Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:22:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30495.05 | 658.35 | 658.35 |
Net Site Energy | 30495.05 | 658.35 | 658.35 |
Total Source Energy | 88039.14 | 1900.66 | 1900.66 |
Net Source Energy | 88039.14 | 1900.66 | 1900.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4099.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 751.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2518.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 385.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2383.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 239.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 182.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.64 |
Humidification | 2091.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.14 |
Heat Recovery | 47.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 553.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26395.83 | 4099.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4340.95 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4099.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 751.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2518.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 385.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2383.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 239.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 182.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.64 |
Humidification | General | 2091.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.14 |
Heat Recovery | General | 47.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 553.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4099.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 751.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2518.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 385.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2383.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 239.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 182.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.64 |
Humidification | Unassigned | 2091.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.14 |
Heat Recovery | Unassigned | 47.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 553.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 133.90 | 88.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 373.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 569.85 | 88.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 133.90 | 88.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 373.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 569.85 | 88.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26395.826 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26395.826 | 100.00 |
Total On-Site and Utility Electric Sources | 26395.826 | 100.00 |
Total Electricity End Uses | 26395.826 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1.60 | 0.04 |
Air to Air Heat Recovery for Heating | 3921.07 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3922.67 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4340.95 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4340.95 | 100.00 |
Total Water End Uses | 4340.95 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 230.17 |
Time Setpoint Not Met During Occupied Cooling | 2845.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-AUG-15:39 | 27-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 20-JUL-15:09 |
Heating | 0.00 | 2644766.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 314575.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233266.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 270164.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38878.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 44938.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 46401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43534.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1987468.20 | 2644766.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2644766.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 314575.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 270164.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 38878.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 44938.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 46401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 43534.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4443.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2379.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7975.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1219.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8127.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7549.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 759.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 576.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6624.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 149.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1752.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 83595.58 | 4443.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 95.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 172.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1804.73 | 95.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 95.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 172.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 12.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1804.73 | 95.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.16 | 0.410836 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.56 | 0.342108 | 0.291000 | 1.62 | 0.912289 | 0.500000 | 0.001114 | 0.000194 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.30 | 0.363680 | 0.309000 | 16.16 | 0.969813 | 0.500000 | 0.001048 | 0.003928 | 16.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.14 | 0.370249 | 0.315000 | 1.62 | 0.987329 | 0.500000 | 0.001029 | 0.001000 | 3.46 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.958681 | 0.249114 | 0.212000 | 0.203240 | 0.664303 | 0.500000 | 0.001529 | 0.000164 | 0.567145 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.36 | 0.113001 | 0.096000 | 0.130751 | 0.301335 | 0.500000 | 0.003372 | 0.000112 | 0.388788 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.07 | 0.115265 | 0.098000 | 0.203054 | 0.307372 | 0.500000 | 0.003305 | 0.000179 | 0.619531 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.60 | 0.096358 | 0.082000 | 0.130973 | 0.300000 | 0.500000 | 0.003954 | 0.000088 | 0.305693 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.91 | 0.268147 | 0.228000 | 2.03 | 0.715058 | 0.500000 | 0.001421 | 0.002185 | 7.57 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.61 | 0.300000 | 0.500000 | 0.003616 | 0.001451 | 5.03 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 21.91 | 0.109012 | 0.093000 | 2.04 | 0.300000 | 0.500000 | 0.003495 | 0.002172 | 7.52 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.84 | 0.103723 | 0.088000 | 1.31 | 0.300000 | 0.500000 | 0.003673 | 0.001386 | 4.80 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.02 | 0.234682 | 0.221000 | 0.224898 | 0.625818 | 0.500000 | 0.001623 | 0.000294 | 1.02 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.46 | 0.105619 | 0.090000 | 0.131145 | 0.300000 | 0.500000 | 0.003607 | 0.000194 | 0.670577 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.26 | 0.105511 | 0.090000 | 0.203717 | 0.300000 | 0.500000 | 0.003611 | 0.000292 | 1.01 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.53 | 0.100501 | 0.085000 | 0.130168 | 0.300000 | 0.500000 | 0.003791 | 0.000189 | 0.656168 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22145.97 | 0.000194 | 463.86 | |
CORE_MID VAV BOX REHEAT COIL | 449013.82 | 0.003928 | 11050.60 | |
CORE_TOP VAV BOX REHEAT COIL | 114254.13 | 0.001000 | 3015.07 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18728.90 | 0.000164 | 494.06 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12837.05 | 0.000112 | 338.61 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20454.86 | 0.000179 | 539.54 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10100.05 | 0.000088 | 266.50 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 249802.34 | 0.002185 | 6587.79 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 165839.20 | 0.001451 | 4373.41 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 248322.89 | 0.002172 | 6548.81 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 158429.75 | 0.001386 | 4178.16 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33569.72 | 0.000294 | 885.12 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22120.30 | 0.000194 | 583.23 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33397.21 | 0.000292 | 880.57 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21645.49 | 0.000189 | 570.72 | |
VAV_BOT WITH REHEAT HEATING COIL | 125824.03 | 0.001101 | 1803.56 | |
VAV_MID WITH REHEAT HEATING COIL | 1279281.37 | 0.011192 | 17883.09 | |
VAV_TOP WITH REHEAT HEATING COIL | 126834.50 | 0.001110 | 1816.45 | |
CAV_BAS HEATING COIL | 305534.04 | 0.000875 | 2622.58 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.505963 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.87 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.491630 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.92 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.77 | 2.29 | 11.55 | 2.96 | 9.42 | 9.42 | 0.300000 | 0.314042 | 9.42 |
VAV_MID WITH REHEAT | 56.28 | 22.85 | 112.56 | 37.29 | 87.68 | 87.68 | 0.300000 | 0.425330 | 87.68 |
VAV_TOP WITH REHEAT | 5.70 | 2.31 | 11.41 | 6.81 | 9.47 | 9.47 | 0.300000 | 0.719617 | 9.47 |
CAV_BAS | 0.000000 | 0.000000 | 5.16 | 1.20 | 5.16 | 5.16 | 1.00 | 0.232807 | 5.16 |
AIRLOOP DATACENTER BASEMENT | 24.92 | 24.92 | 24.92 | 24.92 | 24.92 | 24.92 | 1.00 | 0.999998 | 24.92 |
AIRLOOP DATACENTER BOT | 0.505963 | 0.505963 | 0.505963 | 0.505963 | 0.505963 | 0.505963 | 1.00 | 1.00 | 0.505963 |
AIRLOOP DATACENTER MID | 4.87 | 4.87 | 4.87 | 4.87 | 4.87 | 4.87 | 1.00 | 1.00 | 4.87 |
AIRLOOP DATACENTER TOP | 0.491630 | 0.491630 | 0.491630 | 0.491630 | 0.491630 | 0.491630 | 1.00 | 1.00 | 0.491630 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.42 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 87.68 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.47 | |
CAV_BAS_OA_CONTROLLER | 5.16 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.92 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.505963 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.87 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.491630 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
CAV_BAS OA HEAT RECOVERY | 1.20 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.74 | 6.67 | 10.91 | 0.007266 | 0.007000 | 164773.70 | 0.004713 | 9.42 |
VAV_MID WITH REHEAT COOLING COIL | 24.80 | 6.67 | 10.91 | 0.007280 | 0.007000 | 1543608.25 | 0.044147 | 87.68 |
VAV_TOP WITH REHEAT COOLING COIL | 24.73 | 6.67 | 10.91 | 0.007264 | 0.007000 | 165461.91 | 0.004732 | 9.47 |
CAV_BAS COOLING COIL | 24.76 | 6.67 | 10.90 | 0.007404 | 0.007000 | 92503.33 | 0.002646 | 5.16 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.42 |
VAV_MID WITH REHEAT FAN | 87.68 |
VAV_TOP WITH REHEAT FAN | 9.47 |
CAV_BAS FAN | 5.16 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004713 | 0.000101 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001101 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.044147 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011192 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004732 | 0.000101 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001110 | |
CAV_BAS_COOLC_CONTROLLER | 0.002646 | 0.000180 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.92 | 508417.12 | 322256.01 | 0.012451 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.505963 | 10038.63 | 6434.55 | 0.000246 |
AIRLOOP DATACENTER MID COOLING COIL | 4.87 | 96683.69 | 61966.46 | 0.002368 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.491630 | 9754.97 | 6252.26 | 0.000239 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.92 | 24.92 | 24.92 | 24.92 | 508417.12 | 508417.12 | 33013.32 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.505963 | 0.505963 | 0.505963 | 0.505963 | 10038.63 | 10038.63 | 1525.08 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.87 | 4.87 | 4.87 | 4.87 | 96683.69 | 96683.69 | 15250.79 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.491630 | 0.491630 | 0.491630 | 0.491630 | 9754.97 | 9754.97 | 1525.08 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.92 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.505963 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.87 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.491630 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.92 | 508417.12 | 0.012451 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.505963 | 10038.63 | 0.000246 |
AIRLOOP DATACENTER MID HEATING COIL | 4.87 | 96683.69 | 0.002368 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.491630 | 9754.97 | 0.000239 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 33013.32 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1525.08 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 15250.79 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1525.08 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000226 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.056237 | 9090.92 | |
HEATSYS1 PUMP | 0.028105 | 8380.26 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.056237 | 6.75 |
HEATSYS1 | 0.028105 | 3.37 |
COOLSYS1_SUPPLY | 0.056237 | 6.75 |
SINGLE WATER PLANT LOOP | 0.015304 | 1.84 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.056237 | 0.056237 | 236056.08 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3212601.60 | 3212601.60 | 0.028105 |
CENTRAL BOILER | 630378.10 | 617814.60 | 0.015304 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.028119 | 3146.98 |
COOLSYS1 CHILLER2 PUMP | 0.028119 | 3146.98 |
PLANT CIRC PUMP | 0.015304 | 3864.54 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.056237 | 0.028256 | 987969.42 | 987970.21 | 0.050780 |
COOLSYS1 CHILLER2 | 0.056237 | 0.028256 | 987969.42 | 987970.21 | 0.050780 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015304 | 151953.63 | 76923.45 | 75976.82 | 7004.20 | 46154.07 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.101559 | 12.19 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.101559 | 24894.93 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 38.73 | 1184074.66 | 7.75 | 148009.33 |
TOWERWATERSYS COOLTOWER 2 | 38.73 | 1184074.66 | 7.75 | 148009.33 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.051233 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.6685 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.6266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 0.8399 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.429 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.023 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
47 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
48 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
49 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
50 | 9 | -0.21299096E-14 | 0.28894800E-16 | -0.16188973E-09 | 0.38579871E-16 |
51 | 8 | 0.23581069E-07 | 0.91092976E-13 | 0.39549172E-03 | -0.26812487E-09 |
52 | 7 | -0.12768924E-01 | 0.46460358E-08 | -0.23844895E-01 | 0.14518732E-03 |
53 | 6 | 0.41967891 | 0.16074080E-05 | 0.48427557 | -0.49166618E-02 |
54 | 5 | -5.3303803 | 0.59734123E-04 | -4.5347620 | 0.64917525E-01 |
55 | 4 | 33.621223 | 0.48654995E-03 | 21.805629 | -0.43033321 |
56 | 3 | -112.54166 | 0.10563465E-02 | -56.346116 | 1.5341997 |
57 | 2 | 198.43470 | 0.59216919E-03 | 78.537424 | -2.9214177 |
58 | 1 | -171.64594 | 0.63016798E-04 | -55.447962 | 2.7540249 |
59 | 0 | 57.057407 | 0.35742999E-06 | 15.527221 | |
60 | 9 | 0.75071082E-15 | -0.32535972E-15 | -0.16381989E-09 | -0.10550086E-16 |
61 | 8 | 0.23851931E-07 | 0.85286513E-13 | 0.39826052E-03 | -0.27120466E-09 |
62 | 7 | -0.12851287E-01 | 0.43498253E-08 | -0.23963405E-01 | 0.14612382E-03 |
63 | 6 | 0.42191652 | 0.15033070E-05 | 0.48617502 | -0.49430380E-02 |
64 | 5 | -5.3522123 | 0.55813756E-04 | -4.5493227 | 0.65188236E-01 |
65 | 4 | 33.717764 | 0.45423475E-03 | 21.862480 | -0.43161506 |
66 | 3 | -112.74698 | 0.98544308E-03 | -56.458481 | 1.5371663 |
67 | 2 | 198.63811 | 0.55204883E-03 | 78.640589 | -2.9246480 |
68 | 1 | -171.72104 | 0.58710654E-04 | -55.478167 | 2.7553411 |
69 | 0 | 57.057407 | 0.33274243E-06 | 15.522401 | |
70 | 9 | -0.19159632E-14 | 0.31671484E-16 | -0.15392039E-09 | 0.39566669E-16 |
71 | 8 | 0.22464981E-07 | 0.11360995E-12 | 0.38396804E-03 | -0.25543456E-09 |
72 | 7 | -0.12425740E-01 | 0.58612731E-08 | -0.23350983E-01 | 0.14128520E-03 |
73 | 6 | 0.41035492 | 0.20371532E-05 | 0.47635123 | -0.48067540E-02 |
74 | 5 | -5.2394009 | 0.76003274E-04 | -4.4739732 | 0.63789410E-01 |
75 | 4 | 33.218868 | 0.62128211E-03 | 21.568188 | -0.42499095 |
76 | 3 | -111.68581 | 0.13531787E-02 | -55.876772 | 1.5218344 |
77 | 2 | 197.58670 | 0.76073673E-03 | 78.106675 | -2.9079511 |
78 | 1 | -171.33281 | 0.81169205E-04 | -55.322159 | 2.7485368 |
79 | 0 | 57.057407 | 0.46182178E-06 | 15.547553 | |
80 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
81 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
82 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
83 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
84 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
85 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
86 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
87 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
88 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
89 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
90 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
91 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
92 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
93 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
94 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
95 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
96 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
97 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
98 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
99 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
100 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
101 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
102 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
103 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
104 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
105 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
106 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
107 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
108 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
109 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
110 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
111 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
112 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
113 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
114 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
115 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
116 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
117 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
118 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
119 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
120 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
121 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
122 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
123 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
124 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
125 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
126 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
127 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 35 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 36 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
3 | WINDOW_U_0.262_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
4 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 38 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3411E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3437E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8181E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.8204E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2846E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2860E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7516E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7524E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3986E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5676E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8686E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0022E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3192E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4238E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7727E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8295E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1682 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1043 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1979 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1267 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.4876E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9884E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9911E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7364E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.4197E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6934E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8943E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0174E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3305E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4681E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7732E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8311E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3410E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3443E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8180E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.8212E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2845E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2863E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7515E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7523E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.1029E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.2504E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.4496E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9779E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9476E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0939E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7036E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7426E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.5299E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9298E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.9253E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0948E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3180E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1046E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1958E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9434E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8218E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.9639E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0516E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.1622E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9119E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9549E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7037E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7431E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5338E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5366E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0256E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0281E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4653E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4669E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7517E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7524E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5956E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7569E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0814E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2223E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5040E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5986E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7733E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8312E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 6.3750E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3357E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0799E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6352E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0825E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5564E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.9911E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7359E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5926E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7667E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0746E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2158E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4946E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5666E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7728E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8296E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5336E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5362E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0254E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0276E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4651E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4663E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7515E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7523E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1314E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2890E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6659E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7854E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1236E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1579E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7038E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7432E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8270E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5654E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1221E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1696E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8938E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4775E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1958E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9434E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2452E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.5752E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8300E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2082E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1540E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2653E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7035E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7425E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1897 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1479 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2210 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1788 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1107 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.0310E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1092E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0183E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1121 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.9536E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1167 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 7.2417E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6334E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5128E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2633E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0530E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.7135E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 5.0479E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.2558E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.0959E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1470E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7194E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1093E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0178E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.1338E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 5.0551E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3440E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5618E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0392E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6939E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2633E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0530E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1896 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1480 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2208 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1788 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1108 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.0438E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1223E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0250E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1121 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.9637E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1168 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 7.2524E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.6459E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5222E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2764E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0597E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.7143E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 5.0542E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.2568E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.1010E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1557E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7248E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1223E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0245E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.1361E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 5.0620E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3465E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5681E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0499E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7014E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2764E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0597E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 70318.35619 | 70318.35619 | 5.15516 | 5.15516 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 75834.76920 | 75834.76920 | 5.55977 | 5.55977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 6109.59975 | 6109.59975 | 0.26304 | 1.07782 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 713564.70830 | 713564.70830 | 52.29993 | 52.29993 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 288825.77813 | 288825.77813 | 12.37604 | 12.37604 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 70093.77373 | 70093.77373 | 5.13721 | 5.13721 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 79987.29068 | 79987.29068 | 3.45703 | 3.45703 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12954.23408 | 12954.23408 | 0.95868 | 0.95868 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13107.47555 | 13107.47555 | 0.56714 | 0.56714 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 18404.14201 | 18404.14201 | 1.36199 | 1.36199 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79000 | 6.99871E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8983.44870 | 8983.44870 | 0.38879 | 0.38879 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 27998.06748 | 27998.06748 | 2.07198 | 2.07198 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27.31500 | 7.00701E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14314.14799 | 14314.14799 | 0.61953 | 0.61953 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21582.96740 | 21582.96740 | 1.59723 | 1.59723 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7070.16831 | 7070.16831 | 0.30569 | 0.30569 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 120347.52873 | 120347.52873 | 8.90634 | 8.90634 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 21.22900 | 6.99788E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 174780.64776 | 174780.64776 | 7.56909 | 7.56909 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 197397.36789 | 197397.36789 | 14.60823 | 14.60823 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 116031.00190 | 116031.00190 | 5.02525 | 5.02525 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 296040.82964 | 296040.82964 | 21.90827 | 21.90827 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 173746.37846 | 173746.37846 | 7.52417 | 7.52417 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 200503.76998 | 200503.76998 | 14.83811 | 14.83811 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 110850.82597 | 110850.82597 | 4.80035 | 4.80035 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12405.82592 | 12405.82592 | 0.91809 | 0.91809 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 23483.29864 | 23483.29864 | 1.01764 | 1.01764 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 19690.41638 | 19690.41638 | 1.45717 | 1.45717 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15473.80302 | 15473.80302 | 0.67058 | 0.67058 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 30586.34979 | 30586.34979 | 2.26352 | 2.26352 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 23362.69739 | 23362.69739 | 1.01240 | 1.01240 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20693.21694 | 20693.21694 | 1.53138 | 1.53138 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 15141.82086 | 15141.82086 | 0.65617 | 0.65617 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8668.11807 | 8668.11807 | 0.50596 | 0.50596 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 83476.58303 | 83476.58303 | 4.87260 | 4.87260 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8422.54774 | 8422.54774 | 0.49163 | 0.49163 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371210.94647 | 426892.58844 | 21.66753 | 24.91766 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.11800 | 6.99333E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | -41.90000 | 6.45023E-005 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 133207.11 | 9.42225 | 9.42225 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 131935.76 | 2.95898 | 2.95898 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1237577.17 | 87.68469 | 87.68469 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1316610.99 | 37.29490 | 37.29490 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 134169.76 | 9.46867 | 9.46867 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 132205.52 | 6.81381 | 6.81381 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:00:00 |
7 | CAV_BAS | Cooling | Sensible | 65169.44 | 5.15516 | 5.15516 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 117086.28 | 1.20016 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 421061.53 | 24.91770 | 24.91770 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 33013.32 | 0.33839 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8461.42 | 0.50596 | 0.50596 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1525.08 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81450.53 | 4.87260 | 4.87260 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 15250.79 | 0.15632 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8218.99 | 0.49163 | 0.49163 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1525.08 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.15516 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.41084 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.55977 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34211 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61789 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91229 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11368E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93743E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61789 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22145.96980 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93743E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 463.86435 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.29993 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36368 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.16068 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96981 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04762E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.92817E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.16068 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 449013.82003 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.92817E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11050.60064 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.13721 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37025 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61822 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98733 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02904E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.99545E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.45703 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114254.12629 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.99545E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3015.06746 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95868 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24911 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21200 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20324 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66430 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52942E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63849E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56714 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18728.90405 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63849E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 494.05725 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36199 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11300 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.60000E-002 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13075 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30133 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37166E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12304E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38879 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12837.05324 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12304E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 338.61021 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07198 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11526 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.80000E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20305 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30737 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30544E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78948E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61953 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20454.86071 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78948E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 539.53859 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59723 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.63576E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.20000E-002 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13097 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95402E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.83597E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30569 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10100.05445 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.83597E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 266.49516 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.90634 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26815 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03064 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71506 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42086E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.18538E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.56909 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 249802.34251 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18538E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6587.79314 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.60823 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61634E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45083E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.02525 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 165839.20055 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45083E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4373.40765 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 21.90827 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10901 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03747 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49504E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17244E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.52417 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 248322.89101 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17244E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6548.81069 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.83811 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10372 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.80000E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30575 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67325E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.38601E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.80035 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 158429.74921 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38601E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4178.16162 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01764 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23468 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22490 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62582 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62348E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93683E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01764 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33569.71928 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93683E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 885.11717 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45717 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10562 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.00000E-002 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13115 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60731E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93518E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67058 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22120.30236 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93518E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 583.22778 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26352 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10551 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.00000E-002 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20372 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61100E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.92173E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01240 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33397.21106 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92173E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 880.57163 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53138 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10050 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13017 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79102E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89364E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65617 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21645.49379 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89364E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 570.71504 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50596 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.87260 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49163 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.91766 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.77482 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28591 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.54964 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.95898 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.42225 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.42225 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31404 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 56.28044 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.84929 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 112.56088 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 37.29490 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 87.68469 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 87.68469 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42533 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.70346 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.30815 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.40692 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.81381 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.46867 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.46867 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.71962 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.15516 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.15516 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.15516 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.23281 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.91766 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.91766 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.91766 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.91766 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.91770 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.91770 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50596 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50596 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50596 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50596 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50596 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50596 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.87260 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.87260 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.87260 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.87260 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.87260 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.87260 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49163 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49163 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49163 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49163 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49163 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49163 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.42225 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 87.68469 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.46867 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.15516 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.91770 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50596 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.87260 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49163 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.42225 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.73595 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90823 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.26601E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 164773.70145 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.71251E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.42225 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 125824.03419 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10076E-003 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1803.56480 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.42225 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.71251E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.01048E-004 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.10076E-003 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 87.68469 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.79628 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90828 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.28045E-003 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1543608.24823 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.41470E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 87.68469 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1279281.37093 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11917E-002 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 17883.09134 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 87.68469 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.41470E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.07865E-005 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.11917E-002 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.46867 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.73032 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90822 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.26394E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 165461.90916 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.73219E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.46867 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 126834.49912 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10960E-003 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1816.45282 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.46867 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.73219E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.00628E-004 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.10960E-003 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.15516 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | CAV_BAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.20016 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.75706 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89650 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.40395E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 92503.32698 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.64558E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.15516 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 305534.03812 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.57515 |
354 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.15516 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.64558E-003 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.79995E-004 |
357 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.91770 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.91770 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 508417.12030 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 322256.01332 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.24511E-002 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.91770 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.91770 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.91770 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.91770 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 508417.12030 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 508417.12030 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 33013.32304 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
372 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.91770 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.91770 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 508417.12030 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.24511E-002 |
376 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 33013.32304 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.26373E-004 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50596 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50596 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10038.62812 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6434.55005 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.45845E-004 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50596 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50596 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50596 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50596 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10038.62812 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10038.62812 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1525.07876 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
395 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50596 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50596 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10038.62812 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.45845E-004 |
399 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1525.07876 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.87260 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.87260 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 96683.68992 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 61966.45775 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36778E-003 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.87260 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.87260 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.87260 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.87260 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 96683.68992 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 96683.68992 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 15250.78758 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
414 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.87260 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.87260 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 96683.68992 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36778E-003 |
418 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 15250.78758 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49163 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49163 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9754.96539 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6252.25988 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38898E-004 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49163 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49163 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49163 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49163 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9754.96539 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9754.96539 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1525.07876 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
433 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49163 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49163 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9754.96539 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38898E-004 |
437 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1525.07876 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.62373E-002 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9090.92030 |
440 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.62373E-002 |
441 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.74847 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.62373E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.62373E-002 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 236056.08473 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
446 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.81052E-002 |
447 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.37263 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.81052E-002 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8380.26152 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3212601.60262 |
452 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3212601.60000 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.81052E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.62373E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.74847 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.81186E-002 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3146.97535 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.81186E-002 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3146.97535 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.62373E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.82558E-002 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 987969.41805 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 987970.21500 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.07797E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.62373E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.82558E-002 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 987969.41805 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 987970.21500 |
469 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.07797E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.53036E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.83643 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.53036E-002 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3864.54391 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.53036E-002 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 151953.63065 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 76923.45405 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 75976.81532 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46154.07243 |
480 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 630378.09888 |
481 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 617814.60000 |
482 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.53036E-002 |
483 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
484 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
486 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
487 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
488 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10156 |
489 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.18714 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10156 |
491 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 24894.93419 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 38.72659 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1184074.66100 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.74532 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 148009.33263 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 38.72659 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1184074.66100 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.74532 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 148009.33263 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.12325E-002 |
501 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.12325E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20995.28 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 425298.71 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108263.38 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17745.66 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12162.97 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19380.68 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9570.23 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 236675.66 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 157123.91 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 235274.18 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 150104.87 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 31804.45 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20957.05 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 31641.03 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 20507.25 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 77599.43 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 764311.96 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 78137.42 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.77 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 241434.64 | 168875.86 | 72558.78 | 0.70 | 101689.38 | 1031.39 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2253558.62 | 1574331.27 | 679227.35 | 0.70 | 927295.51 | 9405.15 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 242539.73 | 169673.37 | 72866.36 | 0.70 | 102417.00 | 1038.77 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 133895.76 | 93133.00 | 40762.76 | 0.70 | 52985.37 | 537.41 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 7.2852405304E-004 | 1.4955240909E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.5248171979E-003 | 5.4269400159E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.2821729222E-002 | 7.7903963308E-003 | Pass | Pass | 0.4893665491 | 0.4920069907 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1693797212 | 0.1473544492 | Pass | Pass | 0.8670599957 | 0.9886473633 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.7554952147E-003 | 9.8528116334E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.0932815951E-002 | 1.2605139313E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.2685700725E-002 | 2.2918479963E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.0176368220E-002 | 9.4979178910E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5203560539 | 0.4597458765 | Pass | Pass | 0.7241232645 | 0.6024261472 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6066457744 | 0.5547761702 | Pass | Pass | 0.7315357945 | 0.6641380308 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5733870593 | 0.5188092412 | Pass | Pass | 0.7432750223 | 0.6814921720 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5057853272 | 0.4545981899 | Pass | Pass | 0.7817957147 | 0.6821317527 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7213604338 | 0.5984621867 | Pass | Pass | 0.6213372733 | 0.5698237465 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7432776796 | 0.7283299151 | Pass | Pass | 0.6611676087 | 0.6573970791 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7169575951 | 0.7025194885 | Pass | Pass | 0.6599718290 | 0.6452726436 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7022253154 | 0.6641450182 | Pass | Pass | 0.6949853878 | 0.6527219744 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0208243653E-003 | 3.7749501440E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.5018696011E-002 | 3.4583195519E-002 | Pass | Pass | 0.4940375447 | 0.4811648438 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1756434068 | 0.1068832893 | Pass | Pass | 0.5142711391 | 0.5134227334 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8365701074E-008 | 7.7987890073E-008 | Pass | Pass | 3.8705133309E-003 | 3.7879131637E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.9195726407E-003 | 1.6900921900E-003 | Pass | Pass | 1.4792729671E-003 | 1.3346343509E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7660855134E-003 | 2.4473354953E-003 | Pass | Pass | 2.7562189105E-003 | 1.7222748864E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1579003469E-004 | 7.2057670370E-005 | Pass | Pass | 2.4704113981E-005 | 1.1358396111E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4166.11 | 106.93 | 0.00 | 35444.33 | 5929.82 | 45647.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.262_SHGC_EAST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.262_SHGC_EAST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.262_SHGC_WEST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.262_SHGC_WEST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.262_SHGC_WEST_0.399 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 1390.74 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 1.488 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.57 | 0.0000 | Y | 12.26 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.16 | 0.0000 | Y | 7.80 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.51 | 0.0000 | Y | 11.85 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.02 | 0.0000 | Y | 7.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.52 | 0.0000 | Y | 122.38 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.12 | 0.0000 | Y | 77.87 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.50 | 0.0000 | Y | 118.44 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.98 | 0.0000 | Y | 77.52 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.51 | 0.0000 | Y | 12.24 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.12 | 0.0000 | Y | 7.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.50 | 0.0000 | Y | 11.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.98 | 0.0000 | Y | 7.75 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 789.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 44.84 | 44.84 | 111.72 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.06 | 63.95 | 11.88 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.06 | 52.41 | 261.62 | |
Exterior Lighting Total | 40855.88 | 385.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1960290.66 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3212601.60 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 987970.21 | 5.17 | 984624.61 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 987970.21 | 5.17 | 984624.61 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 633266.76 | |||||
CENTRAL BOILER | Boiler:HotWater | 617814.60 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1184074.66 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1184074.66 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 164773.70 | 241434.64 | 168875.86 | 72558.78 | 0.70 | - | 101689.38 | 1031.39 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1543608.25 | 2253558.62 | 1574331.27 | 679227.35 | 0.70 | - | 927295.51 | 9405.15 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 165461.91 | 242539.73 | 169673.37 | 72866.36 | 0.70 | - | 102417.00 | 1038.77 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 92503.33 | 133895.76 | 93133.00 | 40762.76 | 0.70 | - | 52985.37 | 537.41 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 508417.12 | 322256.01 | 186161.11 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10038.63 | 6434.55 | 3604.08 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 96683.69 | 61966.46 | 34717.23 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9754.97 | 6252.26 | 3502.71 | 0.64 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 22145.97 | 20995.28 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 449013.82 | 425298.71 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 114254.13 | 108263.38 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18728.90 | 17745.66 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12837.05 | 12162.97 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20454.86 | 19380.68 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10100.05 | 9570.23 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 249802.34 | 236675.66 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 165839.20 | 157123.91 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 248322.89 | 235274.18 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 158429.75 | 150104.87 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 33569.72 | 31804.45 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22120.30 | 20957.05 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 33397.21 | 31641.03 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21645.49 | 20507.25 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 125824.03 | 77599.43 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1279281.37 | 764311.96 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 126834.50 | 78137.42 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.77 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 508417.12 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10038.63 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 96683.69 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9754.97 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 33013.32 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1525.08 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 15250.79 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1525.08 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.42 | 21517.86 | 2283.73 | 1.00 | 1.11 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 87.68 | 200247.97 | 2283.73 | 1.00 | 1.07 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.47 | 21623.86 | 2283.73 | 1.00 | 1.11 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.16 | 11848.93 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.92 | 41095.44 | 1649.25 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 566.73 | 1120.11 | 1.00 | 1.60 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.87 | 5457.83 | 1120.11 | 1.00 | 1.16 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 550.68 | 1120.11 | 1.00 | 1.61 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.056237 | 9090.92 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.028105 | 8380.26 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028119 | 3146.98 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.028119 | 3146.98 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015304 | 3864.54 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.101559 | 24894.93 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 70318.36 | 70318.36 | 25.30 | 5.155 | 5.155 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00750 | 19.85 | 0.00700 | 1.200 | 0.00 |
CORE_BOTTOM | 75834.77 | 75834.77 | 30.38 | 5.560 | 5.560 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 19.85 | 0.00700 | 1.078 | 0.00 |
CORE_MID | 713564.71 | 713564.71 | 285.87 | 52.300 | 52.300 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00744 | 19.85 | 0.00700 | 10.778 | 0.00 |
CORE_TOP | 70093.77 | 70093.77 | 28.08 | 5.137 | 5.137 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00744 | 19.85 | 0.00700 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12954.23 | 12954.23 | 41.33 | 0.959 | 0.959 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00729 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 18404.14 | 18404.14 | 91.12 | 1.362 | 1.362 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00713 | 21.79 | 0.00700 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 27998.07 | 27998.07 | 89.33 | 2.072 | 2.072 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00714 | 27.31 | 0.00701 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21582.97 | 21582.97 | 106.86 | 1.597 | 1.597 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00711 | 24.70 | 0.00700 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 120347.53 | 120347.53 | 383.99 | 8.906 | 8.906 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 24.00 | 24.00 | 0.00731 | 21.23 | 0.00700 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 197397.37 | 197397.37 | 977.33 | 14.608 | 14.608 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00712 | 22.37 | 0.00700 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 296040.83 | 296040.83 | 944.55 | 21.908 | 21.908 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00713 | 27.40 | 0.00701 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 200503.77 | 200503.77 | 992.72 | 14.838 | 14.838 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00712 | 24.44 | 0.00700 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12405.83 | 12405.83 | 39.58 | 0.918 | 0.918 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00730 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 19690.42 | 19690.42 | 97.49 | 1.457 | 1.457 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00712 | 22.66 | 0.00700 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 30586.35 | 30586.35 | 97.59 | 2.264 | 2.264 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00712 | 27.40 | 0.00701 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20693.22 | 20693.22 | 102.45 | 1.531 | 1.531 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00712 | 24.44 | 0.00700 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8668.12 | 8668.12 | 239.43 | 0.506 | 0.506 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00708 | 21.84 | 0.00700 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 83476.58 | 83476.58 | 2305.81 | 4.873 | 4.873 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00709 | 21.84 | 0.00700 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8422.55 | 8422.55 | 232.65 | 0.492 | 0.492 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00709 | 21.84 | 0.00700 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371210.95 | 426892.59 | 544.73 | 21.668 | 24.918 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.12 | 0.00699 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.68 | 0.00006 | -41.90 | 0.00006 | 1.200 | 0.00 |
CORE_BOTTOM | 6109.60 | 6109.60 | 2.45 | 0.263 | 1.078 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 1.078 | 0.00 |
CORE_MID | 288825.78 | 288825.78 | 115.71 | 12.376 | 12.376 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 10.778 | 0.00 |
CORE_TOP | 79987.29 | 79987.29 | 32.04 | 3.457 | 3.457 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13107.48 | 13107.48 | 41.82 | 0.567 | 0.567 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8983.45 | 8983.45 | 44.48 | 0.389 | 0.389 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14314.15 | 14314.15 | 45.67 | 0.620 | 0.620 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7070.17 | 7070.17 | 35.01 | 0.306 | 0.306 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 174780.65 | 174780.65 | 557.67 | 7.569 | 7.569 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 116031.00 | 116031.00 | 574.48 | 5.025 | 5.025 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 173746.38 | 173746.38 | 554.36 | 7.524 | 7.524 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 110850.83 | 110850.83 | 548.83 | 4.800 | 4.800 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 23483.30 | 23483.30 | 74.93 | 1.018 | 1.018 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15473.80 | 15473.80 | 76.61 | 0.671 | 0.671 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 23362.70 | 23362.70 | 74.54 | 1.012 | 1.012 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15141.82 | 15141.82 | 74.97 | 0.656 | 0.656 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.49 | 0.00054 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.56 | 0.00061 | -41.90 | 0.00006 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.73 | 0.00054 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | 18.00 | 27.00 | 0.00700 | -41.90 | 0.00006 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.42 | 9.42 | 2.96 | 2.96 | 9.4223 | 2.9590 | 9.4223 | 0.3140 | 0.3000 |
VAV_MID WITH REHEAT | 87.68 | 87.68 | 37.29 | 37.29 | 87.6847 | 37.2949 | 87.6847 | 0.4253 | 0.3000 |
VAV_TOP WITH REHEAT | 9.47 | 9.47 | 6.81 | 6.81 | 9.4687 | 6.8138 | 9.4687 | 0.7196 | 0.3000 |
CAV_BAS | 5.16 | 5.16 | 1.20 | 1.20 | 5.1552 | 1.2002 | 5.1552 | 0.2328 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.92 | 24.92 | 0.34 | 0.34 | 24.9177 | 24.9177 | 24.9177 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5060 | 0.5060 | 0.5060 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.87 | 4.87 | 0.16 | 0.16 | 4.8726 | 4.8726 | 4.8726 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4916 | 0.4916 | 0.4916 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22145.970 | 22145.970 | 1.617894 | 0.00019374 | 463.864 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22145.97 | 22145.97 | 1.617894 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798207 | 50.8004 | 6109.60 | 0.00 | 22226.13 | 22226.13 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 449013.820 | 449013.820 | 16.160677 | 0.00392817 | 11050.601 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 449013.82 | 449013.82 | 16.160677 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 288825.78 | 0.00 | 450426.32 | 450426.32 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 114254.126 | 114254.126 | 3.457033 | 0.00099954 | 3015.067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114254.13 | 114254.13 | 3.457033 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 79987.29 | 0.00 | 114642.54 | 114642.54 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18728.904 | 18728.904 | 0.567145 | 0.00016385 | 494.057 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18728.90 | 18728.90 | 0.567145 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798247 | 50.8031 | 13107.48 | 0.00 | 18791.26 | 18791.26 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12837.053 | 12837.053 | 0.388788 | 0.00011230 | 338.610 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12837.05 | 12837.05 | 0.388788 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798401 | 50.8128 | 8983.45 | 0.00 | 12879.63 | 12879.63 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20454.861 | 20454.861 | 0.619531 | 0.00017895 | 539.539 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20454.86 | 20454.86 | 0.619531 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798540 | 50.8215 | 14314.15 | 0.00 | 20522.62 | 20522.62 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10100.054 | 10100.054 | 0.305693 | 0.00008836 | 266.495 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10100.05 | 10100.05 | 0.305693 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797031 | 50.7268 | 7070.17 | 0.00 | 10134.13 | 10134.13 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 249802.343 | 249802.343 | 7.569087 | 0.00218538 | 6587.793 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 249802.34 | 249802.34 | 7.569087 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797398 | 50.7499 | 174780.65 | 0.00 | 250620.80 | 250620.80 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 165839.201 | 165839.201 | 5.025249 | 0.00145083 | 4373.408 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 165839.20 | 165839.20 | 5.025249 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797400 | 50.7501 | 116031.00 | 0.00 | 166381.79 | 166381.79 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 248322.891 | 248322.891 | 7.524175 | 0.00217244 | 6548.811 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 248322.89 | 248322.89 | 7.524175 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797379 | 50.7488 | 173746.38 | 0.00 | 249136.75 | 249136.75 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 158429.749 | 158429.749 | 4.800348 | 0.00138601 | 4178.162 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 158429.75 | 158429.75 | 4.800348 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797253 | 50.7408 | 110850.83 | 0.00 | 158949.18 | 158949.18 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 33569.719 | 33569.719 | 1.017636 | 0.00029368 | 885.117 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33569.72 | 33459.39 | 1.017636 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797655 | 50.7661 | 23483.30 | 0.00 | 33678.38 | 33678.38 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22120.302 | 22120.302 | 0.670577 | 0.00019352 | 583.228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22120.30 | 22120.30 | 0.670577 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797628 | 50.7645 | 15473.80 | 0.00 | 22191.85 | 22191.85 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 33397.211 | 33397.211 | 1.012399 | 0.00029217 | 880.572 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33397.21 | 33397.21 | 1.012399 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797643 | 50.7654 | 23362.70 | 0.00 | 33505.33 | 33505.33 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 21645.494 | 21645.494 | 0.656168 | 0.00018936 | 570.715 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21645.49 | 21645.49 | 0.656168 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797576 | 50.7612 | 15141.82 | 0.00 | 21715.55 | 21715.55 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 164773.701 | -999.000 | 9.422253 | 0.00471251 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 164773.70 | 158284.08 | 9.422253 | 24.74 | 15.42 | 0.00726601 | 10.91 | 9.59 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 21.5500 | 24.00 | 0.00733764 | 38.9594 | 126596.72 | 0.00 | 167349.85 | 167349.85 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 125824.034 | 125824.034 | 2.826676 | 0.00110076 | 1803.565 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 125824.03 | 125824.03 | 2.826676 | -24.57 | -24.57 | 0.00228934 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 71.8335 | 19.90 | 0.00795855 | 54.2118 | 26259.59 | 0.00 | 93844.97 | 93844.97 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1543608.248 | -999.000 | 87.684694 | 0.04414700 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1543608.25 | 1479874.69 | 87.684694 | 24.80 | 15.45 | 0.00728045 | 10.91 | 9.59 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 23.1580 | 24.00 | 0.00736416 | 39.0986 | 1170247.20 | 0.00 | 1567597.53 | 1567597.53 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1279281.371 | 1279281.371 | 26.305408 | 0.01119171 | 17883.091 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1279281.37 | 1279281.37 | 26.305408 | -28.03 | -28.03 | 0.00186561 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 77.1933 | 18.02 | 0.00795464 | 60.9195 | 290342.62 | 0.00 | 924097.14 | 924097.14 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 165461.909 | -999.000 | 9.468667 | 0.00473219 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 165461.91 | 158991.78 | 9.468667 | 24.73 | 15.41 | 0.00726394 | 10.91 | 9.59 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 21.4444 | 24.00 | 0.00733431 | 38.9419 | 127571.83 | 0.00 | 168050.49 | 168050.49 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 126834.499 | 126834.499 | 2.840600 | 0.00110960 | 1816.453 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 126834.50 | 126834.50 | 2.840600 | -24.68 | -24.68 | 0.00231586 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 71.4814 | 15.94 | 0.00796390 | 69.6038 | 28054.52 | 0.00 | 94496.01 | 94496.01 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 92503.327 | -999.000 | 5.155158 | 0.00264558 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 92503.33 | 87088.12 | 5.155158 | 24.76 | 15.55 | 0.00740395 | 10.90 | 9.59 | 0.00700000 | 26.89 | 0.00700637 | 15.97 | 23.2807 | 24.00 | 0.00754532 | 40.0493 | 61825.17 | 0.00 | 93920.21 | 93920.21 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.086362 | -9.75 | -13.05 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 38.8858 | 22.78 | 0.00006450 | 0.3729 | 0.00 | 0.00 | 100078.50 | 100078.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 508417.120 | 322256.013 | 24.917702 | 0.01245110 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 456527.92 | 454139.93 | -999.0 | 28.42 | 16.54 | 0.00704174 | 12.80 | 10.42 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | -999.0000 | 27.00 | 0.00704222 | 31.3060 | 370732.16 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10038.628 | 6434.550 | 0.505963 | 0.00024585 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 8967.37 | 8874.27 | -999.0 | 27.80 | 16.35 | 0.00708072 | 12.80 | 10.42 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | -999.0000 | 27.00 | 0.00708334 | 31.4847 | 8668.12 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 96683.690 | 61966.458 | 4.872595 | 0.00236778 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 86367.05 | 85437.71 | -999.0 | 27.79 | 16.35 | 0.00708368 | 12.80 | 10.42 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | -999.0000 | 27.00 | 0.00708649 | 31.4986 | 83476.58 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9754.965 | 6252.260 | 0.491630 | 0.00023890 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 8714.05 | 8621.02 | -999.0 | 27.80 | 16.35 | 0.00708302 | 12.80 | 10.42 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | -999.0000 | 27.00 | 0.00708579 | 31.4955 | 8422.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 508417.120 | 508417.120 | 24.917702 | 0.01245110 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 508417.12 | 508417.12 | 24.917702 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 1.3580 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10038.628 | 10038.628 | 0.505963 | 0.00024585 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10038.63 | 10038.63 | 0.505963 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0896 | 25.28 | 0.00053862 | 2.6784 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 96683.690 | 96683.690 | 4.872595 | 0.00236778 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 96683.69 | 96683.69 | 4.872595 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.2082 | 23.77 | 0.00060821 | 3.3101 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9754.965 | 9754.965 | 0.491630 | 0.00023890 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9754.97 | 9754.97 | 0.491630 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.1797 | 22.01 | 0.00053816 | 3.2586 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 33013.323 | 33013.323 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 33013.32 | 33013.32 | 24.917702 | -0.57 | -0.57 | 0.00690581 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 1.3580 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1525.08 | 1525.08 | 0.505963 | -1.29 | -6.20 | 0.00052397 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0896 | 25.28 | 0.00053862 | 2.6784 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 15250.788 | 15250.788 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15250.79 | 15250.79 | 4.872595 | -1.34 | -6.11 | 0.00059076 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.2082 | 23.77 | 0.00060821 | 3.3101 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1525.08 | 1525.08 | 0.491630 | -1.33 | -6.23 | 0.00052310 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.1797 | 22.01 | 0.00053816 | 3.2586 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 22145.970 | 22145.970 | 1.617894 | 0.00019374 | 463.864 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.6757 | 0.689347 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22145.97 | 22145.97 | 1.0000 | 1.91791456 | 1.617894 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19372284 | 60.00 | 32.22 | 27.78 | 0.000 | 22145.97 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.85 | 0.00798207 | 21.00 | 0.00798207 | 50.8004 | 6109.60 | 0.00 | 22226.13 | 22226.13 | 1.91791456 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.16 | 16.01 | 0.00800000 | 44648.5 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 449013.820 | 449013.820 | 16.160677 | 0.00392817 | 11050.601 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 13.7009 | 13.976642 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 449013.82 | 449013.82 | 1.0000 | 19.15750204 | 16.160677 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 3.92776806 | 60.00 | 32.22 | 27.78 | 0.000 | 449013.82 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 288825.78 | 0.00 | 450426.32 | 450426.32 | 19.15750204 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.86 | 19.93 | 0.00800000 | 56571.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 114254.126 | 114254.126 | 3.457033 | 0.00099954 | 3015.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 3.4863 | 3.556436 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 114254.13 | 114254.13 | 1.0000 | 4.09810224 | 3.457033 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.99944297 | 60.00 | 32.22 | 27.78 | 0.000 | 114254.13 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 79987.29 | 0.00 | 114642.54 | 114642.54 | 4.09810224 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18728.904 | 18728.904 | 0.567145 | 0.00016385 | 494.057 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.5715 | 0.582982 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18728.90 | 18728.90 | 1.0000 | 0.67231554 | 0.567145 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.16383191 | 60.00 | 32.22 | 27.78 | 0.000 | 18728.90 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798247 | 21.00 | 0.00798247 | 50.8031 | 13107.48 | 0.00 | 18791.26 | 18791.26 | 0.67231554 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61009.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12837.053 | 12837.053 | 0.388788 | 0.00011230 | 338.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.3917 | 0.399584 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12837.05 | 12837.05 | 1.0000 | 0.46088452 | 0.388788 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.11229269 | 60.00 | 32.22 | 27.78 | 0.000 | 12837.05 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798401 | 21.00 | 0.00798401 | 50.8128 | 8983.45 | 0.00 | 12879.63 | 12879.63 | 0.46088452 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20454.861 | 20454.861 | 0.619531 | 0.00017895 | 539.539 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.6241 | 0.636707 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20454.86 | 20454.86 | 1.0000 | 0.73441642 | 0.619531 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.17892979 | 60.00 | 32.22 | 27.78 | 0.000 | 20454.86 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798540 | 21.00 | 0.00798540 | 50.8215 | 14314.15 | 0.00 | 20522.62 | 20522.62 | 0.73441642 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10100.054 | 10100.054 | 0.305693 | 0.00008836 | 266.495 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.3082 | 0.314389 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10100.05 | 10100.05 | 1.0000 | 0.36238029 | 0.305693 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.08835067 | 60.00 | 32.22 | 27.78 | 0.000 | 10100.05 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797031 | 21.00 | 0.00797031 | 50.7268 | 7070.17 | 0.00 | 10134.13 | 10134.13 | 0.36238029 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61025.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 249802.343 | 249802.343 | 7.569087 | 0.00218538 | 6587.793 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 7.6223 | 7.775702 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 249802.34 | 249802.34 | 1.0000 | 8.97269330 | 7.569087 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.18515693 | 60.00 | 32.22 | 27.78 | 0.000 | 249802.34 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797398 | 21.00 | 0.00797398 | 50.7499 | 174780.65 | 0.00 | 250620.80 | 250620.80 | 8.97269330 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 165839.201 | 165839.201 | 5.025249 | 0.00145083 | 4373.408 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 5.0603 | 5.162146 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 165839.20 | 165839.20 | 1.0000 | 5.95712725 | 5.025249 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.45068567 | 60.00 | 32.22 | 27.78 | 0.000 | 165839.20 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797400 | 21.00 | 0.00797400 | 50.7501 | 116031.00 | 0.00 | 166381.79 | 166381.79 | 5.95712725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 248322.891 | 248322.891 | 7.524175 | 0.00217244 | 6548.811 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 7.5772 | 7.729651 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 248322.89 | 248322.89 | 1.0000 | 8.91945228 | 7.524175 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.17221537 | 60.00 | 32.22 | 27.78 | 0.000 | 248322.89 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797379 | 21.00 | 0.00797379 | 50.7488 | 173746.38 | 0.00 | 249136.75 | 249136.75 | 8.91945228 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 158429.749 | 158429.749 | 4.800348 | 0.00138601 | 4178.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 4.8342 | 4.931509 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 158429.75 | 158429.75 | 1.0000 | 5.69052056 | 4.800348 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.38587117 | 60.00 | 32.22 | 27.78 | 0.000 | 158429.75 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797253 | 21.00 | 0.00797253 | 50.7408 | 110850.83 | 0.00 | 158949.18 | 158949.18 | 5.69052056 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33569.719 | 33569.719 | 1.017636 | 0.00029368 | 885.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 1.0243 | 1.044939 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33569.72 | 33459.39 | 1.0000 | 1.20634576 | 1.017636 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.29365259 | 60.00 | 32.22 | 27.78 | 0.000 | 33569.72 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797655 | 21.00 | 0.00797655 | 50.7661 | 23483.30 | 0.00 | 33678.38 | 33678.38 | 1.20634576 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22120.302 | 22120.302 | 0.670577 | 0.00019352 | 583.228 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.6750 | 0.688548 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22120.30 | 22120.30 | 1.0000 | 0.79492854 | 0.670577 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19349831 | 60.00 | 32.22 | 27.78 | 0.000 | 22120.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797628 | 21.00 | 0.00797628 | 50.7645 | 15473.80 | 0.00 | 22191.85 | 22191.85 | 0.79492854 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33397.211 | 33397.211 | 1.012399 | 0.00029217 | 880.572 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 1.0191 | 1.039569 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33397.21 | 33397.21 | 1.0000 | 1.20013792 | 1.012399 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.29214357 | 60.00 | 32.22 | 27.78 | 0.000 | 33397.21 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797643 | 21.00 | 0.00797643 | 50.7654 | 23362.70 | 0.00 | 33505.33 | 33505.33 | 1.20013792 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21645.494 | 21645.494 | 0.656168 | 0.00018936 | 570.715 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 0.6605 | 0.673768 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21645.49 | 21645.49 | 1.0000 | 0.77784720 | 0.656168 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.18934491 | 60.00 | 32.22 | 27.78 | 0.000 | 21645.49 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797576 | 21.00 | 0.00797576 | 50.7612 | 15141.82 | 0.00 | 21715.55 | 21715.55 | 0.77784720 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 164773.701 | -999.000 | 9.422253 | 0.00471251 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3472 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.422253 | 11.16950931 | 4197.9300 | 999.8980 | 56.23154382 | 15.00 | 6.67 | 8.33 | 1966347.19 | 8.3797 | 8.379685 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | Sensible | 164773.70 | 158284.08 | 1.0000 | 11.16950931 | 9.422253 | 24.74 | 15.42 | 0.00726601 | 43361.6 | 10.91 | 9.59 | 0.00700000 | 28609.5 | 4.71202628 | 6.67 | 15.00 | 8.33 | 21517.862 | 143255.84 | 27.40 | 0.00700714 | 16.15 | 2.03050000 | 21.5500 | 24.00 | 0.00733764 | 24.00 | 0.00733764 | 38.9594 | 126596.72 | 0.00 | 167349.85 | 167349.85 | 11.16950931 | 24.74 | 15.57 | 0.00726601 | 43361.6 | 10.02 | 9.62 | 0.00726601 | 28378.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 125824.034 | 125824.034 | 2.826676 | 0.00110076 | 1803.565 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.422253 | 11.16950931 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 3.8393 | 3.916578 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 125824.03 | 125824.03 | 1.0000 | 3.35085279 | 2.826676 | -24.57 | -24.57 | 0.00228934 | -19066.3 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.10065125 | 60.00 | 32.22 | 27.78 | 0.000 | 125824.03 | -41.90 | 0.00006450 | -41.90 | 2.03050000 | 71.8335 | 19.63 | 0.00796338 | 19.90 | 0.00795855 | 54.2118 | 26259.59 | 0.00 | 93844.97 | 93844.97 | 3.35085279 | 2.80 | -0.73 | 0.00228934 | 8551.0 | 30.55 | 13.13 | 0.00228934 | 36557.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1543608.248 | -999.000 | 87.684694 | 0.04414700 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3740 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 87.684694 | 103.94488148 | 4197.9300 | 999.8980 | 56.23154382 | 15.00 | 6.67 | 8.33 | 1966347.19 | 78.5013 | 78.501307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1543608.25 | 1479874.69 | 1.0000 | 103.94488148 | 87.684694 | 24.80 | 15.45 | 0.00728045 | 43459.9 | 10.91 | 9.59 | 0.00700000 | 28609.6 | 44.14249705 | 6.67 | 15.00 | 8.33 | 200247.974 | 1343360.27 | 27.40 | 0.00700714 | 16.15 | 20.30600000 | 23.1580 | 24.00 | 0.00736416 | 24.00 | 0.00736416 | 39.0986 | 1170247.20 | 0.00 | 1567597.53 | 1567597.53 | 103.94488148 | 24.80 | 15.61 | 0.00728045 | 43459.9 | 9.99 | 9.62 | 0.00728045 | 28378.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1279281.371 | 1279281.371 | 26.305408 | 0.01119171 | 17883.091 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 87.684694 | 103.94488148 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 39.0351 | 39.820729 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1279281.37 | 1279281.37 | 1.0000 | 31.18346444 | 26.305408 | -28.03 | -28.03 | 0.00186561 | -23593.1 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 11.19056983 | 60.00 | 32.22 | 27.78 | 0.000 | 1279281.37 | -41.90 | 0.00006450 | -41.90 | 20.30600000 | 77.1933 | 18.93 | 0.00796174 | 18.02 | 0.00795464 | 60.9195 | 290342.62 | 0.00 | 924097.14 | 924097.14 | 31.18346444 | 2.80 | -1.39 | 0.00186561 | 7489.0 | 32.19 | 13.36 | 0.00186561 | 37123.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 165461.909 | -999.000 | 9.468667 | 0.00473219 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3433 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.468667 | 11.22452986 | 4197.9300 | 999.8980 | 56.23154382 | 15.00 | 6.67 | 8.33 | 1966347.19 | 8.4147 | 8.414684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 165461.91 | 158991.78 | 1.0000 | 11.22452986 | 9.468667 | 24.73 | 15.41 | 0.00726394 | 43350.6 | 10.91 | 9.59 | 0.00700000 | 28609.5 | 4.73170692 | 6.67 | 15.00 | 8.33 | 21623.858 | 143838.05 | 27.40 | 0.00700714 | 16.15 | 2.03050000 | 21.4444 | 24.00 | 0.00733431 | 24.00 | 0.00733431 | 38.9419 | 127571.83 | 0.00 | 168050.49 | 168050.49 | 11.22452986 | 24.73 | 15.57 | 0.00726394 | 43350.6 | 10.03 | 9.62 | 0.00726394 | 28378.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 126834.499 | 126834.499 | 2.840600 | 0.00110960 | 1816.453 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.468667 | 11.22452986 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 3.8701 | 3.948031 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 126834.50 | 126834.50 | 1.0000 | 3.36735896 | 2.840600 | -24.68 | -24.68 | 0.00231586 | -19117.7 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.10949034 | 60.00 | 32.22 | 27.78 | 0.000 | 126834.50 | -41.90 | 0.00006450 | -41.90 | 2.03050000 | 71.4814 | 18.47 | 0.00795884 | 15.94 | 0.00796390 | 69.6038 | 28054.52 | 0.00 | 94496.01 | 94496.01 | 3.36735896 | 2.80 | -0.69 | 0.00231586 | 8617.4 | 30.61 | 13.18 | 0.00231586 | 36679.8 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 92503.327 | -999.000 | 5.155158 | 0.00264558 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6036 | 1004.8586 | 1.1854 | CAV_BAS FAN | Fan:VariableVolume | 5.155158 | 6.11112736 | 4197.9300 | 999.8980 | 56.23154382 | 15.00 | 6.67 | 8.33 | 1966347.19 | 4.7043 | 4.704323 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 92503.33 | 87088.12 | 1.0000 | 6.11112736 | 5.155158 | 24.76 | 15.55 | 0.00740395 | 43734.5 | 10.90 | 9.59 | 0.00700000 | 28597.6 | 2.64531357 | 6.67 | 15.00 | 8.33 | 11848.933 | 80654.39 | 26.89 | 0.00700637 | 15.97 | 1.20015641 | 23.2807 | 24.00 | 0.00754532 | 24.00 | 0.00754532 | 40.0493 | 61825.17 | 0.00 | 93920.21 | 93920.21 | 6.11112736 | 24.76 | 15.70 | 0.00740395 | 43734.5 | 9.67 | 9.61 | 0.00740395 | 28365.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | CAV_BAS FAN | Fan:VariableVolume | 5.155158 | 6.11112736 | 4197.9300 | 999.8980 | 28.10237325 | 54.44 | 82.22 | 27.78 | 3277256.49 | 3.0513 | 3.112742 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.086362 | -9.75 | -13.05 | 0.00006450 | -9641.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -41.90 | 0.00006450 | -41.90 | 1.20015641 | 38.8858 | 0.00 | 0.00006450 | 22.78 | 0.00006450 | 0.3729 | 0.00 | 0.00 | 100078.50 | 100078.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 508417.120 | 322256.013 | 24.917702 | 0.01245110 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9302 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 456527.92 | 454139.93 | 0.8979 | -999.0 | -999.0 | 28.42 | 16.54 | 0.00704174 | 46538.6 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456527.92 | 27.40 | 0.00700714 | 16.15 | 0.33839277 | -999.0000 | 27.00 | 0.00704222 | 27.00 | 0.00704222 | 31.3060 | 370732.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10038.628 | 6434.550 | 0.505963 | 0.00024585 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0027 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 8967.37 | 8874.27 | 0.8933 | -999.0 | -999.0 | 27.80 | 16.35 | 0.00708072 | 46008.7 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8967.37 | 21.84 | 0.00699878 | 14.10 | 0.01563234 | -999.0000 | 27.00 | 0.00708334 | 27.00 | 0.00708334 | 31.4847 | 8668.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 96683.690 | 61966.458 | 4.872595 | 0.00236778 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0082 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 86367.05 | 85437.71 | 0.8933 | -999.0 | -999.0 | 27.79 | 16.35 | 0.00708368 | 46009.9 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86367.05 | 21.84 | 0.00699878 | 14.10 | 0.15632344 | -999.0000 | 27.00 | 0.00708649 | 27.00 | 0.00708649 | 31.4986 | 83476.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9754.965 | 6252.260 | 0.491630 | 0.00023890 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0070 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 8714.05 | 8621.02 | 0.8933 | -999.0 | -999.0 | 27.80 | 16.35 | 0.00708302 | 46009.8 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8714.05 | 21.84 | 0.00699878 | 14.10 | 0.01563234 | -999.0000 | 27.00 | 0.00708579 | 27.00 | 0.00708579 | 31.4955 | 8422.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 508417.120 | 508417.120 | 24.917702 | 0.01245110 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 508417.12 | 508417.12 | 1.0000 | 29.53842254 | 24.917702 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 508417.12 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 1.3580 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10038.628 | 10038.628 | 0.505963 | 0.00024585 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10038.63 | 10038.63 | 1.0000 | 0.59978828 | 0.505963 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10038.63 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.0896 | 0.00 | 0.00053862 | 25.28 | 0.00053862 | 2.6784 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 96683.690 | 96683.690 | 4.872595 | 0.00236778 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 96683.69 | 96683.69 | 1.0000 | 5.77616614 | 4.872595 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 96683.69 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 3.2082 | 0.00 | 0.00060821 | 23.77 | 0.00060821 | 3.3101 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9754.965 | 9754.965 | 0.491630 | 0.00023890 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9754.97 | 9754.97 | 1.0000 | 0.58279776 | 0.491630 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9754.97 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.1797 | 0.00 | 0.00053816 | 22.01 | 0.00053816 | 3.2586 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33013.323 | 33013.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.917702 | 29.53842254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 33013.32 | 33013.32 | 1.0000 | 29.53842254 | 24.917702 | -0.57 | -0.57 | 0.00690581 | 16691.9 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33013.32 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 1.3580 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.505963 | 0.59978828 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1525.08 | 1525.08 | 1.0000 | 0.59978828 | 0.505963 | -1.29 | -6.20 | 0.00052397 | 8.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1525.08 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.0896 | 0.00 | 0.00053862 | 25.28 | 0.00053862 | 2.6784 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15250.788 | 15250.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.872595 | 5.77616614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 15250.79 | 15250.79 | 1.0000 | 5.77616614 | 4.872595 | -1.34 | -6.11 | 0.00059076 | 125.2 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15250.79 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 3.2082 | 0.00 | 0.00060821 | 23.77 | 0.00060821 | 3.3101 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.491630 | 0.58279776 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1525.08 | 1525.08 | 1.0000 | 0.58279776 | 0.491630 | -1.33 | -6.23 | 0.00052310 | -31.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1525.08 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.1797 | 0.00 | 0.00053816 | 22.01 | 0.00053816 | 3.2586 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.42 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 87.68 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.47 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.16 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2846.33 | 4723.67 | 2592.33 |
CORE_BOTTOM | 1694.33 | 2574.50 | 12.50 |
CORE_MID | 1175.00 | 3839.17 | 545.50 |
CORE_TOP | 2701.83 | 4316.50 | 2186.67 |
PERIMETER_BOT_ZN_3 | 3056.00 | 3622.17 | 1684.17 |
PERIMETER_BOT_ZN_2 | 3543.50 | 3379.17 | 1851.33 |
PERIMETER_BOT_ZN_1 | 3543.33 | 3296.33 | 1772.17 |
PERIMETER_BOT_ZN_4 | 2357.83 | 3159.50 | 628.17 |
PERIMETER_MID_ZN_3 | 3443.83 | 4333.67 | 2746.00 |
PERIMETER_MID_ZN_2 | 3165.67 | 3295.33 | 2134.17 |
PERIMETER_MID_ZN_1 | 3604.33 | 3643.50 | 2175.17 |
PERIMETER_MID_ZN_4 | 3640.33 | 3909.17 | 2500.17 |
PERIMETER_TOP_ZN_3 | 3849.00 | 4558.00 | 3220.00 |
PERIMETER_TOP_ZN_2 | 4061.83 | 4037.00 | 2896.50 |
PERIMETER_TOP_ZN_1 | 3915.67 | 3941.67 | 2657.83 |
PERIMETER_TOP_ZN_4 | 3966.17 | 4152.83 | 2942.17 |
DATACENTER_BOT_ZN_6 | 5673.83 | 363.33 | 363.33 |
DATACENTER_MID_ZN_6 | 3858.50 | 433.33 | 35.00 |
DATACENTER_TOP_ZN_6 | 3255.00 | 999.67 | 99.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5441.00 | 5441.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 4224.67 | 0.00 | 2829.83 |
CORE_BOTTOM | 0.00 | 48.50 | 0.00 | 4.67 |
CORE_MID | 3.50 | 0.00 | 1.67 | 0.00 |
CORE_TOP | 52.17 | 0.00 | 11.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 2.50 | 35.00 | 0.17 | 14.50 |
PERIMETER_BOT_ZN_2 | 5.33 | 62.00 | 0.00 | 43.67 |
PERIMETER_BOT_ZN_1 | 9.50 | 54.00 | 0.00 | 42.33 |
PERIMETER_BOT_ZN_4 | 0.83 | 110.00 | 0.00 | 46.50 |
PERIMETER_MID_ZN_3 | 146.00 | 6.50 | 49.67 | 0.33 |
PERIMETER_MID_ZN_2 | 297.00 | 31.33 | 12.83 | 25.00 |
PERIMETER_MID_ZN_1 | 65.00 | 38.17 | 7.83 | 34.50 |
PERIMETER_MID_ZN_4 | 59.00 | 32.00 | 7.33 | 11.50 |
PERIMETER_TOP_ZN_3 | 513.67 | 3.17 | 223.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 271.50 | 25.00 | 64.00 | 20.00 |
PERIMETER_TOP_ZN_1 | 226.00 | 30.50 | 49.83 | 27.17 |
PERIMETER_TOP_ZN_4 | 191.33 | 29.50 | 43.67 | 10.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 763.33 | 4243.67 | 230.17 | 2845.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.307 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.083 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.679 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.631 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 1.076 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.558 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.630 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.599 | 0.013 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.781 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.203 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.437 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.112 | 0.030 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.829 | 0.036 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.325 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.414 | 0.036 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.111 | 0.038 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 21.084 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 12052281.93 | 0.00 | 12052281.93 | 0.00 | 12052281.93 | 37848132.68 | 6641.70 | 1300.38 | 817.92 | 0.00 |
CORE_BOTTOM | 46133662.78 | 0.00 | 46133662.78 | 0.00 | 46133662.78 | 33990283.35 | 3760.99 | 521.77 | 4477.24 | 689.18 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 4975.25 | 1031.13 | 2753.62 | 470.31 |
CORE_TOP | 25760580.53 | 0.00 | 25760580.53 | 0.00 | 25760580.53 | 33990283.35 | 5995.05 | 945.02 | 1819.93 | 372.20 |
PERIMETER_BOT_ZN_3 | 5776545.08 | 0.00 | 5776545.08 | 129862.25 | 5906407.33 | 4267819.30 | 5275.33 | 562.71 | 2921.96 | 689.18 |
PERIMETER_BOT_ZN_2 | 5273017.61 | 0.00 | 5273017.61 | 86574.77 | 5359592.39 | 2750345.05 | 5067.13 | 563.02 | 3129.84 | 689.18 |
PERIMETER_BOT_ZN_1 | 8508980.57 | 0.00 | 8508980.57 | 129862.25 | 8638842.82 | 4267912.63 | 4956.49 | 555.27 | 3248.24 | 689.18 |
PERIMETER_BOT_ZN_4 | 5497127.30 | 0.00 | 5497127.30 | 86574.77 | 5583702.07 | 2750345.05 | 4715.00 | 562.38 | 3482.62 | 689.18 |
PERIMETER_MID_ZN_3 | 40407487.59 | 0.00 | 40407487.59 | 304566.00 | 40712053.59 | 42678193.03 | 4977.88 | 866.43 | 2915.69 | 470.31 |
PERIMETER_MID_ZN_2 | 41057085.40 | 0.00 | 41057085.40 | 203043.86 | 41260129.26 | 27503450.52 | 4897.34 | 661.18 | 3201.48 | 937.79 |
PERIMETER_MID_ZN_1 | 73079660.67 | 0.00 | 73079660.67 | 304566.00 | 73384226.67 | 42679126.28 | 4447.79 | 844.20 | 3468.01 | 470.31 |
PERIMETER_MID_ZN_4 | 37160734.69 | 0.00 | 37160734.69 | 203043.86 | 37363778.55 | 27503450.52 | 4903.94 | 1011.04 | 2845.02 | 470.31 |
PERIMETER_TOP_ZN_3 | 4250511.11 | 0.00 | 4250511.11 | 378154.45 | 4628665.56 | 4267819.30 | 4355.02 | 44.67 | 4360.30 | 372.20 |
PERIMETER_TOP_ZN_2 | 4329029.26 | 0.00 | 4329029.26 | 252102.79 | 4581132.05 | 2750345.05 | 4548.64 | 847.72 | 3363.65 | 372.20 |
PERIMETER_TOP_ZN_1 | 7155620.58 | 0.00 | 7155620.58 | 378154.45 | 7533775.02 | 4267912.63 | 4594.63 | 942.62 | 3222.75 | 372.20 |
PERIMETER_TOP_ZN_4 | 3685885.17 | 0.00 | 3685885.17 | 252102.79 | 3937987.96 | 2750345.05 | 5099.28 | 728.38 | 2932.34 | 372.20 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 10671554.30 | 1.33 | 8.83 | 8749.83 | 2816.67 |
Total Facility | 0.52E+10 | 0.00 | 0.52E+10 | 11845585.74 | 0.52E+10 | 0.50E+10 | 8682.56 | 4393.31 | 8758.65 | 3284.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.5633 | 0.0000 | 0.5633 | 0.0000 | 0.5633 | 1.2002 | 3824.70 | 1300.38 | 817.92 |
CORE_BOTTOM | 2.0092 | 0.0000 | 2.0092 | 0.0000 | 2.0092 | 1.0778 | 1392.50 | 509.45 | 4041.05 |
CORE_MID | 12.6176 | 0.0000 | 12.6176 | 0.0000 | 12.6176 | 10.7782 | 2266.86 | 1027.18 | 2648.97 |
CORE_TOP | 1.1747 | 0.0000 | 1.1747 | 0.0000 | 1.1747 | 1.0778 | 3267.62 | 944.20 | 1731.18 |
PERIMETER_BOT_ZN_3 | 0.2512 | 0.0000 | 0.2512 | 0.0029 | 0.2541 | 0.1353 | 2884.50 | 549.61 | 2508.89 |
PERIMETER_BOT_ZN_2 | 0.2342 | 0.0000 | 0.2342 | 0.0019 | 0.2362 | 0.0872 | 2675.29 | 550.18 | 2717.53 |
PERIMETER_BOT_ZN_1 | 0.3804 | 0.0000 | 0.3804 | 0.0029 | 0.3833 | 0.1353 | 2556.03 | 540.92 | 2846.05 |
PERIMETER_BOT_ZN_4 | 0.2403 | 0.0000 | 0.2403 | 0.0019 | 0.2422 | 0.0872 | 2338.48 | 550.48 | 3054.05 |
PERIMETER_MID_ZN_3 | 1.8251 | 0.0000 | 1.8251 | 0.0068 | 1.8319 | 1.3533 | 2273.08 | 863.45 | 2806.47 |
PERIMETER_MID_ZN_2 | 1.8102 | 0.0000 | 1.8102 | 0.0049 | 1.8151 | 0.8721 | 1696.83 | 656.99 | 2680.18 |
PERIMETER_MID_ZN_1 | 3.3557 | 0.0000 | 3.3557 | 0.0068 | 3.3625 | 1.3533 | 1742.72 | 840.14 | 3360.14 |
PERIMETER_MID_ZN_4 | 1.6726 | 0.0000 | 1.6726 | 0.0046 | 1.6772 | 0.8721 | 2202.29 | 1006.91 | 2733.80 |
PERIMETER_TOP_ZN_3 | 0.1941 | 0.0000 | 0.1941 | 0.0085 | 0.2026 | 0.1353 | 1636.10 | 44.34 | 4262.56 |
PERIMETER_TOP_ZN_2 | 0.1994 | 0.0000 | 0.1994 | 0.0057 | 0.2051 | 0.0872 | 1826.85 | 847.20 | 3268.95 |
PERIMETER_TOP_ZN_1 | 0.3303 | 0.0000 | 0.3303 | 0.0085 | 0.3388 | 0.1353 | 1867.66 | 941.80 | 3133.54 |
PERIMETER_TOP_ZN_4 | 0.1672 | 0.0000 | 0.1672 | 0.0057 | 0.1729 | 0.0872 | 2373.54 | 727.56 | 2841.89 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.7941 | 0.0000 | 10.7941 | 0.0000 | 10.7941 | 0.3384 | 1.00 | 8.83 | 5933.17 |
Total Facility | 230.5149 | 0.0000 | 230.5149 | 0.2696 | 230.7845 | 158.4706 | 5865.56 | 4369.93 | 5941.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.10E+09 | 0.00 | 0.10E+09 | 48026705.38 | 3430.31 | 4.37 | 5325.32 | 689.18 |
VAV_MID WITH REHEAT | 0.66E+09 | 0.00 | 0.66E+09 | 0.48E+09 | 4010.18 | 3.19 | 4746.63 | 470.31 |
VAV_TOP WITH REHEAT | 63492389.23 | 0.00 | 63492389.23 | 48026705.38 | 4093.90 | 2.52 | 4663.58 | 371.76 |
CAV_BAS | 16939315.50 | 0.00 | 16939315.50 | 37848132.68 | 6432.07 | 2.34 | 2325.58 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 1.33 | 0.00 | 8758.67 | 2816.67 |
AIRLOOP DATACENTER BOT | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3433009.67 | 0.00 | 3433009.67 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.3777 | 0.0000 | 4.3777 | 1.5229 | 1163.75 | 2.06 | 4777.19 |
VAV_MID WITH REHEAT | 29.9980 | 0.0000 | 29.9980 | 15.2292 | 1327.65 | 1.84 | 4613.50 |
VAV_TOP WITH REHEAT | 2.9029 | 0.0000 | 2.9029 | 1.5229 | 1377.63 | 2.52 | 4562.85 |
CAV_BAS | 0.7917 | 0.0000 | 0.7917 | 1.2002 | 3615.07 | 2.34 | 2325.58 |
AIRLOOP DATACENTER BASEMENT | 15.1686 | 0.0000 | 15.1686 | 0.3384 | 1.00 | 0.00 | 5942.00 |
AIRLOOP DATACENTER BOT | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1605 | 0.0000 | 0.1605 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 779.53 | 3203.53 | 0.00 | 0.00 | 0.00 | 1660.62 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 364.27 | 2578.65 | 0.00 | 0.00 | 0.00 | 2436.53 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 135.20 | 2378.14 | 0.00 | 0.00 | 0.00 | 2686.30 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1268.10 | 839.21 | 0.00 | 258.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8.83 | 8749.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.6230 | 7.6697 | 0.0000 | 0.0000 | 0.0000 | 2.3573 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.4311 | 53.8108 | 0.0000 | 0.0000 | 0.0000 | 22.3712 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.8442 | 5.3465 | 0.0000 | 0.0000 | 0.0000 | 2.2871 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6867 | 2.6246 | 0.0000 | 1.4134 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.5251 | 15.1935 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1523 |
Defaulted Fields | 1185 |
Fields with Defaults | 3960 |
Autosized Fields | 339 |
Autosizable Fields | 417 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
Electricity:Building | 17194.77 | 216479.19 | 06-MAY-18:20 | 1025582.59 | 01-DEC-08:10 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17194.77 | 216479.19 | 06-MAY-18:20 | 1025582.59 | 01-DEC-08:10 |
InteriorLights:Electricity | 2518.38 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2518.38 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2518.38 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2518.38 | 9223.03 | 02-APR-17:20 | 247210.90 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 48.62 | 603.11 | 02-APR-17:10 | 3823.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 12.26 | 43.94 | 05-FEB-12:30 | 1662.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 12.26 | 43.94 | 05-FEB-12:30 | 1662.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 31.23 | 388.67 | 02-APR-17:10 | 2463.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.80 | 28.32 | 16-JAN-12:00 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.80 | 28.32 | 16-JAN-12:00 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 48.21 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.85 | 43.94 | 15-JAN-11:40 | 1662.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.85 | 43.94 | 15-JAN-11:40 | 1662.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 31.20 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.76 | 28.32 | 05-FEB-11:50 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.76 | 28.32 | 05-FEB-11:50 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 486.03 | 6031.15 | 02-APR-17:10 | 38231.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 122.38 | 439.44 | 05-FEB-12:10 | 16625.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 122.38 | 439.44 | 05-FEB-12:10 | 16625.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 312.22 | 3886.70 | 02-APR-17:10 | 24637.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 77.87 | 283.19 | 16-JAN-11:50 | 10714.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 77.87 | 283.19 | 16-JAN-11:50 | 10714.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 482.10 | 6031.24 | 12-MAR-17:10 | 38231.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 118.44 | 439.45 | 15-JAN-11:40 | 16625.99 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 118.44 | 439.45 | 15-JAN-11:40 | 16625.99 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 311.87 | 3886.68 | 12-MAR-17:10 | 24637.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 77.52 | 283.19 | 29-JAN-12:00 | 10714.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 77.52 | 283.19 | 29-JAN-12:00 | 10714.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 48.60 | 603.11 | 02-APR-17:10 | 3823.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 12.24 | 43.94 | 05-FEB-12:10 | 1662.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 12.24 | 43.94 | 05-FEB-12:10 | 1662.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 31.22 | 388.67 | 02-APR-17:10 | 2463.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.79 | 28.32 | 16-JAN-11:50 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.79 | 28.32 | 16-JAN-11:50 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 48.21 | 603.12 | 12-MAR-17:10 | 3823.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.84 | 43.94 | 15-JAN-11:40 | 1662.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.84 | 43.94 | 15-JAN-11:40 | 1662.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 31.19 | 388.67 | 12-MAR-17:10 | 2463.75 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.75 | 28.32 | 29-JAN-12:00 | 1071.42 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.75 | 28.32 | 29-JAN-12:00 | 1071.42 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1199.22 | 3895.26 | 12-JAN-04:30 | 364419.19 | 30-JUN-12:30 |
HeatRejection:Electricity | 182.18 | 26.05 | 12-JAN-10:00 | 72747.30 | 29-JUN-10:50 |
General:HeatRejection:Electricity | 182.18 | 26.05 | 12-JAN-10:00 | 72747.30 | 29-JUN-10:50 |
Electricity:HVAC | 5105.02 | 53764.67 | 04-SEP-17:40 | 485078.63 | 10-AUG-16:00 |
ExteriorEquipment:Electricity | 2566.30 | 20217.42 | 01-JAN-00:10 | 233397.31 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.71 | 979.82 | 01-JAN-00:10 | 3412.97 | 04-DEC-15:10 |
ElectricityPurchased:Facility | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
ElectricityPurchased:Plant | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
Cogeneration:ElectricityPurchased | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
ElectricityNet:Plant | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
Cogeneration:ElectricityNet | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
General:Cogeneration:ElectricityNet | 26395.83 | 298774.22 | 04-SEP-17:40 | 1987468.20 | 11-AUG-15:40 |
Fans:Electricity | 2383.91 | 47670.69 | 01-JAN-18:40 | 271097.61 | 10-AUG-16:00 |
General:Fans:Electricity | 2383.91 | 47670.69 | 01-JAN-18:40 | 271097.61 | 10-AUG-16:00 |
ExteriorLights:Electricity | 385.22 | 0.00 | 01-JAN-11:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 385.22 | 0.00 | 01-JAN-11:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 47.11 | 0.00 | 01-JAN-00:10 | 5431.84 | 02-JAN-08:20 |
General:HeatRecovery:Electricity | 47.11 | 0.00 | 01-JAN-00:10 | 5431.84 | 02-JAN-08:20 |
Cooling:Electricity | 751.25 | 1424.14 | 12-JAN-08:10 | 331542.65 | 11-AUG-15:20 |
General:Cooling:Electricity | 751.25 | 1424.14 | 12-JAN-08:10 | 331542.65 | 11-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2091.78 | 0.00 | 02-JUN-21:00 | 100000.00 | 01-MAR-09:30 |
General:Humidifier:Electricity | 2091.78 | 0.00 | 02-JUN-21:00 | 100000.00 | 01-MAR-09:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 553.43 | 0.00 | 01-JAN-00:10 | 63525.20 | 11-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 553.43 | 0.00 | 01-JAN-00:10 | 63525.20 | 11-JAN-12:50 |
Pumps:Electricity | 239.88 | 3864.54 | 01-JAN-00:40 | 38878.57 | 11-AUG-15:40 |
General:Pumps:Electricity | 239.88 | 3864.54 | 01-JAN-00:40 | 38878.57 | 11-AUG-15:40 |
WIRED_LTG_ELECTRICITY | 70.77 | 0.00 | 01-JAN-00:10 | 6946.63 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4099.22 | 0.00 | 01-JAN-00:40 | 2644766.10 | 27-FEB-07:10 |
NaturalGas:Plant | 4099.22 | 0.00 | 01-JAN-00:40 | 2644766.10 | 27-FEB-07:10 |
Heating:NaturalGas | 4099.22 | 0.00 | 01-JAN-00:40 | 2644766.10 | 27-FEB-07:10 |
Boiler:Heating:NaturalGas | 4099.22 | 0.00 | 01-JAN-00:40 | 2644766.10 | 27-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4328.00 | 3131.07 | 12-JAN-08:10 | 1954333.84 | 11-AUG-15:40 |
PlantLoopCoolingDemand:HVAC | 4328.00 | 3131.07 | 12-JAN-08:10 | 1954333.84 | 11-AUG-15:40 |
CoolingCoils:PlantLoopCoolingDemand | 4328.00 | 3131.07 | 12-JAN-08:10 | 1954333.84 | 11-AUG-15:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4340.95 | 0.00 | 06-JUN-02:20 | 0.00 | 20-JUL-15:10 |
Water:HVAC | 778.14 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
Humidifier:Water | 778.14 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
General:Humidifier:Water | 778.14 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
MainsWater:Facility | 4340.95 | 0.00 | 06-JUN-02:20 | 0.00 | 20-JUL-15:10 |
MainsWater:HVAC | 778.14 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
Humidifier:MainsWater | 778.14 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
General:Humidifier:MainsWater | 778.14 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
Water:Plant | 3562.81 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-12:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3562.81 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-12:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1282.64 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-15:10 |
General:HeatRejection:Water | 1282.64 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-15:10 |
HeatRejection:MainsWater | 1282.64 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-15:10 |
General:HeatRejection:MainsWater | 1282.64 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-15:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 38137.68 | 91871.67 | 02-JAN-06:00 | 8110846.19 | 11-AUG-15:20 |
EnergyTransfer:Building | 17878.50 | 88814.40 | 27-JAN-22:30 | 1604998.46 | 10-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 263.40 | 0.00 | 01-JAN-00:10 | 104609.32 | 28-SEP-06:20 |
Heating:EnergyTransfer | 1647.96 | 0.00 | 01-FEB-00:20 | 1352679.53 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 416.46 | 23-MAR-06:30 |
General:Heating:EnergyTransfer | 1647.96 | 0.00 | 01-FEB-00:20 | 1352679.53 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 416.46 | 23-MAR-06:30 |
Cooling:EnergyTransfer | 16230.54 | 82955.11 | 02-JAN-04:40 | 1604998.46 | 10-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 263.40 | 0.00 | 01-JAN-00:10 | 104609.32 | 28-SEP-06:20 |
General:Cooling:EnergyTransfer | 16230.54 | 82955.11 | 02-JAN-04:40 | 1604998.46 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 263.40 | 0.00 | 01-JAN-00:10 | 104609.32 | 28-SEP-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 671.17 | 0.00 | 01-JAN-00:10 | 69608.44 | 24-JUL-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 671.17 | 0.00 | 01-JAN-00:10 | 69608.44 | 24-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 671.17 | 0.00 | 01-JAN-00:10 | 69608.44 | 24-JUL-05:10 |
EnergyTransfer:Zone:CORE_MID | 3679.11 | 0.00 | 01-JAN-00:40 | 452237.05 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 28.49 | 0.00 | 01-JAN-00:20 | 452237.05 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 28.49 | 0.00 | 01-JAN-00:20 | 452237.05 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3650.62 | 0.00 | 01-JAN-00:40 | 428281.18 | 05-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3650.62 | 0.00 | 01-JAN-00:40 | 428281.18 | 05-JUL-05:10 |
EnergyTransfer:Zone:CORE_TOP | 324.30 | 0.00 | 01-JAN-00:40 | 66929.00 | 27-NOV-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 55.70 | 0.00 | 01-JAN-00:40 | 66929.00 | 27-NOV-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 55.70 | 0.00 | 01-JAN-00:40 | 66929.00 | 27-NOV-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 268.60 | 0.00 | 01-JAN-00:20 | 43745.75 | 21-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 268.60 | 0.00 | 01-JAN-00:20 | 43745.75 | 21-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.57 | 0.00 | 01-JAN-00:10 | 14579.12 | 11-JUL-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.38 | 0.00 | 01-JAN-00:10 | 9219.62 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.38 | 0.00 | 01-JAN-00:10 | 9219.62 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.20 | 0.00 | 01-JAN-00:10 | 14579.12 | 11-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.20 | 0.00 | 01-JAN-00:10 | 14579.12 | 11-JUL-05:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 70.34 | 0.00 | 01-JAN-00:10 | 18780.43 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 4.30 | 0.00 | 01-JAN-00:10 | 7016.46 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 4.30 | 0.00 | 01-JAN-00:10 | 7016.46 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.04 | 0.00 | 01-JAN-00:10 | 18780.43 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.04 | 0.00 | 01-JAN-00:10 | 18780.43 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 115.49 | 0.00 | 01-JAN-00:10 | 27947.25 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 7.74 | 0.00 | 01-JAN-00:10 | 11994.60 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 7.74 | 0.00 | 01-JAN-00:10 | 11994.60 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 107.75 | 0.00 | 01-JAN-00:10 | 27947.25 | 31-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 107.75 | 0.00 | 01-JAN-00:10 | 27947.25 | 31-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 73.97 | 0.00 | 01-JAN-00:10 | 17185.46 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.49 | 0.00 | 01-JAN-00:10 | 4826.63 | 12-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.49 | 0.00 | 01-JAN-00:10 | 4826.63 | 12-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 73.48 | 0.00 | 01-JAN-00:10 | 17185.46 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 73.48 | 0.00 | 01-JAN-00:10 | 17185.46 | 10-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 697.79 | 0.00 | 01-JAN-00:40 | 126028.54 | 11-JUL-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 344.18 | 0.00 | 01-JAN-00:40 | 124473.38 | 30-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 344.18 | 0.00 | 01-JAN-00:40 | 124473.38 | 30-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 353.61 | 0.00 | 01-JAN-00:10 | 126028.54 | 11-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 353.61 | 0.00 | 01-JAN-00:10 | 126028.54 | 11-JUL-05:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 660.19 | 0.00 | 01-JAN-00:40 | 187364.55 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 206.44 | 0.00 | 01-JAN-00:40 | 127781.06 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 206.44 | 0.00 | 01-JAN-00:40 | 127781.06 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 453.74 | 0.00 | 01-JAN-00:20 | 187364.55 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 453.74 | 0.00 | 01-JAN-00:20 | 187364.55 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1110.09 | 0.00 | 01-JAN-00:40 | 284126.87 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 256.72 | 0.00 | 01-JAN-00:40 | 192392.82 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 256.72 | 0.00 | 01-JAN-00:40 | 192392.82 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 853.38 | 0.00 | 01-JAN-00:20 | 284126.87 | 31-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 853.38 | 0.00 | 01-JAN-00:20 | 284126.87 | 31-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 559.97 | 0.00 | 01-JAN-00:40 | 156493.25 | 06-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 173.35 | 0.00 | 01-JAN-00:40 | 117152.10 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 173.35 | 0.00 | 01-JAN-00:40 | 117152.10 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 386.62 | 0.00 | 01-JAN-00:20 | 156493.25 | 06-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 386.62 | 0.00 | 01-JAN-00:20 | 156493.25 | 06-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 103.91 | 0.00 | 01-JAN-00:40 | 15132.80 | 30-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.10 | 0.00 | 01-JAN-00:40 | 15132.80 | 30-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.10 | 0.00 | 01-JAN-00:40 | 15132.80 | 30-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.81 | 0.00 | 01-JAN-00:10 | 11924.62 | 11-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.81 | 0.00 | 01-JAN-00:10 | 11924.62 | 11-JUL-05:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 86.77 | 0.00 | 01-JAN-00:40 | 18652.82 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.68 | 0.00 | 01-JAN-00:40 | 17856.65 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.68 | 0.00 | 01-JAN-00:40 | 17856.65 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.09 | 0.00 | 01-JAN-00:20 | 18652.82 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.09 | 0.00 | 01-JAN-00:20 | 18652.82 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 132.36 | 0.00 | 01-JAN-00:40 | 28084.26 | 10-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.28 | 0.00 | 01-JAN-00:40 | 27128.71 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.28 | 0.00 | 01-JAN-00:40 | 27128.71 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 75.09 | 0.00 | 01-JAN-00:20 | 28084.26 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 75.09 | 0.00 | 01-JAN-00:20 | 28084.26 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 71.78 | 0.00 | 01-JAN-00:40 | 17429.07 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.16 | 0.00 | 01-JAN-00:40 | 17429.07 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.16 | 0.00 | 01-JAN-00:40 | 17429.07 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.61 | 0.00 | 01-JAN-00:20 | 15850.94 | 06-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.61 | 0.00 | 01-JAN-00:20 | 15850.94 | 06-JUL-17:40 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 70.98 | 0.00 | 01-JAN-00:10 | 14429.07 | 24-JUL-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 10.43 | 0.00 | 01-JAN-00:10 | 4599.81 | 01-MAR-13:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 10.43 | 0.00 | 01-JAN-00:10 | 4599.81 | 01-MAR-13:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.55 | 0.00 | 01-JAN-00:10 | 14429.07 | 24-JUL-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.55 | 0.00 | 01-JAN-00:10 | 14429.07 | 24-JUL-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 494.24 | 0.00 | 01-JAN-00:40 | 188331.59 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 229.27 | 0.00 | 01-JAN-00:40 | 188331.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 229.27 | 0.00 | 01-JAN-00:40 | 188331.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 264.97 | 0.00 | 01-JAN-00:10 | 71582.88 | 24-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 264.97 | 0.00 | 01-JAN-00:10 | 71582.88 | 24-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 134.53 | 0.00 | 01-JAN-00:40 | 33212.45 | 27-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.87 | 0.00 | 01-JAN-00:40 | 33212.45 | 27-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.87 | 0.00 | 01-JAN-00:40 | 33212.45 | 27-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.66 | 0.00 | 01-JAN-00:10 | 14755.46 | 21-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.66 | 0.00 | 01-JAN-00:10 | 14755.46 | 21-JUL-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.20 | 6.50 | 29-JAN-20:10 | 8678.63 | 27-AUG-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.03 | 0.00 | 02-JAN-07:10 | 298.65 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.03 | 0.00 | 02-JAN-07:10 | 298.65 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.17 | 0.00 | 01-JAN-00:10 | 8678.63 | 27-AUG-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 133.17 | 0.00 | 01-JAN-00:10 | 8678.63 | 27-AUG-19:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1096.27 | 13.87 | 06-JAN-20:00 | 82651.59 | 20-APR-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.17 | 0.00 | 02-JAN-07:20 | 5681.91 | 12-JAN-01:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.17 | 0.00 | 02-JAN-07:20 | 5681.91 | 12-JAN-01:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1089.10 | 0.00 | 01-JAN-00:10 | 82651.59 | 20-APR-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1089.10 | 0.00 | 01-JAN-00:10 | 82651.59 | 20-APR-19:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 95.20 | 0.87 | 30-SEP-10:50 | 8253.38 | 20-APR-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.19 | 0.00 | 02-JAN-07:20 | 596.27 | 10-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.19 | 0.00 | 02-JAN-07:20 | 596.27 | 10-JAN-00:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 94.01 | 0.00 | 01-JAN-00:10 | 8253.38 | 20-APR-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 94.01 | 0.00 | 01-JAN-00:10 | 8253.38 | 20-APR-19:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7159.87 | 82952.63 | 02-JAN-05:00 | 370167.01 | 11-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7159.87 | 82952.63 | 02-JAN-05:00 | 370167.01 | 11-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7159.87 | 82952.63 | 02-JAN-05:00 | 370167.01 | 11-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 3766.19 | 0.00 | 01-JAN-00:40 | 2198332.40 | 27-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 11-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 11-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 11-JAN-12:10 |
EnergyTransfer:HVAC | 10941.10 | 2577.74 | 12-JAN-03:50 | 2183816.36 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 3217.95 | 0.00 | 01-JAN-00:40 | 2177365.51 | 27-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 3217.95 | 0.00 | 01-JAN-00:40 | 2177365.51 | 27-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 3217.95 | 0.00 | 01-JAN-00:40 | 2177365.51 | 27-FEB-07:10 |
CoolingCoils:EnergyTransfer | 3800.47 | 1706.93 | 12-JAN-08:10 | 1820587.82 | 11-AUG-15:40 |
HeatRecoveryForHeating:EnergyTransfer | 3921.07 | 0.00 | 01-JAN-00:10 | 898149.78 | 03-MAR-10:30 |
HeatRecoveryForCooling:EnergyTransfer | 1.60 | 0.00 | 01-JAN-00:10 | 123026.06 | 29-JUL-16:00 |
EnergyTransfer:Plant | 9318.09 | 0.00 | 01-JAN-00:40 | 4727043.35 | 11-AUG-15:20 |
LoopToLoop:EnergyTransfer | 1777.67 | 0.00 | 01-JAN-00:10 | 1505151.21 | 11-AUG-15:20 |
WaterSystems:EnergyTransfer | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 11-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 11-JAN-12:10 |
Boilers:EnergyTransfer | 3201.09 | 0.00 | 01-JAN-00:40 | 2185374.21 | 27-FEB-07:10 |
Chillers:EnergyTransfer | 1783.68 | 0.00 | 01-JAN-00:10 | 1487938.18 | 11-AUG-15:20 |
HeatRejection:EnergyTransfer | 2007.41 | 0.00 | 01-JAN-00:10 | 1695794.10 | 03-JUL-15:00 |
General:HeatRejection:EnergyTransfer | 2007.41 | 0.00 | 01-JAN-00:10 | 1695794.10 | 03-JUL-15:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -263.393 | 0.000 | 0.000 | 73.090 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -399.824 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -671.168 | 0.000 | 0.000 | 83.555 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 149.163 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_MID | 0.000 | 0.000 | 28.487 | -3650.617 | 0.000 | 0.000 | 869.791 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1632.155 |
CORE_TOP | 0.000 | 0.000 | 55.698 | -268.597 | 0.000 | 0.000 | 91.211 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -316.761 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.375 | -69.197 | 0.000 | 0.000 | 11.252 | 12.256 | 36.365 | 24.309 | 0.000 | 0.001 | 80.681 | 0.000 | -96.668 | 0.000 | -3.376 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 4.300 | -66.036 | 0.000 | 0.000 | 7.197 | 7.798 | 23.435 | 58.256 | 0.000 | 0.001 | 28.239 | 0.000 | -60.938 | 0.000 | -2.252 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 7.735 | -107.752 | 0.000 | 0.000 | 11.121 | 11.847 | 36.366 | 115.192 | 0.000 | 0.001 | 15.171 | 0.000 | -86.309 | 0.000 | -3.372 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.486 | -73.483 | 0.000 | 0.000 | 7.002 | 7.761 | 23.435 | 39.902 | 0.000 | 0.001 | 63.354 | 0.000 | -66.091 | 0.000 | -2.368 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 344.181 | -353.611 | 0.000 | 0.000 | 115.922 | 122.377 | 363.654 | 253.767 | 0.000 | 0.038 | 128.316 | 0.000 | -901.531 | 0.000 | -73.113 | -0.009 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 206.443 | -453.743 | 0.000 | 0.000 | 54.002 | 77.865 | 234.352 | 585.561 | 0.000 | 0.023 | 0.012 | 0.000 | -575.329 | 0.000 | -49.855 | -79.320 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 256.714 | -853.369 | 0.000 | 0.000 | 112.855 | 118.443 | 363.660 | 1154.206 | 0.000 | 0.032 | 0.003 | 0.000 | -833.914 | 0.000 | -76.394 | -242.232 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 173.350 | -386.619 | 0.000 | 0.000 | 73.999 | 77.517 | 234.351 | 405.894 | 0.000 | 0.021 | 72.982 | 0.000 | -600.713 | 0.000 | -50.782 | -0.007 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 73.098 | -30.809 | 0.000 | 0.000 | 11.765 | 12.237 | 36.365 | 25.890 | 0.000 | 0.004 | 0.001 | 0.000 | -86.585 | 0.000 | -8.710 | -33.256 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 44.678 | -42.095 | 0.000 | 0.000 | 7.427 | 7.786 | 23.435 | 59.045 | 0.000 | 0.003 | 0.001 | 0.000 | -55.509 | 0.000 | -5.952 | -38.818 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 57.276 | -75.085 | 0.000 | 0.000 | 11.464 | 11.844 | 36.366 | 116.163 | 0.000 | 0.004 | 0.001 | 0.000 | -80.073 | 0.000 | -9.115 | -68.843 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 37.163 | -34.613 | 0.000 | 0.000 | 7.496 | 7.751 | 23.435 | 40.830 | 0.000 | 0.002 | 0.001 | 0.000 | -57.944 | 0.000 | -6.086 | -18.035 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.032 | -133.171 | 0.000 | 0.000 | 0.950 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.318 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.170 | -1089.097 | 0.000 | 0.000 | 9.579 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -502.722 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.195 | -94.009 | 0.000 | 0.000 | 0.967 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -65.660 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7159.875 | 0.000 | 0.000 | 20.566 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -403.159 |
GROUNDFLOOR_PLENUM | 10.430 | -60.551 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 57.195 | 0.000 | 0.000 | 0.000 | -7.076 | -0.001 |
MIDFLOOR_PLENUM | 229.275 | -264.965 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.039 | 156.497 | 0.000 | 0.000 | 0.000 | -120.846 | -0.002 |
TOPFLOOR_PLENUM | 105.865 | -28.662 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -13.066 | -64.140 |
Total Facility | 345.570 | -354.179 | 1302.381 | -15876.337 | 0.000 | 0.000 | 1581.213 | 2518.378 | 14676.396 | 2879.015 | 0.000 | 0.175 | 751.619 | 0.000 | -3501.606 | 0.000 | -432.363 | -3890.271 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-OCT-06:11 | 0.00 | 0.00 | 0.00 | -119903.28 | 0.00 | 0.00 | 1277.71 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 100253.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 16-AUG-04:13 | 0.00 | 0.00 | 0.00 | -96133.94 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 89658.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:13 | 0.00 | 0.00 | 0.00 | -831731.65 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 766981.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-AUG-05:04 | 0.00 | 0.00 | 0.00 | -74735.90 | 0.00 | 0.00 | 840.71 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 65710.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-12:52 | 0.00 | 0.00 | 0.00 | -17468.76 | 0.00 | 0.00 | 41.59 | 43.94 | 720.18 | 3954.26 | 0.00 | 0.00 | 12721.28 | 0.00 | -0.00 | 0.00 | -12.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-MAY-08:31 | 0.00 | 0.00 | 0.00 | -28656.71 | 0.00 | 0.00 | 15.40 | 28.32 | 464.11 | 22998.87 | 0.00 | 0.00 | 5340.46 | 0.00 | -0.00 | 0.00 | -190.45 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-JUL-12:52 | 0.00 | 0.00 | 0.00 | -42950.07 | 0.00 | 0.00 | 24.31 | 43.94 | 720.19 | 31299.44 | 0.00 | 0.00 | 10888.43 | 0.00 | -0.00 | 0.00 | -26.25 | 0.00 |
PERIMETER_BOT_ZN_4 | 21-MAY-17:51 | 0.00 | 0.00 | 0.00 | -30003.33 | 0.00 | 0.00 | 0.00 | 28.32 | 360.35 | 16630.86 | 0.00 | 0.00 | 13070.12 | 0.00 | -0.00 | 0.00 | -86.31 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUN-04:23 | 0.00 | 0.00 | 0.00 | -151555.59 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 146747.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3129.55 | -192.73 |
PERIMETER_MID_ZN_2 | 14-MAY-09:31 | 0.00 | 0.00 | 0.00 | -299348.52 | 0.00 | 0.00 | 161.01 | 283.19 | 4641.14 | 195505.34 | 0.00 | 0.00 | 101255.75 | 0.00 | -0.00 | 0.00 | -2497.91 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-13:01 | 0.00 | 0.00 | 0.00 | -455459.02 | 0.00 | 0.00 | 239.12 | 439.45 | 7201.95 | 310489.28 | 0.00 | 0.00 | 137929.90 | 0.00 | -0.00 | 0.00 | -840.68 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 | -288553.65 | 0.00 | 0.00 | 0.00 | 283.19 | 3603.49 | 169745.09 | 0.00 | 0.00 | 118997.81 | 0.00 | -0.00 | 0.00 | -4075.92 | 0.00 |
PERIMETER_TOP_ZN_3 | 07-JUN-04:11 | 0.00 | 0.00 | 0.00 | -16426.45 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 15985.27 | 0.00 | 0.00 | 38.09 | 0.00 | -0.00 | 0.00 | -409.93 | 0.00 |
PERIMETER_TOP_ZN_2 | 21-MAY-09:11 | 0.00 | 0.00 | 0.00 | -29205.56 | 0.00 | 0.00 | 18.00 | 28.32 | 464.11 | 21233.07 | 0.00 | 0.00 | 8116.66 | 0.00 | -0.00 | 0.00 | -654.60 | 0.00 |
PERIMETER_TOP_ZN_1 | 27-AUG-13:31 | 0.00 | 0.00 | 0.00 | -46507.63 | 0.00 | 0.00 | 25.62 | 43.94 | 720.19 | 29118.55 | 0.00 | 0.00 | 16837.35 | 0.00 | -0.00 | 0.00 | -238.02 | 0.00 |
PERIMETER_TOP_ZN_4 | 27-AUG-16:51 | 0.00 | 0.00 | 0.00 | -29422.52 | 0.00 | 0.00 | 18.75 | 28.32 | 464.11 | 18319.93 | 0.00 | 0.00 | 11037.44 | 0.00 | -0.00 | 0.00 | -446.02 | 0.00 |
DATACENTER_BOT_ZN_6 | 27-AUG-18:57 | 0.00 | 0.00 | 0.00 | -8678.63 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 866.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 20-APR-19:00 | 0.00 | 0.00 | 0.00 | -82646.30 | 0.00 | 0.00 | 106.16 | 1055.42 | 77944.22 | 0.00 | 0.00 | 0.00 | 3540.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 20-APR-19:00 | 0.00 | 0.00 | 0.00 | -8252.86 | 0.00 | 0.00 | 10.62 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 342.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | -370167.59 | 0.00 | 0.00 | 2183.08 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15805.20 |
GROUNDFLOOR_PLENUM | 24-JUL-05:10 | 0.00 | -16853.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16888.86 | 0.00 | -0.00 | 0.00 | -34.93 | 0.00 |
MIDFLOOR_PLENUM | 24-FEB-04:11 | 0.00 | -123420.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152269.76 | 0.00 | -0.00 | 0.00 | -28849.76 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:40 | 0.00 | -14757.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 14745.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-04:12 | 0.00 | 59662.30 | 0.00 | -1846672.34 | 0.00 | 0.00 | 0.00 | 10593.62 | 469008.02 | 113731.10 | 0.00 | 0.00 | 1231490.87 | 0.00 | -25371.50 | 0.00 | -12442.08 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-MAR-06:30 | 0.00 | 0.00 | 416.42 | 0.00 | 0.00 | 0.00 | 2000.16 | 4914.68 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20788.80 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 530046.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -594796.24 |
CORE_TOP | 30-JAN-04:11 | 0.00 | 0.00 | 75728.94 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -82203.92 |
PERIMETER_BOT_ZN_3 | 30-JAN-04:01 | 0.00 | 0.00 | 12717.24 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6735.28 | 0.00 | -494.28 | -6300.71 |
PERIMETER_BOT_ZN_2 | 30-JAN-04:01 | 0.00 | 0.00 | 14522.72 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4386.50 | 0.00 | -329.21 | -10330.96 |
PERIMETER_BOT_ZN_1 | 30-JAN-04:01 | 0.00 | 0.00 | 24292.75 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6365.87 | 0.00 | -479.54 | -18260.38 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:01 | 0.00 | 0.00 | 11831.60 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4628.74 | 0.00 | -350.74 | -7376.07 |
PERIMETER_MID_ZN_3 | 01-JAN-20:42 | 0.00 | 0.00 | 136236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45831.03 | 0.00 | -9168.55 | -87503.78 |
PERIMETER_MID_ZN_2 | 01-JAN-20:42 | 0.00 | 0.00 | 196574.56 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29879.09 | 0.00 | -6308.11 | -164425.68 |
PERIMETER_MID_ZN_1 | 01-JAN-20:42 | 0.00 | 0.00 | 294146.59 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44930.41 | 0.00 | -9472.36 | -246010.34 |
PERIMETER_MID_ZN_4 | 30-JAN-04:01 | 0.00 | 0.00 | 191077.95 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42006.78 | 0.00 | -7346.20 | -146964.42 |
PERIMETER_TOP_ZN_3 | 30-JAN-04:11 | 0.00 | 0.00 | 16463.03 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6055.04 | 0.00 | -1287.42 | -9933.61 |
PERIMETER_TOP_ZN_2 | 30-JAN-04:11 | 0.00 | 0.00 | 23075.86 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3950.03 | 0.00 | -870.57 | -18779.21 |
PERIMETER_TOP_ZN_1 | 30-JAN-04:11 | 0.00 | 0.00 | 35676.05 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5939.26 | 0.00 | -1309.88 | -29239.96 |
PERIMETER_TOP_ZN_4 | 30-JAN-04:11 | 0.00 | 0.00 | 23978.11 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4064.62 | 0.00 | -876.37 | -19561.06 |
DATACENTER_BOT_ZN_6 | 29-JAN-22:12 | 0.00 | 0.00 | 480.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2446.78 |
DATACENTER_MID_ZN_6 | 12-JAN-22:13 | 0.00 | 0.00 | 5760.00 | 0.00 | 0.00 | 0.00 | 55.54 | 351.80 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25653.39 |
DATACENTER_TOP_ZN_6 | 10-JAN-00:20 | 0.00 | 0.00 | 596.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2562.47 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 09-APR-15:22 | 12222.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -107.16 | -12115.33 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 219632.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -877.23 | -218755.07 |
TOPFLOOR_PLENUM | 27-FEB-05:33 | 36283.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36283.30 |
Total Facility | 02-JAN-04:01 | -56519.04 | 96051.07 | 1563042.63 | -96051.07 | 0.00 | 0.00 | 0.00 | 10151.57 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -180910.24 | 0.00 | -28807.68 | -1539382.47 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.5496 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.4223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 112.5609 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 87.6847 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.4069 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.4687 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1552 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1552 | 0.2328 | 1.0000 | Not calculated | 1.2002 | 0.2328 | ||
AIRLOOP DATACENTER BASEMENT | 24.9177 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.9177 | 0.0136 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.5060 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5060 | 0.0309 | 1.0000 | Not calculated | 0.0156 | 0.0309 | ||
AIRLOOP DATACENTER MID | 4.8726 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8726 | 0.0321 | 1.0000 | Not calculated | 0.1563 | 0.0321 | ||
AIRLOOP DATACENTER TOP | 0.4916 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4916 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.7748 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2859 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 56.2804 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8493 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.7035 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3081 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.9177 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.9177 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.5060 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5060 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0309 | ||
AIRLOOP DATACENTER MID | 4.8726 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8726 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0321 | ||
AIRLOOP DATACENTER TOP | 0.4916 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4916 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.1552 | 5.1552 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5598 | 5.5598 | 1.6179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.2999 | 52.2999 | 16.1607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1372 | 5.1372 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9587 | 0.9587 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3620 | 1.3620 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0720 | 2.0720 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5972 | 1.5972 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.9063 | 8.9063 | 2.0306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.6082 | 14.6082 | 1.3147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 21.9083 | 21.9083 | 2.0375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.8381 | 14.8381 | 1.3058 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0176 | 1.0176 | 0.2249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4572 | 1.4572 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2635 | 2.2635 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5314 | 1.5314 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5060 | 0.5060 | 0.5060 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8726 | 4.8726 | 4.8726 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4916 | 0.4916 | 0.4916 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.9177 | 24.9177 | 24.9177 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.5496 | 9.4223 | 11.5496 | 2.2859 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 112.5609 | 87.6847 | 112.5609 | 22.8493 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.4069 | 9.4687 | 11.4069 | 2.3081 | 0.0000 | 1.0000 |
CAV_BAS | 5.1552 | 5.1552 | 5.1552 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.9177 | 24.9177 | 24.9177 | 24.9177 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5060 | 0.5060 | 0.5060 | 0.5060 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8726 | 4.8726 | 4.8726 | 4.8726 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4916 | 0.4916 | 0.4916 | 0.4916 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7799 | 2.7799 | 1.6179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.1500 | 26.1500 | 16.1607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5686 | 2.5686 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4793 | 0.4793 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6810 | 0.6810 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0360 | 1.0360 | 0.2031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7986 | 0.7986 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4532 | 4.4532 | 2.0306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3041 | 7.3041 | 1.3147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.9541 | 10.9541 | 2.0375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4191 | 7.4191 | 1.3058 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5088 | 0.5088 | 0.2249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7286 | 0.7286 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1318 | 1.1318 | 0.2037 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7657 | 0.7657 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5060 | 0.5060 | 0.5060 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8726 | 4.8726 | 4.8726 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4916 | 0.4916 | 0.4916 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.9177 | 24.9177 | 24.9177 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.7748 | 2.2859 | 2.2859 | 2.2859 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 56.2804 | 22.8493 | 22.8493 | 22.8493 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.7035 | 2.3081 | 2.3081 | 2.3081 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.9177 | 24.9177 | 24.9177 | 24.9177 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5060 | 0.5060 | 0.5060 | 0.5060 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8726 | 4.8726 | 4.8726 | 4.8726 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4916 | 0.4916 | 0.4916 | 0.4916 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 230.17 |
Number of hours cooling loads not met | 2845.33 |
Number of hours not met | 2982.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4099.22 | 2644766.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 751.25 | 331542.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2518.38 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 385.22 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.71 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2383.91 | 271097.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 239.88 | 38878.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 182.18 | 72747.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2091.78 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 47.11 | 5431.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 553.43 | 63525.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26395.83 |
Natural Gas | 0.00 | 4099.22 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30495.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 54.37 |
Space Heating | 0.00 |
Space Cooling | 16.22 |
Fans (All) | 51.47 |
Service Water Heating | 11.95 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 569.85 |
Subtotal | 569.85 |
Natural Gas [MJ/m2] | |
Space Heating | 88.50 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 88.50 |
Subtotal | 88.50 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.26 |
Space Heating | 13.44 |
Space Cooling | 2.46 |
Fans (All) | 7.82 |
Service Water Heating | 1.81 |
Receptacle Equipment | 48.13 |
Miscellaneous | 18.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 704. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 4920.67 | 137.17 | 115.00 | 3587.17 | 0.00 |
CORE_BOTTOM | 8708.17 | 51.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8607.00 | 153.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8379.17 | 380.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Min | 4920.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 380.83 | 115.00 | 3587.17 | 0.00 |
Average | 8554.28 | 44.76 | 5.00 | 155.96 | 0.00 |
Sum | 196748.33 | 1029.50 | 115.00 | 3587.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 206949.83 | 7400.00 | 1351.33 | 152914.83 | 0.00 |
CORE_BOTTOM | 330727.00 | 86.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 99340.67 | 4054.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 7400.00 | 1351.33 | 152914.83 | 0.00 |
Average | 73125.93 | 501.75 | 58.75 | 6648.47 | 0.00 |
Sum | 1681896.50 | 11540.33 | 1351.33 | 152914.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 4939.00 | 124.00 | 77.50 | 3255.50 | 364.00 |
CORE_BOTTOM | 8669.67 | 90.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8598.17 | 161.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8720.17 | 39.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8479.17 | 280.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8682.50 | 77.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
Min | 4939.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 280.83 | 77.50 | 3255.50 | 364.00 |
Average | 8549.38 | 49.88 | 3.37 | 141.54 | 15.83 |
Sum | 196635.83 | 1147.17 | 77.50 | 3255.50 | 364.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 207615.00 | 6943.83 | 942.83 | 110635.00 | 42479.33 |
CORE_BOTTOM | 330636.00 | 177.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330754.00 | 59.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330773.00 | 40.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 100533.83 | 2861.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330773.00 | 6943.83 | 942.83 | 110635.00 | 42479.33 |
Average | 73198.47 | 438.30 | 40.99 | 4810.22 | 1846.93 |
Sum | 1683564.83 | 10081.00 | 942.83 | 110635.00 | 42479.33 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270470E+11 | 87243.12 | 06-JAN-15:10 | -10.5 | -10.8 | 0.568032E+10 | 7975.11 | 10-JAN-14:09 | -23.2 | -23.4 |
February | 0.292172E+11 | 94123.78 | 13-FEB-07:12 | -17.0 | -17.3 | 0.516347E+10 | 8385.74 | 09-FEB-08:09 | -17.0 | -17.3 |
March | 0.425188E+11 | 99032.06 | 20-MAR-06:11 | -5.4 | -6.3 | 0.616231E+10 | 7696.70 | 15-MAR-13:20 | -5.4 | -6.3 |
April | 0.425852E+11 | 108822.73 | 24-APR-06:11 | -3.7 | -6.2 | 0.574244E+10 | 10407.76 | 20-APR-13:00 | -3.7 | -6.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 | 2.18 | 0.944613E+10 | 12554.72 | 12-MAY-13:00 | 20.60 | 9.86 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.972526E+10 | 12744.69 | 09-JUN-13:00 | 20.60 | 10.21 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.921156E+10 | 13011.05 | 14-JUL-13:00 | 21.10 | 14.79 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 | 11.83 | 0.104872E+11 | 13198.04 | 11-AUG-13:00 | 23.90 | 13.74 |
September | 0.786631E+10 | 117576.06 | 28-SEP-06:11 | -2.8 | -4.0 | 0.867980E+10 | 13026.19 | 01-SEP-13:00 | -2.8 | -4.0 |
October | 0.405052E+11 | 119977.39 | 11-OCT-06:11 | -6.5 | -6.9 | 0.615564E+10 | 11865.34 | 10-OCT-13:00 | -6.5 | -6.9 |
November | 0.381075E+11 | 97095.61 | 13-NOV-07:11 | -17.0 | -17.4 | 0.564671E+10 | 7712.03 | 17-NOV-14:50 | -20.8 | -21.1 |
December | 0.355533E+11 | 99288.86 | 26-DEC-07:11 | -11.3 | -11.7 | 0.549682E+10 | 8119.71 | 27-DEC-10:20 | -19.6 | -19.9 |
Annual Sum or Average | 0.263401E+12 | 0.875976E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -17.0 | -17.4 | 0.516347E+10 | 7696.70 | -23.2 | -23.4 | ||
Maximum of Months | 0.425852E+11 | 119977.39 | 16.35 | 13.77 | 0.104872E+11 | 13198.04 | 23.90 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247049E+11 | 50763.84 | 20-JAN-06:01 | -7.6 | -7.8 | 0.494930E+10 | 6734.84 | 09-JAN-10:30 | -7.6 | -7.8 |
February | 0.273931E+11 | 77891.61 | 15-FEB-06:02 | -15.9 | -16.2 | 0.456558E+10 | 6734.80 | 01-FEB-10:20 | -15.9 | -16.2 |
March | 0.411138E+11 | 81155.63 | 21-MAR-04:01 | -4.9 | -6.1 | 0.548977E+10 | 6734.79 | 01-MAR-10:20 | -4.9 | -6.1 |
April | 0.524419E+11 | 88156.84 | 24-APR-03:02 | -2.8 | -5.4 | 0.488303E+10 | 6751.97 | 05-APR-13:00 | -2.8 | -5.4 |
May | 0.767173E+11 | 91063.14 | 06-MAY-04:02 | 1.88 | 0.90 | 0.530101E+10 | 6765.84 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.865426E+11 | 92824.69 | 27-JUN-04:13 | 13.90 | 12.14 | 0.528881E+10 | 6789.90 | 20-JUN-13:39 | 13.90 | 12.14 |
July | 0.904217E+11 | 92730.79 | 31-JUL-04:13 | 7.20 | 6.57 | 0.491915E+10 | 6811.73 | 19-JUL-13:00 | 7.20 | 6.57 |
August | 0.977192E+11 | 96134.69 | 16-AUG-04:13 | 11.10 | 10.40 | 0.551600E+10 | 6808.14 | 02-AUG-13:09 | 11.10 | 10.40 |
September | 0.700799E+11 | 92472.31 | 07-SEP-04:02 | 1.70 | 1.34 | 0.489480E+10 | 6741.77 | 07-SEP-09:39 | 6.87 | 3.88 |
October | 0.420826E+11 | 89932.12 | 10-OCT-03:02 | -0.6 | -0.9 | 0.507646E+10 | 6734.81 | 30-OCT-09:20 | -16.1 | -16.6 |
November | 0.312911E+11 | 78208.76 | 03-NOV-05:02 | -16.4 | -16.8 | 0.500328E+10 | 6734.83 | 28-NOV-10:20 | -28.9 | -29.1 |
December | 0.306599E+11 | 71308.41 | 21-DEC-06:01 | -13.9 | -14.2 | 0.486592E+10 | 6734.84 | 04-DEC-10:20 | -13.9 | -14.2 |
Annual Sum or Average | 0.671168E+12 | 0.607531E+11 | ||||||||
Minimum of Months | 0.247049E+11 | 50763.84 | -16.4 | -16.8 | 0.456558E+10 | 6734.79 | -28.9 | -29.1 | ||
Maximum of Months | 0.977192E+11 | 96134.69 | 13.90 | 12.14 | 0.551600E+10 | 6811.73 | 19.50 | 12.14 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174981E+11 | 15450.28 | 27-JAN-17:00 | -12.2 | -12.5 | 0.417057E+10 | 6366.21 | 26-JAN-14:00 | -12.2 | -12.5 |
February | 0.185885E+11 | 20960.74 | 17-FEB-13:20 | -15.8 | -16.4 | 0.405450E+10 | 6734.52 | 10-FEB-14:00 | -15.8 | -16.4 |
March | 0.252388E+11 | 51874.80 | 23-MAR-05:03 | -2.8 | -4.2 | 0.522916E+10 | 6734.76 | 29-MAR-09:20 | -11.8 | -13.8 |
April | 0.314822E+11 | 75129.97 | 21-APR-05:02 | -2.0 | -3.0 | 0.482120E+10 | 6734.76 | 10-APR-09:20 | -2.0 | -3.0 |
May | 0.427652E+11 | 75134.28 | 02-MAY-05:02 | 4.08 | 1.38 | 0.527686E+10 | 6734.80 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.459477E+11 | 76998.11 | 26-JUN-04:12 | 12.20 | 11.29 | 0.526669E+10 | 6734.80 | 27-JUN-13:20 | 14.27 | 13.39 |
July | 0.447361E+11 | 83177.62 | 24-JUL-04:13 | 12.80 | 12.43 | 0.489392E+10 | 6735.67 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.448998E+11 | 79522.23 | 14-AUG-04:12 | 11.50 | 10.36 | 0.549458E+10 | 6734.82 | 07-AUG-13:20 | 11.50 | 10.36 |
September | 0.331535E+11 | 75103.68 | 13-SEP-05:02 | 6.10 | 5.77 | 0.485920E+10 | 6740.76 | 21-SEP-09:50 | 7.30 | 6.45 |
October | 0.244479E+11 | 70458.16 | 06-OCT-05:02 | 6.60 | 2.71 | 0.488579E+10 | 6736.55 | 02-OCT-13:09 | 6.60 | 2.71 |
November | 0.185590E+11 | 16106.21 | 03-NOV-16:00 | -11.1 | -11.5 | 0.433624E+10 | 6579.92 | 03-NOV-13:00 | -11.1 | -11.5 |
December | 0.177455E+11 | 14849.24 | 22-DEC-17:00 | -21.7 | -22.0 | 0.404069E+10 | 6192.20 | 22-DEC-14:00 | -21.7 | -22.0 |
Annual Sum or Average | 0.365062E+12 | 0.573294E+11 | ||||||||
Minimum of Months | 0.174981E+11 | 14849.24 | -21.7 | -22.0 | 0.404069E+10 | 6192.20 | -21.7 | -22.0 | ||
Maximum of Months | 0.459477E+11 | 83177.62 | 12.80 | 12.43 | 0.549458E+10 | 6740.76 | 14.27 | 13.39 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647423E+10 | 12444.05 | 20-JAN-17:00 | -11.1 | -11.2 | 0.374387E+10 | 5443.95 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.883863E+10 | 14636.16 | 09-FEB-17:00 | -2.2 | -2.6 | 0.351104E+10 | 6117.63 | 09-FEB-14:00 | -2.2 | -2.6 |
March | 0.153946E+11 | 17892.34 | 22-MAR-16:00 | 5.60 | 2.61 | 0.445358E+10 | 6576.47 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.223130E+11 | 35266.94 | 21-APR-16:00 | 14.40 | 5.45 | 0.445809E+10 | 6742.64 | 18-APR-13:20 | 14.40 | 5.45 |
May | 0.366210E+11 | 67710.92 | 23-MAY-05:03 | 8.30 | 5.28 | 0.523190E+10 | 6743.03 | 26-MAY-09:39 | 7.80 | 3.10 |
June | 0.446438E+11 | 73688.28 | 24-JUN-04:12 | 12.40 | 11.57 | 0.526107E+10 | 6734.78 | 30-JUN-09:20 | 17.93 | 15.10 |
July | 0.432564E+11 | 74644.72 | 25-JUL-04:12 | 14.40 | 13.72 | 0.489007E+10 | 6735.54 | 19-JUL-09:09 | 14.40 | 13.72 |
August | 0.398564E+11 | 74745.98 | 05-AUG-05:04 | 13.98 | 12.01 | 0.546969E+10 | 6734.74 | 17-AUG-09:20 | 12.77 | 10.92 |
September | 0.229569E+11 | 32926.96 | 01-SEP-16:00 | 15.60 | 10.82 | 0.459989E+10 | 6752.68 | 08-SEP-09:00 | 7.20 | 3.85 |
October | 0.143465E+11 | 21458.28 | 04-OCT-16:00 | 10.00 | 4.57 | 0.415173E+10 | 6734.61 | 04-OCT-13:20 | 10.00 | 4.57 |
November | 0.750061E+10 | 12720.35 | 02-NOV-16:00 | -8.9 | -9.4 | 0.373462E+10 | 5485.04 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.639582E+10 | 11632.04 | 21-DEC-17:00 | -16.7 | -17.3 | 0.359224E+10 | 5209.51 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.268598E+12 | 0.530978E+11 | ||||||||
Minimum of Months | 0.639582E+10 | 11632.04 | -16.7 | -17.3 | 0.351104E+10 | 5209.51 | -16.7 | -17.3 | ||
Maximum of Months | 0.446438E+11 | 74745.98 | 15.60 | 13.72 | 0.546969E+10 | 6752.68 | 17.93 | 15.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423192E+09 | 1549.83 | 20-JAN-06:03 | -7.6 | -7.8 | 0.470339E+09 | 674.01 | 20-JAN-14:30 | -10.0 | -10.3 |
February | 0.106828E+10 | 2148.09 | 09-FEB-06:03 | 0.00 | -0.5 | 0.449007E+09 | 767.11 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.225683E+10 | 3690.48 | 22-MAR-13:50 | 5.40 | 1.85 | 0.594964E+09 | 845.62 | 22-MAR-09:00 | 5.40 | 1.85 |
April | 0.455487E+10 | 6435.51 | 24-APR-12:30 | 3.85 | -1.4 | 0.594700E+09 | 846.67 | 05-APR-13:00 | 3.85 | -1.4 |
May | 0.998317E+10 | 15341.68 | 31-MAY-04:14 | 12.03 | 7.57 | 0.664983E+09 | 850.20 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.140388E+11 | 16313.66 | 07-JUN-04:13 | 6.13 | 4.72 | 0.664290E+09 | 853.89 | 20-JUN-13:39 | 23.70 | 14.35 |
July | 0.140133E+11 | 17470.59 | 23-JUL-12:52 | 25.00 | 15.26 | 0.618123E+09 | 856.65 | 19-JUL-13:00 | 25.00 | 15.26 |
August | 0.124986E+11 | 14386.30 | 02-AUG-05:03 | 11.10 | 10.22 | 0.691977E+09 | 855.77 | 02-AUG-13:30 | 22.50 | 15.13 |
September | 0.615220E+10 | 10939.39 | 01-SEP-05:03 | 7.12 | 5.68 | 0.609506E+09 | 845.65 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.256296E+10 | 4172.31 | 04-OCT-14:30 | 11.10 | 4.80 | 0.571909E+09 | 845.62 | 05-OCT-09:20 | 1.67 | 0.09 |
November | 0.102052E+10 | 2072.90 | 03-NOV-05:02 | -16.4 | -16.8 | 0.480015E+09 | 723.61 | 02-NOV-13:00 | -16.4 | -16.8 |
December | 0.623770E+09 | 1586.47 | 26-DEC-11:02 | -10.1 | -10.9 | 0.457604E+09 | 703.01 | 26-DEC-10:00 | -10.1 | -10.9 |
Annual Sum or Average | 0.691965E+11 | 0.686742E+10 | ||||||||
Minimum of Months | 0.423192E+09 | 1549.83 | -16.4 | -16.8 | 0.449007E+09 | 674.01 | -16.4 | -16.8 | ||
Maximum of Months | 0.140388E+11 | 17470.59 | 25.00 | 15.26 | 0.691977E+09 | 856.65 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230029E+09 | 1018.37 | 20-JAN-06:03 | -7.6 | -7.8 | 0.302488E+09 | 427.11 | 20-JAN-10:00 | -7.2 | -7.5 |
February | 0.769951E+09 | 2770.61 | 15-FEB-10:35 | -16.3 | -16.5 | 0.300105E+09 | 544.95 | 09-FEB-10:00 | -16.3 | -16.5 |
March | 0.261901E+10 | 9883.99 | 27-MAR-09:25 | -10.6 | -12.5 | 0.417910E+09 | 544.95 | 01-MAR-10:39 | -10.6 | -12.5 |
April | 0.516141E+10 | 17514.28 | 23-APR-10:02 | 9.50 | 3.47 | 0.388743E+09 | 545.67 | 05-APR-13:00 | 9.50 | 3.47 |
May | 0.117921E+11 | 28654.60 | 21-MAY-08:31 | 11.27 | 5.47 | 0.429422E+09 | 548.75 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.127051E+11 | 23895.75 | 04-JUN-09:32 | 17.07 | 11.33 | 0.428522E+09 | 550.98 | 20-JUN-13:39 | 23.70 | 14.35 |
July | 0.128344E+11 | 28200.65 | 23-JUL-09:32 | 20.17 | 14.57 | 0.398879E+09 | 560.72 | 11-JUL-09:00 | 20.17 | 14.57 |
August | 0.112930E+11 | 20670.14 | 27-AUG-12:01 | 16.88 | 12.79 | 0.446284E+09 | 552.35 | 02-AUG-13:30 | 16.88 | 12.79 |
September | 0.595556E+10 | 23936.75 | 10-SEP-08:42 | 10.63 | 6.01 | 0.394330E+09 | 544.97 | 08-SEP-13:09 | 10.63 | 6.01 |
October | 0.205830E+10 | 9348.28 | 03-OCT-09:25 | 2.50 | 1.67 | 0.376893E+09 | 544.95 | 03-OCT-09:39 | 2.97 | 2.01 |
November | 0.474405E+09 | 1357.75 | 03-NOV-05:02 | -16.4 | -16.8 | 0.304538E+09 | 486.40 | 08-NOV-10:00 | -17.8 | -18.2 |
December | 0.142547E+09 | 1017.40 | 23-DEC-06:03 | -3.8 | -5.0 | 0.291457E+09 | 425.79 | 26-DEC-10:30 | -9.2 | -9.9 |
Annual Sum or Average | 0.660358E+11 | 0.447957E+10 | ||||||||
Minimum of Months | 0.142547E+09 | 1017.40 | -16.4 | -16.8 | 0.291457E+09 | 425.79 | -17.8 | -18.2 | ||
Maximum of Months | 0.128344E+11 | 28654.60 | 20.17 | 14.57 | 0.446284E+09 | 560.72 | 23.70 | 14.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462246E+09 | 3957.42 | 25-JAN-13:30 | -19.8 | -20.0 | 0.479547E+09 | 845.64 | 25-JAN-14:20 | -18.9 | -19.2 |
February | 0.213641E+10 | 13846.56 | 15-FEB-13:30 | -8.9 | -9.7 | 0.490841E+09 | 845.65 | 28-FEB-14:30 | -21.7 | -22.3 |
March | 0.684721E+10 | 28840.07 | 26-MAR-15:02 | -8.4 | -10.3 | 0.644469E+09 | 849.91 | 31-MAR-13:00 | -11.1 | -13.1 |
April | 0.121707E+11 | 35047.06 | 30-APR-13:12 | 8.50 | 4.36 | 0.599110E+09 | 847.69 | 05-APR-13:00 | 8.50 | 4.36 |
May | 0.155670E+11 | 40996.66 | 21-MAY-13:11 | 14.80 | 6.89 | 0.665620E+09 | 855.72 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.175646E+11 | 35584.41 | 11-JUN-13:52 | 17.20 | 10.80 | 0.665174E+09 | 861.88 | 20-JUN-13:39 | 23.70 | 14.35 |
July | 0.181380E+11 | 42955.44 | 23-JUL-12:52 | 25.00 | 15.26 | 0.619003E+09 | 864.40 | 19-JUL-13:00 | 25.00 | 15.26 |
August | 0.186572E+11 | 42786.60 | 27-AUG-13:22 | 18.60 | 13.91 | 0.693140E+09 | 862.82 | 02-AUG-13:30 | 18.60 | 13.91 |
September | 0.104311E+11 | 36086.61 | 10-SEP-11:22 | 15.00 | 8.08 | 0.609056E+09 | 846.46 | 08-SEP-13:09 | 15.00 | 8.08 |
October | 0.437844E+10 | 21706.92 | 03-OCT-13:10 | 10.28 | 6.00 | 0.584353E+09 | 846.71 | 03-OCT-13:00 | 11.70 | 6.58 |
November | 0.112725E+10 | 10609.40 | 08-NOV-13:30 | -13.6 | -14.4 | 0.495983E+09 | 845.65 | 09-NOV-14:30 | -17.8 | -18.3 |
December | 0.272450E+09 | 1670.20 | 27-DEC-13:10 | -23.4 | -23.6 | 0.452057E+09 | 697.21 | 27-DEC-13:20 | -23.5 | -23.7 |
Annual Sum or Average | 0.107753E+12 | 0.699835E+10 | ||||||||
Minimum of Months | 0.272450E+09 | 1670.20 | -23.4 | -23.6 | 0.452057E+09 | 697.21 | -23.5 | -23.7 | ||
Maximum of Months | 0.186572E+11 | 42955.44 | 25.00 | 15.26 | 0.693140E+09 | 864.40 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.714092E+09 | 1115.51 | 23-JAN-14:40 | -10.0 | -10.5 | 0.313620E+09 | 480.88 | 23-JAN-14:50 | -10.3 | -10.7 |
February | 0.135074E+10 | 3532.45 | 09-FEB-15:00 | 0.00 | -1.0 | 0.326894E+09 | 544.95 | 09-FEB-10:00 | 0.00 | -1.0 |
March | 0.361142E+10 | 18202.82 | 26-MAR-16:23 | -8.1 | -9.9 | 0.431936E+09 | 544.95 | 30-MAR-09:20 | -15.2 | -16.5 |
April | 0.945558E+10 | 27798.36 | 22-APR-17:42 | 13.07 | 5.65 | 0.395699E+09 | 546.87 | 05-APR-13:00 | 13.07 | 5.65 |
May | 0.906115E+10 | 30002.44 | 21-MAY-17:51 | 16.10 | 7.32 | 0.429076E+09 | 548.06 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.123896E+11 | 29164.99 | 11-JUN-17:51 | 18.30 | 10.84 | 0.428845E+09 | 551.56 | 20-JUN-13:00 | 23.90 | 14.09 |
July | 0.128578E+11 | 27810.28 | 08-JUL-18:22 | 20.00 | 15.37 | 0.399211E+09 | 553.91 | 19-JUL-13:00 | 22.80 | 14.62 |
August | 0.130399E+11 | 29658.10 | 27-AUG-15:22 | 20.85 | 12.83 | 0.447121E+09 | 553.01 | 02-AUG-13:30 | 20.85 | 12.83 |
September | 0.523228E+10 | 20278.73 | 02-SEP-17:05 | 16.70 | 10.21 | 0.394214E+09 | 544.97 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.273795E+10 | 10371.05 | 04-OCT-05:02 | 7.70 | 2.90 | 0.397666E+09 | 544.95 | 05-OCT-09:20 | 1.67 | 0.09 |
November | 0.151665E+10 | 3880.80 | 08-NOV-15:30 | -15.0 | -15.5 | 0.362476E+09 | 544.95 | 24-NOV-14:30 | -15.9 | -16.2 |
December | 0.151580E+10 | 1468.25 | 21-DEC-06:01 | -13.9 | -14.2 | 0.347898E+09 | 544.95 | 26-DEC-10:20 | -8.9 | -9.7 |
Annual Sum or Average | 0.734830E+11 | 0.467465E+10 | ||||||||
Minimum of Months | 0.714092E+09 | 1115.51 | -15.0 | -15.5 | 0.313620E+09 | 480.88 | -15.9 | -16.5 | ||
Maximum of Months | 0.130399E+11 | 30002.44 | 20.85 | 15.37 | 0.447121E+09 | 553.91 | 23.90 | 14.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12673692.23 | 1238.76 | 07-JAN-17:02 | -9.0 | -9.0 | 0.463369E+09 | 625.97 | 03-JAN-10:50 | -9.0 | -9.0 |
February | 99003113.64 | 1357.43 | 09-FEB-16:10 | 0.13 | -0.8 | 0.421445E+09 | 627.39 | 09-FEB-14:00 | 0.13 | -0.8 |
March | 0.738121E+09 | 1901.75 | 22-MAR-14:10 | 5.60 | 1.96 | 0.520890E+09 | 791.37 | 22-MAR-13:00 | 5.60 | 1.96 |
April | 0.236845E+10 | 4438.93 | 28-APR-14:00 | 11.70 | 4.88 | 0.538643E+09 | 845.62 | 24-APR-13:20 | 11.70 | 4.88 |
May | 0.565557E+10 | 12585.38 | 31-MAY-04:12 | 12.03 | 7.57 | 0.659004E+09 | 845.63 | 19-MAY-13:39 | 12.03 | 7.57 |
June | 0.892997E+10 | 15154.98 | 16-JUN-04:23 | 8.85 | 7.57 | 0.661477E+09 | 845.64 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.810767E+10 | 15091.26 | 07-JUL-04:13 | 13.87 | 10.90 | 0.615232E+09 | 845.74 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.579376E+10 | 11189.40 | 02-AUG-05:02 | 11.10 | 10.22 | 0.684251E+09 | 845.63 | 07-AUG-13:20 | 14.07 | 12.51 |
September | 0.264097E+10 | 4385.41 | 01-SEP-13:40 | 14.63 | 10.60 | 0.561832E+09 | 845.63 | 01-SEP-13:20 | 14.63 | 10.60 |
October | 0.984655E+09 | 2060.90 | 06-OCT-05:02 | 6.60 | 2.71 | 0.494173E+09 | 808.16 | 04-OCT-13:00 | 6.60 | 2.71 |
November | 15428520.17 | 1239.40 | 04-NOV-16:03 | -9.6 | -11.3 | 0.459703E+09 | 625.96 | 29-NOV-10:50 | -28.6 | -28.8 |
December | 14861040.04 | 1234.24 | 30-DEC-17:02 | -10.0 | -10.4 | 0.447154E+09 | 626.00 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.353611E+11 | 0.652717E+10 | ||||||||
Minimum of Months | 12673692.23 | 1234.24 | -10.0 | -11.3 | 0.421445E+09 | 625.96 | -28.6 | -28.8 | ||
Maximum of Months | 0.892997E+10 | 15154.98 | 14.63 | 10.90 | 0.684251E+09 | 845.74 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28843728.10 | 943.24 | 19-JAN-13:04 | -7.1 | -7.8 | 0.215171E+09 | 391.15 | 20-JAN-11:30 | -7.5 | -7.8 |
February | 0.164221E+09 | 1298.54 | 15-FEB-11:05 | -14.9 | -15.2 | 0.201422E+09 | 520.20 | 15-FEB-11:09 | -14.9 | -15.2 |
March | 0.139552E+10 | 9684.14 | 31-MAR-10:05 | -15.9 | -17.2 | 0.283148E+09 | 548.49 | 28-MAR-10:09 | -15.9 | -17.2 |
April | 0.389161E+10 | 17693.40 | 23-APR-09:02 | 8.48 | 2.77 | 0.277977E+09 | 548.50 | 21-APR-10:09 | 8.48 | 2.77 |
May | 0.914723E+10 | 29936.29 | 14-MAY-09:31 | 15.73 | 8.25 | 0.315648E+09 | 548.50 | 19-MAY-14:09 | 13.48 | 8.19 |
June | 0.979774E+10 | 24754.27 | 18-JUN-09:31 | 14.03 | 11.23 | 0.314804E+09 | 548.50 | 13-JUN-12:09 | 14.03 | 11.23 |
July | 0.962974E+10 | 29787.41 | 23-JUL-09:41 | 20.63 | 14.69 | 0.294087E+09 | 548.86 | 11-JUL-10:09 | 20.63 | 14.69 |
August | 0.744156E+10 | 18028.12 | 10-AUG-10:05 | 18.07 | 11.40 | 0.327573E+09 | 548.51 | 24-AUG-12:09 | 20.28 | 14.31 |
September | 0.296442E+10 | 19769.39 | 10-SEP-09:42 | 12.52 | 6.99 | 0.281633E+09 | 548.50 | 01-SEP-10:09 | 12.52 | 6.99 |
October | 0.859788E+09 | 8449.68 | 03-OCT-10:05 | 4.27 | 2.93 | 0.249188E+09 | 548.49 | 03-OCT-10:09 | 4.27 | 2.93 |
November | 35195295.70 | 933.98 | 07-NOV-15:04 | -17.1 | -17.6 | 0.214026E+09 | 396.76 | 01-NOV-10:30 | -17.1 | -17.6 |
December | 18246891.55 | 922.71 | 19-DEC-13:04 | -12.5 | -13.0 | 0.206818E+09 | 385.87 | 27-DEC-13:39 | -23.7 | -23.9 |
Annual Sum or Average | 0.453741E+11 | 0.318149E+10 | ||||||||
Minimum of Months | 18246891.55 | 922.71 | -17.1 | -17.6 | 0.201422E+09 | 385.87 | -23.7 | -23.9 | ||
Maximum of Months | 0.979774E+10 | 29936.29 | 20.63 | 14.69 | 0.327573E+09 | 548.86 | 20.63 | 14.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199303E+09 | 2847.10 | 25-JAN-13:20 | -20.0 | -20.3 | 0.471266E+09 | 845.09 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.150131E+10 | 13141.73 | 15-FEB-13:40 | -8.7 | -9.6 | 0.467666E+09 | 845.64 | 22-FEB-14:00 | -16.7 | -17.5 |
March | 0.628702E+10 | 38786.13 | 12-MAR-13:32 | -7.6 | -9.2 | 0.616497E+09 | 846.89 | 31-MAR-13:00 | -11.1 | -13.1 |
April | 0.114566E+11 | 37595.58 | 23-APR-13:02 | 10.00 | 3.85 | 0.584287E+09 | 847.36 | 26-APR-13:20 | 10.93 | 4.19 |
May | 0.130240E+11 | 43243.52 | 14-MAY-12:11 | 18.17 | 9.44 | 0.660222E+09 | 847.75 | 12-MAY-13:00 | 18.17 | 9.44 |
June | 0.137813E+11 | 40902.01 | 18-JUN-12:51 | 16.70 | 11.52 | 0.661976E+09 | 847.67 | 16-JUN-13:20 | 16.70 | 11.52 |
July | 0.136749E+11 | 45533.38 | 23-JUL-13:01 | 25.00 | 15.26 | 0.615943E+09 | 847.57 | 21-JUL-13:20 | 25.00 | 15.26 |
August | 0.136447E+11 | 39960.15 | 27-AUG-13:42 | 19.13 | 14.11 | 0.688544E+09 | 847.75 | 04-AUG-13:20 | 19.13 | 14.11 |
September | 0.789932E+10 | 37567.90 | 10-SEP-11:42 | 15.40 | 8.26 | 0.591897E+09 | 845.72 | 07-SEP-13:30 | 15.40 | 8.26 |
October | 0.336975E+10 | 21667.40 | 03-OCT-13:30 | 10.85 | 6.24 | 0.552785E+09 | 845.66 | 04-OCT-13:30 | 11.40 | 4.98 |
November | 0.473320E+09 | 8674.66 | 08-NOV-13:40 | -13.5 | -14.3 | 0.475584E+09 | 845.64 | 08-NOV-14:30 | -13.6 | -14.3 |
December | 26294736.77 | 1414.52 | 19-DEC-06:04 | -21.1 | -21.4 | 0.447558E+09 | 625.97 | 22-DEC-10:50 | -24.1 | -24.4 |
Annual Sum or Average | 0.853378E+11 | 0.683422E+10 | ||||||||
Minimum of Months | 26294736.77 | 1414.52 | -21.1 | -21.4 | 0.447558E+09 | 625.97 | -24.1 | -24.4 | ||
Maximum of Months | 0.137813E+11 | 45533.38 | 25.00 | 15.26 | 0.688544E+09 | 847.75 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14484748.65 | 912.05 | 18-JAN-06:04 | -20.0 | -20.2 | 0.299277E+09 | 403.41 | 03-JAN-10:09 | -20.0 | -20.2 |
February | 0.192896E+09 | 1127.48 | 16-FEB-15:50 | -4.5 | -6.8 | 0.275249E+09 | 469.17 | 09-FEB-14:00 | -4.5 | -6.8 |
March | 0.108750E+10 | 5669.94 | 27-MAR-16:50 | -4.9 | -8.2 | 0.353881E+09 | 544.87 | 22-MAR-13:00 | -4.9 | -8.2 |
April | 0.451626E+10 | 25117.80 | 22-APR-17:42 | 13.07 | 5.65 | 0.367307E+09 | 544.95 | 24-APR-13:20 | 4.40 | -1.0 |
May | 0.640970E+10 | 28451.32 | 14-MAY-18:51 | 16.70 | 9.05 | 0.425574E+09 | 544.96 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.860600E+10 | 28854.81 | 11-JUN-17:01 | 18.80 | 10.99 | 0.426979E+09 | 544.96 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.766232E+10 | 25894.14 | 23-JUL-15:41 | 25.60 | 14.89 | 0.397141E+09 | 545.03 | 19-JUL-09:09 | 25.60 | 14.89 |
August | 0.645309E+10 | 25921.22 | 27-AUG-17:42 | 20.68 | 12.29 | 0.443458E+09 | 544.96 | 07-AUG-13:20 | 20.68 | 12.29 |
September | 0.274931E+10 | 17305.03 | 02-SEP-17:05 | 16.70 | 10.21 | 0.372828E+09 | 544.96 | 01-SEP-13:20 | 16.70 | 10.21 |
October | 0.888545E+09 | 4187.16 | 03-OCT-15:10 | 12.62 | 6.83 | 0.329244E+09 | 544.94 | 04-OCT-13:30 | 11.40 | 4.98 |
November | 63279954.22 | 1072.19 | 08-NOV-15:40 | -15.4 | -15.8 | 0.297185E+09 | 448.26 | 08-NOV-15:50 | -15.7 | -16.1 |
December | 18928808.20 | 931.43 | 19-DEC-06:04 | -21.1 | -21.4 | 0.288767E+09 | 403.38 | 15-DEC-14:09 | -21.1 | -21.4 |
Annual Sum or Average | 0.386623E+11 | 0.427689E+10 | ||||||||
Minimum of Months | 14484748.65 | 912.05 | -21.1 | -21.4 | 0.275249E+09 | 403.38 | -21.1 | -21.4 | ||
Maximum of Months | 0.860600E+10 | 28854.81 | 25.60 | 14.89 | 0.443458E+09 | 545.03 | 25.60 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9642800.47 | 1340.20 | 07-JAN-17:02 | -9.0 | -9.0 | 0.460279E+09 | 626.04 | 12-JAN-14:50 | -36.1 | -36.2 |
February | 14434890.63 | 1354.27 | 11-FEB-17:03 | -1.2 | -2.7 | 0.418533E+09 | 625.99 | 28-FEB-10:09 | -25.1 | -25.4 |
March | 0.204187E+09 | 1875.52 | 22-MAR-15:30 | 5.60 | 2.42 | 0.505623E+09 | 710.77 | 22-MAR-13:00 | 5.60 | 2.42 |
April | 0.170770E+10 | 3637.69 | 28-APR-15:20 | 12.20 | 4.90 | 0.496702E+09 | 845.60 | 28-APR-13:20 | 12.20 | 4.90 |
May | 0.486311E+10 | 12015.62 | 31-MAY-05:03 | 12.07 | 7.63 | 0.646625E+09 | 845.63 | 19-MAY-13:39 | 12.07 | 7.63 |
June | 0.864491E+10 | 16426.61 | 07-JUN-04:11 | 6.13 | 4.72 | 0.660546E+09 | 845.64 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.786320E+10 | 16355.00 | 07-JUL-04:13 | 13.87 | 10.90 | 0.614140E+09 | 845.72 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.528187E+10 | 11787.72 | 05-AUG-05:02 | 13.98 | 12.01 | 0.672290E+09 | 845.62 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.186839E+10 | 3417.97 | 01-SEP-16:00 | 15.60 | 10.82 | 0.507988E+09 | 845.61 | 01-SEP-13:20 | 15.60 | 10.82 |
October | 0.330004E+09 | 1887.56 | 04-OCT-15:50 | 10.18 | 4.62 | 0.470215E+09 | 723.12 | 04-OCT-13:00 | 10.18 | 4.62 |
November | 8967774.41 | 1331.43 | 18-NOV-17:02 | -13.0 | -13.3 | 0.456984E+09 | 626.01 | 20-NOV-10:09 | -18.9 | -19.2 |
December | 12307244.47 | 1332.42 | 30-DEC-17:02 | -10.0 | -10.4 | 0.444221E+09 | 626.04 | 27-DEC-14:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.308087E+11 | 0.635415E+10 | ||||||||
Minimum of Months | 8967774.41 | 1331.43 | -13.0 | -13.3 | 0.418533E+09 | 625.99 | -36.1 | -36.2 | ||
Maximum of Months | 0.864491E+10 | 16426.61 | 15.60 | 12.01 | 0.672290E+09 | 845.72 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10647752.69 | 954.63 | 07-JAN-06:04 | -6.8 | -6.9 | 0.298585E+09 | 403.43 | 30-JAN-10:09 | -25.5 | -25.9 |
February | 52725573.02 | 971.59 | 15-FEB-10:50 | -16.0 | -16.2 | 0.271622E+09 | 437.91 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.861254E+09 | 4864.12 | 22-MAR-10:30 | 2.25 | 0.43 | 0.359424E+09 | 544.95 | 15-MAR-09:30 | 2.25 | 0.43 |
April | 0.304665E+10 | 13536.23 | 23-APR-10:32 | 9.80 | 3.70 | 0.365392E+09 | 546.92 | 21-APR-09:30 | 9.80 | 3.70 |
May | 0.862374E+10 | 29204.75 | 21-MAY-09:11 | 12.40 | 5.80 | 0.425994E+09 | 546.12 | 15-MAY-09:50 | 12.40 | 5.80 |
June | 0.986644E+10 | 22436.62 | 18-JUN-10:11 | 14.23 | 11.41 | 0.426517E+09 | 546.01 | 07-JUN-09:00 | 14.23 | 11.41 |
July | 0.969110E+10 | 26827.26 | 09-JUL-08:21 | 16.95 | 12.65 | 0.396995E+09 | 546.52 | 07-JUL-09:50 | 16.95 | 12.65 |
August | 0.716043E+10 | 24515.13 | 27-AUG-10:52 | 13.90 | 11.12 | 0.443457E+09 | 545.78 | 09-AUG-09:00 | 13.90 | 11.12 |
September | 0.226949E+10 | 24794.30 | 10-SEP-09:32 | 12.23 | 6.85 | 0.360801E+09 | 549.01 | 08-SEP-09:00 | 12.23 | 6.85 |
October | 0.490009E+09 | 3978.27 | 03-OCT-10:00 | 3.90 | 2.68 | 0.317177E+09 | 544.95 | 13-OCT-09:50 | -7.1 | -8.0 |
November | 10407627.48 | 925.15 | 01-NOV-05:04 | -9.6 | -10.6 | 0.295801E+09 | 403.43 | 27-NOV-10:50 | -27.2 | -27.4 |
December | 11887945.61 | 894.35 | 12-DEC-06:04 | -23.2 | -23.4 | 0.287897E+09 | 403.49 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.420948E+11 | 0.424966E+10 | ||||||||
Minimum of Months | 10407627.48 | 894.35 | -23.2 | -23.4 | 0.271622E+09 | 403.43 | -27.2 | -27.4 | ||
Maximum of Months | 0.986644E+10 | 29204.75 | 16.95 | 12.65 | 0.443457E+09 | 549.01 | 16.95 | 12.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93834156.92 | 1716.34 | 25-JAN-13:40 | -19.5 | -19.7 | 0.465137E+09 | 729.21 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.792795E+09 | 9599.34 | 15-FEB-13:40 | -8.7 | -9.6 | 0.448433E+09 | 845.63 | 17-FEB-14:00 | -11.1 | -12.7 |
March | 0.431064E+10 | 19493.68 | 31-MAR-14:00 | -11.1 | -13.1 | 0.584440E+09 | 845.64 | 01-MAR-14:30 | -11.1 | -13.1 |
April | 0.943368E+10 | 38362.67 | 23-APR-13:11 | 10.00 | 3.85 | 0.562938E+09 | 850.06 | 18-APR-13:20 | 10.00 | 3.85 |
May | 0.120609E+11 | 44727.24 | 14-MAY-12:41 | 18.72 | 9.38 | 0.651356E+09 | 847.88 | 12-MAY-13:00 | 18.72 | 9.38 |
June | 0.135385E+11 | 42011.28 | 18-JUN-12:51 | 16.70 | 11.52 | 0.660551E+09 | 846.11 | 16-JUN-13:00 | 16.70 | 11.52 |
July | 0.134468E+11 | 42359.34 | 23-JUL-13:11 | 25.00 | 15.26 | 0.614713E+09 | 847.37 | 20-JUL-13:50 | 25.00 | 15.26 |
August | 0.128868E+11 | 46509.64 | 27-AUG-13:31 | 18.87 | 14.02 | 0.683304E+09 | 846.37 | 31-AUG-13:00 | 13.30 | 4.88 |
September | 0.621824E+10 | 38763.63 | 10-SEP-11:31 | 15.20 | 8.17 | 0.559033E+09 | 850.19 | 08-SEP-09:00 | 15.20 | 8.17 |
October | 0.206738E+10 | 18910.33 | 03-OCT-13:30 | 10.85 | 6.24 | 0.513064E+09 | 845.64 | 04-OCT-13:20 | 11.50 | 5.03 |
November | 0.218227E+09 | 5375.09 | 08-NOV-13:40 | -13.5 | -14.3 | 0.465505E+09 | 845.64 | 08-NOV-14:30 | -13.6 | -14.3 |
December | 18784294.56 | 1394.07 | 22-DEC-06:04 | -27.2 | -27.4 | 0.446823E+09 | 626.07 | 22-DEC-10:50 | -24.1 | -24.4 |
Annual Sum or Average | 0.750866E+11 | 0.665530E+10 | ||||||||
Minimum of Months | 18784294.56 | 1394.07 | -27.2 | -27.4 | 0.446823E+09 | 626.07 | -24.1 | -24.4 | ||
Maximum of Months | 0.135385E+11 | 46509.64 | 25.00 | 15.26 | 0.683304E+09 | 850.19 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12234770.40 | 929.76 | 07-JAN-06:04 | -6.8 | -6.9 | 0.298703E+09 | 403.40 | 30-JAN-10:50 | -25.1 | -25.5 |
February | 67319075.68 | 1006.29 | 09-FEB-15:40 | 0.40 | -0.7 | 0.272123E+09 | 441.61 | 09-FEB-14:00 | 0.40 | -0.7 |
March | 0.593586E+09 | 4160.38 | 27-MAR-17:00 | -5.0 | -8.2 | 0.338669E+09 | 521.17 | 22-MAR-15:00 | -5.0 | -8.2 |
April | 0.365245E+10 | 24108.33 | 22-APR-17:42 | 13.07 | 5.65 | 0.346575E+09 | 544.95 | 14-APR-13:20 | 13.07 | 5.65 |
May | 0.582969E+10 | 29305.12 | 14-MAY-18:41 | 16.70 | 9.10 | 0.420006E+09 | 544.96 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.843736E+10 | 26912.50 | 10-JUN-17:42 | 21.60 | 11.19 | 0.426441E+09 | 544.97 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.750066E+10 | 27339.11 | 09-JUL-19:42 | 19.50 | 13.10 | 0.396653E+09 | 545.02 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.599418E+10 | 29421.34 | 27-AUG-16:51 | 21.10 | 12.86 | 0.439469E+09 | 544.95 | 18-AUG-13:20 | 21.10 | 12.86 |
September | 0.206641E+10 | 15194.23 | 02-SEP-17:05 | 16.70 | 10.21 | 0.347145E+09 | 544.95 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.427212E+09 | 2750.39 | 03-OCT-15:10 | 12.62 | 6.83 | 0.311051E+09 | 521.17 | 12-OCT-15:00 | -0.6 | -3.4 |
November | 17773925.51 | 939.08 | 21-NOV-06:04 | -18.4 | -18.7 | 0.296081E+09 | 405.22 | 08-NOV-14:00 | -18.4 | -18.7 |
December | 14704310.92 | 931.87 | 21-DEC-06:04 | -13.9 | -14.2 | 0.288128E+09 | 403.49 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.346136E+11 | 0.418105E+10 | ||||||||
Minimum of Months | 12234770.40 | 929.76 | -18.4 | -18.7 | 0.272123E+09 | 403.40 | -25.1 | -25.5 | ||
Maximum of Months | 0.843736E+10 | 29421.34 | 21.60 | 13.10 | 0.439469E+09 | 545.02 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30034662.36 | 9951.31 | 12-JAN-05:01 | -37.9 | -38.0 | 0.00 | 0.00 | 01-JAN-00:10 | -37.9 | -38.0 |
February | 0.118804E+09 | 8620.42 | 27-FEB-05:01 | -36.1 | -36.2 | 0.00 | 0.00 | 01-FEB-00:10 | -36.1 | -36.2 |
March | 0.727119E+09 | 5771.64 | 04-MAR-06:01 | -26.3 | -26.7 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.7 |
April | 0.404566E+10 | 7565.47 | 24-APR-05:15 | -3.5 | -6.1 | 0.00 | 0.00 | 01-APR-00:10 | -3.5 | -6.1 |
May | 0.973773E+10 | 13968.81 | 15-MAY-05:10 | 6.88 | 1.81 | 0.00 | 0.00 | 01-MAY-00:10 | 6.88 | 1.81 |
June | 0.122471E+11 | 14356.19 | 12-JUN-05:15 | 8.87 | 6.78 | 0.00 | 0.00 | 01-JUN-00:10 | 8.87 | 6.78 |
July | 0.125617E+11 | 16854.89 | 24-JUL-05:10 | 12.98 | 12.52 | 0.00 | 0.00 | 01-JUL-00:10 | 12.98 | 12.52 |
August | 0.124151E+11 | 14602.99 | 14-AUG-05:10 | 11.10 | 10.22 | 0.00 | 0.00 | 01-AUG-00:10 | 11.10 | 10.22 |
September | 0.686265E+10 | 9537.13 | 18-SEP-05:10 | 1.78 | 1.10 | 0.00 | 0.00 | 01-SEP-00:10 | 1.78 | 1.10 |
October | 0.175578E+10 | 5842.22 | 10-OCT-05:15 | -0.6 | -1.1 | 0.00 | 0.00 | 01-OCT-00:10 | -0.6 | -1.1 |
November | 30747284.55 | 6876.61 | 27-NOV-05:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-NOV-00:10 | -25.8 | -26.0 |
December | 18957125.79 | 6276.15 | 15-DEC-05:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-DEC-00:10 | -33.2 | -33.3 |
Annual Sum or Average | 0.605513E+11 | 0.00 | ||||||||
Minimum of Months | 18957125.79 | 5771.64 | -37.9 | -38.0 | 0.00 | 0.00 | -37.9 | -38.0 | ||
Maximum of Months | 0.125617E+11 | 16854.89 | 12.98 | 12.52 | 0.00 | 0.00 | 12.98 | 12.52 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242625E+09 | 11326.95 | 13-JAN-04:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-JAN-00:10 | -33.2 | -33.3 |
February | 0.220976E+09 | 12342.40 | 24-FEB-04:11 | -25.2 | -25.7 | 0.00 | 0.00 | 01-FEB-00:10 | -25.2 | -25.7 |
March | 0.203854E+09 | 11551.27 | 16-MAR-04:01 | -25.1 | -25.6 | 0.00 | 0.00 | 01-MAR-00:10 | -25.1 | -25.6 |
April | 0.133936E+10 | 9530.09 | 03-APR-04:01 | -21.1 | -21.6 | 0.00 | 0.00 | 01-APR-00:10 | -21.1 | -21.6 |
May | 0.416413E+10 | 5348.78 | 31-MAY-14:20 | 20.37 | 10.35 | 0.00 | 0.00 | 01-MAY-00:10 | 20.37 | 10.35 |
June | 0.630427E+10 | 7153.13 | 21-JUN-05:15 | 13.50 | 10.96 | 0.00 | 0.00 | 01-JUN-00:10 | 13.50 | 10.96 |
July | 0.620246E+10 | 9293.09 | 24-JUL-05:15 | 13.17 | 12.61 | 0.00 | 0.00 | 01-JUL-00:10 | 13.17 | 12.61 |
August | 0.514957E+10 | 6178.65 | 01-AUG-14:20 | 19.60 | 14.30 | 0.00 | 0.00 | 01-AUG-00:10 | 19.60 | 14.30 |
September | 0.184576E+10 | 3290.37 | 08-SEP-05:10 | 1.60 | 0.93 | 0.00 | 0.00 | 01-SEP-00:10 | 1.60 | 0.93 |
October | 0.365253E+09 | 11699.30 | 30-OCT-03:01 | -13.5 | -14.2 | 0.00 | 0.00 | 01-OCT-00:10 | -13.5 | -14.2 |
November | 0.210094E+09 | 11049.35 | 20-NOV-04:01 | -19.4 | -19.7 | 0.00 | 0.00 | 01-NOV-00:10 | -19.4 | -19.7 |
December | 0.248250E+09 | 11978.76 | 15-DEC-04:11 | -32.6 | -32.7 | 0.00 | 0.00 | 01-DEC-00:10 | -32.6 | -32.7 |
Annual Sum or Average | 0.264966E+11 | 0.00 | ||||||||
Minimum of Months | 0.203854E+09 | 3290.37 | -33.2 | -33.3 | 0.00 | 0.00 | -33.2 | -33.3 | ||
Maximum of Months | 0.630427E+10 | 12342.40 | 20.37 | 14.30 | 0.00 | 0.00 | 20.37 | 14.30 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 1204595.65 | 515.77 | 22-MAR-16:40 | 5.60 | 2.04 | 0.00 | 0.00 | 01-MAR-00:10 | 5.60 | 2.04 |
April | 0.120372E+10 | 7640.86 | 20-APR-15:40 | 13.50 | 5.99 | 0.00 | 0.00 | 01-APR-00:10 | 13.50 | 5.99 |
May | 0.477662E+10 | 13017.96 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.847552E+10 | 14290.14 | 29-JUN-14:30 | 25.85 | 16.16 | 0.00 | 0.00 | 01-JUN-00:10 | 25.85 | 16.16 |
July | 0.821415E+10 | 14755.46 | 21-JUL-14:40 | 27.23 | 14.65 | 0.00 | 0.00 | 01-JUL-00:10 | 27.23 | 14.65 |
August | 0.534774E+10 | 12214.44 | 10-AUG-15:50 | 22.70 | 12.11 | 0.00 | 0.00 | 01-AUG-00:10 | 22.70 | 12.11 |
September | 0.643662E+09 | 5174.45 | 07-SEP-15:20 | 16.47 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.47 | 8.91 |
October | 39599.33 | 66.00 | 03-OCT-16:30 | 11.40 | 5.76 | 0.00 | 0.00 | 01-OCT-00:10 | 11.40 | 5.76 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.286627E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.847552E+10 | 14755.46 | 27.23 | 16.16 | 0.00 | 0.00 | 27.23 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137975E+10 | 1208.75 | 23-JAN-15:20 | -10.4 | -10.8 | 95130281.99 | 126.82 | 02-JAN-10:50 | -10.4 | -10.8 |
February | 0.671265E+10 | 3610.49 | 15-FEB-16:20 | -7.4 | -8.8 | 86396458.20 | 126.82 | 22-FEB-14:09 | -17.6 | -18.3 |
March | 0.135830E+11 | 6857.34 | 31-MAR-24:00 | -11.8 | -13.4 | 0.103236E+09 | 126.82 | 16-MAR-13:09 | -11.8 | -13.4 |
April | 0.189157E+11 | 8638.95 | 20-APR-19:00 | 11.10 | 4.63 | 91604981.37 | 126.82 | 07-APR-13:09 | 11.10 | 4.63 |
May | 0.479177E+10 | 3570.12 | 31-MAY-24:00 | 12.40 | 8.53 | 99233128.28 | 126.82 | 17-MAY-09:00 | 12.40 | 8.53 |
June | 0.967064E+10 | 5481.03 | 30-JUN-24:00 | 15.10 | 14.10 | 98962164.42 | 126.85 | 27-JUN-09:09 | 15.10 | 14.10 |
July | 0.150989E+11 | 7437.48 | 31-JUL-23:53 | 16.60 | 11.46 | 91885820.10 | 126.84 | 25-JUL-09:09 | 16.60 | 11.46 |
August | 0.200329E+11 | 8678.63 | 27-AUG-18:57 | 19.40 | 11.72 | 0.103238E+09 | 126.83 | 04-AUG-09:09 | 19.40 | 11.72 |
September | 0.431071E+10 | 3066.82 | 30-SEP-24:00 | 1.30 | -0.1 | 91606694.70 | 126.83 | 05-SEP-13:00 | 1.30 | -0.1 |
October | 0.861147E+10 | 4630.63 | 31-OCT-24:00 | -10.1 | -11.0 | 95230016.32 | 126.82 | 27-OCT-13:09 | -10.1 | -11.0 |
November | 0.123573E+11 | 5594.98 | 08-NOV-15:50 | -15.7 | -16.1 | 94300247.60 | 126.82 | 02-NOV-13:09 | -15.7 | -16.1 |
December | 0.177064E+11 | 7107.21 | 26-DEC-17:00 | -15.6 | -15.9 | 91880855.29 | 126.82 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.133171E+12 | 0.114271E+10 | ||||||||
Minimum of Months | 0.137975E+10 | 1208.75 | -15.7 | -16.1 | 86396458.20 | 126.82 | -23.9 | -24.1 | ||
Maximum of Months | 0.200329E+11 | 8678.63 | 19.40 | 14.10 | 0.103238E+09 | 126.85 | 19.40 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374318E+09 | 646.96 | 12-JAN-10:00 | -38.3 | -38.4 | 87476693.19 | 126.82 | 20-JAN-14:09 | -9.3 | -9.5 |
February | 0.394359E+10 | 3091.32 | 16-FEB-16:20 | -4.8 | -7.1 | 86396470.55 | 126.82 | 22-FEB-14:09 | -17.6 | -18.3 |
March | 0.108493E+11 | 6048.27 | 31-MAR-23:20 | -12.1 | -13.7 | 0.103236E+09 | 126.82 | 16-MAR-13:09 | -12.1 | -13.7 |
April | 0.171215E+11 | 8265.16 | 20-APR-19:00 | 11.10 | 4.63 | 91605019.72 | 126.82 | 07-APR-13:09 | 11.10 | 4.63 |
May | 0.389935E+10 | 3248.96 | 31-MAY-24:00 | 12.40 | 8.53 | 99233130.71 | 126.82 | 17-MAY-09:00 | 12.40 | 8.53 |
June | 0.882895E+10 | 5126.15 | 30-JUN-24:00 | 15.10 | 14.10 | 98961987.44 | 126.84 | 27-JUN-13:00 | 15.10 | 14.10 |
July | 0.139709E+11 | 7038.76 | 31-JUL-23:40 | 17.10 | 11.88 | 91886323.97 | 126.84 | 25-JUL-13:00 | 17.10 | 11.88 |
August | 0.186072E+11 | 7906.41 | 27-AUG-18:50 | 19.60 | 11.80 | 0.103239E+09 | 126.83 | 04-AUG-09:09 | 19.60 | 11.80 |
September | 0.299022E+10 | 2406.26 | 30-SEP-23:40 | 1.03 | -0.5 | 91606502.67 | 126.83 | 05-SEP-13:00 | 1.03 | -0.5 |
October | 0.615688E+10 | 3485.24 | 03-OCT-16:00 | 11.70 | 6.37 | 95230025.88 | 126.82 | 27-OCT-13:09 | -11.7 | -12.7 |
November | 0.874481E+10 | 4851.77 | 08-NOV-16:00 | -16.1 | -16.4 | 94300260.07 | 126.82 | 02-NOV-13:09 | -16.1 | -16.4 |
December | 0.134228E+11 | 5891.59 | 21-DEC-17:00 | -16.7 | -17.3 | 91880862.46 | 126.82 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.108910E+12 | 0.113505E+10 | ||||||||
Minimum of Months | 0.374318E+09 | 646.96 | -38.3 | -38.4 | 86396470.55 | 126.82 | -23.9 | -24.1 | ||
Maximum of Months | 0.186072E+11 | 8265.16 | 19.60 | 14.10 | 0.103239E+09 | 126.84 | 19.60 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325809E+09 | 626.64 | 12-JAN-08:15 | -38.1 | -38.2 | 78799018.12 | 121.61 | 19-JAN-14:00 | -6.1 | -6.7 |
February | 0.219887E+10 | 2582.88 | 09-FEB-16:10 | 0.13 | -0.8 | 86317303.39 | 126.82 | 22-FEB-14:09 | -17.6 | -18.3 |
March | 0.851073E+10 | 5300.02 | 31-MAR-17:40 | -9.4 | -11.7 | 0.103236E+09 | 126.82 | 16-MAR-13:09 | -9.4 | -11.7 |
April | 0.156256E+11 | 8253.38 | 20-APR-19:00 | 11.10 | 4.63 | 91605037.72 | 126.82 | 07-APR-13:09 | 11.10 | 4.63 |
May | 0.335687E+10 | 3181.57 | 31-MAY-23:50 | 12.63 | 8.49 | 99233188.19 | 126.82 | 17-MAY-09:00 | 12.63 | 8.49 |
June | 0.868156E+10 | 5082.49 | 30-JUN-23:40 | 15.53 | 12.93 | 98962021.55 | 126.84 | 27-JUN-13:00 | 15.53 | 12.93 |
July | 0.138475E+11 | 6998.40 | 31-JUL-23:15 | 17.60 | 12.30 | 91886403.71 | 126.84 | 25-JUL-13:00 | 17.60 | 12.30 |
August | 0.182927E+11 | 7953.47 | 27-AUG-18:31 | 19.80 | 11.87 | 0.103239E+09 | 126.83 | 04-AUG-09:09 | 19.80 | 11.87 |
September | 0.173804E+10 | 2115.07 | 02-SEP-18:10 | 16.52 | 10.34 | 91421173.87 | 126.83 | 05-SEP-13:00 | 8.90 | 7.75 |
October | 0.370724E+10 | 3289.25 | 03-OCT-16:00 | 11.70 | 6.37 | 95230033.75 | 126.82 | 27-OCT-13:09 | -11.7 | -12.7 |
November | 0.643350E+10 | 4304.98 | 08-NOV-16:00 | -16.1 | -16.4 | 94300265.27 | 126.82 | 02-NOV-13:09 | -16.1 | -16.4 |
December | 0.112904E+11 | 5380.58 | 29-DEC-17:00 | -14.4 | -14.8 | 91880864.61 | 126.82 | 27-DEC-14:09 | -14.4 | -14.8 |
Annual Sum or Average | 0.940088E+11 | 0.112611E+10 | ||||||||
Minimum of Months | 0.325809E+09 | 626.64 | -38.1 | -38.2 | 78799018.12 | 121.61 | -17.6 | -18.3 | ||
Maximum of Months | 0.182927E+11 | 8253.38 | 19.80 | 12.93 | 0.103239E+09 | 126.84 | 19.80 | 12.93 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231325E+12 | 89521.96 | 20-JAN-17:00 | -11.1 | -11.2 | 0.206146E+10 | 2745.34 | 27-JAN-10:09 | -11.7 | -12.0 |
February | 0.430155E+12 | 181434.87 | 09-FEB-17:00 | -2.2 | -2.6 | 0.187028E+10 | 2745.40 | 14-FEB-14:39 | -1.7 | -3.4 |
March | 0.725262E+12 | 357795.21 | 31-MAR-24:00 | -11.8 | -13.4 | 0.223479E+10 | 2745.60 | 02-MAR-10:00 | -11.8 | -13.4 |
April | 0.942467E+12 | 367589.58 | 20-APR-16:00 | 13.30 | 5.81 | 0.198299E+10 | 2745.47 | 10-APR-09:00 | 13.30 | 5.81 |
May | 0.243618E+12 | 177114.40 | 31-MAY-24:00 | 12.40 | 8.53 | 0.214812E+10 | 2745.34 | 19-MAY-09:09 | 12.40 | 8.53 |
June | 0.473711E+12 | 269039.31 | 30-JUN-24:00 | 15.10 | 14.10 | 0.214225E+10 | 2747.80 | 29-JUN-13:00 | 15.10 | 14.10 |
July | 0.736478E+12 | 361897.05 | 31-JUL-23:53 | 16.60 | 11.46 | 0.199002E+10 | 2750.58 | 14-JUL-13:09 | 16.60 | 11.46 |
August | 0.982752E+12 | 370167.01 | 11-AUG-16:00 | 25.60 | 14.77 | 0.223627E+10 | 2751.55 | 03-AUG-13:09 | 25.60 | 14.77 |
September | 0.237619E+12 | 175300.85 | 30-SEP-24:00 | 1.30 | -0.1 | 0.198300E+10 | 2745.34 | 25-SEP-09:00 | 1.30 | -0.1 |
October | 0.484415E+12 | 266143.49 | 31-OCT-24:00 | -10.1 | -11.0 | 0.206150E+10 | 2745.40 | 30-OCT-13:00 | -10.1 | -11.0 |
November | 0.702213E+12 | 274025.46 | 03-NOV-16:00 | -11.1 | -11.5 | 0.204136E+10 | 2745.50 | 30-NOV-10:09 | -28.4 | -28.6 |
December | 0.969855E+12 | 365521.50 | 26-DEC-17:00 | -15.6 | -15.9 | 0.198898E+10 | 2745.51 | 15-DEC-10:09 | -15.6 | -15.9 |
Annual Sum or Average | 0.715987E+13 | 0.247410E+11 | ||||||||
Minimum of Months | 0.231325E+12 | 89521.96 | -15.6 | -15.9 | 0.187028E+10 | 2745.34 | -28.4 | -28.6 | ||
Maximum of Months | 0.982752E+12 | 370167.01 | 25.60 | 14.77 | 0.223627E+10 | 2751.55 | 25.60 | 14.77 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 249873.22 | 416.46 | 23-MAR-06:30 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 249873.22 | |||
Minimum of Months | 0.00 | 0.00 | -25.8 | |
Maximum of Months | 249873.22 | 416.46 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164654E+10 | 53004.70 | 02-JAN-04:01 | -15.1 |
February | 0.271646E+09 | 44479.94 | 27-FEB-05:01 | -36.1 |
March | 6586290.31 | 38537.91 | 01-MAR-06:03 | -28.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 3453148.60 | 38607.45 | 30-OCT-05:01 | -14.5 |
November | 0.295734E+09 | 44444.47 | 27-NOV-05:01 | -25.8 |
December | 0.624755E+09 | 44857.26 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.284872E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.164654E+10 | 53004.70 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142504E+11 | 75728.42 | 30-JAN-04:11 | -25.2 |
February | 0.876101E+10 | 75149.47 | 27-FEB-03:22 | -34.7 |
March | 0.439102E+10 | 73119.05 | 06-MAR-04:01 | -20.0 |
April | 0.867938E+09 | 69433.88 | 03-APR-03:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 70613898.07 | 60507.17 | 25-SEP-05:02 | -1.2 |
October | 0.317285E+10 | 73468.66 | 30-OCT-03:01 | -13.5 |
November | 0.109090E+11 | 75052.17 | 13-NOV-04:11 | -20.2 |
December | 0.132753E+11 | 74813.32 | 26-DEC-04:01 | -12.7 |
Annual Sum or Average | 0.556982E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.142504E+11 | 75728.42 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183591E+10 | 12717.13 | 30-JAN-04:01 | -25.1 |
February | 0.739113E+09 | 12407.73 | 27-FEB-05:01 | -36.1 |
March | 0.222472E+09 | 11901.27 | 01-MAR-05:01 | -28.3 |
April | 2506494.60 | 8987.51 | 03-APR-05:02 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 32693071.06 | 11214.98 | 31-OCT-05:01 | -18.2 |
November | 0.545276E+09 | 11890.35 | 27-NOV-05:01 | -25.8 |
December | 0.997108E+09 | 11864.62 | 15-DEC-05:01 | -33.2 |
Annual Sum or Average | 0.437508E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.183591E+10 | 12717.13 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148246E+10 | 14522.43 | 30-JAN-04:01 | -25.1 |
February | 0.575357E+09 | 13817.80 | 27-FEB-05:01 | -36.1 |
March | 0.173869E+09 | 13346.22 | 01-MAR-05:01 | -28.3 |
April | 3655850.53 | 8687.55 | 03-APR-05:02 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 39822668.20 | 12039.83 | 30-OCT-05:01 | -14.5 |
November | 0.694215E+09 | 13597.80 | 27-NOV-05:01 | -25.8 |
December | 0.133110E+10 | 13638.92 | 15-DEC-05:01 | -33.2 |
Annual Sum or Average | 0.430048E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.148246E+10 | 14522.43 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277346E+10 | 24292.27 | 30-JAN-04:01 | -25.1 |
February | 0.959878E+09 | 23100.36 | 27-FEB-04:01 | -34.7 |
March | 0.282648E+09 | 21205.65 | 01-MAR-05:01 | -28.3 |
April | 7915427.90 | 16315.37 | 03-APR-05:02 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.118475E+09 | 21043.10 | 30-OCT-04:01 | -14.4 |
November | 0.120391E+10 | 22419.34 | 27-NOV-05:01 | -25.8 |
December | 0.238880E+10 | 22330.93 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.773509E+10 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.277346E+10 | 24292.27 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421851E+09 | 11832.00 | 30-JAN-05:01 | -25.6 |
February | 54884155.99 | 10844.55 | 27-FEB-05:01 | -36.1 |
March | 4999155.21 | 8288.18 | 01-MAR-06:03 | -28.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 3860934.66 | 8983.49 | 29-NOV-06:01 | -28.9 |
December | 478520.77 | 3243.16 | 06-DEC-06:01 | -28.7 |
Annual Sum or Average | 0.486074E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.421851E+09 | 11832.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908257E+10 | 13623.86 | 01-JAN-20:42 | -14.9 |
February | 0.531357E+10 | 13437.06 | 27-FEB-03:22 | -34.7 |
March | 0.278680E+10 | 12800.61 | 06-MAR-04:01 | -20.0 |
April | 0.368812E+09 | 12447.41 | 03-APR-03:02 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 22511543.32 | 10291.51 | 30-SEP-05:03 | -4.5 |
October | 0.149104E+10 | 12892.23 | 30-OCT-03:01 | -13.5 |
November | 0.648631E+10 | 13182.84 | 26-NOV-20:22 | -25.3 |
December | 0.886676E+10 | 13236.71 | 11-DEC-02:42 | -21.0 |
Annual Sum or Average | 0.344184E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.908257E+10 | 13623.86 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583365E+10 | 19657.49 | 01-JAN-20:42 | -14.9 |
February | 0.290977E+10 | 19499.08 | 27-FEB-03:22 | -34.7 |
March | 0.110328E+10 | 18467.58 | 01-MAR-04:01 | -27.9 |
April | 0.137489E+09 | 16718.91 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 9030842.87 | 7023.62 | 30-SEP-05:03 | -4.5 |
October | 0.783383E+09 | 18837.50 | 30-OCT-03:01 | -13.5 |
November | 0.409955E+10 | 19230.33 | 13-NOV-04:11 | -20.2 |
December | 0.576828E+10 | 19237.37 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.206444E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.583365E+10 | 19657.49 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771543E+10 | 29414.69 | 01-JAN-20:42 | -14.9 |
February | 0.297683E+10 | 28782.27 | 27-FEB-04:01 | -34.7 |
March | 0.110692E+10 | 27317.17 | 01-MAR-04:01 | -27.9 |
April | 99737196.79 | 24179.07 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 4352669.12 | 4673.48 | 30-SEP-05:03 | -4.5 |
October | 0.748924E+09 | 27587.84 | 30-OCT-03:01 | -13.5 |
November | 0.464530E+10 | 28649.14 | 13-NOV-04:11 | -20.2 |
December | 0.837418E+10 | 28790.73 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.256717E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.837418E+10 | 29414.69 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517531E+10 | 19107.76 | 30-JAN-04:01 | -25.1 |
February | 0.249282E+10 | 18818.81 | 27-FEB-04:01 | -34.7 |
March | 0.104073E+10 | 17877.62 | 01-MAR-04:01 | -27.9 |
April | 66031059.84 | 15646.35 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 4259703.98 | 5656.61 | 30-SEP-05:03 | -4.5 |
October | 0.662676E+09 | 17817.06 | 30-OCT-03:01 | -13.5 |
November | 0.318576E+10 | 18617.96 | 13-NOV-04:11 | -20.2 |
December | 0.470756E+10 | 18608.67 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.173352E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.517531E+10 | 19107.76 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156356E+11 | 16463.16 | 30-JAN-04:11 | -25.2 |
February | 0.116516E+11 | 16204.99 | 27-FEB-03:22 | -34.7 |
March | 0.789930E+10 | 15499.46 | 06-MAR-03:53 | -20.0 |
April | 0.198299E+10 | 15378.64 | 03-APR-02:32 | -20.4 |
May | 3656336.08 | 11622.15 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 16179055.30 | 11962.72 | 31-AUG-05:02 | -1.2 |
September | 0.593952E+09 | 13323.90 | 30-SEP-04:01 | -4.0 |
October | 0.566519E+10 | 15533.60 | 22-OCT-21:03 | -15.2 |
November | 0.136331E+11 | 15915.74 | 26-NOV-20:22 | -25.3 |
December | 0.160164E+11 | 15879.70 | 11-DEC-02:42 | -21.0 |
Annual Sum or Average | 0.730981E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.160164E+11 | 16463.16 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104609E+11 | 23076.23 | 30-JAN-04:11 | -25.2 |
February | 0.681910E+10 | 22392.10 | 27-FEB-03:22 | -34.7 |
March | 0.333980E+10 | 21227.22 | 01-MAR-04:11 | -28.0 |
April | 0.797010E+09 | 21314.40 | 03-APR-03:11 | -21.1 |
May | 816873.88 | 5445.83 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 6097512.51 | 8639.30 | 30-AUG-05:02 | 0.00 |
September | 0.249740E+09 | 18510.22 | 30-SEP-04:01 | -4.0 |
October | 0.306630E+10 | 21352.35 | 23-OCT-03:01 | -11.6 |
November | 0.902518E+10 | 21921.17 | 26-NOV-20:22 | -25.3 |
December | 0.109131E+11 | 21882.09 | 11-DEC-02:42 | -21.0 |
Annual Sum or Average | 0.446780E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.109131E+11 | 23076.23 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140929E+11 | 35676.60 | 30-JAN-04:11 | -25.2 |
February | 0.769407E+10 | 34293.69 | 27-FEB-03:22 | -34.7 |
March | 0.396000E+10 | 32717.12 | 01-MAR-04:11 | -28.0 |
April | 0.889196E+09 | 32395.86 | 03-APR-03:11 | -21.1 |
May | 4044987.38 | 10929.09 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 3061950.07 | 10132.61 | 30-AUG-05:02 | 0.00 |
September | 0.302789E+09 | 28580.63 | 25-SEP-04:01 | -1.1 |
October | 0.359296E+10 | 32690.28 | 23-OCT-03:01 | -11.6 |
November | 0.110882E+11 | 33849.04 | 13-NOV-04:11 | -20.2 |
December | 0.156488E+11 | 33853.84 | 11-DEC-02:42 | -21.0 |
Annual Sum or Average | 0.572761E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.156488E+11 | 35676.60 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942929E+10 | 23978.50 | 30-JAN-04:11 | -25.2 |
February | 0.578524E+10 | 23006.41 | 27-FEB-03:22 | -34.7 |
March | 0.319671E+10 | 21936.50 | 01-MAR-04:11 | -28.0 |
April | 0.506733E+09 | 21659.42 | 03-APR-03:11 | -21.1 |
May | 1415232.56 | 5746.22 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 539654.19 | 3228.53 | 30-AUG-05:02 | 0.00 |
September | 0.186848E+09 | 19138.81 | 25-SEP-04:01 | -1.1 |
October | 0.249338E+10 | 22091.97 | 23-OCT-03:01 | -11.6 |
November | 0.693959E+10 | 22513.80 | 13-NOV-04:11 | -20.2 |
December | 0.862388E+10 | 22465.05 | 04-DEC-04:11 | -20.0 |
Annual Sum or Average | 0.371636E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.942929E+10 | 23978.50 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267191E+10 | 6461.67 | 20-JAN-06:01 | -7.6 |
February | 0.145530E+10 | 9300.63 | 09-FEB-06:03 | 0.00 |
March | 0.658514E+09 | 11341.48 | 26-MAR-15:02 | -8.4 |
April | 0.229594E+09 | 12222.56 | 09-APR-15:22 | 3.90 |
May | 0.209483E+09 | 12016.48 | 21-MAY-13:51 | 15.60 |
June | 0.298678E+09 | 10930.78 | 11-JUN-16:31 | 18.90 |
July | 0.309948E+09 | 11840.58 | 23-JUL-12:12 | 24.27 |
August | 0.315819E+09 | 11960.19 | 27-AUG-15:22 | 20.85 |
September | 0.227495E+09 | 10868.04 | 22-SEP-04:12 | 3.30 |
October | 0.312577E+09 | 9975.25 | 11-OCT-03:02 | -5.6 |
November | 0.151197E+10 | 8579.03 | 02-NOV-05:01 | -11.0 |
December | 0.222872E+10 | 5543.60 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.104300E+11 | |||
Minimum of Months | 0.209483E+09 | 5543.60 | -12.2 | |
Maximum of Months | 0.267191E+10 | 12222.56 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574752E+10 | 21963.27 | 02-JAN-06:13 | -15.2 |
February | 0.332720E+10 | 10851.23 | 27-FEB-06:12 | -35.7 |
March | 0.271643E+10 | 16279.08 | 12-MAR-13:32 | -7.6 |
April | 0.616213E+09 | 15181.26 | 02-APR-13:22 | -7.2 |
May | 0.116199E+09 | 14955.90 | 28-MAY-15:52 | 16.10 |
June | 70566454.88 | 11959.38 | 11-JUN-16:21 | 18.90 |
July | 82176918.03 | 14855.37 | 23-JUL-14:21 | 25.30 |
August | 54038262.70 | 12379.26 | 27-AUG-15:42 | 20.68 |
September | 0.109649E+09 | 12358.72 | 10-SEP-11:02 | 14.60 |
October | 0.134786E+10 | 6897.24 | 22-OCT-13:33 | -11.5 |
November | 0.384420E+10 | 9337.46 | 27-NOV-06:15 | -26.7 |
December | 0.489510E+10 | 12606.19 | 04-DEC-06:13 | -19.4 |
Annual Sum or Average | 0.229272E+11 | |||
Minimum of Months | 54038262.70 | 6897.24 | -35.7 | |
Maximum of Months | 0.574752E+10 | 21963.27 | 25.30 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212318E+11 | 35794.97 | 13-JAN-06:13 | -33.3 |
February | 0.156623E+11 | 36283.30 | 27-FEB-05:33 | -36.1 |
March | 0.116086E+11 | 32102.95 | 06-MAR-05:22 | -20.6 |
April | 0.379404E+10 | 27767.09 | 03-APR-05:02 | -21.2 |
May | 0.656731E+09 | 17651.26 | 10-MAY-05:02 | 5.28 |
June | 0.149919E+09 | 16938.27 | 08-JUN-04:12 | 8.30 |
July | 0.138183E+09 | 16147.81 | 07-JUL-04:12 | 13.87 |
August | 0.451085E+09 | 13217.96 | 10-AUG-05:02 | 10.10 |
September | 0.234732E+10 | 14081.35 | 10-SEP-10:52 | 14.40 |
October | 0.857054E+10 | 30966.63 | 30-OCT-04:12 | -14.4 |
November | 0.189366E+11 | 35274.03 | 27-NOV-05:12 | -26.0 |
December | 0.223180E+11 | 33179.73 | 15-DEC-05:12 | -33.1 |
Annual Sum or Average | 0.105865E+12 | |||
Minimum of Months | 0.138183E+09 | 13217.96 | -36.1 | |
Maximum of Months | 0.223180E+11 | 36283.30 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31708120.45 | 480.58 | 29-JAN-22:12 | -24.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 31708120.45 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 31708120.45 | 480.58 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.717021E+09 | 576.00 | 12-JAN-22:13 | -36.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.717021E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.717021E+09 | 576.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770578E+09 | 596.27 | 10-JAN-00:20 | -18.3 |
February | 0.253167E+09 | 585.50 | 26-FEB-18:30 | -26.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 1455907.31 | 425.98 | 28-MAY-07:47 | 5.82 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 96834405.64 | 569.80 | 25-SEP-03:45 | -1.0 |
October | 72930249.68 | 560.75 | 22-OCT-22:50 | -15.7 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.119497E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.770578E+09 | 596.27 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144187E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.107363E+10 | 1662.56 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.100147E+10 | 1662.56 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.780383E+09 | 914.68 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.820532E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.803306E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.759390E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.869339E+09 | 855.70 | 18-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.847352E+09 | 1569.89 | 28-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.105471E+10 | 1662.56 | 03-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133426E+10 | 1662.56 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.147021E+10 | 1662.56 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.122564E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.759390E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.147021E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.900118E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.668817E+09 | 1071.42 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.636660E+09 | 1071.42 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.503699E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.536265E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.524021E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.495433E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.564813E+09 | 553.10 | 18-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.542933E+09 | 882.65 | 28-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.665162E+09 | 1071.42 | 03-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.823296E+09 | 1071.42 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.936640E+09 | 1071.42 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.779786E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.495433E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.936640E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134454E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.995059E+09 | 1662.60 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.974582E+09 | 1662.60 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.784262E+09 | 914.33 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.829526E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.811752E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.766721E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.873288E+09 | 791.06 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.835919E+09 | 1496.05 | 28-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.100658E+10 | 1662.60 | 03-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.121441E+10 | 1662.60 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140991E+10 | 1662.60 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.118466E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.766721E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140991E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.907216E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.658731E+09 | 1071.42 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.634293E+09 | 1071.42 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.505463E+09 | 729.94 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.527182E+09 | 509.78 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.517432E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.488622E+09 | 548.88 | 25-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.557728E+09 | 549.11 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.541304E+09 | 1014.18 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.659774E+09 | 1071.42 | 03-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.822167E+09 | 1071.42 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.941317E+09 | 1071.42 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.776123E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.488622E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.941317E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144069E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.106967E+10 | 1662.56 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.999411E+09 | 1662.56 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.779544E+09 | 908.69 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.819748E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.803325E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.759040E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.868774E+09 | 846.04 | 18-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.845566E+09 | 1568.41 | 28-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.105021E+10 | 1662.56 | 03-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133184E+10 | 1662.56 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.146988E+10 | 1662.56 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.122377E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.759040E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.146988E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.898838E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.667411E+09 | 1071.42 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.635935E+09 | 1071.42 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.503422E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.535884E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.523672E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.495060E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.564438E+09 | 547.26 | 18-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.542250E+09 | 879.99 | 28-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.663714E+09 | 1071.42 | 03-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.819878E+09 | 1071.42 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.936034E+09 | 1071.42 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.778654E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.495060E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.936034E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134555E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.994080E+09 | 1662.60 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.973988E+09 | 1662.60 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.783532E+09 | 908.31 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.829029E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.811385E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.766326E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.872780E+09 | 791.06 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.835022E+09 | 1492.48 | 28-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.100549E+10 | 1662.60 | 03-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.121389E+10 | 1662.60 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.141322E+10 | 1662.60 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.118443E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.766326E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.141322E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905774E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.657262E+09 | 1071.42 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.633842E+09 | 1071.42 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.505039E+09 | 720.84 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.527259E+09 | 509.78 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.517349E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.488481E+09 | 542.78 | 25-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.557348E+09 | 543.06 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540378E+09 | 1013.50 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.658343E+09 | 1071.42 | 03-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.819867E+09 | 1071.42 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.940764E+09 | 1071.42 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.775171E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.488481E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.940764E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144051E+10 | 1662.56 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.106934E+10 | 1662.56 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.999251E+09 | 1662.56 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.779510E+09 | 908.45 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.819734E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.803320E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.759030E+09 | 791.05 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.868756E+09 | 845.66 | 18-AUG-15:00 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.845523E+09 | 1568.37 | 28-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.105007E+10 | 1662.56 | 03-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133167E+10 | 1662.56 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.146984E+10 | 1662.56 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.122366E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.759030E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.146984E+10 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.898765E+09 | 1071.42 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.667354E+09 | 1071.42 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.635911E+09 | 1071.42 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.503397E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.535874E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.523662E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.495046E+09 | 509.78 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.564418E+09 | 547.03 | 18-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.542231E+09 | 880.23 | 28-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.663653E+09 | 1071.42 | 03-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.819811E+09 | 1071.42 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.936002E+09 | 1071.42 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.778612E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.495046E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.936002E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134548E+10 | 1662.60 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.994055E+09 | 1662.60 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.973963E+09 | 1662.60 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.783513E+09 | 908.07 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.829015E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.811367E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.766309E+09 | 791.06 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.872752E+09 | 791.06 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.834995E+09 | 1492.44 | 28-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.100545E+10 | 1662.60 | 03-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.121385E+10 | 1662.60 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.141320E+10 | 1662.60 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.118439E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.766309E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.141320E+10 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905708E+09 | 1071.42 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.657153E+09 | 1071.42 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.633803E+09 | 1071.42 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.505023E+09 | 720.20 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.527256E+09 | 509.78 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.517339E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.488477E+09 | 542.55 | 25-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.557335E+09 | 542.82 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540335E+09 | 1013.48 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.658261E+09 | 1071.42 | 03-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.819779E+09 | 1071.42 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.940734E+09 | 1071.42 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.775120E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.488477E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.940734E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144187E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355669E+09 |
February | 0.136985E+10 | 0.107363E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289495E+09 |
March | 0.163685E+10 | 0.100147E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442866E+09 |
April | 0.145243E+10 | 0.780383E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509170E+09 |
May | 0.157338E+10 | 0.820532E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309408E+09 |
June | 0.156900E+10 | 0.803306E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358794.23 | 0.181668E+09 |
July | 0.145680E+10 | 0.759390E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 956229.84 | 0.132943E+09 |
August | 0.163685E+10 | 0.869339E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163052.00 | 0.158797E+09 |
September | 0.145243E+10 | 0.847352E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194207E+09 |
October | 0.150991E+10 | 0.105471E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400443E+09 |
November | 0.149516E+10 | 0.133426E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135448E+09 |
December | 0.145680E+10 | 0.147021E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265582E+09 |
Annual Sum or Average | 0.181194E+11 | 0.122564E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1478076.06 | 0.337570E+10 |
Minimum of Months | 0.136985E+10 | 0.759390E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132943E+09 |
Maximum of Months | 0.163685E+10 | 0.147021E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 956229.84 | 0.509170E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.900118E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235637E+09 |
February | 0.882782E+09 | 0.668817E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192477E+09 |
March | 0.105485E+10 | 0.636660E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297049E+09 |
April | 0.936002E+09 | 0.503699E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341580E+09 |
May | 0.101394E+10 | 0.536265E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208976E+09 |
June | 0.101113E+10 | 0.524021E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238544.85 | 0.120893E+09 |
July | 0.938820E+09 | 0.495433E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 623018.25 | 88514828.60 |
August | 0.105485E+10 | 0.564813E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108004.26 | 0.105489E+09 |
September | 0.936002E+09 | 0.542933E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131318E+09 |
October | 0.973041E+09 | 0.665162E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266803E+09 |
November | 0.963541E+09 | 0.823296E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89216858.21 |
December | 0.938820E+09 | 0.936640E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174493E+09 |
Annual Sum or Average | 0.116768E+11 | 0.779786E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 969567.35 | 0.225245E+10 |
Minimum of Months | 0.882782E+09 | 0.495433E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88514828.60 |
Maximum of Months | 0.105485E+10 | 0.936640E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 623018.25 | 0.341580E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.134454E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349149E+09 |
February | 0.136988E+10 | 0.995059E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289246E+09 |
March | 0.163688E+10 | 0.974582E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448039E+09 |
April | 0.145246E+10 | 0.784262E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521936E+09 |
May | 0.157341E+10 | 0.829526E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310165E+09 |
June | 0.156904E+10 | 0.811752E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352994.36 | 0.179255E+09 |
July | 0.145684E+10 | 0.766721E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 909076.69 | 0.132788E+09 |
August | 0.163688E+10 | 0.873288E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154499.53 | 0.159568E+09 |
September | 0.145246E+10 | 0.835919E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194180E+09 |
October | 0.150994E+10 | 0.100658E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396060E+09 |
November | 0.149520E+10 | 0.121441E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132905E+09 |
December | 0.145684E+10 | 0.140991E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258226E+09 |
Annual Sum or Average | 0.181198E+11 | 0.118466E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1416570.58 | 0.337152E+10 |
Minimum of Months | 0.136988E+10 | 0.766721E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132788E+09 |
Maximum of Months | 0.163688E+10 | 0.140991E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 909076.69 | 0.521936E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.907216E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242329E+09 |
February | 0.882782E+09 | 0.658731E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200461E+09 |
March | 0.105485E+10 | 0.634293E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314474E+09 |
April | 0.936002E+09 | 0.505463E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372591E+09 |
May | 0.101394E+10 | 0.527182E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211930E+09 |
June | 0.101113E+10 | 0.517432E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 236306.24 | 0.125246E+09 |
July | 0.938820E+09 | 0.488622E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592146.77 | 93455419.70 |
August | 0.105485E+10 | 0.557728E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102839.28 | 0.112463E+09 |
September | 0.936002E+09 | 0.541304E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131700E+09 |
October | 0.973041E+09 | 0.659774E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280683E+09 |
November | 0.963541E+09 | 0.822167E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95351555.79 |
December | 0.938820E+09 | 0.941317E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187483E+09 |
Annual Sum or Average | 0.116768E+11 | 0.776123E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 931292.29 | 0.236817E+10 |
Minimum of Months | 0.882782E+09 | 0.488622E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93455419.70 |
Maximum of Months | 0.105485E+10 | 0.941317E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592146.77 | 0.372591E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144069E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791391E+09 |
February | 0.136985E+10 | 0.106967E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640067E+09 |
March | 0.163685E+10 | 0.999411E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965464E+09 |
April | 0.145243E+10 | 0.779544E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109321E+10 |
May | 0.157338E+10 | 0.819748E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665919E+09 |
June | 0.156900E+10 | 0.803325E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795966.41 | 0.395347E+09 |
July | 0.145680E+10 | 0.759040E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2628687.82 | 0.292707E+09 |
August | 0.163685E+10 | 0.868774E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351139.57 | 0.343030E+09 |
September | 0.145243E+10 | 0.845566E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405722E+09 |
October | 0.150991E+10 | 0.105021E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848255E+09 |
November | 0.149516E+10 | 0.133184E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294129E+09 |
December | 0.145680E+10 | 0.146988E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576016E+09 |
Annual Sum or Average | 0.181194E+11 | 0.122377E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3775793.80 | 0.731125E+10 |
Minimum of Months | 0.136985E+10 | 0.759040E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292707E+09 |
Maximum of Months | 0.163685E+10 | 0.146988E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2628687.82 | 0.109321E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.898838E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525912E+09 |
February | 0.649041E+09 | 0.667411E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427528E+09 |
March | 0.773965E+09 | 0.635935E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661749E+09 |
April | 0.688021E+09 | 0.503422E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763594E+09 |
May | 0.744847E+09 | 0.535884E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462125E+09 |
June | 0.742030E+09 | 0.523672E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509668.58 | 0.269178E+09 |
July | 0.690839E+09 | 0.495060E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1527205.65 | 0.201372E+09 |
August | 0.773965E+09 | 0.564438E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234078.64 | 0.236528E+09 |
September | 0.688021E+09 | 0.542250E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283887E+09 |
October | 0.715730E+09 | 0.663714E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576730E+09 |
November | 0.708685E+09 | 0.819878E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195297E+09 |
December | 0.690839E+09 | 0.936034E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381642E+09 |
Annual Sum or Average | 0.858171E+10 | 0.778654E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2270952.87 | 0.498554E+10 |
Minimum of Months | 0.649041E+09 | 0.495060E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195297E+09 |
Maximum of Months | 0.773965E+09 | 0.936034E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1527205.65 | 0.763594E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.134555E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794561E+09 |
February | 0.136988E+10 | 0.994080E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655652E+09 |
March | 0.163688E+10 | 0.973988E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102122E+10 |
April | 0.145246E+10 | 0.783532E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119590E+10 |
May | 0.157341E+10 | 0.829029E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698585E+09 |
June | 0.156904E+10 | 0.811385E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795719.92 | 0.403809E+09 |
July | 0.145684E+10 | 0.766326E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2104615.57 | 0.304421E+09 |
August | 0.163688E+10 | 0.872780E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 349558.82 | 0.362733E+09 |
September | 0.145246E+10 | 0.835022E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436397E+09 |
October | 0.150994E+10 | 0.100549E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891584E+09 |
November | 0.149520E+10 | 0.121389E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297452E+09 |
December | 0.145684E+10 | 0.141322E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577106E+09 |
Annual Sum or Average | 0.181198E+11 | 0.118443E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3249894.31 | 0.763942E+10 |
Minimum of Months | 0.136988E+10 | 0.766326E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297452E+09 |
Maximum of Months | 0.163688E+10 | 0.141322E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2104615.57 | 0.119590E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.905774E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530667E+09 |
February | 0.882782E+09 | 0.657262E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431054E+09 |
March | 0.105485E+10 | 0.633842E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663080E+09 |
April | 0.936002E+09 | 0.505039E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795709E+09 |
May | 0.101394E+10 | 0.527259E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473482E+09 |
June | 0.101113E+10 | 0.517349E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530639.68 | 0.277849E+09 |
July | 0.938820E+09 | 0.488481E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1342750.63 | 0.209848E+09 |
August | 0.105485E+10 | 0.557348E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234083.34 | 0.244947E+09 |
September | 0.936002E+09 | 0.540378E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284551E+09 |
October | 0.973041E+09 | 0.658343E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579721E+09 |
November | 0.963541E+09 | 0.819867E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198605E+09 |
December | 0.938820E+09 | 0.940764E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388693E+09 |
Annual Sum or Average | 0.116768E+11 | 0.775171E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2107473.65 | 0.507821E+10 |
Minimum of Months | 0.882782E+09 | 0.488481E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198605E+09 |
Maximum of Months | 0.105485E+10 | 0.940764E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1342750.63 | 0.795709E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144051E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970597E+09 |
February | 0.136985E+10 | 0.106934E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780426E+09 |
March | 0.163685E+10 | 0.999251E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114890E+10 |
April | 0.145243E+10 | 0.779510E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127035E+10 |
May | 0.157338E+10 | 0.819734E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789430E+09 |
June | 0.156900E+10 | 0.803320E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913954.91 | 0.480602E+09 |
July | 0.145680E+10 | 0.759030E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2973748.26 | 0.360063E+09 |
August | 0.163685E+10 | 0.868756E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 376977.11 | 0.411378E+09 |
September | 0.145243E+10 | 0.845523E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459799E+09 |
October | 0.150991E+10 | 0.105007E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977331E+09 |
November | 0.149516E+10 | 0.133167E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357230E+09 |
December | 0.145680E+10 | 0.146984E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703690E+09 |
Annual Sum or Average | 0.181194E+11 | 0.122366E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4264680.28 | 0.870980E+10 |
Minimum of Months | 0.136985E+10 | 0.759030E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357230E+09 |
Maximum of Months | 0.163685E+10 | 0.146984E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2973748.26 | 0.127035E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.898765E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649176E+09 |
February | 0.882782E+09 | 0.667354E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522096E+09 |
March | 0.105485E+10 | 0.635911E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779872E+09 |
April | 0.936002E+09 | 0.503397E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889689E+09 |
May | 0.101394E+10 | 0.535874E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553395E+09 |
June | 0.101113E+10 | 0.523662E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 609293.85 | 0.327843E+09 |
July | 0.938820E+09 | 0.495046E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1747858.96 | 0.248003E+09 |
August | 0.105485E+10 | 0.564418E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251308.47 | 0.285841E+09 |
September | 0.936002E+09 | 0.542231E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326200E+09 |
October | 0.973041E+09 | 0.663653E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661282E+09 |
November | 0.963541E+09 | 0.819811E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238611E+09 |
December | 0.938820E+09 | 0.936002E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470243E+09 |
Annual Sum or Average | 0.116768E+11 | 0.778612E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2608461.27 | 0.595225E+10 |
Minimum of Months | 0.882782E+09 | 0.495046E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238611E+09 |
Maximum of Months | 0.105485E+10 | 0.936002E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1747858.96 | 0.889689E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.134548E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975508E+09 |
February | 0.136988E+10 | 0.994055E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791520E+09 |
March | 0.163688E+10 | 0.973963E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120523E+10 |
April | 0.145246E+10 | 0.783513E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140458E+10 |
May | 0.157341E+10 | 0.829015E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838931E+09 |
June | 0.156904E+10 | 0.811367E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913805.59 | 0.492407E+09 |
July | 0.145684E+10 | 0.766309E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2385578.78 | 0.375409E+09 |
August | 0.163688E+10 | 0.872752E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375471.51 | 0.440639E+09 |
September | 0.145246E+10 | 0.834995E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506061E+09 |
October | 0.150994E+10 | 0.100545E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101954E+10 |
November | 0.149520E+10 | 0.121385E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359273E+09 |
December | 0.145684E+10 | 0.141320E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706101E+09 |
Annual Sum or Average | 0.181198E+11 | 0.118439E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3674855.89 | 0.911519E+10 |
Minimum of Months | 0.136988E+10 | 0.766309E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359273E+09 |
Maximum of Months | 0.163688E+10 | 0.141320E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2385578.78 | 0.140458E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.905708E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651478E+09 |
February | 0.882782E+09 | 0.657153E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525569E+09 |
March | 0.105485E+10 | 0.633803E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787625E+09 |
April | 0.936002E+09 | 0.505023E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937293E+09 |
May | 0.101394E+10 | 0.527256E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571073E+09 |
June | 0.101113E+10 | 0.517339E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 609296.28 | 0.339444E+09 |
July | 0.938820E+09 | 0.488477E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1558540.28 | 0.258793E+09 |
August | 0.105485E+10 | 0.557335E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251309.06 | 0.297603E+09 |
September | 0.936002E+09 | 0.540335E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330655E+09 |
October | 0.973041E+09 | 0.658261E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672823E+09 |
November | 0.963541E+09 | 0.819779E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240390E+09 |
December | 0.938820E+09 | 0.940734E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473031E+09 |
Annual Sum or Average | 0.116768E+11 | 0.775120E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2419145.61 | 0.608578E+10 |
Minimum of Months | 0.882782E+09 | 0.488477E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240390E+09 |
Maximum of Months | 0.105485E+10 | 0.940734E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1558540.28 | 0.937293E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750976E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612788E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937961E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107184E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633839E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375381.52 | 0.369274E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326166.28 | 0.274099E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78850.85 | 0.332158E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402508E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844701E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287062E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558362E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1780398.64 | 0.707557E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274099E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326166.28 | 0.107184E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127236E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104921E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162004E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185639E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108717E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723617.09 | 0.624871E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3005221.33 | 0.459361E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187195.04 | 0.563471E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685302E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144240E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487771E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936293E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3916033.46 | 0.120846E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459361E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3005221.33 | 0.185639E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138637E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113236E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172323E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198272E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121717E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453077.32 | 0.727537E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2099397.01 | 0.545512E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41109.62 | 0.638778E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718916E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146637E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515893E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101084E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2593583.95 | 0.130657E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515893E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2099397.01 | 0.198272E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1566.18 | 28-JAN-23:53 |
February | 2010.79 | 01-FEB-10:09 | 1662.56 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 950.85 | 25-FEB-00:53 |
March | 2010.79 | 01-MAR-10:09 | 1662.56 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 685.10 | 25-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 914.68 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1071.15 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 528.46 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 30-JUN-15:00 | 530.54 | 25-JUN-05:53 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 21-JUL-16:00 | 357.47 | 04-JUL-17:10 |
August | 2010.79 | 01-AUG-09:09 | 855.70 | 18-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 11-AUG-17:00 | 396.02 | 30-AUG-00:45 |
September | 2010.79 | 01-SEP-09:09 | 1569.89 | 28-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 338.98 | 04-SEP-14:00 |
October | 2010.79 | 02-OCT-09:09 | 1662.56 | 03-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 636.63 | 21-OCT-04:01 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 523.49 | 10-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 553.63 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.98 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 1566.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1036.70 | 28-JAN-23:53 |
February | 1295.83 | 01-FEB-10:09 | 1071.42 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 630.91 | 25-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1071.42 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 450.66 | 25-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 708.87 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 355.25 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 30-JUN-15:00 | 351.81 | 25-JUN-05:53 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 | 21-JUL-16:00 | 237.33 | 04-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 553.10 | 18-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 11-AUG-17:00 | 261.57 | 30-AUG-00:45 |
September | 1295.83 | 01-SEP-09:09 | 882.65 | 28-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 228.20 | 04-SEP-14:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 03-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 419.52 | 21-OCT-04:01 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 344.63 | 10-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 363.72 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.20 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 | 1036.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1543.25 | 28-JAN-23:53 |
February | 2010.83 | 01-FEB-10:09 | 1662.60 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 943.95 | 25-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 1662.60 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 790.84 | 12-MAR-15:00 |
April | 2010.83 | 03-APR-09:09 | 914.33 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1128.63 | 01-APR-19:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 524.72 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 30-JUN-15:00 | 506.77 | 24-JUN-21:00 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.60 | 21-JUL-16:00 | 355.99 | 04-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 791.06 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 11-AUG-17:00 | 390.68 | 30-AUG-00:45 |
September | 2010.83 | 01-SEP-09:09 | 1496.05 | 28-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 325.91 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1662.60 | 03-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 628.41 | 22-OCT-18:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 517.86 | 10-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 541.73 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.91 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 50.60 | 1543.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1068.74 | 28-JAN-23:53 |
February | 1295.83 | 01-FEB-10:09 | 1071.42 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 653.75 | 25-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1071.42 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 495.35 | 12-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 729.94 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 880.98 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 354.14 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 30-JUN-15:00 | 360.74 | 25-JUN-05:53 |
July | 1295.83 | 03-JUL-09:09 | 548.88 | 25-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 21-JUL-16:00 | 250.95 | 04-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 549.11 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 11-AUG-17:00 | 276.41 | 30-AUG-00:45 |
September | 1295.83 | 01-SEP-09:09 | 1014.18 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 225.71 | 04-SEP-14:00 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 03-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 448.88 | 21-OCT-04:01 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 367.51 | 10-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 388.59 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.71 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 1068.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3474.17 | 28-JAN-23:53 |
February | 2010.79 | 01-FEB-10:09 | 1662.56 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2080.91 | 25-FEB-00:53 |
March | 2010.79 | 01-MAR-10:09 | 1662.56 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1561.71 | 14-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 908.69 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2277.17 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1104.38 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 30-JUN-15:00 | 1089.26 | 25-JUN-05:53 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 21-JUL-16:00 | 819.67 | 04-JUL-16:55 |
August | 2010.79 | 01-AUG-09:09 | 846.04 | 18-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 11-AUG-16:00 | 855.40 | 30-AUG-00:55 |
September | 2010.79 | 01-SEP-09:09 | 1568.41 | 28-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 705.30 | 04-SEP-13:55 |
October | 2010.79 | 02-OCT-09:09 | 1662.56 | 03-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1410.02 | 21-OCT-04:04 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1140.18 | 10-NOV-05:08 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1187.38 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 705.30 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 3474.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2313.83 | 28-JAN-23:53 |
February | 1239.33 | 01-FEB-08:09 | 1071.42 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1387.31 | 25-FEB-00:53 |
March | 1239.33 | 01-MAR-08:09 | 1071.42 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1042.82 | 14-MAR-21:02 |
April | 1239.33 | 03-APR-07:10 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1541.06 | 01-APR-19:00 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 746.52 | 26-MAY-02:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 30-JUN-15:00 | 729.20 | 25-JUN-06:00 |
July | 1239.33 | 03-JUL-07:10 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 21-JUL-16:00 | 556.18 | 04-JUL-16:55 |
August | 1239.33 | 01-AUG-07:10 | 547.26 | 18-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 11-AUG-16:00 | 572.92 | 30-AUG-00:55 |
September | 1239.33 | 01-SEP-07:10 | 879.99 | 28-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 485.07 | 04-SEP-13:55 |
October | 1239.33 | 02-OCT-07:10 | 1071.42 | 03-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 950.02 | 21-OCT-04:03 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 760.12 | 10-NOV-05:09 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 786.91 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.07 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 2313.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3479.85 | 28-JAN-23:53 |
February | 2010.83 | 01-FEB-10:09 | 1662.60 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2110.88 | 25-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 1662.60 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1827.13 | 12-MAR-14:50 |
April | 2010.83 | 03-APR-09:09 | 908.31 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2602.45 | 01-APR-19:00 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1130.24 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 30-JUN-15:00 | 1091.95 | 18-JUN-14:10 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 21-JUL-16:00 | 850.98 | 04-JUL-16:55 |
August | 2010.83 | 01-AUG-09:09 | 791.06 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 11-AUG-16:10 | 865.88 | 30-AUG-00:55 |
September | 2010.83 | 01-SEP-09:09 | 1492.48 | 28-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 736.31 | 04-SEP-13:55 |
October | 2010.83 | 02-OCT-09:09 | 1662.60 | 03-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1466.11 | 22-OCT-18:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1156.08 | 10-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1192.63 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.31 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 3479.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2319.44 | 28-JAN-23:53 |
February | 1295.83 | 01-FEB-10:09 | 1071.42 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1400.42 | 25-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1071.42 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1043.65 | 14-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 720.84 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1967.40 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 754.84 | 27-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 30-JUN-15:00 | 729.20 | 25-JUN-05:53 |
July | 1295.83 | 03-JUL-09:09 | 542.78 | 25-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 21-JUL-16:00 | 578.73 | 04-JUL-16:55 |
August | 1295.83 | 01-AUG-09:09 | 543.06 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 11-AUG-16:00 | 582.23 | 30-AUG-00:55 |
September | 1295.83 | 01-SEP-09:09 | 1013.50 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 480.34 | 04-SEP-13:55 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 03-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 947.21 | 21-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 765.80 | 10-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 803.04 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.34 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 2319.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1662.56 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4358.84 | 28-JAN-23:53 |
February | 2010.79 | 01-FEB-10:09 | 1662.56 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2583.42 | 25-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1662.56 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1935.20 | 14-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 908.45 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2689.74 | 01-APR-18:53 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1294.56 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 30-JUN-15:00 | 1251.34 | 24-JUN-21:00 |
July | 2010.79 | 03-JUL-09:09 | 791.05 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 21-JUL-16:00 | 993.18 | 04-JUL-16:55 |
August | 2010.79 | 01-AUG-09:09 | 845.66 | 18-AUG-15:00 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 11-AUG-16:00 | 1001.54 | 30-AUG-00:55 |
September | 2010.79 | 01-SEP-09:09 | 1568.37 | 28-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 777.49 | 30-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1662.56 | 03-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1753.74 | 21-OCT-04:45 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1392.98 | 10-NOV-04:52 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1485.62 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.49 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 4358.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2905.89 | 28-JAN-23:55 |
February | 1295.83 | 01-FEB-10:09 | 1071.42 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1732.29 | 25-FEB-00:57 |
March | 1295.83 | 01-MAR-10:09 | 1071.42 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1292.32 | 14-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1813.28 | 01-APR-18:53 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 878.50 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 | 30-JUN-15:00 | 839.30 | 24-JUN-21:00 |
July | 1295.83 | 03-JUL-09:09 | 509.78 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 21-JUL-16:00 | 674.55 | 04-JUL-16:55 |
August | 1295.83 | 01-AUG-09:09 | 547.03 | 18-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 11-AUG-16:00 | 672.60 | 30-AUG-00:55 |
September | 1295.83 | 01-SEP-09:09 | 880.23 | 28-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 524.20 | 04-SEP-13:55 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 03-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1173.10 | 21-OCT-04:24 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 946.46 | 10-NOV-05:09 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 990.42 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.20 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 2905.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1662.60 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4358.86 | 28-JAN-23:57 |
February | 2010.83 | 01-FEB-10:09 | 1662.60 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2595.40 | 25-FEB-00:57 |
March | 2010.83 | 01-MAR-10:09 | 1662.60 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2194.38 | 12-MAR-14:53 |
April | 2010.83 | 03-APR-09:09 | 908.07 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3137.49 | 01-APR-18:53 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1332.26 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 30-JUN-15:00 | 1358.39 | 18-JUN-14:10 |
July | 2010.83 | 03-JUL-09:09 | 791.06 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 21-JUL-16:00 | 1032.80 | 04-JUL-16:55 |
August | 2010.83 | 01-AUG-09:09 | 791.06 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 11-AUG-16:10 | 1018.83 | 30-AUG-00:55 |
September | 2010.83 | 01-SEP-09:09 | 1492.44 | 28-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 817.90 | 30-SEP-21:00 |
October | 2010.83 | 02-OCT-09:09 | 1662.60 | 03-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1766.84 | 21-OCT-04:24 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1419.68 | 10-NOV-05:09 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1485.62 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 817.90 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 4358.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1071.42 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2905.89 | 28-JAN-23:53 |
February | 1295.83 | 01-FEB-10:09 | 1071.42 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1729.50 | 25-FEB-00:57 |
March | 1295.83 | 01-MAR-10:09 | 1071.42 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1294.21 | 14-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 720.20 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2412.53 | 01-APR-18:53 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 894.50 | 27-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 | 30-JUN-15:00 | 859.74 | 24-JUN-21:00 |
July | 1295.83 | 03-JUL-09:09 | 542.55 | 25-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 21-JUL-16:00 | 703.47 | 04-JUL-16:55 |
August | 1295.83 | 01-AUG-09:09 | 542.82 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 11-AUG-16:00 | 688.10 | 30-AUG-00:55 |
September | 1295.83 | 01-SEP-09:09 | 1013.48 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 532.51 | 04-SEP-13:55 |
October | 1295.83 | 02-OCT-09:09 | 1071.42 | 03-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1178.13 | 21-OCT-04:24 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 947.27 | 10-NOV-05:04 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 990.40 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.51 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 2905.89 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3384.73 | 28-JAN-23:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2032.73 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1458.48 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2294.09 | 01-APR-18:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1075.04 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 30-JUN-15:00 | 1090.87 | 25-JUN-05:57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.64 | 21-JUL-16:00 | 712.58 | 04-JUL-16:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 11-AUG-17:00 | 842.47 | 30-AUG-00:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 682.89 | 04-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1358.89 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1120.87 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1179.43 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.64 | 3384.73 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5831.87 | 28-JAN-23:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3520.41 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2549.35 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3945.61 | 01-APR-18:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1853.78 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.62 | 30-JUN-15:00 | 1811.31 | 25-JUN-05:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.25 | 29-JUL-17:02 | 1202.11 | 04-JUL-16:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 11-AUG-16:00 | 1443.84 | 30-AUG-00:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1116.17 | 04-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2350.38 | 21-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1937.52 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1999.49 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1116.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.25 | 5831.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6221.32 | 28-JAN-23:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3830.30 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2756.75 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4380.13 | 01-APR-18:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1987.16 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.81 | 30-JUN-15:00 | 1905.89 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.14 | 21-JUL-16:00 | 1487.60 | 04-JUL-16:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 11-AUG-18:00 | 1523.25 | 30-AUG-00:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1182.59 | 04-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2419.07 | 21-OCT-04:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2040.44 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2175.97 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.14 | 6221.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 87243.12 | 06-JAN-15:10 | 102327.84 | 88464.20 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94123.78 | 13-FEB-07:12 | 21542.70 | 29488.07 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99032.06 | 20-MAR-06:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 108822.73 | 24-APR-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117576.06 | 28-SEP-06:11 | 32314.05 | 44232.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 119977.39 | 11-OCT-06:11 | 35904.50 | 49146.78 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97095.61 | 13-NOV-07:11 | 25133.15 | 34402.75 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99288.86 | 26-DEC-07:11 | 28723.60 | 39317.42 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 119977.39 | 102327.84 | 88464.20 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 50763.84 | 20-JAN-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77891.61 | 15-FEB-06:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81155.63 | 21-MAR-04:01 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88156.84 | 24-APR-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91063.14 | 06-MAY-04:02 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92824.69 | 27-JUN-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92730.79 | 31-JUL-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96134.69 | 16-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92472.31 | 07-SEP-04:02 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89932.12 | 10-OCT-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78208.76 | 03-NOV-05:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71308.41 | 21-DEC-06:01 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 50763.84 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96134.69 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15450.28 | 27-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20960.74 | 17-FEB-13:20 | 30632.53 | 26482.36 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51874.80 | 23-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75129.97 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75134.28 | 02-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76998.11 | 26-JUN-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83177.62 | 24-JUL-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79522.23 | 14-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75103.68 | 13-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70458.16 | 06-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16106.21 | 03-NOV-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14849.24 | 22-DEC-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14849.24 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83177.62 | 30632.53 | 26482.36 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12444.05 | 20-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14636.16 | 09-FEB-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17892.34 | 22-MAR-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35266.94 | 21-APR-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67710.92 | 23-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73688.28 | 24-JUN-04:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74644.72 | 25-JUL-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74745.98 | 05-AUG-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32926.96 | 01-SEP-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21458.28 | 04-OCT-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12720.35 | 02-NOV-16:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11632.04 | 21-DEC-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11632.04 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74745.98 | 15316.26 | 13241.18 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1549.83 | 20-JAN-06:03 | 1417.03 | 472.30 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.73 |
February | 2148.09 | 09-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.81 |
March | 3690.48 | 22-MAR-13:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6435.51 | 24-APR-12:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
May | 15341.68 | 31-MAY-04:14 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16313.66 | 07-JUN-04:13 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.42 |
July | 17470.59 | 23-JUL-12:52 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 |
August | 14386.30 | 02-AUG-05:03 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 |
September | 10939.39 | 01-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
October | 4172.31 | 04-OCT-14:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.69 |
November | 2072.90 | 03-NOV-05:02 | 1619.46 | 539.77 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 |
December | 1586.47 | 26-DEC-11:02 | 17307.99 | 14963.06 | 19444.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1549.83 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17470.59 | 17307.99 | 14963.06 | 19444.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1018.37 | 20-JAN-06:03 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 |
February | 2770.61 | 15-FEB-10:35 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 |
March | 9883.99 | 27-MAR-09:25 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 |
April | 17514.28 | 23-APR-10:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.79 |
May | 28654.60 | 21-MAY-08:31 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.45 |
June | 23895.75 | 04-JUN-09:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.63 |
July | 28200.65 | 23-JUL-09:32 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 |
August | 20670.14 | 27-AUG-12:01 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 |
September | 23936.75 | 10-SEP-08:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.40 |
October | 9348.28 | 03-OCT-09:25 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 |
November | 1357.75 | 03-NOV-05:02 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 |
December | 1017.40 | 23-DEC-06:03 | 782.73 | 260.89 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1017.40 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | |
Maximum of Months | 28654.60 | 2591.66 | 1019.56 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3957.42 | 25-JAN-13:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 |
February | 13846.56 | 15-FEB-13:30 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28840.07 | 26-MAR-15:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35047.06 | 30-APR-13:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.32 |
May | 40996.66 | 21-MAY-13:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.23 |
June | 35584.41 | 11-JUN-13:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.42 |
July | 42955.44 | 23-JUL-12:52 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 |
August | 42786.60 | 27-AUG-13:22 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.93 |
September | 36086.61 | 10-SEP-11:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.85 |
October | 21706.92 | 03-OCT-13:10 | 4021.67 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.40 |
November | 10609.40 | 08-NOV-13:30 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 |
December | 1670.20 | 27-DEC-13:10 | 17308.37 | 11912.55 | 19445.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1670.20 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42955.44 | 17308.37 | 11912.55 | 19445.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1115.51 | 23-JAN-14:40 | 3887.49 | 2252.61 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.31 |
February | 3532.45 | 09-FEB-15:00 | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 |
March | 18202.82 | 26-MAR-16:23 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27798.36 | 22-APR-17:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.61 |
May | 30002.44 | 21-MAY-17:51 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.31 |
June | 29164.99 | 11-JUN-17:51 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.78 |
July | 27810.28 | 08-JUL-18:22 | 0.00 | 169.91 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 |
August | 29658.10 | 27-AUG-15:22 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.52 |
September | 20278.73 | 02-SEP-17:05 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.37 |
October | 10371.05 | 04-OCT-05:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 |
November | 3880.80 | 08-NOV-15:30 | 1239.33 | 540.88 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 |
December | 1468.25 | 21-DEC-06:01 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1115.51 | 0.00 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30002.44 | 3887.49 | 2252.61 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1238.76 | 07-JAN-17:02 | 506.08 | 461.79 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.12 |
February | 1357.43 | 09-FEB-16:10 | 1923.11 | 1569.67 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1901.75 | 22-MAR-14:10 | 3846.22 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4438.93 | 28-APR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12585.38 | 31-MAY-04:12 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15154.98 | 16-JUN-04:23 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.96 |
July | 15091.26 | 07-JUL-04:13 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.21 |
August | 11189.40 | 02-AUG-05:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
September | 4385.41 | 01-SEP-13:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 |
October | 2060.90 | 06-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.63 |
November | 1239.40 | 04-NOV-16:03 | 404.87 | 369.43 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1234.24 | 30-DEC-17:02 | 506.08 | 461.79 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1234.24 | 0.00 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15154.98 | 3846.22 | 1582.09 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 943.24 | 19-JAN-13:04 | 6196.63 | 3967.10 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.43 |
February | 1298.54 | 15-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.46 |
March | 9684.14 | 31-MAR-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.43 |
April | 17693.40 | 23-APR-09:02 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.03 |
May | 29936.29 | 14-MAY-09:31 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.79 |
June | 24754.27 | 18-JUN-09:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.01 |
July | 29787.41 | 23-JUL-09:41 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.18 |
August | 18028.12 | 10-AUG-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 |
September | 19769.39 | 10-SEP-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.54 |
October | 8449.68 | 03-OCT-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.29 |
November | 933.98 | 07-NOV-15:04 | 6196.63 | 4016.62 | 6961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 922.71 | 19-DEC-13:04 | 9914.60 | 7992.67 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 922.71 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29936.29 | 9914.60 | 7992.67 | 11138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2847.10 | 25-JAN-13:20 | 3846.30 | 1582.13 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 |
February | 13141.73 | 15-FEB-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38786.13 | 12-MAR-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.18 |
April | 37595.58 | 23-APR-13:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.12 |
May | 43243.52 | 14-MAY-12:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.30 |
June | 40902.01 | 18-JUN-12:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.85 |
July | 45533.38 | 23-JUL-13:01 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.07 |
August | 39960.15 | 27-AUG-13:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.73 |
September | 37567.90 | 10-SEP-11:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.57 |
October | 21667.40 | 03-OCT-13:30 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.13 |
November | 8674.66 | 08-NOV-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.70 |
December | 1414.52 | 19-DEC-06:04 | 1417.06 | 472.31 | 6721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1414.52 | 607.31 | 263.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45533.38 | 3846.30 | 1582.13 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 912.05 | 18-JAN-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 |
February | 1127.48 | 16-FEB-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 |
March | 5669.94 | 27-MAR-16:50 | 391.37 | 283.21 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.60 |
April | 25117.80 | 22-APR-17:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.99 |
May | 28451.32 | 14-MAY-18:51 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.26 |
June | 28854.81 | 11-JUN-17:01 | 0.00 | 254.87 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.59 |
July | 25894.14 | 23-JUL-15:41 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 |
August | 25921.22 | 27-AUG-17:42 | 0.00 | 169.91 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.93 |
September | 17305.03 | 02-SEP-17:05 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.89 |
October | 4187.16 | 03-OCT-15:10 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.88 |
November | 1072.19 | 08-NOV-15:40 | 1239.33 | 869.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 |
December | 931.43 | 19-DEC-06:04 | 913.19 | 304.37 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 912.05 | 0.00 | 169.91 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28854.81 | 1239.33 | 869.63 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1340.20 | 07-JAN-17:02 | 506.08 | 461.79 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.20 |
February | 1354.27 | 11-FEB-17:03 | 404.87 | 369.43 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.57 |
March | 1875.52 | 22-MAR-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3637.69 | 28-APR-15:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 |
May | 12015.62 | 31-MAY-05:03 | 607.30 | 202.41 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 |
June | 16426.61 | 07-JUN-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.93 |
July | 16355.00 | 07-JUL-04:13 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.47 |
August | 11787.72 | 05-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 |
September | 3417.97 | 01-SEP-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.47 |
October | 1887.56 | 04-OCT-15:50 | 1923.11 | 880.40 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.75 |
November | 1331.43 | 18-NOV-17:02 | 506.08 | 461.79 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1332.42 | 30-DEC-17:02 | 506.08 | 461.79 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1331.43 | 0.00 | 202.41 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16426.61 | 1923.11 | 880.40 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 954.63 | 07-JAN-06:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.21 |
February | 971.59 | 15-FEB-10:50 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.42 |
March | 4864.12 | 22-MAR-10:30 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 |
April | 13536.23 | 23-APR-10:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.20 |
May | 29204.75 | 21-MAY-09:11 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.60 |
June | 22436.62 | 18-JUN-10:11 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.66 |
July | 26827.26 | 09-JUL-08:21 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.37 |
August | 24515.13 | 27-AUG-10:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.58 |
September | 24794.30 | 10-SEP-09:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.38 |
October | 3978.27 | 03-OCT-10:00 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.06 |
November | 925.15 | 01-NOV-05:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.54 |
December | 894.35 | 12-DEC-06:04 | 1174.10 | 391.33 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 894.35 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 | |
Maximum of Months | 29204.75 | 2591.66 | 1019.56 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1716.34 | 25-JAN-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 |
February | 9599.34 | 15-FEB-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19493.68 | 31-MAR-14:00 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.28 |
April | 38362.67 | 23-APR-13:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.37 |
May | 44727.24 | 14-MAY-12:41 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.97 |
June | 42011.28 | 18-JUN-12:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.83 |
July | 42359.34 | 23-JUL-13:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.86 |
August | 46509.64 | 27-AUG-13:31 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.02 |
September | 38763.63 | 10-SEP-11:31 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.18 |
October | 18910.33 | 03-OCT-13:30 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.16 |
November | 5375.09 | 08-NOV-13:40 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.41 |
December | 1394.07 | 22-DEC-06:04 | 1821.93 | 607.25 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1394.07 | 708.53 | 307.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46509.64 | 2010.83 | 791.06 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 929.76 | 07-JAN-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.68 |
February | 1006.29 | 09-FEB-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 |
March | 4160.38 | 27-MAR-17:00 | 391.37 | 283.21 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 |
April | 24108.33 | 22-APR-17:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.00 |
May | 29305.12 | 14-MAY-18:41 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.38 |
June | 26912.50 | 10-JUN-17:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.06 |
July | 27339.11 | 09-JUL-19:42 | 0.00 | 169.91 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.02 |
August | 29421.34 | 27-AUG-16:51 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.02 |
September | 15194.23 | 02-SEP-17:05 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.65 |
October | 2750.39 | 03-OCT-15:10 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 |
November | 939.08 | 21-NOV-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 931.87 | 21-DEC-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 929.76 | 0.00 | 169.91 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29421.34 | 1239.33 | 509.78 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9951.31 | 12-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8620.42 | 27-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5771.64 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.01 |
April | 7565.47 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.92 |
May | 13968.81 | 15-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.78 |
June | 14356.19 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.64 |
July | 16854.89 | 24-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 |
August | 14602.99 | 14-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 |
September | 9537.13 | 18-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.14 |
October | 5842.22 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
November | 6876.61 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6276.15 | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5771.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16854.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11326.95 | 13-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12342.40 | 24-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.98 |
March | 11551.27 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.93 |
April | 9530.09 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.94 |
May | 5348.78 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
June | 7153.13 | 21-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.95 |
July | 9293.09 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.69 |
August | 6178.65 | 01-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.10 |
September | 3290.37 | 08-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.59 |
October | 11699.30 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.19 |
November | 11049.35 | 20-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11978.76 | 15-DEC-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3290.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12342.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1217.30 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1023.77 |
March | 515.77 | 22-MAR-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7640.86 | 20-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.21 |
May | 13017.96 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.83 |
June | 14290.14 | 29-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 |
July | 14755.46 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 0.00 |
August | 12214.44 | 10-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
September | 5174.45 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.85 |
October | 66.00 | 03-OCT-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.47 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.47 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14755.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 1217.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1208.75 | 23-JAN-15:20 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3610.49 | 15-FEB-16:20 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6857.34 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8638.95 | 20-APR-19:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3570.12 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5481.03 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7437.48 | 31-JUL-23:53 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8678.63 | 27-AUG-18:57 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3066.82 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4630.63 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5594.98 | 08-NOV-15:50 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7107.21 | 26-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1208.75 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8678.63 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 646.96 | 12-JAN-10:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3091.32 | 16-FEB-16:20 | 444.28 | 633.26 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6048.27 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8265.16 | 20-APR-19:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3248.96 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5126.15 | 30-JUN-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7038.76 | 31-JUL-23:40 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7906.41 | 27-AUG-18:50 | 0.00 | 123.14 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2406.26 | 30-SEP-23:40 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3485.24 | 03-OCT-16:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4851.77 | 08-NOV-16:00 | 444.28 | 633.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5891.59 | 21-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 646.96 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8265.16 | 444.28 | 633.26 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 626.64 | 12-JAN-08:15 | 444.28 | 633.26 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2582.88 | 09-FEB-16:10 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5300.02 | 31-MAR-17:40 | 23.38 | 105.54 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8253.38 | 20-APR-19:00 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3181.57 | 31-MAY-23:50 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5082.49 | 30-JUN-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6998.40 | 31-JUL-23:15 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7953.47 | 27-AUG-18:31 | 0.00 | 158.32 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2115.07 | 02-SEP-18:10 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3289.25 | 03-OCT-16:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4304.98 | 08-NOV-16:00 | 444.28 | 633.26 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5380.58 | 29-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 626.64 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8253.38 | 444.28 | 633.26 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89521.96 | 20-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181434.87 | 09-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357795.21 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367589.58 | 20-APR-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177114.40 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269039.31 | 30-JUN-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 361897.05 | 31-JUL-23:53 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370167.01 | 11-AUG-16:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175300.85 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266143.49 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274025.46 | 03-NOV-16:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 365521.50 | 26-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89521.96 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370167.01 | 4808.68 | 4157.19 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.163177E+13 | 1147908.06 | 23-JAN-16:19 | 0.105046E+13 | 2496663.00 | 12-JAN-07:10 |
February | 0.183980E+13 | 1306541.52 | 03-FEB-16:00 | 0.592295E+12 | 2644766.10 | 27-FEB-07:10 |
March | 0.245808E+13 | 1428258.89 | 16-MAR-07:10 | 0.261864E+12 | 1984668.04 | 01-MAR-07:10 |
April | 0.267596E+13 | 1673381.15 | 21-APR-15:00 | 0.395058E+11 | 1304578.12 | 03-APR-06:10 |
May | 0.175666E+13 | 1496915.09 | 31-MAY-15:20 | 0.289664E+10 | 313002.37 | 27-MAY-06:10 |
June | 0.210192E+13 | 1714384.84 | 21-JUN-15:30 | 0.145865E+09 | 114830.89 | 15-JUN-09:09 |
July | 0.242487E+13 | 1876290.18 | 12-JUL-15:00 | 0.110735E+09 | 170759.66 | 05-JUL-13:09 |
August | 0.280696E+13 | 1987468.20 | 11-AUG-15:39 | 0.146535E+10 | 387964.53 | 31-AUG-06:10 |
September | 0.154192E+13 | 1258719.33 | 07-SEP-15:50 | 0.130297E+11 | 504861.09 | 29-SEP-06:10 |
October | 0.203423E+13 | 1338853.78 | 03-OCT-14:30 | 0.150222E+12 | 1366382.53 | 30-OCT-06:10 |
November | 0.235879E+13 | 1446876.68 | 22-NOV-16:40 | 0.812560E+12 | 2268208.75 | 27-NOV-07:10 |
December | 0.276487E+13 | 1571714.11 | 29-DEC-16:30 | 0.117466E+13 | 2154207.11 | 15-DEC-07:10 |
Annual Sum or Average | 0.263958E+14 | 0.409922E+13 | ||||
Minimum of Months | 0.154192E+13 | 1147908.06 | 0.110735E+09 | 114830.89 | ||
Maximum of Months | 0.280696E+13 | 1987468.20 | 0.117466E+13 | 2644766.10 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.225484E+12 | 0.623637E+11 | 0.766053E+12 | 0.213324E+12 | 0.170411E+12 | 0.124145E+11 | 0.00 | 0.502197E+10 | 0.155622E+09 | 0.121395E+12 | 0.694984E+10 | 0.482022E+11 | 0.00 |
February | 0.195241E+12 | 0.426998E+11 | 0.978954E+12 | 0.195312E+12 | 0.153830E+12 | 0.112482E+11 | 0.00 | 0.188502E+11 | 0.674725E+09 | 0.193015E+12 | 0.617642E+10 | 0.437958E+11 | 0.00 |
March | 0.222858E+12 | 0.327220E+11 | 0.141687E+13 | 0.226029E+12 | 0.178978E+12 | 0.134662E+11 | 0.00 | 0.394305E+11 | 0.164624E+10 | 0.267692E+12 | 0.688546E+10 | 0.514997E+11 | 0.00 |
April | 0.194889E+12 | 0.190834E+11 | 0.165903E+13 | 0.211475E+12 | 0.197989E+12 | 0.180038E+11 | 0.00 | 0.621417E+11 | 0.401856E+10 | 0.259145E+12 | 0.347968E+10 | 0.467086E+11 | 0.00 |
May | 0.209708E+12 | 0.107131E+11 | 0.774844E+12 | 0.219671E+12 | 0.235125E+12 | 0.222269E+11 | 0.00 | 0.345495E+11 | 0.114592E+11 | 0.188251E+12 | 0.660931E+09 | 0.494520E+11 | 0.00 |
June | 0.208274E+12 | 0.503126E+10 | 0.106252E+13 | 0.217906E+12 | 0.260637E+12 | 0.345059E+11 | 0.00 | 0.107994E+12 | 0.472299E+11 | 0.110221E+12 | 0.341315E+09 | 0.472570E+11 | 0.00 |
July | 0.194896E+12 | 0.751282E+10 | 0.139340E+13 | 0.213239E+12 | 0.256782E+12 | 0.387084E+11 | 0.00 | 0.186084E+12 | 0.608124E+11 | 0.296153E+11 | 0.514007E+09 | 0.433048E+11 | 0.00 |
August | 0.218297E+12 | 0.152657E+11 | 0.173200E+13 | 0.226028E+12 | 0.242824E+12 | 0.321977E+11 | 0.00 | 0.168611E+12 | 0.501903E+11 | 0.748611E+11 | 0.424949E+09 | 0.462555E+11 | 0.00 |
September | 0.197191E+12 | 0.259693E+11 | 0.740713E+12 | 0.211475E+12 | 0.182467E+12 | 0.178530E+11 | 0.00 | 0.213823E+11 | 0.193626E+10 | 0.984737E+11 | 0.261761E+10 | 0.418436E+11 | 0.00 |
October | 0.210934E+12 | 0.406361E+11 | 0.108340E+13 | 0.213317E+12 | 0.171331E+12 | 0.140240E+11 | 0.00 | 0.270491E+11 | 0.158247E+10 | 0.222354E+12 | 0.555323E+10 | 0.440466E+11 | 0.00 |
November | 0.218700E+12 | 0.546324E+11 | 0.135889E+13 | 0.205276E+12 | 0.163655E+12 | 0.126118E+11 | 0.00 | 0.336626E+11 | 0.105046E+10 | 0.258917E+12 | 0.665744E+10 | 0.447335E+11 | 0.00 |
December | 0.221906E+12 | 0.685901E+11 | 0.170972E+13 | 0.213250E+12 | 0.169876E+12 | 0.126192E+11 | 0.00 | 0.464770E+11 | 0.142058E+10 | 0.267840E+12 | 0.684547E+10 | 0.463298E+11 | 0.00 |
Annual Sum or Average | 0.251838E+13 | 0.385220E+12 | 0.146764E+14 | 0.256630E+13 | 0.238391E+13 | 0.239880E+12 | 0.00 | 0.751254E+12 | 0.182177E+12 | 0.209178E+13 | 0.471063E+11 | 0.553429E+12 | 0.00 |
Minimum of Months | 0.194889E+12 | 0.503126E+10 | 0.740713E+12 | 0.195312E+12 | 0.153830E+12 | 0.112482E+11 | 0.00 | 0.502197E+10 | 0.155622E+09 | 0.296153E+11 | 0.341315E+09 | 0.418436E+11 | 0.00 |
Maximum of Months | 0.225484E+12 | 0.685901E+11 | 0.173200E+13 | 0.226029E+12 | 0.260637E+12 | 0.387084E+11 | 0.00 | 0.186084E+12 | 0.608124E+11 | 0.267840E+12 | 0.694984E+10 | 0.514997E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.105046E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.592295E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.261864E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.395058E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.289664E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145865E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.110735E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.146535E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.130297E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.150222E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.812560E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.117466E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.409922E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.110735E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.117466E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 247210.90 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233397.31 | 02-JAN-08:20 | 104959.71 | 02-JAN-06:19 | 19479.61 | 23-JAN-07:40 | 0.00 | 01-JAN-00:10 |
February | 247210.90 | 01-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233397.31 | 01-FEB-08:20 | 96414.94 | 15-FEB-13:30 | 19483.92 | 21-FEB-08:30 | 0.00 | 01-FEB-00:10 |
March | 247210.90 | 01-MAR-08:09 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233397.31 | 01-MAR-08:20 | 127456.09 | 31-MAR-15:20 | 19476.32 | 16-MAR-06:30 | 0.00 | 01-MAR-00:10 |
April | 218186.40 | 04-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233381.93 | 04-APR-07:19 | 237488.47 | 21-APR-15:50 | 19633.31 | 21-APR-12:09 | 0.00 | 01-APR-00:10 |
May | 212815.01 | 01-MAY-07:10 | 27558.46 | 01-MAY-21:10 | 423497.50 | 01-MAY-07:10 | 233379.09 | 01-MAY-07:19 | 250027.64 | 31-MAY-14:30 | 35557.00 | 31-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 212815.01 | 01-JUN-07:10 | 27558.46 | 01-JUN-22:49 | 541788.89 | 01-JUN-07:10 | 233379.09 | 01-JUN-07:19 | 261302.10 | 20-JUN-15:30 | 38221.41 | 20-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 213216.92 | 25-JUL-07:10 | 27558.46 | 11-JUL-22:00 | 660080.29 | 03-JUL-07:10 | 233379.30 | 25-JUL-07:19 | 269289.04 | 12-JUL-15:20 | 38541.46 | 21-JUL-14:09 | 0.00 | 01-JUL-00:10 |
August | 213939.55 | 18-AUG-15:00 | 40855.88 | 24-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233379.31 | 07-AUG-07:19 | 271097.61 | 10-AUG-15:00 | 38878.57 | 11-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 241053.94 | 28-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233394.04 | 28-SEP-07:19 | 187220.12 | 07-SEP-15:20 | 19850.20 | 01-SEP-13:20 | 0.00 | 01-SEP-00:10 |
October | 247210.90 | 03-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233397.31 | 03-OCT-07:19 | 140592.00 | 03-OCT-14:30 | 19531.61 | 03-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233397.31 | 01-NOV-07:19 | 92471.71 | 27-NOV-06:10 | 19554.49 | 13-NOV-07:49 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-08:09 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233397.31 | 01-DEC-08:20 | 92301.28 | 11-DEC-06:10 | 19527.76 | 26-DEC-07:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 212815.01 | 27558.46 | 423497.50 | 233379.09 | 92301.28 | 19476.32 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 233397.31 | 271097.61 | 38878.57 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3359.29 | 27-JAN-15:50 | 303.04 | 19-JAN-17:10 | 53753.78 | 19-JAN-05:10 | 5431.84 | 02-JAN-08:20 | 63525.20 | 11-JAN-12:50 | 0.00 |
February | 11224.54 | 16-FEB-16:19 | 1231.78 | 08-FEB-18:49 | 100000.00 | 08-FEB-13:50 | 5431.84 | 01-FEB-07:10 | 63524.80 | 10-FEB-12:39 | 0.00 |
March | 29984.82 | 22-MAR-15:20 | 3256.30 | 22-MAR-16:30 | 100000.00 | 01-MAR-09:30 | 5431.84 | 01-MAR-07:19 | 63524.98 | 21-MAR-11:00 | 0.00 |
April | 88599.75 | 21-APR-12:09 | 7881.99 | 22-APR-13:00 | 100000.00 | 01-APR-04:30 | 5431.84 | 01-APR-06:10 | 63524.98 | 10-APR-11:39 | 0.00 |
May | 153901.02 | 31-MAY-15:20 | 45326.88 | 31-MAY-14:00 | 100000.00 | 06-MAY-16:19 | 4520.72 | 03-MAY-06:10 | 63473.49 | 01-MAY-11:39 | 0.00 |
June | 286362.55 | 30-JUN-12:30 | 72747.30 | 29-JUN-10:50 | 100000.00 | 01-JUN-21:10 | 4520.72 | 20-JUN-15:39 | 62134.77 | 01-JUN-11:39 | 0.00 |
July | 301652.17 | 21-JUL-14:30 | 72747.30 | 03-JUL-14:50 | 100000.00 | 12-JUL-22:19 | 4520.72 | 11-JUL-12:50 | 58986.02 | 03-JUL-11:00 | 0.00 |
August | 331542.65 | 11-AUG-15:20 | 72747.30 | 23-AUG-14:30 | 100000.00 | 10-AUG-21:10 | 4520.72 | 11-AUG-15:39 | 57914.50 | 01-AUG-11:50 | 0.00 |
September | 79346.24 | 18-SEP-15:00 | 5178.97 | 07-SEP-15:00 | 100000.00 | 10-SEP-13:50 | 5431.84 | 29-SEP-06:10 | 57316.29 | 29-SEP-11:00 | 0.00 |
October | 56150.13 | 03-OCT-14:39 | 2804.92 | 20-OCT-16:00 | 100000.00 | 01-OCT-15:30 | 5431.84 | 03-OCT-06:10 | 58681.75 | 31-OCT-11:30 | 0.00 |
November | 15934.84 | 08-NOV-15:50 | 1155.25 | 02-NOV-17:10 | 100000.00 | 01-NOV-04:30 | 5431.84 | 01-NOV-06:10 | 60880.84 | 29-NOV-12:00 | 0.00 |
December | 19570.41 | 29-DEC-13:20 | 1723.70 | 23-DEC-12:50 | 100000.00 | 01-DEC-00:30 | 5431.84 | 01-DEC-07:10 | 63522.76 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 3359.29 | 303.04 | 53753.78 | 4520.72 | 57316.29 | 0.00 | |||||
Maximum of Months | 331542.65 | 72747.30 | 100000.00 | 5431.84 | 63525.20 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1147908.06 | 23-JAN-16:19 | 247210.90 | 423497.50 | 40855.88 | 233284.51 | 78292.29 | 19419.90 | 0.00 | 2872.71 | 81.36 |
February | 1306541.52 | 03-FEB-16:00 | 247210.90 | 541788.89 | 40855.88 | 233284.51 | 78565.74 | 19416.14 | 0.00 | 9618.65 | 379.32 |
March | 1428258.89 | 16-MAR-07:10 | 247210.90 | 660080.29 | 40855.88 | 233310.75 | 78907.54 | 11681.15 | 0.00 | 13282.70 | 351.19 |
April | 1673381.15 | 21-APR-15:00 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 236657.35 | 19425.05 | 0.00 | 38906.79 | 5331.22 |
May | 1496915.09 | 31-MAY-15:20 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 245831.96 | 35478.54 | 0.00 | 153901.02 | 44586.00 |
June | 1714384.84 | 21-JUN-15:30 | 212815.01 | 541788.89 | 0.00 | 233266.29 | 252254.73 | 37988.50 | 0.00 | 242871.85 | 47193.83 |
July | 1876290.18 | 12-JUL-15:00 | 212815.01 | 660080.29 | 0.00 | 233266.29 | 264484.86 | 35723.36 | 0.00 | 278345.68 | 44889.47 |
August | 1987468.20 | 11-AUG-15:39 | 212815.01 | 778371.69 | 0.00 | 233266.29 | 270164.90 | 38878.57 | 0.00 | 314575.71 | 44938.75 |
September | 1258719.33 | 07-SEP-15:50 | 212815.01 | 423497.50 | 0.00 | 233266.29 | 180445.71 | 19509.42 | 0.00 | 40867.69 | 4704.26 |
October | 1338853.78 | 03-OCT-14:30 | 212815.01 | 541788.89 | 0.00 | 233115.89 | 140592.00 | 19530.52 | 0.00 | 55376.12 | 2100.27 |
November | 1446876.68 | 22-NOV-16:40 | 247210.90 | 660080.29 | 40855.88 | 233284.51 | 78844.51 | 19419.52 | 0.00 | 14556.73 | 495.65 |
December | 1571714.11 | 29-DEC-16:30 | 247210.90 | 778371.69 | 40855.88 | 233284.51 | 78864.80 | 19419.12 | 0.00 | 18853.67 | 645.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1147908.06 | 212815.01 | 423497.50 | 0.00 | 233115.89 | 78292.29 | 11681.15 | 0.00 | 2872.71 | 81.36 | |
Maximum of Months | 1987468.20 | 247210.90 | 778371.69 | 40855.88 | 233310.75 | 270164.90 | 38878.57 | 0.00 | 314575.71 | 47193.83 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2496663.00 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2644766.10 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1984668.04 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1304578.12 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 313002.37 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 114830.89 | 15-JUN-09:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 170759.66 | 05-JUL-13:09 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 387964.53 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 504861.09 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1366382.53 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2268208.75 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2154207.11 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 114830.89 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2644766.10 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 25.21 | 23.83 | 25.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 25.52 | 27.17 | 25.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 25.90 | 30.17 | 25.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 174.00 | 27.08 | 102.33 | 27.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.51 | 508.00 | 29.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.95 | 496.00 | 29.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.20 | 497.00 | 30.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.43 | 514.00 | 30.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 663.50 | 29.96 | 442.50 | 30.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 217.83 | 27.80 | 133.67 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 25.89 | 27.00 | 25.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 25.73 | 28.17 | 25.72 |
Annual Sum or Average | 0.00 | 0.00 | 4224.67 | 29.56 | 2829.83 | 29.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 25.21 | 23.83 | 25.21 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.43 | 514.00 | 30.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.04 | 0.33 | 26.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.48 | 1.50 | 26.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.60 | 0.67 | 26.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.55 | 0.67 | 26.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.61 | 1.50 | 26.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.85 | 0.00 | 25.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.50 | 26.48 | 4.67 | 26.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.61 | 1.50 | 26.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.25 | 1.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Annual Sum or Average | 3.50 | 19.26 | 1.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.41 | 1.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 18.74 | 3.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 9.00 | 18.74 | 2.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
March | 3.67 | 18.95 | 0.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 0.50 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.50 | 18.91 | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
November | 11.00 | 18.78 | 2.67 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
December | 12.50 | 18.81 | 2.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Annual Sum or Average | 52.17 | 18.79 | 11.83 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.00 | 18.95 | 3.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 0.83 | 19.38 | 0.17 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.82 | 0.17 | 25.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.73 | 3.83 | 26.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 26.79 | 9.33 | 26.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.35 | 1.17 | 26.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 19.10 | 0.17 | 19.18 | 35.00 | 26.13 | 14.50 | 26.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.38 | 0.17 | 19.55 | 17.17 | 26.79 | 9.33 | 26.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 1.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 0.17 | 19.35 | 0.00 | 19.35 | 0.17 | 23.33 | 0.17 | 24.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.86 | 2.33 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.62 | 10.67 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.30 | 7.67 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.52 | 12.67 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.26 | 5.50 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.99 | 4.67 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
December | 0.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 5.33 | 19.16 | 0.00 | 19.16 | 62.00 | 26.85 | 43.67 | 27.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.38 | 0.00 | 19.38 | 19.50 | 27.99 | 12.67 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
February | 1.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 0.17 | 19.29 | 0.00 | 19.29 | 2.33 | 27.31 | 2.33 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.03 | 6.00 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.34 | 7.50 | 28.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.69 | 6.00 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.56 | 9.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.90 | 7.17 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.94 | 3.17 | 27.94 |
October | 0.17 | 19.42 | 0.00 | 19.42 | 0.50 | 25.42 | 0.50 | 26.28 |
November | 1.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
December | 3.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 9.50 | 19.02 | 0.00 | 19.02 | 54.00 | 26.53 | 42.33 | 27.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 0.00 | 18.70 |
Maximum of Months | 3.67 | 19.42 | 0.00 | 19.42 | 15.50 | 28.34 | 9.67 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.71 | 0.67 | 27.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.93 | 5.83 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.14 | 4.50 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.48 | 7.50 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.54 | 16.33 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.41 | 10.67 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.60 | 0.83 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.27 | 0.00 | 19.27 | 110.00 | 27.54 | 46.50 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.27 | 0.00 | 19.27 | 36.83 | 28.14 | 16.33 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.33 | 17.17 | 19.50 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
February | 26.67 | 17.74 | 9.17 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
March | 10.17 | 18.81 | 2.17 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 1.17 | 18.85 | 0.17 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.75 | 0.00 | 25.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.12 | 0.17 | 26.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.96 | 0.17 | 25.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.67 | 18.84 | 0.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
November | 21.67 | 18.37 | 6.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
December | 34.33 | 18.22 | 12.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
Annual Sum or Average | 146.00 | 17.87 | 49.67 | 18.08 | 6.50 | 18.34 | 0.33 | 18.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.33 | 18.85 | 19.50 | 19.07 | 4.17 | 26.12 | 0.17 | 26.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.00 | 17.80 | 8.83 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
February | 33.17 | 18.24 | 1.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
March | 5.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
April | 0.67 | 19.02 | 0.00 | 19.02 | 1.67 | 25.25 | 1.67 | 26.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.09 | 6.00 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.05 | 4.33 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.59 | 8.83 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.65 | 2.00 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.85 | 2.17 | 27.85 |
October | 3.67 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
November | 67.33 | 18.73 | 0.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
December | 88.67 | 18.13 | 2.67 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
Annual Sum or Average | 297.00 | 18.19 | 12.83 | 18.06 | 31.33 | 18.94 | 25.00 | 19.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 0.00 | 17.57 |
Maximum of Months | 98.00 | 19.02 | 8.83 | 19.02 | 11.00 | 28.09 | 8.83 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 16.03 | 5.33 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
February | 8.50 | 17.55 | 0.83 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
March | 4.33 | 18.74 | 0.00 | 18.74 | 2.00 | 21.70 | 2.00 | 23.24 |
April | 0.33 | 19.24 | 0.00 | 19.24 | 5.67 | 27.68 | 5.50 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.39 | 6.67 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.02 | 5.17 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.11 | 7.17 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.19 | 5.00 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.87 | 2.67 | 27.87 |
October | 2.00 | 18.84 | 0.00 | 18.84 | 0.33 | 20.07 | 0.33 | 20.98 |
November | 9.33 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
December | 16.50 | 17.03 | 1.67 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
Annual Sum or Average | 65.00 | 17.05 | 7.83 | 16.84 | 38.17 | 20.73 | 34.50 | 22.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 0.00 | 15.80 |
Maximum of Months | 24.00 | 19.24 | 5.33 | 19.24 | 8.33 | 28.39 | 7.17 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.17 | 16.09 | 6.00 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
February | 8.67 | 17.41 | 1.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
March | 5.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
April | 0.33 | 19.29 | 0.00 | 19.29 | 3.17 | 27.14 | 1.17 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.29 | 3.00 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.15 | 2.67 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.95 | 3.00 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.20 | 1.17 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.66 | 0.50 | 27.67 |
October | 1.83 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
November | 8.17 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
December | 10.83 | 18.02 | 0.17 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
Annual Sum or Average | 59.00 | 17.26 | 7.33 | 17.02 | 32.00 | 20.63 | 11.50 | 21.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 | 15.84 |
Maximum of Months | 24.17 | 19.29 | 6.00 | 19.29 | 8.67 | 28.29 | 3.00 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 110.17 | 16.80 | 50.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
February | 87.83 | 16.79 | 38.67 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
March | 55.33 | 17.76 | 21.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
April | 11.83 | 17.47 | 3.33 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.90 | 0.00 | 25.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.99 | 0.00 | 25.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.83 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
October | 30.17 | 17.01 | 10.67 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
November | 98.17 | 16.88 | 45.50 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
December | 119.33 | 17.10 | 53.50 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
Annual Sum or Average | 513.67 | 17.02 | 223.33 | 17.33 | 3.17 | 17.37 | 0.00 | 17.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.33 | 18.99 | 53.50 | 18.99 | 2.33 | 25.99 | 0.00 | 25.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.67 | 14.92 | 16.50 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
February | 44.50 | 15.14 | 10.33 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
March | 21.50 | 16.33 | 1.17 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 5.50 | 16.83 | 0.33 | 16.72 | 0.83 | 18.07 | 0.83 | 19.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.25 | 4.67 | 28.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.07 | 4.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.67 | 8.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.74 | 1.17 | 27.74 |
September | 0.83 | 19.07 | 0.00 | 19.07 | 0.83 | 23.43 | 0.83 | 24.89 |
October | 17.67 | 16.09 | 2.67 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
November | 57.00 | 15.09 | 17.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
December | 63.83 | 15.03 | 15.67 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
Annual Sum or Average | 271.50 | 15.26 | 64.00 | 15.12 | 25.00 | 15.99 | 20.00 | 16.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 | 14.78 |
Maximum of Months | 63.83 | 19.07 | 17.33 | 19.07 | 10.17 | 28.25 | 8.17 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.00 | 15.00 | 14.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
February | 35.17 | 15.43 | 5.17 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
March | 14.00 | 17.11 | 0.83 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
April | 2.50 | 18.16 | 0.00 | 18.16 | 3.00 | 23.57 | 2.83 | 25.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.32 | 6.33 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.02 | 5.00 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.19 | 6.83 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.15 | 4.50 | 28.18 |
September | 0.67 | 19.09 | 0.00 | 19.09 | 1.67 | 25.18 | 1.67 | 26.19 |
October | 14.50 | 16.40 | 2.17 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
November | 45.33 | 15.28 | 12.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
December | 58.83 | 15.10 | 15.33 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Annual Sum or Average | 226.00 | 15.42 | 49.83 | 15.27 | 30.50 | 16.55 | 27.17 | 17.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 | 14.86 |
Maximum of Months | 58.83 | 19.09 | 15.33 | 19.09 | 8.00 | 28.32 | 6.83 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.67 | 15.02 | 15.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
February | 36.00 | 15.47 | 8.67 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
March | 12.50 | 17.26 | 0.17 | 17.30 | 0.00 | 17.30 | 0.00 | 17.30 |
April | 2.33 | 18.20 | 0.00 | 18.20 | 2.00 | 22.69 | 0.67 | 23.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.26 | 3.00 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.30 | 2.17 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.94 | 3.50 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.16 | 1.17 | 28.19 |
September | 0.67 | 19.22 | 0.00 | 19.22 | 0.50 | 22.86 | 0.33 | 23.94 |
October | 11.83 | 16.68 | 1.17 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
November | 34.33 | 15.59 | 7.33 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
December | 41.00 | 15.45 | 11.33 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 191.33 | 15.60 | 43.67 | 15.44 | 29.50 | 16.85 | 10.83 | 17.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 0.00 | 14.87 |
Maximum of Months | 52.67 | 19.22 | 15.00 | 19.22 | 9.00 | 28.30 | 3.50 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 432.17 | 24.16 | 0.00 | 24.16 | 0.00 | 24.16 |
February | 344.83 | 24.12 | 1.17 | 24.13 | 0.00 | 24.13 |
March | 354.17 | 24.06 | 19.17 | 24.16 | 0.00 | 24.16 |
April | 219.33 | 24.66 | 148.50 | 25.55 | 40.83 | 25.75 |
May | 505.67 | 29.63 | 508.00 | 29.62 | 505.67 | 29.62 |
June | 496.00 | 30.05 | 496.00 | 30.05 | 496.00 | 30.05 |
July | 497.00 | 30.30 | 497.00 | 30.30 | 497.00 | 30.30 |
August | 514.00 | 30.53 | 514.00 | 30.53 | 514.00 | 30.53 |
September | 445.67 | 30.00 | 448.33 | 30.00 | 437.83 | 30.03 |
October | 235.17 | 25.85 | 178.33 | 26.52 | 101.00 | 26.85 |
November | 334.00 | 24.06 | 17.33 | 24.17 | 0.00 | 24.17 |
December | 345.67 | 24.06 | 18.50 | 24.17 | 0.00 | 24.17 |
Annual Sum or Average | 4723.67 | 27.34 | 2846.33 | 28.22 | 2592.33 | 28.68 |
Minimum of Months | 219.33 | 24.06 | 0.00 | 24.13 | 0.00 | 24.13 |
Maximum of Months | 514.00 | 30.53 | 514.00 | 30.53 | 514.00 | 30.53 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.50 | 12.00 | 23.47 | 12.00 | 23.44 |
February | 419.00 | 23.88 | 0.00 | 23.88 | 0.00 | 23.88 |
March | 379.67 | 23.99 | 5.33 | 24.02 | 0.00 | 24.02 |
April | 176.67 | 24.02 | 47.17 | 24.41 | 0.00 | 24.41 |
May | 0.00 | 0.00 | 104.83 | 26.17 | 0.00 | 26.17 |
June | 0.17 | 27.19 | 352.33 | 24.60 | 0.17 | 24.60 |
July | 0.33 | 27.26 | 490.83 | 24.54 | 0.33 | 24.54 |
August | 0.00 | 0.00 | 455.00 | 24.50 | 0.00 | 24.50 |
September | 17.00 | 24.00 | 174.83 | 25.26 | 0.00 | 25.26 |
October | 203.83 | 23.98 | 50.33 | 24.46 | 0.00 | 24.46 |
November | 418.50 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
December | 457.33 | 23.94 | 1.67 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 2574.50 | 23.86 | 1694.33 | 24.24 | 12.50 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.47 | 0.00 | 23.44 |
Maximum of Months | 502.00 | 27.26 | 490.83 | 26.17 | 12.00 | 26.17 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.38 | 181.50 | 21.08 | 181.50 | 20.90 |
February | 454.00 | 22.21 | 76.83 | 21.99 | 76.83 | 21.83 |
March | 514.00 | 23.14 | 6.33 | 23.12 | 6.33 | 23.09 |
April | 423.50 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
May | 219.00 | 23.95 | 4.83 | 23.98 | 0.00 | 23.98 |
June | 20.67 | 23.96 | 130.17 | 24.55 | 0.00 | 24.55 |
July | 0.00 | 0.00 | 287.67 | 24.43 | 0.00 | 24.43 |
August | 24.67 | 23.90 | 181.50 | 24.46 | 0.00 | 24.46 |
September | 221.00 | 23.82 | 25.33 | 23.99 | 0.00 | 23.99 |
October | 474.33 | 23.36 | 2.00 | 23.35 | 2.00 | 23.34 |
November | 489.00 | 22.03 | 81.17 | 21.85 | 81.17 | 21.72 |
December | 497.00 | 21.53 | 197.67 | 21.31 | 197.67 | 21.19 |
Annual Sum or Average | 3839.17 | 22.64 | 1175.00 | 22.65 | 545.50 | 22.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.08 | 0.00 | 20.90 |
Maximum of Months | 514.00 | 23.96 | 287.67 | 24.55 | 197.67 | 24.55 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 455.00 | 20.19 | 455.00 | 20.17 |
February | 454.00 | 20.54 | 313.33 | 20.34 | 313.33 | 20.26 |
March | 514.00 | 21.31 | 233.83 | 21.03 | 233.83 | 20.89 |
April | 475.17 | 22.61 | 78.50 | 22.28 | 78.50 | 22.04 |
May | 322.00 | 23.64 | 1.17 | 23.65 | 0.00 | 23.65 |
June | 43.67 | 23.87 | 105.50 | 24.30 | 0.00 | 24.30 |
July | 2.00 | 23.63 | 268.67 | 24.41 | 0.00 | 24.41 |
August | 106.17 | 23.57 | 139.83 | 24.06 | 0.00 | 24.06 |
September | 409.50 | 22.91 | 2.33 | 22.90 | 2.33 | 22.89 |
October | 502.00 | 21.36 | 200.00 | 21.05 | 200.00 | 20.88 |
November | 489.00 | 20.36 | 420.50 | 20.27 | 420.50 | 20.24 |
December | 497.00 | 20.25 | 483.17 | 20.23 | 483.17 | 20.23 |
Annual Sum or Average | 4316.50 | 21.43 | 2701.83 | 21.27 | 2186.67 | 21.01 |
Minimum of Months | 2.00 | 20.25 | 1.17 | 20.19 | 0.00 | 20.17 |
Maximum of Months | 514.00 | 23.87 | 483.17 | 24.41 | 483.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.60 | 446.17 | 20.56 | 446.17 | 20.55 |
February | 454.00 | 21.06 | 260.17 | 20.89 | 260.17 | 20.81 |
March | 514.00 | 22.08 | 110.67 | 21.88 | 110.67 | 21.73 |
April | 418.17 | 23.41 | 17.17 | 23.39 | 10.00 | 23.33 |
May | 43.00 | 24.01 | 81.67 | 25.27 | 0.00 | 25.27 |
June | 2.67 | 27.31 | 380.50 | 24.59 | 2.67 | 24.61 |
July | 29.83 | 26.90 | 488.50 | 24.71 | 29.83 | 24.83 |
August | 22.33 | 24.68 | 393.33 | 24.48 | 5.17 | 24.52 |
September | 168.83 | 23.68 | 58.33 | 24.11 | 0.00 | 24.11 |
October | 481.33 | 22.54 | 71.50 | 22.32 | 71.50 | 22.16 |
November | 489.00 | 21.00 | 327.33 | 20.91 | 327.33 | 20.87 |
December | 497.00 | 20.89 | 420.67 | 20.83 | 420.67 | 20.82 |
Annual Sum or Average | 3622.17 | 21.81 | 3056.00 | 22.13 | 1684.17 | 21.87 |
Minimum of Months | 2.67 | 20.60 | 17.17 | 20.56 | 0.00 | 20.55 |
Maximum of Months | 514.00 | 27.31 | 488.50 | 25.27 | 446.17 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 464.17 | 20.50 | 464.17 | 20.49 |
February | 454.00 | 21.27 | 239.17 | 21.04 | 239.17 | 20.93 |
March | 456.00 | 22.49 | 85.83 | 22.30 | 78.50 | 22.12 |
April | 291.33 | 23.40 | 71.33 | 23.66 | 12.67 | 23.62 |
May | 39.67 | 25.70 | 250.67 | 25.01 | 20.00 | 25.16 |
June | 20.17 | 27.09 | 424.00 | 24.64 | 20.17 | 24.75 |
July | 51.17 | 26.75 | 489.33 | 24.81 | 51.17 | 24.98 |
August | 30.33 | 26.08 | 440.00 | 24.56 | 21.67 | 24.66 |
September | 113.67 | 24.04 | 141.00 | 24.64 | 12.33 | 24.75 |
October | 434.83 | 22.53 | 73.50 | 22.33 | 67.00 | 22.16 |
November | 489.00 | 20.82 | 388.33 | 20.76 | 388.33 | 20.73 |
December | 497.00 | 20.68 | 476.17 | 20.67 | 476.17 | 20.67 |
Annual Sum or Average | 3379.17 | 21.83 | 3543.50 | 22.27 | 1851.33 | 22.02 |
Minimum of Months | 20.17 | 20.53 | 71.33 | 20.50 | 12.33 | 20.49 |
Maximum of Months | 502.00 | 27.09 | 489.33 | 25.01 | 476.17 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.50 | 444.50 | 20.41 | 444.50 | 20.37 |
February | 420.50 | 21.47 | 204.83 | 21.21 | 198.67 | 21.05 |
March | 393.17 | 22.38 | 138.00 | 22.41 | 82.33 | 22.23 |
April | 237.00 | 23.41 | 152.33 | 23.80 | 25.83 | 23.79 |
May | 97.67 | 24.83 | 223.00 | 24.83 | 26.33 | 25.01 |
June | 22.33 | 27.09 | 391.67 | 24.69 | 22.33 | 24.81 |
July | 39.83 | 27.05 | 478.33 | 24.79 | 39.83 | 24.95 |
August | 33.50 | 26.46 | 419.33 | 24.64 | 27.00 | 24.78 |
September | 154.67 | 23.77 | 165.00 | 24.25 | 7.33 | 24.32 |
October | 413.67 | 22.39 | 90.50 | 22.31 | 62.17 | 22.13 |
November | 485.00 | 21.01 | 350.67 | 20.82 | 350.67 | 20.74 |
December | 497.00 | 20.53 | 485.17 | 20.52 | 485.17 | 20.52 |
Annual Sum or Average | 3296.33 | 21.84 | 3543.33 | 22.29 | 1772.17 | 22.03 |
Minimum of Months | 22.33 | 20.50 | 90.50 | 20.41 | 7.33 | 20.37 |
Maximum of Months | 502.00 | 27.09 | 485.17 | 24.83 | 485.17 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.98 | 297.33 | 20.85 | 297.33 | 20.79 |
February | 452.00 | 22.22 | 98.50 | 21.98 | 98.50 | 21.81 |
March | 416.83 | 23.50 | 21.17 | 23.52 | 8.67 | 23.48 |
April | 117.50 | 24.35 | 154.00 | 24.88 | 13.50 | 24.99 |
May | 43.67 | 25.11 | 178.33 | 25.21 | 15.50 | 25.33 |
June | 24.50 | 27.06 | 442.33 | 24.74 | 24.50 | 24.85 |
July | 71.17 | 26.90 | 497.00 | 24.97 | 71.17 | 25.18 |
August | 39.50 | 26.99 | 478.50 | 24.77 | 39.50 | 24.92 |
September | 131.00 | 23.95 | 116.33 | 24.47 | 4.50 | 24.51 |
October | 375.33 | 23.36 | 19.33 | 23.47 | 0.00 | 23.47 |
November | 489.00 | 22.52 | 39.33 | 22.42 | 39.33 | 22.33 |
December | 497.00 | 22.45 | 15.67 | 22.41 | 15.67 | 22.37 |
Annual Sum or Average | 3159.50 | 22.80 | 2357.83 | 23.31 | 628.17 | 23.22 |
Minimum of Months | 24.50 | 20.98 | 15.67 | 20.85 | 0.00 | 20.79 |
Maximum of Months | 502.00 | 27.06 | 497.00 | 25.21 | 297.33 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.92 | 502.00 | 19.92 | 502.00 | 19.92 |
February | 454.00 | 20.07 | 440.83 | 20.06 | 440.83 | 20.05 |
March | 514.00 | 20.72 | 398.67 | 20.60 | 398.67 | 20.56 |
April | 485.00 | 22.21 | 122.00 | 21.85 | 122.00 | 21.60 |
May | 314.67 | 23.78 | 0.67 | 23.78 | 0.00 | 23.78 |
June | 9.17 | 23.85 | 204.17 | 24.44 | 0.00 | 24.44 |
July | 1.67 | 24.14 | 363.50 | 24.47 | 0.17 | 24.47 |
August | 114.00 | 23.43 | 129.67 | 23.92 | 0.00 | 23.92 |
September | 451.17 | 22.67 | 15.83 | 22.61 | 15.83 | 22.56 |
October | 502.00 | 20.98 | 280.50 | 20.76 | 280.50 | 20.66 |
November | 489.00 | 19.99 | 489.00 | 19.99 | 489.00 | 19.99 |
December | 497.00 | 19.91 | 497.00 | 19.91 | 497.00 | 19.91 |
Annual Sum or Average | 4333.67 | 21.08 | 3443.83 | 21.04 | 2746.00 | 20.79 |
Minimum of Months | 1.67 | 19.91 | 0.67 | 19.91 | 0.00 | 19.91 |
Maximum of Months | 514.00 | 24.14 | 502.00 | 24.47 | 502.00 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.75 | 427.00 | 19.75 | 427.00 | 19.75 |
February | 385.00 | 20.13 | 351.50 | 20.06 | 351.50 | 20.04 |
March | 416.67 | 21.49 | 199.83 | 21.16 | 199.17 | 20.99 |
April | 298.50 | 22.71 | 84.17 | 22.69 | 51.33 | 22.48 |
May | 130.17 | 24.20 | 140.83 | 24.61 | 13.00 | 24.74 |
June | 18.50 | 26.11 | 266.00 | 24.62 | 13.17 | 24.72 |
July | 35.17 | 26.87 | 367.33 | 24.85 | 34.50 | 25.01 |
August | 46.83 | 23.98 | 249.33 | 24.41 | 6.33 | 24.46 |
September | 277.67 | 22.99 | 51.83 | 23.31 | 11.00 | 23.32 |
October | 420.83 | 21.35 | 188.83 | 21.04 | 188.17 | 20.88 |
November | 417.00 | 19.82 | 417.00 | 19.82 | 417.00 | 19.82 |
December | 422.00 | 19.69 | 422.00 | 19.69 | 422.00 | 19.69 |
Annual Sum or Average | 3295.33 | 21.11 | 3165.67 | 21.35 | 2134.17 | 21.06 |
Minimum of Months | 18.50 | 19.69 | 51.83 | 19.69 | 6.33 | 19.69 |
Maximum of Months | 427.00 | 26.87 | 427.00 | 24.85 | 427.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 477.83 | 20.02 | 477.83 | 20.00 |
February | 429.00 | 20.91 | 300.67 | 20.67 | 299.50 | 20.57 |
March | 403.17 | 21.76 | 217.83 | 21.74 | 162.00 | 21.54 |
April | 262.00 | 22.86 | 181.50 | 23.25 | 54.33 | 23.12 |
May | 196.17 | 24.05 | 173.00 | 24.37 | 23.33 | 24.54 |
June | 42.83 | 25.26 | 311.00 | 24.55 | 19.33 | 24.69 |
July | 32.67 | 26.64 | 404.50 | 24.71 | 28.33 | 24.86 |
August | 86.67 | 24.32 | 308.00 | 24.44 | 20.17 | 24.57 |
September | 268.67 | 23.11 | 124.33 | 23.56 | 9.67 | 23.58 |
October | 437.33 | 21.71 | 171.00 | 21.53 | 146.00 | 21.31 |
November | 486.00 | 20.32 | 437.67 | 20.22 | 437.67 | 20.18 |
December | 497.00 | 19.94 | 497.00 | 19.94 | 497.00 | 19.94 |
Annual Sum or Average | 3643.50 | 21.43 | 3604.33 | 21.73 | 2175.17 | 21.44 |
Minimum of Months | 32.67 | 19.94 | 124.33 | 19.94 | 9.67 | 19.94 |
Maximum of Months | 502.00 | 26.64 | 497.00 | 24.71 | 497.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 502.00 | 20.01 | 502.00 | 20.01 |
February | 454.00 | 20.29 | 409.67 | 20.23 | 409.67 | 20.21 |
March | 499.17 | 21.23 | 281.67 | 20.98 | 281.67 | 20.87 |
April | 337.67 | 22.72 | 116.00 | 22.71 | 60.33 | 22.51 |
May | 181.33 | 23.86 | 91.00 | 24.24 | 9.00 | 24.34 |
June | 19.00 | 25.55 | 303.50 | 24.65 | 10.17 | 24.72 |
July | 17.67 | 26.61 | 420.50 | 24.66 | 15.83 | 24.74 |
August | 67.17 | 23.91 | 280.33 | 24.38 | 5.83 | 24.42 |
September | 347.00 | 22.96 | 36.00 | 23.08 | 6.00 | 23.08 |
October | 498.17 | 21.33 | 218.17 | 21.07 | 218.17 | 20.93 |
November | 489.00 | 20.15 | 484.50 | 20.15 | 484.50 | 20.15 |
December | 497.00 | 20.05 | 497.00 | 20.05 | 497.00 | 20.05 |
Annual Sum or Average | 3909.17 | 21.19 | 3640.33 | 21.40 | 2500.17 | 21.13 |
Minimum of Months | 17.67 | 20.01 | 36.00 | 20.01 | 5.83 | 20.01 |
Maximum of Months | 502.00 | 26.61 | 502.00 | 24.66 | 502.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.80 | 454.00 | 19.80 | 454.00 | 19.80 |
March | 514.00 | 20.18 | 484.17 | 20.15 | 484.17 | 20.14 |
April | 485.00 | 21.29 | 231.83 | 20.91 | 231.83 | 20.71 |
May | 382.67 | 23.34 | 6.83 | 23.29 | 6.83 | 23.25 |
June | 39.83 | 23.55 | 182.67 | 24.24 | 0.00 | 24.24 |
July | 19.50 | 23.57 | 340.83 | 24.37 | 0.00 | 24.37 |
August | 192.17 | 23.01 | 110.67 | 23.42 | 5.17 | 23.38 |
September | 480.83 | 21.70 | 116.17 | 21.48 | 116.17 | 21.33 |
October | 502.00 | 20.18 | 433.83 | 20.09 | 433.83 | 20.06 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 4558.00 | 20.69 | 3849.00 | 20.66 | 3220.00 | 20.44 |
Minimum of Months | 19.50 | 19.65 | 6.83 | 19.65 | 0.00 | 19.65 |
Maximum of Months | 514.00 | 23.57 | 502.00 | 24.37 | 502.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 502.00 | 19.79 | 502.00 | 19.79 |
February | 454.00 | 19.92 | 444.83 | 19.91 | 444.83 | 19.91 |
March | 509.83 | 20.86 | 353.83 | 20.57 | 353.83 | 20.45 |
April | 383.67 | 22.11 | 150.50 | 21.80 | 126.33 | 21.51 |
May | 160.67 | 23.74 | 151.00 | 24.20 | 13.33 | 24.31 |
June | 38.67 | 24.76 | 318.00 | 24.43 | 13.50 | 24.52 |
July | 44.17 | 26.21 | 424.83 | 24.69 | 34.83 | 24.84 |
August | 85.33 | 23.50 | 283.67 | 24.13 | 6.50 | 24.14 |
September | 373.00 | 22.23 | 87.50 | 22.25 | 55.67 | 22.08 |
October | 499.67 | 20.53 | 359.67 | 20.30 | 359.67 | 20.21 |
November | 489.00 | 19.81 | 489.00 | 19.81 | 489.00 | 19.81 |
December | 497.00 | 19.76 | 497.00 | 19.76 | 497.00 | 19.76 |
Annual Sum or Average | 4037.00 | 20.83 | 4061.83 | 21.07 | 2896.50 | 20.81 |
Minimum of Months | 38.67 | 19.76 | 87.50 | 19.76 | 6.50 | 19.76 |
Maximum of Months | 509.83 | 26.21 | 502.00 | 24.69 | 502.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 493.83 | 19.82 | 493.83 | 19.81 |
February | 447.33 | 20.37 | 376.67 | 20.19 | 376.67 | 20.12 |
March | 431.17 | 21.01 | 303.17 | 20.84 | 274.00 | 20.67 |
April | 297.17 | 22.08 | 210.33 | 22.25 | 108.00 | 21.97 |
May | 232.50 | 23.48 | 164.33 | 23.91 | 25.83 | 24.02 |
June | 74.00 | 24.37 | 290.33 | 24.41 | 18.83 | 24.54 |
July | 57.17 | 25.30 | 381.83 | 24.63 | 28.83 | 24.79 |
August | 122.00 | 23.68 | 281.50 | 24.19 | 22.17 | 24.29 |
September | 320.67 | 22.20 | 141.83 | 22.53 | 49.17 | 22.37 |
October | 471.67 | 20.83 | 306.83 | 20.58 | 295.50 | 20.44 |
November | 489.00 | 19.94 | 468.00 | 19.88 | 468.00 | 19.87 |
December | 497.00 | 19.77 | 497.00 | 19.77 | 497.00 | 19.77 |
Annual Sum or Average | 3941.67 | 21.01 | 3915.67 | 21.26 | 2657.83 | 20.99 |
Minimum of Months | 57.17 | 19.77 | 141.83 | 19.77 | 18.83 | 19.77 |
Maximum of Months | 502.00 | 25.30 | 497.00 | 24.63 | 497.00 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 502.00 | 19.83 | 502.00 | 19.83 |
February | 454.00 | 19.99 | 443.83 | 19.97 | 443.83 | 19.96 |
March | 507.00 | 20.64 | 401.33 | 20.47 | 401.33 | 20.41 |
April | 371.17 | 21.96 | 180.00 | 21.76 | 133.50 | 21.48 |
May | 240.50 | 23.45 | 82.67 | 23.77 | 12.00 | 23.82 |
June | 43.83 | 24.38 | 278.33 | 24.54 | 11.17 | 24.63 |
July | 27.17 | 25.56 | 398.33 | 24.61 | 16.50 | 24.70 |
August | 109.17 | 23.36 | 244.50 | 24.08 | 7.33 | 24.11 |
September | 411.17 | 22.21 | 83.67 | 22.13 | 63.00 | 21.99 |
October | 500.83 | 20.54 | 366.33 | 20.36 | 366.33 | 20.29 |
November | 489.00 | 19.88 | 488.17 | 19.88 | 488.17 | 19.88 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 4152.83 | 20.85 | 3966.17 | 21.03 | 2942.17 | 20.78 |
Minimum of Months | 27.17 | 19.83 | 82.67 | 19.83 | 7.33 | 19.83 |
Maximum of Months | 507.00 | 25.56 | 502.00 | 24.61 | 502.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 293.83 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 394.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 512.33 | 27.00 | 0.00 | 27.00 |
April | 22.00 | 27.00 | 485.00 | 27.00 | 22.00 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 23.83 | 27.00 | 496.00 | 27.00 | 23.83 | 27.00 |
July | 138.33 | 27.00 | 497.00 | 27.00 | 138.33 | 27.00 |
August | 177.50 | 27.00 | 514.00 | 27.00 | 177.50 | 27.00 |
September | 1.67 | 27.00 | 485.00 | 27.00 | 1.67 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 363.33 | 27.00 | 5673.83 | 27.00 | 363.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 293.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 177.50 | 27.00 | 514.00 | 27.00 | 177.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.50 | 25.31 | 19.83 | 25.24 | 12.00 | 25.13 |
February | 35.50 | 27.00 | 116.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 312.67 | 27.00 | 0.00 | 27.00 |
April | 7.83 | 27.00 | 452.83 | 27.00 | 7.83 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.17 | 27.00 | 496.00 | 27.00 | 1.17 | 27.00 |
July | 8.00 | 27.00 | 497.00 | 27.00 | 8.00 | 27.00 |
August | 6.00 | 27.00 | 514.00 | 27.00 | 6.00 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 381.83 | 27.00 | 0.00 | 27.00 |
November | 20.17 | 27.00 | 61.67 | 27.00 | 0.00 | 27.00 |
December | 39.17 | 27.00 | 13.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 433.33 | 25.77 | 3858.50 | 26.86 | 35.00 | 26.85 |
Minimum of Months | 0.00 | 0.00 | 13.50 | 25.24 | 0.00 | 25.13 |
Maximum of Months | 315.50 | 27.00 | 514.00 | 27.00 | 12.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.83 | 24.38 | 74.00 | 24.04 | 74.00 | 23.78 |
February | 110.83 | 26.79 | 29.67 | 26.83 | 0.00 | 26.83 |
March | 59.83 | 27.00 | 141.00 | 27.00 | 0.00 | 27.00 |
April | 20.83 | 27.00 | 363.50 | 27.00 | 6.00 | 27.00 |
May | 0.00 | 0.00 | 504.17 | 27.00 | 0.00 | 27.00 |
June | 1.83 | 27.00 | 496.00 | 27.00 | 1.83 | 27.00 |
July | 10.67 | 27.00 | 497.00 | 27.00 | 10.67 | 27.00 |
August | 6.83 | 27.00 | 514.00 | 27.00 | 6.83 | 27.00 |
September | 5.00 | 26.06 | 442.17 | 26.99 | 0.00 | 26.99 |
October | 41.00 | 27.00 | 192.00 | 27.00 | 0.00 | 27.00 |
November | 121.00 | 27.00 | 1.50 | 27.00 | 0.00 | 27.00 |
December | 131.00 | 27.00 | 0.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 999.67 | 25.69 | 3255.00 | 26.60 | 99.33 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 | 23.78 |
Maximum of Months | 490.83 | 27.00 | 514.00 | 27.00 | 74.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5441.00 | 27.00 | 5943.00 | 27.00 | 5441.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98783 | 10.84855 | 0.54932 | 11.38771 |
February | 454.00000 | 27.00000 | 11.41802 | 0.64011 | 13.72797 |
March | 514.00000 | 26.99999 | 12.19129 | 0.73736 | 16.55420 |
April | 485.00000 | 27.00000 | 15.42135 | 0.86208 | 20.80961 |
May | 508.00000 | 27.00000 | 22.41968 | 0.20065 | 5.89897 |
June | 496.00000 | 27.00037 | 28.42782 | 0.32380 | 7.23641 |
July | 497.00000 | 27.00046 | 29.96818 | 0.38376 | 8.12310 |
August | 514.00000 | 27.00017 | 28.49896 | 0.39739 | 8.35460 |
September | 485.00000 | 27.00013 | 25.27905 | 0.18576 | 5.82649 |
October | 502.00000 | 27.00000 | 17.58679 | 0.75883 | 17.26679 |
November | 489.00000 | 27.00000 | 10.05263 | 0.66431 | 14.32044 |
December | 497.00000 | 27.00000 | 9.12778 | 0.66942 | 14.46757 |
Annual Sum or Average | 5943.00000 | 26.99906 | 18.50053 | 0.52996 | 11.97289 |
Minimum of Months | 454.00000 | 26.98783 | 9.12778 | 0.18576 | 5.82649 |
Maximum of Months | 514.00000 | 27.00046 | 29.96818 | 0.86208 | 20.80961 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.84704 | 10.83269 | 0.20469 | 7.15138 |
February | 454.00000 | 27.00000 | 11.39706 | 0.48081 | 10.01100 |
March | 514.00000 | 26.99999 | 12.18154 | 0.57527 | 12.12374 |
April | 485.00000 | 26.99999 | 15.41212 | 0.72756 | 16.41930 |
May | 508.00000 | 27.00000 | 22.40451 | 0.09981 | 5.31693 |
June | 496.00000 | 27.00036 | 28.44245 | 0.21165 | 6.00735 |
July | 497.00000 | 27.00049 | 29.99733 | 0.24362 | 6.29993 |
August | 514.00000 | 27.00021 | 28.50511 | 0.22977 | 6.19193 |
September | 485.00000 | 27.00011 | 25.31439 | 0.04995 | 5.24284 |
October | 502.00000 | 27.00000 | 17.57431 | 0.61300 | 13.09160 |
November | 489.00000 | 27.00000 | 10.03884 | 0.46651 | 9.64321 |
December | 497.00000 | 27.00000 | 9.11643 | 0.44591 | 9.23865 |
Annual Sum or Average | 5943.00000 | 26.90271 | 18.49863 | 0.36112 | 8.87535 |
Minimum of Months | 454.00000 | 25.84704 | 9.11643 | 0.04995 | 5.24284 |
Maximum of Months | 514.00000 | 27.00049 | 29.99733 | 0.72756 | 16.41930 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42627 | 10.92956 | -0.1274 | 7.68075 |
February | 454.00000 | 26.94867 | 11.40058 | 0.38466 | 8.49804 |
March | 514.00000 | 27.00000 | 12.18383 | 0.47754 | 10.04172 |
April | 485.00000 | 26.99999 | 15.41432 | 0.65063 | 14.42730 |
May | 508.00000 | 27.00012 | 22.40847 | 0.06197 | 5.33749 |
June | 496.00000 | 27.00037 | 28.44896 | 0.20500 | 6.00937 |
July | 497.00000 | 27.00049 | 30.00303 | 0.23752 | 6.29108 |
August | 514.00000 | 27.00022 | 28.51386 | 0.20346 | 6.05982 |
September | 485.00000 | 26.97735 | 25.38053 | -0.0583 | 5.56028 |
October | 502.00000 | 27.00004 | 17.57656 | 0.50534 | 10.62449 |
November | 489.00000 | 27.00000 | 10.04211 | 0.37792 | 8.15627 |
December | 497.00000 | 27.00000 | 9.11911 | 0.36839 | 7.98485 |
Annual Sum or Average | 5943.00000 | 26.77693 | 18.51566 | 0.27272 | 8.04192 |
Minimum of Months | 454.00000 | 24.42627 | 9.11911 | -0.1274 | 5.33749 |
Maximum of Months | 514.00000 | 27.00049 | 30.00303 | 0.65063 | 14.42730 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00012 | 30.00081 | 0.95725 | 24.37674 |
February | 454.00000 | 27.00033 | 29.99640 | 1.14604 | 32.66790 |
March | 514.00000 | 27.00019 | 25.15275 | 1.28592 | 39.55253 |
April | 485.00000 | 27.00011 | 19.51063 | 1.40828 | 45.96004 |
May | 508.00000 | 27.00009 | 29.24302 | 0.52436 | 10.78213 |
June | 496.00000 | 27.00073 | 30.90012 | 0.76908 | 17.50193 |
July | 497.00000 | 27.00566 | 34.29772 | 1.01192 | 26.65182 |
August | 514.00000 | 27.00850 | 30.71954 | 1.18125 | 34.35728 |
September | 485.00000 | 27.00016 | 30.01311 | 0.55654 | 11.52967 |
October | 502.00000 | 27.00033 | 29.67504 | 1.21878 | 36.18047 |
November | 489.00000 | 27.00029 | 27.02317 | 1.30309 | 40.43236 |
December | 497.00000 | 27.00023 | 22.35630 | 1.38766 | 44.85862 |
Annual Sum or Average | 5943.00000 | 27.00142 | 28.24606 | 1.06198 | 30.38423 |
Minimum of Months | 454.00000 | 27.00009 | 19.51063 | 0.52436 | 10.78213 |
Maximum of Months | 514.00000 | 27.00850 | 34.29772 | 1.40828 | 45.96004 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.30073 | 15.21840 | 0.20000 | 5.93242 |
February | 454.00000 | 24.43031 | 12.99447 | 0.23056 | 6.26449 |
March | 514.00000 | 24.47138 | 12.68342 | 0.26177 | 6.66855 |
April | 485.00000 | 25.06502 | 19.06861 | 0.45494 | 11.67684 |
May | 508.00000 | 29.61611 | 98.31173 | 1.75647 | 64.73919 |
June | 496.00000 | 30.04981 | 99.99924 | 1.93952 | 73.79047 |
July | 497.00000 | 30.30435 | 99.99771 | 2.03985 | 78.29993 |
August | 514.00000 | 30.52634 | 99.99959 | 2.12564 | 81.90119 |
September | 485.00000 | 29.55262 | 92.01504 | 1.72736 | 68.52220 |
October | 502.00000 | 25.39856 | 30.18264 | 0.62214 | 18.72557 |
November | 489.00000 | 24.57152 | 11.03858 | 0.26628 | 6.76224 |
December | 497.00000 | 24.51936 | 10.27027 | 0.24136 | 6.50413 |
Annual Sum or Average | 5943.00000 | 26.92434 | 50.51800 | 0.99633 | 36.10730 |
Minimum of Months | 454.00000 | 24.30073 | 10.27027 | 0.20000 | 5.93242 |
Maximum of Months | 514.00000 | 30.52634 | 99.99959 | 2.12564 | 81.90119 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50227 | 19.56056 | 0.04304 | 5.37501 |
February | 454.00000 | 23.94130 | 17.06048 | 0.15179 | 5.72663 |
March | 514.00000 | 24.17385 | 15.41761 | 0.22569 | 6.21280 |
April | 485.00000 | 24.31635 | 14.96590 | 0.29163 | 7.02617 |
May | 508.00000 | 24.46705 | 20.56414 | -0.4064 | 9.31237 |
June | 496.00000 | 24.42722 | 33.71170 | -0.2972 | 7.72617 |
July | 497.00000 | 24.53314 | 41.75043 | -0.1966 | 6.83930 |
August | 514.00000 | 24.44460 | 36.74844 | -0.2505 | 7.30454 |
September | 485.00000 | 24.50907 | 26.10285 | -0.3657 | 8.98813 |
October | 502.00000 | 24.35798 | 20.99117 | 0.31421 | 7.63670 |
November | 489.00000 | 24.09938 | 15.97338 | 0.18487 | 5.85893 |
December | 497.00000 | 24.02815 | 13.52700 | 0.14641 | 5.65489 |
Annual Sum or Average | 5943.00000 | 24.23526 | 23.10038 | -0.0150 | 6.98033 |
Minimum of Months | 454.00000 | 23.50227 | 13.52700 | -0.4064 | 5.37501 |
Maximum of Months | 514.00000 | 24.53314 | 41.75043 | 0.31421 | 9.31237 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37812 | 18.32543 | -0.5012 | 12.31210 |
February | 454.00000 | 22.20623 | 19.93603 | -0.2800 | 8.18314 |
March | 514.00000 | 23.14277 | 19.44867 | -0.0425 | 5.88458 |
April | 485.00000 | 23.83532 | 17.72487 | 0.14432 | 5.88633 |
May | 508.00000 | 24.13232 | 22.23879 | -0.6162 | 13.17872 |
June | 496.00000 | 24.20192 | 35.03813 | -0.4870 | 10.27722 |
July | 497.00000 | 24.25060 | 43.77957 | -0.4118 | 8.89271 |
August | 514.00000 | 24.20240 | 38.70513 | -0.4689 | 9.92104 |
September | 485.00000 | 24.07407 | 29.32350 | -0.6156 | 13.39328 |
October | 502.00000 | 23.40630 | 25.20983 | 0.06182 | 5.92415 |
November | 489.00000 | 22.02929 | 19.88699 | -0.3298 | 8.28697 |
December | 497.00000 | 21.53122 | 15.70061 | -0.4775 | 10.63809 |
Annual Sum or Average | 5943.00000 | 23.20783 | 25.50526 | -0.3360 | 9.40533 |
Minimum of Months | 454.00000 | 21.37812 | 15.70061 | -0.6162 | 5.88458 |
Maximum of Months | 514.00000 | 24.25060 | 43.77957 | 0.14432 | 13.39328 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24957 | 19.18169 | -0.8249 | 21.85866 |
February | 454.00000 | 20.53741 | 21.80599 | -0.7207 | 18.86455 |
March | 514.00000 | 21.30829 | 22.05446 | -0.5118 | 12.55864 |
April | 485.00000 | 22.64085 | 19.79055 | -0.1624 | 8.21536 |
May | 508.00000 | 23.83806 | 23.18823 | -0.7320 | 17.08290 |
June | 496.00000 | 24.14718 | 35.05542 | -0.5088 | 10.64321 |
July | 497.00000 | 24.21496 | 43.92749 | -0.4270 | 9.09202 |
August | 514.00000 | 24.04636 | 39.38053 | -0.5357 | 11.60049 |
September | 485.00000 | 23.08577 | 32.62606 | -0.9818 | 27.23527 |
October | 502.00000 | 21.35658 | 29.16460 | -0.4543 | 11.73834 |
November | 489.00000 | 20.35585 | 20.96324 | -0.7812 | 20.11606 |
December | 497.00000 | 20.24971 | 16.25773 | -0.8426 | 22.01289 |
Annual Sum or Average | 5943.00000 | 22.18403 | 27.00649 | -0.6226 | 15.86650 |
Minimum of Months | 454.00000 | 20.24957 | 16.25773 | -0.9818 | 8.21536 |
Maximum of Months | 514.00000 | 24.21496 | 43.92749 | -0.1624 | 27.23527 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.59743 | 18.21189 | -0.7113 | 16.64704 |
February | 454.00000 | 21.05655 | 18.13209 | -0.5702 | 12.97870 |
March | 514.00000 | 22.07780 | 16.69267 | -0.3124 | 8.37433 |
April | 485.00000 | 23.53880 | 15.18378 | 0.06365 | 6.18994 |
May | 508.00000 | 24.38152 | 20.12035 | -0.4630 | 10.23886 |
June | 496.00000 | 24.43839 | 33.03431 | -0.2715 | 7.42902 |
July | 497.00000 | 24.56913 | 41.06824 | -0.1716 | 6.91872 |
August | 514.00000 | 24.37262 | 36.43272 | -0.3115 | 7.99740 |
September | 485.00000 | 24.12279 | 26.56748 | -0.5881 | 13.35113 |
October | 502.00000 | 22.62135 | 22.07292 | -0.1430 | 7.30515 |
November | 489.00000 | 21.00011 | 17.45157 | -0.5888 | 12.71142 |
December | 497.00000 | 20.88516 | 14.29929 | -0.6482 | 14.23318 |
Annual Sum or Average | 5943.00000 | 22.81911 | 23.33306 | -0.3917 | 10.33541 |
Minimum of Months | 454.00000 | 20.59743 | 14.29929 | -0.7113 | 6.18994 |
Maximum of Months | 514.00000 | 24.56913 | 41.06824 | 0.06365 | 16.64704 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.53054 | 18.25898 | -0.7348 | 17.49875 |
February | 454.00000 | 21.26700 | 18.01161 | -0.5218 | 12.28404 |
March | 514.00000 | 22.69890 | 15.85805 | -0.1418 | 7.73311 |
April | 485.00000 | 23.79931 | 14.46479 | 0.17886 | 7.43588 |
May | 508.00000 | 24.49723 | 19.63227 | -0.2685 | 8.64959 |
June | 496.00000 | 24.45056 | 32.75939 | -0.1633 | 6.94959 |
July | 497.00000 | 24.59402 | 40.76024 | -0.0545 | 7.04821 |
August | 514.00000 | 24.39837 | 36.13239 | -0.2084 | 7.27804 |
September | 485.00000 | 24.29204 | 25.97709 | -0.4633 | 11.59652 |
October | 502.00000 | 22.78488 | 21.71808 | -0.0955 | 7.45336 |
November | 489.00000 | 20.82381 | 17.59481 | -0.6424 | 14.17334 |
December | 497.00000 | 20.68350 | 14.43980 | -0.7179 | 16.33799 |
Annual Sum or Average | 5943.00000 | 22.91598 | 23.02596 | -0.3175 | 10.33889 |
Minimum of Months | 454.00000 | 20.53054 | 14.43980 | -0.7348 | 6.94959 |
Maximum of Months | 514.00000 | 24.59402 | 40.76024 | 0.17886 | 17.49875 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.50092 | 18.28905 | -0.7507 | 18.96340 |
February | 454.00000 | 21.68546 | 17.40406 | -0.4154 | 11.89893 |
March | 514.00000 | 22.82922 | 15.21381 | -0.0800 | 8.61328 |
April | 485.00000 | 23.89516 | 14.04625 | 0.25387 | 9.01403 |
May | 508.00000 | 24.42228 | 19.80148 | -0.3423 | 9.66041 |
June | 496.00000 | 24.43457 | 32.82909 | -0.2007 | 7.32459 |
July | 497.00000 | 24.57651 | 40.85948 | -0.0899 | 7.09665 |
August | 514.00000 | 24.41719 | 36.08588 | -0.1864 | 7.65873 |
September | 485.00000 | 24.15913 | 26.19119 | -0.4881 | 12.41268 |
October | 502.00000 | 22.73722 | 21.57132 | -0.0952 | 8.04756 |
November | 489.00000 | 21.03347 | 17.39958 | -0.5956 | 14.19692 |
December | 497.00000 | 20.53367 | 14.57519 | -0.7634 | 18.13106 |
Annual Sum or Average | 5943.00000 | 22.94681 | 22.91710 | -0.3117 | 11.06147 |
Minimum of Months | 454.00000 | 20.50092 | 14.04625 | -0.7634 | 7.09665 |
Maximum of Months | 514.00000 | 24.57651 | 40.85948 | 0.25387 | 18.96340 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.98312 | 17.88400 | -0.5918 | 13.18993 |
February | 454.00000 | 22.22617 | 17.01679 | -0.2755 | 8.22871 |
March | 514.00000 | 23.66045 | 14.49761 | 0.09392 | 6.28745 |
April | 485.00000 | 24.46435 | 13.45022 | 0.41177 | 9.63559 |
May | 508.00000 | 24.46946 | 19.86890 | -0.3626 | 9.32612 |
June | 496.00000 | 24.54186 | 32.70979 | -0.1464 | 7.09770 |
July | 497.00000 | 24.69078 | 40.60220 | -0.0325 | 6.98215 |
August | 514.00000 | 24.54486 | 35.78964 | -0.1274 | 7.13353 |
September | 485.00000 | 24.26218 | 26.14352 | -0.5003 | 11.44442 |
October | 502.00000 | 23.65801 | 20.41670 | 0.11541 | 6.46139 |
November | 489.00000 | 22.52309 | 16.25791 | -0.2138 | 6.80081 |
December | 497.00000 | 22.44685 | 13.38141 | -0.2512 | 7.11051 |
Annual Sum or Average | 5943.00000 | 23.54953 | 22.39620 | -0.1559 | 8.29728 |
Minimum of Months | 454.00000 | 20.98312 | 13.38141 | -0.5918 | 6.28745 |
Maximum of Months | 514.00000 | 24.69078 | 40.60220 | 0.41177 | 13.18993 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92124 | 17.36022 | -0.9937 | 27.91887 |
February | 454.00000 | 20.07143 | 19.61962 | -0.8980 | 24.31522 |
March | 514.00000 | 20.71625 | 19.35170 | -0.6872 | 16.46890 |
April | 485.00000 | 22.21439 | 17.79284 | -0.2664 | 9.29119 |
May | 508.00000 | 23.91720 | 21.42364 | -0.6934 | 15.68077 |
June | 496.00000 | 24.21846 | 33.68951 | -0.4306 | 9.21229 |
July | 497.00000 | 24.34917 | 42.30025 | -0.3436 | 8.07924 |
August | 514.00000 | 23.98822 | 38.27334 | -0.5526 | 12.28978 |
September | 485.00000 | 22.76547 | 30.78415 | -1.0910 | 31.91377 |
October | 502.00000 | 20.97613 | 25.60815 | -0.5669 | 13.75381 |
November | 489.00000 | 19.98821 | 19.30557 | -0.9416 | 25.77220 |
December | 497.00000 | 19.90539 | 14.28726 | -1.0163 | 28.61505 |
Annual Sum or Average | 5943.00000 | 21.93628 | 25.04024 | -0.7049 | 18.52599 |
Minimum of Months | 454.00000 | 19.90539 | 14.28726 | -1.0910 | 8.07924 |
Maximum of Months | 514.00000 | 24.34917 | 42.30025 | -0.2664 | 31.91377 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.74753 | 16.89948 | -1.0436 | 30.08785 |
February | 385.00000 | 20.12793 | 18.99047 | -0.8731 | 23.45523 |
March | 433.00000 | 21.58685 | 17.91548 | -0.4443 | 12.13794 |
April | 410.00000 | 23.18445 | 15.63695 | 0.00657 | 8.30147 |
May | 430.00000 | 24.32560 | 20.02134 | -0.4113 | 11.25026 |
June | 418.00000 | 24.37049 | 32.92353 | -0.2786 | 8.15543 |
July | 422.00000 | 24.57579 | 41.29658 | -0.1572 | 7.75381 |
August | 433.00000 | 24.26030 | 36.79176 | -0.3665 | 9.43356 |
September | 410.00000 | 23.47771 | 28.66439 | -0.8162 | 22.86123 |
October | 427.00000 | 21.38625 | 24.36029 | -0.4614 | 12.29500 |
November | 417.00000 | 19.81633 | 18.98801 | -0.9873 | 27.72046 |
December | 422.00000 | 19.68623 | 13.86746 | -1.0792 | 31.39612 |
Annual Sum or Average | 5034.00000 | 22.22597 | 23.90732 | -0.5738 | 16.99885 |
Minimum of Months | 385.00000 | 19.68623 | 13.86746 | -1.0792 | 7.75381 |
Maximum of Months | 433.00000 | 24.57579 | 41.29658 | 0.00657 | 31.39612 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07131 | 17.32791 | -0.9325 | 25.87755 |
February | 454.00000 | 21.09075 | 18.65741 | -0.5970 | 16.42936 |
March | 514.00000 | 22.29852 | 17.27967 | -0.2109 | 10.86436 |
April | 485.00000 | 23.53652 | 15.37735 | 0.17374 | 9.84737 |
May | 508.00000 | 24.15604 | 20.47149 | -0.4693 | 12.84355 |
June | 496.00000 | 24.30104 | 33.18474 | -0.3081 | 8.56808 |
July | 497.00000 | 24.44762 | 41.74920 | -0.2028 | 7.85151 |
August | 514.00000 | 24.23421 | 37.10107 | -0.3224 | 9.63059 |
September | 485.00000 | 23.65271 | 28.43270 | -0.6871 | 19.13342 |
October | 502.00000 | 22.05299 | 23.93218 | -0.2665 | 10.40562 |
November | 489.00000 | 20.34559 | 18.99380 | -0.8205 | 21.84708 |
December | 497.00000 | 19.94257 | 14.31768 | -0.9992 | 27.94039 |
Annual Sum or Average | 5943.00000 | 22.52426 | 23.96011 | -0.4688 | 15.06129 |
Minimum of Months | 454.00000 | 19.94257 | 14.31768 | -0.9992 | 7.85151 |
Maximum of Months | 514.00000 | 24.44762 | 41.74920 | 0.17374 | 27.94039 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01397 | 17.34167 | -0.9544 | 26.28840 |
February | 454.00000 | 20.28707 | 19.49905 | -0.8185 | 21.32539 |
March | 514.00000 | 21.30677 | 18.69345 | -0.5149 | 12.92258 |
April | 485.00000 | 23.19495 | 16.19848 | 0.03220 | 8.43569 |
May | 508.00000 | 24.14398 | 20.83083 | -0.5404 | 13.00274 |
June | 496.00000 | 24.36975 | 33.27174 | -0.2994 | 8.28423 |
July | 497.00000 | 24.48687 | 41.84766 | -0.2274 | 7.49989 |
August | 514.00000 | 24.22816 | 37.43651 | -0.3925 | 9.60720 |
September | 485.00000 | 23.30936 | 29.44192 | -0.8770 | 24.00276 |
October | 502.00000 | 21.35570 | 25.05486 | -0.4639 | 11.82276 |
November | 489.00000 | 20.15395 | 19.19688 | -0.8765 | 23.03274 |
December | 497.00000 | 20.05290 | 14.29670 | -0.9571 | 26.01516 |
Annual Sum or Average | 5943.00000 | 22.25838 | 24.48223 | -0.5721 | 15.94495 |
Minimum of Months | 454.00000 | 20.01397 | 14.29670 | -0.9571 | 7.49989 |
Maximum of Months | 514.00000 | 24.48687 | 41.84766 | 0.03220 | 26.28840 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68828 | 17.17005 | -1.1202 | 33.27157 |
February | 454.00000 | 19.80356 | 20.19365 | -1.0431 | 30.27446 |
March | 514.00000 | 20.18305 | 20.63336 | -0.8848 | 23.75361 |
April | 485.00000 | 21.29068 | 18.92848 | -0.5160 | 14.46120 |
May | 508.00000 | 23.52198 | 22.18981 | -0.8391 | 21.41163 |
June | 496.00000 | 24.14105 | 33.76831 | -0.4600 | 9.92520 |
July | 497.00000 | 24.27471 | 42.40879 | -0.3722 | 8.54025 |
August | 514.00000 | 23.70112 | 38.99483 | -0.6576 | 15.95913 |
September | 485.00000 | 21.71988 | 33.27004 | -1.4715 | 49.87285 |
October | 502.00000 | 20.18142 | 27.60326 | -0.8231 | 21.89296 |
November | 489.00000 | 19.73034 | 19.14020 | -1.0913 | 32.08368 |
December | 497.00000 | 19.65261 | 14.11157 | -1.1545 | 34.64844 |
Annual Sum or Average | 5943.00000 | 21.50852 | 25.75820 | -0.8670 | 24.56760 |
Minimum of Months | 454.00000 | 19.65261 | 14.11157 | -1.4715 | 8.54025 |
Maximum of Months | 514.00000 | 24.27471 | 42.40879 | -0.3722 | 49.87285 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79286 | 17.16056 | -1.0976 | 32.24758 |
February | 454.00000 | 19.92381 | 20.33816 | -0.9883 | 28.10021 |
March | 514.00000 | 20.88105 | 20.17396 | -0.6539 | 17.71654 |
April | 485.00000 | 22.55632 | 17.17355 | -0.1620 | 10.57572 |
May | 508.00000 | 24.07937 | 20.61741 | -0.4886 | 13.14904 |
June | 496.00000 | 24.25748 | 33.10105 | -0.2958 | 8.41976 |
July | 497.00000 | 24.44448 | 41.50035 | -0.1794 | 7.79581 |
August | 514.00000 | 24.09443 | 37.46040 | -0.4127 | 10.48449 |
September | 485.00000 | 22.73270 | 31.34595 | -1.0931 | 34.28416 |
October | 502.00000 | 20.54156 | 27.28812 | -0.7121 | 19.09539 |
November | 489.00000 | 19.81061 | 19.14305 | -1.0719 | 31.23636 |
December | 497.00000 | 19.75596 | 14.03539 | -1.1370 | 33.82523 |
Annual Sum or Average | 5943.00000 | 21.92409 | 24.99693 | -0.6878 | 20.46108 |
Minimum of Months | 454.00000 | 19.75596 | 14.03539 | -1.1370 | 7.79581 |
Maximum of Months | 514.00000 | 24.44448 | 41.50035 | -0.1620 | 34.28416 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83576 | 17.30275 | -1.0596 | 30.88222 |
February | 454.00000 | 20.42671 | 19.85380 | -0.8171 | 23.13461 |
March | 514.00000 | 21.52345 | 19.07224 | -0.4528 | 15.59713 |
April | 485.00000 | 22.93177 | 16.36095 | -0.0104 | 11.51862 |
May | 508.00000 | 23.86993 | 21.00410 | -0.5827 | 16.94004 |
June | 496.00000 | 24.21777 | 33.26547 | -0.3396 | 9.47147 |
July | 497.00000 | 24.37914 | 41.86012 | -0.2294 | 8.42742 |
August | 514.00000 | 24.07506 | 37.57365 | -0.3897 | 11.61700 |
September | 485.00000 | 22.92124 | 30.54359 | -0.9746 | 30.95134 |
October | 502.00000 | 21.01710 | 26.44138 | -0.5673 | 16.38919 |
November | 489.00000 | 19.93667 | 19.26939 | -0.9986 | 28.72592 |
December | 497.00000 | 19.77193 | 14.19468 | -1.1202 | 33.14409 |
Annual Sum or Average | 5943.00000 | 22.09124 | 24.78371 | -0.6263 | 19.65855 |
Minimum of Months | 454.00000 | 19.77193 | 14.19468 | -1.1202 | 8.42742 |
Maximum of Months | 514.00000 | 24.37914 | 41.86012 | -0.0104 | 33.14409 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83219 | 17.21565 | -1.0704 | 31.12703 |
February | 454.00000 | 19.98600 | 20.31969 | -0.9558 | 26.79590 |
March | 514.00000 | 20.68959 | 20.28842 | -0.7123 | 18.75294 |
April | 485.00000 | 22.48899 | 17.33776 | -0.1635 | 11.25562 |
May | 508.00000 | 23.87235 | 21.41732 | -0.6477 | 16.85757 |
June | 496.00000 | 24.30393 | 33.32665 | -0.3256 | 8.92571 |
July | 497.00000 | 24.43200 | 41.93374 | -0.2502 | 7.87539 |
August | 514.00000 | 24.05773 | 37.95202 | -0.4626 | 11.63537 |
September | 485.00000 | 22.50366 | 31.69465 | -1.1759 | 37.29886 |
October | 502.00000 | 20.55108 | 27.26767 | -0.7032 | 18.15486 |
November | 489.00000 | 19.88347 | 19.32090 | -1.0139 | 28.86803 |
December | 497.00000 | 19.83049 | 14.24907 | -1.0789 | 31.35318 |
Annual Sum or Average | 5943.00000 | 21.88642 | 25.24867 | -0.7109 | 20.64231 |
Minimum of Months | 454.00000 | 19.83049 | 14.24907 | -1.1759 | 7.87539 |
Maximum of Months | 514.00000 | 24.43200 | 41.93374 | -0.1635 | 37.29886 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 40700869.71 | 653.49 | 23-JAN-15:20 | 30.40 | 0.338444E+09 | 0.00 | 0.379145E+09 | 0.34 | 8.41 | 23-JAN-07:40 | 0.00 | 0.00 |
February | 56988275.23 | 1708.65 | 16-FEB-13:30 | 30.19 | 0.473992E+09 | 0.00 | 0.530980E+09 | 0.37 | 8.41 | 06-FEB-16:30 | 0.00 | 0.00 |
March | 0.321514E+09 | 13372.02 | 22-MAR-14:50 | 53.29 | 0.267966E+10 | 0.00 | 0.300117E+10 | 0.60 | 8.43 | 20-MAR-10:20 | 0.00 | 0.00 |
April | 0.744017E+10 | 69096.15 | 21-APR-12:10 | 140.92 | 0.626241E+11 | 0.00 | 0.700643E+11 | 1.64 | 8.68 | 20-APR-10:10 | 0.00 | 0.00 |
May | 0.147092E+11 | 130127.74 | 31-MAY-15:30 | 209.45 | 0.121480E+12 | 0.00 | 0.136189E+12 | 2.34 | 8.68 | 09-MAY-14:10 | 0.00 | 0.00 |
June | 0.549805E+11 | 151347.94 | 29-JUN-17:30 | 400.07 | 0.439981E+12 | 0.00 | 0.494962E+12 | 4.57 | 8.70 | 14-JUN-04:14 | 0.00 | 0.00 |
July | 0.703112E+11 | 156186.14 | 21-JUL-17:20 | 440.16 | 0.545382E+12 | 0.00 | 0.615693E+12 | 4.79 | 8.69 | 11-JUL-05:04 | 0.00 | 0.00 |
August | 0.423465E+11 | 154843.67 | 25-AUG-13:40 | 361.54 | 0.339710E+12 | 0.00 | 0.382057E+12 | 4.01 | 8.68 | 02-AUG-19:30 | 0.00 | 0.00 |
September | 0.605330E+10 | 71714.14 | 18-SEP-16:00 | 138.26 | 0.507905E+11 | 0.00 | 0.568438E+11 | 1.60 | 8.69 | 01-SEP-13:10 | 0.00 | 0.00 |
October | 0.129812E+10 | 44227.99 | 03-OCT-14:40 | 63.65 | 0.109209E+11 | 0.00 | 0.122190E+11 | 0.71 | 8.68 | 03-OCT-15:00 | 0.00 | 0.00 |
November | 87602581.86 | 2117.50 | 07-NOV-08:25 | 41.76 | 0.728907E+09 | 0.00 | 0.816510E+09 | 0.48 | 8.42 | 24-NOV-13:20 | 0.00 | 0.00 |
December | 61205329.81 | 1658.63 | 18-DEC-16:00 | 34.17 | 0.509365E+09 | 0.00 | 0.570570E+09 | 0.38 | 8.41 | 19-DEC-13:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.197707E+12 | 1943.86 | 0.157562E+13 | 0.00 | 0.177333E+13 | 1.83 | 0.00 | 0.00 | ||||
Minimum of Months | 40700869.71 | 653.49 | 30.19 | 0.338444E+09 | 0.00 | 0.379145E+09 | 0.34 | 8.41 | 0.00 | 0.00 | ||
Maximum of Months | 0.703112E+11 | 156186.14 | 440.16 | 0.545382E+12 | 0.00 | 0.615693E+12 | 4.79 | 8.70 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.127339E+09 | 72185.56 | 31-MAY-15:20 | 0.67 | 0.102018E+10 | 0.00 | 0.114752E+10 | 0.01 | 8.64 | 31-MAY-15:10 | 0.00 | 0.00 |
June | 0.761989E+10 | 103519.50 | 20-JUN-13:05 | 29.58 | 0.604023E+11 | 0.00 | 0.680222E+11 | 0.33 | 8.65 | 12-JUN-15:00 | 0.00 | 0.00 |
July | 0.131724E+11 | 110797.20 | 19-JUL-14:05 | 53.08 | 0.105529E+12 | 0.00 | 0.118702E+12 | 0.58 | 8.66 | 31-JUL-17:50 | 0.00 | 0.00 |
August | 0.510368E+10 | 101152.35 | 11-AUG-15:20 | 20.67 | 0.411112E+11 | 0.00 | 0.462149E+11 | 0.22 | 8.65 | 09-AUG-15:50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.260233E+11 | 104.00 | 0.208063E+12 | 0.00 | 0.234086E+12 | 0.10 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131724E+11 | 110797.20 | 53.08 | 0.105529E+12 | 0.00 | 0.118702E+12 | 0.58 | 8.66 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.155622E+09 | 744.00 | 303.04 | 19-JAN-17:10 | 37996.15 | 04-JAN-12:02 | 18.49 | 18.33 | 16.13 |
February | 0.674725E+09 | 672.00 | 1231.78 | 08-FEB-18:50 | 128727.76 | 02-FEB-13:03 | 19.03 | 18.33 | 16.14 |
March | 0.164624E+10 | 744.00 | 3256.30 | 22-MAR-16:30 | 150400.35 | 11-MAR-13:05 | 19.73 | 18.33 | 16.08 |
April | 0.401856E+10 | 720.00 | 7881.99 | 22-APR-14:00 | 296144.52 | 27-APR-21:03 | 20.37 | 18.33 | 16.26 |
May | 0.113974E+11 | 744.00 | 43776.24 | 07-MAY-15:32 | 108314.38 | 01-MAY-21:03 | 19.08 | 18.41 | 16.23 |
June | 0.454366E+11 | 720.00 | 43776.24 | 02-JUN-12:20 | 396766.95 | 30-JUN-12:10 | 20.99 | 19.45 | 16.30 |
July | 0.578077E+11 | 744.00 | 43776.24 | 02-JUL-14:53 | 601950.52 | 29-JUL-18:40 | 23.85 | 20.51 | 16.30 |
August | 0.491303E+11 | 744.00 | 43776.24 | 01-AUG-11:00 | 615833.74 | 23-AUG-16:00 | 23.81 | 19.66 | 16.29 |
September | 0.191926E+10 | 720.00 | 4995.07 | 07-SEP-16:00 | 81944.69 | 08-SEP-10:05 | 18.87 | 18.33 | 16.23 |
October | 0.158085E+10 | 744.00 | 2804.92 | 20-OCT-17:00 | 131370.18 | 04-OCT-09:05 | 19.22 | 18.33 | 16.20 |
November | 0.105046E+10 | 720.00 | 1155.25 | 02-NOV-17:10 | 172389.60 | 18-NOV-12:03 | 19.51 | 18.33 | 16.20 |
December | 0.142058E+10 | 744.00 | 1723.70 | 23-DEC-12:50 | 270306.54 | 18-DEC-10:02 | 19.93 | 18.33 | 16.22 |
Annual Sum or Average | 0.176238E+12 | 8760.00 | 20.25 | 18.73 | 16.22 | ||||
Minimum of Months | 0.155622E+09 | 672.00 | 303.04 | 37996.15 | 18.49 | 18.33 | 16.08 | ||
Maximum of Months | 0.578077E+11 | 744.00 | 43776.24 | 615833.74 | 23.85 | 20.51 | 16.30 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 196560.30 | 18-JAN-15:00 | 20.90 | 20.90 | 0.14 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 196560.33 | 17-FEB-20:40 | 20.84 | 20.83 | 0.14 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 197800.97 | 29-MAR-12:10 | 20.86 | 20.85 | 0.41 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 631738.38 | 21-APR-12:10 | 21.15 | 21.02 | 5.37 |
May | 61845390.86 | 68.38 | 1550.64 | 31-MAY-15:00 | 1003995.33 | 31-MAY-15:30 | 21.36 | 21.10 | 10.24 |
June | 0.135128E+10 | 290.77 | 14485.53 | 20-JUN-12:50 | 1087913.11 | 20-JUN-12:50 | 22.06 | 21.10 | 24.63 |
July | 0.262160E+10 | 329.73 | 14485.53 | 03-JUL-14:50 | 1125713.69 | 21-JUL-17:20 | 22.34 | 21.16 | 26.25 |
August | 0.947166E+09 | 231.77 | 14485.53 | 02-AUG-12:40 | 1130194.05 | 04-AUG-13:30 | 21.86 | 21.13 | 20.14 |
September | 16993957.55 | 38.20 | 470.84 | 18-SEP-16:00 | 662069.72 | 18-SEP-16:00 | 21.31 | 21.20 | 5.58 |
October | 1612124.42 | 6.00 | 153.64 | 03-OCT-14:40 | 437545.91 | 03-OCT-14:40 | 20.98 | 20.95 | 1.24 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 196556.39 | 13-NOV-16:30 | 20.93 | 20.92 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 196479.30 | 08-DEC-15:00 | 20.86 | 20.86 | 0.11 |
Annual Sum or Average | 0.500050E+10 | 964.86 | 21.29 | 21.00 | 7.92 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 196479.30 | 20.84 | 20.83 | 0.11 | ||
Maximum of Months | 0.262160E+10 | 329.73 | 14485.53 | 1130194.05 | 22.34 | 21.20 | 26.25 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 20.90 | 20.90 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.84 | 20.84 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.86 | 20.86 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.15 | 21.15 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 21.36 | 21.36 | 0.00 |
June | 0.442050E+09 | 23.08 | 14485.53 | 29-JUN-10:50 | 1019409.84 | 21-JUN-14:40 | 22.06 | 21.93 | 1.62 |
July | 0.383149E+09 | 42.60 | 14485.53 | 03-JUL-14:50 | 1032279.23 | 20-JUL-12:30 | 22.34 | 22.10 | 2.89 |
August | 0.112798E+09 | 15.08 | 14485.53 | 23-AUG-14:30 | 1026239.47 | 11-AUG-14:30 | 21.86 | 21.77 | 1.03 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 21.31 | 21.31 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 20.98 | 20.98 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.93 | 20.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.86 | 20.86 | 0.00 |
Annual Sum or Average | 0.937997E+09 | 80.77 | 21.29 | 21.25 | 0.47 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 20.84 | 0.00 | ||
Maximum of Months | 0.442050E+09 | 42.60 | 14485.53 | 1032279.23 | 22.34 | 22.10 | 2.89 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.828272E+12 | 0.00 | 603.70 | 2175238.94 | 12-JAN-07:03 | 0.00 | 38.70 | 73.61 | 1.96 | 0.00 | 0.10 | 0.68 | 12-JAN-07:03 |
February | 0.457251E+12 | 0.00 | 525.94 | 2215408.74 | 27-FEB-07:03 | 0.00 | 35.11 | 71.52 | 1.14 | 0.00 | 0.06 | 0.69 | 27-FEB-07:03 |
March | 0.193681E+12 | 0.00 | 525.70 | 1675688.85 | 01-MAR-06:03 | 0.00 | 29.23 | 65.82 | 0.41 | 0.00 | 0.02 | 0.52 | 01-MAR-06:03 |
April | 0.276320E+11 | 0.00 | 264.33 | 1530214.84 | 04-APR-04:01 | 0.00 | 27.64 | 47.29 | 0.05 | 0.00 | 0.00 | 0.48 | 04-APR-04:01 |
May | 0.195665E+10 | 0.00 | 47.26 | 452752.35 | 26-MAY-13:05 | 0.00 | 26.77 | 30.26 | 0.00 | 0.00 | 0.00 | 0.14 | 26-MAY-13:05 |
June | 94751837.73 | 0.00 | 2.67 | 149093.98 | 15-JUN-09:05 | 0.00 | 26.96 | 27.16 | 0.00 | 0.00 | 0.00 | 0.05 | 15-JUN-09:05 |
July | 79217848.94 | 0.00 | 0.92 | 246142.97 | 05-JUL-13:05 | 0.00 | 27.18 | 27.25 | 0.00 | 0.00 | 0.00 | 0.08 | 05-JUL-13:05 |
August | 0.987709E+09 | 0.00 | 23.47 | 288355.39 | 31-AUG-06:10 | 0.00 | 26.64 | 28.39 | 0.00 | 0.00 | 0.00 | 0.09 | 31-AUG-06:10 |
September | 0.871358E+10 | 0.00 | 190.83 | 671254.81 | 30-SEP-05:03 | 0.00 | 26.43 | 41.09 | 0.01 | 0.00 | 0.00 | 0.21 | 30-SEP-05:03 |
October | 0.104705E+12 | 0.00 | 442.09 | 1633055.50 | 30-OCT-05:01 | 0.00 | 28.37 | 59.45 | 0.20 | 0.00 | 0.01 | 0.51 | 30-OCT-05:01 |
November | 0.634830E+12 | 0.00 | 570.22 | 1907416.11 | 27-NOV-07:10 | 0.00 | 38.04 | 72.75 | 1.49 | 0.00 | 0.08 | 0.59 | 27-NOV-07:10 |
December | 0.942883E+12 | 0.00 | 616.66 | 1880191.45 | 15-DEC-07:02 | 0.00 | 40.20 | 74.63 | 2.20 | 0.00 | 0.11 | 0.59 | 15-DEC-07:02 |
Annual Sum or Average | 0.320109E+13 | 0.00 | 3813.80 | 0.00 | 30.92 | 51.49 | 0.62 | 0.00 | 0.03 | ||||
Minimum of Months | 79217848.94 | 0.00 | 0.92 | 149093.98 | 0.00 | 26.43 | 27.16 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.942883E+12 | 0.00 | 616.66 | 2215408.74 | 0.00 | 40.20 | 74.63 | 2.20 | 0.00 | 0.11 | 0.69 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 18.49 | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.03 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.73 | 19.73 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.37 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.08 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.99 | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 23.85 | 23.85 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 23.81 | 23.81 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 18.87 | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.22 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.51 | 19.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 19.93 | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 18.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | 23.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2880324.63 | 0.00 | 21.64 | 2880324.63 | 0.00 | 0.00 | 0.00 | 0.00 | 414.34 | 19-JAN-09:00 | 414.34 | 19-JAN-09:00 | 0.00 | 0.00 | 0.00 |
February | 19796508.85 | 0.00 | 24.00 | 19796508.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6659.75 | 09-FEB-13:30 | 6659.75 | 09-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.514415E+09 | 0.00 | 34.88 | 0.514415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23650.56 | 22-MAR-11:00 | 23650.56 | 22-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.196701E+10 | 0.00 | 51.99 | 0.196701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37613.14 | 13-APR-12:05 | 37613.14 | 13-APR-12:05 | 0.00 | 0.00 | 0.00 |
May | 0.160568E+11 | 0.00 | 186.21 | 0.160568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101671.09 | 31-MAY-16:00 | 101671.09 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.644174E+11 | 0.00 | 388.51 | 0.640922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161644.76 | 30-JUN-12:05 | 142650.32 | 30-JUN-13:05 | 0.00 | 0.00 | 0.00 |
July | 0.844005E+11 | 0.00 | 422.88 | 0.833672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179284.46 | 03-JUL-15:00 | 154183.73 | 23-JUL-14:51 | 0.00 | 0.00 | 0.00 |
August | 0.515766E+11 | 0.00 | 334.55 | 0.514749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146242.41 | 11-AUG-15:40 | 146242.41 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.269883E+10 | 0.00 | 78.29 | 0.269883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41491.19 | 07-SEP-16:00 | 41491.19 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.129479E+10 | 0.00 | 44.49 | 0.129479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47210.00 | 03-OCT-10:50 | 47210.00 | 03-OCT-10:50 | 0.00 | 0.00 | 0.00 |
November | 14688228.62 | 0.00 | 33.11 | 14688228.62 | 0.00 | 0.00 | 0.00 | 0.00 | 5847.81 | 01-NOV-07:10 | 5847.81 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 6597022.99 | 0.00 | 22.87 | 6597022.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2816.83 | 27-DEC-08:20 | 2816.83 | 27-DEC-08:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222970E+12 | 0.00 | 1643.41 | 0.221510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2880324.63 | 0.00 | 21.64 | 2880324.63 | 0.00 | 0.00 | 0.00 | 0.00 | 414.34 | 414.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.844005E+11 | 0.00 | 422.88 | 0.833672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179284.46 | 154183.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2403088.68 | 0.00 | 2.87 | 2403088.68 | 0.00 | 0.00 | 0.00 | 0.00 | 446.44 | 19-JAN-13:40 | 446.44 | 19-JAN-13:40 | 0.00 | 0.00 | 0.00 |
February | 23373261.01 | 0.00 | 11.21 | 23373261.01 | 0.00 | 0.00 | 0.00 | 0.00 | 7307.05 | 17-FEB-13:10 | 7307.05 | 17-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 0.135499E+10 | 0.00 | 30.04 | 0.135499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114449.85 | 22-MAR-14:40 | 114449.85 | 22-MAR-14:40 | 0.00 | 0.00 | 0.00 |
April | 0.568710E+11 | 0.00 | 114.87 | 0.568710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 538978.38 | 20-APR-13:20 | 538978.38 | 20-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.957058E+11 | 0.00 | 169.20 | 0.957058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 767862.05 | 31-MAY-16:00 | 767862.05 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.391172E+12 | 0.00 | 337.88 | 0.390176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1188159.25 | 30-JUN-12:05 | 1094374.40 | 29-JUN-14:05 | 0.00 | 0.00 | 0.00 |
July | 0.500169E+12 | 0.00 | 356.45 | 0.498830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1205932.35 | 23-JUL-15:01 | 1205932.35 | 23-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.297696E+12 | 0.00 | 284.58 | 0.297696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1101584.98 | 11-AUG-15:40 | 1101584.98 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.445951E+11 | 0.00 | 110.44 | 0.445951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 547763.42 | 18-SEP-15:50 | 547763.42 | 18-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.869322E+10 | 0.00 | 45.44 | 0.869322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 365735.35 | 03-OCT-14:40 | 365735.35 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 |
November | 3156778.28 | 0.00 | 4.79 | 3156778.28 | 0.00 | 0.00 | 0.00 | 0.00 | 770.48 | 02-NOV-07:40 | 770.48 | 02-NOV-07:40 | 0.00 | 0.00 | 0.00 |
December | 380445.70 | 0.00 | 1.50 | 380445.70 | 0.00 | 0.00 | 0.00 | 0.00 | 358.89 | 23-DEC-11:30 | 358.89 | 23-DEC-11:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139629E+13 | 0.00 | 1469.27 | 0.139395E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 380445.70 | 0.00 | 1.50 | 380445.70 | 0.00 | 0.00 | 0.00 | 0.00 | 358.89 | 358.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.500169E+12 | 0.00 | 356.45 | 0.498830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1205932.35 | 1205932.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 |
February | 227935.96 | 0.00 | 1.58 | 227935.96 | 0.00 | 0.00 | 0.00 | 0.00 | 149.30 | 15-FEB-13:50 | 149.30 | 15-FEB-13:50 | 0.00 | 0.00 | 0.00 |
March | 14509425.32 | 0.00 | 19.94 | 14509425.32 | 0.00 | 0.00 | 0.00 | 0.00 | 868.43 | 27-MAR-13:10 | 868.43 | 27-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.229881E+10 | 0.00 | 92.53 | 0.229881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66365.37 | 21-APR-15:20 | 66365.37 | 21-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.912880E+10 | 0.00 | 165.33 | 0.912880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82058.34 | 31-MAY-16:00 | 82058.34 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.403024E+11 | 0.00 | 333.24 | 0.401918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128033.62 | 30-JUN-12:30 | 122951.12 | 29-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.516559E+11 | 0.00 | 353.16 | 0.515368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125836.19 | 21-JUL-14:40 | 125836.19 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.284005E+11 | 0.00 | 276.46 | 0.284005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119171.17 | 11-AUG-15:40 | 119171.17 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.219633E+10 | 0.00 | 97.65 | 0.219633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51822.87 | 08-SEP-15:40 | 51822.87 | 08-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.123207E+09 | 0.00 | 27.72 | 0.123207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13068.06 | 03-OCT-14:40 | 13068.06 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 2084.26 | 0.00 | 0.19 | 2084.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 23-DEC-13:09 | 4.99 | 23-DEC-13:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134121E+12 | 0.00 | 1367.80 | 0.133891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.516559E+11 | 0.00 | 353.16 | 0.515368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128033.62 | 125836.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 95023544.09 | 0.00 | 19.64 | 95023544.09 | 0.00 | 0.00 | 0.00 | 0.00 | 21365.07 | 06-JAN-15:20 | 21365.07 | 06-JAN-15:20 | 0.00 | 0.00 | 0.00 |
February | 0.176569E+09 | 0.00 | 18.42 | 0.176569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16199.96 | 06-FEB-07:15 | 16199.96 | 06-FEB-07:15 | 0.00 | 0.00 | 0.00 |
March | 0.250971E+09 | 0.00 | 25.45 | 0.250971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19042.11 | 28-MAR-06:15 | 19042.11 | 28-MAR-06:15 | 0.00 | 0.00 | 0.00 |
April | 0.286377E+09 | 0.00 | 16.21 | 0.286377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21699.96 | 11-APR-06:16 | 21699.96 | 11-APR-06:16 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 |
September | 990763.83 | 0.00 | 0.02 | 990763.83 | 0.00 | 0.00 | 0.00 | 0.00 | 14861.46 | 29-SEP-06:18 | 14861.46 | 29-SEP-06:18 | 0.00 | 0.00 | 0.00 |
October | 0.203951E+09 | 0.00 | 21.10 | 0.203951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20347.68 | 26-OCT-06:15 | 20347.68 | 26-OCT-06:15 | 0.00 | 0.00 | 0.00 |
November | 0.279328E+09 | 0.00 | 32.35 | 0.279328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18831.10 | 07-NOV-08:25 | 18831.10 | 07-NOV-08:25 | 0.00 | 0.00 | 0.00 |
December | 0.157178E+09 | 0.00 | 23.50 | 0.157178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20821.80 | 18-DEC-15:07 | 20821.80 | 18-DEC-15:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145039E+10 | 0.00 | 156.69 | 0.145039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.286377E+09 | 0.00 | 32.35 | 0.286377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21699.96 | 21699.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.628578E+10 | 0.425695E+10 | 744.00 | 0.588073E+10 | 0.405056E+09 | 0.00 | 0.02 | 19-JAN-05:01 | 0.01 | 12-JAN-08:10 | 2788.00 | 19-JAN-05:01 | 2630.89 | 19-JAN-05:01 | 173.06 | 26-JAN-22:02 | 2048.07 | 19-JAN-12:50 | 0.00 |
February | 0.107547E+11 | 0.521378E+10 | 672.00 | 0.975606E+10 | 0.998612E+09 | 0.00 | 0.02 | 10-FEB-16:00 | 0.02 | 27-FEB-08:10 | 5434.64 | 10-FEB-16:00 | 5057.97 | 10-FEB-16:00 | 441.58 | 14-FEB-00:10 | 2918.88 | 08-FEB-21:30 | 0.00 |
March | 0.145508E+11 | 0.673696E+10 | 744.00 | 0.141015E+11 | 0.449358E+09 | 0.00 | 0.03 | 28-MAR-18:25 | 0.02 | 19-MAR-12:55 | 6071.99 | 21-MAR-17:40 | 5495.09 | 31-MAR-23:10 | 801.80 | 21-MAR-17:30 | 3216.78 | 28-MAR-18:25 | 0.00 |
April | 0.159083E+11 | 0.738948E+10 | 720.00 | 0.158348E+11 | 73498636.41 | 0.00 | 0.21 | 22-APR-14:00 | 0.02 | 30-APR-23:50 | 69249.47 | 22-APR-14:00 | 69249.47 | 22-APR-14:00 | 714.63 | 30-APR-08:00 | 20982.98 | 22-APR-14:00 | 0.00 |
May | 0.947786E+10 | 0.509932E+10 | 744.00 | 0.914381E+10 | 0.334053E+09 | 0.00 | 0.02 | 31-MAY-16:00 | 0.01 | 16-MAY-20:00 | 4932.37 | 30-MAY-11:40 | 4890.33 | 14-MAY-14:11 | 414.72 | 31-MAY-23:20 | 2609.69 | 31-MAY-16:00 | 0.00 |
June | 0.504746E+11 | 0.175283E+11 | 592.22 | 0.471371E+11 | 0.333755E+10 | 0.00 | 0.56 | 30-JUN-13:30 | 0.00 | 10-JUN-01:55 | 253768.72 | 30-JUN-12:00 | 226685.96 | 30-JUN-15:00 | 70441.23 | 30-JUN-12:00 | 73746.24 | 30-JUN-13:30 | 0.00 |
July | 0.208737E+12 | 0.606206E+11 | 522.46 | 0.173893E+12 | 0.348448E+11 | 0.00 | 0.83 | 29-JUL-18:23 | 0.00 | 04-JUL-03:05 | 388599.99 | 29-JUL-18:23 | 321589.41 | 21-JUL-14:30 | 131272.84 | 03-JUL-15:00 | 111427.90 | 29-JUL-18:30 | 0.00 |
August | 0.257326E+12 | 0.699681E+11 | 615.31 | 0.199416E+12 | 0.579107E+11 | 0.00 | 0.86 | 11-AUG-17:00 | 0.00 | 18-AUG-00:45 | 376357.14 | 23-AUG-16:00 | 371067.07 | 11-AUG-16:00 | 129785.15 | 03-AUG-15:00 | 112267.32 | 11-AUG-17:00 | 0.00 |
September | 0.514245E+10 | 0.388497E+10 | 708.03 | 0.478197E+10 | 0.360480E+09 | 0.00 | 0.02 | 07-SEP-15:50 | 0.00 | 03-SEP-15:30 | 4916.31 | 07-SEP-15:50 | 4864.57 | 07-SEP-16:00 | 426.60 | 30-SEP-24:00 | 2249.65 | 07-SEP-15:50 | 0.00 |
October | 0.122857E+11 | 0.588162E+10 | 744.00 | 0.112551E+11 | 0.103059E+10 | 0.00 | 0.03 | 31-OCT-23:10 | 0.01 | 02-OCT-11:00 | 5866.14 | 31-OCT-23:10 | 5289.39 | 31-OCT-23:10 | 576.75 | 31-OCT-23:10 | 3045.01 | 06-OCT-13:40 | 0.00 |
November | 0.145349E+11 | 0.658927E+10 | 720.00 | 0.136412E+11 | 0.893772E+09 | 0.00 | 0.03 | 04-NOV-13:50 | 0.03 | 01-NOV-03:15 | 6088.34 | 27-NOV-05:41 | 5299.33 | 04-NOV-17:25 | 818.19 | 27-NOV-05:45 | 3205.98 | 08-NOV-07:15 | 0.00 |
December | 0.147821E+11 | 0.704759E+10 | 744.00 | 0.146783E+11 | 0.103784E+09 | 0.00 | 0.03 | 19-DEC-13:01 | 0.03 | 01-DEC-01:05 | 6295.96 | 01-DEC-00:10 | 5512.20 | 24-DEC-22:43 | 804.91 | 01-DEC-00:10 | 3392.09 | 19-DEC-13:01 | 0.00 |
Annual Sum or Average | 0.620261E+12 | 0.200217E+12 | 8270.01 | 0.519519E+12 | 0.100742E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.514245E+10 | 0.388497E+10 | 522.46 | 0.478197E+10 | 73498636.41 | 0.00 | 0.02 | 0.00 | 2788.00 | 2630.89 | 173.06 | 2048.07 | 0.00 | ||||||
Maximum of Months | 0.257326E+12 | 0.699681E+11 | 744.00 | 0.199416E+12 | 0.579107E+11 | 0.00 | 0.86 | 0.03 | 388599.99 | 371067.07 | 131272.84 | 112267.32 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.177807E+10 | 0.500595E+09 | 715.16 | 0.177807E+10 | 0.00 | 0.00 | 0.18 | 22-JAN-15:20 | 0.00 | 02-JAN-07:05 | 1315.71 | 22-JAN-15:20 | 1315.71 | 22-JAN-15:20 | 0.00 | 02-JAN-05:23 | 344.29 | 22-JAN-15:20 | 0.00 |
February | 0.719100E+10 | 0.177268E+10 | 672.00 | 0.719100E+10 | -0.0 | 0.00 | 0.47 | 20-FEB-16:03 | 0.23 | 27-FEB-07:03 | 3686.82 | 12-FEB-15:45 | 3686.82 | 12-FEB-15:45 | 0.00 | 08-FEB-17:50 | 886.21 | 20-FEB-16:03 | 0.00 |
March | 0.141657E+11 | 0.328143E+10 | 744.00 | 0.141657E+11 | -0.0 | 0.00 | 0.88 | 31-MAR-23:50 | 0.49 | 01-MAR-07:03 | 7424.07 | 31-MAR-24:00 | 7424.07 | 31-MAR-24:00 | 0.00 | 15-MAR-03:15 | 1669.99 | 31-MAR-23:50 | 0.00 |
April | 0.198204E+11 | 0.430679E+10 | 720.00 | 0.198204E+11 | 0.00 | 0.00 | 1.00 | 01-APR-17:55 | 0.32 | 30-APR-24:00 | 9035.76 | 22-APR-19:00 | 9035.76 | 22-APR-19:00 | 0.00 | 10-APR-04:12 | 1906.49 | 22-APR-19:00 | 0.00 |
May | 0.594982E+10 | 0.142234E+10 | 744.00 | 0.594964E+10 | 176779.08 | 0.00 | 0.48 | 31-MAY-24:00 | 0.19 | 27-MAY-07:00 | 4136.85 | 31-MAY-24:00 | 4136.85 | 31-MAY-24:00 | 19.69 | 16-MAY-16:10 | 917.55 | 31-MAY-24:00 | 0.00 |
June | 0.109895E+11 | 0.249986E+10 | 720.00 | 0.109117E+11 | 77762932.17 | 0.00 | 0.66 | 30-JUN-24:00 | 0.44 | 01-JUN-06:10 | 6055.30 | 30-JUN-24:00 | 6047.81 | 30-JUN-24:00 | 247.62 | 27-JUN-16:00 | 1414.22 | 30-JUN-15:00 | 0.00 |
July | 0.165958E+11 | 0.372832E+10 | 744.00 | 0.164327E+11 | 0.163165E+09 | 0.00 | 0.85 | 31-JUL-23:10 | 0.63 | 05-JUL-21:00 | 8032.87 | 31-JUL-23:50 | 8004.29 | 31-JUL-23:53 | 344.73 | 26-JUL-15:00 | 2033.12 | 29-JUL-17:00 | 0.00 |
August | 0.213925E+11 | 0.453870E+10 | 744.00 | 0.212580E+11 | 0.134448E+09 | 0.00 | 0.98 | 27-AUG-18:22 | 0.33 | 31-AUG-23:53 | 9246.27 | 27-AUG-19:00 | 9245.36 | 27-AUG-18:57 | 274.85 | 03-AUG-14:00 | 2338.00 | 11-AUG-18:00 | 0.00 |
September | 0.532941E+10 | 0.125946E+10 | 720.00 | 0.531252E+10 | 16887125.78 | 0.00 | 0.45 | 30-SEP-24:00 | 0.14 | 30-SEP-07:00 | 3633.55 | 30-SEP-24:00 | 3633.55 | 30-SEP-24:00 | 99.48 | 05-SEP-15:40 | 858.97 | 30-SEP-24:00 | 0.00 |
October | 0.941389E+10 | 0.220851E+10 | 744.00 | 0.941363E+10 | 262836.20 | 0.00 | 0.64 | 31-OCT-24:00 | 0.32 | 30-OCT-06:10 | 5197.37 | 31-OCT-24:00 | 5197.37 | 31-OCT-24:00 | 41.78 | 02-OCT-16:10 | 1211.76 | 31-OCT-24:00 | 0.00 |
November | 0.127836E+11 | 0.302190E+10 | 720.00 | 0.127836E+11 | -0.0 | 0.00 | 0.69 | 19-NOV-15:23 | 0.51 | 29-NOV-07:02 | 5615.42 | 19-NOV-15:27 | 5615.42 | 19-NOV-15:27 | 0.00 | 27-NOV-12:10 | 1309.44 | 19-NOV-15:23 | 0.00 |
December | 0.180901E+11 | 0.413939E+10 | 744.00 | 0.180901E+11 | -0.0 | 0.00 | 0.86 | 23-DEC-05:12 | 0.72 | 15-DEC-07:02 | 7423.46 | 24-DEC-18:00 | 7423.46 | 24-DEC-18:00 | 0.00 | 31-DEC-16:03 | 1633.95 | 23-DEC-05:12 | 0.00 |
Annual Sum or Average | 0.143500E+12 | 0.326800E+11 | 8731.16 | 0.143107E+12 | 0.392703E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.177807E+10 | 0.500595E+09 | 672.00 | 0.177807E+10 | -0.0 | 0.00 | 0.18 | 0.00 | 1315.71 | 1315.71 | 0.00 | 344.29 | 0.00 | ||||||
Maximum of Months | 0.213925E+11 | 0.453870E+10 | 744.00 | 0.212580E+11 | 0.163165E+09 | 0.00 | 1.00 | 0.72 | 9246.27 | 9245.36 | 344.73 | 2338.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.584588E+09 | 0.223732E+09 | 111.46 | 0.584588E+09 | 0.00 | 0.00 | 0.09 | 27-JAN-22:04 | 0.00 | 01-JAN-00:02 | 5793.77 | 27-JAN-22:04 | 5793.77 | 27-JAN-22:04 | 0.00 | 20-JAN-06:15 | 1655.97 | 27-JAN-22:04 | 0.00 |
February | 0.437132E+11 | 0.111795E+11 | 672.00 | 0.437132E+11 | -0.0 | 0.00 | 0.40 | 16-FEB-16:15 | 0.03 | 27-FEB-07:03 | 30432.10 | 16-FEB-16:15 | 30432.10 | 16-FEB-16:15 | 0.00 | 03-FEB-04:30 | 7686.07 | 17-FEB-15:25 | 0.00 |
March | 0.113760E+12 | 0.269069E+11 | 744.00 | 0.113760E+12 | -0.0 | 0.00 | 0.82 | 31-MAR-23:20 | 0.36 | 01-MAR-07:03 | 65940.52 | 31-MAR-23:20 | 65940.52 | 31-MAR-23:20 | 0.00 | 22-MAR-13:00 | 15004.27 | 31-MAR-23:20 | 0.00 |
April | 0.179719E+12 | 0.393561E+11 | 720.00 | 0.179719E+12 | -0.0 | 0.00 | 0.99 | 22-APR-18:50 | 0.26 | 30-APR-24:00 | 86199.90 | 22-APR-18:50 | 86199.90 | 22-APR-18:50 | 0.00 | 01-APR-06:30 | 18240.35 | 22-APR-18:50 | 0.00 |
May | 0.500133E+11 | 0.121015E+11 | 744.00 | 0.500114E+11 | 1954280.41 | 0.00 | 0.46 | 31-MAY-24:00 | 0.13 | 27-MAY-07:00 | 37947.47 | 31-MAY-24:00 | 37947.47 | 31-MAY-24:00 | 210.40 | 16-MAY-16:10 | 8458.39 | 31-MAY-24:00 | 0.00 |
June | 0.100927E+12 | 0.230820E+11 | 720.00 | 0.100157E+12 | 0.769844E+09 | 0.00 | 0.65 | 30-JUN-23:40 | 0.41 | 02-JUN-06:10 | 56840.74 | 30-JUN-23:20 | 56719.84 | 30-JUN-24:00 | 2459.14 | 27-JUN-16:00 | 13325.68 | 30-JUN-15:00 | 0.00 |
July | 0.154102E+12 | 0.347881E+11 | 744.00 | 0.152486E+12 | 0.161578E+10 | 0.00 | 0.84 | 31-JUL-23:10 | 0.60 | 06-JUL-06:10 | 76150.82 | 31-JUL-23:10 | 75846.08 | 31-JUL-23:40 | 3403.98 | 26-JUL-15:00 | 19089.87 | 21-JUL-16:00 | 0.00 |
August | 0.199099E+12 | 0.424570E+11 | 744.00 | 0.197762E+12 | 0.133654E+10 | 0.00 | 0.94 | 10-AUG-19:00 | 0.25 | 31-AUG-23:53 | 84521.92 | 27-AUG-18:47 | 84521.92 | 27-AUG-18:47 | 2726.58 | 03-AUG-14:00 | 22121.56 | 11-AUG-18:00 | 0.00 |
September | 0.395391E+11 | 0.953798E+10 | 720.00 | 0.393776E+11 | 0.161558E+09 | 0.00 | 0.39 | 30-SEP-23:40 | 0.06 | 30-SEP-07:00 | 29520.40 | 30-SEP-23:40 | 29520.40 | 30-SEP-23:40 | 973.26 | 05-SEP-15:40 | 7092.49 | 30-SEP-23:40 | 0.00 |
October | 0.690329E+11 | 0.165747E+11 | 744.00 | 0.690300E+11 | 2898818.92 | 0.00 | 0.53 | 31-OCT-23:20 | 0.15 | 30-OCT-06:10 | 40279.54 | 31-OCT-23:20 | 40279.54 | 31-OCT-23:20 | 469.19 | 02-OCT-16:10 | 9618.98 | 31-OCT-23:20 | 0.00 |
November | 0.911688E+11 | 0.222571E+11 | 720.00 | 0.911688E+11 | -0.0 | 0.00 | 0.59 | 08-NOV-15:50 | 0.32 | 27-NOV-07:02 | 45938.45 | 08-NOV-15:50 | 45938.45 | 08-NOV-15:50 | 0.00 | 02-NOV-04:47 | 10944.31 | 08-NOV-14:15 | 0.00 |
December | 0.137505E+12 | 0.324326E+11 | 744.00 | 0.137505E+12 | 0.00 | 0.00 | 0.76 | 22-DEC-22:02 | 0.57 | 04-DEC-07:10 | 59743.66 | 29-DEC-22:02 | 59743.66 | 29-DEC-22:02 | 0.00 | 04-DEC-05:09 | 13807.47 | 22-DEC-22:02 | 0.00 |
Annual Sum or Average | 0.117916E+13 | 0.270897E+12 | 8127.46 | 0.117527E+13 | 0.388857E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.584588E+09 | 0.223732E+09 | 111.46 | 0.584588E+09 | -0.0 | 0.00 | 0.09 | 0.00 | 5793.77 | 5793.77 | 0.00 | 1655.97 | 0.00 | ||||||
Maximum of Months | 0.199099E+12 | 0.424570E+11 | 744.00 | 0.197762E+12 | 0.161578E+10 | 0.00 | 0.99 | 0.60 | 86199.90 | 86199.90 | 3403.98 | 22121.56 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.238560E+10 | 0.627269E+09 | 567.60 | 0.238560E+10 | 0.00 | 0.00 | 0.33 | 09-FEB-16:00 | 0.00 | 01-FEB-00:03 | 2633.17 | 09-FEB-16:00 | 2633.17 | 09-FEB-16:00 | 0.00 | 09-FEB-20:40 | 618.63 | 09-FEB-16:00 | 0.00 |
March | 0.905063E+10 | 0.218372E+10 | 744.00 | 0.905063E+10 | -0.0 | 0.00 | 0.71 | 31-MAR-23:10 | 0.22 | 06-MAR-04:01 | 5654.36 | 31-MAR-23:10 | 5654.36 | 31-MAR-23:10 | 0.00 | 22-MAR-04:04 | 1313.73 | 31-MAR-23:10 | 0.00 |
April | 0.164887E+11 | 0.364917E+10 | 720.00 | 0.164887E+11 | -0.0 | 0.00 | 0.98 | 22-APR-18:50 | 0.19 | 30-APR-24:00 | 8514.95 | 22-APR-18:50 | 8514.95 | 22-APR-18:50 | 0.00 | 06-APR-04:20 | 1807.46 | 22-APR-18:50 | 0.00 |
May | 0.447053E+10 | 0.108978E+10 | 743.86 | 0.447035E+10 | 182967.55 | 0.00 | 0.45 | 31-MAY-23:50 | 0.00 | 28-MAY-07:35 | 3732.25 | 31-MAY-23:50 | 3732.25 | 31-MAY-23:50 | 20.35 | 16-MAY-16:10 | 833.92 | 31-MAY-23:50 | 0.00 |
June | 0.995794E+10 | 0.228371E+10 | 720.00 | 0.988102E+10 | 76927620.94 | 0.00 | 0.64 | 30-JUN-23:20 | 0.37 | 25-JUN-05:00 | 5653.51 | 30-JUN-23:20 | 5633.26 | 30-JUN-23:40 | 246.07 | 27-JUN-16:00 | 1350.49 | 30-JUN-15:00 | 0.00 |
July | 0.152998E+11 | 0.346324E+10 | 744.00 | 0.151383E+11 | 0.161485E+09 | 0.00 | 0.83 | 31-JUL-23:10 | 0.57 | 06-JUL-06:10 | 7583.68 | 31-JUL-23:10 | 7549.19 | 31-JUL-23:15 | 340.25 | 26-JUL-15:00 | 1935.16 | 29-JUL-17:00 | 0.00 |
August | 0.196083E+11 | 0.419690E+10 | 744.00 | 0.194748E+11 | 0.133518E+09 | 0.00 | 0.93 | 27-AUG-18:31 | 0.21 | 31-AUG-23:53 | 8504.15 | 27-AUG-18:32 | 8504.15 | 27-AUG-18:32 | 272.66 | 03-AUG-14:00 | 2226.11 | 11-AUG-18:00 | 0.00 |
September | 0.261764E+10 | 0.646616E+09 | 681.00 | 0.260224E+10 | 15393510.95 | 0.00 | 0.33 | 02-SEP-18:10 | 0.00 | 23-SEP-02:55 | 2665.75 | 02-SEP-18:10 | 2665.75 | 02-SEP-18:10 | 99.27 | 05-SEP-15:50 | 606.12 | 02-SEP-18:10 | 0.00 |
October | 0.439408E+10 | 0.108619E+10 | 726.89 | 0.439382E+10 | 264334.08 | 0.00 | 0.43 | 31-OCT-23:10 | 0.00 | 10-OCT-00:25 | 3552.50 | 03-OCT-16:00 | 3552.50 | 03-OCT-16:00 | 38.32 | 02-OCT-16:00 | 793.31 | 31-OCT-23:10 | 0.00 |
November | 0.681833E+10 | 0.170669E+10 | 720.00 | 0.681833E+10 | 0.00 | 0.00 | 0.53 | 08-NOV-15:50 | 0.17 | 27-NOV-04:00 | 4056.74 | 08-NOV-15:50 | 4056.74 | 08-NOV-15:50 | 0.00 | 04-NOV-10:08 | 970.14 | 08-NOV-15:50 | 0.00 |
December | 0.116313E+11 | 0.279619E+10 | 744.00 | 0.116313E+11 | -0.0 | 0.00 | 0.69 | 20-DEC-22:02 | 0.42 | 26-DEC-03:50 | 5581.67 | 19-DEC-22:05 | 5581.67 | 19-DEC-22:05 | 0.00 | 08-DEC-04:00 | 1278.13 | 20-DEC-22:02 | 0.00 |
Annual Sum or Average | 0.102723E+12 | 0.237295E+11 | 7855.35 | 0.102335E+12 | 0.387772E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.196083E+11 | 0.419690E+10 | 744.00 | 0.194748E+11 | 0.161485E+09 | 0.00 | 0.98 | 0.57 | 8514.95 | 8514.95 | 340.25 | 2226.11 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 0.00 | 14.19 | 0.00 | 1132.21 | 0.00 | 0.00 | 0.00 |
February | 62.74 | 0.00 | 62.74 | 0.00 | 1031.73 | 0.00 | 0.00 | 0.00 |
March | 167.81 | 0.00 | 167.81 | 8.24 | 787.97 | 0.00 | 0.00 | 0.00 |
April | 303.22 | 6.28 | 296.94 | 103.81 | 434.93 | 0.00 | 0.00 | 0.00 |
May | 463.88 | 72.52 | 391.37 | 337.26 | 190.76 | 0.00 | 0.00 | 0.00 |
June | 606.16 | 134.03 | 472.13 | 585.15 | 89.26 | 0.00 | 0.00 | 0.00 |
July | 508.57 | 81.82 | 426.75 | 498.59 | 109.06 | 0.00 | 0.00 | 0.00 |
August | 324.73 | 17.53 | 307.20 | 249.48 | 184.92 | 0.00 | 0.00 | 0.00 |
September | 181.51 | 0.16 | 181.35 | 53.90 | 389.92 | 0.00 | 0.00 | 0.00 |
October | 88.33 | 0.00 | 88.33 | 2.76 | 694.10 | 0.00 | 0.00 | 0.00 |
November | 27.41 | 0.00 | 27.41 | 0.00 | 1131.20 | 0.00 | 0.00 | 0.00 |
December | 4.31 | 0.00 | 4.31 | 0.00 | 1208.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 230.22 | 26.14 | 204.08 | 154.17 | 613.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.31 | 0.00 | 4.31 | 0.00 | 89.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 606.16 | 134.03 | 472.13 | 585.15 | 1208.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 0.00 | 14.19 | 0.00 | 1132.21 | 0.00 | 0.00 | 0.00 |
February | 62.74 | 0.00 | 62.74 | 0.00 | 1031.73 | 0.00 | 0.00 | 0.00 |
March | 167.81 | 0.00 | 167.81 | 8.24 | 787.97 | 0.00 | 0.00 | 0.00 |
April | 303.22 | 6.28 | 296.94 | 103.81 | 434.93 | 0.00 | 0.00 | 0.00 |
May | 463.88 | 72.52 | 391.37 | 337.26 | 190.76 | 0.00 | 0.00 | 0.00 |
June | 606.16 | 134.03 | 472.13 | 585.15 | 89.26 | 0.00 | 0.00 | 0.00 |
July | 508.57 | 81.82 | 426.75 | 498.59 | 109.06 | 0.00 | 0.00 | 0.00 |
August | 324.73 | 17.53 | 307.20 | 249.48 | 184.92 | 0.00 | 0.00 | 0.00 |
September | 181.51 | 0.16 | 181.35 | 53.90 | 389.92 | 0.00 | 0.00 | 0.00 |
October | 88.33 | 0.00 | 88.33 | 2.76 | 694.10 | 0.00 | 0.00 | 0.00 |
November | 27.41 | 0.00 | 27.41 | 0.00 | 1131.20 | 0.00 | 0.00 | 0.00 |
December | 4.31 | 0.00 | 4.31 | 0.00 | 1208.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 230.22 | 26.14 | 204.08 | 154.17 | 613.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.31 | 0.00 | 4.31 | 0.00 | 89.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 606.16 | 134.03 | 472.13 | 585.15 | 1208.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 0.00 | 14.19 | 0.00 | 1132.21 | 0.00 | 0.00 | 0.00 |
February | 62.74 | 0.00 | 62.74 | 0.00 | 1031.73 | 0.00 | 0.00 | 0.00 |
March | 167.81 | 0.00 | 167.81 | 8.24 | 787.97 | 0.00 | 0.00 | 0.00 |
April | 303.22 | 6.28 | 296.94 | 103.81 | 434.93 | 0.00 | 0.00 | 0.00 |
May | 463.88 | 72.52 | 391.37 | 337.26 | 190.76 | 0.00 | 0.00 | 0.00 |
June | 606.16 | 134.03 | 472.13 | 585.15 | 89.26 | 0.00 | 0.00 | 0.00 |
July | 508.57 | 81.82 | 426.75 | 498.59 | 109.06 | 0.00 | 0.00 | 0.00 |
August | 324.73 | 17.53 | 307.20 | 249.48 | 184.92 | 0.00 | 0.00 | 0.00 |
September | 181.51 | 0.16 | 181.35 | 53.90 | 389.92 | 0.00 | 0.00 | 0.00 |
October | 88.33 | 0.00 | 88.33 | 2.76 | 694.10 | 0.00 | 0.00 | 0.00 |
November | 27.41 | 0.00 | 27.41 | 0.00 | 1131.20 | 0.00 | 0.00 | 0.00 |
December | 4.31 | 0.00 | 4.31 | 0.00 | 1208.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 230.22 | 26.14 | 204.08 | 154.17 | 613.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.31 | 0.00 | 4.31 | 0.00 | 89.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 606.16 | 134.03 | 472.13 | 585.15 | 1208.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 0.00 | 14.19 | 0.00 | 1132.21 | 0.00 | 0.00 | 0.00 |
February | 62.74 | 0.00 | 62.74 | 0.00 | 1031.73 | 0.00 | 0.00 | 0.00 |
March | 167.81 | 0.00 | 167.81 | 8.24 | 787.97 | 0.00 | 0.00 | 0.00 |
April | 303.22 | 6.28 | 296.94 | 103.81 | 434.93 | 0.00 | 0.00 | 0.00 |
May | 463.88 | 72.52 | 391.37 | 337.26 | 190.76 | 0.00 | 0.00 | 0.00 |
June | 606.16 | 134.03 | 472.13 | 585.15 | 89.26 | 0.00 | 0.00 | 0.00 |
July | 508.57 | 81.82 | 426.75 | 498.59 | 109.06 | 0.00 | 0.00 | 0.00 |
August | 324.73 | 17.53 | 307.20 | 249.48 | 184.92 | 0.00 | 0.00 | 0.00 |
September | 181.51 | 0.16 | 181.35 | 53.90 | 389.92 | 0.00 | 0.00 | 0.00 |
October | 88.33 | 0.00 | 88.33 | 2.76 | 694.10 | 0.00 | 0.00 | 0.00 |
November | 27.41 | 0.00 | 27.41 | 0.00 | 1131.20 | 0.00 | 0.00 | 0.00 |
December | 4.31 | 0.00 | 4.31 | 0.00 | 1208.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 230.22 | 26.14 | 204.08 | 154.17 | 613.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.31 | 0.00 | 4.31 | 0.00 | 89.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 606.16 | 134.03 | 472.13 | 585.15 | 1208.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 0.00 | 14.19 | 0.00 | 1132.17 | 0.00 | 0.00 | 0.00 |
February | 62.74 | 0.00 | 62.74 | 0.00 | 1031.69 | 0.00 | 0.00 | 0.00 |
March | 167.81 | 0.00 | 167.81 | 8.24 | 787.94 | 0.00 | 0.00 | 0.00 |
April | 303.21 | 6.28 | 296.93 | 103.81 | 434.92 | 0.00 | 0.00 | 0.00 |
May | 463.86 | 72.51 | 391.35 | 337.25 | 190.75 | 0.00 | 0.00 | 0.00 |
June | 606.13 | 134.02 | 472.11 | 585.12 | 89.26 | 0.00 | 0.00 | 0.00 |
July | 508.55 | 81.82 | 426.73 | 498.57 | 109.05 | 0.00 | 0.00 | 0.00 |
August | 324.71 | 17.53 | 307.19 | 249.47 | 184.92 | 0.00 | 0.00 | 0.00 |
September | 181.50 | 0.16 | 181.34 | 53.90 | 389.91 | 0.00 | 0.00 | 0.00 |
October | 88.33 | 0.00 | 88.33 | 2.76 | 694.07 | 0.00 | 0.00 | 0.00 |
November | 27.41 | 0.00 | 27.41 | 0.00 | 1131.15 | 0.00 | 0.00 | 0.00 |
December | 4.31 | 0.00 | 4.31 | 0.00 | 1208.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 230.22 | 26.14 | 204.07 | 154.16 | 613.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.31 | 0.00 | 4.31 | 0.00 | 89.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 606.13 | 134.02 | 472.11 | 585.12 | 1208.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.16 | 12.69 | 28.47 | 3.34 | 1216.29 | 0.00 | 0.00 | 0.00 |
February | 228.98 | 108.97 | 120.01 | 114.63 | 1033.97 | 0.00 | 0.00 | 0.00 |
March | 655.58 | 332.41 | 323.17 | 543.05 | 778.12 | 0.00 | 0.00 | 0.00 |
April | 901.58 | 456.90 | 444.68 | 823.90 | 433.26 | 0.00 | 0.00 | 0.00 |
May | 1311.59 | 740.19 | 571.40 | 1439.31 | 229.79 | 0.00 | 0.00 | 0.00 |
June | 1205.60 | 563.13 | 642.47 | 1371.27 | 113.94 | 0.00 | 0.00 | 0.00 |
July | 1145.42 | 556.16 | 589.25 | 1334.97 | 129.73 | 0.00 | 0.00 | 0.00 |
August | 906.99 | 442.13 | 464.86 | 1006.58 | 203.62 | 0.00 | 0.00 | 0.00 |
September | 560.59 | 245.82 | 314.77 | 506.80 | 400.08 | 0.00 | 0.00 | 0.00 |
October | 295.56 | 118.51 | 177.05 | 200.39 | 694.28 | 0.00 | 0.00 | 0.00 |
November | 62.40 | 21.48 | 40.92 | 4.22 | 1200.72 | 0.00 | 0.00 | 0.00 |
December | 8.87 | 2.04 | 6.84 | 0.00 | 1319.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 612.70 | 301.37 | 311.34 | 615.76 | 644.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.87 | 2.04 | 6.84 | 0.00 | 113.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1311.59 | 740.19 | 642.47 | 1439.31 | 1319.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.16 | 12.69 | 28.47 | 3.34 | 1216.29 | 0.00 | 0.00 | 0.00 |
February | 228.98 | 108.97 | 120.01 | 114.63 | 1033.97 | 0.00 | 0.00 | 0.00 |
March | 655.58 | 332.41 | 323.17 | 543.05 | 778.12 | 0.00 | 0.00 | 0.00 |
April | 901.58 | 456.90 | 444.68 | 823.90 | 433.26 | 0.00 | 0.00 | 0.00 |
May | 1311.59 | 740.19 | 571.40 | 1439.31 | 229.79 | 0.00 | 0.00 | 0.00 |
June | 1205.60 | 563.13 | 642.47 | 1371.27 | 113.94 | 0.00 | 0.00 | 0.00 |
July | 1145.42 | 556.16 | 589.25 | 1334.97 | 129.73 | 0.00 | 0.00 | 0.00 |
August | 906.99 | 442.13 | 464.86 | 1006.58 | 203.62 | 0.00 | 0.00 | 0.00 |
September | 560.59 | 245.82 | 314.77 | 506.80 | 400.08 | 0.00 | 0.00 | 0.00 |
October | 295.56 | 118.51 | 177.05 | 200.39 | 694.28 | 0.00 | 0.00 | 0.00 |
November | 62.40 | 21.48 | 40.92 | 4.22 | 1200.72 | 0.00 | 0.00 | 0.00 |
December | 8.87 | 2.04 | 6.84 | 0.00 | 1319.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 612.70 | 301.37 | 311.34 | 615.76 | 644.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.87 | 2.04 | 6.84 | 0.00 | 113.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1311.59 | 740.19 | 642.47 | 1439.31 | 1319.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.16 | 12.69 | 28.47 | 3.34 | 1216.26 | 0.00 | 0.00 | 0.00 |
February | 228.97 | 108.96 | 120.01 | 114.63 | 1033.95 | 0.00 | 0.00 | 0.00 |
March | 655.57 | 332.40 | 323.17 | 543.04 | 778.10 | 0.00 | 0.00 | 0.00 |
April | 901.56 | 456.89 | 444.67 | 823.89 | 433.25 | 0.00 | 0.00 | 0.00 |
May | 1311.56 | 740.17 | 571.39 | 1439.29 | 229.79 | 0.00 | 0.00 | 0.00 |
June | 1205.58 | 563.12 | 642.46 | 1371.25 | 113.94 | 0.00 | 0.00 | 0.00 |
July | 1145.40 | 556.15 | 589.24 | 1334.94 | 129.73 | 0.00 | 0.00 | 0.00 |
August | 906.97 | 442.12 | 464.85 | 1006.56 | 203.62 | 0.00 | 0.00 | 0.00 |
September | 560.58 | 245.81 | 314.76 | 506.79 | 400.08 | 0.00 | 0.00 | 0.00 |
October | 295.56 | 118.51 | 177.05 | 200.39 | 694.27 | 0.00 | 0.00 | 0.00 |
November | 62.40 | 21.48 | 40.92 | 4.22 | 1200.70 | 0.00 | 0.00 | 0.00 |
December | 8.87 | 2.04 | 6.84 | 0.00 | 1319.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 612.69 | 301.36 | 311.33 | 615.75 | 644.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.87 | 2.04 | 6.84 | 0.00 | 113.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1311.56 | 740.17 | 642.46 | 1439.29 | 1319.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.49 | 113.40 | 58.09 | 98.24 | 1000.03 | 0.00 | 0.00 | 0.00 |
February | 589.83 | 411.47 | 178.36 | 495.13 | 820.08 | 0.00 | 0.00 | 0.00 |
March | 1010.45 | 686.26 | 324.19 | 989.55 | 641.36 | 0.00 | 0.00 | 0.00 |
April | 1229.78 | 765.89 | 463.89 | 1352.49 | 427.46 | 0.00 | 0.00 | 0.00 |
May | 1010.33 | 522.60 | 487.73 | 1143.26 | 238.51 | 0.00 | 0.00 | 0.00 |
June | 921.32 | 375.93 | 545.39 | 1072.13 | 128.86 | 0.00 | 0.00 | 0.00 |
July | 888.48 | 385.84 | 502.65 | 1057.86 | 137.03 | 0.00 | 0.00 | 0.00 |
August | 922.87 | 508.94 | 413.93 | 1083.00 | 201.99 | 0.00 | 0.00 | 0.00 |
September | 747.48 | 451.06 | 296.42 | 788.47 | 353.80 | 0.00 | 0.00 | 0.00 |
October | 539.40 | 343.26 | 196.13 | 483.93 | 560.93 | 0.00 | 0.00 | 0.00 |
November | 289.81 | 203.00 | 86.81 | 186.53 | 949.92 | 0.00 | 0.00 | 0.00 |
December | 51.47 | 36.39 | 15.07 | 8.59 | 1124.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.52 | 399.71 | 297.81 | 730.55 | 547.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.47 | 36.39 | 15.07 | 8.59 | 128.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.78 | 765.89 | 545.39 | 1352.49 | 1124.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.49 | 113.40 | 58.09 | 98.24 | 1000.03 | 0.00 | 0.00 | 0.00 |
February | 589.83 | 411.47 | 178.36 | 495.13 | 820.08 | 0.00 | 0.00 | 0.00 |
March | 1010.45 | 686.26 | 324.19 | 989.55 | 641.36 | 0.00 | 0.00 | 0.00 |
April | 1229.78 | 765.89 | 463.89 | 1352.49 | 427.46 | 0.00 | 0.00 | 0.00 |
May | 1010.33 | 522.60 | 487.73 | 1143.26 | 238.51 | 0.00 | 0.00 | 0.00 |
June | 921.32 | 375.93 | 545.39 | 1072.13 | 128.86 | 0.00 | 0.00 | 0.00 |
July | 888.48 | 385.84 | 502.64 | 1057.86 | 137.03 | 0.00 | 0.00 | 0.00 |
August | 922.86 | 508.94 | 413.93 | 1082.99 | 201.99 | 0.00 | 0.00 | 0.00 |
September | 747.48 | 451.06 | 296.42 | 788.46 | 353.80 | 0.00 | 0.00 | 0.00 |
October | 539.40 | 343.26 | 196.13 | 483.93 | 560.93 | 0.00 | 0.00 | 0.00 |
November | 289.81 | 203.00 | 86.81 | 186.53 | 949.92 | 0.00 | 0.00 | 0.00 |
December | 51.47 | 36.39 | 15.07 | 8.59 | 1124.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.52 | 399.71 | 297.81 | 730.55 | 547.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.47 | 36.39 | 15.07 | 8.59 | 128.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.78 | 765.89 | 545.39 | 1352.49 | 1124.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.49 | 113.40 | 58.09 | 98.24 | 1000.03 | 0.00 | 0.00 | 0.00 |
February | 589.83 | 411.47 | 178.36 | 495.13 | 820.08 | 0.00 | 0.00 | 0.00 |
March | 1010.45 | 686.26 | 324.19 | 989.55 | 641.36 | 0.00 | 0.00 | 0.00 |
April | 1229.78 | 765.89 | 463.89 | 1352.49 | 427.46 | 0.00 | 0.00 | 0.00 |
May | 1010.33 | 522.60 | 487.73 | 1143.26 | 238.51 | 0.00 | 0.00 | 0.00 |
June | 921.32 | 375.93 | 545.39 | 1072.13 | 128.86 | 0.00 | 0.00 | 0.00 |
July | 888.48 | 385.84 | 502.65 | 1057.86 | 137.03 | 0.00 | 0.00 | 0.00 |
August | 922.87 | 508.94 | 413.93 | 1083.00 | 201.99 | 0.00 | 0.00 | 0.00 |
September | 747.48 | 451.06 | 296.42 | 788.47 | 353.80 | 0.00 | 0.00 | 0.00 |
October | 539.40 | 343.26 | 196.13 | 483.93 | 560.93 | 0.00 | 0.00 | 0.00 |
November | 289.81 | 203.00 | 86.81 | 186.53 | 949.92 | 0.00 | 0.00 | 0.00 |
December | 51.47 | 36.39 | 15.07 | 8.59 | 1124.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.52 | 399.71 | 297.81 | 730.55 | 547.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.47 | 36.39 | 15.07 | 8.59 | 128.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.78 | 765.89 | 545.39 | 1352.49 | 1124.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.49 | 113.40 | 58.09 | 98.24 | 1000.03 | 0.00 | 0.00 | 0.00 |
February | 589.83 | 411.47 | 178.36 | 495.13 | 820.08 | 0.00 | 0.00 | 0.00 |
March | 1010.45 | 686.26 | 324.19 | 989.55 | 641.36 | 0.00 | 0.00 | 0.00 |
April | 1229.78 | 765.89 | 463.89 | 1352.49 | 427.46 | 0.00 | 0.00 | 0.00 |
May | 1010.33 | 522.60 | 487.73 | 1143.26 | 238.51 | 0.00 | 0.00 | 0.00 |
June | 921.32 | 375.93 | 545.39 | 1072.13 | 128.86 | 0.00 | 0.00 | 0.00 |
July | 888.48 | 385.84 | 502.64 | 1057.86 | 137.03 | 0.00 | 0.00 | 0.00 |
August | 922.86 | 508.94 | 413.93 | 1082.99 | 201.99 | 0.00 | 0.00 | 0.00 |
September | 747.48 | 451.06 | 296.42 | 788.46 | 353.80 | 0.00 | 0.00 | 0.00 |
October | 539.40 | 343.26 | 196.13 | 483.93 | 560.93 | 0.00 | 0.00 | 0.00 |
November | 289.81 | 203.00 | 86.81 | 186.53 | 949.92 | 0.00 | 0.00 | 0.00 |
December | 51.47 | 36.39 | 15.07 | 8.59 | 1124.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.52 | 399.71 | 297.81 | 730.55 | 547.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.47 | 36.39 | 15.07 | 8.59 | 128.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.78 | 765.89 | 545.39 | 1352.49 | 1124.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.48 | 113.39 | 58.09 | 98.24 | 999.99 | 0.00 | 0.00 | 0.00 |
February | 589.81 | 411.45 | 178.36 | 495.11 | 820.04 | 0.00 | 0.00 | 0.00 |
March | 1010.41 | 686.23 | 324.18 | 989.51 | 641.33 | 0.00 | 0.00 | 0.00 |
April | 1229.73 | 765.86 | 463.87 | 1352.44 | 427.44 | 0.00 | 0.00 | 0.00 |
May | 1010.29 | 522.58 | 487.71 | 1143.22 | 238.50 | 0.00 | 0.00 | 0.00 |
June | 921.28 | 375.92 | 545.36 | 1072.09 | 128.85 | 0.00 | 0.00 | 0.00 |
July | 888.45 | 385.82 | 502.62 | 1057.82 | 137.02 | 0.00 | 0.00 | 0.00 |
August | 922.83 | 508.92 | 413.91 | 1082.95 | 201.98 | 0.00 | 0.00 | 0.00 |
September | 747.45 | 451.04 | 296.41 | 788.43 | 353.79 | 0.00 | 0.00 | 0.00 |
October | 539.38 | 343.25 | 196.13 | 483.91 | 560.91 | 0.00 | 0.00 | 0.00 |
November | 289.79 | 202.99 | 86.81 | 186.53 | 949.88 | 0.00 | 0.00 | 0.00 |
December | 51.46 | 36.39 | 15.07 | 8.59 | 1124.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.49 | 399.70 | 297.80 | 730.52 | 547.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.46 | 36.39 | 15.07 | 8.59 | 128.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1229.73 | 765.86 | 545.36 | 1352.44 | 1124.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.68 | 3.73 | 17.95 | 0.00 | 1271.04 | 0.00 | 0.00 | 0.00 |
February | 128.34 | 44.19 | 84.15 | 21.16 | 1125.82 | 0.00 | 0.00 | 0.00 |
March | 386.80 | 166.04 | 220.76 | 204.17 | 857.99 | 0.00 | 0.00 | 0.00 |
April | 920.52 | 477.83 | 442.69 | 859.52 | 509.69 | 0.00 | 0.00 | 0.00 |
May | 895.17 | 408.61 | 486.56 | 902.09 | 250.02 | 0.00 | 0.00 | 0.00 |
June | 980.87 | 419.20 | 561.67 | 1080.61 | 139.15 | 0.00 | 0.00 | 0.00 |
July | 820.34 | 310.98 | 509.36 | 903.92 | 153.76 | 0.00 | 0.00 | 0.00 |
August | 674.11 | 285.90 | 388.22 | 697.26 | 232.72 | 0.00 | 0.00 | 0.00 |
September | 407.72 | 170.86 | 236.86 | 318.34 | 416.95 | 0.00 | 0.00 | 0.00 |
October | 159.10 | 47.48 | 111.61 | 49.13 | 771.35 | 0.00 | 0.00 | 0.00 |
November | 63.38 | 22.73 | 40.65 | 4.84 | 1271.20 | 0.00 | 0.00 | 0.00 |
December | 5.69 | 0.56 | 5.13 | 0.00 | 1409.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 456.49 | 196.93 | 259.56 | 421.77 | 698.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.69 | 0.56 | 5.13 | 0.00 | 139.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 980.87 | 477.83 | 561.67 | 1080.61 | 1409.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.68 | 3.73 | 17.95 | 0.00 | 1271.04 | 0.00 | 0.00 | 0.00 |
February | 128.34 | 44.19 | 84.15 | 21.16 | 1125.82 | 0.00 | 0.00 | 0.00 |
March | 386.80 | 166.04 | 220.76 | 204.17 | 857.99 | 0.00 | 0.00 | 0.00 |
April | 920.52 | 477.83 | 442.69 | 859.52 | 509.69 | 0.00 | 0.00 | 0.00 |
May | 895.17 | 408.61 | 486.56 | 902.09 | 250.02 | 0.00 | 0.00 | 0.00 |
June | 980.87 | 419.20 | 561.67 | 1080.61 | 139.15 | 0.00 | 0.00 | 0.00 |
July | 820.34 | 310.98 | 509.36 | 903.92 | 153.76 | 0.00 | 0.00 | 0.00 |
August | 674.11 | 285.90 | 388.22 | 697.26 | 232.72 | 0.00 | 0.00 | 0.00 |
September | 407.72 | 170.86 | 236.86 | 318.34 | 416.95 | 0.00 | 0.00 | 0.00 |
October | 159.10 | 47.48 | 111.61 | 49.13 | 771.35 | 0.00 | 0.00 | 0.00 |
November | 63.38 | 22.73 | 40.65 | 4.84 | 1271.20 | 0.00 | 0.00 | 0.00 |
December | 5.69 | 0.56 | 5.13 | 0.00 | 1409.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 456.49 | 196.93 | 259.56 | 421.77 | 698.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.69 | 0.56 | 5.13 | 0.00 | 139.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 980.87 | 477.83 | 561.67 | 1080.61 | 1409.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.68 | 3.73 | 17.95 | 0.00 | 1271.02 | 0.00 | 0.00 | 0.00 |
February | 128.33 | 44.19 | 84.15 | 21.16 | 1125.80 | 0.00 | 0.00 | 0.00 |
March | 386.79 | 166.04 | 220.76 | 204.17 | 857.97 | 0.00 | 0.00 | 0.00 |
April | 920.50 | 477.82 | 442.69 | 859.50 | 509.68 | 0.00 | 0.00 | 0.00 |
May | 895.16 | 408.60 | 486.55 | 902.07 | 250.01 | 0.00 | 0.00 | 0.00 |
June | 980.85 | 419.19 | 561.66 | 1080.59 | 139.15 | 0.00 | 0.00 | 0.00 |
July | 820.32 | 310.97 | 509.35 | 903.90 | 153.75 | 0.00 | 0.00 | 0.00 |
August | 674.10 | 285.89 | 388.21 | 697.25 | 232.71 | 0.00 | 0.00 | 0.00 |
September | 407.71 | 170.85 | 236.86 | 318.34 | 416.94 | 0.00 | 0.00 | 0.00 |
October | 159.09 | 47.48 | 111.61 | 49.13 | 771.34 | 0.00 | 0.00 | 0.00 |
November | 63.38 | 22.73 | 40.65 | 4.84 | 1271.18 | 0.00 | 0.00 | 0.00 |
December | 5.69 | 0.56 | 5.13 | 0.00 | 1409.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 456.48 | 196.92 | 259.56 | 421.76 | 698.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.69 | 0.56 | 5.13 | 0.00 | 139.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 980.85 | 477.82 | 561.66 | 1080.59 | 1409.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.97 | 0.00 | 70.97 | 0.00 | 5405.12 | 0.00 | 0.00 | 0.00 |
February | 313.72 | 0.00 | 313.72 | 0.00 | 4873.31 | 0.00 | 0.00 | 0.00 |
March | 839.06 | 0.00 | 839.06 | 59.48 | 3670.47 | 0.00 | 0.00 | 0.00 |
April | 1516.07 | 31.40 | 1484.67 | 574.75 | 1991.95 | 0.00 | 0.00 | 0.00 |
May | 2319.39 | 362.58 | 1956.80 | 1761.64 | 877.12 | 0.00 | 0.00 | 0.00 |
June | 3030.74 | 670.13 | 2360.62 | 2987.71 | 404.53 | 0.00 | 0.00 | 0.00 |
July | 2542.82 | 409.11 | 2133.71 | 2561.61 | 493.62 | 0.00 | 0.00 | 0.00 |
August | 1623.61 | 87.63 | 1535.98 | 1316.15 | 826.52 | 0.00 | 0.00 | 0.00 |
September | 907.52 | 0.80 | 906.72 | 315.56 | 1719.01 | 0.00 | 0.00 | 0.00 |
October | 441.64 | 0.00 | 441.64 | 22.76 | 3162.59 | 0.00 | 0.00 | 0.00 |
November | 137.06 | 0.00 | 137.06 | 0.00 | 5313.61 | 0.00 | 0.00 | 0.00 |
December | 21.53 | 0.00 | 21.53 | 0.00 | 5697.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1151.11 | 130.71 | 1020.40 | 804.69 | 2858.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.53 | 0.00 | 21.53 | 0.00 | 404.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3030.74 | 670.13 | 2360.62 | 2987.71 | 5697.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.47 | 38.06 | 85.41 | 10.88 | 3478.02 | 0.00 | 0.00 | 0.00 |
February | 686.92 | 326.89 | 360.03 | 359.12 | 2943.58 | 0.00 | 0.00 | 0.00 |
March | 1966.71 | 997.21 | 969.50 | 1644.49 | 2232.60 | 0.00 | 0.00 | 0.00 |
April | 2704.71 | 1370.69 | 1334.03 | 2474.35 | 1245.74 | 0.00 | 0.00 | 0.00 |
May | 3934.72 | 2220.54 | 1714.18 | 4323.24 | 642.87 | 0.00 | 0.00 | 0.00 |
June | 3616.76 | 1689.38 | 1927.38 | 4124.88 | 313.14 | 0.00 | 0.00 | 0.00 |
July | 3436.22 | 1668.47 | 1767.75 | 4016.74 | 360.09 | 0.00 | 0.00 | 0.00 |
August | 2720.95 | 1326.38 | 1394.57 | 3033.69 | 565.47 | 0.00 | 0.00 | 0.00 |
September | 1681.75 | 737.45 | 944.30 | 1540.75 | 1095.46 | 0.00 | 0.00 | 0.00 |
October | 886.67 | 355.52 | 531.15 | 617.31 | 1938.86 | 0.00 | 0.00 | 0.00 |
November | 187.21 | 64.45 | 122.76 | 14.72 | 3396.14 | 0.00 | 0.00 | 0.00 |
December | 26.62 | 6.11 | 20.51 | 0.00 | 3748.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1838.09 | 904.09 | 934.00 | 1856.80 | 1824.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.62 | 6.11 | 20.51 | 0.00 | 313.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3934.72 | 2220.54 | 1927.38 | 4323.24 | 3748.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 857.44 | 566.97 | 290.47 | 499.69 | 4866.10 | 0.00 | 0.00 | 0.00 |
February | 2949.12 | 2057.31 | 891.80 | 2497.60 | 3989.00 | 0.00 | 0.00 | 0.00 |
March | 5052.18 | 3431.26 | 1620.92 | 4948.78 | 3141.21 | 0.00 | 0.00 | 0.00 |
April | 6148.81 | 3829.41 | 2319.40 | 6738.49 | 2096.11 | 0.00 | 0.00 | 0.00 |
May | 5051.58 | 2612.97 | 2438.61 | 5711.73 | 1134.66 | 0.00 | 0.00 | 0.00 |
June | 4606.55 | 1879.65 | 2726.90 | 5368.91 | 600.69 | 0.00 | 0.00 | 0.00 |
July | 4442.36 | 1929.17 | 2513.20 | 5304.89 | 640.57 | 0.00 | 0.00 | 0.00 |
August | 4614.27 | 2544.65 | 2069.62 | 5426.39 | 948.37 | 0.00 | 0.00 | 0.00 |
September | 3737.36 | 2255.27 | 1482.08 | 3952.37 | 1685.50 | 0.00 | 0.00 | 0.00 |
October | 2696.96 | 1716.30 | 980.66 | 2433.05 | 2715.12 | 0.00 | 0.00 | 0.00 |
November | 1449.01 | 1014.97 | 434.04 | 956.87 | 4573.50 | 0.00 | 0.00 | 0.00 |
December | 257.33 | 181.97 | 75.36 | 44.98 | 5418.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3487.57 | 1998.54 | 1489.03 | 3659.96 | 2644.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.33 | 181.97 | 75.36 | 44.98 | 600.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6148.81 | 3829.41 | 2726.90 | 6738.49 | 5418.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.05 | 11.19 | 53.86 | 0.00 | 3591.72 | 0.00 | 0.00 | 0.00 |
February | 385.01 | 132.56 | 252.45 | 74.80 | 3093.72 | 0.00 | 0.00 | 0.00 |
March | 1160.39 | 498.11 | 662.28 | 646.73 | 2297.07 | 0.00 | 0.00 | 0.00 |
April | 2761.53 | 1433.46 | 1328.07 | 2624.45 | 1372.04 | 0.00 | 0.00 | 0.00 |
May | 2685.49 | 1225.82 | 1459.66 | 2723.75 | 706.92 | 0.00 | 0.00 | 0.00 |
June | 2942.57 | 1257.58 | 1684.99 | 3265.25 | 383.61 | 0.00 | 0.00 | 0.00 |
July | 2460.98 | 932.92 | 1528.07 | 2749.83 | 415.09 | 0.00 | 0.00 | 0.00 |
August | 2022.32 | 857.68 | 1164.64 | 2135.14 | 618.49 | 0.00 | 0.00 | 0.00 |
September | 1223.14 | 512.57 | 710.57 | 980.68 | 1139.93 | 0.00 | 0.00 | 0.00 |
October | 477.28 | 142.45 | 334.84 | 164.19 | 2041.33 | 0.00 | 0.00 | 0.00 |
November | 190.14 | 68.18 | 121.96 | 19.01 | 3443.18 | 0.00 | 0.00 | 0.00 |
December | 17.08 | 1.69 | 15.39 | 0.00 | 3828.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1369.45 | 590.77 | 778.68 | 1287.08 | 1904.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.08 | 1.69 | 15.39 | 0.00 | 383.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2942.57 | 1433.46 | 1684.99 | 3265.25 | 3828.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.97 | 0.00 | 70.97 | 0.00 | 5286.18 | 0.00 | 0.00 | 0.00 |
February | 313.72 | 0.00 | 313.72 | 0.00 | 4723.46 | 0.00 | 0.00 | 0.00 |
March | 839.06 | 0.00 | 839.06 | 74.36 | 3488.38 | 0.00 | 0.00 | 0.00 |
April | 1516.07 | 31.40 | 1484.67 | 632.26 | 1844.81 | 0.00 | 0.00 | 0.00 |
May | 2319.39 | 362.58 | 1956.80 | 1803.99 | 839.10 | 0.00 | 0.00 | 0.00 |
June | 3030.74 | 670.13 | 2360.62 | 2988.44 | 395.12 | 0.00 | 0.00 | 0.00 |
July | 2542.82 | 409.11 | 2133.71 | 2560.80 | 484.18 | 0.00 | 0.00 | 0.00 |
August | 1623.61 | 87.63 | 1535.98 | 1334.26 | 794.49 | 0.00 | 0.00 | 0.00 |
September | 907.52 | 0.80 | 906.72 | 362.24 | 1559.35 | 0.00 | 0.00 | 0.00 |
October | 441.64 | 0.00 | 441.64 | 38.49 | 2932.25 | 0.00 | 0.00 | 0.00 |
November | 137.06 | 0.00 | 137.06 | 0.00 | 5159.30 | 0.00 | 0.00 | 0.00 |
December | 21.53 | 0.00 | 21.53 | 0.00 | 5566.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1151.11 | 130.71 | 1020.40 | 820.98 | 2745.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.53 | 0.00 | 21.53 | 0.00 | 395.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3030.74 | 670.13 | 2360.62 | 2988.44 | 5566.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.47 | 38.06 | 85.41 | 10.69 | 3423.52 | 0.00 | 0.00 | 0.00 |
February | 686.92 | 326.89 | 360.03 | 370.02 | 2853.49 | 0.00 | 0.00 | 0.00 |
March | 1966.71 | 997.21 | 969.50 | 1681.05 | 2107.78 | 0.00 | 0.00 | 0.00 |
April | 2704.71 | 1370.69 | 1334.03 | 2518.01 | 1165.11 | 0.00 | 0.00 | 0.00 |
May | 3934.72 | 2220.54 | 1714.18 | 4340.69 | 621.07 | 0.00 | 0.00 | 0.00 |
June | 3616.76 | 1689.38 | 1927.38 | 4127.10 | 307.62 | 0.00 | 0.00 | 0.00 |
July | 3436.22 | 1668.47 | 1767.75 | 4017.22 | 354.70 | 0.00 | 0.00 | 0.00 |
August | 2720.95 | 1326.38 | 1394.57 | 3042.24 | 549.04 | 0.00 | 0.00 | 0.00 |
September | 1681.75 | 737.45 | 944.30 | 1577.25 | 1007.98 | 0.00 | 0.00 | 0.00 |
October | 886.67 | 355.52 | 531.15 | 646.84 | 1790.22 | 0.00 | 0.00 | 0.00 |
November | 187.21 | 64.45 | 122.76 | 15.39 | 3314.60 | 0.00 | 0.00 | 0.00 |
December | 26.62 | 6.11 | 20.51 | 0.00 | 3692.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1838.09 | 904.09 | 934.00 | 1872.31 | 1760.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.62 | 6.11 | 20.51 | 0.00 | 307.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3934.72 | 2220.54 | 1927.38 | 4340.69 | 3692.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 857.44 | 566.97 | 290.47 | 510.35 | 4755.20 | 0.00 | 0.00 | 0.00 |
February | 2949.12 | 2057.31 | 891.80 | 2540.47 | 3830.32 | 0.00 | 0.00 | 0.00 |
March | 5052.18 | 3431.26 | 1620.92 | 5005.49 | 2969.61 | 0.00 | 0.00 | 0.00 |
April | 6148.81 | 3829.41 | 2319.40 | 6780.40 | 1973.64 | 0.00 | 0.00 | 0.00 |
May | 5051.58 | 2612.97 | 2438.61 | 5723.40 | 1087.79 | 0.00 | 0.00 | 0.00 |
June | 4606.55 | 1879.65 | 2726.90 | 5362.57 | 587.72 | 0.00 | 0.00 | 0.00 |
July | 4442.36 | 1929.17 | 2513.20 | 5297.22 | 628.96 | 0.00 | 0.00 | 0.00 |
August | 4614.27 | 2544.65 | 2069.62 | 5427.90 | 920.03 | 0.00 | 0.00 | 0.00 |
September | 3737.36 | 2255.27 | 1482.08 | 3996.90 | 1564.24 | 0.00 | 0.00 | 0.00 |
October | 2696.96 | 1716.30 | 980.66 | 2497.80 | 2507.86 | 0.00 | 0.00 | 0.00 |
November | 1449.01 | 1014.97 | 434.04 | 979.83 | 4420.30 | 0.00 | 0.00 | 0.00 |
December | 257.33 | 181.97 | 75.36 | 46.02 | 5296.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3487.57 | 1998.54 | 1489.03 | 3683.50 | 2539.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.33 | 181.97 | 75.36 | 46.02 | 587.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6148.81 | 3829.41 | 2726.90 | 6780.40 | 5296.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.05 | 11.19 | 53.86 | 0.00 | 3513.88 | 0.00 | 0.00 | 0.00 |
February | 385.01 | 132.56 | 252.45 | 78.50 | 3003.37 | 0.00 | 0.00 | 0.00 |
March | 1160.39 | 498.11 | 662.28 | 664.23 | 2188.48 | 0.00 | 0.00 | 0.00 |
April | 2761.53 | 1433.46 | 1328.07 | 2652.46 | 1292.39 | 0.00 | 0.00 | 0.00 |
May | 2685.49 | 1225.82 | 1459.66 | 2732.61 | 679.06 | 0.00 | 0.00 | 0.00 |
June | 2942.57 | 1257.58 | 1684.99 | 3260.52 | 375.48 | 0.00 | 0.00 | 0.00 |
July | 2460.98 | 932.92 | 1528.07 | 2744.74 | 407.28 | 0.00 | 0.00 | 0.00 |
August | 2022.32 | 857.68 | 1164.64 | 2137.44 | 599.61 | 0.00 | 0.00 | 0.00 |
September | 1223.14 | 512.57 | 710.57 | 1005.75 | 1056.72 | 0.00 | 0.00 | 0.00 |
October | 477.28 | 142.45 | 334.84 | 178.93 | 1908.81 | 0.00 | 0.00 | 0.00 |
November | 190.14 | 68.18 | 121.96 | 20.48 | 3347.93 | 0.00 | 0.00 | 0.00 |
December | 17.08 | 1.69 | 15.39 | 0.00 | 3747.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1369.45 | 590.77 | 778.68 | 1294.71 | 1837.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.08 | 1.69 | 15.39 | 0.00 | 375.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2942.57 | 1433.46 | 1684.99 | 3260.52 | 3747.49 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38017231.89 | 0.00 | 38017231.89 | 0.00 | 0.303252E+10 |
February | 0.151791E+09 | 0.00 | 0.151791E+09 | 0.00 | 0.249597E+10 |
March | 0.449473E+09 | 0.00 | 0.449473E+09 | 22072756.82 | 0.211050E+10 |
April | 0.785941E+09 | 16277307.71 | 0.769663E+09 | 0.269083E+09 | 0.112735E+10 |
May | 0.124246E+10 | 0.194231E+09 | 0.104823E+10 | 0.903319E+09 | 0.510922E+09 |
June | 0.157116E+10 | 0.347399E+09 | 0.122376E+10 | 0.151670E+10 | 0.231366E+09 |
July | 0.136216E+10 | 0.219156E+09 | 0.114300E+10 | 0.133542E+10 | 0.292104E+09 |
August | 0.869747E+09 | 46942781.44 | 0.822804E+09 | 0.668204E+09 | 0.495297E+09 |
September | 0.470462E+09 | 414710.16 | 0.470047E+09 | 0.139714E+09 | 0.101068E+10 |
October | 0.236582E+09 | 0.00 | 0.236582E+09 | 7389628.82 | 0.185907E+10 |
November | 71051496.91 | 0.00 | 71051496.91 | 0.00 | 0.293207E+10 |
December | 11532443.31 | 0.00 | 11532443.31 | 0.00 | 0.323596E+10 |
Annual Sum or Average | 0.726037E+10 | 0.824420E+09 | 0.643595E+10 | 0.486190E+10 | 0.193338E+11 |
Minimum of Months | 11532443.31 | 0.00 | 11532443.31 | 0.00 | 0.231366E+09 |
Maximum of Months | 0.157116E+10 | 0.347399E+09 | 0.122376E+10 | 0.151670E+10 | 0.323596E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38017196.71 | 0.00 | 38017196.71 | 0.00 | 0.303252E+10 |
February | 0.151791E+09 | 0.00 | 0.151791E+09 | 0.00 | 0.249597E+10 |
March | 0.449473E+09 | 0.00 | 0.449473E+09 | 22072645.36 | 0.211050E+10 |
April | 0.785940E+09 | 16277288.18 | 0.769663E+09 | 0.269082E+09 | 0.112735E+10 |
May | 0.124246E+10 | 0.194230E+09 | 0.104823E+10 | 0.903318E+09 | 0.510922E+09 |
June | 0.157116E+10 | 0.347398E+09 | 0.122376E+10 | 0.151670E+10 | 0.231366E+09 |
July | 0.136216E+10 | 0.219156E+09 | 0.114300E+10 | 0.133542E+10 | 0.292104E+09 |
August | 0.869746E+09 | 46942725.11 | 0.822803E+09 | 0.668203E+09 | 0.495297E+09 |
September | 0.470462E+09 | 414709.66 | 0.470047E+09 | 0.139713E+09 | 0.101068E+10 |
October | 0.236582E+09 | 0.00 | 0.236582E+09 | 7389589.02 | 0.185907E+10 |
November | 71051431.17 | 0.00 | 71051431.17 | 0.00 | 0.293207E+10 |
December | 11532432.17 | 0.00 | 11532432.17 | 0.00 | 0.323596E+10 |
Annual Sum or Average | 0.726037E+10 | 0.824419E+09 | 0.643595E+10 | 0.486189E+10 | 0.193338E+11 |
Minimum of Months | 11532432.17 | 0.00 | 11532432.17 | 0.00 | 0.231366E+09 |
Maximum of Months | 0.157116E+10 | 0.347398E+09 | 0.122376E+10 | 0.151670E+10 | 0.323596E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38017231.89 | 0.00 | 38017231.89 | 0.00 | 0.303252E+10 |
February | 0.151791E+09 | 0.00 | 0.151791E+09 | 0.00 | 0.249597E+10 |
March | 0.449473E+09 | 0.00 | 0.449473E+09 | 22072756.82 | 0.211050E+10 |
April | 0.785941E+09 | 16277307.71 | 0.769663E+09 | 0.269083E+09 | 0.112735E+10 |
May | 0.124246E+10 | 0.194231E+09 | 0.104823E+10 | 0.903319E+09 | 0.510922E+09 |
June | 0.157116E+10 | 0.347399E+09 | 0.122376E+10 | 0.151670E+10 | 0.231366E+09 |
July | 0.136216E+10 | 0.219156E+09 | 0.114300E+10 | 0.133542E+10 | 0.292104E+09 |
August | 0.869747E+09 | 46942781.44 | 0.822804E+09 | 0.668204E+09 | 0.495297E+09 |
September | 0.470462E+09 | 414710.16 | 0.470047E+09 | 0.139714E+09 | 0.101068E+10 |
October | 0.236582E+09 | 0.00 | 0.236582E+09 | 7389628.82 | 0.185907E+10 |
November | 71051496.91 | 0.00 | 71051496.91 | 0.00 | 0.293207E+10 |
December | 11532443.31 | 0.00 | 11532443.31 | 0.00 | 0.323596E+10 |
Annual Sum or Average | 0.726037E+10 | 0.824420E+09 | 0.643595E+10 | 0.486190E+10 | 0.193338E+11 |
Minimum of Months | 11532443.31 | 0.00 | 11532443.31 | 0.00 | 0.231366E+09 |
Maximum of Months | 0.157116E+10 | 0.347399E+09 | 0.122376E+10 | 0.151670E+10 | 0.323596E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38017196.71 | 0.00 | 38017196.71 | 0.00 | 0.303252E+10 |
February | 0.151791E+09 | 0.00 | 0.151791E+09 | 0.00 | 0.249597E+10 |
March | 0.449473E+09 | 0.00 | 0.449473E+09 | 22072645.36 | 0.211050E+10 |
April | 0.785940E+09 | 16277288.18 | 0.769663E+09 | 0.269082E+09 | 0.112735E+10 |
May | 0.124246E+10 | 0.194230E+09 | 0.104823E+10 | 0.903318E+09 | 0.510922E+09 |
June | 0.157116E+10 | 0.347398E+09 | 0.122376E+10 | 0.151670E+10 | 0.231366E+09 |
July | 0.136216E+10 | 0.219156E+09 | 0.114300E+10 | 0.133542E+10 | 0.292104E+09 |
August | 0.869746E+09 | 46942725.11 | 0.822803E+09 | 0.668203E+09 | 0.495297E+09 |
September | 0.470462E+09 | 414709.66 | 0.470047E+09 | 0.139713E+09 | 0.101068E+10 |
October | 0.236582E+09 | 0.00 | 0.236582E+09 | 7389589.02 | 0.185907E+10 |
November | 71051431.17 | 0.00 | 71051431.17 | 0.00 | 0.293207E+10 |
December | 11532432.17 | 0.00 | 11532432.17 | 0.00 | 0.323596E+10 |
Annual Sum or Average | 0.726037E+10 | 0.824419E+09 | 0.643595E+10 | 0.486189E+10 | 0.193338E+11 |
Minimum of Months | 11532432.17 | 0.00 | 11532432.17 | 0.00 | 0.231366E+09 |
Maximum of Months | 0.157116E+10 | 0.347398E+09 | 0.122376E+10 | 0.151670E+10 | 0.323596E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38015699.62 | 0.00 | 38015699.62 | 0.00 | 0.303239E+10 |
February | 0.151785E+09 | 0.00 | 0.151785E+09 | 0.00 | 0.249587E+10 |
March | 0.449455E+09 | 0.00 | 0.449455E+09 | 22071867.19 | 0.211042E+10 |
April | 0.785909E+09 | 16276651.67 | 0.769632E+09 | 0.269072E+09 | 0.112730E+10 |
May | 0.124241E+10 | 0.194223E+09 | 0.104819E+10 | 0.903283E+09 | 0.510901E+09 |
June | 0.157109E+10 | 0.347384E+09 | 0.122371E+10 | 0.151664E+10 | 0.231357E+09 |
July | 0.136210E+10 | 0.219147E+09 | 0.114295E+10 | 0.133536E+10 | 0.292092E+09 |
August | 0.869711E+09 | 46940889.44 | 0.822771E+09 | 0.668177E+09 | 0.495278E+09 |
September | 0.470443E+09 | 414693.44 | 0.470029E+09 | 0.139708E+09 | 0.101064E+10 |
October | 0.236573E+09 | 0.00 | 0.236573E+09 | 7389330.98 | 0.185899E+10 |
November | 71048633.22 | 0.00 | 71048633.22 | 0.00 | 0.293195E+10 |
December | 11531978.51 | 0.00 | 11531978.51 | 0.00 | 0.323583E+10 |
Annual Sum or Average | 0.726008E+10 | 0.824387E+09 | 0.643569E+10 | 0.486170E+10 | 0.193330E+11 |
Minimum of Months | 11531978.51 | 0.00 | 11531978.51 | 0.00 | 0.231357E+09 |
Maximum of Months | 0.157109E+10 | 0.347384E+09 | 0.122371E+10 | 0.151664E+10 | 0.323583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110235E+09 | 33979299.33 | 76255437.02 | 8945964.09 | 0.325770E+10 |
February | 0.553940E+09 | 0.263609E+09 | 0.290331E+09 | 0.277324E+09 | 0.250137E+10 |
March | 0.175590E+10 | 0.890316E+09 | 0.865581E+09 | 0.145451E+10 | 0.208410E+10 |
April | 0.233690E+10 | 0.118428E+10 | 0.115261E+10 | 0.213555E+10 | 0.112300E+10 |
May | 0.351296E+10 | 0.198252E+10 | 0.153044E+10 | 0.385505E+10 | 0.615478E+09 |
June | 0.312492E+10 | 0.145964E+10 | 0.166527E+10 | 0.355434E+10 | 0.295330E+09 |
July | 0.306788E+10 | 0.148963E+10 | 0.157826E+10 | 0.357558E+10 | 0.347479E+09 |
August | 0.242929E+10 | 0.118421E+10 | 0.124508E+10 | 0.269603E+10 | 0.545385E+09 |
September | 0.145304E+10 | 0.637163E+09 | 0.815881E+09 | 0.131362E+10 | 0.103702E+10 |
October | 0.791630E+09 | 0.317414E+09 | 0.474217E+09 | 0.536734E+09 | 0.185957E+10 |
November | 0.161751E+09 | 55683337.07 | 0.106067E+09 | 10930832.56 | 0.311226E+10 |
December | 23767410.86 | 5459522.49 | 18307888.37 | 0.00 | 0.353409E+10 |
Annual Sum or Average | 0.193222E+11 | 0.950390E+10 | 0.981830E+10 | 0.194186E+11 | 0.203128E+11 |
Minimum of Months | 23767410.86 | 5459522.49 | 18307888.37 | 0.00 | 0.295330E+09 |
Maximum of Months | 0.351296E+10 | 0.198252E+10 | 0.166527E+10 | 0.385505E+10 | 0.353409E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110235E+09 | 33979299.33 | 76255437.02 | 8945964.09 | 0.325770E+10 |
February | 0.553940E+09 | 0.263609E+09 | 0.290331E+09 | 0.277324E+09 | 0.250137E+10 |
March | 0.175590E+10 | 0.890316E+09 | 0.865581E+09 | 0.145451E+10 | 0.208410E+10 |
April | 0.233690E+10 | 0.118428E+10 | 0.115261E+10 | 0.213555E+10 | 0.112300E+10 |
May | 0.351296E+10 | 0.198252E+10 | 0.153044E+10 | 0.385505E+10 | 0.615478E+09 |
June | 0.312492E+10 | 0.145964E+10 | 0.166527E+10 | 0.355434E+10 | 0.295330E+09 |
July | 0.306788E+10 | 0.148963E+10 | 0.157826E+10 | 0.357558E+10 | 0.347479E+09 |
August | 0.242929E+10 | 0.118421E+10 | 0.124508E+10 | 0.269603E+10 | 0.545385E+09 |
September | 0.145304E+10 | 0.637163E+09 | 0.815881E+09 | 0.131362E+10 | 0.103702E+10 |
October | 0.791630E+09 | 0.317414E+09 | 0.474217E+09 | 0.536734E+09 | 0.185957E+10 |
November | 0.161751E+09 | 55683337.07 | 0.106067E+09 | 10930832.56 | 0.311226E+10 |
December | 23767410.86 | 5459522.49 | 18307888.37 | 0.00 | 0.353409E+10 |
Annual Sum or Average | 0.193222E+11 | 0.950390E+10 | 0.981830E+10 | 0.194186E+11 | 0.203128E+11 |
Minimum of Months | 23767410.86 | 5459522.49 | 18307888.37 | 0.00 | 0.295330E+09 |
Maximum of Months | 0.351296E+10 | 0.198252E+10 | 0.166527E+10 | 0.385505E+10 | 0.353409E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110233E+09 | 33978678.45 | 76254043.66 | 8945800.63 | 0.325764E+10 |
February | 0.553930E+09 | 0.263604E+09 | 0.290326E+09 | 0.277319E+09 | 0.250133E+10 |
March | 0.175587E+10 | 0.890300E+09 | 0.865566E+09 | 0.145448E+10 | 0.208407E+10 |
April | 0.233685E+10 | 0.118426E+10 | 0.115259E+10 | 0.213552E+10 | 0.112298E+10 |
May | 0.351289E+10 | 0.198248E+10 | 0.153041E+10 | 0.385498E+10 | 0.615467E+09 |
June | 0.312486E+10 | 0.145961E+10 | 0.166524E+10 | 0.355428E+10 | 0.295325E+09 |
July | 0.306783E+10 | 0.148960E+10 | 0.157823E+10 | 0.357551E+10 | 0.347473E+09 |
August | 0.242924E+10 | 0.118418E+10 | 0.124506E+10 | 0.269598E+10 | 0.545375E+09 |
September | 0.145302E+10 | 0.637152E+09 | 0.815866E+09 | 0.131359E+10 | 0.103700E+10 |
October | 0.791616E+09 | 0.317408E+09 | 0.474208E+09 | 0.536725E+09 | 0.185953E+10 |
November | 0.161748E+09 | 55682319.62 | 0.106066E+09 | 10930632.83 | 0.311220E+10 |
December | 23766976.58 | 5459422.73 | 18307553.85 | 0.00 | 0.353402E+10 |
Annual Sum or Average | 0.193219E+11 | 0.950373E+10 | 0.981812E+10 | 0.194183E+11 | 0.203124E+11 |
Minimum of Months | 23766976.58 | 5459422.73 | 18307553.85 | 0.00 | 0.295325E+09 |
Maximum of Months | 0.351289E+10 | 0.198248E+10 | 0.166524E+10 | 0.385498E+10 | 0.353402E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459319E+09 | 0.303719E+09 | 0.155600E+09 | 0.263128E+09 | 0.267847E+10 |
February | 0.142692E+10 | 0.995423E+09 | 0.431496E+09 | 0.119781E+10 | 0.198393E+10 |
March | 0.270639E+10 | 0.183808E+10 | 0.868305E+09 | 0.265041E+10 | 0.171781E+10 |
April | 0.318758E+10 | 0.198519E+10 | 0.120239E+10 | 0.350566E+10 | 0.110797E+10 |
May | 0.270606E+10 | 0.139973E+10 | 0.130633E+10 | 0.306212E+10 | 0.638812E+09 |
June | 0.238806E+10 | 0.974422E+09 | 0.141364E+10 | 0.277896E+10 | 0.334006E+09 |
July | 0.237971E+10 | 0.103343E+10 | 0.134628E+10 | 0.283338E+10 | 0.367018E+09 |
August | 0.247180E+10 | 0.136314E+10 | 0.110867E+10 | 0.290070E+10 | 0.541009E+09 |
September | 0.193747E+10 | 0.116915E+10 | 0.768322E+09 | 0.204370E+10 | 0.917058E+09 |
October | 0.144473E+10 | 0.919399E+09 | 0.525326E+09 | 0.129617E+10 | 0.150240E+10 |
November | 0.751177E+09 | 0.526167E+09 | 0.225010E+09 | 0.483493E+09 | 0.246218E+10 |
December | 0.137847E+09 | 97478138.69 | 40369315.19 | 22997407.70 | 0.301133E+10 |
Annual Sum or Average | 0.219971E+11 | 0.126053E+11 | 0.939174E+10 | 0.230385E+11 | 0.172620E+11 |
Minimum of Months | 0.137847E+09 | 97478138.69 | 40369315.19 | 22997407.70 | 0.334006E+09 |
Maximum of Months | 0.318758E+10 | 0.198519E+10 | 0.141364E+10 | 0.350566E+10 | 0.301133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459319E+09 | 0.303718E+09 | 0.155600E+09 | 0.263128E+09 | 0.267847E+10 |
February | 0.142692E+10 | 0.995422E+09 | 0.431495E+09 | 0.119781E+10 | 0.198393E+10 |
March | 0.270638E+10 | 0.183808E+10 | 0.868304E+09 | 0.265040E+10 | 0.171781E+10 |
April | 0.318758E+10 | 0.198519E+10 | 0.120239E+10 | 0.350565E+10 | 0.110797E+10 |
May | 0.270606E+10 | 0.139973E+10 | 0.130633E+10 | 0.306211E+10 | 0.638813E+09 |
June | 0.238806E+10 | 0.974421E+09 | 0.141364E+10 | 0.277896E+10 | 0.334006E+09 |
July | 0.237971E+10 | 0.103343E+10 | 0.134628E+10 | 0.283337E+10 | 0.367018E+09 |
August | 0.247180E+10 | 0.136313E+10 | 0.110867E+10 | 0.290069E+10 | 0.541009E+09 |
September | 0.193747E+10 | 0.116915E+10 | 0.768321E+09 | 0.204370E+10 | 0.917058E+09 |
October | 0.144472E+10 | 0.919398E+09 | 0.525326E+09 | 0.129616E+10 | 0.150240E+10 |
November | 0.751176E+09 | 0.526166E+09 | 0.225010E+09 | 0.483492E+09 | 0.246218E+10 |
December | 0.137847E+09 | 97478021.73 | 40369269.45 | 22997326.69 | 0.301133E+10 |
Annual Sum or Average | 0.219970E+11 | 0.126053E+11 | 0.939174E+10 | 0.230385E+11 | 0.172620E+11 |
Minimum of Months | 0.137847E+09 | 97478021.73 | 40369269.45 | 22997326.69 | 0.334006E+09 |
Maximum of Months | 0.318758E+10 | 0.198519E+10 | 0.141364E+10 | 0.350565E+10 | 0.301133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459319E+09 | 0.303719E+09 | 0.155600E+09 | 0.263128E+09 | 0.267847E+10 |
February | 0.142692E+10 | 0.995423E+09 | 0.431496E+09 | 0.119781E+10 | 0.198393E+10 |
March | 0.270639E+10 | 0.183808E+10 | 0.868305E+09 | 0.265041E+10 | 0.171781E+10 |
April | 0.318758E+10 | 0.198519E+10 | 0.120239E+10 | 0.350566E+10 | 0.110797E+10 |
May | 0.270606E+10 | 0.139973E+10 | 0.130633E+10 | 0.306212E+10 | 0.638812E+09 |
June | 0.238806E+10 | 0.974422E+09 | 0.141364E+10 | 0.277896E+10 | 0.334006E+09 |
July | 0.237971E+10 | 0.103343E+10 | 0.134628E+10 | 0.283338E+10 | 0.367018E+09 |
August | 0.247180E+10 | 0.136314E+10 | 0.110867E+10 | 0.290070E+10 | 0.541009E+09 |
September | 0.193747E+10 | 0.116915E+10 | 0.768322E+09 | 0.204370E+10 | 0.917058E+09 |
October | 0.144473E+10 | 0.919399E+09 | 0.525326E+09 | 0.129617E+10 | 0.150240E+10 |
November | 0.751177E+09 | 0.526167E+09 | 0.225010E+09 | 0.483493E+09 | 0.246218E+10 |
December | 0.137847E+09 | 97478138.69 | 40369315.19 | 22997407.70 | 0.301133E+10 |
Annual Sum or Average | 0.219971E+11 | 0.126053E+11 | 0.939174E+10 | 0.230385E+11 | 0.172620E+11 |
Minimum of Months | 0.137847E+09 | 97478138.69 | 40369315.19 | 22997407.70 | 0.334006E+09 |
Maximum of Months | 0.318758E+10 | 0.198519E+10 | 0.141364E+10 | 0.350566E+10 | 0.301133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459319E+09 | 0.303718E+09 | 0.155600E+09 | 0.263128E+09 | 0.267847E+10 |
February | 0.142692E+10 | 0.995422E+09 | 0.431495E+09 | 0.119781E+10 | 0.198393E+10 |
March | 0.270638E+10 | 0.183808E+10 | 0.868304E+09 | 0.265040E+10 | 0.171781E+10 |
April | 0.318758E+10 | 0.198519E+10 | 0.120239E+10 | 0.350565E+10 | 0.110797E+10 |
May | 0.270606E+10 | 0.139973E+10 | 0.130633E+10 | 0.306211E+10 | 0.638813E+09 |
June | 0.238806E+10 | 0.974421E+09 | 0.141364E+10 | 0.277896E+10 | 0.334006E+09 |
July | 0.237971E+10 | 0.103343E+10 | 0.134628E+10 | 0.283337E+10 | 0.367018E+09 |
August | 0.247180E+10 | 0.136313E+10 | 0.110867E+10 | 0.290069E+10 | 0.541009E+09 |
September | 0.193747E+10 | 0.116915E+10 | 0.768321E+09 | 0.204370E+10 | 0.917058E+09 |
October | 0.144472E+10 | 0.919398E+09 | 0.525326E+09 | 0.129616E+10 | 0.150240E+10 |
November | 0.751176E+09 | 0.526166E+09 | 0.225010E+09 | 0.483492E+09 | 0.246218E+10 |
December | 0.137847E+09 | 97478021.73 | 40369269.45 | 22997326.69 | 0.301133E+10 |
Annual Sum or Average | 0.219970E+11 | 0.126053E+11 | 0.939174E+10 | 0.230385E+11 | 0.172620E+11 |
Minimum of Months | 0.137847E+09 | 97478021.73 | 40369269.45 | 22997326.69 | 0.334006E+09 |
Maximum of Months | 0.318758E+10 | 0.198519E+10 | 0.141364E+10 | 0.350565E+10 | 0.301133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459301E+09 | 0.303706E+09 | 0.155594E+09 | 0.263118E+09 | 0.267836E+10 |
February | 0.142686E+10 | 0.995383E+09 | 0.431478E+09 | 0.119776E+10 | 0.198385E+10 |
March | 0.270628E+10 | 0.183801E+10 | 0.868270E+09 | 0.265030E+10 | 0.171774E+10 |
April | 0.318745E+10 | 0.198511E+10 | 0.120234E+10 | 0.350552E+10 | 0.110792E+10 |
May | 0.270595E+10 | 0.139968E+10 | 0.130628E+10 | 0.306200E+10 | 0.638787E+09 |
June | 0.238797E+10 | 0.974383E+09 | 0.141358E+10 | 0.277885E+10 | 0.333992E+09 |
July | 0.237962E+10 | 0.103339E+10 | 0.134623E+10 | 0.283326E+10 | 0.367003E+09 |
August | 0.247170E+10 | 0.136308E+10 | 0.110862E+10 | 0.290058E+10 | 0.540987E+09 |
September | 0.193739E+10 | 0.116910E+10 | 0.768291E+09 | 0.204362E+10 | 0.917021E+09 |
October | 0.144467E+10 | 0.919362E+09 | 0.525305E+09 | 0.129611E+10 | 0.150234E+10 |
November | 0.751147E+09 | 0.526145E+09 | 0.225001E+09 | 0.483473E+09 | 0.246208E+10 |
December | 0.137842E+09 | 97474209.90 | 40367688.13 | 22996480.80 | 0.301121E+10 |
Annual Sum or Average | 0.219962E+11 | 0.126048E+11 | 0.939137E+10 | 0.230376E+11 | 0.172613E+11 |
Minimum of Months | 0.137842E+09 | 97474209.90 | 40367688.13 | 22996480.80 | 0.333992E+09 |
Maximum of Months | 0.318745E+10 | 0.198511E+10 | 0.141358E+10 | 0.350552E+10 | 0.301121E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58077755.91 | 9989268.85 | 48088487.06 | 0.00 | 0.340436E+10 |
February | 0.310472E+09 | 0.106898E+09 | 0.203574E+09 | 51183369.52 | 0.272357E+10 |
March | 0.103601E+10 | 0.444719E+09 | 0.591286E+09 | 0.546855E+09 | 0.229804E+10 |
April | 0.238599E+10 | 0.123853E+10 | 0.114746E+10 | 0.222787E+10 | 0.132113E+10 |
May | 0.239763E+10 | 0.109443E+10 | 0.130320E+10 | 0.241615E+10 | 0.669641E+09 |
June | 0.254240E+10 | 0.108656E+10 | 0.145585E+10 | 0.280093E+10 | 0.360678E+09 |
July | 0.219719E+10 | 0.832917E+09 | 0.136427E+10 | 0.242106E+10 | 0.411823E+09 |
August | 0.180555E+10 | 0.765743E+09 | 0.103980E+10 | 0.186755E+10 | 0.623312E+09 |
September | 0.105681E+10 | 0.442864E+09 | 0.613942E+09 | 0.825148E+09 | 0.108074E+10 |
October | 0.426124E+09 | 0.127177E+09 | 0.298947E+09 | 0.131581E+09 | 0.206599E+10 |
November | 0.164281E+09 | 58906745.49 | 0.105374E+09 | 12555425.16 | 0.329495E+10 |
December | 15246855.30 | 1506720.79 | 13740134.51 | 0.00 | 0.377627E+10 |
Annual Sum or Average | 0.143958E+11 | 0.621023E+10 | 0.818553E+10 | 0.133009E+11 | 0.220305E+11 |
Minimum of Months | 15246855.30 | 1506720.79 | 13740134.51 | 0.00 | 0.360678E+09 |
Maximum of Months | 0.254240E+10 | 0.123853E+10 | 0.145585E+10 | 0.280093E+10 | 0.377627E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58077755.91 | 9989268.85 | 48088487.06 | 0.00 | 0.340436E+10 |
February | 0.310472E+09 | 0.106898E+09 | 0.203574E+09 | 51183369.52 | 0.272357E+10 |
March | 0.103601E+10 | 0.444719E+09 | 0.591286E+09 | 0.546855E+09 | 0.229804E+10 |
April | 0.238599E+10 | 0.123853E+10 | 0.114746E+10 | 0.222787E+10 | 0.132113E+10 |
May | 0.239763E+10 | 0.109443E+10 | 0.130320E+10 | 0.241615E+10 | 0.669641E+09 |
June | 0.254240E+10 | 0.108656E+10 | 0.145585E+10 | 0.280093E+10 | 0.360678E+09 |
July | 0.219719E+10 | 0.832917E+09 | 0.136427E+10 | 0.242106E+10 | 0.411823E+09 |
August | 0.180555E+10 | 0.765743E+09 | 0.103980E+10 | 0.186755E+10 | 0.623312E+09 |
September | 0.105681E+10 | 0.442864E+09 | 0.613942E+09 | 0.825148E+09 | 0.108074E+10 |
October | 0.426124E+09 | 0.127177E+09 | 0.298947E+09 | 0.131581E+09 | 0.206599E+10 |
November | 0.164281E+09 | 58906745.49 | 0.105374E+09 | 12555425.16 | 0.329495E+10 |
December | 15246855.30 | 1506720.79 | 13740134.51 | 0.00 | 0.377627E+10 |
Annual Sum or Average | 0.143958E+11 | 0.621023E+10 | 0.818553E+10 | 0.133009E+11 | 0.220305E+11 |
Minimum of Months | 15246855.30 | 1506720.79 | 13740134.51 | 0.00 | 0.360678E+09 |
Maximum of Months | 0.254240E+10 | 0.123853E+10 | 0.145585E+10 | 0.280093E+10 | 0.377627E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58076694.71 | 9989086.32 | 48087608.38 | 0.00 | 0.340430E+10 |
February | 0.310466E+09 | 0.106896E+09 | 0.203570E+09 | 51182434.29 | 0.272352E+10 |
March | 0.103599E+10 | 0.444711E+09 | 0.591275E+09 | 0.546845E+09 | 0.229800E+10 |
April | 0.238594E+10 | 0.123850E+10 | 0.114744E+10 | 0.222783E+10 | 0.132110E+10 |
May | 0.239758E+10 | 0.109441E+10 | 0.130318E+10 | 0.241611E+10 | 0.669629E+09 |
June | 0.254236E+10 | 0.108654E+10 | 0.145582E+10 | 0.280088E+10 | 0.360672E+09 |
July | 0.219715E+10 | 0.832902E+09 | 0.136425E+10 | 0.242101E+10 | 0.411815E+09 |
August | 0.180551E+10 | 0.765729E+09 | 0.103978E+10 | 0.186752E+10 | 0.623300E+09 |
September | 0.105679E+10 | 0.442856E+09 | 0.613931E+09 | 0.825133E+09 | 0.108072E+10 |
October | 0.426116E+09 | 0.127174E+09 | 0.298942E+09 | 0.131579E+09 | 0.206595E+10 |
November | 0.164278E+09 | 58905669.13 | 0.105372E+09 | 12555195.74 | 0.329489E+10 |
December | 15246576.71 | 1506693.26 | 13739883.45 | 0.00 | 0.377620E+10 |
Annual Sum or Average | 0.143955E+11 | 0.621012E+10 | 0.818538E+10 | 0.133006E+11 | 0.220301E+11 |
Minimum of Months | 15246576.71 | 1506693.26 | 13739883.45 | 0.00 | 0.360672E+09 |
Maximum of Months | 0.254236E+10 | 0.123850E+10 | 0.145582E+10 | 0.280088E+10 | 0.377620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190084E+09 | 0.00 | 0.190084E+09 | 0.00 | 0.144771E+11 |
February | 0.758946E+09 | 0.00 | 0.758946E+09 | 0.00 | 0.117895E+11 |
March | 0.224734E+10 | 0.00 | 0.224734E+10 | 0.159303E+09 | 0.983098E+10 |
April | 0.392966E+10 | 81385554.46 | 0.384827E+10 | 0.148975E+10 | 0.516314E+10 |
May | 0.621225E+10 | 0.971141E+09 | 0.524111E+10 | 0.471838E+10 | 0.234929E+10 |
June | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.774413E+10 | 0.104854E+10 |
July | 0.681070E+10 | 0.109577E+10 | 0.571493E+10 | 0.686101E+10 | 0.132212E+10 |
August | 0.434868E+10 | 0.234711E+09 | 0.411397E+10 | 0.352518E+10 | 0.221375E+10 |
September | 0.235228E+10 | 2073525.72 | 0.235021E+10 | 0.817934E+09 | 0.445567E+10 |
October | 0.118290E+10 | 0.00 | 0.118290E+10 | 60963197.44 | 0.847069E+10 |
November | 0.355253E+09 | 0.00 | 0.355253E+09 | 0.00 | 0.137729E+11 |
December | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.152595E+11 |
Annual Sum or Average | 0.363014E+11 | 0.412205E+10 | 0.321794E+11 | 0.253767E+11 | 0.901531E+11 |
Minimum of Months | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.104854E+10 |
Maximum of Months | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.774413E+10 | 0.152595E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330701E+09 | 0.101937E+09 | 0.228764E+09 | 29147926.84 | 0.931554E+10 |
February | 0.166180E+10 | 0.790818E+09 | 0.870984E+09 | 0.868774E+09 | 0.712112E+10 |
March | 0.526764E+10 | 0.267092E+10 | 0.259672E+10 | 0.440459E+10 | 0.597980E+10 |
April | 0.701062E+10 | 0.355282E+10 | 0.345780E+10 | 0.641352E+10 | 0.322896E+10 |
May | 0.105388E+11 | 0.594750E+10 | 0.459127E+10 | 0.115794E+11 | 0.172185E+10 |
June | 0.937465E+10 | 0.437888E+10 | 0.499577E+10 | 0.106917E+11 | 0.811661E+09 |
July | 0.920356E+10 | 0.446883E+10 | 0.473473E+10 | 0.107584E+11 | 0.964474E+09 |
August | 0.728778E+10 | 0.355258E+10 | 0.373520E+10 | 0.812543E+10 | 0.151456E+10 |
September | 0.435909E+10 | 0.191147E+10 | 0.244762E+10 | 0.399363E+10 | 0.283943E+10 |
October | 0.237487E+10 | 0.952231E+09 | 0.142264E+10 | 0.165342E+10 | 0.519303E+10 |
November | 0.485248E+09 | 0.167048E+09 | 0.318199E+09 | 38157194.45 | 0.880278E+10 |
December | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.100397E+11 |
Annual Sum or Average | 0.579660E+11 | 0.285114E+11 | 0.294546E+11 | 0.585561E+11 | 0.575329E+11 |
Minimum of Months | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.811661E+09 |
Maximum of Months | 0.105388E+11 | 0.594750E+10 | 0.499577E+10 | 0.115794E+11 | 0.100397E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229657E+10 | 0.151857E+10 | 0.777993E+09 | 0.133836E+10 | 0.130334E+11 |
February | 0.713451E+10 | 0.497706E+10 | 0.215745E+10 | 0.604220E+10 | 0.965020E+10 |
March | 0.135318E+11 | 0.919029E+10 | 0.434147E+10 | 0.132548E+11 | 0.841341E+10 |
April | 0.159377E+11 | 0.992583E+10 | 0.601188E+10 | 0.174662E+11 | 0.543313E+10 |
May | 0.135301E+11 | 0.699857E+10 | 0.653157E+10 | 0.152983E+11 | 0.303906E+10 |
June | 0.119402E+11 | 0.487205E+10 | 0.706812E+10 | 0.139162E+11 | 0.155699E+10 |
July | 0.118984E+11 | 0.516709E+10 | 0.673134E+10 | 0.142086E+11 | 0.171571E+10 |
August | 0.123589E+11 | 0.681560E+10 | 0.554327E+10 | 0.145340E+11 | 0.254012E+10 |
September | 0.968723E+10 | 0.584566E+10 | 0.384156E+10 | 0.102445E+11 | 0.436882E+10 |
October | 0.722354E+10 | 0.459694E+10 | 0.262660E+10 | 0.651669E+10 | 0.727218E+10 |
November | 0.375584E+10 | 0.263080E+10 | 0.112504E+10 | 0.248020E+10 | 0.118545E+11 |
December | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.120470E+09 | 0.145139E+11 |
Annual Sum or Average | 0.109984E+12 | 0.630258E+11 | 0.469582E+11 | 0.115421E+12 | 0.833914E+11 |
Minimum of Months | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.120470E+09 | 0.155699E+10 |
Maximum of Months | 0.159377E+11 | 0.992583E+10 | 0.706812E+10 | 0.174662E+11 | 0.145139E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174231E+09 | 29967501.09 | 0.144264E+09 | 0.00 | 0.962007E+10 |
February | 0.931405E+09 | 0.320690E+09 | 0.610715E+09 | 0.180949E+09 | 0.748432E+10 |
March | 0.310798E+10 | 0.133414E+10 | 0.177384E+10 | 0.173220E+10 | 0.615247E+10 |
April | 0.715789E+10 | 0.371554E+10 | 0.344235E+10 | 0.680258E+10 | 0.355632E+10 |
May | 0.719281E+10 | 0.328325E+10 | 0.390956E+10 | 0.729528E+10 | 0.189340E+10 |
June | 0.762713E+10 | 0.325964E+10 | 0.436749E+10 | 0.846352E+10 | 0.994324E+09 |
July | 0.659150E+10 | 0.249873E+10 | 0.409277E+10 | 0.736513E+10 | 0.111179E+10 |
August | 0.541658E+10 | 0.229721E+10 | 0.311938E+10 | 0.571877E+10 | 0.165657E+10 |
September | 0.317039E+10 | 0.132858E+10 | 0.184181E+10 | 0.254192E+10 | 0.295470E+10 |
October | 0.127836E+10 | 0.381527E+09 | 0.896833E+09 | 0.439769E+09 | 0.546750E+10 |
November | 0.492837E+09 | 0.176718E+09 | 0.316118E+09 | 49271692.49 | 0.892473E+10 |
December | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.102551E+11 |
Annual Sum or Average | 0.431869E+11 | 0.186305E+11 | 0.245564E+11 | 0.405894E+11 | 0.600713E+11 |
Minimum of Months | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.994324E+09 |
Maximum of Months | 0.762713E+10 | 0.371554E+10 | 0.436749E+10 | 0.846352E+10 | 0.102551E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190084E+09 | 0.00 | 0.190084E+09 | 0.00 | 0.141585E+11 |
February | 0.758946E+09 | 0.00 | 0.758946E+09 | 0.00 | 0.114270E+11 |
March | 0.224734E+10 | 0.00 | 0.224734E+10 | 0.199165E+09 | 0.934327E+10 |
April | 0.392966E+10 | 81385554.46 | 0.384827E+10 | 0.163883E+10 | 0.478174E+10 |
May | 0.621225E+10 | 0.971141E+09 | 0.524111E+10 | 0.483180E+10 | 0.224745E+10 |
June | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.774603E+10 | 0.102415E+10 |
July | 0.681070E+10 | 0.109577E+10 | 0.571493E+10 | 0.685884E+10 | 0.129683E+10 |
August | 0.434868E+10 | 0.234711E+09 | 0.411397E+10 | 0.357367E+10 | 0.212797E+10 |
September | 0.235228E+10 | 2073525.72 | 0.235021E+10 | 0.938916E+09 | 0.404182E+10 |
October | 0.118290E+10 | 0.00 | 0.118290E+10 | 0.103080E+09 | 0.785375E+10 |
November | 0.355253E+09 | 0.00 | 0.355253E+09 | 0.00 | 0.133729E+11 |
December | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.149094E+11 |
Annual Sum or Average | 0.363014E+11 | 0.412205E+10 | 0.321794E+11 | 0.258903E+11 | 0.865848E+11 |
Minimum of Months | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.102415E+10 |
Maximum of Months | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.774603E+10 | 0.149094E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330701E+09 | 0.101937E+09 | 0.228764E+09 | 28625251.65 | 0.916956E+10 |
February | 0.166180E+10 | 0.790818E+09 | 0.870984E+09 | 0.895145E+09 | 0.690316E+10 |
March | 0.526764E+10 | 0.267092E+10 | 0.259672E+10 | 0.450252E+10 | 0.564547E+10 |
April | 0.701062E+10 | 0.355282E+10 | 0.345780E+10 | 0.652668E+10 | 0.301997E+10 |
May | 0.105388E+11 | 0.594750E+10 | 0.459127E+10 | 0.116261E+11 | 0.166348E+10 |
June | 0.937465E+10 | 0.437888E+10 | 0.499577E+10 | 0.106974E+11 | 0.797353E+09 |
July | 0.920356E+10 | 0.446883E+10 | 0.473473E+10 | 0.107597E+11 | 0.950038E+09 |
August | 0.728778E+10 | 0.355258E+10 | 0.373520E+10 | 0.814834E+10 | 0.147054E+10 |
September | 0.435909E+10 | 0.191147E+10 | 0.244762E+10 | 0.408824E+10 | 0.261269E+10 |
October | 0.237487E+10 | 0.952231E+09 | 0.142264E+10 | 0.173251E+10 | 0.479493E+10 |
November | 0.485248E+09 | 0.167048E+09 | 0.318199E+09 | 39895851.31 | 0.859145E+10 |
December | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.989078E+10 |
Annual Sum or Average | 0.579660E+11 | 0.285114E+11 | 0.294546E+11 | 0.590452E+11 | 0.555094E+11 |
Minimum of Months | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.797353E+09 |
Maximum of Months | 0.105388E+11 | 0.594750E+10 | 0.499577E+10 | 0.116261E+11 | 0.989078E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229657E+10 | 0.151857E+10 | 0.777993E+09 | 0.136692E+10 | 0.127363E+11 |
February | 0.713451E+10 | 0.497706E+10 | 0.215745E+10 | 0.614590E+10 | 0.926632E+10 |
March | 0.135318E+11 | 0.919029E+10 | 0.434147E+10 | 0.134067E+11 | 0.795379E+10 |
April | 0.159377E+11 | 0.992583E+10 | 0.601188E+10 | 0.175748E+11 | 0.511569E+10 |
May | 0.135301E+11 | 0.699857E+10 | 0.653157E+10 | 0.153296E+11 | 0.291353E+10 |
June | 0.119402E+11 | 0.487205E+10 | 0.706812E+10 | 0.138998E+11 | 0.152338E+10 |
July | 0.118984E+11 | 0.516709E+10 | 0.673134E+10 | 0.141881E+11 | 0.168461E+10 |
August | 0.123589E+11 | 0.681560E+10 | 0.554327E+10 | 0.145381E+11 | 0.246420E+10 |
September | 0.968723E+10 | 0.584566E+10 | 0.384156E+10 | 0.103600E+11 | 0.405452E+10 |
October | 0.722354E+10 | 0.459694E+10 | 0.262660E+10 | 0.669011E+10 | 0.671705E+10 |
November | 0.375584E+10 | 0.263080E+10 | 0.112504E+10 | 0.253971E+10 | 0.114574E+11 |
December | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.123252E+09 | 0.141863E+11 |
Annual Sum or Average | 0.109984E+12 | 0.630258E+11 | 0.469582E+11 | 0.116163E+12 | 0.800731E+11 |
Minimum of Months | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.123252E+09 | 0.152338E+10 |
Maximum of Months | 0.159377E+11 | 0.992583E+10 | 0.706812E+10 | 0.175748E+11 | 0.141863E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174231E+09 | 29967501.09 | 0.144264E+09 | 0.00 | 0.941157E+10 |
February | 0.931405E+09 | 0.320690E+09 | 0.610715E+09 | 0.189898E+09 | 0.726575E+10 |
March | 0.310798E+10 | 0.133414E+10 | 0.177384E+10 | 0.177907E+10 | 0.586161E+10 |
April | 0.715789E+10 | 0.371554E+10 | 0.344235E+10 | 0.687517E+10 | 0.334987E+10 |
May | 0.719281E+10 | 0.328325E+10 | 0.390956E+10 | 0.731903E+10 | 0.181880E+10 |
June | 0.762713E+10 | 0.325964E+10 | 0.436749E+10 | 0.845126E+10 | 0.973241E+09 |
July | 0.659150E+10 | 0.249873E+10 | 0.409277E+10 | 0.735151E+10 | 0.109085E+10 |
August | 0.541658E+10 | 0.229721E+10 | 0.311938E+10 | 0.572492E+10 | 0.160600E+10 |
September | 0.317039E+10 | 0.132858E+10 | 0.184181E+10 | 0.260690E+10 | 0.273902E+10 |
October | 0.127836E+10 | 0.381527E+09 | 0.896833E+09 | 0.479250E+09 | 0.511256E+10 |
November | 0.492837E+09 | 0.176718E+09 | 0.316118E+09 | 53074163.04 | 0.867784E+10 |
December | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.100373E+11 |
Annual Sum or Average | 0.431869E+11 | 0.186305E+11 | 0.245564E+11 | 0.408301E+11 | 0.579444E+11 |
Minimum of Months | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.973241E+09 |
Maximum of Months | 0.762713E+10 | 0.371554E+10 | 0.436749E+10 | 0.845126E+10 | 0.100373E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5661.02 | 70.97 | 0.00 | 70.97 | 0.00 | 0.00 |
February | 0.00 | 5158.62 | 313.72 | 0.00 | 313.72 | 0.00 | 0.00 |
March | 41.20 | 3939.83 | 839.06 | 0.00 | 839.06 | 0.00 | 0.00 |
April | 519.06 | 2174.65 | 1516.08 | 31.40 | 1484.68 | 0.00 | 0.00 |
May | 1686.29 | 953.77 | 2319.40 | 362.58 | 1956.81 | 0.00 | 0.00 |
June | 2925.71 | 446.30 | 3030.75 | 670.13 | 2360.62 | 0.00 | 0.00 |
July | 2492.92 | 545.29 | 2542.83 | 409.11 | 2133.72 | 0.00 | 0.00 |
August | 1247.38 | 924.61 | 1623.62 | 87.63 | 1535.99 | 0.00 | 0.00 |
September | 269.51 | 1949.60 | 907.52 | 0.80 | 906.72 | 0.00 | 0.00 |
October | 13.79 | 3470.45 | 441.64 | 0.00 | 441.64 | 0.00 | 0.00 |
November | 0.00 | 5655.96 | 137.06 | 0.00 | 137.06 | 0.00 | 0.00 |
December | 0.00 | 6040.80 | 21.53 | 0.00 | 21.53 | 0.00 | 0.00 |
Annual Sum or Average | 770.84 | 3065.33 | 1151.12 | 130.71 | 1020.41 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 446.30 | 21.53 | 0.00 | 21.53 | 0.00 | 0.00 |
Maximum of Months | 2925.71 | 6040.80 | 3030.75 | 670.13 | 2360.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.02 | 3648.83 | 123.47 | 38.06 | 85.41 | 0.00 | 0.00 |
February | 343.90 | 3101.88 | 686.93 | 326.89 | 360.03 | 0.00 | 0.00 |
March | 1629.14 | 2334.33 | 1966.72 | 997.21 | 969.51 | 0.00 | 0.00 |
April | 2471.69 | 1299.76 | 2704.72 | 1370.69 | 1334.03 | 0.00 | 0.00 |
May | 4317.91 | 689.38 | 3934.74 | 2220.55 | 1714.19 | 0.00 | 0.00 |
June | 4113.80 | 341.82 | 3616.78 | 1689.39 | 1927.39 | 0.00 | 0.00 |
July | 4004.88 | 389.20 | 3436.23 | 1668.48 | 1767.75 | 0.00 | 0.00 |
August | 3019.73 | 610.87 | 2720.96 | 1326.39 | 1394.57 | 0.00 | 0.00 |
September | 1520.38 | 1200.24 | 1681.75 | 737.45 | 944.30 | 0.00 | 0.00 |
October | 601.18 | 2082.83 | 886.68 | 355.52 | 531.15 | 0.00 | 0.00 |
November | 12.65 | 3602.13 | 187.21 | 64.45 | 122.76 | 0.00 | 0.00 |
December | 0.00 | 3958.41 | 26.62 | 6.12 | 20.51 | 0.00 | 0.00 |
Annual Sum or Average | 1847.27 | 1932.33 | 1838.10 | 904.09 | 934.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 341.82 | 26.62 | 6.12 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 4317.91 | 3958.41 | 3934.74 | 2220.55 | 1927.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 491.20 | 5000.10 | 857.44 | 566.97 | 290.47 | 0.00 | 0.00 |
February | 2475.61 | 4100.35 | 2949.13 | 2057.32 | 891.81 | 0.00 | 0.00 |
March | 4947.70 | 3206.76 | 5052.20 | 3431.27 | 1620.93 | 0.00 | 0.00 |
April | 6762.40 | 2137.27 | 6148.83 | 3829.42 | 2319.41 | 0.00 | 0.00 |
May | 5716.27 | 1192.52 | 5051.59 | 2612.98 | 2438.62 | 0.00 | 0.00 |
June | 5360.61 | 644.30 | 4606.56 | 1879.66 | 2726.91 | 0.00 | 0.00 |
July | 5289.26 | 685.14 | 4442.38 | 1929.18 | 2513.20 | 0.00 | 0.00 |
August | 5414.94 | 1009.94 | 4614.29 | 2544.66 | 2069.63 | 0.00 | 0.00 |
September | 3942.29 | 1769.00 | 3737.37 | 2255.28 | 1482.09 | 0.00 | 0.00 |
October | 2419.64 | 2804.64 | 2696.97 | 1716.31 | 980.66 | 0.00 | 0.00 |
November | 932.66 | 4749.54 | 1449.02 | 1014.97 | 434.04 | 0.00 | 0.00 |
December | 42.93 | 5621.47 | 257.33 | 181.97 | 75.36 | 0.00 | 0.00 |
Annual Sum or Average | 3652.70 | 2736.85 | 3487.58 | 1998.54 | 1489.04 | 0.00 | 0.00 |
Minimum of Months | 42.93 | 644.30 | 257.33 | 181.97 | 75.36 | 0.00 | 0.00 |
Maximum of Months | 6762.40 | 5621.47 | 6148.83 | 3829.42 | 2726.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3813.10 | 65.05 | 11.19 | 53.86 | 0.00 | 0.00 |
February | 63.47 | 3377.43 | 385.01 | 132.56 | 252.45 | 0.00 | 0.00 |
March | 612.51 | 2573.95 | 1160.39 | 498.11 | 662.28 | 0.00 | 0.00 |
April | 2578.54 | 1529.07 | 2761.54 | 1433.47 | 1328.07 | 0.00 | 0.00 |
May | 2706.25 | 750.04 | 2685.50 | 1225.83 | 1459.67 | 0.00 | 0.00 |
June | 3241.80 | 417.45 | 2942.58 | 1257.58 | 1685.00 | 0.00 | 0.00 |
July | 2711.74 | 461.27 | 2460.99 | 932.92 | 1528.07 | 0.00 | 0.00 |
August | 2091.78 | 698.15 | 2022.33 | 857.68 | 1164.65 | 0.00 | 0.00 |
September | 955.03 | 1250.84 | 1223.15 | 512.57 | 710.58 | 0.00 | 0.00 |
October | 147.38 | 2314.04 | 477.29 | 142.45 | 334.84 | 0.00 | 0.00 |
November | 14.53 | 3813.58 | 190.14 | 68.18 | 121.96 | 0.00 | 0.00 |
December | 0.00 | 4229.67 | 17.08 | 1.69 | 15.39 | 0.00 | 0.00 |
Annual Sum or Average | 1265.30 | 2095.73 | 1369.45 | 590.77 | 778.68 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 417.45 | 17.08 | 1.69 | 15.39 | 0.00 | 0.00 |
Maximum of Months | 3241.80 | 4229.67 | 2942.58 | 1433.47 | 1685.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5405.12 | 70.97 | 0.00 | 70.97 | 0.00 | 0.00 |
February | 0.00 | 4873.31 | 313.72 | 0.00 | 313.72 | 0.00 | 0.00 |
March | 59.48 | 3670.47 | 839.06 | 0.00 | 839.06 | 0.00 | 0.00 |
April | 574.75 | 1991.95 | 1516.07 | 31.40 | 1484.67 | 0.00 | 0.00 |
May | 1761.64 | 877.12 | 2319.39 | 362.58 | 1956.80 | 0.00 | 0.00 |
June | 2987.71 | 404.53 | 3030.74 | 670.13 | 2360.62 | 0.00 | 0.00 |
July | 2561.61 | 493.62 | 2542.82 | 409.11 | 2133.71 | 0.00 | 0.00 |
August | 1316.15 | 826.52 | 1623.61 | 87.63 | 1535.98 | 0.00 | 0.00 |
September | 315.56 | 1719.01 | 907.52 | 0.80 | 906.72 | 0.00 | 0.00 |
October | 22.76 | 3162.59 | 441.64 | 0.00 | 441.64 | 0.00 | 0.00 |
November | 0.00 | 5313.61 | 137.06 | 0.00 | 137.06 | 0.00 | 0.00 |
December | 0.00 | 5697.24 | 21.53 | 0.00 | 21.53 | 0.00 | 0.00 |
Annual Sum or Average | 804.69 | 2858.74 | 1151.11 | 130.71 | 1020.40 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 404.53 | 21.53 | 0.00 | 21.53 | 0.00 | 0.00 |
Maximum of Months | 2987.71 | 5697.24 | 3030.74 | 670.13 | 2360.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.88 | 3478.02 | 123.47 | 38.06 | 85.41 | 0.00 | 0.00 |
February | 359.12 | 2943.58 | 686.92 | 326.89 | 360.03 | 0.00 | 0.00 |
March | 1644.49 | 2232.60 | 1966.71 | 997.21 | 969.50 | 0.00 | 0.00 |
April | 2474.35 | 1245.74 | 2704.71 | 1370.69 | 1334.03 | 0.00 | 0.00 |
May | 4323.24 | 642.87 | 3934.72 | 2220.54 | 1714.18 | 0.00 | 0.00 |
June | 4124.88 | 313.14 | 3616.76 | 1689.38 | 1927.38 | 0.00 | 0.00 |
July | 4016.74 | 360.09 | 3436.22 | 1668.47 | 1767.75 | 0.00 | 0.00 |
August | 3033.69 | 565.47 | 2720.95 | 1326.38 | 1394.57 | 0.00 | 0.00 |
September | 1540.75 | 1095.46 | 1681.75 | 737.45 | 944.30 | 0.00 | 0.00 |
October | 617.31 | 1938.86 | 886.67 | 355.52 | 531.15 | 0.00 | 0.00 |
November | 14.72 | 3396.14 | 187.21 | 64.45 | 122.76 | 0.00 | 0.00 |
December | 0.00 | 3748.40 | 26.62 | 6.11 | 20.51 | 0.00 | 0.00 |
Annual Sum or Average | 1856.80 | 1824.36 | 1838.09 | 904.09 | 934.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 313.14 | 26.62 | 6.11 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 4323.24 | 3748.40 | 3934.72 | 2220.54 | 1927.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 499.69 | 4866.10 | 857.44 | 566.97 | 290.47 | 0.00 | 0.00 |
February | 2497.60 | 3989.00 | 2949.12 | 2057.31 | 891.80 | 0.00 | 0.00 |
March | 4948.78 | 3141.21 | 5052.18 | 3431.26 | 1620.92 | 0.00 | 0.00 |
April | 6738.49 | 2096.11 | 6148.81 | 3829.41 | 2319.40 | 0.00 | 0.00 |
May | 5711.73 | 1134.66 | 5051.58 | 2612.97 | 2438.61 | 0.00 | 0.00 |
June | 5368.91 | 600.69 | 4606.55 | 1879.65 | 2726.90 | 0.00 | 0.00 |
July | 5304.89 | 640.57 | 4442.36 | 1929.17 | 2513.20 | 0.00 | 0.00 |
August | 5426.39 | 948.37 | 4614.27 | 2544.65 | 2069.62 | 0.00 | 0.00 |
September | 3952.37 | 1685.50 | 3737.36 | 2255.27 | 1482.08 | 0.00 | 0.00 |
October | 2433.05 | 2715.12 | 2696.96 | 1716.30 | 980.66 | 0.00 | 0.00 |
November | 956.87 | 4573.50 | 1449.01 | 1014.97 | 434.04 | 0.00 | 0.00 |
December | 44.98 | 5418.89 | 257.33 | 181.97 | 75.36 | 0.00 | 0.00 |
Annual Sum or Average | 3659.96 | 2644.33 | 3487.57 | 1998.54 | 1489.03 | 0.00 | 0.00 |
Minimum of Months | 44.98 | 600.69 | 257.33 | 181.97 | 75.36 | 0.00 | 0.00 |
Maximum of Months | 6738.49 | 5418.89 | 6148.81 | 3829.41 | 2726.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3591.72 | 65.05 | 11.19 | 53.86 | 0.00 | 0.00 |
February | 74.80 | 3093.72 | 385.01 | 132.56 | 252.45 | 0.00 | 0.00 |
March | 646.73 | 2297.07 | 1160.39 | 498.11 | 662.28 | 0.00 | 0.00 |
April | 2624.45 | 1372.04 | 2761.53 | 1433.46 | 1328.07 | 0.00 | 0.00 |
May | 2723.75 | 706.92 | 2685.49 | 1225.82 | 1459.66 | 0.00 | 0.00 |
June | 3265.25 | 383.61 | 2942.57 | 1257.58 | 1684.99 | 0.00 | 0.00 |
July | 2749.83 | 415.09 | 2460.98 | 932.92 | 1528.07 | 0.00 | 0.00 |
August | 2135.14 | 618.49 | 2022.32 | 857.68 | 1164.64 | 0.00 | 0.00 |
September | 980.68 | 1139.93 | 1223.14 | 512.57 | 710.57 | 0.00 | 0.00 |
October | 164.19 | 2041.33 | 477.28 | 142.45 | 334.84 | 0.00 | 0.00 |
November | 19.01 | 3443.18 | 190.14 | 68.18 | 121.96 | 0.00 | 0.00 |
December | 0.00 | 3828.82 | 17.08 | 1.69 | 15.39 | 0.00 | 0.00 |
Annual Sum or Average | 1287.08 | 1904.85 | 1369.45 | 590.77 | 778.68 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 383.61 | 17.08 | 1.69 | 15.39 | 0.00 | 0.00 |
Maximum of Months | 3265.25 | 3828.82 | 2942.57 | 1433.46 | 1684.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5286.18 | 70.97 | 0.00 | 70.97 | 0.00 | 0.00 |
February | 0.00 | 4723.46 | 313.72 | 0.00 | 313.72 | 0.00 | 0.00 |
March | 74.36 | 3488.38 | 839.06 | 0.00 | 839.06 | 0.00 | 0.00 |
April | 632.26 | 1844.81 | 1516.07 | 31.40 | 1484.67 | 0.00 | 0.00 |
May | 1803.99 | 839.10 | 2319.39 | 362.58 | 1956.80 | 0.00 | 0.00 |
June | 2988.44 | 395.12 | 3030.74 | 670.13 | 2360.62 | 0.00 | 0.00 |
July | 2560.80 | 484.18 | 2542.82 | 409.11 | 2133.71 | 0.00 | 0.00 |
August | 1334.26 | 794.49 | 1623.61 | 87.63 | 1535.98 | 0.00 | 0.00 |
September | 362.24 | 1559.35 | 907.52 | 0.80 | 906.72 | 0.00 | 0.00 |
October | 38.49 | 2932.25 | 441.64 | 0.00 | 441.64 | 0.00 | 0.00 |
November | 0.00 | 5159.30 | 137.06 | 0.00 | 137.06 | 0.00 | 0.00 |
December | 0.00 | 5566.53 | 21.53 | 0.00 | 21.53 | 0.00 | 0.00 |
Annual Sum or Average | 820.98 | 2745.59 | 1151.11 | 130.71 | 1020.40 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 395.12 | 21.53 | 0.00 | 21.53 | 0.00 | 0.00 |
Maximum of Months | 2988.44 | 5566.53 | 3030.74 | 670.13 | 2360.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.69 | 3423.52 | 123.47 | 38.06 | 85.41 | 0.00 | 0.00 |
February | 370.02 | 2853.49 | 686.92 | 326.89 | 360.03 | 0.00 | 0.00 |
March | 1681.05 | 2107.78 | 1966.71 | 997.21 | 969.50 | 0.00 | 0.00 |
April | 2518.01 | 1165.11 | 2704.71 | 1370.69 | 1334.03 | 0.00 | 0.00 |
May | 4340.69 | 621.07 | 3934.72 | 2220.54 | 1714.18 | 0.00 | 0.00 |
June | 4127.10 | 307.62 | 3616.76 | 1689.38 | 1927.38 | 0.00 | 0.00 |
July | 4017.22 | 354.70 | 3436.22 | 1668.47 | 1767.75 | 0.00 | 0.00 |
August | 3042.24 | 549.04 | 2720.95 | 1326.38 | 1394.57 | 0.00 | 0.00 |
September | 1577.25 | 1007.98 | 1681.75 | 737.45 | 944.30 | 0.00 | 0.00 |
October | 646.84 | 1790.22 | 886.67 | 355.52 | 531.15 | 0.00 | 0.00 |
November | 15.39 | 3314.60 | 187.21 | 64.45 | 122.76 | 0.00 | 0.00 |
December | 0.00 | 3692.80 | 26.62 | 6.11 | 20.51 | 0.00 | 0.00 |
Annual Sum or Average | 1872.31 | 1760.19 | 1838.09 | 904.09 | 934.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 307.62 | 26.62 | 6.11 | 20.51 | 0.00 | 0.00 |
Maximum of Months | 4340.69 | 3692.80 | 3934.72 | 2220.54 | 1927.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 510.35 | 4755.20 | 857.44 | 566.97 | 290.47 | 0.00 | 0.00 |
February | 2540.47 | 3830.32 | 2949.12 | 2057.31 | 891.80 | 0.00 | 0.00 |
March | 5005.49 | 2969.61 | 5052.18 | 3431.26 | 1620.92 | 0.00 | 0.00 |
April | 6780.40 | 1973.64 | 6148.81 | 3829.41 | 2319.40 | 0.00 | 0.00 |
May | 5723.40 | 1087.79 | 5051.58 | 2612.97 | 2438.61 | 0.00 | 0.00 |
June | 5362.57 | 587.72 | 4606.55 | 1879.65 | 2726.90 | 0.00 | 0.00 |
July | 5297.22 | 628.96 | 4442.36 | 1929.17 | 2513.20 | 0.00 | 0.00 |
August | 5427.90 | 920.03 | 4614.27 | 2544.65 | 2069.62 | 0.00 | 0.00 |
September | 3996.90 | 1564.24 | 3737.36 | 2255.27 | 1482.08 | 0.00 | 0.00 |
October | 2497.80 | 2507.86 | 2696.96 | 1716.30 | 980.66 | 0.00 | 0.00 |
November | 979.83 | 4420.30 | 1449.01 | 1014.97 | 434.04 | 0.00 | 0.00 |
December | 46.02 | 5296.54 | 257.33 | 181.97 | 75.36 | 0.00 | 0.00 |
Annual Sum or Average | 3683.50 | 2539.10 | 3487.57 | 1998.54 | 1489.03 | 0.00 | 0.00 |
Minimum of Months | 46.02 | 587.72 | 257.33 | 181.97 | 75.36 | 0.00 | 0.00 |
Maximum of Months | 6780.40 | 5296.54 | 6148.81 | 3829.41 | 2726.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3513.88 | 65.05 | 11.19 | 53.86 | 0.00 | 0.00 |
February | 78.50 | 3003.37 | 385.01 | 132.56 | 252.45 | 0.00 | 0.00 |
March | 664.23 | 2188.48 | 1160.39 | 498.11 | 662.28 | 0.00 | 0.00 |
April | 2652.46 | 1292.39 | 2761.53 | 1433.46 | 1328.07 | 0.00 | 0.00 |
May | 2732.61 | 679.06 | 2685.49 | 1225.82 | 1459.66 | 0.00 | 0.00 |
June | 3260.52 | 375.48 | 2942.57 | 1257.58 | 1684.99 | 0.00 | 0.00 |
July | 2744.74 | 407.28 | 2460.98 | 932.92 | 1528.07 | 0.00 | 0.00 |
August | 2137.44 | 599.61 | 2022.32 | 857.68 | 1164.64 | 0.00 | 0.00 |
September | 1005.75 | 1056.72 | 1223.14 | 512.57 | 710.57 | 0.00 | 0.00 |
October | 178.93 | 1908.81 | 477.28 | 142.45 | 334.84 | 0.00 | 0.00 |
November | 20.48 | 3347.93 | 190.14 | 68.18 | 121.96 | 0.00 | 0.00 |
December | 0.00 | 3747.49 | 17.08 | 1.69 | 15.39 | 0.00 | 0.00 |
Annual Sum or Average | 1294.71 | 1837.40 | 1369.45 | 590.77 | 778.68 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 375.48 | 17.08 | 1.69 | 15.39 | 0.00 | 0.00 |
Maximum of Months | 3260.52 | 3747.49 | 2942.57 | 1433.46 | 1684.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.151625E+11 | 0.190085E+09 | 0.00 | 0.190085E+09 | 0.00 | 0.00 |
February | 0.00 | 0.124797E+11 | 0.758949E+09 | 0.00 | 0.758949E+09 | 0.00 | 0.00 |
March | 0.110363E+09 | 0.105524E+11 | 0.224735E+10 | 0.00 | 0.224735E+10 | 0.00 | 0.00 |
April | 0.134540E+10 | 0.563669E+10 | 0.392967E+10 | 81385843.46 | 0.384828E+10 | 0.00 | 0.00 |
May | 0.451656E+10 | 0.255459E+10 | 0.621227E+10 | 0.971144E+09 | 0.524113E+10 | 0.00 | 0.00 |
June | 0.758345E+10 | 0.115682E+10 | 0.785572E+10 | 0.173698E+10 | 0.611874E+10 | 0.00 | 0.00 |
July | 0.667703E+10 | 0.146051E+10 | 0.681073E+10 | 0.109577E+10 | 0.571495E+10 | 0.00 | 0.00 |
August | 0.334099E+10 | 0.247647E+10 | 0.434870E+10 | 0.234712E+09 | 0.411398E+10 | 0.00 | 0.00 |
September | 0.698562E+09 | 0.505335E+10 | 0.235229E+10 | 2073533.08 | 0.235022E+10 | 0.00 | 0.00 |
October | 36947766.66 | 0.929527E+10 | 0.118290E+10 | 0.00 | 0.118290E+10 | 0.00 | 0.00 |
November | 0.00 | 0.146602E+11 | 0.355254E+09 | 0.00 | 0.355254E+09 | 0.00 | 0.00 |
December | 0.00 | 0.161797E+11 | 57661729.48 | 0.00 | 57661729.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.243093E+11 | 0.966682E+11 | 0.363016E+11 | 0.412207E+10 | 0.321795E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.115682E+10 | 57661729.48 | 0.00 | 57661729.48 | 0.00 | 0.00 |
Maximum of Months | 0.758345E+10 | 0.161797E+11 | 0.785572E+10 | 0.173698E+10 | 0.611874E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26837728.81 | 0.977303E+10 | 0.330702E+09 | 0.101937E+09 | 0.228765E+09 | 0.00 | 0.00 |
February | 0.831967E+09 | 0.750407E+10 | 0.166181E+10 | 0.790822E+09 | 0.870988E+09 | 0.00 | 0.00 |
March | 0.436349E+10 | 0.625228E+10 | 0.526766E+10 | 0.267093E+10 | 0.259673E+10 | 0.00 | 0.00 |
April | 0.640662E+10 | 0.336898E+10 | 0.701065E+10 | 0.355283E+10 | 0.345781E+10 | 0.00 | 0.00 |
May | 0.115651E+11 | 0.184642E+10 | 0.105388E+11 | 0.594752E+10 | 0.459128E+10 | 0.00 | 0.00 |
June | 0.106630E+11 | 0.885986E+09 | 0.937469E+10 | 0.437890E+10 | 0.499579E+10 | 0.00 | 0.00 |
July | 0.107267E+11 | 0.104243E+10 | 0.920360E+10 | 0.446885E+10 | 0.473475E+10 | 0.00 | 0.00 |
August | 0.808805E+10 | 0.163614E+10 | 0.728781E+10 | 0.355259E+10 | 0.373522E+10 | 0.00 | 0.00 |
September | 0.394082E+10 | 0.311103E+10 | 0.435911E+10 | 0.191148E+10 | 0.244763E+10 | 0.00 | 0.00 |
October | 0.161019E+10 | 0.557866E+10 | 0.237488E+10 | 0.952235E+09 | 0.142264E+10 | 0.00 | 0.00 |
November | 32792297.94 | 0.933672E+10 | 0.485250E+09 | 0.167049E+09 | 0.318201E+09 | 0.00 | 0.00 |
December | 0.00 | 0.106022E+11 | 71301798.31 | 16378467.71 | 54923330.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.582555E+11 | 0.609380E+11 | 0.579663E+11 | 0.285115E+11 | 0.294547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.885986E+09 | 71301798.31 | 16378467.71 | 54923330.60 | 0.00 | 0.00 |
Maximum of Months | 0.115651E+11 | 0.106022E+11 | 0.105388E+11 | 0.594752E+10 | 0.499579E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131563E+10 | 0.133923E+11 | 0.229658E+10 | 0.151858E+10 | 0.777996E+09 | 0.00 | 0.00 |
February | 0.598900E+10 | 0.991956E+10 | 0.713453E+10 | 0.497707E+10 | 0.215746E+10 | 0.00 | 0.00 |
March | 0.132519E+11 | 0.858900E+10 | 0.135318E+11 | 0.919033E+10 | 0.434149E+10 | 0.00 | 0.00 |
April | 0.175281E+11 | 0.553980E+10 | 0.159378E+11 | 0.992586E+10 | 0.601191E+10 | 0.00 | 0.00 |
May | 0.153105E+11 | 0.319404E+10 | 0.135302E+11 | 0.699860E+10 | 0.653159E+10 | 0.00 | 0.00 |
June | 0.138947E+11 | 0.167001E+10 | 0.119402E+11 | 0.487207E+10 | 0.706815E+10 | 0.00 | 0.00 |
July | 0.141668E+11 | 0.183507E+10 | 0.118985E+11 | 0.516711E+10 | 0.673137E+10 | 0.00 | 0.00 |
August | 0.145034E+11 | 0.270502E+10 | 0.123589E+11 | 0.681562E+10 | 0.554329E+10 | 0.00 | 0.00 |
September | 0.102184E+11 | 0.458525E+10 | 0.968726E+10 | 0.584568E+10 | 0.384158E+10 | 0.00 | 0.00 |
October | 0.648077E+10 | 0.751195E+10 | 0.722357E+10 | 0.459695E+10 | 0.262661E+10 | 0.00 | 0.00 |
November | 0.241744E+10 | 0.123108E+11 | 0.375585E+10 | 0.263081E+10 | 0.112504E+10 | 0.00 | 0.00 |
December | 0.114986E+09 | 0.150565E+11 | 0.689231E+09 | 0.487387E+09 | 0.201845E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115192E+12 | 0.863093E+11 | 0.109984E+12 | 0.630261E+11 | 0.469583E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114986E+09 | 0.167001E+10 | 0.689231E+09 | 0.487387E+09 | 0.201845E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175281E+11 | 0.150565E+11 | 0.159378E+11 | 0.992586E+10 | 0.706815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.102130E+11 | 0.174232E+09 | 29967624.02 | 0.144265E+09 | 0.00 | 0.00 |
February | 0.153549E+09 | 0.817067E+10 | 0.931409E+09 | 0.320691E+09 | 0.610718E+09 | 0.00 | 0.00 |
March | 0.164055E+10 | 0.689407E+10 | 0.310800E+10 | 0.133415E+10 | 0.177385E+10 | 0.00 | 0.00 |
April | 0.668357E+10 | 0.396336E+10 | 0.715792E+10 | 0.371555E+10 | 0.344236E+10 | 0.00 | 0.00 |
May | 0.724841E+10 | 0.200891E+10 | 0.719284E+10 | 0.328326E+10 | 0.390958E+10 | 0.00 | 0.00 |
June | 0.840274E+10 | 0.108203E+10 | 0.762716E+10 | 0.325966E+10 | 0.436751E+10 | 0.00 | 0.00 |
July | 0.726313E+10 | 0.123546E+10 | 0.659153E+10 | 0.249874E+10 | 0.409279E+10 | 0.00 | 0.00 |
August | 0.560261E+10 | 0.186992E+10 | 0.541661E+10 | 0.229722E+10 | 0.311939E+10 | 0.00 | 0.00 |
September | 0.247543E+10 | 0.324219E+10 | 0.317040E+10 | 0.132858E+10 | 0.184182E+10 | 0.00 | 0.00 |
October | 0.394742E+09 | 0.619793E+10 | 0.127836E+10 | 0.381528E+09 | 0.896837E+09 | 0.00 | 0.00 |
November | 37666046.05 | 0.988480E+10 | 0.492839E+09 | 0.176719E+09 | 0.316120E+09 | 0.00 | 0.00 |
December | 0.00 | 0.113287E+11 | 45740287.32 | 4520134.84 | 41220152.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.399024E+11 | 0.660911E+11 | 0.431870E+11 | 0.186306E+11 | 0.245565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.108203E+10 | 45740287.32 | 4520134.84 | 41220152.48 | 0.00 | 0.00 |
Maximum of Months | 0.840274E+10 | 0.113287E+11 | 0.762716E+10 | 0.371555E+10 | 0.436751E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.144771E+11 | 0.190084E+09 | 0.00 | 0.190084E+09 | 0.00 | 0.00 |
February | 0.00 | 0.117895E+11 | 0.758946E+09 | 0.00 | 0.758946E+09 | 0.00 | 0.00 |
March | 0.159303E+09 | 0.983098E+10 | 0.224734E+10 | 0.00 | 0.224734E+10 | 0.00 | 0.00 |
April | 0.148975E+10 | 0.516314E+10 | 0.392966E+10 | 81385554.46 | 0.384827E+10 | 0.00 | 0.00 |
May | 0.471838E+10 | 0.234929E+10 | 0.621225E+10 | 0.971141E+09 | 0.524111E+10 | 0.00 | 0.00 |
June | 0.774413E+10 | 0.104854E+10 | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.00 | 0.00 |
July | 0.686101E+10 | 0.132212E+10 | 0.681070E+10 | 0.109577E+10 | 0.571493E+10 | 0.00 | 0.00 |
August | 0.352518E+10 | 0.221375E+10 | 0.434868E+10 | 0.234711E+09 | 0.411397E+10 | 0.00 | 0.00 |
September | 0.817934E+09 | 0.445567E+10 | 0.235228E+10 | 2073525.72 | 0.235021E+10 | 0.00 | 0.00 |
October | 60963197.44 | 0.847069E+10 | 0.118290E+10 | 0.00 | 0.118290E+10 | 0.00 | 0.00 |
November | 0.00 | 0.137729E+11 | 0.355253E+09 | 0.00 | 0.355253E+09 | 0.00 | 0.00 |
December | 0.00 | 0.152595E+11 | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.253767E+11 | 0.901531E+11 | 0.363014E+11 | 0.412205E+10 | 0.321794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.104854E+10 | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.00 |
Maximum of Months | 0.774413E+10 | 0.152595E+11 | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29147926.84 | 0.931554E+10 | 0.330701E+09 | 0.101937E+09 | 0.228764E+09 | 0.00 | 0.00 |
February | 0.868774E+09 | 0.712112E+10 | 0.166180E+10 | 0.790818E+09 | 0.870984E+09 | 0.00 | 0.00 |
March | 0.440459E+10 | 0.597980E+10 | 0.526764E+10 | 0.267092E+10 | 0.259672E+10 | 0.00 | 0.00 |
April | 0.641352E+10 | 0.322896E+10 | 0.701062E+10 | 0.355282E+10 | 0.345780E+10 | 0.00 | 0.00 |
May | 0.115794E+11 | 0.172185E+10 | 0.105388E+11 | 0.594750E+10 | 0.459127E+10 | 0.00 | 0.00 |
June | 0.106917E+11 | 0.811661E+09 | 0.937465E+10 | 0.437888E+10 | 0.499577E+10 | 0.00 | 0.00 |
July | 0.107584E+11 | 0.964474E+09 | 0.920356E+10 | 0.446883E+10 | 0.473473E+10 | 0.00 | 0.00 |
August | 0.812543E+10 | 0.151456E+10 | 0.728778E+10 | 0.355258E+10 | 0.373520E+10 | 0.00 | 0.00 |
September | 0.399363E+10 | 0.283943E+10 | 0.435909E+10 | 0.191147E+10 | 0.244762E+10 | 0.00 | 0.00 |
October | 0.165342E+10 | 0.519303E+10 | 0.237487E+10 | 0.952231E+09 | 0.142264E+10 | 0.00 | 0.00 |
November | 38157194.45 | 0.880278E+10 | 0.485248E+09 | 0.167048E+09 | 0.318199E+09 | 0.00 | 0.00 |
December | 0.00 | 0.100397E+11 | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.585561E+11 | 0.575329E+11 | 0.579660E+11 | 0.285114E+11 | 0.294546E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.811661E+09 | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.00 |
Maximum of Months | 0.115794E+11 | 0.100397E+11 | 0.105388E+11 | 0.594750E+10 | 0.499577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133836E+10 | 0.130334E+11 | 0.229657E+10 | 0.151857E+10 | 0.777993E+09 | 0.00 | 0.00 |
February | 0.604220E+10 | 0.965020E+10 | 0.713451E+10 | 0.497706E+10 | 0.215745E+10 | 0.00 | 0.00 |
March | 0.132548E+11 | 0.841341E+10 | 0.135318E+11 | 0.919029E+10 | 0.434147E+10 | 0.00 | 0.00 |
April | 0.174662E+11 | 0.543313E+10 | 0.159377E+11 | 0.992583E+10 | 0.601188E+10 | 0.00 | 0.00 |
May | 0.152983E+11 | 0.303906E+10 | 0.135301E+11 | 0.699857E+10 | 0.653157E+10 | 0.00 | 0.00 |
June | 0.139162E+11 | 0.155699E+10 | 0.119402E+11 | 0.487205E+10 | 0.706812E+10 | 0.00 | 0.00 |
July | 0.142086E+11 | 0.171571E+10 | 0.118984E+11 | 0.516709E+10 | 0.673134E+10 | 0.00 | 0.00 |
August | 0.145340E+11 | 0.254012E+10 | 0.123589E+11 | 0.681560E+10 | 0.554327E+10 | 0.00 | 0.00 |
September | 0.102445E+11 | 0.436882E+10 | 0.968723E+10 | 0.584566E+10 | 0.384156E+10 | 0.00 | 0.00 |
October | 0.651669E+10 | 0.727218E+10 | 0.722354E+10 | 0.459694E+10 | 0.262660E+10 | 0.00 | 0.00 |
November | 0.248020E+10 | 0.118545E+11 | 0.375584E+10 | 0.263080E+10 | 0.112504E+10 | 0.00 | 0.00 |
December | 0.120470E+09 | 0.145139E+11 | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115421E+12 | 0.833914E+11 | 0.109984E+12 | 0.630258E+11 | 0.469582E+11 | 0.00 | 0.00 |
Minimum of Months | 0.120470E+09 | 0.155699E+10 | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174662E+11 | 0.145139E+11 | 0.159377E+11 | 0.992583E+10 | 0.706812E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.962007E+10 | 0.174231E+09 | 29967501.09 | 0.144264E+09 | 0.00 | 0.00 |
February | 0.180949E+09 | 0.748432E+10 | 0.931405E+09 | 0.320690E+09 | 0.610715E+09 | 0.00 | 0.00 |
March | 0.173220E+10 | 0.615247E+10 | 0.310798E+10 | 0.133414E+10 | 0.177384E+10 | 0.00 | 0.00 |
April | 0.680258E+10 | 0.355632E+10 | 0.715789E+10 | 0.371554E+10 | 0.344235E+10 | 0.00 | 0.00 |
May | 0.729528E+10 | 0.189340E+10 | 0.719281E+10 | 0.328325E+10 | 0.390956E+10 | 0.00 | 0.00 |
June | 0.846352E+10 | 0.994324E+09 | 0.762713E+10 | 0.325964E+10 | 0.436749E+10 | 0.00 | 0.00 |
July | 0.736513E+10 | 0.111179E+10 | 0.659150E+10 | 0.249873E+10 | 0.409277E+10 | 0.00 | 0.00 |
August | 0.571877E+10 | 0.165657E+10 | 0.541658E+10 | 0.229721E+10 | 0.311938E+10 | 0.00 | 0.00 |
September | 0.254192E+10 | 0.295470E+10 | 0.317039E+10 | 0.132858E+10 | 0.184181E+10 | 0.00 | 0.00 |
October | 0.439769E+09 | 0.546750E+10 | 0.127836E+10 | 0.381527E+09 | 0.896833E+09 | 0.00 | 0.00 |
November | 49271692.49 | 0.892473E+10 | 0.492837E+09 | 0.176718E+09 | 0.316118E+09 | 0.00 | 0.00 |
December | 0.00 | 0.102551E+11 | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.405894E+11 | 0.600713E+11 | 0.431869E+11 | 0.186305E+11 | 0.245564E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.994324E+09 | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.00 |
Maximum of Months | 0.846352E+10 | 0.102551E+11 | 0.762713E+10 | 0.371554E+10 | 0.436749E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.141585E+11 | 0.190084E+09 | 0.00 | 0.190084E+09 | 0.00 | 0.00 |
February | 0.00 | 0.114270E+11 | 0.758946E+09 | 0.00 | 0.758946E+09 | 0.00 | 0.00 |
March | 0.199165E+09 | 0.934327E+10 | 0.224734E+10 | 0.00 | 0.224734E+10 | 0.00 | 0.00 |
April | 0.163883E+10 | 0.478174E+10 | 0.392966E+10 | 81385554.46 | 0.384827E+10 | 0.00 | 0.00 |
May | 0.483180E+10 | 0.224745E+10 | 0.621225E+10 | 0.971141E+09 | 0.524111E+10 | 0.00 | 0.00 |
June | 0.774603E+10 | 0.102415E+10 | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.00 | 0.00 |
July | 0.685884E+10 | 0.129683E+10 | 0.681070E+10 | 0.109577E+10 | 0.571493E+10 | 0.00 | 0.00 |
August | 0.357367E+10 | 0.212797E+10 | 0.434868E+10 | 0.234711E+09 | 0.411397E+10 | 0.00 | 0.00 |
September | 0.938916E+09 | 0.404182E+10 | 0.235228E+10 | 2073525.72 | 0.235021E+10 | 0.00 | 0.00 |
October | 0.103080E+09 | 0.785375E+10 | 0.118290E+10 | 0.00 | 0.118290E+10 | 0.00 | 0.00 |
November | 0.00 | 0.133729E+11 | 0.355253E+09 | 0.00 | 0.355253E+09 | 0.00 | 0.00 |
December | 0.00 | 0.149094E+11 | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.258903E+11 | 0.865848E+11 | 0.363014E+11 | 0.412205E+10 | 0.321794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.102415E+10 | 57661519.32 | 0.00 | 57661519.32 | 0.00 | 0.00 |
Maximum of Months | 0.774603E+10 | 0.149094E+11 | 0.785569E+10 | 0.173697E+10 | 0.611872E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 28625251.65 | 0.916956E+10 | 0.330701E+09 | 0.101937E+09 | 0.228764E+09 | 0.00 | 0.00 |
February | 0.895145E+09 | 0.690316E+10 | 0.166180E+10 | 0.790818E+09 | 0.870984E+09 | 0.00 | 0.00 |
March | 0.450252E+10 | 0.564547E+10 | 0.526764E+10 | 0.267092E+10 | 0.259672E+10 | 0.00 | 0.00 |
April | 0.652668E+10 | 0.301997E+10 | 0.701062E+10 | 0.355282E+10 | 0.345780E+10 | 0.00 | 0.00 |
May | 0.116261E+11 | 0.166348E+10 | 0.105388E+11 | 0.594750E+10 | 0.459127E+10 | 0.00 | 0.00 |
June | 0.106974E+11 | 0.797353E+09 | 0.937465E+10 | 0.437888E+10 | 0.499577E+10 | 0.00 | 0.00 |
July | 0.107597E+11 | 0.950038E+09 | 0.920356E+10 | 0.446883E+10 | 0.473473E+10 | 0.00 | 0.00 |
August | 0.814834E+10 | 0.147054E+10 | 0.728778E+10 | 0.355258E+10 | 0.373520E+10 | 0.00 | 0.00 |
September | 0.408824E+10 | 0.261269E+10 | 0.435909E+10 | 0.191147E+10 | 0.244762E+10 | 0.00 | 0.00 |
October | 0.173251E+10 | 0.479493E+10 | 0.237487E+10 | 0.952231E+09 | 0.142264E+10 | 0.00 | 0.00 |
November | 39895851.31 | 0.859145E+10 | 0.485248E+09 | 0.167048E+09 | 0.318199E+09 | 0.00 | 0.00 |
December | 0.00 | 0.989078E+10 | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.590452E+11 | 0.555094E+11 | 0.579660E+11 | 0.285114E+11 | 0.294546E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.797353E+09 | 71301505.82 | 16378400.53 | 54923105.29 | 0.00 | 0.00 |
Maximum of Months | 0.116261E+11 | 0.989078E+10 | 0.105388E+11 | 0.594750E+10 | 0.499577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136692E+10 | 0.127363E+11 | 0.229657E+10 | 0.151857E+10 | 0.777993E+09 | 0.00 | 0.00 |
February | 0.614590E+10 | 0.926632E+10 | 0.713451E+10 | 0.497706E+10 | 0.215745E+10 | 0.00 | 0.00 |
March | 0.134067E+11 | 0.795379E+10 | 0.135318E+11 | 0.919029E+10 | 0.434147E+10 | 0.00 | 0.00 |
April | 0.175748E+11 | 0.511569E+10 | 0.159377E+11 | 0.992583E+10 | 0.601188E+10 | 0.00 | 0.00 |
May | 0.153296E+11 | 0.291353E+10 | 0.135301E+11 | 0.699857E+10 | 0.653157E+10 | 0.00 | 0.00 |
June | 0.138998E+11 | 0.152338E+10 | 0.119402E+11 | 0.487205E+10 | 0.706812E+10 | 0.00 | 0.00 |
July | 0.141881E+11 | 0.168461E+10 | 0.118984E+11 | 0.516709E+10 | 0.673134E+10 | 0.00 | 0.00 |
August | 0.145381E+11 | 0.246420E+10 | 0.123589E+11 | 0.681560E+10 | 0.554327E+10 | 0.00 | 0.00 |
September | 0.103600E+11 | 0.405452E+10 | 0.968723E+10 | 0.584566E+10 | 0.384156E+10 | 0.00 | 0.00 |
October | 0.669011E+10 | 0.671705E+10 | 0.722354E+10 | 0.459694E+10 | 0.262660E+10 | 0.00 | 0.00 |
November | 0.253971E+10 | 0.114574E+11 | 0.375584E+10 | 0.263080E+10 | 0.112504E+10 | 0.00 | 0.00 |
December | 0.123252E+09 | 0.141863E+11 | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116163E+12 | 0.800731E+11 | 0.109984E+12 | 0.630258E+11 | 0.469582E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123252E+09 | 0.152338E+10 | 0.689229E+09 | 0.487385E+09 | 0.201844E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175748E+11 | 0.141863E+11 | 0.159377E+11 | 0.992583E+10 | 0.706812E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.941157E+10 | 0.174231E+09 | 29967501.09 | 0.144264E+09 | 0.00 | 0.00 |
February | 0.189898E+09 | 0.726575E+10 | 0.931405E+09 | 0.320690E+09 | 0.610715E+09 | 0.00 | 0.00 |
March | 0.177907E+10 | 0.586161E+10 | 0.310798E+10 | 0.133414E+10 | 0.177384E+10 | 0.00 | 0.00 |
April | 0.687517E+10 | 0.334987E+10 | 0.715789E+10 | 0.371554E+10 | 0.344235E+10 | 0.00 | 0.00 |
May | 0.731903E+10 | 0.181880E+10 | 0.719281E+10 | 0.328325E+10 | 0.390956E+10 | 0.00 | 0.00 |
June | 0.845126E+10 | 0.973241E+09 | 0.762713E+10 | 0.325964E+10 | 0.436749E+10 | 0.00 | 0.00 |
July | 0.735151E+10 | 0.109085E+10 | 0.659150E+10 | 0.249873E+10 | 0.409277E+10 | 0.00 | 0.00 |
August | 0.572492E+10 | 0.160600E+10 | 0.541658E+10 | 0.229721E+10 | 0.311938E+10 | 0.00 | 0.00 |
September | 0.260690E+10 | 0.273902E+10 | 0.317039E+10 | 0.132858E+10 | 0.184181E+10 | 0.00 | 0.00 |
October | 0.479250E+09 | 0.511256E+10 | 0.127836E+10 | 0.381527E+09 | 0.896833E+09 | 0.00 | 0.00 |
November | 53074163.04 | 0.867784E+10 | 0.492837E+09 | 0.176718E+09 | 0.316118E+09 | 0.00 | 0.00 |
December | 0.00 | 0.100373E+11 | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.408301E+11 | 0.579444E+11 | 0.431869E+11 | 0.186305E+11 | 0.245564E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.973241E+09 | 45740099.69 | 4520116.30 | 41219983.39 | 0.00 | 0.00 |
Maximum of Months | 0.845126E+10 | 0.100373E+11 | 0.762713E+10 | 0.371554E+10 | 0.436749E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.482023E+11 | -0.477512E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -451102813.6 | 60.05 | 0.00 | 0.00 |
February | 0.437962E+11 | -0.433912E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -404962951.5 | 60.05 | 0.00 | 0.00 |
March | 0.514992E+11 | -0.510525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446707289.5 | 60.05 | 0.00 | 0.00 |
April | 0.467090E+11 | -0.462847E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -424342741.0 | 60.05 | 0.00 | 0.00 |
May | 0.494517E+11 | -0.490639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -387789880.3 | 60.05 | 0.00 | 0.00 |
June | 0.472569E+11 | -0.468870E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -369942496.3 | 60.05 | 0.00 | 0.00 |
July | 0.433047E+11 | -0.429257E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -379018151.5 | 60.05 | 0.00 | 0.00 |
August | 0.462556E+11 | -0.458795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -376109436.7 | 60.05 | 0.00 | 0.00 |
September | 0.418438E+11 | -0.414691E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -374690465.0 | 60.05 | 0.00 | 0.00 |
October | 0.440463E+11 | -0.436116E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -434696344.2 | 60.05 | 0.00 | 0.00 |
November | 0.447337E+11 | -0.443026E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -431090508.8 | 60.05 | 0.00 | 0.00 |
December | 0.463297E+11 | -0.458833E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446455871.2 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.553429E+12 | -0.548502E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.492691E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.418438E+11 | -0.510525E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -451102813.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.514992E+11 | -0.414691E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -369942496.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.60 | 0.48 | 10-JAN-10:00 | 793.32 | 29.51 | 84.67 | 70.00 | 619.24 | 30.99 | 85.83 | 45.00 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2697.39 | 34.89 | 189.50 | 173.17 | 2275.90 | 36.06 | 191.50 | 156.33 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:09 | 5975.95 | 32.95 | 283.33 | 299.00 | 5163.66 | 34.08 | 288.83 | 280.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:30 | 8399.59 | 31.63 | 298.17 | 382.67 | 1654.71 | 22.10 | 301.50 | 337.83 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 4783.56 | 23.52 | 270.83 | 455.00 | 1206.52 | 20.78 | 318.17 | 395.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:10 | 2017.70 | 19.05 | 225.67 | 477.67 | 1103.56 | 20.55 | 337.67 | 412.33 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-04:49 | 2394.36 | 19.61 | 239.00 | 474.50 | 1126.68 | 20.58 | 316.17 | 401.00 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:49 | 6006.72 | 27.39 | 286.50 | 407.50 | 1273.68 | 21.21 | 281.67 | 355.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4874.23 | 30.99 | 281.67 | 318.00 | 1669.98 | 22.56 | 233.83 | 279.00 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2733.76 | 32.43 | 233.67 | 235.50 | 2227.67 | 33.01 | 233.00 | 209.00 |
November | 135.83 | 0.55 | 0.48 | 01-NOV-09:00 | 1073.55 | 30.51 | 105.17 | 120.33 | 834.65 | 32.20 | 105.17 | 90.83 |
December | 71.17 | 0.76 | 0.48 | 05-DEC-11:20 | 189.34 | 8.28 | 0.00 | 9.83 | 123.36 | 11.64 | 0.00 | 0.33 |
Annual Sum or Average | 4053.17 | 0.53 | 4123.64 | 26.34 | 2498.17 | 3423.17 | 1671.41 | 24.22 | 2693.33 | 2963.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 189.34 | 8.28 | 0.00 | 9.83 | 123.36 | 11.64 | 0.00 | 0.33 | |
Maximum of Months | 583.50 | 0.76 | 0.48 | 8399.59 | 34.89 | 298.17 | 477.67 | 5163.66 | 36.06 | 337.67 | 412.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.70 | 0.48 | 16-JAN-11:00 | 295.51 | 12.97 | 2.00 | 32.00 | 176.35 | 14.33 | 5.50 | 12.33 |
February | 205.83 | 0.58 | 0.48 | 01-FEB-12:20 | 1022.06 | 21.18 | 75.00 | 143.67 | 637.95 | 22.51 | 90.17 | 98.50 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:09 | 2491.01 | 24.65 | 159.67 | 280.67 | 1551.06 | 24.91 | 194.17 | 241.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3149.55 | 25.99 | 206.17 | 388.67 | 1920.67 | 26.45 | 274.17 | 348.17 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4121.41 | 25.24 | 243.83 | 464.17 | 2128.53 | 24.84 | 306.50 | 422.33 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:39 | 3556.63 | 24.51 | 266.67 | 497.17 | 1568.76 | 23.83 | 341.83 | 438.67 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:49 | 3537.27 | 24.48 | 262.00 | 482.83 | 1826.01 | 24.32 | 328.17 | 428.17 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:49 | 2958.78 | 24.30 | 213.00 | 409.50 | 1483.64 | 23.93 | 261.67 | 361.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2284.78 | 24.03 | 166.00 | 301.17 | 1174.68 | 23.55 | 194.33 | 256.67 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1197.42 | 21.67 | 100.00 | 211.67 | 680.65 | 21.69 | 99.33 | 155.00 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-09:00 | 399.69 | 17.94 | 34.33 | 68.33 | 198.66 | 16.17 | 6.17 | 13.17 |
December | 71.17 | 0.87 | 0.55 | 08-DEC-11:30 | 101.34 | 8.14 | 0.00 | 0.00 | 57.42 | 9.14 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2783.01 | 23.53 | 1728.67 | 3279.83 | 1455.25 | 23.40 | 2102.00 | 2776.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 101.34 | 8.14 | 0.00 | 0.00 | 57.42 | 9.14 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.87 | 0.55 | 4121.41 | 25.99 | 266.67 | 497.17 | 2128.53 | 26.45 | 341.83 | 438.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.52 | 31-JAN-11:30 | 173.56 | 9.67 | 0.00 | 5.33 | 98.78 | 11.36 | 0.00 | 0.00 |
February | 205.83 | 0.62 | 0.48 | 05-FEB-12:30 | 382.76 | 13.97 | 0.00 | 112.00 | 221.76 | 15.62 | 0.00 | 25.17 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 705.41 | 17.20 | 0.00 | 271.83 | 413.44 | 18.76 | 49.33 | 202.00 |
April | 421.83 | 0.50 | 0.48 | 01-APR-07:40 | 932.77 | 19.45 | 6.00 | 395.33 | 571.23 | 20.95 | 171.33 | 339.83 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1144.11 | 23.59 | 177.17 | 501.33 | 653.97 | 23.53 | 334.83 | 458.00 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1363.65 | 24.72 | 252.50 | 537.17 | 773.64 | 24.90 | 441.00 | 499.33 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1230.41 | 23.42 | 200.00 | 517.67 | 693.16 | 23.66 | 383.33 | 464.83 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 954.70 | 20.80 | 79.17 | 423.83 | 561.52 | 22.13 | 207.67 | 366.83 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 687.24 | 17.29 | 0.00 | 296.33 | 393.01 | 18.69 | 35.50 | 206.17 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-07:00 | 477.18 | 15.36 | 0.00 | 191.00 | 262.30 | 16.80 | 0.00 | 36.17 |
November | 135.83 | 0.72 | 0.48 | 01-NOV-13:20 | 231.59 | 11.61 | 0.00 | 26.17 | 130.39 | 13.44 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.76 | 04-DEC-11:30 | 68.57 | 4.88 | 0.00 | 0.00 | 39.24 | 6.45 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 910.21 | 19.77 | 714.83 | 3278.00 | 524.04 | 20.69 | 1623.00 | 2598.33 | ||
Minimum of Months | 71.17 | 0.50 | 0.48 | 68.57 | 4.88 | 0.00 | 0.00 | 39.24 | 6.45 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.76 | 1363.65 | 24.72 | 252.50 | 537.17 | 773.64 | 24.90 | 441.00 | 499.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.72 | 0.48 | 23-JAN-13:20 | 249.56 | 12.87 | 1.67 | 22.33 | 146.69 | 14.25 | 1.83 | 4.17 |
February | 205.83 | 0.56 | 0.48 | 02-FEB-11:09 | 820.69 | 21.58 | 66.17 | 154.00 | 499.84 | 22.98 | 84.50 | 86.17 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1854.95 | 24.15 | 138.00 | 291.50 | 1095.05 | 24.51 | 189.17 | 255.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3580.74 | 24.97 | 178.67 | 389.33 | 1772.61 | 24.45 | 253.00 | 347.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-05:30 | 2808.52 | 22.08 | 161.50 | 483.67 | 1389.78 | 22.18 | 260.17 | 437.17 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-05:30 | 2964.23 | 21.63 | 160.17 | 511.67 | 1488.68 | 21.89 | 290.83 | 454.67 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:49 | 2576.18 | 21.49 | 167.83 | 501.00 | 1321.26 | 21.75 | 268.33 | 441.50 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2339.34 | 22.57 | 163.17 | 423.50 | 1395.51 | 23.38 | 243.50 | 374.33 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:00 | 1864.36 | 24.17 | 136.83 | 314.50 | 1121.67 | 24.56 | 190.83 | 260.83 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-08:30 | 944.53 | 22.78 | 94.50 | 219.00 | 538.96 | 23.11 | 90.00 | 145.17 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-10:30 | 402.15 | 19.81 | 45.00 | 68.33 | 251.86 | 20.85 | 45.83 | 24.50 |
December | 71.17 | 0.89 | 0.70 | 04-DEC-11:30 | 88.16 | 7.91 | 0.00 | 0.00 | 49.66 | 8.90 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.53 | 2244.37 | 22.09 | 1313.50 | 3378.83 | 1191.56 | 22.47 | 1918.00 | 2830.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 88.16 | 7.91 | 0.00 | 0.00 | 49.66 | 8.90 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.89 | 0.70 | 3580.74 | 24.97 | 178.67 | 511.67 | 1772.61 | 24.56 | 290.83 | 454.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.60 | 0.48 | 03-JAN-11:30 | 631.61 | 6.65 | 6.00 | 66.67 | 650.38 | 29.71 | 85.00 | 47.67 |
February | 205.83 | 0.53 | 0.48 | 01-FEB-11:30 | 2721.60 | 34.38 | 187.83 | 173.50 | 2356.94 | 35.63 | 190.33 | 157.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:09 | 6027.20 | 31.92 | 274.00 | 299.00 | 5285.17 | 33.40 | 279.50 | 282.67 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:30 | 8445.01 | 29.68 | 283.67 | 383.67 | 1775.33 | 17.51 | 9.00 | 342.83 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:19 | 4819.41 | 19.24 | 144.33 | 456.17 | 1291.97 | 16.50 | 0.83 | 403.17 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:10 | 2041.96 | 12.71 | 0.00 | 479.00 | 1177.42 | 16.18 | 0.00 | 419.83 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-04:49 | 2419.87 | 13.42 | 15.67 | 475.83 | 1202.32 | 16.16 | 0.17 | 408.33 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:40 | 6037.36 | 24.46 | 237.83 | 407.67 | 1362.64 | 16.59 | 3.50 | 360.67 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:49 | 4904.65 | 29.58 | 268.83 | 318.00 | 1761.52 | 18.26 | 33.33 | 283.50 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2753.75 | 31.20 | 228.33 | 235.33 | 2295.70 | 32.95 | 234.50 | 212.83 |
November | 135.83 | 0.55 | 0.48 | 01-NOV-09:00 | 1049.38 | 25.98 | 94.17 | 119.00 | 871.29 | 30.58 | 105.17 | 93.17 |
December | 71.17 | 0.77 | 0.48 | 04-DEC-11:30 | 176.12 | 1.83 | 0.00 | 6.50 | 128.58 | 5.28 | 0.00 | 1.00 |
Annual Sum or Average | 4053.17 | 0.53 | 4147.76 | 22.25 | 1740.67 | 3420.33 | 1755.49 | 20.73 | 941.33 | 3013.17 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 176.12 | 1.83 | 0.00 | 6.50 | 128.58 | 5.28 | 0.00 | 1.00 | |
Maximum of Months | 583.50 | 0.77 | 0.48 | 8445.01 | 34.38 | 283.67 | 479.00 | 5285.17 | 35.63 | 279.50 | 419.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.70 | 0.48 | 16-JAN-11:50 | 299.30 | 9.68 | 2.00 | 33.00 | 183.95 | 12.59 | 2.17 | 13.00 |
February | 205.83 | 0.58 | 0.48 | 01-FEB-12:09 | 1038.73 | 18.92 | 65.67 | 144.50 | 663.18 | 21.12 | 75.33 | 103.17 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:09 | 2469.94 | 20.77 | 113.33 | 280.83 | 1609.65 | 23.25 | 132.17 | 246.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3184.32 | 22.24 | 135.50 | 388.17 | 1991.78 | 24.52 | 146.17 | 352.17 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4184.21 | 22.70 | 206.33 | 465.83 | 2207.93 | 22.67 | 144.33 | 426.67 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:39 | 3609.90 | 21.90 | 218.33 | 498.67 | 1638.43 | 21.53 | 135.50 | 444.67 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:49 | 3585.10 | 21.24 | 199.67 | 483.67 | 1896.10 | 22.20 | 156.50 | 432.17 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:49 | 2990.30 | 21.44 | 166.67 | 410.17 | 1548.12 | 21.67 | 113.83 | 366.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2295.35 | 20.53 | 131.00 | 301.50 | 1222.56 | 21.56 | 112.33 | 262.67 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:40 | 1216.73 | 19.18 | 95.00 | 213.17 | 720.11 | 20.14 | 78.00 | 162.50 |
November | 135.83 | 0.63 | 0.48 | 01-NOV-09:00 | 405.25 | 15.29 | 33.83 | 69.00 | 240.88 | 17.84 | 35.00 | 22.00 |
December | 71.17 | 0.87 | 0.54 | 08-DEC-11:30 | 102.44 | 5.56 | 0.00 | 0.00 | 60.07 | 7.96 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2814.65 | 20.52 | 1367.33 | 3288.50 | 1515.03 | 21.53 | 1131.33 | 2831.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 102.44 | 5.56 | 0.00 | 0.00 | 60.07 | 7.96 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.87 | 0.54 | 4184.21 | 22.70 | 218.33 | 498.67 | 2207.93 | 24.52 | 156.50 | 444.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.51 | 31-JAN-11:30 | 173.98 | 3.60 | 0.00 | 5.50 | 104.41 | 6.85 | 0.00 | 0.00 |
February | 205.83 | 0.61 | 0.48 | 04-FEB-12:30 | 385.48 | 7.77 | 0.00 | 112.83 | 234.92 | 11.37 | 0.00 | 30.67 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:50 | 713.95 | 11.48 | 0.00 | 272.50 | 438.97 | 15.03 | 0.00 | 213.67 |
April | 421.83 | 0.50 | 0.48 | 01-APR-07:40 | 947.58 | 13.95 | 0.00 | 395.83 | 607.53 | 17.63 | 0.83 | 348.50 |
May | 545.00 | 0.50 | 0.48 | 01-MAY-04:40 | 1164.07 | 19.39 | 144.50 | 501.67 | 714.48 | 21.43 | 126.17 | 475.17 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:30 | 1384.16 | 19.77 | 173.00 | 536.17 | 818.92 | 21.96 | 141.83 | 502.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1243.43 | 18.46 | 136.67 | 517.17 | 734.95 | 20.61 | 110.50 | 469.17 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 969.09 | 15.85 | 62.33 | 424.67 | 595.86 | 19.03 | 66.50 | 374.50 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 696.07 | 11.50 | 0.00 | 296.83 | 417.31 | 14.97 | 0.00 | 223.33 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-07:00 | 482.03 | 9.02 | 0.00 | 191.50 | 278.07 | 12.54 | 0.00 | 52.67 |
November | 135.83 | 0.72 | 0.48 | 01-NOV-11:30 | 232.61 | 5.04 | 0.00 | 27.00 | 137.92 | 8.72 | 0.00 | 0.00 |
December | 71.17 | 0.91 | 0.76 | 04-DEC-11:30 | 68.50 | 0.59 | 0.00 | 0.00 | 41.41 | 2.65 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 922.82 | 14.50 | 516.50 | 3281.67 | 558.59 | 17.39 | 445.83 | 2689.83 | ||
Minimum of Months | 71.17 | 0.50 | 0.48 | 68.50 | 0.59 | 0.00 | 0.00 | 41.41 | 2.65 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.76 | 1384.16 | 19.77 | 173.00 | 536.17 | 818.92 | 21.96 | 141.83 | 502.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 23-JAN-13:20 | 253.04 | 9.39 | 1.67 | 22.67 | 153.24 | 12.40 | 1.83 | 4.50 |
February | 205.83 | 0.56 | 0.48 | 02-FEB-10:00 | 833.89 | 19.15 | 61.50 | 154.83 | 519.91 | 21.49 | 68.83 | 92.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:50 | 1862.35 | 20.51 | 96.67 | 291.67 | 1139.20 | 22.76 | 105.83 | 260.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:09 | 3634.62 | 22.18 | 139.50 | 390.17 | 1842.82 | 22.12 | 107.17 | 351.83 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-05:30 | 2848.47 | 18.75 | 117.67 | 483.33 | 1449.76 | 19.40 | 56.50 | 442.00 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-05:19 | 3007.08 | 18.13 | 111.33 | 512.17 | 1548.86 | 19.08 | 53.50 | 460.50 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-04:49 | 2617.20 | 18.09 | 114.50 | 501.50 | 1376.95 | 18.98 | 56.33 | 448.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2380.19 | 19.42 | 117.33 | 424.17 | 1448.80 | 20.98 | 91.33 | 379.17 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:00 | 1889.75 | 21.43 | 119.83 | 316.00 | 1162.55 | 22.66 | 105.33 | 267.00 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-08:20 | 956.77 | 19.35 | 85.17 | 219.17 | 561.18 | 21.34 | 72.67 | 156.83 |
November | 135.83 | 0.63 | 0.48 | 01-NOV-10:20 | 408.47 | 17.50 | 44.83 | 69.83 | 262.60 | 19.83 | 45.33 | 26.83 |
December | 71.17 | 0.89 | 0.70 | 04-DEC-11:30 | 89.22 | 5.16 | 0.00 | 0.00 | 51.96 | 7.64 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.53 | 2276.56 | 18.91 | 1010.00 | 3385.50 | 1239.70 | 20.17 | 764.67 | 2889.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 89.22 | 5.16 | 0.00 | 0.00 | 51.96 | 7.64 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.89 | 0.70 | 3634.62 | 22.18 | 139.50 | 512.17 | 1842.82 | 22.76 | 107.17 | 460.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.60 | 0.48 | 03-JAN-11:30 | 631.54 | 6.61 | 6.00 | 66.67 | 650.72 | 29.71 | 85.00 | 47.83 |
February | 205.83 | 0.53 | 0.48 | 01-FEB-11:30 | 2721.64 | 34.37 | 187.83 | 173.50 | 2358.06 | 35.63 | 190.33 | 157.67 |
March | 329.50 | 0.51 | 0.48 | 01-MAR-09:09 | 6028.40 | 31.91 | 274.00 | 299.00 | 5287.43 | 33.39 | 279.50 | 282.67 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:30 | 8447.37 | 29.67 | 283.67 | 383.67 | 1777.89 | 17.50 | 8.50 | 342.83 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:19 | 4822.09 | 19.22 | 144.33 | 456.17 | 1293.90 | 16.49 | 0.83 | 403.17 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:10 | 2044.89 | 12.68 | 0.00 | 479.00 | 1179.34 | 16.17 | 0.00 | 420.00 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-04:49 | 2422.83 | 13.40 | 15.67 | 475.83 | 1204.30 | 16.15 | 0.17 | 408.50 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:40 | 6040.02 | 24.44 | 237.83 | 407.83 | 1364.78 | 16.57 | 3.33 | 361.00 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:49 | 4906.37 | 29.56 | 268.83 | 318.00 | 1763.57 | 18.24 | 33.17 | 283.50 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2754.69 | 31.19 | 228.33 | 235.33 | 2296.93 | 32.95 | 234.50 | 213.00 |
November | 135.83 | 0.55 | 0.48 | 01-NOV-09:00 | 1049.42 | 25.97 | 94.17 | 119.00 | 871.80 | 30.57 | 105.17 | 93.17 |
December | 71.17 | 0.77 | 0.48 | 04-DEC-11:30 | 176.07 | 1.81 | 0.00 | 6.50 | 128.69 | 5.27 | 0.00 | 1.00 |
Annual Sum or Average | 4053.17 | 0.53 | 4149.82 | 22.23 | 1740.67 | 3420.50 | 1757.34 | 20.72 | 940.50 | 3014.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 176.07 | 1.81 | 0.00 | 6.50 | 128.69 | 5.27 | 0.00 | 1.00 | |
Maximum of Months | 583.50 | 0.77 | 0.48 | 8447.37 | 34.37 | 283.67 | 479.00 | 5287.43 | 35.63 | 279.50 | 420.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.70 | 0.48 | 16-JAN-11:50 | 299.50 | 9.65 | 2.00 | 33.00 | 184.21 | 12.58 | 2.17 | 13.00 |
February | 205.83 | 0.58 | 0.48 | 01-FEB-11:00 | 1039.21 | 18.90 | 65.67 | 144.50 | 663.81 | 21.11 | 75.33 | 103.33 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:09 | 2470.89 | 20.75 | 113.33 | 280.83 | 1610.93 | 23.23 | 131.83 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3185.47 | 22.21 | 135.50 | 388.17 | 1993.34 | 24.51 | 145.17 | 352.50 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4185.65 | 22.68 | 206.33 | 465.83 | 2209.60 | 22.66 | 144.33 | 426.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:39 | 3611.85 | 21.87 | 218.33 | 498.67 | 1640.24 | 21.52 | 135.50 | 445.00 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:49 | 3586.90 | 21.21 | 199.67 | 483.83 | 1897.83 | 22.19 | 156.50 | 432.17 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:49 | 2991.89 | 21.42 | 166.67 | 410.17 | 1549.73 | 21.65 | 113.33 | 366.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2296.51 | 20.51 | 131.00 | 301.50 | 1223.83 | 21.55 | 111.50 | 262.67 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:40 | 1217.56 | 19.16 | 95.00 | 213.33 | 720.93 | 20.13 | 78.00 | 162.67 |
November | 135.83 | 0.63 | 0.48 | 01-NOV-09:00 | 405.55 | 15.26 | 33.83 | 69.00 | 241.22 | 17.83 | 35.00 | 22.00 |
December | 71.17 | 0.87 | 0.54 | 08-DEC-11:30 | 102.51 | 5.53 | 0.00 | 0.00 | 60.16 | 7.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2815.96 | 20.50 | 1367.33 | 3288.83 | 1516.42 | 21.52 | 1128.67 | 2833.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 102.51 | 5.53 | 0.00 | 0.00 | 60.16 | 7.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.87 | 0.54 | 4185.65 | 22.68 | 218.33 | 498.67 | 2209.60 | 24.51 | 156.50 | 445.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.51 | 31-JAN-11:30 | 174.13 | 3.57 | 0.00 | 5.50 | 104.57 | 6.84 | 0.00 | 0.00 |
February | 205.83 | 0.61 | 0.48 | 04-FEB-12:20 | 385.82 | 7.74 | 0.00 | 112.83 | 235.27 | 11.35 | 0.00 | 30.83 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:50 | 714.62 | 11.45 | 0.00 | 272.67 | 439.60 | 15.01 | 0.00 | 213.67 |
April | 421.83 | 0.50 | 0.48 | 01-APR-07:40 | 948.29 | 13.92 | 0.00 | 395.83 | 608.30 | 17.62 | 0.83 | 348.50 |
May | 545.00 | 0.50 | 0.48 | 01-MAY-04:40 | 1164.93 | 19.36 | 144.50 | 501.83 | 715.36 | 21.42 | 126.00 | 475.17 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:30 | 1385.26 | 19.75 | 173.00 | 536.17 | 819.96 | 21.95 | 141.67 | 502.50 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1244.58 | 18.44 | 136.67 | 517.33 | 735.95 | 20.60 | 110.50 | 469.67 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 970.07 | 15.83 | 62.33 | 424.67 | 596.71 | 19.01 | 66.50 | 375.00 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 696.82 | 11.47 | 0.00 | 297.33 | 417.94 | 14.95 | 0.00 | 224.17 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-07:00 | 482.63 | 8.99 | 0.00 | 191.50 | 278.52 | 12.53 | 0.00 | 53.17 |
November | 135.83 | 0.72 | 0.48 | 01-NOV-11:30 | 232.84 | 5.01 | 0.00 | 27.00 | 138.13 | 8.71 | 0.00 | 0.00 |
December | 71.17 | 0.91 | 0.76 | 04-DEC-11:30 | 68.56 | 0.58 | 0.00 | 0.00 | 41.48 | 2.64 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 923.63 | 14.48 | 516.50 | 3282.67 | 559.34 | 17.38 | 445.50 | 2692.67 | ||
Minimum of Months | 71.17 | 0.50 | 0.48 | 68.56 | 0.58 | 0.00 | 0.00 | 41.48 | 2.64 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.76 | 1385.26 | 19.75 | 173.00 | 536.17 | 819.96 | 21.95 | 141.67 | 502.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 23-JAN-13:20 | 253.24 | 9.36 | 1.67 | 22.83 | 153.46 | 12.39 | 1.83 | 4.67 |
February | 205.83 | 0.56 | 0.48 | 02-FEB-10:00 | 834.35 | 19.12 | 61.50 | 154.83 | 520.44 | 21.47 | 68.50 | 92.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:50 | 1863.26 | 20.48 | 96.67 | 291.67 | 1140.19 | 22.75 | 105.50 | 260.50 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:09 | 3635.70 | 22.16 | 139.50 | 390.17 | 1844.33 | 22.11 | 106.33 | 352.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-05:30 | 2849.82 | 18.73 | 117.67 | 483.50 | 1451.18 | 19.38 | 56.50 | 442.17 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-05:19 | 3008.73 | 18.10 | 111.17 | 512.17 | 1550.38 | 19.07 | 53.50 | 460.50 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-04:49 | 2618.92 | 18.06 | 114.50 | 501.83 | 1378.47 | 18.97 | 56.33 | 448.50 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2381.66 | 19.39 | 117.33 | 424.17 | 1450.14 | 20.97 | 91.00 | 379.33 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:00 | 1890.79 | 21.40 | 119.83 | 316.00 | 1163.56 | 22.65 | 105.33 | 267.00 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-08:20 | 957.54 | 19.33 | 85.17 | 219.33 | 561.86 | 21.32 | 72.67 | 157.00 |
November | 135.83 | 0.63 | 0.48 | 01-NOV-10:20 | 408.77 | 17.48 | 44.83 | 69.83 | 262.93 | 19.81 | 45.33 | 27.00 |
December | 71.17 | 0.89 | 0.70 | 04-DEC-11:30 | 89.29 | 5.14 | 0.00 | 0.00 | 52.04 | 7.63 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.53 | 2277.75 | 18.88 | 1009.83 | 3386.33 | 1240.89 | 20.16 | 762.83 | 2890.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 89.29 | 5.14 | 0.00 | 0.00 | 52.04 | 7.63 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.89 | 0.70 | 3635.70 | 22.16 | 139.50 | 512.17 | 1844.33 | 22.75 | 106.33 | 460.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.222401E+11 | 97819.55 | 12-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134551E+11 | 90090.49 | 27-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.431368E+10 | 81953.77 | 15-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.526022E+09 | 64040.90 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29919150.66 | 13140.10 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2363.92 | 1.11 | 09-JUN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3135.93 | 1.14 | 12-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15346908.28 | 15406.12 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165351E+09 | 28677.49 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.651095E+09 | 53669.42 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212776E+11 | 89128.70 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343925E+11 | 105222.02 | 15-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2363.92 | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343925E+11 | 105222.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.333378E+10 | 14118.36 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148934E+10 | 15199.88 | 16-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504144E+09 | 15282.22 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15888145.75 | 12589.35 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158873E+09 | 15152.56 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140679E+10 | 15109.40 | 07-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227001E+10 | 14654.86 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.917883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333378E+10 | 15282.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249994E+10 | 16254.90 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103513E+10 | 16670.44 | 15-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330672E+09 | 16706.49 | 31-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14430724.46 | 12158.78 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145187E+09 | 16672.66 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141722E+10 | 16700.29 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240512E+10 | 16662.64 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.249994E+10 | 16706.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.434790E+10 | 25419.25 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160315E+10 | 26112.50 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511027E+09 | 26180.15 | 25-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27312174.64 | 24343.50 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285877E+09 | 26111.22 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221694E+10 | 26105.02 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402766E+10 | 26036.19 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.434790E+10 | 26180.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.989049E+09 | 14786.51 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158056E+09 | 14773.27 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13473454.01 | 10600.92 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29007751.43 | 11831.50 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4907166.84 | 4155.25 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.989049E+09 | 14786.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270126E+12 | 1130041.78 | 12-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156720E+12 | 1050372.99 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494680E+11 | 889021.34 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.566083E+10 | 639801.12 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171813E+10 | 421648.81 | 26-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90453183.78 | 149021.35 | 15-JUN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71120035.29 | 237066.78 | 05-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.819380E+09 | 227667.95 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.347019E+10 | 275678.42 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.953243E+10 | 589858.16 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235942E+12 | 886710.70 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374282E+12 | 999729.89 | 15-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110790E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 71120035.29 | 149021.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374282E+12 | 1130041.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.398593E+11 | 545690.34 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.899424E+10 | 545269.20 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.721809E+09 | 540066.72 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385981E+09 | 540518.38 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107034E+11 | 545401.70 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222645E+11 | 545541.73 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398593E+11 | 545690.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114174E+12 | 132054.47 | 03-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718651E+11 | 132042.00 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427907E+11 | 131709.71 | 01-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.668816E+10 | 135227.64 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100320E+10 | 127868.25 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252544E+11 | 131243.94 | 24-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.859084E+11 | 132073.95 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112190E+12 | 132060.74 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114174E+12 | 135227.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.724592E+11 | 193630.13 | 12-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387440E+11 | 193836.35 | 27-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160221E+11 | 193224.37 | 15-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231701E+10 | 192976.82 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.402360E+09 | 88340.92 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124128E+11 | 193695.10 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.531353E+11 | 193741.87 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723758E+11 | 193739.01 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.724592E+11 | 193836.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.990449E+11 | 290140.57 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418551E+11 | 289763.25 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168898E+11 | 289419.44 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204712E+10 | 288600.18 | 04-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350363E+09 | 58843.07 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129305E+11 | 290254.03 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.642264E+11 | 290324.13 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107372E+12 | 290319.77 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344716E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107372E+12 | 290324.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.666293E+11 | 190215.00 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355552E+11 | 189818.03 | 04-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167829E+11 | 189824.74 | 15-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132833E+10 | 189202.26 | 04-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301620E+09 | 71162.00 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117092E+11 | 189883.94 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444851E+11 | 190147.89 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.613259E+11 | 189893.93 | 11-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.666293E+11 | 190215.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.375491E+11 | 123237.85 | 12-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229468E+11 | 106851.96 | 27-FEB-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.902898E+10 | 97130.05 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.993266E+09 | 75756.89 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159602E+09 | 20919.60 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9295596.70 | 7092.05 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5864924.06 | 4619.44 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79199107.93 | 25762.27 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303727E+09 | 31412.73 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342878E+10 | 68903.63 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.336534E+11 | 96717.31 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484144E+11 | 109179.46 | 15-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5864924.06 | 4619.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.484144E+11 | 123237.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247731E+11 | 76016.89 | 23-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159598E+11 | 76017.52 | 13-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898304E+10 | 75951.05 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186109E+10 | 75984.18 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303853E+09 | 74300.01 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.705152E+10 | 76287.77 | 10-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201531E+11 | 76008.82 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242073E+11 | 76007.83 | 26-DEC-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247731E+11 | 76287.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187145E+11 | 15065.35 | 07-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141748E+11 | 15103.87 | 08-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103807E+11 | 15065.94 | 20-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.284959E+10 | 15021.80 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31647320.51 | 14889.86 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37868613.96 | 14894.51 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117760E+10 | 15106.04 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.768893E+10 | 15111.78 | 10-OCT-03:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164987E+11 | 15064.71 | 16-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192966E+11 | 15062.92 | 30-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.908510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.192966E+11 | 15111.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126269E+11 | 21348.67 | 13-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.842871E+10 | 21444.90 | 15-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.441044E+10 | 21453.66 | 16-MAR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110570E+10 | 21366.14 | 03-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1746883.34 | 6995.22 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13160875.26 | 11101.65 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.413927E+09 | 21324.45 | 29-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410815E+10 | 21335.74 | 27-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110046E+11 | 21358.86 | 01-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132819E+11 | 21347.46 | 22-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132819E+11 | 21453.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170868E+11 | 33145.62 | 13-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.963429E+10 | 33261.34 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527215E+10 | 33119.15 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129859E+10 | 32984.92 | 04-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16832478.35 | 14032.96 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17250295.48 | 13028.20 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530645E+09 | 32950.54 | 28-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.488812E+10 | 33117.83 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136856E+11 | 33140.09 | 13-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190598E+11 | 33126.28 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190598E+11 | 33261.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114499E+11 | 22453.89 | 13-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.726043E+10 | 22449.47 | 24-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435872E+10 | 22358.85 | 25-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786649E+09 | 22350.29 | 04-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8432499.21 | 7379.23 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6755228.58 | 4153.82 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.359813E+09 | 22257.30 | 28-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347840E+10 | 22363.06 | 16-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863597E+10 | 22364.77 | 13-NOV-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106227E+11 | 22363.09 | 20-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114499E+11 | 22453.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147610E+11 | 65660.80 | 12-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.971639E+10 | 61422.63 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407493E+10 | 52638.51 | 01-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239400E+09 | 12208.99 | 11-APR-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 223.74 | 0.40 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107815E+10 | 11949.98 | 30-OCT-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136974E+11 | 56998.63 | 14-NOV-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201034E+11 | 57885.19 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.636708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201034E+11 | 65660.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2880324.63 | 2880324.63 | 414.34 | 19-JAN-09:00 | 414.34 | 0.00 |
February | 0.00 | 0.00 | 19796508.85 | 19796508.85 | 6659.75 | 09-FEB-13:30 | 6659.75 | 0.00 |
March | 0.00 | 0.00 | 0.514415E+09 | 0.514415E+09 | 23650.56 | 22-MAR-11:00 | 23650.56 | 0.00 |
April | 0.00 | 0.00 | 0.196701E+10 | 0.196701E+10 | 37613.14 | 13-APR-12:05 | 37613.14 | 0.00 |
May | 0.00 | 0.00 | 0.160568E+11 | 0.160568E+11 | 101671.09 | 31-MAY-16:00 | 101671.09 | 0.00 |
June | 0.00 | 0.00 | 0.644174E+11 | 0.640922E+11 | 161644.76 | 30-JUN-12:05 | 140902.13 | 0.20 |
July | 0.00 | 0.00 | 0.844005E+11 | 0.833672E+11 | 179284.46 | 03-JUL-15:00 | 76640.73 | 0.49 |
August | 0.00 | 0.00 | 0.515766E+11 | 0.514749E+11 | 146242.41 | 11-AUG-15:40 | 146242.41 | 0.36 |
September | 0.00 | 0.00 | 0.269883E+10 | 0.269883E+10 | 41491.19 | 07-SEP-16:00 | 41491.19 | 0.01 |
October | 0.00 | 0.00 | 0.129479E+10 | 0.129479E+10 | 47210.00 | 03-OCT-10:50 | 47210.00 | 0.00 |
November | 0.00 | 0.00 | 14688228.62 | 14688228.62 | 5847.81 | 01-NOV-07:10 | 5847.81 | 0.00 |
December | 0.00 | 0.00 | 6597022.99 | 6597022.99 | 2816.83 | 27-DEC-08:20 | 2816.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222970E+12 | 0.221510E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 2880324.63 | 2880324.63 | 414.34 | 414.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.844005E+11 | 0.833672E+11 | 179284.46 | 146242.41 | 0.49 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2403088.68 | 2403088.68 | 446.44 | 19-JAN-13:40 | 446.44 | 0.00 |
February | 0.00 | 0.00 | 23373261.01 | 23373261.01 | 7307.05 | 17-FEB-13:10 | 7307.05 | 0.00 |
March | 0.00 | 0.00 | 0.135499E+10 | 0.135499E+10 | 114449.85 | 22-MAR-14:40 | 114449.85 | 0.00 |
April | 0.00 | 0.00 | 0.568710E+11 | 0.568710E+11 | 538978.38 | 20-APR-13:20 | 538978.38 | 0.00 |
May | 0.00 | 0.00 | 0.957058E+11 | 0.957058E+11 | 767862.05 | 31-MAY-16:00 | 767862.05 | 0.00 |
June | 0.00 | 0.00 | 0.391172E+12 | 0.390176E+12 | 1188159.25 | 30-JUN-12:05 | 1075548.50 | 0.17 |
July | 0.00 | 0.00 | 0.500169E+12 | 0.498830E+12 | 1205932.35 | 23-JUL-15:01 | 1205932.35 | 0.41 |
August | 0.00 | 0.00 | 0.297696E+12 | 0.297696E+12 | 1101584.98 | 11-AUG-15:40 | 1101584.98 | 0.27 |
September | 0.00 | 0.00 | 0.445951E+11 | 0.445951E+11 | 547763.42 | 18-SEP-15:50 | 547763.42 | 0.02 |
October | 0.00 | 0.00 | 0.869322E+10 | 0.869322E+10 | 365735.35 | 03-OCT-14:40 | 365735.35 | 0.00 |
November | 0.00 | 0.00 | 3156778.28 | 3156778.28 | 770.48 | 02-NOV-07:40 | 770.48 | 0.00 |
December | 0.00 | 0.00 | 380445.70 | 380445.70 | 358.89 | 23-DEC-11:30 | 358.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139629E+13 | 0.139395E+13 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 380445.70 | 380445.70 | 358.89 | 358.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.500169E+12 | 0.498830E+12 | 1205932.35 | 1205932.35 | 0.41 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 227935.96 | 227935.96 | 149.30 | 15-FEB-13:50 | 149.30 | 0.00 |
March | 0.00 | 0.00 | 14509425.32 | 14509425.32 | 868.43 | 27-MAR-13:10 | 868.43 | 0.00 |
April | 0.00 | 0.00 | 0.229881E+10 | 0.229881E+10 | 66365.37 | 21-APR-15:20 | 66365.37 | 0.00 |
May | 0.00 | 0.00 | 0.912880E+10 | 0.912880E+10 | 82058.34 | 31-MAY-16:00 | 82058.34 | 0.00 |
June | 0.00 | 0.00 | 0.403024E+11 | 0.401918E+11 | 128033.62 | 30-JUN-12:30 | 119342.74 | 0.16 |
July | 0.00 | 0.00 | 0.516559E+11 | 0.515368E+11 | 125836.19 | 21-JUL-14:40 | 125836.19 | 0.40 |
August | 0.00 | 0.00 | 0.284005E+11 | 0.284005E+11 | 119171.17 | 11-AUG-15:40 | 119171.17 | 0.26 |
September | 0.00 | 0.00 | 0.219633E+10 | 0.219633E+10 | 51822.87 | 08-SEP-15:40 | 51822.87 | 0.02 |
October | 0.00 | 0.00 | 0.123207E+09 | 0.123207E+09 | 13068.06 | 03-OCT-14:40 | 13068.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2084.26 | 2084.26 | 4.99 | 23-DEC-13:09 | 4.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134121E+12 | 0.133891E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.516559E+11 | 0.515368E+11 | 128033.62 | 125836.19 | 0.40 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 95023544.09 | 95023544.09 | 21365.07 | 06-JAN-15:20 | 21365.07 | 0.00 |
February | 0.00 | 0.00 | 0.176569E+09 | 0.176569E+09 | 16199.96 | 06-FEB-07:15 | 16199.96 | 0.00 |
March | 0.00 | 0.00 | 0.250971E+09 | 0.250971E+09 | 19042.11 | 28-MAR-06:15 | 19042.11 | 0.00 |
April | 0.00 | 0.00 | 0.286377E+09 | 0.286377E+09 | 21699.96 | 11-APR-06:16 | 21699.96 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 990763.83 | 990763.83 | 14861.46 | 29-SEP-06:18 | 14861.46 | 0.00 |
October | 0.00 | 0.00 | 0.203951E+09 | 0.203951E+09 | 20347.68 | 26-OCT-06:15 | 20347.68 | 0.00 |
November | 0.00 | 0.00 | 0.279328E+09 | 0.279328E+09 | 18831.10 | 07-NOV-08:25 | 18831.10 | 0.00 |
December | 0.00 | 0.00 | 0.157178E+09 | 0.157178E+09 | 20821.80 | 18-DEC-15:07 | 20821.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145039E+10 | 0.145039E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.286377E+09 | 0.286377E+09 | 21699.96 | 21699.96 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.628578E+10 | 0.588073E+10 | 2788.00 | 19-JAN-05:01 | 2630.89 | 0.00 |
February | 0.00 | 0.00 | 0.107547E+11 | 0.975606E+10 | 5434.64 | 10-FEB-16:00 | 5057.97 | 0.00 |
March | 0.00 | 0.00 | 0.145508E+11 | 0.141015E+11 | 6071.99 | 21-MAR-17:40 | 5272.66 | 0.00 |
April | 0.00 | 0.00 | 0.159083E+11 | 0.158348E+11 | 69249.47 | 22-APR-14:00 | 69249.47 | 0.00 |
May | 0.00 | 0.00 | 0.947786E+10 | 0.914381E+10 | 4932.37 | 30-MAY-11:40 | 4861.39 | 0.00 |
June | 0.00 | 0.00 | 0.504746E+11 | 0.471371E+11 | 253768.72 | 30-JUN-12:00 | 183327.49 | 0.00 |
July | 0.00 | 0.00 | 0.208737E+12 | 0.173893E+12 | 388599.99 | 29-JUL-18:23 | 314627.68 | 0.00 |
August | 0.00 | 0.00 | 0.257326E+12 | 0.199416E+12 | 376357.14 | 23-AUG-16:00 | 350955.53 | 0.00 |
September | 0.00 | 0.00 | 0.514245E+10 | 0.478197E+10 | 4916.31 | 07-SEP-15:50 | 4855.64 | 0.00 |
October | 0.00 | 0.00 | 0.122857E+11 | 0.112551E+11 | 5866.14 | 31-OCT-23:10 | 5289.39 | 0.00 |
November | 0.00 | 0.00 | 0.145349E+11 | 0.136412E+11 | 6088.34 | 27-NOV-05:41 | 5276.14 | 0.00 |
December | 0.00 | 0.00 | 0.147821E+11 | 0.146783E+11 | 6295.96 | 01-DEC-00:10 | 5491.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.620261E+12 | 0.519519E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.514245E+10 | 0.478197E+10 | 2788.00 | 2630.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.257326E+12 | 0.199416E+12 | 388599.99 | 350955.53 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177807E+10 | 0.177807E+10 | 1315.71 | 22-JAN-15:20 | 1315.71 | 0.00 |
February | 0.00 | 0.00 | 0.719100E+10 | 0.719100E+10 | 3686.82 | 12-FEB-15:45 | 3686.82 | 0.00 |
March | 0.00 | 0.00 | 0.141657E+11 | 0.141657E+11 | 7424.07 | 31-MAR-24:00 | 7424.07 | 0.00 |
April | 0.00 | 0.00 | 0.198204E+11 | 0.198204E+11 | 9035.76 | 22-APR-19:00 | 9035.76 | 0.00 |
May | 0.00 | 0.00 | 0.594982E+10 | 0.594964E+10 | 4136.85 | 31-MAY-24:00 | 4136.85 | 0.00 |
June | 0.00 | 0.00 | 0.109895E+11 | 0.109117E+11 | 6055.30 | 30-JUN-24:00 | 6047.81 | 0.00 |
July | 0.00 | 0.00 | 0.165958E+11 | 0.164327E+11 | 8032.87 | 31-JUL-23:50 | 8003.50 | 0.00 |
August | 0.00 | 0.00 | 0.213925E+11 | 0.212580E+11 | 9246.27 | 27-AUG-19:00 | 9245.36 | 0.00 |
September | 0.00 | 0.00 | 0.532941E+10 | 0.531252E+10 | 3633.55 | 30-SEP-24:00 | 3633.55 | 0.00 |
October | 0.00 | 0.00 | 0.941389E+10 | 0.941363E+10 | 5197.37 | 31-OCT-24:00 | 5197.37 | 0.00 |
November | 0.00 | 0.00 | 0.127836E+11 | 0.127836E+11 | 5615.42 | 19-NOV-15:27 | 5615.42 | 0.00 |
December | 0.00 | 0.00 | 0.180901E+11 | 0.180901E+11 | 7423.46 | 24-DEC-18:00 | 7423.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143500E+12 | 0.143107E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.177807E+10 | 0.177807E+10 | 1315.71 | 1315.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213925E+11 | 0.212580E+11 | 9246.27 | 9245.36 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.584588E+09 | 0.584588E+09 | 5793.77 | 27-JAN-22:04 | 5793.77 | 0.00 |
February | 0.00 | 0.00 | 0.437132E+11 | 0.437132E+11 | 30432.10 | 16-FEB-16:15 | 30432.10 | 0.00 |
March | 0.00 | 0.00 | 0.113760E+12 | 0.113760E+12 | 65940.52 | 31-MAR-23:20 | 65940.52 | 0.00 |
April | 0.00 | 0.00 | 0.179719E+12 | 0.179719E+12 | 86199.90 | 22-APR-18:50 | 86199.90 | 0.00 |
May | 0.00 | 0.00 | 0.500133E+11 | 0.500114E+11 | 37947.47 | 31-MAY-24:00 | 37947.47 | 0.00 |
June | 0.00 | 0.00 | 0.100927E+12 | 0.100157E+12 | 56840.74 | 30-JUN-23:20 | 56587.65 | 0.00 |
July | 0.00 | 0.00 | 0.154102E+12 | 0.152486E+12 | 76150.82 | 31-JUL-23:10 | 75767.57 | 0.00 |
August | 0.00 | 0.00 | 0.199099E+12 | 0.197762E+12 | 84521.92 | 27-AUG-18:47 | 84521.92 | 0.00 |
September | 0.00 | 0.00 | 0.395391E+11 | 0.393776E+11 | 29520.40 | 30-SEP-23:40 | 29520.40 | 0.00 |
October | 0.00 | 0.00 | 0.690329E+11 | 0.690300E+11 | 40279.54 | 31-OCT-23:20 | 40279.54 | 0.00 |
November | 0.00 | 0.00 | 0.911688E+11 | 0.911688E+11 | 45938.45 | 08-NOV-15:50 | 45938.45 | 0.00 |
December | 0.00 | 0.00 | 0.137505E+12 | 0.137505E+12 | 59743.66 | 29-DEC-22:02 | 59743.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117916E+13 | 0.117527E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.584588E+09 | 0.584588E+09 | 5793.77 | 5793.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199099E+12 | 0.197762E+12 | 86199.90 | 86199.90 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.238560E+10 | 0.238560E+10 | 2633.17 | 09-FEB-16:00 | 2633.17 | 0.00 |
March | 0.00 | 0.00 | 0.905063E+10 | 0.905063E+10 | 5654.36 | 31-MAR-23:10 | 5654.36 | 0.00 |
April | 0.00 | 0.00 | 0.164887E+11 | 0.164887E+11 | 8514.95 | 22-APR-18:50 | 8514.95 | 0.00 |
May | 0.00 | 0.00 | 0.447053E+10 | 0.447035E+10 | 3732.25 | 31-MAY-23:50 | 3732.25 | 0.00 |
June | 0.00 | 0.00 | 0.995794E+10 | 0.988102E+10 | 5653.51 | 30-JUN-23:20 | 5627.85 | 0.00 |
July | 0.00 | 0.00 | 0.152998E+11 | 0.151383E+11 | 7583.68 | 31-JUL-23:10 | 7545.17 | 0.00 |
August | 0.00 | 0.00 | 0.196083E+11 | 0.194748E+11 | 8504.15 | 27-AUG-18:32 | 8504.15 | 0.00 |
September | 0.00 | 0.00 | 0.261764E+10 | 0.260224E+10 | 2665.75 | 02-SEP-18:10 | 2665.75 | 0.00 |
October | 0.00 | 0.00 | 0.439408E+10 | 0.439382E+10 | 3552.50 | 03-OCT-16:00 | 3552.50 | 0.00 |
November | 0.00 | 0.00 | 0.681833E+10 | 0.681833E+10 | 4056.74 | 08-NOV-15:50 | 4056.74 | 0.00 |
December | 0.00 | 0.00 | 0.116313E+11 | 0.116313E+11 | 5581.67 | 19-DEC-22:05 | 5581.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.102723E+12 | 0.102335E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196083E+11 | 0.194748E+11 | 8514.95 | 8514.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 309241.16 | 2175238.94 | 12-JAN-07:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 189009.09 | 2215408.74 | 27-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 72312.38 | 1675688.85 | 01-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 10660.49 | 1530214.84 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 730.53 | 452752.35 | 26-MAY-13:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 36.56 | 149093.98 | 15-JUN-09:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.58 | 246142.97 | 05-JUL-13:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 368.77 | 288355.39 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 3361.72 | 671254.81 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39092.44 | 1633055.50 | 30-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 244918.97 | 1907416.11 | 27-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 352032.10 | 1880191.45 | 15-DEC-07:02 |
Annual Sum or Average | 0.00 | 101505.76 | ||||
Minimum of Months | 0.00 | 0.00 | 29.58 | 149093.98 | ||
Maximum of Months | 0.00 | 0.00 | 352032.10 | 2215408.74 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 126.36 | 5435.75 | 23-JAN-15:20 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 195.93 | 14169.42 | 16-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1000.47 | 112032.67 | 22-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24160.53 | 563657.83 | 21-APR-12:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 45899.38 | 1134987.18 | 31-MAY-15:20 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 196363.10 | 1504399.38 | 20-JUN-13:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 246611.99 | 1583011.87 | 19-JUL-14:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 144539.15 | 1487938.18 | 11-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 19595.09 | 580049.13 | 18-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4077.40 | 383534.42 | 03-OCT-14:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 281.21 | 17574.35 | 07-NOV-08:25 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 190.18 | 13773.10 | 18-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 57351.44 | 0.00 | ||||
Minimum of Months | 126.36 | 5435.75 | 0.00 | 0.00 | ||
Maximum of Months | 246611.99 | 1583011.87 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.62 | 3168.35 | 24-JAN-11:20 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 67.43 | 13199.01 | 16-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 795.73 | 110411.39 | 22-MAR-14:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23618.64 | 579691.18 | 21-APR-12:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 45096.96 | 1014430.00 | 31-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 194406.24 | 1476807.98 | 30-JUN-12:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 246211.22 | 1548049.13 | 21-JUL-13:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 143921.14 | 1505151.21 | 11-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 19052.98 | 578681.22 | 18-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 3834.73 | 381881.83 | 03-OCT-14:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 115.47 | 21330.69 | 07-NOV-08:25 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 58.62 | 19780.83 | 18-DEC-15:07 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 56864.27 | 0.00 | ||||
Minimum of Months | 9.62 | 3168.35 | 0.00 | 0.00 | ||
Maximum of Months | 246211.22 | 1548049.13 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8599.74 | 37996.15 | 04-JAN-12:02 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 37762.59 | 128727.76 | 02-FEB-13:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 74748.10 | 150400.35 | 11-MAR-13:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 114319.95 | 296144.52 | 27-APR-21:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 41578.93 | 279013.29 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 151160.81 | 1084024.86 | 30-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 314791.56 | 1390173.97 | 29-JUL-17:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 311860.43 | 1250550.87 | 11-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 29716.04 | 81944.69 | 08-SEP-10:05 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 48669.24 | 131370.18 | 04-OCT-09:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 64866.81 | 172389.60 | 18-NOV-12:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88923.89 | 270306.54 | 18-DEC-10:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 108009.83 | 0.00 | ||||
Minimum of Months | 8599.74 | 37996.15 | 0.00 | 0.00 | ||
Maximum of Months | 314791.56 | 1390173.97 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 17739.75 | 62780.50 | 17-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17847.57 | 62780.22 | 01-FEB-12:43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18970.66 | 62780.03 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17768.26 | 62780.03 | 07-APR-11:35 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 18229.21 | 62779.72 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18000.47 | 61218.35 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15940.88 | 58671.81 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17042.25 | 56912.75 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 15913.22 | 56528.81 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16196.61 | 58205.21 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17004.75 | 60510.58 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 17043.40 | 62780.01 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 17305.15 | ||||
Minimum of Months | 0.00 | 0.00 | 15913.22 | 56528.81 | ||
Maximum of Months | 0.00 | 0.00 | 18970.66 | 62780.50 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12.85 | 8113.38 | 18-JAN-15:00 | 1902.60 | 127832.69 | 21-JAN-11:07 |
February | 11.96 | 8114.04 | 17-FEB-20:40 | 2050.36 | 124382.71 | 02-FEB-13:40 |
March | 127.30 | 86038.46 | 22-MAR-14:30 | 2790.80 | 129423.94 | 10-MAR-07:15 |
April | 22158.36 | 631738.38 | 21-APR-12:10 | 3348.98 | 120560.55 | 04-APR-14:40 |
May | 46311.57 | 1354939.89 | 31-MAY-15:20 | 1935.77 | 111977.89 | 03-MAY-06:40 |
June | 232006.01 | 2220961.20 | 30-JUN-12:10 | 1340.95 | 74410.91 | 13-JUN-05:20 |
July | 306070.54 | 2205288.46 | 03-JUL-15:00 | 1019.32 | 58050.17 | 11-JUL-22:50 |
August | 170099.47 | 2052478.93 | 11-AUG-14:30 | 1757.59 | 100018.24 | 30-AUG-07:00 |
September | 18004.03 | 662069.72 | 18-SEP-16:00 | 2533.23 | 123275.00 | 29-SEP-13:10 |
October | 3141.22 | 437545.91 | 03-OCT-14:40 | 2685.66 | 123027.24 | 26-OCT-12:50 |
November | 10.13 | 8037.02 | 13-NOV-16:30 | 2652.27 | 138472.28 | 17-NOV-15:03 |
December | 7.78 | 6528.79 | 08-DEC-15:00 | 2007.99 | 131083.43 | 30-DEC-15:03 |
Annual Sum or Average | 67026.25 | 2166.48 | ||||
Minimum of Months | 7.78 | 6528.79 | 1019.32 | 58050.17 | ||
Maximum of Months | 306070.54 | 2220961.20 | 3348.98 | 138472.28 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.244511E+10 | 0.31 | 12690.43 | 20-JAN-06:01 | 1.37 |
February | 0.264442E+10 | 0.31 | 13273.94 | 15-FEB-06:01 | 1.41 |
March | 0.496201E+10 | 0.39 | 13273.94 | 14-MAR-05:01 | 1.41 |
April | 0.955535E+10 | 0.55 | 21509.25 | 20-APR-15:50 | 1.91 |
May | 0.180505E+11 | 0.78 | 21509.25 | 08-MAY-05:02 | 1.91 |
June | 0.221068E+11 | 0.95 | 21509.25 | 01-JUN-11:50 | 1.90 |
July | 0.217095E+11 | 0.92 | 21509.25 | 01-JUL-05:02 | 1.89 |
August | 0.223951E+11 | 0.95 | 21509.25 | 01-AUG-05:03 | 1.89 |
September | 0.123338E+11 | 0.63 | 21509.25 | 07-SEP-11:00 | 1.90 |
October | 0.473572E+10 | 0.36 | 13633.36 | 03-OCT-14:00 | 1.43 |
November | 0.285626E+10 | 0.31 | 13273.94 | 07-NOV-06:01 | 1.41 |
December | 0.280248E+10 | 0.31 | 13208.41 | 21-DEC-06:01 | 1.40 |
Annual Sum or Average | 0.126597E+12 | 0.57 | |||
Minimum of Months | 0.244511E+10 | 0.31 | 12690.43 | 1.37 | |
Maximum of Months | 0.223951E+11 | 0.95 | 21509.25 | 1.91 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307621E+11 | 0.39 | 63435.98 | 02-JAN-04:01 | 0.94 |
February | 0.246715E+11 | 0.35 | 63435.98 | 01-FEB-06:01 | 0.94 |
March | 0.307151E+11 | 0.35 | 76642.16 | 23-MAR-05:03 | 1.05 |
April | 0.503959E+11 | 0.40 | 147826.33 | 21-APR-15:50 | 1.57 |
May | 0.828724E+11 | 0.51 | 164071.63 | 31-MAY-14:30 | 1.68 |
June | 0.105330E+12 | 0.59 | 200167.87 | 08-JUN-05:01 | 1.90 |
July | 0.983884E+11 | 0.55 | 200167.87 | 07-JUL-05:01 | 1.89 |
August | 0.856521E+11 | 0.51 | 200167.87 | 02-AUG-05:02 | 1.89 |
September | 0.419870E+11 | 0.36 | 110434.41 | 07-SEP-15:20 | 1.31 |
October | 0.261486E+11 | 0.30 | 73205.67 | 03-OCT-14:05 | 1.02 |
November | 0.252960E+11 | 0.34 | 63435.98 | 06-NOV-06:01 | 0.94 |
December | 0.284713E+11 | 0.36 | 63435.98 | 04-DEC-05:01 | 0.94 |
Annual Sum or Average | 0.630690E+12 | 0.42 | |||
Minimum of Months | 0.246715E+11 | 0.30 | 63435.98 | 0.94 | |
Maximum of Months | 0.105330E+12 | 0.59 | 200167.87 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.393295E+10 | 0.45 | 5916.31 | 02-JAN-04:01 | 0.87 |
February | 0.329372E+10 | 0.44 | 5916.31 | 01-FEB-05:01 | 0.87 |
March | 0.338702E+10 | 0.40 | 5916.31 | 01-MAR-05:01 | 0.87 |
April | 0.379929E+10 | 0.37 | 12123.86 | 21-APR-15:40 | 1.33 |
May | 0.652103E+10 | 0.43 | 16901.82 | 31-MAY-14:40 | 1.63 |
June | 0.963711E+10 | 0.54 | 18310.57 | 20-JUN-15:30 | 1.70 |
July | 0.900278E+10 | 0.50 | 19890.49 | 07-JUL-05:01 | 1.79 |
August | 0.709566E+10 | 0.45 | 18550.67 | 10-AUG-15:50 | 1.72 |
September | 0.294366E+10 | 0.32 | 7842.86 | 08-SEP-15:30 | 1.01 |
October | 0.283662E+10 | 0.36 | 5916.31 | 10-OCT-03:11 | 0.86 |
November | 0.362747E+10 | 0.44 | 5916.31 | 01-NOV-04:01 | 0.87 |
December | 0.403936E+10 | 0.46 | 5916.31 | 01-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.601167E+11 | 0.43 | |||
Minimum of Months | 0.283662E+10 | 0.32 | 5916.31 | 0.86 | |
Maximum of Months | 0.963711E+10 | 0.54 | 19890.49 | 1.79 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.559003E+10 | 0.49 | 11844.19 | 04-JAN-07:05 | 1.92 |
February | 0.789577E+10 | 0.63 | 11844.19 | 01-FEB-07:12 | 1.92 |
March | 0.122324E+11 | 0.80 | 11844.19 | 01-MAR-07:03 | 1.93 |
April | 0.106760E+11 | 0.70 | 11844.19 | 01-APR-06:12 | 1.93 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.164064E+10 | 0.10 | 11844.19 | 28-SEP-06:10 | 1.89 |
October | 0.992924E+10 | 0.63 | 11844.19 | 03-OCT-06:11 | 1.90 |
November | 0.831310E+10 | 0.61 | 11844.19 | 01-NOV-06:12 | 1.92 |
December | 0.688198E+10 | 0.53 | 11844.19 | 01-DEC-07:12 | 1.93 |
Annual Sum or Average | 0.631592E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122324E+11 | 0.80 | 11844.19 | 1.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110070E+12 | 1.37 | 41095.44 | 01-JAN-00:02 | 1.37 |
February | 0.994181E+11 | 1.37 | 41095.44 | 01-FEB-00:03 | 1.37 |
March | 0.110070E+12 | 1.37 | 41095.44 | 01-MAR-00:10 | 1.37 |
April | 0.106519E+12 | 1.38 | 41095.44 | 01-APR-00:10 | 1.38 |
May | 0.110070E+12 | 1.37 | 41095.44 | 01-MAY-00:05 | 1.37 |
June | 0.106519E+12 | 1.37 | 41095.44 | 01-JUN-00:10 | 1.37 |
July | 0.110070E+12 | 1.36 | 41095.44 | 01-JUL-00:10 | 1.36 |
August | 0.110070E+12 | 1.37 | 41095.44 | 01-AUG-00:05 | 1.37 |
September | 0.106519E+12 | 1.37 | 41095.44 | 01-SEP-00:10 | 1.37 |
October | 0.110070E+12 | 1.37 | 41095.44 | 01-OCT-00:10 | 1.37 |
November | 0.106519E+12 | 1.37 | 41095.44 | 01-NOV-00:10 | 1.37 |
December | 0.110070E+12 | 1.37 | 41095.44 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.129599E+13 | 1.37 | |||
Minimum of Months | 0.994181E+11 | 1.36 | 41095.44 | 1.36 | |
Maximum of Months | 0.110070E+12 | 1.38 | 41095.44 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151794E+10 | 0.94 | 566.73 | 01-JAN-00:02 | 0.93 |
February | 0.137104E+10 | 0.94 | 566.73 | 01-FEB-00:03 | 0.94 |
March | 0.151794E+10 | 0.94 | 566.73 | 01-MAR-00:10 | 0.94 |
April | 0.146897E+10 | 0.93 | 566.73 | 01-APR-00:10 | 0.94 |
May | 0.151794E+10 | 0.93 | 566.73 | 01-MAY-00:05 | 0.93 |
June | 0.146897E+10 | 0.93 | 566.73 | 01-JUN-00:10 | 0.93 |
July | 0.151794E+10 | 0.93 | 566.73 | 01-JUL-00:10 | 0.93 |
August | 0.151794E+10 | 0.93 | 566.73 | 01-AUG-00:05 | 0.93 |
September | 0.146897E+10 | 0.93 | 566.73 | 01-SEP-00:10 | 0.93 |
October | 0.151794E+10 | 0.93 | 566.73 | 01-OCT-00:10 | 0.93 |
November | 0.146897E+10 | 0.94 | 566.73 | 01-NOV-00:10 | 0.94 |
December | 0.151794E+10 | 0.94 | 566.73 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.178725E+11 | 0.93 | |||
Minimum of Months | 0.137104E+10 | 0.93 | 566.73 | 0.93 | |
Maximum of Months | 0.151794E+10 | 0.94 | 566.73 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146183E+11 | 0.94 | 5457.83 | 01-JAN-00:02 | 0.93 |
February | 0.132036E+11 | 0.94 | 5457.83 | 01-FEB-00:03 | 0.94 |
March | 0.146183E+11 | 0.94 | 5457.83 | 01-MAR-00:10 | 0.94 |
April | 0.141467E+11 | 0.93 | 5457.83 | 01-APR-00:10 | 0.94 |
May | 0.146183E+11 | 0.93 | 5457.83 | 01-MAY-00:05 | 0.93 |
June | 0.141467E+11 | 0.93 | 5457.83 | 01-JUN-00:10 | 0.93 |
July | 0.146183E+11 | 0.93 | 5457.83 | 01-JUL-00:10 | 0.93 |
August | 0.146183E+11 | 0.93 | 5457.83 | 01-AUG-00:05 | 0.93 |
September | 0.141467E+11 | 0.93 | 5457.83 | 01-SEP-00:10 | 0.93 |
October | 0.146183E+11 | 0.93 | 5457.83 | 01-OCT-00:10 | 0.94 |
November | 0.141467E+11 | 0.94 | 5457.83 | 01-NOV-00:10 | 0.94 |
December | 0.146183E+11 | 0.94 | 5457.83 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.172118E+12 | 0.93 | |||
Minimum of Months | 0.132036E+11 | 0.93 | 5457.83 | 0.93 | |
Maximum of Months | 0.146183E+11 | 0.94 | 5457.83 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147494E+10 | 0.94 | 550.68 | 01-JAN-00:02 | 0.93 |
February | 0.133220E+10 | 0.94 | 550.68 | 01-FEB-00:03 | 0.94 |
March | 0.147494E+10 | 0.94 | 550.68 | 01-MAR-00:10 | 0.94 |
April | 0.142736E+10 | 0.93 | 550.68 | 01-APR-00:10 | 0.94 |
May | 0.147494E+10 | 0.93 | 550.68 | 01-MAY-00:05 | 0.93 |
June | 0.142736E+10 | 0.93 | 550.68 | 01-JUN-00:10 | 0.93 |
July | 0.147494E+10 | 0.93 | 550.68 | 01-JUL-00:10 | 0.93 |
August | 0.147494E+10 | 0.93 | 550.68 | 01-AUG-00:05 | 0.93 |
September | 0.142736E+10 | 0.93 | 550.68 | 01-SEP-00:10 | 0.93 |
October | 0.147494E+10 | 0.93 | 550.68 | 01-OCT-00:10 | 0.94 |
November | 0.142736E+10 | 0.94 | 550.68 | 01-NOV-00:10 | 0.94 |
December | 0.147494E+10 | 0.94 | 550.68 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.173662E+11 | 0.93 | |||
Minimum of Months | 0.133220E+10 | 0.93 | 550.68 | 0.93 | |
Maximum of Months | 0.147494E+10 | 0.94 | 550.68 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.257305E+09 | 0.233890E+09 | 2238.12 | 12-JAN-07:10 | 2034.45 | 2034.45 | 52.10 | 16.22 |
February | 0.113399E+09 | 0.103079E+09 | 2117.40 | 27-FEB-07:10 | 1924.72 | 1924.72 | 48.87 | 15.87 |
March | 32944314.90 | 29946382.24 | 1011.57 | 01-MAR-06:03 | 919.52 | 919.52 | 47.32 | 11.56 |
April | 1924064.20 | 1748974.36 | 394.52 | 03-APR-05:02 | 358.62 | 358.62 | 45.31 | 7.54 |
May | 79672.83 | 72422.60 | 33.33 | 26-MAY-13:05 | 30.30 | 30.30 | 29.55 | 2.07 |
June | 3212.90 | 2920.53 | 5.87 | 15-JUN-09:05 | 5.34 | 5.34 | 26.95 | 0.65 |
July | 3708.42 | 3370.95 | 11.88 | 05-JUL-13:05 | 10.80 | 10.80 | 27.04 | 1.07 |
August | 37340.30 | 33942.33 | 15.25 | 31-AUG-06:10 | 13.86 | 13.86 | 27.53 | 1.27 |
September | 330389.85 | 300324.37 | 69.13 | 30-SEP-05:03 | 62.84 | 62.84 | 30.75 | 3.13 |
October | 7963735.84 | 7239035.88 | 998.09 | 30-OCT-05:01 | 907.27 | 907.27 | 47.99 | 11.49 |
November | 0.156364E+09 | 0.142135E+09 | 1252.90 | 27-NOV-07:08 | 1138.88 | 1138.88 | 46.09 | 12.70 |
December | 0.252008E+09 | 0.229075E+09 | 1391.32 | 15-DEC-07:10 | 1264.71 | 1264.71 | 50.03 | 13.26 |
Annual Sum or Average | 0.822362E+09 | 0.747527E+09 | ||||||
Minimum of Months | 3212.90 | 2920.53 | 5.87 | 5.34 | 5.34 | 26.95 | 0.65 | |
Maximum of Months | 0.257305E+09 | 0.233890E+09 | 2238.12 | 2034.45 | 2034.45 | 52.10 | 16.22 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 7153.32 | 6502.37 | 1.39 | 06-JAN-15:20 | 1.27 | 1.27 | 6.70 | 0.37 |
February | 16777.74 | 15250.97 | 1.28 | 16-FEB-13:30 | 1.16 | 1.16 | 6.70 | 0.34 |
March | 254682.74 | 231506.61 | 18.75 | 22-MAR-14:40 | 17.04 | 17.04 | 6.70 | 2.76 |
April | 13447731.19 | 12223987.66 | 198.08 | 21-APR-12:05 | 180.06 | 180.06 | 6.70 | 10.48 |
May | 34592113.09 | 31444230.80 | 588.58 | 31-MAY-15:10 | 535.02 | 535.02 | 6.71 | 17.66 |
June | 0.317933E+09 | 0.289001E+09 | 3243.62 | 20-JUN-15:10 | 2948.45 | 2948.45 | 6.72 | 37.08 |
July | 0.632757E+09 | 0.575176E+09 | 4840.71 | 07-JUL-10:05 | 4400.21 | 4400.21 | 9.17 | 43.65 |
August | 0.336669E+09 | 0.306032E+09 | 3899.21 | 11-AUG-15:40 | 3544.38 | 3544.38 | 6.72 | 39.99 |
September | 11714057.62 | 10648078.37 | 411.87 | 01-SEP-13:20 | 374.39 | 374.39 | 6.71 | 14.96 |
October | 1808864.49 | 1644257.82 | 96.46 | 03-OCT-14:40 | 87.68 | 87.68 | 6.70 | 7.22 |
November | 23325.88 | 21203.23 | 1.84 | 07-NOV-08:25 | 1.67 | 1.67 | 6.70 | 0.47 |
December | 12426.49 | 11295.68 | 1.80 | 18-DEC-15:07 | 1.64 | 1.64 | 6.70 | 0.47 |
Annual Sum or Average | 0.134924E+10 | 0.122646E+10 | ||||||
Minimum of Months | 7153.32 | 6502.37 | 1.28 | 1.16 | 1.16 | 6.70 | 0.34 | |
Maximum of Months | 0.632757E+09 | 0.575176E+09 | 4840.71 | 4400.21 | 4400.21 | 9.17 | 43.65 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.344371E+09 | 0.313033E+09 | 3146.98 | 04-JAN-14:10 | 2860.60 | 2860.60 | 6.71 | 28.12 |
February | 0.341977E+09 | 0.310857E+09 | 3146.98 | 01-FEB-09:00 | 2860.60 | 2860.60 | 6.72 | 28.12 |
March | 0.603700E+09 | 0.548763E+09 | 3146.98 | 01-MAR-11:40 | 2860.60 | 2860.60 | 6.72 | 28.12 |
April | 0.159650E+10 | 0.145122E+10 | 3146.98 | 01-APR-06:15 | 2860.60 | 2860.60 | 6.76 | 28.12 |
May | 0.237291E+10 | 0.215697E+10 | 3146.98 | 01-MAY-12:05 | 2860.60 | 2860.60 | 6.76 | 28.12 |
June | 0.453248E+10 | 0.412002E+10 | 3146.98 | 01-JUN-08:00 | 2860.60 | 2860.60 | 6.85 | 28.12 |
July | 0.498661E+10 | 0.453283E+10 | 3146.98 | 01-JUL-09:05 | 2860.60 | 2860.60 | 7.21 | 28.12 |
August | 0.409593E+10 | 0.372320E+10 | 3146.98 | 01-AUG-00:05 | 2860.60 | 2860.60 | 6.77 | 28.12 |
September | 0.156640E+10 | 0.142385E+10 | 3146.98 | 01-SEP-07:15 | 2860.60 | 2860.60 | 7.19 | 28.12 |
October | 0.721046E+09 | 0.655431E+09 | 3146.98 | 02-OCT-07:10 | 2860.60 | 2860.60 | 6.76 | 28.12 |
November | 0.473091E+09 | 0.430040E+09 | 3146.98 | 01-NOV-06:15 | 2860.60 | 2860.60 | 6.75 | 28.12 |
December | 0.387157E+09 | 0.351926E+09 | 3146.98 | 01-DEC-07:50 | 2860.60 | 2860.60 | 6.74 | 28.12 |
Annual Sum or Average | 0.220222E+11 | 0.200182E+11 | ||||||
Minimum of Months | 0.341977E+09 | 0.310857E+09 | 3146.98 | 2860.60 | 2860.60 | 6.71 | 28.12 | |
Maximum of Months | 0.498661E+10 | 0.453283E+10 | 3146.98 | 2860.60 | 2860.60 | 7.21 | 28.12 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 9440926.05 | 8581801.78 | 3146.98 | 31-MAY-15:10 | 2860.60 | 2860.60 | 15.79 | 14.06 |
June | 0.395575E+09 | 0.359577E+09 | 3146.98 | 12-JUN-14:30 | 2860.60 | 2860.60 | 15.82 | 14.06 |
July | 0.658977E+09 | 0.599010E+09 | 3146.98 | 03-JUL-14:50 | 2860.60 | 2860.60 | 16.15 | 14.06 |
August | 0.283228E+09 | 0.257454E+09 | 3146.98 | 02-AUG-12:50 | 2860.60 | 2860.60 | 14.95 | 14.06 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 7.89 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.75 | 0.00 |
Annual Sum or Average | 0.134722E+10 | 0.122462E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.658977E+09 | 0.599010E+09 | 3146.98 | 2860.60 | 2860.60 | 16.15 | 14.06 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-JAN-00:02 | 3512.87 | 3512.87 | 18.47 | 16.30 |
February | 0.934910E+10 | 0.849834E+10 | 3864.54 | 01-FEB-00:03 | 3512.87 | 3512.87 | 18.77 | 16.30 |
March | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-MAR-00:10 | 3512.87 | 3512.87 | 19.45 | 16.30 |
April | 0.100169E+11 | 0.910536E+10 | 3864.54 | 01-APR-00:10 | 3512.87 | 3512.87 | 20.24 | 16.30 |
May | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-MAY-00:05 | 3512.87 | 3512.87 | 19.01 | 16.30 |
June | 0.100169E+11 | 0.910536E+10 | 3864.54 | 01-JUN-00:10 | 3512.87 | 3512.87 | 19.48 | 16.30 |
July | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-JUL-00:10 | 3512.87 | 3512.87 | 19.88 | 16.30 |
August | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-AUG-00:05 | 3512.87 | 3512.87 | 22.93 | 16.30 |
September | 0.100169E+11 | 0.910536E+10 | 3864.54 | 01-SEP-00:10 | 3512.87 | 3512.87 | 18.95 | 16.30 |
October | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-OCT-00:10 | 3512.87 | 3512.87 | 19.27 | 16.30 |
November | 0.100169E+11 | 0.910536E+10 | 3864.54 | 01-NOV-00:10 | 3512.87 | 3512.87 | 19.59 | 16.30 |
December | 0.103508E+11 | 0.940887E+10 | 3864.54 | 01-DEC-00:10 | 3512.87 | 3512.87 | 19.97 | 16.30 |
Annual Sum or Average | 0.121872E+12 | 0.110782E+12 | ||||||
Minimum of Months | 0.934910E+10 | 0.849834E+10 | 3864.54 | 3512.87 | 3512.87 | 18.47 | 16.30 | |
Maximum of Months | 0.103508E+11 | 0.940887E+10 | 3864.54 | 3512.87 | 3512.87 | 22.93 | 16.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:02 | 16.86 | 16.86 | 56.64 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.58 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.30 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 56.54 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.52 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.39 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.67 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.65 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.70 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.38 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 56.80 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.62 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.30 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.80 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.134915E+10 | 0.122637E+10 | 12349.37 | 18-JAN-15:00 | 11225.58 | 11225.58 | 21.14 | 50.56 |
February | 0.134174E+10 | 0.121965E+10 | 12349.37 | 17-FEB-20:40 | 11225.58 | 11225.58 | 21.14 | 50.56 |
March | 0.236559E+10 | 0.215032E+10 | 12352.65 | 22-MAR-14:30 | 11228.56 | 11228.56 | 21.51 | 50.56 |
April | 0.626581E+10 | 0.569563E+10 | 12375.61 | 21-APR-12:10 | 11249.43 | 11249.43 | 24.09 | 50.56 |
May | 0.934616E+10 | 0.849566E+10 | 24755.22 | 31-MAY-15:20 | 22502.50 | 22502.50 | 24.31 | 101.13 |
June | 0.191338E+11 | 0.173926E+11 | 24795.69 | 30-JUN-12:10 | 22539.28 | 22539.28 | 26.35 | 101.13 |
July | 0.219663E+11 | 0.199674E+11 | 24794.92 | 03-JUL-15:00 | 22538.58 | 22538.58 | 26.32 | 101.13 |
August | 0.170181E+11 | 0.154695E+11 | 24787.41 | 11-AUG-14:30 | 22531.75 | 22531.75 | 25.96 | 101.13 |
September | 0.614838E+10 | 0.558887E+10 | 12376.89 | 18-SEP-16:00 | 11250.59 | 11250.59 | 24.23 | 50.56 |
October | 0.282951E+10 | 0.257202E+10 | 12367.43 | 03-OCT-14:40 | 11241.99 | 11241.99 | 23.17 | 50.56 |
November | 0.185617E+10 | 0.168725E+10 | 12349.37 | 13-NOV-16:30 | 11225.58 | 11225.58 | 21.14 | 50.56 |
December | 0.151634E+10 | 0.137835E+10 | 12349.31 | 08-DEC-15:00 | 11225.52 | 11225.52 | 21.13 | 50.56 |
Annual Sum or Average | 0.911371E+11 | 0.828436E+11 | ||||||
Minimum of Months | 0.134174E+10 | 0.121965E+10 | 12349.31 | 11225.52 | 11225.52 | 21.13 | 50.56 | |
Maximum of Months | 0.219663E+11 | 0.199674E+11 | 24795.69 | 22539.28 | 22539.28 | 26.35 | 101.13 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 43.74 | 43.74 | 309241.16 | 2175238.94 | 12-JAN-07:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 39.05 | 39.05 | 189009.09 | 2215408.74 | 27-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 48.08 | 48.08 | 72312.38 | 1675688.85 | 01-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.22 | 25.22 | 10660.49 | 1530214.84 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27.40 | 27.40 | 730.53 | 452752.35 | 26-MAY-13:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 27.48 | 27.48 | 36.56 | 149093.98 | 15-JUN-09:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.84 | 26.84 | 29.58 | 246142.97 | 05-JUL-13:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.22 | 27.22 | 368.77 | 288355.39 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.77 | 27.77 | 3361.72 | 671254.81 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.44 | 24.44 | 39092.44 | 1633055.50 | 30-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.68 | 32.68 | 244918.97 | 1907416.11 | 27-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 46.50 | 46.50 | 352032.10 | 1880191.45 | 15-DEC-07:02 |
Annual Sum or Average | 0.00 | 101505.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.44 | 24.44 | 29.58 | 149093.98 | ||
Maximum of Months | 0.00 | 0.00 | 48.08 | 48.08 | 352032.10 | 2215408.74 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 126.36 | 5435.75 | 23-JAN-15:20 | 6.75 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 195.93 | 14169.42 | 16-FEB-13:30 | 6.82 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1000.47 | 112032.67 | 22-MAR-14:50 | 7.65 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 24160.53 | 563657.83 | 21-APR-12:10 | 11.49 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 45899.38 | 1134987.18 | 31-MAY-15:20 | 11.52 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 196363.10 | 1504399.38 | 20-JUN-13:05 | 13.09 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 246611.99 | 1583011.87 | 19-JUL-14:05 | 13.42 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 144539.15 | 1487938.18 | 11-AUG-15:20 | 13.02 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 19595.09 | 580049.13 | 18-SEP-16:00 | 11.62 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4077.40 | 383534.42 | 03-OCT-14:40 | 9.95 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 281.21 | 17574.35 | 07-NOV-08:25 | 6.85 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 190.18 | 13773.10 | 18-DEC-16:00 | 6.82 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 57351.44 | 0.00 | ||||||
Minimum of Months | 126.36 | 5435.75 | 6.75 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 246611.99 | 1583011.87 | 13.42 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.62 | 3168.35 | 24-JAN-11:20 | 11.34 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 67.43 | 13199.01 | 16-FEB-13:30 | 15.89 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 795.73 | 110411.39 | 22-MAR-14:40 | 16.26 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23618.64 | 579691.18 | 21-APR-12:05 | 19.93 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 45096.96 | 1014430.00 | 31-MAY-15:50 | 21.07 | 7.33 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 194406.24 | 1476807.98 | 30-JUN-12:05 | 18.57 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 246211.22 | 1548049.13 | 21-JUL-13:05 | 18.00 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 143921.14 | 1505151.21 | 11-AUG-15:20 | 16.73 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 19052.98 | 578681.22 | 18-SEP-16:00 | 20.73 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 3834.73 | 381881.83 | 03-OCT-14:40 | 19.35 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 115.47 | 21330.69 | 07-NOV-08:25 | 17.47 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 58.62 | 19780.83 | 18-DEC-15:07 | 16.84 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 56864.27 | 0.00 | ||||||
Minimum of Months | 9.62 | 3168.35 | 11.34 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 246211.22 | 1548049.13 | 21.07 | 7.33 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8599.74 | 37996.15 | 04-JAN-12:02 | 19.00 | 18.33 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 37762.59 | 128727.76 | 02-FEB-13:03 | 20.61 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 74748.10 | 150400.35 | 11-MAR-13:05 | 20.99 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 114319.95 | 296144.52 | 27-APR-21:03 | 23.55 | 18.33 | 0.00 | 0.00 | 01-APR-00:10 |
May | 41578.93 | 279013.29 | 31-MAY-16:00 | 23.25 | 22.47 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 151160.81 | 1084024.86 | 30-JUN-15:00 | 37.19 | 30.63 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 314791.56 | 1390173.97 | 29-JUL-17:00 | 42.40 | 33.27 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 311860.43 | 1250550.87 | 11-AUG-17:00 | 40.03 | 29.40 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 29716.04 | 81944.69 | 08-SEP-10:05 | 19.78 | 18.33 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 48669.24 | 131370.18 | 04-OCT-09:05 | 20.65 | 18.33 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 64866.81 | 172389.60 | 18-NOV-12:03 | 21.38 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88923.89 | 270306.54 | 18-DEC-10:02 | 23.10 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 108009.83 | 0.00 | ||||||
Minimum of Months | 8599.74 | 37996.15 | 19.00 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 314791.56 | 1390173.97 | 42.40 | 33.27 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.66 | 57.66 | 17739.75 | 62780.50 | 17-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.06 | 57.06 | 17847.57 | 62780.22 | 01-FEB-12:43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.06 | 57.06 | 18970.66 | 62780.03 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.06 | 57.06 | 17768.26 | 62780.03 | 07-APR-11:35 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.66 | 57.66 | 18229.21 | 62779.72 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.13 | 57.13 | 18000.47 | 61218.35 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.24 | 57.24 | 15940.88 | 58671.81 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.34 | 57.34 | 17042.25 | 56912.75 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.38 | 57.38 | 15913.22 | 56528.81 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.36 | 57.36 | 16196.61 | 58205.21 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.28 | 57.28 | 17004.75 | 60510.58 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.17 | 57.17 | 17043.40 | 62780.01 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 17305.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.06 | 57.06 | 15913.22 | 56528.81 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 18970.66 | 62780.50 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12.85 | 8113.38 | 18-JAN-15:00 | 21.14 | 20.21 | 1902.60 | 127832.69 | 21-JAN-11:07 |
February | 11.96 | 8114.04 | 17-FEB-20:40 | 21.14 | 20.21 | 2050.36 | 124382.71 | 02-FEB-13:40 |
March | 127.30 | 86038.46 | 22-MAR-14:30 | 21.51 | 20.66 | 2790.80 | 129423.94 | 10-MAR-07:15 |
April | 22158.36 | 631738.38 | 21-APR-12:10 | 24.09 | 21.10 | 3348.98 | 120560.55 | 04-APR-14:40 |
May | 46311.57 | 1354939.89 | 31-MAY-15:20 | 24.31 | 22.68 | 1935.77 | 111977.89 | 03-MAY-06:40 |
June | 232006.01 | 2220961.20 | 30-JUN-12:10 | 26.35 | 22.53 | 1340.95 | 74410.91 | 13-JUN-05:20 |
July | 306070.54 | 2205288.46 | 03-JUL-15:00 | 26.32 | 22.56 | 1019.32 | 58050.17 | 11-JUL-22:50 |
August | 170099.47 | 2052478.93 | 11-AUG-14:30 | 25.96 | 21.10 | 1757.59 | 100018.24 | 30-AUG-07:00 |
September | 18004.03 | 662069.72 | 18-SEP-16:00 | 24.23 | 21.10 | 2533.23 | 123275.00 | 29-SEP-13:10 |
October | 3141.22 | 437545.91 | 03-OCT-14:40 | 23.17 | 21.10 | 2685.66 | 123027.24 | 26-OCT-12:50 |
November | 10.13 | 8037.02 | 13-NOV-16:30 | 21.14 | 20.21 | 2652.27 | 138472.28 | 17-NOV-15:03 |
December | 7.78 | 6528.79 | 08-DEC-15:00 | 21.13 | 20.20 | 2007.99 | 131083.43 | 30-DEC-15:03 |
Annual Sum or Average | 67026.25 | 2166.48 | ||||||
Minimum of Months | 7.78 | 6528.79 | 21.13 | 20.20 | 1019.32 | 58050.17 | ||
Maximum of Months | 306070.54 | 2220961.20 | 26.35 | 22.68 | 3348.98 | 138472.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.334107E+11 | 0.00 | 2880324.63 | 0.244511E+10 | 0.00 | 0.00 |
February | 0.177407E+11 | 0.00 | 19796508.85 | 0.264442E+10 | 0.00 | 0.00 |
March | 0.567299E+10 | 0.00 | 0.514415E+09 | 0.496201E+10 | 0.00 | 0.00 |
April | 0.583653E+09 | 0.00 | 0.196701E+10 | 0.955535E+10 | 0.00 | 0.00 |
May | 29919150.66 | 0.00 | 0.160568E+11 | 0.180505E+11 | 0.00 | 0.00 |
June | 2363.92 | 0.00 | 0.644174E+11 | 0.221068E+11 | 0.00 | 0.00 |
July | 3135.93 | 0.00 | 0.844005E+11 | 0.217095E+11 | 0.00 | 0.00 |
August | 15346908.28 | 0.00 | 0.515766E+11 | 0.223951E+11 | 0.00 | 0.00 |
September | 0.165351E+09 | 0.00 | 0.269883E+10 | 0.123338E+11 | 0.00 | 0.00 |
October | 0.124103E+10 | 0.00 | 0.129479E+10 | 0.473572E+10 | 0.00 | 0.00 |
November | 0.263475E+11 | 0.00 | 14688228.62 | 0.285626E+10 | 0.00 | 0.00 |
December | 0.431002E+11 | 0.00 | 6597022.99 | 0.280248E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.128308E+12 | 0.00 | 0.222970E+12 | 0.126597E+12 | 0.00 | 0.00 |
Minimum of Months | 2363.92 | 0.00 | 2880324.63 | 0.244511E+10 | 0.00 | 0.00 |
Maximum of Months | 0.431002E+11 | 0.00 | 0.844005E+11 | 0.223951E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.662292E+12 | 0.00 | 2403088.68 | 0.307621E+11 | 0.00 | 0.00 |
February | 0.353734E+12 | 0.00 | 23373261.01 | 0.246715E+11 | 0.00 | 0.00 |
March | 0.142675E+12 | 0.00 | 0.135499E+10 | 0.307151E+11 | 0.00 | 0.00 |
April | 0.180415E+11 | 0.00 | 0.568710E+11 | 0.503959E+11 | 0.00 | 0.00 |
May | 0.171813E+10 | 0.00 | 0.957058E+11 | 0.828724E+11 | 0.00 | 0.00 |
June | 90453183.78 | 0.00 | 0.391172E+12 | 0.105330E+12 | 0.00 | 0.00 |
July | 71120035.29 | 0.00 | 0.500169E+12 | 0.983884E+11 | 0.00 | 0.00 |
August | 0.819380E+09 | 0.00 | 0.297696E+12 | 0.856521E+11 | 0.00 | 0.00 |
September | 0.552773E+10 | 0.00 | 0.445951E+11 | 0.419870E+11 | 0.00 | 0.00 |
October | 0.722253E+11 | 0.00 | 0.869322E+10 | 0.261486E+11 | 0.00 | 0.00 |
November | 0.494400E+12 | 0.00 | 3156778.28 | 0.252960E+11 | 0.00 | 0.00 |
December | 0.749810E+12 | 0.00 | 380445.70 | 0.284713E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.250141E+13 | 0.00 | 0.139629E+13 | 0.630690E+12 | 0.00 | 0.00 |
Minimum of Months | 71120035.29 | 0.00 | 380445.70 | 0.246715E+11 | 0.00 | 0.00 |
Maximum of Months | 0.749810E+12 | 0.00 | 0.500169E+12 | 0.105330E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.122200E+12 | 0.00 | 0.00 | 0.393295E+10 | 0.00 | 0.00 |
February | 0.784048E+11 | 0.00 | 227935.96 | 0.329372E+10 | 0.00 | 0.00 |
March | 0.424341E+11 | 0.00 | 14509425.32 | 0.338702E+10 | 0.00 | 0.00 |
April | 0.889488E+10 | 0.00 | 0.229881E+10 | 0.379929E+10 | 0.00 | 0.00 |
May | 0.218262E+09 | 0.00 | 0.912880E+10 | 0.652103E+10 | 0.00 | 0.00 |
June | 9295596.70 | 0.00 | 0.403024E+11 | 0.963711E+10 | 0.00 | 0.00 |
July | 5864924.06 | 0.00 | 0.516559E+11 | 0.900278E+10 | 0.00 | 0.00 |
August | 0.154234E+09 | 0.00 | 0.284005E+11 | 0.709566E+10 | 0.00 | 0.00 |
September | 0.308957E+10 | 0.00 | 0.219633E+10 | 0.294366E+10 | 0.00 | 0.00 |
October | 0.306439E+11 | 0.00 | 0.123207E+09 | 0.283662E+10 | 0.00 | 0.00 |
November | 0.103631E+12 | 0.00 | 0.00 | 0.362747E+10 | 0.00 | 0.00 |
December | 0.134883E+12 | 0.00 | 2084.26 | 0.403936E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.524569E+12 | 0.00 | 0.134121E+12 | 0.601167E+11 | 0.00 | 0.00 |
Minimum of Months | 5864924.06 | 0.00 | 0.00 | 0.283662E+10 | 0.00 | 0.00 |
Maximum of Months | 0.134883E+12 | 0.00 | 0.516559E+11 | 0.963711E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.147610E+11 | 0.00 | 95023544.09 | 0.559003E+10 | 0.00 | 0.00 |
February | 0.971639E+10 | 0.00 | 0.176569E+09 | 0.789577E+10 | 0.00 | 0.00 |
March | 0.407493E+10 | 0.00 | 0.250971E+09 | 0.122324E+11 | 0.00 | 0.00 |
April | 0.239400E+09 | 0.00 | 0.286377E+09 | 0.106760E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 223.74 | 0.00 | 990763.83 | 0.164064E+10 | 0.00 | 0.00 |
October | 0.107815E+10 | 0.00 | 0.203951E+09 | 0.992924E+10 | 0.00 | 0.00 |
November | 0.136974E+11 | 0.00 | 0.279328E+09 | 0.831310E+10 | 0.00 | 0.00 |
December | 0.201034E+11 | 0.00 | 0.157178E+09 | 0.688198E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.636708E+11 | 0.00 | 0.145039E+10 | 0.631592E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201034E+11 | 0.00 | 0.286377E+09 | 0.122324E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.105427E+11 | 0.235722E+12 | 0.00 | 45.16 |
February | 0.00 | 0.00 | 0.159684E+11 | 0.297647E+12 | 0.00 | 71.80 |
March | 0.00 | 0.00 | 0.212878E+11 | 0.384499E+12 | 0.00 | 99.58 |
April | 0.00 | 0.00 | 0.232978E+11 | 0.373054E+12 | 0.00 | 96.40 |
May | 0.00 | 0.00 | 0.145772E+11 | 0.303420E+12 | 0.00 | 70.03 |
June | 0.00 | 0.00 | 0.680029E+11 | 0.234268E+12 | 0.00 | 41.00 |
July | 0.00 | 0.00 | 0.269358E+12 | 0.200306E+12 | 0.00 | 11.02 |
August | 0.00 | 0.00 | 0.327294E+12 | 0.254899E+12 | 0.00 | 27.85 |
September | 0.00 | 0.00 | 0.902742E+10 | 0.208878E+12 | 0.00 | 36.63 |
October | 0.00 | 0.00 | 0.181673E+11 | 0.338305E+12 | 0.00 | 82.72 |
November | 0.00 | 0.00 | 0.211242E+11 | 0.372025E+12 | 0.00 | 96.32 |
December | 0.00 | 0.00 | 0.218297E+11 | 0.384958E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.820478E+12 | 0.358798E+13 | 0.00 | 778.14 |
Minimum of Months | 0.00 | 0.00 | 0.902742E+10 | 0.200306E+12 | 0.00 | 11.02 |
Maximum of Months | 0.00 | 0.00 | 0.327294E+12 | 0.384958E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.227867E+10 | 0.201853E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.896368E+10 | 0.314372E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.174472E+11 | 0.479937E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241272E+11 | 0.577576E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.737216E+10 | 0.294028E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134893E+11 | 0.396883E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203242E+11 | 0.524626E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259312E+11 | 0.605663E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.658887E+10 | 0.272843E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.116224E+11 | 0.372645E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.158055E+11 | 0.449087E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.222295E+11 | 0.565733E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.176180E+12 | 0.505525E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.227867E+10 | 0.201853E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259312E+11 | 0.605663E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.808320E+09 | 0.148420E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.548927E+11 | 0.243831E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140667E+12 | 0.415252E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.219075E+12 | 0.535028E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.621148E+11 | 0.267198E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124009E+12 | 0.372287E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.188890E+12 | 0.494063E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241556E+12 | 0.570752E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.490771E+11 | 0.236847E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.856076E+11 | 0.311929E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.113426E+12 | 0.364038E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.169938E+12 | 0.470509E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145006E+13 | 0.443015E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.808320E+09 | 0.148420E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241556E+12 | 0.570752E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147494E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.301287E+10 | 0.195947E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.112343E+11 | 0.365865E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.201379E+11 | 0.507653E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.556031E+10 | 0.256472E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.122417E+11 | 0.371107E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.187630E+11 | 0.493818E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.238052E+11 | 0.567184E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.326425E+10 | 0.207398E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.548027E+10 | 0.256113E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.852501E+10 | 0.313405E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.144275E+11 | 0.427113E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126452E+12 | 0.410957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147494E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.238052E+11 | 0.567184E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.244511E+10 | 2880324.63 | 0.334107E+11 | 0.576511E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264442E+10 | 19796508.85 | 0.177407E+11 | 0.475932E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496201E+10 | 0.514415E+09 | 0.567299E+10 | 0.444698E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.955535E+10 | 0.196701E+10 | 0.583653E+09 | 0.989133E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180505E+11 | 0.160568E+11 | 29919150.66 | 87115432.48 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.221068E+11 | 0.644174E+11 | 2363.92 | 0.139941E+09 | 4921808.43 | 0.00 | 0.00 | 0.00 |
July | 0.217095E+11 | 0.844005E+11 | 3135.93 | 0.323047E+09 | 0.115230E+09 | 0.00 | 0.00 | 0.00 |
August | 0.223951E+11 | 0.515766E+11 | 15346908.28 | 31710399.33 | 82598.42 | 0.00 | 0.00 | 0.00 |
September | 0.123338E+11 | 0.269883E+10 | 0.165351E+09 | 0.217286E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.473572E+10 | 0.129479E+10 | 0.124103E+10 | 0.302350E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285626E+10 | 14688228.62 | 0.263475E+11 | 0.576956E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280248E+10 | 6597022.99 | 0.431002E+11 | 0.521958E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126597E+12 | 0.222970E+12 | 0.128308E+12 | 0.302486E+12 | 0.120234E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244511E+10 | 2880324.63 | 2363.92 | 31710399.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223951E+11 | 0.844005E+11 | 0.431002E+11 | 0.576956E+11 | 0.115230E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307621E+11 | 2403088.68 | 0.662292E+12 | 0.536057E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246715E+11 | 23373261.01 | 0.353734E+12 | 0.469506E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307151E+11 | 0.135499E+10 | 0.142675E+12 | 0.554362E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.503959E+11 | 0.568710E+11 | 0.180415E+11 | 0.161188E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.828724E+11 | 0.957058E+11 | 0.171813E+10 | 0.122965E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105330E+12 | 0.391172E+12 | 90453183.78 | 0.232480E+10 | 13919609.35 | 0.00 | 0.00 | 0.00 |
July | 0.983884E+11 | 0.500169E+12 | 71120035.29 | 0.403953E+10 | 0.135527E+10 | 0.00 | 0.00 | 0.00 |
August | 0.856521E+11 | 0.297696E+12 | 0.819380E+09 | 0.463490E+10 | 2066444.15 | 0.00 | 0.00 | 0.00 |
September | 0.419870E+11 | 0.445951E+11 | 0.552773E+10 | 0.842698E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261486E+11 | 0.869322E+10 | 0.722253E+11 | 0.372398E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252960E+11 | 3156778.28 | 0.494400E+12 | 0.528664E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284713E+11 | 380445.70 | 0.749810E+12 | 0.462815E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630690E+12 | 0.139629E+13 | 0.250141E+13 | 0.319256E+13 | 0.137125E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246715E+11 | 380445.70 | 71120035.29 | 0.232480E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105330E+12 | 0.500169E+12 | 0.749810E+12 | 0.554362E+12 | 0.135527E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.393295E+10 | 0.00 | 0.122200E+12 | 0.531872E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329372E+10 | 227935.96 | 0.784048E+11 | 0.465753E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338702E+10 | 14509425.32 | 0.424341E+11 | 0.571139E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379929E+10 | 0.229881E+10 | 0.889488E+10 | 0.198041E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.652103E+10 | 0.912880E+10 | 0.218262E+09 | 0.190726E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963711E+10 | 0.403024E+11 | 9295596.70 | 0.158729E+09 | 1011947.97 | 0.00 | 0.00 | 0.00 |
July | 0.900278E+10 | 0.516559E+11 | 5864924.06 | 0.290507E+09 | 0.106523E+09 | 0.00 | 0.00 | 0.00 |
August | 0.709566E+10 | 0.284005E+11 | 0.154234E+09 | 0.105772E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294366E+10 | 0.219633E+10 | 0.308957E+10 | 0.123429E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283662E+10 | 0.123207E+09 | 0.306439E+11 | 0.399769E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362747E+10 | 0.00 | 0.103631E+12 | 0.514659E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403936E+10 | 2084.26 | 0.134883E+12 | 0.465237E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601167E+11 | 0.134121E+12 | 0.524569E+12 | 0.330404E+12 | 0.107535E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283662E+10 | 0.00 | 5864924.06 | 0.158729E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.963711E+10 | 0.516559E+11 | 0.134883E+12 | 0.571139E+11 | 0.106523E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.559003E+10 | 95023544.09 | 0.147610E+11 | 0.264431E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.789577E+10 | 0.176569E+09 | 0.971639E+10 | 0.169217E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122324E+11 | 0.250971E+09 | 0.407493E+10 | 0.117493E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106760E+11 | 0.286377E+09 | 0.239400E+09 | 0.136701E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164064E+10 | 990763.83 | 223.74 | 54560401.10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992924E+10 | 0.203951E+09 | 0.107815E+10 | 0.440082E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.831310E+10 | 0.279328E+09 | 0.136974E+11 | 0.157706E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688198E+10 | 0.157178E+09 | 0.201034E+11 | 0.189147E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.631592E+11 | 0.145039E+10 | 0.636708E+11 | 0.956218E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122324E+11 | 0.286377E+09 | 0.201034E+11 | 0.264431E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110070E+12 | 0.628578E+10 | 0.00 | 0.00 | 0.00 | 0.120851E+12 | 0.00 | 0.00 |
February | 0.994181E+11 | 0.107547E+11 | 0.00 | 0.00 | 0.00 | 0.192150E+12 | 0.00 | 0.00 |
March | 0.110070E+12 | 0.145508E+11 | 0.00 | 0.00 | 0.00 | 0.266493E+12 | 0.00 | 0.00 |
April | 0.106519E+12 | 0.159083E+11 | 0.00 | 0.00 | 0.00 | 0.257984E+12 | 0.00 | 0.00 |
May | 0.110070E+12 | 0.947786E+10 | 0.00 | 0.00 | 0.00 | 0.187407E+12 | 0.00 | 0.00 |
June | 0.106519E+12 | 0.504746E+11 | 0.00 | 0.00 | 0.00 | 0.109727E+12 | 0.00 | 0.00 |
July | 0.110070E+12 | 0.208737E+12 | 0.00 | 0.00 | 0.00 | 0.294825E+11 | 0.00 | 0.00 |
August | 0.110070E+12 | 0.257326E+12 | 0.00 | 0.00 | 0.00 | 0.745256E+11 | 0.00 | 0.00 |
September | 0.106519E+12 | 0.514245E+10 | 0.00 | 0.00 | 0.00 | 0.980324E+11 | 0.00 | 0.00 |
October | 0.110070E+12 | 0.122857E+11 | 0.00 | 0.00 | 0.00 | 0.221357E+12 | 0.00 | 0.00 |
November | 0.106519E+12 | 0.145349E+11 | 0.00 | 0.00 | 0.00 | 0.257757E+12 | 0.00 | 0.00 |
December | 0.110070E+12 | 0.147821E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.129599E+13 | 0.620261E+12 | 0.00 | 0.00 | 0.00 | 0.208241E+13 | 0.00 | 0.00 |
Minimum of Months | 0.994181E+11 | 0.514245E+10 | 0.00 | 0.00 | 0.00 | 0.294825E+11 | 0.00 | 0.00 |
Maximum of Months | 0.110070E+12 | 0.257326E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151794E+10 | 0.177807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137104E+10 | 0.719100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151794E+10 | 0.141657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146897E+10 | 0.198204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151794E+10 | 0.594982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146897E+10 | 0.109895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151794E+10 | 0.165958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151794E+10 | 0.213925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146897E+10 | 0.532941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151794E+10 | 0.941389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146897E+10 | 0.127836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151794E+10 | 0.180901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178725E+11 | 0.143500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137104E+10 | 0.177807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151794E+10 | 0.213925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146183E+11 | 0.584588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132036E+11 | 0.437132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146183E+11 | 0.113760E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141467E+11 | 0.179719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146183E+11 | 0.500133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141467E+11 | 0.100927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146183E+11 | 0.154102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146183E+11 | 0.199099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141467E+11 | 0.395391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146183E+11 | 0.690329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141467E+11 | 0.911688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146183E+11 | 0.137505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172118E+12 | 0.117916E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132036E+11 | 0.584588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146183E+11 | 0.199099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133220E+10 | 0.238560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147494E+10 | 0.905063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142736E+10 | 0.164887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147494E+10 | 0.447053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142736E+10 | 0.995794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147494E+10 | 0.152998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147494E+10 | 0.196083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142736E+10 | 0.261764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147494E+10 | 0.439408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142736E+10 | 0.681833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147494E+10 | 0.116313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173662E+11 | 0.102723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147494E+10 | 0.196083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.244511E+10 | 0.334107E+11 | 2880324.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264442E+10 | 0.177407E+11 | 19796508.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496201E+10 | 0.567299E+10 | 0.514415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.955535E+10 | 0.583653E+09 | 0.196701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180505E+11 | 29919150.66 | 0.160568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.221068E+11 | 2363.92 | 0.644174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.217095E+11 | 3135.93 | 0.844005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223951E+11 | 15346908.28 | 0.515766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123338E+11 | 0.165351E+09 | 0.269883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.473572E+10 | 0.124103E+10 | 0.129479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285626E+10 | 0.263475E+11 | 14688228.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280248E+10 | 0.431002E+11 | 6597022.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126597E+12 | 0.128308E+12 | 0.222970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244511E+10 | 2363.92 | 2880324.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.223951E+11 | 0.431002E+11 | 0.844005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.307621E+11 | 0.662292E+12 | 2403088.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246715E+11 | 0.353734E+12 | 23373261.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307151E+11 | 0.142675E+12 | 0.135499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.503959E+11 | 0.180415E+11 | 0.568710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.828724E+11 | 0.171813E+10 | 0.957058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105330E+12 | 90453183.78 | 0.391172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.983884E+11 | 71120035.29 | 0.500169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.856521E+11 | 0.819380E+09 | 0.297696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.419870E+11 | 0.552773E+10 | 0.445951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261486E+11 | 0.722253E+11 | 0.869322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252960E+11 | 0.494400E+12 | 3156778.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284713E+11 | 0.749810E+12 | 380445.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630690E+12 | 0.250141E+13 | 0.139629E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246715E+11 | 71120035.29 | 380445.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105330E+12 | 0.749810E+12 | 0.500169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.393295E+10 | 0.122200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329372E+10 | 0.784048E+11 | 227935.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338702E+10 | 0.424341E+11 | 14509425.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379929E+10 | 0.889488E+10 | 0.229881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.652103E+10 | 0.218262E+09 | 0.912880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963711E+10 | 9295596.70 | 0.403024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.900278E+10 | 5864924.06 | 0.516559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.709566E+10 | 0.154234E+09 | 0.284005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.294366E+10 | 0.308957E+10 | 0.219633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283662E+10 | 0.306439E+11 | 0.123207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362747E+10 | 0.103631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403936E+10 | 0.134883E+12 | 2084.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601167E+11 | 0.524569E+12 | 0.134121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283662E+10 | 5864924.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.963711E+10 | 0.134883E+12 | 0.516559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.559003E+10 | 0.147610E+11 | 95023544.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.789577E+10 | 0.971639E+10 | 0.176569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122324E+11 | 0.407493E+10 | 0.250971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106760E+11 | 0.239400E+09 | 0.286377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164064E+10 | 223.74 | 990763.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992924E+10 | 0.107815E+10 | 0.203951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.831310E+10 | 0.136974E+11 | 0.279328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688198E+10 | 0.201034E+11 | 0.157178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.631592E+11 | 0.636708E+11 | 0.145039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122324E+11 | 0.201034E+11 | 0.286377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.110070E+12 | 0.00 | 0.105427E+11 | 0.00 | 0.425695E+10 | 0.00 | 0.00 | 0.00 | 0.121395E+12 | 0.00 | 0.00 | 0.00 |
February | 0.994181E+11 | 0.00 | 0.159684E+11 | 0.00 | 0.521378E+10 | 0.00 | 0.00 | 0.00 | 0.193015E+12 | 0.00 | 0.00 | 0.00 |
March | 0.110070E+12 | 0.00 | 0.212878E+11 | 0.00 | 0.673696E+10 | 0.00 | 0.00 | 0.00 | 0.267692E+12 | 0.00 | 0.00 | 0.00 |
April | 0.106519E+12 | 0.00 | 0.232978E+11 | 0.00 | 0.738948E+10 | 0.00 | 0.00 | 0.00 | 0.259145E+12 | 0.00 | 0.00 | 0.00 |
May | 0.110070E+12 | 0.00 | 0.145772E+11 | 0.00 | 0.509932E+10 | 0.00 | 0.00 | 0.00 | 0.188251E+12 | 0.00 | 0.00 | 0.00 |
June | 0.106519E+12 | 0.00 | 0.680029E+11 | 0.00 | 0.175283E+11 | 0.00 | 0.00 | 0.00 | 0.110221E+12 | 0.00 | 0.00 | 0.00 |
July | 0.110070E+12 | 0.00 | 0.269358E+12 | 0.00 | 0.606206E+11 | 0.00 | 0.00 | 0.00 | 0.296153E+11 | 0.00 | 0.00 | 0.00 |
August | 0.110070E+12 | 0.00 | 0.327294E+12 | 0.00 | 0.699681E+11 | 0.00 | 0.00 | 0.00 | 0.748611E+11 | 0.00 | 0.00 | 0.00 |
September | 0.106519E+12 | 0.00 | 0.902742E+10 | 0.00 | 0.388497E+10 | 0.00 | 0.00 | 0.00 | 0.984737E+11 | 0.00 | 0.00 | 0.00 |
October | 0.110070E+12 | 0.00 | 0.181673E+11 | 0.00 | 0.588162E+10 | 0.00 | 0.00 | 0.00 | 0.222354E+12 | 0.00 | 0.00 | 0.00 |
November | 0.106519E+12 | 0.00 | 0.211242E+11 | 0.00 | 0.658927E+10 | 0.00 | 0.00 | 0.00 | 0.258917E+12 | 0.00 | 0.00 | 0.00 |
December | 0.110070E+12 | 0.00 | 0.218297E+11 | 0.00 | 0.704759E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129599E+13 | 0.00 | 0.820478E+12 | 0.00 | 0.200217E+12 | 0.00 | 0.00 | 0.00 | 0.209178E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.994181E+11 | 0.00 | 0.902742E+10 | 0.00 | 0.388497E+10 | 0.00 | 0.00 | 0.00 | 0.296153E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110070E+12 | 0.00 | 0.327294E+12 | 0.00 | 0.699681E+11 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151794E+10 | 0.00 | 0.227867E+10 | 0.00 | 0.500595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137104E+10 | 0.00 | 0.896368E+10 | 0.00 | 0.177268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151794E+10 | 0.00 | 0.174472E+11 | 0.00 | 0.328143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146897E+10 | 0.00 | 0.241272E+11 | 0.00 | 0.430679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151794E+10 | 0.00 | 0.737216E+10 | 0.00 | 0.142234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146897E+10 | 0.00 | 0.134893E+11 | 0.00 | 0.249986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151794E+10 | 0.00 | 0.203242E+11 | 0.00 | 0.372832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151794E+10 | 0.00 | 0.259312E+11 | 0.00 | 0.453870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146897E+10 | 0.00 | 0.658887E+10 | 0.00 | 0.125946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151794E+10 | 0.00 | 0.116224E+11 | 0.00 | 0.220851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146897E+10 | 0.00 | 0.158055E+11 | 0.00 | 0.302190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151794E+10 | 0.00 | 0.222295E+11 | 0.00 | 0.413939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178725E+11 | 0.00 | 0.176180E+12 | 0.00 | 0.326800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137104E+10 | 0.00 | 0.227867E+10 | 0.00 | 0.500595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151794E+10 | 0.00 | 0.259312E+11 | 0.00 | 0.453870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146183E+11 | 0.00 | 0.808320E+09 | 0.00 | 0.223732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132036E+11 | 0.00 | 0.548927E+11 | 0.00 | 0.111795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146183E+11 | 0.00 | 0.140667E+12 | 0.00 | 0.269069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141467E+11 | 0.00 | 0.219075E+12 | 0.00 | 0.393561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146183E+11 | 0.00 | 0.621148E+11 | 0.00 | 0.121015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141467E+11 | 0.00 | 0.124009E+12 | 0.00 | 0.230820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146183E+11 | 0.00 | 0.188890E+12 | 0.00 | 0.347881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146183E+11 | 0.00 | 0.241556E+12 | 0.00 | 0.424570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141467E+11 | 0.00 | 0.490771E+11 | 0.00 | 0.953798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146183E+11 | 0.00 | 0.856076E+11 | 0.00 | 0.165747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141467E+11 | 0.00 | 0.113426E+12 | 0.00 | 0.222571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146183E+11 | 0.00 | 0.169938E+12 | 0.00 | 0.324326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172118E+12 | 0.00 | 0.145006E+13 | 0.00 | 0.270897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132036E+11 | 0.00 | 0.808320E+09 | 0.00 | 0.223732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146183E+11 | 0.00 | 0.241556E+12 | 0.00 | 0.424570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133220E+10 | 0.00 | 0.301287E+10 | 0.00 | 0.627269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147494E+10 | 0.00 | 0.112343E+11 | 0.00 | 0.218372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142736E+10 | 0.00 | 0.201379E+11 | 0.00 | 0.364917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147494E+10 | 0.00 | 0.556031E+10 | 0.00 | 0.108978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142736E+10 | 0.00 | 0.122417E+11 | 0.00 | 0.228371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147494E+10 | 0.00 | 0.187630E+11 | 0.00 | 0.346324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147494E+10 | 0.00 | 0.238052E+11 | 0.00 | 0.419690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142736E+10 | 0.00 | 0.326425E+10 | 0.00 | 0.646616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147494E+10 | 0.00 | 0.548027E+10 | 0.00 | 0.108619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142736E+10 | 0.00 | 0.852501E+10 | 0.00 | 0.170669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147494E+10 | 0.00 | 0.144275E+11 | 0.00 | 0.279619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173662E+11 | 0.00 | 0.126452E+12 | 0.00 | 0.237295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147494E+10 | 0.00 | 0.238052E+11 | 0.00 | 0.419690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 83692855.23 | 0.00 | 0.00 | 0.528715E+11 | 0.00 | 0.29 |
February | 0.00 | 0.00 | 0.00 | 78041760.33 | 0.00 | 0.00 | 0.516464E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.116286E+09 | 0.00 | 0.00 | 0.645462E+11 | 0.00 | 0.37 |
April | 0.00 | 0.00 | 0.00 | 0.110694E+09 | 0.00 | 0.00 | 0.592838E+11 | 0.00 | 0.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 30831093.52 | 0.00 | 0.00 | 0.108814E+11 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.00 | 0.117203E+09 | 0.00 | 0.00 | 0.576757E+11 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.00 | 0.117969E+09 | 0.00 | 0.00 | 0.653694E+11 | 0.00 | 0.31 |
December | 0.00 | 0.00 | 0.00 | 0.122585E+09 | 0.00 | 0.00 | 0.676054E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.777303E+09 | 0.00 | 0.00 | 0.429880E+12 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.122585E+09 | 0.00 | 0.00 | 0.676054E+11 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204745E+11 | 0.00 | 0.00 | 35677943.01 | 0.00 | 0.00 | 0.239463E+11 | 0.00 | 0.31 |
February | 0.110600E+11 | 0.00 | 0.00 | 45501089.12 | 0.00 | 0.00 | 0.311543E+11 | 0.00 | 0.35 |
March | 0.345153E+10 | 0.00 | 0.00 | 93321603.95 | 0.00 | 0.00 | 0.493945E+11 | 0.00 | 0.39 |
April | 0.583784E+10 | 0.00 | 0.00 | 0.107567E+09 | 0.00 | 0.00 | 0.588832E+11 | 0.00 | 0.58 |
May | 0.733413E+10 | 0.00 | 0.00 | 0.148207E+09 | 0.00 | 0.00 | 0.831028E+11 | 0.00 | 1.21 |
June | 0.925327E+10 | 5323680.09 | 0.00 | 0.163460E+09 | 0.00 | 0.00 | 0.662212E+11 | 0.00 | 1.51 |
July | 0.125195E+11 | 0.132277E+09 | 0.00 | 0.165854E+09 | 11997895.17 | 0.00 | 0.557254E+11 | 0.00 | 1.46 |
August | 0.102547E+11 | 0.00 | 0.00 | 0.187547E+09 | 0.00 | 0.00 | 0.851099E+11 | 0.00 | 1.56 |
September | 0.559761E+10 | 0.00 | 0.00 | 0.143388E+09 | 0.00 | 0.00 | 0.821754E+11 | 0.00 | 0.90 |
October | 0.164854E+10 | 0.00 | 0.00 | 88745133.77 | 0.00 | 0.00 | 0.502542E+11 | 0.00 | 0.44 |
November | 0.634859E+10 | 0.00 | 0.00 | 65835870.41 | 0.00 | 0.00 | 0.467430E+11 | 0.00 | 0.37 |
December | 0.776907E+10 | 0.00 | 0.00 | 67999626.29 | 0.00 | 0.00 | 0.533581E+11 | 0.00 | 0.35 |
Annual Sum or Average | 0.101549E+12 | 0.137600E+09 | 0.00 | 0.131311E+10 | 11997895.17 | 0.00 | 0.686068E+12 | 0.00 | 0.79 |
Minimum of Months | 0.164854E+10 | 0.00 | 0.00 | 35677943.01 | 0.00 | 0.00 | 0.239463E+11 | 0.00 | 0.31 |
Maximum of Months | 0.204745E+11 | 0.132277E+09 | 0.00 | 0.187547E+09 | 11997895.17 | 0.00 | 0.851099E+11 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.373958E+12 | 0.00 | 0.00 | 14715.02 | 0.00 | 0.165751E+11 | 0.323479E+09 | 0.00 | 0.29 |
February | 0.291709E+12 | 0.00 | 0.00 | 33936629.51 | 0.00 | 0.466610E+10 | 0.297600E+11 | 0.00 | 0.30 |
March | 0.201718E+12 | 0.00 | 0.00 | 0.186103E+09 | 0.00 | 31217085.85 | 0.131374E+12 | 0.00 | 0.32 |
April | 0.833646E+11 | 0.00 | 0.00 | 0.467629E+09 | 0.00 | 0.00 | 0.280223E+12 | 0.00 | 0.37 |
May | 0.504508E+11 | 0.00 | 0.00 | 0.735356E+09 | 0.00 | 0.00 | 0.452215E+12 | 0.00 | 0.70 |
June | 0.379069E+11 | 1463731.21 | 0.00 | 0.806215E+09 | 0.00 | 0.00 | 0.366360E+12 | 0.00 | 0.85 |
July | 0.446991E+11 | 0.927921E+09 | 0.00 | 0.770437E+09 | 0.182176E+09 | 0.00 | 0.294410E+12 | 0.00 | 0.79 |
August | 0.282476E+11 | 0.00 | 0.00 | 0.833844E+09 | 0.00 | 0.00 | 0.405205E+12 | 0.00 | 0.75 |
September | 0.453573E+11 | 0.00 | 0.00 | 0.549091E+09 | 0.00 | 0.00 | 0.354003E+12 | 0.00 | 0.44 |
October | 0.136779E+12 | 0.00 | 0.00 | 0.232392E+09 | 0.00 | 35859799.71 | 0.164252E+12 | 0.00 | 0.32 |
November | 0.369294E+12 | 0.00 | 0.00 | 5134320.38 | 0.00 | 0.500439E+10 | 0.108428E+11 | 0.00 | 0.29 |
December | 0.458523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613187E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.212201E+13 | 0.929385E+09 | 0.00 | 0.462015E+10 | 0.182176E+09 | 0.324445E+11 | 0.248897E+13 | 0.00 | 0.48 |
Minimum of Months | 0.282476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.458523E+12 | 0.927921E+09 | 0.00 | 0.833844E+09 | 0.182176E+09 | 0.165751E+11 | 0.452215E+12 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160919E+11 | 0.00 | 0.00 | 0.26 |
February | 0.144927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111403E+11 | 0.00 | 0.00 | 0.28 |
March | 0.199871E+11 | 0.00 | 0.00 | 357897.84 | 0.00 | 0.415286E+10 | 0.507676E+09 | 0.00 | 0.30 |
April | 0.146988E+11 | 0.00 | 0.00 | 15189966.42 | 0.00 | 0.537565E+09 | 0.117735E+11 | 0.00 | 0.32 |
May | 0.804213E+10 | 0.00 | 0.00 | 52223084.82 | 0.00 | 0.00 | 0.348741E+11 | 0.00 | 0.62 |
June | 0.373303E+10 | 511559.41 | 0.00 | 74335550.50 | 0.00 | 0.00 | 0.350988E+11 | 0.00 | 0.84 |
July | 0.422601E+10 | 85769969.76 | 0.00 | 69858418.59 | 13147993.97 | 0.00 | 0.274349E+11 | 0.00 | 0.77 |
August | 0.420932E+10 | 0.00 | 0.00 | 65986138.80 | 0.00 | 0.00 | 0.333968E+11 | 0.00 | 0.69 |
September | 0.133622E+11 | 0.00 | 0.00 | 17738172.59 | 0.00 | 84431080.55 | 0.141364E+11 | 0.00 | 0.36 |
October | 0.168147E+11 | 0.00 | 0.00 | 1625473.35 | 0.00 | 0.244162E+10 | 0.155475E+10 | 0.00 | 0.28 |
November | 0.173846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139381E+11 | 0.00 | 0.00 | 0.27 |
December | 0.195676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180331E+11 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.151926E+12 | 86281529.17 | 0.00 | 0.297315E+09 | 13147993.97 | 0.664199E+11 | 0.158777E+12 | 0.00 | 0.44 |
Minimum of Months | 0.373303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.199871E+11 | 85769969.76 | 0.00 | 74335550.50 | 13147993.97 | 0.180331E+11 | 0.350988E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395644E+10 | 0.00 | 0.00 | 0.28 |
February | 0.219243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200112E+10 | 0.00 | 0.00 | 0.27 |
March | 0.321881E+10 | 0.00 | 0.00 | 499355.74 | 0.00 | 0.612744E+09 | 0.407000E+09 | 0.00 | 0.26 |
April | 0.202232E+10 | 0.00 | 0.00 | 5592372.75 | 0.00 | 13142500.48 | 0.397894E+10 | 0.00 | 0.45 |
May | 0.100042E+10 | 0.00 | 0.00 | 18308461.16 | 0.00 | 0.00 | 0.107285E+11 | 0.00 | 1.28 |
June | 0.105391E+10 | 960746.93 | 0.00 | 30154225.95 | 0.00 | 0.00 | 0.110364E+11 | 0.00 | 1.94 |
July | 0.149040E+10 | 22527329.21 | 0.00 | 30142297.56 | 856245.01 | 0.00 | 0.869427E+10 | 0.00 | 1.80 |
August | 0.169450E+10 | 0.00 | 0.00 | 21879271.92 | 0.00 | 0.00 | 0.102007E+11 | 0.00 | 1.63 |
September | 0.140772E+10 | 0.00 | 0.00 | 9464486.25 | 0.00 | 0.00 | 0.651087E+10 | 0.00 | 0.68 |
October | 0.273905E+10 | 0.00 | 0.00 | 1392945.92 | 0.00 | 0.101458E+09 | 0.109552E+10 | 0.00 | 0.27 |
November | 0.266589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217003E+10 | 0.00 | 0.00 | 0.26 |
December | 0.244411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327924E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.231016E+11 | 23488076.15 | 0.00 | 0.117433E+09 | 856245.01 | 0.121342E+11 | 0.526521E+11 | 0.00 | 0.79 |
Minimum of Months | 0.100042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.321881E+10 | 22527329.21 | 0.00 | 30154225.95 | 856245.01 | 0.395644E+10 | 0.110364E+11 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.606209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272343E+10 | 0.00 | 0.00 | 0.28 |
February | 0.149082E+10 | 0.00 | 0.00 | 158748.62 | 0.00 | 0.114544E+10 | 92334085.11 | 0.00 | 0.27 |
March | 0.148563E+10 | 0.00 | 0.00 | 4374344.82 | 0.00 | 0.351774E+09 | 0.207283E+10 | 0.00 | 0.35 |
April | 0.103779E+10 | 0.00 | 0.00 | 9609993.87 | 0.00 | 9757548.51 | 0.547587E+10 | 0.00 | 0.73 |
May | 0.447783E+09 | 0.00 | 0.00 | 27113231.57 | 0.00 | 0.00 | 0.135454E+11 | 0.00 | 2.28 |
June | 0.667807E+09 | 965567.60 | 0.00 | 26510046.96 | 0.00 | 0.00 | 0.108407E+11 | 0.00 | 2.74 |
July | 0.937915E+09 | 16117251.49 | 0.00 | 29091514.32 | 439047.41 | 0.00 | 0.844012E+10 | 0.00 | 2.57 |
August | 0.104222E+10 | 0.00 | 0.00 | 21426411.89 | 0.00 | 0.00 | 0.101380E+11 | 0.00 | 2.24 |
September | 0.720752E+09 | 0.00 | 0.00 | 11972798.61 | 0.00 | 0.00 | 0.679424E+10 | 0.00 | 0.97 |
October | 0.151285E+10 | 0.00 | 0.00 | 2311705.45 | 0.00 | 0.109539E+09 | 0.138853E+10 | 0.00 | 0.32 |
November | 0.116127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196218E+10 | 0.00 | 0.00 | 0.26 |
December | 0.452729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324699E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.115638E+11 | 17082819.09 | 0.00 | 0.132569E+09 | 439047.41 | 0.954911E+10 | 0.587881E+11 | 0.00 | 1.11 |
Minimum of Months | 0.447783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.151285E+10 | 16117251.49 | 0.00 | 29091514.32 | 439047.41 | 0.324699E+10 | 0.135454E+11 | 0.00 | 2.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109080E+10 | 0.00 | 0.00 | 225089.77 | 0.00 | 0.407726E+10 | 0.120308E+09 | 0.00 | 0.29 |
February | 0.201643E+10 | 0.00 | 0.00 | 2344577.80 | 0.00 | 0.169451E+10 | 0.147671E+10 | 0.00 | 0.33 |
March | 0.205769E+10 | 0.00 | 0.00 | 12129671.71 | 0.00 | 0.527966E+09 | 0.685668E+10 | 0.00 | 0.52 |
April | 0.144738E+10 | 0.00 | 0.00 | 24171967.73 | 0.00 | 19707258.09 | 0.140624E+11 | 0.00 | 1.22 |
May | 0.908697E+09 | 0.00 | 0.00 | 35044253.16 | 0.00 | 0.00 | 0.168287E+11 | 0.00 | 2.11 |
June | 0.118916E+10 | 1917330.23 | 0.00 | 35200630.89 | 0.00 | 0.00 | 0.127309E+11 | 0.00 | 2.46 |
July | 0.160973E+10 | 37331796.85 | 0.00 | 39417333.09 | 188210.22 | 0.00 | 0.964995E+10 | 0.00 | 2.30 |
August | 0.160880E+10 | 0.00 | 0.00 | 39019252.37 | 0.00 | 0.00 | 0.147964E+11 | 0.00 | 2.43 |
September | 0.135419E+10 | 0.00 | 0.00 | 19106155.10 | 0.00 | 0.00 | 0.120055E+11 | 0.00 | 1.21 |
October | 0.222063E+10 | 0.00 | 0.00 | 5743598.03 | 0.00 | 0.186066E+09 | 0.371546E+10 | 0.00 | 0.41 |
November | 0.220192E+10 | 0.00 | 0.00 | 832398.97 | 0.00 | 0.248795E+10 | 0.387049E+09 | 0.00 | 0.28 |
December | 0.105519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472777E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.187606E+11 | 39249127.08 | 0.00 | 0.213235E+09 | 188210.22 | 0.137212E+11 | 0.926301E+11 | 0.00 | 1.16 |
Minimum of Months | 0.908697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.222063E+10 | 37331796.85 | 0.00 | 39417333.09 | 188210.22 | 0.472777E+10 | 0.168287E+11 | 0.00 | 2.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157328E+10 | 0.00 | 0.00 | 0.28 |
February | 0.214438E+10 | 0.00 | 0.00 | 481879.37 | 0.00 | 0.249449E+09 | 0.398974E+09 | 0.00 | 0.28 |
March | 0.107508E+10 | 0.00 | 0.00 | 5769492.32 | 0.00 | 23724236.49 | 0.366394E+10 | 0.00 | 0.43 |
April | 0.259717E+09 | 0.00 | 0.00 | 21170339.38 | 0.00 | 0.00 | 0.113107E+11 | 0.00 | 1.39 |
May | 0.465672E+09 | 0.00 | 0.00 | 20974483.95 | 0.00 | 0.00 | 0.974189E+10 | 0.00 | 1.85 |
June | 0.484289E+09 | 705049.65 | 0.00 | 27347283.41 | 0.00 | 0.00 | 0.910122E+10 | 0.00 | 2.66 |
July | 0.430213E+09 | 29329539.97 | 0.00 | 28939412.18 | 54265.91 | 0.00 | 0.790389E+10 | 0.00 | 2.52 |
August | 0.346330E+09 | 0.00 | 0.00 | 29007987.48 | 0.00 | 0.00 | 0.112570E+11 | 0.00 | 2.61 |
September | 0.761785E+09 | 0.00 | 0.00 | 8858209.38 | 0.00 | 0.00 | 0.586657E+10 | 0.00 | 0.93 |
October | 0.984012E+09 | 0.00 | 0.00 | 3669586.05 | 0.00 | 0.00 | 0.253699E+10 | 0.00 | 0.38 |
November | 0.289196E+10 | 0.00 | 0.00 | 361804.30 | 0.00 | 11615935.63 | 0.250156E+09 | 0.00 | 0.27 |
December | 0.357166E+10 | 0.00 | 0.00 | 125302.71 | 0.00 | 443622.82 | 0.108398E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.151319E+11 | 30034589.63 | 0.00 | 0.146706E+09 | 54265.91 | 0.185851E+10 | 0.621397E+11 | 0.00 | 1.16 |
Minimum of Months | 0.259717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.357166E+10 | 29329539.97 | 0.00 | 29007987.48 | 54265.91 | 0.157328E+10 | 0.113107E+11 | 0.00 | 2.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622543E+11 | 0.00 | 0.00 | 0.35 |
February | 0.347371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453464E+11 | 0.00 | 0.00 | 0.32 |
March | 0.157068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263474E+11 | 0.00 | 0.00 | 0.31 |
April | 0.243926E+11 | 0.00 | 0.00 | 11820003.93 | 0.00 | 0.400511E+10 | 0.888609E+10 | 0.00 | 0.31 |
May | 0.103681E+11 | 0.00 | 0.00 | 87673597.01 | 0.00 | 0.00 | 0.557209E+11 | 0.00 | 0.76 |
June | 0.387592E+10 | 319566.46 | 0.00 | 0.183316E+09 | 0.00 | 0.00 | 0.725421E+11 | 0.00 | 1.30 |
July | 0.533105E+10 | 0.187213E+09 | 0.00 | 0.153443E+09 | 22890991.44 | 0.00 | 0.519328E+11 | 0.00 | 1.12 |
August | 0.832652E+10 | 0.00 | 0.00 | 90667141.15 | 0.00 | 0.00 | 0.455388E+11 | 0.00 | 0.81 |
September | 0.254157E+11 | 0.00 | 0.00 | 14617812.92 | 0.00 | 0.807597E+09 | 0.114037E+11 | 0.00 | 0.34 |
October | 0.190845E+11 | 0.00 | 0.00 | 20681.33 | 0.00 | 0.145886E+11 | 0.122181E+09 | 0.00 | 0.28 |
November | 0.950660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561284E+11 | 0.00 | 0.00 | 0.32 |
December | 0.651338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715777E+11 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.118117E+12 | 0.187533E+09 | 0.00 | 0.541558E+09 | 22890991.44 | 0.281056E+12 | 0.246147E+12 | 0.00 | 0.55 |
Minimum of Months | 0.539935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.254157E+11 | 0.187213E+09 | 0.00 | 0.183316E+09 | 22890991.44 | 0.715777E+11 | 0.725421E+11 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.764174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368510E+11 | 0.00 | 0.00 | 0.31 |
February | 0.370822E+10 | 0.00 | 0.00 | 4107.83 | 0.00 | 0.232656E+11 | 4347424.63 | 0.00 | 0.27 |
March | 0.101625E+11 | 0.00 | 0.00 | 19482143.86 | 0.00 | 0.962694E+10 | 0.875942E+10 | 0.00 | 0.32 |
April | 0.837940E+10 | 0.00 | 0.00 | 69975641.50 | 0.00 | 0.118748E+10 | 0.360552E+11 | 0.00 | 0.56 |
May | 0.379149E+10 | 0.00 | 0.00 | 0.203890E+09 | 0.00 | 0.00 | 0.101841E+12 | 0.00 | 1.78 |
June | 0.202192E+10 | 308932.77 | 0.00 | 0.201335E+09 | 0.00 | 0.00 | 0.867688E+11 | 0.00 | 2.19 |
July | 0.227040E+10 | 0.164491E+09 | 0.00 | 0.223601E+09 | 11249680.25 | 0.00 | 0.671432E+11 | 0.00 | 2.06 |
August | 0.306125E+10 | 0.00 | 0.00 | 0.140218E+09 | 0.00 | 0.00 | 0.682761E+11 | 0.00 | 1.50 |
September | 0.898904E+10 | 0.00 | 0.00 | 52469228.16 | 0.00 | 0.396249E+09 | 0.258594E+11 | 0.00 | 0.48 |
October | 0.979770E+10 | 0.00 | 0.00 | 6580456.15 | 0.00 | 0.646326E+10 | 0.360172E+10 | 0.00 | 0.25 |
November | 0.103304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324079E+11 | 0.00 | 0.00 | 0.28 |
December | 0.672858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438173E+11 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.546520E+11 | 0.164800E+09 | 0.00 | 0.917557E+09 | 11249680.25 | 0.154016E+12 | 0.398309E+12 | 0.00 | 0.87 |
Minimum of Months | 0.672858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.101625E+11 | 0.164491E+09 | 0.00 | 0.223601E+09 | 11249680.25 | 0.438173E+11 | 0.101841E+12 | 0.00 | 2.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426592E+10 | 0.00 | 0.00 | 322529.76 | 0.00 | 0.552235E+11 | 0.172220E+09 | 0.00 | 0.33 |
February | 0.136310E+11 | 0.00 | 0.00 | 15682795.52 | 0.00 | 0.277864E+11 | 0.977901E+10 | 0.00 | 0.37 |
March | 0.165817E+11 | 0.00 | 0.00 | 0.113086E+09 | 0.00 | 0.116249E+11 | 0.586143E+11 | 0.00 | 0.64 |
April | 0.111115E+11 | 0.00 | 0.00 | 0.234758E+09 | 0.00 | 0.120264E+10 | 0.116564E+12 | 0.00 | 1.07 |
May | 0.939613E+10 | 0.00 | 0.00 | 0.291397E+09 | 0.00 | 0.00 | 0.136296E+12 | 0.00 | 1.82 |
June | 0.404004E+10 | 833165.46 | 0.00 | 0.280507E+09 | 0.00 | 0.00 | 0.102779E+12 | 0.00 | 2.04 |
July | 0.488328E+10 | 0.449088E+09 | 0.00 | 0.306645E+09 | 7414795.58 | 0.00 | 0.732424E+11 | 0.00 | 1.85 |
August | 0.592040E+10 | 0.00 | 0.00 | 0.291588E+09 | 0.00 | 0.00 | 0.103164E+12 | 0.00 | 1.83 |
September | 0.133348E+11 | 0.00 | 0.00 | 0.141271E+09 | 0.00 | 0.319186E+09 | 0.764297E+11 | 0.00 | 0.85 |
October | 0.181242E+11 | 0.00 | 0.00 | 42804555.70 | 0.00 | 0.722756E+10 | 0.260415E+11 | 0.00 | 0.41 |
November | 0.932419E+10 | 0.00 | 0.00 | 3093624.08 | 0.00 | 0.447325E+11 | 0.147127E+10 | 0.00 | 0.32 |
December | 0.114200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695782E+11 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.111755E+12 | 0.449921E+09 | 0.00 | 0.172116E+10 | 7414795.58 | 0.217695E+12 | 0.704553E+12 | 0.00 | 0.99 |
Minimum of Months | 0.114200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.181242E+11 | 0.449088E+09 | 0.00 | 0.306645E+09 | 7414795.58 | 0.695782E+11 | 0.136296E+12 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.555229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381555E+11 | 0.00 | 0.00 | 0.33 |
February | 0.474868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245261E+11 | 0.00 | 0.00 | 0.31 |
March | 0.130649E+11 | 0.00 | 0.00 | 6160681.33 | 0.00 | 0.111998E+11 | 0.416138E+10 | 0.00 | 0.33 |
April | 0.976042E+10 | 0.00 | 0.00 | 75691103.33 | 0.00 | 0.705480E+09 | 0.436251E+11 | 0.00 | 0.72 |
May | 0.527001E+10 | 0.00 | 0.00 | 0.147174E+09 | 0.00 | 0.00 | 0.645914E+11 | 0.00 | 1.36 |
June | 0.207546E+10 | 230043.84 | 0.00 | 0.185184E+09 | 0.00 | 0.00 | 0.605896E+11 | 0.00 | 1.93 |
July | 0.271202E+10 | 0.291379E+09 | 0.00 | 0.151200E+09 | 2869295.29 | 0.00 | 0.415332E+11 | 0.00 | 1.59 |
August | 0.341642E+10 | 0.00 | 0.00 | 0.128497E+09 | 0.00 | 0.00 | 0.479301E+11 | 0.00 | 1.36 |
September | 0.120476E+11 | 0.00 | 0.00 | 33528887.20 | 0.00 | 0.197283E+09 | 0.223177E+11 | 0.00 | 0.52 |
October | 0.132769E+11 | 0.00 | 0.00 | 2258007.18 | 0.00 | 0.701739E+10 | 0.171780E+10 | 0.00 | 0.29 |
November | 0.239656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320960E+11 | 0.00 | 0.00 | 0.31 |
December | 0.939217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418270E+11 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.702635E+11 | 0.291609E+09 | 0.00 | 0.729693E+09 | 2869295.29 | 0.155725E+12 | 0.286466E+12 | 0.00 | 0.78 |
Minimum of Months | 0.555229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.132769E+11 | 0.291379E+09 | 0.00 | 0.185184E+09 | 2869295.29 | 0.418270E+11 | 0.645914E+11 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29150236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707843E+10 | 0.00 | 0.00 | 0.43 |
February | 56709269.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515535E+10 | 0.00 | 0.00 | 0.39 |
March | 0.493832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369266E+10 | 0.00 | 0.00 | 0.37 |
April | 0.230713E+10 | 0.00 | 0.00 | 346102.47 | 0.00 | 0.889343E+09 | 0.331951E+09 | 0.00 | 0.34 |
May | 0.152891E+10 | 0.00 | 0.00 | 6251890.90 | 0.00 | 13362824.33 | 0.420695E+10 | 0.00 | 0.68 |
June | 0.446706E+09 | 145433.53 | 0.00 | 16655141.88 | 0.00 | 0.00 | 0.686689E+10 | 0.00 | 1.27 |
July | 0.646615E+09 | 16848429.30 | 0.00 | 13898298.16 | 1827286.14 | 0.00 | 0.478608E+10 | 0.00 | 1.11 |
August | 0.123726E+10 | 0.00 | 0.00 | 7394517.75 | 0.00 | 28195500.57 | 0.365238E+10 | 0.00 | 0.77 |
September | 0.260997E+10 | 0.00 | 0.00 | 251989.01 | 0.00 | 0.559026E+09 | 0.290755E+09 | 0.00 | 0.36 |
October | 0.806035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231780E+10 | 0.00 | 0.00 | 0.33 |
November | 22561019.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657013E+10 | 0.00 | 0.00 | 0.41 |
December | 35339310.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856571E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.102202E+11 | 16993862.83 | 0.00 | 44797940.18 | 1827286.14 | 0.348700E+11 | 0.201350E+11 | 0.00 | 0.58 |
Minimum of Months | 22561019.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.260997E+10 | 16848429.30 | 0.00 | 16655141.88 | 1827286.14 | 0.856571E+10 | 0.686689E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17532313.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454889E+10 | 0.00 | 0.00 | 0.42 |
February | 0.120700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291304E+10 | 0.00 | 0.00 | 0.35 |
March | 0.859712E+09 | 0.00 | 0.00 | 728519.37 | 0.00 | 0.138216E+10 | 0.286145E+09 | 0.00 | 0.35 |
April | 0.733673E+09 | 0.00 | 0.00 | 4967548.80 | 0.00 | 0.291851E+09 | 0.277296E+10 | 0.00 | 0.55 |
May | 0.381752E+09 | 0.00 | 0.00 | 19112929.11 | 0.00 | 252215.51 | 0.952847E+10 | 0.00 | 1.71 |
June | 0.174017E+09 | 80313.27 | 0.00 | 19971947.25 | 0.00 | 0.00 | 0.885922E+10 | 0.00 | 2.24 |
July | 0.208141E+09 | 14466364.35 | 0.00 | 21913310.80 | 730407.40 | 0.00 | 0.681480E+10 | 0.00 | 2.13 |
August | 0.310485E+09 | 0.00 | 0.00 | 13222559.87 | 0.00 | 10354829.60 | 0.657951E+10 | 0.00 | 1.51 |
September | 0.106661E+10 | 0.00 | 0.00 | 3096053.99 | 0.00 | 0.164100E+09 | 0.165380E+10 | 0.00 | 0.45 |
October | 0.656015E+09 | 0.00 | 0.00 | 155627.75 | 0.00 | 0.113796E+10 | 86092826.99 | 0.00 | 0.31 |
November | 13933692.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419289E+10 | 0.00 | 0.00 | 0.40 |
December | 20776798.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564817E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.456335E+10 | 14546677.62 | 0.00 | 83168496.94 | 730407.40 | 0.202897E+11 | 0.365810E+11 | 0.00 | 0.91 |
Minimum of Months | 13933692.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.106661E+10 | 14466364.35 | 0.00 | 21913310.80 | 730407.40 | 0.564817E+10 | 0.952847E+10 | 0.00 | 2.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606354E+10 | 0.00 | 0.00 | 0.38 |
February | 0.636296E+09 | 0.00 | 0.00 | 644039.20 | 0.00 | 0.342044E+10 | 0.358909E+09 | 0.00 | 0.35 |
March | 0.107504E+10 | 0.00 | 0.00 | 6911632.04 | 0.00 | 0.171149E+10 | 0.354390E+10 | 0.00 | 0.57 |
April | 0.817528E+09 | 0.00 | 0.00 | 18371858.02 | 0.00 | 0.369979E+09 | 0.102313E+11 | 0.00 | 1.01 |
May | 0.904334E+09 | 0.00 | 0.00 | 27207444.84 | 0.00 | 12123963.63 | 0.128620E+11 | 0.00 | 1.70 |
June | 0.468878E+09 | 144883.78 | 0.00 | 27242818.19 | 0.00 | 0.00 | 0.103067E+11 | 0.00 | 2.03 |
July | 0.514330E+09 | 38233058.15 | 0.00 | 29196212.60 | 524172.09 | 0.00 | 0.736481E+10 | 0.00 | 1.87 |
August | 0.668436E+09 | 0.00 | 0.00 | 27566234.78 | 0.00 | 10739831.44 | 0.990634E+10 | 0.00 | 1.79 |
September | 0.136920E+10 | 0.00 | 0.00 | 10213431.99 | 0.00 | 0.185184E+09 | 0.580453E+10 | 0.00 | 0.76 |
October | 0.102036E+10 | 0.00 | 0.00 | 2452832.66 | 0.00 | 0.134880E+10 | 0.145623E+10 | 0.00 | 0.39 |
November | 0.291922E+09 | 0.00 | 0.00 | 131994.68 | 0.00 | 0.527528E+10 | 55113728.47 | 0.00 | 0.35 |
December | 32177692.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799528E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.800153E+10 | 38377941.93 | 0.00 | 0.149938E+09 | 524172.09 | 0.263928E+11 | 0.618898E+11 | 0.00 | 0.97 |
Minimum of Months | 32177692.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.136920E+10 | 38233058.15 | 0.00 | 29196212.60 | 524172.09 | 0.799528E+10 | 0.128620E+11 | 0.00 | 2.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17996051.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428385E+10 | 0.00 | 0.00 | 0.39 |
February | 0.148517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271404E+10 | 0.00 | 0.00 | 0.33 |
March | 0.690906E+09 | 0.00 | 0.00 | 317452.50 | 0.00 | 0.153249E+10 | 0.210482E+09 | 0.00 | 0.33 |
April | 0.807247E+09 | 0.00 | 0.00 | 5700641.05 | 0.00 | 0.239003E+09 | 0.358143E+10 | 0.00 | 0.66 |
May | 0.571703E+09 | 0.00 | 0.00 | 13415923.71 | 0.00 | 3135909.70 | 0.581474E+10 | 0.00 | 1.26 |
June | 0.211111E+09 | 222173.52 | 0.00 | 17846939.44 | 0.00 | 0.00 | 0.599957E+10 | 0.00 | 1.91 |
July | 0.275138E+09 | 26219919.74 | 0.00 | 14846555.89 | 103382.97 | 0.00 | 0.402518E+10 | 0.00 | 1.61 |
August | 0.444535E+09 | 0.00 | 0.00 | 11744672.01 | 0.00 | 1468952.11 | 0.429745E+10 | 0.00 | 1.31 |
September | 0.120757E+10 | 0.00 | 0.00 | 2043161.16 | 0.00 | 0.134457E+09 | 0.141216E+10 | 0.00 | 0.45 |
October | 0.671825E+09 | 0.00 | 0.00 | 46486.42 | 0.00 | 0.106050E+10 | 45245882.90 | 0.00 | 0.29 |
November | 27200293.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356895E+10 | 0.00 | 0.00 | 0.34 |
December | 23843468.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474803E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.509759E+10 | 26442093.26 | 0.00 | 65961832.18 | 103382.97 | 0.182859E+11 | 0.253863E+11 | 0.00 | 0.78 |
Minimum of Months | 17996051.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.120757E+10 | 26219919.74 | 0.00 | 17846939.44 | 103382.97 | 0.474803E+10 | 0.599957E+10 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13678059.51 | 0.00 | 0.00 | 2510345.76 | 0.00 | 0.00 | 0.117406E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7933427.04 | 0.00 | 0.00 | 0.973083E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 16444275.17 | 0.00 | 0.00 | 0.102312E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 19852240.35 | 0.00 | 0.00 | 0.634884E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4422940.11 | 0.00 | 0.00 | 0.454768E+09 | 0.00 | 0.30 |
June | 0.00 | 1684491.54 | 0.00 | 8743437.55 | 0.00 | 0.00 | 0.248031E+09 | 0.00 | 0.30 |
July | 0.00 | 2645339.15 | 0.00 | 11800909.04 | 0.00 | 0.00 | 0.120510E+09 | 0.00 | 0.28 |
August | 0.00 | 16981.63 | 0.00 | 19277356.43 | 0.00 | 0.00 | 0.255502E+09 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 4196999.09 | 0.00 | 0.00 | 0.539205E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8753475.84 | 0.00 | 0.00 | 0.803836E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 15920934.49 | 0.00 | 0.00 | 0.112405E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 25158216.42 | 0.00 | 0.00 | 0.120244E+10 | 0.00 | 0.28 |
Annual Sum or Average | 13678059.51 | 4346812.31 | 0.00 | 0.145015E+09 | 0.00 | 0.00 | 0.855350E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2510345.76 | 0.00 | 0.00 | 0.120510E+09 | 0.00 | 0.28 |
Maximum of Months | 13678059.51 | 2645339.15 | 0.00 | 25158216.42 | 0.00 | 0.00 | 0.120244E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.975602E+10 | 0.00 | 0.00 | 1311683.54 | 0.00 | 0.00 | 0.180570E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 54125025.68 | 0.00 | 0.00 | 0.975464E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.136306E+09 | 0.00 | 0.00 | 0.102595E+11 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.181782E+09 | 0.00 | 0.00 | 0.636583E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 37878488.09 | 0.00 | 0.00 | 0.455365E+10 | 0.00 | 0.30 |
June | 0.00 | 16401861.92 | 0.00 | 81175311.16 | 0.00 | 0.00 | 0.249004E+10 | 0.00 | 0.30 |
July | 0.00 | 26046617.40 | 0.00 | 0.111005E+09 | 0.00 | 0.00 | 0.121700E+10 | 0.00 | 0.28 |
August | 0.00 | 163430.60 | 0.00 | 0.181049E+09 | 0.00 | 0.00 | 0.256836E+10 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 31181889.39 | 0.00 | 0.00 | 0.541001E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 66568732.02 | 0.00 | 0.00 | 0.805886E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.121874E+09 | 0.00 | 0.00 | 0.112773E+11 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.202976E+09 | 0.00 | 0.00 | 0.120721E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.975602E+10 | 42611909.93 | 0.00 | 0.120723E+10 | 0.00 | 0.00 | 0.758330E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1311683.54 | 0.00 | 0.00 | 0.121700E+10 | 0.00 | 0.28 |
Maximum of Months | 0.975602E+10 | 26046617.40 | 0.00 | 0.202976E+09 | 0.00 | 0.00 | 0.120721E+11 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
February | 8017012.94 | 0.00 | 0.00 | 3889304.15 | 0.00 | 0.00 | 0.968646E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11582934.91 | 0.00 | 0.00 | 0.102799E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16985282.94 | 0.00 | 0.00 | 0.637771E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3497438.92 | 0.00 | 0.00 | 0.455673E+09 | 0.00 | 0.30 |
June | 0.00 | 1645959.03 | 0.00 | 8091180.08 | 0.00 | 0.00 | 0.249116E+09 | 0.00 | 0.30 |
July | 0.00 | 2605712.67 | 0.00 | 11065977.89 | 0.00 | 0.00 | 0.121831E+09 | 0.00 | 0.28 |
August | 0.00 | 16275.78 | 0.00 | 17899192.99 | 0.00 | 0.00 | 0.257191E+09 | 0.00 | 0.30 |
September | 50628854.62 | 0.00 | 0.00 | 2055771.64 | 0.00 | 0.00 | 0.491342E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 4839776.95 | 0.00 | 0.00 | 0.807721E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10328336.58 | 0.00 | 0.00 | 0.112960E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18399793.71 | 0.00 | 0.00 | 0.120913E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.117724E+10 | 4267947.48 | 0.00 | 0.108635E+09 | 0.00 | 0.00 | 0.735602E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.111859E+10 | 2605712.67 | 0.00 | 18399793.71 | 0.00 | 0.00 | 0.120913E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.840882E+09 | 0.00 | 0.00 | 0.457176E+12 | 0.00 | 4.86 |
February | 0.00 | 0.00 | 0.00 | 0.137464E+10 | 0.00 | 0.00 | 0.711468E+12 | 0.00 | 8.83 |
March | 0.00 | 0.00 | 0.00 | 0.201449E+10 | 0.00 | 0.00 | 0.108755E+13 | 0.00 | 14.23 |
April | 0.00 | 0.00 | 0.00 | 0.251574E+10 | 0.00 | 0.00 | 0.129038E+13 | 0.00 | 27.15 |
May | 0.00 | 0.00 | 0.00 | 0.674154E+09 | 0.00 | 0.00 | 0.533103E+12 | 0.00 | 14.60 |
June | 0.00 | 88553776.89 | 0.00 | 0.136620E+10 | 0.00 | 0.00 | 0.640280E+12 | 0.00 | 34.24 |
July | 0.00 | 0.576047E+09 | 0.00 | 0.225519E+10 | 0.00 | 0.00 | 0.667673E+12 | 0.00 | 42.43 |
August | 0.00 | 0.00 | 0.00 | 0.274259E+10 | 0.00 | 0.00 | 0.909586E+12 | 0.00 | 44.24 |
September | 0.00 | 0.00 | 0.00 | 0.574322E+09 | 0.00 | 0.00 | 0.438437E+12 | 0.00 | 11.37 |
October | 0.00 | 0.00 | 0.00 | 0.115925E+10 | 0.00 | 0.00 | 0.804480E+12 | 0.00 | 12.95 |
November | 0.00 | 0.00 | 0.00 | 0.232388E+10 | 0.00 | 0.00 | 0.105164E+13 | 0.00 | 11.66 |
December | 0.00 | 0.00 | 0.00 | 0.354577E+10 | 0.00 | 0.00 | 0.133029E+13 | 0.00 | 14.69 |
Annual Sum or Average | 0.00 | 0.664601E+09 | 0.00 | 0.213871E+11 | 0.00 | 0.00 | 0.992206E+13 | 0.00 | 20.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.574322E+09 | 0.00 | 0.00 | 0.438437E+12 | 0.00 | 4.86 |
Maximum of Months | 0.00 | 0.576047E+09 | 0.00 | 0.354577E+10 | 0.00 | 0.00 | 0.133029E+13 | 0.00 | 44.24 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.412308E+11 | 0.114469E+11 | 0.00 | 0.236465E+13 | 0.246866E+12 |
February | 0.529489E+11 | 0.945847E+10 | 0.00 | 0.256261E+13 | 0.228385E+12 |
March | 0.342425E+12 | 0.145258E+11 | 0.00 | 0.336347E+13 | 0.274079E+12 |
April | 0.628702E+12 | 0.159342E+11 | 0.00 | 0.345097E+13 | 0.386173E+12 |
May | 0.786273E+12 | 0.951864E+10 | 0.00 | 0.297567E+13 | 0.258340E+12 |
June | 0.815490E+12 | 0.530821E+10 | 0.00 | 0.265857E+13 | 0.869178E+12 |
July | 0.740349E+12 | 0.427235E+10 | 0.00 | 0.274114E+13 | 0.136712E+13 |
August | 0.553583E+12 | 0.501723E+10 | 0.00 | 0.311094E+13 | 0.114115E+13 |
September | 0.255361E+12 | 0.592757E+10 | 0.00 | 0.270542E+13 | 0.146813E+12 |
October | 0.103533E+12 | 0.127065E+11 | 0.00 | 0.299702E+13 | 0.191145E+12 |
November | -0.124893E+11 | 0.448043E+10 | 0.00 | 0.314476E+13 | 0.348107E+12 |
December | -0.588318E+11 | 0.833191E+10 | 0.00 | 0.336908E+13 | 0.472467E+12 |