Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2024-07-03 12:21:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26370.08 | 569.30 | 569.30 |
Net Site Energy | 26370.08 | 569.30 | 569.30 |
Total Source Energy | 80772.90 | 1743.79 | 1743.79 |
Net Source Energy | 80772.90 | 1743.79 | 1743.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 670.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2472.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2296.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 236.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 178.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.39 |
Humidification | 1142.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.10 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 457.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25054.12 | 1315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3630.65 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 670.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2472.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2296.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 236.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 178.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.39 |
Humidification | General | 1142.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.10 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 457.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 670.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2472.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2296.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 236.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 178.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.39 |
Humidification | Unassigned | 1142.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.10 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 457.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.56 | 28.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 540.89 | 28.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 61.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 107.56 | 28.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 540.89 | 28.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 25054.118 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25054.118 | 100.00 |
Total On-Site and Utility Electric Sources | 25054.118 | 100.00 |
Total Electricity End Uses | 25054.118 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3630.65 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3630.65 | 100.00 |
Total Water End Uses | 3630.65 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 16.00 |
Time Setpoint Not Met During Occupied Cooling | 516.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5937.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-AUG-15:20 | 10-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 14-AUG-17:30 |
Heating | 0.00 | 730515.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 303859.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 244033.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34997.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46730.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37004.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1891077.76 | 730515.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 730515.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 303859.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 244033.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 34997.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 46730.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 37004.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1426.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2123.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7829.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1130.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7274.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 749.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 564.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3619.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1448.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 79346.39 | 1426.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 169.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1712.99 | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 169.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1712.99 | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.04 | 0.420309 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.40 | 0.352235 | 0.299000 | 1.61 | 0.939293 | 0.500000 | 0.001082 | 0.000141 | 1.61 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 50.52 | 0.376463 | 0.320000 | 16.17 | 1.00 | 0.500000 | 0.001012 | 0.003037 | 16.17 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.78 | 0.397686 | 0.338000 | 1.62 | 1.00 | 0.500000 | 0.000958 | 0.000603 | 2.07 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.791935 | 0.301566 | 0.256000 | 0.202735 | 0.804175 | 0.500000 | 0.001263 | 0.000059 | 0.202735 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.26 | 0.121997 | 0.104000 | 0.131201 | 0.325324 | 0.500000 | 0.003123 | 0.000044 | 0.151140 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.76 | 0.135343 | 0.115000 | 0.202929 | 0.360914 | 0.500000 | 0.002815 | 0.000082 | 0.281991 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.53 | 0.100390 | 0.085000 | 0.130311 | 0.300000 | 0.500000 | 0.003795 | 0.000028 | 0.130311 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.12 | 0.335360 | 0.285000 | 2.03 | 0.894294 | 0.500000 | 0.001136 | 0.001385 | 4.77 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.24 | 0.310015 | 0.500000 | 0.003277 | 0.000929 | 3.20 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.27 | 0.130685 | 0.111000 | 2.03 | 0.348493 | 0.500000 | 0.002915 | 0.001394 | 4.80 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.05 | 0.109513 | 0.093000 | 1.31 | 0.300000 | 0.500000 | 0.003479 | 0.000837 | 2.88 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.795997 | 0.300027 | 0.255000 | 0.202979 | 0.800072 | 0.500000 | 0.001270 | 0.000185 | 0.635901 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.31 | 0.117766 | 0.100000 | 0.130687 | 0.314042 | 0.500000 | 0.003235 | 0.000122 | 0.421846 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.91 | 0.124967 | 0.106000 | 0.202578 | 0.333245 | 0.500000 | 0.003049 | 0.000186 | 0.639340 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.47 | 0.105020 | 0.089000 | 0.130428 | 0.300000 | 0.500000 | 0.003628 | 0.000116 | 0.398563 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16084.15 | 0.000141 | 324.24 | |
CORE_MID VAV BOX REHEAT COIL | 347181.88 | 0.003037 | 7907.96 | |
CORE_TOP VAV BOX REHEAT COIL | 68920.72 | 0.000603 | 1820.65 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6719.52 | 0.000059 | 177.15 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5033.75 | 0.000044 | 133.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9381.53 | 0.000082 | 247.75 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3205.46 | 0.000028 | 75.73 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 158294.66 | 0.001385 | 4176.51 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 106144.95 | 0.000929 | 2800.43 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 159380.41 | 0.001394 | 4205.12 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 95641.29 | 0.000837 | 2523.60 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21098.74 | 0.000185 | 556.50 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13995.67 | 0.000122 | 369.14 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21212.60 | 0.000186 | 559.50 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13224.68 | 0.000116 | 348.82 | |
VAV_BOT WITH REHEAT HEATING COIL | 44902.32 | 0.000393 | 747.65 | |
VAV_MID WITH REHEAT HEATING COIL | 383573.09 | 0.003356 | 6422.58 | |
VAV_TOP WITH REHEAT HEATING COIL | 37658.22 | 0.000329 | 636.81 | |
CAV_BAS HEATING COIL | 247476.35 | 0.000875 | 2622.63 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.503260 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.84 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.490135 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.69 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.38 | 2.28 | 10.75 | 2.28 | 8.87 | 8.87 | 0.300000 | 0.257382 | 8.87 |
VAV_MID WITH REHEAT | 51.61 | 22.84 | 103.21 | 26.42 | 81.14 | 81.14 | 0.300000 | 0.325637 | 81.14 |
VAV_TOP WITH REHEAT | 5.13 | 2.28 | 10.26 | 4.17 | 9.07 | 9.07 | 0.300000 | 0.459140 | 9.07 |
CAV_BAS | 0.000000 | 0.000000 | 5.04 | 1.20 | 5.04 | 5.04 | 1.00 | 0.238175 | 5.04 |
AIRLOOP DATACENTER BASEMENT | 24.69 | 24.69 | 24.69 | 24.69 | 24.69 | 24.69 | 1.00 | 0.999997 | 24.69 |
AIRLOOP DATACENTER BOT | 0.503260 | 0.503260 | 0.503260 | 0.503260 | 0.503260 | 0.503260 | 1.00 | 1.00 | 0.503260 |
AIRLOOP DATACENTER MID | 4.84 | 4.84 | 4.84 | 4.84 | 4.84 | 4.84 | 1.00 | 1.00 | 4.84 |
AIRLOOP DATACENTER TOP | 0.490135 | 0.490135 | 0.490135 | 0.490135 | 0.490135 | 0.490135 | 1.00 | 1.00 | 0.490135 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.87 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 81.14 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.07 | |
CAV_BAS_OA_CONTROLLER | 5.04 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.69 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.503260 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.84 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.490135 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.55 | 6.67 | 11.02 | 0.008752 | 0.008500 | 152586.95 | 0.004364 | 8.87 |
VAV_MID WITH REHEAT COOLING COIL | 24.60 | 6.67 | 11.02 | 0.008767 | 0.008500 | 1405566.01 | 0.040199 | 81.14 |
VAV_TOP WITH REHEAT COOLING COIL | 24.54 | 6.67 | 11.02 | 0.008748 | 0.008500 | 155906.13 | 0.004459 | 9.07 |
CAV_BAS COOLING COIL | 24.32 | 6.67 | 11.01 | 0.008876 | 0.008500 | 87283.03 | 0.002496 | 5.04 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.87 |
VAV_MID WITH REHEAT FAN | 81.14 |
VAV_TOP WITH REHEAT FAN | 9.07 |
CAV_BAS FAN | 5.04 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004364 | 0.000109 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000393 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.040199 | 0.000012 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003356 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004459 | 0.000107 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000329 | |
CAV_BAS_COOLC_CONTROLLER | 0.002496 | 0.000191 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.69 | 487972.92 | 351572.04 | 0.011950 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.503260 | 9691.31 | 7074.21 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.84 | 93129.16 | 67973.47 | 0.002281 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.490135 | 9439.67 | 6890.04 | 0.000231 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.69 | 24.69 | 24.69 | 24.69 | 487972.92 | 487972.92 | 17946.39 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.503260 | 0.503260 | 0.503260 | 0.503260 | 9691.31 | 9691.31 | 829.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.84 | 4.84 | 4.84 | 4.84 | 93129.16 | 93129.16 | 8290.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.490135 | 0.490135 | 0.490135 | 0.490135 | 9439.67 | 9439.67 | 829.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.69 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.503260 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.84 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.490135 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.69 | 487972.92 | 0.011950 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.503260 | 9691.31 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.84 | 93129.16 | 0.002281 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.490135 | 9439.67 | 0.000231 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17946.39 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 829.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8290.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 829.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000166 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.051518 | 8328.06 | |
HEATSYS1 PUMP | 0.014099 | 4204.09 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.051518 | 6.18 |
HEATSYS1 | 0.014099 | 1.69 |
COOLSYS1_SUPPLY | 0.051518 | 6.18 |
SINGLE WATER PLANT LOOP | 0.014700 | 1.76 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.051518 | 0.051518 | 216247.55 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1611653.64 | 1611653.64 | 0.014099 |
CENTRAL BOILER | 605500.33 | 593319.48 | 0.014700 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.025759 | 2882.90 |
COOLSYS1 CHILLER2 PUMP | 0.025759 | 2882.90 |
PLANT CIRC PUMP | 0.014700 | 3712.03 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.051518 | 0.026070 | 911530.27 | 911530.39 | 0.046851 |
COOLSYS1 CHILLER2 | 0.051518 | 0.026070 | 911530.27 | 911530.39 | 0.046851 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014700 | 145956.81 | 73887.61 | 72978.40 | 7004.20 | 44332.56 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.093702 | 11.24 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.093702 | 22968.80 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 35.78 | 1092494.20 | 7.16 | 136561.78 |
TOWERWATERSYS COOLTOWER 2 | 35.78 | 1092494.20 | 7.16 | 136561.78 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.047270 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3512E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3535E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2399E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2418E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7066E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7081E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6225E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6233E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4033E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5557E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2841E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4180E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7437E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8528E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6441E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6991E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1730 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.5157E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1984 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1105 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1132 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6955E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7407E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6489E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4116E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5995E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2932E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4666E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7505E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8791E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6446E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7007E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3510E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3535E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2397E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2419E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7065E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7082E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6224E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6232E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3412E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7873E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1769E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6968E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5200E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6658E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4838E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5217E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2220E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5358E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9483E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3145E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7446E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8212E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9359E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8463E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1901E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3059E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9768E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0617E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4742E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5075E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4839E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5223E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8898E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8920E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4472E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4491E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1370E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1384E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6225E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6233E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9411E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0726E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4900E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5963E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1721E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2507E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6447E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7008E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7868E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5303E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6805E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9228E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2741E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2692E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7407E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6484E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9390E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0722E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4870E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5915E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1667E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2339E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6441E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6992E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8896E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8918E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4470E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4488E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1368E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1380E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6224E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6232E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5263E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6468E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1215E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2090E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0126E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0430E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4840E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5224E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0646E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0562E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4656E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6982E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8918E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4714E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9359E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8463E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6381E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9501E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2705E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6152E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0549E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1847E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4837E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5217E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1737 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1289 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1936 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1479 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1267 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9085E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8052E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8715E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.5691E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0666E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2673E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8132E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9722E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1291E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9539E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9044E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8990E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9244E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6487E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0962E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2063E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2773E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8053E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8710E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.2591E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.4039E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5883E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9601E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0173E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6672E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9539E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9044E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1737 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1291 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1936 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1482 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1269 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9249E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8177E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8779E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.5745E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.0744E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2736E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8209E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9842E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1379E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9663E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9108E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8994E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9289E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6494E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0998E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2130E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2816E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8177E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8774E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.2628E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.4102E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5924E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9659E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0278E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6748E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9663E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9108E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69272.51124 | 69272.51124 | 5.03897 | 5.03897 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -4.30000 | 2.65759E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 74233.07892 | 74233.07892 | 5.39993 | 5.39993 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 694769.27538 | 694769.27538 | 50.52406 | 50.52406 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 186122.19222 | 186122.19222 | 7.88206 | 10.77825 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 65781.44902 | 65781.44902 | 4.78278 | 4.78278 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48297.00586 | 48297.00586 | 2.07028 | 2.07028 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10784.09790 | 10784.09790 | 0.79194 | 0.79194 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4701.35511 | 4701.35511 | 0.20111 | 0.20111 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17179.25440 | 17179.25440 | 1.26155 | 1.26155 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3529.08453 | 3529.08453 | 0.15114 | 0.15114 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24029.49603 | 24029.49603 | 1.76460 | 1.76460 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6573.79298 | 6573.79298 | 0.28199 | 0.28199 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20876.77347 | 20876.77347 | 1.53307 | 1.53307 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1908.83469 | 1908.83469 | 8.11295E-002 | 8.72129E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 96973.70334 | 96973.70334 | 7.12131 | 7.12131 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 110819.17486 | 110819.17486 | 4.76759 | 4.76759 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 180275.88509 | 180275.88509 | 13.23848 | 13.23848 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 74305.88569 | 74305.88569 | 3.19727 | 3.19727 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 248859.97617 | 248859.97617 | 18.27495 | 18.27495 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 111578.07367 | 111578.07367 | 4.80038 | 4.80038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 191375.05296 | 191375.05296 | 14.05354 | 14.05354 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 66962.91031 | 66962.91031 | 2.88016 | 2.88016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10839.43017 | 10839.43017 | 0.79600 | 0.79600 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14765.52616 | 14765.52616 | 0.63590 | 0.63590 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17796.43755 | 17796.43755 | 1.30687 | 1.30687 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9794.30663 | 9794.30663 | 0.42185 | 0.42185 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26024.66834 | 26024.66834 | 1.91111 | 1.91111 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 14845.12045 | 14845.12045 | 0.63934 | 0.63934 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19956.37100 | 19956.37100 | 1.46549 | 1.46549 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9255.33100 | 9255.33100 | 0.39856 | 0.39856 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8688.69223 | 8688.69223 | 0.50326 | 0.50326 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:20:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83480.81215 | 83480.81215 | 4.83534 | 4.83534 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8462.07670 | 8462.07670 | 0.49014 | 0.49014 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370719.69289 | 426327.64682 | 21.47228 | 24.69312 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 18.11900 | 8.39428E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -4.30000 | 2.65759E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 124691.43 | 8.86526 | 8.86526 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 36833.81 | 1.79928 | 1.79928 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1141766.19 | 81.14448 | 81.14448 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 412634.96 | 26.42365 | 26.42365 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 127431.07 | 9.07332 | 9.07332 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 40910.93 | 4.16593 | 4.16593 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
7 | CAV_BAS | Cooling | Sensible | 62873.16 | 5.03897 | 5.03897 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63649.34 | 1.20016 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 419116.58 | 24.69319 | 24.69319 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17946.39 | 0.33839 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8480.98 | 0.50326 | 0.50326 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81456.33 | 4.83534 | 4.83534 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8290.49 | 0.15632 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8257.87 | 0.49014 | 0.49014 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.03897 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.42031 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.39993 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35223 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61458 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93929 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08166E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40711E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61458 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16084.14748 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40711E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.24379 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 50.52406 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37646 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.16770 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01205E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03730E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.16770 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 347181.88306 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03730E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7907.95850 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.78278 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39769 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61658 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.58042E-004 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.02949E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.07028 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 68920.72023 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.02949E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1820.65282 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79194 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30157 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20274 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80418 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26341E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.87853E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20274 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6719.51820 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.87853E-005 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.14900 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26155 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12200 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13120 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32532 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12304E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.40375E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15114 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5033.75333 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.40375E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 133.00181 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.76460 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13534 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20293 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36091 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81508E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.20737E-005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28199 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9381.52689 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.20737E-005 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 247.75400 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53307 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10039 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13031 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79521E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80428E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13031 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3205.46307 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80428E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 75.73051 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.12131 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33536 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02957 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89429 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13609E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.38483E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.76759 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 158294.66034 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38483E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4176.51457 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.23848 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31002 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27726E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.28602E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.19727 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 106144.95482 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.28602E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2800.43326 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.27495 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13068 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02852 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34849 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91541E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39433E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.80038 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 159380.40519 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39433E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4205.12458 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.05354 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10951 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30698 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47903E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.36712E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.88016 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 95641.29299 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.36712E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2523.60463 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79600 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30003 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25500 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20298 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80007 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26989E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84581E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63590 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21098.73995 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84581E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 556.50198 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30687 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11777 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13069 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31404 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23523E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22440E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42185 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13995.66738 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22440E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 369.14018 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.91111 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12497 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20258 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33325 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04881E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85577E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63934 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21212.59921 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85577E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 559.50217 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46549 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10502 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.90000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13043 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.62788E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15695E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39856 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13224.68271 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15695E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 348.82314 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50326 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.83534 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49014 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.69312 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.37555 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28176 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.75109 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28176 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.86526 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.86526 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.25738 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 51.60617 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.84338 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 103.21235 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.42365 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 81.14448 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 81.14448 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32564 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.13112 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28325 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.26224 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.16593 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.07332 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.07332 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45914 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.03897 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.03897 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.03897 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.23817 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.69312 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.69312 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.69312 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.69312 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.69319 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.69319 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50326 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50326 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50326 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50326 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50326 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50326 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.83534 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.83534 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.83534 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.83534 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.83534 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.83534 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49014 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49014 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49014 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49014 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49014 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49014 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.86526 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 81.14448 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.07332 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.03897 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.69319 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50326 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.83534 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49014 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.86526 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.54878 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02367 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75240E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 152586.95078 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.36397E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.86526 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 44902.31741 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.92825E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 747.65413 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.86526 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.36397E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.09119E-004 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.92825E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 81.14448 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.60218 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02372 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.76725E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1405566.00948 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.01990E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 81.14448 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 383573.09310 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.35566E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6422.58357 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 81.14448 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.01990E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.18458E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.35566E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.07332 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.53639 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02365 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74784E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 155906.12767 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.45890E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.07332 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 37658.21791 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29451E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 636.81256 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.07332 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.45890E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.06796E-004 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.29451E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.03897 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.31938 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01261 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.87616E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 87283.02919 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.49628E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.03897 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 247476.34913 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.62541 |
350 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.03897 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.49628E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.90760E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.69319 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.69319 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 487972.91959 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 351572.03905 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.19504E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.69319 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.69319 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.69319 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.69319 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 487972.91959 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 487972.91959 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17946.39161 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.69319 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.69319 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 487972.91959 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.19504E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17946.39161 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.65604E-004 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50326 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50326 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9691.30504 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7074.20708 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37339E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50326 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50326 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50326 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50326 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9691.30504 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9691.30504 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50326 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50326 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9691.30504 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37339E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.83534 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.83534 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 93129.15824 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67973.47139 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28073E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.83534 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.83534 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.83534 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.83534 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 93129.15824 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 93129.15824 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8290.48945 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.83534 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.83534 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 93129.15824 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28073E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8290.48945 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49014 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49014 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9439.66569 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6890.03958 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31177E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49014 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49014 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49014 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49014 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9439.66569 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9439.66569 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49014 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49014 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9439.66569 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31177E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.15182E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8328.06014 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.15182E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.18218 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.15182E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.15182E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 216247.55307 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.40994E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.69193 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.40994E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4204.09396 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1611653.64324 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1611653.64000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.40994E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.15182E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.18218 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.57591E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 2882.89844 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.57591E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 2882.89844 |
456 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.15182E-002 |
457 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.60697E-002 |
458 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 911530.26775 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 911530.39000 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 4.68509E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.15182E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.60697E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 911530.26775 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 911530.39000 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 4.68509E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.46997E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.76396 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.46997E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3712.03032 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.46997E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 145956.80553 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 73887.60589 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 72978.40277 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44332.56353 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 605500.33058 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 593319.48000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.46997E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.37018E-002 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.24421 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.37018E-002 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 22968.79879 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 35.78279 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1092494.20242 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.15656 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 136561.77530 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 35.78279 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1092494.20242 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.15656 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 136561.77530 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.72700E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.72700E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15251.02 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 328993.06 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 65318.99 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6365.97 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4770.87 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8890.76 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3036.83 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 149988.29 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 100574.15 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 151016.82 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 90623.70 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19990.42 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13260.40 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20098.28 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12530.04 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 35385.82 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 305710.57 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 30608.39 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.48 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 197702.63 | 146557.57 | 51145.07 | 0.74 | 34199.40 | 346.87 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1815226.04 | 1343632.98 | 471593.05 | 0.74 | 312675.42 | 3171.33 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 202174.06 | 149931.80 | 52242.26 | 0.74 | 35010.89 | 355.10 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 112990.43 | 83574.10 | 29416.33 | 0.74 | 19644.28 | 199.24 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1914006974E-003 | 1.1599245562E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1130239201 | 0.1925141829 | Pass | Pass | 7.2726701277E-002 | 0.2709878706 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.9523260908E-003 | 7.0397883443E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4583776477E-002 | 2.4567230284E-002 | Pass | Pass | 0.3827867315 | 0.5147705328 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.1894940026E-002 | 0.1151296532 | Pass | Pass | 5.6455460508E-002 | 0.2292333022 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1051231037 | 0.1650976934 | Pass | Pass | 6.9527617257E-002 | 0.2742965582 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1285517831 | 0.1885344823 | Pass | Pass | 5.6498315857E-002 | 0.2285334420 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.0540475912E-002 | 0.1362199073 | Pass | Pass | 5.6155316889E-002 | 0.2289532250 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8473933436E-002 | 1.4980539185E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.4198790501E-002 | 8.5192752157E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.4459211879E-002 | 0.1193199610 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.5940104984E-002 | 5.7397617824E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1874165777 | 0.1951227927 | Pass | Pass | 14.8446895664 | 36.2432030526 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1373452530 | 0.1411312654 | Pass | Pass | 13.8819149793 | 35.2049710615 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1068555138 | 0.1282238309 | Pass | Pass | 4.9662288305 | 21.4052531672 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.2260221383E-002 | 7.0988196188E-002 | Pass | Pass | 10.6682015773 | 30.2403698437 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4452088273E-002 | 2.7176170823E-002 | Pass | Pass | 2.2981130143 | 17.4972824193 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8612824463E-003 | 5.9085960346E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.4321509887E-002 | 5.6082057839E-002 | Pass | Pass | 0.3716628861 | 0.4732977011 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8874899528E-006 | 5.7480619921E-006 | Pass | Pass | 2.9766948939E-003 | 3.7220559973E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1830146107E-006 | 6.5082505256E-006 | Pass | Pass | 0.1866557794 | 0.6670628556 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.8111112178E-002 | 2.5092301591E-002 | Pass | Pass | 5.8730923062E-003 | 7.0647952836E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1000326947E-006 | 1.0090299164E-006 | Pass | Pass | 4.9221288705E-005 | 1.0688410189E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5840.58 | 62.17 | 0.00 | 32753.79 | 4863.51 | 43520.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.363_SHGC_EAST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 1390.74 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.29 | 0.0000 | Y | 10.98 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.98 | 0.0000 | Y | 7.00 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.82 | 0.0000 | Y | 10.80 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.08 | 0.0000 | Y | 7.03 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.24 | 0.0000 | Y | 109.64 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.94 | 0.0000 | Y | 69.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.80 | 0.0000 | Y | 107.93 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.04 | 0.0000 | Y | 70.15 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.23 | 0.0000 | Y | 10.96 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.94 | 0.0000 | Y | 6.99 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.80 | 0.0000 | Y | 10.79 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.03 | 0.0000 | Y | 7.01 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 778.07 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.50 | 42.50 | 105.87 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.54 | 63.02 | 11.70 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.54 | 47.95 | 239.37 | |
Exterior Lighting Total | 40855.88 | 356.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1795793.82 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1611653.64 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 911530.39 | 5.17 | 908443.64 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 911530.39 | 5.17 | 908443.64 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 608274.99 | |||||
CENTRAL BOILER | Boiler:HotWater | 593319.48 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1092494.20 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1092494.20 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 152586.95 | 197702.63 | 146557.57 | 51145.07 | 0.74 | - | 34199.40 | 346.87 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1405566.01 | 1815226.04 | 1343632.98 | 471593.05 | 0.74 | - | 312675.42 | 3171.33 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 155906.13 | 202174.06 | 149931.80 | 52242.26 | 0.74 | - | 35010.89 | 355.10 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 87283.03 | 112990.43 | 83574.10 | 29416.33 | 0.74 | - | 19644.28 | 199.24 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 487972.92 | 351572.04 | 136400.88 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9691.31 | 7074.21 | 2617.10 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 93129.16 | 67973.47 | 25155.69 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9439.67 | 6890.04 | 2549.63 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16084.15 | 15251.02 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 347181.88 | 328993.06 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 68920.72 | 65318.99 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6719.52 | 6365.97 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5033.75 | 4770.87 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9381.53 | 8890.76 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3205.46 | 3036.83 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 158294.66 | 149988.29 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 106144.95 | 100574.15 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 159380.41 | 151016.82 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 95641.29 | 90623.70 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21098.74 | 19990.42 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13995.67 | 13260.40 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21212.60 | 20098.28 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13224.68 | 12530.04 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 44902.32 | 35385.82 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 383573.09 | 305710.57 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 37658.22 | 30608.39 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.48 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 487972.92 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9691.31 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 93129.16 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9439.67 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17946.39 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8290.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.87 | 19157.36 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 81.14 | 175348.90 | 2160.95 | 1.00 | 1.08 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.07 | 19606.96 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.04 | 10959.20 | 2174.89 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.69 | 40725.17 | 1649.25 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 563.71 | 1120.11 | 1.00 | 1.60 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.84 | 5416.10 | 1120.11 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 549.00 | 1120.11 | 1.00 | 1.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.051518 | 8328.06 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014099 | 4204.09 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.025759 | 2882.90 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.025759 | 2882.90 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014700 | 3712.03 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.093702 | 22968.80 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69272.51 | 69272.51 | 24.92 | 5.039 | 5.039 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00901 | 19.67 | 0.00840 | 1.200 | 0.00 |
CORE_BOTTOM | 74233.08 | 74233.08 | 29.74 | 5.400 | 5.400 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 19.67 | 0.00840 | 1.078 | 0.00 |
CORE_MID | 694769.28 | 694769.28 | 278.34 | 50.524 | 50.524 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 19.67 | 0.00840 | 10.778 | 0.00 |
CORE_TOP | 65781.45 | 65781.45 | 26.35 | 4.783 | 4.783 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 19.67 | 0.00840 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10784.10 | 10784.10 | 34.41 | 0.792 | 0.792 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00885 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17179.25 | 17179.25 | 85.06 | 1.262 | 1.262 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00864 | 21.11 | 0.00840 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24029.50 | 24029.50 | 76.67 | 1.765 | 1.765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00866 | 26.10 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20876.77 | 20876.77 | 103.36 | 1.533 | 1.533 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 25.13 | 0.00841 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 96973.70 | 96973.70 | 309.41 | 7.121 | 7.121 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00889 | 26.40 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 180275.89 | 180275.89 | 892.56 | 13.238 | 13.238 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00863 | 21.39 | 0.00840 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 248859.98 | 248859.98 | 794.02 | 18.275 | 18.275 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 26.17 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 191375.05 | 191375.05 | 947.52 | 14.054 | 14.054 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 24.97 | 0.00840 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10839.43 | 10839.43 | 34.59 | 0.796 | 0.796 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00884 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17796.44 | 17796.44 | 88.11 | 1.307 | 1.307 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00864 | 21.65 | 0.00840 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26024.67 | 26024.67 | 83.03 | 1.911 | 1.911 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00864 | 26.25 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19956.37 | 19956.37 | 98.81 | 1.465 | 1.465 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 24.97 | 0.00840 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8688.69 | 8688.69 | 240.00 | 0.503 | 0.503 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83480.81 | 83480.81 | 2305.93 | 4.835 | 4.835 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 23.08 | 0.00840 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8462.08 | 8462.08 | 233.74 | 0.490 | 0.490 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370719.69 | 426327.65 | 544.01 | 21.472 | 24.693 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.12 | 0.00839 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 24.41 | 0.00266 | -4.30 | 0.00266 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19.60 | 22.27 | 0.00266 | -4.30 | 0.00266 | 1.078 | 0.00 |
CORE_MID | 186122.19 | 186122.19 | 74.56 | 7.882 | 10.778 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 10.778 | 0.00 |
CORE_TOP | 48297.01 | 48297.01 | 19.35 | 2.070 | 2.070 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4701.36 | 4701.36 | 15.00 | 0.201 | 0.201 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3529.08 | 3529.08 | 17.47 | 0.151 | 0.151 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6573.79 | 6573.79 | 20.97 | 0.282 | 0.282 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1908.83 | 1908.83 | 9.45 | 0.081 | 0.087 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 110819.17 | 110819.17 | 353.59 | 4.768 | 4.768 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 74305.89 | 74305.89 | 367.90 | 3.197 | 3.197 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 111578.07 | 111578.07 | 356.00 | 4.800 | 4.800 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 66962.91 | 66962.91 | 331.54 | 2.880 | 2.880 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14765.53 | 14765.53 | 47.11 | 0.636 | 0.636 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9794.31 | 9794.31 | 48.49 | 0.422 | 0.422 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14845.12 | 14845.12 | 47.36 | 0.639 | 0.639 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9255.33 | 9255.33 | 45.82 | 0.399 | 0.399 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -4.30 | 0.00266 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:20:00 | 18.00 | 26.86 | 0.00850 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 23.70 | 0.00673 | -4.30 | 0.00266 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.87 | 0.00299 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 18.00 | 27.00 | 0.00850 | -4.30 | 0.00266 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.87 | 8.87 | 1.80 | 1.80 | 8.8653 | 2.2818 | 8.8653 | 0.2574 | 0.3000 |
VAV_MID WITH REHEAT | 81.14 | 81.14 | 26.42 | 26.42 | 81.1445 | 26.4236 | 81.1445 | 0.3256 | 0.3000 |
VAV_TOP WITH REHEAT | 9.07 | 9.07 | 4.17 | 4.17 | 9.0733 | 4.1659 | 9.0733 | 0.4591 | 0.3000 |
CAV_BAS | 5.04 | 5.04 | 1.20 | 1.20 | 5.0390 | 1.2002 | 5.0390 | 0.2382 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.69 | 24.69 | 0.34 | 0.34 | 24.6932 | 24.6931 | 24.6932 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.5033 | 0.5033 | 0.5033 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.84 | 4.84 | 0.16 | 0.16 | 4.8353 | 4.8353 | 4.8353 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4901 | 0.4901 | 0.4901 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16084.147 | 16084.147 | 1.614580 | 0.00014071 | 324.244 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 16084.15 | 16084.15 | 1.614580 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 16143.45 | 16143.45 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 347181.883 | 347181.883 | 16.167700 | 0.00303730 | 7907.958 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 347181.88 | 347181.88 | 16.167700 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 186122.19 | 0.00 | 348362.87 | 348362.87 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 68920.720 | 68920.720 | 2.070276 | 0.00060295 | 1820.653 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 68920.72 | 68920.72 | 2.070276 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 48297.01 | 0.00 | 69168.61 | 69168.61 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6719.518 | 6719.518 | 0.202735 | 0.00005879 | 177.149 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6719.52 | 6719.52 | 0.202735 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00764551 | 48.9299 | 4701.36 | 0.00 | 6741.11 | 6741.11 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5033.753 | 5033.753 | 0.151140 | 0.00004404 | 133.002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5033.75 | 5033.75 | 0.151140 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00769093 | 49.2170 | 3529.08 | 0.00 | 5052.05 | 5052.05 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9381.527 | 9381.527 | 0.281991 | 0.00008207 | 247.754 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9381.53 | 9381.53 | 0.281991 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00776055 | 49.6568 | 6573.79 | 0.00 | 9414.74 | 9414.74 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3205.463 | 3205.463 | 0.130311 | 0.00002804 | 75.731 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3205.46 | 3205.46 | 0.130311 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00739990 | 47.3764 | 1908.83 | 0.00 | 3215.94 | 3215.94 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 158294.660 | 158294.660 | 4.767588 | 0.00138483 | 4176.515 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 158294.66 | 158294.66 | 4.767588 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00782858 | 50.0869 | 110819.17 | 0.00 | 158827.44 | 158827.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 106144.955 | 106144.955 | 3.197272 | 0.00092860 | 2800.433 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 106144.95 | 106144.95 | 3.197272 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783969 | 50.1570 | 74305.89 | 0.00 | 106501.20 | 106501.20 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 159380.405 | 159380.405 | 4.800381 | 0.00139433 | 4205.125 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 159380.41 | 159380.41 | 4.800381 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00783153 | 50.1056 | 111578.07 | 0.00 | 159916.58 | 159916.58 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 95641.293 | 95641.293 | 2.880159 | 0.00083671 | 2523.605 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 95641.29 | 95641.29 | 2.880159 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00779347 | 49.8654 | 66962.91 | 0.00 | 95964.38 | 95964.38 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21098.740 | 21098.740 | 0.635901 | 0.00018458 | 556.502 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21098.74 | 21098.74 | 0.635901 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00789748 | 50.5217 | 14765.53 | 0.00 | 21168.48 | 21168.48 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13995.667 | 13995.667 | 0.421846 | 0.00012244 | 369.140 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13995.67 | 13995.67 | 0.421846 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00789920 | 50.5325 | 9794.31 | 0.00 | 14041.86 | 14041.86 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21212.599 | 21212.599 | 0.639340 | 0.00018558 | 559.502 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21212.60 | 21212.60 | 0.639340 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00789849 | 50.5280 | 14845.12 | 0.00 | 21282.70 | 21282.70 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13224.683 | 13224.683 | 0.398563 | 0.00011570 | 348.823 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13224.68 | 13224.68 | 0.398563 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00788557 | 50.4466 | 9255.33 | 0.00 | 13268.46 | 13268.46 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 152586.951 | -999.000 | 8.865262 | 0.00436397 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 152586.95 | 145594.18 | 8.865262 | 24.55 | 16.69 | 0.00875240 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 22.9040 | 24.00 | 0.00885498 | 47.1375 | 120721.28 | 0.00 | 154048.34 | 141517.80 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 44902.317 | 44902.317 | 2.659579 | 0.00039283 | 747.654 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 44902.32 | 44902.32 | 2.659579 | -1.30 | -1.76 | 0.00313301 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 76.3467 | 21.51 | 0.00571940 | 35.5917 | 16713.07 | 0.00 | 42817.01 | 42817.01 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1405566.009 | -999.000 | 81.144482 | 0.04019901 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1405566.01 | 1337803.13 | 81.144482 | 24.60 | 16.72 | 0.00876725 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 25.0245 | 24.00 | 0.00888813 | 47.3115 | 1100410.18 | 0.00 | 1418933.41 | 1300546.08 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 383573.093 | 383573.093 | 24.343345 | 0.00335566 | 6422.584 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 383573.09 | 383573.09 | 24.343345 | -0.36 | -0.65 | 0.00350992 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 83.4150 | 19.60 | 0.00760940 | 53.1043 | 272394.10 | 0.00 | 369950.02 | 369950.02 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 155906.128 | -999.000 | 9.073321 | 0.00445890 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 155906.13 | 148878.03 | 9.073321 | 24.54 | 16.68 | 0.00874784 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 22.3788 | 24.00 | 0.00884614 | 47.0910 | 123503.97 | 0.00 | 157402.03 | 144703.11 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 37658.218 | 37658.218 | 2.721996 | 0.00032945 | 636.813 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37658.22 | 37658.22 | 2.721996 | 1.24 | 0.96 | 0.00397451 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 74.5960 | 17.60 | 0.00771588 | 61.0205 | 30684.49 | 0.00 | 37044.92 | 37044.92 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 87283.029 | -999.000 | 5.038970 | 0.00249628 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 87283.03 | 81356.66 | 5.038970 | 24.32 | 16.71 | 0.00887616 | 11.01 | 11.01 | 0.00850000 | 25.22 | 0.00840522 | 16.63 | 23.8175 | 24.00 | 0.00904443 | 48.1319 | 62082.68 | 0.00 | 88120.48 | 79135.52 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.070992 | -1.02 | -2.36 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 39.0804 | 24.46 | 0.00265759 | 13.8985 | 0.00 | 0.00 | 100079.59 | 100079.59 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 487972.920 | 351572.039 | 24.693189 | 0.01195043 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 454148.90 | 451450.35 | -999.0 | 28.40 | 17.83 | 0.00854052 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | -999.0000 | 27.00 | 0.00854237 | 38.0741 | 370387.05 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9691.305 | 7074.207 | 0.503260 | 0.00023734 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 8980.42 | 8875.41 | -999.0 | 27.83 | 17.67 | 0.00857756 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858319 | 38.2511 | 8688.69 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93129.158 | 67973.471 | 4.835336 | 0.00228073 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 86299.71 | 85251.09 | -999.0 | 27.83 | 17.67 | 0.00858061 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858658 | 38.2661 | 83480.81 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9439.666 | 6890.040 | 0.490135 | 0.00023118 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 8747.38 | 8642.35 | -999.0 | 27.83 | 17.67 | 0.00857965 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858550 | 38.2613 | 8462.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 487972.920 | 487972.920 | 24.693189 | 0.01195043 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 487972.92 | 487972.92 | 24.693189 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.3704 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9691.305 | 9691.305 | 0.503260 | 0.00023734 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9691.31 | 9691.31 | 0.503260 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1062 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 93129.158 | 93129.158 | 4.835336 | 0.00228073 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 93129.16 | 93129.16 | 4.835336 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2329 | 24.80 | 0.00672942 | 34.2530 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9439.666 | 9439.666 | 0.490135 | 0.00023118 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9439.67 | 9439.67 | 0.490135 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1894 | 23.70 | 0.00299331 | 16.3708 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17946.39 | 17946.39 | 24.693189 | -0.06 | -0.06 | 0.00841994 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.3704 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.503260 | -0.13 | -0.13 | 0.00831852 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1062 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8290.49 | 8290.49 | 4.835336 | -0.14 | -0.14 | 0.00659778 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2329 | 24.80 | 0.00672942 | 34.2530 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.490135 | -0.14 | -1.34 | 0.00298260 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1894 | 23.70 | 0.00299331 | 16.3708 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16084.147 | 16084.147 | 1.614580 | 0.00014071 | 324.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.9783 | 0.997990 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 16084.15 | 16084.15 | 1.0000 | 1.92356486 | 1.614580 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.14069678 | 60.00 | 32.22 | 27.78 | 0.000 | 16084.15 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 16143.45 | 16143.45 | 1.92356486 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 347181.883 | 347181.883 | 16.167700 | 0.00303730 | 7907.958 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 21.1170 | 21.541966 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 347181.88 | 347181.88 | 1.0000 | 19.26174580 | 16.167700 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 3.03698873 | 60.00 | 32.22 | 27.78 | 0.000 | 347181.88 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 186122.19 | 0.00 | 348362.87 | 348362.87 | 19.26174580 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.54 | 18.22 | 0.00800000 | 51145.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 68920.720 | 68920.720 | 2.070276 | 0.00060295 | 1820.653 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 4.1920 | 4.276398 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 68920.72 | 68920.72 | 1.0000 | 2.46646907 | 2.070276 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.60288702 | 60.00 | 32.22 | 27.78 | 0.000 | 68920.72 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 48297.01 | 0.00 | 69168.61 | 69168.61 | 2.46646907 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61103.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6719.518 | 6719.518 | 0.202735 | 0.00005879 | 177.149 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.4087 | 0.416933 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6719.52 | 6719.52 | 1.0000 | 0.24153338 | 0.202735 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05877928 | 60.00 | 32.22 | 27.78 | 0.000 | 6719.52 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00764551 | 21.00 | 0.00764551 | 48.9299 | 4701.36 | 0.00 | 6741.11 | 6741.11 | 0.24153338 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5033.753 | 5033.753 | 0.151140 | 0.00004404 | 133.002 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.3062 | 0.312335 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5033.75 | 5033.75 | 1.0000 | 0.18006359 | 0.151140 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04403298 | 60.00 | 32.22 | 27.78 | 0.000 | 5033.75 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.86 | 0.00769093 | 21.00 | 0.00769093 | 49.2170 | 3529.08 | 0.00 | 5052.05 | 5052.05 | 0.18006359 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.31 | 21.28 | 0.00800000 | 61116.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9381.527 | 9381.527 | 0.281991 | 0.00008207 | 247.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.5706 | 0.582106 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9381.53 | 9381.53 | 1.0000 | 0.33595616 | 0.281991 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08206532 | 60.00 | 32.22 | 27.78 | 0.000 | 9381.53 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00776055 | 21.00 | 0.00776055 | 49.6568 | 6573.79 | 0.00 | 9414.74 | 9414.74 | 0.33595616 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61083.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3205.463 | 3205.463 | 0.130311 | 0.00002804 | 75.731 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.1950 | 0.198893 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3205.46 | 3205.46 | 1.0000 | 0.15524930 | 0.130311 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.02803993 | 60.00 | 32.22 | 27.78 | 0.000 | 3205.46 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.82 | 0.00739990 | 21.00 | 0.00739990 | 47.3764 | 1908.83 | 0.00 | 3215.94 | 3215.94 | 0.15524930 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.11 | 19.06 | 0.00800000 | 53774.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 158294.660 | 158294.660 | 4.767588 | 0.00138483 | 4176.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 9.6281 | 9.821878 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 158294.66 | 158294.66 | 1.0000 | 5.67997116 | 4.767588 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.38468948 | 60.00 | 32.22 | 27.78 | 0.000 | 158294.66 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00782858 | 21.00 | 0.00782858 | 50.0869 | 110819.17 | 0.00 | 158827.44 | 158827.44 | 5.67997116 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 106144.955 | 106144.955 | 3.197272 | 0.00092860 | 2800.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 6.4562 | 6.586090 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 106144.95 | 106144.95 | 1.0000 | 3.80914030 | 3.197272 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.92850764 | 60.00 | 32.22 | 27.78 | 0.000 | 106144.95 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783969 | 21.00 | 0.00783969 | 50.1570 | 74305.89 | 0.00 | 106501.20 | 106501.20 | 3.80914030 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 159380.405 | 159380.405 | 4.800381 | 0.00139433 | 4205.125 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 9.6941 | 9.889247 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 159380.41 | 159380.41 | 1.0000 | 5.71903927 | 4.800381 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.39418708 | 60.00 | 32.22 | 27.78 | 0.000 | 159380.41 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783153 | 21.00 | 0.00783153 | 50.1056 | 111578.07 | 0.00 | 159916.58 | 159916.58 | 5.71903927 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 95641.293 | 95641.293 | 2.880159 | 0.00083671 | 2523.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 5.8173 | 5.934358 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 95641.29 | 95641.29 | 1.0000 | 3.43134084 | 2.880159 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.83662640 | 60.00 | 32.22 | 27.78 | 0.000 | 95641.29 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00779347 | 21.00 | 0.00779347 | 49.8654 | 66962.91 | 0.00 | 95964.38 | 95964.38 | 3.43134084 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61026.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21098.740 | 21098.740 | 0.635901 | 0.00018458 | 556.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 1.2833 | 1.309136 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21098.74 | 21098.74 | 1.0000 | 0.75759461 | 0.635901 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.18456215 | 60.00 | 32.22 | 27.78 | 0.000 | 21098.74 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789748 | 21.00 | 0.00789748 | 50.5217 | 14765.53 | 0.00 | 21168.48 | 21168.48 | 0.75759461 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13995.667 | 13995.667 | 0.421846 | 0.00012244 | 369.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.8513 | 0.868404 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13995.67 | 13995.67 | 1.0000 | 0.50257546 | 0.421846 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12242771 | 60.00 | 32.22 | 27.78 | 0.000 | 13995.67 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789920 | 21.00 | 0.00789920 | 50.5325 | 9794.31 | 0.00 | 14041.86 | 14041.86 | 0.50257546 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21212.599 | 21212.599 | 0.639340 | 0.00018558 | 559.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 1.2902 | 1.316201 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21212.60 | 21212.60 | 1.0000 | 0.76169182 | 0.639340 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.18555814 | 60.00 | 32.22 | 27.78 | 0.000 | 21212.60 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789849 | 21.00 | 0.00789849 | 50.5280 | 14845.12 | 0.00 | 21282.70 | 21282.70 | 0.76169182 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13224.683 | 13224.683 | 0.398563 | 0.00011570 | 348.823 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 0.8044 | 0.820566 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13224.68 | 13224.68 | 1.0000 | 0.47483656 | 0.398563 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.11568349 | 60.00 | 32.22 | 27.78 | 0.000 | 13224.68 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00788557 | 21.00 | 0.00788557 | 50.4466 | 9255.33 | 0.00 | 13268.46 | 13268.46 | 0.47483656 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 152586.951 | -999.000 | 8.865262 | 0.00436397 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1103 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.865262 | 10.56182495 | 4197.9300 | 999.8980 | 51.51290114 | 15.00 | 6.67 | 8.33 | 1801342.12 | 8.4707 | 8.470737 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 152586.95 | 145594.18 | 1.0000 | 10.56182495 | 8.865262 | 24.55 | 16.69 | 0.00875240 | 46956.2 | 11.02 | 11.02 | 0.00850000 | 32509.2 | 4.36352231 | 6.67 | 15.00 | 8.33 | 19157.359 | 133429.59 | 26.40 | 0.00840708 | 17.04 | 2.03050000 | 22.9040 | 24.00 | 0.00885498 | 24.00 | 0.00885498 | 47.1375 | 120721.28 | 0.00 | 154048.34 | 141517.80 | 10.56182495 | 24.55 | 16.80 | 0.00875240 | 46956.2 | 11.43 | 11.30 | 0.00828201 | 32370.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 44902.317 | 44902.317 | 2.659579 | 0.00039283 | 747.654 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.865262 | 10.56182495 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 2.7311 | 2.786102 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 44902.32 | 44902.32 | 1.0000 | 3.16854749 | 2.659579 | -1.30 | -1.76 | 0.00313301 | 6518.8 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.39278499 | 60.00 | 32.22 | 27.78 | 0.000 | 44902.32 | -4.30 | 0.00265759 | -4.30 | 2.03050000 | 76.3467 | 8.37 | 0.00466753 | 21.51 | 0.00571940 | 35.5917 | 16713.07 | 0.00 | 42817.01 | 42817.01 | 3.16854749 | 2.80 | 0.72 | 0.00313301 | 10665.3 | 16.17 | 7.78 | 0.00313301 | 24178.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1405566.009 | -999.000 | 81.144482 | 0.04019901 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1379 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 81.144482 | 96.67326443 | 4197.9300 | 999.8980 | 51.51290114 | 15.00 | 6.67 | 8.33 | 1801342.12 | 78.0288 | 78.028821 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1405566.01 | 1337803.13 | 1.0000 | 96.67326443 | 81.144482 | 24.60 | 16.72 | 0.00876725 | 47048.6 | 11.02 | 11.02 | 0.00850000 | 32509.2 | 40.19490923 | 6.67 | 15.00 | 8.33 | 175348.904 | 1230217.11 | 26.40 | 0.00840708 | 17.04 | 20.30600000 | 25.0245 | 24.00 | 0.00888813 | 24.00 | 0.00888813 | 47.3115 | 1100410.18 | 0.00 | 1418933.41 | 1300546.08 | 96.67326443 | 24.60 | 16.83 | 0.00876725 | 47048.6 | 11.43 | 11.30 | 0.00828172 | 32371.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 383573.093 | 383573.093 | 24.343345 | 0.00335566 | 6422.584 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 81.144482 | 96.67326443 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 23.3304 | 23.799971 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 383573.09 | 383573.09 | 1.0000 | 29.00197933 | 24.343345 | -0.36 | -0.65 | 0.00350992 | 8412.2 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 3.35532244 | 60.00 | 32.22 | 27.78 | 0.000 | 383573.09 | -4.30 | 0.00265759 | -4.30 | 20.30600000 | 83.4150 | 19.45 | 0.00779675 | 19.60 | 0.00760940 | 53.1043 | 272394.10 | 0.00 | 369950.02 | 369950.02 | 29.00197933 | 2.80 | 1.26 | 0.00350992 | 11609.9 | 15.41 | 7.86 | 0.00350992 | 24365.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 155906.128 | -999.000 | 9.073321 | 0.00445890 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1018 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.073321 | 10.80970081 | 4197.9300 | 999.8980 | 51.51290114 | 15.00 | 6.67 | 8.33 | 1801342.12 | 8.6550 | 8.654998 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 155906.13 | 148878.03 | 1.0000 | 10.80970081 | 9.073321 | 24.54 | 16.68 | 0.00874784 | 46932.0 | 11.02 | 11.02 | 0.00850000 | 32509.2 | 4.45844066 | 6.67 | 15.00 | 8.33 | 19606.964 | 136299.16 | 26.40 | 0.00840708 | 17.04 | 2.03050000 | 22.3788 | 24.00 | 0.00884614 | 24.00 | 0.00884614 | 47.0910 | 123503.97 | 0.00 | 157402.03 | 144703.11 | 10.80970081 | 24.54 | 16.79 | 0.00874784 | 46932.0 | 11.43 | 11.30 | 0.00828207 | 32370.8 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 37658.218 | 37658.218 | 2.721996 | 0.00032945 | 636.813 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.073321 | 10.80970081 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 2.2905 | 2.336620 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37658.22 | 37658.22 | 1.0000 | 3.24291024 | 2.721996 | 1.24 | 0.96 | 0.00397451 | 11198.9 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.32941691 | 60.00 | 32.22 | 27.78 | 0.000 | 37658.22 | -4.30 | 0.00265759 | -4.30 | 2.03050000 | 74.5960 | 17.52 | 0.00784151 | 17.60 | 0.00771588 | 61.0205 | 30684.49 | 0.00 | 37044.92 | 37044.92 | 3.24291024 | 2.80 | 1.91 | 0.00397451 | 12774.3 | 14.09 | 7.77 | 0.00397451 | 24197.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87283.029 | -999.000 | 5.038970 | 0.00249628 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3403 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:VariableVolume | 5.038970 | 6.00328740 | 4197.9300 | 999.8980 | 51.51290114 | 15.00 | 6.67 | 8.33 | 1801342.12 | 4.8454 | 4.845444 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 87283.03 | 81356.66 | 1.0000 | 6.00328740 | 5.038970 | 24.32 | 16.71 | 0.00887616 | 47037.1 | 11.01 | 11.01 | 0.00850000 | 32497.9 | 2.49602894 | 6.67 | 15.00 | 8.33 | 10959.196 | 76323.83 | 25.22 | 0.00840522 | 16.63 | 1.20015641 | 23.8175 | 24.00 | 0.00904443 | 24.00 | 0.00904443 | 48.1319 | 62082.68 | 0.00 | 88120.48 | 79135.52 | 6.00328740 | 24.32 | 16.82 | 0.00887616 | 47037.1 | 11.41 | 11.30 | 0.00828275 | 32358.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:VariableVolume | 5.038970 | 6.00328740 | 4197.9300 | 999.8980 | 14.09801085 | 54.44 | 82.22 | 27.78 | 1644088.81 | 6.0824 | 6.204807 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.070992 | -1.02 | -2.36 | 0.00265759 | 5612.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.30 | 0.00265759 | -4.30 | 1.20015641 | 39.0804 | 0.00 | 0.00265759 | 24.46 | 0.00265759 | 13.8985 | 0.00 | 0.00 | 100079.59 | 100079.59 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 487972.920 | 351572.039 | 24.693189 | 0.01195043 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7164 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 454148.90 | 451450.35 | 0.9307 | -999.0 | -999.0 | 28.40 | 17.83 | 0.00854052 | 50344.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 454148.90 | 26.40 | 0.00840708 | 17.04 | 0.33839277 | -999.0000 | 27.00 | 0.00854237 | 27.00 | 0.00854237 | 38.0741 | 370387.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9691.305 | 7074.207 | 0.503260 | 0.00023734 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7853 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 8980.42 | 8875.41 | 0.9266 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857756 | 49862.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8980.42 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | -999.0000 | 27.00 | 0.00858319 | 27.00 | 0.00858319 | 38.2511 | 8688.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 93129.158 | 67973.471 | 4.835336 | 0.00228073 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7909 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 86299.71 | 85251.09 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00858061 | 49865.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86299.71 | 23.08 | 0.00840189 | 15.87 | 0.15632344 | -999.0000 | 27.00 | 0.00858658 | 27.00 | 0.00858658 | 38.2661 | 83480.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9439.666 | 6890.040 | 0.490135 | 0.00023118 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7891 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 8747.38 | 8642.35 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857965 | 49864.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8747.38 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | -999.0000 | 27.00 | 0.00858550 | 27.00 | 0.00858550 | 38.2613 | 8462.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 487972.920 | 487972.920 | 24.693189 | 0.01195043 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 487972.92 | 487972.92 | 1.0000 | 29.41877408 | 24.693189 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 487972.92 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.3704 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9691.305 | 9691.305 | 0.503260 | 0.00023734 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9691.31 | 9691.31 | 1.0000 | 0.59956974 | 0.503260 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9691.31 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1062 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 93129.158 | 93129.158 | 4.835336 | 0.00228073 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 93129.16 | 93129.16 | 1.0000 | 5.76068353 | 4.835336 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93129.16 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.2329 | 0.00 | 0.00672942 | 24.80 | 0.00672942 | 34.2530 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9439.666 | 9439.666 | 0.490135 | 0.00023118 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9439.67 | 9439.67 | 1.0000 | 0.58393344 | 0.490135 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9439.67 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1894 | 0.00 | 0.00299331 | 23.70 | 0.00299331 | 16.3708 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.693189 | 29.41877408 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17946.39 | 17946.39 | 1.0000 | 29.41877408 | 24.693189 | -0.06 | -0.06 | 0.00841994 | 20997.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17946.39 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.3704 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.503260 | 0.59956974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.59956974 | 0.503260 | -0.13 | -0.13 | 0.00831852 | 20667.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1062 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.835336 | 5.76068353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8290.49 | 8290.49 | 1.0000 | 5.76068353 | 4.835336 | -0.14 | -0.14 | 0.00659778 | 16359.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8290.49 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.2329 | 0.00 | 0.00672942 | 24.80 | 0.00672942 | 34.2530 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.490135 | 0.58393344 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.58393344 | 0.490135 | -0.14 | -1.34 | 0.00298260 | 7320.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1894 | 0.00 | 0.00299331 | 23.70 | 0.00299331 | 16.3708 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.87 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 81.14 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.07 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.04 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.69 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2808.67 | 172.67 | 33.33 |
CORE_BOTTOM | 2424.33 | 350.50 | 0.00 |
CORE_MID | 1108.67 | 2428.83 | 12.50 |
CORE_TOP | 1203.50 | 3957.50 | 385.33 |
PERIMETER_BOT_ZN_3 | 1242.50 | 3155.50 | 16.00 |
PERIMETER_BOT_ZN_2 | 1765.33 | 3028.50 | 119.67 |
PERIMETER_BOT_ZN_1 | 2047.83 | 2799.50 | 148.17 |
PERIMETER_BOT_ZN_4 | 2815.17 | 1272.83 | 166.00 |
PERIMETER_MID_ZN_3 | 1386.83 | 4339.50 | 712.50 |
PERIMETER_MID_ZN_2 | 1692.33 | 3184.83 | 602.50 |
PERIMETER_MID_ZN_1 | 2058.00 | 3330.33 | 429.33 |
PERIMETER_MID_ZN_4 | 1889.83 | 3564.00 | 479.50 |
PERIMETER_TOP_ZN_3 | 2317.83 | 4692.67 | 1711.33 |
PERIMETER_TOP_ZN_2 | 2801.17 | 3915.67 | 1527.17 |
PERIMETER_TOP_ZN_1 | 2561.00 | 3832.50 | 1194.67 |
PERIMETER_TOP_ZN_4 | 2491.67 | 4021.67 | 1259.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 642.33 | 642.33 |
DATACENTER_MID_ZN_6 | 5924.17 | 88.67 | 88.67 |
DATACENTER_TOP_ZN_6 | 5508.83 | 245.33 | 151.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5795.00 | 5795.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5937.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 769.17 | 0.00 | 373.50 |
CORE_BOTTOM | 0.00 | 1.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 26.50 | 0.00 | 26.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 38.33 | 0.00 | 37.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 77.50 | 0.00 | 44.00 |
PERIMETER_MID_ZN_3 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 1.33 | 27.50 | 0.00 | 27.33 |
PERIMETER_MID_ZN_1 | 0.00 | 36.00 | 0.00 | 34.83 |
PERIMETER_MID_ZN_4 | 0.00 | 32.33 | 0.00 | 17.83 |
PERIMETER_TOP_ZN_3 | 50.17 | 0.00 | 15.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 20.83 | 23.83 | 0.17 | 23.00 |
PERIMETER_TOP_ZN_1 | 15.33 | 30.50 | 0.00 | 29.17 |
PERIMETER_TOP_ZN_4 | 12.00 | 30.50 | 0.00 | 17.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 51.50 | 948.67 | 16.00 | 516.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 1.164 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.983 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.734 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.672 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.866 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.273 | 0.012 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 1.437 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.909 | 0.012 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.689 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.073 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 1.342 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.221 | 0.027 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.675 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.150 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 1.291 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.194 | 0.034 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 26.561 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.29 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.28 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1015.76 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 45963148.25 | 0.00 | 45963148.25 | 0.00 | 45963148.25 | 37848132.68 | 4482.88 | 265.14 | 4011.98 | 0.00 |
CORE_BOTTOM | 40828988.16 | 0.00 | 40828988.16 | 0.00 | 40828988.16 | 33990283.35 | 3833.70 | 107.66 | 4818.64 | 326.18 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 4259.02 | 774.83 | 3726.15 | 123.50 |
CORE_TOP | 27324976.52 | 0.00 | 27324976.52 | 0.00 | 27324976.52 | 33990283.35 | 4483.41 | 1266.78 | 3009.81 | 197.66 |
PERIMETER_BOT_ZN_3 | 4519895.48 | 0.00 | 4519895.48 | 114807.37 | 4634702.85 | 4267819.30 | 5588.97 | 181.12 | 2989.90 | 326.18 |
PERIMETER_BOT_ZN_2 | 4226301.22 | 0.00 | 4226301.22 | 76538.19 | 4302839.41 | 2750345.05 | 5422.90 | 166.35 | 3170.75 | 326.18 |
PERIMETER_BOT_ZN_1 | 7381876.04 | 0.00 | 7381876.04 | 114807.37 | 7496683.41 | 4267912.63 | 5265.00 | 174.79 | 3320.20 | 326.18 |
PERIMETER_BOT_ZN_4 | 6368228.99 | 0.00 | 6368228.99 | 76538.19 | 6444767.19 | 2750345.05 | 4215.49 | 159.20 | 4385.30 | 326.18 |
PERIMETER_MID_ZN_3 | 35312864.22 | 0.00 | 35312864.22 | 269254.52 | 35582118.74 | 42678193.03 | 5082.50 | 849.93 | 2827.57 | 123.50 |
PERIMETER_MID_ZN_2 | 36375163.25 | 0.00 | 36375163.25 | 179502.89 | 36554666.14 | 27503450.52 | 5076.41 | 654.47 | 3029.13 | 646.11 |
PERIMETER_MID_ZN_1 | 68028132.34 | 0.00 | 68028132.34 | 269254.52 | 68297386.85 | 42679126.28 | 4606.35 | 855.12 | 3298.54 | 123.50 |
PERIMETER_MID_ZN_4 | 40310864.67 | 0.00 | 40310864.67 | 179502.89 | 40490367.56 | 27503450.52 | 4864.01 | 860.30 | 3035.69 | 123.50 |
PERIMETER_TOP_ZN_3 | 3456427.58 | 0.00 | 3456427.58 | 334307.04 | 3790734.62 | 4267819.30 | 4507.08 | 1264.15 | 2988.76 | 197.66 |
PERIMETER_TOP_ZN_2 | 3763527.13 | 0.00 | 3763527.13 | 222871.21 | 3986398.34 | 2750345.05 | 4392.13 | 1335.20 | 3032.68 | 197.66 |
PERIMETER_TOP_ZN_1 | 6545744.54 | 0.00 | 6545744.54 | 334307.04 | 6880051.58 | 4267912.63 | 4291.12 | 1434.34 | 3034.54 | 197.66 |
PERIMETER_TOP_ZN_4 | 3944790.17 | 0.00 | 3944790.17 | 222871.21 | 4167661.38 | 2750345.05 | 4457.89 | 1564.30 | 2737.81 | 197.66 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.41E+09 | 0.00 | 0.41E+09 | 0.00 | 0.41E+09 | 10671554.30 | 2.50 | 7.17 | 8750.33 | 2815.50 |
Total Facility | 0.54E+10 | 0.00 | 0.54E+10 | 10472195.81 | 0.54E+10 | 0.50E+10 | 6746.78 | 4380.69 | 8757.44 | 3338.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.1483 | 0.0000 | 2.1483 | 0.0000 | 2.1483 | 1.2002 | 1665.88 | 265.14 | 4011.98 |
CORE_BOTTOM | 1.8341 | 0.0000 | 1.8341 | 0.0000 | 1.8341 | 1.0778 | 1240.46 | 101.69 | 4600.85 |
CORE_MID | 13.6971 | 0.0000 | 13.6971 | 0.0000 | 13.6971 | 10.7782 | 1529.65 | 773.09 | 3640.26 |
CORE_TOP | 1.2553 | 0.0000 | 1.2553 | 0.0000 | 1.2553 | 1.0778 | 1723.91 | 1265.89 | 2953.20 |
PERIMETER_BOT_ZN_3 | 0.2030 | 0.0000 | 0.2030 | 0.0027 | 0.2057 | 0.1353 | 2981.38 | 174.29 | 2787.32 |
PERIMETER_BOT_ZN_2 | 0.1922 | 0.0000 | 0.1922 | 0.0018 | 0.1940 | 0.0872 | 2815.76 | 160.75 | 2966.49 |
PERIMETER_BOT_ZN_1 | 0.3367 | 0.0000 | 0.3367 | 0.0027 | 0.3394 | 0.1353 | 2657.44 | 168.42 | 3117.14 |
PERIMETER_BOT_ZN_4 | 0.2881 | 0.0000 | 0.2881 | 0.0018 | 0.2898 | 0.0872 | 1622.80 | 153.95 | 4166.24 |
PERIMETER_MID_ZN_3 | 1.6188 | 0.0000 | 1.6188 | 0.0062 | 1.6250 | 1.3533 | 2352.90 | 848.05 | 2742.04 |
PERIMETER_MID_ZN_2 | 1.6215 | 0.0000 | 1.6215 | 0.0044 | 1.6259 | 0.8721 | 1878.81 | 651.38 | 2503.81 |
PERIMETER_MID_ZN_1 | 3.1471 | 0.0000 | 3.1471 | 0.0062 | 3.1533 | 1.3533 | 1876.99 | 853.34 | 3212.67 |
PERIMETER_MID_ZN_4 | 1.8437 | 0.0000 | 1.8437 | 0.0042 | 1.8478 | 0.8721 | 2135.12 | 858.77 | 2949.11 |
PERIMETER_TOP_ZN_3 | 0.1586 | 0.0000 | 0.1586 | 0.0077 | 0.1663 | 0.1353 | 1748.53 | 1263.10 | 2931.36 |
PERIMETER_TOP_ZN_2 | 0.1739 | 0.0000 | 0.1739 | 0.0052 | 0.1791 | 0.0872 | 1639.33 | 1333.86 | 2969.82 |
PERIMETER_TOP_ZN_1 | 0.3029 | 0.0000 | 0.3029 | 0.0077 | 0.3106 | 0.1353 | 1535.98 | 1433.06 | 2973.96 |
PERIMETER_TOP_ZN_4 | 0.1805 | 0.0000 | 0.1805 | 0.0052 | 0.1856 | 0.0872 | 1701.59 | 1563.24 | 2678.17 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.6874 | 0.0000 | 13.6874 | 0.0000 | 13.6874 | 0.3384 | 1.00 | 7.17 | 5934.83 |
Total Facility | 241.2070 | 0.0000 | 241.2070 | 0.2447 | 241.4517 | 158.4706 | 3929.78 | 4368.70 | 5941.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 89881843.42 | 0.00 | 89881843.42 | 48026705.38 | 3588.93 | 10.09 | 5160.98 | 326.18 |
VAV_MID WITH REHEAT | 0.68E+09 | 0.00 | 0.68E+09 | 0.48E+09 | 3931.74 | 8.61 | 4819.66 | 123.50 |
VAV_TOP WITH REHEAT | 63921866.06 | 0.00 | 63921866.06 | 48026705.38 | 4070.06 | 3.99 | 4685.95 | 197.66 |
CAV_BAS | 65238589.58 | 0.00 | 65238589.58 | 37848132.68 | 4478.78 | 0.08 | 4281.14 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.59E+09 | 0.00 | 0.59E+09 | 10671554.30 | 2.50 | 0.00 | 8757.50 | 2815.50 |
AIRLOOP DATACENTER BOT | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3467457.73 | 0.00 | 3467457.73 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.0511 | 0.0000 | 4.0511 | 1.5229 | 1064.46 | 7.39 | 4871.15 |
VAV_MID WITH REHEAT | 31.2063 | 0.0000 | 31.2063 | 15.2292 | 1215.31 | 8.44 | 4719.25 |
VAV_TOP WITH REHEAT | 2.9399 | 0.0000 | 2.9399 | 1.5229 | 1315.26 | 3.69 | 4624.04 |
CAV_BAS | 3.0493 | 0.0000 | 3.0493 | 1.2002 | 1661.78 | 0.08 | 4281.14 |
AIRLOOP DATACENTER BASEMENT | 19.4275 | 0.0000 | 19.4275 | 0.3384 | 1.00 | 0.00 | 5942.00 |
AIRLOOP DATACENTER BOT | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1621 | 0.0000 | 0.1621 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 749.88 | 3610.68 | 0.00 | 0.00 | 0.00 | 885.81 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 287.70 | 3223.84 | 0.00 | 0.00 | 0.00 | 1457.12 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 12.52 | 2769.84 | 0.00 | 0.00 | 0.00 | 2233.06 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 251.98 | 4024.81 | 0.00 | 12.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 7.17 | 8750.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.8958 | 6.0160 | 0.0000 | 0.0000 | 0.0000 | 2.4299 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.7697 | 46.3896 | 0.0000 | 0.0000 | 0.0000 | 22.9199 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8795 | 4.8557 | 0.0000 | 0.0000 | 0.0000 | 2.2159 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7101 | 4.3935 | 0.0000 | 1.1092 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4917 | 19.4564 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2219 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1185 |
Fields with Defaults | 3880 |
Autosized Fields | 335 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
Electricity:Building | 17148.51 | 216479.19 | 06-MAY-18:20 | 1025582.59 | 01-DEC-15:30 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17148.51 | 216479.19 | 06-MAY-18:20 | 1025582.59 | 01-DEC-15:30 |
InteriorLights:Electricity | 2472.12 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2472.12 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2472.12 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2472.12 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.35 | 603.11 | 02-APR-17:10 | 3823.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.98 | 43.94 | 01-JAN-09:50 | 1662.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.98 | 43.94 | 01-JAN-09:50 | 1662.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.44 | 388.67 | 02-APR-17:10 | 2463.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.00 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.00 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.17 | 603.12 | 02-APR-17:10 | 3823.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.80 | 43.94 | 01-JAN-08:40 | 1662.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.80 | 43.94 | 01-JAN-08:40 | 1662.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.46 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.03 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.03 | 28.32 | 01-JAN-09:50 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 473.29 | 6031.15 | 02-APR-17:10 | 38231.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 109.64 | 439.44 | 01-JAN-09:40 | 16625.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 109.64 | 439.44 | 01-JAN-09:40 | 16625.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 304.28 | 3886.70 | 02-APR-17:10 | 24637.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 69.92 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 69.92 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 471.59 | 6031.24 | 02-APR-17:10 | 38231.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 107.93 | 439.45 | 01-JAN-08:40 | 16625.99 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 107.93 | 439.45 | 01-JAN-08:40 | 16625.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 304.50 | 3886.68 | 12-MAR-17:10 | 24637.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 70.15 | 283.19 | 01-JAN-09:40 | 10714.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 70.15 | 283.19 | 01-JAN-09:40 | 10714.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.33 | 603.11 | 02-APR-17:10 | 3823.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.96 | 43.94 | 01-JAN-09:40 | 1662.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.96 | 43.94 | 01-JAN-09:40 | 1662.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.43 | 388.67 | 02-APR-17:10 | 2463.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.99 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.99 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.16 | 603.12 | 02-APR-17:10 | 3823.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.79 | 43.94 | 01-JAN-08:40 | 1662.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.79 | 43.94 | 01-JAN-08:40 | 1662.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.45 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.01 | 28.32 | 01-JAN-09:40 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.01 | 28.32 | 01-JAN-09:40 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1046.04 | 3869.20 | 10-JAN-04:40 | 342304.65 | 13-JUN-16:00 |
HeatRejection:Electricity | 178.28 | 82.51 | 10-JAN-08:00 | 70679.03 | 22-MAY-14:00 |
General:HeatRejection:Electricity | 178.28 | 82.51 | 10-JAN-08:00 | 70679.03 | 22-MAY-14:00 |
Electricity:HVAC | 3991.03 | 51649.81 | 29-JAN-01:30 | 395899.42 | 14-AUG-17:00 |
ExteriorEquipment:Electricity | 2566.28 | 20217.42 | 01-JAN-00:10 | 233397.31 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-15:40 |
ElectricityPurchased:Facility | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
ElectricityPurchased:Plant | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
Cogeneration:ElectricityPurchased | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
ElectricityNet:Plant | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
Cogeneration:ElectricityNet | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
General:Cogeneration:ElectricityNet | 25054.12 | 294213.32 | 14-MAY-04:50 | 1891077.76 | 14-AUG-15:20 |
Fans:Electricity | 2296.86 | 47253.97 | 01-JAN-02:40 | 271814.05 | 21-JUN-13:10 |
General:Fans:Electricity | 2296.86 | 47253.97 | 01-JAN-02:40 | 271814.05 | 21-JUN-13:10 |
ExteriorLights:Electricity | 356.94 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.94 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 670.47 | 1721.55 | 02-JAN-07:10 | 308140.72 | 14-AUG-16:00 |
General:Cooling:Electricity | 670.47 | 1721.55 | 02-JAN-07:10 | 308140.72 | 14-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1142.73 | 0.00 | 17-JAN-11:30 | 100000.00 | 20-FEB-16:00 |
General:Humidifier:Electricity | 1142.73 | 0.00 | 17-JAN-11:30 | 100000.00 | 20-FEB-16:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 457.40 | 0.00 | 01-JAN-00:10 | 52812.23 | 15-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 457.40 | 0.00 | 01-JAN-00:10 | 52812.23 | 15-FEB-13:00 |
Pumps:Electricity | 236.64 | 3712.03 | 01-JAN-00:40 | 37697.36 | 28-AUG-14:00 |
General:Pumps:Electricity | 236.64 | 3712.03 | 01-JAN-00:40 | 37697.36 | 28-AUG-14:00 |
WIRED_LTG_ELECTRICITY | 69.47 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1315.97 | 0.00 | 01-JAN-00:40 | 730515.30 | 10-JAN-08:00 |
NaturalGas:Plant | 1315.97 | 0.00 | 01-JAN-00:40 | 730515.30 | 10-JAN-08:00 |
Heating:NaturalGas | 1315.97 | 0.00 | 01-JAN-00:40 | 730515.30 | 10-JAN-08:00 |
Boiler:Heating:NaturalGas | 1315.97 | 0.00 | 01-JAN-00:40 | 730515.30 | 10-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3951.28 | 4875.08 | 02-JAN-07:10 | 1902308.91 | 14-AUG-15:40 |
PlantLoopCoolingDemand:HVAC | 3951.28 | 4875.08 | 02-JAN-07:10 | 1902308.91 | 14-AUG-15:40 |
CoolingCoils:PlantLoopCoolingDemand | 3951.28 | 4875.08 | 02-JAN-07:10 | 1902308.91 | 14-AUG-15:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3630.65 | 0.00 | 29-JAN-01:30 | 0.00 | 14-AUG-17:30 |
Water:HVAC | 425.10 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
Humidifier:Water | 425.10 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
General:Humidifier:Water | 425.10 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
MainsWater:Facility | 3630.65 | 0.00 | 29-JAN-01:30 | 0.00 | 14-AUG-17:30 |
MainsWater:HVAC | 425.10 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
Humidifier:MainsWater | 425.10 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
General:Humidifier:MainsWater | 425.10 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
Water:Plant | 3205.56 | 0.00 | 01-JAN-00:10 | 0.00 | 14-AUG-17:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3205.56 | 0.00 | 01-JAN-00:10 | 0.00 | 14-AUG-17:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 925.39 | 0.00 | 01-JAN-00:10 | 0.00 | 14-AUG-17:30 |
General:HeatRejection:Water | 925.39 | 0.00 | 01-JAN-00:10 | 0.00 | 14-AUG-17:30 |
HeatRejection:MainsWater | 925.39 | 0.00 | 01-JAN-00:10 | 0.00 | 14-AUG-17:30 |
General:HeatRejection:MainsWater | 925.39 | 0.00 | 01-JAN-00:10 | 0.00 | 14-AUG-17:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27250.64 | 97721.67 | 15-JAN-06:00 | 7448884.66 | 14-AUG-15:30 |
EnergyTransfer:Building | 17038.76 | 88699.21 | 09-JAN-00:20 | 1548749.91 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 598.64 | 0.00 | 01-JAN-00:10 | 101166.97 | 02-JAN-07:10 |
Heating:EnergyTransfer | 173.97 | 0.00 | 06-JAN-22:10 | 330313.29 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 173.97 | 0.00 | 06-JAN-22:10 | 330313.29 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 16864.79 | 87998.26 | 09-JAN-05:00 | 1548749.91 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 598.64 | 0.00 | 01-JAN-00:10 | 101166.97 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 16864.79 | 87998.26 | 09-JAN-05:00 | 1548749.91 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 598.64 | 0.00 | 01-JAN-00:10 | 101166.97 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 573.36 | 0.00 | 01-JAN-00:10 | 51306.94 | 10-OCT-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 573.36 | 0.00 | 01-JAN-00:10 | 51306.94 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 573.36 | 0.00 | 01-JAN-00:10 | 51306.94 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_MID | 3904.96 | 0.00 | 01-JAN-00:10 | 385763.54 | 24-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3904.96 | 0.00 | 01-JAN-00:10 | 385763.54 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3904.96 | 0.00 | 01-JAN-00:10 | 385763.54 | 24-JUL-14:00 |
EnergyTransfer:Zone:CORE_TOP | 320.80 | 0.00 | 01-JAN-00:40 | 60713.92 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.96 | 0.00 | 01-JAN-00:10 | 60713.92 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.96 | 0.00 | 01-JAN-00:10 | 60713.92 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 315.84 | 0.00 | 01-JAN-00:40 | 44310.85 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 315.84 | 0.00 | 01-JAN-00:40 | 44310.85 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.81 | 0.00 | 01-JAN-00:10 | 8896.89 | 10-JUL-14:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 276.75 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 276.75 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.81 | 0.00 | 01-JAN-00:10 | 8896.89 | 10-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.81 | 0.00 | 01-JAN-00:10 | 8896.89 | 10-JUL-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.63 | 0.00 | 01-JAN-00:10 | 14007.43 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 581.06 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 581.06 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.62 | 0.00 | 01-JAN-00:10 | 14007.43 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.62 | 0.00 | 01-JAN-00:10 | 14007.43 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 93.13 | 0.00 | 01-JAN-00:10 | 21876.42 | 11-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2525.93 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2525.93 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 93.11 | 0.00 | 01-JAN-00:10 | 21876.42 | 11-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 93.11 | 0.00 | 01-JAN-00:10 | 21876.42 | 11-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 82.93 | 0.00 | 01-JAN-00:10 | 17687.33 | 28-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 82.93 | 0.00 | 01-JAN-00:10 | 17687.33 | 28-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 82.93 | 0.00 | 01-JAN-00:10 | 17687.33 | 28-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 391.56 | 0.00 | 01-JAN-00:10 | 75409.73 | 13-JUN-14:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.48 | 0.00 | 01-JAN-00:10 | 69643.97 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.48 | 0.00 | 01-JAN-00:10 | 69643.97 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 371.08 | 0.00 | 01-JAN-00:10 | 75409.73 | 13-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 371.08 | 0.00 | 01-JAN-00:10 | 75409.73 | 13-JUN-14:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 433.53 | 0.00 | 01-JAN-00:10 | 146705.60 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 12.09 | 0.00 | 01-JAN-00:10 | 48755.69 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 12.09 | 0.00 | 01-JAN-00:10 | 48755.69 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 421.45 | 0.00 | 01-JAN-00:10 | 146705.60 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 421.45 | 0.00 | 01-JAN-00:10 | 146705.60 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 832.27 | 0.00 | 01-JAN-00:10 | 235375.37 | 11-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 9.98 | 0.00 | 01-JAN-00:10 | 54725.62 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 9.98 | 0.00 | 01-JAN-00:10 | 54725.62 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 822.28 | 0.00 | 01-JAN-00:10 | 235375.37 | 11-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 822.28 | 0.00 | 01-JAN-00:10 | 235375.37 | 11-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 475.41 | 0.00 | 01-JAN-00:10 | 167312.52 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.08 | 0.00 | 01-JAN-00:10 | 36533.28 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.08 | 0.00 | 01-JAN-00:10 | 36533.28 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 469.33 | 0.00 | 01-JAN-00:10 | 167312.52 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 469.33 | 0.00 | 01-JAN-00:10 | 167312.52 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.77 | 0.00 | 01-JAN-00:40 | 10882.60 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.13 | 0.00 | 01-JAN-00:40 | 10882.60 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.13 | 0.00 | 01-JAN-00:40 | 10882.60 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.64 | 0.00 | 01-JAN-00:20 | 8367.69 | 13-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.64 | 0.00 | 01-JAN-00:20 | 8367.69 | 13-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.15 | 0.00 | 01-JAN-00:40 | 14570.04 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.46 | 0.00 | 01-JAN-00:40 | 11485.79 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.46 | 0.00 | 01-JAN-00:40 | 11485.79 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.69 | 0.00 | 01-JAN-00:20 | 14570.04 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.69 | 0.00 | 01-JAN-00:20 | 14570.04 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 79.16 | 0.00 | 01-JAN-00:40 | 23734.10 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.40 | 0.00 | 01-JAN-00:10 | 15969.07 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.40 | 0.00 | 01-JAN-00:10 | 15969.07 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.76 | 0.00 | 01-JAN-00:40 | 23734.10 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.76 | 0.00 | 01-JAN-00:40 | 23734.10 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.53 | 0.00 | 01-JAN-00:40 | 17347.32 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.72 | 0.00 | 01-JAN-00:40 | 9351.43 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.72 | 0.00 | 01-JAN-00:40 | 9351.43 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.81 | 0.00 | 01-JAN-00:20 | 17347.32 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.81 | 0.00 | 01-JAN-00:20 | 17347.32 | 13-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 48.10 | 0.00 | 01-JAN-00:10 | 7938.16 | 24-JUL-15:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.20 | 0.00 | 01-JAN-00:10 | 3864.93 | 03-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.20 | 0.00 | 01-JAN-00:10 | 3864.93 | 03-DEC-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 46.91 | 0.00 | 01-JAN-00:10 | 7938.16 | 24-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 46.91 | 0.00 | 01-JAN-00:10 | 7938.16 | 24-JUL-15:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 292.73 | 0.00 | 01-JAN-00:10 | 58614.56 | 24-JUL-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 56.03 | 0.00 | 01-JAN-00:10 | 44114.82 | 18-DEC-14:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 56.03 | 0.00 | 01-JAN-00:10 | 44114.82 | 18-DEC-14:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 236.70 | 0.00 | 01-JAN-00:10 | 58614.56 | 24-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 236.70 | 0.00 | 01-JAN-00:10 | 58614.56 | 24-JUL-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.71 | 0.00 | 01-JAN-00:40 | 17818.60 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.67 | 0.00 | 01-JAN-00:40 | 17818.60 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.67 | 0.00 | 01-JAN-00:40 | 17818.60 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.05 | 0.00 | 01-JAN-00:10 | 16460.93 | 13-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.05 | 0.00 | 01-JAN-00:10 | 16460.93 | 13-JUN-14:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.36 | 868.36 | 10-JAN-08:00 | 8359.97 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.36 | 868.36 | 10-JAN-08:00 | 8359.97 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.36 | 868.36 | 10-JAN-08:00 | 8359.97 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1196.92 | 14.17 | 09-JAN-00:20 | 80067.06 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.11 | 0.00 | 01-JAN-11:40 | 1754.25 | 10-JAN-04:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.11 | 0.00 | 01-JAN-11:40 | 1754.25 | 10-JAN-04:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1196.82 | 0.00 | 01-JAN-00:10 | 80067.06 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1196.82 | 0.00 | 01-JAN-00:10 | 80067.06 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.15 | 0.00 | 11-JAN-20:40 | 8119.07 | 30-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.65 | 0.00 | 02-JAN-14:30 | 587.87 | 08-JAN-17:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.65 | 0.00 | 02-JAN-14:30 | 587.87 | 08-JAN-17:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.51 | 0.00 | 01-JAN-00:10 | 8119.07 | 30-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.51 | 0.00 | 01-JAN-00:10 | 8119.07 | 30-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7162.13 | 86856.69 | 15-JAN-06:00 | 367923.07 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7162.13 | 86856.69 | 15-JAN-06:00 | 367923.07 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7162.13 | 86856.69 | 15-JAN-06:00 | 367923.07 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1430.17 | 0.00 | 01-JAN-00:40 | 628418.34 | 10-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
EnergyTransfer:HVAC | 4432.66 | 6888.54 | 01-JAN-06:00 | 1768281.07 | 14-AUG-15:40 |
HeatingCoils:EnergyTransfer | 978.13 | 0.00 | 01-JAN-00:40 | 611101.00 | 10-JAN-08:00 |
PlantLoopHeatingDemand:HVAC | 978.13 | 0.00 | 01-JAN-00:40 | 611101.00 | 10-JAN-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 978.13 | 0.00 | 01-JAN-00:40 | 611101.00 | 10-JAN-08:00 |
CoolingCoils:EnergyTransfer | 3454.53 | 3153.53 | 02-JAN-07:10 | 1768281.07 | 14-AUG-15:40 |
EnergyTransfer:Plant | 5779.23 | 0.00 | 01-JAN-00:40 | 4443630.15 | 13-JUN-16:00 |
LoopToLoop:EnergyTransfer | 1383.39 | 0.00 | 01-JAN-00:10 | 1401465.73 | 13-JUN-16:00 |
WaterSystems:EnergyTransfer | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
Boilers:EnergyTransfer | 973.10 | 0.00 | 01-JAN-00:40 | 610429.19 | 10-JAN-08:00 |
Chillers:EnergyTransfer | 1398.50 | 0.00 | 01-JAN-00:10 | 1402862.42 | 13-JUN-16:00 |
HeatRejection:EnergyTransfer | 1572.21 | 0.00 | 01-JAN-00:10 | 1601866.12 | 13-JUN-16:00 |
General:HeatRejection:EnergyTransfer | 1572.21 | 0.00 | 01-JAN-00:10 | 1601866.12 | 13-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -598.638 | 0.000 | 0.000 | 92.453 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -83.941 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -573.359 | 0.000 | 0.000 | 83.401 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 51.507 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -3904.956 | 0.000 | 0.000 | 840.884 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1320.422 |
CORE_TOP | 0.000 | 0.000 | 4.960 | -315.834 | 0.000 | 0.000 | 87.741 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -215.317 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -56.811 | 0.000 | 0.000 | 10.697 | 10.984 | 36.365 | 22.885 | 0.000 | 0.001 | 45.865 | 0.000 | -68.032 | 0.000 | -1.955 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.003 | -52.623 | 0.000 | 0.000 | 6.897 | 7.002 | 23.435 | 52.506 | 0.000 | 0.000 | 6.953 | 0.000 | -42.873 | 0.000 | -1.300 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.021 | -93.108 | 0.000 | 0.000 | 10.706 | 10.804 | 36.366 | 105.879 | 0.000 | 0.001 | 0.002 | 0.000 | -64.797 | 0.000 | -1.961 | -3.909 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -82.927 | 0.000 | 0.000 | 6.762 | 7.026 | 23.435 | 50.190 | 0.000 | 0.000 | 46.312 | 0.000 | -49.364 | 0.000 | -1.434 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 20.481 | -371.082 | 0.000 | 0.000 | 112.751 | 109.637 | 363.654 | 239.217 | 0.000 | 0.016 | 178.370 | 0.000 | -611.501 | 0.000 | -41.542 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 12.089 | -421.449 | 0.000 | 0.000 | 52.361 | 69.923 | 234.352 | 525.324 | 0.000 | 0.010 | 0.003 | 0.000 | -400.049 | 0.000 | -28.765 | -43.796 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 9.985 | -822.276 | 0.000 | 0.000 | 109.249 | 107.932 | 363.660 | 1057.934 | 0.000 | 0.015 | 0.028 | 0.000 | -624.078 | 0.000 | -44.208 | -158.212 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 6.080 | -469.321 | 0.000 | 0.000 | 71.289 | 70.151 | 234.351 | 512.542 | 0.000 | 0.009 | 31.510 | 0.000 | -427.055 | 0.000 | -29.557 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.130 | -29.641 | 0.000 | 0.000 | 11.579 | 10.963 | 36.365 | 24.884 | 0.000 | 0.002 | 0.000 | 0.000 | -56.205 | 0.000 | -4.799 | -6.277 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.458 | -38.695 | 0.000 | 0.000 | 7.304 | 6.992 | 23.435 | 53.350 | 0.000 | 0.001 | 0.000 | 0.000 | -36.876 | 0.000 | -3.336 | -19.632 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.396 | -70.761 | 0.000 | 0.000 | 11.200 | 10.793 | 36.366 | 106.859 | 0.000 | 0.002 | 0.000 | 0.000 | -57.803 | 0.000 | -5.146 | -39.907 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.717 | -41.809 | 0.000 | 0.000 | 7.309 | 7.015 | 23.435 | 51.709 | 0.000 | 0.001 | 0.001 | 0.000 | -39.873 | 0.000 | -3.470 | -9.035 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.357 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.100 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.109 | -1196.814 | 0.000 | 0.000 | 9.502 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -387.865 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.647 | -106.505 | 0.000 | 0.000 | 0.952 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.601 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7162.129 | 0.000 | 0.000 | 20.565 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -400.905 |
GROUNDFLOOR_PLENUM | 1.195 | -46.909 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 49.861 | 0.000 | 0.000 | 0.000 | -4.149 | 0.000 |
MIDFLOOR_PLENUM | 56.031 | -236.703 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.021 | 251.944 | 0.000 | 0.000 | 0.000 | -71.293 | -0.003 |
TOPFLOOR_PLENUM | 28.669 | -34.045 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 12.908 | 0.000 | 0.000 | 0.000 | -7.533 | -0.001 |
Total Facility | 85.896 | -317.657 | 88.075 | -16547.097 | 0.000 | 0.000 | 1554.553 | 2472.116 | 14676.396 | 2803.279 | 0.000 | 0.082 | 675.267 | 0.000 | -2478.506 | 0.000 | -250.447 | -2761.929 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | -110752.62 | 0.00 | 0.00 | 1313.57 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 91066.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | -89103.73 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 82628.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-JUL-04:12 | 0.00 | 0.00 | 0.00 | -747266.75 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 682516.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 27-JUN-05:03 | 0.00 | 0.00 | 0.00 | -68835.98 | 0.00 | 0.00 | 846.36 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 59804.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-15:41 | 0.00 | 0.00 | 0.00 | -12869.66 | 0.00 | 0.00 | 44.92 | 43.94 | 720.18 | 4983.11 | 0.00 | 0.00 | 7086.85 | 0.00 | -0.00 | 0.00 | -9.34 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-08:32 | 0.00 | 0.00 | 0.00 | -23198.95 | 0.00 | 0.00 | 22.08 | 28.32 | 464.11 | 19556.84 | 0.00 | 0.00 | 3310.77 | 0.00 | -0.00 | 0.00 | -183.17 | 0.00 |
PERIMETER_BOT_ZN_1 | 30-APR-14:21 | 0.00 | 0.00 | 0.00 | -33908.36 | 0.00 | 0.00 | 30.94 | 43.94 | 720.19 | 20967.74 | 0.00 | 0.00 | 12181.57 | 0.00 | -0.00 | 0.00 | -36.03 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -32567.99 | 0.00 | 0.00 | 14.53 | 28.32 | 464.11 | 21068.46 | 0.00 | 0.00 | 11065.95 | 0.00 | -0.00 | 0.00 | -73.38 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-14:50 | 0.00 | 0.00 | 0.00 | -75412.68 | 0.00 | 0.00 | 11141.35 | 7910.47 | 21605.52 | 55060.78 | 0.00 | 157.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20463.41 |
PERIMETER_MID_ZN_2 | 23-JUL-09:11 | 0.00 | 0.00 | 0.00 | -269172.17 | 0.00 | 0.00 | 180.26 | 283.19 | 4641.14 | 169458.53 | 0.00 | 0.00 | 95904.48 | 0.00 | -0.00 | 0.00 | -1295.43 | 0.00 |
PERIMETER_MID_ZN_1 | 30-APR-12:31 | 0.00 | 0.00 | 0.00 | -368584.61 | 0.00 | 0.00 | 281.25 | 439.45 | 7201.95 | 282505.74 | 0.00 | 0.00 | 79668.68 | 0.00 | -0.00 | 0.00 | -1512.46 | 0.00 |
PERIMETER_MID_ZN_4 | 09-JUL-17:21 | 0.00 | 0.00 | 0.00 | -293314.08 | 0.00 | 0.00 | 0.00 | 283.19 | 3603.49 | 202221.56 | 0.00 | 0.00 | 88649.78 | 0.00 | -0.00 | 0.00 | -1443.93 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-18:11 | 0.00 | 0.00 | 0.00 | -12091.69 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 4672.13 | 0.00 | 0.00 | 6835.98 | 0.00 | -0.00 | 0.00 | -19.54 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-09:32 | 0.00 | 0.00 | 0.00 | -24094.38 | 0.00 | 0.00 | 21.74 | 28.32 | 464.11 | 14935.96 | 0.00 | 0.00 | 8692.60 | 0.00 | -0.00 | 0.00 | -48.36 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:41 | 0.00 | 0.00 | 0.00 | -37889.91 | 0.00 | 0.00 | 29.79 | 43.94 | 720.19 | 24012.11 | 0.00 | 0.00 | 13433.10 | 0.00 | -0.00 | 0.00 | -349.22 | 0.00 |
PERIMETER_TOP_ZN_4 | 21-MAY-16:51 | 0.00 | 0.00 | 0.00 | -29519.49 | 0.00 | 0.00 | 17.37 | 28.32 | 464.11 | 19661.49 | 0.00 | 0.00 | 9540.31 | 0.00 | -0.00 | 0.00 | -192.11 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-17:51 | 0.00 | 0.00 | 0.00 | -8371.54 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 559.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-18:03 | 0.00 | 0.00 | 0.00 | -80081.43 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 1961.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 30-APR-17:51 | 0.00 | 0.00 | 0.00 | -8126.50 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 314.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-16:00 | 0.00 | 0.00 | 0.00 | -367910.16 | 0.00 | 0.00 | 2182.67 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18062.21 |
GROUNDFLOOR_PLENUM | 26-JUN-05:15 | 0.00 | -9520.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9587.50 | 0.00 | -0.00 | 0.00 | -67.32 | 0.00 |
MIDFLOOR_PLENUM | 30-DEC-05:01 | 0.00 | -73276.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82275.78 | 0.00 | -0.00 | 0.00 | -8998.79 | 0.00 |
TOPFLOOR_PLENUM | 21-JUN-13:05 | 0.00 | -16725.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16762.31 | 0.00 | -0.00 | 0.00 | -37.29 | 0.00 |
Total Facility | 30-APR-13:51 | 0.00 | 141777.77 | 0.00 | -1564921.46 | 0.00 | 0.00 | 7583.65 | 11822.20 | 583872.65 | 520833.54 | 0.00 | 0.00 | 303260.94 | 0.00 | 0.00 | 0.00 | -4229.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 67123.70 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -73598.68 |
PERIMETER_BOT_ZN_3 | 11-JAN-06:01 | 0.00 | 0.00 | 1778.87 | 0.00 | 0.00 | 0.00 | 140.07 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 2006.71 | 0.00 | -4904.71 | 0.00 | -48.65 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-JAN-06:01 | 0.00 | 0.00 | 2974.01 | 0.00 | 0.00 | 0.00 | 91.31 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3573.57 | 0.00 | -42.38 | -111.67 |
PERIMETER_BOT_ZN_1 | 10-JAN-06:01 | 0.00 | 0.00 | 7356.57 | 0.00 | 0.00 | 0.00 | 144.45 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5169.30 | 0.00 | -62.81 | -3296.65 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-05:11 | 0.00 | 0.00 | 94091.54 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35156.89 | 0.00 | -5351.96 | -61713.00 |
PERIMETER_MID_ZN_2 | 26-DEC-05:11 | 0.00 | 0.00 | 121821.45 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23564.59 | 0.00 | -3645.45 | -99850.90 |
PERIMETER_MID_ZN_1 | 28-DEC-05:11 | 0.00 | 0.00 | 169553.95 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38841.45 | 0.00 | -6820.25 | -132022.70 |
PERIMETER_MID_ZN_4 | 26-DEC-05:11 | 0.00 | 0.00 | 107991.53 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25181.94 | 0.00 | -3803.10 | -84245.94 |
PERIMETER_TOP_ZN_3 | 26-DEC-05:11 | 0.00 | 0.00 | 11802.13 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2862.62 | 0.00 | -561.19 | -9191.34 |
PERIMETER_TOP_ZN_2 | 27-NOV-05:11 | 0.00 | 0.00 | 16646.54 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1591.01 | 0.00 | -196.01 | -15383.47 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:11 | 0.00 | 0.00 | 24640.64 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3006.20 | 0.00 | -584.18 | -21863.31 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:11 | 0.00 | 0.00 | 16520.35 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2065.97 | 0.00 | -396.69 | -14581.64 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 10-JAN-04:33 | 0.00 | 0.00 | 3975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23637.61 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:40 | 0.00 | 0.00 | 587.88 | 0.00 | 0.00 | 0.00 | 5.75 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2559.82 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 30-APR-14:21 | 12746.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.79 | -12713.93 |
MIDFLOOR_PLENUM | 30-APR-14:31 | 142244.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -407.85 | -141837.04 |
TOPFLOOR_PLENUM | 02-JAN-05:12 | 20530.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20530.57 |
Total Facility | 26-DEC-05:11 | -696608.98 | 653892.81 | 628161.79 | -653892.81 | 0.00 | 0.00 | 0.00 | 10593.62 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -146851.13 | 0.00 | -32692.32 | -349902.39 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.7511 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.8653 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 103.2123 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 81.1445 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2622 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.0733 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0390 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0390 | 0.2382 | 1.0000 | Not calculated | 1.2002 | 0.2382 | ||
AIRLOOP DATACENTER BASEMENT | 24.6931 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.6932 | 0.0137 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.5033 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5033 | 0.0311 | 1.0000 | Not calculated | 0.0156 | 0.0311 | ||
AIRLOOP DATACENTER MID | 4.8353 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8353 | 0.0323 | 1.0000 | Not calculated | 0.1563 | 0.0323 | ||
AIRLOOP DATACENTER TOP | 0.4901 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4901 | 0.0319 | 1.0000 | Not calculated | 0.0156 | 0.0319 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.3755 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2818 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 51.6062 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8434 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1311 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2833 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.6931 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.6931 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.5033 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5033 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0311 | ||
AIRLOOP DATACENTER MID | 4.8353 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8353 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0323 | ||
AIRLOOP DATACENTER TOP | 0.4901 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4901 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0319 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.0390 | 5.0390 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3999 | 5.3999 | 1.6146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 50.5241 | 50.5241 | 16.1677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7828 | 4.7828 | 1.6166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7919 | 0.7919 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2616 | 1.2616 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7646 | 1.7646 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5331 | 1.5331 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1213 | 7.1213 | 2.0296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2385 | 13.2385 | 1.3106 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.2750 | 18.2750 | 2.0285 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0535 | 14.0535 | 1.3070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7960 | 0.7960 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3069 | 1.3069 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9111 | 1.9111 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4655 | 1.4655 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5033 | 0.5033 | 0.5033 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8353 | 4.8353 | 4.8353 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4901 | 0.4901 | 0.4901 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.6931 | 24.6931 | 24.6931 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.7511 | 8.8653 | 10.7511 | 2.2818 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 103.2123 | 81.1445 | 103.2123 | 22.8434 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2622 | 9.0733 | 10.2622 | 2.2833 | 0.0000 | 1.0000 |
CAV_BAS | 5.0390 | 5.0390 | 5.0390 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.6931 | 24.6932 | 24.6931 | 24.6931 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5033 | 0.5033 | 0.5033 | 0.5033 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8353 | 4.8353 | 4.8353 | 4.8353 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4901 | 0.4901 | 0.4901 | 0.4901 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7000 | 2.7000 | 1.6146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.2620 | 25.2620 | 16.1677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3914 | 2.3914 | 1.6166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3960 | 0.3960 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6308 | 0.6308 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8823 | 0.8823 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7665 | 0.7665 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5607 | 3.5607 | 2.0296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6192 | 6.6192 | 1.3106 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1375 | 9.1375 | 2.0285 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0268 | 7.0268 | 1.3070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3980 | 0.3980 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6534 | 0.6534 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9556 | 0.9556 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7327 | 0.7327 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5033 | 0.5033 | 0.5033 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8353 | 4.8353 | 4.8353 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4901 | 0.4901 | 0.4901 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.6931 | 24.6931 | 24.6931 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.3755 | 2.2818 | 2.2818 | 2.2818 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 51.6062 | 22.8434 | 22.8434 | 22.8434 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1311 | 2.2833 | 2.2833 | 2.2833 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.6931 | 24.6931 | 24.6931 | 24.6931 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5033 | 0.5033 | 0.5033 | 0.5033 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8353 | 4.8353 | 4.8353 | 4.8353 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4901 | 0.4901 | 0.4901 | 0.4901 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 16.00 |
Number of hours cooling loads not met | 516.83 |
Number of hours not met | 519.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1315.97 | 730515.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 670.47 | 308140.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2472.12 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.94 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2296.86 | 271814.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 236.64 | 37697.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 178.28 | 70679.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1142.73 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 457.40 | 52812.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25054.12 |
Natural Gas | 0.00 | 1315.97 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 26370.08 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.37 |
Space Heating | 0.00 |
Space Cooling | 14.47 |
Fans (All) | 49.59 |
Service Water Heating | 9.87 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 540.89 |
Subtotal | 540.89 |
Natural Gas [MJ/m2] | |
Space Heating | 28.41 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 28.41 |
Subtotal | 28.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.37 |
Space Heating | 4.99 |
Space Cooling | 2.54 |
Fans (All) | 8.71 |
Service Water Heating | 1.73 |
Receptacle Equipment | 55.66 |
Miscellaneous | 16.99 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 775. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8337.83 | 391.17 | 0.00 | 31.00 | 0.00 |
CORE_BOTTOM | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8717.67 | 42.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8492.33 | 267.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8719.83 | 40.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8713.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8702.50 | 57.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8719.00 | 41.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8703.50 | 56.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8021.00 | 739.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7980.17 | 779.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7949.50 | 810.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7492.17 | 1267.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
Min | 7492.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1267.83 | 0.00 | 31.00 | 0.00 |
Average | 8557.02 | 201.63 | 0.00 | 1.35 | 0.00 |
Sum | 196811.50 | 4637.50 | 0.00 | 31.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367437.67 | 1080.33 | 0.00 | 98.00 | 0.00 |
CORE_BOTTOM | 330805.00 | 8.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1706.00 | 562.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1673.50 | 594.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1654.33 | 613.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85477.50 | 17917.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367437.67 | 17917.50 | 0.00 | 98.00 | 0.00 |
Average | 79427.35 | 903.30 | 0.00 | 4.26 | 0.00 |
Sum | 1826829.00 | 20776.00 | 0.00 | 98.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8302.83 | 426.17 | 0.00 | 31.00 | 0.00 |
CORE_BOTTOM | 8653.17 | 106.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8700.83 | 59.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8716.17 | 43.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8704.67 | 55.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8528.67 | 231.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8717.00 | 43.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8710.17 | 49.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8693.67 | 66.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8699.50 | 60.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8628.67 | 131.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8615.50 | 144.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8612.00 | 148.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8022.50 | 737.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8720.50 | 39.50 | 0.00 | 0.00 | 0.00 |
Min | 8022.50 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 737.50 | 0.00 | 31.00 | 0.00 |
Average | 8651.19 | 107.46 | 0.00 | 1.35 | 0.00 |
Sum | 198977.33 | 2471.67 | 0.00 | 31.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367117.83 | 1400.17 | 0.00 | 98.00 | 0.00 |
CORE_BOTTOM | 330707.00 | 106.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330713.00 | 100.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330796.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2161.50 | 106.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2152.50 | 115.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2150.33 | 117.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92571.33 | 10823.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367117.83 | 10823.67 | 0.00 | 98.00 | 0.00 |
Average | 79774.72 | 555.93 | 0.00 | 4.26 | 0.00 |
Sum | 1834818.50 | 12786.50 | 0.00 | 98.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447016E+11 | 111123.50 | 02-JAN-07:03 | 1.83 | 1.41 | 0.568558E+10 | 7565.05 | 02-JAN-10:09 | 2.17 | 0.99 |
February | 0.406334E+11 | 95235.04 | 21-FEB-07:05 | 4.00 | 4.00 | 0.515234E+10 | 7499.22 | 22-FEB-10:09 | 8.33 | 8.16 |
March | 0.496039E+11 | 96996.31 | 27-MAR-06:03 | 0.33 | -0.3 | 0.615018E+10 | 7499.33 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.503566E+11 | 96456.63 | 24-APR-06:05 | 7.50 | 4.86 | 0.547079E+10 | 7499.54 | 14-APR-13:00 | 7.50 | 4.86 |
May | 0.507026E+11 | 97894.25 | 30-MAY-06:05 | 8.83 | 7.86 | 0.592166E+10 | 7499.26 | 16-MAY-13:20 | 8.83 | 7.86 |
June | 0.527053E+11 | 101625.20 | 19-JUN-06:11 | 11.33 | 10.03 | 0.590621E+10 | 7546.38 | 21-JUN-13:20 | 21.93 | 15.70 |
July | 0.535356E+11 | 102007.13 | 03-JUL-06:11 | 11.00 | 7.66 | 0.549860E+10 | 7502.00 | 10-JUL-09:09 | 23.17 | 16.22 |
August | 0.590587E+11 | 102137.63 | 21-AUG-06:11 | 12.00 | 10.66 | 0.616539E+10 | 7639.26 | 28-AUG-13:50 | 22.83 | 15.32 |
September | 0.508667E+11 | 102371.61 | 25-SEP-06:11 | 11.33 | 9.54 | 0.547350E+10 | 7499.49 | 06-SEP-09:09 | 11.33 | 9.54 |
October | 0.509722E+11 | 104734.47 | 10-OCT-06:11 | 10.67 | 10.67 | 0.569130E+10 | 7499.43 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.489101E+11 | 99358.46 | 24-NOV-07:11 | 11.00 | 10.48 | 0.563266E+10 | 7499.31 | 07-NOV-14:09 | 11.00 | 10.48 |
December | 0.465962E+11 | 97437.74 | 26-DEC-07:05 | 1.83 | 0.22 | 0.548603E+10 | 7499.36 | 04-DEC-14:00 | 1.83 | 0.22 |
Annual Sum or Average | 0.598643E+12 | 0.682343E+11 | ||||||||
Minimum of Months | 0.406334E+11 | 95235.04 | 0.33 | -0.3 | 0.515234E+10 | 7499.22 | 1.83 | 0.22 | ||
Maximum of Months | 0.590587E+11 | 111123.50 | 12.00 | 10.67 | 0.616539E+10 | 7639.26 | 23.17 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367361E+11 | 88619.44 | 02-JAN-04:01 | 1.17 | 0.70 | 0.507022E+10 | 6734.80 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.357614E+11 | 81772.70 | 21-FEB-05:11 | 5.37 | 4.72 | 0.460281E+10 | 6734.81 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.464124E+11 | 82938.60 | 20-MAR-04:12 | 5.33 | 4.89 | 0.550114E+10 | 6734.79 | 06-MAR-10:20 | 5.33 | 4.89 |
April | 0.531063E+11 | 87445.80 | 24-APR-04:12 | 7.00 | 5.73 | 0.488409E+10 | 6735.07 | 14-APR-13:00 | 7.00 | 5.73 |
May | 0.484498E+11 | 85883.87 | 01-MAY-04:12 | 4.67 | 3.91 | 0.528627E+10 | 6734.80 | 04-MAY-09:20 | 9.00 | 8.10 |
June | 0.534077E+11 | 85423.96 | 26-JUN-04:13 | 12.67 | 11.59 | 0.527112E+10 | 6806.20 | 21-JUN-13:20 | 12.67 | 11.59 |
July | 0.576210E+11 | 87675.36 | 05-JUL-04:12 | 7.67 | 6.81 | 0.489825E+10 | 6734.84 | 03-JUL-09:09 | 7.67 | 6.81 |
August | 0.645242E+11 | 85031.48 | 31-AUG-04:13 | 11.83 | 11.83 | 0.549962E+10 | 6803.39 | 28-AUG-13:50 | 11.83 | 11.83 |
September | 0.476994E+11 | 87306.75 | 05-SEP-04:12 | 6.67 | 6.14 | 0.488004E+10 | 6734.97 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.448832E+11 | 89111.07 | 10-OCT-04:12 | 10.33 | 10.33 | 0.508123E+10 | 6734.94 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.431925E+11 | 87877.13 | 13-NOV-05:11 | 3.33 | 3.18 | 0.503113E+10 | 6734.79 | 10-NOV-10:09 | 3.33 | 3.18 |
December | 0.415642E+11 | 85154.44 | 26-DEC-05:11 | 1.97 | 0.30 | 0.490124E+10 | 6734.82 | 20-DEC-10:09 | 1.97 | 0.30 |
Annual Sum or Average | 0.573358E+12 | 0.609072E+11 | ||||||||
Minimum of Months | 0.357614E+11 | 81772.70 | 1.17 | 0.30 | 0.460281E+10 | 6734.79 | 1.97 | 0.30 | ||
Maximum of Months | 0.645242E+11 | 89111.07 | 12.67 | 11.83 | 0.550114E+10 | 6806.20 | 13.33 | 11.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240432E+11 | 60967.34 | 26-JAN-06:02 | 5.00 | 4.51 | 0.493342E+10 | 6734.78 | 20-JAN-10:20 | 5.00 | 4.51 |
February | 0.232277E+11 | 48192.43 | 10-FEB-06:03 | 5.00 | 4.51 | 0.451499E+10 | 6734.78 | 17-FEB-10:20 | 4.00 | 2.99 |
March | 0.291826E+11 | 67624.79 | 24-MAR-05:02 | 4.00 | 3.12 | 0.543148E+10 | 6734.76 | 28-MAR-13:20 | 10.33 | 6.95 |
April | 0.343257E+11 | 73918.68 | 21-APR-05:02 | 8.00 | 6.97 | 0.486451E+10 | 6734.87 | 25-APR-13:09 | 13.67 | 9.46 |
May | 0.379190E+11 | 73693.49 | 02-MAY-05:02 | 4.17 | 3.22 | 0.527013E+10 | 6734.78 | 12-MAY-13:20 | 12.67 | 10.13 |
June | 0.407603E+11 | 74540.92 | 27-JUN-04:12 | 14.00 | 14.00 | 0.526305E+10 | 6740.95 | 21-JUN-13:20 | 14.00 | 14.00 |
July | 0.408624E+11 | 74731.92 | 25-JUL-04:12 | 13.00 | 12.63 | 0.488774E+10 | 6734.81 | 13-JUL-13:20 | 13.00 | 12.63 |
August | 0.440377E+11 | 74337.61 | 17-AUG-04:11 | 13.07 | 12.82 | 0.549067E+10 | 6734.82 | 23-AUG-09:20 | 16.33 | 12.16 |
September | 0.376850E+11 | 73778.04 | 16-SEP-05:02 | 14.00 | 13.42 | 0.486801E+10 | 6734.88 | 06-SEP-09:09 | 14.00 | 13.42 |
October | 0.306228E+11 | 71727.14 | 04-OCT-05:02 | 3.00 | 3.00 | 0.503763E+10 | 6734.86 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.256335E+11 | 66767.28 | 09-NOV-06:02 | 9.00 | 9.00 | 0.494653E+10 | 6734.75 | 10-NOV-10:09 | 11.00 | 9.41 |
December | 0.221966E+11 | 25478.47 | 22-DEC-17:00 | 5.00 | 4.08 | 0.471188E+10 | 6734.78 | 20-DEC-10:30 | 5.00 | 4.08 |
Annual Sum or Average | 0.390496E+12 | 0.602200E+11 | ||||||||
Minimum of Months | 0.221966E+11 | 25478.47 | 3.00 | 3.00 | 0.451499E+10 | 6734.75 | 4.00 | 2.99 | ||
Maximum of Months | 0.440377E+11 | 74731.92 | 14.00 | 14.00 | 0.549067E+10 | 6740.95 | 16.33 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160143E+11 | 18855.40 | 19-JAN-17:00 | 6.00 | 6.00 | 0.424717E+10 | 6734.27 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.159219E+11 | 18821.81 | 24-FEB-17:00 | 6.00 | 4.60 | 0.396747E+10 | 6686.70 | 24-FEB-14:00 | 6.00 | 4.60 |
March | 0.206566E+11 | 24773.78 | 31-MAR-16:00 | 9.00 | 4.96 | 0.493258E+10 | 6734.69 | 31-MAR-13:20 | 9.00 | 4.96 |
April | 0.278823E+11 | 54694.11 | 21-APR-05:02 | 8.00 | 6.97 | 0.474298E+10 | 6734.92 | 14-APR-13:00 | 8.00 | 6.97 |
May | 0.323650E+11 | 64321.83 | 01-MAY-05:03 | 4.33 | 3.72 | 0.518795E+10 | 6734.75 | 12-MAY-09:20 | 11.33 | 9.72 |
June | 0.380017E+11 | 68848.10 | 27-JUN-05:03 | 14.17 | 14.17 | 0.523167E+10 | 6771.84 | 21-JUN-13:20 | 14.17 | 14.17 |
July | 0.388868E+11 | 68185.20 | 18-JUL-05:03 | 16.00 | 14.13 | 0.486397E+10 | 6734.76 | 03-JUL-09:20 | 16.00 | 14.13 |
August | 0.406445E+11 | 66784.43 | 07-AUG-05:02 | 10.17 | 9.06 | 0.546535E+10 | 6734.80 | 08-AUG-09:00 | 18.00 | 14.98 |
September | 0.317800E+11 | 64517.92 | 13-SEP-05:03 | 9.33 | 9.25 | 0.480131E+10 | 6734.83 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.215483E+11 | 31166.30 | 03-OCT-16:00 | 14.00 | 8.96 | 0.470277E+10 | 6734.67 | 18-OCT-13:30 | 13.50 | 12.07 |
November | 0.173918E+11 | 23184.75 | 10-NOV-16:30 | 9.00 | 7.52 | 0.437607E+10 | 6734.38 | 09-NOV-14:00 | 9.00 | 7.52 |
December | 0.147428E+11 | 15997.16 | 21-DEC-17:00 | 6.00 | 5.49 | 0.404777E+10 | 6499.79 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.315836E+12 | 0.565671E+11 | ||||||||
Minimum of Months | 0.147428E+11 | 15997.16 | 4.33 | 3.72 | 0.396747E+10 | 6499.79 | 6.00 | 4.60 | ||
Maximum of Months | 0.406445E+11 | 68848.10 | 16.00 | 14.17 | 0.546535E+10 | 6771.84 | 18.00 | 14.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242575E+10 | 2667.39 | 17-JAN-13:40 | 11.47 | 7.70 | 0.576633E+09 | 845.62 | 25-JAN-14:39 | 11.00 | 9.22 |
February | 0.243066E+10 | 3270.94 | 21-FEB-13:40 | 9.00 | 7.76 | 0.541784E+09 | 845.63 | 21-FEB-10:20 | 9.00 | 7.76 |
March | 0.350678E+10 | 5063.11 | 20-MAR-12:30 | 10.10 | 6.57 | 0.668887E+09 | 845.63 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.540857E+10 | 7115.20 | 28-APR-14:00 | 20.00 | 12.76 | 0.607733E+09 | 845.67 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.546007E+10 | 7218.40 | 22-MAY-15:00 | 24.00 | 16.08 | 0.658728E+09 | 845.63 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.728173E+10 | 12869.16 | 25-JUN-15:41 | 24.83 | 14.82 | 0.660838E+09 | 869.42 | 21-JUN-13:20 | 24.83 | 14.82 |
July | 0.805132E+10 | 10181.87 | 24-JUL-05:02 | 13.00 | 13.00 | 0.614642E+09 | 845.94 | 10-JUL-13:09 | 13.00 | 13.00 |
August | 0.821876E+10 | 8259.68 | 14-AUG-15:20 | 25.33 | 15.98 | 0.689631E+09 | 857.98 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.507746E+10 | 6497.47 | 13-SEP-14:20 | 23.00 | 16.22 | 0.607306E+09 | 845.64 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.357923E+10 | 5655.85 | 10-OCT-13:10 | 13.00 | 11.87 | 0.622466E+09 | 845.63 | 12-OCT-09:30 | 9.00 | 9.00 |
November | 0.284954E+10 | 3588.58 | 08-NOV-14:30 | 12.00 | 11.73 | 0.604264E+09 | 845.62 | 10-NOV-10:09 | 11.00 | 9.41 |
December | 0.252161E+10 | 2445.35 | 11-DEC-06:02 | 3.17 | 3.09 | 0.569335E+09 | 845.61 | 21-DEC-14:20 | 8.00 | 6.98 |
Annual Sum or Average | 0.568115E+11 | 0.742225E+10 | ||||||||
Minimum of Months | 0.242575E+10 | 2445.35 | 3.17 | 3.09 | 0.541784E+09 | 845.61 | 8.00 | 6.98 | ||
Maximum of Months | 0.821876E+10 | 12869.16 | 25.33 | 16.22 | 0.689631E+09 | 869.42 | 24.83 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171088E+10 | 4567.67 | 20-JAN-10:10 | 4.33 | 3.91 | 0.377081E+09 | 544.95 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.180938E+10 | 5907.02 | 17-FEB-09:45 | 2.67 | 1.90 | 0.350789E+09 | 544.96 | 17-FEB-10:20 | 4.00 | 2.99 |
March | 0.234952E+10 | 5414.13 | 25-MAR-09:25 | 10.00 | 7.02 | 0.428115E+09 | 544.96 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.588998E+10 | 22689.19 | 30-APR-08:21 | 17.70 | 12.30 | 0.392763E+09 | 544.98 | 14-APR-13:50 | 17.70 | 12.30 |
May | 0.611493E+10 | 22967.80 | 21-MAY-07:32 | 12.23 | 9.52 | 0.426031E+09 | 545.76 | 23-MAY-09:30 | 19.50 | 14.70 |
June | 0.694459E+10 | 23199.11 | 18-JUN-08:32 | 13.67 | 11.08 | 0.426124E+09 | 547.44 | 21-JUN-13:20 | 21.93 | 15.70 |
July | 0.745696E+10 | 22441.80 | 23-JUL-08:42 | 19.83 | 15.59 | 0.396756E+09 | 546.22 | 10-JUL-09:00 | 19.83 | 15.59 |
August | 0.786048E+10 | 22007.77 | 06-AUG-09:42 | 15.83 | 13.53 | 0.444772E+09 | 551.79 | 28-AUG-13:50 | 22.83 | 15.32 |
September | 0.592853E+10 | 19933.29 | 04-SEP-08:52 | 14.00 | 10.69 | 0.393967E+09 | 545.11 | 11-SEP-09:09 | 18.83 | 15.23 |
October | 0.308153E+10 | 11080.72 | 01-OCT-08:33 | 11.00 | 8.32 | 0.399943E+09 | 544.96 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.186753E+10 | 5300.60 | 13-NOV-09:25 | 8.00 | 7.22 | 0.384912E+09 | 544.95 | 13-NOV-10:20 | 8.33 | 7.62 |
December | 0.160852E+10 | 3436.18 | 26-DEC-10:10 | 3.17 | 1.00 | 0.358935E+09 | 544.95 | 20-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.526228E+11 | 0.478019E+10 | ||||||||
Minimum of Months | 0.160852E+10 | 3436.18 | 2.67 | 1.00 | 0.350789E+09 | 544.95 | 3.17 | 1.00 | ||
Maximum of Months | 0.786048E+10 | 23199.11 | 19.83 | 15.59 | 0.444772E+09 | 551.79 | 22.83 | 15.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422766E+10 | 27970.68 | 15-JAN-13:43 | 9.17 | 6.97 | 0.587364E+09 | 845.65 | 20-JAN-10:00 | 6.00 | 5.49 |
February | 0.487417E+10 | 29902.07 | 19-FEB-13:32 | 6.00 | 4.14 | 0.545145E+09 | 845.65 | 17-FEB-10:00 | 6.00 | 4.14 |
March | 0.440691E+10 | 12735.62 | 28-MAR-12:05 | 11.67 | 7.18 | 0.659559E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.102369E+11 | 33905.21 | 30-APR-14:21 | 23.50 | 12.96 | 0.607674E+09 | 846.85 | 27-APR-13:00 | 23.50 | 12.96 |
May | 0.832956E+10 | 30163.83 | 21-MAY-13:32 | 17.00 | 10.30 | 0.657033E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.935928E+10 | 29235.78 | 25-JUN-15:41 | 24.83 | 14.82 | 0.660192E+09 | 869.97 | 21-JUN-13:20 | 24.83 | 14.82 |
July | 0.109793E+11 | 29859.53 | 09-JUL-12:53 | 19.00 | 14.79 | 0.614972E+09 | 845.66 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.135485E+11 | 32306.28 | 06-AUG-12:22 | 17.00 | 13.49 | 0.690616E+09 | 869.20 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.117980E+11 | 31056.50 | 04-SEP-12:12 | 16.33 | 12.00 | 0.610567E+09 | 847.10 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.735767E+10 | 32080.15 | 01-OCT-13:12 | 12.33 | 9.63 | 0.618622E+09 | 846.89 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.448944E+10 | 23181.21 | 11-NOV-13:13 | 9.00 | 7.29 | 0.598073E+09 | 845.64 | 13-NOV-10:20 | 8.33 | 7.62 |
December | 0.350059E+10 | 16115.18 | 18-DEC-13:30 | 8.00 | 5.46 | 0.563532E+09 | 845.64 | 20-DEC-10:09 | 8.17 | 7.53 |
Annual Sum or Average | 0.931080E+11 | 0.741335E+10 | ||||||||
Minimum of Months | 0.350059E+10 | 12735.62 | 6.00 | 4.14 | 0.545145E+09 | 845.64 | 6.00 | 4.14 | ||
Maximum of Months | 0.135485E+11 | 33905.21 | 24.83 | 14.82 | 0.690616E+09 | 869.97 | 24.83 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234604E+10 | 8277.64 | 30-JAN-16:35 | 7.37 | 6.68 | 0.396586E+09 | 544.95 | 23-JAN-10:20 | 7.37 | 6.68 |
February | 0.341418E+10 | 17474.32 | 19-FEB-16:12 | 5.33 | 4.26 | 0.369459E+09 | 544.96 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.512246E+10 | 11817.99 | 24-MAR-05:02 | 4.00 | 3.12 | 0.444850E+09 | 544.96 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.973196E+10 | 29483.21 | 30-APR-14:21 | 23.50 | 12.96 | 0.396328E+09 | 544.99 | 14-APR-13:50 | 23.50 | 12.96 |
May | 0.766408E+10 | 30731.96 | 21-MAY-16:51 | 20.00 | 12.79 | 0.427853E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.102847E+11 | 30549.41 | 25-JUN-17:41 | 21.83 | 18.99 | 0.427566E+09 | 548.44 | 21-JUN-13:20 | 21.83 | 18.99 |
July | 0.120098E+11 | 32567.24 | 09-JUL-16:51 | 21.00 | 15.03 | 0.398115E+09 | 544.96 | 03-JUL-09:09 | 21.00 | 15.03 |
August | 0.129606E+11 | 28424.51 | 20-AUG-16:41 | 22.33 | 14.82 | 0.446543E+09 | 555.44 | 28-AUG-13:50 | 22.83 | 15.32 |
September | 0.691342E+10 | 25832.24 | 04-SEP-14:52 | 16.00 | 11.55 | 0.395241E+09 | 544.97 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.486700E+10 | 25689.09 | 01-OCT-15:12 | 12.67 | 9.64 | 0.410582E+09 | 544.97 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.400419E+10 | 14986.02 | 09-NOV-06:02 | 9.00 | 9.00 | 0.406297E+09 | 544.96 | 07-NOV-14:09 | 9.00 | 9.00 |
December | 0.360923E+10 | 12109.72 | 11-DEC-06:01 | 3.17 | 3.09 | 0.395861E+09 | 544.96 | 20-DEC-10:09 | 8.17 | 7.53 |
Annual Sum or Average | 0.829276E+11 | 0.491528E+10 | ||||||||
Minimum of Months | 0.234604E+10 | 8277.64 | 3.17 | 3.09 | 0.369459E+09 | 544.95 | 7.37 | 6.68 | ||
Maximum of Months | 0.129606E+11 | 32567.24 | 23.50 | 18.99 | 0.446543E+09 | 555.44 | 23.50 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116738E+10 | 1812.70 | 15-JAN-12:52 | 10.00 | 6.68 | 0.495223E+09 | 762.84 | 19-JAN-14:00 | 9.00 | 7.43 |
February | 0.132951E+10 | 1784.64 | 19-FEB-13:02 | 6.00 | 4.15 | 0.461117E+09 | 753.77 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.208706E+10 | 2062.57 | 30-MAR-14:10 | 12.83 | 7.23 | 0.586874E+09 | 842.88 | 30-MAR-13:00 | 12.83 | 7.23 |
April | 0.323233E+10 | 5490.74 | 28-APR-14:00 | 20.00 | 12.76 | 0.580500E+09 | 845.64 | 25-APR-13:09 | 20.00 | 12.76 |
May | 0.400116E+10 | 6037.18 | 22-MAY-15:00 | 24.00 | 16.08 | 0.642929E+09 | 845.63 | 12-MAY-13:20 | 24.00 | 16.08 |
June | 0.546489E+10 | 7540.97 | 13-JUN-14:50 | 25.85 | 17.77 | 0.656181E+09 | 858.83 | 21-JUN-13:20 | 21.93 | 15.70 |
July | 0.573842E+10 | 7481.41 | 10-JUL-15:00 | 23.00 | 16.69 | 0.610384E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.549066E+10 | 6478.07 | 14-AUG-16:00 | 26.00 | 15.86 | 0.682574E+09 | 845.63 | 11-AUG-13:20 | 26.00 | 15.86 |
September | 0.380149E+10 | 5677.97 | 13-SEP-15:20 | 23.00 | 16.22 | 0.592400E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.232870E+10 | 3115.18 | 06-OCT-15:30 | 17.00 | 9.21 | 0.564041E+09 | 845.62 | 02-OCT-13:20 | 17.00 | 9.21 |
November | 0.160201E+10 | 2094.05 | 09-NOV-06:02 | 9.00 | 9.00 | 0.509761E+09 | 794.91 | 10-NOV-14:00 | 12.00 | 8.42 |
December | 0.864667E+09 | 1619.91 | 21-DEC-14:50 | 8.00 | 6.98 | 0.462298E+09 | 707.75 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.371083E+11 | 0.684428E+10 | ||||||||
Minimum of Months | 0.864667E+09 | 1619.91 | 6.00 | 4.15 | 0.461117E+09 | 707.75 | 8.00 | 6.98 | ||
Maximum of Months | 0.573842E+10 | 7540.97 | 26.00 | 17.77 | 0.682574E+09 | 858.83 | 26.00 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720747E+09 | 4224.81 | 20-JAN-11:05 | 6.33 | 5.61 | 0.245114E+09 | 548.49 | 20-JAN-11:09 | 6.33 | 5.61 |
February | 0.894751E+09 | 5254.71 | 24-FEB-11:05 | 6.00 | 4.60 | 0.233539E+09 | 548.49 | 17-FEB-11:09 | 6.00 | 4.60 |
March | 0.125824E+10 | 5613.00 | 25-MAR-10:05 | 11.08 | 8.00 | 0.289931E+09 | 548.49 | 28-MAR-12:09 | 11.67 | 7.18 |
April | 0.496902E+10 | 24440.98 | 30-APR-07:52 | 17.40 | 12.62 | 0.286150E+09 | 548.52 | 14-APR-14:09 | 17.40 | 12.62 |
May | 0.539951E+10 | 22661.12 | 21-MAY-09:02 | 13.00 | 9.47 | 0.311122E+09 | 548.50 | 22-MAY-14:09 | 23.17 | 15.81 |
June | 0.632670E+10 | 21352.52 | 25-JUN-09:52 | 18.00 | 12.90 | 0.313107E+09 | 548.51 | 09-JUN-14:09 | 18.00 | 12.90 |
July | 0.676060E+10 | 26919.34 | 23-JUL-09:11 | 20.33 | 15.77 | 0.293028E+09 | 548.50 | 24-JUL-12:09 | 19.00 | 15.90 |
August | 0.702759E+10 | 24198.76 | 13-AUG-09:32 | 15.67 | 13.47 | 0.326893E+09 | 548.51 | 14-AUG-10:09 | 22.00 | 16.44 |
September | 0.530028E+10 | 23241.04 | 24-SEP-09:02 | 18.00 | 14.39 | 0.288942E+09 | 548.51 | 07-SEP-10:09 | 18.00 | 14.39 |
October | 0.208048E+10 | 10497.86 | 01-OCT-09:33 | 12.67 | 8.99 | 0.278567E+09 | 548.49 | 03-OCT-10:09 | 13.00 | 9.30 |
November | 0.916371E+09 | 4458.31 | 03-NOV-10:05 | 7.33 | 5.22 | 0.251805E+09 | 548.49 | 03-NOV-12:09 | 9.00 | 5.66 |
December | 0.490260E+09 | 2249.56 | 08-DEC-11:05 | 6.17 | 4.24 | 0.227433E+09 | 539.35 | 08-DEC-11:09 | 6.17 | 4.24 |
Annual Sum or Average | 0.421445E+11 | 0.334563E+10 | ||||||||
Minimum of Months | 0.490260E+09 | 2249.56 | 6.00 | 4.24 | 0.227433E+09 | 539.35 | 6.00 | 4.24 | ||
Maximum of Months | 0.702759E+10 | 26919.34 | 20.33 | 15.77 | 0.326893E+09 | 548.52 | 23.17 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352891E+10 | 32033.89 | 15-JAN-12:52 | 10.00 | 6.68 | 0.561021E+09 | 845.65 | 20-JAN-10:00 | 6.00 | 5.49 |
February | 0.429891E+10 | 30396.80 | 19-FEB-13:02 | 6.00 | 4.15 | 0.522382E+09 | 846.13 | 17-FEB-14:39 | 6.00 | 4.15 |
March | 0.335575E+10 | 11773.16 | 28-MAR-12:05 | 11.67 | 7.18 | 0.626483E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.906802E+10 | 36852.63 | 30-APR-12:31 | 22.00 | 13.38 | 0.597152E+09 | 847.32 | 26-APR-13:20 | 22.00 | 13.38 |
May | 0.769414E+10 | 30078.73 | 21-MAY-12:23 | 16.50 | 9.71 | 0.648923E+09 | 845.68 | 02-MAY-13:30 | 16.50 | 9.71 |
June | 0.826706E+10 | 28664.25 | 11-JUN-13:13 | 18.00 | 14.39 | 0.656089E+09 | 855.75 | 21-JUN-13:20 | 21.93 | 15.70 |
July | 0.954481E+10 | 33313.09 | 30-JUL-13:22 | 17.00 | 12.42 | 0.611866E+09 | 845.67 | 25-JUL-13:30 | 17.00 | 12.42 |
August | 0.119247E+11 | 33817.20 | 13-AUG-12:52 | 21.00 | 15.45 | 0.687122E+09 | 847.60 | 14-AUG-13:20 | 24.00 | 16.90 |
September | 0.119348E+11 | 35054.41 | 10-SEP-11:51 | 21.00 | 15.44 | 0.606845E+09 | 847.45 | 01-SEP-13:20 | 21.00 | 15.44 |
October | 0.692068E+10 | 31405.67 | 01-OCT-13:32 | 12.67 | 9.47 | 0.597914E+09 | 847.14 | 11-OCT-13:20 | 16.00 | 10.47 |
November | 0.355654E+10 | 33605.27 | 11-NOV-13:02 | 9.00 | 7.36 | 0.561462E+09 | 845.67 | 10-NOV-14:50 | 9.00 | 7.36 |
December | 0.213380E+10 | 14902.03 | 18-DEC-13:30 | 8.00 | 5.46 | 0.517637E+09 | 845.64 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.822282E+11 | 0.719490E+10 | ||||||||
Minimum of Months | 0.213380E+10 | 11773.16 | 6.00 | 4.15 | 0.517637E+09 | 845.64 | 6.00 | 4.15 | ||
Maximum of Months | 0.119348E+11 | 36852.63 | 22.00 | 15.45 | 0.687122E+09 | 855.75 | 24.00 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112835E+10 | 4633.09 | 30-JAN-16:27 | 7.55 | 6.78 | 0.337568E+09 | 544.94 | 25-JAN-14:39 | 7.55 | 6.78 |
February | 0.157059E+10 | 7552.06 | 27-FEB-16:30 | 8.00 | 6.72 | 0.319814E+09 | 544.95 | 27-FEB-14:09 | 8.00 | 6.72 |
March | 0.186763E+10 | 8123.63 | 23-MAR-16:40 | 10.00 | 6.65 | 0.397379E+09 | 544.95 | 28-MAR-13:39 | 10.67 | 6.86 |
April | 0.482991E+10 | 27446.79 | 30-APR-17:51 | 24.00 | 13.13 | 0.384480E+09 | 544.97 | 14-APR-13:00 | 24.00 | 13.13 |
May | 0.565183E+10 | 26449.27 | 28-MAY-17:01 | 12.00 | 7.59 | 0.419959E+09 | 544.96 | 22-MAY-13:00 | 12.00 | 7.59 |
June | 0.720298E+10 | 25463.19 | 11-JUN-17:12 | 14.00 | 12.24 | 0.424945E+09 | 545.89 | 21-JUN-13:20 | 21.93 | 15.70 |
July | 0.781579E+10 | 29331.18 | 09-JUL-17:21 | 21.00 | 15.03 | 0.395577E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.728948E+10 | 25914.12 | 13-AUG-16:51 | 19.00 | 14.78 | 0.443703E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.497263E+10 | 26003.81 | 10-SEP-15:51 | 21.00 | 16.54 | 0.388661E+09 | 544.96 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.243903E+10 | 10350.14 | 03-OCT-15:40 | 14.00 | 8.96 | 0.377820E+09 | 544.95 | 12-OCT-13:30 | 11.50 | 10.11 |
November | 0.136648E+10 | 4749.94 | 10-NOV-15:30 | 11.50 | 8.42 | 0.346872E+09 | 544.95 | 10-NOV-14:50 | 11.50 | 8.42 |
December | 0.798035E+09 | 1978.58 | 21-DEC-14:40 | 8.00 | 6.98 | 0.311127E+09 | 544.94 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.469327E+11 | 0.454790E+10 | ||||||||
Minimum of Months | 0.798035E+09 | 1978.58 | 7.55 | 6.65 | 0.311127E+09 | 544.94 | 7.55 | 6.72 | ||
Maximum of Months | 0.781579E+10 | 29331.18 | 24.00 | 16.54 | 0.443703E+09 | 545.89 | 24.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418385E+09 | 1630.71 | 19-JAN-15:40 | 8.33 | 7.46 | 0.470750E+09 | 705.80 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.581456E+09 | 1572.87 | 24-FEB-16:10 | 6.00 | 4.60 | 0.430452E+09 | 690.75 | 03-FEB-14:00 | 6.00 | 4.60 |
March | 0.124809E+10 | 1899.98 | 30-MAR-15:50 | 12.00 | 5.94 | 0.538399E+09 | 783.86 | 30-MAR-13:00 | 12.00 | 5.94 |
April | 0.262057E+10 | 5688.57 | 28-APR-15:20 | 20.07 | 13.24 | 0.551808E+09 | 845.64 | 14-APR-13:00 | 20.07 | 13.24 |
May | 0.345863E+10 | 6662.35 | 22-MAY-15:00 | 24.00 | 16.08 | 0.616397E+09 | 845.63 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.509519E+10 | 12095.31 | 25-JUN-18:11 | 21.23 | 18.83 | 0.646699E+09 | 850.65 | 21-JUN-13:20 | 21.23 | 18.83 |
July | 0.546919E+10 | 8167.27 | 10-JUL-15:00 | 23.00 | 16.69 | 0.604530E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.510005E+10 | 7013.47 | 14-AUG-16:00 | 26.00 | 15.86 | 0.673000E+09 | 845.63 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.323300E+10 | 5869.38 | 13-SEP-15:30 | 23.00 | 16.22 | 0.571486E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.152979E+10 | 2342.06 | 06-OCT-15:50 | 17.00 | 9.21 | 0.515329E+09 | 829.39 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.669012E+09 | 1759.66 | 10-NOV-15:30 | 11.50 | 8.42 | 0.473015E+09 | 747.93 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.218057E+09 | 1420.14 | 21-DEC-14:50 | 8.00 | 6.98 | 0.448644E+09 | 651.05 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.296414E+11 | 0.654051E+10 | ||||||||
Minimum of Months | 0.218057E+09 | 1420.14 | 6.00 | 4.60 | 0.430452E+09 | 651.05 | 6.00 | 4.60 | ||
Maximum of Months | 0.546919E+10 | 12095.31 | 26.00 | 18.83 | 0.673000E+09 | 850.65 | 24.00 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438831E+09 | 1297.71 | 20-JAN-10:40 | 5.33 | 4.86 | 0.310116E+09 | 535.34 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.593867E+09 | 2243.20 | 24-FEB-10:30 | 5.50 | 4.13 | 0.293343E+09 | 544.95 | 17-FEB-10:20 | 5.50 | 4.13 |
March | 0.998271E+09 | 1940.75 | 25-MAR-09:25 | 10.00 | 7.02 | 0.362333E+09 | 544.94 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.447992E+10 | 22477.07 | 30-APR-09:22 | 19.00 | 12.37 | 0.382698E+09 | 544.98 | 14-APR-13:50 | 19.00 | 12.37 |
May | 0.500158E+10 | 22582.35 | 21-MAY-09:31 | 13.00 | 9.98 | 0.416797E+09 | 545.81 | 23-MAY-09:50 | 19.83 | 14.63 |
June | 0.623406E+10 | 24093.70 | 25-JUN-09:32 | 17.33 | 12.62 | 0.423031E+09 | 545.75 | 13-JUN-09:00 | 17.33 | 12.62 |
July | 0.667749E+10 | 23719.36 | 23-JUL-09:22 | 20.50 | 15.83 | 0.395163E+09 | 545.71 | 10-JUL-09:00 | 20.50 | 15.83 |
August | 0.692943E+10 | 23591.84 | 13-AUG-10:02 | 16.33 | 13.74 | 0.441857E+09 | 545.25 | 14-AUG-09:39 | 21.67 | 16.11 |
September | 0.488059E+10 | 22428.86 | 10-SEP-09:42 | 17.83 | 14.32 | 0.387943E+09 | 544.98 | 06-SEP-09:09 | 17.83 | 14.32 |
October | 0.162522E+10 | 6245.65 | 04-OCT-10:00 | 13.00 | 9.81 | 0.354563E+09 | 544.95 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.576876E+09 | 1270.72 | 03-NOV-10:00 | 7.00 | 5.17 | 0.312962E+09 | 525.15 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.258764E+09 | 1093.37 | 06-DEC-10:30 | 5.50 | 4.16 | 0.292474E+09 | 472.17 | 06-DEC-10:39 | 6.00 | 4.49 |
Annual Sum or Average | 0.386949E+11 | 0.437328E+10 | ||||||||
Minimum of Months | 0.258764E+09 | 1093.37 | 5.33 | 4.13 | 0.292474E+09 | 472.17 | 5.50 | 4.13 | ||
Maximum of Months | 0.692943E+10 | 24093.70 | 20.50 | 15.83 | 0.441857E+09 | 545.81 | 21.67 | 16.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216921E+10 | 13625.42 | 11-JAN-13:35 | -1.3 | -2.8 | 0.525906E+09 | 845.64 | 17-JAN-14:39 | 10.67 | 7.88 |
February | 0.293204E+10 | 17662.79 | 17-FEB-13:40 | 6.00 | 3.25 | 0.492839E+09 | 845.64 | 27-FEB-14:09 | 8.83 | 7.77 |
March | 0.220742E+10 | 9128.44 | 28-MAR-12:20 | 11.33 | 7.17 | 0.584293E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.805553E+10 | 34802.81 | 30-APR-13:22 | 22.50 | 12.93 | 0.579634E+09 | 846.59 | 28-APR-13:39 | 22.50 | 12.93 |
May | 0.691129E+10 | 32846.24 | 21-MAY-13:32 | 17.00 | 10.30 | 0.630768E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.789027E+10 | 31878.22 | 25-JUN-16:11 | 23.67 | 14.60 | 0.647338E+09 | 846.32 | 21-JUN-13:20 | 23.67 | 14.60 |
July | 0.922863E+10 | 34373.55 | 30-JUL-13:22 | 17.00 | 12.42 | 0.606842E+09 | 845.68 | 21-JUL-13:09 | 17.00 | 12.42 |
August | 0.114846E+11 | 35546.75 | 06-AUG-14:11 | 18.00 | 13.90 | 0.681119E+09 | 846.56 | 29-AUG-13:00 | 18.00 | 13.90 |
September | 0.110026E+11 | 37898.27 | 10-SEP-13:41 | 21.00 | 15.91 | 0.596308E+09 | 846.65 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.550126E+10 | 32908.92 | 01-OCT-14:01 | 13.00 | 9.37 | 0.563477E+09 | 846.38 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.219847E+10 | 26008.30 | 11-NOV-13:32 | 9.00 | 7.15 | 0.521854E+09 | 845.64 | 17-NOV-14:09 | 8.00 | 6.02 |
December | 0.118015E+10 | 11689.19 | 18-DEC-13:30 | 8.00 | 5.46 | 0.488945E+09 | 845.64 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.707615E+11 | 0.691932E+10 | ||||||||
Minimum of Months | 0.118015E+10 | 9128.44 | -1.3 | -2.8 | 0.488945E+09 | 845.64 | 8.00 | 5.67 | ||
Maximum of Months | 0.114846E+11 | 37898.27 | 23.67 | 15.91 | 0.681119E+09 | 846.65 | 23.67 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609816E+09 | 3716.70 | 19-JAN-15:50 | 8.17 | 7.46 | 0.318149E+09 | 544.93 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.101941E+10 | 6422.60 | 27-FEB-16:30 | 8.00 | 6.72 | 0.300110E+09 | 544.92 | 13-FEB-14:00 | 8.00 | 6.72 |
March | 0.135690E+10 | 7357.25 | 23-MAR-16:40 | 10.00 | 6.65 | 0.368104E+09 | 544.94 | 10-MAR-14:20 | 10.00 | 6.65 |
April | 0.437313E+10 | 26562.00 | 30-APR-16:41 | 24.00 | 12.67 | 0.369977E+09 | 544.98 | 14-APR-13:00 | 24.00 | 12.67 |
May | 0.523215E+10 | 29531.64 | 21-MAY-16:51 | 20.00 | 12.79 | 0.408179E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.695109E+10 | 29498.64 | 25-JUN-16:51 | 21.00 | 14.00 | 0.421188E+09 | 545.18 | 21-JUN-13:20 | 21.00 | 14.00 |
July | 0.761126E+10 | 27376.52 | 09-JUL-17:01 | 21.00 | 15.03 | 0.393383E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.701037E+10 | 29075.23 | 13-AUG-16:41 | 19.33 | 14.91 | 0.440742E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.455251E+10 | 27053.10 | 10-SEP-16:21 | 20.00 | 16.24 | 0.379144E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.188078E+10 | 9857.98 | 03-OCT-15:40 | 14.00 | 8.96 | 0.351005E+09 | 544.94 | 02-OCT-13:20 | 14.00 | 8.96 |
November | 0.847691E+09 | 4020.84 | 10-NOV-15:30 | 11.50 | 8.42 | 0.320985E+09 | 544.92 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.364478E+09 | 1290.28 | 21-DEC-14:50 | 8.00 | 6.98 | 0.296588E+09 | 532.65 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.418096E+11 | 0.436755E+10 | ||||||||
Minimum of Months | 0.364478E+09 | 1290.28 | 8.00 | 6.65 | 0.296588E+09 | 532.65 | 8.00 | 6.65 | ||
Maximum of Months | 0.761126E+10 | 29531.64 | 24.00 | 16.24 | 0.440742E+09 | 545.18 | 24.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122694E+10 | 6904.53 | 02-JAN-06:15 | 1.33 | 0.92 | 0.00 | 0.00 | 01-JAN-00:10 | 1.33 | 0.92 |
February | 0.123569E+10 | 2917.45 | 21-FEB-06:15 | 4.60 | 4.37 | 0.00 | 0.00 | 01-FEB-00:10 | 4.60 | 4.37 |
March | 0.227616E+10 | 3824.30 | 20-MAR-05:15 | 5.00 | 4.51 | 0.00 | 0.00 | 01-MAR-00:10 | 5.00 | 4.51 |
April | 0.512961E+10 | 7072.12 | 24-APR-05:15 | 7.00 | 5.00 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 5.00 |
May | 0.443711E+10 | 8552.30 | 01-MAY-05:15 | 4.67 | 3.91 | 0.00 | 0.00 | 01-MAY-00:10 | 4.67 | 3.91 |
June | 0.610693E+10 | 9520.52 | 26-JUN-05:15 | 14.67 | 12.18 | 0.00 | 0.00 | 01-JUN-00:10 | 14.67 | 12.18 |
July | 0.707221E+10 | 9478.79 | 24-JUL-05:15 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.784832E+10 | 8329.13 | 07-AUG-05:15 | 10.33 | 9.22 | 0.00 | 0.00 | 01-AUG-00:10 | 10.33 | 9.22 |
September | 0.508400E+10 | 7598.44 | 05-SEP-05:15 | 6.67 | 5.99 | 0.00 | 0.00 | 01-SEP-00:10 | 6.67 | 5.99 |
October | 0.317810E+10 | 7322.63 | 10-OCT-05:10 | 11.00 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11.00 | 11.00 |
November | 0.205307E+10 | 5174.75 | 13-NOV-06:15 | 4.33 | 3.86 | 0.00 | 0.00 | 01-NOV-00:10 | 4.33 | 3.86 |
December | 0.126052E+10 | 2899.59 | 26-DEC-06:10 | 1.92 | 0.28 | 0.00 | 0.00 | 01-DEC-00:10 | 1.92 | 0.28 |
Annual Sum or Average | 0.469087E+11 | 0.00 | ||||||||
Minimum of Months | 0.122694E+10 | 2899.59 | 1.33 | 0.28 | 0.00 | 0.00 | 1.33 | 0.28 | ||
Maximum of Months | 0.784832E+10 | 9520.52 | 14.67 | 13.00 | 0.00 | 0.00 | 14.67 | 13.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341846E+09 | 6976.41 | 09-JAN-05:01 | -2.1 | -2.8 | 0.00 | 0.00 | 01-JAN-00:10 | -2.1 | -2.8 |
February | 0.410299E+09 | 6732.93 | 17-FEB-06:01 | -3.1 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -3.1 | -3.1 |
March | 0.615095E+09 | 3920.90 | 06-MAR-06:02 | 4.00 | 3.61 | 0.00 | 0.00 | 01-MAR-00:10 | 4.00 | 3.61 |
April | 0.215900E+10 | 4379.17 | 28-APR-15:20 | 20.07 | 13.24 | 0.00 | 0.00 | 01-APR-00:10 | 20.07 | 13.24 |
May | 0.249333E+10 | 4209.76 | 23-MAY-15:40 | 18.00 | 14.38 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 14.38 |
June | 0.374359E+10 | 5287.33 | 26-JUN-15:30 | 22.50 | 17.36 | 0.00 | 0.00 | 01-JUN-00:10 | 22.50 | 17.36 |
July | 0.422717E+10 | 5861.46 | 24-JUL-14:20 | 19.00 | 15.90 | 0.00 | 0.00 | 01-JUL-00:10 | 19.00 | 15.90 |
August | 0.454186E+10 | 5047.26 | 18-AUG-14:20 | 19.67 | 16.09 | 0.00 | 0.00 | 01-AUG-00:10 | 19.67 | 16.09 |
September | 0.321056E+10 | 4861.19 | 12-SEP-15:20 | 21.67 | 15.62 | 0.00 | 0.00 | 01-SEP-00:10 | 21.67 | 15.62 |
October | 0.122666E+10 | 3233.98 | 04-OCT-05:10 | 3.00 | 3.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3.00 | 3.00 |
November | 0.471431E+09 | 5853.75 | 29-NOV-06:02 | -1.0 | -1.8 | 0.00 | 0.00 | 01-NOV-00:10 | -1.0 | -1.8 |
December | 0.229588E+09 | 7327.77 | 30-DEC-05:01 | -1.8 | -3.4 | 0.00 | 0.00 | 01-DEC-00:10 | -1.8 | -3.4 |
Annual Sum or Average | 0.236704E+11 | 0.00 | ||||||||
Minimum of Months | 0.229588E+09 | 3233.98 | -3.1 | -3.4 | 0.00 | 0.00 | -3.1 | -3.4 | ||
Maximum of Months | 0.454186E+10 | 7327.77 | 22.50 | 17.36 | 0.00 | 0.00 | 22.50 | 17.36 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4096200.78 | 802.12 | 15-JAN-14:15 | 8.67 | 6.71 | 0.00 | 0.00 | 01-JAN-00:10 | 8.67 | 6.71 |
February | 6996744.92 | 932.63 | 19-FEB-14:48 | 6.00 | 4.14 | 0.00 | 0.00 | 01-FEB-00:10 | 6.00 | 4.14 |
March | 0.107587E+09 | 2336.60 | 25-MAR-12:30 | 13.00 | 10.05 | 0.00 | 0.00 | 01-MAR-00:10 | 13.00 | 10.05 |
April | 0.355630E+10 | 13806.57 | 28-APR-14:50 | 20.08 | 13.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.08 | 13.54 |
May | 0.424460E+10 | 14725.38 | 22-MAY-14:30 | 23.50 | 15.92 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 15.92 |
June | 0.651818E+10 | 16724.70 | 21-JUN-13:05 | 21.92 | 15.66 | 0.00 | 0.00 | 01-JUN-00:10 | 21.92 | 15.66 |
July | 0.754331E+10 | 16118.99 | 21-JUL-14:40 | 27.00 | 15.95 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.95 |
August | 0.717321E+10 | 14530.89 | 14-AUG-14:50 | 24.83 | 16.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.83 | 16.12 |
September | 0.419218E+10 | 12147.50 | 12-SEP-15:10 | 21.83 | 15.52 | 0.00 | 0.00 | 01-SEP-00:10 | 21.83 | 15.52 |
October | 0.690601E+09 | 5604.62 | 03-OCT-14:50 | 14.00 | 9.04 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.04 |
November | 8229506.73 | 1268.25 | 11-NOV-13:35 | 9.00 | 7.15 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.340453E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.754331E+10 | 16724.70 | 27.00 | 16.12 | 0.00 | 0.00 | 27.00 | 16.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338186E+10 | 1999.47 | 19-JAN-16:20 | 7.33 | 6.98 | 95230137.22 | 126.83 | 18-JAN-14:00 | 7.33 | 6.98 |
February | 0.791523E+10 | 4205.20 | 27-FEB-17:00 | 8.00 | 6.97 | 86396546.05 | 126.83 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.140899E+11 | 7034.48 | 31-MAR-24:00 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.30 | 1.71 |
April | 0.189443E+11 | 8371.54 | 30-APR-17:51 | 24.00 | 13.13 | 91605075.53 | 126.82 | 28-APR-09:09 | 24.00 | 13.13 |
May | 0.431336E+10 | 3372.32 | 31-MAY-24:00 | 9.40 | 7.45 | 99234941.15 | 126.84 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.930188E+10 | 5209.59 | 30-JUN-24:00 | 11.00 | 9.86 | 98963118.90 | 126.84 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.147652E+11 | 7262.21 | 31-JUL-24:00 | 11.40 | 9.79 | 91885275.23 | 126.83 | 25-JUL-09:09 | 11.40 | 9.79 |
August | 0.197482E+11 | 8293.66 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.420408E+10 | 3263.99 | 30-SEP-24:00 | 7.60 | 5.71 | 91609842.75 | 126.84 | 12-SEP-13:00 | 7.60 | 5.71 |
October | 0.914410E+10 | 5112.29 | 31-OCT-24:00 | 6.60 | 4.32 | 95232033.01 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.136102E+11 | 5771.86 | 03-NOV-16:00 | 8.00 | 4.84 | 94301176.83 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.189392E+11 | 7486.45 | 26-DEC-15:20 | 5.00 | 2.88 | 91880817.79 | 126.82 | 26-DEC-10:09 | 5.00 | 2.88 |
Annual Sum or Average | 0.138357E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.338186E+10 | 1999.47 | 4.30 | 1.71 | 86396546.05 | 126.82 | 4.30 | 1.71 | ||
Maximum of Months | 0.197482E+11 | 8371.54 | 24.00 | 13.92 | 0.103238E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143844E+10 | 1773.56 | 19-JAN-16:30 | 7.00 | 6.74 | 95229895.98 | 126.82 | 18-JAN-14:00 | 7.00 | 6.74 |
February | 0.609513E+10 | 3835.29 | 27-FEB-17:00 | 8.00 | 6.97 | 86396560.58 | 126.82 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.120701E+11 | 6376.95 | 31-MAR-23:30 | 4.50 | 1.74 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.50 | 1.74 |
April | 0.174952E+11 | 8008.14 | 30-APR-18:03 | 24.00 | 13.14 | 91605089.47 | 126.82 | 28-APR-09:09 | 24.00 | 13.14 |
May | 0.356738E+10 | 3105.63 | 31-MAY-23:50 | 9.55 | 7.84 | 99234887.83 | 126.84 | 23-MAY-13:00 | 9.55 | 7.84 |
June | 0.851038E+10 | 4782.95 | 30-JUN-23:40 | 11.00 | 10.07 | 98962822.05 | 126.84 | 27-JUN-09:09 | 11.00 | 10.07 |
July | 0.137561E+11 | 6840.14 | 31-JUL-24:00 | 11.40 | 9.79 | 91885313.01 | 126.84 | 24-JUL-13:00 | 11.40 | 9.79 |
August | 0.185555E+11 | 7743.09 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.347924E+10 | 2923.62 | 30-SEP-23:30 | 7.65 | 5.76 | 91609619.83 | 126.84 | 12-SEP-13:00 | 7.65 | 5.76 |
October | 0.760690E+10 | 4450.68 | 31-OCT-23:50 | 6.62 | 4.28 | 95231928.66 | 126.83 | 10-OCT-13:00 | 6.62 | 4.28 |
November | 0.113545E+11 | 5382.10 | 03-NOV-16:00 | 8.00 | 4.84 | 94301116.95 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.157527E+11 | 6893.74 | 21-DEC-15:20 | 7.67 | 6.81 | 91880840.85 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.119682E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.143844E+10 | 1773.56 | 4.50 | 1.74 | 86396560.58 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.185555E+11 | 8008.14 | 24.00 | 13.92 | 0.103239E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366286E+09 | 1658.84 | 19-JAN-16:30 | 7.00 | 6.74 | 93453077.34 | 127.04 | 05-JAN-10:30 | 7.00 | 6.74 |
February | 0.424269E+10 | 3637.95 | 24-FEB-17:00 | 6.00 | 4.60 | 86396561.76 | 126.82 | 08-FEB-14:00 | 6.00 | 4.60 |
March | 0.103926E+11 | 5931.60 | 31-MAR-23:20 | 4.57 | 1.75 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.57 | 1.75 |
April | 0.167005E+11 | 8126.50 | 30-APR-17:51 | 24.00 | 13.13 | 91605094.28 | 126.82 | 28-APR-09:09 | 24.00 | 13.13 |
May | 0.288102E+10 | 2961.29 | 31-MAY-23:20 | 10.00 | 9.01 | 99234908.78 | 126.84 | 23-MAY-13:00 | 10.00 | 9.01 |
June | 0.818823E+10 | 4574.88 | 30-JUN-23:20 | 11.00 | 10.27 | 98962880.88 | 126.84 | 27-JUN-09:09 | 11.00 | 10.27 |
July | 0.134846E+11 | 6687.46 | 31-JUL-23:20 | 11.33 | 10.03 | 91885412.92 | 126.84 | 24-JUL-13:09 | 11.33 | 10.03 |
August | 0.182775E+11 | 7864.38 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.283898E+10 | 2414.99 | 30-SEP-23:20 | 7.67 | 5.77 | 91609712.36 | 126.84 | 12-SEP-13:00 | 7.67 | 5.77 |
October | 0.608596E+10 | 3889.78 | 31-OCT-23:20 | 6.67 | 4.17 | 95231855.73 | 126.83 | 13-OCT-13:00 | 6.67 | 4.17 |
November | 0.944752E+10 | 5277.81 | 10-NOV-16:10 | 10.33 | 8.12 | 94301129.71 | 126.83 | 08-NOV-14:00 | 10.33 | 8.12 |
December | 0.135995E+11 | 6637.34 | 21-DEC-15:30 | 7.50 | 6.73 | 91880848.35 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.106505E+12 | 0.114104E+10 | ||||||||
Minimum of Months | 0.366286E+09 | 1658.84 | 4.57 | 1.75 | 86396561.76 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.182775E+11 | 8126.50 | 24.00 | 13.92 | 0.103239E+09 | 127.04 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237316E+12 | 91783.47 | 02-JAN-17:00 | 3.00 | 1.77 | 0.206144E+10 | 2745.91 | 25-JAN-14:39 | 11.00 | 9.22 |
February | 0.435088E+12 | 182736.81 | 09-FEB-17:00 | 6.00 | 4.60 | 0.187025E+10 | 2746.00 | 08-FEB-14:30 | 6.00 | 4.60 |
March | 0.728145E+12 | 358533.51 | 31-MAR-24:00 | 4.30 | 1.71 | 0.223479E+10 | 2745.45 | 31-MAR-09:50 | 4.30 | 1.71 |
April | 0.943407E+12 | 367389.12 | 28-APR-16:00 | 20.00 | 12.32 | 0.198310E+10 | 2749.21 | 28-APR-09:09 | 20.00 | 12.32 |
May | 0.240365E+12 | 175824.81 | 31-MAY-24:00 | 9.40 | 7.45 | 0.214808E+10 | 2745.89 | 04-MAY-09:39 | 9.40 | 7.45 |
June | 0.469793E+12 | 267114.00 | 30-JUN-24:00 | 11.00 | 9.86 | 0.214223E+10 | 2748.86 | 26-JUN-13:00 | 11.00 | 9.86 |
July | 0.731700E+12 | 359962.27 | 31-JUL-24:00 | 11.40 | 9.79 | 0.198966E+10 | 2750.01 | 24-JUL-13:00 | 11.40 | 9.79 |
August | 0.977023E+12 | 367923.07 | 14-AUG-16:00 | 26.00 | 15.86 | 0.223739E+10 | 2751.81 | 08-AUG-13:09 | 26.00 | 15.86 |
September | 0.234080E+12 | 175566.81 | 30-SEP-24:00 | 7.60 | 5.71 | 0.198293E+10 | 2745.64 | 05-SEP-09:50 | 7.60 | 5.71 |
October | 0.484930E+12 | 267358.73 | 31-OCT-24:00 | 6.60 | 4.32 | 0.206141E+10 | 2746.10 | 20-OCT-13:30 | 6.60 | 4.32 |
November | 0.706129E+12 | 275316.13 | 13-NOV-17:00 | 8.00 | 7.45 | 0.204132E+10 | 2746.52 | 06-NOV-10:50 | 8.00 | 7.45 |
December | 0.974158E+12 | 366923.50 | 26-DEC-17:00 | 1.00 | 0.17 | 0.198900E+10 | 2745.42 | 13-DEC-10:00 | 1.00 | 0.17 |
Annual Sum or Average | 0.716213E+13 | 0.247416E+11 | ||||||||
Minimum of Months | 0.234080E+12 | 91783.47 | 1.00 | 0.17 | 0.187025E+10 | 2745.42 | 1.00 | 0.17 | ||
Maximum of Months | 0.977023E+12 | 367923.07 | 26.00 | 15.86 | 0.223739E+10 | 2751.81 | 26.00 | 15.86 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172142E+10 | 67123.71 | 02-JAN-04:01 | 1.17 |
February | 0.700531E+09 | 60902.41 | 21-FEB-05:11 | 5.37 |
March | 0.271157E+09 | 60561.82 | 06-MAR-05:11 | 3.87 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 52859679.22 | 56409.45 | 30-OCT-05:03 | 7.00 |
November | 0.629938E+09 | 61521.64 | 20-NOV-05:11 | 0.33 |
December | 0.158469E+10 | 65735.87 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.496060E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.33 | |
Maximum of Months | 0.172142E+10 | 67123.71 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 281635.34 | 1778.86 | 11-JAN-06:01 | -2.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 281635.34 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 281635.34 | 1778.86 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2692875.91 | 2974.04 | 10-JAN-06:01 | -4.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 37904.47 | 442.22 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 2730780.38 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 2692875.91 | 2974.04 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18330638.99 | 7356.64 | 10-JAN-06:01 | -4.0 |
February | 66928.10 | 723.00 | 17-FEB-06:01 | -3.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 2249629.48 | 6916.04 | 18-DEC-06:01 | 0.17 |
Annual Sum or Average | 20647196.56 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 18330638.99 | 7356.64 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604649E+09 | 9232.09 | 09-JAN-05:01 | -2.1 |
February | 0.278671E+09 | 8934.82 | 13-FEB-05:01 | -1.0 |
March | 82772299.06 | 8511.87 | 06-MAR-06:02 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 8896773.60 | 7735.41 | 23-OCT-05:03 | 3.17 |
November | 0.220432E+09 | 8914.59 | 27-NOV-05:11 | 4.00 |
December | 0.852643E+09 | 9409.10 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.204806E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.852643E+09 | 9409.10 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344642E+09 | 11939.04 | 09-JAN-05:01 | -2.1 |
February | 0.150686E+09 | 11045.31 | 17-FEB-05:01 | -2.1 |
March | 47184321.83 | 10447.64 | 06-MAR-06:02 | 4.00 |
April | 20550.34 | 171.25 | 01-APR-05:04 | 2.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 4603226.81 | 3649.83 | 23-OCT-05:03 | 3.17 |
November | 0.131261E+09 | 11311.61 | 27-NOV-05:11 | 4.00 |
December | 0.530497E+09 | 12181.90 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.120889E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.530497E+09 | 12181.90 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252898E+09 | 16599.49 | 09-JAN-05:01 | -2.1 |
February | 93817511.60 | 15452.35 | 17-FEB-06:01 | -3.1 |
March | 37438485.56 | 15341.48 | 06-MAR-06:02 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 894083.10 | 2641.70 | 28-OCT-05:03 | 7.00 |
November | 98219904.59 | 16367.64 | 27-NOV-05:11 | 4.00 |
December | 0.515180E+09 | 16955.31 | 28-DEC-05:11 | 1.67 |
Annual Sum or Average | 0.998448E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 0.515180E+09 | 16955.31 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190268E+09 | 10458.20 | 09-JAN-05:01 | -2.1 |
February | 60795598.42 | 9557.61 | 17-FEB-06:01 | -3.1 |
March | 11184947.53 | 7512.16 | 06-MAR-06:02 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 63984273.84 | 10123.74 | 27-NOV-05:11 | 4.00 |
December | 0.281783E+09 | 10798.93 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.608016E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 0.281783E+09 | 10798.93 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.327499E+10 | 11554.01 | 02-JAN-04:01 | 1.17 |
February | 0.213210E+10 | 11610.97 | 13-FEB-04:01 | -1.8 |
March | 0.128135E+10 | 11349.19 | 06-MAR-05:11 | 3.87 |
April | 0.171228E+09 | 9557.23 | 11-APR-05:02 | 5.83 |
May | 32033916.21 | 9486.81 | 06-MAY-05:02 | 2.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 10931621.96 | 9035.45 | 18-SEP-05:03 | 12.00 |
October | 0.624702E+09 | 10657.85 | 23-OCT-04:11 | 3.00 |
November | 0.182924E+10 | 11775.94 | 27-NOV-05:11 | 4.00 |
December | 0.377302E+10 | 11802.06 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.131296E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.377302E+10 | 11802.06 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182879E+10 | 16184.12 | 02-JAN-04:01 | 1.17 |
February | 0.114285E+10 | 16051.23 | 27-FEB-05:11 | 6.00 |
March | 0.742526E+09 | 16050.97 | 06-MAR-05:11 | 3.87 |
April | 51691090.07 | 12824.46 | 11-APR-05:02 | 5.83 |
May | 10584379.13 | 12431.08 | 05-MAY-05:02 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 666514.50 | 1086.09 | 21-SEP-05:03 | 5.83 |
October | 0.344112E+09 | 14584.27 | 23-OCT-04:11 | 3.00 |
November | 0.104628E+10 | 16646.71 | 27-NOV-05:11 | 4.00 |
December | 0.229043E+10 | 16620.36 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.745794E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.229043E+10 | 16646.71 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190619E+10 | 24110.74 | 02-JAN-04:01 | 1.17 |
February | 0.121178E+10 | 23803.35 | 27-FEB-05:11 | 6.00 |
March | 0.948253E+09 | 23786.39 | 06-MAR-05:11 | 3.87 |
April | 74194665.69 | 19167.05 | 11-APR-05:02 | 5.83 |
May | 40036007.45 | 19077.05 | 05-MAY-05:02 | 6.00 |
June | 436808.17 | 2656.11 | 08-JUN-05:03 | 6.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 2525.25 | 16.84 | 20-SEP-05:08 | 6.00 |
October | 0.363011E+09 | 20764.86 | 23-OCT-04:11 | 3.00 |
November | 0.114174E+10 | 24482.97 | 27-NOV-05:11 | 4.00 |
December | 0.271082E+10 | 24640.24 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.839647E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.271082E+10 | 24640.24 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127659E+10 | 16329.89 | 02-JAN-04:01 | 1.17 |
February | 0.680562E+09 | 15287.53 | 13-FEB-04:01 | -1.8 |
March | 0.409890E+09 | 14967.13 | 06-MAR-05:11 | 3.87 |
April | 16433763.94 | 9571.80 | 01-APR-05:02 | 2.17 |
May | 8834087.57 | 11476.66 | 05-MAY-05:02 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.165120E+09 | 13522.10 | 23-OCT-04:11 | 3.00 |
November | 0.648253E+09 | 15754.46 | 27-NOV-05:11 | 4.00 |
December | 0.151134E+10 | 16520.01 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.471702E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.151134E+10 | 16520.01 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144098E+09 | 8817.06 | 15-JAN-13:43 | 9.17 |
February | 76493958.55 | 10907.20 | 19-FEB-15:32 | 5.33 |
March | 63025036.10 | 9296.05 | 06-MAR-05:11 | 3.87 |
April | 0.122723E+09 | 12745.48 | 30-APR-14:21 | 23.50 |
May | 0.100117E+09 | 10951.69 | 21-MAY-14:52 | 19.00 |
June | 88498904.29 | 11858.41 | 25-JUN-15:41 | 24.83 |
July | 0.133848E+09 | 9618.95 | 09-JUL-16:51 | 21.00 |
August | 0.133561E+09 | 10715.42 | 20-AUG-14:42 | 23.00 |
September | 97299076.34 | 10570.46 | 10-SEP-15:22 | 21.50 |
October | 77862946.31 | 10130.86 | 01-OCT-15:12 | 12.67 |
November | 83312695.24 | 9899.62 | 27-NOV-05:11 | 4.00 |
December | 74397997.43 | 11116.30 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.119524E+10 | |||
Minimum of Months | 63025036.10 | 8817.06 | 1.97 | |
Maximum of Months | 0.144098E+09 | 12745.48 | 24.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122985E+10 | 11850.49 | 15-JAN-12:52 | 10.00 |
February | 0.966014E+09 | 10758.61 | 19-FEB-13:43 | 6.00 |
March | 0.653816E+09 | 5834.14 | 09-MAR-06:02 | 7.15 |
April | 54279804.62 | 14222.27 | 30-APR-14:31 | 23.67 |
May | 68898453.28 | 8375.62 | 21-MAY-15:42 | 18.17 |
June | 59160497.02 | 8171.28 | 11-JUN-13:53 | 18.00 |
July | 89736939.98 | 11417.64 | 30-JUL-15:21 | 16.50 |
August | 71047879.68 | 11664.21 | 13-AUG-15:31 | 21.00 |
September | 92924424.64 | 12479.89 | 10-SEP-15:11 | 21.67 |
October | 0.209515E+09 | 7839.75 | 01-OCT-14:52 | 13.00 |
November | 0.741267E+09 | 9231.47 | 11-NOV-13:02 | 9.00 |
December | 0.136646E+10 | 4411.48 | 18-DEC-14:10 | 8.00 |
Annual Sum or Average | 0.560297E+10 | |||
Minimum of Months | 54279804.62 | 4411.48 | 6.00 | |
Maximum of Months | 0.136646E+10 | 14222.27 | 23.67 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540082E+10 | 20530.60 | 02-JAN-05:12 | 1.00 |
February | 0.380623E+10 | 16344.42 | 13-FEB-06:13 | -1.0 |
March | 0.317072E+10 | 13468.18 | 06-MAR-06:02 | 4.00 |
April | 0.118228E+10 | 11283.58 | 21-APR-05:02 | 8.00 |
May | 0.886606E+09 | 13290.97 | 24-MAY-05:02 | 8.42 |
June | 0.382915E+09 | 12714.80 | 01-JUN-05:02 | 6.50 |
July | 0.306762E+09 | 13425.70 | 06-JUL-05:03 | 9.50 |
August | 0.466103E+09 | 12297.47 | 30-AUG-05:03 | 9.83 |
September | 0.831297E+09 | 12069.25 | 15-SEP-05:02 | 10.83 |
October | 0.229388E+10 | 9866.72 | 23-OCT-05:03 | 3.17 |
November | 0.383624E+10 | 17059.11 | 27-NOV-05:22 | 4.00 |
December | 0.610492E+10 | 19887.92 | 26-DEC-05:22 | 1.95 |
Annual Sum or Average | 0.286688E+11 | |||
Minimum of Months | 0.306762E+09 | 9866.72 | -1.0 | |
Maximum of Months | 0.610492E+10 | 20530.60 | 10.83 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10889671.87 | 397.56 | 10-JAN-04:33 | -3.8 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 10889671.87 | |||
Minimum of Months | 0.00 | 0.00 | -3.8 | |
Maximum of Months | 10889671.87 | 397.56 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.646673E+09 | 587.87 | 08-JAN-17:40 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 648804.89 | 391.70 | 17-SEP-06:45 | 9.83 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.647322E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.646673E+09 | 587.87 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107215E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.871206E+09 | 1560.90 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.954387E+09 | 1387.41 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.806459E+09 | 1166.91 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.842018E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.827951E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.778294E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.888804E+09 | 915.09 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.827355E+09 | 931.95 | 08-SEP-07:30 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.948895E+09 | 1653.31 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.105299E+10 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.111317E+10 | 1662.56 | 01-DEC-15:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.109837E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.778294E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.111317E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.671310E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.551582E+09 | 1000.39 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.611930E+09 | 860.86 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.519486E+09 | 697.61 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.544591E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.535800E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.503696E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.572982E+09 | 573.67 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.530467E+09 | 587.26 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.602369E+09 | 1065.08 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.664485E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.693524E+09 | 1071.42 | 01-DEC-15:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.700222E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.503696E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.693524E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102392E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.848033E+09 | 1556.00 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.945934E+09 | 1374.55 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.807654E+09 | 1158.73 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.845042E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.830980E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.781720E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.891251E+09 | 913.25 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.825333E+09 | 926.67 | 08-SEP-07:30 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.928921E+09 | 1652.96 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.101414E+10 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.106065E+10 | 1662.60 | 01-DEC-15:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.108036E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.781720E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.106065E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.676847E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.554086E+09 | 1006.46 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.613731E+09 | 907.47 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.519792E+09 | 775.18 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.543140E+09 | 560.16 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.533627E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.502089E+09 | 553.30 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.573795E+09 | 595.53 | 22-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.533270E+09 | 776.93 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.606450E+09 | 1065.46 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.665317E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.703619E+09 | 1071.42 | 01-DEC-15:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.702576E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.502089E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.703619E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106880E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.868460E+09 | 1559.83 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.952525E+09 | 1384.38 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.806104E+09 | 1161.38 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.841787E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.827702E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.778144E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.888080E+09 | 908.96 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.826462E+09 | 926.78 | 08-SEP-07:30 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.946297E+09 | 1653.22 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.104960E+10 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.110970E+10 | 1662.56 | 01-DEC-15:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.109637E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.778144E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.110970E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669982E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.550649E+09 | 998.64 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.611002E+09 | 856.23 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.519369E+09 | 689.77 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.544304E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.535530E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.503476E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.572611E+09 | 569.42 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.530151E+09 | 583.69 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.601214E+09 | 1064.92 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.662558E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.691451E+09 | 1071.42 | 01-DEC-15:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.699230E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.503476E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.691451E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102286E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.846472E+09 | 1554.92 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.944891E+09 | 1371.46 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.807332E+09 | 1153.13 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.844672E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.830657E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.781313E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.890695E+09 | 907.03 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.824739E+09 | 921.25 | 08-SEP-07:30 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.928007E+09 | 1652.86 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.101237E+10 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.105922E+10 | 1662.60 | 01-DEC-15:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.107932E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.781313E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.105922E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675579E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.552840E+09 | 1004.79 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612589E+09 | 903.20 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.519542E+09 | 767.45 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.542835E+09 | 554.67 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.533413E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.501928E+09 | 547.42 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.573427E+09 | 592.03 | 22-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.532984E+09 | 768.66 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.604770E+09 | 1065.30 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.663620E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.701581E+09 | 1071.42 | 01-DEC-15:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.701511E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.501928E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.701581E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106867E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.868348E+09 | 1559.61 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.952464E+09 | 1383.82 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.806092E+09 | 1160.35 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.841771E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.827686E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.778126E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.888066E+09 | 908.71 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.826444E+09 | 926.57 | 08-SEP-07:30 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.946126E+09 | 1653.20 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.104934E+10 | 1662.56 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.110955E+10 | 1662.56 | 01-DEC-15:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.109627E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.778126E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.110955E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669901E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.550617E+09 | 998.50 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.610962E+09 | 855.84 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.519360E+09 | 689.04 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.544297E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.535502E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.503463E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.572597E+09 | 569.22 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.530144E+09 | 583.52 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.601173E+09 | 1064.91 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.662418E+09 | 1071.42 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.691354E+09 | 1071.42 | 01-DEC-15:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.699179E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.503463E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.691354E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102282E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.846436E+09 | 1554.70 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.944845E+09 | 1370.88 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.807288E+09 | 1152.09 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.844660E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.830627E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.781304E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.890678E+09 | 906.78 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.824725E+09 | 921.03 | 08-SEP-07:30 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.927930E+09 | 1652.84 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.101226E+10 | 1662.60 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.105905E+10 | 1662.60 | 01-DEC-15:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.107926E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.781304E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.105905E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675487E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.552804E+09 | 1004.65 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612553E+09 | 902.86 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.519534E+09 | 766.83 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.542827E+09 | 554.45 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.533401E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.501923E+09 | 547.19 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.573405E+09 | 591.89 | 22-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.532975E+09 | 768.16 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.604713E+09 | 1065.29 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.663432E+09 | 1071.42 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.701514E+09 | 1071.42 | 01-DEC-15:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.701457E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.501923E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.701514E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.107215E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101911E+09 |
February | 0.136985E+10 | 0.871206E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142879E+09 |
March | 0.163685E+10 | 0.954387E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84851574.75 |
April | 0.145243E+10 | 0.806459E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105773E+09 |
May | 0.157338E+10 | 0.842018E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 0.252373E+09 |
June | 0.156900E+10 | 0.827951E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112359.81 | 0.194403E+09 |
July | 0.145680E+10 | 0.778294E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 516513.72 | 0.188001E+09 |
August | 0.163685E+10 | 0.888804E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72325.53 | 0.135064E+09 |
September | 0.145243E+10 | 0.827355E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141916E+09 |
October | 0.150991E+10 | 0.948895E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154454E+09 |
November | 0.149516E+10 | 0.105299E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191144E+09 |
December | 0.145680E+10 | 0.111317E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261777E+09 |
Annual Sum or Average | 0.181194E+11 | 0.109837E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 701200.60 | 0.195455E+10 |
Minimum of Months | 0.136985E+10 | 0.778294E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84851574.75 |
Maximum of Months | 0.163685E+10 | 0.111317E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 516513.72 | 0.261777E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.671310E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68259541.82 |
February | 0.882782E+09 | 0.551582E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94833013.13 |
March | 0.105485E+10 | 0.611930E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55971765.06 |
April | 0.936002E+09 | 0.519486E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70570649.35 |
May | 0.101394E+10 | 0.544591E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.170238E+09 |
June | 0.101113E+10 | 0.535800E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74915.60 | 0.129572E+09 |
July | 0.938820E+09 | 0.503696E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 353129.07 | 0.125651E+09 |
August | 0.105485E+10 | 0.572982E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48171.99 | 89935167.56 |
September | 0.936002E+09 | 0.530467E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97469648.19 |
October | 0.973041E+09 | 0.602369E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102544E+09 |
November | 0.963541E+09 | 0.664485E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125329E+09 |
December | 0.938820E+09 | 0.693524E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169685E+09 |
Annual Sum or Average | 0.116768E+11 | 0.700222E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 476217.69 | 0.130006E+10 |
Minimum of Months | 0.882782E+09 | 0.503696E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55971765.06 |
Maximum of Months | 0.105485E+10 | 0.693524E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 353129.07 | 0.170238E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.102392E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102085E+09 |
February | 0.136988E+10 | 0.848033E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142930E+09 |
March | 0.163688E+10 | 0.945934E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83371594.43 |
April | 0.145246E+10 | 0.807654E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107529E+09 |
May | 0.157341E+10 | 0.845042E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.254247E+09 |
June | 0.156904E+10 | 0.830980E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112371.87 | 0.195234E+09 |
July | 0.145684E+10 | 0.781720E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497567.53 | 0.190358E+09 |
August | 0.163688E+10 | 0.891251E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71824.34 | 0.139139E+09 |
September | 0.145246E+10 | 0.825333E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148016E+09 |
October | 0.150994E+10 | 0.928921E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155864E+09 |
November | 0.149520E+10 | 0.101414E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189003E+09 |
December | 0.145684E+10 | 0.106065E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253613E+09 |
Annual Sum or Average | 0.181198E+11 | 0.108036E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 681765.26 | 0.196139E+10 |
Minimum of Months | 0.136988E+10 | 0.781720E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83371594.43 |
Maximum of Months | 0.163688E+10 | 0.106065E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497567.53 | 0.254247E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.676847E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71569190.31 |
February | 0.882782E+09 | 0.554086E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103064E+09 |
March | 0.105485E+10 | 0.613731E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60906788.75 |
April | 0.936002E+09 | 0.519792E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78421402.72 |
May | 0.101394E+10 | 0.543140E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 0.180745E+09 |
June | 0.101113E+10 | 0.533627E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74889.79 | 0.142661E+09 |
July | 0.938820E+09 | 0.502089E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295624.89 | 0.142286E+09 |
August | 0.105485E+10 | 0.573795E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47654.37 | 0.104413E+09 |
September | 0.936002E+09 | 0.533270E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103477E+09 |
October | 0.973041E+09 | 0.606450E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112542E+09 |
November | 0.963541E+09 | 0.665317E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140242E+09 |
December | 0.938820E+09 | 0.703619E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193999E+09 |
Annual Sum or Average | 0.116768E+11 | 0.702576E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 418170.10 | 0.143433E+10 |
Minimum of Months | 0.882782E+09 | 0.502089E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60906788.75 |
Maximum of Months | 0.105485E+10 | 0.703619E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295624.89 | 0.193999E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.106880E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208729E+09 |
February | 0.136985E+10 | 0.868460E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296309E+09 |
March | 0.163685E+10 | 0.952525E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178586E+09 |
April | 0.145243E+10 | 0.806104E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229387E+09 |
May | 0.157338E+10 | 0.841787E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559258E+09 |
June | 0.156900E+10 | 0.827702E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245700.57 | 0.433843E+09 |
July | 0.145680E+10 | 0.778144E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1205941.17 | 0.414724E+09 |
August | 0.163685E+10 | 0.888080E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160640.57 | 0.296348E+09 |
September | 0.145243E+10 | 0.826462E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307950E+09 |
October | 0.150991E+10 | 0.946297E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322799E+09 |
November | 0.149516E+10 | 0.104960E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386508E+09 |
December | 0.145680E+10 | 0.110970E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519766E+09 |
Annual Sum or Average | 0.181194E+11 | 0.109637E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1612282.31 | 0.415421E+10 |
Minimum of Months | 0.136985E+10 | 0.778144E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178586E+09 |
Maximum of Months | 0.163685E+10 | 0.110970E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1205941.17 | 0.559258E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.669982E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142951E+09 |
February | 0.649041E+09 | 0.550649E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203048E+09 |
March | 0.773965E+09 | 0.611002E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122906E+09 |
April | 0.688021E+09 | 0.519369E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161395E+09 |
May | 0.744847E+09 | 0.544304E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388324E+09 |
June | 0.742030E+09 | 0.535530E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157340.00 | 0.298474E+09 |
July | 0.690839E+09 | 0.503476E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 732424.69 | 0.291311E+09 |
August | 0.773965E+09 | 0.572611E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107010.99 | 0.210139E+09 |
September | 0.688021E+09 | 0.530151E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221881E+09 |
October | 0.715730E+09 | 0.601214E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223856E+09 |
November | 0.708685E+09 | 0.662558E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263230E+09 |
December | 0.690839E+09 | 0.691451E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348977E+09 |
Annual Sum or Average | 0.858171E+10 | 0.699230E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 996775.67 | 0.287649E+10 |
Minimum of Months | 0.649041E+09 | 0.503476E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122906E+09 |
Maximum of Months | 0.773965E+09 | 0.691451E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 732424.69 | 0.388324E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.102286E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229272E+09 |
February | 0.136988E+10 | 0.846472E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321719E+09 |
March | 0.163688E+10 | 0.944891E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186846E+09 |
April | 0.145246E+10 | 0.807332E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246155E+09 |
May | 0.157341E+10 | 0.844672E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582837E+09 |
June | 0.156904E+10 | 0.830657E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245791.75 | 0.445402E+09 |
July | 0.145684E+10 | 0.781313E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1125021.60 | 0.434580E+09 |
August | 0.163688E+10 | 0.890695E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160638.53 | 0.319769E+09 |
September | 0.145246E+10 | 0.824739E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340989E+09 |
October | 0.150994E+10 | 0.928007E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352029E+09 |
November | 0.149520E+10 | 0.101237E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415948E+09 |
December | 0.145684E+10 | 0.105922E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545285E+09 |
Annual Sum or Average | 0.181198E+11 | 0.107932E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1531451.88 | 0.442083E+10 |
Minimum of Months | 0.136988E+10 | 0.781313E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186846E+09 |
Maximum of Months | 0.163688E+10 | 0.105922E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1125021.60 | 0.582837E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.675579E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145340E+09 |
February | 0.882782E+09 | 0.552840E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208593E+09 |
March | 0.105485E+10 | 0.612589E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123838E+09 |
April | 0.936002E+09 | 0.519542E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164086E+09 |
May | 0.101394E+10 | 0.542835E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399407E+09 |
June | 0.101113E+10 | 0.533413E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163844.68 | 0.310633E+09 |
July | 0.938820E+09 | 0.501928E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662682.47 | 0.303957E+09 |
August | 0.105485E+10 | 0.573427E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107079.40 | 0.219409E+09 |
September | 0.936002E+09 | 0.532984E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223907E+09 |
October | 0.973041E+09 | 0.604770E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229389E+09 |
November | 0.963541E+09 | 0.663620E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269259E+09 |
December | 0.938820E+09 | 0.701581E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357832E+09 |
Annual Sum or Average | 0.116768E+11 | 0.701511E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 933606.55 | 0.295565E+10 |
Minimum of Months | 0.882782E+09 | 0.501928E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123838E+09 |
Maximum of Months | 0.105485E+10 | 0.701581E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662682.47 | 0.399407E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.106867E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231479E+09 |
February | 0.136985E+10 | 0.868348E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330604E+09 |
March | 0.163685E+10 | 0.952464E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202865E+09 |
April | 0.145243E+10 | 0.806092E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267533E+09 |
May | 0.157338E+10 | 0.841771E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658901E+09 |
June | 0.156900E+10 | 0.827686E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283491.81 | 0.523737E+09 |
July | 0.145680E+10 | 0.778126E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349998.86 | 0.501197E+09 |
August | 0.163685E+10 | 0.888066E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186980.31 | 0.358311E+09 |
September | 0.145243E+10 | 0.826444E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356313E+09 |
October | 0.150991E+10 | 0.946126E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358717E+09 |
November | 0.149516E+10 | 0.104934E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427658E+09 |
December | 0.145680E+10 | 0.110955E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581280E+09 |
Annual Sum or Average | 0.181194E+11 | 0.109627E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1820470.98 | 0.479859E+10 |
Minimum of Months | 0.136985E+10 | 0.778126E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202865E+09 |
Maximum of Months | 0.163685E+10 | 0.110955E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349998.86 | 0.658901E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.669901E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156974E+09 |
February | 0.882782E+09 | 0.550617E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225985E+09 |
March | 0.105485E+10 | 0.610962E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139286E+09 |
April | 0.936002E+09 | 0.519360E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190173E+09 |
May | 0.101394E+10 | 0.544297E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461674E+09 |
June | 0.101113E+10 | 0.535502E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189013.12 | 0.361568E+09 |
July | 0.938820E+09 | 0.503463E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 870194.47 | 0.353990E+09 |
August | 0.105485E+10 | 0.572597E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124652.50 | 0.255280E+09 |
September | 0.936002E+09 | 0.530144E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261222E+09 |
October | 0.973041E+09 | 0.601173E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250435E+09 |
November | 0.963541E+09 | 0.662418E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289937E+09 |
December | 0.938820E+09 | 0.691354E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389526E+09 |
Annual Sum or Average | 0.116768E+11 | 0.699179E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1183860.09 | 0.333605E+10 |
Minimum of Months | 0.882782E+09 | 0.503463E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139286E+09 |
Maximum of Months | 0.105485E+10 | 0.691354E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 870194.47 | 0.461674E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.102282E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253257E+09 |
February | 0.136988E+10 | 0.846436E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362510E+09 |
March | 0.163688E+10 | 0.944845E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214377E+09 |
April | 0.145246E+10 | 0.807288E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292052E+09 |
May | 0.157341E+10 | 0.844660E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693505E+09 |
June | 0.156904E+10 | 0.830627E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283515.85 | 0.539251E+09 |
July | 0.145684E+10 | 0.781304E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1266835.27 | 0.527317E+09 |
August | 0.163688E+10 | 0.890678E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186979.36 | 0.389217E+09 |
September | 0.145246E+10 | 0.824725E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403698E+09 |
October | 0.150994E+10 | 0.927930E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400224E+09 |
November | 0.149520E+10 | 0.101226E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463445E+09 |
December | 0.145684E+10 | 0.105905E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606915E+09 |
Annual Sum or Average | 0.181198E+11 | 0.107926E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1737330.47 | 0.514577E+10 |
Minimum of Months | 0.136988E+10 | 0.781304E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214377E+09 |
Maximum of Months | 0.163688E+10 | 0.105905E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1266835.27 | 0.693505E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.675487E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162839E+09 |
February | 0.882782E+09 | 0.552804E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238108E+09 |
March | 0.105485E+10 | 0.612553E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143212E+09 |
April | 0.936002E+09 | 0.519534E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194858E+09 |
May | 0.101394E+10 | 0.542827E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478063E+09 |
June | 0.101113E+10 | 0.533401E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 188986.25 | 0.377801E+09 |
July | 0.938820E+09 | 0.501923E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 783146.39 | 0.369849E+09 |
August | 0.105485E+10 | 0.573405E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124636.30 | 0.267313E+09 |
September | 0.936002E+09 | 0.532975E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264951E+09 |
October | 0.973041E+09 | 0.604713E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262107E+09 |
November | 0.963541E+09 | 0.663432E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304145E+09 |
December | 0.938820E+09 | 0.701514E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406596E+09 |
Annual Sum or Average | 0.116768E+11 | 0.701457E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1096768.94 | 0.346984E+10 |
Minimum of Months | 0.882782E+09 | 0.501923E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143212E+09 |
Maximum of Months | 0.105485E+10 | 0.701514E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 783146.39 | 0.478063E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219055E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305871E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177547E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222197E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531873E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129075.70 | 0.406067E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892546.84 | 0.393786E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86881.12 | 0.288620E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305069E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329430E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410134E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559525E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1108503.66 | 0.414917E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177547E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892546.84 | 0.559525E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365117E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520633E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303563E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386421E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937528E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238492.75 | 0.715269E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1651619.49 | 0.686658E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168353.12 | 0.504023E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534848E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566979E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689696E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918547E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2058465.36 | 0.712928E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303563E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1651619.49 | 0.937528E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356109E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517052E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317003E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428979E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103499E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77634.87 | 0.814066E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079010.94 | 0.785871E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96012.73 | 0.570068E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574044E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572594E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670050E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892251E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1252658.54 | 0.753308E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317003E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079010.94 | 0.103499E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 337.57 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 1560.90 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 303.66 | 08-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1387.41 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 316.07 | 27-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1166.91 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 343.67 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 499.68 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 13-JUN-15:30 | 344.52 | 05-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 | 22-JUL-17:10 | 337.59 | 30-JUL-18:50 |
August | 2010.79 | 01-AUG-09:09 | 915.09 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 14-AUG-16:50 | 235.58 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 931.95 | 08-SEP-07:30 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 311.19 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1653.31 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 391.20 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 413.87 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-15:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 608.08 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.58 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 | 608.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 223.45 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1000.39 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 198.53 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 860.86 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 205.70 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 697.61 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 221.74 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 328.02 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 13-JUN-15:30 | 256.55 | 18-JUN-10:30 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 22-JUL-18:51 | 223.98 | 30-JUL-18:50 |
August | 1295.83 | 01-AUG-09:09 | 573.67 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 14-AUG-16:50 | 151.73 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 587.26 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 207.79 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1065.08 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 253.61 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 266.12 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-15:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 392.49 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.73 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 392.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 334.54 | 01-JAN-14:53 |
February | 2010.83 | 01-FEB-10:09 | 1556.00 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 323.90 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1374.55 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 304.71 | 27-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1158.73 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 331.79 | 23-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 491.55 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 13-JUN-15:30 | 375.46 | 18-JUN-12:00 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 22-JUL-18:51 | 352.64 | 30-JUL-18:50 |
August | 2010.83 | 01-AUG-09:09 | 913.25 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 14-AUG-16:50 | 240.91 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 926.67 | 08-SEP-07:30 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 307.87 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1652.96 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 387.80 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.49 | 25-NOV-05:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-15:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 596.43 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.91 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 596.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 236.68 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1006.46 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 220.84 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 907.47 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 229.34 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 775.18 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 259.32 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 560.16 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 352.56 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 13-JUN-15:30 | 294.62 | 18-JUN-16:00 |
July | 1295.83 | 03-JUL-09:09 | 553.30 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 22-JUL-19:04 | 291.31 | 30-JUL-18:50 |
August | 1295.83 | 01-AUG-09:09 | 595.53 | 22-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 14-AUG-16:50 | 178.24 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 776.93 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 220.61 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1065.46 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 288.63 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 307.24 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-15:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 455.85 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.24 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 455.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 680.82 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 1559.83 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 653.86 | 08-FEB-22:05 |
March | 2010.79 | 01-MAR-10:09 | 1384.38 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 658.53 | 27-MAR-21:20 |
April | 2010.79 | 03-APR-09:09 | 1161.38 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 707.68 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1093.58 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 13-JUN-15:40 | 767.79 | 05-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 | 22-JUL-18:51 | 700.05 | 30-JUL-18:40 |
August | 2010.79 | 01-AUG-09:09 | 908.96 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 14-AUG-16:50 | 511.32 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 926.78 | 08-SEP-07:30 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 654.66 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1653.22 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 812.34 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 795.30 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-15:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1237.07 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.32 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 | 1237.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 458.90 | 08-JAN-08:00 |
February | 1239.33 | 01-FEB-08:09 | 998.64 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 436.34 | 08-FEB-22:05 |
March | 1239.33 | 01-MAR-08:09 | 856.23 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 440.82 | 27-MAR-21:20 |
April | 1239.33 | 03-APR-07:10 | 689.77 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 474.26 | 23-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 726.38 | 04-MAY-23:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 13-JUN-15:40 | 624.42 | 18-JUN-10:00 |
July | 1239.33 | 03-JUL-07:10 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 22-JUL-18:51 | 503.92 | 30-JUL-18:40 |
August | 1239.33 | 01-AUG-07:10 | 569.42 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 | 14-AUG-16:50 | 344.34 | 22-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 583.69 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 448.10 | 06-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 1064.92 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 540.53 | 20-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 525.72 | 25-NOV-05:00 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-15:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 826.90 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.34 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 826.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 771.34 | 01-JAN-14:53 |
February | 2010.83 | 01-FEB-10:09 | 1554.92 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 719.80 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1371.46 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 664.03 | 27-MAR-21:20 |
April | 2010.83 | 03-APR-09:09 | 1153.13 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 784.83 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1096.83 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 13-JUN-15:40 | 848.68 | 18-JUN-16:10 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 22-JUL-18:51 | 809.35 | 30-JUL-18:40 |
August | 2010.83 | 01-AUG-09:09 | 907.03 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 14-AUG-16:50 | 542.59 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 921.25 | 08-SEP-07:30 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 676.40 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1652.86 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 861.67 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 808.55 | 26-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-15:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1281.32 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.59 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 1281.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 468.82 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1004.79 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 451.84 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 903.20 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 452.53 | 27-MAR-21:20 |
April | 1295.83 | 03-APR-09:09 | 767.45 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 484.31 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 554.67 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 750.30 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 13-JUN-15:40 | 653.12 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 547.42 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 22-JUL-19:04 | 655.94 | 30-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 592.03 | 22-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 | 14-AUG-16:50 | 380.41 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 768.66 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 451.79 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1065.30 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 572.45 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 545.66 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-15:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 848.88 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.41 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 848.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 746.52 | 10-JAN-05:52 |
February | 2010.79 | 01-FEB-10:09 | 1559.61 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 805.07 | 08-FEB-22:05 |
March | 2010.79 | 01-MAR-10:09 | 1383.82 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 805.16 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1160.35 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 780.21 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1262.32 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 13-JUN-15:50 | 931.87 | 05-JUN-21:17 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 22-JUL-17:01 | 862.65 | 30-JUL-18:40 |
August | 2010.79 | 01-AUG-09:09 | 908.71 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 14-AUG-16:50 | 618.12 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 926.57 | 08-SEP-07:30 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 736.62 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1653.20 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 924.84 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 942.86 | 25-NOV-05:18 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-15:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1441.23 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.12 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 1441.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 498.84 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 998.50 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 536.77 | 08-FEB-22:05 |
March | 1295.83 | 01-MAR-10:09 | 855.84 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 536.77 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 689.04 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 523.95 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 840.92 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 13-JUN-15:50 | 755.00 | 18-JUN-10:20 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 | 22-JUL-18:51 | 627.43 | 30-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 569.22 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 14-AUG-16:50 | 416.15 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 583.52 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 508.11 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1064.91 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 614.11 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 630.00 | 25-NOV-05:15 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-15:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 961.51 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 | 961.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 773.64 | 01-JAN-14:53 |
February | 2010.83 | 01-FEB-10:09 | 1554.70 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 828.81 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1370.88 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 805.77 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1152.09 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 911.31 | 16-APR-12:10 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1272.97 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 13-JUN-15:50 | 1057.36 | 18-JUN-15:50 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 22-JUL-18:51 | 1004.17 | 30-JUL-18:40 |
August | 2010.83 | 01-AUG-09:09 | 906.78 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 14-AUG-16:50 | 660.13 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 921.03 | 08-SEP-07:30 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 767.93 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1652.84 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 968.87 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 943.46 | 25-NOV-05:15 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-15:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1484.54 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.13 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 1484.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 500.52 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1004.65 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 542.94 | 08-FEB-22:05 |
March | 1295.83 | 01-MAR-10:09 | 902.86 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 539.59 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 766.83 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 561.95 | 15-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 554.45 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 878.60 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 13-JUN-15:50 | 810.54 | 18-JUN-16:30 |
July | 1295.83 | 03-JUL-09:09 | 547.19 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 22-JUL-19:04 | 814.79 | 30-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 591.89 | 22-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 14-AUG-16:50 | 468.37 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 768.16 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 517.44 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1065.29 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 660.40 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 645.73 | 25-NOV-05:13 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-15:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1000.87 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.37 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 1000.87 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 741.10 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 662.09 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 665.80 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 723.33 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1076.53 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 13-JUN-16:00 | 719.20 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.63 | 22-JUL-18:51 | 683.17 | 30-JUL-18:54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 14-AUG-17:00 | 492.43 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 673.91 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 828.77 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 891.89 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1328.43 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.63 | 1328.43 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1253.99 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1139.47 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1131.38 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1239.14 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1904.22 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.63 | 13-JUN-16:00 | 1267.96 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 | 22-JUL-18:51 | 1158.32 | 30-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 14-AUG-17:00 | 872.97 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1161.64 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1424.81 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1460.81 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2200.30 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 | 2200.30 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1108.66 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1207.18 | 08-FEB-22:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1188.44 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1232.66 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2000.73 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 13-JUN-17:00 | 1495.05 | 18-JUN-15:52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.69 | 22-JUL-18:51 | 1449.55 | 30-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 14-AUG-18:00 | 957.54 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1147.61 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1445.98 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1364.89 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2316.74 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.54 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.69 | 2316.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 111123.50 | 02-JAN-07:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95235.04 | 21-FEB-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96996.31 | 27-MAR-06:03 | 10771.35 | 14744.03 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96456.63 | 24-APR-06:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97894.25 | 30-MAY-06:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 101625.20 | 19-JUN-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 102007.13 | 03-JUL-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102137.63 | 21-AUG-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102371.61 | 25-SEP-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 104734.47 | 10-OCT-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99358.46 | 24-NOV-07:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97437.74 | 26-DEC-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95235.04 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 111123.50 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88619.44 | 02-JAN-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81772.70 | 21-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82938.60 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87445.80 | 24-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85883.87 | 01-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85423.96 | 26-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87675.36 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85031.48 | 31-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87306.75 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89111.07 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87877.13 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85154.44 | 26-DEC-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81772.70 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89111.07 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 60967.34 | 26-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48192.43 | 10-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67624.79 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73918.68 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73693.49 | 02-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74540.92 | 27-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74731.92 | 25-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74337.61 | 17-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73778.04 | 16-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71727.14 | 04-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66767.28 | 09-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25478.47 | 22-DEC-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 25478.47 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74731.92 | 15316.26 | 13241.18 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18855.40 | 19-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18821.81 | 24-FEB-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24773.78 | 31-MAR-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54694.11 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64321.83 | 01-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68848.10 | 27-JUN-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68185.20 | 18-JUL-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 66784.43 | 07-AUG-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64517.92 | 13-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31166.30 | 03-OCT-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23184.75 | 10-NOV-16:30 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15997.16 | 21-DEC-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15997.16 | 6448.95 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68848.10 | 15316.26 | 13241.18 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2667.39 | 17-JAN-13:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 |
February | 3270.94 | 21-FEB-13:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 |
March | 5063.11 | 20-MAR-12:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 |
April | 7115.20 | 28-APR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 |
May | 7218.40 | 22-MAY-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12869.16 | 25-JUN-15:41 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
July | 10181.87 | 24-JUL-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 |
August | 8259.68 | 14-AUG-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
September | 6497.47 | 13-SEP-14:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
October | 5655.85 | 10-OCT-13:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 |
November | 3588.58 | 08-NOV-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 |
December | 2445.35 | 11-DEC-06:02 | 1619.46 | 539.77 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2445.35 | 809.73 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12869.16 | 4021.58 | 1582.09 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 36.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4567.67 | 20-JAN-10:10 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5907.02 | 17-FEB-09:45 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5414.13 | 25-MAR-09:25 | 818.42 | 339.85 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22689.19 | 30-APR-08:21 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 |
May | 22967.80 | 21-MAY-07:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 |
June | 23199.11 | 18-JUN-08:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.17 |
July | 22441.80 | 23-JUL-08:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 |
August | 22007.77 | 06-AUG-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.27 |
September | 19933.29 | 04-SEP-08:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 |
October | 11080.72 | 01-OCT-08:33 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5300.60 | 13-NOV-09:25 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
December | 3436.18 | 26-DEC-10:10 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3436.18 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23199.11 | 2591.66 | 1019.56 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27970.68 | 15-JAN-13:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.37 |
February | 29902.07 | 19-FEB-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 |
March | 12735.62 | 28-MAR-12:05 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 |
April | 33905.21 | 30-APR-14:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.03 |
May | 30163.83 | 21-MAY-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.42 |
June | 29235.78 | 25-JUN-15:41 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 |
July | 29859.53 | 09-JUL-12:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 |
August | 32306.28 | 06-AUG-12:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.87 |
September | 31056.50 | 04-SEP-12:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.20 |
October | 32080.15 | 01-OCT-13:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.19 |
November | 23181.21 | 11-NOV-13:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.86 |
December | 16115.18 | 18-DEC-13:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12735.62 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | |
Maximum of Months | 33905.21 | 3846.30 | 1582.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8277.64 | 30-JAN-16:35 | 4957.30 | 2336.30 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17474.32 | 19-FEB-16:12 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 |
March | 11817.99 | 24-MAR-05:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29483.21 | 30-APR-14:21 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 |
May | 30731.96 | 21-MAY-16:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.54 |
June | 30549.41 | 25-JUN-17:41 | 0.00 | 254.87 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 |
July | 32567.24 | 09-JUL-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 |
August | 28424.51 | 20-AUG-16:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 |
September | 25832.24 | 04-SEP-14:52 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 |
October | 25689.09 | 01-OCT-15:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.41 |
November | 14986.02 | 09-NOV-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12109.72 | 11-DEC-06:01 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8277.64 | 0.00 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32567.24 | 4957.30 | 2336.30 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1812.70 | 15-JAN-12:52 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1784.64 | 19-FEB-13:02 | 404.87 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 |
March | 2062.57 | 30-MAR-14:10 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
April | 5490.74 | 28-APR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 |
May | 6037.18 | 22-MAY-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 7540.97 | 13-JUN-14:50 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 0.00 |
July | 7481.41 | 10-JUL-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
August | 6478.07 | 14-AUG-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 0.00 |
September | 5677.97 | 13-SEP-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
October | 3115.18 | 06-OCT-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.44 |
November | 2094.05 | 09-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1619.91 | 21-DEC-14:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1619.91 | 404.87 | 175.78 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7540.97 | 3846.22 | 1582.09 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 143.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4224.81 | 20-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5254.71 | 24-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.41 |
March | 5613.00 | 25-MAR-10:05 | 782.73 | 339.85 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24440.98 | 30-APR-07:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.01 |
May | 22661.12 | 21-MAY-09:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.58 |
June | 21352.52 | 25-JUN-09:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26919.34 | 23-JUL-09:11 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.54 |
August | 24198.76 | 13-AUG-09:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.79 |
September | 23241.04 | 24-SEP-09:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.25 |
October | 10497.86 | 01-OCT-09:33 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 |
November | 4458.31 | 03-NOV-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 |
December | 2249.56 | 08-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2249.56 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26919.34 | 2478.65 | 1019.56 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32033.89 | 15-JAN-12:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30396.80 | 19-FEB-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.43 |
March | 11773.16 | 28-MAR-12:05 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 |
April | 36852.63 | 30-APR-12:31 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.25 |
May | 30078.73 | 21-MAY-12:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.09 |
June | 28664.25 | 11-JUN-13:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.91 |
July | 33313.09 | 30-JUL-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.39 |
August | 33817.20 | 13-AUG-12:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.69 |
September | 35054.41 | 10-SEP-11:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.78 |
October | 31405.67 | 01-OCT-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.97 |
November | 33605.27 | 11-NOV-13:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.18 |
December | 14902.03 | 18-DEC-13:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11773.16 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36852.63 | 3846.30 | 1582.13 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4633.09 | 30-JAN-16:27 | 4957.30 | 2039.12 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7552.06 | 27-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8123.63 | 23-MAR-16:40 | 391.37 | 283.21 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 |
April | 27446.79 | 30-APR-17:51 | 0.00 | 254.87 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 |
May | 26449.27 | 28-MAY-17:01 | 0.00 | 198.23 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.13 |
June | 25463.19 | 11-JUN-17:12 | 0.00 | 169.91 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 |
July | 29331.18 | 09-JUL-17:21 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.39 |
August | 25914.12 | 13-AUG-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.76 |
September | 26003.81 | 10-SEP-15:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.48 |
October | 10350.14 | 03-OCT-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.44 |
November | 4749.94 | 10-NOV-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
December | 1978.58 | 21-DEC-14:40 | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1978.58 | 0.00 | 169.91 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29331.18 | 4957.30 | 2039.12 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1630.71 | 19-JAN-15:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1572.87 | 24-FEB-16:10 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.77 |
March | 1899.98 | 30-MAR-15:50 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.03 |
April | 5688.57 | 28-APR-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 |
May | 6662.35 | 22-MAY-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 |
June | 12095.31 | 25-JUN-18:11 | 0.00 | 351.55 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 |
July | 8167.27 | 10-JUL-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 |
August | 7013.47 | 14-AUG-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 |
September | 5869.38 | 13-SEP-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
October | 2342.06 | 06-OCT-15:50 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.43 |
November | 1759.66 | 10-NOV-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 |
December | 1420.14 | 21-DEC-14:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1420.14 | 0.00 | 351.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12095.31 | 2010.79 | 791.05 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 187.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1297.71 | 20-JAN-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2243.20 | 24-FEB-10:30 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
March | 1940.75 | 25-MAR-09:25 | 818.42 | 339.85 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22477.07 | 30-APR-09:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.23 |
May | 22582.35 | 21-MAY-09:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.70 |
June | 24093.70 | 25-JUN-09:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 |
July | 23719.36 | 23-JUL-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.80 |
August | 23591.84 | 13-AUG-10:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.57 |
September | 22428.86 | 10-SEP-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.39 |
October | 6245.65 | 04-OCT-10:00 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1270.72 | 03-NOV-10:00 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.19 |
December | 1093.37 | 06-DEC-10:30 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1093.37 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24093.70 | 1295.83 | 509.78 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13625.42 | 11-JAN-13:35 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.87 |
February | 17662.79 | 17-FEB-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.64 |
March | 9128.44 | 28-MAR-12:20 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.65 |
April | 34802.81 | 30-APR-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.41 |
May | 32846.24 | 21-MAY-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.63 |
June | 31878.22 | 25-JUN-16:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 |
July | 34373.55 | 30-JUL-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.12 |
August | 35546.75 | 06-AUG-14:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.90 |
September | 37898.27 | 10-SEP-13:41 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.22 |
October | 32908.92 | 01-OCT-14:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.75 |
November | 26008.30 | 11-NOV-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.46 |
December | 11689.19 | 18-DEC-13:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9128.44 | 506.09 | 219.72 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 | |
Maximum of Months | 37898.27 | 3846.30 | 1582.13 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3716.70 | 19-JAN-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6422.60 | 27-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7357.25 | 23-MAR-16:40 | 391.37 | 283.21 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.38 |
April | 26562.00 | 30-APR-16:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 |
May | 29531.64 | 21-MAY-16:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.11 |
June | 29498.64 | 25-JUN-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.66 |
July | 27376.52 | 09-JUL-17:01 | 0.00 | 198.23 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.22 |
August | 29075.23 | 13-AUG-16:41 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.83 |
September | 27053.10 | 10-SEP-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 |
October | 9857.98 | 03-OCT-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 |
November | 4020.84 | 10-NOV-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 |
December | 1290.28 | 21-DEC-14:50 | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1290.28 | 0.00 | 198.23 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29531.64 | 1295.83 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6904.53 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2917.45 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 |
March | 3824.30 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 |
April | 7072.12 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 |
May | 8552.30 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.01 |
June | 9520.52 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 |
July | 9478.79 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.55 |
August | 8329.13 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
September | 7598.44 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.80 |
October | 7322.63 | 10-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5174.75 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 |
December | 2899.59 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2899.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9520.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6976.41 | 09-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6732.93 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.34 |
March | 3920.90 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4379.17 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 |
May | 4209.76 | 23-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 |
June | 5287.33 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 |
July | 5861.46 | 24-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.09 |
August | 5047.26 | 18-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 |
September | 4861.19 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.42 |
October | 3233.98 | 04-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.93 |
November | 5853.75 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
December | 7327.77 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3233.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7327.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 802.12 | 15-JAN-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.78 |
February | 932.63 | 19-FEB-14:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.99 |
March | 2336.60 | 25-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.23 |
April | 13806.57 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.74 |
May | 14725.38 | 22-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.63 |
June | 16724.70 | 21-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 |
July | 16118.99 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 0.00 |
August | 14530.89 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
September | 12147.50 | 12-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.19 |
October | 5604.62 | 03-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.56 |
November | 1268.25 | 11-NOV-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.97 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16724.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 523.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1999.47 | 19-JAN-16:20 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4205.20 | 27-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7034.48 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8371.54 | 30-APR-17:51 | 0.00 | 158.32 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3372.32 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5209.59 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7262.21 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8293.66 | 13-AUG-18:10 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3263.99 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5112.29 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5771.86 | 03-NOV-16:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7486.45 | 26-DEC-15:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1999.47 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8371.54 | 222.14 | 316.63 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1773.56 | 19-JAN-16:30 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3835.29 | 27-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6376.95 | 31-MAR-23:30 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8008.14 | 30-APR-18:03 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3105.63 | 31-MAY-23:50 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4782.95 | 30-JUN-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6840.14 | 31-JUL-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7743.09 | 13-AUG-18:10 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2923.62 | 30-SEP-23:30 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4450.68 | 31-OCT-23:50 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5382.10 | 03-NOV-16:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6893.74 | 21-DEC-15:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1773.56 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8008.14 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1658.84 | 19-JAN-16:30 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3637.95 | 24-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5931.60 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8126.50 | 30-APR-17:51 | 0.00 | 158.32 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2961.29 | 31-MAY-23:20 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4574.88 | 30-JUN-23:20 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6687.46 | 31-JUL-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7864.38 | 13-AUG-18:10 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2414.99 | 30-SEP-23:20 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3889.78 | 31-OCT-23:20 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5277.81 | 10-NOV-16:10 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6637.34 | 21-DEC-15:30 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1658.84 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8126.50 | 222.14 | 316.63 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91783.47 | 02-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182736.81 | 09-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358533.51 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367389.12 | 28-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175824.81 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267114.00 | 30-JUN-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359962.27 | 31-JUL-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367923.07 | 14-AUG-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175566.81 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267358.73 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275316.13 | 13-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366923.50 | 26-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91783.47 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367923.07 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.154171E+13 | 1129267.13 | 02-JAN-16:30 | 0.302377E+12 | 730515.30 | 10-JAN-07:00 |
February | 0.174270E+13 | 1255909.78 | 17-FEB-15:30 | 0.217878E+12 | 655652.41 | 17-FEB-07:10 |
March | 0.236524E+13 | 1414860.12 | 23-MAR-15:00 | 0.183640E+12 | 449411.80 | 08-MAR-07:10 |
April | 0.264384E+13 | 1785437.84 | 28-APR-15:20 | 0.402229E+11 | 336327.70 | 08-APR-06:10 |
May | 0.155974E+13 | 1381304.09 | 22-MAY-14:09 | 0.237652E+11 | 316584.10 | 17-MAY-11:20 |
June | 0.187838E+13 | 1628448.88 | 13-JUN-15:30 | 0.222445E+10 | 144877.45 | 28-JUN-09:09 |
July | 0.226802E+13 | 1756958.56 | 21-JUL-15:20 | 0.336632E+09 | 56365.97 | 08-JUL-11:20 |
August | 0.276100E+13 | 1891077.76 | 14-AUG-15:20 | 77050183.19 | 57097.95 | 24-AUG-06:10 |
September | 0.152423E+13 | 1385400.98 | 27-SEP-15:20 | 0.478172E+10 | 335198.81 | 08-SEP-09:30 |
October | 0.187374E+13 | 1402714.00 | 05-OCT-15:30 | 0.534561E+11 | 294142.26 | 23-OCT-06:10 |
November | 0.220590E+13 | 1425324.03 | 28-NOV-16:19 | 0.164304E+12 | 556762.98 | 29-NOV-07:10 |
December | 0.268961E+13 | 1561977.39 | 22-DEC-16:19 | 0.322902E+12 | 607609.58 | 27-DEC-07:10 |
Annual Sum or Average | 0.250541E+14 | 0.131597E+13 | ||||
Minimum of Months | 0.152423E+13 | 1129267.13 | 77050183.19 | 56365.97 | ||
Maximum of Months | 0.276100E+13 | 1891077.76 | 0.322902E+12 | 730515.30 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.211645E+12 | 0.444933E+11 | 0.766053E+12 | 0.213317E+12 | 0.160988E+12 | 0.142370E+11 | 0.00 | 0.111669E+11 | 0.900536E+09 | 0.789386E+11 | 0.00 | 0.399684E+11 | 0.00 |
February | 0.188400E+12 | 0.345613E+11 | 0.978954E+12 | 0.195309E+12 | 0.148954E+12 | 0.150129E+11 | 0.00 | 0.238811E+11 | 0.192464E+10 | 0.119152E+12 | 0.00 | 0.365525E+11 | 0.00 |
March | 0.221393E+12 | 0.308164E+11 | 0.141687E+13 | 0.226028E+12 | 0.169117E+12 | 0.160559E+11 | 0.00 | 0.403234E+11 | 0.374055E+10 | 0.198201E+12 | 0.00 | 0.426940E+11 | 0.00 |
April | 0.195857E+12 | 0.230363E+11 | 0.165903E+13 | 0.211475E+12 | 0.201442E+12 | 0.158250E+11 | 0.00 | 0.686301E+11 | 0.131402E+11 | 0.217381E+12 | 0.00 | 0.380234E+11 | 0.00 |
May | 0.210448E+12 | 0.191640E+11 | 0.774844E+12 | 0.219671E+12 | 0.205937E+12 | 0.166455E+11 | 0.00 | 0.251733E+11 | 0.703800E+10 | 0.412844E+11 | 0.00 | 0.395395E+11 | 0.00 |
June | 0.209133E+12 | 0.165920E+11 | 0.106252E+13 | 0.217906E+12 | 0.219178E+12 | 0.224004E+11 | 0.00 | 0.590601E+11 | 0.199756E+11 | 0.134571E+11 | 0.00 | 0.381603E+11 | 0.00 |
July | 0.195567E+12 | 0.178410E+11 | 0.139340E+13 | 0.213239E+12 | 0.228719E+12 | 0.305382E+11 | 0.00 | 0.105047E+12 | 0.377076E+11 | 0.103831E+11 | 0.00 | 0.355781E+11 | 0.00 |
August | 0.219034E+12 | 0.214285E+11 | 0.173200E+13 | 0.226028E+12 | 0.240692E+12 | 0.322019E+11 | 0.00 | 0.173530E+12 | 0.634759E+11 | 0.139909E+11 | 0.00 | 0.386189E+11 | 0.00 |
September | 0.196602E+12 | 0.266429E+11 | 0.740713E+12 | 0.211474E+12 | 0.211416E+12 | 0.245057E+11 | 0.00 | 0.436842E+11 | 0.186214E+11 | 0.152606E+11 | 0.00 | 0.353128E+11 | 0.00 |
October | 0.207362E+12 | 0.350556E+11 | 0.108340E+13 | 0.213316E+12 | 0.183461E+12 | 0.165817E+11 | 0.00 | 0.332002E+11 | 0.400908E+10 | 0.601713E+11 | 0.00 | 0.371810E+11 | 0.00 |
November | 0.209132E+12 | 0.409293E+11 | 0.135889E+13 | 0.205271E+12 | 0.164470E+12 | 0.145074E+11 | 0.00 | 0.372019E+11 | 0.371908E+10 | 0.134307E+12 | 0.00 | 0.374732E+11 | 0.00 |
December | 0.207541E+12 | 0.463809E+11 | 0.170972E+13 | 0.213243E+12 | 0.162487E+12 | 0.181300E+11 | 0.00 | 0.495735E+11 | 0.403107E+10 | 0.240203E+12 | 0.00 | 0.382974E+11 | 0.00 |
Annual Sum or Average | 0.247212E+13 | 0.356942E+12 | 0.146764E+14 | 0.256628E+13 | 0.229686E+13 | 0.236642E+12 | 0.00 | 0.670472E+12 | 0.178284E+12 | 0.114273E+13 | 0.00 | 0.457399E+12 | 0.00 |
Minimum of Months | 0.188400E+12 | 0.165920E+11 | 0.740713E+12 | 0.195309E+12 | 0.148954E+12 | 0.142370E+11 | 0.00 | 0.111669E+11 | 0.900536E+09 | 0.103831E+11 | 0.00 | 0.353128E+11 | 0.00 |
Maximum of Months | 0.221393E+12 | 0.463809E+11 | 0.173200E+13 | 0.226028E+12 | 0.240692E+12 | 0.322019E+11 | 0.00 | 0.173530E+12 | 0.634759E+11 | 0.240203E+12 | 0.00 | 0.426940E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.302377E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.217878E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183640E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.402229E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.237652E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.222445E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.336632E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 77050183.19 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.478172E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.534561E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.164304E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.322902E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131597E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 77050183.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.322902E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233397.31 | 02-JAN-08:20 | 101033.72 | 20-JAN-11:00 | 18170.41 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 243017.97 | 01-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233395.08 | 01-FEB-08:20 | 111983.74 | 17-FEB-15:09 | 18113.87 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 235791.35 | 15-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233391.25 | 15-MAR-07:19 | 116306.45 | 23-MAR-15:00 | 18094.66 | 23-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 226878.90 | 10-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233386.53 | 10-APR-07:19 | 243234.11 | 28-APR-14:00 | 21631.14 | 28-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 213358.94 | 04-MAY-07:10 | 27558.46 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 233379.38 | 04-MAY-07:19 | 213421.80 | 22-MAY-15:20 | 35781.80 | 22-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 212815.01 | 01-JUN-07:10 | 27558.46 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 233379.09 | 01-JUN-07:19 | 271814.05 | 21-JUN-13:09 | 35484.20 | 21-JUN-14:20 | 0.00 | 01-JUN-00:10 |
July | 213272.36 | 07-JUL-07:10 | 27558.46 | 01-JUL-20:19 | 660080.29 | 03-JUL-07:10 | 233379.33 | 07-JUL-07:19 | 233886.10 | 21-JUL-15:20 | 36078.34 | 21-JUL-10:30 | 0.00 | 01-JUL-00:10 |
August | 217343.54 | 22-AUG-07:30 | 40855.88 | 14-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233381.49 | 22-AUG-07:40 | 244033.36 | 14-AUG-15:20 | 37697.36 | 28-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 219124.14 | 08-SEP-07:30 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233382.43 | 08-SEP-07:40 | 243421.08 | 12-SEP-15:20 | 36217.64 | 12-SEP-12:50 | 0.00 | 01-SEP-00:10 |
October | 246830.99 | 31-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233397.11 | 31-OCT-07:19 | 184276.77 | 03-OCT-15:09 | 18955.80 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 06-NOV-16:49 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233397.14 | 02-NOV-07:19 | 119164.29 | 03-NOV-14:09 | 18212.99 | 10-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-15:30 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233397.31 | 27-DEC-08:20 | 96865.77 | 21-DEC-13:00 | 18181.73 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 212815.01 | 27558.46 | 423497.50 | 233379.09 | 96865.77 | 18094.66 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233397.31 | 271814.05 | 37697.36 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 21329.45 | 20-JAN-11:00 | 963.60 | 29-JAN-05:00 | 62685.53 | 10-JAN-17:00 | 0.00 | 52757.22 | 31-JAN-12:39 | 0.00 |
February | 34188.06 | 09-FEB-15:20 | 2044.52 | 04-FEB-16:10 | 100000.00 | 20-FEB-15:00 | 0.00 | 52812.23 | 15-FEB-12:00 | 0.00 |
March | 40274.37 | 23-MAR-15:00 | 3039.13 | 25-MAR-12:00 | 100000.00 | 03-MAR-22:19 | 0.00 | 52754.88 | 01-MAR-12:20 | 0.00 |
April | 199802.19 | 28-APR-15:20 | 45911.21 | 28-APR-15:30 | 100000.00 | 01-APR-04:19 | 0.00 | 52227.34 | 03-APR-11:50 | 0.00 |
May | 185073.26 | 22-MAY-14:09 | 70679.03 | 22-MAY-13:00 | 97976.13 | 21-MAY-14:00 | 0.00 | 51334.25 | 01-MAY-11:50 | 0.00 |
June | 279903.85 | 13-JUN-15:00 | 70679.03 | 12-JUN-12:39 | 100000.00 | 08-JUN-11:00 | 0.00 | 49552.87 | 01-JUN-11:30 | 0.00 |
July | 297871.88 | 21-JUL-15:30 | 70679.03 | 10-JUL-09:30 | 100000.00 | 05-JUL-15:50 | 0.00 | 47949.57 | 03-JUL-11:20 | 0.00 |
August | 308140.72 | 14-AUG-15:00 | 70679.03 | 14-AUG-09:00 | 100000.00 | 14-AUG-16:49 | 0.00 | 47401.14 | 31-AUG-11:00 | 0.00 |
September | 158947.61 | 13-SEP-16:30 | 70679.03 | 11-SEP-13:50 | 71093.21 | 29-SEP-16:00 | 0.00 | 47953.77 | 29-SEP-11:20 | 0.00 |
October | 87897.96 | 05-OCT-14:09 | 43991.46 | 07-OCT-14:30 | 100000.00 | 07-OCT-16:10 | 0.00 | 49560.35 | 31-OCT-11:20 | 0.00 |
November | 43001.64 | 03-NOV-14:39 | 4754.97 | 24-NOV-11:00 | 100000.00 | 17-NOV-08:09 | 0.00 | 51296.61 | 30-NOV-12:30 | 0.00 |
December | 25614.02 | 21-DEC-14:09 | 3291.63 | 23-DEC-10:00 | 100000.00 | 03-DEC-11:00 | 0.00 | 52230.78 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 21329.45 | 963.60 | 62685.53 | 0.00 | 47401.14 | 0.00 | ||||
Maximum of Months | 308140.72 | 70679.03 | 100000.00 | 0.00 | 52812.23 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1129267.13 | 02-JAN-16:30 | 247210.90 | 423497.50 | 40855.88 | 233278.53 | 78625.29 | 18058.24 | 0.00 | 7239.06 | 392.46 |
February | 1255909.78 | 17-FEB-15:30 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 111520.05 | 18074.97 | 0.00 | 28321.91 | 1044.01 |
March | 1414860.12 | 23-MAR-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 116306.45 | 18094.66 | 0.00 | 40274.37 | 2091.93 |
April | 1785437.84 | 28-APR-15:20 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 238924.69 | 18712.51 | 0.00 | 199802.19 | 45736.29 |
May | 1381304.09 | 22-MAY-14:09 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 204258.87 | 34492.27 | 0.00 | 185073.26 | 59319.94 |
June | 1628448.88 | 13-JUN-15:30 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 226977.13 | 34623.45 | 0.00 | 270880.87 | 70679.03 |
July | 1756958.56 | 21-JUL-15:20 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 233886.10 | 35155.62 | 0.00 | 296476.75 | 47886.50 |
August | 1891077.76 | 14-AUG-15:20 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 244033.36 | 34997.44 | 0.00 | 303859.02 | 46730.60 |
September | 1385400.98 | 27-SEP-15:20 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 203804.49 | 32957.86 | 0.00 | 131788.50 | 44801.44 |
October | 1402714.00 | 05-OCT-15:30 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 168759.13 | 18303.32 | 0.00 | 85614.34 | 4353.25 |
November | 1425324.03 | 28-NOV-16:19 | 247210.90 | 660080.29 | 40855.88 | 233284.51 | 81591.38 | 18052.15 | 0.00 | 15354.52 | 1162.08 |
December | 1561977.39 | 22-DEC-16:19 | 247210.90 | 778371.69 | 40855.88 | 233284.51 | 83871.98 | 18046.00 | 0.00 | 20742.76 | 1816.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1129267.13 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 78625.29 | 18046.00 | 0.00 | 7239.06 | 392.46 | |
Maximum of Months | 1891077.76 | 247210.90 | 778371.69 | 40855.88 | 233284.51 | 244033.36 | 35155.62 | 0.00 | 303859.02 | 70679.03 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 730515.30 | 10-JAN-07:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 655652.41 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 449411.80 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 336327.70 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 316584.10 | 17-MAY-11:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 144877.45 | 28-JUN-09:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 56365.97 | 08-JUL-11:20 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 57097.95 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 335198.81 | 08-SEP-09:30 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 294142.26 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 556762.98 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 607609.58 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 56365.97 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 730515.30 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 79.33 | 27.17 | 38.00 | 27.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 26.11 | 23.50 | 26.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 26.18 | 27.67 | 26.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 26.44 | 26.33 | 26.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 26.57 | 29.17 | 26.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 26.42 | 30.50 | 26.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 | 26.77 | 30.67 | 26.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 | 26.82 | 33.33 | 26.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 26.79 | 37.17 | 26.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 72.83 | 26.84 | 39.33 | 26.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 26.71 | 32.17 | 26.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 26.44 | 25.67 | 26.39 |
Annual Sum or Average | 0.00 | 0.00 | 769.17 | 26.65 | 373.50 | 26.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 26.11 | 23.50 | 26.11 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 | 27.17 | 39.33 | 27.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.56 | 0.00 | 25.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.58 | 0.00 | 25.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
December | 1.50 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 2.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.04 | 2.00 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.91 | 2.83 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.92 | 4.50 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.97 | 7.17 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.99 | 4.50 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.88 | 5.00 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.61 | 0.50 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.50 | 27.94 | 26.50 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.04 | 7.17 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.77 | 1.00 | 27.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.74 | 1.50 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.13 | 3.17 | 28.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.57 | 3.50 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 3.67 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.85 | 6.33 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.05 | 7.17 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.11 | 7.00 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.03 | 1.83 | 28.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.78 | 2.00 | 27.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 38.33 | 27.91 | 37.67 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.13 | 7.17 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.62 | 1.17 | 27.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.65 | 7.00 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.23 | 4.00 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.96 | 5.50 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.81 | 10.83 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.57 | 9.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.99 | 4.17 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.91 | 0.83 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.37 | 1.17 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 77.50 | 27.79 | 44.00 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.23 | 10.83 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 1.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.07 | 2.33 | 28.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.11 | 2.33 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.00 | 4.50 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.03 | 7.33 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.95 | 5.50 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.84 | 4.83 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 1.33 | 19.36 | 0.00 | 19.36 | 27.50 | 27.58 | 27.33 | 27.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.38 | 0.00 | 19.38 | 7.50 | 28.11 | 7.33 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.81 | 1.00 | 27.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.77 | 1.67 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.28 | 2.67 | 28.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.66 | 3.17 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.89 | 5.83 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.13 | 6.50 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.29 | 7.17 | 28.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.23 | 1.83 | 28.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.90 | 1.67 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.00 | 28.02 | 34.83 | 28.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.29 | 7.17 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.54 | 1.17 | 28.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.17 | 3.17 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.31 | 2.67 | 28.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.46 | 3.83 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.35 | 3.67 | 28.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.97 | 2.83 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.50 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.33 | 28.30 | 17.83 | 28.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.54 | 3.83 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.50 | 19.02 | 5.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 8.00 | 19.14 | 1.83 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 2.67 | 19.20 | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
November | 7.17 | 19.06 | 2.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 17.17 | 18.85 | 6.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 50.17 | 19.00 | 15.83 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.17 | 19.27 | 6.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
February | 4.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 1.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.91 | 2.50 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.92 | 1.83 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.88 | 4.33 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.00 | 6.67 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.84 | 5.00 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.66 | 2.67 | 27.66 |
October | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
November | 3.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
December | 6.50 | 18.13 | 0.17 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
Annual Sum or Average | 20.83 | 18.52 | 0.17 | 18.50 | 23.83 | 23.49 | 23.00 | 24.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 0.00 | 18.06 |
Maximum of Months | 6.50 | 19.29 | 0.17 | 19.29 | 7.00 | 28.00 | 6.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.48 | 0.00 | 18.48 | 0.17 | 18.85 | 0.17 | 19.19 |
February | 2.33 | 19.08 | 0.00 | 19.08 | 0.50 | 20.55 | 0.50 | 21.59 |
March | 1.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.40 | 2.17 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.66 | 3.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.91 | 5.50 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.11 | 6.50 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.18 | 6.50 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.02 | 1.50 | 28.02 |
November | 2.33 | 18.71 | 0.00 | 18.71 | 0.83 | 21.07 | 0.83 | 22.45 |
December | 5.33 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 15.33 | 18.78 | 0.00 | 18.78 | 30.50 | 24.91 | 29.17 | 26.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 | 0.00 | 18.77 |
Maximum of Months | 5.33 | 19.18 | 0.00 | 19.18 | 6.83 | 28.40 | 6.50 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
February | 1.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 0.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.71 | 1.17 | 28.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.15 | 2.83 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.29 | 2.83 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.55 | 3.67 | 28.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.42 | 3.67 | 28.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.95 | 2.83 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
November | 1.67 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
December | 4.50 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 12.00 | 18.75 | 0.00 | 18.75 | 30.50 | 25.64 | 17.17 | 26.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 | 0.00 | 18.44 |
Maximum of Months | 4.50 | 19.22 | 0.00 | 19.22 | 8.33 | 28.71 | 3.67 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.83 | 24.90 | 129.67 | 25.71 | 13.67 | 25.90 |
February | 29.67 | 24.00 | 114.67 | 25.63 | 0.00 | 25.63 |
March | 26.67 | 24.00 | 114.83 | 25.67 | 0.00 | 25.67 |
April | 0.00 | 0.00 | 133.17 | 26.28 | 0.00 | 26.28 |
May | 1.50 | 26.34 | 205.33 | 25.46 | 1.00 | 25.47 |
June | 0.00 | 0.00 | 333.17 | 24.87 | 0.00 | 24.87 |
July | 1.00 | 27.42 | 437.17 | 24.85 | 1.00 | 24.86 |
August | 4.33 | 27.50 | 446.33 | 24.75 | 4.33 | 24.77 |
September | 11.17 | 27.46 | 334.33 | 25.04 | 11.17 | 25.12 |
October | 1.50 | 27.09 | 230.50 | 25.51 | 1.17 | 25.52 |
November | 3.00 | 25.25 | 195.33 | 25.66 | 1.00 | 25.67 |
December | 21.00 | 24.00 | 134.17 | 25.90 | 0.00 | 25.90 |
Annual Sum or Average | 172.67 | 24.78 | 2808.67 | 25.26 | 33.33 | 25.29 |
Minimum of Months | 0.00 | 0.00 | 114.67 | 24.75 | 0.00 | 24.77 |
Maximum of Months | 72.83 | 27.50 | 446.33 | 26.28 | 13.67 | 26.28 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 146.33 | 23.90 | 65.17 | 24.39 | 0.00 | 24.39 |
February | 82.33 | 23.95 | 59.67 | 24.63 | 0.00 | 24.63 |
March | 35.83 | 23.98 | 78.17 | 25.21 | 0.00 | 25.21 |
April | 1.83 | 23.99 | 97.33 | 25.56 | 0.00 | 25.56 |
May | 4.33 | 23.96 | 154.17 | 24.77 | 0.00 | 24.77 |
June | 0.00 | 0.00 | 339.00 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 427.83 | 24.37 | 0.00 | 24.37 |
August | 0.00 | 0.00 | 450.00 | 24.32 | 0.00 | 24.32 |
September | 0.00 | 0.00 | 303.67 | 24.42 | 0.00 | 24.42 |
October | 2.83 | 23.97 | 205.83 | 24.95 | 0.00 | 24.95 |
November | 22.00 | 23.99 | 152.00 | 25.04 | 0.00 | 25.04 |
December | 55.00 | 23.97 | 91.50 | 25.07 | 0.00 | 25.07 |
Annual Sum or Average | 350.50 | 23.94 | 2424.33 | 24.61 | 0.00 | 24.61 |
Minimum of Months | 0.00 | 0.00 | 59.67 | 24.32 | 0.00 | 24.32 |
Maximum of Months | 146.33 | 23.99 | 450.00 | 25.56 | 0.00 | 25.56 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 429.17 | 23.36 | 12.50 | 23.34 | 12.50 | 23.32 |
February | 364.83 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
March | 366.00 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
April | 141.83 | 23.79 | 25.17 | 24.03 | 0.00 | 24.03 |
May | 110.50 | 23.69 | 73.67 | 24.11 | 0.00 | 24.11 |
June | 5.17 | 23.66 | 215.83 | 24.35 | 0.00 | 24.35 |
July | 7.33 | 23.61 | 276.50 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 290.50 | 24.26 | 0.00 | 24.26 |
September | 31.00 | 23.72 | 163.33 | 24.28 | 0.00 | 24.28 |
October | 177.00 | 23.59 | 48.17 | 23.82 | 0.00 | 23.82 |
November | 320.83 | 23.52 | 3.00 | 23.53 | 0.00 | 23.53 |
December | 475.17 | 23.21 | 0.00 | 23.21 | 0.00 | 23.21 |
Annual Sum or Average | 2428.83 | 23.48 | 1108.67 | 23.76 | 12.50 | 23.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 | 23.21 |
Maximum of Months | 475.17 | 23.79 | 290.50 | 24.35 | 12.50 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 21.55 | 118.33 | 21.27 | 118.33 | 21.08 |
February | 454.00 | 21.85 | 71.67 | 21.61 | 71.67 | 21.42 |
March | 510.83 | 22.42 | 22.83 | 22.33 | 22.83 | 22.25 |
April | 329.33 | 23.31 | 0.50 | 23.31 | 0.00 | 23.31 |
May | 268.50 | 23.32 | 46.67 | 23.44 | 0.00 | 23.44 |
June | 104.17 | 23.42 | 186.83 | 23.93 | 0.00 | 23.93 |
July | 95.83 | 23.43 | 246.00 | 24.00 | 0.00 | 24.00 |
August | 70.17 | 23.45 | 245.17 | 24.01 | 0.00 | 24.01 |
September | 210.83 | 23.21 | 93.00 | 23.49 | 0.00 | 23.49 |
October | 436.50 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
November | 479.00 | 22.03 | 45.67 | 21.89 | 45.67 | 21.77 |
December | 497.00 | 21.38 | 126.83 | 21.09 | 126.83 | 20.89 |
Annual Sum or Average | 3957.50 | 22.34 | 1203.50 | 22.46 | 385.33 | 22.30 |
Minimum of Months | 70.17 | 21.38 | 0.00 | 21.09 | 0.00 | 20.89 |
Maximum of Months | 510.83 | 23.45 | 246.00 | 24.01 | 126.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.00 | 22.56 | 16.00 | 22.52 | 16.00 | 22.47 |
February | 428.33 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
March | 432.00 | 23.27 | 7.50 | 23.30 | 0.00 | 23.30 |
April | 214.33 | 23.64 | 18.83 | 23.77 | 0.00 | 23.77 |
May | 175.00 | 23.56 | 73.33 | 23.81 | 0.00 | 23.81 |
June | 28.50 | 23.75 | 267.50 | 24.24 | 0.00 | 24.24 |
July | 1.67 | 23.88 | 366.33 | 24.36 | 0.00 | 24.36 |
August | 11.17 | 23.75 | 342.50 | 24.24 | 0.00 | 24.24 |
September | 147.50 | 23.48 | 130.50 | 23.84 | 0.00 | 23.84 |
October | 315.17 | 23.26 | 20.00 | 23.35 | 0.00 | 23.35 |
November | 420.17 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
December | 493.67 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 3155.50 | 23.06 | 1242.50 | 23.41 | 16.00 | 23.40 |
Minimum of Months | 1.67 | 22.56 | 0.00 | 22.52 | 0.00 | 22.47 |
Maximum of Months | 493.67 | 23.88 | 366.33 | 24.36 | 16.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.00 | 22.54 | 19.67 | 22.54 | 14.50 | 22.49 |
February | 401.00 | 22.74 | 6.00 | 22.78 | 0.00 | 22.78 |
March | 419.33 | 23.03 | 2.67 | 23.05 | 0.00 | 23.05 |
April | 167.00 | 23.64 | 121.00 | 24.06 | 5.50 | 24.12 |
May | 129.00 | 23.69 | 190.33 | 24.27 | 7.67 | 24.33 |
June | 54.83 | 24.57 | 325.83 | 24.39 | 14.67 | 24.49 |
July | 41.17 | 26.23 | 390.33 | 24.67 | 32.00 | 24.83 |
August | 44.00 | 25.16 | 367.50 | 24.46 | 20.17 | 24.58 |
September | 107.83 | 24.10 | 269.50 | 24.39 | 19.00 | 24.52 |
October | 293.50 | 23.12 | 63.83 | 23.38 | 1.00 | 23.39 |
November | 425.33 | 22.91 | 3.50 | 22.93 | 0.00 | 22.93 |
December | 486.50 | 22.40 | 5.17 | 22.39 | 5.17 | 22.37 |
Annual Sum or Average | 3028.50 | 23.01 | 1765.33 | 23.54 | 119.67 | 23.60 |
Minimum of Months | 41.17 | 22.40 | 2.67 | 22.39 | 0.00 | 22.37 |
Maximum of Months | 486.50 | 26.23 | 390.33 | 24.67 | 32.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.33 | 22.36 | 65.33 | 22.63 | 13.00 | 22.62 |
February | 327.83 | 22.61 | 69.67 | 22.96 | 4.33 | 22.98 |
March | 393.50 | 22.94 | 13.17 | 22.99 | 0.00 | 22.99 |
April | 169.00 | 23.71 | 166.50 | 24.11 | 9.83 | 24.19 |
May | 176.00 | 23.47 | 163.33 | 23.98 | 5.67 | 24.04 |
June | 69.00 | 24.18 | 292.67 | 24.31 | 13.33 | 24.40 |
July | 48.83 | 25.34 | 370.33 | 24.57 | 24.83 | 24.70 |
August | 43.50 | 25.88 | 387.83 | 24.55 | 28.83 | 24.71 |
September | 108.17 | 24.33 | 289.67 | 24.47 | 27.83 | 24.64 |
October | 270.83 | 23.17 | 134.50 | 23.61 | 6.50 | 23.66 |
November | 369.67 | 22.87 | 54.17 | 23.12 | 4.50 | 23.17 |
December | 426.83 | 22.28 | 40.67 | 22.43 | 9.50 | 22.40 |
Annual Sum or Average | 2799.50 | 22.98 | 2047.83 | 23.60 | 148.17 | 23.68 |
Minimum of Months | 43.50 | 22.28 | 13.17 | 22.43 | 0.00 | 22.40 |
Maximum of Months | 426.83 | 25.88 | 387.83 | 24.57 | 28.83 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 387.17 | 23.28 | 21.67 | 23.36 | 0.00 | 23.36 |
February | 225.67 | 23.74 | 57.33 | 23.94 | 1.67 | 23.96 |
March | 116.17 | 23.96 | 76.00 | 24.51 | 0.00 | 24.51 |
April | 19.67 | 26.47 | 289.00 | 25.05 | 15.50 | 25.15 |
May | 51.50 | 24.76 | 245.00 | 24.67 | 15.50 | 24.79 |
June | 26.67 | 26.84 | 442.33 | 24.67 | 26.67 | 24.78 |
July | 44.83 | 27.03 | 482.83 | 24.88 | 44.83 | 25.05 |
August | 38.83 | 27.07 | 506.17 | 24.74 | 38.83 | 24.89 |
September | 34.17 | 25.58 | 342.00 | 24.61 | 19.17 | 24.73 |
October | 60.00 | 23.99 | 182.67 | 24.64 | 3.17 | 24.67 |
November | 100.17 | 23.93 | 120.00 | 24.53 | 0.67 | 24.54 |
December | 168.00 | 23.97 | 50.17 | 24.32 | 0.00 | 24.32 |
Annual Sum or Average | 1272.83 | 24.09 | 2815.17 | 24.51 | 166.00 | 24.61 |
Minimum of Months | 19.67 | 23.28 | 21.67 | 23.36 | 0.00 | 23.36 |
Maximum of Months | 387.17 | 27.07 | 506.17 | 25.05 | 44.83 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.04 | 206.83 | 20.88 | 206.83 | 20.79 |
February | 454.00 | 21.21 | 126.83 | 21.04 | 126.83 | 20.93 |
March | 514.00 | 21.90 | 35.00 | 21.82 | 35.00 | 21.76 |
April | 396.67 | 22.91 | 5.33 | 22.93 | 0.83 | 22.93 |
May | 327.83 | 23.10 | 29.00 | 23.17 | 0.00 | 23.17 |
June | 138.83 | 23.41 | 160.67 | 23.83 | 0.00 | 23.83 |
July | 96.33 | 23.41 | 222.67 | 23.96 | 0.00 | 23.96 |
August | 145.50 | 23.30 | 199.33 | 23.74 | 0.00 | 23.74 |
September | 293.50 | 22.98 | 58.17 | 23.15 | 0.00 | 23.15 |
October | 484.83 | 22.24 | 6.00 | 22.22 | 6.00 | 22.19 |
November | 489.00 | 21.40 | 84.33 | 21.27 | 84.33 | 21.17 |
December | 497.00 | 20.75 | 252.67 | 20.60 | 252.67 | 20.52 |
Annual Sum or Average | 4339.50 | 21.96 | 1386.83 | 22.03 | 712.50 | 21.85 |
Minimum of Months | 96.33 | 20.75 | 5.33 | 20.60 | 0.00 | 20.52 |
Maximum of Months | 514.00 | 23.41 | 252.67 | 23.96 | 252.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.67 | 21.31 | 134.00 | 21.13 | 134.00 | 21.02 |
February | 379.67 | 21.62 | 63.00 | 21.47 | 63.00 | 21.36 |
March | 426.50 | 22.13 | 27.33 | 22.05 | 27.17 | 21.97 |
April | 204.00 | 23.19 | 82.33 | 23.65 | 6.17 | 23.72 |
May | 163.50 | 23.28 | 135.83 | 23.96 | 7.67 | 24.04 |
June | 107.00 | 24.04 | 230.33 | 24.35 | 17.67 | 24.49 |
July | 66.33 | 25.07 | 277.67 | 24.77 | 30.33 | 24.95 |
August | 80.33 | 24.36 | 260.50 | 24.46 | 21.83 | 24.62 |
September | 150.17 | 23.60 | 181.50 | 24.21 | 17.50 | 24.35 |
October | 344.33 | 22.35 | 26.17 | 22.48 | 3.50 | 22.47 |
November | 414.33 | 21.64 | 55.67 | 21.52 | 55.67 | 21.42 |
December | 422.00 | 20.87 | 218.00 | 20.69 | 218.00 | 20.60 |
Annual Sum or Average | 3184.83 | 22.13 | 1692.33 | 22.57 | 602.50 | 22.46 |
Minimum of Months | 66.33 | 20.87 | 26.17 | 20.69 | 3.50 | 20.60 |
Maximum of Months | 426.67 | 25.07 | 277.67 | 24.77 | 218.00 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 418.67 | 21.83 | 123.33 | 21.96 | 76.17 | 21.83 |
February | 348.33 | 22.02 | 90.33 | 22.29 | 33.67 | 22.21 |
March | 438.17 | 22.28 | 28.17 | 22.27 | 17.17 | 22.21 |
April | 226.50 | 23.19 | 152.83 | 23.75 | 9.17 | 23.83 |
May | 221.17 | 23.13 | 153.33 | 23.70 | 7.83 | 23.77 |
June | 145.17 | 23.65 | 251.67 | 24.09 | 12.17 | 24.17 |
July | 102.50 | 24.11 | 301.83 | 24.38 | 23.83 | 24.52 |
August | 106.33 | 24.28 | 328.67 | 24.35 | 27.50 | 24.51 |
September | 148.17 | 23.88 | 262.50 | 24.30 | 28.00 | 24.48 |
October | 312.67 | 22.58 | 120.50 | 23.10 | 6.50 | 23.16 |
November | 404.33 | 22.05 | 72.50 | 22.25 | 33.00 | 22.20 |
December | 458.33 | 21.38 | 172.33 | 21.24 | 154.33 | 21.08 |
Annual Sum or Average | 3330.33 | 22.44 | 2058.00 | 23.00 | 429.33 | 22.96 |
Minimum of Months | 102.50 | 21.38 | 28.17 | 21.24 | 6.50 | 21.08 |
Maximum of Months | 458.33 | 24.28 | 328.67 | 24.38 | 154.33 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.50 | 21.50 | 115.67 | 21.34 | 115.33 | 21.22 |
February | 412.00 | 21.80 | 53.33 | 21.75 | 41.83 | 21.65 |
March | 483.00 | 22.38 | 19.33 | 22.35 | 14.17 | 22.31 |
April | 240.33 | 23.33 | 94.00 | 23.66 | 7.00 | 23.73 |
May | 199.00 | 23.42 | 148.17 | 23.87 | 11.17 | 23.98 |
June | 74.17 | 24.02 | 293.50 | 24.31 | 14.00 | 24.40 |
July | 65.00 | 24.51 | 361.50 | 24.46 | 19.00 | 24.57 |
August | 67.00 | 24.40 | 359.33 | 24.34 | 18.00 | 24.45 |
September | 175.00 | 23.52 | 183.17 | 23.99 | 14.83 | 24.10 |
October | 397.00 | 22.58 | 38.50 | 22.74 | 1.50 | 22.75 |
November | 468.50 | 21.88 | 44.00 | 21.78 | 43.33 | 21.68 |
December | 496.50 | 21.10 | 179.33 | 20.93 | 179.33 | 20.83 |
Annual Sum or Average | 3564.00 | 22.26 | 1889.83 | 22.73 | 479.50 | 22.64 |
Minimum of Months | 65.00 | 21.10 | 19.33 | 20.93 | 1.50 | 20.83 |
Maximum of Months | 496.50 | 24.51 | 361.50 | 24.46 | 179.33 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 364.67 | 20.15 | 364.67 | 20.09 |
February | 454.00 | 20.41 | 283.33 | 20.23 | 283.33 | 20.15 |
March | 514.00 | 21.05 | 218.00 | 20.86 | 218.00 | 20.76 |
April | 426.83 | 22.31 | 47.00 | 22.18 | 43.00 | 22.04 |
May | 396.67 | 22.57 | 37.17 | 22.64 | 6.17 | 22.61 |
June | 190.00 | 22.98 | 141.33 | 23.49 | 0.00 | 23.49 |
July | 162.50 | 23.04 | 206.50 | 23.69 | 0.00 | 23.69 |
August | 207.83 | 22.99 | 179.33 | 23.49 | 0.00 | 23.49 |
September | 350.83 | 22.45 | 47.17 | 22.60 | 2.83 | 22.58 |
October | 502.00 | 21.34 | 115.83 | 21.12 | 115.83 | 20.97 |
November | 489.00 | 20.55 | 266.33 | 20.36 | 266.33 | 20.27 |
December | 497.00 | 20.09 | 411.17 | 20.00 | 411.17 | 19.97 |
Annual Sum or Average | 4692.67 | 21.37 | 2317.83 | 21.28 | 1711.33 | 21.04 |
Minimum of Months | 162.50 | 20.09 | 37.17 | 20.00 | 0.00 | 19.97 |
Maximum of Months | 514.00 | 23.04 | 411.17 | 23.69 | 411.17 | 23.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.51 | 329.83 | 20.33 | 329.83 | 20.25 |
February | 454.00 | 20.83 | 238.33 | 20.58 | 238.33 | 20.45 |
March | 514.00 | 21.37 | 168.17 | 21.15 | 168.17 | 21.01 |
April | 247.50 | 22.67 | 91.33 | 22.99 | 21.50 | 22.97 |
May | 216.33 | 22.82 | 142.17 | 23.46 | 6.50 | 23.51 |
June | 137.00 | 23.60 | 270.17 | 24.12 | 18.17 | 24.24 |
July | 106.50 | 24.19 | 332.50 | 24.46 | 27.33 | 24.61 |
August | 122.17 | 23.83 | 317.33 | 24.22 | 21.50 | 24.35 |
September | 193.67 | 22.92 | 216.00 | 23.74 | 10.67 | 23.81 |
October | 436.50 | 21.62 | 89.33 | 21.47 | 79.17 | 21.32 |
November | 489.00 | 20.79 | 222.83 | 20.56 | 222.83 | 20.44 |
December | 497.00 | 20.21 | 383.17 | 20.08 | 383.17 | 20.03 |
Annual Sum or Average | 3915.67 | 21.48 | 2801.17 | 21.78 | 1527.17 | 21.54 |
Minimum of Months | 106.50 | 20.21 | 89.33 | 20.08 | 6.50 | 20.03 |
Maximum of Months | 514.00 | 24.19 | 383.17 | 24.46 | 383.17 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 452.17 | 21.03 | 254.17 | 20.85 | 236.17 | 20.69 |
February | 385.50 | 21.25 | 191.67 | 21.15 | 157.83 | 20.95 |
March | 482.00 | 21.56 | 150.50 | 21.31 | 150.50 | 21.15 |
April | 258.33 | 22.55 | 151.17 | 23.06 | 29.33 | 23.01 |
May | 278.00 | 22.60 | 138.00 | 23.17 | 10.00 | 23.18 |
June | 185.33 | 23.18 | 230.33 | 23.81 | 12.50 | 23.90 |
July | 146.17 | 23.53 | 276.50 | 24.13 | 23.50 | 24.28 |
August | 143.17 | 23.71 | 299.67 | 24.14 | 26.00 | 24.30 |
September | 201.17 | 23.16 | 239.67 | 23.87 | 26.50 | 24.02 |
October | 379.17 | 21.85 | 131.33 | 22.13 | 49.50 | 22.03 |
November | 441.00 | 21.22 | 185.00 | 21.10 | 163.33 | 20.93 |
December | 480.50 | 20.68 | 313.00 | 20.45 | 309.50 | 20.34 |
Annual Sum or Average | 3832.50 | 21.80 | 2561.00 | 22.14 | 1194.67 | 21.93 |
Minimum of Months | 143.17 | 20.68 | 131.33 | 20.45 | 10.00 | 20.34 |
Maximum of Months | 482.00 | 23.71 | 313.00 | 24.14 | 309.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.33 | 20.76 | 281.67 | 20.54 | 281.67 | 20.43 |
February | 427.33 | 21.05 | 183.50 | 20.81 | 181.33 | 20.67 |
March | 496.00 | 21.58 | 134.17 | 21.38 | 130.83 | 21.24 |
April | 305.33 | 22.78 | 97.67 | 23.04 | 21.50 | 23.03 |
May | 274.83 | 22.91 | 133.33 | 23.40 | 10.67 | 23.48 |
June | 132.00 | 23.53 | 262.17 | 24.08 | 15.17 | 24.18 |
July | 109.00 | 23.78 | 327.17 | 24.28 | 19.17 | 24.40 |
August | 114.67 | 23.77 | 317.17 | 24.16 | 18.33 | 24.28 |
September | 245.00 | 22.94 | 159.17 | 23.52 | 13.50 | 23.64 |
October | 442.50 | 21.79 | 68.33 | 21.82 | 40.33 | 21.70 |
November | 480.67 | 21.06 | 178.00 | 20.84 | 178.00 | 20.71 |
December | 497.00 | 20.46 | 349.33 | 20.31 | 349.33 | 20.25 |
Annual Sum or Average | 4021.67 | 21.70 | 2491.67 | 21.97 | 1259.83 | 21.76 |
Minimum of Months | 109.00 | 20.46 | 68.33 | 20.31 | 10.67 | 20.25 |
Maximum of Months | 497.33 | 23.78 | 349.33 | 24.28 | 349.33 | 24.40 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 4.67 | 27.00 | 454.00 | 27.00 | 4.67 | 27.00 |
March | 3.33 | 27.00 | 514.00 | 27.00 | 3.33 | 27.00 |
April | 73.17 | 27.00 | 485.00 | 27.00 | 73.17 | 27.00 |
May | 8.67 | 27.00 | 508.00 | 27.00 | 8.67 | 27.00 |
June | 62.50 | 27.00 | 496.00 | 27.00 | 62.50 | 27.00 |
July | 157.00 | 27.00 | 497.00 | 27.00 | 157.00 | 27.00 |
August | 303.33 | 27.00 | 514.00 | 27.00 | 303.33 | 27.00 |
September | 16.00 | 27.00 | 485.00 | 27.00 | 16.00 | 27.00 |
October | 10.67 | 27.00 | 502.00 | 27.00 | 10.67 | 27.00 |
November | 3.00 | 27.00 | 489.00 | 27.00 | 3.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 642.33 | 27.00 | 5943.00 | 27.00 | 642.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 303.33 | 27.00 | 514.00 | 27.00 | 303.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 491.17 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 11.83 | 27.00 | 485.00 | 27.00 | 11.83 | 27.00 |
May | 4.17 | 27.00 | 508.00 | 27.00 | 4.17 | 27.00 |
June | 10.33 | 27.00 | 496.00 | 27.00 | 10.33 | 27.00 |
July | 20.83 | 27.00 | 497.00 | 27.00 | 20.83 | 27.00 |
August | 36.33 | 27.00 | 514.00 | 27.00 | 36.33 | 27.00 |
September | 4.33 | 27.00 | 485.00 | 27.00 | 4.33 | 27.00 |
October | 0.83 | 27.00 | 502.00 | 27.00 | 0.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 88.67 | 27.00 | 5924.17 | 27.00 | 88.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 36.33 | 27.00 | 514.00 | 27.00 | 36.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 88.33 | 25.28 | 317.00 | 26.62 | 0.00 | 26.62 |
February | 0.00 | 0.00 | 381.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 484.50 | 27.00 | 0.00 | 27.00 |
April | 15.33 | 27.00 | 485.00 | 27.00 | 15.33 | 27.00 |
May | 6.67 | 27.00 | 508.00 | 27.00 | 6.67 | 27.00 |
June | 25.83 | 27.00 | 496.00 | 27.00 | 25.83 | 27.00 |
July | 45.83 | 27.00 | 497.00 | 27.00 | 45.83 | 27.00 |
August | 51.17 | 27.00 | 514.00 | 27.00 | 51.17 | 27.00 |
September | 6.00 | 27.00 | 485.00 | 27.00 | 6.00 | 27.00 |
October | 0.50 | 27.00 | 501.67 | 27.00 | 0.50 | 27.00 |
November | 0.00 | 0.00 | 448.00 | 27.00 | 0.00 | 27.00 |
December | 5.67 | 27.00 | 390.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 245.33 | 26.38 | 5508.83 | 26.97 | 151.33 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 317.00 | 26.62 | 0.00 | 26.62 |
Maximum of Months | 88.33 | 27.00 | 514.00 | 27.00 | 51.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 354.00 | 27.00 | 502.00 | 27.00 | 354.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5795.00 | 27.00 | 5943.00 | 27.00 | 5795.00 | 27.00 |
Minimum of Months | 354.00 | 27.00 | 454.00 | 27.00 | 354.00 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 27.61972 | 0.80588 | 18.80406 |
February | 454.00000 | 27.00000 | 27.91869 | 0.85833 | 20.62363 |
March | 514.00000 | 27.00000 | 27.80969 | 0.89749 | 22.05749 |
April | 485.00000 | 27.00000 | 28.44934 | 0.97567 | 25.16571 |
May | 508.00000 | 27.00014 | 32.80417 | 0.23935 | 6.29923 |
June | 496.00000 | 27.00044 | 35.84672 | 0.33504 | 7.41247 |
July | 497.00000 | 27.00034 | 36.05233 | 0.39388 | 8.30177 |
August | 514.00000 | 27.00016 | 36.17897 | 0.43041 | 8.92872 |
September | 485.00000 | 27.00043 | 36.10438 | 0.26879 | 6.59668 |
October | 502.00000 | 27.00014 | 32.69058 | 0.91998 | 22.91714 |
November | 489.00000 | 27.00006 | 30.53351 | 0.91720 | 22.82161 |
December | 497.00000 | 27.00000 | 26.72680 | 0.89880 | 22.10607 |
Annual Sum or Average | 5943.00000 | 27.00014 | 31.58778 | 0.65975 | 15.94950 |
Minimum of Months | 454.00000 | 27.00000 | 26.72680 | 0.23935 | 6.29923 |
Maximum of Months | 514.00000 | 27.00044 | 36.17897 | 0.97567 | 25.16571 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99996 | 27.61714 | 0.69315 | 15.24585 |
February | 454.00000 | 27.00001 | 27.90397 | 0.73329 | 16.46240 |
March | 514.00000 | 27.00000 | 27.79858 | 0.76539 | 17.43755 |
April | 485.00000 | 27.00000 | 28.43912 | 0.86022 | 20.73843 |
May | 508.00000 | 27.00013 | 32.80206 | 0.16088 | 5.71082 |
June | 496.00000 | 27.00042 | 35.86412 | 0.24201 | 6.33269 |
July | 497.00000 | 27.00035 | 36.05875 | 0.27313 | 6.66811 |
August | 514.00000 | 27.00018 | 36.17918 | 0.29062 | 6.86001 |
September | 485.00000 | 27.00041 | 36.17353 | 0.19013 | 5.89221 |
October | 502.00000 | 27.00013 | 32.68957 | 0.81727 | 19.17664 |
November | 489.00000 | 27.00006 | 30.51478 | 0.76687 | 17.49920 |
December | 497.00000 | 27.00000 | 26.71101 | 0.70040 | 15.41938 |
Annual Sum or Average | 5943.00000 | 27.00014 | 31.58917 | 0.53912 | 12.74365 |
Minimum of Months | 454.00000 | 26.99996 | 26.71101 | 0.16088 | 5.71082 |
Maximum of Months | 514.00000 | 27.00042 | 36.17918 | 0.86022 | 20.73843 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.63049 | 28.31417 | 0.52915 | 11.81524 |
February | 454.00000 | 27.00001 | 27.91251 | 0.64136 | 13.89473 |
March | 514.00000 | 27.00000 | 27.80326 | 0.68418 | 15.02177 |
April | 485.00000 | 27.00000 | 28.44268 | 0.81829 | 19.38326 |
May | 508.00000 | 27.00014 | 32.81333 | 0.11519 | 5.64504 |
June | 496.00000 | 27.00043 | 35.87638 | 0.22250 | 6.27503 |
July | 497.00000 | 27.00036 | 36.06917 | 0.25835 | 6.63886 |
August | 514.00000 | 27.00019 | 36.18941 | 0.27247 | 6.75982 |
September | 485.00000 | 27.00074 | 36.23160 | 0.14503 | 5.74019 |
October | 502.00000 | 27.00013 | 32.73029 | 0.74234 | 16.79294 |
November | 489.00000 | 27.00006 | 30.53759 | 0.67418 | 14.73958 |
December | 497.00000 | 27.00000 | 26.71663 | 0.60700 | 12.91227 |
Annual Sum or Average | 5943.00000 | 26.96896 | 31.66366 | 0.47401 | 11.26616 |
Minimum of Months | 454.00000 | 26.63049 | 26.71663 | 0.11519 | 5.64504 |
Maximum of Months | 514.00000 | 27.00074 | 36.23160 | 0.81829 | 19.38326 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00002 | 30.07537 | 1.03964 | 27.82682 |
February | 454.00000 | 27.00024 | 30.01264 | 1.20207 | 35.35423 |
March | 514.00000 | 27.00022 | 29.83053 | 1.35017 | 42.87855 |
April | 485.00000 | 27.00068 | 28.46159 | 1.49023 | 50.37164 |
May | 508.00000 | 27.00001 | 30.97751 | 0.48583 | 9.99122 |
June | 496.00000 | 27.00054 | 35.15969 | 0.75078 | 16.91537 |
July | 497.00000 | 27.00318 | 36.43385 | 0.97387 | 25.07451 |
August | 514.00000 | 27.01256 | 35.04282 | 1.15790 | 33.23004 |
September | 485.00000 | 26.99987 | 34.71086 | 0.54271 | 11.25033 |
October | 502.00000 | 27.00008 | 31.38356 | 1.24012 | 37.24351 |
November | 489.00000 | 27.00021 | 30.47406 | 1.36972 | 43.90932 |
December | 497.00000 | 27.00036 | 28.62693 | 1.47658 | 49.63209 |
Annual Sum or Average | 5943.00000 | 27.00154 | 31.78100 | 1.08904 | 31.93488 |
Minimum of Months | 454.00000 | 26.99987 | 28.46159 | 0.48583 | 9.99122 |
Maximum of Months | 514.00000 | 27.01256 | 36.43385 | 1.49023 | 50.37164 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.62910 | 30.46301 | 0.43810 | 10.47825 |
February | 454.00000 | 24.56320 | 29.07978 | 0.40893 | 8.90344 |
March | 514.00000 | 24.49691 | 28.28078 | 0.39636 | 8.70877 |
April | 485.00000 | 24.64236 | 28.08870 | 0.43799 | 9.59894 |
May | 508.00000 | 24.59873 | 34.27363 | -0.3802 | 9.06383 |
June | 496.00000 | 24.58619 | 41.75543 | -0.3196 | 8.17285 |
July | 497.00000 | 24.74237 | 43.26609 | -0.2554 | 7.66124 |
August | 514.00000 | 24.62429 | 44.36943 | -0.2744 | 7.78899 |
September | 485.00000 | 24.66607 | 41.47311 | -0.2961 | 8.28105 |
October | 502.00000 | 24.69497 | 34.66019 | 0.49364 | 10.73947 |
November | 489.00000 | 24.67849 | 31.73209 | 0.46654 | 10.18550 |
December | 497.00000 | 24.62996 | 27.43165 | 0.41763 | 9.20938 |
Annual Sum or Average | 5943.00000 | 24.62931 | 34.62043 | 0.12486 | 9.06422 |
Minimum of Months | 454.00000 | 24.49691 | 27.43165 | -0.3802 | 7.66124 |
Maximum of Months | 514.00000 | 24.74237 | 44.36943 | 0.49364 | 10.73947 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.26367 | 30.33820 | 0.34533 | 7.81346 |
February | 454.00000 | 24.27874 | 30.96847 | 0.36085 | 7.88110 |
March | 514.00000 | 24.30834 | 29.91467 | 0.37438 | 8.20634 |
April | 485.00000 | 24.33956 | 29.15811 | 0.40291 | 8.65065 |
May | 508.00000 | 24.27170 | 35.56398 | -0.4554 | 9.69984 |
June | 496.00000 | 24.27143 | 43.18865 | -0.3798 | 8.37967 |
July | 497.00000 | 24.32061 | 45.02424 | -0.3395 | 7.78982 |
August | 514.00000 | 24.27678 | 45.38240 | -0.3403 | 7.77774 |
September | 485.00000 | 24.26476 | 42.55211 | -0.3981 | 8.66478 |
October | 502.00000 | 24.40331 | 36.77856 | 0.44631 | 9.52209 |
November | 489.00000 | 24.40079 | 33.84162 | 0.42156 | 9.04642 |
December | 497.00000 | 24.37268 | 29.42894 | 0.37648 | 8.26063 |
Annual Sum or Average | 5943.00000 | 24.31439 | 36.05490 | 0.06493 | 8.47701 |
Minimum of Months | 454.00000 | 24.26367 | 29.15811 | -0.4554 | 7.77774 |
Maximum of Months | 514.00000 | 24.40331 | 45.38240 | 0.44631 | 9.69984 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45208 | 34.51746 | 0.13418 | 5.84854 |
February | 454.00000 | 23.58723 | 33.13783 | 0.16580 | 5.91672 |
March | 514.00000 | 23.77726 | 32.40214 | 0.21596 | 6.20464 |
April | 485.00000 | 24.11048 | 31.01113 | 0.31282 | 7.18945 |
May | 508.00000 | 24.08875 | 36.68846 | -0.5475 | 11.59828 |
June | 496.00000 | 24.14634 | 44.16124 | -0.4607 | 9.67606 |
July | 497.00000 | 24.15398 | 46.12463 | -0.4432 | 9.32997 |
August | 514.00000 | 24.14111 | 46.57247 | -0.4388 | 9.21818 |
September | 485.00000 | 24.09594 | 43.60252 | -0.4872 | 10.19463 |
October | 502.00000 | 23.99055 | 39.10253 | 0.32297 | 7.39030 |
November | 489.00000 | 23.72052 | 36.58500 | 0.22324 | 6.38291 |
December | 497.00000 | 23.24461 | 32.72422 | 0.06609 | 5.60724 |
Annual Sum or Average | 5943.00000 | 23.87768 | 38.09558 | -0.0806 | 7.89618 |
Minimum of Months | 454.00000 | 23.24461 | 31.01113 | -0.5475 | 5.60724 |
Maximum of Months | 514.00000 | 24.15398 | 46.57247 | 0.32297 | 11.59828 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.55246 | 36.49855 | -0.3531 | 9.64988 |
February | 454.00000 | 21.85239 | 36.88465 | -0.2691 | 8.26157 |
March | 514.00000 | 22.43149 | 35.63276 | -0.1272 | 6.57242 |
April | 485.00000 | 23.55250 | 32.60198 | 0.16637 | 6.29075 |
May | 508.00000 | 23.67463 | 38.11504 | -0.7029 | 16.40151 |
June | 496.00000 | 23.96793 | 44.87073 | -0.5259 | 11.24977 |
July | 497.00000 | 23.99869 | 46.74057 | -0.4967 | 10.65897 |
August | 514.00000 | 23.99902 | 47.20177 | -0.4932 | 10.40312 |
September | 485.00000 | 23.69329 | 45.25545 | -0.6397 | 14.43252 |
October | 502.00000 | 22.82666 | 42.44386 | 0.02341 | 6.10340 |
November | 489.00000 | 22.06711 | 40.71851 | -0.1924 | 7.23447 |
December | 497.00000 | 21.38243 | 35.97408 | -0.4021 | 10.15046 |
Annual Sum or Average | 5943.00000 | 22.92425 | 40.27450 | -0.3357 | 9.79756 |
Minimum of Months | 454.00000 | 21.38243 | 32.60198 | -0.7029 | 6.10340 |
Maximum of Months | 514.00000 | 23.99902 | 47.20177 | 0.16637 | 16.40151 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60389 | 32.65406 | -0.0837 | 6.17478 |
February | 454.00000 | 22.87069 | 33.17915 | -0.0120 | 5.77592 |
March | 514.00000 | 23.41105 | 31.32574 | 0.11580 | 5.88820 |
April | 485.00000 | 23.94071 | 29.39010 | 0.27012 | 6.88550 |
May | 508.00000 | 23.93752 | 35.52704 | -0.6003 | 13.19354 |
June | 496.00000 | 24.16629 | 42.59862 | -0.4256 | 9.25878 |
July | 497.00000 | 24.27854 | 44.32531 | -0.3609 | 8.19792 |
August | 514.00000 | 24.18024 | 44.95817 | -0.3988 | 8.70126 |
September | 485.00000 | 23.91437 | 42.75803 | -0.5600 | 12.23833 |
October | 502.00000 | 23.58695 | 38.13407 | 0.20855 | 6.41358 |
November | 489.00000 | 23.24818 | 35.87755 | 0.09882 | 5.85500 |
December | 497.00000 | 22.80011 | 31.76437 | -0.0424 | 5.63986 |
Annual Sum or Average | 5943.00000 | 23.58336 | 36.90696 | -0.1509 | 7.86653 |
Minimum of Months | 454.00000 | 22.60389 | 29.39010 | -0.6003 | 5.63986 |
Maximum of Months | 514.00000 | 24.27854 | 44.95817 | 0.27012 | 13.19354 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.70131 | 32.44852 | -0.0575 | 6.40592 |
February | 454.00000 | 22.91231 | 32.97969 | 0.00524 | 6.16867 |
March | 514.00000 | 23.24589 | 31.60874 | 0.08264 | 6.04023 |
April | 485.00000 | 24.02224 | 28.80841 | 0.34841 | 8.50104 |
May | 508.00000 | 24.13282 | 34.75234 | -0.4519 | 11.28056 |
June | 496.00000 | 24.22237 | 42.21830 | -0.3345 | 8.96228 |
July | 497.00000 | 24.40711 | 43.85343 | -0.2435 | 8.24137 |
August | 514.00000 | 24.25942 | 44.56509 | -0.2903 | 8.48376 |
September | 485.00000 | 24.19320 | 41.59718 | -0.3772 | 10.23381 |
October | 502.00000 | 23.57761 | 37.95841 | 0.22647 | 6.95750 |
November | 489.00000 | 23.07104 | 36.26566 | 0.06105 | 5.96106 |
December | 497.00000 | 22.43957 | 32.28998 | -0.1229 | 6.27617 |
Annual Sum or Average | 5943.00000 | 23.60335 | 36.64627 | -0.0978 | 7.80191 |
Minimum of Months | 454.00000 | 22.43957 | 28.80841 | -0.4519 | 5.96106 |
Maximum of Months | 514.00000 | 24.40711 | 44.56509 | 0.34841 | 11.28056 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.79333 | 31.86922 | -0.0163 | 7.45402 |
February | 454.00000 | 23.08929 | 32.05815 | 0.07410 | 7.36357 |
March | 514.00000 | 23.20668 | 31.37911 | 0.07971 | 6.23683 |
April | 485.00000 | 24.05227 | 28.70430 | 0.36740 | 9.04822 |
May | 508.00000 | 23.97620 | 35.08321 | -0.5279 | 13.03594 |
June | 496.00000 | 24.17230 | 42.39731 | -0.3808 | 9.37364 |
July | 497.00000 | 24.33822 | 43.98252 | -0.2809 | 8.35535 |
August | 514.00000 | 24.29586 | 44.27958 | -0.2561 | 8.21567 |
September | 485.00000 | 24.21681 | 41.39100 | -0.3187 | 10.00016 |
October | 502.00000 | 23.66115 | 37.44130 | 0.27788 | 8.09717 |
November | 489.00000 | 23.21860 | 35.58200 | 0.11449 | 6.98335 |
December | 497.00000 | 22.59014 | 31.71702 | -0.0798 | 7.18109 |
Annual Sum or Average | 5943.00000 | 23.63725 | 36.36323 | -0.0812 | 8.45109 |
Minimum of Months | 454.00000 | 22.59014 | 28.70430 | -0.5279 | 6.23683 |
Maximum of Months | 514.00000 | 24.33822 | 44.27958 | 0.36740 | 13.03594 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50164 | 30.60688 | 0.13731 | 6.24414 |
February | 454.00000 | 24.01432 | 30.06875 | 0.29094 | 7.34903 |
March | 514.00000 | 24.27586 | 28.56203 | 0.37077 | 8.27930 |
April | 485.00000 | 24.56677 | 27.47054 | 0.54577 | 12.21630 |
May | 508.00000 | 24.33367 | 34.09283 | -0.3468 | 9.18157 |
June | 496.00000 | 24.47556 | 41.31041 | -0.1606 | 7.35007 |
July | 497.00000 | 24.66223 | 42.93905 | -0.0437 | 7.31837 |
August | 514.00000 | 24.54977 | 43.43281 | -0.0666 | 7.17796 |
September | 485.00000 | 24.35980 | 41.03357 | -0.2961 | 8.49420 |
October | 502.00000 | 24.34162 | 35.59020 | 0.43551 | 9.48738 |
November | 489.00000 | 24.29899 | 32.63947 | 0.38305 | 8.51148 |
December | 497.00000 | 24.25784 | 28.09242 | 0.32712 | 7.51619 |
Annual Sum or Average | 5943.00000 | 24.30464 | 34.69367 | 0.12946 | 8.25645 |
Minimum of Months | 454.00000 | 23.50164 | 27.47054 | -0.3468 | 6.24414 |
Maximum of Months | 514.00000 | 24.66223 | 43.43281 | 0.54577 | 12.21630 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04298 | 35.19208 | -0.4841 | 10.96412 |
February | 454.00000 | 21.21232 | 35.85513 | -0.4249 | 9.69361 |
March | 514.00000 | 21.89883 | 34.63991 | -0.2532 | 7.32438 |
April | 485.00000 | 23.12227 | 31.96787 | 0.05663 | 6.17413 |
May | 508.00000 | 23.42738 | 37.16717 | -0.7910 | 19.57445 |
June | 496.00000 | 23.89825 | 43.67730 | -0.5477 | 12.03205 |
July | 497.00000 | 23.97613 | 45.43625 | -0.5020 | 10.93597 |
August | 514.00000 | 23.82448 | 46.42858 | -0.5609 | 12.27530 |
September | 485.00000 | 23.37812 | 44.46139 | -0.7614 | 18.57281 |
October | 502.00000 | 22.29823 | 41.99343 | -0.1011 | 6.29028 |
November | 489.00000 | 21.39872 | 39.56066 | -0.3536 | 8.57975 |
December | 497.00000 | 20.74553 | 34.57284 | -0.5697 | 12.59510 |
Annual Sum or Average | 5943.00000 | 22.52860 | 39.27600 | -0.4419 | 11.26388 |
Minimum of Months | 454.00000 | 20.74553 | 31.96787 | -0.7910 | 6.17413 |
Maximum of Months | 514.00000 | 23.97613 | 46.42858 | 0.05663 | 19.57445 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.31584 | 34.10222 | -0.4184 | 9.95574 |
February | 385.00000 | 21.65450 | 34.30703 | -0.3190 | 8.56920 |
March | 433.00000 | 22.16493 | 33.58801 | -0.1901 | 7.17690 |
April | 410.00000 | 23.73060 | 29.71697 | 0.25513 | 8.07104 |
May | 430.00000 | 23.92832 | 35.09317 | -0.5471 | 14.37655 |
June | 418.00000 | 24.15672 | 42.24107 | -0.3835 | 10.49269 |
July | 422.00000 | 24.41417 | 43.66687 | -0.2748 | 9.44207 |
August | 433.00000 | 24.22187 | 44.50626 | -0.3387 | 9.86270 |
September | 410.00000 | 24.03338 | 41.81492 | -0.4626 | 12.86152 |
October | 427.00000 | 22.70468 | 40.13630 | 0.00440 | 6.70366 |
November | 417.00000 | 21.65510 | 38.43027 | -0.2946 | 8.00622 |
December | 422.00000 | 20.87097 | 33.79488 | -0.5406 | 12.15420 |
Annual Sum or Average | 5034.00000 | 22.91014 | 37.64642 | -0.2932 | 9.81194 |
Minimum of Months | 385.00000 | 20.87097 | 29.71697 | -0.5471 | 6.70366 |
Maximum of Months | 433.00000 | 24.41417 | 44.50626 | 0.25513 | 14.37655 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26671 | 32.64826 | -0.1556 | 8.73984 |
February | 454.00000 | 22.56907 | 32.77091 | -0.0576 | 8.39466 |
March | 514.00000 | 22.54402 | 33.04508 | -0.0833 | 6.96895 |
April | 485.00000 | 23.75279 | 29.79651 | 0.28831 | 8.82899 |
May | 508.00000 | 23.74313 | 35.84432 | -0.6102 | 16.04020 |
June | 496.00000 | 23.99356 | 43.05811 | -0.4571 | 11.33657 |
July | 497.00000 | 24.16461 | 44.57410 | -0.3612 | 10.13592 |
August | 514.00000 | 24.14311 | 44.90058 | -0.3284 | 9.76440 |
September | 485.00000 | 24.07409 | 41.73732 | -0.3627 | 11.72824 |
October | 502.00000 | 23.20242 | 39.15298 | 0.17288 | 8.14018 |
November | 489.00000 | 22.45575 | 37.15426 | -0.0749 | 7.80339 |
December | 497.00000 | 21.61268 | 32.87037 | -0.3400 | 10.13401 |
Annual Sum or Average | 5943.00000 | 23.21379 | 37.33876 | -0.1997 | 9.84646 |
Minimum of Months | 454.00000 | 21.61268 | 29.79651 | -0.6102 | 6.96895 |
Maximum of Months | 514.00000 | 24.16461 | 44.90058 | 0.28831 | 16.04020 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57801 | 34.10939 | -0.3434 | 8.98093 |
February | 454.00000 | 22.01750 | 34.00253 | -0.2152 | 7.86125 |
March | 514.00000 | 22.47638 | 33.31805 | -0.1067 | 6.59088 |
April | 485.00000 | 23.75315 | 30.19647 | 0.26348 | 7.96283 |
May | 508.00000 | 23.86127 | 35.71274 | -0.5570 | 14.43153 |
June | 496.00000 | 24.16671 | 42.54081 | -0.3496 | 9.61012 |
July | 497.00000 | 24.28018 | 44.24407 | -0.2822 | 8.95518 |
August | 514.00000 | 24.18421 | 44.90717 | -0.3310 | 9.15128 |
September | 485.00000 | 23.89936 | 42.58739 | -0.5075 | 13.08857 |
October | 502.00000 | 22.90671 | 40.22090 | 0.06034 | 6.60928 |
November | 489.00000 | 21.97234 | 38.26196 | -0.2098 | 7.30724 |
December | 497.00000 | 21.09924 | 33.92123 | -0.4720 | 10.53852 |
Annual Sum or Average | 5943.00000 | 23.02348 | 37.86967 | -0.2552 | 9.26403 |
Minimum of Months | 454.00000 | 21.09924 | 30.19647 | -0.5570 | 6.59088 |
Maximum of Months | 514.00000 | 24.28018 | 44.90717 | 0.26348 | 14.43153 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28771 | 36.69073 | -0.7239 | 18.30545 |
February | 454.00000 | 20.41105 | 37.38302 | -0.6689 | 16.49778 |
March | 514.00000 | 21.04749 | 36.15802 | -0.4945 | 11.42387 |
April | 485.00000 | 22.52892 | 33.15699 | -0.0972 | 7.29807 |
May | 508.00000 | 22.88173 | 38.49771 | -0.9826 | 27.88648 |
June | 496.00000 | 23.65487 | 44.42824 | -0.6340 | 15.11323 |
July | 497.00000 | 23.76686 | 46.04735 | -0.5740 | 13.48519 |
August | 514.00000 | 23.60892 | 47.12609 | -0.6384 | 15.07896 |
September | 485.00000 | 22.87175 | 45.94069 | -0.9419 | 26.26181 |
October | 502.00000 | 21.33860 | 44.13787 | -0.3579 | 9.24129 |
November | 489.00000 | 20.55420 | 41.33747 | -0.6053 | 14.48882 |
December | 497.00000 | 20.09198 | 35.88049 | -0.7867 | 20.44485 |
Annual Sum or Average | 5943.00000 | 21.93191 | 40.59291 | -0.6258 | 16.29282 |
Minimum of Months | 454.00000 | 20.09198 | 33.15699 | -0.9826 | 7.29807 |
Maximum of Months | 514.00000 | 23.76686 | 47.12609 | -0.0972 | 27.88648 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51291 | 36.21926 | -0.6569 | 16.25088 |
February | 454.00000 | 20.83201 | 36.58787 | -0.5552 | 13.70555 |
March | 514.00000 | 21.37386 | 35.59971 | -0.4097 | 10.27854 |
April | 485.00000 | 23.36946 | 30.58036 | 0.16633 | 8.10231 |
May | 508.00000 | 23.61168 | 36.27612 | -0.6543 | 17.81903 |
June | 496.00000 | 23.98674 | 43.02592 | -0.4304 | 11.70551 |
July | 497.00000 | 24.24111 | 44.36420 | -0.3170 | 10.12555 |
August | 514.00000 | 24.06869 | 45.21463 | -0.3730 | 10.64748 |
September | 485.00000 | 23.73024 | 42.87941 | -0.5641 | 15.71316 |
October | 502.00000 | 21.94235 | 42.49944 | -0.1997 | 8.43073 |
November | 489.00000 | 20.78572 | 40.88742 | -0.5416 | 12.93498 |
December | 497.00000 | 20.21070 | 35.63604 | -0.7492 | 19.17134 |
Annual Sum or Average | 5943.00000 | 22.39947 | 39.17507 | -0.4405 | 12.89967 |
Minimum of Months | 454.00000 | 20.21070 | 30.58036 | -0.7492 | 8.10231 |
Maximum of Months | 514.00000 | 24.24111 | 45.21463 | 0.16633 | 19.17134 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34625 | 34.39385 | -0.4257 | 12.88843 |
February | 454.00000 | 21.70144 | 34.46878 | -0.3110 | 11.50628 |
March | 514.00000 | 21.71523 | 34.75565 | -0.3174 | 9.75002 |
April | 485.00000 | 23.31843 | 30.65975 | 0.16810 | 9.00976 |
May | 508.00000 | 23.33568 | 36.91743 | -0.7627 | 22.17235 |
June | 496.00000 | 23.76918 | 43.71702 | -0.5371 | 14.21462 |
July | 497.00000 | 23.97829 | 45.11139 | -0.4259 | 12.42287 |
August | 514.00000 | 23.98007 | 45.40756 | -0.3894 | 11.73230 |
September | 485.00000 | 23.74770 | 42.66447 | -0.4910 | 15.98665 |
October | 502.00000 | 22.40286 | 40.96188 | -0.0487 | 8.89570 |
November | 489.00000 | 21.52864 | 39.17870 | -0.3393 | 11.02708 |
December | 497.00000 | 20.78961 | 34.44664 | -0.5893 | 15.76957 |
Annual Sum or Average | 5943.00000 | 22.64010 | 38.59666 | -0.3741 | 12.96358 |
Minimum of Months | 454.00000 | 20.78961 | 30.65975 | -0.7627 | 8.89570 |
Maximum of Months | 514.00000 | 23.98007 | 45.40756 | 0.16810 | 22.17235 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78650 | 35.62636 | -0.5765 | 14.38130 |
February | 454.00000 | 21.22723 | 35.50193 | -0.4401 | 11.88477 |
March | 514.00000 | 21.66460 | 34.82981 | -0.3265 | 9.11732 |
April | 485.00000 | 23.27114 | 31.17708 | 0.13810 | 8.18353 |
May | 508.00000 | 23.46794 | 36.75154 | -0.7008 | 20.09438 |
June | 496.00000 | 23.99032 | 43.10201 | -0.4151 | 11.70839 |
July | 497.00000 | 24.12749 | 44.69354 | -0.3368 | 10.66923 |
August | 514.00000 | 24.03649 | 45.40258 | -0.3875 | 10.81925 |
September | 485.00000 | 23.52380 | 43.68806 | -0.6462 | 18.20289 |
October | 502.00000 | 22.07603 | 42.07311 | -0.1589 | 7.84716 |
November | 489.00000 | 21.10887 | 40.05470 | -0.4493 | 11.10660 |
December | 497.00000 | 20.45789 | 35.11551 | -0.6722 | 16.33819 |
Annual Sum or Average | 5943.00000 | 22.48732 | 39.03286 | -0.4148 | 12.53042 |
Minimum of Months | 454.00000 | 20.45789 | 31.17708 | -0.7008 | 7.84716 |
Maximum of Months | 514.00000 | 24.12749 | 45.40258 | 0.13810 | 20.09438 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.614024E+09 | 16330.20 | 20-JAN-12:00 | 80.81 | 0.510952E+10 | 0.00 | 0.572355E+10 | 0.90 | 8.42 | 02-JAN-10:40 | 0.00 | 0.00 |
February | 0.121278E+10 | 23345.82 | 09-FEB-15:20 | 115.11 | 0.100999E+11 | 0.00 | 0.113127E+11 | 1.43 | 8.41 | 17-FEB-13:55 | 0.00 | 0.00 |
March | 0.134699E+10 | 24243.76 | 23-MAR-16:00 | 116.57 | 0.112050E+11 | 0.00 | 0.125520E+11 | 1.30 | 8.41 | 27-MAR-08:40 | 0.00 | 0.00 |
April | 0.805629E+10 | 121363.53 | 28-APR-15:20 | 117.77 | 0.670007E+11 | 0.00 | 0.750570E+11 | 1.37 | 8.68 | 30-APR-18:42 | 0.00 | 0.00 |
May | 0.854520E+10 | 141869.42 | 22-MAY-13:40 | 124.65 | 0.694518E+11 | 0.00 | 0.779970E+11 | 1.39 | 8.68 | 31-MAY-13:50 | 0.00 | 0.00 |
June | 0.219465E+11 | 146185.35 | 13-JUN-18:00 | 225.20 | 0.173621E+12 | 0.00 | 0.195567E+12 | 2.57 | 8.68 | 20-JUN-10:20 | 0.00 | 0.00 |
July | 0.362240E+11 | 147678.46 | 22-JUL-12:00 | 373.98 | 0.290497E+12 | 0.00 | 0.326721E+12 | 4.15 | 8.68 | 18-JUL-14:50 | 0.00 | 0.00 |
August | 0.471730E+11 | 146148.27 | 14-AUG-12:00 | 411.52 | 0.380257E+12 | 0.00 | 0.427430E+12 | 4.57 | 8.68 | 08-AUG-12:40 | 0.00 | 0.00 |
September | 0.256412E+11 | 146507.07 | 13-SEP-16:30 | 270.73 | 0.205288E+12 | 0.00 | 0.230929E+12 | 3.10 | 8.68 | 11-SEP-18:20 | 0.00 | 0.00 |
October | 0.694590E+10 | 76016.07 | 05-OCT-14:05 | 126.31 | 0.579833E+11 | 0.00 | 0.649292E+11 | 1.41 | 8.68 | 05-OCT-11:50 | 0.00 | 0.00 |
November | 0.122727E+10 | 27108.24 | 03-NOV-14:10 | 92.72 | 0.101868E+11 | 0.00 | 0.114141E+11 | 1.07 | 8.42 | 28-NOV-10:40 | 0.00 | 0.00 |
December | 0.935412E+09 | 7198.26 | 21-DEC-14:00 | 156.64 | 0.778475E+10 | 0.00 | 0.872016E+10 | 1.75 | 8.41 | 26-DEC-14:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.159869E+12 | 2212.00 | 0.128848E+13 | 0.00 | 0.144835E+13 | 2.09 | 0.00 | 0.00 | ||||
Minimum of Months | 0.614024E+09 | 7198.26 | 80.81 | 0.510952E+10 | 0.00 | 0.572355E+10 | 0.90 | 8.41 | 0.00 | 0.00 | ||
Maximum of Months | 0.471730E+11 | 147678.46 | 411.52 | 0.380257E+12 | 0.00 | 0.427430E+12 | 4.57 | 8.68 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.526637E+09 | 105440.51 | 22-MAY-14:05 | 2.17 | 0.418960E+10 | 0.00 | 0.471624E+10 | 0.02 | 8.30 | 22-MAY-16:00 | 0.00 | 0.00 |
June | 0.388634E+10 | 99501.85 | 13-JUN-16:00 | 16.58 | 0.305953E+11 | 0.00 | 0.344816E+11 | 0.18 | 8.55 | 12-JUN-17:20 | 0.00 | 0.00 |
July | 0.423039E+10 | 89214.33 | 21-JUL-15:30 | 18.00 | 0.335759E+11 | 0.00 | 0.378063E+11 | 0.19 | 8.52 | 10-JUL-15:50 | 0.00 | 0.00 |
August | 0.281630E+10 | 118032.05 | 28-AUG-14:05 | 11.92 | 0.222770E+11 | 0.00 | 0.250933E+11 | 0.13 | 8.65 | 14-AUG-17:20 | 0.00 | 0.00 |
September | 0.238945E+10 | 77175.94 | 22-SEP-14:05 | 11.33 | 0.193733E+11 | 0.00 | 0.217628E+11 | 0.13 | 8.64 | 27-SEP-14:30 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138491E+11 | 60.00 | 0.110011E+12 | 0.00 | 0.123860E+12 | 0.05 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.423039E+10 | 118032.05 | 18.00 | 0.335759E+11 | 0.00 | 0.378063E+11 | 0.19 | 8.65 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.900536E+09 | 744.00 | 963.60 | 29-JAN-06:00 | 35417.73 | 27-JAN-20:30 | 18.69 | 18.33 | 15.65 |
February | 0.192464E+10 | 672.00 | 2044.52 | 04-FEB-16:10 | 90615.02 | 04-FEB-16:20 | 19.25 | 18.33 | 15.65 |
March | 0.374055E+10 | 744.00 | 3039.13 | 25-MAR-13:00 | 126143.97 | 09-MAR-07:15 | 19.81 | 18.33 | 15.66 |
April | 0.130834E+11 | 720.00 | 43776.24 | 22-APR-12:20 | 566054.02 | 30-APR-19:02 | 20.91 | 18.51 | 15.66 |
May | 0.676303E+10 | 744.00 | 43776.24 | 21-MAY-14:40 | 97296.55 | 22-MAY-15:00 | 18.96 | 18.39 | 15.65 |
June | 0.180952E+11 | 720.00 | 43776.24 | 09-JUN-11:00 | 367219.13 | 13-JUN-17:00 | 19.97 | 18.72 | 15.66 |
July | 0.358832E+11 | 744.00 | 43776.24 | 05-JUL-14:30 | 536203.41 | 22-JUL-19:02 | 21.52 | 19.18 | 15.66 |
August | 0.616749E+11 | 744.00 | 43776.24 | 01-AUG-07:40 | 673742.43 | 14-AUG-17:20 | 24.08 | 19.55 | 15.66 |
September | 0.177192E+11 | 720.00 | 43776.24 | 09-SEP-12:40 | 61755.99 | 13-SEP-16:00 | 19.16 | 18.59 | 15.66 |
October | 0.397956E+10 | 744.00 | 43776.24 | 07-OCT-14:30 | 83957.73 | 31-OCT-23:30 | 19.31 | 18.33 | 15.66 |
November | 0.371775E+10 | 720.00 | 4754.97 | 24-NOV-12:00 | 92264.76 | 03-NOV-16:00 | 19.75 | 18.33 | 15.66 |
December | 0.403107E+10 | 744.00 | 3291.63 | 23-DEC-11:00 | 148658.68 | 01-DEC-20:00 | 20.21 | 18.33 | 15.65 |
Annual Sum or Average | 0.171513E+12 | 8760.00 | 20.14 | 18.58 | 15.66 | ||||
Minimum of Months | 0.900536E+09 | 672.00 | 963.60 | 35417.73 | 18.69 | 18.33 | 15.65 | ||
Maximum of Months | 0.616749E+11 | 744.00 | 43776.24 | 673742.43 | 24.08 | 19.55 | 15.66 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 181207.11 | 09-JAN-05:53 | 20.95 | 20.94 | 1.04 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 225135.68 | 09-FEB-15:20 | 20.95 | 20.92 | 1.89 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 235034.67 | 23-MAR-16:00 | 21.03 | 21.00 | 1.85 |
April | 56858510.61 | 42.62 | 2134.97 | 28-APR-15:30 | 935821.69 | 28-APR-15:20 | 21.60 | 21.44 | 5.58 |
May | 0.215604E+09 | 56.48 | 13451.39 | 22-MAY-13:00 | 1028081.52 | 22-MAY-13:40 | 21.61 | 21.45 | 5.49 |
June | 0.136546E+10 | 131.69 | 13451.39 | 12-JUN-12:10 | 1018968.98 | 20-JUN-15:30 | 21.63 | 21.21 | 11.98 |
July | 0.144377E+10 | 247.53 | 13451.39 | 10-JUL-08:70 | 993294.07 | 12-JUL-15:50 | 21.74 | 21.08 | 19.65 |
August | 0.158459E+10 | 323.63 | 13451.39 | 14-AUG-09:30 | 1040746.44 | 28-AUG-13:20 | 21.93 | 21.07 | 23.60 |
September | 0.772914E+09 | 173.56 | 13451.39 | 11-SEP-12:50 | 1030677.57 | 13-SEP-16:30 | 21.55 | 21.06 | 14.51 |
October | 29521285.52 | 54.17 | 505.35 | 05-OCT-15:40 | 676789.51 | 05-OCT-14:10 | 21.26 | 21.12 | 5.06 |
November | 1329006.17 | 7.50 | 95.92 | 10-NOV-15:10 | 261325.20 | 03-NOV-14:40 | 20.99 | 20.96 | 1.71 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 180697.68 | 15-DEC-06:03 | 20.94 | 20.91 | 1.54 |
Annual Sum or Average | 0.547004E+10 | 1037.18 | 21.35 | 21.10 | 7.87 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 180697.68 | 20.94 | 20.91 | 1.04 | ||
Maximum of Months | 0.158459E+10 | 323.63 | 13451.39 | 1040746.44 | 21.93 | 21.45 | 23.60 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.95 | 20.95 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.95 | 20.95 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.03 | 21.03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.60 | 21.60 | 0.00 |
May | 59365028.56 | 2.00 | 13451.39 | 22-MAY-14:00 | 864437.56 | 22-MAY-14:00 | 21.61 | 21.60 | 0.13 |
June | 0.514878E+09 | 10.92 | 13451.39 | 12-JUN-12:40 | 832215.64 | 21-JUN-13:40 | 21.63 | 21.57 | 0.71 |
July | 0.380657E+09 | 13.50 | 13451.39 | 10-JUL-09:30 | 857152.79 | 21-JUL-10:30 | 21.74 | 21.67 | 0.85 |
August | 0.216481E+09 | 9.42 | 13451.39 | 14-AUG-10:00 | 919974.77 | 14-AUG-17:30 | 21.93 | 21.88 | 0.59 |
September | 0.129236E+09 | 4.83 | 13451.39 | 11-SEP-13:50 | 906941.25 | 27-SEP-14:40 | 21.55 | 21.52 | 0.31 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.26 | 21.26 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.99 | 20.99 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.94 | 20.94 | 0.00 |
Annual Sum or Average | 0.130062E+10 | 40.67 | 21.35 | 21.33 | 0.22 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 20.94 | 0.00 | ||
Maximum of Months | 0.514878E+09 | 13.50 | 13451.39 | 919974.77 | 21.93 | 21.88 | 0.85 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.232345E+12 | 0.00 | 421.07 | 906223.60 | 11-JAN-06:01 | 0.00 | 33.44 | 60.91 | 0.47 | 0.00 | 0.05 | 0.56 | 11-JAN-06:01 |
February | 0.161364E+12 | 0.00 | 371.10 | 922148.36 | 13-FEB-06:01 | 0.00 | 32.59 | 60.38 | 0.33 | 0.00 | 0.04 | 0.57 | 13-FEB-06:01 |
March | 0.130887E+12 | 0.00 | 411.93 | 800484.55 | 06-MAR-06:02 | 0.00 | 30.06 | 59.00 | 0.23 | 0.00 | 0.03 | 0.50 | 06-MAR-06:02 |
April | 0.272627E+11 | 0.00 | 166.00 | 507057.22 | 12-APR-13:05 | 0.00 | 27.55 | 39.97 | 0.05 | 0.00 | 0.01 | 0.31 | 12-APR-13:05 |
May | 0.157418E+11 | 0.00 | 147.94 | 457017.53 | 01-MAY-09:05 | 0.00 | 26.11 | 37.04 | 0.03 | 0.00 | 0.00 | 0.28 | 01-MAY-09:05 |
June | 0.145434E+10 | 0.00 | 25.36 | 227672.22 | 28-JUN-09:10 | 0.00 | 26.56 | 28.56 | 0.00 | 0.00 | 0.00 | 0.14 | 28-JUN-09:10 |
July | 0.215682E+09 | 0.00 | 5.97 | 45375.10 | 25-JUL-09:05 | 0.00 | 25.88 | 26.33 | 0.00 | 0.00 | 0.00 | 0.03 | 25-JUL-09:05 |
August | 49366845.73 | 0.00 | 3.33 | 37717.61 | 24-AUG-06:05 | 0.00 | 24.92 | 25.17 | 0.00 | 0.00 | 0.00 | 0.02 | 24-AUG-06:05 |
September | 0.315164E+10 | 0.00 | 49.92 | 268434.64 | 08-SEP-09:30 | 0.00 | 26.34 | 30.23 | 0.01 | 0.00 | 0.00 | 0.17 | 08-SEP-09:30 |
October | 0.361729E+11 | 0.00 | 252.28 | 411402.64 | 23-OCT-05:03 | 0.00 | 27.04 | 45.66 | 0.06 | 0.00 | 0.01 | 0.26 | 23-OCT-05:03 |
November | 0.118610E+12 | 0.00 | 368.10 | 1054078.47 | 27-NOV-05:11 | 0.00 | 29.13 | 56.23 | 0.22 | 0.00 | 0.03 | 0.65 | 27-NOV-05:11 |
December | 0.245842E+12 | 0.00 | 424.31 | 1002835.51 | 26-DEC-05:11 | 0.00 | 33.03 | 61.08 | 0.47 | 0.00 | 0.06 | 0.62 | 26-DEC-05:11 |
Annual Sum or Average | 0.973097E+12 | 0.00 | 2647.32 | 0.00 | 28.53 | 44.14 | 0.16 | 0.00 | 0.02 | ||||
Minimum of Months | 49366845.73 | 0.00 | 3.33 | 37717.61 | 0.00 | 24.92 | 25.17 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.245842E+12 | 0.00 | 424.31 | 1054078.47 | 0.00 | 33.44 | 61.08 | 0.47 | 0.00 | 0.06 | 0.65 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.69 | 18.69 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.25 | 19.25 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.81 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.91 | 20.91 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 18.96 | 18.96 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 19.97 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 21.52 | 21.52 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 24.08 | 24.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 19.16 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.31 | 19.31 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.75 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.21 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 18.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 24.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.301884E+10 | 0.00 | 67.64 | 0.301884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34543.99 | 17-JAN-12:00 | 34543.99 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.458587E+10 | 0.00 | 101.11 | 0.458587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34358.11 | 09-FEB-15:00 | 34358.11 | 09-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.313213E+10 | 0.00 | 81.03 | 0.313213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28746.06 | 28-MAR-10:00 | 28746.06 | 28-MAR-10:00 | 0.00 | 0.00 | 0.00 |
April | 0.514489E+10 | 0.00 | 69.12 | 0.513900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83646.72 | 30-APR-14:21 | 83646.72 | 30-APR-14:21 | 0.00 | 0.00 | 0.00 |
May | 0.573107E+10 | 0.00 | 71.71 | 0.573107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99069.99 | 22-MAY-15:00 | 99069.99 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.181865E+11 | 0.00 | 173.37 | 0.178722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133383.33 | 25-JUN-17:41 | 113403.33 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.305751E+11 | 0.00 | 309.17 | 0.304746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116779.81 | 21-JUL-15:10 | 116779.81 | 21-JUL-15:10 | 0.00 | 0.00 | 0.00 |
August | 0.406616E+11 | 0.00 | 377.55 | 0.404734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124232.15 | 14-AUG-15:20 | 124232.15 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.191812E+11 | 0.00 | 213.88 | 0.190779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87498.33 | 13-SEP-14:30 | 87498.33 | 13-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.333181E+10 | 0.00 | 59.70 | 0.333181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53319.09 | 06-OCT-09:40 | 53319.09 | 06-OCT-09:40 | 0.00 | 0.00 | 0.00 |
November | 0.403626E+10 | 0.00 | 77.50 | 0.403626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39994.56 | 03-NOV-14:30 | 39994.56 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.627096E+10 | 0.00 | 143.83 | 0.627096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39087.53 | 18-DEC-14:10 | 39087.53 | 18-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143856E+12 | 0.00 | 1745.62 | 0.143144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.301884E+10 | 0.00 | 59.70 | 0.301884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28746.06 | 28746.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.406616E+11 | 0.00 | 377.55 | 0.404734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133383.33 | 124232.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.137888E+10 | 0.00 | 16.03 | 0.137888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114865.47 | 20-JAN-12:00 | 114865.47 | 20-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.445992E+10 | 0.00 | 34.50 | 0.445992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161400.50 | 09-FEB-15:20 | 161400.50 | 09-FEB-15:20 | 0.00 | 0.00 | 0.00 |
March | 0.703128E+10 | 0.00 | 30.29 | 0.703128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199329.04 | 23-MAR-15:50 | 199329.04 | 23-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.562983E+11 | 0.00 | 97.88 | 0.562806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 869576.63 | 30-APR-14:31 | 869576.63 | 30-APR-14:31 | 0.00 | 0.00 | 0.00 |
May | 0.575190E+11 | 0.00 | 101.84 | 0.575190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 861204.11 | 22-MAY-15:00 | 861204.11 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.154289E+12 | 0.00 | 183.43 | 0.152183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1092708.90 | 13-JUN-16:00 | 1010344.48 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.241156E+12 | 0.00 | 302.35 | 0.240802E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1037538.44 | 21-JUL-15:30 | 1037538.44 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.302673E+12 | 0.00 | 377.25 | 0.302039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1006633.24 | 14-AUG-15:30 | 1006633.24 | 14-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.176155E+12 | 0.00 | 238.78 | 0.174590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 826442.99 | 13-SEP-14:50 | 826442.99 | 13-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.522617E+11 | 0.00 | 82.72 | 0.522617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 576141.11 | 05-OCT-14:05 | 576141.11 | 05-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.522023E+10 | 0.00 | 22.69 | 0.522023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226049.69 | 10-NOV-15:10 | 226049.69 | 10-NOV-15:10 | 0.00 | 0.00 | 0.00 |
December | 53733706.85 | 0.00 | 14.14 | 53733706.85 | 0.00 | 0.00 | 0.00 | 0.00 | 18280.59 | 21-DEC-14:10 | 18280.59 | 21-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105850E+13 | 0.00 | 1501.89 | 0.105382E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 53733706.85 | 0.00 | 14.14 | 53733706.85 | 0.00 | 0.00 | 0.00 | 0.00 | 18280.59 | 18280.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.302673E+12 | 0.00 | 377.25 | 0.302039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1092708.90 | 1037538.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 1361862.38 | 0.00 | 0.83 | 1361862.38 | 0.00 | 0.00 | 0.00 | 0.00 | 662.77 | 09-FEB-15:40 | 662.77 | 09-FEB-15:40 | 0.00 | 0.00 | 0.00 |
March | 20163622.10 | 0.00 | 1.17 | 20163622.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6938.17 | 31-MAR-16:00 | 6938.17 | 31-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.348641E+10 | 0.00 | 52.29 | 0.348641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82903.39 | 30-APR-15:22 | 82903.39 | 30-APR-15:22 | 0.00 | 0.00 | 0.00 |
May | 0.490901E+10 | 0.00 | 65.72 | 0.490901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94921.31 | 22-MAY-15:00 | 94921.31 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.155576E+11 | 0.00 | 160.26 | 0.153319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140373.51 | 25-JUN-18:11 | 121027.18 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.245423E+11 | 0.00 | 282.87 | 0.245206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121184.05 | 21-JUL-15:30 | 121184.05 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.292574E+11 | 0.00 | 363.22 | 0.292234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115572.21 | 14-AUG-15:40 | 115572.21 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.150758E+11 | 0.00 | 203.49 | 0.149968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84322.29 | 13-SEP-14:40 | 84322.29 | 13-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.588129E+09 | 0.00 | 22.60 | 0.588129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19589.15 | 07-OCT-15:00 | 19589.15 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 3341121.87 | 0.00 | 0.67 | 3341121.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2546.09 | 24-NOV-12:00 | 2546.09 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.934415E+11 | 0.00 | 1153.12 | 0.930811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.292574E+11 | 0.00 | 363.22 | 0.292234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140373.51 | 121184.05 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 23413772.47 | 0.00 | 4.00 | 23413772.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3750.18 | 25-JAN-15:00 | 3750.18 | 25-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 31699921.68 | 0.00 | 5.67 | 29971670.52 | 0.00 | 0.00 | 0.00 | 0.00 | 10611.52 | 18-MAR-06:05 | 4850.69 | 18-MAR-06:05 | 0.00 | 0.00 | 0.00 |
April | 0.115717E+10 | 0.00 | 30.06 | 0.115717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30304.97 | 28-APR-15:00 | 30304.97 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.438576E+10 | 0.00 | 62.24 | 0.395010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58073.94 | 22-MAY-15:00 | 58073.94 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.118439E+11 | 0.00 | 142.84 | 0.108116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67850.79 | 27-JUN-06:23 | 60982.41 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.214951E+11 | 0.00 | 261.94 | 0.195864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74859.22 | 10-JUL-06:35 | 70201.70 | 10-JUL-10:00 | 0.00 | 0.00 | 0.00 |
August | 0.260899E+11 | 0.00 | 319.39 | 0.249799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73035.73 | 14-AUG-13:10 | 67468.19 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 |
September | 0.124932E+11 | 0.00 | 185.00 | 0.119409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56070.43 | 16-SEP-06:14 | 52672.51 | 25-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.767957E+09 | 0.00 | 34.21 | 0.671228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34032.36 | 20-OCT-06:12 | 17630.25 | 11-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 60100441.57 | 0.00 | 1.86 | 52126610.10 | 0.00 | 0.00 | 0.00 | 0.00 | 29828.50 | 24-NOV-07:11 | 16453.89 | 24-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783483E+11 | 0.00 | 1047.20 | 0.732029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.260899E+11 | 0.00 | 319.39 | 0.249799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74859.22 | 70201.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.382837E+10 | 0.352506E+10 | 719.33 | 0.382827E+10 | 101546.88 | 0.00 | 0.02 | 10-JAN-18:00 | 0.01 | 23-JAN-10:15 | 3039.91 | 10-JAN-17:05 | 3039.91 | 10-JAN-17:05 | 55.82 | 29-JAN-05:50 | 1722.76 | 10-JAN-18:00 | 0.00 |
February | 0.608728E+10 | 0.388692E+10 | 661.42 | 0.603087E+10 | 56408912.15 | 0.00 | 0.02 | 20-FEB-16:00 | 0.01 | 07-FEB-14:15 | 5072.89 | 20-FEB-16:07 | 5072.89 | 20-FEB-16:07 | 65.93 | 06-FEB-18:50 | 2300.83 | 11-FEB-12:50 | 0.00 |
March | 0.108178E+11 | 0.547367E+10 | 701.43 | 0.104464E+11 | 0.371472E+09 | 0.00 | 0.03 | 31-MAR-23:30 | 0.01 | 18-MAR-04:17 | 5494.80 | 31-MAR-23:10 | 5494.80 | 31-MAR-23:10 | 256.37 | 01-MAR-18:30 | 2574.99 | 09-MAR-07:10 | 0.00 |
April | 0.450483E+11 | 0.147972E+11 | 716.68 | 0.429606E+11 | 0.208769E+10 | 0.00 | 0.82 | 30-APR-17:00 | 0.01 | 30-APR-06:17 | 320727.84 | 30-APR-17:31 | 320727.84 | 30-APR-17:31 | 79919.70 | 28-APR-08:00 | 97863.65 | 30-APR-17:00 | 0.00 |
May | 0.223065E+10 | 0.321359E+10 | 565.48 | 0.221108E+10 | 19564149.42 | 0.00 | 0.13 | 22-MAY-15:00 | 0.01 | 28-MAY-09:35 | 46000.01 | 22-MAY-15:00 | 42461.71 | 22-MAY-15:00 | 3538.30 | 22-MAY-15:00 | 14234.61 | 22-MAY-15:00 | 0.00 |
June | 0.183959E+11 | 0.802267E+10 | 296.64 | 0.157453E+11 | 0.265051E+10 | 0.00 | 0.54 | 13-JUN-17:00 | 0.01 | 10-JUN-04:15 | 226519.87 | 13-JUN-17:00 | 223047.80 | 13-JUN-17:00 | 77558.66 | 25-JUN-17:52 | 67724.64 | 13-JUN-17:00 | 0.00 |
July | 0.868795E+11 | 0.264667E+11 | 403.42 | 0.719444E+11 | 0.149351E+11 | 0.00 | 0.77 | 21-JUL-17:00 | 0.01 | 30-JUL-05:15 | 316905.35 | 21-JUL-16:00 | 316905.35 | 21-JUL-16:00 | 61040.70 | 23-JUL-15:51 | 102119.96 | 22-JUL-18:00 | 0.00 |
August | 0.287308E+12 | 0.743954E+11 | 604.10 | 0.213350E+12 | 0.739574E+11 | 0.00 | 1.00 | 14-AUG-17:20 | 0.01 | 28-AUG-03:23 | 411522.92 | 14-AUG-17:00 | 411522.92 | 14-AUG-17:00 | 136788.58 | 08-AUG-13:00 | 129939.12 | 14-AUG-17:20 | 0.00 |
September | 0.949780E+09 | 0.282798E+10 | 352.55 | 0.920170E+09 | 29609834.29 | 0.00 | 0.06 | 27-SEP-16:00 | 0.01 | 03-SEP-08:13 | 16806.39 | 27-SEP-16:00 | 16806.39 | 27-SEP-16:00 | 2405.73 | 13-SEP-16:00 | 6073.43 | 27-SEP-16:00 | 0.00 |
October | 0.311349E+10 | 0.343285E+10 | 536.79 | 0.303956E+10 | 73924529.61 | 0.00 | 0.03 | 31-OCT-23:10 | 0.01 | 18-OCT-02:70 | 5333.04 | 31-OCT-23:10 | 5292.02 | 31-OCT-23:10 | 91.04 | 31-OCT-24:00 | 2405.41 | 07-OCT-15:00 | 0.00 |
November | 0.742704E+10 | 0.450597E+10 | 607.27 | 0.707255E+10 | 0.354484E+09 | 0.00 | 0.03 | 25-NOV-14:00 | 0.01 | 24-NOV-07:11 | 5378.89 | 16-NOV-22:50 | 5303.69 | 19-NOV-12:23 | 259.20 | 20-NOV-23:00 | 2412.07 | 25-NOV-14:00 | 0.00 |
December | 0.140711E+11 | 0.652604E+10 | 744.00 | 0.131709E+11 | 0.900168E+09 | 0.00 | 0.03 | 04-DEC-11:00 | 0.01 | 02-DEC-17:00 | 5989.05 | 17-DEC-18:20 | 5542.83 | 30-DEC-15:02 | 577.06 | 21-DEC-20:00 | 2665.14 | 04-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.486157E+12 | 0.157074E+12 | 6909.11 | 0.390721E+12 | 0.954365E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.949780E+09 | 0.282798E+10 | 296.64 | 0.920170E+09 | 101546.88 | 0.00 | 0.02 | 0.01 | 3039.91 | 3039.91 | 55.82 | 1722.76 | 0.00 | ||||||
Maximum of Months | 0.287308E+12 | 0.743954E+11 | 744.00 | 0.213350E+12 | 0.739574E+11 | 0.00 | 1.00 | 0.01 | 411522.92 | 411522.92 | 136788.58 | 129939.12 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.434928E+10 | 0.103188E+10 | 744.00 | 0.434772E+10 | 1558784.71 | 0.00 | 0.29 | 01-JAN-16:10 | 0.12 | 10-JAN-08:00 | 2399.99 | 01-JAN-16:10 | 2394.40 | 01-JAN-16:05 | 52.54 | 18-JAN-16:20 | 531.01 | 01-JAN-16:10 | 0.00 |
February | 0.879653E+10 | 0.195364E+10 | 672.00 | 0.879526E+10 | 1271294.72 | 0.00 | 0.55 | 19-FEB-16:53 | 0.37 | 17-FEB-07:03 | 4618.77 | 19-FEB-16:57 | 4618.77 | 19-FEB-16:57 | 56.61 | 07-FEB-16:00 | 1022.20 | 19-FEB-16:53 | 0.00 |
March | 0.150676E+11 | 0.319113E+10 | 744.00 | 0.150673E+11 | 313253.90 | 0.00 | 0.85 | 31-MAR-24:00 | 0.59 | 01-MAR-07:05 | 7598.19 | 31-MAR-24:00 | 7598.19 | 31-MAR-24:00 | 66.57 | 20-MAR-06:05 | 1571.68 | 31-MAR-24:00 | 0.00 |
April | 0.200110E+11 | 0.408955E+10 | 720.00 | 0.200103E+11 | 731668.91 | 0.00 | 1.00 | 30-APR-17:22 | 0.31 | 30-APR-24:00 | 8921.26 | 30-APR-19:02 | 8921.26 | 30-APR-19:02 | 60.24 | 28-APR-15:10 | 2318.66 | 30-APR-18:10 | 0.00 |
May | 0.544628E+10 | 0.124539E+10 | 744.00 | 0.542632E+10 | 19966219.54 | 0.00 | 0.45 | 31-MAY-24:00 | 0.18 | 06-MAY-06:05 | 3936.03 | 31-MAY-24:00 | 3936.03 | 31-MAY-24:00 | 137.10 | 23-MAY-16:00 | 834.98 | 31-MAY-24:00 | 0.00 |
June | 0.105350E+11 | 0.226379E+10 | 720.00 | 0.104501E+11 | 84853250.39 | 0.00 | 0.63 | 30-JUN-24:00 | 0.41 | 01-JUN-06:20 | 5773.30 | 30-JUN-24:00 | 5773.30 | 30-JUN-24:00 | 223.41 | 26-JUN-16:10 | 1321.62 | 13-JUN-16:00 | 0.00 |
July | 0.161401E+11 | 0.337482E+10 | 744.00 | 0.160280E+11 | 0.112159E+09 | 0.00 | 0.83 | 31-JUL-24:00 | 0.60 | 01-JUL-06:20 | 7825.91 | 31-JUL-24:00 | 7825.91 | 31-JUL-24:00 | 249.83 | 18-JUL-15:40 | 2077.69 | 22-JUL-18:40 | 0.00 |
August | 0.211452E+11 | 0.432160E+10 | 744.00 | 0.210068E+11 | 0.138404E+09 | 0.00 | 0.95 | 14-AUG-18:00 | 0.30 | 31-AUG-24:00 | 8882.28 | 13-AUG-18:03 | 8857.38 | 13-AUG-18:05 | 278.15 | 08-AUG-13:30 | 2391.76 | 14-AUG-18:00 | 0.00 |
September | 0.544591E+10 | 0.123299E+10 | 720.00 | 0.538149E+10 | 64418138.14 | 0.00 | 0.45 | 30-SEP-24:00 | 0.19 | 21-SEP-06:05 | 3827.69 | 30-SEP-24:00 | 3827.69 | 30-SEP-24:00 | 154.86 | 19-SEP-15:50 | 841.88 | 30-SEP-24:00 | 0.00 |
October | 0.102798E+11 | 0.222306E+10 | 744.00 | 0.102533E+11 | 26497203.92 | 0.00 | 0.65 | 31-OCT-24:00 | 0.38 | 28-OCT-07:00 | 5675.99 | 31-OCT-24:00 | 5675.99 | 31-OCT-24:00 | 128.48 | 17-OCT-15:30 | 1195.83 | 31-OCT-24:00 | 0.00 |
November | 0.146237E+11 | 0.306191E+10 | 720.00 | 0.146080E+11 | 15712560.25 | 0.00 | 0.71 | 19-NOV-15:55 | 0.59 | 25-NOV-07:50 | 6252.60 | 19-NOV-16:00 | 6252.60 | 19-NOV-16:00 | 143.02 | 08-NOV-15:10 | 1309.68 | 19-NOV-15:55 | 0.00 |
December | 0.199153E+11 | 0.409755E+10 | 744.00 | 0.199151E+11 | 156395.49 | 0.00 | 0.91 | 31-DEC-15:05 | 0.78 | 21-DEC-07:05 | 8007.78 | 25-DEC-15:05 | 8007.78 | 25-DEC-15:05 | 40.52 | 20-DEC-17:10 | 1668.50 | 31-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.151756E+12 | 0.320873E+11 | 8760.00 | 0.151290E+12 | 0.466042E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.434928E+10 | 0.103188E+10 | 672.00 | 0.434772E+10 | 156395.49 | 0.00 | 0.29 | 0.12 | 2399.99 | 2394.40 | 40.52 | 531.01 | 0.00 | ||||||
Maximum of Months | 0.211452E+11 | 0.432160E+10 | 744.00 | 0.210068E+11 | 0.138404E+09 | 0.00 | 1.00 | 0.78 | 8921.26 | 8921.26 | 278.15 | 2391.76 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.233584E+11 | 0.582164E+10 | 742.44 | 0.233431E+11 | 15351620.19 | 0.00 | 0.25 | 19-JAN-16:20 | 0.00 | 02-JAN-07:03 | 19401.55 | 19-JAN-16:20 | 19401.55 | 19-JAN-16:20 | 509.04 | 18-JAN-16:30 | 4398.42 | 19-JAN-16:20 | 0.00 |
February | 0.692307E+11 | 0.156503E+11 | 672.00 | 0.692175E+11 | 13169809.19 | 0.00 | 0.50 | 19-FEB-17:05 | 0.27 | 13-FEB-07:03 | 40170.53 | 27-FEB-17:00 | 40170.53 | 27-FEB-17:00 | 560.26 | 07-FEB-16:00 | 8827.31 | 19-FEB-17:05 | 0.00 |
March | 0.129887E+12 | 0.278461E+11 | 744.00 | 0.129884E+12 | 3178303.73 | 0.00 | 0.81 | 31-MAR-23:30 | 0.51 | 27-MAR-06:03 | 69185.57 | 31-MAR-23:30 | 69185.57 | 31-MAR-23:30 | 559.54 | 20-MAR-06:05 | 14421.59 | 31-MAR-23:30 | 0.00 |
April | 0.185048E+12 | 0.380183E+11 | 720.00 | 0.185040E+12 | 7539377.98 | 0.00 | 1.00 | 30-APR-17:51 | 0.28 | 30-APR-24:00 | 85457.67 | 30-APR-18:10 | 85457.67 | 30-APR-18:10 | 604.93 | 28-APR-15:10 | 22274.07 | 30-APR-18:10 | 0.00 |
May | 0.464091E+11 | 0.107140E+11 | 744.00 | 0.462117E+11 | 0.197436E+09 | 0.00 | 0.43 | 31-MAY-23:50 | 0.12 | 05-MAY-06:05 | 36472.44 | 31-MAY-23:50 | 36472.44 | 31-MAY-23:50 | 1362.55 | 23-MAY-16:00 | 7763.76 | 31-MAY-23:50 | 0.00 |
June | 0.968565E+11 | 0.209065E+11 | 720.00 | 0.960139E+11 | 0.842603E+09 | 0.00 | 0.61 | 30-JUN-23:40 | 0.38 | 08-JUN-06:05 | 53245.55 | 30-JUN-23:40 | 53245.55 | 30-JUN-23:40 | 2210.65 | 26-JUN-16:10 | 12578.03 | 13-JUN-16:00 | 0.00 |
July | 0.150710E+12 | 0.316287E+11 | 744.00 | 0.149597E+12 | 0.111337E+10 | 0.00 | 0.82 | 31-JUL-24:00 | 0.57 | 01-JUL-06:20 | 73817.52 | 31-JUL-24:00 | 73817.52 | 31-JUL-24:00 | 2468.05 | 18-JUL-15:40 | 19803.26 | 22-JUL-18:40 | 0.00 |
August | 0.198921E+12 | 0.407826E+11 | 744.00 | 0.197550E+12 | 0.137127E+10 | 0.00 | 0.95 | 14-AUG-18:00 | 0.25 | 31-AUG-24:00 | 83088.08 | 13-AUG-18:03 | 82847.19 | 13-AUG-18:05 | 2757.03 | 08-AUG-13:30 | 22847.43 | 14-AUG-18:00 | 0.00 |
September | 0.466244E+11 | 0.106576E+11 | 720.00 | 0.459938E+11 | 0.630647E+09 | 0.00 | 0.43 | 30-SEP-23:30 | 0.14 | 20-SEP-06:25 | 34652.30 | 30-SEP-23:30 | 34652.30 | 30-SEP-23:30 | 1547.43 | 19-SEP-16:00 | 7666.77 | 30-SEP-23:30 | 0.00 |
October | 0.868329E+11 | 0.190011E+11 | 744.00 | 0.865698E+11 | 0.263106E+09 | 0.00 | 0.60 | 31-OCT-23:50 | 0.31 | 28-OCT-07:00 | 49922.95 | 31-OCT-23:50 | 49922.95 | 31-OCT-23:50 | 1275.01 | 17-OCT-15:30 | 10631.00 | 31-OCT-23:50 | 0.00 |
November | 0.123108E+12 | 0.261539E+11 | 720.00 | 0.122951E+12 | 0.157244E+09 | 0.00 | 0.65 | 03-NOV-16:00 | 0.49 | 27-NOV-07:05 | 56029.18 | 10-NOV-16:10 | 55840.19 | 10-NOV-16:00 | 1425.51 | 08-NOV-15:10 | 11645.10 | 03-NOV-16:00 | 0.00 |
December | 0.166697E+12 | 0.349170E+11 | 744.00 | 0.166695E+12 | 1847996.53 | 0.00 | 0.82 | 29-DEC-15:50 | 0.65 | 18-DEC-07:05 | 70690.28 | 21-DEC-15:20 | 70690.28 | 21-DEC-15:20 | 407.17 | 20-DEC-17:10 | 14526.24 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.132368E+13 | 0.282098E+12 | 8758.44 | 0.131907E+13 | 0.461676E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.233584E+11 | 0.582164E+10 | 672.00 | 0.233431E+11 | 1847996.53 | 0.00 | 0.25 | 0.00 | 19401.55 | 19401.55 | 407.17 | 4398.42 | 0.00 | ||||||
Maximum of Months | 0.198921E+12 | 0.407826E+11 | 744.00 | 0.197550E+12 | 0.137127E+10 | 0.00 | 1.00 | 0.65 | 85457.67 | 85457.67 | 2757.03 | 22847.43 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.651954E+09 | 0.174331E+09 | 394.94 | 0.650979E+09 | 975558.86 | 0.00 | 0.23 | 19-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1829.24 | 19-JAN-16:30 | 1829.24 | 19-JAN-16:30 | 46.69 | 18-JAN-16:40 | 417.00 | 19-JAN-16:30 | 0.00 |
February | 0.508850E+10 | 0.117747E+10 | 672.00 | 0.508726E+10 | 1236831.88 | 0.00 | 0.46 | 17-FEB-17:00 | 0.12 | 20-FEB-08:10 | 3790.09 | 24-FEB-17:00 | 3790.09 | 24-FEB-17:00 | 53.13 | 07-FEB-16:30 | 832.02 | 17-FEB-17:00 | 0.00 |
March | 0.113310E+11 | 0.246551E+10 | 744.00 | 0.113307E+11 | 304398.50 | 0.00 | 0.76 | 31-MAR-23:20 | 0.37 | 06-MAR-05:12 | 6480.60 | 31-MAR-23:20 | 6480.60 | 31-MAR-23:20 | 44.10 | 20-MAR-06:05 | 1364.64 | 31-MAR-23:20 | 0.00 |
April | 0.177292E+11 | 0.366874E+10 | 720.00 | 0.177285E+11 | 744409.24 | 0.00 | 1.00 | 30-APR-17:41 | 0.26 | 30-APR-24:00 | 8667.89 | 30-APR-18:21 | 8667.89 | 30-APR-18:21 | 60.29 | 28-APR-15:10 | 2257.85 | 30-APR-18:21 | 0.00 |
May | 0.397427E+10 | 0.928530E+09 | 744.00 | 0.395464E+10 | 19636518.83 | 0.00 | 0.41 | 31-MAY-23:20 | 0.04 | 05-MAY-06:05 | 3510.30 | 31-MAY-23:20 | 3510.30 | 31-MAY-23:20 | 137.16 | 23-MAY-16:00 | 750.86 | 31-MAY-23:20 | 0.00 |
June | 0.938254E+10 | 0.203435E+10 | 720.00 | 0.929841E+10 | 84129952.19 | 0.00 | 0.58 | 30-JUN-23:20 | 0.31 | 08-JUN-06:05 | 5123.88 | 30-JUN-23:20 | 5123.88 | 30-JUN-23:20 | 222.19 | 26-JUN-16:10 | 1285.19 | 13-JUN-16:00 | 0.00 |
July | 0.148193E+11 | 0.312241E+10 | 744.00 | 0.147081E+11 | 0.111272E+09 | 0.00 | 0.81 | 22-JUL-18:50 | 0.52 | 01-JUL-06:20 | 7236.46 | 31-JUL-23:20 | 7236.46 | 31-JUL-23:20 | 247.12 | 18-JUL-15:40 | 2032.72 | 22-JUL-18:40 | 0.00 |
August | 0.196337E+11 | 0.404128E+10 | 744.00 | 0.194968E+11 | 0.136921E+09 | 0.00 | 0.94 | 14-AUG-18:00 | 0.22 | 31-AUG-24:00 | 8437.67 | 13-AUG-18:03 | 8413.40 | 13-AUG-18:05 | 275.39 | 08-AUG-13:30 | 2307.89 | 14-AUG-18:00 | 0.00 |
September | 0.404001E+10 | 0.935014E+09 | 719.67 | 0.397773E+10 | 62281790.02 | 0.00 | 0.37 | 30-SEP-23:20 | 0.00 | 17-SEP-06:05 | 2964.00 | 30-SEP-23:20 | 2964.00 | 30-SEP-23:20 | 155.33 | 19-SEP-16:00 | 667.00 | 13-SEP-17:00 | 0.00 |
October | 0.718153E+10 | 0.159724E+10 | 744.00 | 0.715589E+10 | 25638392.87 | 0.00 | 0.53 | 31-OCT-23:20 | 0.19 | 23-OCT-06:05 | 4438.78 | 31-OCT-23:20 | 4438.78 | 31-OCT-23:20 | 127.87 | 17-OCT-15:40 | 958.52 | 31-OCT-23:20 | 0.00 |
November | 0.104228E+11 | 0.225284E+10 | 720.00 | 0.104074E+11 | 15447322.14 | 0.00 | 0.63 | 03-NOV-16:00 | 0.33 | 27-NOV-05:11 | 5532.65 | 10-NOV-16:10 | 5513.64 | 10-NOV-16:00 | 142.09 | 08-NOV-15:10 | 1144.79 | 03-NOV-16:00 | 0.00 |
December | 0.145364E+11 | 0.309756E+10 | 744.00 | 0.145362E+11 | 170109.52 | 0.00 | 0.77 | 29-DEC-16:00 | 0.48 | 26-DEC-05:12 | 6819.71 | 21-DEC-15:20 | 6819.71 | 21-DEC-15:20 | 39.61 | 20-DEC-17:10 | 1387.88 | 29-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.118791E+12 | 0.254953E+11 | 8410.61 | 0.118333E+12 | 0.458758E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.651954E+09 | 0.174331E+09 | 394.94 | 0.650979E+09 | 170109.52 | 0.00 | 0.23 | 0.00 | 1829.24 | 1829.24 | 39.61 | 417.00 | 0.00 | ||||||
Maximum of Months | 0.196337E+11 | 0.404128E+10 | 744.00 | 0.194968E+11 | 0.136921E+09 | 0.00 | 1.00 | 0.52 | 8667.89 | 8667.89 | 275.39 | 2307.89 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.31 | 0.00 | 91.31 | 2.72 | 634.57 | 0.00 | 0.00 | 0.00 |
February | 142.59 | 0.00 | 142.59 | 10.78 | 591.92 | 0.00 | 0.00 | 0.00 |
March | 197.32 | 0.00 | 197.32 | 48.66 | 495.34 | 0.00 | 0.00 | 0.00 |
April | 321.26 | 1.44 | 319.82 | 188.30 | 389.50 | 0.00 | 0.00 | 0.00 |
May | 401.66 | 19.38 | 382.28 | 245.44 | 302.74 | 0.00 | 0.00 | 0.00 |
June | 444.01 | 27.84 | 416.17 | 360.20 | 237.43 | 0.00 | 0.00 | 0.00 |
July | 421.17 | 24.01 | 397.15 | 362.86 | 220.35 | 0.00 | 0.00 | 0.00 |
August | 331.06 | 5.19 | 325.87 | 277.39 | 248.37 | 0.00 | 0.00 | 0.00 |
September | 251.98 | 0.06 | 251.93 | 178.59 | 330.11 | 0.00 | 0.00 | 0.00 |
October | 161.47 | 0.00 | 161.47 | 53.96 | 459.42 | 0.00 | 0.00 | 0.00 |
November | 97.02 | 0.00 | 97.02 | 4.65 | 578.04 | 0.00 | 0.00 | 0.00 |
December | 66.07 | 0.00 | 66.07 | 0.00 | 699.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 244.36 | 6.54 | 237.83 | 145.14 | 431.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.07 | 0.00 | 66.07 | 0.00 | 220.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 444.01 | 27.84 | 416.17 | 362.86 | 699.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.31 | 0.00 | 91.31 | 2.72 | 634.57 | 0.00 | 0.00 | 0.00 |
February | 142.59 | 0.00 | 142.59 | 10.78 | 591.92 | 0.00 | 0.00 | 0.00 |
March | 197.32 | 0.00 | 197.32 | 48.66 | 495.34 | 0.00 | 0.00 | 0.00 |
April | 321.26 | 1.44 | 319.82 | 188.29 | 389.50 | 0.00 | 0.00 | 0.00 |
May | 401.66 | 19.38 | 382.28 | 245.44 | 302.74 | 0.00 | 0.00 | 0.00 |
June | 444.01 | 27.84 | 416.17 | 360.20 | 237.43 | 0.00 | 0.00 | 0.00 |
July | 421.17 | 24.01 | 397.15 | 362.86 | 220.35 | 0.00 | 0.00 | 0.00 |
August | 331.06 | 5.19 | 325.87 | 277.39 | 248.37 | 0.00 | 0.00 | 0.00 |
September | 251.98 | 0.06 | 251.93 | 178.59 | 330.11 | 0.00 | 0.00 | 0.00 |
October | 161.47 | 0.00 | 161.47 | 53.96 | 459.42 | 0.00 | 0.00 | 0.00 |
November | 97.02 | 0.00 | 97.02 | 4.65 | 578.04 | 0.00 | 0.00 | 0.00 |
December | 66.07 | 0.00 | 66.07 | 0.00 | 699.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 244.36 | 6.54 | 237.82 | 145.14 | 431.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.07 | 0.00 | 66.07 | 0.00 | 220.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 444.01 | 27.84 | 416.17 | 362.86 | 699.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.31 | 0.00 | 91.31 | 2.72 | 634.57 | 0.00 | 0.00 | 0.00 |
February | 142.59 | 0.00 | 142.59 | 10.78 | 591.92 | 0.00 | 0.00 | 0.00 |
March | 197.32 | 0.00 | 197.32 | 48.66 | 495.34 | 0.00 | 0.00 | 0.00 |
April | 321.26 | 1.44 | 319.82 | 188.30 | 389.50 | 0.00 | 0.00 | 0.00 |
May | 401.66 | 19.38 | 382.28 | 245.44 | 302.74 | 0.00 | 0.00 | 0.00 |
June | 444.01 | 27.84 | 416.17 | 360.20 | 237.43 | 0.00 | 0.00 | 0.00 |
July | 421.17 | 24.01 | 397.15 | 362.86 | 220.35 | 0.00 | 0.00 | 0.00 |
August | 331.06 | 5.19 | 325.87 | 277.39 | 248.37 | 0.00 | 0.00 | 0.00 |
September | 251.98 | 0.06 | 251.93 | 178.59 | 330.11 | 0.00 | 0.00 | 0.00 |
October | 161.47 | 0.00 | 161.47 | 53.96 | 459.42 | 0.00 | 0.00 | 0.00 |
November | 97.02 | 0.00 | 97.02 | 4.65 | 578.04 | 0.00 | 0.00 | 0.00 |
December | 66.07 | 0.00 | 66.07 | 0.00 | 699.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 244.36 | 6.54 | 237.83 | 145.14 | 431.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.07 | 0.00 | 66.07 | 0.00 | 220.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 444.01 | 27.84 | 416.17 | 362.86 | 699.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.31 | 0.00 | 91.31 | 2.72 | 634.57 | 0.00 | 0.00 | 0.00 |
February | 142.59 | 0.00 | 142.59 | 10.78 | 591.92 | 0.00 | 0.00 | 0.00 |
March | 197.32 | 0.00 | 197.32 | 48.66 | 495.34 | 0.00 | 0.00 | 0.00 |
April | 321.26 | 1.44 | 319.82 | 188.29 | 389.50 | 0.00 | 0.00 | 0.00 |
May | 401.66 | 19.38 | 382.28 | 245.44 | 302.74 | 0.00 | 0.00 | 0.00 |
June | 444.01 | 27.84 | 416.17 | 360.20 | 237.43 | 0.00 | 0.00 | 0.00 |
July | 421.17 | 24.01 | 397.15 | 362.86 | 220.35 | 0.00 | 0.00 | 0.00 |
August | 331.06 | 5.19 | 325.87 | 277.39 | 248.37 | 0.00 | 0.00 | 0.00 |
September | 251.98 | 0.06 | 251.93 | 178.59 | 330.11 | 0.00 | 0.00 | 0.00 |
October | 161.47 | 0.00 | 161.47 | 53.96 | 459.42 | 0.00 | 0.00 | 0.00 |
November | 97.02 | 0.00 | 97.02 | 4.65 | 578.04 | 0.00 | 0.00 | 0.00 |
December | 66.07 | 0.00 | 66.07 | 0.00 | 699.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 244.36 | 6.54 | 237.82 | 145.14 | 431.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.07 | 0.00 | 66.07 | 0.00 | 220.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 444.01 | 27.84 | 416.17 | 362.86 | 699.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.31 | 0.00 | 91.31 | 2.72 | 634.54 | 0.00 | 0.00 | 0.00 |
February | 142.58 | 0.00 | 142.58 | 10.78 | 591.89 | 0.00 | 0.00 | 0.00 |
March | 197.31 | 0.00 | 197.31 | 48.65 | 495.32 | 0.00 | 0.00 | 0.00 |
April | 321.25 | 1.44 | 319.81 | 188.29 | 389.48 | 0.00 | 0.00 | 0.00 |
May | 401.64 | 19.38 | 382.27 | 245.43 | 302.73 | 0.00 | 0.00 | 0.00 |
June | 443.99 | 27.84 | 416.15 | 360.19 | 237.42 | 0.00 | 0.00 | 0.00 |
July | 421.15 | 24.01 | 397.14 | 362.85 | 220.34 | 0.00 | 0.00 | 0.00 |
August | 331.05 | 5.19 | 325.86 | 277.37 | 248.36 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 0.06 | 251.92 | 178.58 | 330.10 | 0.00 | 0.00 | 0.00 |
October | 161.46 | 0.00 | 161.46 | 53.96 | 459.41 | 0.00 | 0.00 | 0.00 |
November | 97.01 | 0.00 | 97.01 | 4.65 | 578.01 | 0.00 | 0.00 | 0.00 |
December | 66.07 | 0.00 | 66.07 | 0.00 | 699.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 244.35 | 6.54 | 237.82 | 145.13 | 431.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.07 | 0.00 | 66.07 | 0.00 | 220.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.99 | 27.84 | 416.15 | 362.85 | 699.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.38 | 83.30 | 124.07 | 109.14 | 655.78 | 0.00 | 0.00 | 0.00 |
February | 309.23 | 114.23 | 195.00 | 184.83 | 613.26 | 0.00 | 0.00 | 0.00 |
March | 323.15 | 63.68 | 259.47 | 175.27 | 509.98 | 0.00 | 0.00 | 0.00 |
April | 867.70 | 407.74 | 459.96 | 890.70 | 401.94 | 0.00 | 0.00 | 0.00 |
May | 912.36 | 397.86 | 514.49 | 913.78 | 343.66 | 0.00 | 0.00 | 0.00 |
June | 903.07 | 360.68 | 542.39 | 968.31 | 267.15 | 0.00 | 0.00 | 0.00 |
July | 921.85 | 391.79 | 530.06 | 1031.79 | 247.07 | 0.00 | 0.00 | 0.00 |
August | 873.25 | 417.23 | 456.02 | 1007.25 | 267.80 | 0.00 | 0.00 | 0.00 |
September | 786.39 | 418.17 | 368.23 | 873.62 | 346.60 | 0.00 | 0.00 | 0.00 |
October | 379.60 | 157.32 | 222.29 | 320.41 | 483.20 | 0.00 | 0.00 | 0.00 |
November | 197.90 | 67.45 | 130.45 | 102.87 | 596.26 | 0.00 | 0.00 | 0.00 |
December | 146.67 | 54.53 | 92.14 | 65.89 | 714.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.87 | 244.81 | 325.06 | 554.99 | 453.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.67 | 54.53 | 92.14 | 65.89 | 247.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 921.85 | 418.17 | 542.39 | 1031.79 | 714.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.38 | 83.30 | 124.07 | 109.14 | 655.78 | 0.00 | 0.00 | 0.00 |
February | 309.23 | 114.23 | 195.00 | 184.83 | 613.26 | 0.00 | 0.00 | 0.00 |
March | 323.15 | 63.68 | 259.47 | 175.27 | 509.98 | 0.00 | 0.00 | 0.00 |
April | 867.70 | 407.74 | 459.96 | 890.70 | 401.94 | 0.00 | 0.00 | 0.00 |
May | 912.36 | 397.86 | 514.49 | 913.78 | 343.66 | 0.00 | 0.00 | 0.00 |
June | 903.07 | 360.68 | 542.39 | 968.31 | 267.15 | 0.00 | 0.00 | 0.00 |
July | 921.85 | 391.79 | 530.06 | 1031.79 | 247.07 | 0.00 | 0.00 | 0.00 |
August | 873.25 | 417.23 | 456.02 | 1007.25 | 267.80 | 0.00 | 0.00 | 0.00 |
September | 786.39 | 418.17 | 368.23 | 873.62 | 346.60 | 0.00 | 0.00 | 0.00 |
October | 379.60 | 157.32 | 222.29 | 320.41 | 483.20 | 0.00 | 0.00 | 0.00 |
November | 197.90 | 67.45 | 130.45 | 102.87 | 596.26 | 0.00 | 0.00 | 0.00 |
December | 146.67 | 54.53 | 92.14 | 65.89 | 714.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.87 | 244.81 | 325.06 | 554.99 | 453.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.67 | 54.53 | 92.14 | 65.89 | 247.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 921.85 | 418.17 | 542.39 | 1031.79 | 714.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.37 | 83.30 | 124.07 | 109.14 | 655.77 | 0.00 | 0.00 | 0.00 |
February | 309.23 | 114.23 | 195.00 | 184.83 | 613.25 | 0.00 | 0.00 | 0.00 |
March | 323.15 | 63.68 | 259.47 | 175.27 | 509.97 | 0.00 | 0.00 | 0.00 |
April | 867.68 | 407.73 | 459.95 | 890.69 | 401.93 | 0.00 | 0.00 | 0.00 |
May | 912.34 | 397.86 | 514.48 | 913.76 | 343.65 | 0.00 | 0.00 | 0.00 |
June | 903.05 | 360.67 | 542.38 | 968.29 | 267.15 | 0.00 | 0.00 | 0.00 |
July | 921.83 | 391.78 | 530.05 | 1031.77 | 247.06 | 0.00 | 0.00 | 0.00 |
August | 873.24 | 417.22 | 456.01 | 1007.23 | 267.80 | 0.00 | 0.00 | 0.00 |
September | 786.38 | 418.16 | 368.22 | 873.61 | 346.60 | 0.00 | 0.00 | 0.00 |
October | 379.60 | 157.31 | 222.28 | 320.40 | 483.19 | 0.00 | 0.00 | 0.00 |
November | 197.89 | 67.45 | 130.45 | 102.86 | 596.24 | 0.00 | 0.00 | 0.00 |
December | 146.66 | 54.53 | 92.14 | 65.89 | 714.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 569.86 | 244.81 | 325.05 | 554.97 | 453.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.66 | 54.53 | 92.14 | 65.89 | 247.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 921.83 | 418.16 | 542.38 | 1031.77 | 714.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.41 | 335.59 | 182.82 | 500.33 | 544.01 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 386.35 | 246.79 | 629.65 | 533.31 | 0.00 | 0.00 | 0.00 |
March | 391.45 | 113.97 | 277.48 | 301.41 | 457.44 | 0.00 | 0.00 | 0.00 |
April | 812.88 | 367.41 | 445.47 | 912.24 | 394.45 | 0.00 | 0.00 | 0.00 |
May | 672.33 | 218.89 | 453.44 | 697.23 | 335.85 | 0.00 | 0.00 | 0.00 |
June | 619.36 | 149.92 | 469.44 | 669.13 | 260.48 | 0.00 | 0.00 | 0.00 |
July | 671.06 | 210.15 | 460.91 | 780.92 | 243.50 | 0.00 | 0.00 | 0.00 |
August | 786.33 | 353.72 | 432.61 | 972.06 | 265.76 | 0.00 | 0.00 | 0.00 |
September | 929.24 | 544.37 | 384.88 | 1140.03 | 332.76 | 0.00 | 0.00 | 0.00 |
October | 638.43 | 373.13 | 265.30 | 693.13 | 434.20 | 0.00 | 0.00 | 0.00 |
November | 452.65 | 275.36 | 177.29 | 439.02 | 518.23 | 0.00 | 0.00 | 0.00 |
December | 358.76 | 229.86 | 128.90 | 333.90 | 618.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 622.72 | 295.41 | 327.31 | 671.48 | 410.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.76 | 113.97 | 128.90 | 301.41 | 243.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 929.24 | 544.37 | 469.44 | 1140.03 | 618.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.41 | 335.59 | 182.82 | 500.33 | 544.01 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 386.35 | 246.79 | 629.65 | 533.31 | 0.00 | 0.00 | 0.00 |
March | 391.45 | 113.97 | 277.48 | 301.41 | 457.44 | 0.00 | 0.00 | 0.00 |
April | 812.88 | 367.41 | 445.47 | 912.24 | 394.45 | 0.00 | 0.00 | 0.00 |
May | 672.32 | 218.89 | 453.44 | 697.23 | 335.85 | 0.00 | 0.00 | 0.00 |
June | 619.35 | 149.92 | 469.43 | 669.13 | 260.48 | 0.00 | 0.00 | 0.00 |
July | 671.06 | 210.15 | 460.91 | 780.92 | 243.50 | 0.00 | 0.00 | 0.00 |
August | 786.33 | 353.72 | 432.61 | 972.06 | 265.76 | 0.00 | 0.00 | 0.00 |
September | 929.24 | 544.37 | 384.88 | 1140.03 | 332.76 | 0.00 | 0.00 | 0.00 |
October | 638.43 | 373.13 | 265.30 | 693.13 | 434.20 | 0.00 | 0.00 | 0.00 |
November | 452.64 | 275.36 | 177.29 | 439.02 | 518.23 | 0.00 | 0.00 | 0.00 |
December | 358.76 | 229.86 | 128.90 | 333.90 | 618.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 622.72 | 295.41 | 327.31 | 671.48 | 410.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.76 | 113.97 | 128.90 | 301.41 | 243.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 929.24 | 544.37 | 469.43 | 1140.03 | 618.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.41 | 335.59 | 182.82 | 500.33 | 544.01 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 386.35 | 246.79 | 629.65 | 533.31 | 0.00 | 0.00 | 0.00 |
March | 391.45 | 113.97 | 277.48 | 301.41 | 457.44 | 0.00 | 0.00 | 0.00 |
April | 812.88 | 367.41 | 445.47 | 912.24 | 394.45 | 0.00 | 0.00 | 0.00 |
May | 672.33 | 218.89 | 453.44 | 697.23 | 335.85 | 0.00 | 0.00 | 0.00 |
June | 619.36 | 149.92 | 469.44 | 669.13 | 260.48 | 0.00 | 0.00 | 0.00 |
July | 671.06 | 210.15 | 460.91 | 780.92 | 243.50 | 0.00 | 0.00 | 0.00 |
August | 786.33 | 353.72 | 432.61 | 972.06 | 265.76 | 0.00 | 0.00 | 0.00 |
September | 929.24 | 544.37 | 384.88 | 1140.03 | 332.76 | 0.00 | 0.00 | 0.00 |
October | 638.43 | 373.13 | 265.30 | 693.13 | 434.20 | 0.00 | 0.00 | 0.00 |
November | 452.65 | 275.36 | 177.29 | 439.02 | 518.23 | 0.00 | 0.00 | 0.00 |
December | 358.76 | 229.86 | 128.90 | 333.90 | 618.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 622.72 | 295.41 | 327.31 | 671.48 | 410.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.76 | 113.97 | 128.90 | 301.41 | 243.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 929.24 | 544.37 | 469.44 | 1140.03 | 618.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.41 | 335.59 | 182.82 | 500.33 | 544.01 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 386.35 | 246.79 | 629.65 | 533.31 | 0.00 | 0.00 | 0.00 |
March | 391.45 | 113.97 | 277.48 | 301.41 | 457.44 | 0.00 | 0.00 | 0.00 |
April | 812.88 | 367.41 | 445.47 | 912.24 | 394.45 | 0.00 | 0.00 | 0.00 |
May | 672.32 | 218.89 | 453.44 | 697.23 | 335.85 | 0.00 | 0.00 | 0.00 |
June | 619.35 | 149.92 | 469.43 | 669.13 | 260.48 | 0.00 | 0.00 | 0.00 |
July | 671.06 | 210.15 | 460.91 | 780.92 | 243.50 | 0.00 | 0.00 | 0.00 |
August | 786.33 | 353.72 | 432.61 | 972.06 | 265.76 | 0.00 | 0.00 | 0.00 |
September | 929.24 | 544.37 | 384.88 | 1140.03 | 332.76 | 0.00 | 0.00 | 0.00 |
October | 638.43 | 373.13 | 265.30 | 693.13 | 434.20 | 0.00 | 0.00 | 0.00 |
November | 452.64 | 275.36 | 177.29 | 439.02 | 518.23 | 0.00 | 0.00 | 0.00 |
December | 358.76 | 229.86 | 128.90 | 333.90 | 618.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 622.72 | 295.41 | 327.31 | 671.48 | 410.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.76 | 113.97 | 128.90 | 301.41 | 243.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 929.24 | 544.37 | 469.43 | 1140.03 | 618.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.39 | 335.57 | 182.81 | 500.31 | 543.99 | 0.00 | 0.00 | 0.00 |
February | 633.12 | 386.34 | 246.78 | 629.63 | 533.29 | 0.00 | 0.00 | 0.00 |
March | 391.43 | 113.97 | 277.47 | 301.40 | 457.42 | 0.00 | 0.00 | 0.00 |
April | 812.85 | 367.40 | 445.45 | 912.20 | 394.44 | 0.00 | 0.00 | 0.00 |
May | 672.30 | 218.88 | 453.42 | 697.20 | 335.84 | 0.00 | 0.00 | 0.00 |
June | 619.33 | 149.91 | 469.42 | 669.10 | 260.47 | 0.00 | 0.00 | 0.00 |
July | 671.03 | 210.14 | 460.89 | 780.89 | 243.49 | 0.00 | 0.00 | 0.00 |
August | 786.30 | 353.71 | 432.59 | 972.02 | 265.75 | 0.00 | 0.00 | 0.00 |
September | 929.21 | 544.34 | 384.86 | 1139.99 | 332.75 | 0.00 | 0.00 | 0.00 |
October | 638.40 | 373.12 | 265.28 | 693.10 | 434.18 | 0.00 | 0.00 | 0.00 |
November | 452.63 | 275.34 | 177.28 | 439.00 | 518.21 | 0.00 | 0.00 | 0.00 |
December | 358.75 | 229.85 | 128.90 | 333.88 | 618.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 622.69 | 295.40 | 327.29 | 671.46 | 410.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.75 | 113.97 | 128.90 | 301.40 | 243.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 929.21 | 544.34 | 469.42 | 1139.99 | 618.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.66 | 66.63 | 135.03 | 106.00 | 707.47 | 0.00 | 0.00 | 0.00 |
February | 357.05 | 150.76 | 206.29 | 258.35 | 689.47 | 0.00 | 0.00 | 0.00 |
March | 322.85 | 61.76 | 261.09 | 163.37 | 584.11 | 0.00 | 0.00 | 0.00 |
April | 761.78 | 302.59 | 459.20 | 742.81 | 480.72 | 0.00 | 0.00 | 0.00 |
May | 893.75 | 363.43 | 530.32 | 885.74 | 385.31 | 0.00 | 0.00 | 0.00 |
June | 965.15 | 397.32 | 567.83 | 1037.98 | 311.53 | 0.00 | 0.00 | 0.00 |
July | 982.96 | 433.39 | 549.57 | 1099.25 | 298.45 | 0.00 | 0.00 | 0.00 |
August | 825.62 | 357.47 | 468.15 | 928.91 | 331.16 | 0.00 | 0.00 | 0.00 |
September | 662.37 | 297.02 | 365.35 | 718.06 | 394.09 | 0.00 | 0.00 | 0.00 |
October | 353.35 | 127.06 | 226.29 | 284.95 | 547.61 | 0.00 | 0.00 | 0.00 |
November | 191.22 | 55.82 | 135.40 | 99.42 | 690.29 | 0.00 | 0.00 | 0.00 |
December | 108.24 | 22.84 | 85.40 | 30.32 | 850.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.75 | 219.76 | 332.99 | 530.51 | 521.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.24 | 22.84 | 85.40 | 30.32 | 298.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 982.96 | 433.39 | 567.83 | 1099.25 | 850.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.66 | 66.63 | 135.03 | 106.00 | 707.47 | 0.00 | 0.00 | 0.00 |
February | 357.05 | 150.76 | 206.29 | 258.35 | 689.47 | 0.00 | 0.00 | 0.00 |
March | 322.85 | 61.76 | 261.09 | 163.37 | 584.11 | 0.00 | 0.00 | 0.00 |
April | 761.78 | 302.59 | 459.20 | 742.81 | 480.72 | 0.00 | 0.00 | 0.00 |
May | 893.75 | 363.43 | 530.32 | 885.74 | 385.31 | 0.00 | 0.00 | 0.00 |
June | 965.15 | 397.32 | 567.83 | 1037.98 | 311.53 | 0.00 | 0.00 | 0.00 |
July | 982.96 | 433.39 | 549.57 | 1099.25 | 298.45 | 0.00 | 0.00 | 0.00 |
August | 825.62 | 357.47 | 468.15 | 928.91 | 331.16 | 0.00 | 0.00 | 0.00 |
September | 662.37 | 297.02 | 365.35 | 718.06 | 394.09 | 0.00 | 0.00 | 0.00 |
October | 353.35 | 127.06 | 226.29 | 284.95 | 547.61 | 0.00 | 0.00 | 0.00 |
November | 191.22 | 55.82 | 135.40 | 99.42 | 690.29 | 0.00 | 0.00 | 0.00 |
December | 108.24 | 22.84 | 85.40 | 30.32 | 850.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.75 | 219.76 | 332.99 | 530.51 | 521.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.24 | 22.84 | 85.40 | 30.32 | 298.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 982.96 | 433.39 | 567.83 | 1099.25 | 850.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.66 | 66.63 | 135.03 | 106.00 | 707.46 | 0.00 | 0.00 | 0.00 |
February | 357.05 | 150.76 | 206.29 | 258.35 | 689.46 | 0.00 | 0.00 | 0.00 |
March | 322.85 | 61.76 | 261.09 | 163.37 | 584.10 | 0.00 | 0.00 | 0.00 |
April | 761.77 | 302.58 | 459.19 | 742.79 | 480.71 | 0.00 | 0.00 | 0.00 |
May | 893.73 | 363.42 | 530.31 | 885.73 | 385.30 | 0.00 | 0.00 | 0.00 |
June | 965.13 | 397.31 | 567.82 | 1037.97 | 311.52 | 0.00 | 0.00 | 0.00 |
July | 982.94 | 433.38 | 549.56 | 1099.23 | 298.45 | 0.00 | 0.00 | 0.00 |
August | 825.61 | 357.47 | 468.14 | 928.89 | 331.15 | 0.00 | 0.00 | 0.00 |
September | 662.36 | 297.02 | 365.34 | 718.05 | 394.08 | 0.00 | 0.00 | 0.00 |
October | 353.34 | 127.06 | 226.28 | 284.95 | 547.60 | 0.00 | 0.00 | 0.00 |
November | 191.22 | 55.82 | 135.40 | 99.42 | 690.28 | 0.00 | 0.00 | 0.00 |
December | 108.23 | 22.84 | 85.39 | 30.32 | 850.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.74 | 219.76 | 332.98 | 530.50 | 521.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.23 | 22.84 | 85.39 | 30.32 | 298.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 982.94 | 433.38 | 567.82 | 1099.23 | 850.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.56 | 0.00 | 456.56 | 28.34 | 2807.03 | 0.00 | 0.00 | 0.00 |
February | 712.93 | 0.00 | 712.93 | 95.48 | 2625.66 | 0.00 | 0.00 | 0.00 |
March | 986.57 | 0.00 | 986.57 | 304.89 | 2201.35 | 0.00 | 0.00 | 0.00 |
April | 1606.29 | 7.19 | 1599.10 | 990.42 | 1794.15 | 0.00 | 0.00 | 0.00 |
May | 2008.27 | 96.89 | 1911.38 | 1259.47 | 1440.75 | 0.00 | 0.00 | 0.00 |
June | 2220.02 | 139.21 | 2080.81 | 1817.95 | 1136.11 | 0.00 | 0.00 | 0.00 |
July | 2105.81 | 120.06 | 1985.74 | 1848.45 | 1046.32 | 0.00 | 0.00 | 0.00 |
August | 1655.27 | 25.93 | 1629.34 | 1423.69 | 1165.03 | 0.00 | 0.00 | 0.00 |
September | 1259.89 | 0.28 | 1259.61 | 926.79 | 1553.01 | 0.00 | 0.00 | 0.00 |
October | 807.33 | 0.00 | 807.33 | 318.84 | 2060.19 | 0.00 | 0.00 | 0.00 |
November | 485.08 | 0.00 | 485.08 | 46.60 | 2493.67 | 0.00 | 0.00 | 0.00 |
December | 330.34 | 0.00 | 330.34 | 1.65 | 2986.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1221.80 | 32.68 | 1189.11 | 758.55 | 1939.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.34 | 0.00 | 330.34 | 1.65 | 1046.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2220.02 | 139.21 | 2080.81 | 1848.45 | 2986.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 622.12 | 249.91 | 372.21 | 349.04 | 1782.89 | 0.00 | 0.00 | 0.00 |
February | 927.69 | 342.69 | 584.99 | 578.61 | 1691.65 | 0.00 | 0.00 | 0.00 |
March | 969.45 | 191.04 | 778.41 | 552.77 | 1414.13 | 0.00 | 0.00 | 0.00 |
April | 2603.06 | 1223.20 | 1379.87 | 2661.75 | 1166.39 | 0.00 | 0.00 | 0.00 |
May | 2737.04 | 1193.58 | 1543.46 | 2720.89 | 1004.40 | 0.00 | 0.00 | 0.00 |
June | 2709.17 | 1082.02 | 1627.15 | 2882.00 | 786.03 | 0.00 | 0.00 | 0.00 |
July | 2765.53 | 1175.35 | 1590.18 | 3072.95 | 729.08 | 0.00 | 0.00 | 0.00 |
August | 2619.73 | 1251.68 | 1368.05 | 3001.79 | 791.37 | 0.00 | 0.00 | 0.00 |
September | 2359.16 | 1254.49 | 1104.67 | 2605.32 | 1011.77 | 0.00 | 0.00 | 0.00 |
October | 1138.80 | 471.95 | 666.85 | 972.90 | 1350.00 | 0.00 | 0.00 | 0.00 |
November | 593.69 | 202.34 | 391.35 | 326.93 | 1609.12 | 0.00 | 0.00 | 0.00 |
December | 440.00 | 163.58 | 276.41 | 217.81 | 1910.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1709.59 | 734.43 | 975.16 | 1665.79 | 1268.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.00 | 163.58 | 276.41 | 217.81 | 729.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2765.53 | 1254.49 | 1627.15 | 3072.95 | 1910.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2592.02 | 1677.92 | 914.10 | 2508.96 | 2623.13 | 0.00 | 0.00 | 0.00 |
February | 3165.67 | 1931.74 | 1233.94 | 3150.09 | 2584.46 | 0.00 | 0.00 | 0.00 |
March | 1957.23 | 569.86 | 1387.37 | 1526.80 | 2174.78 | 0.00 | 0.00 | 0.00 |
April | 4064.34 | 1837.03 | 2227.31 | 4550.02 | 1913.33 | 0.00 | 0.00 | 0.00 |
May | 3361.59 | 1094.42 | 2267.16 | 3467.38 | 1652.64 | 0.00 | 0.00 | 0.00 |
June | 3096.74 | 749.59 | 2347.15 | 3335.25 | 1272.11 | 0.00 | 0.00 | 0.00 |
July | 3355.26 | 1050.74 | 2304.52 | 3898.62 | 1185.19 | 0.00 | 0.00 | 0.00 |
August | 3931.63 | 1768.59 | 2163.04 | 4848.58 | 1293.78 | 0.00 | 0.00 | 0.00 |
September | 4646.16 | 2721.80 | 1924.36 | 5669.50 | 1646.98 | 0.00 | 0.00 | 0.00 |
October | 3192.10 | 1865.64 | 1326.46 | 3459.66 | 2099.73 | 0.00 | 0.00 | 0.00 |
November | 2263.20 | 1376.76 | 886.44 | 2204.46 | 2452.41 | 0.00 | 0.00 | 0.00 |
December | 1793.79 | 1149.29 | 644.50 | 1692.61 | 2886.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3113.54 | 1477.03 | 1636.52 | 3354.69 | 1978.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1793.79 | 569.86 | 644.50 | 1526.80 | 1185.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4646.16 | 2721.80 | 2347.15 | 5669.50 | 2886.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.98 | 199.89 | 405.09 | 345.88 | 1848.86 | 0.00 | 0.00 | 0.00 |
February | 1071.15 | 452.27 | 618.87 | 818.43 | 1784.41 | 0.00 | 0.00 | 0.00 |
March | 968.55 | 185.28 | 783.26 | 547.62 | 1472.82 | 0.00 | 0.00 | 0.00 |
April | 2285.32 | 907.75 | 1377.57 | 2284.51 | 1269.82 | 0.00 | 0.00 | 0.00 |
May | 2681.21 | 1090.27 | 1590.94 | 2669.87 | 1090.04 | 0.00 | 0.00 | 0.00 |
June | 2895.42 | 1191.93 | 1703.48 | 3130.36 | 863.62 | 0.00 | 0.00 | 0.00 |
July | 2948.86 | 1300.16 | 1648.70 | 3332.85 | 808.51 | 0.00 | 0.00 | 0.00 |
August | 2476.84 | 1072.40 | 1404.44 | 2828.41 | 879.77 | 0.00 | 0.00 | 0.00 |
September | 1987.09 | 891.05 | 1096.03 | 2173.70 | 1103.77 | 0.00 | 0.00 | 0.00 |
October | 1060.03 | 381.18 | 678.85 | 895.96 | 1425.58 | 0.00 | 0.00 | 0.00 |
November | 573.65 | 167.46 | 406.20 | 331.59 | 1698.97 | 0.00 | 0.00 | 0.00 |
December | 324.70 | 68.52 | 256.19 | 111.63 | 2030.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1658.24 | 659.28 | 998.95 | 1625.26 | 1354.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.70 | 68.52 | 256.19 | 111.63 | 808.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2948.86 | 1300.16 | 1703.48 | 3332.85 | 2030.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.56 | 0.00 | 456.56 | 47.65 | 2529.59 | 0.00 | 0.00 | 0.00 |
February | 712.93 | 0.00 | 712.93 | 139.77 | 2372.84 | 0.00 | 0.00 | 0.00 |
March | 986.57 | 0.00 | 986.57 | 363.45 | 1996.60 | 0.00 | 0.00 | 0.00 |
April | 1606.29 | 7.19 | 1599.10 | 1032.81 | 1682.11 | 0.00 | 0.00 | 0.00 |
May | 2008.27 | 96.89 | 1911.38 | 1308.83 | 1361.25 | 0.00 | 0.00 | 0.00 |
June | 2220.02 | 139.21 | 2080.81 | 1830.94 | 1098.89 | 0.00 | 0.00 | 0.00 |
July | 2105.81 | 120.06 | 1985.74 | 1857.83 | 1015.52 | 0.00 | 0.00 | 0.00 |
August | 1655.27 | 25.93 | 1629.34 | 1432.81 | 1127.39 | 0.00 | 0.00 | 0.00 |
September | 1259.89 | 0.28 | 1259.61 | 960.88 | 1461.42 | 0.00 | 0.00 | 0.00 |
October | 807.33 | 0.00 | 807.33 | 373.66 | 1844.92 | 0.00 | 0.00 | 0.00 |
November | 485.08 | 0.00 | 485.08 | 71.75 | 2220.91 | 0.00 | 0.00 | 0.00 |
December | 330.34 | 0.00 | 330.34 | 9.33 | 2711.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1221.80 | 32.68 | 1189.11 | 789.06 | 1782.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.34 | 0.00 | 330.34 | 9.33 | 1015.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2220.02 | 139.21 | 2080.81 | 1857.83 | 2711.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 622.12 | 249.91 | 372.21 | 380.61 | 1600.01 | 0.00 | 0.00 | 0.00 |
February | 927.69 | 342.69 | 584.99 | 624.79 | 1524.49 | 0.00 | 0.00 | 0.00 |
March | 969.45 | 191.04 | 778.41 | 606.29 | 1281.42 | 0.00 | 0.00 | 0.00 |
April | 2603.06 | 1223.20 | 1379.87 | 2688.50 | 1105.07 | 0.00 | 0.00 | 0.00 |
May | 2737.04 | 1193.58 | 1543.46 | 2744.59 | 957.89 | 0.00 | 0.00 | 0.00 |
June | 2709.17 | 1082.02 | 1627.15 | 2889.68 | 763.72 | 0.00 | 0.00 | 0.00 |
July | 2765.53 | 1175.35 | 1590.18 | 3077.40 | 710.78 | 0.00 | 0.00 | 0.00 |
August | 2619.73 | 1251.68 | 1368.05 | 3007.29 | 770.81 | 0.00 | 0.00 | 0.00 |
September | 2359.16 | 1254.49 | 1104.67 | 2625.45 | 963.90 | 0.00 | 0.00 | 0.00 |
October | 1138.80 | 471.95 | 666.85 | 1013.84 | 1214.87 | 0.00 | 0.00 | 0.00 |
November | 593.69 | 202.34 | 391.35 | 358.50 | 1427.96 | 0.00 | 0.00 | 0.00 |
December | 440.00 | 163.58 | 276.41 | 238.18 | 1732.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1709.59 | 734.43 | 975.16 | 1691.70 | 1169.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.00 | 163.58 | 276.41 | 238.18 | 710.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2765.53 | 1254.49 | 1627.15 | 3077.40 | 1732.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2592.02 | 1677.92 | 914.10 | 2573.58 | 2368.31 | 0.00 | 0.00 | 0.00 |
February | 3165.67 | 1931.74 | 1233.94 | 3216.93 | 2353.09 | 0.00 | 0.00 | 0.00 |
March | 1957.23 | 569.86 | 1387.37 | 1591.45 | 1980.99 | 0.00 | 0.00 | 0.00 |
April | 4064.34 | 1837.03 | 2227.31 | 4575.39 | 1813.54 | 0.00 | 0.00 | 0.00 |
May | 3361.59 | 1094.42 | 2267.16 | 3492.10 | 1570.12 | 0.00 | 0.00 | 0.00 |
June | 3096.74 | 749.59 | 2347.15 | 3340.69 | 1232.07 | 0.00 | 0.00 | 0.00 |
July | 3355.26 | 1050.74 | 2304.52 | 3899.29 | 1151.50 | 0.00 | 0.00 | 0.00 |
August | 3931.63 | 1768.59 | 2163.04 | 4846.24 | 1257.92 | 0.00 | 0.00 | 0.00 |
September | 4646.16 | 2721.80 | 1924.36 | 5684.83 | 1571.11 | 0.00 | 0.00 | 0.00 |
October | 3192.10 | 1865.64 | 1326.46 | 3507.66 | 1907.17 | 0.00 | 0.00 | 0.00 |
November | 2263.20 | 1376.76 | 886.44 | 2253.94 | 2198.52 | 0.00 | 0.00 | 0.00 |
December | 1793.79 | 1149.29 | 644.50 | 1737.37 | 2624.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3113.54 | 1477.03 | 1636.52 | 3388.49 | 1832.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1793.79 | 569.86 | 644.50 | 1591.45 | 1151.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4646.16 | 2721.80 | 2347.15 | 5684.83 | 2624.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.98 | 199.89 | 405.09 | 367.77 | 1688.32 | 0.00 | 0.00 | 0.00 |
February | 1071.15 | 452.27 | 618.87 | 847.23 | 1643.17 | 0.00 | 0.00 | 0.00 |
March | 968.55 | 185.28 | 783.26 | 582.77 | 1355.59 | 0.00 | 0.00 | 0.00 |
April | 2285.32 | 907.75 | 1377.57 | 2302.07 | 1207.29 | 0.00 | 0.00 | 0.00 |
May | 2681.21 | 1090.27 | 1590.94 | 2683.35 | 1042.18 | 0.00 | 0.00 | 0.00 |
June | 2895.42 | 1191.93 | 1703.48 | 3126.98 | 839.36 | 0.00 | 0.00 | 0.00 |
July | 2948.86 | 1300.16 | 1648.70 | 3327.86 | 787.38 | 0.00 | 0.00 | 0.00 |
August | 2476.84 | 1072.40 | 1404.44 | 2824.29 | 856.46 | 0.00 | 0.00 | 0.00 |
September | 1987.09 | 891.05 | 1096.03 | 2185.60 | 1053.64 | 0.00 | 0.00 | 0.00 |
October | 1060.03 | 381.18 | 678.85 | 924.90 | 1305.63 | 0.00 | 0.00 | 0.00 |
November | 573.65 | 167.46 | 406.20 | 350.81 | 1542.50 | 0.00 | 0.00 | 0.00 |
December | 324.70 | 68.52 | 256.19 | 121.37 | 1874.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1658.24 | 659.28 | 998.95 | 1639.69 | 1264.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.70 | 68.52 | 256.19 | 121.37 | 787.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2948.86 | 1300.16 | 1703.48 | 3327.86 | 1874.05 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244571E+09 | 0.00 | 0.244571E+09 | 7298163.48 | 0.169963E+10 |
February | 0.344949E+09 | 0.00 | 0.344949E+09 | 26083700.22 | 0.143196E+10 |
March | 0.528493E+09 | 0.00 | 0.528493E+09 | 0.130319E+09 | 0.132673E+10 |
April | 0.832711E+09 | 3726864.40 | 0.828984E+09 | 0.488061E+09 | 0.100957E+10 |
May | 0.107580E+10 | 51902359.29 | 0.102390E+10 | 0.657395E+09 | 0.810855E+09 |
June | 0.115087E+10 | 72167087.81 | 0.107870E+10 | 0.933638E+09 | 0.615426E+09 |
July | 0.112805E+10 | 64316260.84 | 0.106374E+10 | 0.971895E+09 | 0.590188E+09 |
August | 0.886707E+09 | 13892506.25 | 0.872815E+09 | 0.742950E+09 | 0.665233E+09 |
September | 0.653135E+09 | 144525.63 | 0.652990E+09 | 0.462905E+09 | 0.855656E+09 |
October | 0.432475E+09 | 0.00 | 0.432475E+09 | 0.144524E+09 | 0.123052E+10 |
November | 0.251471E+09 | 0.00 | 0.251471E+09 | 12058059.93 | 0.149827E+10 |
December | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.53 | 0.187251E+10 |
Annual Sum or Average | 0.770620E+10 | 0.206150E+09 | 0.750005E+10 | 0.457713E+10 | 0.136065E+11 |
Minimum of Months | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.53 | 0.590188E+09 |
Maximum of Months | 0.115087E+10 | 72167087.81 | 0.107870E+10 | 0.971895E+09 | 0.187251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244571E+09 | 0.00 | 0.244571E+09 | 7298117.99 | 0.169963E+10 |
February | 0.344949E+09 | 0.00 | 0.344949E+09 | 26083564.88 | 0.143196E+10 |
March | 0.528493E+09 | 0.00 | 0.528493E+09 | 0.130319E+09 | 0.132673E+10 |
April | 0.832710E+09 | 3726859.92 | 0.828983E+09 | 0.488060E+09 | 0.100957E+10 |
May | 0.107580E+10 | 51902297.01 | 0.102390E+10 | 0.657394E+09 | 0.810855E+09 |
June | 0.115087E+10 | 72167001.21 | 0.107870E+10 | 0.933636E+09 | 0.615426E+09 |
July | 0.112805E+10 | 64316183.67 | 0.106374E+10 | 0.971894E+09 | 0.590188E+09 |
August | 0.886707E+09 | 13892489.58 | 0.872814E+09 | 0.742950E+09 | 0.665233E+09 |
September | 0.653134E+09 | 144525.46 | 0.652990E+09 | 0.462904E+09 | 0.855655E+09 |
October | 0.432475E+09 | 0.00 | 0.432475E+09 | 0.144523E+09 | 0.123052E+10 |
November | 0.251471E+09 | 0.00 | 0.251471E+09 | 12057993.55 | 0.149827E+10 |
December | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.21 | 0.187251E+10 |
Annual Sum or Average | 0.770619E+10 | 0.206149E+09 | 0.750004E+10 | 0.457713E+10 | 0.136065E+11 |
Minimum of Months | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.21 | 0.590188E+09 |
Maximum of Months | 0.115087E+10 | 72167001.21 | 0.107870E+10 | 0.971894E+09 | 0.187251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244571E+09 | 0.00 | 0.244571E+09 | 7298163.48 | 0.169963E+10 |
February | 0.344949E+09 | 0.00 | 0.344949E+09 | 26083700.22 | 0.143196E+10 |
March | 0.528493E+09 | 0.00 | 0.528493E+09 | 0.130319E+09 | 0.132673E+10 |
April | 0.832711E+09 | 3726864.40 | 0.828984E+09 | 0.488061E+09 | 0.100957E+10 |
May | 0.107580E+10 | 51902359.29 | 0.102390E+10 | 0.657395E+09 | 0.810855E+09 |
June | 0.115087E+10 | 72167087.81 | 0.107870E+10 | 0.933638E+09 | 0.615426E+09 |
July | 0.112805E+10 | 64316260.84 | 0.106374E+10 | 0.971895E+09 | 0.590188E+09 |
August | 0.886707E+09 | 13892506.25 | 0.872815E+09 | 0.742950E+09 | 0.665233E+09 |
September | 0.653135E+09 | 144525.63 | 0.652990E+09 | 0.462905E+09 | 0.855656E+09 |
October | 0.432475E+09 | 0.00 | 0.432475E+09 | 0.144524E+09 | 0.123052E+10 |
November | 0.251471E+09 | 0.00 | 0.251471E+09 | 12058059.93 | 0.149827E+10 |
December | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.53 | 0.187251E+10 |
Annual Sum or Average | 0.770620E+10 | 0.206150E+09 | 0.750005E+10 | 0.457713E+10 | 0.136065E+11 |
Minimum of Months | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.53 | 0.590188E+09 |
Maximum of Months | 0.115087E+10 | 72167087.81 | 0.107870E+10 | 0.971895E+09 | 0.187251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244571E+09 | 0.00 | 0.244571E+09 | 7298117.99 | 0.169963E+10 |
February | 0.344949E+09 | 0.00 | 0.344949E+09 | 26083564.88 | 0.143196E+10 |
March | 0.528493E+09 | 0.00 | 0.528493E+09 | 0.130319E+09 | 0.132673E+10 |
April | 0.832710E+09 | 3726859.92 | 0.828983E+09 | 0.488060E+09 | 0.100957E+10 |
May | 0.107580E+10 | 51902297.01 | 0.102390E+10 | 0.657394E+09 | 0.810855E+09 |
June | 0.115087E+10 | 72167001.21 | 0.107870E+10 | 0.933636E+09 | 0.615426E+09 |
July | 0.112805E+10 | 64316183.67 | 0.106374E+10 | 0.971894E+09 | 0.590188E+09 |
August | 0.886707E+09 | 13892489.58 | 0.872814E+09 | 0.742950E+09 | 0.665233E+09 |
September | 0.653134E+09 | 144525.46 | 0.652990E+09 | 0.462904E+09 | 0.855655E+09 |
October | 0.432475E+09 | 0.00 | 0.432475E+09 | 0.144523E+09 | 0.123052E+10 |
November | 0.251471E+09 | 0.00 | 0.251471E+09 | 12057993.55 | 0.149827E+10 |
December | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.21 | 0.187251E+10 |
Annual Sum or Average | 0.770619E+10 | 0.206149E+09 | 0.750004E+10 | 0.457713E+10 | 0.136065E+11 |
Minimum of Months | 0.176959E+09 | 0.00 | 0.176959E+09 | 6141.21 | 0.590188E+09 |
Maximum of Months | 0.115087E+10 | 72167001.21 | 0.107870E+10 | 0.971894E+09 | 0.187251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244561E+09 | 0.00 | 0.244561E+09 | 7297869.34 | 0.169956E+10 |
February | 0.344935E+09 | 0.00 | 0.344935E+09 | 26082648.94 | 0.143190E+10 |
March | 0.528472E+09 | 0.00 | 0.528472E+09 | 0.130314E+09 | 0.132668E+10 |
April | 0.832677E+09 | 3726714.19 | 0.828950E+09 | 0.488041E+09 | 0.100953E+10 |
May | 0.107576E+10 | 51900267.39 | 0.102386E+10 | 0.657368E+09 | 0.810823E+09 |
June | 0.115083E+10 | 72164179.15 | 0.107866E+10 | 0.933600E+09 | 0.615401E+09 |
July | 0.112801E+10 | 64313668.61 | 0.106369E+10 | 0.971856E+09 | 0.590164E+09 |
August | 0.886672E+09 | 13891946.32 | 0.872780E+09 | 0.742920E+09 | 0.665206E+09 |
September | 0.653109E+09 | 144519.81 | 0.652964E+09 | 0.462886E+09 | 0.855621E+09 |
October | 0.432458E+09 | 0.00 | 0.432458E+09 | 0.144518E+09 | 0.123047E+10 |
November | 0.251461E+09 | 0.00 | 0.251461E+09 | 12057573.94 | 0.149821E+10 |
December | 0.176952E+09 | 0.00 | 0.176952E+09 | 6141.28 | 0.187243E+10 |
Annual Sum or Average | 0.770589E+10 | 0.206141E+09 | 0.749975E+10 | 0.457695E+10 | 0.136060E+11 |
Minimum of Months | 0.176952E+09 | 0.00 | 0.176952E+09 | 6141.28 | 0.590164E+09 |
Maximum of Months | 0.115083E+10 | 72164179.15 | 0.107866E+10 | 0.971856E+09 | 0.187243E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555434E+09 | 0.223119E+09 | 0.332315E+09 | 0.292316E+09 | 0.175645E+10 |
February | 0.748095E+09 | 0.276352E+09 | 0.471743E+09 | 0.447137E+09 | 0.148360E+10 |
March | 0.865537E+09 | 0.170566E+09 | 0.694972E+09 | 0.469451E+09 | 0.136594E+10 |
April | 0.224907E+10 | 0.105685E+10 | 0.119222E+10 | 0.230870E+10 | 0.104182E+10 |
May | 0.244365E+10 | 0.106564E+10 | 0.137802E+10 | 0.244747E+10 | 0.920459E+09 |
June | 0.234075E+10 | 0.934871E+09 | 0.140587E+10 | 0.250985E+10 | 0.692462E+09 |
July | 0.246909E+10 | 0.104936E+10 | 0.141973E+10 | 0.276353E+10 | 0.661743E+09 |
August | 0.233892E+10 | 0.111751E+10 | 0.122141E+10 | 0.269782E+10 | 0.717288E+09 |
September | 0.203833E+10 | 0.108389E+10 | 0.954440E+09 | 0.226443E+10 | 0.898391E+09 |
October | 0.101673E+10 | 0.421358E+09 | 0.595369E+09 | 0.858179E+09 | 0.129421E+10 |
November | 0.512952E+09 | 0.174821E+09 | 0.338130E+09 | 0.266628E+09 | 0.154549E+10 |
December | 0.392832E+09 | 0.146049E+09 | 0.246782E+09 | 0.176486E+09 | 0.191322E+10 |
Annual Sum or Average | 0.179714E+11 | 0.772039E+10 | 0.102510E+11 | 0.175020E+11 | 0.142911E+11 |
Minimum of Months | 0.392832E+09 | 0.146049E+09 | 0.246782E+09 | 0.176486E+09 | 0.661743E+09 |
Maximum of Months | 0.246909E+10 | 0.111751E+10 | 0.141973E+10 | 0.276353E+10 | 0.191322E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555434E+09 | 0.223119E+09 | 0.332315E+09 | 0.292316E+09 | 0.175645E+10 |
February | 0.748095E+09 | 0.276352E+09 | 0.471743E+09 | 0.447137E+09 | 0.148360E+10 |
March | 0.865537E+09 | 0.170566E+09 | 0.694972E+09 | 0.469451E+09 | 0.136594E+10 |
April | 0.224907E+10 | 0.105685E+10 | 0.119222E+10 | 0.230870E+10 | 0.104182E+10 |
May | 0.244365E+10 | 0.106564E+10 | 0.137802E+10 | 0.244747E+10 | 0.920459E+09 |
June | 0.234075E+10 | 0.934871E+09 | 0.140587E+10 | 0.250985E+10 | 0.692462E+09 |
July | 0.246909E+10 | 0.104936E+10 | 0.141973E+10 | 0.276353E+10 | 0.661743E+09 |
August | 0.233892E+10 | 0.111751E+10 | 0.122141E+10 | 0.269782E+10 | 0.717288E+09 |
September | 0.203833E+10 | 0.108389E+10 | 0.954440E+09 | 0.226443E+10 | 0.898391E+09 |
October | 0.101673E+10 | 0.421358E+09 | 0.595369E+09 | 0.858179E+09 | 0.129421E+10 |
November | 0.512952E+09 | 0.174821E+09 | 0.338130E+09 | 0.266628E+09 | 0.154549E+10 |
December | 0.392832E+09 | 0.146049E+09 | 0.246782E+09 | 0.176486E+09 | 0.191322E+10 |
Annual Sum or Average | 0.179714E+11 | 0.772039E+10 | 0.102510E+11 | 0.175020E+11 | 0.142911E+11 |
Minimum of Months | 0.392832E+09 | 0.146049E+09 | 0.246782E+09 | 0.176486E+09 | 0.661743E+09 |
Maximum of Months | 0.246909E+10 | 0.111751E+10 | 0.141973E+10 | 0.276353E+10 | 0.191322E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555423E+09 | 0.223114E+09 | 0.332309E+09 | 0.292311E+09 | 0.175641E+10 |
February | 0.748081E+09 | 0.276347E+09 | 0.471735E+09 | 0.447129E+09 | 0.148357E+10 |
March | 0.865522E+09 | 0.170563E+09 | 0.694959E+09 | 0.469442E+09 | 0.136591E+10 |
April | 0.224903E+10 | 0.105683E+10 | 0.119220E+10 | 0.230866E+10 | 0.104180E+10 |
May | 0.244361E+10 | 0.106562E+10 | 0.137799E+10 | 0.244742E+10 | 0.920442E+09 |
June | 0.234070E+10 | 0.934854E+09 | 0.140585E+10 | 0.250981E+10 | 0.692449E+09 |
July | 0.246904E+10 | 0.104934E+10 | 0.141970E+10 | 0.276348E+10 | 0.661731E+09 |
August | 0.233888E+10 | 0.111749E+10 | 0.122138E+10 | 0.269777E+10 | 0.717275E+09 |
September | 0.203830E+10 | 0.108387E+10 | 0.954423E+09 | 0.226439E+10 | 0.898374E+09 |
October | 0.101671E+10 | 0.421350E+09 | 0.595359E+09 | 0.858164E+09 | 0.129419E+10 |
November | 0.512943E+09 | 0.174818E+09 | 0.338124E+09 | 0.266623E+09 | 0.154547E+10 |
December | 0.392825E+09 | 0.146047E+09 | 0.246778E+09 | 0.176482E+09 | 0.191319E+10 |
Annual Sum or Average | 0.179711E+11 | 0.772025E+10 | 0.102508E+11 | 0.175017E+11 | 0.142908E+11 |
Minimum of Months | 0.392825E+09 | 0.146047E+09 | 0.246778E+09 | 0.176482E+09 | 0.661731E+09 |
Maximum of Months | 0.246904E+10 | 0.111749E+10 | 0.141970E+10 | 0.276348E+10 | 0.191319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138851E+10 | 0.898838E+09 | 0.489670E+09 | 0.134008E+10 | 0.145709E+10 |
February | 0.153170E+10 | 0.934662E+09 | 0.597034E+09 | 0.152325E+10 | 0.129018E+10 |
March | 0.104846E+10 | 0.305264E+09 | 0.743195E+09 | 0.807302E+09 | 0.122520E+10 |
April | 0.210698E+10 | 0.952330E+09 | 0.115465E+10 | 0.236452E+10 | 0.102242E+10 |
May | 0.180076E+10 | 0.586268E+09 | 0.121449E+10 | 0.186747E+10 | 0.899537E+09 |
June | 0.160537E+10 | 0.388593E+09 | 0.121678E+10 | 0.173438E+10 | 0.675170E+09 |
July | 0.179737E+10 | 0.562865E+09 | 0.123450E+10 | 0.209163E+10 | 0.652197E+09 |
August | 0.210612E+10 | 0.947411E+09 | 0.115871E+10 | 0.260357E+10 | 0.711820E+09 |
September | 0.240860E+10 | 0.141100E+10 | 0.997601E+09 | 0.295496E+10 | 0.862523E+09 |
October | 0.170997E+10 | 0.999398E+09 | 0.710568E+09 | 0.185648E+10 | 0.116295E+10 |
November | 0.117326E+10 | 0.713722E+09 | 0.459535E+09 | 0.113794E+10 | 0.134326E+10 |
December | 0.960911E+09 | 0.615660E+09 | 0.345251E+09 | 0.894312E+09 | 0.165722E+10 |
Annual Sum or Average | 0.196380E+11 | 0.931601E+10 | 0.103220E+11 | 0.211759E+11 | 0.129596E+11 |
Minimum of Months | 0.960911E+09 | 0.305264E+09 | 0.345251E+09 | 0.807302E+09 | 0.652197E+09 |
Maximum of Months | 0.240860E+10 | 0.141100E+10 | 0.123450E+10 | 0.295496E+10 | 0.165722E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138851E+10 | 0.898837E+09 | 0.489669E+09 | 0.134008E+10 | 0.145709E+10 |
February | 0.153170E+10 | 0.934661E+09 | 0.597034E+09 | 0.152325E+10 | 0.129018E+10 |
March | 0.104846E+10 | 0.305264E+09 | 0.743195E+09 | 0.807300E+09 | 0.122520E+10 |
April | 0.210698E+10 | 0.952329E+09 | 0.115465E+10 | 0.236452E+10 | 0.102242E+10 |
May | 0.180075E+10 | 0.586267E+09 | 0.121449E+10 | 0.186746E+10 | 0.899537E+09 |
June | 0.160537E+10 | 0.388592E+09 | 0.121678E+10 | 0.173438E+10 | 0.675170E+09 |
July | 0.179737E+10 | 0.562865E+09 | 0.123450E+10 | 0.209162E+10 | 0.652197E+09 |
August | 0.210612E+10 | 0.947410E+09 | 0.115871E+10 | 0.260357E+10 | 0.711820E+09 |
September | 0.240859E+10 | 0.141099E+10 | 0.997600E+09 | 0.295496E+10 | 0.862522E+09 |
October | 0.170996E+10 | 0.999397E+09 | 0.710567E+09 | 0.185647E+10 | 0.116295E+10 |
November | 0.117326E+10 | 0.713721E+09 | 0.459534E+09 | 0.113794E+10 | 0.134326E+10 |
December | 0.960910E+09 | 0.615659E+09 | 0.345250E+09 | 0.894310E+09 | 0.165722E+10 |
Annual Sum or Average | 0.196380E+11 | 0.931600E+10 | 0.103220E+11 | 0.211759E+11 | 0.129596E+11 |
Minimum of Months | 0.960910E+09 | 0.305264E+09 | 0.345250E+09 | 0.807300E+09 | 0.652197E+09 |
Maximum of Months | 0.240859E+10 | 0.141099E+10 | 0.123450E+10 | 0.295496E+10 | 0.165722E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138851E+10 | 0.898838E+09 | 0.489670E+09 | 0.134008E+10 | 0.145709E+10 |
February | 0.153170E+10 | 0.934662E+09 | 0.597034E+09 | 0.152325E+10 | 0.129018E+10 |
March | 0.104846E+10 | 0.305264E+09 | 0.743195E+09 | 0.807302E+09 | 0.122520E+10 |
April | 0.210698E+10 | 0.952330E+09 | 0.115465E+10 | 0.236452E+10 | 0.102242E+10 |
May | 0.180076E+10 | 0.586268E+09 | 0.121449E+10 | 0.186747E+10 | 0.899537E+09 |
June | 0.160537E+10 | 0.388593E+09 | 0.121678E+10 | 0.173438E+10 | 0.675170E+09 |
July | 0.179737E+10 | 0.562865E+09 | 0.123450E+10 | 0.209163E+10 | 0.652197E+09 |
August | 0.210612E+10 | 0.947411E+09 | 0.115871E+10 | 0.260357E+10 | 0.711820E+09 |
September | 0.240860E+10 | 0.141100E+10 | 0.997601E+09 | 0.295496E+10 | 0.862523E+09 |
October | 0.170997E+10 | 0.999398E+09 | 0.710568E+09 | 0.185648E+10 | 0.116295E+10 |
November | 0.117326E+10 | 0.713722E+09 | 0.459535E+09 | 0.113794E+10 | 0.134326E+10 |
December | 0.960911E+09 | 0.615660E+09 | 0.345251E+09 | 0.894312E+09 | 0.165722E+10 |
Annual Sum or Average | 0.196380E+11 | 0.931601E+10 | 0.103220E+11 | 0.211759E+11 | 0.129596E+11 |
Minimum of Months | 0.960911E+09 | 0.305264E+09 | 0.345251E+09 | 0.807302E+09 | 0.652197E+09 |
Maximum of Months | 0.240860E+10 | 0.141100E+10 | 0.123450E+10 | 0.295496E+10 | 0.165722E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138851E+10 | 0.898837E+09 | 0.489669E+09 | 0.134008E+10 | 0.145709E+10 |
February | 0.153170E+10 | 0.934661E+09 | 0.597034E+09 | 0.152325E+10 | 0.129018E+10 |
March | 0.104846E+10 | 0.305264E+09 | 0.743195E+09 | 0.807300E+09 | 0.122520E+10 |
April | 0.210698E+10 | 0.952329E+09 | 0.115465E+10 | 0.236452E+10 | 0.102242E+10 |
May | 0.180075E+10 | 0.586267E+09 | 0.121449E+10 | 0.186746E+10 | 0.899537E+09 |
June | 0.160537E+10 | 0.388592E+09 | 0.121678E+10 | 0.173438E+10 | 0.675170E+09 |
July | 0.179737E+10 | 0.562865E+09 | 0.123450E+10 | 0.209162E+10 | 0.652197E+09 |
August | 0.210612E+10 | 0.947410E+09 | 0.115871E+10 | 0.260357E+10 | 0.711820E+09 |
September | 0.240859E+10 | 0.141099E+10 | 0.997600E+09 | 0.295496E+10 | 0.862522E+09 |
October | 0.170996E+10 | 0.999397E+09 | 0.710567E+09 | 0.185647E+10 | 0.116295E+10 |
November | 0.117326E+10 | 0.713721E+09 | 0.459534E+09 | 0.113794E+10 | 0.134326E+10 |
December | 0.960910E+09 | 0.615659E+09 | 0.345250E+09 | 0.894310E+09 | 0.165722E+10 |
Annual Sum or Average | 0.196380E+11 | 0.931600E+10 | 0.103220E+11 | 0.211759E+11 | 0.129596E+11 |
Minimum of Months | 0.960910E+09 | 0.305264E+09 | 0.345250E+09 | 0.807300E+09 | 0.652197E+09 |
Maximum of Months | 0.240859E+10 | 0.141099E+10 | 0.123450E+10 | 0.295496E+10 | 0.165722E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138845E+10 | 0.898802E+09 | 0.489650E+09 | 0.134003E+10 | 0.145703E+10 |
February | 0.153164E+10 | 0.934625E+09 | 0.597010E+09 | 0.152319E+10 | 0.129013E+10 |
March | 0.104842E+10 | 0.305252E+09 | 0.743165E+09 | 0.807269E+09 | 0.122515E+10 |
April | 0.210689E+10 | 0.952292E+09 | 0.115460E+10 | 0.236443E+10 | 0.102238E+10 |
May | 0.180068E+10 | 0.586244E+09 | 0.121444E+10 | 0.186739E+10 | 0.899501E+09 |
June | 0.160530E+10 | 0.388577E+09 | 0.121673E+10 | 0.173431E+10 | 0.675143E+09 |
July | 0.179729E+10 | 0.562843E+09 | 0.123445E+10 | 0.209154E+10 | 0.652171E+09 |
August | 0.210603E+10 | 0.947373E+09 | 0.115866E+10 | 0.260346E+10 | 0.711791E+09 |
September | 0.240850E+10 | 0.141094E+10 | 0.997560E+09 | 0.295485E+10 | 0.862488E+09 |
October | 0.170990E+10 | 0.999358E+09 | 0.710539E+09 | 0.185640E+10 | 0.116291E+10 |
November | 0.117321E+10 | 0.713693E+09 | 0.459516E+09 | 0.113789E+10 | 0.134320E+10 |
December | 0.960872E+09 | 0.615635E+09 | 0.345237E+09 | 0.894276E+09 | 0.165715E+10 |
Annual Sum or Average | 0.196372E+11 | 0.931563E+10 | 0.103216E+11 | 0.211750E+11 | 0.129591E+11 |
Minimum of Months | 0.960872E+09 | 0.305252E+09 | 0.345237E+09 | 0.807269E+09 | 0.652171E+09 |
Maximum of Months | 0.240850E+10 | 0.141094E+10 | 0.123445E+10 | 0.295485E+10 | 0.165715E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540132E+09 | 0.178462E+09 | 0.361670E+09 | 0.283912E+09 | 0.189490E+10 |
February | 0.863783E+09 | 0.364717E+09 | 0.499066E+09 | 0.625009E+09 | 0.166796E+10 |
March | 0.864728E+09 | 0.165422E+09 | 0.699306E+09 | 0.437576E+09 | 0.156449E+10 |
April | 0.197454E+10 | 0.784303E+09 | 0.119023E+10 | 0.192536E+10 | 0.124603E+10 |
May | 0.239381E+10 | 0.973405E+09 | 0.142040E+10 | 0.237237E+10 | 0.103201E+10 |
June | 0.250167E+10 | 0.102984E+10 | 0.147183E+10 | 0.269046E+10 | 0.807487E+09 |
July | 0.263277E+10 | 0.116079E+10 | 0.147197E+10 | 0.294423E+10 | 0.799378E+09 |
August | 0.221135E+10 | 0.957452E+09 | 0.125390E+10 | 0.248799E+10 | 0.886970E+09 |
September | 0.171686E+10 | 0.769879E+09 | 0.946981E+09 | 0.186121E+10 | 0.102148E+10 |
October | 0.946408E+09 | 0.340324E+09 | 0.606084E+09 | 0.763218E+09 | 0.146673E+10 |
November | 0.495642E+09 | 0.144684E+09 | 0.350958E+09 | 0.257695E+09 | 0.178923E+10 |
December | 0.289899E+09 | 61175108.52 | 0.228724E+09 | 81213851.14 | 0.227816E+10 |
Annual Sum or Average | 0.174316E+11 | 0.693046E+10 | 0.105011E+11 | 0.167303E+11 | 0.164548E+11 |
Minimum of Months | 0.289899E+09 | 61175108.52 | 0.228724E+09 | 81213851.14 | 0.799378E+09 |
Maximum of Months | 0.263277E+10 | 0.116079E+10 | 0.147197E+10 | 0.294423E+10 | 0.227816E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540132E+09 | 0.178462E+09 | 0.361670E+09 | 0.283912E+09 | 0.189490E+10 |
February | 0.863783E+09 | 0.364717E+09 | 0.499066E+09 | 0.625009E+09 | 0.166796E+10 |
March | 0.864728E+09 | 0.165422E+09 | 0.699306E+09 | 0.437576E+09 | 0.156449E+10 |
April | 0.197454E+10 | 0.784303E+09 | 0.119023E+10 | 0.192536E+10 | 0.124603E+10 |
May | 0.239381E+10 | 0.973405E+09 | 0.142040E+10 | 0.237237E+10 | 0.103201E+10 |
June | 0.250167E+10 | 0.102984E+10 | 0.147183E+10 | 0.269046E+10 | 0.807487E+09 |
July | 0.263277E+10 | 0.116079E+10 | 0.147197E+10 | 0.294423E+10 | 0.799378E+09 |
August | 0.221135E+10 | 0.957452E+09 | 0.125390E+10 | 0.248799E+10 | 0.886970E+09 |
September | 0.171686E+10 | 0.769879E+09 | 0.946981E+09 | 0.186121E+10 | 0.102148E+10 |
October | 0.946408E+09 | 0.340324E+09 | 0.606084E+09 | 0.763218E+09 | 0.146673E+10 |
November | 0.495642E+09 | 0.144684E+09 | 0.350958E+09 | 0.257695E+09 | 0.178923E+10 |
December | 0.289899E+09 | 61175108.52 | 0.228724E+09 | 81213851.14 | 0.227816E+10 |
Annual Sum or Average | 0.174316E+11 | 0.693046E+10 | 0.105011E+11 | 0.167303E+11 | 0.164548E+11 |
Minimum of Months | 0.289899E+09 | 61175108.52 | 0.228724E+09 | 81213851.14 | 0.799378E+09 |
Maximum of Months | 0.263277E+10 | 0.116079E+10 | 0.147197E+10 | 0.294423E+10 | 0.227816E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540122E+09 | 0.178459E+09 | 0.361664E+09 | 0.283907E+09 | 0.189486E+10 |
February | 0.863767E+09 | 0.364710E+09 | 0.499057E+09 | 0.624998E+09 | 0.166793E+10 |
March | 0.864712E+09 | 0.165419E+09 | 0.699293E+09 | 0.437568E+09 | 0.156446E+10 |
April | 0.197450E+10 | 0.784289E+09 | 0.119021E+10 | 0.192532E+10 | 0.124601E+10 |
May | 0.239376E+10 | 0.973387E+09 | 0.142038E+10 | 0.237233E+10 | 0.103199E+10 |
June | 0.250162E+10 | 0.102982E+10 | 0.147180E+10 | 0.269041E+10 | 0.807473E+09 |
July | 0.263272E+10 | 0.116077E+10 | 0.147195E+10 | 0.294418E+10 | 0.799363E+09 |
August | 0.221131E+10 | 0.957434E+09 | 0.125387E+10 | 0.248795E+10 | 0.886953E+09 |
September | 0.171683E+10 | 0.769865E+09 | 0.946964E+09 | 0.186118E+10 | 0.102146E+10 |
October | 0.946390E+09 | 0.340318E+09 | 0.606073E+09 | 0.763204E+09 | 0.146670E+10 |
November | 0.495633E+09 | 0.144681E+09 | 0.350951E+09 | 0.257690E+09 | 0.178920E+10 |
December | 0.289894E+09 | 61173990.71 | 0.228720E+09 | 81212367.19 | 0.227812E+10 |
Annual Sum or Average | 0.174313E+11 | 0.693033E+10 | 0.105009E+11 | 0.167299E+11 | 0.164545E+11 |
Minimum of Months | 0.289894E+09 | 61173990.71 | 0.228720E+09 | 81212367.19 | 0.799363E+09 |
Maximum of Months | 0.263272E+10 | 0.116077E+10 | 0.147195E+10 | 0.294418E+10 | 0.227812E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122284E+10 | 0.00 | 0.122284E+10 | 75908459.93 | 0.751835E+10 |
February | 0.172472E+10 | 0.00 | 0.172472E+10 | 0.230974E+09 | 0.635200E+10 |
March | 0.264243E+10 | 0.00 | 0.264243E+10 | 0.816608E+09 | 0.589610E+10 |
April | 0.416350E+10 | 18634096.65 | 0.414487E+10 | 0.256717E+10 | 0.465045E+10 |
May | 0.537895E+10 | 0.259509E+09 | 0.511945E+10 | 0.337338E+10 | 0.385890E+10 |
June | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.471213E+10 | 0.294480E+10 |
July | 0.564019E+10 | 0.321577E+09 | 0.531862E+10 | 0.495088E+10 | 0.280247E+10 |
August | 0.443348E+10 | 69461691.30 | 0.436402E+10 | 0.381320E+10 | 0.312042E+10 |
September | 0.326564E+10 | 722619.41 | 0.326491E+10 | 0.240223E+10 | 0.402540E+10 |
October | 0.216235E+10 | 0.00 | 0.216235E+10 | 0.853987E+09 | 0.551802E+10 |
November | 0.125734E+10 | 0.00 | 0.125734E+10 | 0.120796E+09 | 0.646359E+10 |
December | 0.884787E+09 | 0.00 | 0.884787E+09 | 4428018.89 | 0.799957E+10 |
Annual Sum or Average | 0.385305E+11 | 0.103074E+10 | 0.374998E+11 | 0.239217E+11 | 0.611501E+11 |
Minimum of Months | 0.884787E+09 | 0.00 | 0.884787E+09 | 4428018.89 | 0.280247E+10 |
Maximum of Months | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.495088E+10 | 0.799957E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166628E+10 | 0.669349E+09 | 0.996935E+09 | 0.934878E+09 | 0.477530E+10 |
February | 0.224426E+10 | 0.829047E+09 | 0.141522E+10 | 0.139978E+10 | 0.409245E+10 |
March | 0.259659E+10 | 0.511692E+09 | 0.208489E+10 | 0.148054E+10 | 0.378761E+10 |
April | 0.674714E+10 | 0.317053E+10 | 0.357661E+10 | 0.689926E+10 | 0.302328E+10 |
May | 0.733089E+10 | 0.319687E+10 | 0.413401E+10 | 0.728763E+10 | 0.269019E+10 |
June | 0.702217E+10 | 0.280458E+10 | 0.421758E+10 | 0.747015E+10 | 0.203738E+10 |
July | 0.740718E+10 | 0.314805E+10 | 0.425913E+10 | 0.823059E+10 | 0.195278E+10 |
August | 0.701669E+10 | 0.335251E+10 | 0.366418E+10 | 0.803999E+10 | 0.211960E+10 |
September | 0.611494E+10 | 0.325164E+10 | 0.286329E+10 | 0.675299E+10 | 0.262251E+10 |
October | 0.305015E+10 | 0.126406E+10 | 0.178609E+10 | 0.260581E+10 | 0.361585E+10 |
November | 0.153884E+10 | 0.524459E+09 | 0.101438E+10 | 0.847401E+09 | 0.417085E+10 |
December | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.583377E+09 | 0.511713E+10 |
Annual Sum or Average | 0.539136E+11 | 0.231609E+11 | 0.307527E+11 | 0.525324E+11 | 0.400049E+11 |
Minimum of Months | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.583377E+09 | 0.195278E+10 |
Maximum of Months | 0.740718E+10 | 0.335251E+10 | 0.425913E+10 | 0.823059E+10 | 0.511713E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694246E+10 | 0.449414E+10 | 0.244832E+10 | 0.671999E+10 | 0.702580E+10 |
February | 0.765839E+10 | 0.467326E+10 | 0.298514E+10 | 0.762070E+10 | 0.625233E+10 |
March | 0.524223E+10 | 0.152630E+10 | 0.371593E+10 | 0.408939E+10 | 0.582493E+10 |
April | 0.105348E+11 | 0.476159E+10 | 0.577318E+10 | 0.117936E+11 | 0.495934E+10 |
May | 0.900367E+10 | 0.293130E+10 | 0.607237E+10 | 0.928704E+10 | 0.442642E+10 |
June | 0.802675E+10 | 0.194294E+10 | 0.608381E+10 | 0.864496E+10 | 0.329730E+10 |
July | 0.898673E+10 | 0.281429E+10 | 0.617243E+10 | 0.104421E+11 | 0.317441E+10 |
August | 0.105305E+11 | 0.473700E+10 | 0.579347E+10 | 0.129864E+11 | 0.346526E+10 |
September | 0.120428E+11 | 0.705490E+10 | 0.498794E+10 | 0.146954E+11 | 0.426898E+10 |
October | 0.854973E+10 | 0.499693E+10 | 0.355280E+10 | 0.926637E+10 | 0.562391E+10 |
November | 0.586621E+10 | 0.356857E+10 | 0.229765E+10 | 0.571395E+10 | 0.635664E+10 |
December | 0.480450E+10 | 0.307826E+10 | 0.172623E+10 | 0.453348E+10 | 0.773245E+10 |
Annual Sum or Average | 0.981887E+11 | 0.465795E+11 | 0.516093E+11 | 0.105793E+12 | 0.624078E+11 |
Minimum of Months | 0.480450E+10 | 0.152630E+10 | 0.172623E+10 | 0.408939E+10 | 0.317441E+10 |
Maximum of Months | 0.120428E+11 | 0.705490E+10 | 0.617243E+10 | 0.146954E+11 | 0.773245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162038E+10 | 0.535380E+09 | 0.108500E+10 | 0.926413E+09 | 0.495198E+10 |
February | 0.259132E+10 | 0.109414E+10 | 0.149718E+10 | 0.197996E+10 | 0.431686E+10 |
March | 0.259416E+10 | 0.496262E+09 | 0.209790E+10 | 0.146673E+10 | 0.394480E+10 |
April | 0.592355E+10 | 0.235289E+10 | 0.357067E+10 | 0.592146E+10 | 0.329137E+10 |
May | 0.718135E+10 | 0.292019E+10 | 0.426117E+10 | 0.715099E+10 | 0.291958E+10 |
June | 0.750492E+10 | 0.308949E+10 | 0.441543E+10 | 0.811388E+10 | 0.223851E+10 |
July | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.892669E+10 | 0.216551E+10 |
August | 0.663398E+10 | 0.287233E+10 | 0.376165E+10 | 0.757562E+10 | 0.235639E+10 |
September | 0.515053E+10 | 0.230961E+10 | 0.284091E+10 | 0.563423E+10 | 0.286097E+10 |
October | 0.283919E+10 | 0.102096E+10 | 0.181823E+10 | 0.239974E+10 | 0.381827E+10 |
November | 0.148691E+10 | 0.434048E+09 | 0.105286E+10 | 0.859491E+09 | 0.440374E+10 |
December | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.298992E+09 | 0.543750E+10 |
Annual Sum or Average | 0.522942E+11 | 0.207912E+11 | 0.315030E+11 | 0.512542E+11 | 0.427055E+11 |
Minimum of Months | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.298992E+09 | 0.216551E+10 |
Maximum of Months | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.892669E+10 | 0.543750E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122284E+10 | 0.00 | 0.122284E+10 | 0.127623E+09 | 0.677525E+10 |
February | 0.172472E+10 | 0.00 | 0.172472E+10 | 0.338141E+09 | 0.574038E+10 |
March | 0.264243E+10 | 0.00 | 0.264243E+10 | 0.973457E+09 | 0.534768E+10 |
April | 0.416350E+10 | 18634096.65 | 0.414487E+10 | 0.267705E+10 | 0.436002E+10 |
May | 0.537895E+10 | 0.259509E+09 | 0.511945E+10 | 0.350558E+10 | 0.364598E+10 |
June | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.474579E+10 | 0.284833E+10 |
July | 0.564019E+10 | 0.321577E+09 | 0.531862E+10 | 0.497600E+10 | 0.271997E+10 |
August | 0.443348E+10 | 69461691.30 | 0.436402E+10 | 0.383763E+10 | 0.301961E+10 |
September | 0.326564E+10 | 722619.41 | 0.326491E+10 | 0.249059E+10 | 0.378801E+10 |
October | 0.216235E+10 | 0.00 | 0.216235E+10 | 0.100082E+10 | 0.494142E+10 |
November | 0.125734E+10 | 0.00 | 0.125734E+10 | 0.185979E+09 | 0.575659E+10 |
December | 0.884787E+09 | 0.00 | 0.884787E+09 | 24992508.45 | 0.726164E+10 |
Annual Sum or Average | 0.385305E+11 | 0.103074E+10 | 0.374998E+11 | 0.248837E+11 | 0.562049E+11 |
Minimum of Months | 0.884787E+09 | 0.00 | 0.884787E+09 | 24992508.45 | 0.271997E+10 |
Maximum of Months | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.497600E+10 | 0.726164E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166628E+10 | 0.669349E+09 | 0.996935E+09 | 0.101944E+10 | 0.428546E+10 |
February | 0.224426E+10 | 0.829047E+09 | 0.141522E+10 | 0.151150E+10 | 0.368805E+10 |
March | 0.259659E+10 | 0.511692E+09 | 0.208489E+10 | 0.162389E+10 | 0.343215E+10 |
April | 0.674714E+10 | 0.317053E+10 | 0.357661E+10 | 0.696858E+10 | 0.286435E+10 |
May | 0.733089E+10 | 0.319687E+10 | 0.413401E+10 | 0.735111E+10 | 0.256562E+10 |
June | 0.702217E+10 | 0.280458E+10 | 0.421758E+10 | 0.749004E+10 | 0.197955E+10 |
July | 0.740718E+10 | 0.314805E+10 | 0.425913E+10 | 0.824250E+10 | 0.190374E+10 |
August | 0.701669E+10 | 0.335251E+10 | 0.366418E+10 | 0.805472E+10 | 0.206453E+10 |
September | 0.611494E+10 | 0.325164E+10 | 0.286329E+10 | 0.680516E+10 | 0.249842E+10 |
October | 0.305015E+10 | 0.126406E+10 | 0.178609E+10 | 0.271548E+10 | 0.325391E+10 |
November | 0.153884E+10 | 0.524459E+09 | 0.101438E+10 | 0.929236E+09 | 0.370127E+10 |
December | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.637948E+09 | 0.463944E+10 |
Annual Sum or Average | 0.539136E+11 | 0.231609E+11 | 0.307527E+11 | 0.533496E+11 | 0.368765E+11 |
Minimum of Months | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.637948E+09 | 0.190374E+10 |
Maximum of Months | 0.740718E+10 | 0.335251E+10 | 0.425913E+10 | 0.824250E+10 | 0.463944E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694246E+10 | 0.449414E+10 | 0.244832E+10 | 0.689309E+10 | 0.634328E+10 |
February | 0.765839E+10 | 0.467326E+10 | 0.298514E+10 | 0.778239E+10 | 0.569259E+10 |
March | 0.524223E+10 | 0.152630E+10 | 0.371593E+10 | 0.426253E+10 | 0.530589E+10 |
April | 0.105348E+11 | 0.476159E+10 | 0.577318E+10 | 0.118594E+11 | 0.470071E+10 |
May | 0.900367E+10 | 0.293130E+10 | 0.607237E+10 | 0.935323E+10 | 0.420540E+10 |
June | 0.802675E+10 | 0.194294E+10 | 0.608381E+10 | 0.865908E+10 | 0.319352E+10 |
July | 0.898673E+10 | 0.281429E+10 | 0.617243E+10 | 0.104438E+11 | 0.308417E+10 |
August | 0.105305E+11 | 0.473700E+10 | 0.579347E+10 | 0.129802E+11 | 0.336921E+10 |
September | 0.120428E+11 | 0.705490E+10 | 0.498794E+10 | 0.147351E+11 | 0.407232E+10 |
October | 0.854973E+10 | 0.499693E+10 | 0.355280E+10 | 0.939492E+10 | 0.510815E+10 |
November | 0.586621E+10 | 0.356857E+10 | 0.229765E+10 | 0.584221E+10 | 0.569857E+10 |
December | 0.480450E+10 | 0.307826E+10 | 0.172623E+10 | 0.465337E+10 | 0.702914E+10 |
Annual Sum or Average | 0.981887E+11 | 0.465795E+11 | 0.516093E+11 | 0.106859E+12 | 0.578030E+11 |
Minimum of Months | 0.480450E+10 | 0.152630E+10 | 0.172623E+10 | 0.426253E+10 | 0.308417E+10 |
Maximum of Months | 0.120428E+11 | 0.705490E+10 | 0.617243E+10 | 0.147351E+11 | 0.702914E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162038E+10 | 0.535380E+09 | 0.108500E+10 | 0.985027E+09 | 0.452199E+10 |
February | 0.259132E+10 | 0.109414E+10 | 0.149718E+10 | 0.204963E+10 | 0.397516E+10 |
March | 0.259416E+10 | 0.496262E+09 | 0.209790E+10 | 0.156089E+10 | 0.363082E+10 |
April | 0.592355E+10 | 0.235289E+10 | 0.357067E+10 | 0.596696E+10 | 0.312929E+10 |
May | 0.718135E+10 | 0.292019E+10 | 0.426117E+10 | 0.718709E+10 | 0.279136E+10 |
June | 0.750492E+10 | 0.308949E+10 | 0.441543E+10 | 0.810514E+10 | 0.217562E+10 |
July | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.891335E+10 | 0.210893E+10 |
August | 0.663398E+10 | 0.287233E+10 | 0.376165E+10 | 0.756459E+10 | 0.229395E+10 |
September | 0.515053E+10 | 0.230961E+10 | 0.284091E+10 | 0.566506E+10 | 0.273103E+10 |
October | 0.283919E+10 | 0.102096E+10 | 0.181823E+10 | 0.247724E+10 | 0.349701E+10 |
November | 0.148691E+10 | 0.434048E+09 | 0.105286E+10 | 0.909305E+09 | 0.399816E+10 |
December | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.325065E+09 | 0.501944E+10 |
Annual Sum or Average | 0.522942E+11 | 0.207912E+11 | 0.315030E+11 | 0.517094E+11 | 0.398727E+11 |
Minimum of Months | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.325065E+09 | 0.210893E+10 |
Maximum of Months | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.891335E+10 | 0.501944E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.62 | 3172.81 | 456.56 | 0.00 | 456.56 | 0.00 | 0.00 |
February | 53.91 | 2959.55 | 712.93 | 0.00 | 712.93 | 0.00 | 0.00 |
March | 243.28 | 2476.70 | 986.58 | 0.00 | 986.58 | 0.00 | 0.00 |
April | 941.47 | 1947.46 | 1606.30 | 7.19 | 1599.11 | 0.00 | 0.00 |
May | 1227.20 | 1513.68 | 2008.28 | 96.89 | 1911.39 | 0.00 | 0.00 |
June | 1800.98 | 1187.15 | 2220.03 | 139.21 | 2080.82 | 0.00 | 0.00 |
July | 1814.30 | 1101.75 | 2105.82 | 120.06 | 1985.75 | 0.00 | 0.00 |
August | 1386.92 | 1241.84 | 1655.28 | 25.93 | 1629.34 | 0.00 | 0.00 |
September | 892.94 | 1650.56 | 1259.89 | 0.28 | 1259.62 | 0.00 | 0.00 |
October | 269.79 | 2297.10 | 807.33 | 0.00 | 807.33 | 0.00 | 0.00 |
November | 23.26 | 2890.16 | 485.09 | 0.00 | 485.09 | 0.00 | 0.00 |
December | 0.01 | 3495.55 | 330.34 | 0.00 | 330.34 | 0.00 | 0.00 |
Annual Sum or Average | 725.69 | 2157.29 | 1221.80 | 32.68 | 1189.12 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 1101.75 | 330.34 | 0.00 | 330.34 | 0.00 | 0.00 |
Maximum of Months | 1814.30 | 3495.55 | 2220.03 | 139.21 | 2080.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.41 | 1967.33 | 622.12 | 249.91 | 372.21 | 0.00 | 0.00 |
February | 554.48 | 1839.77 | 927.69 | 342.70 | 585.00 | 0.00 | 0.00 |
March | 525.82 | 1529.94 | 969.46 | 191.04 | 778.41 | 0.00 | 0.00 |
April | 2672.09 | 1205.80 | 2603.07 | 1223.20 | 1379.87 | 0.00 | 0.00 |
May | 2741.32 | 1030.97 | 2737.05 | 1193.58 | 1543.47 | 0.00 | 0.00 |
June | 2904.91 | 801.46 | 2709.18 | 1082.02 | 1627.16 | 0.00 | 0.00 |
July | 3095.34 | 741.20 | 2765.54 | 1175.35 | 1590.18 | 0.00 | 0.00 |
August | 3021.74 | 803.41 | 2619.74 | 1251.69 | 1368.05 | 0.00 | 0.00 |
September | 2620.85 | 1039.80 | 2359.17 | 1254.50 | 1104.67 | 0.00 | 0.00 |
October | 961.22 | 1449.60 | 1138.80 | 471.95 | 666.85 | 0.00 | 0.00 |
November | 308.59 | 1788.75 | 593.69 | 202.34 | 391.35 | 0.00 | 0.00 |
December | 197.68 | 2142.93 | 440.00 | 163.58 | 276.41 | 0.00 | 0.00 |
Annual Sum or Average | 1664.95 | 1359.49 | 1709.60 | 734.43 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 197.68 | 741.20 | 440.00 | 163.58 | 276.41 | 0.00 | 0.00 |
Maximum of Months | 3095.34 | 2142.93 | 2765.54 | 1254.50 | 1627.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2501.62 | 2720.05 | 2592.03 | 1677.92 | 914.10 | 0.00 | 0.00 |
February | 3148.23 | 2666.53 | 3165.68 | 1931.74 | 1233.94 | 0.00 | 0.00 |
March | 1507.05 | 2287.17 | 1957.23 | 569.86 | 1387.37 | 0.00 | 0.00 |
April | 4561.16 | 1972.25 | 4064.36 | 1837.04 | 2227.31 | 0.00 | 0.00 |
May | 3486.13 | 1679.23 | 3361.60 | 1094.43 | 2267.17 | 0.00 | 0.00 |
June | 3345.62 | 1302.40 | 3096.75 | 749.59 | 2347.16 | 0.00 | 0.00 |
July | 3904.58 | 1217.50 | 3355.27 | 1050.74 | 2304.53 | 0.00 | 0.00 |
August | 4860.26 | 1328.80 | 3931.64 | 1768.60 | 2163.04 | 0.00 | 0.00 |
September | 5700.11 | 1663.80 | 4646.17 | 2721.81 | 1924.37 | 0.00 | 0.00 |
October | 3465.61 | 2170.97 | 3192.11 | 1865.65 | 1326.47 | 0.00 | 0.00 |
November | 2195.08 | 2591.14 | 2263.21 | 1376.77 | 886.44 | 0.00 | 0.00 |
December | 1669.47 | 3093.65 | 1793.80 | 1149.30 | 644.50 | 0.00 | 0.00 |
Annual Sum or Average | 3357.39 | 2054.71 | 3113.56 | 1477.03 | 1636.53 | 0.00 | 0.00 |
Minimum of Months | 1507.05 | 1217.50 | 1793.80 | 569.86 | 644.50 | 0.00 | 0.00 |
Maximum of Months | 5700.11 | 3093.65 | 4646.17 | 2721.81 | 2347.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.00 | 2122.41 | 604.98 | 199.89 | 405.09 | 0.00 | 0.00 |
February | 775.06 | 2068.39 | 1071.15 | 452.27 | 618.88 | 0.00 | 0.00 |
March | 490.11 | 1752.33 | 968.55 | 185.28 | 783.27 | 0.00 | 0.00 |
April | 2228.41 | 1442.16 | 2285.33 | 907.75 | 1377.58 | 0.00 | 0.00 |
May | 2657.21 | 1155.92 | 2681.22 | 1090.28 | 1590.94 | 0.00 | 0.00 |
June | 3113.94 | 934.59 | 2895.43 | 1191.94 | 1703.49 | 0.00 | 0.00 |
July | 3297.73 | 895.35 | 2948.87 | 1300.16 | 1648.70 | 0.00 | 0.00 |
August | 2786.71 | 993.46 | 2476.85 | 1072.41 | 1404.45 | 0.00 | 0.00 |
September | 2154.17 | 1182.26 | 1987.09 | 891.06 | 1096.04 | 0.00 | 0.00 |
October | 854.85 | 1642.83 | 1060.04 | 381.19 | 678.85 | 0.00 | 0.00 |
November | 298.26 | 2070.85 | 573.66 | 167.46 | 406.20 | 0.00 | 0.00 |
December | 90.96 | 2551.69 | 324.71 | 68.52 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1591.53 | 1565.33 | 1658.25 | 659.29 | 998.96 | 0.00 | 0.00 |
Minimum of Months | 90.96 | 895.35 | 324.71 | 68.52 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 3297.73 | 2551.69 | 2948.87 | 1300.16 | 1703.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 28.34 | 2807.03 | 456.56 | 0.00 | 456.56 | 0.00 | 0.00 |
February | 95.48 | 2625.66 | 712.93 | 0.00 | 712.93 | 0.00 | 0.00 |
March | 304.89 | 2201.35 | 986.57 | 0.00 | 986.57 | 0.00 | 0.00 |
April | 990.42 | 1794.15 | 1606.29 | 7.19 | 1599.10 | 0.00 | 0.00 |
May | 1259.47 | 1440.75 | 2008.27 | 96.89 | 1911.38 | 0.00 | 0.00 |
June | 1817.95 | 1136.11 | 2220.02 | 139.21 | 2080.81 | 0.00 | 0.00 |
July | 1848.45 | 1046.32 | 2105.81 | 120.06 | 1985.74 | 0.00 | 0.00 |
August | 1423.69 | 1165.03 | 1655.27 | 25.93 | 1629.34 | 0.00 | 0.00 |
September | 926.79 | 1553.01 | 1259.89 | 0.28 | 1259.61 | 0.00 | 0.00 |
October | 318.84 | 2060.19 | 807.33 | 0.00 | 807.33 | 0.00 | 0.00 |
November | 46.60 | 2493.67 | 485.08 | 0.00 | 485.08 | 0.00 | 0.00 |
December | 1.65 | 2986.70 | 330.34 | 0.00 | 330.34 | 0.00 | 0.00 |
Annual Sum or Average | 758.55 | 1939.06 | 1221.80 | 32.68 | 1189.11 | 0.00 | 0.00 |
Minimum of Months | 1.65 | 1046.32 | 330.34 | 0.00 | 330.34 | 0.00 | 0.00 |
Maximum of Months | 1848.45 | 2986.70 | 2220.02 | 139.21 | 2080.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.04 | 1782.89 | 622.12 | 249.91 | 372.21 | 0.00 | 0.00 |
February | 578.61 | 1691.65 | 927.69 | 342.69 | 584.99 | 0.00 | 0.00 |
March | 552.77 | 1414.13 | 969.45 | 191.04 | 778.41 | 0.00 | 0.00 |
April | 2661.75 | 1166.39 | 2603.06 | 1223.20 | 1379.87 | 0.00 | 0.00 |
May | 2720.89 | 1004.40 | 2737.04 | 1193.58 | 1543.46 | 0.00 | 0.00 |
June | 2882.00 | 786.03 | 2709.17 | 1082.02 | 1627.15 | 0.00 | 0.00 |
July | 3072.95 | 729.08 | 2765.53 | 1175.35 | 1590.18 | 0.00 | 0.00 |
August | 3001.79 | 791.37 | 2619.73 | 1251.68 | 1368.05 | 0.00 | 0.00 |
September | 2605.32 | 1011.77 | 2359.16 | 1254.49 | 1104.67 | 0.00 | 0.00 |
October | 972.90 | 1350.00 | 1138.80 | 471.95 | 666.85 | 0.00 | 0.00 |
November | 326.93 | 1609.12 | 593.69 | 202.34 | 391.35 | 0.00 | 0.00 |
December | 217.81 | 1910.52 | 440.00 | 163.58 | 276.41 | 0.00 | 0.00 |
Annual Sum or Average | 1665.79 | 1268.55 | 1709.59 | 734.43 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 217.81 | 729.08 | 440.00 | 163.58 | 276.41 | 0.00 | 0.00 |
Maximum of Months | 3072.95 | 1910.52 | 2765.53 | 1254.49 | 1627.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2508.96 | 2623.13 | 2592.02 | 1677.92 | 914.10 | 0.00 | 0.00 |
February | 3150.09 | 2584.46 | 3165.67 | 1931.74 | 1233.94 | 0.00 | 0.00 |
March | 1526.80 | 2174.78 | 1957.23 | 569.86 | 1387.37 | 0.00 | 0.00 |
April | 4550.02 | 1913.33 | 4064.34 | 1837.03 | 2227.31 | 0.00 | 0.00 |
May | 3467.38 | 1652.64 | 3361.59 | 1094.42 | 2267.16 | 0.00 | 0.00 |
June | 3335.25 | 1272.11 | 3096.74 | 749.59 | 2347.15 | 0.00 | 0.00 |
July | 3898.62 | 1185.19 | 3355.26 | 1050.74 | 2304.52 | 0.00 | 0.00 |
August | 4848.58 | 1293.78 | 3931.63 | 1768.59 | 2163.04 | 0.00 | 0.00 |
September | 5669.50 | 1646.98 | 4646.16 | 2721.80 | 1924.36 | 0.00 | 0.00 |
October | 3459.66 | 2099.73 | 3192.10 | 1865.64 | 1326.46 | 0.00 | 0.00 |
November | 2204.46 | 2452.41 | 2263.20 | 1376.76 | 886.44 | 0.00 | 0.00 |
December | 1692.61 | 2886.96 | 1793.79 | 1149.29 | 644.50 | 0.00 | 0.00 |
Annual Sum or Average | 3354.69 | 1978.94 | 3113.54 | 1477.03 | 1636.52 | 0.00 | 0.00 |
Minimum of Months | 1526.80 | 1185.19 | 1793.79 | 569.86 | 644.50 | 0.00 | 0.00 |
Maximum of Months | 5669.50 | 2886.96 | 4646.16 | 2721.80 | 2347.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 345.88 | 1848.86 | 604.98 | 199.89 | 405.09 | 0.00 | 0.00 |
February | 818.43 | 1784.41 | 1071.15 | 452.27 | 618.87 | 0.00 | 0.00 |
March | 547.62 | 1472.82 | 968.55 | 185.28 | 783.26 | 0.00 | 0.00 |
April | 2284.51 | 1269.82 | 2285.32 | 907.75 | 1377.57 | 0.00 | 0.00 |
May | 2669.87 | 1090.04 | 2681.21 | 1090.27 | 1590.94 | 0.00 | 0.00 |
June | 3130.36 | 863.62 | 2895.42 | 1191.93 | 1703.48 | 0.00 | 0.00 |
July | 3332.85 | 808.51 | 2948.86 | 1300.16 | 1648.70 | 0.00 | 0.00 |
August | 2828.41 | 879.77 | 2476.84 | 1072.40 | 1404.44 | 0.00 | 0.00 |
September | 2173.70 | 1103.77 | 1987.09 | 891.05 | 1096.03 | 0.00 | 0.00 |
October | 895.96 | 1425.58 | 1060.03 | 381.18 | 678.85 | 0.00 | 0.00 |
November | 331.59 | 1698.97 | 573.65 | 167.46 | 406.20 | 0.00 | 0.00 |
December | 111.63 | 2030.13 | 324.70 | 68.52 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1625.26 | 1354.18 | 1658.24 | 659.28 | 998.95 | 0.00 | 0.00 |
Minimum of Months | 111.63 | 808.51 | 324.70 | 68.52 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 3332.85 | 2030.13 | 2948.86 | 1300.16 | 1703.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 47.65 | 2529.59 | 456.56 | 0.00 | 456.56 | 0.00 | 0.00 |
February | 139.77 | 2372.84 | 712.93 | 0.00 | 712.93 | 0.00 | 0.00 |
March | 363.45 | 1996.60 | 986.57 | 0.00 | 986.57 | 0.00 | 0.00 |
April | 1032.81 | 1682.11 | 1606.29 | 7.19 | 1599.10 | 0.00 | 0.00 |
May | 1308.83 | 1361.25 | 2008.27 | 96.89 | 1911.38 | 0.00 | 0.00 |
June | 1830.94 | 1098.89 | 2220.02 | 139.21 | 2080.81 | 0.00 | 0.00 |
July | 1857.83 | 1015.52 | 2105.81 | 120.06 | 1985.74 | 0.00 | 0.00 |
August | 1432.81 | 1127.39 | 1655.27 | 25.93 | 1629.34 | 0.00 | 0.00 |
September | 960.88 | 1461.42 | 1259.89 | 0.28 | 1259.61 | 0.00 | 0.00 |
October | 373.66 | 1844.92 | 807.33 | 0.00 | 807.33 | 0.00 | 0.00 |
November | 71.75 | 2220.91 | 485.08 | 0.00 | 485.08 | 0.00 | 0.00 |
December | 9.33 | 2711.19 | 330.34 | 0.00 | 330.34 | 0.00 | 0.00 |
Annual Sum or Average | 789.06 | 1782.25 | 1221.80 | 32.68 | 1189.11 | 0.00 | 0.00 |
Minimum of Months | 9.33 | 1015.52 | 330.34 | 0.00 | 330.34 | 0.00 | 0.00 |
Maximum of Months | 1857.83 | 2711.19 | 2220.02 | 139.21 | 2080.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 380.61 | 1600.01 | 622.12 | 249.91 | 372.21 | 0.00 | 0.00 |
February | 624.79 | 1524.49 | 927.69 | 342.69 | 584.99 | 0.00 | 0.00 |
March | 606.29 | 1281.42 | 969.45 | 191.04 | 778.41 | 0.00 | 0.00 |
April | 2688.50 | 1105.07 | 2603.06 | 1223.20 | 1379.87 | 0.00 | 0.00 |
May | 2744.59 | 957.89 | 2737.04 | 1193.58 | 1543.46 | 0.00 | 0.00 |
June | 2889.68 | 763.72 | 2709.17 | 1082.02 | 1627.15 | 0.00 | 0.00 |
July | 3077.40 | 710.78 | 2765.53 | 1175.35 | 1590.18 | 0.00 | 0.00 |
August | 3007.29 | 770.81 | 2619.73 | 1251.68 | 1368.05 | 0.00 | 0.00 |
September | 2625.45 | 963.90 | 2359.16 | 1254.49 | 1104.67 | 0.00 | 0.00 |
October | 1013.84 | 1214.87 | 1138.80 | 471.95 | 666.85 | 0.00 | 0.00 |
November | 358.50 | 1427.96 | 593.69 | 202.34 | 391.35 | 0.00 | 0.00 |
December | 238.18 | 1732.17 | 440.00 | 163.58 | 276.41 | 0.00 | 0.00 |
Annual Sum or Average | 1691.70 | 1169.35 | 1709.59 | 734.43 | 975.16 | 0.00 | 0.00 |
Minimum of Months | 238.18 | 710.78 | 440.00 | 163.58 | 276.41 | 0.00 | 0.00 |
Maximum of Months | 3077.40 | 1732.17 | 2765.53 | 1254.49 | 1627.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2573.58 | 2368.31 | 2592.02 | 1677.92 | 914.10 | 0.00 | 0.00 |
February | 3216.93 | 2353.09 | 3165.67 | 1931.74 | 1233.94 | 0.00 | 0.00 |
March | 1591.45 | 1980.99 | 1957.23 | 569.86 | 1387.37 | 0.00 | 0.00 |
April | 4575.39 | 1813.54 | 4064.34 | 1837.03 | 2227.31 | 0.00 | 0.00 |
May | 3492.10 | 1570.12 | 3361.59 | 1094.42 | 2267.16 | 0.00 | 0.00 |
June | 3340.69 | 1232.07 | 3096.74 | 749.59 | 2347.15 | 0.00 | 0.00 |
July | 3899.29 | 1151.50 | 3355.26 | 1050.74 | 2304.52 | 0.00 | 0.00 |
August | 4846.24 | 1257.92 | 3931.63 | 1768.59 | 2163.04 | 0.00 | 0.00 |
September | 5684.83 | 1571.11 | 4646.16 | 2721.80 | 1924.36 | 0.00 | 0.00 |
October | 3507.66 | 1907.17 | 3192.10 | 1865.64 | 1326.46 | 0.00 | 0.00 |
November | 2253.94 | 2198.52 | 2263.20 | 1376.76 | 886.44 | 0.00 | 0.00 |
December | 1737.37 | 2624.38 | 1793.79 | 1149.29 | 644.50 | 0.00 | 0.00 |
Annual Sum or Average | 3388.49 | 1832.92 | 3113.54 | 1477.03 | 1636.52 | 0.00 | 0.00 |
Minimum of Months | 1591.45 | 1151.50 | 1793.79 | 569.86 | 644.50 | 0.00 | 0.00 |
Maximum of Months | 5684.83 | 2624.38 | 4646.16 | 2721.80 | 2347.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 367.77 | 1688.32 | 604.98 | 199.89 | 405.09 | 0.00 | 0.00 |
February | 847.23 | 1643.17 | 1071.15 | 452.27 | 618.87 | 0.00 | 0.00 |
March | 582.77 | 1355.59 | 968.55 | 185.28 | 783.26 | 0.00 | 0.00 |
April | 2302.07 | 1207.29 | 2285.32 | 907.75 | 1377.57 | 0.00 | 0.00 |
May | 2683.35 | 1042.18 | 2681.21 | 1090.27 | 1590.94 | 0.00 | 0.00 |
June | 3126.98 | 839.36 | 2895.42 | 1191.93 | 1703.48 | 0.00 | 0.00 |
July | 3327.86 | 787.38 | 2948.86 | 1300.16 | 1648.70 | 0.00 | 0.00 |
August | 2824.29 | 856.46 | 2476.84 | 1072.40 | 1404.44 | 0.00 | 0.00 |
September | 2185.60 | 1053.64 | 1987.09 | 891.05 | 1096.03 | 0.00 | 0.00 |
October | 924.90 | 1305.63 | 1060.03 | 381.18 | 678.85 | 0.00 | 0.00 |
November | 350.81 | 1542.50 | 573.65 | 167.46 | 406.20 | 0.00 | 0.00 |
December | 121.37 | 1874.05 | 324.70 | 68.52 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1639.69 | 1264.36 | 1658.24 | 659.28 | 998.95 | 0.00 | 0.00 |
Minimum of Months | 121.37 | 787.38 | 324.70 | 68.52 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 3327.86 | 1874.05 | 2948.86 | 1300.16 | 1703.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 36490432.29 | 0.849806E+10 | 0.122284E+10 | 0.00 | 0.122284E+10 | 0.00 | 0.00 |
February | 0.130417E+09 | 0.715975E+10 | 0.172473E+10 | 0.00 | 0.172473E+10 | 0.00 | 0.00 |
March | 0.651589E+09 | 0.663360E+10 | 0.264244E+10 | 0.00 | 0.264244E+10 | 0.00 | 0.00 |
April | 0.244028E+10 | 0.504783E+10 | 0.416352E+10 | 18634162.82 | 0.414488E+10 | 0.00 | 0.00 |
May | 0.328695E+10 | 0.405424E+10 | 0.537897E+10 | 0.259510E+09 | 0.511947E+10 | 0.00 | 0.00 |
June | 0.466815E+10 | 0.307710E+10 | 0.575431E+10 | 0.360832E+09 | 0.539348E+10 | 0.00 | 0.00 |
July | 0.485943E+10 | 0.295091E+10 | 0.564022E+10 | 0.321579E+09 | 0.531864E+10 | 0.00 | 0.00 |
August | 0.371472E+10 | 0.332614E+10 | 0.443350E+10 | 69461937.96 | 0.436404E+10 | 0.00 | 0.00 |
September | 0.231450E+10 | 0.427824E+10 | 0.326565E+10 | 722621.98 | 0.326492E+10 | 0.00 | 0.00 |
October | 0.722612E+09 | 0.615255E+10 | 0.216236E+10 | 0.00 | 0.216236E+10 | 0.00 | 0.00 |
November | 60289680.89 | 0.749128E+10 | 0.125734E+10 | 0.00 | 0.125734E+10 | 0.00 | 0.00 |
December | 30706.77 | 0.936247E+10 | 0.884790E+09 | 0.00 | 0.884790E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.228855E+11 | 0.680322E+11 | 0.385307E+11 | 0.103074E+10 | 0.374999E+11 | 0.00 | 0.00 |
Minimum of Months | 30706.77 | 0.295091E+10 | 0.884790E+09 | 0.00 | 0.884790E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485943E+10 | 0.936247E+10 | 0.575431E+10 | 0.360832E+09 | 0.539348E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.876944E+09 | 0.526930E+10 | 0.166629E+10 | 0.669352E+09 | 0.996939E+09 | 0.00 | 0.00 |
February | 0.134140E+10 | 0.445076E+10 | 0.224427E+10 | 0.829051E+09 | 0.141522E+10 | 0.00 | 0.00 |
March | 0.140834E+10 | 0.409779E+10 | 0.259660E+10 | 0.511694E+09 | 0.208490E+10 | 0.00 | 0.00 |
April | 0.692606E+10 | 0.312543E+10 | 0.674717E+10 | 0.317054E+10 | 0.357663E+10 | 0.00 | 0.00 |
May | 0.734236E+10 | 0.276136E+10 | 0.733092E+10 | 0.319689E+10 | 0.413403E+10 | 0.00 | 0.00 |
June | 0.752952E+10 | 0.207737E+10 | 0.702219E+10 | 0.280459E+10 | 0.421760E+10 | 0.00 | 0.00 |
July | 0.829055E+10 | 0.198522E+10 | 0.740721E+10 | 0.314806E+10 | 0.425915E+10 | 0.00 | 0.00 |
August | 0.809342E+10 | 0.215185E+10 | 0.701672E+10 | 0.335252E+10 | 0.366420E+10 | 0.00 | 0.00 |
September | 0.679325E+10 | 0.269516E+10 | 0.611496E+10 | 0.325166E+10 | 0.286330E+10 | 0.00 | 0.00 |
October | 0.257452E+10 | 0.388261E+10 | 0.305016E+10 | 0.126407E+10 | 0.178610E+10 | 0.00 | 0.00 |
November | 0.799878E+09 | 0.463645E+10 | 0.153885E+10 | 0.524461E+09 | 0.101439E+10 | 0.00 | 0.00 |
December | 0.529454E+09 | 0.573963E+10 | 0.117849E+10 | 0.438145E+09 | 0.740343E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525057E+11 | 0.428729E+11 | 0.539138E+11 | 0.231610E+11 | 0.307528E+11 | 0.00 | 0.00 |
Minimum of Months | 0.529454E+09 | 0.198522E+10 | 0.117849E+10 | 0.438145E+09 | 0.740343E+09 | 0.00 | 0.00 |
Maximum of Months | 0.829055E+10 | 0.573963E+10 | 0.740721E+10 | 0.335252E+10 | 0.425915E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.670035E+10 | 0.728538E+10 | 0.694248E+10 | 0.449415E+10 | 0.244833E+10 | 0.00 | 0.00 |
February | 0.761620E+10 | 0.645086E+10 | 0.765842E+10 | 0.467327E+10 | 0.298515E+10 | 0.00 | 0.00 |
March | 0.403647E+10 | 0.612595E+10 | 0.524225E+10 | 0.152631E+10 | 0.371595E+10 | 0.00 | 0.00 |
April | 0.118225E+11 | 0.511208E+10 | 0.105348E+11 | 0.476161E+10 | 0.577320E+10 | 0.00 | 0.00 |
May | 0.933726E+10 | 0.449765E+10 | 0.900371E+10 | 0.293131E+10 | 0.607239E+10 | 0.00 | 0.00 |
June | 0.867183E+10 | 0.337582E+10 | 0.802678E+10 | 0.194295E+10 | 0.608383E+10 | 0.00 | 0.00 |
July | 0.104580E+11 | 0.326096E+10 | 0.898676E+10 | 0.281430E+10 | 0.617245E+10 | 0.00 | 0.00 |
August | 0.130177E+11 | 0.355907E+10 | 0.105305E+11 | 0.473701E+10 | 0.579350E+10 | 0.00 | 0.00 |
September | 0.147747E+11 | 0.431258E+10 | 0.120429E+11 | 0.705492E+10 | 0.498796E+10 | 0.00 | 0.00 |
October | 0.928230E+10 | 0.581472E+10 | 0.854976E+10 | 0.499695E+10 | 0.355281E+10 | 0.00 | 0.00 |
November | 0.568964E+10 | 0.671624E+10 | 0.586623E+10 | 0.356858E+10 | 0.229765E+10 | 0.00 | 0.00 |
December | 0.447152E+10 | 0.828603E+10 | 0.480451E+10 | 0.307827E+10 | 0.172624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.105879E+12 | 0.647973E+11 | 0.981891E+11 | 0.465796E+11 | 0.516095E+11 | 0.00 | 0.00 |
Minimum of Months | 0.403647E+10 | 0.326096E+10 | 0.480451E+10 | 0.152631E+10 | 0.172624E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147747E+11 | 0.828603E+10 | 0.120429E+11 | 0.705492E+10 | 0.617245E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851731E+09 | 0.568465E+10 | 0.162039E+10 | 0.535382E+09 | 0.108500E+10 | 0.00 | 0.00 |
February | 0.187502E+10 | 0.500385E+10 | 0.259133E+10 | 0.109414E+10 | 0.149719E+10 | 0.00 | 0.00 |
March | 0.131272E+10 | 0.469344E+10 | 0.259417E+10 | 0.496264E+09 | 0.209790E+10 | 0.00 | 0.00 |
April | 0.577604E+10 | 0.373808E+10 | 0.592358E+10 | 0.235290E+10 | 0.357068E+10 | 0.00 | 0.00 |
May | 0.711708E+10 | 0.309600E+10 | 0.718138E+10 | 0.292020E+10 | 0.426118E+10 | 0.00 | 0.00 |
June | 0.807132E+10 | 0.242245E+10 | 0.750496E+10 | 0.308950E+10 | 0.441545E+10 | 0.00 | 0.00 |
July | 0.883265E+10 | 0.239812E+10 | 0.789825E+10 | 0.348236E+10 | 0.441589E+10 | 0.00 | 0.00 |
August | 0.746393E+10 | 0.266089E+10 | 0.663400E+10 | 0.287234E+10 | 0.376167E+10 | 0.00 | 0.00 |
September | 0.558361E+10 | 0.306441E+10 | 0.515055E+10 | 0.230962E+10 | 0.284093E+10 | 0.00 | 0.00 |
October | 0.228964E+10 | 0.440015E+10 | 0.283921E+10 | 0.102097E+10 | 0.181824E+10 | 0.00 | 0.00 |
November | 0.773079E+09 | 0.536765E+10 | 0.148692E+10 | 0.434049E+09 | 0.105287E+10 | 0.00 | 0.00 |
December | 0.243640E+09 | 0.683444E+10 | 0.869693E+09 | 0.183524E+09 | 0.686169E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.501905E+11 | 0.493641E+11 | 0.522944E+11 | 0.207912E+11 | 0.315032E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243640E+09 | 0.239812E+10 | 0.869693E+09 | 0.183524E+09 | 0.686169E+09 | 0.00 | 0.00 |
Maximum of Months | 0.883265E+10 | 0.683444E+10 | 0.789825E+10 | 0.348236E+10 | 0.441589E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 75908459.93 | 0.751835E+10 | 0.122284E+10 | 0.00 | 0.122284E+10 | 0.00 | 0.00 |
February | 0.230974E+09 | 0.635200E+10 | 0.172472E+10 | 0.00 | 0.172472E+10 | 0.00 | 0.00 |
March | 0.816608E+09 | 0.589610E+10 | 0.264243E+10 | 0.00 | 0.264243E+10 | 0.00 | 0.00 |
April | 0.256717E+10 | 0.465045E+10 | 0.416350E+10 | 18634096.65 | 0.414487E+10 | 0.00 | 0.00 |
May | 0.337338E+10 | 0.385890E+10 | 0.537895E+10 | 0.259509E+09 | 0.511945E+10 | 0.00 | 0.00 |
June | 0.471213E+10 | 0.294480E+10 | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.00 | 0.00 |
July | 0.495088E+10 | 0.280247E+10 | 0.564019E+10 | 0.321577E+09 | 0.531862E+10 | 0.00 | 0.00 |
August | 0.381320E+10 | 0.312042E+10 | 0.443348E+10 | 69461691.30 | 0.436402E+10 | 0.00 | 0.00 |
September | 0.240223E+10 | 0.402540E+10 | 0.326564E+10 | 722619.41 | 0.326491E+10 | 0.00 | 0.00 |
October | 0.853987E+09 | 0.551802E+10 | 0.216235E+10 | 0.00 | 0.216235E+10 | 0.00 | 0.00 |
November | 0.120796E+09 | 0.646359E+10 | 0.125734E+10 | 0.00 | 0.125734E+10 | 0.00 | 0.00 |
December | 4428018.89 | 0.799957E+10 | 0.884787E+09 | 0.00 | 0.884787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239217E+11 | 0.611501E+11 | 0.385305E+11 | 0.103074E+10 | 0.374998E+11 | 0.00 | 0.00 |
Minimum of Months | 4428018.89 | 0.280247E+10 | 0.884787E+09 | 0.00 | 0.884787E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495088E+10 | 0.799957E+10 | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.934878E+09 | 0.477530E+10 | 0.166628E+10 | 0.669349E+09 | 0.996935E+09 | 0.00 | 0.00 |
February | 0.139978E+10 | 0.409245E+10 | 0.224426E+10 | 0.829047E+09 | 0.141522E+10 | 0.00 | 0.00 |
March | 0.148054E+10 | 0.378761E+10 | 0.259659E+10 | 0.511692E+09 | 0.208489E+10 | 0.00 | 0.00 |
April | 0.689926E+10 | 0.302328E+10 | 0.674714E+10 | 0.317053E+10 | 0.357661E+10 | 0.00 | 0.00 |
May | 0.728763E+10 | 0.269019E+10 | 0.733089E+10 | 0.319687E+10 | 0.413401E+10 | 0.00 | 0.00 |
June | 0.747015E+10 | 0.203738E+10 | 0.702217E+10 | 0.280458E+10 | 0.421758E+10 | 0.00 | 0.00 |
July | 0.823059E+10 | 0.195278E+10 | 0.740718E+10 | 0.314805E+10 | 0.425913E+10 | 0.00 | 0.00 |
August | 0.803999E+10 | 0.211960E+10 | 0.701669E+10 | 0.335251E+10 | 0.366418E+10 | 0.00 | 0.00 |
September | 0.675299E+10 | 0.262251E+10 | 0.611494E+10 | 0.325164E+10 | 0.286329E+10 | 0.00 | 0.00 |
October | 0.260581E+10 | 0.361585E+10 | 0.305015E+10 | 0.126406E+10 | 0.178609E+10 | 0.00 | 0.00 |
November | 0.847401E+09 | 0.417085E+10 | 0.153884E+10 | 0.524459E+09 | 0.101438E+10 | 0.00 | 0.00 |
December | 0.583377E+09 | 0.511713E+10 | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525324E+11 | 0.400049E+11 | 0.539136E+11 | 0.231609E+11 | 0.307527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.583377E+09 | 0.195278E+10 | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.00 | 0.00 |
Maximum of Months | 0.823059E+10 | 0.511713E+10 | 0.740718E+10 | 0.335251E+10 | 0.425913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.671999E+10 | 0.702580E+10 | 0.694246E+10 | 0.449414E+10 | 0.244832E+10 | 0.00 | 0.00 |
February | 0.762070E+10 | 0.625233E+10 | 0.765839E+10 | 0.467326E+10 | 0.298514E+10 | 0.00 | 0.00 |
March | 0.408939E+10 | 0.582493E+10 | 0.524223E+10 | 0.152630E+10 | 0.371593E+10 | 0.00 | 0.00 |
April | 0.117936E+11 | 0.495934E+10 | 0.105348E+11 | 0.476159E+10 | 0.577318E+10 | 0.00 | 0.00 |
May | 0.928704E+10 | 0.442642E+10 | 0.900367E+10 | 0.293130E+10 | 0.607237E+10 | 0.00 | 0.00 |
June | 0.864496E+10 | 0.329730E+10 | 0.802675E+10 | 0.194294E+10 | 0.608381E+10 | 0.00 | 0.00 |
July | 0.104421E+11 | 0.317441E+10 | 0.898673E+10 | 0.281429E+10 | 0.617243E+10 | 0.00 | 0.00 |
August | 0.129864E+11 | 0.346526E+10 | 0.105305E+11 | 0.473700E+10 | 0.579347E+10 | 0.00 | 0.00 |
September | 0.146954E+11 | 0.426898E+10 | 0.120428E+11 | 0.705490E+10 | 0.498794E+10 | 0.00 | 0.00 |
October | 0.926637E+10 | 0.562391E+10 | 0.854973E+10 | 0.499693E+10 | 0.355280E+10 | 0.00 | 0.00 |
November | 0.571395E+10 | 0.635664E+10 | 0.586621E+10 | 0.356857E+10 | 0.229765E+10 | 0.00 | 0.00 |
December | 0.453348E+10 | 0.773245E+10 | 0.480450E+10 | 0.307826E+10 | 0.172623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.105793E+12 | 0.624078E+11 | 0.981887E+11 | 0.465795E+11 | 0.516093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.408939E+10 | 0.317441E+10 | 0.480450E+10 | 0.152630E+10 | 0.172623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.146954E+11 | 0.773245E+10 | 0.120428E+11 | 0.705490E+10 | 0.617243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.926413E+09 | 0.495198E+10 | 0.162038E+10 | 0.535380E+09 | 0.108500E+10 | 0.00 | 0.00 |
February | 0.197996E+10 | 0.431686E+10 | 0.259132E+10 | 0.109414E+10 | 0.149718E+10 | 0.00 | 0.00 |
March | 0.146673E+10 | 0.394480E+10 | 0.259416E+10 | 0.496262E+09 | 0.209790E+10 | 0.00 | 0.00 |
April | 0.592146E+10 | 0.329137E+10 | 0.592355E+10 | 0.235289E+10 | 0.357067E+10 | 0.00 | 0.00 |
May | 0.715099E+10 | 0.291958E+10 | 0.718135E+10 | 0.292019E+10 | 0.426117E+10 | 0.00 | 0.00 |
June | 0.811388E+10 | 0.223851E+10 | 0.750492E+10 | 0.308949E+10 | 0.441543E+10 | 0.00 | 0.00 |
July | 0.892669E+10 | 0.216551E+10 | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.00 | 0.00 |
August | 0.757562E+10 | 0.235639E+10 | 0.663398E+10 | 0.287233E+10 | 0.376165E+10 | 0.00 | 0.00 |
September | 0.563423E+10 | 0.286097E+10 | 0.515053E+10 | 0.230961E+10 | 0.284091E+10 | 0.00 | 0.00 |
October | 0.239974E+10 | 0.381827E+10 | 0.283919E+10 | 0.102096E+10 | 0.181823E+10 | 0.00 | 0.00 |
November | 0.859491E+09 | 0.440374E+10 | 0.148691E+10 | 0.434048E+09 | 0.105286E+10 | 0.00 | 0.00 |
December | 0.298992E+09 | 0.543750E+10 | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.512542E+11 | 0.427055E+11 | 0.522942E+11 | 0.207912E+11 | 0.315030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298992E+09 | 0.216551E+10 | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.00 | 0.00 |
Maximum of Months | 0.892669E+10 | 0.543750E+10 | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127623E+09 | 0.677525E+10 | 0.122284E+10 | 0.00 | 0.122284E+10 | 0.00 | 0.00 |
February | 0.338141E+09 | 0.574038E+10 | 0.172472E+10 | 0.00 | 0.172472E+10 | 0.00 | 0.00 |
March | 0.973457E+09 | 0.534768E+10 | 0.264243E+10 | 0.00 | 0.264243E+10 | 0.00 | 0.00 |
April | 0.267705E+10 | 0.436002E+10 | 0.416350E+10 | 18634096.65 | 0.414487E+10 | 0.00 | 0.00 |
May | 0.350558E+10 | 0.364598E+10 | 0.537895E+10 | 0.259509E+09 | 0.511945E+10 | 0.00 | 0.00 |
June | 0.474579E+10 | 0.284833E+10 | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.00 | 0.00 |
July | 0.497600E+10 | 0.271997E+10 | 0.564019E+10 | 0.321577E+09 | 0.531862E+10 | 0.00 | 0.00 |
August | 0.383763E+10 | 0.301961E+10 | 0.443348E+10 | 69461691.30 | 0.436402E+10 | 0.00 | 0.00 |
September | 0.249059E+10 | 0.378801E+10 | 0.326564E+10 | 722619.41 | 0.326491E+10 | 0.00 | 0.00 |
October | 0.100082E+10 | 0.494142E+10 | 0.216235E+10 | 0.00 | 0.216235E+10 | 0.00 | 0.00 |
November | 0.185979E+09 | 0.575659E+10 | 0.125734E+10 | 0.00 | 0.125734E+10 | 0.00 | 0.00 |
December | 24992508.45 | 0.726164E+10 | 0.884787E+09 | 0.00 | 0.884787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.248837E+11 | 0.562049E+11 | 0.385305E+11 | 0.103074E+10 | 0.374998E+11 | 0.00 | 0.00 |
Minimum of Months | 24992508.45 | 0.271997E+10 | 0.884787E+09 | 0.00 | 0.884787E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497600E+10 | 0.726164E+10 | 0.575429E+10 | 0.360831E+09 | 0.539346E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101944E+10 | 0.428546E+10 | 0.166628E+10 | 0.669349E+09 | 0.996935E+09 | 0.00 | 0.00 |
February | 0.151150E+10 | 0.368805E+10 | 0.224426E+10 | 0.829047E+09 | 0.141522E+10 | 0.00 | 0.00 |
March | 0.162389E+10 | 0.343215E+10 | 0.259659E+10 | 0.511692E+09 | 0.208489E+10 | 0.00 | 0.00 |
April | 0.696858E+10 | 0.286435E+10 | 0.674714E+10 | 0.317053E+10 | 0.357661E+10 | 0.00 | 0.00 |
May | 0.735111E+10 | 0.256562E+10 | 0.733089E+10 | 0.319687E+10 | 0.413401E+10 | 0.00 | 0.00 |
June | 0.749004E+10 | 0.197955E+10 | 0.702217E+10 | 0.280458E+10 | 0.421758E+10 | 0.00 | 0.00 |
July | 0.824250E+10 | 0.190374E+10 | 0.740718E+10 | 0.314805E+10 | 0.425913E+10 | 0.00 | 0.00 |
August | 0.805472E+10 | 0.206453E+10 | 0.701669E+10 | 0.335251E+10 | 0.366418E+10 | 0.00 | 0.00 |
September | 0.680516E+10 | 0.249842E+10 | 0.611494E+10 | 0.325164E+10 | 0.286329E+10 | 0.00 | 0.00 |
October | 0.271548E+10 | 0.325391E+10 | 0.305015E+10 | 0.126406E+10 | 0.178609E+10 | 0.00 | 0.00 |
November | 0.929236E+09 | 0.370127E+10 | 0.153884E+10 | 0.524459E+09 | 0.101438E+10 | 0.00 | 0.00 |
December | 0.637948E+09 | 0.463944E+10 | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.533496E+11 | 0.368765E+11 | 0.539136E+11 | 0.231609E+11 | 0.307527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.637948E+09 | 0.190374E+10 | 0.117848E+10 | 0.438144E+09 | 0.740340E+09 | 0.00 | 0.00 |
Maximum of Months | 0.824250E+10 | 0.463944E+10 | 0.740718E+10 | 0.335251E+10 | 0.425913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.689309E+10 | 0.634328E+10 | 0.694246E+10 | 0.449414E+10 | 0.244832E+10 | 0.00 | 0.00 |
February | 0.778239E+10 | 0.569259E+10 | 0.765839E+10 | 0.467326E+10 | 0.298514E+10 | 0.00 | 0.00 |
March | 0.426253E+10 | 0.530589E+10 | 0.524223E+10 | 0.152630E+10 | 0.371593E+10 | 0.00 | 0.00 |
April | 0.118594E+11 | 0.470071E+10 | 0.105348E+11 | 0.476159E+10 | 0.577318E+10 | 0.00 | 0.00 |
May | 0.935323E+10 | 0.420540E+10 | 0.900367E+10 | 0.293130E+10 | 0.607237E+10 | 0.00 | 0.00 |
June | 0.865908E+10 | 0.319352E+10 | 0.802675E+10 | 0.194294E+10 | 0.608381E+10 | 0.00 | 0.00 |
July | 0.104438E+11 | 0.308417E+10 | 0.898673E+10 | 0.281429E+10 | 0.617243E+10 | 0.00 | 0.00 |
August | 0.129802E+11 | 0.336921E+10 | 0.105305E+11 | 0.473700E+10 | 0.579347E+10 | 0.00 | 0.00 |
September | 0.147351E+11 | 0.407232E+10 | 0.120428E+11 | 0.705490E+10 | 0.498794E+10 | 0.00 | 0.00 |
October | 0.939492E+10 | 0.510815E+10 | 0.854973E+10 | 0.499693E+10 | 0.355280E+10 | 0.00 | 0.00 |
November | 0.584221E+10 | 0.569857E+10 | 0.586621E+10 | 0.356857E+10 | 0.229765E+10 | 0.00 | 0.00 |
December | 0.465337E+10 | 0.702914E+10 | 0.480450E+10 | 0.307826E+10 | 0.172623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106859E+12 | 0.578030E+11 | 0.981887E+11 | 0.465795E+11 | 0.516093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426253E+10 | 0.308417E+10 | 0.480450E+10 | 0.152630E+10 | 0.172623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147351E+11 | 0.702914E+10 | 0.120428E+11 | 0.705490E+10 | 0.617243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.985027E+09 | 0.452199E+10 | 0.162038E+10 | 0.535380E+09 | 0.108500E+10 | 0.00 | 0.00 |
February | 0.204963E+10 | 0.397516E+10 | 0.259132E+10 | 0.109414E+10 | 0.149718E+10 | 0.00 | 0.00 |
March | 0.156089E+10 | 0.363082E+10 | 0.259416E+10 | 0.496262E+09 | 0.209790E+10 | 0.00 | 0.00 |
April | 0.596696E+10 | 0.312929E+10 | 0.592355E+10 | 0.235289E+10 | 0.357067E+10 | 0.00 | 0.00 |
May | 0.718709E+10 | 0.279136E+10 | 0.718135E+10 | 0.292019E+10 | 0.426117E+10 | 0.00 | 0.00 |
June | 0.810514E+10 | 0.217562E+10 | 0.750492E+10 | 0.308949E+10 | 0.441543E+10 | 0.00 | 0.00 |
July | 0.891335E+10 | 0.210893E+10 | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.00 | 0.00 |
August | 0.756459E+10 | 0.229395E+10 | 0.663398E+10 | 0.287233E+10 | 0.376165E+10 | 0.00 | 0.00 |
September | 0.566506E+10 | 0.273103E+10 | 0.515053E+10 | 0.230961E+10 | 0.284091E+10 | 0.00 | 0.00 |
October | 0.247724E+10 | 0.349701E+10 | 0.283919E+10 | 0.102096E+10 | 0.181823E+10 | 0.00 | 0.00 |
November | 0.909305E+09 | 0.399816E+10 | 0.148691E+10 | 0.434048E+09 | 0.105286E+10 | 0.00 | 0.00 |
December | 0.325065E+09 | 0.501944E+10 | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.517094E+11 | 0.398727E+11 | 0.522942E+11 | 0.207912E+11 | 0.315030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325065E+09 | 0.210893E+10 | 0.869689E+09 | 0.183523E+09 | 0.686166E+09 | 0.00 | 0.00 |
Maximum of Months | 0.891335E+10 | 0.501944E+10 | 0.789822E+10 | 0.348235E+10 | 0.441587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.399685E+11 | -0.395251E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443440929.5 | 60.05 | 0.00 | 0.00 |
February | 0.365526E+11 | -0.361510E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401518972.7 | 60.05 | 0.00 | 0.00 |
March | 0.426941E+11 | -0.422488E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445294719.4 | 60.05 | 0.00 | 0.00 |
April | 0.380232E+11 | -0.375950E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428175077.6 | 60.05 | 0.00 | 0.00 |
May | 0.395398E+11 | -0.390964E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443475336.2 | 60.05 | 0.00 | 0.00 |
June | 0.381601E+11 | -0.377310E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429140719.0 | 60.05 | 0.00 | 0.00 |
July | 0.355778E+11 | -0.351370E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440802298.9 | 60.05 | 0.00 | 0.00 |
August | 0.386189E+11 | -0.381766E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442383059.8 | 60.05 | 0.00 | 0.00 |
September | 0.353128E+11 | -0.348850E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427765702.5 | 60.05 | 0.00 | 0.00 |
October | 0.371811E+11 | -0.367393E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441858111.1 | 60.05 | 0.00 | 0.00 |
November | 0.374734E+11 | -0.370454E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427999069.0 | 60.05 | 0.00 | 0.00 |
December | 0.382972E+11 | -0.378540E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443265122.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.457400E+12 | -0.452184E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.521512E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.353128E+11 | -0.422488E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -445294719.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.426941E+11 | -0.348850E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -401518972.7 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.51 | 0.48 | 01-JAN-08:39 | 3988.50 | 36.43 | 191.17 | 222.00 | 3311.15 | 37.56 | 193.67 | 194.33 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5720.09 | 36.13 | 213.67 | 246.00 | 2639.36 | 30.38 | 199.33 | 218.50 |
March | 215.50 | 0.50 | 0.48 | 01-MAR-11:39 | 4231.79 | 31.40 | 190.83 | 310.50 | 1194.52 | 22.34 | 210.50 | 266.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:00 | 2680.93 | 21.22 | 218.17 | 355.50 | 1493.33 | 22.64 | 292.50 | 329.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:49 | 2142.01 | 20.81 | 197.33 | 410.33 | 1188.78 | 22.22 | 313.50 | 373.33 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 2088.26 | 21.09 | 202.83 | 412.67 | 1147.62 | 22.50 | 318.83 | 372.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:40 | 2081.01 | 20.86 | 198.83 | 421.33 | 1171.44 | 22.28 | 326.83 | 382.83 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-06:10 | 2400.65 | 20.87 | 193.17 | 382.33 | 1365.49 | 22.29 | 309.50 | 348.33 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3525.37 | 22.82 | 184.83 | 331.17 | 1643.85 | 22.86 | 271.00 | 304.17 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7236.20 | 35.35 | 217.17 | 279.83 | 2119.24 | 25.34 | 206.33 | 239.00 |
November | 171.33 | 0.50 | 0.48 | 01-NOV-11:39 | 4598.84 | 36.28 | 167.17 | 216.67 | 3796.47 | 37.46 | 170.83 | 173.00 |
December | 131.67 | 0.49 | 0.48 | 02-DEC-08:50 | 3869.13 | 37.33 | 128.67 | 183.17 | 3213.09 | 38.53 | 128.67 | 132.67 |
Annual Sum or Average | 3515.67 | 0.50 | 3320.64 | 25.89 | 2303.83 | 3771.50 | 1749.48 | 25.30 | 2941.50 | 3334.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 2081.01 | 20.81 | 128.67 | 183.17 | 1147.62 | 22.22 | 128.67 | 132.67 | |
Maximum of Months | 429.00 | 0.51 | 0.48 | 7236.20 | 37.33 | 218.17 | 421.33 | 3796.47 | 38.53 | 326.83 | 382.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 1472.24 | 24.85 | 88.00 | 210.33 | 866.76 | 24.84 | 101.67 | 145.17 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 1794.87 | 25.04 | 93.67 | 239.33 | 989.45 | 25.16 | 125.00 | 195.00 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 2026.10 | 25.10 | 98.67 | 304.67 | 1065.38 | 25.33 | 166.67 | 252.00 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3769.30 | 26.19 | 167.00 | 364.67 | 2168.68 | 26.44 | 258.67 | 339.50 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:40 | 3864.86 | 25.08 | 151.67 | 422.83 | 1729.00 | 24.47 | 253.00 | 382.33 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:49 | 3897.86 | 25.61 | 150.83 | 420.83 | 1771.45 | 25.19 | 269.83 | 389.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3811.42 | 25.76 | 167.50 | 432.00 | 1724.48 | 25.24 | 272.67 | 401.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3666.45 | 25.45 | 146.83 | 390.50 | 1610.98 | 24.71 | 267.67 | 361.17 |
September | 337.67 | 0.49 | 0.48 | 01-SEP-07:40 | 3470.83 | 25.86 | 152.17 | 338.17 | 1900.41 | 25.88 | 235.83 | 308.00 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2744.86 | 26.30 | 118.50 | 273.83 | 1233.69 | 25.12 | 157.67 | 215.33 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 1508.21 | 24.78 | 82.33 | 204.67 | 854.93 | 24.85 | 96.50 | 136.00 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 1273.61 | 25.45 | 65.33 | 165.33 | 875.78 | 26.77 | 79.33 | 99.33 |
Annual Sum or Average | 3515.67 | 0.50 | 3132.12 | 25.52 | 1482.50 | 3767.17 | 1539.71 | 25.27 | 2284.50 | 3224.50 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 1273.61 | 24.78 | 65.33 | 165.33 | 854.93 | 24.47 | 79.33 | 99.33 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 3897.86 | 26.30 | 167.50 | 432.00 | 2168.68 | 26.77 | 272.67 | 401.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-09:50 | 544.38 | 16.17 | 0.00 | 188.17 | 313.45 | 17.74 | 0.00 | 76.17 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 722.57 | 17.88 | 0.00 | 224.33 | 419.43 | 19.36 | 15.67 | 142.50 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 886.35 | 18.61 | 0.17 | 300.33 | 478.76 | 19.87 | 39.67 | 220.00 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:00 | 1185.48 | 20.23 | 27.33 | 360.83 | 702.30 | 21.57 | 247.00 | 329.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:49 | 1399.79 | 22.03 | 132.83 | 425.50 | 799.36 | 23.25 | 320.17 | 398.00 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1590.43 | 23.10 | 160.33 | 427.83 | 876.97 | 23.49 | 339.00 | 401.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1478.74 | 22.86 | 170.00 | 438.83 | 864.31 | 24.15 | 357.33 | 416.33 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1191.45 | 20.29 | 57.00 | 389.83 | 724.57 | 21.67 | 287.17 | 359.67 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:49 | 974.66 | 19.63 | 0.50 | 326.00 | 605.35 | 21.11 | 161.83 | 283.67 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:30 | 820.96 | 18.52 | 0.00 | 263.17 | 487.62 | 20.00 | 40.50 | 178.17 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 604.12 | 16.94 | 0.00 | 181.67 | 350.11 | 18.46 | 0.00 | 78.83 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:20 | 511.35 | 16.42 | 0.00 | 134.33 | 298.01 | 18.04 | 0.00 | 41.33 |
Annual Sum or Average | 3515.67 | 0.50 | 1113.99 | 20.16 | 548.17 | 3660.83 | 647.79 | 21.43 | 1808.33 | 2924.67 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 511.35 | 16.17 | 0.00 | 134.33 | 298.01 | 17.74 | 0.00 | 41.33 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 1590.43 | 23.10 | 170.00 | 438.83 | 876.97 | 24.15 | 357.33 | 416.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.53 | 0.48 | 01-JAN-09:50 | 1330.67 | 24.10 | 85.17 | 203.17 | 756.19 | 24.12 | 99.17 | 145.83 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 2077.06 | 24.31 | 90.83 | 234.00 | 1111.10 | 24.25 | 124.67 | 182.33 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1911.27 | 24.00 | 98.33 | 303.67 | 1026.45 | 24.24 | 157.67 | 250.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:49 | 3607.08 | 24.06 | 138.67 | 355.17 | 1625.22 | 23.65 | 233.83 | 328.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3268.84 | 22.28 | 94.17 | 413.33 | 1801.90 | 23.13 | 248.50 | 383.17 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 3778.83 | 21.56 | 72.33 | 418.83 | 1682.64 | 21.83 | 246.67 | 380.33 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-05:40 | 3753.53 | 21.46 | 64.33 | 428.00 | 1710.80 | 21.77 | 240.50 | 394.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-06:10 | 3348.90 | 22.97 | 115.17 | 382.83 | 1856.31 | 23.59 | 237.83 | 350.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:00 | 3248.27 | 24.60 | 128.67 | 325.83 | 1768.38 | 24.96 | 204.33 | 297.50 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2583.24 | 25.52 | 113.33 | 269.17 | 1153.07 | 24.50 | 147.83 | 211.50 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:39 | 1461.89 | 23.95 | 76.83 | 197.50 | 778.57 | 23.91 | 90.67 | 132.50 |
December | 131.67 | 0.53 | 0.48 | 02-DEC-09:39 | 1054.55 | 22.32 | 46.17 | 160.83 | 546.27 | 22.08 | 53.33 | 82.33 |
Annual Sum or Average | 3515.67 | 0.50 | 2947.94 | 23.21 | 1124.00 | 3692.33 | 1473.24 | 23.38 | 2085.00 | 3139.50 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1054.55 | 21.46 | 46.17 | 160.83 | 546.27 | 21.77 | 53.33 | 82.33 | |
Maximum of Months | 429.00 | 0.53 | 0.48 | 3778.83 | 25.52 | 138.67 | 428.00 | 1856.31 | 24.96 | 248.50 | 394.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.51 | 0.48 | 01-JAN-08:39 | 4013.00 | 36.01 | 190.67 | 222.17 | 3401.29 | 37.18 | 189.83 | 196.33 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5757.80 | 35.71 | 213.33 | 246.17 | 2802.69 | 29.97 | 141.83 | 224.50 |
March | 215.50 | 0.50 | 0.48 | 01-MAR-11:39 | 4244.79 | 30.11 | 181.17 | 310.67 | 1267.18 | 17.59 | 4.67 | 271.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:49 | 2726.38 | 15.02 | 0.00 | 355.50 | 1597.46 | 18.50 | 16.83 | 333.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:49 | 2176.38 | 14.72 | 0.00 | 410.67 | 1269.58 | 18.16 | 0.00 | 378.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:40 | 2118.59 | 15.05 | 0.00 | 413.50 | 1223.75 | 18.46 | 0.00 | 376.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:40 | 2116.53 | 14.85 | 0.00 | 421.50 | 1251.54 | 18.30 | 2.50 | 386.33 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 2581.84 | 15.03 | 5.50 | 382.50 | 1462.13 | 18.18 | 8.17 | 351.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 4602.34 | 19.97 | 76.17 | 331.33 | 1763.54 | 18.53 | 12.00 | 306.83 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7271.70 | 34.60 | 216.17 | 280.00 | 2237.33 | 21.05 | 33.67 | 244.33 |
November | 171.33 | 0.50 | 0.48 | 01-NOV-11:39 | 4617.22 | 35.83 | 166.83 | 216.67 | 3894.82 | 37.11 | 167.17 | 176.17 |
December | 131.67 | 0.49 | 0.48 | 02-DEC-08:39 | 3878.98 | 36.83 | 128.50 | 183.67 | 3305.08 | 38.15 | 128.67 | 135.67 |
Annual Sum or Average | 3515.67 | 0.50 | 3469.23 | 21.95 | 1178.33 | 3774.33 | 1846.43 | 21.90 | 705.33 | 3381.67 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 2116.53 | 14.72 | 0.00 | 183.67 | 1223.75 | 17.59 | 0.00 | 135.67 | |
Maximum of Months | 429.00 | 0.51 | 0.48 | 7271.70 | 36.83 | 216.17 | 421.50 | 3894.82 | 38.15 | 189.83 | 386.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 1493.91 | 22.77 | 82.50 | 211.00 | 899.14 | 23.29 | 73.33 | 149.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 1826.01 | 22.64 | 75.33 | 239.67 | 1033.20 | 23.31 | 69.83 | 201.33 |
March | 215.50 | 0.50 | 0.48 | 01-MAR-11:39 | 2050.95 | 21.19 | 71.33 | 305.17 | 1110.52 | 23.37 | 65.00 | 256.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3787.78 | 22.14 | 107.17 | 364.33 | 2254.41 | 24.33 | 92.83 | 344.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:40 | 3921.68 | 22.23 | 134.00 | 423.17 | 1808.60 | 21.93 | 72.17 | 388.33 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:49 | 3948.70 | 22.80 | 139.17 | 421.17 | 1853.02 | 22.76 | 81.50 | 392.33 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3855.87 | 22.33 | 139.67 | 432.67 | 1807.12 | 22.81 | 87.17 | 404.17 |
August | 396.33 | 0.49 | 0.48 | 01-AUG-05:30 | 3727.64 | 22.69 | 127.83 | 391.33 | 1691.61 | 22.27 | 72.00 | 364.67 |
September | 337.67 | 0.49 | 0.48 | 01-SEP-07:40 | 3527.76 | 23.00 | 109.33 | 338.67 | 1978.30 | 23.77 | 85.00 | 311.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2753.93 | 22.88 | 85.00 | 274.17 | 1291.58 | 23.12 | 68.67 | 220.50 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 1532.50 | 22.54 | 64.83 | 205.83 | 890.30 | 23.20 | 68.33 | 140.00 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:39 | 1294.99 | 23.32 | 52.67 | 167.00 | 907.15 | 25.47 | 65.33 | 102.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3171.72 | 22.52 | 1188.83 | 3774.17 | 1608.13 | 23.12 | 901.17 | 3276.17 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 1294.99 | 21.19 | 52.67 | 167.00 | 890.30 | 21.93 | 65.00 | 102.50 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 3948.70 | 23.32 | 139.67 | 432.67 | 2254.41 | 25.47 | 92.83 | 404.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-09:39 | 549.60 | 10.28 | 0.00 | 188.83 | 332.54 | 13.79 | 0.00 | 88.50 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 731.17 | 12.16 | 0.00 | 224.50 | 445.48 | 15.64 | 0.00 | 152.00 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 898.17 | 12.67 | 0.00 | 300.67 | 508.24 | 15.98 | 0.00 | 232.17 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:49 | 1206.26 | 15.02 | 0.00 | 360.83 | 748.04 | 18.44 | 5.17 | 334.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:49 | 1423.54 | 16.94 | 38.00 | 425.67 | 851.49 | 20.19 | 53.50 | 402.50 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:49 | 1617.43 | 18.20 | 58.17 | 428.00 | 963.95 | 21.31 | 79.67 | 405.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1507.87 | 18.06 | 58.83 | 439.17 | 919.17 | 21.21 | 79.50 | 419.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1228.64 | 14.93 | 0.00 | 391.83 | 771.93 | 18.44 | 6.67 | 362.67 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 991.00 | 14.53 | 0.00 | 326.33 | 644.79 | 18.01 | 0.00 | 288.67 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:19 | 831.84 | 13.04 | 0.00 | 263.83 | 518.31 | 16.50 | 0.00 | 185.83 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:50 | 610.31 | 11.03 | 0.00 | 182.33 | 371.56 | 14.56 | 0.00 | 87.33 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-09:50 | 515.92 | 10.23 | 0.00 | 135.17 | 316.08 | 13.93 | 0.00 | 49.50 |
Annual Sum or Average | 3515.67 | 0.50 | 1134.15 | 14.84 | 155.00 | 3667.17 | 692.88 | 18.21 | 224.50 | 3008.50 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 515.92 | 10.23 | 0.00 | 135.17 | 316.08 | 13.79 | 0.00 | 49.50 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 1617.43 | 18.20 | 58.83 | 439.17 | 963.95 | 21.31 | 79.67 | 419.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.53 | 0.48 | 01-JAN-09:39 | 1350.67 | 22.00 | 78.00 | 204.67 | 787.36 | 22.54 | 68.67 | 153.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 2074.48 | 20.33 | 58.33 | 234.17 | 1160.54 | 22.23 | 60.83 | 188.00 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1943.89 | 21.16 | 72.33 | 304.83 | 1070.71 | 22.14 | 54.00 | 255.50 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:40 | 3664.17 | 21.11 | 101.83 | 355.67 | 1701.85 | 21.08 | 50.00 | 332.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3318.98 | 18.71 | 73.83 | 414.00 | 1879.56 | 20.33 | 45.50 | 386.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 3830.00 | 17.72 | 50.33 | 420.00 | 1766.58 | 18.61 | 0.00 | 384.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-05:40 | 3802.20 | 17.61 | 53.17 | 428.67 | 1795.48 | 18.57 | 3.67 | 398.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-06:10 | 3392.42 | 19.70 | 86.83 | 383.17 | 1935.78 | 21.00 | 57.00 | 353.83 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:49 | 3284.75 | 21.50 | 96.83 | 325.33 | 1838.78 | 22.76 | 76.17 | 302.17 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2599.56 | 22.25 | 81.67 | 270.17 | 1207.62 | 22.47 | 64.67 | 216.50 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:39 | 1485.08 | 21.59 | 59.50 | 199.17 | 813.04 | 22.17 | 65.00 | 136.67 |
December | 131.67 | 0.53 | 0.48 | 02-DEC-09:30 | 1071.63 | 19.78 | 37.67 | 161.17 | 572.36 | 20.28 | 36.83 | 88.00 |
Annual Sum or Average | 3515.67 | 0.50 | 2985.87 | 19.93 | 850.33 | 3701.00 | 1539.94 | 20.88 | 582.33 | 3194.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1071.63 | 17.61 | 37.67 | 161.17 | 572.36 | 18.57 | 0.00 | 88.00 | |
Maximum of Months | 429.00 | 0.53 | 0.48 | 3830.00 | 22.25 | 101.83 | 428.67 | 1935.78 | 22.76 | 76.17 | 398.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.51 | 0.48 | 01-JAN-08:39 | 4013.86 | 36.00 | 190.67 | 222.17 | 3403.04 | 37.18 | 189.83 | 196.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5759.58 | 35.70 | 213.33 | 246.17 | 2805.21 | 29.97 | 141.83 | 224.67 |
March | 215.50 | 0.50 | 0.48 | 01-MAR-11:39 | 4248.11 | 30.10 | 181.17 | 310.67 | 1269.70 | 17.57 | 4.67 | 272.33 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:49 | 2730.25 | 14.99 | 0.00 | 355.50 | 1599.94 | 18.48 | 16.17 | 333.17 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:49 | 2179.55 | 14.69 | 0.00 | 410.67 | 1271.54 | 18.15 | 0.00 | 378.83 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:40 | 2121.74 | 15.02 | 0.00 | 413.50 | 1225.66 | 18.45 | 0.00 | 376.67 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:40 | 2119.50 | 14.82 | 0.00 | 421.50 | 1253.40 | 18.28 | 2.33 | 386.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 2585.16 | 15.00 | 5.50 | 382.50 | 1464.26 | 18.17 | 7.83 | 351.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 4605.62 | 19.94 | 76.17 | 331.33 | 1766.05 | 18.51 | 11.33 | 307.00 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7273.99 | 34.59 | 216.17 | 280.00 | 2240.18 | 21.03 | 33.50 | 244.33 |
November | 171.33 | 0.50 | 0.48 | 01-NOV-11:39 | 4618.21 | 35.82 | 166.83 | 216.67 | 3897.09 | 37.10 | 167.17 | 176.17 |
December | 131.67 | 0.49 | 0.48 | 02-DEC-08:39 | 3879.75 | 36.82 | 128.50 | 183.67 | 3306.74 | 38.14 | 128.67 | 135.67 |
Annual Sum or Average | 3515.67 | 0.50 | 3472.01 | 21.93 | 1178.33 | 3774.33 | 1848.61 | 21.89 | 703.33 | 3383.33 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 2119.50 | 14.69 | 0.00 | 183.67 | 1225.66 | 17.57 | 0.00 | 135.67 | |
Maximum of Months | 429.00 | 0.51 | 0.48 | 7273.99 | 36.82 | 216.17 | 421.50 | 3897.09 | 38.14 | 189.83 | 386.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 1494.74 | 22.75 | 82.50 | 211.00 | 900.01 | 23.28 | 73.17 | 149.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 1827.14 | 22.61 | 75.33 | 239.67 | 1034.39 | 23.30 | 69.67 | 201.50 |
March | 215.50 | 0.50 | 0.48 | 01-MAR-11:39 | 2052.99 | 21.17 | 71.33 | 305.33 | 1112.08 | 23.35 | 64.83 | 257.00 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3789.79 | 22.11 | 107.17 | 364.33 | 2256.36 | 24.32 | 92.83 | 344.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:40 | 3924.08 | 22.20 | 134.00 | 423.17 | 1810.55 | 21.92 | 72.17 | 388.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:49 | 3951.28 | 22.78 | 139.17 | 421.17 | 1855.06 | 22.74 | 81.50 | 392.33 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3858.18 | 22.31 | 139.67 | 432.67 | 1809.07 | 22.80 | 87.17 | 404.33 |
August | 396.33 | 0.49 | 0.48 | 01-AUG-05:30 | 3729.44 | 22.66 | 127.83 | 391.33 | 1693.41 | 22.26 | 72.00 | 365.00 |
September | 337.67 | 0.49 | 0.48 | 01-SEP-07:40 | 3529.04 | 22.97 | 109.33 | 338.83 | 1979.94 | 23.76 | 84.83 | 311.50 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2755.21 | 22.86 | 85.00 | 274.33 | 1292.98 | 23.11 | 68.17 | 220.67 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 1533.44 | 22.51 | 64.83 | 206.17 | 891.30 | 23.19 | 68.17 | 140.00 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:39 | 1295.71 | 23.29 | 52.67 | 167.00 | 908.02 | 25.46 | 65.17 | 102.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3173.52 | 22.49 | 1188.83 | 3775.00 | 1609.79 | 23.11 | 899.67 | 3277.83 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 1295.71 | 21.17 | 52.67 | 167.00 | 891.30 | 21.92 | 64.83 | 102.50 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 3951.28 | 23.29 | 139.67 | 432.67 | 2256.36 | 25.46 | 92.83 | 404.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-09:39 | 550.15 | 10.25 | 0.00 | 189.00 | 333.03 | 13.77 | 0.00 | 88.67 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 731.92 | 12.13 | 0.00 | 224.83 | 446.12 | 15.63 | 0.00 | 152.17 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 899.44 | 12.64 | 0.00 | 300.67 | 509.11 | 15.97 | 0.00 | 232.33 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:49 | 1207.40 | 14.99 | 0.00 | 360.83 | 749.04 | 18.43 | 5.00 | 334.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:49 | 1425.01 | 16.91 | 38.00 | 425.67 | 852.67 | 20.18 | 52.83 | 402.67 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:49 | 1619.14 | 18.17 | 58.17 | 428.17 | 965.27 | 21.29 | 78.67 | 405.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1509.32 | 18.04 | 58.83 | 439.17 | 920.38 | 21.20 | 78.17 | 419.17 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1229.70 | 14.90 | 0.00 | 391.83 | 772.91 | 18.42 | 6.17 | 362.83 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 991.73 | 14.50 | 0.00 | 326.33 | 645.56 | 18.00 | 0.00 | 288.67 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:19 | 832.61 | 13.01 | 0.00 | 263.83 | 519.01 | 16.48 | 0.00 | 186.00 |
November | 171.33 | 0.53 | 0.48 | 01-NOV-11:50 | 610.91 | 11.00 | 0.00 | 182.67 | 372.10 | 14.55 | 0.00 | 87.67 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-09:50 | 516.39 | 10.20 | 0.00 | 135.33 | 316.53 | 13.91 | 0.00 | 49.67 |
Annual Sum or Average | 3515.67 | 0.50 | 1135.26 | 14.81 | 155.00 | 3668.33 | 693.82 | 18.20 | 220.83 | 3010.17 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 516.39 | 10.20 | 0.00 | 135.33 | 316.53 | 13.77 | 0.00 | 49.67 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 1619.14 | 18.17 | 58.83 | 439.17 | 965.27 | 21.29 | 78.67 | 419.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.53 | 0.48 | 01-JAN-09:39 | 1351.53 | 21.97 | 78.00 | 204.67 | 788.27 | 22.53 | 68.00 | 153.17 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 2075.62 | 20.30 | 58.33 | 234.17 | 1161.80 | 22.22 | 60.67 | 188.33 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 1945.93 | 21.14 | 72.33 | 304.83 | 1072.29 | 22.12 | 53.83 | 255.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:40 | 3666.19 | 21.08 | 101.83 | 355.67 | 1703.74 | 21.07 | 50.00 | 332.33 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3321.25 | 18.68 | 73.83 | 414.00 | 1881.49 | 20.32 | 45.50 | 386.00 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 3832.57 | 17.69 | 50.33 | 420.17 | 1768.69 | 18.59 | 0.00 | 384.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-05:40 | 3804.39 | 17.58 | 53.17 | 428.67 | 1797.45 | 18.56 | 3.67 | 398.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-06:10 | 3394.44 | 19.67 | 86.83 | 383.17 | 1937.70 | 20.99 | 57.00 | 353.83 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:49 | 3286.27 | 21.47 | 96.83 | 325.33 | 1840.42 | 22.75 | 76.17 | 302.67 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2600.91 | 22.22 | 81.67 | 270.33 | 1209.05 | 22.45 | 64.00 | 216.67 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:39 | 1486.07 | 21.56 | 59.50 | 199.17 | 814.06 | 22.16 | 65.00 | 136.67 |
December | 131.67 | 0.53 | 0.48 | 02-DEC-09:30 | 1072.41 | 19.76 | 37.67 | 161.50 | 573.16 | 20.26 | 36.67 | 88.17 |
Annual Sum or Average | 3515.67 | 0.50 | 2987.69 | 19.91 | 850.33 | 3701.67 | 1541.62 | 20.87 | 580.50 | 3196.67 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1072.41 | 17.58 | 37.67 | 161.50 | 573.16 | 18.56 | 0.00 | 88.17 | |
Maximum of Months | 429.00 | 0.53 | 0.48 | 3832.57 | 22.22 | 101.83 | 428.67 | 1937.70 | 22.75 | 76.17 | 398.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108630E+11 | 35454.44 | 10-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725761E+10 | 27621.97 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486280E+10 | 21822.37 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.765069E+09 | 19326.33 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.619634E+09 | 13552.45 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13386003.61 | 4995.98 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15287.43 | 2.06 | 21-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14364.12 | 1.05 | 29-AUG-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119274E+09 | 9282.41 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134859E+10 | 14109.43 | 07-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393379E+10 | 23364.61 | 29-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797286E+10 | 26611.74 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14364.12 | 1.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108630E+11 | 35454.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 35338893.37 | 3649.60 | 11-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35338893.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35338893.37 | 3649.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 33195089.51 | 8627.49 | 11-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2923976.89 | 1152.75 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7180.18 | 11.97 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6543968.13 | 1719.17 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42670214.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33195089.51 | 8627.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 93112563.94 | 14963.33 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12026654.24 | 2680.74 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 760718.22 | 826.76 | 06-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4795760.68 | 983.10 | 20-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36243912.38 | 14955.02 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93112563.94 | 14963.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153403E+12 | 326648.56 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112038E+12 | 284980.85 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.987131E+11 | 347856.86 | 10-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223050E+11 | 400412.22 | 12-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127156E+11 | 354085.80 | 01-MAY-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127091E+10 | 199812.62 | 28-JUN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.215041E+09 | 46325.77 | 25-JUL-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36540472.00 | 33028.86 | 24-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249309E+10 | 220636.48 | 08-SEP-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255823E+11 | 174420.17 | 30-OCT-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.798976E+11 | 236234.34 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151577E+12 | 268731.86 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 36540472.00 | 33028.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153403E+12 | 400412.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142638E+11 | 105779.22 | 05-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.824464E+10 | 108492.67 | 24-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353009E+10 | 105376.81 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97530281.27 | 16149.33 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.951306E+09 | 98349.94 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.640946E+10 | 106663.35 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188960E+11 | 105791.27 | 08-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.523929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188960E+11 | 108492.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.725610E+10 | 143668.18 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.389198E+10 | 143376.39 | 06-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188677E+10 | 143191.72 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17092856.48 | 11034.00 | 01-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.517106E+09 | 46414.50 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343527E+10 | 143304.06 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106990E+11 | 143714.91 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106990E+11 | 143714.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.625525E+10 | 208194.47 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317889E+10 | 208135.10 | 16-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196298E+10 | 208147.71 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8519077.39 | 2986.56 | 01-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4641751.78 | 4836.38 | 05-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319685E+09 | 38955.15 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301545E+10 | 208091.30 | 30-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118966E+11 | 208229.73 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118966E+11 | 208229.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.506585E+10 | 136751.55 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217835E+10 | 136614.25 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.834074E+09 | 95867.05 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149009E+09 | 7442.76 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208553E+10 | 136571.05 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767657E+10 | 137002.12 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.767657E+10 | 137002.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183151E+11 | 36834.72 | 10-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142972E+11 | 33521.16 | 17-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127359E+11 | 25116.90 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340017E+10 | 22510.73 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213142E+10 | 16647.33 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166724E+09 | 8299.91 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16621116.86 | 3739.24 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15001436.96 | 5364.10 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.431000E+09 | 12740.91 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419555E+10 | 17533.51 | 07-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108678E+11 | 27886.36 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178718E+11 | 29767.77 | 27-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.844443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15001436.96 | 3739.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183151E+11 | 36834.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379499E+10 | 71337.11 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183110E+10 | 71324.32 | 27-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.889631E+09 | 71066.38 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259543E+09 | 70597.30 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153958E+10 | 71061.97 | 20-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.450368E+10 | 71079.55 | 18-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450368E+10 | 71337.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.489194E+10 | 11879.81 | 30-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339705E+10 | 11879.41 | 27-FEB-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225366E+10 | 11873.63 | 20-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394736E+09 | 11787.27 | 11-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128097E+09 | 11757.27 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 800616.68 | 675.07 | 07-JUN-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87016566.27 | 11589.85 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123043E+10 | 11823.76 | 16-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310500E+10 | 11854.83 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554621E+10 | 11879.27 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.554621E+10 | 11879.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276000E+10 | 16850.76 | 17-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182082E+10 | 16839.19 | 27-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125971E+10 | 16818.57 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118607E+09 | 16787.71 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35758080.94 | 16343.59 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113110.73 | 269.76 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13235578.33 | 1939.87 | 21-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.653808E+09 | 16823.29 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177316E+10 | 16824.47 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336980E+10 | 16822.28 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336980E+10 | 16850.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293470E+10 | 25095.61 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192633E+10 | 25114.79 | 27-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162963E+10 | 25083.78 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237540E+09 | 25029.31 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143405E+09 | 25023.74 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4046458.00 | 3978.08 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12784748.81 | 1342.88 | 20-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.741879E+09 | 25046.72 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193128E+10 | 25092.88 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406088E+10 | 25082.88 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406088E+10 | 25114.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205546E+10 | 17095.51 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117921E+10 | 17091.51 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768241E+09 | 17060.45 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75170105.70 | 12235.87 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35828222.14 | 14929.17 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6301393.79 | 529.26 | 07-SEP-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401395E+09 | 17042.90 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116641E+10 | 17094.33 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245219E+10 | 17067.27 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.814020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245219E+10 | 17095.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156357E+10 | 17683.90 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.920901E+09 | 13149.58 | 16-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243973E+09 | 10739.63 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3843320.05 | 6049.48 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3480716.81 | 4450.55 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1934.50 | 1.02 | 06-JUN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1316.20 | 1.01 | 15-JUL-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 544.04 | 0.66 | 23-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 131.93 | 0.66 | 18-SEP-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 539217.14 | 1797.39 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46797136.98 | 4201.76 | 29-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.523169E+09 | 11645.41 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 131.93 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156357E+10 | 17683.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.301884E+10 | 0.301884E+10 | 34543.99 | 17-JAN-12:00 | 34543.99 | 0.06 |
February | 0.00 | 0.00 | 0.458587E+10 | 0.458587E+10 | 34358.11 | 09-FEB-15:00 | 34358.11 | 0.04 |
March | 0.00 | 0.00 | 0.313213E+10 | 0.313213E+10 | 28746.06 | 28-MAR-10:00 | 28746.06 | 0.02 |
April | 0.00 | 0.00 | 0.514489E+10 | 0.513900E+10 | 83646.72 | 30-APR-14:21 | 83646.72 | 0.03 |
May | 0.00 | 0.00 | 0.573107E+10 | 0.573107E+10 | 99069.99 | 22-MAY-15:00 | 99069.99 | 0.07 |
June | 0.00 | 0.00 | 0.181865E+11 | 0.178722E+11 | 133383.33 | 25-JUN-17:41 | 67275.67 | 0.23 |
July | 0.00 | 0.00 | 0.305751E+11 | 0.304746E+11 | 116779.81 | 21-JUL-15:10 | 116779.81 | 0.41 |
August | 0.00 | 0.00 | 0.406616E+11 | 0.404734E+11 | 124232.15 | 14-AUG-15:20 | 124232.15 | 0.49 |
September | 0.00 | 0.00 | 0.191812E+11 | 0.190779E+11 | 87498.33 | 13-SEP-14:30 | 87498.33 | 0.27 |
October | 0.00 | 0.00 | 0.333181E+10 | 0.333181E+10 | 53319.09 | 06-OCT-09:40 | 53319.09 | 0.04 |
November | 0.00 | 0.00 | 0.403626E+10 | 0.403626E+10 | 39994.56 | 03-NOV-14:30 | 39994.56 | 0.03 |
December | 0.00 | 0.00 | 0.627096E+10 | 0.627096E+10 | 39087.53 | 18-DEC-14:10 | 39087.53 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.143856E+12 | 0.143144E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.301884E+10 | 0.301884E+10 | 28746.06 | 28746.06 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.406616E+11 | 0.404734E+11 | 133383.33 | 124232.15 | 0.49 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137888E+10 | 0.137888E+10 | 114865.47 | 20-JAN-12:00 | 114865.47 | 0.00 |
February | 0.00 | 0.00 | 0.445992E+10 | 0.445992E+10 | 161400.50 | 09-FEB-15:20 | 161400.50 | 0.01 |
March | 0.00 | 0.00 | 0.703128E+10 | 0.703128E+10 | 199329.04 | 23-MAR-15:50 | 199329.04 | 0.00 |
April | 0.00 | 0.00 | 0.562983E+11 | 0.562806E+11 | 869576.63 | 30-APR-14:31 | 869576.63 | 0.03 |
May | 0.00 | 0.00 | 0.575190E+11 | 0.575190E+11 | 861204.11 | 22-MAY-15:00 | 861204.11 | 0.09 |
June | 0.00 | 0.00 | 0.154289E+12 | 0.152183E+12 | 1092708.90 | 13-JUN-16:00 | 986007.60 | 0.24 |
July | 0.00 | 0.00 | 0.241156E+12 | 0.240802E+12 | 1037538.44 | 21-JUL-15:30 | 1037538.44 | 0.40 |
August | 0.00 | 0.00 | 0.302673E+12 | 0.302039E+12 | 1006633.24 | 14-AUG-15:30 | 1006633.24 | 0.49 |
September | 0.00 | 0.00 | 0.176155E+12 | 0.174590E+12 | 826442.99 | 13-SEP-14:50 | 826442.99 | 0.30 |
October | 0.00 | 0.00 | 0.522617E+11 | 0.522617E+11 | 576141.11 | 05-OCT-14:05 | 576141.11 | 0.06 |
November | 0.00 | 0.00 | 0.522023E+10 | 0.522023E+10 | 226049.69 | 10-NOV-15:10 | 226049.69 | 0.02 |
December | 0.00 | 0.00 | 53733706.85 | 53733706.85 | 18280.59 | 21-DEC-14:10 | 18280.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105850E+13 | 0.105382E+13 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 53733706.85 | 53733706.85 | 18280.59 | 18280.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.302673E+12 | 0.302039E+12 | 1092708.90 | 1037538.44 | 0.49 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1361862.38 | 1361862.38 | 662.77 | 09-FEB-15:40 | 662.77 | 0.00 |
March | 0.00 | 0.00 | 20163622.10 | 20163622.10 | 6938.17 | 31-MAR-16:00 | 6938.17 | 0.00 |
April | 0.00 | 0.00 | 0.348641E+10 | 0.348641E+10 | 82903.39 | 30-APR-15:22 | 82903.39 | 0.03 |
May | 0.00 | 0.00 | 0.490901E+10 | 0.490901E+10 | 94921.31 | 22-MAY-15:00 | 94921.31 | 0.07 |
June | 0.00 | 0.00 | 0.155576E+11 | 0.153319E+11 | 140373.51 | 25-JUN-18:11 | 68132.48 | 0.21 |
July | 0.00 | 0.00 | 0.245423E+11 | 0.245206E+11 | 121184.05 | 21-JUL-15:30 | 121184.05 | 0.37 |
August | 0.00 | 0.00 | 0.292574E+11 | 0.292234E+11 | 115572.21 | 14-AUG-15:40 | 115572.21 | 0.47 |
September | 0.00 | 0.00 | 0.150758E+11 | 0.149968E+11 | 84322.29 | 13-SEP-14:40 | 84322.29 | 0.26 |
October | 0.00 | 0.00 | 0.588129E+09 | 0.588129E+09 | 19589.15 | 07-OCT-15:00 | 19589.15 | 0.00 |
November | 0.00 | 0.00 | 3341121.87 | 3341121.87 | 2546.09 | 24-NOV-12:00 | 2546.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.934415E+11 | 0.930811E+11 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292574E+11 | 0.292234E+11 | 140373.51 | 121184.05 | 0.47 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 23413772.47 | 23413772.47 | 3750.18 | 25-JAN-15:00 | 3750.18 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 31699921.68 | 29971670.52 | 10611.52 | 18-MAR-06:05 | 4850.69 | 0.00 |
April | 0.00 | 0.00 | 0.115717E+10 | 0.115717E+10 | 30304.97 | 28-APR-15:00 | 30304.97 | 0.01 |
May | 0.00 | 0.00 | 0.438576E+10 | 0.395010E+10 | 58073.94 | 22-MAY-15:00 | 58073.94 | 0.07 |
June | 0.00 | 0.00 | 0.118439E+11 | 0.108116E+11 | 67850.79 | 27-JUN-06:23 | 26887.24 | 0.19 |
July | 0.00 | 0.00 | 0.214951E+11 | 0.195864E+11 | 74859.22 | 10-JUL-06:35 | 58053.69 | 0.34 |
August | 0.00 | 0.00 | 0.260899E+11 | 0.249799E+11 | 73035.73 | 14-AUG-13:10 | 67460.88 | 0.41 |
September | 0.00 | 0.00 | 0.124932E+11 | 0.119409E+11 | 56070.43 | 16-SEP-06:14 | 25362.45 | 0.23 |
October | 0.00 | 0.00 | 0.767957E+09 | 0.671228E+09 | 34032.36 | 20-OCT-06:12 | 16994.02 | 0.02 |
November | 0.00 | 0.00 | 60100441.57 | 52126610.10 | 29828.50 | 24-NOV-07:11 | 16453.89 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.783483E+11 | 0.732029E+11 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.260899E+11 | 0.249799E+11 | 74859.22 | 67460.88 | 0.41 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.382837E+10 | 0.382827E+10 | 3039.91 | 10-JAN-17:05 | 3039.91 | 0.00 |
February | 0.00 | 0.00 | 0.608728E+10 | 0.603087E+10 | 5072.89 | 20-FEB-16:07 | 5072.89 | 0.00 |
March | 0.00 | 0.00 | 0.108178E+11 | 0.104464E+11 | 5494.80 | 31-MAR-23:10 | 5494.80 | 0.00 |
April | 0.00 | 0.00 | 0.450483E+11 | 0.429606E+11 | 320727.84 | 30-APR-17:31 | 320727.84 | 0.00 |
May | 0.00 | 0.00 | 0.223065E+10 | 0.221108E+10 | 46000.01 | 22-MAY-15:00 | 42461.71 | 0.00 |
June | 0.00 | 0.00 | 0.183959E+11 | 0.157453E+11 | 226519.87 | 13-JUN-17:00 | 223047.80 | 0.00 |
July | 0.00 | 0.00 | 0.868795E+11 | 0.719444E+11 | 316905.35 | 21-JUL-16:00 | 316905.35 | 0.00 |
August | 0.00 | 0.00 | 0.287308E+12 | 0.213350E+12 | 411522.92 | 14-AUG-17:00 | 411522.92 | 0.00 |
September | 0.00 | 0.00 | 0.949780E+09 | 0.920170E+09 | 16806.39 | 27-SEP-16:00 | 16806.39 | 0.00 |
October | 0.00 | 0.00 | 0.311349E+10 | 0.303956E+10 | 5333.04 | 31-OCT-23:10 | 5292.02 | 0.00 |
November | 0.00 | 0.00 | 0.742704E+10 | 0.707255E+10 | 5378.89 | 16-NOV-22:50 | 5282.69 | 0.00 |
December | 0.00 | 0.00 | 0.140711E+11 | 0.131709E+11 | 5989.05 | 17-DEC-18:20 | 5491.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.486157E+12 | 0.390721E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.949780E+09 | 0.920170E+09 | 3039.91 | 3039.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287308E+12 | 0.213350E+12 | 411522.92 | 411522.92 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.434928E+10 | 0.434772E+10 | 2399.99 | 01-JAN-16:10 | 2394.39 | 0.00 |
February | 0.00 | 0.00 | 0.879653E+10 | 0.879526E+10 | 4618.77 | 19-FEB-16:57 | 4618.77 | 0.00 |
March | 0.00 | 0.00 | 0.150676E+11 | 0.150673E+11 | 7598.19 | 31-MAR-24:00 | 7598.19 | 0.00 |
April | 0.00 | 0.00 | 0.200110E+11 | 0.200103E+11 | 8921.26 | 30-APR-19:02 | 8921.26 | 0.00 |
May | 0.00 | 0.00 | 0.544628E+10 | 0.542632E+10 | 3936.03 | 31-MAY-24:00 | 3936.03 | 0.00 |
June | 0.00 | 0.00 | 0.105350E+11 | 0.104501E+11 | 5773.30 | 30-JUN-24:00 | 5773.30 | 0.00 |
July | 0.00 | 0.00 | 0.161401E+11 | 0.160280E+11 | 7825.91 | 31-JUL-24:00 | 7825.91 | 0.00 |
August | 0.00 | 0.00 | 0.211452E+11 | 0.210068E+11 | 8882.28 | 13-AUG-18:03 | 8857.38 | 0.00 |
September | 0.00 | 0.00 | 0.544591E+10 | 0.538149E+10 | 3827.69 | 30-SEP-24:00 | 3827.69 | 0.00 |
October | 0.00 | 0.00 | 0.102798E+11 | 0.102533E+11 | 5675.99 | 31-OCT-24:00 | 5675.99 | 0.00 |
November | 0.00 | 0.00 | 0.146237E+11 | 0.146080E+11 | 6252.60 | 19-NOV-16:00 | 6252.60 | 0.00 |
December | 0.00 | 0.00 | 0.199153E+11 | 0.199151E+11 | 8007.78 | 25-DEC-15:05 | 8007.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151756E+12 | 0.151290E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.434928E+10 | 0.434772E+10 | 2399.99 | 2394.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211452E+11 | 0.210068E+11 | 8921.26 | 8921.26 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.233584E+11 | 0.233431E+11 | 19401.55 | 19-JAN-16:20 | 19401.55 | 0.00 |
February | 0.00 | 0.00 | 0.692307E+11 | 0.692175E+11 | 40170.53 | 27-FEB-17:00 | 40170.53 | 0.00 |
March | 0.00 | 0.00 | 0.129887E+12 | 0.129884E+12 | 69185.57 | 31-MAR-23:30 | 69185.57 | 0.00 |
April | 0.00 | 0.00 | 0.185048E+12 | 0.185040E+12 | 85457.67 | 30-APR-18:10 | 85457.67 | 0.00 |
May | 0.00 | 0.00 | 0.464091E+11 | 0.462117E+11 | 36472.44 | 31-MAY-23:50 | 36472.44 | 0.00 |
June | 0.00 | 0.00 | 0.968565E+11 | 0.960139E+11 | 53245.55 | 30-JUN-23:40 | 53245.55 | 0.00 |
July | 0.00 | 0.00 | 0.150710E+12 | 0.149597E+12 | 73817.52 | 31-JUL-24:00 | 73817.52 | 0.00 |
August | 0.00 | 0.00 | 0.198921E+12 | 0.197550E+12 | 83088.08 | 13-AUG-18:03 | 82847.18 | 0.00 |
September | 0.00 | 0.00 | 0.466244E+11 | 0.459938E+11 | 34652.30 | 30-SEP-23:30 | 34652.30 | 0.00 |
October | 0.00 | 0.00 | 0.868329E+11 | 0.865698E+11 | 49922.95 | 31-OCT-23:50 | 49922.95 | 0.00 |
November | 0.00 | 0.00 | 0.123108E+12 | 0.122951E+12 | 56029.18 | 10-NOV-16:10 | 55810.55 | 0.00 |
December | 0.00 | 0.00 | 0.166697E+12 | 0.166695E+12 | 70690.28 | 21-DEC-15:20 | 70690.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132368E+13 | 0.131907E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.233584E+11 | 0.233431E+11 | 19401.55 | 19401.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198921E+12 | 0.197550E+12 | 85457.67 | 85457.67 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.651954E+09 | 0.650979E+09 | 1829.24 | 19-JAN-16:30 | 1829.24 | 0.00 |
February | 0.00 | 0.00 | 0.508850E+10 | 0.508726E+10 | 3790.09 | 24-FEB-17:00 | 3790.09 | 0.00 |
March | 0.00 | 0.00 | 0.113310E+11 | 0.113307E+11 | 6480.60 | 31-MAR-23:20 | 6480.60 | 0.00 |
April | 0.00 | 0.00 | 0.177292E+11 | 0.177285E+11 | 8667.89 | 30-APR-18:21 | 8667.89 | 0.00 |
May | 0.00 | 0.00 | 0.397427E+10 | 0.395464E+10 | 3510.30 | 31-MAY-23:20 | 3510.30 | 0.00 |
June | 0.00 | 0.00 | 0.938254E+10 | 0.929841E+10 | 5123.88 | 30-JUN-23:20 | 5123.88 | 0.00 |
July | 0.00 | 0.00 | 0.148193E+11 | 0.147081E+11 | 7236.46 | 31-JUL-23:20 | 7236.46 | 0.00 |
August | 0.00 | 0.00 | 0.196337E+11 | 0.194968E+11 | 8437.67 | 13-AUG-18:03 | 8413.40 | 0.00 |
September | 0.00 | 0.00 | 0.404001E+10 | 0.397773E+10 | 2964.00 | 30-SEP-23:20 | 2964.00 | 0.00 |
October | 0.00 | 0.00 | 0.718153E+10 | 0.715589E+10 | 4438.78 | 31-OCT-23:20 | 4438.78 | 0.00 |
November | 0.00 | 0.00 | 0.104228E+11 | 0.104074E+11 | 5532.65 | 10-NOV-16:10 | 5511.01 | 0.00 |
December | 0.00 | 0.00 | 0.145364E+11 | 0.145362E+11 | 6819.71 | 21-DEC-15:20 | 6819.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118791E+12 | 0.118333E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.651954E+09 | 0.650979E+09 | 1829.24 | 1829.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196337E+11 | 0.194968E+11 | 8667.89 | 8667.89 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 86747.84 | 906223.60 | 11-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 66701.52 | 922148.36 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 48867.55 | 800484.55 | 06-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 10518.01 | 507057.22 | 12-APR-13:05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5877.31 | 457017.53 | 01-MAY-09:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 561.09 | 227672.22 | 28-JUN-09:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 80.53 | 45375.10 | 25-JUL-09:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.44 | 37717.61 | 24-AUG-06:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1215.92 | 268434.64 | 08-SEP-09:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13505.40 | 411402.64 | 23-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 45759.98 | 1054078.47 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 91786.85 | 1002835.51 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 30856.70 | ||||
Minimum of Months | 0.00 | 0.00 | 18.44 | 37717.61 | ||
Maximum of Months | 0.00 | 0.00 | 91786.85 | 1054078.47 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1907.68 | 135647.09 | 20-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 4174.89 | 193167.78 | 09-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4183.47 | 200597.49 | 23-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25849.04 | 817822.81 | 28-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27572.59 | 1485327.83 | 22-MAY-14:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 79731.81 | 1402862.42 | 13-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121466.21 | 1330672.69 | 21-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 150940.70 | 1603019.21 | 28-AUG-14:05 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 88692.30 | 1197483.86 | 22-SEP-14:05 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21648.49 | 593627.88 | 05-OCT-14:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3930.09 | 224298.73 | 03-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2906.49 | 59757.41 | 21-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 44691.48 | 0.00 | ||||
Minimum of Months | 1907.68 | 59757.41 | 0.00 | 0.00 | ||
Maximum of Months | 150940.70 | 1603019.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1623.46 | 135889.29 | 20-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3726.86 | 192335.74 | 09-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 3778.95 | 198117.22 | 23-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25731.40 | 1075509.57 | 30-APR-14:31 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27462.41 | 1622275.22 | 22-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 80070.00 | 1780016.08 | 21-JUN-13:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121000.30 | 1670500.21 | 21-JUL-10:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 150598.47 | 1890023.10 | 28-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 88381.94 | 1329288.19 | 12-SEP-12:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21220.19 | 602717.53 | 05-OCT-14:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3593.20 | 226965.23 | 03-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2354.90 | 58208.69 | 21-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 44402.32 | 0.00 | ||||
Minimum of Months | 1623.46 | 58208.69 | 0.00 | 0.00 | ||
Maximum of Months | 150598.47 | 1890023.10 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19295.06 | 35417.73 | 27-JAN-20:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49636.37 | 90615.02 | 04-FEB-16:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80360.38 | 126143.97 | 09-MAR-07:15 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 140515.32 | 1066701.30 | 30-APR-18:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34051.04 | 441082.79 | 22-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 89088.18 | 975584.74 | 13-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 174275.65 | 1355014.38 | 22-JUL-18:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 314504.24 | 1397459.02 | 14-AUG-17:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 45124.18 | 337955.57 | 13-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 53021.66 | 117599.73 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77176.24 | 92264.76 | 03-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102069.07 | 148658.68 | 01-DEC-20:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 98772.13 | 0.00 | ||||
Minimum of Months | 19295.06 | 35417.73 | 0.00 | 0.00 | ||
Maximum of Months | 314504.24 | 1397459.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14672.84 | 52248.30 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14859.05 | 52330.96 | 14-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15688.43 | 52245.88 | 01-MAR-12:35 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14420.48 | 51469.97 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14512.95 | 50340.24 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14472.79 | 48910.00 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13036.65 | 47643.80 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14169.96 | 46995.40 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13376.28 | 47647.94 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13634.03 | 48915.83 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14208.61 | 50301.09 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14049.77 | 51474.56 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 14255.07 | ||||
Minimum of Months | 0.00 | 0.00 | 13036.65 | 46995.40 | ||
Maximum of Months | 0.00 | 0.00 | 15688.43 | 52330.96 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 605.61 | 156815.80 | 20-JAN-14:00 | 2515.52 | 105299.42 | 10-JAN-06:40 |
February | 1425.59 | 225135.68 | 09-FEB-15:20 | 3839.35 | 105250.99 | 13-FEB-06:40 |
March | 1874.48 | 235034.67 | 23-MAR-16:00 | 3616.58 | 101624.08 | 25-MAR-06:00 |
April | 27770.68 | 935821.69 | 28-APR-15:20 | 1183.47 | 91067.69 | 08-APR-09:30 |
May | 30842.98 | 1826918.21 | 22-MAY-14:05 | 1143.48 | 76131.93 | 06-MAY-09:20 |
June | 96771.31 | 2174086.70 | 13-JUN-16:00 | 844.51 | 67379.96 | 08-JUN-06:50 |
July | 144341.41 | 1805926.78 | 22-JUL-15:10 | 1379.06 | 77228.04 | 31-JUL-05:40 |
August | 176700.84 | 1888667.96 | 28-AUG-14:05 | 719.86 | 70442.34 | 30-AUG-05:40 |
September | 102605.48 | 1813882.51 | 27-SEP-14:40 | 1114.17 | 84426.09 | 21-SEP-05:40 |
October | 23121.47 | 676789.51 | 05-OCT-14:10 | 1317.13 | 90824.28 | 23-OCT-05:30 |
November | 2557.43 | 261325.20 | 03-NOV-14:40 | 2715.89 | 91193.59 | 16-NOV-06:30 |
December | 247.44 | 28606.51 | 19-DEC-16:30 | 5580.25 | 112080.17 | 29-DEC-06:30 |
Annual Sum or Average | 51070.75 | 2158.00 | ||||
Minimum of Months | 247.44 | 28606.51 | 719.86 | 67379.96 | ||
Maximum of Months | 176700.84 | 2174086.70 | 5580.25 | 112080.17 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.359144E+10 | 0.31 | 11098.43 | 10-JAN-06:01 | 1.27 |
February | 0.386636E+10 | 0.34 | 8502.25 | 27-FEB-14:50 | 1.07 |
March | 0.508478E+10 | 0.37 | 9464.18 | 24-MAR-05:02 | 1.15 |
April | 0.973861E+10 | 0.54 | 19149.70 | 28-APR-14:50 | 1.78 |
May | 0.761519E+10 | 0.46 | 15452.18 | 22-MAY-14:50 | 1.55 |
June | 0.981419E+10 | 0.55 | 19149.70 | 21-JUN-13:05 | 1.78 |
July | 0.115241E+11 | 0.59 | 19149.70 | 24-JUL-05:02 | 1.78 |
August | 0.135325E+11 | 0.67 | 19149.70 | 14-AUG-13:30 | 1.77 |
September | 0.838320E+10 | 0.49 | 17031.32 | 11-SEP-14:50 | 1.65 |
October | 0.596319E+10 | 0.39 | 13962.19 | 03-OCT-14:50 | 1.46 |
November | 0.463922E+10 | 0.35 | 10286.29 | 09-NOV-06:02 | 1.20 |
December | 0.422002E+10 | 0.33 | 12378.42 | 11-DEC-06:01 | 1.36 |
Annual Sum or Average | 0.879728E+11 | 0.45 | |||
Minimum of Months | 0.359144E+10 | 0.31 | 8502.25 | 1.07 | |
Maximum of Months | 0.135325E+11 | 0.67 | 19149.70 | 1.78 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.232736E+11 | 0.28 | 78211.29 | 20-JAN-06:02 | 1.08 |
February | 0.235508E+11 | 0.29 | 110002.61 | 24-FEB-06:02 | 1.33 |
March | 0.267357E+11 | 0.30 | 90144.88 | 27-MAR-05:02 | 1.18 |
April | 0.530504E+11 | 0.39 | 152881.28 | 28-APR-15:00 | 1.63 |
May | 0.559276E+11 | 0.41 | 131568.63 | 23-MAY-14:05 | 1.48 |
June | 0.683242E+11 | 0.46 | 175278.76 | 21-JUN-13:05 | 1.78 |
July | 0.737046E+11 | 0.47 | 147834.72 | 21-JUL-15:20 | 1.59 |
August | 0.817137E+11 | 0.50 | 151570.85 | 14-AUG-15:20 | 1.62 |
September | 0.636483E+11 | 0.44 | 156173.87 | 12-SEP-15:20 | 1.65 |
October | 0.359118E+11 | 0.32 | 106887.36 | 03-OCT-15:10 | 1.30 |
November | 0.240521E+11 | 0.28 | 97394.50 | 17-NOV-06:03 | 1.24 |
December | 0.211731E+11 | 0.27 | 35525.07 | 11-DEC-06:01 | 0.69 |
Annual Sum or Average | 0.551066E+12 | 0.37 | |||
Minimum of Months | 0.211731E+11 | 0.27 | 35525.07 | 0.69 | |
Maximum of Months | 0.817137E+11 | 0.50 | 175278.76 | 1.78 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.233872E+10 | 0.30 | 4665.03 | 23-JAN-05:52 | 0.75 |
February | 0.209157E+10 | 0.29 | 4665.03 | 13-FEB-05:22 | 0.75 |
March | 0.231121E+10 | 0.30 | 4665.03 | 06-MAR-05:11 | 0.75 |
April | 0.395560E+10 | 0.33 | 14633.30 | 28-APR-14:50 | 1.48 |
May | 0.450344E+10 | 0.36 | 13842.79 | 22-MAY-15:20 | 1.43 |
June | 0.594770E+10 | 0.41 | 19599.12 | 21-JUN-13:05 | 1.78 |
July | 0.658448E+10 | 0.42 | 15789.26 | 21-JUL-15:30 | 1.55 |
August | 0.691254E+10 | 0.44 | 15660.03 | 14-AUG-15:20 | 1.54 |
September | 0.487210E+10 | 0.37 | 14459.47 | 12-SEP-15:20 | 1.46 |
October | 0.259581E+10 | 0.29 | 7278.07 | 03-OCT-14:50 | 0.97 |
November | 0.211601E+10 | 0.28 | 4665.03 | 20-NOV-06:03 | 0.75 |
December | 0.231647E+10 | 0.30 | 4665.03 | 11-DEC-05:23 | 0.75 |
Annual Sum or Average | 0.465456E+11 | 0.34 | |||
Minimum of Months | 0.209157E+10 | 0.28 | 4665.03 | 0.75 | |
Maximum of Months | 0.691254E+10 | 0.44 | 19599.12 | 1.78 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.521914E+10 | 0.44 | 10954.81 | 02-JAN-07:03 | 1.79 |
February | 0.512820E+10 | 0.47 | 10954.81 | 01-FEB-07:05 | 1.80 |
March | 0.842061E+10 | 0.61 | 10954.81 | 01-MAR-07:05 | 1.80 |
April | 0.122156E+11 | 0.80 | 10954.81 | 01-APR-06:05 | 1.80 |
May | 0.113254E+11 | 0.74 | 10954.81 | 01-MAY-06:05 | 1.80 |
June | 0.126099E+11 | 0.83 | 10954.81 | 01-JUN-06:10 | 1.79 |
July | 0.103410E+11 | 0.69 | 10954.81 | 01-JUL-06:10 | 1.79 |
August | 0.119679E+11 | 0.79 | 10954.81 | 01-AUG-06:10 | 1.79 |
September | 0.120304E+11 | 0.79 | 10954.81 | 01-SEP-06:10 | 1.79 |
October | 0.124250E+11 | 0.79 | 10954.81 | 02-OCT-06:10 | 1.79 |
November | 0.111803E+11 | 0.75 | 10954.81 | 01-NOV-06:05 | 1.80 |
December | 0.821276E+10 | 0.58 | 10954.81 | 01-DEC-07:05 | 1.80 |
Annual Sum or Average | 0.121076E+12 | 0.69 | |||
Minimum of Months | 0.512820E+10 | 0.44 | 10954.81 | 1.79 | |
Maximum of Months | 0.126099E+11 | 0.83 | 10954.81 | 1.80 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109078E+12 | 1.36 | 40725.17 | 01-JAN-00:05 | 1.36 |
February | 0.985223E+11 | 1.36 | 40725.17 | 01-FEB-00:10 | 1.36 |
March | 0.109078E+12 | 1.36 | 40725.17 | 01-MAR-00:30 | 1.36 |
April | 0.105560E+12 | 1.36 | 40725.17 | 01-APR-00:10 | 1.37 |
May | 0.109078E+12 | 1.36 | 40725.17 | 01-MAY-00:10 | 1.36 |
June | 0.105560E+12 | 1.36 | 40725.17 | 01-JUN-00:20 | 1.36 |
July | 0.109078E+12 | 1.36 | 40725.17 | 01-JUL-00:10 | 1.36 |
August | 0.109078E+12 | 1.36 | 40725.17 | 01-AUG-00:10 | 1.36 |
September | 0.105560E+12 | 1.36 | 40725.17 | 01-SEP-00:10 | 1.36 |
October | 0.109078E+12 | 1.36 | 40725.17 | 01-OCT-00:10 | 1.36 |
November | 0.105560E+12 | 1.36 | 40725.17 | 01-NOV-00:10 | 1.36 |
December | 0.109078E+12 | 1.36 | 40725.17 | 01-DEC-00:10 | 1.36 |
Annual Sum or Average | 0.128431E+13 | 1.36 | |||
Minimum of Months | 0.985223E+11 | 1.36 | 40725.17 | 1.36 | |
Maximum of Months | 0.109078E+12 | 1.36 | 40725.17 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150983E+10 | 0.93 | 563.71 | 01-JAN-00:05 | 0.92 |
February | 0.136372E+10 | 0.93 | 563.71 | 01-FEB-00:10 | 0.93 |
March | 0.150983E+10 | 0.93 | 563.71 | 01-MAR-00:10 | 0.92 |
April | 0.146112E+10 | 0.93 | 563.71 | 01-APR-00:10 | 0.93 |
May | 0.150983E+10 | 0.92 | 563.71 | 01-MAY-00:10 | 0.92 |
June | 0.146112E+10 | 0.92 | 563.71 | 01-JUN-00:10 | 0.92 |
July | 0.150983E+10 | 0.92 | 563.71 | 01-JUL-00:10 | 0.92 |
August | 0.150983E+10 | 0.92 | 563.71 | 01-AUG-00:10 | 0.92 |
September | 0.146112E+10 | 0.92 | 563.71 | 01-SEP-00:10 | 0.92 |
October | 0.150983E+10 | 0.92 | 563.71 | 01-OCT-00:10 | 0.93 |
November | 0.146112E+10 | 0.92 | 563.71 | 01-NOV-00:10 | 0.93 |
December | 0.150983E+10 | 0.93 | 563.71 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.177770E+11 | 0.92 | |||
Minimum of Months | 0.136372E+10 | 0.92 | 563.71 | 0.92 | |
Maximum of Months | 0.150983E+10 | 0.93 | 563.71 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145065E+11 | 0.93 | 5416.10 | 01-JAN-00:05 | 0.92 |
February | 0.131026E+11 | 0.93 | 5416.10 | 01-FEB-00:10 | 0.93 |
March | 0.145065E+11 | 0.93 | 5416.10 | 01-MAR-00:10 | 0.92 |
April | 0.140385E+11 | 0.93 | 5416.10 | 01-APR-00:10 | 0.93 |
May | 0.145065E+11 | 0.92 | 5416.10 | 01-MAY-00:10 | 0.92 |
June | 0.140385E+11 | 0.92 | 5416.10 | 01-JUN-00:10 | 0.92 |
July | 0.145065E+11 | 0.92 | 5416.10 | 01-JUL-00:10 | 0.92 |
August | 0.145065E+11 | 0.92 | 5416.10 | 01-AUG-00:10 | 0.92 |
September | 0.140385E+11 | 0.92 | 5416.10 | 01-SEP-00:10 | 0.92 |
October | 0.145065E+11 | 0.92 | 5416.10 | 01-OCT-00:10 | 0.93 |
November | 0.140385E+11 | 0.92 | 5416.10 | 01-NOV-00:10 | 0.93 |
December | 0.145065E+11 | 0.93 | 5416.10 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.170802E+12 | 0.92 | |||
Minimum of Months | 0.131026E+11 | 0.92 | 5416.10 | 0.92 | |
Maximum of Months | 0.145065E+11 | 0.93 | 5416.10 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147045E+10 | 0.93 | 549.00 | 01-JAN-00:05 | 0.92 |
February | 0.132815E+10 | 0.93 | 549.00 | 01-FEB-00:10 | 0.93 |
March | 0.147045E+10 | 0.93 | 549.00 | 01-MAR-00:10 | 0.92 |
April | 0.142302E+10 | 0.93 | 549.00 | 01-APR-00:10 | 0.93 |
May | 0.147045E+10 | 0.92 | 549.00 | 01-MAY-00:10 | 0.92 |
June | 0.142302E+10 | 0.92 | 549.00 | 01-JUN-00:10 | 0.92 |
July | 0.147045E+10 | 0.92 | 549.00 | 01-JUL-00:10 | 0.92 |
August | 0.147045E+10 | 0.92 | 549.00 | 01-AUG-00:10 | 0.92 |
September | 0.142302E+10 | 0.92 | 549.00 | 01-SEP-00:10 | 0.92 |
October | 0.147045E+10 | 0.92 | 549.00 | 01-OCT-00:10 | 0.93 |
November | 0.142302E+10 | 0.92 | 549.00 | 01-NOV-00:10 | 0.93 |
December | 0.147045E+10 | 0.93 | 549.00 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173134E+11 | 0.92 | |||
Minimum of Months | 0.132815E+10 | 0.92 | 549.00 | 0.92 | |
Maximum of Months | 0.147045E+10 | 0.93 | 549.00 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 28256547.78 | 25685201.93 | 383.84 | 10-JAN-06:01 | 348.91 | 348.91 | 42.00 | 5.13 |
February | 13393380.04 | 12174582.46 | 362.50 | 27-FEB-06:02 | 329.52 | 329.52 | 41.61 | 5.00 |
March | 8308270.66 | 7552218.03 | 352.88 | 06-MAR-06:02 | 320.77 | 320.77 | 43.23 | 4.94 |
April | 1330782.22 | 1209681.04 | 83.19 | 12-APR-13:05 | 75.62 | 75.62 | 33.28 | 2.49 |
May | 674252.49 | 612895.51 | 65.45 | 01-MAY-09:05 | 59.49 | 59.49 | 32.37 | 2.20 |
June | 52614.35 | 47826.44 | 16.23 | 28-JUN-09:10 | 14.75 | 14.75 | 28.50 | 1.02 |
July | 6641.27 | 6036.91 | 1.50 | 25-JUL-09:05 | 1.36 | 1.36 | 25.15 | 0.19 |
August | 1440.73 | 1309.62 | 1.19 | 24-AUG-06:05 | 1.08 | 1.08 | 24.97 | 0.16 |
September | 122408.26 | 111269.11 | 21.18 | 08-SEP-09:30 | 19.25 | 19.25 | 28.07 | 1.19 |
October | 1665846.74 | 1514254.68 | 59.48 | 23-OCT-05:03 | 54.07 | 54.07 | 35.02 | 2.09 |
November | 8859752.31 | 8053514.85 | 363.27 | 27-NOV-06:03 | 330.21 | 330.21 | 42.22 | 5.01 |
December | 24231367.73 | 22026313.27 | 377.03 | 18-DEC-06:01 | 342.72 | 342.72 | 42.45 | 5.09 |
Annual Sum or Average | 86903304.57 | 78995103.86 | ||||||
Minimum of Months | 1440.73 | 1309.62 | 1.19 | 1.08 | 1.08 | 24.97 | 0.16 | |
Maximum of Months | 28256547.78 | 25685201.93 | 383.84 | 348.91 | 348.91 | 43.23 | 5.13 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 703567.90 | 639543.22 | 35.28 | 20-JAN-15:50 | 32.07 | 32.07 | 6.70 | 3.95 |
February | 1460959.49 | 1328012.18 | 54.45 | 09-FEB-15:20 | 49.49 | 49.49 | 6.70 | 5.07 |
March | 1466380.58 | 1332939.95 | 40.13 | 23-MAR-15:50 | 36.48 | 36.48 | 6.70 | 4.26 |
April | 37251357.15 | 33861483.65 | 3551.44 | 28-APR-14:50 | 3228.26 | 3228.26 | 8.55 | 36.54 |
May | 66914756.44 | 60825513.60 | 4745.46 | 22-MAY-13:50 | 4313.62 | 4313.62 | 10.61 | 41.09 |
June | 0.220106E+09 | 0.200076E+09 | 8377.20 | 21-JUN-13:05 | 7614.87 | 7614.87 | 11.36 | 51.51 |
July | 0.315696E+09 | 0.286968E+09 | 3679.59 | 21-JUL-10:30 | 3344.74 | 3344.74 | 11.68 | 37.07 |
August | 0.355254E+09 | 0.322926E+09 | 6538.15 | 28-AUG-13:40 | 5943.18 | 5943.18 | 10.04 | 46.71 |
September | 0.221232E+09 | 0.201100E+09 | 3844.61 | 12-SEP-12:50 | 3494.75 | 3494.75 | 9.16 | 37.74 |
October | 30588545.55 | 27804987.90 | 923.68 | 03-OCT-14:05 | 839.63 | 839.63 | 6.71 | 20.63 |
November | 2388315.74 | 2170979.01 | 159.12 | 10-NOV-15:10 | 144.64 | 144.64 | 6.70 | 8.98 |
December | 679013.00 | 617222.82 | 14.87 | 21-DEC-14:10 | 13.52 | 13.52 | 6.70 | 2.30 |
Annual Sum or Average | 0.125374E+10 | 0.113965E+10 | ||||||
Minimum of Months | 679013.00 | 617222.82 | 14.87 | 13.52 | 13.52 | 6.70 | 2.30 | |
Maximum of Months | 0.355254E+09 | 0.322926E+09 | 8377.20 | 7614.87 | 7614.87 | 11.68 | 51.51 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.838635E+09 | 0.762319E+09 | 2882.90 | 02-JAN-08:10 | 2620.55 | 2620.55 | 6.72 | 25.76 |
February | 0.119467E+10 | 0.108596E+10 | 2882.90 | 01-FEB-11:00 | 2620.55 | 2620.55 | 6.73 | 25.76 |
March | 0.120981E+10 | 0.109972E+10 | 2882.90 | 01-MAR-10:00 | 2620.55 | 2620.55 | 6.73 | 25.76 |
April | 0.122223E+10 | 0.111101E+10 | 2882.90 | 01-APR-13:25 | 2620.55 | 2620.55 | 7.31 | 25.76 |
May | 0.129364E+10 | 0.117592E+10 | 2882.90 | 01-MAY-09:10 | 2620.55 | 2620.55 | 7.20 | 25.76 |
June | 0.233727E+10 | 0.212458E+10 | 2882.90 | 01-JUN-05:02 | 2620.55 | 2620.55 | 6.73 | 25.76 |
July | 0.388132E+10 | 0.352812E+10 | 2882.90 | 01-JUL-05:05 | 2620.55 | 2620.55 | 6.72 | 25.76 |
August | 0.427096E+10 | 0.388231E+10 | 2882.90 | 01-AUG-04:12 | 2620.55 | 2620.55 | 6.86 | 25.76 |
September | 0.280973E+10 | 0.255404E+10 | 2882.90 | 01-SEP-04:12 | 2620.55 | 2620.55 | 7.03 | 25.76 |
October | 0.131091E+10 | 0.119162E+10 | 2882.90 | 01-OCT-10:32 | 2620.55 | 2620.55 | 7.26 | 25.76 |
November | 0.962283E+09 | 0.874715E+09 | 2882.90 | 01-NOV-07:20 | 2620.55 | 2620.55 | 6.79 | 25.76 |
December | 0.162567E+10 | 0.147773E+10 | 2882.90 | 01-DEC-10:20 | 2620.55 | 2620.55 | 6.73 | 25.76 |
Annual Sum or Average | 0.229571E+11 | 0.208680E+11 | ||||||
Minimum of Months | 0.838635E+09 | 0.762319E+09 | 2882.90 | 2620.55 | 2620.55 | 6.72 | 25.76 | |
Maximum of Months | 0.427096E+10 | 0.388231E+10 | 2882.90 | 2620.55 | 2620.55 | 7.31 | 25.76 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 7.78 | 0.00 |
May | 24216346.92 | 22012659.35 | 2882.90 | 22-MAY-13:50 | 2620.55 | 2620.55 | 14.86 | 12.88 |
June | 0.184217E+09 | 0.167453E+09 | 2882.90 | 12-JUN-12:30 | 2620.55 | 2620.55 | 15.63 | 12.88 |
July | 0.192001E+09 | 0.174529E+09 | 2882.90 | 10-JUL-08:20 | 2620.55 | 2620.55 | 15.36 | 12.88 |
August | 0.132325E+09 | 0.120283E+09 | 2882.90 | 14-AUG-09:50 | 2620.55 | 2620.55 | 15.47 | 12.88 |
September | 0.156541E+09 | 0.142296E+09 | 2882.90 | 11-SEP-13:40 | 2620.55 | 2620.55 | 15.22 | 12.88 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 7.61 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.89 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.75 | 0.00 |
Annual Sum or Average | 0.689301E+09 | 0.626575E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.192001E+09 | 0.174529E+09 | 2882.90 | 2620.55 | 2620.55 | 15.63 | 12.88 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-JAN-00:05 | 3374.24 | 3374.24 | 18.60 | 15.66 |
February | 0.898014E+10 | 0.816295E+10 | 3712.03 | 01-FEB-00:10 | 3374.24 | 3374.24 | 19.16 | 15.66 |
March | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-MAR-00:10 | 3374.24 | 3374.24 | 19.74 | 15.66 |
April | 0.962158E+10 | 0.874602E+10 | 3712.03 | 01-APR-00:10 | 3374.24 | 3374.24 | 20.39 | 15.66 |
May | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-MAY-00:10 | 3374.24 | 3374.24 | 19.03 | 15.66 |
June | 0.962158E+10 | 0.874602E+10 | 3712.03 | 01-JUN-00:10 | 3374.24 | 3374.24 | 19.44 | 15.66 |
July | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-JUL-00:10 | 3374.24 | 3374.24 | 19.82 | 15.66 |
August | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-AUG-00:10 | 3374.24 | 3374.24 | 20.36 | 15.66 |
September | 0.962158E+10 | 0.874602E+10 | 3712.03 | 01-SEP-00:10 | 3374.24 | 3374.24 | 18.93 | 15.66 |
October | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-OCT-00:10 | 3374.24 | 3374.24 | 19.40 | 15.66 |
November | 0.962158E+10 | 0.874602E+10 | 3712.03 | 01-NOV-00:10 | 3374.24 | 3374.24 | 19.87 | 15.66 |
December | 0.994230E+10 | 0.903755E+10 | 3712.03 | 01-DEC-00:10 | 3374.24 | 3374.24 | 20.20 | 15.66 |
Annual Sum or Average | 0.117063E+12 | 0.106410E+12 | ||||||
Minimum of Months | 0.898014E+10 | 0.816295E+10 | 3712.03 | 3374.24 | 3374.24 | 18.60 | 15.66 | |
Maximum of Months | 0.994230E+10 | 0.903755E+10 | 3712.03 | 3374.24 | 3374.24 | 20.39 | 15.66 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.90 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.93 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.93 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.03 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.22 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.19 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.20 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.17 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.24 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.96 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.19 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.11 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.90 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.24 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.331418E+10 | 0.301259E+10 | 11400.17 | 20-JAN-14:00 | 10362.75 | 10362.75 | 21.90 | 46.65 |
February | 0.472125E+10 | 0.429162E+10 | 11403.04 | 09-FEB-15:20 | 10365.37 | 10365.37 | 22.25 | 46.65 |
March | 0.478112E+10 | 0.434604E+10 | 11403.46 | 23-MAR-16:00 | 10365.74 | 10365.74 | 22.31 | 46.65 |
April | 0.483331E+10 | 0.439348E+10 | 11434.22 | 28-APR-15:20 | 10393.71 | 10393.71 | 25.90 | 46.65 |
May | 0.520485E+10 | 0.473121E+10 | 22866.31 | 22-MAY-14:05 | 20785.48 | 20785.48 | 25.79 | 93.30 |
June | 0.992795E+10 | 0.902451E+10 | 22883.38 | 13-JUN-16:00 | 20800.99 | 20800.99 | 26.68 | 93.30 |
July | 0.160940E+11 | 0.146294E+11 | 22865.28 | 22-JUL-15:10 | 20784.54 | 20784.54 | 25.73 | 93.30 |
August | 0.173881E+11 | 0.158058E+11 | 22869.35 | 28-AUG-14:05 | 20788.24 | 20788.24 | 25.94 | 93.30 |
September | 0.115872E+11 | 0.105328E+11 | 22865.67 | 27-SEP-14:40 | 20784.90 | 20784.90 | 25.75 | 93.30 |
October | 0.518335E+10 | 0.471167E+10 | 11422.06 | 05-OCT-14:10 | 10382.65 | 10382.65 | 24.57 | 46.65 |
November | 0.380305E+10 | 0.345697E+10 | 11404.56 | 03-NOV-14:40 | 10366.75 | 10366.75 | 22.44 | 46.65 |
December | 0.642424E+10 | 0.583963E+10 | 11394.78 | 19-DEC-16:30 | 10357.86 | 10357.86 | 21.25 | 46.65 |
Annual Sum or Average | 0.932626E+11 | 0.847757E+11 | ||||||
Minimum of Months | 0.331418E+10 | 0.301259E+10 | 11394.78 | 10357.86 | 10357.86 | 21.25 | 46.65 | |
Maximum of Months | 0.173881E+11 | 0.158058E+11 | 22883.38 | 20800.99 | 20800.99 | 26.68 | 93.30 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 37.05 | 82.00 | 86747.84 | 906223.60 | 11-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 27.55 | 27.55 | 66701.52 | 922148.36 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.42 | 33.42 | 48867.55 | 800484.55 | 06-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31.03 | 31.03 | 10518.01 | 507057.22 | 12-APR-13:05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 25.70 | 25.70 | 5877.31 | 457017.53 | 01-MAY-09:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 27.48 | 27.48 | 561.09 | 227672.22 | 28-JUN-09:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.17 | 29.17 | 80.53 | 45375.10 | 25-JUL-09:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 25.00 | 18.44 | 37717.61 | 24-AUG-06:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.46 | 24.46 | 1215.92 | 268434.64 | 08-SEP-09:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.99 | 25.99 | 13505.40 | 411402.64 | 23-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.78 | 28.78 | 45759.98 | 1054078.47 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32.47 | 32.47 | 91786.85 | 1002835.51 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 30856.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.46 | 24.46 | 18.44 | 37717.61 | ||
Maximum of Months | 0.00 | 0.00 | 37.05 | 82.00 | 91786.85 | 1054078.47 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1907.68 | 135647.09 | 20-JAN-12:00 | 7.96 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 4174.89 | 193167.78 | 09-FEB-15:20 | 8.49 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4183.47 | 200597.49 | 23-MAR-16:00 | 8.56 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25849.04 | 817822.81 | 28-APR-15:20 | 14.29 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27572.59 | 1485327.83 | 22-MAY-14:05 | 13.59 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 79731.81 | 1402862.42 | 13-JUN-16:00 | 13.20 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121466.21 | 1330672.69 | 21-JUL-15:30 | 12.87 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 150940.70 | 1603019.21 | 28-AUG-14:05 | 14.13 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 88692.30 | 1197483.86 | 22-SEP-14:05 | 12.25 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21648.49 | 593627.88 | 05-OCT-14:05 | 12.20 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3930.09 | 224298.73 | 03-NOV-14:10 | 8.78 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2906.49 | 59757.41 | 21-DEC-14:00 | 7.25 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 44691.48 | 0.00 | ||||||
Minimum of Months | 1907.68 | 59757.41 | 7.25 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 150940.70 | 1603019.21 | 14.29 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1623.46 | 135889.29 | 20-JAN-12:00 | 16.60 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3726.86 | 192335.74 | 09-FEB-15:20 | 15.77 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 3778.95 | 198117.22 | 23-MAR-16:00 | 17.84 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25731.40 | 1075509.57 | 30-APR-14:31 | 20.53 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27462.41 | 1622275.22 | 22-MAY-14:00 | 17.53 | 10.18 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 80070.00 | 1780016.08 | 21-JUN-13:05 | 14.96 | 11.42 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121000.30 | 1670500.21 | 21-JUL-10:30 | 17.47 | 11.77 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 150598.47 | 1890023.10 | 28-AUG-14:00 | 17.22 | 12.49 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 88381.94 | 1329288.19 | 12-SEP-12:50 | 15.12 | 9.36 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21220.19 | 602717.53 | 05-OCT-14:05 | 18.84 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3593.20 | 226965.23 | 03-NOV-14:10 | 17.63 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2354.90 | 58208.69 | 21-DEC-14:00 | 12.84 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 44402.32 | 0.00 | ||||||
Minimum of Months | 1623.46 | 58208.69 | 12.84 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 150598.47 | 1890023.10 | 20.53 | 12.49 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19295.06 | 35417.73 | 27-JAN-20:30 | 18.98 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49636.37 | 90615.02 | 04-FEB-16:20 | 20.00 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80360.38 | 126143.97 | 09-MAR-07:15 | 20.65 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 140515.32 | 1066701.30 | 30-APR-18:10 | 37.65 | 27.58 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34051.04 | 441082.79 | 22-MAY-15:00 | 26.40 | 24.62 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 89088.18 | 975584.74 | 13-JUN-17:00 | 36.02 | 29.36 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 174275.65 | 1355014.38 | 22-JUL-18:00 | 42.75 | 33.37 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 314504.24 | 1397459.02 | 14-AUG-17:20 | 43.49 | 31.36 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 45124.18 | 337955.57 | 13-SEP-16:00 | 24.53 | 23.39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 53021.66 | 117599.73 | 07-OCT-15:00 | 20.49 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77176.24 | 92264.76 | 03-NOV-16:00 | 20.03 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102069.07 | 148658.68 | 01-DEC-20:00 | 21.06 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 98772.13 | 0.00 | ||||||
Minimum of Months | 19295.06 | 35417.73 | 18.98 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 314504.24 | 1397459.02 | 43.49 | 33.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.09 | 58.09 | 14672.84 | 52248.30 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.56 | 57.56 | 14859.05 | 52330.96 | 14-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.56 | 57.56 | 15688.43 | 52245.88 | 01-MAR-12:35 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.59 | 57.59 | 14420.48 | 51469.97 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.13 | 58.13 | 14512.95 | 50340.24 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.72 | 57.72 | 14472.79 | 48910.00 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.78 | 57.78 | 13036.65 | 47643.80 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.81 | 57.81 | 14169.96 | 46995.40 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.81 | 57.81 | 13376.28 | 47647.94 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.78 | 57.78 | 13634.03 | 48915.83 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.72 | 57.72 | 14208.61 | 50301.09 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.65 | 57.65 | 14049.77 | 51474.56 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 14255.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.56 | 57.56 | 13036.65 | 46995.40 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 15688.43 | 52330.96 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 605.61 | 156815.80 | 20-JAN-14:00 | 21.90 | 21.10 | 2515.52 | 105299.42 | 10-JAN-06:40 |
February | 1425.59 | 225135.68 | 09-FEB-15:20 | 22.25 | 21.10 | 3839.35 | 105250.99 | 13-FEB-06:40 |
March | 1874.48 | 235034.67 | 23-MAR-16:00 | 22.31 | 21.10 | 3616.58 | 101624.08 | 25-MAR-06:00 |
April | 27770.68 | 935821.69 | 28-APR-15:20 | 25.90 | 21.10 | 1183.47 | 91067.69 | 08-APR-09:30 |
May | 30842.98 | 1826918.21 | 22-MAY-14:05 | 25.79 | 21.36 | 1143.48 | 76131.93 | 06-MAY-09:20 |
June | 96771.31 | 2174086.70 | 13-JUN-16:00 | 26.68 | 22.52 | 844.51 | 67379.96 | 08-JUN-06:50 |
July | 144341.41 | 1805926.78 | 22-JUL-15:10 | 25.73 | 21.75 | 1379.06 | 77228.04 | 31-JUL-05:40 |
August | 176700.84 | 1888667.96 | 28-AUG-14:05 | 25.94 | 21.27 | 719.86 | 70442.34 | 30-AUG-05:40 |
September | 102605.48 | 1813882.51 | 27-SEP-14:40 | 25.75 | 21.10 | 1114.17 | 84426.09 | 21-SEP-05:40 |
October | 23121.47 | 676789.51 | 05-OCT-14:10 | 24.57 | 21.10 | 1317.13 | 90824.28 | 23-OCT-05:30 |
November | 2557.43 | 261325.20 | 03-NOV-14:40 | 22.44 | 21.10 | 2715.89 | 91193.59 | 16-NOV-06:30 |
December | 247.44 | 28606.51 | 19-DEC-16:30 | 21.25 | 20.55 | 5580.25 | 112080.17 | 29-DEC-06:30 |
Annual Sum or Average | 51070.75 | 2158.00 | ||||||
Minimum of Months | 247.44 | 28606.51 | 21.25 | 20.55 | 719.86 | 67379.96 | ||
Maximum of Months | 176700.84 | 2174086.70 | 26.68 | 22.52 | 5580.25 | 112080.17 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.110246E+11 | 0.00 | 0.301884E+10 | 0.359144E+10 | 0.00 | 0.00 |
February | 0.727256E+10 | 0.00 | 0.458587E+10 | 0.386636E+10 | 0.00 | 0.00 |
March | 0.486356E+10 | 0.00 | 0.313213E+10 | 0.508478E+10 | 0.00 | 0.00 |
April | 0.765069E+09 | 0.00 | 0.514489E+10 | 0.973861E+10 | 0.00 | 0.00 |
May | 0.619634E+09 | 0.00 | 0.573107E+10 | 0.761519E+10 | 0.00 | 0.00 |
June | 13386003.61 | 0.00 | 0.181865E+11 | 0.981419E+10 | 0.00 | 0.00 |
July | 15287.43 | 0.00 | 0.305751E+11 | 0.115241E+11 | 0.00 | 0.00 |
August | 14364.12 | 0.00 | 0.406616E+11 | 0.135325E+11 | 0.00 | 0.00 |
September | 0.119274E+09 | 0.00 | 0.191812E+11 | 0.838320E+10 | 0.00 | 0.00 |
October | 0.134859E+10 | 0.00 | 0.333181E+10 | 0.596319E+10 | 0.00 | 0.00 |
November | 0.393860E+10 | 0.00 | 0.403626E+10 | 0.463922E+10 | 0.00 | 0.00 |
December | 0.801565E+10 | 0.00 | 0.627096E+10 | 0.422002E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.379810E+11 | 0.00 | 0.143856E+12 | 0.879728E+11 | 0.00 | 0.00 |
Minimum of Months | 14364.12 | 0.00 | 0.301884E+10 | 0.359144E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110246E+11 | 0.00 | 0.406616E+11 | 0.135325E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.186244E+12 | 0.00 | 0.137888E+10 | 0.232736E+11 | 0.00 | 0.00 |
February | 0.129532E+12 | 0.00 | 0.445992E+10 | 0.235508E+11 | 0.00 | 0.00 |
March | 0.106927E+12 | 0.00 | 0.703128E+10 | 0.267357E+11 | 0.00 | 0.00 |
April | 0.224281E+11 | 0.00 | 0.562983E+11 | 0.530504E+11 | 0.00 | 0.00 |
May | 0.127202E+11 | 0.00 | 0.575190E+11 | 0.559276E+11 | 0.00 | 0.00 |
June | 0.127091E+10 | 0.00 | 0.154289E+12 | 0.683242E+11 | 0.00 | 0.00 |
July | 0.215041E+09 | 0.00 | 0.241156E+12 | 0.737046E+11 | 0.00 | 0.00 |
August | 36540472.00 | 0.00 | 0.302673E+12 | 0.817137E+11 | 0.00 | 0.00 |
September | 0.249309E+10 | 0.00 | 0.176155E+12 | 0.636483E+11 | 0.00 | 0.00 |
October | 0.275194E+11 | 0.00 | 0.522617E+11 | 0.359118E+11 | 0.00 | 0.00 |
November | 0.948433E+11 | 0.00 | 0.522023E+10 | 0.240521E+11 | 0.00 | 0.00 |
December | 0.200745E+12 | 0.00 | 53733706.85 | 0.211731E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.784974E+12 | 0.00 | 0.105850E+13 | 0.551066E+12 | 0.00 | 0.00 |
Minimum of Months | 36540472.00 | 0.00 | 53733706.85 | 0.211731E+11 | 0.00 | 0.00 |
Maximum of Months | 0.200745E+12 | 0.00 | 0.302673E+12 | 0.817137E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.347522E+11 | 0.00 | 0.00 | 0.233872E+10 | 0.00 | 0.00 |
February | 0.244517E+11 | 0.00 | 1361862.38 | 0.209157E+10 | 0.00 | 0.00 |
March | 0.195368E+11 | 0.00 | 20163622.10 | 0.231121E+10 | 0.00 | 0.00 |
April | 0.422622E+10 | 0.00 | 0.348641E+10 | 0.395560E+10 | 0.00 | 0.00 |
May | 0.247451E+10 | 0.00 | 0.490901E+10 | 0.450344E+10 | 0.00 | 0.00 |
June | 0.171684E+09 | 0.00 | 0.155576E+11 | 0.594770E+10 | 0.00 | 0.00 |
July | 16621116.86 | 0.00 | 0.245423E+11 | 0.658448E+10 | 0.00 | 0.00 |
August | 15001436.96 | 0.00 | 0.292574E+11 | 0.691254E+10 | 0.00 | 0.00 |
September | 0.550338E+09 | 0.00 | 0.150758E+11 | 0.487210E+10 | 0.00 | 0.00 |
October | 0.748261E+10 | 0.00 | 0.588129E+09 | 0.259581E+10 | 0.00 | 0.00 |
November | 0.203832E+11 | 0.00 | 3341121.87 | 0.211601E+10 | 0.00 | 0.00 |
December | 0.378045E+11 | 0.00 | 0.00 | 0.231647E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.151865E+12 | 0.00 | 0.934415E+11 | 0.465456E+11 | 0.00 | 0.00 |
Minimum of Months | 15001436.96 | 0.00 | 0.00 | 0.209157E+10 | 0.00 | 0.00 |
Maximum of Months | 0.378045E+11 | 0.00 | 0.292574E+11 | 0.691254E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.156357E+10 | 0.00 | 23413772.47 | 0.521914E+10 | 0.00 | 0.00 |
February | 0.920901E+09 | 0.00 | 0.00 | 0.512820E+10 | 0.00 | 0.00 |
March | 0.243973E+09 | 0.00 | 31699921.68 | 0.842061E+10 | 0.00 | 0.00 |
April | 3843320.05 | 0.00 | 0.115717E+10 | 0.122156E+11 | 0.00 | 0.00 |
May | 3480716.81 | 0.00 | 0.438576E+10 | 0.113254E+11 | 0.00 | 0.00 |
June | 1934.50 | 0.00 | 0.118439E+11 | 0.126099E+11 | 0.00 | 0.00 |
July | 1316.20 | 0.00 | 0.214951E+11 | 0.103410E+11 | 0.00 | 0.00 |
August | 544.04 | 0.00 | 0.260899E+11 | 0.119679E+11 | 0.00 | 0.00 |
September | 131.93 | 0.00 | 0.124932E+11 | 0.120304E+11 | 0.00 | 0.00 |
October | 539217.14 | 0.00 | 0.767957E+09 | 0.124250E+11 | 0.00 | 0.00 |
November | 46797136.98 | 0.00 | 60100441.57 | 0.111803E+11 | 0.00 | 0.00 |
December | 0.523169E+09 | 0.00 | 0.00 | 0.821276E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.330627E+10 | 0.00 | 0.783483E+11 | 0.121076E+12 | 0.00 | 0.00 |
Minimum of Months | 131.93 | 0.00 | 0.00 | 0.512820E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156357E+10 | 0.00 | 0.260899E+11 | 0.126099E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.735343E+10 | 0.191542E+12 | 0.00 | 29.37 |
February | 0.00 | 0.00 | 0.997420E+10 | 0.221561E+12 | 0.00 | 44.32 |
March | 0.00 | 0.00 | 0.162915E+11 | 0.312753E+12 | 0.00 | 73.73 |
April | 0.00 | 0.00 | 0.598455E+11 | 0.337738E+12 | 0.00 | 80.87 |
May | 0.00 | 0.00 | 0.544423E+10 | 0.153576E+12 | 0.00 | 15.36 |
June | 0.00 | 0.00 | 0.264185E+11 | 0.127039E+12 | 0.00 | 5.01 |
July | 0.00 | 0.00 | 0.113346E+12 | 0.145928E+12 | 0.00 | 3.86 |
August | 0.00 | 0.00 | 0.361703E+12 | 0.197465E+12 | 0.00 | 5.20 |
September | 0.00 | 0.00 | 0.377776E+10 | 0.123648E+12 | 0.00 | 5.68 |
October | 0.00 | 0.00 | 0.654634E+10 | 0.172682E+12 | 0.00 | 22.38 |
November | 0.00 | 0.00 | 0.119330E+11 | 0.244373E+12 | 0.00 | 49.96 |
December | 0.00 | 0.00 | 0.205971E+11 | 0.355807E+12 | 0.00 | 89.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.643231E+12 | 0.258411E+13 | 0.00 | 425.10 |
Minimum of Months | 0.00 | 0.00 | 0.377776E+10 | 0.123648E+12 | 0.00 | 3.86 |
Maximum of Months | 0.00 | 0.00 | 0.361703E+12 | 0.355807E+12 | 0.00 | 89.36 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.538116E+10 | 0.254171E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107502E+11 | 0.331736E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182588E+11 | 0.470096E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241006E+11 | 0.555067E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.669168E+10 | 0.275522E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127988E+11 | 0.372491E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.195149E+11 | 0.488464E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254668E+11 | 0.583143E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.667890E+10 | 0.269411E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125029E+11 | 0.373289E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.176856E+11 | 0.452304E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.240128E+11 | 0.560738E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183843E+12 | 0.498643E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.538116E+10 | 0.254171E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.254668E+11 | 0.583143E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.291801E+11 | 0.203281E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.848810E+11 | 0.287529E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157733E+12 | 0.423526E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223066E+12 | 0.520568E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.571231E+11 | 0.252204E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.117763E+12 | 0.349450E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.182339E+12 | 0.461352E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239704E+12 | 0.552891E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.572820E+11 | 0.246961E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105834E+12 | 0.335076E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149262E+12 | 0.401924E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.201614E+12 | 0.494234E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160578E+13 | 0.452900E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.291801E+11 | 0.203281E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.239704E+12 | 0.552891E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.826285E+09 | 0.164478E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.626597E+10 | 0.250563E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.137965E+11 | 0.393596E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213980E+11 | 0.509176E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.490280E+10 | 0.239898E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.114169E+11 | 0.345737E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.179417E+11 | 0.459286E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.236750E+11 | 0.551173E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.497503E+10 | 0.235803E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.877877E+10 | 0.306769E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.126757E+11 | 0.367586E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.176339E+11 | 0.456801E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144287E+12 | 0.428087E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.826285E+09 | 0.164478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.236750E+11 | 0.551173E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.359144E+10 | 0.301884E+10 | 0.110246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386636E+10 | 0.458587E+10 | 0.727256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.508478E+10 | 0.313213E+10 | 0.486356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.973861E+10 | 0.514489E+10 | 0.765069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.761519E+10 | 0.573107E+10 | 0.619634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981419E+10 | 0.181865E+11 | 13386003.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115241E+11 | 0.305751E+11 | 15287.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135325E+11 | 0.406616E+11 | 14364.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.838320E+10 | 0.191812E+11 | 0.119274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.596319E+10 | 0.333181E+10 | 0.134859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.463922E+10 | 0.403626E+10 | 0.393860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422002E+10 | 0.627096E+10 | 0.801565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879728E+11 | 0.143856E+12 | 0.379810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359144E+10 | 0.301884E+10 | 14364.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135325E+11 | 0.406616E+11 | 0.110246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.232736E+11 | 0.137888E+10 | 0.186244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235508E+11 | 0.445992E+10 | 0.129532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267357E+11 | 0.703128E+10 | 0.106927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.530504E+11 | 0.562983E+11 | 0.224281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.559276E+11 | 0.575190E+11 | 0.127202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683242E+11 | 0.154289E+12 | 0.127091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737046E+11 | 0.241156E+12 | 0.215041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.817137E+11 | 0.302673E+12 | 36540472.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.636483E+11 | 0.176155E+12 | 0.249309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359118E+11 | 0.522617E+11 | 0.275194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240521E+11 | 0.522023E+10 | 0.948433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211731E+11 | 53733706.85 | 0.200745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551066E+12 | 0.105850E+13 | 0.784974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.211731E+11 | 53733706.85 | 36540472.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.817137E+11 | 0.302673E+12 | 0.200745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.233872E+10 | 0.00 | 0.347522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209157E+10 | 1361862.38 | 0.244517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231121E+10 | 20163622.10 | 0.195368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395560E+10 | 0.348641E+10 | 0.422622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450344E+10 | 0.490901E+10 | 0.247451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.594770E+10 | 0.155576E+11 | 0.171684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658448E+10 | 0.245423E+11 | 16621116.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.691254E+10 | 0.292574E+11 | 15001436.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.487210E+10 | 0.150758E+11 | 0.550338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259581E+10 | 0.588129E+09 | 0.748261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211601E+10 | 3341121.87 | 0.203832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231647E+10 | 0.00 | 0.378045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465456E+11 | 0.934415E+11 | 0.151865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.209157E+10 | 0.00 | 15001436.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.691254E+10 | 0.292574E+11 | 0.378045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.521914E+10 | 23413772.47 | 0.156357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.512820E+10 | 0.00 | 0.920901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842061E+10 | 31699921.68 | 0.243973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122156E+11 | 0.115717E+10 | 3843320.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113254E+11 | 0.438576E+10 | 3480716.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126099E+11 | 0.118439E+11 | 1934.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103410E+11 | 0.214951E+11 | 1316.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119679E+11 | 0.260899E+11 | 544.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120304E+11 | 0.124932E+11 | 131.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124250E+11 | 0.767957E+09 | 539217.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111803E+11 | 60100441.57 | 46797136.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.821276E+10 | 0.00 | 0.523169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121076E+12 | 0.783483E+11 | 0.330627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.512820E+10 | 0.00 | 131.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126099E+11 | 0.260899E+11 | 0.156357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109078E+12 | 0.382837E+10 | 0.00 | 0.00 | 0.00 | 0.785849E+11 | 0.00 | 0.00 |
February | 0.985223E+11 | 0.608728E+10 | 0.00 | 0.00 | 0.00 | 0.118618E+12 | 0.00 | 0.00 |
March | 0.109078E+12 | 0.108178E+11 | 0.00 | 0.00 | 0.00 | 0.197312E+12 | 0.00 | 0.00 |
April | 0.105560E+12 | 0.450483E+11 | 0.00 | 0.00 | 0.00 | 0.216407E+12 | 0.00 | 0.00 |
May | 0.109078E+12 | 0.223065E+10 | 0.00 | 0.00 | 0.00 | 0.410994E+11 | 0.00 | 0.00 |
June | 0.105560E+12 | 0.183959E+11 | 0.00 | 0.00 | 0.00 | 0.133968E+11 | 0.00 | 0.00 |
July | 0.109078E+12 | 0.868795E+11 | 0.00 | 0.00 | 0.00 | 0.103366E+11 | 0.00 | 0.00 |
August | 0.109078E+12 | 0.287308E+12 | 0.00 | 0.00 | 0.00 | 0.139282E+11 | 0.00 | 0.00 |
September | 0.105560E+12 | 0.949780E+09 | 0.00 | 0.00 | 0.00 | 0.151923E+11 | 0.00 | 0.00 |
October | 0.109078E+12 | 0.311349E+10 | 0.00 | 0.00 | 0.00 | 0.599016E+11 | 0.00 | 0.00 |
November | 0.105560E+12 | 0.742704E+10 | 0.00 | 0.00 | 0.00 | 0.133705E+12 | 0.00 | 0.00 |
December | 0.109078E+12 | 0.140711E+11 | 0.00 | 0.00 | 0.00 | 0.239126E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.128431E+13 | 0.486157E+12 | 0.00 | 0.00 | 0.00 | 0.113761E+13 | 0.00 | 0.00 |
Minimum of Months | 0.985223E+11 | 0.949780E+09 | 0.00 | 0.00 | 0.00 | 0.103366E+11 | 0.00 | 0.00 |
Maximum of Months | 0.109078E+12 | 0.287308E+12 | 0.00 | 0.00 | 0.00 | 0.239126E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150983E+10 | 0.434928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136372E+10 | 0.879653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150983E+10 | 0.150676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146112E+10 | 0.200110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150983E+10 | 0.544628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146112E+10 | 0.105350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150983E+10 | 0.161401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150983E+10 | 0.211452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146112E+10 | 0.544591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150983E+10 | 0.102798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146112E+10 | 0.146237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150983E+10 | 0.199153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177770E+11 | 0.151756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136372E+10 | 0.434928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150983E+10 | 0.211452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145065E+11 | 0.233584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131026E+11 | 0.692307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145065E+11 | 0.129887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140385E+11 | 0.185048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145065E+11 | 0.464091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140385E+11 | 0.968565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145065E+11 | 0.150710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145065E+11 | 0.198921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140385E+11 | 0.466244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145065E+11 | 0.868329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140385E+11 | 0.123108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145065E+11 | 0.166697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170802E+12 | 0.132368E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131026E+11 | 0.233584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145065E+11 | 0.198921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147045E+10 | 0.651954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132815E+10 | 0.508850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147045E+10 | 0.113310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142302E+10 | 0.177292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147045E+10 | 0.397427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142302E+10 | 0.938254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147045E+10 | 0.148193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147045E+10 | 0.196337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142302E+10 | 0.404001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147045E+10 | 0.718153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142302E+10 | 0.104228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147045E+10 | 0.145364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173134E+11 | 0.118791E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132815E+10 | 0.651954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147045E+10 | 0.196337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.359144E+10 | 0.110246E+11 | 0.301884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386636E+10 | 0.727256E+10 | 0.458587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.508478E+10 | 0.486356E+10 | 0.313213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.973861E+10 | 0.765069E+09 | 0.514489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.761519E+10 | 0.619634E+09 | 0.573107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981419E+10 | 13386003.61 | 0.181865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115241E+11 | 15287.43 | 0.305751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135325E+11 | 14364.12 | 0.406616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.838320E+10 | 0.119274E+09 | 0.191812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.596319E+10 | 0.134859E+10 | 0.333181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.463922E+10 | 0.393860E+10 | 0.403626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422002E+10 | 0.801565E+10 | 0.627096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879728E+11 | 0.379810E+11 | 0.143856E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359144E+10 | 14364.12 | 0.301884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135325E+11 | 0.110246E+11 | 0.406616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.232736E+11 | 0.186244E+12 | 0.137888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235508E+11 | 0.129532E+12 | 0.445992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267357E+11 | 0.106927E+12 | 0.703128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.530504E+11 | 0.224281E+11 | 0.562983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.559276E+11 | 0.127202E+11 | 0.575190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683242E+11 | 0.127091E+10 | 0.154289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737046E+11 | 0.215041E+09 | 0.241156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.817137E+11 | 36540472.00 | 0.302673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.636483E+11 | 0.249309E+10 | 0.176155E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359118E+11 | 0.275194E+11 | 0.522617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240521E+11 | 0.948433E+11 | 0.522023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211731E+11 | 0.200745E+12 | 53733706.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551066E+12 | 0.784974E+12 | 0.105850E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.211731E+11 | 36540472.00 | 53733706.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.817137E+11 | 0.200745E+12 | 0.302673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.233872E+10 | 0.347522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209157E+10 | 0.244517E+11 | 1361862.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231121E+10 | 0.195368E+11 | 20163622.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395560E+10 | 0.422622E+10 | 0.348641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450344E+10 | 0.247451E+10 | 0.490901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.594770E+10 | 0.171684E+09 | 0.155576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658448E+10 | 16621116.86 | 0.245423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.691254E+10 | 15001436.96 | 0.292574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.487210E+10 | 0.550338E+09 | 0.150758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259581E+10 | 0.748261E+10 | 0.588129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211601E+10 | 0.203832E+11 | 3341121.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231647E+10 | 0.378045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465456E+11 | 0.151865E+12 | 0.934415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.209157E+10 | 15001436.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.691254E+10 | 0.378045E+11 | 0.292574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.521914E+10 | 0.156357E+10 | 23413772.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.512820E+10 | 0.920901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.842061E+10 | 0.243973E+09 | 31699921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122156E+11 | 3843320.05 | 0.115717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113254E+11 | 3480716.81 | 0.438576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126099E+11 | 1934.50 | 0.118439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103410E+11 | 1316.20 | 0.214951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119679E+11 | 544.04 | 0.260899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120304E+11 | 131.93 | 0.124932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124250E+11 | 539217.14 | 0.767957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111803E+11 | 46797136.98 | 60100441.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.821276E+10 | 0.523169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121076E+12 | 0.330627E+10 | 0.783483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.512820E+10 | 131.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126099E+11 | 0.156357E+10 | 0.260899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109078E+12 | 0.00 | 0.735343E+10 | 0.00 | 0.352506E+10 | 0.00 | 0.00 | 0.00 | 0.789386E+11 | 0.00 | 0.00 | 0.00 |
February | 0.985223E+11 | 0.00 | 0.997420E+10 | 0.00 | 0.388692E+10 | 0.00 | 0.00 | 0.00 | 0.119152E+12 | 0.00 | 0.00 | 0.00 |
March | 0.109078E+12 | 0.00 | 0.162915E+11 | 0.00 | 0.547367E+10 | 0.00 | 0.00 | 0.00 | 0.198201E+12 | 0.00 | 0.00 | 0.00 |
April | 0.105560E+12 | 0.00 | 0.598455E+11 | 0.00 | 0.147972E+11 | 0.00 | 0.00 | 0.00 | 0.217381E+12 | 0.00 | 0.00 | 0.00 |
May | 0.109078E+12 | 0.00 | 0.544423E+10 | 0.00 | 0.321359E+10 | 0.00 | 0.00 | 0.00 | 0.412844E+11 | 0.00 | 0.00 | 0.00 |
June | 0.105560E+12 | 0.00 | 0.264185E+11 | 0.00 | 0.802267E+10 | 0.00 | 0.00 | 0.00 | 0.134571E+11 | 0.00 | 0.00 | 0.00 |
July | 0.109078E+12 | 0.00 | 0.113346E+12 | 0.00 | 0.264667E+11 | 0.00 | 0.00 | 0.00 | 0.103831E+11 | 0.00 | 0.00 | 0.00 |
August | 0.109078E+12 | 0.00 | 0.361703E+12 | 0.00 | 0.743954E+11 | 0.00 | 0.00 | 0.00 | 0.139909E+11 | 0.00 | 0.00 | 0.00 |
September | 0.105560E+12 | 0.00 | 0.377776E+10 | 0.00 | 0.282798E+10 | 0.00 | 0.00 | 0.00 | 0.152606E+11 | 0.00 | 0.00 | 0.00 |
October | 0.109078E+12 | 0.00 | 0.654634E+10 | 0.00 | 0.343285E+10 | 0.00 | 0.00 | 0.00 | 0.601713E+11 | 0.00 | 0.00 | 0.00 |
November | 0.105560E+12 | 0.00 | 0.119330E+11 | 0.00 | 0.450597E+10 | 0.00 | 0.00 | 0.00 | 0.134307E+12 | 0.00 | 0.00 | 0.00 |
December | 0.109078E+12 | 0.00 | 0.205971E+11 | 0.00 | 0.652604E+10 | 0.00 | 0.00 | 0.00 | 0.240203E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128431E+13 | 0.00 | 0.643231E+12 | 0.00 | 0.157074E+12 | 0.00 | 0.00 | 0.00 | 0.114273E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985223E+11 | 0.00 | 0.377776E+10 | 0.00 | 0.282798E+10 | 0.00 | 0.00 | 0.00 | 0.103831E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109078E+12 | 0.00 | 0.361703E+12 | 0.00 | 0.743954E+11 | 0.00 | 0.00 | 0.00 | 0.240203E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150983E+10 | 0.00 | 0.538116E+10 | 0.00 | 0.103188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136372E+10 | 0.00 | 0.107502E+11 | 0.00 | 0.195364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150983E+10 | 0.00 | 0.182588E+11 | 0.00 | 0.319113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146112E+10 | 0.00 | 0.241006E+11 | 0.00 | 0.408955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150983E+10 | 0.00 | 0.669168E+10 | 0.00 | 0.124539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146112E+10 | 0.00 | 0.127988E+11 | 0.00 | 0.226379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150983E+10 | 0.00 | 0.195149E+11 | 0.00 | 0.337482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150983E+10 | 0.00 | 0.254668E+11 | 0.00 | 0.432160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146112E+10 | 0.00 | 0.667890E+10 | 0.00 | 0.123299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150983E+10 | 0.00 | 0.125029E+11 | 0.00 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146112E+10 | 0.00 | 0.176856E+11 | 0.00 | 0.306191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150983E+10 | 0.00 | 0.240128E+11 | 0.00 | 0.409755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177770E+11 | 0.00 | 0.183843E+12 | 0.00 | 0.320873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136372E+10 | 0.00 | 0.538116E+10 | 0.00 | 0.103188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150983E+10 | 0.00 | 0.254668E+11 | 0.00 | 0.432160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145065E+11 | 0.00 | 0.291801E+11 | 0.00 | 0.582164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131026E+11 | 0.00 | 0.848810E+11 | 0.00 | 0.156503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145065E+11 | 0.00 | 0.157733E+12 | 0.00 | 0.278461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140385E+11 | 0.00 | 0.223066E+12 | 0.00 | 0.380183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145065E+11 | 0.00 | 0.571231E+11 | 0.00 | 0.107140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140385E+11 | 0.00 | 0.117763E+12 | 0.00 | 0.209065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145065E+11 | 0.00 | 0.182339E+12 | 0.00 | 0.316287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145065E+11 | 0.00 | 0.239704E+12 | 0.00 | 0.407826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140385E+11 | 0.00 | 0.572820E+11 | 0.00 | 0.106576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145065E+11 | 0.00 | 0.105834E+12 | 0.00 | 0.190011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140385E+11 | 0.00 | 0.149262E+12 | 0.00 | 0.261539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145065E+11 | 0.00 | 0.201614E+12 | 0.00 | 0.349170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170802E+12 | 0.00 | 0.160578E+13 | 0.00 | 0.282098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131026E+11 | 0.00 | 0.291801E+11 | 0.00 | 0.582164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145065E+11 | 0.00 | 0.239704E+12 | 0.00 | 0.407826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147045E+10 | 0.00 | 0.826285E+09 | 0.00 | 0.174331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132815E+10 | 0.00 | 0.626597E+10 | 0.00 | 0.117747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147045E+10 | 0.00 | 0.137965E+11 | 0.00 | 0.246551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142302E+10 | 0.00 | 0.213980E+11 | 0.00 | 0.366874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147045E+10 | 0.00 | 0.490280E+10 | 0.00 | 0.928530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142302E+10 | 0.00 | 0.114169E+11 | 0.00 | 0.203435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147045E+10 | 0.00 | 0.179417E+11 | 0.00 | 0.312241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147045E+10 | 0.00 | 0.236750E+11 | 0.00 | 0.404128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142302E+10 | 0.00 | 0.497503E+10 | 0.00 | 0.935014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147045E+10 | 0.00 | 0.877877E+10 | 0.00 | 0.159724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142302E+10 | 0.00 | 0.126757E+11 | 0.00 | 0.225284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147045E+10 | 0.00 | 0.176339E+11 | 0.00 | 0.309756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173134E+11 | 0.00 | 0.144287E+12 | 0.00 | 0.254953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132815E+10 | 0.00 | 0.826285E+09 | 0.00 | 0.174331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147045E+10 | 0.00 | 0.236750E+11 | 0.00 | 0.404128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 89932514.94 | 0.00 | 0.00 | 0.577286E+11 | 0.00 | 0.46 |
February | 0.00 | 0.00 | 0.00 | 83488602.06 | 0.00 | 0.00 | 0.518316E+11 | 0.00 | 0.48 |
March | 0.00 | 0.00 | 0.00 | 95799986.79 | 0.00 | 0.00 | 0.644822E+11 | 0.00 | 0.58 |
April | 0.00 | 0.00 | 0.00 | 0.102651E+09 | 0.00 | 0.00 | 0.668897E+11 | 0.00 | 0.84 |
May | 0.00 | 0.00 | 0.00 | 0.105708E+09 | 0.00 | 0.00 | 0.635303E+11 | 0.00 | 0.80 |
June | 0.00 | 1646826.94 | 0.00 | 0.123124E+09 | 0.00 | 0.00 | 0.593070E+11 | 0.00 | 1.05 |
July | 0.00 | 49111594.35 | 0.00 | 0.127328E+09 | 0.00 | 0.00 | 0.479399E+11 | 0.00 | 1.00 |
August | 0.00 | 0.00 | 0.00 | 0.141660E+09 | 0.00 | 0.00 | 0.510753E+11 | 0.00 | 1.20 |
September | 0.00 | 0.00 | 0.00 | 0.112784E+09 | 0.00 | 0.00 | 0.559581E+11 | 0.00 | 1.07 |
October | 0.00 | 0.00 | 0.00 | 0.112406E+09 | 0.00 | 0.00 | 0.684861E+11 | 0.00 | 0.82 |
November | 0.00 | 0.00 | 0.00 | 99354264.58 | 0.00 | 0.00 | 0.657927E+11 | 0.00 | 0.65 |
December | 0.00 | 0.00 | 0.00 | 91416216.80 | 0.00 | 0.00 | 0.609531E+11 | 0.00 | 0.50 |
Annual Sum or Average | 0.00 | 50758421.28 | 0.00 | 0.128565E+10 | 0.00 | 0.00 | 0.713975E+12 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 83488602.06 | 0.00 | 0.00 | 0.479399E+11 | 0.00 | 0.46 |
Maximum of Months | 0.00 | 49111594.35 | 0.00 | 0.141660E+09 | 0.00 | 0.00 | 0.684861E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173371E+10 | 0.00 | 0.00 | 70604994.57 | 0.00 | 0.00 | 0.499944E+11 | 0.00 | 0.39 |
February | 0.158107E+10 | 0.00 | 0.00 | 73665197.60 | 0.00 | 0.00 | 0.451727E+11 | 0.00 | 0.41 |
March | 0.132626E+10 | 0.00 | 0.00 | 92641236.56 | 0.00 | 0.00 | 0.583214E+11 | 0.00 | 0.50 |
April | 0.427774E+10 | 0.00 | 0.00 | 0.106513E+09 | 0.00 | 0.00 | 0.612504E+11 | 0.00 | 0.77 |
May | 0.398977E+10 | 0.00 | 0.00 | 93476997.73 | 0.00 | 0.00 | 0.550409E+11 | 0.00 | 0.70 |
June | 0.398950E+10 | 4016963.12 | 0.00 | 0.105394E+09 | 56301366.98 | 0.00 | 0.549955E+11 | 0.00 | 0.94 |
July | 0.745402E+10 | 24748718.99 | 0.00 | 0.107214E+09 | 8435291.63 | 0.00 | 0.498978E+11 | 0.00 | 1.03 |
August | 0.815033E+10 | 0.00 | 0.00 | 0.123521E+09 | 0.00 | 0.00 | 0.520681E+11 | 0.00 | 1.19 |
September | 0.369774E+10 | 0.00 | 0.00 | 95282018.88 | 0.00 | 0.00 | 0.472296E+11 | 0.00 | 0.87 |
October | 0.176650E+10 | 0.00 | 0.00 | 93459165.89 | 0.00 | 0.00 | 0.541979E+11 | 0.00 | 0.62 |
November | 0.159669E+10 | 0.00 | 0.00 | 88219925.37 | 0.00 | 0.00 | 0.525747E+11 | 0.00 | 0.50 |
December | 0.149255E+10 | 0.00 | 0.00 | 86043897.50 | 0.00 | 0.00 | 0.510484E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.410559E+11 | 28765682.11 | 0.00 | 0.113604E+10 | 64736658.60 | 0.00 | 0.631792E+12 | 0.00 | 0.69 |
Minimum of Months | 0.132626E+10 | 0.00 | 0.00 | 70604994.57 | 0.00 | 0.00 | 0.451727E+11 | 0.00 | 0.39 |
Maximum of Months | 0.815033E+10 | 24748718.99 | 0.00 | 0.123521E+09 | 56301366.98 | 0.00 | 0.612504E+11 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194338E+12 | 0.00 | 0.00 | 0.214721E+09 | 0.00 | 0.00 | 0.210920E+12 | 0.00 | 0.32 |
February | 0.154664E+12 | 0.00 | 0.00 | 0.257210E+09 | 0.00 | 0.00 | 0.209283E+12 | 0.00 | 0.32 |
March | 0.135382E+12 | 0.00 | 0.00 | 0.360826E+09 | 0.00 | 0.00 | 0.299500E+12 | 0.00 | 0.37 |
April | 0.348209E+11 | 0.00 | 0.00 | 0.594862E+09 | 0.00 | 0.00 | 0.388317E+12 | 0.00 | 0.50 |
May | 0.449667E+11 | 0.00 | 0.00 | 0.645151E+09 | 0.00 | 0.00 | 0.415434E+12 | 0.00 | 0.55 |
June | 0.301223E+11 | 38943944.11 | 0.00 | 0.755526E+09 | 0.599330E+09 | 0.00 | 0.415678E+12 | 0.00 | 0.72 |
July | 0.417072E+11 | 0.204250E+09 | 0.00 | 0.718845E+09 | 97397627.22 | 0.00 | 0.358911E+12 | 0.00 | 0.74 |
August | 0.366669E+11 | 0.00 | 0.00 | 0.821349E+09 | 0.00 | 0.00 | 0.368227E+12 | 0.00 | 0.83 |
September | 0.366935E+11 | 0.00 | 0.00 | 0.676999E+09 | 0.00 | 0.00 | 0.356460E+12 | 0.00 | 0.69 |
October | 0.737557E+11 | 0.00 | 0.00 | 0.465235E+09 | 0.00 | 0.00 | 0.302150E+12 | 0.00 | 0.41 |
November | 0.135089E+12 | 0.00 | 0.00 | 0.292274E+09 | 0.00 | 0.00 | 0.237327E+12 | 0.00 | 0.34 |
December | 0.207808E+12 | 0.00 | 0.00 | 0.156472E+09 | 0.00 | 0.00 | 0.171222E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.112601E+13 | 0.243194E+09 | 0.00 | 0.595947E+10 | 0.696727E+09 | 0.00 | 0.373343E+13 | 0.00 | 0.51 |
Minimum of Months | 0.301223E+11 | 0.00 | 0.00 | 0.156472E+09 | 0.00 | 0.00 | 0.171222E+12 | 0.00 | 0.30 |
Maximum of Months | 0.207808E+12 | 0.204250E+09 | 0.00 | 0.821349E+09 | 0.599330E+09 | 0.00 | 0.415678E+12 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302174E+11 | 0.00 | 0.00 | 1035533.66 | 0.00 | 0.157585E+10 | 0.160567E+10 | 0.00 | 0.29 |
February | 0.270038E+11 | 0.00 | 0.00 | 1710693.16 | 0.00 | 0.506422E+09 | 0.251789E+10 | 0.00 | 0.29 |
March | 0.279256E+11 | 0.00 | 0.00 | 5321622.19 | 0.00 | 0.319499E+09 | 0.679753E+10 | 0.00 | 0.32 |
April | 0.108261E+11 | 3290969.07 | 0.00 | 32271490.07 | 0.00 | 0.00 | 0.257487E+11 | 0.00 | 0.44 |
May | 0.104530E+11 | 0.00 | 0.00 | 41331280.78 | 0.00 | 0.00 | 0.305574E+11 | 0.00 | 0.50 |
June | 0.659594E+10 | 871836.84 | 0.00 | 57234769.23 | 45433521.28 | 0.00 | 0.357320E+11 | 0.00 | 0.68 |
July | 0.665486E+10 | 10486248.13 | 0.00 | 58488276.71 | 4071683.21 | 0.00 | 0.321133E+11 | 0.00 | 0.72 |
August | 0.568448E+10 | 0.00 | 0.00 | 62657816.76 | 0.00 | 0.00 | 0.321906E+11 | 0.00 | 0.78 |
September | 0.932963E+10 | 0.00 | 0.00 | 41027390.76 | 0.00 | 0.00 | 0.243300E+11 | 0.00 | 0.60 |
October | 0.182239E+11 | 0.00 | 0.00 | 12286987.35 | 0.00 | 72110214.00 | 0.112908E+11 | 0.00 | 0.35 |
November | 0.252868E+11 | 0.00 | 0.00 | 2740600.77 | 0.00 | 0.566089E+09 | 0.348161E+10 | 0.00 | 0.30 |
December | 0.301476E+11 | 0.00 | 0.00 | 97424.34 | 0.00 | 0.136112E+10 | 0.426122E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.208349E+12 | 14649054.04 | 0.00 | 0.316204E+09 | 49505204.49 | 0.440108E+10 | 0.206792E+12 | 0.00 | 0.46 |
Minimum of Months | 0.568448E+10 | 0.00 | 0.00 | 97424.34 | 0.00 | 0.00 | 0.426122E+09 | 0.00 | 0.29 |
Maximum of Months | 0.302174E+11 | 10486248.13 | 0.00 | 62657816.76 | 45433521.28 | 0.157585E+10 | 0.357320E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382666E+10 | 0.00 | 0.00 | 557662.55 | 0.00 | 1116661.90 | 0.510098E+09 | 0.00 | 0.26 |
February | 0.298844E+10 | 0.00 | 0.00 | 1039088.35 | 0.00 | 0.00 | 0.857341E+09 | 0.00 | 0.26 |
March | 0.249376E+10 | 0.00 | 0.00 | 3270339.99 | 0.00 | 0.00 | 0.243979E+10 | 0.00 | 0.33 |
April | 0.144510E+10 | 0.00 | 0.00 | 7717533.11 | 0.00 | 0.00 | 0.531713E+10 | 0.00 | 0.66 |
May | 0.129085E+10 | 0.00 | 0.00 | 8147671.40 | 0.00 | 0.00 | 0.537565E+10 | 0.00 | 0.66 |
June | 0.700178E+09 | 1797181.14 | 0.00 | 12538133.91 | 6657762.04 | 0.00 | 0.707200E+10 | 0.00 | 1.04 |
July | 0.105805E+10 | 5379329.30 | 0.00 | 13233806.67 | 1059181.58 | 0.00 | 0.663057E+10 | 0.00 | 1.15 |
August | 0.119325E+10 | 0.00 | 0.00 | 13551147.40 | 0.00 | 0.00 | 0.622411E+10 | 0.00 | 1.23 |
September | 0.139221E+10 | 0.00 | 0.00 | 7151850.29 | 0.00 | 0.00 | 0.394179E+10 | 0.00 | 0.76 |
October | 0.194013E+10 | 0.00 | 0.00 | 3811797.23 | 0.00 | 0.00 | 0.282294E+10 | 0.00 | 0.43 |
November | 0.258776E+10 | 0.00 | 0.00 | 1842839.03 | 0.00 | 0.00 | 0.145547E+10 | 0.00 | 0.29 |
December | 0.344352E+10 | 0.00 | 0.00 | 395258.10 | 0.00 | 0.00 | 0.502166E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.243599E+11 | 7176510.45 | 0.00 | 73257128.03 | 7716943.61 | 1116661.90 | 0.431491E+11 | 0.00 | 0.61 |
Minimum of Months | 0.700178E+09 | 0.00 | 0.00 | 395258.10 | 0.00 | 0.00 | 0.502166E+09 | 0.00 | 0.24 |
Maximum of Months | 0.382666E+10 | 5379329.30 | 0.00 | 13551147.40 | 6657762.04 | 1116661.90 | 0.707200E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233414E+10 | 0.00 | 0.00 | 945770.32 | 0.00 | 34210096.85 | 0.577185E+09 | 0.00 | 0.27 |
February | 0.186778E+10 | 0.00 | 0.00 | 1627675.04 | 0.00 | 0.00 | 0.869986E+09 | 0.00 | 0.29 |
March | 0.168182E+10 | 0.00 | 0.00 | 2482780.25 | 0.00 | 0.00 | 0.164300E+10 | 0.00 | 0.35 |
April | 0.803287E+09 | 0.00 | 0.00 | 11418420.25 | 0.00 | 0.00 | 0.643553E+10 | 0.00 | 1.10 |
May | 0.649689E+09 | 0.00 | 0.00 | 11581168.56 | 0.00 | 0.00 | 0.666939E+10 | 0.00 | 1.13 |
June | 0.446241E+09 | 1176108.07 | 0.00 | 14319125.87 | 4388782.08 | 0.00 | 0.689182E+10 | 0.00 | 1.54 |
July | 0.598614E+09 | 7691742.37 | 0.00 | 15136665.38 | 685455.56 | 0.00 | 0.646056E+10 | 0.00 | 1.64 |
August | 0.772005E+09 | 0.00 | 0.00 | 15317988.04 | 0.00 | 0.00 | 0.638710E+10 | 0.00 | 1.82 |
September | 0.585670E+09 | 0.00 | 0.00 | 11884467.75 | 0.00 | 0.00 | 0.555670E+10 | 0.00 | 1.37 |
October | 0.122204E+10 | 0.00 | 0.00 | 4621057.36 | 0.00 | 0.00 | 0.270740E+10 | 0.00 | 0.56 |
November | 0.174787E+10 | 0.00 | 0.00 | 1336997.51 | 0.00 | 0.00 | 0.921251E+09 | 0.00 | 0.30 |
December | 0.231999E+10 | 0.00 | 0.00 | 514252.27 | 0.00 | 164314.60 | 0.294238E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.150291E+11 | 8867850.43 | 0.00 | 91186368.60 | 5074237.64 | 34374411.45 | 0.454141E+11 | 0.00 | 0.89 |
Minimum of Months | 0.446241E+09 | 0.00 | 0.00 | 514252.27 | 0.00 | 0.00 | 0.294238E+09 | 0.00 | 0.24 |
Maximum of Months | 0.233414E+10 | 7691742.37 | 0.00 | 15317988.04 | 4388782.08 | 34210096.85 | 0.689182E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311912E+10 | 0.00 | 0.00 | 5338262.41 | 0.00 | 89446809.28 | 0.316971E+10 | 0.00 | 0.39 |
February | 0.254633E+10 | 0.00 | 0.00 | 7780174.42 | 0.00 | 797897.87 | 0.376232E+10 | 0.00 | 0.45 |
March | 0.253699E+10 | 0.00 | 0.00 | 5291056.86 | 0.00 | 0.00 | 0.364145E+10 | 0.00 | 0.43 |
April | 0.122700E+10 | 0.00 | 0.00 | 20557189.58 | 0.00 | 0.00 | 0.111969E+11 | 0.00 | 1.29 |
May | 0.125525E+10 | 0.00 | 0.00 | 14162110.77 | 0.00 | 0.00 | 0.875571E+10 | 0.00 | 1.04 |
June | 0.884416E+09 | 1986244.23 | 0.00 | 16834064.41 | 6788119.72 | 0.00 | 0.878725E+10 | 0.00 | 1.36 |
July | 0.107058E+10 | 7890838.55 | 0.00 | 20544504.44 | 845384.07 | 0.00 | 0.888919E+10 | 0.00 | 1.56 |
August | 0.110609E+10 | 0.00 | 0.00 | 28104565.46 | 0.00 | 0.00 | 0.103595E+11 | 0.00 | 2.02 |
September | 0.879410E+09 | 0.00 | 0.00 | 25433187.51 | 0.00 | 0.00 | 0.104648E+11 | 0.00 | 1.78 |
October | 0.169242E+10 | 0.00 | 0.00 | 12860289.48 | 0.00 | 0.00 | 0.770072E+10 | 0.00 | 0.92 |
November | 0.250553E+10 | 0.00 | 0.00 | 6120059.22 | 0.00 | 0.00 | 0.327885E+10 | 0.00 | 0.43 |
December | 0.321641E+10 | 0.00 | 0.00 | 3386576.95 | 0.00 | 7512911.61 | 0.168459E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.220395E+11 | 9877082.78 | 0.00 | 0.166412E+09 | 7633503.79 | 97757618.75 | 0.816909E+11 | 0.00 | 1.00 |
Minimum of Months | 0.879410E+09 | 0.00 | 0.00 | 3386576.95 | 0.00 | 0.00 | 0.168459E+10 | 0.00 | 0.30 |
Maximum of Months | 0.321641E+10 | 7890838.55 | 0.00 | 28104565.46 | 6788119.72 | 89446809.28 | 0.111969E+11 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171966E+10 | 0.00 | 0.00 | 2396618.48 | 0.00 | 0.00 | 0.174191E+10 | 0.00 | 0.33 |
February | 0.659353E+09 | 0.00 | 0.00 | 5839964.36 | 0.00 | 0.00 | 0.365860E+10 | 0.00 | 0.47 |
March | 0.168430E+09 | 0.00 | 0.00 | 9320258.30 | 0.00 | 0.00 | 0.640445E+10 | 0.00 | 0.70 |
April | 0.143972E+09 | 0.00 | 0.00 | 22417231.23 | 0.00 | 0.00 | 0.114094E+11 | 0.00 | 1.81 |
May | 0.302522E+09 | 0.00 | 0.00 | 15804811.94 | 0.00 | 0.00 | 0.865240E+10 | 0.00 | 1.44 |
June | 0.166010E+09 | 27024848.20 | 0.00 | 22532241.58 | 179546.86 | 0.00 | 0.103314E+11 | 0.00 | 2.24 |
July | 0.236769E+09 | 11122442.47 | 0.00 | 29192523.18 | 75703.25 | 0.00 | 0.106731E+11 | 0.00 | 2.60 |
August | 0.295547E+09 | 0.00 | 0.00 | 31996556.55 | 0.00 | 0.00 | 0.109891E+11 | 0.00 | 2.92 |
September | 0.293266E+09 | 0.00 | 0.00 | 14670290.65 | 0.00 | 0.00 | 0.644020E+10 | 0.00 | 1.60 |
October | 0.220836E+09 | 0.00 | 0.00 | 9189926.51 | 0.00 | 0.00 | 0.584908E+10 | 0.00 | 0.89 |
November | 0.254525E+09 | 0.00 | 0.00 | 7319198.17 | 0.00 | 0.00 | 0.469756E+10 | 0.00 | 0.58 |
December | 0.188725E+09 | 0.00 | 0.00 | 6502441.10 | 0.00 | 0.00 | 0.424500E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.464961E+10 | 38147290.66 | 0.00 | 0.177182E+09 | 255250.11 | 0.00 | 0.850922E+11 | 0.00 | 1.34 |
Minimum of Months | 0.143972E+09 | 0.00 | 0.00 | 2396618.48 | 0.00 | 0.00 | 0.174191E+10 | 0.00 | 0.33 |
Maximum of Months | 0.171966E+10 | 27024848.20 | 0.00 | 31996556.55 | 179546.86 | 0.00 | 0.114094E+11 | 0.00 | 2.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144587E+11 | 0.00 | 0.00 | 0.29 |
February | 0.334431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728684E+10 | 0.00 | 0.00 | 0.28 |
March | 0.411096E+11 | 0.00 | 0.00 | 543840.06 | 0.00 | 0.312284E+10 | 0.885534E+09 | 0.00 | 0.30 |
April | 0.216712E+11 | 0.00 | 0.00 | 29870046.10 | 0.00 | 0.00 | 0.214387E+11 | 0.00 | 0.42 |
May | 0.192872E+11 | 0.00 | 0.00 | 44458622.50 | 0.00 | 0.00 | 0.307688E+11 | 0.00 | 0.50 |
June | 0.103292E+11 | 10520136.91 | 0.00 | 82334930.13 | 75235417.51 | 0.00 | 0.471676E+11 | 0.00 | 0.78 |
July | 0.106941E+11 | 54422536.56 | 0.00 | 82363129.29 | 12226580.36 | 0.00 | 0.429730E+11 | 0.00 | 0.83 |
August | 0.125750E+11 | 0.00 | 0.00 | 78414827.46 | 0.00 | 0.00 | 0.370440E+11 | 0.00 | 0.84 |
September | 0.201954E+11 | 0.00 | 0.00 | 39313490.44 | 0.00 | 0.00 | 0.208465E+11 | 0.00 | 0.58 |
October | 0.315099E+11 | 0.00 | 0.00 | 5274874.09 | 0.00 | 0.573747E+09 | 0.444588E+10 | 0.00 | 0.31 |
November | 0.343076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582233E+10 | 0.00 | 0.00 | 0.29 |
December | 0.256480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197789E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.293137E+12 | 64942673.47 | 0.00 | 0.362574E+09 | 87461997.87 | 0.510433E+11 | 0.205570E+12 | 0.00 | 0.48 |
Minimum of Months | 0.103292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.411096E+11 | 54422536.56 | 0.00 | 82363129.29 | 75235417.51 | 0.197789E+11 | 0.471676E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168736E+11 | 0.00 | 0.00 | 761243.43 | 0.00 | 0.745141E+10 | 0.647561E+09 | 0.00 | 0.23 |
February | 0.166187E+11 | 0.00 | 0.00 | 3821815.37 | 0.00 | 0.344965E+10 | 0.262257E+10 | 0.00 | 0.24 |
March | 0.186450E+11 | 0.00 | 0.00 | 6329009.53 | 0.00 | 0.167661E+10 | 0.480774E+10 | 0.00 | 0.26 |
April | 0.747588E+10 | 0.00 | 0.00 | 99113098.73 | 0.00 | 1760467.89 | 0.513835E+11 | 0.00 | 0.91 |
May | 0.740842E+10 | 0.00 | 0.00 | 98643617.33 | 0.00 | 0.00 | 0.550511E+11 | 0.00 | 0.99 |
June | 0.438537E+10 | 13075257.60 | 0.00 | 0.129409E+09 | 45362602.99 | 0.00 | 0.600137E+11 | 0.00 | 1.39 |
July | 0.374466E+10 | 83421381.41 | 0.00 | 0.146772E+09 | 7895389.53 | 0.00 | 0.570308E+11 | 0.00 | 1.46 |
August | 0.458971E+10 | 0.00 | 0.00 | 0.143407E+09 | 0.00 | 0.00 | 0.574142E+11 | 0.00 | 1.61 |
September | 0.703472E+10 | 0.00 | 0.00 | 0.104620E+09 | 0.00 | 0.00 | 0.457940E+11 | 0.00 | 1.20 |
October | 0.135077E+11 | 0.00 | 0.00 | 26669769.75 | 0.00 | 0.343211E+09 | 0.134372E+11 | 0.00 | 0.38 |
November | 0.171667E+11 | 0.00 | 0.00 | 1567699.40 | 0.00 | 0.321054E+10 | 0.119567E+10 | 0.00 | 0.24 |
December | 0.134478E+11 | 0.00 | 0.00 | 33436.97 | 0.00 | 0.105518E+11 | 29746436.06 | 0.00 | 0.23 |
Annual Sum or Average | 0.130898E+12 | 96496639.00 | 0.00 | 0.761148E+09 | 53257992.52 | 0.266849E+11 | 0.349428E+12 | 0.00 | 0.76 |
Minimum of Months | 0.374466E+10 | 0.00 | 0.00 | 33436.97 | 0.00 | 0.00 | 29746436.06 | 0.00 | 0.23 |
Maximum of Months | 0.186450E+11 | 83421381.41 | 0.00 | 0.146772E+09 | 45362602.99 | 0.105518E+11 | 0.600137E+11 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302973E+11 | 0.00 | 0.00 | 45768658.34 | 0.00 | 0.560950E+10 | 0.330227E+11 | 0.00 | 0.43 |
February | 0.262342E+11 | 0.00 | 0.00 | 69136855.96 | 0.00 | 0.299684E+10 | 0.389591E+11 | 0.00 | 0.49 |
March | 0.311628E+11 | 0.00 | 0.00 | 33291186.90 | 0.00 | 0.121886E+10 | 0.242360E+11 | 0.00 | 0.39 |
April | 0.130008E+11 | 0.00 | 0.00 | 0.192611E+09 | 0.00 | 0.00 | 0.936462E+11 | 0.00 | 1.12 |
May | 0.140370E+11 | 0.00 | 0.00 | 0.128401E+09 | 0.00 | 0.00 | 0.772801E+11 | 0.00 | 0.96 |
June | 0.989793E+10 | 19817097.21 | 0.00 | 0.145292E+09 | 70210771.83 | 0.00 | 0.736015E+11 | 0.00 | 1.20 |
July | 0.909979E+10 | 0.105312E+09 | 0.00 | 0.183640E+09 | 9397836.46 | 0.00 | 0.746523E+11 | 0.00 | 1.36 |
August | 0.863260E+10 | 0.00 | 0.00 | 0.257356E+09 | 0.00 | 0.00 | 0.896246E+11 | 0.00 | 1.79 |
September | 0.102148E+11 | 0.00 | 0.00 | 0.267290E+09 | 0.00 | 0.00 | 0.987237E+11 | 0.00 | 1.75 |
October | 0.202557E+11 | 0.00 | 0.00 | 0.119164E+09 | 0.00 | 0.121381E+09 | 0.596639E+11 | 0.00 | 0.77 |
November | 0.278502E+11 | 0.00 | 0.00 | 47091093.38 | 0.00 | 0.271969E+10 | 0.266215E+11 | 0.00 | 0.42 |
December | 0.277381E+11 | 0.00 | 0.00 | 18875875.09 | 0.00 | 0.121792E+11 | 0.148408E+11 | 0.00 | 0.35 |
Annual Sum or Average | 0.228421E+12 | 0.125129E+09 | 0.00 | 0.150792E+10 | 79608608.30 | 0.248455E+11 | 0.704872E+12 | 0.00 | 0.92 |
Minimum of Months | 0.863260E+10 | 0.00 | 0.00 | 18875875.09 | 0.00 | 0.00 | 0.148408E+11 | 0.00 | 0.35 |
Maximum of Months | 0.311628E+11 | 0.105312E+09 | 0.00 | 0.267290E+09 | 70210771.83 | 0.121792E+11 | 0.987237E+11 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230854E+11 | 0.00 | 0.00 | 3249959.85 | 0.00 | 0.521874E+10 | 0.269955E+10 | 0.00 | 0.30 |
February | 0.209976E+11 | 0.00 | 0.00 | 11110786.91 | 0.00 | 0.210416E+10 | 0.764441E+10 | 0.00 | 0.33 |
March | 0.232011E+11 | 0.00 | 0.00 | 10792055.08 | 0.00 | 0.573073E+09 | 0.887997E+10 | 0.00 | 0.34 |
April | 0.805447E+10 | 0.00 | 0.00 | 97396049.38 | 0.00 | 0.00 | 0.489195E+11 | 0.00 | 0.94 |
May | 0.733053E+10 | 0.00 | 0.00 | 0.107744E+09 | 0.00 | 0.00 | 0.578787E+11 | 0.00 | 1.09 |
June | 0.411743E+10 | 0.287595E+09 | 0.00 | 0.144490E+09 | 784270.07 | 0.00 | 0.661322E+11 | 0.00 | 1.57 |
July | 0.401703E+10 | 0.110135E+09 | 0.00 | 0.183341E+09 | 1101341.20 | 0.00 | 0.635249E+11 | 0.00 | 1.71 |
August | 0.449836E+10 | 0.00 | 0.00 | 0.164105E+09 | 0.00 | 0.00 | 0.563322E+11 | 0.00 | 1.68 |
September | 0.784249E+10 | 0.00 | 0.00 | 92220320.39 | 0.00 | 0.00 | 0.382012E+11 | 0.00 | 1.14 |
October | 0.164846E+11 | 0.00 | 0.00 | 24767122.00 | 0.00 | 0.00 | 0.149460E+11 | 0.00 | 0.44 |
November | 0.220218E+11 | 0.00 | 0.00 | 3776471.06 | 0.00 | 0.199362E+10 | 0.295327E+10 | 0.00 | 0.30 |
December | 0.209326E+11 | 0.00 | 0.00 | 264770.03 | 0.00 | 0.804295E+10 | 0.351084E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.162583E+12 | 0.397730E+09 | 0.00 | 0.843257E+09 | 1885611.27 | 0.179326E+11 | 0.368463E+12 | 0.00 | 0.85 |
Minimum of Months | 0.401703E+10 | 0.00 | 0.00 | 264770.03 | 0.00 | 0.00 | 0.351084E+09 | 0.00 | 0.29 |
Maximum of Months | 0.232011E+11 | 0.287595E+09 | 0.00 | 0.183341E+09 | 1101341.20 | 0.804295E+10 | 0.661322E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320190E+10 | 0.00 | 0.00 | 0.30 |
February | 0.158168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226949E+10 | 0.00 | 0.00 | 0.30 |
March | 0.299080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139910E+10 | 0.00 | 0.00 | 0.32 |
April | 0.223261E+10 | 0.00 | 0.00 | 1921482.57 | 334652.39 | 0.294925E+09 | 0.153490E+10 | 0.00 | 0.39 |
May | 0.234051E+10 | 0.00 | 0.00 | 3089218.93 | 0.00 | 70144464.01 | 0.231032E+10 | 0.00 | 0.47 |
June | 0.119686E+10 | 695480.31 | 0.00 | 7164310.67 | 5574428.03 | 0.00 | 0.431645E+10 | 0.00 | 0.75 |
July | 0.113562E+10 | 2093538.97 | 0.00 | 7676407.73 | 511245.06 | 0.00 | 0.413659E+10 | 0.00 | 0.80 |
August | 0.127723E+10 | 0.00 | 0.00 | 6949618.53 | 0.00 | 0.00 | 0.348619E+10 | 0.00 | 0.79 |
September | 0.205604E+10 | 0.00 | 0.00 | 2869157.59 | 0.00 | 45016626.34 | 0.162292E+10 | 0.00 | 0.54 |
October | 0.262502E+10 | 0.00 | 0.00 | 112959.44 | 0.00 | 0.725882E+09 | 0.153716E+09 | 0.00 | 0.32 |
November | 0.174030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199802E+10 | 0.00 | 0.00 | 0.30 |
December | 0.869227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330959E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.211918E+11 | 2789019.29 | 0.00 | 29783155.44 | 6420325.48 | 0.133141E+11 | 0.175611E+11 | 0.00 | 0.47 |
Minimum of Months | 0.869227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.299080E+10 | 2093538.97 | 0.00 | 7676407.73 | 5574428.03 | 0.330959E+10 | 0.431645E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107202E+10 | 0.00 | 0.00 | 2441.82 | 0.00 | 0.172329E+10 | 6017123.02 | 0.00 | 0.30 |
February | 0.128022E+10 | 0.00 | 0.00 | 70123.80 | 0.00 | 0.114590E+10 | 60356957.49 | 0.00 | 0.30 |
March | 0.199572E+10 | 0.00 | 0.00 | 101386.60 | 0.00 | 0.720102E+09 | 0.118707E+09 | 0.00 | 0.32 |
April | 0.758317E+09 | 1579151.20 | 0.00 | 8742710.07 | 0.00 | 55452272.81 | 0.490444E+10 | 0.00 | 0.89 |
May | 0.837890E+09 | 0.00 | 0.00 | 8742004.72 | 0.00 | 15862315.10 | 0.521684E+10 | 0.00 | 0.96 |
June | 0.466671E+09 | 3004953.12 | 0.00 | 12528389.28 | 1836340.61 | 0.00 | 0.608658E+10 | 0.00 | 1.40 |
July | 0.413817E+09 | 5259231.11 | 0.00 | 13916407.82 | 316032.90 | 0.00 | 0.583261E+10 | 0.00 | 1.48 |
August | 0.438875E+09 | 0.00 | 0.00 | 13905396.38 | 0.00 | 0.00 | 0.586095E+10 | 0.00 | 1.63 |
September | 0.784990E+09 | 0.00 | 0.00 | 8792713.41 | 0.00 | 6219924.94 | 0.416397E+10 | 0.00 | 1.15 |
October | 0.145351E+10 | 0.00 | 0.00 | 1560511.81 | 0.00 | 0.356560E+09 | 0.966825E+09 | 0.00 | 0.41 |
November | 0.134554E+10 | 0.00 | 0.00 | 62.04 | 0.00 | 0.106681E+10 | 1079296.55 | 0.00 | 0.30 |
December | 0.853346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185218E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.117009E+11 | 9843335.42 | 0.00 | 68362147.74 | 2152373.51 | 0.694237E+10 | 0.332184E+11 | 0.00 | 0.79 |
Minimum of Months | 0.413817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.199572E+10 | 5259231.11 | 0.00 | 13916407.82 | 1836340.61 | 0.185218E+10 | 0.608658E+10 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194483E+10 | 0.00 | 0.00 | 2491248.11 | 0.00 | 0.169842E+10 | 0.194177E+10 | 0.00 | 0.38 |
February | 0.190813E+10 | 0.00 | 0.00 | 4351251.94 | 0.00 | 0.104717E+10 | 0.282362E+10 | 0.00 | 0.45 |
March | 0.271176E+10 | 0.00 | 0.00 | 1627444.50 | 0.00 | 0.901902E+09 | 0.134397E+10 | 0.00 | 0.36 |
April | 0.124903E+10 | 333990.31 | 0.00 | 16664015.01 | 0.00 | 0.159790E+09 | 0.913071E+10 | 0.00 | 1.08 |
May | 0.157907E+10 | 0.00 | 0.00 | 11056739.52 | 0.00 | 71747505.43 | 0.721077E+10 | 0.00 | 0.91 |
June | 0.106561E+10 | 3944753.60 | 0.00 | 13687076.59 | 3211229.13 | 550321.70 | 0.731833E+10 | 0.00 | 1.17 |
July | 0.887578E+09 | 2999006.26 | 0.00 | 17594564.70 | 477068.82 | 0.00 | 0.770199E+10 | 0.00 | 1.34 |
August | 0.764788E+09 | 0.00 | 0.00 | 25044247.96 | 0.00 | 0.00 | 0.932399E+10 | 0.00 | 1.74 |
September | 0.107627E+10 | 0.00 | 0.00 | 24161004.76 | 0.00 | 278022.73 | 0.967517E+10 | 0.00 | 1.68 |
October | 0.179134E+10 | 0.00 | 0.00 | 9183306.40 | 0.00 | 0.453357E+09 | 0.558838E+10 | 0.00 | 0.79 |
November | 0.209502E+10 | 0.00 | 0.00 | 2530897.68 | 0.00 | 0.104966E+10 | 0.157982E+10 | 0.00 | 0.38 |
December | 0.153945E+10 | 0.00 | 0.00 | 987008.09 | 0.00 | 0.229027E+10 | 0.783430E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.186129E+11 | 7277750.17 | 0.00 | 0.129379E+09 | 3688297.95 | 0.767315E+10 | 0.644219E+11 | 0.00 | 0.88 |
Minimum of Months | 0.764788E+09 | 0.00 | 0.00 | 987008.09 | 0.00 | 0.00 | 0.783430E+09 | 0.00 | 0.33 |
Maximum of Months | 0.271176E+10 | 3944753.60 | 0.00 | 25044247.96 | 3211229.13 | 0.229027E+10 | 0.967517E+10 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135925E+10 | 0.00 | 0.00 | 107907.22 | 0.00 | 0.131803E+10 | 0.101190E+09 | 0.00 | 0.30 |
February | 0.149763E+10 | 0.00 | 0.00 | 689834.92 | 0.00 | 0.693877E+09 | 0.583816E+09 | 0.00 | 0.33 |
March | 0.207293E+10 | 0.00 | 0.00 | 564301.90 | 0.00 | 0.439058E+09 | 0.541124E+09 | 0.00 | 0.34 |
April | 0.940405E+09 | 215037.15 | 0.00 | 8527455.24 | 0.00 | 49229723.82 | 0.456438E+10 | 0.00 | 0.90 |
May | 0.917949E+09 | 0.00 | 0.00 | 9797848.44 | 0.00 | 20147027.43 | 0.541962E+10 | 0.00 | 1.04 |
June | 0.451072E+09 | 21558582.35 | 0.00 | 14166950.25 | 214262.80 | 0.00 | 0.662528E+10 | 0.00 | 1.55 |
July | 0.438353E+09 | 3579421.98 | 0.00 | 17270453.51 | 36592.17 | 0.00 | 0.646377E+10 | 0.00 | 1.68 |
August | 0.429879E+09 | 0.00 | 0.00 | 16058515.56 | 0.00 | 0.00 | 0.570360E+10 | 0.00 | 1.63 |
September | 0.869654E+09 | 0.00 | 0.00 | 8040443.13 | 0.00 | 0.00 | 0.358018E+10 | 0.00 | 1.09 |
October | 0.155656E+10 | 0.00 | 0.00 | 1612878.98 | 0.00 | 0.260575E+09 | 0.122728E+10 | 0.00 | 0.46 |
November | 0.157079E+10 | 0.00 | 0.00 | 182302.84 | 0.00 | 0.716092E+09 | 0.158918E+09 | 0.00 | 0.30 |
December | 0.102438E+10 | 0.00 | 0.00 | 1420.13 | 0.00 | 0.160399E+10 | 4270972.98 | 0.00 | 0.29 |
Annual Sum or Average | 0.131289E+11 | 25353041.48 | 0.00 | 77020312.12 | 250854.97 | 0.510100E+10 | 0.349734E+11 | 0.00 | 0.83 |
Minimum of Months | 0.429879E+09 | 0.00 | 0.00 | 1420.13 | 0.00 | 0.00 | 4270972.98 | 0.00 | 0.29 |
Maximum of Months | 0.207293E+10 | 21558582.35 | 0.00 | 17270453.51 | 214262.80 | 0.160399E+10 | 0.662528E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3341296.07 | 0.00 | 0.00 | 0.637187E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7974510.70 | 0.00 | 0.00 | 0.561609E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13992597.98 | 0.00 | 0.00 | 0.622567E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18566930.64 | 0.00 | 0.00 | 0.465358E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4337253.02 | 0.00 | 0.00 | 0.472292E+09 | 0.00 | 0.29 |
June | 0.00 | 125392.80 | 0.00 | 9428686.06 | 0.00 | 0.00 | 0.321887E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 13954596.80 | 0.00 | 0.00 | 0.226140E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 20471945.17 | 0.00 | 0.00 | 0.219458E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 4273069.56 | 0.00 | 0.00 | 0.311065E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8943208.22 | 0.00 | 0.00 | 0.461710E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12712932.34 | 0.00 | 0.00 | 0.529182E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17310051.23 | 0.00 | 0.00 | 0.611191E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 125392.80 | 0.00 | 0.135307E+09 | 0.00 | 0.00 | 0.543965E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3341296.07 | 0.00 | 0.00 | 0.219458E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 125392.80 | 0.00 | 20471945.17 | 0.00 | 0.00 | 0.637187E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31759918.44 | 0.00 | 0.00 | 18483147.72 | 0.00 | 0.00 | 0.635516E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 64848514.33 | 0.00 | 0.00 | 0.563047E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.123185E+09 | 0.00 | 0.00 | 0.624199E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.173460E+09 | 0.00 | 0.00 | 0.466565E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 37347980.43 | 0.00 | 0.00 | 0.473071E+10 | 0.00 | 0.29 |
June | 0.00 | 1154053.57 | 0.00 | 87553742.71 | 0.00 | 0.00 | 0.322943E+10 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 0.131354E+09 | 0.00 | 0.00 | 0.227159E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.193802E+09 | 0.00 | 0.00 | 0.220622E+10 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 36749725.47 | 0.00 | 0.00 | 0.312870E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 76732131.52 | 0.00 | 0.00 | 0.463159E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.109279E+09 | 0.00 | 0.00 | 0.530935E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.148479E+09 | 0.00 | 0.00 | 0.613542E+10 | 0.00 | 0.28 |
Annual Sum or Average | 31759918.44 | 1154053.57 | 0.00 | 0.120127E+10 | 0.00 | 0.00 | 0.545363E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18483147.72 | 0.00 | 0.00 | 0.220622E+10 | 0.00 | 0.28 |
Maximum of Months | 31759918.44 | 1154053.57 | 0.00 | 0.193802E+09 | 0.00 | 0.00 | 0.635516E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255663E+09 | 0.00 | 0.00 | 646728.66 | 0.00 | 0.00 | 0.378963E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5190037.72 | 0.00 | 0.00 | 0.564412E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11048008.24 | 0.00 | 0.00 | 0.625495E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16785647.04 | 0.00 | 0.00 | 0.467132E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3285100.70 | 0.00 | 0.00 | 0.473650E+09 | 0.00 | 0.29 |
June | 0.00 | 119377.24 | 0.00 | 8546867.80 | 0.00 | 0.00 | 0.323347E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 12996477.03 | 0.00 | 0.00 | 0.227449E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 19195780.16 | 0.00 | 0.00 | 0.220972E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 3210916.76 | 0.00 | 0.00 | 0.314200E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6527511.19 | 0.00 | 0.00 | 0.464971E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9573866.44 | 0.00 | 0.00 | 0.532573E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13482201.21 | 0.00 | 0.00 | 0.614950E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.255663E+09 | 119377.24 | 0.00 | 0.110489E+09 | 0.00 | 0.00 | 0.520811E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 646728.66 | 0.00 | 0.00 | 0.220972E+09 | 0.00 | 0.28 |
Maximum of Months | 0.255663E+09 | 119377.24 | 0.00 | 19195780.16 | 0.00 | 0.00 | 0.625495E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.503841E+09 | 0.00 | 0.00 | 0.422703E+12 | 0.00 | 9.33 |
February | 0.00 | 0.00 | 0.00 | 0.932768E+09 | 0.00 | 0.00 | 0.647075E+12 | 0.00 | 15.86 |
March | 0.00 | 0.00 | 0.00 | 0.143455E+10 | 0.00 | 0.00 | 0.102461E+13 | 0.00 | 24.18 |
April | 0.00 | 0.00 | 0.00 | 0.224437E+10 | 0.00 | 0.00 | 0.122010E+13 | 0.00 | 36.30 |
May | 0.00 | 0.00 | 0.00 | 0.545148E+09 | 0.00 | 0.00 | 0.389955E+12 | 0.00 | 13.02 |
June | 0.00 | 242939.51 | 0.00 | 0.113993E+10 | 0.00 | 0.00 | 0.571542E+12 | 0.00 | 27.28 |
July | 0.00 | 20813702.54 | 0.00 | 0.199698E+10 | 0.00 | 0.00 | 0.764485E+12 | 0.00 | 39.48 |
August | 0.00 | 0.00 | 0.00 | 0.274073E+10 | 0.00 | 0.00 | 0.812468E+12 | 0.00 | 46.47 |
September | 0.00 | 0.00 | 0.00 | 0.572328E+09 | 0.00 | 0.00 | 0.355518E+12 | 0.00 | 17.18 |
October | 0.00 | 0.00 | 0.00 | 0.100906E+10 | 0.00 | 0.00 | 0.651879E+12 | 0.00 | 20.75 |
November | 0.00 | 0.00 | 0.00 | 0.145307E+10 | 0.00 | 0.00 | 0.938552E+12 | 0.00 | 25.09 |
December | 0.00 | 0.00 | 0.00 | 0.206797E+10 | 0.00 | 0.00 | 0.130825E+13 | 0.00 | 28.82 |
Annual Sum or Average | 0.00 | 21056642.05 | 0.00 | 0.166407E+11 | 0.00 | 0.00 | 0.910714E+13 | 0.00 | 25.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.503841E+09 | 0.00 | 0.00 | 0.355518E+12 | 0.00 | 9.33 |
Maximum of Months | 0.00 | 20813702.54 | 0.00 | 0.274073E+10 | 0.00 | 0.00 | 0.130825E+13 | 0.00 | 46.47 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.145732E+12 | 0.308649E+10 | 0.00 | 0.225986E+13 | 0.130107E+12 |
February | 0.235514E+12 | 0.437803E+10 | 0.00 | 0.232717E+13 | 0.192834E+12 |
March | 0.283568E+12 | 0.276720E+10 | 0.00 | 0.295915E+13 | 0.287052E+12 |
April | 0.731302E+12 | 0.341083E+10 | 0.00 | 0.337460E+13 | 0.443684E+12 |
May | 0.902801E+12 | 0.815628E+10 | 0.00 | 0.251730E+13 | 0.187512E+12 |
June | 0.905874E+12 | 0.641204E+10 | 0.00 | 0.268277E+13 | 0.433102E+12 |
July | 0.913652E+12 | 0.614348E+10 | 0.00 | 0.285686E+13 | 0.763635E+12 |
August | 0.746490E+12 | 0.452865E+10 | 0.00 | 0.285026E+13 | 0.120038E+13 |
September | 0.552393E+12 | 0.488556E+10 | 0.00 | 0.249049E+13 | 0.360813E+12 |
October | 0.254500E+12 | 0.479602E+10 | 0.00 | 0.262107E+13 | 0.233293E+12 |
November | 0.113813E+12 | 0.579989E+10 | 0.00 | 0.277090E+13 | 0.264170E+12 |
December | 0.549361E+11 | 0.780322E+10 | 0.00 | 0.304311E+13 | 0.366921E+12 |
Annual Sum or Average | 0.584058E+13 | 0.621677E+11 | 0.00 | 0.327535E+14 | 0.486350E+13 |
Minimum of Months | 0.549361E+11 | 0.276720E+10 | 0.00 | 0.225986E+13 | 0.130107E+12 |