Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:25:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32836.72 | 708.90 | 708.90 |
Net Site Energy | 32836.72 | 708.90 | 708.90 |
Total Source Energy | 103993.89 | 2245.10 | 2245.10 |
Net Source Energy | 103993.89 | 2245.10 | 2245.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6616.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2940.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 929.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2008.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23450.89 |
Humidification | 14.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 279.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32836.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25736.29 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6616.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2940.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 929.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2008.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23450.89 |
Humidification | General | 14.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 279.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6616.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2940.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 929.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2008.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23450.89 |
Humidification | Unassigned | 14.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 279.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 276.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 708.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 276.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Other | 372.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 708.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32836.719 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32836.719 | 100.00 |
Total On-Site and Utility Electric Sources | 32836.719 | 100.00 |
Total Electricity End Uses | 32836.719 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 25736.29 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 25736.29 | 100.00 |
Total Water End Uses | 25736.29 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 4038.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 28-APR-11:50 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 694580.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248658.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54068.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 86931.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18880.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2327571.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 694580.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 248658.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 54068.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 86931.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 18880.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20953.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7779.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1105.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9311.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2943.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6361.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 44.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 886.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 103993.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 201.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 137.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2245.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 201.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 137.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2245.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.48 | 0.386732 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.89 | 0.323124 | 0.275000 | 1.62 | 0.861665 | 0.500000 | 0.001179 |
CORE_MID VAV BOX COMPONENT | 56.02 | 0.339533 | 0.289000 | 16.19 | 0.905422 | 0.500000 | 0.001122 |
CORE_TOP VAV BOX COMPONENT | 5.66 | 0.335955 | 0.286000 | 1.62 | 0.895881 | 0.500000 | 0.001134 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.27 | 0.187788 | 0.160000 | 0.203482 | 0.500767 | 0.500000 | 0.002029 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.07 | 0.143800 | 0.122000 | 0.130573 | 0.383466 | 0.500000 | 0.002650 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.43 | 0.167240 | 0.142000 | 0.202782 | 0.445973 | 0.500000 | 0.002278 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.40 | 0.110119 | 0.094000 | 0.131377 | 0.300000 | 0.500000 | 0.003460 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.60 | 0.189554 | 0.161000 | 2.03 | 0.505478 | 0.500000 | 0.002010 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.17 | 0.367382 | 0.500000 | 0.002766 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.13 | 0.169062 | 0.144000 | 2.03 | 0.450833 | 0.500000 | 0.002254 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.37 | 0.124437 | 0.106000 | 1.31 | 0.331832 | 0.500000 | 0.003062 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.39 | 0.171448 | 0.146000 | 0.203372 | 0.457196 | 0.500000 | 0.002222 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.15 | 0.134154 | 0.114000 | 0.130784 | 0.357745 | 0.500000 | 0.002840 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.54 | 0.155206 | 0.132000 | 0.203117 | 0.413883 | 0.500000 | 0.002455 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.32 | 0.116356 | 0.099000 | 0.130948 | 0.310283 | 0.500000 | 0.003274 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 54039.38 |
CORE_MID VAV BOX REHEAT COIL | 540458.70 |
CORE_TOP VAV BOX REHEAT COIL | 54054.47 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6792.84 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4358.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6769.50 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4385.78 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 101629.06 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 67773.29 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 101496.51 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 56531.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12879.41 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8520.58 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12858.97 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7458.49 |
VAV_BOT WITH REHEAT HEATING COIL | 9601.77 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 |
CAV_BAS HEATING COIL | 246504.63 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 11172.98 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 516.15 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5161.45 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 516.15 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.471856 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.50 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.453781 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.61 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.53 | 2.29 | 11.05 | 2.29 | 10.05 | 10.05 | 0.300000 | 0.227629 | 10.05 |
VAV_MID WITH REHEAT | 53.14 | 22.87 | 106.28 | 22.87 | 94.46 | 94.46 | 0.300000 | 0.242111 | 94.46 |
VAV_TOP WITH REHEAT | 5.53 | 2.29 | 11.06 | 2.45 | 10.73 | 10.73 | 0.300000 | 0.228698 | 10.73 |
CAV_BAS | 0.000000 | 0.000000 | 5.48 | 1.20 | 5.48 | 5.48 | 1.00 | 0.219148 | 5.48 |
AIRLOOP DATACENTER BASEMENT | 24.61 | 24.61 | 24.61 | 24.61 | 24.61 | 24.61 | 1.00 | 0.999992 | 24.61 |
AIRLOOP DATACENTER BOT | 0.471856 | 0.471856 | 0.471856 | 0.471856 | 0.471856 | 0.471856 | 1.00 | 1.00 | 0.471856 |
AIRLOOP DATACENTER MID | 4.50 | 4.50 | 4.50 | 4.50 | 4.50 | 4.50 | 1.00 | 1.00 | 4.50 |
AIRLOOP DATACENTER TOP | 0.453781 | 0.453781 | 0.453781 | 0.453781 | 0.453781 | 0.453781 | 1.00 | 1.00 | 0.453781 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.05 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 94.46 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.73 | |
CAV_BAS_OA_CONTROLLER | 5.48 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.61 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.471856 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.50 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.453781 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.80 | 6.67 | 11.04 | 0.008024 | 0.007000 | 237911.42 | 0.006804 | 10.05 |
VAV_MID WITH REHEAT COOLING COIL | 28.09 | 6.67 | 11.04 | 0.008112 | 0.007000 | 2295411.74 | 0.065648 | 94.46 |
VAV_TOP WITH REHEAT COOLING COIL | 27.57 | 6.67 | 11.05 | 0.007986 | 0.007000 | 249692.36 | 0.007141 | 10.73 |
CAV_BAS COOLING COIL | 27.96 | 6.67 | 11.03 | 0.008275 | 0.007000 | 135020.26 | 0.003862 | 5.48 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.05 |
VAV_MID WITH REHEAT FAN | 94.46 |
VAV_TOP WITH REHEAT FAN | 10.73 |
CAV_BAS FAN | 5.48 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006804 | 0.000070 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.065648 | 0.000007 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007141 | 0.000067 |
CAV_BAS_COOLC_CONTROLLER | 0.003862 | 0.000123 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.61 | 516051.43 | 329295.59 | 0.012638 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.471856 | 9952.01 | 6319.30 | 0.000244 |
AIRLOOP DATACENTER MID COOLING COIL | 4.50 | 94991.39 | 60294.81 | 0.002326 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.453781 | 9581.94 | 6080.75 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.61 | 24.61 | 24.61 | 24.61 | 516051.43 | 516051.43 | 11172.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.471856 | 0.471856 | 0.471856 | 0.471856 | 9952.01 | 9952.01 | 516.15 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.50 | 4.50 | 4.50 | 4.50 | 94991.39 | 94991.39 | 5161.45 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.453781 | 0.453781 | 0.453781 | 0.453781 | 9581.94 | 9581.94 | 516.15 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.61 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.471856 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.50 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.453781 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.61 | 516051.43 | 0.012638 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.471856 | 9952.01 | 0.000244 |
AIRLOOP DATACENTER MID HEATING COIL | 4.50 | 94991.39 | 0.002326 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.453781 | 9581.94 | 0.000235 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000026 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.083455 | 13490.82 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.083455 | 10.01 |
COOLSYS1_SUPPLY | 0.083455 | 10.01 |
SINGLE WATER PLANT LOOP | 0.015443 | 1.85 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.083455 | 0.083455 | 350304.41 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.041728 | 4670.07 |
COOLSYS1 CHILLER2 PUMP | 0.041728 | 4670.07 |
PLANT CIRC PUMP | 0.015443 | 3899.69 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.083455 | 0.042089 | 1471653.38 | 1471653.21 | 0.073927 |
COOLSYS1 CHILLER2 | 0.083455 | 0.042089 | 1471653.38 | 1471653.21 | 0.073927 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015443 | 153335.40 | 77622.70 | 76667.70 | 7004.20 | 46573.62 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 636110.34 | 623823.46 | 0.015443 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.147853 | 17.74 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.147853 | 36242.78 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 56.82 | 1761570.67 | 11.36 | 220196.33 |
TOWERWATERSYS COOLTOWER 2 | 56.82 | 1761570.67 | 11.36 | 220196.33 |
Design Water Flow Rate [m3/s] Equipment # 27 | |
WSHPPLANT OPERATION SCHEME | 0.076315 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1309E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1321E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2756E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2766E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5903E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5431E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1580E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2332E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2977E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3606E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6066E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6560E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5556E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5883E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6239E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0110E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2576E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1206E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2225E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2224E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7703E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6101E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1630E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2571E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3030E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3860E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6116E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6751E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5560E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5892E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1308E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1322E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2755E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2767E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5904E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5430E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3510E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4698E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1851E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3048E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0297E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0949E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6379E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6605E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7168E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7424E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4614E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5672E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5307E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4151E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8851E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0771E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3252E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3782E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1533E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1922E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0104E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0266E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6380E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6608E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4920E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4932E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2886E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2896E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1402E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1409E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5197E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5879E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3112E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3654E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1575E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1953E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5560E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5893E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2700E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1690E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7659E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9711E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5501E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0381E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7703E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6072E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5177E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5850E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3088E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3605E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1536E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1834E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5557E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5883E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4919E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4931E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2885E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2894E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1401E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1406E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9101E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9651E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6550E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6949E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6076E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6224E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6381E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6609E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0075E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4827E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6194E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2600E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8049E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1457E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8851E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0771E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9312E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0285E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6814E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7753E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6258E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6839E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6379E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6604E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0793E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4954E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5602E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6640E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9294E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4364E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3990E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6803E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4413E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5383E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1569E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3241E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2109E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1313E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4843E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6997E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8655E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8859E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2913E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5116E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0465E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1378E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3990E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6800E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6364E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1762E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2002E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8941E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3942E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7652E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4843E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6997E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0903E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.5049E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5734E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6745E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9427E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4449E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4063E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6840E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4457E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5423E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1618E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3279E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2183E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1358E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4917E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7034E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8661E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8880E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2920E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5133E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0498E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1398E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4063E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6837E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6391E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1793E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2031E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8969E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3999E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7687E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4917E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7034E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 75828.46754 | 75828.46754 | 5.47647 | 5.47647 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 81502.46674 | 81502.46674 | 5.88642 | 5.88642 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 775805.44984 | 775805.44984 | 56.01935 | 56.01935 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 156942.65042 | 156942.65042 | 6.56199 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 78403.74229 | 78403.74229 | 5.66160 | 5.66160 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 28567.50119 | 28567.50119 | 1.20513 | 1.20513 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 17447.76637 | 17447.76637 | 1.27176 | 1.27176 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 145.90778 | 145.90778 | 6.24964E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14683.54423 | 14683.54423 | 1.07027 | 1.07027 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 402.14033 | 402.14033 | 1.71544E-002 | 8.72129E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19591.93325 | 19591.93325 | 1.42804 | 1.42804 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 1893.02937 | 1893.02937 | 7.99421E-002 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19174.76263 | 19174.76263 | 1.39763 | 1.39763 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 172848.00784 | 172848.00784 | 12.59906 | 12.59906 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 71647.88680 | 71647.88680 | 3.04433 | 3.04433 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 153261.16297 | 153261.16297 | 11.17131 | 11.17131 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 47767.81867 | 47767.81867 | 2.03017 | 2.03017 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 193803.31675 | 193803.31675 | 14.12649 | 14.12649 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 71555.06090 | 71555.06090 | 3.04036 | 3.04036 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 169680.60198 | 169680.60198 | 12.36812 | 12.36812 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 39903.45493 | 39903.45493 | 1.69342 | 1.69342 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19110.05745 | 19110.05745 | 1.39296 | 1.39296 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 9067.02823 | 9067.02823 | 0.38581 | 0.38581 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15738.84336 | 15738.84336 | 1.14722 | 1.14722 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 5997.69293 | 5997.69293 | 0.25524 | 0.25524 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21110.39422 | 21110.39422 | 1.53876 | 1.53876 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 9052.69641 | 9052.69641 | 0.38519 | 0.38519 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18146.32519 | 18146.32519 | 1.32271 | 1.32271 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 5253.62340 | 5253.62340 | 0.22342 | 0.22342 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8208.48186 | 8208.48186 | 0.47186 | 0.47186 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78305.59887 | 78305.59887 | 4.50131 | 4.50131 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7893.14035 | 7893.14035 | 0.45378 | 0.45378 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 40.63367 | 1.07781E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372312.76151 | 428159.67574 | 21.40401 | 24.61461 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 182192.15 | 10.04694 | 10.04694 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 184.19 | 1.52292 | 1.52292 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1726786.25 | 94.46225 | 94.46225 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 2450.52 | 20.58651 | 20.58651 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 191124.83 | 10.73376 | 10.73376 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 244.81 | 2.45478 | 2.45478 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
7 | CAV_BAS | Cooling | Sensible | 92106.09 | 5.47647 | 5.47647 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 39626.51 | 1.20016 | 1.20016 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 428615.36 | 24.61482 | 24.61482 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 11172.98 | 0.33839 | 0.33839 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8241.56 | 0.47186 | 0.47186 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78639.90 | 4.50131 | 4.50131 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5161.45 | 0.15632 | 0.15632 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8065.50 | 0.45378 | 0.45378 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.47647 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.38673 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.88642 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32312 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61876 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86166 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17911E-003 |
12 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 54039.37785 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.01935 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33953 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18959 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90542 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12213E-003 |
20 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 540458.69695 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.66160 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33596 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61922 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89588 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13408E-003 |
28 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 54054.46933 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27176 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18779 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20348 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50077 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02889E-003 |
36 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6792.84301 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07027 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14380 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12200 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13057 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38347 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64952E-003 |
44 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4358.94321 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42804 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16724 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20278 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44597 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27817E-003 |
52 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6769.50238 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39763 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11012 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.40000E-002 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13138 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45990E-003 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4385.77572 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.59906 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18955 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16100 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02845 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50548 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00998E-003 |
68 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 101629.05787 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.17131 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36738 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76552E-003 |
73 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 67773.28597 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.12649 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16906 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14400 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03421 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45083 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25361E-003 |
81 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 101496.51015 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.36812 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12444 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31102 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33183 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06179E-003 |
89 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 56531.45974 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39296 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17145 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14600 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20337 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45720 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22224E-003 |
97 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12879.40735 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14722 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13415 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11400 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13078 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35774 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84001E-003 |
105 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8520.58463 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53876 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15521 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20312 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41388 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45480E-003 |
113 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12858.97162 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32271 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11636 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13095 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31028 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27443E-003 |
121 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7458.48905 |
122 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47186 |
123 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.50131 |
124 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45378 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.61461 |
126 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.52706 |
127 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28698 |
128 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.05412 |
129 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28698 |
130 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.04694 |
131 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.04694 |
132 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22763 |
134 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.14216 |
135 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.87032 |
136 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 106.28433 |
137 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.87032 |
138 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 94.46225 |
139 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 94.46225 |
140 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.24211 |
142 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.53163 |
143 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28744 |
144 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.06325 |
145 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.45478 |
146 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.73376 |
147 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.73376 |
148 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
149 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22870 |
150 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
151 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
152 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.47647 |
153 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
154 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.47647 |
155 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.47647 |
156 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.21915 |
158 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.61461 |
159 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.61461 |
160 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.61461 |
161 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.61461 |
162 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.61482 |
163 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.61482 |
164 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
166 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47186 |
167 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47186 |
168 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47186 |
169 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47186 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47186 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47186 |
172 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
173 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
174 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.50131 |
175 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.50131 |
176 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.50131 |
177 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.50131 |
178 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.50131 |
179 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.50131 |
180 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
181 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
182 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45378 |
183 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45378 |
184 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45378 |
185 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45378 |
186 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45378 |
187 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45378 |
188 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
189 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
190 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.04694 |
191 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 94.46225 |
192 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.73376 |
193 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.47647 |
194 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.61482 |
195 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47186 |
196 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.50131 |
197 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45378 |
198 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.04694 |
199 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.80012 |
200 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
201 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03937 |
202 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.02421E-003 |
203 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
204 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 237911.41563 |
205 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.80424E-003 |
206 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.04694 |
207 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 9601.77191 |
208 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.04694 |
209 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.80424E-003 |
210 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.99844E-005 |
211 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 94.46225 |
212 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.08613 |
213 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
214 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03965 |
215 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.11178E-003 |
216 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
217 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2295411.74424 |
218 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.56485E-002 |
219 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 94.46225 |
220 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
221 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 94.46225 |
222 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.56485E-002 |
223 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.25364E-006 |
224 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.73376 |
225 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.56571 |
226 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
227 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04861 |
228 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.98559E-003 |
229 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
230 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 249692.35749 |
231 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.14117E-003 |
232 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.73376 |
233 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
234 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.73376 |
235 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.14117E-003 |
236 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.66824E-005 |
237 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.47647 |
238 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
239 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.95662 |
240 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
241 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02882 |
242 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.27468E-003 |
243 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
244 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 135020.25900 |
245 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86156E-003 |
246 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.47647 |
247 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 246504.63470 |
248 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.47647 |
249 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.86156E-003 |
250 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.23315E-004 |
251 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.61482 |
252 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
253 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.61482 |
254 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 516051.43397 |
255 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 329295.58620 |
256 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26381E-002 |
257 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.61482 |
258 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.61482 |
259 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.61482 |
260 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.61482 |
261 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 516051.43397 |
262 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 516051.43397 |
263 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11172.98038 |
264 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
265 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.61482 |
266 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.61482 |
267 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 516051.43397 |
268 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26381E-002 |
269 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11172.98038 |
270 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.59140E-005 |
271 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
272 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
273 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
274 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47186 |
275 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
276 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47186 |
277 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9952.01346 |
278 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6319.30285 |
279 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43724E-004 |
280 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47186 |
281 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47186 |
282 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47186 |
283 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47186 |
284 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9952.01346 |
285 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9952.01346 |
286 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
287 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
288 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47186 |
289 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47186 |
290 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9952.01346 |
291 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43724E-004 |
292 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
293 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.50131 |
294 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
295 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50131 |
296 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94991.38887 |
297 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 60294.80604 |
298 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32633E-003 |
299 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.50131 |
300 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.50131 |
301 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.50131 |
302 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.50131 |
303 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94991.38887 |
304 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94991.38887 |
305 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5161.45407 |
306 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
307 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.50131 |
308 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50131 |
309 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94991.38887 |
310 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32633E-003 |
311 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5161.45407 |
312 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45378 |
313 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
314 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45378 |
315 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9581.94041 |
316 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6080.74795 |
317 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34661E-004 |
318 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45378 |
319 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45378 |
320 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45378 |
321 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45378 |
322 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9581.94041 |
323 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9581.94041 |
324 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
325 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
326 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45378 |
327 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45378 |
328 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9581.94041 |
329 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34661E-004 |
330 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
331 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.34555E-002 |
332 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13490.81732 |
333 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.34555E-002 |
334 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.01465 |
335 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.34555E-002 |
336 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.34555E-002 |
337 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 350304.41493 |
338 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
339 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.34555E-002 |
340 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.01465 |
341 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.17277E-002 |
342 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4670.07389 |
343 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.17277E-002 |
344 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4670.07389 |
345 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.34555E-002 |
346 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.20891E-002 |
347 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1471653.38208 |
348 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1471653.20500 |
349 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.39267E-002 |
350 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.34555E-002 |
351 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.20891E-002 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1471653.38208 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1471653.20500 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.39267E-002 |
355 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.54428E-002 |
356 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.85313 |
357 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.54428E-002 |
358 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3899.68549 |
359 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.54428E-002 |
360 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 153335.39563 |
361 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 77622.70066 |
362 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 76667.69782 |
363 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
364 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46573.62040 |
365 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 636110.33693 |
366 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 623823.46000 |
367 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.54428E-002 |
368 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
369 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
370 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
371 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
372 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
373 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14785 |
374 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.74240 |
375 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14785 |
376 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 36242.78280 |
377 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 56.81625 |
378 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1761570.66556 |
379 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.36325 |
380 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 220196.33319 |
381 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 56.81625 |
382 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1761570.66556 |
383 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.36325 |
384 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 220196.33319 |
385 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 7.63150E-002 |
386 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 7.63150E-002 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 287331.62 | 194526.37 | 92805.25 | 0.68 | 64277.59 | 651.94 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2725883.22 | 1839308.65 | 886574.57 | 0.67 | 597019.14 | 6055.30 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 305007.49 | 206990.70 | 98016.79 | 0.68 | 69264.29 | 702.52 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 159138.54 | 107110.02 | 52028.52 | 0.67 | 34806.24 | 353.02 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 9.21 | 31.42 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 9.21 | 31.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2522381960 | 0.2639411812 | Pass | Pass | 0.4847606174 | 1.7851945228 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1294647005 | 0.2155618905 | Pass | Pass | 0.1271413207 | 0.3532162050 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.6918881921E-002 | 0.1109078150 | Pass | Pass | 1.5134361563E-002 | 0.1222668400 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.7867417789E-002 | 1.1365104006E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1080061662 | 0.1521599182 | Pass | Pass | 0.1125389960 | 0.3151351520 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1133639432 | 0.1545930805 | Pass | Pass | 0.1125730867 | 0.3152284455 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1406181138 | 0.1885386257 | Pass | Pass | 0.1129903113 | 0.3164102459 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1223228700 | 0.1735716081 | Pass | Pass | 0.1315752185 | 0.3908081008 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.2298664569E-002 | 8.1307973081E-002 | Pass | Pass | 1.4689199758E-002 | 0.1203979698 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7682362645E-002 | 8.3871271847E-002 | Pass | Pass | 1.4712851745E-002 | 0.1204963244 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.7267119674E-002 | 0.1186213489 | Pass | Pass | 1.4150110632E-002 | 0.1181285466 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.8411085235E-002 | 9.7209768896E-002 | Pass | Pass | 1.4472363928E-002 | 0.1194930534 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.9406312446E-002 | 2.6791147846E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2964288170E-002 | 2.5908081478E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.9384412160E-002 | 5.5912391044E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9730182505E-002 | 4.4493214558E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.8253237523E-002 | 2.7262483239E-002 | Pass | Pass | 0.2276219719 | 0.6895613916 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0059634781E-002 | 1.7852451904E-002 | Pass | Pass | 5.9333419773E-002 | 0.4072401793 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1207035610E-002 | 3.5016004840E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0183558506E-004 | 1.3675964085E-004 | Pass | Pass | 2.0212227805E-003 | 1.4265723417E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.5940866062E-005 | 1.0679520314E-004 | Pass | Pass | 5.8258339848E-003 | 2.9825107727E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.5665299549E-005 | 9.3456552979E-005 | Pass | Pass | 1.8374954561E-002 | 7.7941448121E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.9803907273E-004 | 3.5694248241E-004 | Pass | Pass | 6.3672230950E-005 | 1.0683709304E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3644.20 | -62.7 | 0.00 | -7675.1 | 46696.69 | 42603.05 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.13 | 0.0000 | Y | 10.53 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.07 | 0.0000 | Y | 6.77 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.89 | 0.0000 | Y | 10.44 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 6.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 105.17 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.04 | 0.0000 | Y | 67.65 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.87 | 0.0000 | Y | 104.32 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.99 | 0.0000 | Y | 67.54 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 10.52 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 6.76 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.87 | 0.0000 | Y | 10.43 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.99 | 0.0000 | Y | 6.75 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 774.17 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.85 | 41.85 | 104.26 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.85 | 62.85 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.85 | 46.68 | 233.05 | |
Exterior Lighting Total | 40855.88 | 348.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2909047.97 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1471653.21 | 6.01 | 1463452.50 | 5.99 | 9.21 | 31.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1471653.21 | 6.01 | 1463452.50 | 5.99 | 9.21 | 31.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 639025.26 | |||||
CENTRAL BOILER | Boiler:HotWater | 623823.46 | 1.00 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1761570.67 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1761570.67 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 237911.42 | 287331.62 | 194526.37 | 92805.25 | 0.68 | - | 64277.59 | 651.94 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2295411.74 | 2725883.22 | 1839308.65 | 886574.57 | 0.67 | - | 597019.14 | 6055.30 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 249692.36 | 305007.49 | 206990.70 | 98016.79 | 0.68 | - | 69264.29 | 702.52 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 135020.26 | 159138.54 | 107110.02 | 52028.52 | 0.67 | - | 34806.24 | 353.02 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 516051.43 | 329295.59 | 186755.85 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9952.01 | 6319.30 | 3632.71 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94991.39 | 60294.81 | 34696.58 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9581.94 | 6080.75 | 3501.19 | 0.63 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 54039.38 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 540458.70 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 54054.47 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6792.84 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4358.94 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6769.50 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4385.78 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 101629.06 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 67773.29 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 101496.51 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 56531.46 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12879.41 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8520.58 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12858.97 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7458.49 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 9601.77 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 246504.63 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 516051.43 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9952.01 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94991.39 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9581.94 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 11172.98 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5161.45 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.05 | 21710.91 | 2160.95 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 94.46 | 204127.89 | 2160.95 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.73 | 23071.83 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.48 | 11910.70 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.61 | 40595.91 | 1649.25 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 528.53 | 1120.11 | 1.00 | 1.63 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.50 | 5041.96 | 1120.11 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 508.28 | 1120.11 | 1.00 | 1.65 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.083455 | 13490.82 | 161652.92 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041728 | 4670.07 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041728 | 4670.07 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015443 | 3899.69 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.147853 | 36242.78 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 75828.47 | 75828.47 | 27.28 | 5.476 | 5.476 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 81502.47 | 81502.47 | 32.65 | 5.886 | 5.886 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 775805.45 | 775805.45 | 310.80 | 56.019 | 56.019 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 78403.74 | 78403.74 | 31.41 | 5.662 | 5.662 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 35.62 | 0.01077 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17447.77 | 17447.77 | 55.67 | 1.272 | 1.272 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00725 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14683.54 | 14683.54 | 72.70 | 1.070 | 1.070 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00719 | 39.36 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19591.93 | 19591.93 | 62.51 | 1.428 | 1.428 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00722 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19174.76 | 19174.76 | 94.94 | 1.398 | 1.398 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00715 | 41.96 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 172848.01 | 172848.01 | 551.50 | 12.599 | 12.599 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00730 | 42.70 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 153261.16 | 153261.16 | 758.81 | 11.171 | 11.171 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00722 | 39.60 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 193803.32 | 193803.32 | 618.35 | 14.126 | 14.126 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00727 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 169680.60 | 169680.60 | 840.11 | 12.368 | 12.368 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00720 | 41.83 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19110.06 | 19110.06 | 60.97 | 1.393 | 1.393 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00729 | 42.61 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15738.84 | 15738.84 | 77.92 | 1.147 | 1.147 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 24.00 | 24.00 | 0.00723 | 39.84 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21110.39 | 21110.39 | 67.36 | 1.539 | 1.539 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18146.33 | 18146.33 | 89.84 | 1.323 | 1.323 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00720 | 41.96 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8208.48 | 8208.48 | 226.74 | 0.472 | 0.472 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78305.60 | 78305.60 | 2162.97 | 4.501 | 4.501 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7893.14 | 7893.14 | 218.03 | 0.454 | 0.454 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.00 | 27.00 | 0.00709 | 40.63 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372312.76 | 428159.68 | 546.35 | 21.404 | 24.615 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.39 | 0.00915 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.79 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 156942.65 | 156942.65 | 62.87 | 6.562 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 28567.50 | 28567.50 | 11.44 | 1.205 | 1.205 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 145.91 | 145.91 | 0.47 | 0.006 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00875 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 402.14 | 402.14 | 1.99 | 0.017 | 0.087 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00841 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 1893.03 | 1893.03 | 6.04 | 0.080 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.60 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 71647.89 | 71647.89 | 228.61 | 3.044 | 3.044 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 47767.82 | 47767.82 | 236.50 | 2.030 | 2.030 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 71555.06 | 71555.06 | 228.30 | 3.040 | 3.040 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 39903.45 | 39903.45 | 197.57 | 1.693 | 1.693 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 9067.03 | 9067.03 | 28.93 | 0.386 | 0.386 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 5997.69 | 5997.69 | 29.70 | 0.255 | 0.255 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 9052.70 | 9052.70 | 28.88 | 0.385 | 0.385 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 5253.62 | 5253.62 | 26.01 | 0.223 | 0.223 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.31 | 0.00701 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.80 | 0.00825 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.05 | 10.05 | 1.52 | 1.52 | 10.0469 | 2.2870 | 10.0469 | 0.2276 | 0.3000 |
VAV_MID WITH REHEAT | 94.46 | 94.46 | 20.59 | 20.59 | 94.4622 | 22.8703 | 94.4622 | 0.2421 | 0.3000 |
VAV_TOP WITH REHEAT | 10.73 | 10.73 | 2.45 | 2.45 | 10.7338 | 2.4548 | 10.7338 | 0.2287 | 0.3000 |
CAV_BAS | 5.48 | 5.48 | 1.20 | 1.20 | 5.4765 | 1.2002 | 5.4765 | 0.2191 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.61 | 24.61 | 0.34 | 0.34 | 24.6148 | 24.6146 | 24.6148 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4719 | 0.4719 | 0.4719 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.50 | 4.50 | 0.16 | 0.16 | 4.5013 | 4.5013 | 4.5013 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4538 | 0.4538 | 0.4538 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 54039.378 | 54039.378 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 54039.38 | 35981.13 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 540458.697 | 540458.697 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 540458.70 | 359811.31 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 156942.65 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 54054.469 | 54054.469 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 54054.47 | 40230.85 | 1.205126 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28567.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6792.843 | 6792.843 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6792.84 | 4517.79 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00874893 | 56.4648 | 145.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4358.943 | 4358.943 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4358.94 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00840845 | 54.2965 | 402.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6769.502 | 6769.502 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6769.50 | 4517.89 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824423 | 53.2498 | 1893.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4385.776 | 4385.776 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 4385.78 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 101629.058 | 101629.058 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101629.06 | 101629.06 | 3.044327 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814328 | 52.6056 | 71647.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 67773.286 | 67773.286 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 67773.29 | 67773.29 | 2.030168 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814041 | 52.5872 | 47767.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 101496.510 | 101496.510 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101496.51 | 101496.51 | 3.040356 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814375 | 52.6086 | 71555.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 56531.460 | 56531.460 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56531.46 | 56531.46 | 1.693416 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818180 | 52.8510 | 39903.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 12879.407 | 12879.407 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12879.41 | 12879.41 | 0.385806 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811173 | 52.4044 | 9067.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8520.585 | 8520.585 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8520.58 | 8520.58 | 0.255236 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00810975 | 52.3918 | 5997.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 12858.972 | 12858.972 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12858.97 | 12858.97 | 0.385194 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811227 | 52.4078 | 9052.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7458.489 | 7458.489 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7458.49 | 7458.49 | 0.223421 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814352 | 52.6070 | 5253.62 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 237911.416 | -999.000 | 10.046943 | 0.00680424 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 237911.42 | 209676.87 | 10.046943 | 27.80 | 17.31 | 0.00802421 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.2101 | 24.00 | 0.00732535 | 39.4908 | 137779.45 | 0.00 | 238231.31 | 222249.77 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 9601.772 | 9601.772 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9601.77 | 9601.77 | 3.014083 | 10.17 | 10.17 | 0.00909556 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 67.3671 | 21.46 | 0.00869434 | 54.5413 | 0.00 | 0.00 | -999.00 | -999.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2295411.744 | -999.000 | 94.462249 | 0.06564848 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2295411.74 | 2006406.10 | 94.462249 | 28.09 | 17.48 | 0.00811178 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.4964 | 24.00 | 0.00737004 | 39.7292 | 1281402.90 | 0.00 | 2298422.26 | 2122981.87 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 28.338675 | 15.06 | 13.34 | 0.00884181 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 71.6547 | 21.00 | 0.00807100 | 52.1452 | 359447.17 | 0.00 | -999.00 | -999.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 249692.357 | -999.000 | 10.733759 | 0.00714117 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 249692.36 | 220738.05 | 10.733759 | 27.57 | 17.19 | 0.00798559 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.9170 | 24.00 | 0.00733086 | 39.5205 | 146827.28 | 0.00 | 250033.50 | 234293.39 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 3.220128 | 15.77 | 13.52 | 0.00873768 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 63.0565 | 21.00 | 0.00803160 | 51.8942 | 41876.94 | 0.00 | -999.00 | -999.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 135020.259 | -999.000 | 5.476467 | 0.00386156 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 135020.26 | 115773.58 | 5.476467 | 27.96 | 17.57 | 0.00827468 | 11.03 | 9.77 | 0.00700000 | 40.57 | 0.01077797 | 23.25 | 21.9148 | 24.00 | 0.00748912 | 40.3633 | 68933.97 | 0.00 | 135200.08 | 122285.21 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 246504.635 | 246504.635 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 246504.63 | 246504.63 | 5.476467 | 2.78 | 2.78 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 21.9148 | 26.39 | 0.00915345 | 42.6736 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 516051.434 | 329295.586 | 24.614818 | 0.01263807 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 466887.65 | 461438.93 | -999.0 | 28.61 | 16.80 | 0.00709357 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | -999.0000 | 27.00 | 0.00704210 | 31.7848 | 371831.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9952.013 | 6319.303 | 0.471856 | 0.00024372 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9014.99 | 8775.99 | -999.0 | 28.44 | 16.85 | 0.00721401 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00708961 | 31.9951 | 8066.57 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94991.389 | 60294.806 | 4.501313 | 0.00232633 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 86055.38 | 83670.88 | -999.0 | 28.43 | 16.85 | 0.00722379 | 12.80 | 10.55 | 0.00700000 | 40.63 | 0.01077808 | 23.27 | -999.0000 | 27.00 | 0.00709376 | 32.0138 | 77045.51 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9581.940 | 6080.748 | 0.453781 | 0.00023466 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 8681.70 | 8446.67 | -999.0 | 28.45 | 16.85 | 0.00721878 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00709164 | 32.0042 | 7888.23 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 516051.434 | 516051.434 | 24.614818 | 0.01263807 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516051.43 | 516051.43 | 24.614818 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.3748 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9952.013 | 9952.013 | 0.471856 | 0.00024372 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9952.01 | 9952.01 | 0.471856 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3130 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94991.389 | 94991.389 | 4.501313 | 0.00232633 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94991.39 | 94991.39 | 4.501313 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4728 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9581.940 | 9581.940 | 0.453781 | 0.00023466 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9581.94 | 9581.94 | 0.453781 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4449 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11172.98 | 11172.98 | 24.614818 | 0.17 | 0.17 | 0.00702960 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.3748 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.471856 | 0.42 | 0.42 | 0.00707134 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3130 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5161.45 | 5161.45 | 4.501313 | 0.44 | 0.44 | 0.00708561 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4728 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.453781 | 0.44 | 0.44 | 0.00828249 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4449 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 54039.378 | 54039.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 54039.38 | 35981.13 | 1.0000 | 1.29726454 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54039.38 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 540458.697 | 540458.697 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 540458.70 | 359811.31 | 1.0000 | 12.97264538 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 540458.70 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 156942.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 54054.469 | 54054.469 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 54054.47 | 40230.85 | 1.0000 | 1.45048396 | 1.205126 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54054.47 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28567.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6792.843 | 6792.843 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6792.84 | 4517.79 | 1.0000 | 0.16288451 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6792.84 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.99 | 0.00874893 | 21.00 | 0.00874893 | 56.4648 | 145.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4358.943 | 4358.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4358.94 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4358.94 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00840845 | 21.00 | 0.00840845 | 54.2965 | 402.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6769.502 | 6769.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6769.50 | 4517.89 | 1.0000 | 0.16288807 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6769.50 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.90 | 0.00824423 | 21.00 | 0.00824423 | 53.2498 | 1893.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4385.776 | 4385.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 4385.78 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4385.78 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 101629.058 | 101629.058 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101629.06 | 101629.06 | 1.0000 | 3.66413643 | 3.044327 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101629.06 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814328 | 21.00 | 0.00814328 | 52.6056 | 71647.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 67773.286 | 67773.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 67773.29 | 67773.29 | 1.0000 | 2.44349964 | 2.030168 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67773.29 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814041 | 21.00 | 0.00814041 | 52.5872 | 47767.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 101496.510 | 101496.510 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101496.51 | 101496.51 | 1.0000 | 3.65935755 | 3.040356 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101496.51 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814375 | 21.00 | 0.00814375 | 52.6086 | 71555.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 56531.460 | 56531.460 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 56531.46 | 56531.46 | 1.0000 | 2.03818657 | 1.693416 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56531.46 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00818180 | 21.00 | 0.00818180 | 52.8510 | 39903.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12879.407 | 12879.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12879.41 | 12879.41 | 1.0000 | 0.46435445 | 0.385806 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12879.41 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811173 | 21.00 | 0.00811173 | 52.4044 | 9067.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8520.585 | 8520.585 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8520.58 | 8520.58 | 1.0000 | 0.30720136 | 0.255236 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8520.58 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00810975 | 21.00 | 0.00810975 | 52.3918 | 5997.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12858.972 | 12858.972 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12858.97 | 12858.97 | 1.0000 | 0.46361766 | 0.385194 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12858.97 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811227 | 21.00 | 0.00811227 | 52.4078 | 9052.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7458.489 | 7458.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7458.49 | 7458.49 | 1.0000 | 0.26890854 | 0.223421 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7458.49 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814352 | 21.00 | 0.00814352 | 52.6070 | 5253.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 237911.416 | -999.000 | 10.046943 | 0.00680424 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7566 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.046943 | 12.09244970 | 4197.9300 | 999.8980 | 83.44694050 | 15.00 | 6.67 | 8.33 | 2918035.78 | 8.1531 | 8.153136 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 237911.42 | 209676.87 | 1.0000 | 12.09244970 | 10.046943 | 27.80 | 17.31 | 0.00802421 | 48417.4 | 11.04 | 9.78 | 0.00700000 | 28743.0 | 6.80354227 | 6.67 | 15.00 | 8.33 | 21710.908 | 216200.51 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 20.2101 | 24.00 | 0.00732535 | 24.00 | 0.00732535 | 39.4908 | 137779.45 | 0.00 | 238231.31 | 222249.77 | 12.09244970 | 27.80 | 17.31 | 0.00802421 | 48417.4 | 9.78 | 9.76 | 0.00749957 | 28716.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9601.772 | 9601.772 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.046943 | 12.09244970 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9601.77 | 9601.77 | 1.0000 | 3.62773491 | 3.014083 | 10.17 | 10.17 | 0.00909556 | 33134.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9601.77 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 67.3671 | 4.93 | 0.00897605 | 21.46 | 0.00869434 | 54.5413 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2295411.744 | -999.000 | 94.462249 | 0.06564848 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9194 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 94.462249 | 113.69428825 | 4197.9300 | 999.8980 | 83.44694050 | 15.00 | 6.67 | 8.33 | 2918035.78 | 78.6629 | 78.662906 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2295411.74 | 2006406.10 | 1.0000 | 113.69428825 | 94.462249 | 28.09 | 17.48 | 0.00811178 | 48932.7 | 11.04 | 9.78 | 0.00700000 | 28743.3 | 65.64178849 | 6.67 | 15.00 | 8.33 | 204127.888 | 2091283.86 | 42.80 | 0.01078182 | 23.86 | 20.30600000 | 21.4964 | 24.00 | 0.00737004 | 24.00 | 0.00737004 | 39.7292 | 1281402.90 | 0.00 | 2298422.26 | 2122981.87 | 113.69428825 | 28.09 | 17.48 | 0.00811178 | 48932.7 | 9.78 | 9.76 | 0.00749922 | 28716.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 94.462249 | 113.69428825 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 34.10828648 | 28.338675 | 15.06 | 13.34 | 0.00884181 | 37493.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 20.30600000 | 71.6547 | 21.03 | 0.00805402 | 21.00 | 0.00807100 | 52.1452 | 359447.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 249692.357 | -999.000 | 10.733759 | 0.00714117 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6848 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.733759 | 12.91909804 | 4197.9300 | 999.8980 | 83.44694050 | 15.00 | 6.67 | 8.33 | 2918035.78 | 8.5569 | 8.556864 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 249692.36 | 220738.05 | 1.0000 | 12.91909804 | 10.733759 | 27.57 | 17.19 | 0.00798559 | 48079.8 | 11.05 | 9.78 | 0.00700000 | 28752.4 | 7.14044134 | 6.67 | 15.00 | 8.33 | 23071.834 | 226620.52 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 18.9170 | 24.00 | 0.00733086 | 24.00 | 0.00733086 | 39.5205 | 146827.28 | 0.00 | 250033.50 | 234293.39 | 12.91909804 | 27.57 | 17.20 | 0.00798559 | 48079.8 | 9.78 | 9.76 | 0.00750195 | 28726.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.733759 | 12.91909804 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 3.87572941 | 3.220128 | 15.77 | 13.52 | 0.00873768 | 37951.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 63.0565 | 21.00 | 0.00802804 | 21.00 | 0.00803160 | 51.8942 | 41876.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 135020.259 | -999.000 | 5.476467 | 0.00386156 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2222 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.476467 | 6.59144848 | 4197.9300 | 999.8980 | 83.44694050 | 15.00 | 6.67 | 8.33 | 2918035.78 | 4.6271 | 4.627094 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 135020.26 | 115773.58 | 1.0000 | 6.59144848 | 5.476467 | 27.96 | 17.57 | 0.00827468 | 49216.5 | 11.03 | 9.77 | 0.00700000 | 28732.3 | 3.86116840 | 6.67 | 15.00 | 8.33 | 11910.705 | 123109.55 | 40.57 | 0.01077797 | 23.25 | 1.20015641 | 21.9148 | 24.00 | 0.00748912 | 24.00 | 0.00748912 | 40.3633 | 68933.97 | 0.00 | 135200.08 | 122285.21 | 6.59144848 | 27.96 | 17.57 | 0.00827468 | 49216.5 | 9.77 | 9.75 | 0.00749689 | 28705.0 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 246504.635 | 246504.635 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.476467 | 6.59144848 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 246504.63 | 246504.63 | 1.0000 | 6.59144848 | 5.476467 | 2.78 | 2.78 | 0.00915345 | 25736.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 246504.63 | 12.70 | 0.00915345 | 12.70 | 1.20015641 | 21.9148 | 0.00 | 0.00915345 | 26.39 | 0.00915345 | 42.6736 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 516051.434 | 329295.586 | 24.614818 | 0.01263807 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0266 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 466887.65 | 461438.93 | 0.9047 | -999.0 | -999.0 | 28.61 | 16.80 | 0.00709357 | 46866.1 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 466887.65 | 42.80 | 0.01078182 | 23.86 | 0.33839277 | -999.0000 | 27.00 | 0.00704210 | 27.00 | 0.00704210 | 31.7848 | 371831.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9952.013 | 6319.303 | 0.471856 | 0.00024372 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2505 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 9014.99 | 8775.99 | 0.9058 | -999.0 | -999.0 | 28.44 | 16.85 | 0.00721401 | 47003.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9014.99 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00708961 | 27.00 | 0.00708961 | 31.9951 | 8066.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94991.389 | 60294.806 | 4.501313 | 0.00232633 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2687 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 86055.38 | 83670.88 | 0.9059 | -999.0 | -999.0 | 28.43 | 16.85 | 0.00722379 | 47013.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86055.38 | 40.63 | 0.01077808 | 23.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709376 | 27.00 | 0.00709376 | 32.0138 | 77045.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9581.940 | 6080.748 | 0.453781 | 0.00023466 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2593 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | Sensible | 8681.70 | 8446.67 | 0.9060 | -999.0 | -999.0 | 28.45 | 16.85 | 0.00721878 | 47026.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8681.70 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00709164 | 27.00 | 0.00709164 | 32.0042 | 7888.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516051.434 | 516051.434 | 24.614818 | 0.01263807 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516051.43 | 516051.43 | 1.0000 | 29.62627175 | 24.614818 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516051.43 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.3748 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9952.013 | 9952.013 | 0.471856 | 0.00024372 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9952.01 | 9952.01 | 1.0000 | 0.56792317 | 0.471856 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9952.01 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3130 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94991.389 | 94991.389 | 4.501313 | 0.00232633 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94991.39 | 94991.39 | 1.0000 | 5.41775747 | 4.501313 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94991.39 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.4728 | 0.00 | 0.00701121 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9581.940 | 9581.940 | 0.453781 | 0.00023466 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9581.94 | 9581.94 | 1.0000 | 0.54616884 | 0.453781 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9581.94 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4449 | 0.00 | 0.00825142 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.614818 | 29.62627175 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11172.98 | 11172.98 | 1.0000 | 29.62627175 | 24.614818 | 0.17 | 0.17 | 0.00702960 | 17758.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11172.98 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.3748 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.471856 | 0.56792317 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.56792317 | 0.471856 | 0.42 | 0.42 | 0.00707134 | 18113.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3130 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.501313 | 5.41775747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5161.45 | 5161.45 | 1.0000 | 5.41775747 | 4.501313 | 0.44 | 0.44 | 0.00708561 | 18169.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5161.45 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.4728 | 0.00 | 0.00701121 | 25.31 | 0.00701121 | 34.9605 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.453781 | 0.54616884 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.54616884 | 0.453781 | 0.44 | 0.44 | 0.00828249 | 21160.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4449 | 0.00 | 0.00825142 | 24.80 | 0.00825142 | 42.3286 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5851.00 | 3973.83 | 3973.83 |
CORE_BOTTOM | 5806.17 | 205.50 | 205.50 |
CORE_MID | 5473.00 | 37.00 | 0.00 |
CORE_TOP | 5228.50 | 272.83 | 14.67 |
PERIMETER_BOT_ZN_3 | 5514.17 | 672.67 | 556.50 |
PERIMETER_BOT_ZN_2 | 5598.67 | 748.50 | 655.17 |
PERIMETER_BOT_ZN_1 | 5712.33 | 771.50 | 711.33 |
PERIMETER_BOT_ZN_4 | 5837.67 | 955.67 | 946.67 |
PERIMETER_MID_ZN_3 | 4922.33 | 896.17 | 316.83 |
PERIMETER_MID_ZN_2 | 4446.17 | 751.83 | 492.50 |
PERIMETER_MID_ZN_1 | 5535.33 | 688.00 | 510.17 |
PERIMETER_MID_ZN_4 | 5392.00 | 862.33 | 601.33 |
PERIMETER_TOP_ZN_3 | 4776.50 | 1171.33 | 382.00 |
PERIMETER_TOP_ZN_2 | 5142.00 | 964.33 | 528.83 |
PERIMETER_TOP_ZN_1 | 5400.00 | 848.17 | 546.83 |
PERIMETER_TOP_ZN_4 | 5227.83 | 1031.17 | 624.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2110.83 | 2110.83 |
DATACENTER_MID_ZN_6 | 5943.00 | 478.50 | 478.50 |
DATACENTER_TOP_ZN_6 | 5943.00 | 732.33 | 732.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 5956.33 | 0.00 | 3991.83 |
CORE_BOTTOM | 0.00 | 95.83 | 0.00 | 7.33 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 1.33 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 346.83 | 0.00 | 111.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 400.67 | 0.00 | 138.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 392.00 | 0.00 | 149.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 571.33 | 0.00 | 184.67 |
PERIMETER_MID_ZN_3 | 0.00 | 147.17 | 0.00 | 60.67 |
PERIMETER_MID_ZN_2 | 0.00 | 227.00 | 0.00 | 99.00 |
PERIMETER_MID_ZN_1 | 0.00 | 210.33 | 0.00 | 102.33 |
PERIMETER_MID_ZN_4 | 0.00 | 312.83 | 0.00 | 102.17 |
PERIMETER_TOP_ZN_3 | 0.00 | 184.33 | 0.00 | 69.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 253.33 | 0.00 | 101.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 242.33 | 0.00 | 103.67 |
PERIMETER_TOP_ZN_4 | 0.00 | 330.50 | 0.00 | 107.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 638.50 | 0.00 | 425.00 |
DATACENTER_MID_ZN_6 | 0.00 | 458.50 | 0.00 | 373.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 448.67 | 0.00 | 359.67 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 75.50 | 0.00 | 75.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 6019.33 | 0.00 | 4038.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.177 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.490 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.459 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.454 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.639 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.745 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.771 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.961 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.712 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.878 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.931 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.967 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.690 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.882 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.894 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.922 | 0.050 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.663 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.648 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.32 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.96 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.57 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1032.96 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 7486826.98 | 0.00 | 7486826.98 | 0.00 | 7486826.98 | 37848132.68 | 7032.27 | 1727.73 | 0.00 | 128.81 |
CORE_BOTTOM | 25120912.04 | 0.00 | 25120912.04 | 0.00 | 25120912.04 | 33990283.35 | 7012.69 | 1031.21 | 716.10 | 1591.45 |
CORE_MID | 0.22E+09 | 0.00 | 0.22E+09 | 0.00 | 0.22E+09 | 0.34E+09 | 7061.41 | 946.57 | 752.02 | 1089.14 |
CORE_TOP | 21744167.82 | 0.00 | 21744167.82 | 0.00 | 21744167.82 | 33990283.35 | 7192.58 | 1069.11 | 498.32 | 1057.92 |
PERIMETER_BOT_ZN_3 | 4029414.10 | 0.00 | 4029414.10 | 144958.23 | 4174372.33 | 4267819.30 | 3654.82 | 1094.72 | 4010.46 | 1591.45 |
PERIMETER_BOT_ZN_2 | 2954039.74 | 0.00 | 2954039.74 | 96638.75 | 3050678.49 | 2750345.05 | 3220.75 | 913.50 | 4625.74 | 1591.45 |
PERIMETER_BOT_ZN_1 | 4682574.65 | 0.00 | 4682574.65 | 144958.23 | 4827532.88 | 4267912.63 | 2747.82 | 898.97 | 5113.22 | 1591.45 |
PERIMETER_BOT_ZN_4 | 3834525.19 | 0.00 | 3834525.19 | 96638.75 | 3931163.94 | 2750345.05 | 1989.52 | 804.79 | 5965.69 | 1591.45 |
PERIMETER_MID_ZN_3 | 40926073.26 | 0.00 | 40926073.26 | 339958.49 | 41266031.75 | 42678193.03 | 4431.55 | 802.37 | 3526.08 | 1089.14 |
PERIMETER_MID_ZN_2 | 32047880.99 | 0.00 | 32047880.99 | 226638.84 | 32274519.83 | 27503450.52 | 3592.13 | 769.58 | 4398.29 | 1986.22 |
PERIMETER_MID_ZN_1 | 52106491.50 | 0.00 | 52106491.50 | 339958.49 | 52446449.99 | 42679126.28 | 3109.12 | 883.71 | 4767.17 | 1089.14 |
PERIMETER_MID_ZN_4 | 35650709.01 | 0.00 | 35650709.01 | 226638.84 | 35877347.84 | 27503450.52 | 2935.74 | 938.08 | 4886.18 | 1089.14 |
PERIMETER_TOP_ZN_3 | 3995024.55 | 0.00 | 3995024.55 | 422083.30 | 4417107.85 | 4267819.30 | 4160.88 | 1068.65 | 3530.46 | 1057.92 |
PERIMETER_TOP_ZN_2 | 3214817.58 | 0.00 | 3214817.58 | 281388.67 | 3496206.25 | 2750345.05 | 3296.97 | 903.96 | 4559.07 | 1057.92 |
PERIMETER_TOP_ZN_1 | 5038437.22 | 0.00 | 5038437.22 | 422083.30 | 5460520.52 | 4267912.63 | 3170.12 | 881.93 | 4707.95 | 1057.92 |
PERIMETER_TOP_ZN_4 | 3425347.90 | 0.00 | 3425347.90 | 281388.67 | 3706736.57 | 2750345.05 | 3017.28 | 928.15 | 4814.57 | 1057.92 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.40E+10 | 0.00 | 0.40E+10 | 13222084.47 | 0.40E+10 | 0.50E+10 | 8758.18 | 8760.00 | 6406.11 | 3714.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.3254 | 0.0000 | 0.3254 | 0.0000 | 0.3254 | 1.2002 | 4333.72 | 1609.28 | 0.00 |
CORE_BOTTOM | 0.9019 | 0.0000 | 0.9019 | 0.0000 | 0.9019 | 1.0778 | 4916.61 | 348.02 | 678.37 |
CORE_MID | 8.4506 | 0.0000 | 8.4506 | 0.0000 | 8.4506 | 10.7782 | 4737.59 | 459.56 | 745.85 |
CORE_TOP | 0.8350 | 0.0000 | 0.8350 | 0.0000 | 0.8350 | 1.0778 | 4816.30 | 631.06 | 495.64 |
PERIMETER_BOT_ZN_3 | 0.1474 | 0.0000 | 0.1474 | 0.0039 | 0.1512 | 0.1353 | 2028.39 | 378.19 | 3536.42 |
PERIMETER_BOT_ZN_2 | 0.1108 | 0.0000 | 0.1108 | 0.0026 | 0.1133 | 0.0872 | 1523.35 | 315.47 | 4104.18 |
PERIMETER_BOT_ZN_1 | 0.1780 | 0.0000 | 0.1780 | 0.0039 | 0.1819 | 0.1353 | 1027.85 | 281.57 | 4633.58 |
PERIMETER_BOT_ZN_4 | 0.1428 | 0.0000 | 0.1428 | 0.0026 | 0.1454 | 0.0872 | 647.62 | 227.52 | 5067.86 |
PERIMETER_MID_ZN_3 | 1.6402 | 0.0000 | 1.6402 | 0.0090 | 1.6493 | 1.3533 | 2169.66 | 416.14 | 3357.20 |
PERIMETER_MID_ZN_2 | 1.3031 | 0.0000 | 1.3031 | 0.0063 | 1.3094 | 0.8721 | 1218.46 | 374.28 | 3441.25 |
PERIMETER_MID_ZN_1 | 2.1485 | 0.0000 | 2.1485 | 0.0090 | 2.1575 | 1.3533 | 1053.97 | 355.30 | 4533.73 |
PERIMETER_MID_ZN_4 | 1.4357 | 0.0000 | 1.4357 | 0.0060 | 1.4418 | 0.8721 | 1102.12 | 412.42 | 4428.46 |
PERIMETER_TOP_ZN_3 | 0.1589 | 0.0000 | 0.1589 | 0.0112 | 0.1701 | 0.1353 | 2010.40 | 622.15 | 3310.44 |
PERIMETER_TOP_ZN_2 | 0.1309 | 0.0000 | 0.1309 | 0.0075 | 0.1384 | 0.0872 | 1141.43 | 549.36 | 4252.21 |
PERIMETER_TOP_ZN_1 | 0.2064 | 0.0000 | 0.2064 | 0.0112 | 0.2176 | 0.1353 | 1021.78 | 490.08 | 4431.14 |
PERIMETER_TOP_ZN_4 | 0.1368 | 0.0000 | 0.1368 | 0.0075 | 0.1443 | 0.0872 | 1060.62 | 546.54 | 4335.84 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 154.9884 | 0.0000 | 154.9884 | 0.3543 | 155.3428 | 158.4706 | 5941.42 | 5943.00 | 5288.19 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 58845917.77 | 0.00 | 58845917.77 | 48026705.38 | 1862.84 | 3.93 | 6893.24 | 1591.45 |
VAV_MID WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.48E+09 | 2495.31 | 2.36 | 6262.33 | 1089.14 |
VAV_TOP WITH REHEAT | 54204949.19 | 0.00 | 54204949.19 | 48026705.38 | 2543.98 | 2.61 | 6213.41 | 1057.92 |
CAV_BAS | 10845738.11 | 0.00 | 10845738.11 | 37848132.68 | 7029.97 | 0.00 | 1730.03 | 128.81 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1452 | 0.0000 | 2.1452 | 1.5229 | 564.22 | 2.03 | 5376.75 |
VAV_MID WITH REHEAT | 21.7050 | 0.0000 | 21.7050 | 15.2292 | 742.62 | 1.09 | 5199.29 |
VAV_TOP WITH REHEAT | 2.1266 | 0.0000 | 2.1266 | 1.5229 | 757.59 | 1.02 | 5184.39 |
CAV_BAS | 0.4713 | 0.0000 | 0.4713 | 1.2002 | 4332.68 | 0.00 | 1610.32 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 381.17 | 0.00 | 0.00 | 0.00 | 0.00 | 6622.62 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 513.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5802.68 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 277.21 | 0.00 | 0.00 | 0.00 | 0.00 | 5993.61 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1727.73 | 0.00 | 0.00 | 14.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3836 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3544 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.5625 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.5046 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.3755 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4270 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7389 | 0.0000 | 0.0000 | 0.7877 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1455 |
Defaulted Fields | 1152 |
Fields with Defaults | 3681 |
Autosized Fields | 289 |
Autosizable Fields | 361 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 472 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
Electricity:Building | 17132.95 | 216480.96 | 29-MAY-17:20 | 1013929.88 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17132.95 | 216480.96 | 29-MAY-17:20 | 1013929.88 | 15-DEC-17:00 |
InteriorLights:Electricity | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.90 | 603.11 | 26-MAR-17:10 | 3655.10 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.53 | 43.94 | 01-JAN-09:30 | 1494.55 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.53 | 43.94 | 01-JAN-09:30 | 1494.55 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.21 | 388.67 | 21-MAY-17:10 | 2341.43 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.77 | 28.32 | 01-JAN-08:00 | 949.09 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.77 | 28.32 | 01-JAN-08:00 | 949.09 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.81 | 603.12 | 12-MAR-17:10 | 3651.78 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.44 | 43.94 | 01-JAN-08:00 | 1491.19 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.44 | 43.94 | 01-JAN-08:00 | 1491.19 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.20 | 388.67 | 12-MAR-17:10 | 2361.62 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.76 | 28.32 | 01-JAN-09:30 | 969.29 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.76 | 28.32 | 01-JAN-09:30 | 969.29 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 468.82 | 6031.15 | 19-MAR-17:10 | 36531.88 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.17 | 439.44 | 01-JAN-09:20 | 14926.37 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.17 | 439.44 | 01-JAN-09:20 | 14926.37 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.00 | 3886.70 | 21-MAY-17:10 | 23386.54 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.65 | 283.19 | 01-JAN-08:00 | 9463.12 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.65 | 283.19 | 01-JAN-08:00 | 9463.12 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 467.98 | 6031.24 | 12-MAR-17:10 | 36498.44 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.32 | 439.45 | 01-JAN-08:00 | 14892.59 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.32 | 439.45 | 01-JAN-08:00 | 14892.59 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 301.89 | 3886.68 | 12-MAR-17:10 | 23589.44 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.54 | 283.19 | 01-JAN-09:30 | 9666.11 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.54 | 283.19 | 01-JAN-09:30 | 9666.11 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.88 | 603.11 | 19-MAR-17:10 | 3652.84 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.52 | 43.94 | 01-JAN-09:20 | 1492.29 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.52 | 43.94 | 01-JAN-09:20 | 1492.29 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.20 | 388.67 | 21-MAY-17:10 | 2338.41 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.76 | 28.32 | 01-JAN-08:00 | 946.07 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.76 | 28.32 | 01-JAN-08:00 | 946.07 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.80 | 603.12 | 12-MAR-17:10 | 3649.49 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.43 | 43.94 | 01-JAN-08:00 | 1488.90 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.43 | 43.94 | 01-JAN-08:00 | 1488.90 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.19 | 388.67 | 12-MAR-17:10 | 2358.73 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.75 | 28.32 | 01-JAN-09:30 | 966.40 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.75 | 28.32 | 01-JAN-09:30 | 966.40 | 14-MAR-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6469.73 | 8088.16 | 20-JAN-05:50 | 636113.16 | 10-AUG-16:00 |
HeatRejection:Electricity | 2008.67 | 4172.18 | 20-JAN-07:00 | 86931.00 | 29-APR-19:50 |
General:HeatRejection:Electricity | 2008.67 | 4172.18 | 20-JAN-07:00 | 86931.00 | 29-APR-19:50 |
Electricity:HVAC | 6373.46 | 82911.09 | 10-JAN-03:00 | 481479.17 | 07-AUG-15:40 |
ExteriorEquipment:Electricity | 2566.27 | 20217.42 | 01-JAN-00:10 | 233393.66 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.67 | 979.82 | 01-JAN-00:10 | 3409.32 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
ElectricityNet:Plant | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 32836.72 | 343855.05 | 15-JAN-05:00 | 2327571.96 | 10-AUG-16:00 |
Heating:Electricity | 0.03 | 0.00 | 01-JAN-00:10 | 1994.36 | 02-JAN-07:00 |
General:Heating:Electricity | 0.03 | 0.00 | 01-JAN-00:10 | 1994.36 | 02-JAN-07:00 |
Fans:Electricity | 2940.31 | 46674.68 | 01-JAN-00:10 | 267139.12 | 07-AUG-15:40 |
General:Fans:Electricity | 2940.31 | 46674.68 | 01-JAN-00:10 | 267139.12 | 07-AUG-15:40 |
ExteriorLights:Electricity | 348.98 | 0.00 | 01-JAN-07:10 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 348.98 | 0.00 | 01-JAN-07:10 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 6616.26 | 33463.67 | 21-JAN-05:50 | 694580.07 | 10-AUG-16:00 |
General:Cooling:Electricity | 6616.26 | 33463.67 | 21-JAN-05:50 | 694580.07 | 10-AUG-16:00 |
Humidifier:Electricity | 14.06 | 0.00 | 01-JAN-12:10 | 13579.48 | 18-DEC-06:00 |
General:Humidifier:Electricity | 14.06 | 0.00 | 01-JAN-12:10 | 13579.48 | 18-DEC-06:00 |
Boiler:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 279.92 | 0.00 | 01-JAN-00:10 | 37717.36 | 11-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 279.92 | 0.00 | 01-JAN-00:10 | 37717.36 | 11-JAN-12:40 |
Pumps:Electricity | 929.28 | 3899.69 | 24-JUL-05:00 | 55450.47 | 24-JUL-05:10 |
General:Pumps:Electricity | 929.28 | 3899.69 | 24-JUL-05:00 | 55450.47 | 24-JUL-05:10 |
WIRED_LTG_ELECTRICITY | 69.03 | 0.00 | 01-JAN-00:10 | 6753.49 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 40342.44 | 176163.93 | 21-JAN-05:50 | 3650361.60 | 10-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 40342.44 | 176163.93 | 21-JAN-05:50 | 3650361.60 | 10-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 40342.44 | 176163.93 | 21-JAN-05:50 | 3650361.60 | 10-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 25736.29 | 0.00 | 10-JAN-00:10 | 0.00 | 28-APR-11:50 |
Water:HVAC | 5.23 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
Humidifier:Water | 5.23 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
General:Humidifier:Water | 5.23 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
MainsWater:Facility | 25736.29 | 0.00 | 10-JAN-00:10 | 0.00 | 28-APR-11:50 |
MainsWater:HVAC | 5.23 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
Humidifier:MainsWater | 5.23 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
General:Humidifier:MainsWater | 5.23 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
Water:Plant | 25731.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 25731.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 23450.89 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:Water | 23450.89 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
HeatRejection:MainsWater | 23450.89 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:MainsWater | 23450.89 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 144933.10 | 244151.71 | 21-JAN-05:50 | 14412741.10 | 10-AUG-16:00 |
EnergyTransfer:Building | 24589.67 | 101438.94 | 22-JAN-06:00 | 1810433.24 | 07-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 304.43 | 0.00 | 01-JAN-00:10 | 102128.35 | 30-OCT-06:00 |
Heating:EnergyTransfer | 6.85 | 0.00 | 01-JAN-00:10 | 25410.50 | 01-JAN-13:50 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 157.29 | 10-FEB-05:10 |
General:Heating:EnergyTransfer | 6.85 | 0.00 | 01-JAN-00:10 | 25410.50 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 157.29 | 10-FEB-05:10 |
Cooling:EnergyTransfer | 24582.83 | 101438.94 | 22-JAN-06:00 | 1810433.24 | 07-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 304.43 | 0.00 | 01-JAN-00:10 | 102128.35 | 30-OCT-06:00 |
General:Cooling:EnergyTransfer | 24582.83 | 101438.94 | 22-JAN-06:00 | 1810433.24 | 07-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 304.43 | 0.00 | 01-JAN-00:10 | 102128.35 | 30-OCT-06:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 990.66 | 0.00 | 01-JAN-00:10 | 81388.75 | 21-AUG-05:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 990.66 | 0.00 | 01-JAN-00:10 | 81388.75 | 21-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 990.66 | 0.00 | 01-JAN-00:10 | 81388.75 | 21-AUG-05:20 |
EnergyTransfer:Zone:CORE_MID | 6058.14 | 0.00 | 01-JAN-00:10 | 452231.90 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6058.14 | 0.00 | 01-JAN-00:10 | 452231.90 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6058.14 | 0.00 | 01-JAN-00:10 | 452231.90 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 628.39 | 0.00 | 01-JAN-00:10 | 55159.61 | 05-SEP-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 628.39 | 0.00 | 01-JAN-00:10 | 55159.61 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 628.39 | 0.00 | 01-JAN-00:10 | 55159.61 | 05-SEP-05:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 172.68 | 0.00 | 01-JAN-00:10 | 16923.19 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 172.68 | 0.00 | 01-JAN-00:10 | 16923.19 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 172.68 | 0.00 | 01-JAN-00:10 | 16923.19 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 128.65 | 0.00 | 01-JAN-00:10 | 14160.36 | 04-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 128.65 | 0.00 | 01-JAN-00:10 | 14160.36 | 04-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 128.65 | 0.00 | 01-JAN-00:10 | 14160.36 | 04-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 199.39 | 0.00 | 01-JAN-00:10 | 18942.76 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 199.39 | 0.00 | 01-JAN-00:10 | 18942.76 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 199.39 | 0.00 | 01-JAN-00:10 | 18942.76 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 158.90 | 0.00 | 01-JAN-00:10 | 16046.79 | 10-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 158.90 | 0.00 | 01-JAN-00:10 | 16046.79 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 158.90 | 0.00 | 01-JAN-00:10 | 16046.79 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1253.26 | 0.00 | 01-JAN-00:10 | 142751.18 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1253.26 | 0.00 | 01-JAN-00:10 | 142751.18 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1253.26 | 0.00 | 01-JAN-00:10 | 142751.18 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1004.95 | 0.00 | 01-JAN-00:10 | 130062.78 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1004.95 | 0.00 | 01-JAN-00:10 | 130062.78 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1004.95 | 0.00 | 01-JAN-00:10 | 130062.78 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1589.25 | 0.00 | 01-JAN-00:10 | 167871.50 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1589.25 | 0.00 | 01-JAN-00:10 | 167871.50 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1589.25 | 0.00 | 01-JAN-00:10 | 167871.50 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1094.17 | 0.00 | 01-JAN-00:10 | 133339.86 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1094.17 | 0.00 | 01-JAN-00:10 | 133339.86 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1094.17 | 0.00 | 01-JAN-00:10 | 133339.86 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 129.75 | 0.00 | 01-JAN-00:10 | 15396.96 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 105.89 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 105.89 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 129.75 | 0.00 | 01-JAN-00:10 | 15396.96 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 129.75 | 0.00 | 01-JAN-00:10 | 15396.96 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 106.01 | 0.00 | 01-JAN-00:10 | 13022.28 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 26.19 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 26.19 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 106.01 | 0.00 | 01-JAN-00:10 | 13022.28 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 106.01 | 0.00 | 01-JAN-00:10 | 13022.28 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 162.08 | 0.00 | 01-JAN-00:10 | 17592.16 | 05-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 162.08 | 0.00 | 01-JAN-00:10 | 17592.16 | 05-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 162.08 | 0.00 | 01-JAN-00:10 | 17592.16 | 05-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.80 | 0.00 | 01-JAN-00:10 | 14015.13 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.80 | 0.00 | 01-JAN-00:10 | 14015.13 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.80 | 0.00 | 01-JAN-00:10 | 14015.13 | 10-AUG-15:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 188.76 | 0.00 | 01-JAN-00:10 | 23747.60 | 07-AUG-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.74 | 0.00 | 01-JAN-00:10 | 3081.75 | 16-JAN-10:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.74 | 0.00 | 01-JAN-00:10 | 3081.75 | 16-JAN-10:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 188.01 | 0.00 | 01-JAN-00:10 | 23747.60 | 07-AUG-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 188.01 | 0.00 | 01-JAN-00:10 | 23747.60 | 07-AUG-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1250.07 | 0.00 | 01-JAN-00:10 | 151389.23 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.36 | 0.00 | 01-JAN-00:10 | 25245.22 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.36 | 0.00 | 01-JAN-00:10 | 25245.22 | 01-JAN-13:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1245.71 | 0.00 | 01-JAN-00:10 | 151389.23 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1245.71 | 0.00 | 01-JAN-00:10 | 151389.23 | 07-AUG-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 180.21 | 0.00 | 01-JAN-00:10 | 27393.08 | 16-AUG-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.74 | 0.00 | 01-JAN-00:10 | 5491.30 | 28-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.74 | 0.00 | 01-JAN-00:10 | 5491.30 | 28-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 178.47 | 0.00 | 01-JAN-00:10 | 27393.08 | 16-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 178.47 | 0.00 | 01-JAN-00:10 | 27393.08 | 16-AUG-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 146.16 | 1277.19 | 21-JAN-08:00 | 7869.57 | 30-APR-21:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 146.16 | 1277.19 | 21-JAN-08:00 | 7869.57 | 30-APR-21:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 146.16 | 1277.19 | 21-JAN-08:00 | 7869.57 | 30-APR-21:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1353.00 | 8551.40 | 21-JAN-08:00 | 73747.03 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1353.00 | 8551.40 | 21-JAN-08:00 | 73747.03 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1353.00 | 8551.40 | 21-JAN-08:00 | 73747.03 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 135.00 | 354.88 | 01-JAN-08:30 | 7599.66 | 23-APR-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 135.00 | 354.88 | 01-JAN-08:30 | 7599.66 | 23-APR-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 135.00 | 354.88 | 01-JAN-08:30 | 7599.66 | 23-APR-17:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7243.96 | 89261.23 | 21-JAN-20:00 | 371661.62 | 04-AUG-14:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7243.96 | 89261.23 | 21-JAN-20:00 | 371661.62 | 04-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7243.96 | 89261.23 | 21-JAN-20:00 | 371661.62 | 04-AUG-14:10 |
PlantLoopHeatingDemand:Facility | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 36978.08 | 142700.25 | 21-JAN-05:50 | 3432014.47 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.03 | 0.00 | 01-JAN-00:10 | 1994.36 | 02-JAN-07:00 |
CoolingCoils:EnergyTransfer | 36978.05 | 142700.25 | 21-JAN-05:50 | 3432014.47 | 10-AUG-16:00 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 83365.35 | 0.00 | 01-JAN-00:10 | 9190321.83 | 10-AUG-16:00 |
LoopToLoop:EnergyTransfer | 26773.71 | 0.00 | 01-JAN-00:10 | 2898533.18 | 10-AUG-16:00 |
WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
Chillers:EnergyTransfer | 26532.26 | 0.00 | 01-JAN-00:10 | 2898339.53 | 10-AUG-16:00 |
HeatRejection:EnergyTransfer | 29784.12 | 0.00 | 01-JAN-00:10 | 3374572.47 | 10-AUG-16:00 |
General:HeatRejection:EnergyTransfer | 29784.12 | 0.00 | 01-JAN-00:10 | 3374572.47 | 10-AUG-16:00 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -304.415 | 0.000 | 0.000 | 62.564 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -348.275 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -990.662 | 0.000 | 0.000 | 83.282 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 468.930 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6058.156 | 0.000 | 0.000 | 834.913 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 838.749 | 0.000 | 0.000 | 0.000 | 0.000 | -0.020 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -628.390 | 0.000 | 0.000 | 83.566 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 106.374 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -172.677 | 0.000 | 0.000 | 10.457 | 10.532 | 36.365 | 61.230 | 0.000 | 0.762 | 70.614 | 0.000 | -17.027 | 0.000 | -0.256 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -128.653 | 0.000 | 0.000 | 6.735 | 6.773 | 23.435 | 63.266 | 0.000 | 0.505 | 38.626 | 0.000 | -10.516 | 0.000 | -0.171 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -199.394 | 0.000 | 0.000 | 10.446 | 10.441 | 36.366 | 99.243 | 0.000 | 0.756 | 59.295 | 0.000 | -16.873 | 0.000 | -0.281 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -158.903 | 0.000 | 0.000 | 6.724 | 6.764 | 23.435 | 63.055 | 0.000 | 0.497 | 72.069 | 0.000 | -13.423 | 0.000 | -0.218 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1253.258 | 0.000 | 0.000 | 105.062 | 105.166 | 363.654 | 645.437 | 0.000 | 18.150 | 170.174 | 0.000 | -149.003 | 0.000 | -5.381 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -1004.954 | 0.000 | 0.000 | 49.407 | 67.649 | 234.352 | 643.499 | 0.000 | 11.729 | 100.265 | 0.000 | -97.990 | 0.000 | -3.958 | -0.004 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1589.248 | 0.000 | 0.000 | 104.639 | 104.323 | 363.660 | 1012.376 | 0.000 | 17.757 | 152.179 | 0.000 | -159.088 | 0.000 | -6.597 | -0.006 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1094.165 | 0.000 | 0.000 | 67.492 | 67.541 | 234.351 | 651.636 | 0.000 | 11.656 | 177.483 | 0.000 | -111.730 | 0.000 | -4.263 | -0.008 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -129.752 | 0.000 | 0.000 | 10.541 | 10.516 | 36.365 | 63.956 | 0.000 | 2.201 | 21.246 | 0.000 | -14.433 | 0.000 | -0.640 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -106.006 | 0.000 | 0.000 | 6.758 | 6.765 | 23.435 | 64.192 | 0.000 | 1.436 | 13.418 | 0.000 | -9.527 | 0.000 | -0.471 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -162.078 | 0.000 | 0.000 | 10.480 | 10.432 | 36.366 | 100.506 | 0.000 | 2.157 | 18.453 | 0.000 | -15.520 | 0.000 | -0.796 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -111.796 | 0.000 | 0.000 | 6.765 | 6.754 | 23.435 | 64.693 | 0.000 | 1.420 | 20.144 | 0.000 | -10.899 | 0.000 | -0.516 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -146.162 | 0.000 | 0.000 | 0.938 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -12.283 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1353.003 | 0.000 | 0.000 | 9.395 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -231.461 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -135.005 | 0.000 | 0.000 | 0.939 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.442 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7243.965 | 0.000 | 0.000 | 20.506 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -319.009 |
GROUNDFLOOR_PLENUM | 0.743 | -188.014 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.363 | 186.497 | 0.000 | 0.000 | 0.000 | -0.589 | 0.000 |
MIDFLOOR_PLENUM | 4.362 | -1245.706 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.316 | 1224.851 | 0.000 | 0.000 | 0.000 | -9.823 | 0.000 |
TOPFLOOR_PLENUM | 1.743 | -178.471 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.826 | 174.946 | 0.000 | 0.000 | 0.000 | -1.046 | -0.002 |
Total Facility | 6.849 | -1612.191 | 0.000 | -22970.643 | 0.000 | 0.000 | 1491.609 | 2456.550 | 14676.396 | 3533.089 | 0.000 | 99.532 | 3914.320 | 0.000 | -626.030 | 0.000 | -35.004 | -934.514 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-05:51 | 0.00 | 0.00 | 0.00 | -116562.59 | 0.00 | 0.00 | 539.95 | 1638.29 | 13457.54 | 0.00 | 0.00 | 0.00 | 100926.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | -100924.21 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 94449.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-NOV-05:13 | 0.00 | 0.00 | 0.00 | -888142.14 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 823392.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-05:04 | 0.00 | 0.00 | 0.00 | -86165.29 | 0.00 | 0.00 | 803.13 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 77177.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-16:22 | 0.00 | 0.00 | 0.00 | -22696.70 | 0.00 | 0.00 | 37.75 | 43.94 | 720.18 | 5262.12 | 0.00 | 124.90 | 16507.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 25-JUN-10:22 | 0.00 | 0.00 | 0.00 | -19636.71 | 0.00 | 0.00 | 22.34 | 28.32 | 464.11 | 7675.53 | 0.00 | 36.66 | 11409.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-13:03 | 0.00 | 0.00 | 0.00 | -27937.05 | 0.00 | 0.00 | 32.25 | 43.94 | 720.19 | 14804.81 | 0.00 | 51.67 | 12284.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-15:41 | 0.00 | 0.00 | 0.00 | -25963.75 | 0.00 | 0.00 | 19.82 | 28.32 | 464.11 | 8693.35 | 0.00 | 62.60 | 16695.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | -235101.35 | 0.00 | 0.00 | 369.85 | 439.44 | 7201.84 | 60628.88 | 0.00 | 4470.64 | 161990.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-10:11 | 0.00 | 0.00 | 0.00 | -211607.64 | 0.00 | 0.00 | 211.69 | 283.19 | 4641.14 | 82219.00 | 0.00 | 2040.40 | 122212.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | -273772.64 | 0.00 | 0.00 | 336.06 | 439.45 | 7201.95 | 73301.09 | 0.00 | 4260.92 | 188233.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-16:11 | 0.00 | 0.00 | 0.00 | -249546.75 | 0.00 | 0.00 | 184.69 | 283.19 | 4641.11 | 92725.13 | 0.00 | 2796.86 | 148915.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 03-SEP-14:51 | 0.00 | 0.00 | 0.00 | -26069.06 | 0.00 | 0.00 | 36.11 | 43.94 | 720.18 | 5755.82 | 0.00 | 564.60 | 18948.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-10:11 | 0.00 | 0.00 | 0.00 | -22084.17 | 0.00 | 0.00 | 20.39 | 28.32 | 464.11 | 8138.55 | 0.00 | 245.33 | 13187.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-14:51 | 0.00 | 0.00 | 0.00 | -29986.91 | 0.00 | 0.00 | 32.41 | 43.94 | 720.19 | 7797.92 | 0.00 | 527.45 | 20864.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 03-SEP-14:51 | 0.00 | 0.00 | 0.00 | -26118.28 | 0.00 | 0.00 | 19.03 | 28.32 | 464.11 | 9335.10 | 0.00 | 343.31 | 15928.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-21:03 | 0.00 | 0.00 | 0.00 | -7876.47 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 64.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 23-APR-17:42 | 0.00 | 0.00 | 0.00 | -73746.77 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4373.37 |
DATACENTER_TOP_ZN_6 | 23-APR-17:22 | 0.00 | 0.00 | 0.00 | -7602.20 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -209.82 |
DATACENTER_BASEMENT_ZN_6 | 10-AUG-21:01 | 0.00 | 0.00 | 0.00 | -374740.16 | 0.00 | 0.00 | 112.62 | 461.93 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5466.91 |
GROUNDFLOOR_PLENUM | 24-JUL-05:20 | 0.00 | -25978.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 | 25968.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-05:12 | 0.00 | -218633.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.68 | 218294.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 04-SEP-15:31 | 0.00 | -28841.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.86 | 28130.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -148675.18 | 0.00 | -2266891.83 | 0.00 | 0.00 | 14400.76 | 10593.62 | 616289.16 | 30473.51 | 0.00 | 1303.28 | 1742506.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-FEB-05:10 | 0.00 | 0.00 | 157.11 | 0.00 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14213.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:07 | 0.00 | 0.00 | 317.65 | 0.00 | 0.00 | 0.00 | 138.85 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 1286.70 | 0.00 | -2750.89 | 0.00 | -20.03 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:07 | 0.00 | 0.00 | 78.55 | 0.00 | 0.00 | 0.00 | 89.34 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 1037.38 | 0.00 | -1854.22 | 0.00 | -13.36 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-DEC-05:11 | 11511.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -105.73 | -11405.53 |
MIDFLOOR_PLENUM | 21-FEB-05:11 | 70910.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4210.53 | -66699.48 |
TOPFLOOR_PLENUM | 21-FEB-06:03 | 15524.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -91.30 | -15433.32 |
Total Facility | 21-FEB-05:11 | -1293573.18 | 1373665.28 | 0.00 | -1373665.28 | 0.00 | 0.00 | 0.00 | 10593.62 | 350716.63 | 0.00 | 0.00 | 0.00 | 1060103.02 | 0.00 | -114105.37 | 0.00 | -13734.71 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.0541 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0469 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 106.2843 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 94.4622 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.0633 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7338 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4765 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4765 | 0.2191 | 1.0000 | Not calculated | 1.2002 | 0.2191 | ||
AIRLOOP DATACENTER BASEMENT | 24.6146 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.6148 | 0.0137 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.4719 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4719 | 0.0331 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5013 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5013 | 0.0347 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4538 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4538 | 0.0344 | 1.0000 | Not calculated | 0.0156 | 0.0344 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5271 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2870 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.1422 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8703 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5316 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2874 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.6146 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.6146 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.4719 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4719 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5013 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5013 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4538 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4538 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0344 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.4765 | 5.4765 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8864 | 5.8864 | 1.6188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.0193 | 56.0193 | 16.1896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6616 | 5.6616 | 1.6192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2718 | 1.2718 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0703 | 1.0703 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4280 | 1.4280 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3976 | 1.3976 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.5991 | 12.5991 | 2.0284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1713 | 11.1713 | 1.3070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.1265 | 14.1265 | 2.0342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3681 | 12.3681 | 1.3110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3930 | 1.3930 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1472 | 1.1472 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5388 | 1.5388 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3227 | 1.3227 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4719 | 0.4719 | 0.4719 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5013 | 4.5013 | 4.5013 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4538 | 0.4538 | 0.4538 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.6146 | 24.6146 | 24.6146 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.0541 | 10.0469 | 11.0541 | 2.2870 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 106.2843 | 94.4622 | 106.2843 | 22.8703 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.0633 | 10.7338 | 11.0633 | 2.2874 | 0.0000 | 1.0000 |
CAV_BAS | 5.4765 | 5.4765 | 5.4765 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.6146 | 24.6148 | 24.6146 | 24.6146 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4719 | 0.4719 | 0.4719 | 0.4719 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5013 | 4.5013 | 4.5013 | 4.5013 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4538 | 0.4538 | 0.4538 | 0.4538 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9432 | 2.9432 | 1.6188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.0097 | 28.0097 | 16.1896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8308 | 2.8308 | 1.6192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6359 | 0.6359 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5351 | 0.5351 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7140 | 0.7140 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6988 | 0.6988 | 0.1314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2995 | 6.2995 | 2.0284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5857 | 5.5857 | 1.3070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0632 | 7.0632 | 2.0342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1841 | 6.1841 | 1.3110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6965 | 0.6965 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5736 | 0.5736 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7694 | 0.7694 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6614 | 0.6614 | 0.1309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4719 | 0.4719 | 0.4719 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5013 | 4.5013 | 4.5013 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4538 | 0.4538 | 0.4538 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.6146 | 24.6146 | 24.6146 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5271 | 2.2870 | 2.2870 | 2.2870 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.1422 | 22.8703 | 22.8703 | 22.8703 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5316 | 2.2874 | 2.2874 | 2.2874 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.6146 | 24.6146 | 24.6146 | 24.6146 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4719 | 0.4719 | 0.4719 | 0.4719 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5013 | 4.5013 | 4.5013 | 4.5013 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4538 | 0.4538 | 0.4538 | 0.4538 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 4038.33 |
Number of hours not met | 4038.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.03 | 1994.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6616.26 | 694580.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2456.55 | 240337.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 348.98 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.67 | 3409.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2940.31 | 267139.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 929.28 | 55450.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2008.67 | 86931.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 14.06 | 13579.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 279.92 | 37717.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 32836.72 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 32836.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.03 |
Space Heating | 0.00 |
Space Cooling | 142.84 |
Fans (All) | 63.48 |
Service Water Heating | 6.04 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 708.90 |
Subtotal | 708.90 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.48 |
Space Heating | 0.00 |
Space Cooling | 20.15 |
Fans (All) | 8.95 |
Service Water Heating | 0.85 |
Receptacle Equipment | 44.70 |
Miscellaneous | 17.87 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 915. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 2458.50 | 1224.50 | 461.67 | 4530.50 | 84.83 |
CORE_BOTTOM | 8432.33 | 327.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7853.00 | 907.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7708.00 | 1052.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7718.00 | 1042.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6732.33 | 2027.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8336.00 | 424.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7954.33 | 805.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7913.50 | 846.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7518.00 | 1242.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8229.00 | 531.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7881.83 | 878.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7840.33 | 919.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7494.17 | 1265.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6237.00 | 2523.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6054.67 | 2705.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6126.67 | 2633.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8042.17 | 717.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7103.83 | 1656.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8601.00 | 159.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7773.83 | 986.17 | 0.00 | 0.00 | 0.00 |
Min | 2458.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2705.33 | 461.67 | 4530.50 | 84.83 |
Average | 7457.72 | 1081.54 | 20.07 | 196.98 | 3.69 |
Sum | 171527.67 | 24875.33 | 461.67 | 4530.50 | 84.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 123874.83 | 24381.83 | 21502.00 | 186949.33 | 11908.00 |
CORE_BOTTOM | 330216.00 | 597.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330810.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1446.33 | 821.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1403.17 | 864.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1412.00 | 856.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 89079.67 | 14315.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 24381.83 | 21502.00 | 186949.33 | 11908.00 |
Average | 68934.96 | 1819.12 | 934.87 | 8128.23 | 517.74 |
Sum | 1585504.00 | 41839.67 | 21502.00 | 186949.33 | 11908.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 2039.50 | 1658.67 | 295.33 | 2159.17 | 2607.33 |
CORE_BOTTOM | 5746.17 | 3013.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7357.33 | 1402.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6898.33 | 1861.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6083.50 | 2676.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6122.17 | 2637.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5782.17 | 2977.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5425.33 | 3334.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6086.33 | 2673.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5897.67 | 2862.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5731.67 | 3028.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5769.33 | 2990.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6122.17 | 2637.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5949.50 | 2810.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5803.33 | 2956.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5823.17 | 2936.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7188.17 | 1571.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7121.67 | 1638.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7183.67 | 1576.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8568.50 | 191.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 4896.00 | 3864.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3369.83 | 5390.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3239.00 | 5521.00 | 0.00 | 0.00 | 0.00 |
Min | 2039.50 | 191.50 | 0.00 | 0.00 | 0.00 |
Max | 8568.50 | 5521.00 | 295.33 | 2159.17 | 2607.33 |
Average | 5834.98 | 2704.94 | 12.84 | 93.88 | 113.36 |
Sum | 134204.50 | 62213.67 | 295.33 | 2159.17 | 2607.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 121989.83 | 28160.00 | 15412.50 | 63856.17 | 139197.50 |
CORE_BOTTOM | 325261.00 | 5552.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328429.00 | 2384.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 326959.00 | 3854.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38872.67 | 52.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24902.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1773.00 | 495.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1717.00 | 551.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1736.00 | 532.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98520.50 | 4874.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328429.00 | 28160.00 | 15412.50 | 63856.17 | 139197.50 |
Average | 68816.31 | 2020.07 | 670.11 | 2776.36 | 6052.07 |
Sum | 1582775.17 | 46461.67 | 15412.50 | 63856.17 | 139197.50 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.593225E+11 | 110264.16 | 01-JAN-18:32 | 19.57 | 15.21 | 0.579108E+10 | 11209.16 | 30-JAN-14:00 | 22.00 | 20.56 |
February | 0.481812E+11 | 100845.80 | 21-FEB-05:11 | 14.67 | 13.69 | 0.561059E+10 | 11845.72 | 07-FEB-14:00 | 14.67 | 13.69 |
March | 0.483432E+11 | 98924.62 | 08-MAR-05:12 | 14.67 | 11.01 | 0.710240E+10 | 11807.53 | 28-MAR-13:00 | 31.00 | 19.33 |
April | 0.265553E+11 | 99666.90 | 13-APR-04:50 | 19.02 | 14.96 | 0.736785E+10 | 12760.91 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.435225E+10 | 98436.51 | 01-MAY-04:22 | 21.65 | 21.48 | 0.952469E+10 | 12816.30 | 31-MAY-13:00 | 38.00 | 26.73 |
June | 0.386011E+10 | 89922.32 | 22-JUN-10:05 | 38.00 | 24.19 | 0.979081E+10 | 13043.83 | 16-JUN-13:00 | 38.00 | 24.19 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 | 27.02 | 0.955298E+10 | 13373.21 | 21-JUL-13:00 | 42.00 | 27.65 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 | 28.28 | 0.110378E+11 | 13755.24 | 18-AUG-13:00 | 38.00 | 27.45 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 | 25.04 | 0.961135E+10 | 13652.27 | 01-SEP-13:00 | 39.10 | 25.51 |
October | 0.877978E+10 | 116576.28 | 30-OCT-05:51 | 21.90 | 17.76 | 0.968448E+10 | 13682.18 | 10-OCT-13:00 | 21.90 | 17.76 |
November | 0.455149E+11 | 106958.55 | 05-NOV-05:52 | 20.00 | 15.15 | 0.718851E+10 | 13060.07 | 03-NOV-13:00 | 20.00 | 15.15 |
December | 0.595196E+11 | 108911.26 | 12-DEC-22:17 | 19.80 | 14.62 | 0.586109E+10 | 12179.00 | 12-DEC-14:00 | 19.80 | 14.62 |
Annual Sum or Average | 0.304429E+12 | 0.981236E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.67 | 11.01 | 0.561059E+10 | 11209.16 | 14.67 | 13.69 | ||
Maximum of Months | 0.595196E+11 | 116576.28 | 38.00 | 28.28 | 0.110378E+11 | 13755.24 | 42.00 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492326E+11 | 99412.64 | 02-JAN-05:11 | 13.67 | 11.10 | 0.507998E+10 | 6734.85 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.509347E+11 | 99844.75 | 08-FEB-05:13 | 22.00 | 18.65 | 0.460984E+10 | 6734.92 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.691177E+11 | 97359.11 | 16-MAR-04:13 | 15.67 | 12.92 | 0.550006E+10 | 6735.13 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.784491E+11 | 95379.65 | 13-APR-04:13 | 19.07 | 15.51 | 0.488568E+10 | 6774.57 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.922583E+11 | 98464.49 | 01-MAY-04:23 | 21.65 | 21.48 | 0.529949E+10 | 6764.68 | 08-MAY-13:00 | 35.00 | 24.82 |
June | 0.970356E+11 | 98874.51 | 05-JUN-03:03 | 29.88 | 24.74 | 0.528351E+10 | 6761.30 | 20-JUN-13:00 | 38.00 | 26.22 |
July | 0.103145E+12 | 99851.56 | 05-JUL-03:03 | 30.02 | 27.78 | 0.491965E+10 | 6766.84 | 27-JUL-13:00 | 37.00 | 29.28 |
August | 0.115388E+12 | 99927.03 | 28-AUG-03:03 | 31.07 | 27.26 | 0.552462E+10 | 6780.69 | 15-AUG-13:00 | 31.07 | 27.26 |
September | 0.968431E+11 | 95193.92 | 11-SEP-04:25 | 29.25 | 27.56 | 0.489812E+10 | 6749.27 | 11-SEP-13:00 | 35.00 | 27.36 |
October | 0.982980E+11 | 99630.10 | 30-OCT-04:23 | 22.55 | 18.27 | 0.509041E+10 | 6736.51 | 19-OCT-09:30 | 22.55 | 18.27 |
November | 0.764879E+11 | 100951.66 | 27-NOV-05:13 | 18.00 | 16.14 | 0.503336E+10 | 6736.30 | 03-NOV-09:09 | 18.00 | 16.14 |
December | 0.634696E+11 | 97407.59 | 28-DEC-05:11 | 15.00 | 12.67 | 0.490216E+10 | 6734.81 | 20-DEC-10:20 | 15.00 | 12.67 |
Annual Sum or Average | 0.990659E+12 | 0.610269E+11 | ||||||||
Minimum of Months | 0.492326E+11 | 95193.92 | 13.67 | 11.10 | 0.460984E+10 | 6734.81 | 15.00 | 12.67 | ||
Maximum of Months | 0.115388E+12 | 100951.66 | 31.07 | 27.78 | 0.552462E+10 | 6780.69 | 38.00 | 29.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371186E+11 | 82939.61 | 31-JAN-05:12 | 16.67 | 14.41 | 0.506509E+10 | 6734.84 | 09-JAN-10:20 | 16.67 | 14.41 |
February | 0.361152E+11 | 85582.64 | 21-FEB-05:11 | 14.67 | 13.69 | 0.460004E+10 | 6734.96 | 15-FEB-14:09 | 14.67 | 13.69 |
March | 0.462363E+11 | 86210.38 | 06-MAR-05:12 | 16.67 | 12.96 | 0.549659E+10 | 6735.15 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.477690E+11 | 85678.64 | 13-APR-04:12 | 19.07 | 15.51 | 0.487818E+10 | 6735.23 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.577311E+11 | 80595.50 | 04-MAY-04:13 | 23.53 | 18.44 | 0.527864E+10 | 6735.06 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.588619E+11 | 67443.30 | 12-JUN-05:02 | 29.02 | 24.10 | 0.526140E+10 | 6734.91 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.600448E+11 | 72823.61 | 05-JUL-05:03 | 30.00 | 28.44 | 0.488655E+10 | 6735.20 | 03-JUL-09:09 | 30.00 | 28.44 |
August | 0.639877E+11 | 74120.10 | 07-AUG-05:01 | 32.82 | 23.16 | 0.548892E+10 | 6734.72 | 03-AUG-13:20 | 32.82 | 23.16 |
September | 0.567402E+11 | 76919.49 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487404E+10 | 6734.77 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.543699E+11 | 88808.24 | 20-OCT-04:13 | 22.60 | 16.22 | 0.507110E+10 | 6734.73 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.470632E+11 | 88832.26 | 13-NOV-05:13 | 21.00 | 17.39 | 0.502528E+10 | 6734.77 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.397762E+11 | 85157.55 | 06-DEC-05:11 | 18.00 | 17.36 | 0.489133E+10 | 6734.81 | 01-DEC-14:20 | 18.00 | 17.36 |
Annual Sum or Average | 0.605814E+12 | 0.608172E+11 | ||||||||
Minimum of Months | 0.361152E+11 | 67443.30 | 14.67 | 12.96 | 0.460004E+10 | 6734.72 | 14.67 | 13.69 | ||
Maximum of Months | 0.639877E+11 | 88832.26 | 32.82 | 28.44 | 0.549659E+10 | 6735.23 | 35.75 | 28.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325321E+11 | 83871.39 | 30-JAN-05:12 | 20.00 | 17.44 | 0.501887E+10 | 6734.81 | 09-JAN-10:20 | 20.00 | 17.44 |
February | 0.333704E+11 | 84765.71 | 09-FEB-05:11 | 23.00 | 19.02 | 0.457666E+10 | 6734.93 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.450302E+11 | 84518.78 | 24-MAR-04:12 | 20.07 | 19.04 | 0.548766E+10 | 6735.15 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.492728E+11 | 84640.55 | 13-APR-04:12 | 19.07 | 15.51 | 0.487912E+10 | 6735.20 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.631331E+11 | 80037.89 | 03-MAY-04:12 | 23.10 | 18.53 | 0.528372E+10 | 6735.03 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.652000E+11 | 83633.82 | 12-JUN-05:03 | 29.02 | 24.10 | 0.526588E+10 | 6734.90 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.677943E+11 | 84676.43 | 05-JUL-05:03 | 30.00 | 28.44 | 0.489426E+10 | 6735.19 | 03-JUL-09:09 | 30.00 | 28.44 |
August | 0.717700E+11 | 86185.79 | 07-AUG-05:04 | 32.82 | 23.16 | 0.549485E+10 | 6734.67 | 21-AUG-09:20 | 32.67 | 28.09 |
September | 0.616400E+11 | 84171.21 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487906E+10 | 6734.76 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.566291E+11 | 82918.88 | 21-OCT-04:12 | 22.40 | 15.15 | 0.507396E+10 | 6734.73 | 20-OCT-09:20 | 22.40 | 15.15 |
November | 0.458745E+11 | 85411.15 | 13-NOV-05:12 | 21.00 | 17.39 | 0.502341E+10 | 6734.75 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.361428E+11 | 85371.98 | 11-DEC-05:12 | 22.00 | 18.87 | 0.486484E+10 | 6734.79 | 01-DEC-14:20 | 22.00 | 18.87 |
Annual Sum or Average | 0.628389E+12 | 0.607423E+11 | ||||||||
Minimum of Months | 0.325321E+11 | 80037.89 | 19.07 | 15.15 | 0.457666E+10 | 6734.67 | 20.00 | 15.15 | ||
Maximum of Months | 0.717700E+11 | 86185.79 | 32.82 | 28.44 | 0.549485E+10 | 6735.20 | 35.75 | 28.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502269E+10 | 12985.19 | 30-JAN-06:03 | 20.03 | 17.43 | 0.632676E+09 | 845.63 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.605999E+10 | 17323.50 | 08-FEB-05:12 | 22.00 | 18.65 | 0.576766E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.973158E+10 | 16473.52 | 02-MAR-05:12 | 29.07 | 15.68 | 0.690181E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.128160E+11 | 20552.28 | 30-APR-16:22 | 31.25 | 25.60 | 0.614413E+09 | 852.79 | 28-APR-13:00 | 31.25 | 25.60 |
May | 0.182643E+11 | 21994.03 | 28-MAY-11:02 | 34.92 | 25.77 | 0.666911E+09 | 851.16 | 08-MAY-13:00 | 34.92 | 25.77 |
June | 0.204087E+11 | 22705.74 | 25-JUN-16:22 | 34.80 | 28.07 | 0.664715E+09 | 850.55 | 20-JUN-13:00 | 34.80 | 28.07 |
July | 0.225741E+11 | 22316.68 | 30-JUL-14:22 | 42.50 | 25.87 | 0.619523E+09 | 851.57 | 27-JUL-13:00 | 42.50 | 25.87 |
August | 0.243484E+11 | 21646.50 | 05-AUG-17:42 | 40.17 | 26.20 | 0.695418E+09 | 854.14 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.185580E+11 | 21768.12 | 03-SEP-15:42 | 37.50 | 26.65 | 0.616138E+09 | 848.15 | 11-SEP-13:00 | 35.00 | 27.36 |
October | 0.164628E+11 | 21145.30 | 09-OCT-13:02 | 37.50 | 19.97 | 0.639855E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.110582E+11 | 17343.56 | 30-NOV-05:11 | 19.67 | 18.31 | 0.632129E+09 | 845.63 | 16-NOV-14:50 | 19.67 | 18.31 |
December | 0.737213E+10 | 14983.71 | 12-DEC-06:02 | 23.03 | 17.89 | 0.614083E+09 | 845.63 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.172677E+12 | 0.766281E+10 | ||||||||
Minimum of Months | 0.502269E+10 | 12985.19 | 19.67 | 15.68 | 0.576766E+09 | 845.62 | 19.67 | 17.43 | ||
Maximum of Months | 0.243484E+11 | 22705.74 | 42.50 | 28.07 | 0.695418E+09 | 854.14 | 42.50 | 28.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395847E+10 | 9033.65 | 30-JAN-05:12 | 20.00 | 17.44 | 0.409340E+09 | 544.96 | 24-JAN-10:00 | 20.00 | 17.44 |
February | 0.456909E+10 | 13795.40 | 08-FEB-05:12 | 22.00 | 18.65 | 0.372206E+09 | 544.97 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.704814E+10 | 11715.69 | 28-MAR-05:02 | 25.67 | 14.74 | 0.444863E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.948165E+10 | 17118.11 | 30-APR-10:22 | 31.50 | 22.64 | 0.396155E+09 | 550.04 | 28-APR-13:00 | 31.50 | 22.64 |
May | 0.142882E+11 | 19568.29 | 28-MAY-10:22 | 34.10 | 25.37 | 0.430050E+09 | 548.96 | 08-MAY-13:00 | 34.10 | 25.37 |
June | 0.150950E+11 | 19646.37 | 25-JUN-10:22 | 35.15 | 25.69 | 0.428505E+09 | 548.39 | 20-JUN-13:00 | 35.15 | 25.69 |
July | 0.163694E+11 | 19488.22 | 30-JUL-09:42 | 41.80 | 21.60 | 0.399438E+09 | 549.05 | 27-JUL-13:00 | 41.80 | 21.60 |
August | 0.177497E+11 | 18569.41 | 13-AUG-10:22 | 38.80 | 25.02 | 0.448374E+09 | 550.86 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.144455E+11 | 18743.10 | 03-SEP-10:22 | 38.00 | 23.76 | 0.397303E+09 | 546.73 | 11-SEP-13:00 | 35.00 | 27.36 |
October | 0.126101E+11 | 18456.14 | 22-OCT-08:53 | 31.90 | 22.98 | 0.412592E+09 | 544.95 | 20-OCT-09:20 | 31.90 | 22.98 |
November | 0.806672E+10 | 14856.83 | 05-NOV-10:23 | 30.85 | 19.47 | 0.407642E+09 | 544.95 | 16-NOV-14:50 | 30.17 | 19.09 |
December | 0.497093E+10 | 10422.94 | 12-DEC-06:02 | 23.03 | 17.89 | 0.395590E+09 | 544.96 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.128653E+12 | 0.494206E+10 | ||||||||
Minimum of Months | 0.395847E+10 | 9033.65 | 20.00 | 14.74 | 0.372206E+09 | 544.95 | 20.00 | 17.44 | ||
Maximum of Months | 0.177497E+11 | 19646.37 | 41.80 | 25.69 | 0.448374E+09 | 550.86 | 41.80 | 27.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.889853E+10 | 19729.47 | 30-JAN-05:12 | 20.00 | 17.44 | 0.636560E+09 | 845.65 | 17-JAN-14:09 | 20.00 | 17.44 |
February | 0.949507E+10 | 25024.95 | 05-FEB-12:23 | 31.05 | 19.28 | 0.578329E+09 | 846.54 | 07-FEB-14:09 | 30.50 | 20.52 |
March | 0.126191E+11 | 24801.50 | 26-MAR-12:32 | 34.67 | 17.89 | 0.690918E+09 | 845.94 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.140324E+11 | 23076.66 | 30-APR-13:02 | 36.58 | 21.44 | 0.614761E+09 | 853.54 | 28-APR-13:00 | 36.58 | 21.44 |
May | 0.178380E+11 | 24346.56 | 28-MAY-11:02 | 34.92 | 25.77 | 0.666841E+09 | 851.32 | 08-MAY-13:00 | 34.92 | 25.77 |
June | 0.190592E+11 | 24745.21 | 25-JUN-14:21 | 35.50 | 28.88 | 0.664564E+09 | 850.44 | 20-JUN-13:00 | 35.50 | 28.88 |
July | 0.216417E+11 | 24985.63 | 30-JUL-13:42 | 44.08 | 24.34 | 0.619424E+09 | 851.60 | 27-JUL-13:00 | 44.08 | 24.34 |
August | 0.248268E+11 | 24122.86 | 20-AUG-13:02 | 38.67 | 26.76 | 0.695551E+09 | 854.69 | 15-AUG-13:00 | 38.67 | 26.76 |
September | 0.213344E+11 | 25648.49 | 24-SEP-13:03 | 34.50 | 26.27 | 0.616468E+09 | 848.60 | 11-SEP-13:00 | 34.50 | 26.27 |
October | 0.213939E+11 | 27931.09 | 29-OCT-13:03 | 34.92 | 15.89 | 0.640523E+09 | 846.28 | 20-OCT-13:00 | 34.92 | 15.89 |
November | 0.164509E+11 | 25189.53 | 26-NOV-12:43 | 27.58 | 19.87 | 0.633399E+09 | 846.32 | 13-NOV-14:09 | 27.58 | 19.87 |
December | 0.118029E+11 | 26235.67 | 03-DEC-12:52 | 29.80 | 17.63 | 0.616032E+09 | 845.99 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.199393E+12 | 0.767337E+10 | ||||||||
Minimum of Months | 0.889853E+10 | 19729.47 | 20.00 | 15.89 | 0.578329E+09 | 845.65 | 20.00 | 15.89 | ||
Maximum of Months | 0.248268E+11 | 27931.09 | 44.08 | 28.88 | 0.695551E+09 | 854.69 | 44.08 | 28.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547299E+10 | 18567.91 | 30-JAN-05:12 | 20.00 | 17.44 | 0.411144E+09 | 544.96 | 17-JAN-14:20 | 20.00 | 17.44 |
February | 0.696966E+10 | 20357.92 | 27-FEB-05:12 | 18.00 | 16.52 | 0.373751E+09 | 544.98 | 15-FEB-14:09 | 18.00 | 16.52 |
March | 0.112397E+11 | 20829.96 | 21-MAR-04:12 | 17.67 | 13.93 | 0.446324E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.139547E+11 | 24488.27 | 23-APR-16:22 | 31.75 | 18.84 | 0.397154E+09 | 551.07 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.144216E+11 | 25043.52 | 28-MAY-15:41 | 35.02 | 23.40 | 0.430124E+09 | 549.20 | 08-MAY-13:00 | 35.02 | 23.40 |
June | 0.166916E+11 | 25975.75 | 25-JUN-15:41 | 34.67 | 28.11 | 0.428653E+09 | 548.85 | 20-JUN-13:00 | 34.67 | 28.11 |
July | 0.189725E+11 | 24906.93 | 02-JUL-15:42 | 38.33 | 22.99 | 0.399676E+09 | 549.72 | 27-JUL-13:00 | 37.00 | 29.28 |
August | 0.217410E+11 | 24669.83 | 06-AUG-15:43 | 40.25 | 25.55 | 0.448872E+09 | 552.03 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.143408E+11 | 24267.56 | 03-SEP-15:42 | 37.50 | 26.65 | 0.397332E+09 | 546.87 | 11-SEP-13:00 | 35.00 | 27.36 |
October | 0.138223E+11 | 23386.32 | 09-OCT-15:02 | 36.97 | 20.38 | 0.412782E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.115557E+11 | 20843.07 | 28-NOV-05:12 | 19.00 | 15.91 | 0.408576E+09 | 544.96 | 16-NOV-14:50 | 19.00 | 15.91 |
December | 0.971963E+10 | 23801.95 | 03-DEC-14:12 | 27.00 | 20.88 | 0.398118E+09 | 544.96 | 01-DEC-14:09 | 27.00 | 20.88 |
Annual Sum or Average | 0.158902E+12 | 0.495251E+10 | ||||||||
Minimum of Months | 0.547299E+10 | 18567.91 | 17.67 | 13.93 | 0.373751E+09 | 544.95 | 18.00 | 15.91 | ||
Maximum of Months | 0.217410E+11 | 25975.75 | 40.25 | 28.11 | 0.448872E+09 | 552.03 | 40.00 | 29.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356508E+10 | 5278.47 | 23-JAN-14:10 | 27.50 | 16.66 | 0.616087E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.414897E+10 | 12380.62 | 09-FEB-06:02 | 22.92 | 19.06 | 0.567834E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.671831E+10 | 15332.78 | 27-MAR-04:12 | 22.43 | 13.90 | 0.686655E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.888268E+10 | 16056.68 | 23-APR-15:31 | 32.33 | 18.32 | 0.613391E+09 | 845.70 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.142598E+11 | 21960.89 | 07-MAY-15:41 | 34.58 | 21.82 | 0.665869E+09 | 845.68 | 04-MAY-13:00 | 34.58 | 21.82 |
June | 0.159226E+11 | 21668.78 | 04-JUN-16:01 | 36.83 | 28.89 | 0.663693E+09 | 845.64 | 02-JUN-13:09 | 36.83 | 28.89 |
July | 0.172303E+11 | 22011.60 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617783E+09 | 846.66 | 21-JUL-13:20 | 42.50 | 25.87 |
August | 0.179750E+11 | 22128.67 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692511E+09 | 846.79 | 02-AUG-13:20 | 40.85 | 24.99 |
September | 0.139416E+11 | 23518.25 | 04-SEP-15:31 | 40.80 | 24.09 | 0.614963E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.110162E+11 | 21429.96 | 15-OCT-14:21 | 34.50 | 20.54 | 0.639007E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.728711E+10 | 14941.19 | 10-NOV-06:02 | 21.87 | 20.45 | 0.630732E+09 | 845.62 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.437851E+10 | 12689.97 | 11-DEC-06:02 | 21.90 | 19.23 | 0.604636E+09 | 845.63 | 01-DEC-14:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.125326E+12 | 0.761316E+10 | ||||||||
Minimum of Months | 0.356508E+10 | 5278.47 | 21.87 | 13.90 | 0.567834E+09 | 845.62 | 21.90 | 16.66 | ||
Maximum of Months | 0.179750E+11 | 23518.25 | 42.50 | 28.89 | 0.692511E+09 | 846.79 | 42.50 | 28.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288326E+10 | 6403.46 | 24-JAN-11:05 | 24.00 | 18.08 | 0.298844E+09 | 548.51 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.342882E+10 | 10529.86 | 05-FEB-14:52 | 32.00 | 19.39 | 0.273166E+09 | 548.51 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.552608E+10 | 15629.04 | 26-MAR-13:32 | 33.67 | 18.36 | 0.327295E+09 | 548.54 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.760651E+10 | 19883.03 | 23-APR-10:12 | 32.80 | 16.75 | 0.292832E+09 | 548.53 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.116254E+11 | 20439.10 | 07-MAY-09:42 | 35.92 | 17.80 | 0.317454E+09 | 548.56 | 11-MAY-12:09 | 35.87 | 23.99 |
June | 0.122879E+11 | 20333.06 | 04-JUN-10:02 | 36.17 | 25.27 | 0.315911E+09 | 548.52 | 02-JUN-12:09 | 36.17 | 25.27 |
July | 0.132137E+11 | 20019.81 | 30-JUL-09:42 | 41.80 | 21.60 | 0.295169E+09 | 548.49 | 03-JUL-10:09 | 41.80 | 21.60 |
August | 0.141265E+11 | 19554.70 | 06-AUG-15:01 | 40.85 | 24.99 | 0.329619E+09 | 548.49 | 24-AUG-12:09 | 37.25 | 26.69 |
September | 0.112973E+11 | 21170.85 | 04-SEP-10:11 | 38.00 | 23.07 | 0.293430E+09 | 548.49 | 26-SEP-14:09 | 39.00 | 24.02 |
October | 0.909756E+10 | 19404.58 | 15-OCT-10:22 | 33.50 | 18.06 | 0.305265E+09 | 548.50 | 11-OCT-12:09 | 33.50 | 18.06 |
November | 0.598804E+10 | 16775.12 | 05-NOV-14:42 | 32.17 | 20.87 | 0.301434E+09 | 548.49 | 06-NOV-15:09 | 31.90 | 21.82 |
December | 0.341440E+10 | 9353.30 | 11-DEC-06:02 | 21.90 | 19.23 | 0.290596E+09 | 548.50 | 01-DEC-13:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.100495E+12 | 0.364101E+10 | ||||||||
Minimum of Months | 0.288326E+10 | 6403.46 | 21.90 | 16.75 | 0.273166E+09 | 548.49 | 21.90 | 18.06 | ||
Maximum of Months | 0.141265E+11 | 21170.85 | 41.80 | 25.27 | 0.329619E+09 | 548.56 | 41.80 | 26.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780808E+10 | 17173.78 | 22-JAN-14:33 | 26.00 | 16.51 | 0.633296E+09 | 845.66 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.802231E+10 | 25834.05 | 05-FEB-13:32 | 31.43 | 19.44 | 0.575809E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.100689E+11 | 25127.51 | 26-MAR-13:32 | 33.67 | 18.36 | 0.689603E+09 | 846.72 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.104953E+11 | 23228.61 | 02-APR-14:31 | 33.33 | 18.48 | 0.614087E+09 | 845.73 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.143242E+11 | 24562.74 | 07-MAY-15:41 | 34.58 | 21.82 | 0.665858E+09 | 845.70 | 04-MAY-13:00 | 34.58 | 21.82 |
June | 0.151328E+11 | 23944.81 | 04-JUN-16:01 | 36.83 | 28.89 | 0.663542E+09 | 845.66 | 02-JUN-13:09 | 36.83 | 28.89 |
July | 0.169698E+11 | 24686.36 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617723E+09 | 845.72 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.192382E+11 | 24852.51 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692667E+09 | 846.85 | 17-AUG-13:20 | 43.33 | 25.24 |
September | 0.174616E+11 | 27388.05 | 04-SEP-15:31 | 40.80 | 24.09 | 0.615525E+09 | 846.81 | 20-SEP-13:20 | 36.80 | 24.08 |
October | 0.167953E+11 | 26927.11 | 29-OCT-13:41 | 34.18 | 18.90 | 0.640345E+09 | 846.77 | 17-OCT-13:20 | 34.18 | 18.90 |
November | 0.133853E+11 | 26611.44 | 05-NOV-12:02 | 33.90 | 17.83 | 0.633327E+09 | 846.79 | 07-NOV-14:20 | 31.00 | 22.83 |
December | 0.922336E+10 | 24861.77 | 03-DEC-15:02 | 26.85 | 20.89 | 0.614087E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.158925E+12 | 0.765587E+10 | ||||||||
Minimum of Months | 0.780808E+10 | 17173.78 | 26.00 | 16.51 | 0.575809E+09 | 845.66 | 23.00 | 17.31 | ||
Maximum of Months | 0.192382E+11 | 27388.05 | 42.50 | 28.89 | 0.692667E+09 | 846.85 | 43.33 | 28.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328199E+10 | 8312.83 | 30-JAN-06:03 | 20.03 | 17.43 | 0.403269E+09 | 544.96 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.401425E+10 | 18276.61 | 05-FEB-15:32 | 32.00 | 19.08 | 0.369716E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.650352E+10 | 21470.69 | 26-MAR-16:52 | 31.20 | 18.81 | 0.444730E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.821707E+10 | 21668.14 | 09-APR-16:02 | 29.17 | 23.02 | 0.396282E+09 | 545.01 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.120553E+11 | 23120.00 | 07-MAY-15:41 | 34.58 | 21.82 | 0.429539E+09 | 545.00 | 04-MAY-13:00 | 34.58 | 21.82 |
June | 0.131376E+11 | 22337.36 | 04-JUN-17:21 | 35.00 | 28.83 | 0.428039E+09 | 544.96 | 02-JUN-13:09 | 35.00 | 28.83 |
July | 0.141467E+11 | 22035.50 | 30-JUL-15:02 | 40.45 | 27.73 | 0.398461E+09 | 545.00 | 03-JUL-09:09 | 40.45 | 27.73 |
August | 0.153405E+11 | 22716.49 | 06-AUG-16:21 | 40.05 | 25.93 | 0.446634E+09 | 544.95 | 04-AUG-09:20 | 40.05 | 25.93 |
September | 0.120225E+11 | 24966.75 | 04-SEP-16:11 | 40.47 | 23.66 | 0.396764E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.976970E+10 | 22190.06 | 15-OCT-14:21 | 34.50 | 20.54 | 0.412493E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.673193E+10 | 21784.23 | 05-NOV-15:22 | 31.70 | 21.27 | 0.407610E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.419544E+10 | 11952.26 | 11-DEC-06:02 | 21.90 | 19.23 | 0.394047E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.109417E+12 | 0.492759E+10 | ||||||||
Minimum of Months | 0.328199E+10 | 8312.83 | 20.03 | 17.43 | 0.369716E+09 | 544.95 | 20.03 | 17.43 | ||
Maximum of Months | 0.153405E+11 | 24966.75 | 40.47 | 28.83 | 0.446634E+09 | 545.01 | 40.45 | 28.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324473E+10 | 5515.54 | 23-JAN-14:10 | 27.50 | 16.66 | 0.601459E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.395320E+10 | 12249.19 | 06-FEB-06:02 | 21.88 | 19.06 | 0.559820E+09 | 845.65 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.665550E+10 | 17460.58 | 28-MAR-05:02 | 25.67 | 14.74 | 0.682911E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.909454E+10 | 21326.29 | 30-APR-13:31 | 35.03 | 22.43 | 0.612775E+09 | 845.70 | 28-APR-13:09 | 35.03 | 22.43 |
May | 0.150092E+11 | 24127.43 | 21-MAY-13:02 | 38.00 | 22.80 | 0.665984E+09 | 845.68 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.168435E+11 | 25920.73 | 04-JUN-16:11 | 36.67 | 28.92 | 0.663807E+09 | 845.65 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.184594E+11 | 24779.26 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617939E+09 | 845.70 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.192006E+11 | 24916.66 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692643E+09 | 845.76 | 17-AUG-13:50 | 42.33 | 26.20 |
September | 0.147046E+11 | 26076.85 | 03-SEP-14:51 | 38.00 | 27.45 | 0.615083E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.113125E+11 | 23956.13 | 01-OCT-12:42 | 34.50 | 25.92 | 0.639066E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.718106E+10 | 19981.96 | 05-NOV-14:52 | 32.00 | 20.75 | 0.629782E+09 | 845.62 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.409415E+10 | 13380.07 | 11-DEC-06:02 | 21.90 | 19.23 | 0.596622E+09 | 845.63 | 01-DEC-14:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.129753E+12 | 0.757789E+10 | ||||||||
Minimum of Months | 0.324473E+10 | 5515.54 | 21.88 | 14.74 | 0.559820E+09 | 845.62 | 21.90 | 16.66 | ||
Maximum of Months | 0.192006E+11 | 26076.85 | 42.50 | 28.92 | 0.692643E+09 | 845.76 | 42.50 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280121E+10 | 4332.76 | 24-JAN-11:00 | 24.00 | 17.69 | 0.401416E+09 | 544.96 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.344931E+10 | 11022.62 | 06-FEB-06:02 | 21.88 | 19.06 | 0.368185E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.571941E+10 | 17784.88 | 26-MAR-13:42 | 33.33 | 18.37 | 0.443109E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.793796E+10 | 20023.98 | 30-APR-11:32 | 36.00 | 21.14 | 0.395849E+09 | 545.01 | 25-APR-09:09 | 36.00 | 21.14 |
May | 0.123746E+11 | 20008.33 | 21-MAY-10:22 | 38.15 | 20.67 | 0.429504E+09 | 544.99 | 04-MAY-13:00 | 38.15 | 20.67 |
June | 0.131644E+11 | 21384.45 | 04-JUN-15:31 | 36.67 | 28.71 | 0.427971E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.142765E+11 | 20747.11 | 30-JUL-10:22 | 43.70 | 22.01 | 0.398464E+09 | 545.06 | 31-JUL-09:00 | 39.90 | 23.78 |
August | 0.152273E+11 | 20503.66 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446580E+09 | 545.23 | 30-AUG-09:50 | 39.75 | 24.22 |
September | 0.120268E+11 | 22094.73 | 04-SEP-10:11 | 38.00 | 23.07 | 0.396708E+09 | 544.96 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.949136E+10 | 20124.95 | 01-OCT-10:02 | 32.33 | 26.77 | 0.412378E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.614787E+10 | 19074.61 | 05-NOV-14:52 | 32.00 | 20.75 | 0.407251E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.338918E+10 | 9935.23 | 11-DEC-06:02 | 21.90 | 19.23 | 0.391450E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.106006E+12 | 0.491887E+10 | ||||||||
Minimum of Months | 0.280121E+10 | 4332.76 | 21.88 | 17.69 | 0.368185E+09 | 544.95 | 21.90 | 17.69 | ||
Maximum of Months | 0.152273E+11 | 22094.73 | 43.70 | 28.71 | 0.446580E+09 | 545.23 | 39.90 | 28.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.712808E+10 | 16290.50 | 29-JAN-15:43 | 25.83 | 19.95 | 0.626651E+09 | 845.66 | 24-JAN-10:00 | 25.83 | 19.95 |
February | 0.759771E+10 | 26793.04 | 05-FEB-12:23 | 31.05 | 19.28 | 0.571853E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.991621E+10 | 27500.11 | 26-MAR-13:42 | 33.33 | 18.37 | 0.687346E+09 | 845.88 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.106575E+11 | 26277.09 | 30-APR-11:32 | 36.00 | 21.14 | 0.613549E+09 | 845.73 | 28-APR-13:09 | 36.00 | 21.14 |
May | 0.150632E+11 | 26581.52 | 21-MAY-13:02 | 38.00 | 22.80 | 0.665980E+09 | 845.70 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.160402E+11 | 28140.96 | 04-JUN-15:31 | 36.67 | 28.71 | 0.663686E+09 | 845.66 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.181924E+11 | 27375.18 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617899E+09 | 845.71 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.204682E+11 | 27563.02 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692785E+09 | 846.12 | 17-AUG-13:50 | 42.33 | 26.20 |
September | 0.181841E+11 | 29996.81 | 03-SEP-14:51 | 38.00 | 27.45 | 0.615572E+09 | 845.98 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.169565E+11 | 28940.77 | 01-OCT-12:42 | 34.50 | 25.92 | 0.640313E+09 | 846.13 | 20-OCT-13:00 | 34.00 | 18.77 |
November | 0.132145E+11 | 29013.10 | 05-NOV-12:12 | 33.80 | 18.48 | 0.632900E+09 | 846.14 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.866007E+10 | 28109.43 | 03-DEC-13:22 | 28.40 | 19.50 | 0.611073E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.162079E+12 | 0.763961E+10 | ||||||||
Minimum of Months | 0.712808E+10 | 16290.50 | 25.83 | 18.37 | 0.571853E+09 | 845.66 | 23.00 | 16.45 | ||
Maximum of Months | 0.204682E+11 | 29996.81 | 42.50 | 28.71 | 0.692785E+09 | 846.14 | 42.50 | 28.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304036E+10 | 6774.04 | 29-JAN-15:43 | 25.83 | 19.95 | 0.396180E+09 | 544.96 | 17-JAN-14:20 | 25.83 | 19.95 |
February | 0.383493E+10 | 14367.57 | 05-FEB-17:03 | 31.00 | 18.53 | 0.366193E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.641875E+10 | 22677.91 | 26-MAR-16:21 | 31.50 | 18.68 | 0.443498E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.829373E+10 | 22837.95 | 23-APR-16:22 | 31.75 | 18.84 | 0.396093E+09 | 545.01 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.125003E+11 | 23612.87 | 21-MAY-16:22 | 37.25 | 23.23 | 0.429571E+09 | 544.99 | 04-MAY-13:00 | 37.25 | 23.23 |
June | 0.137177E+11 | 26022.69 | 04-JUN-16:11 | 36.67 | 28.92 | 0.428075E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.148999E+11 | 23932.42 | 30-JUL-15:02 | 40.45 | 27.73 | 0.398518E+09 | 545.00 | 03-JUL-09:09 | 40.45 | 27.73 |
August | 0.161305E+11 | 24657.74 | 06-AUG-15:41 | 40.25 | 25.55 | 0.446681E+09 | 544.94 | 04-AUG-13:20 | 40.25 | 25.55 |
September | 0.124657E+11 | 26129.09 | 03-SEP-14:51 | 38.00 | 27.45 | 0.396797E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.989167E+10 | 22903.32 | 01-OCT-17:22 | 33.50 | 27.13 | 0.412485E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.665048E+10 | 23444.39 | 05-NOV-15:32 | 31.60 | 21.44 | 0.407306E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.395196E+10 | 13036.87 | 11-DEC-06:02 | 21.90 | 19.23 | 0.390886E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.111796E+12 | 0.491228E+10 | ||||||||
Minimum of Months | 0.304036E+10 | 6774.04 | 21.90 | 18.53 | 0.366193E+09 | 544.94 | 23.00 | 17.31 | ||
Maximum of Months | 0.161305E+11 | 26129.09 | 40.45 | 28.92 | 0.446681E+09 | 545.01 | 40.45 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509613E+10 | 9559.20 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.637199E+10 | 12945.27 | 08-FEB-06:10 | 21.85 | 18.67 | 0.00 | 0.00 | 01-FEB-00:10 | 21.85 | 18.67 |
March | 0.984563E+10 | 12235.59 | 27-MAR-15:40 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.128158E+11 | 16093.70 | 29-APR-05:08 | 25.00 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 16.37 |
May | 0.196760E+11 | 22103.38 | 30-MAY-05:15 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.218666E+11 | 22149.84 | 12-JUN-05:15 | 29.13 | 24.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.13 | 24.04 |
July | 0.246037E+11 | 25983.13 | 24-JUL-05:20 | 32.67 | 27.85 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 27.85 |
August | 0.275721E+11 | 25957.48 | 07-AUG-05:30 | 32.45 | 23.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.45 | 23.07 |
September | 0.211700E+11 | 25296.76 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.189232E+11 | 22447.98 | 10-OCT-05:15 | 26.67 | 24.04 | 0.00 | 0.00 | 01-OCT-00:10 | 26.67 | 24.04 |
November | 0.124615E+11 | 16899.06 | 13-NOV-06:12 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.761125E+10 | 11032.03 | 12-DEC-06:15 | 23.07 | 17.90 | 0.00 | 0.00 | 01-DEC-00:10 | 23.07 | 17.90 |
Annual Sum or Average | 0.188014E+12 | 0.00 | ||||||||
Minimum of Months | 0.509613E+10 | 9559.20 | 20.07 | 16.37 | 0.00 | 0.00 | 20.07 | 16.37 | ||
Maximum of Months | 0.275721E+11 | 25983.13 | 35.00 | 27.85 | 0.00 | 0.00 | 35.00 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278431E+10 | 4600.47 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.369529E+10 | 6721.04 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.638477E+10 | 9711.20 | 27-MAR-16:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.848316E+10 | 10587.53 | 24-APR-05:02 | 21.83 | 13.96 | 0.00 | 0.00 | 01-APR-00:10 | 21.83 | 13.96 |
May | 0.136436E+11 | 12826.87 | 30-MAY-05:15 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.151759E+11 | 14188.10 | 05-JUN-05:02 | 29.00 | 23.92 | 0.00 | 0.00 | 01-JUN-00:10 | 29.00 | 23.92 |
July | 0.170402E+11 | 18669.40 | 17-JUL-05:13 | 31.00 | 26.67 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 26.67 |
August | 0.187140E+11 | 21865.28 | 07-AUG-05:12 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.143801E+11 | 20151.11 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.119185E+11 | 13314.14 | 02-OCT-05:02 | 26.83 | 24.79 | 0.00 | 0.00 | 01-OCT-00:10 | 26.83 | 24.79 |
November | 0.811627E+10 | 11539.23 | 13-NOV-06:12 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.423463E+10 | 7416.70 | 11-DEC-06:15 | 21.80 | 19.16 | 0.00 | 0.00 | 01-DEC-00:10 | 21.80 | 19.16 |
Annual Sum or Average | 0.124571E+12 | 0.00 | ||||||||
Minimum of Months | 0.278431E+10 | 4600.47 | 20.07 | 13.96 | 0.00 | 0.00 | 20.07 | 13.96 | ||
Maximum of Months | 0.187140E+11 | 21865.28 | 35.00 | 26.67 | 0.00 | 0.00 | 35.00 | 26.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320867E+10 | 8622.95 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.478979E+10 | 13653.26 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.866186E+10 | 19270.58 | 27-MAR-14:30 | 35.00 | 19.13 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 19.13 |
April | 0.123333E+11 | 21263.42 | 28-APR-12:50 | 37.58 | 22.61 | 0.00 | 0.00 | 01-APR-00:10 | 37.58 | 22.61 |
May | 0.207403E+11 | 24155.19 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.232570E+11 | 24854.43 | 09-JUN-14:40 | 41.67 | 25.61 | 0.00 | 0.00 | 01-JUN-00:10 | 41.67 | 25.61 |
July | 0.264201E+11 | 27116.43 | 21-JUL-12:50 | 42.92 | 26.64 | 0.00 | 0.00 | 01-JUL-00:10 | 42.92 | 26.64 |
August | 0.282823E+11 | 27393.08 | 16-AUG-13:50 | 44.03 | 25.58 | 0.00 | 0.00 | 01-AUG-00:10 | 44.03 | 25.58 |
September | 0.208919E+11 | 28843.24 | 04-SEP-15:31 | 40.80 | 24.09 | 0.00 | 0.00 | 01-SEP-00:10 | 40.80 | 24.09 |
October | 0.157678E+11 | 19735.03 | 05-OCT-14:40 | 36.00 | 22.65 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 22.65 |
November | 0.955336E+10 | 15853.01 | 01-NOV-14:20 | 32.67 | 26.20 | 0.00 | 0.00 | 01-NOV-00:10 | 32.67 | 26.20 |
December | 0.456455E+10 | 10963.71 | 04-DEC-14:05 | 27.00 | 21.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 21.00 |
Annual Sum or Average | 0.178471E+12 | 0.00 | ||||||||
Minimum of Months | 0.320867E+10 | 8622.95 | 27.00 | 16.66 | 0.00 | 0.00 | 27.00 | 16.66 | ||
Maximum of Months | 0.282823E+11 | 28843.24 | 44.03 | 26.64 | 0.00 | 0.00 | 44.03 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430315E+10 | 1900.49 | 29-JAN-17:40 | 24.33 | 19.64 | 95238476.19 | 126.85 | 17-JAN-14:00 | 24.33 | 19.64 |
February | 0.861566E+10 | 3840.62 | 05-FEB-17:20 | 31.00 | 18.60 | 86409279.14 | 126.85 | 07-FEB-10:09 | 26.33 | 20.66 |
March | 0.146780E+11 | 7210.83 | 31-MAR-23:50 | 22.37 | 20.31 | 0.103244E+09 | 126.85 | 30-MAR-09:09 | 22.37 | 20.31 |
April | 0.192296E+11 | 7876.55 | 30-APR-21:03 | 27.82 | 23.12 | 92135057.92 | 140.28 | 26-APR-13:09 | 27.82 | 23.12 |
May | 0.507050E+10 | 3725.62 | 31-MAY-24:00 | 32.70 | 23.39 | 99239833.24 | 126.86 | 17-MAY-13:09 | 32.70 | 23.39 |
June | 0.986696E+10 | 5579.59 | 30-JUN-23:57 | 31.70 | 26.86 | 98977765.51 | 126.88 | 23-JUN-09:09 | 31.70 | 26.86 |
July | 0.154732E+11 | 7384.53 | 31-JUL-23:57 | 33.30 | 28.31 | 91889976.29 | 126.84 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.196844E+11 | 7750.45 | 15-AUG-04:03 | 29.75 | 23.27 | 0.114490E+09 | 153.23 | 10-AUG-13:00 | 29.75 | 23.27 |
September | 0.503456E+10 | 3718.38 | 30-SEP-24:00 | 29.00 | 26.44 | 91607165.81 | 126.85 | 21-SEP-13:09 | 29.00 | 26.44 |
October | 0.101474E+11 | 5472.93 | 31-OCT-24:00 | 27.40 | 21.22 | 95250610.16 | 126.87 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.144073E+11 | 6085.16 | 12-NOV-16:53 | 29.00 | 17.88 | 94310970.61 | 126.85 | 01-NOV-09:09 | 29.00 | 17.88 |
December | 0.196515E+11 | 7707.11 | 25-DEC-16:55 | 24.00 | 19.34 | 91884026.84 | 126.83 | 15-DEC-10:09 | 24.00 | 19.34 |
Annual Sum or Average | 0.146162E+12 | 0.115468E+10 | ||||||||
Minimum of Months | 0.430315E+10 | 1900.49 | 22.37 | 17.88 | 86409279.14 | 126.83 | 22.37 | 17.88 | ||
Maximum of Months | 0.196844E+11 | 7876.55 | 33.30 | 28.31 | 0.114490E+09 | 153.23 | 33.30 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346489E+10 | 1711.27 | 31-JAN-17:00 | 23.00 | 17.31 | 95234439.48 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.778617E+10 | 3580.86 | 07-FEB-17:00 | 28.00 | 21.23 | 86408481.64 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.137920E+11 | 6936.37 | 31-MAR-23:55 | 22.30 | 20.22 | 0.103244E+09 | 126.85 | 02-MAR-14:00 | 22.30 | 20.22 |
April | 0.182203E+11 | 7374.70 | 23-APR-17:44 | 30.17 | 19.07 | 92048641.74 | 139.48 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.449089E+10 | 3473.06 | 31-MAY-24:00 | 32.70 | 23.39 | 99237647.82 | 126.85 | 11-MAY-13:00 | 32.70 | 23.39 |
June | 0.908032E+10 | 5219.72 | 30-JUN-23:57 | 31.70 | 26.86 | 98979116.68 | 126.87 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.143086E+11 | 6984.85 | 31-JUL-24:00 | 33.30 | 28.31 | 91892433.68 | 126.85 | 18-JUL-09:09 | 33.30 | 28.31 |
August | 0.185913E+11 | 7233.62 | 14-AUG-02:23 | 31.00 | 24.74 | 0.113422E+09 | 151.42 | 10-AUG-13:00 | 31.00 | 24.74 |
September | 0.437716E+10 | 3412.59 | 30-SEP-23:33 | 29.00 | 26.39 | 91606059.42 | 126.85 | 05-SEP-13:50 | 29.00 | 26.39 |
October | 0.929286E+10 | 5229.59 | 31-OCT-24:00 | 27.40 | 21.22 | 95250739.16 | 126.87 | 06-OCT-09:09 | 27.40 | 21.22 |
November | 0.135099E+11 | 5535.70 | 05-NOV-16:54 | 31.00 | 21.45 | 94311454.41 | 126.85 | 01-NOV-09:09 | 31.00 | 21.45 |
December | 0.183856E+11 | 7202.50 | 04-DEC-17:00 | 26.00 | 20.50 | 91884228.95 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.135300E+12 | 0.115352E+10 | ||||||||
Minimum of Months | 0.346489E+10 | 1711.27 | 22.30 | 17.31 | 86408481.64 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.185913E+11 | 7374.70 | 33.30 | 28.31 | 0.113422E+09 | 151.42 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300826E+10 | 1738.81 | 31-JAN-17:00 | 23.00 | 17.31 | 95233964.71 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.754106E+10 | 3651.47 | 05-FEB-17:20 | 31.00 | 18.60 | 86408654.42 | 126.85 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.136752E+11 | 6883.11 | 31-MAR-23:55 | 22.30 | 20.22 | 0.103244E+09 | 126.85 | 02-MAR-14:00 | 22.30 | 20.22 |
April | 0.182428E+11 | 7602.22 | 23-APR-17:22 | 30.50 | 19.17 | 92044246.75 | 140.00 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.462609E+10 | 3529.94 | 31-MAY-24:00 | 32.70 | 23.39 | 99238390.35 | 126.85 | 11-MAY-13:09 | 32.70 | 23.39 |
June | 0.922276E+10 | 5241.69 | 30-JUN-23:57 | 31.70 | 26.86 | 98979113.05 | 126.87 | 08-JUN-13:09 | 31.70 | 26.86 |
July | 0.145270E+11 | 7046.11 | 31-JUL-24:00 | 33.30 | 28.31 | 91892081.04 | 126.85 | 18-JUL-09:09 | 33.30 | 28.31 |
August | 0.187669E+11 | 7345.04 | 14-AUG-03:02 | 31.00 | 24.41 | 0.113475E+09 | 152.86 | 10-AUG-13:00 | 31.00 | 24.41 |
September | 0.450859E+10 | 3452.66 | 30-SEP-24:00 | 29.00 | 26.44 | 91606541.04 | 126.85 | 25-SEP-13:09 | 29.00 | 26.44 |
October | 0.935151E+10 | 5225.16 | 31-OCT-24:00 | 27.40 | 21.22 | 95251007.86 | 126.87 | 17-OCT-13:09 | 27.40 | 21.22 |
November | 0.134368E+11 | 5687.56 | 05-NOV-17:05 | 30.83 | 21.62 | 94311681.90 | 126.85 | 01-NOV-09:09 | 30.83 | 21.62 |
December | 0.180975E+11 | 7225.04 | 06-DEC-17:00 | 26.00 | 20.50 | 91884534.13 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.135004E+12 | 0.115357E+10 | ||||||||
Minimum of Months | 0.300826E+10 | 1738.81 | 22.30 | 17.31 | 86408654.42 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.187669E+11 | 7602.22 | 33.30 | 28.31 | 0.113475E+09 | 152.86 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243411E+12 | 93812.30 | 30-JAN-17:00 | 22.00 | 19.30 | 0.206204E+10 | 2747.82 | 19-JAN-10:09 | 22.00 | 19.30 |
February | 0.440177E+12 | 185391.78 | 07-FEB-17:00 | 28.00 | 21.23 | 0.187074E+10 | 2747.69 | 13-FEB-10:09 | 19.50 | 13.91 |
March | 0.732269E+12 | 359488.49 | 31-MAR-23:55 | 22.30 | 20.22 | 0.223516E+10 | 2746.77 | 16-MAR-09:09 | 22.30 | 20.22 |
April | 0.945678E+12 | 370645.98 | 28-APR-13:05 | 36.42 | 23.03 | 0.198523E+10 | 2922.13 | 28-APR-12:20 | 36.42 | 23.03 |
May | 0.246280E+12 | 178052.86 | 31-MAY-23:53 | 32.70 | 23.39 | 0.214870E+10 | 2747.15 | 30-MAY-09:09 | 32.70 | 23.39 |
June | 0.475921E+12 | 269784.87 | 30-JUN-23:53 | 31.70 | 26.86 | 0.214278E+10 | 2746.99 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.739286E+12 | 362610.24 | 31-JUL-23:57 | 33.30 | 28.31 | 0.198934E+10 | 2746.26 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.986147E+12 | 374754.19 | 10-AUG-21:01 | 34.93 | 27.53 | 0.229024E+10 | 3179.44 | 16-AUG-13:09 | 44.17 | 25.68 |
September | 0.243203E+12 | 179127.70 | 30-SEP-24:00 | 29.00 | 26.44 | 0.198367E+10 | 2747.20 | 15-SEP-09:09 | 29.00 | 26.44 |
October | 0.495833E+12 | 270669.21 | 31-OCT-24:00 | 27.40 | 21.22 | 0.206206E+10 | 2746.86 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.714659E+12 | 278977.75 | 03-NOV-16:00 | 30.20 | 23.81 | 0.204165E+10 | 2746.05 | 01-NOV-09:09 | 30.20 | 23.81 |
December | 0.981091E+12 | 369967.47 | 12-DEC-17:00 | 23.80 | 16.27 | 0.198929E+10 | 2747.66 | 18-DEC-10:09 | 20.42 | 13.70 |
Annual Sum or Average | 0.724396E+13 | 0.248009E+11 | ||||||||
Minimum of Months | 0.243203E+12 | 93812.30 | 22.00 | 16.27 | 0.187074E+10 | 2746.05 | 19.50 | 13.70 | ||
Maximum of Months | 0.986147E+12 | 374754.19 | 36.42 | 28.31 | 0.229024E+10 | 3179.44 | 44.17 | 28.31 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 94376.14 | 157.29 | 10-FEB-05:10 | 19.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 94376.14 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 94376.14 | 157.29 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63534.20 | 317.67 | 02-JAN-06:07 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 63534.20 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 63534.20 | 317.67 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15711.59 | 78.56 | 02-JAN-06:07 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 15711.59 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 15711.59 | 78.56 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81600846.21 | 8461.17 | 17-JAN-05:12 | 16.67 |
February | 87324502.50 | 9344.94 | 10-FEB-05:12 | 19.93 |
March | 87248070.40 | 10431.03 | 06-MAR-05:12 | 16.67 |
April | 58212421.88 | 6853.50 | 02-APR-14:02 | 33.83 |
May | 30097666.78 | 4327.72 | 07-MAY-14:32 | 37.00 |
June | 24176214.15 | 3913.52 | 25-JUN-10:22 | 35.15 |
July | 33032338.45 | 4447.80 | 30-JUL-10:22 | 43.70 |
August | 32759181.03 | 4080.02 | 05-AUG-17:42 | 40.17 |
September | 25134537.51 | 4344.11 | 24-SEP-11:02 | 35.00 |
October | 48536602.15 | 4687.03 | 29-OCT-11:42 | 34.42 |
November | 92430166.78 | 9905.35 | 30-NOV-05:11 | 19.67 |
December | 0.142665E+09 | 11511.09 | 28-DEC-05:11 | 15.00 |
Annual Sum or Average | 0.743217E+09 | |||
Minimum of Months | 24176214.15 | 3913.52 | 15.00 | |
Maximum of Months | 0.142665E+09 | 11511.09 | 43.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48041990.41 | 6643.68 | 02-JAN-05:11 | 13.67 |
February | 39829503.20 | 7090.04 | 21-FEB-05:11 | 14.67 |
March | 32488416.87 | 6991.37 | 02-MAR-04:02 | 29.10 |
April | 34796638.73 | 6793.59 | 02-APR-14:31 | 33.33 |
May | 33410394.02 | 6210.80 | 07-MAY-14:21 | 37.00 |
June | 26991400.04 | 5467.73 | 04-JUN-14:41 | 36.33 |
July | 40536476.87 | 5953.51 | 30-JUL-11:02 | 44.67 |
August | 26829519.10 | 5191.46 | 13-AUG-14:22 | 40.00 |
September | 31429284.89 | 6149.94 | 17-SEP-14:01 | 36.00 |
October | 41311731.72 | 6248.80 | 29-OCT-13:41 | 34.18 |
November | 38449576.52 | 5127.90 | 05-NOV-14:42 | 32.17 |
December | 42079365.07 | 5642.38 | 18-DEC-06:02 | 13.17 |
Annual Sum or Average | 0.436194E+09 | |||
Minimum of Months | 26829519.10 | 5127.90 | 13.17 | |
Maximum of Months | 48041990.41 | 7090.04 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632600E+09 | 14068.98 | 13-JAN-06:02 | 13.93 |
February | 0.362631E+09 | 15521.39 | 21-FEB-06:03 | 13.95 |
March | 0.217600E+09 | 13402.38 | 08-MAR-06:03 | 14.07 |
April | 62601774.90 | 11695.80 | 05-APR-05:02 | 17.00 |
May | 10415363.33 | 8363.47 | 02-MAY-04:12 | 22.87 |
June | 1651876.96 | 3153.46 | 08-JUN-03:02 | 26.02 |
July | 158644.10 | 933.22 | 30-JUL-08:22 | 36.90 |
August | 17189.19 | 143.24 | 27-AUG-08:22 | 33.50 |
September | 3633916.51 | 3704.10 | 30-SEP-03:02 | 26.62 |
October | 20043586.84 | 10300.00 | 30-OCT-04:12 | 22.40 |
November | 67540121.73 | 11697.34 | 22-NOV-06:03 | 16.98 |
December | 0.364406E+09 | 13063.86 | 29-DEC-06:03 | 15.87 |
Annual Sum or Average | 0.174330E+10 | |||
Minimum of Months | 17189.19 | 143.24 | 13.93 | |
Maximum of Months | 0.632600E+09 | 15521.39 | 36.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.933590E+09 | 1238.63 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.819018E+09 | 1276.00 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.950450E+09 | 1494.55 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.827557E+09 | 1229.48 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.869102E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.856744E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.814146E+09 | 923.62 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.912899E+09 | 870.17 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.833294E+09 | 892.88 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.888312E+09 | 1102.95 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.911821E+09 | 1387.48 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.915503E+09 | 1425.05 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105324E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.814146E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.950450E+09 | 1494.55 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.594899E+09 | 839.76 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.525423E+09 | 841.46 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.610093E+09 | 949.09 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.533221E+09 | 719.94 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.563352E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555924E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.526790E+09 | 573.74 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.589462E+09 | 509.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.536606E+09 | 509.78 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.568312E+09 | 552.37 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.585418E+09 | 919.61 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.583138E+09 | 930.96 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.677264E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.525423E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.610093E+09 | 949.09 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.904139E+09 | 1093.21 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.804415E+09 | 1207.59 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.944747E+09 | 1491.19 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.829231E+09 | 1238.10 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.877305E+09 | 844.67 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.865491E+09 | 860.31 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.820966E+09 | 1086.98 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916749E+09 | 864.26 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.832132E+09 | 888.58 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.878157E+09 | 882.27 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.886496E+09 | 1203.88 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.880983E+09 | 1333.08 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104408E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.804415E+09 | 844.67 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.944747E+09 | 1491.19 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.590340E+09 | 794.30 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521946E+09 | 753.00 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.613543E+09 | 969.29 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.535867E+09 | 831.29 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564862E+09 | 575.15 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.556075E+09 | 577.69 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.529213E+09 | 749.03 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.591615E+09 | 595.30 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.537857E+09 | 704.14 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.571952E+09 | 770.56 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.575642E+09 | 772.88 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.574792E+09 | 887.77 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.676370E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521946E+09 | 575.15 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.613543E+09 | 969.29 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.931091E+09 | 1231.93 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.817108E+09 | 1271.19 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.949108E+09 | 1492.64 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.826780E+09 | 1224.14 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868687E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.855728E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.813663E+09 | 918.07 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.912338E+09 | 861.58 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.832388E+09 | 885.59 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.886960E+09 | 1093.74 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.909834E+09 | 1383.60 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.912899E+09 | 1422.04 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105166E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.813663E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.949108E+09 | 1492.64 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593631E+09 | 833.97 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.524591E+09 | 835.41 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.609263E+09 | 946.31 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.532801E+09 | 713.38 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562980E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555529E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.526451E+09 | 569.85 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.589039E+09 | 509.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.536222E+09 | 509.78 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.567834E+09 | 546.66 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.584583E+09 | 915.69 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.582008E+09 | 927.32 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.676493E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.524591E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.609263E+09 | 946.31 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903638E+09 | 1087.04 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803834E+09 | 1202.43 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.943834E+09 | 1489.26 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.828484E+09 | 1232.82 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.876667E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864762E+09 | 850.96 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.820152E+09 | 1079.08 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916051E+09 | 855.38 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.831355E+09 | 881.07 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.876997E+09 | 873.60 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.886065E+09 | 1198.15 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.880438E+09 | 1329.14 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104323E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803834E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.943834E+09 | 1489.26 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.589394E+09 | 787.08 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521089E+09 | 744.57 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612518E+09 | 966.61 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.534907E+09 | 824.93 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564164E+09 | 570.42 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.555398E+09 | 573.12 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.528430E+09 | 740.45 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.590966E+09 | 591.77 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.537314E+09 | 693.86 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.571284E+09 | 763.66 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.574982E+09 | 766.20 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.573641E+09 | 882.98 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.675409E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521089E+09 | 570.42 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.612518E+09 | 966.61 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.930973E+09 | 1231.27 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.817006E+09 | 1270.41 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.949033E+09 | 1492.29 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.826756E+09 | 1223.27 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868674E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.855711E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.813639E+09 | 917.85 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.912305E+09 | 861.26 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.832363E+09 | 885.31 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.886900E+09 | 1092.97 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.909784E+09 | 1383.13 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.912827E+09 | 1421.59 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105160E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.813639E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.949033E+09 | 1492.29 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593603E+09 | 833.61 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.524567E+09 | 834.95 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.609241E+09 | 946.07 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.532787E+09 | 712.74 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562953E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555516E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.526434E+09 | 569.66 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.589005E+09 | 509.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.536209E+09 | 509.78 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.567795E+09 | 546.49 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.584560E+09 | 915.42 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.581927E+09 | 927.04 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.676460E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.524567E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.609241E+09 | 946.07 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903623E+09 | 1086.03 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803808E+09 | 1201.56 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.943796E+09 | 1488.90 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.828458E+09 | 1231.97 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.876625E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864724E+09 | 850.61 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.820122E+09 | 1077.95 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916015E+09 | 855.03 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.831324E+09 | 880.78 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.876982E+09 | 873.32 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.886055E+09 | 1197.50 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.880419E+09 | 1328.60 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104319E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803808E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.943796E+09 | 1488.90 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.589349E+09 | 786.53 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521068E+09 | 743.95 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612583E+09 | 966.40 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.534888E+09 | 824.44 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564149E+09 | 570.26 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.555362E+09 | 572.96 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.528402E+09 | 739.80 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.590930E+09 | 591.64 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.537268E+09 | 693.20 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.571264E+09 | 763.26 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.574970E+09 | 765.83 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.573570E+09 | 882.60 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.675380E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521068E+09 | 570.26 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.612583E+09 | 966.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.933590E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 588305.80 | 67584432.15 |
February | 0.136985E+10 | 0.819018E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5895503.62 | 68044020.83 |
March | 0.163685E+10 | 0.950450E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15274099.85 | 35738074.74 |
April | 0.145243E+10 | 0.827557E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35867022.18 | 14533921.33 |
May | 0.157338E+10 | 0.869102E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89134629.84 | 1485493.17 |
June | 0.156900E+10 | 0.856744E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111920E+09 | 113677.28 |
July | 0.145680E+10 | 0.814146E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157904E+09 | 0.00 |
August | 0.163685E+10 | 0.912899E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150955E+09 | 0.00 |
September | 0.145243E+10 | 0.833294E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106694E+09 | 222946.70 |
October | 0.150991E+10 | 0.888312E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59924613.23 | 2468621.57 |
November | 0.149516E+10 | 0.911821E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24501184.46 | 16841888.89 |
December | 0.145680E+10 | 0.915503E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3745942.47 | 49028557.54 |
Annual Sum or Average | 0.181194E+11 | 0.105324E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762405E+09 | 0.256062E+09 |
Minimum of Months | 0.136985E+10 | 0.814146E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 588305.80 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.950450E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157904E+09 | 68044020.83 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.594899E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258592.90 | 46369743.72 |
February | 0.882782E+09 | 0.525423E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3628865.21 | 45603780.76 |
March | 0.105485E+10 | 0.610093E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10103458.97 | 23455131.90 |
April | 0.936002E+09 | 0.533221E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23538728.40 | 9416145.56 |
May | 0.101394E+10 | 0.563352E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58864188.02 | 1063431.37 |
June | 0.101113E+10 | 0.555924E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74364145.20 | 83531.95 |
July | 0.938820E+09 | 0.526790E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105019E+09 | 0.00 |
August | 0.105485E+10 | 0.589462E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100473E+09 | 0.00 |
September | 0.936002E+09 | 0.536606E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70470823.95 | 163494.94 |
October | 0.973041E+09 | 0.568312E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39425504.51 | 1794069.53 |
November | 0.963541E+09 | 0.585418E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15910644.00 | 11284499.77 |
December | 0.938820E+09 | 0.583138E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2460616.27 | 31306439.05 |
Annual Sum or Average | 0.116768E+11 | 0.677264E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504517E+09 | 0.170540E+09 |
Minimum of Months | 0.882782E+09 | 0.525423E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258592.90 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.610093E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105019E+09 | 46369743.72 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.904139E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 332783.31 | 75171543.19 |
February | 0.136988E+10 | 0.804415E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5148358.82 | 73459851.67 |
March | 0.163688E+10 | 0.944747E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14669498.58 | 38550558.24 |
April | 0.145246E+10 | 0.829231E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35077927.32 | 15105275.61 |
May | 0.157341E+10 | 0.877305E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89476324.61 | 1408504.25 |
June | 0.156904E+10 | 0.865491E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112708E+09 | 85360.73 |
July | 0.145684E+10 | 0.820966E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158395E+09 | 0.00 |
August | 0.163688E+10 | 0.916749E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151034E+09 | 0.00 |
September | 0.145246E+10 | 0.832132E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105925E+09 | 229672.73 |
October | 0.150994E+10 | 0.878157E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58234784.09 | 2973804.02 |
November | 0.149520E+10 | 0.886496E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22190822.07 | 19540334.58 |
December | 0.145684E+10 | 0.880983E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3021306.55 | 54376205.98 |
Annual Sum or Average | 0.181198E+11 | 0.104408E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756214E+09 | 0.280901E+09 |
Minimum of Months | 0.136988E+10 | 0.804415E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 332783.31 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.944747E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158395E+09 | 75171543.19 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.590340E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 237704.84 | 52558571.28 |
February | 0.882782E+09 | 0.521946E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3461466.81 | 54950122.33 |
March | 0.105485E+10 | 0.613543E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9481603.18 | 32169046.95 |
April | 0.936002E+09 | 0.535867E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22364054.85 | 14465942.44 |
May | 0.101394E+10 | 0.564862E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58559156.90 | 1255796.94 |
June | 0.101113E+10 | 0.556075E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73569556.15 | 112999.33 |
July | 0.938820E+09 | 0.529213E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104041E+09 | 0.00 |
August | 0.105485E+10 | 0.591615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99285597.89 | 0.00 |
September | 0.936002E+09 | 0.537857E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70321109.78 | 165376.43 |
October | 0.973041E+09 | 0.571952E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38632279.61 | 2276733.08 |
November | 0.963541E+09 | 0.575642E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14592722.25 | 15865995.96 |
December | 0.938820E+09 | 0.574792E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1973539.33 | 43704354.70 |
Annual Sum or Average | 0.116768E+11 | 0.676370E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496520E+09 | 0.217525E+09 |
Minimum of Months | 0.882782E+09 | 0.521946E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 237704.84 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.613543E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104041E+09 | 54950122.33 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.931091E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2510872.62 | 0.134265E+09 |
February | 0.136985E+10 | 0.817108E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14906333.64 | 0.138238E+09 |
March | 0.163685E+10 | 0.949108E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35030413.95 | 79215060.31 |
April | 0.145243E+10 | 0.826780E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84967428.64 | 37588547.12 |
May | 0.157338E+10 | 0.868687E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210591E+09 | 3438332.73 |
June | 0.156900E+10 | 0.855728E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265527E+09 | 169479.36 |
July | 0.145680E+10 | 0.813663E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373412E+09 | 0.00 |
August | 0.163685E+10 | 0.912338E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357429E+09 | 0.00 |
September | 0.145243E+10 | 0.832388E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254718E+09 | 432286.81 |
October | 0.150991E+10 | 0.886960E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144760E+09 | 5620668.60 |
November | 0.149516E+10 | 0.909834E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61132198.03 | 38505595.74 |
December | 0.145680E+10 | 0.912899E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10054525.16 | 0.100664E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105166E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181504E+10 | 0.538137E+09 |
Minimum of Months | 0.136985E+10 | 0.813663E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2510872.62 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.949108E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373412E+09 | 0.138238E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.593631E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 602578.39 | 99459353.13 |
February | 0.649041E+09 | 0.524591E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7906825.59 | 0.100618E+09 |
March | 0.773965E+09 | 0.609263E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21674083.80 | 58043257.82 |
April | 0.688021E+09 | 0.532801E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52740726.22 | 27751308.12 |
May | 0.744847E+09 | 0.562980E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136977E+09 | 2706048.98 |
June | 0.742030E+09 | 0.555529E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174011E+09 | 156104.02 |
July | 0.690839E+09 | 0.526451E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245809E+09 | 0.00 |
August | 0.773965E+09 | 0.589039E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235134E+09 | 0.00 |
September | 0.688021E+09 | 0.536222E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165591E+09 | 351960.33 |
October | 0.715730E+09 | 0.567834E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91813099.40 | 4714479.25 |
November | 0.708685E+09 | 0.584583E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35553415.74 | 29031643.26 |
December | 0.690839E+09 | 0.582008E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5119676.87 | 72964200.90 |
Annual Sum or Average | 0.858171E+10 | 0.676493E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117293E+10 | 0.395796E+09 |
Minimum of Months | 0.649041E+09 | 0.524591E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 602578.39 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.609263E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245809E+09 | 0.100618E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.903638E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 700473.41 | 0.170295E+09 |
February | 0.136988E+10 | 0.803834E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11615004.27 | 0.165010E+09 |
March | 0.163688E+10 | 0.943834E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32821553.27 | 92649174.95 |
April | 0.145246E+10 | 0.828484E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81463953.79 | 40761019.72 |
May | 0.157341E+10 | 0.876667E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210727E+09 | 3531860.64 |
June | 0.156904E+10 | 0.864762E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267494E+09 | 141006.89 |
July | 0.145684E+10 | 0.820152E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374278E+09 | 0.00 |
August | 0.163688E+10 | 0.916051E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356063E+09 | 0.00 |
September | 0.145246E+10 | 0.831355E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249026E+09 | 553214.48 |
October | 0.150994E+10 | 0.876997E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134891E+09 | 8695100.78 |
November | 0.149520E+10 | 0.886065E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50002409.85 | 50711038.13 |
December | 0.145684E+10 | 0.880438E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6613758.05 | 0.127336E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104323E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177570E+10 | 0.659683E+09 |
Minimum of Months | 0.136988E+10 | 0.803834E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 700473.41 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.943834E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374278E+09 | 0.170295E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.589394E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 904524.72 | 0.103349E+09 |
February | 0.882782E+09 | 0.521089E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8578740.17 | 0.106045E+09 |
March | 0.105485E+10 | 0.612518E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21881741.55 | 64145549.65 |
April | 0.936002E+09 | 0.534907E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52562492.64 | 31504785.57 |
May | 0.101394E+10 | 0.564164E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136246E+09 | 3215997.11 |
June | 0.101113E+10 | 0.555398E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172284E+09 | 204805.09 |
July | 0.938820E+09 | 0.528430E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244603E+09 | 0.00 |
August | 0.105485E+10 | 0.590966E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234112E+09 | 0.00 |
September | 0.936002E+09 | 0.537314E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164005E+09 | 435866.36 |
October | 0.973041E+09 | 0.571284E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90291716.45 | 5777023.75 |
November | 0.963541E+09 | 0.574982E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35059045.49 | 32002061.70 |
December | 0.938820E+09 | 0.573641E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5069686.22 | 79655306.26 |
Annual Sum or Average | 0.116768E+11 | 0.675409E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116560E+10 | 0.426335E+09 |
Minimum of Months | 0.882782E+09 | 0.521089E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 904524.72 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.612518E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244603E+09 | 0.106045E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.930973E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3181114.85 | 0.154212E+09 |
February | 0.136985E+10 | 0.817006E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17649374.60 | 0.164648E+09 |
March | 0.163685E+10 | 0.949033E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41817328.82 | 96550852.91 |
April | 0.145243E+10 | 0.826756E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101380E+09 | 47099562.63 |
May | 0.157338E+10 | 0.868674E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255332E+09 | 4746418.56 |
June | 0.156900E+10 | 0.855711E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322382E+09 | 263923.04 |
July | 0.145680E+10 | 0.813639E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455385E+09 | 0.00 |
August | 0.163685E+10 | 0.912305E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436317E+09 | 0.00 |
September | 0.145243E+10 | 0.832363E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309146E+09 | 611316.08 |
October | 0.150991E+10 | 0.886900E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174397E+09 | 7410914.45 |
November | 0.149516E+10 | 0.909784E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72140471.78 | 46799241.64 |
December | 0.145680E+10 | 0.912827E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11918909.10 | 0.117835E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105160E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220105E+10 | 0.640178E+09 |
Minimum of Months | 0.136985E+10 | 0.813639E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3181114.85 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.949033E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455385E+09 | 0.164648E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.593603E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863415.31 | 0.114992E+09 |
February | 0.882782E+09 | 0.524567E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9796997.15 | 0.119840E+09 |
March | 0.105485E+10 | 0.609241E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26800852.86 | 70517857.96 |
April | 0.936002E+09 | 0.532787E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64531763.36 | 34611115.49 |
May | 0.101394E+10 | 0.562953E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167535E+09 | 3670210.18 |
June | 0.101113E+10 | 0.555516E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212887E+09 | 231267.31 |
July | 0.938820E+09 | 0.526434E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301232E+09 | 0.00 |
August | 0.105485E+10 | 0.589005E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288655E+09 | 0.00 |
September | 0.936002E+09 | 0.536209E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202389E+09 | 488793.40 |
October | 0.973041E+09 | 0.567795E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112067E+09 | 6120418.79 |
November | 0.963541E+09 | 0.584560E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43131381.68 | 35262278.87 |
December | 0.938820E+09 | 0.581927E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6258175.73 | 85494320.73 |
Annual Sum or Average | 0.116768E+11 | 0.676460E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143615E+10 | 0.471228E+09 |
Minimum of Months | 0.882782E+09 | 0.524567E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863415.31 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.609241E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301232E+09 | 0.119840E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.903623E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809713.24 | 0.201159E+09 |
February | 0.136988E+10 | 0.803808E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13944910.41 | 0.198840E+09 |
March | 0.163688E+10 | 0.943796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39466940.29 | 0.113331E+09 |
April | 0.145246E+10 | 0.828458E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98001791.92 | 51024248.68 |
May | 0.157341E+10 | 0.876625E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255374E+09 | 4862482.19 |
June | 0.156904E+10 | 0.864724E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324242E+09 | 222979.37 |
July | 0.145684E+10 | 0.820122E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456214E+09 | 0.00 |
August | 0.163688E+10 | 0.916015E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434885E+09 | 0.00 |
September | 0.145246E+10 | 0.831324E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302928E+09 | 773726.23 |
October | 0.150994E+10 | 0.876982E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163568E+09 | 11330936.79 |
November | 0.149520E+10 | 0.886055E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59959862.19 | 61932787.60 |
December | 0.145684E+10 | 0.880419E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7615416.13 | 0.152352E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104319E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215701E+10 | 0.795830E+09 |
Minimum of Months | 0.136988E+10 | 0.803808E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809713.24 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.943796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456214E+09 | 0.201159E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.589349E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1085740.77 | 0.122231E+09 |
February | 0.882782E+09 | 0.521068E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10262906.90 | 0.128184E+09 |
March | 0.105485E+10 | 0.612583E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26366677.73 | 78791211.37 |
April | 0.936002E+09 | 0.534888E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63563047.43 | 39293696.59 |
May | 0.101394E+10 | 0.564149E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165846E+09 | 4275273.45 |
June | 0.101113E+10 | 0.555362E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209969E+09 | 314382.17 |
July | 0.938820E+09 | 0.528402E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299161E+09 | 0.00 |
August | 0.105485E+10 | 0.590930E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286589E+09 | 0.00 |
September | 0.936002E+09 | 0.537268E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199776E+09 | 602811.45 |
October | 0.973041E+09 | 0.571264E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109581E+09 | 7518215.68 |
November | 0.963541E+09 | 0.574970E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42067644.17 | 39168512.95 |
December | 0.938820E+09 | 0.573570E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5856064.01 | 95241408.93 |
Annual Sum or Average | 0.116768E+11 | 0.675380E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142012E+10 | 0.515621E+09 |
Minimum of Months | 0.882782E+09 | 0.521068E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1085740.77 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.612583E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299161E+09 | 0.128184E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771333.62 | 0.150761E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10243441.19 | 0.149829E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25349825.86 | 82636614.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63784942.41 | 36375996.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161397E+09 | 4643321.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201003E+09 | 586953.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288094E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273538E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190045E+09 | 752276.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103222E+09 | 8326762.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40111679.58 | 42029289.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5526880.82 | 0.112638E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136309E+10 | 0.588579E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771333.62 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288094E+09 | 0.150761E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2220809.87 | 0.250252E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19872558.68 | 0.250736E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46523272.74 | 0.141005E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120304E+09 | 63699602.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310823E+09 | 6129651.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388026E+09 | 503811.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555702E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524166E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369641E+09 | 816778.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204855E+09 | 11283352.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78194053.01 | 70051964.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11235200.77 | 0.187805E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263156E+10 | 0.982283E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2220809.87 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555702E+09 | 0.250736E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256393.54 | 0.262531E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18496653.69 | 0.271849E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45937491.99 | 0.157932E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113286E+09 | 68719910.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327616E+09 | 6686827.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424606E+09 | 551744.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606367E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580909E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401980E+09 | 881747.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219316E+09 | 11561441.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78069313.06 | 68757789.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8638287.81 | 0.196091E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282648E+10 | 0.104556E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256393.54 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606367E+09 | 0.271849E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1238.63 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.27 | 29-JAN-12:00 | 181.57 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1276.00 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.70 | 05-FEB-14:42 | 152.34 | 10-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 1494.55 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.30 | 26-MAR-14:00 | 127.81 | 06-MAR-05:53 |
April | 2010.79 | 03-APR-09:09 | 1229.48 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.76 | 30-APR-13:06 | 92.58 | 05-APR-03:40 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 910.65 | 21-MAY-12:51 | 31.37 | 01-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.56 | 11-JUN-13:04 | 22.67 | 07-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 923.62 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.29 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 870.17 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 892.88 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 | 03-SEP-16:00 | 23.67 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1102.95 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.49 | 09-OCT-15:06 | 54.08 | 20-OCT-04:30 |
November | 2010.79 | 01-NOV-09:09 | 1387.48 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.57 | 19-NOV-13:52 | 79.05 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 1425.05 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | 10-DEC-12:00 | 116.18 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 37.27 | 0.00 | |||||
Maximum of Months | 2010.79 | 1494.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 910.65 | 181.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 839.76 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | 29-JAN-12:00 | 120.87 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 841.46 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 05-FEB-15:20 | 99.99 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 949.09 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.75 | 26-MAR-13:58 | 81.29 | 06-MAR-05:53 |
April | 1295.83 | 03-APR-09:09 | 719.94 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.78 | 30-APR-13:04 | 59.49 | 05-APR-01:20 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.26 | 21-MAY-12:51 | 20.89 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.48 | 11-JUN-13:04 | 15.32 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 573.74 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 509.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.32 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 509.78 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.93 | 03-SEP-15:43 | 16.21 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 552.37 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.87 | 09-OCT-15:04 | 36.49 | 20-OCT-04:30 |
November | 1295.83 | 01-NOV-09:09 | 919.61 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.60 | 19-NOV-14:10 | 50.82 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 930.96 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 | 10-DEC-12:40 | 72.44 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | 0.00 | |||||
Maximum of Months | 1295.83 | 949.09 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 602.26 | 120.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1093.21 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 29-JAN-12:00 | 190.34 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1207.59 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.60 | 05-FEB-15:05 | 163.27 | 10-FEB-23:50 |
March | 2010.83 | 01-MAR-10:09 | 1491.19 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.79 | 26-MAR-13:55 | 135.09 | 17-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1238.10 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.60 | 30-APR-13:04 | 93.63 | 05-APR-01:20 |
May | 2010.83 | 01-MAY-09:09 | 844.67 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 909.81 | 21-MAY-12:51 | 30.90 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 860.31 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.30 | 11-JUN-13:04 | 20.90 | 07-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 1086.98 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.29 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 864.26 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 888.58 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 | 03-SEP-16:00 | 23.72 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 882.27 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.30 | 09-OCT-15:10 | 56.37 | 20-OCT-03:57 |
November | 2010.83 | 01-NOV-09:09 | 1203.88 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.40 | 19-NOV-14:05 | 79.44 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 1333.08 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.41 | 10-DEC-12:17 | 113.37 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 844.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 0.00 | |||||
Maximum of Months | 2010.83 | 1491.19 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 909.81 | 190.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 794.30 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 29-JAN-12:00 | 138.90 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 753.00 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 | 05-FEB-15:05 | 123.35 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 969.29 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 | 26-MAR-13:55 | 112.64 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 831.29 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.51 | 30-APR-13:04 | 80.70 | 05-APR-01:20 |
May | 1295.83 | 01-MAY-09:09 | 575.15 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 603.43 | 21-MAY-12:51 | 24.75 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 577.69 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.19 | 11-JUN-13:04 | 17.72 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 749.03 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 595.30 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 704.14 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.74 | 03-SEP-16:00 | 16.45 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 770.56 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.05 | 09-OCT-15:04 | 39.77 | 20-OCT-03:57 |
November | 1295.83 | 01-NOV-09:09 | 772.88 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.66 | 05-NOV-15:04 | 62.10 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 887.77 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 10-DEC-12:17 | 95.46 | 16-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 575.15 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 0.00 | |||||
Maximum of Months | 1295.83 | 969.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 603.43 | 138.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1231.93 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.33 | 29-JAN-11:50 | 354.80 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1271.19 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.23 | 05-FEB-14:40 | 301.07 | 10-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1492.64 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 276.18 | 26-MAR-13:55 | 293.95 | 05-MAR-14:55 |
April | 2010.79 | 03-APR-09:09 | 1224.14 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.16 | 30-APR-12:53 | 211.85 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2118.22 | 21-MAY-12:51 | 62.66 | 02-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.79 | 11-JUN-13:04 | 36.47 | 07-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 918.07 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 861.58 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 885.59 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.47 | 04-SEP-16:54 | 45.01 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1093.74 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.26 | 09-OCT-15:04 | 115.93 | 20-OCT-04:03 |
November | 2010.79 | 01-NOV-09:09 | 1383.60 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.67 | 19-NOV-14:00 | 167.48 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1422.04 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.64 | 10-DEC-12:00 | 231.53 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 129.33 | 0.00 | |||||
Maximum of Months | 2010.79 | 1492.64 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2118.22 | 354.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 833.97 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 | 29-JAN-11:50 | 248.83 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 835.41 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 204.45 | 05-FEB-14:56 | 211.38 | 10-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 946.31 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 184.41 | 26-MAR-14:16 | 204.49 | 05-MAR-14:55 |
April | 1239.33 | 03-APR-07:10 | 713.38 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.11 | 30-APR-12:52 | 146.72 | 05-APR-01:00 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.06 | 21-MAY-12:51 | 44.93 | 02-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.37 | 11-JUN-13:04 | 26.43 | 07-JUN-04:30 |
July | 1239.33 | 03-JUL-07:10 | 569.85 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.63 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1239.33 | 01-AUG-07:10 | 509.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.80 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1239.33 | 01-SEP-07:10 | 509.78 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.09 | 03-SEP-16:00 | 31.63 | 25-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 546.66 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.08 | 09-OCT-15:04 | 81.66 | 20-OCT-04:03 |
November | 1239.33 | 01-NOV-07:10 | 915.69 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.05 | 19-NOV-13:56 | 112.73 | 22-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 927.32 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.87 | 10-DEC-12:40 | 153.58 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 | 0.00 | |||||
Maximum of Months | 1239.33 | 946.31 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.06 | 248.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1087.04 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 23-JAN-13:00 | 405.56 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1202.43 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 276.61 | 05-FEB-14:56 | 349.63 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1489.26 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.69 | 02-MAR-04:06 | 347.64 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 1232.82 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.16 | 30-APR-12:52 | 219.28 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2113.78 | 21-MAY-12:51 | 64.16 | 02-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 850.96 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.56 | 11-JUN-13:04 | 35.45 | 07-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 1079.08 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 855.38 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 881.07 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.15 | 04-SEP-16:54 | 48.27 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 873.60 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.95 | 09-OCT-15:10 | 132.58 | 20-OCT-04:03 |
November | 2010.83 | 01-NOV-09:09 | 1198.15 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.09 | 19-NOV-13:56 | 177.56 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1329.14 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.35 | 10-DEC-12:17 | 234.88 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 0.00 | |||||
Maximum of Months | 2010.83 | 1489.26 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2113.78 | 405.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 787.08 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.36 | 29-JAN-11:50 | 258.73 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 744.57 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 204.99 | 05-FEB-14:56 | 228.10 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 966.61 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.03 | 02-MAR-04:06 | 231.26 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 824.93 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.11 | 30-APR-12:52 | 158.83 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 570.42 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1400.96 | 21-MAY-12:51 | 49.60 | 02-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 573.12 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.41 | 11-JUN-13:04 | 30.66 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 740.45 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.62 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 591.77 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.80 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 693.86 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.76 | 04-SEP-16:54 | 33.87 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 763.66 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.70 | 09-OCT-15:04 | 90.58 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 766.20 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.68 | 19-NOV-13:56 | 119.30 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 882.98 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.65 | 10-DEC-12:00 | 160.86 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 570.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 67.36 | 0.00 | |||||
Maximum of Months | 1295.83 | 966.61 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1400.96 | 258.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1231.27 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.40 | 29-JAN-12:00 | 407.59 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1270.41 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 393.54 | 05-FEB-14:42 | 354.81 | 10-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1492.29 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 325.72 | 26-MAR-13:53 | 360.91 | 05-MAR-15:10 |
April | 2010.79 | 03-APR-09:09 | 1223.27 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.05 | 30-APR-12:55 | 255.10 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2583.29 | 21-MAY-12:51 | 77.37 | 02-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.44 | 11-JUN-13:04 | 47.57 | 07-JUN-04:40 |
July | 2010.79 | 03-JUL-09:09 | 917.85 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.92 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 861.26 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.89 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 885.31 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 719.91 | 04-SEP-16:54 | 43.44 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1092.97 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.51 | 09-OCT-15:04 | 145.24 | 20-OCT-04:03 |
November | 2010.79 | 01-NOV-09:09 | 1383.13 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.03 | 19-NOV-13:52 | 198.25 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 1421.59 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.55 | 10-DEC-12:20 | 267.49 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 166.40 | 0.00 | |||||
Maximum of Months | 2010.79 | 1492.29 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2583.29 | 407.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 833.61 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 29-JAN-12:00 | 286.55 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 834.95 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.36 | 05-FEB-15:08 | 248.95 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 946.07 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.16 | 26-MAR-13:46 | 251.00 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 712.74 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.58 | 30-APR-12:53 | 176.35 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.49 | 21-MAY-12:51 | 55.13 | 02-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.90 | 11-JUN-13:04 | 34.29 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 569.66 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.94 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 509.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 509.78 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.74 | 04-SEP-16:54 | 29.01 | 25-SEP-04:40 |
October | 1295.83 | 02-OCT-09:09 | 546.49 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.18 | 09-OCT-15:04 | 101.60 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 915.42 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.41 | 05-NOV-14:55 | 133.45 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 927.04 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 10-DEC-12:20 | 177.06 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 0.00 | |||||
Maximum of Months | 1295.83 | 946.07 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.49 | 286.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1086.03 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 23-JAN-13:00 | 471.93 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1201.56 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.60 | 05-FEB-15:05 | 416.60 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1488.90 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 313.21 | 26-MAR-14:00 | 429.12 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 1231.97 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.69 | 30-APR-12:53 | 263.89 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2577.61 | 21-MAY-12:51 | 79.15 | 02-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 850.61 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.47 | 11-JUN-13:04 | 46.16 | 07-JUN-04:40 |
July | 2010.83 | 03-JUL-09:09 | 1077.95 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.92 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 855.03 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.89 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 880.78 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.04 | 04-SEP-16:54 | 44.52 | 24-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 873.32 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 599.32 | 09-OCT-15:10 | 164.94 | 20-OCT-04:03 |
November | 2010.83 | 01-NOV-09:09 | 1197.50 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.55 | 05-NOV-14:55 | 211.03 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 1328.60 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.76 | 10-DEC-12:37 | 271.82 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 0.00 | |||||
Maximum of Months | 2010.83 | 1488.90 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2577.61 | 471.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 786.53 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.20 | 29-JAN-11:57 | 302.29 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 743.95 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 228.24 | 05-FEB-15:05 | 271.94 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 966.40 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.26 | 26-MAR-13:46 | 286.72 | 05-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 824.44 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.37 | 30-APR-12:53 | 191.30 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 570.26 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.87 | 21-MAY-12:51 | 60.85 | 02-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 572.96 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.46 | 11-JUN-13:04 | 40.13 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 739.80 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.94 | 30-JUL-14:40 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 591.64 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 693.20 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.69 | 04-SEP-16:54 | 33.39 | 24-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 763.26 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.30 | 09-OCT-15:04 | 112.74 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 765.83 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.67 | 19-NOV-13:46 | 142.58 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 882.60 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.50 | 10-DEC-12:13 | 188.10 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 570.26 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 86.20 | 0.00 | |||||
Maximum of Months | 1295.83 | 966.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.87 | 302.29 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 | 29-JAN-11:53 | 395.38 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.60 | 05-FEB-14:52 | 324.15 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.86 | 26-MAR-14:00 | 282.69 | 06-MAR-05:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.17 | 30-APR-12:52 | 202.68 | 05-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.58 | 21-MAY-12:51 | 67.36 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.97 | 11-JUN-12:52 | 45.97 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.01 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.50 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.60 | 03-SEP-16:00 | 52.09 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.51 | 09-OCT-14:51 | 111.49 | 20-OCT-04:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.25 | 19-NOV-13:52 | 176.25 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.39 | 10-DEC-12:40 | 244.09 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.58 | 395.38 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.63 | 29-JAN-11:53 | 651.05 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.92 | 05-FEB-14:42 | 545.73 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.97 | 26-MAR-14:00 | 491.88 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.84 | 30-APR-13:00 | 362.49 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3404.72 | 21-MAY-12:51 | 100.86 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.76 | 11-JUN-12:52 | 70.60 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1250.47 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1165.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.02 | 03-SEP-16:00 | 75.01 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764.04 | 09-OCT-14:51 | 182.47 | 20-OCT-04:12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.26 | 19-NOV-14:00 | 305.27 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.42 | 10-DEC-12:40 | 417.79 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.63 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3404.72 | 651.05 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.70 | 29-JAN-12:00 | 661.31 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.91 | 05-FEB-14:52 | 535.76 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.41 | 26-MAR-14:00 | 593.61 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.37 | 30-APR-13:00 | 376.89 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299.78 | 21-MAY-12:51 | 115.97 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.19 | 11-JUN-12:52 | 76.50 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1280.11 | 30-JUL-14:10 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1162.04 | 13-AUG-14:10 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.75 | 04-SEP-14:00 | 80.52 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.01 | 09-OCT-15:30 | 212.13 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.94 | 19-NOV-14:00 | 296.23 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.36 | 10-DEC-11:55 | 419.04 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.70 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299.78 | 661.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 110264.16 | 01-JAN-18:32 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 100845.80 | 21-FEB-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98924.62 | 08-MAR-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99666.90 | 13-APR-04:50 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98436.51 | 01-MAY-04:22 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89922.32 | 22-JUN-10:05 | 34109.28 | 29488.07 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 116576.28 | 30-OCT-05:51 | 17952.25 | 16382.87 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 106958.55 | 05-NOV-05:52 | 4488.06 | 4095.26 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 108911.26 | 12-DEC-22:17 | 5385.68 | 9829.72 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 116576.28 | 34109.28 | 29488.07 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 99412.64 | 02-JAN-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99844.75 | 08-FEB-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97359.11 | 16-MAR-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95379.65 | 13-APR-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98464.49 | 01-MAY-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98874.51 | 05-JUN-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99851.56 | 05-JUL-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99927.03 | 28-AUG-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95193.92 | 11-SEP-04:25 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99630.10 | 30-OCT-04:23 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 100951.66 | 27-NOV-05:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97407.59 | 28-DEC-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95193.92 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100951.66 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 82939.61 | 31-JAN-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85582.64 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86210.38 | 06-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85678.64 | 13-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80595.50 | 04-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67443.30 | 12-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72823.61 | 05-JUL-05:03 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74120.10 | 07-AUG-05:01 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76919.49 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88808.24 | 20-OCT-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88832.26 | 13-NOV-05:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85157.55 | 06-DEC-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67443.30 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88832.26 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 83871.39 | 30-JAN-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84765.71 | 09-FEB-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84518.78 | 24-MAR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84640.55 | 13-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80037.89 | 03-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83633.82 | 12-JUN-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84676.43 | 05-JUL-05:03 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86185.79 | 07-AUG-05:04 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84171.21 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82918.88 | 21-OCT-04:12 | 0.00 | 2149.44 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85411.15 | 13-NOV-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85371.98 | 11-DEC-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80037.89 | 0.00 | 2149.44 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86185.79 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12985.19 | 30-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
February | 17323.50 | 08-FEB-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 |
March | 16473.52 | 02-MAR-05:12 | 0.00 | 269.88 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 70.92 | 0.00 |
April | 20552.28 | 30-APR-16:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 0.00 |
May | 21994.03 | 28-MAY-11:02 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.05 | 0.00 |
June | 22705.74 | 25-JUN-16:22 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 124.90 | 0.00 |
July | 22316.68 | 30-JUL-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.57 | 0.00 |
August | 21646.50 | 05-AUG-17:42 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.48 | 0.00 |
September | 21768.12 | 03-SEP-15:42 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.99 | 0.00 |
October | 21145.30 | 09-OCT-13:02 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 155.92 | 0.00 |
November | 17343.56 | 30-NOV-05:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
December | 14983.71 | 12-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12985.19 | 0.00 | 219.72 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22705.74 | 1012.16 | 472.30 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 331.57 | 42.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9033.65 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 |
February | 13795.40 | 08-FEB-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.03 |
March | 11715.69 | 28-MAR-05:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
April | 17118.11 | 30-APR-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
May | 19568.29 | 28-MAY-10:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 | 0.00 |
June | 19646.37 | 25-JUN-10:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 | 0.00 |
July | 19488.22 | 30-JUL-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 98.34 | 0.00 |
August | 18569.41 | 13-AUG-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 165.44 | 0.00 |
September | 18743.10 | 03-SEP-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 95.10 | 0.00 |
October | 18456.14 | 22-OCT-08:53 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 | 0.00 |
November | 14856.83 | 05-NOV-10:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 | 0.00 |
December | 10422.94 | 12-DEC-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9033.65 | 0.00 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19646.37 | 652.28 | 260.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 165.44 | 26.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19729.47 | 30-JAN-05:12 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 |
February | 25024.95 | 05-FEB-12:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 79.67 | 0.00 |
March | 24801.50 | 26-MAR-12:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 0.00 |
April | 23076.66 | 30-APR-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 0.00 |
May | 24346.56 | 28-MAY-11:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 93.45 | 0.00 |
June | 24745.21 | 25-JUN-14:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 136.81 | 0.00 |
July | 24985.63 | 30-JUL-13:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 311.58 | 0.00 |
August | 24122.86 | 20-AUG-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 218.76 | 0.00 |
September | 25648.49 | 24-SEP-13:03 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 147.11 | 0.00 |
October | 27931.09 | 29-OCT-13:03 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 0.00 |
November | 25189.53 | 26-NOV-12:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
December | 26235.67 | 03-DEC-12:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19729.47 | 0.00 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27931.09 | 708.53 | 404.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 311.58 | 19.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18567.91 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 |
February | 20357.92 | 27-FEB-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 |
March | 20829.96 | 21-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
April | 24488.27 | 23-APR-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 57.39 | 0.00 |
May | 25043.52 | 28-MAY-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 61.76 | 0.00 |
June | 25975.75 | 25-JUN-15:41 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 | 0.00 |
July | 24906.93 | 02-JUL-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 124.24 | 0.00 |
August | 24669.83 | 06-AUG-15:43 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 125.12 | 0.00 |
September | 24267.56 | 03-SEP-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 154.93 | 0.00 |
October | 23386.32 | 09-OCT-15:02 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 135.60 | 0.00 |
November | 20843.07 | 28-NOV-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 |
December | 23801.95 | 03-DEC-14:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18567.91 | 0.00 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25975.75 | 521.82 | 260.89 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 154.93 | 29.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5278.47 | 23-JAN-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.52 | 0.00 |
February | 12380.62 | 09-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 |
March | 15332.78 | 27-MAR-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 |
April | 16056.68 | 23-APR-15:31 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 254.36 | 0.00 |
May | 21960.89 | 07-MAY-15:41 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 350.17 | 0.00 |
June | 21668.78 | 04-JUN-16:01 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 280.03 | 0.00 |
July | 22011.60 | 30-JUL-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.74 | 0.00 |
August | 22128.67 | 06-AUG-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 472.04 | 0.00 |
September | 23518.25 | 04-SEP-15:31 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 447.06 | 0.00 |
October | 21429.96 | 15-OCT-14:21 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 288.07 | 0.00 |
November | 14941.19 | 10-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 |
December | 12689.97 | 11-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5278.47 | 0.00 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23518.25 | 4021.58 | 1582.09 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 784.74 | 27.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6403.46 | 24-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
February | 10529.86 | 05-FEB-14:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 181.15 | 0.00 |
March | 15629.04 | 26-MAR-13:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 147.61 | 0.00 |
April | 19883.03 | 23-APR-10:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 0.00 |
May | 20439.10 | 07-MAY-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 72.58 | 0.00 |
June | 20333.06 | 04-JUN-10:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 141.23 | 0.00 |
July | 20019.81 | 30-JUL-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 233.69 | 0.00 |
August | 19554.70 | 06-AUG-15:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 315.79 | 0.00 |
September | 21170.85 | 04-SEP-10:11 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 204.04 | 0.00 |
October | 19404.58 | 15-OCT-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 59.46 | 0.00 |
November | 16775.12 | 05-NOV-14:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 166.36 | 0.00 |
December | 9353.30 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6403.46 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21170.85 | 2478.65 | 1019.56 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 315.79 | 18.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17173.78 | 22-JAN-14:33 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 |
February | 25834.05 | 05-FEB-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 0.00 |
March | 25127.51 | 26-MAR-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 196.38 | 0.00 |
April | 23228.61 | 02-APR-14:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 238.29 | 0.00 |
May | 24562.74 | 07-MAY-15:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 351.91 | 0.00 |
June | 23944.81 | 04-JUN-16:01 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 285.89 | 0.00 |
July | 24686.36 | 30-JUL-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 784.59 | 0.00 |
August | 24852.51 | 06-AUG-15:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 471.20 | 0.00 |
September | 27388.05 | 04-SEP-15:31 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 426.09 | 0.00 |
October | 26927.11 | 29-OCT-13:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 208.40 | 0.00 |
November | 26611.44 | 05-NOV-12:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 | 0.00 |
December | 24861.77 | 03-DEC-15:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17173.78 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27388.05 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 784.59 | 16.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8312.83 | 30-JAN-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
February | 18276.61 | 05-FEB-15:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 170.43 | 0.00 |
March | 21470.69 | 26-MAR-16:52 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 85.31 | 0.00 |
April | 21668.14 | 09-APR-16:02 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 | 0.00 |
May | 23120.00 | 07-MAY-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 199.79 | 0.00 |
June | 22337.36 | 04-JUN-17:21 | 0.00 | 198.23 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 143.64 | 0.00 |
July | 22035.50 | 30-JUL-15:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 490.87 | 0.00 |
August | 22716.49 | 06-AUG-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 257.57 | 0.00 |
September | 24966.75 | 04-SEP-16:11 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.69 | 0.00 |
October | 22190.06 | 15-OCT-14:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 172.18 | 0.00 |
November | 21784.23 | 05-NOV-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 137.54 | 0.00 |
December | 11952.26 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8312.83 | 0.00 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24966.75 | 652.28 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.87 | 19.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5515.54 | 23-JAN-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 0.00 |
February | 12249.19 | 06-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 |
March | 17460.58 | 28-MAR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
April | 21326.29 | 30-APR-13:31 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 395.87 | 0.00 |
May | 24127.43 | 21-MAY-13:02 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2254.49 | 0.00 |
June | 25920.73 | 04-JUN-16:11 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 299.22 | 0.00 |
July | 24779.26 | 30-JUL-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 954.01 | 0.00 |
August | 24916.66 | 06-AUG-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 572.05 | 0.00 |
September | 26076.85 | 03-SEP-14:51 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 564.60 | 0.00 |
October | 23956.13 | 01-OCT-12:42 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.22 | 0.00 |
November | 19981.96 | 05-NOV-14:52 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.74 | 0.00 |
December | 13380.07 | 11-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5515.54 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26076.85 | 4021.58 | 1582.09 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2254.49 | 33.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4332.76 | 24-JAN-11:00 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
February | 11022.62 | 06-FEB-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 |
March | 17784.88 | 26-MAR-13:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 193.49 | 0.00 |
April | 20023.98 | 30-APR-11:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 115.77 | 0.00 |
May | 20008.33 | 21-MAY-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 395.24 | 0.00 |
June | 21384.45 | 04-JUN-15:31 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 206.89 | 0.00 |
July | 20747.11 | 30-JUL-10:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 369.62 | 0.00 |
August | 20503.66 | 06-AUG-15:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 381.70 | 0.00 |
September | 22094.73 | 04-SEP-10:11 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 245.33 | 0.00 |
October | 20124.95 | 01-OCT-10:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 0.00 |
November | 19074.61 | 05-NOV-14:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 203.08 | 0.00 |
December | 9935.23 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4332.76 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22094.73 | 1295.83 | 509.78 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 395.24 | 22.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16290.50 | 29-JAN-15:43 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 |
February | 26793.04 | 05-FEB-12:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 227.07 | 0.00 |
March | 27500.11 | 26-MAR-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 251.80 | 0.00 |
April | 26277.09 | 30-APR-11:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 180.00 | 0.00 |
May | 26581.52 | 21-MAY-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 2262.52 | 0.00 |
June | 28140.96 | 04-JUN-15:31 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 321.15 | 0.00 |
July | 27375.18 | 30-JUL-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 953.97 | 0.00 |
August | 27563.02 | 06-AUG-15:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 571.15 | 0.00 |
September | 29996.81 | 03-SEP-14:51 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 527.45 | 0.00 |
October | 28940.77 | 01-OCT-12:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 216.93 | 0.00 |
November | 29013.10 | 05-NOV-12:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 139.84 | 0.00 |
December | 28109.43 | 03-DEC-13:22 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16290.50 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29996.81 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 2262.52 | 24.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6774.04 | 29-JAN-15:43 | 195.68 | 84.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
February | 14367.57 | 05-FEB-17:03 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 127.11 | 0.00 |
March | 22677.91 | 26-MAR-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 0.00 |
April | 22837.95 | 23-APR-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 167.14 | 0.00 |
May | 23612.87 | 21-MAY-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 360.53 | 0.00 |
June | 26022.69 | 04-JUN-16:11 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 178.53 | 0.00 |
July | 23932.42 | 30-JUL-15:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 596.20 | 0.00 |
August | 24657.74 | 06-AUG-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 323.42 | 0.00 |
September | 26129.09 | 03-SEP-14:51 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 343.31 | 0.00 |
October | 22903.32 | 01-OCT-17:22 | 0.00 | 202.30 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 140.69 | 0.00 |
November | 23444.39 | 05-NOV-15:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 158.55 | 0.00 |
December | 13036.87 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6774.04 | 0.00 | 84.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26129.09 | 652.28 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 596.20 | 23.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9559.20 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
February | 12945.27 | 08-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.63 |
March | 12235.59 | 27-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.47 | 0.00 |
April | 16093.70 | 29-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 22103.38 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
June | 22149.84 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 | 0.00 |
July | 25983.13 | 24-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 | 0.00 |
August | 25957.48 | 07-AUG-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 0.00 |
September | 25296.76 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 0.00 |
October | 22447.98 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 0.00 |
November | 16899.06 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
December | 11032.03 | 12-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9559.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25983.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.47 | 20.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4600.47 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
February | 6721.04 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.76 | 0.00 |
March | 9711.20 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.03 | 0.00 |
April | 10587.53 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
May | 12826.87 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 0.00 |
June | 14188.10 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
July | 18669.40 | 17-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.62 | 0.00 |
August | 21865.28 | 07-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 0.00 |
September | 20151.11 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 | 0.00 |
October | 13314.14 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 0.00 |
November | 11539.23 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 |
December | 7416.70 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4600.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21865.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.03 | 53.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8622.95 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.55 | 0.00 |
February | 13653.26 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.92 | 0.00 |
March | 19270.58 | 27-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.16 | 0.00 |
April | 21263.42 | 28-APR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.74 | 0.00 |
May | 24155.19 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.94 | 0.00 |
June | 24854.43 | 09-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.52 | 0.00 |
July | 27116.43 | 21-JUL-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.18 | 0.00 |
August | 27393.08 | 16-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.40 | 0.00 |
September | 28843.24 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.86 | 0.00 |
October | 19735.03 | 05-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.28 | 0.00 |
November | 15853.01 | 01-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.84 | 0.00 |
December | 10963.71 | 04-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8622.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 0.00 | |
Maximum of Months | 28843.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.86 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1900.49 | 29-JAN-17:40 | 23.38 | 35.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3840.62 | 05-FEB-17:20 | 11.69 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7210.83 | 31-MAR-23:50 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7876.55 | 30-APR-21:03 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3725.62 | 31-MAY-24:00 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5579.59 | 30-JUN-23:57 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7384.53 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7750.45 | 15-AUG-04:03 | 0.00 | 105.54 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3718.38 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5472.93 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6085.16 | 12-NOV-16:53 | 46.77 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7707.11 | 25-DEC-16:55 | 23.38 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1900.49 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7876.55 | 46.77 | 105.54 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1711.27 | 31-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3580.86 | 07-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6936.37 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7374.70 | 23-APR-17:44 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3473.06 | 31-MAY-24:00 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5219.72 | 30-JUN-23:57 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6984.85 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7233.62 | 14-AUG-02:23 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3412.59 | 30-SEP-23:33 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5229.59 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5535.70 | 05-NOV-16:54 | 58.46 | 87.96 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7202.50 | 04-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1711.27 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7374.70 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1738.81 | 31-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3651.47 | 05-FEB-17:20 | 11.69 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6883.11 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7602.22 | 23-APR-17:22 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3529.94 | 31-MAY-24:00 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5241.69 | 30-JUN-23:57 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7046.11 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7345.04 | 14-AUG-03:02 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3452.66 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5225.16 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5687.56 | 05-NOV-17:05 | 0.00 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7225.04 | 06-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1738.81 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7602.22 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93812.30 | 30-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 185391.78 | 07-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359488.49 | 31-MAR-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 370645.98 | 28-APR-13:05 | 10055.84 | 8314.37 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 178052.86 | 31-MAY-23:53 | 0.00 | 692.81 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269784.87 | 30-JUN-23:53 | 0.00 | 692.81 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362610.24 | 31-JUL-23:57 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 374754.19 | 10-AUG-21:01 | 2024.71 | 3695.42 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 179127.70 | 30-SEP-24:00 | 0.00 | 461.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 270669.21 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 278977.75 | 03-NOV-16:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369967.47 | 12-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93812.30 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 374754.19 | 10055.84 | 8314.37 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.176227E+13 | 1301167.90 | 24-JAN-16:10 | 0.00 | 0.00 |
February | 0.201156E+13 | 1599729.81 | 08-FEB-15:09 | 0.00 | 0.00 |
March | 0.275937E+13 | 1798093.67 | 01-MAR-15:09 | 0.00 | 0.00 |
April | 0.314062E+13 | 2001365.42 | 28-APR-15:09 | 0.00 | 0.00 |
May | 0.226236E+13 | 1671842.16 | 31-MAY-15:00 | 0.00 | 0.00 |
June | 0.278571E+13 | 1859609.54 | 12-JUN-14:30 | 0.00 | 0.00 |
July | 0.337178E+13 | 2131459.64 | 19-JUL-15:09 | 0.00 | 0.00 |
August | 0.394422E+13 | 2327571.96 | 10-AUG-15:00 | 0.00 | 0.00 |
September | 0.236156E+13 | 1759363.74 | 07-SEP-14:09 | 0.00 | 0.00 |
October | 0.264690E+13 | 1776959.86 | 06-OCT-15:50 | 0.00 | 0.00 |
November | 0.276176E+13 | 1861128.74 | 01-NOV-15:20 | 0.00 | 0.00 |
December | 0.302862E+13 | 1873801.43 | 04-DEC-11:39 | 0.00 | 0.00 |
Annual Sum or Average | 0.328367E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.176227E+13 | 1301167.90 | 0.00 | 0.00 | |
Maximum of Months | 0.394422E+13 | 2327571.96 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.206609E+12 | 0.353743E+11 | 0.766053E+12 | 0.213315E+12 | 0.189868E+12 | 0.478850E+11 | 25611236.62 | 0.177369E+12 | 0.946072E+11 | 0.279759E+10 | 0.00 | 0.283627E+11 | 0.00 |
February | 0.186576E+12 | 0.297811E+11 | 0.978954E+12 | 0.195308E+12 | 0.180750E+12 | 0.454664E+11 | 397851.32 | 0.260391E+12 | 0.106328E+12 | 0.293371E+10 | 0.00 | 0.250764E+11 | 0.00 |
March | 0.221317E+12 | 0.301448E+11 | 0.141687E+13 | 0.226028E+12 | 0.219384E+12 | 0.609944E+11 | 0.00 | 0.422883E+12 | 0.131965E+12 | 0.230189E+10 | 0.00 | 0.274741E+11 | 0.00 |
April | 0.196707E+12 | 0.262757E+11 | 0.165903E+13 | 0.211475E+12 | 0.225121E+12 | 0.709532E+11 | 0.00 | 0.578803E+12 | 0.149439E+12 | 0.306669E+09 | 0.00 | 0.225121E+11 | 0.00 |
May | 0.211636E+12 | 0.247812E+11 | 0.774844E+12 | 0.219671E+12 | 0.271670E+12 | 0.868359E+11 | 0.00 | 0.462518E+12 | 0.188896E+12 | 6852992.73 | 0.00 | 0.215036E+11 | 0.00 |
June | 0.210384E+12 | 0.230488E+11 | 0.106252E+13 | 0.217906E+12 | 0.281253E+12 | 0.957733E+11 | 0.00 | 0.667325E+12 | 0.208012E+12 | 0.00 | 0.00 | 0.194848E+11 | 0.00 |
July | 0.197054E+12 | 0.242828E+11 | 0.139340E+13 | 0.213239E+12 | 0.296763E+12 | 0.102904E+12 | 0.00 | 0.907575E+12 | 0.218545E+12 | 0.00 | 0.00 | 0.180087E+11 | 0.00 |
August | 0.220038E+12 | 0.262287E+11 | 0.173200E+13 | 0.226028E+12 | 0.321711E+12 | 0.108318E+12 | 0.00 | 0.106447E+13 | 0.224902E+12 | 0.00 | 0.00 | 0.205233E+11 | 0.00 |
September | 0.196878E+12 | 0.277324E+11 | 0.740713E+12 | 0.211475E+12 | 0.271141E+12 | 0.966618E+11 | 0.00 | 0.584807E+12 | 0.211632E+12 | 0.00 | 0.00 | 0.205190E+11 | 0.00 |
October | 0.205233E+12 | 0.316237E+11 | 0.108340E+13 | 0.213315E+12 | 0.256292E+12 | 0.862616E+11 | 0.00 | 0.553507E+12 | 0.193527E+12 | 76217406.34 | 0.00 | 0.236602E+11 | 0.00 |
November | 0.203936E+12 | 0.334772E+11 | 0.135889E+13 | 0.205268E+12 | 0.225821E+12 | 0.701438E+11 | 0.00 | 0.486778E+12 | 0.151462E+12 | 0.373168E+09 | 0.00 | 0.256107E+11 | 0.00 |
December | 0.200182E+12 | 0.362323E+11 | 0.170972E+13 | 0.213240E+12 | 0.200535E+12 | 0.570794E+11 | 0.00 | 0.449830E+12 | 0.129356E+12 | 0.526424E+10 | 0.00 | 0.271860E+11 | 0.00 |
Annual Sum or Average | 0.245655E+13 | 0.348983E+12 | 0.146764E+14 | 0.256627E+13 | 0.294031E+13 | 0.929277E+12 | 26009087.95 | 0.661626E+13 | 0.200867E+13 | 0.140603E+11 | 0.00 | 0.279922E+12 | 0.00 |
Minimum of Months | 0.186576E+12 | 0.230488E+11 | 0.740713E+12 | 0.195308E+12 | 0.180750E+12 | 0.454664E+11 | 0.00 | 0.177369E+12 | 0.946072E+11 | 0.00 | 0.00 | 0.180087E+11 | 0.00 |
Maximum of Months | 0.221317E+12 | 0.362323E+11 | 0.173200E+13 | 0.226028E+12 | 0.321711E+12 | 0.108318E+12 | 25611236.62 | 0.106447E+13 | 0.224902E+12 | 0.526424E+10 | 0.00 | 0.283627E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 226111.18 | 23-JAN-16:00 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233384.70 | 09-JAN-08:20 | 133506.44 | 23-JAN-13:30 | 28017.66 | 30-JAN-06:10 | 1994.36 | 02-JAN-06:00 |
February | 229973.87 | 09-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233383.63 | 09-FEB-08:20 | 171101.16 | 08-FEB-13:00 | 51006.60 | 06-FEB-15:20 | 280.77 | 13-FEB-06:49 |
March | 240337.66 | 15-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233393.66 | 15-MAR-07:19 | 212673.04 | 27-MAR-15:20 | 52869.08 | 23-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 229558.90 | 18-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233387.95 | 18-APR-07:19 | 215003.43 | 28-APR-15:20 | 52289.83 | 06-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 213600.87 | 23-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233379.51 | 23-MAY-07:19 | 236249.59 | 30-MAY-15:30 | 52268.65 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 214307.22 | 08-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 233379.88 | 08-JUN-07:19 | 241460.63 | 01-JUN-15:00 | 52713.64 | 15-JUN-16:30 | 0.00 | 01-JUN-00:10 |
July | 221308.06 | 20-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 233383.58 | 20-JUL-07:19 | 258058.14 | 31-JUL-15:50 | 55450.47 | 24-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 215437.24 | 29-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233380.48 | 29-AUG-07:19 | 267139.12 | 07-AUG-15:39 | 55290.02 | 21-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 217262.40 | 06-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233381.44 | 06-SEP-07:19 | 261769.61 | 05-SEP-15:00 | 54075.47 | 05-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 219508.73 | 31-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233382.63 | 31-OCT-07:19 | 220015.51 | 02-OCT-15:39 | 52985.17 | 20-OCT-12:39 | 0.00 | 01-OCT-00:10 |
November | 231953.64 | 29-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233382.92 | 29-NOV-08:20 | 204136.70 | 06-NOV-15:30 | 51650.13 | 01-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 235558.19 | 15-DEC-16:00 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233390.55 | 15-DEC-08:20 | 162909.98 | 04-DEC-13:00 | 50710.20 | 04-DEC-13:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 213600.87 | 40855.88 | 423497.50 | 233379.51 | 133506.44 | 28017.66 | 0.00 | |||||||
Maximum of Months | 240337.66 | 40855.88 | 778371.69 | 233393.66 | 267139.12 | 55450.47 | 1994.36 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 218819.56 | 30-JAN-13:00 | 86931.00 | 30-JAN-13:00 | 5460.40 | 01-JAN-05:00 | 0.00 | 37717.36 | 11-JAN-12:39 | 0.00 |
February | 298199.32 | 08-FEB-12:00 | 86931.00 | 06-FEB-11:20 | 6794.12 | 15-FEB-05:00 | 0.00 | 37276.79 | 01-FEB-12:20 | 0.00 |
March | 359117.59 | 23-MAR-11:00 | 86931.00 | 01-MAR-13:30 | 9429.58 | 08-MAR-05:00 | 0.00 | 34905.41 | 01-MAR-12:00 | 0.00 |
April | 427082.55 | 27-APR-10:09 | 86931.00 | 29-APR-19:49 | 5134.57 | 05-APR-04:00 | 0.00 | 31671.89 | 03-APR-11:39 | 0.00 |
May | 417383.67 | 31-MAY-15:00 | 86931.00 | 13-MAY-19:49 | 1438.24 | 07-MAY-10:00 | 0.00 | 28823.13 | 01-MAY-11:39 | 0.00 |
June | 485529.54 | 22-JUN-14:09 | 86931.00 | 01-JUN-21:49 | 0.00 | 01-JUN-00:10 | 0.00 | 26046.88 | 01-JUN-11:50 | 0.00 |
July | 628811.26 | 19-JUL-14:00 | 86931.00 | 01-JUL-00:20 | 0.00 | 01-JUL-00:10 | 0.00 | 24706.39 | 31-JUL-11:39 | 0.00 |
August | 694580.07 | 10-AUG-15:00 | 86931.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 26555.49 | 31-AUG-11:39 | 0.00 |
September | 503786.84 | 07-SEP-14:09 | 86931.00 | 01-SEP-00:40 | 0.00 | 01-SEP-00:10 | 0.00 | 29009.26 | 29-SEP-11:30 | 0.00 |
October | 418324.56 | 06-OCT-15:00 | 86931.00 | 01-OCT-00:20 | 4490.14 | 29-OCT-12:00 | 0.00 | 32997.64 | 30-OCT-11:20 | 0.00 |
November | 421802.45 | 01-NOV-14:09 | 86931.00 | 01-NOV-07:10 | 5680.71 | 22-NOV-06:00 | 0.00 | 35633.69 | 30-NOV-12:20 | 0.00 |
December | 377379.32 | 04-DEC-13:09 | 86931.00 | 04-DEC-09:09 | 13579.48 | 18-DEC-05:00 | 0.00 | 37400.47 | 22-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 218819.56 | 86931.00 | 0.00 | 0.00 | 24706.39 | 0.00 | ||||
Maximum of Months | 694580.07 | 86931.00 | 13579.48 | 0.00 | 37717.36 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1301167.90 | 24-JAN-16:10 | 212849.03 | 423497.50 | 0.00 | 233266.29 | 116087.57 | 27345.64 | 0.00 | 194712.07 | 65353.62 |
February | 1599729.81 | 08-FEB-15:09 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 161815.48 | 50706.43 | 0.00 | 291981.60 | 86931.00 |
March | 1798093.67 | 01-MAR-15:09 | 212815.01 | 660080.29 | 0.00 | 233115.89 | 181195.56 | 51063.79 | 0.00 | 352624.19 | 86931.00 |
April | 2001365.42 | 28-APR-15:09 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 214288.02 | 51072.77 | 0.00 | 402898.32 | 86931.00 |
May | 1671842.16 | 31-MAY-15:00 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 226291.28 | 52268.65 | 0.00 | 417383.67 | 86931.00 |
June | 1859609.54 | 12-JUN-14:30 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 236180.36 | 52546.88 | 0.00 | 481324.15 | 86931.00 |
July | 2131459.64 | 19-JUL-15:09 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 240517.26 | 53627.28 | 0.00 | 625805.82 | 86931.00 |
August | 2327571.96 | 10-AUG-15:00 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 248658.68 | 54068.43 | 0.00 | 694580.07 | 86931.00 |
September | 1759363.74 | 07-SEP-14:09 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 229936.16 | 53202.06 | 0.00 | 503786.84 | 86931.00 |
October | 1776959.86 | 06-OCT-15:50 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 210882.17 | 51864.46 | 0.00 | 416228.16 | 86931.00 |
November | 1861128.74 | 01-NOV-15:20 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 190540.42 | 51378.38 | 0.00 | 401009.93 | 86931.00 |
December | 1873801.43 | 04-DEC-11:39 | 212815.01 | 778371.69 | 0.00 | 233115.89 | 150210.53 | 50433.46 | 0.00 | 332661.96 | 86931.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1301167.90 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 116087.57 | 27345.64 | 0.00 | 194712.07 | 65353.62 | |
Maximum of Months | 2327571.96 | 212849.03 | 778371.69 | 0.00 | 233266.29 | 248658.68 | 54068.43 | 0.00 | 694580.07 | 86931.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 27.71 | 34.50 | 27.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 139.33 | 27.95 | 88.33 | 27.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 260.00 | 27.86 | 179.17 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 486.83 | 28.61 | 330.67 | 28.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 724.83 | 29.86 | 494.33 | 29.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 714.00 | 30.14 | 490.00 | 30.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.72 | 497.00 | 30.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 31.18 | 514.00 | 31.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.88 | 485.00 | 30.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 727.83 | 30.57 | 486.50 | 30.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 484.00 | 28.61 | 303.50 | 28.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 145.17 | 27.91 | 88.83 | 27.97 |
Annual Sum or Average | 0.00 | 0.00 | 5956.33 | 29.97 | 3991.83 | 30.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 27.71 | 34.50 | 27.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 31.18 | 514.00 | 31.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.63 | 0.00 | 25.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.61 | 0.00 | 25.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.89 | 0.00 | 25.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.98 | 0.17 | 25.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.16 | 0.00 | 26.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.23 | 0.83 | 26.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 26.53 | 6.17 | 26.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.21 | 0.00 | 26.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.16 | 0.17 | 26.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.77 | 0.00 | 25.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.68 | 0.00 | 25.68 |
Annual Sum or Average | 0.00 | 0.00 | 95.83 | 26.22 | 7.33 | 26.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 26.53 | 6.17 | 26.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.89 | 0.00 | 25.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.67 | 0.00 | 25.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.89 | 0.00 | 25.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.76 | 0.00 | 25.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.99 | 3.67 | 27.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.24 | 13.67 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 27.33 | 13.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 27.57 | 26.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 | 27.48 | 24.17 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 27.34 | 15.00 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.15 | 12.50 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.71 | 2.33 | 26.95 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 346.83 | 27.38 | 111.17 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 27.57 | 26.00 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.83 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.11 | 2.00 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.34 | 11.17 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 27.44 | 16.33 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 27.43 | 15.00 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 27.67 | 26.83 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 81.33 | 27.60 | 23.33 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 27.50 | 18.17 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 | 27.36 | 16.17 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.19 | 8.00 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 400.67 | 27.51 | 138.00 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 27.67 | 26.83 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.40 | 5.33 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.51 | 5.33 | 27.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.34 | 4.00 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.25 | 8.50 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.19 | 12.00 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 27.21 | 11.17 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 80.83 | 27.51 | 23.67 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.50 | 27.47 | 24.50 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 27.45 | 16.50 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.45 | 16.33 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.58 | 13.17 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.60 | 8.50 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 392.00 | 27.42 | 149.00 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.19 | 4.00 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 82.50 | 27.60 | 24.50 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.49 | 1.33 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.27 | 4.50 | 27.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.19 | 7.83 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 27.57 | 18.17 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 27.46 | 16.83 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 27.61 | 20.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.83 | 27.98 | 26.83 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.50 | 28.05 | 24.50 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 27.51 | 19.33 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 60.83 | 27.45 | 19.33 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 27.39 | 14.67 | 27.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.21 | 11.33 | 27.38 |
Annual Sum or Average | 0.00 | 0.00 | 571.33 | 27.64 | 184.67 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.19 | 1.33 | 27.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.83 | 28.05 | 26.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.34 | 1.83 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.24 | 9.33 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.03 | 9.00 | 27.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 27.26 | 15.33 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.11 | 10.00 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.21 | 9.67 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.17 | 5.50 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 147.17 | 27.18 | 60.67 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 27.34 | 15.33 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.54 | 2.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.62 | 10.83 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.41 | 13.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.19 | 10.67 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 27.49 | 17.83 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.34 | 13.17 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.33 | 12.67 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.41 | 13.67 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.38 | 4.83 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 227.00 | 27.39 | 99.00 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 27.62 | 17.83 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.43 | 3.33 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.63 | 3.67 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.50 | 3.33 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.51 | 6.83 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.25 | 9.50 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 26.92 | 8.17 | 27.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 27.25 | 14.17 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 27.19 | 10.67 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.27 | 11.33 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.46 | 12.83 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.80 | 11.83 | 27.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.60 | 6.67 | 27.61 |
Annual Sum or Average | 0.00 | 0.00 | 210.33 | 27.31 | 102.33 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.92 | 3.33 | 27.13 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 27.80 | 14.17 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.53 | 1.00 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.24 | 2.17 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.45 | 7.00 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.36 | 11.83 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 27.32 | 10.67 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 27.55 | 22.00 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 27.50 | 18.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 27.34 | 12.83 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.27 | 10.50 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.59 | 5.67 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 312.83 | 27.43 | 102.17 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 27.59 | 22.00 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.03 | 0.83 | 27.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.47 | 3.33 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.40 | 9.83 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.19 | 9.50 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 27.44 | 16.33 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 27.29 | 11.17 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.36 | 10.33 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.39 | 7.50 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 184.33 | 27.35 | 69.00 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 27.47 | 16.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.51 | 2.00 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.68 | 11.00 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.58 | 12.67 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.35 | 10.83 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 27.62 | 18.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 27.46 | 14.17 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.49 | 12.83 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.58 | 13.33 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.41 | 5.83 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 253.33 | 27.52 | 101.83 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 27.68 | 18.67 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.44 | 2.17 | 27.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.67 | 3.17 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.50 | 3.50 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.59 | 7.67 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.41 | 9.83 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.17 | 8.83 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.41 | 15.83 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 27.35 | 11.83 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.40 | 11.50 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.61 | 12.50 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.85 | 11.17 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.60 | 5.67 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 242.33 | 27.44 | 103.67 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.17 | 2.17 | 27.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.85 | 15.83 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.66 | 1.00 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.44 | 2.67 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.57 | 7.83 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 27.49 | 12.17 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.43 | 12.17 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | 27.65 | 22.67 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 27.60 | 18.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 27.44 | 13.33 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.41 | 10.33 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.63 | 6.33 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
Annual Sum or Average | 0.00 | 0.00 | 330.50 | 27.53 | 107.17 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | 27.66 | 22.67 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.91 | 17.33 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 618.50 | 28.25 | 407.67 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 638.50 | 28.24 | 425.00 | 28.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 618.50 | 28.25 | 407.67 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.92 | 11.67 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 446.83 | 28.25 | 362.17 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 458.50 | 28.24 | 373.83 | 28.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 446.83 | 28.25 | 362.17 | 28.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.86 | 13.50 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 433.83 | 28.35 | 346.17 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 448.67 | 28.33 | 359.67 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 433.83 | 28.35 | 346.17 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.99 | 1.83 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 27.95 | 73.67 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 75.50 | 27.95 | 75.50 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 27.99 | 73.67 | 27.99 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.33 | 28.12 | 450.33 | 25.07 | 30.33 | 25.25 |
February | 108.17 | 27.58 | 442.67 | 25.76 | 108.17 | 26.06 |
March | 172.83 | 27.89 | 503.83 | 26.32 | 172.83 | 26.64 |
April | 324.67 | 28.73 | 480.00 | 27.95 | 324.67 | 28.17 |
May | 490.33 | 29.97 | 508.00 | 29.87 | 490.33 | 29.90 |
June | 484.33 | 30.28 | 496.00 | 30.21 | 484.33 | 30.23 |
July | 497.00 | 30.82 | 497.00 | 30.82 | 497.00 | 30.82 |
August | 514.00 | 31.26 | 514.00 | 31.26 | 514.00 | 31.26 |
September | 485.00 | 30.97 | 485.00 | 30.97 | 485.00 | 30.97 |
October | 476.33 | 30.77 | 502.00 | 30.61 | 476.33 | 30.66 |
November | 284.83 | 28.85 | 487.33 | 27.71 | 284.83 | 28.02 |
December | 106.00 | 27.61 | 484.83 | 25.63 | 106.00 | 25.93 |
Annual Sum or Average | 3973.83 | 30.08 | 5851.00 | 29.04 | 3973.83 | 29.34 |
Minimum of Months | 30.33 | 27.58 | 442.67 | 25.07 | 30.33 | 25.25 |
Maximum of Months | 514.00 | 31.26 | 514.00 | 31.26 | 514.00 | 31.26 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 437.33 | 24.44 | 0.00 | 24.44 |
February | 0.50 | 27.08 | 436.33 | 24.42 | 0.50 | 24.43 |
March | 0.00 | 0.00 | 490.83 | 24.30 | 0.00 | 24.30 |
April | 5.00 | 26.62 | 479.00 | 24.35 | 5.00 | 24.37 |
May | 10.33 | 26.60 | 507.17 | 24.47 | 10.33 | 24.51 |
June | 15.33 | 26.60 | 496.00 | 24.48 | 15.33 | 24.54 |
July | 50.67 | 26.58 | 497.00 | 24.74 | 50.67 | 24.89 |
August | 52.00 | 26.64 | 514.00 | 24.67 | 52.00 | 24.84 |
September | 39.33 | 26.59 | 485.00 | 24.65 | 39.33 | 24.79 |
October | 32.33 | 26.66 | 497.50 | 24.66 | 32.33 | 24.78 |
November | 0.00 | 0.00 | 485.67 | 24.43 | 0.00 | 24.43 |
December | 0.00 | 0.00 | 480.33 | 24.40 | 0.00 | 24.40 |
Annual Sum or Average | 205.50 | 26.61 | 5806.17 | 24.51 | 205.50 | 24.58 |
Minimum of Months | 0.00 | 0.00 | 436.33 | 24.30 | 0.00 | 24.30 |
Maximum of Months | 52.00 | 27.08 | 514.00 | 24.74 | 52.00 | 24.89 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.00 | 23.63 | 344.33 | 24.25 | 0.00 | 24.25 |
February | 4.67 | 23.69 | 390.50 | 24.29 | 0.00 | 24.29 |
March | 0.67 | 23.62 | 426.17 | 24.29 | 0.00 | 24.29 |
April | 1.00 | 23.83 | 438.33 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 482.17 | 24.15 | 0.00 | 24.15 |
June | 0.00 | 0.00 | 495.50 | 24.10 | 0.00 | 24.10 |
July | 0.00 | 0.00 | 496.17 | 24.12 | 0.00 | 24.12 |
August | 0.00 | 0.00 | 514.00 | 24.10 | 0.00 | 24.10 |
September | 0.00 | 0.00 | 485.00 | 24.16 | 0.00 | 24.16 |
October | 0.00 | 0.00 | 486.50 | 24.24 | 0.00 | 24.24 |
November | 0.00 | 0.00 | 481.50 | 24.30 | 0.00 | 24.30 |
December | 8.67 | 23.60 | 432.83 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 37.00 | 23.63 | 5473.00 | 24.20 | 0.00 | 24.20 |
Minimum of Months | 0.00 | 0.00 | 344.33 | 24.10 | 0.00 | 24.10 |
Maximum of Months | 22.00 | 23.83 | 514.00 | 24.30 | 0.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.67 | 23.41 | 242.67 | 23.84 | 13.50 | 23.84 |
February | 57.17 | 23.43 | 328.50 | 24.11 | 0.00 | 24.11 |
March | 11.83 | 23.46 | 409.83 | 24.24 | 0.00 | 24.24 |
April | 0.00 | 0.00 | 444.67 | 24.28 | 0.00 | 24.28 |
May | 0.00 | 0.00 | 487.67 | 24.24 | 0.00 | 24.24 |
June | 0.00 | 0.00 | 496.00 | 24.18 | 0.00 | 24.18 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.20 | 0.00 | 24.20 |
September | 1.17 | 26.60 | 485.00 | 24.25 | 1.17 | 24.26 |
October | 0.00 | 0.00 | 489.83 | 24.28 | 0.00 | 24.28 |
November | 0.00 | 0.00 | 476.00 | 24.29 | 0.00 | 24.29 |
December | 59.00 | 23.42 | 357.33 | 24.07 | 0.00 | 24.07 |
Annual Sum or Average | 272.83 | 23.43 | 5228.50 | 24.19 | 14.67 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 242.67 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 143.67 | 26.60 | 514.00 | 24.29 | 13.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.83 | 23.38 | 282.83 | 24.07 | 0.00 | 24.07 |
February | 24.00 | 23.39 | 376.50 | 24.27 | 0.00 | 24.27 |
March | 4.33 | 23.69 | 458.17 | 24.29 | 0.17 | 24.29 |
April | 21.67 | 26.83 | 477.83 | 24.55 | 21.67 | 24.64 |
May | 71.83 | 26.87 | 508.00 | 24.87 | 71.83 | 25.09 |
June | 85.00 | 26.84 | 496.00 | 24.89 | 85.00 | 25.14 |
July | 114.50 | 26.95 | 497.00 | 25.14 | 114.50 | 25.42 |
August | 93.50 | 26.95 | 514.00 | 24.95 | 93.50 | 25.22 |
September | 88.50 | 26.85 | 485.00 | 24.97 | 88.50 | 25.22 |
October | 65.33 | 26.84 | 502.00 | 24.87 | 65.33 | 25.07 |
November | 16.00 | 26.78 | 487.17 | 24.52 | 16.00 | 24.59 |
December | 10.17 | 23.64 | 429.67 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 672.67 | 26.28 | 5514.17 | 24.69 | 556.50 | 24.87 |
Minimum of Months | 4.33 | 23.38 | 282.83 | 24.07 | 0.00 | 24.07 |
Maximum of Months | 114.50 | 26.95 | 514.00 | 25.14 | 114.50 | 25.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.67 | 23.40 | 337.33 | 24.24 | 0.50 | 24.24 |
February | 22.33 | 23.85 | 402.00 | 24.34 | 3.17 | 24.36 |
March | 14.33 | 25.06 | 465.33 | 24.34 | 6.50 | 24.38 |
April | 43.17 | 26.89 | 477.17 | 24.68 | 43.17 | 24.85 |
May | 86.50 | 26.95 | 508.00 | 24.96 | 86.50 | 25.21 |
June | 88.17 | 26.90 | 496.00 | 24.92 | 88.17 | 25.18 |
July | 115.17 | 27.01 | 497.00 | 25.16 | 115.17 | 25.46 |
August | 94.83 | 26.99 | 514.00 | 24.97 | 94.83 | 25.25 |
September | 100.00 | 26.94 | 485.00 | 25.05 | 100.00 | 25.32 |
October | 82.00 | 26.93 | 502.00 | 24.97 | 82.00 | 25.21 |
November | 35.17 | 26.83 | 487.00 | 24.66 | 35.17 | 24.80 |
December | 15.17 | 23.36 | 427.83 | 24.26 | 0.00 | 24.26 |
Annual Sum or Average | 748.50 | 26.50 | 5598.67 | 24.76 | 655.17 | 24.96 |
Minimum of Months | 14.33 | 23.36 | 337.33 | 24.24 | 0.00 | 24.24 |
Maximum of Months | 115.17 | 27.01 | 514.00 | 25.16 | 115.17 | 25.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.67 | 24.42 | 385.50 | 24.50 | 16.67 | 24.59 |
February | 34.17 | 25.45 | 409.50 | 24.55 | 19.83 | 24.65 |
March | 20.67 | 26.26 | 475.83 | 24.45 | 16.83 | 24.53 |
April | 35.50 | 26.89 | 479.33 | 24.64 | 35.50 | 24.79 |
May | 62.17 | 26.88 | 508.00 | 24.83 | 62.17 | 25.03 |
June | 71.67 | 26.82 | 496.00 | 24.83 | 71.67 | 25.05 |
July | 110.83 | 26.92 | 497.00 | 25.11 | 110.83 | 25.39 |
August | 94.00 | 26.95 | 514.00 | 24.96 | 94.00 | 25.22 |
September | 99.17 | 26.91 | 485.00 | 25.03 | 99.17 | 25.30 |
October | 90.67 | 26.97 | 502.00 | 25.03 | 90.67 | 25.29 |
November | 56.83 | 26.97 | 489.00 | 24.84 | 56.83 | 25.04 |
December | 41.17 | 26.56 | 471.17 | 24.66 | 37.17 | 24.81 |
Annual Sum or Average | 771.50 | 26.64 | 5712.33 | 24.81 | 711.33 | 25.01 |
Minimum of Months | 20.67 | 24.42 | 385.50 | 24.45 | 16.67 | 24.53 |
Maximum of Months | 110.83 | 26.97 | 514.00 | 25.11 | 110.83 | 25.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 25.28 | 413.33 | 24.56 | 9.17 | 24.60 |
February | 24.83 | 26.94 | 445.17 | 24.70 | 24.83 | 24.81 |
March | 42.17 | 26.95 | 507.83 | 24.72 | 42.17 | 24.88 |
April | 95.33 | 26.92 | 485.00 | 25.02 | 95.33 | 25.29 |
May | 99.33 | 26.90 | 508.00 | 25.00 | 99.33 | 25.27 |
June | 96.33 | 26.93 | 496.00 | 24.97 | 96.33 | 25.24 |
July | 118.83 | 27.06 | 497.00 | 25.20 | 118.83 | 25.50 |
August | 101.17 | 27.09 | 514.00 | 25.04 | 101.17 | 25.33 |
September | 105.50 | 26.91 | 485.00 | 25.06 | 105.50 | 25.34 |
October | 109.17 | 26.90 | 502.00 | 25.08 | 109.17 | 25.36 |
November | 84.33 | 26.93 | 489.00 | 25.01 | 84.33 | 25.26 |
December | 60.50 | 26.94 | 495.33 | 24.92 | 60.50 | 25.11 |
Annual Sum or Average | 955.67 | 26.92 | 5837.67 | 24.96 | 946.67 | 25.20 |
Minimum of Months | 18.17 | 25.28 | 413.33 | 24.56 | 9.17 | 24.60 |
Maximum of Months | 118.83 | 27.09 | 514.00 | 25.20 | 118.83 | 25.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.17 | 23.06 | 125.50 | 23.38 | 0.00 | 23.38 |
February | 110.17 | 23.08 | 235.33 | 23.82 | 0.00 | 23.82 |
March | 53.67 | 23.26 | 370.67 | 24.13 | 0.00 | 24.13 |
April | 13.17 | 25.64 | 452.50 | 24.47 | 10.00 | 24.51 |
May | 41.00 | 26.88 | 507.00 | 24.70 | 41.00 | 24.86 |
June | 44.00 | 26.86 | 496.00 | 24.69 | 44.00 | 24.85 |
July | 76.83 | 26.89 | 497.00 | 24.95 | 76.83 | 25.18 |
August | 59.00 | 26.85 | 514.00 | 24.75 | 59.00 | 24.95 |
September | 50.00 | 26.82 | 485.00 | 24.76 | 50.00 | 24.94 |
October | 35.67 | 26.61 | 496.33 | 24.66 | 35.67 | 24.78 |
November | 3.50 | 23.45 | 463.83 | 24.34 | 0.17 | 24.34 |
December | 140.00 | 23.16 | 279.17 | 23.81 | 0.17 | 23.81 |
Annual Sum or Average | 896.17 | 24.42 | 4922.33 | 24.44 | 316.83 | 24.56 |
Minimum of Months | 3.50 | 23.06 | 125.50 | 23.38 | 0.00 | 23.38 |
Maximum of Months | 269.17 | 26.89 | 514.00 | 24.95 | 76.83 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 122.67 | 23.11 | 183.83 | 23.83 | 0.17 | 23.83 |
February | 49.83 | 23.17 | 280.33 | 24.20 | 2.00 | 24.22 |
March | 33.00 | 24.08 | 346.67 | 24.41 | 7.50 | 24.46 |
April | 51.50 | 26.73 | 396.00 | 24.88 | 50.33 | 25.08 |
May | 60.50 | 26.99 | 430.00 | 24.98 | 60.50 | 25.20 |
June | 53.00 | 26.97 | 418.00 | 24.90 | 53.00 | 25.11 |
July | 93.00 | 26.98 | 422.00 | 25.20 | 93.00 | 25.48 |
August | 77.50 | 26.92 | 433.00 | 24.99 | 77.50 | 25.25 |
September | 63.83 | 26.98 | 410.00 | 25.03 | 63.83 | 25.26 |
October | 60.00 | 26.89 | 426.50 | 25.00 | 60.00 | 25.20 |
November | 25.17 | 26.68 | 409.33 | 24.72 | 24.17 | 24.83 |
December | 61.83 | 23.16 | 290.50 | 24.12 | 0.50 | 24.12 |
Annual Sum or Average | 751.83 | 25.61 | 4446.17 | 24.75 | 492.50 | 24.94 |
Minimum of Months | 25.17 | 23.11 | 183.83 | 23.83 | 0.17 | 23.83 |
Maximum of Months | 122.67 | 26.99 | 433.00 | 25.20 | 93.00 | 25.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.83 | 23.76 | 345.83 | 24.33 | 15.17 | 24.41 |
February | 61.00 | 24.19 | 379.00 | 24.39 | 17.50 | 24.49 |
March | 33.67 | 24.58 | 435.00 | 24.41 | 12.17 | 24.47 |
April | 32.83 | 26.59 | 463.33 | 24.63 | 31.50 | 24.76 |
May | 39.17 | 26.89 | 506.67 | 24.69 | 39.17 | 24.84 |
June | 38.83 | 26.84 | 496.00 | 24.65 | 38.83 | 24.80 |
July | 73.00 | 26.89 | 497.00 | 24.93 | 73.00 | 25.15 |
August | 66.33 | 26.86 | 514.00 | 24.79 | 66.33 | 25.00 |
September | 64.17 | 26.94 | 485.00 | 24.88 | 64.17 | 25.10 |
October | 67.33 | 26.99 | 502.00 | 24.94 | 67.33 | 25.16 |
November | 52.67 | 26.96 | 486.83 | 24.83 | 52.50 | 25.02 |
December | 67.17 | 24.98 | 424.67 | 24.56 | 32.50 | 24.71 |
Annual Sum or Average | 688.00 | 25.93 | 5535.33 | 24.69 | 510.17 | 24.86 |
Minimum of Months | 32.83 | 23.76 | 345.83 | 24.33 | 12.17 | 24.41 |
Maximum of Months | 91.83 | 26.99 | 514.00 | 24.94 | 73.00 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 141.67 | 23.22 | 261.00 | 23.91 | 2.50 | 23.92 |
February | 58.50 | 23.41 | 346.83 | 24.20 | 4.50 | 24.23 |
March | 27.83 | 24.66 | 440.00 | 24.42 | 10.33 | 24.47 |
April | 37.50 | 26.81 | 477.50 | 24.72 | 37.50 | 24.87 |
May | 70.83 | 26.96 | 508.00 | 24.89 | 70.83 | 25.12 |
June | 85.00 | 26.86 | 496.00 | 24.89 | 85.00 | 25.15 |
July | 114.00 | 26.92 | 497.00 | 25.12 | 114.00 | 25.40 |
August | 96.67 | 26.90 | 514.00 | 24.94 | 96.67 | 25.21 |
September | 87.67 | 26.92 | 485.00 | 24.98 | 87.67 | 25.24 |
October | 61.00 | 26.90 | 499.67 | 24.89 | 61.00 | 25.09 |
November | 27.33 | 26.86 | 486.33 | 24.64 | 27.17 | 24.75 |
December | 54.33 | 23.47 | 380.67 | 24.23 | 4.17 | 24.25 |
Annual Sum or Average | 862.33 | 25.77 | 5392.00 | 24.70 | 601.33 | 24.90 |
Minimum of Months | 27.33 | 23.22 | 261.00 | 23.91 | 2.50 | 23.92 |
Maximum of Months | 141.67 | 26.96 | 514.00 | 25.12 | 114.00 | 25.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 324.83 | 22.71 | 107.50 | 23.04 | 0.00 | 23.04 |
February | 163.00 | 22.85 | 204.33 | 23.57 | 0.33 | 23.57 |
March | 84.00 | 23.13 | 349.17 | 24.03 | 0.83 | 24.03 |
April | 37.67 | 25.23 | 438.17 | 24.51 | 24.67 | 24.60 |
May | 48.00 | 26.89 | 506.67 | 24.75 | 48.00 | 24.92 |
June | 49.33 | 26.88 | 496.00 | 24.72 | 49.33 | 24.90 |
July | 85.17 | 26.92 | 497.00 | 24.99 | 85.17 | 25.24 |
August | 69.67 | 26.86 | 514.00 | 24.80 | 69.67 | 25.02 |
September | 56.83 | 26.81 | 485.00 | 24.80 | 56.83 | 24.99 |
October | 42.50 | 26.63 | 492.67 | 24.70 | 42.50 | 24.84 |
November | 21.00 | 23.74 | 447.67 | 24.32 | 2.83 | 24.33 |
December | 189.33 | 22.85 | 238.33 | 23.56 | 1.83 | 23.56 |
Annual Sum or Average | 1171.33 | 24.12 | 4776.50 | 24.39 | 382.00 | 24.53 |
Minimum of Months | 21.00 | 22.71 | 107.50 | 23.04 | 0.00 | 23.04 |
Maximum of Months | 324.83 | 26.92 | 514.00 | 24.99 | 85.17 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 187.33 | 22.86 | 190.00 | 23.53 | 0.00 | 23.53 |
February | 82.17 | 22.93 | 296.83 | 23.99 | 2.33 | 24.01 |
March | 59.50 | 23.69 | 405.17 | 24.26 | 8.83 | 24.31 |
April | 58.17 | 26.39 | 463.67 | 24.75 | 51.83 | 24.93 |
May | 63.50 | 27.01 | 508.00 | 24.86 | 63.50 | 25.08 |
June | 59.50 | 26.97 | 496.00 | 24.80 | 59.50 | 25.01 |
July | 98.83 | 27.00 | 497.00 | 25.08 | 98.83 | 25.35 |
August | 82.50 | 26.94 | 514.00 | 24.88 | 82.50 | 25.13 |
September | 69.17 | 26.98 | 485.00 | 24.91 | 69.17 | 25.14 |
October | 62.33 | 26.90 | 501.67 | 24.87 | 62.33 | 25.07 |
November | 32.67 | 26.25 | 472.00 | 24.60 | 27.33 | 24.72 |
December | 108.67 | 23.02 | 312.67 | 23.91 | 2.67 | 23.91 |
Annual Sum or Average | 964.33 | 25.12 | 5142.00 | 24.61 | 528.83 | 24.79 |
Minimum of Months | 32.67 | 22.86 | 190.00 | 23.53 | 0.00 | 23.53 |
Maximum of Months | 187.33 | 27.01 | 514.00 | 25.08 | 98.83 | 25.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 127.83 | 23.17 | 316.33 | 24.07 | 12.17 | 24.14 |
February | 79.50 | 23.56 | 354.33 | 24.24 | 15.67 | 24.33 |
March | 63.67 | 23.99 | 411.50 | 24.33 | 14.33 | 24.40 |
April | 49.33 | 25.91 | 451.00 | 24.64 | 39.17 | 24.78 |
May | 45.83 | 26.91 | 505.67 | 24.74 | 45.83 | 24.90 |
June | 45.17 | 26.87 | 496.00 | 24.69 | 45.17 | 24.86 |
July | 81.50 | 26.91 | 497.00 | 24.98 | 81.50 | 25.21 |
August | 75.33 | 26.88 | 514.00 | 24.83 | 75.33 | 25.07 |
September | 71.17 | 26.93 | 485.00 | 24.91 | 71.17 | 25.14 |
October | 68.17 | 26.98 | 502.00 | 24.94 | 68.17 | 25.16 |
November | 51.83 | 26.84 | 479.00 | 24.80 | 49.83 | 24.99 |
December | 88.83 | 24.17 | 388.17 | 24.41 | 28.50 | 24.55 |
Annual Sum or Average | 848.17 | 25.47 | 5400.00 | 24.66 | 546.83 | 24.84 |
Minimum of Months | 45.17 | 23.17 | 316.33 | 24.07 | 12.17 | 24.14 |
Maximum of Months | 127.83 | 26.98 | 514.00 | 24.98 | 81.50 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 190.33 | 22.85 | 219.33 | 23.60 | 2.33 | 23.62 |
February | 89.67 | 23.11 | 321.33 | 24.04 | 5.17 | 24.08 |
March | 50.33 | 24.06 | 412.17 | 24.35 | 11.33 | 24.42 |
April | 43.83 | 26.64 | 465.67 | 24.74 | 42.50 | 24.90 |
May | 73.17 | 26.97 | 507.50 | 24.91 | 73.17 | 25.14 |
June | 86.33 | 26.89 | 496.00 | 24.91 | 86.33 | 25.16 |
July | 115.33 | 26.95 | 497.00 | 25.14 | 115.33 | 25.42 |
August | 97.17 | 26.93 | 514.00 | 24.95 | 97.17 | 25.22 |
September | 90.83 | 26.92 | 485.00 | 25.00 | 90.83 | 25.26 |
October | 64.00 | 26.89 | 500.00 | 24.90 | 64.00 | 25.10 |
November | 31.17 | 26.59 | 473.33 | 24.62 | 28.67 | 24.75 |
December | 99.00 | 23.22 | 336.50 | 24.07 | 7.67 | 24.10 |
Annual Sum or Average | 1031.17 | 25.32 | 5227.83 | 24.66 | 624.50 | 24.87 |
Minimum of Months | 31.17 | 22.85 | 219.33 | 23.60 | 2.33 | 23.62 |
Maximum of Months | 190.33 | 26.97 | 514.00 | 25.14 | 115.33 | 25.42 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.50 | 27.00 | 454.00 | 27.00 | 0.50 | 27.00 |
March | 22.33 | 27.00 | 514.00 | 27.00 | 22.33 | 27.00 |
April | 229.83 | 27.09 | 485.00 | 27.06 | 229.83 | 27.07 |
May | 74.67 | 27.00 | 508.00 | 27.00 | 74.67 | 27.00 |
June | 266.00 | 27.00 | 496.00 | 27.00 | 266.00 | 27.00 |
July | 463.83 | 27.00 | 497.00 | 27.00 | 463.83 | 27.00 |
August | 514.00 | 28.15 | 514.00 | 28.15 | 514.00 | 28.15 |
September | 197.33 | 27.00 | 485.00 | 27.00 | 197.33 | 27.00 |
October | 155.33 | 27.00 | 502.00 | 27.00 | 155.33 | 27.00 |
November | 111.33 | 27.00 | 489.00 | 27.00 | 111.33 | 27.00 |
December | 75.67 | 27.00 | 497.00 | 27.00 | 75.67 | 27.00 |
Annual Sum or Average | 2110.83 | 27.29 | 5943.00 | 27.15 | 2110.83 | 27.18 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 28.15 | 514.00 | 28.15 | 514.00 | 28.15 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 19.67 | 27.64 | 485.00 | 27.06 | 19.67 | 27.08 |
May | 2.50 | 27.00 | 508.00 | 27.00 | 2.50 | 27.00 |
June | 9.50 | 27.00 | 496.00 | 27.00 | 9.50 | 27.00 |
July | 32.17 | 27.00 | 497.00 | 27.00 | 32.17 | 27.00 |
August | 400.33 | 28.24 | 514.00 | 28.10 | 400.33 | 28.14 |
September | 13.17 | 27.00 | 485.00 | 27.00 | 13.17 | 27.00 |
October | 1.17 | 27.00 | 502.00 | 27.00 | 1.17 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 478.50 | 28.06 | 5943.00 | 27.16 | 478.50 | 27.22 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 400.33 | 28.24 | 514.00 | 28.10 | 400.33 | 28.14 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 1.83 | 27.00 | 514.00 | 27.00 | 1.83 | 27.00 |
April | 40.00 | 27.38 | 485.00 | 27.06 | 40.00 | 27.08 |
May | 24.83 | 27.00 | 508.00 | 27.00 | 24.83 | 27.00 |
June | 50.83 | 27.00 | 496.00 | 27.00 | 50.83 | 27.00 |
July | 139.00 | 27.00 | 497.00 | 27.00 | 139.00 | 27.00 |
August | 399.83 | 28.28 | 514.00 | 28.13 | 399.83 | 28.17 |
September | 50.33 | 27.00 | 485.00 | 27.00 | 50.33 | 27.00 |
October | 19.67 | 27.00 | 502.00 | 27.00 | 19.67 | 27.00 |
November | 6.00 | 27.00 | 489.00 | 27.00 | 6.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 732.33 | 27.72 | 5943.00 | 27.16 | 732.33 | 27.22 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 399.83 | 28.28 | 514.00 | 28.13 | 399.83 | 28.17 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.20 | 514.00 | 27.20 | 514.00 | 27.20 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.02 | 5943.00 | 27.02 | 5943.00 | 27.02 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.20 | 514.00 | 27.20 | 514.00 | 27.20 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00098 | 31.53003 | 0.89519 | 21.94924 |
February | 454.00000 | 27.00161 | 31.09232 | 0.93709 | 23.57286 |
March | 514.00000 | 27.00089 | 30.91641 | 0.97648 | 25.16314 |
April | 485.00000 | 27.04389 | 31.73587 | 1.03757 | 27.78187 |
May | 508.00000 | 27.00068 | 36.42906 | 0.35892 | 7.74561 |
June | 496.00000 | 27.00247 | 36.64807 | 0.41641 | 8.66116 |
July | 497.00000 | 27.00111 | 36.37990 | 0.47490 | 9.76272 |
August | 514.00000 | 28.14656 | 35.19856 | 0.79066 | 18.92559 |
September | 485.00000 | 27.00022 | 39.99635 | 0.40487 | 8.47474 |
October | 502.00000 | 27.00230 | 34.75294 | 1.02449 | 27.19240 |
November | 489.00000 | 27.00121 | 32.30194 | 1.00810 | 26.48709 |
December | 497.00000 | 27.00040 | 30.39151 | 0.99513 | 25.93745 |
Annual Sum or Average | 5943.00000 | 27.10373 | 33.96056 | 0.77561 | 19.27362 |
Minimum of Months | 454.00000 | 27.00022 | 30.39151 | 0.35892 | 7.74561 |
Maximum of Months | 514.00000 | 28.14656 | 39.99635 | 1.03757 | 27.78187 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00048 | 31.92316 | 0.83803 | 19.86071 |
February | 454.00000 | 27.00151 | 31.24093 | 0.86440 | 20.80438 |
March | 514.00000 | 27.00087 | 30.96068 | 0.89765 | 22.04627 |
April | 485.00000 | 27.03134 | 31.77662 | 0.94645 | 23.96603 |
May | 508.00000 | 27.00047 | 36.79227 | 0.28148 | 6.69723 |
June | 496.00000 | 27.00258 | 36.89268 | 0.31372 | 7.08600 |
July | 497.00000 | 27.00137 | 36.55979 | 0.34677 | 7.54241 |
August | 514.00000 | 27.99184 | 35.39863 | 0.60495 | 13.45643 |
September | 485.00000 | 27.00009 | 40.68252 | 0.31839 | 7.15343 |
October | 502.00000 | 27.00228 | 34.98470 | 0.94734 | 23.98102 |
November | 489.00000 | 27.00123 | 32.38439 | 0.92470 | 23.08646 |
December | 497.00000 | 27.00042 | 30.42623 | 0.88819 | 21.68876 |
Annual Sum or Average | 5943.00000 | 27.08928 | 34.18135 | 0.67963 | 16.41075 |
Minimum of Months | 454.00000 | 27.00009 | 30.42623 | 0.28148 | 6.69723 |
Maximum of Months | 514.00000 | 27.99184 | 40.68252 | 0.94734 | 23.98102 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00041 | 32.16743 | 0.81716 | 19.17287 |
February | 454.00000 | 27.00153 | 31.28404 | 0.85212 | 20.39511 |
March | 514.00000 | 27.00089 | 30.96095 | 0.89408 | 21.94156 |
April | 485.00000 | 27.03427 | 31.76668 | 0.95219 | 24.22978 |
May | 508.00000 | 27.00055 | 36.71009 | 0.30243 | 6.99942 |
June | 496.00000 | 27.00259 | 36.83440 | 0.33708 | 7.44742 |
July | 497.00000 | 27.00134 | 36.51600 | 0.37621 | 8.03280 |
August | 514.00000 | 28.01241 | 35.35378 | 0.63525 | 14.53290 |
September | 485.00000 | 27.00014 | 40.55256 | 0.33774 | 7.46378 |
October | 502.00000 | 27.00231 | 34.96601 | 0.95476 | 24.29813 |
November | 489.00000 | 27.00125 | 32.38693 | 0.92221 | 23.01048 |
December | 497.00000 | 27.00045 | 30.43539 | 0.87240 | 21.13485 |
Annual Sum or Average | 5943.00000 | 27.09131 | 34.17385 | 0.68659 | 16.52350 |
Minimum of Months | 454.00000 | 27.00014 | 30.43539 | 0.30243 | 6.99942 |
Maximum of Months | 514.00000 | 28.01241 | 40.55256 | 0.95476 | 24.29813 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00361 | 30.87398 | 1.11732 | 31.31782 |
February | 454.00000 | 27.00393 | 30.98348 | 1.26278 | 38.37581 |
March | 514.00000 | 27.00243 | 31.33083 | 1.39820 | 45.41879 |
April | 485.00000 | 27.00752 | 32.11218 | 1.54036 | 53.09700 |
May | 508.00000 | 27.00319 | 34.69895 | 0.60996 | 12.83839 |
June | 496.00000 | 27.00358 | 35.34041 | 0.83404 | 19.68874 |
July | 497.00000 | 27.00213 | 35.62600 | 1.05250 | 28.39404 |
August | 514.00000 | 27.19605 | 35.33839 | 1.31425 | 41.08227 |
September | 485.00000 | 27.00369 | 36.66408 | 0.69348 | 15.14498 |
October | 502.00000 | 27.00326 | 33.80114 | 1.35557 | 43.16418 |
November | 489.00000 | 27.00192 | 32.17397 | 1.45412 | 48.41738 |
December | 497.00000 | 27.00270 | 30.91645 | 1.54838 | 53.53314 |
Annual Sum or Average | 5943.00000 | 27.02009 | 33.33644 | 1.18115 | 35.84939 |
Minimum of Months | 454.00000 | 27.00192 | 30.87398 | 0.60996 | 12.83839 |
Maximum of Months | 514.00000 | 27.19605 | 36.66408 | 1.54838 | 53.53314 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.77474 | 48.50119 | 0.62937 | 14.59987 |
February | 454.00000 | 25.27902 | 56.66695 | 0.80824 | 21.80818 |
March | 514.00000 | 25.74556 | 62.03857 | 0.95635 | 28.32224 |
April | 485.00000 | 27.39006 | 73.27488 | 1.43269 | 49.17428 |
May | 508.00000 | 29.77884 | 97.44406 | 1.83158 | 69.46133 |
June | 496.00000 | 30.14689 | 97.49510 | 1.97250 | 75.37200 |
July | 497.00000 | 30.81631 | 99.99681 | 2.24003 | 86.06061 |
August | 514.00000 | 31.26269 | 99.99690 | 2.41538 | 91.31566 |
September | 485.00000 | 30.96683 | 99.99928 | 2.29990 | 88.03556 |
October | 502.00000 | 30.45698 | 91.16028 | 2.39307 | 86.68697 |
November | 489.00000 | 27.03308 | 66.88565 | 1.33058 | 44.33994 |
December | 497.00000 | 25.16810 | 55.79944 | 0.78638 | 20.63341 |
Annual Sum or Average | 5943.00000 | 28.25715 | 79.27949 | 1.59703 | 56.56530 |
Minimum of Months | 454.00000 | 24.77474 | 48.50119 | 0.62937 | 14.59987 |
Maximum of Months | 514.00000 | 31.26269 | 99.99928 | 2.41538 | 91.31566 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38065 | 49.85497 | 0.54833 | 11.63188 |
February | 454.00000 | 24.40313 | 53.20626 | 0.59329 | 12.75310 |
March | 514.00000 | 24.28915 | 50.92090 | 0.56835 | 12.00573 |
April | 485.00000 | 24.31969 | 52.18959 | 0.60935 | 13.07331 |
May | 508.00000 | 24.42689 | 52.40694 | -0.1581 | 6.36135 |
June | 496.00000 | 24.41096 | 53.46754 | -0.1356 | 6.23533 |
July | 497.00000 | 24.55090 | 51.73856 | -0.0814 | 6.34807 |
August | 514.00000 | 24.47467 | 51.32041 | -0.0861 | 6.30187 |
September | 485.00000 | 24.49765 | 53.03588 | -0.1045 | 6.34832 |
October | 502.00000 | 24.52570 | 51.99117 | 0.69477 | 15.74430 |
November | 489.00000 | 24.43165 | 54.66552 | 0.65067 | 14.24057 |
December | 497.00000 | 24.38581 | 53.52192 | 0.60177 | 12.89419 |
Annual Sum or Average | 5943.00000 | 24.42476 | 52.34012 | 0.30546 | 10.30013 |
Minimum of Months | 454.00000 | 24.28915 | 49.85497 | -0.1581 | 6.23533 |
Maximum of Months | 514.00000 | 24.55090 | 54.66552 | 0.69477 | 15.74430 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17906 | 50.89803 | 0.47385 | 9.90858 |
February | 454.00000 | 24.23863 | 54.13340 | 0.51865 | 10.83922 |
March | 514.00000 | 24.23683 | 51.68890 | 0.51387 | 10.72237 |
April | 485.00000 | 24.23135 | 53.57738 | 0.53545 | 11.18893 |
May | 508.00000 | 24.14321 | 54.85474 | -0.3424 | 7.57715 |
June | 496.00000 | 24.10298 | 57.07679 | -0.3350 | 7.39907 |
July | 497.00000 | 24.11571 | 56.75997 | -0.3290 | 7.31389 |
August | 514.00000 | 24.10230 | 57.25574 | -0.3232 | 7.22627 |
September | 485.00000 | 24.16165 | 57.22304 | -0.3176 | 7.21965 |
October | 502.00000 | 24.22824 | 55.58899 | 0.55689 | 11.63611 |
November | 489.00000 | 24.29864 | 56.41660 | 0.57152 | 12.02655 |
December | 497.00000 | 24.21937 | 54.78567 | 0.52110 | 10.88745 |
Annual Sum or Average | 5943.00000 | 24.18747 | 55.01784 | 0.16682 | 9.47945 |
Minimum of Months | 454.00000 | 24.10230 | 50.89803 | -0.3424 | 7.21965 |
Maximum of Months | 514.00000 | 24.29864 | 57.25574 | 0.57152 | 12.02655 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.88184 | 53.43876 | 0.40329 | 8.77299 |
February | 454.00000 | 24.07385 | 55.03615 | 0.47611 | 10.00236 |
March | 514.00000 | 24.18199 | 52.18928 | 0.50186 | 10.46651 |
April | 485.00000 | 24.25864 | 53.68519 | 0.54892 | 11.51050 |
May | 508.00000 | 24.22965 | 54.66129 | -0.2916 | 7.08615 |
June | 496.00000 | 24.18111 | 56.87239 | -0.2833 | 6.88560 |
July | 497.00000 | 24.24587 | 56.32472 | -0.2558 | 6.68741 |
August | 514.00000 | 24.19862 | 56.98033 | -0.2620 | 6.69298 |
September | 485.00000 | 24.24816 | 57.06995 | -0.2679 | 6.87101 |
October | 502.00000 | 24.27698 | 55.73911 | 0.57755 | 12.16819 |
November | 489.00000 | 24.27790 | 56.90529 | 0.56723 | 11.88671 |
December | 497.00000 | 24.02827 | 55.75599 | 0.47014 | 9.91092 |
Annual Sum or Average | 5943.00000 | 24.17387 | 55.38122 | 0.17893 | 9.06370 |
Minimum of Months | 454.00000 | 23.88184 | 52.18928 | -0.2916 | 6.68741 |
Maximum of Months | 514.00000 | 24.27790 | 57.06995 | 0.57755 | 12.16819 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.05432 | 50.29804 | 0.43472 | 9.29808 |
February | 454.00000 | 24.23109 | 53.13970 | 0.52543 | 11.09752 |
March | 514.00000 | 24.25677 | 50.39899 | 0.55135 | 11.63520 |
April | 485.00000 | 24.43582 | 51.30286 | 0.65301 | 14.51475 |
May | 508.00000 | 24.58473 | 51.29248 | -0.0220 | 6.67051 |
June | 496.00000 | 24.55568 | 52.45511 | 0.02088 | 6.63933 |
July | 497.00000 | 24.71892 | 50.75260 | 0.09668 | 7.39206 |
August | 514.00000 | 24.59136 | 50.54524 | 0.06800 | 6.94852 |
September | 485.00000 | 24.62380 | 52.19095 | 0.01527 | 6.88320 |
October | 502.00000 | 24.61298 | 51.22812 | 0.73932 | 17.33551 |
November | 489.00000 | 24.44918 | 54.04488 | 0.64984 | 14.31113 |
December | 497.00000 | 24.24377 | 53.55325 | 0.53642 | 11.28921 |
Annual Sum or Average | 5943.00000 | 24.44767 | 51.74384 | 0.35369 | 10.31513 |
Minimum of Months | 454.00000 | 24.05432 | 50.29804 | -0.0220 | 6.63933 |
Maximum of Months | 514.00000 | 24.71892 | 54.04488 | 0.73932 | 17.33551 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18030 | 49.69881 | 0.48203 | 10.34500 |
February | 454.00000 | 24.29533 | 52.77210 | 0.55840 | 11.99664 |
March | 514.00000 | 24.28068 | 50.21617 | 0.57444 | 12.32845 |
April | 485.00000 | 24.47197 | 51.06078 | 0.68869 | 15.68723 |
May | 508.00000 | 24.61809 | 51.04591 | 0.05422 | 6.99706 |
June | 496.00000 | 24.57059 | 52.30227 | 0.07589 | 6.89338 |
July | 497.00000 | 24.73549 | 50.62752 | 0.14879 | 7.89329 |
August | 514.00000 | 24.60247 | 50.41107 | 0.12246 | 7.25598 |
September | 485.00000 | 24.65531 | 51.95348 | 0.09117 | 7.32836 |
October | 502.00000 | 24.65243 | 50.89478 | 0.78633 | 18.96704 |
November | 489.00000 | 24.50303 | 53.75083 | 0.68396 | 15.43895 |
December | 497.00000 | 24.22607 | 53.56983 | 0.54058 | 11.45314 |
Annual Sum or Average | 5943.00000 | 24.48354 | 51.50334 | 0.39861 | 11.02617 |
Minimum of Months | 454.00000 | 24.18030 | 49.69881 | 0.05422 | 6.89338 |
Maximum of Months | 514.00000 | 24.73549 | 53.75083 | 0.78633 | 18.96704 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35219 | 48.85027 | 0.56090 | 12.42109 |
February | 454.00000 | 24.40208 | 52.21358 | 0.62035 | 13.74434 |
March | 514.00000 | 24.34176 | 49.92393 | 0.61055 | 13.30837 |
April | 485.00000 | 24.47084 | 51.13386 | 0.67820 | 15.32440 |
May | 508.00000 | 24.57421 | 51.34046 | -0.0333 | 6.62056 |
June | 496.00000 | 24.53865 | 52.54223 | -0.0084 | 6.52129 |
July | 497.00000 | 24.70775 | 50.79267 | 0.07761 | 7.22079 |
August | 514.00000 | 24.59207 | 50.52514 | 0.07649 | 6.96355 |
September | 485.00000 | 24.64850 | 52.03926 | 0.07183 | 7.17249 |
October | 502.00000 | 24.67922 | 50.82912 | 0.81456 | 19.98134 |
November | 489.00000 | 24.59554 | 53.26966 | 0.75855 | 17.94027 |
December | 497.00000 | 24.46156 | 52.45382 | 0.65126 | 14.66923 |
Annual Sum or Average | 5943.00000 | 24.53078 | 51.30710 | 0.40402 | 11.79314 |
Minimum of Months | 454.00000 | 24.34176 | 48.85027 | -0.0333 | 6.52129 |
Maximum of Months | 514.00000 | 24.70775 | 53.26966 | 0.81456 | 19.98134 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42416 | 48.65557 | 0.56991 | 12.37019 |
February | 454.00000 | 24.56269 | 51.58739 | 0.67500 | 15.28356 |
March | 514.00000 | 24.53340 | 49.15120 | 0.71128 | 16.38334 |
April | 485.00000 | 24.64849 | 50.35821 | 0.80749 | 19.71001 |
May | 508.00000 | 24.62825 | 51.10399 | 0.05533 | 7.07459 |
June | 496.00000 | 24.58950 | 52.26470 | 0.11292 | 7.24463 |
July | 497.00000 | 24.75810 | 50.53371 | 0.20525 | 8.47989 |
August | 514.00000 | 24.63845 | 50.27822 | 0.21043 | 8.21709 |
September | 485.00000 | 24.65646 | 52.02032 | 0.08549 | 7.34909 |
October | 502.00000 | 24.68811 | 50.88333 | 0.81270 | 19.92771 |
November | 489.00000 | 24.68071 | 53.01463 | 0.79032 | 19.02603 |
December | 497.00000 | 24.66657 | 51.66061 | 0.73603 | 17.29237 |
Annual Sum or Average | 5943.00000 | 24.62284 | 50.94201 | 0.47885 | 13.16176 |
Minimum of Months | 454.00000 | 24.42416 | 48.65557 | 0.05533 | 7.07459 |
Maximum of Months | 514.00000 | 24.75810 | 53.01463 | 0.81270 | 19.92771 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.48601 | 52.10482 | 0.28045 | 7.33821 |
February | 454.00000 | 23.82869 | 54.76670 | 0.40233 | 8.90576 |
March | 514.00000 | 24.10348 | 51.26106 | 0.47887 | 10.17403 |
April | 485.00000 | 24.39235 | 52.57309 | 0.60020 | 13.06190 |
May | 508.00000 | 24.52708 | 52.71354 | -0.1051 | 6.63246 |
June | 496.00000 | 24.49611 | 55.10792 | -0.0620 | 6.43718 |
July | 497.00000 | 24.64827 | 54.44656 | 0.00449 | 6.80455 |
August | 514.00000 | 24.50739 | 55.31488 | -0.0329 | 6.44492 |
September | 485.00000 | 24.54665 | 55.57897 | -0.0778 | 6.65295 |
October | 502.00000 | 24.51700 | 54.24432 | 0.66679 | 14.95610 |
November | 489.00000 | 24.31810 | 55.71958 | 0.57938 | 12.31662 |
December | 497.00000 | 23.80991 | 55.70039 | 0.40243 | 8.92319 |
Annual Sum or Average | 5943.00000 | 24.26758 | 54.11190 | 0.25948 | 9.04265 |
Minimum of Months | 454.00000 | 23.48601 | 51.26106 | -0.1051 | 6.43718 |
Maximum of Months | 514.00000 | 24.64827 | 55.71958 | 0.66679 | 14.95610 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.87231 | 50.19376 | 0.38168 | 8.78867 |
February | 385.00000 | 24.14009 | 53.26759 | 0.48992 | 10.69875 |
March | 433.00000 | 24.30401 | 50.16002 | 0.54421 | 11.83376 |
April | 410.00000 | 24.61232 | 51.79315 | 0.68509 | 15.80110 |
May | 430.00000 | 24.69480 | 52.18769 | 0.00582 | 7.09154 |
June | 418.00000 | 24.63287 | 54.69383 | 0.02666 | 6.90315 |
July | 422.00000 | 24.81309 | 53.78974 | 0.10201 | 7.74418 |
August | 433.00000 | 24.64842 | 54.78685 | 0.06494 | 7.04965 |
September | 410.00000 | 24.72138 | 54.89477 | 0.03201 | 7.27927 |
October | 427.00000 | 24.72837 | 53.38708 | 0.74925 | 17.80186 |
November | 417.00000 | 24.58175 | 54.50725 | 0.66278 | 14.90413 |
December | 422.00000 | 24.08584 | 54.30891 | 0.47798 | 10.38598 |
Annual Sum or Average | 5034.00000 | 24.48766 | 53.15275 | 0.35043 | 10.51122 |
Minimum of Months | 385.00000 | 23.87231 | 50.16002 | 0.00582 | 6.90315 |
Maximum of Months | 433.00000 | 24.81309 | 54.89477 | 0.74925 | 17.80186 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21120 | 49.08802 | 0.51121 | 11.54557 |
February | 454.00000 | 24.26956 | 52.67358 | 0.56710 | 12.59530 |
March | 514.00000 | 24.29642 | 50.26552 | 0.57059 | 12.43957 |
April | 485.00000 | 24.46331 | 52.18139 | 0.64011 | 14.27638 |
May | 508.00000 | 24.52300 | 52.72342 | -0.1057 | 6.63421 |
June | 496.00000 | 24.47575 | 55.22627 | -0.0836 | 6.42029 |
July | 497.00000 | 24.63915 | 54.48218 | -0.0033 | 6.77057 |
August | 514.00000 | 24.52191 | 55.19383 | -0.0069 | 6.52277 |
September | 485.00000 | 24.60720 | 55.14354 | 0.00570 | 6.91071 |
October | 502.00000 | 24.66475 | 53.34220 | 0.77535 | 18.64787 |
November | 489.00000 | 24.59612 | 54.28430 | 0.73135 | 17.12900 |
December | 497.00000 | 24.35623 | 53.12555 | 0.60020 | 13.55720 |
Annual Sum or Average | 5943.00000 | 24.46942 | 53.13718 | 0.34754 | 11.09396 |
Minimum of Months | 454.00000 | 24.21120 | 49.08802 | -0.1057 | 6.42029 |
Maximum of Months | 514.00000 | 24.66475 | 55.22627 | 0.77535 | 18.64787 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91016 | 50.41431 | 0.40118 | 9.14080 |
February | 454.00000 | 24.15298 | 53.30569 | 0.51107 | 11.08845 |
March | 514.00000 | 24.32006 | 50.22878 | 0.57567 | 12.52977 |
April | 485.00000 | 24.55133 | 51.79296 | 0.68991 | 15.87391 |
May | 508.00000 | 24.60351 | 52.34030 | -0.0074 | 6.97889 |
June | 496.00000 | 24.55656 | 54.73810 | 0.03009 | 6.85131 |
July | 497.00000 | 24.70594 | 54.09555 | 0.09791 | 7.50399 |
August | 514.00000 | 24.56641 | 54.90856 | 0.07678 | 7.04080 |
September | 485.00000 | 24.63226 | 55.03246 | 0.02918 | 7.14428 |
October | 502.00000 | 24.64336 | 53.60258 | 0.74824 | 17.71693 |
November | 489.00000 | 24.50585 | 54.80505 | 0.66878 | 15.02131 |
December | 497.00000 | 24.17718 | 54.04550 | 0.51878 | 11.26031 |
Annual Sum or Average | 5943.00000 | 24.44522 | 53.26484 | 0.35972 | 10.66038 |
Minimum of Months | 454.00000 | 23.91016 | 50.22878 | -0.0074 | 6.85131 |
Maximum of Months | 514.00000 | 24.70594 | 55.03246 | 0.74824 | 17.71693 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.15316 | 53.26977 | 0.19783 | 7.09884 |
February | 454.00000 | 23.62302 | 55.59406 | 0.35253 | 8.53342 |
March | 514.00000 | 24.01061 | 51.79088 | 0.45873 | 10.00426 |
April | 485.00000 | 24.37472 | 52.86711 | 0.60295 | 13.25477 |
May | 508.00000 | 24.54143 | 52.87533 | -0.0813 | 6.76563 |
June | 496.00000 | 24.50980 | 55.30449 | -0.0361 | 6.58356 |
July | 497.00000 | 24.66455 | 54.61382 | 0.03657 | 7.11387 |
August | 514.00000 | 24.52185 | 55.53997 | -0.0035 | 6.64614 |
September | 485.00000 | 24.55967 | 55.86407 | -0.0542 | 6.82277 |
October | 502.00000 | 24.52359 | 54.63909 | 0.67755 | 15.34235 |
November | 489.00000 | 24.28115 | 56.25070 | 0.57178 | 12.24428 |
December | 497.00000 | 23.59041 | 56.64495 | 0.34793 | 8.48551 |
Annual Sum or Average | 5943.00000 | 24.19949 | 54.58632 | 0.25426 | 9.06584 |
Minimum of Months | 454.00000 | 23.15316 | 51.79088 | -0.0813 | 6.58356 |
Maximum of Months | 514.00000 | 24.66455 | 56.64495 | 0.67755 | 15.34235 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63604 | 51.42854 | 0.32696 | 8.36051 |
February | 454.00000 | 23.95718 | 54.09738 | 0.45335 | 10.15752 |
March | 514.00000 | 24.18214 | 50.91082 | 0.52950 | 11.57642 |
April | 485.00000 | 24.49949 | 52.06604 | 0.67767 | 15.55158 |
May | 508.00000 | 24.59337 | 52.46562 | 0.01000 | 7.00407 |
June | 496.00000 | 24.54056 | 54.98979 | 0.03620 | 6.82018 |
July | 497.00000 | 24.70053 | 54.33565 | 0.11080 | 7.71840 |
August | 514.00000 | 24.55364 | 55.21304 | 0.07795 | 7.00336 |
September | 485.00000 | 24.61588 | 55.37625 | 0.03544 | 7.18610 |
October | 502.00000 | 24.61751 | 53.91462 | 0.74474 | 17.59758 |
November | 489.00000 | 24.45963 | 55.32667 | 0.64761 | 14.44088 |
December | 497.00000 | 23.90430 | 55.28841 | 0.43833 | 9.81658 |
Annual Sum or Average | 5943.00000 | 24.35704 | 53.77167 | 0.33898 | 10.25368 |
Minimum of Months | 454.00000 | 23.63604 | 50.91082 | 0.01000 | 6.82018 |
Maximum of Months | 514.00000 | 24.70053 | 55.37625 | 0.74474 | 17.59758 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99474 | 49.90453 | 0.45059 | 10.82572 |
February | 454.00000 | 24.12778 | 53.30785 | 0.52900 | 12.05754 |
March | 514.00000 | 24.22100 | 50.75271 | 0.55334 | 12.22582 |
April | 485.00000 | 24.44286 | 52.48396 | 0.64186 | 14.43562 |
May | 508.00000 | 24.53867 | 52.88484 | -0.0816 | 6.77935 |
June | 496.00000 | 24.49322 | 55.41071 | -0.0562 | 6.55813 |
July | 497.00000 | 24.65741 | 54.64439 | 0.02949 | 7.07945 |
August | 514.00000 | 24.53463 | 55.42827 | 0.02151 | 6.75698 |
September | 485.00000 | 24.61396 | 55.45049 | 0.02652 | 7.16286 |
October | 502.00000 | 24.66190 | 53.76296 | 0.78299 | 18.96804 |
November | 489.00000 | 24.56077 | 54.74613 | 0.72306 | 16.93165 |
December | 497.00000 | 24.22482 | 53.77622 | 0.56189 | 12.89828 |
Annual Sum or Average | 5943.00000 | 24.42395 | 53.53747 | 0.34616 | 11.03285 |
Minimum of Months | 454.00000 | 23.99474 | 49.90453 | -0.0816 | 6.55813 |
Maximum of Months | 514.00000 | 24.66190 | 55.45049 | 0.78299 | 18.96804 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65556 | 51.33957 | 0.33621 | 8.68146 |
February | 454.00000 | 24.00294 | 53.96123 | 0.47314 | 10.64995 |
March | 514.00000 | 24.25324 | 50.68793 | 0.56059 | 12.33352 |
April | 485.00000 | 24.53291 | 52.07458 | 0.69145 | 16.00190 |
May | 508.00000 | 24.60969 | 52.53653 | 0.01184 | 7.18532 |
June | 496.00000 | 24.56299 | 54.96306 | 0.05180 | 7.07136 |
July | 497.00000 | 24.71381 | 54.29035 | 0.12458 | 7.87508 |
August | 514.00000 | 24.57271 | 55.16019 | 0.10101 | 7.32923 |
September | 485.00000 | 24.63553 | 55.34636 | 0.04785 | 7.38179 |
October | 502.00000 | 24.63926 | 54.01644 | 0.75564 | 18.01036 |
November | 489.00000 | 24.46973 | 55.29610 | 0.66133 | 14.87229 |
December | 497.00000 | 24.02205 | 54.78178 | 0.47797 | 10.71260 |
Annual Sum or Average | 5943.00000 | 24.39121 | 53.69192 | 0.35607 | 10.65965 |
Minimum of Months | 454.00000 | 23.65556 | 50.68793 | 0.01184 | 7.07136 |
Maximum of Months | 514.00000 | 24.71381 | 55.34636 | 0.75564 | 18.01036 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.721813E+11 | 171485.95 | 30-JAN-14:00 | 454.07 | 0.710632E+12 | 0.00 | 0.782814E+12 | 6.26 | 10.67 | 01-JAN-08:00 | 0.00 | 0.00 |
February | 0.889463E+11 | 212878.84 | 08-FEB-12:05 | 427.79 | 0.828510E+12 | 0.00 | 0.917456E+12 | 6.34 | 10.65 | 15-FEB-05:55 | 0.00 | 0.00 |
March | 0.131158E+12 | 221792.49 | 29-MAR-11:10 | 574.86 | 0.117684E+13 | 0.00 | 0.130799E+13 | 7.56 | 10.65 | 07-MAR-06:00 | 0.00 | 0.00 |
April | 0.168120E+12 | 222811.42 | 25-APR-10:00 | 652.78 | 0.145241E+13 | 0.00 | 0.162053E+13 | 8.63 | 10.64 | 26-APR-02:35 | 0.00 | 0.00 |
May | 0.228624E+12 | 236683.49 | 30-MAY-04:03 | 698.75 | 0.192166E+13 | 0.00 | 0.215028E+13 | 8.44 | 10.61 | 15-MAY-04:20 | 0.00 | 0.00 |
June | 0.264979E+12 | 246516.38 | 24-JUN-17:07 | 679.79 | 0.212914E+13 | 0.00 | 0.239412E+13 | 7.93 | 10.61 | 02-JUN-01:47 | 0.00 | 0.00 |
July | 0.313389E+12 | 244028.97 | 22-JUL-17:10 | 690.29 | 0.238301E+13 | 0.00 | 0.269639E+13 | 7.38 | 10.61 | 04-JUL-02:55 | 0.00 | 0.00 |
August | 0.333456E+12 | 247613.46 | 19-AUG-17:09 | 710.41 | 0.250038E+13 | 0.00 | 0.283384E+13 | 7.47 | 10.39 | 15-AUG-22:00 | 0.00 | 0.00 |
September | 0.276305E+12 | 246498.13 | 02-SEP-17:10 | 688.12 | 0.217114E+13 | 0.00 | 0.244744E+13 | 7.89 | 10.61 | 26-SEP-04:25 | 0.00 | 0.00 |
October | 0.225753E+12 | 236949.21 | 07-OCT-17:10 | 692.47 | 0.186261E+13 | 0.00 | 0.208836E+13 | 8.27 | 10.61 | 21-OCT-03:00 | 0.00 | 0.00 |
November | 0.155729E+12 | 219776.97 | 24-NOV-10:10 | 610.13 | 0.134363E+13 | 0.00 | 0.149936E+13 | 8.05 | 10.62 | 26-NOV-05:25 | 0.00 | 0.00 |
December | 0.104100E+12 | 208595.88 | 05-DEC-11:10 | 550.76 | 0.964201E+12 | 0.00 | 0.106830E+13 | 7.40 | 10.66 | 30-DEC-07:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.236274E+13 | 7430.22 | 0.194442E+14 | 0.00 | 0.218069E+14 | 7.64 | 0.00 | 0.00 | ||||
Minimum of Months | 0.721813E+11 | 171485.95 | 427.79 | 0.710632E+12 | 0.00 | 0.782814E+12 | 6.26 | 10.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.333456E+12 | 247613.46 | 710.41 | 0.250038E+13 | 0.00 | 0.283384E+13 | 8.63 | 10.67 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.203887E+10 | 121128.47 | 08-FEB-15:05 | 6.94 | 0.189009E+11 | 0.00 | 0.209398E+11 | 0.10 | 11.02 | 07-FEB-12:10 | 0.00 | 0.00 |
March | 0.903574E+10 | 121800.65 | 28-MAR-12:05 | 31.68 | 0.841388E+11 | 0.00 | 0.931745E+11 | 0.40 | 11.28 | 22-MAR-15:00 | 0.00 | 0.00 |
April | 0.221926E+11 | 147501.79 | 27-APR-10:05 | 73.94 | 0.204658E+12 | 0.00 | 0.226851E+12 | 0.95 | 11.29 | 28-APR-08:70 | 0.00 | 0.00 |
May | 0.721396E+11 | 218339.88 | 30-MAY-05:03 | 207.54 | 0.622895E+12 | 0.00 | 0.695035E+12 | 2.45 | 11.27 | 11-MAY-07:30 | 0.00 | 0.00 |
June | 0.131537E+12 | 240682.74 | 09-JUN-05:03 | 331.15 | 0.107245E+13 | 0.00 | 0.120399E+13 | 3.82 | 10.96 | 21-JUN-09:10 | 0.00 | 0.00 |
July | 0.185359E+12 | 242740.44 | 12-JUL-05:03 | 392.98 | 0.140591E+13 | 0.00 | 0.159127E+13 | 4.13 | 11.21 | 03-JUL-07:20 | 0.00 | 0.00 |
August | 0.215169E+12 | 241944.75 | 01-AUG-03:02 | 431.95 | 0.159922E+13 | 0.00 | 0.181439E+13 | 4.44 | 10.80 | 15-AUG-18:50 | 0.00 | 0.00 |
September | 0.139904E+12 | 241788.65 | 11-SEP-05:03 | 331.89 | 0.110900E+13 | 0.00 | 0.124891E+13 | 3.74 | 11.10 | 30-SEP-05:04 | 0.00 | 0.00 |
October | 0.745329E+11 | 231882.35 | 10-OCT-05:02 | 208.38 | 0.637327E+12 | 0.00 | 0.711860E+12 | 2.43 | 11.20 | 20-OCT-12:10 | 0.00 | 0.00 |
November | 0.335289E+11 | 173424.49 | 10-NOV-06:04 | 104.45 | 0.299779E+12 | 0.00 | 0.333308E+12 | 1.31 | 11.29 | 25-NOV-06:04 | 0.00 | 0.00 |
December | 0.368599E+10 | 134975.63 | 04-DEC-13:05 | 12.50 | 0.338156E+11 | 0.00 | 0.375016E+11 | 0.16 | 11.01 | 08-DEC-14:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.889124E+12 | 2133.41 | 0.708810E+13 | 0.00 | 0.797723E+13 | 2.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.215169E+12 | 242740.44 | 431.95 | 0.159922E+13 | 0.00 | 0.181439E+13 | 4.44 | 11.29 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.913772E+11 | 744.00 | 43776.24 | 01-JAN-09:45 | 278498.30 | 19-JAN-05:17 | 24.58 | 21.13 | 16.45 |
February | 0.986212E+11 | 672.00 | 43776.24 | 01-FEB-00:10 | 399726.11 | 07-FEB-14:05 | 29.11 | 23.07 | 16.45 |
March | 0.116768E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 643733.47 | 31-MAR-23:25 | 34.85 | 26.20 | 16.45 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 742484.24 | 28-APR-12:40 | 41.99 | 30.58 | 16.45 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:05 | 392455.70 | 31-MAY-23:13 | 36.91 | 32.82 | 16.45 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 549650.10 | 30-JUN-24:00 | 42.40 | 35.46 | 16.45 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 719350.25 | 31-JUL-23:23 | 48.43 | 38.64 | 16.45 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:03 | 780372.97 | 04-AUG-13:05 | 52.22 | 39.83 | 16.45 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 399241.54 | 30-SEP-23:15 | 38.39 | 34.04 | 16.45 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 520787.35 | 31-OCT-23:23 | 38.65 | 31.93 | 16.45 |
November | 0.113468E+12 | 720.00 | 43776.24 | 01-NOV-00:05 | 572420.71 | 01-NOV-14:05 | 37.63 | 28.71 | 16.45 |
December | 0.116859E+12 | 744.00 | 43776.24 | 01-DEC-00:05 | 686896.41 | 03-DEC-13:12 | 36.10 | 25.06 | 16.45 |
Annual Sum or Average | 0.134650E+13 | 8760.00 | 38.50 | 30.67 | 16.45 | ||||
Minimum of Months | 0.913772E+11 | 672.00 | 43776.24 | 278498.30 | 24.58 | 21.13 | 16.45 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 780372.97 | 52.22 | 39.83 | 16.45 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.317819E+10 | 392.53 | 21577.38 | 09-JAN-13:05 | 1381710.06 | 24-JAN-13:40 | 22.38 | 21.39 | 43.09 |
February | 0.704218E+10 | 388.58 | 21577.38 | 01-FEB-16:10 | 1587967.41 | 08-FEB-11:20 | 22.78 | 21.51 | 45.57 |
March | 0.125755E+11 | 499.83 | 21577.38 | 01-MAR-06:04 | 1672758.16 | 13-MAR-13:00 | 23.08 | 21.46 | 53.45 |
April | 0.274743E+11 | 596.29 | 21577.38 | 03-APR-05:04 | 1635131.59 | 24-APR-09:30 | 24.13 | 22.05 | 62.34 |
May | 0.458475E+11 | 693.62 | 21577.38 | 01-MAY-00:05 | 1624542.41 | 08-MAY-07:50 | 26.63 | 23.99 | 62.63 |
June | 0.516458E+11 | 679.71 | 21577.38 | 01-JUN-00:10 | 1636172.23 | 02-JUN-07:40 | 29.46 | 26.42 | 58.12 |
July | 0.525184E+11 | 690.29 | 21577.38 | 01-JUL-00:05 | 1674098.62 | 19-JUL-15:00 | 30.88 | 27.58 | 56.76 |
August | 0.551840E+11 | 710.41 | 21577.38 | 01-AUG-00:03 | 1703358.72 | 10-AUG-16:00 | 31.38 | 27.90 | 58.38 |
September | 0.532017E+11 | 688.12 | 21577.38 | 01-SEP-00:05 | 1585339.51 | 07-SEP-14:05 | 30.07 | 26.97 | 57.82 |
October | 0.475461E+11 | 683.34 | 21577.38 | 01-OCT-00:05 | 1653439.84 | 20-OCT-10:00 | 27.02 | 24.44 | 60.10 |
November | 0.268063E+11 | 542.26 | 21577.38 | 01-NOV-03:02 | 1638970.73 | 21-NOV-11:50 | 24.14 | 22.23 | 57.93 |
December | 0.109820E+11 | 463.20 | 21577.38 | 01-DEC-12:50 | 1533590.56 | 01-DEC-14:00 | 22.76 | 21.43 | 51.42 |
Annual Sum or Average | 0.394002E+12 | 7028.18 | 26.25 | 23.96 | 55.68 | ||||
Minimum of Months | 0.317819E+10 | 388.58 | 21577.38 | 1381710.06 | 22.38 | 21.39 | 43.09 | ||
Maximum of Months | 0.551840E+11 | 710.41 | 21577.38 | 1703358.72 | 31.38 | 27.90 | 62.63 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 51785713.54 | 0.67 | 21577.38 | 30-JAN-14:00 | 719508.26 | 30-JAN-14:50 | 22.38 | 22.37 | 0.03 |
February | 0.664355E+09 | 8.91 | 21577.38 | 06-FEB-06:06 | 1382366.99 | 06-FEB-15:05 | 22.78 | 22.73 | 0.80 |
March | 0.262182E+10 | 34.82 | 21577.38 | 01-MAR-13:05 | 1469339.54 | 23-MAR-15:00 | 23.08 | 22.92 | 2.99 |
April | 0.849670E+10 | 111.39 | 21577.38 | 03-APR-07:10 | 1396677.74 | 25-APR-14:05 | 24.13 | 23.57 | 9.06 |
May | 0.257979E+11 | 332.25 | 21577.38 | 01-MAY-07:10 | 1418040.70 | 29-MAY-14:42 | 26.63 | 25.09 | 26.43 |
June | 0.428984E+11 | 552.40 | 21577.38 | 01-JUN-05:07 | 1591705.06 | 12-JUN-05:03 | 29.46 | 26.81 | 45.09 |
July | 0.487759E+11 | 627.92 | 21577.38 | 01-JUL-00:05 | 1674098.62 | 19-JUL-15:00 | 30.88 | 27.76 | 50.59 |
August | 0.524674E+11 | 675.44 | 21577.38 | 01-AUG-00:03 | 1703358.72 | 10-AUG-16:00 | 31.38 | 28.00 | 54.92 |
September | 0.449622E+11 | 578.82 | 21577.38 | 01-SEP-00:05 | 1585339.51 | 07-SEP-14:05 | 30.07 | 27.26 | 46.65 |
October | 0.287303E+11 | 371.40 | 21577.38 | 01-OCT-00:05 | 1420513.46 | 10-OCT-05:03 | 27.02 | 25.28 | 28.55 |
November | 0.111873E+11 | 145.10 | 21577.38 | 01-NOV-07:10 | 1247173.38 | 13-NOV-14:00 | 24.14 | 23.44 | 12.61 |
December | 0.151473E+10 | 19.50 | 21577.38 | 04-DEC-09:10 | 1115788.86 | 04-DEC-14:05 | 22.76 | 22.67 | 1.58 |
Annual Sum or Average | 0.268169E+12 | 3458.62 | 26.25 | 24.84 | 23.40 | ||||
Minimum of Months | 51785713.54 | 0.67 | 21577.38 | 719508.26 | 22.38 | 22.37 | 0.03 | ||
Maximum of Months | 0.524674E+11 | 675.44 | 21577.38 | 1703358.72 | 31.38 | 28.00 | 54.92 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 24.58 | 24.58 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 29.11 | 29.11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 34.85 | 34.85 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 41.99 | 41.99 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 36.91 | 36.91 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 42.40 | 42.40 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 48.43 | 48.43 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 52.22 | 52.22 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 38.39 | 38.39 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 38.65 | 38.65 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 37.63 | 37.63 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 36.10 | 36.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 38.50 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 24.58 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | 52.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.717690E+11 | 0.00 | 431.69 | 0.688605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230239.10 | 30-JAN-05:12 | 161009.77 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.889395E+11 | 0.00 | 411.67 | 0.827802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249873.37 | 09-FEB-05:11 | 171027.21 | 08-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.135242E+12 | 0.00 | 557.58 | 0.126787E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223715.58 | 29-MAR-04:12 | 178201.42 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.184042E+12 | 0.00 | 621.98 | 0.163733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241308.61 | 18-APR-03:12 | 181593.70 | 29-APR-03:12 | 0.00 | 0.00 | 0.00 |
May | 0.266090E+12 | 0.00 | 647.31 | 0.226514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 305174.78 | 30-MAY-03:02 | 202303.34 | 28-MAY-16:21 | 0.00 | 0.00 | 0.00 |
June | 0.328941E+12 | 0.00 | 638.12 | 0.249406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317255.87 | 27-JUN-03:12 | 200908.26 | 05-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.387119E+12 | 0.00 | 651.85 | 0.278475E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 332307.74 | 24-JUL-03:02 | 219444.38 | 04-JUL-15:42 | 0.00 | 0.00 | 0.00 |
August | 0.429391E+12 | 0.00 | 659.25 | 0.309129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 333916.89 | 08-AUG-03:02 | 226904.06 | 06-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.337955E+12 | 0.00 | 631.78 | 0.241654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 324883.45 | 10-SEP-19:42 | 226296.15 | 04-SEP-15:42 | 0.00 | 0.00 | 0.00 |
October | 0.282226E+12 | 0.00 | 645.49 | 0.222024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 312317.07 | 01-OCT-19:03 | 202816.23 | 09-OCT-20:23 | 0.00 | 0.00 | 0.00 |
November | 0.180683E+12 | 0.00 | 579.96 | 0.153952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259536.42 | 10-NOV-06:02 | 178047.24 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.114528E+12 | 0.00 | 527.11 | 0.102744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 219120.93 | 12-DEC-05:22 | 159134.45 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280693E+13 | 0.00 | 7003.80 | 0.222606E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.717690E+11 | 0.00 | 411.67 | 0.688605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 219120.93 | 159134.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.429391E+12 | 0.00 | 659.25 | 0.309129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 333916.89 | 226904.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.512018E+12 | 0.00 | 414.56 | 0.488755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1747796.97 | 30-JAN-06:03 | 1162055.63 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.616548E+12 | 0.00 | 384.38 | 0.567385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2077401.98 | 09-FEB-06:02 | 1417381.28 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.931949E+12 | 0.00 | 461.11 | 0.866400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2061821.12 | 01-MAR-06:02 | 1651687.35 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.124459E+13 | 0.00 | 486.70 | 0.109279E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2215879.66 | 20-APR-04:12 | 1590264.86 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.201440E+13 | 0.00 | 607.56 | 0.165376E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2854493.67 | 30-MAY-05:02 | 1731566.44 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.257852E+13 | 0.00 | 624.86 | 0.180421E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2921678.04 | 20-JUN-05:02 | 1760097.78 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.307243E+13 | 0.00 | 646.92 | 0.200344E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3200017.57 | 30-JUL-16:22 | 1789660.98 | 14-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.332682E+13 | 0.00 | 655.62 | 0.214972E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3074188.12 | 08-AUG-05:01 | 1917713.80 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.265183E+13 | 0.00 | 604.12 | 0.172078E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3138918.52 | 10-SEP-16:52 | 1819436.01 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.195468E+13 | 0.00 | 554.42 | 0.144047E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2787408.11 | 07-OCT-05:02 | 1693576.47 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.124214E+13 | 0.00 | 452.86 | 0.102519E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2439139.26 | 10-NOV-06:02 | 1588426.56 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.714591E+12 | 0.00 | 422.89 | 0.630447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2055199.71 | 12-DEC-06:02 | 1451221.48 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208605E+14 | 0.00 | 6315.98 | 0.154433E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.512018E+12 | 0.00 | 384.38 | 0.488755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1747796.97 | 1162055.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.332682E+13 | 0.00 | 655.62 | 0.214972E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3200017.57 | 1917713.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.463729E+11 | 0.00 | 402.72 | 0.440827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149644.54 | 30-JAN-06:03 | 96424.40 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.594816E+11 | 0.00 | 374.18 | 0.545864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214846.15 | 06-FEB-06:02 | 150140.72 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.937424E+11 | 0.00 | 452.61 | 0.871785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218983.38 | 29-MAR-05:02 | 179571.05 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.129249E+12 | 0.00 | 485.06 | 0.114063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258535.71 | 30-APR-14:51 | 174176.64 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.214606E+12 | 0.00 | 607.53 | 0.178471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 316127.51 | 30-MAY-05:02 | 193844.75 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.273572E+12 | 0.00 | 626.44 | 0.195972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317111.49 | 04-JUN-16:51 | 199497.52 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.325921E+12 | 0.00 | 647.66 | 0.219121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 347593.05 | 30-JUL-16:22 | 206979.48 | 24-JUL-04:22 | 0.00 | 0.00 | 0.00 |
August | 0.351643E+12 | 0.00 | 656.26 | 0.234165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 339301.45 | 08-AUG-05:01 | 215874.26 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.277131E+12 | 0.00 | 605.09 | 0.184172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 336949.84 | 10-SEP-17:22 | 237157.56 | 04-SEP-15:31 | 0.00 | 0.00 | 0.00 |
October | 0.200945E+12 | 0.00 | 553.53 | 0.149621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 301834.98 | 07-OCT-05:02 | 189034.07 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.123136E+12 | 0.00 | 447.46 | 0.101640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 245000.89 | 10-NOV-06:02 | 174613.49 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.672757E+11 | 0.00 | 412.28 | 0.590095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218591.53 | 11-DEC-06:02 | 147248.04 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216308E+13 | 0.00 | 6270.82 | 0.162208E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.463729E+11 | 0.00 | 374.18 | 0.440827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149644.54 | 96424.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.351643E+12 | 0.00 | 656.26 | 0.234165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 347593.05 | 237157.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.674921E+11 | 0.00 | 386.14 | 0.652194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 251523.49 | 30-JAN-20:32 | 114869.43 | 01-JAN-18:32 | 0.00 | 0.00 | 0.00 |
February | 0.586168E+11 | 0.00 | 297.99 | 0.554347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 264825.47 | 08-FEB-06:52 | 107337.95 | 11-FEB-05:23 | 0.00 | 0.00 | 0.00 |
March | 0.634981E+11 | 0.00 | 276.08 | 0.576037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 269233.11 | 29-MAR-04:05 | 104767.36 | 03-MAR-06:15 | 0.00 | 0.00 | 0.00 |
April | 0.403935E+11 | 0.00 | 129.15 | 0.322722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 282098.88 | 30-APR-03:03 | 103253.39 | 10-APR-12:30 | 0.00 | 0.00 | 0.00 |
May | 0.698620E+10 | 0.00 | 16.33 | 0.535787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186092.57 | 01-MAY-04:22 | 109284.37 | 01-MAY-11:00 | 0.00 | 0.00 | 0.00 |
June | 0.702341E+10 | 0.00 | 13.17 | 0.522461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270711.11 | 22-JUN-07:53 | 121565.35 | 22-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 |
October | 0.135038E+11 | 0.00 | 29.40 | 0.106736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 288096.54 | 29-OCT-02:33 | 120628.03 | 21-OCT-12:05 | 0.00 | 0.00 | 0.00 |
November | 0.668507E+11 | 0.00 | 191.05 | 0.552551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 277409.68 | 04-NOV-04:23 | 115244.67 | 06-NOV-03:45 | 0.00 | 0.00 | 0.00 |
December | 0.752827E+11 | 0.00 | 349.85 | 0.685903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 261533.33 | 12-DEC-20:31 | 112288.03 | 12-DEC-22:17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399647E+12 | 0.00 | 1689.15 | 0.355631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.752827E+11 | 0.00 | 386.14 | 0.685903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 288096.54 | 121565.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.354478E+12 | 0.905194E+11 | 744.00 | 0.343723E+12 | 0.107550E+11 | 0.00 | 0.33 | 23-JAN-14:00 | 0.29 | 21-JAN-05:55 | 143265.94 | 30-JAN-15:00 | 134105.48 | 23-JAN-14:00 | 10955.22 | 30-JAN-15:00 | 44229.86 | 23-JAN-14:00 | 0.00 |
February | 0.545438E+12 | 0.141225E+12 | 672.00 | 0.532336E+12 | 0.131021E+11 | 0.00 | 0.56 | 07-FEB-14:00 | 0.48 | 01-FEB-05:00 | 238139.64 | 07-FEB-16:10 | 227762.87 | 06-FEB-15:00 | 11722.97 | 07-FEB-16:10 | 82167.14 | 06-FEB-15:00 | 0.00 |
March | 0.849618E+12 | 0.232905E+12 | 744.00 | 0.836878E+12 | 0.127404E+11 | 0.00 | 0.87 | 31-MAR-23:15 | 0.66 | 08-MAR-06:00 | 408391.06 | 31-MAR-23:05 | 398192.09 | 31-MAR-23:55 | 12100.93 | 28-MAR-16:00 | 131676.56 | 27-MAR-11:00 | 0.00 |
April | 0.106396E+13 | 0.318261E+12 | 720.00 | 0.105046E+13 | 0.134972E+11 | 0.00 | 1.00 | 26-APR-10:00 | 0.37 | 30-APR-23:15 | 422560.64 | 28-APR-14:05 | 419744.91 | 28-APR-13:05 | 15929.42 | 10-APR-10:00 | 179476.03 | 28-APR-12:00 | 0.00 |
May | 0.377963E+12 | 0.133663E+12 | 744.00 | 0.360049E+12 | 0.179139E+11 | 0.00 | 0.55 | 31-MAY-23:13 | 0.31 | 03-MAY-06:00 | 231381.54 | 31-MAY-23:03 | 221110.15 | 31-MAY-23:53 | 15789.25 | 30-MAY-00:55 | 82712.11 | 31-MAY-23:13 | 0.00 |
June | 0.615667E+12 | 0.221397E+12 | 720.00 | 0.587892E+12 | 0.277755E+11 | 0.00 | 0.75 | 30-JUN-24:00 | 0.52 | 22-JUN-08:00 | 329504.04 | 30-JUN-23:03 | 312505.27 | 30-JUN-23:53 | 18743.84 | 08-JUN-13:00 | 111695.06 | 30-JUN-24:00 | 0.00 |
July | 0.890897E+12 | 0.333106E+12 | 744.00 | 0.857455E+12 | 0.334417E+11 | 0.00 | 0.96 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 425555.31 | 31-JUL-23:03 | 406037.50 | 31-JUL-24:00 | 22576.12 | 20-JUL-11:00 | 159381.36 | 21-JUL-12:00 | 0.00 |
August | 0.113899E+13 | 0.423014E+12 | 744.00 | 0.110448E+13 | 0.345106E+11 | 0.00 | 1.00 | 01-AUG-10:00 | 0.39 | 31-AUG-23:13 | 445994.20 | 04-AUG-14:00 | 421424.67 | 10-AUG-21:01 | 24697.44 | 04-AUG-14:00 | 191280.80 | 16-AUG-12:00 | 0.00 |
September | 0.385337E+12 | 0.138622E+12 | 720.00 | 0.354701E+12 | 0.306353E+11 | 0.00 | 0.56 | 30-SEP-23:05 | 0.33 | 30-SEP-05:20 | 242641.35 | 30-SEP-23:05 | 220708.18 | 30-SEP-24:00 | 22708.67 | 30-SEP-23:05 | 76824.22 | 30-SEP-23:15 | 0.00 |
October | 0.631844E+12 | 0.207996E+12 | 744.00 | 0.607611E+12 | 0.242327E+11 | 0.00 | 0.72 | 31-OCT-23:20 | 0.51 | 29-OCT-07:00 | 319857.53 | 31-OCT-23:05 | 311491.32 | 31-OCT-24:00 | 18944.50 | 07-OCT-10:10 | 98266.89 | 31-OCT-23:20 | 0.00 |
November | 0.835570E+12 | 0.244530E+12 | 720.00 | 0.818452E+12 | 0.171185E+11 | 0.00 | 0.78 | 01-NOV-14:00 | 0.67 | 26-NOV-05:40 | 335717.98 | 01-NOV-15:00 | 321459.74 | 13-NOV-15:00 | 15598.76 | 01-NOV-15:00 | 118313.52 | 01-NOV-14:00 | 0.00 |
December | 0.110099E+13 | 0.281727E+12 | 744.00 | 0.108366E+13 | 0.173259E+11 | 0.00 | 0.92 | 04-DEC-13:10 | 0.84 | 31-DEC-06:00 | 421990.35 | 05-DEC-17:00 | 410161.12 | 11-DEC-17:00 | 13762.23 | 26-DEC-07:40 | 133896.57 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.879074E+13 | 0.276697E+13 | 8760.00 | 0.853770E+13 | 0.253049E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.354478E+12 | 0.905194E+11 | 672.00 | 0.343723E+12 | 0.107550E+11 | 0.00 | 0.33 | 0.29 | 143265.94 | 134105.48 | 10955.22 | 44229.86 | 0.00 | ||||||
Maximum of Months | 0.113899E+13 | 0.423014E+12 | 744.00 | 0.110448E+13 | 0.345106E+11 | 0.00 | 1.00 | 0.84 | 445994.20 | 421424.67 | 24697.44 | 191280.80 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.566317E+10 | 0.143050E+10 | 744.00 | 0.532296E+10 | 0.340205E+09 | 0.00 | 0.32 | 29-JAN-17:25 | 0.20 | 21-JAN-08:00 | 2687.29 | 30-JAN-15:00 | 2380.04 | 29-JAN-17:40 | 422.90 | 30-JAN-15:05 | 782.15 | 23-JAN-14:00 | 0.00 |
February | 0.100586E+11 | 0.254796E+10 | 672.00 | 0.960745E+10 | 0.451185E+09 | 0.00 | 0.57 | 07-FEB-16:10 | 0.43 | 01-FEB-07:00 | 4841.37 | 07-FEB-16:10 | 4446.41 | 05-FEB-17:20 | 491.84 | 07-FEB-16:10 | 1559.48 | 06-FEB-15:00 | 0.00 |
March | 0.163660E+11 | 0.437530E+10 | 744.00 | 0.158976E+11 | 0.468341E+09 | 0.00 | 0.89 | 31-MAR-23:05 | 0.63 | 08-MAR-07:00 | 8115.51 | 31-MAR-23:05 | 7653.09 | 31-MAR-23:50 | 494.69 | 28-MAR-16:00 | 2521.88 | 27-MAR-11:00 | 0.00 |
April | 0.211832E+11 | 0.613162E+10 | 720.00 | 0.205774E+11 | 0.605799E+09 | 0.00 | 1.00 | 02-APR-13:48 | 0.39 | 30-APR-23:43 | 8898.93 | 30-APR-17:57 | 8476.18 | 23-APR-16:22 | 591.32 | 30-APR-15:00 | 3351.90 | 28-APR-12:00 | 0.00 |
May | 0.745713E+10 | 0.253547E+10 | 744.00 | 0.671862E+10 | 0.738509E+09 | 0.00 | 0.58 | 31-MAY-23:13 | 0.28 | 03-MAY-07:00 | 4772.08 | 31-MAY-23:03 | 4367.81 | 31-MAY-24:00 | 663.00 | 30-MAY-02:00 | 1629.96 | 31-MAY-23:13 | 0.00 |
June | 0.127495E+11 | 0.437805E+10 | 720.00 | 0.115482E+11 | 0.120129E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.52 | 03-JUN-06:40 | 6938.89 | 30-JUN-23:03 | 6206.11 | 30-JUN-23:57 | 800.83 | 08-JUN-13:10 | 2226.14 | 30-JUN-23:57 | 0.00 |
July | 0.188197E+11 | 0.669641E+10 | 744.00 | 0.173244E+11 | 0.149531E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.74 | 03-JUL-06:40 | 8714.84 | 31-JUL-24:00 | 8025.16 | 31-JUL-24:00 | 962.64 | 20-JUL-14:00 | 3169.72 | 30-JUL-14:00 | 0.00 |
August | 0.230426E+11 | 0.807538E+10 | 744.00 | 0.214916E+11 | 0.155099E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.40 | 31-AUG-23:05 | 8989.95 | 27-AUG-06:00 | 8345.90 | 06-AUG-05:00 | 967.36 | 30-AUG-20:00 | 3574.74 | 16-AUG-12:00 | 0.00 |
September | 0.797532E+10 | 0.272279E+10 | 720.00 | 0.669334E+10 | 0.128199E+10 | 0.00 | 0.60 | 30-SEP-23:05 | 0.30 | 26-SEP-07:00 | 5245.45 | 30-SEP-23:05 | 4292.10 | 30-SEP-24:00 | 987.37 | 30-SEP-23:05 | 1554.89 | 30-SEP-23:15 | 0.00 |
October | 0.127391E+11 | 0.402947E+10 | 744.00 | 0.117033E+11 | 0.103581E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.48 | 21-OCT-07:00 | 6358.02 | 31-OCT-23:05 | 6012.09 | 31-OCT-24:00 | 852.29 | 07-OCT-10:10 | 1942.91 | 09-OCT-15:20 | 0.00 |
November | 0.164431E+11 | 0.466079E+10 | 720.00 | 0.157103E+11 | 0.732812E+09 | 0.00 | 0.83 | 01-NOV-14:05 | 0.65 | 22-NOV-07:00 | 7016.19 | 01-NOV-16:00 | 6652.70 | 12-NOV-16:53 | 674.00 | 01-NOV-15:00 | 2346.25 | 01-NOV-14:00 | 0.00 |
December | 0.213451E+11 | 0.532104E+10 | 744.00 | 0.207695E+11 | 0.575633E+09 | 0.00 | 0.96 | 05-DEC-17:00 | 0.80 | 30-DEC-08:00 | 8669.45 | 05-DEC-17:00 | 8183.20 | 25-DEC-16:50 | 578.54 | 05-DEC-17:00 | 2577.57 | 10-DEC-12:23 | 0.00 |
Annual Sum or Average | 0.173843E+12 | 0.529048E+11 | 8760.00 | 0.163365E+12 | 0.104779E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.566317E+10 | 0.143050E+10 | 672.00 | 0.532296E+10 | 0.340205E+09 | 0.00 | 0.32 | 0.20 | 2687.29 | 2380.04 | 422.90 | 782.15 | 0.00 | ||||||
Maximum of Months | 0.230426E+11 | 0.807538E+10 | 744.00 | 0.214916E+11 | 0.155099E+10 | 0.00 | 1.00 | 0.80 | 8989.95 | 8476.18 | 987.37 | 3574.74 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.474605E+11 | 0.121272E+11 | 744.00 | 0.441923E+11 | 0.326821E+10 | 0.00 | 0.31 | 30-JAN-14:20 | 0.15 | 21-JAN-08:00 | 24587.93 | 30-JAN-15:00 | 21415.85 | 23-JAN-14:05 | 4129.94 | 30-JAN-15:05 | 7129.15 | 23-JAN-14:00 | 0.00 |
February | 0.916477E+11 | 0.233459E+11 | 672.00 | 0.871906E+11 | 0.445714E+10 | 0.00 | 0.57 | 07-FEB-16:10 | 0.39 | 13-FEB-07:00 | 45849.10 | 07-FEB-16:10 | 41727.26 | 06-FEB-15:00 | 4875.85 | 07-FEB-16:10 | 14772.64 | 06-FEB-15:00 | 0.00 |
March | 0.154122E+12 | 0.412954E+11 | 744.00 | 0.149464E+12 | 0.465790E+10 | 0.00 | 0.90 | 31-MAR-23:05 | 0.60 | 08-MAR-07:00 | 78106.19 | 31-MAR-23:05 | 73531.03 | 31-MAR-23:55 | 4913.08 | 28-MAR-16:10 | 24030.49 | 27-MAR-11:00 | 0.00 |
April | 0.201098E+12 | 0.582529E+11 | 720.00 | 0.195054E+12 | 0.604467E+10 | 0.00 | 1.00 | 24-APR-11:50 | 0.33 | 30-APR-23:55 | 84273.48 | 30-APR-17:55 | 79889.97 | 26-APR-14:05 | 5948.96 | 30-APR-15:00 | 31989.76 | 28-APR-12:00 | 0.00 |
May | 0.679768E+11 | 0.231852E+11 | 744.00 | 0.607356E+11 | 0.724120E+10 | 0.00 | 0.58 | 31-MAY-23:03 | 0.26 | 03-MAY-07:00 | 45187.01 | 31-MAY-23:03 | 40908.92 | 31-MAY-24:00 | 6449.30 | 30-MAY-02:00 | 15405.81 | 31-MAY-23:13 | 0.00 |
June | 0.118891E+12 | 0.408908E+11 | 720.00 | 0.106983E+12 | 0.119074E+11 | 0.00 | 0.80 | 30-JUN-23:03 | 0.51 | 07-JUN-06:00 | 65980.91 | 30-JUN-23:03 | 58218.55 | 30-JUN-23:57 | 8076.53 | 30-JUN-23:03 | 21016.32 | 30-JUN-23:13 | 0.00 |
July | 0.175821E+12 | 0.626748E+11 | 744.00 | 0.160945E+12 | 0.148757E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.72 | 03-JUL-06:00 | 83080.82 | 31-JUL-24:00 | 76086.14 | 31-JUL-24:00 | 9574.59 | 20-JUL-14:00 | 29465.41 | 21-JUL-12:00 | 0.00 |
August | 0.219010E+12 | 0.769942E+11 | 744.00 | 0.203448E+12 | 0.155619E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:13 | 85131.68 | 08-AUG-04:53 | 78646.06 | 06-AUG-05:00 | 9638.63 | 30-AUG-20:00 | 34115.82 | 16-AUG-12:00 | 0.00 |
September | 0.722992E+11 | 0.247288E+11 | 720.00 | 0.597246E+11 | 0.125746E+11 | 0.00 | 0.60 | 30-SEP-23:05 | 0.28 | 26-SEP-07:00 | 49578.15 | 30-SEP-23:05 | 39624.19 | 30-SEP-23:33 | 10188.14 | 30-SEP-23:05 | 14630.04 | 30-SEP-23:05 | 0.00 |
October | 0.118088E+12 | 0.374267E+11 | 744.00 | 0.107835E+12 | 0.102537E+11 | 0.00 | 0.74 | 31-OCT-24:00 | 0.47 | 21-OCT-07:00 | 60946.23 | 31-OCT-23:05 | 57443.88 | 31-OCT-24:00 | 8458.57 | 07-OCT-10:10 | 18003.38 | 31-OCT-23:20 | 0.00 |
November | 0.154786E+12 | 0.439425E+11 | 720.00 | 0.147498E+12 | 0.728803E+10 | 0.00 | 0.82 | 01-NOV-14:00 | 0.63 | 22-NOV-07:00 | 66858.32 | 01-NOV-16:00 | 61194.72 | 05-NOV-16:54 | 6705.43 | 01-NOV-15:00 | 22365.19 | 01-NOV-14:00 | 0.00 |
December | 0.200123E+12 | 0.500407E+11 | 744.00 | 0.194384E+12 | 0.573864E+10 | 0.00 | 0.96 | 05-DEC-17:00 | 0.78 | 30-DEC-08:00 | 82665.61 | 05-DEC-17:00 | 76901.71 | 04-DEC-17:00 | 5768.79 | 05-DEC-17:00 | 24233.09 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.162132E+13 | 0.494905E+12 | 8760.00 | 0.151745E+13 | 0.103869E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.474605E+11 | 0.121272E+11 | 672.00 | 0.441923E+11 | 0.326821E+10 | 0.00 | 0.31 | 0.15 | 24587.93 | 21415.85 | 4129.94 | 7129.15 | 0.00 | ||||||
Maximum of Months | 0.219010E+12 | 0.769942E+11 | 744.00 | 0.203448E+12 | 0.155619E+11 | 0.00 | 1.00 | 0.78 | 85131.68 | 79889.97 | 10188.14 | 34115.82 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.429235E+10 | 0.111018E+10 | 744.00 | 0.397352E+10 | 0.318831E+09 | 0.00 | 0.31 | 29-JAN-17:25 | 0.09 | 01-JAN-08:00 | 2490.92 | 30-JAN-14:50 | 2196.81 | 23-JAN-14:05 | 415.57 | 30-JAN-15:05 | 729.55 | 23-JAN-14:00 | 0.00 |
February | 0.892808E+10 | 0.228643E+10 | 672.00 | 0.848383E+10 | 0.444259E+09 | 0.00 | 0.57 | 07-FEB-16:10 | 0.34 | 13-FEB-08:00 | 4634.41 | 07-FEB-16:10 | 4237.00 | 05-FEB-17:20 | 488.59 | 07-FEB-16:10 | 1494.85 | 06-FEB-15:00 | 0.00 |
March | 0.153062E+11 | 0.411364E+10 | 744.00 | 0.148406E+11 | 0.465646E+09 | 0.00 | 0.89 | 31-MAR-23:05 | 0.57 | 08-MAR-07:00 | 7766.70 | 31-MAR-23:05 | 7303.94 | 31-MAR-23:55 | 491.76 | 28-MAR-16:10 | 2413.74 | 27-MAR-11:00 | 0.00 |
April | 0.201429E+11 | 0.584412E+10 | 720.00 | 0.195384E+11 | 0.604576E+09 | 0.00 | 1.00 | 02-APR-13:43 | 0.34 | 30-APR-23:25 | 8546.27 | 30-APR-17:55 | 8179.90 | 23-APR-17:22 | 589.35 | 30-APR-15:00 | 3226.95 | 28-APR-12:00 | 0.00 |
May | 0.694750E+10 | 0.237077E+10 | 744.00 | 0.621982E+10 | 0.727679E+09 | 0.00 | 0.58 | 31-MAY-23:03 | 0.25 | 03-MAY-07:00 | 4574.29 | 31-MAY-23:03 | 4151.87 | 31-MAY-24:00 | 649.19 | 30-MAY-02:00 | 1560.02 | 31-MAY-23:13 | 0.00 |
June | 0.120445E+11 | 0.414380E+10 | 720.00 | 0.108514E+11 | 0.119310E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.50 | 03-JUN-06:50 | 6620.40 | 30-JUN-23:03 | 5847.92 | 30-JUN-23:57 | 807.28 | 30-JUN-23:03 | 2116.65 | 09-JUN-15:00 | 0.00 |
July | 0.178133E+11 | 0.634971E+10 | 744.00 | 0.163239E+11 | 0.148943E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.72 | 03-JUL-06:00 | 8374.64 | 31-JUL-24:00 | 7674.30 | 31-JUL-24:00 | 960.23 | 20-JUL-14:00 | 3031.30 | 30-JUL-14:00 | 0.00 |
August | 0.220857E+11 | 0.776330E+10 | 744.00 | 0.205299E+11 | 0.155583E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:13 | 8577.38 | 20-AUG-21:04 | 7952.06 | 06-AUG-05:00 | 968.74 | 30-AUG-20:00 | 3441.52 | 16-AUG-12:00 | 0.00 |
September | 0.737715E+10 | 0.252492E+10 | 720.00 | 0.611460E+10 | 0.126255E+10 | 0.00 | 0.60 | 30-SEP-23:05 | 0.27 | 26-SEP-07:00 | 5007.28 | 30-SEP-23:05 | 4007.96 | 30-SEP-23:30 | 1008.09 | 30-SEP-23:05 | 1479.31 | 30-SEP-23:10 | 0.00 |
October | 0.118794E+11 | 0.376914E+10 | 744.00 | 0.108531E+11 | 0.102628E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.45 | 21-OCT-07:00 | 6090.24 | 31-OCT-23:05 | 5744.05 | 31-OCT-24:00 | 848.44 | 07-OCT-10:10 | 1813.70 | 09-OCT-15:30 | 0.00 |
November | 0.154158E+11 | 0.438658E+10 | 720.00 | 0.146873E+11 | 0.728576E+09 | 0.00 | 0.82 | 01-NOV-14:05 | 0.61 | 22-NOV-07:00 | 6735.74 | 01-NOV-16:00 | 6274.22 | 05-NOV-16:34 | 671.36 | 01-NOV-15:00 | 2253.37 | 01-NOV-14:00 | 0.00 |
December | 0.197346E+11 | 0.495433E+10 | 744.00 | 0.191612E+11 | 0.573398E+09 | 0.00 | 0.96 | 05-DEC-17:00 | 0.73 | 31-DEC-08:00 | 8292.05 | 05-DEC-17:00 | 7716.80 | 06-DEC-17:00 | 576.98 | 05-DEC-17:00 | 2430.84 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.161968E+12 | 0.496169E+11 | 8760.00 | 0.151577E+12 | 0.103901E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.429235E+10 | 0.111018E+10 | 672.00 | 0.397352E+10 | 0.318831E+09 | 0.00 | 0.31 | 0.09 | 2490.92 | 2196.81 | 415.57 | 729.55 | 0.00 | ||||||
Maximum of Months | 0.220857E+11 | 0.776330E+10 | 744.00 | 0.205299E+11 | 0.155583E+10 | 0.00 | 1.00 | 0.73 | 8577.38 | 8179.90 | 1008.09 | 3441.52 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.59 | 280.25 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.23 | 237.92 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 246.82 | 179.41 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 357.88 | 115.02 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 540.53 | 33.82 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 621.85 | 12.17 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 685.22 | 0.83 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 669.68 | 0.30 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 506.69 | 15.58 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 362.22 | 59.29 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.23 | 134.47 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 133.89 | 234.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 388.32 | 107.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.59 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 685.22 | 280.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.59 | 280.25 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.23 | 237.92 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 246.82 | 179.41 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 357.88 | 115.02 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 540.53 | 33.82 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 621.85 | 12.17 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 685.22 | 0.83 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 669.68 | 0.30 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 506.69 | 15.58 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 362.22 | 59.29 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.23 | 134.47 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 133.89 | 234.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 388.32 | 107.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.59 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 685.22 | 280.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.59 | 280.25 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.23 | 237.92 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 246.82 | 179.41 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 357.88 | 115.02 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 540.53 | 33.82 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 621.85 | 12.17 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 685.22 | 0.83 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 669.68 | 0.30 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 506.69 | 15.58 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 362.22 | 59.29 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.23 | 134.47 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 133.89 | 234.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 388.32 | 107.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.59 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 685.22 | 280.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.59 | 280.25 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 168.23 | 237.92 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 246.82 | 179.41 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 357.88 | 115.02 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 540.53 | 33.82 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 621.85 | 12.17 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 685.22 | 0.83 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 669.68 | 0.30 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 506.69 | 15.58 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 362.22 | 59.29 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 231.23 | 134.47 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 133.89 | 234.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 388.32 | 107.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.59 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 685.22 | 280.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.59 | 280.24 | 0.00 | 0.00 | 0.00 |
February | 128.46 | 0.00 | 128.46 | 168.22 | 237.91 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 246.81 | 179.40 | 0.00 | 0.00 | 0.00 |
April | 166.25 | 0.34 | 165.91 | 357.87 | 115.02 | 0.00 | 0.00 | 0.00 |
May | 187.13 | 5.49 | 181.64 | 540.51 | 33.82 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.23 | 621.82 | 12.17 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.55 | 685.20 | 0.83 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.73 | 669.65 | 0.30 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.88 | 506.67 | 15.58 | 0.00 | 0.00 | 0.00 |
October | 138.20 | 0.00 | 138.20 | 362.21 | 59.29 | 0.00 | 0.00 | 0.00 |
November | 118.64 | 0.00 | 118.64 | 231.22 | 134.47 | 0.00 | 0.00 | 0.00 |
December | 104.60 | 0.00 | 104.60 | 133.89 | 234.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 388.30 | 107.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.60 | 0.00 | 104.60 | 119.59 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.23 | 685.20 | 280.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 299.29 | 288.58 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 366.09 | 245.21 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 471.46 | 184.97 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 674.61 | 119.47 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 901.94 | 37.46 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 948.26 | 12.76 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1014.80 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1045.44 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 849.73 | 16.68 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 668.63 | 62.47 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 468.91 | 137.85 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 294.83 | 235.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 668.72 | 111.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 294.83 | 0.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1045.44 | 288.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 299.29 | 288.58 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 366.09 | 245.21 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 471.46 | 184.97 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 674.61 | 119.47 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 901.94 | 37.46 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 948.26 | 12.76 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1014.80 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1045.44 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 849.73 | 16.68 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 668.63 | 62.47 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 468.91 | 137.85 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 294.83 | 235.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 668.72 | 111.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 294.83 | 0.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1045.44 | 288.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 299.29 | 288.58 | 0.00 | 0.00 | 0.00 |
February | 245.48 | 66.53 | 178.96 | 366.09 | 245.21 | 0.00 | 0.00 | 0.00 |
March | 271.16 | 66.83 | 204.33 | 471.45 | 184.97 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.19 | 233.95 | 674.60 | 119.47 | 0.00 | 0.00 | 0.00 |
May | 368.95 | 117.55 | 251.40 | 901.92 | 37.46 | 0.00 | 0.00 | 0.00 |
June | 361.33 | 110.50 | 250.83 | 948.24 | 12.76 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1014.78 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 345.33 | 105.99 | 239.35 | 1045.42 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 324.65 | 100.35 | 224.31 | 849.71 | 16.68 | 0.00 | 0.00 | 0.00 |
October | 294.59 | 96.24 | 198.35 | 668.62 | 62.47 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.67 | 468.90 | 137.85 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 144.99 | 294.82 | 235.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.10 | 88.30 | 207.80 | 668.71 | 111.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 144.99 | 294.82 | 0.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.95 | 117.55 | 251.40 | 1045.42 | 288.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.49 | 269.93 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 566.50 | 235.40 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 521.80 | 183.50 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 483.23 | 118.16 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 541.35 | 33.16 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 569.57 | 9.40 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 667.53 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 747.40 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 752.20 | 15.23 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 790.87 | 59.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.45 | 136.69 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.26 | 229.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 629.40 | 107.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 483.23 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 790.87 | 269.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.49 | 269.93 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 566.50 | 235.40 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 521.80 | 183.50 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 483.22 | 118.16 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 541.35 | 33.16 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 569.57 | 9.40 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 667.53 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 747.40 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 752.20 | 15.23 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 790.87 | 59.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.45 | 136.69 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.26 | 229.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 629.40 | 107.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 483.22 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 790.87 | 269.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.49 | 269.93 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 566.50 | 235.40 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 521.80 | 183.50 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 483.23 | 118.16 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 541.35 | 33.16 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 569.57 | 9.40 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 667.53 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 747.40 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 752.20 | 15.23 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 790.87 | 59.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.45 | 136.69 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.26 | 229.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 629.40 | 107.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 483.23 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 790.87 | 269.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.49 | 269.93 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 566.50 | 235.40 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 521.80 | 183.50 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 483.22 | 118.16 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 541.35 | 33.16 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 569.57 | 9.40 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 667.53 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 747.40 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 752.20 | 15.23 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 790.87 | 59.75 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 741.45 | 136.69 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 599.26 | 229.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 629.40 | 107.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 483.22 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 790.87 | 269.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.20 | 170.29 | 191.91 | 566.47 | 269.92 | 0.00 | 0.00 | 0.00 |
February | 340.12 | 139.12 | 200.99 | 566.48 | 235.39 | 0.00 | 0.00 | 0.00 |
March | 279.93 | 76.00 | 203.93 | 521.78 | 183.50 | 0.00 | 0.00 | 0.00 |
April | 220.05 | 23.33 | 196.72 | 483.21 | 118.15 | 0.00 | 0.00 | 0.00 |
May | 186.40 | 2.85 | 183.55 | 541.32 | 33.16 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.33 | 569.55 | 9.40 | 0.00 | 0.00 | 0.00 |
July | 175.54 | 1.49 | 174.05 | 667.51 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 203.61 | 14.43 | 189.19 | 747.37 | 0.21 | 0.00 | 0.00 | 0.00 |
September | 268.47 | 61.53 | 206.94 | 752.17 | 15.23 | 0.00 | 0.00 | 0.00 |
October | 351.48 | 139.73 | 211.74 | 790.84 | 59.74 | 0.00 | 0.00 | 0.00 |
November | 387.75 | 186.92 | 200.83 | 741.42 | 136.68 | 0.00 | 0.00 | 0.00 |
December | 359.95 | 177.80 | 182.14 | 599.23 | 229.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.53 | 82.51 | 193.03 | 629.38 | 107.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.54 | 0.22 | 174.05 | 483.21 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.75 | 186.92 | 211.74 | 790.84 | 269.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.35 | 340.01 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 378.82 | 300.53 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 512.52 | 240.78 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 649.67 | 167.11 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 878.04 | 45.28 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 951.69 | 17.11 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 992.77 | 1.77 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 1012.10 | 1.06 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 857.90 | 19.84 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 662.52 | 77.45 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 473.76 | 184.71 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.55 | 316.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 666.49 | 141.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 300.35 | 1.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 1012.10 | 340.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.35 | 340.01 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 378.82 | 300.53 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 512.52 | 240.78 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 649.67 | 167.11 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 878.04 | 45.28 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 951.69 | 17.11 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 992.77 | 1.77 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 1012.10 | 1.06 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 857.90 | 19.84 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 662.52 | 77.45 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 473.76 | 184.71 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.55 | 316.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 666.49 | 141.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 300.35 | 1.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 1012.10 | 340.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.35 | 340.00 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.32 | 378.81 | 300.52 | 0.00 | 0.00 | 0.00 |
March | 298.80 | 88.46 | 210.34 | 512.51 | 240.78 | 0.00 | 0.00 | 0.00 |
April | 326.54 | 91.74 | 234.80 | 649.66 | 167.11 | 0.00 | 0.00 | 0.00 |
May | 355.44 | 106.40 | 249.04 | 878.02 | 45.28 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 951.67 | 17.11 | 0.00 | 0.00 | 0.00 |
July | 336.97 | 96.40 | 240.57 | 992.75 | 1.77 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 1012.08 | 1.06 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.31 | 225.53 | 857.89 | 19.84 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.40 | 197.84 | 662.51 | 77.45 | 0.00 | 0.00 | 0.00 |
November | 251.15 | 82.13 | 169.02 | 473.75 | 184.71 | 0.00 | 0.00 | 0.00 |
December | 210.25 | 63.56 | 146.70 | 308.54 | 316.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.75 | 666.48 | 141.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.25 | 63.45 | 146.70 | 300.35 | 1.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 1012.08 | 340.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 645.45 | 1250.85 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 884.98 | 1060.39 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1270.91 | 822.11 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1846.06 | 522.96 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2812.51 | 129.21 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3250.21 | 31.05 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3623.88 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3572.20 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2697.69 | 44.06 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1930.48 | 213.89 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1219.94 | 593.27 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 719.95 | 1035.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2046.67 | 472.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 645.45 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3623.88 | 1250.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 905.99 | 810.73 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1099.58 | 693.88 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1407.66 | 541.86 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2020.55 | 354.52 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2745.41 | 89.12 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2902.33 | 20.62 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3133.13 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3235.09 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2623.17 | 29.45 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2048.15 | 143.51 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1412.47 | 392.20 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 887.34 | 675.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2040.52 | 310.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 887.34 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3235.09 | 810.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2814.31 | 1310.74 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2820.55 | 1126.46 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2608.88 | 882.94 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2447.27 | 556.06 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2802.79 | 131.14 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2990.31 | 22.96 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3515.04 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3924.47 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3868.19 | 50.73 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 4004.18 | 247.98 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3705.43 | 654.33 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2989.04 | 1106.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3210.22 | 504.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2447.27 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 4004.18 | 1310.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 934.80 | 896.86 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1175.85 | 766.29 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1579.40 | 611.13 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 2004.75 | 413.77 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2675.56 | 114.19 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2933.95 | 29.63 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3104.14 | 1.19 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3191.11 | 0.39 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2633.51 | 43.03 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2043.34 | 184.19 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1471.90 | 454.21 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 986.54 | 761.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2066.33 | 354.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 934.80 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3191.11 | 896.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 667.52 | 1176.74 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 893.23 | 1016.69 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1264.29 | 802.17 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1826.40 | 524.95 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2776.97 | 136.03 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3210.17 | 34.58 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3572.54 | 1.20 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3525.78 | 0.11 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2661.19 | 46.80 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1909.25 | 219.33 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1213.04 | 580.91 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 731.87 | 985.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2028.03 | 457.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 667.52 | 0.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3572.54 | 1176.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 928.15 | 770.09 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1111.65 | 669.19 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1410.45 | 529.96 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2014.63 | 354.59 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2729.21 | 92.62 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2883.95 | 22.47 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3107.21 | 0.70 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3213.23 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2606.54 | 30.81 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2040.69 | 145.36 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1414.32 | 384.38 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 901.78 | 646.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2035.51 | 302.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 901.78 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3213.23 | 770.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2826.50 | 1252.23 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2818.74 | 1089.55 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2596.62 | 863.99 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2426.14 | 556.67 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2766.57 | 137.40 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2949.16 | 25.51 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3462.37 | 0.52 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3877.60 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3829.93 | 53.45 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 3978.10 | 251.75 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3690.80 | 642.72 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2990.82 | 1067.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3187.02 | 492.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2426.14 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 3978.10 | 1252.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 940.45 | 855.81 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1173.95 | 741.70 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1569.24 | 598.86 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 1988.61 | 412.75 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2652.03 | 117.63 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2908.67 | 31.43 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3072.68 | 1.61 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3161.61 | 0.49 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2610.17 | 45.13 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2028.33 | 186.48 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1463.88 | 445.88 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 987.12 | 733.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2051.41 | 345.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 940.45 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3161.61 | 855.81 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320319E+09 | 0.750615E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.406976E+09 | 0.575568E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.661086E+09 | 0.480521E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.927635E+09 | 0.298138E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.144776E+10 | 90574204.36 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.161183E+10 | 31541412.48 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.183530E+10 | 2225912.31 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.179367E+10 | 813499.38 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.131333E+10 | 40391071.04 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.970174E+09 | 0.158815E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.599359E+09 | 0.348558E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.358622E+09 | 0.627652E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.122461E+11 | 0.340541E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320319E+09 | 813499.38 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.183530E+10 | 0.750615E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320318E+09 | 0.750615E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.406976E+09 | 0.575567E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.661086E+09 | 0.480520E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.927634E+09 | 0.298137E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.144776E+10 | 90574097.25 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.161183E+10 | 31541343.42 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.183530E+10 | 2225900.75 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.179367E+10 | 813494.99 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.131333E+10 | 40391002.09 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.970173E+09 | 0.158815E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.599358E+09 | 0.348558E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.358622E+09 | 0.627651E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.122461E+11 | 0.340541E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320318E+09 | 813494.99 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.183530E+10 | 0.750615E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320319E+09 | 0.750615E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.406976E+09 | 0.575568E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.661086E+09 | 0.480521E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.927635E+09 | 0.298138E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.144776E+10 | 90574204.36 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.161183E+10 | 31541412.48 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.183530E+10 | 2225912.31 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.179367E+10 | 813499.38 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.131333E+10 | 40391071.04 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.970174E+09 | 0.158815E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.599359E+09 | 0.348558E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.358622E+09 | 0.627652E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.122461E+11 | 0.340541E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320319E+09 | 813499.38 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.183530E+10 | 0.750615E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320318E+09 | 0.750615E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.406976E+09 | 0.575567E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.661086E+09 | 0.480520E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.927634E+09 | 0.298137E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.144776E+10 | 90574097.25 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.161183E+10 | 31541343.42 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.183530E+10 | 2225900.75 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.179367E+10 | 813494.99 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.131333E+10 | 40391002.09 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.970173E+09 | 0.158815E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.599358E+09 | 0.348558E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.358622E+09 | 0.627651E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.122461E+11 | 0.340541E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320318E+09 | 813494.99 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.183530E+10 | 0.750615E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300167E+09 | 0.00 | 0.300167E+09 | 0.320306E+09 | 0.750585E+09 |
February | 0.310779E+09 | 0.00 | 0.310779E+09 | 0.406959E+09 | 0.575544E+09 |
March | 0.395219E+09 | 0.00 | 0.395219E+09 | 0.661060E+09 | 0.480501E+09 |
April | 0.430919E+09 | 887885.91 | 0.430031E+09 | 0.927598E+09 | 0.298126E+09 |
May | 0.501205E+09 | 14700043.40 | 0.486505E+09 | 0.144770E+10 | 90570553.82 |
June | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.161176E+10 | 31540141.22 |
July | 0.492415E+09 | 14187670.25 | 0.478227E+09 | 0.183523E+10 | 2225822.60 |
August | 0.458396E+09 | 3791392.35 | 0.454605E+09 | 0.179359E+10 | 813466.59 |
September | 0.404087E+09 | 46304.72 | 0.404041E+09 | 0.131328E+10 | 40389443.10 |
October | 0.370155E+09 | 0.00 | 0.370155E+09 | 0.970135E+09 | 0.158809E+09 |
November | 0.307520E+09 | 0.00 | 0.307520E+09 | 0.599335E+09 | 0.348544E+09 |
December | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.358608E+09 | 0.627626E+09 |
Annual Sum or Average | 0.477035E+10 | 62444616.66 | 0.470791E+10 | 0.122456E+11 | 0.340527E+10 |
Minimum of Months | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.320306E+09 | 813466.59 |
Maximum of Months | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.183523E+10 | 0.750585E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.801630E+09 | 0.772937E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.885649E+09 | 0.593220E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.126275E+10 | 0.495428E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.174860E+10 | 0.309661E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.241575E+10 | 0.100339E+09 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.245788E+10 | 33078600.85 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.271803E+10 | 1924147.48 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.280010E+10 | 671985.61 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.220250E+10 | 43247158.19 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.179086E+10 | 0.167315E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.121540E+10 | 0.357310E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.789663E+09 | 0.630084E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.210888E+11 | 0.350522E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.789663E+09 | 671985.61 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.280010E+10 | 0.772937E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.801630E+09 | 0.772937E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.885649E+09 | 0.593220E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.126275E+10 | 0.495428E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.174860E+10 | 0.309661E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.241575E+10 | 0.100339E+09 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.245788E+10 | 33078600.85 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.271803E+10 | 1924147.48 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.280010E+10 | 671985.61 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.220250E+10 | 43247158.19 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.179086E+10 | 0.167315E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.121540E+10 | 0.357310E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.789663E+09 | 0.630084E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.210888E+11 | 0.350522E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.789663E+09 | 671985.61 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.280010E+10 | 0.772937E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603338E+09 | 0.182539E+09 | 0.420799E+09 | 0.801615E+09 | 0.772923E+09 |
February | 0.593870E+09 | 0.160942E+09 | 0.432929E+09 | 0.885633E+09 | 0.593209E+09 |
March | 0.726276E+09 | 0.179000E+09 | 0.547275E+09 | 0.126273E+10 | 0.495419E+09 |
April | 0.855746E+09 | 0.249336E+09 | 0.606409E+09 | 0.174856E+10 | 0.309656E+09 |
May | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.241570E+10 | 0.100337E+09 |
June | 0.936567E+09 | 0.286413E+09 | 0.650155E+09 | 0.245784E+10 | 33077996.44 |
July | 0.903278E+09 | 0.260414E+09 | 0.642865E+09 | 0.271798E+10 | 1924112.32 |
August | 0.924942E+09 | 0.283877E+09 | 0.641065E+09 | 0.280005E+10 | 671973.33 |
September | 0.841503E+09 | 0.260099E+09 | 0.581404E+09 | 0.220246E+10 | 43246367.97 |
October | 0.789033E+09 | 0.257777E+09 | 0.531255E+09 | 0.179083E+10 | 0.167312E+09 |
November | 0.639882E+09 | 0.202682E+09 | 0.437200E+09 | 0.121538E+10 | 0.357303E+09 |
December | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.789648E+09 | 0.630072E+09 |
Annual Sum or Average | 0.933782E+10 | 0.278476E+10 | 0.655306E+10 | 0.210884E+11 | 0.350515E+10 |
Minimum of Months | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.789648E+09 | 671973.33 |
Maximum of Months | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.280005E+10 | 0.772923E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.151729E+10 | 0.722993E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137048E+10 | 0.569486E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139760E+10 | 0.491497E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.125252E+10 | 0.306266E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.144994E+10 | 88821217.30 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.147633E+10 | 24365650.43 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.178792E+10 | 1322122.16 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.200182E+10 | 562238.82 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.194970E+10 | 39488293.43 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.211827E+10 | 0.160027E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.192184E+10 | 0.354301E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160505E+10 | 0.615513E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.198488E+11 | 0.337464E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.125252E+10 | 562238.82 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.211827E+10 | 0.722993E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.151728E+10 | 0.722992E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137048E+10 | 0.569486E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139760E+10 | 0.491497E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.125252E+10 | 0.306266E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.144994E+10 | 88821113.05 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.147633E+10 | 24365592.94 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.178792E+10 | 1322114.59 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.200182E+10 | 562235.30 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.194970E+10 | 39488224.88 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.211827E+10 | 0.160026E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.192183E+10 | 0.354301E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160505E+10 | 0.615513E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.198488E+11 | 0.337464E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.125252E+10 | 562235.30 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.211827E+10 | 0.722992E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.151729E+10 | 0.722993E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137048E+10 | 0.569486E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139760E+10 | 0.491497E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.125252E+10 | 0.306266E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.144994E+10 | 88821217.30 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.147633E+10 | 24365650.43 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.178792E+10 | 1322122.16 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.200182E+10 | 562238.82 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.194970E+10 | 39488293.43 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.211827E+10 | 0.160027E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.192184E+10 | 0.354301E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160505E+10 | 0.615513E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.198488E+11 | 0.337464E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.125252E+10 | 562238.82 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.211827E+10 | 0.722993E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.151728E+10 | 0.722992E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137048E+10 | 0.569486E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.139760E+10 | 0.491497E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.125252E+10 | 0.306266E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.144994E+10 | 88821113.05 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.147633E+10 | 24365592.94 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.178792E+10 | 1322114.59 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.200182E+10 | 562235.30 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.194970E+10 | 39488224.88 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.211827E+10 | 0.160026E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.192183E+10 | 0.354301E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160505E+10 | 0.615513E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.198488E+11 | 0.337464E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.125252E+10 | 562235.30 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.211827E+10 | 0.722992E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970107E+09 | 0.456091E+09 | 0.514016E+09 | 0.151723E+10 | 0.722963E+09 |
February | 0.822813E+09 | 0.336567E+09 | 0.486247E+09 | 0.137042E+10 | 0.569463E+09 |
March | 0.749771E+09 | 0.203559E+09 | 0.546212E+09 | 0.139754E+10 | 0.491477E+09 |
April | 0.570364E+09 | 60469395.23 | 0.509895E+09 | 0.125247E+10 | 0.306254E+09 |
May | 0.499253E+09 | 7645558.38 | 0.491607E+09 | 0.144988E+10 | 88817637.41 |
June | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.147627E+10 | 24364668.39 |
July | 0.470168E+09 | 3994997.90 | 0.466173E+09 | 0.178785E+10 | 1322068.87 |
August | 0.545358E+09 | 38640821.54 | 0.506717E+09 | 0.200174E+10 | 562216.16 |
September | 0.695866E+09 | 0.159478E+09 | 0.536388E+09 | 0.194963E+10 | 39486701.88 |
October | 0.941392E+09 | 0.374256E+09 | 0.567135E+09 | 0.211819E+10 | 0.160020E+09 |
November | 0.100504E+10 | 0.484506E+09 | 0.520538E+09 | 0.192176E+10 | 0.354287E+09 |
December | 0.964086E+09 | 0.476229E+09 | 0.487857E+09 | 0.160499E+10 | 0.615488E+09 |
Annual Sum or Average | 0.868924E+10 | 0.260200E+10 | 0.608724E+10 | 0.198480E+11 | 0.337450E+10 |
Minimum of Months | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.125247E+10 | 562216.16 |
Maximum of Months | 0.100504E+10 | 0.484506E+09 | 0.567135E+09 | 0.211819E+10 | 0.722963E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.804470E+09 | 0.910675E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.916442E+09 | 0.727037E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137273E+10 | 0.644912E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168394E+10 | 0.433148E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.235173E+10 | 0.121288E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.246678E+10 | 44340344.29 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.265903E+10 | 4732859.43 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.271081E+10 | 2825896.95 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.222369E+10 | 51422808.99 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.177449E+10 | 0.207442E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.122799E+10 | 0.478772E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.826412E+09 | 0.847895E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210185E+11 | 0.447449E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.804470E+09 | 2825896.95 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.271081E+10 | 0.910675E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.804470E+09 | 0.910675E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.916442E+09 | 0.727037E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137273E+10 | 0.644912E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168394E+10 | 0.433148E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.235173E+10 | 0.121288E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.246678E+10 | 44340344.29 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.265903E+10 | 4732859.43 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.271081E+10 | 2825896.95 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.222369E+10 | 51422808.99 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.177449E+10 | 0.207442E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.122799E+10 | 0.478772E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.826412E+09 | 0.847895E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210185E+11 | 0.447449E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.804470E+09 | 2825896.95 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.271081E+10 | 0.910675E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591682E+09 | 0.169936E+09 | 0.421746E+09 | 0.804456E+09 | 0.910658E+09 |
February | 0.610256E+09 | 0.174020E+09 | 0.436235E+09 | 0.916425E+09 | 0.727023E+09 |
March | 0.800316E+09 | 0.236936E+09 | 0.563381E+09 | 0.137270E+10 | 0.644900E+09 |
April | 0.846395E+09 | 0.237792E+09 | 0.608604E+09 | 0.168391E+10 | 0.433140E+09 |
May | 0.952007E+09 | 0.284974E+09 | 0.667033E+09 | 0.235169E+10 | 0.121285E+09 |
June | 0.952084E+09 | 0.300122E+09 | 0.651962E+09 | 0.246673E+10 | 44339534.10 |
July | 0.902549E+09 | 0.258201E+09 | 0.644348E+09 | 0.265898E+10 | 4732772.95 |
August | 0.925915E+09 | 0.281518E+09 | 0.644397E+09 | 0.271077E+10 | 2825845.32 |
September | 0.852371E+09 | 0.267791E+09 | 0.584581E+09 | 0.222364E+10 | 51421869.38 |
October | 0.782758E+09 | 0.252852E+09 | 0.529905E+09 | 0.177445E+10 | 0.207439E+09 |
November | 0.650984E+09 | 0.212893E+09 | 0.438092E+09 | 0.122797E+10 | 0.478763E+09 |
December | 0.563141E+09 | 0.170228E+09 | 0.392914E+09 | 0.826397E+09 | 0.847880E+09 |
Annual Sum or Average | 0.943046E+10 | 0.284726E+10 | 0.658320E+10 | 0.210181E+11 | 0.447441E+10 |
Minimum of Months | 0.563141E+09 | 0.169936E+09 | 0.392914E+09 | 0.804456E+09 | 2825845.32 |
Maximum of Months | 0.952084E+09 | 0.300122E+09 | 0.667033E+09 | 0.271077E+10 | 0.910658E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.172878E+10 | 0.335027E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.214094E+10 | 0.256529E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.340400E+10 | 0.220193E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.478498E+10 | 0.135551E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.753302E+10 | 0.346080E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.842455E+10 | 80489199.07 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.970621E+10 | 1937140.49 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.956778E+10 | 140229.06 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.699243E+10 | 0.114215E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.517059E+10 | 0.572870E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.316208E+10 | 0.153776E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.192830E+10 | 0.277383E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.645437E+11 | 0.149003E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.172878E+10 | 140229.06 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.970621E+10 | 0.335027E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.242661E+10 | 0.217146E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.266011E+10 | 0.167863E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.377029E+10 | 0.145133E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.523727E+10 | 0.918906E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.735331E+10 | 0.238710E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.752283E+10 | 53449845.48 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.839177E+10 | 1250814.62 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.866486E+10 | 83989.30 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.679927E+10 | 76346376.66 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.548577E+10 | 0.384387E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366113E+10 | 0.101658E+10 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.237665E+10 | 0.180791E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.643499E+11 | 0.979904E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.237665E+10 | 83989.30 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.866486E+10 | 0.217146E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.753784E+10 | 0.351068E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.682347E+10 | 0.272513E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.698762E+10 | 0.236486E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.634333E+10 | 0.144132E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.750698E+10 | 0.351258E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.775089E+10 | 59519034.89 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.941468E+10 | 741386.21 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.105113E+11 | 105232.59 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.100264E+11 | 0.131493E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.107248E+11 | 0.664195E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.960448E+10 | 0.169602E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.800585E+10 | 0.296351E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.101238E+12 | 0.159088E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.634333E+10 | 105232.59 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.107248E+11 | 0.351068E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.250377E+10 | 0.240215E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.284463E+10 | 0.185381E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.423027E+10 | 0.163686E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.519632E+10 | 0.107248E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.716622E+10 | 0.305846E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.760479E+10 | 76793276.09 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.831413E+10 | 3181641.36 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.854706E+10 | 1041547.54 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.682606E+10 | 0.111527E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.547288E+10 | 0.493343E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.381516E+10 | 0.117732E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.264236E+10 | 0.203866E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.651636E+11 | 0.111730E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.250377E+10 | 1041547.54 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.854706E+10 | 0.240215E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.178789E+10 | 0.315178E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.216089E+10 | 0.245958E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.338628E+10 | 0.214855E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.473403E+10 | 0.136067E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.743783E+10 | 0.364343E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.832075E+10 | 89638731.91 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.956870E+10 | 3201089.34 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.944345E+10 | 289985.77 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.689780E+10 | 0.121297E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.511374E+10 | 0.587445E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.314421E+10 | 0.150573E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.196024E+10 | 0.264066E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.639558E+11 | 0.144332E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.178789E+10 | 289985.77 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.956870E+10 | 0.315178E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.248595E+10 | 0.206260E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.268929E+10 | 0.161891E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.377776E+10 | 0.141944E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.522193E+10 | 0.919103E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.730992E+10 | 0.248075E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.747519E+10 | 58234777.11 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.832235E+10 | 1865475.57 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.860630E+10 | 155870.39 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.675614E+10 | 79852029.58 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.546577E+10 | 0.389333E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366591E+10 | 0.996308E+09 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.241534E+10 | 0.173279E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.641919E+11 | 0.952667E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.241534E+10 | 155870.39 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.860630E+10 | 0.206260E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.757049E+10 | 0.335398E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.681911E+10 | 0.263584E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.695478E+10 | 0.231411E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.628857E+10 | 0.144290E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.740999E+10 | 0.368004E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.764421E+10 | 66123572.71 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.927362E+10 | 1404722.61 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.103858E+11 | 229088.91 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.992717E+10 | 0.138530E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.106549E+11 | 0.674290E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.956656E+10 | 0.166593E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.801061E+10 | 0.285901E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.100506E+12 | 0.155203E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.628857E+10 | 229088.91 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.106549E+11 | 0.335398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.251891E+10 | 0.229221E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.284003E+10 | 0.179431E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.420304E+10 | 0.160399E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.515449E+10 | 0.106985E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.710320E+10 | 0.315052E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.753926E+10 | 81476676.50 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.822986E+10 | 4307084.50 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.846806E+10 | 1302438.57 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.676556E+10 | 0.116977E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.543268E+10 | 0.499458E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.379439E+10 | 0.115571E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.264391E+10 | 0.196463E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.646934E+11 | 0.108993E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.251891E+10 | 1302438.57 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.846806E+10 | 0.229221E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 597.96 | 1401.23 | 560.37 | 0.00 | 560.37 | 0.00 | 0.00 |
February | 841.13 | 1189.57 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1234.10 | 897.02 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1789.40 | 575.11 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2702.64 | 169.08 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3109.21 | 60.84 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
July | 3426.09 | 4.16 | 919.26 | 26.49 | 892.78 | 0.00 | 0.00 |
August | 3348.36 | 1.52 | 855.76 | 7.08 | 848.68 | 0.00 | 0.00 |
September | 2533.42 | 77.91 | 779.51 | 0.09 | 779.43 | 0.00 | 0.00 |
October | 1811.09 | 296.47 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1156.16 | 672.37 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 669.47 | 1171.68 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 1941.58 | 539.92 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 597.96 | 1.52 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3426.09 | 1401.23 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 897.88 | 865.74 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1098.27 | 735.64 | 736.46 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1414.36 | 554.91 | 813.49 | 200.50 | 612.99 | 0.00 | 0.00 |
April | 2023.82 | 358.40 | 990.46 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2705.79 | 112.39 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2844.75 | 38.29 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3044.38 | 2.16 | 1011.75 | 291.69 | 720.06 | 0.00 | 0.00 |
August | 3136.30 | 0.75 | 1036.01 | 317.97 | 718.05 | 0.00 | 0.00 |
September | 2549.17 | 50.05 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2005.88 | 187.40 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1406.71 | 413.55 | 740.61 | 234.59 | 506.03 | 0.00 | 0.00 |
December | 884.47 | 705.73 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2006.15 | 333.45 | 888.31 | 264.92 | 623.40 | 0.00 | 0.00 |
Minimum of Months | 884.47 | 0.75 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3136.30 | 865.74 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2832.43 | 1349.66 | 1811.04 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2832.48 | 1177.00 | 1700.64 | 695.64 | 1005.01 | 0.00 | 0.00 |
March | 2609.00 | 917.51 | 1399.71 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2416.11 | 590.79 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2706.71 | 165.81 | 932.03 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2847.84 | 47.00 | 877.76 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3337.65 | 2.47 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3736.95 | 1.05 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3760.97 | 76.17 | 1342.38 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 3954.33 | 298.73 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3707.22 | 683.44 | 1938.81 | 934.65 | 1004.16 | 0.00 | 0.00 |
December | 2996.27 | 1149.02 | 1799.80 | 889.05 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3146.98 | 535.04 | 1377.71 | 412.56 | 965.16 | 0.00 | 0.00 |
Minimum of Months | 2416.11 | 1.05 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 3954.33 | 1349.66 | 1938.81 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 901.06 | 1020.01 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1136.45 | 901.58 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1537.54 | 722.34 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1949.00 | 501.33 | 979.64 | 275.23 | 704.41 | 0.00 | 0.00 |
May | 2634.09 | 135.85 | 1066.33 | 319.20 | 747.13 | 0.00 | 0.00 |
June | 2855.05 | 51.32 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 2978.28 | 5.30 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3036.29 | 3.17 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2573.69 | 59.52 | 986.55 | 309.95 | 676.61 | 0.00 | 0.00 |
October | 1987.54 | 232.35 | 876.76 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1421.28 | 554.13 | 753.46 | 246.41 | 507.06 | 0.00 | 0.00 |
December | 925.64 | 949.70 | 630.77 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 1999.47 | 425.65 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 901.06 | 3.17 | 630.77 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3036.29 | 1020.01 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 645.45 | 1250.85 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 884.98 | 1060.39 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1270.91 | 822.11 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1846.06 | 522.96 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2812.51 | 129.21 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3250.21 | 31.05 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3623.88 | 0.72 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3572.20 | 0.05 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2697.69 | 44.06 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1930.48 | 213.89 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1219.94 | 593.27 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 719.95 | 1035.63 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2046.67 | 472.49 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 645.45 | 0.05 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3623.88 | 1250.85 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 905.99 | 810.73 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1099.58 | 693.88 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1407.66 | 541.86 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2020.55 | 354.52 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2745.41 | 89.12 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2902.33 | 20.62 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3133.13 | 0.47 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3235.09 | 0.03 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2623.17 | 29.45 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2048.15 | 143.51 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1412.47 | 392.20 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 887.34 | 675.00 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2040.52 | 310.73 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 887.34 | 0.03 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3235.09 | 810.73 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2814.31 | 1310.74 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2820.55 | 1126.46 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2608.88 | 882.94 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2447.27 | 556.06 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2802.79 | 131.14 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2990.31 | 22.96 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3515.04 | 0.28 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3924.47 | 0.04 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3868.19 | 50.73 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 4004.18 | 247.98 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3705.43 | 654.33 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2989.04 | 1106.45 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3210.22 | 504.47 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2447.27 | 0.04 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 4004.18 | 1310.74 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 934.80 | 896.86 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1175.85 | 766.29 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1579.40 | 611.13 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 2004.75 | 413.77 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2675.56 | 114.19 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2933.95 | 29.63 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3104.14 | 1.19 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3191.11 | 0.39 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2633.51 | 43.03 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2043.34 | 184.19 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1471.90 | 454.21 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 986.54 | 761.15 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2066.33 | 354.29 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 934.80 | 0.39 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3191.11 | 896.86 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 667.52 | 1176.74 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 893.23 | 1016.69 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1264.29 | 802.17 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1826.40 | 524.95 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2776.97 | 136.03 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3210.17 | 34.58 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3572.54 | 1.20 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3525.78 | 0.11 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2661.19 | 46.80 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1909.25 | 219.33 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1213.04 | 580.91 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 731.87 | 985.91 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2028.03 | 457.67 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 667.52 | 0.11 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3572.54 | 1176.74 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 928.15 | 770.09 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1111.65 | 669.19 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1410.45 | 529.96 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2014.63 | 354.59 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2729.21 | 92.62 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2883.95 | 22.47 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3107.21 | 0.70 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3213.23 | 0.06 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2606.54 | 30.81 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2040.69 | 145.36 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1414.32 | 384.38 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 901.78 | 646.95 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2035.51 | 302.09 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 901.78 | 0.06 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3213.23 | 770.09 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2826.50 | 1252.23 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2818.74 | 1089.55 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2596.62 | 863.99 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2426.14 | 556.67 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2766.57 | 137.40 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2949.16 | 25.51 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3462.37 | 0.52 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3877.60 | 0.09 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3829.93 | 53.45 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 3978.10 | 251.75 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3690.80 | 642.72 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2990.82 | 1067.43 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3187.02 | 492.15 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2426.14 | 0.09 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 3978.10 | 1252.23 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 940.45 | 855.81 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1173.95 | 741.70 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1569.24 | 598.86 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1988.61 | 412.75 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2652.03 | 117.63 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2908.67 | 31.43 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3072.68 | 1.61 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3161.61 | 0.49 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2610.17 | 45.13 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2028.33 | 186.48 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1463.88 | 445.88 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 987.12 | 733.51 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2051.41 | 345.61 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 940.45 | 0.49 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3161.61 | 855.81 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160158E+10 | 0.375305E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.203486E+10 | 0.287781E+10 | 0.155395E+10 | 0.00 | 0.155395E+10 | 0.00 | 0.00 |
March | 0.330540E+10 | 0.240258E+10 | 0.197616E+10 | 0.00 | 0.197616E+10 | 0.00 | 0.00 |
April | 0.463814E+10 | 0.149068E+10 | 0.215466E+10 | 4439570.55 | 0.215022E+10 | 0.00 | 0.00 |
May | 0.723874E+10 | 0.452867E+09 | 0.250611E+10 | 73502551.72 | 0.243260E+10 | 0.00 | 0.00 |
June | 0.805907E+10 | 0.157706E+09 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
July | 0.917644E+10 | 11129448.73 | 0.246215E+10 | 70940604.60 | 0.239121E+10 | 0.00 | 0.00 |
August | 0.896826E+10 | 4067455.32 | 0.229205E+10 | 18957563.92 | 0.227310E+10 | 0.00 | 0.00 |
September | 0.656662E+10 | 0.201954E+09 | 0.202050E+10 | 231530.94 | 0.202027E+10 | 0.00 | 0.00 |
October | 0.485083E+10 | 0.794069E+09 | 0.185084E+10 | 0.00 | 0.185084E+10 | 0.00 | 0.00 |
November | 0.299677E+10 | 0.174278E+10 | 0.153765E+10 | 0.00 | 0.153765E+10 | 0.00 | 0.00 |
December | 0.179310E+10 | 0.313823E+10 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.612298E+11 | 0.170269E+11 | 0.238525E+11 | 0.312233E+09 | 0.235403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160158E+10 | 4067455.32 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.917644E+10 | 0.375305E+10 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240487E+10 | 0.231880E+10 | 0.181004E+10 | 0.547624E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.265693E+10 | 0.177965E+10 | 0.178163E+10 | 0.482831E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.378823E+10 | 0.148628E+10 | 0.217885E+10 | 0.537008E+09 | 0.164185E+10 | 0.00 | 0.00 |
April | 0.524575E+10 | 0.928978E+09 | 0.256727E+10 | 0.748018E+09 | 0.181925E+10 | 0.00 | 0.00 |
May | 0.724720E+10 | 0.301014E+09 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
June | 0.737360E+10 | 99235198.14 | 0.280974E+10 | 0.859248E+09 | 0.195049E+10 | 0.00 | 0.00 |
July | 0.815405E+10 | 5772407.27 | 0.270987E+10 | 0.781250E+09 | 0.192862E+10 | 0.00 | 0.00 |
August | 0.840025E+10 | 2015944.56 | 0.277486E+10 | 0.851642E+09 | 0.192322E+10 | 0.00 | 0.00 |
September | 0.660746E+10 | 0.129741E+09 | 0.252454E+10 | 0.780305E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.537254E+10 | 0.501942E+09 | 0.236713E+10 | 0.773342E+09 | 0.159379E+10 | 0.00 | 0.00 |
November | 0.364619E+10 | 0.107192E+10 | 0.191967E+10 | 0.608054E+09 | 0.131162E+10 | 0.00 | 0.00 |
December | 0.236897E+10 | 0.189024E+10 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.632661E+11 | 0.105156E+11 | 0.280138E+11 | 0.835437E+10 | 0.196594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236897E+10 | 2015944.56 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.840025E+10 | 0.231880E+10 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.758637E+10 | 0.361493E+10 | 0.485069E+10 | 0.228053E+10 | 0.257016E+10 | 0.00 | 0.00 |
February | 0.685234E+10 | 0.284741E+10 | 0.411420E+10 | 0.168289E+10 | 0.243131E+10 | 0.00 | 0.00 |
March | 0.698794E+10 | 0.245746E+10 | 0.374897E+10 | 0.101783E+10 | 0.273115E+10 | 0.00 | 0.00 |
April | 0.626255E+10 | 0.153132E+10 | 0.285191E+10 | 0.302357E+09 | 0.254956E+10 | 0.00 | 0.00 |
May | 0.724964E+10 | 0.444102E+09 | 0.249634E+10 | 38229006.22 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.738159E+10 | 0.121827E+09 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
July | 0.893955E+10 | 6610542.36 | 0.235092E+10 | 19975623.99 | 0.233094E+10 | 0.00 | 0.00 |
August | 0.100090E+11 | 2811164.39 | 0.272688E+10 | 0.193210E+09 | 0.253367E+10 | 0.00 | 0.00 |
September | 0.974844E+10 | 0.197440E+09 | 0.347944E+10 | 0.797415E+09 | 0.268202E+10 | 0.00 | 0.00 |
October | 0.105913E+11 | 0.800126E+09 | 0.470711E+10 | 0.187134E+10 | 0.283577E+10 | 0.00 | 0.00 |
November | 0.960910E+10 | 0.177149E+10 | 0.502538E+10 | 0.242261E+10 | 0.260278E+10 | 0.00 | 0.00 |
December | 0.802520E+10 | 0.307754E+10 | 0.482058E+10 | 0.238122E+10 | 0.243936E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.992430E+11 | 0.168731E+11 | 0.434476E+11 | 0.130104E+11 | 0.304372E+11 | 0.00 | 0.00 |
Minimum of Months | 0.626255E+10 | 2811164.39 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105913E+11 | 0.361493E+10 | 0.502538E+10 | 0.242261E+10 | 0.283577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241340E+10 | 0.273201E+10 | 0.177507E+10 | 0.509815E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.274931E+10 | 0.218110E+10 | 0.183079E+10 | 0.522068E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.411816E+10 | 0.193472E+10 | 0.240098E+10 | 0.710816E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.505180E+10 | 0.129943E+10 | 0.253922E+10 | 0.713384E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.705515E+10 | 0.363860E+09 | 0.285606E+10 | 0.854933E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.740028E+10 | 0.133020E+09 | 0.285629E+10 | 0.900378E+09 | 0.195591E+10 | 0.00 | 0.00 |
July | 0.797704E+10 | 14198491.81 | 0.270768E+10 | 0.774614E+09 | 0.193307E+10 | 0.00 | 0.00 |
August | 0.813239E+10 | 8477639.23 | 0.277778E+10 | 0.844564E+09 | 0.193322E+10 | 0.00 | 0.00 |
September | 0.667102E+10 | 0.154267E+09 | 0.255715E+10 | 0.803382E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.532343E+10 | 0.622324E+09 | 0.234830E+10 | 0.758567E+09 | 0.158974E+10 | 0.00 | 0.00 |
November | 0.368396E+10 | 0.143631E+10 | 0.195298E+10 | 0.638686E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.247922E+10 | 0.254367E+10 | 0.168944E+10 | 0.510689E+09 | 0.117876E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.630551E+11 | 0.134234E+11 | 0.282917E+11 | 0.854189E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241340E+10 | 8477639.23 | 0.168944E+10 | 0.509815E+09 | 0.117876E+10 | 0.00 | 0.00 |
Maximum of Months | 0.813239E+10 | 0.273201E+10 | 0.285629E+10 | 0.900378E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172878E+10 | 0.335027E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.214094E+10 | 0.256529E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.340400E+10 | 0.220193E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.478498E+10 | 0.135551E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.753302E+10 | 0.346080E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.842455E+10 | 80489199.07 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.970621E+10 | 1937140.49 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.956778E+10 | 140229.06 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.699243E+10 | 0.114215E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.517059E+10 | 0.572870E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.316208E+10 | 0.153776E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.192830E+10 | 0.277383E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.645437E+11 | 0.149003E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.172878E+10 | 140229.06 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.970621E+10 | 0.335027E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.242661E+10 | 0.217146E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.266011E+10 | 0.167863E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.377029E+10 | 0.145133E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.523727E+10 | 0.918906E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.735331E+10 | 0.238710E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.752283E+10 | 53449845.48 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.839177E+10 | 1250814.62 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.866486E+10 | 83989.30 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.679927E+10 | 76346376.66 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.548577E+10 | 0.384387E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366113E+10 | 0.101658E+10 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.237665E+10 | 0.180791E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.643499E+11 | 0.979904E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237665E+10 | 83989.30 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866486E+10 | 0.217146E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.753784E+10 | 0.351068E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.682347E+10 | 0.272513E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.698762E+10 | 0.236486E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.634333E+10 | 0.144132E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.750698E+10 | 0.351258E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.775089E+10 | 59519034.89 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.941468E+10 | 741386.21 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.105113E+11 | 105232.59 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.100264E+11 | 0.131493E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.107248E+11 | 0.664195E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.960448E+10 | 0.169602E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.800585E+10 | 0.296351E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101238E+12 | 0.159088E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634333E+10 | 105232.59 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107248E+11 | 0.351068E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250377E+10 | 0.240215E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.284463E+10 | 0.185381E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.423027E+10 | 0.163686E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.519632E+10 | 0.107248E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.716622E+10 | 0.305846E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.760479E+10 | 76793276.09 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.831413E+10 | 3181641.36 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.854706E+10 | 1041547.54 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.682606E+10 | 0.111527E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.547288E+10 | 0.493343E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.381516E+10 | 0.117732E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.264236E+10 | 0.203866E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.651636E+11 | 0.111730E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250377E+10 | 1041547.54 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.854706E+10 | 0.240215E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178789E+10 | 0.315178E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.216089E+10 | 0.245958E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.338628E+10 | 0.214855E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.473403E+10 | 0.136067E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.743783E+10 | 0.364343E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.832075E+10 | 89638731.91 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.956870E+10 | 3201089.34 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.944345E+10 | 289985.77 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.689780E+10 | 0.121297E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.511374E+10 | 0.587445E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.314421E+10 | 0.150573E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.196024E+10 | 0.264066E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.639558E+11 | 0.144332E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.178789E+10 | 289985.77 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.956870E+10 | 0.315178E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248595E+10 | 0.206260E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.268929E+10 | 0.161891E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.377776E+10 | 0.141944E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.522193E+10 | 0.919103E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.730992E+10 | 0.248075E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.747519E+10 | 58234777.11 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.832235E+10 | 1865475.57 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.860630E+10 | 155870.39 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.675614E+10 | 79852029.58 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.546577E+10 | 0.389333E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366591E+10 | 0.996308E+09 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.241534E+10 | 0.173279E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.641919E+11 | 0.952667E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241534E+10 | 155870.39 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.860630E+10 | 0.206260E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.757049E+10 | 0.335398E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.681911E+10 | 0.263584E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.695478E+10 | 0.231411E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.628857E+10 | 0.144290E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.740999E+10 | 0.368004E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.764421E+10 | 66123572.71 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.927362E+10 | 1404722.61 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.103858E+11 | 229088.91 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.992717E+10 | 0.138530E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.106549E+11 | 0.674290E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.956656E+10 | 0.166593E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.801061E+10 | 0.285901E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100506E+12 | 0.155203E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.628857E+10 | 229088.91 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106549E+11 | 0.335398E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251891E+10 | 0.229221E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.284003E+10 | 0.179431E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.420304E+10 | 0.160399E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.515449E+10 | 0.106985E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.710320E+10 | 0.315052E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.753926E+10 | 81476676.50 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.822986E+10 | 4307084.50 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.846806E+10 | 1302438.57 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.676556E+10 | 0.116977E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.543268E+10 | 0.499458E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.379439E+10 | 0.115571E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.264391E+10 | 0.196463E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646934E+11 | 0.108993E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251891E+10 | 1302438.57 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.846806E+10 | 0.229221E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.283629E+11 | -0.279220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440844857.6 | 60.05 | 0.00 | 0.00 |
February | 0.250765E+11 | -0.246830E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -393419875.9 | 60.05 | 0.00 | 0.00 |
March | 0.274739E+11 | -0.270429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -430997366.9 | 60.05 | 0.00 | 0.00 |
April | 0.225123E+11 | -0.221129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -399470473.4 | 60.05 | 0.00 | 0.00 |
May | 0.215037E+11 | -0.211188E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -384876635.2 | 60.05 | 0.00 | 0.00 |
June | 0.194849E+11 | -0.191167E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -368182956.6 | 60.05 | 0.00 | 0.00 |
July | 0.180085E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -372392831.1 | 60.05 | 0.00 | 0.00 |
August | 0.205235E+11 | -0.201569E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -366618046.3 | 60.05 | 0.00 | 0.00 |
September | 0.205189E+11 | -0.201605E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -358460085.9 | 60.05 | 0.00 | 0.00 |
October | 0.236600E+11 | -0.232841E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -375995874.4 | 60.05 | 0.00 | 0.00 |
November | 0.256105E+11 | -0.252094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -401069944.8 | 60.05 | 0.00 | 0.00 |
December | 0.271863E+11 | -0.267502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -436176481.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.279922E+12 | -0.275193E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.472851E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.180085E+11 | -0.279220E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -440844857.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.283629E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -358460085.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4187.85 | 34.38 | 311.00 | 293.00 | 1081.44 | 25.75 | 306.67 | 280.33 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2168.98 | 26.03 | 160.50 | 274.83 | 966.54 | 21.70 | 215.67 | 244.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1604.46 | 20.06 | 41.33 | 314.33 | 827.56 | 21.23 | 242.50 | 277.17 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1258.39 | 18.99 | 0.67 | 322.83 | 663.56 | 20.27 | 226.17 | 284.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1073.66 | 18.93 | 0.00 | 349.67 | 586.61 | 20.25 | 186.33 | 304.17 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 1029.03 | 18.86 | 0.00 | 344.33 | 571.46 | 20.21 | 187.33 | 298.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1080.69 | 18.79 | 0.00 | 345.17 | 592.75 | 20.13 | 219.83 | 304.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1265.49 | 19.26 | 13.67 | 343.17 | 675.68 | 20.59 | 261.50 | 304.00 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1577.57 | 20.02 | 71.00 | 318.67 | 826.79 | 21.36 | 258.00 | 284.83 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2096.10 | 21.89 | 116.83 | 316.67 | 992.90 | 22.22 | 272.33 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3529.96 | 32.29 | 257.33 | 298.17 | 1121.01 | 25.39 | 312.67 | 281.83 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4175.93 | 34.74 | 308.17 | 289.00 | 1154.67 | 26.89 | 301.00 | 275.17 |
Annual Sum or Average | 4323.33 | 0.51 | 1994.77 | 23.19 | 1280.50 | 3809.83 | 819.08 | 21.99 | 2990.00 | 3426.67 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1029.03 | 18.79 | 0.00 | 274.83 | 571.46 | 20.13 | 186.33 | 244.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4187.85 | 34.74 | 311.00 | 349.67 | 1154.67 | 26.89 | 312.67 | 304.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1543.18 | 23.78 | 112.00 | 275.33 | 805.53 | 23.84 | 173.00 | 236.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1668.33 | 23.48 | 102.67 | 263.33 | 715.93 | 22.41 | 155.00 | 227.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1572.14 | 22.75 | 97.50 | 309.17 | 797.96 | 23.01 | 167.50 | 271.33 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1825.70 | 22.64 | 109.33 | 320.50 | 929.51 | 22.97 | 150.83 | 284.33 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2071.31 | 23.40 | 129.50 | 359.00 | 877.24 | 22.68 | 159.00 | 321.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 1995.88 | 23.32 | 126.50 | 353.33 | 866.27 | 22.77 | 164.67 | 318.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1880.79 | 23.06 | 123.67 | 348.33 | 828.03 | 22.45 | 167.33 | 312.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1928.76 | 22.77 | 114.17 | 341.50 | 860.57 | 22.16 | 173.50 | 307.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1926.22 | 23.59 | 107.00 | 311.50 | 986.87 | 23.89 | 183.67 | 285.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1793.52 | 23.59 | 107.00 | 305.33 | 921.91 | 23.79 | 194.17 | 275.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1550.71 | 23.61 | 93.83 | 279.17 | 794.12 | 23.73 | 179.17 | 244.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1276.48 | 22.56 | 86.00 | 269.33 | 660.28 | 22.67 | 161.33 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1770.70 | 23.20 | 1309.17 | 3735.83 | 841.75 | 23.01 | 2029.17 | 3310.50 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1276.48 | 22.56 | 86.00 | 263.33 | 660.28 | 22.16 | 150.83 | 225.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2071.31 | 23.78 | 129.50 | 359.00 | 986.87 | 23.89 | 194.17 | 321.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:30 | 604.68 | 16.87 | 0.00 | 260.33 | 347.02 | 18.18 | 0.00 | 179.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 687.65 | 17.71 | 0.00 | 253.33 | 393.69 | 19.02 | 0.00 | 192.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 801.27 | 18.34 | 0.00 | 306.17 | 452.43 | 19.60 | 1.50 | 254.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 917.28 | 18.58 | 0.00 | 327.00 | 510.74 | 19.81 | 75.83 | 286.50 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1080.04 | 19.60 | 3.50 | 368.50 | 592.15 | 20.81 | 186.00 | 333.50 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:40 | 1193.52 | 22.45 | 96.17 | 366.00 | 641.39 | 21.25 | 236.00 | 332.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1154.75 | 20.50 | 41.00 | 358.50 | 625.87 | 21.84 | 252.83 | 327.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1047.22 | 19.26 | 0.17 | 350.17 | 581.18 | 20.57 | 187.00 | 315.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 915.14 | 18.96 | 0.00 | 317.00 | 520.50 | 20.27 | 69.67 | 275.33 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:40 | 758.30 | 18.10 | 0.00 | 300.00 | 441.46 | 19.43 | 1.50 | 247.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:00 | 656.68 | 17.78 | 0.00 | 262.33 | 383.67 | 19.16 | 0.00 | 198.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 586.35 | 16.99 | 0.00 | 250.00 | 336.97 | 18.33 | 0.00 | 160.17 |
Annual Sum or Average | 4323.33 | 0.52 | 886.27 | 18.88 | 140.83 | 3719.33 | 495.31 | 19.95 | 1010.33 | 3104.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 586.35 | 16.87 | 0.00 | 250.00 | 336.97 | 18.18 | 0.00 | 160.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1193.52 | 22.45 | 96.17 | 368.50 | 641.39 | 21.84 | 252.83 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1497.00 | 23.48 | 108.17 | 274.33 | 774.48 | 23.58 | 175.50 | 235.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1468.10 | 22.28 | 76.33 | 262.33 | 736.75 | 22.43 | 159.00 | 223.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:00 | 1683.72 | 22.95 | 96.67 | 309.83 | 849.71 | 23.13 | 176.00 | 273.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1701.17 | 19.62 | 55.00 | 324.67 | 878.74 | 19.49 | 116.83 | 288.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1784.67 | 17.87 | 0.00 | 350.17 | 921.79 | 19.83 | 119.50 | 315.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1898.82 | 18.06 | 0.00 | 345.83 | 974.28 | 20.01 | 130.00 | 313.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1818.30 | 18.03 | 3.67 | 348.17 | 822.90 | 19.77 | 130.50 | 310.33 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1856.27 | 20.11 | 59.83 | 342.67 | 953.72 | 20.16 | 142.83 | 309.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1797.39 | 22.21 | 87.17 | 318.17 | 920.63 | 22.58 | 174.33 | 287.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1856.26 | 23.81 | 110.33 | 303.33 | 954.88 | 24.01 | 192.50 | 273.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1614.74 | 24.02 | 99.50 | 278.33 | 828.72 | 24.12 | 180.83 | 245.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1411.20 | 23.62 | 101.83 | 269.67 | 723.64 | 23.69 | 172.67 | 227.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1712.02 | 21.14 | 798.50 | 3727.50 | 867.49 | 21.75 | 1870.50 | 3303.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1411.20 | 17.87 | 0.00 | 262.33 | 723.64 | 19.49 | 116.83 | 223.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1898.82 | 24.02 | 110.33 | 350.17 | 974.28 | 24.12 | 192.50 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4207.91 | 33.84 | 310.17 | 293.00 | 1147.14 | 21.84 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2187.98 | 22.15 | 140.67 | 274.83 | 1028.84 | 16.93 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1621.56 | 13.67 | 5.00 | 315.00 | 880.29 | 16.86 | 0.00 | 280.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1273.61 | 13.01 | 0.00 | 323.50 | 705.34 | 16.29 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1088.63 | 13.09 | 0.00 | 350.00 | 623.76 | 16.45 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1044.00 | 12.93 | 0.00 | 344.33 | 607.73 | 16.34 | 0.00 | 304.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1095.74 | 12.76 | 0.00 | 345.17 | 630.14 | 16.11 | 0.00 | 308.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1281.34 | 13.32 | 0.00 | 343.83 | 718.02 | 16.66 | 0.00 | 308.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1597.22 | 13.91 | 0.00 | 318.83 | 879.22 | 17.30 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2125.39 | 15.99 | 34.50 | 317.50 | 1057.25 | 18.02 | 10.50 | 291.17 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3549.26 | 30.55 | 255.33 | 298.33 | 1191.68 | 21.59 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4186.97 | 34.28 | 305.83 | 289.50 | 1220.80 | 23.26 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2012.28 | 18.47 | 1051.50 | 3813.83 | 870.36 | 17.97 | 291.33 | 3469.83 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1044.00 | 12.76 | 0.00 | 274.83 | 607.73 | 16.11 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4207.91 | 34.28 | 310.17 | 350.00 | 1220.80 | 23.26 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1568.52 | 21.25 | 111.83 | 276.17 | 840.23 | 21.89 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1697.93 | 20.78 | 102.33 | 263.67 | 753.19 | 20.04 | 47.17 | 231.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1609.16 | 19.71 | 97.33 | 310.33 | 838.78 | 20.65 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1848.78 | 19.73 | 109.33 | 321.17 | 973.06 | 20.70 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2087.84 | 19.65 | 119.33 | 359.83 | 924.35 | 20.19 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2026.25 | 20.36 | 125.83 | 354.50 | 912.39 | 20.26 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1904.55 | 19.24 | 114.17 | 348.83 | 873.59 | 19.89 | 61.83 | 315.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1948.28 | 19.86 | 113.67 | 342.33 | 907.08 | 19.63 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1959.49 | 20.70 | 106.83 | 311.83 | 1033.19 | 21.66 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1830.29 | 20.66 | 104.67 | 306.33 | 964.93 | 21.65 | 75.83 | 278.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1567.55 | 19.85 | 84.33 | 279.33 | 832.76 | 21.60 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1298.71 | 19.72 | 85.17 | 270.67 | 692.34 | 20.52 | 55.67 | 231.50 |
Annual Sum or Average | 4323.33 | 0.52 | 1796.81 | 20.10 | 1274.83 | 3745.00 | 883.97 | 20.69 | 797.67 | 3358.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1298.71 | 19.24 | 84.33 | 263.67 | 692.34 | 19.63 | 47.17 | 231.00 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2087.84 | 21.25 | 125.83 | 359.83 | 1033.19 | 21.89 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.13 | 11.11 | 0.00 | 260.50 | 368.96 | 14.50 | 0.00 | 193.17 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 698.63 | 11.86 | 0.00 | 253.67 | 418.67 | 15.30 | 0.00 | 201.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 814.23 | 12.56 | 0.00 | 306.50 | 481.19 | 15.93 | 0.00 | 260.50 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 931.92 | 12.94 | 0.00 | 327.33 | 543.18 | 16.24 | 0.00 | 291.17 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1097.14 | 13.76 | 2.83 | 368.67 | 629.82 | 17.15 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1211.82 | 17.75 | 77.33 | 366.33 | 685.81 | 18.84 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1172.02 | 14.89 | 26.83 | 359.00 | 665.11 | 18.16 | 27.17 | 331.00 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1063.49 | 13.49 | 0.00 | 350.50 | 617.87 | 16.89 | 0.00 | 319.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 929.92 | 13.46 | 0.00 | 317.33 | 553.57 | 16.82 | 0.00 | 280.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 770.75 | 12.66 | 0.00 | 300.67 | 469.62 | 16.06 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.01 | 12.11 | 0.00 | 263.17 | 408.02 | 15.62 | 0.00 | 209.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.54 | 0.00 | 174.33 |
Annual Sum or Average | 4323.33 | 0.52 | 900.17 | 13.27 | 107.00 | 3724.67 | 527.04 | 16.45 | 62.50 | 3192.67 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.50 | 0.00 | 174.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1211.82 | 17.75 | 77.33 | 368.67 | 685.81 | 18.84 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1522.02 | 20.93 | 108.17 | 275.83 | 808.86 | 21.62 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1498.38 | 19.17 | 76.33 | 263.00 | 774.95 | 20.04 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1723.73 | 19.87 | 96.67 | 311.17 | 893.37 | 20.74 | 65.67 | 277.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1722.67 | 15.98 | 55.00 | 325.67 | 921.42 | 16.37 | 0.00 | 292.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1808.02 | 13.42 | 0.00 | 351.00 | 967.92 | 16.65 | 0.00 | 320.67 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1930.46 | 13.59 | 0.00 | 346.50 | 1020.90 | 16.84 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1844.22 | 13.63 | 3.67 | 349.33 | 868.43 | 16.63 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1874.15 | 16.45 | 59.83 | 342.83 | 1000.35 | 17.08 | 5.50 | 312.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1823.98 | 19.10 | 86.83 | 318.00 | 966.96 | 20.14 | 57.33 | 289.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1894.84 | 21.12 | 110.33 | 304.50 | 997.79 | 21.90 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1642.75 | 21.30 | 98.67 | 279.00 | 867.81 | 22.05 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1434.89 | 20.94 | 101.83 | 270.17 | 757.06 | 21.66 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1739.59 | 17.70 | 797.33 | 3737.00 | 910.00 | 19.12 | 473.33 | 3354.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1434.89 | 13.42 | 0.00 | 263.00 | 757.06 | 16.37 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1930.46 | 21.30 | 110.33 | 351.00 | 1020.90 | 22.05 | 79.33 | 320.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4210.55 | 33.83 | 310.17 | 293.00 | 1149.14 | 21.83 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2190.99 | 22.13 | 140.67 | 274.83 | 1030.70 | 16.91 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1624.28 | 13.64 | 5.00 | 315.00 | 881.86 | 16.84 | 0.00 | 281.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1275.69 | 12.98 | 0.00 | 323.50 | 706.54 | 16.28 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1090.23 | 13.06 | 0.00 | 350.17 | 624.74 | 16.43 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1045.45 | 12.90 | 0.00 | 344.33 | 608.65 | 16.33 | 0.00 | 304.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1097.32 | 12.73 | 0.00 | 345.33 | 631.12 | 16.09 | 0.00 | 308.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1283.33 | 13.29 | 0.00 | 343.83 | 719.21 | 16.64 | 0.00 | 308.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1599.80 | 13.88 | 0.00 | 318.83 | 880.74 | 17.29 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2128.39 | 15.96 | 34.50 | 317.50 | 1059.10 | 18.01 | 10.50 | 291.50 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3552.16 | 30.54 | 255.33 | 298.33 | 1193.74 | 21.58 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4189.43 | 34.27 | 305.83 | 289.50 | 1222.82 | 23.25 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2014.57 | 18.44 | 1051.50 | 3814.17 | 871.84 | 17.95 | 291.33 | 3471.00 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1045.45 | 12.73 | 0.00 | 274.83 | 608.65 | 16.09 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4210.55 | 34.27 | 310.17 | 350.17 | 1222.82 | 23.25 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1569.87 | 21.22 | 111.83 | 276.17 | 841.33 | 21.88 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1699.51 | 20.75 | 102.33 | 263.67 | 754.37 | 20.03 | 47.17 | 231.33 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1611.04 | 19.68 | 97.33 | 310.33 | 840.02 | 20.64 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1850.67 | 19.70 | 109.33 | 321.17 | 974.33 | 20.68 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2089.68 | 19.62 | 119.33 | 359.83 | 925.65 | 20.18 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2028.13 | 20.33 | 125.83 | 354.50 | 913.70 | 20.24 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1906.50 | 19.22 | 114.17 | 348.83 | 874.91 | 19.88 | 61.83 | 316.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1950.27 | 19.83 | 113.67 | 342.33 | 908.46 | 19.62 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1961.44 | 20.68 | 106.83 | 312.00 | 1034.60 | 21.65 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1831.86 | 20.63 | 104.67 | 306.33 | 966.24 | 21.64 | 75.83 | 278.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1568.95 | 19.83 | 84.33 | 279.33 | 833.93 | 21.59 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1299.98 | 19.70 | 85.17 | 270.67 | 693.38 | 20.50 | 55.67 | 231.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1798.54 | 20.07 | 1274.83 | 3745.17 | 885.23 | 20.67 | 797.67 | 3359.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1299.98 | 19.22 | 84.33 | 263.67 | 693.38 | 19.62 | 47.17 | 231.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2089.68 | 21.22 | 125.83 | 359.83 | 1034.60 | 21.88 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.83 | 11.08 | 0.00 | 260.50 | 369.50 | 14.48 | 0.00 | 193.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 699.46 | 11.83 | 0.00 | 253.67 | 419.29 | 15.28 | 0.00 | 201.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 815.27 | 12.53 | 0.00 | 306.67 | 481.92 | 15.92 | 0.00 | 260.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 933.17 | 12.91 | 0.00 | 327.33 | 544.02 | 16.23 | 0.00 | 291.50 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1098.62 | 13.73 | 2.83 | 368.67 | 630.80 | 17.14 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1213.48 | 17.72 | 77.33 | 366.33 | 686.90 | 18.82 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1173.65 | 14.86 | 26.83 | 359.00 | 666.18 | 18.15 | 27.17 | 331.17 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1064.89 | 13.46 | 0.00 | 350.50 | 618.83 | 16.87 | 0.00 | 319.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 931.04 | 13.43 | 0.00 | 317.33 | 554.39 | 16.80 | 0.00 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 771.59 | 12.63 | 0.00 | 300.67 | 470.28 | 16.05 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.71 | 12.08 | 0.00 | 263.17 | 408.59 | 15.61 | 0.00 | 209.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.52 | 0.00 | 174.83 |
Annual Sum or Average | 4323.33 | 0.52 | 901.32 | 13.24 | 107.00 | 3724.83 | 527.85 | 16.43 | 62.50 | 3194.83 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.48 | 0.00 | 174.83 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1213.48 | 17.72 | 77.33 | 368.67 | 686.90 | 18.82 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1523.37 | 20.91 | 108.17 | 276.00 | 809.96 | 21.61 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1499.99 | 19.14 | 76.33 | 263.00 | 776.15 | 20.03 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1715.05 | 18.72 | 85.83 | 310.17 | 894.66 | 20.72 | 65.67 | 278.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1724.59 | 15.95 | 55.00 | 326.00 | 922.72 | 16.36 | 0.00 | 292.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1809.90 | 13.39 | 0.00 | 351.00 | 969.23 | 16.64 | 0.00 | 320.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1932.40 | 13.56 | 0.00 | 346.83 | 1022.24 | 16.82 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1846.21 | 13.60 | 3.67 | 349.33 | 869.78 | 16.61 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1876.18 | 16.42 | 59.83 | 343.00 | 1001.77 | 17.06 | 5.50 | 312.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1826.01 | 19.07 | 86.83 | 318.17 | 968.39 | 20.13 | 57.33 | 289.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1896.53 | 21.09 | 110.33 | 304.50 | 999.08 | 21.89 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1644.13 | 21.27 | 98.67 | 279.17 | 868.98 | 22.04 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1436.18 | 20.92 | 101.83 | 270.17 | 758.12 | 21.65 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1740.49 | 17.58 | 786.50 | 3737.33 | 911.28 | 19.10 | 473.33 | 3355.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1436.18 | 13.39 | 0.00 | 263.00 | 758.12 | 16.36 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1932.40 | 21.27 | 110.33 | 351.00 | 1022.24 | 22.04 | 79.33 | 320.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21167735.28 | 1663.99 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 397851.32 | 280.77 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21565586.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21167735.28 | 1663.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4443501.34 | 944.59 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4443501.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4443501.34 | 944.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.717690E+11 | 0.688605E+11 | 230239.10 | 30-JAN-05:12 | 161009.77 | 0.57 |
February | 0.00 | 0.00 | 0.889395E+11 | 0.827802E+11 | 249873.37 | 09-FEB-05:11 | 167906.21 | 0.61 |
March | 0.00 | 0.00 | 0.135242E+12 | 0.126787E+12 | 223715.58 | 29-MAR-04:12 | 152264.23 | 0.72 |
April | 0.00 | 0.00 | 0.184042E+12 | 0.163733E+12 | 241308.61 | 18-APR-03:12 | 171599.89 | 0.84 |
May | 0.00 | 0.00 | 0.266090E+12 | 0.226514E+12 | 305174.78 | 30-MAY-03:02 | 195003.39 | 0.87 |
June | 0.00 | 0.00 | 0.328941E+12 | 0.249406E+12 | 317255.87 | 27-JUN-03:12 | 191492.08 | 0.89 |
July | 0.00 | 0.00 | 0.387119E+12 | 0.278475E+12 | 332307.74 | 24-JUL-03:02 | 206633.20 | 0.88 |
August | 0.00 | 0.00 | 0.429391E+12 | 0.309129E+12 | 333916.89 | 08-AUG-03:02 | 197571.11 | 0.89 |
September | 0.00 | 0.00 | 0.337955E+12 | 0.241654E+12 | 324883.45 | 10-SEP-19:42 | 202729.16 | 0.88 |
October | 0.00 | 0.00 | 0.282226E+12 | 0.222024E+12 | 312317.07 | 01-OCT-19:03 | 196743.23 | 0.86 |
November | 0.00 | 0.00 | 0.180683E+12 | 0.153952E+12 | 259536.42 | 10-NOV-06:02 | 169301.49 | 0.80 |
December | 0.00 | 0.00 | 0.114528E+12 | 0.102744E+12 | 219120.93 | 12-DEC-05:22 | 156226.99 | 0.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.280693E+13 | 0.222606E+13 | 0.79 | |||
Minimum of Months | 0.00 | 0.00 | 0.717690E+11 | 0.688605E+11 | 219120.93 | 152264.23 | 0.57 | |
Maximum of Months | 0.00 | 0.00 | 0.429391E+12 | 0.309129E+12 | 333916.89 | 206633.20 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.512018E+12 | 0.488755E+12 | 1747796.97 | 30-JAN-06:03 | 1162055.63 | 0.54 |
February | 0.00 | 0.00 | 0.616548E+12 | 0.567385E+12 | 2077401.98 | 09-FEB-06:02 | 1399060.83 | 0.57 |
March | 0.00 | 0.00 | 0.931949E+12 | 0.866400E+12 | 2061821.12 | 01-MAR-06:02 | 1373087.89 | 0.60 |
April | 0.00 | 0.00 | 0.124459E+13 | 0.109279E+13 | 2215879.66 | 20-APR-04:12 | 1466352.85 | 0.66 |
May | 0.00 | 0.00 | 0.201440E+13 | 0.165376E+13 | 2854493.67 | 30-MAY-05:02 | 1731566.44 | 0.81 |
June | 0.00 | 0.00 | 0.257852E+13 | 0.180421E+13 | 2921678.04 | 20-JUN-05:02 | 1701421.28 | 0.87 |
July | 0.00 | 0.00 | 0.307243E+13 | 0.200344E+13 | 3200017.57 | 30-JUL-16:22 | 1570890.33 | 0.87 |
August | 0.00 | 0.00 | 0.332682E+13 | 0.214972E+13 | 3074188.12 | 08-AUG-05:01 | 1684915.69 | 0.88 |
September | 0.00 | 0.00 | 0.265183E+13 | 0.172078E+13 | 3138918.52 | 10-SEP-16:52 | 1452971.79 | 0.84 |
October | 0.00 | 0.00 | 0.195468E+13 | 0.144047E+13 | 2787408.11 | 07-OCT-05:02 | 1632993.21 | 0.73 |
November | 0.00 | 0.00 | 0.124214E+13 | 0.102519E+13 | 2439139.26 | 10-NOV-06:02 | 1535293.23 | 0.62 |
December | 0.00 | 0.00 | 0.714591E+12 | 0.630447E+12 | 2055199.71 | 12-DEC-06:02 | 1451221.48 | 0.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.208605E+14 | 0.154433E+14 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.512018E+12 | 0.488755E+12 | 1747796.97 | 1162055.63 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.332682E+13 | 0.214972E+13 | 3200017.57 | 1731566.44 | 0.88 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.463729E+11 | 0.440827E+11 | 149644.54 | 30-JAN-06:03 | 96424.40 | 0.53 |
February | 0.00 | 0.00 | 0.594816E+11 | 0.545864E+11 | 214846.15 | 06-FEB-06:02 | 150140.72 | 0.56 |
March | 0.00 | 0.00 | 0.937424E+11 | 0.871785E+11 | 218983.38 | 29-MAR-05:02 | 146441.50 | 0.59 |
April | 0.00 | 0.00 | 0.129249E+12 | 0.114063E+12 | 258535.71 | 30-APR-14:51 | 145254.59 | 0.66 |
May | 0.00 | 0.00 | 0.214606E+12 | 0.178471E+12 | 316127.51 | 30-MAY-05:02 | 193844.75 | 0.81 |
June | 0.00 | 0.00 | 0.273572E+12 | 0.195972E+12 | 317111.49 | 04-JUN-16:51 | 170944.87 | 0.87 |
July | 0.00 | 0.00 | 0.325921E+12 | 0.219121E+12 | 347593.05 | 30-JUL-16:22 | 177796.74 | 0.87 |
August | 0.00 | 0.00 | 0.351643E+12 | 0.234165E+12 | 339301.45 | 08-AUG-05:01 | 188614.78 | 0.88 |
September | 0.00 | 0.00 | 0.277131E+12 | 0.184172E+12 | 336949.84 | 10-SEP-17:22 | 161781.03 | 0.84 |
October | 0.00 | 0.00 | 0.200945E+12 | 0.149621E+12 | 301834.98 | 07-OCT-05:02 | 179286.22 | 0.73 |
November | 0.00 | 0.00 | 0.123136E+12 | 0.101640E+12 | 245000.89 | 10-NOV-06:02 | 152194.29 | 0.62 |
December | 0.00 | 0.00 | 0.672757E+11 | 0.590095E+11 | 218591.53 | 11-DEC-06:02 | 147248.04 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.216308E+13 | 0.162208E+13 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.463729E+11 | 0.440827E+11 | 149644.54 | 96424.40 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.351643E+12 | 0.234165E+12 | 347593.05 | 193844.75 | 0.88 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.674921E+11 | 0.652194E+11 | 251523.49 | 30-JAN-20:32 | 78927.51 | 0.51 |
February | 0.00 | 0.00 | 0.586168E+11 | 0.554347E+11 | 264825.47 | 08-FEB-06:52 | 79072.78 | 0.44 |
March | 0.00 | 0.00 | 0.634981E+11 | 0.576037E+11 | 269233.11 | 29-MAR-04:05 | 76087.35 | 0.37 |
April | 0.00 | 0.00 | 0.403935E+11 | 0.322722E+11 | 282098.88 | 30-APR-03:03 | 75810.64 | 0.17 |
May | 0.00 | 0.00 | 0.698620E+10 | 0.535787E+10 | 186092.57 | 01-MAY-04:22 | 102655.08 | 0.02 |
June | 0.00 | 0.00 | 0.702341E+10 | 0.522461E+10 | 270711.11 | 22-JUN-07:53 | 73490.96 | 0.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135038E+11 | 0.106736E+11 | 288096.54 | 29-OCT-02:33 | 79136.25 | 0.03 |
November | 0.00 | 0.00 | 0.668507E+11 | 0.552551E+11 | 277409.68 | 04-NOV-04:23 | 77492.11 | 0.26 |
December | 0.00 | 0.00 | 0.752827E+11 | 0.685903E+11 | 261533.33 | 12-DEC-20:31 | 83483.88 | 0.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.399647E+12 | 0.355631E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.752827E+11 | 0.685903E+11 | 288096.54 | 102655.08 | 0.51 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.354478E+12 | 0.343723E+12 | 143265.94 | 30-JAN-15:00 | 132310.72 | 0.00 |
February | 0.00 | 0.00 | 0.545438E+12 | 0.532336E+12 | 238139.64 | 07-FEB-16:10 | 226416.67 | 0.00 |
March | 0.00 | 0.00 | 0.849618E+12 | 0.836878E+12 | 408391.06 | 31-MAR-23:05 | 397606.56 | 0.00 |
April | 0.00 | 0.00 | 0.106396E+13 | 0.105046E+13 | 422560.64 | 28-APR-14:05 | 413611.12 | 0.00 |
May | 0.00 | 0.00 | 0.377963E+12 | 0.360049E+12 | 231381.54 | 31-MAY-23:03 | 220611.98 | 0.00 |
June | 0.00 | 0.00 | 0.615667E+12 | 0.587892E+12 | 329504.04 | 30-JUN-23:03 | 311644.21 | 0.00 |
July | 0.00 | 0.00 | 0.890897E+12 | 0.857455E+12 | 425555.31 | 31-JUL-23:03 | 405414.88 | 0.00 |
August | 0.00 | 0.00 | 0.113899E+13 | 0.110448E+13 | 445994.20 | 04-AUG-14:00 | 421296.76 | 0.00 |
September | 0.00 | 0.00 | 0.385337E+12 | 0.354701E+12 | 242641.35 | 30-SEP-23:05 | 219932.68 | 0.00 |
October | 0.00 | 0.00 | 0.631844E+12 | 0.607611E+12 | 319857.53 | 31-OCT-23:05 | 310845.26 | 0.00 |
November | 0.00 | 0.00 | 0.835570E+12 | 0.818452E+12 | 335717.98 | 01-NOV-15:00 | 320119.22 | 0.00 |
December | 0.00 | 0.00 | 0.110099E+13 | 0.108366E+13 | 421990.35 | 05-DEC-17:00 | 409106.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.879074E+13 | 0.853770E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.354478E+12 | 0.343723E+12 | 143265.94 | 132310.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113899E+13 | 0.110448E+13 | 445994.20 | 421296.76 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.566317E+10 | 0.532296E+10 | 2687.29 | 30-JAN-15:00 | 2264.76 | 0.00 |
February | 0.00 | 0.00 | 0.100586E+11 | 0.960745E+10 | 4841.37 | 07-FEB-16:10 | 4349.54 | 0.00 |
March | 0.00 | 0.00 | 0.163660E+11 | 0.158976E+11 | 8115.51 | 31-MAR-23:05 | 7630.87 | 0.00 |
April | 0.00 | 0.00 | 0.211832E+11 | 0.205774E+11 | 8898.93 | 30-APR-17:57 | 8351.19 | 0.00 |
May | 0.00 | 0.00 | 0.745713E+10 | 0.671862E+10 | 4772.08 | 31-MAY-23:03 | 4321.81 | 0.00 |
June | 0.00 | 0.00 | 0.127495E+11 | 0.115482E+11 | 6938.89 | 30-JUN-23:03 | 6138.90 | 0.00 |
July | 0.00 | 0.00 | 0.188197E+11 | 0.173244E+11 | 8714.84 | 31-JUL-24:00 | 8025.16 | 0.00 |
August | 0.00 | 0.00 | 0.230426E+11 | 0.214916E+11 | 8989.95 | 27-AUG-06:00 | 8182.11 | 0.00 |
September | 0.00 | 0.00 | 0.797532E+10 | 0.669334E+10 | 5245.45 | 30-SEP-23:05 | 4258.08 | 0.00 |
October | 0.00 | 0.00 | 0.127391E+11 | 0.117033E+11 | 6358.02 | 31-OCT-23:05 | 5966.85 | 0.00 |
November | 0.00 | 0.00 | 0.164431E+11 | 0.157103E+11 | 7016.19 | 01-NOV-16:00 | 6363.71 | 0.00 |
December | 0.00 | 0.00 | 0.213451E+11 | 0.207695E+11 | 8669.45 | 05-DEC-17:00 | 8090.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173843E+12 | 0.163365E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.566317E+10 | 0.532296E+10 | 2687.29 | 2264.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230426E+11 | 0.214916E+11 | 8989.95 | 8351.19 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.474605E+11 | 0.441923E+11 | 24587.93 | 30-JAN-15:00 | 20462.26 | 0.00 |
February | 0.00 | 0.00 | 0.916477E+11 | 0.871906E+11 | 45849.10 | 07-FEB-16:10 | 40973.25 | 0.00 |
March | 0.00 | 0.00 | 0.154122E+12 | 0.149464E+12 | 78106.19 | 31-MAR-23:05 | 73207.22 | 0.00 |
April | 0.00 | 0.00 | 0.201098E+12 | 0.195054E+12 | 84273.48 | 30-APR-17:55 | 78691.77 | 0.00 |
May | 0.00 | 0.00 | 0.679768E+11 | 0.607356E+11 | 45187.01 | 31-MAY-23:03 | 40654.62 | 0.00 |
June | 0.00 | 0.00 | 0.118891E+12 | 0.106983E+12 | 65980.91 | 30-JUN-23:03 | 57904.39 | 0.00 |
July | 0.00 | 0.00 | 0.175821E+12 | 0.160945E+12 | 83080.82 | 31-JUL-24:00 | 76086.14 | 0.00 |
August | 0.00 | 0.00 | 0.219010E+12 | 0.203448E+12 | 85131.68 | 08-AUG-04:53 | 76391.71 | 0.00 |
September | 0.00 | 0.00 | 0.722992E+11 | 0.597246E+11 | 49578.15 | 30-SEP-23:05 | 39390.01 | 0.00 |
October | 0.00 | 0.00 | 0.118088E+12 | 0.107835E+12 | 60946.23 | 31-OCT-23:05 | 56981.30 | 0.00 |
November | 0.00 | 0.00 | 0.154786E+12 | 0.147498E+12 | 66858.32 | 01-NOV-16:00 | 60360.04 | 0.00 |
December | 0.00 | 0.00 | 0.200123E+12 | 0.194384E+12 | 82665.61 | 05-DEC-17:00 | 76896.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162132E+13 | 0.151745E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.474605E+11 | 0.441923E+11 | 24587.93 | 20462.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219010E+12 | 0.203448E+12 | 85131.68 | 78691.77 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.429235E+10 | 0.397352E+10 | 2490.92 | 30-JAN-14:50 | 2079.02 | 0.00 |
February | 0.00 | 0.00 | 0.892808E+10 | 0.848383E+10 | 4634.41 | 07-FEB-16:10 | 4145.81 | 0.00 |
March | 0.00 | 0.00 | 0.153062E+11 | 0.148406E+11 | 7766.70 | 31-MAR-23:05 | 7276.52 | 0.00 |
April | 0.00 | 0.00 | 0.201429E+11 | 0.195384E+11 | 8546.27 | 30-APR-17:55 | 7992.87 | 0.00 |
May | 0.00 | 0.00 | 0.694750E+10 | 0.621982E+10 | 4574.29 | 31-MAY-23:03 | 4121.81 | 0.00 |
June | 0.00 | 0.00 | 0.120445E+11 | 0.108514E+11 | 6620.40 | 30-JUN-23:03 | 5813.11 | 0.00 |
July | 0.00 | 0.00 | 0.178133E+11 | 0.163239E+11 | 8374.64 | 31-JUL-24:00 | 7674.30 | 0.00 |
August | 0.00 | 0.00 | 0.220857E+11 | 0.205299E+11 | 8577.38 | 20-AUG-21:04 | 7726.77 | 0.00 |
September | 0.00 | 0.00 | 0.737715E+10 | 0.611460E+10 | 5007.28 | 30-SEP-23:05 | 3999.19 | 0.00 |
October | 0.00 | 0.00 | 0.118794E+11 | 0.108531E+11 | 6090.24 | 31-OCT-23:05 | 5693.35 | 0.00 |
November | 0.00 | 0.00 | 0.154158E+11 | 0.146873E+11 | 6735.74 | 01-NOV-16:00 | 6085.39 | 0.00 |
December | 0.00 | 0.00 | 0.197346E+11 | 0.191612E+11 | 8292.05 | 05-DEC-17:00 | 7715.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161968E+12 | 0.151577E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.429235E+10 | 0.397352E+10 | 2490.92 | 2079.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220857E+11 | 0.205299E+11 | 8577.38 | 7992.87 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 265319.77 | 1247975.70 | 30-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 353464.48 | 2013489.78 | 08-FEB-15:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 480198.28 | 2041783.41 | 01-MAR-15:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 655329.33 | 2333451.32 | 27-APR-10:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 973492.56 | 2826172.19 | 30-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1263292.21 | 4016609.94 | 11-JUN-15:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1444427.83 | 4277129.78 | 24-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1560598.86 | 4248485.69 | 21-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1290304.56 | 3586530.00 | 05-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 951861.33 | 3305568.37 | 07-OCT-17:10 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 658691.10 | 2560642.19 | 10-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 377476.92 | 2153109.96 | 04-DEC-13:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 859123.74 | 0.00 | ||||
Minimum of Months | 265319.77 | 1247975.70 | 0.00 | 0.00 | ||
Maximum of Months | 1560598.86 | 4277129.78 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 263073.64 | 2556852.71 | 30-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 351399.71 | 3777725.55 | 09-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 477391.02 | 3744468.22 | 29-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 652242.72 | 3853186.58 | 12-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 968519.24 | 4161289.02 | 27-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1256386.76 | 4602763.10 | 09-JUN-03:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1434878.75 | 4812273.23 | 22-JUL-17:04 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1551552.58 | 4639398.03 | 08-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1284892.19 | 4325594.02 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 947664.43 | 4350357.92 | 18-OCT-03:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 655980.40 | 4049231.66 | 02-NOV-04:12 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 374584.29 | 3743755.41 | 11-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 854443.39 | 0.00 | ||||
Minimum of Months | 263073.64 | 2556852.71 | 0.00 | 0.00 | ||
Maximum of Months | 1551552.58 | 4812273.23 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 358265.51 | 856882.54 | 23-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 621177.98 | 1350639.74 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 957006.34 | 1917534.78 | 27-MAR-11:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1379706.54 | 2384632.43 | 28-APR-12:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1078403.47 | 1738638.82 | 31-MAY-19:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1403662.34 | 2046374.33 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1764893.52 | 2466576.59 | 21-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1994018.38 | 2659298.67 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1165501.60 | 1696701.80 | 26-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1180969.66 | 1706353.44 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1120743.38 | 1653959.29 | 05-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1030196.01 | 1600363.63 | 10-DEC-12:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1174678.74 | 0.00 | ||||
Minimum of Months | 358265.51 | 856882.54 | 0.00 | 0.00 | ||
Maximum of Months | 1994018.38 | 2659298.67 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 10346.39 | 36784.64 | 12-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 10124.80 | 36400.81 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10018.70 | 34668.91 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 8455.29 | 31368.88 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 7809.90 | 28236.43 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 7301.11 | 25320.08 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 6511.33 | 23922.66 | 31-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 7451.38 | 25781.45 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 7703.11 | 28649.04 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 8617.10 | 32224.18 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9648.28 | 35051.65 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9909.48 | 36590.29 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 8650.20 | ||||
Minimum of Months | 0.00 | 0.00 | 6511.33 | 23922.66 | ||
Maximum of Months | 0.00 | 0.00 | 10346.39 | 36784.64 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 306917.70 | 2258280.11 | 30-JAN-14:00 | 589.74 | 118558.80 | 20-JAN-05:40 |
February | 438729.29 | 4076657.46 | 07-FEB-16:00 | 236.15 | 57252.66 | 12-FEB-17:00 |
March | 631106.22 | 3872534.32 | 28-MAR-12:05 | 699.08 | 87469.82 | 23-MAR-00:50 |
April | 1059308.46 | 4542335.51 | 28-APR-15:00 | 489.13 | 60581.84 | 26-APR-01:40 |
May | 2210395.77 | 7628263.53 | 29-MAY-14:42 | 6.84 | 11306.33 | 07-MAY-05:20 |
June | 3680738.45 | 7722559.60 | 11-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4497612.86 | 8375868.18 | 19-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4971839.51 | 8460155.69 | 10-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 4021593.36 | 8118782.23 | 07-SEP-14:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2380213.92 | 7380943.63 | 01-OCT-16:32 | 25.32 | 29685.67 | 21-OCT-03:05 |
November | 1171613.17 | 6740571.15 | 01-NOV-14:05 | 305.80 | 58471.86 | 26-NOV-05:50 |
December | 495768.92 | 4160868.27 | 05-DEC-15:05 | 500.81 | 68157.46 | 13-DEC-03:50 |
Annual Sum or Average | 2166004.18 | 238.18 | ||||
Minimum of Months | 306917.70 | 2258280.11 | 0.00 | 0.00 | ||
Maximum of Months | 4971839.51 | 8460155.69 | 699.08 | 118558.80 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.608468E+10 | 0.38 | 21702.22 | 30-JAN-05:12 | 1.76 |
February | 0.747807E+10 | 0.45 | 21702.22 | 06-FEB-06:02 | 1.76 |
March | 0.114540E+11 | 0.59 | 21702.22 | 02-MAR-05:12 | 1.76 |
April | 0.154517E+11 | 0.75 | 21702.22 | 03-APR-05:02 | 1.76 |
May | 0.219042E+11 | 0.89 | 21702.22 | 01-MAY-04:22 | 1.76 |
June | 0.246618E+11 | 0.97 | 21702.22 | 01-JUN-03:12 | 1.76 |
July | 0.263613E+11 | 0.98 | 21702.22 | 01-JUL-03:12 | 1.76 |
August | 0.307262E+11 | 1.09 | 21702.22 | 01-AUG-03:02 | 1.76 |
September | 0.231416E+11 | 0.94 | 21702.22 | 01-SEP-03:12 | 1.76 |
October | 0.214305E+11 | 0.88 | 21702.22 | 02-OCT-03:02 | 1.76 |
November | 0.143983E+11 | 0.70 | 21702.22 | 01-NOV-05:03 | 1.75 |
December | 0.943570E+10 | 0.52 | 21702.22 | 12-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.212528E+12 | 0.76 | |||
Minimum of Months | 0.608468E+10 | 0.38 | 21702.22 | 1.75 | |
Maximum of Months | 0.307262E+11 | 1.09 | 21702.22 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.400939E+11 | 0.33 | 132695.67 | 30-JAN-06:03 | 1.34 |
February | 0.442721E+11 | 0.36 | 204046.24 | 06-FEB-06:02 | 1.76 |
March | 0.655022E+11 | 0.42 | 204046.24 | 02-MAR-06:02 | 1.76 |
April | 0.765782E+11 | 0.48 | 204046.24 | 03-APR-05:02 | 1.76 |
May | 0.112444E+12 | 0.62 | 204046.24 | 01-MAY-04:12 | 1.76 |
June | 0.122221E+12 | 0.68 | 204046.24 | 03-JUN-05:02 | 1.76 |
July | 0.131345E+12 | 0.69 | 204046.24 | 01-JUL-05:02 | 1.76 |
August | 0.150159E+12 | 0.75 | 204046.24 | 01-AUG-05:01 | 1.76 |
September | 0.115196E+12 | 0.65 | 204046.24 | 01-SEP-05:03 | 1.75 |
October | 0.988866E+11 | 0.56 | 204046.24 | 02-OCT-05:02 | 1.75 |
November | 0.755679E+11 | 0.45 | 204046.24 | 02-NOV-04:12 | 1.76 |
December | 0.481312E+11 | 0.35 | 204046.24 | 11-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.108040E+13 | 0.53 | |||
Minimum of Months | 0.400939E+11 | 0.33 | 132695.67 | 1.34 | |
Maximum of Months | 0.150159E+12 | 0.75 | 204046.24 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345053E+10 | 0.31 | 9160.77 | 30-JAN-06:03 | 0.99 |
February | 0.393277E+10 | 0.33 | 20173.70 | 06-FEB-06:02 | 1.60 |
March | 0.604131E+10 | 0.39 | 23062.61 | 27-MAR-04:12 | 1.75 |
April | 0.743033E+10 | 0.46 | 23062.61 | 03-APR-05:02 | 1.75 |
May | 0.116156E+11 | 0.61 | 23062.61 | 01-MAY-04:12 | 1.75 |
June | 0.128181E+11 | 0.67 | 23062.61 | 05-JUN-05:02 | 1.75 |
July | 0.140431E+11 | 0.69 | 23062.61 | 01-JUL-05:02 | 1.75 |
August | 0.158126E+11 | 0.73 | 23062.61 | 01-AUG-04:42 | 1.74 |
September | 0.118227E+11 | 0.63 | 23062.61 | 04-SEP-15:31 | 1.75 |
October | 0.967618E+10 | 0.53 | 23062.61 | 02-OCT-05:02 | 1.75 |
November | 0.676760E+10 | 0.41 | 23062.61 | 20-NOV-06:02 | 1.75 |
December | 0.415452E+10 | 0.33 | 20167.84 | 11-DEC-06:02 | 1.60 |
Annual Sum or Average | 0.107565E+12 | 0.51 | |||
Minimum of Months | 0.345053E+10 | 0.31 | 9160.77 | 0.99 | |
Maximum of Months | 0.158126E+11 | 0.73 | 23062.61 | 1.75 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152253E+11 | 0.89 | 11905.94 | 01-JAN-00:30 | 1.77 |
February | 0.121516E+11 | 0.77 | 11905.94 | 01-FEB-05:12 | 1.77 |
March | 0.113732E+11 | 0.65 | 11905.94 | 02-MAR-14:50 | 1.72 |
April | 0.468037E+10 | 0.28 | 11905.94 | 01-APR-04:11 | 1.77 |
May | 0.692797E+09 | 0.04 | 11905.94 | 01-MAY-04:22 | 1.77 |
June | 0.571343E+09 | 0.03 | 11905.94 | 22-JUN-07:50 | 1.72 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.128532E+10 | 0.07 | 11905.94 | 20-OCT-03:45 | 1.76 |
November | 0.810619E+10 | 0.47 | 11905.94 | 04-NOV-04:23 | 1.76 |
December | 0.138004E+11 | 0.80 | 11905.94 | 01-DEC-05:12 | 1.77 |
Annual Sum or Average | 0.678865E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152253E+11 | 0.89 | 11905.94 | 1.77 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108732E+12 | 1.35 | 40595.91 | 01-JAN-00:05 | 1.35 |
February | 0.982096E+11 | 1.35 | 40595.91 | 01-FEB-00:10 | 1.35 |
March | 0.108732E+12 | 1.35 | 40595.91 | 01-MAR-00:10 | 1.35 |
April | 0.105225E+12 | 1.35 | 40595.91 | 01-APR-00:05 | 1.35 |
May | 0.108732E+12 | 1.34 | 40595.91 | 01-MAY-00:05 | 1.34 |
June | 0.105225E+12 | 1.34 | 40595.91 | 01-JUN-00:10 | 1.34 |
July | 0.108732E+12 | 1.34 | 40595.91 | 01-JUL-00:05 | 1.34 |
August | 0.108732E+12 | 1.34 | 40595.91 | 01-AUG-00:03 | 1.34 |
September | 0.105225E+12 | 1.34 | 40595.91 | 01-SEP-00:05 | 1.34 |
October | 0.108732E+12 | 1.34 | 40595.91 | 01-OCT-00:05 | 1.34 |
November | 0.105225E+12 | 1.35 | 40595.91 | 01-NOV-00:05 | 1.35 |
December | 0.108732E+12 | 1.35 | 40595.91 | 01-DEC-00:05 | 1.35 |
Annual Sum or Average | 0.128023E+13 | 1.35 | |||
Minimum of Months | 0.982096E+11 | 1.34 | 40595.91 | 1.34 | |
Maximum of Months | 0.108732E+12 | 1.35 | 40595.91 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141561E+10 | 0.91 | 528.53 | 01-JAN-00:05 | 0.92 |
February | 0.127862E+10 | 0.91 | 528.53 | 01-FEB-00:10 | 0.91 |
March | 0.141561E+10 | 0.91 | 528.53 | 01-MAR-00:10 | 0.91 |
April | 0.136995E+10 | 0.91 | 528.53 | 01-APR-00:05 | 0.91 |
May | 0.141561E+10 | 0.91 | 528.53 | 01-MAY-00:05 | 0.91 |
June | 0.136995E+10 | 0.91 | 528.53 | 01-JUN-00:10 | 0.91 |
July | 0.141561E+10 | 0.91 | 528.53 | 01-JUL-00:05 | 0.91 |
August | 0.141561E+10 | 0.91 | 528.53 | 01-AUG-00:03 | 0.91 |
September | 0.136995E+10 | 0.91 | 528.53 | 01-SEP-00:05 | 0.91 |
October | 0.141561E+10 | 0.91 | 528.53 | 01-OCT-00:05 | 0.91 |
November | 0.136995E+10 | 0.91 | 528.53 | 01-NOV-00:05 | 0.91 |
December | 0.141561E+10 | 0.91 | 528.53 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.166677E+11 | 0.91 | |||
Minimum of Months | 0.127862E+10 | 0.91 | 528.53 | 0.91 | |
Maximum of Months | 0.141561E+10 | 0.91 | 528.53 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135044E+11 | 0.91 | 5041.96 | 01-JAN-00:05 | 0.91 |
February | 0.121975E+11 | 0.91 | 5041.96 | 01-FEB-00:10 | 0.91 |
March | 0.135044E+11 | 0.91 | 5041.96 | 01-MAR-00:10 | 0.91 |
April | 0.130688E+11 | 0.91 | 5041.96 | 01-APR-00:05 | 0.91 |
May | 0.135044E+11 | 0.91 | 5041.96 | 01-MAY-00:05 | 0.91 |
June | 0.130688E+11 | 0.91 | 5041.96 | 01-JUN-00:10 | 0.91 |
July | 0.135044E+11 | 0.91 | 5041.96 | 01-JUL-00:05 | 0.91 |
August | 0.135044E+11 | 0.91 | 5041.96 | 01-AUG-00:03 | 0.91 |
September | 0.130688E+11 | 0.91 | 5041.96 | 01-SEP-00:05 | 0.91 |
October | 0.135044E+11 | 0.91 | 5041.96 | 01-OCT-00:05 | 0.91 |
November | 0.130688E+11 | 0.91 | 5041.96 | 01-NOV-00:05 | 0.91 |
December | 0.135044E+11 | 0.91 | 5041.96 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.159003E+12 | 0.91 | |||
Minimum of Months | 0.121975E+11 | 0.91 | 5041.96 | 0.91 | |
Maximum of Months | 0.135044E+11 | 0.91 | 5041.96 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136139E+10 | 0.91 | 508.28 | 01-JAN-00:05 | 0.91 |
February | 0.122964E+10 | 0.91 | 508.28 | 01-FEB-00:10 | 0.91 |
March | 0.136139E+10 | 0.91 | 508.28 | 01-MAR-00:10 | 0.91 |
April | 0.131747E+10 | 0.91 | 508.28 | 01-APR-00:05 | 0.91 |
May | 0.136139E+10 | 0.91 | 508.28 | 01-MAY-00:05 | 0.91 |
June | 0.131747E+10 | 0.91 | 508.28 | 01-JUN-00:10 | 0.91 |
July | 0.136139E+10 | 0.91 | 508.28 | 01-JUL-00:05 | 0.91 |
August | 0.136139E+10 | 0.91 | 508.28 | 01-AUG-00:03 | 0.91 |
September | 0.131747E+10 | 0.91 | 508.28 | 01-SEP-00:05 | 0.91 |
October | 0.136139E+10 | 0.91 | 508.28 | 01-OCT-00:05 | 0.91 |
November | 0.131747E+10 | 0.91 | 508.28 | 01-NOV-00:05 | 0.91 |
December | 0.136139E+10 | 0.91 | 508.28 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.160292E+11 | 0.91 | |||
Minimum of Months | 0.122964E+10 | 0.91 | 508.28 | 0.91 | |
Maximum of Months | 0.136139E+10 | 0.91 | 508.28 | 0.91 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.270669E+09 | 0.246038E+09 | 5213.69 | 30-JAN-06:03 | 4739.24 | 4739.24 | 8.19 | 56.86 |
February | 0.381302E+09 | 0.346604E+09 | 12035.18 | 08-FEB-06:03 | 10939.98 | 10939.98 | 9.96 | 79.59 |
March | 0.735526E+09 | 0.668594E+09 | 13397.87 | 30-MAR-05:02 | 12178.66 | 12178.66 | 9.67 | 83.01 |
April | 0.103616E+10 | 0.941870E+09 | 13570.41 | 04-APR-05:03 | 12335.51 | 12335.51 | 10.22 | 83.45 |
May | 0.165908E+10 | 0.150810E+10 | 12040.90 | 22-MAY-05:03 | 10945.18 | 10945.18 | 11.55 | 79.59 |
June | 0.217942E+10 | 0.198109E+10 | 12035.73 | 12-JUN-03:02 | 10940.48 | 10940.48 | 10.14 | 79.59 |
July | 0.288497E+10 | 0.262244E+10 | 12045.22 | 15-JUL-17:04 | 10949.11 | 10949.11 | 12.72 | 79.59 |
August | 0.339228E+10 | 0.308359E+10 | 12041.93 | 04-AUG-05:03 | 10946.11 | 10946.11 | 11.83 | 79.59 |
September | 0.230523E+10 | 0.209546E+10 | 12035.69 | 23-SEP-05:02 | 10940.45 | 10940.45 | 10.13 | 79.59 |
October | 0.160662E+10 | 0.146042E+10 | 12036.34 | 25-OCT-05:03 | 10941.03 | 10941.03 | 10.30 | 79.59 |
November | 0.103238E+10 | 0.938434E+09 | 13314.76 | 06-NOV-05:12 | 12103.12 | 12103.12 | 9.40 | 82.81 |
December | 0.440610E+09 | 0.400515E+09 | 12040.45 | 11-DEC-06:04 | 10944.77 | 10944.77 | 11.42 | 79.59 |
Annual Sum or Average | 0.179243E+11 | 0.162932E+11 | ||||||
Minimum of Months | 0.270669E+09 | 0.246038E+09 | 5213.69 | 4739.24 | 4739.24 | 8.19 | 56.86 | |
Maximum of Months | 0.339228E+10 | 0.308359E+10 | 13570.41 | 12335.51 | 12335.51 | 12.72 | 83.45 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.763394E+10 | 0.693925E+10 | 4670.07 | 01-JAN-00:15 | 4245.10 | 4245.10 | 6.95 | 41.72 |
February | 0.719205E+10 | 0.653758E+10 | 4670.07 | 01-FEB-05:12 | 4245.10 | 4245.10 | 9.10 | 41.72 |
March | 0.966472E+10 | 0.878523E+10 | 4670.07 | 01-MAR-03:55 | 4245.10 | 4245.10 | 7.53 | 41.72 |
April | 0.109747E+11 | 0.997600E+10 | 4670.07 | 01-APR-00:20 | 4245.10 | 4245.10 | 6.94 | 41.72 |
May | 0.117476E+11 | 0.106786E+11 | 4670.07 | 01-MAY-00:05 | 4245.10 | 4245.10 | 10.92 | 41.72 |
June | 0.114288E+11 | 0.103888E+11 | 4670.07 | 01-JUN-00:10 | 4245.10 | 4245.10 | 10.91 | 41.72 |
July | 0.116054E+11 | 0.105493E+11 | 4670.07 | 01-JUL-00:05 | 4245.10 | 4245.10 | 13.05 | 41.72 |
August | 0.119437E+11 | 0.108568E+11 | 4670.07 | 01-AUG-00:03 | 4245.10 | 4245.10 | 12.59 | 41.72 |
September | 0.115688E+11 | 0.105160E+11 | 4670.07 | 01-SEP-00:05 | 4245.10 | 4245.10 | 8.94 | 41.72 |
October | 0.116420E+11 | 0.105826E+11 | 4670.07 | 01-OCT-00:05 | 4245.10 | 4245.10 | 12.85 | 41.72 |
November | 0.102576E+11 | 0.932419E+10 | 4670.07 | 01-NOV-00:20 | 4245.10 | 4245.10 | 6.96 | 41.72 |
December | 0.925954E+10 | 0.841692E+10 | 4670.07 | 01-DEC-01:05 | 4245.10 | 4245.10 | 6.86 | 41.72 |
Annual Sum or Average | 0.124919E+12 | 0.113551E+12 | ||||||
Minimum of Months | 0.719205E+10 | 0.653758E+10 | 4670.07 | 4245.10 | 4245.10 | 6.86 | 41.72 | |
Maximum of Months | 0.119437E+11 | 0.108568E+11 | 4670.07 | 4245.10 | 4245.10 | 13.05 | 41.72 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.84 | 0.00 |
February | 0.175548E+09 | 0.159573E+09 | 4670.07 | 06-FEB-06:04 | 4245.10 | 4245.10 | 15.61 | 20.86 |
March | 0.702192E+09 | 0.638293E+09 | 4670.07 | 01-MAR-13:05 | 4245.10 | 4245.10 | 11.26 | 41.72 |
April | 0.154986E+10 | 0.140883E+10 | 4670.07 | 03-APR-07:40 | 4245.10 | 4245.10 | 14.73 | 20.86 |
May | 0.392837E+10 | 0.357089E+10 | 4670.07 | 01-MAY-07:20 | 4245.10 | 4245.10 | 16.00 | 20.86 |
June | 0.610797E+10 | 0.555214E+10 | 4670.07 | 01-JUN-07:20 | 4245.10 | 4245.10 | 14.71 | 20.86 |
July | 0.716669E+10 | 0.651452E+10 | 4670.07 | 01-JUL-03:30 | 4245.10 | 4245.10 | 14.44 | 20.86 |
August | 0.782854E+10 | 0.711614E+10 | 4670.07 | 01-AUG-00:23 | 4245.10 | 4245.10 | 11.68 | 41.72 |
September | 0.603093E+10 | 0.548212E+10 | 4670.07 | 01-SEP-05:03 | 4245.10 | 4245.10 | 12.93 | 41.72 |
October | 0.386006E+10 | 0.350879E+10 | 4670.07 | 01-OCT-13:51 | 4245.10 | 4245.10 | 12.47 | 41.72 |
November | 0.224546E+10 | 0.204113E+10 | 4670.07 | 01-NOV-05:07 | 4245.10 | 4245.10 | 14.86 | 20.86 |
December | 0.309626E+09 | 0.281450E+09 | 4670.07 | 04-DEC-09:40 | 4245.10 | 4245.10 | 14.94 | 20.86 |
Annual Sum or Average | 0.399053E+11 | 0.362739E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 0.00 | |
Maximum of Months | 0.782854E+10 | 0.711614E+10 | 4670.07 | 4245.10 | 4245.10 | 16.00 | 41.72 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-JAN-00:05 | 3544.81 | 3544.81 | 21.65 | 16.45 |
February | 0.943412E+10 | 0.857561E+10 | 3899.69 | 01-FEB-00:10 | 3544.81 | 3544.81 | 24.46 | 16.45 |
March | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-MAR-00:10 | 3544.81 | 3544.81 | 33.81 | 16.45 |
April | 0.101080E+11 | 0.918816E+10 | 3899.69 | 01-APR-00:05 | 3544.81 | 3544.81 | 37.13 | 16.45 |
May | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-MAY-00:05 | 3544.81 | 3544.81 | 32.77 | 16.45 |
June | 0.101080E+11 | 0.918816E+10 | 3899.69 | 01-JUN-00:10 | 3544.81 | 3544.81 | 41.71 | 16.45 |
July | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-JUL-00:05 | 3544.81 | 3544.81 | 44.52 | 16.45 |
August | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-AUG-00:03 | 3544.81 | 3544.81 | 49.91 | 16.45 |
September | 0.101080E+11 | 0.918816E+10 | 3899.69 | 01-SEP-00:05 | 3544.81 | 3544.81 | 38.10 | 16.45 |
October | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-OCT-00:05 | 3544.81 | 3544.81 | 38.14 | 16.45 |
November | 0.101080E+11 | 0.918816E+10 | 3899.69 | 01-NOV-00:05 | 3544.81 | 3544.81 | 39.37 | 16.45 |
December | 0.104449E+11 | 0.949443E+10 | 3899.69 | 01-DEC-00:05 | 3544.81 | 3544.81 | 34.94 | 16.45 |
Annual Sum or Average | 0.122980E+12 | 0.111789E+12 | ||||||
Minimum of Months | 0.943412E+10 | 0.857561E+10 | 3899.69 | 3544.81 | 3544.81 | 21.65 | 16.45 | |
Maximum of Months | 0.104449E+11 | 0.949443E+10 | 3899.69 | 3544.81 | 3544.81 | 49.91 | 16.45 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 57.81 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.92 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 58.02 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 58.16 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 58.56 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.50 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 58.66 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 58.70 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 58.47 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 58.23 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 58.07 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.95 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.81 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.70 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.294226E+11 | 0.267451E+11 | 18080.75 | 30-JAN-14:00 | 16435.40 | 16435.40 | 28.44 | 73.61 |
February | 0.281814E+11 | 0.256168E+11 | 36139.81 | 07-FEB-16:00 | 32851.09 | 32851.09 | 27.73 | 147.23 |
March | 0.393342E+11 | 0.357548E+11 | 36129.76 | 28-MAR-12:05 | 32841.95 | 32841.95 | 27.39 | 147.23 |
April | 0.471752E+11 | 0.428823E+11 | 36162.78 | 28-APR-15:00 | 32871.96 | 32871.96 | 28.48 | 147.23 |
May | 0.589430E+11 | 0.535792E+11 | 36192.04 | 08-MAY-14:00 | 32898.57 | 32898.57 | 30.07 | 147.23 |
June | 0.658399E+11 | 0.598485E+11 | 36192.04 | 01-JUN-19:50 | 32898.57 | 32898.57 | 29.56 | 147.23 |
July | 0.706888E+11 | 0.642561E+11 | 36192.04 | 01-JUL-04:05 | 32898.57 | 32898.57 | 31.50 | 147.23 |
August | 0.745957E+11 | 0.678075E+11 | 36192.04 | 01-AUG-00:23 | 32898.57 | 32898.57 | 32.07 | 147.23 |
September | 0.665396E+11 | 0.604845E+11 | 36192.04 | 01-SEP-07:30 | 32898.57 | 32898.57 | 29.48 | 147.23 |
October | 0.585951E+11 | 0.532630E+11 | 36192.04 | 01-OCT-13:51 | 32898.57 | 32898.57 | 32.65 | 147.23 |
November | 0.463911E+11 | 0.421695E+11 | 36192.04 | 01-NOV-09:50 | 32898.57 | 32898.57 | 29.45 | 147.23 |
December | 0.365118E+11 | 0.331893E+11 | 36143.96 | 05-DEC-15:05 | 32854.86 | 32854.86 | 27.86 | 147.23 |
Annual Sum or Average | 0.622218E+12 | 0.565596E+12 | ||||||
Minimum of Months | 0.281814E+11 | 0.256168E+11 | 18080.75 | 16435.40 | 16435.40 | 27.39 | 73.61 | |
Maximum of Months | 0.745957E+11 | 0.678075E+11 | 36192.04 | 32898.57 | 32898.57 | 32.65 | 147.23 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 265319.77 | 1247975.70 | 30-JAN-14:00 | 13.84 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 353464.48 | 2013489.78 | 08-FEB-15:05 | 12.46 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 480198.28 | 2041783.41 | 01-MAR-15:05 | 12.54 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 655329.33 | 2333451.32 | 27-APR-10:05 | 13.38 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 973492.56 | 2826172.19 | 30-MAY-05:03 | 14.79 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1263292.21 | 4016609.94 | 11-JUN-15:02 | 18.21 | 9.78 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1444427.83 | 4277129.78 | 24-JUL-05:03 | 18.96 | 10.52 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1560598.86 | 4248485.69 | 21-AUG-05:03 | 18.87 | 10.44 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1290304.56 | 3586530.00 | 05-SEP-05:03 | 16.97 | 8.54 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 951861.33 | 3305568.37 | 07-OCT-17:10 | 16.17 | 11.95 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 658691.10 | 2560642.19 | 10-NOV-06:02 | 14.03 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 377476.92 | 2153109.96 | 04-DEC-13:05 | 12.86 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 859123.74 | 0.00 | ||||||
Minimum of Months | 265319.77 | 1247975.70 | 12.46 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1560598.86 | 4277129.78 | 18.96 | 11.95 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 263073.64 | 2556852.71 | 30-JAN-06:03 | 17.45 | 9.54 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 351399.71 | 3777725.55 | 09-FEB-06:02 | 18.05 | 12.08 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 477391.02 | 3744468.22 | 29-MAR-05:02 | 17.95 | 12.03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 652242.72 | 3853186.58 | 12-APR-05:02 | 18.28 | 12.19 | 0.00 | 0.00 | 01-APR-00:05 |
May | 968519.24 | 4161289.02 | 27-MAY-05:02 | 19.20 | 12.63 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1256386.76 | 4602763.10 | 09-JUN-03:12 | 20.53 | 13.26 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1434878.75 | 4812273.23 | 22-JUL-17:04 | 21.16 | 15.37 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1551552.58 | 4639398.03 | 08-AUG-05:01 | 20.64 | 7.47 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1284892.19 | 4325594.02 | 05-SEP-03:02 | 20.16 | 12.83 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 947664.43 | 4350357.92 | 18-OCT-03:02 | 19.82 | 12.89 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 655980.40 | 4049231.66 | 02-NOV-04:12 | 18.87 | 12.47 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 374584.29 | 3743755.41 | 11-DEC-06:02 | 17.95 | 12.03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 854443.39 | 0.00 | ||||||
Minimum of Months | 263073.64 | 2556852.71 | 17.45 | 7.47 | 0.00 | 0.00 | ||
Maximum of Months | 1551552.58 | 4812273.23 | 21.16 | 15.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 358265.51 | 856882.54 | 23-JAN-14:00 | 33.16 | 29.35 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 621177.98 | 1350639.74 | 06-FEB-15:00 | 41.52 | 34.88 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 957006.34 | 1917534.78 | 27-MAR-11:05 | 50.96 | 41.37 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1379706.54 | 2384632.43 | 28-APR-12:00 | 58.63 | 46.48 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1078403.47 | 1738638.82 | 31-MAY-19:00 | 48.00 | 43.67 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1403662.34 | 2046374.33 | 12-JUN-12:00 | 53.09 | 45.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1764893.52 | 2466576.59 | 21-JUL-12:00 | 59.96 | 49.77 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1994018.38 | 2659298.67 | 16-AUG-12:00 | 63.08 | 50.63 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1165501.60 | 1696701.80 | 26-SEP-13:00 | 47.30 | 42.82 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1180969.66 | 1706353.44 | 04-OCT-12:00 | 47.47 | 40.52 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1120743.38 | 1653959.29 | 05-NOV-12:00 | 46.59 | 37.34 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1030196.01 | 1600363.63 | 10-DEC-12:03 | 45.70 | 34.14 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1174678.74 | 0.00 | ||||||
Minimum of Months | 358265.51 | 856882.54 | 33.16 | 29.35 | 0.00 | 0.00 | ||
Maximum of Months | 1994018.38 | 2659298.67 | 63.08 | 50.63 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.65 | 58.65 | 10346.39 | 36784.64 | 12-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.32 | 58.32 | 10124.80 | 36400.81 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.40 | 58.40 | 10018.70 | 34668.91 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 58.54 | 58.54 | 8455.29 | 31368.88 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.98 | 58.98 | 7809.90 | 28236.43 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.84 | 58.84 | 7301.11 | 25320.08 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 58.92 | 58.92 | 6511.33 | 23922.66 | 31-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.91 | 58.91 | 7451.38 | 25781.45 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.82 | 58.82 | 7703.11 | 28649.04 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 58.68 | 58.68 | 8617.10 | 32224.18 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 58.52 | 58.52 | 9648.28 | 35051.65 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 58.38 | 58.38 | 9909.48 | 36590.29 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 8650.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.32 | 58.32 | 6511.33 | 23922.66 | ||
Maximum of Months | 0.00 | 0.00 | 58.98 | 58.98 | 10346.39 | 36784.64 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 306917.70 | 2258280.11 | 30-JAN-14:00 | 28.44 | 23.79 | 589.74 | 118558.80 | 20-JAN-05:40 |
February | 438729.29 | 4076657.46 | 07-FEB-16:00 | 27.73 | 24.87 | 236.15 | 57252.66 | 12-FEB-17:00 |
March | 631106.22 | 3872534.32 | 28-MAR-12:05 | 27.39 | 23.86 | 699.08 | 87469.82 | 23-MAR-00:50 |
April | 1059308.46 | 4542335.51 | 28-APR-15:00 | 28.48 | 25.18 | 489.13 | 60581.84 | 26-APR-01:40 |
May | 2210395.77 | 7628263.53 | 29-MAY-14:42 | 33.50 | 28.89 | 6.84 | 11306.33 | 07-MAY-05:20 |
June | 3680738.45 | 7722559.60 | 11-JUN-15:03 | 33.65 | 28.94 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4497612.86 | 8375868.18 | 19-JUL-15:00 | 34.71 | 29.27 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4971839.51 | 8460155.69 | 10-AUG-16:00 | 34.85 | 29.31 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 4021593.36 | 8118782.23 | 07-SEP-14:05 | 34.29 | 29.14 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2380213.92 | 7380943.63 | 01-OCT-16:32 | 33.09 | 28.73 | 25.32 | 29685.67 | 21-OCT-03:05 |
November | 1171613.17 | 6740571.15 | 01-NOV-14:05 | 32.05 | 28.15 | 305.80 | 58471.86 | 26-NOV-05:50 |
December | 495768.92 | 4160868.27 | 05-DEC-15:05 | 27.86 | 24.90 | 500.81 | 68157.46 | 13-DEC-03:50 |
Annual Sum or Average | 2166004.18 | 238.18 | ||||||
Minimum of Months | 306917.70 | 2258280.11 | 27.39 | 23.79 | 0.00 | 0.00 | ||
Maximum of Months | 4971839.51 | 8460155.69 | 34.85 | 29.31 | 699.08 | 118558.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.717690E+11 | 0.608468E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.889395E+11 | 0.747807E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135242E+12 | 0.114540E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.184042E+12 | 0.154517E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.266090E+12 | 0.219042E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.328941E+12 | 0.246618E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.387119E+12 | 0.263613E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.429391E+12 | 0.307262E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.337955E+12 | 0.231416E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.282226E+12 | 0.214305E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180683E+12 | 0.143983E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.114528E+12 | 0.943570E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.280693E+13 | 0.212528E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.717690E+11 | 0.608468E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.429391E+12 | 0.307262E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.512018E+12 | 0.400939E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.616548E+12 | 0.442721E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.931949E+12 | 0.655022E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124459E+13 | 0.765782E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.201440E+13 | 0.112444E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.257852E+13 | 0.122221E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.307243E+13 | 0.131345E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.332682E+13 | 0.150159E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.265183E+13 | 0.115196E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.195468E+13 | 0.988866E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.124214E+13 | 0.755679E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.714591E+12 | 0.481312E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208605E+14 | 0.108040E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.512018E+12 | 0.400939E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.332682E+13 | 0.150159E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.463729E+11 | 0.347615E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.594816E+11 | 0.393317E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.937424E+11 | 0.604131E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.129249E+12 | 0.743033E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.214606E+12 | 0.116156E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.273572E+12 | 0.128181E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.325921E+12 | 0.140431E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.351643E+12 | 0.158126E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.277131E+12 | 0.118227E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.200945E+12 | 0.967618E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.123136E+12 | 0.676760E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.672757E+11 | 0.415452E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216308E+13 | 0.107591E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.463729E+11 | 0.347615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.351643E+12 | 0.158126E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.674921E+11 | 0.152253E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.586168E+11 | 0.121516E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.634981E+11 | 0.113732E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.403935E+11 | 0.468037E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.698620E+10 | 0.692797E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.702341E+10 | 0.571343E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135038E+11 | 0.128532E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.668507E+11 | 0.810619E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.752827E+11 | 0.138004E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.399647E+12 | 0.678865E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.752827E+11 | 0.152253E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.444998E+12 | 0.202049E+12 | 0.00 | 1.04 |
February | 0.00 | 0.00 | 0.686663E+12 | 0.242369E+12 | 0.00 | 1.09 |
March | 0.00 | 0.00 | 0.108252E+13 | 0.343939E+12 | 0.00 | 0.86 |
April | 0.00 | 0.00 | 0.138222E+13 | 0.423793E+12 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.511626E+12 | 0.242402E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.837064E+12 | 0.326622E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.122400E+13 | 0.441838E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.156200E+13 | 0.531746E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.523959E+12 | 0.243847E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.839840E+12 | 0.316804E+12 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.108010E+13 | 0.350128E+12 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.138272E+13 | 0.395724E+12 | 0.00 | 1.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.115577E+14 | 0.406126E+13 | 0.00 | 5.23 |
Minimum of Months | 0.00 | 0.00 | 0.444998E+12 | 0.202049E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.156200E+13 | 0.531746E+12 | 0.00 | 1.96 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.709367E+10 | 0.284612E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.126066E+11 | 0.382658E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.207413E+11 | 0.579092E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.273148E+11 | 0.750157E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.999260E+10 | 0.395108E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.171275E+11 | 0.574800E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.255161E+11 | 0.811202E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.311180E+11 | 0.949099E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.106981E+11 | 0.409274E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.167686E+11 | 0.544508E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.211039E+11 | 0.603074E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.266661E+11 | 0.673666E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226747E+12 | 0.695725E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.709367E+10 | 0.284612E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.311180E+11 | 0.949099E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.595877E+11 | 0.256316E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114994E+12 | 0.355434E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.195417E+12 | 0.547998E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.259351E+12 | 0.713217E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.911620E+11 | 0.366896E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159781E+12 | 0.539596E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.238496E+12 | 0.761792E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.296004E+12 | 0.904985E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.970280E+11 | 0.377975E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.155515E+12 | 0.509311E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198729E+12 | 0.570113E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250164E+12 | 0.635451E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211623E+13 | 0.653908E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.595877E+11 | 0.256316E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.296004E+12 | 0.904985E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.540253E+10 | 0.247157E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112145E+11 | 0.351608E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194198E+11 | 0.547503E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.259871E+11 | 0.716159E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.931827E+10 | 0.373216E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.161883E+11 | 0.546127E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.241630E+11 | 0.771110E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.298490E+11 | 0.912469E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.990207E+10 | 0.384239E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.156485E+11 | 0.513053E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198024E+11 | 0.570405E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246890E+11 | 0.631572E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211584E+12 | 0.656462E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.540253E+10 | 0.247157E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.298490E+11 | 0.912469E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.608468E+10 | 0.717690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.747807E+10 | 0.889395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114540E+11 | 0.135242E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154517E+11 | 0.184042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219042E+11 | 0.266090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.246618E+11 | 0.328941E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.263613E+11 | 0.387119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307262E+11 | 0.429391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231416E+11 | 0.337955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214305E+11 | 0.282226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143983E+11 | 0.180683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943570E+10 | 0.114528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212528E+12 | 0.280693E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.608468E+10 | 0.717690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.307262E+11 | 0.429391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.400939E+11 | 0.512018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442721E+11 | 0.616548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655022E+11 | 0.931949E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.765782E+11 | 0.124459E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112444E+12 | 0.201440E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122221E+12 | 0.257852E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131345E+12 | 0.307243E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150159E+12 | 0.332682E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115196E+12 | 0.265183E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.988866E+11 | 0.195468E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.755679E+11 | 0.124214E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.481312E+11 | 0.714591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108040E+13 | 0.208605E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.400939E+11 | 0.512018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150159E+12 | 0.332682E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.345053E+10 | 0.463729E+11 | 25611236.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393277E+10 | 0.594816E+11 | 397851.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.604131E+10 | 0.937424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.743033E+10 | 0.129249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116156E+11 | 0.214606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128181E+11 | 0.273572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140431E+11 | 0.325921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158126E+11 | 0.351643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118227E+11 | 0.277131E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967618E+10 | 0.200945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676760E+10 | 0.123136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.415452E+10 | 0.672757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107565E+12 | 0.216308E+13 | 26009087.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345053E+10 | 0.463729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158126E+11 | 0.351643E+12 | 25611236.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152253E+11 | 0.674921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121516E+11 | 0.586168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113732E+11 | 0.634981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468037E+10 | 0.403935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692797E+09 | 0.698620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571343E+09 | 0.702341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128532E+10 | 0.135038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810619E+10 | 0.668507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138004E+11 | 0.752827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678865E+11 | 0.399647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152253E+11 | 0.752827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108732E+12 | 0.354478E+12 | 0.00 | 0.00 | 0.00 | 0.278505E+10 | 0.00 | 0.00 |
February | 0.982096E+11 | 0.545438E+12 | 0.00 | 0.00 | 0.00 | 0.292056E+10 | 0.00 | 0.00 |
March | 0.108732E+12 | 0.849618E+12 | 0.00 | 0.00 | 0.00 | 0.229158E+10 | 0.00 | 0.00 |
April | 0.105225E+12 | 0.106396E+13 | 0.00 | 0.00 | 0.00 | 0.305295E+09 | 0.00 | 0.00 |
May | 0.108732E+12 | 0.377963E+12 | 0.00 | 0.00 | 0.00 | 6822282.87 | 0.00 | 0.00 |
June | 0.105225E+12 | 0.615667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108732E+12 | 0.890897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108732E+12 | 0.113899E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105225E+12 | 0.385337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108732E+12 | 0.631844E+12 | 0.00 | 0.00 | 0.00 | 75875858.34 | 0.00 | 0.00 |
November | 0.105225E+12 | 0.835570E+12 | 0.00 | 0.00 | 0.00 | 0.371496E+09 | 0.00 | 0.00 |
December | 0.108732E+12 | 0.110099E+13 | 0.00 | 0.00 | 0.00 | 0.524065E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.128023E+13 | 0.879074E+13 | 0.00 | 0.00 | 0.00 | 0.139973E+11 | 0.00 | 0.00 |
Minimum of Months | 0.982096E+11 | 0.354478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108732E+12 | 0.113899E+13 | 0.00 | 0.00 | 0.00 | 0.524065E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141561E+10 | 0.566317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127862E+10 | 0.100586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141561E+10 | 0.163660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136995E+10 | 0.211832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141561E+10 | 0.745713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136995E+10 | 0.127495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141561E+10 | 0.188197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141561E+10 | 0.230426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136995E+10 | 0.797532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141561E+10 | 0.127391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136995E+10 | 0.164431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141561E+10 | 0.213451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166677E+11 | 0.173843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127862E+10 | 0.566317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141561E+10 | 0.230426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135044E+11 | 0.474605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121975E+11 | 0.916477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135044E+11 | 0.154122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130688E+11 | 0.201098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135044E+11 | 0.679768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130688E+11 | 0.118891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135044E+11 | 0.175821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135044E+11 | 0.219010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130688E+11 | 0.722992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135044E+11 | 0.118088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130688E+11 | 0.154786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135044E+11 | 0.200123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159003E+12 | 0.162132E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121975E+11 | 0.474605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135044E+11 | 0.219010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136139E+10 | 0.429235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122964E+10 | 0.892808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136139E+10 | 0.153062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131747E+10 | 0.201429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136139E+10 | 0.694750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131747E+10 | 0.120445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136139E+10 | 0.178133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136139E+10 | 0.220857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131747E+10 | 0.737715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136139E+10 | 0.118794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131747E+10 | 0.154158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136139E+10 | 0.197346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160292E+11 | 0.161968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122964E+10 | 0.429235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136139E+10 | 0.220857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.608468E+10 | 0.00 | 0.717690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.747807E+10 | 0.00 | 0.889395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114540E+11 | 0.00 | 0.135242E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154517E+11 | 0.00 | 0.184042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219042E+11 | 0.00 | 0.266090E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.246618E+11 | 0.00 | 0.328941E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.263613E+11 | 0.00 | 0.387119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307262E+11 | 0.00 | 0.429391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231416E+11 | 0.00 | 0.337955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214305E+11 | 0.00 | 0.282226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143983E+11 | 0.00 | 0.180683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943570E+10 | 0.00 | 0.114528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212528E+12 | 0.00 | 0.280693E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.608468E+10 | 0.00 | 0.717690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.307262E+11 | 0.00 | 0.429391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.400939E+11 | 0.00 | 0.512018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442721E+11 | 0.00 | 0.616548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655022E+11 | 0.00 | 0.931949E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.765782E+11 | 0.00 | 0.124459E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112444E+12 | 0.00 | 0.201440E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122221E+12 | 0.00 | 0.257852E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131345E+12 | 0.00 | 0.307243E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150159E+12 | 0.00 | 0.332682E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115196E+12 | 0.00 | 0.265183E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.988866E+11 | 0.00 | 0.195468E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.755679E+11 | 0.00 | 0.124214E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.481312E+11 | 0.00 | 0.714591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108040E+13 | 0.00 | 0.208605E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.400939E+11 | 0.00 | 0.512018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150159E+12 | 0.00 | 0.332682E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.345053E+10 | 0.00 | 0.463729E+11 | 0.00 | 0.00 | 25611236.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393277E+10 | 0.00 | 0.594816E+11 | 0.00 | 0.00 | 397851.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.604131E+10 | 0.00 | 0.937424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.743033E+10 | 0.00 | 0.129249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116156E+11 | 0.00 | 0.214606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128181E+11 | 0.00 | 0.273572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140431E+11 | 0.00 | 0.325921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158126E+11 | 0.00 | 0.351643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118227E+11 | 0.00 | 0.277131E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967618E+10 | 0.00 | 0.200945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676760E+10 | 0.00 | 0.123136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.415452E+10 | 0.00 | 0.672757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107565E+12 | 0.00 | 0.216308E+13 | 0.00 | 0.00 | 26009087.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345053E+10 | 0.00 | 0.463729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158126E+11 | 0.00 | 0.351643E+12 | 0.00 | 0.00 | 25611236.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152253E+11 | 0.00 | 0.674921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121516E+11 | 0.00 | 0.586168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113732E+11 | 0.00 | 0.634981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468037E+10 | 0.00 | 0.403935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692797E+09 | 0.00 | 0.698620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.571343E+09 | 0.00 | 0.702341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128532E+10 | 0.00 | 0.135038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810619E+10 | 0.00 | 0.668507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138004E+11 | 0.00 | 0.752827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678865E+11 | 0.00 | 0.399647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152253E+11 | 0.00 | 0.752827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108732E+12 | 0.00 | 0.444998E+12 | 0.00 | 0.905194E+11 | 0.00 | 0.00 | 0.00 | 0.279759E+10 | 0.00 | 0.00 | 0.00 |
February | 0.982096E+11 | 0.00 | 0.686663E+12 | 0.00 | 0.141225E+12 | 0.00 | 0.00 | 0.00 | 0.293371E+10 | 0.00 | 0.00 | 0.00 |
March | 0.108732E+12 | 0.00 | 0.108252E+13 | 0.00 | 0.232905E+12 | 0.00 | 0.00 | 0.00 | 0.230189E+10 | 0.00 | 0.00 | 0.00 |
April | 0.105225E+12 | 0.00 | 0.138222E+13 | 0.00 | 0.318261E+12 | 0.00 | 0.00 | 0.00 | 0.306669E+09 | 0.00 | 0.00 | 0.00 |
May | 0.108732E+12 | 0.00 | 0.511626E+12 | 0.00 | 0.133663E+12 | 0.00 | 0.00 | 0.00 | 6852992.73 | 0.00 | 0.00 | 0.00 |
June | 0.105225E+12 | 0.00 | 0.837064E+12 | 0.00 | 0.221397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108732E+12 | 0.00 | 0.122400E+13 | 0.00 | 0.333106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108732E+12 | 0.00 | 0.156200E+13 | 0.00 | 0.423014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105225E+12 | 0.00 | 0.523959E+12 | 0.00 | 0.138622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108732E+12 | 0.00 | 0.839840E+12 | 0.00 | 0.207996E+12 | 0.00 | 0.00 | 0.00 | 76217406.34 | 0.00 | 0.00 | 0.00 |
November | 0.105225E+12 | 0.00 | 0.108010E+13 | 0.00 | 0.244530E+12 | 0.00 | 0.00 | 0.00 | 0.373168E+09 | 0.00 | 0.00 | 0.00 |
December | 0.108732E+12 | 0.00 | 0.138272E+13 | 0.00 | 0.281727E+12 | 0.00 | 0.00 | 0.00 | 0.526424E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128023E+13 | 0.00 | 0.115577E+14 | 0.00 | 0.276697E+13 | 0.00 | 0.00 | 0.00 | 0.140603E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.982096E+11 | 0.00 | 0.444998E+12 | 0.00 | 0.905194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108732E+12 | 0.00 | 0.156200E+13 | 0.00 | 0.423014E+12 | 0.00 | 0.00 | 0.00 | 0.526424E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141561E+10 | 0.00 | 0.709367E+10 | 0.00 | 0.143050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127862E+10 | 0.00 | 0.126066E+11 | 0.00 | 0.254796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141561E+10 | 0.00 | 0.207413E+11 | 0.00 | 0.437530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136995E+10 | 0.00 | 0.273148E+11 | 0.00 | 0.613162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141561E+10 | 0.00 | 0.999260E+10 | 0.00 | 0.253547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136995E+10 | 0.00 | 0.171275E+11 | 0.00 | 0.437805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141561E+10 | 0.00 | 0.255161E+11 | 0.00 | 0.669641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141561E+10 | 0.00 | 0.311180E+11 | 0.00 | 0.807538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136995E+10 | 0.00 | 0.106981E+11 | 0.00 | 0.272279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141561E+10 | 0.00 | 0.167686E+11 | 0.00 | 0.402947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136995E+10 | 0.00 | 0.211039E+11 | 0.00 | 0.466079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141561E+10 | 0.00 | 0.266661E+11 | 0.00 | 0.532104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166677E+11 | 0.00 | 0.226747E+12 | 0.00 | 0.529048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127862E+10 | 0.00 | 0.709367E+10 | 0.00 | 0.143050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141561E+10 | 0.00 | 0.311180E+11 | 0.00 | 0.807538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135044E+11 | 0.00 | 0.595877E+11 | 0.00 | 0.121272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121975E+11 | 0.00 | 0.114994E+12 | 0.00 | 0.233459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135044E+11 | 0.00 | 0.195417E+12 | 0.00 | 0.412954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130688E+11 | 0.00 | 0.259351E+12 | 0.00 | 0.582529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135044E+11 | 0.00 | 0.911620E+11 | 0.00 | 0.231852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130688E+11 | 0.00 | 0.159781E+12 | 0.00 | 0.408908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135044E+11 | 0.00 | 0.238496E+12 | 0.00 | 0.626748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135044E+11 | 0.00 | 0.296004E+12 | 0.00 | 0.769942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130688E+11 | 0.00 | 0.970280E+11 | 0.00 | 0.247288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135044E+11 | 0.00 | 0.155515E+12 | 0.00 | 0.374267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130688E+11 | 0.00 | 0.198729E+12 | 0.00 | 0.439425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135044E+11 | 0.00 | 0.250164E+12 | 0.00 | 0.500407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159003E+12 | 0.00 | 0.211623E+13 | 0.00 | 0.494905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121975E+11 | 0.00 | 0.595877E+11 | 0.00 | 0.121272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135044E+11 | 0.00 | 0.296004E+12 | 0.00 | 0.769942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136139E+10 | 0.00 | 0.540253E+10 | 0.00 | 0.111018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122964E+10 | 0.00 | 0.112145E+11 | 0.00 | 0.228643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136139E+10 | 0.00 | 0.194198E+11 | 0.00 | 0.411364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131747E+10 | 0.00 | 0.259871E+11 | 0.00 | 0.584412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136139E+10 | 0.00 | 0.931827E+10 | 0.00 | 0.237077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131747E+10 | 0.00 | 0.161883E+11 | 0.00 | 0.414380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136139E+10 | 0.00 | 0.241630E+11 | 0.00 | 0.634971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136139E+10 | 0.00 | 0.298490E+11 | 0.00 | 0.776330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131747E+10 | 0.00 | 0.990207E+10 | 0.00 | 0.252492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136139E+10 | 0.00 | 0.156485E+11 | 0.00 | 0.376914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131747E+10 | 0.00 | 0.198024E+11 | 0.00 | 0.438658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136139E+10 | 0.00 | 0.246890E+11 | 0.00 | 0.495433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160292E+11 | 0.00 | 0.211584E+12 | 0.00 | 0.496169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122964E+10 | 0.00 | 0.540253E+10 | 0.00 | 0.111018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136139E+10 | 0.00 | 0.298490E+11 | 0.00 | 0.776330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.440296E+09 | 0.00 | 0.127296E+09 | 0.00 | 0.00 | 0.135623E+11 | 0.00 | 0.35 |
February | 0.00 | 0.978537E+09 | 0.00 | 0.107213E+09 | 0.00 | 0.00 | 0.864517E+10 | 0.00 | 0.30 |
March | 0.00 | 0.311095E+10 | 0.00 | 80495813.95 | 0.00 | 0.00 | 0.563663E+10 | 0.00 | 0.25 |
April | 0.00 | 0.517217E+10 | 0.00 | 43772827.12 | 0.00 | 0.00 | 0.141945E+10 | 0.00 | 0.12 |
May | 0.00 | 0.156104E+10 | 0.00 | 444061.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.173033E+10 | 0.00 | 10558318.85 | 0.00 | 0.00 | 0.120980E+09 | 0.00 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.170706E+10 | 0.00 | 38004098.05 | 0.00 | 0.00 | 0.665038E+09 | 0.00 | 0.03 |
November | 0.00 | 0.830070E+10 | 0.00 | 80421416.86 | 0.00 | 0.00 | 0.190904E+10 | 0.00 | 0.18 |
December | 0.00 | 0.326951E+10 | 0.00 | 0.116819E+09 | 0.00 | 0.00 | 0.728380E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.262706E+11 | 0.00 | 0.605024E+09 | 0.00 | 0.00 | 0.392424E+11 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.830070E+10 | 0.00 | 0.127296E+09 | 0.00 | 0.00 | 0.135623E+11 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101370E+10 | 0.320185E+09 | 0.00 | 90664495.74 | 0.165842E+09 | 0.00 | 0.143045E+11 | 0.00 | 0.37 |
February | 0.796949E+09 | 0.140487E+10 | 0.00 | 76898864.10 | 0.349155E+09 | 0.00 | 0.903347E+10 | 0.00 | 0.37 |
March | 0.202492E+10 | 0.355542E+10 | 0.00 | 74316321.24 | 0.856613E+09 | 0.00 | 0.689130E+10 | 0.00 | 0.42 |
April | 0.159262E+10 | 0.896595E+10 | 0.00 | 34983680.12 | 0.492660E+10 | 0.00 | 0.207995E+10 | 0.00 | 0.47 |
May | 0.214166E+09 | 0.230696E+11 | 0.00 | 15586812.25 | 0.113594E+11 | 0.00 | 0.368481E+09 | 0.00 | 0.45 |
June | 22623798.64 | 0.414092E+11 | 0.00 | 2064094.95 | 0.188001E+11 | 0.00 | 18183691.53 | 0.00 | 0.46 |
July | 60783634.45 | 0.600648E+11 | 0.00 | 2924999.00 | 0.217029E+11 | 0.00 | 55548772.46 | 0.00 | 0.44 |
August | 0.00 | 0.716660E+11 | 0.00 | 0.00 | 0.168201E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.484448E+11 | 0.00 | 1274798.69 | 0.213907E+11 | 0.00 | 7092401.12 | 0.00 | 0.45 |
October | 0.237622E+09 | 0.310239E+11 | 0.00 | 13175967.42 | 0.116751E+11 | 0.00 | 0.351061E+09 | 0.00 | 0.46 |
November | 0.107136E+10 | 0.118372E+11 | 0.00 | 32962854.35 | 0.268995E+10 | 0.00 | 0.117507E+10 | 0.00 | 0.44 |
December | 0.174723E+10 | 0.232824E+10 | 0.00 | 87785593.17 | 0.104689E+10 | 0.00 | 0.825115E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.878198E+10 | 0.304090E+12 | 0.00 | 0.432638E+09 | 0.111783E+12 | 0.00 | 0.425358E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.320185E+09 | 0.00 | 0.00 | 0.165842E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.202492E+10 | 0.716660E+11 | 0.00 | 90664495.74 | 0.217029E+11 | 0.00 | 0.143045E+11 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.853791E+10 | 0.295307E+10 | 0.00 | 0.619131E+09 | 0.190707E+10 | 0.00 | 0.127732E+12 | 0.00 | 0.35 |
February | 0.755240E+10 | 0.125113E+11 | 0.00 | 0.518051E+09 | 0.286465E+10 | 0.00 | 0.796370E+11 | 0.00 | 0.34 |
March | 0.769257E+10 | 0.328847E+11 | 0.00 | 0.521981E+09 | 0.349190E+10 | 0.00 | 0.644869E+11 | 0.00 | 0.35 |
April | 0.562238E+10 | 0.798730E+11 | 0.00 | 0.234465E+09 | 0.335929E+11 | 0.00 | 0.213277E+11 | 0.00 | 0.36 |
May | 0.227139E+10 | 0.188588E+12 | 0.00 | 55598440.10 | 0.120745E+12 | 0.00 | 0.297646E+10 | 0.00 | 0.41 |
June | 0.246870E+09 | 0.315741E+12 | 0.00 | 7247498.08 | 0.238938E+12 | 0.00 | 0.210804E+09 | 0.00 | 0.43 |
July | 0.104146E+10 | 0.413649E+12 | 0.00 | 4036539.02 | 0.342544E+12 | 0.00 | 82858170.34 | 0.00 | 0.43 |
August | 0.00 | 0.482167E+12 | 0.00 | 0.00 | 0.322650E+12 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 3535270.73 | 0.359727E+12 | 0.00 | 5990944.70 | 0.258257E+12 | 0.00 | 0.132964E+09 | 0.00 | 0.41 |
October | 0.157790E+10 | 0.218991E+12 | 0.00 | 59407908.53 | 0.132873E+12 | 0.00 | 0.316763E+10 | 0.00 | 0.38 |
November | 0.177500E+10 | 0.105193E+12 | 0.00 | 0.216766E+09 | 0.130289E+11 | 0.00 | 0.109599E+11 | 0.00 | 0.34 |
December | 0.655226E+10 | 0.222300E+11 | 0.00 | 0.549758E+09 | 0.562170E+10 | 0.00 | 0.748362E+11 | 0.00 | 0.35 |
Annual Sum or Average | 0.428737E+11 | 0.223451E+13 | 0.00 | 0.279243E+10 | 0.147651E+13 | 0.00 | 0.385551E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.295307E+10 | 0.00 | 0.00 | 0.190707E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.853791E+10 | 0.482167E+12 | 0.00 | 0.619131E+09 | 0.342544E+12 | 0.00 | 0.127732E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365358E+10 | 0.192677E+09 | 0.00 | 43051684.61 | 0.201106E+09 | 0.00 | 0.851762E+10 | 0.00 | 0.33 |
February | 0.198634E+10 | 0.113661E+10 | 0.00 | 39494182.93 | 0.264918E+09 | 0.00 | 0.572594E+10 | 0.00 | 0.33 |
March | 0.943031E+09 | 0.298117E+10 | 0.00 | 44315095.12 | 0.265191E+09 | 0.00 | 0.555675E+10 | 0.00 | 0.34 |
April | 0.514837E+09 | 0.753825E+10 | 0.00 | 22038321.08 | 0.303630E+10 | 0.00 | 0.185607E+10 | 0.00 | 0.36 |
May | 0.208949E+09 | 0.185061E+11 | 0.00 | 5780207.03 | 0.112508E+11 | 0.00 | 0.272662E+09 | 0.00 | 0.41 |
June | 25539160.73 | 0.314031E+11 | 0.00 | 906622.23 | 0.230106E+11 | 0.00 | 19922276.78 | 0.00 | 0.43 |
July | 0.102079E+09 | 0.419457E+11 | 0.00 | 760426.62 | 0.321938E+11 | 0.00 | 11392186.28 | 0.00 | 0.43 |
August | 0.00 | 0.487614E+11 | 0.00 | 0.00 | 0.304024E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.360620E+11 | 0.00 | 524122.39 | 0.247604E+11 | 0.00 | 6971381.79 | 0.00 | 0.42 |
October | 0.172450E+09 | 0.215114E+11 | 0.00 | 5500115.53 | 0.127958E+11 | 0.00 | 0.285162E+09 | 0.00 | 0.38 |
November | 0.146733E+09 | 0.101322E+11 | 0.00 | 17401929.68 | 0.116769E+10 | 0.00 | 0.922376E+09 | 0.00 | 0.33 |
December | 0.169909E+10 | 0.198013E+10 | 0.00 | 39843153.71 | 0.610305E+09 | 0.00 | 0.536566E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.945262E+10 | 0.222151E+12 | 0.00 | 0.219616E+09 | 0.139959E+12 | 0.00 | 0.285405E+11 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.192677E+09 | 0.00 | 0.00 | 0.201106E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.365358E+10 | 0.487614E+11 | 0.00 | 44315095.12 | 0.321938E+11 | 0.00 | 0.851762E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.522581E+09 | 44595306.76 | 0.00 | 6696553.87 | 20846616.05 | 0.00 | 0.913827E+09 | 0.00 | 0.30 |
February | 0.312235E+09 | 0.206488E+09 | 0.00 | 6960442.14 | 44306086.94 | 0.00 | 0.655142E+09 | 0.00 | 0.33 |
March | 0.315177E+09 | 0.611613E+09 | 0.00 | 8044483.87 | 0.102394E+09 | 0.00 | 0.664330E+09 | 0.00 | 0.45 |
April | 0.209466E+09 | 0.190231E+10 | 0.00 | 4299975.88 | 0.449631E+09 | 0.00 | 0.240044E+09 | 0.00 | 0.57 |
May | 17467873.13 | 0.615895E+10 | 0.00 | 2727979.94 | 0.514970E+09 | 0.00 | 69637988.11 | 0.00 | 0.67 |
June | 707391.46 | 0.116710E+11 | 0.00 | 389233.70 | 0.624701E+09 | 0.00 | 5898243.16 | 0.00 | 0.72 |
July | 1826407.84 | 0.169598E+11 | 0.00 | 626817.00 | 0.444881E+09 | 0.00 | 17562299.82 | 0.00 | 0.75 |
August | 0.00 | 0.178686E+11 | 0.00 | 0.00 | 0.509257E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 0.00 | 0.122660E+11 | 0.00 | 183697.99 | 0.691472E+09 | 0.00 | 1044504.24 | 0.00 | 0.66 |
October | 28211688.00 | 0.629465E+10 | 0.00 | 1874631.85 | 0.717015E+09 | 0.00 | 49482751.11 | 0.00 | 0.58 |
November | 0.156220E+09 | 0.189717E+10 | 0.00 | 3224908.89 | 0.314899E+09 | 0.00 | 0.104721E+09 | 0.00 | 0.48 |
December | 0.324028E+09 | 0.326564E+09 | 0.00 | 7743703.35 | 0.131569E+09 | 0.00 | 0.658604E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.188792E+10 | 0.762078E+11 | 0.00 | 42772428.47 | 0.456594E+10 | 0.00 | 0.338029E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 44595306.76 | 0.00 | 0.00 | 20846616.05 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.522581E+09 | 0.178686E+11 | 0.00 | 8044483.87 | 0.717015E+09 | 0.00 | 0.913827E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272986E+09 | 34678862.08 | 0.00 | 5865740.82 | 12098283.43 | 0.00 | 0.829248E+09 | 0.00 | 0.36 |
February | 0.179474E+09 | 0.149492E+09 | 0.00 | 5613514.72 | 22474243.15 | 0.00 | 0.550954E+09 | 0.00 | 0.38 |
March | 0.203848E+09 | 0.452227E+09 | 0.00 | 5939275.11 | 61318993.15 | 0.00 | 0.473373E+09 | 0.00 | 0.50 |
April | 0.135891E+09 | 0.144478E+10 | 0.00 | 3259747.24 | 0.255158E+09 | 0.00 | 0.178519E+09 | 0.00 | 0.63 |
May | 8127655.56 | 0.482739E+10 | 0.00 | 2336360.36 | 0.223224E+09 | 0.00 | 60449442.26 | 0.00 | 0.80 |
June | 453930.58 | 0.856092E+10 | 0.00 | 271360.29 | 0.356962E+09 | 0.00 | 4051158.35 | 0.00 | 0.82 |
July | 1110963.97 | 0.121285E+11 | 0.00 | 397458.47 | 0.253917E+09 | 0.00 | 11586734.97 | 0.00 | 0.84 |
August | 0.00 | 0.127825E+11 | 0.00 | 0.00 | 0.325041E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.965668E+10 | 0.00 | 142007.56 | 0.237075E+09 | 0.00 | 824792.94 | 0.00 | 0.79 |
October | 13167528.92 | 0.501481E+10 | 0.00 | 1758352.90 | 0.300114E+09 | 0.00 | 56196747.29 | 0.00 | 0.68 |
November | 89405794.53 | 0.139578E+10 | 0.00 | 2540307.91 | 0.189886E+09 | 0.00 | 92526333.76 | 0.00 | 0.53 |
December | 0.235600E+09 | 0.213534E+09 | 0.00 | 5209788.26 | 84459203.78 | 0.00 | 0.431380E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.114007E+10 | 0.566613E+11 | 0.00 | 33333913.63 | 0.232173E+10 | 0.00 | 0.268911E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 34678862.08 | 0.00 | 0.00 | 12098283.43 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.272986E+09 | 0.127825E+11 | 0.00 | 5939275.11 | 0.356962E+09 | 0.00 | 0.829248E+09 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382530E+09 | 97488678.64 | 0.00 | 14449439.18 | 9555172.48 | 0.00 | 0.183702E+10 | 0.00 | 0.50 |
February | 0.260483E+09 | 0.342704E+09 | 0.00 | 12414807.82 | 18177050.17 | 0.00 | 0.111712E+10 | 0.00 | 0.50 |
March | 0.297222E+09 | 0.842000E+09 | 0.00 | 11094883.55 | 81289891.26 | 0.00 | 0.868879E+09 | 0.00 | 0.57 |
April | 0.207249E+09 | 0.221138E+10 | 0.00 | 4549798.28 | 0.391145E+09 | 0.00 | 0.248546E+09 | 0.00 | 0.61 |
May | 19476911.88 | 0.588305E+10 | 0.00 | 2461833.57 | 0.607066E+09 | 0.00 | 62613680.73 | 0.00 | 0.65 |
June | 1251708.52 | 0.105297E+11 | 0.00 | 329788.39 | 0.910794E+09 | 0.00 | 4863800.30 | 0.00 | 0.67 |
July | 2030886.24 | 0.160656E+11 | 0.00 | 563709.35 | 0.518442E+09 | 0.00 | 15518124.53 | 0.00 | 0.71 |
August | 0.00 | 0.181111E+11 | 0.00 | 0.00 | 0.519306E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.144052E+11 | 0.00 | 187436.78 | 0.389081E+09 | 0.00 | 1065300.37 | 0.00 | 0.75 |
October | 17322790.44 | 0.865498E+10 | 0.00 | 3008765.52 | 0.251048E+09 | 0.00 | 85399798.77 | 0.00 | 0.74 |
November | 0.125649E+09 | 0.302691E+10 | 0.00 | 6017194.48 | 0.185825E+09 | 0.00 | 0.190917E+09 | 0.00 | 0.69 |
December | 0.271658E+09 | 0.660480E+09 | 0.00 | 14387196.89 | 81428035.27 | 0.00 | 0.111446E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.158487E+10 | 0.808307E+11 | 0.00 | 69464853.83 | 0.396316E+10 | 0.00 | 0.554640E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 97488678.64 | 0.00 | 0.00 | 9555172.48 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.382530E+09 | 0.181111E+11 | 0.00 | 14449439.18 | 0.910794E+09 | 0.00 | 0.183702E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120962E+09 | 58470945.41 | 0.00 | 9061173.37 | 7755951.48 | 0.00 | 0.133186E+10 | 0.00 | 0.49 |
February | 60589220.58 | 0.250068E+09 | 0.00 | 9875317.53 | 7693428.73 | 0.00 | 0.106623E+10 | 0.00 | 0.60 |
March | 85809379.23 | 0.779318E+09 | 0.00 | 12426378.15 | 14350157.53 | 0.00 | 0.110931E+10 | 0.00 | 0.81 |
April | 37786972.64 | 0.261317E+10 | 0.00 | 6791776.26 | 28195030.25 | 0.00 | 0.453636E+09 | 0.00 | 0.96 |
May | 7789648.76 | 0.527667E+10 | 0.00 | 2152788.36 | 0.146166E+09 | 0.00 | 55875221.77 | 0.00 | 0.83 |
June | 435636.27 | 0.102681E+11 | 0.00 | 319888.34 | 0.207656E+09 | 0.00 | 4843059.58 | 0.00 | 0.94 |
July | 233374.76 | 0.150248E+11 | 0.00 | 556656.20 | 0.116801E+09 | 0.00 | 17930966.37 | 0.00 | 1.02 |
August | 0.00 | 0.169731E+11 | 0.00 | 0.00 | 0.123516E+09 | 0.00 | 0.00 | 0.00 | 1.07 |
September | 0.00 | 0.100086E+11 | 0.00 | 129602.31 | 0.232573E+09 | 0.00 | 730682.64 | 0.00 | 0.79 |
October | 8574461.48 | 0.581769E+10 | 0.00 | 1621610.01 | 0.129136E+09 | 0.00 | 51567777.12 | 0.00 | 0.76 |
November | 41054553.14 | 0.220119E+10 | 0.00 | 5423933.07 | 48510130.90 | 0.00 | 0.211012E+09 | 0.00 | 0.77 |
December | 87536455.08 | 0.564288E+09 | 0.00 | 13774720.16 | 17685239.65 | 0.00 | 0.125506E+10 | 0.00 | 0.77 |
Annual Sum or Average | 0.450771E+09 | 0.698354E+11 | 0.00 | 62133843.76 | 0.108004E+10 | 0.00 | 0.555806E+10 | 0.00 | 0.82 |
Minimum of Months | 0.00 | 58470945.41 | 0.00 | 0.00 | 7693428.73 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.120962E+09 | 0.169731E+11 | 0.00 | 13774720.16 | 0.232573E+09 | 0.00 | 0.133186E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.934020E+10 | 0.386230E+09 | 0.00 | 29997260.50 | 0.225646E+09 | 0.00 | 0.440879E+10 | 0.00 | 0.29 |
February | 0.513508E+10 | 0.187225E+10 | 0.00 | 36478305.60 | 0.433412E+09 | 0.00 | 0.412128E+10 | 0.00 | 0.31 |
March | 0.329170E+10 | 0.618422E+10 | 0.00 | 49171054.86 | 0.430296E+09 | 0.00 | 0.471919E+10 | 0.00 | 0.39 |
April | 0.106476E+10 | 0.189520E+11 | 0.00 | 27674458.41 | 0.353053E+10 | 0.00 | 0.221819E+10 | 0.00 | 0.50 |
May | 0.198170E+09 | 0.626847E+11 | 0.00 | 16244502.02 | 0.891223E+10 | 0.00 | 0.756481E+09 | 0.00 | 0.73 |
June | 19777490.14 | 0.119080E+12 | 0.00 | 2951501.17 | 0.156900E+11 | 0.00 | 69811256.12 | 0.00 | 0.83 |
July | 81768333.23 | 0.173054E+12 | 0.00 | 2754710.27 | 0.175633E+11 | 0.00 | 90723467.72 | 0.00 | 0.85 |
August | 0.00 | 0.182982E+12 | 0.00 | 0.00 | 0.192281E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 138616.95 | 0.118665E+12 | 0.00 | 1188691.05 | 0.202426E+11 | 0.00 | 25527958.51 | 0.00 | 0.73 |
October | 0.201850E+09 | 0.531027E+11 | 0.00 | 9003936.26 | 0.133799E+11 | 0.00 | 0.452771E+09 | 0.00 | 0.56 |
November | 0.554730E+09 | 0.183108E+11 | 0.00 | 17425586.65 | 0.164391E+10 | 0.00 | 0.828342E+09 | 0.00 | 0.40 |
December | 0.497624E+10 | 0.293961E+10 | 0.00 | 34842442.38 | 0.728491E+09 | 0.00 | 0.353609E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.248644E+11 | 0.758214E+12 | 0.00 | 0.227732E+09 | 0.102008E+12 | 0.00 | 0.212272E+11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.386230E+09 | 0.00 | 0.00 | 0.225646E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.934020E+10 | 0.182982E+12 | 0.00 | 49171054.86 | 0.202426E+11 | 0.00 | 0.471919E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.397846E+10 | 0.299597E+09 | 0.00 | 36683770.99 | 0.133688E+09 | 0.00 | 0.613036E+10 | 0.00 | 0.34 |
February | 0.232528E+10 | 0.153489E+10 | 0.00 | 39433686.82 | 0.152471E+09 | 0.00 | 0.497351E+10 | 0.00 | 0.39 |
March | 0.158518E+10 | 0.505073E+10 | 0.00 | 47055201.23 | 0.196464E+09 | 0.00 | 0.470222E+10 | 0.00 | 0.49 |
April | 0.537597E+09 | 0.170541E+11 | 0.00 | 29983602.42 | 0.136448E+10 | 0.00 | 0.231195E+10 | 0.00 | 0.65 |
May | 73343307.02 | 0.512285E+11 | 0.00 | 16150038.19 | 0.420217E+10 | 0.00 | 0.732280E+09 | 0.00 | 0.90 |
June | 11136924.41 | 0.932638E+11 | 0.00 | 2364718.08 | 0.766052E+10 | 0.00 | 55662440.10 | 0.00 | 0.97 |
July | 45359815.44 | 0.134728E+12 | 0.00 | 2078234.74 | 0.716361E+10 | 0.00 | 72318717.45 | 0.00 | 1.00 |
August | 0.00 | 0.146254E+12 | 0.00 | 0.00 | 0.774299E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 89318.71 | 0.989402E+11 | 0.00 | 970499.37 | 0.967265E+10 | 0.00 | 21139370.72 | 0.00 | 0.90 |
October | 56954279.06 | 0.475432E+11 | 0.00 | 11621334.68 | 0.555288E+10 | 0.00 | 0.598250E+09 | 0.00 | 0.70 |
November | 0.202317E+09 | 0.148760E+11 | 0.00 | 18053468.17 | 0.833330E+09 | 0.00 | 0.968648E+09 | 0.00 | 0.50 |
December | 0.219625E+10 | 0.228795E+10 | 0.00 | 34514581.75 | 0.450310E+09 | 0.00 | 0.402626E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.110120E+11 | 0.613061E+12 | 0.00 | 0.238909E+09 | 0.451256E+11 | 0.00 | 0.245926E+11 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.299597E+09 | 0.00 | 0.00 | 0.133688E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.397846E+10 | 0.146254E+12 | 0.00 | 47055201.23 | 0.967265E+10 | 0.00 | 0.613036E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.452251E+10 | 0.114553E+10 | 0.00 | 0.123457E+09 | 65500033.43 | 0.00 | 0.190154E+11 | 0.00 | 0.56 |
February | 0.332921E+10 | 0.392427E+10 | 0.00 | 0.102829E+09 | 0.120246E+09 | 0.00 | 0.115951E+11 | 0.00 | 0.57 |
March | 0.226255E+10 | 0.945215E+10 | 0.00 | 88122594.54 | 0.201268E+09 | 0.00 | 0.860532E+10 | 0.00 | 0.57 |
April | 0.886890E+09 | 0.241356E+11 | 0.00 | 34436325.89 | 0.265567E+10 | 0.00 | 0.271339E+10 | 0.00 | 0.59 |
May | 0.198897E+09 | 0.625040E+11 | 0.00 | 16096057.44 | 0.907679E+10 | 0.00 | 0.739302E+09 | 0.00 | 0.73 |
June | 20885067.16 | 0.110269E+12 | 0.00 | 2744276.00 | 0.180275E+11 | 0.00 | 64464933.82 | 0.00 | 0.79 |
July | 85873112.81 | 0.169172E+12 | 0.00 | 2572299.05 | 0.186670E+11 | 0.00 | 85397796.40 | 0.00 | 0.84 |
August | 0.00 | 0.198978E+12 | 0.00 | 0.00 | 0.166647E+11 | 0.00 | 0.00 | 0.00 | 0.90 |
September | 139010.97 | 0.156943E+12 | 0.00 | 1367241.52 | 0.142563E+11 | 0.00 | 29332769.97 | 0.00 | 0.90 |
October | 58913898.34 | 0.906009E+11 | 0.00 | 23030077.60 | 0.629435E+10 | 0.00 | 0.955049E+09 | 0.00 | 0.84 |
November | 0.266368E+09 | 0.342476E+11 | 0.00 | 44872512.99 | 0.547289E+09 | 0.00 | 0.193863E+10 | 0.00 | 0.71 |
December | 0.259774E+10 | 0.764313E+10 | 0.00 | 0.112127E+09 | 0.218162E+09 | 0.00 | 0.117665E+11 | 0.00 | 0.60 |
Annual Sum or Average | 0.142300E+11 | 0.869015E+12 | 0.00 | 0.551654E+09 | 0.867948E+11 | 0.00 | 0.575080E+11 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.114553E+10 | 0.00 | 0.00 | 65500033.43 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.452251E+10 | 0.198978E+12 | 0.00 | 0.123457E+09 | 0.186670E+11 | 0.00 | 0.190154E+11 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400318E+10 | 0.440469E+09 | 0.00 | 42331001.21 | 0.111701E+09 | 0.00 | 0.678688E+10 | 0.00 | 0.38 |
February | 0.240554E+10 | 0.201270E+10 | 0.00 | 45870754.48 | 0.165387E+09 | 0.00 | 0.539959E+10 | 0.00 | 0.45 |
March | 0.124803E+10 | 0.646277E+10 | 0.00 | 56311412.31 | 75696428.95 | 0.00 | 0.590298E+10 | 0.00 | 0.58 |
April | 0.342779E+09 | 0.209817E+11 | 0.00 | 29493041.30 | 0.847699E+09 | 0.00 | 0.240970E+10 | 0.00 | 0.72 |
May | 84498258.80 | 0.598334E+11 | 0.00 | 15094843.56 | 0.261051E+10 | 0.00 | 0.666478E+09 | 0.00 | 0.96 |
June | 10319347.21 | 0.109531E+12 | 0.00 | 2456861.57 | 0.386083E+10 | 0.00 | 62617738.44 | 0.00 | 1.06 |
July | 14851918.27 | 0.154854E+12 | 0.00 | 3084240.00 | 0.342397E+10 | 0.00 | 0.120614E+09 | 0.00 | 1.09 |
August | 0.00 | 0.171206E+12 | 0.00 | 0.00 | 0.440734E+10 | 0.00 | 0.00 | 0.00 | 1.13 |
September | 0.00 | 0.116243E+12 | 0.00 | 929670.47 | 0.588926E+10 | 0.00 | 21113913.66 | 0.00 | 0.98 |
October | 93849686.72 | 0.546509E+11 | 0.00 | 8980014.32 | 0.417780E+10 | 0.00 | 0.438488E+09 | 0.00 | 0.77 |
November | 0.213498E+09 | 0.178214E+11 | 0.00 | 20546887.94 | 0.563958E+09 | 0.00 | 0.966193E+09 | 0.00 | 0.57 |
December | 0.204072E+10 | 0.331069E+10 | 0.00 | 43489687.92 | 0.389304E+09 | 0.00 | 0.488941E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.104573E+11 | 0.717348E+12 | 0.00 | 0.268588E+09 | 0.265235E+11 | 0.00 | 0.276641E+11 | 0.00 | 0.76 |
Minimum of Months | 0.00 | 0.440469E+09 | 0.00 | 0.00 | 75696428.95 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.400318E+10 | 0.171206E+12 | 0.00 | 56311412.31 | 0.588926E+10 | 0.00 | 0.678688E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.943774E+09 | 23762308.11 | 0.00 | 2485569.39 | 25258740.91 | 378029.17 | 0.382463E+09 | 0.00 | 0.29 |
February | 0.484250E+09 | 0.162562E+09 | 0.00 | 3305518.93 | 44552290.89 | 0.00 | 0.390162E+09 | 0.00 | 0.31 |
March | 0.317994E+09 | 0.542161E+09 | 0.00 | 4699273.90 | 31832819.83 | 0.00 | 0.458604E+09 | 0.00 | 0.38 |
April | 0.131775E+09 | 0.172873E+10 | 0.00 | 2799743.40 | 0.292622E+09 | 0.00 | 0.180927E+09 | 0.00 | 0.49 |
May | 18261145.97 | 0.587247E+10 | 0.00 | 1606785.02 | 0.762259E+09 | 0.00 | 67315887.92 | 0.00 | 0.71 |
June | 2375490.31 | 0.114260E+11 | 0.00 | 306857.17 | 0.129958E+10 | 0.00 | 6385430.13 | 0.00 | 0.80 |
July | 7701172.72 | 0.166494E+11 | 0.00 | 306641.94 | 0.144758E+10 | 0.00 | 9446402.84 | 0.00 | 0.83 |
August | 0.00 | 0.176499E+11 | 0.00 | 0.00 | 0.159918E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 12021.36 | 0.115201E+11 | 0.00 | 103674.17 | 0.180837E+10 | 0.00 | 1338542.37 | 0.00 | 0.72 |
October | 21759786.63 | 0.517609E+10 | 0.00 | 872921.17 | 0.119884E+10 | 0.00 | 42483414.24 | 0.00 | 0.55 |
November | 59570678.04 | 0.173399E+10 | 0.00 | 1652737.28 | 0.144122E+09 | 0.00 | 72365814.14 | 0.00 | 0.39 |
December | 0.466477E+09 | 0.257675E+09 | 0.00 | 3033869.57 | 78897670.35 | 0.00 | 0.323021E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.245395E+10 | 0.727429E+11 | 0.00 | 21173591.93 | 0.873309E+10 | 378029.17 | 0.193451E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 23762308.11 | 0.00 | 0.00 | 25258740.91 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.943774E+09 | 0.176499E+11 | 0.00 | 4699273.90 | 0.180837E+10 | 378029.17 | 0.458604E+09 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.420648E+09 | 28433973.73 | 0.00 | 3463031.43 | 10000095.17 | 243101.25 | 0.596005E+09 | 0.00 | 0.35 |
February | 0.216511E+09 | 0.140378E+09 | 0.00 | 3971165.37 | 15816298.96 | 0.00 | 0.512041E+09 | 0.00 | 0.40 |
March | 0.160576E+09 | 0.466405E+09 | 0.00 | 4843670.00 | 13975437.70 | 0.00 | 0.476073E+09 | 0.00 | 0.50 |
April | 64347911.70 | 0.156674E+10 | 0.00 | 3155327.91 | 0.123085E+09 | 0.00 | 0.217091E+09 | 0.00 | 0.66 |
May | 6044875.64 | 0.487377E+10 | 0.00 | 1639929.21 | 0.343560E+09 | 0.00 | 66529684.96 | 0.00 | 0.89 |
June | 1165289.76 | 0.901041E+10 | 0.00 | 249479.98 | 0.688078E+09 | 0.00 | 5509813.29 | 0.00 | 0.96 |
July | 4232219.96 | 0.130840E+11 | 0.00 | 234432.71 | 0.568184E+09 | 0.00 | 7467122.25 | 0.00 | 0.99 |
August | 0.00 | 0.141584E+11 | 0.00 | 0.00 | 0.712662E+09 | 0.00 | 0.00 | 0.00 | 1.00 |
September | 16790.45 | 0.967421E+10 | 0.00 | 85261.24 | 0.869698E+09 | 0.00 | 1052367.74 | 0.00 | 0.90 |
October | 6246981.77 | 0.469508E+10 | 0.00 | 1195853.88 | 0.516466E+09 | 0.00 | 57235249.57 | 0.00 | 0.71 |
November | 23366619.49 | 0.148624E+10 | 0.00 | 1984236.88 | 74275749.19 | 0.00 | 87548231.28 | 0.00 | 0.52 |
December | 0.209950E+09 | 0.229431E+09 | 0.00 | 3297827.01 | 39737679.77 | 0.00 | 0.391055E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.111311E+10 | 0.594135E+11 | 0.00 | 24120215.62 | 0.397554E+10 | 243101.25 | 0.241761E+10 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 28433973.73 | 0.00 | 0.00 | 10000095.17 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.420648E+09 | 0.141584E+11 | 0.00 | 4843670.00 | 0.869698E+09 | 243101.25 | 0.596005E+09 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.473809E+09 | 93177852.79 | 0.00 | 11030653.92 | 6151298.83 | 0.00 | 0.182541E+10 | 0.00 | 0.54 |
February | 0.291732E+09 | 0.334117E+09 | 0.00 | 9824952.57 | 8758997.56 | 0.00 | 0.117073E+10 | 0.00 | 0.54 |
March | 0.246010E+09 | 0.802068E+09 | 0.00 | 8617811.22 | 16481432.60 | 0.00 | 0.824886E+09 | 0.00 | 0.55 |
April | 0.119065E+09 | 0.214490E+10 | 0.00 | 3538762.85 | 0.223992E+09 | 0.00 | 0.225168E+09 | 0.00 | 0.57 |
May | 18932929.99 | 0.584402E+10 | 0.00 | 1598481.82 | 0.771689E+09 | 0.00 | 65282929.80 | 0.00 | 0.71 |
June | 2372510.35 | 0.106174E+11 | 0.00 | 289379.67 | 0.150223E+10 | 0.00 | 6018564.24 | 0.00 | 0.76 |
July | 7756463.85 | 0.162814E+11 | 0.00 | 290065.62 | 0.154795E+10 | 0.00 | 9181635.98 | 0.00 | 0.82 |
August | 0.00 | 0.190879E+11 | 0.00 | 0.00 | 0.133992E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
September | 12006.28 | 0.148832E+11 | 0.00 | 119947.73 | 0.126871E+10 | 0.00 | 1546165.92 | 0.00 | 0.87 |
October | 6702141.36 | 0.851124E+10 | 0.00 | 2312870.40 | 0.578812E+09 | 0.00 | 94451212.32 | 0.00 | 0.81 |
November | 25543794.97 | 0.316962E+10 | 0.00 | 5493736.69 | 54804653.60 | 0.00 | 0.189327E+09 | 0.00 | 0.70 |
December | 0.240181E+09 | 0.692757E+09 | 0.00 | 10296732.85 | 23874482.21 | 0.00 | 0.112393E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.143212E+10 | 0.824619E+11 | 0.00 | 53413395.34 | 0.734336E+10 | 0.00 | 0.553593E+10 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 93177852.79 | 0.00 | 0.00 | 6151298.83 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.473809E+09 | 0.190879E+11 | 0.00 | 11030653.92 | 0.154795E+10 | 0.00 | 0.182541E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.434909E+09 | 36836318.14 | 0.00 | 3685790.95 | 8355536.56 | 0.00 | 0.619060E+09 | 0.00 | 0.37 |
February | 0.226118E+09 | 0.176502E+09 | 0.00 | 4343461.81 | 14504656.80 | 0.00 | 0.526951E+09 | 0.00 | 0.43 |
March | 0.145150E+09 | 0.551939E+09 | 0.00 | 5445123.23 | 5896499.32 | 0.00 | 0.550469E+09 | 0.00 | 0.56 |
April | 40831269.05 | 0.183517E+10 | 0.00 | 2975077.25 | 80381718.63 | 0.00 | 0.214967E+09 | 0.00 | 0.69 |
May | 7572320.21 | 0.544109E+10 | 0.00 | 1470055.86 | 0.224612E+09 | 0.00 | 59377158.16 | 0.00 | 0.92 |
June | 630307.30 | 0.101703E+11 | 0.00 | 249696.81 | 0.357574E+09 | 0.00 | 6186292.58 | 0.00 | 1.02 |
July | 1200327.52 | 0.144164E+11 | 0.00 | 334269.60 | 0.327737E+09 | 0.00 | 12251001.94 | 0.00 | 1.05 |
August | 0.00 | 0.160107E+11 | 0.00 | 0.00 | 0.423778E+09 | 0.00 | 0.00 | 0.00 | 1.08 |
September | 10194.90 | 0.109329E+11 | 0.00 | 84138.67 | 0.528620E+09 | 0.00 | 1106661.08 | 0.00 | 0.94 |
October | 9667958.29 | 0.514787E+10 | 0.00 | 886381.98 | 0.388062E+09 | 0.00 | 42235718.27 | 0.00 | 0.75 |
November | 22624254.22 | 0.166888E+10 | 0.00 | 2157244.56 | 52779815.75 | 0.00 | 88193019.48 | 0.00 | 0.56 |
December | 0.201340E+09 | 0.304414E+09 | 0.00 | 3856494.98 | 35833870.83 | 0.00 | 0.448597E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.109005E+10 | 0.666931E+11 | 0.00 | 25487735.72 | 0.244814E+10 | 0.00 | 0.256939E+10 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 36836318.14 | 0.00 | 0.00 | 5896499.32 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.434909E+09 | 0.160107E+11 | 0.00 | 5445123.23 | 0.528620E+09 | 0.00 | 0.619060E+09 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 51106414.09 | 0.00 | 6401640.04 | 0.00 | 0.00 | 0.209462E+09 | 0.00 | 0.58 |
February | 0.00 | 0.137674E+09 | 0.00 | 8036880.91 | 0.00 | 0.00 | 72142553.49 | 0.00 | 0.58 |
March | 0.00 | 0.210274E+09 | 0.00 | 12997500.26 | 0.00 | 0.00 | 53607279.85 | 0.00 | 0.59 |
April | 0.00 | 0.494930E+09 | 0.00 | 4966205.28 | 0.00 | 0.00 | 9408109.54 | 0.00 | 0.59 |
May | 0.00 | 0.845828E+09 | 0.00 | 111596.46 | 0.00 | 0.00 | 623437.01 | 0.00 | 0.59 |
June | 0.00 | 0.137988E+10 | 0.00 | 4972.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.181545E+10 | 0.00 | 6198.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.183106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.145370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.104213E+10 | 0.00 | 417767.03 | 0.00 | 0.00 | 714152.41 | 0.00 | 0.59 |
November | 0.00 | 0.543652E+09 | 0.00 | 1246862.75 | 0.00 | 0.00 | 1400781.68 | 0.00 | 0.58 |
December | 0.00 | 0.239822E+09 | 0.00 | 14917810.81 | 0.00 | 0.00 | 52943684.79 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.100455E+11 | 0.00 | 49107434.35 | 0.00 | 0.00 | 0.400302E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 51106414.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.183106E+10 | 0.00 | 14917810.81 | 0.00 | 0.00 | 0.209462E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.470246E+09 | 0.00 | 50861691.97 | 0.00 | 0.00 | 0.218483E+10 | 0.00 | 0.58 |
February | 0.00 | 0.135166E+10 | 0.00 | 72023349.99 | 0.00 | 0.00 | 0.744970E+09 | 0.00 | 0.58 |
March | 0.00 | 0.209273E+10 | 0.00 | 0.122051E+09 | 0.00 | 0.00 | 0.545478E+09 | 0.00 | 0.59 |
April | 0.00 | 0.494929E+10 | 0.00 | 47514777.40 | 0.00 | 0.00 | 95735966.53 | 0.00 | 0.59 |
May | 0.00 | 0.833608E+10 | 0.00 | 1036713.19 | 0.00 | 0.00 | 6579062.37 | 0.00 | 0.59 |
June | 0.00 | 0.137163E+11 | 0.00 | 57507.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.180912E+11 | 0.00 | 61096.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.185056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103447E+11 | 0.00 | 3892516.52 | 0.00 | 0.00 | 7566872.12 | 0.00 | 0.59 |
November | 0.00 | 0.541450E+10 | 0.00 | 11772338.13 | 0.00 | 0.00 | 15138662.51 | 0.00 | 0.58 |
December | 0.00 | 0.238988E+10 | 0.00 | 0.139693E+09 | 0.00 | 0.00 | 0.540043E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.999791E+11 | 0.00 | 0.448964E+09 | 0.00 | 0.00 | 0.414035E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.470246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.185056E+11 | 0.00 | 0.139693E+09 | 0.00 | 0.00 | 0.218483E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 45812485.99 | 0.00 | 4182909.84 | 0.00 | 0.00 | 0.225801E+09 | 0.00 | 0.58 |
February | 0.00 | 0.134714E+09 | 0.00 | 6808864.22 | 0.00 | 0.00 | 75818538.98 | 0.00 | 0.58 |
March | 0.00 | 0.209301E+09 | 0.00 | 11981679.09 | 0.00 | 0.00 | 54909689.69 | 0.00 | 0.59 |
April | 0.00 | 0.494857E+09 | 0.00 | 4725666.63 | 0.00 | 0.00 | 9594944.41 | 0.00 | 0.59 |
May | 0.00 | 0.836611E+09 | 0.00 | 101743.05 | 0.00 | 0.00 | 657638.87 | 0.00 | 0.59 |
June | 0.00 | 0.137358E+10 | 0.00 | 5610.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.181071E+10 | 0.00 | 5903.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.184844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103521E+10 | 0.00 | 383981.01 | 0.00 | 0.00 | 765303.77 | 0.00 | 0.59 |
November | 0.00 | 0.541333E+09 | 0.00 | 1151352.11 | 0.00 | 0.00 | 1574784.50 | 0.00 | 0.58 |
December | 0.00 | 0.238756E+09 | 0.00 | 13642260.65 | 0.00 | 0.00 | 54466543.46 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.100056E+11 | 0.00 | 42989970.56 | 0.00 | 0.00 | 0.423589E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 45812485.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.184844E+10 | 0.00 | 13642260.65 | 0.00 | 0.00 | 0.225801E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.143910E+10 | 0.00 | 0.343295E+09 | 0.00 | 0.00 | 0.440809E+10 | 0.00 | 0.66 |
February | 0.00 | 0.312099E+10 | 0.00 | 0.398468E+09 | 0.00 | 0.00 | 0.152701E+10 | 0.00 | 0.66 |
March | 0.00 | 0.450558E+10 | 0.00 | 0.615328E+09 | 0.00 | 0.00 | 0.112462E+10 | 0.00 | 0.66 |
April | 0.00 | 0.106003E+11 | 0.00 | 0.213102E+09 | 0.00 | 0.00 | 0.167589E+09 | 0.00 | 0.66 |
May | 0.00 | 0.194409E+11 | 0.00 | 5721004.14 | 0.00 | 0.00 | 13771974.08 | 0.00 | 0.66 |
June | 0.00 | 0.306812E+11 | 0.00 | 133357.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.397613E+11 | 0.00 | 590889.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.418742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.335086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.231796E+11 | 0.00 | 21595179.87 | 0.00 | 0.00 | 12910218.97 | 0.00 | 0.66 |
November | 0.00 | 0.118142E+11 | 0.00 | 58577597.46 | 0.00 | 0.00 | 24360001.82 | 0.00 | 0.66 |
December | 0.00 | 0.504861E+10 | 0.00 | 0.707962E+09 | 0.00 | 0.00 | 0.105128E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.224975E+12 | 0.00 | 0.236477E+10 | 0.00 | 0.00 | 0.832963E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.143910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.418742E+11 | 0.00 | 0.707962E+09 | 0.00 | 0.00 | 0.440809E+10 | 0.00 | 0.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.255660E+12 | 0.237665E+10 | 0.00 | 0.465299E+12 | 0.143484E+13 |
February | 0.288057E+12 | 0.187465E+10 | 0.00 | 0.290824E+12 | 0.190994E+13 |
March | 0.352915E+12 | 0.822489E+09 | 0.00 | 0.188112E+12 | 0.290554E+13 |
April | 0.371076E+12 | -0.197438E+10 | 0.00 | -0.174537E+12 | 0.376003E+13 |
May | 0.377708E+12 | -0.569273E+10 | 0.00 | -0.690113E+12 | 0.371651E+13 |
June | 0.359412E+12 | -0.113104E+11 | 0.00 | -0.136531E+13 | 0.491155E+13 |
July | 0.349873E+12 | -0.153266E+11 | 0.00 | -0.191941E+13 | 0.610574E+13 |
August | 0.332876E+12 | -0.151368E+11 | 0.00 | -0.205541E+13 | 0.689189E+13 |
September | 0.291539E+12 | -0.119454E+11 | 0.00 | -0.157239E+13 | 0.462015E+13 |
October | 0.246708E+12 | -0.617660E+10 | 0.00 | -0.855177E+12 | 0.409569E+13 |
November | 0.202517E+12 | -0.135134E+10 | 0.00 | -0.214264E+12 | 0.336524E+13 |
December | 0.215858E+12 | 0.111646E+10 | 0.00 | 0.227148E+12 | 0.297951E+13 |
Annual Sum or Average | 0.364420E+13 | -0.627241E+11 | 0.00 | -0.767522E+13 | 0.466966E+14 |
Minimum of Months | 0.202517E+12 | -0.153266E+11 | 0.00 | -0.205541E+13 | 0.143484E+13 |
Maximum of Months | 0.377708E+12 | 0.237665E+10 | 0.00 | 0.465299E+12 | 0.689189E+13 |