Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:21:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26081.58 | 563.07 | 563.07 |
Net Site Energy | 26081.58 | 563.07 | 563.07 |
Total Source Energy | 82505.73 | 1781.20 | 1781.20 |
Net Source Energy | 82505.73 | 1781.20 | 1781.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 45.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1670.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2461.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 347.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2384.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 395.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 661.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4074.04 |
Humidification | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.73 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 392.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26036.15 | 45.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6532.94 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 45.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1670.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2461.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 347.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2384.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 395.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 661.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4074.04 |
Humidification | General | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.73 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 392.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 45.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1670.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2461.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 347.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2384.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 395.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 661.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4074.04 |
Humidification | Unassigned | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.73 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 392.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 129.19 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 562.09 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 129.19 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 562.09 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26036.151 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26036.151 | 100.00 |
Total On-Site and Utility Electric Sources | 26036.151 | 100.00 |
Total Electricity End Uses | 26036.151 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6532.94 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6532.94 | 100.00 |
Total Water End Uses | 6532.94 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 839.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5914.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-10:30 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 16-OCT-11:09 |
Heating | 0.00 | 322456.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 420641.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233115.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 169826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37240.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 72551.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1958493.27 | 322456.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 322456.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 420641.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 169826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 37240.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 72551.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 33929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 49.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5290.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7797.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1100.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7550.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2093.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1521.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1244.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 82456.49 | 49.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 45.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1780.13 | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 45.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1780.13 | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 4.98 | 0.425376 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.41 | 0.351413 | 0.299000 | 1.62 | 0.937101 | 0.500000 | 0.001084 | 0.000140 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 50.88 | 0.373809 | 0.318000 | 16.18 | 0.996824 | 0.500000 | 0.001019 | 0.002868 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.96 | 0.383431 | 0.326000 | 1.62 | 1.00 | 0.500000 | 0.000994 | 0.000515 | 1.78 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.834864 | 0.286059 | 0.243000 | 0.202872 | 0.762824 | 0.500000 | 0.001332 | 0.000043 | 0.202872 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.04 | 0.148329 | 0.126000 | 0.130737 | 0.395543 | 0.500000 | 0.002569 | 0.000030 | 0.130737 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.18 | 0.202455 | 0.172000 | 0.202899 | 0.539880 | 0.500000 | 0.001882 | 0.000057 | 0.202899 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.30 | 0.118149 | 0.100000 | 0.130263 | 0.315065 | 0.500000 | 0.003225 | 0.000017 | 0.130263 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.63 | 0.313028 | 0.266000 | 2.03 | 0.834741 | 0.500000 | 0.001217 | 0.001175 | 4.08 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.67 | 0.384748 | 0.500000 | 0.002641 | 0.000790 | 2.74 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.30 | 0.211372 | 0.180000 | 2.03 | 0.563660 | 0.500000 | 0.001803 | 0.001183 | 4.10 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.29 | 0.136366 | 0.116000 | 1.31 | 0.363643 | 0.500000 | 0.002794 | 0.000690 | 2.39 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.862193 | 0.276992 | 0.235000 | 0.202615 | 0.738646 | 0.500000 | 0.001375 | 0.000160 | 0.555986 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.06 | 0.144758 | 0.123000 | 0.130772 | 0.386022 | 0.500000 | 0.002632 | 0.000106 | 0.368880 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.22 | 0.195317 | 0.166000 | 0.202979 | 0.520844 | 0.500000 | 0.001951 | 0.000161 | 0.558611 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 0.128675 | 0.109000 | 0.130372 | 0.343135 | 0.500000 | 0.002961 | 0.000099 | 0.342235 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15991.94 | 0.000140 | 322.38 | |
CORE_MID VAV BOX REHEAT COIL | 327785.36 | 0.002868 | 7377.27 | |
CORE_TOP VAV BOX REHEAT COIL | 58881.19 | 0.000515 | 1556.10 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4889.44 | 0.000043 | 115.10 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3441.63 | 0.000030 | 83.26 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6552.33 | 0.000057 | 171.35 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1979.79 | 0.000017 | 42.15 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 134256.10 | 0.001175 | 3542.83 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 90281.63 | 0.000790 | 2382.28 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 135170.48 | 0.001183 | 3566.93 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 78822.44 | 0.000690 | 2080.25 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18303.74 | 0.000160 | 482.84 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12143.13 | 0.000106 | 320.32 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18389.96 | 0.000161 | 485.11 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11267.86 | 0.000099 | 297.25 | |
VAV_BOT WITH REHEAT HEATING COIL | 25941.30 | 0.000227 | 447.90 | |
VAV_MID WITH REHEAT HEATING COIL | 178424.12 | 0.001561 | 3127.22 | |
VAV_TOP WITH REHEAT HEATING COIL | 16485.56 | 0.000144 | 290.57 | |
CAV_BAS HEATING COIL | 231088.18 | 0.000875 | 2622.54 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.476161 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.55 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.462064 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.88 | 2.29 | 9.77 | 2.29 | 8.72 | 8.72 | 0.300000 | 0.261997 | 8.72 |
VAV_MID WITH REHEAT | 45.88 | 22.87 | 91.76 | 24.09 | 80.90 | 80.90 | 0.300000 | 0.297756 | 80.90 |
VAV_TOP WITH REHEAT | 4.65 | 2.28 | 9.30 | 3.61 | 8.55 | 8.55 | 0.300000 | 0.421700 | 8.55 |
CAV_BAS | 0.000000 | 0.000000 | 4.98 | 1.20 | 4.98 | 4.98 | 1.00 | 0.241046 | 4.98 |
AIRLOOP DATACENTER BASEMENT | 24.82 | 24.82 | 24.82 | 24.82 | 24.82 | 24.82 | 1.00 | 0.999990 | 24.82 |
AIRLOOP DATACENTER BOT | 0.476161 | 0.476161 | 0.476161 | 0.476161 | 0.476161 | 0.476161 | 1.00 | 1.00 | 0.476161 |
AIRLOOP DATACENTER MID | 4.55 | 4.55 | 4.55 | 4.55 | 4.55 | 4.55 | 1.00 | 1.00 | 4.55 |
AIRLOOP DATACENTER TOP | 0.462064 | 0.462064 | 0.462064 | 0.462064 | 0.462064 | 0.462064 | 1.00 | 1.00 | 0.462064 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.72 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 80.90 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.55 | |
CAV_BAS_OA_CONTROLLER | 4.98 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.82 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.476161 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.55 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.462064 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.78 | 6.67 | 11.01 | 0.008722 | 0.008500 | 161182.76 | 0.004610 | 8.72 |
VAV_MID WITH REHEAT COOLING COIL | 25.99 | 6.67 | 11.01 | 0.008733 | 0.008500 | 1518525.00 | 0.043430 | 80.90 |
VAV_TOP WITH REHEAT COOLING COIL | 25.73 | 6.67 | 11.01 | 0.008716 | 0.008500 | 157457.20 | 0.004503 | 8.55 |
CAV_BAS COOLING COIL | 25.38 | 6.67 | 10.99 | 0.008832 | 0.008500 | 91407.47 | 0.002614 | 4.98 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.72 |
VAV_MID WITH REHEAT FAN | 80.90 |
VAV_TOP WITH REHEAT FAN | 8.55 |
CAV_BAS FAN | 4.98 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004610 | 0.000103 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000227 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.043430 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001561 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004503 | 0.000106 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000144 | |
CAV_BAS_COOLC_CONTROLLER | 0.002614 | 0.000182 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.82 | 489487.20 | 348915.86 | 0.011988 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.476161 | 9210.19 | 6628.39 | 0.000226 |
AIRLOOP DATACENTER MID COOLING COIL | 4.55 | 88002.25 | 63311.30 | 0.002155 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.462064 | 8944.59 | 6434.48 | 0.000219 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.82 | 24.82 | 24.82 | 24.82 | 489487.20 | 489487.20 | 14546.91 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.476161 | 0.476161 | 0.476161 | 0.476161 | 9210.19 | 9210.19 | 672.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.55 | 4.55 | 4.55 | 4.55 | 88002.25 | 88002.25 | 6720.07 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.462064 | 0.462064 | 0.462064 | 0.462064 | 8944.59 | 8944.59 | 672.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.82 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.476161 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.55 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.462064 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.82 | 489487.20 | 0.011988 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.476161 | 9210.19 | 0.000226 |
AIRLOOP DATACENTER MID HEATING COIL | 4.55 | 88002.25 | 0.002155 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.462064 | 8944.59 | 0.000219 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14546.91 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 672.01 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6720.07 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 672.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000097 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.055157 | 8916.28 | |
HEATSYS1 PUMP | 0.010839 | 3232.03 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.055157 | 6.62 |
HEATSYS1 | 0.010839 | 1.30 |
COOLSYS1_SUPPLY | 0.055157 | 6.62 |
SINGLE WATER PLANT LOOP | 0.014587 | 1.75 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.055157 | 0.055157 | 231521.30 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1239008.01 | 1239008.01 | 0.010839 |
CENTRAL BOILER | 600871.24 | 588613.80 | 0.014587 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.027578 | 3086.52 |
COOLSYS1 CHILLER2 PUMP | 0.027578 | 3086.52 |
PLANT CIRC PUMP | 0.014587 | 3683.65 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.055157 | 0.027885 | 975009.57 | 975010.31 | 0.050114 |
COOLSYS1 CHILLER2 | 0.055157 | 0.027885 | 975009.57 | 975010.31 | 0.050114 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014587 | 144840.96 | 73322.85 | 72420.48 | 7004.20 | 43993.71 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.100227 | 12.03 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.100227 | 24568.37 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 38.58 | 1167855.69 | 7.72 | 145981.96 |
TOWERWATERSYS COOLTOWER 2 | 38.58 | 1167855.69 | 7.72 | 145981.96 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.050560 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1598E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1613E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4848E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4861E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1390E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1400E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1956E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3022E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5154E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6096E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1648E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2402E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1051 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6440E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1176 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0925E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7574E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9570E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1939E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2918E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5133E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5977E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1629E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2328E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1596E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1611E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4846E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4858E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1388E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1397E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5873E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7463E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3347E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5002E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2762E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3577E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8165E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8760E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4211E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6386E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7363E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5402E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5425E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6119E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2772E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3272E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2497E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2683E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7723E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7737E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5128E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5139E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3406E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3414E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8039E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8858E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5380E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6016E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3596E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4010E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7764E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4548E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1339E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1037E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9136E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4491E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8037E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8833E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5383E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6012E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3610E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4057E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7723E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7737E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5128E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5139E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3406E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3414E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7781E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8460E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5676E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6169E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4526E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4721E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2252E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0327E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9208E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8303E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1082E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6843E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8282E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0104E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6317E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8261E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4799E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5664E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1033 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5600E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1118 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.1337E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.4862E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4245E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5840E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7303E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1403E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4333E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4690E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3150E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4734E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3076E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7435E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8265E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4985E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3751E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0465E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9472E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7063E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6993E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8862E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5081E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1034 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5742E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1119 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1500E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5000E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4356E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5872E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7344E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1438E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4370E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4761E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3198E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4738E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3102E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7441E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8286E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5025E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3776E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0505E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9518E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7109E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7036E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8941E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5134E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67899.00576 | 67899.00576 | 4.97895 | 4.97895 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 73807.02720 | 73807.02720 | 5.41256 | 5.41256 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 694050.27334 | 694050.27334 | 50.88276 | 50.88276 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 167893.94275 | 167893.94275 | 7.15003 | 10.77825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67667.35341 | 67667.35341 | 4.96058 | 4.96058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 41277.82507 | 41277.82507 | 1.78143 | 1.78143 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11277.14770 | 11277.14770 | 0.83486 | 0.83486 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2887.35346 | 2887.35346 | 0.12370 | 0.13533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14015.76560 | 14015.76560 | 1.03759 | 1.03759 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.22398E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2151.03648 | 2151.03648 | 9.39436E-002 | 9.39436E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15934.46022 | 15934.46022 | 1.17965 | 1.17965 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 30.73633 | 8.23260E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4549.14356 | 4549.14356 | 0.19613 | 0.19613 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17595.84047 | 17595.84047 | 1.30263 | 1.30263 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 695.26333 | 695.26333 | 3.01097E-002 | 8.72129E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 103055.96655 | 103055.96655 | 7.62937 | 7.62937 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 94014.54482 | 94014.54482 | 4.07500 | 4.07500 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 144089.73019 | 144089.73019 | 10.66707 | 10.66707 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 25.84133 | 8.22486E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 63216.99310 | 63216.99310 | 2.74058 | 2.74058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 152622.56957 | 152622.56957 | 11.29882 | 11.29882 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 94653.77788 | 94653.77788 | 4.10283 | 4.10283 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 152452.54957 | 152452.54957 | 11.28617 | 11.28617 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.23188E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 55205.83270 | 55205.83270 | 2.39185 | 2.39185 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11646.34642 | 11646.34642 | 0.86219 | 0.86219 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12811.95587 | 12811.95587 | 0.55599 | 0.55599 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14361.42984 | 14361.42984 | 1.06319 | 1.06319 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8499.45113 | 8499.45113 | 0.36888 | 0.36888 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16516.92041 | 16516.92041 | 1.22276 | 1.22276 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12872.21912 | 12872.21912 | 0.55861 | 0.55861 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16156.45048 | 16156.45048 | 1.19607 | 1.19607 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7887.64945 | 7887.64945 | 0.34223 | 0.34223 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8154.58688 | 8154.58688 | 0.47616 | 0.47616 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77866.29418 | 77866.29418 | 4.54679 | 4.54679 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7913.14175 | 7913.14175 | 0.46206 | 0.46206 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369604.69156 | 425045.39529 | 21.58149 | 24.81871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 23.20100 | 8.22076E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 3.80000 | 5.05843E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 128499.29 | 8.72195 | 8.72195 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 16979.82 | 1.58873 | 1.58873 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1166837.40 | 80.90025 | 80.90025 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 216949.83 | 24.08851 | 24.08851 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 131360.63 | 8.55381 | 8.55381 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 21465.93 | 3.60714 | 3.60714 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
7 | CAV_BAS | Cooling | Sensible | 68335.71 | 4.97895 | 4.97895 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51592.61 | 1.20016 | 1.20016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 419735.54 | 24.81896 | 24.81896 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14546.91 | 0.33839 | 0.33839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8064.56 | 0.47616 | 0.47616 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77022.96 | 4.54679 | 4.54679 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6720.07 | 0.15632 | 0.15632 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7830.05 | 0.46206 | 0.46206 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 4.97895 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.42538 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.41256 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35141 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61836 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93710 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08419E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39904E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61836 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15991.94036 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39904E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 322.38496 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 50.88276 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37381 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18072 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99682 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01924E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.86761E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18072 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 327785.36485 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.86761E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7377.27289 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.96058 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38343 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61715 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.93659E-004 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.15118E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78143 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 58881.19240 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.15118E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1556.09842 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83486 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28606 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20287 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76282 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33189E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.27749E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20287 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4889.43842 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.27749E-005 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 115.09845 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03759 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14833 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13074 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39554 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56862E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01089E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13074 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3441.63108 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01089E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 83.25551 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17965 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20246 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17200 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20290 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53988 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88190E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.73227E-005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20290 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6552.33124 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.73227E-005 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.35319 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30263 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11815 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13026 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31506 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22473E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73200E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13026 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1979.78511 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73200E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.14657 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.62937 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31303 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02941 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83474 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21714E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17453E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.07500 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 134256.09843 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17453E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3542.83109 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.66707 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38475 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64069E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.89823E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.74058 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 90281.63226 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.89823E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2382.28299 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.29882 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21137 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03379 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56366 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80251E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18253E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.10283 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 135170.47888 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18253E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3566.92925 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.28617 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13637 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30920 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36364 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79395E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.89573E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.39185 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 78822.44301 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.89573E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2080.25500 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86219 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27699 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20262 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73865 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37549E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60129E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55599 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18303.74111 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60129E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 482.84220 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06319 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14476 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13077 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38602 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63197E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06233E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36888 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12143.13050 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06233E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 320.31842 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22276 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19532 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16600 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20298 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52084 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95068E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60883E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55861 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18389.95891 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60883E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 485.11397 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19607 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12868 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13037 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34313 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96094E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.85761E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34223 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11267.85600 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.85761E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 297.25235 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47616 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.54679 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46206 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.81871 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.88365 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28513 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.76730 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28513 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.72195 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.72195 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.26200 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 45.88210 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86516 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 91.76419 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.08851 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 80.90025 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 80.90025 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29776 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.65240 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28389 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.30480 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.60714 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.55381 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.55381 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42170 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.97895 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.97895 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.97895 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.24105 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.81871 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.81871 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.81871 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.81871 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.81896 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.81896 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47616 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47616 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47616 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47616 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47616 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47616 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.54679 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.54679 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.54679 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.54679 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.54679 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.54679 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46206 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46206 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46206 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46206 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46206 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46206 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.72195 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 80.90025 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.55381 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.97895 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.81896 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47616 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.54679 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46206 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.72195 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.77667 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00915 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72175E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 161182.76377 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.60981E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.72195 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 25941.30292 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26946E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 447.90333 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.72195 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.60981E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.03299E-004 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26946E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 80.90025 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.98880 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00919 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73313E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1518524.99741 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.34296E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 80.90025 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 178424.11919 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56093E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3127.22137 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 80.90025 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.34296E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.09646E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.56093E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.55381 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.73196 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00913 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71566E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 157457.20087 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.50326E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.55381 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 16485.56287 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44223E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 290.56592 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.55381 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50326E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.05744E-004 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44223E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.97895 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.37689 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98626 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.83249E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 91407.46520 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.61424E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.97895 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 231088.17838 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.54389 |
350 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.97895 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.61424E-003 |
352 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82152E-004 |
353 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.81896 |
355 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.81896 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 489487.20413 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 348915.85833 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.19875E-002 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.81896 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.81896 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.81896 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.81896 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 489487.20413 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 489487.20413 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14546.90948 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.81896 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.81896 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 489487.20413 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.19875E-002 |
372 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14546.90948 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 9.72367E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47616 |
378 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47616 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9210.18685 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6628.39163 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25557E-004 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47616 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47616 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47616 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47616 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9210.18685 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9210.18685 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
391 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47616 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47616 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9210.18685 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25557E-004 |
395 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.54679 |
397 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.54679 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 88002.24870 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 63311.29888 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.15517E-003 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.54679 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.54679 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.54679 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.54679 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 88002.24870 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 88002.24870 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6720.06953 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
410 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.54679 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.54679 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 88002.24870 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.15517E-003 |
414 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6720.06953 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46206 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46206 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 8944.59009 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6434.47526 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19052E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46206 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46206 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46206 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46206 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8944.59009 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8944.59009 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46206 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46206 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 8944.59009 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19052E-004 |
433 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.51569E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8916.27803 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.51569E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.61883 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.51569E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.51569E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 231521.29979 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.08394E-002 |
443 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.30073 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.08394E-002 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3232.02576 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
447 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1239008.00755 |
448 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1239008.01000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.08394E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.51569E-002 |
451 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.61883 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.75785E-002 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3086.51999 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.75785E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3086.51999 |
456 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.51569E-002 |
457 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.78852E-002 |
458 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 975009.57035 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 975010.31000 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.01136E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.51569E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.78852E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 975009.57035 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 975010.31000 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.01136E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.45873E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.75047 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.45873E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3683.65161 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.45873E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 144840.95672 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 73322.85396 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 72420.47836 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 43993.71238 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 600871.24309 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 588613.80000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.45873E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10023 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.02727 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10023 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 24568.36971 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 38.58397 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1167855.69324 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.71679 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 145981.96166 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 38.58397 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1167855.69324 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.71679 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 145981.96166 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.05600E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.05600E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15163.68 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 310631.98 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 55809.35 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4632.36 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3260.31 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6204.43 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1876.65 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 127216.85 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 85547.21 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 128083.08 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 74691.28 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17342.92 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11505.63 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17424.60 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10676.46 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 21954.76 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 155333.12 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 14502.55 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.96 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 201438.64 | 146010.32 | 55428.33 | 0.72 | 33545.45 | 340.24 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1881222.98 | 1359263.40 | 521959.58 | 0.72 | 310140.39 | 3145.62 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 197204.25 | 143058.88 | 54145.36 | 0.73 | 32919.55 | 333.89 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 114984.84 | 83384.21 | 31600.63 | 0.73 | 19434.37 | 197.11 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 8.8139003917E-004 | 1.0766121704E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2171822982 | 0.2189489989 | Pass | Pass | 0.1216881402 | 0.3264824023 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.2923907630E-003 | 5.7231781366E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5128975624E-002 | 9.9013120390E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1419387218 | 0.1474015245 | Pass | Pass | 0.1204400700 | 0.3248849626 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1661007580 | 0.1819034394 | Pass | Pass | 0.1216682000 | 0.3285796813 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1504087923 | 0.1508318447 | Pass | Pass | 0.1204396632 | 0.3235081757 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1491150297 | 0.1528322227 | Pass | Pass | 0.1204538059 | 0.3248974470 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5333848314E-002 | 2.1207652510E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.1867730336E-002 | 0.1039057912 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.8856106451E-002 | 9.1329178694E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.1337138164E-002 | 4.0762930859E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0114421392E-002 | 2.3499849675E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.2487627536E-002 | 0.1001160618 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.0241211580E-002 | 8.8043005148E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.5900725873E-002 | 3.9936145029E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6678279463E-002 | 3.5374145154E-002 | Pass | Pass | 1.0568412042 | 8.5203065518 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.3164063207E-003 | 3.6420694030E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6082782196E-002 | 3.5551977854E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7009333292E-006 | 7.0260026803E-006 | Pass | Pass | 2.5367920738E-003 | 2.1448930107E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.5455980202E-006 | 5.4956012339E-006 | Pass | Pass | 1.0111678975E-002 | 6.2786981293E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5148017770E-002 | 1.3137272906E-002 | Pass | Pass | 2.4517836388E-002 | 4.6313685836E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.1526737184E-005 | 1.3672463457E-004 | Pass | Pass | 4.6116961054E-005 | 1.0818541076E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6404.49 | 39.32 | 0.00 | 26939.57 | 12243.64 | 45627.02 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.424_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.55 | 0.0000 | Y | 10.70 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.43 | 0.0000 | Y | 6.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.22 | 0.0000 | Y | 10.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 6.83 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.50 | 0.0000 | Y | 106.79 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.40 | 0.0000 | Y | 68.57 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 105.63 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 68.23 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.50 | 0.0000 | Y | 10.68 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.40 | 0.0000 | Y | 6.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 10.56 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 6.82 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 775.53 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.14 | 42.14 | 104.99 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.75 | 62.95 | 11.69 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.75 | 46.20 | 230.67 | |
Exterior Lighting Total | 40855.88 | 347.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1922632.25 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1239008.01 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 975010.31 | 5.17 | 971708.60 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 975010.31 | 5.17 | 971708.60 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 603624.69 | |||||
CENTRAL BOILER | Boiler:HotWater | 588613.80 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1167855.69 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1167855.69 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 161182.76 | 201438.64 | 146010.32 | 55428.33 | 0.72 | - | 33545.45 | 340.24 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1518525.00 | 1881222.98 | 1359263.40 | 521959.58 | 0.72 | - | 310140.39 | 3145.62 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 157457.20 | 197204.25 | 143058.88 | 54145.36 | 0.73 | - | 32919.55 | 333.89 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 91407.47 | 114984.84 | 83384.21 | 31600.63 | 0.73 | - | 19434.37 | 197.11 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 489487.20 | 348915.86 | 140571.35 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9210.19 | 6628.39 | 2581.80 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 88002.25 | 63311.30 | 24690.95 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8944.59 | 6434.48 | 2510.11 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15991.94 | 15163.68 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 327785.36 | 310631.98 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 58881.19 | 55809.35 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4889.44 | 4632.36 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3441.63 | 3260.31 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6552.33 | 6204.43 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 1979.79 | 1876.65 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 134256.10 | 127216.85 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 90281.63 | 85547.21 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 135170.48 | 128083.08 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 78822.44 | 74691.28 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18303.74 | 17342.92 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12143.13 | 11505.63 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18389.96 | 17424.60 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11267.86 | 10676.46 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 25941.30 | 21954.76 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 178424.12 | 155333.12 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 16485.56 | 14502.55 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.96 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 489487.20 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9210.19 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 88002.25 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 8944.59 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14546.91 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6720.07 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.72 | 18847.68 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 80.90 | 174821.14 | 2160.95 | 1.00 | 1.08 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.55 | 18484.33 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.98 | 10898.97 | 2189.01 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.82 | 40932.60 | 1649.25 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 533.35 | 1120.11 | 1.00 | 1.63 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.55 | 5092.89 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 517.56 | 1120.11 | 1.00 | 1.64 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.055157 | 8916.28 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.010839 | 3232.03 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027578 | 3086.52 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027578 | 3086.52 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014587 | 3683.65 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.100227 | 24568.37 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67899.01 | 67899.01 | 24.43 | 4.979 | 4.979 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00902 | 24.71 | 0.00822 | 1.200 | 0.00 |
CORE_BOTTOM | 73807.03 | 73807.03 | 29.57 | 5.413 | 5.413 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 24.71 | 0.00822 | 1.078 | 0.00 |
CORE_MID | 694050.27 | 694050.27 | 278.05 | 50.883 | 50.883 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 24.71 | 0.00822 | 10.778 | 0.00 |
CORE_TOP | 67667.35 | 67667.35 | 27.11 | 4.961 | 4.961 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 24.71 | 0.00822 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11277.15 | 11277.15 | 35.98 | 0.835 | 0.835 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14015.77 | 14015.77 | 69.39 | 1.038 | 1.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00867 | 25.28 | 0.00822 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15934.46 | 15934.46 | 50.84 | 1.180 | 1.180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 24.00 | 24.00 | 0.00874 | 30.74 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17595.84 | 17595.84 | 87.12 | 1.303 | 1.303 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 103055.97 | 103055.97 | 328.82 | 7.629 | 7.629 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00885 | 31.30 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 144089.73 | 144089.73 | 713.40 | 10.667 | 10.667 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 25.84 | 0.00822 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 152622.57 | 152622.57 | 486.96 | 11.299 | 11.299 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00874 | 30.86 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 152452.55 | 152452.55 | 754.81 | 11.286 | 11.286 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00866 | 30.29 | 0.00823 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11646.35 | 11646.35 | 37.16 | 0.862 | 0.862 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00881 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14361.43 | 14361.43 | 71.10 | 1.063 | 1.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 26.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16516.92 | 16516.92 | 52.70 | 1.223 | 1.223 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00872 | 31.00 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16156.45 | 16156.45 | 79.99 | 1.196 | 1.196 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8154.59 | 8154.59 | 225.25 | 0.476 | 0.476 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77866.29 | 77866.29 | 2150.84 | 4.547 | 4.547 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7913.14 | 7913.14 | 218.58 | 0.462 | 0.462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369604.69 | 425045.40 | 542.37 | 21.581 | 24.819 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 23.20 | 0.00822 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.97 | 0.00506 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.88 | 0.00506 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 167893.94 | 167893.94 | 67.26 | 7.150 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 41277.83 | 41277.83 | 16.54 | 1.781 | 1.781 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2887.35 | 2887.35 | 9.21 | 0.124 | 0.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00733 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2151.04 | 2151.04 | 10.65 | 0.094 | 0.094 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00749 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4549.14 | 4549.14 | 14.51 | 0.196 | 0.196 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 695.26 | 695.26 | 3.44 | 0.030 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00688 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 94014.54 | 94014.54 | 299.97 | 4.075 | 4.075 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 63216.99 | 63216.99 | 312.99 | 2.741 | 2.741 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 94653.78 | 94653.78 | 302.00 | 4.103 | 4.103 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 55205.83 | 55205.83 | 273.33 | 2.392 | 2.392 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12811.96 | 12811.96 | 40.88 | 0.556 | 0.556 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8499.45 | 8499.45 | 42.08 | 0.369 | 0.369 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12872.22 | 12872.22 | 41.07 | 0.559 | 0.559 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7887.65 | 7887.65 | 39.05 | 0.342 | 0.342 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.07 | 0.00830 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.15 | 0.00549 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.72 | 8.72 | 1.59 | 1.59 | 8.7220 | 2.2851 | 8.7220 | 0.2620 | 0.3000 |
VAV_MID WITH REHEAT | 80.90 | 80.90 | 24.09 | 24.09 | 80.9003 | 24.0885 | 80.9003 | 0.2978 | 0.3000 |
VAV_TOP WITH REHEAT | 8.55 | 8.55 | 3.61 | 3.61 | 8.5538 | 3.6071 | 8.5538 | 0.4217 | 0.3000 |
CAV_BAS | 4.98 | 4.98 | 1.20 | 1.20 | 4.9789 | 1.2002 | 4.9789 | 0.2410 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.82 | 24.82 | 0.34 | 0.34 | 24.8190 | 24.8187 | 24.8190 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4762 | 0.4762 | 0.4762 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.55 | 4.55 | 0.16 | 0.16 | 4.5468 | 4.5468 | 4.5468 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4621 | 0.4621 | 0.4621 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15991.940 | 15991.940 | 1.618355 | 0.00013990 | 322.385 | 12/21 00:10:00 | 12/21 00:10:00 | 15991.94 | 15991.94 | 1.618355 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 16050.91 | 16050.91 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 327785.365 | 327785.365 | 16.180718 | 0.00286761 | 7377.273 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 327785.36 | 327785.36 | 16.180718 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 167893.94 | 0.00 | 328905.65 | 328905.65 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 58881.192 | 58881.192 | 1.781428 | 0.00051512 | 1556.098 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 58881.19 | 58881.19 | 1.781428 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 41277.83 | 0.00 | 59097.66 | 59097.66 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4889.438 | 4889.438 | 0.202872 | 0.00004277 | 115.098 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4889.44 | 4889.44 | 0.202872 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00732828 | 46.5456 | 2887.35 | 0.00 | 4905.45 | 4905.45 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3441.631 | 3441.631 | 0.130737 | 0.00003011 | 83.256 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3441.63 | 3441.63 | 0.130737 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00749056 | 47.5639 | 2151.04 | 0.00 | 3452.76 | 3452.76 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6552.331 | 6552.331 | 0.202899 | 0.00005732 | 171.353 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6552.33 | 6552.33 | 0.202899 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00755905 | 47.9939 | 4549.14 | 0.00 | 6571.95 | 6571.95 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 1979.785 | 1979.785 | 0.130263 | 0.00001732 | 42.147 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 1979.79 | 1979.79 | 0.130263 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00687978 | 43.7274 | 695.26 | 0.00 | 1986.76 | 1986.76 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 134256.098 | 134256.098 | 4.075002 | 0.00117453 | 3542.831 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 134256.10 | 134256.10 | 4.075002 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770635 | 48.9183 | 94014.54 | 0.00 | 134712.00 | 134712.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 90281.632 | 90281.632 | 2.740578 | 0.00078982 | 2382.283 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 90281.63 | 90281.63 | 2.740578 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00772160 | 49.0138 | 63216.99 | 0.00 | 90587.32 | 90587.32 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 135170.479 | 135170.479 | 4.102833 | 0.00118253 | 3566.929 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 135170.48 | 135170.48 | 4.102833 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00771008 | 48.9417 | 94653.78 | 0.00 | 135629.26 | 135629.26 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 78822.443 | 78822.443 | 2.391850 | 0.00068957 | 2080.255 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 78822.44 | 78822.44 | 2.391850 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00763536 | 48.4735 | 55205.83 | 0.00 | 79091.84 | 79091.84 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18303.741 | 18303.741 | 0.555986 | 0.00016013 | 482.842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18303.74 | 18303.74 | 0.555986 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782200 | 49.6427 | 12811.96 | 0.00 | 18364.69 | 18364.69 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12143.131 | 12143.131 | 0.368880 | 0.00010623 | 320.318 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12143.13 | 12143.13 | 0.368880 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782750 | 49.6771 | 8499.45 | 0.00 | 12183.49 | 12183.49 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18389.959 | 18389.959 | 0.558611 | 0.00016088 | 485.114 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18389.96 | 18389.96 | 0.558611 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782382 | 49.6540 | 12872.22 | 0.00 | 18451.17 | 18451.17 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11267.856 | 11267.856 | 0.342235 | 0.00009858 | 297.252 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11267.86 | 11267.86 | 0.342235 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00778997 | 49.4422 | 7887.65 | 0.00 | 11305.47 | 11305.47 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 161182.764 | -999.000 | 8.721954 | 0.00460981 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 161182.76 | 155238.18 | 8.721954 | 25.78 | 17.00 | 0.00872175 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 23.2803 | 24.00 | 0.00887891 | 46.8825 | 112635.90 | 0.00 | 163656.29 | 151433.25 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 25941.303 | 25941.303 | 2.616586 | 0.00022695 | 447.903 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25941.30 | 25941.30 | 2.616586 | 4.45 | 4.36 | 0.00522387 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 77.6011 | 21.92 | 0.00621836 | 37.3923 | 10279.96 | 0.00 | 26577.63 | 26577.63 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1518524.997 | -999.000 | 80.900255 | 0.04342962 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1518525.00 | 1460565.50 | 80.900255 | 25.99 | 17.08 | 0.00873313 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 25.1000 | 24.00 | 0.00892034 | 47.0982 | 1006338.86 | 0.00 | 1541493.14 | 1425023.52 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 178424.119 | 178424.119 | 24.270076 | 0.00156093 | 3127.221 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 178424.12 | 178424.12 | 24.270076 | 6.61 | 5.84 | 0.00552444 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 83.6668 | 21.00 | 0.00787083 | 49.9474 | 318448.69 | 0.00 | 188049.92 | 188049.92 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 157457.201 | -999.000 | 8.553813 | 0.00450326 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 157457.20 | 151787.22 | 8.553813 | 25.73 | 16.98 | 0.00871566 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 23.7380 | 24.00 | 0.00886574 | 46.8139 | 115542.23 | 0.00 | 159882.20 | 148057.17 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 16485.563 | 16485.563 | 2.566144 | 0.00014422 | 290.566 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16485.56 | 16485.56 | 2.566144 | 7.39 | 6.38 | 0.00565156 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 79.1265 | 20.30 | 0.00787733 | 52.2035 | 37493.78 | 0.00 | 17557.39 | 17557.39 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 91407.465 | -999.000 | 4.978945 | 0.00261424 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 91407.47 | 86312.37 | 4.978945 | 25.38 | 16.96 | 0.00883249 | 10.99 | 10.99 | 0.00850000 | 29.25 | 0.00823024 | 17.77 | 24.1046 | 24.00 | 0.00904663 | 47.7558 | 61802.84 | 0.00 | 92828.59 | 84198.29 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.095922 | 0.92 | 0.92 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 38.7657 | 24.97 | 0.00505843 | 25.3554 | 0.00 | 0.00 | 100077.82 | 100077.82 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 489487.204 | 348915.858 | 24.818965 | 0.01198751 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 454794.56 | 452269.26 | -999.0 | 28.48 | 17.76 | 0.00853829 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | -999.0000 | 27.00 | 0.00854251 | 37.7682 | 369192.89 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9210.187 | 6628.392 | 0.476161 | 0.00022556 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8529.67 | 8432.50 | -999.0 | 28.03 | 17.65 | 0.00857699 | 12.80 | 11.93 | 0.00850000 | 28.94 | 0.00822975 | 17.67 | -999.0000 | 27.00 | 0.00858877 | 37.9676 | 8154.59 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88002.249 | 63311.299 | 4.546789 | 0.00215517 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 81508.48 | 80538.78 | -999.0 | 28.03 | 17.65 | 0.00858045 | 12.80 | 11.93 | 0.00850000 | 28.94 | 0.00822975 | 17.67 | -999.0000 | 27.00 | 0.00859294 | 37.9860 | 77866.29 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8944.590 | 6434.475 | 0.462064 | 0.00021905 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8284.81 | 8187.89 | -999.0 | 28.04 | 17.65 | 0.00857913 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859135 | 37.9790 | 7912.20 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 489487.204 | 489487.204 | 24.818965 | 0.01198751 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 489487.20 | 489487.20 | 24.818965 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.3634 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9210.187 | 9210.187 | 0.476161 | 0.00022556 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9210.19 | 9210.19 | 0.476161 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.2830 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88002.249 | 88002.249 | 4.546789 | 0.00215517 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 88002.25 | 88002.25 | 4.546789 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4381 | 25.07 | 0.00829879 | 41.1266 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8944.590 | 8944.590 | 0.462064 | 0.00021905 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8944.59 | 8944.59 | 0.462064 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3832 | 24.15 | 0.00548527 | 28.8570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.91 | 14546.91 | 24.818965 | 0.05 | 0.05 | 0.00845308 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.3634 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.476161 | 0.12 | 0.12 | 0.00838701 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.2830 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6720.07 | 6720.07 | 4.546789 | 0.13 | 0.13 | 0.00818738 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4381 | 25.07 | 0.00829879 | 41.1266 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.462064 | 0.13 | 0.13 | 0.00547083 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3832 | 24.15 | 0.00548527 | 28.8570 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15991.940 | 15991.940 | 1.618355 | 0.00013990 | 322.385 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 1.2652 | 1.290705 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 15991.94 | 15991.94 | 1.0000 | 1.91253746 | 1.618355 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.13989020 | 60.00 | 32.22 | 27.78 | 0.000 | 15991.94 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 16050.91 | 16050.91 | 1.91253746 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 327785.365 | 327785.365 | 16.180718 | 0.00286761 | 7377.273 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 25.9335 | 26.455468 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 327785.36 | 327785.36 | 1.0000 | 19.12202750 | 16.180718 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 2.86731684 | 60.00 | 32.22 | 27.78 | 0.000 | 327785.36 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 167893.94 | 0.00 | 328905.65 | 328905.65 | 19.12202750 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.67 | 17.93 | 0.00800000 | 50260.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 58881.192 | 58881.192 | 1.781428 | 0.00051512 | 1556.098 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 4.6585 | 4.752285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 58881.19 | 58881.19 | 1.0000 | 2.10525418 | 1.781428 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.51506581 | 60.00 | 32.22 | 27.78 | 0.000 | 58881.19 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 41277.83 | 0.00 | 59097.66 | 59097.66 | 2.10525418 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.33 | 21.28 | 0.00800000 | 61131.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4889.438 | 4889.438 | 0.202872 | 0.00004277 | 115.098 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 0.3868 | 0.394625 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4889.44 | 4889.44 | 1.0000 | 0.23974984 | 0.202872 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04277058 | 60.00 | 32.22 | 27.78 | 0.000 | 4889.44 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.83 | 0.00732828 | 21.00 | 0.00732828 | 46.5456 | 2887.35 | 0.00 | 4905.45 | 4905.45 | 0.23974984 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.87 | 18.98 | 0.00800000 | 53520.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3441.631 | 3441.631 | 0.130737 | 0.00003011 | 83.256 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 0.2723 | 0.277773 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 3441.63 | 3441.63 | 1.0000 | 0.15450208 | 0.130737 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03010582 | 60.00 | 32.22 | 27.78 | 0.000 | 3441.63 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00749056 | 21.00 | 0.00749056 | 47.5639 | 2151.04 | 0.00 | 3452.76 | 3452.76 | 0.15450208 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.72 | 19.57 | 0.00800000 | 55407.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6552.331 | 6552.331 | 0.202899 | 0.00005732 | 171.353 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 0.5184 | 0.528837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6552.33 | 6552.33 | 1.0000 | 0.23978222 | 0.202899 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05731680 | 60.00 | 32.22 | 27.78 | 0.000 | 6552.33 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00755905 | 21.00 | 0.00755905 | 47.9939 | 4549.14 | 0.00 | 6571.95 | 6571.95 | 0.23978222 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.68 | 21.09 | 0.00800000 | 60467.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1979.785 | 1979.785 | 0.130263 | 0.00001732 | 42.147 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 0.1566 | 0.159788 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 1979.79 | 1979.79 | 1.0000 | 0.15394231 | 0.130263 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.01731826 | 60.00 | 32.22 | 27.78 | 0.000 | 1979.79 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.94 | 0.00687978 | 21.00 | 0.00687978 | 43.7274 | 695.26 | 0.00 | 1986.76 | 1986.76 | 0.15394231 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.46 | 16.48 | 0.00800000 | 45965.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 134256.098 | 134256.098 | 4.075002 | 0.00117453 | 3542.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 10.6220 | 10.835773 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 134256.10 | 134256.10 | 1.0000 | 4.81575004 | 4.075002 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.17441110 | 60.00 | 32.22 | 27.78 | 0.000 | 134256.10 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00770635 | 21.00 | 0.00770635 | 48.9183 | 94014.54 | 0.00 | 134712.00 | 134712.00 | 4.81575004 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 90281.632 | 90281.632 | 2.740578 | 0.00078982 | 2382.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 7.1429 | 7.286606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 90281.63 | 90281.63 | 1.0000 | 3.23875708 | 2.740578 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.78974253 | 60.00 | 32.22 | 27.78 | 0.000 | 90281.63 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00772160 | 21.00 | 0.00772160 | 49.0138 | 63216.99 | 0.00 | 90587.32 | 90587.32 | 3.23875708 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61029.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 135170.479 | 135170.479 | 4.102833 | 0.00118253 | 3566.929 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 10.6943 | 10.909573 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 135170.48 | 135170.48 | 1.0000 | 4.84864089 | 4.102833 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.18240969 | 60.00 | 32.22 | 27.78 | 0.000 | 135170.48 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00771008 | 21.00 | 0.00771008 | 48.9417 | 94653.78 | 0.00 | 135629.26 | 135629.26 | 4.84864089 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61032.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 78822.443 | 78822.443 | 2.391850 | 0.00068957 | 2080.255 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 6.2362 | 6.361738 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 78822.44 | 78822.44 | 1.0000 | 2.82663767 | 2.391850 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.68950277 | 60.00 | 32.22 | 27.78 | 0.000 | 78822.44 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00763536 | 21.00 | 0.00763536 | 48.4735 | 55205.83 | 0.00 | 79091.84 | 79091.84 | 2.82663767 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61040.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18303.741 | 18303.741 | 0.555986 | 0.00016013 | 482.842 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 1.4481 | 1.477290 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18303.74 | 18303.74 | 1.0000 | 0.65705191 | 0.555986 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16011278 | 60.00 | 32.22 | 27.78 | 0.000 | 18303.74 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00782200 | 21.00 | 0.00782200 | 49.6427 | 12811.96 | 0.00 | 18364.69 | 18364.69 | 0.65705191 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12143.131 | 12143.131 | 0.368880 | 0.00010623 | 320.318 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 0.9607 | 0.980069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12143.13 | 12143.13 | 1.0000 | 0.43593456 | 0.368880 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10622257 | 60.00 | 32.22 | 27.78 | 0.000 | 12143.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00782750 | 21.00 | 0.00782750 | 49.6771 | 8499.45 | 0.00 | 12183.49 | 12183.49 | 0.43593456 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18389.959 | 18389.959 | 0.558611 | 0.00016088 | 485.114 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 1.4550 | 1.484249 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18389.96 | 18389.96 | 1.0000 | 0.66015462 | 0.558611 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16086697 | 60.00 | 32.22 | 27.78 | 0.000 | 18389.96 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00782382 | 21.00 | 0.00782382 | 49.6540 | 12872.22 | 0.00 | 18451.17 | 18451.17 | 0.66015462 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61009.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11267.856 | 11267.856 | 0.342235 | 0.00009858 | 297.252 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 0.8915 | 0.909426 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11267.86 | 11267.86 | 1.0000 | 0.40444581 | 0.342235 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09856606 | 60.00 | 32.22 | 27.78 | 0.000 | 11267.86 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00778997 | 21.00 | 0.00778997 | 49.4422 | 7887.65 | 0.00 | 11305.47 | 11305.47 | 0.40444581 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61012.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 161182.764 | -999.000 | 8.721954 | 0.00460981 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0533 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.721954 | 10.30741857 | 4197.9300 | 999.8980 | 55.15130071 | 15.00 | 6.67 | 8.33 | 1928572.43 | 8.3576 | 8.357620 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 161182.76 | 155238.18 | 1.0000 | 10.30741857 | 8.721954 | 25.78 | 17.00 | 0.00872175 | 48131.9 | 11.01 | 11.01 | 0.00850000 | 32494.4 | 4.60933639 | 6.67 | 15.00 | 8.33 | 18847.677 | 142335.09 | 31.30 | 0.00823349 | 18.45 | 2.03050000 | 23.2803 | 24.00 | 0.00887891 | 24.00 | 0.00887891 | 46.8825 | 112635.90 | 0.00 | 163656.29 | 151433.25 | 10.30741857 | 25.78 | 17.20 | 0.00872175 | 48131.9 | 11.39 | 11.26 | 0.00825157 | 32254.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25941.303 | 25941.303 | 2.616586 | 0.00022695 | 447.903 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.721954 | 10.30741857 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 2.0524 | 2.093716 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25941.30 | 25941.30 | 1.0000 | 3.09222557 | 2.616586 | 4.45 | 4.36 | 0.00522387 | 17580.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.22692268 | 60.00 | 32.22 | 27.78 | 0.000 | 25941.30 | 3.80 | 0.00505843 | 3.80 | 2.03050000 | 77.6011 | 6.71 | 0.00579701 | 21.92 | 0.00621836 | 37.3923 | 10279.96 | 0.00 | 26577.63 | 26577.63 | 3.09222557 | 2.80 | 2.80 | 0.00522387 | 15905.3 | 11.27 | 7.89 | 0.00522387 | 24500.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1518524.997 | -999.000 | 80.900255 | 0.04342962 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0745 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.900255 | 95.60619475 | 4197.9300 | 999.8980 | 55.15130071 | 15.00 | 6.67 | 8.33 | 1928572.43 | 78.7383 | 78.738292 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1518525.00 | 1460565.50 | 1.0000 | 95.60619475 | 80.900255 | 25.99 | 17.08 | 0.00873313 | 48377.5 | 11.01 | 11.01 | 0.00850000 | 32494.4 | 43.42519243 | 6.67 | 15.00 | 8.33 | 174821.142 | 1343703.86 | 31.30 | 0.00823349 | 18.45 | 20.30600000 | 25.1000 | 24.00 | 0.00892034 | 24.00 | 0.00892034 | 47.0982 | 1006338.86 | 0.00 | 1541493.14 | 1425023.52 | 95.60619475 | 25.99 | 17.28 | 0.00873313 | 48377.5 | 11.39 | 11.26 | 0.00825012 | 32254.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 178424.119 | 178424.119 | 24.270076 | 0.00156093 | 3127.221 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.900255 | 95.60619475 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 14.1165 | 14.400562 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 178424.12 | 178424.12 | 1.0000 | 28.68185842 | 24.270076 | 6.61 | 5.84 | 0.00552444 | 20525.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 1.56077280 | 60.00 | 32.22 | 27.78 | 0.000 | 178424.12 | 3.80 | 0.00505843 | 3.80 | 20.30600000 | 83.6668 | 21.00 | 0.00791156 | 21.00 | 0.00787083 | 49.9474 | 318448.69 | 0.00 | 188049.92 | 188049.92 | 28.68185842 | 2.80 | 2.80 | 0.00552444 | 16658.6 | 9.26 | 7.28 | 0.00552444 | 23215.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 157457.201 | -999.000 | 8.553813 | 0.00450326 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0420 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.553813 | 10.10871331 | 4197.9300 | 999.8980 | 55.15130071 | 15.00 | 6.67 | 8.33 | 1928572.43 | 8.1644 | 8.164443 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 157457.20 | 151787.22 | 1.0000 | 10.10871331 | 8.553813 | 25.73 | 16.98 | 0.00871566 | 48070.7 | 11.01 | 11.01 | 0.00850000 | 32494.4 | 4.50279663 | 6.67 | 15.00 | 8.33 | 18484.334 | 138972.87 | 31.30 | 0.00823349 | 18.45 | 2.03050000 | 23.7380 | 24.00 | 0.00886574 | 24.00 | 0.00886574 | 46.8139 | 115542.23 | 0.00 | 159882.20 | 148057.17 | 10.10871331 | 25.73 | 17.18 | 0.00871566 | 48070.7 | 11.39 | 11.26 | 0.00825184 | 32254.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16485.563 | 16485.563 | 2.566144 | 0.00014422 | 290.566 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.553813 | 10.10871331 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 1.3043 | 1.330545 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16485.56 | 16485.56 | 1.0000 | 3.03261399 | 2.566144 | 7.39 | 6.38 | 0.00565156 | 21637.8 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.14420818 | 60.00 | 32.22 | 27.78 | 0.000 | 16485.56 | 3.80 | 0.00505843 | 3.80 | 2.03050000 | 79.1265 | 21.00 | 0.00789999 | 20.30 | 0.00787733 | 52.2035 | 37493.78 | 0.00 | 17557.39 | 17557.39 | 3.03261399 | 2.80 | 2.80 | 0.00565156 | 16977.2 | 8.50 | 7.06 | 0.00565156 | 22766.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91407.465 | -999.000 | 4.978945 | 0.00261424 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2592 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:VariableVolume | 4.978945 | 5.88401144 | 4197.9300 | 999.8980 | 55.15130071 | 15.00 | 6.67 | 8.33 | 1928572.43 | 4.7396 | 4.739644 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 91407.47 | 86312.37 | 1.0000 | 5.88401144 | 4.978945 | 25.38 | 16.96 | 0.00883249 | 48005.9 | 10.99 | 10.99 | 0.00850000 | 32471.0 | 2.61397525 | 6.67 | 15.00 | 8.33 | 10898.966 | 80508.50 | 29.25 | 0.00823024 | 17.77 | 1.20015641 | 24.1046 | 24.00 | 0.00904663 | 24.00 | 0.00904663 | 47.7558 | 61802.84 | 0.00 | 92828.59 | 84198.29 | 5.88401144 | 25.38 | 17.15 | 0.00883249 | 48005.9 | 11.37 | 11.25 | 0.00825093 | 32229.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:VariableVolume | 4.978945 | 5.88401144 | 4197.9300 | 999.8980 | 10.83827682 | 54.44 | 82.22 | 27.78 | 1263943.54 | 7.9117 | 8.070973 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.095922 | 0.92 | 0.92 | 0.00505843 | 13579.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | 3.80 | 0.00505843 | 3.80 | 1.20015641 | 38.7657 | 0.00 | 0.00505843 | 24.97 | 0.00505843 | 25.3554 | 0.00 | 0.00 | 100077.82 | 100077.82 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 489487.204 | 348915.858 | 24.818965 | 0.01198751 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7123 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 454794.56 | 452269.26 | 0.9291 | -999.0 | -999.0 | 28.48 | 17.76 | 0.00853829 | 50419.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 454794.56 | 31.30 | 0.00823349 | 18.45 | 0.33839277 | -999.0000 | 27.00 | 0.00854251 | 27.00 | 0.00854251 | 37.7682 | 369192.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9210.187 | 6628.392 | 0.476161 | 0.00022556 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7842 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8529.67 | 8432.50 | 0.9261 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00857699 | 50059.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8529.67 | 28.94 | 0.00822975 | 17.67 | 0.01563234 | -999.0000 | 27.00 | 0.00858877 | 27.00 | 0.00858877 | 37.9676 | 8154.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 88002.249 | 63311.299 | 4.546789 | 0.00215517 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7906 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 81508.48 | 80538.78 | 0.9262 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00858045 | 50071.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81508.48 | 28.94 | 0.00822975 | 17.67 | 0.15632344 | -999.0000 | 27.00 | 0.00859294 | 27.00 | 0.00859294 | 37.9860 | 77866.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8944.590 | 6434.475 | 0.462064 | 0.00021905 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7882 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8284.81 | 8187.89 | 0.9262 | -999.0 | -999.0 | 28.04 | 17.65 | 0.00857913 | 50074.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8284.81 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | -999.0000 | 27.00 | 0.00859135 | 27.00 | 0.00859135 | 37.9790 | 7912.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 489487.204 | 489487.204 | 24.818965 | 0.01198751 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 489487.20 | 489487.20 | 1.0000 | 29.33052309 | 24.818965 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 489487.20 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.3634 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9210.187 | 9210.187 | 0.476161 | 0.00022556 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9210.19 | 9210.19 | 1.0000 | 0.56271701 | 0.476161 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9210.19 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.2830 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88002.249 | 88002.249 | 4.546789 | 0.00215517 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 88002.25 | 88002.25 | 1.0000 | 5.37329798 | 4.546789 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88002.25 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.4381 | 0.00 | 0.00829879 | 25.07 | 0.00829879 | 41.1266 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8944.590 | 8944.590 | 0.462064 | 0.00021905 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8944.59 | 8944.59 | 1.0000 | 0.54605790 | 0.462064 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8944.59 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3832 | 0.00 | 0.00548527 | 24.15 | 0.00548527 | 28.8570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.818965 | 29.33052309 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14546.91 | 14546.91 | 1.0000 | 29.33052309 | 24.818965 | 0.05 | 0.05 | 0.00845308 | 21193.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14546.91 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.3634 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.476161 | 0.56271701 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.56271701 | 0.476161 | 0.12 | 0.12 | 0.00838701 | 21102.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.2830 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.546789 | 5.37329798 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6720.07 | 6720.07 | 1.0000 | 5.37329798 | 4.546789 | 0.13 | 0.13 | 0.00818738 | 20609.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6720.07 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.4381 | 0.00 | 0.00829879 | 25.07 | 0.00829879 | 41.1266 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.462064 | 0.54605790 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.54605790 | 0.462064 | 0.13 | 0.13 | 0.00547083 | 13812.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3832 | 0.00 | 0.00548527 | 24.15 | 0.00548527 | 28.8570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.72 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 80.90 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.55 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 4.98 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.82 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4561.83 | 457.83 | 372.17 |
CORE_BOTTOM | 4402.17 | 99.00 | 0.50 |
CORE_MID | 3314.33 | 755.67 | 13.67 |
CORE_TOP | 2526.33 | 2162.33 | 20.67 |
PERIMETER_BOT_ZN_3 | 2889.67 | 1508.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 3337.50 | 1305.00 | 109.00 |
PERIMETER_BOT_ZN_1 | 3915.00 | 1000.17 | 180.83 |
PERIMETER_BOT_ZN_4 | 4790.00 | 512.67 | 349.17 |
PERIMETER_MID_ZN_3 | 1837.00 | 3080.67 | 11.33 |
PERIMETER_MID_ZN_2 | 2265.83 | 1931.17 | 115.83 |
PERIMETER_MID_ZN_1 | 3332.50 | 1651.83 | 171.50 |
PERIMETER_MID_ZN_4 | 3160.33 | 1898.83 | 151.17 |
PERIMETER_TOP_ZN_3 | 1867.67 | 3599.00 | 273.67 |
PERIMETER_TOP_ZN_2 | 2535.00 | 2669.83 | 208.00 |
PERIMETER_TOP_ZN_1 | 2950.17 | 2246.33 | 197.17 |
PERIMETER_TOP_ZN_4 | 2900.83 | 2443.67 | 244.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 995.17 | 995.17 |
DATACENTER_MID_ZN_6 | 5943.00 | 39.00 | 39.00 |
DATACENTER_TOP_ZN_6 | 5922.33 | 156.67 | 155.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5899.83 | 5899.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5914.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 931.33 | 0.00 | 516.83 |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.50 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 26.83 | 0.00 | 26.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 78.33 | 0.00 | 78.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 114.83 | 0.00 | 74.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 24.67 | 0.00 | 24.67 |
PERIMETER_MID_ZN_1 | 0.00 | 108.33 | 0.00 | 108.17 |
PERIMETER_MID_ZN_4 | 0.00 | 41.50 | 0.00 | 31.50 |
PERIMETER_TOP_ZN_3 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.67 | 22.17 | 0.00 | 22.17 |
PERIMETER_TOP_ZN_1 | 0.17 | 51.50 | 0.00 | 51.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 40.83 | 0.00 | 31.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 2.83 | 0.00 | 2.83 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 54.83 | 0.00 | 54.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.17 | 1285.17 | 0.00 | 839.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 1.502 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 1.327 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.947 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.920 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 1.179 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 1.627 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 1.854 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 2.710 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.847 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 1.285 | 0.034 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 1.504 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 1.563 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.865 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 1.377 | 0.040 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 1.573 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 1.605 | 0.040 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 37.394 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.32 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.96 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.57 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1032.96 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 59065936.13 | 0.00 | 59065936.13 | 0.00 | 59065936.13 | 37848132.68 | 4525.37 | 275.32 | 3959.30 | 0.00 |
CORE_BOTTOM | 55708987.42 | 0.00 | 55708987.42 | 0.00 | 55708987.42 | 33990283.35 | 3397.03 | 7.25 | 5355.71 | 500.36 |
CORE_MID | 0.38E+09 | 0.00 | 0.38E+09 | 0.00 | 0.38E+09 | 0.34E+09 | 3929.37 | 128.30 | 4702.33 | 121.81 |
CORE_TOP | 36895718.97 | 0.00 | 36895718.97 | 0.00 | 36895718.97 | 33990283.35 | 4035.22 | 205.02 | 4519.77 | 73.22 |
PERIMETER_BOT_ZN_3 | 6215570.45 | 0.00 | 6215570.45 | 116163.57 | 6331734.02 | 4267819.30 | 3470.96 | 38.07 | 5250.96 | 500.36 |
PERIMETER_BOT_ZN_2 | 5449936.57 | 0.00 | 5449936.57 | 77442.33 | 5527378.90 | 2750345.05 | 3399.76 | 29.74 | 5330.51 | 500.36 |
PERIMETER_BOT_ZN_1 | 9595095.83 | 0.00 | 9595095.83 | 116163.57 | 9711259.41 | 4267912.63 | 3395.63 | 26.90 | 5337.47 | 500.36 |
PERIMETER_BOT_ZN_4 | 9034904.14 | 0.00 | 9034904.14 | 77442.33 | 9112346.47 | 2750345.05 | 3284.36 | 8.63 | 5467.00 | 500.36 |
PERIMETER_MID_ZN_3 | 43147681.48 | 0.00 | 43147681.48 | 272433.03 | 43420114.51 | 42678193.03 | 4222.81 | 144.16 | 4393.03 | 121.81 |
PERIMETER_MID_ZN_2 | 42812477.86 | 0.00 | 42812477.86 | 181621.90 | 42994099.76 | 27503450.52 | 4156.18 | 98.42 | 4505.39 | 958.28 |
PERIMETER_MID_ZN_1 | 75942292.38 | 0.00 | 75942292.38 | 272433.03 | 76214725.41 | 42679126.28 | 3765.79 | 107.77 | 4886.44 | 121.81 |
PERIMETER_MID_ZN_4 | 50937547.08 | 0.00 | 50937547.08 | 181621.90 | 51119168.98 | 27503450.52 | 3880.64 | 130.62 | 4748.75 | 121.81 |
PERIMETER_TOP_ZN_3 | 4367800.59 | 0.00 | 4367800.59 | 338250.81 | 4706051.40 | 4267819.30 | 3969.34 | 242.99 | 4547.67 | 73.22 |
PERIMETER_TOP_ZN_2 | 4454259.08 | 0.00 | 4454259.08 | 225500.39 | 4679759.47 | 2750345.05 | 3900.25 | 208.87 | 4650.88 | 73.22 |
PERIMETER_TOP_ZN_1 | 7898480.76 | 0.00 | 7898480.76 | 338250.81 | 8236731.57 | 4267912.63 | 3889.92 | 201.96 | 4668.12 | 73.22 |
PERIMETER_TOP_ZN_4 | 5204396.30 | 0.00 | 5204396.30 | 225500.39 | 5429896.68 | 2750345.05 | 3907.30 | 254.57 | 4598.13 | 73.22 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.58E+09 | 0.00 | 0.58E+09 | 0.00 | 0.58E+09 | 10671554.30 | 9.57 | 60.33 | 8690.10 | 2817.00 |
Total Facility | 0.68E+10 | 0.00 | 0.68E+10 | 10595812.78 | 0.68E+10 | 0.50E+10 | 5320.91 | 4363.67 | 8749.73 | 3653.47 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.7608 | 0.0000 | 2.7608 | 0.0000 | 2.7608 | 1.2002 | 1708.37 | 275.32 | 3959.30 |
CORE_BOTTOM | 2.4632 | 0.0000 | 2.4632 | 0.0000 | 2.4632 | 1.0778 | 1051.07 | 4.43 | 4887.50 |
CORE_MID | 17.5754 | 0.0000 | 17.5754 | 0.0000 | 17.5754 | 10.7782 | 1233.27 | 128.30 | 4581.43 |
CORE_TOP | 1.7076 | 0.0000 | 1.7076 | 0.0000 | 1.7076 | 1.0778 | 1273.13 | 205.02 | 4464.85 |
PERIMETER_BOT_ZN_3 | 0.2747 | 0.0000 | 0.2747 | 0.0031 | 0.2778 | 0.1353 | 1118.16 | 33.70 | 4791.14 |
PERIMETER_BOT_ZN_2 | 0.2445 | 0.0000 | 0.2445 | 0.0021 | 0.2466 | 0.0872 | 1046.95 | 25.37 | 4870.68 |
PERIMETER_BOT_ZN_1 | 0.4326 | 0.0000 | 0.4326 | 0.0031 | 0.4357 | 0.1353 | 1042.83 | 22.56 | 4877.61 |
PERIMETER_BOT_ZN_4 | 0.4069 | 0.0000 | 0.4069 | 0.0021 | 0.4090 | 0.0872 | 934.98 | 5.27 | 5002.75 |
PERIMETER_MID_ZN_3 | 1.9766 | 0.0000 | 1.9766 | 0.0073 | 1.9839 | 1.3533 | 1526.61 | 144.16 | 4272.22 |
PERIMETER_MID_ZN_2 | 1.9305 | 0.0000 | 1.9305 | 0.0051 | 1.9355 | 0.8721 | 1184.99 | 94.09 | 3754.92 |
PERIMETER_MID_ZN_1 | 3.5090 | 0.0000 | 3.5090 | 0.0073 | 3.5163 | 1.3533 | 1069.60 | 107.77 | 4765.63 |
PERIMETER_MID_ZN_4 | 2.3458 | 0.0000 | 2.3458 | 0.0049 | 2.3507 | 0.8721 | 1184.44 | 130.62 | 4627.94 |
PERIMETER_TOP_ZN_3 | 0.2020 | 0.0000 | 0.2020 | 0.0091 | 0.2111 | 0.1353 | 1207.98 | 242.96 | 4492.07 |
PERIMETER_TOP_ZN_2 | 0.2068 | 0.0000 | 0.2068 | 0.0061 | 0.2129 | 0.0872 | 1139.02 | 208.74 | 4595.24 |
PERIMETER_TOP_ZN_1 | 0.3670 | 0.0000 | 0.3670 | 0.0091 | 0.3761 | 0.1353 | 1128.15 | 201.91 | 4612.94 |
PERIMETER_TOP_ZN_4 | 0.2409 | 0.0000 | 0.2409 | 0.0061 | 0.2470 | 0.0872 | 1145.36 | 254.57 | 4543.06 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 19.1952 | 0.0000 | 19.1952 | 0.0000 | 19.1952 | 0.3384 | 9.57 | 60.33 | 5873.10 |
Total Facility | 303.0391 | 0.0000 | 303.0391 | 0.2868 | 303.3259 | 158.4706 | 2503.91 | 4357.99 | 5932.73 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.12E+09 | 0.00 | 0.12E+09 | 48026705.38 | 3180.17 | 0.60 | 5579.23 | 500.36 |
VAV_MID WITH REHEAT | 0.83E+09 | 0.00 | 0.83E+09 | 0.48E+09 | 3679.89 | 1.71 | 5078.41 | 121.81 |
VAV_TOP WITH REHEAT | 82148975.43 | 0.00 | 82148975.43 | 48026705.38 | 3825.95 | 1.64 | 4932.41 | 73.22 |
CAV_BAS | 82491543.76 | 0.00 | 82491543.76 | 37848132.68 | 4524.64 | 0.19 | 4235.17 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.81E+09 | 0.00 | 0.81E+09 | 10671554.30 | 9.57 | 0.00 | 8750.43 | 2817.00 |
AIRLOOP DATACENTER BOT | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3411840.17 | 0.00 | 3411840.17 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 5.3378 | 0.0000 | 5.3378 | 1.5229 | 862.58 | 0.25 | 5080.17 |
VAV_MID WITH REHEAT | 38.2414 | 0.0000 | 38.2414 | 15.2292 | 984.69 | 1.71 | 4956.60 |
VAV_TOP WITH REHEAT | 3.8049 | 0.0000 | 3.8049 | 1.5229 | 1065.80 | 1.44 | 4875.76 |
CAV_BAS | 3.8557 | 0.0000 | 3.8557 | 1.2002 | 1707.64 | 0.19 | 4235.17 |
AIRLOOP DATACENTER BASEMENT | 26.8080 | 0.0000 | 26.8080 | 0.3384 | 9.57 | 0.00 | 5933.43 |
AIRLOOP DATACENTER BOT | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1595 | 0.0000 | 0.1595 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 30.44 | 5345.41 | 0.00 | 0.00 | 0.00 | 205.35 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 478.96 | 4327.51 | 0.00 | 0.00 | 0.00 | 278.95 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 49.46 | 4557.69 | 0.00 | 0.00 | 0.00 | 388.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 275.30 | 3959.33 | 0.00 | 3.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 60.33 | 8690.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.8873 | 6.4302 | 0.0000 | 0.0000 | 0.0000 | 2.3482 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.4723 | 49.2738 | 0.0000 | 0.0000 | 0.0000 | 23.2473 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8537 | 4.8194 | 0.0000 | 0.0000 | 0.0000 | 2.2285 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6779 | 5.6703 | 0.0000 | 1.3296 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4752 | 27.1227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1185 |
Fields with Defaults | 3880 |
Autosized Fields | 335 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
Electricity:Building | 17138.39 | 216479.19 | 14-MAY-17:20 | 1025582.59 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17138.39 | 216479.19 | 14-MAY-17:20 | 1025582.59 | 01-DEC-16:40 |
InteriorLights:Electricity | 2461.99 | 9223.03 | 30-APR-17:20 | 247210.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2461.99 | 9223.03 | 30-APR-17:20 | 247210.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 2461.99 | 9223.03 | 30-APR-17:20 | 247210.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2461.99 | 9223.03 | 30-APR-17:20 | 247210.90 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.06 | 603.11 | 16-APR-17:10 | 3823.11 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.70 | 43.94 | 01-JAN-08:40 | 1662.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.70 | 43.94 | 01-JAN-08:40 | 1662.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.30 | 388.67 | 16-APR-17:10 | 2463.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.86 | 28.32 | 01-JAN-07:20 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.86 | 28.32 | 01-JAN-07:20 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.94 | 603.12 | 16-APR-17:10 | 3823.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.57 | 43.94 | 01-JAN-07:20 | 1662.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.57 | 43.94 | 01-JAN-07:20 | 1662.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.27 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.83 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.83 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 470.45 | 6031.15 | 16-APR-17:10 | 38231.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.79 | 439.44 | 01-JAN-08:40 | 16625.62 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.79 | 439.44 | 01-JAN-08:40 | 16625.62 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.92 | 3886.70 | 16-APR-17:10 | 24637.60 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.57 | 283.19 | 01-JAN-07:20 | 10714.18 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.57 | 283.19 | 01-JAN-07:20 | 10714.18 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 469.29 | 6031.24 | 16-APR-17:10 | 38231.83 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.63 | 439.45 | 01-JAN-07:20 | 16625.99 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 105.63 | 439.45 | 01-JAN-07:20 | 16625.99 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 302.58 | 3886.68 | 12-MAR-17:10 | 24637.51 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.23 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.23 | 283.19 | 01-JAN-08:40 | 10714.18 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.04 | 603.11 | 16-APR-17:10 | 3823.11 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.68 | 43.94 | 01-JAN-08:40 | 1662.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.68 | 43.94 | 01-JAN-08:40 | 1662.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.29 | 388.67 | 16-APR-17:10 | 2463.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.86 | 28.32 | 01-JAN-07:20 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.86 | 28.32 | 01-JAN-07:20 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.93 | 603.12 | 16-APR-17:10 | 3823.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.56 | 43.94 | 01-JAN-07:20 | 1662.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.56 | 43.94 | 01-JAN-07:20 | 1662.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.26 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.82 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.82 | 28.32 | 01-JAN-08:40 | 1071.42 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2200.09 | 4018.72 | 08-JAN-06:00 | 412714.77 | 07-AUG-10:30 |
HeatRejection:Electricity | 661.18 | 257.01 | 03-JAN-07:10 | 72551.47 | 13-JAN-14:40 |
General:HeatRejection:Electricity | 661.18 | 257.01 | 03-JAN-07:10 | 72551.47 | 13-JAN-14:40 |
Electricity:HVAC | 3838.72 | 51929.72 | 01-JAN-06:00 | 367021.58 | 17-OCT-08:20 |
ExteriorEquipment:Electricity | 2566.27 | 20217.42 | 01-JAN-00:10 | 233385.64 | 24-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
ElectricityPurchased:Plant | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
Cogeneration:ElectricityPurchased | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
General:Cogeneration:ElectricityPurchased | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
ElectricityNet:Plant | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
Cogeneration:ElectricityNet | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
General:Cogeneration:ElectricityNet | 26036.15 | 294577.50 | 28-MAY-05:00 | 1958493.27 | 07-AUG-10:30 |
Fans:Electricity | 2384.05 | 47076.41 | 26-APR-21:10 | 190806.28 | 16-OCT-08:20 |
General:Fans:Electricity | 2384.05 | 47076.41 | 26-APR-21:10 | 190806.28 | 16-OCT-08:20 |
ExteriorLights:Electricity | 347.35 | 0.00 | 01-JAN-07:00 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 347.35 | 0.00 | 01-JAN-07:00 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1670.61 | 3309.33 | 03-JAN-07:10 | 420641.88 | 07-AUG-10:30 |
General:Cooling:Electricity | 1670.61 | 3309.33 | 03-JAN-07:10 | 420641.88 | 07-AUG-10:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 480.46 | 0.00 | 01-JAN-00:30 | 100000.00 | 08-JAN-11:30 |
General:Humidifier:Electricity | 480.46 | 0.00 | 01-JAN-00:30 | 100000.00 | 08-JAN-11:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 392.80 | 0.00 | 01-JAN-00:10 | 45273.59 | 02-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 392.80 | 0.00 | 01-JAN-00:10 | 45273.59 | 02-FEB-12:40 |
Pumps:Electricity | 395.04 | 3683.65 | 01-JAN-00:10 | 43335.47 | 16-OCT-14:40 |
General:Pumps:Electricity | 395.04 | 3683.65 | 01-JAN-00:10 | 43335.47 | 16-OCT-14:40 |
WIRED_LTG_ELECTRICITY | 69.18 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 45.43 | 0.00 | 01-JAN-00:10 | 322456.12 | 03-JAN-07:10 |
NaturalGas:Plant | 45.43 | 0.00 | 01-JAN-00:10 | 322456.12 | 03-JAN-07:10 |
Heating:NaturalGas | 45.43 | 0.00 | 01-JAN-00:10 | 322456.12 | 03-JAN-07:10 |
Boiler:Heating:NaturalGas | 45.43 | 0.00 | 01-JAN-00:10 | 322456.12 | 03-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10352.21 | 12578.16 | 03-JAN-07:10 | 2420502.24 | 07-AUG-10:30 |
PlantLoopCoolingDemand:HVAC | 10352.21 | 12578.16 | 03-JAN-07:10 | 2420502.24 | 07-AUG-10:30 |
CoolingCoils:PlantLoopCoolingDemand | 10352.21 | 12578.16 | 03-JAN-07:10 | 2420502.24 | 07-AUG-10:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6532.94 | 0.00 | 01-JAN-00:30 | 0.00 | 16-OCT-11:10 |
Water:HVAC | 178.73 | 0.00 | 01-JAN-00:30 | 0.00 | 01-APR-16:10 |
Humidifier:Water | 178.73 | 0.00 | 01-JAN-00:30 | 0.00 | 01-APR-16:10 |
General:Humidifier:Water | 178.73 | 0.00 | 01-JAN-00:30 | 0.00 | 01-APR-16:10 |
MainsWater:Facility | 6532.94 | 0.00 | 01-JAN-00:30 | 0.00 | 16-OCT-11:10 |
MainsWater:HVAC | 178.73 | 0.00 | 01-JAN-00:30 | 0.00 | 01-APR-16:10 |
Humidifier:MainsWater | 178.73 | 0.00 | 01-JAN-00:30 | 0.00 | 01-APR-16:10 |
General:Humidifier:MainsWater | 178.73 | 0.00 | 01-JAN-00:30 | 0.00 | 01-APR-16:10 |
Water:Plant | 6354.21 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 6354.21 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4074.04 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:Water | 4074.04 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 4074.04 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:MainsWater | 4074.04 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 46676.91 | 108272.88 | 01-JAN-06:00 | 8960689.43 | 07-AUG-10:30 |
EnergyTransfer:Building | 18510.40 | 94968.94 | 08-JAN-07:40 | 1409833.57 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 607.04 | 0.00 | 01-JAN-00:10 | 99444.57 | 02-JAN-07:10 |
Heating:EnergyTransfer | 19.21 | 0.00 | 02-JAN-22:10 | 105181.24 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 19.21 | 0.00 | 02-JAN-22:10 | 105181.24 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 18491.19 | 94443.98 | 08-JAN-07:40 | 1409833.57 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 607.04 | 0.00 | 01-JAN-00:10 | 99444.57 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 18491.19 | 94443.98 | 08-JAN-07:40 | 1409833.57 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 607.04 | 0.00 | 01-JAN-00:10 | 99444.57 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 633.24 | 0.00 | 01-JAN-00:10 | 56110.51 | 02-OCT-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 633.24 | 0.00 | 01-JAN-00:10 | 56110.51 | 02-OCT-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 633.24 | 0.00 | 01-JAN-00:10 | 56110.51 | 02-OCT-07:20 |
EnergyTransfer:Zone:CORE_MID | 4533.92 | 0.00 | 01-JAN-00:10 | 401662.42 | 02-OCT-09:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4533.92 | 0.00 | 01-JAN-00:10 | 401662.42 | 02-OCT-09:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4533.92 | 0.00 | 01-JAN-00:10 | 401662.42 | 02-OCT-09:50 |
EnergyTransfer:Zone:CORE_TOP | 400.10 | 0.00 | 01-JAN-00:10 | 46265.50 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.07 | 0.00 | 01-JAN-00:10 | 20744.31 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.07 | 0.00 | 01-JAN-00:10 | 20744.31 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 400.03 | 0.00 | 01-JAN-00:10 | 46265.50 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 400.03 | 0.00 | 01-JAN-00:10 | 46265.50 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.46 | 0.00 | 01-JAN-00:10 | 9005.08 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.46 | 0.00 | 01-JAN-00:10 | 9005.08 | 16-OCT-11:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.46 | 0.00 | 01-JAN-00:10 | 9005.08 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.14 | 0.00 | 01-JAN-00:10 | 11277.64 | 16-OCT-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.14 | 0.00 | 01-JAN-00:10 | 11277.64 | 16-OCT-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.14 | 0.00 | 01-JAN-00:10 | 11277.64 | 16-OCT-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.33 | 0.00 | 01-JAN-00:10 | 17974.26 | 30-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.33 | 0.00 | 01-JAN-00:10 | 17974.26 | 30-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.33 | 0.00 | 01-JAN-00:10 | 17974.26 | 30-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.03 | 0.00 | 01-JAN-00:10 | 14809.92 | 26-APR-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.03 | 0.00 | 01-JAN-00:10 | 14809.92 | 26-APR-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 103.03 | 0.00 | 01-JAN-00:10 | 14809.92 | 26-APR-15:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 478.98 | 0.00 | 01-JAN-00:10 | 73372.03 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.27 | 0.00 | 01-JAN-00:10 | 35708.61 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.27 | 0.00 | 01-JAN-00:10 | 35708.61 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 478.71 | 0.00 | 01-JAN-00:10 | 73372.03 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 478.71 | 0.00 | 01-JAN-00:10 | 73372.03 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 494.87 | 0.00 | 01-JAN-00:10 | 108410.87 | 14-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 21570.25 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 21570.25 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 494.77 | 0.00 | 01-JAN-00:10 | 108410.87 | 14-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 494.77 | 0.00 | 01-JAN-00:10 | 108410.87 | 14-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 962.95 | 0.00 | 01-JAN-00:10 | 172909.16 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 19139.87 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 19139.87 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 962.92 | 0.00 | 01-JAN-00:10 | 172909.16 | 31-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 962.92 | 0.00 | 01-JAN-00:10 | 172909.16 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 598.72 | 0.00 | 01-JAN-00:10 | 123248.17 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1925.27 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1925.27 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 598.72 | 0.00 | 01-JAN-00:10 | 123248.17 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 598.72 | 0.00 | 01-JAN-00:10 | 123248.17 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.01 | 0.00 | 01-JAN-00:10 | 9337.55 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.28 | 0.00 | 01-JAN-00:10 | 9337.55 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.28 | 0.00 | 01-JAN-00:10 | 9337.55 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.73 | 0.00 | 01-JAN-00:10 | 8080.65 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.73 | 0.00 | 01-JAN-00:10 | 8080.65 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 48.43 | 0.00 | 01-JAN-00:10 | 10704.48 | 14-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.45 | 0.00 | 01-JAN-00:10 | 5688.46 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.45 | 0.00 | 01-JAN-00:10 | 5688.46 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.99 | 0.00 | 01-JAN-00:10 | 10704.48 | 14-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.99 | 0.00 | 01-JAN-00:10 | 10704.48 | 14-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.94 | 0.00 | 01-JAN-00:10 | 18240.87 | 16-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.35 | 0.00 | 01-JAN-00:10 | 6737.03 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.35 | 0.00 | 01-JAN-00:10 | 6737.03 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.59 | 0.00 | 01-JAN-00:10 | 18240.87 | 16-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.59 | 0.00 | 01-JAN-00:10 | 18240.87 | 16-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.81 | 0.00 | 01-JAN-00:10 | 12870.59 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.22 | 0.00 | 01-JAN-00:10 | 4077.70 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.22 | 0.00 | 01-JAN-00:10 | 4077.70 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.58 | 0.00 | 01-JAN-00:10 | 12870.59 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.58 | 0.00 | 01-JAN-00:10 | 12870.59 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.25 | 0.00 | 01-JAN-00:10 | 9831.62 | 02-OCT-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.13 | 0.00 | 01-JAN-00:10 | 3174.71 | 26-FEB-13:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.13 | 0.00 | 01-JAN-00:10 | 3174.71 | 26-FEB-13:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 67.12 | 0.00 | 01-JAN-00:10 | 9831.62 | 02-OCT-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 67.12 | 0.00 | 01-JAN-00:10 | 9831.62 | 02-OCT-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 381.17 | 0.00 | 01-JAN-00:10 | 62805.81 | 16-OCT-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.58 | 0.00 | 01-JAN-00:10 | 24680.60 | 14-MAY-14:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.58 | 0.00 | 01-JAN-00:10 | 24680.60 | 14-MAY-14:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 374.60 | 0.00 | 01-JAN-00:10 | 62805.81 | 16-OCT-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 374.60 | 0.00 | 01-JAN-00:10 | 62805.81 | 16-OCT-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.95 | 0.00 | 01-JAN-00:10 | 17762.05 | 16-OCT-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.64 | 0.00 | 01-JAN-00:10 | 7801.81 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.64 | 0.00 | 01-JAN-00:10 | 7801.81 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.32 | 0.00 | 01-JAN-00:10 | 17762.05 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 57.32 | 0.00 | 01-JAN-00:10 | 17762.05 | 16-OCT-14:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.10 | 1182.35 | 10-JAN-07:00 | 8047.70 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.10 | 1182.35 | 10-JAN-07:00 | 8047.70 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.10 | 1182.35 | 10-JAN-07:00 | 8047.70 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1284.96 | 4763.09 | 01-JAN-07:00 | 74966.61 | 06-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1284.96 | 4763.09 | 01-JAN-07:00 | 74966.61 | 06-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1284.96 | 4763.09 | 01-JAN-07:00 | 74966.61 | 06-AUG-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.66 | 5.08 | 08-JAN-00:40 | 7642.59 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.10 | 0.00 | 02-JAN-10:00 | 531.27 | 01-JAN-01:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.10 | 0.00 | 02-JAN-10:00 | 531.27 | 01-JAN-01:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.56 | 0.00 | 01-JAN-00:10 | 7642.59 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.56 | 0.00 | 01-JAN-00:10 | 7642.59 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7153.34 | 87344.05 | 14-MAY-05:00 | 368328.60 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7153.34 | 87344.05 | 14-MAY-05:00 | 368328.60 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7153.34 | 87344.05 | 14-MAY-05:00 | 368328.60 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 418.04 | 0.00 | 01-JAN-00:10 | 236270.43 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
EnergyTransfer:HVAC | 9463.18 | 11978.78 | 01-JAN-07:00 | 2268853.00 | 07-AUG-10:30 |
HeatingCoils:EnergyTransfer | 30.51 | 0.00 | 01-JAN-00:10 | 221415.14 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 30.51 | 0.00 | 01-JAN-00:10 | 221415.14 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 30.51 | 0.00 | 01-JAN-00:10 | 221415.14 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 9432.67 | 9268.83 | 03-JAN-07:10 | 2268853.00 | 07-AUG-10:30 |
EnergyTransfer:Plant | 18703.33 | 0.00 | 01-JAN-00:10 | 5338679.65 | 07-AUG-10:30 |
LoopToLoop:EnergyTransfer | 5836.99 | 0.00 | 01-JAN-00:10 | 1679266.49 | 07-AUG-10:30 |
WaterSystems:EnergyTransfer | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-12:40 |
Boilers:EnergyTransfer | 30.09 | 0.00 | 01-JAN-00:10 | 260654.36 | 03-JAN-07:10 |
Chillers:EnergyTransfer | 5848.83 | 0.00 | 01-JAN-00:10 | 1678503.79 | 07-AUG-10:30 |
HeatRejection:EnergyTransfer | 6599.90 | 0.00 | 01-JAN-00:10 | 1947496.43 | 07-AUG-10:30 |
General:HeatRejection:EnergyTransfer | 6599.90 | 0.00 | 01-JAN-00:10 | 1947496.43 | 07-AUG-10:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -607.039 | 0.000 | 0.000 | 92.159 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -75.246 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -633.244 | 0.000 | 0.000 | 83.398 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 111.396 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4533.942 | 0.000 | 0.000 | 835.872 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -686.424 |
CORE_TOP | 0.000 | 0.000 | 0.065 | -400.032 | 0.000 | 0.000 | 84.569 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -123.052 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -69.460 | 0.000 | 0.000 | 10.526 | 10.696 | 36.365 | 21.896 | 0.000 | 0.009 | 40.952 | 0.000 | -49.778 | 0.000 | -1.206 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -61.138 | 0.000 | 0.000 | 6.769 | 6.863 | 23.435 | 50.781 | 0.000 | 0.006 | 5.540 | 0.000 | -31.445 | 0.000 | -0.811 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -111.333 | 0.000 | 0.000 | 10.486 | 10.570 | 36.366 | 100.385 | 0.000 | 0.008 | 3.577 | 0.000 | -48.815 | 0.000 | -1.244 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -103.027 | 0.000 | 0.000 | 6.738 | 6.831 | 23.435 | 56.653 | 0.000 | 0.005 | 47.405 | 0.000 | -37.120 | 0.000 | -0.921 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.270 | -478.711 | 0.000 | 0.000 | 107.580 | 106.792 | 363.654 | 232.589 | 0.000 | 0.232 | 147.731 | 0.000 | -454.794 | 0.000 | -25.344 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.100 | -494.772 | 0.000 | 0.000 | 49.961 | 68.567 | 234.352 | 505.854 | 0.000 | 0.119 | 0.001 | 0.000 | -302.041 | 0.000 | -18.204 | -43.936 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.025 | -962.941 | 0.000 | 0.000 | 105.309 | 105.631 | 363.660 | 999.720 | 0.000 | 0.176 | 0.031 | 0.000 | -474.555 | 0.000 | -28.251 | -108.774 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.001 | -598.722 | 0.000 | 0.000 | 68.280 | 68.228 | 234.351 | 576.104 | 0.000 | 0.133 | 0.002 | 0.000 | -327.576 | 0.000 | -18.934 | -1.865 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.281 | -43.733 | 0.000 | 0.000 | 10.981 | 10.679 | 36.365 | 24.021 | 0.000 | 0.030 | 5.697 | 0.000 | -42.416 | 0.000 | -2.905 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.445 | -47.986 | 0.000 | 0.000 | 6.871 | 6.856 | 23.435 | 51.227 | 0.000 | 0.015 | 0.002 | 0.000 | -28.465 | 0.000 | -2.103 | -10.296 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.355 | -88.591 | 0.000 | 0.000 | 10.651 | 10.563 | 36.366 | 100.463 | 0.000 | 0.021 | 0.003 | 0.000 | -44.980 | 0.000 | -3.307 | -21.541 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.224 | -56.583 | 0.000 | 0.000 | 6.921 | 6.823 | 23.435 | 57.727 | 0.000 | 0.016 | 0.000 | 0.000 | -31.086 | 0.000 | -2.226 | -5.251 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.099 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.358 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1284.962 | 0.000 | 0.000 | 9.501 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -299.608 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.098 | -121.562 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -36.993 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7153.330 | 0.000 | 0.000 | 20.516 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -409.654 |
GROUNDFLOOR_PLENUM | 1.128 | -67.122 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.014 | 68.604 | 0.000 | 0.000 | 0.000 | -2.624 | 0.000 |
MIDFLOOR_PLENUM | 6.578 | -374.598 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.278 | 412.810 | 0.000 | 0.000 | 0.000 | -45.068 | 0.000 |
TOPFLOOR_PLENUM | 8.639 | -57.316 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.025 | 53.467 | 0.000 | 0.000 | 0.000 | -4.815 | -0.002 |
Total Facility | 16.345 | -499.035 | 2.865 | -17992.206 | 0.000 | 0.000 | 1528.988 | 2461.994 | 14676.396 | 2777.420 | 0.000 | 1.088 | 897.224 | 0.000 | -1873.070 | 0.000 | -157.964 | -1840.006 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | -105344.28 | 0.00 | 0.00 | 1299.44 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 85672.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | -90762.29 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 84287.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-OCT-04:12 | 0.00 | 0.00 | 0.00 | -753001.75 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 688251.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-OCT-04:12 | 0.00 | 0.00 | 0.00 | -71348.41 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 64873.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 03-OCT-04:12 | 0.00 | 0.00 | 0.00 | -11031.49 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 11796.60 | 0.00 | -1568.25 | 0.00 | -9.89 | 0.00 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:32 | 0.00 | 0.00 | 0.00 | -18973.04 | 0.00 | 0.00 | 22.25 | 28.32 | 464.11 | 13480.33 | 0.00 | 30.22 | 4947.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-11:11 | 0.00 | 0.00 | 0.00 | -22674.14 | 0.00 | 0.00 | 32.62 | 43.94 | 720.19 | 21286.40 | 0.00 | 24.39 | 566.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 15-OCT-13:51 | 0.00 | 0.00 | 0.00 | -23880.42 | 0.00 | 0.00 | 21.38 | 28.32 | 464.11 | 11745.74 | 0.00 | 25.09 | 11595.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | -77156.05 | 0.00 | 0.00 | 1116.18 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 79921.92 | 0.00 | -13979.27 | 0.00 | -179.94 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 | -192608.16 | 0.00 | 0.00 | 230.19 | 283.19 | 4641.14 | 133243.60 | 0.00 | 0.00 | 54325.63 | 0.00 | -0.00 | 0.00 | -115.59 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:32 | 0.00 | 0.00 | 0.00 | -214708.31 | 0.00 | 0.00 | 347.88 | 439.45 | 7201.95 | 186005.17 | 0.00 | 0.00 | 21753.77 | 0.00 | -0.00 | 0.00 | -1039.91 | 0.00 |
PERIMETER_MID_ZN_4 | 20-AUG-16:01 | 0.00 | 0.00 | 0.00 | -214604.77 | 0.00 | 0.00 | 212.33 | 283.19 | 4641.11 | 130994.60 | 0.00 | 0.00 | 79685.16 | 0.00 | -0.00 | 0.00 | -1211.62 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -9658.37 | 0.00 | 0.00 | 112.08 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 9455.21 | 0.00 | -936.28 | 0.00 | -0.36 | 0.00 |
PERIMETER_TOP_ZN_2 | 15-OCT-09:02 | 0.00 | 0.00 | 0.00 | -19202.43 | 0.00 | 0.00 | 22.95 | 28.32 | 464.11 | 11990.02 | 0.00 | 116.11 | 6580.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-14:21 | 0.00 | 0.00 | 0.00 | -24084.19 | 0.00 | 0.00 | 30.88 | 43.94 | 720.19 | 13708.01 | 0.00 | 52.73 | 9528.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:41 | 0.00 | 0.00 | 0.00 | -23049.15 | 0.00 | 0.00 | 19.56 | 28.32 | 464.11 | 12868.02 | 0.00 | 16.77 | 9652.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-17:45 | 0.00 | 0.00 | 0.00 | -8047.70 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 235.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-17:52 | 0.00 | 0.00 | 0.00 | -74966.61 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3153.53 |
DATACENTER_TOP_ZN_6 | 06-AUG-17:45 | 0.00 | 0.00 | 0.00 | -7642.59 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -169.42 |
DATACENTER_BASEMENT_ZN_6 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | -368277.07 | 0.00 | 0.00 | 2153.49 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17666.12 |
GROUNDFLOOR_PLENUM | 16-OCT-05:10 | 0.00 | -12190.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12217.83 | 0.00 | -0.00 | 0.00 | -27.71 | 0.00 |
MIDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -80538.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80880.67 | 0.00 | -0.00 | 0.00 | -342.40 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-14:05 | 0.00 | -18608.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.93 | 18526.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | -2661.22 | 0.00 | -1609226.84 | 0.00 | 0.00 | 15843.25 | 10593.62 | 616289.16 | 0.00 | 0.00 | 0.00 | 1046723.02 | 0.00 | -75792.94 | 0.00 | -1768.04 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-06:03 | 0.00 | 0.00 | 53615.04 | 0.00 | 0.00 | 0.00 | 1163.43 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -62963.20 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JAN-06:02 | 0.00 | 0.00 | 89646.06 | 0.00 | 0.00 | 0.00 | 1466.86 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45969.58 | 0.00 | -1112.49 | -54308.01 |
PERIMETER_MID_ZN_2 | 09-JAN-06:02 | 0.00 | 0.00 | 72236.79 | 0.00 | 0.00 | 0.00 | 929.61 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31955.69 | 0.00 | -761.93 | -47071.77 |
PERIMETER_MID_ZN_1 | 30-MAR-05:03 | 0.00 | 0.00 | 61286.23 | 0.00 | 0.00 | 0.00 | 1426.85 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41253.70 | 0.00 | -1306.69 | -30430.02 |
PERIMETER_MID_ZN_4 | 03-JAN-06:03 | 0.00 | 0.00 | 7343.55 | 0.00 | 0.00 | 0.00 | 903.28 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 13818.91 | 0.00 | -28306.03 | 0.00 | -382.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 11482.62 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1760.31 | 0.00 | -385.09 | -10150.25 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 12309.91 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1204.72 | 0.00 | -279.90 | -11349.24 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 15646.41 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1887.27 | 0.00 | -432.19 | -14140.00 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 11663.14 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1362.81 | 0.00 | -308.41 | -10515.87 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 01-JAN-01:20 | 0.00 | 0.00 | 531.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2497.46 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:12 | 10233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -361.69 | -9871.91 |
MIDFLOOR_PLENUM | 19-MAR-15:21 | 70074.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2989.01 | -67085.01 |
TOPFLOOR_PLENUM | 25-APR-05:02 | 13115.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -60.22 | -13055.77 |
Total Facility | 30-MAR-05:03 | -1018330.70 | 1066783.31 | 262421.42 | -1066783.31 | 0.00 | 0.00 | 17706.84 | 10593.62 | 497997.76 | 0.00 | 0.00 | 0.00 | 400506.58 | 0.00 | -163152.85 | 0.00 | -7742.67 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.7673 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.7220 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 91.7642 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 80.9003 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.3048 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.5538 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9789 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9789 | 0.2410 | 1.0000 | Not calculated | 1.2002 | 0.2410 | ||
AIRLOOP DATACENTER BASEMENT | 24.8187 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.8190 | 0.0136 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.4762 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4762 | 0.0328 | 1.0000 | Not calculated | 0.0156 | 0.0328 | ||
AIRLOOP DATACENTER MID | 4.5468 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5468 | 0.0344 | 1.0000 | Not calculated | 0.1563 | 0.0344 | ||
AIRLOOP DATACENTER TOP | 0.4621 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4621 | 0.0338 | 1.0000 | Not calculated | 0.0156 | 0.0338 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.8836 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2851 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 45.8821 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8652 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.6524 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2839 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.8187 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.8187 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.4762 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4762 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0328 | ||
AIRLOOP DATACENTER MID | 4.5468 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5468 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0344 | ||
AIRLOOP DATACENTER TOP | 0.4621 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4621 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0338 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 4.9789 | 4.9789 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4126 | 5.4126 | 1.6184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 50.8828 | 50.8828 | 16.1807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9606 | 4.9606 | 1.6172 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8349 | 0.8349 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0376 | 1.0376 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1796 | 1.1796 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3026 | 1.3026 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.6294 | 7.6294 | 2.0294 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.6671 | 10.6671 | 1.3120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2988 | 11.2988 | 2.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2862 | 11.2862 | 1.3092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8622 | 0.8622 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0632 | 1.0632 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2228 | 1.2228 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1961 | 1.1961 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4762 | 0.4762 | 0.4762 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5468 | 4.5468 | 4.5468 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4621 | 0.4621 | 0.4621 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.8187 | 24.8187 | 24.8187 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.7673 | 8.7220 | 9.7673 | 2.2851 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 91.7642 | 80.9003 | 91.7642 | 22.8652 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.3048 | 8.5538 | 9.3048 | 2.2839 | 0.0000 | 1.0000 |
CAV_BAS | 4.9789 | 4.9789 | 4.9789 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.8187 | 24.8190 | 24.8187 | 24.8187 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4762 | 0.4762 | 0.4762 | 0.4762 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5468 | 4.5468 | 4.5468 | 4.5468 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4621 | 0.4621 | 0.4621 | 0.4621 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7063 | 2.7063 | 1.6184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.4414 | 25.4414 | 16.1807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4803 | 2.4803 | 1.6172 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4174 | 0.4174 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5188 | 0.5188 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5898 | 0.5898 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6513 | 0.6513 | 0.1303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8147 | 3.8147 | 2.0294 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3335 | 5.3335 | 1.3120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6494 | 5.6494 | 2.0338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6431 | 5.6431 | 1.3092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4311 | 0.4311 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5316 | 0.5316 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6114 | 0.6114 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5980 | 0.5980 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4762 | 0.4762 | 0.4762 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5468 | 4.5468 | 4.5468 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4621 | 0.4621 | 0.4621 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.8187 | 24.8187 | 24.8187 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.8836 | 2.2851 | 2.2851 | 2.2851 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 45.8821 | 22.8652 | 22.8652 | 22.8652 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.6524 | 2.2839 | 2.2839 | 2.2839 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.8187 | 24.8187 | 24.8187 | 24.8187 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4762 | 0.4762 | 0.4762 | 0.4762 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5468 | 4.5468 | 4.5468 | 4.5468 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4621 | 0.4621 | 0.4621 | 0.4621 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 839.17 |
Number of hours not met | 839.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 45.43 | 322456.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1670.61 | 420641.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2461.99 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 347.35 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2384.05 | 190806.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 395.04 | 43335.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 661.18 | 72551.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 480.46 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 392.80 | 45273.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26036.15 |
Natural Gas | 0.00 | 45.43 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 26081.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.15 |
Space Heating | 0.00 |
Space Cooling | 36.07 |
Fans (All) | 51.47 |
Service Water Heating | 8.48 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 562.09 |
Subtotal | 562.09 |
Natural Gas [MJ/m2] | |
Space Heating | 0.98 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.98 |
Subtotal | 0.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.44 |
Space Heating | 0.17 |
Space Cooling | 6.41 |
Fans (All) | 9.14 |
Service Water Heating | 1.51 |
Receptacle Equipment | 56.27 |
Miscellaneous | 17.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 962. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7823.17 | 824.67 | 112.17 | 0.00 | 0.00 |
CORE_BOTTOM | 8688.17 | 71.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8686.50 | 73.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8677.83 | 82.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7925.33 | 834.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8670.83 | 89.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8676.33 | 83.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8589.67 | 170.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8595.83 | 164.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6997.83 | 1762.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6938.17 | 1821.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6896.33 | 1863.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 3886.67 | 4873.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
Min | 3886.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4873.33 | 112.17 | 0.00 | 0.00 |
Average | 8192.88 | 562.24 | 4.88 | 0.00 | 0.00 |
Sum | 188436.33 | 12931.50 | 112.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 362944.00 | 4240.00 | 1432.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330750.00 | 63.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1103.50 | 1164.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1068.50 | 1199.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1048.33 | 1219.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 44756.83 | 58638.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 362944.00 | 58638.17 | 1432.00 | 0.00 | 0.00 |
Average | 77380.27 | 2892.38 | 62.26 | 0.00 | 0.00 |
Sum | 1779746.17 | 66524.83 | 1432.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6660.17 | 1997.83 | 101.33 | 0.67 | 0.00 |
CORE_BOTTOM | 7683.17 | 1076.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7871.50 | 888.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8098.50 | 661.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8417.17 | 342.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8394.33 | 365.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8293.67 | 466.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7204.50 | 1555.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8634.67 | 125.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8327.00 | 433.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8362.17 | 397.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7949.83 | 810.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8670.33 | 89.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8446.00 | 314.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8486.67 | 273.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8065.67 | 694.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7972.33 | 787.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7915.67 | 844.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7892.67 | 867.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 4671.67 | 4088.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7916.83 | 843.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8069.83 | 690.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7928.50 | 831.50 | 0.00 | 0.00 | 0.00 |
Min | 4671.67 | 89.67 | 0.00 | 0.00 | 0.00 |
Max | 8670.33 | 4088.33 | 101.33 | 0.67 | 0.00 |
Average | 7910.12 | 845.44 | 4.41 | 0.03 | 0.00 |
Sum | 181932.83 | 19445.17 | 101.33 | 0.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 357581.00 | 9632.17 | 1393.50 | 9.33 | 0.00 |
CORE_BOTTOM | 329161.00 | 1652.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329596.67 | 1216.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329944.00 | 869.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1640.17 | 627.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1598.00 | 670.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1581.00 | 687.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 54795.33 | 48599.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 357581.00 | 48599.67 | 1393.50 | 9.33 | 0.00 |
Average | 77493.31 | 2780.61 | 60.59 | 0.41 | 0.00 |
Sum | 1782346.17 | 63954.00 | 1393.50 | 9.33 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:53
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513510E+11 | 105631.20 | 02-JAN-07:05 | 11.00 | 8.46 | 0.569786E+10 | 7651.70 | 02-JAN-10:09 | 13.33 | 8.97 |
February | 0.438715E+11 | 96910.23 | 27-FEB-07:11 | 10.33 | 8.74 | 0.515891E+10 | 7500.19 | 01-FEB-14:09 | 10.33 | 8.74 |
March | 0.518900E+11 | 99149.42 | 20-MAR-06:11 | 10.67 | 10.09 | 0.615564E+10 | 7499.55 | 01-MAR-14:09 | 10.67 | 10.09 |
April | 0.489504E+11 | 99705.46 | 10-APR-06:11 | 12.00 | 10.34 | 0.547171E+10 | 7499.62 | 13-APR-09:00 | 23.00 | 15.74 |
May | 0.490367E+11 | 97299.08 | 30-MAY-06:11 | 12.67 | 11.58 | 0.592193E+10 | 7499.40 | 24-MAY-09:50 | 12.67 | 11.58 |
June | 0.498983E+11 | 93151.47 | 12-JUN-06:11 | 14.00 | 12.64 | 0.590574E+10 | 8588.96 | 21-JUN-07:19 | 18.33 | 15.07 |
July | 0.509256E+11 | 90501.07 | 05-JUL-06:11 | 17.33 | 14.28 | 0.549780E+10 | 7545.91 | 31-JUL-09:30 | 24.50 | 19.53 |
August | 0.558824E+11 | 90178.55 | 28-AUG-06:11 | 14.00 | 14.00 | 0.616567E+10 | 7671.82 | 07-AUG-09:30 | 14.00 | 14.00 |
September | 0.465166E+11 | 91689.89 | 20-SEP-06:11 | 12.33 | 11.23 | 0.557757E+10 | 10184.12 | 29-SEP-13:00 | 34.00 | 17.85 |
October | 0.528685E+11 | 101024.63 | 16-OCT-06:11 | 19.67 | 9.82 | 0.583940E+10 | 10408.26 | 04-OCT-13:00 | 19.67 | 9.82 |
November | 0.531230E+11 | 97721.79 | 13-NOV-07:05 | 12.33 | 11.14 | 0.563990E+10 | 7499.95 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.527254E+11 | 99174.58 | 26-DEC-07:05 | 7.67 | 1.53 | 0.549643E+10 | 7500.23 | 20-DEC-14:00 | 7.67 | 1.53 |
Annual Sum or Average | 0.607040E+12 | 0.685286E+11 | ||||||||
Minimum of Months | 0.438715E+11 | 90178.55 | 7.67 | 1.53 | 0.515891E+10 | 7499.40 | 7.67 | 1.53 | ||
Maximum of Months | 0.558824E+11 | 105631.20 | 19.67 | 14.28 | 0.616567E+10 | 10408.26 | 34.00 | 19.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459507E+11 | 90763.26 | 02-JAN-05:11 | 11.00 | 9.07 | 0.507859E+10 | 6735.06 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.425465E+11 | 86618.65 | 21-FEB-05:12 | 8.00 | 6.97 | 0.460573E+10 | 6735.47 | 01-FEB-14:09 | 8.00 | 6.97 |
March | 0.525209E+11 | 84381.88 | 13-MAR-04:12 | 12.00 | 11.28 | 0.550014E+10 | 6735.03 | 01-MAR-14:09 | 12.00 | 11.28 |
April | 0.551550E+11 | 84327.97 | 17-APR-04:12 | 10.33 | 8.77 | 0.488219E+10 | 6735.15 | 13-APR-09:00 | 10.33 | 8.77 |
May | 0.487946E+11 | 83940.40 | 30-MAY-04:12 | 11.00 | 10.06 | 0.528551E+10 | 6735.17 | 03-MAY-13:00 | 11.00 | 10.06 |
June | 0.525850E+11 | 84972.56 | 12-JUN-04:12 | 13.07 | 11.97 | 0.527101E+10 | 6734.75 | 23-JUN-09:20 | 21.33 | 15.56 |
July | 0.593480E+11 | 83760.19 | 13-JUL-04:13 | 17.00 | 15.07 | 0.489618E+10 | 6734.79 | 11-JUL-09:20 | 17.00 | 15.07 |
August | 0.667454E+11 | 83023.00 | 23-AUG-04:13 | 15.80 | 14.08 | 0.549607E+10 | 6734.74 | 21-AUG-09:20 | 15.80 | 14.08 |
September | 0.487552E+11 | 88160.34 | 05-SEP-04:13 | 16.00 | 14.34 | 0.488278E+10 | 6734.74 | 15-SEP-09:20 | 18.33 | 14.33 |
October | 0.555316E+11 | 88502.46 | 16-OCT-04:13 | 19.67 | 9.61 | 0.508008E+10 | 6798.53 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.518450E+11 | 88952.34 | 13-NOV-05:12 | 11.00 | 10.06 | 0.503007E+10 | 6735.37 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.534629E+11 | 86897.88 | 11-DEC-05:12 | 7.67 | 7.12 | 0.490211E+10 | 6735.79 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.633241E+12 | 0.609105E+11 | ||||||||
Minimum of Months | 0.425465E+11 | 83023.00 | 7.67 | 6.97 | 0.460573E+10 | 6734.74 | 8.00 | 6.97 | ||
Maximum of Months | 0.667454E+11 | 90763.26 | 19.67 | 15.07 | 0.550014E+10 | 6798.53 | 26.17 | 16.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335213E+11 | 73422.41 | 18-JAN-06:02 | 15.67 | 11.88 | 0.504934E+10 | 6735.01 | 10-JAN-14:09 | 15.67 | 11.88 |
February | 0.308306E+11 | 72993.39 | 02-FEB-06:02 | 12.00 | 10.34 | 0.458199E+10 | 6735.27 | 01-FEB-14:09 | 12.00 | 10.34 |
March | 0.361151E+11 | 73921.22 | 23-MAR-05:02 | 10.67 | 9.62 | 0.547782E+10 | 6734.97 | 01-MAR-14:09 | 10.67 | 9.62 |
April | 0.365737E+11 | 74212.64 | 25-APR-05:02 | 11.33 | 11.25 | 0.486516E+10 | 6735.07 | 13-APR-13:00 | 11.33 | 11.25 |
May | 0.389894E+11 | 74153.81 | 23-MAY-05:02 | 12.33 | 10.66 | 0.527570E+10 | 6735.13 | 03-MAY-13:00 | 12.33 | 10.66 |
June | 0.407868E+11 | 74193.29 | 01-JUN-05:02 | 12.17 | 12.17 | 0.526404E+10 | 6734.81 | 15-JUN-13:20 | 22.00 | 16.84 |
July | 0.417575E+11 | 74523.15 | 20-JUL-04:11 | 17.00 | 17.00 | 0.488938E+10 | 6734.78 | 11-JUL-09:20 | 17.00 | 17.00 |
August | 0.449807E+11 | 74358.71 | 22-AUG-04:11 | 15.67 | 13.45 | 0.549189E+10 | 6734.81 | 21-AUG-13:20 | 15.67 | 13.45 |
September | 0.391723E+11 | 74188.03 | 25-SEP-04:12 | 17.00 | 16.37 | 0.487398E+10 | 6734.80 | 20-SEP-13:20 | 17.00 | 16.37 |
October | 0.407494E+11 | 75315.64 | 17-OCT-04:12 | 16.33 | 8.45 | 0.506674E+10 | 6734.98 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.354524E+11 | 74103.90 | 21-NOV-06:02 | 13.00 | 11.87 | 0.501159E+10 | 6735.16 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.344627E+11 | 73107.66 | 07-DEC-06:02 | 12.00 | 8.96 | 0.487362E+10 | 6735.08 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.453392E+12 | 0.607212E+11 | ||||||||
Minimum of Months | 0.308306E+11 | 72993.39 | 10.67 | 8.45 | 0.458199E+10 | 6734.78 | 10.67 | 9.62 | ||
Maximum of Months | 0.449807E+11 | 75315.64 | 17.00 | 17.00 | 0.549189E+10 | 6735.27 | 22.00 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250955E+11 | 34434.13 | 18-JAN-15:00 | 23.00 | 14.79 | 0.482907E+10 | 6734.80 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.240659E+11 | 34756.48 | 02-FEB-15:00 | 19.00 | 13.19 | 0.443381E+10 | 6735.54 | 01-FEB-14:09 | 19.00 | 13.19 |
March | 0.289834E+11 | 39278.67 | 24-MAR-05:03 | 12.00 | 12.00 | 0.533485E+10 | 6734.88 | 01-MAR-14:09 | 12.00 | 12.00 |
April | 0.332844E+11 | 68011.54 | 27-APR-05:03 | 15.00 | 14.41 | 0.481428E+10 | 6735.08 | 13-APR-13:00 | 15.00 | 14.41 |
May | 0.357764E+11 | 68296.19 | 04-MAY-05:02 | 14.33 | 12.38 | 0.522936E+10 | 6735.17 | 03-MAY-13:00 | 14.33 | 12.38 |
June | 0.397721E+11 | 69915.93 | 28-JUN-05:03 | 16.17 | 15.98 | 0.524608E+10 | 6734.73 | 23-JUN-09:20 | 16.17 | 15.98 |
July | 0.422364E+11 | 70189.01 | 26-JUL-05:02 | 18.00 | 16.69 | 0.488366E+10 | 6734.76 | 11-JUL-09:20 | 18.00 | 16.69 |
August | 0.448589E+11 | 70778.88 | 10-AUG-05:02 | 18.00 | 16.69 | 0.548450E+10 | 6734.78 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.364952E+11 | 70165.92 | 25-SEP-05:03 | 17.00 | 16.37 | 0.485080E+10 | 6734.74 | 21-SEP-09:20 | 17.00 | 16.37 |
October | 0.362414E+11 | 71359.72 | 02-OCT-04:12 | 19.03 | 17.69 | 0.502786E+10 | 6734.84 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.274673E+11 | 57787.93 | 01-NOV-05:03 | 12.83 | 9.89 | 0.490010E+10 | 6735.16 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.257546E+11 | 34371.42 | 19-DEC-15:00 | 22.00 | 9.60 | 0.470534E+10 | 6735.49 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.400031E+12 | 0.597397E+11 | ||||||||
Minimum of Months | 0.240659E+11 | 34371.42 | 12.00 | 9.60 | 0.443381E+10 | 6734.73 | 12.00 | 10.62 | ||
Maximum of Months | 0.448589E+11 | 71359.72 | 23.00 | 17.69 | 0.548450E+10 | 6735.54 | 26.83 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389667E+10 | 5953.90 | 17-JAN-13:30 | 23.00 | 16.97 | 0.624292E+09 | 845.66 | 10-JAN-14:09 | 23.00 | 16.97 |
February | 0.378977E+10 | 5130.12 | 21-FEB-13:10 | 20.67 | 13.69 | 0.570064E+09 | 845.71 | 01-FEB-14:09 | 20.67 | 13.69 |
March | 0.482490E+10 | 5975.70 | 13-MAR-13:40 | 17.67 | 13.75 | 0.682229E+09 | 845.66 | 01-MAR-14:09 | 17.67 | 13.75 |
April | 0.596817E+10 | 7060.14 | 26-APR-13:40 | 26.33 | 16.87 | 0.610228E+09 | 845.67 | 13-APR-13:00 | 26.33 | 16.87 |
May | 0.578123E+10 | 6842.25 | 04-MAY-13:30 | 23.00 | 16.67 | 0.660951E+09 | 845.69 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.703044E+10 | 10506.19 | 19-JUN-05:02 | 16.17 | 14.82 | 0.661164E+09 | 845.63 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.822197E+10 | 10526.53 | 05-JUL-05:02 | 17.00 | 14.42 | 0.614770E+09 | 845.63 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.868244E+10 | 10540.88 | 21-AUG-05:02 | 16.92 | 15.63 | 0.689725E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.576876E+10 | 10765.89 | 06-SEP-05:02 | 16.98 | 15.03 | 0.611126E+09 | 845.63 | 01-SEP-13:09 | 16.98 | 15.03 |
October | 0.629613E+10 | 11033.49 | 03-OCT-04:12 | 19.00 | 17.66 | 0.635319E+09 | 845.81 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.465956E+10 | 5772.66 | 13-NOV-11:30 | 18.50 | 14.08 | 0.626065E+09 | 845.69 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.453934E+10 | 6078.31 | 05-DEC-14:30 | 24.50 | 12.89 | 0.607892E+09 | 845.74 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.694594E+11 | 0.759382E+10 | ||||||||
Minimum of Months | 0.378977E+10 | 5130.12 | 16.17 | 12.89 | 0.570064E+09 | 845.63 | 16.98 | 10.63 | ||
Maximum of Months | 0.868244E+10 | 11033.49 | 26.33 | 17.66 | 0.689725E+09 | 845.81 | 26.33 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360545E+10 | 7160.00 | 20-JAN-09:00 | 17.00 | 13.94 | 0.407239E+09 | 544.98 | 10-JAN-14:09 | 17.00 | 13.94 |
February | 0.327942E+10 | 11289.59 | 20-FEB-09:13 | 14.00 | 8.34 | 0.368739E+09 | 545.01 | 01-FEB-14:09 | 14.00 | 8.34 |
March | 0.419756E+10 | 11210.13 | 19-MAR-08:13 | 15.13 | 13.86 | 0.441002E+09 | 544.98 | 01-MAR-14:09 | 15.13 | 13.86 |
April | 0.558235E+10 | 17616.65 | 30-APR-09:53 | 25.00 | 16.34 | 0.393685E+09 | 545.01 | 13-APR-09:00 | 25.00 | 16.34 |
May | 0.529060E+10 | 17680.79 | 28-MAY-08:53 | 19.00 | 14.25 | 0.426950E+09 | 545.00 | 03-MAY-13:00 | 19.00 | 14.25 |
June | 0.596025E+10 | 17793.27 | 18-JUN-07:23 | 18.50 | 15.13 | 0.426161E+09 | 544.96 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.726034E+10 | 18577.56 | 23-JUL-08:12 | 23.67 | 19.22 | 0.396697E+09 | 544.96 | 07-JUL-13:09 | 23.67 | 19.22 |
August | 0.775304E+10 | 18418.85 | 06-AUG-08:42 | 23.67 | 19.12 | 0.444786E+09 | 545.50 | 14-AUG-09:09 | 25.32 | 20.33 |
September | 0.529869E+10 | 18509.40 | 10-SEP-08:32 | 21.00 | 17.14 | 0.394442E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.534112E+10 | 18974.01 | 15-OCT-08:32 | 31.67 | 15.30 | 0.410280E+09 | 545.12 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.385660E+10 | 10438.75 | 19-NOV-08:23 | 21.50 | 11.71 | 0.404371E+09 | 545.00 | 06-NOV-10:00 | 21.50 | 11.71 |
December | 0.371187E+10 | 7752.06 | 05-DEC-08:50 | 23.17 | 11.57 | 0.393093E+09 | 545.03 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.611373E+11 | 0.490744E+10 | ||||||||
Minimum of Months | 0.327942E+10 | 7160.00 | 14.00 | 8.34 | 0.368739E+09 | 544.96 | 14.00 | 8.34 | ||
Maximum of Months | 0.775304E+10 | 18974.01 | 31.67 | 19.22 | 0.444786E+09 | 545.50 | 26.17 | 20.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104415E+11 | 21281.03 | 29-JAN-11:22 | 16.00 | 12.07 | 0.634808E+09 | 885.31 | 18-JAN-14:09 | 16.00 | 12.07 |
February | 0.785194E+10 | 20723.22 | 19-FEB-11:32 | 16.00 | 13.40 | 0.573580E+09 | 852.02 | 21-FEB-14:09 | 19.00 | 14.25 |
March | 0.801626E+10 | 20738.98 | 19-MAR-12:13 | 20.67 | 15.69 | 0.683059E+09 | 846.49 | 10-MAR-14:00 | 20.67 | 15.69 |
April | 0.837962E+10 | 17163.78 | 09-APR-13:13 | 19.67 | 14.29 | 0.610731E+09 | 846.22 | 26-APR-13:39 | 26.33 | 16.87 |
May | 0.619467E+10 | 8932.44 | 04-MAY-12:30 | 23.50 | 16.62 | 0.659189E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.682276E+10 | 8008.50 | 30-JUN-12:30 | 23.50 | 17.99 | 0.660218E+09 | 845.64 | 22-JUN-09:00 | 23.50 | 17.99 |
July | 0.850656E+10 | 15551.07 | 30-JUL-13:13 | 24.00 | 19.70 | 0.614804E+09 | 845.65 | 07-JUL-13:09 | 24.00 | 19.70 |
August | 0.109519E+11 | 15634.88 | 20-AUG-13:02 | 23.83 | 18.58 | 0.690317E+09 | 846.37 | 29-AUG-13:00 | 24.00 | 17.64 |
September | 0.967292E+10 | 20265.72 | 10-SEP-12:32 | 22.00 | 18.09 | 0.613246E+09 | 893.23 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.118170E+11 | 22674.31 | 15-OCT-11:11 | 32.00 | 16.55 | 0.641896E+09 | 1022.50 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.108815E+11 | 21898.68 | 23-NOV-12:32 | 18.67 | 6.96 | 0.632530E+09 | 885.44 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.117944E+11 | 22599.26 | 25-DEC-13:11 | 22.00 | 9.35 | 0.619221E+09 | 905.80 | 18-DEC-14:09 | 22.00 | 9.35 |
Annual Sum or Average | 0.111331E+12 | 0.763360E+10 | ||||||||
Minimum of Months | 0.619467E+10 | 8008.50 | 16.00 | 6.96 | 0.573580E+09 | 845.64 | 16.00 | 9.22 | ||
Maximum of Months | 0.118170E+11 | 22674.31 | 32.00 | 19.70 | 0.690317E+09 | 1022.50 | 35.33 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485221E+10 | 11541.93 | 22-JAN-15:13 | 16.33 | 12.34 | 0.409478E+09 | 544.99 | 10-JAN-14:09 | 16.33 | 12.34 |
February | 0.550533E+10 | 18156.95 | 05-FEB-15:23 | 16.50 | 10.42 | 0.372919E+09 | 545.02 | 01-FEB-14:09 | 16.50 | 10.42 |
March | 0.784708E+10 | 22261.13 | 19-MAR-15:32 | 18.00 | 14.77 | 0.445614E+09 | 545.00 | 01-MAR-14:09 | 18.00 | 14.77 |
April | 0.106012E+11 | 23203.69 | 30-APR-15:52 | 22.00 | 15.83 | 0.396608E+09 | 545.01 | 13-APR-13:50 | 22.00 | 15.83 |
May | 0.754125E+10 | 23761.56 | 21-MAY-16:02 | 18.83 | 13.76 | 0.428507E+09 | 545.02 | 03-MAY-13:00 | 18.83 | 13.76 |
June | 0.968340E+10 | 22590.85 | 18-JUN-16:02 | 21.83 | 17.37 | 0.427624E+09 | 544.96 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.119129E+11 | 23459.81 | 23-JUL-16:11 | 24.00 | 19.12 | 0.398204E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 19.12 |
August | 0.136438E+11 | 23723.99 | 06-AUG-16:01 | 23.83 | 19.74 | 0.446436E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.778433E+10 | 23834.78 | 10-SEP-15:52 | 22.00 | 16.83 | 0.396005E+09 | 544.96 | 01-SEP-13:09 | 22.00 | 16.83 |
October | 0.828283E+10 | 23880.46 | 15-OCT-13:51 | 31.00 | 15.24 | 0.412106E+09 | 545.39 | 30-OCT-13:09 | 26.17 | 16.67 |
November | 0.743968E+10 | 22369.21 | 23-NOV-13:52 | 21.00 | 8.10 | 0.407819E+09 | 545.07 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.793178E+10 | 23469.47 | 25-DEC-14:32 | 22.00 | 9.59 | 0.397608E+09 | 545.09 | 20-DEC-14:50 | 22.00 | 9.59 |
Annual Sum or Average | 0.103026E+12 | 0.493893E+10 | ||||||||
Minimum of Months | 0.485221E+10 | 11541.93 | 16.33 | 8.10 | 0.372919E+09 | 544.96 | 16.33 | 9.59 | ||
Maximum of Months | 0.136438E+11 | 23880.46 | 31.00 | 19.74 | 0.446436E+09 | 545.39 | 26.17 | 19.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273962E+10 | 4058.97 | 18-JAN-14:20 | 24.07 | 14.82 | 0.578484E+09 | 845.62 | 24-JAN-14:30 | 24.50 | 15.08 |
February | 0.254424E+10 | 3435.50 | 03-FEB-15:00 | 23.00 | 8.84 | 0.539648E+09 | 845.69 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.302712E+10 | 4082.51 | 23-MAR-14:40 | 22.33 | 17.37 | 0.645734E+09 | 845.63 | 09-MAR-14:20 | 22.33 | 17.37 |
April | 0.370774E+10 | 5510.58 | 26-APR-14:00 | 26.00 | 16.74 | 0.595450E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.438230E+10 | 6075.82 | 04-MAY-13:50 | 23.00 | 16.67 | 0.653200E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.533037E+10 | 5828.68 | 29-JUN-16:00 | 23.00 | 18.43 | 0.657562E+09 | 845.63 | 06-JUN-13:20 | 23.00 | 18.43 |
July | 0.579838E+10 | 6436.56 | 19-JUL-14:40 | 27.00 | 20.40 | 0.612465E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.40 |
August | 0.573659E+10 | 6370.87 | 17-AUG-14:00 | 28.00 | 21.19 | 0.686246E+09 | 845.63 | 21-AUG-13:20 | 22.00 | 16.84 |
September | 0.446150E+10 | 7572.20 | 30-SEP-05:02 | 23.80 | 13.84 | 0.605025E+09 | 845.63 | 15-SEP-13:20 | 23.80 | 13.84 |
October | 0.442067E+10 | 7716.72 | 02-OCT-05:02 | 19.08 | 17.74 | 0.625037E+09 | 845.66 | 27-OCT-13:09 | 21.00 | 14.82 |
November | 0.293255E+10 | 3678.10 | 01-NOV-13:50 | 17.17 | 13.44 | 0.598737E+09 | 845.66 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.278982E+10 | 4029.76 | 05-DEC-15:00 | 25.00 | 13.22 | 0.563745E+09 | 845.64 | 04-DEC-14:09 | 25.00 | 13.22 |
Annual Sum or Average | 0.478709E+11 | 0.736133E+10 | ||||||||
Minimum of Months | 0.254424E+10 | 3435.50 | 17.17 | 8.84 | 0.539648E+09 | 845.62 | 18.00 | 8.84 | ||
Maximum of Months | 0.579838E+10 | 7716.72 | 28.00 | 21.19 | 0.686246E+09 | 845.69 | 27.00 | 20.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247020E+10 | 6566.12 | 20-JAN-11:05 | 21.17 | 15.50 | 0.294657E+09 | 548.50 | 05-JAN-11:09 | 21.17 | 15.50 |
February | 0.237339E+10 | 6616.89 | 21-FEB-09:30 | 15.50 | 10.47 | 0.266193E+09 | 548.52 | 02-FEB-13:09 | 15.50 | 10.47 |
March | 0.309011E+10 | 12874.44 | 19-MAR-08:43 | 15.78 | 14.06 | 0.317922E+09 | 548.51 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.454565E+10 | 18098.40 | 30-APR-10:13 | 25.33 | 16.65 | 0.288546E+09 | 548.55 | 13-APR-10:09 | 25.33 | 16.65 |
May | 0.450008E+10 | 18148.11 | 28-MAY-09:23 | 20.00 | 14.85 | 0.313270E+09 | 548.54 | 03-MAY-14:09 | 20.00 | 14.85 |
June | 0.527694E+10 | 18926.90 | 25-JUN-09:12 | 22.33 | 16.69 | 0.313116E+09 | 548.51 | 22-JUN-10:09 | 22.33 | 16.69 |
July | 0.641842E+10 | 19271.43 | 23-JUL-08:62 | 23.33 | 19.11 | 0.293251E+09 | 548.49 | 17-JUL-10:09 | 23.33 | 19.11 |
August | 0.672376E+10 | 18835.32 | 20-AUG-09:22 | 22.00 | 18.63 | 0.327678E+09 | 548.49 | 29-AUG-14:09 | 23.83 | 17.58 |
September | 0.459625E+10 | 18125.08 | 03-SEP-08:32 | 19.33 | 14.88 | 0.289613E+09 | 548.51 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.427489E+10 | 15459.23 | 15-OCT-08:43 | 32.33 | 15.60 | 0.301425E+09 | 548.55 | 30-OCT-12:09 | 24.33 | 16.19 |
November | 0.272117E+10 | 6235.57 | 19-NOV-09:43 | 25.67 | 13.67 | 0.294887E+09 | 548.52 | 29-NOV-15:09 | 17.83 | 10.70 |
December | 0.248584E+10 | 6503.80 | 05-DEC-09:20 | 24.67 | 12.23 | 0.285053E+09 | 548.51 | 20-DEC-15:09 | 18.67 | 12.31 |
Annual Sum or Average | 0.494767E+11 | 0.358561E+10 | ||||||||
Minimum of Months | 0.237339E+10 | 6235.57 | 15.50 | 10.47 | 0.266193E+09 | 548.49 | 15.50 | 10.47 | ||
Maximum of Months | 0.672376E+10 | 19271.43 | 32.33 | 19.11 | 0.327678E+09 | 548.55 | 25.33 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101065E+11 | 20474.23 | 22-JAN-13:22 | 17.50 | 12.39 | 0.634109E+09 | 916.18 | 18-JAN-14:09 | 17.50 | 12.39 |
February | 0.722053E+10 | 19924.48 | 05-FEB-12:13 | 17.67 | 11.17 | 0.567346E+09 | 876.14 | 22-FEB-14:09 | 18.80 | 12.73 |
March | 0.675253E+10 | 19896.13 | 19-MAR-13:23 | 19.50 | 14.94 | 0.670736E+09 | 846.40 | 10-MAR-14:20 | 19.50 | 14.94 |
April | 0.655071E+10 | 11515.48 | 26-APR-13:05 | 26.83 | 17.07 | 0.603596E+09 | 846.79 | 26-APR-13:20 | 26.67 | 17.00 |
May | 0.517244E+10 | 8312.20 | 04-MAY-12:30 | 23.50 | 16.62 | 0.653212E+09 | 845.71 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.548821E+10 | 7156.09 | 30-JUN-12:30 | 23.50 | 17.99 | 0.656294E+09 | 845.65 | 20-JUN-13:20 | 23.50 | 17.99 |
July | 0.640838E+10 | 10214.12 | 31-JUL-12:40 | 28.00 | 21.19 | 0.612393E+09 | 845.65 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.836283E+10 | 12740.45 | 30-AUG-13:00 | 24.00 | 18.12 | 0.688380E+09 | 846.63 | 29-AUG-13:20 | 24.00 | 18.12 |
September | 0.896888E+10 | 19605.92 | 04-SEP-12:43 | 22.00 | 16.84 | 0.611710E+09 | 924.21 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.107219E+11 | 21487.30 | 01-OCT-12:32 | 25.33 | 20.49 | 0.642147E+09 | 968.68 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.991337E+10 | 20602.39 | 05-NOV-11:12 | 17.33 | 11.34 | 0.631093E+09 | 913.83 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.106260E+11 | 21437.10 | 24-DEC-13:02 | 17.00 | 11.59 | 0.617817E+09 | 934.40 | 19-DEC-14:09 | 17.00 | 11.59 |
Annual Sum or Average | 0.962923E+11 | 0.758883E+10 | ||||||||
Minimum of Months | 0.517244E+10 | 7156.09 | 17.00 | 11.17 | 0.567346E+09 | 845.65 | 17.00 | 9.22 | ||
Maximum of Months | 0.107219E+11 | 21487.30 | 28.00 | 21.19 | 0.688380E+09 | 968.68 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299977E+10 | 8182.10 | 26-JAN-15:30 | 16.00 | 12.30 | 0.390931E+09 | 544.99 | 10-JAN-14:09 | 16.00 | 12.30 |
February | 0.297807E+10 | 10402.98 | 20-FEB-16:53 | 17.00 | 11.53 | 0.360260E+09 | 545.01 | 01-FEB-14:09 | 17.00 | 11.53 |
March | 0.378150E+10 | 19149.56 | 19-MAR-16:41 | 17.17 | 14.59 | 0.430059E+09 | 544.98 | 01-MAR-14:09 | 17.17 | 14.59 |
April | 0.540597E+10 | 20048.92 | 16-APR-15:52 | 18.00 | 11.97 | 0.391586E+09 | 545.00 | 13-APR-13:00 | 18.00 | 11.97 |
May | 0.545267E+10 | 19877.60 | 14-MAY-16:32 | 17.00 | 12.41 | 0.425147E+09 | 545.01 | 03-MAY-13:00 | 17.00 | 12.41 |
June | 0.656276E+10 | 19288.28 | 25-JUN-16:42 | 21.00 | 16.52 | 0.425880E+09 | 544.96 | 07-JUN-13:30 | 21.00 | 16.52 |
July | 0.744953E+10 | 21324.71 | 04-JUL-16:31 | 19.67 | 15.52 | 0.396940E+09 | 544.96 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.772022E+10 | 21466.55 | 20-AUG-16:01 | 21.80 | 17.34 | 0.445065E+09 | 544.96 | 21-AUG-13:20 | 22.00 | 16.84 |
September | 0.575094E+10 | 20455.83 | 03-SEP-15:52 | 19.00 | 15.88 | 0.394226E+09 | 544.96 | 19-SEP-13:30 | 21.00 | 14.99 |
October | 0.503480E+10 | 20580.36 | 01-OCT-15:12 | 22.67 | 19.46 | 0.408180E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.355805E+10 | 8673.98 | 07-NOV-15:30 | 19.00 | 14.51 | 0.398480E+09 | 545.02 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.317757E+10 | 8636.70 | 18-DEC-15:30 | 22.00 | 8.99 | 0.382071E+09 | 545.00 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.598719E+11 | 0.484883E+10 | ||||||||
Minimum of Months | 0.297807E+10 | 8182.10 | 16.00 | 8.99 | 0.360260E+09 | 544.96 | 16.00 | 10.63 | ||
Maximum of Months | 0.772022E+10 | 21466.55 | 22.67 | 19.46 | 0.445065E+09 | 545.02 | 26.83 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208681E+10 | 3720.14 | 18-JAN-14:50 | 23.27 | 14.80 | 0.544461E+09 | 845.62 | 24-JAN-14:00 | 25.00 | 15.45 |
February | 0.200521E+10 | 3155.80 | 16-FEB-14:50 | 17.08 | 13.83 | 0.508427E+09 | 845.71 | 01-FEB-14:09 | 17.08 | 13.83 |
March | 0.251352E+10 | 4168.52 | 23-MAR-15:00 | 22.00 | 17.40 | 0.611520E+09 | 845.62 | 09-MAR-14:00 | 22.00 | 17.40 |
April | 0.341099E+10 | 5993.71 | 26-APR-14:00 | 26.00 | 16.74 | 0.581146E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.408008E+10 | 6611.09 | 04-MAY-13:40 | 23.00 | 16.67 | 0.640653E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.523504E+10 | 6436.59 | 30-JUN-14:00 | 23.00 | 17.85 | 0.652967E+09 | 845.62 | 26-JUN-09:00 | 23.00 | 17.85 |
July | 0.588609E+10 | 7203.96 | 19-JUL-14:50 | 27.00 | 20.29 | 0.610705E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.29 |
August | 0.576158E+10 | 6984.01 | 17-AUG-14:00 | 28.00 | 21.19 | 0.683351E+09 | 845.63 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.423216E+10 | 9658.50 | 30-SEP-05:02 | 23.80 | 13.84 | 0.597114E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.403875E+10 | 8081.10 | 16-OCT-13:10 | 33.75 | 16.65 | 0.612555E+09 | 845.64 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.233322E+10 | 3446.35 | 10-NOV-14:30 | 19.50 | 15.78 | 0.567646E+09 | 845.64 | 09-NOV-14:00 | 19.50 | 15.78 |
December | 0.214967E+10 | 3662.09 | 05-DEC-15:00 | 25.00 | 13.22 | 0.528309E+09 | 845.63 | 06-DEC-14:00 | 19.00 | 12.39 |
Annual Sum or Average | 0.437331E+11 | 0.713885E+10 | ||||||||
Minimum of Months | 0.200521E+10 | 3155.80 | 17.08 | 13.22 | 0.508427E+09 | 845.62 | 17.08 | 12.39 | ||
Maximum of Months | 0.588609E+10 | 9658.50 | 33.75 | 21.19 | 0.683351E+09 | 845.71 | 27.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202390E+10 | 5144.47 | 20-JAN-09:40 | 18.33 | 14.51 | 0.389908E+09 | 544.97 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.204971E+10 | 5080.93 | 02-FEB-10:10 | 17.17 | 12.19 | 0.351511E+09 | 545.02 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.275935E+10 | 8072.35 | 23-MAR-09:30 | 20.50 | 15.62 | 0.421980E+09 | 544.98 | 01-MAR-14:09 | 20.50 | 15.62 |
April | 0.445423E+10 | 16939.57 | 30-APR-10:02 | 25.17 | 16.50 | 0.388719E+09 | 545.01 | 13-APR-09:00 | 25.17 | 16.50 |
May | 0.442581E+10 | 15450.09 | 28-MAY-09:23 | 20.00 | 14.85 | 0.421721E+09 | 545.00 | 03-MAY-13:00 | 20.00 | 14.85 |
June | 0.543980E+10 | 17936.76 | 25-JUN-10:02 | 23.00 | 17.26 | 0.423508E+09 | 544.97 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.672182E+10 | 18240.48 | 30-JUL-09:02 | 23.17 | 19.60 | 0.396016E+09 | 544.96 | 17-JUL-09:50 | 23.17 | 19.60 |
August | 0.701015E+10 | 18840.91 | 06-AUG-08:52 | 24.00 | 19.32 | 0.444031E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.463900E+10 | 18627.69 | 10-SEP-09:02 | 22.17 | 17.48 | 0.390283E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.414440E+10 | 19203.49 | 15-OCT-09:02 | 32.67 | 16.02 | 0.405763E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.228730E+10 | 4666.13 | 01-NOV-09:20 | 14.67 | 12.52 | 0.394046E+09 | 544.99 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.203022E+10 | 5203.74 | 05-DEC-09:50 | 25.67 | 12.88 | 0.378012E+09 | 545.01 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.479857E+11 | 0.480550E+10 | ||||||||
Minimum of Months | 0.202390E+10 | 4666.13 | 14.67 | 12.19 | 0.351511E+09 | 544.96 | 16.83 | 10.63 | ||
Maximum of Months | 0.701015E+10 | 19203.49 | 32.67 | 19.60 | 0.444031E+09 | 545.02 | 25.67 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860242E+10 | 21411.76 | 22-JAN-13:32 | 17.67 | 12.39 | 0.619547E+09 | 882.25 | 18-JAN-14:09 | 17.67 | 12.39 |
February | 0.616582E+10 | 22136.32 | 20-FEB-13:42 | 17.00 | 10.89 | 0.552206E+09 | 846.22 | 01-FEB-14:09 | 17.00 | 10.89 |
March | 0.584604E+10 | 16016.30 | 19-MAR-11:43 | 20.83 | 15.93 | 0.650431E+09 | 846.30 | 10-MAR-14:50 | 20.83 | 15.93 |
April | 0.616114E+10 | 15151.39 | 30-APR-14:42 | 23.17 | 16.65 | 0.593715E+09 | 845.71 | 13-APR-13:50 | 23.17 | 16.65 |
May | 0.482605E+10 | 8799.54 | 04-MAY-12:30 | 23.50 | 16.62 | 0.641533E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.541300E+10 | 7762.58 | 30-JUN-13:10 | 23.00 | 17.85 | 0.650990E+09 | 845.64 | 26-JUN-09:00 | 23.00 | 17.85 |
July | 0.653113E+10 | 13229.16 | 30-JUL-14:21 | 23.50 | 19.15 | 0.610378E+09 | 845.65 | 07-JUL-13:09 | 23.50 | 19.15 |
August | 0.842562E+10 | 13267.35 | 30-AUG-13:05 | 23.83 | 18.18 | 0.686178E+09 | 846.28 | 30-AUG-13:00 | 23.00 | 18.43 |
September | 0.869028E+10 | 21072.20 | 10-SEP-13:02 | 22.17 | 18.15 | 0.607210E+09 | 910.53 | 29-SEP-13:39 | 34.67 | 17.98 |
October | 0.101912E+11 | 24084.46 | 15-OCT-14:21 | 31.00 | 15.37 | 0.634695E+09 | 944.87 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.863661E+10 | 22543.71 | 23-NOV-13:42 | 20.67 | 7.94 | 0.619458E+09 | 864.12 | 30-NOV-14:09 | 22.67 | 10.93 |
December | 0.910017E+10 | 22820.87 | 25-DEC-13:51 | 22.00 | 9.96 | 0.602151E+09 | 898.88 | 19-DEC-14:09 | 22.00 | 9.96 |
Annual Sum or Average | 0.885895E+11 | 0.746849E+10 | ||||||||
Minimum of Months | 0.482605E+10 | 7762.58 | 17.00 | 7.94 | 0.552206E+09 | 845.64 | 17.00 | 9.96 | ||
Maximum of Months | 0.101912E+11 | 24084.46 | 31.00 | 19.15 | 0.686178E+09 | 944.87 | 34.67 | 19.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248285E+10 | 7936.48 | 18-JAN-15:00 | 23.00 | 14.79 | 0.375658E+09 | 544.98 | 10-JAN-14:09 | 23.00 | 14.79 |
February | 0.255052E+10 | 10293.50 | 20-FEB-16:22 | 17.00 | 11.08 | 0.346185E+09 | 545.05 | 01-FEB-14:09 | 17.00 | 11.08 |
March | 0.334885E+10 | 12669.85 | 19-MAR-16:23 | 17.50 | 14.74 | 0.414506E+09 | 544.98 | 01-MAR-14:09 | 17.50 | 14.74 |
April | 0.517117E+10 | 21957.91 | 30-APR-16:02 | 22.00 | 15.83 | 0.386356E+09 | 545.00 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.521679E+10 | 20617.42 | 29-MAY-17:22 | 17.00 | 13.18 | 0.420344E+09 | 545.01 | 03-MAY-13:00 | 17.00 | 13.18 |
June | 0.652644E+10 | 20589.07 | 18-JUN-16:02 | 21.83 | 17.37 | 0.424094E+09 | 544.96 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.753671E+10 | 22605.80 | 30-JUL-16:21 | 21.50 | 18.49 | 0.396434E+09 | 544.96 | 07-JUL-13:09 | 21.50 | 18.49 |
August | 0.774590E+10 | 22146.98 | 27-AUG-15:32 | 22.00 | 18.09 | 0.444409E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.557788E+10 | 22002.30 | 04-SEP-15:52 | 20.00 | 16.16 | 0.392045E+09 | 544.96 | 01-SEP-13:09 | 20.00 | 16.16 |
October | 0.475370E+10 | 23049.39 | 15-OCT-15:41 | 30.17 | 14.99 | 0.403301E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.305524E+10 | 8417.19 | 10-NOV-14:50 | 19.17 | 15.85 | 0.385807E+09 | 545.04 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.261669E+10 | 8331.64 | 19-DEC-15:30 | 21.50 | 8.94 | 0.366935E+09 | 545.06 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.565828E+11 | 0.475608E+10 | ||||||||
Minimum of Months | 0.248285E+10 | 7936.48 | 17.00 | 8.94 | 0.346185E+09 | 544.96 | 17.00 | 11.08 | ||
Maximum of Months | 0.774590E+10 | 23049.39 | 30.17 | 18.49 | 0.444409E+09 | 545.06 | 26.83 | 18.49 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396042E+10 | 8785.88 | 02-JAN-06:10 | 11.00 | 8.38 | 0.00 | 0.00 | 01-JAN-00:10 | 11.00 | 8.38 |
February | 0.362535E+10 | 7286.13 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 8.00 | 6.97 |
March | 0.449180E+10 | 6816.41 | 20-MAR-05:15 | 10.67 | 10.47 | 0.00 | 0.00 | 01-MAR-00:10 | 10.67 | 10.47 |
April | 0.579253E+10 | 6995.88 | 10-APR-05:15 | 12.00 | 10.34 | 0.00 | 0.00 | 01-APR-00:10 | 12.00 | 10.34 |
May | 0.488300E+10 | 7248.71 | 01-MAY-05:15 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 12.00 |
June | 0.614780E+10 | 7170.15 | 05-JUN-05:15 | 12.33 | 11.23 | 0.00 | 0.00 | 01-JUN-00:10 | 12.33 | 11.23 |
July | 0.723669E+10 | 8891.01 | 24-JUL-05:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-JUL-00:10 | 16.67 | 16.67 |
August | 0.798056E+10 | 8621.27 | 07-AUG-05:15 | 18.00 | 17.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.00 | 17.96 |
September | 0.588094E+10 | 9613.03 | 05-SEP-05:15 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.00 | 14.76 |
October | 0.674975E+10 | 12190.36 | 16-OCT-05:10 | 18.67 | 9.56 | 0.00 | 0.00 | 01-OCT-00:10 | 18.67 | 9.56 |
November | 0.522348E+10 | 8150.62 | 13-NOV-06:15 | 11.33 | 10.63 | 0.00 | 0.00 | 01-NOV-00:10 | 11.33 | 10.63 |
December | 0.514904E+10 | 7893.60 | 26-DEC-06:15 | 7.00 | 1.09 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 1.09 |
Annual Sum or Average | 0.671214E+11 | 0.00 | ||||||||
Minimum of Months | 0.362535E+10 | 6816.41 | 7.00 | 1.09 | 0.00 | 0.00 | 7.00 | 1.09 | ||
Maximum of Months | 0.798056E+10 | 12190.36 | 18.67 | 17.96 | 0.00 | 0.00 | 18.67 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177138E+10 | 3292.84 | 21-JAN-06:15 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 13.00 |
February | 0.169935E+10 | 3268.94 | 03-FEB-06:10 | 12.33 | 3.94 | 0.00 | 0.00 | 01-FEB-00:10 | 12.33 | 3.94 |
March | 0.183935E+10 | 3487.87 | 23-MAR-15:40 | 21.33 | 17.27 | 0.00 | 0.00 | 01-MAR-00:10 | 21.33 | 17.27 |
April | 0.284305E+10 | 4188.81 | 27-APR-15:20 | 18.80 | 14.83 | 0.00 | 0.00 | 01-APR-00:10 | 18.80 | 14.83 |
May | 0.305352E+10 | 3997.25 | 04-MAY-14:20 | 22.67 | 16.59 | 0.00 | 0.00 | 01-MAY-00:10 | 22.67 | 16.59 |
June | 0.392077E+10 | 4519.82 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.470242E+10 | 5041.19 | 31-JUL-14:20 | 26.67 | 20.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.67 | 20.72 |
August | 0.516761E+10 | 5073.51 | 18-AUG-15:20 | 26.00 | 20.57 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 20.57 |
September | 0.400336E+10 | 5195.72 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.404929E+10 | 8054.29 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.238160E+10 | 3426.90 | 14-NOV-06:10 | 10.17 | 9.49 | 0.00 | 0.00 | 01-NOV-00:10 | 10.17 | 9.49 |
December | 0.202795E+10 | 3430.41 | 21-DEC-06:10 | 6.93 | 3.97 | 0.00 | 0.00 | 01-DEC-00:10 | 6.93 | 3.97 |
Annual Sum or Average | 0.374596E+11 | 0.00 | ||||||||
Minimum of Months | 0.169935E+10 | 3268.94 | 6.93 | 3.94 | 0.00 | 0.00 | 6.93 | 3.94 | ||
Maximum of Months | 0.516761E+10 | 8054.29 | 32.00 | 20.72 | 0.00 | 0.00 | 32.00 | 20.72 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154836E+10 | 7435.16 | 18-JAN-15:10 | 22.83 | 14.90 | 0.00 | 0.00 | 01-JAN-00:10 | 22.83 | 14.90 |
February | 0.166088E+10 | 7255.56 | 01-FEB-14:05 | 19.00 | 15.70 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.70 |
March | 0.254308E+10 | 10637.19 | 23-MAR-15:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-MAR-00:10 | 22.00 | 17.40 |
April | 0.538119E+10 | 14183.07 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.539188E+10 | 13224.72 | 03-MAY-13:05 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.732920E+10 | 13326.52 | 30-JUN-13:30 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.915386E+10 | 14952.69 | 19-JUL-13:40 | 27.00 | 20.62 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 20.62 |
August | 0.942791E+10 | 14531.58 | 14-AUG-13:05 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.622766E+10 | 14375.62 | 29-SEP-14:05 | 33.83 | 17.79 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 17.79 |
October | 0.507044E+10 | 18607.68 | 16-OCT-14:05 | 31.67 | 15.90 | 0.00 | 0.00 | 01-OCT-00:10 | 31.67 | 15.90 |
November | 0.204517E+10 | 7077.66 | 10-NOV-14:05 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.153579E+10 | 6727.82 | 05-DEC-15:05 | 24.67 | 13.10 | 0.00 | 0.00 | 01-DEC-00:10 | 24.67 | 13.10 |
Annual Sum or Average | 0.573154E+11 | 0.00 | ||||||||
Minimum of Months | 0.153579E+10 | 6727.82 | 19.00 | 13.10 | 0.00 | 0.00 | 19.00 | 13.10 | ||
Maximum of Months | 0.942791E+10 | 18607.68 | 33.83 | 20.62 | 0.00 | 0.00 | 33.83 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405672E+10 | 2069.56 | 30-JAN-16:50 | 14.00 | 11.30 | 95233002.70 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.833869E+10 | 4154.30 | 20-FEB-16:53 | 17.00 | 11.53 | 86400307.65 | 126.84 | 13-FEB-14:00 | 17.00 | 11.53 |
March | 0.143781E+11 | 7020.42 | 31-MAR-24:00 | 9.70 | 9.11 | 0.103240E+09 | 126.83 | 24-MAR-09:00 | 9.70 | 9.11 |
April | 0.189581E+11 | 7942.41 | 30-APR-17:22 | 21.00 | 15.77 | 91606562.75 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.432156E+10 | 3297.74 | 31-MAY-24:00 | 13.10 | 11.97 | 99240425.05 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.925153E+10 | 5332.88 | 30-JUN-24:00 | 16.40 | 15.78 | 98967294.04 | 126.85 | 28-JUN-13:09 | 16.40 | 15.78 |
July | 0.146917E+11 | 7211.83 | 31-JUL-24:00 | 18.10 | 17.45 | 91888234.59 | 126.84 | 20-JUL-09:09 | 18.10 | 17.45 |
August | 0.196764E+11 | 8047.70 | 06-AUG-17:42 | 21.33 | 19.00 | 0.103238E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.432957E+10 | 3548.05 | 30-SEP-24:00 | 18.40 | 17.30 | 91615924.79 | 126.85 | 25-SEP-13:00 | 18.40 | 17.30 |
October | 0.957716E+10 | 5311.72 | 31-OCT-24:00 | 14.90 | 11.04 | 95236487.54 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.140241E+11 | 5991.49 | 12-NOV-16:20 | 16.33 | 13.71 | 94302869.54 | 126.83 | 10-NOV-14:00 | 16.33 | 13.71 |
December | 0.194955E+11 | 8018.45 | 25-DEC-16:20 | 19.33 | 9.96 | 91977301.73 | 132.35 | 19-DEC-10:00 | 19.33 | 9.96 |
Annual Sum or Average | 0.141099E+12 | 0.114295E+10 | ||||||||
Minimum of Months | 0.405672E+10 | 2069.56 | 9.70 | 9.11 | 86400307.65 | 126.83 | 9.70 | 9.11 | ||
Maximum of Months | 0.196764E+11 | 8047.70 | 21.33 | 19.00 | 0.103240E+09 | 132.35 | 21.00 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297232E+10 | 1896.45 | 30-JAN-16:50 | 14.00 | 11.30 | 95232858.71 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.722944E+10 | 3821.34 | 22-FEB-17:00 | 14.00 | 12.23 | 86400137.60 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.130098E+11 | 6372.60 | 31-MAR-23:30 | 9.90 | 9.31 | 0.103240E+09 | 126.83 | 24-MAR-13:00 | 9.90 | 9.31 |
April | 0.176728E+11 | 7378.50 | 30-APR-17:22 | 21.00 | 15.77 | 91606679.01 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.369037E+10 | 2987.33 | 31-MAY-24:00 | 13.10 | 11.97 | 99240022.52 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.850991E+10 | 5041.86 | 30-JUN-24:00 | 16.40 | 15.78 | 98966809.87 | 126.84 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.138320E+11 | 6889.69 | 31-JUL-24:00 | 18.10 | 17.45 | 91888112.21 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.186435E+11 | 7496.66 | 06-AUG-17:55 | 21.00 | 18.98 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.375019E+10 | 3304.00 | 30-SEP-24:00 | 18.40 | 17.30 | 91612657.37 | 126.85 | 05-SEP-13:00 | 18.40 | 17.30 |
October | 0.867421E+10 | 4936.66 | 31-OCT-24:00 | 14.90 | 11.04 | 95235983.47 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.127104E+11 | 5571.50 | 07-NOV-16:30 | 18.00 | 14.13 | 94302849.23 | 126.83 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.178013E+11 | 7378.30 | 18-DEC-16:20 | 20.33 | 7.98 | 91925022.75 | 129.24 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.128496E+12 | 0.114289E+10 | ||||||||
Minimum of Months | 0.297232E+10 | 1896.45 | 9.90 | 7.98 | 86400137.60 | 126.83 | 9.90 | 9.31 | ||
Maximum of Months | 0.186435E+11 | 7496.66 | 21.00 | 18.98 | 0.103240E+09 | 129.24 | 22.83 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185393E+10 | 1829.52 | 26-JAN-16:10 | 15.67 | 12.54 | 95175753.88 | 126.84 | 20-JAN-14:00 | 15.67 | 12.54 |
February | 0.626551E+10 | 3810.74 | 22-FEB-17:00 | 14.00 | 12.23 | 86400112.03 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.121562E+11 | 6037.43 | 31-MAR-23:20 | 9.97 | 9.37 | 0.103240E+09 | 126.83 | 24-MAR-13:00 | 9.97 | 9.37 |
April | 0.172316E+11 | 7453.86 | 30-APR-17:35 | 20.67 | 15.73 | 91606869.86 | 126.83 | 05-APR-09:09 | 20.67 | 15.73 |
May | 0.324420E+10 | 2739.15 | 31-MAY-23:40 | 13.20 | 12.26 | 99240097.61 | 126.84 | 05-MAY-13:00 | 13.20 | 12.26 |
June | 0.831250E+10 | 4927.39 | 30-JUN-24:00 | 16.40 | 15.78 | 98967099.18 | 126.85 | 28-JUN-13:00 | 16.40 | 15.78 |
July | 0.137434E+11 | 6796.05 | 31-JUL-24:00 | 18.10 | 17.45 | 91888468.89 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.185318E+11 | 7642.59 | 06-AUG-17:50 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.346975E+10 | 3268.69 | 30-SEP-23:50 | 18.37 | 17.42 | 91613420.86 | 126.85 | 13-SEP-13:00 | 18.37 | 17.42 |
October | 0.824757E+10 | 4735.70 | 31-OCT-23:40 | 15.13 | 11.58 | 95236067.74 | 126.85 | 02-OCT-13:00 | 15.13 | 11.58 |
November | 0.118349E+11 | 5555.58 | 07-NOV-16:20 | 18.33 | 14.34 | 94302911.14 | 126.84 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.166706E+11 | 7378.18 | 19-DEC-16:20 | 20.33 | 7.94 | 91888822.67 | 127.11 | 19-DEC-14:09 | 20.33 | 7.94 |
Annual Sum or Average | 0.121562E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.185393E+10 | 1829.52 | 9.97 | 7.94 | 86400112.03 | 126.83 | 9.97 | 7.94 | ||
Maximum of Months | 0.185318E+11 | 7642.59 | 21.33 | 19.00 | 0.103240E+09 | 127.11 | 20.67 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239354E+12 | 92177.23 | 02-JAN-17:00 | 11.00 | 7.91 | 0.206142E+10 | 2746.27 | 17-JAN-14:09 | 23.33 | 16.85 |
February | 0.435342E+12 | 183070.99 | 21-FEB-17:00 | 16.00 | 13.03 | 0.187017E+10 | 2746.43 | 09-FEB-14:20 | 16.00 | 13.03 |
March | 0.727701E+12 | 357753.12 | 31-MAR-24:00 | 9.70 | 9.11 | 0.223512E+10 | 2750.49 | 23-MAR-13:09 | 9.70 | 9.11 |
April | 0.941180E+12 | 366206.62 | 26-APR-16:00 | 22.00 | 16.41 | 0.198502E+10 | 2751.71 | 27-APR-09:09 | 19.33 | 16.00 |
May | 0.239133E+12 | 175004.29 | 31-MAY-24:00 | 13.10 | 11.97 | 0.214805E+10 | 2746.12 | 04-MAY-13:09 | 13.10 | 11.97 |
June | 0.467417E+12 | 266714.09 | 30-JUN-24:00 | 16.40 | 15.78 | 0.214260E+10 | 2748.82 | 21-JUN-13:09 | 16.40 | 15.78 |
July | 0.729159E+12 | 358826.63 | 31-JUL-23:55 | 18.10 | 17.45 | 0.199047E+10 | 2750.66 | 25-JUL-13:09 | 18.10 | 17.45 |
August | 0.973459E+12 | 368328.60 | 14-AUG-16:00 | 25.00 | 18.49 | 0.228240E+10 | 3306.58 | 17-AUG-13:00 | 28.00 | 21.19 |
September | 0.233216E+12 | 176122.05 | 30-SEP-24:00 | 18.40 | 17.30 | 0.198296E+10 | 2746.48 | 13-SEP-13:00 | 18.40 | 17.30 |
October | 0.485603E+12 | 267575.31 | 31-OCT-24:00 | 14.90 | 11.04 | 0.206171E+10 | 2748.61 | 06-OCT-13:50 | 14.90 | 11.04 |
November | 0.706592E+12 | 275625.16 | 13-NOV-17:00 | 15.00 | 13.80 | 0.204175E+10 | 2750.05 | 10-NOV-14:00 | 15.00 | 13.80 |
December | 0.975180E+12 | 367277.71 | 26-DEC-17:00 | 16.00 | 8.71 | 0.198945E+10 | 2750.45 | 08-DEC-14:09 | 16.00 | 8.71 |
Annual Sum or Average | 0.715334E+13 | 0.247911E+11 | ||||||||
Minimum of Months | 0.233216E+12 | 92177.23 | 9.70 | 7.91 | 0.187017E+10 | 2746.12 | 9.70 | 8.71 | ||
Maximum of Months | 0.975180E+12 | 368328.60 | 25.00 | 18.49 | 0.228240E+10 | 3306.58 | 28.00 | 21.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63342241.90 | 53625.40 | 02-JAN-06:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 2007580.34 | 16729.84 | 26-DEC-06:02 | 7.00 |
Annual Sum or Average | 65349822.24 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 63342241.90 | 53625.40 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20816970.72 | 8965.01 | 09-JAN-06:02 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 5697272.99 | 8709.99 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 477909.07 | 2421.57 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 26992152.78 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 20816970.72 | 8965.01 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5739251.07 | 7224.18 | 09-JAN-06:02 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 3659943.48 | 6984.87 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 560339.04 | 2258.90 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 9959533.59 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 5739251.07 | 7224.18 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2534517.26 | 6128.65 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 2534517.26 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 2534517.26 | 6128.65 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 139684.91 | 734.36 | 03-JAN-06:03 | 4.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 139684.91 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 139684.91 | 734.36 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485395E+09 | 11482.67 | 02-JAN-05:11 | 11.00 |
February | 0.167827E+09 | 10635.16 | 06-FEB-05:12 | 8.33 |
March | 0.224144E+09 | 10913.55 | 30-MAR-04:12 | 4.57 |
April | 16769867.58 | 10229.31 | 01-APR-05:02 | 7.83 |
May | 1635211.36 | 7628.88 | 15-MAY-05:02 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 4348998.69 | 7956.79 | 30-OCT-05:03 | 10.83 |
November | 0.107025E+09 | 10662.15 | 27-NOV-05:12 | 8.67 |
December | 0.273973E+09 | 10582.40 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.128112E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.485395E+09 | 11482.67 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176880E+09 | 12310.00 | 02-JAN-05:11 | 11.00 |
February | 61443594.37 | 10979.93 | 28-FEB-06:02 | 10.17 |
March | 82120736.08 | 11867.26 | 30-MAR-04:12 | 4.57 |
April | 4889869.40 | 10851.12 | 01-APR-05:02 | 7.83 |
May | 201822.55 | 1258.64 | 13-MAY-05:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 37937.80 | 252.92 | 30-OCT-05:03 | 10.83 |
November | 30159304.53 | 9802.82 | 18-NOV-06:02 | 8.17 |
December | 89439229.23 | 11131.32 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.445173E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.176880E+09 | 12310.00 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131659E+09 | 15646.51 | 02-JAN-05:11 | 11.00 |
February | 40385101.45 | 14192.56 | 28-FEB-06:02 | 10.17 |
March | 0.119182E+09 | 15128.55 | 30-MAR-04:12 | 4.57 |
April | 10821927.52 | 14089.38 | 01-APR-05:02 | 7.83 |
May | 2753878.57 | 7116.51 | 15-MAY-05:02 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 7161051.78 | 9257.54 | 24-NOV-06:03 | 8.92 |
December | 42750482.81 | 14075.89 | 14-DEC-06:02 | 7.17 |
Annual Sum or Average | 0.354713E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.131659E+09 | 15646.51 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124620E+09 | 11663.23 | 02-JAN-05:11 | 11.00 |
February | 14460973.94 | 9606.33 | 06-FEB-06:02 | 9.00 |
March | 39586050.17 | 10353.01 | 08-MAR-06:02 | 5.17 |
April | 3527696.12 | 6681.86 | 01-APR-05:02 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 6334437.21 | 7090.59 | 27-NOV-06:03 | 10.67 |
December | 35726992.70 | 10089.31 | 14-DEC-06:02 | 7.17 |
Annual Sum or Average | 0.224257E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.17 | |
Maximum of Months | 0.124620E+09 | 11663.23 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86417619.53 | 8129.87 | 02-JAN-05:11 | 11.00 |
February | 81462136.29 | 7940.87 | 13-FEB-05:12 | 14.33 |
March | 83811438.03 | 8724.72 | 06-MAR-05:12 | 11.00 |
April | 0.111776E+09 | 9336.56 | 03-APR-04:12 | 11.67 |
May | 78735152.84 | 7179.33 | 01-MAY-04:12 | 13.00 |
June | 61461092.07 | 7313.94 | 19-JUN-04:12 | 16.00 |
July | 0.108225E+09 | 8259.29 | 13-JUL-04:11 | 17.00 |
August | 0.114560E+09 | 8041.27 | 23-AUG-04:11 | 15.80 |
September | 63881979.48 | 7590.55 | 01-SEP-04:12 | 15.00 |
October | 94772877.43 | 8841.79 | 05-OCT-04:12 | 20.67 |
November | 99754510.16 | 8294.93 | 06-NOV-05:12 | 10.00 |
December | 0.143355E+09 | 10233.76 | 18-DEC-05:12 | 17.67 |
Annual Sum or Average | 0.112821E+10 | |||
Minimum of Months | 61461092.07 | 7179.33 | 10.00 | |
Maximum of Months | 0.143355E+09 | 10233.76 | 20.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103954E+09 | 5319.01 | 17-JAN-05:12 | 14.67 |
February | 69426938.39 | 5487.19 | 14-FEB-06:02 | 13.00 |
March | 50181234.12 | 7007.46 | 19-MAR-15:21 | 18.00 |
April | 50892975.02 | 4753.07 | 18-APR-05:02 | 11.17 |
May | 49747008.60 | 4481.09 | 14-MAY-15:52 | 17.00 |
June | 32633669.93 | 4820.93 | 12-JUN-04:12 | 13.07 |
July | 45329946.92 | 3960.08 | 13-JUL-04:11 | 17.00 |
August | 36295751.82 | 3842.81 | 30-AUG-04:12 | 18.00 |
September | 45048535.55 | 5599.99 | 04-SEP-14:42 | 21.00 |
October | 58724453.12 | 6662.97 | 15-OCT-14:42 | 31.00 |
November | 54401087.06 | 4807.87 | 28-NOV-06:03 | 15.67 |
December | 61124513.89 | 5120.60 | 14-DEC-06:02 | 7.17 |
Annual Sum or Average | 0.657760E+09 | |||
Minimum of Months | 32633669.93 | 3842.81 | 7.17 | |
Maximum of Months | 0.103954E+09 | 7007.46 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159020E+10 | 10158.75 | 09-JAN-06:02 | 2.17 |
February | 0.112232E+10 | 5868.86 | 02-FEB-06:02 | 12.00 |
March | 0.131794E+10 | 8265.95 | 24-MAR-05:03 | 12.00 |
April | 0.551937E+09 | 13115.57 | 25-APR-05:02 | 11.33 |
May | 0.463718E+09 | 11261.21 | 04-MAY-05:02 | 14.33 |
June | 0.198230E+09 | 13039.71 | 14-JUN-05:03 | 13.17 |
July | 87541307.16 | 11255.96 | 06-JUL-05:03 | 14.33 |
August | 0.106265E+09 | 11155.52 | 31-AUG-05:03 | 15.17 |
September | 0.249964E+09 | 11584.43 | 12-SEP-05:03 | 15.00 |
October | 0.487563E+09 | 11568.02 | 18-OCT-05:03 | 15.00 |
November | 0.101926E+10 | 10973.82 | 01-NOV-05:03 | 12.83 |
December | 0.144396E+10 | 7267.59 | 06-DEC-06:03 | 12.33 |
Annual Sum or Average | 0.863890E+10 | |||
Minimum of Months | 87541307.16 | 5868.86 | 2.17 | |
Maximum of Months | 0.159020E+10 | 13115.57 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98243502.43 | 531.27 | 01-JAN-01:20 | 8.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 98243502.43 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 98243502.43 | 531.27 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.977592E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.831186E+09 | 1459.89 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.955956E+09 | 1075.94 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.821346E+09 | 918.38 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.867444E+09 | 894.69 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.857344E+09 | 873.60 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.805024E+09 | 846.59 | 12-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.907113E+09 | 897.00 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.841239E+09 | 1151.73 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.913375E+09 | 1177.76 | 24-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.958348E+09 | 1662.56 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.959881E+09 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106958E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.805024E+09 | 846.59 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.977592E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620700E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.532757E+09 | 946.05 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.612425E+09 | 684.92 | 06-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.529653E+09 | 597.80 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.561401E+09 | 550.45 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555902E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.521509E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.585823E+09 | 547.36 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.539607E+09 | 598.53 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.581918E+09 | 801.93 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.613211E+09 | 1071.42 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.608378E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.686328E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.521509E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.620700E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.944236E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.816646E+09 | 1446.84 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.948992E+09 | 925.17 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.822311E+09 | 914.53 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.872151E+09 | 899.72 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864783E+09 | 885.58 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.811386E+09 | 862.55 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.910669E+09 | 899.58 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.838451E+09 | 1126.23 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.888480E+09 | 1095.32 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.930851E+09 | 1662.60 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.921315E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105703E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.811386E+09 | 862.55 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.948992E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616004E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.529797E+09 | 921.08 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612366E+09 | 747.62 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.529909E+09 | 594.79 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.560211E+09 | 590.23 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.553417E+09 | 581.92 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.519090E+09 | 573.21 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.585220E+09 | 592.97 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.541411E+09 | 783.17 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.577980E+09 | 790.41 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.602963E+09 | 1071.42 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.602229E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.683060E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.519090E+09 | 573.21 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.616004E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.975473E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.829643E+09 | 1457.62 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.954401E+09 | 1068.22 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.820770E+09 | 912.40 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.867035E+09 | 887.41 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.856890E+09 | 865.14 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.804670E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.906478E+09 | 889.86 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.840262E+09 | 1145.35 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.910323E+09 | 1171.36 | 24-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.956480E+09 | 1662.56 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.956782E+09 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106792E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.804670E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.975473E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.619927E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.532175E+09 | 942.78 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.611892E+09 | 675.93 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.529348E+09 | 594.39 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.560966E+09 | 545.13 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555597E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.521280E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.585529E+09 | 542.17 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.539102E+09 | 595.47 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.580789E+09 | 794.70 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.612572E+09 | 1071.42 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.607548E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.685672E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.521280E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.619927E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.943446E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.816353E+09 | 1444.54 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.948271E+09 | 923.66 | 01-MAR-17:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.821836E+09 | 908.37 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.871502E+09 | 892.67 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864114E+09 | 877.70 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.810873E+09 | 853.36 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.910073E+09 | 892.56 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.837689E+09 | 1119.61 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.887499E+09 | 1088.31 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.930533E+09 | 1662.60 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.920879E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105631E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.810873E+09 | 853.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.948271E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615225E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.529316E+09 | 917.51 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.611454E+09 | 739.03 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.529453E+09 | 591.23 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.559766E+09 | 586.40 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.552909E+09 | 577.61 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.518745E+09 | 568.42 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.584881E+09 | 589.29 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540721E+09 | 775.35 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.576920E+09 | 783.01 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.602213E+09 | 1071.42 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.601197E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.682280E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.518745E+09 | 568.42 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.615225E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.975431E+09 | 1662.56 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.829612E+09 | 1457.20 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.954369E+09 | 1067.08 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.820710E+09 | 912.16 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.867021E+09 | 887.11 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.856860E+09 | 864.80 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.804661E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.906457E+09 | 889.58 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.840231E+09 | 1144.31 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.910233E+09 | 1170.41 | 24-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.956449E+09 | 1662.56 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.956740E+09 | 1662.56 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106788E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.804661E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.975431E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.619875E+09 | 1071.42 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.532142E+09 | 942.52 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.611880E+09 | 675.77 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.529226E+09 | 594.26 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.560956E+09 | 544.87 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555590E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.521273E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.585509E+09 | 541.90 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.539090E+09 | 595.32 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.580760E+09 | 794.18 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.612542E+09 | 1071.42 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.607512E+09 | 1071.42 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.685636E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.521273E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.619875E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.943433E+09 | 1662.60 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.816343E+09 | 1444.10 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.948254E+09 | 923.66 | 01-MAR-17:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.821792E+09 | 908.12 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.871484E+09 | 892.39 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864087E+09 | 877.39 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.810849E+09 | 853.00 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.910045E+09 | 892.29 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.837629E+09 | 1118.52 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.887458E+09 | 1087.22 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.930524E+09 | 1662.60 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.920841E+09 | 1662.60 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105627E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.810849E+09 | 853.00 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.948254E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615212E+09 | 1071.42 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.529304E+09 | 917.21 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.611423E+09 | 738.39 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.529443E+09 | 591.09 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.559755E+09 | 586.25 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.552881E+09 | 577.45 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.518735E+09 | 568.23 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.584872E+09 | 589.15 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540683E+09 | 774.78 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.576892E+09 | 782.44 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.602204E+09 | 1071.42 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.601182E+09 | 1071.42 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.682259E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.518735E+09 | 568.23 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.615212E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.977592E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110867.89 | 0.131317E+09 |
February | 0.136985E+10 | 0.831186E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20384.94 | 0.154631E+09 |
March | 0.163685E+10 | 0.955956E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 | 0.163086E+09 |
April | 0.145243E+10 | 0.821346E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118272.28 | 95053684.27 |
May | 0.157338E+10 | 0.867444E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 0.111563E+09 |
June | 0.156900E+10 | 0.857344E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12681.91 | 59697640.33 |
July | 0.145680E+10 | 0.805024E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 852967.24 | 42192004.80 |
August | 0.163685E+10 | 0.907113E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 894187.12 | 51313398.52 |
September | 0.145243E+10 | 0.841239E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1438965.89 | 52296721.89 |
October | 0.150991E+10 | 0.913375E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5000756.85 | 84308875.32 |
November | 0.149516E+10 | 0.958348E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253210.34 | 0.124366E+09 |
December | 0.145680E+10 | 0.959881E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83882.57 | 0.136664E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106958E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8786236.50 | 0.120649E+10 |
Minimum of Months | 0.136985E+10 | 0.805024E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 42192004.80 |
Maximum of Months | 0.163685E+10 | 0.977592E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5000756.85 | 0.163086E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.620700E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68596.00 | 88942733.27 |
February | 0.882782E+09 | 0.532757E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13589.24 | 0.103382E+09 |
March | 0.105485E+10 | 0.612425E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 0.108602E+09 |
April | 0.936002E+09 | 0.529653E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62506.43 | 63945822.89 |
May | 0.101394E+10 | 0.561401E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 76129663.03 |
June | 0.101113E+10 | 0.555902E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8450.93 | 40115075.73 |
July | 0.938820E+09 | 0.521509E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 565413.63 | 29072213.93 |
August | 0.105485E+10 | 0.585823E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 591201.63 | 34667243.29 |
September | 0.936002E+09 | 0.539607E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 958689.16 | 36136162.63 |
October | 0.973041E+09 | 0.581918E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3130030.81 | 56914253.44 |
November | 0.963541E+09 | 0.613211E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64512.62 | 82816349.54 |
December | 0.938820E+09 | 0.608378E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55035.23 | 90159755.50 |
Annual Sum or Average | 0.116768E+11 | 0.686328E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5518064.77 | 0.810883E+09 |
Minimum of Months | 0.882782E+09 | 0.521509E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 29072213.93 |
Maximum of Months | 0.105485E+10 | 0.620700E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3130030.81 | 0.108602E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.944236E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93721.53 | 0.136847E+09 |
February | 0.136988E+10 | 0.816646E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20376.12 | 0.158982E+09 |
March | 0.163688E+10 | 0.948992E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 | 0.164612E+09 |
April | 0.145246E+10 | 0.822311E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93713.94 | 97707929.70 |
May | 0.157341E+10 | 0.872151E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 0.110503E+09 |
June | 0.156904E+10 | 0.864783E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12682.41 | 58489031.34 |
July | 0.145684E+10 | 0.811386E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 848379.63 | 42445964.20 |
August | 0.163688E+10 | 0.910669E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 886544.13 | 53444001.42 |
September | 0.145246E+10 | 0.838451E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1412973.29 | 56548232.62 |
October | 0.150994E+10 | 0.888480E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4382285.58 | 90133160.15 |
November | 0.149520E+10 | 0.930851E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39360.84 | 0.131029E+09 |
December | 0.145684E+10 | 0.921315E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57831.07 | 0.143683E+09 |
Annual Sum or Average | 0.181198E+11 | 0.105703E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7847930.97 | 0.124443E+10 |
Minimum of Months | 0.136988E+10 | 0.811386E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 42445964.20 |
Maximum of Months | 0.163688E+10 | 0.948992E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4382285.58 | 0.164612E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.616004E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68595.14 | 94834306.86 |
February | 0.882782E+09 | 0.529797E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13589.57 | 0.115968E+09 |
March | 0.105485E+10 | 0.612366E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 0.121933E+09 |
April | 0.936002E+09 | 0.529909E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62508.40 | 74486544.31 |
May | 0.101394E+10 | 0.560211E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 83124985.12 |
June | 0.101113E+10 | 0.553417E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8453.29 | 45322659.34 |
July | 0.938820E+09 | 0.519090E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 565340.43 | 34670444.34 |
August | 0.105485E+10 | 0.585220E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 590760.29 | 43468507.76 |
September | 0.936002E+09 | 0.541411E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 956066.25 | 40823414.64 |
October | 0.973041E+09 | 0.577980E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3074349.36 | 65408119.10 |
November | 0.963541E+09 | 0.602963E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28696.35 | 95016216.25 |
December | 0.938820E+09 | 0.602229E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55038.24 | 0.105808E+09 |
Annual Sum or Average | 0.116768E+11 | 0.683060E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5423439.80 | 0.920863E+09 |
Minimum of Months | 0.882782E+09 | 0.519090E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 34670444.34 |
Maximum of Months | 0.105485E+10 | 0.616004E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3074349.36 | 0.121933E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.975473E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499793.55 | 0.269271E+09 |
February | 0.136985E+10 | 0.829643E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42995.85 | 0.317743E+09 |
March | 0.163685E+10 | 0.954401E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57239.47 | 0.343202E+09 |
April | 0.145243E+10 | 0.820770E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 705891.22 | 0.200187E+09 |
May | 0.157338E+10 | 0.867035E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246166E+09 |
June | 0.156900E+10 | 0.856890E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23726.50 | 0.132449E+09 |
July | 0.145680E+10 | 0.804670E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2022769.02 | 93604898.61 |
August | 0.163685E+10 | 0.906478E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2117029.38 | 0.115689E+09 |
September | 0.145243E+10 | 0.840262E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3319897.85 | 0.111933E+09 |
October | 0.150991E+10 | 0.910323E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12516661.10 | 0.175122E+09 |
November | 0.149516E+10 | 0.956480E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1366004.59 | 0.256266E+09 |
December | 0.145680E+10 | 0.956782E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 551935.78 | 0.272788E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106792E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23223944.31 | 0.253442E+10 |
Minimum of Months | 0.136985E+10 | 0.804670E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93604898.61 |
Maximum of Months | 0.163685E+10 | 0.975473E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12516661.10 | 0.343202E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.619927E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121174.68 | 0.191809E+09 |
February | 0.649041E+09 | 0.532175E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19960.54 | 0.224566E+09 |
March | 0.773965E+09 | 0.611892E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241762E+09 |
April | 0.688021E+09 | 0.529348E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119459.53 | 0.146854E+09 |
May | 0.744847E+09 | 0.560966E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176119E+09 |
June | 0.742030E+09 | 0.555597E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9451.56 | 94249247.39 |
July | 0.690839E+09 | 0.521280E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124625.70 | 71173505.06 |
August | 0.773965E+09 | 0.585529E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1127839.32 | 86758377.92 |
September | 0.688021E+09 | 0.539102E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2140769.81 | 82792403.78 |
October | 0.715730E+09 | 0.580789E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6979204.22 | 0.127071E+09 |
November | 0.708685E+09 | 0.612572E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154097.90 | 0.182214E+09 |
December | 0.690839E+09 | 0.607548E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88749.57 | 0.194985E+09 |
Annual Sum or Average | 0.858171E+10 | 0.685672E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11885332.83 | 0.182035E+10 |
Minimum of Months | 0.649041E+09 | 0.521280E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71173505.06 |
Maximum of Months | 0.773965E+09 | 0.619927E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6979204.22 | 0.241762E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.943446E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157267.40 | 0.312739E+09 |
February | 0.136988E+10 | 0.816353E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42834.00 | 0.358112E+09 |
March | 0.163688E+10 | 0.948271E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369319E+09 |
April | 0.145246E+10 | 0.821836E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207506.15 | 0.219916E+09 |
May | 0.157341E+10 | 0.871502E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251351E+09 |
June | 0.156904E+10 | 0.864114E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23727.10 | 0.131642E+09 |
July | 0.145684E+10 | 0.810873E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1967305.68 | 96366234.35 |
August | 0.163688E+10 | 0.910073E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1943763.42 | 0.126115E+09 |
September | 0.145246E+10 | 0.837689E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3199381.19 | 0.131239E+09 |
October | 0.150994E+10 | 0.887499E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9879904.07 | 0.206325E+09 |
November | 0.149520E+10 | 0.930533E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76294.72 | 0.297835E+09 |
December | 0.145684E+10 | 0.920879E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100965.07 | 0.324102E+09 |
Annual Sum or Average | 0.181198E+11 | 0.105631E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17598948.80 | 0.282506E+10 |
Minimum of Months | 0.136988E+10 | 0.810873E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96366234.35 |
Maximum of Months | 0.163688E+10 | 0.948271E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9879904.07 | 0.369319E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.615225E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170858.40 | 0.195177E+09 |
February | 0.882782E+09 | 0.529316E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28663.62 | 0.232610E+09 |
March | 0.105485E+10 | 0.611454E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.39 | 0.247104E+09 |
April | 0.936002E+09 | 0.529453E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234461.26 | 0.154073E+09 |
May | 0.101394E+10 | 0.559766E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183311E+09 |
June | 0.101113E+10 | 0.552909E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15816.69 | 98332152.69 |
July | 0.938820E+09 | 0.518745E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1268480.47 | 75159766.17 |
August | 0.105485E+10 | 0.584881E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298211.95 | 92272311.80 |
September | 0.936002E+09 | 0.540721E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203332.51 | 88938341.03 |
October | 0.973041E+09 | 0.576920E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466771.20 | 0.134304E+09 |
November | 0.963541E+09 | 0.602213E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 460979.04 | 0.189530E+09 |
December | 0.938820E+09 | 0.601197E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118875.53 | 0.202555E+09 |
Annual Sum or Average | 0.116768E+11 | 0.682280E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13266830.06 | 0.189337E+10 |
Minimum of Months | 0.882782E+09 | 0.518745E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75159766.17 |
Maximum of Months | 0.105485E+10 | 0.615225E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466771.20 | 0.247104E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.975431E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 964829.03 | 0.292859E+09 |
February | 0.136985E+10 | 0.829612E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63631.21 | 0.347434E+09 |
March | 0.163685E+10 | 0.954369E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119158.08 | 0.390452E+09 |
April | 0.145243E+10 | 0.820710E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1044561.87 | 0.236941E+09 |
May | 0.157338E+10 | 0.867021E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291944E+09 |
June | 0.156900E+10 | 0.856860E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22832.96 | 0.162953E+09 |
July | 0.145680E+10 | 0.804661E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2331952.08 | 0.118440E+09 |
August | 0.163685E+10 | 0.906457E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434641.28 | 0.143249E+09 |
September | 0.145243E+10 | 0.840231E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4044721.72 | 0.134694E+09 |
October | 0.150991E+10 | 0.910233E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15084767.86 | 0.202306E+09 |
November | 0.149516E+10 | 0.956449E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2153214.36 | 0.285652E+09 |
December | 0.145680E+10 | 0.956740E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2044138.44 | 0.298037E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106788E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30308448.90 | 0.290496E+10 |
Minimum of Months | 0.136985E+10 | 0.804661E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118440E+09 |
Maximum of Months | 0.163685E+10 | 0.975431E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15084767.86 | 0.390452E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.619875E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265551.48 | 0.210788E+09 |
February | 0.882782E+09 | 0.532142E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31609.05 | 0.248167E+09 |
March | 0.105485E+10 | 0.611880E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277182E+09 |
April | 0.936002E+09 | 0.529226E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161628.84 | 0.175223E+09 |
May | 0.101394E+10 | 0.560956E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210299E+09 |
June | 0.101113E+10 | 0.555590E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15216.84 | 0.115458E+09 |
July | 0.938820E+09 | 0.521273E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1469313.97 | 88991189.68 |
August | 0.105485E+10 | 0.585509E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1498262.11 | 0.107074E+09 |
September | 0.936002E+09 | 0.539090E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2693774.86 | 0.100034E+09 |
October | 0.973041E+09 | 0.580760E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8667609.52 | 0.148338E+09 |
November | 0.963541E+09 | 0.612542E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 320236.19 | 0.206039E+09 |
December | 0.938820E+09 | 0.607512E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 203535.91 | 0.215453E+09 |
Annual Sum or Average | 0.116768E+11 | 0.685636E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15326738.77 | 0.210305E+10 |
Minimum of Months | 0.882782E+09 | 0.521273E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88991189.68 |
Maximum of Months | 0.105485E+10 | 0.619875E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8667609.52 | 0.277182E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.943433E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 235811.67 | 0.353290E+09 |
February | 0.136988E+10 | 0.816343E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47390.22 | 0.404674E+09 |
March | 0.163688E+10 | 0.948254E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426990E+09 |
April | 0.145246E+10 | 0.821792E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 247758.12 | 0.262858E+09 |
May | 0.157341E+10 | 0.871484E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299038E+09 |
June | 0.156904E+10 | 0.864087E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22833.68 | 0.161998E+09 |
July | 0.145684E+10 | 0.810849E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2269030.90 | 0.121677E+09 |
August | 0.163688E+10 | 0.910045E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2247297.79 | 0.156274E+09 |
September | 0.145246E+10 | 0.837629E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3939838.30 | 0.159804E+09 |
October | 0.150994E+10 | 0.887458E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12180158.60 | 0.244939E+09 |
November | 0.149520E+10 | 0.930524E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95645.63 | 0.345123E+09 |
December | 0.145684E+10 | 0.920841E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154558.66 | 0.370566E+09 |
Annual Sum or Average | 0.181198E+11 | 0.105627E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21440323.56 | 0.330723E+10 |
Minimum of Months | 0.136988E+10 | 0.810849E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121677E+09 |
Maximum of Months | 0.163688E+10 | 0.948254E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12180158.60 | 0.426990E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.615212E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 279054.45 | 0.220686E+09 |
February | 0.882782E+09 | 0.529304E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31674.75 | 0.264255E+09 |
March | 0.105485E+10 | 0.611423E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10985.75 | 0.288139E+09 |
April | 0.936002E+09 | 0.529443E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 341260.74 | 0.185911E+09 |
May | 0.101394E+10 | 0.559755E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221125E+09 |
June | 0.101113E+10 | 0.552881E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15220.57 | 0.121110E+09 |
July | 0.938820E+09 | 0.518735E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1475131.48 | 93932324.46 |
August | 0.105485E+10 | 0.584872E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1504870.90 | 0.114063E+09 |
September | 0.936002E+09 | 0.540683E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2686199.68 | 0.108627E+09 |
October | 0.973041E+09 | 0.576892E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9077591.76 | 0.159360E+09 |
November | 0.963541E+09 | 0.602204E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 693825.15 | 0.218883E+09 |
December | 0.938820E+09 | 0.601182E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 272473.03 | 0.229827E+09 |
Annual Sum or Average | 0.116768E+11 | 0.682259E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16388288.24 | 0.222592E+10 |
Minimum of Months | 0.882782E+09 | 0.518735E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93932324.46 |
Maximum of Months | 0.105485E+10 | 0.615212E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9077591.76 | 0.288139E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116447.58 | 0.288460E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21751.39 | 0.334865E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349854E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143710.29 | 0.205604E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237667E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3068.49 | 0.127027E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147280.10 | 92485975.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085186.88 | 0.116144E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2521132.85 | 0.114836E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8983985.81 | 0.185706E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251454.02 | 0.272353E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57445.27 | 0.299412E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14331462.67 | 0.262441E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92485975.90 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8983985.81 | 0.349854E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307938.93 | 0.489695E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44343.03 | 0.572562E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602561E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453746.20 | 0.351301E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416253E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5140.39 | 0.221172E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2161435.97 | 0.160362E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2020649.59 | 0.204043E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4533724.00 | 0.198991E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17175622.52 | 0.317820E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960819.33 | 0.466527E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174532.10 | 0.505565E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27837952.07 | 0.450685E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160362E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17175622.52 | 0.602561E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592161.43 | 0.478425E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10798.31 | 0.570412E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631432E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88479.86 | 0.400031E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475715E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271329E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017831.89 | 0.210074E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759931.28 | 0.244844E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4602617.54 | 0.235238E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16547309.77 | 0.335299E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016606.38 | 0.470432E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215796.11 | 0.491667E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24851532.57 | 0.481490E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210074E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16547309.77 | 0.631432E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 14-JAN-11:00 | 341.81 | 02-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1459.89 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 01-FEB-12:00 | 297.13 | 12-FEB-19:00 |
March | 2010.79 | 01-MAR-10:09 | 1075.94 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 314.20 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 918.38 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 | 30-APR-10:53 | 193.66 | 17-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 894.69 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 173.88 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 873.60 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 29-JUN-11:00 | 125.17 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 846.59 | 12-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 31-JUL-13:00 | 99.14 | 09-JUL-17:30 |
August | 2010.79 | 01-AUG-09:09 | 897.00 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 17-AUG-14:00 | 90.11 | 21-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 1151.73 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 29-SEP-14:00 | 101.48 | 04-SEP-17:30 |
October | 2010.79 | 02-OCT-09:09 | 1177.76 | 24-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 15-OCT-09:00 | 207.85 | 11-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 19-NOV-12:51 | 275.57 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 05-DEC-10:00 | 251.40 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 846.59 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 90.11 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 341.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 14-JAN-11:00 | 230.08 | 02-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 946.05 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 01-FEB-12:00 | 190.15 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 684.92 | 06-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 203.27 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 597.80 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 26-APR-13:00 | 126.35 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 550.45 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 114.96 | 27-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 29-JUN-11:00 | 81.39 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 31-JUL-13:00 | 63.80 | 04-JUL-14:20 |
August | 1295.83 | 01-AUG-09:09 | 547.36 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 17-AUG-14:00 | 58.66 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 598.53 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 29-SEP-14:00 | 82.50 | 03-SEP-06:40 |
October | 1295.83 | 02-OCT-09:09 | 801.93 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.81 | 15-OCT-12:34 | 138.10 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 19-NOV-12:51 | 184.16 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 05-DEC-10:00 | 163.54 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 64.81 | 230.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 14-JAN-11:00 | 310.31 | 02-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1446.84 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 01-FEB-12:00 | 285.38 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 925.17 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 309.11 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 914.53 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 26-APR-13:00 | 191.13 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 899.72 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 166.88 | 27-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 885.58 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 29-JUN-11:00 | 123.25 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 862.55 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 31-JUL-13:00 | 95.28 | 09-JUL-16:52 |
August | 2010.83 | 01-AUG-09:09 | 899.58 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 17-AUG-14:00 | 92.33 | 27-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 1126.23 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.16 | 29-SEP-14:00 | 124.65 | 03-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1095.32 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.69 | 15-OCT-12:55 | 213.80 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 18-NOV-13:10 | 280.12 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 05-DEC-10:00 | 254.72 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 862.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 92.33 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 92.69 | 310.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 14-JAN-11:00 | 229.46 | 02-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 921.08 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 01-FEB-12:00 | 225.31 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 747.62 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 233.17 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 594.79 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 26-APR-13:00 | 158.76 | 16-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 590.23 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 147.20 | 29-MAY-16:10 |
June | 1295.83 | 01-JUN-09:09 | 581.92 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 29-JUN-11:00 | 108.85 | 04-JUN-16:50 |
July | 1295.83 | 03-JUL-09:09 | 573.21 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 31-JUL-13:00 | 97.28 | 09-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 592.97 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 17-AUG-14:00 | 84.46 | 27-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 783.17 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 29-SEP-14:00 | 106.76 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 790.41 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.09 | 15-OCT-12:33 | 161.46 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 | 18-NOV-13:00 | 213.15 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 05-DEC-10:00 | 189.60 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 573.21 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.46 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 64.09 | 233.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 15-JAN-10:00 | 588.42 | 02-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1457.62 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 01-FEB-12:00 | 608.23 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 1068.22 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 11-MAR-13:05 | 659.08 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 912.40 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 | 30-APR-11:07 | 406.14 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 887.41 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 391.30 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 865.14 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 29-JUN-11:00 | 272.88 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.88 | 23-JUL-10:55 | 219.77 | 16-JUL-18:00 |
August | 2010.79 | 01-AUG-09:09 | 889.86 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 06-AUG-12:53 | 194.28 | 21-AUG-23:55 |
September | 2010.79 | 01-SEP-09:09 | 1145.35 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | 29-SEP-14:00 | 214.54 | 24-SEP-15:10 |
October | 2010.79 | 02-OCT-09:09 | 1171.36 | 24-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.93 | 15-OCT-08:52 | 424.64 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.05 | 19-NOV-12:51 | 560.32 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.28 | 25-DEC-11:52 | 529.12 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.28 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 273.93 | 659.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 15-JAN-14:20 | 408.23 | 02-JAN-03:00 |
February | 1239.33 | 01-FEB-08:09 | 942.78 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 01-FEB-12:00 | 405.14 | 25-FEB-03:00 |
March | 1239.33 | 01-MAR-08:09 | 675.93 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 439.45 | 28-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 594.39 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 26-APR-13:00 | 275.85 | 21-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 545.13 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 273.09 | 29-MAY-12:55 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 29-JUN-11:00 | 187.30 | 04-JUN-14:10 |
July | 1239.33 | 03-JUL-07:10 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 31-JUL-13:00 | 158.88 | 16-JUL-18:00 |
August | 1239.33 | 01-AUG-07:10 | 542.17 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 17-AUG-14:10 | 132.23 | 27-AUG-18:20 |
September | 1239.33 | 01-SEP-07:10 | 595.47 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.91 | 29-SEP-14:10 | 191.06 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 794.70 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.10 | 15-OCT-12:45 | 295.55 | 30-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 19-NOV-12:51 | 387.19 | 23-NOV-07:00 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 05-DEC-10:00 | 358.73 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.23 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 152.10 | 439.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 14-JAN-11:00 | 634.15 | 02-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1444.54 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 | 01-FEB-12:00 | 635.72 | 20-FEB-14:50 |
March | 2010.83 | 01-MAR-10:09 | 923.66 | 01-MAR-17:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 671.70 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 908.37 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 26-APR-13:00 | 423.61 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 892.67 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 387.47 | 29-MAY-12:55 |
June | 2010.83 | 01-JUN-09:09 | 877.70 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 29-JUN-11:00 | 272.44 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 853.36 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 | 31-JUL-13:00 | 215.13 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 892.56 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 17-AUG-14:00 | 199.91 | 21-AUG-23:55 |
September | 2010.83 | 01-SEP-09:09 | 1119.61 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.44 | 29-SEP-14:00 | 305.34 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1088.31 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.91 | 15-OCT-12:59 | 483.68 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 18-NOV-14:00 | 612.53 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 05-DEC-10:00 | 567.34 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 853.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.91 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 212.91 | 671.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 14-JAN-11:00 | 412.86 | 02-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 917.51 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 01-FEB-12:00 | 419.86 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 739.03 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 11-MAR-11:00 | 460.61 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 591.23 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | 30-APR-11:10 | 361.48 | 16-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 586.40 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 346.33 | 29-MAY-16:00 |
June | 1295.83 | 01-JUN-09:09 | 577.61 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 29-JUN-11:00 | 246.36 | 04-JUN-16:50 |
July | 1295.83 | 03-JUL-09:09 | 568.42 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 31-JUL-13:00 | 223.05 | 16-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 589.29 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 17-AUG-14:00 | 170.01 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 775.35 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 | 29-SEP-14:00 | 247.88 | 03-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 783.01 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.25 | 15-OCT-08:52 | 310.79 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 19-NOV-12:02 | 400.39 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 05-DEC-10:00 | 371.67 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 568.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.01 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 168.25 | 460.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.70 | 15-JAN-10:00 | 647.85 | 27-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1457.20 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 01-FEB-12:00 | 683.30 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 1067.08 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 12-MAR-10:00 | 783.40 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 912.16 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 | 30-APR-11:00 | 479.15 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 887.11 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 482.32 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 864.80 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 29-JUN-11:00 | 332.79 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 31-JUL-13:00 | 276.61 | 09-JUL-17:30 |
August | 2010.79 | 01-AUG-09:09 | 889.58 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 | 06-AUG-12:32 | 237.78 | 27-AUG-18:10 |
September | 2010.79 | 01-SEP-09:09 | 1144.31 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.29 | 29-SEP-14:00 | 279.38 | 04-SEP-18:00 |
October | 2010.79 | 02-OCT-09:09 | 1170.41 | 24-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.56 | 15-OCT-08:52 | 480.28 | 11-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.65 | 19-NOV-12:53 | 603.95 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.25 | 25-DEC-12:00 | 602.63 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.78 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 353.56 | 783.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 15-JAN-10:00 | 440.62 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 942.52 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 01-FEB-12:00 | 456.04 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 675.77 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 522.10 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 594.26 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 26-APR-13:00 | 330.17 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 544.87 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 343.10 | 29-MAY-12:55 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 244.22 | 04-JUN-14:10 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 31-JUL-13:00 | 205.23 | 04-JUL-14:00 |
August | 1295.83 | 01-AUG-09:09 | 541.90 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 17-AUG-14:00 | 177.80 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 595.32 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 29-SEP-14:00 | 214.04 | 03-SEP-17:55 |
October | 1295.83 | 02-OCT-09:09 | 794.18 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.57 | 15-OCT-12:24 | 333.93 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 | 19-NOV-13:00 | 415.32 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 25-DEC-12:00 | 410.99 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 179.57 | 522.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 15-JAN-10:00 | 714.01 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 1444.10 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 01-FEB-12:00 | 795.57 | 20-FEB-15:00 |
March | 2010.83 | 01-MAR-10:09 | 923.66 | 01-MAR-17:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 786.73 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 908.12 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 | 26-APR-13:00 | 512.52 | 16-APR-18:00 |
May | 2010.83 | 01-MAY-09:09 | 892.39 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 479.54 | 29-MAY-12:55 |
June | 2010.83 | 01-JUN-09:09 | 877.39 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 29-JUN-11:00 | 332.48 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 853.00 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 31-JUL-13:00 | 280.44 | 09-JUL-16:52 |
August | 2010.83 | 01-AUG-09:09 | 892.29 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 | 17-AUG-14:00 | 265.34 | 27-AUG-18:10 |
September | 2010.83 | 01-SEP-09:09 | 1118.52 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.76 | 29-SEP-14:00 | 371.65 | 04-SEP-13:50 |
October | 2010.83 | 02-OCT-09:09 | 1087.22 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.31 | 15-OCT-12:47 | 551.43 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | 18-NOV-13:05 | 678.03 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 05-DEC-10:00 | 657.04 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 853.00 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.34 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 254.31 | 795.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 | 15-JAN-10:00 | 458.20 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 917.21 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 01-FEB-12:00 | 480.18 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 738.39 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 11-MAR-11:05 | 535.91 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 591.09 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 30-APR-10:57 | 456.04 | 16-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 586.25 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 435.97 | 29-MAY-16:00 |
June | 1295.83 | 01-JUN-09:09 | 577.45 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 312.05 | 04-JUN-16:50 |
July | 1295.83 | 03-JUL-09:09 | 568.23 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 31-JUL-13:00 | 278.51 | 09-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 589.15 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 17-AUG-14:00 | 227.22 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 774.78 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 29-SEP-14:00 | 305.44 | 03-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 782.44 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.86 | 15-OCT-08:52 | 362.16 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 | 19-NOV-12:22 | 445.94 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 25-DEC-12:00 | 431.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 568.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.22 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 216.86 | 535.91 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 14-JAN-11:00 | 744.43 | 02-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 01-FEB-12:00 | 640.49 | 12-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 673.32 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 26-APR-13:00 | 415.20 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 374.04 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 29-JUN-11:00 | 262.64 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 31-JUL-13:00 | 197.21 | 02-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 | 17-AUG-14:00 | 188.66 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.84 | 29-SEP-13:50 | 226.46 | 04-SEP-17:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.08 | 15-OCT-13:00 | 448.67 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.51 | 19-NOV-13:00 | 614.47 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 05-DEC-10:00 | 546.87 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.66 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.08 | 744.43 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 | 15-JAN-10:00 | 1107.94 | 02-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 | 01-FEB-12:00 | 1102.91 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1166.05 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 | 30-APR-10:53 | 700.10 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 667.66 | 27-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 29-JUN-11:00 | 459.41 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 | 23-JUL-11:00 | 340.15 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.25 | 06-AUG-12:53 | 331.19 | 21-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.55 | 29-SEP-13:50 | 378.92 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.10 | 15-OCT-13:00 | 764.87 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.32 | 19-NOV-13:00 | 1063.37 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 05-DEC-10:00 | 954.63 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.10 | 1166.05 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.78 | 15-JAN-10:00 | 1018.60 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | 01-FEB-12:00 | 1098.14 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1236.96 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 | 26-APR-13:00 | 778.20 | 16-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 794.52 | 20-MAY-17:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 558.28 | 04-JUN-14:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 31-JUL-13:00 | 498.77 | 09-JUL-16:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | 17-AUG-14:00 | 407.71 | 27-AUG-17:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.93 | 29-SEP-13:30 | 483.04 | 03-SEP-17:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.43 | 15-OCT-08:52 | 769.48 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.91 | 19-NOV-13:00 | 960.65 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 | 04-DEC-10:00 | 969.54 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.71 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.43 | 1236.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 105631.20 | 02-JAN-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96910.23 | 27-FEB-07:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99149.42 | 20-MAR-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99705.46 | 10-APR-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97299.08 | 30-MAY-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93151.47 | 12-JUN-06:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 90501.07 | 05-JUL-06:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90178.55 | 28-AUG-06:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91689.89 | 20-SEP-06:11 | 25133.15 | 34402.75 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101024.63 | 16-OCT-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97721.79 | 13-NOV-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99174.58 | 26-DEC-07:05 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90178.55 | 7180.90 | 9829.36 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105631.20 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90763.26 | 02-JAN-05:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86618.65 | 21-FEB-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84381.88 | 13-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84327.97 | 17-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83940.40 | 30-MAY-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84972.56 | 12-JUN-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83760.19 | 13-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83023.00 | 23-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88160.34 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88502.46 | 16-OCT-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88952.34 | 13-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86897.88 | 11-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 83023.00 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90763.26 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 73422.41 | 18-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72993.39 | 02-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73921.22 | 23-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74212.64 | 25-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74153.81 | 23-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74193.29 | 01-JUN-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74523.15 | 20-JUL-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74358.71 | 22-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74188.03 | 25-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75315.64 | 17-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74103.90 | 21-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73107.66 | 07-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72993.39 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75315.64 | 8061.19 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34434.13 | 18-JAN-15:00 | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34756.48 | 02-FEB-15:00 | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39278.67 | 24-MAR-05:03 | 4836.72 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68011.54 | 27-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68296.19 | 04-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69915.93 | 28-JUN-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70189.01 | 26-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70778.88 | 10-AUG-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70165.92 | 25-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71359.72 | 02-OCT-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57787.93 | 01-NOV-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34371.42 | 19-DEC-15:00 | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 34371.42 | 0.00 | 1612.08 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71359.72 | 16014.58 | 13241.18 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5953.90 | 17-JAN-13:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 |
February | 5130.12 | 21-FEB-13:10 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
March | 5975.70 | 13-MAR-13:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 |
April | 7060.14 | 26-APR-13:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 0.00 |
May | 6842.25 | 04-MAY-13:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 |
June | 10506.19 | 19-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 |
July | 10526.53 | 05-JUL-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10540.88 | 21-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 |
September | 10765.89 | 06-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
October | 11033.49 | 03-OCT-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.89 |
November | 5772.66 | 13-NOV-11:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
December | 6078.31 | 05-DEC-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5130.12 | 0.00 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11033.49 | 3846.22 | 1582.09 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 28.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7160.00 | 20-JAN-09:00 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11289.59 | 20-FEB-09:13 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.86 |
March | 11210.13 | 19-MAR-08:13 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.45 |
April | 17616.65 | 30-APR-09:53 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 |
May | 17680.79 | 28-MAY-08:53 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 |
June | 17793.27 | 18-JUN-07:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 |
July | 18577.56 | 23-JUL-08:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
August | 18418.85 | 06-AUG-08:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 |
September | 18509.40 | 10-SEP-08:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 |
October | 18974.01 | 15-OCT-08:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
November | 10438.75 | 19-NOV-08:23 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 |
December | 7752.06 | 05-DEC-08:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7160.00 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18974.01 | 1239.33 | 509.78 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 76.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21281.03 | 29-JAN-11:22 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.08 |
February | 20723.22 | 19-FEB-11:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.80 |
March | 20738.98 | 19-MAR-12:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.92 |
April | 17163.78 | 09-APR-13:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.10 |
May | 8932.44 | 04-MAY-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
June | 8008.50 | 30-JUN-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
July | 15551.07 | 30-JUL-13:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 |
August | 15634.88 | 20-AUG-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 |
September | 20265.72 | 10-SEP-12:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 |
October | 22674.31 | 15-OCT-11:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 | 0.00 |
November | 21898.68 | 23-NOV-12:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 |
December | 22599.26 | 25-DEC-13:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8008.50 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22674.31 | 1923.15 | 791.06 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 | 140.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11541.93 | 22-JAN-15:13 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.40 |
February | 18156.95 | 05-FEB-15:23 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 |
March | 22261.13 | 19-MAR-15:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.73 |
April | 23203.69 | 30-APR-15:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 |
May | 23761.56 | 21-MAY-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.84 |
June | 22590.85 | 18-JUN-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
July | 23459.81 | 23-JUL-16:11 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
August | 23723.99 | 06-AUG-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 |
September | 23834.78 | 10-SEP-15:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.72 |
October | 23880.46 | 15-OCT-13:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 0.00 |
November | 22369.21 | 23-NOV-13:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
December | 23469.47 | 25-DEC-14:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11541.93 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23880.46 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 85.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4058.97 | 18-JAN-14:20 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
February | 3435.50 | 03-FEB-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
March | 4082.51 | 23-MAR-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 |
April | 5510.58 | 26-APR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 0.00 |
May | 6075.82 | 04-MAY-13:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 |
June | 5828.68 | 29-JUN-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
July | 6436.56 | 19-JUL-14:40 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
August | 6370.87 | 17-AUG-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 0.00 |
September | 7572.20 | 30-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
October | 7716.72 | 02-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 |
November | 3678.10 | 01-NOV-13:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 |
December | 4029.76 | 05-DEC-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3435.50 | 1012.16 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7716.72 | 2010.79 | 791.05 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 38.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6566.12 | 20-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
February | 6616.89 | 21-FEB-09:30 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
March | 12874.44 | 19-MAR-08:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 |
April | 18098.40 | 30-APR-10:13 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 |
May | 18148.11 | 28-MAY-09:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.25 |
June | 18926.90 | 25-JUN-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.59 |
July | 19271.43 | 23-JUL-08:62 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 |
August | 18835.32 | 20-AUG-09:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 |
September | 18125.08 | 03-SEP-08:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 |
October | 15459.23 | 15-OCT-08:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 113.06 | 0.00 |
November | 6235.57 | 19-NOV-09:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 |
December | 6503.80 | 05-DEC-09:20 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6235.57 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19271.43 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 113.06 | 127.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20474.23 | 22-JAN-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.81 |
February | 19924.48 | 05-FEB-12:13 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.19 |
March | 19896.13 | 19-MAR-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.11 |
April | 11515.48 | 26-APR-13:05 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 | 0.00 |
May | 8312.20 | 04-MAY-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
June | 7156.09 | 30-JUN-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 |
July | 10214.12 | 31-JUL-12:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 32.60 | 0.00 |
August | 12740.45 | 30-AUG-13:00 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
September | 19605.92 | 04-SEP-12:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.62 |
October | 21487.30 | 01-OCT-12:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.99 |
November | 20602.39 | 05-NOV-11:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.37 |
December | 21437.10 | 24-DEC-13:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7156.09 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21487.30 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 32.60 | 325.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8182.10 | 26-JAN-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.92 |
February | 10402.98 | 20-FEB-16:53 | 195.68 | 84.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.86 |
March | 19149.56 | 19-MAR-16:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.61 |
April | 20048.92 | 16-APR-15:52 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.17 |
May | 19877.60 | 14-MAY-16:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.37 |
June | 19288.28 | 25-JUN-16:42 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 |
July | 21324.71 | 04-JUL-16:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21466.55 | 20-AUG-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.16 |
September | 20455.83 | 03-SEP-15:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.34 |
October | 20580.36 | 01-OCT-15:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.51 |
November | 8673.98 | 07-NOV-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 |
December | 8636.70 | 18-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8182.10 | 195.68 | 84.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21466.55 | 1239.33 | 509.78 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3720.14 | 18-JAN-14:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
February | 3155.80 | 16-FEB-14:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
March | 4168.52 | 23-MAR-15:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 |
April | 5993.71 | 26-APR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
May | 6611.09 | 04-MAY-13:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 |
June | 6436.59 | 30-JUN-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
July | 7203.96 | 19-JUL-14:50 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 | 0.00 |
August | 6984.01 | 17-AUG-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 0.00 |
September | 9658.50 | 30-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 8081.10 | 16-OCT-13:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.18 | 0.00 |
November | 3446.35 | 10-NOV-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 |
December | 3662.09 | 05-DEC-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3155.80 | 1012.16 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9658.50 | 4021.58 | 1582.09 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 106.18 | 60.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5144.47 | 20-JAN-09:40 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 |
February | 5080.93 | 02-FEB-10:10 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
March | 8072.35 | 23-MAR-09:30 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 |
April | 16939.57 | 30-APR-10:02 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.56 |
May | 15450.09 | 28-MAY-09:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.71 |
June | 17936.76 | 25-JUN-10:02 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.14 |
July | 18240.48 | 30-JUL-09:02 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 |
August | 18840.91 | 06-AUG-08:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.46 |
September | 18627.69 | 10-SEP-09:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.45 |
October | 19203.49 | 15-OCT-09:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 116.11 | 0.00 |
November | 4666.13 | 01-NOV-09:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.98 |
December | 5203.74 | 05-DEC-09:50 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4666.13 | 260.91 | 113.28 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19203.49 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 116.11 | 157.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21411.76 | 22-JAN-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.75 |
February | 22136.32 | 20-FEB-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.89 |
March | 16016.30 | 19-MAR-11:43 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.95 |
April | 15151.39 | 30-APR-14:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.25 |
May | 8799.54 | 04-MAY-12:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
June | 7762.58 | 30-JUN-13:10 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
July | 13229.16 | 30-JUL-14:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.56 |
August | 13267.35 | 30-AUG-13:05 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
September | 21072.20 | 10-SEP-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.88 |
October | 24084.46 | 15-OCT-14:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 52.73 | 0.00 |
November | 22543.71 | 23-NOV-13:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.90 |
December | 22820.87 | 25-DEC-13:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7762.58 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24084.46 | 4021.67 | 1582.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 52.73 | 594.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7936.48 | 18-JAN-15:00 | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
February | 10293.50 | 20-FEB-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.68 |
March | 12669.85 | 19-MAR-16:23 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.67 |
April | 21957.91 | 30-APR-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.59 |
May | 20617.42 | 29-MAY-17:22 | 0.00 | 141.60 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.48 |
June | 20589.07 | 18-JUN-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.68 |
July | 22605.80 | 30-JUL-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.15 |
August | 22146.98 | 27-AUG-15:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.28 |
September | 22002.30 | 04-SEP-15:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.92 |
October | 23049.39 | 15-OCT-15:41 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 | 0.00 |
November | 8417.19 | 10-NOV-14:50 | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 |
December | 8331.64 | 19-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7936.48 | 0.00 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23049.39 | 1295.83 | 509.78 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 | 315.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8785.88 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.74 |
February | 7286.13 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.46 |
March | 6816.41 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 |
April | 6995.88 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 |
May | 7248.71 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7170.15 | 05-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
July | 8891.01 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8621.27 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 |
September | 9613.03 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12190.36 | 16-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 |
November | 8150.62 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 |
December | 7893.60 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6816.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12190.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3292.84 | 21-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3268.94 | 03-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.63 |
March | 3487.87 | 23-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
April | 4188.81 | 27-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 |
May | 3997.25 | 04-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 |
June | 4519.82 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 |
July | 5041.19 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 0.00 |
August | 5073.51 | 18-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 0.00 |
September | 5195.72 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 | 0.00 |
October | 8054.29 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 |
November | 3426.90 | 14-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.73 |
December | 3430.41 | 21-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3268.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8054.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 | 132.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7435.16 | 18-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 |
February | 7255.56 | 01-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.20 |
March | 10637.19 | 23-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 |
April | 14183.07 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 0.00 |
May | 13224.72 | 03-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 |
June | 13326.52 | 30-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 |
July | 14952.69 | 19-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 | 0.00 |
August | 14531.58 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
September | 14375.62 | 29-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.72 | 0.00 |
October | 18607.68 | 16-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.93 | 0.00 |
November | 7077.66 | 10-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.63 |
December | 6727.82 | 05-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6727.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18607.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.72 | 99.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2069.56 | 30-JAN-16:50 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4154.30 | 20-FEB-16:53 | 35.07 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7020.42 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7942.41 | 30-APR-17:22 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3297.74 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5332.88 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7211.83 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8047.70 | 06-AUG-17:42 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3548.05 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5311.72 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5991.49 | 12-NOV-16:20 | 23.38 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8018.45 | 25-DEC-16:20 | 23.38 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2069.56 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8047.70 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1896.45 | 30-JAN-16:50 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3821.34 | 22-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6372.60 | 31-MAR-23:30 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7378.50 | 30-APR-17:22 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2987.33 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5041.86 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6889.69 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7496.66 | 06-AUG-17:55 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3304.00 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4936.66 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5571.50 | 07-NOV-16:30 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7378.30 | 18-DEC-16:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1896.45 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7496.66 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1829.52 | 26-JAN-16:10 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3810.74 | 22-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6037.43 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7453.86 | 30-APR-17:35 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2739.15 | 31-MAY-23:40 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4927.39 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6796.05 | 31-JUL-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7642.59 | 06-AUG-17:50 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3268.69 | 30-SEP-23:50 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4735.70 | 31-OCT-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5555.58 | 07-NOV-16:20 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7378.18 | 19-DEC-16:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1829.52 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7642.59 | 222.14 | 316.63 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92177.23 | 02-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183070.99 | 21-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357753.12 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366206.62 | 26-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175004.29 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266714.09 | 30-JUN-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358826.63 | 31-JUL-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368328.60 | 14-AUG-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176122.05 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267575.31 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275625.16 | 13-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367277.71 | 26-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92177.23 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368328.60 | 4808.68 | 4157.19 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.160701E+13 | 1352955.92 | 18-JAN-11:00 | 0.168003E+11 | 322456.12 | 03-JAN-07:10 |
February | 0.172954E+13 | 1491163.26 | 03-FEB-15:09 | 0.450146E+10 | 139112.11 | 09-FEB-07:10 |
March | 0.228313E+13 | 1626901.39 | 23-MAR-15:39 | 0.125060E+11 | 241228.73 | 30-MAR-06:10 |
April | 0.256804E+13 | 1812564.89 | 26-APR-10:39 | 0.490059E+09 | 130829.24 | 01-APR-06:10 |
May | 0.158789E+13 | 1290998.32 | 03-MAY-14:30 | 0.104060E+09 | 100412.64 | 09-MAY-09:39 |
June | 0.195944E+13 | 1503574.49 | 28-JUN-10:00 | 1211.52 | 2.02 | 28-JUN-13:00 |
July | 0.249349E+13 | 1787330.83 | 31-JUL-14:09 | 8223.31 | 2.04 | 21-JUL-13:50 |
August | 0.306992E+13 | 1958493.27 | 07-AUG-10:30 | 44034.16 | 4.06 | 15-AUG-11:20 |
September | 0.161998E+13 | 1397810.57 | 29-SEP-15:00 | 1248.55 | 2.08 | 13-SEP-09:00 |
October | 0.211533E+13 | 1595894.17 | 16-OCT-10:00 | 97811494.80 | 34540.90 | 12-OCT-06:10 |
November | 0.225738E+13 | 1661890.85 | 28-NOV-11:00 | 0.117239E+10 | 81421.74 | 24-NOV-07:10 |
December | 0.274501E+13 | 1824537.60 | 19-DEC-11:00 | 0.975526E+10 | 192802.94 | 22-DEC-07:10 |
Annual Sum or Average | 0.260362E+14 | 0.454275E+11 | ||||
Minimum of Months | 0.158789E+13 | 1290998.32 | 1211.52 | 2.02 | ||
Maximum of Months | 0.306992E+13 | 1958493.27 | 0.168003E+11 | 322456.12 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.208244E+12 | 0.377521E+11 | 0.766053E+12 | 0.213315E+12 | 0.184879E+12 | 0.253180E+11 | 0.00 | 0.517029E+11 | 0.203901E+11 | 0.650419E+11 | 0.00 | 0.343122E+11 | 0.00 |
February | 0.187066E+12 | 0.310313E+11 | 0.978954E+12 | 0.195308E+12 | 0.168583E+12 | 0.209813E+11 | 0.00 | 0.461697E+11 | 0.148963E+11 | 0.553318E+11 | 0.00 | 0.312148E+11 | 0.00 |
March | 0.221452E+12 | 0.299078E+11 | 0.141687E+13 | 0.226028E+12 | 0.191380E+12 | 0.230979E+11 | 0.00 | 0.701983E+11 | 0.209350E+11 | 0.469520E+11 | 0.00 | 0.363074E+11 | 0.00 |
April | 0.196447E+12 | 0.247703E+11 | 0.165903E+13 | 0.211475E+12 | 0.197562E+12 | 0.287799E+11 | 0.00 | 0.150143E+12 | 0.521534E+11 | 0.153992E+11 | 0.00 | 0.322838E+11 | 0.00 |
May | 0.211477E+12 | 0.228103E+11 | 0.774844E+12 | 0.219671E+12 | 0.200081E+12 | 0.303714E+11 | 0.00 | 0.546234E+11 | 0.355383E+11 | 0.485996E+10 | 0.00 | 0.336119E+11 | 0.00 |
June | 0.210360E+12 | 0.210075E+11 | 0.106252E+13 | 0.217906E+12 | 0.203237E+12 | 0.358247E+11 | 0.00 | 0.116271E+12 | 0.594292E+11 | 0.306972E+09 | 0.00 | 0.325781E+11 | 0.00 |
July | 0.196656E+12 | 0.220001E+11 | 0.139340E+13 | 0.213239E+12 | 0.220829E+12 | 0.474960E+11 | 0.00 | 0.262827E+12 | 0.106480E+12 | 0.00 | 0.00 | 0.305642E+11 | 0.00 |
August | 0.219780E+12 | 0.242313E+11 | 0.173200E+13 | 0.226028E+12 | 0.235061E+12 | 0.528769E+11 | 0.00 | 0.411201E+12 | 0.135364E+12 | 0.00 | 0.00 | 0.333762E+11 | 0.00 |
September | 0.197124E+12 | 0.270872E+11 | 0.740713E+12 | 0.211475E+12 | 0.203618E+12 | 0.369879E+11 | 0.00 | 0.103857E+12 | 0.642105E+11 | 0.424777E+10 | 0.00 | 0.306558E+11 | 0.00 |
October | 0.205865E+12 | 0.325062E+11 | 0.108340E+13 | 0.213315E+12 | 0.204471E+12 | 0.402648E+11 | 0.00 | 0.164557E+12 | 0.801307E+11 | 0.585072E+11 | 0.00 | 0.323135E+11 | 0.00 |
November | 0.205691E+12 | 0.354138E+11 | 0.135889E+13 | 0.205269E+12 | 0.187161E+12 | 0.262995E+11 | 0.00 | 0.942410E+11 | 0.299947E+11 | 0.819083E+11 | 0.00 | 0.325061E+11 | 0.00 |
December | 0.201831E+12 | 0.388307E+11 | 0.170972E+13 | 0.213241E+12 | 0.187186E+12 | 0.267463E+11 | 0.00 | 0.144819E+12 | 0.416618E+11 | 0.147901E+12 | 0.00 | 0.330753E+11 | 0.00 |
Annual Sum or Average | 0.246199E+13 | 0.347348E+12 | 0.146764E+14 | 0.256627E+13 | 0.238405E+13 | 0.395045E+12 | 0.00 | 0.167061E+13 | 0.661184E+12 | 0.480456E+12 | 0.00 | 0.392799E+12 | 0.00 |
Minimum of Months | 0.187066E+12 | 0.210075E+11 | 0.740713E+12 | 0.195308E+12 | 0.168583E+12 | 0.209813E+11 | 0.00 | 0.461697E+11 | 0.148963E+11 | 0.00 | 0.00 | 0.305642E+11 | 0.00 |
Maximum of Months | 0.221452E+12 | 0.388307E+11 | 0.173200E+13 | 0.226028E+12 | 0.235061E+12 | 0.528769E+11 | 0.00 | 0.411201E+12 | 0.135364E+12 | 0.147901E+12 | 0.00 | 0.363074E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.168003E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.450146E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.125060E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.490059E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.104060E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1211.52 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8223.31 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 44034.16 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1248.55 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 97811494.80 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.117239E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.975526E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.454275E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1211.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.168003E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-16:49 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233383.04 | 31-JAN-08:20 | 147821.80 | 18-JAN-15:00 | 38255.90 | 18-JAN-13:30 | 0.00 | 01-JAN-00:10 |
February | 238754.30 | 27-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233380.55 | 10-FEB-08:20 | 150652.25 | 03-FEB-15:00 | 35672.12 | 01-FEB-11:39 | 0.00 | 01-FEB-00:10 |
March | 221234.97 | 16-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233383.54 | 16-MAR-07:19 | 168648.17 | 23-MAR-15:39 | 38172.31 | 23-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 217421.17 | 21-APR-15:00 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233381.07 | 05-APR-07:19 | 182972.89 | 26-APR-14:30 | 37205.75 | 12-APR-13:50 | 0.00 | 01-APR-00:10 |
May | 216556.76 | 09-MAY-07:10 | 27558.46 | 01-MAY-18:30 | 423497.50 | 01-MAY-07:10 | 233381.07 | 09-MAY-07:19 | 156958.87 | 04-MAY-14:09 | 36053.57 | 03-MAY-13:39 | 0.00 | 01-MAY-00:10 |
June | 215577.59 | 09-JUN-07:10 | 27558.46 | 01-JUN-18:49 | 541788.89 | 01-JUN-07:10 | 233380.55 | 09-JUN-07:19 | 167815.50 | 30-JUN-15:00 | 35975.51 | 21-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 214335.12 | 12-JUL-07:10 | 27558.46 | 01-JUL-18:00 | 660080.29 | 03-JUL-07:10 | 233379.90 | 12-JUL-07:19 | 189065.71 | 31-JUL-14:30 | 36727.41 | 28-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 216583.66 | 21-AUG-07:10 | 40855.88 | 08-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233381.08 | 21-AUG-07:19 | 189998.99 | 17-AUG-14:30 | 37240.70 | 07-AUG-10:30 | 0.00 | 01-AUG-00:10 |
September | 225109.11 | 18-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233385.59 | 18-SEP-07:19 | 183476.60 | 11-SEP-14:30 | 40832.74 | 29-SEP-10:39 | 0.00 | 01-SEP-00:10 |
October | 225202.86 | 24-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233385.64 | 24-OCT-07:19 | 190806.28 | 16-OCT-08:20 | 43335.47 | 16-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 06-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233380.83 | 24-NOV-08:39 | 154101.50 | 13-NOV-15:30 | 36619.53 | 28-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-16:40 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233380.68 | 08-DEC-08:20 | 154252.64 | 05-DEC-16:10 | 36694.23 | 19-DEC-13:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 214335.12 | 27558.46 | 423497.50 | 233379.90 | 147821.80 | 35672.12 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233385.64 | 190806.28 | 43335.47 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 204110.44 | 18-JAN-13:30 | 72551.47 | 13-JAN-14:39 | 100000.00 | 08-JAN-11:30 | 0.00 | 45272.41 | 31-JAN-12:39 | 0.00 |
February | 202840.70 | 01-FEB-11:50 | 58163.86 | 01-FEB-11:00 | 100000.00 | 01-FEB-08:09 | 0.00 | 45273.59 | 02-FEB-12:39 | 0.00 |
March | 233079.22 | 23-MAR-13:39 | 72551.47 | 22-MAR-12:30 | 100000.00 | 07-MAR-11:30 | 0.00 | 45062.75 | 01-MAR-12:20 | 0.00 |
April | 290281.79 | 26-APR-10:39 | 72551.47 | 04-APR-12:39 | 100000.00 | 01-APR-04:19 | 0.00 | 44278.06 | 03-APR-11:20 | 0.00 |
May | 173040.99 | 03-MAY-13:30 | 72551.47 | 04-MAY-12:30 | 100000.00 | 24-MAY-05:30 | 0.00 | 43298.27 | 01-MAY-11:20 | 0.00 |
June | 244305.46 | 29-JUN-12:00 | 72551.47 | 14-JUN-10:39 | 58350.72 | 12-JUN-09:00 | 0.00 | 42134.70 | 01-JUN-11:00 | 0.00 |
July | 364349.97 | 28-JUL-12:30 | 72551.47 | 03-JUL-12:30 | 0.00 | 01-JUL-00:10 | 0.00 | 41194.75 | 03-JUL-11:20 | 0.00 |
August | 420641.88 | 07-AUG-10:30 | 72551.47 | 01-AUG-12:30 | 0.00 | 01-AUG-00:10 | 0.00 | 41103.32 | 31-AUG-11:00 | 0.00 |
September | 247487.18 | 29-SEP-10:39 | 72551.47 | 01-SEP-13:20 | 100000.00 | 29-SEP-07:40 | 0.00 | 41860.18 | 29-SEP-11:50 | 0.00 |
October | 334411.58 | 03-OCT-13:39 | 72551.47 | 02-OCT-07:19 | 100000.00 | 13-OCT-04:30 | 0.00 | 43051.02 | 31-OCT-11:00 | 0.00 |
November | 251631.89 | 28-NOV-13:00 | 58163.86 | 10-NOV-12:09 | 100000.00 | 09-NOV-05:30 | 0.00 | 44134.66 | 30-NOV-12:30 | 0.00 |
December | 286867.21 | 19-DEC-12:30 | 58163.86 | 07-DEC-13:20 | 100000.00 | 04-DEC-05:19 | 0.00 | 44911.14 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 173040.99 | 58163.86 | 0.00 | 0.00 | 41103.32 | 0.00 | ||||
Maximum of Months | 420641.88 | 72551.47 | 100000.00 | 0.00 | 45273.59 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1352955.92 | 18-JAN-11:00 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 102883.14 | 35841.16 | 0.00 | 163020.89 | 45246.04 |
February | 1491163.26 | 03-FEB-15:09 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 124722.60 | 35038.71 | 0.00 | 172835.93 | 45342.99 |
March | 1626901.39 | 23-MAR-15:39 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 168648.17 | 35805.91 | 0.00 | 209325.05 | 72551.47 |
April | 1812564.89 | 26-APR-10:39 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 154691.66 | 35401.96 | 0.00 | 290281.79 | 72551.47 |
May | 1290998.32 | 03-MAY-14:30 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 154993.82 | 20450.27 | 0.00 | 162974.34 | 58163.86 |
June | 1503574.49 | 28-JUN-10:00 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 139153.93 | 35727.28 | 0.00 | 234514.19 | 72551.47 |
July | 1787330.83 | 31-JUL-14:09 | 212815.01 | 660080.29 | 0.00 | 233115.89 | 186435.71 | 36521.68 | 0.00 | 362349.42 | 72551.47 |
August | 1958493.27 | 07-AUG-10:30 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 169826.67 | 37240.70 | 0.00 | 420641.88 | 72551.47 |
September | 1397810.57 | 29-SEP-15:00 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 158952.50 | 37959.10 | 0.00 | 226312.77 | 72551.47 |
October | 1595894.17 | 16-OCT-10:00 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 140868.69 | 36183.74 | 0.00 | 323757.49 | 72551.47 |
November | 1661890.85 | 28-NOV-11:00 | 212815.01 | 660080.29 | 0.00 | 233115.89 | 102670.84 | 35851.74 | 0.00 | 236698.04 | 44544.79 |
December | 1824537.60 | 19-DEC-11:00 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 105389.51 | 35106.87 | 0.00 | 278481.10 | 44280.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1290998.32 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 102670.84 | 20450.27 | 0.00 | 162974.34 | 44280.81 | |
Maximum of Months | 1958493.27 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 186435.71 | 37959.10 | 0.00 | 420641.88 | 72551.47 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 322456.12 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 139112.11 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 241228.73 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 130829.24 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 100412.64 | 09-MAY-09:39 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2.02 | 28-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2.04 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4.06 | 15-AUG-11:20 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2.08 | 13-SEP-09:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 34540.90 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 81421.74 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 192802.94 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 2.02 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 322456.12 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 95.67 | 27.43 | 46.50 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 26.56 | 28.83 | 26.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 26.28 | 29.67 | 26.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 26.36 | 28.50 | 26.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 26.30 | 30.00 | 26.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | 26.27 | 32.17 | 26.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 26.43 | 32.67 | 26.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 26.35 | 35.83 | 26.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 112.00 | 27.06 | 68.83 | 27.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 | 27.26 | 104.00 | 27.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 27.00 | 40.00 | 26.95 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 26.97 | 39.83 | 26.92 |
Annual Sum or Average | 0.00 | 0.00 | 931.33 | 26.84 | 516.83 | 26.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 26.27 | 28.50 | 26.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 | 27.43 | 104.00 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.61 | 0.50 | 26.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.83 | 0.00 | 25.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.98 | 0.00 | 25.98 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 26.08 | 0.50 | 26.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.61 | 0.50 | 26.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.49 | 0.67 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.58 | 1.50 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.70 | 3.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.67 | 2.50 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.78 | 2.83 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.74 | 4.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 2.33 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.69 | 3.17 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.50 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.83 | 27.72 | 26.83 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.76 | 4.83 | 27.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.88 | 4.50 | 27.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.68 | 2.50 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.42 | 2.33 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.32 | 2.17 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.99 | 6.67 | 26.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 26.20 | 23.00 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.11 | 9.17 | 27.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 25.96 | 22.33 | 25.96 |
Annual Sum or Average | 0.00 | 0.00 | 78.33 | 26.62 | 78.00 | 26.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.88 | 23.00 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.49 | 1.33 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.90 | 3.17 | 27.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.82 | 3.33 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.60 | 9.33 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.92 | 5.50 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.67 | 4.00 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.57 | 12.17 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.44 | 11.50 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.84 | 4.50 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.65 | 8.00 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.87 | 5.00 | 27.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.48 | 6.17 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 114.83 | 27.62 | 74.00 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.44 | 1.33 | 27.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.92 | 12.17 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.48 | 1.17 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.68 | 2.67 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.66 | 2.33 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.77 | 3.17 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.86 | 6.33 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.85 | 4.33 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.80 | 2.00 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.33 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.67 | 27.76 | 24.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.86 | 6.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 25.78 | 14.67 | 25.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.92 | 4.83 | 27.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.64 | 2.33 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.83 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.48 | 8.33 | 26.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 26.09 | 27.67 | 26.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.03 | 16.33 | 26.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 25.56 | 33.17 | 25.56 |
Annual Sum or Average | 0.00 | 0.00 | 108.33 | 26.03 | 108.17 | 26.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.92 | 33.17 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.85 | 0.67 | 27.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.00 | 3.67 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.84 | 4.67 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 3.00 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.02 | 6.00 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.11 | 4.00 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.03 | 3.00 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.87 | 4.83 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 41.50 | 27.95 | 31.50 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.11 | 6.00 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.83 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.53 | 1.50 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.71 | 2.67 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.76 | 7.17 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.69 | 5.17 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.66 | 1.67 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.71 | 2.17 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.23 | 0.00 | 19.23 | 22.17 | 27.45 | 22.17 | 27.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.33 | 0.00 | 19.33 | 7.17 | 27.76 | 7.17 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.38 | 0.00 | 19.38 | 3.50 | 27.42 | 3.50 | 27.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.73 | 3.67 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.54 | 2.00 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.57 | 6.50 | 26.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 26.26 | 21.67 | 26.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.96 | 4.83 | 27.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.03 | 7.83 | 27.03 |
Annual Sum or Average | 0.17 | 19.38 | 0.00 | 19.38 | 51.50 | 26.84 | 51.33 | 26.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 21.83 | 27.96 | 21.67 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.79 | 0.67 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 3.83 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 4.67 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.98 | 3.00 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.11 | 6.67 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.18 | 4.17 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.04 | 3.33 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.93 | 4.50 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.83 | 28.01 | 31.17 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.18 | 6.67 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.70 | 2.83 | 27.70 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 27.70 | 2.83 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.70 | 2.83 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 28.29 | 54.83 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 54.83 | 28.29 | 54.83 | 28.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 28.29 | 54.83 | 28.29 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.00 | 25.95 | 287.33 | 25.36 | 14.67 | 25.51 |
February | 25.33 | 24.25 | 260.17 | 25.01 | 1.83 | 25.03 |
March | 0.00 | 0.00 | 332.00 | 24.83 | 0.00 | 24.83 |
April | 2.83 | 24.00 | 410.50 | 24.74 | 0.00 | 24.74 |
May | 0.00 | 0.00 | 394.00 | 24.75 | 0.00 | 24.75 |
June | 0.00 | 0.00 | 465.33 | 24.60 | 0.00 | 24.60 |
July | 97.00 | 25.60 | 497.00 | 24.86 | 97.00 | 24.97 |
August | 109.67 | 25.61 | 514.00 | 24.77 | 109.67 | 24.90 |
September | 71.33 | 26.74 | 479.17 | 25.12 | 71.33 | 25.31 |
October | 53.67 | 27.59 | 380.67 | 25.62 | 53.67 | 25.84 |
November | 29.50 | 25.59 | 308.83 | 25.20 | 13.00 | 25.29 |
December | 32.50 | 25.24 | 232.83 | 25.51 | 11.00 | 25.60 |
Annual Sum or Average | 457.83 | 25.93 | 4561.83 | 25.00 | 372.17 | 25.09 |
Minimum of Months | 0.00 | 0.00 | 232.83 | 24.60 | 0.00 | 24.60 |
Maximum of Months | 109.67 | 27.59 | 514.00 | 25.62 | 109.67 | 25.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 23.98 | 238.33 | 24.64 | 0.00 | 24.64 |
February | 25.50 | 24.00 | 243.00 | 24.53 | 0.00 | 24.53 |
March | 0.00 | 0.00 | 330.67 | 24.45 | 0.00 | 24.45 |
April | 2.33 | 24.03 | 434.83 | 24.33 | 0.00 | 24.33 |
May | 0.00 | 0.00 | 369.50 | 24.35 | 0.00 | 24.35 |
June | 0.00 | 0.00 | 480.17 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 454.83 | 24.34 | 0.00 | 24.34 |
October | 1.33 | 24.00 | 343.00 | 24.56 | 0.00 | 24.56 |
November | 14.67 | 24.11 | 283.00 | 24.59 | 0.50 | 24.59 |
December | 24.17 | 24.00 | 213.83 | 24.77 | 0.00 | 24.77 |
Annual Sum or Average | 99.00 | 24.01 | 4402.17 | 24.41 | 0.50 | 24.41 |
Minimum of Months | 0.00 | 0.00 | 213.83 | 24.22 | 0.00 | 24.22 |
Maximum of Months | 31.00 | 24.11 | 514.00 | 24.77 | 0.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.00 | 23.73 | 128.17 | 24.00 | 13.67 | 24.01 |
February | 104.50 | 23.69 | 117.67 | 24.04 | 0.00 | 24.04 |
March | 76.00 | 23.67 | 185.83 | 24.12 | 0.00 | 24.12 |
April | 37.50 | 23.52 | 239.50 | 24.17 | 0.00 | 24.17 |
May | 20.83 | 23.59 | 273.33 | 24.26 | 0.00 | 24.26 |
June | 0.33 | 23.54 | 418.50 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 491.33 | 24.18 | 0.00 | 24.18 |
August | 0.00 | 0.00 | 514.00 | 24.16 | 0.00 | 24.16 |
September | 2.50 | 23.59 | 416.83 | 24.21 | 0.00 | 24.21 |
October | 41.83 | 23.81 | 266.17 | 24.29 | 0.00 | 24.29 |
November | 114.33 | 23.81 | 184.67 | 24.17 | 0.00 | 24.17 |
December | 198.83 | 23.77 | 78.33 | 23.97 | 0.00 | 23.97 |
Annual Sum or Average | 755.67 | 23.73 | 3314.33 | 24.16 | 13.67 | 24.16 |
Minimum of Months | 0.00 | 0.00 | 78.33 | 23.97 | 0.00 | 23.97 |
Maximum of Months | 198.83 | 23.81 | 514.00 | 24.29 | 13.67 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.67 | 22.85 | 43.67 | 22.87 | 12.33 | 22.80 |
February | 305.50 | 22.95 | 38.67 | 23.07 | 0.00 | 23.07 |
March | 298.50 | 23.14 | 87.50 | 23.35 | 0.00 | 23.35 |
April | 143.50 | 23.16 | 178.00 | 23.69 | 0.00 | 23.69 |
May | 140.83 | 23.27 | 199.00 | 23.78 | 0.00 | 23.78 |
June | 29.00 | 23.37 | 363.67 | 24.10 | 0.00 | 24.10 |
July | 1.33 | 23.44 | 473.00 | 24.17 | 0.00 | 24.17 |
August | 0.00 | 0.00 | 495.33 | 24.13 | 0.00 | 24.13 |
September | 35.00 | 23.37 | 349.50 | 24.06 | 0.17 | 24.06 |
October | 155.83 | 23.46 | 205.17 | 23.89 | 0.00 | 23.89 |
November | 287.33 | 23.21 | 76.00 | 23.41 | 6.67 | 23.42 |
December | 399.83 | 23.03 | 16.83 | 23.06 | 1.50 | 23.05 |
Annual Sum or Average | 2162.33 | 23.09 | 2526.33 | 23.65 | 20.67 | 23.64 |
Minimum of Months | 0.00 | 0.00 | 16.83 | 22.87 | 0.00 | 22.80 |
Maximum of Months | 399.83 | 23.46 | 495.33 | 24.17 | 12.33 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 306.83 | 23.29 | 42.00 | 23.43 | 0.00 | 23.43 |
February | 240.50 | 23.42 | 51.33 | 23.55 | 0.00 | 23.55 |
March | 198.00 | 23.35 | 124.50 | 23.67 | 0.00 | 23.67 |
April | 61.50 | 23.60 | 238.33 | 24.10 | 0.00 | 24.10 |
May | 75.50 | 23.55 | 238.83 | 24.07 | 0.00 | 24.07 |
June | 1.67 | 23.43 | 435.00 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 492.33 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 508.50 | 24.19 | 0.00 | 24.19 |
September | 18.67 | 23.51 | 381.33 | 24.19 | 0.00 | 24.19 |
October | 82.67 | 23.72 | 258.17 | 24.25 | 0.00 | 24.25 |
November | 218.67 | 23.66 | 92.50 | 23.87 | 0.00 | 23.87 |
December | 304.50 | 23.63 | 26.83 | 23.68 | 0.00 | 23.68 |
Annual Sum or Average | 1508.50 | 23.49 | 2889.67 | 23.99 | 0.00 | 23.99 |
Minimum of Months | 0.00 | 0.00 | 26.83 | 23.43 | 0.00 | 23.43 |
Maximum of Months | 306.83 | 23.72 | 508.50 | 24.30 | 0.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 213.67 | 23.34 | 106.67 | 23.79 | 0.17 | 23.79 |
February | 199.33 | 23.34 | 105.33 | 23.74 | 0.83 | 23.75 |
March | 183.17 | 23.34 | 188.17 | 23.86 | 4.00 | 23.89 |
April | 80.00 | 23.87 | 302.50 | 24.28 | 9.67 | 24.34 |
May | 69.00 | 23.99 | 305.50 | 24.36 | 9.83 | 24.42 |
June | 25.50 | 25.29 | 421.67 | 24.37 | 13.50 | 24.44 |
July | 28.67 | 26.89 | 481.50 | 24.55 | 28.67 | 24.68 |
August | 21.00 | 26.87 | 496.33 | 24.38 | 21.00 | 24.47 |
September | 27.83 | 24.89 | 409.83 | 24.36 | 11.50 | 24.43 |
October | 60.17 | 24.15 | 308.67 | 24.46 | 9.33 | 24.53 |
November | 171.33 | 23.57 | 149.00 | 23.99 | 0.50 | 24.00 |
December | 225.33 | 23.46 | 62.33 | 23.75 | 0.00 | 23.75 |
Annual Sum or Average | 1305.00 | 23.70 | 3337.50 | 24.20 | 109.00 | 24.26 |
Minimum of Months | 21.00 | 23.34 | 62.33 | 23.74 | 0.00 | 23.75 |
Maximum of Months | 225.33 | 26.89 | 496.33 | 24.55 | 28.67 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 134.50 | 23.73 | 243.50 | 24.27 | 13.67 | 24.37 |
February | 154.67 | 23.67 | 184.33 | 24.15 | 14.67 | 24.27 |
March | 167.83 | 23.50 | 219.33 | 23.97 | 10.17 | 24.05 |
April | 70.83 | 23.79 | 299.00 | 24.29 | 6.83 | 24.33 |
May | 115.33 | 23.39 | 230.83 | 23.98 | 0.00 | 23.98 |
June | 17.50 | 23.47 | 392.83 | 24.18 | 0.00 | 24.18 |
July | 4.67 | 26.71 | 485.17 | 24.33 | 4.67 | 24.35 |
August | 17.17 | 26.73 | 508.83 | 24.34 | 17.17 | 24.41 |
September | 34.50 | 25.90 | 426.00 | 24.51 | 25.00 | 24.63 |
October | 67.00 | 25.63 | 374.17 | 24.78 | 40.00 | 24.97 |
November | 93.67 | 24.50 | 297.33 | 24.57 | 22.67 | 24.71 |
December | 122.50 | 24.35 | 253.67 | 24.61 | 26.00 | 24.77 |
Annual Sum or Average | 1000.17 | 24.06 | 3915.00 | 24.34 | 180.83 | 24.44 |
Minimum of Months | 4.67 | 23.39 | 184.33 | 23.97 | 0.00 | 23.98 |
Maximum of Months | 167.83 | 26.73 | 508.83 | 24.78 | 40.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 96.33 | 23.76 | 208.83 | 24.31 | 1.50 | 24.32 |
February | 37.83 | 24.90 | 273.00 | 24.64 | 11.83 | 24.73 |
March | 21.17 | 25.78 | 387.00 | 24.59 | 12.67 | 24.66 |
April | 38.00 | 27.08 | 475.00 | 24.81 | 38.00 | 24.97 |
May | 27.83 | 26.69 | 421.83 | 24.65 | 25.33 | 24.77 |
June | 24.17 | 26.98 | 494.67 | 24.61 | 24.17 | 24.72 |
July | 75.17 | 26.99 | 497.00 | 24.98 | 75.17 | 25.22 |
August | 62.17 | 26.98 | 514.00 | 24.81 | 62.17 | 25.02 |
September | 27.83 | 26.93 | 472.17 | 24.64 | 27.83 | 24.77 |
October | 37.50 | 26.58 | 401.00 | 24.88 | 32.00 | 25.03 |
November | 34.17 | 25.76 | 339.17 | 24.84 | 20.00 | 24.95 |
December | 30.50 | 25.87 | 306.33 | 25.00 | 18.50 | 25.11 |
Annual Sum or Average | 512.67 | 25.99 | 4790.00 | 24.74 | 349.17 | 24.88 |
Minimum of Months | 21.17 | 23.76 | 208.83 | 24.31 | 1.50 | 24.32 |
Maximum of Months | 96.33 | 27.08 | 514.00 | 25.00 | 75.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.33 | 22.40 | 17.50 | 22.41 | 7.50 | 22.38 |
February | 391.50 | 22.59 | 8.00 | 22.62 | 0.00 | 22.62 |
March | 417.67 | 22.68 | 34.17 | 22.78 | 0.00 | 22.78 |
April | 276.33 | 22.99 | 85.50 | 23.23 | 0.00 | 23.23 |
May | 211.33 | 23.22 | 131.67 | 23.57 | 0.00 | 23.57 |
June | 68.17 | 23.36 | 319.00 | 23.99 | 0.00 | 23.99 |
July | 16.17 | 23.31 | 432.83 | 24.14 | 0.00 | 24.14 |
August | 35.67 | 23.25 | 403.00 | 24.01 | 0.00 | 24.01 |
September | 118.33 | 23.19 | 242.83 | 23.78 | 0.00 | 23.78 |
October | 231.17 | 23.22 | 144.67 | 23.60 | 0.00 | 23.60 |
November | 392.33 | 22.78 | 13.67 | 22.81 | 1.83 | 22.80 |
December | 477.67 | 22.54 | 4.17 | 22.54 | 2.00 | 22.53 |
Annual Sum or Average | 3080.67 | 22.77 | 1837.00 | 23.26 | 11.33 | 23.26 |
Minimum of Months | 16.17 | 22.40 | 4.17 | 22.41 | 0.00 | 22.38 |
Maximum of Months | 477.67 | 23.36 | 432.83 | 24.14 | 7.50 | 24.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.00 | 22.90 | 37.50 | 23.06 | 1.67 | 23.04 |
February | 257.50 | 22.82 | 47.17 | 23.08 | 0.00 | 23.08 |
March | 241.67 | 22.81 | 106.83 | 23.31 | 3.00 | 23.33 |
April | 138.33 | 23.36 | 199.33 | 24.05 | 8.00 | 24.12 |
May | 122.83 | 23.55 | 209.50 | 24.22 | 8.00 | 24.28 |
June | 58.50 | 24.27 | 297.83 | 24.37 | 15.17 | 24.47 |
July | 45.50 | 26.23 | 390.00 | 24.70 | 36.83 | 24.87 |
August | 34.33 | 26.13 | 395.67 | 24.51 | 27.17 | 24.65 |
September | 71.33 | 23.79 | 283.33 | 24.24 | 10.67 | 24.32 |
October | 106.50 | 23.51 | 211.17 | 24.21 | 5.33 | 24.26 |
November | 246.50 | 23.13 | 68.83 | 23.44 | 0.00 | 23.44 |
December | 316.17 | 23.03 | 18.67 | 23.12 | 0.00 | 23.12 |
Annual Sum or Average | 1931.17 | 23.25 | 2265.83 | 23.90 | 115.83 | 23.98 |
Minimum of Months | 34.33 | 22.81 | 18.67 | 23.06 | 0.00 | 23.04 |
Maximum of Months | 316.17 | 26.23 | 395.67 | 24.70 | 36.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 179.00 | 23.42 | 227.00 | 24.09 | 15.83 | 24.20 |
February | 212.00 | 23.20 | 160.67 | 23.80 | 15.50 | 23.93 |
March | 240.33 | 22.96 | 177.17 | 23.54 | 9.67 | 23.62 |
April | 157.33 | 23.13 | 221.67 | 23.86 | 3.00 | 23.88 |
May | 197.17 | 23.17 | 181.00 | 23.69 | 0.00 | 23.69 |
June | 92.33 | 23.30 | 290.33 | 23.93 | 0.00 | 23.93 |
July | 23.67 | 23.76 | 417.83 | 24.20 | 3.00 | 24.22 |
August | 23.17 | 24.67 | 454.67 | 24.25 | 9.33 | 24.29 |
September | 63.17 | 24.68 | 385.83 | 24.42 | 24.67 | 24.55 |
October | 108.67 | 24.75 | 336.67 | 24.68 | 43.50 | 24.87 |
November | 157.67 | 23.87 | 251.17 | 24.35 | 21.83 | 24.49 |
December | 197.33 | 23.76 | 228.50 | 24.33 | 25.17 | 24.49 |
Annual Sum or Average | 1651.83 | 23.50 | 3332.50 | 24.11 | 171.50 | 24.21 |
Minimum of Months | 23.17 | 22.96 | 160.67 | 23.54 | 0.00 | 23.62 |
Maximum of Months | 240.33 | 24.75 | 454.67 | 24.68 | 43.50 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.83 | 22.85 | 77.50 | 23.13 | 0.00 | 23.13 |
February | 273.83 | 23.03 | 89.17 | 23.37 | 1.50 | 23.39 |
March | 254.50 | 23.02 | 141.33 | 23.46 | 2.67 | 23.49 |
April | 116.83 | 23.77 | 269.33 | 24.23 | 18.33 | 24.35 |
May | 112.33 | 23.96 | 281.83 | 24.30 | 19.83 | 24.42 |
June | 34.00 | 25.05 | 423.50 | 24.37 | 16.33 | 24.46 |
July | 32.50 | 26.96 | 493.00 | 24.60 | 32.50 | 24.74 |
August | 21.50 | 26.95 | 505.17 | 24.42 | 21.50 | 24.52 |
September | 37.17 | 25.13 | 400.17 | 24.44 | 17.83 | 24.53 |
October | 123.83 | 24.02 | 283.17 | 24.35 | 19.67 | 24.47 |
November | 243.67 | 23.25 | 131.17 | 23.66 | 1.00 | 23.66 |
December | 326.83 | 23.09 | 65.00 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 1898.83 | 23.39 | 3160.33 | 24.01 | 151.17 | 24.10 |
Minimum of Months | 21.50 | 22.85 | 65.00 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 326.83 | 26.96 | 505.17 | 24.60 | 32.50 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.17 | 21.69 | 88.33 | 21.46 | 87.67 | 21.29 |
February | 425.67 | 21.91 | 35.83 | 21.80 | 34.67 | 21.70 |
March | 452.17 | 22.09 | 55.67 | 22.09 | 31.00 | 22.00 |
April | 312.00 | 22.56 | 86.00 | 22.84 | 4.67 | 22.81 |
May | 266.17 | 22.79 | 115.17 | 23.17 | 0.17 | 23.17 |
June | 121.17 | 23.15 | 278.17 | 23.81 | 0.00 | 23.81 |
July | 41.83 | 23.14 | 392.83 | 24.07 | 0.00 | 24.07 |
August | 87.17 | 23.16 | 359.33 | 23.91 | 0.00 | 23.91 |
September | 192.00 | 22.95 | 209.50 | 23.52 | 0.00 | 23.52 |
October | 278.50 | 22.80 | 126.33 | 23.23 | 1.00 | 23.23 |
November | 456.17 | 22.23 | 36.00 | 22.14 | 30.00 | 22.04 |
December | 491.00 | 21.77 | 84.50 | 21.56 | 84.50 | 21.40 |
Annual Sum or Average | 3599.00 | 22.26 | 1867.67 | 22.70 | 273.67 | 22.59 |
Minimum of Months | 41.83 | 21.69 | 35.83 | 21.46 | 0.00 | 21.29 |
Maximum of Months | 491.00 | 23.16 | 392.83 | 24.07 | 87.67 | 24.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 397.50 | 22.43 | 62.00 | 22.38 | 34.67 | 22.24 |
February | 341.00 | 22.30 | 48.50 | 22.42 | 11.83 | 22.35 |
March | 314.17 | 22.32 | 110.50 | 22.73 | 12.17 | 22.67 |
April | 178.17 | 22.86 | 245.17 | 23.73 | 6.00 | 23.76 |
May | 167.83 | 23.06 | 236.67 | 23.86 | 3.83 | 23.89 |
June | 97.33 | 23.79 | 346.67 | 24.18 | 16.50 | 24.28 |
July | 65.00 | 25.70 | 440.00 | 24.61 | 44.83 | 24.79 |
August | 61.17 | 25.27 | 446.50 | 24.42 | 35.33 | 24.57 |
September | 111.17 | 23.27 | 310.33 | 24.00 | 8.50 | 24.06 |
October | 153.83 | 23.12 | 214.50 | 23.88 | 4.50 | 23.92 |
November | 335.50 | 22.73 | 48.17 | 22.84 | 8.17 | 22.79 |
December | 447.17 | 22.63 | 26.00 | 22.53 | 21.67 | 22.44 |
Annual Sum or Average | 2669.83 | 22.81 | 2535.00 | 23.49 | 208.00 | 23.51 |
Minimum of Months | 61.17 | 22.30 | 26.00 | 22.38 | 3.83 | 22.24 |
Maximum of Months | 447.17 | 25.70 | 446.50 | 24.61 | 44.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.67 | 22.63 | 195.33 | 23.31 | 26.00 | 23.28 |
February | 258.83 | 22.46 | 132.00 | 23.07 | 18.67 | 23.11 |
March | 307.83 | 22.48 | 146.00 | 22.95 | 21.67 | 22.96 |
April | 209.33 | 22.72 | 204.50 | 23.51 | 5.50 | 23.52 |
May | 241.50 | 22.73 | 157.67 | 23.30 | 1.17 | 23.29 |
June | 143.67 | 23.07 | 266.67 | 23.75 | 0.00 | 23.75 |
July | 60.00 | 23.46 | 378.33 | 24.13 | 5.00 | 24.16 |
August | 64.50 | 23.96 | 414.83 | 24.19 | 14.83 | 24.26 |
September | 109.83 | 23.79 | 344.17 | 24.22 | 22.33 | 24.34 |
October | 151.67 | 24.02 | 307.83 | 24.41 | 38.50 | 24.61 |
November | 217.00 | 23.09 | 209.67 | 23.79 | 18.00 | 23.87 |
December | 244.50 | 22.93 | 193.17 | 23.59 | 25.50 | 23.61 |
Annual Sum or Average | 2246.33 | 22.92 | 2950.17 | 23.70 | 197.17 | 23.75 |
Minimum of Months | 60.00 | 22.46 | 132.00 | 22.95 | 0.00 | 22.96 |
Maximum of Months | 307.83 | 24.02 | 414.83 | 24.41 | 38.50 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 375.33 | 22.27 | 90.00 | 22.35 | 34.83 | 22.21 |
February | 318.83 | 22.36 | 85.17 | 22.66 | 12.83 | 22.60 |
March | 323.83 | 22.52 | 119.50 | 22.92 | 11.50 | 22.90 |
April | 166.50 | 23.24 | 232.17 | 23.93 | 17.83 | 24.06 |
May | 171.83 | 23.42 | 243.17 | 24.00 | 19.50 | 24.13 |
June | 65.83 | 24.14 | 383.83 | 24.27 | 17.17 | 24.37 |
July | 39.17 | 26.52 | 471.50 | 24.59 | 34.17 | 24.74 |
August | 32.50 | 25.79 | 481.17 | 24.39 | 22.00 | 24.49 |
September | 85.83 | 23.99 | 357.00 | 24.27 | 19.00 | 24.38 |
October | 173.67 | 23.52 | 259.50 | 24.09 | 18.67 | 24.21 |
November | 311.17 | 22.69 | 107.33 | 23.05 | 8.50 | 23.01 |
December | 379.17 | 22.47 | 70.50 | 22.53 | 28.67 | 22.42 |
Annual Sum or Average | 2443.67 | 22.86 | 2900.83 | 23.61 | 244.67 | 23.65 |
Minimum of Months | 32.50 | 22.27 | 70.50 | 22.35 | 8.50 | 22.21 |
Maximum of Months | 379.17 | 26.52 | 481.17 | 24.59 | 34.83 | 24.74 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 14.33 | 27.00 | 454.00 | 27.00 | 14.33 | 27.00 |
March | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
April | 215.83 | 27.00 | 485.00 | 27.00 | 215.83 | 27.00 |
May | 0.17 | 27.00 | 508.00 | 27.00 | 0.17 | 27.00 |
June | 43.50 | 27.00 | 496.00 | 27.00 | 43.50 | 27.00 |
July | 177.00 | 27.00 | 497.00 | 27.00 | 177.00 | 27.00 |
August | 315.00 | 27.00 | 514.00 | 27.00 | 315.00 | 27.00 |
September | 12.33 | 27.00 | 485.00 | 27.00 | 12.33 | 27.00 |
October | 36.50 | 27.00 | 502.00 | 27.00 | 36.50 | 27.00 |
November | 57.50 | 27.00 | 489.00 | 27.00 | 57.50 | 27.00 |
December | 79.50 | 27.01 | 497.00 | 27.01 | 79.50 | 27.01 |
Annual Sum or Average | 995.17 | 27.00 | 5943.00 | 27.00 | 995.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 315.00 | 27.01 | 514.00 | 27.01 | 315.00 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.17 | 27.00 | 514.00 | 27.00 | 0.17 | 27.00 |
April | 5.83 | 27.00 | 485.00 | 27.00 | 5.83 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 1.00 | 27.00 | 497.00 | 27.00 | 1.00 | 27.00 |
August | 27.67 | 27.00 | 514.00 | 27.00 | 27.67 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 3.00 | 27.00 | 502.00 | 27.00 | 3.00 | 27.00 |
November | 0.33 | 27.00 | 489.00 | 27.00 | 0.33 | 27.00 |
December | 1.00 | 27.00 | 497.00 | 27.00 | 1.00 | 27.00 |
Annual Sum or Average | 39.00 | 27.00 | 5943.00 | 27.00 | 39.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 27.67 | 27.00 | 514.00 | 27.00 | 27.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 25.93 | 487.00 | 26.99 | 0.00 | 26.99 |
February | 0.00 | 0.00 | 448.33 | 27.00 | 0.00 | 27.00 |
March | 2.17 | 27.00 | 514.00 | 27.00 | 2.17 | 27.00 |
April | 20.17 | 27.00 | 485.00 | 27.00 | 20.17 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.33 | 27.00 | 496.00 | 27.00 | 0.33 | 27.00 |
July | 33.67 | 27.00 | 497.00 | 27.00 | 33.67 | 27.00 |
August | 87.50 | 27.00 | 514.00 | 27.00 | 87.50 | 27.00 |
September | 3.33 | 27.00 | 485.00 | 27.00 | 3.33 | 27.00 |
October | 7.00 | 27.00 | 502.00 | 27.00 | 7.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.83 | 27.00 | 497.00 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 156.67 | 26.99 | 5922.33 | 27.00 | 155.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 448.33 | 26.99 | 0.00 | 26.99 |
Maximum of Months | 87.50 | 27.00 | 514.00 | 27.00 | 87.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.50 | 27.00 | 502.00 | 27.00 | 472.50 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 494.33 | 27.00 | 508.00 | 27.00 | 494.33 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.17 | 514.00 | 27.17 | 514.00 | 27.17 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5899.83 | 27.02 | 5943.00 | 27.02 | 5899.83 | 27.02 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.17 | 514.00 | 27.17 | 514.00 | 27.17 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00027 | 32.15552 | 0.88816 | 21.72734 |
February | 454.00000 | 27.00034 | 32.95185 | 0.93064 | 23.36095 |
March | 514.00000 | 27.00029 | 34.33803 | 0.97691 | 25.19694 |
April | 485.00000 | 27.00014 | 35.13808 | 1.03197 | 27.52202 |
May | 508.00000 | 27.00063 | 36.34351 | 0.26600 | 6.53077 |
June | 496.00000 | 27.00089 | 36.74230 | 0.33293 | 7.35571 |
July | 497.00000 | 27.00071 | 37.14903 | 0.39439 | 8.29127 |
August | 514.00000 | 27.00022 | 37.14947 | 0.43266 | 8.95799 |
September | 485.00000 | 27.00105 | 37.65666 | 0.29298 | 6.84947 |
October | 502.00000 | 27.00058 | 34.08969 | 0.96636 | 24.77810 |
November | 489.00000 | 27.00022 | 31.92487 | 0.96801 | 24.86833 |
December | 497.00000 | 27.00600 | 29.54978 | 0.97573 | 25.18511 |
Annual Sum or Average | 5943.00000 | 27.00095 | 34.61425 | 0.70254 | 17.48980 |
Minimum of Months | 454.00000 | 27.00014 | 29.54978 | 0.26600 | 6.53077 |
Maximum of Months | 514.00000 | 27.00600 | 37.65666 | 1.03197 | 27.52202 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00026 | 32.20922 | 0.81783 | 19.22067 |
February | 454.00000 | 27.00033 | 32.97311 | 0.84636 | 20.21178 |
March | 514.00000 | 27.00027 | 34.32661 | 0.87732 | 21.31893 |
April | 485.00000 | 27.00015 | 35.12221 | 0.92527 | 23.15133 |
May | 508.00000 | 27.00061 | 36.42755 | 0.19769 | 5.90088 |
June | 496.00000 | 27.00085 | 36.78470 | 0.24467 | 6.31610 |
July | 497.00000 | 27.00070 | 37.17469 | 0.28604 | 6.76683 |
August | 514.00000 | 27.00023 | 37.16074 | 0.30687 | 7.03104 |
September | 485.00000 | 27.00080 | 37.81157 | 0.22638 | 6.15164 |
October | 502.00000 | 27.00054 | 34.12090 | 0.89486 | 21.97367 |
November | 489.00000 | 27.00022 | 31.91051 | 0.86674 | 20.95744 |
December | 497.00000 | 27.00284 | 29.53213 | 0.84800 | 20.26942 |
Annual Sum or Average | 5943.00000 | 27.00065 | 34.64459 | 0.60920 | 14.88393 |
Minimum of Months | 454.00000 | 27.00015 | 29.53213 | 0.19769 | 5.90088 |
Maximum of Months | 514.00000 | 27.00284 | 37.81157 | 0.92527 | 23.15133 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98257 | 32.39402 | 0.75827 | 17.37804 |
February | 454.00000 | 27.00032 | 33.01619 | 0.79515 | 18.52172 |
March | 514.00000 | 27.00028 | 34.34698 | 0.83535 | 19.88338 |
April | 485.00000 | 27.00016 | 35.13176 | 0.90514 | 22.44936 |
May | 508.00000 | 27.00061 | 36.46467 | 0.17157 | 5.83086 |
June | 496.00000 | 27.00087 | 36.78702 | 0.23741 | 6.33320 |
July | 497.00000 | 27.00074 | 37.17276 | 0.29007 | 6.89081 |
August | 514.00000 | 27.00026 | 37.16302 | 0.30726 | 7.11371 |
September | 485.00000 | 27.00085 | 37.84323 | 0.21067 | 6.09959 |
October | 502.00000 | 27.00055 | 34.13238 | 0.87513 | 21.29054 |
November | 489.00000 | 27.00023 | 31.92853 | 0.82084 | 19.39455 |
December | 497.00000 | 27.00051 | 29.54089 | 0.78912 | 18.30216 |
Annual Sum or Average | 5943.00000 | 26.99898 | 34.67521 | 0.58087 | 14.07562 |
Minimum of Months | 454.00000 | 26.98257 | 29.54089 | 0.17157 | 5.83086 |
Maximum of Months | 514.00000 | 27.00087 | 37.84323 | 0.90514 | 22.44936 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99994 | 32.13231 | 1.08401 | 29.82796 |
February | 454.00000 | 26.99988 | 32.66149 | 1.22858 | 36.70160 |
March | 514.00000 | 27.00150 | 34.55043 | 1.38750 | 44.86002 |
April | 485.00000 | 27.00958 | 35.32665 | 1.53284 | 52.69057 |
May | 508.00000 | 26.99984 | 36.76657 | 0.51218 | 10.55858 |
June | 496.00000 | 27.00200 | 41.97975 | 0.77655 | 17.74889 |
July | 497.00000 | 27.00785 | 45.17418 | 1.01948 | 26.97578 |
August | 514.00000 | 27.17466 | 42.34746 | 1.23381 | 37.04123 |
September | 485.00000 | 26.99996 | 44.71672 | 0.61227 | 12.94078 |
October | 502.00000 | 27.00133 | 37.71308 | 1.30091 | 40.39759 |
November | 489.00000 | 27.00151 | 31.35285 | 1.38383 | 44.69701 |
December | 497.00000 | 27.00245 | 27.33812 | 1.47694 | 49.66541 |
Annual Sum or Average | 5943.00000 | 27.01725 | 36.86804 | 1.12830 | 33.64612 |
Minimum of Months | 454.00000 | 26.99984 | 27.33812 | 0.51218 | 10.55858 |
Maximum of Months | 514.00000 | 27.17466 | 45.17418 | 1.53284 | 52.69057 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.74605 | 36.42304 | 0.52306 | 12.14717 |
February | 454.00000 | 24.63011 | 38.03291 | 0.49814 | 10.89679 |
March | 514.00000 | 24.53993 | 40.41285 | 0.49822 | 10.70250 |
April | 485.00000 | 24.63359 | 43.91652 | 0.54549 | 11.77759 |
May | 508.00000 | 24.58679 | 43.42242 | -0.3244 | 8.17073 |
June | 496.00000 | 24.56162 | 48.74567 | -0.2874 | 7.66740 |
July | 497.00000 | 24.71814 | 55.98005 | -0.1797 | 6.98980 |
August | 514.00000 | 24.59701 | 57.22898 | -0.2013 | 6.97654 |
September | 485.00000 | 24.87069 | 54.65937 | -0.1457 | 8.29856 |
October | 502.00000 | 25.02451 | 43.86270 | 0.64907 | 16.02506 |
November | 489.00000 | 24.74851 | 36.28757 | 0.52707 | 11.82177 |
December | 497.00000 | 24.74315 | 31.84179 | 0.49248 | 11.15623 |
Annual Sum or Average | 5943.00000 | 24.69961 | 44.28674 | 0.21317 | 10.20810 |
Minimum of Months | 454.00000 | 24.53993 | 31.84179 | -0.3244 | 6.97654 |
Maximum of Months | 514.00000 | 25.02451 | 57.22898 | 0.64907 | 16.02506 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36082 | 36.57282 | 0.43977 | 9.43555 |
February | 454.00000 | 24.32696 | 39.08456 | 0.45276 | 9.60494 |
March | 514.00000 | 24.29294 | 41.91642 | 0.47351 | 9.95546 |
April | 485.00000 | 24.30651 | 45.32979 | 0.51206 | 10.71234 |
May | 508.00000 | 24.25881 | 45.24336 | -0.3886 | 8.49042 |
June | 496.00000 | 24.27290 | 51.36543 | -0.3242 | 7.55461 |
July | 497.00000 | 24.28887 | 55.21703 | -0.2800 | 6.92289 |
August | 514.00000 | 24.22280 | 56.15971 | -0.2851 | 6.91408 |
September | 485.00000 | 24.31513 | 52.65047 | -0.3066 | 7.43562 |
October | 502.00000 | 24.38572 | 42.48392 | 0.51211 | 10.99705 |
November | 489.00000 | 24.38636 | 37.08899 | 0.46892 | 10.08779 |
December | 497.00000 | 24.38989 | 31.81825 | 0.43436 | 9.39905 |
Annual Sum or Average | 5943.00000 | 24.31683 | 44.62668 | 0.13928 | 8.95098 |
Minimum of Months | 454.00000 | 24.22280 | 31.81825 | -0.3886 | 6.91408 |
Maximum of Months | 514.00000 | 24.38989 | 56.15971 | 0.51211 | 10.99705 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04717 | 40.20154 | 0.35561 | 7.98310 |
February | 454.00000 | 24.03993 | 41.00876 | 0.36169 | 7.93051 |
March | 514.00000 | 24.06172 | 43.89134 | 0.38922 | 8.33769 |
April | 485.00000 | 24.07708 | 46.81799 | 0.42346 | 8.95022 |
May | 508.00000 | 24.13506 | 46.13641 | -0.4611 | 9.69396 |
June | 496.00000 | 24.15868 | 52.33998 | -0.3986 | 8.56290 |
July | 497.00000 | 24.17217 | 56.49774 | -0.3589 | 7.88957 |
August | 514.00000 | 24.15806 | 57.42664 | -0.3520 | 7.76130 |
September | 485.00000 | 24.17381 | 53.54477 | -0.3855 | 8.37420 |
October | 502.00000 | 24.17879 | 43.86293 | 0.43593 | 9.27801 |
November | 489.00000 | 24.13737 | 39.36510 | 0.38150 | 8.40393 |
December | 497.00000 | 24.03105 | 34.17071 | 0.31608 | 7.37311 |
Annual Sum or Average | 5943.00000 | 24.11471 | 46.32028 | 0.05594 | 8.38121 |
Minimum of Months | 454.00000 | 24.03105 | 34.17071 | -0.4611 | 7.37311 |
Maximum of Months | 514.00000 | 24.17879 | 57.42664 | 0.43593 | 9.69396 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16271 | 42.29651 | 0.12046 | 6.50745 |
February | 454.00000 | 23.29662 | 43.61433 | 0.16908 | 6.46157 |
March | 514.00000 | 23.50854 | 45.88404 | 0.24130 | 6.90008 |
April | 485.00000 | 23.78297 | 47.96581 | 0.34867 | 8.03322 |
May | 508.00000 | 23.85631 | 47.21624 | -0.5607 | 12.25627 |
June | 496.00000 | 24.05391 | 52.77480 | -0.4321 | 9.17854 |
July | 497.00000 | 24.14509 | 56.62393 | -0.3602 | 7.87927 |
August | 514.00000 | 24.11327 | 57.68568 | -0.3617 | 7.88222 |
September | 485.00000 | 24.01282 | 54.39729 | -0.4432 | 9.43519 |
October | 502.00000 | 23.93224 | 45.13373 | 0.37123 | 8.36740 |
November | 489.00000 | 23.55421 | 41.34245 | 0.22436 | 6.89405 |
December | 497.00000 | 23.21926 | 36.68429 | 0.10374 | 6.15979 |
Annual Sum or Average | 5943.00000 | 23.72282 | 47.67367 | -0.0507 | 8.00915 |
Minimum of Months | 454.00000 | 23.16271 | 36.68429 | -0.5607 | 6.15979 |
Maximum of Months | 514.00000 | 24.14509 | 57.68568 | 0.37123 | 12.25627 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62550 | 37.79944 | 0.22242 | 6.66322 |
February | 454.00000 | 23.71698 | 39.98889 | 0.26564 | 6.84913 |
March | 514.00000 | 23.80226 | 42.70845 | 0.31343 | 7.53291 |
April | 485.00000 | 24.06402 | 45.49641 | 0.41977 | 8.89891 |
May | 508.00000 | 24.05187 | 45.06438 | -0.4869 | 10.38487 |
June | 496.00000 | 24.20494 | 50.78556 | -0.3618 | 8.04477 |
July | 497.00000 | 24.29323 | 54.56763 | -0.2871 | 7.10460 |
August | 514.00000 | 24.18357 | 55.72032 | -0.3210 | 7.43098 |
September | 485.00000 | 24.13854 | 52.55950 | -0.3988 | 8.71768 |
October | 502.00000 | 24.17611 | 42.58953 | 0.43219 | 9.43572 |
November | 489.00000 | 23.91283 | 37.87739 | 0.30890 | 7.40671 |
December | 497.00000 | 23.81884 | 32.61536 | 0.24515 | 6.56650 |
Annual Sum or Average | 5943.00000 | 24.00066 | 44.85850 | 0.02674 | 7.92677 |
Minimum of Months | 454.00000 | 23.62550 | 32.61536 | -0.4869 | 6.56650 |
Maximum of Months | 514.00000 | 24.29323 | 55.72032 | 0.43219 | 10.38487 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.88259 | 36.60677 | 0.30754 | 7.74934 |
February | 454.00000 | 23.82574 | 39.38583 | 0.31379 | 7.75211 |
March | 514.00000 | 23.87037 | 42.33819 | 0.35761 | 8.56119 |
April | 485.00000 | 24.15305 | 45.01600 | 0.48407 | 10.64036 |
May | 508.00000 | 24.20874 | 44.38254 | -0.3844 | 9.48669 |
June | 496.00000 | 24.24303 | 50.50437 | -0.3035 | 8.07424 |
July | 497.00000 | 24.39685 | 53.98216 | -0.1904 | 7.21683 |
August | 514.00000 | 24.25204 | 55.18082 | -0.2301 | 7.33418 |
September | 485.00000 | 24.24222 | 51.93123 | -0.3114 | 8.15894 |
October | 502.00000 | 24.28607 | 42.05662 | 0.48770 | 10.77212 |
November | 489.00000 | 23.99410 | 37.41333 | 0.35046 | 8.17704 |
December | 497.00000 | 23.88521 | 32.17467 | 0.28237 | 7.26166 |
Annual Sum or Average | 5943.00000 | 24.10501 | 44.29176 | 0.09461 | 8.43405 |
Minimum of Months | 454.00000 | 23.82574 | 32.17467 | -0.3844 | 7.21683 |
Maximum of Months | 514.00000 | 24.39685 | 55.18082 | 0.48770 | 10.77212 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13518 | 35.66694 | 0.43404 | 10.20963 |
February | 454.00000 | 24.01907 | 38.74826 | 0.40157 | 9.59820 |
March | 514.00000 | 23.93137 | 41.88253 | 0.38933 | 9.26158 |
April | 485.00000 | 24.17860 | 44.93383 | 0.48266 | 10.58993 |
May | 508.00000 | 23.98814 | 45.19595 | -0.4999 | 11.10075 |
June | 496.00000 | 24.13646 | 51.02785 | -0.3908 | 8.58191 |
July | 497.00000 | 24.29871 | 54.52488 | -0.2812 | 7.26583 |
August | 514.00000 | 24.25476 | 55.25002 | -0.2526 | 7.10617 |
September | 485.00000 | 24.33100 | 51.52774 | -0.2517 | 7.69981 |
October | 502.00000 | 24.46361 | 41.46711 | 0.57816 | 13.30359 |
November | 489.00000 | 24.32984 | 36.23956 | 0.49754 | 11.31516 |
December | 497.00000 | 24.33051 | 30.84189 | 0.46930 | 10.95688 |
Annual Sum or Average | 5943.00000 | 24.19986 | 43.99138 | 0.12818 | 9.74767 |
Minimum of Months | 454.00000 | 23.93137 | 30.84189 | -0.4999 | 7.10617 |
Maximum of Months | 514.00000 | 24.46361 | 55.25002 | 0.57816 | 13.30359 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.22278 | 35.77416 | 0.41235 | 9.15961 |
February | 454.00000 | 24.38112 | 37.55172 | 0.49312 | 10.74372 |
March | 514.00000 | 24.40048 | 40.20960 | 0.54987 | 12.07549 |
April | 485.00000 | 24.61648 | 43.38265 | 0.69088 | 16.10905 |
May | 508.00000 | 24.42230 | 43.51864 | -0.2475 | 7.84834 |
June | 496.00000 | 24.49418 | 49.41240 | -0.1115 | 6.80240 |
July | 497.00000 | 24.68013 | 52.86768 | 0.02934 | 7.21235 |
August | 514.00000 | 24.54243 | 53.92874 | 0.01790 | 6.86103 |
September | 485.00000 | 24.49599 | 50.81108 | -0.1502 | 7.08492 |
October | 502.00000 | 24.58044 | 40.86307 | 0.61579 | 14.11708 |
November | 489.00000 | 24.54161 | 35.43741 | 0.55113 | 12.32164 |
December | 497.00000 | 24.56906 | 30.12350 | 0.52597 | 11.75987 |
Annual Sum or Average | 5943.00000 | 24.49567 | 42.87110 | 0.27907 | 10.15656 |
Minimum of Months | 454.00000 | 24.22278 | 30.12350 | -0.2475 | 6.80240 |
Maximum of Months | 514.00000 | 24.68013 | 53.92874 | 0.69088 | 16.10905 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.57791 | 40.63183 | -0.0338 | 6.36482 |
February | 454.00000 | 22.77728 | 43.03346 | 0.03337 | 6.00027 |
March | 514.00000 | 22.92364 | 45.93882 | 0.09022 | 6.29789 |
April | 485.00000 | 23.41172 | 48.00190 | 0.24237 | 6.91746 |
May | 508.00000 | 23.69962 | 46.47815 | -0.6301 | 14.16217 |
June | 496.00000 | 23.96999 | 51.99024 | -0.4721 | 10.04514 |
July | 497.00000 | 24.09935 | 56.00829 | -0.3866 | 8.41672 |
August | 514.00000 | 23.96784 | 57.56907 | -0.4301 | 9.17877 |
September | 485.00000 | 23.79554 | 54.11235 | -0.5387 | 11.66528 |
October | 502.00000 | 23.68941 | 44.43773 | 0.29611 | 7.59868 |
November | 489.00000 | 23.01294 | 41.15230 | 0.08200 | 6.16280 |
December | 497.00000 | 22.59208 | 35.86806 | -0.0579 | 6.03918 |
Annual Sum or Average | 5943.00000 | 23.38084 | 47.14027 | -0.1526 | 8.25785 |
Minimum of Months | 454.00000 | 22.57791 | 35.86806 | -0.6301 | 6.00027 |
Maximum of Months | 514.00000 | 24.09935 | 57.56907 | 0.29611 | 14.16217 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.30228 | 38.49298 | 0.15282 | 6.73777 |
February | 385.00000 | 23.28002 | 41.16617 | 0.17066 | 6.79718 |
March | 433.00000 | 23.42565 | 43.62899 | 0.23235 | 7.66491 |
April | 410.00000 | 23.96913 | 45.64506 | 0.41554 | 9.83835 |
May | 430.00000 | 24.10017 | 44.78260 | -0.4501 | 11.34980 |
June | 418.00000 | 24.18773 | 50.78745 | -0.3512 | 9.25522 |
July | 422.00000 | 24.45703 | 54.26004 | -0.1975 | 7.89870 |
August | 433.00000 | 24.30408 | 55.75278 | -0.2386 | 7.89614 |
September | 410.00000 | 24.10364 | 52.52659 | -0.3880 | 9.74415 |
October | 427.00000 | 24.11116 | 43.20145 | 0.42379 | 9.75737 |
November | 417.00000 | 23.57550 | 39.22830 | 0.23377 | 7.08778 |
December | 422.00000 | 23.30828 | 33.78385 | 0.12662 | 6.28557 |
Annual Sum or Average | 5034.00000 | 23.84717 | 45.29471 | 0.00948 | 8.36662 |
Minimum of Months | 385.00000 | 23.28002 | 33.78385 | -0.4501 | 6.28557 |
Maximum of Months | 433.00000 | 24.45703 | 55.75278 | 0.42379 | 11.34980 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98477 | 36.43574 | 0.39900 | 10.22862 |
February | 454.00000 | 23.73432 | 39.87494 | 0.33211 | 9.21392 |
March | 514.00000 | 23.57463 | 43.35350 | 0.29584 | 8.59893 |
April | 485.00000 | 23.86389 | 46.13019 | 0.39057 | 9.31932 |
May | 508.00000 | 23.75687 | 46.10609 | -0.5940 | 13.71765 |
June | 496.00000 | 23.91793 | 52.10997 | -0.4865 | 10.53694 |
July | 497.00000 | 24.13060 | 55.80649 | -0.3644 | 8.40364 |
August | 514.00000 | 24.14878 | 56.51787 | -0.3170 | 7.93992 |
September | 485.00000 | 24.22645 | 52.04459 | -0.2993 | 8.58958 |
October | 502.00000 | 24.35924 | 42.04664 | 0.54268 | 12.78472 |
November | 489.00000 | 24.15091 | 37.37139 | 0.44918 | 10.86613 |
December | 497.00000 | 24.12664 | 31.80129 | 0.41248 | 10.60673 |
Annual Sum or Average | 5943.00000 | 23.99851 | 45.01668 | 0.06014 | 10.07558 |
Minimum of Months | 454.00000 | 23.57463 | 31.80129 | -0.5940 | 7.93992 |
Maximum of Months | 514.00000 | 24.35924 | 56.51787 | 0.54268 | 13.71765 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.31541 | 38.58182 | 0.16664 | 7.05563 |
February | 454.00000 | 23.48369 | 40.81327 | 0.23141 | 7.41762 |
March | 514.00000 | 23.56831 | 43.50897 | 0.27946 | 8.01533 |
April | 485.00000 | 24.07062 | 45.53803 | 0.46400 | 10.77190 |
May | 508.00000 | 24.11909 | 44.80812 | -0.4092 | 10.55795 |
June | 496.00000 | 24.23948 | 50.70286 | -0.2845 | 8.04029 |
July | 497.00000 | 24.43682 | 54.42537 | -0.1607 | 7.23319 |
August | 514.00000 | 24.30461 | 55.78389 | -0.1974 | 7.15734 |
September | 485.00000 | 24.26242 | 52.02423 | -0.2899 | 8.29914 |
October | 502.00000 | 24.17878 | 42.76337 | 0.45950 | 10.61644 |
November | 489.00000 | 23.73170 | 38.84039 | 0.28763 | 7.90905 |
December | 497.00000 | 23.47979 | 33.62761 | 0.17973 | 6.91108 |
Annual Sum or Average | 5943.00000 | 23.93514 | 45.15988 | 0.05840 | 8.33516 |
Minimum of Months | 454.00000 | 23.31541 | 33.62761 | -0.4092 | 6.91108 |
Maximum of Months | 514.00000 | 24.43682 | 55.78389 | 0.46400 | 10.77190 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.81571 | 41.98573 | -0.2377 | 8.50317 |
February | 454.00000 | 22.03663 | 44.83824 | -0.1573 | 7.24236 |
March | 514.00000 | 22.31415 | 47.41781 | -0.0679 | 6.91647 |
April | 485.00000 | 23.06391 | 49.04431 | 0.15610 | 6.90348 |
May | 508.00000 | 23.37186 | 47.48457 | -0.7433 | 18.48659 |
June | 496.00000 | 23.82944 | 52.45904 | -0.5181 | 11.49978 |
July | 497.00000 | 24.03481 | 56.26073 | -0.4019 | 9.02407 |
August | 514.00000 | 23.87914 | 57.97754 | -0.4552 | 10.01451 |
September | 485.00000 | 23.57591 | 55.01248 | -0.6138 | 14.20232 |
October | 502.00000 | 23.37349 | 45.45539 | 0.21693 | 7.47919 |
November | 489.00000 | 22.34177 | 42.44807 | -0.0922 | 6.93344 |
December | 497.00000 | 21.79494 | 37.35368 | -0.2662 | 8.16900 |
Annual Sum or Average | 5943.00000 | 22.95946 | 48.17736 | -0.2666 | 9.63831 |
Minimum of Months | 454.00000 | 21.79494 | 37.35368 | -0.7433 | 6.90348 |
Maximum of Months | 514.00000 | 24.03481 | 57.97754 | 0.21693 | 18.48659 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.75925 | 39.64486 | 0.00260 | 7.14374 |
February | 454.00000 | 22.73961 | 42.76610 | 0.02870 | 6.95612 |
March | 514.00000 | 23.02897 | 45.06223 | 0.12820 | 7.59359 |
April | 485.00000 | 23.73940 | 46.43410 | 0.36617 | 9.46645 |
May | 508.00000 | 23.86174 | 45.56465 | -0.5244 | 13.23872 |
June | 496.00000 | 24.05616 | 51.29693 | -0.3774 | 9.89753 |
July | 497.00000 | 24.34516 | 54.66663 | -0.2070 | 8.01055 |
August | 514.00000 | 24.20299 | 56.09534 | -0.2465 | 8.03738 |
September | 485.00000 | 23.92664 | 53.27000 | -0.4336 | 10.94333 |
October | 502.00000 | 23.87358 | 43.69535 | 0.36864 | 9.07909 |
November | 489.00000 | 23.15213 | 40.15166 | 0.11713 | 6.74812 |
December | 497.00000 | 22.76132 | 35.23664 | -0.0221 | 6.56833 |
Annual Sum or Average | 5943.00000 | 23.54293 | 46.19052 | -0.0680 | 8.65135 |
Minimum of Months | 454.00000 | 22.73961 | 35.23664 | -0.5244 | 6.56833 |
Maximum of Months | 514.00000 | 24.34516 | 56.09534 | 0.36864 | 13.23872 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.47768 | 37.28207 | 0.24985 | 9.43031 |
February | 454.00000 | 23.20558 | 41.25866 | 0.18612 | 8.85474 |
March | 514.00000 | 23.11658 | 44.55739 | 0.16976 | 8.45410 |
April | 485.00000 | 23.57732 | 47.01388 | 0.31781 | 9.05556 |
May | 508.00000 | 23.45149 | 47.04283 | -0.7009 | 17.77635 |
June | 496.00000 | 23.77381 | 52.58479 | -0.5333 | 12.14885 |
July | 497.00000 | 24.06093 | 56.07494 | -0.3804 | 9.10908 |
August | 514.00000 | 24.06783 | 56.89318 | -0.3386 | 8.68166 |
September | 485.00000 | 24.06295 | 52.74492 | -0.3569 | 10.11720 |
October | 502.00000 | 24.14979 | 42.83380 | 0.48637 | 12.11705 |
November | 489.00000 | 23.75524 | 38.06780 | 0.33265 | 9.79709 |
December | 497.00000 | 23.64336 | 32.67147 | 0.27036 | 9.47845 |
Annual Sum or Average | 5943.00000 | 23.69731 | 45.79844 | -0.0276 | 10.43722 |
Minimum of Months | 454.00000 | 23.11658 | 32.67147 | -0.7009 | 8.45410 |
Maximum of Months | 514.00000 | 24.14979 | 56.89318 | 0.48637 | 17.77635 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.72827 | 39.51955 | 0.00613 | 7.59791 |
February | 454.00000 | 22.90463 | 42.21447 | 0.08057 | 7.44605 |
March | 514.00000 | 23.10187 | 44.67804 | 0.15594 | 7.85690 |
April | 485.00000 | 23.83293 | 46.31865 | 0.40277 | 10.38732 |
May | 508.00000 | 23.89110 | 45.55759 | -0.4913 | 13.27033 |
June | 496.00000 | 24.13361 | 51.07380 | -0.3190 | 9.00543 |
July | 497.00000 | 24.38791 | 54.64218 | -0.1703 | 7.62172 |
August | 514.00000 | 24.24798 | 56.09674 | -0.2121 | 7.58476 |
September | 485.00000 | 24.12480 | 52.67045 | -0.3393 | 9.55578 |
October | 502.00000 | 23.95990 | 43.54680 | 0.40234 | 10.19516 |
November | 489.00000 | 23.24334 | 39.74862 | 0.15607 | 7.61382 |
December | 497.00000 | 22.87574 | 34.71705 | 0.01798 | 7.18345 |
Annual Sum or Average | 5943.00000 | 23.62384 | 45.93591 | -0.0275 | 8.78536 |
Minimum of Months | 454.00000 | 22.72827 | 34.71705 | -0.4913 | 7.18345 |
Maximum of Months | 514.00000 | 24.38791 | 56.09674 | 0.40277 | 13.27033 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.347522E+11 | 146289.58 | 13-JAN-14:10 | 271.75 | 0.281509E+12 | 0.00 | 0.316262E+12 | 3.03 | 8.68 | 05-JAN-10:30 | 0.00 | 0.00 |
February | 0.196169E+11 | 147150.44 | 03-FEB-13:40 | 214.44 | 0.160644E+12 | 0.00 | 0.180261E+12 | 2.65 | 8.68 | 22-FEB-12:20 | 0.00 | 0.00 |
March | 0.204179E+11 | 151825.05 | 23-MAR-15:00 | 231.92 | 0.166624E+12 | 0.00 | 0.187042E+12 | 2.59 | 8.68 | 01-MAR-11:20 | 0.00 | 0.00 |
April | 0.365154E+11 | 159430.70 | 12-APR-12:50 | 335.37 | 0.294499E+12 | 0.00 | 0.331015E+12 | 3.85 | 8.68 | 08-APR-14:40 | 0.00 | 0.00 |
May | 0.378441E+11 | 160081.93 | 04-MAY-13:50 | 365.23 | 0.307611E+12 | 0.00 | 0.345455E+12 | 4.07 | 8.68 | 16-MAY-12:30 | 0.00 | 0.00 |
June | 0.622509E+11 | 161959.74 | 19-JUN-10:30 | 437.46 | 0.488027E+12 | 0.00 | 0.550278E+12 | 4.96 | 8.69 | 26-JUN-05:03 | 0.00 | 0.00 |
July | 0.926392E+11 | 162227.05 | 17-JUL-10:00 | 561.82 | 0.707487E+12 | 0.00 | 0.800126E+12 | 6.05 | 8.69 | 25-JUL-04:13 | 0.00 | 0.00 |
August | 0.104705E+12 | 161871.03 | 16-AUG-07:40 | 615.83 | 0.789522E+12 | 0.00 | 0.894227E+12 | 6.60 | 8.70 | 30-AUG-05:03 | 0.00 | 0.00 |
September | 0.655015E+11 | 158710.35 | 11-SEP-12:20 | 423.73 | 0.513448E+12 | 0.00 | 0.578949E+12 | 4.78 | 8.69 | 07-SEP-05:04 | 0.00 | 0.00 |
October | 0.753037E+11 | 157725.91 | 30-OCT-13:00 | 451.40 | 0.582687E+12 | 0.00 | 0.657991E+12 | 4.90 | 8.68 | 14-OCT-05:03 | 0.00 | 0.00 |
November | 0.376410E+11 | 147756.52 | 30-NOV-14:20 | 296.24 | 0.300602E+12 | 0.00 | 0.338243E+12 | 3.39 | 8.68 | 19-NOV-10:30 | 0.00 | 0.00 |
December | 0.417667E+11 | 148927.57 | 05-DEC-13:30 | 291.73 | 0.326674E+12 | 0.00 | 0.368441E+12 | 3.20 | 8.68 | 25-DEC-12:44 | 0.00 | 0.00 |
Annual Sum or Average | 0.628954E+12 | 4496.94 | 0.491934E+13 | 0.00 | 0.554829E+13 | 4.18 | 0.00 | 0.00 | ||||
Minimum of Months | 0.196169E+11 | 146289.58 | 214.44 | 0.160644E+12 | 0.00 | 0.180261E+12 | 2.59 | 8.68 | 0.00 | 0.00 | ||
Maximum of Months | 0.104705E+12 | 162227.05 | 615.83 | 0.789522E+12 | 0.00 | 0.894227E+12 | 6.60 | 8.70 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.261069E+09 | 85220.58 | 18-JAN-13:30 | 1.50 | 0.208435E+10 | 0.00 | 0.234542E+10 | 0.02 | 8.62 | 18-JAN-14:50 | 0.00 | 0.00 |
February | 0.186673E+09 | 77311.90 | 03-FEB-14:05 | 0.92 | 0.152295E+10 | 0.00 | 0.170962E+10 | 0.01 | 8.66 | 01-FEB-11:40 | 0.00 | 0.00 |
March | 0.851197E+09 | 76390.64 | 23-MAR-13:05 | 4.00 | 0.690189E+10 | 0.00 | 0.775309E+10 | 0.04 | 8.35 | 23-MAR-12:30 | 0.00 | 0.00 |
April | 0.163081E+10 | 85344.49 | 26-APR-10:10 | 8.08 | 0.132017E+11 | 0.00 | 0.148325E+11 | 0.09 | 8.44 | 25-APR-14:20 | 0.00 | 0.00 |
May | 0.201485E+09 | 73125.89 | 03-MAY-13:05 | 1.50 | 0.164314E+10 | 0.00 | 0.184462E+10 | 0.02 | 8.44 | 04-MAY-12:20 | 0.00 | 0.00 |
June | 0.719962E+10 | 99708.47 | 26-JUN-12:05 | 29.75 | 0.571964E+11 | 0.00 | 0.643960E+11 | 0.33 | 8.33 | 21-JUN-12:30 | 0.00 | 0.00 |
July | 0.298663E+11 | 121047.25 | 28-JUL-12:30 | 104.25 | 0.224256E+12 | 0.00 | 0.254123E+12 | 1.06 | 8.41 | 25-JUL-16:50 | 0.00 | 0.00 |
August | 0.420478E+11 | 134496.32 | 07-AUG-10:30 | 143.67 | 0.313542E+12 | 0.00 | 0.355590E+12 | 1.46 | 8.42 | 07-AUG-17:00 | 0.00 | 0.00 |
September | 0.152379E+11 | 105786.41 | 21-SEP-12:05 | 60.67 | 0.119492E+12 | 0.00 | 0.134730E+12 | 0.66 | 8.59 | 30-SEP-14:30 | 0.00 | 0.00 |
October | 0.225029E+11 | 130452.63 | 03-OCT-13:40 | 81.42 | 0.172406E+12 | 0.00 | 0.194909E+12 | 0.85 | 8.67 | 14-OCT-10:00 | 0.00 | 0.00 |
November | 0.434255E+09 | 77539.45 | 28-NOV-14:05 | 1.92 | 0.350085E+10 | 0.00 | 0.393510E+10 | 0.02 | 8.66 | 30-NOV-13:50 | 0.00 | 0.00 |
December | 0.169154E+10 | 81144.53 | 19-DEC-13:05 | 7.75 | 0.137481E+11 | 0.00 | 0.154396E+11 | 0.09 | 8.67 | 05-DEC-09:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.122112E+12 | 445.42 | 0.929496E+12 | 0.00 | 0.105161E+13 | 0.39 | 0.00 | 0.00 | ||||
Minimum of Months | 0.186673E+09 | 73125.89 | 0.92 | 0.152295E+10 | 0.00 | 0.170962E+10 | 0.01 | 8.33 | 0.00 | 0.00 | ||
Maximum of Months | 0.420478E+11 | 134496.32 | 143.67 | 0.313542E+12 | 0.00 | 0.355590E+12 | 1.46 | 8.67 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.193891E+11 | 744.00 | 43776.24 | 03-JAN-12:05 | 171001.09 | 14-JAN-12:00 | 19.32 | 18.76 | 15.54 |
February | 0.145732E+11 | 672.00 | 43776.24 | 01-FEB-07:55 | 313556.91 | 01-FEB-12:05 | 19.55 | 18.48 | 15.54 |
March | 0.199261E+11 | 744.00 | 43776.24 | 01-MAR-10:20 | 426917.00 | 23-MAR-14:05 | 20.50 | 18.66 | 15.54 |
April | 0.497274E+11 | 720.00 | 43776.24 | 01-APR-08:30 | 695691.49 | 26-APR-11:00 | 23.92 | 19.68 | 15.54 |
May | 0.340353E+11 | 744.00 | 43776.24 | 01-MAY-09:40 | 96375.89 | 04-MAY-12:05 | 19.39 | 18.81 | 15.54 |
June | 0.520725E+11 | 720.00 | 43776.24 | 01-JUN-08:40 | 377033.04 | 29-JUN-11:00 | 21.38 | 19.68 | 15.54 |
July | 0.878668E+11 | 744.00 | 43776.24 | 01-JUL-05:30 | 693320.13 | 19-JUL-14:00 | 26.52 | 21.58 | 15.54 |
August | 0.112419E+12 | 744.00 | 43776.24 | 01-AUG-00:10 | 771743.62 | 18-AUG-12:05 | 32.61 | 23.12 | 15.54 |
September | 0.537249E+11 | 720.00 | 43776.24 | 01-SEP-08:40 | 276643.15 | 21-SEP-13:30 | 20.67 | 19.90 | 15.54 |
October | 0.703053E+11 | 744.00 | 43776.24 | 01-OCT-00:10 | 466098.23 | 01-OCT-12:00 | 23.10 | 20.92 | 15.54 |
November | 0.292303E+11 | 720.00 | 43776.24 | 01-NOV-11:30 | 508439.38 | 19-NOV-13:02 | 21.04 | 18.93 | 15.54 |
December | 0.410772E+11 | 744.00 | 43776.24 | 03-DEC-13:32 | 628525.23 | 19-DEC-13:00 | 22.94 | 19.37 | 15.54 |
Annual Sum or Average | 0.584347E+12 | 8760.00 | 22.61 | 19.84 | 15.54 | ||||
Minimum of Months | 0.145732E+11 | 672.00 | 43776.24 | 96375.89 | 19.32 | 18.48 | 15.54 | ||
Maximum of Months | 0.112419E+12 | 744.00 | 43776.24 | 771743.62 | 32.61 | 23.12 | 15.54 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.988334E+09 | 194.71 | 14387.61 | 13-JAN-13:50 | 1057279.02 | 24-JAN-15:05 | 21.79 | 21.21 | 15.94 |
February | 0.321278E+09 | 140.00 | 14387.61 | 01-FEB-12:00 | 1100150.23 | 03-FEB-13:40 | 21.50 | 21.13 | 13.41 |
March | 0.853510E+09 | 151.91 | 14387.61 | 22-MAR-11:00 | 1007267.68 | 10-MAR-13:30 | 21.43 | 21.07 | 12.67 |
April | 0.208926E+10 | 241.21 | 14387.61 | 04-APR-11:00 | 1060052.01 | 12-APR-15:00 | 21.70 | 21.06 | 20.34 |
May | 0.147215E+10 | 272.87 | 14387.61 | 02-MAY-12:30 | 1092191.97 | 03-MAY-14:40 | 21.74 | 21.09 | 22.13 |
June | 0.570365E+10 | 371.64 | 14387.61 | 13-JUN-10:40 | 1046409.79 | 21-JUN-14:30 | 22.31 | 21.26 | 28.42 |
July | 0.129414E+11 | 463.10 | 14387.61 | 01-JUL-10:20 | 1040493.21 | 05-JUL-12:40 | 23.13 | 21.66 | 34.90 |
August | 0.151503E+11 | 478.78 | 14387.61 | 01-AUG-09:50 | 1017696.26 | 21-AUG-13:50 | 23.41 | 21.77 | 38.22 |
September | 0.746983E+10 | 375.10 | 14387.61 | 01-SEP-10:30 | 1050159.16 | 01-SEP-13:50 | 22.56 | 21.46 | 28.25 |
October | 0.678515E+10 | 379.04 | 14387.61 | 01-OCT-10:40 | 1109429.51 | 12-OCT-13:50 | 22.67 | 21.43 | 28.18 |
November | 0.762012E+09 | 201.03 | 14387.61 | 10-NOV-12:05 | 1100218.26 | 30-NOV-14:30 | 21.77 | 21.12 | 17.40 |
December | 0.571910E+09 | 208.91 | 14387.61 | 07-DEC-13:20 | 1098238.44 | 18-DEC-12:00 | 21.82 | 21.14 | 17.16 |
Annual Sum or Average | 0.551088E+11 | 3478.30 | 22.16 | 21.29 | 23.16 | ||||
Minimum of Months | 0.321278E+09 | 140.00 | 14387.61 | 1007267.68 | 21.43 | 21.06 | 12.67 | ||
Maximum of Months | 0.151503E+11 | 478.78 | 14387.61 | 1109429.51 | 23.41 | 21.77 | 38.22 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 12666022.02 | 0.67 | 14387.61 | 13-JAN-14:40 | 917131.87 | 13-JAN-14:40 | 21.79 | 21.79 | 0.04 |
February | 1797895.67 | 0.33 | 1878.38 | 01-FEB-11:50 | 932276.54 | 01-FEB-11:50 | 21.50 | 21.50 | 0.02 |
March | 0.155386E+09 | 3.00 | 14387.61 | 22-MAR-12:30 | 769971.66 | 23-MAR-13:30 | 21.43 | 21.41 | 0.20 |
April | 0.336670E+09 | 6.50 | 14387.61 | 04-APR-12:40 | 831648.29 | 12-APR-14:00 | 21.70 | 21.67 | 0.42 |
May | 30914084.41 | 0.67 | 14387.61 | 03-MAY-14:05 | 805919.11 | 03-MAY-13:05 | 21.74 | 21.73 | 0.04 |
June | 0.165314E+10 | 31.92 | 14387.61 | 14-JUN-10:40 | 778186.75 | 21-JUN-14:05 | 22.31 | 22.16 | 2.11 |
July | 0.567160E+10 | 109.50 | 14387.61 | 03-JUL-12:05 | 912587.36 | 28-JUL-12:30 | 23.13 | 22.62 | 7.17 |
August | 0.779521E+10 | 150.50 | 14387.61 | 01-AUG-12:30 | 984120.17 | 07-AUG-10:30 | 23.41 | 22.70 | 9.84 |
September | 0.301571E+10 | 58.50 | 14387.61 | 01-SEP-13:20 | 878180.28 | 29-SEP-08:40 | 22.56 | 22.30 | 4.02 |
October | 0.304024E+10 | 73.29 | 14387.61 | 02-OCT-07:20 | 990884.76 | 16-OCT-08:70 | 22.67 | 22.30 | 4.83 |
November | 2435229.35 | 0.75 | 1593.94 | 30-NOV-14:00 | 912304.58 | 30-NOV-14:00 | 21.77 | 21.77 | 0.05 |
December | 12702550.61 | 3.17 | 2683.52 | 05-DEC-14:10 | 931806.40 | 19-DEC-11:00 | 21.82 | 21.81 | 0.21 |
Annual Sum or Average | 0.217285E+11 | 438.79 | 22.16 | 21.98 | 2.44 | ||||
Minimum of Months | 1797895.67 | 0.33 | 1593.94 | 769971.66 | 21.43 | 21.41 | 0.02 | ||
Maximum of Months | 0.779521E+10 | 150.50 | 14387.61 | 990884.76 | 23.41 | 22.70 | 9.84 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.114117E+11 | 0.00 | 111.86 | 488861.17 | 09-JAN-06:02 | 0.00 | 32.42 | 39.91 | 0.02 | 0.00 | 0.00 | 0.39 | 09-JAN-06:02 |
February | 0.287112E+10 | 0.00 | 82.89 | 99342.68 | 09-FEB-07:05 | 0.00 | 27.72 | 34.36 | 0.01 | 0.00 | 0.00 | 0.08 | 09-FEB-07:05 |
March | 0.824188E+10 | 0.00 | 107.10 | 459524.68 | 30-MAR-05:03 | 0.00 | 28.16 | 35.76 | 0.01 | 0.00 | 0.00 | 0.37 | 30-MAR-05:03 |
April | 0.316984E+09 | 0.00 | 14.33 | 91375.61 | 01-APR-06:05 | 0.00 | 27.34 | 28.41 | 0.00 | 0.00 | 0.00 | 0.07 | 01-APR-06:05 |
May | 66164186.48 | 0.00 | 6.76 | 64103.97 | 09-MAY-09:40 | 0.00 | 27.05 | 27.55 | 0.00 | 0.00 | 0.00 | 0.05 | 09-MAY-09:40 |
June | 766.02 | 0.00 | 0.17 | 1.28 | 28-JUN-14:00 | 0.00 | 27.15 | 27.17 | 0.00 | 0.00 | 0.00 | 0.00 | 28-JUN-14:00 |
July | 5875.13 | 0.00 | 1.28 | 1.33 | 08-JUL-04:12 | 0.00 | 27.15 | 27.25 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-04:12 |
August | 33733.27 | 0.00 | 6.58 | 2.57 | 15-AUG-11:20 | 0.00 | 27.15 | 27.64 | 0.00 | 0.00 | 0.00 | 0.00 | 15-AUG-11:20 |
September | 789.43 | 0.00 | 0.17 | 1.32 | 13-SEP-10:00 | 0.00 | 27.15 | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13-SEP-10:00 |
October | 61846429.56 | 0.00 | 13.14 | 21896.68 | 12-OCT-06:10 | 0.00 | 26.69 | 27.67 | 0.00 | 0.00 | 0.00 | 0.02 | 12-OCT-06:10 |
November | 0.742710E+09 | 0.00 | 54.90 | 77564.28 | 24-NOV-06:03 | 0.00 | 27.07 | 31.23 | 0.00 | 0.00 | 0.00 | 0.06 | 24-NOV-06:03 |
December | 0.637486E+10 | 0.00 | 94.36 | 152984.15 | 13-DEC-06:03 | 0.00 | 29.32 | 35.86 | 0.01 | 0.00 | 0.00 | 0.12 | 13-DEC-06:03 |
Annual Sum or Average | 0.300873E+11 | 0.00 | 493.53 | 0.00 | 27.87 | 30.83 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 766.02 | 0.00 | 0.17 | 1.28 | 0.00 | 26.69 | 27.16 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114117E+11 | 0.00 | 111.86 | 488861.17 | 0.00 | 32.42 | 39.91 | 0.02 | 0.00 | 0.00 | 0.39 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 19.32 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.55 | 19.55 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 23.92 | 23.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.39 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.38 | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 26.52 | 26.52 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 32.61 | 32.61 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 20.67 | 20.67 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 23.10 | 23.10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.04 | 21.04 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 22.94 | 22.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 22.61 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | 32.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.214056E+11 | 0.00 | 224.23 | 0.213595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86455.28 | 18-JAN-14:10 | 86455.28 | 18-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.120058E+11 | 0.00 | 170.31 | 0.119342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80732.21 | 01-FEB-12:00 | 80732.21 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.142555E+11 | 0.00 | 173.92 | 0.138114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93730.48 | 23-MAR-14:00 | 78764.63 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.317720E+11 | 0.00 | 293.40 | 0.317480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105862.64 | 26-APR-13:05 | 105138.94 | 26-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.280624E+11 | 0.00 | 330.28 | 0.279769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76867.45 | 03-MAY-13:00 | 76867.45 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.509381E+11 | 0.00 | 422.74 | 0.466190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118679.78 | 29-JUN-13:00 | 85458.42 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.929980E+11 | 0.00 | 543.01 | 0.693219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163573.68 | 31-JUL-16:00 | 108436.52 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.114054E+12 | 0.00 | 597.64 | 0.800233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177760.91 | 07-AUG-10:40 | 111233.39 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.579903E+11 | 0.00 | 402.53 | 0.488571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132003.26 | 22-SEP-11:30 | 131166.28 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.747789E+11 | 0.00 | 423.20 | 0.626031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162565.11 | 03-OCT-13:20 | 133583.06 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.249936E+11 | 0.00 | 256.67 | 0.245685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92585.36 | 28-NOV-14:00 | 92585.36 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.288812E+11 | 0.00 | 236.46 | 0.288014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98164.13 | 05-DEC-15:00 | 98164.13 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552136E+12 | 0.00 | 4074.40 | 0.467624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120058E+11 | 0.00 | 170.31 | 0.119342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76867.45 | 76867.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114054E+12 | 0.00 | 597.64 | 0.800233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177760.91 | 133583.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.228955E+12 | 0.00 | 252.05 | 0.228366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 731976.94 | 18-JAN-13:05 | 731976.94 | 18-JAN-13:05 | 0.00 | 0.00 | 0.00 |
February | 0.130324E+12 | 0.00 | 194.09 | 0.129588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 668974.22 | 01-FEB-12:00 | 668974.22 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.135732E+12 | 0.00 | 196.55 | 0.132019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 820041.97 | 23-MAR-14:05 | 659748.02 | 23-MAR-14:05 | 0.00 | 0.00 | 0.00 |
April | 0.225478E+12 | 0.00 | 284.57 | 0.225391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 849861.81 | 26-APR-14:05 | 849861.81 | 26-APR-14:05 | 0.00 | 0.00 | 0.00 |
May | 0.232424E+12 | 0.00 | 334.52 | 0.231782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 676639.13 | 04-MAY-12:05 | 676639.13 | 04-MAY-12:05 | 0.00 | 0.00 | 0.00 |
June | 0.402723E+12 | 0.00 | 409.95 | 0.370860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 997000.23 | 29-JUN-13:00 | 699515.98 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.692662E+12 | 0.00 | 453.79 | 0.526366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1228992.02 | 28-JUL-12:30 | 896355.12 | 31-JUL-14:05 | 0.00 | 0.00 | 0.00 |
August | 0.817380E+12 | 0.00 | 466.76 | 0.592133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1277590.15 | 07-AUG-10:30 | 924211.91 | 17-AUG-14:05 | 0.00 | 0.00 | 0.00 |
September | 0.482204E+12 | 0.00 | 401.33 | 0.409898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1127309.67 | 30-SEP-05:02 | 1127309.67 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.565784E+12 | 0.00 | 407.93 | 0.484908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1304991.57 | 03-OCT-13:40 | 1123278.94 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.238333E+12 | 0.00 | 264.24 | 0.234981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 704401.14 | 28-NOV-14:00 | 704401.14 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.258017E+12 | 0.00 | 259.92 | 0.257620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 757773.73 | 05-DEC-15:05 | 757773.73 | 05-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441002E+13 | 0.00 | 3925.69 | 0.382391E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.130324E+12 | 0.00 | 194.09 | 0.129588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 668974.22 | 659748.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.817380E+12 | 0.00 | 466.76 | 0.592133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1304991.57 | 1127309.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.128754E+11 | 0.00 | 204.08 | 0.128439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71465.07 | 18-JAN-13:50 | 71465.07 | 18-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.716560E+10 | 0.00 | 158.89 | 0.711362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60523.57 | 03-FEB-15:00 | 60523.57 | 03-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.893663E+10 | 0.00 | 154.38 | 0.873376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76923.11 | 23-MAR-14:30 | 66973.23 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.218585E+11 | 0.00 | 265.48 | 0.218544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99481.85 | 26-APR-14:00 | 99481.85 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.224028E+11 | 0.00 | 316.38 | 0.223485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75847.23 | 03-MAY-13:10 | 75847.23 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.414600E+11 | 0.00 | 398.73 | 0.379768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111652.80 | 29-JUN-13:00 | 75644.39 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.739668E+11 | 0.00 | 443.00 | 0.561033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159235.17 | 31-JUL-15:40 | 106729.81 | 31-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.864253E+11 | 0.00 | 452.64 | 0.623553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160105.33 | 14-AUG-13:50 | 106976.61 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.472299E+11 | 0.00 | 383.36 | 0.402995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124695.30 | 29-SEP-13:40 | 124695.30 | 29-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.543329E+11 | 0.00 | 387.71 | 0.464682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143773.62 | 03-OCT-13:30 | 133114.68 | 16-OCT-14:05 | 0.00 | 0.00 | 0.00 |
November | 0.138355E+11 | 0.00 | 230.85 | 0.137213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67801.39 | 28-NOV-14:00 | 67801.39 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.158062E+11 | 0.00 | 208.54 | 0.157704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74696.09 | 05-DEC-15:00 | 74696.09 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406296E+12 | 0.00 | 3604.03 | 0.345589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.716560E+10 | 0.00 | 154.38 | 0.711362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60523.57 | 60523.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.864253E+11 | 0.00 | 452.64 | 0.623553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160105.33 | 133114.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.162015E+11 | 0.00 | 192.23 | 0.157361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85227.95 | 17-JAN-12:05 | 71535.46 | 17-JAN-12:05 | 0.00 | 0.00 | 0.00 |
February | 0.896401E+10 | 0.00 | 142.95 | 0.827871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62133.86 | 13-FEB-07:23 | 53825.53 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.100962E+11 | 0.00 | 161.61 | 0.898264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56594.43 | 22-MAR-13:00 | 44992.47 | 10-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.220655E+11 | 0.00 | 246.77 | 0.201827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65665.45 | 27-APR-06:25 | 58756.63 | 03-APR-10:00 | 0.00 | 0.00 | 0.00 |
May | 0.212420E+11 | 0.00 | 263.77 | 0.194641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68749.65 | 05-MAY-06:25 | 48838.57 | 04-MAY-12:10 | 0.00 | 0.00 | 0.00 |
June | 0.385478E+11 | 0.00 | 328.42 | 0.315885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83302.67 | 30-JUN-06:25 | 63965.22 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.528255E+11 | 0.00 | 329.47 | 0.421849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112125.79 | 31-JUL-09:20 | 70900.12 | 31-JUL-09:30 | 0.00 | 0.00 | 0.00 |
August | 0.600294E+11 | 0.00 | 362.71 | 0.464196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117534.10 | 07-AUG-10:10 | 73211.79 | 14-AUG-10:00 | 0.00 | 0.00 | 0.00 |
September | 0.357270E+11 | 0.00 | 289.26 | 0.279597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99238.04 | 22-SEP-10:00 | 60213.06 | 05-SEP-12:05 | 0.00 | 0.00 | 0.00 |
October | 0.473251E+11 | 0.00 | 294.45 | 0.386887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116995.00 | 05-OCT-13:00 | 97026.15 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 |
November | 0.178655E+11 | 0.00 | 208.45 | 0.173911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67309.42 | 10-NOV-07:16 | 62152.42 | 27-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.202930E+11 | 0.00 | 194.95 | 0.197604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72595.59 | 04-DEC-10:00 | 72595.59 | 04-DEC-10:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351183E+12 | 0.00 | 3015.04 | 0.296637E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.896401E+10 | 0.00 | 142.95 | 0.827871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56594.43 | 44992.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.600294E+11 | 0.00 | 362.71 | 0.464196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117534.10 | 97026.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.802613E+10 | 0.508820E+10 | 462.16 | 0.796215E+10 | 63977056.69 | 0.00 | 0.31 | 14-JAN-11:00 | 0.01 | 29-JAN-05:25 | 104900.67 | 14-JAN-11:00 | 104900.67 | 14-JAN-11:00 | 9009.49 | 17-JAN-12:00 | 36321.88 | 14-JAN-11:10 | 0.00 |
February | 0.744384E+10 | 0.478508E+10 | 366.74 | 0.738414E+10 | 59695932.15 | 0.00 | 0.50 | 01-FEB-12:00 | 0.01 | 27-FEB-04:10 | 194182.11 | 01-FEB-12:00 | 194182.11 | 01-FEB-12:00 | 11658.85 | 01-FEB-13:30 | 60497.10 | 01-FEB-12:00 | 0.00 |
March | 0.398588E+11 | 0.135453E+11 | 421.61 | 0.319603E+11 | 0.789844E+10 | 0.00 | 0.60 | 23-MAR-14:00 | 0.01 | 04-MAR-06:00 | 260635.96 | 23-MAR-14:00 | 226916.70 | 11-MAR-14:00 | 80172.88 | 23-MAR-15:20 | 69796.44 | 11-MAR-14:00 | 0.00 |
April | 0.245355E+12 | 0.650949E+11 | 493.04 | 0.187297E+12 | 0.580574E+11 | 0.00 | 0.97 | 26-APR-11:00 | 0.01 | 17-APR-05:03 | 447546.03 | 26-APR-11:00 | 406628.13 | 26-APR-13:00 | 104061.64 | 25-APR-09:30 | 124588.22 | 26-APR-11:00 | 0.00 |
May | 0.899389E+09 | 0.303517E+10 | 232.28 | 0.829920E+09 | 69468353.94 | 0.00 | 0.13 | 04-MAY-12:00 | 0.01 | 14-MAY-14:44 | 47464.01 | 04-MAY-12:00 | 42750.23 | 03-MAY-12:00 | 6176.56 | 04-MAY-12:00 | 14473.27 | 04-MAY-12:00 | 0.00 |
June | 0.659318E+11 | 0.206195E+11 | 339.73 | 0.473480E+11 | 0.185838E+11 | 0.00 | 0.54 | 29-JUN-11:00 | 0.01 | 02-JUN-04:55 | 244257.59 | 29-JUN-11:00 | 163478.86 | 29-JUN-11:00 | 80778.74 | 29-JUN-11:00 | 65653.19 | 29-JUN-11:00 | 0.00 |
July | 0.381008E+12 | 0.987367E+11 | 671.62 | 0.239182E+12 | 0.141826E+12 | 0.00 | 0.95 | 31-JUL-14:00 | 0.01 | 05-JUL-21:12 | 463654.75 | 31-JUL-14:00 | 317642.26 | 31-JUL-14:00 | 167477.83 | 31-JUL-23:55 | 125022.68 | 19-JUL-14:00 | 0.00 |
August | 0.856170E+12 | 0.209133E+12 | 743.17 | 0.486085E+12 | 0.370085E+12 | 0.00 | 1.00 | 05-AUG-12:40 | 0.01 | 31-AUG-23:10 | 493278.58 | 14-AUG-10:00 | 377378.78 | 29-AUG-13:00 | 241863.79 | 18-AUG-08:20 | 136188.33 | 14-AUG-11:00 | 0.00 |
September | 0.177342E+11 | 0.863114E+10 | 270.15 | 0.162373E+11 | 0.149692E+10 | 0.00 | 0.42 | 21-SEP-13:30 | 0.01 | 02-SEP-01:00 | 187155.04 | 21-SEP-13:30 | 136721.11 | 29-SEP-07:40 | 83805.12 | 22-SEP-12:00 | 55585.84 | 29-SEP-12:20 | 0.00 |
October | 0.120452E+12 | 0.384530E+11 | 531.06 | 0.100785E+12 | 0.196671E+11 | 0.00 | 0.66 | 01-OCT-12:00 | 0.01 | 30-OCT-00:40 | 314550.42 | 01-OCT-11:52 | 228935.82 | 16-OCT-07:40 | 123637.67 | 01-OCT-11:52 | 93544.60 | 16-OCT-11:00 | 0.00 |
November | 0.637070E+11 | 0.208927E+11 | 491.23 | 0.575154E+11 | 0.619166E+10 | 0.00 | 0.77 | 19-NOV-12:57 | 0.01 | 25-NOV-14:05 | 316110.59 | 19-NOV-12:53 | 316110.59 | 19-NOV-12:53 | 61230.43 | 10-NOV-13:00 | 98899.10 | 19-NOV-12:57 | 0.00 |
December | 0.177991E+12 | 0.536485E+11 | 619.18 | 0.167841E+12 | 0.101497E+11 | 0.00 | 0.99 | 19-DEC-13:00 | 0.01 | 24-DEC-17:25 | 382034.32 | 05-DEC-10:00 | 382034.32 | 05-DEC-10:00 | 82415.86 | 07-DEC-13:00 | 125501.30 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.198458E+13 | 0.541663E+12 | 5641.96 | 0.135043E+13 | 0.634149E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.899389E+09 | 0.303517E+10 | 232.28 | 0.829920E+09 | 59695932.15 | 0.00 | 0.13 | 0.01 | 47464.01 | 42750.23 | 6176.56 | 14473.27 | 0.00 | ||||||
Maximum of Months | 0.856170E+12 | 0.209133E+12 | 743.17 | 0.486085E+12 | 0.370085E+12 | 0.00 | 1.00 | 0.01 | 493278.58 | 406628.13 | 241863.79 | 136188.33 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.524669E+10 | 0.121878E+10 | 744.00 | 0.520474E+10 | 41953395.06 | 0.00 | 0.33 | 15-JAN-16:03 | 0.17 | 28-JAN-07:10 | 2467.31 | 18-JAN-16:10 | 2441.46 | 15-JAN-16:10 | 171.94 | 17-JAN-15:00 | 661.91 | 13-JAN-14:00 | 0.00 |
February | 0.941775E+10 | 0.203093E+10 | 672.00 | 0.935731E+10 | 60443005.07 | 0.00 | 0.57 | 05-FEB-16:55 | 0.41 | 11-FEB-07:50 | 4705.68 | 20-FEB-17:00 | 4687.68 | 20-FEB-17:00 | 207.25 | 13-FEB-17:00 | 1175.06 | 01-FEB-12:00 | 0.00 |
March | 0.155654E+11 | 0.321583E+10 | 744.00 | 0.154717E+11 | 93615336.07 | 0.00 | 0.85 | 31-MAR-24:00 | 0.62 | 01-MAR-07:05 | 7553.77 | 31-MAR-24:00 | 7553.77 | 31-MAR-24:00 | 270.19 | 23-MAR-16:10 | 1571.31 | 11-MAR-14:00 | 0.00 |
April | 0.202325E+11 | 0.415502E+10 | 720.00 | 0.201014E+11 | 0.131120E+09 | 0.00 | 0.98 | 02-APR-13:53 | 0.31 | 30-APR-24:00 | 8484.91 | 16-APR-17:12 | 8475.77 | 30-APR-17:26 | 255.95 | 13-APR-16:00 | 2282.81 | 26-APR-13:00 | 0.00 |
May | 0.560537E+10 | 0.127373E+10 | 744.00 | 0.550654E+10 | 98831382.22 | 0.00 | 0.46 | 31-MAY-24:00 | 0.20 | 13-MAY-06:10 | 3848.73 | 31-MAY-24:00 | 3831.23 | 31-MAY-24:00 | 209.57 | 05-MAY-15:30 | 814.97 | 31-MAY-24:00 | 0.00 |
June | 0.106316E+11 | 0.234118E+10 | 720.00 | 0.104390E+11 | 0.192574E+09 | 0.00 | 0.67 | 30-JUN-24:00 | 0.44 | 01-JUN-06:10 | 5870.79 | 30-JUN-24:00 | 5866.26 | 30-JUN-24:00 | 298.69 | 28-JUN-13:05 | 1201.26 | 29-JUN-11:00 | 0.00 |
July | 0.162670E+11 | 0.365002E+10 | 744.00 | 0.159820E+11 | 0.284956E+09 | 0.00 | 0.87 | 31-JUL-23:35 | 0.66 | 07-JUL-21:00 | 7745.18 | 31-JUL-24:00 | 7745.18 | 31-JUL-24:00 | 366.43 | 28-JUL-14:00 | 1885.18 | 31-JUL-14:05 | 0.00 |
August | 0.212802E+11 | 0.483362E+10 | 744.00 | 0.209539E+11 | 0.326358E+09 | 0.00 | 1.00 | 17-AUG-14:40 | 0.31 | 31-AUG-24:00 | 8581.05 | 06-AUG-17:45 | 8581.05 | 06-AUG-17:45 | 367.32 | 18-AUG-16:00 | 2448.79 | 17-AUG-14:00 | 0.00 |
September | 0.572502E+10 | 0.134263E+10 | 720.00 | 0.554494E+10 | 0.180080E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.22 | 20-SEP-06:10 | 4081.40 | 30-SEP-24:00 | 4081.40 | 30-SEP-24:00 | 328.04 | 22-SEP-10:50 | 988.28 | 29-SEP-13:00 | 0.00 |
October | 0.109789E+11 | 0.255869E+10 | 744.00 | 0.108535E+11 | 0.125325E+09 | 0.00 | 0.67 | 31-OCT-24:00 | 0.43 | 28-OCT-06:12 | 5848.86 | 31-OCT-24:00 | 5845.09 | 31-OCT-24:00 | 347.74 | 03-OCT-15:00 | 1781.63 | 16-OCT-11:00 | 0.00 |
November | 0.152241E+11 | 0.320109E+10 | 720.00 | 0.151512E+11 | 72828811.93 | 0.00 | 0.81 | 28-NOV-14:00 | 0.63 | 18-NOV-07:30 | 6549.78 | 12-NOV-16:20 | 6524.92 | 12-NOV-16:20 | 272.94 | 10-NOV-16:50 | 1794.28 | 28-NOV-14:00 | 0.00 |
December | 0.206891E+11 | 0.430264E+10 | 744.00 | 0.206565E+11 | 32630423.24 | 0.00 | 1.00 | 18-DEC-15:40 | 0.82 | 23-DEC-07:05 | 8551.80 | 25-DEC-16:20 | 8551.80 | 25-DEC-16:20 | 251.28 | 07-DEC-16:50 | 2310.39 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.156864E+12 | 0.341242E+11 | 8760.00 | 0.155223E+12 | 0.164071E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.524669E+10 | 0.121878E+10 | 672.00 | 0.520474E+10 | 32630423.24 | 0.00 | 0.33 | 0.17 | 2467.31 | 2441.46 | 171.94 | 661.91 | 0.00 | ||||||
Maximum of Months | 0.212802E+11 | 0.483362E+10 | 744.00 | 0.209539E+11 | 0.326358E+09 | 0.00 | 1.00 | 0.82 | 8581.05 | 8581.05 | 367.32 | 2448.79 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.409687E+11 | 0.967913E+10 | 744.00 | 0.405591E+11 | 0.409616E+09 | 0.00 | 0.31 | 18-JAN-16:10 | 0.09 | 03-JAN-07:05 | 22973.73 | 18-JAN-16:10 | 22106.11 | 18-JAN-16:10 | 1641.94 | 17-JAN-15:00 | 6000.89 | 24-JAN-15:50 | 0.00 |
February | 0.824985E+11 | 0.179424E+11 | 672.00 | 0.818987E+11 | 0.599772E+09 | 0.00 | 0.55 | 03-FEB-15:00 | 0.35 | 25-FEB-18:00 | 42055.09 | 21-FEB-17:00 | 41878.28 | 20-FEB-17:05 | 2071.41 | 13-FEB-17:00 | 10991.87 | 01-FEB-12:00 | 0.00 |
March | 0.141322E+12 | 0.293793E+11 | 744.00 | 0.140390E+12 | 0.931942E+09 | 0.00 | 0.81 | 31-MAR-23:40 | 0.56 | 30-MAR-06:05 | 68818.93 | 31-MAR-23:30 | 68818.93 | 31-MAR-23:30 | 2675.81 | 23-MAR-16:10 | 14874.20 | 23-MAR-14:00 | 0.00 |
April | 0.188841E+12 | 0.389187E+11 | 720.00 | 0.187537E+12 | 0.130389E+10 | 0.00 | 0.96 | 26-APR-13:20 | 0.27 | 30-APR-24:00 | 78923.38 | 30-APR-17:45 | 78877.93 | 30-APR-17:26 | 2532.96 | 13-APR-16:00 | 21765.02 | 26-APR-13:00 | 0.00 |
May | 0.490795E+11 | 0.112335E+11 | 744.00 | 0.481090E+11 | 0.970558E+09 | 0.00 | 0.44 | 31-MAY-24:00 | 0.16 | 13-MAY-06:20 | 35195.41 | 31-MAY-23:40 | 34967.91 | 31-MAY-24:00 | 2067.83 | 05-MAY-15:30 | 7479.34 | 31-MAY-23:50 | 0.00 |
June | 0.982582E+11 | 0.217174E+11 | 720.00 | 0.963503E+11 | 0.190783E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.41 | 01-JUN-06:10 | 55561.40 | 30-JUN-24:00 | 55511.80 | 30-JUN-24:00 | 2961.50 | 28-JUN-13:05 | 11354.44 | 29-JUN-11:00 | 0.00 |
July | 0.153410E+12 | 0.344880E+11 | 744.00 | 0.150579E+12 | 0.283086E+10 | 0.00 | 0.87 | 31-JUL-23:55 | 0.64 | 08-JUL-06:40 | 73989.80 | 31-JUL-24:00 | 73989.80 | 31-JUL-24:00 | 3635.99 | 28-JUL-14:00 | 17983.47 | 19-JUL-14:05 | 0.00 |
August | 0.201818E+12 | 0.458958E+11 | 744.00 | 0.198566E+12 | 0.325206E+10 | 0.00 | 0.99 | 17-AUG-14:20 | 0.26 | 31-AUG-24:00 | 80893.80 | 17-AUG-16:00 | 80059.50 | 06-AUG-17:55 | 3653.42 | 18-AUG-16:00 | 23347.07 | 17-AUG-14:00 | 0.00 |
September | 0.508028E+11 | 0.119961E+11 | 720.00 | 0.490316E+11 | 0.177124E+10 | 0.00 | 0.48 | 30-SEP-24:00 | 0.19 | 20-SEP-06:10 | 38132.92 | 30-SEP-24:00 | 38132.92 | 30-SEP-24:00 | 3232.13 | 22-SEP-10:50 | 9289.60 | 29-SEP-13:00 | 0.00 |
October | 0.100104E+12 | 0.234685E+11 | 744.00 | 0.988614E+11 | 0.124229E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.39 | 28-OCT-06:45 | 54502.95 | 31-OCT-24:00 | 54459.79 | 31-OCT-24:00 | 3443.93 | 03-OCT-15:00 | 16856.85 | 16-OCT-11:00 | 0.00 |
November | 0.138475E+12 | 0.292974E+11 | 720.00 | 0.137751E+12 | 0.723535E+09 | 0.00 | 0.81 | 28-NOV-14:00 | 0.58 | 18-NOV-07:30 | 61223.53 | 10-NOV-16:20 | 59305.21 | 12-NOV-16:23 | 2702.30 | 10-NOV-16:50 | 16954.21 | 28-NOV-14:00 | 0.00 |
December | 0.189306E+12 | 0.396363E+11 | 744.00 | 0.188979E+12 | 0.327323E+09 | 0.00 | 1.00 | 19-DEC-10:10 | 0.76 | 13-DEC-07:05 | 79279.98 | 07-DEC-16:20 | 77713.12 | 19-DEC-16:20 | 2484.70 | 07-DEC-16:50 | 22067.86 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.143488E+13 | 0.313653E+12 | 8760.00 | 0.141861E+13 | 0.162709E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.409687E+11 | 0.967913E+10 | 672.00 | 0.405591E+11 | 0.327323E+09 | 0.00 | 0.31 | 0.09 | 22973.73 | 22106.11 | 1641.94 | 6000.89 | 0.00 | ||||||
Maximum of Months | 0.201818E+12 | 0.458958E+11 | 744.00 | 0.198566E+12 | 0.325206E+10 | 0.00 | 1.00 | 0.76 | 80893.80 | 80059.50 | 3653.42 | 23347.07 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.290170E+10 | 0.703512E+09 | 706.37 | 0.286175E+10 | 39950629.16 | 0.00 | 0.30 | 18-JAN-16:10 | 0.00 | 01-JAN-00:10 | 2322.35 | 18-JAN-16:10 | 2235.05 | 18-JAN-16:10 | 162.07 | 20-JAN-16:30 | 601.33 | 24-JAN-15:50 | 0.00 |
February | 0.730528E+10 | 0.160774E+10 | 672.00 | 0.724598E+10 | 59302506.82 | 0.00 | 0.55 | 03-FEB-15:00 | 0.25 | 26-FEB-07:00 | 4224.34 | 01-FEB-16:50 | 4083.93 | 22-FEB-17:00 | 209.52 | 13-FEB-17:00 | 1084.11 | 01-FEB-12:00 | 0.00 |
March | 0.133005E+11 | 0.278882E+10 | 744.00 | 0.132076E+11 | 92834156.83 | 0.00 | 0.77 | 31-MAR-23:20 | 0.46 | 30-MAR-06:05 | 6554.99 | 31-MAR-23:20 | 6554.99 | 31-MAR-23:20 | 267.99 | 23-MAR-16:10 | 1501.74 | 23-MAR-14:00 | 0.00 |
April | 0.184642E+11 | 0.382762E+10 | 720.00 | 0.183339E+11 | 0.130251E+09 | 0.00 | 0.95 | 26-APR-13:50 | 0.24 | 30-APR-24:00 | 7978.88 | 30-APR-17:40 | 7971.42 | 30-APR-17:35 | 253.74 | 13-APR-16:00 | 2197.33 | 26-APR-13:00 | 0.00 |
May | 0.448340E+10 | 0.103542E+10 | 744.00 | 0.438689E+10 | 96509226.60 | 0.00 | 0.41 | 31-MAY-23:20 | 0.08 | 13-MAY-06:10 | 3298.04 | 31-MAY-23:20 | 3256.99 | 31-MAY-23:40 | 204.91 | 05-MAY-15:30 | 705.33 | 31-MAY-23:20 | 0.00 |
June | 0.965004E+10 | 0.214220E+10 | 720.00 | 0.945907E+10 | 0.190964E+09 | 0.00 | 0.65 | 30-JUN-23:50 | 0.36 | 01-JUN-06:10 | 5451.26 | 30-JUN-23:40 | 5444.99 | 30-JUN-24:00 | 297.97 | 28-JUN-13:05 | 1151.53 | 29-JUN-11:00 | 0.00 |
July | 0.152746E+11 | 0.344628E+10 | 744.00 | 0.149915E+11 | 0.283175E+09 | 0.00 | 0.85 | 31-JUL-23:35 | 0.60 | 06-JUL-06:10 | 7313.61 | 31-JUL-24:00 | 7313.61 | 31-JUL-24:00 | 364.45 | 28-JUL-14:00 | 1824.86 | 19-JUL-14:05 | 0.00 |
August | 0.200921E+11 | 0.458624E+10 | 744.00 | 0.197670E+11 | 0.325098E+09 | 0.00 | 0.99 | 17-AUG-14:40 | 0.23 | 31-AUG-24:00 | 8181.38 | 17-AUG-16:00 | 8160.15 | 06-AUG-17:50 | 365.89 | 18-AUG-16:00 | 2358.78 | 17-AUG-14:00 | 0.00 |
September | 0.482098E+10 | 0.114754E+10 | 720.00 | 0.464421E+10 | 0.176772E+09 | 0.00 | 0.47 | 30-SEP-24:00 | 0.13 | 20-SEP-06:25 | 3786.25 | 30-SEP-23:50 | 3786.25 | 30-SEP-23:50 | 324.42 | 22-SEP-11:00 | 963.53 | 29-SEP-13:00 | 0.00 |
October | 0.960567E+10 | 0.227057E+10 | 744.00 | 0.948167E+10 | 0.124005E+09 | 0.00 | 0.65 | 15-OCT-16:32 | 0.31 | 30-OCT-06:14 | 5263.41 | 31-OCT-23:30 | 5253.31 | 31-OCT-23:40 | 345.15 | 03-OCT-15:00 | 1707.13 | 16-OCT-11:00 | 0.00 |
November | 0.129932E+11 | 0.277452E+10 | 720.00 | 0.129212E+11 | 72034031.87 | 0.00 | 0.79 | 28-NOV-14:00 | 0.48 | 27-NOV-07:05 | 6140.10 | 10-NOV-16:20 | 5910.33 | 07-NOV-16:20 | 270.04 | 10-NOV-16:50 | 1699.63 | 28-NOV-14:00 | 0.00 |
December | 0.178220E+11 | 0.377287E+10 | 744.00 | 0.177895E+11 | 32500557.35 | 0.00 | 1.00 | 19-DEC-12:20 | 0.66 | 26-DEC-07:05 | 7928.80 | 07-DEC-16:20 | 7774.15 | 19-DEC-16:10 | 248.48 | 07-DEC-16:50 | 2242.17 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.136714E+12 | 0.301033E+11 | 8722.37 | 0.135090E+12 | 0.162340E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.290170E+10 | 0.703512E+09 | 672.00 | 0.286175E+10 | 32500557.35 | 0.00 | 0.30 | 0.00 | 2322.35 | 2235.05 | 162.07 | 601.33 | 0.00 | ||||||
Maximum of Months | 0.200921E+11 | 0.458624E+10 | 744.00 | 0.197670E+11 | 0.325098E+09 | 0.00 | 1.00 | 0.66 | 8181.38 | 8160.15 | 365.89 | 2358.78 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 51.40 | 438.47 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 64.08 | 400.30 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 98.24 | 405.55 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 143.82 | 317.87 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 190.17 | 267.68 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 247.76 | 211.24 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.19 | 186.35 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.12 | 195.54 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 160.05 | 241.01 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 134.29 | 275.90 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 61.38 | 402.48 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 42.47 | 451.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 138.86 | 315.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 42.47 | 186.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.19 | 451.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 51.40 | 438.47 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 64.08 | 400.30 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 98.24 | 405.55 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 143.82 | 317.87 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 190.17 | 267.68 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 247.76 | 211.24 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.19 | 186.35 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.12 | 195.54 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 160.05 | 241.01 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 134.29 | 275.90 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 61.38 | 402.48 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 42.47 | 451.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 138.86 | 315.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 42.47 | 186.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.19 | 451.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 51.40 | 438.47 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 64.08 | 400.30 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 98.24 | 405.55 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 143.82 | 317.87 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 190.17 | 267.68 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 247.76 | 211.24 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.19 | 186.35 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.12 | 195.54 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 160.05 | 241.01 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 134.29 | 275.90 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 61.38 | 402.48 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 42.47 | 451.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 138.86 | 315.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 42.47 | 186.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.19 | 451.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 51.40 | 438.47 | 0.00 | 0.00 | 0.00 |
February | 130.01 | 0.00 | 130.01 | 64.08 | 400.30 | 0.00 | 0.00 | 0.00 |
March | 159.32 | 0.00 | 159.32 | 98.24 | 405.55 | 0.00 | 0.00 | 0.00 |
April | 183.55 | 0.71 | 182.84 | 143.82 | 317.87 | 0.00 | 0.00 | 0.00 |
May | 220.57 | 10.27 | 210.30 | 190.17 | 267.68 | 0.00 | 0.00 | 0.00 |
June | 235.03 | 22.98 | 212.05 | 247.76 | 211.24 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.88 | 260.19 | 186.35 | 0.00 | 0.00 | 0.00 |
August | 184.81 | 3.70 | 181.11 | 207.12 | 195.54 | 0.00 | 0.00 | 0.00 |
September | 156.42 | 0.02 | 156.40 | 160.05 | 241.01 | 0.00 | 0.00 | 0.00 |
October | 124.08 | 0.00 | 124.08 | 134.29 | 275.90 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 61.38 | 402.48 | 0.00 | 0.00 | 0.00 |
December | 96.42 | 0.00 | 96.42 | 42.47 | 451.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.85 | 4.72 | 156.13 | 138.86 | 315.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.42 | 0.00 | 96.42 | 42.47 | 186.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.03 | 22.98 | 212.05 | 260.19 | 451.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.57 | 0.00 | 103.57 | 51.40 | 438.45 | 0.00 | 0.00 | 0.00 |
February | 130.00 | 0.00 | 130.00 | 64.08 | 400.29 | 0.00 | 0.00 | 0.00 |
March | 159.31 | 0.00 | 159.31 | 98.24 | 405.54 | 0.00 | 0.00 | 0.00 |
April | 183.54 | 0.71 | 182.84 | 143.82 | 317.85 | 0.00 | 0.00 | 0.00 |
May | 220.56 | 10.27 | 210.29 | 190.16 | 267.67 | 0.00 | 0.00 | 0.00 |
June | 235.02 | 22.98 | 212.04 | 247.75 | 211.23 | 0.00 | 0.00 | 0.00 |
July | 222.53 | 18.65 | 203.87 | 260.18 | 186.34 | 0.00 | 0.00 | 0.00 |
August | 184.80 | 3.70 | 181.10 | 207.11 | 195.53 | 0.00 | 0.00 | 0.00 |
September | 156.41 | 0.02 | 156.39 | 160.04 | 241.00 | 0.00 | 0.00 | 0.00 |
October | 124.07 | 0.00 | 124.07 | 134.29 | 275.89 | 0.00 | 0.00 | 0.00 |
November | 112.34 | 0.00 | 112.34 | 61.38 | 402.46 | 0.00 | 0.00 | 0.00 |
December | 96.41 | 0.00 | 96.41 | 42.47 | 451.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.84 | 4.72 | 156.13 | 138.86 | 315.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.41 | 0.00 | 96.41 | 42.47 | 186.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.02 | 22.98 | 212.04 | 260.18 | 451.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.41 | 166.02 | 144.40 | 356.38 | 452.10 | 0.00 | 0.00 | 0.00 |
February | 327.45 | 150.01 | 177.44 | 353.93 | 412.87 | 0.00 | 0.00 | 0.00 |
March | 397.76 | 177.22 | 220.54 | 453.69 | 415.46 | 0.00 | 0.00 | 0.00 |
April | 508.53 | 255.04 | 253.49 | 670.48 | 333.20 | 0.00 | 0.00 | 0.00 |
May | 479.91 | 200.28 | 279.63 | 608.01 | 302.01 | 0.00 | 0.00 | 0.00 |
June | 476.92 | 206.93 | 269.99 | 650.61 | 240.45 | 0.00 | 0.00 | 0.00 |
July | 540.39 | 268.53 | 271.85 | 796.37 | 211.84 | 0.00 | 0.00 | 0.00 |
August | 533.68 | 283.47 | 250.21 | 797.65 | 213.39 | 0.00 | 0.00 | 0.00 |
September | 388.56 | 178.05 | 210.51 | 544.86 | 259.74 | 0.00 | 0.00 | 0.00 |
October | 343.95 | 176.78 | 167.17 | 489.11 | 289.01 | 0.00 | 0.00 | 0.00 |
November | 313.55 | 159.29 | 154.25 | 362.84 | 411.01 | 0.00 | 0.00 | 0.00 |
December | 299.12 | 166.19 | 132.93 | 342.10 | 452.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 410.57 | 199.38 | 211.19 | 536.76 | 332.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.12 | 150.01 | 132.93 | 342.10 | 211.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.39 | 283.47 | 279.63 | 797.65 | 452.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.41 | 166.02 | 144.40 | 356.38 | 452.10 | 0.00 | 0.00 | 0.00 |
February | 327.45 | 150.01 | 177.44 | 353.93 | 412.87 | 0.00 | 0.00 | 0.00 |
March | 397.76 | 177.22 | 220.54 | 453.69 | 415.46 | 0.00 | 0.00 | 0.00 |
April | 508.53 | 255.04 | 253.49 | 670.48 | 333.20 | 0.00 | 0.00 | 0.00 |
May | 479.91 | 200.28 | 279.63 | 608.01 | 302.01 | 0.00 | 0.00 | 0.00 |
June | 476.92 | 206.93 | 269.99 | 650.61 | 240.45 | 0.00 | 0.00 | 0.00 |
July | 540.39 | 268.53 | 271.85 | 796.37 | 211.84 | 0.00 | 0.00 | 0.00 |
August | 533.68 | 283.47 | 250.21 | 797.65 | 213.39 | 0.00 | 0.00 | 0.00 |
September | 388.56 | 178.05 | 210.51 | 544.86 | 259.74 | 0.00 | 0.00 | 0.00 |
October | 343.95 | 176.78 | 167.17 | 489.11 | 289.01 | 0.00 | 0.00 | 0.00 |
November | 313.55 | 159.29 | 154.25 | 362.84 | 411.01 | 0.00 | 0.00 | 0.00 |
December | 299.12 | 166.19 | 132.93 | 342.10 | 452.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 410.57 | 199.38 | 211.19 | 536.76 | 332.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.12 | 150.01 | 132.93 | 342.10 | 211.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.39 | 283.47 | 279.63 | 797.65 | 452.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.41 | 166.01 | 144.39 | 356.37 | 452.10 | 0.00 | 0.00 | 0.00 |
February | 327.45 | 150.01 | 177.44 | 353.92 | 412.86 | 0.00 | 0.00 | 0.00 |
March | 397.75 | 177.22 | 220.54 | 453.68 | 415.45 | 0.00 | 0.00 | 0.00 |
April | 508.52 | 255.03 | 253.49 | 670.47 | 333.20 | 0.00 | 0.00 | 0.00 |
May | 479.90 | 200.27 | 279.63 | 608.00 | 302.00 | 0.00 | 0.00 | 0.00 |
June | 476.91 | 206.92 | 269.99 | 650.59 | 240.44 | 0.00 | 0.00 | 0.00 |
July | 540.38 | 268.53 | 271.85 | 796.35 | 211.83 | 0.00 | 0.00 | 0.00 |
August | 533.67 | 283.47 | 250.20 | 797.63 | 213.39 | 0.00 | 0.00 | 0.00 |
September | 388.55 | 178.05 | 210.50 | 544.85 | 259.74 | 0.00 | 0.00 | 0.00 |
October | 343.94 | 176.78 | 167.16 | 489.10 | 289.00 | 0.00 | 0.00 | 0.00 |
November | 313.54 | 159.29 | 154.25 | 362.83 | 411.00 | 0.00 | 0.00 | 0.00 |
December | 299.11 | 166.19 | 132.92 | 342.09 | 452.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 410.56 | 199.37 | 211.19 | 536.75 | 332.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.11 | 150.01 | 132.92 | 342.09 | 211.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.38 | 283.47 | 279.63 | 797.63 | 452.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 985.51 | 406.00 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 727.43 | 374.50 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 568.74 | 391.02 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 508.40 | 324.69 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 292.50 | 287.15 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 256.62 | 226.32 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 318.56 | 198.68 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 475.65 | 207.16 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 666.05 | 245.46 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.44 | 846.54 | 269.69 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 940.48 | 375.63 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 636.64 | 309.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 256.62 | 198.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 985.51 | 406.00 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 727.43 | 374.50 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 568.74 | 391.02 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 508.39 | 324.69 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 292.50 | 287.15 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 256.62 | 226.32 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 318.56 | 198.68 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 475.65 | 207.16 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 666.05 | 245.46 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.43 | 846.54 | 269.69 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 940.47 | 375.63 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 636.64 | 309.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 256.62 | 198.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 985.51 | 406.00 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 727.43 | 374.50 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 568.74 | 391.02 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 508.40 | 324.69 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 292.50 | 287.15 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 256.62 | 226.32 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 318.56 | 198.68 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 475.65 | 207.16 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 666.05 | 245.46 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.44 | 846.54 | 269.69 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 940.48 | 375.63 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 636.64 | 309.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 256.62 | 198.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.50 | 501.38 | 182.12 | 985.51 | 406.00 | 0.00 | 0.00 | 0.00 |
February | 537.19 | 330.88 | 206.31 | 727.43 | 374.50 | 0.00 | 0.00 | 0.00 |
March | 428.27 | 206.87 | 221.39 | 568.74 | 391.02 | 0.00 | 0.00 | 0.00 |
April | 357.83 | 136.44 | 221.38 | 508.39 | 324.69 | 0.00 | 0.00 | 0.00 |
May | 254.80 | 31.36 | 223.44 | 292.50 | 287.15 | 0.00 | 0.00 | 0.00 |
June | 223.53 | 13.50 | 210.03 | 256.62 | 226.32 | 0.00 | 0.00 | 0.00 |
July | 236.78 | 26.65 | 210.12 | 318.56 | 198.68 | 0.00 | 0.00 | 0.00 |
August | 304.19 | 95.95 | 208.24 | 475.65 | 207.16 | 0.00 | 0.00 | 0.00 |
September | 423.28 | 214.49 | 208.79 | 666.05 | 245.46 | 0.00 | 0.00 | 0.00 |
October | 538.31 | 359.88 | 178.43 | 846.54 | 269.69 | 0.00 | 0.00 | 0.00 |
November | 654.26 | 461.90 | 192.36 | 940.47 | 375.63 | 0.00 | 0.00 | 0.00 |
December | 730.19 | 555.77 | 174.42 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.30 | 244.30 | 203.01 | 636.64 | 309.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.53 | 13.50 | 174.42 | 256.62 | 198.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.19 | 555.77 | 223.44 | 1056.36 | 412.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 683.47 | 501.36 | 182.11 | 985.47 | 405.98 | 0.00 | 0.00 | 0.00 |
February | 537.17 | 330.87 | 206.30 | 727.40 | 374.49 | 0.00 | 0.00 | 0.00 |
March | 428.25 | 206.86 | 221.39 | 568.72 | 391.01 | 0.00 | 0.00 | 0.00 |
April | 357.81 | 136.44 | 221.38 | 508.37 | 324.67 | 0.00 | 0.00 | 0.00 |
May | 254.79 | 31.36 | 223.44 | 292.49 | 287.14 | 0.00 | 0.00 | 0.00 |
June | 223.52 | 13.50 | 210.02 | 256.61 | 226.31 | 0.00 | 0.00 | 0.00 |
July | 236.77 | 26.65 | 210.11 | 318.55 | 198.68 | 0.00 | 0.00 | 0.00 |
August | 304.18 | 95.95 | 208.23 | 475.63 | 207.15 | 0.00 | 0.00 | 0.00 |
September | 423.26 | 214.48 | 208.78 | 666.02 | 245.45 | 0.00 | 0.00 | 0.00 |
October | 538.29 | 359.86 | 178.43 | 846.51 | 269.67 | 0.00 | 0.00 | 0.00 |
November | 654.24 | 461.88 | 192.36 | 940.44 | 375.62 | 0.00 | 0.00 | 0.00 |
December | 730.16 | 555.75 | 174.41 | 1056.32 | 412.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.28 | 244.29 | 203.00 | 636.62 | 309.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.52 | 13.50 | 174.41 | 256.61 | 198.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 730.16 | 555.75 | 223.44 | 1056.32 | 412.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.46 | 149.02 | 146.44 | 349.47 | 509.00 | 0.00 | 0.00 | 0.00 |
February | 352.48 | 162.72 | 189.76 | 396.30 | 480.98 | 0.00 | 0.00 | 0.00 |
March | 404.04 | 178.75 | 225.29 | 460.20 | 491.99 | 0.00 | 0.00 | 0.00 |
April | 556.99 | 290.03 | 266.97 | 731.06 | 408.84 | 0.00 | 0.00 | 0.00 |
May | 547.14 | 252.72 | 294.42 | 708.72 | 341.12 | 0.00 | 0.00 | 0.00 |
June | 579.64 | 289.81 | 289.83 | 794.57 | 279.54 | 0.00 | 0.00 | 0.00 |
July | 613.59 | 328.33 | 285.26 | 885.79 | 256.11 | 0.00 | 0.00 | 0.00 |
August | 575.67 | 311.99 | 263.68 | 840.18 | 271.44 | 0.00 | 0.00 | 0.00 |
September | 492.88 | 263.73 | 229.15 | 702.75 | 293.18 | 0.00 | 0.00 | 0.00 |
October | 376.78 | 205.71 | 171.08 | 540.56 | 339.43 | 0.00 | 0.00 | 0.00 |
November | 340.35 | 178.03 | 162.32 | 410.83 | 488.32 | 0.00 | 0.00 | 0.00 |
December | 300.59 | 161.22 | 139.37 | 353.68 | 553.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.36 | 231.30 | 222.06 | 598.82 | 392.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 295.46 | 149.02 | 139.37 | 349.47 | 256.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.59 | 328.33 | 294.42 | 885.79 | 553.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.46 | 149.02 | 146.44 | 349.47 | 509.00 | 0.00 | 0.00 | 0.00 |
February | 352.48 | 162.72 | 189.76 | 396.30 | 480.98 | 0.00 | 0.00 | 0.00 |
March | 404.04 | 178.75 | 225.29 | 460.20 | 491.99 | 0.00 | 0.00 | 0.00 |
April | 556.99 | 290.03 | 266.97 | 731.06 | 408.84 | 0.00 | 0.00 | 0.00 |
May | 547.14 | 252.72 | 294.42 | 708.72 | 341.12 | 0.00 | 0.00 | 0.00 |
June | 579.64 | 289.81 | 289.83 | 794.57 | 279.54 | 0.00 | 0.00 | 0.00 |
July | 613.59 | 328.33 | 285.26 | 885.79 | 256.11 | 0.00 | 0.00 | 0.00 |
August | 575.67 | 311.99 | 263.68 | 840.18 | 271.44 | 0.00 | 0.00 | 0.00 |
September | 492.88 | 263.73 | 229.15 | 702.75 | 293.18 | 0.00 | 0.00 | 0.00 |
October | 376.78 | 205.71 | 171.08 | 540.56 | 339.43 | 0.00 | 0.00 | 0.00 |
November | 340.35 | 178.03 | 162.32 | 410.83 | 488.32 | 0.00 | 0.00 | 0.00 |
December | 300.59 | 161.22 | 139.37 | 353.68 | 553.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.36 | 231.30 | 222.06 | 598.82 | 392.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 295.46 | 149.02 | 139.37 | 349.47 | 256.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.59 | 328.33 | 294.42 | 885.79 | 553.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.45 | 149.01 | 146.44 | 349.46 | 508.99 | 0.00 | 0.00 | 0.00 |
February | 352.48 | 162.72 | 189.76 | 396.30 | 480.97 | 0.00 | 0.00 | 0.00 |
March | 404.03 | 178.75 | 225.28 | 460.19 | 491.98 | 0.00 | 0.00 | 0.00 |
April | 556.98 | 290.02 | 266.96 | 731.04 | 408.83 | 0.00 | 0.00 | 0.00 |
May | 547.13 | 252.72 | 294.41 | 708.71 | 341.11 | 0.00 | 0.00 | 0.00 |
June | 579.63 | 289.80 | 289.82 | 794.55 | 279.54 | 0.00 | 0.00 | 0.00 |
July | 613.58 | 328.32 | 285.26 | 885.77 | 256.10 | 0.00 | 0.00 | 0.00 |
August | 575.66 | 311.98 | 263.68 | 840.17 | 271.43 | 0.00 | 0.00 | 0.00 |
September | 492.87 | 263.73 | 229.14 | 702.74 | 293.17 | 0.00 | 0.00 | 0.00 |
October | 376.78 | 205.70 | 171.07 | 540.55 | 339.42 | 0.00 | 0.00 | 0.00 |
November | 340.34 | 178.02 | 162.32 | 410.83 | 488.31 | 0.00 | 0.00 | 0.00 |
December | 300.58 | 161.22 | 139.36 | 353.67 | 553.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.35 | 231.29 | 222.06 | 598.81 | 392.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 295.45 | 149.01 | 139.36 | 349.46 | 256.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.58 | 328.32 | 294.41 | 885.77 | 553.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.85 | 0.00 | 517.85 | 311.98 | 1975.69 | 0.00 | 0.00 | 0.00 |
February | 650.04 | 0.00 | 650.04 | 371.44 | 1801.65 | 0.00 | 0.00 | 0.00 |
March | 796.57 | 0.00 | 796.57 | 544.18 | 1840.94 | 0.00 | 0.00 | 0.00 |
April | 917.74 | 3.53 | 914.21 | 774.10 | 1446.82 | 0.00 | 0.00 | 0.00 |
May | 1102.84 | 51.35 | 1051.48 | 981.07 | 1271.09 | 0.00 | 0.00 | 0.00 |
June | 1175.13 | 114.89 | 1060.24 | 1258.81 | 998.93 | 0.00 | 0.00 | 0.00 |
July | 1112.66 | 93.26 | 1019.40 | 1329.41 | 887.58 | 0.00 | 0.00 | 0.00 |
August | 924.03 | 18.50 | 905.52 | 1068.14 | 930.49 | 0.00 | 0.00 | 0.00 |
September | 782.09 | 0.12 | 781.97 | 826.08 | 1122.11 | 0.00 | 0.00 | 0.00 |
October | 620.38 | 0.00 | 620.38 | 714.19 | 1258.29 | 0.00 | 0.00 | 0.00 |
November | 561.71 | 0.00 | 561.71 | 362.43 | 1806.06 | 0.00 | 0.00 | 0.00 |
December | 482.07 | 0.00 | 482.07 | 281.90 | 1988.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.25 | 23.60 | 780.65 | 737.53 | 1442.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.07 | 0.00 | 482.07 | 281.90 | 887.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.13 | 114.89 | 1060.24 | 1329.41 | 1988.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 931.23 | 498.04 | 433.19 | 1081.12 | 1277.34 | 0.00 | 0.00 | 0.00 |
February | 982.35 | 450.02 | 532.33 | 1066.96 | 1168.22 | 0.00 | 0.00 | 0.00 |
March | 1193.27 | 531.66 | 661.61 | 1360.64 | 1190.94 | 0.00 | 0.00 | 0.00 |
April | 1525.58 | 765.11 | 760.47 | 1999.41 | 967.44 | 0.00 | 0.00 | 0.00 |
May | 1439.71 | 600.83 | 838.89 | 1806.35 | 884.29 | 0.00 | 0.00 | 0.00 |
June | 1430.75 | 620.78 | 809.97 | 1933.14 | 705.08 | 0.00 | 0.00 | 0.00 |
July | 1621.15 | 805.59 | 815.56 | 2365.83 | 634.68 | 0.00 | 0.00 | 0.00 |
August | 1601.02 | 850.41 | 750.61 | 2367.85 | 649.01 | 0.00 | 0.00 | 0.00 |
September | 1165.67 | 534.15 | 631.51 | 1624.66 | 751.70 | 0.00 | 0.00 | 0.00 |
October | 1031.83 | 530.33 | 501.49 | 1463.22 | 829.18 | 0.00 | 0.00 | 0.00 |
November | 940.63 | 477.88 | 462.75 | 1094.15 | 1169.70 | 0.00 | 0.00 | 0.00 |
December | 897.35 | 498.57 | 398.77 | 1040.91 | 1278.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1231.69 | 598.13 | 633.56 | 1604.05 | 957.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 897.35 | 450.02 | 398.77 | 1040.91 | 634.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1621.15 | 850.41 | 838.89 | 2367.85 | 1278.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3417.44 | 2506.85 | 910.59 | 4895.91 | 2004.03 | 0.00 | 0.00 | 0.00 |
February | 2685.93 | 1654.39 | 1031.54 | 3607.34 | 1823.26 | 0.00 | 0.00 | 0.00 |
March | 2141.31 | 1034.35 | 1106.96 | 2832.66 | 1886.40 | 0.00 | 0.00 | 0.00 |
April | 1789.12 | 682.21 | 1106.91 | 2541.66 | 1553.59 | 0.00 | 0.00 | 0.00 |
May | 1273.99 | 156.78 | 1117.21 | 1458.94 | 1396.63 | 0.00 | 0.00 | 0.00 |
June | 1117.63 | 67.48 | 1050.15 | 1292.67 | 1083.17 | 0.00 | 0.00 | 0.00 |
July | 1183.87 | 133.27 | 1050.60 | 1606.84 | 956.90 | 0.00 | 0.00 | 0.00 |
August | 1520.92 | 479.75 | 1041.18 | 2379.26 | 1013.58 | 0.00 | 0.00 | 0.00 |
September | 2116.36 | 1072.44 | 1043.93 | 3307.68 | 1201.80 | 0.00 | 0.00 | 0.00 |
October | 2691.52 | 1799.36 | 892.16 | 4206.66 | 1317.88 | 0.00 | 0.00 | 0.00 |
November | 3271.27 | 2309.47 | 961.80 | 4671.46 | 1832.48 | 0.00 | 0.00 | 0.00 |
December | 3650.92 | 2778.83 | 872.09 | 5254.39 | 2007.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2236.49 | 1221.47 | 1015.02 | 3170.09 | 1504.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1117.63 | 67.48 | 872.09 | 1292.67 | 956.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3650.92 | 2778.83 | 1117.21 | 5254.39 | 2007.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 886.37 | 447.04 | 439.32 | 1078.81 | 1372.29 | 0.00 | 0.00 | 0.00 |
February | 1057.44 | 488.16 | 569.28 | 1222.79 | 1261.02 | 0.00 | 0.00 | 0.00 |
March | 1212.11 | 536.26 | 675.85 | 1423.03 | 1281.64 | 0.00 | 0.00 | 0.00 |
April | 1670.96 | 870.07 | 800.89 | 2237.82 | 1065.81 | 0.00 | 0.00 | 0.00 |
May | 1641.41 | 758.16 | 883.25 | 2130.31 | 959.19 | 0.00 | 0.00 | 0.00 |
June | 1738.89 | 869.41 | 869.48 | 2397.72 | 757.56 | 0.00 | 0.00 | 0.00 |
July | 1840.76 | 984.97 | 855.78 | 2684.99 | 687.59 | 0.00 | 0.00 | 0.00 |
August | 1726.99 | 935.96 | 791.03 | 2555.84 | 714.68 | 0.00 | 0.00 | 0.00 |
September | 1478.62 | 791.19 | 687.43 | 2113.39 | 814.00 | 0.00 | 0.00 | 0.00 |
October | 1130.34 | 617.12 | 513.22 | 1649.80 | 906.31 | 0.00 | 0.00 | 0.00 |
November | 1021.03 | 534.07 | 486.96 | 1275.48 | 1263.05 | 0.00 | 0.00 | 0.00 |
December | 901.75 | 483.66 | 418.09 | 1116.47 | 1394.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1360.07 | 693.89 | 666.18 | 1826.81 | 1038.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 886.37 | 447.04 | 418.09 | 1078.81 | 687.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1840.76 | 984.97 | 883.25 | 2684.99 | 1394.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 517.85 | 0.00 | 517.85 | 366.40 | 1782.09 | 0.00 | 0.00 | 0.00 |
February | 650.04 | 0.00 | 650.04 | 424.40 | 1627.08 | 0.00 | 0.00 | 0.00 |
March | 796.57 | 0.00 | 796.57 | 589.56 | 1705.12 | 0.00 | 0.00 | 0.00 |
April | 917.74 | 3.53 | 914.21 | 793.74 | 1371.73 | 0.00 | 0.00 | 0.00 |
May | 1102.84 | 51.35 | 1051.48 | 1006.18 | 1211.94 | 0.00 | 0.00 | 0.00 |
June | 1175.13 | 114.89 | 1060.24 | 1254.56 | 969.93 | 0.00 | 0.00 | 0.00 |
July | 1112.66 | 93.26 | 1019.40 | 1313.01 | 871.55 | 0.00 | 0.00 | 0.00 |
August | 924.03 | 18.50 | 905.52 | 1057.89 | 910.09 | 0.00 | 0.00 | 0.00 |
September | 782.09 | 0.12 | 781.97 | 831.79 | 1074.77 | 0.00 | 0.00 | 0.00 |
October | 620.38 | 0.00 | 620.38 | 731.71 | 1188.02 | 0.00 | 0.00 | 0.00 |
November | 561.71 | 0.00 | 561.71 | 409.60 | 1650.94 | 0.00 | 0.00 | 0.00 |
December | 482.07 | 0.00 | 482.07 | 336.75 | 1793.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.25 | 23.60 | 780.65 | 761.70 | 1345.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.07 | 0.00 | 482.07 | 336.75 | 871.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.13 | 114.89 | 1060.24 | 1313.01 | 1793.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 931.23 | 498.04 | 433.19 | 1127.54 | 1165.14 | 0.00 | 0.00 | 0.00 |
February | 982.35 | 450.02 | 532.33 | 1108.53 | 1065.95 | 0.00 | 0.00 | 0.00 |
March | 1193.27 | 531.66 | 661.61 | 1394.81 | 1113.91 | 0.00 | 0.00 | 0.00 |
April | 1525.58 | 765.11 | 760.47 | 2013.44 | 926.79 | 0.00 | 0.00 | 0.00 |
May | 1439.71 | 600.83 | 838.89 | 1821.70 | 849.49 | 0.00 | 0.00 | 0.00 |
June | 1430.75 | 620.78 | 809.97 | 1934.62 | 687.68 | 0.00 | 0.00 | 0.00 |
July | 1621.15 | 805.59 | 815.56 | 2359.60 | 625.98 | 0.00 | 0.00 | 0.00 |
August | 1601.02 | 850.41 | 750.61 | 2363.77 | 637.80 | 0.00 | 0.00 | 0.00 |
September | 1165.67 | 534.15 | 631.51 | 1630.82 | 723.96 | 0.00 | 0.00 | 0.00 |
October | 1031.83 | 530.33 | 501.49 | 1477.30 | 790.54 | 0.00 | 0.00 | 0.00 |
November | 940.63 | 477.88 | 462.75 | 1130.27 | 1084.60 | 0.00 | 0.00 | 0.00 |
December | 897.35 | 498.57 | 398.77 | 1087.40 | 1169.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1231.69 | 598.13 | 633.56 | 1624.41 | 902.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 897.35 | 450.02 | 398.77 | 1087.40 | 625.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1621.15 | 850.41 | 838.89 | 2363.77 | 1169.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3417.44 | 2506.85 | 910.59 | 4944.29 | 1857.56 | 0.00 | 0.00 | 0.00 |
February | 2685.93 | 1654.39 | 1031.54 | 3647.57 | 1680.61 | 0.00 | 0.00 | 0.00 |
March | 2141.31 | 1034.35 | 1106.96 | 2864.93 | 1768.08 | 0.00 | 0.00 | 0.00 |
April | 1789.12 | 682.21 | 1106.91 | 2550.20 | 1484.56 | 0.00 | 0.00 | 0.00 |
May | 1273.99 | 156.78 | 1117.21 | 1473.03 | 1332.58 | 0.00 | 0.00 | 0.00 |
June | 1117.63 | 67.48 | 1050.15 | 1288.46 | 1052.60 | 0.00 | 0.00 | 0.00 |
July | 1183.87 | 133.27 | 1050.60 | 1591.93 | 941.86 | 0.00 | 0.00 | 0.00 |
August | 1520.92 | 479.75 | 1041.18 | 2364.29 | 994.77 | 0.00 | 0.00 | 0.00 |
September | 2116.36 | 1072.44 | 1043.93 | 3302.28 | 1161.09 | 0.00 | 0.00 | 0.00 |
October | 2691.52 | 1799.36 | 892.16 | 4212.25 | 1264.78 | 0.00 | 0.00 | 0.00 |
November | 3271.27 | 2309.47 | 961.80 | 4703.62 | 1720.79 | 0.00 | 0.00 | 0.00 |
December | 3650.92 | 2778.83 | 872.09 | 5300.77 | 1871.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2236.49 | 1221.47 | 1015.02 | 3185.66 | 1426.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1117.63 | 67.48 | 872.09 | 1288.46 | 941.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3650.92 | 2778.83 | 1117.21 | 5300.77 | 1871.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 886.37 | 447.04 | 439.32 | 1103.10 | 1269.63 | 0.00 | 0.00 | 0.00 |
February | 1057.44 | 488.16 | 569.28 | 1244.92 | 1166.98 | 0.00 | 0.00 | 0.00 |
March | 1212.11 | 536.26 | 675.85 | 1438.75 | 1206.59 | 0.00 | 0.00 | 0.00 |
April | 1670.96 | 870.07 | 800.89 | 2235.65 | 1024.28 | 0.00 | 0.00 | 0.00 |
May | 1641.41 | 758.16 | 883.25 | 2128.60 | 922.99 | 0.00 | 0.00 | 0.00 |
June | 1738.89 | 869.41 | 869.48 | 2384.44 | 738.86 | 0.00 | 0.00 | 0.00 |
July | 1840.76 | 984.97 | 855.78 | 2666.48 | 676.45 | 0.00 | 0.00 | 0.00 |
August | 1726.99 | 935.96 | 791.03 | 2539.50 | 702.26 | 0.00 | 0.00 | 0.00 |
September | 1478.62 | 791.19 | 687.43 | 2105.83 | 789.03 | 0.00 | 0.00 | 0.00 |
October | 1130.34 | 617.12 | 513.22 | 1650.98 | 868.96 | 0.00 | 0.00 | 0.00 |
November | 1021.03 | 534.07 | 486.96 | 1293.14 | 1181.17 | 0.00 | 0.00 | 0.00 |
December | 901.75 | 483.66 | 418.09 | 1140.53 | 1292.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1360.07 | 693.89 | 666.18 | 1830.51 | 985.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 886.37 | 447.04 | 418.09 | 1103.10 | 676.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1840.76 | 984.97 | 883.25 | 2666.48 | 1292.32 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277405E+09 | 0.00 | 0.277405E+09 | 0.137674E+09 | 0.117440E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.155023E+09 | 0.968414E+09 |
March | 0.426713E+09 | 0.00 | 0.426713E+09 | 0.263133E+09 | 0.108623E+10 |
April | 0.475764E+09 | 1831143.67 | 0.473933E+09 | 0.372785E+09 | 0.823909E+09 |
May | 0.590774E+09 | 27509653.95 | 0.563264E+09 | 0.509356E+09 | 0.716955E+09 |
June | 0.609193E+09 | 59558836.48 | 0.549634E+09 | 0.642204E+09 | 0.547541E+09 |
July | 0.596037E+09 | 49957737.97 | 0.546079E+09 | 0.696886E+09 | 0.499109E+09 |
August | 0.494989E+09 | 9911660.66 | 0.485077E+09 | 0.554753E+09 | 0.523733E+09 |
September | 0.405442E+09 | 63548.65 | 0.405379E+09 | 0.414849E+09 | 0.624693E+09 |
October | 0.332331E+09 | 0.00 | 0.332331E+09 | 0.359689E+09 | 0.738966E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.159108E+09 | 0.104323E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.120840E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148833E+09 | 0.492377E+10 | 0.437922E+10 | 0.995558E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.499109E+09 |
Maximum of Months | 0.609193E+09 | 59558836.48 | 0.563264E+09 | 0.696886E+09 | 0.120840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277404E+09 | 0.00 | 0.277404E+09 | 0.137674E+09 | 0.117440E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.155023E+09 | 0.968414E+09 |
March | 0.426712E+09 | 0.00 | 0.426712E+09 | 0.263133E+09 | 0.108623E+10 |
April | 0.475764E+09 | 1831141.48 | 0.473933E+09 | 0.372785E+09 | 0.823909E+09 |
May | 0.590773E+09 | 27509620.94 | 0.563264E+09 | 0.509355E+09 | 0.716955E+09 |
June | 0.609193E+09 | 59558765.02 | 0.549634E+09 | 0.642204E+09 | 0.547541E+09 |
July | 0.596036E+09 | 49957678.03 | 0.546079E+09 | 0.696886E+09 | 0.499108E+09 |
August | 0.494988E+09 | 9911648.77 | 0.485077E+09 | 0.554753E+09 | 0.523733E+09 |
September | 0.405442E+09 | 63548.58 | 0.405378E+09 | 0.414849E+09 | 0.624693E+09 |
October | 0.332330E+09 | 0.00 | 0.332330E+09 | 0.359689E+09 | 0.738966E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.159108E+09 | 0.104323E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.120840E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148832E+09 | 0.492376E+10 | 0.437922E+10 | 0.995558E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.499108E+09 |
Maximum of Months | 0.609193E+09 | 59558765.02 | 0.563264E+09 | 0.696886E+09 | 0.120840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277405E+09 | 0.00 | 0.277405E+09 | 0.137674E+09 | 0.117440E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.155023E+09 | 0.968414E+09 |
March | 0.426713E+09 | 0.00 | 0.426713E+09 | 0.263133E+09 | 0.108623E+10 |
April | 0.475764E+09 | 1831143.67 | 0.473933E+09 | 0.372785E+09 | 0.823909E+09 |
May | 0.590774E+09 | 27509653.95 | 0.563264E+09 | 0.509356E+09 | 0.716955E+09 |
June | 0.609193E+09 | 59558836.48 | 0.549634E+09 | 0.642204E+09 | 0.547541E+09 |
July | 0.596037E+09 | 49957737.97 | 0.546079E+09 | 0.696886E+09 | 0.499109E+09 |
August | 0.494989E+09 | 9911660.66 | 0.485077E+09 | 0.554753E+09 | 0.523733E+09 |
September | 0.405442E+09 | 63548.65 | 0.405379E+09 | 0.414849E+09 | 0.624693E+09 |
October | 0.332331E+09 | 0.00 | 0.332331E+09 | 0.359689E+09 | 0.738966E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.159108E+09 | 0.104323E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.120840E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148833E+09 | 0.492377E+10 | 0.437922E+10 | 0.995558E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.499109E+09 |
Maximum of Months | 0.609193E+09 | 59558836.48 | 0.563264E+09 | 0.696886E+09 | 0.120840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277404E+09 | 0.00 | 0.277404E+09 | 0.137674E+09 | 0.117440E+10 |
February | 0.314518E+09 | 0.00 | 0.314518E+09 | 0.155023E+09 | 0.968414E+09 |
March | 0.426712E+09 | 0.00 | 0.426712E+09 | 0.263133E+09 | 0.108623E+10 |
April | 0.475764E+09 | 1831141.48 | 0.473933E+09 | 0.372785E+09 | 0.823909E+09 |
May | 0.590773E+09 | 27509620.94 | 0.563264E+09 | 0.509355E+09 | 0.716955E+09 |
June | 0.609193E+09 | 59558765.02 | 0.549634E+09 | 0.642204E+09 | 0.547541E+09 |
July | 0.596036E+09 | 49957678.03 | 0.546079E+09 | 0.696886E+09 | 0.499108E+09 |
August | 0.494988E+09 | 9911648.77 | 0.485077E+09 | 0.554753E+09 | 0.523733E+09 |
September | 0.405442E+09 | 63548.58 | 0.405378E+09 | 0.414849E+09 | 0.624693E+09 |
October | 0.332330E+09 | 0.00 | 0.332330E+09 | 0.359689E+09 | 0.738966E+09 |
November | 0.291195E+09 | 0.00 | 0.291195E+09 | 0.159108E+09 | 0.104323E+10 |
December | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.120840E+10 |
Annual Sum or Average | 0.507260E+10 | 0.148832E+09 | 0.492376E+10 | 0.437922E+10 | 0.995558E+10 |
Minimum of Months | 0.258240E+09 | 0.00 | 0.258240E+09 | 0.113760E+09 | 0.499108E+09 |
Maximum of Months | 0.609193E+09 | 59558765.02 | 0.563264E+09 | 0.696886E+09 | 0.120840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277393E+09 | 0.00 | 0.277393E+09 | 0.137669E+09 | 0.117435E+10 |
February | 0.314506E+09 | 0.00 | 0.314506E+09 | 0.155017E+09 | 0.968375E+09 |
March | 0.426695E+09 | 0.00 | 0.426695E+09 | 0.263122E+09 | 0.108619E+10 |
April | 0.475745E+09 | 1831069.87 | 0.473914E+09 | 0.372770E+09 | 0.823875E+09 |
May | 0.590750E+09 | 27508545.19 | 0.563241E+09 | 0.509335E+09 | 0.716926E+09 |
June | 0.609169E+09 | 59556436.00 | 0.549612E+09 | 0.642179E+09 | 0.547519E+09 |
July | 0.596013E+09 | 49955724.46 | 0.546057E+09 | 0.696858E+09 | 0.499088E+09 |
August | 0.494969E+09 | 9911261.18 | 0.485057E+09 | 0.554731E+09 | 0.523712E+09 |
September | 0.405426E+09 | 63546.09 | 0.405362E+09 | 0.414832E+09 | 0.624668E+09 |
October | 0.332317E+09 | 0.00 | 0.332317E+09 | 0.359675E+09 | 0.738936E+09 |
November | 0.291183E+09 | 0.00 | 0.291183E+09 | 0.159101E+09 | 0.104319E+10 |
December | 0.258230E+09 | 0.00 | 0.258230E+09 | 0.113756E+09 | 0.120835E+10 |
Annual Sum or Average | 0.507240E+10 | 0.148827E+09 | 0.492357E+10 | 0.437905E+10 | 0.995518E+10 |
Minimum of Months | 0.258230E+09 | 0.00 | 0.258230E+09 | 0.113756E+09 | 0.499088E+09 |
Maximum of Months | 0.609169E+09 | 59556436.00 | 0.563241E+09 | 0.696858E+09 | 0.120835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.831412E+09 | 0.444659E+09 | 0.386753E+09 | 0.954532E+09 | 0.121091E+10 |
February | 0.792177E+09 | 0.362903E+09 | 0.429275E+09 | 0.856230E+09 | 0.998808E+09 |
March | 0.106536E+10 | 0.474668E+09 | 0.590695E+09 | 0.121516E+10 | 0.111277E+10 |
April | 0.131812E+10 | 0.661062E+09 | 0.657055E+09 | 0.173789E+10 | 0.863666E+09 |
May | 0.128539E+10 | 0.536423E+09 | 0.748967E+09 | 0.162849E+10 | 0.808893E+09 |
June | 0.123618E+10 | 0.536357E+09 | 0.699823E+09 | 0.168637E+10 | 0.623245E+09 |
July | 0.144738E+10 | 0.719240E+09 | 0.728136E+09 | 0.213298E+10 | 0.567388E+09 |
August | 0.142940E+10 | 0.759250E+09 | 0.670151E+09 | 0.213642E+10 | 0.571556E+09 |
September | 0.100715E+10 | 0.461512E+09 | 0.545633E+09 | 0.141227E+10 | 0.673250E+09 |
October | 0.921225E+09 | 0.473486E+09 | 0.447739E+09 | 0.131003E+10 | 0.774085E+09 |
November | 0.812715E+09 | 0.412893E+09 | 0.399822E+09 | 0.940480E+09 | 0.106533E+10 |
December | 0.801158E+09 | 0.445132E+09 | 0.356026E+09 | 0.916267E+09 | 0.121192E+10 |
Annual Sum or Average | 0.129477E+11 | 0.628758E+10 | 0.666008E+10 | 0.169271E+11 | 0.104818E+11 |
Minimum of Months | 0.792177E+09 | 0.362903E+09 | 0.356026E+09 | 0.856230E+09 | 0.567388E+09 |
Maximum of Months | 0.144738E+10 | 0.759250E+09 | 0.748967E+09 | 0.213642E+10 | 0.121192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.831412E+09 | 0.444659E+09 | 0.386753E+09 | 0.954532E+09 | 0.121091E+10 |
February | 0.792177E+09 | 0.362903E+09 | 0.429275E+09 | 0.856230E+09 | 0.998808E+09 |
March | 0.106536E+10 | 0.474668E+09 | 0.590695E+09 | 0.121516E+10 | 0.111277E+10 |
April | 0.131812E+10 | 0.661062E+09 | 0.657055E+09 | 0.173789E+10 | 0.863666E+09 |
May | 0.128539E+10 | 0.536423E+09 | 0.748967E+09 | 0.162849E+10 | 0.808893E+09 |
June | 0.123618E+10 | 0.536357E+09 | 0.699823E+09 | 0.168637E+10 | 0.623245E+09 |
July | 0.144738E+10 | 0.719240E+09 | 0.728136E+09 | 0.213298E+10 | 0.567388E+09 |
August | 0.142940E+10 | 0.759250E+09 | 0.670151E+09 | 0.213642E+10 | 0.571556E+09 |
September | 0.100715E+10 | 0.461512E+09 | 0.545633E+09 | 0.141227E+10 | 0.673250E+09 |
October | 0.921225E+09 | 0.473486E+09 | 0.447739E+09 | 0.131003E+10 | 0.774085E+09 |
November | 0.812715E+09 | 0.412893E+09 | 0.399822E+09 | 0.940480E+09 | 0.106533E+10 |
December | 0.801158E+09 | 0.445132E+09 | 0.356026E+09 | 0.916267E+09 | 0.121192E+10 |
Annual Sum or Average | 0.129477E+11 | 0.628758E+10 | 0.666008E+10 | 0.169271E+11 | 0.104818E+11 |
Minimum of Months | 0.792177E+09 | 0.362903E+09 | 0.356026E+09 | 0.856230E+09 | 0.567388E+09 |
Maximum of Months | 0.144738E+10 | 0.759250E+09 | 0.748967E+09 | 0.213642E+10 | 0.121192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.831396E+09 | 0.444650E+09 | 0.386746E+09 | 0.954514E+09 | 0.121089E+10 |
February | 0.792163E+09 | 0.362896E+09 | 0.429267E+09 | 0.856214E+09 | 0.998790E+09 |
March | 0.106534E+10 | 0.474659E+09 | 0.590684E+09 | 0.121514E+10 | 0.111275E+10 |
April | 0.131809E+10 | 0.661050E+09 | 0.657043E+09 | 0.173786E+10 | 0.863650E+09 |
May | 0.128537E+10 | 0.536414E+09 | 0.748953E+09 | 0.162846E+10 | 0.808878E+09 |
June | 0.123616E+10 | 0.536347E+09 | 0.699810E+09 | 0.168634E+10 | 0.623233E+09 |
July | 0.144735E+10 | 0.719226E+09 | 0.728123E+09 | 0.213295E+10 | 0.567378E+09 |
August | 0.142937E+10 | 0.759236E+09 | 0.670139E+09 | 0.213638E+10 | 0.571545E+09 |
September | 0.100713E+10 | 0.461504E+09 | 0.545623E+09 | 0.141225E+10 | 0.673238E+09 |
October | 0.921208E+09 | 0.473477E+09 | 0.447731E+09 | 0.131000E+10 | 0.774071E+09 |
November | 0.812700E+09 | 0.412885E+09 | 0.399815E+09 | 0.940462E+09 | 0.106531E+10 |
December | 0.801144E+09 | 0.445124E+09 | 0.356020E+09 | 0.916251E+09 | 0.121190E+10 |
Annual Sum or Average | 0.129474E+11 | 0.628747E+10 | 0.665995E+10 | 0.169268E+11 | 0.104816E+11 |
Minimum of Months | 0.792163E+09 | 0.362896E+09 | 0.356020E+09 | 0.856214E+09 | 0.567378E+09 |
Maximum of Months | 0.144735E+10 | 0.759236E+09 | 0.748953E+09 | 0.213638E+10 | 0.121190E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487792E+09 | 0.263959E+10 | 0.108742E+10 |
February | 0.129958E+10 | 0.800470E+09 | 0.499105E+09 | 0.175979E+10 | 0.905996E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592982E+09 | 0.152332E+10 | 0.104732E+10 |
April | 0.927490E+09 | 0.353661E+09 | 0.573829E+09 | 0.131776E+10 | 0.841584E+09 |
May | 0.682459E+09 | 83985929.99 | 0.598473E+09 | 0.783434E+09 | 0.769098E+09 |
June | 0.579385E+09 | 34981177.23 | 0.544404E+09 | 0.665172E+09 | 0.586612E+09 |
July | 0.634185E+09 | 71391175.62 | 0.562794E+09 | 0.853240E+09 | 0.532153E+09 |
August | 0.814738E+09 | 0.256994E+09 | 0.557744E+09 | 0.127398E+10 | 0.554852E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541180E+09 | 0.172640E+10 | 0.636229E+09 |
October | 0.144181E+10 | 0.963892E+09 | 0.477920E+09 | 0.226737E+10 | 0.722325E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.243771E+10 | 0.973637E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.282937E+10 | 0.110579E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770413E+10 | 0.640200E+10 | 0.200771E+11 | 0.976301E+10 |
Minimum of Months | 0.579385E+09 | 34981177.23 | 0.467169E+09 | 0.665172E+09 | 0.532153E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.282937E+10 | 0.110579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487791E+09 | 0.263959E+10 | 0.108742E+10 |
February | 0.129957E+10 | 0.800469E+09 | 0.499105E+09 | 0.175979E+10 | 0.905996E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592981E+09 | 0.152332E+10 | 0.104732E+10 |
April | 0.927489E+09 | 0.353660E+09 | 0.573829E+09 | 0.131776E+10 | 0.841584E+09 |
May | 0.682458E+09 | 83985829.21 | 0.598473E+09 | 0.783433E+09 | 0.769098E+09 |
June | 0.579385E+09 | 34981135.25 | 0.544403E+09 | 0.665171E+09 | 0.586612E+09 |
July | 0.634185E+09 | 71391089.96 | 0.562794E+09 | 0.853239E+09 | 0.532153E+09 |
August | 0.814737E+09 | 0.256994E+09 | 0.557744E+09 | 0.127397E+10 | 0.554851E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541179E+09 | 0.172639E+10 | 0.636229E+09 |
October | 0.144181E+10 | 0.963891E+09 | 0.477920E+09 | 0.226737E+10 | 0.722324E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.243771E+10 | 0.973637E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.282936E+10 | 0.110579E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770412E+10 | 0.640199E+10 | 0.200771E+11 | 0.976301E+10 |
Minimum of Months | 0.579385E+09 | 34981135.25 | 0.467169E+09 | 0.665171E+09 | 0.532153E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.282936E+10 | 0.110579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487792E+09 | 0.263959E+10 | 0.108742E+10 |
February | 0.129958E+10 | 0.800470E+09 | 0.499105E+09 | 0.175979E+10 | 0.905996E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592982E+09 | 0.152332E+10 | 0.104732E+10 |
April | 0.927490E+09 | 0.353661E+09 | 0.573829E+09 | 0.131776E+10 | 0.841584E+09 |
May | 0.682459E+09 | 83985929.99 | 0.598473E+09 | 0.783434E+09 | 0.769098E+09 |
June | 0.579385E+09 | 34981177.23 | 0.544404E+09 | 0.665172E+09 | 0.586612E+09 |
July | 0.634185E+09 | 71391175.62 | 0.562794E+09 | 0.853240E+09 | 0.532153E+09 |
August | 0.814738E+09 | 0.256994E+09 | 0.557744E+09 | 0.127398E+10 | 0.554852E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541180E+09 | 0.172640E+10 | 0.636229E+09 |
October | 0.144181E+10 | 0.963892E+09 | 0.477920E+09 | 0.226737E+10 | 0.722325E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.243771E+10 | 0.973637E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.282937E+10 | 0.110579E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770413E+10 | 0.640200E+10 | 0.200771E+11 | 0.976301E+10 |
Minimum of Months | 0.579385E+09 | 34981177.23 | 0.467169E+09 | 0.665172E+09 | 0.532153E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.282937E+10 | 0.110579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183068E+10 | 0.134289E+10 | 0.487791E+09 | 0.263959E+10 | 0.108742E+10 |
February | 0.129957E+10 | 0.800469E+09 | 0.499105E+09 | 0.175979E+10 | 0.905996E+09 |
March | 0.114707E+10 | 0.554089E+09 | 0.592981E+09 | 0.152332E+10 | 0.104732E+10 |
April | 0.927489E+09 | 0.353660E+09 | 0.573829E+09 | 0.131776E+10 | 0.841584E+09 |
May | 0.682458E+09 | 83985829.21 | 0.598473E+09 | 0.783433E+09 | 0.769098E+09 |
June | 0.579385E+09 | 34981135.25 | 0.544403E+09 | 0.665171E+09 | 0.586612E+09 |
July | 0.634185E+09 | 71391089.96 | 0.562794E+09 | 0.853239E+09 | 0.532153E+09 |
August | 0.814737E+09 | 0.256994E+09 | 0.557744E+09 | 0.127397E+10 | 0.554851E+09 |
September | 0.109714E+10 | 0.555957E+09 | 0.541179E+09 | 0.172639E+10 | 0.636229E+09 |
October | 0.144181E+10 | 0.963891E+09 | 0.477920E+09 | 0.226737E+10 | 0.722324E+09 |
November | 0.169585E+10 | 0.119724E+10 | 0.498605E+09 | 0.243771E+10 | 0.973637E+09 |
December | 0.195575E+10 | 0.148858E+10 | 0.467169E+09 | 0.282936E+10 | 0.110579E+10 |
Annual Sum or Average | 0.141061E+11 | 0.770412E+10 | 0.640199E+10 | 0.200771E+11 | 0.976301E+10 |
Minimum of Months | 0.579385E+09 | 34981135.25 | 0.467169E+09 | 0.665171E+09 | 0.532153E+09 |
Maximum of Months | 0.195575E+10 | 0.148858E+10 | 0.598473E+09 | 0.282936E+10 | 0.110579E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183060E+10 | 0.134283E+10 | 0.487772E+09 | 0.263949E+10 | 0.108738E+10 |
February | 0.129952E+10 | 0.800438E+09 | 0.499085E+09 | 0.175972E+10 | 0.905960E+09 |
March | 0.114702E+10 | 0.554067E+09 | 0.592958E+09 | 0.152326E+10 | 0.104728E+10 |
April | 0.927453E+09 | 0.353647E+09 | 0.573806E+09 | 0.131771E+10 | 0.841550E+09 |
May | 0.682431E+09 | 83982544.98 | 0.598449E+09 | 0.783402E+09 | 0.769067E+09 |
June | 0.579362E+09 | 34979767.33 | 0.544382E+09 | 0.665145E+09 | 0.586588E+09 |
July | 0.634160E+09 | 71388298.25 | 0.562772E+09 | 0.853206E+09 | 0.532131E+09 |
August | 0.814705E+09 | 0.256984E+09 | 0.557722E+09 | 0.127392E+10 | 0.554829E+09 |
September | 0.109709E+10 | 0.555935E+09 | 0.541158E+09 | 0.172633E+10 | 0.636203E+09 |
October | 0.144175E+10 | 0.963853E+09 | 0.477901E+09 | 0.226728E+10 | 0.722295E+09 |
November | 0.169578E+10 | 0.119719E+10 | 0.498585E+09 | 0.243761E+10 | 0.973597E+09 |
December | 0.195567E+10 | 0.148852E+10 | 0.467151E+09 | 0.282925E+10 | 0.110574E+10 |
Annual Sum or Average | 0.141056E+11 | 0.770382E+10 | 0.640174E+10 | 0.200763E+11 | 0.976262E+10 |
Minimum of Months | 0.579362E+09 | 34979767.33 | 0.467151E+09 | 0.665145E+09 | 0.532131E+09 |
Maximum of Months | 0.195567E+10 | 0.148852E+10 | 0.598449E+09 | 0.282925E+10 | 0.110574E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791358E+09 | 0.399125E+09 | 0.392233E+09 | 0.936017E+09 | 0.136331E+10 |
February | 0.852730E+09 | 0.393660E+09 | 0.459070E+09 | 0.958737E+09 | 0.116359E+10 |
March | 0.108218E+10 | 0.478775E+09 | 0.603409E+09 | 0.123260E+10 | 0.131773E+10 |
April | 0.144373E+10 | 0.751746E+09 | 0.691980E+09 | 0.189490E+10 | 0.105971E+10 |
May | 0.146547E+10 | 0.676896E+09 | 0.788569E+09 | 0.189824E+10 | 0.913651E+09 |
June | 0.150242E+10 | 0.751181E+09 | 0.751238E+09 | 0.205951E+10 | 0.724570E+09 |
July | 0.164344E+10 | 0.879393E+09 | 0.764052E+09 | 0.237250E+10 | 0.685959E+09 |
August | 0.154187E+10 | 0.835631E+09 | 0.706241E+09 | 0.225034E+10 | 0.727022E+09 |
September | 0.127754E+10 | 0.683594E+09 | 0.593948E+09 | 0.182152E+10 | 0.759922E+09 |
October | 0.100918E+10 | 0.550967E+09 | 0.458209E+09 | 0.144784E+10 | 0.909124E+09 |
November | 0.882182E+09 | 0.461443E+09 | 0.420739E+09 | 0.106488E+10 | 0.126573E+10 |
December | 0.805090E+09 | 0.431812E+09 | 0.373277E+09 | 0.947300E+09 | 0.148295E+10 |
Annual Sum or Average | 0.142972E+11 | 0.729422E+10 | 0.700297E+10 | 0.188844E+11 | 0.123733E+11 |
Minimum of Months | 0.791358E+09 | 0.393660E+09 | 0.373277E+09 | 0.936017E+09 | 0.685959E+09 |
Maximum of Months | 0.164344E+10 | 0.879393E+09 | 0.788569E+09 | 0.237250E+10 | 0.148295E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791358E+09 | 0.399125E+09 | 0.392233E+09 | 0.936017E+09 | 0.136331E+10 |
February | 0.852730E+09 | 0.393660E+09 | 0.459070E+09 | 0.958737E+09 | 0.116359E+10 |
March | 0.108218E+10 | 0.478775E+09 | 0.603409E+09 | 0.123260E+10 | 0.131773E+10 |
April | 0.144373E+10 | 0.751746E+09 | 0.691980E+09 | 0.189490E+10 | 0.105971E+10 |
May | 0.146547E+10 | 0.676896E+09 | 0.788569E+09 | 0.189824E+10 | 0.913651E+09 |
June | 0.150242E+10 | 0.751181E+09 | 0.751238E+09 | 0.205951E+10 | 0.724570E+09 |
July | 0.164344E+10 | 0.879393E+09 | 0.764052E+09 | 0.237250E+10 | 0.685959E+09 |
August | 0.154187E+10 | 0.835631E+09 | 0.706241E+09 | 0.225034E+10 | 0.727022E+09 |
September | 0.127754E+10 | 0.683594E+09 | 0.593948E+09 | 0.182152E+10 | 0.759922E+09 |
October | 0.100918E+10 | 0.550967E+09 | 0.458209E+09 | 0.144784E+10 | 0.909124E+09 |
November | 0.882182E+09 | 0.461443E+09 | 0.420739E+09 | 0.106488E+10 | 0.126573E+10 |
December | 0.805090E+09 | 0.431812E+09 | 0.373277E+09 | 0.947300E+09 | 0.148295E+10 |
Annual Sum or Average | 0.142972E+11 | 0.729422E+10 | 0.700297E+10 | 0.188844E+11 | 0.123733E+11 |
Minimum of Months | 0.791358E+09 | 0.393660E+09 | 0.373277E+09 | 0.936017E+09 | 0.685959E+09 |
Maximum of Months | 0.164344E+10 | 0.879393E+09 | 0.788569E+09 | 0.237250E+10 | 0.148295E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791344E+09 | 0.399118E+09 | 0.392226E+09 | 0.936000E+09 | 0.136329E+10 |
February | 0.852714E+09 | 0.393653E+09 | 0.459061E+09 | 0.958720E+09 | 0.116357E+10 |
March | 0.108216E+10 | 0.478767E+09 | 0.603398E+09 | 0.123258E+10 | 0.131771E+10 |
April | 0.144370E+10 | 0.751732E+09 | 0.691967E+09 | 0.189486E+10 | 0.105970E+10 |
May | 0.146544E+10 | 0.676884E+09 | 0.788555E+09 | 0.189821E+10 | 0.913634E+09 |
June | 0.150239E+10 | 0.751167E+09 | 0.751224E+09 | 0.205948E+10 | 0.724556E+09 |
July | 0.164341E+10 | 0.879377E+09 | 0.764038E+09 | 0.237245E+10 | 0.685946E+09 |
August | 0.154184E+10 | 0.835616E+09 | 0.706228E+09 | 0.225030E+10 | 0.727008E+09 |
September | 0.127752E+10 | 0.683582E+09 | 0.593937E+09 | 0.182149E+10 | 0.759908E+09 |
October | 0.100916E+10 | 0.550957E+09 | 0.458201E+09 | 0.144782E+10 | 0.909107E+09 |
November | 0.882166E+09 | 0.461435E+09 | 0.420731E+09 | 0.106486E+10 | 0.126570E+10 |
December | 0.805075E+09 | 0.431805E+09 | 0.373270E+09 | 0.947283E+09 | 0.148292E+10 |
Annual Sum or Average | 0.142969E+11 | 0.729409E+10 | 0.700284E+10 | 0.188840E+11 | 0.123730E+11 |
Minimum of Months | 0.791344E+09 | 0.393653E+09 | 0.373270E+09 | 0.936000E+09 | 0.685946E+09 |
Maximum of Months | 0.164341E+10 | 0.879377E+09 | 0.788555E+09 | 0.237245E+10 | 0.148292E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.835617E+09 | 0.529168E+10 |
February | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.898586E+09 | 0.435856E+10 |
March | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.145754E+10 | 0.493078E+10 |
April | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.200646E+10 | 0.375016E+10 |
May | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.262770E+10 | 0.340449E+10 |
June | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.326285E+10 | 0.258923E+10 |
July | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.356070E+10 | 0.237731E+10 |
August | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.286090E+10 | 0.249223E+10 |
September | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.214119E+10 | 0.290850E+10 |
October | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.191290E+10 | 0.337019E+10 |
November | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.939419E+09 | 0.468131E+10 |
December | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.755041E+09 | 0.532492E+10 |
Annual Sum or Average | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.232589E+11 | 0.454794E+11 |
Minimum of Months | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.755041E+09 | 0.237731E+10 |
Maximum of Months | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.356070E+10 | 0.532492E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.289567E+10 | 0.342122E+10 |
February | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.258118E+10 | 0.282616E+10 |
March | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.364433E+10 | 0.318982E+10 |
April | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.518246E+10 | 0.250760E+10 |
May | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.483812E+10 | 0.236847E+10 |
June | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.501069E+10 | 0.182756E+10 |
July | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.633665E+10 | 0.169994E+10 |
August | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.634206E+10 | 0.173830E+10 |
September | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.421113E+10 | 0.194840E+10 |
October | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.391909E+10 | 0.222088E+10 |
November | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.283603E+10 | 0.303187E+10 |
December | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.278797E+10 | 0.342394E+10 |
Annual Sum or Average | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.505854E+11 | 0.302041E+11 |
Minimum of Months | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.258118E+10 | 0.169994E+10 |
Maximum of Months | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.634206E+10 | 0.342394E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.131132E+11 | 0.536760E+10 |
February | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.872688E+10 | 0.441082E+10 |
March | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.758700E+10 | 0.505254E+10 |
April | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.658799E+10 | 0.402689E+10 |
May | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.390762E+10 | 0.374073E+10 |
June | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.335061E+10 | 0.280758E+10 |
July | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.430376E+10 | 0.256297E+10 |
August | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.637260E+10 | 0.271477E+10 |
September | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.857351E+10 | 0.311508E+10 |
October | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.112671E+11 | 0.352981E+10 |
November | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.121084E+11 | 0.474979E+10 |
December | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.140734E+11 | 0.537695E+10 |
Annual Sum or Average | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.999720E+11 | 0.474555E+11 |
Minimum of Months | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.335061E+10 | 0.256297E+10 |
Maximum of Months | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.140734E+11 | 0.537695E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.288949E+10 | 0.367553E+10 |
February | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.295819E+10 | 0.305066E+10 |
March | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.381145E+10 | 0.343276E+10 |
April | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.580043E+10 | 0.276259E+10 |
May | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.570582E+10 | 0.256911E+10 |
June | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.621489E+10 | 0.196359E+10 |
July | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.719148E+10 | 0.184163E+10 |
August | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.684556E+10 | 0.191419E+10 |
September | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.547791E+10 | 0.210988E+10 |
October | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.441882E+10 | 0.242747E+10 |
November | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.330605E+10 | 0.327383E+10 |
December | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.299035E+10 | 0.373632E+10 |
Annual Sum or Average | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.576104E+11 | 0.327576E+11 |
Minimum of Months | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.288949E+10 | 0.184163E+10 |
Maximum of Months | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.719148E+10 | 0.373632E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.981370E+09 | 0.477315E+10 |
February | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.102670E+10 | 0.393623E+10 |
March | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.157908E+10 | 0.456698E+10 |
April | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.205737E+10 | 0.355553E+10 |
May | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.269496E+10 | 0.324606E+10 |
June | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.325182E+10 | 0.251407E+10 |
July | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.351678E+10 | 0.233436E+10 |
August | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.283346E+10 | 0.243758E+10 |
September | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.215599E+10 | 0.278579E+10 |
October | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.195980E+10 | 0.318198E+10 |
November | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.106167E+10 | 0.427923E+10 |
December | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.901949E+09 | 0.480503E+10 |
Annual Sum or Average | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.240209E+11 | 0.424160E+11 |
Minimum of Months | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.901949E+09 | 0.233436E+10 |
Maximum of Months | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.351678E+10 | 0.480503E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.302000E+10 | 0.312072E+10 |
February | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.268177E+10 | 0.257875E+10 |
March | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.373587E+10 | 0.298350E+10 |
April | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.521883E+10 | 0.240225E+10 |
May | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.487925E+10 | 0.227526E+10 |
June | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.501454E+10 | 0.178246E+10 |
July | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.631995E+10 | 0.167661E+10 |
August | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.633111E+10 | 0.170828E+10 |
September | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.422708E+10 | 0.187649E+10 |
October | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.395680E+10 | 0.211738E+10 |
November | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.292966E+10 | 0.281127E+10 |
December | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.291250E+10 | 0.313251E+10 |
Annual Sum or Average | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.512274E+11 | 0.284655E+11 |
Minimum of Months | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.268177E+10 | 0.167661E+10 |
Maximum of Months | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.633111E+10 | 0.313251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.132428E+11 | 0.497528E+10 |
February | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.882420E+10 | 0.406573E+10 |
March | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.767344E+10 | 0.473562E+10 |
April | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.661011E+10 | 0.384798E+10 |
May | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.394535E+10 | 0.356917E+10 |
June | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.333968E+10 | 0.272835E+10 |
July | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.426383E+10 | 0.252267E+10 |
August | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.633250E+10 | 0.266439E+10 |
September | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.855951E+10 | 0.300954E+10 |
October | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.112821E+11 | 0.338758E+10 |
November | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.121918E+11 | 0.446030E+10 |
December | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.141976E+11 | 0.501319E+10 |
Annual Sum or Average | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.100463E+12 | 0.449798E+11 |
Minimum of Months | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.333968E+10 | 0.252267E+10 |
Maximum of Months | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.141976E+11 | 0.501319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.295455E+10 | 0.340058E+10 |
February | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.301171E+10 | 0.282317E+10 |
March | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.385356E+10 | 0.323173E+10 |
April | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.579482E+10 | 0.265494E+10 |
May | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.570124E+10 | 0.247215E+10 |
June | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.618048E+10 | 0.191512E+10 |
July | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.714190E+10 | 0.181182E+10 |
August | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.680180E+10 | 0.188094E+10 |
September | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.545832E+10 | 0.204516E+10 |
October | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.442200E+10 | 0.232742E+10 |
November | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.335182E+10 | 0.306159E+10 |
December | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.305481E+10 | 0.346136E+10 |
Annual Sum or Average | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.577270E+11 | 0.310860E+11 |
Minimum of Months | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.295455E+10 | 0.181182E+10 |
Maximum of Months | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.714190E+10 | 0.346136E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 257.01 | 2192.33 | 517.85 | 0.00 | 517.85 | 0.00 | 0.00 |
February | 320.40 | 2001.50 | 650.04 | 0.00 | 650.04 | 0.00 | 0.00 |
March | 491.21 | 2027.75 | 796.57 | 0.00 | 796.57 | 0.00 | 0.00 |
April | 719.10 | 1589.32 | 917.75 | 3.53 | 914.22 | 0.00 | 0.00 |
May | 950.85 | 1338.39 | 1102.84 | 51.35 | 1051.49 | 0.00 | 0.00 |
June | 1238.81 | 1056.20 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
July | 1300.93 | 931.72 | 1112.66 | 93.26 | 1019.40 | 0.00 | 0.00 |
August | 1035.60 | 977.69 | 924.03 | 18.50 | 905.53 | 0.00 | 0.00 |
September | 800.24 | 1205.03 | 782.10 | 0.12 | 781.97 | 0.00 | 0.00 |
October | 671.46 | 1379.48 | 620.38 | 0.00 | 620.38 | 0.00 | 0.00 |
November | 306.92 | 2012.39 | 561.71 | 0.00 | 561.71 | 0.00 | 0.00 |
December | 212.36 | 2255.81 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Annual Sum or Average | 694.32 | 1578.43 | 804.25 | 23.60 | 780.65 | 0.00 | 0.00 |
Minimum of Months | 212.36 | 931.72 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Maximum of Months | 1300.93 | 2255.81 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1069.14 | 1356.30 | 931.23 | 498.05 | 433.19 | 0.00 | 0.00 |
February | 1061.79 | 1238.59 | 982.36 | 450.03 | 532.33 | 0.00 | 0.00 |
March | 1361.06 | 1246.38 | 1193.28 | 531.66 | 661.62 | 0.00 | 0.00 |
April | 2011.44 | 999.61 | 1525.59 | 765.11 | 760.48 | 0.00 | 0.00 |
May | 1824.01 | 906.01 | 1439.72 | 600.83 | 838.89 | 0.00 | 0.00 |
June | 1951.81 | 721.34 | 1430.75 | 620.78 | 809.98 | 0.00 | 0.00 |
July | 2389.08 | 635.51 | 1621.15 | 805.59 | 815.56 | 0.00 | 0.00 |
August | 2392.92 | 640.18 | 1601.02 | 850.41 | 750.61 | 0.00 | 0.00 |
September | 1634.56 | 779.22 | 1165.67 | 534.15 | 631.52 | 0.00 | 0.00 |
October | 1467.32 | 867.03 | 1031.83 | 530.34 | 501.50 | 0.00 | 0.00 |
November | 1088.51 | 1233.01 | 940.64 | 477.88 | 462.75 | 0.00 | 0.00 |
December | 1026.28 | 1357.43 | 897.35 | 498.58 | 398.77 | 0.00 | 0.00 |
Annual Sum or Average | 1610.26 | 997.12 | 1231.70 | 598.13 | 633.56 | 0.00 | 0.00 |
Minimum of Months | 1026.28 | 635.51 | 897.35 | 450.03 | 398.77 | 0.00 | 0.00 |
Maximum of Months | 2392.92 | 1357.43 | 1621.15 | 850.41 | 838.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4927.51 | 2029.97 | 3417.46 | 2506.86 | 910.60 | 0.00 | 0.00 |
February | 3637.10 | 1872.50 | 2685.94 | 1654.40 | 1031.54 | 0.00 | 0.00 |
March | 2843.70 | 1955.10 | 2141.32 | 1034.36 | 1106.96 | 0.00 | 0.00 |
April | 2541.95 | 1623.41 | 1789.12 | 682.21 | 1106.91 | 0.00 | 0.00 |
May | 1462.49 | 1435.73 | 1273.99 | 156.78 | 1117.21 | 0.00 | 0.00 |
June | 1283.11 | 1131.57 | 1117.63 | 67.48 | 1050.15 | 0.00 | 0.00 |
July | 1592.80 | 993.41 | 1183.88 | 133.27 | 1050.61 | 0.00 | 0.00 |
August | 2378.22 | 1035.78 | 1520.93 | 479.75 | 1041.18 | 0.00 | 0.00 |
September | 3330.21 | 1227.28 | 2116.37 | 1072.44 | 1043.93 | 0.00 | 0.00 |
October | 4232.66 | 1348.41 | 2691.53 | 1799.36 | 892.17 | 0.00 | 0.00 |
November | 4702.34 | 1878.14 | 3271.28 | 2309.48 | 961.81 | 0.00 | 0.00 |
December | 5281.78 | 2064.25 | 3650.94 | 2778.84 | 872.10 | 0.00 | 0.00 |
Annual Sum or Average | 3183.18 | 1547.90 | 2236.49 | 1221.47 | 1015.02 | 0.00 | 0.00 |
Minimum of Months | 1283.11 | 993.41 | 1117.63 | 67.48 | 872.10 | 0.00 | 0.00 |
Maximum of Months | 5281.78 | 2064.25 | 3650.94 | 2778.84 | 1117.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1048.40 | 1527.00 | 886.37 | 447.05 | 439.33 | 0.00 | 0.00 |
February | 1188.90 | 1442.93 | 1057.45 | 488.17 | 569.28 | 0.00 | 0.00 |
March | 1380.59 | 1475.95 | 1212.12 | 536.26 | 675.86 | 0.00 | 0.00 |
April | 2193.16 | 1226.51 | 1670.97 | 870.07 | 800.90 | 0.00 | 0.00 |
May | 2126.15 | 1023.35 | 1641.42 | 758.17 | 883.25 | 0.00 | 0.00 |
June | 2383.68 | 838.62 | 1738.90 | 869.42 | 869.48 | 0.00 | 0.00 |
July | 2657.35 | 768.32 | 1840.76 | 984.98 | 855.79 | 0.00 | 0.00 |
August | 2520.53 | 814.31 | 1727.00 | 935.96 | 791.04 | 0.00 | 0.00 |
September | 2108.23 | 879.53 | 1478.63 | 791.19 | 687.44 | 0.00 | 0.00 |
October | 1621.68 | 1018.28 | 1130.34 | 617.12 | 513.22 | 0.00 | 0.00 |
November | 1232.49 | 1464.95 | 1021.04 | 534.07 | 486.96 | 0.00 | 0.00 |
December | 1061.04 | 1661.00 | 901.75 | 483.66 | 418.09 | 0.00 | 0.00 |
Annual Sum or Average | 1796.45 | 1177.05 | 1360.07 | 693.89 | 666.18 | 0.00 | 0.00 |
Minimum of Months | 1048.40 | 768.32 | 886.37 | 447.05 | 418.09 | 0.00 | 0.00 |
Maximum of Months | 2657.35 | 1661.00 | 1840.76 | 984.98 | 883.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 311.98 | 1975.69 | 517.85 | 0.00 | 517.85 | 0.00 | 0.00 |
February | 371.44 | 1801.65 | 650.04 | 0.00 | 650.04 | 0.00 | 0.00 |
March | 544.18 | 1840.94 | 796.57 | 0.00 | 796.57 | 0.00 | 0.00 |
April | 774.10 | 1446.82 | 917.74 | 3.53 | 914.21 | 0.00 | 0.00 |
May | 981.07 | 1271.09 | 1102.84 | 51.35 | 1051.48 | 0.00 | 0.00 |
June | 1258.81 | 998.93 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
July | 1329.41 | 887.58 | 1112.66 | 93.26 | 1019.40 | 0.00 | 0.00 |
August | 1068.14 | 930.49 | 924.03 | 18.50 | 905.52 | 0.00 | 0.00 |
September | 826.08 | 1122.11 | 782.09 | 0.12 | 781.97 | 0.00 | 0.00 |
October | 714.19 | 1258.29 | 620.38 | 0.00 | 620.38 | 0.00 | 0.00 |
November | 362.43 | 1806.06 | 561.71 | 0.00 | 561.71 | 0.00 | 0.00 |
December | 281.90 | 1988.10 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Annual Sum or Average | 737.53 | 1442.14 | 804.25 | 23.60 | 780.65 | 0.00 | 0.00 |
Minimum of Months | 281.90 | 887.58 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Maximum of Months | 1329.41 | 1988.10 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1081.12 | 1277.34 | 931.23 | 498.04 | 433.19 | 0.00 | 0.00 |
February | 1066.96 | 1168.22 | 982.35 | 450.02 | 532.33 | 0.00 | 0.00 |
March | 1360.64 | 1190.94 | 1193.27 | 531.66 | 661.61 | 0.00 | 0.00 |
April | 1999.41 | 967.44 | 1525.58 | 765.11 | 760.47 | 0.00 | 0.00 |
May | 1806.35 | 884.29 | 1439.71 | 600.83 | 838.89 | 0.00 | 0.00 |
June | 1933.14 | 705.08 | 1430.75 | 620.78 | 809.97 | 0.00 | 0.00 |
July | 2365.83 | 634.68 | 1621.15 | 805.59 | 815.56 | 0.00 | 0.00 |
August | 2367.85 | 649.01 | 1601.02 | 850.41 | 750.61 | 0.00 | 0.00 |
September | 1624.66 | 751.70 | 1165.67 | 534.15 | 631.51 | 0.00 | 0.00 |
October | 1463.22 | 829.18 | 1031.83 | 530.33 | 501.49 | 0.00 | 0.00 |
November | 1094.15 | 1169.70 | 940.63 | 477.88 | 462.75 | 0.00 | 0.00 |
December | 1040.91 | 1278.35 | 897.35 | 498.57 | 398.77 | 0.00 | 0.00 |
Annual Sum or Average | 1604.05 | 957.77 | 1231.69 | 598.13 | 633.56 | 0.00 | 0.00 |
Minimum of Months | 1040.91 | 634.68 | 897.35 | 450.02 | 398.77 | 0.00 | 0.00 |
Maximum of Months | 2367.85 | 1278.35 | 1621.15 | 850.41 | 838.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4895.91 | 2004.03 | 3417.44 | 2506.85 | 910.59 | 0.00 | 0.00 |
February | 3607.34 | 1823.26 | 2685.93 | 1654.39 | 1031.54 | 0.00 | 0.00 |
March | 2832.66 | 1886.40 | 2141.31 | 1034.35 | 1106.96 | 0.00 | 0.00 |
April | 2541.66 | 1553.59 | 1789.12 | 682.21 | 1106.91 | 0.00 | 0.00 |
May | 1458.94 | 1396.63 | 1273.99 | 156.78 | 1117.21 | 0.00 | 0.00 |
June | 1292.67 | 1083.17 | 1117.63 | 67.48 | 1050.15 | 0.00 | 0.00 |
July | 1606.84 | 956.90 | 1183.87 | 133.27 | 1050.60 | 0.00 | 0.00 |
August | 2379.26 | 1013.58 | 1520.92 | 479.75 | 1041.18 | 0.00 | 0.00 |
September | 3307.68 | 1201.80 | 2116.36 | 1072.44 | 1043.93 | 0.00 | 0.00 |
October | 4206.66 | 1317.88 | 2691.52 | 1799.36 | 892.16 | 0.00 | 0.00 |
November | 4671.46 | 1832.48 | 3271.27 | 2309.47 | 961.80 | 0.00 | 0.00 |
December | 5254.39 | 2007.52 | 3650.92 | 2778.83 | 872.09 | 0.00 | 0.00 |
Annual Sum or Average | 3170.09 | 1504.81 | 2236.49 | 1221.47 | 1015.02 | 0.00 | 0.00 |
Minimum of Months | 1292.67 | 956.90 | 1117.63 | 67.48 | 872.09 | 0.00 | 0.00 |
Maximum of Months | 5254.39 | 2007.52 | 3650.92 | 2778.83 | 1117.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1078.81 | 1372.29 | 886.37 | 447.04 | 439.32 | 0.00 | 0.00 |
February | 1222.79 | 1261.02 | 1057.44 | 488.16 | 569.28 | 0.00 | 0.00 |
March | 1423.03 | 1281.64 | 1212.11 | 536.26 | 675.85 | 0.00 | 0.00 |
April | 2237.82 | 1065.81 | 1670.96 | 870.07 | 800.89 | 0.00 | 0.00 |
May | 2130.31 | 959.19 | 1641.41 | 758.16 | 883.25 | 0.00 | 0.00 |
June | 2397.72 | 757.56 | 1738.89 | 869.41 | 869.48 | 0.00 | 0.00 |
July | 2684.99 | 687.59 | 1840.76 | 984.97 | 855.78 | 0.00 | 0.00 |
August | 2555.84 | 714.68 | 1726.99 | 935.96 | 791.03 | 0.00 | 0.00 |
September | 2113.39 | 814.00 | 1478.62 | 791.19 | 687.43 | 0.00 | 0.00 |
October | 1649.80 | 906.31 | 1130.34 | 617.12 | 513.22 | 0.00 | 0.00 |
November | 1275.48 | 1263.05 | 1021.03 | 534.07 | 486.96 | 0.00 | 0.00 |
December | 1116.47 | 1394.98 | 901.75 | 483.66 | 418.09 | 0.00 | 0.00 |
Annual Sum or Average | 1826.81 | 1038.74 | 1360.07 | 693.89 | 666.18 | 0.00 | 0.00 |
Minimum of Months | 1078.81 | 687.59 | 886.37 | 447.04 | 418.09 | 0.00 | 0.00 |
Maximum of Months | 2684.99 | 1394.98 | 1840.76 | 984.97 | 883.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.40 | 1782.09 | 517.85 | 0.00 | 517.85 | 0.00 | 0.00 |
February | 424.40 | 1627.08 | 650.04 | 0.00 | 650.04 | 0.00 | 0.00 |
March | 589.56 | 1705.12 | 796.57 | 0.00 | 796.57 | 0.00 | 0.00 |
April | 793.74 | 1371.73 | 917.74 | 3.53 | 914.21 | 0.00 | 0.00 |
May | 1006.18 | 1211.94 | 1102.84 | 51.35 | 1051.48 | 0.00 | 0.00 |
June | 1254.56 | 969.93 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
July | 1313.01 | 871.55 | 1112.66 | 93.26 | 1019.40 | 0.00 | 0.00 |
August | 1057.89 | 910.09 | 924.03 | 18.50 | 905.52 | 0.00 | 0.00 |
September | 831.79 | 1074.77 | 782.09 | 0.12 | 781.97 | 0.00 | 0.00 |
October | 731.71 | 1188.02 | 620.38 | 0.00 | 620.38 | 0.00 | 0.00 |
November | 409.60 | 1650.94 | 561.71 | 0.00 | 561.71 | 0.00 | 0.00 |
December | 336.75 | 1793.99 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Annual Sum or Average | 761.70 | 1345.00 | 804.25 | 23.60 | 780.65 | 0.00 | 0.00 |
Minimum of Months | 336.75 | 871.55 | 482.07 | 0.00 | 482.07 | 0.00 | 0.00 |
Maximum of Months | 1313.01 | 1793.99 | 1175.13 | 114.89 | 1060.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1127.54 | 1165.14 | 931.23 | 498.04 | 433.19 | 0.00 | 0.00 |
February | 1108.53 | 1065.95 | 982.35 | 450.02 | 532.33 | 0.00 | 0.00 |
March | 1394.81 | 1113.91 | 1193.27 | 531.66 | 661.61 | 0.00 | 0.00 |
April | 2013.44 | 926.79 | 1525.58 | 765.11 | 760.47 | 0.00 | 0.00 |
May | 1821.70 | 849.49 | 1439.71 | 600.83 | 838.89 | 0.00 | 0.00 |
June | 1934.62 | 687.68 | 1430.75 | 620.78 | 809.97 | 0.00 | 0.00 |
July | 2359.60 | 625.98 | 1621.15 | 805.59 | 815.56 | 0.00 | 0.00 |
August | 2363.77 | 637.80 | 1601.02 | 850.41 | 750.61 | 0.00 | 0.00 |
September | 1630.82 | 723.96 | 1165.67 | 534.15 | 631.51 | 0.00 | 0.00 |
October | 1477.30 | 790.54 | 1031.83 | 530.33 | 501.49 | 0.00 | 0.00 |
November | 1130.27 | 1084.60 | 940.63 | 477.88 | 462.75 | 0.00 | 0.00 |
December | 1087.40 | 1169.55 | 897.35 | 498.57 | 398.77 | 0.00 | 0.00 |
Annual Sum or Average | 1624.41 | 902.63 | 1231.69 | 598.13 | 633.56 | 0.00 | 0.00 |
Minimum of Months | 1087.40 | 625.98 | 897.35 | 450.02 | 398.77 | 0.00 | 0.00 |
Maximum of Months | 2363.77 | 1169.55 | 1621.15 | 850.41 | 838.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4944.29 | 1857.56 | 3417.44 | 2506.85 | 910.59 | 0.00 | 0.00 |
February | 3647.57 | 1680.61 | 2685.93 | 1654.39 | 1031.54 | 0.00 | 0.00 |
March | 2864.93 | 1768.08 | 2141.31 | 1034.35 | 1106.96 | 0.00 | 0.00 |
April | 2550.20 | 1484.56 | 1789.12 | 682.21 | 1106.91 | 0.00 | 0.00 |
May | 1473.03 | 1332.58 | 1273.99 | 156.78 | 1117.21 | 0.00 | 0.00 |
June | 1288.46 | 1052.60 | 1117.63 | 67.48 | 1050.15 | 0.00 | 0.00 |
July | 1591.93 | 941.86 | 1183.87 | 133.27 | 1050.60 | 0.00 | 0.00 |
August | 2364.29 | 994.77 | 1520.92 | 479.75 | 1041.18 | 0.00 | 0.00 |
September | 3302.28 | 1161.09 | 2116.36 | 1072.44 | 1043.93 | 0.00 | 0.00 |
October | 4212.25 | 1264.78 | 2691.52 | 1799.36 | 892.16 | 0.00 | 0.00 |
November | 4703.62 | 1720.79 | 3271.27 | 2309.47 | 961.80 | 0.00 | 0.00 |
December | 5300.77 | 1871.71 | 3650.92 | 2778.83 | 872.09 | 0.00 | 0.00 |
Annual Sum or Average | 3185.66 | 1426.30 | 2236.49 | 1221.47 | 1015.02 | 0.00 | 0.00 |
Minimum of Months | 1288.46 | 941.86 | 1117.63 | 67.48 | 872.09 | 0.00 | 0.00 |
Maximum of Months | 5300.77 | 1871.71 | 3650.92 | 2778.83 | 1117.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1103.10 | 1269.63 | 886.37 | 447.04 | 439.32 | 0.00 | 0.00 |
February | 1244.92 | 1166.98 | 1057.44 | 488.16 | 569.28 | 0.00 | 0.00 |
March | 1438.75 | 1206.59 | 1212.11 | 536.26 | 675.85 | 0.00 | 0.00 |
April | 2235.65 | 1024.28 | 1670.96 | 870.07 | 800.89 | 0.00 | 0.00 |
May | 2128.60 | 922.99 | 1641.41 | 758.16 | 883.25 | 0.00 | 0.00 |
June | 2384.44 | 738.86 | 1738.89 | 869.41 | 869.48 | 0.00 | 0.00 |
July | 2666.48 | 676.45 | 1840.76 | 984.97 | 855.78 | 0.00 | 0.00 |
August | 2539.50 | 702.26 | 1726.99 | 935.96 | 791.03 | 0.00 | 0.00 |
September | 2105.83 | 789.03 | 1478.62 | 791.19 | 687.43 | 0.00 | 0.00 |
October | 1650.98 | 868.96 | 1130.34 | 617.12 | 513.22 | 0.00 | 0.00 |
November | 1293.14 | 1181.17 | 1021.03 | 534.07 | 486.96 | 0.00 | 0.00 |
December | 1140.53 | 1292.32 | 901.75 | 483.66 | 418.09 | 0.00 | 0.00 |
Annual Sum or Average | 1830.51 | 985.73 | 1360.07 | 693.89 | 666.18 | 0.00 | 0.00 |
Minimum of Months | 1103.10 | 676.45 | 886.37 | 447.04 | 418.09 | 0.00 | 0.00 |
Maximum of Months | 2666.48 | 1292.32 | 1840.76 | 984.97 | 883.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.688366E+09 | 0.587195E+10 | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.00 | 0.00 |
February | 0.775109E+09 | 0.484203E+10 | 0.157258E+10 | 0.00 | 0.157258E+10 | 0.00 | 0.00 |
March | 0.131565E+10 | 0.543113E+10 | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.00 | 0.00 |
April | 0.186391E+10 | 0.411951E+10 | 0.237880E+10 | 9155640.17 | 0.236965E+10 | 0.00 | 0.00 |
May | 0.254676E+10 | 0.358475E+10 | 0.295384E+10 | 0.137547E+09 | 0.281630E+10 | 0.00 | 0.00 |
June | 0.321100E+10 | 0.273768E+10 | 0.304594E+10 | 0.297792E+09 | 0.274815E+10 | 0.00 | 0.00 |
July | 0.348440E+10 | 0.249552E+10 | 0.298016E+10 | 0.249787E+09 | 0.273037E+10 | 0.00 | 0.00 |
August | 0.277374E+10 | 0.261864E+10 | 0.247492E+10 | 49557880.04 | 0.242536E+10 | 0.00 | 0.00 |
September | 0.207423E+10 | 0.312344E+10 | 0.202719E+10 | 317740.55 | 0.202688E+10 | 0.00 | 0.00 |
October | 0.179843E+10 | 0.369480E+10 | 0.166164E+10 | 0.00 | 0.166164E+10 | 0.00 | 0.00 |
November | 0.795532E+09 | 0.521610E+10 | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.00 | 0.00 |
December | 0.568796E+09 | 0.604196E+10 | 0.129119E+10 | 0.00 | 0.129119E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.218959E+11 | 0.497775E+11 | 0.253628E+11 | 0.744157E+09 | 0.246186E+11 | 0.00 | 0.00 |
Minimum of Months | 0.568796E+09 | 0.249552E+10 | 0.129119E+10 | 0.00 | 0.129119E+10 | 0.00 | 0.00 |
Maximum of Months | 0.348440E+10 | 0.604196E+10 | 0.304594E+10 | 0.297792E+09 | 0.281630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.286358E+10 | 0.363272E+10 | 0.249422E+10 | 0.133397E+10 | 0.116025E+10 | 0.00 | 0.00 |
February | 0.256867E+10 | 0.299641E+10 | 0.237652E+10 | 0.108870E+10 | 0.128782E+10 | 0.00 | 0.00 |
March | 0.364546E+10 | 0.333830E+10 | 0.319607E+10 | 0.142400E+10 | 0.177207E+10 | 0.00 | 0.00 |
April | 0.521364E+10 | 0.259098E+10 | 0.395433E+10 | 0.198317E+10 | 0.197115E+10 | 0.00 | 0.00 |
May | 0.488544E+10 | 0.242666E+10 | 0.385615E+10 | 0.160926E+10 | 0.224689E+10 | 0.00 | 0.00 |
June | 0.505908E+10 | 0.186972E+10 | 0.370852E+10 | 0.160906E+10 | 0.209946E+10 | 0.00 | 0.00 |
July | 0.639891E+10 | 0.170215E+10 | 0.434210E+10 | 0.215771E+10 | 0.218439E+10 | 0.00 | 0.00 |
August | 0.640921E+10 | 0.171466E+10 | 0.428818E+10 | 0.227774E+10 | 0.201044E+10 | 0.00 | 0.00 |
September | 0.423679E+10 | 0.201974E+10 | 0.302142E+10 | 0.138453E+10 | 0.163689E+10 | 0.00 | 0.00 |
October | 0.393006E+10 | 0.232224E+10 | 0.276366E+10 | 0.142045E+10 | 0.134321E+10 | 0.00 | 0.00 |
November | 0.282142E+10 | 0.319596E+10 | 0.243813E+10 | 0.123867E+10 | 0.119946E+10 | 0.00 | 0.00 |
December | 0.274879E+10 | 0.363574E+10 | 0.240346E+10 | 0.133539E+10 | 0.106807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.507811E+11 | 0.314453E+11 | 0.388427E+11 | 0.188626E+11 | 0.199801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256867E+10 | 0.170215E+10 | 0.237652E+10 | 0.108870E+10 | 0.106807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.640921E+10 | 0.363574E+10 | 0.434210E+10 | 0.227774E+10 | 0.224689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131978E+11 | 0.543707E+10 | 0.915332E+10 | 0.671438E+10 | 0.243894E+10 | 0.00 | 0.00 |
February | 0.879888E+10 | 0.452994E+10 | 0.649782E+10 | 0.400232E+10 | 0.249551E+10 | 0.00 | 0.00 |
March | 0.761655E+10 | 0.523654E+10 | 0.573531E+10 | 0.277042E+10 | 0.296488E+10 | 0.00 | 0.00 |
April | 0.658875E+10 | 0.420789E+10 | 0.463741E+10 | 0.176829E+10 | 0.286912E+10 | 0.00 | 0.00 |
May | 0.391714E+10 | 0.384546E+10 | 0.341227E+10 | 0.419926E+09 | 0.299234E+10 | 0.00 | 0.00 |
June | 0.332583E+10 | 0.293304E+10 | 0.289690E+10 | 0.174904E+09 | 0.272200E+10 | 0.00 | 0.00 |
July | 0.426616E+10 | 0.266074E+10 | 0.317090E+10 | 0.356953E+09 | 0.281395E+10 | 0.00 | 0.00 |
August | 0.636982E+10 | 0.277424E+10 | 0.407366E+10 | 0.128496E+10 | 0.278870E+10 | 0.00 | 0.00 |
September | 0.863190E+10 | 0.318112E+10 | 0.548564E+10 | 0.277976E+10 | 0.270588E+10 | 0.00 | 0.00 |
October | 0.113368E+11 | 0.361159E+10 | 0.720900E+10 | 0.481942E+10 | 0.238958E+10 | 0.00 | 0.00 |
November | 0.121885E+11 | 0.486814E+10 | 0.847917E+10 | 0.598616E+10 | 0.249301E+10 | 0.00 | 0.00 |
December | 0.141467E+11 | 0.552889E+10 | 0.977867E+10 | 0.744284E+10 | 0.233583E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100385E+12 | 0.488147E+11 | 0.705301E+11 | 0.385203E+11 | 0.320097E+11 | 0.00 | 0.00 |
Minimum of Months | 0.332583E+10 | 0.266074E+10 | 0.289690E+10 | 0.174904E+09 | 0.233583E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141467E+11 | 0.552889E+10 | 0.977867E+10 | 0.744284E+10 | 0.299234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.280803E+10 | 0.408991E+10 | 0.237406E+10 | 0.119737E+10 | 0.117669E+10 | 0.00 | 0.00 |
February | 0.287619E+10 | 0.349074E+10 | 0.255817E+10 | 0.118097E+10 | 0.137720E+10 | 0.00 | 0.00 |
March | 0.369778E+10 | 0.395318E+10 | 0.324653E+10 | 0.143632E+10 | 0.181021E+10 | 0.00 | 0.00 |
April | 0.568466E+10 | 0.317913E+10 | 0.433115E+10 | 0.225522E+10 | 0.207593E+10 | 0.00 | 0.00 |
May | 0.569469E+10 | 0.274094E+10 | 0.439637E+10 | 0.203068E+10 | 0.236569E+10 | 0.00 | 0.00 |
June | 0.617850E+10 | 0.217370E+10 | 0.450723E+10 | 0.225353E+10 | 0.225370E+10 | 0.00 | 0.00 |
July | 0.711745E+10 | 0.205786E+10 | 0.493030E+10 | 0.263816E+10 | 0.229214E+10 | 0.00 | 0.00 |
August | 0.675098E+10 | 0.218105E+10 | 0.462559E+10 | 0.250688E+10 | 0.211871E+10 | 0.00 | 0.00 |
September | 0.546454E+10 | 0.227975E+10 | 0.383260E+10 | 0.205077E+10 | 0.178183E+10 | 0.00 | 0.00 |
October | 0.434350E+10 | 0.272735E+10 | 0.302751E+10 | 0.165289E+10 | 0.137462E+10 | 0.00 | 0.00 |
November | 0.319463E+10 | 0.379716E+10 | 0.264653E+10 | 0.138432E+10 | 0.126221E+10 | 0.00 | 0.00 |
December | 0.284188E+10 | 0.444883E+10 | 0.241525E+10 | 0.129543E+10 | 0.111983E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.566528E+11 | 0.371196E+11 | 0.428913E+11 | 0.218825E+11 | 0.210088E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280803E+10 | 0.205786E+10 | 0.237406E+10 | 0.118097E+10 | 0.111983E+10 | 0.00 | 0.00 |
Maximum of Months | 0.711745E+10 | 0.444883E+10 | 0.493030E+10 | 0.263816E+10 | 0.236569E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.835617E+09 | 0.529168E+10 | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.00 | 0.00 |
February | 0.898586E+09 | 0.435856E+10 | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.00 | 0.00 |
March | 0.145754E+10 | 0.493078E+10 | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.00 | 0.00 |
April | 0.200646E+10 | 0.375016E+10 | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.00 | 0.00 |
May | 0.262770E+10 | 0.340449E+10 | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.00 | 0.00 |
June | 0.326285E+10 | 0.258923E+10 | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.00 | 0.00 |
July | 0.356070E+10 | 0.237731E+10 | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.00 | 0.00 |
August | 0.286090E+10 | 0.249223E+10 | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.00 | 0.00 |
September | 0.214119E+10 | 0.290850E+10 | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.00 | 0.00 |
October | 0.191290E+10 | 0.337019E+10 | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.00 | 0.00 |
November | 0.939419E+09 | 0.468131E+10 | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.00 | 0.00 |
December | 0.755041E+09 | 0.532492E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.232589E+11 | 0.454794E+11 | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.755041E+09 | 0.237731E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Maximum of Months | 0.356070E+10 | 0.532492E+10 | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289567E+10 | 0.342122E+10 | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.00 | 0.00 |
February | 0.258118E+10 | 0.282616E+10 | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.00 | 0.00 |
March | 0.364433E+10 | 0.318982E+10 | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.00 | 0.00 |
April | 0.518246E+10 | 0.250760E+10 | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.00 | 0.00 |
May | 0.483812E+10 | 0.236847E+10 | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.00 | 0.00 |
June | 0.501069E+10 | 0.182756E+10 | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.00 | 0.00 |
July | 0.633665E+10 | 0.169994E+10 | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.00 | 0.00 |
August | 0.634206E+10 | 0.173830E+10 | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.00 | 0.00 |
September | 0.421113E+10 | 0.194840E+10 | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.00 | 0.00 |
October | 0.391909E+10 | 0.222088E+10 | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.00 | 0.00 |
November | 0.283603E+10 | 0.303187E+10 | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.00 | 0.00 |
December | 0.278797E+10 | 0.342394E+10 | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505854E+11 | 0.302041E+11 | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258118E+10 | 0.169994E+10 | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.634206E+10 | 0.342394E+10 | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131132E+11 | 0.536760E+10 | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.00 | 0.00 |
February | 0.872688E+10 | 0.441082E+10 | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.00 | 0.00 |
March | 0.758700E+10 | 0.505254E+10 | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.00 | 0.00 |
April | 0.658799E+10 | 0.402689E+10 | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.00 | 0.00 |
May | 0.390762E+10 | 0.374073E+10 | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.00 | 0.00 |
June | 0.335061E+10 | 0.280758E+10 | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.00 | 0.00 |
July | 0.430376E+10 | 0.256297E+10 | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.00 | 0.00 |
August | 0.637260E+10 | 0.271477E+10 | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.00 | 0.00 |
September | 0.857351E+10 | 0.311508E+10 | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.00 | 0.00 |
October | 0.112671E+11 | 0.352981E+10 | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.00 | 0.00 |
November | 0.121084E+11 | 0.474979E+10 | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.00 | 0.00 |
December | 0.140734E+11 | 0.537695E+10 | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.999720E+11 | 0.474555E+11 | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335061E+10 | 0.256297E+10 | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.00 | 0.00 |
Maximum of Months | 0.140734E+11 | 0.537695E+10 | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.288949E+10 | 0.367553E+10 | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.00 | 0.00 |
February | 0.295819E+10 | 0.305066E+10 | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.00 | 0.00 |
March | 0.381145E+10 | 0.343276E+10 | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.00 | 0.00 |
April | 0.580043E+10 | 0.276259E+10 | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.00 | 0.00 |
May | 0.570582E+10 | 0.256911E+10 | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.00 | 0.00 |
June | 0.621489E+10 | 0.196359E+10 | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.00 | 0.00 |
July | 0.719148E+10 | 0.184163E+10 | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.00 | 0.00 |
August | 0.684556E+10 | 0.191419E+10 | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.00 | 0.00 |
September | 0.547791E+10 | 0.210988E+10 | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.00 | 0.00 |
October | 0.441882E+10 | 0.242747E+10 | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.00 | 0.00 |
November | 0.330605E+10 | 0.327383E+10 | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.00 | 0.00 |
December | 0.299035E+10 | 0.373632E+10 | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.576104E+11 | 0.327576E+11 | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288949E+10 | 0.184163E+10 | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.719148E+10 | 0.373632E+10 | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.981370E+09 | 0.477315E+10 | 0.138701E+10 | 0.00 | 0.138701E+10 | 0.00 | 0.00 |
February | 0.102670E+10 | 0.393623E+10 | 0.157257E+10 | 0.00 | 0.157257E+10 | 0.00 | 0.00 |
March | 0.157908E+10 | 0.456698E+10 | 0.213354E+10 | 0.00 | 0.213354E+10 | 0.00 | 0.00 |
April | 0.205737E+10 | 0.355553E+10 | 0.237879E+10 | 9155607.65 | 0.236964E+10 | 0.00 | 0.00 |
May | 0.269496E+10 | 0.324606E+10 | 0.295383E+10 | 0.137547E+09 | 0.281629E+10 | 0.00 | 0.00 |
June | 0.325182E+10 | 0.251407E+10 | 0.304593E+10 | 0.297791E+09 | 0.274814E+10 | 0.00 | 0.00 |
July | 0.351678E+10 | 0.233436E+10 | 0.298015E+10 | 0.249786E+09 | 0.273036E+10 | 0.00 | 0.00 |
August | 0.283346E+10 | 0.243758E+10 | 0.247491E+10 | 49557704.06 | 0.242536E+10 | 0.00 | 0.00 |
September | 0.215599E+10 | 0.278579E+10 | 0.202719E+10 | 317739.42 | 0.202687E+10 | 0.00 | 0.00 |
October | 0.195980E+10 | 0.318198E+10 | 0.166163E+10 | 0.00 | 0.166163E+10 | 0.00 | 0.00 |
November | 0.106167E+10 | 0.427923E+10 | 0.145596E+10 | 0.00 | 0.145596E+10 | 0.00 | 0.00 |
December | 0.901949E+09 | 0.480503E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.240209E+11 | 0.424160E+11 | 0.253627E+11 | 0.744154E+09 | 0.246185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.901949E+09 | 0.233436E+10 | 0.129118E+10 | 0.00 | 0.129118E+10 | 0.00 | 0.00 |
Maximum of Months | 0.351678E+10 | 0.480503E+10 | 0.304593E+10 | 0.297791E+09 | 0.281629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302000E+10 | 0.312072E+10 | 0.249421E+10 | 0.133396E+10 | 0.116025E+10 | 0.00 | 0.00 |
February | 0.268177E+10 | 0.257875E+10 | 0.237651E+10 | 0.108870E+10 | 0.128781E+10 | 0.00 | 0.00 |
March | 0.373587E+10 | 0.298350E+10 | 0.319606E+10 | 0.142399E+10 | 0.177207E+10 | 0.00 | 0.00 |
April | 0.521883E+10 | 0.240225E+10 | 0.395431E+10 | 0.198317E+10 | 0.197114E+10 | 0.00 | 0.00 |
May | 0.487925E+10 | 0.227526E+10 | 0.385613E+10 | 0.160925E+10 | 0.224688E+10 | 0.00 | 0.00 |
June | 0.501454E+10 | 0.178246E+10 | 0.370850E+10 | 0.160905E+10 | 0.209945E+10 | 0.00 | 0.00 |
July | 0.631995E+10 | 0.167661E+10 | 0.434208E+10 | 0.215770E+10 | 0.218439E+10 | 0.00 | 0.00 |
August | 0.633111E+10 | 0.170828E+10 | 0.428816E+10 | 0.227773E+10 | 0.201043E+10 | 0.00 | 0.00 |
September | 0.422708E+10 | 0.187649E+10 | 0.302141E+10 | 0.138452E+10 | 0.163688E+10 | 0.00 | 0.00 |
October | 0.395680E+10 | 0.211738E+10 | 0.276365E+10 | 0.142044E+10 | 0.134320E+10 | 0.00 | 0.00 |
November | 0.292966E+10 | 0.281127E+10 | 0.243812E+10 | 0.123867E+10 | 0.119945E+10 | 0.00 | 0.00 |
December | 0.291250E+10 | 0.313251E+10 | 0.240345E+10 | 0.133538E+10 | 0.106807E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.512274E+11 | 0.284655E+11 | 0.388426E+11 | 0.188626E+11 | 0.199800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268177E+10 | 0.167661E+10 | 0.237651E+10 | 0.108870E+10 | 0.106807E+10 | 0.00 | 0.00 |
Maximum of Months | 0.633111E+10 | 0.313251E+10 | 0.434208E+10 | 0.227773E+10 | 0.224688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132428E+11 | 0.497528E+10 | 0.915328E+10 | 0.671435E+10 | 0.243893E+10 | 0.00 | 0.00 |
February | 0.882420E+10 | 0.406573E+10 | 0.649780E+10 | 0.400230E+10 | 0.249550E+10 | 0.00 | 0.00 |
March | 0.767344E+10 | 0.473562E+10 | 0.573529E+10 | 0.277041E+10 | 0.296487E+10 | 0.00 | 0.00 |
April | 0.661011E+10 | 0.384798E+10 | 0.463739E+10 | 0.176828E+10 | 0.286911E+10 | 0.00 | 0.00 |
May | 0.394535E+10 | 0.356917E+10 | 0.341225E+10 | 0.419925E+09 | 0.299233E+10 | 0.00 | 0.00 |
June | 0.333968E+10 | 0.272835E+10 | 0.289689E+10 | 0.174904E+09 | 0.272199E+10 | 0.00 | 0.00 |
July | 0.426383E+10 | 0.252267E+10 | 0.317089E+10 | 0.356952E+09 | 0.281394E+10 | 0.00 | 0.00 |
August | 0.633250E+10 | 0.266439E+10 | 0.407364E+10 | 0.128495E+10 | 0.278869E+10 | 0.00 | 0.00 |
September | 0.855951E+10 | 0.300954E+10 | 0.548562E+10 | 0.277975E+10 | 0.270586E+10 | 0.00 | 0.00 |
October | 0.112821E+11 | 0.338758E+10 | 0.720897E+10 | 0.481940E+10 | 0.238957E+10 | 0.00 | 0.00 |
November | 0.121918E+11 | 0.446030E+10 | 0.847914E+10 | 0.598614E+10 | 0.249300E+10 | 0.00 | 0.00 |
December | 0.141976E+11 | 0.501319E+10 | 0.977864E+10 | 0.744282E+10 | 0.233582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100463E+12 | 0.449798E+11 | 0.705298E+11 | 0.385202E+11 | 0.320096E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333968E+10 | 0.252267E+10 | 0.289689E+10 | 0.174904E+09 | 0.233582E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141976E+11 | 0.501319E+10 | 0.977864E+10 | 0.744282E+10 | 0.299233E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295455E+10 | 0.340058E+10 | 0.237405E+10 | 0.119736E+10 | 0.117669E+10 | 0.00 | 0.00 |
February | 0.301171E+10 | 0.282317E+10 | 0.255816E+10 | 0.118097E+10 | 0.137720E+10 | 0.00 | 0.00 |
March | 0.385356E+10 | 0.323173E+10 | 0.324652E+10 | 0.143631E+10 | 0.181021E+10 | 0.00 | 0.00 |
April | 0.579482E+10 | 0.265494E+10 | 0.433113E+10 | 0.225521E+10 | 0.207592E+10 | 0.00 | 0.00 |
May | 0.570124E+10 | 0.247215E+10 | 0.439635E+10 | 0.203067E+10 | 0.236568E+10 | 0.00 | 0.00 |
June | 0.618048E+10 | 0.191512E+10 | 0.450721E+10 | 0.225352E+10 | 0.225369E+10 | 0.00 | 0.00 |
July | 0.714190E+10 | 0.181182E+10 | 0.493028E+10 | 0.263815E+10 | 0.229213E+10 | 0.00 | 0.00 |
August | 0.680180E+10 | 0.188094E+10 | 0.462557E+10 | 0.250687E+10 | 0.211870E+10 | 0.00 | 0.00 |
September | 0.545832E+10 | 0.204516E+10 | 0.383259E+10 | 0.205076E+10 | 0.178183E+10 | 0.00 | 0.00 |
October | 0.442200E+10 | 0.232742E+10 | 0.302750E+10 | 0.165289E+10 | 0.137461E+10 | 0.00 | 0.00 |
November | 0.335182E+10 | 0.306159E+10 | 0.264652E+10 | 0.138432E+10 | 0.126220E+10 | 0.00 | 0.00 |
December | 0.305481E+10 | 0.346136E+10 | 0.241524E+10 | 0.129542E+10 | 0.111982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.577270E+11 | 0.310860E+11 | 0.428911E+11 | 0.218825E+11 | 0.210087E+11 | 0.00 | 0.00 |
Minimum of Months | 0.295455E+10 | 0.181182E+10 | 0.237405E+10 | 0.118097E+10 | 0.111982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.714190E+10 | 0.346136E+10 | 0.493028E+10 | 0.263815E+10 | 0.236568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.343126E+11 | -0.338717E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440911250.9 | 60.05 | 0.00 | 0.00 |
February | 0.312144E+11 | -0.308141E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -400283116.5 | 60.05 | 0.00 | 0.00 |
March | 0.363075E+11 | -0.358631E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444426058.0 | 60.05 | 0.00 | 0.00 |
April | 0.322838E+11 | -0.318553E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428571723.2 | 60.05 | 0.00 | 0.00 |
May | 0.336120E+11 | -0.331681E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443937692.9 | 60.05 | 0.00 | 0.00 |
June | 0.325779E+11 | -0.321480E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429864110.1 | 60.05 | 0.00 | 0.00 |
July | 0.305643E+11 | -0.301227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441519996.8 | 60.05 | 0.00 | 0.00 |
August | 0.333763E+11 | -0.329331E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443196620.8 | 60.05 | 0.00 | 0.00 |
September | 0.306554E+11 | -0.302295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -425918124.0 | 60.05 | 0.00 | 0.00 |
October | 0.323137E+11 | -0.318763E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -437400941.5 | 60.05 | 0.00 | 0.00 |
November | 0.325060E+11 | -0.320795E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -426561154.7 | 60.05 | 0.00 | 0.00 |
December | 0.330753E+11 | -0.326345E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440826651.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.392799E+12 | -0.387596E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.520342E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.305643E+11 | -0.358631E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -444426058.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.363075E+11 | -0.301227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -400283116.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7834.21 | 37.54 | 285.17 | 281.00 | 1692.61 | 26.81 | 208.83 | 265.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 6954.72 | 35.76 | 275.67 | 274.67 | 1248.96 | 24.79 | 216.50 | 252.83 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2064.61 | 20.44 | 98.67 | 315.50 | 997.95 | 21.27 | 198.83 | 286.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1359.72 | 19.63 | 36.83 | 332.67 | 823.48 | 20.98 | 159.00 | 297.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1170.42 | 19.42 | 0.67 | 365.67 | 671.75 | 20.77 | 160.00 | 322.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1041.19 | 19.06 | 0.00 | 358.00 | 616.90 | 20.44 | 112.83 | 310.50 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 1050.72 | 19.08 | 1.00 | 368.00 | 642.36 | 20.48 | 143.83 | 331.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1173.52 | 19.23 | 8.83 | 354.83 | 726.09 | 20.59 | 153.33 | 317.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:49 | 1704.23 | 20.26 | 53.83 | 309.50 | 947.22 | 21.03 | 152.83 | 277.83 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3856.03 | 27.17 | 157.00 | 304.50 | 1165.20 | 21.76 | 138.67 | 276.17 |
November | 300.00 | 0.50 | 0.48 | 01-NOV-06:49 | 7582.60 | 37.31 | 294.83 | 279.50 | 1521.54 | 26.38 | 219.83 | 270.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7708.79 | 38.42 | 293.33 | 283.00 | 2157.92 | 29.56 | 209.33 | 271.50 |
Annual Sum or Average | 4065.67 | 0.50 | 3305.90 | 25.21 | 1505.83 | 3826.83 | 1052.24 | 22.61 | 2073.83 | 3479.67 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 1041.19 | 19.06 | 0.00 | 274.67 | 616.90 | 20.44 | 112.83 | 252.83 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7834.21 | 38.42 | 294.83 | 368.00 | 2157.92 | 29.56 | 219.83 | 331.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:19 | 1740.26 | 23.79 | 90.00 | 266.33 | 882.61 | 23.58 | 112.00 | 229.00 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1902.41 | 23.87 | 87.17 | 268.33 | 993.02 | 23.92 | 119.00 | 224.00 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2318.77 | 23.78 | 107.17 | 317.50 | 1263.35 | 23.98 | 141.67 | 279.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2350.46 | 23.18 | 93.83 | 339.00 | 1242.06 | 23.53 | 104.17 | 308.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2266.06 | 22.53 | 99.67 | 377.83 | 1233.25 | 23.12 | 126.00 | 333.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2258.88 | 21.75 | 89.33 | 369.33 | 1197.37 | 22.41 | 90.00 | 326.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:19 | 2487.22 | 22.18 | 99.67 | 378.17 | 1309.51 | 22.70 | 95.33 | 342.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:49 | 2500.57 | 22.99 | 103.33 | 363.17 | 1273.62 | 23.23 | 91.67 | 329.17 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:40 | 2610.78 | 23.28 | 98.83 | 312.67 | 989.90 | 22.25 | 86.50 | 277.00 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2360.91 | 23.19 | 89.17 | 286.33 | 971.28 | 22.12 | 89.50 | 241.33 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1983.63 | 24.04 | 98.50 | 264.83 | 1071.05 | 23.98 | 125.83 | 233.67 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1739.47 | 24.25 | 97.83 | 267.33 | 904.18 | 23.92 | 108.00 | 226.50 |
Annual Sum or Average | 4065.67 | 0.50 | 2234.51 | 23.16 | 1154.50 | 3810.83 | 1128.12 | 23.20 | 1289.67 | 3350.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1739.47 | 21.75 | 87.17 | 264.83 | 882.61 | 22.12 | 86.50 | 224.00 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2610.78 | 24.25 | 107.17 | 378.17 | 1309.51 | 23.98 | 141.67 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 553.44 | 16.92 | 0.00 | 237.50 | 357.08 | 18.68 | 0.00 | 163.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:30 | 659.33 | 17.67 | 0.00 | 249.00 | 403.28 | 19.16 | 0.00 | 178.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:00 | 770.98 | 17.99 | 0.00 | 306.50 | 459.53 | 19.31 | 6.50 | 251.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 860.57 | 19.15 | 0.00 | 336.33 | 545.08 | 20.53 | 63.83 | 297.33 |
May | 393.83 | 0.49 | 0.48 | 01-MAY-06:30 | 1067.79 | 19.84 | 27.00 | 382.50 | 619.37 | 21.15 | 156.00 | 352.17 |
June | 381.00 | 0.49 | 0.48 | 01-JUN-06:30 | 1128.29 | 21.52 | 83.17 | 375.00 | 668.82 | 22.71 | 181.00 | 341.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1060.36 | 21.41 | 84.83 | 385.00 | 622.39 | 21.20 | 174.33 | 360.67 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 872.98 | 19.23 | 7.17 | 364.33 | 561.51 | 20.58 | 85.17 | 337.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 769.32 | 18.47 | 0.00 | 305.50 | 490.54 | 19.91 | 8.50 | 259.17 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 589.17 | 17.10 | 0.00 | 263.50 | 384.16 | 18.68 | 0.50 | 184.33 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:40 | 561.97 | 16.50 | 0.00 | 241.00 | 359.57 | 18.15 | 0.00 | 171.00 |
December | 297.00 | 0.54 | 0.48 | 01-DEC-08:20 | 504.20 | 16.19 | 0.00 | 230.50 | 331.02 | 18.02 | 0.00 | 144.00 |
Annual Sum or Average | 4065.67 | 0.51 | 808.33 | 18.70 | 202.17 | 3676.67 | 497.33 | 19.99 | 675.83 | 3040.67 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 504.20 | 16.19 | 0.00 | 230.50 | 331.02 | 18.02 | 0.00 | 144.00 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 1128.29 | 21.52 | 84.83 | 385.00 | 668.82 | 22.71 | 181.00 | 360.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:39 | 2255.51 | 24.57 | 107.00 | 254.00 | 847.70 | 22.81 | 118.83 | 215.83 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:30 | 2076.54 | 23.92 | 90.00 | 256.83 | 1106.99 | 24.08 | 134.00 | 217.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:00 | 2315.05 | 23.32 | 101.17 | 311.00 | 1243.51 | 23.54 | 143.33 | 270.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 3186.72 | 22.08 | 82.33 | 332.83 | 1200.26 | 20.07 | 77.33 | 300.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2991.13 | 20.10 | 52.83 | 368.83 | 1210.03 | 20.25 | 97.17 | 330.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2536.68 | 17.89 | 0.00 | 362.17 | 1370.32 | 20.26 | 91.17 | 327.00 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:19 | 2675.91 | 17.95 | 5.67 | 372.17 | 1415.82 | 20.18 | 89.17 | 344.83 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:30 | 3304.97 | 21.76 | 88.33 | 356.17 | 1338.49 | 20.25 | 81.33 | 327.17 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:19 | 2946.08 | 24.52 | 106.67 | 306.67 | 1511.97 | 24.33 | 115.00 | 273.50 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2821.19 | 25.26 | 114.33 | 288.17 | 1117.57 | 23.53 | 105.33 | 244.17 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-07:49 | 2203.59 | 24.41 | 106.50 | 257.17 | 1199.47 | 24.34 | 135.67 | 218.67 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:20 | 2002.04 | 24.40 | 110.17 | 249.00 | 1101.35 | 24.30 | 121.83 | 204.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2645.64 | 22.23 | 965.00 | 3715.00 | 1235.74 | 22.12 | 1310.17 | 3274.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 2002.04 | 17.89 | 0.00 | 249.00 | 847.70 | 20.07 | 77.33 | 204.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3304.97 | 25.26 | 114.33 | 372.17 | 1511.97 | 24.34 | 143.33 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7903.14 | 37.01 | 284.83 | 281.00 | 1804.16 | 22.57 | 97.17 | 266.17 |
February | 279.67 | 0.49 | 0.48 | 01-FEB-07:19 | 6996.72 | 35.33 | 275.00 | 274.67 | 1338.60 | 20.76 | 61.00 | 254.67 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2099.74 | 14.21 | 11.17 | 315.83 | 1069.13 | 17.03 | 3.33 | 290.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1395.33 | 13.61 | 0.00 | 333.17 | 883.80 | 17.15 | 0.00 | 304.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1191.53 | 13.60 | 0.00 | 366.17 | 716.59 | 17.05 | 0.00 | 329.83 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1061.27 | 13.38 | 0.00 | 358.00 | 658.25 | 16.84 | 0.00 | 316.00 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:10 | 1073.76 | 13.53 | 0.00 | 368.83 | 686.43 | 17.03 | 0.00 | 335.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1204.37 | 13.51 | 0.00 | 355.00 | 778.76 | 17.01 | 0.00 | 323.83 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:49 | 1747.15 | 14.15 | 14.00 | 309.83 | 1018.93 | 16.90 | 0.17 | 282.67 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3916.32 | 23.17 | 141.67 | 304.67 | 1256.29 | 17.15 | 14.00 | 279.50 |
November | 300.00 | 0.50 | 0.48 | 01-NOV-06:49 | 7642.30 | 36.90 | 294.67 | 279.67 | 1624.68 | 22.18 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:10 | 7779.55 | 38.00 | 293.00 | 283.17 | 2272.76 | 25.99 | 142.83 | 272.83 |
Annual Sum or Average | 4065.67 | 0.50 | 3346.46 | 21.04 | 1314.33 | 3830.00 | 1123.83 | 18.71 | 411.17 | 3526.50 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 1061.27 | 13.38 | 0.00 | 274.67 | 658.25 | 16.84 | 0.00 | 254.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7903.14 | 38.00 | 294.67 | 368.83 | 2272.76 | 25.99 | 142.83 | 335.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:19 | 1773.54 | 21.07 | 85.00 | 266.50 | 926.85 | 21.54 | 55.00 | 234.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1908.04 | 19.70 | 70.83 | 268.50 | 1040.46 | 21.79 | 54.50 | 229.67 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2362.09 | 21.00 | 106.50 | 318.00 | 1315.39 | 21.84 | 77.67 | 284.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2392.29 | 19.99 | 93.67 | 339.83 | 1304.42 | 20.99 | 65.17 | 311.00 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2296.57 | 19.34 | 99.33 | 378.83 | 1289.96 | 20.62 | 70.17 | 338.33 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2295.22 | 18.50 | 88.83 | 369.83 | 1254.22 | 19.82 | 60.67 | 333.33 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:19 | 2523.26 | 19.00 | 99.67 | 378.83 | 1372.91 | 20.12 | 68.67 | 348.33 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:40 | 2534.79 | 19.85 | 103.33 | 363.17 | 1337.25 | 20.68 | 69.67 | 334.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:40 | 2657.11 | 20.47 | 98.83 | 313.50 | 1044.26 | 19.69 | 43.67 | 281.50 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2403.89 | 20.34 | 88.83 | 287.00 | 1020.31 | 19.67 | 42.50 | 246.83 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 2011.64 | 21.37 | 95.17 | 265.50 | 1115.31 | 22.13 | 68.33 | 238.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1747.67 | 20.72 | 86.17 | 266.67 | 947.66 | 22.12 | 64.33 | 232.33 |
Annual Sum or Average | 4065.67 | 0.50 | 2267.40 | 20.03 | 1116.17 | 3816.17 | 1182.12 | 20.86 | 740.33 | 3411.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1747.67 | 18.50 | 70.83 | 265.50 | 926.85 | 19.67 | 42.50 | 229.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2657.11 | 21.37 | 106.50 | 378.83 | 1372.91 | 22.13 | 77.67 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 562.61 | 11.18 | 0.00 | 238.17 | 380.37 | 14.99 | 0.00 | 178.83 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:30 | 670.49 | 12.14 | 0.00 | 250.00 | 429.47 | 15.69 | 0.00 | 191.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 784.95 | 12.60 | 0.00 | 306.83 | 489.53 | 15.97 | 0.00 | 260.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 880.11 | 13.79 | 0.00 | 336.33 | 582.18 | 17.34 | 0.00 | 304.33 |
May | 393.83 | 0.49 | 0.48 | 01-MAY-06:30 | 1088.32 | 14.12 | 0.00 | 382.83 | 659.72 | 17.67 | 0.00 | 355.83 |
June | 381.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1151.37 | 16.32 | 42.50 | 375.67 | 711.92 | 19.54 | 40.83 | 347.17 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1085.28 | 16.41 | 45.17 | 385.33 | 665.28 | 17.86 | 0.00 | 363.17 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:00 | 903.29 | 13.91 | 0.00 | 366.00 | 599.55 | 17.49 | 0.00 | 341.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 785.80 | 13.12 | 0.00 | 305.67 | 523.62 | 16.65 | 0.00 | 265.67 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 601.91 | 11.58 | 0.00 | 265.33 | 410.11 | 15.26 | 0.00 | 200.17 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:30 | 571.72 | 11.05 | 0.00 | 242.50 | 383.10 | 14.64 | 0.00 | 185.50 |
December | 297.00 | 0.54 | 0.48 | 01-DEC-08:09 | 512.27 | 10.52 | 0.00 | 231.33 | 352.60 | 14.31 | 0.00 | 160.17 |
Annual Sum or Average | 4065.67 | 0.51 | 825.79 | 13.28 | 87.67 | 3686.00 | 530.37 | 16.62 | 40.83 | 3153.83 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 512.27 | 10.52 | 0.00 | 231.33 | 352.60 | 14.31 | 0.00 | 160.17 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 1151.37 | 16.41 | 45.17 | 385.33 | 711.92 | 19.54 | 40.83 | 363.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-08:39 | 2287.66 | 22.15 | 105.33 | 255.00 | 892.02 | 20.70 | 45.33 | 221.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:30 | 2115.91 | 21.17 | 85.17 | 257.83 | 1156.95 | 21.96 | 60.00 | 222.83 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 2363.75 | 20.51 | 100.83 | 311.50 | 1296.79 | 21.32 | 71.50 | 275.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:10 | 3227.04 | 18.73 | 82.33 | 333.33 | 1266.85 | 16.74 | 0.00 | 304.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:00 | 3021.86 | 16.17 | 52.50 | 369.50 | 1273.28 | 16.87 | 0.00 | 336.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:49 | 2579.83 | 13.21 | 0.00 | 364.00 | 1435.04 | 16.79 | 0.00 | 330.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:19 | 2715.48 | 13.35 | 5.67 | 372.50 | 1484.59 | 16.71 | 0.00 | 348.83 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:30 | 3336.07 | 18.40 | 88.17 | 357.33 | 1405.95 | 16.95 | 7.00 | 330.83 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:10 | 2994.72 | 21.43 | 104.83 | 307.50 | 1577.89 | 21.99 | 73.67 | 277.50 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 2851.12 | 21.90 | 107.83 | 289.00 | 1172.20 | 21.22 | 58.50 | 250.33 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-07:40 | 2238.33 | 21.98 | 104.33 | 258.33 | 1245.91 | 22.49 | 75.00 | 225.50 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-08:09 | 2032.80 | 22.00 | 104.67 | 251.00 | 1145.04 | 22.54 | 74.67 | 211.17 |
Annual Sum or Average | 4065.67 | 0.51 | 2683.19 | 18.88 | 941.67 | 3726.83 | 1294.19 | 19.40 | 465.67 | 3334.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 2032.80 | 13.21 | 0.00 | 251.00 | 892.02 | 16.71 | 0.00 | 211.17 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 3336.07 | 22.15 | 107.83 | 372.50 | 1577.89 | 22.54 | 75.00 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7904.48 | 37.00 | 284.83 | 281.00 | 1806.00 | 22.56 | 97.17 | 266.17 |
February | 279.67 | 0.49 | 0.48 | 01-FEB-07:19 | 6999.06 | 35.32 | 275.00 | 274.67 | 1340.45 | 20.75 | 61.00 | 254.83 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2102.26 | 14.18 | 11.17 | 316.00 | 1070.72 | 17.02 | 3.33 | 290.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1396.94 | 13.58 | 0.00 | 333.17 | 884.89 | 17.13 | 0.00 | 304.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1193.09 | 13.57 | 0.00 | 366.17 | 717.60 | 17.03 | 0.00 | 330.00 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1062.50 | 13.35 | 0.00 | 358.17 | 659.10 | 16.83 | 0.00 | 316.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:10 | 1074.84 | 13.50 | 0.00 | 368.83 | 687.25 | 17.01 | 0.00 | 335.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1205.61 | 13.48 | 0.00 | 355.00 | 779.67 | 17.00 | 0.00 | 324.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:49 | 1749.07 | 14.12 | 14.00 | 309.83 | 1020.18 | 16.88 | 0.17 | 283.00 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3918.21 | 23.15 | 141.67 | 304.67 | 1257.64 | 17.13 | 14.00 | 279.50 |
November | 300.00 | 0.50 | 0.48 | 01-NOV-06:49 | 7643.96 | 36.90 | 294.67 | 279.67 | 1626.48 | 22.17 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:10 | 7780.51 | 37.99 | 293.00 | 283.17 | 2274.50 | 25.98 | 142.83 | 272.83 |
Annual Sum or Average | 4065.67 | 0.50 | 3348.05 | 21.02 | 1314.33 | 3830.33 | 1125.13 | 18.70 | 411.17 | 3527.83 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 1062.50 | 13.35 | 0.00 | 274.67 | 659.10 | 16.83 | 0.00 | 254.83 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7904.48 | 37.99 | 294.67 | 368.83 | 2274.50 | 25.98 | 142.83 | 335.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:19 | 1774.21 | 21.04 | 85.00 | 266.50 | 927.70 | 21.53 | 55.00 | 234.50 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1909.11 | 19.67 | 70.83 | 268.50 | 1041.49 | 21.78 | 54.50 | 229.67 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2363.57 | 20.97 | 106.50 | 318.00 | 1316.59 | 21.83 | 77.67 | 284.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2393.52 | 19.96 | 93.67 | 339.83 | 1305.56 | 20.97 | 65.17 | 311.00 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2298.09 | 19.31 | 99.17 | 378.83 | 1291.20 | 20.60 | 70.17 | 338.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2296.56 | 18.47 | 88.83 | 369.83 | 1255.37 | 19.81 | 60.67 | 333.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:19 | 2524.43 | 18.97 | 99.67 | 378.83 | 1374.07 | 20.11 | 68.67 | 348.67 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:40 | 2535.80 | 19.82 | 103.33 | 363.50 | 1338.32 | 20.66 | 69.67 | 334.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-06:40 | 2658.19 | 20.44 | 98.83 | 313.50 | 1045.27 | 19.68 | 43.67 | 281.67 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2404.72 | 20.31 | 88.83 | 287.00 | 1021.15 | 19.66 | 42.50 | 247.00 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 2012.38 | 21.34 | 95.17 | 265.50 | 1116.16 | 22.12 | 68.33 | 238.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1748.18 | 20.70 | 86.17 | 266.83 | 948.37 | 22.11 | 64.33 | 232.33 |
Annual Sum or Average | 4065.67 | 0.50 | 2268.48 | 20.01 | 1116.00 | 3816.67 | 1183.15 | 20.84 | 740.33 | 3413.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1748.18 | 18.47 | 70.83 | 265.50 | 927.70 | 19.66 | 42.50 | 229.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2658.19 | 21.34 | 106.50 | 378.83 | 1374.07 | 22.12 | 77.67 | 348.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 562.93 | 11.14 | 0.00 | 238.50 | 380.78 | 14.97 | 0.00 | 178.83 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:30 | 671.07 | 12.11 | 0.00 | 250.00 | 430.00 | 15.67 | 0.00 | 191.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 785.76 | 12.57 | 0.00 | 306.83 | 490.18 | 15.96 | 0.00 | 260.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 880.79 | 13.76 | 0.00 | 336.33 | 582.83 | 17.32 | 0.00 | 304.50 |
May | 393.83 | 0.49 | 0.48 | 01-MAY-06:30 | 1089.44 | 14.09 | 0.00 | 382.83 | 660.59 | 17.66 | 0.00 | 356.00 |
June | 381.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1152.48 | 16.29 | 42.50 | 375.67 | 712.80 | 19.53 | 40.83 | 347.33 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1086.12 | 16.38 | 45.17 | 385.33 | 666.06 | 17.85 | 0.00 | 363.17 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:00 | 903.90 | 13.88 | 0.00 | 366.17 | 600.19 | 17.47 | 0.00 | 341.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 786.37 | 13.09 | 0.00 | 305.67 | 524.19 | 16.63 | 0.00 | 266.17 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 602.30 | 11.54 | 0.00 | 265.50 | 410.53 | 15.25 | 0.00 | 200.50 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:30 | 572.08 | 11.01 | 0.00 | 243.00 | 383.52 | 14.62 | 0.00 | 186.00 |
December | 297.00 | 0.54 | 0.48 | 01-DEC-08:09 | 512.51 | 10.49 | 0.00 | 231.33 | 352.96 | 14.29 | 0.00 | 160.50 |
Annual Sum or Average | 4065.67 | 0.51 | 826.45 | 13.25 | 87.67 | 3687.17 | 530.99 | 16.60 | 40.83 | 3156.33 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 512.51 | 10.49 | 0.00 | 231.33 | 352.96 | 14.29 | 0.00 | 160.50 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 1152.48 | 16.38 | 45.17 | 385.33 | 712.80 | 19.53 | 40.83 | 363.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-08:39 | 2288.37 | 22.13 | 105.33 | 255.00 | 892.93 | 20.68 | 45.33 | 221.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:30 | 2116.97 | 21.14 | 85.17 | 257.83 | 1158.06 | 21.95 | 60.00 | 223.00 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-07:49 | 2365.19 | 20.48 | 100.83 | 311.50 | 1298.06 | 21.31 | 71.50 | 275.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:10 | 3228.23 | 18.70 | 82.33 | 333.33 | 1268.09 | 16.72 | 0.00 | 304.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:00 | 3023.33 | 16.14 | 52.33 | 369.67 | 1274.57 | 16.86 | 0.00 | 336.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:49 | 2581.13 | 13.17 | 0.00 | 364.00 | 1436.35 | 16.77 | 0.00 | 330.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:19 | 2716.50 | 13.31 | 5.67 | 372.50 | 1485.84 | 16.69 | 0.00 | 348.83 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:30 | 3337.08 | 18.37 | 88.17 | 357.33 | 1407.12 | 16.93 | 7.00 | 331.00 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:10 | 2995.91 | 21.41 | 104.83 | 307.50 | 1579.15 | 21.98 | 73.67 | 277.50 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 2851.96 | 21.87 | 107.83 | 289.00 | 1173.10 | 21.20 | 58.50 | 250.33 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-07:40 | 2239.10 | 21.96 | 104.33 | 258.33 | 1246.87 | 22.48 | 75.00 | 225.50 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-08:09 | 2033.35 | 21.97 | 104.67 | 251.00 | 1145.86 | 22.53 | 74.67 | 211.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2684.25 | 18.85 | 941.50 | 3727.00 | 1295.33 | 19.38 | 465.67 | 3335.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 2033.35 | 13.17 | 0.00 | 251.00 | 892.93 | 16.69 | 0.00 | 211.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 3337.08 | 22.13 | 107.83 | 372.50 | 1579.15 | 22.53 | 75.00 | 348.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390002E+09 | 12609.72 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44854781.84 | 5180.31 | 09-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179524E+09 | 8924.83 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4912789.11 | 4125.01 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3745.70 | 1.74 | 25-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1820.10 | 0.74 | 08-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5743.12 | 1.71 | 08-JUL-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25135.80 | 1.87 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4187.39 | 1.63 | 13-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10165.76 | 1.77 | 05-OCT-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7070.81 | 1.64 | 21-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87869065.36 | 6744.04 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1820.10 | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390002E+09 | 12609.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686084E+10 | 139753.60 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163214E+10 | 75953.09 | 10-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543230E+10 | 101504.51 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140009E+09 | 60533.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36066364.41 | 60110.61 | 09-MAY-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14354281.94 | 17566.49 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202536E+09 | 37996.22 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.422137E+10 | 96523.39 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686084E+10 | 139753.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100037E+10 | 119739.10 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59830829.67 | 10213.78 | 06-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404477E+09 | 120562.16 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30815155.67 | 11872.14 | 01-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21253044.66 | 10002.32 | 24-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295785E+09 | 43169.22 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100037E+10 | 120562.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211764E+09 | 103146.02 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118313E+09 | 99403.94 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6453608.42 | 4831.98 | 01-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48233330.12 | 34835.48 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211764E+09 | 103146.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23939805.84 | 12019.22 | 03-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152495E+09 | 85084.64 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5526967.08 | 2846.55 | 01-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15341158.98 | 13145.22 | 13-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152495E+09 | 85084.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117715E+09 | 15230.71 | 03-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28742328.40 | 8199.58 | 30-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4438437.62 | 3840.25 | 13-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117715E+09 | 15230.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119434E+10 | 15765.89 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417995E+09 | 9833.70 | 09-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103136E+10 | 13428.90 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39748527.27 | 8820.11 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3538599.49 | 1704.97 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6062.74 | 1.58 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5259.11 | 1.60 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21601.41 | 1.74 | 18-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2871.95 | 0.71 | 15-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14424156.62 | 4287.58 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120526E+09 | 7213.60 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794071E+09 | 12571.16 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2871.95 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119434E+10 | 15765.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256558E+09 | 67167.81 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1408644.44 | 1582.89 | 27-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27870116.25 | 26996.03 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256558E+09 | 67167.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.834516E+09 | 12757.54 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385755E+09 | 12697.44 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449893E+09 | 12687.66 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52160771.84 | 12600.43 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6251675.46 | 9790.16 | 15-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29802922.09 | 10183.35 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269202E+09 | 12686.76 | 08-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545038E+09 | 12685.49 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.834516E+09 | 12757.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286672E+09 | 14115.68 | 03-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146945E+09 | 14109.97 | 10-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156521E+09 | 14099.08 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11728503.23 | 14095.20 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 431241.93 | 2108.47 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6692426.64 | 1100.88 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63347021.49 | 12552.67 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166856E+09 | 14106.95 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.839193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.286672E+09 | 14115.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242897E+09 | 17950.97 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135565E+09 | 18023.32 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250440E+09 | 17870.08 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31029584.66 | 17864.55 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17435925.98 | 9135.06 | 15-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 630994.48 | 381.18 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30974709.71 | 11859.71 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110810E+09 | 17864.67 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.250440E+09 | 18023.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242602E+09 | 14233.03 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73550941.59 | 12406.53 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106308E+09 | 13968.86 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10406440.87 | 8546.81 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1105717.66 | 452.38 | 13-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33175722.00 | 9072.19 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116861E+09 | 13371.34 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242602E+09 | 14233.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 372.84 | 0.99 | 02-JAN-10:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28896.91 | 92.90 | 11-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1063260.82 | 2900.71 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1569.27 | 0.48 | 28-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 492.77 | 0.71 | 24-MAY-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2112.72 | 0.50 | 09-JUN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30.98 | 0.36 | 21-SEP-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1657.67 | 0.70 | 26-OCT-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1117.05 | 1.00 | 02-NOV-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 624.44 | 1.06 | 26-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1100135.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1063260.82 | 2900.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.214056E+11 | 0.213595E+11 | 86455.28 | 18-JAN-14:10 | 86455.28 | 0.20 |
February | 0.00 | 0.00 | 0.120058E+11 | 0.119342E+11 | 80732.21 | 01-FEB-12:00 | 80732.21 | 0.16 |
March | 0.00 | 0.00 | 0.142555E+11 | 0.138114E+11 | 93730.48 | 23-MAR-14:00 | 78764.63 | 0.19 |
April | 0.00 | 0.00 | 0.317720E+11 | 0.317480E+11 | 105862.64 | 26-APR-13:05 | 103365.15 | 0.39 |
May | 0.00 | 0.00 | 0.280624E+11 | 0.279769E+11 | 76867.45 | 03-MAY-13:00 | 76867.45 | 0.43 |
June | 0.00 | 0.00 | 0.509381E+11 | 0.466190E+11 | 118679.78 | 29-JUN-13:00 | 78678.96 | 0.59 |
July | 0.00 | 0.00 | 0.929980E+11 | 0.693219E+11 | 163573.68 | 31-JUL-16:00 | 92193.85 | 0.73 |
August | 0.00 | 0.00 | 0.114054E+12 | 0.800233E+11 | 177760.91 | 07-AUG-10:40 | 104471.48 | 0.80 |
September | 0.00 | 0.00 | 0.579903E+11 | 0.488571E+11 | 132003.26 | 22-SEP-11:30 | 64237.27 | 0.54 |
October | 0.00 | 0.00 | 0.747789E+11 | 0.626031E+11 | 162565.11 | 03-OCT-13:20 | 96032.79 | 0.41 |
November | 0.00 | 0.00 | 0.249936E+11 | 0.245685E+11 | 92585.36 | 28-NOV-14:00 | 92585.36 | 0.23 |
December | 0.00 | 0.00 | 0.288812E+11 | 0.288014E+11 | 98164.13 | 05-DEC-15:00 | 98164.13 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.552136E+12 | 0.467624E+12 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 0.120058E+11 | 0.119342E+11 | 76867.45 | 64237.27 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.114054E+12 | 0.800233E+11 | 177760.91 | 104471.48 | 0.80 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.228955E+12 | 0.228366E+12 | 731976.94 | 18-JAN-13:05 | 731976.94 | 0.23 |
February | 0.00 | 0.00 | 0.130324E+12 | 0.129588E+12 | 668974.22 | 01-FEB-12:00 | 668974.22 | 0.19 |
March | 0.00 | 0.00 | 0.135732E+12 | 0.132019E+12 | 820041.97 | 23-MAR-14:05 | 659748.02 | 0.22 |
April | 0.00 | 0.00 | 0.225478E+12 | 0.225391E+12 | 849861.81 | 26-APR-14:05 | 849861.81 | 0.38 |
May | 0.00 | 0.00 | 0.232424E+12 | 0.231782E+12 | 676639.13 | 04-MAY-12:05 | 676639.13 | 0.43 |
June | 0.00 | 0.00 | 0.402723E+12 | 0.370860E+12 | 997000.23 | 29-JUN-13:00 | 668255.40 | 0.57 |
July | 0.00 | 0.00 | 0.692662E+12 | 0.526366E+12 | 1228992.02 | 28-JUL-12:30 | 738289.56 | 0.61 |
August | 0.00 | 0.00 | 0.817380E+12 | 0.592133E+12 | 1277590.15 | 07-AUG-10:30 | 764207.77 | 0.63 |
September | 0.00 | 0.00 | 0.482204E+12 | 0.409898E+12 | 1127309.67 | 30-SEP-05:02 | 1127309.67 | 0.54 |
October | 0.00 | 0.00 | 0.565784E+12 | 0.484908E+12 | 1304991.57 | 03-OCT-13:40 | 765682.59 | 0.39 |
November | 0.00 | 0.00 | 0.238333E+12 | 0.234981E+12 | 704401.14 | 28-NOV-14:00 | 704401.14 | 0.24 |
December | 0.00 | 0.00 | 0.258017E+12 | 0.257620E+12 | 757773.73 | 05-DEC-15:05 | 757773.73 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.441002E+13 | 0.382391E+13 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.130324E+12 | 0.129588E+12 | 668974.22 | 659748.02 | 0.13 | |
Maximum of Months | 0.00 | 0.00 | 0.817380E+12 | 0.592133E+12 | 1304991.57 | 1127309.67 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128754E+11 | 0.128439E+11 | 71465.07 | 18-JAN-13:50 | 71465.07 | 0.18 |
February | 0.00 | 0.00 | 0.716560E+10 | 0.711362E+10 | 60523.57 | 03-FEB-15:00 | 60523.57 | 0.15 |
March | 0.00 | 0.00 | 0.893663E+10 | 0.873376E+10 | 76923.11 | 23-MAR-14:30 | 64924.72 | 0.17 |
April | 0.00 | 0.00 | 0.218585E+11 | 0.218544E+11 | 99481.85 | 26-APR-14:00 | 99481.85 | 0.35 |
May | 0.00 | 0.00 | 0.224028E+11 | 0.223485E+11 | 75847.23 | 03-MAY-13:10 | 75847.23 | 0.41 |
June | 0.00 | 0.00 | 0.414600E+11 | 0.379768E+11 | 111652.80 | 29-JUN-13:00 | 74401.56 | 0.55 |
July | 0.00 | 0.00 | 0.739668E+11 | 0.561033E+11 | 159235.17 | 31-JUL-15:40 | 93738.71 | 0.60 |
August | 0.00 | 0.00 | 0.864253E+11 | 0.623553E+11 | 160105.33 | 14-AUG-13:50 | 97058.87 | 0.61 |
September | 0.00 | 0.00 | 0.472299E+11 | 0.402995E+11 | 124695.30 | 29-SEP-13:40 | 124695.30 | 0.52 |
October | 0.00 | 0.00 | 0.543329E+11 | 0.464682E+11 | 143773.62 | 03-OCT-13:30 | 84782.92 | 0.38 |
November | 0.00 | 0.00 | 0.138355E+11 | 0.137213E+11 | 67801.39 | 28-NOV-14:00 | 67801.39 | 0.20 |
December | 0.00 | 0.00 | 0.158062E+11 | 0.157704E+11 | 74696.09 | 05-DEC-15:00 | 74696.09 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.406296E+12 | 0.345589E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.716560E+10 | 0.711362E+10 | 60523.57 | 60523.57 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.864253E+11 | 0.623553E+11 | 160105.33 | 124695.30 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.162015E+11 | 0.157361E+11 | 85227.95 | 17-JAN-12:05 | 71535.46 | 0.16 |
February | 0.00 | 0.00 | 0.896401E+10 | 0.827871E+10 | 62133.86 | 13-FEB-07:23 | 26772.05 | 0.14 |
March | 0.00 | 0.00 | 0.100962E+11 | 0.898264E+10 | 56594.43 | 22-MAR-13:00 | 37535.49 | 0.18 |
April | 0.00 | 0.00 | 0.220655E+11 | 0.201827E+11 | 65665.45 | 27-APR-06:25 | 31691.07 | 0.33 |
May | 0.00 | 0.00 | 0.212420E+11 | 0.194641E+11 | 68749.65 | 05-MAY-06:25 | 36661.42 | 0.34 |
June | 0.00 | 0.00 | 0.385478E+11 | 0.315885E+11 | 83302.67 | 30-JUN-06:25 | 37317.39 | 0.45 |
July | 0.00 | 0.00 | 0.528255E+11 | 0.421849E+11 | 112125.79 | 31-JUL-09:20 | 66966.66 | 0.44 |
August | 0.00 | 0.00 | 0.600294E+11 | 0.464196E+11 | 117534.10 | 07-AUG-10:10 | 65646.38 | 0.49 |
September | 0.00 | 0.00 | 0.357270E+11 | 0.279597E+11 | 99238.04 | 22-SEP-10:00 | 41002.60 | 0.40 |
October | 0.00 | 0.00 | 0.473251E+11 | 0.386887E+11 | 116995.00 | 05-OCT-13:00 | 64791.01 | 0.29 |
November | 0.00 | 0.00 | 0.178655E+11 | 0.173911E+11 | 67309.42 | 10-NOV-07:16 | 34218.82 | 0.18 |
December | 0.00 | 0.00 | 0.202930E+11 | 0.197604E+11 | 72595.59 | 04-DEC-10:00 | 72595.59 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.351183E+12 | 0.296637E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.896401E+10 | 0.827871E+10 | 56594.43 | 26772.05 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.600294E+11 | 0.464196E+11 | 117534.10 | 72595.59 | 0.49 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.802613E+10 | 0.796215E+10 | 104900.67 | 14-JAN-11:00 | 104900.67 | 0.00 |
February | 0.00 | 0.00 | 0.744384E+10 | 0.738414E+10 | 194182.11 | 01-FEB-12:00 | 194182.11 | 0.00 |
March | 0.00 | 0.00 | 0.398588E+11 | 0.319603E+11 | 260635.96 | 23-MAR-14:00 | 194830.04 | 0.00 |
April | 0.00 | 0.00 | 0.245355E+12 | 0.187297E+12 | 447546.03 | 26-APR-11:00 | 377084.82 | 0.00 |
May | 0.00 | 0.00 | 0.899389E+09 | 0.829920E+09 | 47464.01 | 04-MAY-12:00 | 41287.46 | 0.00 |
June | 0.00 | 0.00 | 0.659318E+11 | 0.473480E+11 | 244257.59 | 29-JUN-11:00 | 163478.86 | 0.00 |
July | 0.00 | 0.00 | 0.381008E+12 | 0.239182E+12 | 463654.75 | 31-JUL-14:00 | 317642.26 | 0.00 |
August | 0.00 | 0.00 | 0.856170E+12 | 0.486085E+12 | 493278.58 | 14-AUG-10:00 | 331930.27 | 0.00 |
September | 0.00 | 0.00 | 0.177342E+11 | 0.162373E+11 | 187155.04 | 21-SEP-13:30 | 132769.14 | 0.00 |
October | 0.00 | 0.00 | 0.120452E+12 | 0.100785E+12 | 314550.42 | 01-OCT-11:52 | 190912.75 | 0.00 |
November | 0.00 | 0.00 | 0.637070E+11 | 0.575154E+11 | 316110.59 | 19-NOV-12:53 | 316110.59 | 0.00 |
December | 0.00 | 0.00 | 0.177991E+12 | 0.167841E+12 | 382034.32 | 05-DEC-10:00 | 382034.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198458E+13 | 0.135043E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.899389E+09 | 0.829920E+09 | 47464.01 | 41287.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.856170E+12 | 0.486085E+12 | 493278.58 | 382034.32 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.524669E+10 | 0.520474E+10 | 2467.31 | 18-JAN-16:10 | 2378.13 | 0.00 |
February | 0.00 | 0.00 | 0.941775E+10 | 0.935731E+10 | 4705.68 | 20-FEB-17:00 | 4687.68 | 0.00 |
March | 0.00 | 0.00 | 0.155654E+11 | 0.154717E+11 | 7553.77 | 31-MAR-24:00 | 7553.77 | 0.00 |
April | 0.00 | 0.00 | 0.202325E+11 | 0.201014E+11 | 8484.91 | 16-APR-17:12 | 8457.10 | 0.00 |
May | 0.00 | 0.00 | 0.560537E+10 | 0.550654E+10 | 3848.73 | 31-MAY-24:00 | 3831.23 | 0.00 |
June | 0.00 | 0.00 | 0.106316E+11 | 0.104390E+11 | 5870.79 | 30-JUN-24:00 | 5866.26 | 0.00 |
July | 0.00 | 0.00 | 0.162670E+11 | 0.159820E+11 | 7745.18 | 31-JUL-24:00 | 7745.18 | 0.00 |
August | 0.00 | 0.00 | 0.212802E+11 | 0.209539E+11 | 8581.05 | 06-AUG-17:45 | 8581.05 | 0.00 |
September | 0.00 | 0.00 | 0.572502E+10 | 0.554494E+10 | 4081.40 | 30-SEP-24:00 | 4081.40 | 0.00 |
October | 0.00 | 0.00 | 0.109789E+11 | 0.108535E+11 | 5848.86 | 31-OCT-24:00 | 5845.09 | 0.00 |
November | 0.00 | 0.00 | 0.152241E+11 | 0.151512E+11 | 6549.78 | 12-NOV-16:20 | 6524.92 | 0.00 |
December | 0.00 | 0.00 | 0.206891E+11 | 0.206565E+11 | 8551.80 | 25-DEC-16:20 | 8551.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156864E+12 | 0.155223E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.524669E+10 | 0.520474E+10 | 2467.31 | 2378.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212802E+11 | 0.209539E+11 | 8581.05 | 8581.05 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.409687E+11 | 0.405591E+11 | 22973.73 | 18-JAN-16:10 | 22106.11 | 0.00 |
February | 0.00 | 0.00 | 0.824985E+11 | 0.818987E+11 | 42055.09 | 21-FEB-17:00 | 40721.53 | 0.00 |
March | 0.00 | 0.00 | 0.141322E+12 | 0.140390E+12 | 68818.93 | 31-MAR-23:30 | 68818.93 | 0.00 |
April | 0.00 | 0.00 | 0.188841E+12 | 0.187537E+12 | 78923.38 | 30-APR-17:45 | 78769.07 | 0.00 |
May | 0.00 | 0.00 | 0.490795E+11 | 0.481090E+11 | 35195.41 | 31-MAY-23:40 | 34902.46 | 0.00 |
June | 0.00 | 0.00 | 0.982582E+11 | 0.963503E+11 | 55561.40 | 30-JUN-24:00 | 55511.80 | 0.00 |
July | 0.00 | 0.00 | 0.153410E+12 | 0.150579E+12 | 73989.80 | 31-JUL-24:00 | 73989.80 | 0.00 |
August | 0.00 | 0.00 | 0.201818E+12 | 0.198566E+12 | 80893.80 | 17-AUG-16:00 | 77405.98 | 0.00 |
September | 0.00 | 0.00 | 0.508028E+11 | 0.490316E+11 | 38132.92 | 30-SEP-24:00 | 38132.92 | 0.00 |
October | 0.00 | 0.00 | 0.100104E+12 | 0.988614E+11 | 54502.95 | 31-OCT-24:00 | 54459.79 | 0.00 |
November | 0.00 | 0.00 | 0.138475E+12 | 0.137751E+12 | 61223.53 | 10-NOV-16:20 | 58618.08 | 0.00 |
December | 0.00 | 0.00 | 0.189306E+12 | 0.188979E+12 | 79279.98 | 07-DEC-16:20 | 76883.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143488E+13 | 0.141861E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.409687E+11 | 0.405591E+11 | 22973.73 | 22106.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201818E+12 | 0.198566E+12 | 80893.80 | 78769.07 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.290170E+10 | 0.286175E+10 | 2322.35 | 18-JAN-16:10 | 2235.05 | 0.00 |
February | 0.00 | 0.00 | 0.730528E+10 | 0.724598E+10 | 4224.34 | 01-FEB-16:50 | 4025.53 | 0.00 |
March | 0.00 | 0.00 | 0.133005E+11 | 0.132076E+11 | 6554.99 | 31-MAR-23:20 | 6554.99 | 0.00 |
April | 0.00 | 0.00 | 0.184642E+11 | 0.183339E+11 | 7978.88 | 30-APR-17:40 | 7971.42 | 0.00 |
May | 0.00 | 0.00 | 0.448340E+10 | 0.438689E+10 | 3298.04 | 31-MAY-23:20 | 3253.53 | 0.00 |
June | 0.00 | 0.00 | 0.965004E+10 | 0.945907E+10 | 5451.26 | 30-JUN-23:40 | 5442.09 | 0.00 |
July | 0.00 | 0.00 | 0.152746E+11 | 0.149915E+11 | 7313.61 | 31-JUL-24:00 | 7313.61 | 0.00 |
August | 0.00 | 0.00 | 0.200921E+11 | 0.197670E+11 | 8181.38 | 17-AUG-16:00 | 7832.17 | 0.00 |
September | 0.00 | 0.00 | 0.482098E+10 | 0.464421E+10 | 3786.25 | 30-SEP-23:50 | 3786.25 | 0.00 |
October | 0.00 | 0.00 | 0.960567E+10 | 0.948167E+10 | 5263.41 | 31-OCT-23:30 | 5252.66 | 0.00 |
November | 0.00 | 0.00 | 0.129932E+11 | 0.129212E+11 | 6140.10 | 10-NOV-16:20 | 5879.59 | 0.00 |
December | 0.00 | 0.00 | 0.178220E+11 | 0.177895E+11 | 7928.80 | 07-DEC-16:20 | 7689.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136714E+12 | 0.135090E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.290170E+10 | 0.286175E+10 | 2322.35 | 2235.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200921E+11 | 0.197670E+11 | 8181.38 | 7971.42 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4260.63 | 488861.17 | 09-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1186.81 | 99342.68 | 09-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3077.17 | 459524.68 | 30-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 122.30 | 91375.61 | 01-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24.71 | 64103.97 | 09-MAY-09:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 1.28 | 28-JUN-14:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 1.33 | 08-JUL-04:12 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.01 | 2.57 | 15-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 1.32 | 13-SEP-10:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.09 | 21896.68 | 12-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 286.54 | 77564.28 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2380.10 | 152984.15 | 13-DEC-06:03 |
Annual Sum or Average | 0.00 | 954.06 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 1.28 | ||
Maximum of Months | 0.00 | 0.00 | 4260.63 | 488861.17 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 106477.25 | 1307500.08 | 18-JAN-13:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 67489.64 | 1223693.01 | 03-FEB-14:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64955.55 | 1206321.39 | 23-MAR-13:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 119496.77 | 1298328.15 | 26-APR-10:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 115853.72 | 1170522.17 | 03-MAY-13:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 212605.61 | 1428249.79 | 26-JUN-12:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 350519.31 | 1574521.19 | 28-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 414916.11 | 1678503.79 | 07-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 247448.42 | 1462932.55 | 21-SEP-12:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 286286.77 | 1657778.60 | 03-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 118007.07 | 1192230.72 | 28-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 128690.37 | 1262026.65 | 19-DEC-13:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 187164.71 | 0.00 | ||||
Minimum of Months | 64955.55 | 1170522.17 | 0.00 | 0.00 | ||
Maximum of Months | 414916.11 | 1678503.79 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 106405.06 | 1257264.79 | 13-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 66697.62 | 1181283.94 | 01-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64289.15 | 1413241.93 | 23-MAR-13:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 118306.24 | 1280053.49 | 26-APR-10:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 114690.99 | 1131710.73 | 03-MAY-12:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 210839.13 | 1309125.87 | 30-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 348711.21 | 2031561.10 | 25-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 413104.49 | 2178485.87 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 246153.48 | 1969231.09 | 22-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 288362.00 | 2328922.10 | 05-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 117144.07 | 1366480.75 | 28-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 127669.14 | 1378836.11 | 19-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186304.15 | 0.00 | ||||
Minimum of Months | 64289.15 | 1131710.73 | 0.00 | 0.00 | ||
Maximum of Months | 413104.49 | 2328922.10 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 53494.95 | 648553.92 | 14-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 65985.64 | 839427.30 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 117530.75 | 832223.23 | 11-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 303619.88 | 1368229.39 | 26-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57031.04 | 432996.06 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 165290.60 | 874827.56 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 446751.29 | 1420932.26 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 780947.19 | 1573497.90 | 14-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 127018.71 | 1294437.87 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 259472.53 | 1571832.80 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 146501.98 | 1163345.62 | 19-NOV-12:57 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 250053.82 | 1275620.22 | 19-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 232997.98 | 0.00 | ||||
Minimum of Months | 53494.95 | 432996.06 | 0.00 | 0.00 | ||
Maximum of Months | 780947.19 | 1573497.90 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12564.79 | 44636.63 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12655.77 | 44638.17 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13307.34 | 44417.23 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12208.91 | 43614.20 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 12302.44 | 42650.75 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12321.69 | 41560.07 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11166.97 | 40717.83 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 12214.87 | 40638.33 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 11582.52 | 41325.60 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11820.76 | 42413.92 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12295.20 | 43470.45 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12103.53 | 44259.75 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12209.62 | ||||
Minimum of Months | 0.00 | 0.00 | 11166.97 | 40638.33 | ||
Maximum of Months | 0.00 | 0.00 | 13307.34 | 44638.17 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 121592.69 | 1885851.01 | 13-JAN-14:40 | 1056.20 | 104786.12 | 09-JAN-07:00 |
February | 75524.54 | 1864553.09 | 01-FEB-11:50 | 966.62 | 94348.57 | 04-FEB-06:50 |
March | 75916.32 | 1911297.96 | 23-MAR-13:30 | 1021.32 | 62921.75 | 23-MAR-05:50 |
April | 143174.02 | 1973340.24 | 26-APR-11:20 | 921.70 | 61539.66 | 10-APR-08:00 |
May | 134245.82 | 1860766.72 | 04-MAY-12:30 | 655.85 | 57384.97 | 12-MAY-08:00 |
June | 282496.24 | 2523340.62 | 29-JUN-13:00 | 405.10 | 39949.91 | 09-JUN-20:00 |
July | 572066.24 | 3523967.93 | 31-JUL-13:00 | 440.20 | 45618.45 | 07-JUL-21:00 |
August | 698162.17 | 3721442.84 | 07-AUG-10:30 | 439.53 | 40202.65 | 21-AUG-20:20 |
September | 347746.89 | 3112690.91 | 22-SEP-10:05 | 275.50 | 44449.31 | 15-SEP-20:30 |
October | 407270.98 | 3475326.68 | 03-OCT-13:50 | 669.17 | 88159.55 | 27-OCT-05:40 |
November | 133086.96 | 1824609.17 | 30-NOV-14:00 | 999.72 | 91558.76 | 24-NOV-08:30 |
December | 146886.55 | 1863612.80 | 19-DEC-11:00 | 1004.80 | 98958.38 | 26-DEC-06:40 |
Annual Sum or Average | 263425.14 | 737.06 | ||||
Minimum of Months | 75524.54 | 1824609.17 | 275.50 | 39949.91 | ||
Maximum of Months | 698162.17 | 3721442.84 | 1056.20 | 104786.12 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.594262E+10 | 0.40 | 13353.74 | 02-JAN-10:30 | 1.45 |
February | 0.582195E+10 | 0.42 | 13114.86 | 21-FEB-16:00 | 1.42 |
March | 0.768434E+10 | 0.47 | 13372.96 | 23-MAR-15:20 | 1.44 |
April | 0.964074E+10 | 0.56 | 14930.66 | 26-APR-14:00 | 1.54 |
May | 0.716077E+10 | 0.46 | 11989.12 | 25-MAY-05:02 | 1.35 |
June | 0.874665E+10 | 0.52 | 16486.13 | 19-JUN-05:02 | 1.64 |
July | 0.105522E+11 | 0.60 | 18840.14 | 24-JUL-05:02 | 1.79 |
August | 0.124771E+11 | 0.69 | 18840.14 | 07-AUG-05:03 | 1.79 |
September | 0.813856E+10 | 0.49 | 18840.14 | 06-SEP-05:02 | 1.79 |
October | 0.882130E+10 | 0.51 | 18840.14 | 02-OCT-05:02 | 1.79 |
November | 0.769326E+10 | 0.47 | 15686.29 | 13-NOV-09:00 | 1.59 |
December | 0.762513E+10 | 0.46 | 15646.72 | 26-DEC-09:10 | 1.61 |
Annual Sum or Average | 0.100305E+12 | 0.50 | |||
Minimum of Months | 0.582195E+10 | 0.40 | 11989.12 | 1.35 | |
Maximum of Months | 0.124771E+11 | 0.69 | 18840.14 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.378236E+11 | 0.33 | 84560.52 | 09-JAN-06:02 | 1.15 |
February | 0.355482E+11 | 0.34 | 78595.55 | 03-FEB-16:00 | 1.10 |
March | 0.420931E+11 | 0.36 | 96834.04 | 23-MAR-15:40 | 1.23 |
April | 0.514879E+11 | 0.40 | 105982.90 | 26-APR-14:05 | 1.30 |
May | 0.510636E+11 | 0.40 | 89051.98 | 03-MAY-14:05 | 1.17 |
June | 0.586711E+11 | 0.43 | 115455.59 | 19-JUN-05:02 | 1.38 |
July | 0.656673E+11 | 0.45 | 158686.17 | 24-JUL-05:02 | 1.68 |
August | 0.752794E+11 | 0.49 | 144171.30 | 07-AUG-05:03 | 1.58 |
September | 0.589196E+11 | 0.43 | 174751.21 | 30-SEP-05:02 | 1.80 |
October | 0.541791E+11 | 0.40 | 174751.21 | 02-OCT-05:02 | 1.79 |
November | 0.423080E+11 | 0.36 | 78247.38 | 01-NOV-14:05 | 1.08 |
December | 0.387163E+11 | 0.34 | 78455.12 | 05-DEC-16:10 | 1.09 |
Annual Sum or Average | 0.611757E+12 | 0.39 | |||
Minimum of Months | 0.355482E+11 | 0.33 | 78247.38 | 1.08 | |
Maximum of Months | 0.752794E+11 | 0.49 | 174751.21 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.292717E+10 | 0.30 | 7075.59 | 18-JAN-15:50 | 0.99 |
February | 0.278748E+10 | 0.31 | 7182.36 | 03-FEB-15:40 | 1.01 |
March | 0.335698E+10 | 0.33 | 10182.83 | 23-MAR-15:20 | 1.23 |
April | 0.467557E+10 | 0.37 | 11590.94 | 26-APR-14:20 | 1.33 |
May | 0.465389E+10 | 0.37 | 10409.60 | 03-MAY-15:20 | 1.25 |
June | 0.583050E+10 | 0.42 | 10957.25 | 30-JUN-16:00 | 1.28 |
July | 0.689082E+10 | 0.44 | 12951.14 | 31-JUL-14:40 | 1.43 |
August | 0.776525E+10 | 0.48 | 12825.86 | 17-AUG-15:20 | 1.42 |
September | 0.553306E+10 | 0.40 | 18476.94 | 30-SEP-05:02 | 1.80 |
October | 0.480813E+10 | 0.37 | 18476.94 | 16-OCT-14:10 | 1.80 |
November | 0.320997E+10 | 0.31 | 7276.88 | 10-NOV-15:20 | 1.00 |
December | 0.293526E+10 | 0.30 | 6955.91 | 05-DEC-15:50 | 0.98 |
Annual Sum or Average | 0.553741E+11 | 0.37 | |||
Minimum of Months | 0.278748E+10 | 0.30 | 6955.91 | 0.98 | |
Maximum of Months | 0.776525E+10 | 0.48 | 18476.94 | 1.80 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120964E+11 | 0.79 | 10894.61 | 02-JAN-07:05 | 1.82 |
February | 0.105377E+11 | 0.77 | 10894.61 | 01-FEB-07:05 | 1.83 |
March | 0.121563E+11 | 0.81 | 10894.61 | 01-MAR-07:05 | 1.82 |
April | 0.973540E+10 | 0.69 | 10894.61 | 01-APR-06:05 | 1.83 |
May | 0.111137E+11 | 0.75 | 10894.61 | 01-MAY-06:10 | 1.81 |
June | 0.796680E+10 | 0.61 | 10894.61 | 01-JUN-06:10 | 1.81 |
July | 0.116293E+11 | 0.76 | 10894.61 | 01-JUL-06:10 | 1.81 |
August | 0.134494E+11 | 0.87 | 10894.61 | 01-AUG-06:10 | 1.80 |
September | 0.900429E+10 | 0.64 | 10894.61 | 01-SEP-06:10 | 1.81 |
October | 0.105734E+11 | 0.70 | 10894.61 | 02-OCT-06:10 | 1.77 |
November | 0.119274E+11 | 0.80 | 10894.61 | 01-NOV-06:10 | 1.81 |
December | 0.118200E+11 | 0.77 | 10894.61 | 01-DEC-07:10 | 1.83 |
Annual Sum or Average | 0.132010E+12 | 0.75 | |||
Minimum of Months | 0.796680E+10 | 0.61 | 10894.61 | 1.77 | |
Maximum of Months | 0.134494E+11 | 0.87 | 10894.61 | 1.83 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109634E+12 | 1.37 | 40932.60 | 01-JAN-00:10 | 1.37 |
February | 0.990242E+11 | 1.37 | 40932.60 | 01-FEB-00:10 | 1.37 |
March | 0.109634E+12 | 1.37 | 40932.60 | 01-MAR-00:10 | 1.37 |
April | 0.106097E+12 | 1.37 | 40932.60 | 01-APR-00:10 | 1.37 |
May | 0.109634E+12 | 1.37 | 40932.60 | 01-MAY-00:05 | 1.36 |
June | 0.106097E+12 | 1.36 | 40932.60 | 01-JUN-00:10 | 1.37 |
July | 0.109634E+12 | 1.36 | 40932.60 | 01-JUL-00:10 | 1.36 |
August | 0.109634E+12 | 1.36 | 40932.60 | 01-AUG-00:10 | 1.36 |
September | 0.106097E+12 | 1.36 | 40932.60 | 01-SEP-00:05 | 1.36 |
October | 0.109634E+12 | 1.37 | 40932.60 | 01-OCT-00:10 | 1.36 |
November | 0.106097E+12 | 1.37 | 40932.60 | 01-NOV-00:10 | 1.37 |
December | 0.109634E+12 | 1.38 | 40932.60 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.129085E+13 | 1.37 | |||
Minimum of Months | 0.990242E+11 | 1.36 | 40932.60 | 1.36 | |
Maximum of Months | 0.109634E+12 | 1.38 | 40932.60 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142853E+10 | 0.93 | 533.35 | 01-JAN-00:10 | 0.93 |
February | 0.129028E+10 | 0.93 | 533.35 | 01-FEB-00:10 | 0.93 |
March | 0.142853E+10 | 0.93 | 533.35 | 01-MAR-00:10 | 0.93 |
April | 0.138245E+10 | 0.93 | 533.35 | 01-APR-00:10 | 0.93 |
May | 0.142853E+10 | 0.93 | 533.35 | 01-MAY-00:05 | 0.93 |
June | 0.138245E+10 | 0.93 | 533.35 | 01-JUN-00:10 | 0.93 |
July | 0.142853E+10 | 0.93 | 533.35 | 01-JUL-00:10 | 0.93 |
August | 0.142853E+10 | 0.93 | 533.35 | 01-AUG-00:10 | 0.93 |
September | 0.138245E+10 | 0.93 | 533.35 | 01-SEP-00:05 | 0.93 |
October | 0.142853E+10 | 0.93 | 533.35 | 01-OCT-00:10 | 0.93 |
November | 0.138245E+10 | 0.93 | 533.35 | 01-NOV-00:10 | 0.93 |
December | 0.142853E+10 | 0.93 | 533.35 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.168198E+11 | 0.93 | |||
Minimum of Months | 0.129028E+10 | 0.93 | 533.35 | 0.93 | |
Maximum of Months | 0.142853E+10 | 0.93 | 533.35 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136408E+11 | 0.93 | 5092.89 | 01-JAN-00:10 | 0.93 |
February | 0.123207E+11 | 0.93 | 5092.89 | 01-FEB-00:10 | 0.93 |
March | 0.136408E+11 | 0.93 | 5092.89 | 01-MAR-00:10 | 0.93 |
April | 0.132008E+11 | 0.93 | 5092.89 | 01-APR-00:10 | 0.93 |
May | 0.136408E+11 | 0.93 | 5092.89 | 01-MAY-00:05 | 0.93 |
June | 0.132008E+11 | 0.93 | 5092.89 | 01-JUN-00:10 | 0.93 |
July | 0.136408E+11 | 0.93 | 5092.89 | 01-JUL-00:10 | 0.93 |
August | 0.136408E+11 | 0.93 | 5092.89 | 01-AUG-00:10 | 0.93 |
September | 0.132008E+11 | 0.93 | 5092.89 | 01-SEP-00:05 | 0.93 |
October | 0.136408E+11 | 0.93 | 5092.89 | 01-OCT-00:10 | 0.93 |
November | 0.132008E+11 | 0.93 | 5092.89 | 01-NOV-00:10 | 0.93 |
December | 0.136408E+11 | 0.93 | 5092.89 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.160610E+12 | 0.93 | |||
Minimum of Months | 0.123207E+11 | 0.93 | 5092.89 | 0.93 | |
Maximum of Months | 0.136408E+11 | 0.93 | 5092.89 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138624E+10 | 0.93 | 517.56 | 01-JAN-00:10 | 0.93 |
February | 0.125209E+10 | 0.93 | 517.56 | 01-FEB-00:10 | 0.93 |
March | 0.138624E+10 | 0.93 | 517.56 | 01-MAR-00:10 | 0.93 |
April | 0.134152E+10 | 0.93 | 517.56 | 01-APR-00:10 | 0.93 |
May | 0.138624E+10 | 0.93 | 517.56 | 01-MAY-00:05 | 0.93 |
June | 0.134152E+10 | 0.93 | 517.56 | 01-JUN-00:10 | 0.93 |
July | 0.138624E+10 | 0.93 | 517.56 | 01-JUL-00:10 | 0.93 |
August | 0.138624E+10 | 0.93 | 517.56 | 01-AUG-00:10 | 0.93 |
September | 0.134152E+10 | 0.93 | 517.56 | 01-SEP-00:05 | 0.93 |
October | 0.138624E+10 | 0.93 | 517.56 | 01-OCT-00:10 | 0.93 |
November | 0.134152E+10 | 0.93 | 517.56 | 01-NOV-00:10 | 0.93 |
December | 0.138624E+10 | 0.93 | 517.56 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.163218E+11 | 0.93 | |||
Minimum of Months | 0.125209E+10 | 0.93 | 517.56 | 0.93 | |
Maximum of Months | 0.138624E+10 | 0.93 | 517.56 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 53421081.51 | 48559763.09 | 1830.21 | 09-JAN-06:02 | 1663.66 | 1663.66 | 39.92 | 2.78 |
February | 12313661.32 | 11193118.14 | 419.76 | 09-FEB-07:10 | 381.56 | 381.56 | 31.27 | 0.46 |
March | 36523836.13 | 33200167.04 | 1866.07 | 30-MAR-05:03 | 1696.26 | 1696.26 | 43.67 | 2.87 |
April | 1385824.05 | 1259714.06 | 389.66 | 01-APR-06:10 | 354.20 | 354.20 | 30.87 | 0.42 |
May | 274271.07 | 249312.41 | 260.87 | 09-MAY-09:40 | 237.13 | 237.13 | 26.97 | 0.28 |
June | 33.92 | 30.84 | 0.01 | 28-JUN-14:00 | 0.00 | 0.00 | 27.15 | 0.00 |
July | 37.82 | 34.38 | 0.01 | 08-JUL-04:12 | 0.01 | 0.01 | 27.15 | 0.00 |
August | 164.15 | 149.21 | 0.01 | 15-AUG-11:20 | 0.01 | 0.01 | 27.15 | 0.00 |
September | 24.42 | 22.20 | 0.01 | 13-SEP-10:00 | 0.01 | 0.01 | 27.15 | 0.00 |
October | 257640.97 | 234195.64 | 91.10 | 12-OCT-06:10 | 82.81 | 82.81 | 26.81 | 0.09 |
November | 3173125.60 | 2884371.17 | 322.98 | 27-NOV-06:03 | 293.58 | 293.58 | 29.82 | 0.35 |
December | 28485135.08 | 25892987.79 | 740.52 | 13-DEC-06:03 | 673.14 | 673.14 | 39.12 | 0.85 |
Annual Sum or Average | 0.135835E+09 | 0.123474E+09 | ||||||
Minimum of Months | 24.42 | 22.20 | 0.01 | 0.00 | 0.00 | 26.81 | 0.00 | |
Maximum of Months | 53421081.51 | 48559763.09 | 1866.07 | 1696.26 | 1696.26 | 43.67 | 2.87 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.238573E+09 | 0.216863E+09 | 5432.54 | 18-JAN-15:20 | 4938.18 | 4938.18 | 9.21 | 45.20 |
February | 99027391.05 | 90015898.46 | 3498.67 | 01-FEB-13:10 | 3180.29 | 3180.29 | 8.16 | 37.81 |
March | 0.101896E+09 | 92623701.13 | 3823.44 | 23-MAR-13:20 | 3475.50 | 3475.50 | 10.58 | 39.21 |
April | 0.212371E+09 | 0.193045E+09 | 2859.76 | 12-APR-13:50 | 2599.52 | 2599.52 | 10.07 | 34.79 |
May | 0.210155E+09 | 0.191030E+09 | 3230.79 | 03-MAY-12:50 | 2936.79 | 2936.79 | 8.44 | 36.59 |
June | 0.386730E+09 | 0.351537E+09 | 3070.23 | 30-JUN-05:03 | 2790.84 | 2790.84 | 7.72 | 35.83 |
July | 0.765048E+09 | 0.695429E+09 | 7929.77 | 20-JUL-05:02 | 7208.16 | 7208.16 | 9.14 | 52.54 |
August | 0.995843E+09 | 0.905221E+09 | 7930.19 | 07-AUG-05:03 | 7208.54 | 7208.54 | 9.66 | 52.54 |
September | 0.602778E+09 | 0.547925E+09 | 7776.42 | 22-SEP-05:03 | 7068.76 | 7068.76 | 9.34 | 52.13 |
October | 0.839784E+09 | 0.763364E+09 | 8968.88 | 16-OCT-14:40 | 8152.72 | 8152.72 | 6.73 | 55.15 |
November | 0.217333E+09 | 0.197556E+09 | 3554.50 | 08-NOV-13:40 | 3231.04 | 3231.04 | 8.17 | 38.06 |
December | 0.213436E+09 | 0.194014E+09 | 2352.01 | 19-DEC-13:30 | 2137.97 | 2137.97 | 8.72 | 32.07 |
Annual Sum or Average | 0.488297E+10 | 0.443862E+10 | ||||||
Minimum of Months | 99027391.05 | 90015898.46 | 2352.01 | 2137.97 | 2137.97 | 6.73 | 32.07 | |
Maximum of Months | 0.995843E+09 | 0.905221E+09 | 8968.88 | 8152.72 | 8152.72 | 10.58 | 55.15 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.301959E+10 | 0.274480E+10 | 3086.52 | 02-JAN-07:05 | 2805.65 | 2805.65 | 6.72 | 27.58 |
February | 0.238277E+10 | 0.216594E+10 | 3086.52 | 01-FEB-05:13 | 2805.65 | 2805.65 | 6.76 | 27.58 |
March | 0.257693E+10 | 0.234243E+10 | 3086.52 | 01-MAR-06:02 | 2805.65 | 2805.65 | 6.75 | 27.58 |
April | 0.372651E+10 | 0.338739E+10 | 3086.52 | 01-APR-05:02 | 2805.65 | 2805.65 | 6.76 | 27.58 |
May | 0.405829E+10 | 0.368899E+10 | 3086.52 | 01-MAY-00:05 | 2805.65 | 2805.65 | 6.73 | 27.58 |
June | 0.486082E+10 | 0.441849E+10 | 3086.52 | 01-JUN-05:02 | 2805.65 | 2805.65 | 6.98 | 27.58 |
July | 0.624264E+10 | 0.567456E+10 | 3086.52 | 01-JUL-04:12 | 2805.65 | 2805.65 | 9.01 | 27.58 |
August | 0.684272E+10 | 0.622004E+10 | 3086.52 | 01-AUG-00:25 | 2805.65 | 2805.65 | 6.86 | 27.58 |
September | 0.470828E+10 | 0.427983E+10 | 3086.52 | 01-SEP-00:05 | 2805.65 | 2805.65 | 6.75 | 27.58 |
October | 0.501572E+10 | 0.455929E+10 | 3086.52 | 01-OCT-07:05 | 2805.65 | 2805.65 | 6.98 | 27.58 |
November | 0.329171E+10 | 0.299216E+10 | 3086.52 | 01-NOV-04:12 | 2805.65 | 2805.65 | 7.06 | 27.58 |
December | 0.324160E+10 | 0.294661E+10 | 3086.52 | 01-DEC-07:11 | 2805.65 | 2805.65 | 6.93 | 27.58 |
Annual Sum or Average | 0.499676E+11 | 0.454205E+11 | ||||||
Minimum of Months | 0.238277E+10 | 0.216594E+10 | 3086.52 | 2805.65 | 2805.65 | 6.72 | 27.58 | |
Maximum of Months | 0.684272E+10 | 0.622004E+10 | 3086.52 | 2805.65 | 2805.65 | 9.01 | 27.58 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 25000811.90 | 22725738.01 | 3086.52 | 13-JAN-14:20 | 2805.65 | 2805.65 | 14.68 | 13.79 |
February | 17593163.93 | 15992186.01 | 3086.52 | 01-FEB-11:30 | 2805.65 | 2805.65 | 14.89 | 13.79 |
March | 44445887.82 | 40401312.02 | 3086.52 | 22-MAR-12:20 | 2805.65 | 2805.65 | 15.35 | 13.79 |
April | 94447511.61 | 85852788.05 | 3086.52 | 04-APR-13:20 | 2805.65 | 2805.65 | 15.43 | 13.79 |
May | 18519119.92 | 16833880.01 | 3086.52 | 02-MAY-13:20 | 2805.65 | 2805.65 | 15.47 | 13.79 |
June | 0.372234E+09 | 0.338361E+09 | 3086.52 | 19-JUN-10:40 | 2805.65 | 2805.65 | 15.36 | 13.79 |
July | 0.121208E+10 | 0.110178E+10 | 3086.52 | 03-JUL-12:05 | 2805.65 | 2805.65 | 11.24 | 27.58 |
August | 0.165561E+10 | 0.150495E+10 | 3086.52 | 02-AUG-09:20 | 2805.65 | 2805.65 | 15.34 | 13.79 |
September | 0.725024E+09 | 0.659046E+09 | 3086.52 | 01-SEP-13:20 | 2805.65 | 2805.65 | 15.74 | 13.79 |
October | 0.991699E+09 | 0.901454E+09 | 3086.52 | 02-OCT-07:20 | 2805.65 | 2805.65 | 15.65 | 13.79 |
November | 34260371.86 | 31142678.02 | 3086.52 | 28-NOV-11:50 | 2805.65 | 2805.65 | 14.98 | 13.79 |
December | 0.112967E+09 | 0.102687E+09 | 3086.52 | 05-DEC-09:20 | 2805.65 | 2805.65 | 14.79 | 13.79 |
Annual Sum or Average | 0.530388E+10 | 0.482122E+10 | ||||||
Minimum of Months | 17593163.93 | 15992186.01 | 3086.52 | 2805.65 | 2805.65 | 11.24 | 13.79 | |
Maximum of Months | 0.165561E+10 | 0.150495E+10 | 3086.52 | 2805.65 | 2805.65 | 15.74 | 27.58 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-JAN-00:10 | 3348.44 | 3348.44 | 18.70 | 15.54 |
February | 0.891149E+10 | 0.810054E+10 | 3683.65 | 01-FEB-00:10 | 3348.44 | 3348.44 | 19.27 | 15.54 |
March | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-MAR-00:10 | 3348.44 | 3348.44 | 19.77 | 15.54 |
April | 0.954802E+10 | 0.867915E+10 | 3683.65 | 01-APR-00:10 | 3348.44 | 3348.44 | 20.29 | 15.54 |
May | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-MAY-00:05 | 3348.44 | 3348.44 | 18.95 | 15.54 |
June | 0.954802E+10 | 0.867915E+10 | 3683.65 | 01-JUN-00:10 | 3348.44 | 3348.44 | 19.35 | 15.54 |
July | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-JUL-00:10 | 3348.44 | 3348.44 | 19.89 | 15.54 |
August | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-AUG-00:10 | 3348.44 | 3348.44 | 29.77 | 15.54 |
September | 0.954802E+10 | 0.867915E+10 | 3683.65 | 01-SEP-00:05 | 3348.44 | 3348.44 | 18.93 | 15.54 |
October | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-OCT-00:10 | 3348.44 | 3348.44 | 19.90 | 15.54 |
November | 0.954802E+10 | 0.867915E+10 | 3683.65 | 01-NOV-00:10 | 3348.44 | 3348.44 | 19.90 | 15.54 |
December | 0.986629E+10 | 0.896846E+10 | 3683.65 | 01-DEC-00:10 | 3348.44 | 3348.44 | 20.40 | 15.54 |
Annual Sum or Average | 0.116168E+12 | 0.105596E+12 | ||||||
Minimum of Months | 0.891149E+10 | 0.810054E+10 | 3683.65 | 3348.44 | 3348.44 | 18.70 | 15.54 | |
Maximum of Months | 0.986629E+10 | 0.896846E+10 | 3683.65 | 3348.44 | 3348.44 | 29.77 | 15.54 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 57.22 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 57.38 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 57.45 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.49 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.56 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.62 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.61 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.64 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.56 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.37 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.51 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.51 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.22 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.64 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.120022E+11 | 0.109100E+11 | 24455.39 | 13-JAN-14:40 | 22229.95 | 22229.95 | 25.62 | 99.80 |
February | 0.945612E+10 | 0.859562E+10 | 24454.34 | 01-FEB-11:50 | 22229.00 | 22229.00 | 25.57 | 99.80 |
March | 0.103589E+11 | 0.941625E+10 | 24456.64 | 23-MAR-13:30 | 22231.09 | 22231.09 | 25.68 | 99.80 |
April | 0.150879E+11 | 0.137149E+11 | 24459.69 | 26-APR-11:20 | 22233.86 | 22233.86 | 25.83 | 99.80 |
May | 0.161050E+11 | 0.146394E+11 | 24454.16 | 04-MAY-12:30 | 22228.83 | 22228.83 | 25.56 | 99.80 |
June | 0.205477E+11 | 0.186778E+11 | 24486.74 | 29-JUN-13:00 | 22258.45 | 22258.45 | 27.15 | 99.80 |
July | 0.292970E+11 | 0.266310E+11 | 24533.97 | 31-JUL-12:40 | 22301.38 | 22301.38 | 29.46 | 99.80 |
August | 0.334035E+11 | 0.303638E+11 | 24533.97 | 07-AUG-10:05 | 22301.38 | 22301.38 | 29.68 | 99.80 |
September | 0.212945E+11 | 0.193567E+11 | 24515.79 | 22-SEP-10:05 | 22284.85 | 22284.85 | 28.56 | 99.80 |
October | 0.234381E+11 | 0.213053E+11 | 24533.70 | 03-OCT-13:50 | 22301.13 | 22301.13 | 29.43 | 99.80 |
November | 0.130958E+11 | 0.119041E+11 | 24452.38 | 30-NOV-14:00 | 22227.22 | 22227.22 | 25.47 | 99.80 |
December | 0.131706E+11 | 0.119720E+11 | 24454.30 | 19-DEC-11:00 | 22228.96 | 22228.96 | 25.57 | 99.80 |
Annual Sum or Average | 0.217257E+12 | 0.197487E+12 | ||||||
Minimum of Months | 0.945612E+10 | 0.859562E+10 | 24452.38 | 22227.22 | 22227.22 | 25.47 | 99.80 | |
Maximum of Months | 0.334035E+11 | 0.303638E+11 | 24533.97 | 22301.38 | 22301.38 | 29.68 | 99.80 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 82.00 | 82.00 | 4260.63 | 488861.17 | 09-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29.37 | 29.37 | 1186.81 | 99342.68 | 09-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29.02 | 29.02 | 3077.17 | 459524.68 | 30-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31.18 | 31.18 | 122.30 | 91375.61 | 01-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.45 | 26.45 | 24.71 | 64103.97 | 09-MAY-09:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 27.15 | 27.15 | 0.00 | 1.28 | 28-JUN-14:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.15 | 27.15 | 0.00 | 1.33 | 08-JUL-04:12 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.15 | 27.15 | 0.01 | 2.57 | 15-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.15 | 27.15 | 0.00 | 1.32 | 13-SEP-10:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.15 | 27.15 | 23.09 | 21896.68 | 12-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.86 | 25.86 | 286.54 | 77564.28 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.94 | 28.94 | 2380.10 | 152984.15 | 13-DEC-06:03 |
Annual Sum or Average | 0.00 | 954.06 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.86 | 25.86 | 0.00 | 1.28 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 4260.63 | 488861.17 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 106477.25 | 1307500.08 | 18-JAN-13:30 | 12.36 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 67489.64 | 1223693.01 | 03-FEB-14:05 | 12.00 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64955.55 | 1206321.39 | 23-MAR-13:05 | 11.92 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 119496.77 | 1298328.15 | 26-APR-10:10 | 12.32 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 115853.72 | 1170522.17 | 03-MAY-13:05 | 11.77 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 212605.61 | 1428249.79 | 26-JUN-12:05 | 12.88 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 350519.31 | 1574521.19 | 28-JUL-12:30 | 13.52 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 414916.11 | 1678503.79 | 07-AUG-10:30 | 13.97 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 247448.42 | 1462932.55 | 21-SEP-12:05 | 13.03 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 286286.77 | 1657778.60 | 03-OCT-13:40 | 13.88 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 118007.07 | 1192230.72 | 28-NOV-14:05 | 11.86 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 128690.37 | 1262026.65 | 19-DEC-13:05 | 12.16 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 187164.71 | 0.00 | ||||||
Minimum of Months | 64955.55 | 1170522.17 | 11.77 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 414916.11 | 1678503.79 | 13.97 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 106405.06 | 1257264.79 | 13-JAN-15:05 | 14.48 | 8.91 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 66697.62 | 1181283.94 | 01-FEB-13:10 | 14.16 | 8.71 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64289.15 | 1413241.93 | 23-MAR-13:20 | 15.31 | 11.05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 118306.24 | 1280053.49 | 26-APR-10:30 | 17.20 | 9.79 | 0.00 | 0.00 | 01-APR-00:10 |
May | 114690.99 | 1131710.73 | 03-MAY-12:50 | 14.09 | 8.51 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 210839.13 | 1309125.87 | 30-JUN-05:03 | 15.43 | 8.69 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 348711.21 | 2031561.10 | 25-JUL-05:02 | 15.94 | 11.08 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 413104.49 | 2178485.87 | 07-AUG-05:03 | 16.61 | 11.39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 246153.48 | 1969231.09 | 22-SEP-05:03 | 15.73 | 10.94 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 288362.00 | 2328922.10 | 05-OCT-05:03 | 17.30 | 11.72 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 117144.07 | 1366480.75 | 28-NOV-14:00 | 17.02 | 8.55 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 127669.14 | 1378836.11 | 19-DEC-13:30 | 16.98 | 8.66 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186304.15 | 0.00 | ||||||
Minimum of Months | 64289.15 | 1131710.73 | 14.09 | 8.51 | 0.00 | 0.00 | ||
Maximum of Months | 413104.49 | 2328922.10 | 17.30 | 11.72 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 53494.95 | 648553.92 | 14-JAN-12:00 | 30.25 | 27.10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 65985.64 | 839427.30 | 01-FEB-12:00 | 33.70 | 28.01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 117530.75 | 832223.23 | 11-MAR-14:00 | 33.57 | 26.50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 303619.88 | 1368229.39 | 26-APR-11:00 | 43.16 | 30.54 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57031.04 | 432996.06 | 03-MAY-13:00 | 26.32 | 24.60 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 165290.60 | 874827.56 | 29-JUN-11:00 | 34.34 | 27.44 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 446751.29 | 1420932.26 | 19-JUL-14:00 | 44.10 | 31.52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 780947.19 | 1573497.90 | 14-AUG-11:00 | 46.79 | 32.99 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 127018.71 | 1294437.87 | 29-SEP-13:00 | 41.85 | 37.54 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 259472.53 | 1571832.80 | 16-OCT-11:00 | 46.76 | 39.59 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 146501.98 | 1163345.62 | 19-NOV-12:57 | 39.52 | 30.29 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 250053.82 | 1275620.22 | 19-DEC-13:00 | 41.52 | 30.09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 232997.98 | 0.00 | ||||||
Minimum of Months | 53494.95 | 432996.06 | 26.32 | 24.60 | 0.00 | 0.00 | ||
Maximum of Months | 780947.19 | 1573497.90 | 46.79 | 39.59 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.36 | 58.36 | 12564.79 | 44636.63 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.92 | 57.92 | 12655.77 | 44638.17 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.93 | 57.93 | 13307.34 | 44417.23 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.97 | 57.97 | 12208.91 | 43614.20 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.43 | 58.43 | 12302.44 | 42650.75 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.07 | 58.07 | 12321.69 | 41560.07 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.11 | 58.11 | 11166.97 | 40717.83 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.13 | 58.13 | 12214.87 | 40638.33 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.12 | 58.12 | 11582.52 | 41325.60 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.08 | 58.08 | 11820.76 | 42413.92 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.03 | 58.03 | 12295.20 | 43470.45 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.98 | 57.98 | 12103.53 | 44259.75 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12209.62 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.92 | 57.92 | 11166.97 | 40638.33 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 13307.34 | 44638.17 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 121592.69 | 1885851.01 | 13-JAN-14:40 | 25.62 | 21.22 | 1056.20 | 104786.12 | 09-JAN-07:00 |
February | 75524.54 | 1864553.09 | 01-FEB-11:50 | 25.57 | 21.10 | 966.62 | 94348.57 | 04-FEB-06:50 |
March | 75916.32 | 1911297.96 | 23-MAR-13:30 | 25.68 | 21.99 | 1021.32 | 62921.75 | 23-MAR-05:50 |
April | 143174.02 | 1973340.24 | 26-APR-11:20 | 25.83 | 22.41 | 921.70 | 61539.66 | 10-APR-08:00 |
May | 134245.82 | 1860766.72 | 04-MAY-12:30 | 25.56 | 21.77 | 655.85 | 57384.97 | 12-MAY-08:00 |
June | 282496.24 | 2523340.62 | 29-JUN-13:00 | 27.15 | 23.60 | 405.10 | 39949.91 | 09-JUN-20:00 |
July | 572066.24 | 3523967.93 | 31-JUL-13:00 | 29.55 | 25.52 | 440.20 | 45618.45 | 07-JUL-21:00 |
August | 698162.17 | 3721442.84 | 07-AUG-10:30 | 30.02 | 25.30 | 439.53 | 40202.65 | 21-AUG-20:20 |
September | 347746.89 | 3112690.91 | 22-SEP-10:05 | 28.56 | 24.75 | 275.50 | 44449.31 | 15-SEP-20:30 |
October | 407270.98 | 3475326.68 | 03-OCT-13:50 | 29.43 | 24.75 | 669.17 | 88159.55 | 27-OCT-05:40 |
November | 133086.96 | 1824609.17 | 30-NOV-14:00 | 25.47 | 21.10 | 999.72 | 91558.76 | 24-NOV-08:30 |
December | 146886.55 | 1863612.80 | 19-DEC-11:00 | 25.57 | 21.10 | 1004.80 | 98958.38 | 26-DEC-06:40 |
Annual Sum or Average | 263425.14 | 737.06 | ||||||
Minimum of Months | 75524.54 | 1824609.17 | 25.47 | 21.10 | 275.50 | 39949.91 | ||
Maximum of Months | 698162.17 | 3721442.84 | 30.02 | 25.52 | 1056.20 | 104786.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.390002E+09 | 0.00 | 0.214056E+11 | 0.594262E+10 | 0.00 | 0.00 |
February | 44854781.84 | 0.00 | 0.120058E+11 | 0.582195E+10 | 0.00 | 0.00 |
March | 0.179524E+09 | 0.00 | 0.142555E+11 | 0.768434E+10 | 0.00 | 0.00 |
April | 4912789.11 | 0.00 | 0.317720E+11 | 0.964074E+10 | 0.00 | 0.00 |
May | 3745.70 | 0.00 | 0.280624E+11 | 0.716077E+10 | 0.00 | 0.00 |
June | 1820.10 | 0.00 | 0.509381E+11 | 0.874665E+10 | 0.00 | 0.00 |
July | 5743.12 | 0.00 | 0.929980E+11 | 0.105522E+11 | 0.00 | 0.00 |
August | 25135.80 | 0.00 | 0.114054E+12 | 0.124771E+11 | 0.00 | 0.00 |
September | 4187.39 | 0.00 | 0.579903E+11 | 0.813856E+10 | 0.00 | 0.00 |
October | 10165.76 | 0.00 | 0.747789E+11 | 0.882130E+10 | 0.00 | 0.00 |
November | 7070.81 | 0.00 | 0.249936E+11 | 0.769326E+10 | 0.00 | 0.00 |
December | 87869065.36 | 0.00 | 0.288812E+11 | 0.762513E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.707220E+09 | 0.00 | 0.552136E+12 | 0.100305E+12 | 0.00 | 0.00 |
Minimum of Months | 1820.10 | 0.00 | 0.120058E+11 | 0.582195E+10 | 0.00 | 0.00 |
Maximum of Months | 0.390002E+09 | 0.00 | 0.114054E+12 | 0.124771E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.821463E+10 | 0.00 | 0.228955E+12 | 0.378236E+11 | 0.00 | 0.00 |
February | 0.169197E+10 | 0.00 | 0.130324E+12 | 0.355482E+11 | 0.00 | 0.00 |
March | 0.613632E+10 | 0.00 | 0.135732E+12 | 0.420931E+11 | 0.00 | 0.00 |
April | 0.182804E+09 | 0.00 | 0.225478E+12 | 0.514879E+11 | 0.00 | 0.00 |
May | 36066364.41 | 0.00 | 0.232424E+12 | 0.510636E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.402723E+12 | 0.586711E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.692662E+12 | 0.656673E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.817380E+12 | 0.752794E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.482204E+12 | 0.589196E+11 | 0.00 | 0.00 |
October | 14354281.94 | 0.00 | 0.565784E+12 | 0.541791E+11 | 0.00 | 0.00 |
November | 0.223789E+09 | 0.00 | 0.238333E+12 | 0.423080E+11 | 0.00 | 0.00 |
December | 0.458517E+10 | 0.00 | 0.258017E+12 | 0.387163E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.210851E+11 | 0.00 | 0.441002E+13 | 0.611757E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.130324E+12 | 0.355482E+11 | 0.00 | 0.00 |
Maximum of Months | 0.821463E+10 | 0.00 | 0.817380E+12 | 0.752794E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.305758E+10 | 0.00 | 0.128754E+11 | 0.292717E+10 | 0.00 | 0.00 |
February | 0.116122E+10 | 0.00 | 0.716560E+10 | 0.278748E+10 | 0.00 | 0.00 |
March | 0.199452E+10 | 0.00 | 0.893663E+10 | 0.335698E+10 | 0.00 | 0.00 |
April | 0.145074E+09 | 0.00 | 0.218585E+11 | 0.467557E+10 | 0.00 | 0.00 |
May | 28763160.54 | 0.00 | 0.224028E+11 | 0.465389E+10 | 0.00 | 0.00 |
June | 6062.74 | 0.00 | 0.414600E+11 | 0.583050E+10 | 0.00 | 0.00 |
July | 5259.11 | 0.00 | 0.739668E+11 | 0.689082E+10 | 0.00 | 0.00 |
August | 21601.41 | 0.00 | 0.864253E+11 | 0.776525E+10 | 0.00 | 0.00 |
September | 2871.95 | 0.00 | 0.472299E+11 | 0.553306E+10 | 0.00 | 0.00 |
October | 51550499.83 | 0.00 | 0.543329E+11 | 0.480813E+10 | 0.00 | 0.00 |
November | 0.517225E+09 | 0.00 | 0.138355E+11 | 0.320997E+10 | 0.00 | 0.00 |
December | 0.176151E+10 | 0.00 | 0.158062E+11 | 0.293526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.871748E+10 | 0.00 | 0.406296E+12 | 0.553741E+11 | 0.00 | 0.00 |
Minimum of Months | 2871.95 | 0.00 | 0.716560E+10 | 0.278748E+10 | 0.00 | 0.00 |
Maximum of Months | 0.305758E+10 | 0.00 | 0.864253E+11 | 0.776525E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 372.84 | 0.00 | 0.162015E+11 | 0.120964E+11 | 0.00 | 0.00 |
February | 28896.91 | 0.00 | 0.896401E+10 | 0.105377E+11 | 0.00 | 0.00 |
March | 1063260.82 | 0.00 | 0.100962E+11 | 0.121563E+11 | 0.00 | 0.00 |
April | 1569.27 | 0.00 | 0.220655E+11 | 0.973540E+10 | 0.00 | 0.00 |
May | 492.77 | 0.00 | 0.212420E+11 | 0.111137E+11 | 0.00 | 0.00 |
June | 2112.72 | 0.00 | 0.385478E+11 | 0.796680E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.528255E+11 | 0.116293E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.600294E+11 | 0.134494E+11 | 0.00 | 0.00 |
September | 30.98 | 0.00 | 0.357270E+11 | 0.900429E+10 | 0.00 | 0.00 |
October | 1657.67 | 0.00 | 0.473251E+11 | 0.105734E+11 | 0.00 | 0.00 |
November | 1117.05 | 0.00 | 0.178655E+11 | 0.119274E+11 | 0.00 | 0.00 |
December | 624.44 | 0.00 | 0.202930E+11 | 0.118200E+11 | 0.00 | 0.00 |
Annual Sum or Average | 1100135.46 | 0.00 | 0.351183E+12 | 0.132010E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.896401E+10 | 0.796680E+10 | 0.00 | 0.00 |
Maximum of Months | 1063260.82 | 0.00 | 0.600294E+11 | 0.134494E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.131143E+11 | 0.179764E+12 | 0.00 | 24.20 |
February | 0.00 | 0.00 | 0.122289E+11 | 0.159141E+12 | 0.00 | 20.58 |
March | 0.00 | 0.00 | 0.534040E+11 | 0.170131E+12 | 0.00 | 17.47 |
April | 0.00 | 0.00 | 0.310450E+12 | 0.186591E+12 | 0.00 | 5.73 |
May | 0.00 | 0.00 | 0.393456E+10 | 0.117529E+12 | 0.00 | 1.81 |
June | 0.00 | 0.00 | 0.865513E+11 | 0.127024E+12 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.479745E+12 | 0.208371E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.106530E+13 | 0.318767E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.263653E+11 | 0.118976E+12 | 0.00 | 1.58 |
October | 0.00 | 0.00 | 0.158905E+12 | 0.206594E+12 | 0.00 | 21.76 |
November | 0.00 | 0.00 | 0.845997E+11 | 0.208898E+12 | 0.00 | 30.47 |
December | 0.00 | 0.00 | 0.231639E+12 | 0.311184E+12 | 0.00 | 55.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.252624E+13 | 0.231297E+13 | 0.00 | 178.73 |
Minimum of Months | 0.00 | 0.00 | 0.393456E+10 | 0.117529E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.106530E+13 | 0.318767E+12 | 0.00 | 55.02 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.646547E+10 | 0.264731E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114487E+11 | 0.332121E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187812E+11 | 0.464436E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243875E+11 | 0.553746E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.687911E+10 | 0.270226E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129728E+11 | 0.372363E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.199170E+11 | 0.507855E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.261138E+11 | 0.626214E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.706766E+10 | 0.272508E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135375E+11 | 0.398722E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.184252E+11 | 0.458354E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249917E+11 | 0.573117E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190988E+12 | 0.509439E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.646547E+10 | 0.264731E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.261138E+11 | 0.626214E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.506478E+11 | 0.233199E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100441E+12 | 0.302632E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.170702E+12 | 0.430201E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.227760E+12 | 0.521195E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.603130E+11 | 0.248743E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.119976E+12 | 0.349182E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.187898E+12 | 0.481289E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.247714E+12 | 0.595366E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.627989E+11 | 0.251969E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123572E+12 | 0.371094E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.167772E+12 | 0.424982E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.228943E+12 | 0.532771E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174854E+13 | 0.474262E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.506478E+11 | 0.233199E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.247714E+12 | 0.595366E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.360521E+10 | 0.208975E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.891302E+10 | 0.285982E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160893E+11 | 0.417506E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.222918E+11 | 0.516914E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.551881E+10 | 0.242165E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.117922E+11 | 0.348372E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.187209E+11 | 0.483252E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246783E+11 | 0.597248E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.596852E+10 | 0.248906E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.118762E+11 | 0.365681E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.157677E+11 | 0.411604E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.215949E+11 | 0.515911E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166817E+12 | 0.464252E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.360521E+10 | 0.208975E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.246783E+11 | 0.597248E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.594262E+10 | 0.214056E+11 | 0.390002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582195E+10 | 0.120058E+11 | 44854781.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768434E+10 | 0.142555E+11 | 0.179524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.964074E+10 | 0.317720E+11 | 4912789.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.716077E+10 | 0.280624E+11 | 3745.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.874665E+10 | 0.509381E+11 | 1820.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105522E+11 | 0.929980E+11 | 5743.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124771E+11 | 0.114054E+12 | 25135.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.813856E+10 | 0.579903E+11 | 4187.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.882130E+10 | 0.747789E+11 | 10165.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.769326E+10 | 0.249936E+11 | 7070.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762513E+10 | 0.288812E+11 | 87869065.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100305E+12 | 0.552136E+12 | 0.707220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.582195E+10 | 0.120058E+11 | 1820.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124771E+11 | 0.114054E+12 | 0.390002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.378236E+11 | 0.228955E+12 | 0.821463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355482E+11 | 0.130324E+12 | 0.169197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420931E+11 | 0.135732E+12 | 0.613632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.514879E+11 | 0.225478E+12 | 0.182804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.510636E+11 | 0.232424E+12 | 36066364.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.586711E+11 | 0.402723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656673E+11 | 0.692662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.752794E+11 | 0.817380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.589196E+11 | 0.482204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.541791E+11 | 0.565784E+12 | 14354281.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.423080E+11 | 0.238333E+12 | 0.223789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387163E+11 | 0.258017E+12 | 0.458517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611757E+12 | 0.441002E+13 | 0.210851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355482E+11 | 0.130324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.752794E+11 | 0.817380E+12 | 0.821463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.292717E+10 | 0.128754E+11 | 0.305758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278748E+10 | 0.716560E+10 | 0.116122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335698E+10 | 0.893663E+10 | 0.199452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.467557E+10 | 0.218585E+11 | 0.145074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.465389E+10 | 0.224028E+11 | 28763160.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583050E+10 | 0.414600E+11 | 6062.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.689082E+10 | 0.739668E+11 | 5259.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.776525E+10 | 0.864253E+11 | 21601.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.553306E+10 | 0.472299E+11 | 2871.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.480813E+10 | 0.543329E+11 | 51550499.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320997E+10 | 0.138355E+11 | 0.517225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293526E+10 | 0.158062E+11 | 0.176151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553741E+11 | 0.406296E+12 | 0.871748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278748E+10 | 0.716560E+10 | 2871.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.776525E+10 | 0.864253E+11 | 0.305758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.120964E+11 | 0.162015E+11 | 372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105377E+11 | 0.896401E+10 | 28896.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121563E+11 | 0.100962E+11 | 1063260.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.973540E+10 | 0.220655E+11 | 1569.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111137E+11 | 0.212420E+11 | 492.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.796680E+10 | 0.385478E+11 | 2112.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116293E+11 | 0.528255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134494E+11 | 0.600294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.900429E+10 | 0.357270E+11 | 30.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105734E+11 | 0.473251E+11 | 1657.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119274E+11 | 0.178655E+11 | 1117.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118200E+11 | 0.202930E+11 | 624.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132010E+12 | 0.351183E+12 | 1100135.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.796680E+10 | 0.896401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134494E+11 | 0.600294E+11 | 1063260.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109634E+12 | 0.802613E+10 | 0.00 | 0.00 | 0.00 | 0.647504E+11 | 0.00 | 0.00 |
February | 0.990242E+11 | 0.744384E+10 | 0.00 | 0.00 | 0.00 | 0.550838E+11 | 0.00 | 0.00 |
March | 0.109634E+12 | 0.398588E+11 | 0.00 | 0.00 | 0.00 | 0.467416E+11 | 0.00 | 0.00 |
April | 0.106097E+12 | 0.245355E+12 | 0.00 | 0.00 | 0.00 | 0.153301E+11 | 0.00 | 0.00 |
May | 0.109634E+12 | 0.899389E+09 | 0.00 | 0.00 | 0.00 | 0.483818E+10 | 0.00 | 0.00 |
June | 0.106097E+12 | 0.659318E+11 | 0.00 | 0.00 | 0.00 | 0.305596E+09 | 0.00 | 0.00 |
July | 0.109634E+12 | 0.381008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109634E+12 | 0.856170E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106097E+12 | 0.177342E+11 | 0.00 | 0.00 | 0.00 | 0.422874E+10 | 0.00 | 0.00 |
October | 0.109634E+12 | 0.120452E+12 | 0.00 | 0.00 | 0.00 | 0.582450E+11 | 0.00 | 0.00 |
November | 0.106097E+12 | 0.637070E+11 | 0.00 | 0.00 | 0.00 | 0.815413E+11 | 0.00 | 0.00 |
December | 0.109634E+12 | 0.177991E+12 | 0.00 | 0.00 | 0.00 | 0.147238E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.129085E+13 | 0.198458E+13 | 0.00 | 0.00 | 0.00 | 0.478303E+12 | 0.00 | 0.00 |
Minimum of Months | 0.990242E+11 | 0.899389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109634E+12 | 0.856170E+12 | 0.00 | 0.00 | 0.00 | 0.147238E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142853E+10 | 0.524669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129028E+10 | 0.941775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142853E+10 | 0.155654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138245E+10 | 0.202325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142853E+10 | 0.560537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138245E+10 | 0.106316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142853E+10 | 0.162670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142853E+10 | 0.212802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138245E+10 | 0.572502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142853E+10 | 0.109789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138245E+10 | 0.152241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142853E+10 | 0.206891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168198E+11 | 0.156864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129028E+10 | 0.524669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142853E+10 | 0.212802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136408E+11 | 0.409687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123207E+11 | 0.824985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136408E+11 | 0.141322E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132008E+11 | 0.188841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136408E+11 | 0.490795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132008E+11 | 0.982582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136408E+11 | 0.153410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136408E+11 | 0.201818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132008E+11 | 0.508028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136408E+11 | 0.100104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132008E+11 | 0.138475E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136408E+11 | 0.189306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160610E+12 | 0.143488E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123207E+11 | 0.409687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136408E+11 | 0.201818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138624E+10 | 0.290170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125209E+10 | 0.730528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138624E+10 | 0.133005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134152E+10 | 0.184642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138624E+10 | 0.448340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134152E+10 | 0.965004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138624E+10 | 0.152746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138624E+10 | 0.200921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134152E+10 | 0.482098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138624E+10 | 0.960567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134152E+10 | 0.129932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138624E+10 | 0.178220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163218E+11 | 0.136714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125209E+10 | 0.290170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138624E+10 | 0.200921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.594262E+10 | 0.390002E+09 | 0.214056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582195E+10 | 44854781.84 | 0.120058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768434E+10 | 0.179524E+09 | 0.142555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.964074E+10 | 4912789.11 | 0.317720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.716077E+10 | 3745.70 | 0.280624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.874665E+10 | 1820.10 | 0.509381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105522E+11 | 5743.12 | 0.929980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124771E+11 | 25135.80 | 0.114054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.813856E+10 | 4187.39 | 0.579903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.882130E+10 | 10165.76 | 0.747789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.769326E+10 | 7070.81 | 0.249936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762513E+10 | 87869065.36 | 0.288812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100305E+12 | 0.707220E+09 | 0.552136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.582195E+10 | 1820.10 | 0.120058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124771E+11 | 0.390002E+09 | 0.114054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.378236E+11 | 0.821463E+10 | 0.228955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355482E+11 | 0.169197E+10 | 0.130324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420931E+11 | 0.613632E+10 | 0.135732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.514879E+11 | 0.182804E+09 | 0.225478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.510636E+11 | 36066364.41 | 0.232424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.586711E+11 | 0.00 | 0.402723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656673E+11 | 0.00 | 0.692662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.752794E+11 | 0.00 | 0.817380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.589196E+11 | 0.00 | 0.482204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.541791E+11 | 14354281.94 | 0.565784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.423080E+11 | 0.223789E+09 | 0.238333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387163E+11 | 0.458517E+10 | 0.258017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611757E+12 | 0.210851E+11 | 0.441002E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355482E+11 | 0.00 | 0.130324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.752794E+11 | 0.821463E+10 | 0.817380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.292717E+10 | 0.305758E+10 | 0.128754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278748E+10 | 0.116122E+10 | 0.716560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335698E+10 | 0.199452E+10 | 0.893663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.467557E+10 | 0.145074E+09 | 0.218585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.465389E+10 | 28763160.54 | 0.224028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583050E+10 | 6062.74 | 0.414600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.689082E+10 | 5259.11 | 0.739668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.776525E+10 | 21601.41 | 0.864253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.553306E+10 | 2871.95 | 0.472299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.480813E+10 | 51550499.83 | 0.543329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320997E+10 | 0.517225E+09 | 0.138355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293526E+10 | 0.176151E+10 | 0.158062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553741E+11 | 0.871748E+10 | 0.406296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278748E+10 | 2871.95 | 0.716560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.776525E+10 | 0.305758E+10 | 0.864253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.120964E+11 | 372.84 | 0.162015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105377E+11 | 28896.91 | 0.896401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121563E+11 | 1063260.82 | 0.100962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.973540E+10 | 1569.27 | 0.220655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111137E+11 | 492.77 | 0.212420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.796680E+10 | 2112.72 | 0.385478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116293E+11 | 0.00 | 0.528255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134494E+11 | 0.00 | 0.600294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.900429E+10 | 30.98 | 0.357270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105734E+11 | 1657.67 | 0.473251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119274E+11 | 1117.05 | 0.178655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118200E+11 | 624.44 | 0.202930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132010E+12 | 1100135.46 | 0.351183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.796680E+10 | 0.00 | 0.896401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134494E+11 | 1063260.82 | 0.600294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109634E+12 | 0.00 | 0.131143E+11 | 0.00 | 0.508820E+10 | 0.00 | 0.00 | 0.00 | 0.650419E+11 | 0.00 | 0.00 | 0.00 |
February | 0.990242E+11 | 0.00 | 0.122289E+11 | 0.00 | 0.478508E+10 | 0.00 | 0.00 | 0.00 | 0.553318E+11 | 0.00 | 0.00 | 0.00 |
March | 0.109634E+12 | 0.00 | 0.534040E+11 | 0.00 | 0.135453E+11 | 0.00 | 0.00 | 0.00 | 0.469520E+11 | 0.00 | 0.00 | 0.00 |
April | 0.106097E+12 | 0.00 | 0.310450E+12 | 0.00 | 0.650949E+11 | 0.00 | 0.00 | 0.00 | 0.153992E+11 | 0.00 | 0.00 | 0.00 |
May | 0.109634E+12 | 0.00 | 0.393456E+10 | 0.00 | 0.303517E+10 | 0.00 | 0.00 | 0.00 | 0.485996E+10 | 0.00 | 0.00 | 0.00 |
June | 0.106097E+12 | 0.00 | 0.865513E+11 | 0.00 | 0.206195E+11 | 0.00 | 0.00 | 0.00 | 0.306972E+09 | 0.00 | 0.00 | 0.00 |
July | 0.109634E+12 | 0.00 | 0.479745E+12 | 0.00 | 0.987367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109634E+12 | 0.00 | 0.106530E+13 | 0.00 | 0.209133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106097E+12 | 0.00 | 0.263653E+11 | 0.00 | 0.863114E+10 | 0.00 | 0.00 | 0.00 | 0.424777E+10 | 0.00 | 0.00 | 0.00 |
October | 0.109634E+12 | 0.00 | 0.158905E+12 | 0.00 | 0.384530E+11 | 0.00 | 0.00 | 0.00 | 0.585072E+11 | 0.00 | 0.00 | 0.00 |
November | 0.106097E+12 | 0.00 | 0.845997E+11 | 0.00 | 0.208927E+11 | 0.00 | 0.00 | 0.00 | 0.819083E+11 | 0.00 | 0.00 | 0.00 |
December | 0.109634E+12 | 0.00 | 0.231639E+12 | 0.00 | 0.536485E+11 | 0.00 | 0.00 | 0.00 | 0.147901E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129085E+13 | 0.00 | 0.252624E+13 | 0.00 | 0.541663E+12 | 0.00 | 0.00 | 0.00 | 0.480456E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.990242E+11 | 0.00 | 0.393456E+10 | 0.00 | 0.303517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109634E+12 | 0.00 | 0.106530E+13 | 0.00 | 0.209133E+12 | 0.00 | 0.00 | 0.00 | 0.147901E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142853E+10 | 0.00 | 0.646547E+10 | 0.00 | 0.121878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129028E+10 | 0.00 | 0.114487E+11 | 0.00 | 0.203093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142853E+10 | 0.00 | 0.187812E+11 | 0.00 | 0.321583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138245E+10 | 0.00 | 0.243875E+11 | 0.00 | 0.415502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142853E+10 | 0.00 | 0.687911E+10 | 0.00 | 0.127373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138245E+10 | 0.00 | 0.129728E+11 | 0.00 | 0.234118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142853E+10 | 0.00 | 0.199170E+11 | 0.00 | 0.365002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142853E+10 | 0.00 | 0.261138E+11 | 0.00 | 0.483362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138245E+10 | 0.00 | 0.706766E+10 | 0.00 | 0.134263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142853E+10 | 0.00 | 0.135375E+11 | 0.00 | 0.255869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138245E+10 | 0.00 | 0.184252E+11 | 0.00 | 0.320109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142853E+10 | 0.00 | 0.249917E+11 | 0.00 | 0.430264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168198E+11 | 0.00 | 0.190988E+12 | 0.00 | 0.341242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129028E+10 | 0.00 | 0.646547E+10 | 0.00 | 0.121878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142853E+10 | 0.00 | 0.261138E+11 | 0.00 | 0.483362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136408E+11 | 0.00 | 0.506478E+11 | 0.00 | 0.967913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123207E+11 | 0.00 | 0.100441E+12 | 0.00 | 0.179424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136408E+11 | 0.00 | 0.170702E+12 | 0.00 | 0.293793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132008E+11 | 0.00 | 0.227760E+12 | 0.00 | 0.389187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136408E+11 | 0.00 | 0.603130E+11 | 0.00 | 0.112335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132008E+11 | 0.00 | 0.119976E+12 | 0.00 | 0.217174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136408E+11 | 0.00 | 0.187898E+12 | 0.00 | 0.344880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136408E+11 | 0.00 | 0.247714E+12 | 0.00 | 0.458958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132008E+11 | 0.00 | 0.627989E+11 | 0.00 | 0.119961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136408E+11 | 0.00 | 0.123572E+12 | 0.00 | 0.234685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132008E+11 | 0.00 | 0.167772E+12 | 0.00 | 0.292974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136408E+11 | 0.00 | 0.228943E+12 | 0.00 | 0.396363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160610E+12 | 0.00 | 0.174854E+13 | 0.00 | 0.313653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123207E+11 | 0.00 | 0.506478E+11 | 0.00 | 0.967913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136408E+11 | 0.00 | 0.247714E+12 | 0.00 | 0.458958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138624E+10 | 0.00 | 0.360521E+10 | 0.00 | 0.703512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125209E+10 | 0.00 | 0.891302E+10 | 0.00 | 0.160774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138624E+10 | 0.00 | 0.160893E+11 | 0.00 | 0.278882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134152E+10 | 0.00 | 0.222918E+11 | 0.00 | 0.382762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138624E+10 | 0.00 | 0.551881E+10 | 0.00 | 0.103542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134152E+10 | 0.00 | 0.117922E+11 | 0.00 | 0.214220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138624E+10 | 0.00 | 0.187209E+11 | 0.00 | 0.344628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138624E+10 | 0.00 | 0.246783E+11 | 0.00 | 0.458624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134152E+10 | 0.00 | 0.596852E+10 | 0.00 | 0.114754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138624E+10 | 0.00 | 0.118762E+11 | 0.00 | 0.227057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134152E+10 | 0.00 | 0.157677E+11 | 0.00 | 0.277452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138624E+10 | 0.00 | 0.215949E+11 | 0.00 | 0.377287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163218E+11 | 0.00 | 0.166817E+12 | 0.00 | 0.301033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125209E+10 | 0.00 | 0.360521E+10 | 0.00 | 0.703512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138624E+10 | 0.00 | 0.246783E+11 | 0.00 | 0.458624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.118800E+09 | 0.00 | 0.114764E+09 | 0.00 | 0.00 | 0.533731E+11 | 0.00 | 0.99 |
February | 0.00 | 7885089.77 | 0.00 | 96187674.19 | 0.00 | 0.00 | 0.506230E+11 | 0.00 | 0.98 |
March | 0.00 | 40587550.25 | 0.00 | 0.113982E+09 | 0.00 | 0.00 | 0.601239E+11 | 0.00 | 1.01 |
April | 0.00 | 0.110901E+09 | 0.00 | 0.107699E+09 | 0.00 | 0.00 | 0.420901E+11 | 0.00 | 1.00 |
May | 0.00 | 17994490.89 | 0.00 | 0.111511E+09 | 0.00 | 0.00 | 0.448177E+11 | 0.00 | 1.07 |
June | 0.00 | 0.973888E+09 | 0.00 | 0.108601E+09 | 0.00 | 0.00 | 0.260837E+11 | 0.00 | 0.98 |
July | 0.00 | 0.369998E+10 | 0.00 | 97748278.00 | 0.00 | 0.00 | 0.189397E+11 | 0.00 | 1.03 |
August | 0.00 | 0.457413E+10 | 0.00 | 95452582.22 | 0.00 | 0.00 | 0.200796E+11 | 0.00 | 1.16 |
September | 0.00 | 0.141995E+10 | 0.00 | 0.101643E+09 | 0.00 | 0.00 | 0.264751E+11 | 0.00 | 1.01 |
October | 0.00 | 0.372883E+10 | 0.00 | 0.111162E+09 | 0.00 | 0.00 | 0.263274E+11 | 0.00 | 0.93 |
November | 0.00 | 9146633.16 | 0.00 | 0.118696E+09 | 0.00 | 0.00 | 0.530783E+11 | 0.00 | 1.09 |
December | 0.00 | 76001.20 | 0.00 | 0.114411E+09 | 0.00 | 0.00 | 0.495660E+11 | 0.00 | 0.98 |
Annual Sum or Average | 0.00 | 0.147022E+11 | 0.00 | 0.129186E+10 | 0.00 | 0.00 | 0.471578E+12 | 0.00 | 1.02 |
Minimum of Months | 0.00 | 76001.20 | 0.00 | 95452582.22 | 0.00 | 0.00 | 0.189397E+11 | 0.00 | 0.93 |
Maximum of Months | 0.00 | 0.457413E+10 | 0.00 | 0.118696E+09 | 0.00 | 0.00 | 0.601239E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.282931E+10 | 58445505.85 | 0.00 | 93974474.51 | 19465392.96 | 0.00 | 0.427690E+11 | 0.00 | 0.75 |
February | 0.254531E+10 | 16740189.81 | 0.00 | 86133509.71 | 0.00 | 0.00 | 0.445296E+11 | 0.00 | 0.81 |
March | 0.235518E+10 | 0.00 | 0.00 | 0.107146E+09 | 15660101.98 | 0.00 | 0.563003E+11 | 0.00 | 0.90 |
April | 0.559915E+10 | 7701462.62 | 0.00 | 0.106841E+09 | 41479709.09 | 0.00 | 0.458219E+11 | 0.00 | 1.04 |
May | 0.330050E+10 | 35033024.27 | 0.00 | 94372037.32 | 0.00 | 0.00 | 0.419420E+11 | 0.00 | 0.93 |
June | 0.266395E+10 | 0.378370E+09 | 0.00 | 99725350.53 | 0.00 | 0.00 | 0.343112E+11 | 0.00 | 1.06 |
July | 0.656361E+10 | 0.379477E+10 | 0.00 | 72442236.52 | 0.282164E+09 | 0.00 | 0.171689E+11 | 0.00 | 1.08 |
August | 0.694627E+10 | 0.523332E+10 | 0.00 | 68182412.77 | 0.319404E+09 | 0.00 | 0.157241E+11 | 0.00 | 1.20 |
September | 0.201905E+10 | 0.106554E+10 | 0.00 | 84254917.08 | 54802745.66 | 0.00 | 0.275304E+11 | 0.00 | 0.93 |
October | 0.217783E+10 | 0.301874E+10 | 0.00 | 84573095.87 | 0.242339E+09 | 0.00 | 0.270235E+11 | 0.00 | 0.91 |
November | 0.293563E+10 | 2901200.90 | 0.00 | 0.106829E+09 | 14290412.10 | 0.00 | 0.485324E+11 | 0.00 | 0.93 |
December | 0.389935E+10 | 2028013.83 | 0.00 | 0.110230E+09 | 0.00 | 0.00 | 0.463409E+11 | 0.00 | 0.87 |
Annual Sum or Average | 0.438351E+11 | 0.136136E+11 | 0.00 | 0.111470E+10 | 0.989606E+09 | 0.00 | 0.447994E+12 | 0.00 | 0.95 |
Minimum of Months | 0.201905E+10 | 0.00 | 0.00 | 68182412.77 | 0.00 | 0.00 | 0.157241E+11 | 0.00 | 0.75 |
Maximum of Months | 0.694627E+10 | 0.523332E+10 | 0.00 | 0.110230E+09 | 0.319404E+09 | 0.00 | 0.563003E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.448682E+11 | 0.109672E+09 | 0.00 | 0.552879E+09 | 0.595552E+09 | 0.00 | 0.245636E+12 | 0.00 | 0.47 |
February | 0.353988E+11 | 0.171134E+09 | 0.00 | 0.507468E+09 | 0.00 | 0.00 | 0.276747E+12 | 0.00 | 0.54 |
March | 0.321363E+11 | 0.00 | 0.00 | 0.600870E+09 | 0.312590E+09 | 0.00 | 0.348451E+12 | 0.00 | 0.58 |
April | 0.309840E+11 | 51271778.59 | 0.00 | 0.634612E+09 | 0.697052E+09 | 0.00 | 0.301595E+12 | 0.00 | 0.70 |
May | 0.283145E+11 | 0.362226E+09 | 0.00 | 0.698394E+09 | 0.00 | 0.00 | 0.326334E+12 | 0.00 | 0.74 |
June | 0.198224E+11 | 0.229967E+10 | 0.00 | 0.740628E+09 | 455455.99 | 0.00 | 0.259888E+12 | 0.00 | 0.82 |
July | 0.230116E+11 | 0.253845E+11 | 0.00 | 0.551214E+09 | 0.263873E+10 | 0.00 | 0.128397E+12 | 0.00 | 0.77 |
August | 0.117688E+11 | 0.325940E+11 | 0.00 | 0.571883E+09 | 0.310265E+10 | 0.00 | 0.123363E+12 | 0.00 | 0.81 |
September | 0.214192E+11 | 0.926917E+10 | 0.00 | 0.629463E+09 | 0.581793E+09 | 0.00 | 0.209533E+12 | 0.00 | 0.74 |
October | 0.169193E+11 | 0.207571E+11 | 0.00 | 0.570515E+09 | 0.299782E+10 | 0.00 | 0.191933E+12 | 0.00 | 0.66 |
November | 0.277032E+11 | 4974767.84 | 0.00 | 0.628361E+09 | 0.157603E+09 | 0.00 | 0.280973E+12 | 0.00 | 0.54 |
December | 0.397692E+11 | 15471336.04 | 0.00 | 0.569194E+09 | 0.00 | 0.00 | 0.239894E+12 | 0.00 | 0.48 |
Annual Sum or Average | 0.332115E+12 | 0.910192E+11 | 0.00 | 0.725548E+10 | 0.110842E+11 | 0.00 | 0.293274E+13 | 0.00 | 0.66 |
Minimum of Months | 0.117688E+11 | 0.00 | 0.00 | 0.507468E+09 | 0.00 | 0.00 | 0.123363E+12 | 0.00 | 0.47 |
Maximum of Months | 0.448682E+11 | 0.325940E+11 | 0.00 | 0.740628E+09 | 0.310265E+10 | 0.00 | 0.348451E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132849E+11 | 2287939.52 | 0.00 | 22266349.88 | 46997507.25 | 0.153128E+09 | 0.122164E+11 | 0.00 | 0.45 |
February | 0.109461E+11 | 5152917.57 | 0.00 | 24262778.46 | 0.00 | 0.00 | 0.159475E+11 | 0.00 | 0.49 |
March | 0.112150E+11 | 0.00 | 0.00 | 30979201.87 | 36212775.44 | 0.00 | 0.216183E+11 | 0.00 | 0.52 |
April | 0.675503E+10 | 254350.53 | 0.00 | 45638966.82 | 38217570.73 | 0.00 | 0.243915E+11 | 0.00 | 0.66 |
May | 0.686023E+10 | 15161229.86 | 0.00 | 51294213.54 | 0.00 | 0.00 | 0.267675E+11 | 0.00 | 0.70 |
June | 0.336204E+10 | 0.121407E+09 | 0.00 | 62811584.06 | 0.00 | 0.00 | 0.247912E+11 | 0.00 | 0.82 |
July | 0.262089E+10 | 0.220187E+10 | 0.00 | 50255146.67 | 0.172792E+09 | 0.00 | 0.126846E+11 | 0.00 | 0.79 |
August | 0.115654E+10 | 0.294659E+10 | 0.00 | 51487435.32 | 0.200955E+09 | 0.00 | 0.118390E+11 | 0.00 | 0.83 |
September | 0.382445E+10 | 0.693242E+09 | 0.00 | 50124750.84 | 43342236.95 | 0.00 | 0.179664E+11 | 0.00 | 0.71 |
October | 0.475778E+10 | 0.182956E+10 | 0.00 | 37797337.09 | 0.242816E+09 | 0.00 | 0.126673E+11 | 0.00 | 0.62 |
November | 0.929733E+10 | 0.00 | 0.00 | 31496720.59 | 2358033.29 | 0.00 | 0.182755E+11 | 0.00 | 0.52 |
December | 0.119249E+11 | 315381.91 | 0.00 | 24058639.23 | 1868872.50 | 1316224.94 | 0.122950E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.860052E+11 | 0.781584E+10 | 0.00 | 0.482473E+09 | 0.785560E+09 | 0.154444E+09 | 0.211460E+12 | 0.00 | 0.63 |
Minimum of Months | 0.115654E+10 | 0.00 | 0.00 | 22266349.88 | 0.00 | 0.00 | 0.118390E+11 | 0.00 | 0.45 |
Maximum of Months | 0.132849E+11 | 0.294659E+10 | 0.00 | 62811584.06 | 0.242816E+09 | 0.153128E+09 | 0.267675E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194086E+10 | 6938843.15 | 0.00 | 4342840.53 | 2499077.01 | 0.00 | 0.199528E+10 | 0.00 | 0.53 |
February | 0.166527E+10 | 2001446.37 | 0.00 | 4599601.73 | 0.00 | 0.00 | 0.259889E+10 | 0.00 | 0.60 |
March | 0.155173E+10 | 0.00 | 0.00 | 6478602.16 | 1963102.42 | 0.00 | 0.383440E+10 | 0.00 | 0.69 |
April | 0.122766E+10 | 1004810.84 | 0.00 | 8610286.54 | 5199769.28 | 0.00 | 0.411713E+10 | 0.00 | 0.92 |
May | 0.979327E+09 | 5103658.54 | 0.00 | 8827226.02 | 0.00 | 0.00 | 0.420649E+10 | 0.00 | 0.89 |
June | 0.473824E+09 | 57949770.87 | 0.00 | 11552204.56 | 0.00 | 0.00 | 0.415951E+10 | 0.00 | 1.13 |
July | 0.894242E+09 | 0.620334E+09 | 0.00 | 8256079.06 | 35371225.03 | 0.00 | 0.205125E+10 | 0.00 | 1.19 |
August | 0.912653E+09 | 0.798021E+09 | 0.00 | 7229808.28 | 40039527.57 | 0.00 | 0.165223E+10 | 0.00 | 1.23 |
September | 0.572784E+09 | 0.168350E+09 | 0.00 | 7269369.80 | 6869904.34 | 0.00 | 0.252383E+10 | 0.00 | 0.86 |
October | 0.691344E+09 | 0.445027E+09 | 0.00 | 6430998.63 | 30444945.27 | 0.00 | 0.209503E+10 | 0.00 | 0.80 |
November | 0.140161E+10 | 323575.62 | 0.00 | 6271163.64 | 1791402.29 | 0.00 | 0.311867E+10 | 0.00 | 0.68 |
December | 0.167139E+10 | 221447.92 | 0.00 | 5820311.18 | 0.00 | 0.00 | 0.247726E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.139827E+11 | 0.210528E+10 | 0.00 | 85688492.12 | 0.124179E+09 | 0.00 | 0.348300E+11 | 0.00 | 0.85 |
Minimum of Months | 0.473824E+09 | 0.00 | 0.00 | 4342840.53 | 0.00 | 0.00 | 0.165223E+10 | 0.00 | 0.53 |
Maximum of Months | 0.194086E+10 | 0.798021E+09 | 0.00 | 11552204.56 | 40039527.57 | 0.00 | 0.420649E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.960378E+09 | 5644463.32 | 0.00 | 5789561.46 | 1610481.16 | 0.00 | 0.264744E+10 | 0.00 | 0.75 |
February | 0.945112E+09 | 1503892.71 | 0.00 | 5162401.96 | 0.00 | 0.00 | 0.268295E+10 | 0.00 | 0.80 |
March | 0.934447E+09 | 220220.34 | 0.00 | 6922658.80 | 1124093.68 | 0.00 | 0.357850E+10 | 0.00 | 0.93 |
April | 0.817095E+09 | 2116716.35 | 0.00 | 9573069.24 | 2654726.81 | 0.00 | 0.414497E+10 | 0.00 | 1.33 |
May | 0.524266E+09 | 5094175.27 | 0.00 | 9457187.52 | 0.00 | 0.00 | 0.416830E+10 | 0.00 | 1.26 |
June | 0.335739E+09 | 47439449.48 | 0.00 | 10640586.12 | 0.00 | 0.00 | 0.344009E+10 | 0.00 | 1.49 |
July | 0.546256E+09 | 0.536335E+09 | 0.00 | 8880275.27 | 12932437.88 | 0.00 | 0.198750E+10 | 0.00 | 1.63 |
August | 0.607344E+09 | 0.783961E+09 | 0.00 | 7239735.75 | 15040502.77 | 0.00 | 0.156035E+10 | 0.00 | 1.72 |
September | 0.328366E+09 | 0.131187E+09 | 0.00 | 7960234.14 | 4427175.10 | 0.00 | 0.247748E+10 | 0.00 | 1.22 |
October | 0.400986E+09 | 0.335335E+09 | 0.00 | 6322390.52 | 19293347.01 | 0.00 | 0.204772E+10 | 0.00 | 1.02 |
November | 0.843671E+09 | 235188.06 | 0.00 | 6358778.47 | 1154434.07 | 0.00 | 0.293098E+10 | 0.00 | 0.87 |
December | 0.101418E+10 | 201224.07 | 0.00 | 5854216.98 | 0.00 | 0.00 | 0.233871E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.825784E+10 | 0.184927E+10 | 0.00 | 90161096.24 | 58237198.48 | 0.00 | 0.340050E+11 | 0.00 | 1.15 |
Minimum of Months | 0.328366E+09 | 201224.07 | 0.00 | 5162401.96 | 0.00 | 0.00 | 0.156035E+10 | 0.00 | 0.75 |
Maximum of Months | 0.101418E+10 | 0.783961E+09 | 0.00 | 10640586.12 | 19293347.01 | 0.00 | 0.416830E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.990839E+09 | 38568635.84 | 0.00 | 20416158.94 | 1971210.79 | 0.00 | 0.803906E+10 | 0.00 | 1.35 |
February | 0.102304E+10 | 6110795.60 | 0.00 | 14933267.00 | 0.00 | 0.00 | 0.675471E+10 | 0.00 | 1.22 |
March | 0.124985E+10 | 3845717.46 | 0.00 | 13434650.22 | 77176.19 | 0.00 | 0.680885E+10 | 0.00 | 1.16 |
April | 0.123565E+10 | 6850759.01 | 0.00 | 13534773.12 | 1181116.42 | 0.00 | 0.572487E+10 | 0.00 | 1.29 |
May | 0.121061E+10 | 6524986.23 | 0.00 | 9290125.39 | 0.00 | 0.00 | 0.416390E+10 | 0.00 | 0.96 |
June | 0.645100E+09 | 66683065.76 | 0.00 | 10320376.34 | 0.00 | 0.00 | 0.368000E+10 | 0.00 | 1.10 |
July | 0.904355E+09 | 0.711399E+09 | 0.00 | 7765598.18 | 27129993.91 | 0.00 | 0.191774E+10 | 0.00 | 1.22 |
August | 0.908017E+09 | 0.113079E+10 | 0.00 | 8844160.40 | 26343400.11 | 0.00 | 0.193694E+10 | 0.00 | 1.53 |
September | 0.416701E+09 | 0.278111E+09 | 0.00 | 14322099.14 | 6397204.41 | 0.00 | 0.412642E+10 | 0.00 | 1.41 |
October | 0.509226E+09 | 0.846158E+09 | 0.00 | 15780420.99 | 13174742.89 | 0.00 | 0.382883E+10 | 0.00 | 1.37 |
November | 0.643638E+09 | 5295790.56 | 0.00 | 22043244.40 | 146810.92 | 0.00 | 0.852935E+10 | 0.00 | 1.52 |
December | 0.756853E+09 | 632202.92 | 0.00 | 26992577.57 | 0.00 | 0.00 | 0.839087E+10 | 0.00 | 1.50 |
Annual Sum or Average | 0.104939E+11 | 0.310097E+10 | 0.00 | 0.177677E+09 | 76421655.65 | 0.00 | 0.639015E+11 | 0.00 | 1.30 |
Minimum of Months | 0.416701E+09 | 632202.92 | 0.00 | 7765598.18 | 0.00 | 0.00 | 0.191774E+10 | 0.00 | 0.96 |
Maximum of Months | 0.124985E+10 | 0.113079E+10 | 0.00 | 26992577.57 | 27129993.91 | 0.00 | 0.852935E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.481502E+09 | 16218222.22 | 0.00 | 8530038.44 | 1264558.60 | 0.00 | 0.393578E+10 | 0.00 | 1.00 |
February | 0.197919E+09 | 2928288.67 | 0.00 | 10942759.12 | 0.00 | 0.00 | 0.558624E+10 | 0.00 | 1.33 |
March | 0.140887E+09 | 1146030.57 | 0.00 | 15781533.02 | 314055.59 | 0.00 | 0.825284E+10 | 0.00 | 1.70 |
April | 0.190620E+09 | 9057582.15 | 0.00 | 24250599.88 | 128691.34 | 0.00 | 0.903941E+10 | 0.00 | 2.46 |
May | 0.195492E+09 | 5202470.21 | 0.00 | 15498492.13 | 0.00 | 0.00 | 0.633735E+10 | 0.00 | 1.78 |
June | 0.131348E+09 | 63456266.21 | 0.00 | 18788504.23 | 0.00 | 0.00 | 0.617077E+10 | 0.00 | 2.40 |
July | 0.271352E+09 | 0.941339E+09 | 0.00 | 19025385.28 | 4580511.72 | 0.00 | 0.379277E+10 | 0.00 | 2.61 |
August | 0.282419E+09 | 0.124558E+10 | 0.00 | 18190854.17 | 2991459.90 | 0.00 | 0.345584E+10 | 0.00 | 2.95 |
September | 0.107923E+09 | 0.184844E+09 | 0.00 | 14126960.58 | 1854762.81 | 0.00 | 0.413182E+10 | 0.00 | 1.80 |
October | 0.139456E+09 | 0.520133E+09 | 0.00 | 12333720.17 | 7121087.55 | 0.00 | 0.352640E+10 | 0.00 | 1.60 |
November | 0.172197E+09 | 3936243.25 | 0.00 | 15208577.82 | 101963.40 | 0.00 | 0.673017E+10 | 0.00 | 1.64 |
December | 0.202729E+09 | 374027.61 | 0.00 | 17223142.87 | 0.00 | 0.00 | 0.667886E+10 | 0.00 | 1.60 |
Annual Sum or Average | 0.251384E+10 | 0.299421E+10 | 0.00 | 0.189901E+09 | 18357090.91 | 0.00 | 0.676383E+11 | 0.00 | 1.91 |
Minimum of Months | 0.107923E+09 | 374027.61 | 0.00 | 8530038.44 | 0.00 | 0.00 | 0.345584E+10 | 0.00 | 1.00 |
Maximum of Months | 0.481502E+09 | 0.124558E+10 | 0.00 | 24250599.88 | 7121087.55 | 0.00 | 0.903941E+10 | 0.00 | 2.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248540E+11 | 3835489.57 | 0.00 | 11493476.85 | 82688824.36 | 0.754927E+09 | 0.388337E+10 | 0.00 | 0.37 |
February | 0.227988E+11 | 17005347.04 | 0.00 | 13260901.04 | 0.00 | 0.00 | 0.728057E+10 | 0.00 | 0.40 |
March | 0.256482E+11 | 0.00 | 0.00 | 18728268.50 | 39205568.10 | 0.210579E+09 | 0.104792E+11 | 0.00 | 0.44 |
April | 0.171214E+11 | 4548279.70 | 0.00 | 39146965.07 | 89034423.90 | 0.00 | 0.175709E+11 | 0.00 | 0.59 |
May | 0.143313E+11 | 49593143.02 | 0.00 | 55523962.35 | 0.00 | 0.00 | 0.255044E+11 | 0.00 | 0.68 |
June | 0.829117E+10 | 0.343793E+09 | 0.00 | 75558572.97 | 57124.07 | 0.00 | 0.266570E+11 | 0.00 | 0.86 |
July | 0.547710E+10 | 0.423359E+10 | 0.00 | 53041762.37 | 0.330954E+09 | 0.00 | 0.132270E+11 | 0.00 | 0.84 |
August | 0.590271E+10 | 0.486066E+10 | 0.00 | 43108043.67 | 0.389140E+09 | 0.00 | 0.907058E+10 | 0.00 | 0.82 |
September | 0.113650E+11 | 0.145558E+10 | 0.00 | 43158598.47 | 81466618.54 | 0.00 | 0.132793E+11 | 0.00 | 0.67 |
October | 0.127145E+11 | 0.310368E+10 | 0.00 | 29559027.45 | 0.291562E+09 | 0.00 | 0.855413E+10 | 0.00 | 0.57 |
November | 0.214100E+11 | 371529.14 | 0.00 | 18927632.28 | 19803180.66 | 0.00 | 0.795505E+10 | 0.00 | 0.40 |
December | 0.246380E+11 | 841057.07 | 0.00 | 9839889.37 | 624767.85 | 45798529.70 | 0.318194E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.194552E+12 | 0.140735E+11 | 0.00 | 0.411347E+09 | 0.132454E+10 | 0.101130E+10 | 0.146643E+12 | 0.00 | 0.59 |
Minimum of Months | 0.547710E+10 | 0.00 | 0.00 | 9839889.37 | 0.00 | 0.00 | 0.318194E+10 | 0.00 | 0.37 |
Maximum of Months | 0.256482E+11 | 0.486066E+10 | 0.00 | 75558572.97 | 0.389140E+09 | 0.754927E+09 | 0.266570E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105455E+11 | 34603981.97 | 0.00 | 33303695.34 | 13491338.93 | 0.141308E+09 | 0.129391E+11 | 0.00 | 0.47 |
February | 0.100738E+11 | 17845314.91 | 0.00 | 31737105.44 | 0.00 | 0.00 | 0.151317E+11 | 0.00 | 0.54 |
March | 0.105315E+11 | 7654085.08 | 0.00 | 45983377.33 | 20015844.64 | 79565888.82 | 0.210946E+11 | 0.00 | 0.66 |
April | 0.666304E+10 | 26314623.74 | 0.00 | 76572460.89 | 43497436.09 | 0.00 | 0.323811E+11 | 0.00 | 1.07 |
May | 0.611911E+10 | 57506671.51 | 0.00 | 76942016.16 | 0.00 | 0.00 | 0.328104E+11 | 0.00 | 1.06 |
June | 0.369393E+10 | 0.305417E+09 | 0.00 | 94543918.28 | 36931.67 | 0.00 | 0.287214E+11 | 0.00 | 1.30 |
July | 0.230067E+10 | 0.424456E+10 | 0.00 | 87932644.47 | 82490117.17 | 0.00 | 0.184937E+11 | 0.00 | 1.41 |
August | 0.190868E+10 | 0.603902E+10 | 0.00 | 74221153.44 | 0.122793E+09 | 0.00 | 0.148358E+11 | 0.00 | 1.46 |
September | 0.501139E+10 | 0.121664E+10 | 0.00 | 65215763.98 | 51223730.66 | 0.00 | 0.189854E+11 | 0.00 | 1.04 |
October | 0.532126E+10 | 0.273642E+10 | 0.00 | 44873484.52 | 0.178880E+09 | 0.00 | 0.143162E+11 | 0.00 | 0.80 |
November | 0.935472E+10 | 1581412.08 | 0.00 | 38414979.99 | 11533859.34 | 0.00 | 0.159885E+11 | 0.00 | 0.55 |
December | 0.106771E+11 | 1367230.19 | 0.00 | 32598394.05 | 0.00 | 29146410.64 | 0.106185E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.822006E+11 | 0.146889E+11 | 0.00 | 0.702339E+09 | 0.523962E+09 | 0.250020E+09 | 0.236316E+12 | 0.00 | 0.90 |
Minimum of Months | 0.190868E+10 | 1367230.19 | 0.00 | 31737105.44 | 0.00 | 0.00 | 0.106185E+11 | 0.00 | 0.46 |
Maximum of Months | 0.106771E+11 | 0.603902E+10 | 0.00 | 94543918.28 | 0.178880E+09 | 0.141308E+09 | 0.328104E+11 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.997611E+10 | 0.369636E+09 | 0.00 | 0.205039E+09 | 17365914.58 | 0.00 | 0.614109E+11 | 0.00 | 1.05 |
February | 0.119321E+11 | 77628290.48 | 0.00 | 0.137098E+09 | 0.00 | 0.00 | 0.504742E+11 | 0.00 | 0.98 |
March | 0.153878E+11 | 64385163.74 | 0.00 | 0.108390E+09 | 3435177.45 | 94931574.95 | 0.462801E+11 | 0.00 | 0.90 |
April | 0.121762E+11 | 51688020.40 | 0.00 | 0.100646E+09 | 55525357.41 | 0.00 | 0.410784E+11 | 0.00 | 1.01 |
May | 0.138127E+11 | 68213663.83 | 0.00 | 71319743.80 | 0.00 | 0.00 | 0.310327E+11 | 0.00 | 0.81 |
June | 0.964757E+10 | 0.418571E+09 | 0.00 | 75600254.11 | 57247.17 | 0.00 | 0.251913E+11 | 0.00 | 0.89 |
July | 0.608615E+10 | 0.514676E+10 | 0.00 | 55342853.40 | 0.279916E+09 | 0.00 | 0.130428E+11 | 0.00 | 0.92 |
August | 0.392392E+10 | 0.785128E+10 | 0.00 | 71896319.80 | 0.335943E+09 | 0.00 | 0.146355E+11 | 0.00 | 1.16 |
September | 0.654250E+10 | 0.305024E+10 | 0.00 | 0.128893E+09 | 59932581.60 | 0.00 | 0.341698E+11 | 0.00 | 1.29 |
October | 0.612880E+10 | 0.812435E+10 | 0.00 | 0.139144E+09 | 45652159.57 | 0.00 | 0.311232E+11 | 0.00 | 1.20 |
November | 0.783229E+10 | 56007687.95 | 0.00 | 0.200059E+09 | 1752959.81 | 0.00 | 0.608260E+11 | 0.00 | 1.10 |
December | 0.922763E+10 | 8161020.30 | 0.00 | 0.243907E+09 | 0.00 | 0.00 | 0.562341E+11 | 0.00 | 1.08 |
Annual Sum or Average | 0.112674E+12 | 0.252869E+11 | 0.00 | 0.153734E+10 | 0.799581E+09 | 94931574.95 | 0.465499E+12 | 0.00 | 1.03 |
Minimum of Months | 0.392392E+10 | 8161020.30 | 0.00 | 55342853.40 | 0.00 | 0.00 | 0.130428E+11 | 0.00 | 0.81 |
Maximum of Months | 0.153878E+11 | 0.812435E+10 | 0.00 | 0.243907E+09 | 0.335943E+09 | 94931574.95 | 0.614109E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125847E+11 | 93745979.50 | 0.00 | 35634288.13 | 21433253.52 | 7277616.28 | 0.117588E+11 | 0.00 | 0.51 |
February | 0.101162E+11 | 24033359.20 | 0.00 | 40216663.35 | 0.00 | 0.00 | 0.185366E+11 | 0.00 | 0.65 |
March | 0.976532E+10 | 0.00 | 0.00 | 56031353.20 | 25291915.63 | 0.00 | 0.274884E+11 | 0.00 | 0.77 |
April | 0.516891E+10 | 41859074.50 | 0.00 | 0.106579E+09 | 43484960.61 | 0.00 | 0.401256E+11 | 0.00 | 1.29 |
May | 0.482846E+10 | 44558112.98 | 0.00 | 0.102885E+09 | 0.00 | 0.00 | 0.413035E+11 | 0.00 | 1.29 |
June | 0.224436E+10 | 0.315411E+09 | 0.00 | 0.116684E+09 | 36851.33 | 0.00 | 0.385381E+11 | 0.00 | 1.63 |
July | 0.133425E+10 | 0.575794E+10 | 0.00 | 0.109959E+09 | 0.126613E+09 | 0.00 | 0.213571E+11 | 0.00 | 1.64 |
August | 0.913836E+09 | 0.632609E+10 | 0.00 | 96397272.98 | 0.139136E+09 | 0.00 | 0.172269E+11 | 0.00 | 1.68 |
September | 0.294473E+10 | 0.165160E+10 | 0.00 | 92889016.81 | 20342062.27 | 0.00 | 0.267566E+11 | 0.00 | 1.31 |
October | 0.445991E+10 | 0.354193E+10 | 0.00 | 56457213.23 | 86842130.55 | 0.00 | 0.152274E+11 | 0.00 | 0.94 |
November | 0.870899E+10 | 10210168.16 | 0.00 | 51764902.06 | 5786592.75 | 0.00 | 0.188474E+11 | 0.00 | 0.65 |
December | 0.114076E+11 | 1395642.55 | 0.00 | 41183972.69 | 403044.17 | 0.00 | 0.118993E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.744772E+11 | 0.178088E+11 | 0.00 | 0.906681E+09 | 0.469369E+09 | 7277616.28 | 0.289066E+12 | 0.00 | 1.08 |
Minimum of Months | 0.913836E+09 | 0.00 | 0.00 | 35634288.13 | 0.00 | 0.00 | 0.117588E+11 | 0.00 | 0.51 |
Maximum of Months | 0.125847E+11 | 0.632609E+10 | 0.00 | 0.116684E+09 | 0.139136E+09 | 7277616.28 | 0.413035E+11 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223865E+10 | 0.00 | 0.00 | 529974.04 | 6138138.15 | 0.448005E+09 | 0.251697E+09 | 0.00 | 0.40 |
February | 0.221731E+10 | 466033.80 | 0.00 | 600708.47 | 0.00 | 0.202240E+09 | 0.466793E+09 | 0.00 | 0.41 |
March | 0.260380E+10 | 0.00 | 0.00 | 1079428.51 | 4537154.62 | 0.231609E+09 | 0.719815E+09 | 0.00 | 0.44 |
April | 0.166731E+10 | 32230.39 | 0.00 | 3404704.71 | 4788338.52 | 24153386.69 | 0.169307E+10 | 0.00 | 0.57 |
May | 0.151586E+10 | 1983552.70 | 0.00 | 4798576.80 | 0.00 | 1243182.69 | 0.239027E+10 | 0.00 | 0.66 |
June | 0.861740E+09 | 17594672.18 | 0.00 | 7409571.20 | 0.00 | 0.00 | 0.275944E+10 | 0.00 | 0.86 |
July | 0.602569E+09 | 0.363172E+09 | 0.00 | 5550960.36 | 21649356.02 | 0.00 | 0.136721E+10 | 0.00 | 0.87 |
August | 0.536105E+09 | 0.432938E+09 | 0.00 | 4674763.80 | 27747334.70 | 0.00 | 0.974553E+09 | 0.00 | 0.85 |
September | 0.111391E+10 | 0.108106E+09 | 0.00 | 4243763.59 | 7880002.64 | 0.00 | 0.132250E+10 | 0.00 | 0.66 |
October | 0.122712E+10 | 0.263689E+09 | 0.00 | 2436440.70 | 31566115.00 | 16806016.89 | 0.686359E+09 | 0.00 | 0.56 |
November | 0.217045E+10 | 0.00 | 0.00 | 785373.18 | 295441.64 | 0.146088E+09 | 0.552851E+09 | 0.00 | 0.43 |
December | 0.220756E+10 | 23638.95 | 0.00 | 345107.27 | 234153.92 | 0.338195E+09 | 0.176425E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.189624E+11 | 0.118800E+10 | 0.00 | 35859372.64 | 0.104836E+09 | 0.140834E+10 | 0.133610E+11 | 0.00 | 0.59 |
Minimum of Months | 0.536105E+09 | 0.00 | 0.00 | 345107.27 | 0.00 | 0.00 | 0.176425E+09 | 0.00 | 0.40 |
Maximum of Months | 0.260380E+10 | 0.432938E+09 | 0.00 | 7409571.20 | 31566115.00 | 0.448005E+09 | 0.275944E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105315E+10 | 1069753.64 | 0.00 | 2062847.14 | 3023784.05 | 0.133032E+09 | 0.984260E+09 | 0.00 | 0.48 |
February | 0.102754E+10 | 510116.72 | 0.00 | 2403400.96 | 0.00 | 73543516.51 | 0.131841E+10 | 0.00 | 0.56 |
March | 0.115129E+10 | 345176.32 | 0.00 | 3637930.21 | 2682427.22 | 72199822.29 | 0.186869E+10 | 0.00 | 0.66 |
April | 0.692463E+09 | 772935.51 | 0.00 | 7300910.68 | 2665121.50 | 4597774.20 | 0.326906E+10 | 0.00 | 1.09 |
May | 0.685233E+09 | 2788978.08 | 0.00 | 7191914.43 | 0.00 | 290497.72 | 0.329046E+10 | 0.00 | 1.07 |
June | 0.394630E+09 | 17595428.48 | 0.00 | 9667957.17 | 0.00 | 0.00 | 0.312740E+10 | 0.00 | 1.37 |
July | 0.226522E+09 | 0.381622E+09 | 0.00 | 9364050.96 | 3647019.38 | 0.00 | 0.201608E+10 | 0.00 | 1.52 |
August | 0.202615E+09 | 0.573707E+09 | 0.00 | 7887045.44 | 4388226.32 | 0.00 | 0.155026E+10 | 0.00 | 1.59 |
September | 0.508941E+09 | 0.102686E+09 | 0.00 | 6695535.81 | 5011467.67 | 0.00 | 0.199234E+10 | 0.00 | 1.08 |
October | 0.534617E+09 | 0.265555E+09 | 0.00 | 3989207.56 | 16007533.74 | 251691.51 | 0.124736E+10 | 0.00 | 0.81 |
November | 0.947963E+09 | 0.00 | 0.00 | 2793004.80 | 190683.72 | 26471518.20 | 0.137001E+10 | 0.00 | 0.56 |
December | 0.107882E+10 | 30755.59 | 0.00 | 2025146.49 | 143080.12 | 91215681.67 | 0.752013E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.850378E+10 | 0.134668E+10 | 0.00 | 65018951.66 | 37759343.75 | 0.401603E+09 | 0.227863E+11 | 0.00 | 0.94 |
Minimum of Months | 0.202615E+09 | 0.00 | 0.00 | 2025146.49 | 0.00 | 0.00 | 0.752013E+09 | 0.00 | 0.47 |
Maximum of Months | 0.115129E+10 | 0.573707E+09 | 0.00 | 9667957.17 | 16007533.74 | 0.133032E+09 | 0.329046E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.997765E+09 | 34730976.45 | 0.00 | 15933777.09 | 327831.06 | 0.126884E+09 | 0.641733E+10 | 0.00 | 1.19 |
February | 0.117527E+10 | 2431977.85 | 0.00 | 11135700.95 | 0.00 | 73550300.97 | 0.505502E+10 | 0.00 | 1.02 |
March | 0.156013E+10 | 5598381.10 | 0.00 | 8915285.29 | 1301556.63 | 0.131483E+09 | 0.460136E+10 | 0.00 | 0.90 |
April | 0.120707E+10 | 1701145.65 | 0.00 | 9391329.79 | 3520148.99 | 17441306.76 | 0.422449E+10 | 0.00 | 0.98 |
May | 0.144114E+10 | 2687762.24 | 0.00 | 6383150.40 | 0.00 | 6163213.24 | 0.302483E+10 | 0.00 | 0.77 |
June | 0.948711E+09 | 21439405.41 | 0.00 | 7576438.17 | 0.00 | 0.00 | 0.271630E+10 | 0.00 | 0.90 |
July | 0.635994E+09 | 0.429951E+09 | 0.00 | 6160571.22 | 20100955.64 | 0.00 | 0.143027E+10 | 0.00 | 0.95 |
August | 0.392375E+09 | 0.674575E+09 | 0.00 | 8028353.22 | 21145843.10 | 0.00 | 0.159298E+10 | 0.00 | 1.22 |
September | 0.615969E+09 | 0.215244E+09 | 0.00 | 13201679.22 | 6258113.28 | 0.00 | 0.370189E+10 | 0.00 | 1.28 |
October | 0.619002E+09 | 0.721039E+09 | 0.00 | 13122644.44 | 4269331.23 | 0.00 | 0.293896E+10 | 0.00 | 1.21 |
November | 0.937324E+09 | 709573.71 | 0.00 | 16302905.24 | 0.00 | 12363112.00 | 0.646070E+10 | 0.00 | 1.26 |
December | 0.988580E+09 | 1555693.31 | 0.00 | 18705415.35 | 0.00 | 47808740.19 | 0.562423E+10 | 0.00 | 1.21 |
Annual Sum or Average | 0.115193E+11 | 0.211166E+10 | 0.00 | 0.134857E+09 | 56923779.93 | 0.415694E+09 | 0.477884E+11 | 0.00 | 1.07 |
Minimum of Months | 0.392375E+09 | 709573.71 | 0.00 | 6160571.22 | 0.00 | 0.00 | 0.143027E+10 | 0.00 | 0.77 |
Maximum of Months | 0.156013E+10 | 0.721039E+09 | 0.00 | 18705415.35 | 21145843.10 | 0.131483E+09 | 0.646070E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111924E+10 | 7684567.11 | 0.00 | 2721547.86 | 1083326.31 | 0.164810E+09 | 0.133358E+10 | 0.00 | 0.58 |
February | 0.105137E+10 | 830205.82 | 0.00 | 3086529.38 | 0.00 | 44717554.52 | 0.179604E+10 | 0.00 | 0.68 |
March | 0.110496E+10 | 0.00 | 0.00 | 4557941.42 | 2919410.05 | 54782037.99 | 0.269752E+10 | 0.00 | 0.79 |
April | 0.521983E+09 | 2039961.85 | 0.00 | 10225758.97 | 2339249.79 | 9935950.28 | 0.409220E+10 | 0.00 | 1.26 |
May | 0.521590E+09 | 1568743.82 | 0.00 | 9655555.34 | 0.00 | 0.00 | 0.417578E+10 | 0.00 | 1.25 |
June | 0.265339E+09 | 15054124.98 | 0.00 | 11627217.58 | 0.00 | 0.00 | 0.409649E+10 | 0.00 | 1.63 |
July | 0.140010E+09 | 0.488717E+09 | 0.00 | 12279226.17 | 10822967.04 | 0.00 | 0.232265E+10 | 0.00 | 1.69 |
August | 96264920.51 | 0.540947E+09 | 0.00 | 10125894.41 | 10669874.21 | 0.00 | 0.181196E+10 | 0.00 | 1.75 |
September | 0.325862E+09 | 0.116247E+09 | 0.00 | 9470423.13 | 1405553.75 | 0.00 | 0.274491E+10 | 0.00 | 1.29 |
October | 0.474872E+09 | 0.294121E+09 | 0.00 | 5241331.28 | 11165515.17 | 0.00 | 0.139051E+10 | 0.00 | 0.92 |
November | 0.986442E+09 | 27777.04 | 0.00 | 3988724.30 | 172765.50 | 12170861.51 | 0.197111E+10 | 0.00 | 0.73 |
December | 0.109276E+10 | 64188.67 | 0.00 | 3014594.41 | 150665.20 | 78155343.46 | 0.121700E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.770069E+10 | 0.146730E+10 | 0.00 | 85994744.24 | 40729327.00 | 0.364572E+09 | 0.296497E+11 | 0.00 | 1.10 |
Minimum of Months | 96264920.51 | 0.00 | 0.00 | 2721547.86 | 0.00 | 0.00 | 0.121700E+10 | 0.00 | 0.58 |
Maximum of Months | 0.111924E+10 | 0.540947E+09 | 0.00 | 12279226.17 | 11165515.17 | 0.164810E+09 | 0.417578E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 4114812.56 | 0.00 | 0.00 | 0.330917E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8209503.84 | 0.00 | 0.00 | 0.290499E+09 | 0.00 | 0.29 |
March | 0.00 | 19219.66 | 0.00 | 14833679.90 | 0.00 | 0.00 | 0.337455E+09 | 0.00 | 0.31 |
April | 0.00 | 182465.76 | 0.00 | 18453284.83 | 0.00 | 0.00 | 0.197166E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4339368.48 | 0.00 | 0.00 | 0.243241E+09 | 0.00 | 0.29 |
June | 0.00 | 7706537.92 | 0.00 | 8436988.41 | 0.00 | 0.00 | 0.116773E+09 | 0.00 | 0.30 |
July | 0.00 | 60342898.46 | 0.00 | 5654516.64 | 0.00 | 0.00 | 25242418.04 | 0.00 | 0.28 |
August | 0.00 | 77815404.93 | 0.00 | 5885824.91 | 0.00 | 0.00 | 17918120.80 | 0.00 | 0.31 |
September | 0.00 | 13869052.72 | 0.00 | 3325884.05 | 0.00 | 0.00 | 93590787.65 | 0.00 | 0.29 |
October | 0.00 | 23063791.76 | 0.00 | 7026654.68 | 0.00 | 0.00 | 0.146225E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13562197.01 | 0.00 | 0.00 | 0.274391E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18739659.91 | 0.00 | 0.00 | 0.308900E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.182999E+09 | 0.00 | 0.112582E+09 | 0.00 | 0.00 | 0.238232E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3325884.05 | 0.00 | 0.00 | 17918120.80 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 77815404.93 | 0.00 | 18739659.91 | 0.00 | 0.00 | 0.337455E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 32626195.84 | 0.00 | 0.00 | 0.332647E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 73296968.49 | 0.00 | 0.00 | 0.291769E+10 | 0.00 | 0.29 |
March | 0.00 | 161664.91 | 0.00 | 0.136396E+09 | 0.00 | 0.00 | 0.338603E+10 | 0.00 | 0.31 |
April | 0.00 | 1805534.31 | 0.00 | 0.173748E+09 | 0.00 | 0.00 | 0.198113E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 38217178.97 | 0.00 | 0.00 | 0.245307E+10 | 0.00 | 0.29 |
June | 0.00 | 75090405.26 | 0.00 | 78701884.39 | 0.00 | 0.00 | 0.117972E+10 | 0.00 | 0.30 |
July | 0.00 | 0.599279E+09 | 0.00 | 53644660.35 | 0.00 | 0.00 | 0.256451E+09 | 0.00 | 0.28 |
August | 0.00 | 0.775464E+09 | 0.00 | 56352916.93 | 0.00 | 0.00 | 0.181745E+09 | 0.00 | 0.31 |
September | 0.00 | 0.131005E+09 | 0.00 | 29793642.00 | 0.00 | 0.00 | 0.958077E+09 | 0.00 | 0.29 |
October | 0.00 | 0.226898E+09 | 0.00 | 64478774.60 | 0.00 | 0.00 | 0.146997E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.125139E+09 | 0.00 | 0.00 | 0.275366E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.173920E+09 | 0.00 | 0.00 | 0.309782E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.180970E+10 | 0.00 | 0.103631E+10 | 0.00 | 0.00 | 0.239618E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 29793642.00 | 0.00 | 0.00 | 0.181745E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.775464E+09 | 0.00 | 0.173920E+09 | 0.00 | 0.00 | 0.338603E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22132917.38 | 0.00 | 0.00 | 2427499.42 | 0.00 | 0.00 | 0.312592E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6654306.86 | 0.00 | 0.00 | 0.293112E+09 | 0.00 | 0.29 |
March | 0.00 | 16723.44 | 0.00 | 12984998.29 | 0.00 | 0.00 | 0.339594E+09 | 0.00 | 0.31 |
April | 0.00 | 180687.33 | 0.00 | 17090141.94 | 0.00 | 0.00 | 0.198533E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3560375.90 | 0.00 | 0.00 | 0.246190E+09 | 0.00 | 0.29 |
June | 0.00 | 7561199.42 | 0.00 | 7765092.71 | 0.00 | 0.00 | 0.118169E+09 | 0.00 | 0.30 |
July | 0.00 | 59974724.23 | 0.00 | 5334178.40 | 0.00 | 0.00 | 25704675.74 | 0.00 | 0.28 |
August | 0.00 | 77530999.72 | 0.00 | 5598953.18 | 0.00 | 0.00 | 18259816.68 | 0.00 | 0.31 |
September | 0.00 | 13033881.92 | 0.00 | 2823921.75 | 0.00 | 0.00 | 96339466.24 | 0.00 | 0.29 |
October | 0.00 | 22664993.37 | 0.00 | 6162236.30 | 0.00 | 0.00 | 0.147457E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11900038.86 | 0.00 | 0.00 | 0.276234E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16623312.64 | 0.00 | 0.00 | 0.310595E+09 | 0.00 | 0.28 |
Annual Sum or Average | 22132917.38 | 0.180963E+09 | 0.00 | 98925056.24 | 0.00 | 0.00 | 0.238278E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2427499.42 | 0.00 | 0.00 | 18259816.68 | 0.00 | 0.28 |
Maximum of Months | 22132917.38 | 77530999.72 | 0.00 | 17090141.94 | 0.00 | 0.00 | 0.339594E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.526637E+09 | 0.00 | 0.00 | 0.407322E+12 | 0.00 | 17.73 |
February | 0.00 | 0.00 | 0.00 | 0.947766E+09 | 0.00 | 0.00 | 0.583017E+12 | 0.00 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.156221E+10 | 0.00 | 0.00 | 0.845087E+12 | 0.00 | 35.89 |
April | 0.00 | 0.104782E+09 | 0.00 | 0.238615E+10 | 0.00 | 0.00 | 0.817193E+12 | 0.00 | 46.42 |
May | 0.00 | 0.00 | 0.00 | 0.539318E+09 | 0.00 | 0.00 | 0.354587E+12 | 0.00 | 20.44 |
June | 0.00 | 46821997.69 | 0.00 | 0.106747E+10 | 0.00 | 0.00 | 0.509252E+12 | 0.00 | 37.68 |
July | 0.00 | 0.183778E+11 | 0.00 | 0.182237E+10 | 0.00 | 0.00 | 0.476441E+12 | 0.00 | 47.67 |
August | 0.00 | 0.451347E+11 | 0.00 | 0.197684E+10 | 0.00 | 0.00 | 0.272130E+12 | 0.00 | 48.47 |
September | 0.00 | 0.480864E+09 | 0.00 | 0.518363E+09 | 0.00 | 0.00 | 0.327847E+12 | 0.00 | 25.58 |
October | 0.00 | 0.981384E+09 | 0.00 | 0.108800E+10 | 0.00 | 0.00 | 0.535414E+12 | 0.00 | 36.92 |
November | 0.00 | 0.00 | 0.00 | 0.161940E+10 | 0.00 | 0.00 | 0.831325E+12 | 0.00 | 39.27 |
December | 0.00 | 0.00 | 0.00 | 0.225834E+10 | 0.00 | 0.00 | 0.105392E+13 | 0.00 | 43.20 |
Annual Sum or Average | 0.00 | 0.651263E+11 | 0.00 | 0.163129E+11 | 0.00 | 0.00 | 0.701353E+13 | 0.00 | 35.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.518363E+09 | 0.00 | 0.00 | 0.272130E+12 | 0.00 | 17.73 |
Maximum of Months | 0.00 | 0.451347E+11 | 0.00 | 0.238615E+10 | 0.00 | 0.00 | 0.105392E+13 | 0.00 | 48.47 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:53
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.315339E+12 | 0.433633E+10 | 0.00 | 0.230122E+13 | 0.437810E+12 |
February | 0.388831E+12 | 0.518775E+10 | 0.00 | 0.244136E+13 | 0.347526E+12 |
March | 0.542116E+12 | 0.528369E+10 | 0.00 | 0.284029E+13 | 0.496407E+12 |
April | 0.688212E+12 | 0.313938E+10 | 0.00 | 0.265578E+13 | 0.100944E+13 |
May | 0.725152E+12 | 0.376463E+10 | 0.00 | 0.226212E+13 | 0.480748E+12 |
June | 0.710318E+12 | 0.196098E+10 | 0.00 | 0.211495E+13 | 0.930495E+12 |
July | 0.760319E+12 | 0.989441E+09 | 0.00 | 0.155369E+13 | 0.190574E+13 |
August | 0.707418E+12 | 0.103980E+10 | 0.00 | 0.110952E+13 | 0.280254E+13 |
September | 0.549940E+12 | 0.164250E+10 | 0.00 | 0.178566E+13 | 0.907150E+12 |
October | 0.387480E+12 | 0.277421E+10 | 0.00 | 0.196994E+13 | 0.128939E+13 |
November | 0.344901E+12 | 0.434092E+10 | 0.00 | 0.283358E+13 | 0.679099E+12 |
December | 0.284464E+12 | 0.485564E+10 | 0.00 | 0.307089E+13 | 0.957278E+12 |
Annual Sum or Average | 0.640449E+13 | 0.393153E+11 | 0.00 | 0.269390E+14 | 0.122436E+14 |
Minimum of Months | 0.284464E+12 | 0.989441E+09 | 0.00 | 0.110952E+13 | 0.347526E+12 |
Maximum of Months | 0.760319E+12 | 0.528369E+10 | 0.00 | 0.307089E+13 | 0.280254E+13 |