435 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9569.38 | 9569.38 | 0.465016 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3617 | 23.78 | 0.00614020 | 32.7694 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13450.69 | 13450.69 | 25.150993 | 0.08 | 0.08 | 0.00698752 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.3454 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.481893 | 0.20 | 0.20 | 0.00696991 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2439 | 26.91 | 0.00700000 | 30.9761 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.66 | 6213.66 | 4.600708 | 0.21 | 0.21 | 0.00660664 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3978 | 24.62 | 0.00662543 | 33.6020 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.465016 | 0.21 | 0.21 | 0.00613792 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3617 | 23.78 | 0.00614020 | 32.7694 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 52650.948 | 52650.948 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 52650.95 | 35089.98 | 1.0000 | 1.26513510 | 1.077825 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52650.95 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 527007.258 | 527007.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 527007.26 | 350899.84 | 1.0000 | 12.65135096 | 10.778248 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 527007.26 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.88 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 225191.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 67249.459 | 67249.459 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 67249.46 | 67249.46 | 1.0000 | 2.42461355 | 2.065636 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67249.46 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 47477.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6890.826 | 6890.826 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6890.83 | 6890.83 | 1.0000 | 0.24844201 | 0.211659 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6890.83 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00795573 | 21.00 | 0.00795573 | 50.1373 | 4872.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5026.306 | 5026.306 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5026.31 | 5026.31 | 1.0000 | 0.18121854 | 0.154388 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5026.31 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00796107 | 21.00 | 0.00796107 | 50.1706 | 3550.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9164.878 | 9164.878 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9164.88 | 9164.88 | 1.0000 | 0.33043073 | 0.281509 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9164.88 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00797000 | 21.00 | 0.00797000 | 50.2261 | 6465.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4244.079 | 4244.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4244.08 | 2898.34 | 1.0000 | 0.10449692 | 0.089026 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4244.08 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.82 | 0.00792514 | 21.00 | 0.00792514 | 49.9469 | 2060.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 160168.378 | 160168.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160168.38 | 160168.38 | 1.0000 | 5.77471446 | 4.919736 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 160168.38 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00797868 | 21.00 | 0.00797868 | 50.2801 | 112646.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 105850.117 | 105850.117 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105850.12 | 105850.12 | 1.0000 | 3.81632261 | 3.251295 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 105850.12 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00797908 | 21.00 | 0.00797908 | 50.2826 | 74436.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 160169.402 | 160169.402 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160169.40 | 160169.40 | 1.0000 | 5.77475138 | 4.919767 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 160169.40 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00797868 | 21.00 | 0.00797868 | 50.2801 | 112646.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 96902.865 | 96902.865 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 96902.87 | 96902.87 | 1.0000 | 3.49373818 | 2.976471 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 96902.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797438 | 21.00 | 0.00797438 | 50.2534 | 68167.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19892.098 | 19892.098 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19892.10 | 19892.10 | 1.0000 | 0.71719016 | 0.611006 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19892.10 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798455 | 21.00 | 0.00798455 | 50.3166 | 13979.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13054.679 | 13054.679 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13054.68 | 13054.68 | 1.0000 | 0.47067370 | 0.400988 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13054.68 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798455 | 21.00 | 0.00798455 | 50.3166 | 9173.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19892.290 | 19892.290 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19892.29 | 19892.29 | 1.0000 | 0.71719709 | 0.611012 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19892.29 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798455 | 21.00 | 0.00798455 | 50.3166 | 13979.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12396.715 | 12396.715 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12396.72 | 12396.72 | 1.0000 | 0.44695146 | 0.380778 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12396.72 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798225 | 21.00 | 0.00798225 | 50.3023 | 8712.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 219632.233 | -999.000 | 9.975311 | 0.00628145 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1535 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.975311 | 11.70887539 | 4197.9300 | 999.8980 | 77.82363398 | 15.00 | 6.67 | 8.33 | 2721395.74 | 8.0706 | 8.070573 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 219632.23 | 201338.25 | 1.0000 | 11.70887539 | 9.975311 | 27.67 | 16.73 | 0.00769977 | 47454.2 | 10.99 | 9.55 | 0.00700000 | 28696.4 | 6.28081329 | 6.67 | 15.00 | 8.33 | 21556.117 | 198076.12 | 42.00 | 0.00915790 | 22.26 | 2.03050000 | 20.3553 | 24.00 | 0.00732651 | 24.00 | 0.00732651 | 38.5187 | 133297.63 | 0.00 | 224132.49 | 215675.20 | 11.70887539 | 27.67 | 16.99 | 0.00769977 | 47454.2 | 9.59 | 9.58 | 0.00741300 | 28312.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20474.163 | 20474.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.975311 | 11.70887539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20474.16 | 20474.16 | 1.0000 | 3.51266262 | 2.992593 | 7.00 | 6.93 | 0.00631853 | 22917.9 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20474.16 | 6.30 | 0.00607234 | 6.30 | 2.03050000 | 67.8508 | 8.48 | 0.00683810 | 21.42 | 0.00723648 | 44.4941 | 16948.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2145362.071 | -999.000 | 95.192743 | 0.06135708 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2574 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.192743 | 111.73585727 | 4197.9300 | 999.8980 | 77.82363398 | 15.00 | 6.67 | 8.33 | 2721395.74 | 78.8332 | 78.833153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 2145362.07 | 1956251.62 | 1.0000 | 111.73585727 | 95.192743 | 27.96 | 16.88 | 0.00775568 | 47896.9 | 10.99 | 9.55 | 0.00700000 | 28696.6 | 61.35082460 | 6.67 | 15.00 | 8.33 | 205706.447 | 1939655.62 | 42.00 | 0.00915790 | 22.26 | 20.30600000 | 21.3315 | 24.00 | 0.00735981 | 24.00 | 0.00735981 | 38.6918 | 1234017.63 | 0.00 | 2188540.11 | 2091907.38 | 111.73585727 | 27.96 | 17.14 | 0.00775568 | 47896.9 | 9.59 | 9.58 | 0.00741233 | 28310.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91305.685 | 91305.685 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.192743 | 111.73585727 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 91305.69 | 91305.69 | 1.0000 | 33.52075718 | 28.557823 | 10.09 | 8.72 | 0.00661926 | 26816.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91305.69 | 6.30 | 0.00607234 | 6.30 | 20.30600000 | 71.1049 | 19.41 | 0.00796511 | 19.60 | 0.00794003 | 54.5622 | 298828.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 233936.927 | -999.000 | 10.888033 | 0.00669057 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0690 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.888033 | 12.78021429 | 4197.9300 | 999.8980 | 77.82363398 | 15.00 | 6.67 | 8.33 | 2721395.74 | 8.5962 | 8.596211 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 233936.93 | 215336.58 | 1.0000 | 12.78021429 | 10.888033 | 27.35 | 16.58 | 0.00765432 | 47010.7 | 11.00 | 9.55 | 0.00700000 | 28706.1 | 6.68988398 | 6.67 | 15.00 | 8.33 | 23403.440 | 210533.49 | 41.90 | 0.00915774 | 22.24 | 2.03050000 | 18.6489 | 24.00 | 0.00730859 | 24.00 | 0.00730859 | 38.4257 | 145306.20 | 0.00 | 238881.92 | 231171.95 | 12.78021429 | 27.35 | 16.84 | 0.00765432 | 47010.7 | 9.60 | 9.59 | 0.00741481 | 28319.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8549.589 | 8549.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.888033 | 12.78021429 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8549.59 | 8549.59 | 1.0000 | 3.83406429 | 3.266410 | 10.58 | 9.14 | 0.00678991 | 27746.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8549.59 | 6.30 | 0.00607234 | 6.30 | 2.03050000 | 62.1631 | 17.61 | 0.00796881 | 19.50 | 0.00795555 | 55.0201 | 38574.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 122464.507 | -999.000 | 5.346384 | 0.00350247 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5544 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:VariableVolume | 5.346384 | 6.27550781 | 4197.9300 | 999.8980 | 77.82363398 | 15.00 | 6.67 | 8.33 | 2721395.74 | 4.5001 | 4.500062 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 122464.51 | 109567.03 | 1.0000 | 6.27550781 | 5.346384 | 27.86 | 16.97 | 0.00791543 | 48200.0 | 10.98 | 9.54 | 0.00700000 | 28685.3 | 3.50211212 | 6.67 | 15.00 | 8.33 | 11627.788 | 110836.72 | 39.77 | 0.00915417 | 21.63 | 1.20015641 | 22.4480 | 24.00 | 0.00751389 | 24.00 | 0.00751389 | 39.4923 | 65595.07 | 0.00 | 124905.55 | 116906.29 | 6.27550781 | 27.86 | 17.24 | 0.00791543 | 48200.0 | 9.59 | 9.58 | 0.00740935 | 28296.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 243321.822 | 243321.822 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:VariableVolume | 5.346384 | 6.27550781 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 243321.82 | 243321.82 | 1.0000 | 6.27550781 | 5.346384 | 1.41 | 1.41 | 0.00607234 | 16623.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 243321.82 | 6.30 | 0.00607234 | 6.30 | 1.20015641 | 22.4480 | 0.00 | 0.00607234 | 24.76 | 0.00607234 | 30.5633 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 517011.502 | 322278.091 | 25.150993 | 0.01266158 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9842 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | Sensible | 464198.72 | 460169.62 | 0.8978 | -999.0 | -999.0 | 28.63 | 16.53 | 0.00707074 | 46828.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 464198.72 | 42.00 | 0.00915790 | 22.26 | 0.33839277 | -999.0000 | 27.00 | 0.00704224 | 27.00 | 0.00704224 | 30.9984 | 370534.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9909.425 | 6163.638 | 0.481893 | 0.00024268 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1472 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8898.80 | 8726.04 | 0.8980 | -999.0 | -999.0 | 28.43 | 16.54 | 0.00715844 | 46853.3 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8898.80 | 41.03 | 0.00915628 | 21.99 | 0.01563234 | -999.0000 | 27.00 | 0.00709012 | 27.00 | 0.00709012 | 31.2049 | 8020.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92222.952 | 58101.444 | 4.600708 | 0.00225853 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9879 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 82418.59 | 81665.53 | 0.8937 | -999.0 | -999.0 | 28.15 | 16.37 | 0.00707278 | 46348.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82418.59 | 32.36 | 0.00914193 | 19.41 | 0.15632344 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 76445.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9569.378 | 5949.941 | 0.465016 | 0.00023435 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1521 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | Sensible | 8594.63 | 8425.13 | 0.8981 | -999.0 | -999.0 | 28.44 | 16.54 | 0.00716107 | 46868.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8594.63 | 41.03 | 0.00915628 | 21.99 | 0.01563234 | -999.0000 | 27.00 | 0.00709165 | 27.00 | 0.00709165 | 31.2116 | 7886.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 517011.502 | 517011.502 | 25.150993 | 0.01266158 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 517011.50 | 517011.50 | 1.0000 | 29.52187044 | 25.150993 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 517011.50 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.3454 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9909.425 | 9909.425 | 0.481893 | 0.00024268 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9909.42 | 9909.42 | 1.0000 | 0.56563902 | 0.481893 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9909.42 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2439 | 0.00 | 0.00700000 | 26.91 | 0.00700000 | 30.9761 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92222.952 | 92222.952 | 4.600708 | 0.00225853 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92222.95 | 92222.95 | 1.0000 | 5.40024361 | 4.600708 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92222.95 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3978 | 0.00 | 0.00662543 | 24.62 | 0.00662543 | 33.6020 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9569.378 | 9569.378 | 0.465016 | 0.00023435 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9569.38 | 9569.38 | 1.0000 | 0.54582915 | 0.465016 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9569.38 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3617 | 0.00 | 0.00614020 | 23.78 | 0.00614020 | 32.7694 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.150993 | 29.52187044 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13450.69 | 13450.69 | 1.0000 | 29.52187044 | 25.150993 | 0.08 | 0.08 | 0.00698752 | 17561.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13450.69 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.3454 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.481893 | 0.56563902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.56563902 | 0.481893 | 0.20 | 0.20 | 0.00696991 | 17639.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2439 | 0.00 | 0.00700000 | 26.91 | 0.00700000 | 30.9761 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.600708 | 5.40024361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6213.66 | 6213.66 | 1.0000 | 5.40024361 | 4.600708 | 0.21 | 0.21 | 0.00660664 | 16740.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.66 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3978 | 0.00 | 0.00662543 | 24.62 | 0.00662543 | 33.6020 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.465016 | 0.54582915 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.54582915 | 0.465016 | 0.21 | 0.21 | 0.00613792 | 15565.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3617 | 0.00 | 0.00614020 | 23.78 | 0.00614020 | 32.7694 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5379.50 | 3282.00 | 3280.67 |
CORE_BOTTOM | 5313.83 | 212.67 | 202.33 |
CORE_MID | 4555.83 | 476.33 | 23.33 |
CORE_TOP | 4251.33 | 1110.50 | 43.50 |
PERIMETER_BOT_ZN_3 | 4464.33 | 1336.67 | 476.00 |
PERIMETER_BOT_ZN_2 | 4702.00 | 1199.67 | 573.33 |
PERIMETER_BOT_ZN_1 | 5179.83 | 996.83 | 622.67 |
PERIMETER_BOT_ZN_4 | 5360.17 | 969.00 | 799.00 |
PERIMETER_MID_ZN_3 | 3981.50 | 1866.67 | 327.83 |
PERIMETER_MID_ZN_2 | 3658.67 | 1397.67 | 444.33 |
PERIMETER_MID_ZN_1 | 4958.67 | 1013.00 | 450.50 |
PERIMETER_MID_ZN_4 | 4455.50 | 1548.83 | 531.83 |
PERIMETER_TOP_ZN_3 | 4054.33 | 2086.00 | 540.83 |
PERIMETER_TOP_ZN_2 | 4339.33 | 1754.33 | 555.00 |
PERIMETER_TOP_ZN_1 | 4809.33 | 1273.50 | 533.17 |
PERIMETER_TOP_ZN_4 | 4404.50 | 1792.00 | 642.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1923.83 | 1923.83 |
DATACENTER_MID_ZN_6 | 5935.83 | 471.17 | 471.17 |
DATACENTER_TOP_ZN_6 | 5885.00 | 667.83 | 640.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 4966.33 | 0.00 | 3355.50 |
CORE_BOTTOM | 0.00 | 90.50 | 0.00 | 6.33 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.83 | 1.83 | 0.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 277.67 | 0.00 | 87.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 319.33 | 0.00 | 115.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 326.17 | 0.00 | 134.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 487.67 | 0.00 | 158.33 |
PERIMETER_MID_ZN_3 | 0.17 | 99.17 | 0.00 | 39.67 |
PERIMETER_MID_ZN_2 | 0.17 | 172.17 | 0.00 | 80.50 |
PERIMETER_MID_ZN_1 | 0.00 | 175.00 | 0.00 | 94.33 |
PERIMETER_MID_ZN_4 | 0.00 | 249.67 | 0.00 | 82.17 |
PERIMETER_TOP_ZN_3 | 2.17 | 134.83 | 0.17 | 50.50 |
PERIMETER_TOP_ZN_2 | 1.33 | 197.17 | 0.00 | 84.50 |
PERIMETER_TOP_ZN_1 | 0.50 | 193.50 | 0.00 | 88.33 |
PERIMETER_TOP_ZN_4 | 0.50 | 263.00 | 0.00 | 87.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 317.33 | 0.00 | 247.67 |
DATACENTER_MID_ZN_6 | 0.00 | 413.83 | 0.00 | 351.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 247.33 | 0.00 | 209.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.50 | 5044.17 | 0.33 | 3416.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.70 | 149.60 | 6779.02 | 0.228 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.41 | 134.35 | 6849.35 | 0.504 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.41 | 134.35 | 6849.35 | 0.470 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.41 | 134.35 | 6849.35 | 0.455 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.96 | 16.87 | 860.00 | 0.580 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.709 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.96 | 16.87 | 860.02 | 0.803 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.939 | 0.008 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.96 | 16.87 | 860.00 | 0.643 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.820 | 0.019 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.96 | 16.87 | 860.02 | 0.973 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.907 | 0.018 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.96 | 16.87 | 860.00 | 0.626 | 0.022 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.825 | 0.023 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.96 | 16.87 | 860.02 | 0.931 | 0.022 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.862 | 0.023 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 0.663 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.70 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 0.613 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.70 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.91 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.40 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1022.56 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 9575271.89 | 0.00 | 9575271.89 | 0.00 | 9575271.89 | 37848132.68 | 6559.45 | 2200.55 | 0.00 | 168.52 |
CORE_BOTTOM | 24668387.25 | 0.00 | 24668387.25 | 0.00 | 24668387.25 | 33990283.35 | 6694.34 | 784.87 | 1280.79 | 1312.62 |
CORE_MID | 0.22E+09 | 0.00 | 0.22E+09 | 0.00 | 0.22E+09 | 0.34E+09 | 6608.03 | 1053.55 | 1098.41 | 905.86 |
CORE_TOP | 21195913.53 | 0.00 | 21195913.53 | 0.00 | 21195913.53 | 33990283.35 | 6876.10 | 1331.30 | 552.60 | 896.65 |
PERIMETER_BOT_ZN_3 | 3564320.44 | 0.00 | 3564320.44 | 60968.50 | 3625288.94 | 4267819.30 | 4698.59 | 785.55 | 3275.86 | 1312.62 |
PERIMETER_BOT_ZN_2 | 2723845.08 | 0.00 | 2723845.08 | 40645.64 | 2764490.71 | 2750345.05 | 4085.63 | 558.05 | 4116.32 | 1312.62 |
PERIMETER_BOT_ZN_1 | 4681385.41 | 0.00 | 4681385.41 | 60968.50 | 4742353.91 | 4267912.63 | 3124.32 | 803.18 | 4832.50 | 1312.62 |
PERIMETER_BOT_ZN_4 | 3639607.81 | 0.00 | 3639607.81 | 40645.64 | 3680253.45 | 2750345.05 | 2693.35 | 517.91 | 5548.74 | 1312.62 |
PERIMETER_MID_ZN_3 | 36480225.58 | 0.00 | 36480225.58 | 142984.65 | 36623210.23 | 42678193.03 | 4956.70 | 894.19 | 2909.12 | 905.86 |
PERIMETER_MID_ZN_2 | 29335983.53 | 0.00 | 29335983.53 | 95323.04 | 29431306.57 | 27503450.52 | 4058.17 | 862.43 | 3839.40 | 1743.86 |
PERIMETER_MID_ZN_1 | 53163393.61 | 0.00 | 53163393.61 | 142984.65 | 53306378.26 | 42679126.28 | 3210.82 | 866.24 | 4682.95 | 905.86 |
PERIMETER_MID_ZN_4 | 33004077.24 | 0.00 | 33004077.24 | 95323.04 | 33099400.27 | 27503450.52 | 3804.38 | 729.88 | 4225.74 | 905.86 |
PERIMETER_TOP_ZN_3 | 3583995.11 | 0.00 | 3583995.11 | 177526.26 | 3761521.37 | 4267819.30 | 4766.15 | 1038.06 | 2955.78 | 896.65 |
PERIMETER_TOP_ZN_2 | 2964210.07 | 0.00 | 2964210.07 | 118350.76 | 3082560.83 | 2750345.05 | 3529.96 | 1281.30 | 3948.74 | 896.65 |
PERIMETER_TOP_ZN_1 | 5126455.89 | 0.00 | 5126455.89 | 177526.26 | 5303982.15 | 4267912.63 | 3119.96 | 1192.65 | 4447.39 | 896.65 |
PERIMETER_TOP_ZN_4 | 3166090.43 | 0.00 | 3166090.43 | 118350.76 | 3284441.19 | 2750345.05 | 3307.45 | 1247.13 | 4205.42 | 896.65 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.39E+10 | 0.00 | 0.39E+10 | 5561136.05 | 0.39E+10 | 0.50E+10 | 8739.70 | 8760.00 | 6206.59 | 3655.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.4191 | 0.0000 | 0.4191 | 0.0000 | 0.4191 | 1.2002 | 3869.29 | 2073.71 | 0.00 |
CORE_BOTTOM | 0.9281 | 0.0000 | 0.9281 | 0.0000 | 0.9281 | 1.0778 | 4438.32 | 280.66 | 1224.02 |
CORE_MID | 8.6429 | 0.0000 | 8.6429 | 0.0000 | 8.6429 | 10.7782 | 4293.58 | 557.20 | 1092.22 |
CORE_TOP | 0.8367 | 0.0000 | 0.8367 | 0.0000 | 0.8367 | 1.0778 | 4518.71 | 884.33 | 539.96 |
PERIMETER_BOT_ZN_3 | 0.1338 | 0.0000 | 0.1338 | 0.0017 | 0.1355 | 0.1353 | 2753.07 | 282.00 | 2907.93 |
PERIMETER_BOT_ZN_2 | 0.1054 | 0.0000 | 0.1054 | 0.0012 | 0.1066 | 0.0872 | 1994.70 | 227.98 | 3720.33 |
PERIMETER_BOT_ZN_1 | 0.1855 | 0.0000 | 0.1855 | 0.0017 | 0.1873 | 0.1353 | 1238.51 | 258.65 | 4445.83 |
PERIMETER_BOT_ZN_4 | 0.1396 | 0.0000 | 0.1396 | 0.0012 | 0.1407 | 0.0872 | 965.36 | 178.01 | 4799.63 |
PERIMETER_MID_ZN_3 | 1.4827 | 0.0000 | 1.4827 | 0.0041 | 1.4868 | 1.3533 | 2582.96 | 575.61 | 2784.43 |
PERIMETER_MID_ZN_2 | 1.2175 | 0.0000 | 1.2175 | 0.0028 | 1.2203 | 0.8721 | 1472.55 | 542.99 | 3018.47 |
PERIMETER_MID_ZN_1 | 2.2480 | 0.0000 | 2.2480 | 0.0041 | 2.2520 | 1.3533 | 1095.26 | 355.19 | 4492.55 |
PERIMETER_MID_ZN_4 | 1.3460 | 0.0000 | 1.3460 | 0.0027 | 1.3488 | 0.8721 | 1576.52 | 519.37 | 3847.11 |
PERIMETER_TOP_ZN_3 | 0.1445 | 0.0000 | 0.1445 | 0.0051 | 0.1495 | 0.1353 | 2366.02 | 797.57 | 2779.41 |
PERIMETER_TOP_ZN_2 | 0.1225 | 0.0000 | 0.1225 | 0.0034 | 0.1259 | 0.0872 | 1394.52 | 842.85 | 3705.63 |
PERIMETER_TOP_ZN_1 | 0.2151 | 0.0000 | 0.2151 | 0.0051 | 0.2202 | 0.1353 | 998.69 | 734.72 | 4209.59 |
PERIMETER_TOP_ZN_4 | 0.1280 | 0.0000 | 0.1280 | 0.0034 | 0.1313 | 0.0872 | 1312.24 | 828.95 | 3801.81 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 154.6619 | 0.0000 | 154.6619 | 0.1595 | 154.8215 | 158.4706 | 5922.94 | 5943.00 | 5240.84 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 54115527.86 | 0.00 | 54115527.86 | 48026705.38 | 2243.43 | 3.62 | 6512.96 | 1312.62 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 2744.26 | 2.54 | 6013.19 | 905.86 |
VAV_TOP WITH REHEAT | 49650320.25 | 0.00 | 49650320.25 | 48026705.38 | 2779.91 | 2.17 | 5977.92 | 896.65 |
CAV_BAS | 13192465.18 | 0.00 | 13192465.18 | 37848132.68 | 6552.28 | 0.50 | 2207.22 | 168.52 |
AIRLOOP DATACENTER BASEMENT | 14702971.99 | 0.00 | 14702971.99 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 6792163.95 | 0.00 | 6792163.95 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.0562 | 0.0000 | 2.0562 | 1.5229 | 668.08 | 2.24 | 5272.68 |
VAV_MID WITH REHEAT | 20.5781 | 0.0000 | 20.5781 | 15.2292 | 811.18 | 1.20 | 5130.62 |
VAV_TOP WITH REHEAT | 1.9933 | 0.0000 | 1.9933 | 1.5229 | 835.05 | 1.25 | 5106.70 |
CAV_BAS | 0.5774 | 0.0000 | 0.5774 | 1.2002 | 3869.26 | 0.00 | 2073.74 |
AIRLOOP DATACENTER BASEMENT | 0.4662 | 0.0000 | 0.4662 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2154 | 0.0000 | 0.2154 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 711.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5909.73 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 745.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5316.62 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 5627.06 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2200.47 | 0.00 | 0.00 | 47.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.5936 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2660 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.5053 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 23.2895 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.5505 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2922 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6541 | 0.0000 | 0.0000 | 0.4358 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4662 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1455 |
Defaulted Fields | 1152 |
Fields with Defaults | 3681 |
Autosized Fields | 289 |
Autosizable Fields | 361 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 472 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
Electricity:Building | 17135.85 | 216479.19 | 21-MAY-17:20 | 1015041.04 | 29-DEC-17:00 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17135.85 | 216479.19 | 21-MAY-17:20 | 1015041.04 | 29-DEC-17:00 |
InteriorLights:Electricity | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.99 | 603.11 | 12-MAR-17:10 | 3626.39 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.62 | 43.94 | 01-JAN-09:20 | 1465.83 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.62 | 43.94 | 01-JAN-09:20 | 1465.83 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.25 | 388.67 | 23-APR-17:10 | 2334.01 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 941.67 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 941.67 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.87 | 603.12 | 12-MAR-17:10 | 3618.21 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.51 | 43.94 | 01-JAN-08:00 | 1457.63 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.51 | 43.94 | 01-JAN-08:00 | 1457.63 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.25 | 388.67 | 12-MAR-17:10 | 2341.98 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.81 | 28.32 | 01-JAN-09:20 | 949.65 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.81 | 28.32 | 01-JAN-09:20 | 949.65 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 469.71 | 6031.15 | 12-MAR-17:10 | 36241.40 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.05 | 439.44 | 01-JAN-09:10 | 14635.89 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.05 | 439.44 | 01-JAN-09:10 | 14635.89 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.41 | 3886.70 | 23-APR-17:10 | 23306.76 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.06 | 283.19 | 01-JAN-07:50 | 9383.34 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.06 | 283.19 | 01-JAN-07:50 | 9383.34 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 468.64 | 6031.24 | 12-MAR-17:10 | 36159.18 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.98 | 439.45 | 01-JAN-08:00 | 14553.33 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.98 | 439.45 | 01-JAN-08:00 | 14553.33 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 302.35 | 3886.68 | 12-MAR-17:10 | 23387.96 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.00 | 283.19 | 01-JAN-09:10 | 9464.63 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.00 | 283.19 | 01-JAN-09:10 | 9464.63 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.97 | 603.11 | 12-MAR-17:10 | 3623.73 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.60 | 43.94 | 01-JAN-09:10 | 1463.18 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.60 | 43.94 | 01-JAN-09:10 | 1463.18 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.24 | 388.67 | 23-APR-17:10 | 2330.45 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 938.11 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 938.11 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.86 | 603.12 | 12-MAR-17:10 | 3615.49 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.50 | 43.94 | 01-JAN-08:00 | 1454.91 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.50 | 43.94 | 01-JAN-08:00 | 1454.91 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.23 | 388.67 | 12-MAR-17:10 | 2338.54 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.80 | 28.32 | 01-JAN-09:10 | 946.21 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.80 | 28.32 | 01-JAN-09:10 | 946.21 | 11-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 5599.32 | 6226.60 | 03-JAN-05:50 | 566134.88 | 22-JUN-15:40 |
HeatRejection:Electricity | 1733.41 | 2260.75 | 05-JAN-07:00 | 84051.29 | 16-MAY-22:00 |
General:HeatRejection:Electricity | 1733.41 | 2260.75 | 05-JAN-07:00 | 84051.29 | 16-MAY-22:00 |
Electricity:HVAC | 6139.09 | 84568.87 | 16-JAN-12:40 | 672743.17 | 02-JAN-06:10 |
ExteriorEquipment:Electricity | 2566.27 | 20217.42 | 01-JAN-00:10 | 233393.00 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3408.66 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
ElectricityPurchased:Plant | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
Cogeneration:ElectricityPurchased | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
ElectricityNet:Plant | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
Cogeneration:ElectricityNet | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
General:Cogeneration:ElectricityNet | 31735.17 | 342620.63 | 01-JAN-00:10 | 2177920.65 | 07-AUG-15:30 |
Heating:Electricity | 45.55 | 0.00 | 01-JAN-00:10 | 550160.60 | 02-JAN-06:10 |
General:Heating:Electricity | 45.55 | 0.00 | 01-JAN-00:10 | 550160.60 | 02-JAN-06:10 |
Fans:Electricity | 2801.16 | 47694.13 | 01-JAN-14:40 | 259488.91 | 06-JUL-16:00 |
General:Fans:Electricity | 2801.16 | 47694.13 | 01-JAN-14:40 | 259488.91 | 06-JUL-16:00 |
ExteriorLights:Electricity | 349.31 | 0.00 | 01-JAN-07:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 349.31 | 0.00 | 01-JAN-07:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 5872.97 | 30244.62 | 01-JAN-05:00 | 567251.39 | 28-AUG-14:30 |
General:Cooling:Electricity | 5872.97 | 30244.62 | 01-JAN-05:00 | 567251.39 | 28-AUG-14:30 |
Humidifier:Electricity | 92.49 | 0.00 | 12-JAN-13:20 | 29206.62 | 22-DEC-07:00 |
General:Humidifier:Electricity | 92.49 | 0.00 | 12-JAN-13:20 | 29206.62 | 22-DEC-07:00 |
Boiler:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 307.72 | 0.00 | 01-JAN-00:10 | 41462.49 | 17-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 307.72 | 0.00 | 01-JAN-00:10 | 41462.49 | 17-JAN-12:30 |
Pumps:Electricity | 830.42 | 3888.16 | 01-JAN-00:10 | 50659.79 | 24-OCT-14:40 |
General:Pumps:Electricity | 830.42 | 3888.16 | 01-JAN-00:10 | 50659.79 | 24-OCT-14:40 |
WIRED_LTG_ELECTRICITY | 69.11 | 0.00 | 01-JAN-00:10 | 6718.22 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 35615.66 | 159329.04 | 01-JAN-05:00 | 3151968.04 | 28-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 35615.66 | 159329.04 | 01-JAN-05:00 | 3151968.04 | 28-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 35615.66 | 159329.04 | 01-JAN-05:00 | 3151968.04 | 28-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 21079.15 | 0.00 | 11-MAR-00:30 | 0.00 | 12-JUN-15:30 |
Water:HVAC | 34.41 | 0.00 | 12-JAN-13:20 | 0.00 | 22-DEC-07:00 |
Humidifier:Water | 34.41 | 0.00 | 12-JAN-13:20 | 0.00 | 22-DEC-07:00 |
General:Humidifier:Water | 34.41 | 0.00 | 12-JAN-13:20 | 0.00 | 22-DEC-07:00 |
MainsWater:Facility | 21079.15 | 0.00 | 11-MAR-00:30 | 0.00 | 12-JUN-15:30 |
MainsWater:HVAC | 34.41 | 0.00 | 12-JAN-13:20 | 0.00 | 22-DEC-07:00 |
Humidifier:MainsWater | 34.41 | 0.00 | 12-JAN-13:20 | 0.00 | 22-DEC-07:00 |
General:Humidifier:MainsWater | 34.41 | 0.00 | 12-JAN-13:20 | 0.00 | 22-DEC-07:00 |
Water:Plant | 21044.74 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 21044.74 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 18764.58 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
General:HeatRejection:Water | 18764.58 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
HeatRejection:MainsWater | 18764.58 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
General:HeatRejection:MainsWater | 18764.58 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 125008.80 | 220016.91 | 03-JAN-05:50 | 12440042.33 | 22-JUN-15:30 |
EnergyTransfer:Building | 23100.32 | 89999.70 | 03-JAN-04:50 | 1756864.22 | 28-APR-15:40 |
EnergyTransfer:Zone:BASEMENT | 335.13 | 0.00 | 01-JAN-00:10 | 91027.92 | 02-OCT-05:10 |
Heating:EnergyTransfer | 33.18 | 0.00 | 03-JAN-22:10 | 348743.70 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 33.18 | 0.00 | 03-JAN-22:10 | 348743.70 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 23067.14 | 89758.11 | 01-JAN-06:00 | 1756864.22 | 28-APR-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 335.13 | 0.00 | 01-JAN-00:10 | 91027.92 | 02-OCT-05:10 |
General:Cooling:EnergyTransfer | 23067.14 | 89758.11 | 01-JAN-06:00 | 1756864.22 | 28-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 335.13 | 0.00 | 01-JAN-00:10 | 91027.92 | 02-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 913.98 | 0.00 | 01-JAN-00:10 | 79017.67 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 913.98 | 0.00 | 01-JAN-00:10 | 79017.67 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 913.98 | 0.00 | 01-JAN-00:10 | 79017.67 | 07-AUG-05:20 |
EnergyTransfer:Zone:CORE_MID | 5634.91 | 0.00 | 01-JAN-00:10 | 452062.26 | 30-MAY-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 10264.70 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 10264.70 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5634.90 | 0.00 | 01-JAN-00:10 | 452062.26 | 30-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5634.90 | 0.00 | 01-JAN-00:10 | 452062.26 | 30-MAY-13:10 |
EnergyTransfer:Zone:CORE_TOP | 574.53 | 0.00 | 01-JAN-00:10 | 57389.89 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.54 | 0.00 | 01-JAN-00:10 | 53297.91 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.54 | 0.00 | 01-JAN-00:10 | 53297.91 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 573.99 | 0.00 | 01-JAN-00:10 | 57389.89 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 573.99 | 0.00 | 01-JAN-00:10 | 57389.89 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 146.09 | 0.00 | 01-JAN-00:10 | 16810.12 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 146.09 | 0.00 | 01-JAN-00:10 | 16810.12 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 146.09 | 0.00 | 01-JAN-00:10 | 16810.12 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 113.35 | 0.00 | 01-JAN-00:10 | 14659.56 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 113.35 | 0.00 | 01-JAN-00:10 | 14659.56 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 113.35 | 0.00 | 01-JAN-00:10 | 14659.56 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 186.17 | 0.00 | 01-JAN-00:10 | 19015.69 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 981.19 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 981.19 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 186.17 | 0.00 | 01-JAN-00:10 | 19015.69 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 186.17 | 0.00 | 01-JAN-00:10 | 19015.69 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 143.02 | 0.00 | 01-JAN-00:10 | 18069.64 | 27-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 143.02 | 0.00 | 01-JAN-00:10 | 18069.64 | 27-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 143.02 | 0.00 | 01-JAN-00:10 | 18069.64 | 27-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1041.93 | 0.00 | 01-JAN-00:10 | 144831.52 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.17 | 0.00 | 01-JAN-00:10 | 78594.55 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.17 | 0.00 | 01-JAN-00:10 | 78594.55 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1038.76 | 0.00 | 01-JAN-00:10 | 144831.52 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1038.76 | 0.00 | 01-JAN-00:10 | 144831.52 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 880.16 | 0.00 | 01-JAN-00:10 | 147123.62 | 12-JUN-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.00 | 0.00 | 01-JAN-00:10 | 46965.20 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.00 | 0.00 | 01-JAN-00:10 | 46965.20 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 879.16 | 0.00 | 01-JAN-00:10 | 147123.62 | 12-JUN-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 879.16 | 0.00 | 01-JAN-00:10 | 147123.62 | 12-JUN-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1514.21 | 0.00 | 01-JAN-00:10 | 184229.52 | 02-OCT-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.45 | 0.00 | 01-JAN-00:10 | 46624.92 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.45 | 0.00 | 01-JAN-00:10 | 46624.92 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1513.76 | 0.00 | 01-JAN-00:10 | 184229.52 | 02-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1513.76 | 0.00 | 01-JAN-00:10 | 184229.52 | 02-OCT-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 966.00 | 0.00 | 01-JAN-00:10 | 159818.95 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.49 | 0.00 | 01-JAN-00:10 | 33379.67 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.49 | 0.00 | 01-JAN-00:10 | 33379.67 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 965.51 | 0.00 | 01-JAN-00:10 | 159818.95 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 965.51 | 0.00 | 01-JAN-00:10 | 159818.95 | 08-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 109.46 | 0.00 | 01-JAN-00:10 | 15940.98 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.92 | 0.00 | 01-JAN-00:10 | 15924.70 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.92 | 0.00 | 01-JAN-00:10 | 15924.70 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 107.54 | 0.00 | 01-JAN-00:10 | 15940.98 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 107.54 | 0.00 | 01-JAN-00:10 | 15940.98 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 93.50 | 0.00 | 01-JAN-00:10 | 15139.16 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.71 | 0.00 | 01-JAN-00:10 | 9879.53 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.71 | 0.00 | 01-JAN-00:10 | 9879.53 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 92.79 | 0.00 | 01-JAN-00:10 | 15139.16 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 92.79 | 0.00 | 01-JAN-00:10 | 15139.16 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 153.02 | 0.00 | 01-JAN-00:10 | 20076.32 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.53 | 0.00 | 01-JAN-00:10 | 13125.44 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.53 | 0.00 | 01-JAN-00:10 | 13125.44 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 152.49 | 0.00 | 01-JAN-00:10 | 20076.32 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 152.49 | 0.00 | 01-JAN-00:10 | 20076.32 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 99.02 | 0.00 | 01-JAN-00:10 | 17192.01 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.50 | 0.00 | 01-JAN-00:10 | 8343.26 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.50 | 0.00 | 01-JAN-00:10 | 8343.26 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 98.53 | 0.00 | 01-JAN-00:10 | 17192.01 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 98.53 | 0.00 | 01-JAN-00:10 | 17192.01 | 08-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 160.15 | 0.00 | 01-JAN-00:10 | 23445.57 | 05-JUL-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.95 | 0.00 | 01-JAN-00:10 | 4047.07 | 24-DEC-10:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.95 | 0.00 | 01-JAN-00:10 | 4047.07 | 24-DEC-10:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 159.20 | 0.00 | 01-JAN-00:10 | 23445.57 | 05-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 159.20 | 0.00 | 01-JAN-00:10 | 23445.57 | 05-JUL-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1044.21 | 0.00 | 01-JAN-00:10 | 145270.47 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.37 | 0.00 | 01-JAN-00:10 | 44185.28 | 03-JAN-15:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.37 | 0.00 | 01-JAN-00:10 | 44185.28 | 03-JAN-15:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1028.84 | 0.00 | 01-JAN-00:10 | 145270.47 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1028.84 | 0.00 | 01-JAN-00:10 | 145270.47 | 12-JUN-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 171.98 | 0.00 | 01-JAN-00:10 | 33599.39 | 12-JUN-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.26 | 0.00 | 01-JAN-00:10 | 20680.05 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.26 | 0.00 | 01-JAN-00:10 | 20680.05 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 164.73 | 0.00 | 01-JAN-00:10 | 33599.39 | 12-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 164.73 | 0.00 | 01-JAN-00:10 | 33599.39 | 12-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.81 | 1048.54 | 03-JAN-08:00 | 7924.26 | 16-APR-21:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.81 | 1048.54 | 03-JAN-08:00 | 7924.26 | 16-APR-21:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.81 | 1048.54 | 03-JAN-08:00 | 7924.26 | 16-APR-21:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1321.19 | 15.53 | 03-JAN-04:50 | 73348.02 | 16-APR-21:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.16 | 0.00 | 01-JAN-14:50 | 2643.88 | 01-JAN-12:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.16 | 0.00 | 01-JAN-14:50 | 2643.88 | 01-JAN-12:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1321.03 | 0.00 | 01-JAN-00:10 | 73348.02 | 16-APR-21:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1321.03 | 0.00 | 01-JAN-00:10 | 73348.02 | 16-APR-21:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.85 | 1.20 | 04-JAN-01:40 | 7620.49 | 16-APR-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-13:20 | 348.92 | 01-JAN-14:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-13:20 | 348.92 | 01-JAN-14:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.73 | 0.00 | 01-JAN-00:10 | 7620.49 | 16-APR-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.73 | 0.00 | 01-JAN-00:10 | 7620.49 | 16-APR-21:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7223.64 | 88224.21 | 08-JAN-06:00 | 371390.00 | 28-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7223.64 | 88224.21 | 08-JAN-06:00 | 371390.00 | 28-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7223.64 | 88224.21 | 08-JAN-06:00 | 371390.00 | 28-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 302.96 | 0.00 | 01-JAN-00:10 | 41062.73 | 17-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 302.96 | 0.00 | 01-JAN-00:10 | 41062.73 | 17-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 302.96 | 0.00 | 01-JAN-00:10 | 41062.73 | 17-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 302.96 | 0.00 | 01-JAN-00:10 | 41062.73 | 17-JAN-12:10 |
EnergyTransfer:HVAC | 32516.01 | 129125.92 | 01-JAN-05:20 | 2959929.12 | 28-AUG-14:10 |
HeatingCoils:EnergyTransfer | 45.55 | 0.00 | 01-JAN-00:10 | 550160.60 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 32470.45 | 123260.51 | 02-JAN-04:50 | 2959929.12 | 28-AUG-14:10 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 69392.48 | 0.00 | 01-JAN-00:10 | 8108622.51 | 22-JUN-15:30 |
LoopToLoop:EnergyTransfer | 22242.37 | 0.00 | 01-JAN-00:10 | 2558606.88 | 22-JUN-15:30 |
WaterSystems:EnergyTransfer | 302.96 | 0.00 | 01-JAN-00:10 | 41062.73 | 17-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 302.96 | 0.00 | 01-JAN-00:10 | 41062.73 | 17-JAN-12:10 |
Chillers:EnergyTransfer | 22059.69 | 0.00 | 01-JAN-00:10 | 2559124.94 | 22-JUN-15:30 |
HeatRejection:EnergyTransfer | 24787.46 | 0.00 | 01-JAN-00:10 | 2970456.84 | 22-JUN-15:30 |
General:HeatRejection:EnergyTransfer | 24787.46 | 0.00 | 01-JAN-00:10 | 2970456.84 | 22-JUN-15:30 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -335.124 | 0.000 | 0.000 | 67.146 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -322.148 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -913.976 | 0.000 | 0.000 | 83.292 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 392.234 | 0.000 | 0.000 | 0.000 | 0.000 | -0.010 |
CORE_MID | 0.000 | 0.000 | 0.006 | -5634.892 | 0.000 | 0.000 | 836.136 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 414.256 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.539 | -573.991 | 0.000 | 0.000 | 84.291 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 50.712 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -146.087 | 0.000 | 0.000 | 10.514 | 10.623 | 36.365 | 50.238 | 0.000 | 0.264 | 66.808 | 0.000 | -28.564 | 0.000 | -0.161 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -113.354 | 0.000 | 0.000 | 6.751 | 6.814 | 23.435 | 59.907 | 0.000 | 0.174 | 34.084 | 0.000 | -17.703 | 0.000 | -0.110 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.001 | -186.170 | 0.000 | 0.000 | 10.465 | 10.509 | 36.366 | 108.766 | 0.000 | 0.261 | 47.893 | 0.000 | -27.913 | 0.000 | -0.178 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -143.015 | 0.000 | 0.000 | 6.734 | 6.810 | 23.435 | 59.538 | 0.000 | 0.171 | 68.146 | 0.000 | -21.689 | 0.000 | -0.130 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.172 | -1038.751 | 0.000 | 0.000 | 107.002 | 106.054 | 363.654 | 533.152 | 0.000 | 6.333 | 171.833 | 0.000 | -249.228 | 0.000 | -3.221 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.999 | -879.153 | 0.000 | 0.000 | 49.825 | 68.061 | 234.352 | 608.734 | 0.000 | 4.039 | 79.769 | 0.000 | -164.195 | 0.000 | -2.430 | -0.012 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.445 | -1513.751 | 0.000 | 0.000 | 105.015 | 104.979 | 363.660 | 1101.968 | 0.000 | 6.158 | 102.958 | 0.000 | -267.360 | 0.000 | -4.071 | -0.002 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.494 | -965.504 | 0.000 | 0.000 | 68.239 | 68.003 | 234.351 | 615.319 | 0.000 | 4.015 | 161.323 | 0.000 | -183.714 | 0.000 | -2.525 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.922 | -107.541 | 0.000 | 0.000 | 10.792 | 10.605 | 36.365 | 52.987 | 0.000 | 0.766 | 17.899 | 0.000 | -23.430 | 0.000 | -0.366 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.707 | -92.788 | 0.000 | 0.000 | 6.840 | 6.806 | 23.435 | 60.994 | 0.000 | 0.495 | 9.335 | 0.000 | -15.545 | 0.000 | -0.278 | -0.002 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.533 | -152.485 | 0.000 | 0.000 | 10.558 | 10.497 | 36.366 | 109.803 | 0.000 | 0.745 | 9.922 | 0.000 | -25.462 | 0.000 | -0.477 | -0.002 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.497 | -98.527 | 0.000 | 0.000 | 6.871 | 6.800 | 23.435 | 61.242 | 0.000 | 0.488 | 16.988 | 0.000 | -17.500 | 0.000 | -0.295 | -0.002 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.812 | 0.000 | 0.000 | 0.944 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -13.639 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.159 | -1321.028 | 0.000 | 0.000 | 9.413 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -263.613 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.125 | -129.729 | 0.000 | 0.000 | 0.946 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -28.848 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7223.648 | 0.000 | 0.000 | 20.561 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -339.382 |
GROUNDFLOOR_PLENUM | 0.952 | -159.195 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.465 | 158.143 | 0.000 | 0.000 | 0.000 | -0.364 | -0.000 |
MIDFLOOR_PLENUM | 15.368 | -1028.839 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.051 | 1010.503 | 0.000 | 0.000 | 0.000 | -6.084 | -0.004 |
TOPFLOOR_PLENUM | 7.257 | -164.726 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.934 | 157.150 | 0.000 | 0.000 | 0.000 | -0.615 | -0.007 |
Total Facility | 23.577 | -1352.760 | 9.599 | -21714.326 | 0.000 | 0.000 | 1502.334 | 2459.457 | 14676.396 | 3422.648 | 0.000 | 34.361 | 2969.959 | 0.000 | -1042.304 | 0.000 | -21.305 | -967.679 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-JAN-05:11 | 0.00 | 0.00 | 0.00 | -104666.21 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 90610.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 14-AUG-03:03 | 0.00 | 0.00 | 0.00 | -98298.01 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 91823.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-OCT-04:12 | 0.00 | 0.00 | 0.00 | -843815.04 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 779065.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-05:01 | 0.00 | 0.00 | 0.00 | -86969.05 | 0.00 | 0.00 | 794.22 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 77990.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 28-MAY-17:02 | 0.00 | 0.00 | 0.00 | -24129.94 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 6108.35 | 0.00 | 205.94 | 17212.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-09:02 | 0.00 | 0.00 | 0.00 | -20949.71 | 0.00 | 0.00 | 17.58 | 28.32 | 464.11 | 13424.10 | 0.00 | 102.33 | 6913.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 08-OCT-13:31 | 0.00 | 0.00 | 0.00 | -24863.44 | 0.00 | 0.00 | 32.20 | 43.94 | 720.19 | 15407.24 | 0.00 | 6.45 | 8653.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 28-MAY-16:22 | 0.00 | 0.00 | 0.00 | -27190.47 | 0.00 | 0.00 | 15.07 | 28.32 | 464.11 | 14845.68 | 0.00 | 139.62 | 11697.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-16:31 | 0.00 | 0.00 | 0.00 | -232768.19 | 0.00 | 0.00 | 370.23 | 439.44 | 7201.84 | 63176.63 | 0.00 | 1578.48 | 160001.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-09:51 | 0.00 | 0.00 | 0.00 | -213698.64 | 0.00 | 0.00 | 180.08 | 283.19 | 4641.14 | 112797.06 | 0.00 | 2192.83 | 93604.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-15:11 | 0.00 | 0.00 | 0.00 | -249291.04 | 0.00 | 0.00 | 305.64 | 439.45 | 7201.95 | 109736.59 | 0.00 | 528.99 | 131078.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -247641.24 | 0.00 | 0.00 | 147.00 | 283.19 | 4641.11 | 138685.61 | 0.00 | 2730.33 | 101154.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-APR-15:51 | 0.00 | 0.00 | 0.00 | -25477.21 | 0.00 | 0.00 | 37.94 | 43.94 | 720.18 | 4810.27 | 0.00 | 313.50 | 19551.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-APR-09:51 | 0.00 | 0.00 | 0.00 | -21574.91 | 0.00 | 0.00 | 19.34 | 28.32 | 464.11 | 11607.02 | 0.00 | 22.71 | 9433.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:01 | 0.00 | 0.00 | 0.00 | -27939.19 | 0.00 | 0.00 | 30.13 | 43.94 | 720.19 | 18396.25 | 0.00 | 57.50 | 8691.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-APR-15:51 | 0.00 | 0.00 | 0.00 | -26572.95 | 0.00 | 0.00 | 14.99 | 28.32 | 464.11 | 14500.38 | 0.00 | 153.45 | 11411.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-21:32 | 0.00 | 0.00 | 0.00 | -7926.92 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 114.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-21:03 | 0.00 | 0.00 | 0.00 | -73431.46 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4688.68 |
DATACENTER_TOP_ZN_6 | 16-APR-21:32 | 0.00 | 0.00 | 0.00 | -7632.77 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -179.25 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-13:05 | 0.00 | 0.00 | 0.00 | -371419.21 | 0.00 | 0.00 | 2282.62 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14653.12 |
GROUNDFLOOR_PLENUM | 05-JUL-05:09 | 0.00 | -25748.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 25727.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 03-JUL-05:12 | 0.00 | -192460.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.72 | 191889.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:50 | 0.00 | -33600.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.59 | 33437.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-05:01 | 0.00 | -146484.70 | 0.00 | -2022218.45 | 0.00 | 0.00 | 14490.13 | 10593.62 | 379706.36 | 45882.28 | 0.00 | 1444.01 | 1716586.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-06:03 | 0.00 | 0.00 | 41054.93 | 0.00 | 0.00 | 0.00 | 11241.25 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -134143.40 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 57778.51 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -64253.50 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 02-JAN-06:03 | 0.00 | 0.00 | 3414.74 | 0.00 | 0.00 | 0.00 | 140.88 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4208.00 | 0.00 | 0.00 | -375.35 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 139644.66 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34624.48 | 0.00 | 0.00 | -113150.50 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 86849.39 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23541.17 | 0.00 | 0.00 | -68547.70 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 129569.39 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38033.43 | 0.00 | 0.00 | -99666.41 |
PERIMETER_MID_ZN_4 | 02-JAN-05:12 | 0.00 | 0.00 | 75633.38 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25078.10 | 0.00 | 0.00 | -55794.74 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 18488.77 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2768.53 | 0.00 | 0.00 | -16533.27 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 11906.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1869.55 | 0.00 | 0.00 | -10560.66 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 18133.75 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2932.09 | 0.00 | 0.00 | -16014.70 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 10801.14 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1966.33 | 0.00 | 0.00 | -9358.75 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-12:25 | 0.00 | 0.00 | 2660.11 | 0.00 | 0.00 | 0.00 | 53.48 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22375.56 |
DATACENTER_TOP_ZN_6 | 01-JAN-14:05 | 0.00 | 0.00 | 352.66 | 0.00 | 0.00 | 0.00 | 6.85 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2325.71 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 11-DEC-05:11 | 12289.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12289.89 |
MIDFLOOR_PLENUM | 04-JUN-16:01 | 71306.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3840.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -75146.97 |
TOPFLOOR_PLENUM | 02-JAN-06:03 | 22113.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22113.51 |
Total Facility | 02-JAN-05:11 | -417524.92 | 410873.81 | 544684.94 | -410873.81 | 0.00 | 0.00 | 0.00 | 10593.62 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -145892.75 | 0.00 | 0.00 | -224286.12 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9140 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.9753 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.6820 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 95.1927 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.0342 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.8880 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.3464 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.3464 | 0.2245 | 1.0000 | Not calculated | 1.2002 | 0.2245 | ||
AIRLOOP DATACENTER BASEMENT | 25.1507 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.1510 | 0.0135 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.4819 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4819 | 0.0324 | 1.0000 | Not calculated | 0.0156 | 0.0324 | ||
AIRLOOP DATACENTER MID | 4.6007 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6007 | 0.0340 | 1.0000 | Not calculated | 0.1563 | 0.0340 | ||
AIRLOOP DATACENTER TOP | 0.4650 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4650 | 0.0336 | 1.0000 | Not calculated | 0.0156 | 0.0336 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4570 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2845 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.3410 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8549 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5171 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2871 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.1507 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.1507 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.4819 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4819 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0324 | ||
AIRLOOP DATACENTER MID | 4.6007 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6007 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0340 | ||
AIRLOOP DATACENTER TOP | 0.4650 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4650 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0336 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.3464 | 5.3464 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9457 | 5.9457 | 1.6172 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.7985 | 56.7985 | 16.1876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8036 | 5.8036 | 1.6192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2930 | 1.2930 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0262 | 1.0262 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3052 | 1.3052 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3439 | 1.3439 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.7324 | 12.7324 | 2.0244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.6907 | 10.6907 | 1.3043 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.7237 | 12.7237 | 2.0358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.7367 | 11.7367 | 1.3028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4264 | 1.4264 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1098 | 1.1098 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4224 | 1.4224 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2720 | 1.2720 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4819 | 0.4819 | 0.4819 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6007 | 4.6007 | 4.6007 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4650 | 0.4650 | 0.4650 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.1507 | 25.1507 | 25.1507 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9140 | 9.9753 | 10.9140 | 2.2845 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.6820 | 95.1927 | 104.6820 | 22.8549 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.0342 | 10.8880 | 11.0342 | 2.2871 | 0.0000 | 1.0000 |
CAV_BAS | 5.3464 | 5.3464 | 5.3464 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.1507 | 25.1510 | 25.1507 | 25.1507 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4819 | 0.4819 | 0.4819 | 0.4819 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6007 | 4.6007 | 4.6007 | 4.6007 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4650 | 0.4650 | 0.4650 | 0.4650 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9728 | 2.9728 | 1.6172 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.3992 | 28.3992 | 16.1876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9018 | 2.9018 | 1.6192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6465 | 0.6465 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5131 | 0.5131 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6526 | 0.6526 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6720 | 0.6720 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3662 | 6.3662 | 2.0244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3454 | 5.3454 | 1.3043 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3619 | 6.3619 | 2.0358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8683 | 5.8683 | 1.3028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7132 | 0.7132 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5549 | 0.5549 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7112 | 0.7112 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6360 | 0.6360 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4819 | 0.4819 | 0.4819 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6007 | 4.6007 | 4.6007 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4650 | 0.4650 | 0.4650 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.1507 | 25.1507 | 25.1507 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4570 | 2.2845 | 2.2845 | 2.2845 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.3410 | 22.8549 | 22.8549 | 22.8549 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5171 | 2.2871 | 2.2871 | 2.2871 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.1507 | 25.1507 | 25.1507 | 25.1507 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4819 | 0.4819 | 0.4819 | 0.4819 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6007 | 4.6007 | 4.6007 | 4.6007 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4650 | 0.4650 | 0.4650 | 0.4650 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 3416.33 |
Number of hours not met | 3416.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 45.55 | 550160.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5872.97 | 567251.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2459.46 | 239082.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 349.31 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3408.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2801.16 | 259488.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 830.42 | 50659.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1733.41 | 84051.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 92.49 | 29206.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 307.72 | 41462.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31735.17 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31735.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.10 |
Space Heating | 0.98 |
Space Cooling | 126.79 |
Fans (All) | 60.47 |
Service Water Heating | 6.64 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 685.12 |
Subtotal | 685.12 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.75 |
Space Heating | 0.14 |
Space Cooling | 18.51 |
Fans (All) | 8.83 |
Service Water Heating | 0.97 |
Receptacle Equipment | 46.25 |
Miscellaneous | 17.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 955. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 3591.00 | 686.67 | 266.00 | 4192.17 | 24.17 |
CORE_BOTTOM | 8440.00 | 320.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8027.67 | 732.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7907.67 | 852.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7924.67 | 835.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7170.50 | 1589.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8421.50 | 338.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8144.83 | 615.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8072.83 | 687.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7739.83 | 1020.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8332.50 | 427.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8114.33 | 645.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8038.83 | 721.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7744.83 | 1015.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7028.00 | 1732.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6471.17 | 2288.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7003.50 | 1756.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8678.33 | 81.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7428.33 | 1331.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8662.67 | 97.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7922.17 | 837.83 | 0.00 | 0.00 | 0.00 |
Min | 3591.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 2288.83 | 266.00 | 4192.17 | 24.17 |
Average | 7755.50 | 809.62 | 11.57 | 182.27 | 1.05 |
Sum | 178376.50 | 18621.17 | 266.00 | 4192.17 | 24.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 165891.50 | 11703.83 | 8781.83 | 178831.17 | 3407.67 |
CORE_BOTTOM | 330202.00 | 611.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330809.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330777.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1623.83 | 644.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1427.50 | 840.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1606.00 | 662.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101032.83 | 2362.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330809.00 | 11703.83 | 8781.83 | 178831.17 | 3407.67 |
Average | 71296.46 | 733.20 | 381.82 | 7775.27 | 148.16 |
Sum | 1639818.67 | 16863.67 | 8781.83 | 178831.17 | 3407.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3371.50 | 940.00 | 200.00 | 2185.17 | 2063.33 |
CORE_BOTTOM | 6463.67 | 2296.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7679.33 | 1080.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7384.67 | 1375.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6718.17 | 2041.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6674.67 | 2085.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6492.83 | 2267.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6223.83 | 2536.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6825.50 | 1934.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6653.00 | 2107.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6508.00 | 2252.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6544.17 | 2215.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6825.00 | 1935.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6689.67 | 2070.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6553.33 | 2206.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6588.33 | 2171.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7737.67 | 1022.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7293.83 | 1466.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7661.83 | 1098.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 6060.00 | 2700.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 4896.33 | 3863.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4528.00 | 4232.00 | 0.00 | 0.00 | 0.00 |
Min | 3371.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4232.00 | 200.00 | 2185.17 | 2063.33 |
Average | 6571.01 | 1995.57 | 8.70 | 95.01 | 89.71 |
Sum | 151133.33 | 45898.17 | 200.00 | 2185.17 | 2063.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 165607.67 | 13008.33 | 6132.50 | 71540.33 | 112327.17 |
CORE_BOTTOM | 326499.17 | 4313.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328764.00 | 2049.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 327996.33 | 2816.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38924.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.33 | 0.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1901.00 | 367.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1703.83 | 564.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1867.83 | 400.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103395.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328764.00 | 13008.33 | 6132.50 | 71540.33 | 112327.17 |
Average | 71051.29 | 1022.75 | 266.63 | 3110.45 | 4883.79 |
Sum | 1634179.67 | 23523.33 | 6132.50 | 71540.33 | 112327.17 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532995E+11 | 104666.38 | 23-JAN-05:11 | 6.33 | 5.49 | 0.566809E+10 | 7499.26 | 13-JAN-10:20 | 6.33 | 5.49 |
February | 0.486762E+11 | 99863.90 | 21-FEB-05:12 | 11.87 | 10.80 | 0.514121E+10 | 7499.27 | 01-FEB-10:20 | 11.87 | 10.80 |
March | 0.486265E+11 | 98367.83 | 06-MAR-05:12 | 15.13 | 13.89 | 0.669433E+10 | 11644.80 | 13-MAR-13:00 | 32.40 | 18.84 |
April | 0.138868E+11 | 100356.77 | 23-APR-05:52 | 20.40 | 17.28 | 0.794789E+10 | 12672.73 | 21-APR-13:00 | 20.40 | 17.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 | 18.24 | 0.975706E+10 | 12727.00 | 05-MAY-13:00 | 42.90 | 20.64 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 | 22.58 | 0.100015E+11 | 13111.00 | 14-JUN-13:00 | 35.80 | 24.44 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.958925E+10 | 13557.90 | 06-JUL-13:00 | 39.90 | 25.44 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 | 26.26 | 0.109733E+11 | 13727.37 | 09-AUG-13:00 | 34.80 | 26.31 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 | 25.91 | 0.955136E+10 | 13615.43 | 01-SEP-13:00 | 32.80 | 26.38 |
October | 0.480300E+11 | 103624.88 | 09-OCT-00:31 | 20.73 | 18.26 | 0.712194E+10 | 12911.76 | 06-OCT-13:00 | 20.73 | 18.26 |
November | 0.630979E+11 | 98375.48 | 20-NOV-05:11 | 12.73 | 11.55 | 0.562083E+10 | 7499.24 | 16-NOV-10:20 | 12.73 | 11.55 |
December | 0.595133E+11 | 100327.06 | 11-DEC-05:11 | 10.13 | 9.51 | 0.547475E+10 | 7499.23 | 18-DEC-10:20 | 20.37 | 13.79 |
Annual Sum or Average | 0.335130E+12 | 0.935415E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.33 | 5.49 | 0.514121E+10 | 7499.23 | 6.33 | 5.49 | ||
Maximum of Months | 0.630979E+11 | 104666.38 | 32.95 | 26.26 | 0.109733E+11 | 13727.37 | 42.90 | 26.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399498E+11 | 90293.14 | 02-JAN-05:11 | 6.47 | 6.24 | 0.507724E+10 | 6734.81 | 04-JAN-10:20 | 13.03 | 10.49 |
February | 0.434919E+11 | 95665.44 | 21-FEB-05:12 | 11.87 | 10.80 | 0.460616E+10 | 6734.82 | 02-FEB-10:39 | 11.87 | 10.80 |
March | 0.657829E+11 | 92597.94 | 06-MAR-05:13 | 15.13 | 13.89 | 0.550025E+10 | 6734.82 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.858319E+11 | 97391.56 | 17-APR-03:03 | 25.38 | 19.61 | 0.488944E+10 | 6741.92 | 27-APR-09:20 | 32.50 | 22.11 |
May | 0.947376E+11 | 97208.16 | 01-MAY-03:03 | 30.53 | 18.79 | 0.530078E+10 | 6761.13 | 15-MAY-13:00 | 35.00 | 22.87 |
June | 0.975489E+11 | 92097.69 | 09-JUN-04:24 | 31.60 | 23.82 | 0.529042E+10 | 6783.62 | 30-JUN-13:00 | 36.90 | 23.24 |
July | 0.101597E+12 | 95079.57 | 06-JUL-03:13 | 31.43 | 25.65 | 0.492069E+10 | 6785.74 | 03-JUL-13:00 | 31.43 | 25.65 |
August | 0.110682E+12 | 98329.10 | 14-AUG-03:03 | 29.15 | 25.88 | 0.551686E+10 | 6771.75 | 02-AUG-13:00 | 29.15 | 25.88 |
September | 0.923415E+11 | 98317.74 | 25-SEP-03:14 | 26.73 | 24.23 | 0.489544E+10 | 6742.33 | 11-SEP-13:39 | 26.73 | 24.23 |
October | 0.744324E+11 | 97333.46 | 30-OCT-04:13 | 16.40 | 14.90 | 0.508470E+10 | 6736.19 | 06-OCT-09:09 | 16.40 | 14.90 |
November | 0.567376E+11 | 96623.13 | 20-NOV-05:11 | 12.73 | 11.55 | 0.503221E+10 | 6734.78 | 16-NOV-10:20 | 12.73 | 11.55 |
December | 0.508429E+11 | 96212.27 | 26-DEC-05:12 | 10.17 | 8.84 | 0.490276E+10 | 6734.79 | 27-DEC-10:20 | 17.47 | 12.54 |
Annual Sum or Average | 0.913976E+12 | 0.610169E+11 | ||||||||
Minimum of Months | 0.399498E+11 | 90293.14 | 6.47 | 6.24 | 0.460616E+10 | 6734.78 | 11.87 | 10.49 | ||
Maximum of Months | 0.110682E+12 | 98329.10 | 31.60 | 25.88 | 0.551686E+10 | 6785.74 | 36.90 | 25.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276763E+11 | 76587.97 | 27-JAN-06:03 | 11.07 | 9.85 | 0.498124E+10 | 6734.76 | 13-JAN-10:20 | 11.07 | 9.85 |
February | 0.317232E+11 | 82242.68 | 27-FEB-05:12 | 11.13 | 10.43 | 0.458324E+10 | 6734.80 | 02-FEB-10:39 | 11.13 | 10.43 |
March | 0.469912E+11 | 84030.59 | 08-MAR-05:12 | 15.77 | 13.75 | 0.549465E+10 | 6734.82 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.530239E+11 | 82884.64 | 11-APR-04:12 | 18.13 | 13.57 | 0.487464E+10 | 6734.81 | 04-APR-09:20 | 18.13 | 13.57 |
May | 0.598495E+11 | 79631.32 | 13-MAY-04:12 | 22.77 | 20.21 | 0.527876E+10 | 6734.79 | 31-MAY-09:20 | 34.17 | 23.02 |
June | 0.576984E+11 | 75511.79 | 12-JUN-05:01 | 34.12 | 19.12 | 0.526482E+10 | 6734.76 | 05-JUN-13:20 | 34.12 | 19.12 |
July | 0.558806E+11 | 68839.61 | 28-JUL-05:02 | 27.02 | 25.79 | 0.488956E+10 | 6734.75 | 06-JUL-09:20 | 27.02 | 25.79 |
August | 0.574978E+11 | 77961.39 | 21-AUG-05:03 | 25.50 | 25.24 | 0.549355E+10 | 6734.72 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.506145E+11 | 81509.50 | 05-SEP-05:03 | 26.20 | 25.15 | 0.487835E+10 | 6734.71 | 11-SEP-13:20 | 31.00 | 26.99 |
October | 0.498625E+11 | 84396.85 | 26-OCT-04:12 | 17.43 | 17.01 | 0.507446E+10 | 6734.76 | 24-OCT-09:20 | 17.43 | 17.01 |
November | 0.411142E+11 | 83814.15 | 10-NOV-05:12 | 16.83 | 15.16 | 0.502011E+10 | 6734.78 | 06-NOV-10:20 | 16.83 | 15.16 |
December | 0.315581E+11 | 80045.28 | 01-DEC-06:02 | 11.02 | 8.79 | 0.486152E+10 | 6734.76 | 27-DEC-10:20 | 17.47 | 12.54 |
Annual Sum or Average | 0.563490E+12 | 0.606949E+11 | ||||||||
Minimum of Months | 0.276763E+11 | 68839.61 | 11.02 | 8.79 | 0.458324E+10 | 6734.71 | 11.07 | 9.85 | ||
Maximum of Months | 0.598495E+11 | 84396.85 | 34.12 | 25.79 | 0.549465E+10 | 6734.82 | 34.17 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214300E+11 | 32438.91 | 26-JAN-16:30 | 19.40 | 12.94 | 0.465287E+10 | 6734.69 | 13-JAN-14:20 | 19.40 | 12.94 |
February | 0.266956E+11 | 77988.58 | 23-FEB-06:02 | 15.05 | 13.57 | 0.448059E+10 | 6734.73 | 15-FEB-10:20 | 15.05 | 13.57 |
March | 0.454055E+11 | 84408.93 | 14-MAR-04:12 | 20.77 | 16.48 | 0.548095E+10 | 6734.81 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.574764E+11 | 84571.67 | 10-APR-05:03 | 18.28 | 13.09 | 0.487812E+10 | 6734.80 | 04-APR-09:20 | 18.28 | 13.09 |
May | 0.682142E+11 | 85728.58 | 30-MAY-04:02 | 30.87 | 21.02 | 0.528595E+10 | 6734.70 | 08-MAY-13:20 | 30.87 | 21.02 |
June | 0.663953E+11 | 86977.92 | 12-JUN-05:01 | 34.12 | 19.12 | 0.526973E+10 | 6734.75 | 05-JUN-13:20 | 34.12 | 19.12 |
July | 0.630094E+11 | 83222.44 | 05-JUL-05:03 | 32.57 | 24.73 | 0.489672E+10 | 6734.68 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.632927E+11 | 85173.62 | 07-AUG-05:04 | 29.53 | 24.79 | 0.549715E+10 | 6734.68 | 16-AUG-09:20 | 25.07 | 24.43 |
September | 0.539944E+11 | 81755.40 | 13-SEP-04:03 | 25.88 | 25.23 | 0.488122E+10 | 6734.68 | 05-SEP-09:20 | 25.88 | 25.23 |
October | 0.490784E+11 | 84307.31 | 10-OCT-04:12 | 19.83 | 18.10 | 0.507174E+10 | 6734.75 | 17-OCT-09:20 | 26.63 | 18.34 |
November | 0.352153E+11 | 79606.80 | 01-NOV-05:02 | 15.60 | 12.04 | 0.497332E+10 | 6734.75 | 06-NOV-10:20 | 23.67 | 17.41 |
December | 0.237863E+11 | 33671.34 | 01-DEC-16:20 | 21.93 | 13.92 | 0.464920E+10 | 6734.72 | 29-DEC-10:20 | 18.10 | 13.45 |
Annual Sum or Average | 0.573993E+12 | 0.600176E+11 | ||||||||
Minimum of Months | 0.214300E+11 | 32438.91 | 15.05 | 12.04 | 0.448059E+10 | 6734.68 | 15.05 | 12.94 | ||
Maximum of Months | 0.682142E+11 | 86977.92 | 34.12 | 25.23 | 0.549715E+10 | 6734.81 | 34.12 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292791E+10 | 4477.59 | 26-JAN-14:10 | 22.35 | 13.84 | 0.604529E+09 | 845.62 | 13-JAN-14:20 | 22.35 | 13.84 |
February | 0.407172E+10 | 6620.84 | 23-FEB-14:30 | 26.10 | 14.00 | 0.567373E+09 | 845.62 | 13-FEB-10:20 | 26.10 | 14.00 |
March | 0.878303E+10 | 16038.35 | 13-MAR-05:02 | 20.77 | 15.50 | 0.689525E+09 | 845.64 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.149809E+11 | 22766.00 | 30-APR-15:02 | 37.88 | 18.24 | 0.614799E+09 | 846.83 | 27-APR-09:20 | 37.88 | 18.24 |
May | 0.192334E+11 | 24129.61 | 28-MAY-17:02 | 41.37 | 19.64 | 0.667044E+09 | 850.14 | 31-MAY-13:50 | 39.95 | 22.45 |
June | 0.201283E+11 | 22193.92 | 11-JUN-15:41 | 43.37 | 23.26 | 0.665810E+09 | 854.62 | 09-JUN-13:00 | 43.37 | 23.26 |
July | 0.199368E+11 | 23357.03 | 04-JUL-17:03 | 39.95 | 24.24 | 0.619245E+09 | 854.87 | 03-JUL-13:00 | 39.95 | 24.24 |
August | 0.200155E+11 | 21019.86 | 06-AUG-14:22 | 36.10 | 26.31 | 0.693592E+09 | 852.27 | 02-AUG-13:00 | 36.10 | 26.31 |
September | 0.153295E+11 | 21018.91 | 24-SEP-15:52 | 34.80 | 25.26 | 0.615186E+09 | 846.66 | 13-SEP-13:00 | 34.80 | 25.26 |
October | 0.108253E+11 | 21243.15 | 08-OCT-14:51 | 32.40 | 18.84 | 0.638391E+09 | 845.62 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.597151E+10 | 7269.82 | 09-NOV-14:20 | 29.33 | 17.81 | 0.628531E+09 | 845.62 | 16-NOV-10:20 | 22.00 | 16.54 |
December | 0.388337E+10 | 5413.28 | 26-DEC-14:10 | 22.68 | 14.39 | 0.601237E+09 | 845.62 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.146087E+12 | 0.760526E+10 | ||||||||
Minimum of Months | 0.292791E+10 | 4477.59 | 20.77 | 13.84 | 0.567373E+09 | 845.62 | 19.70 | 13.84 | ||
Maximum of Months | 0.201283E+11 | 24129.61 | 43.37 | 26.31 | 0.693592E+09 | 854.87 | 43.37 | 26.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254166E+10 | 4411.40 | 26-JAN-10:20 | 18.10 | 12.94 | 0.402527E+09 | 544.95 | 04-JAN-10:39 | 18.10 | 12.94 |
February | 0.365730E+10 | 9022.16 | 20-FEB-10:13 | 20.20 | 12.52 | 0.368919E+09 | 544.96 | 02-FEB-10:39 | 20.20 | 12.52 |
March | 0.755366E+10 | 17212.89 | 12-MAR-11:02 | 28.45 | 18.09 | 0.444932E+09 | 545.15 | 28-MAR-09:00 | 28.40 | 17.95 |
April | 0.125831E+11 | 20312.29 | 30-APR-09:43 | 30.90 | 15.93 | 0.396591E+09 | 558.16 | 28-APR-09:30 | 30.90 | 15.93 |
May | 0.159398E+11 | 20953.44 | 29-MAY-09:02 | 34.05 | 21.14 | 0.431042E+09 | 575.33 | 03-MAY-09:30 | 34.05 | 21.14 |
June | 0.150124E+11 | 18335.02 | 11-JUN-09:42 | 36.22 | 25.04 | 0.430059E+09 | 581.87 | 12-JUN-09:39 | 39.50 | 22.03 |
July | 0.139306E+11 | 19560.50 | 04-JUL-09:43 | 34.98 | 25.17 | 0.399312E+09 | 562.21 | 07-JUL-09:50 | 36.70 | 24.48 |
August | 0.136260E+11 | 17347.54 | 06-AUG-09:42 | 32.08 | 25.07 | 0.447028E+09 | 549.43 | 02-AUG-13:00 | 32.08 | 25.07 |
September | 0.116754E+11 | 17301.20 | 24-SEP-09:52 | 31.10 | 25.26 | 0.396602E+09 | 545.69 | 13-SEP-13:00 | 31.10 | 25.26 |
October | 0.887917E+10 | 17869.36 | 09-OCT-10:32 | 29.13 | 20.48 | 0.411875E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.496001E+10 | 9262.43 | 05-NOV-10:32 | 24.63 | 16.65 | 0.405953E+09 | 544.95 | 16-NOV-10:20 | 22.00 | 16.54 |
December | 0.299486E+10 | 4989.61 | 01-DEC-10:00 | 18.30 | 11.37 | 0.390676E+09 | 544.95 | 18-DEC-10:20 | 20.37 | 13.79 |
Annual Sum or Average | 0.113354E+12 | 0.492552E+10 | ||||||||
Minimum of Months | 0.254166E+10 | 4411.40 | 18.10 | 11.37 | 0.368919E+09 | 544.95 | 18.10 | 12.52 | ||
Maximum of Months | 0.159398E+11 | 20953.44 | 36.22 | 25.26 | 0.447028E+09 | 581.87 | 39.50 | 25.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.736596E+10 | 13538.42 | 12-JAN-13:50 | 23.12 | 13.90 | 0.624904E+09 | 845.91 | 12-JAN-14:50 | 23.55 | 14.16 |
February | 0.871879E+10 | 24067.26 | 20-FEB-13:32 | 26.23 | 13.43 | 0.573551E+09 | 846.17 | 07-FEB-14:00 | 26.23 | 13.43 |
March | 0.140789E+11 | 22967.85 | 05-MAR-13:42 | 28.68 | 17.18 | 0.691199E+09 | 851.69 | 28-MAR-13:00 | 35.00 | 18.14 |
April | 0.181224E+11 | 24203.61 | 30-APR-13:03 | 36.98 | 18.66 | 0.615318E+09 | 854.93 | 27-APR-13:50 | 36.98 | 18.66 |
May | 0.196175E+11 | 24376.33 | 28-MAY-15:02 | 42.22 | 19.09 | 0.667093E+09 | 850.47 | 15-MAY-13:00 | 42.22 | 19.09 |
June | 0.195111E+11 | 22332.28 | 11-JUN-15:41 | 43.37 | 23.26 | 0.665736E+09 | 854.88 | 30-JUN-13:00 | 36.90 | 23.24 |
July | 0.194105E+11 | 23193.98 | 04-JUL-13:03 | 38.42 | 25.08 | 0.619184E+09 | 855.13 | 10-JUL-13:00 | 39.20 | 26.55 |
August | 0.202463E+11 | 21635.35 | 06-AUG-13:42 | 35.80 | 26.36 | 0.693645E+09 | 852.61 | 02-AUG-13:00 | 35.80 | 26.36 |
September | 0.178354E+11 | 22641.71 | 24-SEP-13:12 | 34.77 | 24.64 | 0.616389E+09 | 897.57 | 28-SEP-13:50 | 35.43 | 22.76 |
October | 0.178537E+11 | 24862.66 | 08-OCT-13:31 | 32.20 | 18.87 | 0.643423E+09 | 922.76 | 02-OCT-13:39 | 32.20 | 18.87 |
November | 0.140906E+11 | 23314.22 | 26-NOV-11:42 | 24.83 | 14.08 | 0.633193E+09 | 866.93 | 13-NOV-14:09 | 24.83 | 14.08 |
December | 0.931942E+10 | 22589.56 | 24-DEC-13:23 | 23.40 | 13.38 | 0.611235E+09 | 846.20 | 06-DEC-14:00 | 23.40 | 13.38 |
Annual Sum or Average | 0.186171E+12 | 0.765487E+10 | ||||||||
Minimum of Months | 0.736596E+10 | 13538.42 | 23.12 | 13.38 | 0.573551E+09 | 845.91 | 23.40 | 13.38 | ||
Maximum of Months | 0.202463E+11 | 24862.66 | 43.37 | 26.36 | 0.693645E+09 | 922.76 | 42.22 | 26.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366257E+10 | 7335.19 | 31-JAN-15:50 | 21.15 | 11.24 | 0.404838E+09 | 544.95 | 04-JAN-10:39 | 21.15 | 11.24 |
February | 0.559665E+10 | 23056.75 | 20-FEB-14:52 | 26.30 | 14.02 | 0.372684E+09 | 544.96 | 02-FEB-10:39 | 26.30 | 14.02 |
March | 0.114817E+11 | 22960.84 | 05-MAR-14:22 | 28.95 | 17.44 | 0.446320E+09 | 544.97 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.171522E+11 | 26966.36 | 02-APR-15:41 | 33.88 | 20.63 | 0.397043E+09 | 545.93 | 27-APR-09:20 | 32.50 | 22.11 |
May | 0.160549E+11 | 27188.50 | 28-MAY-16:22 | 42.00 | 19.52 | 0.430286E+09 | 548.69 | 15-MAY-13:00 | 42.00 | 19.52 |
June | 0.169677E+11 | 24706.45 | 11-JUN-15:41 | 43.37 | 23.26 | 0.429696E+09 | 552.41 | 09-JUN-13:00 | 43.37 | 23.26 |
July | 0.163947E+11 | 24631.83 | 04-JUL-16:23 | 39.80 | 24.49 | 0.399525E+09 | 552.66 | 03-JUL-13:00 | 39.80 | 24.49 |
August | 0.173474E+11 | 22981.67 | 06-AUG-15:02 | 36.30 | 26.24 | 0.447461E+09 | 550.24 | 02-AUG-13:00 | 36.30 | 26.24 |
September | 0.117196E+11 | 22765.69 | 24-SEP-15:52 | 34.80 | 25.26 | 0.396629E+09 | 545.67 | 13-SEP-13:00 | 34.80 | 25.26 |
October | 0.112627E+11 | 24669.02 | 08-OCT-14:51 | 32.40 | 18.84 | 0.412604E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.865072E+10 | 19707.90 | 06-NOV-05:12 | 14.67 | 13.54 | 0.408227E+09 | 544.96 | 15-NOV-14:39 | 26.43 | 17.71 |
December | 0.672454E+10 | 18695.64 | 24-DEC-15:23 | 23.45 | 13.85 | 0.397256E+09 | 544.95 | 18-DEC-10:20 | 23.45 | 13.85 |
Annual Sum or Average | 0.143015E+12 | 0.494257E+10 | ||||||||
Minimum of Months | 0.366257E+10 | 7335.19 | 14.67 | 11.24 | 0.372684E+09 | 544.95 | 21.15 | 11.24 | ||
Maximum of Months | 0.173474E+11 | 27188.50 | 43.37 | 26.24 | 0.447461E+09 | 552.66 | 43.37 | 26.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192279E+10 | 2846.02 | 26-JAN-15:00 | 21.60 | 13.66 | 0.536768E+09 | 845.61 | 26-JAN-14:20 | 21.60 | 13.66 |
February | 0.274231E+10 | 5400.24 | 24-FEB-15:00 | 26.40 | 17.38 | 0.537653E+09 | 845.62 | 24-FEB-14:20 | 26.40 | 17.38 |
March | 0.623666E+10 | 11325.01 | 29-MAR-04:12 | 21.40 | 17.71 | 0.683782E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.108483E+11 | 21214.87 | 02-APR-15:41 | 33.88 | 20.63 | 0.613877E+09 | 845.63 | 17-APR-09:20 | 31.40 | 21.81 |
May | 0.152149E+11 | 23274.44 | 29-MAY-16:31 | 41.03 | 21.41 | 0.665903E+09 | 845.65 | 04-MAY-09:30 | 41.03 | 21.41 |
June | 0.153893E+11 | 21843.75 | 11-JUN-16:21 | 43.25 | 23.12 | 0.663554E+09 | 845.65 | 12-JUN-09:30 | 39.25 | 21.97 |
July | 0.139826E+11 | 21642.27 | 02-JUL-17:01 | 40.18 | 26.57 | 0.617445E+09 | 845.64 | 07-JUL-09:30 | 36.30 | 24.34 |
August | 0.133050E+11 | 21661.76 | 27-AUG-14:32 | 35.53 | 29.11 | 0.692021E+09 | 845.62 | 21-AUG-13:20 | 35.53 | 29.11 |
September | 0.102588E+11 | 21373.89 | 17-SEP-14:51 | 34.20 | 26.01 | 0.614360E+09 | 845.62 | 08-SEP-13:20 | 34.20 | 26.01 |
October | 0.765349E+10 | 21206.69 | 01-OCT-15:11 | 35.83 | 20.00 | 0.636546E+09 | 845.62 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.405825E+10 | 5982.28 | 09-NOV-14:30 | 29.30 | 17.79 | 0.614115E+09 | 845.62 | 06-NOV-10:20 | 29.30 | 17.79 |
December | 0.226333E+10 | 2621.52 | 28-DEC-15:30 | 24.15 | 15.30 | 0.543161E+09 | 845.62 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.103876E+12 | 0.741919E+10 | ||||||||
Minimum of Months | 0.192279E+10 | 2621.52 | 21.40 | 13.66 | 0.536768E+09 | 845.61 | 19.70 | 13.66 | ||
Maximum of Months | 0.153893E+11 | 23274.44 | 43.25 | 29.11 | 0.692021E+09 | 845.65 | 41.03 | 29.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147047E+10 | 5241.57 | 26-JAN-11:05 | 19.98 | 13.28 | 0.280407E+09 | 548.49 | 05-JAN-11:09 | 19.98 | 13.28 |
February | 0.273562E+10 | 8030.34 | 22-FEB-11:05 | 23.90 | 14.68 | 0.267061E+09 | 548.49 | 15-FEB-11:09 | 23.90 | 14.68 |
March | 0.644795E+10 | 18512.21 | 12-MAR-10:02 | 26.28 | 17.32 | 0.327447E+09 | 548.50 | 27-MAR-10:09 | 25.97 | 17.24 |
April | 0.106559E+11 | 19109.41 | 16-APR-09:22 | 33.85 | 21.42 | 0.293184E+09 | 548.82 | 28-APR-10:09 | 33.92 | 18.49 |
May | 0.133578E+11 | 21379.81 | 29-MAY-09:51 | 35.80 | 22.19 | 0.317552E+09 | 548.84 | 03-MAY-10:09 | 35.80 | 22.19 |
June | 0.120733E+11 | 18818.96 | 11-JUN-10:22 | 37.75 | 25.19 | 0.315869E+09 | 548.84 | 05-JUN-10:09 | 37.75 | 25.19 |
July | 0.103050E+11 | 18639.72 | 04-JUL-10:32 | 36.00 | 24.99 | 0.294915E+09 | 548.61 | 07-JUL-10:09 | 37.08 | 24.60 |
August | 0.969969E+10 | 18274.73 | 06-AUG-09:31 | 31.87 | 24.94 | 0.329236E+09 | 548.48 | 21-AUG-12:09 | 30.20 | 27.51 |
September | 0.820924E+10 | 18290.30 | 17-SEP-14:51 | 34.20 | 26.01 | 0.292989E+09 | 548.49 | 14-SEP-12:09 | 34.20 | 26.01 |
October | 0.715350E+10 | 19392.68 | 01-OCT-09:52 | 29.70 | 19.34 | 0.304499E+09 | 548.50 | 10-OCT-14:09 | 31.67 | 20.72 |
November | 0.400307E+10 | 8475.72 | 01-NOV-10:05 | 23.77 | 15.01 | 0.297908E+09 | 548.49 | 15-NOV-15:09 | 26.45 | 17.85 |
December | 0.180417E+10 | 5543.74 | 01-DEC-11:05 | 20.45 | 12.21 | 0.278185E+09 | 548.49 | 18-DEC-11:09 | 21.85 | 14.75 |
Annual Sum or Average | 0.879158E+11 | 0.359925E+10 | ||||||||
Minimum of Months | 0.147047E+10 | 5241.57 | 19.98 | 12.21 | 0.267061E+09 | 548.48 | 19.98 | 13.28 | ||
Maximum of Months | 0.133578E+11 | 21379.81 | 37.75 | 26.01 | 0.329236E+09 | 548.84 | 37.75 | 27.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662981E+10 | 15234.43 | 08-JAN-15:53 | 22.20 | 14.15 | 0.612990E+09 | 845.88 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.782650E+10 | 22893.54 | 19-FEB-14:32 | 25.73 | 14.25 | 0.566869E+09 | 846.39 | 23-FEB-14:20 | 26.20 | 13.97 |
March | 0.122541E+11 | 23545.43 | 12-MAR-13:22 | 30.95 | 19.20 | 0.689890E+09 | 853.52 | 28-MAR-13:00 | 35.00 | 18.14 |
April | 0.145662E+11 | 22676.87 | 02-APR-15:41 | 33.88 | 20.63 | 0.614818E+09 | 846.63 | 05-APR-13:20 | 31.97 | 17.64 |
May | 0.160502E+11 | 23408.95 | 29-MAY-15:51 | 41.30 | 21.57 | 0.666049E+09 | 846.73 | 30-MAY-13:20 | 39.27 | 24.02 |
June | 0.152485E+11 | 21723.19 | 11-JUN-16:21 | 43.25 | 23.12 | 0.663563E+09 | 846.82 | 05-JUN-13:20 | 43.25 | 23.12 |
July | 0.141110E+11 | 21581.95 | 02-JUL-16:21 | 40.35 | 26.46 | 0.617479E+09 | 846.78 | 06-JUL-13:20 | 39.70 | 25.48 |
August | 0.142729E+11 | 22220.87 | 27-AUG-14:32 | 35.53 | 29.11 | 0.692202E+09 | 846.68 | 08-AUG-13:20 | 35.53 | 29.11 |
September | 0.134934E+11 | 23200.64 | 17-SEP-14:51 | 34.20 | 26.01 | 0.615322E+09 | 875.36 | 28-SEP-13:50 | 35.43 | 22.76 |
October | 0.158402E+11 | 24929.58 | 01-OCT-15:11 | 35.83 | 20.00 | 0.643210E+09 | 916.26 | 02-OCT-13:00 | 36.40 | 21.05 |
November | 0.132480E+11 | 24738.88 | 12-NOV-13:41 | 28.12 | 16.00 | 0.632588E+09 | 880.73 | 01-NOV-13:50 | 28.12 | 16.00 |
December | 0.783554E+10 | 22947.34 | 03-DEC-13:02 | 24.08 | 14.17 | 0.603294E+09 | 845.99 | 01-DEC-14:20 | 24.08 | 14.17 |
Annual Sum or Average | 0.151376E+12 | 0.761827E+10 | ||||||||
Minimum of Months | 0.662981E+10 | 15234.43 | 22.20 | 14.15 | 0.566869E+09 | 845.88 | 23.40 | 13.97 | ||
Maximum of Months | 0.160502E+11 | 24929.58 | 43.25 | 29.11 | 0.692202E+09 | 916.26 | 43.25 | 29.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199265E+10 | 5160.11 | 31-JAN-16:10 | 20.95 | 11.21 | 0.369641E+09 | 544.95 | 27-JAN-14:20 | 20.95 | 11.21 |
February | 0.300224E+10 | 9525.37 | 20-FEB-16:23 | 25.10 | 14.37 | 0.357831E+09 | 544.95 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.697507E+10 | 20429.28 | 12-MAR-14:42 | 31.45 | 19.56 | 0.444259E+09 | 544.97 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.115310E+11 | 22829.35 | 02-APR-16:21 | 33.70 | 20.58 | 0.396515E+09 | 544.96 | 17-APR-09:20 | 31.40 | 21.81 |
May | 0.138844E+11 | 24764.79 | 28-MAY-16:31 | 41.90 | 19.53 | 0.429621E+09 | 544.97 | 04-MAY-09:30 | 41.90 | 19.53 |
June | 0.134852E+11 | 21971.11 | 11-JUN-16:21 | 43.25 | 23.12 | 0.428023E+09 | 544.97 | 12-JUN-09:30 | 39.25 | 21.97 |
July | 0.111931E+11 | 21635.56 | 02-JUL-16:21 | 40.35 | 26.46 | 0.398274E+09 | 544.97 | 07-JUL-09:30 | 36.30 | 24.34 |
August | 0.108549E+11 | 21249.29 | 06-AUG-16:11 | 36.20 | 26.31 | 0.446350E+09 | 544.95 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.896559E+10 | 21432.87 | 17-SEP-14:51 | 34.20 | 26.01 | 0.396444E+09 | 544.95 | 08-SEP-13:20 | 34.20 | 26.01 |
October | 0.766160E+10 | 22408.80 | 01-OCT-15:11 | 35.83 | 20.00 | 0.411767E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.462661E+10 | 19731.19 | 12-NOV-15:02 | 28.08 | 15.73 | 0.403097E+09 | 544.95 | 17-NOV-14:50 | 28.03 | 17.85 |
December | 0.237873E+10 | 5862.74 | 01-DEC-15:30 | 22.85 | 13.56 | 0.371115E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.965510E+11 | 0.485294E+10 | ||||||||
Minimum of Months | 0.199265E+10 | 5160.11 | 20.95 | 11.21 | 0.357831E+09 | 544.95 | 19.70 | 11.21 | ||
Maximum of Months | 0.138844E+11 | 24764.79 | 43.25 | 26.46 | 0.446350E+09 | 544.97 | 41.90 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147567E+10 | 2762.60 | 26-JAN-15:00 | 21.60 | 13.66 | 0.514445E+09 | 845.61 | 26-JAN-14:20 | 21.60 | 13.66 |
February | 0.243983E+10 | 5646.83 | 23-FEB-14:50 | 25.90 | 14.07 | 0.519066E+09 | 845.62 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.620753E+10 | 20724.24 | 12-MAR-15:31 | 31.37 | 19.80 | 0.676929E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.115014E+11 | 25474.39 | 30-APR-15:51 | 37.80 | 18.20 | 0.613824E+09 | 845.63 | 04-APR-09:20 | 37.80 | 18.20 |
May | 0.164679E+11 | 25363.68 | 21-MAY-16:11 | 34.70 | 23.74 | 0.666072E+09 | 845.62 | 08-MAY-13:20 | 34.70 | 23.74 |
June | 0.165625E+11 | 24983.99 | 11-JUN-15:41 | 43.37 | 23.26 | 0.663648E+09 | 845.63 | 05-JUN-13:20 | 43.37 | 23.26 |
July | 0.150381E+11 | 24787.53 | 02-JUL-17:01 | 40.18 | 26.57 | 0.617631E+09 | 845.61 | 07-JUL-13:20 | 39.97 | 24.71 |
August | 0.140295E+11 | 23748.78 | 06-AUG-15:42 | 36.30 | 26.24 | 0.692106E+09 | 845.61 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.107071E+11 | 24625.22 | 17-SEP-14:51 | 34.20 | 26.01 | 0.614459E+09 | 845.62 | 08-SEP-13:20 | 34.20 | 26.01 |
October | 0.767075E+10 | 23563.13 | 01-OCT-15:21 | 35.75 | 20.04 | 0.634420E+09 | 845.62 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.368117E+10 | 6463.39 | 09-NOV-14:40 | 29.27 | 17.76 | 0.598912E+09 | 845.62 | 15-NOV-14:20 | 26.37 | 17.60 |
December | 0.176031E+10 | 2526.28 | 28-DEC-16:00 | 23.80 | 15.20 | 0.515379E+09 | 845.61 | 29-DEC-14:00 | 19.50 | 14.92 |
Annual Sum or Average | 0.107542E+12 | 0.732689E+10 | ||||||||
Minimum of Months | 0.147567E+10 | 2526.28 | 21.60 | 13.66 | 0.514445E+09 | 845.61 | 19.50 | 13.66 | ||
Maximum of Months | 0.165625E+11 | 25474.39 | 43.37 | 26.57 | 0.692106E+09 | 845.63 | 43.37 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140546E+10 | 2976.92 | 26-JAN-14:20 | 22.20 | 13.80 | 0.364942E+09 | 544.95 | 13-JAN-14:20 | 22.20 | 13.80 |
February | 0.260270E+10 | 6152.78 | 23-FEB-10:40 | 22.80 | 14.32 | 0.356518E+09 | 544.95 | 15-FEB-14:20 | 22.80 | 14.32 |
March | 0.662324E+10 | 19122.45 | 12-MAR-10:12 | 26.67 | 17.47 | 0.443096E+09 | 544.97 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.113265E+11 | 21573.36 | 30-APR-09:51 | 31.40 | 16.16 | 0.396413E+09 | 545.23 | 28-APR-09:50 | 31.40 | 16.16 |
May | 0.144489E+11 | 20258.51 | 29-MAY-09:22 | 34.75 | 21.56 | 0.429635E+09 | 549.30 | 04-MAY-09:39 | 34.75 | 21.56 |
June | 0.130969E+11 | 19737.16 | 11-JUN-10:22 | 37.75 | 25.19 | 0.427942E+09 | 554.09 | 12-JUN-09:50 | 39.75 | 22.08 |
July | 0.112597E+11 | 19506.27 | 04-JUL-10:32 | 36.00 | 24.99 | 0.398219E+09 | 545.05 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.104423E+11 | 18590.31 | 06-AUG-15:02 | 36.30 | 26.24 | 0.446189E+09 | 545.06 | 07-AUG-09:00 | 33.20 | 25.77 |
September | 0.876576E+10 | 19545.62 | 17-SEP-14:51 | 34.20 | 26.01 | 0.396246E+09 | 544.95 | 08-SEP-13:20 | 34.20 | 26.01 |
October | 0.739889E+10 | 19719.40 | 01-OCT-11:21 | 32.90 | 19.80 | 0.411005E+09 | 544.95 | 17-OCT-09:20 | 26.63 | 18.34 |
November | 0.383703E+10 | 6412.22 | 09-NOV-10:20 | 25.33 | 18.04 | 0.400472E+09 | 544.96 | 06-NOV-14:00 | 25.33 | 18.04 |
December | 0.158175E+10 | 3017.95 | 01-DEC-10:40 | 19.57 | 11.89 | 0.366048E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.927891E+11 | 0.483672E+10 | ||||||||
Minimum of Months | 0.140546E+10 | 2976.92 | 19.57 | 11.89 | 0.356518E+09 | 544.95 | 19.70 | 13.80 | ||
Maximum of Months | 0.144489E+11 | 21573.36 | 37.75 | 26.24 | 0.446189E+09 | 554.09 | 39.75 | 26.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547009E+10 | 13405.94 | 12-JAN-14:20 | 23.40 | 14.05 | 0.594577E+09 | 845.64 | 25-JAN-14:20 | 22.93 | 13.01 |
February | 0.711005E+10 | 26165.68 | 20-FEB-14:12 | 26.37 | 13.66 | 0.555719E+09 | 845.91 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.121211E+11 | 26456.12 | 12-MAR-13:32 | 31.03 | 19.26 | 0.686643E+09 | 846.04 | 08-MAR-14:50 | 31.03 | 19.26 |
April | 0.152076E+11 | 26781.66 | 30-APR-14:31 | 37.73 | 18.38 | 0.614775E+09 | 845.92 | 21-APR-13:00 | 37.73 | 18.38 |
May | 0.173007E+11 | 25397.59 | 21-MAY-16:11 | 34.70 | 23.74 | 0.666176E+09 | 845.92 | 19-MAY-13:50 | 34.70 | 23.74 |
June | 0.164168E+11 | 24893.97 | 11-JUN-15:41 | 43.37 | 23.26 | 0.663643E+09 | 845.96 | 07-JUN-13:09 | 43.37 | 23.26 |
July | 0.151630E+11 | 24679.76 | 02-JUL-16:21 | 40.35 | 26.46 | 0.617651E+09 | 845.76 | 07-JUL-13:00 | 40.30 | 24.54 |
August | 0.149925E+11 | 24125.65 | 06-AUG-14:22 | 36.10 | 26.31 | 0.692266E+09 | 845.82 | 08-AUG-13:00 | 36.60 | 26.49 |
September | 0.139506E+11 | 26532.34 | 17-SEP-14:51 | 34.20 | 26.01 | 0.615066E+09 | 853.83 | 28-SEP-13:50 | 35.43 | 22.76 |
October | 0.158290E+11 | 27939.13 | 01-OCT-12:01 | 34.03 | 19.84 | 0.640132E+09 | 891.72 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.124654E+11 | 27524.26 | 05-NOV-13:41 | 29.32 | 17.20 | 0.626566E+09 | 847.85 | 01-NOV-13:50 | 29.32 | 17.20 |
December | 0.645993E+10 | 15240.56 | 01-DEC-13:50 | 23.35 | 13.02 | 0.588630E+09 | 845.90 | 01-DEC-14:00 | 23.40 | 13.35 |
Annual Sum or Average | 0.152487E+12 | 0.756184E+10 | ||||||||
Minimum of Months | 0.547009E+10 | 13405.94 | 23.35 | 13.02 | 0.555719E+09 | 845.64 | 22.93 | 13.01 | ||
Maximum of Months | 0.173007E+11 | 27939.13 | 43.37 | 26.46 | 0.692266E+09 | 891.72 | 43.37 | 26.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169126E+10 | 5073.77 | 12-JAN-15:50 | 23.35 | 14.44 | 0.356015E+09 | 544.95 | 13-JAN-14:20 | 21.30 | 15.27 |
February | 0.277345E+10 | 11885.55 | 20-FEB-16:12 | 25.27 | 14.30 | 0.347879E+09 | 544.95 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.692926E+10 | 23502.18 | 12-MAR-16:11 | 31.07 | 19.87 | 0.441895E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.119113E+11 | 26570.87 | 30-APR-15:51 | 37.80 | 18.20 | 0.396512E+09 | 544.96 | 04-APR-09:20 | 37.80 | 18.20 |
May | 0.146743E+11 | 25380.54 | 21-MAY-16:11 | 34.70 | 23.74 | 0.429669E+09 | 544.95 | 08-MAY-13:20 | 34.70 | 23.74 |
June | 0.142023E+11 | 24107.71 | 11-JUN-15:41 | 43.37 | 23.26 | 0.428030E+09 | 544.96 | 05-JUN-13:20 | 43.37 | 23.26 |
July | 0.118633E+11 | 23833.12 | 02-JUL-16:21 | 40.35 | 26.46 | 0.398340E+09 | 544.94 | 11-JUL-09:20 | 28.23 | 25.15 |
August | 0.112482E+11 | 22522.18 | 06-AUG-16:22 | 36.15 | 26.34 | 0.446364E+09 | 544.95 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.925465E+10 | 23682.68 | 17-SEP-14:51 | 34.20 | 26.01 | 0.396463E+09 | 544.95 | 08-SEP-13:20 | 34.20 | 26.01 |
October | 0.766319E+10 | 23507.12 | 15-OCT-15:31 | 32.27 | 19.28 | 0.411196E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.433385E+10 | 21515.96 | 05-NOV-15:42 | 28.08 | 17.72 | 0.396888E+09 | 544.96 | 06-NOV-14:00 | 28.40 | 18.16 |
December | 0.198269E+10 | 5718.35 | 28-DEC-15:40 | 24.03 | 15.27 | 0.356124E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.985277E+11 | 0.480537E+10 | ||||||||
Minimum of Months | 0.169126E+10 | 5073.77 | 23.35 | 14.30 | 0.347879E+09 | 544.94 | 19.70 | 14.83 | ||
Maximum of Months | 0.146743E+11 | 26570.87 | 43.37 | 26.46 | 0.446364E+09 | 544.96 | 43.37 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169424E+10 | 3146.43 | 12-JAN-17:00 | 22.30 | 14.53 | 0.00 | 0.00 | 01-JAN-00:10 | 22.30 | 14.53 |
February | 0.391946E+10 | 9583.00 | 21-FEB-06:15 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.976405E+10 | 14001.57 | 14-MAR-05:10 | 20.70 | 16.42 | 0.00 | 0.00 | 01-MAR-00:10 | 20.70 | 16.42 |
April | 0.170030E+11 | 20197.78 | 17-APR-05:15 | 24.33 | 18.88 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 18.88 |
May | 0.216075E+11 | 24603.89 | 30-MAY-05:15 | 30.30 | 21.64 | 0.00 | 0.00 | 01-MAY-00:10 | 30.30 | 21.64 |
June | 0.216873E+11 | 25030.96 | 12-JUN-05:10 | 34.12 | 19.12 | 0.00 | 0.00 | 01-JUN-00:10 | 34.12 | 19.12 |
July | 0.209341E+11 | 25750.77 | 05-JUL-05:09 | 32.57 | 24.73 | 0.00 | 0.00 | 01-JUL-00:10 | 32.57 | 24.73 |
August | 0.213546E+11 | 24308.78 | 07-AUG-05:09 | 29.53 | 24.79 | 0.00 | 0.00 | 01-AUG-00:10 | 29.53 | 24.79 |
September | 0.166579E+11 | 19560.97 | 18-SEP-05:15 | 26.73 | 24.13 | 0.00 | 0.00 | 01-SEP-00:10 | 26.73 | 24.13 |
October | 0.131032E+11 | 19928.09 | 02-OCT-05:12 | 21.80 | 17.53 | 0.00 | 0.00 | 01-OCT-00:10 | 21.80 | 17.53 |
November | 0.760924E+10 | 11749.02 | 13-NOV-06:15 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 15.27 | 12.05 |
December | 0.386082E+10 | 7126.93 | 26-DEC-06:08 | 10.17 | 8.52 | 0.00 | 0.00 | 01-DEC-00:10 | 10.17 | 8.52 |
Annual Sum or Average | 0.159195E+12 | 0.00 | ||||||||
Minimum of Months | 0.169424E+10 | 3146.43 | 10.17 | 8.52 | 0.00 | 0.00 | 10.17 | 8.52 | ||
Maximum of Months | 0.216873E+11 | 25750.77 | 34.12 | 24.79 | 0.00 | 0.00 | 34.12 | 24.79 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576157E+09 | 2766.60 | 02-JAN-05:11 | 6.47 | 6.24 | 0.00 | 0.00 | 01-JAN-00:10 | 6.47 | 6.24 |
February | 0.201061E+10 | 4990.53 | 22-FEB-16:50 | 25.83 | 15.78 | 0.00 | 0.00 | 01-FEB-00:10 | 25.83 | 15.78 |
March | 0.671374E+10 | 10144.22 | 13-MAR-05:02 | 20.77 | 15.50 | 0.00 | 0.00 | 01-MAR-00:10 | 20.77 | 15.50 |
April | 0.117602E+11 | 14438.32 | 17-APR-05:03 | 24.22 | 18.83 | 0.00 | 0.00 | 01-APR-00:10 | 24.22 | 18.83 |
May | 0.154778E+11 | 18259.23 | 30-MAY-05:15 | 30.30 | 21.64 | 0.00 | 0.00 | 01-MAY-00:10 | 30.30 | 21.64 |
June | 0.150280E+11 | 18996.55 | 12-JUN-05:13 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.133402E+11 | 19247.43 | 03-JUL-05:12 | 29.33 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 29.33 | 24.63 |
August | 0.127000E+11 | 14352.31 | 08-AUG-05:01 | 30.10 | 25.30 | 0.00 | 0.00 | 01-AUG-00:10 | 30.10 | 25.30 |
September | 0.102394E+11 | 13590.77 | 18-SEP-05:02 | 26.72 | 24.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.72 | 24.18 |
October | 0.904390E+10 | 13130.08 | 02-OCT-05:12 | 21.80 | 17.53 | 0.00 | 0.00 | 01-OCT-00:10 | 21.80 | 17.53 |
November | 0.477631E+10 | 7082.61 | 09-NOV-06:12 | 17.67 | 16.00 | 0.00 | 0.00 | 01-NOV-00:10 | 17.67 | 16.00 |
December | 0.121800E+10 | 3177.89 | 01-DEC-06:10 | 11.02 | 8.79 | 0.00 | 0.00 | 01-DEC-00:10 | 11.02 | 8.79 |
Annual Sum or Average | 0.102884E+12 | 0.00 | ||||||||
Minimum of Months | 0.576157E+09 | 2766.60 | 6.47 | 6.24 | 0.00 | 0.00 | 6.47 | 6.24 | ||
Maximum of Months | 0.154778E+11 | 19247.43 | 34.23 | 25.30 | 0.00 | 0.00 | 34.23 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108145E+10 | 5988.96 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.340857E+10 | 13172.40 | 22-FEB-15:05 | 27.00 | 16.16 | 0.00 | 0.00 | 01-FEB-00:10 | 27.00 | 16.16 |
March | 0.105369E+11 | 22046.25 | 28-MAR-15:40 | 35.53 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 35.53 | 18.66 |
April | 0.199504E+11 | 27656.18 | 28-APR-15:00 | 39.20 | 20.99 | 0.00 | 0.00 | 01-APR-00:10 | 39.20 | 20.99 |
May | 0.265789E+11 | 31738.75 | 01-MAY-14:30 | 44.00 | 22.05 | 0.00 | 0.00 | 01-MAY-00:10 | 44.00 | 22.05 |
June | 0.264737E+11 | 33599.39 | 12-JUN-13:50 | 43.80 | 22.37 | 0.00 | 0.00 | 01-JUN-00:10 | 43.80 | 22.37 |
July | 0.214928E+11 | 29916.14 | 07-JUL-13:50 | 40.22 | 24.59 | 0.00 | 0.00 | 01-JUL-00:10 | 40.22 | 24.59 |
August | 0.196828E+11 | 26533.11 | 07-AUG-14:40 | 37.27 | 26.48 | 0.00 | 0.00 | 01-AUG-00:10 | 37.27 | 26.48 |
September | 0.151894E+11 | 22452.22 | 26-SEP-15:00 | 36.10 | 22.69 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 22.69 |
October | 0.126140E+11 | 21910.01 | 02-OCT-14:20 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.615578E+10 | 14356.10 | 09-NOV-14:40 | 29.27 | 17.76 | 0.00 | 0.00 | 01-NOV-00:10 | 29.27 | 17.76 |
December | 0.156312E+10 | 7605.61 | 01-DEC-15:00 | 23.40 | 13.35 | 0.00 | 0.00 | 01-DEC-00:10 | 23.40 | 13.35 |
Annual Sum or Average | 0.164728E+12 | 0.00 | ||||||||
Minimum of Months | 0.108145E+10 | 5988.96 | 23.40 | 13.35 | 0.00 | 0.00 | 23.40 | 13.35 | ||
Maximum of Months | 0.265789E+11 | 33599.39 | 44.00 | 26.48 | 0.00 | 0.00 | 44.00 | 26.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375569E+10 | 1832.43 | 12-JAN-17:00 | 22.30 | 14.53 | 95236499.96 | 126.84 | 17-JAN-10:20 | 13.53 | 12.90 |
February | 0.836518E+10 | 3980.61 | 20-FEB-17:20 | 24.07 | 14.47 | 86404553.66 | 126.85 | 09-FEB-14:00 | 24.07 | 14.47 |
March | 0.146773E+11 | 7254.55 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 15-MAR-09:09 | 23.70 | 16.75 |
April | 0.193741E+11 | 7926.94 | 16-APR-21:32 | 28.07 | 20.03 | 93175598.50 | 138.15 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.516114E+10 | 3605.38 | 31-MAY-23:53 | 28.10 | 22.60 | 99239995.72 | 126.86 | 09-MAY-09:00 | 28.10 | 22.60 |
June | 0.988878E+10 | 5628.75 | 30-JUN-23:53 | 33.10 | 24.67 | 98978996.49 | 126.88 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.153414E+11 | 7531.26 | 31-JUL-24:00 | 29.40 | 26.34 | 91893805.00 | 126.85 | 18-JUL-09:09 | 29.40 | 26.34 |
August | 0.199652E+11 | 7800.96 | 20-AUG-17:55 | 26.30 | 25.51 | 0.107602E+09 | 143.54 | 07-AUG-13:00 | 26.30 | 25.51 |
September | 0.487622E+10 | 3700.67 | 30-SEP-24:00 | 26.60 | 21.92 | 91606313.78 | 126.86 | 27-SEP-13:09 | 26.60 | 21.92 |
October | 0.987839E+10 | 5382.61 | 31-OCT-24:00 | 17.80 | 15.13 | 95245589.68 | 126.87 | 13-OCT-09:00 | 17.80 | 15.13 |
November | 0.141600E+11 | 5889.70 | 12-NOV-16:12 | 27.13 | 15.56 | 94305804.41 | 126.84 | 10-NOV-10:09 | 27.13 | 15.56 |
December | 0.193689E+11 | 7572.52 | 24-DEC-17:10 | 20.40 | 13.19 | 91882866.63 | 126.83 | 15-DEC-10:09 | 20.40 | 13.19 |
Annual Sum or Average | 0.144812E+12 | 0.114881E+10 | ||||||||
Minimum of Months | 0.375569E+10 | 1832.43 | 17.80 | 13.19 | 86404553.66 | 126.83 | 13.53 | 12.90 | ||
Maximum of Months | 0.199652E+11 | 7926.94 | 33.10 | 26.34 | 0.107602E+09 | 143.54 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229704E+10 | 1673.42 | 12-JAN-17:00 | 22.30 | 14.53 | 95219935.66 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.732540E+10 | 3589.04 | 21-FEB-17:00 | 25.40 | 15.70 | 86403482.09 | 126.84 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.137988E+11 | 6972.93 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.182293E+11 | 7343.25 | 16-APR-21:03 | 28.32 | 20.05 | 94209960.63 | 141.67 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.458673E+10 | 3403.15 | 31-MAY-23:53 | 28.10 | 22.60 | 99238270.19 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.911146E+10 | 5257.26 | 30-JUN-23:53 | 33.10 | 24.67 | 98979006.50 | 126.87 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.141912E+11 | 7007.11 | 31-JUL-24:00 | 29.40 | 26.34 | 91894710.65 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.186277E+11 | 7212.23 | 20-AUG-17:55 | 26.30 | 25.51 | 0.109501E+09 | 145.92 | 07-AUG-13:00 | 26.30 | 25.51 |
September | 0.422294E+10 | 3403.69 | 30-SEP-24:00 | 26.60 | 21.92 | 91605244.42 | 126.82 | 27-SEP-13:09 | 26.60 | 21.92 |
October | 0.914885E+10 | 5090.97 | 31-OCT-24:00 | 17.80 | 15.13 | 95243863.60 | 126.86 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.130808E+11 | 5435.66 | 08-NOV-16:40 | 28.33 | 18.82 | 94305034.11 | 126.83 | 10-NOV-10:09 | 23.57 | 17.22 |
December | 0.174825E+11 | 7162.43 | 01-DEC-17:00 | 21.20 | 14.26 | 91882554.65 | 126.83 | 15-DEC-10:09 | 14.62 | 12.17 |
Annual Sum or Average | 0.132103E+12 | 0.115172E+10 | ||||||||
Minimum of Months | 0.229704E+10 | 1673.42 | 17.80 | 14.26 | 86403482.09 | 126.82 | 14.62 | 12.17 | ||
Maximum of Months | 0.186277E+11 | 7343.25 | 33.10 | 26.34 | 0.109501E+09 | 145.92 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131186E+10 | 1699.49 | 12-JAN-17:00 | 22.30 | 14.53 | 94716921.16 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.670619E+10 | 3639.11 | 22-FEB-17:00 | 25.70 | 15.75 | 86404203.81 | 126.84 | 09-FEB-14:00 | 25.70 | 15.75 |
March | 0.136289E+11 | 6927.38 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.183755E+11 | 7632.79 | 16-APR-21:32 | 28.07 | 20.03 | 93130618.46 | 138.89 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.479105E+10 | 3348.89 | 31-MAY-23:53 | 28.10 | 22.60 | 99238708.18 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.929814E+10 | 5325.84 | 30-JUN-23:53 | 33.10 | 24.67 | 98980394.71 | 126.88 | 28-JUN-13:09 | 33.10 | 24.67 |
July | 0.143904E+11 | 7059.67 | 31-JUL-23:57 | 29.40 | 26.34 | 91896513.83 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.189019E+11 | 7439.79 | 20-AUG-17:03 | 26.63 | 25.62 | 0.106664E+09 | 142.82 | 07-AUG-13:00 | 26.63 | 25.62 |
September | 0.430020E+10 | 3421.96 | 30-SEP-23:45 | 26.60 | 21.97 | 91605258.14 | 126.82 | 27-SEP-13:09 | 26.60 | 21.97 |
October | 0.906911E+10 | 4959.46 | 31-OCT-24:00 | 17.80 | 15.13 | 95245009.35 | 126.86 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.125973E+11 | 5482.55 | 09-NOV-16:40 | 27.67 | 17.53 | 94305792.41 | 126.83 | 10-NOV-10:09 | 23.57 | 17.22 |
December | 0.163588E+11 | 7167.08 | 28-DEC-17:00 | 22.80 | 14.91 | 91883196.85 | 126.83 | 15-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.129729E+12 | 0.114731E+10 | ||||||||
Minimum of Months | 0.131186E+10 | 1699.49 | 17.80 | 14.53 | 86404203.81 | 126.82 | 17.80 | 14.91 | ||
Maximum of Months | 0.189019E+11 | 7632.79 | 33.10 | 26.34 | 0.106664E+09 | 142.82 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240149E+12 | 92203.80 | 26-JAN-17:00 | 18.60 | 12.70 | 0.206233E+10 | 2747.89 | 13-JAN-10:00 | 18.60 | 12.70 |
February | 0.437081E+12 | 183837.27 | 21-FEB-17:00 | 25.40 | 15.70 | 0.187109E+10 | 2749.97 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.729739E+12 | 358960.25 | 31-MAR-23:55 | 23.70 | 16.75 | 0.223540E+10 | 2749.95 | 23-MAR-09:09 | 23.70 | 16.75 |
April | 0.945217E+12 | 368311.98 | 17-APR-16:00 | 34.90 | 21.57 | 0.198325E+10 | 2745.76 | 10-APR-09:09 | 34.90 | 21.57 |
May | 0.245557E+12 | 177383.30 | 31-MAY-23:53 | 28.10 | 22.60 | 0.214881E+10 | 2747.30 | 24-MAY-09:09 | 28.10 | 22.60 |
June | 0.475898E+12 | 269831.60 | 30-JUN-23:53 | 33.10 | 24.67 | 0.214283E+10 | 2747.18 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.739797E+12 | 362655.29 | 31-JUL-23:57 | 29.40 | 26.34 | 0.198946E+10 | 2746.44 | 18-JUL-09:09 | 29.40 | 26.34 |
August | 0.986386E+12 | 371414.13 | 07-AUG-13:05 | 36.62 | 26.39 | 0.223531E+10 | 2762.00 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.242780E+12 | 179208.43 | 30-SEP-24:00 | 26.60 | 21.92 | 0.198357E+10 | 2747.18 | 20-SEP-09:09 | 26.60 | 21.92 |
October | 0.491968E+12 | 269356.17 | 31-OCT-24:00 | 17.80 | 15.13 | 0.206197E+10 | 2747.07 | 30-OCT-09:09 | 17.80 | 15.13 |
November | 0.710819E+12 | 277106.31 | 13-NOV-17:00 | 26.40 | 16.65 | 0.204199E+10 | 2750.01 | 02-NOV-09:09 | 26.40 | 16.65 |
December | 0.978250E+12 | 368151.72 | 04-DEC-16:40 | 20.77 | 14.56 | 0.199000E+10 | 2751.45 | 20-DEC-14:00 | 20.30 | 10.35 |
Annual Sum or Average | 0.722364E+13 | 0.247460E+11 | ||||||||
Minimum of Months | 0.240149E+12 | 92203.80 | 17.80 | 12.70 | 0.187109E+10 | 2745.76 | 17.80 | 10.35 | ||
Maximum of Months | 0.986386E+12 | 371414.13 | 36.62 | 26.39 | 0.223540E+10 | 2762.00 | 37.20 | 26.34 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 615882.24 | 4105.88 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 615882.24 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 615882.24 | 4105.88 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538874E+09 | 57778.58 | 02-JAN-05:11 | 6.47 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.538874E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.538874E+09 | 57778.58 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 655251.42 | 3415.08 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 655251.42 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 655251.42 | 3415.08 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266489E+09 | 13966.50 | 02-JAN-05:11 | 6.47 |
February | 11759463.18 | 9775.45 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 38991738.89 | 12413.24 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.317240E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.266489E+09 | 13966.50 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87060537.23 | 8686.67 | 02-JAN-05:11 | 6.47 |
February | 2997592.35 | 7442.37 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 9857334.61 | 6585.95 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 99915464.19 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 87060537.23 | 8686.67 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40625181.46 | 12959.27 | 02-JAN-05:11 | 6.47 |
February | 3896094.56 | 9303.33 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 44521276.02 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 40625181.46 | 12959.27 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44929256.36 | 7565.57 | 02-JAN-05:12 | 6.47 |
February | 1238162.81 | 3238.66 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 3215559.77 | 3836.93 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 49382978.93 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 44929256.36 | 7565.57 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119693E+10 | 18488.77 | 02-JAN-05:11 | 6.47 |
February | 0.194308E+09 | 15685.22 | 06-FEB-06:02 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 14381216.24 | 9766.19 | 27-NOV-06:03 | 9.55 |
December | 0.516231E+09 | 16816.98 | 22-DEC-05:12 | 11.37 |
Annual Sum or Average | 0.192185E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.119693E+10 | 18488.77 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464966E+09 | 11906.26 | 02-JAN-05:11 | 6.47 |
February | 65130104.56 | 10306.93 | 11-FEB-05:12 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 556080.46 | 498.77 | 27-NOV-06:03 | 9.55 |
December | 0.176049E+09 | 10545.20 | 11-DEC-05:11 | 10.13 |
Annual Sum or Average | 0.706701E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.464966E+09 | 11906.26 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385804E+09 | 18133.77 | 02-JAN-05:11 | 6.47 |
February | 60294470.26 | 15488.94 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 87328891.68 | 15421.73 | 22-DEC-06:02 | 12.42 |
Annual Sum or Average | 0.533428E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.385804E+09 | 18133.77 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359303E+09 | 10801.15 | 02-JAN-05:11 | 6.47 |
February | 41946039.27 | 9257.14 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 95607832.10 | 9296.36 | 20-DEC-06:03 | 6.40 |
Annual Sum or Average | 0.496857E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.40 | |
Maximum of Months | 0.359303E+09 | 10801.15 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85281075.81 | 11356.39 | 02-JAN-05:11 | 6.47 |
February | 93104689.78 | 9312.22 | 11-FEB-06:02 | 9.30 |
March | 69278748.85 | 7961.66 | 20-MAR-04:12 | 15.40 |
April | 56853682.18 | 7974.40 | 23-APR-06:00 | 20.40 |
May | 34713950.94 | 6834.00 | 23-MAY-03:02 | 28.47 |
June | 51728750.53 | 6409.06 | 04-JUN-16:01 | 42.22 |
July | 53766984.59 | 4611.03 | 23-JUL-13:42 | 32.88 |
August | 66098401.44 | 4493.54 | 27-AUG-13:42 | 35.50 |
September | 95902066.14 | 6258.03 | 10-SEP-05:43 | 25.00 |
October | 76086731.50 | 6901.97 | 26-OCT-04:12 | 17.43 |
November | 90642111.67 | 8983.16 | 27-NOV-05:12 | 9.77 |
December | 0.178370E+09 | 12289.20 | 11-DEC-05:11 | 10.13 |
Annual Sum or Average | 0.951827E+09 | |||
Minimum of Months | 34713950.94 | 4493.54 | 6.47 | |
Maximum of Months | 0.178370E+09 | 12289.20 | 42.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.909119E+09 | 6867.56 | 18-JAN-06:03 | 13.58 |
February | 0.121180E+09 | 7012.89 | 10-FEB-06:02 | 12.33 |
March | 41635267.91 | 5494.24 | 12-MAR-14:42 | 31.45 |
April | 34544527.85 | 6704.62 | 02-APR-15:01 | 33.82 |
May | 30042423.24 | 7053.62 | 14-MAY-15:21 | 36.15 |
June | 26355853.27 | 7130.83 | 04-JUN-16:01 | 42.22 |
July | 35571803.71 | 5628.66 | 02-JUL-15:41 | 40.33 |
August | 30087359.32 | 6270.73 | 13-AUG-15:11 | 34.80 |
September | 26361841.24 | 6241.55 | 11-SEP-03:02 | 26.07 |
October | 44832904.74 | 6501.72 | 01-OCT-14:31 | 35.97 |
November | 55025441.35 | 5233.50 | 28-NOV-05:12 | 15.20 |
December | 0.182017E+09 | 6595.98 | 12-DEC-06:02 | 10.68 |
Annual Sum or Average | 0.153677E+10 | |||
Minimum of Months | 26355853.27 | 5233.50 | 10.68 | |
Maximum of Months | 0.909119E+09 | 7130.83 | 42.22 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263246E+10 | 22113.72 | 02-JAN-06:03 | 6.45 |
February | 0.121536E+10 | 14441.32 | 24-FEB-06:03 | 15.00 |
March | 0.443224E+09 | 15009.21 | 31-MAR-05:03 | 16.93 |
April | 47525729.55 | 12540.80 | 10-APR-04:12 | 18.47 |
May | 7058487.90 | 6578.45 | 25-MAY-03:02 | 26.60 |
June | 4806618.98 | 5087.14 | 28-JUN-03:02 | 26.40 |
July | 4597987.68 | 6668.10 | 19-JUL-04:03 | 24.72 |
August | 6712919.74 | 4941.95 | 22-AUG-03:02 | 25.88 |
September | 19419428.69 | 7577.69 | 11-SEP-03:02 | 26.07 |
October | 0.189649E+09 | 14662.56 | 30-OCT-05:03 | 16.20 |
November | 0.775787E+09 | 15195.74 | 14-NOV-06:03 | 14.57 |
December | 0.190982E+10 | 8561.25 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.725642E+10 | |||
Minimum of Months | 4597987.68 | 4941.95 | 5.43 | |
Maximum of Months | 0.263246E+10 | 22113.72 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15895654.67 | 266.00 | 01-JAN-12:25 | 14.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 15895654.67 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 15895654.67 | 266.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125036E+09 | 352.65 | 01-JAN-14:05 | 16.22 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.125036E+09 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 0.125036E+09 | 352.65 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.940365E+09 | 1365.60 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.829509E+09 | 1334.84 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.940812E+09 | 1347.93 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.822203E+09 | 871.10 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.869443E+09 | 927.00 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.866259E+09 | 925.30 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.826987E+09 | 1292.19 | 26-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.931486E+09 | 1338.07 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.847034E+09 | 1384.03 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.901842E+09 | 1465.83 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.923986E+09 | 1426.82 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.923300E+09 | 1441.86 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106232E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.822203E+09 | 871.10 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.940812E+09 | 1465.83 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.597426E+09 | 870.03 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.530331E+09 | 865.23 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603430E+09 | 754.29 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.529216E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562928E+09 | 578.13 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.560508E+09 | 578.51 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.533564E+09 | 800.32 | 26-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.599338E+09 | 832.44 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.543714E+09 | 864.82 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.575445E+09 | 927.86 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.591249E+09 | 941.67 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.587244E+09 | 936.94 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.681439E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.529216E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.603430E+09 | 941.67 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.906505E+09 | 1307.00 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.812138E+09 | 1288.00 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.935193E+09 | 1330.25 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.823964E+09 | 880.11 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.876436E+09 | 1069.79 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.873021E+09 | 1081.30 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.833058E+09 | 1313.45 | 26-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.933849E+09 | 1347.51 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.844613E+09 | 1381.27 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.889996E+09 | 1457.63 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.895741E+09 | 1259.70 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.884461E+09 | 1367.23 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105090E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.812138E+09 | 880.11 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.935193E+09 | 1457.63 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593148E+09 | 887.46 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.526655E+09 | 871.36 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.606064E+09 | 900.36 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530734E+09 | 697.90 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564011E+09 | 734.71 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.561374E+09 | 736.32 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.536948E+09 | 858.59 | 26-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.604298E+09 | 881.20 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.546544E+09 | 904.09 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.581156E+09 | 949.65 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.581731E+09 | 842.70 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.577693E+09 | 857.26 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.681035E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.526655E+09 | 697.90 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.606064E+09 | 949.65 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.937666E+09 | 1361.88 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.827704E+09 | 1330.80 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.939542E+09 | 1343.96 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.821661E+09 | 862.01 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868978E+09 | 921.60 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.865093E+09 | 919.82 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.826009E+09 | 1287.83 | 26-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.930285E+09 | 1334.28 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.845755E+09 | 1380.81 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.900297E+09 | 1463.59 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.921825E+09 | 1423.49 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.920563E+09 | 1439.14 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106054E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.821661E+09 | 862.01 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.939542E+09 | 1463.59 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596354E+09 | 864.77 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.529453E+09 | 859.83 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.602958E+09 | 747.22 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.528964E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562545E+09 | 574.29 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.559991E+09 | 574.75 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.532888E+09 | 793.93 | 26-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.598447E+09 | 827.17 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.543090E+09 | 860.37 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.574773E+09 | 924.43 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.590398E+09 | 938.33 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.586242E+09 | 933.45 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.680610E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.528964E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.602958E+09 | 938.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.906111E+09 | 1303.04 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.811461E+09 | 1283.63 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.934410E+09 | 1326.14 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.823410E+09 | 871.65 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.875802E+09 | 1062.03 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.872066E+09 | 1073.58 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.831729E+09 | 1309.26 | 26-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.932529E+09 | 1343.80 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.843714E+09 | 1378.02 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.888677E+09 | 1455.33 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.893890E+09 | 1254.40 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.884119E+09 | 1363.72 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104979E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.811461E+09 | 871.65 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.934410E+09 | 1455.33 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.592121E+09 | 882.67 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.525807E+09 | 866.12 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.605281E+09 | 895.79 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530274E+09 | 688.60 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.563345E+09 | 725.76 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.560586E+09 | 727.43 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.535859E+09 | 853.00 | 26-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.603076E+09 | 876.20 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.545657E+09 | 899.69 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.580142E+09 | 946.46 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.581182E+09 | 837.30 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.576992E+09 | 852.12 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.680032E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.525807E+09 | 688.60 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.605281E+09 | 946.46 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.937583E+09 | 1361.28 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.827540E+09 | 1330.13 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.939505E+09 | 1343.36 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.821646E+09 | 861.71 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868958E+09 | 921.38 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.865053E+09 | 919.60 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.825962E+09 | 1287.06 | 26-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.930205E+09 | 1333.61 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.845662E+09 | 1380.23 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.900248E+09 | 1463.18 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.921691E+09 | 1423.09 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.920501E+09 | 1438.70 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106046E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.821646E+09 | 861.71 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.939505E+09 | 1463.18 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596334E+09 | 864.39 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.529425E+09 | 859.41 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.602942E+09 | 746.76 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.528956E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562525E+09 | 574.11 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.559971E+09 | 574.57 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.532858E+09 | 793.40 | 26-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.598382E+09 | 826.71 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.543055E+09 | 859.97 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.574737E+09 | 924.15 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.590373E+09 | 938.11 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.586216E+09 | 933.18 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.680577E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.528956E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.602942E+09 | 938.11 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.906101E+09 | 1302.35 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.811434E+09 | 1282.89 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.934342E+09 | 1325.51 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.823375E+09 | 871.37 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.875762E+09 | 1060.84 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.872023E+09 | 1072.41 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.831653E+09 | 1308.53 | 26-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.932464E+09 | 1343.14 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.843663E+09 | 1377.43 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.888651E+09 | 1454.91 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.893875E+09 | 1253.85 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.884110E+09 | 1363.22 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104975E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.811434E+09 | 871.37 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.934342E+09 | 1454.91 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.592104E+09 | 882.30 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.525769E+09 | 865.71 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.605245E+09 | 895.45 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530214E+09 | 688.15 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.563327E+09 | 725.08 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.560510E+09 | 726.74 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.535821E+09 | 852.55 | 26-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.602963E+09 | 875.80 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.545610E+09 | 899.34 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.580114E+09 | 946.21 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.581165E+09 | 836.98 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.576927E+09 | 851.78 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.679977E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.525769E+09 | 688.15 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.605245E+09 | 946.21 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.940365E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39427775.15 |
February | 0.136985E+10 | 0.829509E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529669.12 | 42076646.71 |
March | 0.163685E+10 | 0.940812E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7627956.87 | 26381807.75 |
April | 0.145243E+10 | 0.822203E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30248552.25 | 2278815.24 |
May | 0.157338E+10 | 0.869443E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65531521.38 | 795426.72 |
June | 0.156900E+10 | 0.866259E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44310096.22 | 474731.04 |
July | 0.145680E+10 | 0.826987E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54785626.07 | 228996.14 |
August | 0.163685E+10 | 0.931486E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30792805.72 | 390519.37 |
September | 0.145243E+10 | 0.847034E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18032420.60 | 982859.74 |
October | 0.150991E+10 | 0.901842E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9773688.12 | 2409374.85 |
November | 0.149516E+10 | 0.923986E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2080625.73 | 8975910.24 |
December | 0.145680E+10 | 0.923300E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26845.13 | 36390060.23 |
Annual Sum or Average | 0.181194E+11 | 0.106232E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263740E+09 | 0.160813E+09 |
Minimum of Months | 0.136985E+10 | 0.822203E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228996.14 |
Maximum of Months | 0.163685E+10 | 0.940812E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65531521.38 | 42076646.71 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.597426E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26968713.40 |
February | 0.882782E+09 | 0.530331E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270351.82 | 29037726.84 |
March | 0.105485E+10 | 0.603430E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4686589.85 | 17928583.45 |
April | 0.936002E+09 | 0.529216E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19871196.26 | 1644639.72 |
May | 0.101394E+10 | 0.562928E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43055668.84 | 569849.23 |
June | 0.101113E+10 | 0.560508E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29399086.22 | 322048.22 |
July | 0.938820E+09 | 0.533564E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36523064.08 | 144033.44 |
August | 0.105485E+10 | 0.599338E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20535727.85 | 248192.52 |
September | 0.936002E+09 | 0.543714E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11892619.57 | 668928.14 |
October | 0.973041E+09 | 0.575445E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6291619.05 | 1703381.92 |
November | 0.963541E+09 | 0.591249E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244452.86 | 6257895.31 |
December | 0.938820E+09 | 0.587244E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5993.21 | 24441570.18 |
Annual Sum or Average | 0.116768E+11 | 0.681439E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173776E+09 | 0.109936E+09 |
Minimum of Months | 0.882782E+09 | 0.529216E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144033.44 |
Maximum of Months | 0.105485E+10 | 0.603430E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43055668.84 | 29037726.84 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.906505E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42532340.03 |
February | 0.136988E+10 | 0.812138E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392215.54 | 46902572.50 |
March | 0.163688E+10 | 0.935193E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6786277.07 | 29398059.30 |
April | 0.145246E+10 | 0.823964E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29687275.86 | 2512868.41 |
May | 0.157341E+10 | 0.876436E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65553017.35 | 756037.89 |
June | 0.156904E+10 | 0.873021E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44511757.19 | 426763.85 |
July | 0.145684E+10 | 0.833058E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55139935.18 | 201852.91 |
August | 0.163688E+10 | 0.933849E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30867497.03 | 373948.52 |
September | 0.145246E+10 | 0.844613E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17834254.14 | 850527.44 |
October | 0.150994E+10 | 0.889996E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9042594.91 | 2681953.23 |
November | 0.149520E+10 | 0.895741E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1665235.21 | 10430686.79 |
December | 0.145684E+10 | 0.884461E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7736.71 | 40565381.17 |
Annual Sum or Average | 0.181198E+11 | 0.105090E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261488E+09 | 0.177633E+09 |
Minimum of Months | 0.136988E+10 | 0.812138E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201852.91 |
Maximum of Months | 0.163688E+10 | 0.935193E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65553017.35 | 46902572.50 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.593148E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29580041.95 |
February | 0.882782E+09 | 0.526655E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261812.98 | 33644224.66 |
March | 0.105485E+10 | 0.606064E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4469267.63 | 23169175.05 |
April | 0.936002E+09 | 0.530734E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19342864.58 | 2440893.37 |
May | 0.101394E+10 | 0.564011E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43011627.11 | 615384.38 |
June | 0.101113E+10 | 0.561374E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29060116.56 | 394139.27 |
July | 0.938820E+09 | 0.536948E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35743432.85 | 209250.79 |
August | 0.105485E+10 | 0.604298E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20009746.24 | 359423.20 |
September | 0.936002E+09 | 0.546544E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11844486.07 | 648137.55 |
October | 0.973041E+09 | 0.581156E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6131882.14 | 1961228.19 |
November | 0.963541E+09 | 0.581731E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1131322.73 | 7379033.53 |
December | 0.938820E+09 | 0.577693E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5195.04 | 29374386.98 |
Annual Sum or Average | 0.116768E+11 | 0.681035E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171012E+09 | 0.129775E+09 |
Minimum of Months | 0.882782E+09 | 0.526655E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209250.79 |
Maximum of Months | 0.105485E+10 | 0.606064E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43011627.11 | 33644224.66 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.937666E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102489.81 | 75705233.15 |
February | 0.136985E+10 | 0.827704E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2483902.30 | 85201401.77 |
March | 0.163685E+10 | 0.939542E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18876220.32 | 58677425.28 |
April | 0.145243E+10 | 0.821661E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72280023.32 | 5225355.93 |
May | 0.157338E+10 | 0.868978E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155504E+09 | 1480139.67 |
June | 0.156900E+10 | 0.865093E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105224E+09 | 1018904.50 |
July | 0.145680E+10 | 0.826009E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130499E+09 | 436975.60 |
August | 0.163685E+10 | 0.930285E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74282713.05 | 901205.82 |
September | 0.145243E+10 | 0.845755E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43593187.39 | 1389249.19 |
October | 0.150991E+10 | 0.900297E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23684663.76 | 5043008.09 |
November | 0.149516E+10 | 0.921825E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5974712.92 | 18008411.86 |
December | 0.145680E+10 | 0.920563E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 830636.97 | 68992007.44 |
Annual Sum or Average | 0.181194E+11 | 0.106054E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633335E+09 | 0.322079E+09 |
Minimum of Months | 0.136985E+10 | 0.821661E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102489.81 | 436975.60 |
Maximum of Months | 0.163685E+10 | 0.939542E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155504E+09 | 85201401.77 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.596354E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 56648441.95 |
February | 0.649041E+09 | 0.529453E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529086.94 | 64429138.54 |
March | 0.773965E+09 | 0.602958E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10294449.09 | 44050718.88 |
April | 0.688021E+09 | 0.528964E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45466871.08 | 4499529.21 |
May | 0.744847E+09 | 0.562545E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100636E+09 | 1140589.76 |
June | 0.742030E+09 | 0.559991E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68738554.98 | 742653.58 |
July | 0.690839E+09 | 0.532888E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85269556.19 | 305570.53 |
August | 0.773965E+09 | 0.598447E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48087061.93 | 660220.64 |
September | 0.688021E+09 | 0.543090E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27820034.53 | 985096.09 |
October | 0.715730E+09 | 0.574773E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14243015.62 | 3892480.55 |
November | 0.708685E+09 | 0.590398E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2692575.91 | 13974612.86 |
December | 0.690839E+09 | 0.586242E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117238.68 | 51712795.04 |
Annual Sum or Average | 0.858171E+10 | 0.680610E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403894E+09 | 0.243042E+09 |
Minimum of Months | 0.649041E+09 | 0.528964E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 305570.53 |
Maximum of Months | 0.773965E+09 | 0.602958E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100636E+09 | 64429138.54 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.906111E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95716347.70 |
February | 0.136988E+10 | 0.811461E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 834127.72 | 0.107254E+09 |
March | 0.163688E+10 | 0.934410E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15363091.92 | 70678866.45 |
April | 0.145246E+10 | 0.823410E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69329341.06 | 6394839.64 |
May | 0.157341E+10 | 0.875802E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154682E+09 | 1521971.81 |
June | 0.156904E+10 | 0.872066E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105295E+09 | 999488.32 |
July | 0.145684E+10 | 0.831729E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130416E+09 | 436624.66 |
August | 0.163688E+10 | 0.932529E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73463485.91 | 954509.53 |
September | 0.145246E+10 | 0.843714E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42016211.22 | 1533050.94 |
October | 0.150994E+10 | 0.888677E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20698162.46 | 6264820.10 |
November | 0.149520E+10 | 0.893890E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3679148.52 | 24102847.23 |
December | 0.145684E+10 | 0.884119E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13125.87 | 91280261.77 |
Annual Sum or Average | 0.181198E+11 | 0.104979E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615789E+09 | 0.407138E+09 |
Minimum of Months | 0.136988E+10 | 0.811461E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436624.66 |
Maximum of Months | 0.163688E+10 | 0.934410E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154682E+09 | 0.107254E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.592121E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57893267.00 |
February | 0.882782E+09 | 0.525807E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 614912.98 | 65957758.23 |
March | 0.105485E+10 | 0.605281E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10746660.66 | 47808448.07 |
April | 0.936002E+09 | 0.530274E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45449391.90 | 5146544.05 |
May | 0.101394E+10 | 0.563345E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100112E+09 | 1405393.13 |
June | 0.101113E+10 | 0.560586E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68033401.40 | 916664.51 |
July | 0.938820E+09 | 0.535859E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84155128.71 | 382372.89 |
August | 0.105485E+10 | 0.603076E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47408948.05 | 827374.45 |
September | 0.936002E+09 | 0.545657E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27534579.03 | 1299519.84 |
October | 0.973041E+09 | 0.580142E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14501939.76 | 3907425.80 |
November | 0.963541E+09 | 0.581182E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2902187.60 | 13958852.02 |
December | 0.938820E+09 | 0.576992E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54601.95 | 52994265.28 |
Annual Sum or Average | 0.116768E+11 | 0.680032E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401513E+09 | 0.252498E+09 |
Minimum of Months | 0.882782E+09 | 0.525807E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382372.89 |
Maximum of Months | 0.105485E+10 | 0.605281E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100112E+09 | 65957758.23 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.937583E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251326.54 | 82338839.35 |
February | 0.136985E+10 | 0.827540E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3424811.45 | 97008697.21 |
March | 0.163685E+10 | 0.939505E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22188166.14 | 70685082.14 |
April | 0.145243E+10 | 0.821646E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87130387.12 | 6795296.49 |
May | 0.157338E+10 | 0.868958E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188538E+09 | 2096432.75 |
June | 0.156900E+10 | 0.865053E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127773E+09 | 1394844.09 |
July | 0.145680E+10 | 0.825962E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157632E+09 | 562845.80 |
August | 0.163685E+10 | 0.930205E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89545383.30 | 1228686.98 |
September | 0.145243E+10 | 0.845662E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52243855.54 | 1911045.19 |
October | 0.150991E+10 | 0.900248E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28351325.83 | 6108144.66 |
November | 0.149516E+10 | 0.921691E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7629990.45 | 20346264.59 |
December | 0.145680E+10 | 0.920501E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1753603.34 | 75628653.28 |
Annual Sum or Average | 0.181194E+11 | 0.106046E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766462E+09 | 0.366105E+09 |
Minimum of Months | 0.136985E+10 | 0.821646E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251326.54 | 562845.80 |
Maximum of Months | 0.163685E+10 | 0.939505E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188538E+09 | 97008697.21 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.596334E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30611.48 | 61757267.70 |
February | 0.882782E+09 | 0.529425E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 708442.35 | 73925758.47 |
March | 0.105485E+10 | 0.602942E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12582808.52 | 53190326.73 |
April | 0.936002E+09 | 0.528956E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55783224.74 | 5792668.48 |
May | 0.101394E+10 | 0.562525E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123088E+09 | 1581155.81 |
June | 0.101113E+10 | 0.559971E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84229171.78 | 998900.46 |
July | 0.938820E+09 | 0.532858E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103983E+09 | 392360.12 |
August | 0.105485E+10 | 0.598382E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58720207.28 | 879639.11 |
September | 0.936002E+09 | 0.543055E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34027434.20 | 1339606.58 |
October | 0.973041E+09 | 0.574737E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17522152.46 | 4726385.66 |
November | 0.963541E+09 | 0.590373E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3470697.05 | 15959431.48 |
December | 0.938820E+09 | 0.586216E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420968.37 | 57214670.41 |
Annual Sum or Average | 0.116768E+11 | 0.680577E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494566E+09 | 0.277758E+09 |
Minimum of Months | 0.882782E+09 | 0.528956E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30611.48 | 392360.12 |
Maximum of Months | 0.105485E+10 | 0.602942E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123088E+09 | 73925758.47 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.906101E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108887E+09 |
February | 0.136988E+10 | 0.811434E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 934474.64 | 0.125942E+09 |
March | 0.163688E+10 | 0.934342E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18350420.03 | 85690049.14 |
April | 0.145246E+10 | 0.823375E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84215822.45 | 8255874.50 |
May | 0.157341E+10 | 0.875762E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187653E+09 | 2150616.10 |
June | 0.156904E+10 | 0.872023E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127838E+09 | 1372298.56 |
July | 0.145684E+10 | 0.831653E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157558E+09 | 563868.27 |
August | 0.163688E+10 | 0.932464E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88663542.26 | 1292209.28 |
September | 0.145246E+10 | 0.843663E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50625913.33 | 2124702.91 |
October | 0.150994E+10 | 0.888651E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25197424.37 | 7645287.13 |
November | 0.149520E+10 | 0.893875E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4443774.41 | 28615575.33 |
December | 0.145684E+10 | 0.884110E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11183.79 | 0.104955E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104975E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745492E+09 | 0.477493E+09 |
Minimum of Months | 0.136988E+10 | 0.811434E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563868.27 |
Maximum of Months | 0.163688E+10 | 0.934342E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187653E+09 | 0.125942E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.592104E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.30 | 65687518.29 |
February | 0.882782E+09 | 0.525769E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 719709.35 | 77234178.34 |
March | 0.105485E+10 | 0.605245E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12916971.92 | 58040372.35 |
April | 0.936002E+09 | 0.530214E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55345861.04 | 6593865.59 |
May | 0.101394E+10 | 0.563327E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 1903671.51 |
June | 0.101113E+10 | 0.560510E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83064801.61 | 1192670.37 |
July | 0.938820E+09 | 0.535821E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102162E+09 | 506903.87 |
August | 0.105485E+10 | 0.602963E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57430558.46 | 1090632.91 |
September | 0.936002E+09 | 0.545610E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33264501.53 | 1767476.26 |
October | 0.973041E+09 | 0.580114E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17640561.57 | 4772743.30 |
November | 0.963541E+09 | 0.581165E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3579372.15 | 16273297.55 |
December | 0.938820E+09 | 0.576927E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211782.46 | 60409966.78 |
Annual Sum or Average | 0.116768E+11 | 0.679977E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488409E+09 | 0.295473E+09 |
Minimum of Months | 0.882782E+09 | 0.525769E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1559.30 | 506903.87 |
Maximum of Months | 0.105485E+10 | 0.605245E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 77234178.34 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87251664.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438152.43 | 94433882.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12415224.28 | 61305444.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53921286.49 | 6118118.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117642E+09 | 2221029.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80566515.36 | 1190952.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97118816.20 | 624160.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52734532.76 | 1007800.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30622711.70 | 2173021.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16777083.61 | 5671280.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2856416.56 | 20820317.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.33 | 81472382.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465093E+09 | 0.364290E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624160.60 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117642E+09 | 94433882.57 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144844E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1196117.00 | 0.159996E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23340764.88 | 0.106775E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102741E+09 | 9891846.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226010E+09 | 2759746.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154089E+09 | 1561645.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193014E+09 | 677397.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105881E+09 | 1199450.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61301651.65 | 1792537.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31583823.47 | 9614027.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5770119.16 | 35184374.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202972.57 | 0.134067E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905130E+09 | 0.608363E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677397.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226010E+09 | 0.159996E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142131E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219834.08 | 0.165791E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18592897.82 | 0.113525E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101210E+09 | 10097805.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239857E+09 | 3286172.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166081E+09 | 1626270.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202091E+09 | 610939.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110629E+09 | 1995383.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62112753.64 | 2181224.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29245371.54 | 9324674.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4010499.55 | 34672825.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312401.21 | 0.129663E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934363E+09 | 0.614905E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610939.44 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239857E+09 | 0.165791E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1365.60 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.54 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1334.84 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 | 19-FEB-15:00 | 137.40 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1347.93 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.11 | 26-MAR-15:00 | 305.17 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 871.10 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.44 | 15-APR-17:06 | 59.22 | 22-APR-17:55 |
May | 2010.79 | 01-MAY-09:09 | 927.00 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.27 | 28-MAY-14:24 | 32.10 | 15-MAY-03:10 |
June | 2010.79 | 01-JUN-09:09 | 925.30 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.21 | 03-JUN-17:08 | 27.76 | 18-JUN-04:10 |
July | 2010.79 | 03-JUL-09:09 | 1292.19 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.51 | 02-JUL-11:44 | 24.05 | 19-JUL-02:40 |
August | 2010.79 | 01-AUG-09:09 | 1338.07 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.29 | 06-AUG-13:44 | 27.97 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 1384.03 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.99 | 24-SEP-13:56 | 19.20 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 1465.83 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.82 | 15-OCT-13:10 | 47.23 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1426.82 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 12-NOV-14:00 | 71.57 | 28-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1441.86 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 | 24-DEC-14:20 | 156.98 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 871.10 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | |||||
Maximum of Months | 2010.79 | 1465.83 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 271.27 | 305.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 870.03 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 66.12 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 865.23 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 19-FEB-15:00 | 88.43 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 754.29 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 26-MAR-14:38 | 204.17 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 15-APR-17:06 | 41.29 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 578.13 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.25 | 28-MAY-15:04 | 23.02 | 15-MAY-03:10 |
June | 1295.83 | 01-JUN-09:09 | 578.51 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.37 | 03-JUN-17:07 | 18.30 | 18-JUN-04:10 |
July | 1295.83 | 03-JUL-09:09 | 800.32 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 | 02-JUL-11:44 | 15.28 | 19-JUL-02:40 |
August | 1295.83 | 01-AUG-09:09 | 832.44 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 06-AUG-13:44 | 18.37 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 864.82 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 | 24-SEP-14:34 | 12.78 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 927.86 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 | 15-OCT-13:06 | 30.50 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 941.67 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 12-NOV-14:00 | 46.79 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 936.94 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 28-DEC-14:00 | 98.88 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 | |||||
Maximum of Months | 1295.83 | 941.67 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 180.25 | 204.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1307.00 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 111.14 | 22-JAN-14:00 |
February | 2010.83 | 01-FEB-10:09 | 1288.00 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 21-FEB-15:00 | 135.77 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1330.25 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 26-MAR-15:14 | 343.68 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 880.11 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.88 | 15-APR-17:06 | 60.90 | 22-APR-17:55 |
May | 2010.83 | 01-MAY-09:09 | 1069.79 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.97 | 28-MAY-15:04 | 31.51 | 15-MAY-03:10 |
June | 2010.83 | 01-JUN-09:09 | 1081.30 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.32 | 03-JUN-17:08 | 26.31 | 18-JUN-04:10 |
July | 2010.83 | 03-JUL-09:09 | 1313.45 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.86 | 02-JUL-11:44 | 22.46 | 19-JUL-02:40 |
August | 2010.83 | 01-AUG-09:09 | 1347.51 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.93 | 06-AUG-14:00 | 27.49 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 1381.27 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.55 | 24-SEP-15:00 | 17.96 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 1457.63 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.85 | 15-OCT-12:50 | 46.24 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1259.70 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 12-NOV-14:00 | 76.12 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1367.23 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 28-DEC-14:00 | 186.39 | 31-DEC-14:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 880.11 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | |||||
Maximum of Months | 2010.83 | 1457.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 270.97 | 343.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 887.46 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 73.32 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 871.36 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 21-FEB-15:00 | 103.42 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 900.36 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 | 26-MAR-14:34 | 280.91 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 697.90 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.18 | 15-APR-17:10 | 52.83 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 734.71 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.82 | 28-MAY-15:04 | 25.36 | 15-MAY-03:10 |
June | 1295.83 | 01-JUN-09:09 | 736.32 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 | 17-JUN-19:47 | 21.61 | 18-JUN-04:10 |
July | 1295.83 | 03-JUL-09:09 | 858.59 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.01 | 02-JUL-11:44 | 18.75 | 19-JUL-02:40 |
August | 1295.83 | 01-AUG-09:09 | 881.20 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.62 | 06-AUG-14:00 | 22.16 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 904.09 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 | 24-SEP-13:54 | 12.42 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 949.65 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.25 | 15-OCT-12:24 | 36.04 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 842.70 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 12-NOV-13:54 | 57.46 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 857.26 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 28-DEC-14:00 | 125.62 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 697.90 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | |||||
Maximum of Months | 1295.83 | 949.65 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 180.82 | 280.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1361.88 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 08-JAN-14:53 | 201.66 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1330.80 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.84 | 19-FEB-14:55 | 289.47 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1343.96 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.09 | 26-MAR-15:00 | 630.92 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 862.01 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.62 | 15-APR-17:07 | 100.35 | 22-APR-17:55 |
May | 2010.79 | 01-MAY-09:09 | 921.60 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.74 | 28-MAY-14:33 | 54.51 | 15-MAY-02:45 |
June | 2010.79 | 01-JUN-09:09 | 919.82 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.20 | 17-JUN-20:00 | 53.04 | 18-JUN-04:05 |
July | 2010.79 | 03-JUL-09:09 | 1287.83 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.33 | 02-JUL-11:44 | 45.63 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1334.28 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.66 | 06-AUG-14:14 | 58.46 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1380.81 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.09 | 24-SEP-14:56 | 24.00 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 1463.59 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.35 | 15-OCT-12:30 | 90.34 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1423.49 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 12-NOV-14:30 | 140.97 | 28-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1439.14 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.71 | 24-DEC-13:52 | 308.81 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 862.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 24.00 | |||||
Maximum of Months | 2010.79 | 1463.59 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 630.74 | 630.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 864.77 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 08-JAN-14:53 | 134.33 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 859.83 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | 19-FEB-15:00 | 192.61 | 09-FEB-22:10 |
March | 1239.33 | 01-MAR-08:09 | 747.22 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.24 | 26-MAR-14:58 | 459.57 | 24-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.71 | 15-APR-17:06 | 82.94 | 22-APR-17:55 |
May | 1239.33 | 01-MAY-07:10 | 574.29 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.30 | 28-MAY-14:33 | 43.42 | 15-MAY-02:45 |
June | 1239.33 | 01-JUN-07:10 | 574.75 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.81 | 03-JUN-17:08 | 36.82 | 18-JUN-03:53 |
July | 1239.33 | 03-JUL-07:10 | 793.93 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.72 | 02-JUL-11:44 | 30.37 | 19-JUL-02:55 |
August | 1239.33 | 01-AUG-07:10 | 827.17 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.39 | 06-AUG-14:14 | 40.88 | 15-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 860.37 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.65 | 24-SEP-14:54 | 16.16 | 08-SEP-22:20 |
October | 1239.33 | 02-OCT-07:10 | 924.43 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 | 15-OCT-12:04 | 60.93 | 12-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 938.33 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 | 12-NOV-14:30 | 99.28 | 28-NOV-05:00 |
December | 1239.33 | 01-DEC-08:09 | 933.45 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 24-DEC-14:20 | 206.93 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 16.16 | |||||
Maximum of Months | 1239.33 | 938.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 422.30 | 459.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1303.04 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 270.60 | 22-JAN-14:10 |
February | 2010.83 | 01-FEB-10:09 | 1283.63 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.69 | 21-FEB-15:00 | 299.98 | 18-FEB-05:55 |
March | 2010.83 | 01-MAR-10:09 | 1326.14 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 | 26-MAR-14:55 | 746.72 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 871.65 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.05 | 15-APR-17:06 | 116.73 | 22-APR-17:55 |
May | 2010.83 | 01-MAY-09:09 | 1062.03 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.03 | 28-MAY-14:33 | 58.73 | 15-MAY-02:45 |
June | 2010.83 | 01-JUN-09:09 | 1073.58 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.49 | 03-JUN-17:10 | 52.51 | 18-JUN-04:05 |
July | 2010.83 | 03-JUL-09:09 | 1309.26 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.13 | 02-JUL-11:44 | 45.47 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1343.80 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.30 | 06-AUG-14:14 | 60.41 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1378.02 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.30 | 24-SEP-15:00 | 24.34 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 1455.33 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.75 | 15-OCT-13:00 | 93.69 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1254.40 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.18 | 13-NOV-14:00 | 169.57 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1363.72 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 28-DEC-14:00 | 435.99 | 31-DEC-14:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 871.65 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | |||||
Maximum of Months | 2010.83 | 1455.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 633.03 | 746.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 882.67 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 141.78 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 866.12 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 | 19-FEB-13:32 | 201.00 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 895.79 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.74 | 26-MAR-13:00 | 509.75 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 688.60 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.57 | 15-APR-17:06 | 81.16 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 725.76 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.72 | 28-MAY-14:53 | 54.19 | 15-MAY-02:45 |
June | 1295.83 | 01-JUN-09:09 | 727.43 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.33 | 03-JUN-17:07 | 43.61 | 18-JUN-02:35 |
July | 1295.83 | 03-JUL-09:09 | 853.00 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.68 | 02-JUL-11:44 | 32.69 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 876.20 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.22 | 06-AUG-14:00 | 44.32 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 899.69 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.41 | 24-SEP-14:14 | 17.79 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 946.46 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.57 | 15-OCT-12:11 | 63.83 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 837.30 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 12-NOV-12:51 | 104.49 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 852.12 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 24-DEC-13:52 | 216.60 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 688.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | |||||
Maximum of Months | 1295.83 | 946.46 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 418.72 | 509.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1361.28 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 08-JAN-14:53 | 219.35 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1330.13 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.72 | 19-FEB-15:00 | 335.72 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1343.36 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 241.22 | 26-MAR-14:53 | 751.90 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 861.71 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.58 | 15-APR-17:06 | 117.43 | 22-APR-17:55 |
May | 2010.79 | 01-MAY-09:09 | 921.38 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 774.28 | 28-MAY-14:53 | 83.40 | 15-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 919.60 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.57 | 03-JUN-17:08 | 71.15 | 18-JUN-03:53 |
July | 2010.79 | 03-JUL-09:09 | 1287.06 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.99 | 02-JUL-11:44 | 54.54 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1333.61 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.80 | 06-AUG-13:44 | 77.05 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1380.23 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.55 | 24-SEP-14:56 | 29.13 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 1463.18 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.66 | 15-OCT-12:00 | 106.29 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1423.09 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.54 | 12-NOV-14:00 | 161.59 | 29-NOV-24:00 |
December | 2010.79 | 01-DEC-10:09 | 1438.70 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 24-DEC-14:00 | 353.43 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 861.71 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 29.13 | |||||
Maximum of Months | 2010.79 | 1463.18 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 774.28 | 751.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 864.39 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 08-JAN-14:53 | 146.05 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 859.41 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 | 19-FEB-15:00 | 222.73 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 746.76 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.14 | 26-MAR-14:36 | 550.09 | 24-MAR-22:55 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.75 | 15-APR-17:06 | 95.52 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 574.11 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.18 | 28-MAY-14:53 | 62.79 | 15-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 574.57 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.34 | 03-JUN-17:07 | 48.68 | 18-JUN-03:53 |
July | 1295.83 | 03-JUL-09:09 | 793.40 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.92 | 02-JUL-11:44 | 36.13 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 826.71 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.57 | 06-AUG-13:44 | 53.40 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 859.97 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.26 | 24-SEP-14:54 | 19.37 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 924.15 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.36 | 15-OCT-12:14 | 71.43 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 938.11 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 12-NOV-14:30 | 114.31 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 933.18 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.07 | 24-DEC-14:00 | 236.86 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 19.37 | |||||
Maximum of Months | 1295.83 | 938.11 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 516.18 | 550.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1302.35 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 317.40 | 22-JAN-15:00 |
February | 2010.83 | 01-FEB-10:09 | 1282.89 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 21-FEB-15:00 | 343.50 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1325.51 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.70 | 26-MAR-15:14 | 900.46 | 24-MAR-22:55 |
April | 2010.83 | 03-APR-09:09 | 871.37 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.12 | 15-APR-17:06 | 136.53 | 22-APR-17:55 |
May | 2010.83 | 01-MAY-09:09 | 1060.84 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 774.28 | 28-MAY-14:53 | 87.79 | 15-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 1072.41 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.19 | 03-JUN-17:08 | 70.61 | 18-JUN-03:53 |
July | 2010.83 | 03-JUL-09:09 | 1308.53 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.67 | 02-JUL-11:44 | 54.33 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1343.14 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.73 | 06-AUG-13:44 | 79.36 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1377.43 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.08 | 24-SEP-15:00 | 29.55 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 1454.91 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.62 | 15-OCT-12:54 | 110.09 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1253.85 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.20 | 13-NOV-14:00 | 200.89 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1363.22 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 28-DEC-14:00 | 515.25 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 871.37 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 | |||||
Maximum of Months | 2010.83 | 1454.91 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 774.28 | 900.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 882.30 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 08-JAN-13:53 | 159.99 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 865.71 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 19-FEB-13:42 | 236.36 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 895.45 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.07 | 26-MAR-12:53 | 613.46 | 24-MAR-22:55 |
April | 1295.83 | 03-APR-09:09 | 688.15 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.28 | 15-APR-17:10 | 95.48 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 725.08 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.18 | 28-MAY-14:53 | 74.04 | 15-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 726.74 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.75 | 17-JUN-19:47 | 57.49 | 18-JUN-02:23 |
July | 1295.83 | 03-JUL-09:09 | 852.55 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.13 | 02-JUL-11:44 | 39.24 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 875.80 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.62 | 06-AUG-13:44 | 57.62 | 15-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 899.34 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.03 | 24-SEP-14:14 | 21.66 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 946.21 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.72 | 15-OCT-12:16 | 75.55 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 836.98 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 12-NOV-12:51 | 124.00 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 851.78 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 24-DEC-13:43 | 252.09 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 688.15 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 21.66 | |||||
Maximum of Months | 1295.83 | 946.21 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 516.18 | 613.46 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 213.00 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 19-FEB-14:53 | 308.20 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.94 | 26-MAR-15:00 | 677.92 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.73 | 15-APR-17:01 | 114.78 | 22-APR-18:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.32 | 28-MAY-14:50 | 64.96 | 15-MAY-03:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.68 | 03-JUN-17:02 | 56.97 | 18-JUN-04:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.67 | 02-JUL-11:31 | 46.95 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 06-AUG-14:10 | 51.15 | 15-AUG-23:57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.41 | 24-SEP-14:20 | 27.15 | 08-SEP-22:30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.14 | 15-OCT-12:50 | 89.77 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 12-NOV-13:41 | 159.60 | 28-NOV-05:14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 28-DEC-14:00 | 336.78 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.32 | 677.92 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 357.04 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 19-FEB-15:00 | 538.48 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.95 | 26-MAR-14:42 | 1172.82 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.33 | 15-APR-17:01 | 172.83 | 22-APR-18:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.58 | 28-MAY-15:00 | 76.77 | 15-MAY-02:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.79 | 03-JUN-17:02 | 84.07 | 18-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.12 | 02-JUL-12:00 | 68.93 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.54 | 06-AUG-14:00 | 78.79 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.18 | 24-SEP-14:00 | 36.14 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.53 | 15-OCT-12:30 | 149.04 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 12-NOV-14:10 | 266.12 | 28-NOV-05:14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 24-DEC-14:00 | 571.22 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.58 | 1172.82 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 352.16 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 | 24-FEB-15:00 | 557.46 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.01 | 26-MAR-15:00 | 1200.86 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.24 | 15-APR-17:01 | 143.56 | 22-APR-18:25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936.05 | 28-MAY-15:00 | 99.01 | 15-MAY-03:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.70 | 03-JUN-17:10 | 90.87 | 18-JUN-03:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.96 | 02-JUL-11:30 | 67.62 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.74 | 06-AUG-08:52 | 108.92 | 15-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.74 | 24-SEP-14:00 | 34.37 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.78 | 15-OCT-11:51 | 152.83 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.13 | 12-NOV-14:10 | 249.03 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.64 | 24-DEC-14:00 | 551.84 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936.05 | 1200.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 104666.38 | 23-JAN-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99863.90 | 21-FEB-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98367.83 | 06-MAR-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100356.77 | 23-APR-05:52 | 4488.06 | 4095.26 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 103624.88 | 09-OCT-00:31 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98375.48 | 20-NOV-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 100327.06 | 11-DEC-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 104666.38 | 4488.06 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90293.14 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95665.44 | 21-FEB-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92597.94 | 06-MAR-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97391.56 | 17-APR-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97208.16 | 01-MAY-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92097.69 | 09-JUN-04:24 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95079.57 | 06-JUL-03:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98329.10 | 14-AUG-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98317.74 | 25-SEP-03:14 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97333.46 | 30-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96623.13 | 20-NOV-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96212.27 | 26-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90293.14 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98329.10 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76587.97 | 27-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82242.68 | 27-FEB-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84030.59 | 08-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82884.64 | 11-APR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79631.32 | 13-MAY-04:12 | 0.00 | 2149.44 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75511.79 | 12-JUN-05:01 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68839.61 | 28-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77961.39 | 21-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81509.50 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84396.85 | 26-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83814.15 | 10-NOV-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80045.28 | 01-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 68839.61 | 0.00 | 2149.44 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84396.85 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32438.91 | 26-JAN-16:30 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77988.58 | 23-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84408.93 | 14-MAR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84571.67 | 10-APR-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85728.58 | 30-MAY-04:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86977.92 | 12-JUN-05:01 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83222.44 | 05-JUL-05:03 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85173.62 | 07-AUG-05:04 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81755.40 | 13-SEP-04:03 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84307.31 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79606.80 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33671.34 | 01-DEC-16:20 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 32438.91 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86977.92 | 15316.26 | 13241.18 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4477.59 | 26-JAN-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 |
February | 6620.84 | 23-FEB-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 0.00 |
March | 16038.35 | 13-MAR-05:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 |
April | 22766.00 | 30-APR-15:02 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 117.78 | 0.00 |
May | 24129.61 | 28-MAY-17:02 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 205.94 | 0.00 |
June | 22193.92 | 11-JUN-15:41 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.02 | 0.00 |
July | 23357.03 | 04-JUL-17:03 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 0.00 |
August | 21019.86 | 06-AUG-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.75 | 0.00 |
September | 21018.91 | 24-SEP-15:52 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.13 | 0.00 |
October | 21243.15 | 08-OCT-14:51 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
November | 7269.82 | 09-NOV-14:20 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
December | 5413.28 | 26-DEC-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4477.59 | 0.00 | 263.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24129.61 | 4021.58 | 1582.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 205.94 | 10.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4411.40 | 26-JAN-10:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 |
February | 9022.16 | 20-FEB-10:13 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.46 |
March | 17212.89 | 12-MAR-11:02 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 0.00 |
April | 20312.29 | 30-APR-09:43 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 0.00 |
May | 20953.44 | 29-MAY-09:02 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 102.33 | 0.00 |
June | 18335.02 | 11-JUN-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 0.00 |
July | 19560.50 | 04-JUL-09:43 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 0.00 |
August | 17347.54 | 06-AUG-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 | 0.00 |
September | 17301.20 | 24-SEP-09:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 | 0.00 |
October | 17869.36 | 09-OCT-10:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9262.43 | 05-NOV-10:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 |
December | 4989.61 | 01-DEC-10:00 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4411.40 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20953.44 | 1295.83 | 509.78 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 102.33 | 18.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13538.42 | 12-JAN-13:50 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
February | 24067.26 | 20-FEB-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 |
March | 22967.85 | 05-MAR-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 0.00 |
April | 24203.61 | 30-APR-13:03 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 99.84 | 0.00 |
May | 24376.33 | 28-MAY-15:02 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 252.94 | 0.00 |
June | 22332.28 | 11-JUN-15:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 0.00 |
July | 23193.98 | 04-JUL-13:03 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 65.46 | 0.00 |
August | 21635.35 | 06-AUG-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 79.36 | 0.00 |
September | 22641.71 | 24-SEP-13:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 54.69 | 0.00 |
October | 24862.66 | 08-OCT-13:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
November | 23314.22 | 26-NOV-11:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
December | 22589.56 | 24-DEC-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13538.42 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24862.66 | 1923.15 | 791.06 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 252.94 | 40.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7335.19 | 31-JAN-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
February | 23056.75 | 20-FEB-14:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
March | 22960.84 | 05-MAR-14:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
April | 26966.36 | 02-APR-15:41 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 | 0.00 |
May | 27188.50 | 28-MAY-16:22 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.62 | 0.00 |
June | 24706.45 | 11-JUN-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 0.00 |
July | 24631.83 | 04-JUL-16:23 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 0.00 |
August | 22981.67 | 06-AUG-15:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 47.38 | 0.00 |
September | 22765.69 | 24-SEP-15:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 | 0.00 |
October | 24669.02 | 08-OCT-14:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 0.00 |
November | 19707.90 | 06-NOV-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18695.64 | 24-DEC-15:23 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7335.19 | 0.00 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27188.50 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.62 | 17.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2846.02 | 26-JAN-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
February | 5400.24 | 24-FEB-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 0.00 |
March | 11325.01 | 29-MAR-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21214.87 | 02-APR-15:41 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 227.33 | 0.00 |
May | 23274.44 | 29-MAY-16:31 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 157.85 | 0.00 |
June | 21843.75 | 11-JUN-16:21 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 112.35 | 0.00 |
July | 21642.27 | 02-JUL-17:01 | 0.00 | 307.61 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 179.80 | 0.00 |
August | 21661.76 | 27-AUG-14:32 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.39 | 0.00 |
September | 21373.89 | 17-SEP-14:51 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 137.32 | 0.00 |
October | 21206.69 | 01-OCT-15:11 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 73.62 | 0.00 |
November | 5982.28 | 09-NOV-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 0.00 |
December | 2621.52 | 28-DEC-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2621.52 | 0.00 | 263.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23274.44 | 2010.79 | 791.05 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 227.33 | 12.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5241.57 | 26-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
February | 8030.34 | 22-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
March | 18512.21 | 12-MAR-10:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 |
April | 19109.41 | 16-APR-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
May | 21379.81 | 29-MAY-09:51 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 219.28 | 0.00 |
June | 18818.96 | 11-JUN-10:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 62.07 | 0.00 |
July | 18639.72 | 04-JUL-10:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 88.20 | 0.00 |
August | 18274.73 | 06-AUG-09:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 102.70 | 0.00 |
September | 18290.30 | 17-SEP-14:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 88.02 | 0.00 |
October | 19392.68 | 01-OCT-09:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
November | 8475.72 | 01-NOV-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
December | 5543.74 | 01-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5241.57 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21379.81 | 2478.65 | 1019.56 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 219.28 | 15.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15234.43 | 08-JAN-15:53 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 |
February | 22893.54 | 19-FEB-14:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.77 |
March | 23545.43 | 12-MAR-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 0.00 |
April | 22676.87 | 02-APR-15:41 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 194.79 | 0.00 |
May | 23408.95 | 29-MAY-15:51 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 218.26 | 0.00 |
June | 21723.19 | 11-JUN-16:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 112.84 | 0.00 |
July | 21581.95 | 02-JUL-16:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 | 0.00 |
August | 22220.87 | 27-AUG-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 77.62 | 0.00 |
September | 23200.64 | 17-SEP-14:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 113.67 | 0.00 |
October | 24929.58 | 01-OCT-15:11 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 52.90 | 0.00 |
November | 24738.88 | 12-NOV-13:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 |
December | 22947.34 | 03-DEC-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15234.43 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24929.58 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 218.26 | 67.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5160.11 | 31-JAN-16:10 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 |
February | 9525.37 | 20-FEB-16:23 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 |
March | 20429.28 | 12-MAR-14:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 | 0.00 |
April | 22829.35 | 02-APR-16:21 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.46 | 0.00 |
May | 24764.79 | 28-MAY-16:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 273.03 | 0.00 |
June | 21971.11 | 11-JUN-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 | 0.00 |
July | 21635.56 | 02-JUL-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 113.11 | 0.00 |
August | 21249.29 | 06-AUG-16:11 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 91.92 | 0.00 |
September | 21432.87 | 17-SEP-14:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 75.49 | 0.00 |
October | 22408.80 | 01-OCT-15:11 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 0.00 |
November | 19731.19 | 12-NOV-15:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 0.00 |
December | 5862.74 | 01-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5160.11 | 260.91 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24764.79 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 273.03 | 10.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2762.60 | 26-JAN-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 |
February | 5646.83 | 23-FEB-14:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 0.00 |
March | 20724.24 | 12-MAR-15:31 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 58.63 | 0.00 |
April | 25474.39 | 30-APR-15:51 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 313.50 | 0.00 |
May | 25363.68 | 21-MAY-16:11 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24983.99 | 11-JUN-15:41 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 146.12 | 0.00 |
July | 24787.53 | 02-JUL-17:01 | 0.00 | 307.61 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 216.76 | 0.00 |
August | 23748.78 | 06-AUG-15:42 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.26 | 0.00 |
September | 24625.22 | 17-SEP-14:51 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 159.66 | 0.00 |
October | 23563.13 | 01-OCT-15:21 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 87.28 | 0.00 |
November | 6463.39 | 09-NOV-14:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 0.00 |
December | 2526.28 | 28-DEC-16:00 | 1923.11 | 839.49 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2526.28 | 0.00 | 263.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25474.39 | 2010.79 | 839.49 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 313.50 | 16.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2976.92 | 26-JAN-14:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
February | 6152.78 | 23-FEB-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 |
March | 19122.45 | 12-MAR-10:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
April | 21573.36 | 30-APR-09:51 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 | 0.00 |
May | 20258.51 | 29-MAY-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 329.68 | 0.00 |
June | 19737.16 | 11-JUN-10:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 75.13 | 0.00 |
July | 19506.27 | 04-JUL-10:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 106.83 | 0.00 |
August | 18590.31 | 06-AUG-15:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 149.37 | 0.00 |
September | 19545.62 | 17-SEP-14:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 101.71 | 0.00 |
October | 19719.40 | 01-OCT-11:21 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 40.48 | 0.00 |
November | 6412.22 | 09-NOV-10:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
December | 3017.95 | 01-DEC-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2976.92 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21573.36 | 1295.83 | 509.78 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 329.68 | 9.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13405.94 | 12-JAN-14:20 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
February | 26165.68 | 20-FEB-14:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
March | 26456.12 | 12-MAR-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 0.00 |
April | 26781.66 | 30-APR-14:31 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 271.89 | 0.00 |
May | 25397.59 | 21-MAY-16:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24893.97 | 11-JUN-15:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 146.22 | 0.00 |
July | 24679.76 | 02-JUL-16:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 225.59 | 0.00 |
August | 24125.65 | 06-AUG-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 226.15 | 0.00 |
September | 26532.34 | 17-SEP-14:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 131.48 | 0.00 |
October | 27939.13 | 01-OCT-12:01 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 0.00 |
November | 27524.26 | 05-NOV-13:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
December | 15240.56 | 01-DEC-13:50 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13405.94 | 607.31 | 263.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27939.13 | 2010.83 | 791.06 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 271.89 | 13.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5073.77 | 12-JAN-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
February | 11885.55 | 20-FEB-16:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
March | 23502.18 | 12-MAR-16:11 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | 0.00 |
April | 26570.87 | 30-APR-15:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 153.45 | 0.00 |
May | 25380.54 | 21-MAY-16:11 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24107.71 | 11-JUN-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 89.95 | 0.00 |
July | 23833.12 | 02-JUL-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 136.76 | 0.00 |
August | 22522.18 | 06-AUG-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 115.04 | 0.00 |
September | 23682.68 | 17-SEP-14:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 88.12 | 0.00 |
October | 23507.12 | 15-OCT-15:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 66.81 | 0.00 |
November | 21515.96 | 05-NOV-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 | 0.00 |
December | 5718.35 | 28-DEC-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5073.77 | 326.14 | 141.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26570.87 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 153.45 | 11.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3146.43 | 12-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
February | 9583.00 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
March | 14001.57 | 14-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
April | 20197.78 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
May | 24603.89 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 0.00 |
June | 25030.96 | 12-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 | 0.00 |
July | 25750.77 | 05-JUL-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 0.00 |
August | 24308.78 | 07-AUG-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 0.00 |
September | 19560.97 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
October | 19928.09 | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
November | 11749.02 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 |
December | 7126.93 | 26-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3146.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25750.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 | 10.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2766.60 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4990.53 | 22-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 0.00 |
March | 10144.22 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.58 |
April | 14438.32 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
May | 18259.23 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
June | 18996.55 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.90 | 0.00 |
July | 19247.43 | 03-JUL-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 0.00 |
August | 14352.31 | 08-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 0.00 |
September | 13590.77 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 0.00 |
October | 13130.08 | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 7082.61 | 09-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
December | 3177.89 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2766.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19247.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 50.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5988.96 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
February | 13172.40 | 22-FEB-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 0.00 |
March | 22046.25 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27656.18 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.20 | 0.00 |
May | 31738.75 | 01-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.05 | 0.00 |
June | 33599.39 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.59 | 0.00 |
July | 29916.14 | 07-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.76 | 0.00 |
August | 26533.11 | 07-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 0.00 |
September | 22452.22 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.41 | 0.00 |
October | 21910.01 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.01 | 0.00 |
November | 14356.10 | 09-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 0.00 |
December | 7605.61 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5988.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33599.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.59 | 20.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1832.43 | 12-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3980.61 | 20-FEB-17:20 | 11.69 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7254.55 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7926.94 | 16-APR-21:32 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3605.38 | 31-MAY-23:53 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5628.75 | 30-JUN-23:53 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7531.26 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7800.96 | 20-AUG-17:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3700.67 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5382.61 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5889.70 | 12-NOV-16:12 | 58.46 | 87.96 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7572.52 | 24-DEC-17:10 | 11.69 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1832.43 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7926.94 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1673.42 | 12-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3589.04 | 21-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6972.93 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7343.25 | 16-APR-21:03 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3403.15 | 31-MAY-23:53 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5257.26 | 30-JUN-23:53 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7007.11 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7212.23 | 20-AUG-17:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3403.69 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5090.97 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5435.66 | 08-NOV-16:40 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7162.43 | 01-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1673.42 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7343.25 | 222.14 | 316.63 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1699.49 | 12-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3639.11 | 22-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6927.38 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7632.79 | 16-APR-21:32 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3348.89 | 31-MAY-23:53 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5325.84 | 30-JUN-23:53 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7059.67 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7439.79 | 20-AUG-17:03 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3421.96 | 30-SEP-23:45 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4959.46 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5482.55 | 09-NOV-16:40 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7167.08 | 28-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1699.49 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7632.79 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92203.80 | 26-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183837.27 | 21-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358960.25 | 31-MAR-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368311.98 | 17-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177383.30 | 31-MAY-23:53 | 0.00 | 692.81 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269831.60 | 30-JUN-23:53 | 0.00 | 692.81 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362655.29 | 31-JUL-23:57 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371414.13 | 07-AUG-13:05 | 10055.84 | 8314.37 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 179208.43 | 30-SEP-24:00 | 0.00 | 461.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269356.17 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277106.31 | 13-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368151.72 | 04-DEC-16:40 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92203.80 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371414.13 | 10055.84 | 8314.37 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.168319E+13 | 1273285.97 | 02-JAN-08:09 | 0.00 | 0.00 |
February | 0.193957E+13 | 1513168.60 | 22-FEB-16:10 | 0.00 | 0.00 |
March | 0.276567E+13 | 1767650.10 | 28-MAR-15:00 | 0.00 | 0.00 |
April | 0.323548E+13 | 2047344.09 | 18-APR-15:20 | 0.00 | 0.00 |
May | 0.231657E+13 | 1666146.54 | 30-MAY-14:20 | 0.00 | 0.00 |
June | 0.277828E+13 | 1887865.15 | 22-JUN-15:20 | 0.00 | 0.00 |
July | 0.324369E+13 | 2053134.03 | 05-JUL-15:00 | 0.00 | 0.00 |
August | 0.370341E+13 | 2177920.65 | 07-AUG-15:30 | 0.00 | 0.00 |
September | 0.219282E+13 | 1641110.96 | 14-SEP-15:30 | 0.00 | 0.00 |
October | 0.242029E+13 | 1663380.43 | 02-OCT-15:39 | 0.00 | 0.00 |
November | 0.256672E+13 | 1702155.98 | 09-NOV-16:00 | 0.00 | 0.00 |
December | 0.288948E+13 | 1680941.88 | 28-DEC-15:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.317352E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.168319E+13 | 1273285.97 | 0.00 | 0.00 | |
Maximum of Months | 0.370341E+13 | 2177920.65 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.206783E+12 | 0.361832E+11 | 0.766053E+12 | 0.213315E+12 | 0.176048E+12 | 0.420513E+11 | 0.317807E+11 | 0.125753E+12 | 0.414560E+11 | 0.122311E+11 | 0.00 | 0.315336E+11 | 0.00 |
February | 0.186910E+12 | 0.303449E+11 | 0.978954E+12 | 0.195308E+12 | 0.172726E+12 | 0.405806E+11 | 0.463697E+10 | 0.216416E+12 | 0.716659E+11 | 0.139547E+11 | 0.00 | 0.280712E+11 | 0.00 |
March | 0.220926E+12 | 0.301927E+11 | 0.141687E+13 | 0.226028E+12 | 0.227082E+12 | 0.579258E+11 | 26762.39 | 0.419774E+12 | 0.126755E+12 | 0.925834E+10 | 0.00 | 0.308546E+11 | 0.00 |
April | 0.196482E+12 | 0.260362E+11 | 0.165903E+13 | 0.211475E+12 | 0.254161E+12 | 0.757266E+11 | 0.00 | 0.640082E+12 | 0.146443E+12 | 0.825944E+09 | 0.00 | 0.252211E+11 | 0.00 |
May | 0.211614E+12 | 0.240896E+11 | 0.774844E+12 | 0.219671E+12 | 0.285438E+12 | 0.873708E+11 | 0.00 | 0.500655E+12 | 0.188960E+12 | 16704371.31 | 0.00 | 0.239128E+11 | 0.00 |
June | 0.210701E+12 | 0.218994E+11 | 0.106252E+13 | 0.217906E+12 | 0.283685E+12 | 0.896751E+11 | 0.00 | 0.671381E+12 | 0.199155E+12 | 0.00 | 0.00 | 0.213605E+11 | 0.00 |
July | 0.197509E+12 | 0.235907E+11 | 0.139340E+13 | 0.213240E+12 | 0.271203E+12 | 0.949054E+11 | 0.00 | 0.817596E+12 | 0.212799E+12 | 0.00 | 0.00 | 0.194454E+11 | 0.00 |
August | 0.220711E+12 | 0.257509E+11 | 0.173200E+13 | 0.226028E+12 | 0.275436E+12 | 0.975093E+11 | 0.00 | 0.890869E+12 | 0.213135E+12 | 0.00 | 0.00 | 0.219655E+11 | 0.00 |
September | 0.197370E+12 | 0.276816E+11 | 0.740713E+12 | 0.211475E+12 | 0.238297E+12 | 0.829870E+11 | 0.00 | 0.476190E+12 | 0.196147E+12 | 0.00 | 0.00 | 0.219604E+11 | 0.00 |
October | 0.205724E+12 | 0.320159E+11 | 0.108340E+13 | 0.213315E+12 | 0.229961E+12 | 0.673121E+11 | 0.00 | 0.411347E+12 | 0.149853E+12 | 0.181351E+10 | 0.00 | 0.255466E+11 | 0.00 |
November | 0.204319E+12 | 0.341881E+11 | 0.135889E+13 | 0.205269E+12 | 0.200945E+12 | 0.497313E+11 | 0.170458E+09 | 0.361988E+12 | 0.107091E+12 | 0.162094E+11 | 0.00 | 0.279196E+11 | 0.00 |
December | 0.200409E+12 | 0.373354E+11 | 0.170972E+13 | 0.213240E+12 | 0.186180E+12 | 0.446443E+11 | 0.896431E+10 | 0.340923E+12 | 0.799503E+11 | 0.381811E+11 | 0.00 | 0.299330E+11 | 0.00 |
Annual Sum or Average | 0.245946E+13 | 0.349309E+12 | 0.146764E+14 | 0.256627E+13 | 0.280116E+13 | 0.830420E+12 | 0.455525E+11 | 0.587297E+13 | 0.173341E+13 | 0.924907E+11 | 0.00 | 0.307724E+12 | 0.00 |
Minimum of Months | 0.186910E+12 | 0.218994E+11 | 0.740713E+12 | 0.195308E+12 | 0.172726E+12 | 0.405806E+11 | 0.00 | 0.125753E+12 | 0.414560E+11 | 0.00 | 0.00 | 0.194454E+11 | 0.00 |
Maximum of Months | 0.220926E+12 | 0.373354E+11 | 0.173200E+13 | 0.226028E+12 | 0.285438E+12 | 0.975093E+11 | 0.317807E+11 | 0.890869E+12 | 0.213135E+12 | 0.381811E+11 | 0.00 | 0.315336E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 233997.28 | 18-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233390.30 | 18-JAN-08:20 | 116350.16 | 12-JAN-15:30 | 25681.89 | 12-JAN-15:09 | 550160.60 | 02-JAN-06:10 |
February | 232898.07 | 10-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233389.72 | 10-FEB-08:20 | 156399.55 | 22-FEB-16:10 | 27001.23 | 23-FEB-13:00 | 158560.65 | 11-FEB-06:10 |
March | 233370.01 | 14-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233389.97 | 14-MAR-07:19 | 196891.28 | 14-MAR-15:39 | 49522.90 | 27-MAR-13:30 | 44.60 | 01-MAR-06:00 |
April | 216805.19 | 03-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233381.20 | 03-APR-07:19 | 221037.20 | 17-APR-15:20 | 49523.25 | 19-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 221022.76 | 24-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233383.43 | 24-MAY-07:19 | 252054.28 | 30-MAY-14:20 | 50108.55 | 30-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 221165.50 | 23-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 233383.51 | 23-JUN-07:19 | 251724.80 | 13-JUN-14:09 | 50322.56 | 09-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 232541.22 | 26-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 233389.53 | 26-JUL-07:19 | 259488.91 | 06-JUL-15:00 | 50589.94 | 03-JUL-05:19 | 0.00 | 01-JUL-00:10 |
August | 234187.88 | 16-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233390.40 | 16-AUG-07:19 | 241238.99 | 08-AUG-15:39 | 49724.90 | 07-AUG-14:30 | 0.00 | 01-AUG-00:10 |
September | 235834.97 | 08-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233391.27 | 08-SEP-07:19 | 217306.78 | 18-SEP-15:30 | 49245.38 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 239082.52 | 11-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233393.00 | 11-OCT-07:19 | 201601.61 | 10-OCT-15:39 | 50659.79 | 24-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 234185.02 | 27-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233384.45 | 03-NOV-07:19 | 163733.34 | 13-NOV-16:19 | 50093.92 | 06-NOV-13:50 | 25217.51 | 27-NOV-06:30 |
December | 236669.35 | 29-DEC-16:00 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233383.54 | 29-DEC-08:20 | 131040.88 | 01-DEC-15:50 | 26159.95 | 01-DEC-13:00 | 213524.32 | 23-DEC-06:30 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 216805.19 | 40855.88 | 423497.50 | 233381.20 | 116350.16 | 25681.89 | 0.00 | |||||||
Maximum of Months | 239082.52 | 40855.88 | 778371.69 | 233393.00 | 259488.91 | 50659.79 | 550160.60 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 126657.49 | 12-JAN-15:09 | 44938.65 | 12-JAN-15:50 | 7657.72 | 21-JAN-17:19 | 0.00 | 41462.49 | 17-JAN-12:30 | 0.00 |
February | 272937.64 | 22-FEB-15:30 | 63913.76 | 24-FEB-14:50 | 11061.75 | 05-FEB-10:09 | 0.00 | 41183.70 | 01-FEB-12:00 | 0.00 |
March | 344311.45 | 28-MAR-12:09 | 84051.29 | 06-MAR-13:00 | 13864.17 | 03-MAR-05:00 | 0.00 | 39411.61 | 01-MAR-12:39 | 0.00 |
April | 460656.42 | 18-APR-15:50 | 84051.29 | 01-APR-14:00 | 11108.37 | 11-APR-04:00 | 0.00 | 35953.78 | 03-APR-11:50 | 0.00 |
May | 421813.39 | 30-MAY-15:09 | 84051.29 | 16-MAY-21:00 | 2126.62 | 28-MAY-14:00 | 0.00 | 31776.80 | 01-MAY-11:20 | 0.00 |
June | 539984.43 | 22-JUN-15:39 | 84051.29 | 11-JUN-03:49 | 0.00 | 01-JUN-00:10 | 0.00 | 28704.90 | 01-JUN-11:39 | 0.00 |
July | 535070.41 | 05-JUL-15:00 | 84051.29 | 01-JUL-00:40 | 0.00 | 01-JUL-00:10 | 0.00 | 26582.19 | 03-JUL-11:39 | 0.00 |
August | 567251.39 | 28-AUG-14:30 | 84051.29 | 01-AUG-00:40 | 0.00 | 01-AUG-00:10 | 0.00 | 28493.45 | 31-AUG-11:20 | 0.00 |
September | 407440.60 | 14-SEP-14:30 | 84051.29 | 01-SEP-00:40 | 0.00 | 01-SEP-00:10 | 0.00 | 31293.97 | 29-SEP-11:00 | 0.00 |
October | 354302.36 | 02-OCT-15:39 | 84051.29 | 02-OCT-07:40 | 7644.31 | 31-OCT-23:00 | 0.00 | 35285.86 | 30-OCT-11:00 | 0.00 |
November | 324236.88 | 16-NOV-14:30 | 84051.29 | 06-NOV-11:30 | 14915.36 | 30-NOV-22:00 | 0.00 | 38985.26 | 30-NOV-12:39 | 0.00 |
December | 236469.86 | 28-DEC-15:09 | 45603.85 | 28-DEC-14:00 | 29206.62 | 22-DEC-06:00 | 0.00 | 40817.29 | 26-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 126657.49 | 44938.65 | 0.00 | 0.00 | 26582.19 | 0.00 | ||||
Maximum of Months | 567251.39 | 84051.29 | 29206.62 | 0.00 | 41462.49 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1273285.97 | 02-JAN-08:09 | 218297.05 | 423497.50 | 0.00 | 233306.12 | 78881.19 | 25125.28 | 226872.66 | 36014.09 | 2647.29 |
February | 1513168.60 | 22-FEB-16:10 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 156399.55 | 26505.44 | 0.00 | 265544.46 | 47278.40 |
March | 1767650.10 | 28-MAR-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 171618.08 | 48311.03 | 0.00 | 329287.36 | 84051.29 |
April | 2047344.09 | 18-APR-15:20 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 211236.36 | 48682.56 | 0.00 | 453420.69 | 84051.29 |
May | 1666146.54 | 30-MAY-14:20 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 252054.28 | 49339.72 | 0.00 | 394965.59 | 84051.29 |
June | 1887865.15 | 22-JUN-15:20 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 209308.38 | 50033.55 | 0.00 | 536266.49 | 84051.29 |
July | 2053134.03 | 05-JUL-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 257805.74 | 49847.02 | 0.00 | 535070.41 | 84051.29 |
August | 2177920.65 | 07-AUG-15:30 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 240144.92 | 49669.87 | 0.00 | 559357.83 | 84051.29 |
September | 1641110.96 | 14-SEP-15:30 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 209139.26 | 49133.90 | 0.00 | 406143.61 | 84051.29 |
October | 1663380.43 | 02-OCT-15:39 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 163081.86 | 49318.05 | 0.00 | 354302.36 | 84051.29 |
November | 1702155.98 | 09-NOV-16:00 | 223178.81 | 660080.29 | 0.00 | 233270.18 | 155134.53 | 26322.30 | 0.00 | 312229.93 | 63913.76 |
December | 1680941.88 | 28-DEC-15:30 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 126435.91 | 25711.68 | 0.00 | 235060.34 | 45580.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1273285.97 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 78881.19 | 25125.28 | 0.00 | 36014.09 | 2647.29 | |
Maximum of Months | 2177920.65 | 223178.81 | 778371.69 | 0.00 | 233306.12 | 257805.74 | 50033.55 | 226872.66 | 559357.83 | 84051.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.95 | 2.33 | 27.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.24 | 8.00 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 168.33 | 27.95 | 119.00 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 606.83 | 29.10 | 410.17 | 29.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.94 | 508.00 | 29.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.35 | 496.00 | 30.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.78 | 497.00 | 30.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 31.09 | 514.00 | 31.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.79 | 485.00 | 30.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 435.33 | 28.60 | 283.00 | 28.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 27.38 | 24.50 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.28 | 8.50 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 4966.33 | 30.09 | 3355.50 | 30.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.95 | 2.33 | 27.05 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 31.09 | 514.00 | 31.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.77 | 0.00 | 25.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.89 | 0.83 | 25.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.13 | 0.17 | 26.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.19 | 0.33 | 26.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 26.49 | 2.67 | 26.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 26.60 | 1.83 | 26.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 26.34 | 0.50 | 26.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.91 | 0.00 | 25.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Annual Sum or Average | 0.00 | 0.00 | 90.50 | 26.31 | 6.33 | 26.30 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 26.60 | 2.67 | 26.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.10 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.94 | 0.00 | 25.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.67 | 0.00 | 25.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.86 | 0.00 | 25.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.10 | 0.17 | 19.28 | 1.83 | 23.52 | 0.00 | 23.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.10 | 0.17 | 19.28 | 0.67 | 25.94 | 0.00 | 25.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.88 | 0.50 | 27.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.16 | 9.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 27.32 | 15.50 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 27.33 | 14.67 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 | 27.48 | 20.83 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 27.32 | 13.33 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 26.97 | 9.83 | 27.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.11 | 3.83 | 27.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 277.67 | 27.31 | 87.67 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 | 27.48 | 20.83 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.83 | 27.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.52 | 4.50 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.47 | 13.67 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 27.47 | 20.83 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 59.00 | 27.36 | 18.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 27.56 | 20.83 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 27.36 | 13.00 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 27.14 | 11.83 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.51 | 10.33 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 319.33 | 27.42 | 115.33 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 27.56 | 20.83 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.67 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.84 | 5.17 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.61 | 6.83 | 27.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.37 | 12.00 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 27.34 | 14.67 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.27 | 13.00 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 27.43 | 19.50 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 27.30 | 12.83 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 26.99 | 12.17 | 27.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.15 | 18.83 | 27.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.01 | 11.67 | 28.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.66 | 5.67 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 326.17 | 27.34 | 134.00 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.99 | 1.67 | 27.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 28.01 | 19.50 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.72 | 3.83 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.37 | 8.17 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 27.77 | 22.83 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 71.33 | 27.64 | 20.67 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 27.70 | 18.50 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 85.50 | 27.80 | 25.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 78.50 | 27.72 | 20.67 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 27.22 | 12.17 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.49 | 12.50 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.52 | 8.33 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.49 | 5.00 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 487.67 | 27.65 | 158.33 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 85.50 | 27.80 | 25.67 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.09 | 3.67 | 27.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.22 | 9.33 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.02 | 6.00 | 27.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.20 | 11.67 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 26.88 | 5.83 | 27.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.10 | 2.50 | 27.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.22 | 0.00 | 19.22 | 99.17 | 27.10 | 39.67 | 27.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.22 | 0.00 | 19.22 | 27.33 | 27.31 | 11.67 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.56 | 5.00 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.57 | 12.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.51 | 13.83 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 27.26 | 11.00 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.42 | 14.33 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.10 | 8.17 | 27.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.29 | 5.67 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.68 | 10.00 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.31 | 0.00 | 19.31 | 172.17 | 27.39 | 80.50 | 27.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.31 | 0.00 | 19.31 | 36.67 | 27.68 | 14.33 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.48 | 2.00 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.91 | 4.83 | 27.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.81 | 6.33 | 27.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.40 | 8.83 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.28 | 9.67 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.01 | 6.17 | 27.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.21 | 11.33 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.03 | 6.83 | 27.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.18 | 5.00 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.31 | 17.33 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.05 | 11.50 | 28.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.66 | 4.50 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 175.00 | 27.33 | 94.33 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.01 | 2.00 | 27.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 28.05 | 17.33 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.76 | 3.33 | 27.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.48 | 10.67 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 27.55 | 16.67 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 27.48 | 11.67 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 27.48 | 15.67 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.21 | 8.50 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.07 | 5.83 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.73 | 6.17 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.50 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 249.67 | 27.45 | 82.17 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 27.76 | 16.67 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.24 | 0.17 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.31 | 5.67 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 27.45 | 10.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 27.23 | 7.83 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.40 | 13.00 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.11 | 7.33 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.30 | 4.17 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.45 | 1.83 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 2.17 | 18.42 | 0.17 | 18.17 | 134.83 | 27.16 | 50.50 | 27.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.37 | 0.17 | 19.37 | 34.17 | 27.45 | 13.00 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.53 | 5.50 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.73 | 12.33 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 27.66 | 14.00 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 27.40 | 11.33 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 27.56 | 16.17 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 27.26 | 8.83 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.43 | 6.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.72 | 10.17 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 1.33 | 19.03 | 0.00 | 19.03 | 197.17 | 27.48 | 84.50 | 27.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.43 | 0.00 | 19.43 | 41.83 | 27.73 | 16.17 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.83 | 0.00 | 18.83 | 0.17 | 20.96 | 0.17 | 22.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.83 | 4.17 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.89 | 6.00 | 27.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.55 | 9.00 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 27.45 | 10.50 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.22 | 7.33 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 27.41 | 12.83 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.22 | 7.50 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.30 | 6.17 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 28.04 | 12.33 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.03 | 10.50 | 28.04 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.83 | 27.59 |
Annual Sum or Average | 0.50 | 18.83 | 0.00 | 18.83 | 193.50 | 27.48 | 88.33 | 27.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 20.96 | 0.17 | 22.24 |
Maximum of Months | 0.50 | 18.83 | 0.00 | 18.83 | 34.33 | 28.04 | 12.83 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 1.00 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.91 | 3.17 | 27.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 27.61 | 10.83 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 57.83 | 27.66 | 17.00 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 27.60 | 12.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 27.60 | 16.33 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.36 | 9.50 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.22 | 7.33 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.93 | 7.00 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.77 | 0.00 | 18.77 | 263.00 | 27.56 | 87.33 | 27.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.77 | 0.00 | 18.77 | 57.83 | 27.93 | 17.00 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 89.83 | 28.07 | 77.50 | 28.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 227.50 | 28.05 | 170.17 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 317.33 | 28.05 | 247.67 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 227.50 | 28.07 | 170.17 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 124.00 | 28.18 | 110.17 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 289.83 | 28.09 | 241.17 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 413.83 | 28.12 | 351.33 | 28.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 289.83 | 28.18 | 241.17 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 87.50 | 28.14 | 75.33 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 159.83 | 28.07 | 134.00 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 247.33 | 28.10 | 209.33 | 28.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 159.83 | 28.14 | 134.00 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 25.38 | 282.67 | 24.97 | 1.00 | 24.98 |
February | 1.50 | 27.63 | 351.00 | 24.69 | 1.50 | 24.71 |
March | 121.67 | 27.95 | 436.67 | 26.01 | 121.67 | 26.36 |
April | 381.00 | 29.36 | 470.33 | 28.94 | 381.00 | 29.07 |
May | 508.00 | 30.04 | 508.00 | 30.04 | 508.00 | 30.04 |
June | 496.00 | 30.44 | 496.00 | 30.44 | 496.00 | 30.44 |
July | 497.00 | 30.87 | 497.00 | 30.87 | 497.00 | 30.87 |
August | 514.00 | 31.17 | 514.00 | 31.17 | 514.00 | 31.17 |
September | 485.00 | 30.88 | 485.00 | 30.88 | 485.00 | 30.88 |
October | 256.83 | 28.89 | 502.00 | 27.49 | 256.83 | 27.84 |
November | 16.67 | 27.66 | 466.50 | 24.80 | 16.67 | 24.90 |
December | 2.00 | 27.79 | 370.33 | 24.85 | 2.00 | 24.86 |
Annual Sum or Average | 3282.00 | 30.26 | 5379.50 | 28.92 | 3280.67 | 29.29 |
Minimum of Months | 1.50 | 25.38 | 282.67 | 24.69 | 1.00 | 24.71 |
Maximum of Months | 514.00 | 31.17 | 514.00 | 31.17 | 514.00 | 31.17 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.83 | 25.16 | 218.17 | 24.79 | 12.83 | 24.84 |
February | 2.83 | 26.34 | 350.67 | 24.44 | 2.83 | 24.45 |
March | 0.50 | 26.60 | 459.50 | 24.33 | 0.50 | 24.33 |
April | 4.67 | 26.67 | 463.00 | 24.45 | 4.67 | 24.47 |
May | 8.33 | 26.68 | 508.00 | 24.48 | 8.33 | 24.52 |
June | 18.50 | 26.60 | 496.00 | 24.50 | 18.50 | 24.58 |
July | 63.33 | 26.60 | 497.00 | 24.80 | 63.33 | 24.98 |
August | 47.17 | 26.64 | 514.00 | 24.64 | 47.17 | 24.80 |
September | 36.83 | 26.63 | 485.00 | 24.66 | 36.83 | 24.79 |
October | 7.33 | 26.79 | 502.00 | 24.49 | 7.33 | 24.52 |
November | 0.00 | 0.00 | 468.33 | 24.44 | 0.00 | 24.44 |
December | 3.33 | 24.00 | 352.17 | 24.54 | 0.00 | 24.54 |
Annual Sum or Average | 212.67 | 26.45 | 5313.83 | 24.54 | 202.33 | 24.62 |
Minimum of Months | 0.00 | 0.00 | 218.17 | 24.33 | 0.00 | 24.33 |
Maximum of Months | 63.33 | 26.79 | 514.00 | 24.80 | 63.33 | 24.98 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 236.33 | 23.30 | 86.00 | 23.49 | 12.50 | 23.43 |
February | 81.50 | 23.71 | 218.17 | 24.14 | 8.67 | 24.19 |
March | 3.83 | 24.66 | 397.67 | 24.26 | 1.83 | 24.27 |
April | 0.00 | 0.00 | 409.67 | 24.20 | 0.00 | 24.20 |
May | 0.00 | 0.00 | 491.17 | 24.15 | 0.00 | 24.15 |
June | 0.00 | 0.00 | 496.00 | 24.16 | 0.00 | 24.16 |
July | 0.00 | 0.00 | 497.00 | 24.17 | 0.00 | 24.17 |
August | 0.00 | 0.00 | 514.00 | 24.18 | 0.00 | 24.18 |
September | 0.33 | 26.12 | 485.00 | 24.24 | 0.33 | 24.24 |
October | 0.00 | 0.00 | 494.17 | 24.30 | 0.00 | 24.30 |
November | 10.83 | 23.69 | 373.67 | 24.29 | 0.00 | 24.29 |
December | 143.50 | 23.54 | 93.33 | 23.87 | 0.00 | 23.87 |
Annual Sum or Average | 476.33 | 23.46 | 4555.83 | 24.15 | 23.33 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 86.00 | 23.49 | 0.00 | 23.43 |
Maximum of Months | 236.33 | 26.12 | 514.00 | 24.30 | 12.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.50 | 22.40 | 36.67 | 22.30 | 21.83 | 22.16 |
February | 205.00 | 23.05 | 141.17 | 23.50 | 8.50 | 23.53 |
March | 31.67 | 23.62 | 365.17 | 24.17 | 3.17 | 24.18 |
April | 0.33 | 26.65 | 425.00 | 24.27 | 0.33 | 24.27 |
May | 4.00 | 26.56 | 503.67 | 24.29 | 4.00 | 24.31 |
June | 2.00 | 26.53 | 496.00 | 24.25 | 2.00 | 24.26 |
July | 0.17 | 26.53 | 497.00 | 24.29 | 0.17 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.24 | 0.00 | 24.24 |
September | 0.00 | 0.00 | 484.67 | 24.29 | 0.00 | 24.29 |
October | 0.00 | 0.00 | 486.83 | 24.29 | 0.00 | 24.29 |
November | 94.00 | 23.20 | 264.33 | 23.92 | 0.00 | 23.92 |
December | 356.83 | 22.71 | 36.83 | 22.80 | 3.50 | 22.79 |
Annual Sum or Average | 1110.50 | 22.75 | 4251.33 | 23.92 | 43.50 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 36.67 | 22.30 | 0.00 | 22.16 |
Maximum of Months | 416.50 | 26.65 | 514.00 | 24.29 | 21.83 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 374.83 | 22.89 | 37.17 | 22.97 | 12.00 | 22.98 |
February | 163.33 | 23.18 | 161.67 | 23.69 | 0.00 | 23.69 |
March | 22.67 | 24.01 | 399.50 | 24.29 | 3.33 | 24.31 |
April | 39.83 | 26.90 | 468.67 | 24.72 | 39.83 | 24.88 |
May | 82.00 | 26.87 | 508.00 | 24.92 | 82.00 | 25.15 |
June | 78.17 | 26.83 | 496.00 | 24.87 | 78.17 | 25.10 |
July | 102.33 | 26.90 | 497.00 | 25.07 | 102.33 | 25.34 |
August | 75.17 | 26.86 | 514.00 | 24.83 | 75.17 | 25.06 |
September | 62.17 | 26.79 | 485.00 | 24.83 | 62.17 | 25.03 |
October | 21.00 | 26.80 | 498.17 | 24.55 | 21.00 | 24.64 |
November | 47.00 | 23.49 | 338.00 | 24.18 | 0.00 | 24.18 |
December | 268.17 | 23.24 | 61.17 | 23.41 | 0.00 | 23.41 |
Annual Sum or Average | 1336.67 | 24.40 | 4464.33 | 24.47 | 476.00 | 24.65 |
Minimum of Months | 21.00 | 22.89 | 37.17 | 22.97 | 0.00 | 22.98 |
Maximum of Months | 374.83 | 26.90 | 514.00 | 25.07 | 102.33 | 25.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.67 | 23.06 | 60.67 | 23.25 | 12.00 | 23.27 |
February | 97.67 | 23.06 | 235.00 | 23.99 | 0.50 | 24.00 |
March | 34.17 | 25.16 | 439.00 | 24.44 | 16.67 | 24.52 |
April | 58.50 | 27.01 | 472.67 | 24.85 | 58.50 | 25.07 |
May | 99.83 | 26.91 | 508.00 | 25.02 | 99.83 | 25.29 |
June | 84.50 | 26.82 | 496.00 | 24.90 | 84.50 | 25.15 |
July | 101.17 | 26.95 | 497.00 | 25.08 | 101.17 | 25.35 |
August | 72.67 | 26.90 | 514.00 | 24.83 | 72.67 | 25.06 |
September | 74.33 | 26.85 | 485.00 | 24.90 | 74.33 | 25.13 |
October | 47.67 | 26.92 | 497.83 | 24.75 | 47.67 | 24.92 |
November | 44.50 | 23.82 | 377.50 | 24.35 | 5.50 | 24.38 |
December | 219.00 | 23.14 | 119.33 | 23.58 | 0.00 | 23.58 |
Annual Sum or Average | 1199.67 | 24.89 | 4702.00 | 24.61 | 573.33 | 24.81 |
Minimum of Months | 34.17 | 23.06 | 60.67 | 23.25 | 0.00 | 23.27 |
Maximum of Months | 265.67 | 27.01 | 514.00 | 25.08 | 101.17 | 25.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 189.50 | 23.07 | 213.00 | 23.71 | 13.33 | 23.71 |
February | 91.33 | 23.66 | 311.67 | 24.31 | 14.83 | 24.41 |
March | 38.17 | 25.97 | 454.00 | 24.55 | 26.50 | 24.68 |
April | 54.67 | 26.97 | 476.00 | 24.82 | 54.67 | 25.02 |
May | 77.17 | 26.90 | 508.00 | 24.90 | 77.17 | 25.14 |
June | 73.67 | 26.82 | 496.00 | 24.84 | 73.67 | 25.07 |
July | 98.00 | 26.88 | 497.00 | 25.05 | 98.00 | 25.31 |
August | 72.50 | 26.88 | 514.00 | 24.83 | 72.50 | 25.05 |
September | 72.33 | 26.84 | 485.00 | 24.89 | 72.33 | 25.12 |
October | 60.50 | 27.02 | 502.00 | 24.91 | 60.50 | 25.12 |
November | 58.17 | 26.25 | 436.83 | 24.80 | 44.83 | 24.98 |
December | 110.83 | 23.67 | 286.33 | 24.31 | 14.33 | 24.40 |
Annual Sum or Average | 996.83 | 25.44 | 5179.83 | 24.71 | 622.67 | 24.90 |
Minimum of Months | 38.17 | 23.07 | 213.00 | 23.71 | 13.33 | 23.71 |
Maximum of Months | 189.50 | 27.02 | 514.00 | 25.05 | 98.00 | 25.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.67 | 23.39 | 185.17 | 23.93 | 12.00 | 23.94 |
February | 35.50 | 24.94 | 347.33 | 24.58 | 14.67 | 24.67 |
March | 40.17 | 26.97 | 500.17 | 24.73 | 40.17 | 24.88 |
April | 96.83 | 26.96 | 485.00 | 25.05 | 96.83 | 25.32 |
May | 102.00 | 26.96 | 508.00 | 25.03 | 102.00 | 25.31 |
June | 97.17 | 26.84 | 496.00 | 24.97 | 97.17 | 25.23 |
July | 119.17 | 26.97 | 497.00 | 25.17 | 119.17 | 25.46 |
August | 98.00 | 26.96 | 514.00 | 24.97 | 98.00 | 25.25 |
September | 86.83 | 26.82 | 485.00 | 24.95 | 86.83 | 25.19 |
October | 80.67 | 26.94 | 502.00 | 24.99 | 80.67 | 25.23 |
November | 36.83 | 26.98 | 470.50 | 24.82 | 36.83 | 24.96 |
December | 24.17 | 25.75 | 370.00 | 24.74 | 14.67 | 24.82 |
Annual Sum or Average | 969.00 | 26.27 | 5360.17 | 24.88 | 799.00 | 25.10 |
Minimum of Months | 24.17 | 23.39 | 185.17 | 23.93 | 12.00 | 23.94 |
Maximum of Months | 151.67 | 26.98 | 514.00 | 25.17 | 119.17 | 25.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.67 | 21.77 | 39.67 | 21.64 | 39.67 | 21.53 |
February | 324.50 | 22.56 | 57.33 | 22.79 | 1.00 | 22.78 |
March | 93.67 | 23.29 | 304.00 | 24.00 | 0.00 | 24.00 |
April | 13.83 | 26.61 | 437.83 | 24.53 | 12.50 | 24.60 |
May | 43.17 | 26.90 | 508.00 | 24.72 | 43.17 | 24.88 |
June | 54.33 | 26.63 | 496.00 | 24.69 | 54.33 | 24.87 |
July | 70.67 | 26.75 | 497.00 | 24.88 | 70.67 | 25.09 |
August | 33.00 | 26.80 | 514.00 | 24.60 | 33.00 | 24.73 |
September | 49.00 | 26.46 | 485.00 | 24.66 | 49.00 | 24.81 |
October | 16.50 | 24.16 | 469.67 | 24.35 | 4.17 | 24.37 |
November | 197.00 | 22.95 | 152.67 | 23.45 | 0.00 | 23.45 |
December | 478.33 | 22.16 | 20.33 | 22.08 | 20.33 | 22.01 |
Annual Sum or Average | 1866.67 | 22.93 | 3981.50 | 23.91 | 327.83 | 24.00 |
Minimum of Months | 13.83 | 21.77 | 20.33 | 21.64 | 0.00 | 21.53 |
Maximum of Months | 492.67 | 26.90 | 514.00 | 24.88 | 70.67 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 372.67 | 22.37 | 18.67 | 22.31 | 14.00 | 22.23 |
February | 160.33 | 22.75 | 129.00 | 23.50 | 0.00 | 23.50 |
March | 49.00 | 24.44 | 331.33 | 24.49 | 16.00 | 24.59 |
April | 48.17 | 27.00 | 390.33 | 24.96 | 48.00 | 25.16 |
May | 67.67 | 27.03 | 430.00 | 25.03 | 67.67 | 25.27 |
June | 66.17 | 26.81 | 418.00 | 24.92 | 66.17 | 25.15 |
July | 82.67 | 26.86 | 422.00 | 25.11 | 82.67 | 25.35 |
August | 42.17 | 26.89 | 433.00 | 24.79 | 42.17 | 24.96 |
September | 58.50 | 26.64 | 410.00 | 24.88 | 58.50 | 25.08 |
October | 48.00 | 26.67 | 411.83 | 24.85 | 44.83 | 25.03 |
November | 88.50 | 23.20 | 257.00 | 24.14 | 1.33 | 24.15 |
December | 313.83 | 22.61 | 7.50 | 22.62 | 3.00 | 22.60 |
Annual Sum or Average | 1397.67 | 23.92 | 3658.67 | 24.41 | 444.33 | 24.59 |
Minimum of Months | 42.17 | 22.37 | 7.50 | 22.31 | 0.00 | 22.23 |
Maximum of Months | 372.67 | 27.03 | 433.00 | 25.11 | 82.67 | 25.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 234.00 | 22.58 | 174.00 | 23.30 | 5.00 | 23.29 |
February | 126.67 | 23.22 | 266.83 | 24.10 | 15.50 | 24.21 |
March | 55.17 | 24.94 | 421.17 | 24.50 | 24.00 | 24.62 |
April | 34.00 | 26.99 | 460.83 | 24.72 | 34.00 | 24.87 |
May | 44.50 | 26.94 | 508.00 | 24.74 | 44.50 | 24.90 |
June | 53.17 | 26.63 | 496.00 | 24.69 | 53.17 | 24.86 |
July | 69.00 | 26.77 | 497.00 | 24.88 | 69.00 | 25.08 |
August | 35.33 | 26.86 | 514.00 | 24.63 | 35.33 | 24.77 |
September | 60.00 | 26.65 | 485.00 | 24.78 | 60.00 | 24.97 |
October | 55.50 | 27.10 | 499.33 | 24.90 | 55.50 | 25.10 |
November | 77.67 | 25.39 | 410.67 | 24.73 | 43.67 | 24.92 |
December | 168.00 | 23.04 | 225.83 | 23.93 | 10.83 | 24.01 |
Annual Sum or Average | 1013.00 | 24.55 | 4958.67 | 24.54 | 450.50 | 24.70 |
Minimum of Months | 34.00 | 22.58 | 174.00 | 23.30 | 5.00 | 23.29 |
Maximum of Months | 234.00 | 27.10 | 514.00 | 24.90 | 69.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 394.17 | 22.30 | 38.50 | 22.36 | 11.00 | 22.31 |
February | 189.17 | 22.78 | 165.33 | 23.53 | 2.67 | 23.56 |
March | 47.17 | 24.57 | 398.83 | 24.43 | 15.17 | 24.51 |
April | 53.17 | 26.99 | 477.33 | 24.84 | 53.17 | 25.04 |
May | 87.50 | 26.95 | 508.00 | 24.96 | 87.50 | 25.22 |
June | 85.17 | 26.84 | 496.00 | 24.89 | 85.17 | 25.14 |
July | 98.00 | 26.88 | 497.00 | 25.04 | 98.00 | 25.30 |
August | 64.67 | 26.90 | 514.00 | 24.79 | 64.67 | 25.00 |
September | 70.50 | 26.75 | 485.00 | 24.85 | 70.50 | 25.07 |
October | 31.83 | 26.99 | 492.67 | 24.69 | 31.83 | 24.82 |
November | 87.67 | 23.54 | 313.67 | 24.19 | 8.83 | 24.25 |
December | 339.83 | 22.67 | 69.17 | 22.90 | 3.33 | 22.88 |
Annual Sum or Average | 1548.83 | 24.03 | 4455.50 | 24.40 | 531.83 | 24.59 |
Minimum of Months | 31.83 | 22.30 | 38.50 | 22.36 | 2.67 | 22.31 |
Maximum of Months | 394.17 | 26.99 | 514.00 | 25.04 | 98.00 | 25.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 21.21 | 118.17 | 20.94 | 118.17 | 20.76 |
February | 352.67 | 22.17 | 70.50 | 22.28 | 23.17 | 22.18 |
March | 130.00 | 23.04 | 293.00 | 23.86 | 2.17 | 23.88 |
April | 29.67 | 26.02 | 435.50 | 24.58 | 21.83 | 24.69 |
May | 52.50 | 26.93 | 508.00 | 24.78 | 52.50 | 24.96 |
June | 62.50 | 26.66 | 496.00 | 24.73 | 62.50 | 24.93 |
July | 81.67 | 26.76 | 497.00 | 24.93 | 81.67 | 25.16 |
August | 38.67 | 26.82 | 514.00 | 24.63 | 38.67 | 24.78 |
September | 52.50 | 26.49 | 485.00 | 24.68 | 52.50 | 24.85 |
October | 42.33 | 24.11 | 438.50 | 24.34 | 12.50 | 24.40 |
November | 262.00 | 22.57 | 126.83 | 23.03 | 3.33 | 23.01 |
December | 486.67 | 21.57 | 71.83 | 21.34 | 71.83 | 21.16 |
Annual Sum or Average | 2086.00 | 22.63 | 4054.33 | 23.68 | 540.83 | 23.70 |
Minimum of Months | 29.67 | 21.21 | 70.50 | 20.94 | 2.17 | 20.76 |
Maximum of Months | 494.83 | 26.93 | 514.00 | 24.93 | 118.17 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 460.67 | 21.86 | 65.00 | 21.62 | 61.67 | 21.42 |
February | 224.00 | 22.49 | 147.00 | 23.10 | 7.33 | 23.05 |
March | 67.50 | 23.83 | 392.67 | 24.30 | 14.50 | 24.39 |
April | 55.33 | 26.88 | 463.83 | 24.84 | 53.17 | 25.04 |
May | 71.83 | 27.06 | 508.00 | 24.91 | 71.83 | 25.15 |
June | 72.17 | 26.81 | 496.00 | 24.82 | 72.17 | 25.04 |
July | 88.33 | 26.87 | 497.00 | 24.99 | 88.33 | 25.24 |
August | 47.17 | 26.90 | 514.00 | 24.70 | 47.17 | 24.87 |
September | 62.67 | 26.63 | 485.00 | 24.78 | 62.67 | 24.97 |
October | 61.00 | 25.86 | 474.17 | 24.68 | 44.33 | 24.84 |
November | 131.17 | 22.75 | 266.17 | 23.79 | 1.33 | 23.78 |
December | 412.50 | 22.19 | 30.50 | 22.05 | 30.50 | 21.92 |
Annual Sum or Average | 1754.33 | 23.44 | 4339.33 | 24.13 | 555.00 | 24.25 |
Minimum of Months | 47.17 | 21.86 | 30.50 | 21.62 | 1.33 | 21.42 |
Maximum of Months | 460.67 | 27.06 | 514.00 | 24.99 | 88.33 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 289.00 | 21.99 | 172.00 | 22.46 | 42.17 | 22.25 |
February | 160.17 | 22.61 | 233.00 | 23.69 | 14.50 | 23.76 |
March | 81.00 | 24.23 | 399.17 | 24.40 | 24.00 | 24.52 |
April | 43.50 | 26.68 | 455.67 | 24.75 | 39.50 | 24.91 |
May | 54.00 | 26.96 | 508.00 | 24.79 | 54.00 | 24.98 |
June | 62.00 | 26.65 | 496.00 | 24.73 | 62.00 | 24.92 |
July | 80.67 | 26.77 | 497.00 | 24.93 | 80.67 | 25.15 |
August | 41.17 | 26.87 | 514.00 | 24.66 | 41.17 | 24.81 |
September | 62.67 | 26.66 | 485.00 | 24.80 | 62.67 | 24.99 |
October | 60.33 | 26.75 | 484.83 | 24.86 | 54.33 | 25.07 |
November | 108.67 | 24.32 | 369.83 | 24.50 | 38.67 | 24.69 |
December | 230.33 | 22.40 | 194.83 | 23.23 | 19.50 | 23.15 |
Annual Sum or Average | 1273.50 | 24.00 | 4809.33 | 24.38 | 533.17 | 24.52 |
Minimum of Months | 41.17 | 21.99 | 172.00 | 22.46 | 14.50 | 22.25 |
Maximum of Months | 289.00 | 26.96 | 514.00 | 24.93 | 80.67 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 419.00 | 21.78 | 86.83 | 21.62 | 66.67 | 21.42 |
February | 235.00 | 22.41 | 145.33 | 23.11 | 5.83 | 23.10 |
March | 81.67 | 23.92 | 378.33 | 24.32 | 15.67 | 24.40 |
April | 57.33 | 26.92 | 467.83 | 24.86 | 56.33 | 25.07 |
May | 90.50 | 26.98 | 508.00 | 24.98 | 90.50 | 25.24 |
June | 88.83 | 26.79 | 496.00 | 24.89 | 88.83 | 25.15 |
July | 102.83 | 26.89 | 497.00 | 25.06 | 102.83 | 25.33 |
August | 68.00 | 26.90 | 514.00 | 24.81 | 68.00 | 25.03 |
September | 73.50 | 26.75 | 485.00 | 24.87 | 73.50 | 25.09 |
October | 45.17 | 26.10 | 476.33 | 24.66 | 34.33 | 24.81 |
November | 151.17 | 23.08 | 270.50 | 23.90 | 8.50 | 23.96 |
December | 379.00 | 22.14 | 79.33 | 22.21 | 31.00 | 22.08 |
Annual Sum or Average | 1792.00 | 23.62 | 4404.50 | 24.20 | 642.00 | 24.35 |
Minimum of Months | 45.17 | 21.78 | 79.33 | 21.62 | 5.83 | 21.42 |
Maximum of Months | 419.00 | 26.98 | 514.00 | 25.06 | 102.83 | 25.33 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 49.50 | 27.00 | 514.00 | 27.00 | 49.50 | 27.00 |
April | 354.50 | 27.28 | 485.00 | 27.23 | 354.50 | 27.25 |
May | 127.00 | 27.00 | 508.00 | 27.00 | 127.00 | 27.00 |
June | 293.00 | 27.00 | 496.00 | 27.00 | 293.00 | 27.00 |
July | 394.50 | 27.00 | 497.00 | 27.00 | 394.50 | 27.00 |
August | 490.83 | 27.46 | 514.00 | 27.45 | 490.83 | 27.45 |
September | 126.17 | 27.00 | 485.00 | 27.00 | 126.17 | 27.00 |
October | 52.00 | 27.00 | 502.00 | 27.00 | 52.00 | 27.00 |
November | 27.83 | 27.00 | 489.00 | 27.00 | 27.83 | 27.00 |
December | 8.50 | 27.00 | 497.00 | 27.00 | 8.50 | 27.00 |
Annual Sum or Average | 1923.83 | 27.17 | 5943.00 | 27.08 | 1923.83 | 27.10 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 490.83 | 27.46 | 514.00 | 27.45 | 490.83 | 27.45 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 494.83 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.17 | 27.00 | 514.00 | 27.00 | 0.17 | 27.00 |
April | 142.33 | 27.98 | 485.00 | 27.46 | 142.33 | 27.56 |
May | 7.50 | 27.00 | 508.00 | 27.00 | 7.50 | 27.00 |
June | 21.67 | 27.00 | 496.00 | 27.00 | 21.67 | 27.00 |
July | 24.33 | 27.00 | 497.00 | 27.00 | 24.33 | 27.00 |
August | 268.83 | 28.04 | 514.00 | 27.75 | 268.83 | 27.82 |
September | 3.50 | 27.00 | 485.00 | 27.00 | 3.50 | 27.00 |
October | 2.83 | 27.00 | 502.00 | 27.00 | 2.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 471.17 | 27.89 | 5935.83 | 27.14 | 471.17 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 268.83 | 28.04 | 514.00 | 27.75 | 268.83 | 27.82 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.50 | 24.65 | 450.83 | 26.81 | 3.50 | 26.78 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 5.50 | 27.00 | 514.00 | 27.00 | 5.50 | 27.00 |
April | 133.00 | 27.71 | 485.00 | 27.31 | 133.00 | 27.38 |
May | 79.50 | 27.00 | 508.00 | 27.00 | 79.50 | 27.00 |
June | 104.17 | 27.00 | 496.00 | 27.00 | 104.17 | 27.00 |
July | 88.83 | 27.00 | 497.00 | 27.00 | 88.83 | 27.00 |
August | 193.67 | 27.84 | 514.00 | 27.47 | 193.67 | 27.55 |
September | 17.33 | 27.00 | 485.00 | 27.00 | 17.33 | 27.00 |
October | 15.33 | 27.00 | 502.00 | 27.00 | 15.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 490.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 667.83 | 27.28 | 5885.00 | 27.07 | 640.83 | 27.09 |
Minimum of Months | 0.00 | 0.00 | 450.83 | 26.81 | 0.00 | 26.78 |
Maximum of Months | 193.67 | 27.84 | 514.00 | 27.47 | 193.67 | 27.55 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00073 | 28.66205 | 0.83770 | 19.84184 |
February | 454.00000 | 27.00098 | 28.82872 | 0.89631 | 21.99716 |
March | 514.00000 | 27.00065 | 30.17671 | 0.97023 | 24.91481 |
April | 485.00000 | 27.20347 | 31.66295 | 1.08525 | 30.00574 |
May | 508.00000 | 27.00072 | 36.51317 | 0.37098 | 7.91991 |
June | 496.00000 | 27.00244 | 36.15401 | 0.41491 | 8.63604 |
July | 497.00000 | 27.00160 | 35.22764 | 0.44904 | 9.27211 |
August | 514.00000 | 27.43760 | 33.78519 | 0.57545 | 12.49959 |
September | 485.00000 | 27.00011 | 39.17709 | 0.37535 | 7.98215 |
October | 502.00000 | 27.00174 | 32.24718 | 0.97885 | 25.27135 |
November | 489.00000 | 27.00071 | 29.46504 | 0.95945 | 24.47661 |
December | 497.00000 | 27.00024 | 27.38302 | 0.94317 | 23.82195 |
Annual Sum or Average | 5943.00000 | 27.05528 | 32.45928 | 0.73651 | 18.00644 |
Minimum of Months | 454.00000 | 27.00011 | 27.38302 | 0.37098 | 7.91991 |
Maximum of Months | 514.00000 | 27.43760 | 39.17709 | 1.08525 | 30.00574 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99230 | 29.69922 | 0.75355 | 17.06630 |
February | 454.00000 | 27.00085 | 29.55377 | 0.81947 | 19.22812 |
March | 514.00000 | 27.00056 | 30.85516 | 0.89890 | 22.10453 |
April | 485.00000 | 27.31284 | 32.16790 | 1.01749 | 27.11150 |
May | 508.00000 | 27.00052 | 37.41144 | 0.29935 | 6.91112 |
June | 496.00000 | 27.00239 | 37.00856 | 0.31875 | 7.15817 |
July | 497.00000 | 27.00166 | 36.08937 | 0.32159 | 7.19615 |
August | 514.00000 | 27.59403 | 34.49954 | 0.46758 | 10.20029 |
September | 485.00000 | 27.00003 | 40.58273 | 0.29516 | 6.84513 |
October | 502.00000 | 27.00155 | 33.02235 | 0.91749 | 22.81016 |
November | 489.00000 | 27.00060 | 30.15525 | 0.87329 | 21.14612 |
December | 497.00000 | 27.00020 | 27.96998 | 0.80989 | 18.90639 |
Annual Sum or Average | 5943.00000 | 27.07695 | 33.27018 | 0.64773 | 15.51336 |
Minimum of Months | 454.00000 | 26.99230 | 27.96998 | 0.29516 | 6.84513 |
Maximum of Months | 514.00000 | 27.59403 | 40.58273 | 1.01749 | 27.11150 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.82507 | 30.35756 | 0.66796 | 15.22082 |
February | 454.00000 | 27.00093 | 29.05215 | 0.78277 | 18.06626 |
March | 514.00000 | 27.00064 | 30.21888 | 0.88890 | 21.77808 |
April | 485.00000 | 27.20044 | 31.67949 | 1.00736 | 26.68837 |
May | 508.00000 | 27.00057 | 36.76437 | 0.32567 | 7.32149 |
June | 496.00000 | 27.00255 | 36.33991 | 0.34447 | 7.57606 |
July | 497.00000 | 27.00188 | 35.41154 | 0.34366 | 7.55979 |
August | 514.00000 | 27.33538 | 33.95893 | 0.42009 | 9.29155 |
September | 485.00000 | 27.00003 | 39.90875 | 0.30438 | 7.00104 |
October | 502.00000 | 27.00167 | 32.40956 | 0.91234 | 22.65122 |
November | 489.00000 | 27.00069 | 29.53770 | 0.84404 | 20.15349 |
December | 497.00000 | 27.00027 | 27.41735 | 0.74932 | 17.00591 |
Annual Sum or Average | 5943.00000 | 27.03136 | 32.77423 | 0.63099 | 14.98641 |
Minimum of Months | 454.00000 | 26.82507 | 27.41735 | 0.30438 | 7.00104 |
Maximum of Months | 514.00000 | 27.33538 | 39.90875 | 1.00736 | 26.68837 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00486 | 30.02342 | 1.07455 | 29.36628 |
February | 454.00000 | 27.00611 | 30.12472 | 1.22544 | 36.50502 |
March | 514.00000 | 27.00392 | 30.78238 | 1.37431 | 44.15170 |
April | 485.00000 | 27.00359 | 32.23904 | 1.53802 | 52.96947 |
May | 508.00000 | 27.00346 | 34.69866 | 0.60042 | 12.59792 |
June | 496.00000 | 27.00361 | 34.76694 | 0.82936 | 19.52742 |
July | 497.00000 | 27.00279 | 34.13220 | 1.04471 | 28.05250 |
August | 514.00000 | 27.00205 | 33.40867 | 1.23768 | 37.11594 |
September | 485.00000 | 27.00350 | 35.23754 | 0.67497 | 14.60652 |
October | 502.00000 | 27.00316 | 31.73126 | 1.30535 | 40.55008 |
November | 489.00000 | 27.00486 | 30.46861 | 1.41032 | 46.06421 |
December | 497.00000 | 27.00521 | 30.01344 | 1.51988 | 51.98175 |
Annual Sum or Average | 5943.00000 | 27.00391 | 32.31511 | 1.15220 | 34.42790 |
Minimum of Months | 454.00000 | 27.00205 | 30.01344 | 0.60042 | 12.59792 |
Maximum of Months | 514.00000 | 27.00611 | 35.23754 | 1.53802 | 52.96947 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54822 | 39.80389 | 0.50007 | 10.83782 |
February | 454.00000 | 24.52953 | 43.82134 | 0.52520 | 11.29792 |
March | 514.00000 | 25.25102 | 54.90787 | 0.78175 | 22.04410 |
April | 485.00000 | 28.45735 | 79.58099 | 1.74608 | 63.41320 |
May | 508.00000 | 30.04156 | 99.99826 | 1.93619 | 73.63540 |
June | 496.00000 | 30.44336 | 99.99925 | 2.09262 | 80.55089 |
July | 497.00000 | 30.87254 | 99.99792 | 2.26257 | 86.78638 |
August | 514.00000 | 31.17138 | 99.99788 | 2.38029 | 90.38561 |
September | 485.00000 | 30.87732 | 99.99928 | 2.26512 | 86.93427 |
October | 502.00000 | 26.77080 | 62.78227 | 1.23121 | 40.12181 |
November | 489.00000 | 24.66680 | 46.90042 | 0.60135 | 13.40000 |
December | 497.00000 | 24.62142 | 39.91405 | 0.53084 | 11.56810 |
Annual Sum or Average | 5943.00000 | 27.71001 | 72.51900 | 1.41043 | 49.50584 |
Minimum of Months | 454.00000 | 24.52953 | 39.80389 | 0.50007 | 10.83782 |
Maximum of Months | 514.00000 | 31.17138 | 99.99928 | 2.38029 | 90.38561 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33838 | 42.56680 | 0.46065 | 10.02398 |
February | 454.00000 | 24.33421 | 45.22205 | 0.49995 | 10.51374 |
March | 514.00000 | 24.29325 | 48.59044 | 0.54677 | 11.52758 |
April | 485.00000 | 24.40763 | 47.15008 | 0.61249 | 13.33365 |
May | 508.00000 | 24.44618 | 51.44411 | -0.1508 | 6.32492 |
June | 496.00000 | 24.42653 | 52.68048 | -0.1319 | 6.23836 |
July | 497.00000 | 24.57058 | 52.41034 | -0.0780 | 6.45041 |
August | 514.00000 | 24.45977 | 52.31174 | -0.0999 | 6.30309 |
September | 485.00000 | 24.50526 | 53.37286 | -0.1129 | 6.40468 |
October | 502.00000 | 24.45523 | 52.83388 | 0.63808 | 14.02209 |
November | 489.00000 | 24.42184 | 47.85513 | 0.56350 | 12.01476 |
December | 497.00000 | 24.39762 | 40.64266 | 0.49016 | 10.36091 |
Annual Sum or Average | 5943.00000 | 24.42161 | 48.95691 | 0.26735 | 9.44307 |
Minimum of Months | 454.00000 | 24.29325 | 40.64266 | -0.1508 | 6.23836 |
Maximum of Months | 514.00000 | 24.57058 | 53.37286 | 0.63808 | 14.02209 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73538 | 44.12447 | 0.28341 | 7.10638 |
February | 454.00000 | 24.07148 | 45.86743 | 0.40577 | 8.77034 |
March | 514.00000 | 24.20289 | 49.00207 | 0.48952 | 10.20225 |
April | 485.00000 | 24.17354 | 49.01787 | 0.49779 | 10.30830 |
May | 508.00000 | 24.15006 | 54.66042 | -0.3365 | 7.48026 |
June | 496.00000 | 24.16180 | 56.63497 | -0.3183 | 7.27649 |
July | 497.00000 | 24.16746 | 57.49358 | -0.3175 | 7.23984 |
August | 514.00000 | 24.18330 | 57.67473 | -0.3108 | 7.20027 |
September | 485.00000 | 24.23579 | 57.34317 | -0.3052 | 7.22525 |
October | 502.00000 | 24.29226 | 54.45792 | 0.55840 | 11.73652 |
November | 489.00000 | 24.22138 | 48.32751 | 0.48044 | 10.03826 |
December | 497.00000 | 23.94339 | 42.02932 | 0.33872 | 7.66387 |
Annual Sum or Average | 5943.00000 | 24.12842 | 51.43574 | 0.11927 | 8.51666 |
Minimum of Months | 454.00000 | 23.73538 | 42.02932 | -0.3365 | 7.10638 |
Maximum of Months | 514.00000 | 24.29226 | 57.67473 | 0.55840 | 11.73652 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.66828 | 45.80641 | 0.00525 | 7.31187 |
February | 454.00000 | 23.59031 | 47.60554 | 0.28010 | 7.58901 |
March | 514.00000 | 24.12920 | 49.58538 | 0.47257 | 9.92258 |
April | 485.00000 | 24.23576 | 49.15659 | 0.52927 | 11.07990 |
May | 508.00000 | 24.26833 | 54.28105 | -0.2649 | 6.90293 |
June | 496.00000 | 24.24444 | 56.23247 | -0.2563 | 6.75468 |
July | 497.00000 | 24.28709 | 57.04683 | -0.2507 | 6.71259 |
August | 514.00000 | 24.24174 | 57.53339 | -0.2681 | 6.82412 |
September | 485.00000 | 24.28815 | 57.41508 | -0.2713 | 6.95785 |
October | 502.00000 | 24.27582 | 55.10196 | 0.55870 | 11.73543 |
November | 489.00000 | 23.92383 | 49.77466 | 0.40010 | 8.76256 |
December | 497.00000 | 23.06832 | 44.84819 | 0.11339 | 6.60241 |
Annual Sum or Average | 5943.00000 | 23.93751 | 52.07184 | 0.08519 | 8.09738 |
Minimum of Months | 454.00000 | 22.66828 | 44.84819 | -0.2713 | 6.60241 |
Maximum of Months | 514.00000 | 24.28815 | 57.53339 | 0.55870 | 11.73543 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17211 | 44.31396 | 0.13761 | 6.27043 |
February | 454.00000 | 23.78187 | 46.20173 | 0.32914 | 7.91755 |
March | 514.00000 | 24.22357 | 48.04519 | 0.51334 | 10.88228 |
April | 485.00000 | 24.52070 | 46.06019 | 0.66787 | 15.12844 |
May | 508.00000 | 24.60097 | 50.24513 | -0.0090 | 6.64319 |
June | 496.00000 | 24.55521 | 51.62096 | 0.01009 | 6.49345 |
July | 497.00000 | 24.69255 | 51.58962 | 0.04749 | 7.20387 |
August | 514.00000 | 24.53815 | 51.59838 | -0.0115 | 6.60968 |
September | 485.00000 | 24.57725 | 52.65692 | -0.0552 | 6.62359 |
October | 502.00000 | 24.44953 | 52.15800 | 0.63213 | 13.93250 |
November | 489.00000 | 24.13947 | 48.17584 | 0.45717 | 9.66211 |
December | 497.00000 | 23.61514 | 42.45289 | 0.25100 | 6.90316 |
Annual Sum or Average | 5943.00000 | 24.24177 | 48.78424 | 0.24623 | 8.68391 |
Minimum of Months | 454.00000 | 23.17211 | 42.45289 | -0.0552 | 6.27043 |
Maximum of Months | 514.00000 | 24.69255 | 52.65692 | 0.66787 | 15.12844 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52249 | 42.99953 | 0.23435 | 6.92214 |
February | 454.00000 | 23.99214 | 45.33811 | 0.40596 | 9.24233 |
March | 514.00000 | 24.30955 | 47.51807 | 0.57523 | 12.60743 |
April | 485.00000 | 24.57108 | 45.68952 | 0.73894 | 17.46108 |
May | 508.00000 | 24.64952 | 49.95759 | 0.09654 | 7.26803 |
June | 496.00000 | 24.57942 | 51.45126 | 0.06983 | 6.76938 |
July | 497.00000 | 24.70286 | 51.51360 | 0.07858 | 7.52621 |
August | 514.00000 | 24.53960 | 51.54357 | 0.00777 | 6.70988 |
September | 485.00000 | 24.60297 | 52.44990 | 0.00211 | 6.70223 |
October | 502.00000 | 24.53504 | 51.61244 | 0.69176 | 15.89249 |
November | 489.00000 | 24.26697 | 47.51166 | 0.51459 | 11.15952 |
December | 497.00000 | 23.72163 | 41.96139 | 0.29057 | 7.52063 |
Annual Sum or Average | 5943.00000 | 24.33486 | 48.32283 | 0.30743 | 9.63862 |
Minimum of Months | 454.00000 | 23.52249 | 41.96139 | 0.00211 | 6.70223 |
Maximum of Months | 514.00000 | 24.70286 | 52.44990 | 0.73894 | 17.46108 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78693 | 41.72711 | 0.34167 | 8.78387 |
February | 454.00000 | 24.18027 | 44.51784 | 0.49489 | 11.38388 |
March | 514.00000 | 24.37724 | 47.20816 | 0.62051 | 13.84190 |
April | 485.00000 | 24.56571 | 45.80798 | 0.71825 | 16.72821 |
May | 508.00000 | 24.60023 | 50.24054 | -0.0036 | 6.66011 |
June | 496.00000 | 24.54405 | 51.67114 | -0.0044 | 6.44177 |
July | 497.00000 | 24.68318 | 51.63537 | 0.03536 | 7.11307 |
August | 514.00000 | 24.53715 | 51.60252 | -0.0081 | 6.62467 |
September | 485.00000 | 24.60387 | 52.50307 | -0.0016 | 6.70892 |
October | 502.00000 | 24.65790 | 51.11034 | 0.77136 | 18.60313 |
November | 489.00000 | 24.52527 | 46.25399 | 0.66253 | 15.31246 |
December | 497.00000 | 24.17950 | 40.23454 | 0.46044 | 10.70116 |
Annual Sum or Average | 5943.00000 | 24.43796 | 47.90740 | 0.33858 | 10.72241 |
Minimum of Months | 454.00000 | 23.78693 | 40.23454 | -0.0081 | 6.44177 |
Maximum of Months | 514.00000 | 24.68318 | 52.50307 | 0.77136 | 18.60313 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96486 | 41.51875 | 0.35832 | 8.35600 |
February | 454.00000 | 24.40479 | 43.85199 | 0.54414 | 11.95189 |
March | 514.00000 | 24.53149 | 46.73333 | 0.69835 | 16.08698 |
April | 485.00000 | 24.66947 | 45.40779 | 0.83107 | 20.62797 |
May | 508.00000 | 24.64504 | 50.04625 | 0.08847 | 7.41042 |
June | 496.00000 | 24.60296 | 51.40407 | 0.11840 | 7.32047 |
July | 497.00000 | 24.73993 | 51.36337 | 0.14022 | 8.07858 |
August | 514.00000 | 24.59054 | 51.33115 | 0.10190 | 7.27859 |
September | 485.00000 | 24.61003 | 52.51440 | 0.00372 | 6.81995 |
October | 502.00000 | 24.67276 | 51.15592 | 0.76595 | 18.34320 |
November | 489.00000 | 24.62344 | 46.06471 | 0.67226 | 15.36546 |
December | 497.00000 | 24.50888 | 39.23196 | 0.54633 | 11.95951 |
Annual Sum or Average | 5943.00000 | 24.54743 | 47.58545 | 0.40405 | 11.61356 |
Minimum of Months | 454.00000 | 23.96486 | 39.23196 | 0.00372 | 6.81995 |
Maximum of Months | 514.00000 | 24.73993 | 52.51440 | 0.83107 | 20.62797 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.81535 | 47.08585 | -0.2052 | 7.30089 |
February | 454.00000 | 22.97656 | 48.15088 | 0.11751 | 6.73548 |
March | 514.00000 | 24.00808 | 48.65943 | 0.43007 | 9.38714 |
April | 485.00000 | 24.42032 | 47.10734 | 0.59506 | 12.97983 |
May | 508.00000 | 24.53463 | 52.38960 | -0.0899 | 6.50489 |
June | 496.00000 | 24.48125 | 54.71328 | -0.0776 | 6.30477 |
July | 497.00000 | 24.61234 | 55.59328 | -0.0546 | 6.77457 |
August | 514.00000 | 24.45927 | 56.11490 | -0.1229 | 6.48666 |
September | 485.00000 | 24.47620 | 56.18767 | -0.1620 | 6.68303 |
October | 502.00000 | 24.30601 | 53.54941 | 0.56255 | 12.01836 |
November | 489.00000 | 23.58282 | 49.69790 | 0.29884 | 7.57331 |
December | 497.00000 | 22.22321 | 45.68333 | -0.0983 | 6.54317 |
Annual Sum or Average | 5943.00000 | 23.83087 | 51.27376 | 0.09871 | 7.94308 |
Minimum of Months | 454.00000 | 21.81535 | 45.68333 | -0.2052 | 6.30477 |
Maximum of Months | 514.00000 | 24.61234 | 56.18767 | 0.59506 | 12.97983 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.56885 | 44.74774 | -0.0185 | 6.55565 |
February | 385.00000 | 23.62673 | 45.44316 | 0.28964 | 8.13826 |
March | 433.00000 | 24.33267 | 46.73294 | 0.54722 | 12.18331 |
April | 410.00000 | 24.66809 | 45.60524 | 0.71343 | 16.79631 |
May | 430.00000 | 24.70934 | 51.56557 | 0.04656 | 7.28685 |
June | 418.00000 | 24.62036 | 54.10707 | 0.01264 | 6.73030 |
July | 422.00000 | 24.76602 | 55.05267 | 0.02241 | 7.43476 |
August | 433.00000 | 24.58612 | 55.60176 | -0.0598 | 6.74693 |
September | 410.00000 | 24.63266 | 55.65385 | -0.0740 | 6.77038 |
October | 427.00000 | 24.60158 | 52.22160 | 0.66950 | 15.37105 |
November | 417.00000 | 24.10165 | 47.36645 | 0.44557 | 10.07667 |
December | 422.00000 | 22.97964 | 43.25712 | 0.08861 | 6.51972 |
Annual Sum or Average | 5034.00000 | 24.18526 | 49.81271 | 0.22262 | 9.21582 |
Minimum of Months | 385.00000 | 22.56885 | 43.25712 | -0.0740 | 6.51972 |
Maximum of Months | 433.00000 | 24.76602 | 55.65385 | 0.71343 | 16.79631 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45550 | 41.92220 | 0.24912 | 8.43181 |
February | 454.00000 | 23.98839 | 44.49321 | 0.43329 | 10.73728 |
March | 514.00000 | 24.32338 | 47.11926 | 0.58641 | 13.11566 |
April | 485.00000 | 24.52554 | 46.61565 | 0.66992 | 15.23908 |
May | 508.00000 | 24.54559 | 52.31698 | -0.0719 | 6.52958 |
June | 496.00000 | 24.47840 | 54.72422 | -0.0812 | 6.31988 |
July | 497.00000 | 24.61317 | 55.58203 | -0.0520 | 6.79489 |
August | 514.00000 | 24.47759 | 55.98896 | -0.0999 | 6.52387 |
September | 485.00000 | 24.55032 | 55.73247 | -0.0763 | 6.68099 |
October | 502.00000 | 24.65477 | 51.82803 | 0.75173 | 18.02908 |
November | 489.00000 | 24.44714 | 45.88993 | 0.62985 | 14.67162 |
December | 497.00000 | 23.89338 | 40.44106 | 0.37111 | 9.83807 |
Annual Sum or Average | 5943.00000 | 24.33122 | 49.43343 | 0.27375 | 10.22661 |
Minimum of Months | 454.00000 | 23.45550 | 40.44106 | -0.0999 | 6.31988 |
Maximum of Months | 514.00000 | 24.65477 | 55.98896 | 0.75173 | 18.02908 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.67169 | 44.51502 | 0.01527 | 6.78305 |
February | 454.00000 | 23.61548 | 45.93470 | 0.29626 | 8.41656 |
March | 514.00000 | 24.28661 | 47.42766 | 0.55707 | 12.28201 |
April | 485.00000 | 24.59180 | 46.44320 | 0.72310 | 17.00838 |
May | 508.00000 | 24.61797 | 51.99374 | 0.03627 | 7.18527 |
June | 496.00000 | 24.55279 | 54.34936 | 0.03551 | 6.87147 |
July | 497.00000 | 24.67730 | 55.23137 | 0.02149 | 7.34033 |
August | 514.00000 | 24.52751 | 55.71325 | -0.0430 | 6.71155 |
September | 485.00000 | 24.57721 | 55.66796 | -0.0624 | 6.80810 |
October | 502.00000 | 24.53046 | 52.53150 | 0.67138 | 15.29513 |
November | 489.00000 | 24.10589 | 47.56548 | 0.46538 | 10.36169 |
December | 497.00000 | 23.12318 | 42.95105 | 0.13196 | 6.87138 |
Annual Sum or Average | 5943.00000 | 24.16003 | 50.06501 | 0.23620 | 9.32299 |
Minimum of Months | 454.00000 | 22.67169 | 42.95105 | -0.0624 | 6.71155 |
Maximum of Months | 514.00000 | 24.67730 | 55.71325 | 0.72310 | 17.00838 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25306 | 47.82079 | -0.3676 | 10.28748 |
February | 454.00000 | 22.57457 | 49.23815 | 0.01113 | 7.20568 |
March | 514.00000 | 23.87922 | 49.31531 | 0.40228 | 9.33347 |
April | 485.00000 | 24.42660 | 47.53447 | 0.61227 | 13.58366 |
May | 508.00000 | 24.55208 | 52.45700 | -0.0563 | 6.68949 |
June | 496.00000 | 24.49239 | 54.75102 | -0.0461 | 6.44003 |
July | 497.00000 | 24.63034 | 55.69155 | -0.0247 | 7.03695 |
August | 514.00000 | 24.46909 | 56.28217 | -0.1008 | 6.57353 |
September | 485.00000 | 24.48908 | 56.53682 | -0.1433 | 6.76165 |
October | 502.00000 | 24.24540 | 54.30238 | 0.55365 | 12.03332 |
November | 489.00000 | 23.23746 | 51.00087 | 0.21267 | 7.37360 |
December | 497.00000 | 21.61612 | 47.07185 | -0.2647 | 8.60004 |
Annual Sum or Average | 5943.00000 | 23.66356 | 51.85750 | 0.06555 | 8.49569 |
Minimum of Months | 454.00000 | 21.25306 | 47.07185 | -0.3676 | 6.44003 |
Maximum of Months | 514.00000 | 24.63034 | 56.53682 | 0.61227 | 13.58366 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03742 | 45.84630 | -0.1648 | 8.33110 |
February | 454.00000 | 23.32936 | 46.70266 | 0.21524 | 7.91493 |
March | 514.00000 | 24.19626 | 47.85592 | 0.53314 | 12.01704 |
April | 485.00000 | 24.56305 | 46.83418 | 0.72526 | 17.10649 |
May | 508.00000 | 24.60747 | 52.07334 | 0.06337 | 7.28050 |
June | 496.00000 | 24.52729 | 54.45457 | 0.02943 | 6.72724 |
July | 497.00000 | 24.65948 | 55.46753 | 0.02686 | 7.44851 |
August | 514.00000 | 24.49667 | 56.02782 | -0.0550 | 6.68503 |
September | 485.00000 | 24.53786 | 56.14945 | -0.0727 | 6.72447 |
October | 502.00000 | 24.45937 | 53.14268 | 0.65618 | 14.99902 |
November | 489.00000 | 23.83697 | 48.53085 | 0.38607 | 9.41046 |
December | 497.00000 | 22.49771 | 44.75476 | -0.0434 | 7.23398 |
Annual Sum or Average | 5943.00000 | 23.98360 | 50.68880 | 0.19081 | 9.32359 |
Minimum of Months | 454.00000 | 22.03742 | 44.75476 | -0.1648 | 6.68503 |
Maximum of Months | 514.00000 | 24.65948 | 56.14945 | 0.72526 | 17.10649 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.93496 | 42.64069 | 0.09455 | 9.03147 |
February | 454.00000 | 23.68414 | 45.38214 | 0.34665 | 10.25550 |
March | 514.00000 | 24.22784 | 47.72524 | 0.56479 | 12.94409 |
April | 485.00000 | 24.52327 | 47.09422 | 0.68474 | 15.81098 |
May | 508.00000 | 24.56124 | 52.40065 | -0.0393 | 6.75255 |
June | 496.00000 | 24.48964 | 54.76271 | -0.0497 | 6.45411 |
July | 497.00000 | 24.63059 | 55.68474 | -0.0223 | 7.06351 |
August | 514.00000 | 24.48521 | 56.16756 | -0.0787 | 6.63902 |
September | 485.00000 | 24.55466 | 56.12345 | -0.0607 | 6.84470 |
October | 502.00000 | 24.59067 | 52.60975 | 0.74177 | 17.84096 |
November | 489.00000 | 24.24749 | 46.81922 | 0.57251 | 13.78366 |
December | 497.00000 | 23.44202 | 41.58571 | 0.23764 | 9.29177 |
Annual Sum or Average | 5943.00000 | 24.20072 | 49.95802 | 0.24769 | 10.21370 |
Minimum of Months | 454.00000 | 22.93496 | 41.58571 | -0.0787 | 6.45411 |
Maximum of Months | 514.00000 | 24.63059 | 56.16756 | 0.74177 | 17.84096 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15318 | 45.14342 | -0.1308 | 8.49954 |
February | 454.00000 | 23.27925 | 46.87196 | 0.20786 | 8.35621 |
March | 514.00000 | 24.19107 | 48.01773 | 0.53623 | 12.13740 |
April | 485.00000 | 24.58456 | 46.93089 | 0.73589 | 17.52704 |
May | 508.00000 | 24.62468 | 52.11679 | 0.06374 | 7.53408 |
June | 496.00000 | 24.55516 | 54.42909 | 0.06209 | 7.14505 |
July | 497.00000 | 24.68510 | 55.36996 | 0.04616 | 7.64994 |
August | 514.00000 | 24.52990 | 55.92024 | -0.0258 | 6.86006 |
September | 485.00000 | 24.58049 | 56.05290 | -0.0477 | 6.95502 |
October | 502.00000 | 24.47748 | 53.25954 | 0.66417 | 15.22282 |
November | 489.00000 | 23.85343 | 48.63408 | 0.40061 | 9.84123 |
December | 497.00000 | 22.59496 | 44.17874 | -0.0096 | 7.50518 |
Annual Sum or Average | 5943.00000 | 24.01417 | 50.61069 | 0.20790 | 9.60063 |
Minimum of Months | 454.00000 | 22.15318 | 44.17874 | -0.1308 | 6.86006 |
Maximum of Months | 514.00000 | 24.68510 | 56.05290 | 0.73589 | 17.52704 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.327493E+11 | 81715.04 | 12-JAN-15:05 | 411.94 | 0.320593E+12 | 0.00 | 0.353342E+12 | 5.41 | 10.00 | 05-JAN-15:10 | 0.00 | 0.00 |
February | 0.603640E+11 | 187294.93 | 22-FEB-15:30 | 403.46 | 0.555944E+12 | 0.00 | 0.616308E+12 | 5.76 | 10.03 | 27-FEB-05:14 | 0.00 | 0.00 |
March | 0.129363E+12 | 200283.31 | 29-MAR-10:10 | 564.76 | 0.112804E+13 | 0.00 | 0.125741E+13 | 7.05 | 10.04 | 25-MAR-04:13 | 0.00 | 0.00 |
April | 0.172774E+12 | 205041.31 | 28-APR-19:20 | 679.71 | 0.149588E+13 | 0.00 | 0.166866E+13 | 8.64 | 10.03 | 08-APR-04:12 | 0.00 | 0.00 |
May | 0.225972E+12 | 210880.65 | 06-MAY-17:06 | 693.15 | 0.187189E+13 | 0.00 | 0.209786E+13 | 8.05 | 10.00 | 15-MAY-04:15 | 0.00 | 0.00 |
June | 0.254126E+12 | 233751.61 | 10-JUN-17:10 | 663.98 | 0.197264E+13 | 0.00 | 0.222677E+13 | 7.46 | 10.00 | 02-JUN-04:17 | 0.00 | 0.00 |
July | 0.280800E+12 | 234203.60 | 01-JUL-17:09 | 689.76 | 0.210283E+13 | 0.00 | 0.238363E+13 | 7.22 | 9.68 | 11-JUL-01:13 | 0.00 | 0.00 |
August | 0.271601E+12 | 233254.17 | 12-AUG-17:10 | 711.33 | 0.205047E+13 | 0.00 | 0.232207E+13 | 7.55 | 9.53 | 15-AUG-22:15 | 0.00 | 0.00 |
September | 0.223646E+12 | 217815.49 | 05-SEP-05:03 | 649.62 | 0.174932E+13 | 0.00 | 0.197297E+13 | 7.39 | 9.90 | 26-SEP-04:35 | 0.00 | 0.00 |
October | 0.154032E+12 | 203570.83 | 17-OCT-11:10 | 602.12 | 0.132511E+13 | 0.00 | 0.147914E+13 | 7.37 | 10.01 | 25-OCT-04:12 | 0.00 | 0.00 |
November | 0.103948E+12 | 198548.34 | 16-NOV-14:30 | 481.78 | 0.909727E+12 | 0.00 | 0.101368E+13 | 6.24 | 10.04 | 13-NOV-05:12 | 0.00 | 0.00 |
December | 0.452872E+11 | 97420.91 | 01-DEC-15:05 | 444.85 | 0.441020E+12 | 0.00 | 0.486307E+12 | 5.84 | 10.03 | 01-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.195466E+13 | 6996.46 | 0.159235E+14 | 0.00 | 0.178781E+14 | 7.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.327493E+11 | 81715.04 | 403.46 | 0.320593E+12 | 0.00 | 0.353342E+12 | 5.41 | 9.53 | 0.00 | 0.00 | ||
Maximum of Months | 0.280800E+12 | 234203.60 | 711.33 | 0.210283E+13 | 0.00 | 0.238363E+13 | 8.64 | 10.04 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.120051E+11 | 120079.29 | 28-MAR-12:05 | 43.33 | 0.110600E+12 | 0.00 | 0.122605E+12 | 0.54 | 10.72 | 24-MAR-16:00 | 0.00 | 0.00 |
April | 0.480745E+11 | 129842.59 | 18-APR-14:05 | 155.19 | 0.427364E+12 | 0.00 | 0.475439E+12 | 1.94 | 10.73 | 28-APR-08:30 | 0.00 | 0.00 |
May | 0.103338E+12 | 210816.66 | 07-MAY-17:01 | 280.60 | 0.848451E+12 | 0.00 | 0.951789E+12 | 3.15 | 10.44 | 06-MAY-17:42 | 0.00 | 0.00 |
June | 0.140070E+12 | 226451.49 | 14-JUN-05:03 | 338.13 | 0.108523E+13 | 0.00 | 0.122530E+13 | 3.73 | 10.46 | 12-JUN-05:30 | 0.00 | 0.00 |
July | 0.160018E+12 | 228778.30 | 02-JUL-17:03 | 373.94 | 0.121333E+13 | 0.00 | 0.137335E+13 | 3.89 | 9.96 | 10-JUL-21:00 | 0.00 | 0.00 |
August | 0.164400E+12 | 228584.54 | 14-AUG-05:03 | 386.34 | 0.124744E+13 | 0.00 | 0.141184E+13 | 4.02 | 10.00 | 03-AUG-06:00 | 0.00 | 0.00 |
September | 0.101063E+12 | 217815.49 | 05-SEP-05:03 | 272.11 | 0.810938E+12 | 0.00 | 0.912001E+12 | 3.08 | 10.20 | 29-SEP-07:20 | 0.00 | 0.00 |
October | 0.373082E+11 | 125413.66 | 26-OCT-12:05 | 119.06 | 0.329968E+12 | 0.00 | 0.367276E+12 | 1.43 | 10.65 | 26-OCT-12:00 | 0.00 | 0.00 |
November | 0.682490E+10 | 106848.75 | 09-NOV-11:05 | 26.00 | 0.629096E+11 | 0.00 | 0.697345E+11 | 0.34 | 10.73 | 13-NOV-13:20 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.773103E+12 | 1994.70 | 0.613623E+13 | 0.00 | 0.690933E+13 | 1.85 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.164400E+12 | 228778.30 | 386.34 | 0.124744E+13 | 0.00 | 0.141184E+13 | 4.02 | 10.73 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.412676E+11 | 744.00 | 43776.24 | 02-JAN-14:00 | 270042.73 | 02-JAN-04:55 | 22.13 | 18.89 | 16.39 |
February | 0.707706E+11 | 672.00 | 43776.24 | 01-FEB-10:40 | 373502.92 | 24-FEB-16:10 | 26.63 | 20.73 | 16.40 |
March | 0.115833E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 638350.82 | 31-MAR-24:00 | 34.14 | 25.48 | 16.40 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:03 | 738550.25 | 16-APR-17:02 | 44.92 | 33.32 | 16.40 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:03 | 379996.83 | 31-MAY-23:25 | 38.65 | 34.47 | 16.40 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 551342.82 | 30-JUN-23:42 | 43.11 | 36.11 | 16.40 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 695405.67 | 31-JUL-23:17 | 44.80 | 35.15 | 16.40 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 741788.22 | 25-AUG-14:05 | 46.50 | 34.40 | 16.40 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 378539.55 | 30-SEP-23:15 | 34.48 | 30.25 | 16.40 |
October | 0.117130E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 483965.06 | 31-OCT-23:30 | 33.76 | 27.35 | 16.40 |
November | 0.102635E+12 | 720.00 | 43776.24 | 01-NOV-00:10 | 547497.89 | 16-NOV-05:30 | 31.65 | 23.07 | 16.40 |
December | 0.795932E+11 | 744.00 | 43776.24 | 01-DEC-08:65 | 658776.83 | 28-DEC-15:05 | 31.07 | 20.28 | 16.40 |
Annual Sum or Average | 0.121938E+13 | 8760.00 | 36.04 | 28.33 | 16.40 | ||||
Minimum of Months | 0.412676E+11 | 672.00 | 43776.24 | 270042.73 | 22.13 | 18.89 | 16.39 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 741788.22 | 46.50 | 36.11 | 16.40 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.188414E+09 | 225.93 | 1162.41 | 12-JAN-15:50 | 846826.97 | 12-JAN-15:10 | 21.61 | 21.12 | 30.05 |
February | 0.895245E+09 | 310.69 | 20137.52 | 24-FEB-14:50 | 1517328.96 | 22-FEB-15:40 | 22.19 | 21.27 | 37.80 |
March | 0.886793E+10 | 488.78 | 20137.52 | 06-MAR-11:00 | 1571869.17 | 15-MAR-14:30 | 23.01 | 21.31 | 49.45 |
April | 0.237936E+11 | 620.65 | 20137.52 | 01-APR-09:00 | 1570091.41 | 10-APR-10:00 | 24.06 | 21.72 | 62.49 |
May | 0.454451E+11 | 693.07 | 20137.52 | 01-MAY-04:06 | 1524286.88 | 06-MAY-09:00 | 26.80 | 24.05 | 60.31 |
June | 0.478601E+11 | 663.98 | 20137.52 | 01-JUN-00:25 | 1510063.85 | 14-JUN-05:03 | 29.16 | 26.15 | 54.73 |
July | 0.500040E+11 | 689.76 | 20137.52 | 01-JUL-00:10 | 1526037.24 | 03-JUL-05:06 | 30.94 | 27.81 | 52.11 |
August | 0.515677E+11 | 711.33 | 20137.52 | 01-AUG-00:05 | 1501683.08 | 28-AUG-05:03 | 30.51 | 27.48 | 55.46 |
September | 0.469925E+11 | 649.62 | 20137.52 | 01-SEP-00:05 | 1324636.84 | 26-SEP-07:20 | 28.86 | 26.20 | 51.61 |
October | 0.237868E+11 | 564.80 | 20137.52 | 01-OCT-00:05 | 1531363.46 | 16-OCT-09:00 | 23.86 | 21.88 | 53.97 |
November | 0.419587E+10 | 423.62 | 20137.52 | 06-NOV-10:30 | 1567948.27 | 02-NOV-13:30 | 22.73 | 21.31 | 44.25 |
December | 0.357090E+09 | 276.54 | 1827.61 | 28-DEC-15:00 | 967609.57 | 01-DEC-15:05 | 21.78 | 21.11 | 34.79 |
Annual Sum or Average | 0.303954E+12 | 6318.76 | 25.48 | 23.46 | 48.96 | ||||
Minimum of Months | 0.188414E+09 | 225.93 | 1162.41 | 846826.97 | 21.61 | 21.11 | 30.05 | ||
Maximum of Months | 0.515677E+11 | 711.33 | 20137.52 | 1571869.17 | 30.94 | 27.81 | 62.49 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 21.61 | 21.61 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 22.19 | 22.19 | 0.00 |
March | 0.205431E+10 | 31.83 | 20137.52 | 06-MAR-13:05 | 1305382.47 | 14-MAR-13:30 | 23.01 | 22.85 | 2.88 |
April | 0.918111E+10 | 141.18 | 20137.52 | 01-APR-15:00 | 1328652.59 | 10-APR-14:05 | 24.06 | 23.37 | 13.14 |
May | 0.262650E+11 | 362.30 | 20137.52 | 01-MAY-05:03 | 1348630.59 | 30-MAY-15:20 | 26.80 | 25.09 | 29.69 |
June | 0.378273E+11 | 521.79 | 20137.52 | 01-JUN-05:07 | 1510063.85 | 14-JUN-05:03 | 29.16 | 26.54 | 41.13 |
July | 0.455449E+11 | 628.25 | 20137.52 | 01-JUL-00:10 | 1526037.24 | 03-JUL-05:06 | 30.94 | 27.88 | 46.42 |
August | 0.443166E+11 | 611.31 | 20137.52 | 01-AUG-00:05 | 1501683.08 | 28-AUG-05:03 | 30.51 | 27.59 | 46.20 |
September | 0.356866E+11 | 492.26 | 20137.52 | 01-SEP-00:05 | 1317136.49 | 14-SEP-14:40 | 28.86 | 26.48 | 36.56 |
October | 0.893645E+10 | 124.62 | 20137.52 | 02-OCT-07:40 | 1281936.54 | 24-OCT-14:50 | 23.86 | 23.28 | 10.70 |
November | 0.260462E+09 | 9.00 | 20137.52 | 06-NOV-11:30 | 1287435.91 | 16-NOV-14:10 | 22.73 | 22.68 | 0.86 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.78 | 21.78 | 0.00 |
Annual Sum or Average | 0.210073E+12 | 2922.54 | 25.48 | 24.29 | 19.08 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 21.61 | 0.00 | ||
Maximum of Months | 0.455449E+11 | 628.25 | 20137.52 | 1526037.24 | 30.94 | 27.88 | 46.42 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 22.13 | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 26.63 | 26.63 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 34.14 | 34.14 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 44.92 | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 38.65 | 38.65 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 43.11 | 43.11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 44.80 | 44.80 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 46.50 | 46.50 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 34.48 | 34.48 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 33.76 | 33.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 31.65 | 31.65 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 31.07 | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 36.04 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 46.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.355809E+11 | 0.00 | 357.14 | 0.355359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76084.64 | 18-JAN-06:03 | 72476.68 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.576291E+11 | 0.00 | 384.07 | 0.575109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148776.47 | 25-FEB-06:02 | 104988.14 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.125262E+12 | 0.00 | 546.19 | 0.122878E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 219571.89 | 13-MAR-04:22 | 165609.40 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.210107E+12 | 0.00 | 628.15 | 0.201633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260167.98 | 17-APR-03:02 | 211586.29 | 30-APR-17:02 | 0.00 | 0.00 | 0.00 |
May | 0.281537E+12 | 0.00 | 648.69 | 0.244254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284133.32 | 22-MAY-04:23 | 217517.70 | 29-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.322872E+12 | 0.00 | 629.26 | 0.252312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 303701.11 | 14-JUN-03:02 | 214838.98 | 11-JUN-16:21 | 0.00 | 0.00 | 0.00 |
July | 0.360660E+12 | 0.00 | 649.20 | 0.244777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 309323.16 | 05-JUL-03:02 | 227187.66 | 04-JUL-17:42 | 0.00 | 0.00 | 0.00 |
August | 0.378287E+12 | 0.00 | 660.27 | 0.251838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 319625.23 | 27-AUG-14:22 | 204281.54 | 06-AUG-17:02 | 0.00 | 0.00 | 0.00 |
September | 0.290015E+12 | 0.00 | 608.02 | 0.200422E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 292149.22 | 18-SEP-03:02 | 189051.38 | 18-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.171191E+12 | 0.00 | 563.75 | 0.152484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 238896.69 | 02-OCT-05:03 | 174600.95 | 02-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.953984E+11 | 0.00 | 456.89 | 0.940350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163969.59 | 09-NOV-05:12 | 119307.98 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.566276E+11 | 0.00 | 419.33 | 0.566274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91901.73 | 04-DEC-15:00 | 91901.73 | 04-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238517E+13 | 0.00 | 6550.96 | 0.191431E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.355809E+11 | 0.00 | 357.14 | 0.355359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76084.64 | 72476.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.378287E+12 | 0.00 | 660.27 | 0.252312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 319625.23 | 227187.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.215781E+12 | 0.00 | 324.32 | 0.215781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 591530.94 | 12-JAN-15:05 | 591530.94 | 12-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.396255E+12 | 0.00 | 357.17 | 0.395444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1078081.03 | 25-FEB-06:02 | 861585.36 | 22-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.913988E+12 | 0.00 | 473.15 | 0.898962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1928172.20 | 13-MAR-04:12 | 1508712.00 | 30-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.148381E+13 | 0.00 | 557.28 | 0.142737E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2089190.97 | 27-APR-05:02 | 1611011.13 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.217174E+13 | 0.00 | 631.16 | 0.183624E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2541249.65 | 22-MAY-05:02 | 1827158.82 | 30-MAY-05:01 | 0.00 | 0.00 | 0.00 |
June | 0.245488E+13 | 0.00 | 596.92 | 0.180290E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2774148.62 | 14-JUN-05:01 | 1937154.12 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.266632E+13 | 0.00 | 601.63 | 0.159561E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2935439.46 | 25-JUL-05:02 | 1821355.18 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.264440E+13 | 0.00 | 585.37 | 0.152427E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2896318.90 | 12-AUG-05:02 | 1690552.68 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.204257E+13 | 0.00 | 524.73 | 0.127240E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2815375.30 | 05-SEP-05:02 | 1665050.36 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.125669E+13 | 0.00 | 487.47 | 0.110663E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2157171.37 | 11-OCT-03:02 | 1539001.59 | 02-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.689374E+12 | 0.00 | 428.44 | 0.679793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1395598.69 | 09-NOV-06:03 | 981330.12 | 08-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.297936E+12 | 0.00 | 366.22 | 0.297936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 670332.12 | 29-DEC-06:03 | 670332.12 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172337E+14 | 0.00 | 5933.87 | 0.130533E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.215781E+12 | 0.00 | 324.32 | 0.215781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 591530.94 | 591530.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.266632E+13 | 0.00 | 631.16 | 0.183624E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2935439.46 | 1937154.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.172890E+11 | 0.00 | 295.07 | 0.172890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57737.92 | 12-JAN-15:30 | 57737.92 | 12-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.358521E+11 | 0.00 | 338.61 | 0.357738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98237.74 | 25-FEB-06:02 | 95668.99 | 22-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.930587E+11 | 0.00 | 462.24 | 0.916819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185819.38 | 29-MAR-04:12 | 150906.48 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.161503E+12 | 0.00 | 551.26 | 0.155821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230594.90 | 03-APR-04:12 | 182339.19 | 30-APR-16:31 | 0.00 | 0.00 | 0.00 |
May | 0.238722E+12 | 0.00 | 631.12 | 0.204961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281173.01 | 22-MAY-05:02 | 235004.37 | 29-MAY-16:41 | 0.00 | 0.00 | 0.00 |
June | 0.267239E+12 | 0.00 | 598.36 | 0.202035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311166.15 | 14-JUN-05:01 | 223263.79 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.283854E+12 | 0.00 | 605.79 | 0.176556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326648.52 | 25-JUL-05:02 | 208415.70 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.278032E+12 | 0.00 | 590.72 | 0.165937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 320805.95 | 28-AUG-04:02 | 201281.88 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.212651E+12 | 0.00 | 524.67 | 0.136024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 293480.88 | 14-SEP-05:02 | 179561.09 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.127058E+12 | 0.00 | 478.11 | 0.112875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 226029.21 | 11-OCT-03:02 | 164185.54 | 02-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.634742E+11 | 0.00 | 407.56 | 0.629027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117422.72 | 09-NOV-06:03 | 109344.95 | 09-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.227096E+11 | 0.00 | 330.85 | 0.227096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66240.74 | 01-DEC-15:00 | 66240.74 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180144E+13 | 0.00 | 5814.35 | 0.138456E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.172890E+11 | 0.00 | 295.07 | 0.172890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57737.92 | 57737.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.283854E+12 | 0.00 | 631.12 | 0.204961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326648.52 | 235004.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.471565E+11 | 0.00 | 391.77 | 0.469716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121243.12 | 18-JAN-05:13 | 90330.16 | 14-JAN-05:13 | 0.00 | 0.00 | 0.00 |
February | 0.505305E+11 | 0.00 | 358.00 | 0.499500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135429.18 | 25-FEB-05:12 | 93547.68 | 21-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.605110E+11 | 0.00 | 329.04 | 0.587339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 244785.63 | 13-MAR-21:02 | 97395.24 | 15-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.193734E+11 | 0.00 | 69.79 | 0.176889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256515.03 | 22-APR-21:45 | 105451.27 | 23-APR-05:52 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 |
October | 0.672671E+11 | 0.00 | 225.04 | 0.587950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 270773.74 | 07-OCT-03:15 | 112133.81 | 02-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.730658E+11 | 0.00 | 393.04 | 0.723878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144218.19 | 09-NOV-05:12 | 95295.09 | 03-NOV-04:12 | 0.00 | 0.00 | 0.00 |
December | 0.587673E+11 | 0.00 | 396.28 | 0.586657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114092.63 | 30-DEC-05:12 | 95319.50 | 29-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.376672E+12 | 0.00 | 2162.96 | 0.363193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.730658E+11 | 0.00 | 396.28 | 0.723878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 270773.74 | 112133.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.351062E+12 | 0.836711E+11 | 744.00 | 0.337222E+12 | 0.138396E+11 | 0.00 | 0.32 | 12-JAN-16:00 | 0.29 | 22-JAN-06:00 | 136526.57 | 17-JAN-17:00 | 132156.84 | 12-JAN-15:00 | 6815.35 | 17-JAN-17:00 | 38708.08 | 12-JAN-15:00 | 0.00 |
February | 0.545992E+12 | 0.131803E+12 | 672.00 | 0.528425E+12 | 0.175667E+11 | 0.00 | 0.54 | 22-FEB-15:00 | 0.48 | 01-FEB-00:10 | 230357.12 | 27-FEB-10:05 | 224987.76 | 22-FEB-15:00 | 10175.51 | 27-FEB-10:00 | 71114.50 | 22-FEB-15:00 | 0.00 |
March | 0.852777E+12 | 0.229884E+12 | 744.00 | 0.836378E+12 | 0.163986E+11 | 0.00 | 0.87 | 31-MAR-24:00 | 0.67 | 01-MAR-00:10 | 401767.23 | 31-MAR-24:00 | 399123.23 | 31-MAR-23:55 | 13681.31 | 06-MAR-04:40 | 123383.39 | 28-MAR-15:20 | 0.00 |
April | 0.106327E+13 | 0.344204E+12 | 720.00 | 0.105507E+13 | 0.819855E+10 | 0.00 | 1.00 | 15-APR-12:50 | 0.37 | 30-APR-23:53 | 421009.15 | 18-APR-16:00 | 414845.27 | 27-APR-16:00 | 12038.53 | 11-APR-05:00 | 175204.88 | 15-APR-15:00 | 0.00 |
May | 0.380202E+12 | 0.141313E+12 | 744.00 | 0.363317E+12 | 0.168852E+11 | 0.00 | 0.54 | 31-MAY-23:10 | 0.32 | 28-MAY-05:00 | 232531.71 | 31-MAY-23:10 | 219420.70 | 31-MAY-23:53 | 15443.74 | 22-MAY-23:20 | 73217.80 | 31-MAY-23:15 | 0.00 |
June | 0.616508E+12 | 0.226906E+12 | 720.00 | 0.590632E+12 | 0.258756E+11 | 0.00 | 0.76 | 30-JUN-23:13 | 0.53 | 18-JUN-04:57 | 325677.80 | 30-JUN-23:03 | 313909.20 | 30-JUN-23:53 | 18615.85 | 28-JUN-13:10 | 116054.52 | 30-JUN-23:13 | 0.00 |
July | 0.893594E+12 | 0.307862E+12 | 744.00 | 0.856391E+12 | 0.372022E+11 | 0.00 | 0.93 | 31-JUL-23:13 | 0.72 | 19-JUL-03:00 | 422437.14 | 31-JUL-23:03 | 405266.63 | 31-JUL-23:57 | 19829.77 | 18-JUL-08:30 | 142970.46 | 07-JUL-15:00 | 0.00 |
August | 0.113972E+13 | 0.373191E+12 | 744.00 | 0.110120E+13 | 0.385163E+11 | 0.00 | 1.00 | 07-AUG-13:05 | 0.38 | 31-AUG-23:13 | 434215.56 | 25-AUG-14:05 | 416928.40 | 07-AUG-13:05 | 19670.71 | 21-AUG-14:00 | 167367.37 | 07-AUG-15:00 | 0.00 |
September | 0.383826E+12 | 0.125497E+12 | 720.00 | 0.352442E+12 | 0.313837E+11 | 0.00 | 0.54 | 30-SEP-23:05 | 0.33 | 27-SEP-05:00 | 234536.20 | 30-SEP-23:05 | 220609.11 | 30-SEP-24:00 | 18072.03 | 12-SEP-16:00 | 70705.71 | 30-SEP-23:15 | 0.00 |
October | 0.617852E+12 | 0.181927E+12 | 744.00 | 0.601200E+12 | 0.166521E+11 | 0.00 | 0.68 | 31-OCT-23:30 | 0.50 | 29-OCT-05:00 | 317797.82 | 31-OCT-24:00 | 307567.68 | 31-OCT-24:00 | 11515.91 | 06-OCT-09:10 | 93535.05 | 02-OCT-15:00 | 0.00 |
November | 0.833539E+12 | 0.208543E+12 | 720.00 | 0.811549E+12 | 0.219901E+11 | 0.00 | 0.75 | 08-NOV-15:00 | 0.67 | 01-NOV-05:00 | 326851.55 | 24-NOV-08:50 | 319301.58 | 08-NOV-15:00 | 14282.96 | 23-NOV-08:00 | 106969.85 | 08-NOV-15:00 | 0.00 |
December | 0.111612E+13 | 0.246742E+12 | 744.00 | 0.107800E+13 | 0.381236E+11 | 0.00 | 0.90 | 28-DEC-15:00 | 0.84 | 01-DEC-00:10 | 429141.06 | 22-DEC-08:65 | 408349.07 | 28-DEC-15:00 | 26589.49 | 22-DEC-07:15 | 116859.27 | 28-DEC-14:20 | 0.00 |
Annual Sum or Average | 0.879446E+13 | 0.260154E+13 | 8760.00 | 0.851183E+13 | 0.282632E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.351062E+12 | 0.836711E+11 | 672.00 | 0.337222E+12 | 0.819855E+10 | 0.00 | 0.32 | 0.29 | 136526.57 | 132156.84 | 6815.35 | 38708.08 | 0.00 | ||||||
Maximum of Months | 0.113972E+13 | 0.373191E+12 | 744.00 | 0.110120E+13 | 0.385163E+11 | 0.00 | 1.00 | 0.84 | 434215.56 | 416928.40 | 26589.49 | 175204.88 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.468073E+10 | 0.112927E+10 | 744.00 | 0.452252E+10 | 0.158203E+09 | 0.00 | 0.30 | 12-JAN-17:00 | 0.16 | 03-JAN-08:00 | 2419.53 | 12-JAN-17:00 | 2285.32 | 12-JAN-17:00 | 254.45 | 17-JAN-17:00 | 657.36 | 12-JAN-16:00 | 0.00 |
February | 0.946194E+10 | 0.226788E+10 | 672.00 | 0.921951E+10 | 0.242432E+09 | 0.00 | 0.55 | 20-FEB-17:03 | 0.39 | 01-FEB-07:00 | 4496.53 | 21-FEB-17:00 | 4465.85 | 20-FEB-17:20 | 261.54 | 15-FEB-17:00 | 1331.41 | 22-FEB-15:00 | 0.00 |
March | 0.162526E+11 | 0.428841E+10 | 744.00 | 0.158935E+11 | 0.359091E+09 | 0.00 | 0.89 | 31-MAR-24:00 | 0.62 | 01-MAR-07:00 | 7854.42 | 31-MAR-24:00 | 7733.62 | 31-MAR-23:55 | 349.84 | 10-MAR-17:10 | 2424.32 | 28-MAR-16:00 | 0.00 |
April | 0.212193E+11 | 0.662839E+10 | 720.00 | 0.208718E+11 | 0.347457E+09 | 0.00 | 1.00 | 01-APR-17:00 | 0.40 | 30-APR-24:00 | 8745.59 | 16-APR-20:54 | 8495.78 | 16-APR-21:32 | 398.76 | 26-APR-08:00 | 3253.01 | 15-APR-15:00 | 0.00 |
May | 0.760235E+10 | 0.271683E+10 | 744.00 | 0.691441E+10 | 0.687941E+09 | 0.00 | 0.56 | 31-MAY-23:10 | 0.29 | 13-MAY-07:00 | 4738.79 | 31-MAY-23:10 | 4170.16 | 31-MAY-23:53 | 656.42 | 22-MAY-23:00 | 1524.16 | 28-MAY-16:31 | 0.00 |
June | 0.127319E+11 | 0.447634E+10 | 720.00 | 0.116209E+11 | 0.111100E+10 | 0.00 | 0.81 | 30-JUN-23:53 | 0.54 | 02-JUN-06:00 | 6767.60 | 30-JUN-23:03 | 6288.43 | 30-JUN-23:53 | 822.84 | 28-JUN-13:40 | 2395.55 | 11-JUN-16:10 | 0.00 |
July | 0.186917E+11 | 0.613192E+10 | 744.00 | 0.170405E+11 | 0.165117E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.75 | 19-JUL-02:40 | 8847.47 | 31-JUL-23:03 | 8122.98 | 31-JUL-24:00 | 859.34 | 18-JUL-08:20 | 3045.31 | 02-JUL-16:50 | 0.00 |
August | 0.233082E+11 | 0.724088E+10 | 744.00 | 0.215624E+11 | 0.174574E+10 | 0.00 | 1.00 | 01-AUG-00:05 | 0.39 | 31-AUG-23:05 | 8995.68 | 20-AUG-16:54 | 8333.92 | 20-AUG-18:05 | 883.80 | 21-AUG-14:00 | 3112.81 | 07-AUG-15:00 | 0.00 |
September | 0.767257E+10 | 0.238315E+10 | 720.00 | 0.637314E+10 | 0.129943E+10 | 0.00 | 0.57 | 30-SEP-23:05 | 0.31 | 08-SEP-21:20 | 4830.06 | 30-SEP-23:05 | 4236.60 | 30-SEP-24:00 | 738.97 | 12-SEP-16:00 | 1382.01 | 30-SEP-23:15 | 0.00 |
October | 0.118721E+11 | 0.339522E+10 | 744.00 | 0.112332E+11 | 0.638905E+09 | 0.00 | 0.67 | 31-OCT-23:10 | 0.46 | 28-OCT-07:00 | 5984.86 | 31-OCT-23:10 | 5751.57 | 31-OCT-24:00 | 502.78 | 06-OCT-09:50 | 1875.56 | 01-OCT-15:51 | 0.00 |
November | 0.155412E+11 | 0.382638E+10 | 720.00 | 0.152041E+11 | 0.337055E+09 | 0.00 | 0.78 | 08-NOV-16:20 | 0.62 | 25-NOV-08:00 | 6555.74 | 08-NOV-16:50 | 6431.89 | 12-NOV-16:20 | 291.84 | 08-NOV-17:10 | 2054.30 | 08-NOV-15:00 | 0.00 |
December | 0.203850E+11 | 0.447620E+10 | 744.00 | 0.201917E+11 | 0.193329E+09 | 0.00 | 0.92 | 25-DEC-14:53 | 0.78 | 23-DEC-08:00 | 8209.93 | 28-DEC-17:00 | 8026.67 | 28-DEC-17:00 | 265.88 | 29-DEC-17:10 | 2222.98 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.169419E+12 | 0.489609E+11 | 8760.00 | 0.160648E+12 | 0.877176E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.468073E+10 | 0.112927E+10 | 672.00 | 0.452252E+10 | 0.158203E+09 | 0.00 | 0.30 | 0.16 | 2419.53 | 2285.32 | 254.45 | 657.36 | 0.00 | ||||||
Maximum of Months | 0.233082E+11 | 0.724088E+10 | 744.00 | 0.215624E+11 | 0.174574E+10 | 0.00 | 1.00 | 0.78 | 8995.68 | 8495.78 | 883.80 | 3253.01 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.311152E+11 | 0.768575E+10 | 722.00 | 0.298270E+11 | 0.128820E+10 | 0.00 | 0.30 | 12-JAN-17:00 | 0.00 | 01-JAN-00:10 | 22271.91 | 12-JAN-17:00 | 21017.61 | 12-JAN-17:00 | 2404.36 | 17-JAN-16:40 | 5985.14 | 12-JAN-17:00 | 0.00 |
February | 0.834391E+11 | 0.200854E+11 | 672.00 | 0.812036E+11 | 0.223551E+10 | 0.00 | 0.55 | 22-FEB-17:00 | 0.33 | 11-FEB-07:50 | 42316.04 | 22-FEB-17:00 | 40784.60 | 22-FEB-17:00 | 2531.61 | 15-FEB-17:00 | 12490.84 | 22-FEB-15:00 | 0.00 |
March | 0.152878E+12 | 0.402064E+11 | 744.00 | 0.149492E+12 | 0.338536E+10 | 0.00 | 0.91 | 31-MAR-24:00 | 0.61 | 01-MAR-07:00 | 75408.30 | 31-MAR-24:00 | 74274.56 | 31-MAR-23:55 | 3405.10 | 10-MAR-17:10 | 22911.02 | 28-MAR-16:00 | 0.00 |
April | 0.199884E+12 | 0.620794E+11 | 720.00 | 0.196597E+12 | 0.328705E+10 | 0.00 | 1.00 | 01-APR-14:50 | 0.35 | 30-APR-24:00 | 81577.86 | 16-APR-20:54 | 78934.46 | 16-APR-21:05 | 3916.78 | 26-APR-08:00 | 30284.75 | 15-APR-15:00 | 0.00 |
May | 0.693212E+11 | 0.247425E+11 | 744.00 | 0.627395E+11 | 0.658174E+10 | 0.00 | 0.57 | 31-MAY-23:10 | 0.28 | 13-MAY-07:00 | 45050.19 | 31-MAY-23:10 | 39432.72 | 31-MAY-23:53 | 6343.09 | 22-MAY-23:15 | 13670.30 | 28-MAY-16:51 | 0.00 |
June | 0.118631E+12 | 0.415439E+11 | 720.00 | 0.107797E+12 | 0.108334E+11 | 0.00 | 0.82 | 30-JUN-23:03 | 0.53 | 24-JUN-13:20 | 63926.80 | 30-JUN-23:03 | 58923.04 | 30-JUN-23:53 | 8111.67 | 28-JUN-13:20 | 21814.19 | 08-JUN-16:00 | 0.00 |
July | 0.174474E+12 | 0.569702E+11 | 744.00 | 0.158242E+12 | 0.162327E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.75 | 19-JUL-03:00 | 82780.89 | 31-JUL-23:03 | 75741.89 | 31-JUL-24:00 | 8477.31 | 18-JUL-08:20 | 27755.23 | 02-JUL-16:50 | 0.00 |
August | 0.218727E+12 | 0.675149E+11 | 744.00 | 0.201535E+12 | 0.171913E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.34 | 31-AUG-23:05 | 84517.91 | 10-AUG-14:00 | 77264.29 | 20-AUG-17:45 | 8692.69 | 21-AUG-14:00 | 28984.52 | 07-AUG-15:00 | 0.00 |
September | 0.691101E+11 | 0.214125E+11 | 720.00 | 0.565567E+11 | 0.125533E+11 | 0.00 | 0.57 | 30-SEP-23:05 | 0.29 | 08-SEP-21:20 | 45267.93 | 30-SEP-23:05 | 39150.21 | 30-SEP-24:00 | 7203.81 | 12-SEP-16:00 | 12845.43 | 30-SEP-23:10 | 0.00 |
October | 0.110521E+12 | 0.315173E+11 | 744.00 | 0.104378E+12 | 0.614290E+10 | 0.00 | 0.68 | 31-OCT-23:20 | 0.45 | 31-OCT-06:00 | 56631.68 | 31-OCT-23:10 | 54353.38 | 31-OCT-24:00 | 4932.61 | 06-OCT-09:50 | 17290.07 | 02-OCT-15:10 | 0.00 |
November | 0.143781E+12 | 0.353730E+11 | 720.00 | 0.140612E+12 | 0.316899E+10 | 0.00 | 0.79 | 08-NOV-16:20 | 0.59 | 26-NOV-07:00 | 62370.93 | 08-NOV-17:00 | 59804.37 | 08-NOV-16:30 | 2819.81 | 08-NOV-17:10 | 19380.58 | 08-NOV-15:00 | 0.00 |
December | 0.184163E+12 | 0.405419E+11 | 744.00 | 0.182396E+12 | 0.176668E+10 | 0.00 | 0.93 | 28-DEC-16:50 | 0.73 | 24-DEC-06:00 | 77566.74 | 28-DEC-17:00 | 75825.26 | 28-DEC-17:00 | 2572.51 | 29-DEC-17:10 | 20884.90 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.155604E+13 | 0.449673E+12 | 8738.00 | 0.147138E+13 | 0.846672E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.311152E+11 | 0.768575E+10 | 672.00 | 0.298270E+11 | 0.128820E+10 | 0.00 | 0.30 | 0.00 | 22271.91 | 21017.61 | 2404.36 | 5985.14 | 0.00 | ||||||
Maximum of Months | 0.218727E+12 | 0.675149E+11 | 744.00 | 0.201535E+12 | 0.171913E+11 | 0.00 | 1.00 | 0.75 | 84517.91 | 78934.46 | 8692.69 | 30284.75 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.202886E+10 | 0.517262E+09 | 603.39 | 0.191316E+10 | 0.115700E+09 | 0.00 | 0.29 | 12-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2267.60 | 12-JAN-17:00 | 2133.47 | 12-JAN-17:00 | 262.83 | 17-JAN-15:05 | 611.84 | 12-JAN-17:00 | 0.00 |
February | 0.775095E+10 | 0.189573E+10 | 672.00 | 0.751475E+10 | 0.236202E+09 | 0.00 | 0.54 | 22-FEB-17:00 | 0.23 | 11-FEB-05:55 | 4297.52 | 22-FEB-17:00 | 4136.48 | 22-FEB-17:00 | 260.36 | 15-FEB-17:00 | 1276.84 | 22-FEB-15:00 | 0.00 |
March | 0.151516E+11 | 0.402634E+10 | 744.00 | 0.147945E+11 | 0.357064E+09 | 0.00 | 0.88 | 31-MAR-24:00 | 0.55 | 01-MAR-08:00 | 7508.13 | 31-MAR-24:00 | 7387.54 | 31-MAR-23:55 | 348.22 | 10-MAR-17:10 | 2354.20 | 28-MAR-16:00 | 0.00 |
April | 0.201709E+11 | 0.632218E+10 | 720.00 | 0.198243E+11 | 0.346571E+09 | 0.00 | 1.00 | 01-APR-16:50 | 0.35 | 30-APR-24:00 | 8453.13 | 16-APR-20:54 | 8184.09 | 16-APR-21:15 | 398.53 | 26-APR-08:00 | 3141.69 | 15-APR-15:00 | 0.00 |
May | 0.717200E+10 | 0.257362E+10 | 744.00 | 0.649347E+10 | 0.678535E+09 | 0.00 | 0.55 | 31-MAY-23:10 | 0.26 | 13-MAY-07:00 | 4467.89 | 31-MAY-23:10 | 3894.75 | 31-MAY-23:53 | 640.84 | 31-MAY-23:10 | 1569.18 | 28-MAY-16:51 | 0.00 |
June | 0.120845E+11 | 0.425866E+10 | 720.00 | 0.109812E+11 | 0.110337E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.51 | 24-JUN-13:40 | 6471.11 | 30-JUN-23:03 | 5966.59 | 30-JUN-23:53 | 821.34 | 28-JUN-13:40 | 2391.24 | 11-JUN-16:50 | 0.00 |
July | 0.176825E+11 | 0.581315E+10 | 744.00 | 0.160388E+11 | 0.164371E+10 | 0.00 | 0.99 | 31-JUL-23:03 | 0.72 | 19-JUL-03:00 | 8423.79 | 31-JUL-23:03 | 7632.62 | 31-JUL-23:57 | 854.62 | 18-JUL-08:20 | 2973.43 | 02-JUL-16:50 | 0.00 |
August | 0.222001E+11 | 0.692063E+10 | 744.00 | 0.204543E+11 | 0.174582E+10 | 0.00 | 1.00 | 01-AUG-10:00 | 0.34 | 31-AUG-23:13 | 8646.28 | 20-AUG-16:54 | 7966.47 | 20-AUG-17:05 | 882.29 | 21-AUG-14:00 | 3005.99 | 07-AUG-15:00 | 0.00 |
September | 0.702291E+10 | 0.218882E+10 | 720.00 | 0.574774E+10 | 0.127517E+10 | 0.00 | 0.56 | 30-SEP-23:05 | 0.28 | 27-SEP-07:00 | 4566.93 | 30-SEP-23:05 | 3939.30 | 30-SEP-23:33 | 727.09 | 12-SEP-16:00 | 1303.98 | 30-SEP-23:10 | 0.00 |
October | 0.110053E+11 | 0.316764E+10 | 744.00 | 0.103732E+11 | 0.632132E+09 | 0.00 | 0.65 | 01-OCT-16:52 | 0.40 | 28-OCT-07:00 | 5568.04 | 31-OCT-23:10 | 5310.43 | 31-OCT-23:50 | 502.06 | 06-OCT-09:50 | 1809.18 | 01-OCT-16:21 | 0.00 |
November | 0.139264E+11 | 0.347299E+10 | 720.00 | 0.135924E+11 | 0.334054E+09 | 0.00 | 0.77 | 08-NOV-16:20 | 0.49 | 26-NOV-07:40 | 6292.71 | 08-NOV-16:50 | 6033.50 | 08-NOV-16:20 | 289.52 | 08-NOV-17:10 | 1971.55 | 08-NOV-15:00 | 0.00 |
December | 0.173232E+11 | 0.387615E+10 | 744.00 | 0.171310E+11 | 0.192182E+09 | 0.00 | 0.91 | 28-DEC-16:50 | 0.59 | 31-DEC-08:70 | 7791.78 | 28-DEC-17:00 | 7609.93 | 28-DEC-17:00 | 264.09 | 29-DEC-17:10 | 2113.90 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.153519E+12 | 0.450332E+11 | 8619.39 | 0.144859E+12 | 0.866050E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.202886E+10 | 0.517262E+09 | 603.39 | 0.191316E+10 | 0.115700E+09 | 0.00 | 0.29 | 0.00 | 2267.60 | 2133.47 | 260.36 | 611.84 | 0.00 | ||||||
Maximum of Months | 0.222001E+11 | 0.692063E+10 | 744.00 | 0.204543E+11 | 0.174582E+10 | 0.00 | 1.00 | 0.72 | 8646.28 | 8184.09 | 882.29 | 3141.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.64 | 467.10 | 16.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.71 | 360.91 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 236.99 | 213.76 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 408.83 | 82.67 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 569.69 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 615.89 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 537.43 | 6.07 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 450.46 | 16.68 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 355.77 | 46.41 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 262.67 | 170.33 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.38 | 322.87 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.43 | 461.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 318.61 | 181.15 | 16.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.64 | 6.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 615.89 | 467.10 | 16.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.64 | 467.10 | 16.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.71 | 360.91 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 236.99 | 213.76 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 408.83 | 82.67 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 569.69 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 615.89 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 537.43 | 6.07 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 450.46 | 16.68 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 355.77 | 46.41 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 262.67 | 170.33 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.38 | 322.87 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.43 | 461.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 318.61 | 181.15 | 16.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.64 | 6.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 615.89 | 467.10 | 16.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.64 | 467.10 | 16.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.71 | 360.91 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 236.99 | 213.76 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 408.83 | 82.67 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 569.69 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 615.89 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 537.43 | 6.07 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 450.46 | 16.68 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 355.77 | 46.41 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 262.67 | 170.33 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.38 | 322.87 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.43 | 461.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 318.61 | 181.15 | 16.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.64 | 6.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 615.89 | 467.10 | 16.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.64 | 467.10 | 16.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.71 | 360.91 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 236.99 | 213.76 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 408.83 | 82.67 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 569.69 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 615.89 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 537.43 | 6.07 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 450.46 | 16.68 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 355.77 | 46.41 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 262.67 | 170.33 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.38 | 322.87 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.43 | 461.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 318.61 | 181.15 | 16.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.64 | 6.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 615.89 | 467.10 | 16.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.64 | 467.08 | 16.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.71 | 360.89 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 236.98 | 213.75 | 0.00 | 0.00 | 0.00 |
April | 163.79 | 0.56 | 163.23 | 408.82 | 82.67 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.37 | 569.67 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.89 | 615.86 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 185.26 | 2.93 | 182.33 | 537.41 | 6.07 | 0.00 | 0.00 | 0.00 |
August | 170.07 | 0.53 | 169.54 | 450.44 | 16.68 | 0.00 | 0.00 | 0.00 |
September | 151.54 | 0.01 | 151.53 | 355.76 | 46.41 | 0.00 | 0.00 | 0.00 |
October | 131.28 | 0.00 | 131.28 | 262.66 | 170.32 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.38 | 322.85 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.43 | 461.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.39 | 1.35 | 146.05 | 318.60 | 181.15 | 16.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.64 | 6.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 615.86 | 467.08 | 16.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.44 | 100.93 | 150.52 | 256.07 | 472.86 | 15.83 | 0.00 | 0.00 |
February | 305.47 | 126.11 | 179.36 | 404.64 | 369.78 | 0.00 | 0.00 | 0.00 |
March | 372.64 | 153.81 | 218.83 | 630.10 | 222.73 | 0.00 | 0.00 | 0.00 |
April | 443.35 | 206.71 | 236.64 | 940.00 | 90.80 | 0.00 | 0.00 | 0.00 |
May | 436.38 | 193.47 | 242.91 | 1063.68 | 23.30 | 0.00 | 0.00 | 0.00 |
June | 355.15 | 117.84 | 237.31 | 956.23 | 16.09 | 0.00 | 0.00 | 0.00 |
July | 298.50 | 63.03 | 235.46 | 771.90 | 5.90 | 0.00 | 0.00 | 0.00 |
August | 268.96 | 46.81 | 222.15 | 652.61 | 17.39 | 0.00 | 0.00 | 0.00 |
September | 287.35 | 80.14 | 207.22 | 615.32 | 53.41 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 126.97 | 187.36 | 603.85 | 184.21 | 0.00 | 0.00 | 0.00 |
November | 278.70 | 119.63 | 159.07 | 425.32 | 332.60 | 0.00 | 0.00 | 0.00 |
December | 243.01 | 96.28 | 146.73 | 269.86 | 465.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.19 | 119.13 | 202.06 | 633.22 | 187.12 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 243.01 | 46.81 | 146.73 | 256.07 | 5.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.35 | 206.71 | 242.91 | 1063.68 | 472.86 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.44 | 100.93 | 150.52 | 256.07 | 472.86 | 15.83 | 0.00 | 0.00 |
February | 305.47 | 126.11 | 179.36 | 404.64 | 369.78 | 0.00 | 0.00 | 0.00 |
March | 372.64 | 153.81 | 218.83 | 630.10 | 222.73 | 0.00 | 0.00 | 0.00 |
April | 443.35 | 206.71 | 236.64 | 940.00 | 90.80 | 0.00 | 0.00 | 0.00 |
May | 436.38 | 193.47 | 242.91 | 1063.68 | 23.30 | 0.00 | 0.00 | 0.00 |
June | 355.15 | 117.84 | 237.31 | 956.23 | 16.09 | 0.00 | 0.00 | 0.00 |
July | 298.50 | 63.03 | 235.46 | 771.90 | 5.90 | 0.00 | 0.00 | 0.00 |
August | 268.96 | 46.81 | 222.15 | 652.61 | 17.39 | 0.00 | 0.00 | 0.00 |
September | 287.35 | 80.14 | 207.22 | 615.32 | 53.41 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 126.97 | 187.36 | 603.85 | 184.21 | 0.00 | 0.00 | 0.00 |
November | 278.70 | 119.63 | 159.07 | 425.32 | 332.60 | 0.00 | 0.00 | 0.00 |
December | 243.01 | 96.28 | 146.73 | 269.86 | 465.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.19 | 119.13 | 202.06 | 633.22 | 187.12 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 243.01 | 46.81 | 146.73 | 256.07 | 5.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.35 | 206.71 | 242.91 | 1063.68 | 472.86 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.44 | 100.92 | 150.52 | 256.07 | 472.85 | 15.83 | 0.00 | 0.00 |
February | 305.47 | 126.11 | 179.36 | 404.63 | 369.78 | 0.00 | 0.00 | 0.00 |
March | 372.64 | 153.81 | 218.83 | 630.09 | 222.72 | 0.00 | 0.00 | 0.00 |
April | 443.34 | 206.71 | 236.63 | 939.98 | 90.79 | 0.00 | 0.00 | 0.00 |
May | 436.37 | 193.46 | 242.91 | 1063.66 | 23.30 | 0.00 | 0.00 | 0.00 |
June | 355.15 | 117.84 | 237.31 | 956.21 | 16.09 | 0.00 | 0.00 | 0.00 |
July | 298.49 | 63.03 | 235.46 | 771.89 | 5.90 | 0.00 | 0.00 | 0.00 |
August | 268.95 | 46.80 | 222.15 | 652.59 | 17.39 | 0.00 | 0.00 | 0.00 |
September | 287.35 | 80.13 | 207.21 | 615.31 | 53.41 | 0.00 | 0.00 | 0.00 |
October | 314.32 | 126.97 | 187.36 | 603.84 | 184.21 | 0.00 | 0.00 | 0.00 |
November | 278.69 | 119.63 | 159.07 | 425.31 | 332.60 | 0.00 | 0.00 | 0.00 |
December | 243.01 | 96.28 | 146.73 | 269.86 | 465.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.18 | 119.12 | 202.06 | 633.21 | 187.11 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 243.01 | 46.80 | 146.73 | 256.07 | 5.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.34 | 206.71 | 242.91 | 1063.66 | 472.85 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.67 | 431.52 | 18.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.06 | 352.37 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 714.40 | 220.90 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 666.27 | 87.90 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 613.77 | 18.58 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 603.68 | 13.22 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 549.34 | 4.92 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 517.74 | 15.33 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 595.58 | 47.05 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 894.90 | 180.97 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.62 | 326.46 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.14 | 434.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 689.80 | 177.03 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 517.74 | 4.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.62 | 434.53 | 18.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.67 | 431.52 | 18.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.06 | 352.37 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 714.40 | 220.90 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 666.27 | 87.90 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 613.77 | 18.58 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 603.68 | 13.22 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 549.34 | 4.92 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 517.74 | 15.33 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 595.58 | 47.05 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 894.90 | 180.97 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.62 | 326.46 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.13 | 434.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 689.80 | 177.03 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 517.74 | 4.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.62 | 434.53 | 18.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.67 | 431.52 | 18.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.06 | 352.37 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 714.40 | 220.90 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 666.27 | 87.90 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 613.77 | 18.58 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 603.68 | 13.22 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 549.34 | 4.92 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 517.74 | 15.33 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 595.58 | 47.05 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 894.90 | 180.97 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.62 | 326.46 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.14 | 434.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 689.80 | 177.03 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 517.74 | 4.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.62 | 434.53 | 18.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.67 | 431.52 | 18.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.06 | 352.37 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 714.40 | 220.90 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 666.27 | 87.90 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 613.77 | 18.58 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 603.68 | 13.22 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 549.34 | 4.92 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 517.74 | 15.33 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 595.58 | 47.05 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 894.90 | 180.97 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.62 | 326.46 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.13 | 434.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 689.80 | 177.03 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 517.74 | 4.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.62 | 434.53 | 18.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.43 | 291.92 | 188.51 | 683.64 | 431.51 | 18.00 | 0.00 | 0.00 |
February | 456.82 | 253.73 | 203.09 | 710.03 | 352.36 | 0.00 | 0.00 | 0.00 |
March | 390.59 | 172.52 | 218.07 | 714.38 | 220.89 | 0.00 | 0.00 | 0.00 |
April | 274.35 | 77.43 | 196.92 | 666.25 | 87.89 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.69 | 613.75 | 18.58 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 603.66 | 13.22 | 0.00 | 0.00 | 0.00 |
July | 188.25 | 2.59 | 185.66 | 549.31 | 4.92 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.03 | 517.72 | 15.33 | 0.00 | 0.00 | 0.00 |
September | 267.71 | 69.48 | 198.22 | 595.56 | 47.04 | 0.00 | 0.00 | 0.00 |
October | 460.57 | 257.18 | 203.39 | 894.86 | 180.96 | 0.00 | 0.00 | 0.00 |
November | 575.27 | 380.24 | 195.03 | 975.58 | 326.44 | 0.00 | 0.00 | 0.00 |
December | 513.41 | 321.72 | 191.69 | 757.10 | 434.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.12 | 154.02 | 194.09 | 689.77 | 177.02 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 517.72 | 4.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.27 | 380.24 | 218.07 | 975.58 | 434.52 | 18.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.00 | 95.73 | 150.26 | 278.59 | 553.26 | 15.83 | 0.00 | 0.00 |
February | 281.30 | 103.67 | 177.64 | 377.97 | 449.50 | 0.00 | 0.00 | 0.00 |
March | 364.78 | 145.82 | 218.96 | 613.12 | 285.14 | 0.00 | 0.00 | 0.00 |
April | 443.39 | 207.93 | 235.46 | 923.99 | 122.67 | 0.00 | 0.00 | 0.00 |
May | 419.85 | 178.09 | 241.76 | 1033.49 | 26.88 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 153.18 | 241.17 | 1018.40 | 19.82 | 0.00 | 0.00 | 0.00 |
July | 292.63 | 56.92 | 235.71 | 740.95 | 10.43 | 0.00 | 0.00 | 0.00 |
August | 268.75 | 47.76 | 220.98 | 633.02 | 27.48 | 0.00 | 0.00 | 0.00 |
September | 295.42 | 86.73 | 208.70 | 632.27 | 56.03 | 0.00 | 0.00 | 0.00 |
October | 307.49 | 122.44 | 185.05 | 591.48 | 220.27 | 0.00 | 0.00 | 0.00 |
November | 278.18 | 118.56 | 159.62 | 434.03 | 413.13 | 0.00 | 0.00 | 0.00 |
December | 238.04 | 90.77 | 147.27 | 266.05 | 577.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.12 | 117.14 | 201.98 | 629.32 | 229.26 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 238.04 | 47.76 | 147.27 | 266.05 | 10.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.39 | 207.93 | 241.76 | 1033.49 | 577.91 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.00 | 95.73 | 150.26 | 278.59 | 553.26 | 15.83 | 0.00 | 0.00 |
February | 281.30 | 103.67 | 177.64 | 377.97 | 449.50 | 0.00 | 0.00 | 0.00 |
March | 364.78 | 145.82 | 218.96 | 613.12 | 285.14 | 0.00 | 0.00 | 0.00 |
April | 443.39 | 207.93 | 235.46 | 923.99 | 122.67 | 0.00 | 0.00 | 0.00 |
May | 419.85 | 178.09 | 241.76 | 1033.49 | 26.88 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 153.18 | 241.17 | 1018.40 | 19.82 | 0.00 | 0.00 | 0.00 |
July | 292.63 | 56.92 | 235.71 | 740.95 | 10.43 | 0.00 | 0.00 | 0.00 |
August | 268.75 | 47.76 | 220.98 | 633.02 | 27.48 | 0.00 | 0.00 | 0.00 |
September | 295.42 | 86.73 | 208.70 | 632.27 | 56.03 | 0.00 | 0.00 | 0.00 |
October | 307.49 | 122.44 | 185.05 | 591.48 | 220.27 | 0.00 | 0.00 | 0.00 |
November | 278.18 | 118.56 | 159.62 | 434.03 | 413.13 | 0.00 | 0.00 | 0.00 |
December | 238.04 | 90.77 | 147.27 | 266.05 | 577.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.12 | 117.14 | 201.98 | 629.32 | 229.26 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 238.04 | 47.76 | 147.27 | 266.05 | 10.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.39 | 207.93 | 241.76 | 1033.49 | 577.91 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 245.99 | 95.73 | 150.26 | 278.59 | 553.25 | 15.83 | 0.00 | 0.00 |
February | 281.30 | 103.67 | 177.63 | 377.96 | 449.49 | 0.00 | 0.00 | 0.00 |
March | 364.77 | 145.81 | 218.96 | 613.10 | 285.14 | 0.00 | 0.00 | 0.00 |
April | 443.38 | 207.93 | 235.45 | 923.98 | 122.66 | 0.00 | 0.00 | 0.00 |
May | 419.84 | 178.09 | 241.75 | 1033.47 | 26.88 | 0.00 | 0.00 | 0.00 |
June | 394.34 | 153.17 | 241.17 | 1018.38 | 19.82 | 0.00 | 0.00 | 0.00 |
July | 292.62 | 56.91 | 235.71 | 740.94 | 10.43 | 0.00 | 0.00 | 0.00 |
August | 268.74 | 47.76 | 220.98 | 633.01 | 27.48 | 0.00 | 0.00 | 0.00 |
September | 295.42 | 86.73 | 208.69 | 632.26 | 56.03 | 0.00 | 0.00 | 0.00 |
October | 307.48 | 122.44 | 185.04 | 591.47 | 220.27 | 0.00 | 0.00 | 0.00 |
November | 278.17 | 118.55 | 159.62 | 434.02 | 413.12 | 0.00 | 0.00 | 0.00 |
December | 238.03 | 90.77 | 147.26 | 266.04 | 577.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.12 | 117.14 | 201.97 | 629.31 | 229.25 | 15.83 | 0.00 | 0.00 |
Minimum of Months | 238.03 | 47.76 | 147.26 | 266.04 | 10.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.38 | 207.93 | 241.75 | 1033.47 | 577.90 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 528.19 | 0.00 | 528.19 | 368.32 | 2023.02 | 4.67 | 0.00 | 0.00 |
February | 626.35 | 0.00 | 626.35 | 661.80 | 1616.24 | 0.00 | 0.00 | 0.00 |
March | 754.75 | 0.00 | 754.75 | 1226.27 | 994.02 | 0.00 | 0.00 | 0.00 |
April | 818.97 | 2.78 | 816.19 | 2138.10 | 349.33 | 0.00 | 0.00 | 0.00 |
May | 907.36 | 25.46 | 881.90 | 2964.71 | 64.46 | 0.00 | 0.00 | 0.00 |
June | 939.26 | 34.79 | 904.47 | 3217.23 | 48.10 | 0.00 | 0.00 | 0.00 |
July | 926.33 | 14.67 | 911.66 | 2849.79 | 12.72 | 0.00 | 0.00 | 0.00 |
August | 850.39 | 2.65 | 847.74 | 2402.77 | 41.58 | 0.00 | 0.00 | 0.00 |
September | 757.72 | 0.05 | 757.67 | 1873.22 | 146.01 | 0.00 | 0.00 | 0.00 |
October | 656.43 | 0.00 | 656.43 | 1366.60 | 779.61 | 0.00 | 0.00 | 0.00 |
November | 556.01 | 0.00 | 556.01 | 756.54 | 1464.60 | 0.00 | 0.00 | 0.00 |
December | 515.26 | 0.00 | 515.26 | 401.87 | 1986.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.98 | 6.73 | 730.25 | 1690.61 | 790.30 | 4.67 | 0.00 | 0.00 |
Minimum of Months | 515.26 | 0.00 | 515.26 | 368.32 | 12.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.26 | 34.79 | 911.66 | 3217.23 | 2023.02 | 4.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 754.32 | 302.78 | 451.55 | 809.99 | 1287.72 | 5.50 | 0.00 | 0.00 |
February | 916.41 | 378.34 | 538.07 | 1222.13 | 1052.40 | 0.00 | 0.00 | 0.00 |
March | 1117.92 | 461.44 | 656.48 | 1877.94 | 662.14 | 0.00 | 0.00 | 0.00 |
April | 1330.04 | 620.13 | 709.91 | 2829.06 | 254.76 | 0.00 | 0.00 | 0.00 |
May | 1309.12 | 580.39 | 728.73 | 3229.97 | 49.01 | 0.00 | 0.00 | 0.00 |
June | 1065.45 | 353.52 | 711.94 | 2926.35 | 34.98 | 0.00 | 0.00 | 0.00 |
July | 895.49 | 189.10 | 706.38 | 2392.80 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 806.87 | 140.41 | 666.46 | 2022.83 | 30.16 | 0.00 | 0.00 | 0.00 |
September | 862.05 | 240.40 | 621.64 | 1884.38 | 108.38 | 0.00 | 0.00 | 0.00 |
October | 942.98 | 380.90 | 562.08 | 1813.11 | 533.18 | 0.00 | 0.00 | 0.00 |
November | 836.09 | 358.89 | 477.20 | 1280.08 | 962.50 | 0.00 | 0.00 | 0.00 |
December | 729.03 | 288.85 | 440.19 | 844.88 | 1292.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.55 | 357.37 | 606.18 | 1930.28 | 520.66 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 729.03 | 140.41 | 440.19 | 809.99 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.04 | 620.13 | 728.73 | 3229.97 | 1292.71 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2402.22 | 1459.65 | 942.57 | 3413.03 | 2083.49 | 5.33 | 0.00 | 0.00 |
February | 2284.16 | 1268.69 | 1015.47 | 3532.62 | 1716.69 | 0.00 | 0.00 | 0.00 |
March | 1953.02 | 862.63 | 1090.39 | 3562.53 | 1085.38 | 0.00 | 0.00 | 0.00 |
April | 1371.80 | 387.17 | 984.64 | 3376.89 | 400.66 | 0.00 | 0.00 | 0.00 |
May | 986.51 | 73.03 | 913.48 | 3167.79 | 64.94 | 0.00 | 0.00 | 0.00 |
June | 902.40 | 15.40 | 887.00 | 3143.29 | 47.63 | 0.00 | 0.00 | 0.00 |
July | 941.29 | 12.95 | 928.34 | 2893.86 | 11.27 | 0.00 | 0.00 | 0.00 |
August | 998.51 | 53.33 | 945.18 | 2713.44 | 43.82 | 0.00 | 0.00 | 0.00 |
September | 1338.58 | 347.43 | 991.15 | 3032.53 | 175.37 | 0.00 | 0.00 | 0.00 |
October | 2302.89 | 1285.93 | 1016.97 | 4469.14 | 890.01 | 0.00 | 0.00 | 0.00 |
November | 2876.44 | 1901.26 | 975.17 | 4855.43 | 1608.67 | 0.00 | 0.00 | 0.00 |
December | 2567.15 | 1608.65 | 958.50 | 3788.87 | 2092.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1740.64 | 770.14 | 970.49 | 3494.32 | 847.79 | 5.33 | 0.00 | 0.00 |
Minimum of Months | 902.40 | 12.95 | 887.00 | 2713.44 | 11.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2876.44 | 1901.26 | 1090.39 | 4855.43 | 2092.28 | 5.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 737.99 | 287.20 | 450.79 | 894.20 | 1437.46 | 0.00 | 0.00 | 0.00 |
February | 843.91 | 311.00 | 532.90 | 1185.65 | 1170.51 | 0.00 | 0.00 | 0.00 |
March | 1094.33 | 437.44 | 656.89 | 1881.38 | 746.25 | 0.00 | 0.00 | 0.00 |
April | 1330.15 | 623.79 | 706.36 | 2835.33 | 299.43 | 0.00 | 0.00 | 0.00 |
May | 1259.53 | 534.27 | 725.26 | 3142.57 | 64.82 | 0.00 | 0.00 | 0.00 |
June | 1183.03 | 459.52 | 723.51 | 3128.52 | 44.11 | 0.00 | 0.00 | 0.00 |
July | 877.87 | 170.75 | 707.12 | 2327.84 | 13.08 | 0.00 | 0.00 | 0.00 |
August | 806.23 | 143.29 | 662.94 | 2004.49 | 38.91 | 0.00 | 0.00 | 0.00 |
September | 886.26 | 260.18 | 626.08 | 1930.28 | 132.21 | 0.00 | 0.00 | 0.00 |
October | 922.46 | 367.32 | 555.14 | 1809.48 | 590.31 | 0.00 | 0.00 | 0.00 |
November | 834.52 | 355.67 | 478.85 | 1356.97 | 1070.32 | 0.00 | 0.00 | 0.00 |
December | 714.10 | 272.30 | 441.80 | 889.84 | 1414.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 957.36 | 351.43 | 605.93 | 1951.16 | 582.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 714.10 | 143.29 | 441.80 | 889.84 | 13.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.15 | 623.79 | 725.26 | 3142.57 | 1437.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 528.19 | 0.00 | 528.19 | 415.86 | 1836.88 | 0.00 | 0.00 | 0.00 |
February | 626.35 | 0.00 | 626.35 | 693.63 | 1508.64 | 0.00 | 0.00 | 0.00 |
March | 754.75 | 0.00 | 754.75 | 1221.71 | 962.57 | 0.00 | 0.00 | 0.00 |
April | 818.97 | 2.78 | 816.19 | 2105.05 | 354.60 | 0.00 | 0.00 | 0.00 |
May | 907.36 | 25.46 | 881.90 | 2916.67 | 72.44 | 0.00 | 0.00 | 0.00 |
June | 939.26 | 34.79 | 904.47 | 3165.68 | 52.50 | 0.00 | 0.00 | 0.00 |
July | 926.33 | 14.67 | 911.66 | 2792.40 | 13.64 | 0.00 | 0.00 | 0.00 |
August | 850.39 | 2.65 | 847.74 | 2358.62 | 44.72 | 0.00 | 0.00 | 0.00 |
September | 757.72 | 0.05 | 757.67 | 1843.68 | 155.46 | 0.00 | 0.00 | 0.00 |
October | 656.43 | 0.00 | 656.43 | 1353.95 | 765.28 | 0.00 | 0.00 | 0.00 |
November | 556.01 | 0.00 | 556.01 | 780.86 | 1378.37 | 0.00 | 0.00 | 0.00 |
December | 515.26 | 0.00 | 515.26 | 456.92 | 1811.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.98 | 6.73 | 730.25 | 1680.22 | 742.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.26 | 0.00 | 515.26 | 415.86 | 13.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.26 | 34.79 | 911.66 | 3165.68 | 1836.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 754.32 | 302.78 | 451.55 | 868.32 | 1172.55 | 0.00 | 0.00 | 0.00 |
February | 916.41 | 378.34 | 538.07 | 1253.06 | 992.07 | 0.00 | 0.00 | 0.00 |
March | 1117.92 | 461.44 | 656.48 | 1881.43 | 645.44 | 0.00 | 0.00 | 0.00 |
April | 1330.04 | 620.13 | 709.91 | 2814.71 | 257.34 | 0.00 | 0.00 | 0.00 |
May | 1309.12 | 580.39 | 728.73 | 3206.19 | 53.63 | 0.00 | 0.00 | 0.00 |
June | 1065.45 | 353.52 | 711.94 | 2901.04 | 37.42 | 0.00 | 0.00 | 0.00 |
July | 895.49 | 189.10 | 706.38 | 2364.06 | 8.52 | 0.00 | 0.00 | 0.00 |
August | 806.87 | 140.41 | 666.46 | 2002.82 | 32.09 | 0.00 | 0.00 | 0.00 |
September | 862.05 | 240.40 | 621.64 | 1873.03 | 113.69 | 0.00 | 0.00 | 0.00 |
October | 942.98 | 380.90 | 562.08 | 1812.59 | 524.49 | 0.00 | 0.00 | 0.00 |
November | 836.09 | 358.89 | 477.20 | 1303.43 | 915.86 | 0.00 | 0.00 | 0.00 |
December | 729.03 | 288.85 | 440.19 | 900.03 | 1189.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.55 | 357.37 | 606.18 | 1934.11 | 492.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 729.03 | 140.41 | 440.19 | 868.32 | 8.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.04 | 620.13 | 728.73 | 3206.19 | 1189.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2402.22 | 1459.65 | 942.57 | 3469.94 | 1915.54 | 0.00 | 0.00 | 0.00 |
February | 2284.16 | 1268.69 | 1015.47 | 3554.58 | 1624.40 | 0.00 | 0.00 | 0.00 |
March | 1953.02 | 862.63 | 1090.39 | 3550.68 | 1056.60 | 0.00 | 0.00 | 0.00 |
April | 1371.80 | 387.17 | 984.64 | 3343.23 | 405.38 | 0.00 | 0.00 | 0.00 |
May | 986.51 | 73.03 | 913.48 | 3120.03 | 72.46 | 0.00 | 0.00 | 0.00 |
June | 902.40 | 15.40 | 887.00 | 3091.38 | 52.21 | 0.00 | 0.00 | 0.00 |
July | 941.29 | 12.95 | 928.34 | 2836.29 | 12.05 | 0.00 | 0.00 | 0.00 |
August | 998.51 | 53.33 | 945.18 | 2669.81 | 47.15 | 0.00 | 0.00 | 0.00 |
September | 1338.58 | 347.43 | 991.15 | 3002.50 | 184.73 | 0.00 | 0.00 | 0.00 |
October | 2302.89 | 1285.93 | 1016.97 | 4454.53 | 875.95 | 0.00 | 0.00 | 0.00 |
November | 2876.44 | 1901.26 | 975.17 | 4865.54 | 1539.37 | 0.00 | 0.00 | 0.00 |
December | 2567.15 | 1608.65 | 958.50 | 3842.43 | 1948.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1740.64 | 770.14 | 970.49 | 3481.82 | 807.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 902.40 | 12.95 | 887.00 | 2669.81 | 12.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2876.44 | 1901.26 | 1090.39 | 4865.54 | 1948.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 737.99 | 287.20 | 450.79 | 918.57 | 1328.30 | 0.00 | 0.00 | 0.00 |
February | 843.91 | 311.00 | 532.90 | 1196.29 | 1108.23 | 0.00 | 0.00 | 0.00 |
March | 1094.33 | 437.44 | 656.89 | 1872.20 | 726.24 | 0.00 | 0.00 | 0.00 |
April | 1330.15 | 623.79 | 706.36 | 2813.58 | 301.18 | 0.00 | 0.00 | 0.00 |
May | 1259.53 | 534.27 | 725.26 | 3114.04 | 69.23 | 0.00 | 0.00 | 0.00 |
June | 1183.03 | 459.52 | 723.51 | 3096.92 | 46.37 | 0.00 | 0.00 | 0.00 |
July | 877.87 | 170.75 | 707.12 | 2294.57 | 13.97 | 0.00 | 0.00 | 0.00 |
August | 806.23 | 143.29 | 662.94 | 1979.54 | 41.58 | 0.00 | 0.00 | 0.00 |
September | 886.26 | 260.18 | 626.08 | 1911.73 | 137.68 | 0.00 | 0.00 | 0.00 |
October | 922.46 | 367.32 | 555.14 | 1799.50 | 580.24 | 0.00 | 0.00 | 0.00 |
November | 834.52 | 355.67 | 478.85 | 1363.57 | 1020.95 | 0.00 | 0.00 | 0.00 |
December | 714.10 | 272.30 | 441.80 | 916.78 | 1315.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 957.36 | 351.43 | 605.93 | 1941.98 | 554.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 714.10 | 143.29 | 441.80 | 916.78 | 13.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.15 | 623.79 | 725.26 | 3114.04 | 1328.30 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149019E+09 | 0.125109E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287183E+09 | 0.873105E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.634762E+09 | 0.572523E+09 |
April | 0.424558E+09 | 1439819.52 | 0.423118E+09 | 0.105969E+10 | 0.214288E+09 |
May | 0.486059E+09 | 13639734.17 | 0.472420E+09 | 0.152587E+10 | 53027767.73 |
June | 0.486918E+09 | 18035552.38 | 0.468883E+09 | 0.159638E+10 | 37142182.58 |
July | 0.496220E+09 | 7857944.09 | 0.488362E+09 | 0.143946E+10 | 16270789.10 |
August | 0.455544E+09 | 1419727.41 | 0.454125E+09 | 0.120651E+10 | 44686695.74 |
September | 0.392809E+09 | 27582.24 | 0.392782E+09 | 0.922161E+09 | 0.120298E+09 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.703538E+09 | 0.456200E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361281E+09 | 0.836871E+09 |
December | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.161851E+09 | 0.123740E+10 |
Annual Sum or Average | 0.464832E+10 | 42420359.81 | 0.460590E+10 | 0.100477E+11 | 0.571290E+10 |
Minimum of Months | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.149019E+09 | 16270789.10 |
Maximum of Months | 0.496220E+09 | 18035552.38 | 0.488362E+09 | 0.159638E+10 | 0.125109E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149019E+09 | 0.125108E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287183E+09 | 0.873105E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.634761E+09 | 0.572523E+09 |
April | 0.424558E+09 | 1439817.79 | 0.423118E+09 | 0.105969E+10 | 0.214288E+09 |
May | 0.486059E+09 | 13639717.81 | 0.472419E+09 | 0.152586E+10 | 53027683.06 |
June | 0.486918E+09 | 18035530.74 | 0.468882E+09 | 0.159638E+10 | 37142148.32 |
July | 0.496220E+09 | 7857934.66 | 0.488362E+09 | 0.143946E+10 | 16270761.24 |
August | 0.455544E+09 | 1419725.71 | 0.454124E+09 | 0.120651E+10 | 44686640.17 |
September | 0.392809E+09 | 27582.20 | 0.392781E+09 | 0.922161E+09 | 0.120298E+09 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.703537E+09 | 0.456200E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361280E+09 | 0.836871E+09 |
December | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.161850E+09 | 0.123740E+10 |
Annual Sum or Average | 0.464832E+10 | 42420308.91 | 0.460590E+10 | 0.100477E+11 | 0.571290E+10 |
Minimum of Months | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.149019E+09 | 16270761.24 |
Maximum of Months | 0.496220E+09 | 18035530.74 | 0.488362E+09 | 0.159638E+10 | 0.125108E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149019E+09 | 0.125109E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287183E+09 | 0.873105E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.634762E+09 | 0.572523E+09 |
April | 0.424558E+09 | 1439819.52 | 0.423118E+09 | 0.105969E+10 | 0.214288E+09 |
May | 0.486059E+09 | 13639734.17 | 0.472420E+09 | 0.152587E+10 | 53027767.73 |
June | 0.486918E+09 | 18035552.38 | 0.468883E+09 | 0.159638E+10 | 37142182.58 |
July | 0.496220E+09 | 7857944.09 | 0.488362E+09 | 0.143946E+10 | 16270789.10 |
August | 0.455544E+09 | 1419727.41 | 0.454125E+09 | 0.120651E+10 | 44686695.74 |
September | 0.392809E+09 | 27582.24 | 0.392782E+09 | 0.922161E+09 | 0.120298E+09 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.703538E+09 | 0.456200E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361281E+09 | 0.836871E+09 |
December | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.161851E+09 | 0.123740E+10 |
Annual Sum or Average | 0.464832E+10 | 42420359.81 | 0.460590E+10 | 0.100477E+11 | 0.571290E+10 |
Minimum of Months | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.149019E+09 | 16270789.10 |
Maximum of Months | 0.496220E+09 | 18035552.38 | 0.488362E+09 | 0.159638E+10 | 0.125109E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149019E+09 | 0.125108E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287183E+09 | 0.873105E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.634761E+09 | 0.572523E+09 |
April | 0.424558E+09 | 1439817.79 | 0.423118E+09 | 0.105969E+10 | 0.214288E+09 |
May | 0.486059E+09 | 13639717.81 | 0.472419E+09 | 0.152586E+10 | 53027683.06 |
June | 0.486918E+09 | 18035530.74 | 0.468882E+09 | 0.159638E+10 | 37142148.32 |
July | 0.496220E+09 | 7857934.66 | 0.488362E+09 | 0.143946E+10 | 16270761.24 |
August | 0.455544E+09 | 1419725.71 | 0.454124E+09 | 0.120651E+10 | 44686640.17 |
September | 0.392809E+09 | 27582.20 | 0.392781E+09 | 0.922161E+09 | 0.120298E+09 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.703537E+09 | 0.456200E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361280E+09 | 0.836871E+09 |
December | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.161850E+09 | 0.123740E+10 |
Annual Sum or Average | 0.464832E+10 | 42420308.91 | 0.460590E+10 | 0.100477E+11 | 0.571290E+10 |
Minimum of Months | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.149019E+09 | 16270761.24 |
Maximum of Months | 0.496220E+09 | 18035530.74 | 0.488362E+09 | 0.159638E+10 | 0.125108E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282935E+09 | 0.00 | 0.282935E+09 | 0.149013E+09 | 0.125103E+10 |
February | 0.303044E+09 | 0.00 | 0.303044E+09 | 0.287171E+09 | 0.873070E+09 |
March | 0.404295E+09 | 0.00 | 0.404295E+09 | 0.634736E+09 | 0.572500E+09 |
April | 0.424541E+09 | 1439761.49 | 0.423101E+09 | 0.105965E+10 | 0.214280E+09 |
May | 0.486040E+09 | 13639184.43 | 0.472401E+09 | 0.152580E+10 | 53025630.47 |
June | 0.486899E+09 | 18034825.47 | 0.468864E+09 | 0.159632E+10 | 37140685.58 |
July | 0.496200E+09 | 7857627.38 | 0.488342E+09 | 0.143940E+10 | 16270133.31 |
August | 0.455526E+09 | 1419670.19 | 0.454106E+09 | 0.120646E+10 | 44684894.67 |
September | 0.392793E+09 | 27581.12 | 0.392766E+09 | 0.922124E+09 | 0.120293E+09 |
October | 0.351629E+09 | 0.00 | 0.351629E+09 | 0.703509E+09 | 0.456182E+09 |
November | 0.288226E+09 | 0.00 | 0.288226E+09 | 0.361266E+09 | 0.836837E+09 |
December | 0.276008E+09 | 0.00 | 0.276008E+09 | 0.161844E+09 | 0.123736E+10 |
Annual Sum or Average | 0.464814E+10 | 42418650.09 | 0.460572E+10 | 0.100473E+11 | 0.571267E+10 |
Minimum of Months | 0.276008E+09 | 0.00 | 0.276008E+09 | 0.149013E+09 | 16270133.31 |
Maximum of Months | 0.496200E+09 | 18034825.47 | 0.488342E+09 | 0.159632E+10 | 0.125103E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673468E+09 | 0.270321E+09 | 0.403147E+09 | 0.685857E+09 | 0.126650E+10 |
February | 0.739000E+09 | 0.305094E+09 | 0.433906E+09 | 0.978906E+09 | 0.894580E+09 |
March | 0.998091E+09 | 0.411977E+09 | 0.586114E+09 | 0.168766E+10 | 0.596554E+09 |
April | 0.114916E+10 | 0.535799E+09 | 0.613365E+09 | 0.243648E+10 | 0.235344E+09 |
May | 0.116880E+10 | 0.518180E+09 | 0.650615E+09 | 0.284896E+10 | 62416292.14 |
June | 0.920561E+09 | 0.305441E+09 | 0.615119E+09 | 0.247854E+10 | 41695111.47 |
July | 0.799498E+09 | 0.168833E+09 | 0.630665E+09 | 0.206747E+10 | 15809986.56 |
August | 0.720381E+09 | 0.125363E+09 | 0.595018E+09 | 0.174794E+10 | 46571762.99 |
September | 0.744818E+09 | 0.207711E+09 | 0.537106E+09 | 0.159491E+10 | 0.138432E+09 |
October | 0.841901E+09 | 0.340072E+09 | 0.501828E+09 | 0.161735E+10 | 0.493397E+09 |
November | 0.722388E+09 | 0.310081E+09 | 0.412306E+09 | 0.110242E+10 | 0.862110E+09 |
December | 0.650888E+09 | 0.257886E+09 | 0.393003E+09 | 0.722794E+09 | 0.124747E+10 |
Annual Sum or Average | 0.101290E+11 | 0.375676E+10 | 0.637219E+10 | 0.199693E+11 | 0.590088E+10 |
Minimum of Months | 0.650888E+09 | 0.125363E+09 | 0.393003E+09 | 0.685857E+09 | 15809986.56 |
Maximum of Months | 0.116880E+10 | 0.535799E+09 | 0.650615E+09 | 0.284896E+10 | 0.126650E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673468E+09 | 0.270321E+09 | 0.403147E+09 | 0.685857E+09 | 0.126650E+10 |
February | 0.739000E+09 | 0.305094E+09 | 0.433906E+09 | 0.978906E+09 | 0.894580E+09 |
March | 0.998091E+09 | 0.411977E+09 | 0.586114E+09 | 0.168766E+10 | 0.596554E+09 |
April | 0.114916E+10 | 0.535799E+09 | 0.613365E+09 | 0.243648E+10 | 0.235344E+09 |
May | 0.116880E+10 | 0.518180E+09 | 0.650615E+09 | 0.284896E+10 | 62416292.14 |
June | 0.920561E+09 | 0.305441E+09 | 0.615119E+09 | 0.247854E+10 | 41695111.47 |
July | 0.799498E+09 | 0.168833E+09 | 0.630665E+09 | 0.206747E+10 | 15809986.56 |
August | 0.720381E+09 | 0.125363E+09 | 0.595018E+09 | 0.174794E+10 | 46571762.99 |
September | 0.744818E+09 | 0.207711E+09 | 0.537106E+09 | 0.159491E+10 | 0.138432E+09 |
October | 0.841901E+09 | 0.340072E+09 | 0.501828E+09 | 0.161735E+10 | 0.493397E+09 |
November | 0.722388E+09 | 0.310081E+09 | 0.412306E+09 | 0.110242E+10 | 0.862110E+09 |
December | 0.650888E+09 | 0.257886E+09 | 0.393003E+09 | 0.722794E+09 | 0.124747E+10 |
Annual Sum or Average | 0.101290E+11 | 0.375676E+10 | 0.637219E+10 | 0.199693E+11 | 0.590088E+10 |
Minimum of Months | 0.650888E+09 | 0.125363E+09 | 0.393003E+09 | 0.685857E+09 | 15809986.56 |
Maximum of Months | 0.116880E+10 | 0.535799E+09 | 0.650615E+09 | 0.284896E+10 | 0.126650E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673456E+09 | 0.270316E+09 | 0.403140E+09 | 0.685845E+09 | 0.126648E+10 |
February | 0.738986E+09 | 0.305088E+09 | 0.433898E+09 | 0.978888E+09 | 0.894564E+09 |
March | 0.998073E+09 | 0.411970E+09 | 0.586103E+09 | 0.168763E+10 | 0.596543E+09 |
April | 0.114914E+10 | 0.535789E+09 | 0.613354E+09 | 0.243643E+10 | 0.235340E+09 |
May | 0.116877E+10 | 0.518171E+09 | 0.650603E+09 | 0.284891E+10 | 62415151.65 |
June | 0.920544E+09 | 0.305436E+09 | 0.615108E+09 | 0.247849E+10 | 41694349.61 |
July | 0.799483E+09 | 0.168830E+09 | 0.630654E+09 | 0.206743E+10 | 15809697.68 |
August | 0.720368E+09 | 0.125361E+09 | 0.595007E+09 | 0.174791E+10 | 46570912.02 |
September | 0.744804E+09 | 0.207707E+09 | 0.537097E+09 | 0.159488E+10 | 0.138429E+09 |
October | 0.841885E+09 | 0.340066E+09 | 0.501819E+09 | 0.161732E+10 | 0.493388E+09 |
November | 0.722374E+09 | 0.310076E+09 | 0.412299E+09 | 0.110240E+10 | 0.862094E+09 |
December | 0.650876E+09 | 0.257881E+09 | 0.392995E+09 | 0.722781E+09 | 0.124745E+10 |
Annual Sum or Average | 0.101288E+11 | 0.375669E+10 | 0.637208E+10 | 0.199689E+11 | 0.590077E+10 |
Minimum of Months | 0.650876E+09 | 0.125361E+09 | 0.392995E+09 | 0.685845E+09 | 15809697.68 |
Maximum of Months | 0.116877E+10 | 0.535789E+09 | 0.650603E+09 | 0.284891E+10 | 0.126648E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781916E+09 | 0.504922E+09 | 0.183115E+10 | 0.115579E+10 |
February | 0.110518E+10 | 0.613850E+09 | 0.491333E+09 | 0.171778E+10 | 0.852463E+09 |
March | 0.104620E+10 | 0.462100E+09 | 0.584105E+09 | 0.191346E+10 | 0.591649E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.172698E+10 | 0.227828E+09 |
May | 0.528459E+09 | 39120360.68 | 0.489339E+09 | 0.164393E+10 | 49767401.31 |
June | 0.467811E+09 | 7983059.50 | 0.459828E+09 | 0.156475E+10 | 34274671.02 |
July | 0.504237E+09 | 6935363.78 | 0.497301E+09 | 0.147134E+10 | 13189660.51 |
August | 0.534888E+09 | 28567075.68 | 0.506321E+09 | 0.138671E+10 | 41059500.87 |
September | 0.693930E+09 | 0.180111E+09 | 0.513819E+09 | 0.154375E+10 | 0.121945E+09 |
October | 0.123363E+10 | 0.688853E+09 | 0.544776E+09 | 0.239690E+10 | 0.484699E+09 |
November | 0.149116E+10 | 0.985627E+09 | 0.505536E+09 | 0.252880E+10 | 0.846173E+09 |
December | 0.137519E+10 | 0.861730E+09 | 0.513456E+09 | 0.202791E+10 | 0.116386E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612118E+10 | 0.217535E+11 | 0.558270E+10 |
Minimum of Months | 0.467811E+09 | 6935363.78 | 0.459828E+09 | 0.138671E+10 | 13189660.51 |
Maximum of Months | 0.149116E+10 | 0.985627E+09 | 0.584105E+09 | 0.252880E+10 | 0.116386E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781915E+09 | 0.504922E+09 | 0.183114E+10 | 0.115579E+10 |
February | 0.110518E+10 | 0.613849E+09 | 0.491333E+09 | 0.171777E+10 | 0.852463E+09 |
March | 0.104620E+10 | 0.462099E+09 | 0.584104E+09 | 0.191346E+10 | 0.591649E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.172698E+10 | 0.227828E+09 |
May | 0.528459E+09 | 39120313.74 | 0.489339E+09 | 0.164393E+10 | 49767321.51 |
June | 0.467810E+09 | 7983049.92 | 0.459827E+09 | 0.156475E+10 | 34274639.86 |
July | 0.504236E+09 | 6935355.45 | 0.497301E+09 | 0.147134E+10 | 13189636.68 |
August | 0.534888E+09 | 28567041.40 | 0.506321E+09 | 0.138671E+10 | 41059449.25 |
September | 0.693929E+09 | 0.180111E+09 | 0.513819E+09 | 0.154375E+10 | 0.121945E+09 |
October | 0.123363E+10 | 0.688853E+09 | 0.544775E+09 | 0.239690E+10 | 0.484699E+09 |
November | 0.149116E+10 | 0.985626E+09 | 0.505535E+09 | 0.252880E+10 | 0.846173E+09 |
December | 0.137518E+10 | 0.861729E+09 | 0.513456E+09 | 0.202791E+10 | 0.116386E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612117E+10 | 0.217534E+11 | 0.558270E+10 |
Minimum of Months | 0.467810E+09 | 6935355.45 | 0.459827E+09 | 0.138671E+10 | 13189636.68 |
Maximum of Months | 0.149116E+10 | 0.985626E+09 | 0.584104E+09 | 0.252880E+10 | 0.116386E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781916E+09 | 0.504922E+09 | 0.183115E+10 | 0.115579E+10 |
February | 0.110518E+10 | 0.613850E+09 | 0.491333E+09 | 0.171778E+10 | 0.852463E+09 |
March | 0.104620E+10 | 0.462100E+09 | 0.584105E+09 | 0.191346E+10 | 0.591649E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.172698E+10 | 0.227828E+09 |
May | 0.528459E+09 | 39120360.68 | 0.489339E+09 | 0.164393E+10 | 49767401.31 |
June | 0.467811E+09 | 7983059.50 | 0.459828E+09 | 0.156475E+10 | 34274671.02 |
July | 0.504237E+09 | 6935363.78 | 0.497301E+09 | 0.147134E+10 | 13189660.51 |
August | 0.534888E+09 | 28567075.68 | 0.506321E+09 | 0.138671E+10 | 41059500.87 |
September | 0.693930E+09 | 0.180111E+09 | 0.513819E+09 | 0.154375E+10 | 0.121945E+09 |
October | 0.123363E+10 | 0.688853E+09 | 0.544776E+09 | 0.239690E+10 | 0.484699E+09 |
November | 0.149116E+10 | 0.985627E+09 | 0.505536E+09 | 0.252880E+10 | 0.846173E+09 |
December | 0.137519E+10 | 0.861730E+09 | 0.513456E+09 | 0.202791E+10 | 0.116386E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612118E+10 | 0.217535E+11 | 0.558270E+10 |
Minimum of Months | 0.467811E+09 | 6935363.78 | 0.459828E+09 | 0.138671E+10 | 13189660.51 |
Maximum of Months | 0.149116E+10 | 0.985627E+09 | 0.584105E+09 | 0.252880E+10 | 0.116386E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781915E+09 | 0.504922E+09 | 0.183114E+10 | 0.115579E+10 |
February | 0.110518E+10 | 0.613849E+09 | 0.491333E+09 | 0.171777E+10 | 0.852463E+09 |
March | 0.104620E+10 | 0.462099E+09 | 0.584104E+09 | 0.191346E+10 | 0.591649E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.172698E+10 | 0.227828E+09 |
May | 0.528459E+09 | 39120313.74 | 0.489339E+09 | 0.164393E+10 | 49767321.51 |
June | 0.467810E+09 | 7983049.92 | 0.459827E+09 | 0.156475E+10 | 34274639.86 |
July | 0.504236E+09 | 6935355.45 | 0.497301E+09 | 0.147134E+10 | 13189636.68 |
August | 0.534888E+09 | 28567041.40 | 0.506321E+09 | 0.138671E+10 | 41059449.25 |
September | 0.693929E+09 | 0.180111E+09 | 0.513819E+09 | 0.154375E+10 | 0.121945E+09 |
October | 0.123363E+10 | 0.688853E+09 | 0.544775E+09 | 0.239690E+10 | 0.484699E+09 |
November | 0.149116E+10 | 0.985626E+09 | 0.505535E+09 | 0.252880E+10 | 0.846173E+09 |
December | 0.137518E+10 | 0.861729E+09 | 0.513456E+09 | 0.202791E+10 | 0.116386E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612117E+10 | 0.217534E+11 | 0.558270E+10 |
Minimum of Months | 0.467810E+09 | 6935355.45 | 0.459827E+09 | 0.138671E+10 | 13189636.68 |
Maximum of Months | 0.149116E+10 | 0.985626E+09 | 0.584104E+09 | 0.252880E+10 | 0.116386E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128679E+10 | 0.781885E+09 | 0.504902E+09 | 0.183107E+10 | 0.115575E+10 |
February | 0.110514E+10 | 0.613825E+09 | 0.491313E+09 | 0.171771E+10 | 0.852429E+09 |
March | 0.104616E+10 | 0.462081E+09 | 0.584081E+09 | 0.191338E+10 | 0.591625E+09 |
April | 0.711124E+09 | 0.200701E+09 | 0.510423E+09 | 0.172691E+10 | 0.227819E+09 |
May | 0.528438E+09 | 39118783.96 | 0.489319E+09 | 0.164386E+10 | 49765395.46 |
June | 0.467792E+09 | 7982737.74 | 0.459809E+09 | 0.156468E+10 | 34273289.60 |
July | 0.504216E+09 | 6935084.25 | 0.497281E+09 | 0.147128E+10 | 13189128.91 |
August | 0.534867E+09 | 28565924.30 | 0.506301E+09 | 0.138665E+10 | 41057845.99 |
September | 0.693902E+09 | 0.180104E+09 | 0.513798E+09 | 0.154369E+10 | 0.121940E+09 |
October | 0.123358E+10 | 0.688826E+09 | 0.544754E+09 | 0.239680E+10 | 0.484680E+09 |
November | 0.149110E+10 | 0.985587E+09 | 0.505515E+09 | 0.252870E+10 | 0.846139E+09 |
December | 0.137513E+10 | 0.861695E+09 | 0.513436E+09 | 0.202783E+10 | 0.116381E+10 |
Annual Sum or Average | 0.109782E+11 | 0.485731E+10 | 0.612093E+10 | 0.217526E+11 | 0.558247E+10 |
Minimum of Months | 0.467792E+09 | 6935084.25 | 0.459809E+09 | 0.138665E+10 | 13189128.91 |
Maximum of Months | 0.149110E+10 | 0.985587E+09 | 0.584081E+09 | 0.252870E+10 | 0.116381E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.658880E+09 | 0.256411E+09 | 0.402469E+09 | 0.746188E+09 | 0.148185E+10 |
February | 0.680533E+09 | 0.250795E+09 | 0.429738E+09 | 0.914386E+09 | 0.108744E+10 |
March | 0.977029E+09 | 0.390553E+09 | 0.586476E+09 | 0.164217E+10 | 0.763730E+09 |
April | 0.114926E+10 | 0.538959E+09 | 0.610301E+09 | 0.239499E+10 | 0.317950E+09 |
May | 0.112452E+10 | 0.476997E+09 | 0.647519E+09 | 0.276810E+10 | 72007427.44 |
June | 0.102215E+10 | 0.397030E+09 | 0.625119E+09 | 0.263969E+10 | 51383007.16 |
July | 0.783770E+09 | 0.152444E+09 | 0.631326E+09 | 0.198456E+10 | 27934320.12 |
August | 0.719810E+09 | 0.127932E+09 | 0.591878E+09 | 0.169549E+10 | 73596507.27 |
September | 0.765736E+09 | 0.224798E+09 | 0.540938E+09 | 0.163884E+10 | 0.145234E+09 |
October | 0.823580E+09 | 0.327948E+09 | 0.495632E+09 | 0.158423E+10 | 0.589984E+09 |
November | 0.721030E+09 | 0.307299E+09 | 0.413731E+09 | 0.112500E+10 | 0.107082E+10 |
December | 0.637556E+09 | 0.243115E+09 | 0.394442E+09 | 0.712583E+09 | 0.154788E+10 |
Annual Sum or Average | 0.100638E+11 | 0.369428E+10 | 0.636957E+10 | 0.198462E+11 | 0.722981E+10 |
Minimum of Months | 0.637556E+09 | 0.127932E+09 | 0.394442E+09 | 0.712583E+09 | 27934320.12 |
Maximum of Months | 0.114926E+10 | 0.538959E+09 | 0.647519E+09 | 0.276810E+10 | 0.154788E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.658880E+09 | 0.256411E+09 | 0.402469E+09 | 0.746188E+09 | 0.148185E+10 |
February | 0.680533E+09 | 0.250795E+09 | 0.429738E+09 | 0.914386E+09 | 0.108744E+10 |
March | 0.977029E+09 | 0.390553E+09 | 0.586476E+09 | 0.164217E+10 | 0.763730E+09 |
April | 0.114926E+10 | 0.538959E+09 | 0.610301E+09 | 0.239499E+10 | 0.317950E+09 |
May | 0.112452E+10 | 0.476997E+09 | 0.647519E+09 | 0.276810E+10 | 72007427.44 |
June | 0.102215E+10 | 0.397030E+09 | 0.625119E+09 | 0.263969E+10 | 51383007.16 |
July | 0.783770E+09 | 0.152444E+09 | 0.631326E+09 | 0.198456E+10 | 27934320.12 |
August | 0.719810E+09 | 0.127932E+09 | 0.591878E+09 | 0.169549E+10 | 73596507.27 |
September | 0.765736E+09 | 0.224798E+09 | 0.540938E+09 | 0.163884E+10 | 0.145234E+09 |
October | 0.823580E+09 | 0.327948E+09 | 0.495632E+09 | 0.158423E+10 | 0.589984E+09 |
November | 0.721030E+09 | 0.307299E+09 | 0.413731E+09 | 0.112500E+10 | 0.107082E+10 |
December | 0.637556E+09 | 0.243115E+09 | 0.394442E+09 | 0.712583E+09 | 0.154788E+10 |
Annual Sum or Average | 0.100638E+11 | 0.369428E+10 | 0.636957E+10 | 0.198462E+11 | 0.722981E+10 |
Minimum of Months | 0.637556E+09 | 0.127932E+09 | 0.394442E+09 | 0.712583E+09 | 27934320.12 |
Maximum of Months | 0.114926E+10 | 0.538959E+09 | 0.647519E+09 | 0.276810E+10 | 0.154788E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.658868E+09 | 0.256406E+09 | 0.402462E+09 | 0.746174E+09 | 0.148182E+10 |
February | 0.680520E+09 | 0.250790E+09 | 0.429730E+09 | 0.914369E+09 | 0.108742E+10 |
March | 0.977011E+09 | 0.390546E+09 | 0.586465E+09 | 0.164214E+10 | 0.763716E+09 |
April | 0.114924E+10 | 0.538949E+09 | 0.610290E+09 | 0.239495E+10 | 0.317944E+09 |
May | 0.112450E+10 | 0.476988E+09 | 0.647507E+09 | 0.276804E+10 | 72006111.70 |
June | 0.102213E+10 | 0.397023E+09 | 0.625107E+09 | 0.263964E+10 | 51382068.28 |
July | 0.783756E+09 | 0.152441E+09 | 0.631315E+09 | 0.198452E+10 | 27933809.70 |
August | 0.719797E+09 | 0.127930E+09 | 0.591867E+09 | 0.169546E+10 | 73595162.50 |
September | 0.765722E+09 | 0.224794E+09 | 0.540928E+09 | 0.163881E+10 | 0.145232E+09 |
October | 0.823565E+09 | 0.327942E+09 | 0.495623E+09 | 0.158420E+10 | 0.589973E+09 |
November | 0.721017E+09 | 0.307293E+09 | 0.413724E+09 | 0.112498E+10 | 0.107080E+10 |
December | 0.637545E+09 | 0.243110E+09 | 0.394434E+09 | 0.712570E+09 | 0.154786E+10 |
Annual Sum or Average | 0.100637E+11 | 0.369421E+10 | 0.636945E+10 | 0.198459E+11 | 0.722968E+10 |
Minimum of Months | 0.637545E+09 | 0.127930E+09 | 0.394434E+09 | 0.712570E+09 | 27933809.70 |
Maximum of Months | 0.114924E+10 | 0.538949E+09 | 0.647507E+09 | 0.276804E+10 | 0.154786E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.986512E+09 | 0.541846E+10 |
February | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.160104E+10 | 0.391001E+10 |
March | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.328445E+10 | 0.266239E+10 |
April | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.554195E+10 | 0.905455E+09 |
May | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.794067E+10 | 0.172650E+09 |
June | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.833907E+10 | 0.124673E+09 |
July | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.763288E+10 | 34080475.66 |
August | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.643559E+10 | 0.111366E+09 |
September | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.485538E+10 | 0.378449E+09 |
October | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.366030E+10 | 0.208811E+10 |
November | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.196096E+10 | 0.379625E+10 |
December | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.107636E+10 | 0.532093E+10 |
Annual Sum or Average | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.533152E+11 | 0.249228E+11 |
Minimum of Months | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.986512E+09 | 34080475.66 |
Maximum of Months | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.833907E+10 | 0.541846E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.216947E+10 | 0.344904E+10 |
February | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.295658E+10 | 0.254597E+10 |
March | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.502988E+10 | 0.177348E+10 |
April | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.733292E+10 | 0.660341E+09 |
May | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.865115E+10 | 0.131278E+09 |
June | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.758511E+10 | 90656075.11 |
July | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.640888E+10 | 21774741.33 |
August | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.541794E+10 | 80776503.97 |
September | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.488430E+10 | 0.280926E+09 |
October | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.485625E+10 | 0.142808E+10 |
November | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.331796E+10 | 0.249480E+10 |
December | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.226291E+10 | 0.346240E+10 |
Annual Sum or Average | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.608734E+11 | 0.164195E+11 |
Minimum of Months | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.216947E+10 | 21774741.33 |
Maximum of Months | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.865115E+10 | 0.346240E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.914145E+10 | 0.558043E+10 |
February | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.854612E+10 | 0.415301E+10 |
March | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.954189E+10 | 0.290708E+10 |
April | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.875289E+10 | 0.103851E+10 |
May | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.848460E+10 | 0.173924E+09 |
June | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.814741E+10 | 0.123469E+09 |
July | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.775092E+10 | 30181250.96 |
August | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.726767E+10 | 0.117368E+09 |
September | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.786031E+10 | 0.454567E+09 |
October | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.119702E+11 | 0.238382E+10 |
November | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.125853E+11 | 0.416967E+10 |
December | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.101481E+11 | 0.560396E+10 |
Annual Sum or Average | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.110197E+12 | 0.267360E+11 |
Minimum of Months | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.726767E+10 | 30181250.96 |
Maximum of Months | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.125853E+11 | 0.560396E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.239501E+10 | 0.385008E+10 |
February | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.286832E+10 | 0.283171E+10 |
March | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.503908E+10 | 0.199875E+10 |
April | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.734918E+10 | 0.776126E+09 |
May | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.841707E+10 | 0.173619E+09 |
June | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.810912E+10 | 0.114335E+09 |
July | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.623488E+10 | 35038111.32 |
August | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.536883E+10 | 0.104212E+09 |
September | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.500327E+10 | 0.342685E+09 |
October | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.484651E+10 | 0.158107E+10 |
November | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.351726E+10 | 0.277427E+10 |
December | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.238334E+10 | 0.378952E+10 |
Annual Sum or Average | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.615319E+11 | 0.183714E+11 |
Minimum of Months | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.238334E+10 | 35038111.32 |
Maximum of Months | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.841707E+10 | 0.385008E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.111385E+10 | 0.491990E+10 |
February | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.167803E+10 | 0.364971E+10 |
March | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.327224E+10 | 0.257814E+10 |
April | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.545629E+10 | 0.919122E+09 |
May | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.781202E+10 | 0.194012E+09 |
June | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.820545E+10 | 0.136069E+09 |
July | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.747915E+10 | 36525699.11 |
August | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.631732E+10 | 0.119778E+09 |
September | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.477882E+10 | 0.402963E+09 |
October | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.362641E+10 | 0.204973E+10 |
November | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.202399E+10 | 0.357273E+10 |
December | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.122382E+10 | 0.485146E+10 |
Annual Sum or Average | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.529874E+11 | 0.234301E+11 |
Minimum of Months | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.111385E+10 | 36525699.11 |
Maximum of Months | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.820545E+10 | 0.491990E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.232571E+10 | 0.314055E+10 |
February | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.303141E+10 | 0.240002E+10 |
March | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.503923E+10 | 0.172874E+10 |
April | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.729573E+10 | 0.667017E+09 |
May | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.858746E+10 | 0.143635E+09 |
June | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.751949E+10 | 96995910.61 |
July | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.633189E+10 | 22819243.79 |
August | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.536436E+10 | 85963135.39 |
September | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.485488E+10 | 0.294678E+09 |
October | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.485484E+10 | 0.140480E+10 |
November | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.337849E+10 | 0.237391E+10 |
December | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.241063E+10 | 0.318616E+10 |
Annual Sum or Average | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.609942E+11 | 0.155453E+11 |
Minimum of Months | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.232571E+10 | 22819243.79 |
Maximum of Months | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.858746E+10 | 0.318616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.929389E+10 | 0.513058E+10 |
February | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.859923E+10 | 0.392974E+10 |
March | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.951015E+10 | 0.283000E+10 |
April | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.866566E+10 | 0.105075E+10 |
May | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.835668E+10 | 0.194087E+09 |
June | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.801285E+10 | 0.135318E+09 |
July | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.759672E+10 | 32264347.40 |
August | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.715083E+10 | 0.126294E+09 |
September | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.778249E+10 | 0.478808E+09 |
October | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.119310E+11 | 0.234615E+10 |
November | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.126115E+11 | 0.399005E+10 |
December | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.102916E+11 | 0.521800E+10 |
Annual Sum or Average | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.109803E+12 | 0.254620E+11 |
Minimum of Months | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.715083E+10 | 32264347.40 |
Maximum of Months | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.126115E+11 | 0.521800E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.246029E+10 | 0.355772E+10 |
February | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.289406E+10 | 0.268103E+10 |
March | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.501449E+10 | 0.194517E+10 |
April | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.729279E+10 | 0.780651E+09 |
May | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.834065E+10 | 0.185425E+09 |
June | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.802723E+10 | 0.120195E+09 |
July | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.614577E+10 | 37424122.00 |
August | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.530201E+10 | 0.111379E+09 |
September | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.495520E+10 | 0.356868E+09 |
October | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.481979E+10 | 0.155411E+10 |
November | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.353437E+10 | 0.264631E+10 |
December | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.245550E+10 | 0.352329E+10 |
Annual Sum or Average | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.612422E+11 | 0.174996E+11 |
Minimum of Months | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.245550E+10 | 37424122.00 |
Maximum of Months | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.834065E+10 | 0.355772E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.19 | 2335.49 | 528.20 | 0.00 | 528.20 | 0.00 | 0.00 |
February | 593.54 | 1804.52 | 626.35 | 0.00 | 626.35 | 0.00 | 0.00 |
March | 1184.95 | 1068.77 | 754.76 | 0.00 | 754.76 | 0.00 | 0.00 |
April | 2044.15 | 413.36 | 818.97 | 2.78 | 816.19 | 0.00 | 0.00 |
May | 2848.44 | 98.99 | 907.36 | 25.46 | 881.90 | 0.00 | 0.00 |
June | 3079.41 | 71.65 | 939.26 | 34.79 | 904.47 | 0.00 | 0.00 |
July | 2687.14 | 30.37 | 926.33 | 14.67 | 911.66 | 0.00 | 0.00 |
August | 2252.28 | 83.42 | 850.40 | 2.65 | 847.75 | 0.00 | 0.00 |
September | 1778.85 | 232.05 | 757.73 | 0.05 | 757.67 | 0.00 | 0.00 |
October | 1313.34 | 851.62 | 656.44 | 0.00 | 656.44 | 0.00 | 0.00 |
November | 696.91 | 1614.32 | 556.01 | 0.00 | 556.01 | 0.00 | 0.00 |
December | 302.14 | 2309.95 | 515.27 | 0.00 | 515.27 | 0.00 | 0.00 |
Annual Sum or Average | 1593.04 | 905.77 | 736.98 | 6.73 | 730.26 | 0.00 | 0.00 |
Minimum of Months | 278.19 | 30.37 | 515.27 | 0.00 | 515.27 | 0.00 | 0.00 |
Maximum of Months | 3079.41 | 2335.49 | 939.26 | 34.79 | 911.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 768.20 | 1418.56 | 754.33 | 302.78 | 451.55 | 0.00 | 0.00 |
February | 1213.91 | 1109.34 | 916.41 | 378.34 | 538.07 | 0.00 | 0.00 |
March | 1890.28 | 668.18 | 1117.93 | 461.44 | 656.49 | 0.00 | 0.00 |
April | 2819.98 | 272.39 | 1330.04 | 620.13 | 709.91 | 0.00 | 0.00 |
May | 3191.02 | 69.91 | 1309.13 | 580.40 | 728.73 | 0.00 | 0.00 |
June | 2868.66 | 48.26 | 1065.46 | 353.52 | 711.94 | 0.00 | 0.00 |
July | 2315.70 | 17.71 | 895.49 | 189.10 | 706.39 | 0.00 | 0.00 |
August | 1957.81 | 52.16 | 806.87 | 140.41 | 666.46 | 0.00 | 0.00 |
September | 1845.95 | 160.22 | 862.05 | 240.41 | 621.65 | 0.00 | 0.00 |
October | 1811.54 | 552.64 | 942.98 | 380.90 | 562.08 | 0.00 | 0.00 |
November | 1275.94 | 997.81 | 836.09 | 358.89 | 477.20 | 0.00 | 0.00 |
December | 809.58 | 1397.25 | 729.04 | 288.85 | 440.19 | 0.00 | 0.00 |
Annual Sum or Average | 1899.65 | 561.34 | 963.55 | 357.38 | 606.18 | 0.00 | 0.00 |
Minimum of Months | 768.20 | 17.71 | 729.04 | 140.41 | 440.19 | 0.00 | 0.00 |
Maximum of Months | 3191.02 | 1418.56 | 1330.04 | 620.13 | 728.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3418.33 | 2157.60 | 2402.23 | 1459.66 | 942.57 | 0.00 | 0.00 |
February | 3550.27 | 1761.86 | 2284.17 | 1268.69 | 1015.48 | 0.00 | 0.00 |
March | 3571.99 | 1104.47 | 1953.02 | 862.63 | 1090.39 | 0.00 | 0.00 |
April | 3331.34 | 439.48 | 1371.81 | 387.17 | 984.64 | 0.00 | 0.00 |
May | 3068.84 | 92.90 | 986.51 | 73.03 | 913.48 | 0.00 | 0.00 |
June | 3018.39 | 66.12 | 902.40 | 15.40 | 887.01 | 0.00 | 0.00 |
July | 2746.66 | 24.62 | 941.29 | 12.95 | 928.35 | 0.00 | 0.00 |
August | 2588.67 | 76.65 | 998.51 | 53.33 | 945.19 | 0.00 | 0.00 |
September | 2977.89 | 235.23 | 1338.59 | 347.43 | 991.15 | 0.00 | 0.00 |
October | 4474.46 | 904.82 | 2302.90 | 1285.93 | 1016.97 | 0.00 | 0.00 |
November | 4878.05 | 1632.27 | 2876.45 | 1901.27 | 975.18 | 0.00 | 0.00 |
December | 3785.64 | 2172.65 | 2567.16 | 1608.65 | 958.51 | 0.00 | 0.00 |
Annual Sum or Average | 3448.96 | 885.12 | 1740.64 | 770.15 | 970.50 | 0.00 | 0.00 |
Minimum of Months | 2588.67 | 24.62 | 902.40 | 12.95 | 887.01 | 0.00 | 0.00 |
Maximum of Months | 4878.05 | 2172.65 | 2876.45 | 1901.27 | 1090.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 835.78 | 1659.77 | 737.99 | 287.20 | 450.79 | 0.00 | 0.00 |
February | 1133.90 | 1348.50 | 843.91 | 311.00 | 532.91 | 0.00 | 0.00 |
March | 1839.33 | 855.43 | 1094.34 | 437.44 | 656.89 | 0.00 | 0.00 |
April | 2771.96 | 368.00 | 1330.15 | 623.79 | 706.36 | 0.00 | 0.00 |
May | 3100.45 | 80.65 | 1259.53 | 534.27 | 725.26 | 0.00 | 0.00 |
June | 3055.17 | 59.47 | 1183.04 | 459.52 | 723.51 | 0.00 | 0.00 |
July | 2222.84 | 31.29 | 877.87 | 170.75 | 707.13 | 0.00 | 0.00 |
August | 1899.06 | 82.43 | 806.23 | 143.29 | 662.94 | 0.00 | 0.00 |
September | 1896.80 | 168.09 | 886.26 | 260.18 | 626.08 | 0.00 | 0.00 |
October | 1774.44 | 660.82 | 922.46 | 367.32 | 555.14 | 0.00 | 0.00 |
November | 1302.08 | 1239.37 | 834.52 | 355.67 | 478.85 | 0.00 | 0.00 |
December | 798.14 | 1733.73 | 714.10 | 272.30 | 441.80 | 0.00 | 0.00 |
Annual Sum or Average | 1887.95 | 687.76 | 957.36 | 351.43 | 605.93 | 0.00 | 0.00 |
Minimum of Months | 798.14 | 31.29 | 714.10 | 143.29 | 441.80 | 0.00 | 0.00 |
Maximum of Months | 3100.45 | 1733.73 | 1330.15 | 623.79 | 725.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 368.32 | 2023.02 | 528.19 | 0.00 | 528.19 | 0.00 | 0.00 |
February | 661.80 | 1616.24 | 626.35 | 0.00 | 626.35 | 0.00 | 0.00 |
March | 1226.27 | 994.02 | 754.75 | 0.00 | 754.75 | 0.00 | 0.00 |
April | 2138.10 | 349.33 | 818.97 | 2.78 | 816.19 | 0.00 | 0.00 |
May | 2964.71 | 64.46 | 907.36 | 25.46 | 881.90 | 0.00 | 0.00 |
June | 3217.23 | 48.10 | 939.26 | 34.79 | 904.47 | 0.00 | 0.00 |
July | 2849.79 | 12.72 | 926.33 | 14.67 | 911.66 | 0.00 | 0.00 |
August | 2402.77 | 41.58 | 850.39 | 2.65 | 847.74 | 0.00 | 0.00 |
September | 1873.22 | 146.01 | 757.72 | 0.05 | 757.67 | 0.00 | 0.00 |
October | 1366.60 | 779.61 | 656.43 | 0.00 | 656.43 | 0.00 | 0.00 |
November | 756.54 | 1464.60 | 556.01 | 0.00 | 556.01 | 0.00 | 0.00 |
December | 401.87 | 1986.61 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Annual Sum or Average | 1690.61 | 790.30 | 736.98 | 6.73 | 730.25 | 0.00 | 0.00 |
Minimum of Months | 368.32 | 12.72 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Maximum of Months | 3217.23 | 2023.02 | 939.26 | 34.79 | 911.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 809.99 | 1287.72 | 754.32 | 302.78 | 451.55 | 0.00 | 0.00 |
February | 1222.13 | 1052.40 | 916.41 | 378.34 | 538.07 | 0.00 | 0.00 |
March | 1877.94 | 662.14 | 1117.92 | 461.44 | 656.48 | 0.00 | 0.00 |
April | 2829.06 | 254.76 | 1330.04 | 620.13 | 709.91 | 0.00 | 0.00 |
May | 3229.97 | 49.01 | 1309.12 | 580.39 | 728.73 | 0.00 | 0.00 |
June | 2926.35 | 34.98 | 1065.45 | 353.52 | 711.94 | 0.00 | 0.00 |
July | 2392.80 | 8.13 | 895.49 | 189.10 | 706.38 | 0.00 | 0.00 |
August | 2022.83 | 30.16 | 806.87 | 140.41 | 666.46 | 0.00 | 0.00 |
September | 1884.38 | 108.38 | 862.05 | 240.40 | 621.64 | 0.00 | 0.00 |
October | 1813.11 | 533.18 | 942.98 | 380.90 | 562.08 | 0.00 | 0.00 |
November | 1280.08 | 962.50 | 836.09 | 358.89 | 477.20 | 0.00 | 0.00 |
December | 844.88 | 1292.71 | 729.03 | 288.85 | 440.19 | 0.00 | 0.00 |
Annual Sum or Average | 1930.28 | 520.66 | 963.55 | 357.37 | 606.18 | 0.00 | 0.00 |
Minimum of Months | 809.99 | 8.13 | 729.03 | 140.41 | 440.19 | 0.00 | 0.00 |
Maximum of Months | 3229.97 | 1292.71 | 1330.04 | 620.13 | 728.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3413.03 | 2083.49 | 2402.22 | 1459.65 | 942.57 | 0.00 | 0.00 |
February | 3532.62 | 1716.69 | 2284.16 | 1268.69 | 1015.47 | 0.00 | 0.00 |
March | 3562.53 | 1085.38 | 1953.02 | 862.63 | 1090.39 | 0.00 | 0.00 |
April | 3376.89 | 400.66 | 1371.80 | 387.17 | 984.64 | 0.00 | 0.00 |
May | 3167.79 | 64.94 | 986.51 | 73.03 | 913.48 | 0.00 | 0.00 |
June | 3143.29 | 47.63 | 902.40 | 15.40 | 887.00 | 0.00 | 0.00 |
July | 2893.86 | 11.27 | 941.29 | 12.95 | 928.34 | 0.00 | 0.00 |
August | 2713.44 | 43.82 | 998.51 | 53.33 | 945.18 | 0.00 | 0.00 |
September | 3032.53 | 175.37 | 1338.58 | 347.43 | 991.15 | 0.00 | 0.00 |
October | 4469.14 | 890.01 | 2302.89 | 1285.93 | 1016.97 | 0.00 | 0.00 |
November | 4855.43 | 1608.67 | 2876.44 | 1901.26 | 975.17 | 0.00 | 0.00 |
December | 3788.87 | 2092.28 | 2567.15 | 1608.65 | 958.50 | 0.00 | 0.00 |
Annual Sum or Average | 3494.32 | 847.79 | 1740.64 | 770.14 | 970.49 | 0.00 | 0.00 |
Minimum of Months | 2713.44 | 11.27 | 902.40 | 12.95 | 887.00 | 0.00 | 0.00 |
Maximum of Months | 4855.43 | 2092.28 | 2876.44 | 1901.26 | 1090.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 894.20 | 1437.46 | 737.99 | 287.20 | 450.79 | 0.00 | 0.00 |
February | 1185.65 | 1170.51 | 843.91 | 311.00 | 532.90 | 0.00 | 0.00 |
March | 1881.38 | 746.25 | 1094.33 | 437.44 | 656.89 | 0.00 | 0.00 |
April | 2835.33 | 299.43 | 1330.15 | 623.79 | 706.36 | 0.00 | 0.00 |
May | 3142.57 | 64.82 | 1259.53 | 534.27 | 725.26 | 0.00 | 0.00 |
June | 3128.52 | 44.11 | 1183.03 | 459.52 | 723.51 | 0.00 | 0.00 |
July | 2327.84 | 13.08 | 877.87 | 170.75 | 707.12 | 0.00 | 0.00 |
August | 2004.49 | 38.91 | 806.23 | 143.29 | 662.94 | 0.00 | 0.00 |
September | 1930.28 | 132.21 | 886.26 | 260.18 | 626.08 | 0.00 | 0.00 |
October | 1809.48 | 590.31 | 922.46 | 367.32 | 555.14 | 0.00 | 0.00 |
November | 1356.97 | 1070.32 | 834.52 | 355.67 | 478.85 | 0.00 | 0.00 |
December | 889.84 | 1414.84 | 714.10 | 272.30 | 441.80 | 0.00 | 0.00 |
Annual Sum or Average | 1951.16 | 582.55 | 957.36 | 351.43 | 605.93 | 0.00 | 0.00 |
Minimum of Months | 889.84 | 13.08 | 714.10 | 143.29 | 441.80 | 0.00 | 0.00 |
Maximum of Months | 3142.57 | 1437.46 | 1330.15 | 623.79 | 725.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.86 | 1836.88 | 528.19 | 0.00 | 528.19 | 0.00 | 0.00 |
February | 693.63 | 1508.64 | 626.35 | 0.00 | 626.35 | 0.00 | 0.00 |
March | 1221.71 | 962.57 | 754.75 | 0.00 | 754.75 | 0.00 | 0.00 |
April | 2105.05 | 354.60 | 818.97 | 2.78 | 816.19 | 0.00 | 0.00 |
May | 2916.67 | 72.44 | 907.36 | 25.46 | 881.90 | 0.00 | 0.00 |
June | 3165.68 | 52.50 | 939.26 | 34.79 | 904.47 | 0.00 | 0.00 |
July | 2792.40 | 13.64 | 926.33 | 14.67 | 911.66 | 0.00 | 0.00 |
August | 2358.62 | 44.72 | 850.39 | 2.65 | 847.74 | 0.00 | 0.00 |
September | 1843.68 | 155.46 | 757.72 | 0.05 | 757.67 | 0.00 | 0.00 |
October | 1353.95 | 765.28 | 656.43 | 0.00 | 656.43 | 0.00 | 0.00 |
November | 780.86 | 1378.37 | 556.01 | 0.00 | 556.01 | 0.00 | 0.00 |
December | 456.92 | 1811.33 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Annual Sum or Average | 1680.22 | 742.96 | 736.98 | 6.73 | 730.25 | 0.00 | 0.00 |
Minimum of Months | 415.86 | 13.64 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Maximum of Months | 3165.68 | 1836.88 | 939.26 | 34.79 | 911.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 868.32 | 1172.55 | 754.32 | 302.78 | 451.55 | 0.00 | 0.00 |
February | 1253.06 | 992.07 | 916.41 | 378.34 | 538.07 | 0.00 | 0.00 |
March | 1881.43 | 645.44 | 1117.92 | 461.44 | 656.48 | 0.00 | 0.00 |
April | 2814.71 | 257.34 | 1330.04 | 620.13 | 709.91 | 0.00 | 0.00 |
May | 3206.19 | 53.63 | 1309.12 | 580.39 | 728.73 | 0.00 | 0.00 |
June | 2901.04 | 37.42 | 1065.45 | 353.52 | 711.94 | 0.00 | 0.00 |
July | 2364.06 | 8.52 | 895.49 | 189.10 | 706.38 | 0.00 | 0.00 |
August | 2002.82 | 32.09 | 806.87 | 140.41 | 666.46 | 0.00 | 0.00 |
September | 1873.03 | 113.69 | 862.05 | 240.40 | 621.64 | 0.00 | 0.00 |
October | 1812.59 | 524.49 | 942.98 | 380.90 | 562.08 | 0.00 | 0.00 |
November | 1303.43 | 915.86 | 836.09 | 358.89 | 477.20 | 0.00 | 0.00 |
December | 900.03 | 1189.57 | 729.03 | 288.85 | 440.19 | 0.00 | 0.00 |
Annual Sum or Average | 1934.11 | 492.94 | 963.55 | 357.37 | 606.18 | 0.00 | 0.00 |
Minimum of Months | 868.32 | 8.52 | 729.03 | 140.41 | 440.19 | 0.00 | 0.00 |
Maximum of Months | 3206.19 | 1189.57 | 1330.04 | 620.13 | 728.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3469.94 | 1915.54 | 2402.22 | 1459.65 | 942.57 | 0.00 | 0.00 |
February | 3554.58 | 1624.40 | 2284.16 | 1268.69 | 1015.47 | 0.00 | 0.00 |
March | 3550.68 | 1056.60 | 1953.02 | 862.63 | 1090.39 | 0.00 | 0.00 |
April | 3343.23 | 405.38 | 1371.80 | 387.17 | 984.64 | 0.00 | 0.00 |
May | 3120.03 | 72.46 | 986.51 | 73.03 | 913.48 | 0.00 | 0.00 |
June | 3091.38 | 52.21 | 902.40 | 15.40 | 887.00 | 0.00 | 0.00 |
July | 2836.29 | 12.05 | 941.29 | 12.95 | 928.34 | 0.00 | 0.00 |
August | 2669.81 | 47.15 | 998.51 | 53.33 | 945.18 | 0.00 | 0.00 |
September | 3002.50 | 184.73 | 1338.58 | 347.43 | 991.15 | 0.00 | 0.00 |
October | 4454.53 | 875.95 | 2302.89 | 1285.93 | 1016.97 | 0.00 | 0.00 |
November | 4865.54 | 1539.37 | 2876.44 | 1901.26 | 975.17 | 0.00 | 0.00 |
December | 3842.43 | 1948.18 | 2567.15 | 1608.65 | 958.50 | 0.00 | 0.00 |
Annual Sum or Average | 3481.82 | 807.40 | 1740.64 | 770.14 | 970.49 | 0.00 | 0.00 |
Minimum of Months | 2669.81 | 12.05 | 902.40 | 12.95 | 887.00 | 0.00 | 0.00 |
Maximum of Months | 4865.54 | 1948.18 | 2876.44 | 1901.26 | 1090.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 918.57 | 1328.30 | 737.99 | 287.20 | 450.79 | 0.00 | 0.00 |
February | 1196.29 | 1108.23 | 843.91 | 311.00 | 532.90 | 0.00 | 0.00 |
March | 1872.20 | 726.24 | 1094.33 | 437.44 | 656.89 | 0.00 | 0.00 |
April | 2813.58 | 301.18 | 1330.15 | 623.79 | 706.36 | 0.00 | 0.00 |
May | 3114.04 | 69.23 | 1259.53 | 534.27 | 725.26 | 0.00 | 0.00 |
June | 3096.92 | 46.37 | 1183.03 | 459.52 | 723.51 | 0.00 | 0.00 |
July | 2294.57 | 13.97 | 877.87 | 170.75 | 707.12 | 0.00 | 0.00 |
August | 1979.54 | 41.58 | 806.23 | 143.29 | 662.94 | 0.00 | 0.00 |
September | 1911.73 | 137.68 | 886.26 | 260.18 | 626.08 | 0.00 | 0.00 |
October | 1799.50 | 580.24 | 922.46 | 367.32 | 555.14 | 0.00 | 0.00 |
November | 1363.57 | 1020.95 | 834.52 | 355.67 | 478.85 | 0.00 | 0.00 |
December | 916.78 | 1315.44 | 714.10 | 272.30 | 441.80 | 0.00 | 0.00 |
Annual Sum or Average | 1941.98 | 554.91 | 957.36 | 351.43 | 605.93 | 0.00 | 0.00 |
Minimum of Months | 916.78 | 13.97 | 714.10 | 143.29 | 441.80 | 0.00 | 0.00 |
Maximum of Months | 3114.04 | 1328.30 | 1330.15 | 623.79 | 725.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745091E+09 | 0.625537E+10 | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.00 | 0.00 |
February | 0.143590E+10 | 0.436549E+10 | 0.151527E+10 | 0.00 | 0.151527E+10 | 0.00 | 0.00 |
March | 0.317378E+10 | 0.286259E+10 | 0.202154E+10 | 0.00 | 0.202154E+10 | 0.00 | 0.00 |
April | 0.529843E+10 | 0.107143E+10 | 0.212277E+10 | 7199036.12 | 0.211557E+10 | 0.00 | 0.00 |
May | 0.762926E+10 | 0.265137E+09 | 0.243028E+10 | 68198088.39 | 0.236208E+10 | 0.00 | 0.00 |
June | 0.798184E+10 | 0.185709E+09 | 0.243457E+10 | 90176991.69 | 0.234439E+10 | 0.00 | 0.00 |
July | 0.719724E+10 | 81353234.00 | 0.248108E+10 | 39289384.90 | 0.244179E+10 | 0.00 | 0.00 |
August | 0.603251E+10 | 0.223432E+09 | 0.227770E+10 | 7098576.44 | 0.227060E+10 | 0.00 | 0.00 |
September | 0.461077E+10 | 0.601485E+09 | 0.196403E+10 | 137910.00 | 0.196389E+10 | 0.00 | 0.00 |
October | 0.351766E+10 | 0.228098E+10 | 0.175820E+10 | 0.00 | 0.175820E+10 | 0.00 | 0.00 |
November | 0.180639E+10 | 0.418432E+10 | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
December | 0.809246E+09 | 0.618697E+10 | 0.138009E+10 | 0.00 | 0.138009E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.502381E+11 | 0.285643E+11 | 0.232414E+11 | 0.212100E+09 | 0.230293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.745091E+09 | 81353234.00 | 0.138009E+10 | 0.00 | 0.138009E+10 | 0.00 | 0.00 |
Maximum of Months | 0.798184E+10 | 0.625537E+10 | 0.248108E+10 | 90176991.69 | 0.244179E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205756E+10 | 0.379948E+10 | 0.202039E+10 | 0.810957E+09 | 0.120943E+10 | 0.00 | 0.00 |
February | 0.293670E+10 | 0.268372E+10 | 0.221699E+10 | 0.915275E+09 | 0.130171E+10 | 0.00 | 0.00 |
March | 0.506294E+10 | 0.178965E+10 | 0.299425E+10 | 0.123592E+10 | 0.175833E+10 | 0.00 | 0.00 |
April | 0.730939E+10 | 0.706028E+09 | 0.344747E+10 | 0.160739E+10 | 0.184008E+10 | 0.00 | 0.00 |
May | 0.854682E+10 | 0.187248E+09 | 0.350637E+10 | 0.155453E+10 | 0.195183E+10 | 0.00 | 0.00 |
June | 0.743557E+10 | 0.125085E+09 | 0.276167E+10 | 0.916318E+09 | 0.184535E+10 | 0.00 | 0.00 |
July | 0.620237E+10 | 47429670.79 | 0.239848E+10 | 0.506495E+09 | 0.189198E+10 | 0.00 | 0.00 |
August | 0.524379E+10 | 0.139714E+09 | 0.216113E+10 | 0.376087E+09 | 0.178504E+10 | 0.00 | 0.00 |
September | 0.478469E+10 | 0.415293E+09 | 0.223444E+10 | 0.623130E+09 | 0.161131E+10 | 0.00 | 0.00 |
October | 0.485203E+10 | 0.148018E+10 | 0.252569E+10 | 0.102021E+10 | 0.150548E+10 | 0.00 | 0.00 |
November | 0.330724E+10 | 0.258631E+10 | 0.216715E+10 | 0.930239E+09 | 0.123691E+10 | 0.00 | 0.00 |
December | 0.216837E+10 | 0.374238E+10 | 0.195265E+10 | 0.773652E+09 | 0.117900E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.599075E+11 | 0.177025E+11 | 0.303867E+11 | 0.112702E+11 | 0.191165E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205756E+10 | 47429670.79 | 0.195265E+10 | 0.376087E+09 | 0.117900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.854682E+10 | 0.379948E+10 | 0.350637E+10 | 0.160739E+10 | 0.195183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915565E+10 | 0.577891E+10 | 0.643414E+10 | 0.390955E+10 | 0.252459E+10 | 0.00 | 0.00 |
February | 0.858881E+10 | 0.426228E+10 | 0.552587E+10 | 0.306922E+10 | 0.245665E+10 | 0.00 | 0.00 |
March | 0.956722E+10 | 0.295822E+10 | 0.523098E+10 | 0.231048E+10 | 0.292050E+10 | 0.00 | 0.00 |
April | 0.863483E+10 | 0.113913E+10 | 0.355573E+10 | 0.100354E+10 | 0.255219E+10 | 0.00 | 0.00 |
May | 0.821958E+10 | 0.248835E+09 | 0.264228E+10 | 0.195600E+09 | 0.244667E+10 | 0.00 | 0.00 |
June | 0.782367E+10 | 0.171372E+09 | 0.233903E+10 | 39914956.58 | 0.229912E+10 | 0.00 | 0.00 |
July | 0.735666E+10 | 65947723.29 | 0.252116E+10 | 34676522.71 | 0.248649E+10 | 0.00 | 0.00 |
August | 0.693349E+10 | 0.205296E+09 | 0.267442E+10 | 0.142834E+09 | 0.253159E+10 | 0.00 | 0.00 |
September | 0.771870E+10 | 0.609721E+09 | 0.346962E+10 | 0.900548E+09 | 0.256907E+10 | 0.00 | 0.00 |
October | 0.119844E+11 | 0.242348E+10 | 0.616809E+10 | 0.344424E+10 | 0.272386E+10 | 0.00 | 0.00 |
November | 0.126439E+11 | 0.423083E+10 | 0.745575E+10 | 0.492809E+10 | 0.252766E+10 | 0.00 | 0.00 |
December | 0.101395E+11 | 0.581924E+10 | 0.687587E+10 | 0.430861E+10 | 0.256726E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108766E+12 | 0.279133E+11 | 0.548929E+11 | 0.242873E+11 | 0.306056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.693349E+10 | 65947723.29 | 0.233903E+10 | 34676522.71 | 0.229912E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126439E+11 | 0.581924E+10 | 0.745575E+10 | 0.492809E+10 | 0.292050E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223855E+10 | 0.444552E+10 | 0.197663E+10 | 0.769228E+09 | 0.120740E+10 | 0.00 | 0.00 |
February | 0.274314E+10 | 0.326229E+10 | 0.204159E+10 | 0.752379E+09 | 0.128921E+10 | 0.00 | 0.00 |
March | 0.492647E+10 | 0.229118E+10 | 0.293107E+10 | 0.117165E+10 | 0.175942E+10 | 0.00 | 0.00 |
April | 0.718492E+10 | 0.953844E+09 | 0.344776E+10 | 0.161687E+10 | 0.183089E+10 | 0.00 | 0.00 |
May | 0.830424E+10 | 0.216021E+09 | 0.337353E+10 | 0.143098E+10 | 0.194255E+10 | 0.00 | 0.00 |
June | 0.791901E+10 | 0.154148E+09 | 0.306643E+10 | 0.119108E+10 | 0.187535E+10 | 0.00 | 0.00 |
July | 0.595365E+10 | 83802449.94 | 0.235130E+10 | 0.457328E+09 | 0.189397E+10 | 0.00 | 0.00 |
August | 0.508644E+10 | 0.220788E+09 | 0.215942E+10 | 0.383794E+09 | 0.177562E+10 | 0.00 | 0.00 |
September | 0.491650E+10 | 0.435700E+09 | 0.229719E+10 | 0.674391E+09 | 0.162280E+10 | 0.00 | 0.00 |
October | 0.475267E+10 | 0.176994E+10 | 0.247073E+10 | 0.983839E+09 | 0.148689E+10 | 0.00 | 0.00 |
November | 0.337498E+10 | 0.321245E+10 | 0.216308E+10 | 0.921890E+09 | 0.124119E+10 | 0.00 | 0.00 |
December | 0.213774E+10 | 0.464362E+10 | 0.191266E+10 | 0.729340E+09 | 0.118332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.595383E+11 | 0.216893E+11 | 0.301914E+11 | 0.110828E+11 | 0.191086E+11 | 0.00 | 0.00 |
Minimum of Months | 0.213774E+10 | 83802449.94 | 0.191266E+10 | 0.383794E+09 | 0.118332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.830424E+10 | 0.464362E+10 | 0.344776E+10 | 0.161687E+10 | 0.194255E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.986512E+09 | 0.541846E+10 | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.00 | 0.00 |
February | 0.160104E+10 | 0.391001E+10 | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.00 | 0.00 |
March | 0.328445E+10 | 0.266239E+10 | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.00 | 0.00 |
April | 0.554195E+10 | 0.905455E+09 | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.00 | 0.00 |
May | 0.794067E+10 | 0.172650E+09 | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.00 | 0.00 |
June | 0.833907E+10 | 0.124673E+09 | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.00 | 0.00 |
July | 0.763288E+10 | 34080475.66 | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.00 | 0.00 |
August | 0.643559E+10 | 0.111366E+09 | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.00 | 0.00 |
September | 0.485538E+10 | 0.378449E+09 | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.00 | 0.00 |
October | 0.366030E+10 | 0.208811E+10 | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.00 | 0.00 |
November | 0.196096E+10 | 0.379625E+10 | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
December | 0.107636E+10 | 0.532093E+10 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.533152E+11 | 0.249228E+11 | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.00 | 0.00 |
Minimum of Months | 0.986512E+09 | 34080475.66 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833907E+10 | 0.541846E+10 | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216947E+10 | 0.344904E+10 | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.00 | 0.00 |
February | 0.295658E+10 | 0.254597E+10 | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.00 | 0.00 |
March | 0.502988E+10 | 0.177348E+10 | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.00 | 0.00 |
April | 0.733292E+10 | 0.660341E+09 | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.00 | 0.00 |
May | 0.865115E+10 | 0.131278E+09 | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.00 | 0.00 |
June | 0.758511E+10 | 90656075.11 | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.00 | 0.00 |
July | 0.640888E+10 | 21774741.33 | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.00 | 0.00 |
August | 0.541794E+10 | 80776503.97 | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.00 | 0.00 |
September | 0.488430E+10 | 0.280926E+09 | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.00 | 0.00 |
October | 0.485625E+10 | 0.142808E+10 | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.00 | 0.00 |
November | 0.331796E+10 | 0.249480E+10 | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.00 | 0.00 |
December | 0.226291E+10 | 0.346240E+10 | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.608734E+11 | 0.164195E+11 | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216947E+10 | 21774741.33 | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865115E+10 | 0.346240E+10 | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.914145E+10 | 0.558043E+10 | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.00 | 0.00 |
February | 0.854612E+10 | 0.415301E+10 | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.00 | 0.00 |
March | 0.954189E+10 | 0.290708E+10 | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.00 | 0.00 |
April | 0.875289E+10 | 0.103851E+10 | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.00 | 0.00 |
May | 0.848460E+10 | 0.173924E+09 | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.00 | 0.00 |
June | 0.814741E+10 | 0.123469E+09 | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.00 | 0.00 |
July | 0.775092E+10 | 30181250.96 | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.00 | 0.00 |
August | 0.726767E+10 | 0.117368E+09 | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.00 | 0.00 |
September | 0.786031E+10 | 0.454567E+09 | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.00 | 0.00 |
October | 0.119702E+11 | 0.238382E+10 | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.00 | 0.00 |
November | 0.125853E+11 | 0.416967E+10 | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.00 | 0.00 |
December | 0.101481E+11 | 0.560396E+10 | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110197E+12 | 0.267360E+11 | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.726767E+10 | 30181250.96 | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125853E+11 | 0.560396E+10 | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.239501E+10 | 0.385008E+10 | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.00 | 0.00 |
February | 0.286832E+10 | 0.283171E+10 | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.00 | 0.00 |
March | 0.503908E+10 | 0.199875E+10 | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.00 | 0.00 |
April | 0.734918E+10 | 0.776126E+09 | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.00 | 0.00 |
May | 0.841707E+10 | 0.173619E+09 | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.00 | 0.00 |
June | 0.810912E+10 | 0.114335E+09 | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.00 | 0.00 |
July | 0.623488E+10 | 35038111.32 | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.00 | 0.00 |
August | 0.536883E+10 | 0.104212E+09 | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.00 | 0.00 |
September | 0.500327E+10 | 0.342685E+09 | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.00 | 0.00 |
October | 0.484651E+10 | 0.158107E+10 | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.00 | 0.00 |
November | 0.351726E+10 | 0.277427E+10 | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.00 | 0.00 |
December | 0.238334E+10 | 0.378952E+10 | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.615319E+11 | 0.183714E+11 | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238334E+10 | 35038111.32 | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841707E+10 | 0.385008E+10 | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111385E+10 | 0.491990E+10 | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.00 | 0.00 |
February | 0.167803E+10 | 0.364971E+10 | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.00 | 0.00 |
March | 0.327224E+10 | 0.257814E+10 | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.00 | 0.00 |
April | 0.545629E+10 | 0.919122E+09 | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.00 | 0.00 |
May | 0.781202E+10 | 0.194012E+09 | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.00 | 0.00 |
June | 0.820545E+10 | 0.136069E+09 | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.00 | 0.00 |
July | 0.747915E+10 | 36525699.11 | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.00 | 0.00 |
August | 0.631732E+10 | 0.119778E+09 | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.00 | 0.00 |
September | 0.477882E+10 | 0.402963E+09 | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.00 | 0.00 |
October | 0.362641E+10 | 0.204973E+10 | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.00 | 0.00 |
November | 0.202399E+10 | 0.357273E+10 | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
December | 0.122382E+10 | 0.485146E+10 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.529874E+11 | 0.234301E+11 | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111385E+10 | 36525699.11 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.820545E+10 | 0.491990E+10 | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232571E+10 | 0.314055E+10 | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.00 | 0.00 |
February | 0.303141E+10 | 0.240002E+10 | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.00 | 0.00 |
March | 0.503923E+10 | 0.172874E+10 | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.00 | 0.00 |
April | 0.729573E+10 | 0.667017E+09 | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.00 | 0.00 |
May | 0.858746E+10 | 0.143635E+09 | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.00 | 0.00 |
June | 0.751949E+10 | 96995910.61 | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.00 | 0.00 |
July | 0.633189E+10 | 22819243.79 | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.00 | 0.00 |
August | 0.536436E+10 | 85963135.39 | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.00 | 0.00 |
September | 0.485488E+10 | 0.294678E+09 | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.00 | 0.00 |
October | 0.485484E+10 | 0.140480E+10 | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.00 | 0.00 |
November | 0.337849E+10 | 0.237391E+10 | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.00 | 0.00 |
December | 0.241063E+10 | 0.318616E+10 | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.609942E+11 | 0.155453E+11 | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232571E+10 | 22819243.79 | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.858746E+10 | 0.318616E+10 | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.929389E+10 | 0.513058E+10 | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.00 | 0.00 |
February | 0.859923E+10 | 0.392974E+10 | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.00 | 0.00 |
March | 0.951015E+10 | 0.283000E+10 | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.00 | 0.00 |
April | 0.866566E+10 | 0.105075E+10 | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.00 | 0.00 |
May | 0.835668E+10 | 0.194087E+09 | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.00 | 0.00 |
June | 0.801285E+10 | 0.135318E+09 | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.00 | 0.00 |
July | 0.759672E+10 | 32264347.40 | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.00 | 0.00 |
August | 0.715083E+10 | 0.126294E+09 | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.00 | 0.00 |
September | 0.778249E+10 | 0.478808E+09 | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.00 | 0.00 |
October | 0.119310E+11 | 0.234615E+10 | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.00 | 0.00 |
November | 0.126115E+11 | 0.399005E+10 | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.00 | 0.00 |
December | 0.102916E+11 | 0.521800E+10 | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109803E+12 | 0.254620E+11 | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.715083E+10 | 32264347.40 | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126115E+11 | 0.521800E+10 | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246029E+10 | 0.355772E+10 | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.00 | 0.00 |
February | 0.289406E+10 | 0.268103E+10 | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.00 | 0.00 |
March | 0.501449E+10 | 0.194517E+10 | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.00 | 0.00 |
April | 0.729279E+10 | 0.780651E+09 | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.00 | 0.00 |
May | 0.834065E+10 | 0.185425E+09 | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.00 | 0.00 |
June | 0.802723E+10 | 0.120195E+09 | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.00 | 0.00 |
July | 0.614577E+10 | 37424122.00 | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.00 | 0.00 |
August | 0.530201E+10 | 0.111379E+09 | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.00 | 0.00 |
September | 0.495520E+10 | 0.356868E+09 | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.00 | 0.00 |
October | 0.481979E+10 | 0.155411E+10 | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.00 | 0.00 |
November | 0.353437E+10 | 0.264631E+10 | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.00 | 0.00 |
December | 0.245550E+10 | 0.352329E+10 | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.612422E+11 | 0.174996E+11 | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245550E+10 | 37424122.00 | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.834065E+10 | 0.355772E+10 | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.315338E+11 | -0.310899E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443893921.9 | 60.05 | 0.00 | 0.00 |
February | 0.280714E+11 | -0.276703E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401108757.3 | 60.05 | 0.00 | 0.00 |
March | 0.308543E+11 | -0.304178E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -436571053.2 | 60.05 | 0.00 | 0.00 |
April | 0.252212E+11 | -0.248333E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -387883780.3 | 60.05 | 0.00 | 0.00 |
May | 0.239131E+11 | -0.235308E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -382300017.9 | 60.05 | 0.00 | 0.00 |
June | 0.213604E+11 | -0.209954E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -364987215.2 | 60.05 | 0.00 | 0.00 |
July | 0.194454E+11 | -0.190738E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -371661818.1 | 60.05 | 0.00 | 0.00 |
August | 0.219653E+11 | -0.215975E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -367808746.9 | 60.05 | 0.00 | 0.00 |
September | 0.219603E+11 | -0.216007E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -359583708.7 | 60.05 | 0.00 | 0.00 |
October | 0.255466E+11 | -0.251288E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -417794791.2 | 60.05 | 0.00 | 0.00 |
November | 0.279197E+11 | -0.274922E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427459379.1 | 60.05 | 0.00 | 0.00 |
December | 0.299328E+11 | -0.294903E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442428300.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.307724E+12 | -0.302921E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.480348E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.194454E+11 | -0.310899E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -443893921.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.315338E+11 | -0.190738E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -359583708.7 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5587.00 | 35.39 | 298.33 | 287.33 | 1241.27 | 25.72 | 289.83 | 266.00 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3361.53 | 29.30 | 203.33 | 271.17 | 1099.85 | 21.65 | 213.67 | 243.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1746.34 | 20.45 | 79.17 | 323.67 | 946.86 | 21.50 | 247.50 | 291.33 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1185.67 | 18.87 | 9.67 | 328.83 | 700.32 | 20.16 | 180.17 | 296.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1006.26 | 18.69 | 0.00 | 349.83 | 590.02 | 20.07 | 144.67 | 309.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 995.79 | 18.34 | 0.00 | 334.33 | 570.38 | 19.69 | 136.17 | 292.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1113.23 | 18.84 | 0.33 | 333.17 | 578.71 | 20.10 | 146.33 | 281.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1250.72 | 18.83 | 18.50 | 321.67 | 627.42 | 20.07 | 172.33 | 271.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 1523.47 | 19.57 | 66.67 | 302.17 | 788.20 | 20.88 | 210.50 | 263.00 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2574.74 | 21.53 | 109.17 | 305.33 | 1062.27 | 21.12 | 226.50 | 278.33 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 7555.70 | 36.61 | 310.50 | 287.83 | 1296.96 | 23.62 | 260.83 | 265.00 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5899.83 | 36.71 | 308.83 | 286.00 | 1459.62 | 27.89 | 308.67 | 278.67 |
Annual Sum or Average | 4237.50 | 0.52 | 2656.38 | 23.86 | 1404.50 | 3731.33 | 889.30 | 21.71 | 2537.17 | 3336.33 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 995.79 | 18.34 | 0.00 | 271.17 | 570.38 | 19.69 | 136.17 | 243.83 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 7555.70 | 36.71 | 310.50 | 349.83 | 1459.62 | 27.89 | 308.67 | 309.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1654.05 | 23.82 | 107.17 | 267.67 | 872.87 | 23.89 | 165.83 | 223.67 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2049.04 | 23.96 | 100.33 | 257.50 | 1081.03 | 24.07 | 154.83 | 219.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 1971.01 | 23.44 | 101.50 | 319.17 | 1019.94 | 23.69 | 165.17 | 287.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2387.77 | 22.87 | 110.33 | 328.00 | 1256.65 | 23.21 | 118.00 | 300.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2476.59 | 23.26 | 128.50 | 357.33 | 965.45 | 22.42 | 123.50 | 323.50 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 1978.26 | 21.99 | 108.00 | 337.83 | 831.36 | 21.50 | 124.83 | 299.67 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1637.28 | 21.95 | 102.00 | 337.50 | 731.31 | 21.54 | 125.50 | 286.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1499.77 | 21.42 | 98.33 | 322.83 | 692.23 | 21.07 | 133.50 | 267.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1674.99 | 22.42 | 90.50 | 298.00 | 848.32 | 22.83 | 152.17 | 257.67 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1842.26 | 23.15 | 102.67 | 297.50 | 932.82 | 23.23 | 161.67 | 265.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:10 | 1663.43 | 23.57 | 94.83 | 268.67 | 846.23 | 23.55 | 154.50 | 238.83 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1729.72 | 24.45 | 112.50 | 262.33 | 919.78 | 24.44 | 169.17 | 226.83 |
Annual Sum or Average | 4237.50 | 0.52 | 1892.20 | 22.97 | 1256.67 | 3654.33 | 915.77 | 22.88 | 1748.67 | 3196.67 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1499.77 | 21.42 | 90.50 | 257.50 | 692.23 | 21.07 | 118.00 | 219.83 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2476.59 | 24.45 | 128.50 | 357.33 | 1256.65 | 24.44 | 169.17 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:20 | 554.70 | 16.48 | 0.00 | 248.17 | 340.77 | 18.00 | 0.00 | 167.50 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 639.90 | 17.35 | 0.00 | 249.00 | 392.01 | 18.81 | 0.00 | 183.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:20 | 756.72 | 18.45 | 0.00 | 313.67 | 462.82 | 19.83 | 0.33 | 262.83 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 817.80 | 18.47 | 0.00 | 332.67 | 508.17 | 19.78 | 48.83 | 298.50 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 970.86 | 19.17 | 6.17 | 365.50 | 570.02 | 20.49 | 149.67 | 336.33 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1072.99 | 20.78 | 64.00 | 348.33 | 599.84 | 20.33 | 170.67 | 311.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1086.46 | 20.41 | 40.33 | 345.00 | 568.04 | 20.99 | 144.17 | 297.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 971.60 | 18.52 | 0.00 | 325.67 | 507.87 | 19.72 | 90.17 | 271.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 848.14 | 18.39 | 0.00 | 299.17 | 471.66 | 19.64 | 35.33 | 245.17 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:40 | 671.39 | 17.30 | 0.00 | 288.50 | 420.34 | 18.78 | 0.00 | 235.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:09 | 572.50 | 16.88 | 0.00 | 252.50 | 371.70 | 18.55 | 0.00 | 191.67 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:39 | 546.82 | 16.57 | 0.00 | 243.33 | 338.97 | 18.16 | 0.00 | 165.00 |
Annual Sum or Average | 4237.50 | 0.52 | 807.41 | 18.33 | 110.50 | 3611.50 | 469.96 | 19.50 | 639.17 | 2965.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 546.82 | 16.48 | 0.00 | 243.33 | 338.97 | 18.00 | 0.00 | 165.00 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1086.46 | 20.78 | 64.00 | 365.50 | 599.84 | 20.99 | 170.67 | 336.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:20 | 1657.27 | 23.60 | 104.33 | 266.50 | 860.01 | 23.62 | 165.83 | 223.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-09:09 | 1962.25 | 23.60 | 103.67 | 262.00 | 788.60 | 22.39 | 150.00 | 223.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:30 | 1923.06 | 23.35 | 101.17 | 319.83 | 990.90 | 23.59 | 174.83 | 288.67 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:00 | 2188.74 | 21.13 | 84.50 | 332.00 | 1142.84 | 21.60 | 90.50 | 302.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2100.92 | 17.39 | 0.00 | 352.00 | 1089.87 | 19.52 | 80.67 | 322.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2089.78 | 17.41 | 0.00 | 337.67 | 865.07 | 19.36 | 87.83 | 302.50 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:30 | 1585.75 | 18.11 | 3.67 | 336.17 | 722.72 | 19.68 | 97.00 | 287.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1479.98 | 19.38 | 54.17 | 321.83 | 736.93 | 19.55 | 97.17 | 272.50 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:09 | 1644.12 | 21.62 | 81.00 | 301.33 | 827.96 | 21.98 | 150.83 | 257.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:00 | 1954.50 | 23.25 | 105.00 | 293.67 | 986.71 | 23.34 | 149.83 | 263.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1713.61 | 23.69 | 97.17 | 270.00 | 862.85 | 23.66 | 155.83 | 240.33 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:39 | 1510.17 | 23.76 | 101.00 | 268.83 | 781.18 | 23.73 | 170.00 | 231.67 |
Annual Sum or Average | 4237.50 | 0.52 | 1826.18 | 21.16 | 835.67 | 3661.83 | 892.98 | 21.71 | 1570.33 | 3215.33 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1479.98 | 17.39 | 0.00 | 262.00 | 722.72 | 19.36 | 80.67 | 223.17 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2188.74 | 23.76 | 105.00 | 352.00 | 1142.84 | 23.73 | 174.83 | 322.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5621.98 | 34.87 | 296.67 | 287.33 | 1323.48 | 21.54 | 84.50 | 268.33 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3400.83 | 26.56 | 195.33 | 271.33 | 1177.88 | 16.80 | 0.00 | 246.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1780.18 | 14.28 | 7.50 | 323.67 | 1013.47 | 17.40 | 0.00 | 294.67 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 1213.00 | 13.17 | 0.00 | 329.17 | 749.46 | 16.56 | 0.00 | 299.67 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1025.74 | 12.79 | 0.00 | 350.17 | 629.34 | 16.24 | 0.00 | 315.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1012.82 | 12.35 | 0.00 | 334.67 | 607.46 | 15.73 | 0.00 | 296.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1125.18 | 12.41 | 0.00 | 333.83 | 614.53 | 15.74 | 0.00 | 287.00 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1260.65 | 12.37 | 0.00 | 322.00 | 665.37 | 15.63 | 0.00 | 277.00 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:19 | 1541.26 | 13.13 | 0.00 | 302.67 | 838.23 | 16.51 | 0.00 | 267.50 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2623.77 | 15.66 | 42.67 | 307.67 | 1141.33 | 16.87 | 10.00 | 282.00 |
November | 317.83 | 0.50 | 0.48 | 01-NOV-07:19 | 7610.53 | 36.19 | 310.33 | 288.00 | 1400.77 | 20.73 | 74.33 | 272.67 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5935.37 | 36.29 | 308.00 | 286.50 | 1547.51 | 24.15 | 123.17 | 279.67 |
Annual Sum or Average | 4237.50 | 0.51 | 2684.78 | 19.26 | 1160.50 | 3737.00 | 949.80 | 17.66 | 292.00 | 3386.67 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1012.82 | 12.35 | 0.00 | 271.33 | 607.46 | 15.63 | 0.00 | 246.83 | |
Maximum of Months | 406.00 | 0.52 | 0.48 | 7610.53 | 36.29 | 310.33 | 350.17 | 1547.51 | 24.15 | 123.17 | 315.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1680.21 | 21.38 | 106.83 | 269.00 | 910.14 | 22.03 | 77.33 | 228.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2085.42 | 21.32 | 100.00 | 258.67 | 1124.62 | 22.06 | 74.00 | 226.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 2019.42 | 20.47 | 101.50 | 320.17 | 1070.72 | 21.36 | 70.67 | 291.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2415.04 | 19.97 | 110.17 | 328.83 | 1311.20 | 20.89 | 81.17 | 303.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2495.02 | 19.31 | 117.00 | 357.50 | 1020.01 | 19.76 | 66.50 | 327.33 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 2006.53 | 18.92 | 107.17 | 338.83 | 878.60 | 18.86 | 51.33 | 304.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1658.37 | 18.33 | 96.33 | 338.83 | 776.08 | 18.92 | 48.17 | 294.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1520.80 | 18.31 | 97.67 | 324.00 | 788.56 | 19.50 | 69.00 | 274.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1707.75 | 19.41 | 90.00 | 298.50 | 889.48 | 20.50 | 64.50 | 263.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1881.16 | 20.26 | 100.83 | 298.17 | 978.22 | 21.14 | 72.17 | 268.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1687.61 | 20.02 | 87.83 | 269.67 | 888.77 | 21.58 | 64.83 | 242.50 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1754.95 | 22.08 | 112.50 | 263.83 | 956.81 | 22.70 | 81.67 | 231.83 |
Annual Sum or Average | 4237.50 | 0.52 | 1921.01 | 19.90 | 1227.83 | 3666.00 | 966.00 | 20.68 | 821.33 | 3255.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1520.80 | 18.31 | 87.83 | 258.67 | 776.08 | 18.86 | 48.17 | 226.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2495.02 | 22.08 | 117.00 | 357.50 | 1311.20 | 22.70 | 81.67 | 327.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:09 | 563.11 | 10.87 | 0.00 | 248.83 | 362.60 | 14.39 | 0.00 | 179.50 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 650.48 | 11.78 | 0.00 | 249.17 | 417.37 | 15.28 | 0.00 | 193.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:09 | 770.61 | 13.10 | 0.00 | 314.67 | 493.14 | 16.57 | 0.00 | 270.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 835.40 | 13.26 | 0.00 | 332.83 | 542.33 | 16.67 | 0.00 | 304.83 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 990.58 | 13.32 | 1.17 | 365.83 | 607.96 | 16.86 | 1.17 | 339.33 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1092.44 | 15.58 | 39.17 | 348.33 | 641.54 | 18.75 | 40.50 | 317.50 |
July | 379.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1100.51 | 14.66 | 29.17 | 345.17 | 603.84 | 17.82 | 29.67 | 303.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 983.79 | 12.28 | 0.00 | 325.67 | 539.16 | 15.55 | 0.00 | 279.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 860.48 | 12.56 | 0.00 | 299.33 | 501.37 | 15.88 | 0.00 | 252.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:30 | 683.34 | 11.88 | 0.00 | 289.00 | 447.84 | 15.32 | 0.00 | 242.00 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:09 | 582.02 | 11.29 | 0.00 | 253.33 | 395.97 | 14.95 | 0.00 | 203.33 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:30 | 554.92 | 10.92 | 0.00 | 244.50 | 360.64 | 14.52 | 0.00 | 178.00 |
Annual Sum or Average | 4237.50 | 0.52 | 820.86 | 12.73 | 69.50 | 3616.67 | 500.59 | 16.14 | 71.33 | 3062.67 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 554.92 | 10.87 | 0.00 | 244.50 | 360.64 | 14.39 | 0.00 | 178.00 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1100.51 | 15.58 | 39.17 | 365.83 | 641.54 | 18.75 | 40.50 | 339.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:09 | 1683.35 | 21.17 | 104.00 | 267.50 | 897.15 | 21.75 | 74.33 | 227.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:00 | 1994.86 | 21.06 | 103.17 | 263.00 | 829.67 | 20.10 | 48.00 | 228.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1969.55 | 20.39 | 101.17 | 320.00 | 1040.65 | 21.25 | 69.33 | 292.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:49 | 2215.82 | 17.89 | 84.50 | 332.50 | 1196.61 | 18.98 | 54.67 | 305.33 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-07:19 | 2125.59 | 12.79 | 0.00 | 352.83 | 1143.43 | 16.23 | 0.00 | 326.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2120.42 | 12.88 | 0.00 | 338.00 | 916.29 | 16.11 | 0.00 | 306.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1607.93 | 13.62 | 3.50 | 337.17 | 762.81 | 16.49 | 0.00 | 293.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1501.09 | 15.64 | 52.17 | 323.00 | 774.40 | 16.45 | 4.67 | 277.83 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-08:09 | 1676.84 | 18.44 | 80.17 | 302.33 | 869.67 | 19.48 | 52.00 | 263.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1994.05 | 20.60 | 104.67 | 294.50 | 1031.45 | 21.29 | 74.17 | 267.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1742.92 | 20.93 | 95.83 | 270.50 | 905.10 | 21.73 | 67.17 | 244.67 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:30 | 1524.19 | 20.16 | 90.17 | 269.17 | 817.76 | 21.90 | 70.00 | 236.50 |
Annual Sum or Average | 4237.50 | 0.52 | 1855.06 | 17.72 | 819.33 | 3670.50 | 937.47 | 19.15 | 514.33 | 3269.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1501.09 | 12.79 | 0.00 | 263.00 | 762.81 | 16.11 | 0.00 | 227.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2215.82 | 21.17 | 104.67 | 352.83 | 1196.61 | 21.90 | 74.33 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5624.00 | 34.86 | 296.67 | 287.33 | 1325.45 | 21.53 | 84.50 | 268.33 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3403.50 | 26.55 | 195.33 | 271.33 | 1179.69 | 16.78 | 0.00 | 246.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1782.61 | 14.25 | 7.50 | 323.67 | 1014.98 | 17.39 | 0.00 | 294.83 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 1214.45 | 13.14 | 0.00 | 329.17 | 750.44 | 16.55 | 0.00 | 299.67 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1026.96 | 12.76 | 0.00 | 350.17 | 630.18 | 16.22 | 0.00 | 315.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1014.13 | 12.32 | 0.00 | 334.67 | 608.33 | 15.71 | 0.00 | 296.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1127.12 | 12.38 | 0.00 | 333.83 | 615.60 | 15.72 | 0.00 | 287.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1262.97 | 12.35 | 0.00 | 322.33 | 666.63 | 15.61 | 0.00 | 277.33 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:19 | 1543.85 | 13.11 | 0.00 | 302.67 | 839.72 | 16.50 | 0.00 | 267.67 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2626.21 | 15.64 | 42.67 | 307.67 | 1142.95 | 16.85 | 10.00 | 282.17 |
November | 317.83 | 0.50 | 0.48 | 01-NOV-07:19 | 7612.61 | 36.19 | 310.33 | 288.00 | 1402.62 | 20.72 | 74.33 | 272.67 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5937.38 | 36.28 | 308.00 | 286.50 | 1549.59 | 24.14 | 123.17 | 279.67 |
Annual Sum or Average | 4237.50 | 0.51 | 2686.79 | 19.24 | 1160.50 | 3737.33 | 951.21 | 17.65 | 292.00 | 3387.83 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1014.13 | 12.32 | 0.00 | 271.33 | 608.33 | 15.61 | 0.00 | 246.83 | |
Maximum of Months | 406.00 | 0.52 | 0.48 | 7612.61 | 36.28 | 310.33 | 350.17 | 1549.59 | 24.14 | 123.17 | 315.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1681.15 | 21.35 | 106.83 | 269.00 | 911.10 | 22.02 | 77.33 | 228.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2086.60 | 21.29 | 100.00 | 258.67 | 1125.72 | 22.05 | 74.00 | 226.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 2020.70 | 20.44 | 101.50 | 320.17 | 1071.92 | 21.34 | 70.67 | 291.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2416.28 | 19.95 | 110.17 | 328.83 | 1312.36 | 20.87 | 81.17 | 304.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2496.37 | 19.28 | 117.00 | 357.83 | 1021.17 | 19.75 | 66.50 | 327.33 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 2008.17 | 18.89 | 107.17 | 338.83 | 879.79 | 18.84 | 51.33 | 304.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1660.51 | 18.31 | 96.33 | 338.83 | 777.38 | 18.91 | 48.17 | 294.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1522.99 | 18.28 | 97.50 | 324.17 | 789.87 | 19.49 | 69.00 | 275.17 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1709.62 | 19.39 | 90.00 | 298.50 | 890.79 | 20.48 | 64.50 | 263.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1882.26 | 20.23 | 100.83 | 298.17 | 979.31 | 21.13 | 72.17 | 268.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1688.45 | 19.99 | 87.83 | 269.67 | 889.71 | 21.57 | 64.83 | 242.83 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1755.86 | 22.05 | 112.50 | 264.00 | 957.76 | 22.69 | 81.67 | 232.50 |
Annual Sum or Average | 4237.50 | 0.52 | 1922.43 | 19.88 | 1227.67 | 3666.67 | 967.15 | 20.67 | 821.33 | 3257.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1522.99 | 18.28 | 87.83 | 258.67 | 777.38 | 18.84 | 48.17 | 226.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2496.37 | 22.05 | 117.00 | 357.83 | 1312.36 | 22.69 | 81.67 | 327.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:09 | 563.55 | 10.84 | 0.00 | 249.00 | 363.04 | 14.37 | 0.00 | 179.83 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 651.03 | 11.75 | 0.00 | 249.33 | 417.89 | 15.27 | 0.00 | 193.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:09 | 771.28 | 13.07 | 0.00 | 314.83 | 493.75 | 16.56 | 0.00 | 270.50 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 836.09 | 13.23 | 0.00 | 332.83 | 542.96 | 16.65 | 0.00 | 304.83 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 991.60 | 13.29 | 1.17 | 365.83 | 608.75 | 16.84 | 1.17 | 339.67 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1093.78 | 15.55 | 39.17 | 348.33 | 642.47 | 18.74 | 40.50 | 317.83 |
July | 379.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1102.28 | 14.64 | 29.17 | 345.33 | 604.89 | 17.80 | 29.67 | 303.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 985.40 | 12.26 | 0.00 | 325.67 | 540.12 | 15.54 | 0.00 | 279.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 861.62 | 12.53 | 0.00 | 299.33 | 502.16 | 15.87 | 0.00 | 252.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:30 | 683.85 | 11.85 | 0.00 | 289.17 | 448.37 | 15.31 | 0.00 | 242.17 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:09 | 582.32 | 11.25 | 0.00 | 253.33 | 396.38 | 14.93 | 0.00 | 204.17 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:30 | 555.32 | 10.89 | 0.00 | 244.67 | 361.08 | 14.51 | 0.00 | 178.33 |
Annual Sum or Average | 4237.50 | 0.52 | 821.76 | 12.70 | 69.50 | 3617.67 | 501.28 | 16.12 | 71.33 | 3065.67 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 555.32 | 10.84 | 0.00 | 244.67 | 361.08 | 14.37 | 0.00 | 178.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1102.28 | 15.55 | 39.17 | 365.83 | 642.47 | 18.74 | 40.50 | 339.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:09 | 1684.31 | 21.14 | 104.00 | 267.83 | 898.11 | 21.74 | 74.33 | 227.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:00 | 1996.07 | 21.04 | 103.17 | 263.00 | 830.75 | 20.08 | 48.00 | 228.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1970.84 | 20.36 | 101.17 | 320.00 | 1041.84 | 21.24 | 69.33 | 292.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:49 | 2217.04 | 17.86 | 84.50 | 332.50 | 1197.74 | 18.97 | 54.67 | 305.50 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-07:19 | 2126.96 | 12.76 | 0.00 | 352.83 | 1144.61 | 16.21 | 0.00 | 326.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2122.05 | 12.84 | 0.00 | 338.00 | 917.51 | 16.10 | 0.00 | 306.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1610.11 | 13.58 | 3.50 | 337.17 | 764.11 | 16.47 | 0.00 | 293.50 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1503.29 | 15.61 | 52.00 | 323.00 | 775.71 | 16.44 | 4.67 | 278.00 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:00 | 1678.75 | 18.41 | 80.17 | 302.33 | 870.98 | 19.47 | 52.00 | 263.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1995.21 | 20.57 | 104.67 | 294.67 | 1032.53 | 21.27 | 74.17 | 267.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1743.76 | 20.90 | 95.83 | 270.50 | 906.03 | 21.72 | 67.17 | 244.67 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:30 | 1525.13 | 20.13 | 90.17 | 269.33 | 818.70 | 21.89 | 70.00 | 236.67 |
Annual Sum or Average | 4237.50 | 0.52 | 1856.49 | 17.69 | 819.17 | 3671.17 | 938.61 | 19.13 | 514.33 | 3270.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1503.29 | 12.76 | 0.00 | 263.00 | 764.11 | 16.10 | 0.00 | 227.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2217.04 | 21.14 | 104.67 | 352.83 | 1197.74 | 21.89 | 74.33 | 326.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.885166E+09 | 11048.43 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136196E+09 | 6700.86 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98168.28 | 490.84 | 27-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182366E+09 | 10093.87 | 23-DEC-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.885166E+09 | 11048.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6081238.00 | 5343.16 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6081238.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6081238.00 | 5343.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130771E+11 | 91305.69 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204641E+10 | 73454.94 | 02-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58833191.90 | 16761.11 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.369030E+10 | 91305.69 | 21-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130771E+11 | 91305.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147375E+09 | 146329.83 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147375E+09 | 146329.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.572281E+10 | 160168.38 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.766825E+09 | 123238.51 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166032E+10 | 160168.38 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.814995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.572281E+10 | 160168.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188736E+10 | 105850.12 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161918E+09 | 93795.00 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325660E+09 | 83222.90 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188736E+10 | 105850.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.985390E+09 | 160169.40 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139206E+09 | 117296.31 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73760190.81 | 11864.42 | 23-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.985390E+09 | 160169.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149635E+10 | 96902.87 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112584E+09 | 40856.10 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246607E+09 | 48528.57 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149635E+10 | 96902.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228689E+10 | 8549.59 | 01-JAN-01:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499999E+09 | 8549.59 | 01-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47400982.66 | 5180.14 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943947E+09 | 8549.59 | 04-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228689E+10 | 8549.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123567E+10 | 67249.46 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41248414.33 | 5400.75 | 23-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123567E+10 | 67249.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193340E+10 | 19892.10 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387488E+09 | 19892.10 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26762.39 | 44.60 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52280477.70 | 12551.76 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.960532E+09 | 19892.10 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193340E+10 | 19892.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.732164E+09 | 13054.68 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134087E+09 | 13054.68 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10139561.74 | 1351.94 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337498E+09 | 13054.68 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.732164E+09 | 13054.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694990E+09 | 19892.29 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141224E+09 | 19892.29 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243504E+09 | 19892.29 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694990E+09 | 19892.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.647574E+09 | 12396.72 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107177E+09 | 12396.72 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1705454.62 | 360.20 | 27-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252132E+09 | 12396.72 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.647574E+09 | 12396.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 42406882.68 | 6132.59 | 05-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3857560.55 | 2426.50 | 02-FEB-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6439990.99 | 2264.45 | 21-DEC-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52704434.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42406882.68 | 6132.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.355809E+11 | 0.355359E+11 | 76084.64 | 18-JAN-06:03 | 61485.87 | 0.38 |
February | 0.00 | 0.00 | 0.576291E+11 | 0.575109E+11 | 148776.47 | 25-FEB-06:02 | 101901.71 | 0.52 |
March | 0.00 | 0.00 | 0.125262E+12 | 0.122878E+12 | 219571.89 | 13-MAR-04:22 | 164898.47 | 0.73 |
April | 0.00 | 0.00 | 0.210107E+12 | 0.201633E+12 | 260167.98 | 17-APR-03:02 | 188724.71 | 0.83 |
May | 0.00 | 0.00 | 0.281537E+12 | 0.244254E+12 | 284133.32 | 22-MAY-04:23 | 189722.22 | 0.87 |
June | 0.00 | 0.00 | 0.322872E+12 | 0.252312E+12 | 303701.11 | 14-JUN-03:02 | 201393.15 | 0.87 |
July | 0.00 | 0.00 | 0.360660E+12 | 0.244777E+12 | 309323.16 | 05-JUL-03:02 | 206263.26 | 0.87 |
August | 0.00 | 0.00 | 0.378287E+12 | 0.251838E+12 | 319625.23 | 27-AUG-14:22 | 202426.97 | 0.89 |
September | 0.00 | 0.00 | 0.290015E+12 | 0.200422E+12 | 292149.22 | 18-SEP-03:02 | 189051.38 | 0.84 |
October | 0.00 | 0.00 | 0.171191E+12 | 0.152484E+12 | 238896.69 | 02-OCT-05:03 | 174600.95 | 0.76 |
November | 0.00 | 0.00 | 0.953984E+11 | 0.940350E+11 | 163969.59 | 09-NOV-05:12 | 110891.01 | 0.62 |
December | 0.00 | 0.00 | 0.566276E+11 | 0.566274E+11 | 91901.73 | 04-DEC-15:00 | 91901.73 | 0.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.238517E+13 | 0.191431E+13 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.355809E+11 | 0.355359E+11 | 76084.64 | 61485.87 | 0.38 | |
Maximum of Months | 0.00 | 0.00 | 0.378287E+12 | 0.252312E+12 | 319625.23 | 206263.26 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.215781E+12 | 0.215781E+12 | 591530.94 | 12-JAN-15:05 | 591530.94 | 0.33 |
February | 0.00 | 0.00 | 0.396255E+12 | 0.395444E+12 | 1078081.03 | 25-FEB-06:02 | 731984.08 | 0.48 |
March | 0.00 | 0.00 | 0.913988E+12 | 0.898962E+12 | 1928172.20 | 13-MAR-04:12 | 1499884.83 | 0.62 |
April | 0.00 | 0.00 | 0.148381E+13 | 0.142737E+13 | 2089190.97 | 27-APR-05:02 | 1611011.13 | 0.73 |
May | 0.00 | 0.00 | 0.217174E+13 | 0.183624E+13 | 2541249.65 | 22-MAY-05:02 | 1644025.91 | 0.84 |
June | 0.00 | 0.00 | 0.245488E+13 | 0.180290E+13 | 2774148.62 | 14-JUN-05:01 | 1780836.24 | 0.83 |
July | 0.00 | 0.00 | 0.266632E+13 | 0.159561E+13 | 2935439.46 | 25-JUL-05:02 | 1646701.23 | 0.81 |
August | 0.00 | 0.00 | 0.264440E+13 | 0.152427E+13 | 2896318.90 | 12-AUG-05:02 | 1638773.01 | 0.79 |
September | 0.00 | 0.00 | 0.204257E+13 | 0.127240E+13 | 2815375.30 | 05-SEP-05:02 | 1665050.36 | 0.73 |
October | 0.00 | 0.00 | 0.125669E+13 | 0.110663E+13 | 2157171.37 | 11-OCT-03:02 | 1507650.76 | 0.66 |
November | 0.00 | 0.00 | 0.689374E+12 | 0.679793E+12 | 1395598.69 | 09-NOV-06:03 | 921223.74 | 0.58 |
December | 0.00 | 0.00 | 0.297936E+12 | 0.297936E+12 | 670332.12 | 29-DEC-06:03 | 670332.12 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.172337E+14 | 0.130533E+14 | 0.65 | |||
Minimum of Months | 0.00 | 0.00 | 0.215781E+12 | 0.215781E+12 | 591530.94 | 591530.94 | 0.33 | |
Maximum of Months | 0.00 | 0.00 | 0.266632E+13 | 0.183624E+13 | 2935439.46 | 1780836.24 | 0.84 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.172890E+11 | 0.172890E+11 | 57737.92 | 12-JAN-15:30 | 57737.92 | 0.30 |
February | 0.00 | 0.00 | 0.358521E+11 | 0.357738E+11 | 98237.74 | 25-FEB-06:02 | 65634.84 | 0.46 |
March | 0.00 | 0.00 | 0.930587E+11 | 0.916819E+11 | 185819.38 | 29-MAR-04:12 | 150906.48 | 0.61 |
April | 0.00 | 0.00 | 0.161503E+12 | 0.155821E+12 | 230594.90 | 03-APR-04:12 | 169103.24 | 0.73 |
May | 0.00 | 0.00 | 0.238722E+12 | 0.204961E+12 | 281173.01 | 22-MAY-05:02 | 185376.49 | 0.84 |
June | 0.00 | 0.00 | 0.267239E+12 | 0.202035E+12 | 311166.15 | 14-JUN-05:01 | 203740.52 | 0.83 |
July | 0.00 | 0.00 | 0.283854E+12 | 0.176556E+12 | 326648.52 | 25-JUL-05:02 | 184857.62 | 0.81 |
August | 0.00 | 0.00 | 0.278032E+12 | 0.165937E+12 | 320805.95 | 28-AUG-04:02 | 196366.14 | 0.79 |
September | 0.00 | 0.00 | 0.212651E+12 | 0.136024E+12 | 293480.88 | 14-SEP-05:02 | 177026.69 | 0.73 |
October | 0.00 | 0.00 | 0.127058E+12 | 0.112875E+12 | 226029.21 | 11-OCT-03:02 | 153741.54 | 0.64 |
November | 0.00 | 0.00 | 0.634742E+11 | 0.629027E+11 | 117422.72 | 09-NOV-06:03 | 75656.81 | 0.55 |
December | 0.00 | 0.00 | 0.227096E+11 | 0.227096E+11 | 66240.74 | 01-DEC-15:00 | 66240.74 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.180144E+13 | 0.138456E+13 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.172890E+11 | 0.172890E+11 | 57737.92 | 57737.92 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.283854E+12 | 0.204961E+12 | 326648.52 | 203740.52 | 0.84 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471565E+11 | 0.469716E+11 | 121243.12 | 18-JAN-05:13 | 87908.17 | 0.44 |
February | 0.00 | 0.00 | 0.505305E+11 | 0.499500E+11 | 135429.18 | 25-FEB-05:12 | 88883.53 | 0.51 |
March | 0.00 | 0.00 | 0.605110E+11 | 0.587339E+11 | 244785.63 | 13-MAR-21:02 | 74141.32 | 0.43 |
April | 0.00 | 0.00 | 0.193734E+11 | 0.176889E+11 | 256515.03 | 22-APR-21:45 | 72984.68 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.672671E+11 | 0.587950E+11 | 270773.74 | 07-OCT-03:15 | 72937.16 | 0.30 |
November | 0.00 | 0.00 | 0.730658E+11 | 0.723878E+11 | 144218.19 | 09-NOV-05:12 | 88488.65 | 0.54 |
December | 0.00 | 0.00 | 0.587673E+11 | 0.586657E+11 | 114092.63 | 30-DEC-05:12 | 84763.17 | 0.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.376672E+12 | 0.363193E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.730658E+11 | 0.723878E+11 | 270773.74 | 88883.53 | 0.54 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.351062E+12 | 0.337222E+12 | 136526.57 | 17-JAN-17:00 | 129711.22 | 0.00 |
February | 0.00 | 0.00 | 0.545992E+12 | 0.528425E+12 | 230357.12 | 27-FEB-10:05 | 220211.20 | 0.00 |
March | 0.00 | 0.00 | 0.852777E+12 | 0.836378E+12 | 401767.23 | 31-MAR-24:00 | 399120.90 | 0.00 |
April | 0.00 | 0.00 | 0.106327E+13 | 0.105507E+13 | 421009.15 | 18-APR-16:00 | 413889.98 | 0.00 |
May | 0.00 | 0.00 | 0.380202E+12 | 0.363317E+12 | 232531.71 | 31-MAY-23:10 | 218729.89 | 0.00 |
June | 0.00 | 0.00 | 0.616508E+12 | 0.590632E+12 | 325677.80 | 30-JUN-23:03 | 313245.13 | 0.00 |
July | 0.00 | 0.00 | 0.893594E+12 | 0.856391E+12 | 422437.14 | 31-JUL-23:03 | 404509.38 | 0.00 |
August | 0.00 | 0.00 | 0.113972E+13 | 0.110120E+13 | 434215.56 | 25-AUG-14:05 | 415312.89 | 0.00 |
September | 0.00 | 0.00 | 0.383826E+12 | 0.352442E+12 | 234536.20 | 30-SEP-23:05 | 219908.13 | 0.00 |
October | 0.00 | 0.00 | 0.617852E+12 | 0.601200E+12 | 317797.82 | 31-OCT-24:00 | 307567.68 | 0.00 |
November | 0.00 | 0.00 | 0.833539E+12 | 0.811549E+12 | 326851.55 | 24-NOV-08:50 | 313132.49 | 0.00 |
December | 0.00 | 0.00 | 0.111612E+13 | 0.107800E+13 | 429141.06 | 22-DEC-08:65 | 404595.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.879446E+13 | 0.851183E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.351062E+12 | 0.337222E+12 | 136526.57 | 129711.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113972E+13 | 0.110120E+13 | 434215.56 | 415312.89 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.468073E+10 | 0.452252E+10 | 2419.53 | 12-JAN-17:00 | 2285.32 | 0.00 |
February | 0.00 | 0.00 | 0.946194E+10 | 0.921951E+10 | 4496.53 | 21-FEB-17:00 | 4339.31 | 0.00 |
March | 0.00 | 0.00 | 0.162526E+11 | 0.158935E+11 | 7854.42 | 31-MAR-24:00 | 7733.54 | 0.00 |
April | 0.00 | 0.00 | 0.212193E+11 | 0.208718E+11 | 8745.59 | 16-APR-20:54 | 8473.94 | 0.00 |
May | 0.00 | 0.00 | 0.760235E+10 | 0.691441E+10 | 4738.79 | 31-MAY-23:10 | 4123.73 | 0.00 |
June | 0.00 | 0.00 | 0.127319E+11 | 0.116209E+11 | 6767.60 | 30-JUN-23:03 | 6231.20 | 0.00 |
July | 0.00 | 0.00 | 0.186917E+11 | 0.170405E+11 | 8847.47 | 31-JUL-23:03 | 8027.87 | 0.00 |
August | 0.00 | 0.00 | 0.233082E+11 | 0.215624E+11 | 8995.68 | 20-AUG-16:54 | 8319.78 | 0.00 |
September | 0.00 | 0.00 | 0.767257E+10 | 0.637314E+10 | 4830.06 | 30-SEP-23:05 | 4202.35 | 0.00 |
October | 0.00 | 0.00 | 0.118721E+11 | 0.112332E+11 | 5984.86 | 31-OCT-23:10 | 5714.59 | 0.00 |
November | 0.00 | 0.00 | 0.155412E+11 | 0.152041E+11 | 6555.74 | 08-NOV-16:50 | 6280.86 | 0.00 |
December | 0.00 | 0.00 | 0.203850E+11 | 0.201917E+11 | 8209.93 | 28-DEC-17:00 | 8026.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169419E+12 | 0.160648E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.468073E+10 | 0.452252E+10 | 2419.53 | 2285.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.233082E+11 | 0.215624E+11 | 8995.68 | 8473.94 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.311152E+11 | 0.298270E+11 | 22271.91 | 12-JAN-17:00 | 21017.61 | 0.00 |
February | 0.00 | 0.00 | 0.834391E+11 | 0.812036E+11 | 42316.04 | 22-FEB-17:00 | 40784.60 | 0.00 |
March | 0.00 | 0.00 | 0.152878E+12 | 0.149492E+12 | 75408.30 | 31-MAR-24:00 | 74273.72 | 0.00 |
April | 0.00 | 0.00 | 0.199884E+12 | 0.196597E+12 | 81577.86 | 16-APR-20:54 | 78875.36 | 0.00 |
May | 0.00 | 0.00 | 0.693212E+11 | 0.627395E+11 | 45050.19 | 31-MAY-23:10 | 38791.96 | 0.00 |
June | 0.00 | 0.00 | 0.118631E+12 | 0.107797E+12 | 63926.80 | 30-JUN-23:03 | 58637.07 | 0.00 |
July | 0.00 | 0.00 | 0.174474E+12 | 0.158242E+12 | 82780.89 | 31-JUL-23:03 | 74677.73 | 0.00 |
August | 0.00 | 0.00 | 0.218727E+12 | 0.201535E+12 | 84517.91 | 10-AUG-14:00 | 76233.88 | 0.00 |
September | 0.00 | 0.00 | 0.691101E+11 | 0.565567E+11 | 45267.93 | 30-SEP-23:05 | 38901.33 | 0.00 |
October | 0.00 | 0.00 | 0.110521E+12 | 0.104378E+12 | 56631.68 | 31-OCT-23:10 | 53973.68 | 0.00 |
November | 0.00 | 0.00 | 0.143781E+12 | 0.140612E+12 | 62370.93 | 08-NOV-17:00 | 59635.83 | 0.00 |
December | 0.00 | 0.00 | 0.184163E+12 | 0.182396E+12 | 77566.74 | 28-DEC-17:00 | 75825.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155604E+13 | 0.147138E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.311152E+11 | 0.298270E+11 | 22271.91 | 21017.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218727E+12 | 0.201535E+12 | 84517.91 | 78875.36 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.202886E+10 | 0.191316E+10 | 2267.60 | 12-JAN-17:00 | 2133.47 | 0.00 |
February | 0.00 | 0.00 | 0.775095E+10 | 0.751475E+10 | 4297.52 | 22-FEB-17:00 | 4136.48 | 0.00 |
March | 0.00 | 0.00 | 0.151516E+11 | 0.147945E+11 | 7508.13 | 31-MAR-24:00 | 7387.46 | 0.00 |
April | 0.00 | 0.00 | 0.201709E+11 | 0.198243E+11 | 8453.13 | 16-APR-20:54 | 8174.32 | 0.00 |
May | 0.00 | 0.00 | 0.717200E+10 | 0.649347E+10 | 4467.89 | 31-MAY-23:10 | 3827.05 | 0.00 |
June | 0.00 | 0.00 | 0.120845E+11 | 0.109812E+11 | 6471.11 | 30-JUN-23:03 | 5932.43 | 0.00 |
July | 0.00 | 0.00 | 0.176825E+11 | 0.160388E+11 | 8423.79 | 31-JUL-23:03 | 7594.44 | 0.00 |
August | 0.00 | 0.00 | 0.222001E+11 | 0.204543E+11 | 8646.28 | 20-AUG-16:54 | 7965.40 | 0.00 |
September | 0.00 | 0.00 | 0.702291E+10 | 0.574774E+10 | 4566.93 | 30-SEP-23:05 | 3925.85 | 0.00 |
October | 0.00 | 0.00 | 0.110053E+11 | 0.103732E+11 | 5568.04 | 31-OCT-23:10 | 5291.07 | 0.00 |
November | 0.00 | 0.00 | 0.139264E+11 | 0.135924E+11 | 6292.71 | 08-NOV-16:50 | 6019.94 | 0.00 |
December | 0.00 | 0.00 | 0.173232E+11 | 0.171310E+11 | 7791.78 | 28-DEC-17:00 | 7609.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153519E+12 | 0.144859E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.202886E+10 | 0.191316E+10 | 2267.60 | 2133.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222001E+11 | 0.204543E+11 | 8646.28 | 8174.32 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 119695.57 | 758546.26 | 12-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 229804.97 | 1321740.47 | 22-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 471461.37 | 1979208.37 | 28-MAR-12:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 757696.88 | 2043833.86 | 21-APR-12:05 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1033820.84 | 3080302.49 | 30-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1202329.94 | 3356274.55 | 11-JUN-13:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1261814.69 | 3852942.34 | 31-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1254626.84 | 3360781.57 | 28-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1014117.56 | 3102646.95 | 05-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 638132.88 | 2032003.26 | 26-OCT-12:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 380224.62 | 1837066.44 | 09-NOV-11:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 164658.02 | 862410.33 | 01-DEC-15:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 713249.66 | 0.00 | ||||
Minimum of Months | 119695.57 | 758546.26 | 0.00 | 0.00 | ||
Maximum of Months | 1261814.69 | 3852942.34 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117591.14 | 799725.63 | 14-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 227711.80 | 1348179.69 | 25-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 468638.27 | 3157393.05 | 14-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 753839.38 | 3700083.05 | 26-APR-05:02 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1028756.39 | 3891589.88 | 25-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1196600.63 | 4190095.17 | 14-JUN-05:01 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1255318.78 | 4359736.73 | 03-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1248741.85 | 4291686.06 | 28-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1009428.58 | 4171854.28 | 14-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 636229.20 | 3887921.73 | 07-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 378019.51 | 1957699.10 | 06-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 162431.96 | 869455.28 | 01-DEC-15:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 709483.58 | 0.00 | ||||
Minimum of Months | 117591.14 | 799725.63 | 0.00 | 0.00 | ||
Maximum of Months | 1255318.78 | 4359736.73 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 216362.07 | 585275.91 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 475936.70 | 1009751.73 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 912990.86 | 1766866.33 | 28-MAR-15:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1550817.22 | 2280179.38 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1178321.86 | 1895923.12 | 03-MAY-15:10 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1442243.13 | 2150911.60 | 08-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1542589.98 | 2116395.70 | 02-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1644030.37 | 2124380.49 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 931763.31 | 1478347.16 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 890634.34 | 1616397.33 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 767254.55 | 1402730.24 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 732702.56 | 1251697.97 | 28-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1026671.69 | 0.00 | ||||
Minimum of Months | 216362.07 | 585275.91 | 0.00 | 0.00 | ||
Maximum of Months | 1644030.37 | 2280179.38 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 11527.54 | 40953.89 | 17-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11357.95 | 40708.74 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11277.03 | 38965.93 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 9503.44 | 35292.60 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8709.18 | 31619.57 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 8024.89 | 28021.01 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 7047.35 | 25841.50 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 7988.44 | 27583.91 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8257.98 | 30767.60 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 9304.95 | 34947.78 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10527.79 | 38434.91 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10931.17 | 40529.26 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 9528.22 | ||||
Minimum of Months | 0.00 | 0.00 | 7047.35 | 25841.50 | ||
Maximum of Months | 0.00 | 0.00 | 11527.54 | 40953.89 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 124579.43 | 846826.97 | 12-JAN-15:10 | 4663.87 | 138634.65 | 23-JAN-05:40 |
February | 255198.13 | 1517328.96 | 22-FEB-15:40 | 1593.75 | 127108.26 | 02-FEB-07:00 |
March | 577596.87 | 2857611.88 | 10-MAR-13:05 | 509.71 | 63523.21 | 27-MAR-03:50 |
April | 1127095.56 | 4924386.26 | 18-APR-14:05 | 591.45 | 78636.76 | 11-APR-04:00 |
May | 2338054.74 | 6661613.09 | 17-MAY-15:40 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3406299.22 | 7656341.91 | 22-JUN-15:40 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4151761.76 | 7666823.58 | 08-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 4180066.03 | 7654718.71 | 28-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 3036043.28 | 7113354.40 | 14-SEP-14:40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 978313.93 | 4507970.50 | 04-OCT-11:00 | 85.47 | 31958.41 | 15-OCT-07:30 |
November | 443614.13 | 2635522.63 | 09-NOV-14:05 | 489.93 | 77365.40 | 27-NOV-05:55 |
December | 175174.80 | 967609.57 | 01-DEC-15:05 | 3251.96 | 146818.92 | 20-DEC-07:20 |
Annual Sum or Average | 1741997.50 | 933.99 | ||||
Minimum of Months | 124579.43 | 846826.97 | 0.00 | 0.00 | ||
Maximum of Months | 4180066.03 | 7666823.58 | 4663.87 | 146818.92 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.434570E+10 | 0.33 | 8021.45 | 26-JAN-06:03 | 0.98 |
February | 0.573785E+10 | 0.40 | 12712.07 | 23-FEB-06:02 | 1.29 |
March | 0.111436E+11 | 0.59 | 21547.49 | 13-MAR-04:22 | 1.80 |
April | 0.187696E+11 | 0.86 | 21547.49 | 03-APR-03:02 | 1.80 |
May | 0.227360E+11 | 0.93 | 21547.49 | 01-MAY-03:02 | 1.80 |
June | 0.250366E+11 | 1.01 | 21547.49 | 01-JUN-05:03 | 1.80 |
July | 0.246738E+11 | 0.98 | 21547.49 | 03-JUL-03:02 | 1.80 |
August | 0.270280E+11 | 1.04 | 21547.49 | 01-AUG-03:12 | 1.80 |
September | 0.197306E+11 | 0.87 | 21547.49 | 01-SEP-03:12 | 1.80 |
October | 0.128935E+11 | 0.65 | 21547.49 | 02-OCT-04:12 | 1.80 |
November | 0.810058E+10 | 0.47 | 14744.34 | 06-NOV-05:12 | 1.42 |
December | 0.658089E+10 | 0.40 | 11089.13 | 04-DEC-15:20 | 1.19 |
Annual Sum or Average | 0.186777E+12 | 0.71 | |||
Minimum of Months | 0.434570E+10 | 0.33 | 8021.45 | 0.98 | |
Maximum of Months | 0.270280E+11 | 1.04 | 21547.49 | 1.80 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.286965E+11 | 0.30 | 81369.36 | 21-JAN-06:02 | 1.02 |
February | 0.366361E+11 | 0.34 | 79910.74 | 22-FEB-16:10 | 1.00 |
March | 0.695995E+11 | 0.44 | 205624.16 | 13-MAR-05:02 | 1.80 |
April | 0.985253E+11 | 0.59 | 205624.16 | 03-APR-05:02 | 1.80 |
May | 0.121567E+12 | 0.68 | 205624.16 | 23-MAY-05:02 | 1.80 |
June | 0.121550E+12 | 0.68 | 205624.16 | 10-JUN-05:02 | 1.80 |
July | 0.107224E+12 | 0.62 | 205624.16 | 10-JUL-05:03 | 1.80 |
August | 0.109366E+12 | 0.62 | 205624.16 | 03-AUG-05:03 | 1.80 |
September | 0.860852E+11 | 0.54 | 205624.16 | 06-SEP-05:03 | 1.80 |
October | 0.732502E+11 | 0.46 | 205624.16 | 02-OCT-04:12 | 1.80 |
November | 0.496291E+11 | 0.38 | 106513.24 | 01-NOV-05:02 | 1.19 |
December | 0.331752E+11 | 0.31 | 87761.50 | 22-DEC-06:02 | 1.07 |
Annual Sum or Average | 0.935303E+12 | 0.50 | |||
Minimum of Months | 0.286965E+11 | 0.30 | 79910.74 | 1.00 | |
Maximum of Months | 0.121567E+12 | 0.68 | 205624.16 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270936E+10 | 0.32 | 4433.81 | 02-JAN-05:11 | 0.67 |
February | 0.322207E+10 | 0.33 | 7800.69 | 22-FEB-15:40 | 0.91 |
March | 0.658163E+10 | 0.42 | 19144.18 | 29-MAR-04:12 | 1.58 |
April | 0.104999E+11 | 0.58 | 23394.08 | 03-APR-04:12 | 1.79 |
May | 0.133915E+11 | 0.68 | 23394.08 | 15-MAY-04:12 | 1.79 |
June | 0.134755E+11 | 0.68 | 23394.08 | 06-JUN-05:01 | 1.79 |
July | 0.115613E+11 | 0.62 | 23394.08 | 03-JUL-05:01 | 1.79 |
August | 0.112985E+11 | 0.60 | 23394.08 | 14-AUG-04:42 | 1.79 |
September | 0.885852E+10 | 0.52 | 23394.08 | 23-SEP-05:02 | 1.79 |
October | 0.704967E+10 | 0.43 | 23311.51 | 04-OCT-05:02 | 1.79 |
November | 0.436589E+10 | 0.35 | 8959.21 | 09-NOV-16:00 | 0.99 |
December | 0.278762E+10 | 0.31 | 4874.40 | 01-DEC-15:00 | 0.71 |
Annual Sum or Average | 0.958014E+11 | 0.49 | |||
Minimum of Months | 0.270936E+10 | 0.31 | 4433.81 | 0.67 | |
Maximum of Months | 0.134755E+11 | 0.68 | 23394.08 | 1.79 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125520E+11 | 0.83 | 11623.14 | 01-JAN-00:30 | 1.82 |
February | 0.117480E+11 | 0.83 | 11623.14 | 01-FEB-05:25 | 1.82 |
March | 0.120129E+11 | 0.73 | 11623.14 | 01-MAR-05:12 | 1.82 |
April | 0.274314E+10 | 0.17 | 11623.14 | 05-APR-03:43 | 1.77 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.902377E+10 | 0.54 | 11623.14 | 01-OCT-04:35 | 1.80 |
November | 0.152265E+11 | 0.96 | 11623.14 | 01-NOV-04:12 | 1.82 |
December | 0.158925E+11 | 1.00 | 11623.14 | 01-DEC-05:12 | 1.82 |
Annual Sum or Average | 0.791988E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158925E+11 | 1.00 | 11623.14 | 1.82 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111101E+12 | 1.38 | 41480.20 | 01-JAN-00:10 | 1.38 |
February | 0.100349E+12 | 1.38 | 41480.20 | 01-FEB-00:20 | 1.38 |
March | 0.111101E+12 | 1.38 | 41480.20 | 01-MAR-00:10 | 1.38 |
April | 0.107517E+12 | 1.38 | 41480.20 | 01-APR-00:03 | 1.38 |
May | 0.111101E+12 | 1.38 | 41480.20 | 01-MAY-00:03 | 1.38 |
June | 0.107517E+12 | 1.38 | 41480.20 | 01-JUN-00:10 | 1.38 |
July | 0.111101E+12 | 1.38 | 41480.20 | 01-JUL-00:10 | 1.38 |
August | 0.111101E+12 | 1.38 | 41480.20 | 01-AUG-00:05 | 1.38 |
September | 0.107517E+12 | 1.38 | 41480.20 | 01-SEP-00:05 | 1.38 |
October | 0.111101E+12 | 1.38 | 41480.20 | 01-OCT-00:05 | 1.38 |
November | 0.107517E+12 | 1.38 | 41480.20 | 01-NOV-00:30 | 1.38 |
December | 0.111101E+12 | 1.38 | 41480.20 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.130812E+13 | 1.38 | |||
Minimum of Months | 0.100349E+12 | 1.38 | 41480.20 | 1.38 | |
Maximum of Months | 0.111101E+12 | 1.38 | 41480.20 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144573E+10 | 0.94 | 539.77 | 01-JAN-00:10 | 0.94 |
February | 0.130582E+10 | 0.94 | 539.77 | 01-FEB-00:10 | 0.94 |
March | 0.144573E+10 | 0.94 | 539.77 | 01-MAR-00:10 | 0.94 |
April | 0.139909E+10 | 0.94 | 539.77 | 01-APR-00:03 | 0.94 |
May | 0.144573E+10 | 0.94 | 539.77 | 01-MAY-00:03 | 0.94 |
June | 0.139909E+10 | 0.93 | 539.77 | 01-JUN-00:05 | 0.94 |
July | 0.144573E+10 | 0.93 | 539.77 | 01-JUL-00:10 | 0.94 |
August | 0.144573E+10 | 0.94 | 539.77 | 01-AUG-00:05 | 0.94 |
September | 0.139909E+10 | 0.93 | 539.77 | 01-SEP-00:05 | 0.93 |
October | 0.144573E+10 | 0.94 | 539.77 | 01-OCT-00:05 | 0.94 |
November | 0.139909E+10 | 0.94 | 539.77 | 01-NOV-00:10 | 0.94 |
December | 0.144573E+10 | 0.94 | 539.77 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.170223E+11 | 0.94 | |||
Minimum of Months | 0.130582E+10 | 0.93 | 539.77 | 0.93 | |
Maximum of Months | 0.144573E+10 | 0.94 | 539.77 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138026E+11 | 0.94 | 5153.29 | 01-JAN-00:10 | 0.94 |
February | 0.124668E+11 | 0.94 | 5153.29 | 01-FEB-00:10 | 0.94 |
March | 0.138026E+11 | 0.94 | 5153.29 | 01-MAR-00:10 | 0.94 |
April | 0.133573E+11 | 0.94 | 5153.29 | 01-APR-00:03 | 0.94 |
May | 0.138026E+11 | 0.93 | 5153.29 | 01-MAY-00:03 | 0.94 |
June | 0.133573E+11 | 0.93 | 5153.29 | 01-JUN-00:05 | 0.94 |
July | 0.138026E+11 | 0.93 | 5153.29 | 01-JUL-00:10 | 0.93 |
August | 0.138026E+11 | 0.93 | 5153.29 | 01-AUG-00:05 | 0.94 |
September | 0.133573E+11 | 0.93 | 5153.29 | 01-SEP-00:05 | 0.93 |
October | 0.138026E+11 | 0.94 | 5153.29 | 01-OCT-00:05 | 0.94 |
November | 0.133573E+11 | 0.94 | 5153.29 | 01-NOV-00:10 | 0.94 |
December | 0.138026E+11 | 0.94 | 5153.29 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.162514E+12 | 0.94 | |||
Minimum of Months | 0.124668E+11 | 0.93 | 5153.29 | 0.93 | |
Maximum of Months | 0.138026E+11 | 0.94 | 5153.29 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139509E+10 | 0.94 | 520.87 | 01-JAN-00:10 | 0.94 |
February | 0.126008E+10 | 0.94 | 520.87 | 01-FEB-00:10 | 0.94 |
March | 0.139509E+10 | 0.94 | 520.87 | 01-MAR-00:10 | 0.94 |
April | 0.135009E+10 | 0.94 | 520.87 | 01-APR-00:03 | 0.94 |
May | 0.139509E+10 | 0.93 | 520.87 | 01-MAY-00:03 | 0.94 |
June | 0.135009E+10 | 0.93 | 520.87 | 01-JUN-00:05 | 0.94 |
July | 0.139509E+10 | 0.93 | 520.87 | 01-JUL-00:10 | 0.94 |
August | 0.139509E+10 | 0.94 | 520.87 | 01-AUG-00:05 | 0.94 |
September | 0.135009E+10 | 0.93 | 520.87 | 01-SEP-00:05 | 0.93 |
October | 0.139509E+10 | 0.94 | 520.87 | 01-OCT-00:05 | 0.94 |
November | 0.135009E+10 | 0.94 | 520.87 | 01-NOV-00:10 | 0.94 |
December | 0.139509E+10 | 0.94 | 520.87 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.164261E+11 | 0.94 | |||
Minimum of Months | 0.126008E+10 | 0.93 | 520.87 | 0.93 | |
Maximum of Months | 0.139509E+10 | 0.94 | 520.87 | 0.94 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.110331E+09 | 0.100291E+09 | 836.21 | 12-JAN-06:03 | 760.11 | 760.11 | 6.70 | 24.74 |
February | 0.292127E+09 | 0.265543E+09 | 1818.05 | 23-FEB-14:00 | 1652.61 | 1652.61 | 6.71 | 35.00 |
March | 0.809208E+09 | 0.735570E+09 | 10953.60 | 14-MAR-05:03 | 9956.82 | 9956.82 | 9.75 | 73.51 |
April | 0.142842E+10 | 0.129843E+10 | 11362.67 | 10-APR-05:02 | 10328.67 | 10328.67 | 8.55 | 74.59 |
May | 0.199221E+10 | 0.181092E+10 | 11262.23 | 25-MAY-05:02 | 10237.37 | 10237.37 | 10.01 | 74.32 |
June | 0.230647E+10 | 0.209658E+10 | 11262.57 | 16-JUN-05:02 | 10237.68 | 10237.68 | 10.11 | 74.32 |
July | 0.237662E+10 | 0.216035E+10 | 11264.51 | 03-JUL-05:12 | 10239.44 | 10239.44 | 10.68 | 74.32 |
August | 0.241997E+10 | 0.219976E+10 | 11262.72 | 18-AUG-05:02 | 10237.81 | 10237.81 | 10.15 | 74.32 |
September | 0.174081E+10 | 0.158240E+10 | 11263.91 | 09-SEP-05:03 | 10238.89 | 10238.89 | 10.50 | 74.32 |
October | 0.120563E+10 | 0.109592E+10 | 12655.93 | 16-OCT-05:02 | 11504.24 | 11504.24 | 10.34 | 77.82 |
November | 0.698618E+09 | 0.635043E+09 | 3710.11 | 06-NOV-13:50 | 3372.49 | 3372.49 | 8.98 | 47.41 |
December | 0.188670E+09 | 0.171501E+09 | 1141.19 | 01-DEC-06:02 | 1037.34 | 1037.34 | 6.70 | 28.49 |
Annual Sum or Average | 0.155691E+11 | 0.141523E+11 | ||||||
Minimum of Months | 0.110331E+09 | 0.100291E+09 | 836.21 | 760.11 | 760.11 | 6.70 | 24.74 | |
Maximum of Months | 0.241997E+10 | 0.219976E+10 | 12655.93 | 11504.24 | 11504.24 | 10.68 | 77.82 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.645895E+10 | 0.587118E+10 | 4355.37 | 01-JAN-04:35 | 3959.03 | 3959.03 | 6.76 | 38.91 |
February | 0.632604E+10 | 0.575037E+10 | 4355.37 | 01-FEB-05:13 | 3959.03 | 3959.03 | 7.16 | 38.91 |
March | 0.885507E+10 | 0.804926E+10 | 4355.37 | 01-MAR-05:12 | 3959.03 | 3959.03 | 8.78 | 38.91 |
April | 0.106574E+11 | 0.968756E+10 | 4355.37 | 01-APR-00:25 | 3959.03 | 3959.03 | 6.88 | 38.91 |
May | 0.108681E+11 | 0.987913E+10 | 4355.37 | 01-MAY-00:03 | 3959.03 | 3959.03 | 9.41 | 38.91 |
June | 0.104108E+11 | 0.946342E+10 | 4355.37 | 01-JUN-00:25 | 3959.03 | 3959.03 | 7.06 | 38.91 |
July | 0.108149E+11 | 0.983078E+10 | 4355.37 | 01-JUL-00:10 | 3959.03 | 3959.03 | 12.19 | 38.91 |
August | 0.111531E+11 | 0.101382E+11 | 4355.37 | 01-AUG-00:05 | 3959.03 | 3959.03 | 12.65 | 38.91 |
September | 0.101856E+11 | 0.925870E+10 | 4355.37 | 01-SEP-00:05 | 3959.03 | 3959.03 | 9.07 | 38.91 |
October | 0.944083E+10 | 0.858171E+10 | 4355.37 | 01-OCT-00:05 | 3959.03 | 3959.03 | 7.04 | 38.91 |
November | 0.755395E+10 | 0.686654E+10 | 4355.37 | 01-NOV-04:12 | 3959.03 | 3959.03 | 10.93 | 38.91 |
December | 0.697499E+10 | 0.634027E+10 | 4355.37 | 01-DEC-05:12 | 3959.03 | 3959.03 | 7.81 | 38.91 |
Annual Sum or Average | 0.109700E+12 | 0.997171E+11 | ||||||
Minimum of Months | 0.632604E+10 | 0.575037E+10 | 4355.37 | 3959.03 | 3959.03 | 6.76 | 38.91 | |
Maximum of Months | 0.111531E+11 | 0.101382E+11 | 4355.37 | 3959.03 | 3959.03 | 12.65 | 38.91 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.83 | 0.00 |
March | 0.850603E+09 | 0.773198E+09 | 4355.37 | 06-MAR-13:05 | 3959.03 | 3959.03 | 11.13 | 38.91 |
April | 0.272602E+10 | 0.247796E+10 | 4355.37 | 03-APR-08:20 | 3959.03 | 3959.03 | 14.92 | 19.46 |
May | 0.474343E+10 | 0.431178E+10 | 4355.37 | 01-MAY-05:01 | 3959.03 | 3959.03 | 12.37 | 38.91 |
June | 0.572542E+10 | 0.520441E+10 | 4355.37 | 01-JUN-07:20 | 3959.03 | 3959.03 | 14.47 | 19.46 |
July | 0.632128E+10 | 0.574604E+10 | 4355.37 | 01-JUL-05:03 | 3959.03 | 3959.03 | 15.90 | 19.46 |
August | 0.649085E+10 | 0.590019E+10 | 4355.37 | 01-AUG-05:02 | 3959.03 | 3959.03 | 13.84 | 38.91 |
September | 0.473183E+10 | 0.430124E+10 | 4355.37 | 01-SEP-05:04 | 3959.03 | 3959.03 | 16.63 | 19.46 |
October | 0.228940E+10 | 0.208106E+10 | 4355.37 | 02-OCT-07:20 | 3959.03 | 3959.03 | 14.99 | 19.46 |
November | 0.478219E+09 | 0.434701E+09 | 4355.37 | 01-NOV-12:40 | 3959.03 | 3959.03 | 15.37 | 19.46 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 7.40 | 0.00 |
Annual Sum or Average | 0.343571E+11 | 0.312306E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 0.649085E+10 | 0.590019E+10 | 4355.37 | 3959.03 | 3959.03 | 16.63 | 38.91 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-JAN-00:10 | 3534.34 | 3534.34 | 21.22 | 16.40 |
February | 0.940624E+10 | 0.855027E+10 | 3888.16 | 01-FEB-00:10 | 3534.34 | 3534.34 | 23.64 | 16.40 |
March | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-MAR-00:10 | 3534.34 | 3534.34 | 26.33 | 16.40 |
April | 0.100781E+11 | 0.916100E+10 | 3888.16 | 01-APR-00:03 | 3534.34 | 3534.34 | 38.66 | 16.40 |
May | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-MAY-00:03 | 3534.34 | 3534.34 | 36.27 | 16.40 |
June | 0.100781E+11 | 0.916100E+10 | 3888.16 | 01-JUN-00:05 | 3534.34 | 3534.34 | 36.90 | 16.40 |
July | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-JUL-00:10 | 3534.34 | 3534.34 | 45.85 | 16.40 |
August | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-AUG-00:05 | 3534.34 | 3534.34 | 45.57 | 16.40 |
September | 0.100781E+11 | 0.916100E+10 | 3888.16 | 01-SEP-00:05 | 3534.34 | 3534.34 | 34.54 | 16.40 |
October | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-OCT-00:05 | 3534.34 | 3534.34 | 35.37 | 16.40 |
November | 0.100781E+11 | 0.916100E+10 | 3888.16 | 01-NOV-00:10 | 3534.34 | 3534.34 | 29.11 | 16.40 |
December | 0.104141E+11 | 0.946637E+10 | 3888.16 | 01-DEC-00:10 | 3534.34 | 3534.34 | 28.69 | 16.40 |
Annual Sum or Average | 0.122617E+12 | 0.111459E+12 | ||||||
Minimum of Months | 0.940624E+10 | 0.855027E+10 | 3888.16 | 3534.34 | 3534.34 | 21.22 | 16.40 | |
Maximum of Months | 0.104141E+11 | 0.946637E+10 | 3888.16 | 3534.34 | 3534.34 | 45.85 | 16.40 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 57.57 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.67 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 57.72 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.93 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 58.41 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.34 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 58.47 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 58.55 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 58.44 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 58.20 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 58.00 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.80 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.57 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.55 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.249551E+11 | 0.226842E+11 | 16854.10 | 12-JAN-15:10 | 15320.38 | 15320.38 | 24.04 | 68.86 |
February | 0.244542E+11 | 0.222289E+11 | 16885.16 | 22-FEB-15:40 | 15348.61 | 15348.61 | 26.37 | 68.86 |
March | 0.368839E+11 | 0.335275E+11 | 33761.69 | 10-MAR-13:05 | 30689.38 | 30689.38 | 26.06 | 137.73 |
April | 0.507274E+11 | 0.461112E+11 | 33857.61 | 18-APR-13:30 | 30776.56 | 30776.56 | 29.45 | 137.73 |
May | 0.592400E+11 | 0.538492E+11 | 33857.61 | 09-MAY-13:40 | 30776.56 | 30776.56 | 29.48 | 137.73 |
June | 0.610450E+11 | 0.554899E+11 | 33857.61 | 05-JUN-14:50 | 30776.56 | 30776.56 | 29.47 | 137.73 |
July | 0.648656E+11 | 0.589628E+11 | 33857.61 | 01-JUL-07:20 | 30776.56 | 30776.56 | 29.63 | 137.73 |
August | 0.669184E+11 | 0.608288E+11 | 33857.61 | 01-AUG-05:04 | 30776.56 | 30776.56 | 30.27 | 137.73 |
September | 0.561414E+11 | 0.510325E+11 | 33857.61 | 01-SEP-05:06 | 30776.56 | 30776.56 | 30.25 | 137.73 |
October | 0.438493E+11 | 0.398590E+11 | 33842.99 | 04-OCT-11:00 | 30763.28 | 30763.28 | 28.93 | 137.73 |
November | 0.308132E+11 | 0.280092E+11 | 33750.78 | 09-NOV-14:05 | 30679.46 | 30679.46 | 25.68 | 137.73 |
December | 0.269536E+11 | 0.245009E+11 | 16859.19 | 01-DEC-15:05 | 15325.01 | 15325.01 | 24.46 | 68.86 |
Annual Sum or Average | 0.546847E+12 | 0.497084E+12 | ||||||
Minimum of Months | 0.244542E+11 | 0.222289E+11 | 16854.10 | 15320.38 | 15320.38 | 24.04 | 68.86 | |
Maximum of Months | 0.669184E+11 | 0.608288E+11 | 33857.61 | 30776.56 | 30776.56 | 30.27 | 137.73 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 119695.57 | 758546.26 | 12-JAN-15:05 | 11.35 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 229804.97 | 1321740.47 | 22-FEB-15:30 | 14.82 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 471461.37 | 1979208.37 | 28-MAR-12:05 | 12.77 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 757696.88 | 2043833.86 | 21-APR-12:05 | 12.97 | 6.70 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1033820.84 | 3080302.49 | 30-MAY-05:03 | 16.16 | 7.72 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1202329.94 | 3356274.55 | 11-JUN-13:02 | 17.01 | 8.57 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1261814.69 | 3852942.34 | 31-JUL-05:03 | 18.54 | 10.10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1254626.84 | 3360781.57 | 28-AUG-05:01 | 17.02 | 8.59 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1014117.56 | 3102646.95 | 05-SEP-05:03 | 16.23 | 7.79 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 638132.88 | 2032003.26 | 26-OCT-12:05 | 12.94 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 380224.62 | 1837066.44 | 09-NOV-11:05 | 12.34 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 164658.02 | 862410.33 | 01-DEC-15:05 | 11.99 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 713249.66 | 0.00 | ||||||
Minimum of Months | 119695.57 | 758546.26 | 11.35 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1261814.69 | 3852942.34 | 18.54 | 10.10 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117591.14 | 799725.63 | 14-JAN-06:03 | 15.26 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 227711.80 | 1348179.69 | 25-FEB-06:02 | 16.97 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 468638.27 | 3157393.05 | 14-MAR-05:03 | 16.97 | 11.52 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 753839.38 | 3700083.05 | 26-APR-05:02 | 18.60 | 12.35 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1028756.39 | 3891589.88 | 25-MAY-05:02 | 19.22 | 12.64 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1196600.63 | 4190095.17 | 14-JUN-05:01 | 20.33 | 7.38 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1255318.78 | 4359736.73 | 03-JUL-03:02 | 20.73 | 9.69 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1248741.85 | 4291686.06 | 28-AUG-05:01 | 20.51 | 7.58 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1009428.58 | 4171854.28 | 14-SEP-03:02 | 20.13 | 13.07 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 636229.20 | 3887921.73 | 07-OCT-04:12 | 19.44 | 12.62 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 378019.51 | 1957699.10 | 06-NOV-13:50 | 16.57 | 8.99 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 162431.96 | 869455.28 | 01-DEC-15:05 | 14.61 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 709483.58 | 0.00 | ||||||
Minimum of Months | 117591.14 | 799725.63 | 14.61 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1255318.78 | 4359736.73 | 20.73 | 13.07 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 216362.07 | 585275.91 | 12-JAN-15:00 | 28.53 | 24.88 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 475936.70 | 1009751.73 | 22-FEB-15:00 | 35.82 | 29.38 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 912990.86 | 1766866.33 | 28-MAR-15:10 | 48.56 | 39.04 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1550817.22 | 2280179.38 | 15-APR-15:00 | 57.04 | 44.80 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1178321.86 | 1895923.12 | 03-MAY-15:10 | 50.70 | 46.13 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1442243.13 | 2150911.60 | 08-JUN-16:00 | 54.91 | 47.37 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1542589.98 | 2116395.70 | 02-JUL-16:10 | 54.35 | 44.13 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1644030.37 | 2124380.49 | 07-AUG-15:00 | 54.48 | 41.90 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 931763.31 | 1478347.16 | 17-SEP-20:00 | 43.74 | 39.15 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 890634.34 | 1616397.33 | 02-OCT-15:00 | 46.05 | 38.96 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 767254.55 | 1402730.24 | 04-NOV-14:00 | 42.47 | 33.51 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 732702.56 | 1251697.97 | 28-DEC-14:20 | 39.92 | 28.61 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1026671.69 | 0.00 | ||||||
Minimum of Months | 216362.07 | 585275.91 | 28.53 | 24.88 | 0.00 | 0.00 | ||
Maximum of Months | 1644030.37 | 2280179.38 | 57.04 | 47.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.50 | 58.50 | 11527.54 | 40953.89 | 17-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.11 | 58.11 | 11357.95 | 40708.74 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.19 | 58.19 | 11277.03 | 38965.93 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 58.35 | 58.35 | 9503.44 | 35292.60 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.84 | 58.84 | 8709.18 | 31619.57 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 58.71 | 58.71 | 8024.89 | 28021.01 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.82 | 58.82 | 7047.35 | 25841.50 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.83 | 58.83 | 7988.44 | 27583.91 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.74 | 58.74 | 8257.98 | 30767.60 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 58.58 | 58.58 | 9304.95 | 34947.78 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.39 | 58.39 | 10527.79 | 38434.91 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.22 | 58.22 | 10931.17 | 40529.26 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 9528.22 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.11 | 58.11 | 7047.35 | 25841.50 | ||
Maximum of Months | 0.00 | 0.00 | 58.84 | 58.84 | 11527.54 | 40953.89 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 124579.43 | 846826.97 | 12-JAN-15:10 | 24.04 | 21.10 | 4663.87 | 138634.65 | 23-JAN-05:40 |
February | 255198.13 | 1517328.96 | 22-FEB-15:40 | 26.37 | 21.10 | 1593.75 | 127108.26 | 02-FEB-07:00 |
March | 577596.87 | 2857611.88 | 10-MAR-13:05 | 26.06 | 22.36 | 509.71 | 63523.21 | 27-MAR-03:50 |
April | 1127095.56 | 4924386.26 | 18-APR-14:05 | 29.65 | 25.74 | 591.45 | 78636.76 | 11-APR-04:00 |
May | 2338054.74 | 6661613.09 | 17-MAY-15:40 | 32.67 | 28.05 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3406299.22 | 7656341.91 | 22-JUN-15:40 | 34.40 | 29.18 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4151761.76 | 7666823.58 | 08-JUL-05:03 | 34.42 | 29.19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 4180066.03 | 7654718.71 | 28-AUG-05:03 | 34.40 | 29.18 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 3036043.28 | 7113354.40 | 14-SEP-14:40 | 33.46 | 28.88 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 978313.93 | 4507970.50 | 04-OCT-11:00 | 28.93 | 25.26 | 85.47 | 31958.41 | 15-OCT-07:30 |
November | 443614.13 | 2635522.63 | 09-NOV-14:05 | 25.68 | 21.40 | 489.93 | 77365.40 | 27-NOV-05:55 |
December | 175174.80 | 967609.57 | 01-DEC-15:05 | 24.46 | 21.10 | 3251.96 | 146818.92 | 20-DEC-07:20 |
Annual Sum or Average | 1741997.50 | 933.99 | ||||||
Minimum of Months | 124579.43 | 846826.97 | 24.04 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 4180066.03 | 7666823.58 | 34.42 | 29.19 | 4663.87 | 146818.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.355809E+11 | 0.523695E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.576291E+11 | 0.587404E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.125262E+12 | 0.111436E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.210107E+12 | 0.187696E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.281537E+12 | 0.227360E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.322872E+12 | 0.250366E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.360660E+12 | 0.246738E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.378287E+12 | 0.270280E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.290015E+12 | 0.197306E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.171191E+12 | 0.128935E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.953984E+11 | 0.810068E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.566276E+11 | 0.676326E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.238517E+13 | 0.187987E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.355809E+11 | 0.523695E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.378287E+12 | 0.270280E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.215781E+12 | 0.520129E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.396255E+12 | 0.398630E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.913988E+12 | 0.695995E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.148381E+13 | 0.985253E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217174E+13 | 0.121567E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.245488E+13 | 0.121550E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.266632E+13 | 0.107224E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.264440E+13 | 0.109366E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.204257E+13 | 0.860852E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125669E+13 | 0.732502E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.689374E+12 | 0.496879E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.297936E+12 | 0.391719E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172337E+14 | 0.967902E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.215781E+12 | 0.391719E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266632E+13 | 0.121567E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.172890E+11 | 0.102400E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.358521E+11 | 0.449204E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.930587E+11 | 0.658165E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.161503E+12 | 0.104999E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.238722E+12 | 0.133915E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.267239E+12 | 0.134755E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.283854E+12 | 0.115613E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278032E+12 | 0.112985E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.212651E+12 | 0.885852E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127058E+12 | 0.704967E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.634742E+11 | 0.447742E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.227096E+11 | 0.556648E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180144E+13 | 0.107493E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.172890E+11 | 0.447742E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.283854E+12 | 0.134755E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.471565E+11 | 0.125944E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.505305E+11 | 0.117518E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.605110E+11 | 0.120129E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.193734E+11 | 0.274314E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.672671E+11 | 0.902377E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.730658E+11 | 0.152265E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.587673E+11 | 0.158989E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.376672E+12 | 0.792515E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.730658E+11 | 0.158989E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.434733E+12 | 0.207003E+12 | 0.00 | 4.55 |
February | 0.00 | 0.00 | 0.677795E+12 | 0.246107E+12 | 0.00 | 5.19 |
March | 0.00 | 0.00 | 0.108266E+13 | 0.350243E+12 | 0.00 | 3.44 |
April | 0.00 | 0.00 | 0.140747E+13 | 0.452546E+12 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.521515E+12 | 0.252430E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.843414E+12 | 0.334422E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.120146E+13 | 0.418962E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.151291E+13 | 0.484292E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.509323E+12 | 0.233013E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.799779E+12 | 0.294841E+12 | 0.00 | 0.67 |
November | 0.00 | 0.00 | 0.104208E+13 | 0.332269E+12 | 0.00 | 6.03 |
December | 0.00 | 0.00 | 0.136286E+13 | 0.396024E+12 | 0.00 | 14.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.113960E+14 | 0.400215E+13 | 0.00 | 34.41 |
Minimum of Months | 0.00 | 0.00 | 0.434733E+12 | 0.207003E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.151291E+13 | 0.484292E+12 | 0.00 | 14.20 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.581000E+10 | 0.257500E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.117298E+11 | 0.357370E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.205410E+11 | 0.573414E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.278477E+11 | 0.802748E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.103192E+11 | 0.416256E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.172083E+11 | 0.587543E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.248236E+11 | 0.757765E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.305491E+11 | 0.868661E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.100557E+11 | 0.378224E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152673E+11 | 0.484095E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.193675E+11 | 0.522547E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248612E+11 | 0.592192E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218380E+12 | 0.659831E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.581000E+10 | 0.257500E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.305491E+11 | 0.868661E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.388009E+11 | 0.214883E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103525E+12 | 0.325523E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193084E+12 | 0.540090E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.261963E+12 | 0.754368E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.940637E+11 | 0.385451E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.160175E+12 | 0.549012E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.231445E+12 | 0.707728E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.286242E+12 | 0.813174E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.905226E+11 | 0.347699E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142038E+12 | 0.453198E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179154E+12 | 0.487303E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224705E+12 | 0.543445E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200572E+13 | 0.612187E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.388009E+11 | 0.214883E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.286242E+12 | 0.813174E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.254612E+10 | 0.191236E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.964669E+10 | 0.315582E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191779E+11 | 0.542143E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.264930E+11 | 0.767227E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.974562E+10 | 0.396872E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.163432E+11 | 0.560875E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.234956E+11 | 0.720824E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.291208E+11 | 0.831572E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.921173E+10 | 0.353891E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.141730E+11 | 0.456274E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173994E+11 | 0.482308E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211993E+11 | 0.527125E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198552E+12 | 0.614593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.254612E+10 | 0.191236E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.291208E+11 | 0.831572E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.434570E+10 | 0.355809E+11 | 0.891247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573785E+10 | 0.576291E+11 | 0.136196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111436E+11 | 0.125262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187696E+11 | 0.210107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227360E+11 | 0.281537E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250366E+11 | 0.322872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.246738E+11 | 0.360660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270280E+11 | 0.378287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197306E+11 | 0.290015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128935E+11 | 0.171191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810058E+10 | 0.953984E+11 | 98168.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658089E+10 | 0.566276E+11 | 0.182366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186777E+12 | 0.238517E+13 | 0.120991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.434570E+10 | 0.355809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270280E+11 | 0.378287E+12 | 0.891247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.286965E+11 | 0.215781E+12 | 0.233164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366361E+11 | 0.396255E+12 | 0.322695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.695995E+11 | 0.913988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.985253E+11 | 0.148381E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121567E+12 | 0.217174E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121550E+12 | 0.245488E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107224E+12 | 0.266632E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109366E+12 | 0.264440E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860852E+11 | 0.204257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.732502E+11 | 0.125669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496291E+11 | 0.689374E+12 | 58833191.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331752E+11 | 0.297936E+12 | 0.599665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935303E+12 | 0.172337E+14 | 0.325988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.286965E+11 | 0.215781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121567E+12 | 0.266632E+13 | 0.233164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270936E+10 | 0.172890E+11 | 0.753069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322207E+10 | 0.358521E+11 | 0.126998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.658163E+10 | 0.930587E+11 | 26762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104999E+11 | 0.161503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133915E+11 | 0.238722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134755E+11 | 0.267239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115613E+11 | 0.283854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112985E+11 | 0.278032E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.885852E+10 | 0.212651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704967E+10 | 0.127058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436589E+10 | 0.634742E+11 | 0.111526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278762E+10 | 0.227096E+11 | 0.277886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958014E+11 | 0.180144E+13 | 0.116911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.270936E+10 | 0.172890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134755E+11 | 0.283854E+12 | 0.753069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125520E+11 | 0.471606E+11 | 42406882.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117480E+11 | 0.505305E+11 | 3857560.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120129E+11 | 0.605110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274314E+10 | 0.193734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902377E+10 | 0.672671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152265E+11 | 0.730658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158925E+11 | 0.587673E+11 | 6439990.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.791988E+11 | 0.376676E+12 | 52704434.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158925E+11 | 0.730658E+11 | 42406882.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111101E+12 | 0.351062E+12 | 0.00 | 0.00 | 0.00 | 0.121762E+11 | 0.00 | 0.00 |
February | 0.100349E+12 | 0.545992E+12 | 0.00 | 0.00 | 0.00 | 0.138921E+11 | 0.00 | 0.00 |
March | 0.111101E+12 | 0.852777E+12 | 0.00 | 0.00 | 0.00 | 0.921685E+10 | 0.00 | 0.00 |
April | 0.107517E+12 | 0.106327E+13 | 0.00 | 0.00 | 0.00 | 0.822243E+09 | 0.00 | 0.00 |
May | 0.111101E+12 | 0.380202E+12 | 0.00 | 0.00 | 0.00 | 16629515.12 | 0.00 | 0.00 |
June | 0.107517E+12 | 0.616508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111101E+12 | 0.893594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111101E+12 | 0.113972E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107517E+12 | 0.383826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111101E+12 | 0.617852E+12 | 0.00 | 0.00 | 0.00 | 0.180538E+10 | 0.00 | 0.00 |
November | 0.107517E+12 | 0.833539E+12 | 0.00 | 0.00 | 0.00 | 0.161367E+11 | 0.00 | 0.00 |
December | 0.111101E+12 | 0.111612E+13 | 0.00 | 0.00 | 0.00 | 0.380100E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.130812E+13 | 0.879446E+13 | 0.00 | 0.00 | 0.00 | 0.920762E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100349E+12 | 0.351062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111101E+12 | 0.113972E+13 | 0.00 | 0.00 | 0.00 | 0.380100E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144573E+10 | 0.468073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130582E+10 | 0.946194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144573E+10 | 0.162526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139909E+10 | 0.212193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144573E+10 | 0.760235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139909E+10 | 0.127319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144573E+10 | 0.186917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144573E+10 | 0.233082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139909E+10 | 0.767257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144573E+10 | 0.118721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139909E+10 | 0.155412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144573E+10 | 0.203850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170223E+11 | 0.169419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130582E+10 | 0.468073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144573E+10 | 0.233082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138026E+11 | 0.311152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124668E+11 | 0.834391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138026E+11 | 0.152878E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133573E+11 | 0.199884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138026E+11 | 0.693212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133573E+11 | 0.118631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138026E+11 | 0.174474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138026E+11 | 0.218727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133573E+11 | 0.691101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138026E+11 | 0.110521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133573E+11 | 0.143781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138026E+11 | 0.184163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162514E+12 | 0.155604E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124668E+11 | 0.311152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138026E+11 | 0.218727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139509E+10 | 0.202886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126008E+10 | 0.775095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139509E+10 | 0.151516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135009E+10 | 0.201709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139509E+10 | 0.717200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135009E+10 | 0.120845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139509E+10 | 0.176825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139509E+10 | 0.222001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135009E+10 | 0.702291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139509E+10 | 0.110053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135009E+10 | 0.139264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139509E+10 | 0.173232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164261E+11 | 0.153519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126008E+10 | 0.202886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139509E+10 | 0.222001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.434570E+10 | 0.00 | 0.355809E+11 | 0.00 | 0.00 | 0.891247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573785E+10 | 0.00 | 0.576291E+11 | 0.00 | 0.00 | 0.136196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111436E+11 | 0.00 | 0.125262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187696E+11 | 0.00 | 0.210107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227360E+11 | 0.00 | 0.281537E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250366E+11 | 0.00 | 0.322872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.246738E+11 | 0.00 | 0.360660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270280E+11 | 0.00 | 0.378287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197306E+11 | 0.00 | 0.290015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128935E+11 | 0.00 | 0.171191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810058E+10 | 0.00 | 0.953984E+11 | 0.00 | 0.00 | 98168.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658089E+10 | 0.00 | 0.566276E+11 | 0.00 | 0.00 | 0.182366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186777E+12 | 0.00 | 0.238517E+13 | 0.00 | 0.00 | 0.120991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.434570E+10 | 0.00 | 0.355809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270280E+11 | 0.00 | 0.378287E+12 | 0.00 | 0.00 | 0.891247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.286965E+11 | 0.00 | 0.215781E+12 | 0.00 | 0.00 | 0.233164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366361E+11 | 0.00 | 0.396255E+12 | 0.00 | 0.00 | 0.322695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.695995E+11 | 0.00 | 0.913988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.985253E+11 | 0.00 | 0.148381E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121567E+12 | 0.00 | 0.217174E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121550E+12 | 0.00 | 0.245488E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107224E+12 | 0.00 | 0.266632E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109366E+12 | 0.00 | 0.264440E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860852E+11 | 0.00 | 0.204257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.732502E+11 | 0.00 | 0.125669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496291E+11 | 0.00 | 0.689374E+12 | 0.00 | 0.00 | 58833191.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331752E+11 | 0.00 | 0.297936E+12 | 0.00 | 0.00 | 0.599665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935303E+12 | 0.00 | 0.172337E+14 | 0.00 | 0.00 | 0.325988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.286965E+11 | 0.00 | 0.215781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121567E+12 | 0.00 | 0.266632E+13 | 0.00 | 0.00 | 0.233164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.270936E+10 | 0.00 | 0.172890E+11 | 0.00 | 0.00 | 0.753069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322207E+10 | 0.00 | 0.358521E+11 | 0.00 | 0.00 | 0.126998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.658163E+10 | 0.00 | 0.930587E+11 | 0.00 | 0.00 | 26762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104999E+11 | 0.00 | 0.161503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133915E+11 | 0.00 | 0.238722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134755E+11 | 0.00 | 0.267239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115613E+11 | 0.00 | 0.283854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112985E+11 | 0.00 | 0.278032E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.885852E+10 | 0.00 | 0.212651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.704967E+10 | 0.00 | 0.127058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436589E+10 | 0.00 | 0.634742E+11 | 0.00 | 0.00 | 0.111526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278762E+10 | 0.00 | 0.227096E+11 | 0.00 | 0.00 | 0.277886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958014E+11 | 0.00 | 0.180144E+13 | 0.00 | 0.00 | 0.116911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.270936E+10 | 0.00 | 0.172890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134755E+11 | 0.00 | 0.283854E+12 | 0.00 | 0.00 | 0.753069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125520E+11 | 0.00 | 0.471565E+11 | 0.00 | 0.00 | 42406882.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117480E+11 | 0.00 | 0.505305E+11 | 0.00 | 0.00 | 3857560.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120129E+11 | 0.00 | 0.605110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274314E+10 | 0.00 | 0.193734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902377E+10 | 0.00 | 0.672671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152265E+11 | 0.00 | 0.730658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158925E+11 | 0.00 | 0.587673E+11 | 0.00 | 0.00 | 6439990.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.791988E+11 | 0.00 | 0.376672E+12 | 0.00 | 0.00 | 52704434.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158925E+11 | 0.00 | 0.730658E+11 | 0.00 | 0.00 | 42406882.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111101E+12 | 0.00 | 0.434733E+12 | 0.00 | 0.836711E+11 | 0.00 | 0.00 | 0.00 | 0.122311E+11 | 0.00 | 0.00 | 0.00 |
February | 0.100349E+12 | 0.00 | 0.677795E+12 | 0.00 | 0.131803E+12 | 0.00 | 0.00 | 0.00 | 0.139547E+11 | 0.00 | 0.00 | 0.00 |
March | 0.111101E+12 | 0.00 | 0.108266E+13 | 0.00 | 0.229884E+12 | 0.00 | 0.00 | 0.00 | 0.925834E+10 | 0.00 | 0.00 | 0.00 |
April | 0.107517E+12 | 0.00 | 0.140747E+13 | 0.00 | 0.344204E+12 | 0.00 | 0.00 | 0.00 | 0.825944E+09 | 0.00 | 0.00 | 0.00 |
May | 0.111101E+12 | 0.00 | 0.521515E+12 | 0.00 | 0.141313E+12 | 0.00 | 0.00 | 0.00 | 16704371.31 | 0.00 | 0.00 | 0.00 |
June | 0.107517E+12 | 0.00 | 0.843414E+12 | 0.00 | 0.226906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111101E+12 | 0.00 | 0.120146E+13 | 0.00 | 0.307862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111101E+12 | 0.00 | 0.151291E+13 | 0.00 | 0.373191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107517E+12 | 0.00 | 0.509323E+12 | 0.00 | 0.125497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111101E+12 | 0.00 | 0.799779E+12 | 0.00 | 0.181927E+12 | 0.00 | 0.00 | 0.00 | 0.181351E+10 | 0.00 | 0.00 | 0.00 |
November | 0.107517E+12 | 0.00 | 0.104208E+13 | 0.00 | 0.208543E+12 | 0.00 | 0.00 | 0.00 | 0.162094E+11 | 0.00 | 0.00 | 0.00 |
December | 0.111101E+12 | 0.00 | 0.136286E+13 | 0.00 | 0.246742E+12 | 0.00 | 0.00 | 0.00 | 0.381811E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130812E+13 | 0.00 | 0.113960E+14 | 0.00 | 0.260154E+13 | 0.00 | 0.00 | 0.00 | 0.924907E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100349E+12 | 0.00 | 0.434733E+12 | 0.00 | 0.836711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111101E+12 | 0.00 | 0.151291E+13 | 0.00 | 0.373191E+12 | 0.00 | 0.00 | 0.00 | 0.381811E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144573E+10 | 0.00 | 0.581000E+10 | 0.00 | 0.112927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130582E+10 | 0.00 | 0.117298E+11 | 0.00 | 0.226788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144573E+10 | 0.00 | 0.205410E+11 | 0.00 | 0.428841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139909E+10 | 0.00 | 0.278477E+11 | 0.00 | 0.662839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144573E+10 | 0.00 | 0.103192E+11 | 0.00 | 0.271683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139909E+10 | 0.00 | 0.172083E+11 | 0.00 | 0.447634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144573E+10 | 0.00 | 0.248236E+11 | 0.00 | 0.613192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144573E+10 | 0.00 | 0.305491E+11 | 0.00 | 0.724088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139909E+10 | 0.00 | 0.100557E+11 | 0.00 | 0.238315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144573E+10 | 0.00 | 0.152673E+11 | 0.00 | 0.339522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139909E+10 | 0.00 | 0.193675E+11 | 0.00 | 0.382638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144573E+10 | 0.00 | 0.248612E+11 | 0.00 | 0.447620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170223E+11 | 0.00 | 0.218380E+12 | 0.00 | 0.489609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130582E+10 | 0.00 | 0.581000E+10 | 0.00 | 0.112927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144573E+10 | 0.00 | 0.305491E+11 | 0.00 | 0.724088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138026E+11 | 0.00 | 0.388009E+11 | 0.00 | 0.768575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124668E+11 | 0.00 | 0.103525E+12 | 0.00 | 0.200854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138026E+11 | 0.00 | 0.193084E+12 | 0.00 | 0.402064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133573E+11 | 0.00 | 0.261963E+12 | 0.00 | 0.620794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138026E+11 | 0.00 | 0.940637E+11 | 0.00 | 0.247425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133573E+11 | 0.00 | 0.160175E+12 | 0.00 | 0.415439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138026E+11 | 0.00 | 0.231445E+12 | 0.00 | 0.569702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138026E+11 | 0.00 | 0.286242E+12 | 0.00 | 0.675149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133573E+11 | 0.00 | 0.905226E+11 | 0.00 | 0.214125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138026E+11 | 0.00 | 0.142038E+12 | 0.00 | 0.315173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133573E+11 | 0.00 | 0.179154E+12 | 0.00 | 0.353730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138026E+11 | 0.00 | 0.224705E+12 | 0.00 | 0.405419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162514E+12 | 0.00 | 0.200572E+13 | 0.00 | 0.449673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124668E+11 | 0.00 | 0.388009E+11 | 0.00 | 0.768575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138026E+11 | 0.00 | 0.286242E+12 | 0.00 | 0.675149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139509E+10 | 0.00 | 0.254612E+10 | 0.00 | 0.517262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126008E+10 | 0.00 | 0.964669E+10 | 0.00 | 0.189573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139509E+10 | 0.00 | 0.191779E+11 | 0.00 | 0.402634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135009E+10 | 0.00 | 0.264930E+11 | 0.00 | 0.632218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139509E+10 | 0.00 | 0.974562E+10 | 0.00 | 0.257362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135009E+10 | 0.00 | 0.163432E+11 | 0.00 | 0.425866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139509E+10 | 0.00 | 0.234956E+11 | 0.00 | 0.581315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139509E+10 | 0.00 | 0.291208E+11 | 0.00 | 0.692063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135009E+10 | 0.00 | 0.921173E+10 | 0.00 | 0.218882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139509E+10 | 0.00 | 0.141730E+11 | 0.00 | 0.316764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135009E+10 | 0.00 | 0.173994E+11 | 0.00 | 0.347299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139509E+10 | 0.00 | 0.211993E+11 | 0.00 | 0.387615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164261E+11 | 0.00 | 0.198552E+12 | 0.00 | 0.450332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126008E+10 | 0.00 | 0.254612E+10 | 0.00 | 0.517262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139509E+10 | 0.00 | 0.291208E+11 | 0.00 | 0.692063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.114048E+09 | 0.00 | 0.00 | 0.245503E+11 | 0.00 | 0.36 |
February | 0.00 | 51906479.50 | 0.00 | 0.101822E+09 | 0.00 | 0.00 | 0.150568E+11 | 0.00 | 0.36 |
March | 0.00 | 0.814596E+09 | 0.00 | 93276222.17 | 0.00 | 0.00 | 0.717194E+10 | 0.00 | 0.29 |
April | 0.00 | 0.732918E+09 | 0.00 | 25816918.41 | 0.00 | 0.00 | 0.100547E+10 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.585748E+10 | 0.00 | 83464099.88 | 0.00 | 0.00 | 0.239052E+10 | 0.00 | 0.20 |
November | 0.00 | 0.269989E+09 | 0.00 | 0.131437E+09 | 0.00 | 0.00 | 0.114583E+11 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.00 | 0.129116E+09 | 0.00 | 0.00 | 0.222907E+11 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.772689E+10 | 0.00 | 0.678980E+09 | 0.00 | 0.00 | 0.839240E+11 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.585748E+10 | 0.00 | 0.131437E+09 | 0.00 | 0.00 | 0.245503E+11 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130206E+10 | 0.00 | 0.00 | 75750668.46 | 0.00 | 0.00 | 0.254418E+11 | 0.00 | 0.38 |
February | 0.114192E+10 | 0.00 | 0.00 | 83298485.75 | 795918.61 | 0.00 | 0.168607E+11 | 0.00 | 0.38 |
March | 0.184699E+10 | 0.122365E+10 | 0.00 | 94964034.00 | 0.339448E+09 | 0.00 | 0.884521E+10 | 0.00 | 0.41 |
April | 0.892573E+09 | 0.776773E+10 | 0.00 | 34598819.46 | 0.304410E+10 | 0.00 | 0.848043E+09 | 0.00 | 0.45 |
May | 38889936.19 | 0.267443E+11 | 0.00 | 2791318.94 | 0.909555E+10 | 0.00 | 19018270.17 | 0.00 | 0.45 |
June | 0.00 | 0.423486E+11 | 0.00 | 0.00 | 0.146869E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.605197E+11 | 0.00 | 0.00 | 0.194923E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.656133E+11 | 0.00 | 0.00 | 0.183704E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.449375E+11 | 0.00 | 0.00 | 0.150374E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.792660E+09 | 0.828416E+10 | 0.00 | 43774364.63 | 0.168485E+10 | 0.00 | 0.248506E+10 | 0.00 | 0.41 |
November | 0.150321E+10 | 0.177746E+09 | 0.00 | 0.101661E+09 | 75480950.08 | 0.00 | 0.126863E+11 | 0.00 | 0.39 |
December | 0.146655E+10 | 0.00 | 0.00 | 0.100599E+09 | 0.00 | 0.00 | 0.245692E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.898485E+10 | 0.257617E+12 | 0.00 | 0.537438E+09 | 0.818272E+11 | 0.00 | 0.917553E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.184699E+10 | 0.656133E+11 | 0.00 | 0.101661E+09 | 0.194923E+11 | 0.00 | 0.254418E+11 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.855837E+11 | 0.00 | 0.00 | 0.337031E+09 | 0.00 | 40990790.01 | 0.130448E+12 | 0.00 | 0.34 |
February | 0.204963E+11 | 0.00 | 0.00 | 0.525565E+09 | 0.112220E+09 | 0.00 | 0.130941E+12 | 0.00 | 0.36 |
March | 0.714933E+10 | 0.108854E+11 | 0.00 | 0.712856E+09 | 0.365343E+10 | 0.00 | 0.819859E+11 | 0.00 | 0.36 |
April | 0.257149E+10 | 0.622804E+11 | 0.00 | 0.211631E+09 | 0.367019E+11 | 0.00 | 0.663968E+10 | 0.00 | 0.39 |
May | 0.319884E+09 | 0.216682E+12 | 0.00 | 4549876.64 | 0.105254E+12 | 0.00 | 0.120779E+09 | 0.00 | 0.42 |
June | 0.00 | 0.327097E+12 | 0.00 | 0.00 | 0.174651E+12 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.416159E+12 | 0.00 | 0.00 | 0.281854E+12 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.475034E+12 | 0.00 | 0.00 | 0.217382E+12 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.333168E+12 | 0.00 | 0.00 | 0.146840E+12 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.257636E+10 | 0.713930E+11 | 0.00 | 0.291170E+09 | 0.144412E+11 | 0.00 | 0.237221E+11 | 0.00 | 0.35 |
November | 0.108674E+11 | 0.164866E+10 | 0.00 | 0.680868E+09 | 0.111660E+10 | 0.00 | 0.106914E+12 | 0.00 | 0.36 |
December | 0.365545E+11 | 0.00 | 0.00 | 0.475881E+09 | 22715977.95 | 0.00 | 0.166731E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.166119E+12 | 0.191435E+13 | 0.00 | 0.323955E+10 | 0.982029E+12 | 40990790.01 | 0.647503E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.855837E+11 | 0.475034E+12 | 0.00 | 0.712856E+09 | 0.281854E+12 | 40990790.01 | 0.166731E+12 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130348E+11 | 0.00 | 0.00 | 12965357.74 | 0.00 | 0.450136E+09 | 0.527725E+10 | 0.00 | 0.32 |
February | 0.529435E+10 | 0.00 | 0.00 | 32408648.35 | 497365.49 | 0.00 | 0.774897E+10 | 0.00 | 0.33 |
March | 0.106299E+10 | 0.791117E+09 | 0.00 | 61049084.54 | 0.222516E+09 | 0.00 | 0.690930E+10 | 0.00 | 0.34 |
April | 0.241996E+09 | 0.556142E+10 | 0.00 | 25115514.27 | 0.318630E+10 | 0.00 | 0.724731E+09 | 0.00 | 0.39 |
May | 28160450.68 | 0.213738E+11 | 0.00 | 418468.07 | 0.947255E+10 | 0.00 | 10067892.83 | 0.00 | 0.42 |
June | 0.00 | 0.327770E+11 | 0.00 | 0.00 | 0.164364E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.419779E+11 | 0.00 | 0.00 | 0.269008E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.474533E+11 | 0.00 | 0.00 | 0.214319E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.328677E+11 | 0.00 | 0.00 | 0.143386E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.220568E+09 | 0.639747E+10 | 0.00 | 24830247.31 | 0.120689E+10 | 0.00 | 0.184724E+10 | 0.00 | 0.34 |
November | 0.292146E+10 | 52911681.28 | 0.00 | 49440493.61 | 67299752.99 | 0.00 | 0.682272E+10 | 0.00 | 0.33 |
December | 0.102355E+11 | 0.00 | 0.00 | 20236743.64 | 1143539.04 | 0.00 | 0.656679E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.330398E+11 | 0.189253E+12 | 0.00 | 0.226465E+09 | 0.932649E+11 | 0.450136E+09 | 0.359071E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.130348E+11 | 0.474533E+11 | 0.00 | 61049084.54 | 0.269008E+11 | 0.450136E+09 | 0.774897E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177807E+10 | 0.00 | 0.00 | 2040534.14 | 0.00 | 0.00 | 0.513620E+09 | 0.00 | 0.26 |
February | 0.819594E+09 | 0.00 | 0.00 | 5248426.95 | 99908.69 | 0.00 | 0.784793E+09 | 0.00 | 0.29 |
March | 0.352640E+09 | 0.227270E+09 | 0.00 | 9765264.11 | 37200442.79 | 0.00 | 0.804694E+09 | 0.00 | 0.42 |
April | 0.110866E+09 | 0.181802E+10 | 0.00 | 5088620.26 | 0.185466E+09 | 0.00 | 0.111147E+09 | 0.00 | 0.59 |
May | 1347700.63 | 0.671319E+10 | 0.00 | 577216.96 | 0.390484E+09 | 0.00 | 7216805.21 | 0.00 | 0.68 |
June | 0.00 | 0.106847E+11 | 0.00 | 0.00 | 0.564188E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.147213E+11 | 0.00 | 0.00 | 0.644344E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.141823E+11 | 0.00 | 0.00 | 0.766056E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.855630E+10 | 0.00 | 0.00 | 0.109834E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.124048E+09 | 0.140211E+10 | 0.00 | 3944955.50 | 0.181032E+09 | 0.00 | 0.209522E+09 | 0.00 | 0.45 |
November | 0.466781E+09 | 26786911.89 | 0.00 | 8007825.71 | 9474842.11 | 0.00 | 0.777569E+09 | 0.00 | 0.31 |
December | 0.126917E+10 | 0.00 | 0.00 | 4297623.57 | 0.00 | 0.00 | 0.755900E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.492251E+10 | 0.583320E+11 | 0.00 | 38970467.21 | 0.387669E+10 | 0.00 | 0.396446E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.177807E+10 | 0.147213E+11 | 0.00 | 9765264.11 | 0.109834E+10 | 0.00 | 0.804694E+09 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.870205E+09 | 0.00 | 0.00 | 3218563.18 | 0.00 | 0.00 | 0.898663E+09 | 0.00 | 0.31 |
February | 0.417240E+09 | 0.00 | 0.00 | 5824221.41 | 64140.05 | 0.00 | 0.944938E+09 | 0.00 | 0.38 |
March | 0.214238E+09 | 0.186448E+09 | 0.00 | 9402276.39 | 17259001.91 | 0.00 | 0.764808E+09 | 0.00 | 0.54 |
April | 63249910.05 | 0.154861E+10 | 0.00 | 5293023.82 | 90803268.60 | 0.00 | 0.122261E+09 | 0.00 | 0.74 |
May | 531783.43 | 0.557805E+10 | 0.00 | 449754.44 | 0.165976E+09 | 0.00 | 5527116.36 | 0.00 | 0.87 |
June | 0.00 | 0.788064E+10 | 0.00 | 0.00 | 0.335891E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.00 | 0.101219E+11 | 0.00 | 0.00 | 0.530357E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.937115E+10 | 0.00 | 0.00 | 0.693255E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.669921E+10 | 0.00 | 0.00 | 0.453507E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 70543695.87 | 0.113294E+10 | 0.00 | 4205036.46 | 94975064.14 | 0.00 | 0.205019E+09 | 0.00 | 0.56 |
November | 0.281845E+09 | 20137906.66 | 0.00 | 7373077.76 | 6082722.27 | 0.00 | 0.723530E+09 | 0.00 | 0.39 |
December | 0.752084E+09 | 0.00 | 0.00 | 3977903.69 | 0.00 | 0.00 | 0.733545E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.266994E+10 | 0.425391E+11 | 0.00 | 39743857.16 | 0.238817E+10 | 0.00 | 0.439829E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.870205E+09 | 0.101219E+11 | 0.00 | 9402276.39 | 0.693255E+09 | 0.00 | 0.944938E+09 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.993363E+09 | 0.00 | 0.00 | 12338358.34 | 0.00 | 2840532.02 | 0.314705E+10 | 0.00 | 0.53 |
February | 0.573282E+09 | 196827.00 | 0.00 | 16661112.23 | 18773.04 | 0.00 | 0.216358E+10 | 0.00 | 0.56 |
March | 0.290328E+09 | 0.415299E+09 | 0.00 | 17310842.75 | 15657341.68 | 0.00 | 0.135799E+10 | 0.00 | 0.63 |
April | 0.106034E+09 | 0.233121E+10 | 0.00 | 6497456.08 | 0.119503E+09 | 0.00 | 0.133969E+09 | 0.00 | 0.70 |
May | 2208080.69 | 0.685845E+10 | 0.00 | 539155.13 | 0.392306E+09 | 0.00 | 6183193.01 | 0.00 | 0.69 |
June | 0.00 | 0.102157E+11 | 0.00 | 0.00 | 0.680980E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.139485E+11 | 0.00 | 0.00 | 0.950456E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.140866E+11 | 0.00 | 0.00 | 0.101677E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.101542E+11 | 0.00 | 0.00 | 0.810218E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 91008619.45 | 0.238868E+10 | 0.00 | 9499028.53 | 84542366.93 | 0.00 | 0.367625E+09 | 0.00 | 0.73 |
November | 0.260526E+09 | 80788092.05 | 0.00 | 26909661.90 | 2340026.21 | 0.00 | 0.211694E+10 | 0.00 | 0.68 |
December | 0.685872E+09 | 0.00 | 0.00 | 17198108.52 | 0.00 | 0.00 | 0.305456E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.300262E+10 | 0.604797E+11 | 0.00 | 0.106954E+09 | 0.407279E+10 | 2840532.02 | 0.123479E+11 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.993363E+09 | 0.140866E+11 | 0.00 | 26909661.90 | 0.101677E+10 | 2840532.02 | 0.314705E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573591E+09 | 0.00 | 0.00 | 5662932.85 | 0.00 | 0.00 | 0.158064E+10 | 0.00 | 0.42 |
February | 0.170953E+09 | 199649.54 | 0.00 | 10605836.23 | 5576.03 | 0.00 | 0.168867E+10 | 0.00 | 0.58 |
March | 77879676.02 | 0.343317E+09 | 0.00 | 16560519.73 | 2633385.43 | 0.00 | 0.145301E+10 | 0.00 | 0.84 |
April | 11088557.06 | 0.231901E+10 | 0.00 | 8989796.17 | 16931767.22 | 0.00 | 0.236365E+09 | 0.00 | 1.08 |
May | 498421.41 | 0.590546E+10 | 0.00 | 530660.79 | 0.126293E+09 | 0.00 | 6445545.71 | 0.00 | 0.90 |
June | 0.00 | 0.943760E+10 | 0.00 | 0.00 | 0.193573E+09 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 0.00 | 0.128370E+11 | 0.00 | 0.00 | 0.193093E+09 | 0.00 | 0.00 | 0.00 | 0.91 |
August | 0.00 | 0.133135E+11 | 0.00 | 0.00 | 0.126402E+09 | 0.00 | 0.00 | 0.00 | 0.91 |
September | 0.00 | 0.697463E+10 | 0.00 | 0.00 | 0.388431E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 42425361.07 | 0.155253E+10 | 0.00 | 6214327.05 | 34357964.40 | 0.00 | 0.319253E+09 | 0.00 | 0.73 |
November | 81861909.45 | 52431794.63 | 0.00 | 16048025.20 | 822970.65 | 0.00 | 0.166852E+10 | 0.00 | 0.69 |
December | 0.121608E+09 | 0.00 | 0.00 | 13043081.03 | 0.00 | 0.00 | 0.288861E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.107991E+10 | 0.527356E+11 | 0.00 | 77655179.04 | 0.108254E+10 | 0.00 | 0.984151E+10 | 0.00 | 0.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.573591E+09 | 0.133135E+11 | 0.00 | 16560519.73 | 0.388431E+09 | 0.00 | 0.288861E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179828E+11 | 0.00 | 0.00 | 1605569.47 | 0.00 | 0.498805E+10 | 0.476315E+09 | 0.00 | 0.28 |
February | 0.108678E+11 | 0.00 | 0.00 | 20828710.98 | 14034385.78 | 0.790736E+09 | 0.322456E+10 | 0.00 | 0.28 |
March | 0.358037E+10 | 0.220923E+10 | 0.00 | 64230685.44 | 0.456303E+09 | 0.00 | 0.586783E+10 | 0.00 | 0.37 |
April | 0.346480E+09 | 0.174456E+11 | 0.00 | 32513188.41 | 0.363992E+10 | 0.00 | 0.901123E+09 | 0.00 | 0.58 |
May | 28269238.46 | 0.699332E+11 | 0.00 | 2503339.08 | 0.724080E+10 | 0.00 | 52187633.20 | 0.00 | 0.76 |
June | 0.00 | 0.109924E+12 | 0.00 | 0.00 | 0.117309E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.141094E+12 | 0.00 | 0.00 | 0.181804E+11 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.133345E+12 | 0.00 | 0.00 | 0.177753E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.780952E+11 | 0.00 | 0.00 | 0.144469E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.119205E+10 | 0.131277E+11 | 0.00 | 22189040.80 | 0.173517E+10 | 0.00 | 0.133397E+10 | 0.00 | 0.41 |
November | 0.785704E+10 | 0.229876E+09 | 0.00 | 38688066.76 | 0.135679E+09 | 0.00 | 0.344908E+10 | 0.00 | 0.30 |
December | 0.180556E+11 | 0.00 | 0.00 | 3789115.11 | 2840901.67 | 0.101935E+10 | 0.122751E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.599104E+11 | 0.565403E+12 | 0.00 | 0.186348E+09 | 0.753583E+11 | 0.679813E+10 | 0.165326E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.180556E+11 | 0.141094E+12 | 0.00 | 64230685.44 | 0.181804E+11 | 0.498805E+10 | 0.586783E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.854578E+10 | 0.00 | 0.00 | 11886430.39 | 0.00 | 0.180827E+10 | 0.384757E+10 | 0.00 | 0.26 |
February | 0.471377E+10 | 0.00 | 0.00 | 39883249.69 | 9041780.48 | 76061206.46 | 0.740964E+10 | 0.00 | 0.37 |
March | 0.151945E+10 | 0.213489E+10 | 0.00 | 83298486.79 | 0.174150E+09 | 0.00 | 0.810578E+10 | 0.00 | 0.57 |
April | 0.137944E+09 | 0.178060E+11 | 0.00 | 42627853.10 | 0.156647E+10 | 0.00 | 0.119344E+10 | 0.00 | 0.86 |
May | 13594753.43 | 0.614037E+11 | 0.00 | 2158653.02 | 0.308948E+10 | 0.00 | 44395210.26 | 0.00 | 1.00 |
June | 0.00 | 0.866207E+11 | 0.00 | 0.00 | 0.527676E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
July | 0.00 | 0.106937E+12 | 0.00 | 0.00 | 0.860036E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.987303E+11 | 0.00 | 0.00 | 0.916155E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.00 | 0.634592E+11 | 0.00 | 0.00 | 0.706376E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.409668E+09 | 0.117917E+11 | 0.00 | 32619291.47 | 0.720134E+09 | 0.00 | 0.210138E+10 | 0.00 | 0.57 |
November | 0.341595E+10 | 0.214931E+09 | 0.00 | 55782985.98 | 87412253.31 | 0.00 | 0.648632E+10 | 0.00 | 0.41 |
December | 0.841151E+10 | 0.00 | 0.00 | 17881913.43 | 1830276.70 | 0.323706E+09 | 0.429727E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.271677E+11 | 0.449098E+12 | 0.00 | 0.286139E+09 | 0.357510E+11 | 0.220803E+10 | 0.334858E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.854578E+10 | 0.106937E+12 | 0.00 | 83298486.79 | 0.916155E+10 | 0.180827E+10 | 0.810578E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108013E+11 | 0.00 | 0.00 | 0.108667E+09 | 0.00 | 0.919015E+09 | 0.314942E+11 | 0.00 | 0.61 |
February | 0.626566E+10 | 27985623.86 | 0.00 | 0.147117E+09 | 251875.46 | 0.150275E+09 | 0.220503E+11 | 0.00 | 0.64 |
March | 0.225796E+10 | 0.482273E+10 | 0.00 | 0.153717E+09 | 0.118228E+09 | 0.00 | 0.140105E+11 | 0.00 | 0.68 |
April | 0.315603E+09 | 0.255976E+11 | 0.00 | 48827482.33 | 0.247478E+10 | 0.00 | 0.122615E+10 | 0.00 | 0.76 |
May | 28205169.82 | 0.746158E+11 | 0.00 | 2674046.01 | 0.663401E+10 | 0.00 | 53550277.38 | 0.00 | 0.79 |
June | 0.00 | 0.108792E+12 | 0.00 | 0.00 | 0.119642E+11 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.142657E+12 | 0.00 | 0.00 | 0.180907E+11 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.146340E+12 | 0.00 | 0.00 | 0.154436E+11 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.106921E+12 | 0.00 | 0.00 | 0.990842E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 0.311529E+09 | 0.276685E+11 | 0.00 | 75522887.30 | 0.474501E+09 | 0.00 | 0.407573E+10 | 0.00 | 0.82 |
November | 0.318578E+10 | 0.106649E+10 | 0.00 | 0.259017E+09 | 25115171.90 | 0.00 | 0.227866E+11 | 0.00 | 0.83 |
December | 0.851945E+10 | 3431992.40 | 0.00 | 0.141695E+09 | 1094546.83 | 0.00 | 0.318775E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.316855E+11 | 0.638512E+12 | 0.00 | 0.937236E+09 | 0.651349E+11 | 0.106929E+10 | 0.127575E+12 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.108013E+11 | 0.146340E+12 | 0.00 | 0.259017E+09 | 0.180907E+11 | 0.919015E+09 | 0.318775E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109230E+11 | 0.00 | 0.00 | 17601789.04 | 0.00 | 0.135604E+10 | 0.474324E+10 | 0.00 | 0.34 |
February | 0.555604E+10 | 13247851.06 | 0.00 | 41710341.88 | 556237.65 | 95066722.00 | 0.642751E+10 | 0.00 | 0.40 |
March | 0.137083E+10 | 0.302830E+10 | 0.00 | 84957960.00 | 96234792.39 | 0.00 | 0.795918E+10 | 0.00 | 0.62 |
April | 0.140532E+09 | 0.223536E+11 | 0.00 | 40046930.39 | 0.636759E+09 | 0.00 | 0.100834E+10 | 0.00 | 0.96 |
May | 4573684.86 | 0.699780E+11 | 0.00 | 3184997.59 | 0.149898E+10 | 0.00 | 60374323.89 | 0.00 | 1.08 |
June | 0.00 | 0.104141E+12 | 0.00 | 0.00 | 0.276365E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
July | 0.00 | 0.123266E+12 | 0.00 | 0.00 | 0.549524E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
August | 0.00 | 0.119063E+12 | 0.00 | 0.00 | 0.588685E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.00 | 0.751426E+11 | 0.00 | 0.00 | 0.506185E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 0.328010E+09 | 0.142714E+11 | 0.00 | 27671402.46 | 0.507335E+09 | 0.00 | 0.185232E+10 | 0.00 | 0.62 |
November | 0.314151E+10 | 0.415426E+09 | 0.00 | 63596767.58 | 51361443.80 | 0.00 | 0.637659E+10 | 0.00 | 0.46 |
December | 0.971573E+10 | 0.00 | 0.00 | 24279356.23 | 1828175.34 | 0.145647E+09 | 0.535952E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.311802E+11 | 0.531672E+12 | 0.00 | 0.303050E+09 | 0.220006E+11 | 0.159676E+10 | 0.337871E+11 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.109230E+11 | 0.123266E+12 | 0.00 | 84957960.00 | 0.588685E+10 | 0.135604E+10 | 0.795918E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142348E+10 | 0.00 | 0.00 | 110329.49 | 0.00 | 0.870254E+09 | 33524518.90 | 0.00 | 0.31 |
February | 0.100673E+10 | 0.00 | 0.00 | 1704308.41 | 62217.46 | 0.202873E+09 | 0.249181E+09 | 0.00 | 0.29 |
March | 0.344758E+09 | 0.153335E+09 | 0.00 | 6369131.15 | 26400233.74 | 0.00 | 0.578656E+09 | 0.00 | 0.36 |
April | 30894702.86 | 0.146673E+10 | 0.00 | 4332053.27 | 0.301158E+09 | 0.00 | 0.115856E+09 | 0.00 | 0.56 |
May | 2617524.05 | 0.638640E+10 | 0.00 | 201759.52 | 0.613972E+09 | 0.00 | 4146900.72 | 0.00 | 0.73 |
June | 0.00 | 0.102370E+11 | 0.00 | 0.00 | 0.969289E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.136831E+11 | 0.00 | 0.00 | 0.146245E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.128617E+11 | 0.00 | 0.00 | 0.154449E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.753039E+10 | 0.00 | 0.00 | 0.130179E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.118168E+09 | 0.113027E+10 | 0.00 | 2386367.90 | 0.149851E+09 | 0.00 | 0.112951E+09 | 0.00 | 0.40 |
November | 0.737258E+09 | 7791776.49 | 0.00 | 3667755.88 | 8304075.12 | 33798601.23 | 0.294515E+09 | 0.00 | 0.29 |
December | 0.137144E+10 | 0.00 | 0.00 | 166170.83 | 143049.92 | 0.547144E+09 | 48084422.25 | 0.00 | 0.29 |
Annual Sum or Average | 0.503535E+10 | 0.534568E+11 | 0.00 | 18937876.43 | 0.637790E+10 | 0.165407E+10 | 0.143691E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.142348E+10 | 0.136831E+11 | 0.00 | 6369131.15 | 0.154449E+10 | 0.870254E+09 | 0.578656E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.916365E+09 | 0.00 | 0.00 | 734102.28 | 0.00 | 0.348062E+09 | 0.263100E+09 | 0.00 | 0.32 |
February | 0.452272E+09 | 0.00 | 0.00 | 3605796.41 | 40225.32 | 78163723.20 | 0.715604E+09 | 0.00 | 0.39 |
March | 0.131546E+09 | 0.146417E+09 | 0.00 | 8726766.18 | 10296209.64 | 0.00 | 0.874812E+09 | 0.00 | 0.58 |
April | 10521344.53 | 0.150143E+10 | 0.00 | 5720963.33 | 0.137178E+09 | 0.00 | 0.150351E+09 | 0.00 | 0.84 |
May | 1037159.88 | 0.563859E+10 | 0.00 | 180493.20 | 0.271313E+09 | 0.00 | 3785655.05 | 0.00 | 0.98 |
June | 0.00 | 0.814364E+10 | 0.00 | 0.00 | 0.448907E+09 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.00 | 0.104317E+11 | 0.00 | 0.00 | 0.761871E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
August | 0.00 | 0.967762E+10 | 0.00 | 0.00 | 0.862216E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.00 | 0.626921E+10 | 0.00 | 0.00 | 0.663021E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 51945241.68 | 0.105337E+10 | 0.00 | 3843751.75 | 66543426.38 | 0.00 | 0.192347E+09 | 0.00 | 0.58 |
November | 0.322267E+09 | 8400584.04 | 0.00 | 5603841.32 | 5308179.15 | 3903444.14 | 0.644490E+09 | 0.00 | 0.43 |
December | 0.766117E+09 | 0.00 | 0.00 | 1143677.90 | 92485.75 | 0.219856E+09 | 0.334174E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.265207E+10 | 0.428704E+11 | 0.00 | 29559392.36 | 0.322679E+10 | 0.649985E+09 | 0.317866E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.916365E+09 | 0.104317E+11 | 0.00 | 8726766.18 | 0.862216E+09 | 0.348062E+09 | 0.874812E+09 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898078E+09 | 0.00 | 0.00 | 8506703.42 | 0.00 | 0.401907E+09 | 0.273503E+10 | 0.00 | 0.58 |
February | 0.574307E+09 | 117175.94 | 0.00 | 13532739.98 | 11718.74 | 90756455.13 | 0.216277E+10 | 0.00 | 0.62 |
March | 0.204545E+09 | 0.304154E+09 | 0.00 | 15632451.36 | 9720881.37 | 0.00 | 0.145285E+10 | 0.00 | 0.66 |
April | 25438448.99 | 0.204851E+10 | 0.00 | 6561825.96 | 0.217281E+09 | 0.00 | 0.165726E+09 | 0.00 | 0.72 |
May | 2372515.47 | 0.675554E+10 | 0.00 | 212125.60 | 0.559706E+09 | 0.00 | 4502398.92 | 0.00 | 0.76 |
June | 0.00 | 0.101336E+11 | 0.00 | 0.00 | 0.983416E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.137920E+11 | 0.00 | 0.00 | 0.146863E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.139114E+11 | 0.00 | 0.00 | 0.142313E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.100542E+11 | 0.00 | 0.00 | 0.897155E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 48221758.03 | 0.225064E+10 | 0.00 | 11096087.47 | 46303791.53 | 0.00 | 0.384434E+09 | 0.00 | 0.79 |
November | 0.315924E+09 | 44450236.93 | 0.00 | 26151573.04 | 2259595.58 | 0.00 | 0.231651E+10 | 0.00 | 0.82 |
December | 0.805998E+09 | 138536.10 | 0.00 | 11072089.59 | 35684.02 | 0.162804E+09 | 0.279796E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.287489E+10 | 0.592947E+11 | 0.00 | 92765596.43 | 0.560765E+10 | 0.655468E+09 | 0.120198E+11 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.898078E+09 | 0.139114E+11 | 0.00 | 26151573.04 | 0.146863E+10 | 0.401907E+09 | 0.279796E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.852455E+09 | 0.00 | 0.00 | 1442094.61 | 0.00 | 0.357641E+09 | 0.464652E+09 | 0.00 | 0.35 |
February | 0.514922E+09 | 71015.54 | 0.00 | 3832190.89 | 3225.24 | 72390372.05 | 0.615877E+09 | 0.00 | 0.40 |
March | 0.142003E+09 | 0.199928E+09 | 0.00 | 8452811.56 | 6169141.33 | 0.00 | 0.789487E+09 | 0.00 | 0.59 |
April | 12318995.06 | 0.176643E+10 | 0.00 | 5274324.18 | 58729320.91 | 0.00 | 0.127699E+09 | 0.00 | 0.90 |
May | 395458.08 | 0.611802E+10 | 0.00 | 257784.39 | 0.140779E+09 | 0.00 | 5082197.19 | 0.00 | 1.02 |
June | 0.00 | 0.932695E+10 | 0.00 | 0.00 | 0.249702E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
July | 0.00 | 0.115403E+11 | 0.00 | 0.00 | 0.511902E+09 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.00 | 0.111144E+11 | 0.00 | 0.00 | 0.549353E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.705290E+10 | 0.00 | 0.00 | 0.466258E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 48626397.85 | 0.118319E+10 | 0.00 | 3670525.87 | 46892845.72 | 0.00 | 0.148267E+09 | 0.00 | 0.60 |
November | 0.326491E+09 | 18011506.16 | 0.00 | 6491793.28 | 3345670.89 | 0.00 | 0.596096E+09 | 0.00 | 0.45 |
December | 0.826995E+09 | 0.00 | 0.00 | 1891585.04 | 92526.16 | 0.165696E+09 | 0.474997E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.272421E+10 | 0.483203E+11 | 0.00 | 31313109.82 | 0.203323E+10 | 0.595728E+09 | 0.322216E+10 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.852455E+09 | 0.115403E+11 | 0.00 | 8452811.56 | 0.549353E+09 | 0.357641E+09 | 0.789487E+09 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 7500002.65 | 0.00 | 0.00 | 0.611201E+09 | 0.00 | 0.58 |
February | 0.00 | 7554840.81 | 0.00 | 16053402.15 | 0.00 | 0.00 | 0.292062E+09 | 0.00 | 0.59 |
March | 0.00 | 0.121305E+09 | 0.00 | 15524337.52 | 0.00 | 0.00 | 95639241.87 | 0.00 | 0.59 |
April | 0.00 | 0.360944E+09 | 0.00 | 6552563.21 | 0.00 | 0.00 | 7251498.96 | 0.00 | 0.59 |
May | 0.00 | 0.867222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.130958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.178397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.178647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.127918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.430572E+09 | 0.00 | 1622954.56 | 0.00 | 0.00 | 4339747.29 | 0.00 | 0.59 |
November | 0.00 | 45932994.72 | 0.00 | 21846968.90 | 0.00 | 0.00 | 0.148636E+09 | 0.00 | 0.59 |
December | 0.00 | 86462.24 | 0.00 | 41201616.78 | 0.00 | 0.00 | 0.484138E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.799281E+10 | 0.00 | 0.110302E+09 | 0.00 | 0.00 | 0.164327E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.178647E+10 | 0.00 | 41201616.78 | 0.00 | 0.00 | 0.611201E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396871E+09 | 0.00 | 0.00 | 44593374.27 | 0.00 | 0.00 | 0.604219E+10 | 0.00 | 0.58 |
February | 0.00 | 58297205.40 | 0.00 | 0.142512E+09 | 0.00 | 0.00 | 0.310717E+10 | 0.00 | 0.59 |
March | 0.00 | 0.111516E+10 | 0.00 | 0.154429E+09 | 0.00 | 0.00 | 0.105563E+10 | 0.00 | 0.59 |
April | 0.00 | 0.339727E+10 | 0.00 | 71238901.84 | 0.00 | 0.00 | 88150384.23 | 0.00 | 0.59 |
May | 0.00 | 0.840456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.128453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.175791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.175350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.409540E+10 | 0.00 | 17228727.46 | 0.00 | 0.00 | 59479204.88 | 0.00 | 0.59 |
November | 0.00 | 0.400710E+09 | 0.00 | 0.208288E+09 | 0.00 | 0.00 | 0.163296E+10 | 0.00 | 0.59 |
December | 0.00 | 236933.73 | 0.00 | 0.372806E+09 | 0.00 | 0.00 | 0.504819E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.396871E+09 | 0.778071E+11 | 0.00 | 0.101110E+10 | 0.00 | 0.00 | 0.170338E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.396871E+09 | 0.175791E+11 | 0.00 | 0.372806E+09 | 0.00 | 0.00 | 0.604219E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240790E+09 | 0.00 | 0.00 | 2468229.64 | 0.00 | 0.00 | 0.407156E+09 | 0.00 | 0.58 |
February | 0.00 | 7072304.72 | 0.00 | 12780167.73 | 0.00 | 0.00 | 0.300793E+09 | 0.00 | 0.59 |
March | 0.00 | 0.120585E+09 | 0.00 | 14302458.00 | 0.00 | 0.00 | 97458095.41 | 0.00 | 0.59 |
April | 0.00 | 0.360509E+09 | 0.00 | 6273853.53 | 0.00 | 0.00 | 7487442.74 | 0.00 | 0.59 |
May | 0.00 | 0.859529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.130370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.177807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.179423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.425943E+09 | 0.00 | 1493596.15 | 0.00 | 0.00 | 4957822.75 | 0.00 | 0.59 |
November | 0.00 | 45360167.35 | 0.00 | 19099902.72 | 0.00 | 0.00 | 0.153139E+09 | 0.00 | 0.59 |
December | 0.00 | 78069.21 | 0.00 | 34665963.85 | 0.00 | 0.00 | 0.491626E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.240790E+09 | 0.795203E+10 | 0.00 | 91084171.62 | 0.00 | 0.00 | 0.146262E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.240790E+09 | 0.179423E+10 | 0.00 | 34665963.85 | 0.00 | 0.00 | 0.491626E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.482754E+09 | 0.00 | 0.00 | 0.140056E+11 | 0.00 | 0.66 |
February | 0.00 | 0.169410E+09 | 0.00 | 0.837728E+09 | 0.00 | 0.00 | 0.676848E+10 | 0.00 | 0.66 |
March | 0.00 | 0.255882E+10 | 0.00 | 0.760680E+09 | 0.00 | 0.00 | 0.211354E+10 | 0.00 | 0.66 |
April | 0.00 | 0.786980E+10 | 0.00 | 0.277362E+09 | 0.00 | 0.00 | 0.114308E+09 | 0.00 | 0.66 |
May | 0.00 | 0.198458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.291626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.392609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.398530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.300600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.963854E+10 | 0.00 | 81335421.31 | 0.00 | 0.00 | 95004746.20 | 0.00 | 0.66 |
November | 0.00 | 0.939530E+09 | 0.00 | 0.108231E+10 | 0.00 | 0.00 | 0.338255E+10 | 0.00 | 0.66 |
December | 0.00 | 6794.92 | 0.00 | 0.205078E+10 | 0.00 | 0.00 | 0.111866E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.179358E+12 | 0.00 | 0.557295E+10 | 0.00 | 0.00 | 0.376661E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.398530E+11 | 0.00 | 0.205078E+10 | 0.00 | 0.00 | 0.140056E+11 | 0.00 | 0.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.282960E+12 | 0.128892E+10 | 0.00 | 0.803742E+12 | 0.914891E+12 |
February | 0.323748E+12 | 0.157456E+10 | 0.00 | 0.545388E+12 | 0.152921E+13 |
March | 0.429645E+12 | 0.967893E+09 | 0.00 | 0.289110E+12 | 0.289172E+13 |
April | 0.458863E+12 | -664900165.7 | 0.00 | -0.135245E+12 | 0.412241E+13 |
May | 0.492653E+12 | -0.327298E+10 | 0.00 | -0.727245E+12 | 0.393293E+13 |
June | 0.460754E+12 | -0.381767E+10 | 0.00 | -0.125172E+13 | 0.475485E+13 |
July | 0.370766E+12 | -0.822796E+10 | 0.00 | -0.178794E+13 | 0.553137E+13 |
August | 0.311074E+12 | -0.569784E+10 | 0.00 | -0.179061E+13 | 0.589273E+13 |
September | 0.340234E+12 | -0.336285E+10 | 0.00 | -0.126933E+13 | 0.375719E+13 |
October | 0.325597E+12 | -280606600.6 | 0.00 | -0.963453E+11 | 0.303205E+13 |
November | 0.287178E+12 | 0.398766E+09 | 0.00 | 0.450978E+12 | 0.247894E+13 |
December | 0.257048E+12 | 0.133120E+10 | 0.00 | 0.777007E+12 | 0.225674E+13 |
Annual Sum or Average | 0.434052E+13 | -0.197635E+11 | 0.00 | -0.419221E+13 | 0.410950E+14 |
Minimum of Months | 0.257048E+12 | -0.822796E+10 | 0.00 | -0.179061E+13 | 0.914891E+12 |
Maximum of Months | 0.492653E+12 | 0.157456E+10 | 0.00 | 0.803742E+12 | 0.589273E+13 |